Kidde Smoke Alarm PI9000CA User Manual

9 V Battery-Operated  
Dual Sensor  
Smoke Alarm  
®
Photoelectric / Ionization with Hush  
Alarm Manual  
Model PI9000CA  
Ionization sensing alarms may detect invisible fire  
particles (associated with fast flaming fires) sooner  
than photoelectric alarms. Photoelectric sensing  
alarms may detect visible fire particles (associated  
with slow smoldering fires) sooner than ionization  
alarms. Home fires develop in different ways and  
are often unpredictable. For maximum protection,  
Kidde recommends that both Ionization and  
SINGLE STATION  
SMOKE ALARM  
Photoelectric alarms be installed.  
Download from Www.Somanuals.com. All Manuals Search And Download  
Installation  
This product is designed to detect products of combustion  
using both an ionization sensor and a photoelectric sensor.  
The ionization sensor contains 0.9 microcurie of  
Americium 241, a radioactive material. Distributed under  
U.S. NRC License No. 32-23858-01E. Manufactured in  
compliance with U.S. NRC safety criteria in 10 CFR 32.27.  
The purchaser is exempt from any regulatory requirements.  
This smoke alarm uses an extremely small amount of  
radioactive element in the ionization sensor chamber. Do  
not try to repair the smoke alarm yourself. Refer to the  
instructions in Warranty for service.  
WARNING! Removal of the smoke alarm battery will render the  
alarm inoperative. Battery door will not close unless battery is  
present.  
IMPORTANT! Read all instructions before installation and keep  
this manual near the alarm for future reference.  
Download from Www.Somanuals.com. All Manuals Search And Download  
2
Installation  
Recommended Locations  
• Locate the first alarm in the immediate area of the  
bedrooms. Try to monitor the exit path, as the  
bedrooms are usually farthest from the exit. If more  
than one sleeping area exists, locate additional alarms in  
each sleeping area (Image 1A).  
• Locate additional alarms to monitor any stairway as  
stairways act like chimneys for smoke and heat.  
• Locate at least one alarm on every floor level (Image 1B).  
• Locate an alarm in every bedroom.  
• Locate an alarm in every room where electrical  
appliances are operated (i.e. portable heaters or  
humidifiers).  
• Locate an alarm in every room where someone sleeps  
with the door closed. The closed door may prevent an  
alarm not located in that room from waking the sleeper.  
• Smoke, heat, and combustion products rise to the  
ceiling and spread horizontally. Mounting the smoke  
alarm on the ceiling in the centre of the room places it  
closest to all points in the room. Ceiling mounting is  
preferred in ordinary residential construction.  
• When mounting an alarm on the ceiling, locate it at a  
minimum of 10 cm (4") from the side wall (Image 2A).  
• When mounting the alarm on the wall, use an inside  
wall with the top edge of the alarm at a minimum of 10  
cm (4") and a maximum of 30.5 cm (12") below the  
ceiling (Image 2A).  
• Put smoke alarms at both ends of a bedroom hallway  
or large room if the hallway or room is more than 9.1 m  
(30') long.  
• For mobile home installation, select locations carefully  
to avoid thermal barriers that may form at the ceiling.  
For more details, see Mobile Homes.  
Download from Www.Somanuals.com. All Manuals Search And Download  
3
Installation  
DINING  
ROOM  
KITCHEN  
BEDROOM BEDROOM  
BEDROOM  
HALL  
BEDROOM  
KITCHEN  
LIVING  
ROOM  
BEDROOM  
LIVING  
ROOM  
Smoke Alarms for Minimum Protection  
Smoke Alarms for Additional Protection  
BASEMENT  
Ionization Type Smoke Alarm with  
Hush® Control or Photoelectric Type  
SINGLE FLOOR PLAN  
MULTIPLE FLOOR PLAN  
IMAGE 1A  
IMAGE 1B  
• Install smoke alarms on sloped, peaked or cathedral  
ceilings at or within 0.9 m (3') of the highest point  
(measured horizontally). NFPA Standard 72 states: “Smoke  
alarms in rooms with ceiling slopes greater than 0.3 m in  
2.4 m (1' in 8') horizontally shall be located on the high  
side of the room.” NFPA Standard 72 states: “A row of  
detectors shall be spaced and located within 0.9 m (3') of  
the peak of the ceiling measured horizontally” (Image 2B  
and Image 2C).  
BEDROOM  
HALL  
MASTER  
BEDROOM  
FIRE  
EXTINGUISHERS  
SMOKE  
ALARMS  
KITCHEN  
FAMILY ROOM  
GARAGE  
CARBON  
MONOXIDE  
ALARMS  
BASEMENT  
WORKSHOP  
TALKING  
SMOKE/CO  
ALARM  
IMAGE 1C  
TOTAL HOME PROTECTION  
Download from Www.Somanuals.com. All Manuals Search And Download  
4
Installation  
Locations to Avoid  
• Do not install within 0.9 m (3') of the following: The  
door to a kitchen, or a bathroom that contains a tub or  
shower, forced air supply ducts used for heating or  
cooling, ceiling or whole house ventilating fans, or  
other high, air-flow areas.  
• Do not place the alarm where drapes or other objects  
will block the sensor. Smoke must be able to reach the  
sensor to accurately detect conditions.  
• Do not install in peaks of vaulted ceilings, “A” frame  
ceilings or gabled roofs. (Less than 10 cm (4") from the  
peak of an “A” frame type ceiling.)  
• Install at least 30.5 cm (12") away from fluorescent  
lights as electronic noise may cause nuisance alarms.  
• Keep out of insect infested areas. Avoid excessively  
dusty, dirty or greasy areas. Dust particles may cause  
nuisance alarms or failure to alarm.  
• Extreme temperatures may effect the sensitivity of the  
alarm. Do not install in areas where the temperature is  
colder than 4.4°C (40°F) or hotter than 37.8°C (100°F),  
such as garages or unfinished attics.  
• Do not install in areas where the relative humidity (RH)  
is greater than 85%. Very humid areas, with moisture or  
steam, can cause nuisance alarms.  
• Avoid placing ionization smoke alarms in kitchen areas.  
Normal cooking may cause nuisance alarms. If a  
®
kitchen alarm is desired, it should have a Hush feature  
or be a photoelectric type.  
• Do not place in the garage. Particles of combustion are  
present when you start your automobile.  
• Smoke alarms are not to be used with detector guards  
unless the combination (alarm and guard) has been  
evaluated and found suitable for that purpose.  
Download from Www.Somanuals.com. All Manuals Search And Download  
5
Installation  
10 cm (4”)  
MINIMUM  
CEILING  
IMAGE 2A  
NEVER HERE  
BEST  
PLACEMENT  
ACCEPTABLE  
PLACEMENT  
SIDE WALL  
NOT IN  
THIS AREA  
IMAGE 2B  
10 cm (4”)  
ANYWHERE IN THIS  
AREA  
0.9 m (3’)  
0.9 m (3’)  
HORIZONTAL DISTANCE FROM PEAK  
IMAGE 2C  
NOT IN  
THIS AREA  
ANYWHERE IN THIS  
AREA  
10 cm (4”)  
0.9 m (3’)  
Download from Www.Somanuals.com. All Manuals Search And Download  
6
Installation  
Mobile Homes  
Modern mobile homes have been designed to be energy  
efficient. Install smoke alarms as recommended in  
Recommended Locations and Image 2A.  
In older mobile homes that are not well-insulated  
compared to present standards, extreme heat or cold can  
be transferred from the outside to the inside through  
poorly insulated walls and roof. This may create a thermal  
barrier that can prevent the smoke from reaching an alarm  
mounted on the ceiling. In such units, install the smoke  
alarm on an inside wall with the top edge of the alarm at  
a minimum of 10 cm (4") and a maximum of 30.5 cm (12")  
below the ceiling (Image 2A).  
If you are not sure about the insulation in your mobile  
home, or if you notice that the outer walls and ceiling are  
either hot or cold, install the alarm on an inside wall. For  
minimum protection, install at least one alarm close to the  
bedrooms. For additional protection, see Image 1A.  
WARNING: Test your smoke alarm operation after R.V. or mobile  
home vehicle has been in storage, before each trip and at least  
once a week during use.  
Mounting  
CAUTION: This unit is sealed. The cover is not removable!  
• After selecting the proper smoke alarm location as  
described in Section 1, hold the mounting plate against  
the selected installation location (wall or ceiling) and  
mark the centre of the holes with a pencil. To ensure  
aesthetic alignment of the alarm with the hallway, or  
wall, the “A” line on the mounting plate should be  
parallel with the hallway when ceiling mounted or  
horizontal when mall mounted (Image 3A and 3B). Drill  
a hole through the pencil marks and use the enclosed  
screws and anchors to secure. Use 3/16" drill bit for  
anchor holes.  
Download from Www.Somanuals.com. All Manuals Search And Download  
7
Installation  
A
A
ALINE  
ALIGNMENT MARKS  
IMAGE 3A  
IMAGE 3B  
Remove  
Install  
WALL MOUNTING  
POSITION  
ROTATE TO MOUNT OR  
TO REMOVE  
IMAGE 3C  
IMAGE 3D  
• Install the alarm on the mounting plate and rotate the  
alarm in the direction of the “ON” arrow on the cover  
until the alarm ratchets into place (Image 3D). This  
ratcheting function allows for aesthetic alignment.  
Note: The alarm will attach to the mounting plate in 4  
positions (every 90°).  
Download from Www.Somanuals.com. All Manuals Search And Download  
8
Installation  
Battery  
This unit will not function without a properly installed  
battery. When installing a battery, press the battery  
reminder tab down into the battery compartment and  
install the battery (See Image 4A and 4B). For initial  
installation a pre-installed 9 V battery is included with a  
battery pull tab that allows for easy connection.  
CAUTION: If the battery reminder tab is not held down in the  
battery compartment by the battery, the battery door will not  
close and the unit will not attach to the mounting plate.  
Battery  
tab  
IMAGE 4A  
IMAGE 4B  
Testing  
• After installation, test your alarm by depressing and  
holding down the test button for 5 seconds until the  
alarm sounds.  
CAUTION: Due to the loudness (85 decibels) of the alarm, always  
stand an arms-length away from the unit when testing.  
Operation  
The smoke alarm is operating once a fresh battery is installed  
and testing is complete. When the smoke alarm ionization  
sensor chamber senses products of combustion, the horn will  
sound a loud (85 db) alarm until the sensing chamber is  
cleared of smoke particles.  
Do9wnload from Www.Somanuals.com. All Manuals Search And Download  
Operation  
®
Hush Control Feature  
Smoke alarms are designed to minimize nuisance alarms.  
Cigarette smoke will not normally set off the alarm, unless  
the smoke is blown directly into the alarm. Combustion  
particles from cooking may set off the alarm if the alarm is  
located close to the cooking area. Large quantities of  
combustible particles are generated from spills or when  
broiling. Using the fan on a range hood that vents to the  
outside (non-recirculating type) will also help remove  
®
these combustible particles from the kitchen. The Hush  
button is extremely useful in a kitchen area or other areas  
prone to nuisance alarms.  
®
The Hush feature has the capability of temporarily  
desensitizing the smoke alarm circuit for about 8 minutes.  
This feature is to be used only when a known alarm  
condition, such as smoke from cooking, activates the  
alarm.  
If the alarm does sound, check for fires first. If a fire is  
discovered, get out and call the fire department. If no fire  
is present, check to see if one of the reasons listed in  
Locations to Avoid may have caused the alarm.  
®
The smoke alarm is desensitized by pushing the Hush  
button on the smoke alarm cover. If the smoke is not too  
dense, the alarm will silence immediately and the red LED  
will flash every 2 seconds for approximately 8 minutes.  
This indicates that the alarm is in a temporarily  
desensitized condition. The smoke alarm will automatically  
reset after approximately 8 minutes. If after this period  
particles of combustion are still present, the alarm will  
sound again.  
®
The Hush feature can be used repeatedly until the air has  
been cleared of the condition causing the alarm. Pushing  
®
the Test button on the alarm will end the Hush period.  
NOTE: Dense smoke will override the Hush® control feature and  
sound a continuous alarm.  
CAUTION: Before using the alarm Hush® feature, identify the  
source of the smoke and be certain a safe condition exists.  
Download from Www.Somanuals.com. All Manuals Search And Download  
10  
Operation  
Alarm Tamper-Resist Feature  
This alarm has a tamper-resist feature. This feature will  
help deter children or others from removing the alarm  
from the mounting plate.  
Activate the tamper-resist feature by breaking off the four  
posts in the square holes in the mounting plate (see Image 5A).  
Rotate the alarm onto the mounting plate until you hear  
the tamper-resist tab snap into place, locking the alarm. To  
remove the alarm, press on the tamper resist tab and  
rotate the alarm off the mounting plate.  
LOCATION  
OF POSTS  
A
A
IMAGE 5A  
IMAGE 5B  
IMAGE 5C  
IMAGE 5D  
Do1w1nload from Www.Somanuals.com. All Manuals Search And Download  
Operation  
LED Indicators  
This smoke alarm is equipped with a red LED indicator.  
The red LED is located under the test button and has  
several modes of operation.  
Standby Condition  
The red LED will flash every 30–40  
seconds to indicate that the smoke  
alarm is operating properly.  
Alarm Condition  
When the alarm senses particles of  
combustion and goes into alarm, the  
red LED will flash rapidly (once every  
two seconds). The rapid flashing LED  
and temporal alarm will continue  
until the air is cleared.  
Hush Condition  
The red LED will flash every 2 seconds  
®
as long as the alarm is in Hush mode.  
Low Battery Condition The red LED will be accompanied  
by an audible chirp. Replace the  
battery when this condition occurs.  
Alarm Memory  
This smoke alarm is equipped with an  
alarm memory feature which produces  
a rapid chirping sound when the test  
button is pushed. This sound indicates  
that the alarm has been activated  
since it was last tested. Releasing  
the test button clears the memory.  
If the alarm memory sound is heard,  
release the test button and press the  
test button again to enter the normal  
test mode.  
Smoke Sensing Chamber Operation  
The alarm will “chirp” if any of the components in the  
smoke sensing chamber fail. This chirp will occur between  
the flashes of the red LED indicator light. If the “chirp”  
occurs at the same time as the red LED flash, see Battery  
Replacement section for more information.  
Download from Www.Somanuals.com. All Manuals Search And Download  
12  
Operation  
Testing  
Test by pushing the Test button on the cover and hold it  
down for a minimum of 5 seconds. This will sound the  
alarm if all the electronic circuitry, horn and battery are  
working. If no alarm sounds, the unit has defective  
batteries or other failure. DO NOT use an open flame to  
test your alarm, you could damage the alarm or ignite  
combustible materials and start a structure fire.  
Test the alarm weekly to ensure proper operation. Erratic or  
low sound coming from your alarm may indicate a defective  
alarm, and it should be returned to place of purchase (see  
Warranty section).  
NOTE: WEEKLY TESTING IS REQUIRED!  
Maintenance  
Alarm Removal  
If the smoke alarm tamper resist feature has been activated, refer  
to the alarm tamper-resist feature section for removal instructions.  
To remove the alarm from the mounting plate, rotate the alarm  
in the direction of the "OFF" arrow on the cover.  
Battery Replacement  
This smoke alarm uses a 9 V alkaline battery (a lithium battery  
may also be used). A fresh alkaline battery should last for one  
year under normal operating conditions. This alarm has a low  
battery monitor circuit which will cause the alarm to “chirp”  
approximately every 30 seconds for a minimum of 7 days when  
the battery loses power. Replace when this condition occurs.  
Continued “chirping” after the battery replacement may indicate  
defective circuitry, and the alarm should be returned to place  
of purchase.  
Use only the following 9 V batteries for replacement:  
Alkaline Type  
Energizer 522  
Duracell MN1604 or MX1604  
Gold Peak 1604A  
Panasonic 6AM6, 6AM-6, 6AM-6PI,  
6AM6X, and 6LR61(GA)  
Ultralife U9VL-J  
Lithium Type  
Do1w3nload from Www.Somanuals.com. All Manuals Search And Download  
Maintenance  
After installing or changing the battery, reinstall your alarm and  
test your alarm by using the test button.  
WARNING! Use only the batteries specified above. Use of different  
batteries than the recommended ones, may have a detrimental effect  
on the smoke alarm. A good safety measure is to replace the battery  
at least once a year, or at the same time you change your clocks for  
daylight saving time. Be sure to follow the battery installation  
instructions printed on the back of the alarm.  
NOTE: WEEKLY TESTING IS REQUIRED!  
NOTE: If after battery replacement the alarm continues to chirp,  
®
push the Test button. The Hush feature may have been  
activated accidently while changing the battery and pushing the  
®
Test button will end the Hush cycle.  
Cleaning the Alarm  
The alarm should be cleaned at least once a year.  
• To clean your alarm, remove it from the mounting plate as  
outlined in previous sections. You can clean the alarm by  
using compressed air or a vacuum cleaner hose with a soft  
brush attachment. Blow or vacuum around the perimeter of  
the alarm to remove dust and dirt. The outside of the alarm  
can be wiped with a damp cloth (do not use a wet cloth to  
avoid water entering the unit).  
• After cleaning, reinstall your alarm and test your alarm by  
using the Test button. If cleaning does not restore the alarm  
to normal operation, the alarm should be replaced.  
• Do not paint the unit. Paint will seal the vents and interfere  
with the sensor’s ability to detect smoke. Never attempt to  
disassemble the unit or clean inside. This action will void  
your warranty.  
Replacing the Alarm  
The National Fire Protection Association (NFPA) and Kidde  
recommend replacing this alarm ten years from the date code  
label (located on the back of the alarm).  
Download from Www.Somanuals.com. All Manuals Search And Download  
14  
Fire Safety  
Limitations of Smoke Alarms  
WARNING: Please read carefully and thoroughly.  
• NFPA 72 states: Life safety from fire in residential occupancies  
is based primarily on early notification to occupants of the  
need to escape, followed by the appropriate egress actions  
by those occupants. Fire warning systems for dwelling units  
are capable of protecting about half of the occupants in  
potentially fatal fires. Victims are often intimate with the  
fire, too old or young, or physically or mentally impaired  
such that they cannot escape even when warned early  
enough that escape should be possible. For these people,  
other strategies such as protection-in-place or assisted  
escape or rescue are necessary.  
• Smoke alarms are devices that can provide early  
warning of possible fires at a reasonable cost; however,  
alarms have sensing limitations. Ionization sensing  
alarms may detect invisible fire particles (associated  
with fast flaming fires) sooner than photoelectric alarms.  
Photoelectric sensing alarms may detect visible fire  
particles (associated with slow, smouldering fires)  
sooner than ionization alarms. Home fires develop in  
different ways and are often unpredictable. For  
maximum protection, Kidde recommends that both  
ionization and photoelectric alarms be installed.  
• A battery powered alarm must have a battery of the  
specified type, in good condition and installed properly.  
• A.C. powered alarms (without battery backup) will not  
operate if the A.C. power has been cut off, such as by  
an electrical fire or an open fuse.  
• Smoke alarms must be tested regularly to make sure the  
batteries and the alarm circuits are in good operating  
condition.  
• Smoke alarms cannot provide an alarm if smoke does  
not reach the alarm. Therefore, smoke alarms may not  
sense fires starting in chimneys, walls, on roofs, on the  
other side of a closed door or on a different floor.  
Do1w5nload from Www.Somanuals.com. All Manuals Search And Download  
Fire Safety  
• If the alarm is located outside the bedroom or on a  
different floor, it may not wake up a sound sleeper.  
• The use of alcohol or drugs may also impair one’s  
ability to hear the smoke alarm. For maximum  
protection, a smoke alarm should be installed in each  
sleeping area on every level of a home.  
• Although smoke alarms can help save lives by providing  
an early warning of a fire, they are not a substitute for  
an insurance policy. Home owners and renters should  
have adequate insurance to protect their lives and property.  
Good Safety Habits  
Develop and practice a plan of escape!  
• Make a floor plan indicating all doors and windows and  
at least two (2) escape routes from each room. Second  
story windows may need an escape ladder.  
• Have a family meeting and discuss your escape plan,  
showing everyone what to do in case of fire.  
• Determine a place outside your home where you all  
can meet if a fire occurs.  
• Familiarize everyone with the sound of the smoke alarm  
and train them to leave your home when they hear it.  
• Practice a fire drill at least every six months, including  
fire drills at night. Ensure that small children hear the  
alarm and wake when it sounds. They must wake up in  
order to execute the escape plan. Practice allows all  
occupants to test your plan before an emergency. You  
may not be able to reach your children. It is important  
they know what to do.  
• Install and maintain fire extinguishers on every level of  
the home and in the kitchen, basement and garage.  
Know how to use a fire extinguisher prior to an  
emergency.  
Download from Www.Somanuals.com. All Manuals Search And Download  
16  
Fire Safety  
What To Do When The Alarm Sounds  
• Alert small children in the home.  
• Leave immediately by your escape plan. Every second  
counts, so don’t waste time getting dressed or picking  
up valuables.  
• In leaving, don’t open any inside door without first  
feeling its surface. If hot, or if you see smoke seeping  
through cracks, don’t open that door! Instead, use your  
alternate exit. If the inside of the door is cool, place  
your shoulder against it, open it slightly and be ready to  
slam it shut if heat and smoke rush in.  
• Stay close to the floor if the air is smoky. Breathe  
shallowly through a cloth, wet if possible.  
• Once outside, go to your selected meeting place and  
make sure everyone is there.  
• Call the fire department from your neighbor’s home–not  
from yours!  
• Don’t return to your home until the fire officials say that  
it is all right to do so.  
There are situations where a smoke alarm may not be  
effective to protect against fire as stated in the NFPA  
Standard 72. For instance:  
a) smoking in bed  
b) leaving children home alone  
c) cleaning with flammable liquids, such as gasoline.  
NRC Information  
Ionization type smoke alarms use a very small amount of  
a radioactive element in the sensing chamber to enable  
detection of visible and invisible combustion products. The  
radioactive element is safely contained in the chamber and  
requires no adjustments or maintenance. This smoke alarm  
meets or exceeds all government standards. It is  
manufactured and distributed under license from the U.S.  
Nuclear Regulatory Commission.  
Download from Www.Somanuals.com. All Manuals Search And Download  
17  
Fire Safety  
Additional Recommendations  
The National Fire Protection Association’s Standard 72  
provides the following information:  
Smoke alarms shall be installed outside each separate  
sleeping area in the immediate vicinity of the bedrooms  
and on each additional story of the family living unit,  
including basements and excluding crawl spaces and  
unfinished attics. In new construction, a smoke alarm also  
shall be installed in each sleeping room.  
Smoke Detection:Are More Smoke Alarms Desirable?  
Required number of smoke alarms (as shown in Image 1A  
and Image 1B): The required number of smoke alarms  
might not provide reliable early warning protection for  
those areas separated by a door from the areas protected  
by the required smoke alarms. For this reason, it is  
recommended that the householder consider the use of  
additional smoke alarms for those areas for increased  
protection.  
The additional areas include the basement, bedrooms,  
dining room, furnace room, utility room, and hallways not  
protected by the required smoke alarms. The installation  
of the smoke alarms in the kitchen, attic (finished or  
unfinished), or garage is normally not recommended, as  
these locations occasionally experience conditions that  
can result in improper operation.  
Alarms should be installed in accordance with the  
National Fire Protection Association’s Standard 72 (NFPA,  
Batterymarch Park, Quincy, MA 02269).  
Notify your local fire department and insurance company  
of your smoke alarm installation.  
Download from Www.Somanuals.com. All Manuals Search And Download  
18  
Warranty  
If after reviewing this manual you feel that your smoke  
alarm is defective in any way, do not tamper with the unit.  
In many cases, the quickest way to exchange your alarm  
is to return it to the original place of purchase. Alternatively,  
you may return it for servicing to Kidde. If you have questions,  
call Kidde Customer Service at 1-800-880-6788.  
10 Year Limited Warranty  
Kidde warrants to the original purchaser that the enclosed  
smoke alarm (but not the battery) will be free from defects in  
material and workmanship or design under normal use and  
service for a period of ten years from the date of purchase.  
The obligation of Kidde under this warranty is limited to  
repairing or replacing the smoke alarm or any part which we  
find to be defective in material, workmanship or design, free  
of charge to the customer, upon sending the smoke alarm  
with proof of date of purchase, postage and return postage  
prepaid, to Kidde, Customer Service Department, 130 Esna  
Park Drive, Markham, ON L3R 1E3. 1-800-880-6788.  
This warranty shall not apply to the smoke alarm if it has  
been damaged, modified, abused or altered after the date of  
purchase or if it fails to operate due to improper maintenance  
or inadequate AC or DC electrical power.  
The liability of Kidde or any of its parent or subsidiary  
corporations arising from the sale of this smoke alarm or under  
the terms of this limited warranty shall not in any case exceed the  
cost of replacement of this smoke alarm and, in no case, shall  
Kidde or any of its parent or subsidiary corporations be liable for  
consequential loss or damages resulting from the failure of this  
smoke alarm or for breach of this or any other warranty, express  
or implied, even if the loss or damage is caused by the company’s  
negligence or fault.  
Since some provinces do not allow limitations on the duration  
of an implied warranty or do not allow the exclusion or  
limitation of incidental or consequential damages, the above  
limitations or exclusions may not apply to you. While this  
warranty gives you specific legal rights, you may also have  
other rights which vary from province to province.  
Also, Kidde makes no warranty, express or implied, written or  
oral, including that of merchantability or fitness for any  
particular purpose, with respect to the battery.  
The above warranty may not be altered except in writing  
signed by both parties hereto.  
Do1w9nload from Www.Somanuals.com. All Manuals Search And Download  

Indesit Washer Dryer PWDE 7125 W User Manual
Ingersoll Rand Outboard Motor 92N User Manual
Intel Laptop W653DI1 User Manual
Jensen Clock Radio JCR 222 User Manual
JVC CD Player GET0425 001A User Manual
JVC DVD Player XV N672S User Manual
JVC Projector AV P950U User Manual
Kenwood TV Receiver KTC D500E User Manual
Klipsch Speaker SWS User Manual
Korg CD Player MR 2000S User Manual