Carrier Ceiling Suspended Duct Free Split System 40QAC User Manual |
40QAC / 38HDR
40QAQ / 38QRR
Ceiling---Suspended Duct Free Split System
Sizes 018 to 060
Installation Instructions
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory--authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions included in
literature and attached to the unit. Consult local building codes and
current editions of the National Electrical Code ( NEC ) NFPA 70.
In Canada, refer to current editions of the Canadian electrical code
CSA 22.1.
40QAC, QAQ Unit
!
Recognize safety information. This is the safety--alert symbol
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury. Understand
these signal words; DANGER, WARNING, and CAUTION. These
words are used with the safety--alert symbol. DANGER identifies
the most serious hazards which will result in severe personal injury
or death. WARNING signifies hazards which could result in
personal injury or death. CAUTION is used to identify unsafe
practices which would result in minor personal injury or product
and property damage. NOTE is used to highlight suggestions
which will result in enhanced installation, reliability, or operation.
!
WARNING
the environmentally sound refrigerant
ELECTRICAL SHOCK HAZARD
38HDR, QRR Unit
Failure to follow this warning could result in personal
injury or death.
NOTE: Read the entire instruction manual before starting the
installation.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF
position. There may be more than 1 disconnect switch.
Lock out and tag switch with a suitable warning label.
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
!
CAUTION
Failure to follow this warning could result in personal injury or
equipment damage.
PERSONAL INJURY AND EQUIPMENT DAMAGE
HAZARD
Puron refrigerant systems operate at higher pressures than
standard R--22 systems. To avoid damage to the unit or
possible personal injury, do not use R--22 service equipment or
components on Puron refrigerant equipment.
Failure to follow this caution may result in personal injury
and / or equipment damage.
DO NOT operate the unit without a filter or with grille
removed.
4 6 0 - 3 - 6 0
2 0 8 / 2 3 0 - 3 - 6 0
2 3 0 - 1 - 6 0
2 0 8 - 2 3 0 - 1 - 6 0
3
4 6 0 - 3 - 6 0
2 0 8 / 2 3 0 - 3 - 6 0
2 3 0 - 1 - 6 0
2 0 8 - 2 3 0 - 1 - 6 0
4
4 6 0 - 3 - 6 0
2 0 8 / 2 3 0 - 3 - 6 0
2 3 0 - 1 - 6 0
2 0 8 - 2 3 0 - 1 - 6 0
5
4 6 0 - 3 - 6 0
2 0 8 / 2 3 0 - 3 - 6 0
2 3 0 - 1 - 6 0
2 0 8 - 2 3 0 - 1 - 6 0
6
These installation instructions cover the installation of the matched
systems listed in table 2.
Table 2 – Matched Systems
System
Type
Nominal
Capacity
Outdoor Unit
Indoor Unit
Parts List
Indoor Unit
40QAC 024 --- --- --- 3
*
018
38HD R018 --- --- --- 3
024
030
036
048
060
018
024
030
036
048
060
38HD R024 --- --- --- 3
38HD R030 --- --- --- 3
40QAC 024 --- --- --- 3
40QAC 036 --- --- --- 3
40QAC 036 --- --- --- 3
40QAC 048 --- --- --- 3
40QAC 060 --- --- --- 3
40QAQ024 --- --- --- 3
40QAQ024 --- --- --- 3
40QAQ036 --- --- --- 3
40QAQ036 --- --- --- 3
40QAQ048 --- --- --- 3
40QAQ060 --- --- --- 3
The following items are included with the indoor unit:
Table 1 – Installation Materials
38HDR036--- --- ---3/5/6
38HDR048--- --- ---3/5/6
38HDR060--- --- ---3/5/6
38QRR018 --- --- --- 3
Part No.
Name of Part
Side Panels
Hex Head Bolts
Mounting Bracket
Pistons
Qty.
2
4
2
1
1
2
3
4
5
6
38QRR024 --- --- --- 3
38QRR030 --- --- --- 3
Installation Template
Adapter Tubes
1
2
38QRR036--- --- ---3/5/6
38QRR048--- --- ---3/5/6
38QRR060--- --- ---3/5/6
* Units must be configured for 1---1/2 ton operation. Refer to instructions
on page 9.
SYSTEM REQUIREMENTS
Clearances
Allow sufficient space around the indoor and outdoor unit for
proper airflow circulation and servicing. Refer to Fig. 1 through
Fig. 5 for minimum required clearances.
Piping: Piping and insulation is field supplied.
Piping Lengths
The minimum length between the indoor and outdoor units is 10 ft
(3 m). Refer to table 3 for the maximum lengths allowed.
A09532
Fig. 6 -- Hanging Fan Coil Unit
Table 3 – Maximum Refrigerant Line Lengths
Unit
Size
Max Line
Length ft(m)
Max Elevation (ID
over OD) ft(m)
Max Elevation (OD
over OD) ft(m)
Outdoor Unit
The following items are included with the outdoor unit:
18K
24K
30K
36K
48K
60K
200 (61)
200 (61)
200 (61)
200 (61)
200 (61)
200 (61)
65 (19.8)
65 (19.8)
65 (19.8)
65 (19.8)
65 (19.8)
65 (19.8)
200 (61)
200 (61)
200 (61)
200 (61)
200 (61)
200 (61)
Note:For lengths greater than 25 ft (7.6 m), refer to the Duct Free Long
Line Guide.
Pipe Sizes
Refer to table 4 for pipe sizes.
A09536
Table 4 – Pipe Sizes
Fig. 7 -- 38HDR018--036
PIPE SIZES (in)
Vapor
Unit Size
Liquid Phase
38HDR
5/8
38QRR
5/8
5/8
3/4
3/4
3/4
3/4
18
24
30
36
48
60
3/8
3/8
3/8
3/8
3/8
3/8
5/8
3/4
3/4
7/8
7/8
Note:On heat pumps, both lines need to be insulated using at least 1/2 inch
closed foam insulation.
A09537
Fig. 8 -- 38QRR018--036
Piston
Cap
---
Flare
Model
Filter Drier
Pistons
Connector
38HDR
38QRR
n
n
---
n
---
n
n
7
Refrigerant Charge
Power and Connecting Cables -- Field Supplied
The 38HDR and 38QRR units can be matched with multiple
outdoor units and thus additional charge might be required when
matched with the 40QAC or 40QAQ units.
Power:
S The main power is supplied to both the indoor and outdoor
units.
Table 5 – Additional Charge
S Consult local building codes, NEC (National Electric Code) or
CEC (Canadian Electric Code) for any special requirements.
S Use Table 7 for the electrical requirements for the outdoor units
and Table 8 for the indoor units to correctly size the cables and
disconnect switches.
Additional Charge lb. (kg.)
Unit Size
018
024
030
036
38HDR
0.7 (0.32)
1.3 (0.59)
1.4 (0.64)
0.2 (0.1)
0.2 (0.1)
0.5 (0.23)
38QRR
0.7 (0.32)
0.8 (0.36)
0
0.5 (0.23)
048
060
0
0
Control Wiring
Thermostat wires should be used for control wiring between the
indoor and outdoor units. A two conductor cable is required for
the cooling only units and a seven conductor cable is required on
heat pumps. 18 AWG is recommended for any length up to 200 ft
(61.0 m).
Note:The above additional charge is required amount for line lengths up to
25 ft (7.6 m). For line lengths exceeding 25 ft (7.6 m), additional charge will
be required. Refer to the Duct Free Splits Long Line Guide.
Metering Device
The 40QAC and 40QAQ units use an accurator or a TXV as
shown in Table 6.
User Interface -- Finished Goods Accessory
Any of the following three thermostats can be used depending on
the type of system on hand and the desired features. Refer to Table
9 to select the proper thermostat.
Table 6 – Accurator Sizes
Cooling Only
40QAC
TVX
Heat Pumps
Unit Size
40QAQ
38QRR
018
024
030
036
048
060
49
55
65
70
80
TXV
40
43
55
63
73
80
TVX
TVX
TVX
TVX
TVX
NOTE: Pistons are supplied with either the indoor or outdoor units.
Table 7 – 38HDR / QRR Electrical Requirements
38HDR
FUSE/HACR BKR
38QRR
UNIT SIZE
V --- P H --- H z
MIN CKT AMPS
MIN CKT AMPS
FUSE/HACR BKR AMPS
AMPS
018
024
030
208/230---1---60
208/230---1---60
208/230---1---60
208/230---1---60
208/230---3---60
460 --- 3 --- 60
12.1
17.7
19.1
19.1
13.0
7.9
20
12.1
18.8
17.5
20.9
14.1
7.9
20
30
30
30
20
15
50
30
15
60
40
15
25
30
30
20
036
048
060
15
208/230---1---60
208/230---3---60
460 --- 3 --- 60
26.4
17.9
8.4
40
34.6
22.4
10.0
34.5
23.6
10.6
25
15
208/230---1---60
208/230---3---60
460 --- 3 --- 60
34.5
21.5
10.6
60
30
15
Table 8 – 40QAC / QAQ Electrical Requirements
40QAC
40QAQ
MOCP
15.0
VOLTAGE
UNIT
V --- P h --- 6 0 H z
MCA
0.63
1.60
2.00
3.30
MOCP
15.0
MCA
9.29
024
036
048
060
208/230---1
208/230---1
208/230---1
208/230---1
15.0
17.70
23.80
28.70
20.0
15.0
25.0
15.0
30.0
Table 9 – Thermostat Selection
System Type
Model Number
Cooling Only & HP
53DFS250---SL
Cooling Only
53DFS250---FS
Cooling Only
53DFST2---NP
7 Day Programmable
5+1+1 Day Programmable
Remote Room Sensor
Dry Contact Equipped
---
√
---
√
√
√
---
√
√
√
---
8
Operating Range
INSTALL INDOOR UNIT
Ensure that the system operates within the application guidelines
shown in the following tables.
Plan the installation carefully before you begin.
1. Select indoor unit location. If possible, place the unit adja-
cent to an outside wall if fresh air is required, and ensure
that the location allows for complete air distribution.
NOTE: If unit is not installed adjacent to an outside
wall and fresh air is required, a power ventilation kit ac-
cessory is available.
Cooling operating range:
Maximum
Minimum
DB
_F (_C)
WB
_F (_C)
DB
_F (_C)
WB
_F (_C)
125
55
Outdoor Unit
Indoor Unit
---
---
(51.7)
(12.8)
2. Remove the indoor unit from the carton and place it upside
down and perform the following steps:
95
(35)
71
(21.7)
67
(19.4)
57
(13.9)
a. Remove side panels by sliding forward, then away from
sides of the unit . See Fig. 9.
Heating operating range:
Maximum
Minimum
DB
_F (_C)
WB
_F (_C)
DB
_F (_C)
WB
_F (_C)
75
67
--- 20
Outdoor Unit
---
---
(23.9)
(19.4)
(---28.9)
80
(26.7)
71
(21.7)
55
(12.8)
Indoor Unit
Accessories
An extensive list of field installed accessories is available for both
indoor and outdoor units. Identify what accessories, if any, are
required for the application at hand and consult the separate
installation instructions for the accessories.
Some of the
accessories, especially on the indoor units, can be installed much
easier if planned ahead.
A09525
Fig. 9 -- Removal of Mounting Brackets from Indoor Unit
INSTALLATION
Complete Pre--installation Checks
b. Remove air filters from inlet grilles; then remove and
retain screws securing inlet grilles to indoor unit.
c. Remove inlet grilles from indoor unit by sliding for-
ward.
1. Unpack Unit -- Store the indoor and outdoor units in the
original packaging until it is moved to the final site for in-
stallation.
2. Inspect Shipment -- Upon receipt of shipment, check the
indoor and outdoor units for damage. If there is any dam-
age, forward claim papers directly to the transportation
company. Manufacturer is not responsible for damage in-
curred in transit.
3. Inspect Parts Supplied With Units – Check all items
against parts list (see page 7). If any items are missing, noti-
fy your distributor or Carrier office. To prevent loss or
damage, leave all parts in original packages until installa-
tion.
d. If a size 024 indoor unit is to be matched with a size
018 outdoor unit, switch the Molex plug on the motor.
The Molex plugs are labeled as 018 or 024.
e. Loosen hex bolts on the side of the unit and remove the
mounting brackets by sliding them out in direction
shown in Fig. 10. Allow approximately 3/8 inch space
between the bolt head and the unit as shown in Fig. 10.
Consider System Requirements
1. Consult local building codes and NEC for special installa-
tion requirements.
2. When deciding the location of the indoor and outdoor units,
ensure that the piping run does not exceed the allowed dis-
tances listed in Table 3.
3. Make sure the indoor and outdoor units are easily accessible
to electrical power.
4. Allow sufficient clearances for airflow, wiring, refrigerant
piping, and servicing the unit. See Fig.1 through Fig. 5.
A09527
Fig. 10 -- Installing Hex--Head Mounting Bolts
in Fan Coil Unit
5. Condensate piping can be directed through the inside wall
to an approved drain or straight outside.
f. If piping is going to be run from the right hand side,
open knock--out by removing the pre--split portion in
the rear of the right hand side panel with a saw or cutter
knife.
9
3. Mount Unit -- the installation location should have already
been identified taking into account the piping length, wiring
and piping,connections, and clearances.
a. Use mounting template, included inside box, to locate
mounting bolt holes, piping holes, electrical connec-
tions, and accessory outdoor intake, if used. See Fig. 11
and Fig. 12.
DIMENSIONS in. (cm)
Unit Size
024
B
46
C
49---5/8
(126.0)
57---1/2
(146.1)
(116.8)
53---7/8
(136.8)
036
DIMENSIONS in. (cm)
Unit Size
66---5/8
(169.2)
87
70---1/4
(178.4)
90---5/8
(230.2)
048
A
B
C
50---15/16
46
49---5/8
(126.0)
57---1/2
(146.1)
70---1/4
(178.4)
90---5/8
(230.2)
060
024
036
048
060
(221)
(129.4)
(116.8)
53---7/8
(136.8)
58---13/16
(149.4)
* --- Concealed mounting holes
{ --- E xposed mou n tin g h ol es.
71---9/16
(181.8)
92
66---5/8
(169.2)
87
A09046
Fig. 12 -- Mounting Included with Fan Coil Unit
(233.7)
(221)
A09528
NOTE: If fresh air is required, a minimum of 3 inch (76.2 mm)
Fig. 11 -- Fan Coil Unit Hanging Dimensions
clearance is required in back of unit.
b. Mount hanging brackets on ceiling (see Fig. 13) for
either concealed or exposed bolt hanging position.
A09530
Fig. 13 -- Mounting Hanging Brackets
10
When mounting brackets, select the proper type of hardware from
the guidelines below. See Fig. 14
Mounting on Ground
1. Mount unit on a solid level concrete pad.
2. If a heat pump is being installed, use a field-- provided snow
stand or ice rack where prolonged subfreezing temperatures
or heavy snow occurs.
3. Position unit so water or ice from roof does not fall directly
onto unit.
!
CAUTION
EQUIPMENT
PERSONAL
DAMAGE HAZARD
INJURY
AND/OR
Failure to follow this caution may result in personal injury
and / or equipment damage.
Solid structure in ceiling MUST be used due to weight of the
unit.
4. On cooling only units, an accessory stacking kit can be used
when units are to be stacked. See installation instructions
provided with the accessory kit.
Mounting on Roof
Wooden Structure:
Install hanging bolts on a square wooden piece placed over beams.
Newly Built Concrete Slab:
Install hanging bolts with inserts, embedded bolts, etc.
Metal Structure:
!
CAUTION
PERSONAL
DAMAGE HAZARD
INJURY
AND/OR
EQUIPMENT
Install hanging bolts utilizing an existing angle or by installing a
new support angle.
Previously Built Concrete Slab:
Failure to follow this caution may result in personal injury
and / or equipment damage.
Be sure unit panels are securely in place prior to rigging.
Install hanging bolts with expansion anchor.
1. Rig the unit. Keep the unit upright and lift using a sling.
Use cardboard or padding under the sling, and spreader bars
to prevent sling damage to the unit. See Fig 15. See Fig. 2
through Fig. 5 for center of gravity reference
2. Mount unit on a solid concrete pad or platform.
3. Isolate unit and piping from structure
4. If a heat pump is being installed, use a field-- provided snow
stand or ice rack where prolonged subfreezing temperatures
or heavy snow occurs.
5. On cooling only units, an accessory stacking kit can be used
when units are to be stacked. See installation instructions
provided with accessory kit.
A09526
Fig. 14 -- Fan Coil Unit Mounting Methods
(hardware is field--supplied)
c. Drill holes for routing refrigerant lines, condensate line
and electrical and control connections.
d. Lift the unit into place, and fit the hex--head bolts on
sides of indoor unit into mounting slots of mounting
brackets. Ensure unit is mounted with a slight tilt to the
rear side for proper drainage.
e. Tighten indoor unit hex--head bolts securely.
INSTALL OUTDOOR UNIT
The outdoor units can be installed on the ground, on the roof, or
mounted on a wall.
A07396
Fig. 15 -- Lifting Unit with Sling
NOTE: Install the unit so that the coil does not face into
prevailing winds. If this is not possible and constant wind winds
above 25 mph are expected, use accessory wind baffle. See
installation instructions provided with accessory kit. Wind baffles
should also be used on all units with accessory low ambient
temperature control.
Mounting Unit on Wall
The units can also be mounted on the wall using the accessory
mounting kit.
11
Complete Outdoor Refrigerant Piping Connec-
tions
Follow the following general guidelines:
1. Use refrigerant grade field – supplied tubing.
Refer to Table 4 for the correct line sizes.
2. Do not use less than 10 ft (93.05 m) of interconnecting
tubing.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
NOTE: Teflon Seal must face toward the outdoor heat pump unit.
A09538
If any section of pipe is buried, there must be a 6 in. (152.4
mm) vertical rise to the valve connections on the outdoor
unit. If more than the recommended length is buried,
refrigerant may migrate to cooler, buried section during
extended periods of system shutdown. This causes
refrigerant slugging and could possibly damage the
compressor at start--up.
Fig. 16 -- AccuRater Metering Device at Service
Valve (Bypass Type Components),
Heat Pump Systems Only
NOTE: The Teflon seal on the piston should point towards the
liquid service valve.
The size of the factory supplied piston might have to
adjusted for long line applications (over 80 ft / 24.4 m).
Refer to the Duct Free Long Line Application Guide
for additional information.
When more than 80 ft (24.4 m) of interconnecting tubing is used,
consult the Duct--Free Split System Long Line Application Guide
for required accessories.
3. On cooling only units, insulate the liquid line. On heat
pumps, insulate both lines. A minimum of 1/2 inch foam
pipe insulation is recommended.
4. Run the refrigerant tubes as directly as possible and avoid
unnecessary turns and bends.
3. On 38HDR units, remove the plastic caps on the liquid and
suction service valves. Braze the completed filter drier as-
sembly (from Step 1) to the liquid service valve. On the
38QRR unit, connect the completed filter drier assembly
(from Step 1) to the piston cap.
5. Suspend refrigerant tubes to avoid damage to insulation or
tubes so they do not transmit vibration to the structure.
4. Braze the field supplied line set to the filter drier assembly
and to the suction valve.
6. When passing refrigerant tubes through the wall, seal the
opening so rain and insects do not enter the structure. Leave
some slack in refrigerant tubes between structure and out-
door unit to absorb vibration.
5. Insulate any exposed areas between the filter drier and the
liquid valve.
Complete Outdoor Power and Control Wiring
NOTE: A fusible plug is located in unit suction line; do not cap
this plug. If local codes require additional safety devices, install as
directed.
!
WARNING
ELECTRICAL SHOCK HAZARD
Connection at Outdoor Unit
Failure to follow this warning could result in personal injury or
death.
!
CAUTION
The unit cabinet must have an uninterrupted or unbroken
ground to minimize personal injury if an electrical fault should
occur. The ground may consist of electrical wire or metal
conduit when installed in accordance with existing electrical
codes.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage
or improper operation.
To prevent damage to unit or service valves observe the
following:
S A brazing shield MUST be used.
S Wrap service valves with wet cloth or use a heat sink
material.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage
or improper operation.
1. Braze the connector tubes (field supplied for the 38HDR
units and factory supplied for the 38QRR units) to the inlet
of the factory supplied filter drier. If a cooling only unit is
being installed move to step 3 (see Fig. 8).
2. Remove the plastic cap from the liquid and suction service
valve on the 38QRR unit and assemble the heating piston
and piston cap supplied with the outdoor unit as shown in
Fig. 16.
Unit failure as a result of operation on improper line voltage or
excessive phase imbalance constitutes abuse and may cause
damage to electrical components. Such operation could void
any applicable Carrier warranty.
12
GROUND LEAD
GROUNDING LUG
BLK
!
WARNING
SINGLE-PHASE
CONN TO
DISCONNECT
PER NEC
ELECTRICAL SHOCK HAZARD
BLK
Failure to follow this warning could result in personal injury or
death.
SINGLE-PHASE UNIT
Before performing service or maintenance, be sure indoor unit
main power switch is turned OFF and indoor blower has
stopped.
BLK
BLU
Lock out and tag switch with suitable warning label.
THREE-PHASE
CONN TO
DISCONNECT
PER NEC
Power Wiring
YEL
1. Mount outdoor power disconnect. The unit is factory wired
for the voltage shown on the unit nameplate. The fused dis-
connect switch must be provided within sight of the unit,
readily accessible, but out of reach of children. Provisions
for locking the disconnect switch on the OFF (open) posi-
tion is advisable. The disconnect switch must comply with
NEC and local codes. Protect the unit and wiring using only
the recommended fuse/circuit breaker size. See Table 10..
GROUNDING LUG
THREE-PHASE UNIT
GROUND LEAD
LEGEND
NEC -- National Electrical Code
-- Splice (field)
Field Wiring
Factory Wiring
A08251
2. Run power wiring from main box to disconnect per NEC
and local codes.
Fig. 17 -- Line Power Connections
3. Run power wiring from the disconnect switch to outdoor
unit. Use only minimum 60_C copper conductors between
the disconnect switch and the unit for field power connec-
tion.
NOTE: Operating unit on improper line voltage constitutes
abuse and could affect Carrier warranty. DO NOT install unit
in a system where voltage may fluctuate above or below
permissible limits.
4. Route the field power wires through the conduit connection
opening in the unit side panel and connect in junction box
as shown in Fig 17. The unit and power wiring must be
grounded.
Control Wiring
The control circuit is 24 volts AC (minimum 40VA) supplied from
the indoor unit.
1. Make sure you have enough control wires to cover the dis-
tance between the indoor and outdoor unit.
2. Route one end of the control wiring through the opening
provided in the unit side panel and connect to the control
terminal strip using either Fig. 18 for 38HDR units and Fig.
19 for 38QRR units.
Y1
A09603
A09509
Fig. 18 -- 38HDR Typical Control Circuit Connections
Fig. 19 -- 38QRR Typical Control Circuit Connections
NOTE: Use No. 18 AWG color--coded, insulated (35_C minimum) wire. If the distance between the indoor and outdoor unit is greater than
100 ft. (30.5 m), as measured along the control voltage wires, use No. 16 AWG color--coded wire to avoid excessive voltage drop.
13
ELECTRICAL DATA
Table 10 – 38HDR Electrical Data
VOLTAGE RANGE*
COMPRESSOR
OUTDOOR FAN MOTOR
38HDR
MIN CKT
AMPS
FUSE/HACR
BKR AMPS
V --- P H --- H z
UNIT SIZE
Min
187
187
187
187
187
414
187
187
414
187
187
414
Max
253
253
253
253
253
506
253
253
506
253
253
506
RLA
9.0
LRA
48.0
58.3
73.0
77.0
71.0
38.0
109.0
83.1
41.0
134.0
110.0
52.0
FLA
0.8
0.8
1.5
1.5
1.5
0.8
1.5
1.5
0.8
1.5
1.5
0.8
NEC Hp
0.125
0.125
0.25
kW Out
0.09
0.09
0.19
0.19
0.19
0.19
0.19
0.19
0.19
0.19
0.19
0.19
018
024
030
208/230---1---60
208/230---1---60
208/230---1---60
208/230---1---60
208/230---3---60
460 --- 3 --- 60
12.1
17.7
19.1
19.1
13.0
7.9
20
25
30
30
20
15
40
25
15
60
30
15
13.5
14.1
14.1
9.2
0.25
0.25
036
048
060
5.6
0.25
208/230---1---60
208/230---3---60
460 --- 3 --- 60
19.9
13.1
6.1
0.25
26.4
17.9
8.9
0.25
0.25
208/230---1---60
208/230---3---60
460 --- 3 --- 60
26.4
15.0
7.8
0.25
34.5
21.5
10.6
0.25
0.25
Table 11 – 38QRR Electrical Data
VOLTAGE
RANGE*
COMPRESSOR
OUTDOOR FAN MOTOR
38QRR
MIN CKT
FUSE/HACR BKR
AMPS
V --- P H --- H z
UNIT SIZE
AMPS
RLA
LRA
FLA
NEC Hp
kw Out
Min
Max
253
253
253
253
253
506
253
253
506
253
253
506
018
024
030
208/230---1---60
208/230---1---60
208/230---1---60
208/230---1---60
208/230---3---60
460 --- 3 --- 60
187
187
187
187
187
414
187
187
414
187
187
414
9.0
14.4
12.8
15.5
10.1
5.6
48.0
58.3
64.0
77.0
71.0
38.0
117.0
83.1
41.0
134.0
110.0
52.0
0.8
0.8
1.5
1.5
1.5
0.8
1.5
1.5
0.8
1.5
1.5
0.8
0.125
0.125
0.25
0.25
0.25
0.25
0.25
0.25
0.25
0.25
0.25
0.25
0.09
0.09
0.19
0.19
0.19
0.19
0.19
0.19
0.19
0.19
0.19
0.19
12.1
18.8
17.5
20.9
14.1
7.9
20
30
30
30
20
15
50
30
15
60
40
15
036
048
060
208/230---1---60
208/230---3---60
460 --- 3 --- 60
26.5
16.7
7.3
34.6
22.4
10.0
34.5
23.6
10.6
208/230---1---60
208/230---3---60
460 --- 3 --- 60
26.4
17.7
7.8
Table 12 – 40QAC/QAQ Electrical Data
VOLTAGE
RANGE*
MINIMUM
WIRE SIZE
(AWG)
HEATER
POWER
VOLTAGE
FAN
FLA
UNIT
V --- P h --- 6 0 H z
MIN.
MAX.
253
253
253
253
253
253
253
253
kW
—
—
—
—
FLA
—
MCA
0.63
MOCP
15.0
15.0
15.0
15.0
15.0
20.0
25.0
30.0
FLA
40QAC024---3
40QAC036---3
40QAC048---3
40QAC060---3
40QAQ024---3
40QAQ036---3
40QAQ048---3
40QAQ060---3
208/230---1
208/230---1
208/230---1
208/230---1
208/230---1
208/230---1
208/230---1
208/230---1
187
187
187
187
187
187
187
187
0.50
1.30
0.50
1.30
14
14
14
14
14
14
12
10
—
1.60
1.60{
2.60}
0.50
—
2.00
1.60
—
3.30
2.60
2.00
3.00
4.00
5.00
8.66
13.00
17.40
21.70
9.29
11.29
14.30
19.00
24.30
1.30
17.70
23.80
28.70
1.60{
2.60{
LEGEND
NOTES
FLA --- Fu l l L oad Amps
*
Permissible limits of the voltage range at which the unit will operate
satisfactorily
LRA --- L ocked Rotor Amps
MCA --- Minimum Circuit Amps
RLA --- Rated Load Amps
{
}
One fan is 1.1 amps, the second fan is 0.5 amps.
Two fans each operating at 1.3 amps.
14
A09597
Fig. 20 -- 38HDR and 40QAC Cooling System Wiring Diagram
15
A09598
Fig. 21 -- 38QRR and 40QAQ Heat Pump System Wiring Diagram
16
Complete Indoor Piping
Connect Condensate Drain Line
The piping to the indoor unit can be routed from the back, side and
top. If the unit is being piped from the top or the side see note
below.
Observe all local sanitary codes when installing condensate drains.
Refer to Fig. 23 for drain pipe connection from indoor unit.
1. Use hard polyvinyl chloride (PVC) pipe material with nom-
inal ID of 3/4 in. to connect at drain line. Use pipe insula-
tion 1/4 in. thick, such as Armaflex insulation, on exposed
piping inside the conditioned space.
2. To insure regular flow of condensate water, the drain pipe
should be pitched toward an open drain or sump at a down-
ward slope of at least 1/4 in. per ft.
3. If the drain piping is routed through the side of the unit, at-
tach a field fabricated piece of sheet metal to support the
drain pipe as shown in Fig. 23.
1. On heat 40QAQ024 – 048, the cooling piston (indoor) is
shipped in the factory installed metering device with the in-
door unit. Use Table 6 to verify that you have the correct
piston size for the system being installed.
2. Run the line set and the control wiring from the outdoor to
the indoor unit through the hole in the wall. Keep the piping
general guidelines in mind.
3. Cut the liquid and suction line to the correct length using a
tube cutter.
4. Remove the flare nuts from the indoor piping connections.
Install them onto the liquid and suction lines and make flare
connections.
4. Attach drain pipe with nylon wire tie passing through hole
as shown in Fig. 23.
5. Apply a small amount of refrigerant oil to the flare connec-
tion and tubing.
6. Align the tubing with the refrigerant connections on the in-
door unit.
7. Tighten the flare nut and finish the installation using two
wrenches as shown in Fig. 22.
NOTE: When piping is being routed from the top or side, two
pipe adaptors are supplied with the unit. Flare the pipe
adaptors to the indoor unit connections and sweat the other
ends to the line set.
(Field Fabricated)
A09534
Fig. 23 -- Routing Drain Piping
A07354
Fig. 22 -- Tighten Flare Nut
NOTE: Do not fasten nylon wire ties tight enough to deform the
insulation, as this affects performance.
8. Insulate both connections on the 38QRR and the liquid line
connection on the 38HDR units.
5. Install an external trap at the end of the condensate line.
NOTE: Should the installation require one, a condensate pump
may be ordered as a fields--installed accessory. It is easier to install
pump before hanging the unit.
17
2. Route line power leads from inside disconnect to the fan
coil. Place wire through the whole on the control box.
3. Connect wire to high voltage terminal board (TB1) and
ground screw.
Complete Control Wiring
1. Run the control wiring close to the terminal block on the
indoor unit.
2. Connect the wires as shown in Fig 18 and Fig. 20 for
38HDR units, and Fig. 19 and Fig. 21 for 38QRR units.
NOTE: When routing the wire in the unit, use care to keep the
wire away from refrigerant and condensate piping and any
sharp edges.
Complete Power Connection To Indoor Unit
Be sure field wiring complies with local building codes and NEC,
and unit voltage is within limits shown in Table 12.
Contact local power company for correction of improper line
voltage.
NOTE: The 208/230--v units are factory wired for 230--v to
24--v transformer operation, For 208--v to 24--v operation,
interchange the blue (208--v) and red (230--v) wires. Cap any
unused wires with wire nuts.
Install Thermostat
These systems use a three speed thermostat. Refer to Table 9 for a
list of recommended thermostats.
!
WARNING
ELECTRICAL SHOCK HAZARD
1. Mount thermostat to a wall in the occupied space using
hardware provided with the thermostat. Locate the thermo-
stat, preferably on an interior wall, in an area that is not sub-
jected to drafts or direct sunlight through windows.
2. Run the thermostat wires to the control box of the indoor
unit. If running the thermostat through the back of the unit,
3/8 in. space between the unit and the wall is required.
Failure to follow this warning could result in personal injury
or death.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF position.
There may be more than 1 disconnect switch. Lock out and
tag switch with a suitable warning label.
3. Route wires over refrigerant and drain piping as shown in
Fig. 24.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage
or improper operation.
Unit failure as a result of operation on improper line voltage or
excessive phase imbalance constitutes abuse and may cause
damage to electrical components. Such operation could void
any applicable Carrier warranty.
NOTE: Use copper wire only between disconnect switch(es) and
unit.
NOTE: Install branch circuit disconnect of adequate size to handle
unit starting current per NEC. Locate disconnect within sight of,
and readily accessible from, unit, per section 440--14 of NEC.
Some codes allow indoor unit to share disconnect with outdoor
unit if disconnect can be locked; check local code before installing
in this manner.
*Field-supplied.
A09533
Fig. 24 -- Routing Wires Over Piping
NOTE: Do not route wires under the piping, or wires could
impede air filter removal.
1. Route ground and power wires.
4. Connect the thermostat wires to the indoor unit per Fig 25
for a 40QAC unit and Fig. 26 for a 40QAQ unit.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
According to NEC and most local codes, the unit must have
an uninterrupted, unbroken ground to minimize personal
injury if an electric fault should occur. The ground may
consist of electrical wire or metal conduit when installed in
accordance with existing electrical codes.
18
HP ONLY
COOLING ONLY
Heating Only
A09545
Fig. 25 -- Thermostat Wire Connection for 40QAC
Fig. 26 -- Thermostat Wire Connection for 40QAQ
Reassemble Indoor Unit
1. Reinstall filters and inlet grilles
2. Reinstall the side panels
Evacuate and Dehydrate the System
!
CAUTION
UNIT DAMAGE HAZARD
START--UP
Preliminary Checks
Failure to follow this caution may result in equipment damage
or improper operation.
1. Check condensate drainage system; on the opposite side of
the drain connection, insert a water bottle up into the fan
coil unit and fill the drain pan (see Fig. 27). Water must
flow steadily; if not, check the pipe slope or inspect for any
pipe restrictions.
Never use the system compressor as a vacuum pump.
Using Vacuum Pump
1. Completely tighten flare nuts A, B, C, D, connect manifold
gage charge hose to a charge port of the low side service
valve. (See Fig. 28.)
2. Connect charge hose to vacuum pump.
3. Fully open the low side of manifold gage. (See Fig. 29.)
4. Start vacuum pump
5. Evacuate using either deep vacuum or triple evacuation
method.
6. After evacuation is complete, fully close the low side of
manifold gage and stop operation of vacuum pump.
7. The factory charge contained in the outdoor unit is good for
up to 25 ft. (8 m) of line length. For refrigerant lines longer
than 25 ft (8 m), add 0.3 oz. per foot of extra piping up to
the maximum allowable length.
8. Disconnect charge hose from charge connection of the low
side service valve.
A09538
Fig. 27 -- Inserting Water Into Drain Pan
9. Fully open service valves B and A.
2. Make sure all wiring connections are correct and they are
tight.
10. Securely tighten caps of service valves.
3. Field electrical power source must agree with unit name
plate rating.
Indoor Unit
C
Refrigerant
Low Side
Outdoor Unit
A
B
4. Check that all barriers, covers, and panels are in place. En-
sure that the filters and return--air grilles on the indoor unit
have been installed and that the discharge louvers are posi-
tioned correctly.
D
High Side
Service Valve
Fig. 28 -- Service Valve
5. All service valves must be closed.
A07360
6. On units with crankcase heaters, ensure belly--band heaters
are tight around the compressor.
19
Triple Evacuation Method
Manifold Gage
The triple evacuation method should only be used when vacuum
pump is only capable of pumping down to 28 in. of mercury
vacuum and system does not contain any liquid water.
Refer to Fig. 31 and proceed as follows:
500 microns
1. Pump system down to 28 in. of mercury and allow pump to
continue operating for an additional 15 minutes.
Low side valve
High side valve
Charge hose
Charge hose
2. Close service valves and shut off vacuum pump.
3. Connect a nitrogen cylinder and regulator to system and
open until system pressure is 2 psig.
Vacuum pump
4. Close service valve and allow system to stand for 1 hr. Dur-
ing this time, dry nitrogen will be able to diffuse throughout
the system absorbing moisture.
5. Repeat this procedure as indicated in Fig. 31. System will
then be free of any contaminants and water vapor.
Low side valve
Fig. 29 -- Manifold
A07361
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable of
pulling a vacuum of 500 microns and a vacuum gage capable of
accurately measuring this vacuum depth. The deep vacuum method
is the most positive way of assuring a system is free of air and
liquid water. (See Fig. 30)
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
5000
4500
4000
EVACUATE
CHECK FOR TIGHT, DRY SYSTEM
(IF IT HOLDS DEEP VACUUM)
LEAK IN
3500
SYSTEM
3000
2500
2000
1500
1000
RELEASE CHARGE INTO SYSTEM
A95425
VACUUM TIGHT
Fig. 31 -- Triple Evacuation Method
TOO WET
TIGHT
To Start the Unit:
500
DRY SYSTEM
1. If the outdoor unit is equipped with a crankcase heater, turn
on the indoor and outdoor disconnect switches to supply
power the system 12 hours before starting the system.
2. Release charge into the system by opening (back--seating)
liquid and suction line service valves.
0
1
2
3
4
5
6
7
MINUTES
A95424
Fig. 30 -- Deep Vacuum Graph
3. Set the wireless remote control or wired remote control be-
low ambient temperature. Operate the unit for 15 minutes.
4. Refer to Table 5 to determine if additional charge is re-
quired. Also, if you have a long line application, refer to the
Duct Free Long Line Application Guide to determine the
additional charge that is required beyond 25 ft (7.6 m).
5. Calculate the total additional charge required and weigh in.
6. Charge should be added as liquid (not gas) slowly and care-
fully to low side to avoid liquid slugging.
20
SAFETIES — The system is equipped with the following safety
devices to protect system components: Indoor coil freeze
protection thermostat — If a coil temperature of 28_F (--2.22_C) or
lower is sensed, the compressor and outdoor fan will be shut down
until the coil temperature exceeds 28_F (--2.22_C). The indoor fan
will continue to run. Condensate float switch (units equipped with
accessory condensate pump, cooling cycle only) — If the level of
condensate in the drain pan rises too high, the condensate float
switch will turn the system off.
OPERATING SEQUENCE
Ceiling--suspended fan coil units have a relay board which controls
system operation in response to a room thermostat. The user may
manually select any one of 3 fan speeds for unit operation. The
discharge louvers on the unit can be stationary or swing
continuously. A switch located at the bottom of the unit will turn
the swing function on and off.
Ceiling--suspended systems may be equipped with an accessory
power ventilation kit and/or condensate pump.
CLEANING AND MAINTENANCE
FAN OPERATION
—
Fan coils are capable of 3--speed
operation. See thermostat instructions for fan speed selection.
When the fan(s) is operating in medium or high speed and the unit
is equipped with the power ventilation kit, the ventilation fan will
operate to provide fresh air.
!
WARNING
ELECTRICAL SHOCK HAZARD
COOLING MODE OPERATION — When the room thermostat
senses a demand for cooling, the fan coil relay board is energized.
The indoor fan(s) will start in the selected speed (if it is not already
operating). The reversing valve (heat pump only) will energize for
cooling operation.
Failure to follow this warning could result in personal
injury or death.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF
position. There may be more than 1 disconnect switch.
Lock out and tag switch with a suitable warning label.
The internal condensate pump (if so equipped) runs whenever the
reversing valve is energized (heat pump only) and/or the unit is in
cooling. As long as the condensate float switch and freeze
protection thermostat are closed, the cooling relays in the fan coil
unit will close. This energizes the compressor and outdoor fan in
the outdoor unit.
!
CAUTION
UNIT DAMAGE HAZARD
The compressor will continue to operate until the room thermostat
is satisfied. When the cooling demand is satisfied, the compressor
and outdoor fan will stop. If the system is in the AUTO. position,
the indoor fan will stop with the compressor.
If the unit has the accessory ventilation kit, the ventilation fan will
operate whenever the indoor fan is set for medium or high speed.
Failure to follow this caution may result in equipment
damage or improper operation.
To avoid shrinkage, do not wash filter in water over
120_F (48.9_C). To avoid damage, do not expose filter to
fire or direct sunlight . Clean the filter more frequently
when air is extremely dirty.
HEAT PUMP OPERATION — When the room thermostat
senses a demand for heating the indoor fan will start in the selected
speed (if not already operating), and the reversing valve will not be
energized.
For proper system operation, perform the cleaning and
maintenance operations in Table 13.
Lubrication — The indoor--fan, automatic air sweep, and the
outdoor--fan motors are factory lubricated and require no oiling.
The internal condensate pump (if supplied) and freeze protection
thermostat are not operated during heating operation. The control
relay (CR2) closes, and the compressor and outdoor fan are
energized through the defrost board (DFB), which is located in the
outdoor unit. The microprocessor logic in the DFB is energized
when the compressor starts, and the defrost timer runs. Once every
90 minutes (factory default setting) of compressor run time, the
DFB logic checks the defrost thermostat (DFT). If the DFT is
open, the unit continues in heating operation. If the DFT is closed,
the DFB switches the unit to defrost mode. The timing on the DFB
may be set at either 30, 50, or 90 minutes.
DEFROST (Heat Pump Only) — The DFB energizes the RVS
(reversing valve solenoid), and the reversing valve switches to the
cooling position. The K1 relay on the DFB opens and the outdoor
fan stops. The W2 contact on the DFB is also energized, which in
turn energizes the defrost relay on the fan coil relay board, turns off
the electric heater and stops the indoor fan.
AIR FILTERS
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Operating the system with dirty air filters may damage the
indoor unit and can cause reduced cooling performance,
intermittent system operation, frost build--up on the indoor
coil, and blown fuses. Inspect and clean or replace the air
filters monthly.
REMOVE AIR FILTERS — Remove filters by pulling them
straight out.
The DFB logic checks the 10--minute defrost timer and the DFT. If
the DFT opens in less than 10 minutes, the DFB switches the unit
back to normal heating operation. If the DFT remains closed, the
DFB switches the unit back to heating operation after 10 minutes.
When the DFB changes back to heating mode, the RVR (reversing
valve relay) is de--energized and the reversing valve switches back
to heating operation. Both the outdoor and indoor fans come back
on, and if necessary, the electric heater also turns on. SYSTEM
CLEAN OR REPLACE FILTERS — Filters can be vacuumed
or washed in warm water. Shake filter to remove any excess water,
and replace by sliding filter behind grille until filter snaps in place.
Refer to Fig. 32. If the filter has begun to break down or is torn,
replace it. Replacement filters are available through your dealer.
21
Table 13 – Cleaning and Maintenance Schedule
TASK
MONTHLY
QUARTERLY
YEARLY
INDOOR UNIT
Clean Air Filters
Clean Drain Pipe
X
X
Clean Condensate Drain Pan
Clean Indoor Coil
X
X
Clean Indoor Unit Front Panel
OUTDOOR UNIT
X
X
Clean the Fins From Outside
Open the Unit and Clean Fins Inside
Remove Dust From Electrical Parts
Check Electrical Connections are Tight
Clean Outdoor Fan
X
X
X
X
X
X
Clean Outdoor Coil
Check that Outdoor Fan Assembly is Tight
Clean Drain Pan
X
NOTE: Maintenance procedures for the outdoor units are in the individual unit installation instructions.
CLEAN INDOOR UNIT BOTTOM PANEL — If the bottom
panel of the unit becomes dirty or smudged, wipe the outside of the
panel with a soft dry cloth. Use a mild liquid detergent and wipe
SERVICE
!
WARNING
off carefully with a dry cloth.
CLEAN INDOOR COIL — To clean the coil, remove indoor
unit bottom panel and vacuum the coil fins, using care not to bend
or damage fins.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
CLEAN OUTDOOR COIL (Outdoor Unit)
Before servicing system, main electrical disconnect switch
must be in the OFF position. There may be more than 1
disconnect switch. Lock out and tag switch with a suitable
warning label.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
!
CAUTION
Sheet metal parts may have sharp edges or burrs. Use care and
wear appropriate protective clothing and gloves when
cleaning. Clean coil carefully.
ENVIRONMENTAL HAZARD
Failure to follow this caution may result in environmental
damage.
Federal regulations require that you do not vent refrigerant to
the atmosphere. Recover during system repair or final unit
disposal.
To clean the outdoor coil:
1. Remove any dirt or obstruction from discharge opening.
2. Use a garden hose to spray water on the coil. Debris that
collects between coil fins inhibits heat transfer — direct the
water spray between coil fins to flush out debris.
CLEAN CONDENSATE DRAINS — Clean all drains and drain
pans at the start of each cooling season. Check the flow by pouring
water into the drain.
To clean or replace drain pan:
1. Place a plastic sheet on the floor to catch any water that may
spill from drain pan.
2. Remove the intake grille and distribution assembly (at-
tached).
3. Remove the condensate water in the drain pan by letting
water drain into a 3--gallon bucket.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage.
A09539
Fig. 32 -- Cleaning Filters
Do not use a screwdriver to pry drain pan out of assembly
-- it could damage the pan.
4. Remove the 4 screws holding the drain pan.
5. Carefully hold the drain pan to remove it from the assembly.
22
IF SYSTEM FAILS TO OPERATE — Be sure:
Before Calling for Service
S
S
unit ON/OFF switch is in ON position
fuse or circuit breaker is not tripped
Save the cost of a service call by doing the following:
1. Be sure main power to system is turned on.
2. Press Mode button until OFF is displayed. Wait 5 minutes.
FRESH AIR INSTALLATION OPTION
3. Press Mode button until either COOL or HEAT is displayed
(as desired).
The units have an installation option, which allows for field
installation of fresh air ventilation. Plan the installation carefully.
Before beginning, measure carefully and follow acceptable
building practices, NEC, and local codes.
Ventilation--Air Accessory — Refer to ventilation air accessory
installation instructions.
4. Adjust thermostat set point to desired room temperature. If
system starts within a few minutes, service may not be ne-
cessary. If system does not operate properly, check Table 14
for typical solutions.
TROUBLESHOOTING
If the under--ceiling fan coil unit fails to start or operate properly, sometimes the problem is minor and can be handled without a service call.
Refer to Table 14 for some common problems, causes, and typical solutions. See Fig. 36 and 37 for additional system troubleshooting details.
If the problem cannot be corrected, contact a local dealer for further assistance.
Table 14 – Troubleshooting
PROBLEM
CAUSE
TYPICAL SOLUTION
Blown fuse or circuit breaker tripped at building power
entry.
Replace fuse or reset circuit breaker.*
Indoor and/or outdoor unit disconnect switch is off.
Thermostat is set to night mode.
Power failure.
Turn on disconnect switch(es).
Cancel mode using Day/Night button on thermostat.
Restore power.
System Does Not Start.
Press Mode button on thermostat until thermostat dis-
plays the desired unit mode.
Unit is in off mode.
Three---minute time delay is running.
Wait for 3 minutes.
Temperature is above or below the selected temperat-
ure.
Select new temperature using the thermostat.
Clean or replace air filter(s).
Air filter(s) in indoor unit is dirty or needs to be replaced.
Temperature is set too high or too low.
Outdoor unit outdoor coil restricted.
Fan speed is set too low.
Reset temperature to desired comfort setting using the
thermostat.
System Does Not Cool Properly.
System Does not Heat Properly.
Remove obstruction.
Adjust fan speed to high or auto. using the Fan button
on the thermostat.
Air filter(s) in indoor unit is dirty or needs to be replaced.
Temperature is set too high or too low.
Outdoor unit outdoor coil restricted.
Fan speed is set too low.
Clean or replace air filter(s).
Reset temperature to desired comfort setting using the
thermostat.
Remove obstruction.
Adjust fan speed to high or auto. using the Fan button
on the thermostat.
Check manual defrost timer setting and adjust as ne-
cessary.
Outdoor unit outdoor coil is frosted up.
Low outdoor---air temperature.
Run system in fan---only mode until frost is gone.
Clean or replace air filter(s).
Ice or frost has Formed on Indoor
Coil.{
Air filter(s) in indoor unit is dirty or needs to be replaced.
Air filter(s) in indoor unit is dirty or needs to be replaced.
Fan coil unit coil is blocked.
Clean or replace air filter(s).
Insufficient Airflow.
Clean air discharge louvers.
*
†
If fuse blows or circuit breaker trips again after first start attempt, DO NOT attempt to start system again. Contact your local dealer for assistance.
When outdoor temperature is approximately 55_F (12.8_C) or below, indoor coil frosting may occur when system is operated in cooling or maximum
dehumidification mode. Units are not intended to operate below 55_F (12.8_C) without appropriate accessories.
23
LEGEND
NC
— Normally Closed
ODT — Outdoor Thermostat
NOTE: For systems with indoor units equipped with microprocessor
control, see separate controls, service, and troubleshooting manual.
A07435
Fig. 33 -- Troubleshooting the Heating Cycle
24
LEGEND
NC
— Normally Closed
ODT — Outdoor Thermostat
NOTE: For systems with indoor units equipped with microprocessor
control, see separate controls, service, and troubleshooting manual.
A07436
Fig. 34 -- Troubleshooting the Cooling Cycle
25
C a t a l o g N o : 4 0 Q A C --- Q --- 2 S I
Copyright 2009 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231
Printed in U.S.A.
Edition Date: 10/09
R e p l a ce s: 4 0 QA C --- Q --- 1 SI
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.