JADE™ Economizer Module
(MODEL W7220)
INSTALLATION INSTRUCTIONS
over is required in addition to the MA sensor. An additional
Return Air (RA) Sylkbus sensor can be added to the system
for differential enthalpy changeover.
DCV (CO ) Sensor (C7232): 2-10 Vdc control signal;
2
minimum impedance >50k ohm.
Outputs
Actuator signal: 2-10 Vdc; minimum actuator impedance is
2k ohm; Sylkbus two-wire output for Honeywell Sylkbus
communicating actuators.
Exhaust fan, Y1, Y2 and AUX1 O: Contact closure (24 Vac)
All Relay Outputs (at 30 Vac):
Running: 1.5A maximum
Inrush: 7.5A maximum
When Installing This Product
1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous condi-
tion.
2. Check ratings given in instructions and on the product to
ensure the product is suitable for your application.
3. Installer must be a trained, experienced service techni-
cian.
4. After installation is complete, check out product opera-
tion as provided in these instructions.
This document describes wiring, power up, basic
troubleshooting, and common installation issues for the
JADE™ Economizer Module (Model W7220). For further
information on mounting and operation, refer to Honeywell
document 63-2700.
BEFORE INSTALLATION
Review the following before installing the The W7220:
Electrical
Accessories
50048926-001 2-pin edge connector for sensors
(20 pieces per bag)
50048926-002 6-pin edge connector for field wiring
(20 pieces per bag)
Rated Voltage: 20 to 30 Vac RMS; 50/60 Hz
Transformer: 100 VA maximum system input
Relay Digital Output Rating: 30 Vac
C7250 20k sensor for MA or OA (dry bulb changeover)
C7400S Sylkbus sensor for enthalpy control in OA and/or RA
and RA for differential dry bulb changeover
W7220 PCMOD interface tool for JADE controller and Per-
economizertools for the software
IMPORTANT
All inputs and outputs must be Class 2 wiring.
Inputs
50053060-001 Duct mounting kit for sensors
A Mixed air (MA) analog sensor is required on all W7220
units; either an OA (Outdoor Air) sensor for dry bulb change
over or an OA Sylkbus sensor for outdoor enthalpy change
62-0331-07
Download from Www.Somanuals.com. All Manuals Search And Download.
JADE™ ECONOMIZER MODULE
ROOF TOP UNIT
MA TEMP
SENSOR
20K NTC
W7220 ECONOMIZER CONTROLLER MODULE
Y1
W1
G
O/B
W2
OCC
Y2
3
1K1
MA
MA
OAT
OAT
AUX2-I
OCC
E-GND
OA TEMP
SENSOR
20K NTC
1
AUX1-0
Y2I
CO2
SENSOR
2-10 VDC
IAQ (2-10V)
IAQ COM
IAQ 24V
Y2O
Y1I
(OPTIONAL)
ACT (2-10V)
ACT COM
ACT 24V
Y1O
C R
TR
1K1
R(+)
C(-)
TR1
M7215
(OPTIONAL COMMUNICATING DCA)
24 VAC
IN
IN
+
-
2
1
2
NOTE THAT THE C7250 20K NTC SENSOR CAN BE MOUNTED IN THE OAT ONLY IN THIS CONFIGURATION.
WHEN USING A HEAT PUMP THERMOSTAT OR A PROGRAMMABLE THERMOSTAT, THERMOSTAT TERMINALS
MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W.
THERMOSTAT
3
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.
M28980B
Fig. 1. Stand-alone dry bulb Economizer configuration with black motor M7215.
3
62-0331—07
Download from Www.Somanuals.com. All Manuals Search And Download.
JADE™ ECONOMIZER MODULE
ROOF TOP UNIT
MA TEMP
SENSOR
20K NTC
W7220 ECONOMIZER CONTROLLER MODULE
Y1
W1
G
O/B
W2
OCC
Y2
3
1K1
MA
MA
AUX2-I
OCC
E-GND
OA
OA
OA TEMP
SENSOR
20K NTC
1
AUX1-0
Y2I
CO2
SENSOR
2-10 VDC
IAQ (2-10V)
IAQ COM
IAQ 24V
Y2O
Y1I
(OPTIONAL)
ACT (2-10V)
ACT COM
ACT 24V
Y1O
C R
1K1
R(+)
C(-)
24 VAC
MS7503 OR MS7505
2
3
1
2
NOTE THAT THE 20K NTC SENSOR CAN BE MOUNTED IN THE OA TERMINALS ONLY IN THIS CONFIGURATION.
THERMOSTAT
WHEN USING A HEAT PUMP THERMOSTAT OR A PROGRAMMABLE THERMOSTAT, THERMOSTAT TERMINALS
MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W.
3
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.
M32564B
Fig. 2. Stand-alone dry-bulb Economizer configuration with Honeywell MS7403 Direct Coupled Actuator.
ROOF TOP UNIT
MA TEMP
W7220 ECONOMIZER CONTROLLER MODULE
SENSOR
20K NTC
Y1
W1
G
O/B
W2
OCC
Y2
3
1K1
1
MA
MA
AUX2-I
OA TEMP
SENSOR
20K NTC
OCC
E-GND
OA
OA
AUX1-0
Y2I
CO2
SENSOR
2-10 VDC
IAQ (2-10V)
IAQ COM
IAQ 24V
Y2O
Y1I
(OPTIONAL)
ACT (2-10V)
ACT COM
ACT 24V
Y1O
C R
1K1
1
2
R(+)
24 VAC
MS3103J
OR MS3105J
3
4
5
S-BUS
S-BUS
C(-)
2
1
2
NOTE THAT THE 20K NTC SENSOR CAN BE MOUNTED IN THE OA TERMINALS ONLY IN THIS CONFIGURATION.
THERMOSTAT
WHEN USING A HEAT PUMP THERMOSTAT OR A PROGRAMMABLE THERMOSTAT, THERMOSTAT TERMINALS
MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W.
3
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.
M32650B
Fig. 3. Stand-alone dry-bulb Economizer configuration with Honeywell MS3103J or MS3105J communicating actuators.
62-0331—07
4
Download from Www.Somanuals.com. All Manuals Search And Download.
JADE™ ECONOMIZER MODULE
2
ROOF TOP UNIT
MA TEMP
SENSOR
20K NTC
W7220 ECONOMIZER CONTROLLER MODULE
O/B
Y1
W1
G
OCC
Y2
W2
4
1K1
MA
MA
AUX2-I
OCC
E-GND
S-BUS
S-BUS
AUX1-0
Y2I
CO2
SENSOR
2-10 VDC
IAQ (2-10V)
IAQ COM
IAQ 24V
Y2O
Y1I
(OPTIONAL)
ACT (2-10V)
ACT COM
ACT 24V
Y1O
C R
1K1
TR
R(+)
24 VAC
TR1
M7215
C(-)
IN
+
3
IN
-
THERMOSTAT
OUTSIDE AIR
TEMP/HUMIDITY (ENTHALPY)
SYLKBUS SENSOR
1
IN THIS CONFIGURATION, AN OPTIONAL DISCHARGE AIR TEMP/HUMIDITY
(ENTHALPY) SYLKBUS SENSOR CAN BE ADDED FOR ADVANCED
CONTROL AS SHOWN IN THE LOWER LEFT OF THIS FIGURE.
1
2
3
DO NOT USE THE C7250 20K NTC SENSOR WITH THE OA TERMINAL IN THIS
CONFIGURATION.
RETURN AIR
TEMP/HUMIDITY (ENTHALPY)
SYLKBUS SENSOR
WHEN USING A HEAT PUMP THERMOSTAT OR A PROGRAMMABLE THERMOSTAT,
THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O OR B AND W2
MAY BE LABELED W.
4
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION
RELAY BETWEEN O AND C.
M32565B
Fig. 4. Economizer with Sylk Bus sensors for enthalpy configuration with Honeywell M7215 black motor.
5
62-0331—07
Download from Www.Somanuals.com. All Manuals Search And Download.
JADE™ ECONOMIZER MODULE
2
ROOF TOP UNIT
MA TEMP
SENSOR
20K NTC
W7220 ECONOMIZER CONTROLLER MODULE
O/B
Y1
W1
G
OCC
Y2
W2
4
1K1
MA
MA
AUX2-I
OCC
E-GND
S-BUS
S-BUS
AUX1-0
Y2I
IAQ (2-10V)
IAQ COM
IAQ 24V
ACT (2-10V)
ACT COM
ACT 24V
CO2
SENSOR
2-10 VDC
Y2O
Y1I
(OPTIONAL)
Y1O
C R
1K1
R(+)
24 VAC
C(-)
MS7503 OR MS7505
3
3
OUTSIDE AIR
TEMP/HUMIDITY (ENTHALPY)
SYLKBUS SENSOR
THERMOSTAT
1
IN THIS CONFIGURATION, AN OPTIONAL DISCHARGE AIR TEMP/HUMIDITY
(ENTHALPY) SYLKBUS SENSOR CAN BE ADDED FOR ADVANCED
CONTROL AS SHOWN IN THE LOWER LEFT OF THIS FIGURE.
1
RETURN AIR
TEMP/HUMIDITY (ENTHALPY)
SYLKBUS SENSOR
2
3
DO NOT USE THE C7250 20K NTC SENSOR WITH THE OA TERMINAL IN THIS
CONFIGURATION.
WHEN USING A HEAT PUMP THERMOSTAT OR A PROGRAMMABLE THERMOSTAT,
THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O OR B AND W2
MAY BE LABELED W.
4
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION
RELAY BETWEEN O AND C.
M32566B
Fig. 5. Economizer with Sylk Bus sensors for enthalpy configuration with a Honeywell MS7505 or MS7503 Direct
Coupled Actuator.
62-0331—07
6
Download from Www.Somanuals.com. All Manuals Search And Download.
JADE™ ECONOMIZER MODULE
ROOF TOP UNIT
MA TEMP
SENSOR
20K NTC
W7220 ECONOMIZER CONTROLLER MODULE
O/B
Y1
OCC
W1
G
Y2
W2
4
1K1
MA
MA
AUX2-I
OCC
E-GND
S-BUS
S-BUS
AUX1-0
Y2I
IAQ (2-10V)
IAQ COM
IAQ 24V
ACT (2-10V)
ACT COM
ACT 24V
CO2
SENSOR
2-10 VDC
Y2O
Y1I
(OPTIONAL)
Y1O
C R
1K1
R(+)
24 VAC
1
2
C(-)
2
MS3103J
OR MS3105J
3
4
5
S-BUS
S-BUS
3
THERMOSTAT
1
IN THIS CONFIGURATION, AN OPTIONAL DISCHARGE AIR TEM/HUMIDITY
(ENTHALPY) SYLKBUS SENSOR CAN BE ADDED FOR ADVANCED
CONTROL AS SHOWN IN THE LOWER LEFT OF THIS FIGURE.
C7400S
OUTSIDE AIR
TEMP/HUMIDITY (ENTHALPY)
SYLKBUS SENSOR
2
3
THE S-BUS COMPONENTS MAY BE DAISY CHAINED TO ANOTHER S-BUS
COMPONENT.
WHEN USING A HEAT PUMP THERMOSTAT OR A PROGRAMMABLE
THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE
LABELED O OR B AND W2 MAY BE LABELED W.
C7400S
RETURN AIR
TEMP/HUMIDITY (ENTHALPY)
SYLKBUS SENSOR
1
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN
ISOLATION RELAY BETWEEN O AND C.
4
M32653B
Fig. 6. Economizer with Sylk bus sensor for enthalpy configuration with Honeywell MS3103 or MS3105 communicating
actuators.
EXH1 OR AUX1 O
C
1
2
V
ACTUATOR
NOTE: ON/OFF ACTUATORS CAN BE USED ON THE EXH1 OR AUX1
O TERMINAL WITH GROUND TO THE C TERMINAL. WHEN
PROGRAMMING THE EXH1 OR AUX1 O, THE % IS THE PERCENT
OPEN POSITION OF THE OUTDOOR AIR DAMPER WHEN THE
EXH1 OR AUX1 O TERMINAL IS ENERGIZED AND THE 2-POS
DAMPER GOES OPEN. IF USING THE AUX1 O TERMINAL
PROGRAM AUX1 O FOR EXH2.
M33409
Fig. 7. 2-position actuator.
7
62-0331—07
Download from Www.Somanuals.com. All Manuals Search And Download.
JADE™ ECONOMIZER MODULE
ECONOMIZING
AVAILABLE
DUAL ENTHALPY
HIGH LIMIT
NOT AVAILABLE
SINGLE ENTHALPY
P2 (T,RH)
P1
(T,RH)
ES5
ES4
ES3
ES2
ES1
HL
TEMPERATURE
M32286
Fig. 8. Single Enthalpy curves and boundaries.
Table 1. Single Enthalpy and Dual Enthalpy High Limit Curves.
Point P1
Point P2
Humidity %RH
Enthalpy
Curve
Temp.
Temp.
Enthalpy
Dry-Bulb (°F)
Dewpoint (°F)
(btu/lb/da) Temp. °F
Humidity %RH
Temp. °F
66.3
ES1
ES2
ES3
ES4
ES5
HL
80.0
75.0
70.0
65.0
60.0
86.0
60.0
57.0
54.0
51.0
48.0
66.0
28.0
26.0
24.0
22.0
20.0
32.4
80.0
75.0
70.0
65.0
60.0
86.0
36.8
39.6
42.3
44.8
46.9
38.9
80.1
80.0
81.4
84.2
88.5
80.3
63.3
59.7
55.7
51.3
72.4
Power Up
After the module is mounted and wired, apply power.
Power Loss (Outage or Brownout)
a
All setpoints and advanced settings are restored after any
power loss or interruption.
Power Up Delay
Upon power up (or after a power outage or brownout), the
W7220 controller module begins a 5 minute power up delay
before enabling mechanical cooling.
NOTE: If power goes below 18 Vac, the W7220 controller
module assumes a power loss and the 5 minute
power up delay will become functional when
power returns above 18 Vac.
Initial Menu Display
TROUBLESHOOTING
On initial start up, Honeywell displays on the first line and
Economizer W7220 on the second line. After a brief pause,
the revision of the software appears on the first line and the
second line will be blank.
Alarms
The Economizer module provides alarm messages that
display on the 2-line LCD.
NOTE: Upon power up, the module waits several sec-
onds before checking for alarms. This allows
time for all the configured devices (e.g. sensors,
actuator) to become operational. If one or more
alarms are present and there has been no keypad
activity for at least 5 minutes, the Alarms menu
displays and cycles through the active alarms.
You can also navigate to the Alarms menu at any time.
a
All settings are stored in non-volatile flash memory.
62-0331—07
8
Download from Www.Somanuals.com. All Manuals Search And Download.
JADE™ ECONOMIZER MODULE
To clear an alarm, perform the following:
Table 2. Alarms Menu.
Alarm
1. Navigate to the desired alarm.
2. Press the ↵ button.
Menu
ALARMS(_)
3. ERASE? displays.
MA T SENS ERR
CO2 SENS ERR
OA T SENS ERR
DA ENTHL ERR
4. Press the ↵ button.
5. ALARM ERASED displays.
6. Press the
button (MenuUp/Exit) to complete the
action and return to the previous menu.
a
SYS ALARM
NOTE: If an alarm still exists after you clear it, it re-dis-
plays within 5 seconds.
b
ACT Over Voltage
b
NOTE: Jade will be in the "set up" mode for the first 60
minutes after powered. If a sensor for OA air or
Sylkbus device (sensor, actuator) is discon-
nected during the set up mode, the Jade will not
alarm that failure. The MA sensor is a system
"critical" sensor; if the MA sensor is removed
during the set up mode, the Jade will alarm. After
60 minutes the Jade controller will change to
operation mode and all components removed or
failed will alarm in the operation mode.
ACT Under Voltage
b
ACT Stalled
NOTES:
1.
The Alarms menu displays only when alarm(s)
are active and includes the number of active
alarms in parenthesis ().
The alarms listed are a few examples. Additional
alarms display depending on the parameter set-
tings and configuration.
2.
a
When AUX1 O is set to SYS and there is any alarm (e.g., failed sensors,
etc.), the AUX1 O terminal has 24 Vac out and the LCD displays the
ALARM.
This alarm is only displayed when a communicating actuator is used. (ex:
MS3105AJ)
b
Clearing Alarms
Once the alarm has been identified and the cause has been
removed (e.g. replaced faulty sensor), the alarm can be
cleared from the display.
9
62-0331—07
Download from Www.Somanuals.com. All Manuals Search And Download.
JADE™ ECONOMIZER MODULE
COMMON INSTALLATION ISSUES AND CONCERNS
Table 3. Installation Issues and Concerns.
Area
Issue or Concern
Possible Cause and Remedy
Configuration
Are the old sensors in the unit No, the C7400A and C7150 sensors are not compatible with the W7220. The enthalpy sensor
(C7400A, C7150 or C7232)
for the W7220 is the C7400S. The Mixed Air or Outdoor air dry bulb sensors are the C7250A.
compatible with the economizer The C7232 CO sensor is compatible with the W7220.
2
controller?
The unit has a W7459
If you have a W7459 economizer with a M7415 motor you will need to change to a M7215
motor. The W7220 has a 2 to 10 Vdc out to the motor, so you will need a M7215 motor. The
economizer and black motor.
Do I need to change the motor? M7215 motors are used with the W7212 economizers. So if you have one of these units, you
will not have to change the motor.
Wiring
I have 4 terminals on my
actuator and the wiring only
shows 3 wires.
The economizer 24 Vac COM can be wired to the Honeywell actuator common (
TR1). The actuators have internal ground circuits.
or
There is an Earth Ground
terminal. Do I need to wire to
earth ground?
Yes, the economizer must be wired to earth ground.
What are the part numbers of The 2-pin connectors are Honeywell part number 50048926-001 and the 6-pin connectors
the 2 and 6 pin side
connectors?
are Honeywell part number 50048926-002. Both are available in accessory bags of 20 each.
62-0331—07
10
Download from Www.Somanuals.com. All Manuals Search And Download.
JADE™ ECONOMIZER MODULE
Table 3. Installation Issues and Concerns. (Continued)
Issue or Concern Possible Cause and Remedy
Operation or Use My outdoor temperature Check the sensor wiring. Enthalpy sensors are to be wired to the Sylk Bus terminals.
Area
reading on the STATUS menu is Temperature sensors are to be wired to the OAT and MAT terminals.
not accurate.
If my enthalpy sensor drifts in The sensors are not able to be re-calibrated in the field. However there is a menu item under
accuracy over time, can I re-
calibrate it?
the ADVANCED menu where you are able to input a limited offset in temperature and
humidity for each sensor you have connected to the economizer.
Can I go back to factory
defaults and start over?
Under the SYSTEM SETUP menu you can change the setpoints to the factory defaults.
Will I be able to see the LCD
screen when it is in the unit?
The LCD screen has a backlight that is always illuminated.
What is a good setpoint for the The mixed air temperature is the temperature of air that you want to supply to the space. In a
Mixed Air Temperature (MAT)? commercial building, this is between 50 to 55°F (10 to 13°C). The mixed air is the mixing of
the return air and the outdoor air.
I am using enthalpy sensors.
In the event the humidity sensor in the enthalpy sensors fails, the backup algorithm in the
Why did the control ask me to control is to default to the temperature sensor in the enthalpy sensor.
input a dry bulb changeover
temperature?
In checkout, the outdoor
damper closes when I
command it open.
Check the actuator linkage or rotation. In the CHECKOUT mode, the outdoor damper should
drive open or closed with the return air damper having the opposite effect.
How do I set my minimum
position?
The minimum position is set using the VENTMIN and VENTMAX setup in the SETPOINTS
menu. VENTMIN is the minimum ventilation required when using an occupancy sensor and
VENTMAX is the minimum ventilation when not using an occupancy sensor for Demand
Control Ventilation. The VENTMAX position is set the same as with the potentiometer on the
analog economizers and is the output voltage to the damper actuator. The range is 2 Vdc
closed OA damper and 10 Vdc open OA damper.
What if my damper does not go Check the damper linkage or hub to make sure the damper is able to close completely.
completely closed in the
checkout operation?
How do I set the OCC?
There are two settings for the OCC setting, INPUT and ALWAYS. INPUT is from the space
thermostat, if it has an occupancy output. ALWAYS is the unit in the occupied mode, if the
economizer is powered (fan on).
Does the economizer save my Yes, once the changes are stored in the controller they will be stored until they are changed
program values if the unit loses by the operator.
power?
If the unit is left in checkout,
how long will the unit stay in
checkout mode without input?
The unit will remain in checkout for 10 minutes, then return to normal operation.
11
62-0331—07
Download from Www.Somanuals.com. All Manuals Search And Download.
JADE™ ECONOMIZER MODULE
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
® U.S. Registered Trademark
© 2012 Honeywell International Inc.
62-0331—07 M.S. Rev. 02-12
Printed in United States
Golden Valley, MN 55422
customer.honeywell.com