Klaxalarm Boxer (17-970303)  
Battery Operated - Manual Call Point/Sounder  
The Manual Call Point has a built-in alarm sounder and is powered by batteries. Up to 12 units can be connected  
together using 2 core screened fire proof cable (the screen core is used as a negative). The indicating LED will  
light on operation of the device(s) and switch off on resetting.  
The Batteries should be replaced once every 12 months. The unit does not draw any current from the batteries until  
operated. There is no low battery warning feature but as the battery voltage falls a slight drop in sound output is  
noticeable during normal testing.  
1. Installation  
Surface Mounting  
Fix the surface back box to a flat vertical surface using at least two of the  
four mounting holes provided.  
The back box may be drilled to allow cable access, a step drill is the most  
efficient and least stressful to the moulding. A 20mm hole is provided in  
the rear.  
NOTE Please ensure that the spade connectors are located exactly as  
per diagram (shown right) else the battery may foul against them  
Terminations/Connections  
When interlinking more than one unit - cabling may be connected into the  
terminals provided (Red=Permanent positive, Blue=Common Negative,  
Yellow=Switched Positive). Although there are three conductors a 2 core  
screen cable can be used, as the screen may be utilised.  
If using Pirelli FP200 then wire as Red:RED, Black:YELLOW,  
Screen:BLUE.  
Flush Mounting  
The Call Point may be flush mounted utilising the optional flush bezel, combined  
with any standard single gang flush mounting back box (with a minimum internal  
depth of 25mm). After installing the back box securely, attach the bezel using the  
two M3 screws  
Call Point 1st fix testing  
Please remember that all high voltage testing must be carried out before the installation of the Call Point front unit  
as this may cause damage.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klaxon Signals Ltd  
Wrigley St  
Oldham  
England  
OL4 1HW  
Technical Helpline:  
Sales Hotline:  
Fax:  
E-mail:  
Web:  
+44 (0) 161 287 4029  
+44 (0) 161 287 5555  
+44 (0) 161 287 5511  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Infinity Speaker CC 2 User Manual
Jacuzzi Hot Tub 9625 User Manual
Jacuzzi Swimming Pool Vacuum 2003+ User Manual
JBL Speaker System Media100 200 User Manual
John Lewis Dishwasher JLDWS1202 User Manual
JVC Camcorder Accessories CB A260 User Manual
JVC Stereo System CA MXJ206 User Manual
Kambrook Kitchen Utensil EK9B User Manual
Kodak Film Camera F620 Zoom User Manual
Konica Minolta Digital Camera Dinax 7D User Manual