Lennox International Inc Water Dispenser Gas Fired Hot Water Boiler User Manual

INSTALLATION  
INSTRUCTIONS  
PRODUCT LITERATURE  
Lennox Industries Inc.  
Dallas, Texas  
GWB9-050IH-2  
GWB9-075IH-2  
GWB9-100IH-2  
GAS-FIRED, DIRECT VENT,  
CONDENSING, HOT WATER BOILER  
RETAIN THESE INSTRUCTIONS FOR  
FUTURE REFERENCE  
These instructions must be afxed on or  
adjacent to the boiler.  
!
WARNING  
Improper installation, adjustment,  
alteration, service, or maintenance  
could result in death or serious injury.  
Refer to this manual for assistance. For  
additional information consult a qualied  
installer, service agency, or the gas  
supplier.  
GAS-FIRED HOT WATER BOILERS  
These low pressure gas red hot water boilers  
are design certied by CSA (Canadian Standards  
Association) for use with natural and propane  
gases (100 MBH model is certied for natural gas  
only). They are constructed and hydrostatically  
tested for a maximum working pressure of 50  
psi (pounds per square inch) in accordance  
with A.S.M.E. (American Society of Mechanical  
Engineers) Boiler and Pressure Vessel Code  
Section IV Standards for Heating Boilers.  
This boiler cannot be used with all types  
of chimneys. Read these instructions  
carefully before installing.  
P/N# 240009449, Rev. A [07/2012]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INTRODUCTION  
Dimensions....................................................................................................................2  
Introduction...................................................................................................................3  
Important Safety Information...........................................................................................4  
Boiler Ratings & Capacities ..............................................................................................5  
Boilers For Use At High Altitude........................................................................................5  
Before Installing The Boiler..............................................................................................8  
Boiler Installation ...........................................................................................................9  
Near Boiler Piping......................................................................................................... 11  
Combustion Air And Vent Pipe ........................................................................................ 22  
Gas Supply Piping......................................................................................................... 28  
Electrical Wiring ........................................................................................................... 30  
Controls And Accessories............................................................................................... 35  
Start Up......................................................................................................................37  
Operating Instructions................................................................................................... 38  
S9381a Integrated Boiler Control Operation And Adjustments............................................. 39  
Maintenance And Cleaning............................................................................................. 45  
Troubleshooting............................................................................................................ 47  
Differential Air Pressure Switch Check ............................................................................. 49  
Appendix A - Water Quality, Water Treatment And Freeze Protection.................................... 50  
Installation And Check-Out Certicate ............................................................................. 54  
Introduction  
• This appliance is a gas-red direct vent hot water boiler  
• Induced draft fan draws in outside combustion air,  
with cast aluminum boiler sections.  
takes cooler ue gases from boiler unit and provides  
positive removal of ue gases from the building  
through readily available PVC and CPVC pipes.  
• The heating system water absorbs large amounts of  
heat from the cast aluminum heat exchanger, cooling  
ue gases and causing condensation.  
• These low pressure gas-red hot water boilers are  
design certied by CSA International for use with  
natural gas and propane gases (90-100 model is  
certied for natural gas only).  
• Sealed combustion, premix gas burner, and low ame  
temperature means reduced CO and NOx emissions,  
which contribute to cleaner and healthier environment.  
• This appliance takes its combustion air directly from  
outdoors (sealed combustion) and does not compete  
with building occupants for fresh air.  
• Boilers are constructed and hydrostatically tested  
for maximum working pressure of 50 psig (pounds  
per square inch gage) in accordance with A.S.M.E.  
(American Society of Mechanical Engineers) Boiler and  
Pressure Vessel Code Section IV Standards for heating  
boilers.  
• Sealed combustion (also known as “direct vent”)  
is safest and best way to obtain plenty of clean  
combustion air.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
IMPORTANT SAFETY INFORMATION  
General  
Installation shall conform to requirements of author-  
ity having jurisdiction or in absence of such require-  
ments:  
Boiler installation shall be completed by qualied agency.  
See glossary for additional information.  
United States  
WARNING  
!
• National Fuel Gas Code, ANSI Z223.1/NFPA 54  
.
Fire, explosion, asphyxiation and electrical shock  
hazard. Improper installation could result in death  
or serious injury. Read this manual and understand  
all requirements before beginning installation.  
• National Electrical Code, NFPA 70.  
• Canada  
• Natural Gas and Propane Installation Code, CAN/CSA  
B149.1.  
• Canadian Electrical Code, Part I, Safety Standard for  
Electrical Installations, CSA C22.1  
Keep this manual near boiler  
Retain for future reference  
Become faamiliar wiith symbols identifying  
potential hazards.  
Where required by authority having jurisdiction,  
installation shall conform to Standard for Controls  
and Safety Devices for Automatically Fired Boilers,  
ANSI/ASME CSD-1.  
This iss the safetyy aalleerrtt ssyymmbbooll.. SSyymmbbooll aalleerrttss yyoouu ttoo  
potential personal injury hazzarrddss.. OObbeeyy all safety messsaaggeess  
followwiinngg tthhiiss ssyymmbbooll ttoo aavooiidd ppossiblle injuury or death.  
Additional manual reset low water cutoff and/or manual  
reset high limit may be required.  
Requirements for Commonwealth of  
Massachusetts:  
!
DANGER  
Boiler installation must conform to Commonwealth of  
Massachusetts code 248 CMR which includes but is not  
limited to:  
Indicates a hazardous situation which, if not avoided,  
WILL result in death or serious injury  
• Installation by licensed plumber or gas tter.  
!
WARNING  
Indicates a hazardous situation which, if not avoided,  
could result in death or serious injury.  
Installers - Follow local regulations with respect to  
installation of CO (Carbon Monoxide) Detectors. Follow  
maintenance recommendations“Maintenance And Cleaning”  
on page 45.  
!
CAUTION  
Indicates a hazardous situation which, if not avoided,  
could result in minor or moderate injury.  
NOTICE  
Used to address practices not related to personal  
injury.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
BOILER RATINGS & CAPACITIES  
Table 1 - SEA LEVEL RATINGS – NATURAL AND PROPANE GASES  
Input  
++ Heating Capacity  
*(MBH)  
Net AHRI Rating  
*(MBH)  
Shipping  
Weight (lbs.)  
Model  
Flue Diameter  
*(MBH)  
90-50  
90-75  
50  
75  
45  
68  
90  
39  
59  
78  
220  
220  
220  
2” CPVC & PVC  
2” CPVC & PVC  
2” CPVC & PVC  
90-100**  
100  
* 1 MBH = 1,000 Btuh  
Btuh = British Thermal Units Per Hour  
** 90-100 model is certied for natural gas only.  
++ AFUE (Annual Fuel Utilization Efciency) and Heating Capacity is based on the D.O.E. (Department of Energy) test  
procedure.  
Heating Capacity indicates the amount of heat available after subtracting losses up the stack. Most of this heat is available  
to heat water. A small portion is heat from jacket and surfaces of the boiler, and it is assumed that this heat stays in the  
structure.  
Net AHRI rating represents portion of remaining heat that can be applied to heat radiation or terminal units (i.e. nned  
tube baseboard, cast iron radiators, radiant oor, etc.). The difference between Heating Capacity and Net AHRI Rating,  
called piping and pickup allowance, establishes reserve for heating volume of water in system and offsetting heat losses  
from piping.  
Net AHRI ratings shown are based on piping and pickup factor of 1.15 in accordance with AHRI Standard as published  
by Hydronics Institute. Net AHRI rating of boiler selected should be greater than or equal to the calculated peak heating  
load (heat loss) for building or area(s) served by boiler and associated hot water heating systems. Consult manufacturer  
before selecting a boiler for installations having unusual piping and pickup requirements.  
Boilers are factory equipped for operation at altitudes ranging from 0-5,000 feet above sea level (4,500 feet in Canada).  
Boilers for use at high altitude  
Canada - Contact Provincial authority having jurisdiction for installations above 4,500 feet (1,350m) above sea level.  
United States - See “Boilers For Use At High Altitude” on page 6.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
BOILERS FOR USE AT HIGH ALTITUDE - UNITED STATES INSTALLATIONS  
• Boilers (with exception of 90-75 propane (LP) product)  
are factory equipped for operation at altitudes ranging  
from 0-10,000 feet above sea level.  
• Instructions on how to adjust gas manifold pressure  
settings see Figure 27 and Figure 28, Page 44  
.
Note 90-75 propane (LP) applications for 5,000 - 10,000  
feet above sea level require orice change as well as gas  
manifold pressure adjustment based upon caloric (Btu)  
value of supply gas.  
• No changes to factory settings are required for installa-  
tions from 0-5,000 feet above sea level.  
• For altitudes from 5,000-10,000 feet above sea level  
gas manifold pressure needs to be adjusted based upon  
caloric (Btu) value of supply gas (contact local gas  
utility or distributor for this value).  
Refer to Table 2 and Table 3 for high altitude orice part  
number. For replacing orice refer to specic instructions  
included with conversion kit.  
• For specic settings refer to Table 2 for natural gas  
applications and Table 3, Page 7 for propane (LP) gas  
applications.  
Table 2 - 90 - 50/75/100 SERIES 2 NATURAL GAS  
MODEL 90-50  
Stock Factory  
Btu Value of Natural Gas++  
Settings  
0-5,000  
50  
750  
850  
950  
5,000-10,000  
1000  
1050  
Altitude in Ft.  
Normal Input (MBH)  
Manifold Pressure In W.C.  
Orice  
4
4
2.5  
3.5  
2.5  
2.5  
43331094  
43331094  
MODEL 90-75  
Stock Factory  
Settings  
0-5,000  
75  
Btu Value of Natural Gas++  
750  
850  
950  
5,000-10,000  
1000  
1050  
Altitude in Ft.  
Normal Input (MBH)  
Manifold Pressure In W.C.  
Orice  
2.5  
3.5  
3.5  
2.5  
2.5  
2.5  
43331092  
43331092  
MODEL 90-100  
Stock Factory  
Btu Value of Natural Gas++  
Settings  
0-5,000  
100  
750  
850  
950  
5,000-10,000  
1000  
1050  
Altitude in Ft.  
Normal Input (MBH)  
Manifold Pressure In W.C.  
Orice  
2.5  
3.5  
3.5  
2.5  
2.5  
2.5  
43331090  
43331090  
++Contact local gas utility or distributor for Btu value of gas.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
BOILERS FOR USE AT HIGH ALTITUDE - UNITED STATES INSTALLATIONS  
Model 90-75 propane (LP) units only at altitudes  
above 5,000 ft., install 90-75 High Altitude Orice Kit  
#550002629*.  
For all other altitudes use sea level orice  
Table 3 - 90 - 50/75 SERIES 2 PROPANE GAS  
MODEL 90-50  
Stock Factory  
Settings  
0-5,000  
50  
Btu Value of Propane Gas++  
2300  
2350  
2400  
5,000-10,000  
2450  
2500  
Altitude in Ft.  
Normal Input (MBH)  
Manifold Pressure In W.C.  
Orice  
3
3
2.5  
2.5  
2.5  
2.5  
43331095  
43331095  
MODEL 90-75*  
Stock Factory  
Btu Value of Propane Gas++  
Settings  
0-5,000  
75  
2300  
2350  
2400  
5,000-10,000  
2450  
2500  
Altitude in Ft.  
Normal Input (MBH)  
Manifold Pressure In W.C.  
Orice  
3
3
2.5  
3.5  
3.5  
3.5  
43331093  
43331096*  
* For model 90-75 Propane units only at altitudes above 5,000 ft., install 90-75 High Altitude Orice Kit #550002629 For all other  
altitudes use sea level orice.  
++Contact local gas utility or distributor for Btu value of gas.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
BEFORE INSTALLING THE BOILER  
1. Boiler is equipped for residential installations. If used  
Boiler Sizing  
for commercial applications, any additional code  
requirements must be adhered to for installation. This  
may require additional controls including but not limited  
to a low water cut off, a manual reset high temperature  
limit, and wiring and/or piping modications.  
Check to be sure you have selected boiler with proper  
capacity before starting installation. AHRI Rating of boiler  
selected should be greater than or equal to calculated  
peak heating load (heat loss) for building or area(s) served  
by boiler and associated hot water heating systems. See  
Table 1, Page 5.  
2. Before servicing boiler - allow boiler to cool. Shut off  
electricity and gas supply connected to boiler prior to  
servicing.  
Heat loss calculations should be based on approved  
industry methods.  
3. Inspect gas line for leaks.  
4. Verify gas input rate is correct. Over ring may result  
in early failure of boiler sections. This may cause  
dangerous operation. Under ring may result in too  
much air for pre-mix burner causing poor or loss of  
combustion.  
Boiler Location Considerations  
Before selecting boiler location consider following.  
• Supplied with correct type of gas (natural gas or  
propane).  
5. Never vent products of combustion from this boiler to  
enclosed space. Always vent to outdoors. Never vent to  
another room or to inside building.  
• Connected to suitable combustion air intake piping  
system to supply correct amounts of fresh (outdoor)  
air for combustion, refer to “Combustion Air and Vent  
Pipe” on page 22 for details.  
6. Be sure there is adequate outdoor air supply to boiler  
for complete combustion.  
• Connected to a suitable venting system to remove  
the hazardous products of gas combustion, refer to  
“Combustion Air and Vent Pipe” on page 22 for details.  
7. Follow regular service and maintenance schedule for  
efcient and safe operation.  
8. Keep boiler area clean of debris and free of combustible  
• Connected to a suitable hot water heating system.  
and ammable materials.  
• Supplied with a suitable electrical supply for all boiler  
motors and controls.  
9. Proper through wall or through roof combustion venting  
shall be in accordance with materials and methods  
described in this manual. Installation must comply with  
local codes.  
• Connected to a properly located thermostat or  
operating control. Not included with boiler.  
• Placed on level surface. DO NOT install on carpeting.  
10. Boiler and related hot water heating systems are not do  
it yourself items they must be installed and serviced by  
qualied professionals.  
• Condensate drain line must be pitched down to oor  
drain or external condensate pump with reservoir at ¼”  
per foot (wood frame or blocks may be used to raise  
boiler).  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
BOILER INSTALLATION  
• When vent pipe is exposed to temperatures below  
Locating The Boiler  
freezing, such as when it passes through an unheated  
space or when chimney is used as a raceway, vent pipe  
must be insulated with 1/2” Armaex or equivalent.  
In extreme cold climate areas, use ¾” Armaex or  
equivalent.  
1. Place crated boiler as close to selected location as  
possible and un-crate boiler. Boiler may be moved into  
position with appliance dolly or 2 wheel hand truck.  
Insert dolly or hand truck under left hand side of  
boiler. It is possible to slide boiler for short distance on  
smooth oor or surface.  
!
WARNING  
1. Select level location central to piping systems served  
and as close to vent and air intake terminals as  
possible.  
Solvent cements are combustible. Keep away from  
heat, sparks, and open ame. Use only in well ven-  
tilated areas. Avoid breathing in vapor or allowing  
contact with skin or eyes. Failure these instructions  
could result in re, personal injury, or death.  
2. Accessibility clearances, if more stringent (i.e. larger  
clearances) than required re protection clearances,  
must be used for boiler installation. Accessibility  
clearances may be achieved with the use of removable  
walls or partitions.  
• Combustion air must be clean outdoor air. Combustion  
air must not be taken from inside structure because  
that air frequently is contaminated by halogens, which  
include uorides, chlorides, phosphates, bromides and  
iodides. These elements are found in aerosols, deter-  
gents, bleaches, cleaning solvents, salts, air fresheners,  
paints, adhesives and other household products.  
3. Boiler is approved for installation in closets and on  
combustible oors. This boiler shall NOT be installed on  
carpeting.  
4. Clearances shown in Table 4 indicate required  
clearances. Maintain minimum 1” clearance between  
combustible construction and each of left, top and  
back surfaces of the boiler. Minimum 11” clearance  
is required on right side, to allow room for induced  
draft blower. Maintain 18” clearance at side where  
passage is required to access another side for cleaning  
or servicing, inspection or replacement of parts. Allow  
24” at front and left side and 8” at top for servicing. No  
clearances are required to venting or combustion air  
intake piping.  
• Locate combustion air inlet as far away as possible  
from swimming pool and swimming pool pump house.  
• All combustion air and vent pipes must be airtight and  
watertight. Combustion air and vent piping must also  
terminate as shown in “Combustion Air and Vent  
Pipe” section.  
• Vent connections serving appliances vented by  
natural draft shall not be connected into any portion  
of mechanical draft systems operating under positive  
pressure.  
5. Install equipment in location which facilitates operation  
of venting and combustion air intake piping systems as  
described in this manual.  
6. Advise owner to keep venting and combustion air  
intake passages free of obstructions. Both venting  
and combustion air intake piping systems connected  
to outdoors must permit ow through piping systems  
without restrictions for boiler operation.  
Table 4 - Required Clearances  
7. Install boiler such that the automatic gas ignition  
system components are protected from water  
(dripping, spraying, rain, etc.) during operation and  
service (circulator replacement, condensate trap,  
control replacement, etc.).  
Accessibility,  
Cleaning, and  
Servicing  
Combustible  
Clearance  
Unit  
Top  
1” (26mm)  
1 “ (26mm)  
11” (280mm)  
1” (26mm)  
8” (204mm)  
Left Side  
Right Side  
Base  
24” (610mm)  
Combustion Air And Vent Pipe Requirements  
-
-
This boiler requires a dedicated direct vent system. In a  
direct vent system, all air for combustion is taken directly  
from outside atmosphere, and all ue products are  
discharged to outside atmosphere.  
Front  
Back  
1” (26mm)  
1” (26mm)  
0 (0)  
24” (610mm)  
Terminate combustion air and vent pipe connections in  
same atmospheric pressure zone, through roof or sidewall  
(roof termination preferred). See Figure 12 thru Figure 14,  
pages 24 and 25 for required clearances.  
-
-
Intake/Vent Piping  
Near Boiler Hot  
Water Piping  
1” (26mm)  
-
• Keep boiler area clean of debris and free of ammable  
and combustible materials, vapors and liquids.  
All distances measured from the cabinet of the boiler.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
BOILER INSTALLATION  
3. In-so-far as is practical, close all building doors and  
Condensate Drain Requirements  
windows and all doors between the space in which the  
appliances remaining connected to the common venting  
system are located and other spaces of the building.  
Turn on clothes dryer and any appliance not connected  
to the common venting system. Turn on any exhaust  
fans, such as range hoods and bathroom exhaust, so  
they will operate at maximum speed. Do not operate a  
summer exhaust fan. Close re dampers.  
• Pitch condensate drain line down to oor drain at mini-  
mum of ¼” per foot. External condensate pump (not  
furnished) may be used if oor drain is not available.  
• Condensate pump must be designed for ue gas con-  
densate application.  
• Condensate trap provided with boiler, an additional trap  
is not required and should not be used.  
4. Place in operation the appliance being inspected.  
Follow the lighting instructions. Adjust thermostat so  
appliances will operate continuously.  
• Wood frame or blocks may be used to raise boiler  
to maintain drain pitch or to be above external  
condensate pump reservoir.  
5. Test for spillage at the draft hood relief opening after 5  
minutes of main burner operation. Use the ame of a  
match or candle, or the smoke from a cigarette, cigar  
or pipe.  
Foundation Requirements  
• Install boiler on level surface.  
6. After it has been determined that each appliance  
remaining connected to the common venting system  
properly vents when tested as outlined above, return  
doors, windows, exhaust fans, re place dampers,  
and any other gas-burning appliance to their previous  
condition of use.  
!
WARNING  
Fire hazard. Do not install boiler on carpeting.  
Failure to follow these instructions could result in  
death or serious injury.  
• Boiler is NOT to be installed on carpeting.  
7. Any improper operation of the common venting system  
should be corrected so the installation conforms with  
the National Fuel Code, NFPA-54/ANSI -Z223.1 and/  
or the Natural Gas and Propane Installation Code,  
CAN/CSA B149.1.. When re-sizing any portion of the  
common venting system, the common venting system  
should be re-sized to approach the minimum size as  
determined using the appropriate tables in Chapter 13  
of the National Fuel Gas Code, NFPA-54/ANSI- Z223.1  
and/or the Natural Gas and Propane Installation Code,  
• If boiler is not level condensate drain lines will not  
function properly. Adjustable feet are located on the  
boiler to make up for minor surface irregularities or tilt.  
• Wood frame or blocks may be used to raise boiler  
to maintain drain pitch or to be above external  
condensate pump reservoir.  
Removal of Existing Boiler From Common Vent  
System  
CAN/CSA B149.1.  
When an existing boiler is removed from a common  
venting system, the common venting system is likely to be  
too large for proper venting of the appliances remaining  
connected to it. At the time of removal of an existing boiler,  
the following steps shall be followed with each appliance  
remaining connected to the common venting system  
placed in operation, while the other appliances remaining  
connected to the common venting system are not in  
operation.  
1. Seal any unused openings in the common venting  
system.  
2. Visually inspect the venting system for proper size and  
horizontal pitch and determine there is no blockage, or  
restrictions, leakage, corrosion and other deciencies  
which could cause an unsafe condition.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NEAR BOILER PIPING  
Clean the System First  
Supply And Return Lines  
Before connecting boiler to heating system, clean and ush  
system thoroughly. Verify system is free of sediment, ux  
and any residual boiler water additives.  
• Boiler is set up to receive 1 ¼” NPT supply and return  
piping from top access.  
• Boiler may be piped from left side by turning supply  
elbow.  
Systems having antifreeze not recommended must be  
completely ushed to insure no old antifreeze remains.  
In older systems obviously discolored, murky or dirty  
water; or pH reading outside acceptable range (between  
7.0 and 8.0) are indications the system should be cleaned  
or treated. Thoroughly ush system with clean water to  
remove any sediment or contaminants. Sludge and iron  
oxide deposits can cause rapid breakdown of inhibitors.  
• Install furnished dielectric unions at boiler supply and  
return lines prior to making system piping connections  
• Do Not install copper supply and return piping directly  
into aluminum boiler section casings due to galvanic  
corrosion between dissimilar metals.  
• Must use provided dielectric unions between copper  
system piping and boiler to make nal connection to  
boiler.  
Flushing with clean water. If chemical cleaners are used,  
use only those recommended for use with aluminum  
boilers. Follow chemical cleaner manufacturer’s instructions  
completely.  
• Furnished circulator pump can be installed at installer  
preferred location.  
DO NOT mix different manufacturer’s products.  
• When boiler installation is for new heating system,  
install all of radiation units (panels, radiators,  
baseboard, or tubing) and supply and return mains.  
• After all heating system piping and components  
have been installed, make nal connection of system  
piping to boiler. A hot water boiler installed above  
radiation level, or as required by the Authority having  
jurisdiction, must be equipped with low water cut off  
device.  
• Periodic inspection is necessary for ushing of oat  
type devices, per low water cut off manufacturers  
specic instructions.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NEAR BOILER PIPING  
Figure 2 - Single Zone Boiler Piping  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NEAR BOILER PIPING  
Multi-Zone Systems  
Multi-zone systems with two zones are typically piped as  
shown in gures 3 or 4. Multi-zone systems with more than  
two zones are likely to have small zones with very low heat  
and ow requirements compared to full heating capacity of  
the boiler. This can result in very low ow in the boiler if  
only one small zone is calling for heat.  
Primary Secondary Piping is recommended for multi-zone  
systems with more than two zones to insure proper water  
ow through the boiler at all times. See gures 5, 6 and 7  
for typical primary secondary piping congurations.  
Figure 3 - Two Zone Boiler Piping With Zone Valves  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NEAR BOILER PIPING  
Figure 4 - Two Zone Boiler Piping With Circulators  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NEAR BOILER PIPING  
Figure 5 - Primary/Secondary Piping And Wiring With Circulators And Domestic Hot  
Water  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NEAR BOILER PIPING  
Figure 6 - Piping and Wiring Primary/Secondary Multi Zone System Piping With Zone  
Valves And Domestic Hot Water (With Zone Valve)  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NEAR BOILER PIPING  
Figure 7 - Piping And Wiring Primary/Secondary Piping With Zone Valves And Domestic  
Hot Water (With Circulator)  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NEAR BOILER PIPING  
!
WARNING  
Figure 8 - Relief Valve Boiler Piping  
Burn and scald hazard. Safety relief valve could  
discharge steam or hot water during operation.  
Install discharge piping per these instructions.  
RELIEF VALVE  
DISCHARGE  
LINE  
Safety Relief Valve  
Installation of safety relief valve shall conform to ANSI/  
ASME Boiler and Pressure Vessel Code, Section IV.  
• Install furnished safety relief valve using 3/4” x 4½”  
pipe provided with boiler. See Figure 8.  
• Install safety relief valve with spindle in vertical  
position.  
• Do not install shutoff valve between boiler and safety  
relief valve.  
• Install discharge piping from safety relief valve. See  
Figure 8.  
• Use ¾” or larger pipe.  
• Use pipe suitable for temperatures of 375°F (191°C) or  
greater.  
Check local  
codes for  
maximum  
distance  
from oor  
or allowable  
safe point of  
discharge.  
• Individual boiler discharge piping shall be independent  
of other discharge piping.  
• Size and arrange discharge piping to avoid reducing  
safety relief valve relieving capacity below minimum  
relief valve capacity stated on rating plate.  
• Run pipe as short and straight as possible to location  
protecting user from scalding and properly drain piping.  
• Install union, if used, close to safety relief valve outlet.  
• Install elbow(s), if used, close to safety relief valve  
outlet and downstream of union (if used).  
• Terminate pipe with plain end (not threaded).  
Expansion Tank And Make-Up Water  
Determine required system ll pressure, system design  
temperature, and system water content.  
• Boiler contains 2.6 gallons (U.S.). Size expansion tank  
accordingly. Consult expansion tank manufacturer for  
proper sizing information.  
• Connect properly sized expansion tank (not furnished).  
Diaphragm type expansion tank see Figure 9, Page 19.  
See Figure 10, Page 20 for conventional closed type  
expansion tanks.  
• For diaphragm type expansion tanks, adjust tank  
air pressure to match system ll pressure. Install  
furnished air vents shown for diaphragm type  
expansion tank system only.  
• Install make-up water connections as shown per local  
codes.  
• If pressure reducing valve is used, adjust to match  
system ll pressure.  
• Verify clean water supply is available. When water  
supply is from well or pump, install sand strainer at  
pump  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NEAR BOILER PIPING  
Figure 9 - Diaphragm Type Expansion Tank Piping  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NEAR BOILER PIPING  
Figure 10 - Conventional (Closed Type) Expansion Tank Piping  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NEAR BOILER PIPING  
Condensate Drain Piping  
Filling Condensate Trap With Water  
Boiler is factory equipped with a condensate trap. An  
additional trap is not required and should NOT be used.  
On initial start up condensate trap must be manually lled  
with water.  
1. Provide ½” PVC condensate drain and ttings.  
Condensate drain to be pitched down to oor drain at a  
minimum of ¼” per foot.  
Following are the steps required to initially ll condensate  
trap for start up. Steps are only required at initial start up  
or if maintenance requires draining of condensate trap.  
2. Install ½” PVC tee to overow tting as shown in  
1. Disconnect vent condensate drain line from vent pipe  
Figure 11.  
connector on outlet of induced draft blower.  
3. The ½” diameter schedule 40 PVC or CPVC condensate  
drain and pipe ttings must conform to ANSI standards  
and ASTM D 1785 or D2846.  
2. Pour about 1 cup of cold tap water into vent drain line  
with funnel.  
3. Excess water should go through overow and out  
through condensate drain line. Verify proper operation  
of drain line (or external condensate pump if used).  
4. Schedule 40 PVC or CPVC cement and primer must  
conform to ASTM D2564 or F493.  
5. In Canada, use CSA or ULC certied schedule 40 PVC  
4. Reinstall vent drain line.  
or CPVC drain pipe cement.  
6. Condensate pump with reservoir (not furnished) may  
be used to remove condensate to a drain line (sanitary  
line) above boiler if oor drain is not available or is not  
accessible.  
Chilled Water Piping  
Install boiler, when used in connection with refrigeration  
system, so chilled medium is piped in parallel with boiler  
with appropriate valves to prevent chilled medium from  
entering boiler.  
Boiler piping system of hot water boiler connected to  
heating coils located in air handling units where they may  
be exposed to refrigerated air circulation must be equipped  
with ow control valves or other automatic means to  
prevent gravity circulation of the boiler water during cooling  
cycle.  
Figure 11 - Condensate Drain Piping  
FROM BLOWER  
PITCH DRAIN PIPE  
DOWN TO FLOOR  
DRAIN AT MINIMUM  
1/4” PER FOOT  
TO DRAIN  
OPEN  
1/2” PVC  
PVC TEE 1/2”SLIP X  
CONDENSATE  
1/2” SLIP X 1/2” SLIP  
DRAIN  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMBUSTION AIR AND VENT PIPE  
Connections And Termination  
6. Combustion air and vent piping lengths. Table 5,  
Page 23. First 5 ft. of vent piping run must be 2”  
CPVC:  
Provisions for combustion and ventilation air must be  
in accordance with section, Air For Combustion and  
Ventilation, of the National Fuel Gas Code,ANSI 2223.1/  
NFPA54, or Sections 8.2, 8.3 or 8.4 of National Gas and  
Propane Installation Code, CAN/CGA-B 149.1, or applicable  
provisions of the local building code.  
Length of pipe is counted from boiler jacket (air  
intake pipe) or from vent pipe connector(vent pipe).  
Termination is not counted toward the “Total Equivalent  
Length.  
Boilers require dedicated direct vent system. All air for  
combustion is taken directly from outdoors through  
combustion air intake pipe. All ue products are discharged  
to outdoors through vent pipe.  
For elbows, reduce maximum vent length as shown:  
• 2” 90° elbow -1 ½ ft. per elbow.  
• 3” 90° elbow - 3 ft. per elbow.  
1. See Figure 12 thru Figure 14, Pages 24 and 25  
for combustion air and vent pipe roof and sidewall  
termination. Roof termination is preferred. Combustion  
air and vent pipes must terminate together in same  
atmospheric pressure zone as shown.  
Example:  
To add two (2) 90° elbows to a 3” pipe for a 75 boiler.  
Each elbow is 3 ft. per 90 ° elbow for a total of 6 ft..  
2. Construction through which vent and air intake pipes  
may be installed is maximum 24 inches, minimum ¼”  
thickness.  
(1 elbow @ 3 ft. + 1 elbow @ 3 ft. = 6 equivalent ft. of  
pipe)  
3. Combustion air and vent pipe ttings must conform  
to American National Standards Institute (ANSI)  
standards and American Society for Testing and  
Materials (ASTM) standards D1784 (schedule-40  
CPVC), D1785 (schedule-40 PVC), D2665 (PVC-DWV),  
D2241 (SDR-21 and SDR-26 PVC), D2661 (ABS-DWV),  
or F628 (schedule-40 ABS). Pipe cement and primer  
must conform to ASTM standards D2564 (PVC) or  
D2235 (ABS).  
Total additional pipe is then subtracted from maximum  
allowable pipe length to give new maximum length of  
106 ft. with two (2), 90° elbows.  
“TOTAL EQUIVALENT LENGTH”:  
Original 112 ft. max. - 6 equivalent ft. for 2 elbows =  
new 106 ft. maximum length.  
4. Canada construct all combustion air and vent pipes  
for this unit of ULC S636 listed schedule-40 CPVC,  
schedule-40 PVC, PVC-DWV or ABS-DWV pipe and pipe  
cement. SDR pipe is not approved in Canada.  
• First 3 feet (900mm) of venting must be readily  
available for visual inspection.  
7. Pitch combustion air and vent piping back to boiler at  
minimum ¼” per ft. (21 mm/m) from intake and vent  
terminals so all moisture in combustion air and vent  
piping drains to boiler. Pitch pipes continuously with no  
sags or low spots where moisture can accumulate and  
block ow of air or ue gas. Combustion air and vent  
pipes must be airtight and watertight.  
• Specied primers and glues of certied vent  
system must be from single manufacturer, and not  
intermixed with other manufacturer’s vent system  
parts.  
• Components of the certied system must not be  
interchanged with other vent systems, or unlisted  
pipe and/or ttings.  
8. Consider following when determining appropriate  
location for termination of combustion air and vent  
piping.  
• Position termination where vent vapors will not damage  
plants/shrubs or air conditioning equipment.  
• Position termination as to not be effected by wind eddy,  
air born leaves, snow, or recirculated ue gases.  
NOTICE  
Transition from 2” pipe to 3” pipe must be made in  
vertical run.  
• Position termination where it will not be subjected to  
potential damage by foreign objects, such as stones,  
balls, etc..  
5. Boiler combustion air and vent piping connections are  
sized for 2” pipe. Any pipe size change (to 3”) must be  
made outside of boiler casing in vertical run of pipe to  
allow for proper drainage of vent condensate. Due to  
potential for ue gas temperatures over 155°F, rst  
ve (5) feet of vent pipe must be CPVC, the remain-  
ing vent pipe can be PVC. If any elbows are employed  
within the rst 5 feet of vent, they must be CPVC too.  
Two (2) - 30” pieces of 2” CPVC pipe. 2½” piece of 2”  
CPVC pipe, a 2” CPVC elbow and 2” CPVC pipe coupling  
are furnished with the boiler.  
• Position termination should where vent vapors are not  
objectionable.  
• Place vent on wall away from prevailing wind. Locate or  
guard vent to prevent accidental contact with people or  
pets.  
• Terminate vent above normal snowline. Avoid locations  
where snow may drift and block vent. Ice or snow may  
cause boiler to shut down if vent becomes obstructed.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMBUSTION AIR AND VENT PIPE  
Table 5 - Combustion Air And Vent Piping Lengths - Total Equivalent Length  
BOILER  
SIZE  
2” PIPE MINIMUM  
VENTING  
2” PIPE MAXIMUM  
VENTING  
3” PIPE MINIMUM  
VENTING  
3” PIPE MAXIMUM  
VENTING  
100  
2 FEET  
2 FEET  
21 FEET  
26 FEET  
15 FEET  
20 FEET  
92 FEET  
75 & 50  
112 FEET  
• Under certain conditions, ue gas will condense,  
forming moisture, and may be corrosive. Take steps to  
prevent building materials at vent from being damaged  
by exhaust of ue gas.  
• Vent shall not terminate underneath veranda, porch or  
deck unless,  
(a) veranda, porch or deck is fully open on minimum of  
two sides beneath oor, and  
• Vent shall not terminate where it may cause hazardous  
frost or ice accumulations on adjacent property  
surfaces.  
(b) distance between top of vent termination and  
underside of veranda, porch or deck is greater than 1  
ft. (300mm).  
9. Venting system shall terminate at least 3 ft. (0.9m)  
above any forced air inlet (except boiler’s combustion  
air inlet) within 10 ft.(3m).  
See gures 12 and 13 and 14 for two pipe terminations.  
See gures 15, 16 and 17 for concentric vent terminations.  
• Venting system shall terminate at least 12 in. from any  
air opening into any building.  
Installation  
1. Attach combustion air intake piping using eld supplied  
2” exible coupling. Attach vent piping to furnished 2”  
vent pipe connector on draft inducer outlet.  
• Vent bottom shall be located at least 12 in. above  
grade.  
• Termination of the vent shall be not less than 7 ft.  
(2.1m) above adjacent public walkway or paved  
driveway.  
2. All pipe joints are to be water tight  
3. Working from boiler to outside, cut pipe to required  
length(s).  
• Vent terminal shall not be installed closer than 3 ft.  
from inside corner of L shaped structure.  
4. Deburr inside and outside of pipe.  
5. Chamfer outside edge of pipe for better distribution of  
• Vent termination should be kept at least 3 ft. away  
from vegetation.  
primer and cement.  
6. Clean and dry all surfaces to be joined.  
7. Check dry t of pipe and mark insertion depth on pipe.  
• USA only. Venting system shall terminate at least 4  
ft. horizontally from, and in no case above or below,  
unless 4 ft. (1.22m) horizontal distance is maintained,  
from electric meters, gas meters, regulators, and relief  
equipment.  
8. After pipes have been cut and pre-assembled, apply  
cement primer to pipe tting socket and end of pipe to  
insertion mark. Quickly apply approved cement to end  
of pipe and tting socket (over primer). Apply cement  
in light, uniform coat on inside of socket to prevent  
buildup of excess cement. Apply second coat.  
• Canada only. Venting system shall terminate at  
least 6 ft. (1.83m) horizontally from, in no case above  
or below, unless a 6 ft. (1.83m) horizontal distance  
is maintained, from electric meters, gas meters,  
regulators, and relief equipment.  
9. While cement is still wet, insert pipe into socket with  
¼ turn twist. Be sure pipe is fully inserted into tting  
socket.  
• Vent shall not terminate within 6 ft. (1.8m) of  
mechanical air-supply inlet to any building.  
10. Wipe excess cement from joint. Continuous bead of  
cement will be visible around perimeter of properly  
made joint.  
• Vent shall not terminate above regulator within 3  
ft. (900 mm) horizontally of vertical center line of  
regulator vent outlet to maximum vertical distance of  
15 ft. (9.5m).  
11. Handle pipe joint carefully until cement sets.  
12. Support combustion air and vent piping minimum of  
every 5 feet using pre-formed metal hanging straps.  
Do not rigidly support pipes. Allow movement due to  
expansion and contraction.  
• Vent shall not terminate within 3 ft. (900mm) of  
window or door that can be opened in any building, or  
any non-mechanical air-supply inlet to any building, or  
of combustion air inlet of any other appliance.  
13. Slope horizontal portion of combustion air and vent  
pipes toward boiler minimum of ¼” per linear ft.  
(21mm/m) with no sags between hangers.  
14. Use appropriate methods to seal openings where vent  
and combustion air pipes pass through roof or side  
wall.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMBUSTION AIR AND VENT PIPE  
Figure 12 - Roof Vent / Intake Terminations  
VENT  
AIR INTAKE  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMBUSTION AIR AND VENT PIPE  
Figure 13 - Side Wall Vent / Intake terminations - Less Than 12” Clearance Above Grade  
Less Than 12” Clearance  
Figure 14 - Side Wall Vent/Intake Terminations - 12” Or More Clearance Above Grade  
12” Or More Clearance  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMBUSTION AIR AND VENT PIPE  
Figure 17 - Concentric Vent Roof  
Figure 15 - Concentric Vent Terminations  
Installation  
1" (2.54cm)  
Maximum  
VENT  
NOTE:  
SUPPORT MUST BE  
FIELD INSTALLED TO  
SECURE TERMINATION  
KIT TO STRUCTURE.  
D
COMBUSTION AIR  
A
Vent  
Combustion  
C
Air  
1" (2.54cm)  
Overhang  
ROOF BOOT/FLASHING  
Maximum  
A
(FIELD SUPPLIED)  
B
ELBOW  
(FIELD SUPPLIED)  
SUPPORT  
(FIELD SUPPLIED)  
12" (30cm) Minimum  
B
C
* See Note  
36"(0.9m) Minimum  
Below  
MAINTANIN 12 IN.  
(18IN. FOR CANADA)  
MINIMUM CLEARANCE  
ABOVE HIGHEST  
COM  
AIR  
VENT  
D
Maintain 12"(30cm)  
Vent  
clearance above highest  
ANTICIPATED SNOW  
LEVEL. MAXIMUM OF  
24 IN. ABOVE ROOF  
anticipated snow level or  
Combustion  
Air  
grade  
*Must be less than 4" or greater than 24" Horizontal dis-  
tance between end bells of each air intake to prevent ue  
gas recirculation.  
Figure 16 - Concentric Vent  
STRAP  
A
(FIELD SUPPLIED)  
ELBOW  
(FIELD SUPPLIED)  
B
B
C
COMBUSTION  
AIR  
1” MAXIMUM  
VENT  
VENT  
C
COMBUSTION AIR  
A
NOTE:  
SECURING STRAP MUST BE FIELD INSTALLED TO  
PREVENT MOVEMENT OF TERMINATION KIT IN SIDE  
WALL.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMBUSTION AIR AND VENT PIPE  
Figure 18 - Combustion Air and Vent Piping - Boiler Connections  
2” (50.8mm) DIAMETER VENT AND  
COMBUSTION AIR INTAKE PIPING  
- 21 feet maximum total equivalent  
length for 90-100 models  
-26 feet maximum total equivalent  
length for 90-50 and -90-75 models  
- 2 feet minimum total equivalent  
length for all models  
TRANSITION FITTING  
2” (50.8mm) to 3” (76.2mm)  
IN VERTICAL RUN  
3” (76.2mm) DIAMETER VENT AND  
COMBUSTION AIR INTAKE PIPING  
- 92 feet maximum total equivalent length  
for 90-100 models  
- 15 feet minimum total equivalent length  
for 90-100 models  
- 112 feet maximum total equivalent length  
for 90-50 and 90-75 models  
- 20 feet minimum total equivalent length  
for 90-50 and 90-75 models  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS SUPPLY PIPING  
!
CAUTION  
!
DANGER  
WHAT TO DO IF YOU SMELL GAS  
Fire Hazard. Do not use matches, candles, open  
ames, or other methods providing ignition source.  
Failure to comply will result in death or serious  
injury.  
• Do not try to light any appliance.  
• Do not touch any electrical switch; do not use  
any phone in your building.  
• Immediately call your gas supplier from a  
neighbor’s phone. Follow gas supplier’s  
instructions.  
Leak Check Gas Piping  
Pressure test boiler and gas connection before placing  
boiler in operation.  
• If you cannot reach your gas supplier, call the re  
department.  
Disconnect boiler and its individual gas shutoff  
valve from gas supply system.  
Isolate boiler from gas supply system by closing  
manual gas shutoff valve. See Figure 19,  
Page 29.  
Check Gas Supply  
Gas pipe to your boiler must be correct size for length of  
run and for total Btu per hour input of all gas utilization  
equipment connected to it. See Table 7, Page 29.  
Locate leakage using gas detector, noncorrosive  
detection uid, or other leak detection method  
acceptable to authority having jurisdiction. Do  
not use matches, candles, open ames, or other  
methods providing ignition source.  
Boiler and its individual shutoff valve must be disconnected  
from gas supply piping system during any system pressure  
testing at test pressures in excess of ½ psig (3.5kpa).  
Boiler must be isolated from gas supply piping system  
by closing its individual manual shutoff valve during  
any pressure testing of gas supply piping system at test  
pressures equal to or less than ½ psig (3.50ka).  
Correct leaks immediately and retest.  
Table 6 - Gas Supply Pressure  
NATURAL PROPANE  
Connecting The Gas Piping  
See Figure 19, Page 29 for general layout at boiler.  
Gas line enters boiler from right side jacket panel.  
GAS  
GAS  
Boiler is equipped with ½” NPT connection on gas valve for  
supply piping.  
MAXIMUM GAS  
SUPPLY PRESSURE  
10” w.c.  
14” w.c.  
Following rules apply:  
MINIMUM GAS SUPPLY  
PRESSURE  
4” w.c.  
10” w.c.  
1. Use piping materials and joining methods acceptable  
to authority having jurisdiction. In absence of such  
requirements:  
• USA - National Fuel Gas Code, ANSI Z223.1/NFPA 54  
• Canada - Natural Gas and Propane Installation Code,  
CAN/CSA B149.1  
2. Size and install gas piping system to provide sufcient  
gas supply to meet maximum input at not less than  
minimum supply pressure. See Table 7, Page 29  
3. Use ground joint unions.  
4. Provide sediment trap up stream of gas valve.  
5. Use two pipe wrenches when making the connection to  
gas valve to keep it from turning.  
6. Install a manual shutoff valve in the vertical pipe about  
5 feet above oor.  
7. Tighten all joints securely.  
8. Propane gas connections should only be made by  
licensed propane installer.  
9. Two stage regulation should be used by propane  
installer.  
10. Propane gas piping should be checked out by propane  
installer.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS SUPPLY PIPING  
Table 7 – Gas Pipe Sizes  
NATURAL GAS  
Pipe Capacity - BTU Per Hour Input Includes Fittings  
Length of  
Pipe - Ft.  
1/2”  
3/4”  
1”  
1 1/4”  
625,000  
445,000  
365,000  
20  
40  
60  
92,000  
63,000  
50,000  
190,000  
350,000  
245,000  
195,000  
130,000  
105,000  
PROPANE GAS  
Pipe Capacity - BTU Per Hour Input Includes Fittings  
Length of  
Pipe - Ft.  
Copper Tubing*  
Iron Pipe  
5/8”  
3/4”  
216,000  
1/2”  
3/4”  
20  
40  
60  
131,000  
90,000  
72,000  
189,000  
129,000  
103,000  
393,000  
267,000  
217,000  
145,000  
121,000  
* Outside diameter  
Figure 19 - Gas Piping  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL WIRING  
Connect Circulator Pump Wiring  
!
WARNING  
See Figure 20, Page 31 for circulator pump eld wiring con-  
nections.  
Electrical shock hazard. Turn OFF electrical power  
supply at service panel before making electrical  
connections. Failure to do so could result in death  
or serious injury.  
Supplied 5 foot wiring harness with exible metal conduit  
for connection from circulator pump to junction box.  
If two 120 Volt circulator wire terminals inside junction box  
are not used, leave two wire nuts to prevent short circuit.  
Electrically bond boiler to ground in accordance with  
requirements of authority having jurisdiction. Refer to:  
NOTICE  
• USA- National Electrical Code, ANSI/NFPA 70.  
• Canada - Canadian Electrical Code, Part I, CSA C22.1:  
Safety Standard for Electrical Installations.  
Label all wires prior to disconnection when servicing  
controls. Wiring errors can cause improper and  
dangerous operation. Verify proper operation after  
servicing.  
Electric Power Supply  
Prior to making any line Voltage connections, turn OFf  
electrical power at fuse box.  
Things to Avoid when Locating Thermostats  
1. Run separate 115 Volt circuit from separate over  
current protection device in electrical service entrance  
panel. This should be 15 ampere circuit.  
DEAD SPOTS:  
Corners and alcoves  
Behind doors  
HOT SPOTS:  
Concealed pipes  
Fireplace  
COLD SPOTS:  
2. See Figure 20, Page 31 for diagram showing service  
switch junction box and power supply connection  
points.  
Concealed pipes or ducts  
Stairwells - drafts  
3. Locate service switch in vicinity of boiler. Verify it is  
TV sets  
turned OFF during service or maintenance.  
Radios  
• Connect black (hot) lead from power supply to black  
wire labeled L 120 VAC.  
Lamps  
Unheated rooms on  
other side of wall  
Direct sunlight  
Kitchens  
• Connect white (neutral) lead from power supply to  
white wire labeled N 120 VAC.  
• Connect green (ground) lead from power supply to  
green wire labeled G 120 VAC.  
4. Run 14 gauge or heavier copper wire from boiler to  
grounded connection in service panel or properly driven  
and electrically grounded ground rod.  
Thermostat Installation  
• Thermostat location has important effect on operation  
of boiler system.  
• Follow instructions included with your thermostat.  
• Locate thermostat about ve feet above oor on inside  
wall.  
• Mount directly on wall or on vertical mounted outlet  
box.  
• It should be sensing average room temperature.  
Set heat anticipator (where applicable) at 0.7 amps.  
Connect 24 Volt thermostat leads to two(2) yellow wires  
located in junction box, located on outer jacket of boiler.  
See Figure 20, Page 31 for junction box and thermostat  
eld wiring connections.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL WIRING  
Figure 20 - Wiring Schematic  
NOTICE  
If any of original wire as supplied with this appliance  
must be replaced, it must be replaced with type  
105°C Thermoplastic wire or its equivalent  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL WIRING  
Figure 21 - Ladder Wiring Diagram  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL WIRING  
Figure 22 - Suggested Wiring Schematic for Domestic Hot Water Priority Two Zone  
System with Circulators Using Argo AR822II Pump Relay  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL WIRING  
Figure 23 - Ladder Diagram for Figure 22  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CONTROLS AND ACCESSORIES  
• Boiler temperature is cooling at a rate greater than  
5°F/minute while circulator is running.  
This section provides a brief description of the key controls  
and accessories found in this boiler.  
See Figure 26, Page 41 for detailed sequence of operation.  
See the Repair Parts Manual for locations of all control  
components and accessories described.  
4. For Installations using Indirect Hot Water Heater  
Depending on the specic installation, thermal purge  
delay might or might not affect end user’s expectation for  
domestic hot water delivery. In event the customer has a  
concern that it takes too long for hot water, the situation  
may be resolved in three ways.  
Integrated Boiler Control (IBC)  
Integrated Boiler Control (IBC) is a microprocessor based  
controller for high efciency gas boiler that monitors  
all safety controls and which controls operation of the  
combustion air blower, circulator pump, burner, and  
a combination direct spark igniter/ame sensor. This  
controller is not intended for use with a vent damper.  
Controller is mounted on control panel inside of boiler and  
contains a three character user interface display.  
A. Add a Domestic Hot Water Module, ECR part  
Number 240009562 (Honeywell part number  
W8375s1008). This control senses when hot water  
is being drawn, and instructs the integrated boiler  
control to bypass the thermal purge operation until  
domestic how water draw ends. Thermal purge will  
then be re-enabled.  
DHW module incorporates a temperature sensor  
installed at the indirect water heater’s hot water  
supply tting ( Note - this sensor is in addition to,  
not in place of, the limit control on the hot water  
tank.) The Module is connected to the Enviracom  
terminals in the Integrated Boiler Control.  
High Limit Control  
High Limit Control determines maximum boiler water  
temperature and also provides means for protecting boiler  
and heating system from unsafe operating conditions which  
could damage boiler.  
B. Thermal purge parameters may be adjusted (higher  
thermal purge temperature limit and/or shorter  
thermal purge time delay) to bring the burner on  
sooner.  
Limit control sensor is mounted in ¾” NPT control well on  
top of the front boiler section at hot water outlet.  
Limit control is incorporated in IBC and is eld adjustable  
between 80°F and 190°F.  
Field setpoint adjustment for each installation depends on  
heating system requirements.  
C. Thermal purge function can be disabled.  
Limit Control automatically resets when boiler water  
temperature decreases (10-30°F adjustable differential).  
Differential can be adjusted to provide exibility for boiler  
Gas Control Valve  
Electrically controlled Combination Gas Control Valve is  
designed to meet requirements for use with direct ignition  
systems found in this boiler. Valve is piped to gas/air mixer.  
operation. Larger the differential, longer run cycle of boiler.  
Thermal Purge Operation  
Direct Spark Igniter  
1. Thermal purge feature complies with 2012 DOE  
and NRCan requirements that boiler control must  
incorporate automatic means to adjust water  
temperature.  
2. Intent of thermal purge is to insure usable residual  
heat in the boiler is circulated until it is sufciently  
depleted from the system before the burner is allowed  
to re. To that end, on call for heat, burner is held  
off while circulator runs until boiler temperature drops  
to thermal purge temperature limit or time delay is  
exceeded. Both of these parameters are adjustable.  
Direct spark igniter utilizes a spark gap to initiate gas  
combustion in the burner. Igniter is mounted next to burner  
through gas/air mixer. The igniter also serves as means for  
proving main burner ame by ame rectication. In the  
event of a lack of ame signal on three (3) consecutive tri-  
als for ignition, IBC will lockout and display Error Code 62.  
Draft Inducer Temperature Safety Switch  
Draft Inducer Temperature Safety Switch is a disc  
thermostat (180 °F setpoint) located on induced draft fan  
outlet port. Switch protects inducer and vent pipe from  
potential high temperature condition for discharging ue  
gases. Condition would typically be result of higher high  
limit control setting or over ring. Temperature safety  
switch automatically resets when the vent temperature  
decreases. (15 °F switch differential).  
3. When boiler temperature falls below thermal purge  
temperature limit or time delay expires, burner is  
allowed to re.  
In addition to thermal purge temperature and thermal  
purge time delay parameters, two other conditions release  
integrated boiler controller from thermal purge and allow  
burner to run in order to maintain comfort in the space.  
• Boiler temperature has dropped 10°F from boiler water  
temperature measured at beginning of the call for heat.  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CONTROLS AND ACCESSORIES  
Casting Temperature Safety Switch  
Drain Valve  
In event of lack of or loss of water in boiler, Casting  
Temperature Safety Switch (300 °F setpoint) installed  
on top of the aluminum boiler section shuts off boiler by  
shutting off power to Integrated Boiler Control (IBC). This  
fault requires manual reset of casting temperature safety  
switch to restart the boiler. Verify that boiler is properly  
lled with water before resetting this switch.  
Manual drain valve provides means of draining water in  
heating system, including boiler and hot water supply and  
return piping systems installed above drain valve. This  
drain valve is installed in ¾” tapping at bottom of front  
boiler section. Any piping installed below elevation of  
this drain valve will require additional drain valves to be  
installed at low points in piping systems in order to drain  
entire system.  
Never run cold water into a hot empty boiler.  
A.S.M.E. Rated Pressure Relief Valve  
Differential Pressure Air Proving Switch/Blocked  
Vent Safety Shutoff  
Each boiler must have a properly sized and installed  
American Society of Mechanical Engineers rated pressure  
relief valve. Water expands as it is heated by burner/  
boiler sections. If there is no place for water to expand  
its volume, (i.e. a properly sized and properly functioning  
expansion tank) pressure on inside of boiler and heating  
system will increase. Furnished relief valve automatically  
opens at 30 psig pressure to relieve strain on boiler and  
heating system from increasing pressure. Pressure relief  
valve discharge must be piped with piping same size as  
valve discharge opening to open drain, tub or sink, or  
other suitable drainage point not subject to freezing, in  
accordance with A.S.M.E. specications and requirements  
of local jurisdiction.  
Differential pressure switch monitors air ow by sensing  
differential pressure measured in inches of water (” w.c.).  
Pressure switch contacts close when draft inducer is  
running. Closed switch indicates there is adequate air ow  
for combustion. Pressure switch shuts off main burner if  
differential pressure is inadequate due to blocked vent pipe,  
blocked air intake, blocked boiler sections, or blocked draft  
inducer. If pressure switch contacts fail to close control will  
display Error Code 29.  
Draft Inducer  
Draft inducer (blower) provides means for pulling  
combustion air into and through the mixer, burner, ue  
ways of cast aluminum boiler sections and ue adapter  
before being discharged through vent piping to outdoors.  
See applicable sections for proper sizing and installation of  
combustion air and vent piping in this manual.  
External Condensate Pump (Optional)  
For installations where there is no oor drain or other  
appropriate drainage receptacle available to receive  
condensate from the boiler, an external oat activated  
condensate pump with integral sump is required. This unit  
can be installed to pump the condensate to a remote tie in  
point to a sanitary sewer system. For this application, the  
boiler must be installed so that proper pitch of piping to the  
external condensate reservoir (sump) can be accomplished.  
Use wood frame or blocks to raise boiler as required for  
proper installation.  
Circulator Pump  
Every forced hot water system requires at least one  
circulating pump.  
Circulating pump imparts the necessary energy to move  
water through closed loop supply and return piping  
systems, terminal heating equipment (i.e. nned tube  
radiators, etc.) and back through boiler for reheating.  
To provide required hot water ow rates, circulator pump  
must be properly sized to overcome frictional losses  
(usually measured in feet of water, also referred to as  
“pump head loss”) of supply and return piping systems and  
boiler.  
The circulator pump is furnished for single zone or zone  
valve controlled heating system and should be located on  
downstream (i.e., pumping away) side of expansion tank.  
For pump controlled system (where there is a circulator for  
each zone) circulator provided with boiler can work for one  
zone. For more details on piping and circulators, see “Near  
Boiler Piping” on page 11.  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
START UP  
Purging Air For Systems With Conventional  
Water Quality, Water Treatment and Freeze  
Protection - see Appendix A  
Closed Type Expansion Tanks:  
Refer to the appropriate diagrams“Near Boiler Piping” on  
page 11 for more information.  
Filling Boiler With Water And Purging Air For  
Systems With Diaphragm Type Expansion Tanks  
Refer to the appropriate diagrams,“Near Boiler Piping” on  
page 11 for more information.  
1. Close all zone service valves on the supply and return  
piping. Open the feed valve and ll boiler with water.  
Make sure air vent is open. Hold relief valve open until  
water runs air free for ve seconds to rapidly bleed air  
from boiler, then let the relief valve snap shut.  
2. Open the zone service valve on the supply pipe for the  
rst zone. Open the purge valve on the rst zone. Feed  
water will ll the zone, pushing air out the purge valve.  
Close the purge valve when the water runs air free.  
Close the zone service valve.  
1. Close all zone service valves on the supply and return  
piping and close the expansion tank service valve.  
Drain expansion tank. Open the feed valve and ll  
boiler with water. Hold relief valve open until water  
runs air free for ve seconds to rapidly bleed air from  
boiler, then let the relief valve snap shut.  
2. Open the zone service valve on the supply pipe for the  
rst zone. Open the purge valve on the rst zone. Feed  
water will ll the zone, pushing air out the purge valve.  
Close the purge valve when the water runs air free.  
Close the zone service valve.  
3. Repeat step 2 for all remaining zones.  
4. Open the expansion tank service valve and the tank  
vent. Fill the tank to the proper level and close the  
tank vent. Remove the handle from the expansion tank  
service valve so the homeowner doesn’t accidentally  
close it.  
5. Open all service valves. Any air remaining trapped in  
the return lines between the service valves and the  
boiler will be pushed towards the expansion tank when  
the boiler is placed in operation.  
3. Repeat step 2 for all remaining zones.  
4. Open all service valves. Any air remaining trapped in  
the return lines between the service valves and the  
boiler will be pushed towards the air vent when the  
boiler is placed in operation.  
5. Inspect piping system. Repair any leaks immediately.  
6. Inspect piping system. Repair any leaks immediately.  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATING INSTRUCTIONS  
WARNING  
!
!
CAUTION  
If you do not follow these instructions  
exactly, a re or explosion may result causing  
property damage, personal injury or loss of  
life.  
WHAT TO DO IF YOU SMELL GAS  
• Do not try to light any appliance.  
• Do not touch any electrical switch; do not use  
any phone in your building.  
• This appliance is equipped with an ignition device  
which automatically lights burner. Do NOT try to  
light this burner by hand.  
• Immediately call your gas supplier from a  
neighbor’s phone. Follow the gas supplier’s  
instructions.  
• Before operating smell all around appliance area  
for gas. Be sure to smell next to oor because  
some gas is heavier than air and will settle to the  
oor.  
• If you cannot reach your gas supplier, call the re  
department.  
Use only your hand to turn the gas shutoff  
valve. Never use tools. If valve will not turn  
by hand, do not try to repair it, call a qualied  
service technician. Force or attempted repair may  
result in re or explosion.  
To Turn Off Gas To Appliance  
1. Set the thermostat to lowest setting.  
2. Turn off all electric power to the appliance if service is  
to be preformed.  
3. Remove the front jacket panel.  
Do not use this appliance if any part has  
been under water. Immediately call a qualied  
service technician to inspect appliance and to  
replace any part of control system and any gas  
control which has been under water.  
4. Turn gas control knob clockwise  
5. Replace the front jacket panel.  
to “OFF”.  
Stop! Read Safety information above.  
1. Set thermostat to lowest setting.  
2. Turn off all electric power to the appliance.  
3. This appliance is equipped with an ignition device which  
automatically lights the burner. DO NOT try to light the  
burner by hand.  
Figure 24 - Gas Valve  
4. Remove the front jacket panel.  
5. Turn the gas control knob clockwise  
to “OFF”.  
6. Wait ve (5) minutes to clear out any gas. Then smell  
for gas, including near the oor. If you smell gas,  
STOP! Follow “B” in the safety information above on  
this label. If you don’t smell gas go on to next step.  
ON  
INLET  
7. Turn the gas control knob counterclockwise  
to  
“ON”.  
OFF  
8. Replace front jacket panel.  
9. Turn on all electrical power to the appliance.  
10. Set the thermostat to desired setting.  
GAS CONTROL KNOB  
SHOWN IN "ON" POSITION  
11. If the appliance will not operate, follow the instructions  
“To Turn Off Gas To Appliance” and call your service  
technician or gas supplier.  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
S9381A INTEGRATED BOILER CONTROL OPERATION AND ADJUSTMENTS  
S9381A control has a number of user adjustable  
parameters as shown in Table 8.  
Table 8 - User Parameters  
Adjusting Settings  
Figure 25 - Display  
To discourage unauthorized changing of settings, a  
procedure to enter the adjustment mode is required.  
To enter the adjustment mode, press the UP, DOWN,  
and I buttons simultaneously for three seconds. Press  
and release the I button until the parameter requiring  
adjustment is displayed.  
Then press the UP or DOWN button until the parameter has  
reached the desired value. After 60 seconds without any  
button inputs, the control will automatically return to the  
READ mode.  
Display  
In RUN mode, status items and parameters are viewable.  
To read settings, press and release the I Key to nd the  
parameter of interest. For example, press and release  
I until setpoint (sp) is displayed, followed by a three-  
digit number, i.e., 220, followed by °F or °C. See Display  
Readout, Figure 25.  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
S9381A INTEGRATED BOILER CONTROL OPERATION AND ADJUSTMENTS  
Table 9 - State Code Denitions  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
S9381A INTEGRATED BOILER CONTROL OPERATION AND ADJUSTMENTS  
Figure 26 - Sequence of Operation  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CHECK OUT PROCEDURE AND ADJUSTMENT  
Verify Proper Sequence Of Operation  
Test Other Safety Controls  
Place boiler into operation and observe operation through  
several cycles. Follow remaining steps in this section to  
insure boiler is operating correctly.  
If boiler is equipped with low water cut off, manual reset  
high limit, or additional safety controls, test for operation  
as outlined by control manufacturer. Burner should be  
operating and should go off when controls are tested. When  
safety controls are restored, burner should reignite.  
First couple of cold starts may be rough due to gas line not  
being completely purged of air, causing low ring rate and  
high excess air levels.  
Set Thermostat Heat Anticipator (If Used) And  
Verify Thermostat Operation  
Inspect Venting And Air Intake System  
Operate boiler and verify all vent/air intake connections are  
gas-tight and watertight. Repair any leaks immediately.  
For single thermostat connected to yellow thermostat lead  
wires in furnished eld wiring junction box, heat anticipator  
should be set at 0.7 amps. For other wiring congurations,  
refer to instructions provided by thermostat manufacturer  
regarding adjustment of heat anticipator. Cycle boiler  
with thermostat. Raise thermostat to highest setting and  
verify boiler goes through normal start up cycle. Lower  
thermostat to lowest setting and verify boiler goes off.  
Inspect Condensate Drain  
Verify all connections are watertight, and that condensate  
ows freely. Repair any leaks immediately.  
Inspect System Piping  
Verify all connections are watertight. Repair any leaks  
immediately.  
Measure Natural Gas Input Rate  
Correct input rate is essential for proper and efcient  
operation of the burner and boiler.  
1. Determine elevation at installation site.  
Test Ignition System Safety Shutoff Device  
1. Turn off manual gas valve  
2. Table 1 and Table 2, Page 6 to determine correct input  
rate for the local elevation.  
3. Obtain yearly average heating value of local gas supply  
from gas utility. At sea level elevation, it should be  
approximately 1000 Btu’s per standard cubic foot.  
2. Set thermostat to call for heat  
3. Boiler begins normal sequence of operation  
4. After approximately 20 seconds (pre purge, state code  
4. Operate boiler for 5 minutes.  
4) gas valve is powered (state code 6).  
5. Turn off all other gas appliances, extinguishing standing  
5. After 13 second trial for ignition, gas valve closes,  
(state code 10)as integrated boiler control senses that  
ame is not present.  
pilots where applicable.  
6. At gas meter, measure time in seconds required to use  
one cubic foot of gas.  
6. After about 30 seconds, control will go back to step 4  
and make two more attempts to light the burner, then  
go into soft lockout and display Error code 62.  
7. Calculate input rate according to the following formula:  
3600 x heating value from step 3  
7. To restart system, open manual gas valve that was  
closed in Step 1. Reset lockout by breaking and  
restoring power to boiler. Observe normal operation.  
Btuh in put rate = time from step 6  
8. Measured input rate should be within +/-2% of input  
rating from step 2. If within 2%, go to step 9. If not,  
adjustment is required, proceed as follows:  
A. Turn boiler off  
B. Set up U-tube manometer or differential pressure  
gauge for measuring manifold pressure. See  
Figure 27, Page 44.  
Test High Limit Control And Adjust  
While burner is operating,adjust high limit setpoint below  
actual boiler water temperature. Burner should go off while  
circulator continues to operate. Raise limit setting above  
boiler water temperature and burner should reignite after  
inter-purge (retry delay). Set high limit control to design  
temperature requirements of system. Maximum high limit  
setting is 190°F. Minimum high limit setting is 80°F.  
C. Manometer or gauge must be able to read at least  
0.0 to 3.0 inches water column of pressure, and  
resolve to at least 0.1 inches water column.  
D. Turn boiler on.  
E. Manifold pressure has been nominally set at 2.5  
inches w.c. Manifold pressure and input rate must  
always be measured with pressure regulator cover  
screw installed. Cover screw must be removed for  
adjustment. Manifold pressure reading will change  
(increase) when cover screw is removed.  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CHECK OUT PROCEDURE AND ADJUSTMENT  
F. After adjusting input rate, turn boiler off, remove  
Set Thermostat To Desired Room Temperature  
Observe several operating cycles to verify proper operation.  
manometer or pressure gauge, reinstall ” plug  
on gas valve. Turn boiler on.  
G. Boiler should typically operate between:  
• 8.5% -10.0% CO2 on Natural Gas  
• 9.5% -11.0% CO2 on Propane Gas  
Review All Instructions  
Review all instructions shipped with this boiler with owner  
or maintenance person. Instructions must be afxed on or  
adjacent to the boiler.  
Under all conditions CO level should not exceed 100  
ppm.  
Complete and sign the “Installation and Check-Out  
9. Restore all gas appliances that may have been shut off  
(while measuring boiler input rate) to normal operating  
conditions.  
Certicate” on page 54  
.
I. Remove regulator cover screw on top of gas valve,  
and insert an appropriate screwdriver into adjustment  
screw.  
II. Turn adjustment screw clockwise to increase input  
rate, or counter clockwise to decrease input rate.  
III. Replace cover screw, or cover hole temporarily with  
your nger to check new manifold pressure setting. Do  
not set manifold pressure lower than 2.0 inches w.c.  
or higher than 3.0 inches w.c. when adjusting input  
rate.  
IV.Measure new input rate (cover screw must be  
installed). Repeat steps I.-IV until the input rate is  
within +/-2% of the nameplate input rating.  
V. If the actual input rate can not be set to within 2%  
of the correct input rating by adjusting manifold  
pressure, a change in gas orice size is required.  
Consult the boiler manufacturer for information on  
correct orice sizing. The specic gravity (G) and the  
higher heating value (HHV) of the local natural gas  
must be obtained from the local gas utility in order to  
determine the proper orice size.  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CHECK OUT PROCEDURE AND ADJUSTMENT  
Figure 27 - Manifold Pressure Measurement Detail  
Following steps and diagram indicate location of the  
connection points required to measure manifold pressure.  
Refer to “Differential Air Pressure Switch Check” on page  
49 when reading manifold pressure.  
Manifold pressure may be measured using a U-Tube  
Manometer or Differential Pressure Gauge. Diagram shows  
connection of both measuring devices. Only ONE DEVICE IS  
REQUIRED to measure manifold pressure.  
When measurement is complete, disconnect U-Tube  
Manometer or Differential Pressure Gauge. Be sure to  
reinstall ” plug, using appropriate pipe thread sealant  
approved for use with natural and liqueed Petroleum  
gases.  
Remove plug. Install appropriate barbed tting and connect  
pressure side line from U-Tube Manometer or Differential  
Pressure Gauge.  
Figure 28 - Gas Valve  
PRESSURE REGULATOR  
ADJUSTMENT (UNDER CAP SCREW)  
NOTICE  
WIRING TERMINALS (2)  
VR8205  
Regulator cover screw must be installed at all times un-  
less adjusting manifold pressure. Firing rate and manifold  
pressure must only be measured with cover screw rmly  
installed.  
OUTLET  
PRESSURE  
TAP  
INLET  
PRESSURE  
TAP  
OUTLET  
INLET  
ON  
OFF  
GAS CONTROL KNOB  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAINTENANCE AND CLEANING  
2. Check boiler area is free from combustible materials,  
Maintenance As Outlined Below Can Be  
Performed By Owner Unless Otherwise Noted.  
gasoline, and other ammable vapors and liquids.  
3. Circulator pump and blower motor furnished with boiler  
are permanently lubricated from factory and require no  
further lubrication. Additional or non-factory supplied  
pumps and/or motors should be lubricated according to  
the pump and/or motor manufacturer’s instruction.  
• The acidic nature of ue gasses condensing on  
aluminum boiler sections may cause formation of  
aluminum oxide. This oxide formation is normal,  
is generally uniform throughout boiler sections,  
and represents negligible mass of aluminum that is  
consumed by oxidation during life of the boiler.  
• If left unchecked, this buildup may eventually cause  
blockage of ue gas passages in boiler sections,  
reducing efciency, and ultimately shutting down the  
boiler due to lack of combustion air ow.  
Daily During Heating Season  
1. Check for and remove any obstruction to the ow of  
combustion air or venting of ue gases.  
• Regular service and maintenance by a qualied service  
agency must be performed to assure safe trouble free  
operation and maximum efciency.  
2. Check boiler area is free from combustible materials,  
gasoline, and other ammable vapors and liquids.  
Monthly During Heating Season  
Beginning Of Each Heating Season  
1. Remove jacket front and top panels and check for  
piping leaks around relief valve and other ttings. If  
found, contact qualied service agency to repair. DO  
NOT use stop leak compounds.  
1. Annual service call by qualied service agency, which  
includes:  
A. Examine ue passages between boiler sections,  
burner, and condensate lines, and clean if  
necessary following “Annual Examination And  
Cleaning Of Boiler Components” on page 46.  
2. Test relief valve. Refer to valve manufacturers  
instructions packaged with relief valve.  
3. Visually inspect venting and air intake system for  
proper function, deterioration, or leakage. If vent or  
air intake show any signs of deterioration or leakage,  
contact a qualied service agency to repair or replace  
immediately and to insure proper reassembly and  
resealing of vent and air intake system.  
B. Visually inspect venting and air intake system  
for proper function, deterioration or leakage. If  
vent or air intake show any signs of deterioration  
or leakage, repair or replace them, immediately.  
Insure proper reassembly and resealing of vent and  
air intake system  
4. Visually inspect clear vinyl condensate lines and PVC  
condensate drain pipe for proper operation, leakage,  
and deterioration. If condensate lines or drain pipe  
show any signs of blockage, leakage, or deterioration  
contact a qualied service agency to clean, repair, or  
replace them immediately.  
C. Check for and remove any obstruction to ow of  
combustion air or venting of ue gases. Check air  
bafe located inside 1½” x 2” exible coupling on  
mixer, clean if necessary and make sure to put it  
back. Refer to repair parts diagram of mixer and  
pressure switch assembly for exact location.  
D. Follow instructions for“Operating Instructions” on  
page 38.  
Periodically During Heating Season  
Where low water cutoffs are used, periodic inspection of  
low water cut off is necessary, including ushing of oat  
type devices. Refer to low water cut off manufacturer’s  
specic instructions.  
E. Follow instructions for“Check Out Procedure and  
Adjustment” on page 42.  
F. Visually inspect condensate drain lines for proper  
operation and deterioration. Check for plugged  
condensate drain lines.  
G. Check silicone rubber seals between boiler sections.  
Insure that there are no leaks. Use RTV silicone  
rubber adhesive sealant rated for at least 400° F to  
replace or repair seals in locations where original  
seals have deteriorated.  
End of Each Heating Season - Annual Shutdown  
Procedure  
Follow instructions “To Turn Off Gas To Appliance” on page  
38.  
If heating system is to remain out of service during  
freezing weather, and does not contain antifreeze, drain  
system completely. If boiler will be exposed to freezing  
temperatures, drain condensate lines. Otherwise, do not  
drain system or boiler.  
H. Check all gasketed joints for leakage, and tighten  
bolts or replace gaskets if necessary.  
I. Remove jacket front and top panels and check for  
piping leaks around relief valve and other ttings.  
Repair, if found. DO NOT use stop leak compounds.  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAINTENANCE AND CLEANING  
K. Reinstall burner and mixer gasket and position  
Annual Examination And Cleaning Of Boiler  
Components  
mixer assembly over studs. Install ve (5) nuts but  
do not tighten. Reinstall igniter and igniter gasket  
and fasten with two (2) screws. Use care when  
installing the igniter. Tighten ve (5) nuts holding  
mixer assembly.  
!
DANGER  
Before servicing, turn off electrical power to boiler  
at service switch. Close manual gas valve to turn  
gas supply OFF to boiler. Failure to comply will result  
in death or serious injury.  
L. Connect:  
• Gas line to gas valve  
• Condensate drain line to boiler  
• Pressure switch hose to gas valve  
• Air by-pass to mixer  
• 1 ½” x 2” exible coupling to air inlet and make  
sure to put air bafe back to correct position  
NOTICE  
Have qualied service agency perform the following  
service procedures. Boiler owner should not attempt  
these procedures.  
• Igniter wires  
• Gas valve wires  
1. Before Servicing, turn off electrical power to boiler at  
service switch. Close manual gas valve to turn off gas  
supply to boiler.  
2. Cleaning Flue passages between boiler sections.  
A. Any buildup of sediment or aluminum oxide (white  
powdery or aky substance) in ue passages must  
be cleaned as follows.  
3. Visually inspect condensate lines leading from boiler  
sections and vent pipe connector to condensate trap.  
Refer to repair parts diagrams. Any foreign material or  
debris visible in condensate lines needs to be cleaned  
out as follows:  
A. Disconnect condensate drain lines from condensate  
trap.  
B. Remove condensate trap and drain all water from  
trap.  
C. Disconnect condensate lines from tting on bottom  
of boiler and vent pipe connector.  
D. Run cold water through condensate lines and trap  
B. Remove jacket front and top panels. Disconnect  
condensate drain line from barbed tting on bottom  
of boiler. Keep open end of drain line above water  
level in condensate trap to prevent trap from  
draining. Disconnect pressure switch hose from  
barbed tting on gas valve. Disconnect 1½ x 2”  
exible coupling from air inlet. Disconnect air by-  
pass (½” transparent vinyl tube) from bottom of  
mixer.  
to thoroughly ush out any sediment or debris.  
E. Reinstall condensate trap and condensate lines.  
C. Remove air bafe from ½” x 2” exible coupling  
and clean air bafe if necessary. Refer to repair  
parts diagram, mixer and pressure switch  
assembly.  
F. Follow instructions under “Near Boiler Piping” for  
lling condensate trap with water.  
4. Inspection of ue connector requires following steps. Refer  
to repair parts diagram.  
D. Conrm manual gas valve is closed and disconnect  
gas line to gas valve at union. Disconnect wires to  
gas valve and igniter.  
E. Loosen but do not remove ve (5) nuts attaching  
mixer assembly to boiler. Remove two (2) igniter  
screws and remove igniter.  
A. Loosen the clamp on the draft inducer end of the  
2” vent pipe connector that connects the vent  
to the draft inducer. Disconnect (unplug) wiring  
harness from draft inducer motor and draft inducer  
temperature safety switch. Remove four (4) bolts  
that attach draft inducer to ue connector.  
B. Remove draft inducer and gasket from top of ue  
F. Remove ve (5) nuts and remove mixer assembly.  
connector.  
Remove burner and mixer gasket.  
C. Inspect interior of ue connector. Any buildup of  
sediment or aluminum oxide on inside surface must  
be cleaned. Position draft inducer gasket and draft  
inducer and fasten with four (4) screws. Be sure to  
connect ground wire from draft inducer motor to  
one of four mounting screws.  
G. Aluminum oxide deposits are water soluble and  
may be rinsed away with spraying or running  
water. Before rinsing, connect a ½” I.D. hose to  
barbed tting on bottom of boiler and run hose to  
bucket or drain.  
H. After rinsing, remove any remaining loosened  
sediment using shop vacuum with snorkel  
attachment.  
D. Connect wiring harness leads to draft inducer motor  
and draft inducer temperature safety switch.  
E. Connect vent pipe connector to draft inducer outlet.  
I. Inspect burner for any foreign matter in ame  
ports or inside burner. Any foreign matter should  
be removed by blowing with compressed air or  
vacuuming.  
J. Inspect interior of mixer for any signs of sediment  
or aluminum oxide and clean if necessary.  
NOTICE  
Verify proper operation after servicing.  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLESHOOTING  
2. Troubleshooting tools:  
!
WARNING  
A. Voltmeter to check 120 vac and 24 vac  
Fire, explosion or shock hazard. Do not attempt to  
modify the physical or electrical characteristics of  
this boiler in any way. Failure to comply could result  
in death or serious injury.  
B. Continuity tester.  
C. Inclined manometer or pressure gauge with  
0-3.0” Range (0.01” Scale) for measuring suction  
pressures at pressure switch.  
D. U-tube manometer or differential pressure gauge  
with 0-14” range (0.1” Scale) for measuring inlet  
Important  
1. In reset from lockout condition, all electrical meter  
readings at the gas control valve (24 vac) must be  
taken within trial for ignition period.  
and manifold gas pressures.  
3. IBC Error Codes.  
A. IBC uses advanced diagnostic capability to assist in  
troubleshooting error conditions. Table 10, Page 48  
shows error codes that may arise during fault  
condition.  
2. If any component does not function properly, make  
sure it is correctly installed and wired before replacing  
it.  
3. Static electricity discharge can damage integrated  
boiler control (IBC). Touch metal surface to discharge  
static electricity before touching IBC.  
B. State Conditions shown in Table 9, Page 40 provide  
suggestions for servicing these potential errors.  
4. IBC cannot be repaired. If it malfunctions it must be  
replaced.  
5. Only trained service technicians should service IBC  
systems. Following troubleshooting, check out system  
following sequence of operation for a normal light off  
sequence.  
6. All controls are factory tested in the assembly process  
and a defective control is generally the least likely  
cause. If you suspect you have a defective control,  
read through this section before you replace it.  
7. It is extremely unlikely that the two consecutive  
controls are defective. If it seems to be happening,  
chances are that either there is nothing wrong with the  
control or it is being damaged by some other problem  
(an electrical short burning out a transformer, for  
example).  
Initial Service Checks  
1. Before troubleshooting:  
A. Make sure that circuit breaker is on or fuse is ok at  
electrical panel.  
B. Make sure that service switch is on.  
C. Make sure that gas is on at the gas meter, at all  
appropriate manual shutoff valves and at the gas  
control valve.  
D. Make sure that the thermostat is calling for heat.  
E. Check that wire connectors at the integrated boiler  
control and at the originating control are securely  
plugged in or connected.  
F. Check that hoses are securely connected and are  
not plugged or damaged.  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLESHOOTING  
Table 10 Error Codes  
-
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DIFFERENTIAL AIR PRESSURE SWITCH CHECK  
• Following steps and diagram indicate locations of  
connection points required to check differential air  
pressure.  
PRESSURE  
SWITCH  
CONNECTS  
BOILER  
STATUS  
DIFFERENTIAL  
PRESSURE (W.C.)  
• Differential air pressure switch is safety device which  
prevents boiler from ring if there is air intake, boiler  
heat exchanger or vent blockage.  
Not Running  
Setpoint  
0”  
Normally Open  
• Turn off service switch, or lower thermostat setting.  
• Remove vinyl caps from Tee and 4-way connector.  
1.00” for Model-100  
1.60” for Model-75  
2.10” for Model-50  
• Install testing lines as shown to inclined manometer or  
differential pressure gauge with ability to read 0.01” to  
3.0” w.c.  
Running  
Without  
Blockage  
Greater Than  
Setpoints  
Closed  
Open  
• Turn on service switch and set thermostat to call for  
heat.  
Running  
With  
Less Than or Equal to  
Setpoints  
Blockage  
If manometer readings do not correspond to chart above,  
check for possible causes:  
• - Blockage or moisture in suction lines  
• - Blockage in air intake or vent pipes  
• - Undersized air intake or vent pipes  
• - Loose blower wheel or motor shaft  
• - Incorrect pressure switch or pressure switch setpoint  
When pressure reading is proper and the pressure switch is  
operating properly, remove testing lines and reinstall vinyl  
caps to Tee and 4-way connector.  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A - WATER QUALITY, WATER TREATMENT AND FREEZE PROTECTION  
Aluminum Series  
High Efciency Gas-Fired Boiler  
DIELECTRIC ISOLATION & ANTIFREEZE PROTECTION  
ADDENDUM  
!
WARNING  
Follow these instructions to prevent damage to  
boiler’s heat exchanger caused by inadequate  
dielectric isolation, incorrect water treatment or  
antifreeze application. Failure to comply could result  
in death or serious injury.  
• Install boiler so gas ignition system components are  
protected from water (dripping, spraying, rain, etc)  
during appliance operation and service (circulator re-  
placement, etc).  
• DIELECTRIC ISOLATION  
Two (2) 1-1/4” X 1-1/4” Female to female dielectric  
isolation unions are shipped loose in boiler parts bag.  
Install Dielectric Isolation unions at boiler supply line  
and return line. Install isolation ttings nearest boiler  
prior to system piping connections.  
• WATER TREATMENT and ANTIFREEZE  
PROTECTION  
MUST be applied for ALL aluminum series high  
efciency gas-red boilers using antifreeze  
protection.  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System and Operating Precautions  
Applies to ALL Aluminum High Efciency Gas-Fired Water Boilers  
Clean System First  
Eliminate System Leaks  
BEFORE connecting boiler to heating system, clean and  
ush system thoroughly. Verify system is free of sediment,  
ux and any residual boiler water additives.  
Continuous addition of make-up water will constantly add  
oxygen to system. Eliminate all system leaks. All system  
leaks must be repaired immediately.  
Systems having antifreeze not recommended must be  
completely ushed to ensure no old antifreeze remains.  
In older systems obviously discolored, murky or dirty  
water; or pH reading outside acceptable range (between  
7.0 and 8.0) are indications the system should be cleaned  
or treated. Thoroughly ush system with clean water to  
remove any sediment or contaminants. Sludge and iron  
oxide deposits can cause rapid breakdown of inhibitors.  
DO NOT use stop leak compounds. Leaks in threaded  
connections in aluminum boiler sections must be repaired  
immediately. Aluminum threads will not seal themselves.  
Verify expansion tank is operational and properly sized.  
Undersized expansion tanks cause relief valve weeping and  
substantial make-up water addition.  
Operation of this boiler in system containing signicant  
amounts of dissolved oxygen can cause severe heat  
exchanger corrosion damage.  
Flushing with clean water. If chemical cleaners are used,  
use only those recommended for use with aluminum  
boilers. Follow chemical cleaner manufacturer’s instructions  
completely.  
This boiler is not designed for use in systems containing  
regular additions of make-up water. Regular additions of  
make-up water may cause severe heat exchanger damage.  
System leaks may not always be visible. An unseen system  
leak will become obvious if boiler pressure decreases when  
make-up valve is closed.  
DO NOT mix different manufacturer’s products.  
Fill Water and Chemistry  
Verify water used to ll system meets these requirements:  
System uid pH maintained between 7.0 and 8.0.  
Maintain water hardness below 7 grains hardness.  
This boiler is designed for closed loop hydronic heat system  
ONLY! This boiler is not suitable for natural gravity type  
installations, or any other open type system.  
Filling with chlorinated potable water is acceptable. DO  
NOT ll boiler with water containing chlorine in excess of  
100 ppm.  
DO NOT use inhibitors or other additives that are not listed  
in this addendum.  
Consult local water treatment specialist for  
recommendations if any of above requirements is outside  
stated ranges.  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System and Operating Precautions  
Applies to ALL Aluminum High Efciency Gas-Fired Water Boilers  
General Guidelines When Using Antifreeze  
• Recommend taking pH reading annually, and  
adjusted as necessary. Follow antifreeze/inhibitor  
manufacturer’s instructions for details on how to  
adjust pH.  
Use only antifreeze products recommended  
for use with aluminum boilers, as listed in  
this addendum. See Table 11.  
• Continuous addition of make-up water will dilute  
power of antifreeze and change buffers ability to  
maintain pH.  
• Antifreeze solutions can break down over time.  
Failure to check antifreeze chemistry on annual  
basis may result in accelerated corrosion of  
boiler and other system components. Consult with  
antifreeze manufacturer for recommendations.  
• Flush old antifreeze from system. Flush boiler and  
system separately.  
• Do not use antifreeze unless required.  
• Use of antifreeze in any boiler will reduce  
heating capacity as much as 10-20%. Take  
into consideration when sizing heating system,  
pumps and expansion tank. Consult antifreeze  
manufacturer’s literature for specic information  
on reduced capacity.  
• Antifreeze, if needed, must be of type listed on  
next page due to their operational characteristics  
of : type 356 T6 aluminum at operating  
temperatures between 20°F (-6.7°C) and 250°F  
(121°C). (See Table 11 for allowable products.)  
• Always clean system prior to using antifreeze as  
stated in this supplement.  
• Using antifreeze manufacturer’s instructions,  
determine freezing temperature needed and use  
correct amount of antifreeze. Never exceed 50%  
antifreeze by volume.  
• Follow antifreeze manufacturer’s instructions for  
use, safe handling and storage of their products.  
Refer to MSDS (Material Safety Data Sheets)  
provided by antifreeze manufacturer for potential  
hazards and rst aid procedures for exposure or  
ingestion.  
• Boiler operating pressure must remain below 15  
psi for antifreeze solutions that specify a maximum  
of 250°F (121°C). Otherwise, increase system  
operating/tank pressure to 20 psig. Note: Refer  
to expansion tank manufacturer instructions for  
adjusting tank pressure.  
• Antifreeze will raise pH of hydronic solution in  
heating system above recommended level due to  
corrosion inhibitors. Solution must be treated to  
maintain a pH within recommended level. Follow  
antifreeze manufacturer’s instructions to adjust  
pH.  
• If system has leaked, water and antifreeze  
chemistry will need to be adjusted. To avoid  
damage to boiler, check pH and chemistry of boiler  
solution and consult the antifreeze manufacturer  
for recommendations.  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System and Operating Precautions  
Applies to ALL Aluminum High Efciency Gas-Fired Water Boilers  
Table 11 - Antifreeze Products  
Compatible Aluminum Antifreeze & Inhibitor Suppliers  
Noble Company  
P. O. Box 350  
Grand Haven, MI 49417  
Noburst AL Antifreeze  
Tel:  
800-878-5788  
231-799-8850  
Fax:  
Rhomar Water Management, Inc.  
P. O. Box 229  
Rhogard Antifreeze &  
Pro-Tek 922 Inhibitor*  
Springeld, MO 65801  
Tel:  
800-543-5975  
417-862-6410  
Fax:  
* Pro-Tek 922 Inhibitor may be used to adjust the pH level of the hydronic system, but on occasion may not resolve the  
pH issue. In these cases, ush the system and rell with untreated water and antifreeze suitable for aluminum heat  
exchangers, as listed in this supplement.  
Hydronic Agencies, Ltd.  
(Fernox North Distributor)  
15363 117 Avenue  
Edmonton, AB T5M 3X4  
Canada  
Alphi-11  
Tel:  
780-452-8661  
780-488-2304  
Fax:  
Fernox  
Interstate Chemical  
2797 Freedland Road  
P.O. Box 1600  
Intercool NFP-30,40,50 AA  
Intercool RPH-15*  
Hermitage, PA 16148-0600  
Tel: 800-422-2436  
Fax: 724-981-8383  
Hercules Chemical Company, Inc.  
111 South Street  
Passaic, NJ 07055  
Hercules cryo-tek™-100/Al  
Tel: 800-221-9330  
Fax: 800-333-3456  
* This product may be used to adjust pH level of hydronic system, but on occasion may not resolve pH issue. In these  
cases it is recommended to ush system and rell with untreated water and new boiler manufacturer approved  
antifreeze suitable for Aluminum heat exchangers.  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION AND CHECK-OUT CERTIFICATE  
INSTALLATION AND CHECK-OUT CERTIFICATE  
Boiler Model  
Serial #  
Date Installed___________  
Measured BTU/HR input____________  
Installation instructions have been followed  
Checkout procedure and adjustments performed  
Maintenance and Service issues reviewed with owner/ maintenance person  
Installation booklet afxed on or adjacent to boiler  
Installer (Company)  
Address  
Phone  
Installer’s Name  
Signature  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTES  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRODUCT LITERATURE  
Lennox Industries Inc.  
Dallas, Texas  
Manufactured by:  
ECR International, Inc.  
2201 Dwyer Avenue, Utica NY 13501  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Legacy Car Audio Car Speaker LW15590 User Manual
LG Electronics Refrigerator LRFD21855 User Manual
Logitech Wireless Office Headset F540 User Manual
Magnavox DVD VCR Combo CMWD2205 User Manual
Makita Planer 10170 User Manual
Manitowoc Ice Ice Maker CSA 151 User Manual
Mark Levinson Stereo Amplifier JC 2 User Manual
Maytag Clothes Dryer MED5800TW0 User Manual
Melissa Coffeemaker 745 112 User Manual
Memorex TV VCR Combo MVT2139 User Manual