| V4055F,G Fluid Power Actuator   with Manual Control   PRODUCT DATA   FEATURES   • Fast opening time of 13 seconds at 120 V, 60 Hz.   • Maximum closing time, is 1 second, which meets approval   body requirements.   • • Unit available with FM approved proof of closure switch.   Red “OPEN” indicator attached to the actuator piston will   show if the valve is even slightly open; yellow “SHUT”   indicator on the valve stem will show only when the gas   valve is fully closed.   • Ambient temperature rating of -40°F to +150°F (-40°C to   +66°C).   • • Valve and actuator may be mounted in any position.   Optional, field-adjustable, spdt auxiliary switch, rated at   112 hp (0.37 kW), may be added in the field.   • Standard enclosure meets NEMA 1 (IP30) general   purpose requirements.   • • • Red light indicates when valve is ready to open.   Rocker switch allows manual operation of valve.   Valve closes on power loss.   APPLICATION   The V4055F and G fluid power gas valve actuators are for use   with the V5055 valve for gas safety shutoff applications to   control the gas supply of commercial and industrial burners.   NOTICE: Per Industry standards, the actuator is required a   conduit seal or a cable type that is sealed be installed in a   device that can result in a flammable liquid flow through a   conduit or cable to an electrical ignition source in the event of   a seal leakage or diaphragm failure.   Contents   Application ........................................................................   Specifications ...................................................................   Operation ..........................................................................   Ordering Information ........................................................   Installation ........................................................................   Wiring ...............................................................................   Checkout and Service ......................................................   1 2 2 2 3 5 5 65-0029-02   V4055F,G FLUID POWER ACTUATOR WITH MANUAL CONTROL   Fig. 1. Approximate mounting dimensions of V4055 actuators and V5055 valves, in inches. (mm).   2 6-3/4 (172)   3-23/32 (95)   5 (127)   27/32 (22)   KNOCKOUT   FOR1/2 INCH   CONDUIT (4)   1 2 3 ALLOW 4 INCHES (102 MM) CLEARANCE FOR ACTUATOR   REMOVAL.   ADD 1/8 INCH (3 MM) TO DIMENSION FOR MODELS WITH   NEMA 4 ENCLOSURE.   1-9/32   (33)   ADD 1/4 INCH (6 MM) TO DIMENSION FOR A MODELS WITH   NEMA 4 ENCLOSURE.   1 3 A 3/4 (19) BOLT   HOLES [8] ON   3-3/4 (95)   C RADIUS   B E 9-3/16   (233)   1/2 INCH NPT UPSTREAM   TAP AND PLUG (OPTIONAL   ON DOMESTIC MODELS)   OCTAGON   F D 1/8 OR 1/4 INCH NPT   DOWNSTREAM TAP   AND PLUG (OPTIONAL   ON DOMESTIC MODELS)   1/4 INCH NPT UPSTREAM   TAP AND PLUG (1/4 BSP ON   INTERNATIONAL MODELS)   D VALVE   SIZE   INCH   3/4   1 DIM C   DIM D   DIM E   IN. MM   DIM F   OCTAGON   DIM A   DIM B   IN.   MM   IN.   MM   IN.   MM   IN.   MM   IN.   MM   IN.   MM   4-13/16   4-13/16   4-13/16   4-13/16   7-19/32   7-19/32   7-19/32   13-1/8   13-1/8   333.5   333.5   333.5   333.5   336.5   349.0   349.0   2-3/4   2-3/4   2-3/4   2-3/4   2-7/8   3-3/8   3-3/8   70.0   70.0   70.0   70.0   73.0   85.5   85.5   8-3/16   8-3/16   8-3/16   8-3/16   8-5/16   208.0 5-3/4 146.0 2-1/4 57.0   208.0 5-3/4 146.0 2-1/4 57.0   208.0 5-3/4 146.0 2-1/4 57.0   208.0 5-3/4 146.0 2-1/4 57.0   211.1 8-3/8 212.5 2-3/4 70.0   2-13/16   2-13/16   2-13/16   2-13/16   3-1/2   71.0   71.0   122.0   122.0   122.0   122.0   192.5   192.5   192.5   1-1/4 13-1/8   1-1/2 13-1/8   71.0   71.0   2 13-1/4   2-1/2 13-3/4   89.0   8-13/16 224.0 9-1/4 235.0 2-3/4 70.0   8-13/16 224.0 9-1/4 235.0 2-3/4 70.0   4-1/2   114.5   114.5   3 4 13-3/4   4-1/2   16-3/16 411.0 5-13/16 128.0 11-7/32 285.0 12-1/2 317.5 4-5/8 117.0   M23960A   3. Installer must be a trained, experienced, flame safeguard   control technician.   After installation is complete, check out product operation as   provided in these instructions.   INSTALLATION   When installing this product...   NOTICE: Per Industry standards, the actuator is required a   conduit seal or a cable type that is sealed be installed in a   device that can result in a flammable liquid flow through a   conduit or cable to an electrical ignition source in the event of a   seal leakage or diaphragm failure.   1. Read these instructions carefully. Failure to follow them   could damage the product or cause a hazardous   condition.   2. Check the ratings given in the instructions and on the   product to make sure the product is suitable for your   application.   4.   3 65-0029-02   V4055F,G FLUID POWER ACTUATOR WITH MANUAL CONTROL   CAUTION   Electrical Shock and Equipment Damage Hazard.   Can cause serious injury or death.   1. Disconnect power supply before making wiring   connections to prevent electrical shock and   equipment damage.   2. All wiring must comply with all applicable electrical   codes, ordinances and regulations. All wiring must   be NEC Class 1.   3. Voltage and frequency of the power supply   connected to this control must agree with those   marked on the device.   4. Maximum total connected load to both switches (if   used) must not exceed 1800 VA.   WARNING   Can cause explosion, serious injury or death.   1. Turn off gas supply before starting installation.   2. Disconnect power supply for valve actuator before   beginning installation.   Explosion Hazard.   133568   AUXILIARY   SWITCH   133569   VALVE-   CLOSED   INDICATION   SWITCH   3. Install the valve so the arrow on the valve body   points in the gas flow direction.   Install Valve   The actuator is mounted directly on the valve bonnet after the   valve is installed in the gas supply line. Refer to the instruction   sheet packed with the gas valve for details of installation. When   installing the valve, ensure that:   EACH SWITCH SECURED   BY TWO SCREWS FROM   UNDERSIDE OF BASE   ADJUSTING SCREW   FOR AUXILIARY SWITCH   IF ONLY ONE SWITCH IS   USED, INSTALL BARRIER   IN OPEN POSITION   M23961A   1. Sufficient clearance.is left for installation and service of   the actuator.   2. Ambient temperatures at the valve location will remain   within -40°F to +150°F (-40°C to +66°C).   Fig. 2. V4055 actuator with cover removed.   NOTE: A V5055A, B or D valve can also be fitted with a bon-   net assembly with 2 seals to provide a valve seal   overtravel interlock.   Install Accessory Switches (If Needed)   A SPDT switch may be installed to operate an auxiliary load up   to 1/2 hp (0.37 kW). The switch may be adjusted to operate at   any point in the valve stroke.   The SPDT valve-closed indication switch is installed to make or   break a circuit when the valve is in the closed position. The   switch is not adjustable.   A valve-closed indication switch may also be installed on any   V4055 actuator to provide a valve seal overtravel interlock   (valve-closed indication) when used with a V5055C or E valve   (with double seal).   NOTE: Mark the actuator or valve to indicate any changes   made.   To install the switches, proceed as follows:   1. Remove the actuator faceplate (2 screws).   2. Remove the silver-colored barrier to expose the actuator   stem.   3. Insert the auxiliary switch in the position indicated in Fig.   2. Fasten with 2 screws through the actuator base.   4. Insert the valve-closed indication switch in the position   shown in Fig. 2. The valve-closed indication switch   mounts against the side of the actuator housing. The   mounting holes are spaced to mount the switch only in   the correct position. Fasten with 2 screws through the   actuator base.   5. If only 1 switch is used, install the narrow barrier included   with the switch in the unused space.   6. Mount the actuator before making wiring connections   and adjustments to the switch.   65-0029-02   4 V4055F,G FLUID POWER ACTUATOR WITH MANUAL CONTROL   Mount Actuator On Valve   Check the final position of the valve body to be sure that the   actuator will be in the proper position when mounted on the   valve.   L1   HOT   1 1 2 L2   If two smaller size valves are mounted very close together, as   in an Industrial Risk Insurers (formerly F.I.A.) type valve train, it   may be necessary to mount the actuator “off center” to provide   adequate clearance.   PROOF-OF-CLOSURE   SWITCH   Slip the bottom collar of the actuator over the valve bonnet   assembly. Rotate the actuator to the desired position and use a   5/32 inch Allen wrench to tighten the two setscrews securely   (50 to 60 Ib.-in. [5.7 to 6.8 N.m]).   AUXILIARY   SWITCH   C C NC   NO   NC   NO   WIRING   Disconnect power supply before making wiring connections to   prevent electrical shock and equipment damage. Wiring must   comply with all applicable electrical codes, ordinances, and   regulations. Wiring to the actuator must be NEC Class 1.   2 2 3 3 Connect the power supply to terminals 1 and 2 on the V4055   terminal strip. Refer to Fig. 3 for auxiliary switch connections.   For typical system hookups, refer to instructions packed with   device used to control valve.   1 2 3 POWER SUPPLY. PROVIDE OVERLOAD PROTECTION AND   DISCONNECT MEANS AS REQUIRED.   SWITCH BETWEEN THESE TWO LEADS IS CLOSED WHEN   VALVE IS SHUT (DE-ENERGIZED).   When all wiring connections are complete, replace the actuator   faceplate.   SWITCH BETWEEN THESE TWO LEADS IS OPEN WHEN   VALVE IS SHUT (DE-ENERGIZED).   M7334B   NOTICE: Per Industry Standards, the actuator is required a   conduit seal or a cable type that is sealed be installed in a   device that can result in a flammable liquid flow through a   conduit or cable to an electrical ignition source in the event of a   seal leakage or diaphragm failure.   Fig. 3. External connections to the V4055 actuator.   Adjust The Auxiliary Switch (If Used)   The auxiliary switch is adjustable throughout the stroke of the   actuator. With the switch installed in the actuator, turn the   adjusting screw (Fig. 2) clockwise   operate earlier in the stroke or counterclockwise   cause the switch to operate later in the stroke.   to cause the switch to   to   NOTE: The valve-closed indication switch is not adjustable.   CHECKOUT AND SERVICE   CAUTION   Only a trained, experienced, flame safeguard control   service technician should check out and service this   control.   Checkout   After the installation is complete, cycle the valve several times   with the manual fuel shutoff cock closed before testing the   system in actual operation.   Service   The actuator is not field repairable, except for replacing the   auxiliary switch, valve-closed indication switch, and READY TO   OPEN light. See INSTALLATION section for procedure. Do not   disassemble the valve actuator.   If the actuator should fail to operate properly, replace it.   5 65-0029-02   V4055F,G FLUID POWER ACTUATOR WITH MANUAL CONTROL   1. Turn off the gas supply at the manual shutoff valve   located upstream from the valve(s) being serviced.   2. Shut off all electrical power to the valve actuator(s).   3. Mark and disconnect the wires from the actuator termi-   nals. Remove conduit and disengage the damper linkage   assembly (if applicable.   the bonnet assembly is seated. Tighten the   remaining bolts. Torque the bolts as   follows:   Valve Size   Torque   55 in.-lb.   75 in.-lb.   3/4 in. (19 mm) to 1-1/2 in. (38 mm)   2 in. (51 mm) to 4 in. (102 mm)   4. Loosen the two set screws from the valve to lift off the   actuator.   5. If the actuator is to be replaced and it did not leak   hydraulic fluid, skip to Step 11.   11. Remount the actuator on the bonnet assembly. Tighten   the two set screws (50-60 inch pounds.   NOTE: It is good practice to inspect the inside of the   valve whenever the actuator is replaced. To do   so, remove the bonnet assembly, inspect the   valve and bonnet. If all is well, proceed to Step   7.   12. Replace the damper crank arm assembly.   13. Re-attach the wires removed from the actuator terminals   and turn on the electrical power.   14. With the gas still off, cycle the actuator to check for   proper mechanical operation.   6. If the actuator leaked hydraulic fluid onto the valve (the   fluid is red), it must be cleaned off from the valve and   bonnet assembly.   CAUTION   Be sure to perform a bonnet seal and seat leak check   after installation.   a. Wipe off the outer valve body.   b. Remove the valve bonnet bolts and lift off the bonnet.   Be sure to read and follow all instructions that come   with the actuators, valves, seal and bonnet kits.   NOTE: V5055/V5097C and E Valves have additional   internal springs that will push the bonnet up as   the bolts are loosened.   Table 3. Replacement Bonnets for   V5055/V5097 Gas Valves.   c. Inspect the inside of the valve.   Replacement   Bonnet**   Valve Size (in   inches.)   Valve   V5097A   IMPORTANT   If fluid is present on the inside surfaces of the valve   body or bonnet surfaces, the bonnet assembly or   entire valve must be replaced. See Table 3 below for   the bonnet assembly part number.   133398AA   133417AA   V5055A   3/4, 1, 1-1/4, 1-1/2   2, 2-1/2, 3   Not Available (On-Off)   4 133398BA   133417BA   V5055B   V5097B   3/4, 1, 1-1/4, 1-1/2   2, 2-1/2, 3   d. If the inside surfaces are clear of hydraulic fluid,   clean the bonnet assembly and be sure to remove all   hydraulic fluid from the inside and outside of the   actuator mounting curb. This is the “cup-like” area   around the valve stem. Avoid using a cleaning solu-   tion as it may damage the rubber seals used in the   valve.   Not Available (Characterized Guide)   4 133398CA   133417CA   136911CA   V5055C   V5097C   3/4, 1, 1-1/4, 1-1/2   2, 2-1/2, 3   (Proof of Closure)   4 7. If the valve bonnet assembly is in good condition and is   not replaced, replace the bonnet seal. Do not reuse the   old bonnet seal. See Table 4 below for the seal number.   8. Coat seals with grease provided and position in valve   body/bonnet assembly.   9. Carefully seat the bonnet assembly on the valve body.   Be sure the seals are in their proper position. On those   valves with a spring below the disc, be sure the spring is   centered in the indentation on the inside of the valve   body.   Not Available V5055D   Not Available   V5097D   V5097E   3/4, 1, 1-1/4, 1-1/2   2, 2-1/2, 3   136308BA   V5055E   3/4, 1, 1-1/4, 1-1/2   2, 2-1/2, 3   Not Available   **Each replacement assembly contains the bonnet assembly,   two rubber seals, and a tube of grease. It must be used only on   the type of valve indicated above.   10. After positioning the bonnet assembly, replace the   screws removed earlier.   Table 4. Gas Valve Replacement Seals.   Replacement Seal   NOTE: When replacing the bonnet assembly on the 4-   inch valve, draw it evenly into the valve body.   Finger-tighten the eight bolts. Draw the bonnet   assembly into the valve by tightening, in order,   bolts 1, 5, 7 and 3 (two turns each). Repeat until   Assy #   Valve Size (in inches.)   133393A   3/4, 1, 1-1/4, 1-1/2   133392A   137253A   2, 2-1/2, 3   4 65-0029-02   6 V4055F,G FLUID POWER ACTUATOR WITH MANUAL CONTROL   7 65-0029-02   V4055F,G FLUID POWER ACTUATOR WITH MANUAL CONTROL   Automation and Control Solutions   Honeywell International Inc.   1985 Douglas Drive North   ® U.S. Registered Trademark   © 2012 Honeywell International Inc.   65-0029-02 JPG Rev. 11-12   Printed in United States   Golden Valley, MN 55422   customer.honeywell.com   |