Command Module and Drive
Module
Site Preparation Guide
AP1172-E1, First Edition
Download from Www.Somanuals.com. All Manuals Search And Download.
Regulatory Compliance Statements
FCC Radio Frequency Interference Statement
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to
Part 15 of the Federal Communications Commission (FCC) Rules. These limits are designed to provide
reasonable protection against harmful interference in a commercial installation. This equipment generates,
uses, and can radiate radio frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio communications. Operation of this equipment in a
residential area is likely to cause harmful interference, in which case the user will be required to correct the
interference at his own expense.
LSI Logic Corporation is not responsible for any radio or television interference caused by unauthorized
modification of this equipment or the substitution or attachment of connecting cables and equipment other
than those specified by LSI Logic Corporation. It is the user’s responsibility to correct interference caused by
such unauthorized modification, substitution, or attachment.
Laser Products Statement
This equipment has been tested and found to comply with regulations for Class 1 laser product pursuant to
21 CFR, Section 1040-10. For outside the USA, this equipment has been tested and found compliant with
Class 1 laser product requirements contained in European Normalization standard EN 60825-1 1994+A11.
Class 1 levels of laser radiation are not considered to be hazardous and are considered safe based upon
current medical knowledge. This class includes all lasers or laser systems which cannot emit levels of optical
radiation above the exposure limits for the eye under any exposure conditions inherent in the design of the
laser product.
LSI Logic Corporation is not responsible for any damage or injury caused by unauthorized modification of
this equipment or the substitution or attachment of connecting cables and equipment other than those
specified by LSI Logic Corporation. It is the user’s responsibility to correct interference caused by such
unauthorized modification, substitution, or attachment.
This Class A digital apparatus meets all requirements of the Canadian
Interference-Causing Equipment Regulations.
Cet appareil numérique de la classé A respecte toutes les exigences du
Règlement sure le matèriel brouilleur du Canada.
Command Module and Drive Module Site Preparation Guide
i
Download from Www.Somanuals.com. All Manuals Search And Download.
Revision Record
Edition or Revision
Date
Affected Pages or Remarks
First Edition
September 2002
New Book.
Part Number: AP1172-E1
ii
Command Module and Drive Module Site Preparation Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Contents
Cabinet Features........................................................................................................................... 1-2
Area Requirements....................................................................................................................... 1-4
Weights.................................................................................................................................... 1-5
Area Requirements....................................................................................................................... 2-2
Weights.................................................................................................................................... 2-2
Airflow..................................................................................................................................... 2-5
Power Cord Routing............................................................................................................... 2-8
Interface Cables and Connections............................................................................................. 2-12
Command Module and Drive Module Site Preparation Guide
iii
Download from Www.Somanuals.com. All Manuals Search And Download.
Area Requirements....................................................................................................................... 3-2
Dimensions ............................................................................................................................. 3-4
Shipping Carton Dimensions ................................................................................................ 3-5
Environmental Requirements ..................................................................................................... 3-7
Power Requirements.................................................................................................................... 3-8
Power Cord Routing............................................................................................................... 3-9
Site Wiring ............................................................................................................................ 3-12
Interface Cables and Connections............................................................................................. 3-13
FC-1 10x and FC-1 14x Drive Modules............................................................................... 3-13
FC-2 14x Drive Module........................................................................................................ 3-15
Area Requirements....................................................................................................................... 4-2
Dimensions ............................................................................................................................. 4-4
Shipping Carton Dimensions ................................................................................................ 4-5
Environmental Requirements ..................................................................................................... 4-7
Power Requirements.................................................................................................................... 4-8
Power Cord Routing............................................................................................................... 4-9
Site Wiring ............................................................................................................................ 4-11
Interface Cables and Connections............................................................................................. 4-12
iv
Command Module and Drive Module Site Preparation Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
List of Figures
Figure 1-1. 72-inch Cabinet ........................................................................................................ 1-2
Figure 1-2. Cabinet Area Requirements ..................................................................................... 1-4
Figure 1-3. Cabinet Dimensions ................................................................................................. 1-6
Figure 1-4. Cabinet AC Distribution .......................................................................................... 1-9
Figure 1-5. Cabinet Ladder Cord .............................................................................................. 1-10
Figure 1-6. Types of 72-Inch Cabinet Power Cords and Receptacles ..................................... 1-11
Figure 2-1. Command Module Dimensions .............................................................................. 2-4
Figure 2-2. Command Module Airflow ..................................................................................... 2-5
Figure 2-3. Redundant Command Module AC Power Connections ....................................... 2-9
Figure 2-4. Types of 72-Inch Cabinet AC Power Cords and Receptacles .............................. 2-10
Figure 2-5. Optical and Copper GBICs .................................................................................... 2-12
Figure 2-6. SFP Transceiver and Fiber Optic Cable ................................................................ 2-14
Figure 3-1. FC-1 10x Drive Module Dimensions ...................................................................... 3-4
Figure 3-2. FC-1 14x and FC-2 14x Drive Module Dimensions ............................................... 3-5
Figure 3-3. Drive Module Airflow .............................................................................................. 3-6
Figure 3-4. Redundant AC Power Connections to Drive Modules ........................................ 3-10
Figure 3-5. Types of 72-Inch Cabinet AC Power Cords and Receptacles .............................. 3-11
Figure 3-6. Optical and Copper GBICs .................................................................................... 3-13
Figure 3-7. SFP Transceiver and Fiber Optic Cable ................................................................ 3-15
Figure 4-1. E2400 10x Array Module Dimensions .................................................................... 4-4
Figure 4-2. E2400 14x Array Module Dimensions .................................................................... 4-5
Figure 4-3. Array Module Airflow .............................................................................................. 4-6
Figure 4-4. Redundant AC Power Connections to Array Modules .......................................... 4-9
Figure 4-5. Types of 72-Inch Cabinet AC Power Cords and Receptacles .............................. 4-10
Figure 4-6. Optical and Copper GBICs .................................................................................... 4-12
Command Module and Drive Module Site Preparation Guide
v
Download from Www.Somanuals.com. All Manuals Search And Download.
vi
Command Module and Drive Module Site Preparation Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
List of Tables
Table 1-1. Cabinet, Crate, and Module Weights ....................................................................... 1-5
Table 1-2. Cabinet Environmental Requirements ..................................................................... 1-7
Table 1-3. Power Requirements ................................................................................................. 1-8
Table 2-1. E4400 Command Module Weight ............................................................................ 2-2
Table 2-2. E4600 Command Module Weight ............................................................................ 2-3
Table 2-3. E5600 Command Module Weight ............................................................................ 2-3
Table 2-4. Command Module Shipping Carton Dimensions .................................................. 2-4
Table 2-5. Command Module Environmental Requirements .................................................. 2-6
Table 2-6. Command Module Heat Dissipation ....................................................................... 2-7
Table 2-7. Command Module Power Requirements ................................................................ 2-8
Table 2-8. E4400 Command Module Fibre Channel Interface Cables .................................. 2-13
Table 3-1. FC-1 10x Drive Module Weight ............................................................................... 3-2
Table 3-2. FC-1 14x Drive Module Weight ............................................................................... 3-3
Table 3-3. FC-2 14x Drive Module Weight ............................................................................... 3-3
Table 3-4. Drive Module Shipping Carton Dimensions ........................................................... 3-5
Table 3-5. Drive Module Environmental Requirements ........................................................... 3-7
Table 3-6. Drive Module Heat Dissipation ................................................................................ 3-7
Table 3-7. FC-1 10x Drive Module Power Requirements ......................................................... 3-8
Table 3-8. FC-1 14x Drive Module Power Requirements ......................................................... 3-8
Table 3-9. FC-2 14x Drive Module Power Requirements ......................................................... 3-9
Table 3-11. FC-2 14x Drive Module Fibre Channel Interface Cables .................................... 3-15
Command Module and Drive Module Site Preparation Guide
vii
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 4-1. E2400 10x Array Module Weight ............................................................................. 4-2
Table 4-2. E2400 14x Array Module Weight ............................................................................. 4-3
Table 4-3. Array Module Shipping Carton Dimensions ........................................................... 4-5
Table 4-4. Array Module Environmental Requirements .......................................................... 4-7
Table 4-5. Array Module Heat Dissipation ............................................................................... 4-7
Table 4-6. E2400 10x Array Module Power Requirements ...................................................... 4-8
Table 4-7. E2400 14x Array Module Power Requirements ...................................................... 4-8
viii
Command Module and Drive Module Site Preparation Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Chapter
1
72-Inch Cabinet Site Preparation
This chapter contains essential site preparation information for the 72-inch cabinet that
you will use to determine installation, service, and operating floor space requirements;
heating and air conditioning specifications; and voltage and power requirements.
Command Module and Drive Module Site Preparation Guide
1-1
Download from Www.Somanuals.com. All Manuals Search And Download.
72-Inch Cabinet Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cabinet Features
Industry Association (EIA) rails, which provide mounting holes for installing 19-inch wide
devices. The cabinet has four roller casters and four adjustable guides (located beneath the
cabinet) for moving and leveling the cabinet during installation and relocation. Newer
models of this cabinet have interface cable access holes on the top and a removable stability
foot that prevents the cabinet from tipping when it is moved.
Standard
EIA Rails
Cable Access Holes
(not available on all
models)
Roller Casters
Empty Cabinet
Removable Stability Foot
(not available on all models)
Populated Cabinet
Figure 1-1 72-inch Cabinet
1-2
Command Module and Drive Module Site Preparation Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cabinet Features
You can customize the cabinet to meet your data storage needs, based on performance,
capacity, and availability requirements. The cabinet contains two AC power distribution
boxes and can support a combination of twelve modules. The cabinet will ship with a
maximum of three command modules installed.
The command module is a rackmount unit containing two controllers, a battery,
redundant cooling fans and power supplies.
•
The array module may contain up to fourteen drives, redundant fans and power
supplies, and two controllers.
•
The drive module may contain up to fourteen drives, redundant fans and power
supplies, and an Environmental Service Module (ESM).
•
Command Module and Drive Module Site Preparation Guide
1-3
Download from Www.Somanuals.com. All Manuals Search And Download.
72-Inch Cabinet Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Area Requirements
The floor area at the installation site must provide enough stability to support the weight
of the cabinet and installed devices, sufficient space to install and service the cabinet and
components, and sufficient ventilation to provide a free flow of air to the cabinet. Airflow
Figure 1-2 Cabinet Area Requirements
1-4
Command Module and Drive Module Site Preparation Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Area Requirements
Weights
The total weight depends on the type and quantity of modules installed in the cabinet.
Use these weights to estimate the total weight of your system, based on the number of
modules installed in the cabinet.
Table 1-1 Cabinet, Crate, and Module Weights
Cabinets and Modules
Unit Weight
Cabinet
Empty
Empty
123.0 kg (270.0 lb)
Pallet and Packaging1
98.0 kg (215.0 lb)
50.8 kg (112 lb)
E2400 10x Array Module
Deskside, Low Profile (LP) drives2
Maximum
E2400 10x Array Module
Deskside, Half Height (HH) drives3
Maximum
Maximum
Maximum
Maximum
Maximum
Maximum
Maximum
Maximum
Maximum
Maximum
Maximum
54.4 kg (120.0 lb)
38.9 kg (86.4 lb)
42.3 kg (94.0 lb)
52.84 kg (116.5 lb)
40.95 kg (90.5 lb)
44.5 kg (98.0 lb)
47.8 kg (105.0 lb)
38.3 kg (84.4 lb)
41.7 kg (92.0 lb)
40.95 kg (90.5 lb)
30.87 kg (68 lb)
E2400 10x Array Module
Rackmount, LP drives
E2400 10x Array Module
Rackmount, HH drives
E2400 14x Array Module
Deskside, LP drives
E2400 14x Array Module
Rackmount, LP drives
FC-1 10x Drive Module
Deskside, LP drives
FC-1 10x Drive Module
Deskside, HH drives
FC-1 10x Drive Module
Rackmount, LP drives
FC-1 10x Drive Module
Deskside, HH drives
FC-1 14x Drive Module
Rackmount, LP drives
FC-2 14x Drive Module
Rackmount, LP drives
E4400 Command Module
Maximum
Maximum
55.6 kg (122.3 lb)
43.99 kg (97.0 lb)
E4600 or E5600 Command Module
1
Add for international shipments only
2
Low-Profile drives
3
Half-Height drives
Command Module and Drive Module Site Preparation Guide
1-5
Download from Www.Somanuals.com. All Manuals Search And Download.
72-Inch Cabinet Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dimensions
foot:
Height – 183 cm (72 in.)
•
Width – 56 cm (22 in.)
•
Depth – 91 cm (36 in.)
•
Figure 1-3 Cabinet Dimensions
1-6
Command Module and Drive Module Site Preparation Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Environmental Requirements
Environmental Requirements
Table 1-2 Cabinet Environmental Requirements
Environment
Altitude
Requirements
Operating Range
Storage Range
Transit Range
Below Sea Level
Above Sea Level
Temperature
30.5 m (100 ft.)
30.5 m (100 ft.)
30.5 m (100 ft.)
3048 m
(10,000 ft.)
3048 m
(10,000 ft.)
12,000 m
(40,000 ft.)
Operating Range
Storage Range
Transit Range
Temperature
Range
10° C to 35° C
(50° F to 104° F)
-10° C to 65° C
(140° F to 149° F)
-40° to 65° C
(-40° F to 149° F)
Temperature
Change
10° C per hour
(21° F per hour)
15° C per hour
(31° F per hour)
20° C per hour
(42° F per hour)
Relative Humidity
No Condensation
Dew Point
Operating Range
Storage Range
Transit Range
Maximum Allowed
20% to 80%
10% to 90%
5% to 95%
28° C (82° F)
10% per hour
Humidity Gradient
Noise
Steady/Non-Steady
6.8 bels
Configuration A1
Normal Operation
65 dBA
Level
Configuration B1
Configuration C1
Component
1.62 kVA
1601 W
5467 Btu/hr
3.23 kVA
3202 W
10,934 Btu/hr
2.90 kVA
2866 W
9788 Btu/hr
LP Drives2
Heat Dissipation1
1.69 kVA
1677 W
3.39 kVA
3354 W
3.02 kVA
2988 W
HH Drives2
5727 Btu/hr
11,454 Btu/hr
10,205 Btu/hr
1
These are kVA, W, and Btu calculations for three configurations containing Low-Profile (LP) and Half-Height (HH)
drives, including:
Configuration A contains 1 command module and 5 drive modules
Configuration B contains 2 command modules and 10 drive modules
Configuration C contains 3 command modules and 8 drive modules
2
LP drives are 1.0 inch tall; HH drives are 1.6 inches tall.
Command Module and Drive Module Site Preparation Guide
1-7
Download from Www.Somanuals.com. All Manuals Search And Download.
72-Inch Cabinet Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power Requirements
This section provides information regarding power requirements, AC power distribution
box specifications, ladder cord and power cord routing instructions, and site wiring
conditions.
The AC power source must provide the correct voltage, current, and frequency specified
rackmount cabinets.
Table 1-3 Power Requirements
Unit/Component
Requirements
Domestic
250 VAC, 30 A
International
230 VAC, 32 A
AC Power
AC Plug
NEMA L6-30P, locking plug
6-30R, receptacle
IEC 309 locking plug
IEC 309 receptacle
Receptacle
Circuit Breaker
Voltage Range
Frequency
25 A
180 to 257 VAC
49 to 50.5 Hz or 59 to 60.6 Hz
220 VAC, 50/60 Hz
Current
(specified frequency)
Configuration A1
Configuration B1 Configuration C1
LP Drives2
7.35 A
14.70 A
13.16 A
Operational Current
HH Drives2
LP Drives
7.70 A
10.95 A
11.45 A
15.40 A
21.90 A
22.90 A
13.72 A
22.20 A
23.00 A
Surge Current
HH Drives
1
Power specifications for three configurations containing Low-Profile (LP) and Half-Height (HH) drives, including:
Configuration A contains 1 command module and 5 drive modules
Configuration B contains 2 command modules and 10 drive modules
Configuration C contains 3 command modules and 8 drive modules
2
LP drives are 1.0 inch tall; HH drives are 1.6 inches tall.
1-8
Command Module and Drive Module Site Preparation Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Requirements
AC Power Distribution Boxes
The cabinet has two identical AC power distribution boxes with two separate power cords
or international units and includes the following features:
One domestic plug (NEMA L6-30P, 30 A, 220 VAC) or one international plug
(IEC 309, 32 A, 3-pin, 230 VAC)
•
One circuit breaker (25 A)
•
Two power outlets (IEC 320, 16 A, C-19, filtered individually for international and
domestic EMC compliance)
•
Support for up to 12 attachments per box (24 per cabinet) using two ladder cables
•
AC Power
Distribution Boxes
AC Power Distribution Box
Power Cords
Figure 1-4 Cabinet AC Distribution
Command Module and Drive Module Site Preparation Guide
1-9
Download from Www.Somanuals.com. All Manuals Search And Download.
72-Inch Cabinet Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ladder Cords
connect to a maximum of six modules. You may connect up to twelve 220/230 VAC
modules to each AC power distribution box for a maximum of twenty-four power
attachments inside the cabinet.
Although the cabinet may not be fully populated when shipped, the cabinet is shipped with
two ladder cords. Each cord has the following specifications:
Cord – 10 A per cord (1.67 A per connection if all are used)
•
Input Connector – IEC 320, C-19, 16 A, 250 VAC
•
Plugs – IEC 320, C-14, 10 A, 250 VAC
•
Ladder Step – 5.25 inches between connections
•
Cord Routing – Route cords between the mounting rails and side skins of cabinet
•
Figure 1-5 Cabinet Ladder Cord
1-10
Command Module and Drive Module Site Preparation Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Requirements
Power Cords and Receptacles
The cabinet is shipped with two power cords: one for domestic (inside USA) use, the other
for international (outside USA) use. Each power cord connects to an independent 25 A
circuit breaker and an AC power distribution box. The AC power distribution box has two
outlets for connecting the power cords from modules installed in the cabinet to an
250 VAC, 16 A, IEC 320-C19 Cord
From AC Power
Distribution Box
Independent
External
Power Source
250 VAC, 30 A, NEMA L6-30 Cord
(Domestic)
230 VAC, 32 A, IEC 309 Cord
(International)
Figure 1-6 Types of 72-Inch Cabinet Power Cords and Receptacles
Command Module and Drive Module Site Preparation Guide
1-11
Download from Www.Somanuals.com. All Manuals Search And Download.
72-Inch Cabinet Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Site Wiring
The cabinet’s AC power distribution boxes use common industrial wiring. Consider the
following information when preparing the cabinet installation site:
AC power source – The AC power source must provide the correct voltage, current, and
frequency specified on the manufacturer’s nameplate.
•
Earth ground – You must have an earth grounding conductor to the cabinet’s power
receptacles.
•
Circuit overloading – Ensure the power circuits and associated circuit breakers provide
•
sufficient power and overload protection. To prevent possible damage to the AC power
distribution boxes and other components in the cabinet, use an external, independent
power source which is isolated from large switching loads (such as air conditioning
motors, elevator motors, and factory loads).
Module power distribution – There are two accessory outlets inside the cabinet for
module power distribution. All units attached to these outlets must be auto-ranging
between 180 through 257 VAC, 50-60 Hz.
•
Power interruptions – The cabinet and its modules will withstand the following
applied voltage interruptions (with or without an integrated UPS):
•
Input transient – 50% of nominal voltage
•
Duration – one half cycle
•
Maximum frequency – once every ten seconds
•
Power failures – After a total power failure, the modules within the cabinet will
automatically perform a power-up recovery without operator intervention after power
is restored.
•
1-12
Command Module and Drive Module Site Preparation Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Chapter
2
Command Module Site Preparation
This chapter provides technical specifications and information you will need to prepare a
site before installing the E4400, E4600, and the E5600 command modules. This chapter
provides information you will use to determine installation, service, and operating floor
space requirements; heating and air conditioning specifications; voltage and power
requirements; and adapter, module, transceiver, and cabling specifications for interface
connectors.
Command Module and Drive Module Site Preparation Guide
2-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Command Module Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Area Requirements
The floor space at the installation site must provide enough strength to support the weight
of the command module and associated equipment, sufficient space to install, operate, and
service the command module, and sufficient ventilation to provide a free flow of air to the
unit.
Weights
The total weight of the command module depends on the number of components installed
Table 2-1 E4400 Command Module Weight
1
3
Maximum
Empty Unit
2
2
Shipping
Weight
Shipping
Weight
Unit
Unit Weight
Unit Weight
Rackmount Command
Module
43.99 kg (97.0 lb) 57.2 kg (125.9 lb) 16.1 kg (35.8 lb) 30.8 kg (67.8 lb)
Battery
9.7 kg (21.4 lb)
3.0 kg (6.6 lb)
0.9 kg (1.9 lb)
1.5 kg (3.3 lb)
11.8 kg (26.0 lb)
5.0 kg (11.0 lb)
2.3 kg (5.0 lb)
2.9 kg (6.5 lb)
Controller
Controller Fan
Power Supply
Not applicable.
Fan Communications
Module
1.84 kg (4.06 lb)
2.46 kg (5.44 lb)
GBIC Minihub
0.567 kg (1.25 lb) 0.712 kg (1.57 lb)
0.567 kg (1.25 lb) 0.712 kg (1.57 lb)
DB-9 Minihub
1
Maximum weight equals a command module with all canisters installed (fully loaded).
Shipping weight equals the empty or maximum weight of the command module, plus all shipping materials.
Empty weight equals a command module with all canisters removed.
2
3
2-2
Command Module and Drive Module Site Preparation Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Area Requirements
Table 2-2 E4600 Command Module Weight
1
3
Maximum
Unit Weight
Empty Unit
2
2
Unit
Rackmount
Weight
Shipping Weight
Shipping Weight
43.99 kg (97.0 lb) 57.2 kg (125.9 lb) 18.07 kg (39.84 lb)
10.89 kg (24.0 lb) 12.97 kg (28.6 lb)
30.8 kg (67.8 lb)
Command Module
Battery
Controller
3.0 kg (6.6 lb)
0.9 kg (1.9 lb)
1.5 kg (3.3 lb)
5.0 kg (11.0 lb)
2.3 kg (5.0 lb)
2.9 kg (6.5 lb)
Controller Fan
Power Supply
Not applicable.
Fan Communications
Module
1.84 kg (4.06 lb)
0.567 kg (1.25 lb)
2.9 kg (6.3 lb)
0.6 kg (1.5 lb)
SFP Minihub
1
Maximum weight equals a command module with all canisters installed (fully loaded).
2
3
Shipping weight equals the empty or maximum weight of the command module, plus all shipping materials.
Empty weight equals a command module with all canisters removed.
Table 2-3 E5600 Command Module Weight
1
3
Maximum
Unit Weight
Empty Unit
2
2
Unit
Weight
Shipping Weight
Shipping Weight
Rackmount
Command Module
43.99 kg (97.0 lb) 57.2 kg (125.9 lb) 18.07 kg (39.84 lb)
10.89 kg (24.0 lb) 12.97 kg (28.6 lb)
30.8 kg (67.8 lb)
Battery
Controller
3.0 kg (6.6 lb)
0.9 kg (1.9 lb)
1.5 kg (3.3 lb)
5.0 kg (11.0 lb)
2.3 kg (5.0 lb)
2.9 kg (6.5 lb)
Controller Fan
Power Supply
Not applicable.
Fan Communications
Module
1.84 kg (4.06 lb)
0.567 kg (1.25 lb)
2.9 kg (6.3 lb)
0.6 kg (1.5 lb)
SFP Minihub
1
Maximum weight equals a command module with all canisters installed (fully loaded).
2
3
Shipping weight equals the empty or maximum weight of the command module, plus all shipping materials.
Empty weight equals a command module with all canisters removed.
Command Module and Drive Module Site Preparation Guide
2-3
Download from Www.Somanuals.com. All Manuals Search And Download.
Command Module Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dimensions
44.5 cm (17.5 in.)
Rackmount
17.5 cm (6.9 in.)
61.0 cm (24.0 in.)
48.2 cm (19.0 in.)
2.0 cm (0.8 in.)
Figure 2-1 Command Module Dimensions
Shipping Carton Dimensions
Shipping carton dimensions include the height of the pallet and are the same for all models
Table 2-4 Command Module Shipping Carton Dimensions
Carton Height
Carton Width
Carton Depth
44.4 cm (17.5 in.)
62.2 cm (24.5 in.)
78.7 cm (31.0 in.)
2-4
Command Module and Drive Module Site Preparation Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Area Requirements
Airflow
For proper ventilation, allow at least 2 feet of clearance in front of and behind the
Back
Front
Figure 2-2 Command Module Airflow
Command Module and Drive Module Site Preparation Guide
2-5
Download from Www.Somanuals.com. All Manuals Search And Download.
Command Module Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Environmental Requirements
Table 2-5 Command Module Environmental Requirements
Requirement
Condition
Parameter
E4400
E4600
E5600
0° C to 43° C
(32° F to 109° F)
0° C to 40° C
(32° F to 104° F)
Operating Range
10° C (18° F) per hour
Maximum Rate of Change
Storage Range
-10° C to 65° C (14° F to 149° F)
15° C (27° F) per hour
Temperature
Maximum Rate of Change
-40° C to 60° C
-40° C to 65° C
(-40° F to 149° F)
Transit Range
(-40° F to 140°
F)
20° C (36° F) per hour
20% to 80%
10% to 93%
Maximum Rate of Change
Operating Range
Storage Range
10% to 90%
Relative Humidity
No condensation
Transit Range
5% to 95%
26° C (79° F)
10% per hour
6.5 bels
Maximum Dew Point
Maximum Gradient
Sound Power
Sound
Sound Pressure
65 dBA
3000 m (9840
ft.)
Operating and Storage
Transit
3048 (10,000 ft.)
Altitude
(Above Sea Level)1
12,000 m (40,000 ft.)
30.5 m (100 ft.)
Altitude
(Below Sea Level)
Operating, Storage,
and Transit
1
If you plan to operate a command module at altitudes between 1000 m to 3000 m (3280 ft. to 9850 ft.) above sea level,
lower the environmental temperature 1.7° C (3.3° F) for every 1000 m (3280 ft.) above sea level.
2-6
Command Module and Drive Module Site Preparation Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Environmental Requirements
Table 2-6 Command Module Heat Dissipation
Model
E4400
E4600
E5600
Heat Dissipation
657.5 Btu/hr (0.1925 kVA or 192.5 W)
790.0 Btu/hr (0.2333 kVA or 231.0 W)
786.6 Btu/hr (0.2300 kVA or 230.0 W)
Command Module and Drive Module Site Preparation Guide
2-7
Download from Www.Somanuals.com. All Manuals Search And Download.
Command Module Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power Requirements
This section provides information regarding command module AC power requirements,
power cord routing instructions, and site wiring conditions.
The AC power source must provide the correct voltage, current, and frequency specified
on the manufacturer’s nameplate. Internal AC power units for rackmount cabinets must
Table 2-7 Command Module Power Requirements
Item
Unit of Measure
Slow-blow Fuse
Nominal Voltage
Frequency
Requirement
3 A per Power Supply
90 to 264 VAC
Circuit Breaker
50 to 60 Hz
AC Power
1 A1
2 A1
Operating Current
Maximum Surge Current
1
Typical current at 240 VAC, 60 Hz at 0.70 power efficiency, 0.99 power factor.
Power Cord Routing
All modules are shipped with two AC power cords that are appropriate for use in a typical
outlet in the destination country. Each power cord connects one of the power supplies in a
module to an independent, external power source, such as a wall receptacle or
uninterruptible power supply (UPS). If you have a rackmount cabinet with internal power
cabling, such as a ladder cable, you do not need these power cords.
A rackmount cabinet can have up to two AC power distribution boxes with separate power
independent, external power source. Each AC power distribution box has a ladder cable
that runs up the inside of the cabinet and connects to one of the power supplies in each
module.
Figure 2-4 on page 2-10 shows the power cords and receptacles for domestic (inside USA)
and international use (outside USA).
2-8
Command Module and Drive Module Site Preparation Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Requirements
Ladder Cord Connector
Ladder Cord
Command Module Power Supplies
AC Power
Distribution Boxes
AC Power Distribution Box
Power Cords
Figure 2-3 Redundant Command Module AC Power Connections
Command Module and Drive Module Site Preparation Guide
2-9
Download from Www.Somanuals.com. All Manuals Search And Download.
Command Module Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
250 VAC, 16 A, IEC 320-C19 Cord
From AC Power
Distribution Box
Independent
External
Power Source
250 VAC, 30 A, NEMA L6-30 Cord
(Domestic)
230 VAC, 32 A, IEC 309 Cord
(International)
Figure 2-4 Types of 72-Inch Cabinet AC Power Cords and Receptacles
2-10
Command Module and Drive Module Site Preparation Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Requirements
Site Wiring
The command module uses wide-ranging, redundant power supplies that automatically
accommodate voltages to the AC power source. The power supplies operate at a range
between 90 VAC and 264 VAC, and at a minimum frequency of 50 Hz and a maximum
frequency of 60 Hz. The power supplies meet standard voltage requirements for both
domestic (inside USA) and international (outside USA) operation. They use standard
industrial wiring with line-to-neutral or line-to-line power connections.
Consider the following information when preparing the command module installation
site:
Earth ground – The unit must be properly grounded, including an earth ground
conductor on the AC power source.
•
Circuit overloading – Ensure the power circuits and associated circuit breakers in the
•
cabinet and building provide sufficient power and overload protection. To prevent
possible damage to the unit, isolate its power source from large switching loads (such as
air conditioning motors, elevator motors, and factory loads).
Power interruptions – The command modules will withstand the following applied
voltage interruptions (with or without an integrated UPS):
•
Input transient – 50% of nominal voltage
•
Duration – one half cycle
•
Frequency – once every 10 seconds
•
Power failures – After a total power failure, the unit will automatically perform a
power-up recovery sequence without operator intervention after power is restored.
•
Command Module and Drive Module Site Preparation Guide
2-11
Download from Www.Somanuals.com. All Manuals Search And Download.
Command Module Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Interface Cables and Connections
This section provides information about command module interface cables, such as GBIC
Figure 2-6 on page 2-14 for command module interface connector examples.
E4400 Command Module
The E4400 command module supports Fibre Channel connections to both hosts and drive
modules. Up to four host minihubs and four drive minihubs, for a maximum of eight
connections, can be installed in each command module. The E4400 supports two types of
minihubs:
GBIC minihub – contains a pair of connectors for attaching either of the following:
•
Optical GBIC module – used with fiber optic cable
•
Copper GBIC module – used with copper fiber cable
•
DB-9 minihub – contains a pair of DB-9 connectors for attaching copper fiber cable
•
Fiber Optic or
Copper Fiber Cable
GBIC Module
Copper Fiber Cable
DB-9 Connector
Figure 2-5 Optical and Copper GBICs
2-12
Command Module and Drive Module Site Preparation Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Interface Cables and Connections
If you order optical GBIC connectors, you will need fiber optic cable. If you order copper
types and cable lengths available from your local dealer.
Table 2-8 E4400 Command Module Fibre Channel Interface Cables
Descriptions
Data Rate
Order Information
Part
Transfer
Speed
Maximum
Range
Cable
Length
Number
006-1086672
006-1086416
006-1086673
006-1086417
006-1086682
006-1086672
006-1086483
006-1086473
2 meter
3 meter
5 meter
10 meter
2 meter
3 meter
5 meter
10 meter
Fiber optic
Multimode, 50micrometer,
shortwave laser
100 MB/s
100 MB/s
1062.5 Mb/s 0.5 kilometer
Copper fiber
Shielded, twisted pair,
electrical signal
1062.5 Mb/s
30 meters
Command Module and Drive Module Site Preparation Guide
2-13
Download from Www.Somanuals.com. All Manuals Search And Download.
Command Module Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
E4600 and E5600 Command Modules
The E4600 and E5600 command modules support fiber optic connections to both hosts
and drive modules. Up to four host minihubs and four drive minihubs can be installed in a
command module. Each Small Form-factor Pluggable (SFP) minihub has two connectors,
one end of the fiber optic cable and plugs into the SFP minihub, which is connected to the
command module. The other end of the cable connects to an optical GBIC module in the
drive module.
SFP Transceiver
Fiber Optic Cable
Figure 2-6 SFP Transceiver and Fiber Optic Cable
local dealer.
Table 2-9 E4600 Command Module Fibre Channel Host and Drive Interface Cables
Descriptions
Data Rate
Order Information
Transfer
Speed
Cable
Maximum
Part Number
Length
006-1086713
006-1086714
006-1086715
006-1086716
006-1086717
006-1086718
006-1086723
006-1086724
006-1086725
006-1086726
006-1086727
006-1086728
2 meter
3 meter
5 meter
10 meter
25 meter
50 meter
2 meter
3 meter
5 meter
10 meter
25 meter
50 meter
Fiber optic
50/125UM LC/LC
At least
200 MB/s
At least
2125 Mb/s
.03 kilometer
Fiber optic
50/125UM SC/LC
100 MB/s
1062.5 Mb/s 0.5 kilometer
2-14
Command Module and Drive Module Site Preparation Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Interface Cables and Connections
Table 2-10 E5600 Command Module Fibre Channel Host and Drive Interface Cables
Descriptions
Data Rate
Order Information
Transfer
Speed
Part
Cable
Maximum
Length
Number
006-1086713
006-1086714
006-1086715
006-1086716
006-1086717
006-1086718
2 meter
3 meter
5 meter
10 meter
25 meter
50 meter
Fiber optic
50/125 um LC/LC
At least
200 MB/s
At least
2125 Mb/s
300
kilometer
Command Module and Drive Module Site Preparation Guide
2-15
Download from Www.Somanuals.com. All Manuals Search And Download.
Command Module Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-16
Command Module and Drive Module Site Preparation Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Chapter
3
Drive Module Site Preparation
This chapter provides technical specifications and information you will need to prepare a
site before installing a FC-1 10x, FC-1 14x, or FC-2 14x drive module. This chapter
provides information you will use to determine installation, service, and operating floor
space requirements; heating and air conditioning specifications; voltage and power
requirements; and adapter, module, transceiver, and cabling specifications for interface
connectors.
Command Module and Drive Module Site Preparation Guide
3-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Drive Module Site Preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Area Requirements
The floor space at the installation site must provide enough strength to support the weight
of the drive module and associated equipment, sufficient space to install, operate, and
service the drive module, and sufficient ventilation to provide a free flow of air to the unit.
Weights
The total weight of the drive module depends on the number of components installed
Table 3-1 FC-1 10x Drive Module Weight
Weight
1
2
3
Unit
Maximum Unit
Empty Unit
Shipping
Drive Module
Deskside Low Profile (LP) drives4
44.5 kg (98.0 lb)
23.6 kg (52.0 lb)
59.0 kg (130.0 lb)
Drive Module
Deskside Half Height (HH) drives5
47.8 kg (105.0 lb)
38.3 kg (84.4 lb)
41.7 kg (92.0 lb)
23.6 kg (52.0 lb)
12.7 kg (28.0 lb)
12.7 kg (28.0 lb)
62.4 kg (137.0 lb)
43.5 kg (96.0 lb)
47.0 kg (103.6 lb)
Drive Module
Rackmount LP drives
Drive Module
Rackmount HH drives
LP Drive, 18 GB or 36 GB
HH Drive, 36 GB or 73 GB
ESM
1.06 kg (2.34 lb)
1.4 kg (3.08 lb)
1.7 kg (3.8 lb)
2.3 kg (5.0 lb)
1.0 kg (2.3 lb)
Not applicable.
Power Supply
Fan
1
Maximum weight equals a drive module with all canisters installed (fully loaded).
Empty weight equals a drive module with all canisters removed.
2
3
4
5
Shipping weight equals the maximum weight of the drive module, plus all shipping material.
Low-Profile drives.
Half-Height drives.
3-2
Command Module and Drive Module Site Preparation Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Area Requirements
Table 3-2 FC-1 14x Drive Module Weight
Weight
3
Unit
Maximum Unit
Shipping
Drive Module
Rackmount Low Profile (LP) drives
40.95 kg (90.5 lb)1
47.25 kg (105.0 lb)
Drive Module
Drive-ready Rackmount LP drives
30.5 kg (66.4 lb)2
37.44 kg (83.2 lb)
LP Drive, 18 GB or 36 GB
LP Drive, Blank Canisters
ESM
1.0 kg (2.2 lb)
0.32 kg (0.72 lb)
1.67 kg (3.7 lb)
2.49 kg (5.5 lb)
1.0 kg (2.2 lb)
Power Supply
Fan
1
Maximum weight equals a drive module with all canisters installed (fully loaded).
2
3
Drive-ready weight equals a drive module with all canisters installed and blank drives (empty).
Shipping weight equals the maximum or drive-ready weight of the drive module, plus all shipping material.
Table 3-3 FC-2 14x Drive Module Weight
Weight
3
Unit
Maximum Unit
Shipping
Drive Module
Rackmount Low Profile (LP) drives
41.77 kg (92 lb)1
53.57 kg (118 lb)
42.68 kg (94 lb)
Drive Module
Drive-ready Rackmount LP drives
30.87 kg (68 lb)2
LP Drive, 18 GB or 36 GB
LP Drive, 73 GB
LP Drive, Blank Canisters
ESM
1.0 kg (2.2 lb)
1.12 kg (2.46 lb)
0.32 kg (0.72 lb)
1.59 kg (3.7 lb)
2.45 kg (5.39 lb)
1.01 kg (2.23 lb)
0.78 kg (1.72 lb)
2.04 kg (4.5 lb)
3.56 kg (7.39 lb)
1.92 kg (4.23 lb)
Power Supply
Fan
1
Maximum weight equals a drive module with all canisters installed (fully loaded).
2
3
Drive-ready weight equals a drive module with all canisters installed and blank drives (empty).
Shipping weight equals the maximum or drive-ready weight of the drive module, plus all shipping material.
Command Module and Drive Module Site Preparation Guide
3-3
Download from Www.Somanuals.com. All Manuals Search And Download.
Drive Module Site Preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dimensions
model descriptions.
16.6 cm (6.5 in.)
52.7 cm (20.7 in.)
56.0 cm (22.0 in.)
44.7 cm (17.6 in.)
12.9 cm (5.08 in.)
13.18 cm (5.2 in.)
55.91 cm (22.0 in.)
48.0 cm (18.9 in.)
1.59 cm (0.625 in.)
Figure 3-1 FC-1 10x Drive Module Dimensions
3-4
Command Module and Drive Module Site Preparation Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Area Requirements
44.70 cm (17.60 in)
59.74 cm (23.52 in.)
12.9 cm
(5.08 in.)
13.23 cm
(5.21 in.)
56.13 cm (22.1 in.)
48.18 cm (18.97 in.)
3.63 cm (1.43 in.)
Figure 3-2 FC-1 14x and FC-2 14x Drive Module Dimensions
Shipping Carton Dimensions
Table 3-4 Drive Module Shipping Carton Dimensions
Model
Carton Height
Carton Width
Carton Depth
FC-1 10x
FC-1 14x and FC-2 14x
38.1 cm (15.0 in.)
61.4 cm (24.0 in.)
83.2 cm (32.7 in.)
44.45 cm (17.5 in.) 62.23 cm (24.5 in.) 74.93 cm (29.5 in.)
Command Module and Drive Module Site Preparation Guide
3-5
Download from Www.Somanuals.com. All Manuals Search And Download.
Drive Module Site Preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Airflow
For proper ventilation, allow at least 2 feet of clearance in front of and behind the drive
Deskside
Back
Front
Rackmount
Figure 3-3 Drive Module Airflow
3-6
Command Module and Drive Module Site Preparation Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Environmental Requirements
Environmental Requirements
Table 3-5 Drive Module Environmental Requirements
Requirement
Condition
Parameter
Operating Range
FC-1 10x, FC-1 14x, and FC-2 14x
10° C to 40° C (50° F to 104° F)
10° C (18° F) per hour
Maximum Rate of Change
Storage Range
-10° C to 50° C (14° F to 122° F)
15° C (27° F) per hour
Temperature
Maximum Rate of Change
Transit Range
-40° C to 60° C (-40° F to 140° F)
20° C (36° F) per hour
20% to 80%
Maximum Rate of Change
Operating Range
Storage Range
10% to 90%
Relative Humidity
No condensation
Transit Range
5% to 95%
26° C (79° F)
10% per hour
6.0 bels
Maximum Dew Point
Maximum Gradient
Sound Power
Sound
Sound Pressure
60 dBA
Operating and Storage
Transit
3000 m (9840 ft.)
12,000 m (40,000 ft.)
Altitude
(Above Sea Level)1
Altitude
(Below Sea Level)
Operating, Storage, and Transit
30.5 m (100 ft.)
1
If you plan to operate a drive module at altitudes between 1000 m to 3000 m (3280 ft. to 9850 ft.) above sea level,
lower the environmental temperature 1.7° C (3.3° F) for every 1000 m (3280 ft.) above sea level.
Table 3-6 Drive Module Heat Dissipation
Low Profile (LP)
18 GB and 36 GB Drives
Half Height (HH)
36 GB and 73 GB Drives
Model
FC-1 10x
1036 Btu/hr (0.306 kVA or 303 W)
1050 Btu/hr (0.309 kVA or 306 W)
1084 Btu/hr (0.320 kVA or 317 W)
1070 Btu/hr (0.33 kVA or 313 W)
Not applicable.
FC-1 14x
FC-2 14x
Not applicable.
Command Module and Drive Module Site Preparation Guide
3-7
Download from Www.Somanuals.com. All Manuals Search And Download.
Drive Module Site Preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power Requirements
This section provides information regarding drive module AC power requirements, power
cord routing instructions, and site wiring conditions.
The AC power source must provide the correct voltage, current, and frequency specified
on the manufacturer’s nameplate. Internal AC power units for rackmount cabinets must
Table 3-7 FC-1 10x Drive Module Power Requirements
Item
Unit of Measure
Slow-blow Fuse
Requirement
Circuit Breaker
10 A per Power Supply
Low Range
High Range
198 to 264 VAC
50 to 60 Hz
Nominal Voltage
Frequency
90 to 136 VAC
50 to 60 Hz
3.02 A
1.31 A1
1.34 A1
AC Power
Idle Current
Maximum Operating Current
3.11 A
4.70 A
Maximum Surge Current
(10-drive spin up)
1.92 A1
1
Typical current: 240 VAC, 60 Hz at 0.70 power efficiency, 0.99 power factor.
Table 3-8 FC-1 14x Drive Module Power Requirements
Item
Unit of Measure
Slow-blow Fuse
Requirement
10 A per Power Supply
Circuit Breaker
Low Range
High Range
198 to 264 VAC
50 to 60 Hz
Nominal Voltage
Frequency
90 to 136 VAC
50 to 60 Hz
2.95 A1
3.03 A1
1.42 A2
1.46 A2
Idle Current
AC Power
Maximum Operating Current
Maximum Surge Current
(14-drive spin up)
4.28 A1
1.97 A2
1
Typical current: 115 V AC, 60 Hz at 0.72 power efficiency, 0.99 power factor.
Typical current: 230 V AC, 60 Hz at 0.72 power efficiency, 0.99 power factor.
2
3-8
Command Module and Drive Module Site Preparation Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Requirements
Table 3-9 FC-2 14x Drive Module Power Requirements
Item
Unit of Measure
Requirement
Circuit Breaker Slow-blow Fuse
10 A per Power Supply
Low Range
High Range
198 to 264 VAC
50 to 60 Hz
Nominal Voltage
Frequency
90 to 136 VAC
50 to 60 Hz
AC Power
2.93 A1
3.18 A1
5.85 A1
1.27 A2
1.37 A2
2.36 A2
Idle Current
Maximum Operating Current
Maximum Surge Current
1
2
Typical current: 100 V AC, 60 Hz at 0.73 power efficiency, 0.99 power factor.
Typical current: 240 V AC, 60 Hz at 0.73 power efficiency, 0.99 power factor.
Power Cord Routing
All modules are shipped with two AC power cords that are appropriate for use in a typical
outlet in the destination country. Each power cord connects one of the power supplies in a
module to an independent, external power source, such as a wall receptacle or
uninterruptible power supply (UPS). If you have a rackmount cabinet with internal power
cabling, such as a ladder cable, you do not need these power cords.
Typically, a rackmount cabinet has two AC power distribution boxes with separate power
independent, external power source. Each AC power distribution box has a ladder cable
that runs up the inside of the cabinet and connects to one of the power supplies in each
module.
Figure 3-5 on page 3-11 shows the power cords and receptacles for domestic and
international use.
Command Module and Drive Module Site Preparation Guide
3-9
Download from Www.Somanuals.com. All Manuals Search And Download.
Drive Module Site Preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Drive Module Power Supplies
Ladder Cord Connector
Ladder Cord
AC Power
Distribution Boxes
AC Power Distribution Box
Power Cords
Figure 3-4 Redundant AC Power Connections to Drive Modules
3-10
Command Module and Drive Module Site Preparation Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Requirements
250 VAC, 16 A, IEC 320-C19 Cord
From AC Power
Distribution Box
Independent
External
Power Source
250 VAC, 30 A, NEMA L6-30 Cord
(Domestic)
230 VAC, 32 A, IEC 309 Cord
(International)
Figure 3-5 Types of 72-Inch Cabinet AC Power Cords and Receptacles
Command Module and Drive Module Site Preparation Guide
3-11
Download from Www.Somanuals.com. All Manuals Search And Download.
Drive Module Site Preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Site Wiring
The drive modules use wide-ranging, redundant power supplies that automatically
accommodate voltages to the AC power source. The power supplies operate at a range
between 90 VAC and 264 VAC, and at a minimum frequency of 50 Hz and a maximum
frequency of 60 Hz. The power supplies meet standard voltage requirements for both
domestic (inside USA) and international (outside USA) operation. They use standard
industrial wiring with line-to-neutral or line-to-line power connections.
Consider the following information when preparing the drive module installation site:
Earth ground – The unit must be properly grounded, including an earth ground
conductor on the AC power source.
•
Circuit overloading – Ensure the power circuits and associated circuit breakers in the
•
cabinet and building provide sufficient power and overload protection. To prevent
possible damage to the unit, isolate its power source from large switching loads (such as
air conditioning motors, elevator motors, and factory loads).
Power interruptions – The drive modules will withstand the following applied voltage
interruptions (with or without an integrated UPS):
•
Input transient – 50% of nominal voltage
•
Duration – one half cycle
•
Frequency – once every 10 seconds
•
Power failures – After a total power failure, the unit will automatically perform a
power-up recovery sequence without operator intervention after power is restored.
•
3-12
Command Module and Drive Module Site Preparation Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Interface Cables and Connections
Interface Cables and Connections
This section provides information about drive module interface cables, such as GBIC
modules and SFP transceivers, and their appropriate connections.
FC-1 10x and FC-1 14x Drive Modules
The FC-1 10x and FC-1 14x drive modules support Fibre Channel connections to
modules may be fiber optic or copper. The module type depends on what type of drive
interface you ordered and what type of cable you will be using to attach the drive module
to the command module.
Copper Fiber Drive
Interface Cable
Fiber Optic Host
Interface Cable
Optical GBIC Module
Copper GBIC Module
Figure 3-6 Optical and Copper GBICs
Command Module and Drive Module Site Preparation Guide
3-13
Download from Www.Somanuals.com. All Manuals Search And Download.
Drive Module Site Preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
If you order optical GBIC modules, you will need fiber optic cable. If you order copper
lengths available from your local dealer.
Table 3-10 FC-1 10x and FC-1 14x Drive Module Fibre Channel Interface Cables
Descriptions
Data Rate
Order Information
Part
Transfer
Speed
Maximum
Range
Cable
Length
Number
006-1086672
006-1086416
006-1086673
006-1086417
006-1086682
006-1086672
006-1086483
006-1086473
006-1086723
006-1086724
006-1086725
006-1086726
006-1086727
006-1086728
2 meter
3 meter
5 meter
10 meter
2 meter
3 meter
5 meter
10 meter
2 meter
3 meter
5 meter
10 meter
25 meter
50 meter
Fiber optic
Multi-mode, 50 micrometer,
shortwave laser
0.5
kilometer
100 MB/s
100 MB/s
1062.5 Mb/s
1062.5 Mb/s
Copper fiber
Shielded, twisted pair,
electrical signal
30 meters
Fiber optic
50/125UM SC/LC
0.5
kilometer
100 MB/s
1062.5 Mb/s
3-14
Command Module and Drive Module Site Preparation Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Interface Cables and Connections
FC-2 14x Drive Module
The FC-2 14x drive module supports Fibre Channel connections to command modules.
The drive module ships with two ESMs, and each has connectors for two optical Small
SFP Transceiver
Fiber Optic Cable
Figure 3-7 SFP Transceiver and Fiber Optic Cable
interface connector cable lengths available from your local dealer.
Table 3-11 FC-2 14x Drive Module Fibre Channel Interface Cables
Descriptions
Data Rate
Order Information
Part
Transfer
Speed
Maximum
Range
Cable
Length
Number
006-1086713
006-1086714
006-1086715
006-1086716
2 meter
3 meter
5 meter
10 meter
Fiber optic
50/125UM LC/LC
At least
200 MB/s
At least
2125 Mb/s
0.3 kilometer
Command Module and Drive Module Site Preparation Guide
3-15
Download from Www.Somanuals.com. All Manuals Search And Download.
Drive Module Site Preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-16
Command Module and Drive Module Site Preparation Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Chapter
4
Array Module Site Preparation
This chapter provides technical specifications and information you will need to prepare a
site before installing the E2400 10x and E2400 14x array modules. This chapter provides
information you will use to determine installation, service, and operating floor space
requirements; heating and air conditioning specifications; voltage and power
requirements; and adapter, module, transceiver, and cabling specifications for interface
connectors.
Command Module and Drive Module Site Preparation Guide
4-1
Download from Www.Somanuals.com. All Manuals Search And Download.
Array Module Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Area Requirements
The floor space at the installation site must provide enough strength to support the weight
of the array module and associated equipment, sufficient space to install, operate, and
service the array module, and sufficient ventilation to provide a free flow of air to the unit.
Weights
The total weight of the array module depends on the number of components installed.
Table 4-1 E2400 10x Array Module Weight
Weight
1
2
3
Unit
Maximum Unit
Empty Unit
Shipping
Array Module
Deskside, Low Profile (LP) drives
50.8 kg (112 lb)
23.6 kg (52.0 lb)
23.6 kg (52.0 lb)
17.8 kg (39.2 lb)
17.8 kg (39.2 lb)
59.0 kg (130.1 lb)
62.6 kg (138.1 lb)
44.1 kg (98.0 lb)
47.5 kg (105.6 lb)
Array Module
Deskside, Half Height (HH) drives
54.4 kg (120.0 lb)
38.9 kg (86.4 lb)
42.3 kg (94.0 lb)
Array Module
Rackmount, LP drives
Array Module
Rackmount, HH drives
LP Drive, 18 GB or 36 GB
HH Drive, 36 GB or 73 GB
Controller
1.06 kg (2.34 lb)
1.4 kg (3.08 lb)
2.2 kg (4.8 lb)
2.3 kg (5.0 lb)
1.0 kg (2.3 lb)
Power Supply
Fan
1
Maximum weight equals an array module with all canisters installed (fully loaded).
Empty weight equals an array module with all canisters removed.
2
3
Shipping weight equals the maximum weight of the array module, plus all shipping materials.
4-2
Command Module and Drive Module Site Preparation Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Area Requirements
Table 4-2 E2400 14x Array Module Weight
Weight
1
2
3
Unit
Maximum Unit
Empty Unit
Shipping
Array Module
Deskside, Low Profile (LP) drives,
18 GB or 36 GB
52.84 kg (116.5 lb) 27.0 kg (59.54 lb)
59.0 kg (130.1 lb)
Array Module
Rackmount, LP drives, 18 GB or 36 GB
40.95 kg (90.5 lb) 15.21 kg (33.54 lb) 47.25 kg (105.0 lb)
LP Drive, 18 GB or 36 GB
Controller
1.06 kg (2.34 lb)
2.2 kg (4.8 lb)
2.3 kg (5.0 lb)
1.0 kg (2.3 lb)
Power Supply
Fan
1
Maximum weight equals an array module with all canisters installed (fully loaded).
Empty weight equals an array module with all canisters removed.
2
3
Shipping weight equals the maximum weight of the array module, plus all shipping materials.
Command Module and Drive Module Site Preparation Guide
4-3
Download from Www.Somanuals.com. All Manuals Search And Download.
Array Module Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dimensions
model descriptions.
16.6 cm (6.5 in.)
52.7 cm (20.7 in.)
56.0 cm (22.0 in.)
44.7 cm (17.6 in.)
12.9 cm (5.08 in.)
13.18 cm (5.2 in.)
55.91 cm (22.0 in.)
48.0 cm (18.9 in.)
1.59 cm (0.625 in.)
Figure 4-1 E2400 10x Array Module Dimensions
4-4
Command Module and Drive Module Site Preparation Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Area Requirements
16.6 cm (6.5 in.)
52.7 cm (20.7 in.)
56.0 cm (22.0 in.)
44.70 cm (17.60 in.)
59.74 cm (23.52 in.)
12.9 cm (5.08 in.)
13.23 cm (5.21 in.)
56.13 cm (22.1 in.)
48.18 cm (18.97 in.)
3.63 cm (1.43 in.)
Figure 4-2 E2400 14x Array Module Dimensions
Shipping Carton Dimensions
Table 4-3 Array Module Shipping Carton Dimensions
Model
Carton Height
38.1 cm (15.0 in.)
44.45 cm (17.5 in.)
Carton Width
Carton Depth
E2400 10x
E2400 14x
61.4 cm (24.0 in.)
83.2 cm (32.7 in.)
62.23 cm (24.5 in.) 74.93 cm (29.5 in.)
Command Module and Drive Module Site Preparation Guide
4-5
Download from Www.Somanuals.com. All Manuals Search And Download.
Array Module Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Airflow
For proper ventilation, allow at least 2 feet of clearance in front of and behind the array
Deskside
Back
Front
Rackmount
Figure 4-3 Array Module Airflow
4-6
Command Module and Drive Module Site Preparation Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Environmental Requirements
Environmental Requirements
Table 4-4 Array Module Environmental Requirements
Requirement
Condition
Parameter
Operating Range
E2400 10x and E2400 14x
10° C to 40° C (50° F to 104° F)
10° C (18° F) per hour
Maximum Rate of Change
Storage Range
-10° C to 50° C (14° F to 122° F)
15° C (27° F) per hour
Temperature
Maximum Rate of Change
Transit Range
-40° C to 60° C (-40° F to 140° F)
20° C (36° F) per hour
20% to 80%
Maximum Rate of Change
Operating Range
Storage Range
10% to 90%
Relative Humidity
No condensation
Transit Range
5% to 95%
26° C (79° F)
10% per hour
6.0 bels
Maximum Dew Point
Maximum Gradient
Sound Power
Sound
Sound Pressure
60 dBA
Operating and Storage
Transit
3000 m (9840 ft.)
12,000 m (40,000 ft.)
Altitude
(Above Sea Level)1
Altitude
Operating, Storage,
and Transit
30.5 m (100 ft.)
(Below Sea Level)
1
If you plan to operate an array module at altitudes between 1000 m to 3000 m (3280 ft. to 9850 ft.) above sea level,
lower the environmental temperature 1.7° C (3.3° F) for every 1000 m (3280 ft.) above sea level.
Table 4-5 Array Module Heat Dissipation
Low Profile (LP)
18 GB and 36 GB Drives
Half Height (HH)
36 GB and 73 GB Drives
Model
E2400 10x
E2400 14x
1187 Btu/hr (0.35 kVA or 347 W)
1118 Btu/hr (0.328 kVA or 327 W)
1221 Btu/hr (0.37 kVA or 357 W)
Not applicable.
Command Module and Drive Module Site Preparation Guide
4-7
Download from Www.Somanuals.com. All Manuals Search And Download.
Array Module Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power Requirements
This section provides information regarding array module AC power requirements, power
cord routing instructions, and site wiring conditions.
The AC power source must provide the correct voltage, current, and frequency specified
on the manufacturer’s nameplate. Internal AC power units for rackmount cabinets must
for more information.
Table 4-6 E2400 10x Array Module Power Requirements
Item
Unit of Measure
Slow-blow Fuse
Requirement
Circuit Breaker
10 A per Power Supply
Low Range
High Range
198 to 264 VAC
50 to 60 Hz
Nominal Voltage
Frequency
90 to 136 VAC
50 to 60 Hz
3.39 A
1.45 A1
1.50 A1
AC Power
Idle Current
Maximum Operating Current
3.53 A
5.19 A
Maximum Surge Current
(10-drive spin up)
2.10 A1
1
Typical current at 240 VAC, 60 Hz at 0.70 power efficiency, 0.99 power factor.
Table 4-7 E2400 14x Array Module Power Requirements
Item
Unit of Measure
Slow-blow Fuse
Requirement
10 A per Power Supply
Circuit Breaker
Low Range
High Range
198 to 264 VAC
50 to 60 Hz
Nominal Voltage
Frequency
90 to 136 VAC
50 to 60 Hz
2.9 A1
3.3 A1
1.3 A2
1.4 A2
Idle Current
AC Power
Maximum Operating
Current
Maximum Surge Current
(14-drive spin up)
5.9 A1
2.4 A2
1
Typical voltage: 100 V AC, 60 Hz at 79% power supply efficiency and 0.99 power factor.
Typical voltage: 240 V AC, 60 Hz at 81% power supply efficiency and 0.92 power factor.
2
4-8
Command Module and Drive Module Site Preparation Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Requirements
Power Cord Routing
All modules are shipped with two AC power cords that are appropriate for use in a typical
outlet in the destination country. Each power cord connects one of the power supplies in a
module to an independent, external power source, such as a wall receptacle or
uninterruptible power supply (UPS). If you have a rackmount cabinet with internal power
cabling, such as a ladder cable, you do not need these power cords.
Typically, a rackmount cabinet has two AC distribution boxes with two separate power
independent, external power source. Each AC distribution box has a ladder cable that runs
up the inside of the cabinet and connects to one of the power supplies in each unit.
Figure 4-5 shows the power cords and receptacles for domestic (inside USA) and
international use (outside USA).
Array Module Power Supplies
Ladder Cable Connector
Ladder Cable
AC Power
Distribution Boxes
AC Power Distribution Box
Power Cords
Figure 4-4 Redundant AC Power Connections to Array Modules
Command Module and Drive Module Site Preparation Guide
4-9
Download from Www.Somanuals.com. All Manuals Search And Download.
Array Module Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
250 VAC, 16 A, IEC 320-C19 Cord
From AC Power
Distribution Box
Independent
External
Power Source
250 VAC, 30 A, NEMA L6-30 Cord
(Domestic)
230 VAC, 32 A, IEC 309 Cord
(International)
Figure 4-5 Types of 72-Inch Cabinet AC Power Cords and Receptacles
4-10
Command Module and Drive Module Site Preparation Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power Requirements
Site Wiring
The array modules use wide-ranging, redundant power supplies that automatically
accommodate voltages to the AC power source. The power supplies operate at a range
between 90 VAC and 264 VAC, and at a minimum frequency of 50 Hz and a maximum
frequency of 60 Hz. The power supplies meet standard voltage requirements for both
domestic (inside USA) and international (outside USA) operation. They use standard
industrial wiring with line-to-neutral or line-to-line power connections.
Consider the following information when preparing the array module installation site.
Earth ground – The unit must be properly grounded, including an earth ground
conductor on the AC power source.
•
Circuit overloading – Ensure the power circuits and associated circuit breakers in the
•
cabinet and building provide sufficient power and overload protection. To prevent
possible damage to the unit, isolate its power source from large switching loads (such as
air conditioning motors, elevator motors, and factory loads).
Power interruptions – The array modules will withstand the following applied voltage
interruptions (with or without an integrated UPS):
•
Input transient – 50% of nominal voltage
•
Duration – one half cycle
•
Frequency – once every 10 seconds
•
Power failures – After a total power failure, the unit will automatically perform a
power-up recovery sequence without operator intervention once power is restored.
•
Command Module and Drive Module Site Preparation Guide
4-11
Download from Www.Somanuals.com. All Manuals Search And Download.
Array Module Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Interface Cables and Connections
This section provides information about array module interface cables and their
appropriate connections.
The E2400 10x and E2400 14x array modules support Fibre Channel connections to drive
modules. Each module has four GBIC connectors; two on each controller. The connectors
drive interface you order and what type of cable you will be using to attach the array
module to the drive module.
Copper
Optical
Figure 4-6 Optical and Copper GBICs
4-12
Command Module and Drive Module Site Preparation Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Interface Cables and Connections
If you order optical GBIC connectors, you will need fiber optic cable. If you order copper
lengths available from your local dealer.
Table 4-8 E2400 10x and E2400 14x Array Module Fibre Channel Interface Cables
Descriptions
Data Rate
Order Information
Part
Transfer
Speed
Maximum
Range
Cable
Length
Number
006-1086672
006-1086416
006-1086673
006-1086417
006-1086682
006-1086672
006-1086483
006-1086473
2 meter
3 meter
5 meter
10 meter
2 meter
3 meter
5 meter
10 meter
Fiber optic
Multi-mode, 50 micrometer,
shortwave laser
100 MB/s
100 MB/s
1062.5 Mb/s 0.5 kilometer
Copper fiber
Shielded, twisted pair,
electrical signal
1062.5 Mb/s
30 meters
Command Module and Drive Module Site Preparation Guide
4-13
Download from Www.Somanuals.com. All Manuals Search And Download.
Array Module Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-14
Command Module and Drive Module Site Preparation Guide
Download from Www.Somanuals.com. All Manuals Search And Download.
Index
A
D
array module
dimensions
dimensions 4-4
cabinet 1-6
weight 4-2
drive module
dimensions 3-4
weight 3-2
C
cabinet
dimensions 1-6
features 1-2
E
weight 1-5
environmental requirements
cabinet 1-7
E2400 10x
cable
command module
dimensions 4-4
weight 4-2
dimensions 2-4
weight 2-2
E2400 14x
dimensions 4-5
weight 4-3
E4400
dimensions 2-4
weight 2-2
Command Module and Drive Module Site Preparation Guide
Index-1
Download from Www.Somanuals.com. All Manuals Search And Download.
E4600
dimensions 2-4
M
weight 2-3
O
E5600
dimensions 2-4
weight 2-3
P
power cord routing
power requirements
cabinet 1-8
F
FC-1 10x
dimensions 3-4
weight 3-2
FC-1 14x
S
dimensions 3-5
site wiring requirements
cabinet 1-12
weight 3-3
FC-2 14x
dimensions 3-5
weight 3-3
U
W
weight
I
cabinet 1-5
interface connections
L
Index-2