INSTALLATION AND OPERATION MANUAL
Direct-Vent Gas
Fireplace Inserts
Retain These Instructions For Future Reference
P/N 775,218M Rev. A, 05/2007
A French manual is available upon request. Order P/N 775,218CF.
Ce manuel d’installation est disponible en francais, simplement
en faire la demande. Numéro de la pièce 775,218CF.
Shown with Cast Pillar face
In the Commonwealth of Massachusetts:
• Installation must be performed by a licensed plumber or gas fitter
• See Table of Contents for location of additional Commonwealth
of Massachusetts requirements
Ravenna™ 33/40 (RDV33/40)
Report No. 050-S-15c-5
WARNINGS
• Hot! Do not touch! The glass and surfaces of this appliance will be hot during operation and will
retain heat for a while after shutting off the appliance. Severe burns may result.
• Carefully supervise children in the same room as appliance.
• Suitable for installation into masonry or factory built fireplaces. These appliances may be installed in an after-
market permanently located, manufactured (mobile) home, where not prohibited by local codes. This appliance
is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with
other gases unless a certified kit is used.
• Lennox™ gas-burning appliances are designed for use as a supplemental heater. They are not intended for
continuous use as a primary heat source.
AVERTISSEMENT:Assurez-vousdebiensuivrelesinstruc-
tionsdonnées danscettenoticepourréduireauminimum
le risque d’incendie ou d’explosion ou pour éviter tout
dommage matériel, toute blessure ou la mort.
WARNING: If the information in this manual is not
followed exactly, a fire or explosion may result
causing property damage, personal injury or loss
of life.
FOR YOUR SAFETY
POURVOTRESÉCURITÉ: Nepasentreposerniutiliserd'essence
ni d'autres vapeurs ou liquides inflammables à proximité de
cet appareil ou de tout autre appareil.
POUR VOTRE SÉCURITÉ: Que faire si vous sentez une odeur
de gaz:
Do not store or use gasoline or other flammable
vapors or liquids in the vicinity of this or any other
appliance.
WHAT TO DO IF YOU SMELL GAS:
• Ne pas tenter d'allumer d'appareil.
• Ne touchez à aucun interrupteur.
• DO NOT light any appliance.
• DO NOT touch any electrical switches.
• DO NOT use any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow your gas supplier's
instructions.
• Ne pas vous servir des téléphones se trouvant dans le bâti-
ment
• Appelez immédiatement votre fournisseur de gaz depuis un
voisin. Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz, appelez
le service des incendies.
L'installation et l'entretien doivent être assurés par un
installateur ou un service d'entretien qualifié ou par le
fournisseur de gaz.
• If your gas supplier cannot be reached, call
the fire department.
Installationandservicemustbeperformedbyaquali-
fied installer, service agency or the gas supplier.
Download from Www.Somanuals.com. All Manuals Search And Download.
Cautions & safety
FOR YOUR SAFETY do not install or operate your
Your Lennox™ gas insert must be equipped for the
proper fuel type & altitude at which it will be operated.
Any operation outside the parameters outlined in this
manual may result in a hazardous condition & will void
thewarranty.Pleasecarefullyreadthesectionspertain-
ing to these subjects and/or be sure your appliance is
properly equipped.
Ravenna™ gas insert without first reading & under-
standing this manual. Any installation or operation of
the appliance deviating from that which is stated in this
manual WILL void the warranty & may be hazardous.
INSTALLATION & REPAIR SHOULD ONLY BE DONE BY
A QUALIFIED SERVICE TECHNICIAN. DO NOT ATTEMPT
TO SERVICE THE APPLIANCE YOURSELF.
Do not use this insert if any part has been under water.
Immediatelycallaqualifiedservicetechniciantoinspect
theappliance&toreplaceanypartofthecontrolsystem
& any gas control which has been under water.
The insert should be inspected & cleaned before use
& at least annually by a qualified service technician.
More frequent cleaning may be required due to exces-
sive lint from bedding material, carpeting, etc.
Due to high temperatures, the insert should be located
out of traffic areas & away from furniture & draper-
ies.
It is imperative that control compartments, burners, &
circulating air passageways of the room heater be kept
clean.
Children & adults should be alerted to the hazards of
high surface temperature & should stay away to avoid
burns or clothing ignition. Young children should be
carefullysupervisedwhentheyareinthesameroomas
the Lennox gas insert. Clothing or any other flammable
material should not be placed on or near the insert.
Adequate clearances around the combustion chamber
and accessibility clearances for servicing & proper
operation must be maintained.
Turn off the gas before servicing this appliance. It is
recommended that a qualified service technician per-
form an appliance check-up at the beginning of each
heating season.
Never use solid fuels such as wood, paper, cardboard,
coal, or any flammable liquids, etc., in this appli-
ance.
All installations must conform with all local, state,
& national codes. In the absence of local codes, the
installation must conform with National Fuel Gas Code
ANSI Zꢀꢀꢁ.1-latest edition, also known as NFPA 54 (In
Canada,thecurrentCAN/CSA B149.1installationcode).
Refer to the National Fuel Gas Code & local zoning &
codeauthoritiesfordetailsoninstallationrequirements.
Your Ravenna gas insert must be vented to the outside
in accordance with the latest edition of the National
Fuel Gas Code.
Any grill, panel, or glass removed for service MUST be
replaced prior to operating the insert. Do not operate
appliance with the glass front removed, cracked or
broken. Replacement of the glass should be done by a
qualified service technician.
DO NOT USE abrasive cleaner on the glass door assem-
bly. DO NOT ATTEMPT to clean the glass door when it
is hot.
This gas insert MUST be vented directly to the outside
& MUST NEVER be attached to a chimney serving a
separate solid fuel burning appliance. Each gas appli-
ance MUST USE a separate vent system. Common vent
systems are PROHIBITED.
Gold & nickel plated surfaces must be cleaned with
glass cleaner & a clean soft cloth before firing the first
timeorfingerprintswillremainpermanently.NEVERuse
brass polish to clean gold or nickel, this will remove
the plating!!!
MobilehomeinstallationsmustconformwiththeMobile
Home Construction and Safety Standard, Title ꢀ4 CFR,
Partꢁꢀ80(inCanadaCAN/CSAZꢀ40MH),or,whensuch
a standard is not applicable, the Standard for Mobile
Home Installations, ANSI Aꢀꢀ5.1 - latest edition.
When opening the lower door on the face while the
insert is burning, pull at the far left or far right vent
openings, because the door is hot during operation.
Lennox Hearth Products, its employees, or any of its
representatives assume no responsibility for any dam-
ages caused by an inoperable, inadequate, or unsafe
condition as a result of any improper operation, service
or installation procedures, whether direct or indirect.
The appliance, when installed, must be electrically
grounded in accordance with local codes or in the ab-
sence of local codes, with the National Electrical Code,
ANSI/NFPA 70 - latest edition. In Canada, the current
CSA Cꢀꢀ-1 Canadian Electrical Code - latest edition.
INSTALLER: THESE INSTRUCTIONS ARE TO REMAIN
WITH THE HOME OWNER!
ꢁ
Download from Www.Somanuals.com. All Manuals Search And Download.
If the factory-built fireplace has no gas access hole(s)
provided, an access hole of 1-1/2 inches (38 mm) or less
may be drilled through the lower sides or bottom of the
firebox in a proper workmanship like manner. This access
hole must be plugged with a non-combustible insulation
after the gas supply line has been installed. The installer
must mechanically attach the marking supplied with the gas
fireplace insert to the inside of the firebox of the fireplace
into which the gas fireplace insert is installed.
Orifice Size/Altitude Adjustment
For altitudes above 2,000 feet (In Canada 4,500 FT/1370
M),the orifice should be de-rated by 4% for every 1,000 feet
to maintain the proper ratio of gas to air. Improper orifice
sizing may result in damage and unsafe conditions. Chang-
ing the orifice should only be done by a qualified service
technician. Contact your Lennox Hearth Products dealer for
proper orifice sizes.
The Ravenna™ Insert
IMPORTANT: When installing these appliances into a fac-
tory built fireplace or heat-form, the air flow within and
aroundthefireplaceshallnotbealteredbytheinstallation
of the insert (i.e. DO NOT BLOCK louvers or cooling air
inlet or outlet ports, circulating air chambers in a steel
fireplace liner or metal heat circulator).
• Mustconformwithalllocal,state,andnationalinstallation
codes. In the absence of local codes, the installation must
conform with NationalFuelGasCodeANSIZ223.1-latest
edition, also known as NFPA 54 (In Canada, the current
CAN/CSA B149.1 installation code). Refer to the National
Fuel Gas Code and local zoning and code authorities for
details on installation requirements.
• MustconformwiththeManufacturedHomeConstruction
and Safety Standard, Title 24 CFR, Part 3280 (in Canada
CAN/CSA Z240 MH), or when such a standard is not
applicable, the Standard for Manufactured Home Instal-
lations, ANSI A225.1 - latest edition for manufactured
(mobile) home installations.
WARNING
THIS FIREPLACE HAS BEEN ALTERED TO
ACCOMMODATE A FIREPLACE INSERT AND
SHOULD BE INSPECTED BY A QUALIFIED
PERSON PRIOR TO RE-USE AS A
CONVENTIONAL FIREPLACE.
• Must be vented directly to the outside in accordance with
the latest edition of the National Fuel Gas Code and must
never be attached to a chimney serving a separate solid
fuel burning appliance.
Codes & Approvals
• Has been certified for use with either natural gas or pro-
pane.
CertifiCation
• Is not for use with solid fuels.
Gas appliances must be tested and certified by a nation-
ally recognized testing and certification laboratory to ANSI
(American National Standard Institute) gas appliance safety
standards.
• Is approved for sitting rooms and/or bedrooms.
Fireplace Requirements
This insert has been tested and certified by OMNI -Test
LaboratoriestoANSIZ21.88-2005/CSA2.33-2005Standard
for Vented Gas Fireplace Heater and CGA 2.17-M91 and UL
307B Gas Burning Heating Appliances for Manufactured
(Mobile) Homes.
These heaters are designed to be installed into an existing
masonry fireplace (built to UBC 37 or ULC S628 standards)
or factory built solid fuel, wood burning fireplace (listed to
UL127orULCS610)only. Allexhaustgasesmustbevented
outsidethestructure. Combustionairisdrawnfromoutside
the structure. When installing in a factory built fireplace, the
fireplace grate must be removed and the damper must be
removed or secured open.
It has met all necessary ANSI Standards and is fully certified
for installation in any community. If there are any questions
or if you need further substantiation either write to or call
your Lennox Hearth Products dealer. If you have further
questions, please contact Lennox Hearth Products.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Inspection
Commonwealth Of Massachusetts
Requirements
The state or local gas inspector of the side wall horizontally vented gas
fueledequipmentshallnotapprovetheinstallationunless,uponinspection,
the inspector observes carbon monoxide detectors and signage installed
in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
Note: The following requirements reference various Massachusetts
and national codes not contained in this document.
Forallsidewallhorizontallyventedgasfueledequipmentinstalledinevery
dwelling, building or structure used in whole or in part for residential
purposes, including those owned or operated by the Commonwealth and
where the side wall exhaust vent termination is less than seven (7) feet
above finished grade in the area of the venting, including but not limited
to decks and porches, the following requirements shall be satisfied:
Exemptions
The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
• The equipment listed in Chapter 10 entitled “Equipment Not Required
To Be Vented” in the most current edition of ANSI Z233.1 / NFPA 54
(In Canada CAN/CSA B149.1 - current edition) as adopted by the
Board; and
Installation Of Carbon Monoxide Detectors
• Product Approved side wall horizontally vented gas fueled equipment
installed in a room or structure separate from the dwelling, building
or structure used in whole or in part for residential purposes.
At the time of installation of the side wall horizontal vented gas fueled
equipment, the installing plumber or gas-fitter shall observe that a hard
wired carbon monoxide detector with an alarm and battery back-up is
installed on the floor level where the gas equipment is to be installed.
In addition, the installing plumber or gas-fitter shall observe that a bat-
tery operated or hard wired carbon monoxide detector with an alarm is
installed on each additional level of the dwelling, building or structure
served by the side wall horizontal vented gas fueled equipment. It shall
be the responsibility of the property owner to secure the services of
qualified licensed professionals for the installation of hard wired carbon
monoxide detectors.
MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided
WhenthemanufacturerofProductApprovedsidewallhorizontallyvented
gas equipment provides a venting system design or venting system com-
ponentswiththeequipment,theinstructionsprovidedbythemanufacturer
for installation of the equipment and the venting system shall include:
In the event that the side wall horizontally vented gas fueled equipment
is installed in a crawl space or an attic, the hard wired carbon monoxide
detector with alarm and battery back-up may be installed on the next
adjacent floor level.
• Detailed instructions for the installation of the venting system design
or the venting system components; and
In the event that the requirements of this subdivision can not be met
at the time of completion of installation, the owner shall have a period
of thirty (30) days to comply with the above requirements; provided,
however,thatduringsaidthirty(30)dayperiod,abatteryoperatedcarbon
monoxide detector with an alarm shall be installed.
• A complete parts list for the venting system design or venting sys-
tem.
Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side wall horizontally
vented gas fueled equipment does not provide the parts for venting the
fluegases, butidentifies“specialventingsystems”, thefollowingrequire-
ments shall be satisfied by the manufacturer:
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accordance with the
above provisions shall comply with NFPA 720 and be ANSI/UL 2034
listed and IAS certified.
• Thereferenced“specialventingsystem”instructionsshallbeincluded
with the appliance or equipment installation instructions; and
Signage
• The “special venting systems” shall be Product Approved by the
Board, and the instructions for that system shall include a parts list
and detailed installation instructions.
A metal or plastic identification plate shall be permanently mounted to
the exterior of the building at a minimum height of eight (8) feet above
grade directly in line with the exhaust vent terminal for the horizontally
vented gas fueled heating appliance or equipment. The sign shall read, in
print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY
BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”
A copy of all installation instructions for all Product Approved side wall
horizontally vented gas fueled equipment, all venting instructions, all
parts lists for venting instructions, and/or all venting design instructions
shall remain with the appliance or equipment at the completion of the
installation.
• Installation and repair must be done by a plumber or gas fitter licensed
in the Commonwealth of Massachusetts.
• The flexible gas line connector used shall not exceed 36 inches (92
centimeters) in length.
• The individual manual shut-off must be a T-handle type valve.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
paCkaging list
Pre-Installation
To install a Ravenna™ insert, an insert body, face, surround
(flange) kit, and brick panel are required.
features
Installation Options
Manufactured (Mobile) Home
Natural Gas Or Propane (LP)
Bedrooms
Insert Body Packaging List
1 Insert Body with Burner Cassette
1 Set of Refractory Brick Panels
1 Log Set
Optional Wall-mounted Or Remote Thermostat
Electrical
1 Ravenna 40 orifice (additional clearance necessary!!!
- see clearances for Ravenna 40)
1 Bag of Embers
The standard fan motor requires 120 Volts AC for operation.
The fireplace is not dependent on the fan or an outside elec-
trical supply to operate. WARNING - Electrical Grounding
Instructions-Thisapplianceisequippedwithathree-prong
(grounding) plug for your protection against shock hazard
and should be plugged directly into a properly grounded
three-prong receptacle. Do not cut or remove the ground-
ing prong from this plug.
1 Fasteners: 6 slotted 1/4" truss screws
6 speed nuts
9 spring clips
3 plastic adhesive wire restraints
1 Installation and Operation Manual
Decorative Faces - One Required
Millivolt Valve
Traditional
Foundry
Cast pillar
Arch inset
Screen
This insert is operated with a millivolt valve and therefore
burns even during a power outage.
Fuel
Surround Kits - One Required
Traditional 1-pc. (41"W x ꢀ9"H)
This insert comes from the factory equipped to burn natural
gas at a specified elevation. The insert can be converted
to burn LP (liquid propane) by installing a conversion kit.
Only Lennox Hearth Products conversion kits can be used
to convert from NG to LP or LP to NG. Contact your Lennox
Hearth Products dealer for details.
Traditional ꢁ-pc.(41"W x ꢀ9"H, 48"W x ꢀ9"H, 41"W x
ꢁꢁ"H or 48"W x ꢁꢁ"H)
Cast Iron (45-1/ꢀ"W x ꢁ0"H-Cast Pillar face only)
Surround Kit Contents
1 Top Surround
2 Side Surrounds
3 Gold or Nickel Plated Trim Pieces
2 Elbowed Trim Fasteners
RATINGS
Ravenna 40 (RDV40)
NATURAL GAS LP GAS
40,000/ꢀ8,000 ꢁ7,500/ꢀꢂ,000 ꢁꢁ,000/ꢀ4,000 ꢁꢁ,000/ꢀ4,000
Ravenna 33 (RDV33)
NATURAL GAS
LP GAS
Max/Min Input BTUh 0-ꢀ,000 Feet
(0-ꢂ10 M)u
Manifold Pressure (IN. WC)
Min. Inlet Pressure (IN. WC)
ꢁ.5
5.0
10.0
10.5
8ꢁ%
ꢁ.5
5.0
10.0
10.5
8ꢁ%
Maximum heat output BTUs/hour-
steady state (depending on vent
configuration)v
8ꢁ%
8ꢁ%
ꢂ7.17%
1/8”
ꢂ9.07%
#49
ꢂ5.55%
#ꢁꢂ
ꢂ7.80%
#51
P4 Efficiency
w
Orifice (DMS) 0-ꢀ,000 Feet (0-ꢂ10
M)u
uUnit factory equipped for 0-ꢀ000 FT/0-ꢂ10 M, In Canada 0-4500 FT/0-1ꢁ70 M
vThe Steady State Efficiency numbers based on maximum vent configuration.
wTested to CSA P.4.1-0ꢀ “Testing Method for Measuring Annual Fireplace Efficiency.
Electrical Rating: 1ꢀ0 VAC, ꢂ0 HZ, Less Than ꢀ Amps
ꢂ
Download from Www.Somanuals.com. All Manuals Search And Download.
insert dimensions
minimum fireplaCe Cavity
31-1/4”
(794mm)
13-3/4”
(349mm)
15-3/4"
(400mm)
A
B
Top View
C
D
Figure 1
15-3/4"
(400mm)
Figure ꢁ
CAUTIONS
• The fireplace in which this gas insert is to be
installed must be thoroughly cleaned if it has
been used to burn wood or synthetic logs. Have
the chimney and all inside surfaces of the fire-
place brushed and vacuumed so that no soot,
embers, or loose combustion deposits can be
drawnintotheheatcirculationblowerandblown
into the living area.
19-1/2"
(495mm)
19-3/4
(502mm)
• Ifanyportionofthechimneysystemshowssigns
of structural or mechanical weaknesses, such
as: cracks, leaky joints, corroded or warped
surfaces, the faulty portion must be repaired
or replaced prior to installing this appliance.
• The factory built firebox must accept the insert
withoutmodificationotherthanremovingbolted
or screwed together pieces such as baffles /
smoke shelf / deflectors, ash lips, glass door,
screen or door tracks, log grates, refractory or
masonry lining and damper assemblies. Any
fireplacecomponent,whichisremoved,mustbe
retainedsotheycanbereinstalledtorestorethe
fireplace to its original operating condition. The
removal of any part must not alter the integrity
oftheoutershellofthepre-engineeredfireplace
cabinet in any way. Any parts removed must be
replaceable. If any components are removed
from (or altered) from the existing fireplace,
a Warning Label (see Page 4) must be affixed
inside the fireplace firebox, so that it shall be
visibleuponremovalofthefireplaceinsert. Note:
RTV high temperature silicone is an approved
adhesive to affix the label.
Figure ꢀ
Side View
Insert Dimensions
Width of insert behind Surround Panels
ꢀ8" (711mm)
Rear height
19-ꢁ/4" (50ꢀmm)
1ꢂ" (40ꢂmm)
Insert depth into fireplace
Flue collar diameter (OD)
ꢀ-15/1ꢂ"
ꢀ-15/1ꢂ" (75mm)
minimum fireplaCe opening required
A = 29-3/4” (756mm) Front Opening
B = 19-1/2” (495mm) Height
C = 19” (483mm) Rear Width
D = 16” (406mm) Fireplace Depth
* Top air duct will need to be removed for short ZC applica-
tions. Replace tap tights when removed.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
rdv33 faCing and mantel ClearanCes
(rdv40 - add 4" to rdv33 dimensions)
Clearances to Combustibles
WARNING: If unit is converted to an RDV40 from an
RDVꢁꢁ ensure that the clearances to combustibles are
correct for RDV40.
3"/76mm
3"/76mm
minimum ClearanCes to Combustibles
3"/76mm
Facing &
1-1/2”
38mm
E = From Top Facing or Mantel to Bottom of Insert -
.2 RDV40 = 35-1/2”(902mm) and RDV33 = 31-
1/2”(800mm)
Mantel -
Side View
F = 25-1/2" From Center of Glass Door to Side Facing or
Wall - RDV40 = 25.5”(648mm) and RDV33 = 25.5”
(648mm)
39-1/2”
1003mm
33-1/2”
851mm
J = 10.5” (267mm) Mantel to Bottom of Insert -
.2 RDV40 = 43”(1092mm) and RDV33 = 39”(991mm)
36-1/2”
927mm
31-1/2”
800mm
hearth proteCtion
G = Minimum Hearth Protection from Front of Insert*
H = Vertical Distance from Insert Bottom to Combustible
Material.
Figure 4
G
H
14”(356mm)
0”(0mm)
10”(254mm)
2”(21mm)
0”(0mm)
RDV40
RDV33
4”(102mm)
ClearanCes
G
H
13”(330mm)
0”(0mm)
10”(254mm)
2”(21mm)
0”(0mm)
Mantel
MANTEL
4”(102mm)
Trim
TRIM
F
Note: Hearth protection to be min. ꢁ/8” (10mm) thick non-
combustible or equivalent, with a k factor of .84.
J
E
C
L
insert leveling
Ateachfrontandrearcorneroftheinsertisanadjustableleg
provided to level the insert should the hearth of the fireplace
beuneven.Toadjustthelegs,loosenthetwo5/32"allenhead
screws, move the leg to the desired height, and then tighten
the screws. Repeat these steps for each adjusting leg.
H
G
Hearth / Floor Protection
Figure 5
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
The existing fireplace chimneys may take
various contours which the flexible liners will
accommodate.However,keeptheflexibleliner
as STRAIGHT as possible, avoid unnecessary
bending.
The standard cap
inTerminationKit,
H0908, is a high
wind cap
Installation
venting installation
Your Lennox™ gas insert must be vented to the outside
in accordance with the current edition of the National Fuel
Gas Code ANSI-Z223.1 (In Canada, the current CAN/CSA
B149.1installationcode). Theinsertmustnotbeconnected
to a chimney flue serving a separate solid fuel burning ap-
pliance.
Vertical Cap
Termination
Connector
This gas insert requires a 3” diameter listed flex liner. The
vent should terminate with a listed direct vent termination
cap. The chimney should be sealed around the cap to pre-
vent air and rain from entering the chimney. Adhere to the
vent manufacturer's instructions for installation and vent
termination. These appliances are approved for use with
the following vent kits.
Liner Requirements:
Use ꢁ" (7ꢂ mm) diameter listed gas
vent liner (UL1777 ONLY) for the
EXHAUST
Use ꢁ" (7ꢂ mm) diameter listed
liner (UL 181 or UL1777) for the
AIR INTAKE.
Exhaust
Vent Kits *
Vertical Height Min. = 10 ft. (ꢁ.1 M)
Vertical height Max. = ꢁ5 ft. (10.7 M)
Note: Measured from flue collar on
unit to the end of the vent pipe or liner
Intake
Cat. No.
Model
Description
H0909
FKDVI Flex Liner Kit, DVI 3” X 35’
(requires 2, one for exhaust, and one for intake)
H0908
TKDVI Termination Kit, DVI
(termination cap and flashing)
The flexible vent pipe
must NOT be allowed to
sag behind insert or in
fireplace flue.
vertiCal venting
The vent pipes must be connected to the proper collars on
the unit and the exhaust vent pipe must be connected to the
termination cap or the unit will not operate. The combustion
air vent pipe can be connected to the termination cap or it
can terminate inside the chimney.
The bottom opening of the chimney must be sealed around
the vent pipes if the combustion air vent is not connected
to the termination cap. Use unfaced fiberglass insulation to
seal around the vent pipes. The insulation may give off an
odor during the first hour of operation.
Combustion Air Intake
Figure ꢂ
Makesurethatbothlinerswillpassthroughexistingdamperarea.Remove
or lock damper to allow the passage of the flexible liners. If the damper
will not allow the passage of both liners, DO NOT PROCEED FURTHER.
(If fireplace is masonry) Consult a local mason for removal of the damper
without risk of structural damage or leakage (if the fireplace is factory
built) The appliance may NOT be installed into the fireplace.
NOTE: The minimum vertical rise (exhaust vent) is 10 feet
(3.1 M) and the maximum vertical rise is 35 feet (10.7 M).
These dimensions are measured from the starting collars
of the unit to the end of the vent pipe.
Thefireplaceandfireplacechimneymustbecleanandingood
workingorderandconstructedofnon-combustiblematerials.
Inspect chimney cleanouts for proper fit and seal.
WARNING
Donotsubstitutetheheat-ratedflexliner(UL1777)forthe
exhaustwithanyothertypelinerorafiremayresultcaus-
ing property damage, personal injury or loss of life.
*Otherapprovedventcomponentsinclude;StandardSimpsonDura-ventCo-linear
Chimney Liner Kit, Direct Vent Termination #991, Liner Termination Kit (includes
termination connector and flashing) #923GK & 3" x 35' Alum Flex #2280
9
Download from Www.Somanuals.com. All Manuals Search And Download.
zero ClearanCe fireplaCe installation
Thisinsertmaybeinstalledinamasonryorfactorybuilt/zero
clearance (ZC) fireplace. When installing in a ZC fireplace,
the ZC grate must be removed and the ZC damper must be
removed or secured open. The ZC doors, screen, refractory
ormasonrylining, baffles, andsmokeshelfmayberemoved
if necessary to install the gas insert. However, do not cut or
alter the fireplace components. The removal of any parts to
facilitateinstallationmustnotaltertheintegrityoftheinneror
outershellsofthefireplacecabinet.Anypartsremovedmust
be replaceable if the insert is taken out of the fireplace or the
fireplace clearly marked with a paint stick that "This fireplace
has been altered and is no longer safe to operate."
2 Screws
The insert is designed to fit into a ZC fireplace with a mini-
mum firebox height of 19-1/2" (495mm). To facilitate this
the hood will need to be removed and discarded (Note: the
screws should be replaced in the insert body).
Figure 7
If the factory-built fireplace has no gas access hole(s) pro-
vided, an access hole of 1-1/2" (37.5 mm) or less may be
drilled through the lower sides or bottom of the firebox in
a proper workmanship like manner. This access hole must
be plugged with a non-combustible insulation after the gas
supply line has been installed.
Rear log
Retainer
Theinstallermustmechanicallyattachthemarkingsupplied
with the gas fireplace insert to the inside of the firebox of the
fireplace into which the gas fireplace insert is installed.
Figure 8
ravenna™ 33 Conversion to ravenna 40
To convert to a Ravenna 40 gas insert, after step 1 remove
and replace the stock burner orifice with the 0.125" NG
orifice supplied in the installation manual bag. Pipe dope
or other approved gas line sealant will need to be applied
before inserting into bulkhead. The foil sticker on the light-
ing label stating RDV33 will need to be removed. RDV40
will appear underneath.
2. Place the rear brick panel on the brackets and reinstall the
log rack with the rear log. IMPORTANT!!! SCREWS PASS
THROUGH THE LOG RACK AND THE BURNER PAN.
3. Install the side brick panels by sliding them into place.
briCk panel & log set installation
1. Remove the log rack (2 screws) and install the rear log
on the retainer.
Side Brick Panels
Figure 9
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Install a light layer of rockwool directly over the ports.
- A light layer will give a more constant rear flame.
- A heavy layer will give more glow, but will need to
be adjusted after light up.
2. Install all surround panels and trim with the insert po-
sitioned in the fireplace, but a few inches in front of its
final location.
3. If an Arch face is to be installed on the insert, the sight
obstructor that comes with the face must be installed
prior to installing the surround panels. See the instruc-
tions included with the face for proper sight obstructor
installation.
4. Install the side surround panels by lining up the holes in
the tabs on the side surround panels in front of the holes
on the surround brackets. Next insert two slotted 1/4"
truss screws for each side surround panel and secure
loosely.
5. Fasten the top surround panel with the remaining two
truss screws. Tighten all six truss screws after adjusting
the surround panels to eliminate space between side and
top surround panels.
6. Assemble the surround trim by inserting the elbowed
retainer in the rectangular slot in the ends of the longest
piece of trim and secure by tightening the screw in the
retainer. Slide the mitred ends of the two side trim pieces
onto the elbowed retainer and secure by tightening the
retainer screw.
Figure 10
5. Install front logs on retainer slots.
7.Thefastenedtrimpiecesshouldnowbehorseshoeshaped.
Slide the trim down over the surround panels so the edge
of the surround panel fits just behind the rounded edge
of the trim.
8. Install three spring clips (found in parts bag in firebox)
in each piece of trim by inserting them between the rear
of the surround and the channel of the trim. The spring
clips will push the trim tight to the surround.
Figure 11
Front Logs
6. Place embers around the perimeter of the rockwool.
IMPORTANT!!! Do not cover the ports with the embers.
7. Place top log on pin.
A
Spring Handle Latches
B
C
Door Mounting Plates
Top Log
Figure 1ꢁ
faCe installation
Ports
Figure 1ꢀ
A number of different face finishes and styles are available
for your Ravenna gas insert. The Arch face comes with a
sight obstructor that must be installed prior to installing
the surround panels and face. Instructions for installing the
sight obstructor are included with the face. The faces come
with hooked brackets. To install the face, hang the hooked
brackets on the surround brackets (See C in Figure 13).
surround installation
The Ravenna™ insert surrounds are made of heavy gage
steel for durability and, if desired, for the ease of making
an inside fit in the fireplace. See Packaging List for avail-
able sizes.
Note: Gold and nickel plated surfaces must be cleaned with
glasscleanerandasoftcleanclothbeforefiringthefirsttime
or fingerprints and stains will remin permanently. NEVER
use brass polish to clean gold or nickel surfaces, this will
remove the plating!!!
1. Remove the speed nuts (A in Figure 13) from the parts
bag and install (with the flat surface forward) on the six
holes in the surround brackets - three on each side of the
insert (B in in Figure 13). A flat bladed screwdriver may
help in installing the nuts.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Gas Line Installation
Fuel
Type
Inlet Pressure
Manifold Pressure
Desired Minimum Maximum
On Hi
Fire
On Lo
Fire
After leveling, position the insert in the fireplace - holding
it about six inches out from its final location.
Natural 7" WC
Gas
5" WC
10.5" WC ꢁ.5" WC 1.7" WC
10" WC 5.4” WC
Caution: Specific hearth requirements apply (see Clear-
ances to Combustibles).
LP Gas 11" WC 10.5" WC 1ꢁ" WC
The Ravenna™ gas insert must be connected to the gas line
in accordance with local codes and/or the National Fuel Gas
Code,ANSIZ223.1(InCanada,thecurrentCAN/CSA B149.1
installation code). The insert comes with an 8" nipple at-
tached to the supply side of the gas valve. After connecting
the gas line, all joints in the line and connections at the valve
should be checked for leaks with a gas leak test solution
before final positioning of the unit.
Robertshaw Millivolt Gas Valve
TH
TP
TP/TH
The Manifold
(Outlet) Tap
Inlet (Supply)
Pressure Tap
Figure 14
gas pressure requirements
lp and natural gas supplies
A MAJOR CAUSE OF OPERATING PROBLEMS WITH GAS
APPLIANCES IS IMPROPER GAS PRESSURE!
Your Ravenna gas insert is equipped from the factory for
use with natural gas only as specified on the Safety / Listing
label attached to the appliance. This appliance can only be
operated using propane gas (LP) if a certified fuel conver-
sion kit provided by Lennox Hearth Products is installed by
a qualified service technician.
The most important item to check during the initial
installation and the first thing to check when operating
problems occur is gas pressure! This appliance will
not function properly unless the required gas pressure
is supplied. See the table on this page for gas pressure
requirements.
Also check the orifice size on the label on the igniter bracket.
It must be the correct size for the fuel and altitude.
Two pressure taps are provided on the insert's valve to
check gas pressures. The taps are located to the right of
the on/off/pilot knob (see Figure 14). The bottom tap is the
inlet (supply) pressure side. To check inlet pressure (with
the insert burning), insert a small phillips screwdriver into
the tap and turn a half turn counter-clockwise. Cover the
tap with the line from a manometer and check the pressure.
Close the tap gently but securely after completing the check.
The manifold (outlet) tap is above the inlet tap. To check
manifold pressure (with the insert burning at the high burn
setting) insert a small phillips screwdriver into the tap and
turn a half turn counter-clockwise. Cover the tap with the
line from the manometer and check the pressure. Again,
close the tap gently but securely after completing the check.
Check the taps for gas leaks with a gas leak test solution
(retighten if necessary).
Do not run propane tank dry. Running the tank dry may
cause a hazardous condition due to pressure drop in
empty tank.
Solid fuel is NOT to be used with this unit.
Air Shutter Adjustment
The Ravenna gas insert has an air shutter control lever
located behind the lower door on the insert's face and to
the left of the gas valve (see Figures 15a & 15b). The lever
is linked to the primary air shutter on the main burner. The
air shutter regulates the amount of primary air the burner
receives and therefore how clean the insert burns. The air
shutter should only be adjusted by a qualified gas techni-
cian. The insert should burn for about 15 minutes with the
logs installed before adjusting the air shutter. More air will
result in shorter flames and less color, less air will result
in bigger flames and more color. To adjust the air shutter,
insert a regular screwdriver into the slide adjustment and
slide it side to side (see Figures 15a & 15b). Caution: The
air shutter should never be set so as to make the tips of
the flames sooty or create sooting on the viewing glass,
logs, or heat exchanger. If soot begins to form after burn-
ing, the air shutter should be opened gradually until the
sooting condition stops. Gas quality and gas pressure
may vary, which can affect the burning characteristics
of the insert.
Ifthepressureisnotsufficient,makesurethegassupplyline
is large enough, the supply regulator is properly adjusted,
and the total gas load for the residence does not exceed the
amount supplied.
The appliance and its individual shut off valve must be
disconnected from the gas supply piping system during any
pressure testing of that system at test pressures in excess of
1/ꢀ psig.
The appliance must be isolated from the gas supply piping
system by closing its individual manual shut-off valve during
any pressure testing of the gas supply piping system at test
pressures equal to or less than 1/ꢀ psig. Check with your gas
supplier or plumber.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
1ꢀ
Download from Www.Somanuals.com. All Manuals Search And Download.
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS
EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROP-
ERTY DAMAGE, INJURY, OR LOSS OF LIFE.
CAUTION: HOT WHILE IN OPERATION. DO NOT TOUCH. KEEP
CHILDREN,FURNITURE,GASOLINE,ANDOTHERLIQUIDSWITH
FLAMMABLEVAPORSAWAY.NEVEROPERATEUNITWITHGLASS
OFF OR ATTEMPT TO REMOVE THE GLASS WHILE HOT.
A. This appliance is equipped with a piezo ignition device
to light the pilot. When lighting the pilot, follow these
instructions exactly.
See Detail Shutter
Adjustment
Figure 15a
B. BEFORE LIGHTING, smell around the appliance area for
gas. Be sure to smell next to the floor, because some gas
is heavier than air and will settle on the floor.
Moving shutter
WHAT TO DO IF YOU SMELL GAS:
bracket to the right
will open shutter,
to the left will close
shutter.
DO NOT try to light the appliance.
DO NOT touch any electric switch,
DO NOT use any phone in the building. Immediately call
your gas supplier from a neighbor's phone. Follow the gas
supplier'sinstructions.Ifyoucannotreachyourgassupplier,
call the fire department.
Figure 15b
Shutter Adjustment Detail
C. Use only your hand to push in or turn the gas control
knob. Never use any tool. If the knob will not push in or
turn by hand, don't try to repair it, call a qualified service
technician. Force or attempted repair may result in a fire
or explosion.
D.DONOTusethisapplianceifanyparthasbeenunderwater.
Immediately call a qualified service technician to inspect
theapplianceandtoreplaceanypartofthecontrolsystem
and any gas control which has been under water.
Operating Instructions
pre-lighting CheCklist
Be sure to check these items before the initial lighting of
the insert:
c The insert gas label corresponds to the gas supply avail-
able - that is "natural gas" for natural gas or "LP gas" for
LP gas.
c Gas pressure has been checked carefully - see Page 12.
c All gas fittings have been checked for leaks.
c All clearances to combustibles have been met-see Page 8.
c All combustible materials have been removed from the
area in front of the insert.
c All vented areas of the insert face are unobstructed.
c House is ventilated to clear initial paint curing odors - see
Page 15.
c All packaging materials have been removed from the
firebox.
c Whileinsertiscool, fingerprintsorothermarkshavebeen
cleaned from any gold or nickel surfaces with denatured
alcohol and a soft cloth. Marks left on these surfaces
may become etched into the finish if not removed prior
to burning the unit.
c Brick panels and log set have been installed.
c The glass door is in place and is properly sealed.
OPERATING INSTRUCTIONS
CAUTION: Your Lennox™ gas INSERT MUST ALWAYS BE
OPERATED WITH GLASS IN PLACE.
STOP!! Read the safety information above before pro-
ceeding.
1. Openthelowerdoor. Makesuregassupplyshut-offcocks
are open and ON/OFF rocker switch is "OFF." If equipped
with a thermostat, set it to the lowest setting.
2. Turn off all electrical power to the appliance.
3. Push in gas cock dial slightly and turn clockwise
"OFF."
to
NOTE: Dial cannot be turned from "PILOT" to "OFF" unless
dial is pushed in slightly. Do not force.
4. Wait five minutes to clear out any gas. Then smell for gas,
including near the floor. If you smell gas, STOP! Follow
"B" above. If you don't smell gas continue.
Lighting Instructions
The following is a copy of the operating and lighting instruc-
tions found with each insert:
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
1ꢁ
Download from Www.Somanuals.com. All Manuals Search And Download.
5. Locate the pilot by looking over the top of the left front
log. A blue flame will be seen when the pilot is lit.
6. Turn the gas control knob counter-clockwise
the "PILOT" position.
Robertshaw Millivolt Gas Valve
to
TH
TP
7. Push the knob all the way in and hold in that position.
Immediately light the pilot by pressing the igniter button
several times until pilot is lit. Continue to hold the knob
in for about 30 seconds after the pilot is lit. Realease
knob and it will pop back out. Pilot should remain lit. If it
goes out, repeat steps 4-8 holding knob in an additional
15 seconds after pilot is lit. If knob does not pop out
when released, stop and immediately call your service
technician or gas supplier. If the pilot will not stay lit after
several tries, turn the gas control knob to "OFF" and call
your service technician or your gas supplier.
TP/TH
GasControlKnob
(Pilot/On/Off)
FlameHeightControl
Knob(HI/LO)
PiezoIgniter
Allumeur
ON/OFFSwitch
Interrupteur
8. After pilot is lit, turn gas control knob counter-clockwise
to "ON." Knob can only be turned to "ON" if the
Gas Pilot Hood
Veilleuse à gaz
Thermopile
knob has popped out.
Igniter (electrode)
Allumeur
9. To turn burner on, turn "ON/OFF" rocker switch to "ON"
or set the thermostat to the desired temperature above
room temperature.
Thermocouple
10. Adjust the flame height (and heat output) by turning the
flame height knob clockwise
for full flame and
for reduced flame.
counter-clockwise
PILOT ASSEMBLY
Figure 1ꢂ
11. Turn on the electric power to the appliance and set the
blower to the desired air flow after it turns on when the
appliance reaches operating temperature.
Flame Color & Behavior
TO TURN OFF GAS TO APPLIANCE
Your Ravenna™ gas insert is designed for maximum heat-
ing efficiency. Therefore, upon lighting of the main burner
the flames will be semi-transparent or “bluish.” After 10-20
minutes of operation the logs will heat up and the flames
will become a yellow/orange color.
1. Turn off the "ON/OFF" rocker switch and/or thermostat (if
installed) to its lowest setting.
2. Turn off electric power to the appliance if service is to
be performed.
3. Push in gas control knob slightly and turn clockwise
to "OFF." Do not force.
Adjustingtheinserttocausetheflamestoturnorangesooner
may result in poor combustion, sooting, and a hazardous
situation. See the drawing to the right showing proper flame
appearance.
This appliance needs fresh air for safe operation and
must be installed so there are provisions for adequate
combustion and ventilation air.
Burner Flame Appearance
WARNING: Improperinstallation, adjustment, alteration,
service,ormaintenancecancauseinjuryorpropertydam-
age. For assistance or additional information, consult a
qualified installer, service agency, or your gas supplier.
Soot above
Flame Tip
Soot at
No Soot at
Flame Tip
Flame Tip
Dark Orange
Flame
Semi-Transparent
Yellow Flame
Ports on Pan
Burner Assembly
Operation of this appliance when not connected to a prop-
erly installed and maintained venting system can result in
carbon monoxide (CO) poisoning and possible death.
No Blue Flame
Center
Blue Flame
Center
PROPERLY
BURNING FLAME
IMPROPERLY
BURNING FLAME
SHUTDOWN PROCEDURE
Figure 17
To turn off the burner, turn the rocker switch to "OFF" or
adjust the thermostat (if installed) to a setting below room
temperature. The pilot will remain lit for future burner igni-
tion. For complete shutdown, see "TO TURN OFF GAS TO
APPLIANCE" above.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
14
Download from Www.Somanuals.com. All Manuals Search And Download.
Paint Curing
Blower Operation
Your Ravenna gas insert comes equipped with a 150 CFM
blower with a variable speed control and an automatic
temperature activated On/Off snap switch.
This insert has been painted with StoveBright high tem-
perature metallic stove paint. It leaves the factory dry to
the touch, but finishes curing as the insert is used. Fire
the insert four successive times for ten minutes each time
with a five minute cool down between each firing. Ventilate
the house during these first firings as the paint gives off an
unpleasant odor. It is recommended that persons sensitive
to an imbalance in the indoor air quality avoid the insert
during the curing process.
operation:
1. Plugtheblowerpowercordintoagrounded(three-prong)
outlet. This appliance is equipped with a three-prong
(grounding)plugforyourprotectionagainstshockhazard
and should be plugged directly into a properly grounded
three-prongreceptacle. Donotcutorremovetheground-
ing prong from this plug.
Quiet Operation
2. After the insert warms up, the fan will turn on if the speed
control (located at the right below the firebox) is left in
the "ON" position. The fan will not operate until the insert
is warm.
3. Once the fan turns on, turn the knob to the desired speed.
No further adjustment is necessary.
As the Ravenna™ gas insert is burning, a number of normal
operationalsoundsmaybeheard.Theflowofgasthroughthe
gas valve and orifice may make a rushing or whistling noise.
If this noise is objectionable, it can be reduced by turning
down the flame. Turning down the flame can reduce total
heat output by more than 30%. When the blower turns on,
the sound of rushing air may be heard. The blower sounds
may be reduced by adjusting the speed control located on
the blower assembly. Also, a slight clicking sound may be
heard as the gas valve or blower switch turn on and off.
4. If you do not wish to have the fan on, turn the knob until
it clicks into the "OFF" position.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
15
Download from Www.Somanuals.com. All Manuals Search And Download.
The thermostat, remote control, and rocker switch will turn
theburneronandoffindependently.Besuretosettherocker
switch to the “OFF” position when using the thermostat or
remote control and set the thermostat or remote control to
the lowest temperature when you wish to use the rocker
switch only, otherwise one may override the other. If a re-
mote thermostat is to be used with the insert, do not place
the receiver under the firebox.
operating options
The rocker switch on your Ravenna™ gas insert is used to
turn the burner on and off while the pilot is on. The rocker
switch can be installed in the hole in the right side of the
top surround panel or in the hole in the panel to the left
of the igniter button. The hole in the panel is covered by a
label which must be carefully cut out before installing the
rocker switch. The switch must be disconnected from the
coil of wire to which it is attached, the plastic nut unscrewed
from the back side of the switch, and then the switch can
be inserted into the hole at either location. If the switch is
to be located in the surround, route the wire behind the
igniter bracket and through the hole in the lower right side
oftheinsert. Attachthethreeplasticadhesivewirerestraints
(found in the bag in the firebox) to the side surround panel.
Feed the wire through these restraints and up to the switch.
Care should be taken to ensure the wire does not come in
contact with the hot surfaces of the firebox. Reconnect the
wires to the switch.
Thermostat Wire
Wire Size
1ꢀ Gage
14 Gage
1ꢂ Gage
18 Gage
ꢀ0 Gage
Maximum Length
100 Feet
ꢂ4 Feet
40 Feet
ꢀ5 Feet
1ꢂ Feet
A wall-mounted switch, a millivolt wall thermostat, or a
remote control, can be used to supplement the rocker
switch. The gas valve is powered by millivolts generated by
the pilot assembly. This millivolt system is very sensitive to
electrical resistance, therefore, make sure all connections
are tight, clean, and free from corrosion. Do not splice any
millivolt wires. Consult the table on this Page to determine
the proper gage of wire for the thermostat or wall switch
connections. This table refers to the total length of the wire
(out to the switch and back). The thermostat must be a
millivolt type. A 24-volt furnace thermostat will not work.
Never hook up household current - 120 Volts - to the mil-
livolt system. It is not recommended to hook up any more
than two switches to the insert (for example a rocker switch
and a wall thermostat). Additional switches may affect the
system resistance and increase the chance of the burner not
igniting.Followtheinstructionsincludedwiththethermostat
or remote control for wiring.
millivolt Control system
This fireplace operates on a millivolt control system. As
such, no additional power supply is needed for the fireplace
to heat. The pilot assembly contains a thermocouple, that
when heated by the pilot flame, generates electricity (mil-
livolts- mV=1/1000 of a volt) which opens a valve allowing
gas to flow to the pilot assembly. The pilot assembly also
contains a thermopile, that when heated by the pilot flame,
generates electricity that flows to terminal #1 (labeled
THTP) on the gas valve. When the electricity is conducted
from terminal #1 through the on/off switch, thermostat, or
receiver of the remote control to terminal #3 (labeled TH)
on the gas valve, the main burner will ignite.
Pilot Hood
Millivolt Control
Schematic
Sparker
Piezo Igniter
Thermocouple
Thermopile
Wiring Terminals
Pilot Assembly
TH
TP
Pilot Gas Line
TH/TP
White
Brown
Gas Inlet
ON/OFF Rocker Switch,
Thermostat, or Remote
Thermostat
Figure 18
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
1ꢂ
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance & Servicing
Millivolt and System Checks
Check
Test
To
Test
Connect
Meter
Thermostat
Connects
Meter
Reading
Should Be
maintenanCe CheCklist
Leads to
Terminals
The following should only be performed by a qualified
service technician.
A
B
Complete
System
ꢀ & ꢁ
Closed
Open
100 MV
or More
Thermopile
Output
1 & ꢀ
Greater
Than
ꢁꢀ5 MV
Caution: Label all wires prior to disconnection when
servicing controls. Wiring errors can cause improper
and dangerous operation. Verify proper operation after
C
System
ꢀ & ꢁ
Closed
ꢀ.5 Ohms
servicing.
Resistance
1.Annual inspection should be made and the following
checks performed:
proper pilot flame appearanCe
oWhen unit is cool, remove glass and inspect burner for
dirt, soot, and lint accumulations, and remove if neces-
sary. If excessive soot accumulation is present on burner,
have a qualified service technician adjust the burner for
proper combustion.
oClean inside of glass with gas fireplace glass cleaner.
NEVER attempt to remove or clean the glass when the
unit is hot.
oCheck the hot air outlet vents for lint or other accumula-
tions. Never block or restrict vent openings, obstruct flow
of ventilation air, or use vents other than those approved
for use with the Ravenna gas insert.
Figure 19
oCheck that the chimney and its outlet are open and free
of soot, blockage, or debris.
glass door Cleaning and maintenanCe
oCheckgasketsonceayear.Gasketsmustbetight.Replace
if necessary.
Cleaning: Whencool,theglassmaybecleanedwithaclean,
softclothandWindex.Forcleaningwhitecondensationfrom
the interior glass, use KEL KEM gas fireplace glass cleaner
available from your insert dealer. Use of caustic or abrasive
cleaners may damage the glass. DO NOT operate the insert
withbrokenglass. DONOTcleandoororglasswhenhot. DO
NOT abuse the glass door by striking or slamming it shut.
DO NOT use substitute materials if replacing the glass. DO
NOT spray commercial glass cleaner with ammonia on the
door and glass gasket as it may dissolve the gasket glue.
oInspectthepilotsystemforproperflame.NEVERADJUST
THE PILOT until after the gas pressure has been checked
and the supply lines have been completely bled (this may
take an hour or more when bleeding through the pilot).
All pilots are checked and burned at the factory prior to
shipment.Thepilotadjustment screwislocatedbelowthe
ON/OFF/PILOT control knob. Remove the pilot adjusting
cover with a flat-bladed screwdriver to access the pilot
adjustingscrew.Adjustthepilotscrewtoproperlysizethe
flames. The flames should directly contact the thermopile
and extend across the main burner ports. Be careful not
to back the screw out of its threads. Replace the cover
and check for gas leaks using a gas leak test solution.
Glass Replacement: The glass in the insert door cannot be
replacedseparately.Shouldtheglassbedamaged,theentire
glass, gasket, and metal frame assembly must be replaced
as a unit. This replacement glass assembly is available from
yourLennoxHearthProductsdealer.Theglassisneo-ceramic
and alternative types must not be used.
oCheck that the area around the insert is kept clear and is
free of combustible materials, gasoline, and other flam-
mable vapors and liquids.
WARNING: Do not operate appliance with the glass panel
removed, cracked, or broken. Do not remove glass door
while the insert is hot. Replacement of the glass door
should be done by a qualified service technician.
oCheck the millivolt system as per the table on this page.
ꢀ.The viewing glass should be cleaned periodically (see
Glass Maintenance).
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
17
Download from Www.Somanuals.com. All Manuals Search And Download.
fuel Conversion
glass door removal
Converting your Ravenna™ gas insert between natural gas
and LP can be accomplished by installing a conversion kit
(valve regulator and burner orifice). Only a qualified service
technician should perform the conversion.
Caution: Do not slam or strike glass door or damage
may occur.
Do not remove the glass door while the insert is hot. To re-
move the glass door, pull forward and up on the top latches.
Lift the glass door up and off the lower spring latch. Be
careful not to damage or scratch the glass while handling.
To reinstall the glass, reverse the removal steps. Do not
operate the insert with the glass removed.
Conversion kit: Please see instructions provided with
conversion kit.
blower removal
Unplugthepowersupply cordfromtheelectricaloutlet prior
to removing the blower. The fan can be accessed through
the back wall of the firebox.
Caution: Label all wires prior to disconnection when
servicing controls. Wiring errors can cause improper and
dangerousoperation. Verifyproperoperationafterservic-
ing (see the fan wiring diagram below for reference).
(A) Spring Handle Latches
(B) Door Mounting Plates
Remove the insert face, glass door, log set, and brick panels.
All of these items are fragile so handle them with care. Next,
remove the nine allen head screws around the outside of
the panel fastened to the back wall of the firebox. Rotate
the top of this panel toward the front, remove the two wires
connected to the fan, and then lift the panel with the fan at-
tached out of the firebox. To reinstall the fan, repeat these
steps in the reverse order.
Figure ꢀ0
glass door Cleaning and repair
Cleaning: Do not remove or clean the glass door when hot.
A gas door glass cleaner (available from your Lennox Hearth
Products dealer) or windex should be used with a soft cloth
to clean the glass. Do not use an abrasive cleaner.
Electrical Requirements:
This gas insert operates without an outside power source,
however the blower requires a 120 Volt electical service
outlet. Ths appliance, when installed, must be electrically
grounded in accordance with local codes, or in the absence
of local codes, the National Electrical Code ANSI/NFPA 70
- latest edition. (See Operating Options for thermostat and
ON/OFF switch information).
Repair: If the glass is broken in the glass door, the entire
door (metal frame, gasket, and glass) should be replaced
as a unit. This replacement unit is available from your Len-
nox Hearth Products dealer. Do not use substitute parts or
materials.
Caution: Do not operate this insert with broken glass.
Fan Snap Switch
Blower Wiring
Schematic
Fan Speed Control
Ground (Green)
Black (Hot)
Power Source
White (Neutral)
White
Black
Blower
Figure ꢀ1
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
18
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
NOTE: When troubleshooting the gas control system, be sure the external gas shut off valve, located at the gas sup-
ply inlet is in the “ON” position.
IMPORTANT: Call your gas supplier or plumber for additional help with any gas control problem. Valve system
troubleshooting should only be accomplished by a qualified service technician.
SYMPTOM
PROBABLE CAUSE
CORRECTIVE ACTION
Thin black coating (soot)
forms on the viewing
glass, logs, or firebox
Improper log or ember
placement
See Brick Panel and Log Set Installation on Pages 10 & 11. If there is soot in one
specific location, the rockwool below this location needs to be adjusted. This can be done
by pulling embers forward slightly. If the flames have soot tails, the shutter will need to
be opened.
Improper air shutter
setting
If sooting continues open air shutter (see Air Shutter Adjustment on Page 12 & 13)
Not enough combus-
tion air
Check for debris obstructing air flow in valve compartment under insert or in front of
lower venting.
Humming or whistling
coming from insert.
Normal operating noise See Quiet Operation on Page 15. The noise may be reduced by slightly turning down the
flame. Turning the flame down will reduce the heat output of the insert.
Obstructed orifice
opening
If noise is excessive or is “whistling” have your gas supplier check the regulator and
orifices and replace if necessary.
A change in flame appear- A change in gas pres-
ance or burner operation. sure
Have your gas supplier check for correct gas pressure (7" W.C. / po. C.E. [1.74 kPa] natu-
ral gas; 11" W.C. / po. C.E. [2.74 kPa] LP gas). NOTE: NEVER BLOCK OR OBSTRUCT AIR
INTAKE OR OUTLET VENTS.
Improper ember place-
ment
See Brick Panel and Log Set Installation on Pages 10 & 11.
Spark igniter will not light No gas supplied to unit Check gas supply. To purge, hold in gas cock on valve for 1-2 minutes and try again.
pilot after repeated tries.
or air in line
Defective igniter (no
spark at electrode)
Check for spark at electrode and pilot, if no spark and electrode wire is properly con-
nected, replace igniter and igniter wire.
Defective or misaligned Using a match, light pilot. If pilot lights, turn off pilot and trigger the igniter again. If pilot
electrode at pilot (spark lights, an intermittent gas/air supply may be the problem, if longer purge will not light
at electrode)
- check gap between electrode and pilot - should be 1/8 inch (3 mm) to have a strong
spark. If OK, replace pilot.
Pilot will not stay lit after
carefully following lighting
instructions.
Low gas inlet pressure
Defective thermopile
Check inlet pressure and adjust pilot if necessary.
Be sure wire connections from thermopile are tight at gas valve terminals.
Either rocker switch or thermostat wires may be grounded. Remove wires from valve
terminals. If pilot stays lit, trace switch wiring for a ground. May be grounded to insert or
gas supply.
Check open circuit millivolt output of thermopile. Reading should be greater than 325mV.
Also check thermopile wire for kinks that can cause loss of mV. Replace faulty thermopile
if wire is okay and reading is less than 325mV.
Defective automatic
valve operator
Turn valve knob to “ON” and thermostat (if installed) to 90º. Millivolt meter should read
greater than 100 mV. If reading is OK and burner does not turn on, replace gas valve
(qualified service technician only).
Main burner will not burn. Pilot has gone out
See Lighting Instructions.
Rocker switch, thermo- Disconnect rocker switch and thermostat wires at terminals 1 and 3 on valve. Jumper
stat, or wires defective
across from 1 to 3 with pilot lit. If burner comes on either rocker switch, thermostat, or
wiring is not functioning.
Thermopile may not be
generating sufficient
millivolts
Check thermopile with millivolt meter (see Maintenance and Servicing), recheck symp-
tom #2.
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Replacement Parts
Ravenna™ 33/40 (RDV33/40)
Part Number
Description
47500
H3045
H6010
H5922
H5938
H5939
H5941
H5924
H5963
H5926
H5971
H5925
H5929
H5927
H5972
H5433
H5434
H6013
H5875
H5655
H5744
H6007
H5745
70006
70005
71155
H5975
H5977
H5730
H5858
H2739
H5863
H5864
H7105
H5989
H5839
H5913
H5914
H5980
H5893
H5908
H5910
75169
75170
75010
Cassette Assembly NG 33,000 BTU (if LP, also requires H5433 Conversion Kit)
Cassette Assembly NG 40,000 BTU (if LP, also requires H5433 Conversion Kit)
Burner Assembly
Pilot Assembly Convertible, NG or LP
Gas Control Valve NG (if LP, also requires H5941 LP Regulator)
Regulator, NG
Regulator, LP
Orifice Main Burner #36 NG 33,000 BTU
Orifice Main Burner 1/8" NG 40,000 BTU
Orifice High Altitude Main Burner #37 NG 33,000 BTU
Orifice High Altitude Main Burner #30 NG 40,000 BTU
Orifice Main Burner #51 LP 33,000 BTU
Orifice Main Burner #49 LP 40,000 BTU
Orifice High Altitude Main Burner #52 LP 33,000 BTU
Orifice High Altitude Main Burner #53 LP 40,000 BTU
Conversion Kit, NG to LP
Conversion Kit, LP to NG
Blower W/Mounting Bracket
Blower Snap Switch
Blower Speed Control (rheostat)
On/Off Switch
On/Off Switch Wires Only
Piezo Igniter
Thermostat
AC Remote Control Thermostat
DC Remote Control Thermostat
Power Cord
Blower Wire
Speed Control Wire (for rheostat)
Log Set
Brick Panel Set
Bag of Embers (volcanic stone)
Bag of Rockwool
Firebox Door w/Glass
Hardware Package
Log Set Support
Hinge, Right, Double Door W/Screen all Faces
Hinge, Left, Double Door W/Screen all Faces
Knob Extension Kit, Robertshaw, Bay Face
Accent Trim, Gold, Traditional Face
Glass, Pillar Center
Glass Pillar Side
Knob, Gold, Set of 2
Knobs, Brushed Nickel, set of 2
Knobs, Black Nickel, set of 2
ꢀ0
Download from Www.Somanuals.com. All Manuals Search And Download.
SAFETY / LISTING LABEL
SERIAL
NO.
MODEL
Revenna™
MODÈLE
HOMOLOGUÉ FOYER RADIANT PRÉFABRIQUÉ AU GAZ - INSERTION DE FOYER AU GAZ - NE PAS
UTILISER AVEC DU COMBUSTIBLE SOLIDE
RDV
TESTÉ SELON LA NORME ANSI Z21.88-2005/CSA 2.33-2005 «FOYER RADIANT AU GAZ», UL307B, CSA P.4.1-02, ET CGA 2.17-M91.
MANUFACTURED BY / FABRIQUÉ PAR:
LENNOX HEARTH PRODUCTS
PO BOX 987
CET APPAREIL DOIT ÊTRE INSTALLÉ CONFORMÉMENT AUX EXIGENCES DES CODES RÉGIONAUX ET DU CODE D’INSTALLATION
ANSI NFPA 54-DERNIÈRE ÉDITION (ETATS-UNIS), OU CAN/CGA-B149.1-DERNIÈRE ÉDITION (CANADA). CET APPAREIL DOIT ÊTRE
INSTALLÉ SELON LES DIRECTIVES D’INSTALLATION DU FABRICANT. POUR INSTALLATION DANS DES FOYERS À COMBUSTIBLE
SOLIDE SEULEMENT - DE MAÇONNERIE OU PRÉFABRIQUÉ EN USINE. CE FOYER RADIANT AU GAZ À ÉVACUATION N’EST PAS
CONÇU POUR ÊTRE UTILISÉ AVEC DES FILTRES À AIR.
CET APPAREIL DOIT ÊTRE UTILISÉ AVEC LE TYPE DE GAZ INDIQUÉ SUR LA PLAQUE SIGNALÉTIQUE ET PEUT ÊTRE INSTALLÉ
DANS UNE MAISON PRÉUSINÉE OU DANS UNE MAISON MOBILE FIXE, LÀ OÙ LES CODES RÉGIONAUX LE PERMETTENT. VOIR LE
MANUEL D’ENTRETIEN POUR PLUS DE DÉTAILS. CET APPAREIL NE PEUT PAS ÊTRE CONVERTI POUR L’USAGE AVEC D’AUTRES
TYPES DE GAZ À MOINS D’UTILISER UNE TROUSSE DE CONVERSION HOMOLOGUÉE.
Report No. / Número de Rapport
050-S-15c-5
AUBURN, WA., USA 98071
FACTORY EQUIPPED FOR NATURAL GAS. IF CONTROL PANEL CONTRADICTS THIS LABEL, UNIT FUEL TYPE HAS BEEN CONVERTED.
CET APPAREIL EST MUNI D’ÉQUIPEMENT POUR L’USAGE DU GAZ NATUREL. SI L’ÉTIQUETTE DU PANNEAU DES COMMANDES CONTREDIT
CETTE ÉTIQUETTE, C’EST QUE LE TYPE DE CARBURANT DE CET APPAREIL A ÉTÉ CONVERTI.
LISTED VENTED GAS FIREPLACE HEATER - FIREPLACE INSERT - NOT FOR USE WITH SOLID FUEL
TESTED TO ANSI Z21.88-2005/CSA 2.33-2005 “VENTED GAS FIREPLACE HEATERS”, UL307b, CSA P.4.1-02, AND CGA 2.17-M91.
THIS APPLIANCE MUST BE INSTALLED IN ACCORDANCE WITH LOCAL CODES, IF ANY. IF NOT, FOLLOW THE CURRENT ANSI
Z223.1/NFPA 54-LATEST EDITION (USA) OR CAN/CGA B149.1-LATEST EDITION (CANADA). THIS APPLIANCE MUST BE INSTALLED
IN ACCORDANCE WITH THE MANUFACTURER’S INSTALLATION INSTRUCTION. FOR INSTALLATION IN SOLID FUEL BURNING
FIREPLACES ONLY - MASONRY OR FACTORY BUILT. THIS VENTED GAS FIREPLACE HEATER IS NOT FOR USE WITH AIR FILTERS.
THIS APPLIANCE IS ONLY FOR USE WITH THE TYPE OF GAS INDICATED ON THE RATING PLATE AND MAY BE INSTALLED IN AN
AFTERMARKET, PERMANENTLY LOCATED, MANUFACTURED (MOBILE) HOME WHERE NOT PROHIBITED BY LOCAL CODES. SEE
OWNER’S MANUAL FOR DETAILS. THIS APPLIANCE IS NOT CONVERTIBLE FOR USE WITH OTHER GASES UNLESS A CERTIFIED
KIT IS USED.
DANGER: RISK OF ELECTRICAL SHOCK. DISCONNECT POWER BEFORE SERVICING UNIT.
IF ELECTRICALLY CONNECTED, CONNECTIONS AND GROUNDING MUST BE IN ACCORDANCE WITH LOCAL CODES, IF ANY.
IF NOT, FOLLOW THE CURRENT NATIONAL ELECTRICAL CODE ANSI/NFPA 70-LATEST EDITION (USA) OR CSA C22-1-LATEST
EDITION (CANADA).
DANGER: RISQUE DE CHOC ÉLECTRIQUE. DÉBRANCHEZ L’APPAREIL AVANT D’EN FAIRE L’ENTRETIEN.
SI L’APPAREIL REQUIERT UN BRANCHEMENT ÉLETRIQUE, LES RACCORDEMENTS ET LA MISE À LA TERRE DOIVENT ÉTRE
CONFORMES AUX EXIGENCES DES CODES RÉGIONAUX ET DU CODE D’INSTALLATION ANSI/NFPA 70 OU CSA C22-1.
SPÉCIFICATIONS
Ravenna 40 (RDV40)
Ravenna 33 (RDV33)
GAZ NATUREL GAZ PROPANE GAZ NATUREL
GAZ PROPANE
33000/24000
10,0
ENTRÉE MAX/MIN BTU/HR 0-4500 pi (0-1370 M)*
PRESSION À LA SORTIE (IN. WC/C.E.)
40000/28000
37500/26000
10,0
33000/24000
3,5
5,0
3,5
5,0
PRESSION MINIMUM D’ENTRÉE DU GAZ (IN. WC/C.E.)
ORIFICE (DMS) 0-4500 pi (0-1370 M)*
10,5
10,5
1/8”
#49
#36
#51
*L’APPAREIL PRÉUSINÉ EST MUNI D’ÉQUIPEMENT POUR 0-2000 PIEDS (0-610 M). AU CANADA 0-4500 PIEDS (0-1370M).
SPÉCIFICATIONS ÉLECTRIQUE 120 VCA, 60 HZ, MOINS DE 2 AMPÈRES
RATINGS
Ravenna 40 (RDV40)
Ravenna 33 (RDV33)
CHEMINÉE - ÉVACUATION :INSTALLER AVEC DE L’ÉVENT À GAZ DE TYPE B-VENT OU UN CONDUIT FLEXIBLE À SIMPLE
PAROI HOMOLOGUÉ COMME TUBAGE.
CET APPAREIL DOIT ÊTRE RELIÉ À UN SYSTÈME D’ÉVACUATION TEL QUE SPÉCIFIÉ DANS LE MANUEL D’INSTALLATION DU
FABRICANT.
EN ALTITUDE, AU-DELÀ DE 2000 PI/610 M, (AU CANADA 0-4500 PI/0-1370M) LA CAPACITÉ ÉNERGÉTIQUE DE L’APPAREIL
DIMINUE DE QUATRE (4)% POUR CHAQUE 1000 PI (405 M).
NATURAL GAS
LP GAS
37,500/26,000
10.0
NATURAL GAS
LP GAS
33,000/24,000
10.0
MAX/MIN INPUT BTUH 0-2,000 FT (0-610 M)*
MANIFOLD PRESSURE (IN. WC)
40,000/28,000
33,000/24,000
3.5
5.0
3.5
5.0
#36
MIN. INLET PRESSURE (IN. WC)
10.5
10.5
SI LE MODÈLE RDV33 EST CONVERTI COMME MODÈLE RDV40, ASSUREZ VOUS QUE LES
DÉGAGEMENT AUX COMBUSTIBLES SONT RESPECTER SELON LE MODÈLE RDV40.
ORIFICE (DMS) 0-2,000 FT (0-610 M)*
1/8”
#49
#51
*UNIT FACTORY EQUIPPED FOR 0-2000 FT/0-610 M, IN CANADA 0-4500 FT/0-1370 M
ELECTRICAL RATING: 120 VAC, 60 HZ, LESS THAN 2 AMPS
DÉGAGEMENTS AUX COMBUSTIBLES
-
RDV40
RDV33
DÉGAGEMENTS MINIMUMS
CHIMNEY - USE WITH B-VENT CHIMNEY OR SINGLE WALL GAS VENT FLEX CHIMNEY LINER LISTED TO UL 1777 OR ULC S635.
THIS APPLIANCE MUST BE PROPERLY CONNECTED TO A VENTING SYSTEM IN ACCORDANCE WITH THE MANUFACTURER’S
INSTALLATION INSTRUCTIONS.
FOR ALTITUDES ABOVE 2,000 FT/610M (IN CANADA 4500 FT/1370M) DE-RATE THE APPLIANCE BY FOUR (4)% FOR EVERY
1,000 FT (405 M).
E
F
= Dessus du foyer à partir de la base
= Mur latéral à partir du centre du foyer
35.5”(902mm) 31.5”(800mm)
25.5”(648mm) 25.5” (648mm)
MANTEAU
DE FOYER
*J = 10.5” (267mm) manteau de foyer à partir
de la base
43”(1092mm)
39”(991mm)
F
PIÈCE DE
FINITION
*
Voir le manuel d’entretien pour les informatinos supplémentaires reliées
aux distances à respecter pour le manteau de foyer
J
E
C
L
WARNING: IF UNIT IS CONVERTED TO AN RDV40 FROM AN RDV33 ENSURE THAT THE
CLEARANCES TO COMBUSTIBLES ARE CORRECT FOR RDV40.
DIMENSIONS MINIMUMS
14”
10”
0”
G
H
DE FOYER REQUISES
(356mm) (254mm)
(0mm)
H
A = 29.75” (756mm) Ouverture avant
B = 19.50” (495mm) Hauteur
RDV40
RDV33
MINIMUM CLEARANCES TO COMBUSTIBLES
0”
2”
4”
G
MINIMUM CLEARANCES
MANTEL
RDV40
RDV33
(0mm)
(21mm) (102mm)
C = 19.00” (483mm) Largeur arrière
D = 16.00” (406mm) Profondeur du foyer
E = Top Facing to Bottom of Insert
35.5”(902mm) 31.5”(800mm)
F = Center of Glass to Side Facing or Side Wall 25.5”(648mm) 25.5” (648mm)
13”
10”
0”
TRIM
PROTECTION DU FOYER
G = Extension d’âtre min. devant
G = le foyer
H = Distance verticale de la base de
H = l’appareil aux combustibles
G
H
*J = 10.5” (267mm) Mantel to Bottom of Insert 43”(1092mm)
* See owner’s manual for additional mantel clearances and options
39”(991mm)
Note: Extension d’âtre fabriqué avec
3/8” (10mm) minimum de matériaux
non-combustible ou équivalent
possédant un facteur k de 0.84.
F
(330mm) (254mm)
(0mm)
J
0”
2”
4”
MINIMUM FIREPLACE SIZES REQUIRED
A=29.75” (756mm) Front Opening
E
(0mm)
(21mm) (102mm)
C
L
G
H
14”(356mm) 10”(254mm)
0”(0mm) 2”(21mm)
0”(0mm)
B=19.50” (495mm) Height
C=19.00” (483mm) Rear Width
D=16.00” (406mm) Fireplace Depth
RDV40
4”(102mm)
H
G
DANGER:
CET APPAREIL DÉGAGE DES TEMPÉRATURES ÉLEVÉES ET DEVRAIT ÊTRE INSTALLÉ À L’ÉCART DES
HEARTH PROTECTION
G = Minimum Hearth Protection RDV33
G = from Front of Insert
H = Vertical Distance from Insert
H = Bottom to Combustible Material
G
H
13”(330mm) 10”(254mm)
0”(0mm) 2”(21mm)
0”(0mm)
ENDROITS TRÈS PASSANTS ET LOIN DES MEUBLES ET RIDEAUX. SURVEILLEZ LES ENFANTS QUI SE TROUVENT DANS
LA PIÈCE. GARDEZ LA ZONE AUTOUR DU FOYER EXEMPTE DE MATÉRIAUX COMBUSTIBLES, D’ESSENCE ET AUTRES
VAPEURS ET LIQUIDES INFLAMMABLES. MAINTENEZ LE BRÛLEUR ET LE BOÎTIER DES COMMANDES PROPRE EN TOUT
TEMPS. VOIR LES MANUELS D’INSTALLATION ET D’ENTRETIEN QUI ACCOMPAGNENT L’APPAREIL. SEUL LE PANNEAU
VITRÉ FOURNI PAR LE MANUFACTURIER PEUT ÊTRE UTILISÉ AVEC CET APPAREIL. EN AUCUN CAS, L’APPAREIL NE
PEUT ÊTRE UTILISÉ SANS LA VITRE OU AVEC LA VITRE BRISÉE. LE REMPLACEMENT DE LA VITRE DOIT ÊTRE EFFECTUÉ
PAR UN TECHNICIEN DE SERVICE QUALIFIÉ.
4”(102mm)
Note: Hearth protection to be min. 3/8” (10mm) thick
non-combustible or equivalent, with a k factor of .84.
CAUTION:
HOT WHILE IN OPERATION. DO NOT TOUCH. SEVERE BURNS MAY RESULT. KEEP
CHILDREN, CLOTHING, FURNITURE, GASOLINE AND OTHER LIQUIDS HAVING FLAMMABLE VAPORS
AWAY. KEEP BURNER AND CONTROL COMPARTMENT CLEAN. SEE INSTALLATION AND OPERATING
INSTRUCTIONS ACCOMPANYING APPLIANCE. FOR USE WITH GLASS DOORS CERTIFIED WITH THIS
APPLIANCE ONLY. DO NOT OPERATE THE APPLIANCE WITH GLASS REMOVED, CRACKED OR BROKEN.
REPLACEMENT OF THE PANEL(S) SHOULD BE DONE BY A LICENSED OR QUALIFIED PERSON.
AVERTISSEMENT: UNE INSTALLATION INADÉQUATE DE MÊME QU’UN AJUSTEMENT, UNE MODIFICATION, UNE
RÉPARATION OU UN ENTRETIEN INCORRECTS PEUVENT CAUSER DES BLESSURES OU DOMMAGES À LA PROPRIÉTÉ.
RÉFÉREZ-VOUS AU MANUEL D’ENTRETIEN LIVRÉ AVEC CET APPAREIL. POUR DE L’ASSISTANCE, CONSULTEZ UN
INSTALLATEUR QUALIFIÉ, UNE ENTREPRISE DE SERVICE OU UN FOURNISSEUR DE GAZ.
WARNING: IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE CAN
CAUSE INJURY OR PROPERTY DAMAGE. REFER TO THE OWNER’S INFORMATION MANUAL PROVIDED
WITH THIS APPLIANCE. FOR ASSISTANCE OR ADDITIONAL INFORMATION CONSULT A QUALIFIED
INSTALLER, SERVICE AGENCY OR GAS SUPPLIER.
DATE OF MANUFACTURE / DATE DE FABRICATION
JAN
FEB MAR APR MAY JUN
JUL AUG SEP OCT NOV DEC
2007 2008 2009 2010
JANV FEVR MARS AVR MAI JUIN JUIL AOÛT SEPT OCT NOV DEC
Part No./ No. pièce #36200 Rev. A, 05/2007
IGN
DO NOT REMOVE OR COVER THIS LABEL
N’ENLEVEZ PAS OU NE COUVREZ PAS CETTE ÉTIQUETTE
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
ꢀ1
Download from Www.Somanuals.com. All Manuals Search And Download.
Lighting Label
FOR YOUR SAFETY READ BEFORE OPERATING
POUR VOTRE SÉCURITÉ, LIRE AVANT L’ALLUMAGE
WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING
PROPERTY DAMAGE, INJURY OR LOSS OF LIFE.
AVERTISSEMENT: SI VOUS NE RESPECTEZ PAS RIGOUREUSEMENT LES INSTRUCTIONS CI-DESSOUS, VOUS POURRIEZ ENCOURIR UN RISQUE D’INCENDIE ET/OU
D’EXPLOSION QUI POURRAIENT CAUSER DES DOMMANGES MATÉRIELS ET CORPORELS POUVANT ENTRAÎNER LA MORT.
CAUTION: HOT WHILE IN OPERATION. DO NOT TOUCH. KEEP CHILDREN, FURNITURE, GASOLINE AND OTHER LIQUIDS WITH
FLAMMABLE VAPORS AWAY. NEVER OPERATE UNIT WITH GLASS DOOR OFF OR ATTEMPT TO OPEN THE DOOR WHILE HOT.
DANGER: CET APPAREIL DÉGAGE DES TEMPÉRATURES ÉLEVÉES ET DEVRAIT ÊTRE INSTALLÉ À L’ÉCART DES ENDROITS TRÈS PASSANTS ET LOIN DES MEUBLES
ET RIDEAUX. GARDEZ LA ZONE AUTOUR DU FOYER EXEMPTE DE MATÉRIAUX COMBUSTIBLES, D’ESSENCE ET AUTRES VAPEURS ET LIQUIDES INFLAMMABLES.
A. This appliance is equipped with a piezo ignition device to light the pilot. When lighting the pilot, follow these instructions exactly.
A. Cet appareil utilise un système d’allumage par étincelle (allumeur Piézo-électrique) pour allumer la veilleuse. Assurez-vous de suivre
rigoureusement les instructions d’allumage de la veilleuse.
B. AVANT D’ALLUMER L’APPAREIL, assurez-vous qu’il n’y a pas d’odeur de gaz près de l’appareil ni près du sol car certains gaz plus
lourds que l’air auraient tendance à s’y accumuler en cas de fuite.
B. BEFORE LIGHTING, smell around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air
and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
•
•
•
•
DO NOT try to light the appliance.
•
•
•
•
N’ALLUMEZ aucun appareil.
DO NOT touch any electric switch; do not use any phone in the building.
Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire department.
Ne touchez aucune prise électrique; N’utilisez aucun téléphone dans votre édifice.
Sortez de la maison. À partir d’un autre endroit, appelez immédiatement votre fournisseur de gaz et suivez les directives.
S’il est impossible de joindre le distributeur du gaz, appelez les pompiers.
C. Use only your hand to push in or turn the gas control knob. Never use any tool. If the knob will not push in or turn by hand, don't try
to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
C. N’utilisez aucun outil pour tourner ou pousser le dispositif de contrôle du gaz. Si vous ne pouvez le faire manuellement, n’essayez
pas de réparer l’appareil. Appelez un technicien de service qualifié. Si vous tentez de forcer ou réparer le dispositif de contrôle du gaz
vous pourriez encourir un risque d’incendie et/ou d’explosion.
D. N’utilisez pas cet appareil si une de ses composantes a été émergée dans l’eau. Appelez immédiatement un technicien de service
qualifié et reconnu afin qu’il inspecte et remplace au besoin toutes pièces du système qui auraient été en contact avec l’eau.
D. DO NOT use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance
and to replace any part of the control system and any gas control which has been under water.
OPERATING INSTRUCTIONS
ALLUMAGE
DANGER: VOTRE APPAREIL AU GAZ LENNOX DOIT ÊTRE OPÉRÉ AVEC DES PORTES DE VERRE.
ATTENTION! Lisez les consignes de sécurité ci-dessous avant d’opérer votre appareil.
CAUTION: YOUR COUNTRY GAS APPLIANCE MUST ALWAYS BE OPERATED WITH GLASS DOOR IN PLACE.
STOP! Read the safety information above before proceeding.
Robertshaw Millivolt Gas Valve
RobertShaw Vanne Gaz Millivolt
1. Ouvrir la porte du bas. Assurez-vous que l’alimentation en gaz est
équippé d’un thermostat, placez-le à la température la plus basse.
2. Couper le courant électrique qui alimente l’appareil.
à
la position Fermée “OFF”. Si l’appareil est
1. Open the lower door. Make sure gas supply shut-off cocks are open and ON/OFF
Rocker Switch is “OFF”. If equipped with a thermostat, set it to the lowest setting.
2. Turn off all electrical power to the appliance.
TH
TP
3. Enfoncez légèrement le bouton de contrôle du gaz et tournez-le dans le sens des aiguilles d’une montre
NOTE: Le bouton de contrôle du gaz ne peut être tourné de la position “PILOT” à “OFF” sans qu’une légère pression ne soit appliquée.
4. Attendez au moins 5 minutes pour que le gaz qui se trouve dans la chambre de combustion puissse s’échapper. Si vous sentez une
odeur de gaz ARRÊTEZ! Référez-vous à la section B ci-dessus. Si vous ne sentez pas d’odeur de gaz, allez à la prochaine étape.
5. Vous localiserez la veilleuse à l'arrière et au centre du brûleur derrière la bûche centrale. Une flamme bleue est visible lorsque le veilleuse
est allumée.
à la position “OFF”.
3. Push in Gas Control Knob slightly and turn clockwise
NOTE: Knob cannot be turned from “PILOT” to “OFF” unless Knob is pushed in
slightly. Do not force.
4. Wait five (5) minutes to clear out any gas. If you smell gas, STOP! Follow “B” above.
If you don’t smell gas continue.
to “OFF”.
TP/TH
5. Locate the pilot by looking over the top of the front left log. Blue flame will be
seen when the pilot is lit.
GasControlKnob
(Pilot/On/Off)
FlameHeightControlKnob
(HI/LO)
6. Tournez le bouton de contrôle de gaz dans le sens inverse des aiguilles d’une montre
pour le placer sur “PILOT”.
6. Turn the gas control knob counterclockwise
to the “PILOT” position.
Boutondecontrôle
(Veilleuse/Ouverte/Fermée)
-LO/HI+
7. Cet appareil de chauffage est equipé d’un système d’allumage par étincelle (allumeur Piézo-électirque), devant être utilisé pour
l’allumage de la veilleuse. Poussez complètement le bouton de contrôle du gaz et le maintenir dans cette position. Appuyez
immédiatement sur le bouton (allumeur Piézo-électrique) situé à gauche du robinet de contrôle du gaz.L’étincelle produite par
l’allumeur Piézo-électrique doit allumer la veilleuse. Continuez à maintenir le bouton de contrôle dans cette position pendant environ 30
secondes après l’allumage de la veilleuse. Relâchez le bouton de contrôle du gaz qui reviendra à la position initiale. La veilleuse doit
rester allumée. Répétez les étapes 4 à 8 pendant 15 secondes supplémentaires si la veilleuse s’éteind.
(CommandeDeTailleDeFlamme)
7. Push the knob all the way in and hold in that position. Immediately light the pilot by
pressing the ignitor button several times until pilot is lit. Continue to hold the knob
in for about 30 seconds after the pilot is lit. Release knob and it will pop back out.
Pilot should remain lit. If it goes out, repeat steps 4-8 holding knob in an additional 15 seconds after
pilot is lit.
ON/OFFSwitch
Interrupteur
PiezoIgniter
Allumeur
•
•
If knob does not pop out when released, stop and immediately call your service technician or gas
supplier.
If the pilot will not stay lit after several tries, turn the gas control knob to “OFF” and call your service
technician or your gas supplier.
•
Si le bouton de contrôle du gaz ne revient pas à la position initiale une fois relâché, appeler immédiatement un technicien qualifié ou
votre distributeur de gaz.
Si la veileuse ne reste pas allumée après plusieurs essais, tournez le bouton de contrôle du gaz à la position “OFF” et appelez
immédiatement un technicien qualifié ou votre distributeur de gaz.
•
Gas Pilot Hood
Veilleuse à gaz
Thermopile
8. After pilot is lit, turn gas control counterclockwise
knob has popped out.
9. To turn burner on, turn “ON/OFF” rocker switch to “ON” or set the thermostat to the desired temperature
above room temperature.
10. Adjust the flame height (and heat output) by turning the flame height knob clockwise
flame and counterclockwise for full flame.
11. Turn on all electrical power to the appliance.
to “ON”. Knob can only be turned “ON” if the
8. Lorsque la veilleuse est allumée, tournez le bouton de contrôle du gaz dans le sens invers des aiguilles d’une montre
placer à la position “ON”. Le bouton de contrôle peut-être tourné à la position “ON” seulement si il n’est plus enfoncé.
9. Pour allumer le brûleur, mettre l’interrupteur à la position “ON” ou ajustez le thermostat à la température souhaitée.
pour le
Igniter (electrode)
Allumeur
Thermocouple
10. Ajustez la flamme et la température souhaitée en tournant le bouton de réglage de la flamme dans les sens des aiguille d’une montre
for reduced
pour l’abaisser et dans le sens contraire
pour l’augmenter.
11. Allumez l’alimentation électrique de l’appareil.
12. Ajustez le ventilateur au volume désiré lorsque l’appareil aura atteint la température de fonctionnement.
12. Set the blower to the desired air flow after it turns on when the appliance reaches operating temperature.
PILOT ASSEMBLY
POUR COUPER L’ALIMENTATION EN GAZ DE L’APPAREIL
1. Fermez l’interrupteur et/ou le thermostat «MARCHE/ARRÊT».
TO TURN OFF GAS TO APPLIANCE
1. Turn off the “ON/OFF” rocker switch and/or thermostat (if installed).
2. Coupez l’alimentation électrique de l’appareil si vous prévoyez en faire le service.
2. Turn off electric power to the appliance if service is to be performed.
3. Tournez le bouton de commande du gaz dans le sens des aiguilles d’une montre
à “OFF”. Ne le forcez pas.
3. Turn gas control knob clockwise
to "OFF". Do not force.
Cet appareil a besoin d’air frais pour opérer sécritairement et doit être installé pour qu’il y ait un apport en air suffisant. Référez-
vous aux manuels d’entretien et d’installation fournis avec l’appareil.
This appliance needs fresh air for safe operation and must be installed so there are provisions for adequate
combustion and ventilation air. See Installation and Operation Manual accompanying appliance.
AVERTISSEMENT: Une installation inadéquate, un mauvais ajustement, une altération ou toutes autres modifications
inappropriés pourraient entraîner des blessures physiques et/ou des dommanges matériels. Référez-vous au guide
d’utilisation fourni avec ce foyer. Pour assistance ou information supplémentaires contactez un installateur qualifié,
un agent de service ou un fournisseur de gaz.
Si vous opérez cet appareil sans qu’il ne soit correctement raccordé à un conduit d’évacuation, vous pourriez risquer d’être
empoisonné au monoxyde de carbone (CO) ce qui pourrait entraîner des conséquences grave ou la mort.
WARNING: Improper installation, adjustment, alteration, service or maintenance can
cause injury or property damage. For assistance or additional information, consult a
qualified installer, service agency or your gas supplier.
Operation of this appliance when not connected to a properly installed and maintained venting system can result
in carbon monoxide (CO) poisoning and possible death.
SHUTDOWN PROCEDURE
1. To turn off the burner, switch the rocker switch to “OFF” or adjust the thermostat to a setting below room temperature
(if installed). The pilot will remain lit for future burner ignition.
PROCÉDURE D’ARRÊT
1. Pour arrêter le brûleur, mettre l’interrupteur à la position “OFF” ou ajustez le thermostat à une température en dessous de la
température ambiante. La veilleuse restera allumée pour permettre un alummage ultérieur.
#36200 Rev. A, 04/07
IGN
For complete shutdown: See “TO TURN OFF GAS TO APPLIANCE” above.
Pour un arrêt complet: Consultez la procédure ci-dessus «POUR COUPER L’ALIMENTATION EN GAZ DE L’APPAREIL».
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
ꢀꢀ
Download from Www.Somanuals.com. All Manuals Search And Download.
Normally, all parts should be ordered through your Lennox distributor or
dealer. Parts will be shipped at prevailing prices at time of order.
WARRANTY
Your gas appliance is covered by a limited warranty (provided with
appliance). Please read the warranty to be familiar with its coverage.
When ordering repair parts, always give the following information:
1. The model number of the appliance.
ꢀ. The serial number of the appliance.
ꢁ. The part number.
Retain this manual. File it with your other documents for future refer-
ence.
4. The description of the part.
5. The quantity required.
PRODUCT REFERENCE INFORMATION
ꢂ. The installation date of the appliance.
We recommend that you record the following important information
about your fireplace. Please contact your Lennox Hearth Products dealer
for any questions or concerns. For the number of your nearest Lennox
Hearth Products dealer, please call 877-247-3673.
If you encounter any problems or have any questions concerning the
installation or application of this system, please contact your distributor,
or Lennox Hearth Products directly:
REPLACEMENT PARTS
LENNOX HEARTH PRODUCTS
PO Box 987
Auburn, WA 98071
See Page 20 for a complete replacement parts list. Use only parts sup-
plied from the manufacturer.
Your Fireplace Insert's Model Number___________________________________
Your Fireplace Insert’s Serial Number ___________________________________
The Date On Which Your Fireplace Insert Was Installed______________________
The Type of Gas Your Fireplace Insert Uses_______________________________
Your Dealer's Name _________________________________________________
Fuel Type (Check one)
c
Natural Gas
c
Propane Gas (LP)
�
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
ꢀꢁ
Download from Www.Somanuals.com. All Manuals Search And Download.
Lennox™ reserves the right to make changes at any time, without notice, in design,
materials, specifications, prices and also to discontinue colors, styles and products.
Consult your local distributor for fireplace code information.
Printed in U.S.A. © Lennox Hearth Products ꢀ007
1110 West Taft Avenue • Orange, CA 9ꢀ8ꢂ5
P/N 775,ꢀ18M REV. A 05/ꢀ007
Download from Www.Somanuals.com. All Manuals Search And Download.
|