Jade Range Smoke Alarm W7220 User Manual

JADE™ Economizer Module  
(MODEL W7220)  
INSTALLATION INSTRUCTIONS  
over is required in addition to the MA sensor. An additional  
Return Air (RA) Sylkbus sensor can be added to the system  
for differential enthalpy changeover.  
DCV (CO ) Sensor (C7232): 2-10 Vdc control signal;  
2
minimum impedance >50k ohm.  
Outputs  
Actuator signal: 2-10 Vdc; minimum actuator impedance is  
2k ohm; Sylkbus two-wire output for Honeywell Sylkbus  
communicating actuators.  
Exhaust fan, Y1, Y2 and AUX1 O: Contact closure (24 Vac)  
All Relay Outputs (at 30 Vac):  
Running: 1.5A maximum  
Inrush: 7.5A maximum  
When Installing This Product  
1. Read these instructions carefully. Failure to follow them  
could damage the product or cause a hazardous condi-  
tion.  
2. Check ratings given in instructions and on the product to  
ensure the product is suitable for your application.  
3. Installer must be a trained, experienced service techni-  
cian.  
4. After installation is complete, check out product opera-  
tion as provided in these instructions.  
This document describes wiring, power up, basic  
troubleshooting, and common installation issues for the  
JADE™ Economizer Module (Model W7220). For further  
information on mounting and operation, refer to Honeywell  
document 63-2700.  
BEFORE INSTALLATION  
Review the following before installing the The W7220:  
Electrical  
Accessories  
50048926-001 2-pin edge connector for sensors  
(20 pieces per bag)  
50048926-002 6-pin edge connector for field wiring  
(20 pieces per bag)  
Rated Voltage: 20 to 30 Vac RMS; 50/60 Hz  
Transformer: 100 VA maximum system input  
Relay Digital Output Rating: 30 Vac  
C7250 20k sensor for MA or OA (dry bulb changeover)  
C7400S Sylkbus sensor for enthalpy control in OA and/or RA  
and RA for differential dry bulb changeover  
W7220 PCMOD interface tool for JADE controller and Per-  
economizertools for the software  
IMPORTANT  
All inputs and outputs must be Class 2 wiring.  
Inputs  
50053060-001 Duct mounting kit for sensors  
A Mixed air (MA) analog sensor is required on all W7220  
units; either an OA (Outdoor Air) sensor for dry bulb change  
over or an OA Sylkbus sensor for outdoor enthalpy change  
62-0331-07  
Download from Www.Somanuals.com. All Manuals Search And Download.  
JADE™ ECONOMIZER MODULE  
ROOF TOP UNIT  
MA TEMP  
SENSOR  
20K NTC  
W7220 ECONOMIZER CONTROLLER MODULE  
Y1  
W1  
G
O/B  
W2  
OCC  
Y2  
3
1K1  
MA  
MA  
OAT  
OAT  
AUX2-I  
OCC  
E-GND  
OA TEMP  
SENSOR  
20K NTC  
1
AUX1-0  
Y2I  
CO2  
SENSOR  
2-10 VDC  
IAQ (2-10V)  
IAQ COM  
IAQ 24V  
Y2O  
Y1I  
(OPTIONAL)  
ACT (2-10V)  
ACT COM  
ACT 24V  
Y1O  
C R  
TR  
1K1  
R(+)  
C(-)  
TR1  
M7215  
(OPTIONAL COMMUNICATING DCA)  
24 VAC  
IN  
IN  
+
-
2
1
2
NOTE THAT THE C7250 20K NTC SENSOR CAN BE MOUNTED IN THE OAT ONLY IN THIS CONFIGURATION.  
WHEN USING A HEAT PUMP THERMOSTAT OR A PROGRAMMABLE THERMOSTAT, THERMOSTAT TERMINALS  
MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W.  
THERMOSTAT  
3
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.  
M28980B  
Fig. 1. Stand-alone dry bulb Economizer configuration with black motor M7215.  
3
62-0331—07  
Download from Www.Somanuals.com. All Manuals Search And Download.  
JADE™ ECONOMIZER MODULE  
ROOF TOP UNIT  
MA TEMP  
SENSOR  
20K NTC  
W7220 ECONOMIZER CONTROLLER MODULE  
Y1  
W1  
G
O/B  
W2  
OCC  
Y2  
3
1K1  
MA  
MA  
AUX2-I  
OCC  
E-GND  
OA  
OA  
OA TEMP  
SENSOR  
20K NTC  
1
AUX1-0  
Y2I  
CO2  
SENSOR  
2-10 VDC  
IAQ (2-10V)  
IAQ COM  
IAQ 24V  
Y2O  
Y1I  
(OPTIONAL)  
ACT (2-10V)  
ACT COM  
ACT 24V  
Y1O  
C R  
1K1  
R(+)  
C(-)  
24 VAC  
MS7503 OR MS7505  
2
3
1
2
NOTE THAT THE 20K NTC SENSOR CAN BE MOUNTED IN THE OA TERMINALS ONLY IN THIS CONFIGURATION.  
THERMOSTAT  
WHEN USING A HEAT PUMP THERMOSTAT OR A PROGRAMMABLE THERMOSTAT, THERMOSTAT TERMINALS  
MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W.  
3
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.  
M32564B  
Fig. 2. Stand-alone dry-bulb Economizer configuration with Honeywell MS7403 Direct Coupled Actuator.  
ROOF TOP UNIT  
MA TEMP  
W7220 ECONOMIZER CONTROLLER MODULE  
SENSOR  
20K NTC  
Y1  
W1  
G
O/B  
W2  
OCC  
Y2  
3
1K1  
1
MA  
MA  
AUX2-I  
OA TEMP  
SENSOR  
20K NTC  
OCC  
E-GND  
OA  
OA  
AUX1-0  
Y2I  
CO2  
SENSOR  
2-10 VDC  
IAQ (2-10V)  
IAQ COM  
IAQ 24V  
Y2O  
Y1I  
(OPTIONAL)  
ACT (2-10V)  
ACT COM  
ACT 24V  
Y1O  
C R  
1K1  
1
2
R(+)  
24 VAC  
MS3103J  
OR MS3105J  
3
4
5
S-BUS  
S-BUS  
C(-)  
2
1
2
NOTE THAT THE 20K NTC SENSOR CAN BE MOUNTED IN THE OA TERMINALS ONLY IN THIS CONFIGURATION.  
THERMOSTAT  
WHEN USING A HEAT PUMP THERMOSTAT OR A PROGRAMMABLE THERMOSTAT, THERMOSTAT TERMINALS  
MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W.  
3
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.  
M32650B  
Fig. 3. Stand-alone dry-bulb Economizer configuration with Honeywell MS3103J or MS3105J communicating actuators.  
62-0331—07  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
JADE™ ECONOMIZER MODULE  
2
ROOF TOP UNIT  
MA TEMP  
SENSOR  
20K NTC  
W7220 ECONOMIZER CONTROLLER MODULE  
O/B  
Y1  
W1  
G
OCC  
Y2  
W2  
4
1K1  
MA  
MA  
AUX2-I  
OCC  
E-GND  
S-BUS  
S-BUS  
AUX1-0  
Y2I  
CO2  
SENSOR  
2-10 VDC  
IAQ (2-10V)  
IAQ COM  
IAQ 24V  
Y2O  
Y1I  
(OPTIONAL)  
ACT (2-10V)  
ACT COM  
ACT 24V  
Y1O  
C R  
1K1  
TR  
R(+)  
24 VAC  
TR1  
M7215  
C(-)  
IN  
+
3
IN  
-
THERMOSTAT  
OUTSIDE AIR  
TEMP/HUMIDITY (ENTHALPY)  
SYLKBUS SENSOR  
1
IN THIS CONFIGURATION, AN OPTIONAL DISCHARGE AIR TEMP/HUMIDITY  
(ENTHALPY) SYLKBUS SENSOR CAN BE ADDED FOR ADVANCED  
CONTROL AS SHOWN IN THE LOWER LEFT OF THIS FIGURE.  
1
2
3
DO NOT USE THE C7250 20K NTC SENSOR WITH THE OA TERMINAL IN THIS  
CONFIGURATION.  
RETURN AIR  
TEMP/HUMIDITY (ENTHALPY)  
SYLKBUS SENSOR  
WHEN USING A HEAT PUMP THERMOSTAT OR A PROGRAMMABLE THERMOSTAT,  
THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O OR B AND W2  
MAY BE LABELED W.  
4
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION  
RELAY BETWEEN O AND C.  
M32565B  
Fig. 4. Economizer with Sylk Bus sensors for enthalpy configuration with Honeywell M7215 black motor.  
5
62-0331—07  
Download from Www.Somanuals.com. All Manuals Search And Download.  
JADE™ ECONOMIZER MODULE  
2
ROOF TOP UNIT  
MA TEMP  
SENSOR  
20K NTC  
W7220 ECONOMIZER CONTROLLER MODULE  
O/B  
Y1  
W1  
G
OCC  
Y2  
W2  
4
1K1  
MA  
MA  
AUX2-I  
OCC  
E-GND  
S-BUS  
S-BUS  
AUX1-0  
Y2I  
IAQ (2-10V)  
IAQ COM  
IAQ 24V  
ACT (2-10V)  
ACT COM  
ACT 24V  
CO2  
SENSOR  
2-10 VDC  
Y2O  
Y1I  
(OPTIONAL)  
Y1O  
C R  
1K1  
R(+)  
24 VAC  
C(-)  
MS7503 OR MS7505  
3
3
OUTSIDE AIR  
TEMP/HUMIDITY (ENTHALPY)  
SYLKBUS SENSOR  
THERMOSTAT  
1
IN THIS CONFIGURATION, AN OPTIONAL DISCHARGE AIR TEMP/HUMIDITY  
(ENTHALPY) SYLKBUS SENSOR CAN BE ADDED FOR ADVANCED  
CONTROL AS SHOWN IN THE LOWER LEFT OF THIS FIGURE.  
1
RETURN AIR  
TEMP/HUMIDITY (ENTHALPY)  
SYLKBUS SENSOR  
2
3
DO NOT USE THE C7250 20K NTC SENSOR WITH THE OA TERMINAL IN THIS  
CONFIGURATION.  
WHEN USING A HEAT PUMP THERMOSTAT OR A PROGRAMMABLE THERMOSTAT,  
THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O OR B AND W2  
MAY BE LABELED W.  
4
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION  
RELAY BETWEEN O AND C.  
M32566B  
Fig. 5. Economizer with Sylk Bus sensors for enthalpy configuration with a Honeywell MS7505 or MS7503 Direct  
Coupled Actuator.  
62-0331—07  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
JADE™ ECONOMIZER MODULE  
ROOF TOP UNIT  
MA TEMP  
SENSOR  
20K NTC  
W7220 ECONOMIZER CONTROLLER MODULE  
O/B  
Y1  
OCC  
W1  
G
Y2  
W2  
4
1K1  
MA  
MA  
AUX2-I  
OCC  
E-GND  
S-BUS  
S-BUS  
AUX1-0  
Y2I  
IAQ (2-10V)  
IAQ COM  
IAQ 24V  
ACT (2-10V)  
ACT COM  
ACT 24V  
CO2  
SENSOR  
2-10 VDC  
Y2O  
Y1I  
(OPTIONAL)  
Y1O  
C R  
1K1  
R(+)  
24 VAC  
1
2
C(-)  
2
MS3103J  
OR MS3105J  
3
4
5
S-BUS  
S-BUS  
3
THERMOSTAT  
1
IN THIS CONFIGURATION, AN OPTIONAL DISCHARGE AIR TEM/HUMIDITY  
(ENTHALPY) SYLKBUS SENSOR CAN BE ADDED FOR ADVANCED  
CONTROL AS SHOWN IN THE LOWER LEFT OF THIS FIGURE.  
C7400S  
OUTSIDE AIR  
TEMP/HUMIDITY (ENTHALPY)  
SYLKBUS SENSOR  
2
3
THE S-BUS COMPONENTS MAY BE DAISY CHAINED TO ANOTHER S-BUS  
COMPONENT.  
WHEN USING A HEAT PUMP THERMOSTAT OR A PROGRAMMABLE  
THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE  
LABELED O OR B AND W2 MAY BE LABELED W.  
C7400S  
RETURN AIR  
TEMP/HUMIDITY (ENTHALPY)  
SYLKBUS SENSOR  
1
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN  
ISOLATION RELAY BETWEEN O AND C.  
4
M32653B  
Fig. 6. Economizer with Sylk bus sensor for enthalpy configuration with Honeywell MS3103 or MS3105 communicating  
actuators.  
EXH1 OR AUX1 O  
C
1
2
V
ACTUATOR  
NOTE: ON/OFF ACTUATORS CAN BE USED ON THE EXH1 OR AUX1  
O TERMINAL WITH GROUND TO THE C TERMINAL. WHEN  
PROGRAMMING THE EXH1 OR AUX1 O, THE % IS THE PERCENT  
OPEN POSITION OF THE OUTDOOR AIR DAMPER WHEN THE  
EXH1 OR AUX1 O TERMINAL IS ENERGIZED AND THE 2-POS  
DAMPER GOES OPEN. IF USING THE AUX1 O TERMINAL  
PROGRAM AUX1 O FOR EXH2.  
M33409  
Fig. 7. 2-position actuator.  
7
62-0331—07  
Download from Www.Somanuals.com. All Manuals Search And Download.  
JADE™ ECONOMIZER MODULE  
ECONOMIZING  
AVAILABLE  
DUAL ENTHALPY  
HIGH LIMIT  
NOT AVAILABLE  
SINGLE ENTHALPY  
P2 (T,RH)  
P1  
(T,RH)  
ES5  
ES4  
ES3  
ES2  
ES1  
HL  
TEMPERATURE  
M32286  
Fig. 8. Single Enthalpy curves and boundaries.  
Table 1. Single Enthalpy and Dual Enthalpy High Limit Curves.  
Point P1  
Point P2  
Humidity %RH  
Enthalpy  
Curve  
Temp.  
Temp.  
Enthalpy  
Dry-Bulb (°F)  
Dewpoint (°F)  
(btu/lb/da) Temp. °F  
Humidity %RH  
Temp. °F  
66.3  
ES1  
ES2  
ES3  
ES4  
ES5  
HL  
80.0  
75.0  
70.0  
65.0  
60.0  
86.0  
60.0  
57.0  
54.0  
51.0  
48.0  
66.0  
28.0  
26.0  
24.0  
22.0  
20.0  
32.4  
80.0  
75.0  
70.0  
65.0  
60.0  
86.0  
36.8  
39.6  
42.3  
44.8  
46.9  
38.9  
80.1  
80.0  
81.4  
84.2  
88.5  
80.3  
63.3  
59.7  
55.7  
51.3  
72.4  
Power Up  
After the module is mounted and wired, apply power.  
Power Loss (Outage or Brownout)  
a
All setpoints and advanced settings are restored after any  
power loss or interruption.  
Power Up Delay  
Upon power up (or after a power outage or brownout), the  
W7220 controller module begins a 5 minute power up delay  
before enabling mechanical cooling.  
NOTE: If power goes below 18 Vac, the W7220 controller  
module assumes a power loss and the 5 minute  
power up delay will become functional when  
power returns above 18 Vac.  
Initial Menu Display  
TROUBLESHOOTING  
On initial start up, Honeywell displays on the first line and  
Economizer W7220 on the second line. After a brief pause,  
the revision of the software appears on the first line and the  
second line will be blank.  
Alarms  
The Economizer module provides alarm messages that  
display on the 2-line LCD.  
NOTE: Upon power up, the module waits several sec-  
onds before checking for alarms. This allows  
time for all the configured devices (e.g. sensors,  
actuator) to become operational. If one or more  
alarms are present and there has been no keypad  
activity for at least 5 minutes, the Alarms menu  
displays and cycles through the active alarms.  
You can also navigate to the Alarms menu at any time.  
a
All settings are stored in non-volatile flash memory.  
62-0331—07  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
JADE™ ECONOMIZER MODULE  
To clear an alarm, perform the following:  
Table 2. Alarms Menu.  
Alarm  
1. Navigate to the desired alarm.  
2. Press the button.  
Menu  
ALARMS(_)  
3. ERASE? displays.  
MA T SENS ERR  
CO2 SENS ERR  
OA T SENS ERR  
DA ENTHL ERR  
4. Press the button.  
5. ALARM ERASED displays.  
6. Press the  
button (MenuUp/Exit) to complete the  
action and return to the previous menu.  
a
SYS ALARM  
NOTE: If an alarm still exists after you clear it, it re-dis-  
plays within 5 seconds.  
b
ACT Over Voltage  
b
NOTE: Jade will be in the "set up" mode for the first 60  
minutes after powered. If a sensor for OA air or  
Sylkbus device (sensor, actuator) is discon-  
nected during the set up mode, the Jade will not  
alarm that failure. The MA sensor is a system  
"critical" sensor; if the MA sensor is removed  
during the set up mode, the Jade will alarm. After  
60 minutes the Jade controller will change to  
operation mode and all components removed or  
failed will alarm in the operation mode.  
ACT Under Voltage  
b
ACT Stalled  
NOTES:  
1.  
The Alarms menu displays only when alarm(s)  
are active and includes the number of active  
alarms in parenthesis ().  
The alarms listed are a few examples. Additional  
alarms display depending on the parameter set-  
tings and configuration.  
2.  
a
When AUX1 O is set to SYS and there is any alarm (e.g., failed sensors,  
etc.), the AUX1 O terminal has 24 Vac out and the LCD displays the  
ALARM.  
This alarm is only displayed when a communicating actuator is used. (ex:  
MS3105AJ)  
b
Clearing Alarms  
Once the alarm has been identified and the cause has been  
removed (e.g. replaced faulty sensor), the alarm can be  
cleared from the display.  
9
62-0331—07  
Download from Www.Somanuals.com. All Manuals Search And Download.  
JADE™ ECONOMIZER MODULE  
COMMON INSTALLATION ISSUES AND CONCERNS  
Table 3. Installation Issues and Concerns.  
Area  
Issue or Concern  
Possible Cause and Remedy  
Configuration  
Are the old sensors in the unit No, the C7400A and C7150 sensors are not compatible with the W7220. The enthalpy sensor  
(C7400A, C7150 or C7232)  
for the W7220 is the C7400S. The Mixed Air or Outdoor air dry bulb sensors are the C7250A.  
compatible with the economizer The C7232 CO sensor is compatible with the W7220.  
2
controller?  
The unit has a W7459  
If you have a W7459 economizer with a M7415 motor you will need to change to a M7215  
motor. The W7220 has a 2 to 10 Vdc out to the motor, so you will need a M7215 motor. The  
economizer and black motor.  
Do I need to change the motor? M7215 motors are used with the W7212 economizers. So if you have one of these units, you  
will not have to change the motor.  
Wiring  
I have 4 terminals on my  
actuator and the wiring only  
shows 3 wires.  
The economizer 24 Vac COM can be wired to the Honeywell actuator common (  
TR1). The actuators have internal ground circuits.  
or  
There is an Earth Ground  
terminal. Do I need to wire to  
earth ground?  
Yes, the economizer must be wired to earth ground.  
What are the part numbers of The 2-pin connectors are Honeywell part number 50048926-001 and the 6-pin connectors  
the 2 and 6 pin side  
connectors?  
are Honeywell part number 50048926-002. Both are available in accessory bags of 20 each.  
62-0331—07  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
JADE™ ECONOMIZER MODULE  
Table 3. Installation Issues and Concerns. (Continued)  
Issue or Concern Possible Cause and Remedy  
Operation or Use My outdoor temperature Check the sensor wiring. Enthalpy sensors are to be wired to the Sylk Bus terminals.  
Area  
reading on the STATUS menu is Temperature sensors are to be wired to the OAT and MAT terminals.  
not accurate.  
If my enthalpy sensor drifts in The sensors are not able to be re-calibrated in the field. However there is a menu item under  
accuracy over time, can I re-  
calibrate it?  
the ADVANCED menu where you are able to input a limited offset in temperature and  
humidity for each sensor you have connected to the economizer.  
Can I go back to factory  
defaults and start over?  
Under the SYSTEM SETUP menu you can change the setpoints to the factory defaults.  
Will I be able to see the LCD  
screen when it is in the unit?  
The LCD screen has a backlight that is always illuminated.  
What is a good setpoint for the The mixed air temperature is the temperature of air that you want to supply to the space. In a  
Mixed Air Temperature (MAT)? commercial building, this is between 50 to 55°F (10 to 13°C). The mixed air is the mixing of  
the return air and the outdoor air.  
I am using enthalpy sensors.  
In the event the humidity sensor in the enthalpy sensors fails, the backup algorithm in the  
Why did the control ask me to control is to default to the temperature sensor in the enthalpy sensor.  
input a dry bulb changeover  
temperature?  
In checkout, the outdoor  
damper closes when I  
command it open.  
Check the actuator linkage or rotation. In the CHECKOUT mode, the outdoor damper should  
drive open or closed with the return air damper having the opposite effect.  
How do I set my minimum  
position?  
The minimum position is set using the VENTMIN and VENTMAX setup in the SETPOINTS  
menu. VENTMIN is the minimum ventilation required when using an occupancy sensor and  
VENTMAX is the minimum ventilation when not using an occupancy sensor for Demand  
Control Ventilation. The VENTMAX position is set the same as with the potentiometer on the  
analog economizers and is the output voltage to the damper actuator. The range is 2 Vdc  
closed OA damper and 10 Vdc open OA damper.  
What if my damper does not go Check the damper linkage or hub to make sure the damper is able to close completely.  
completely closed in the  
checkout operation?  
How do I set the OCC?  
There are two settings for the OCC setting, INPUT and ALWAYS. INPUT is from the space  
thermostat, if it has an occupancy output. ALWAYS is the unit in the occupied mode, if the  
economizer is powered (fan on).  
Does the economizer save my Yes, once the changes are stored in the controller they will be stored until they are changed  
program values if the unit loses by the operator.  
power?  
If the unit is left in checkout,  
how long will the unit stay in  
checkout mode without input?  
The unit will remain in checkout for 10 minutes, then return to normal operation.  
11  
62-0331—07  
Download from Www.Somanuals.com. All Manuals Search And Download.  
JADE™ ECONOMIZER MODULE  
Automation and Control Solutions  
Honeywell International Inc.  
1985 Douglas Drive North  
® U.S. Registered Trademark  
© 2012 Honeywell International Inc.  
62-0331—07 M.S. Rev. 02-12  
Printed in United States  
Golden Valley, MN 55422  
customer.honeywell.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Intellinet Network Solutions Network Router 529930 User Manual
iSimple Indoor Furnishings PGHHY1 User Manual
Jabra Headphones GN1200 User Manual
John Deere Air Compressor AC2 80ES User Manual
JVC DVD Player XV FA90BK User Manual
JVC MP3 Player KD R820BT User Manual
JVC Stereo System CA FSX5 User Manual
Kenwood CD Player KDC X959 User Manual
KitchenAid Ice Maker KUIS18PNTB1 User Manual
KitchenAid Oven KEBK206SSS03 User Manual