50XP
Performancet 13 SEER
Single---Packaged Air Conditioner System with PuronR
(R---410A) Refrigerant Single and Three Phase
2 to 5 Nominal Tons (Sizes 024---060)
Product Data
Easy Installation
Factory--assembled package is a fully self--contained, electric
cooling unit that is prewired, pre--piped, and pre--charged for
minimum installation expense. These units are available in a
variety of standard cooling sizes with voltage options to meet
residential and light commercial requirements. Units are
lightweight and install easily on a rooftop or at ground level. The
high tech composite base eliminates rust problems associated with
ground level applications.
Durable, dependable components
Scroll Compressors are designed for high efficiency. Each
compressor is hermetically sealed against contamination to help
promote longer life and dependable operation. Each compressor
also has vibration isolation to provide quieter operation. All
compressors have internal high pressure and overcurrent
protection.
Convertible duct configuration
Unit is designed for easy use in either downflow or horizontal
applications. Each unit is easily converted from horizontal to
downflow. Downflow operation is easily provided in the field to
allow vertical ductwork connections. The basepan utilizes
knockout style seals on the bottom openings to ensure a positive
seal in the horizontal airflow mode.
C99064
Fig. 1 -- Unit 50XP
Direct--drive variable speed blower motor is standard on all
models.
Single--Packaged Products with Energy--Saving Features and
PuronR refrigerant.
S Up to 13.5 SEER
S Factory--Installed TXV
S Variable Speed Blower--Standard
S Low Sound Levels
Direct--drive PSC condenser--fan motors are designed to help
reduce energy consumption and provide for cooing operation
down to 55_F (13_C) outdoor temperature. Motormasterr II low
ambient kit is available as a field--installed accessory.
Thermostat controls
Time Guardr
II anti--short cycle protection circuitry. If a
non--corporate thermostat without anti--short cycle protection is
used the Time Guard II field--installed anti--short cycle kit is
recommended.
Refrigerant system is designed to provide dependability. Liquid
filter driers are used to promote clean, unrestricted operation. Each
unit leaves the factory with a full refrigerant charge. Refrigerant
service connections make checking operating pressures easier.
FEATURES/BENEFITS
One--piece cooling unit
with optional electric heater, low
installation cost, dependable performance and easy maintenance.
Efficient operation
High--efficiency design with a SEER (Seasonal Energy Efficiency
Ratio) of up to 13.5.
Puron Environmentally Sound Refrigerant is Carrier’s unique
refrigerant designed to help protect the environment. Puron is an
HFC refrigerant which does not contain chlorine that can harm the
ozone layer. Puron refrigerant is in service in millions of systems
proving highly reliable, environmentally sound performance.
IdealHumidity Technology featuring Thermidistat control and
Variable Speed Blower motor that provides greater comfort,
humidity control, and energy efficiency. You can expect up to 30
times better dehumidification; economical constant fan for less
than $50 a year, which provides improved indoor air quality and
more even temperatures from room to room; and reduced indoor
noise due to lower air velocity. In addition, you’ll realize improved
installation flexibility with 3 different airflow choices for best
overall comfort.
Thermostatic Expansion Valve -- A hard shutoff, balance port
TXV maintains a constant superheat at the evaporator exit (cooling
cycle) resulting in higher overall system efficiency.
Evaporator and condenser coils are computer--designed for
optimum heat transfer and cooling efficiency. The evaporator coil
is fabricated from copper tube and aluminum fins and is located
inside the unit for protection again damage. The condenser coil is
internally mounted on the top tier of the unit. Copper fin coils and
pre--coated fin coils are available from the factory by special order.
these coils are recommended in applications where aluminum fins
are likely to be damaged due to corrosion. They are ideal for
seacoast applications.
High and Low Pressure Switches provide added reliability for the
compressor.
1
MODEL NUMBER NOMENCLATURE
---
50XP
024
--- --- ---
3
0
--- ---
1
Options
BT --- AL evap, vin y l con den ser
CC --- AL evap, CU con den ser
CU --- CU evap & condenser
Type of Unit
50XP --- Single Packaged
Air Conditioner
System
TP --- Base unit with tin plated indoor coil hairpins
TV --- TP with vinyl coating on outdoor coil
TC --- TP with AL indoor coil & CU/CU outdoor
coil
N/A
See Price Page for full list of factory options.
Only used if ordering an option
Nominal Cooling Capacity
024 --- 2.0 Tons
030 --- 2.5 Tons
036 --- 3.0 Tons
Packaging
042 --- 3.5 Tons
048 --- 4.0 Tons
060 --- 5.0 Tons
Series
Electrical Supply
N/A
3 --- 208/230---1---60
5 --- 208/230---3---60
LEGEND
AL --- Aluminum
CU --- Copper
ISO 9001:2000
REGISTERED
3
ARI* CAPACITIES
Cooling Capacities and Efficiencies
NET COOLING
CAPACITIES (Btuh)
24,000
UNIT 50XP
NOMINAL TONS
STANDARD CFM
EER**
SEER†
024
030
036
042
048
060
2
2--1/2
3
770
960
1100
1450
1450
1710
11.0
11.0
11.2
11.2
11.0
11.0
13.2
13.0
13.5
13.0
13.0
13.0
29,000
36,000
3--1/2
4
41,000
45,000
5
57,000
LEGEND
Notes:
d B --- Sound Levels (decibels)
db—Dry Bulb
1. Ratings are net values, reflecting the effects of circulating fan heat.
Ratings are based on:
SEER—Seasonal Energy Efficiency Ratio
wb—Wet Bulb
COP---Coefficient of Performance
* Air Conditioning & Refrigeration Institute.
**At “A” conditions---80_F (26.7_C) indoor db/67_F (19.4_C) indoor wb &
95_F (35_C) outdoor db.
{ Rated in accordance with U.S. Government DOE Department of Energy)
test procedures and/or ARI Standards 210/240.
Cooling Standard: 80°F (26.7_C) db, 67°F wb (19.4_C) in door en ter in g --- air
temperature and 95°F db (35_C) outdoor entering---air temperature.
2. Before purchasing this appliance, read important energy cost and effi-
ciency information available from your retailer.
A--Weighted Sound Power (dBA)
STANDARD
RATING
(dBA)
TYPICAL OCTAVE BAND SPECTRUM (dBA) (without tone adjustment)
50XP
125
250
500
1000
2000
4000
8000
024
030
036
042
048
060
72
72
72
72
78
78
58.8
58.8
60.7
56.7
62.4
63.5
63.5
63.5
63.3
62.8
69.9
67.6
67.2
67.2
66.8
67.8
71.3
71.8
66.9
66.9
66.5
67.4
73.4
75.5
63.7
63.7
64.2
63.7
70.0
71.0
58.3
58.3
60.3
57.7
66.3
68.1
50.0
50.0
53.0
50.8
60.1
59.9
*
Tested in accordance with ARI Standard 270 (not listed in ARI).
4
PHYSICAL DATA
Physical Data--Unit 50XP
UNIT SIZE
024
030
036
042
048
060
NOMINAL CAPACITY (ton)
2
2 --- 1/2
3
3 --- 1/2
4
5
SHIPPING WEIGHT (lb)
SHIPPING WEIGHT (kg)
356
161
360
163
378
171
436
198
470
213
515
234
Scroll
1
COMPRESSORS
Quantity
REFRIGERANT (R---410A)
Quantity (lb.)
Quantity (kg)
7.3
3.3
8.0
3.6
9.5
4.3
10.7
4.9
11.25
5.1
13.2
6.0
REFRIGERANT METERING DEVICE
TXV
OUTDOOR COIL
Rows...Fins/in.
Face Area (sq ft)
2...21
11.95
2...21
12.0
2...21
13.6
2...21
15.4
2...21
17.4
2...21
19.3
OUTDOOR FAN
Nominal Cfm
Diameter (in.)
Diameter (mm)
Motor Hp (Rpm)
2350
22
558.8
1/8 (825)
2700
22
558.8
1/8 (825)
2350
22
558.8
1/8 (825)
2800
22
558.8
1/8 (825)
3300
22
3300
22
558.8
558.8
1/4 (1100)
1/4 (1100)
INDOOR COIL
Rows...Fins/in.
Face Area (sq ft)
3...15
3.7
3...15
3.7
4...15
3.7
3...15
4.7
4...15
4.7
4...17
5.7
INDOOR BLOWER
Nominal Cooling Airflow (Cfm)
Size (in.)
1400
11x10
279.4x254
3/4 (1075)
1750
11x10
279.4x254
1.0 (1040)
800
1000
10x10
254x254
1/2 (1050)
1100
1400
10x10
11x10
11x10
Size (mm.)
254x254
1/2 (1050)
279.4x254
3/4 (1000)
279.4x254
3/4 (1075)
Motor HP (RPM)
HIGH---PRESSURE SWITCH
(psig) Cut---out Reset (Auto)
650 +/--- 15
420 +/--- 25
L O S S --- O F --- C H A R G E / L O W --- P R E S S U R E
SWITCH (Liquid Line) (psig) cut---out Re-
set (auto)
20 +/ --- 5
45 +/--- 10
RETURN---AIR FILTERS†}
Throwaway Size (in.)
Throwaway Size (mm)
20x20x1
508x508x25
20x24x1
508x610x25
24x30x1
610x762x25
{
Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity
of 300 ft/minute for throwaway type or 450 ft/minute for high---capacity type. Air filter pressure drop for non---standard filters must not exceed 0.08 IN. W.C..
} If using accessory filter rack refer to the filter rack installation instructions for correct filter sizes and quantity.
5
compartment. Heater sizes range from 5.0 to 20.0 kW. The electric
heater design allows the use of a single--point power supply for the
entire unit, resulting in lower installed costs.
OPTIONS AND ACCESSORIES
Factory--installed options
Coil options include Tin--Plated* indoor hairpins, copper/copper
and vinyl--coated construction for refrigerant coils. Units are
shipped standard with copper tube/aluminum fin construction. See
model number nomenclature for coil options.
*Tin--Plated indoor coils are built with special hairpins that are
designed to resist both general pitting corrosion and excessive
indoor corrosion(Formicary Corrosion).
Filter Rack features easy installation, serviceability, and
high--filtering performance for vertical or horizontal applications.
Flat roof curbs in both 8 in. (203.2 mm) and 14 in. (355.6 mm)
sizes are available for roof mounted applications.
Square--to--round duct transition kit enables 024--048 size units
to be fitted to 14 in. (355.6 mm) round ductwork.
Thermidistat Control coupled with the system’s variable speed
indoor blower delivers Carrier’s patented IdealHumidity
Technology that allows for even greater humidity control. Along
with more precisely controlling temperature and humidity, the
Thermidistat offers full seven--day programmability allowing you
to further customize your comfort and energy savings.
Field--installed accessories
Economizer with Solid -State Controls and Barometric
Relief Dampers
Manual Air Damper (25% open)
Electric Heaters
Filter Rack
Thermostats provide control for the system heating and cooling
functions. Thermostat models are available in both programmable
and non--programmable versions.
Flat Roof Curbs (8 -in. and 14 -in.) (203.2 and 355.6 mm)
Square -to -Round Duct Transition Kit
Thermidistatt
Crankcase Heater provides anti--floodback protection for
Thermostats
low--load cooling applications.
Crankcase Heater
Compressor Start Kit (for use on single--phase units only)
Rigging Kit
Low Ambient Kit (Motormaster® II Control)
Solid -State Time Guard® II Device
Lifting Kit
Compressor start kit assists compressor start--up by providing
additional starting torque on single phase units and prolongs
compressor motor life.
Rigging kit includes lifting brackets which are inserted into the
unit base rigging holds to lift unit for rooftop applications.
Low--ambient kit (Motormaster II control) allows the use of
mechanical cooling down to outdoor temperatures as low as 0_F
(--17_C) when properly installed.
Solid--state Time Guard II device provides short--cycling
protection for the compressor. Not required with corporate
electronic thermostats.
Economizer with solid--state controls and barometric relief
dampers includes filter racks and provide outdoor air during
cooling and reduce compressor operation.
Manual outside air damper includes hood and filter rack with
adjustable damper blade for up to 25% outdoor air.
Electric heaters provide additional heat in the unit when required.
Each package has a heater module that slides into the controls
Lifting kit, including 4 metal brackets that are available to assist in
lifting this product onto a roof application.
Electric Heaters
USED WITH SIZES
CATALOG
ORDERING NO.
NOMINAL
CAPACITY (kW)
FUSES
024
030
036
042
048
060
ELECTRIC HEATERS (208/230 — SINGLE PHASE — 60 Hz)
CPHEATER052A00
CPHEATER069A00
CPHEATER065A00
CPHEATER051A00
CPHEATER053A00
CPHEATER054A00
5.0
7.5
0
0
0
4
6
6
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
10.0
15.0
20.0
20.0
X
ELECTRIC HEATERS (208/230 — THREE PHASE — 60 Hz)
CPHEATER055A00
CPHEATER056A00
CPHEATER057A00
CPHEATER059A00
5.0
0
0
0
6
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
10.0
15.0
20.0
NOTE: Electric heaters are rated at 240v. Refer to Multiplication Factors table for other voltages.
X = Approved combinations.
Minimum Airflow for Reliable Electric Heater Operation (CFM)
UNIT SIZE
AIRFLOW
024
750
030
1000
036
1250
042
1400
048
1500
060
1800
6
ECONOMIZER
COIL
FILTER ACCESS DOOR
(HORIZONTAL
APPLICATION ONLY.)
DO NOT REMOVE
FROM DOWNFLOW
DISCHARGE.
FILTER
REPLACEMENT
PANEL
ECONOMIZER
HOLE FOR
ECONOMIZER
WIRING HARDNESS
17 13/32
11 13/32”
RAINHOOD
DOOR
LATCH ANGLE
CAULK BOTTOM CORNER
OF ECONOMIZER
ON EACH SIDE
16 1/4”
SIDE VIEW
HINGED FILTER
ACCESS DOOR
INSTALL
FILTER ACCESS
DOOR STICKER
FI LTER
ALUMINUM
FILTER
COIL
ECONOMIZER
BASE
FLANGE
ON BASE
AIL
DET
MANUAL OUTSIDE AIR DAMPER
FILTER RACK
BEND FLANGE AT 90˚ -SCREW TO
DIVIDER WITH 1-IN. SCREW
REPLACEMENT
PANEL
MANUAL OUTSIDE
AIR HOOD
TOP FILTER RACK
EV APORATOR
COIL
DAMPER
BLADE
BOTTOM FILTER
RACK
A05239
7
UNIT DIMENSIONS -- 50XP024--036
A08452
8
UNIT DIMENSIONS -- 50XP042--060
A08453
9
ACCESSORY ROOF CURB - 50XP024
-060
HVACunit
base
HVAC unit
base
Gask eting
inner flange*
Screw
(NOTE A)
Screw
(NOTE A)
Gasketing
inner flange*
*Gasketing
outer flange
*Gasketing
outer flange
Wood nailer*
Wood nailer*
Flashing field
supplied
Flashing field
supplied
Roofcurb*
Roofcurb*
Insulation(field
supplied)
Insulation(field
supplied)
Roofing material
field supplied
Roofing material
field supplied
Duct work
field supplied
Duct work
field supplied
Cant strip
field supplied
Cant strip
field supplied
Roof
Roof
*Provided with roofcurb
*Provided with roofcurb
Roof Curb for Small Cabinet
Roof Curb for
Large Cabinet
Note A:When unit mounting screw is use,d
retainer bracket must also be used.
Note A:When unit mounting screw is use,d
retainer bracket must also be used.
Supply opening
(B x C)
BTyp.
D
CTyp.
445/16"
(1126 mm)
R/A
S/A
A
Gasket around
duct
Short
Support
Insulated
deck pan
Gasket around
outer edge
Insulated
deck pan
Long
Support
Return opening
(B X C)
C00076
A
B
C
D
UNIT SIZE
ORDERING NUMBER
IN. (MM)
IN. (MM)
11 (279)
IN. (MM)
IN. (MM)
CPRFCURB006A00
CPRFCURB007A00
CPRFCURB008A00
CPRFCURB009A00
8 (203)
14 (356)
8 (203)
16--1/2 (419)
16--1/2 (419)
17--3/8 (441)
17--3/8 (441)
28--3/4 (730)
28--3/4 (730)
40--1/4 (1022)
40--1/4 (1022)
50XP024 -036
50XP042 -060
11 (279)
16--3/16 (411)
16--3/16 (411)
14 (356)
NOTES:
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied, as required, to unit being installed.
3. Roof curb is made of 16--gauge steel.
4. Attach ductwork to curb (flanges of duct rest on curb).
5. Insulated panels: 1--in. (25.4 mm) thick fiberglass 1 lb. density.
6. When unit mounting screw is used (see Note A), a retainer bracket must be used as well. This bracket must also be used when required by code for hurricane or seismic
conditions. This bracket is available through Micrometl.
10
50XP UNIT SUGGESTED RIGGING
1
2
(914 mm)
DETAIL A
3
4
A07216
A08005
SMALL CABINET
LARGE CABINET
Unit*
024
lb
024
kg
030
lb
030
kg
036
lb
036
kg
042
lb
042
kg
048
lb
048
kg
060
060
kg
Unit*
lb
Rigging
Weight
Rigging
Weight
345
156
349
158
367
166
425
193
459
208
504
229
NOTE: See dimensional drawing for corner weight distribution. Corner weights shown on drawing are based on unit---only weights and do not include pack-
aging.
SELECTION PROCEDURE (WITH EXAMPLE)
1. Determine cooling and heating requirements at
design conditions:
4. Determine fan speed and power requirements at
design conditions.
Given:
Before entering the air delivery tables, calculate the total static
pressure required. From the given example, the Filter Pressure
Drop Table, and the Accessory Electric Heat Pressure Drop table,
find:
Required Cooling Capacity (TC) . . . . . . . . . . 34,500 Btuh
Sensible Heat Capacity (SHC) . . . . . . . . . . . . 26,000 Btuh
Required Heating Capacity . . . . . . . . . . . . . . . 15,000 Btuh
Condenser Entering Air Temperature . . . . . . . . 95°F(35°C)
Indoor--Air Temperature . . . . . . . . . . . . . 80°F (26°C) edb
67°F (19°C) ewb
Evaporator Air Quantity . . . . . . . . . . . . . . . . . . 1200 CFM
External Static Pressure . . . . . . . . . . . . . . . . . 0.20 IN. W.C.
Electrical Characteristics . . . . . . . . . . . . . . . . . . . 230--1--60
External Static Pressure
Filter
0.200 IN. W.C.
0.130 IN. W.C.
0.032 IN. W.C.
0.362 IN. W.C.
Wet Coil Pressure Drop
Total Static Pressure
Enter the table for Dry Coil Air Delivery—At 0.362 IN. W.C. ESP
(external static pressure) and NOM speed pin selection, the motor
will deliver 1235 cfm.
2. Select unit based on required cooling capacity.
5. Select unit that corresponds to power source
available.
The Electrical Data Table shows that the unit is designed to operate
at 208--1--60.
Enter Net Cooling Capacities table at condenser entering
temperature of 95°F (35°C). The 036 unit at 1225 CFM and 67°F
(19°C) ewb (entering wet bulb) will provide a total capacity of
36,500 Btuh and a SHC of 27,600 Btuh. Calculate SHC correction,
if required, using Note 4 under Cooling Capacities tables.
3. Select electric heat.
The required heating capacity is 15,000 Btuh.
Determine additional electric heat capacity in kW.
15,000 Btuh
= 4.4kW of heat required
3,414 Btuh/kW
Enter the Electric Heater Packages table for 208/240, single--phase,
036 unit. The 5 kW heater at 240v most closely satisfies the
heating required. To calculate kW at the 208v, multiply the heater
kW by multiplication factor 0.75 found in the Wattage
Multiplication Factors table.
5 kW x 0.75 = 3.75 kW
3.75 kW x 3414 = 12,802.50 Btuh
11
12
13
14
15
PERFORMANCE DATA (CONT)
Economizer 1--in. Filter Pressure Drop (IN. W.C.)
UNIT50XP
024 -036
042 -060
PRESSURE DROP
0.20
0.25
Multiplication Factors
HEATER kW RATING
VOLTAGE DISTRIBUTION V/3/60
MULTIPLICATION FACTOR
200
208
230
240
0.69
0.75
0.92
1.00
240
Filter Pressure Drop Table (IN. W.C.)
CFM
900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300
FILTER SIZE
in. (mm)
500
600
700
800
20X20X1
0.05 0.07 0.08 0.10 0.12 0.13 0.14 0.15
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
(508X508X25)
20X24X1
(508X610x25)
24X30X1
(610X762x25)
—
—
—
—
—
—
0.09 0.10 0.11 0.13 0.14 0.15 0.16
—
—
—
—
0.07 0.08 0.09 0.10 0.11 0.12 0.13 0.14 0.15 0.16 0.17 0.18
Electric Heat Pressure Drop Tables (IN. W.C.)
Small Cabinet: 024--036
CFM
STATIC
500
0.00
0.00
0.00
0.00
600
0.00
0.00
0.00
0.00
700
0.00
0.00
0.00
0.00
800
0.00
0.00
0.00
0.02
900
0.00
0.00
0.00
0.04
1000
0.00
0.00
0.02
0.06
1100
0.00
0.02
0.04
0.08
1200
0.00
0.03
0.06
0.10
1300
0.02
0.05
0.07
0.12
1400
0.04
0.07
0.09
0.14
1500
0.06
0.08
0.10
0.16
1600
0.07
0.09
0.11
0.18
5 kW
7.5 kW
10 kW
15 kW
Large Cabinet: 042--060
CFM
1800
0.05
0.06
0.06
0.08
0.09
STATIC
1100
0.00
0.00
0.00
0.00
0.02
1200
0.00
0.00
0.00
0.02
0.03
1300
0.00
0.01
0.01
0.03
0.04
1400
1500
0.02
0.03
0.03
0.05
0.06
1600
0.03
0.04
0.04
0.06
0.07
1700
1900
2000
2100
0.08
0.09
0.09
0.11
0.12
2200
2300
0.10
0.11
0.11
0.13
0.14
2400
2500
5 kW
7.5 kW
10 kW
15 kW
20 kW
0.01
0.02
0.02
0.04
0.05
0.04
0.05
0.05
0.07
0.08
0.06
0.07
0.07
0.09
0.10
0.07
0.08
0.08
0.10
0.11
0.09
0.10
0.10
0.12
0.13
0.11
0.12
0.12
0.14
0.15
0.12
0.13
0.13
0.15
0.16
ECM Dry Coil Airflow--Small Cabinet
CFM ADJUST PIN SELECT
LO PIN
NOM PIN
0.4 -0.69
HI PIN
UNIT
EXTERNAL STATIC
PRESSURE RANGE
COOLING
COOLING DEHUMIDIFY
COOLING
COOLING DEHUMIDIFY
COOLING
COOLING DEHUMIDIFY
SIZE
024
030
036
0.0 -0.39
0.4 -0.69
0.7 -1.0
0.0 -0.39
0.7 -1.0
0.0 -0.39
0.4 -0.69
0.7 -1.0
800
715
1010
890
1110
990
725
670
920
845
1025
960
--
--
825
795
970
910
885
715
1105
890
1235
990
805
695
1030
865
1175
975
730
645
930
825
1115
940
990
795
1255
1010
1400
1125
930
775
1160
980
1355
1110
855
745
1050
925
1280
1085
ECM Dry Coil Airflow--Large Cabinet
CFM ADJUST PIN SELECT
LO PIN
NOM PIN
NOM PIN
UNIT SIZE
EXTERNAL STATIC PRESSURE RANGE
COOLING
0.1 -1.0
1100
980
1260
1120
1575
1400
0.1 -1.0
1225
980
1400
1120
1750
1400
0.1 -1.0
1410
1125
1610
1290
2010
1610
042
COOLING DEHUMIDIFY
COOLING
COOLING DEHUMIDIFY
COOLING
048
060
COOLING DEHUMIDIFY
Wet Coil Pressure Drop (IN. W.C.)
Standard CFM (S.C.F.M)
Unit
Size
024
030
036
042
048
060
600
0.005
700
0.007
0.007
800
0.010
0.010
900
1000
0.015
0.015
0.023
0.014
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
0.012
0.012
0.019
0.018
0.027
0.017
0.021
0.032
0.020
0.027
0.024
0.037
0.024
0.032
0.042
0.027
0.036
0.047
0.031
0.041
0.029
0.035
0.046
0.032
0.039
0.052
0.036
0.043
0.057
0.040
0.063
0.045
0.068
0.049
0.053
16
TYPICAL PIPING AND WIRING
ROOF-MOUNTING
CURB
ROOF
RETURN-AIR
FLEXIBLE DUCT
SUPPLY-AIR
FLEXIBLE DUCT
CEILING
CONCENTRIC DIFFUSER BOX
(FIELD-SUPPLIED)
C00023
INDOOR
THERMOSTAT
RETURN
AIR
FROM
POWER
SOURCE
TOP COVER
DISCONNECT
PER NEC*
*NEC - NATIONAL ELECTRICAL CODE
C00063
17
APPLICATION DATA
Maximum cooling airflow — To minimize the possibility of
condensate blow--off from the evaporator, airflow through the units
should not exceed 450 cfm per ton.
Condensate trap — A 2--in. (51 mm) condensate trap must be
field supplied.
1” (25 mm) MIN
.
Minimum cooling airflow — Minimum cooling airflow is 350
cfm per ton for standard cooling modes. Airflow can be lower in
certain modes when humidity removal is an issue.
TRAP
OUTLET
2” (51 mm) MIN.
Minimum cooling operating outdoor air temperature — All
standard units have a minimum outdoor operating temperature of
55_F (13_C). With accessory low ambient temperature kit, units
can operate at temperatures down to 0_F (--17_C).
A08001
Ductwork — Secure downflow discharge ductwork to roof curb.
For horizontal discharge applications, attach ductwork to unit with
flanges.
Maximum cooling operating outdoor air temperature —
Maximum outdoor operating air temperature is 125_F (52_C).
To convert a unit to downflow discharge — Units are equipped
with factory--installed inserts in the downflow openings. Removal
of the inserts is similar to removing an electrical knock--out. Leave
on duct covers to seal the horizontal discharge openings in the unit.
Units installed in horizontal discharge orientation do not require
duct covers.
18
ELECTRICAL DATA
ELECTRIC HEAT
POWER SUPPLY
VOLTAGE
COMPRESSOR
OFM
FLA
IFM
FLA
NOMINAL
V --- P H --- H Z
RANGE
MAX
FUSE or
CKT BKR
30/30
30/35
40/45
60/60
30/30
30/35
40/45
60/60
-
UNIT
NOMINAL
FLA
MCA
MOCP
KW
MIN
MAX
RLA
LRA
-/-
3.8/5
5.4/7.2
7.5/10
-/-
3.8/5
5.4/7.2
7.5/10
11.3/15
-/-
-/-
22.0/22.0
27.9/31.4
37.9/42.9
50.5/57.5
23.6/23.6
27.9/31.4
37.9/42.9
50.5/57.5
73.1/83.5
26.9/26.9
31.1/34.5
41.0/46.0
53.6/60.6
76.2/86.6
23.0/23.0
23.0/23.5
34.6/38.6
47.6/53.6
30.9/30.9
31.1/34.5
41.0/46.0
53.6/60.6
76.2/86.6
---
18.1/20.8
26/30
36.1/41.7
-/-
18.1/20.8
26/30
36.1/41.7
54.2/62.5
-/-
---
50XP-024
50XP-030
208/230-1-60
208/230-1-60
187
253
13.5
61.0
0.8
0.8
4.3
4.3
---
---
---
---
187
253
15.9
73.0
---
---
80/90
35/35
35/35
45/50
---
---
3.8/5
5.4/7.2
7.5/10
11.3/15
-/-
5
10
18.1/20.8
26/30
36.1/41.7
54.2/62.5
-/-
10.4/12
20.8/24.1
31.3/36.1
-/-
---
208/230-1-60
208/230-3-60
187
187
253
253
16.9
12.2
83.0
77.0
0.8
0.8
6.8
6.8
---
60/70
50XP-036
---
80/90
30/30
30/30
35/35
50/60
45/45
45/45
45/50
---
---
---
---
15
-/-
---
---
3.8/5
5.4/7.2
7.5/10
11.3/15
15/20
-/-
3.8/5
7.5/10
11.3/15
15/20
-/-
18.1/20.8
26/30
36.1/41.7
54.2/62.5
72.2/83.3
-/-
10.4/12
20.8/24.1
31.3/36.1
41.6/48
-/-
---
---
208/230-1-60
208/230-3-60
208/230-1-60
208/230-3-60
208/230-1-60
208/230-3-60
187
187
187
187
187
187
253
253
253
253
253
253
22.4
15.4
21.3
14.7
27.0
19.2
105.0
88.0
0.8
0.8
1.6
1.6
1.6
1.6
6.8
6.8
6.8
6.8
9.1
9.1
60/70
---
---
80/90
100/125
50XP-042
98.8/112.7
27.0/27.0
27.0/27.0
34.6/38.6
47.6/53.6
60.5/68.5
33.9/33.9
33.9/34.5
41.0/46.0
53.6/60.6
76.2/86.6
98.8/112.7
26.7/26.7
26.7/26.7
34.6/38.6
47.6/53.6
60.5/68.5
44.3/44.3
44.3/44.3
44.3/48.9
56.5/63.5
79.1/89.5
101.6/115.5
33.0/33.0
33.0/33.0
37.4/41.4
50.5/56.5
63.3/71.3
35/35
35/35
35/35
50/60
---
45/45
45/45
45/50
---
---
---
35/35
35/35
35/35
50/60
---
60/60
60/60
60/60
---
---
---
---
---
---
---
70/70
---
3.8/5
5.4/7.2
7.5/10
11.3/15
15/20
-/-
3.8/5
7.5/10
11.3/15
15/20
-/-
18.1/20.8
26/30
36.1/41.7
54.2/62.5
72.2/83.3
-/-
10.4/12
20.8/24.1
31.3/36.1
41.6/48
-/-
---
---
109.0
91.0
60/70
80/90
100/125
50XP-048
---
---
---
---
70/70
---
---
---
3.8/5
5.4/7.2
7.5/10
11.3/15
15/20
-/-
3.8/5
7.5/10
11.3/15
15/20
18.1/20.8
26/30
36.1/41.7
54.2/62.5
72.2/83.3
-/-
10.4/12
20.8/24.1
31.3/36.1
41.6/48
145.0
137.0
60/70
80/90
100/125
---
50XP-060
40/40
40/40
40/45
60/60
---
---
---
---
70/80
460-3-60.
452 v
464 v
455 v
464 455
452
1371
*Heater capacity (kW) based on heater voltage of 208v, 240v, &
480v. If power distribution voltage to unit varies from rated
heater voltage, heater kW will vary accordingly.
457
452
457
5
7
2
464
457
457
455
7
7
457
1.53
19
TYPICAL WIRING SCHEMATIC 208/230--1--60
A08460
20
TYPICAL WIRING SCHEMATIC 208/230--3--60
A08461
21
CONTROLS
Operating sequence
Cooling — When the system thermostat calls for cooling, 24 V is
supplied to the “Y” and “G” terminals of the thermostat. This
completes the circuit to the contactor coil (C) and indoor fan
board. The normally open contacts of C close and complete the
circuit to compressor motor (COMP) and to outdoor (condenser)
fan motor (OFM). Both motors start instantly. The IFM starts
according to the selection pin set--up on the Easy Select Board.
On the loss of the thermostat call for cooling, 24 V is removed
from both the “Y” and “G” terminals (provided the fan switch is in
the “AUTO” position) de--energizing the compressor contactor and
opening the contacts supplying power to compressor/OFM. After a
preselected delay, the IFM shuts off. If the thermostat fan selector
switch is in the “ON” position, the IFM will run continuously at
speed selected on Easy Select Board
Heating — If accessory electric heaters are installed, on a call for
heat, circuit R--W is made through the thermostat contacts. Circuit
R--G is made which energizes the IFM. If the heaters are staged,
then the thermostat closes a second set of contacts (W2) when
second stage is required. When thermostat is satisfied, contacts
open, deenergizing the heater relay. After a preselected delay, the
IFM shuts off. If the thermostat fan selector switch is in the “ON”
position, the IFM will run continuously at speed selected on Easy
Select Board.
NOTE: On units with a Time Guard II device: Once the
compressor has started and then stopped, it cannot be restarted
again until 5 minutes have elapsed.
The indoor blower operation with a call for fan operation (G) in
cooling mode will perform by the on/off delay profile selected at
start up on the Easy Select Board.
®
22
C. Fans:
1. The evaporator fan shall be direct--drive variable speed
GUIDE SPECIFICATIONS
Packaged Electric Cooling Unit
Constant Volume Application
HVAC Guide Specifications
motor and control, as shown on equipment drawings.
2. Fan wheel shall be made from steel, be double--inlet type
with forward curved blades with corrosion resistant finish.
Fan wheel shall be dynamically balanced.
Size Range:
Model Number: 50XP
Part 1 — General
2 to 5 Tons, Nominal Cooling
3. Condenser fan shall be direct drive propeller type with alu-
minum blades riveted to corrosion resistant steel spiders, be
dynamically balanced, and discharge air vertically.
D. Compressor:
SYSTEM DESCRIPTION
1. Fully hermetic compressors with factory--installed vibration
isolation.
2. Scroll compressors shall be standard on all units.
Outdoor rooftop mounted or ground mounted, electric cooling
unit utilizing a hermetic compressor for cooling duty and
optional electric heating. Unit shall discharge supply air
vertically or horizontally as shown on contract drawings.
Condenser fan/coil section shall have a draw--thru design with
vertical discharge for minimum sound levels.
E. Coils:
Evaporator and condenser coils shall have aluminum plate fins
mechanically bonded to seamless copper tubes with all joints
brazed. (Copper/copper and vinyl--coated construction
available as option). Tube sheet openings shall be belled to
prevent tube wear.
QUALITY ASSURANCE
A. Unit shall be rated in accordance with ARI Standards
210/240 and 270.
B. Unit shall be designed in accordance with UL Standard
1995.
C. Unit shall be manufactured in a facility registered to ISO
9001 manufacturing quality standard.
F. Refrigerant Components:
Refrigerant expansion device shall be of the TXV
(thermostatic expansion valve) type.
G. Filters:
D. Unit shall be UL listed and c--UL certified as a total
package for safety requirements.
E. Roof curb shall be designed to conform to NRCA
Standards.
Filter section shall consist of field--installed, throwaway, 1--in.
(25 mm) thick fiberglass filters of commercially available
sizes.
H. Controls and Safeties:
F. Insulation and adhesives shall meet NFPA 90A
requirements for flame spread and smoke generation.
1. Unit controls shall be complete with a self--contained low
voltage control circuit.
G. Cabinet insulation shall meet ASHRAE Standard 62P.
DELIVERY, STORAGE AND HANDLING
2. Units shall incorporate an internal compressor protector that
provides reset capability.
Unit shall be stored and handled per manufacturer’s
recommendations.
3. Unit shall provide High and Low/Loss--of--Charge Pressure
Safety Protection.
Part 2 — Products
EQUIPMENT
A. General:
I. Operating Characteristics:
1. Unit shall be capable of starting and running at 125_F
(51_C) ambient outdoor temperature,exceeding maximum
load criteria of ARI Standard 210.
Factory--assembled, single--piece, cooling unit. Contained
within the enclosure shall be all factory wiring, piping,
controls, refrigerant charge with R--410A refrigerant, and
special features required prior to field start--up.
2. Compressor with standard controls shall be capable of op-
eration down to 55_F (13_C) ambient outdoor temperature.
3. Indoor Fan on/off delay profile is selected (for cooling) on
the Easy Select board.
B. Unit Cabinet:
J. Electrical Requirements:
1. Unit cabinet shall be constructed of phosphated,
zinc--coated, pre--painted steel capable of with--standing 500
hours in salt spray.
All unit power wiring shall enter the unit cabinet at a single
location.
2. Normal service shall be through a single removable cabinet
panel.
K. Motors:
1. Compressor motors shall be of the refrigerant--cooled type
with line--break thermal and current overload protection.
3. The unit shall be constructed on a rust proof unit base that
has an externally trapped, integrated sloped drain pan.
2. All fan motors shall have permanently lubricated bearings,
and inherent, automatic reset, thermal overload protection.
4. Evaporator fan compartment top surface shall be insulated
with a minimum 1/2--in. (13 mm) thick, flexible fiberglass
insulation, coated on the air side and retained by adhesive
and mechanical means. The evaporator wall sections will be
insulated with a minimum semi--rigid foil--faced board ca-
pable of being wiped clean. Aluminum foil--faced fiberglass
insulation shall be used in the entire indoor air cavity
section.
3. Condenser fan motor shall be totally enclosed.
L. Grille:
1. Louvered Grille:
Louvered grille shall be standard on all units.
5. Unit shall have a field--supplied condensate trap.
23
6. Low Ambient Package:
GUIDE SPECIFICATIONS (CONT)
Shall consist of a solid--state control and condenser coil
temperature sensor for controlling condenser--fan motor op-
eration, which shall allow unit to operate down to 0_F
(--18_C) outdoor ambient temperature when properly
installed.
M. Special Features:
1. Coil Options:
Shall include factory--installed optional tin--plated indoor,
copper/copper and vinyl--coated refrigerant coils.
2. Economizer:
7. Filter Rack Kit:
Shall provide filter mounting for downflow or horizontal
applications.
a. Economizer controls capable of providing free cooling
using outside air.
8. Square--To--Round Duct Transitions (024--048):
Shall have the ability to convert the supply and return open-
ings from rectangular to round. (024--048 only)
b. Equipped with low leakage dampers not to exceed 3%
leakage, at 1.0 IN. W.C. pressure differential.
c. Spring return motor shuts off outdoor damper on power
failure.
3. Flat Roof Curb:
9. Compressor Protection:
Solid--state control shall protect compressor by preventing
“short cycling.“
Curbs shall have seal strip and a wood nailer for flashing
and shall be installed per manufacturer’s instructions.
4. Manual Outdoor Air Damper:
10. Crankcase Heater:
Shall provide anti--floodback protection for low--load cool-
ing applications.
Package shall consist of damper, birdscreen, and rainhood
which can be preset to admit outdoor air for year--round
ventilation.
11. Electric Heaters:
a. Electric heater shall be availabel as a field--installed
option.
5. Thermostat:
b. Heater elements shall be open wire type, adequately
supported and insulated with ceramic bushings.
To provide for one--stage heating and cooling in addition
manual or automatic changeover and indoor fan control.
c. Electric heater packages must provide single point
power connection capability.
12. Compressor Start Kit (single phase units only):
Shall provide additional starting torque for single--phase
compressors.
Catalog No: 50XP---05PD
Copyright 2008 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231
Printed in U.S.A.
Edition Date: 09/08
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Replaces: 50XP---4PD
24
|