Carrier 50XP User Manual

50XP  
Performancet 13 SEER  
Single---Packaged Air Conditioner System with PuronR  
(R---410A) Refrigerant Single and Three Phase  
2 to 5 Nominal Tons (Sizes 024---060)  
Product Data  
Easy Installation  
Factory--assembled package is a fully self--contained, electric  
cooling unit that is prewired, pre--piped, and pre--charged for  
minimum installation expense. These units are available in a  
variety of standard cooling sizes with voltage options to meet  
residential and light commercial requirements. Units are  
lightweight and install easily on a rooftop or at ground level. The  
high tech composite base eliminates rust problems associated with  
ground level applications.  
Durable, dependable components  
Scroll Compressors are designed for high efficiency. Each  
compressor is hermetically sealed against contamination to help  
promote longer life and dependable operation. Each compressor  
also has vibration isolation to provide quieter operation. All  
compressors have internal high pressure and overcurrent  
protection.  
Convertible duct configuration  
Unit is designed for easy use in either downflow or horizontal  
applications. Each unit is easily converted from horizontal to  
downflow. Downflow operation is easily provided in the field to  
allow vertical ductwork connections. The basepan utilizes  
knockout style seals on the bottom openings to ensure a positive  
seal in the horizontal airflow mode.  
C99064  
Fig. 1 -- Unit 50XP  
Direct--drive variable speed blower motor is standard on all  
models.  
Single--Packaged Products with Energy--Saving Features and  
PuronR refrigerant.  
S Up to 13.5 SEER  
S Factory--Installed TXV  
S Variable Speed Blower--Standard  
S Low Sound Levels  
Direct--drive PSC condenser--fan motors are designed to help  
reduce energy consumption and provide for cooing operation  
down to 55_F (13_C) outdoor temperature. Motormasterr II low  
ambient kit is available as a field--installed accessory.  
Thermostat controls  
Time Guardr  
II anti--short cycle protection circuitry. If a  
non--corporate thermostat without anti--short cycle protection is  
used the Time Guard II field--installed anti--short cycle kit is  
recommended.  
Refrigerant system is designed to provide dependability. Liquid  
filter driers are used to promote clean, unrestricted operation. Each  
unit leaves the factory with a full refrigerant charge. Refrigerant  
service connections make checking operating pressures easier.  
FEATURES/BENEFITS  
One--piece cooling unit  
with optional electric heater, low  
installation cost, dependable performance and easy maintenance.  
Efficient operation  
High--efficiency design with a SEER (Seasonal Energy Efficiency  
Ratio) of up to 13.5.  
Puron Environmentally Sound Refrigerant is Carrier’s unique  
refrigerant designed to help protect the environment. Puron is an  
HFC refrigerant which does not contain chlorine that can harm the  
ozone layer. Puron refrigerant is in service in millions of systems  
proving highly reliable, environmentally sound performance.  
IdealHumidity Technology featuring Thermidistat control and  
Variable Speed Blower motor that provides greater comfort,  
humidity control, and energy efficiency. You can expect up to 30  
times better dehumidification; economical constant fan for less  
than $50 a year, which provides improved indoor air quality and  
more even temperatures from room to room; and reduced indoor  
noise due to lower air velocity. In addition, you’ll realize improved  
installation flexibility with 3 different airflow choices for best  
overall comfort.  
Thermostatic Expansion Valve -- A hard shutoff, balance port  
TXV maintains a constant superheat at the evaporator exit (cooling  
cycle) resulting in higher overall system efficiency.  
Evaporator and condenser coils are computer--designed for  
optimum heat transfer and cooling efficiency. The evaporator coil  
is fabricated from copper tube and aluminum fins and is located  
inside the unit for protection again damage. The condenser coil is  
internally mounted on the top tier of the unit. Copper fin coils and  
pre--coated fin coils are available from the factory by special order.  
these coils are recommended in applications where aluminum fins  
are likely to be damaged due to corrosion. They are ideal for  
seacoast applications.  
High and Low Pressure Switches provide added reliability for the  
compressor.  
1
MODEL NUMBER NOMENCLATURE  
---  
50XP  
024  
--- --- ---  
3
0
--- ---  
1
Options  
BT --- AL evap, vin y l con den ser  
CC --- AL evap, CU con den ser  
CU --- CU evap & condenser  
Type of Unit  
50XP --- Single Packaged  
Air Conditioner  
System  
TP --- Base unit with tin plated indoor coil hairpins  
TV --- TP with vinyl coating on outdoor coil  
TC --- TP with AL indoor coil & CU/CU outdoor  
coil  
N/A  
See Price Page for full list of factory options.  
Only used if ordering an option  
Nominal Cooling Capacity  
024 --- 2.0 Tons  
030 --- 2.5 Tons  
036 --- 3.0 Tons  
Packaging  
042 --- 3.5 Tons  
048 --- 4.0 Tons  
060 --- 5.0 Tons  
Series  
Electrical Supply  
N/A  
3 --- 208/230---1---60  
5 --- 208/230---3---60  
LEGEND  
AL --- Aluminum  
CU --- Copper  
ISO 9001:2000  
REGISTERED  
3
ARI* CAPACITIES  
Cooling Capacities and Efficiencies  
NET COOLING  
CAPACITIES (Btuh)  
24,000  
UNIT 50XP  
NOMINAL TONS  
STANDARD CFM  
EER**  
SEER†  
024  
030  
036  
042  
048  
060  
2
2--1/2  
3
770  
960  
1100  
1450  
1450  
1710  
11.0  
11.0  
11.2  
11.2  
11.0  
11.0  
13.2  
13.0  
13.5  
13.0  
13.0  
13.0  
29,000  
36,000  
3--1/2  
4
41,000  
45,000  
5
57,000  
LEGEND  
Notes:  
d B --- Sound Levels (decibels)  
db—Dry Bulb  
1. Ratings are net values, reflecting the effects of circulating fan heat.  
Ratings are based on:  
SEER—Seasonal Energy Efficiency Ratio  
wb—Wet Bulb  
COP---Coefficient of Performance  
* Air Conditioning & Refrigeration Institute.  
**At A” conditions---80_F (26.7_C) indoor db/67_F (19.4_C) indoor wb &  
95_F (35_C) outdoor db.  
{ Rated in accordance with U.S. Government DOE Department of Energy)  
test procedures and/or ARI Standards 210/240.  
Cooling Standard: 80°F (26.7_C) db, 67°F wb (19.4_C) in door en ter in g --- air  
temperature and 95°F db (35_C) outdoor entering---air temperature.  
2. Before purchasing this appliance, read important energy cost and effi-  
ciency information available from your retailer.  
A--Weighted Sound Power (dBA)  
STANDARD  
RATING  
(dBA)  
TYPICAL OCTAVE BAND SPECTRUM (dBA) (without tone adjustment)  
50XP  
125  
250  
500  
1000  
2000  
4000  
8000  
024  
030  
036  
042  
048  
060  
72  
72  
72  
72  
78  
78  
58.8  
58.8  
60.7  
56.7  
62.4  
63.5  
63.5  
63.5  
63.3  
62.8  
69.9  
67.6  
67.2  
67.2  
66.8  
67.8  
71.3  
71.8  
66.9  
66.9  
66.5  
67.4  
73.4  
75.5  
63.7  
63.7  
64.2  
63.7  
70.0  
71.0  
58.3  
58.3  
60.3  
57.7  
66.3  
68.1  
50.0  
50.0  
53.0  
50.8  
60.1  
59.9  
*
Tested in accordance with ARI Standard 270 (not listed in ARI).  
4
PHYSICAL DATA  
Physical Data--Unit 50XP  
UNIT SIZE  
024  
030  
036  
042  
048  
060  
NOMINAL CAPACITY (ton)  
2
2 --- 1/2  
3
3 --- 1/2  
4
5
SHIPPING WEIGHT (lb)  
SHIPPING WEIGHT (kg)  
356  
161  
360  
163  
378  
171  
436  
198  
470  
213  
515  
234  
Scroll  
1
COMPRESSORS  
Quantity  
REFRIGERANT (R---410A)  
Quantity (lb.)  
Quantity (kg)  
7.3  
3.3  
8.0  
3.6  
9.5  
4.3  
10.7  
4.9  
11.25  
5.1  
13.2  
6.0  
REFRIGERANT METERING DEVICE  
TXV  
OUTDOOR COIL  
Rows...Fins/in.  
Face Area (sq ft)  
2...21  
11.95  
2...21  
12.0  
2...21  
13.6  
2...21  
15.4  
2...21  
17.4  
2...21  
19.3  
OUTDOOR FAN  
Nominal Cfm  
Diameter (in.)  
Diameter (mm)  
Motor Hp (Rpm)  
2350  
22  
558.8  
1/8 (825)  
2700  
22  
558.8  
1/8 (825)  
2350  
22  
558.8  
1/8 (825)  
2800  
22  
558.8  
1/8 (825)  
3300  
22  
3300  
22  
558.8  
558.8  
1/4 (1100)  
1/4 (1100)  
INDOOR COIL  
Rows...Fins/in.  
Face Area (sq ft)  
3...15  
3.7  
3...15  
3.7  
4...15  
3.7  
3...15  
4.7  
4...15  
4.7  
4...17  
5.7  
INDOOR BLOWER  
Nominal Cooling Airflow (Cfm)  
Size (in.)  
1400  
11x10  
279.4x254  
3/4 (1075)  
1750  
11x10  
279.4x254  
1.0 (1040)  
800  
1000  
10x10  
254x254  
1/2 (1050)  
1100  
1400  
10x10  
11x10  
11x10  
Size (mm.)  
254x254  
1/2 (1050)  
279.4x254  
3/4 (1000)  
279.4x254  
3/4 (1075)  
Motor HP (RPM)  
HIGH---PRESSURE SWITCH  
(psig) Cut---out Reset (Auto)  
650 +/--- 15  
420 +/--- 25  
L O S S --- O F --- C H A R G E / L O W --- P R E S S U R E  
SWITCH (Liquid Line) (psig) cut---out Re-  
set (auto)  
20 +/ --- 5  
45 +/--- 10  
RETURN---AIR FILTERS}  
Throwaway Size (in.)  
Throwaway Size (mm)  
20x20x1  
508x508x25  
20x24x1  
508x610x25  
24x30x1  
610x762x25  
{
Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity  
of 300 ft/minute for throwaway type or 450 ft/minute for high---capacity type. Air filter pressure drop for non---standard filters must not exceed 0.08 IN. W.C..  
} If using accessory filter rack refer to the filter rack installation instructions for correct filter sizes and quantity.  
5
compartment. Heater sizes range from 5.0 to 20.0 kW. The electric  
heater design allows the use of a single--point power supply for the  
entire unit, resulting in lower installed costs.  
OPTIONS AND ACCESSORIES  
Factory--installed options  
Coil options include Tin--Plated* indoor hairpins, copper/copper  
and vinyl--coated construction for refrigerant coils. Units are  
shipped standard with copper tube/aluminum fin construction. See  
model number nomenclature for coil options.  
*Tin--Plated indoor coils are built with special hairpins that are  
designed to resist both general pitting corrosion and excessive  
indoor corrosion(Formicary Corrosion).  
Filter Rack features easy installation, serviceability, and  
high--filtering performance for vertical or horizontal applications.  
Flat roof curbs in both 8 in. (203.2 mm) and 14 in. (355.6 mm)  
sizes are available for roof mounted applications.  
Square--to--round duct transition kit enables 024--048 size units  
to be fitted to 14 in. (355.6 mm) round ductwork.  
Thermidistat Control coupled with the system’s variable speed  
indoor blower delivers Carrier’s patented IdealHumidity  
Technology that allows for even greater humidity control. Along  
with more precisely controlling temperature and humidity, the  
Thermidistat offers full seven--day programmability allowing you  
to further customize your comfort and energy savings.  
Field--installed accessories  
Economizer with Solid -State Controls and Barometric  
Relief Dampers  
Manual Air Damper (25% open)  
Electric Heaters  
Filter Rack  
Thermostats provide control for the system heating and cooling  
functions. Thermostat models are available in both programmable  
and non--programmable versions.  
Flat Roof Curbs (8 -in. and 14 -in.) (203.2 and 355.6 mm)  
Square -to -Round Duct Transition Kit  
Thermidistatt  
Crankcase Heater provides anti--floodback protection for  
Thermostats  
low--load cooling applications.  
Crankcase Heater  
Compressor Start Kit (for use on single--phase units only)  
Rigging Kit  
Low Ambient Kit (Motormaster® II Control)  
Solid -State Time Guard® II Device  
Lifting Kit  
Compressor start kit assists compressor start--up by providing  
additional starting torque on single phase units and prolongs  
compressor motor life.  
Rigging kit includes lifting brackets which are inserted into the  
unit base rigging holds to lift unit for rooftop applications.  
Low--ambient kit (Motormaster II control) allows the use of  
mechanical cooling down to outdoor temperatures as low as 0_F  
(--17_C) when properly installed.  
Solid--state Time Guard II device provides short--cycling  
protection for the compressor. Not required with corporate  
electronic thermostats.  
Economizer with solid--state controls and barometric relief  
dampers includes filter racks and provide outdoor air during  
cooling and reduce compressor operation.  
Manual outside air damper includes hood and filter rack with  
adjustable damper blade for up to 25% outdoor air.  
Electric heaters provide additional heat in the unit when required.  
Each package has a heater module that slides into the controls  
Lifting kit, including 4 metal brackets that are available to assist in  
lifting this product onto a roof application.  
Electric Heaters  
USED WITH SIZES  
CATALOG  
ORDERING NO.  
NOMINAL  
CAPACITY (kW)  
FUSES  
024  
030  
036  
042  
048  
060  
ELECTRIC HEATERS (208/230 — SINGLE PHASE — 60 Hz)  
CPHEATER052A00  
CPHEATER069A00  
CPHEATER065A00  
CPHEATER051A00  
CPHEATER053A00  
CPHEATER054A00  
5.0  
7.5  
0
0
0
4
6
6
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
10.0  
15.0  
20.0  
20.0  
X
ELECTRIC HEATERS (208/230 — THREE PHASE — 60 Hz)  
CPHEATER055A00  
CPHEATER056A00  
CPHEATER057A00  
CPHEATER059A00  
5.0  
0
0
0
6
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
10.0  
15.0  
20.0  
NOTE: Electric heaters are rated at 240v. Refer to Multiplication Factors table for other voltages.  
X = Approved combinations.  
Minimum Airflow for Reliable Electric Heater Operation (CFM)  
UNIT SIZE  
AIRFLOW  
024  
750  
030  
1000  
036  
1250  
042  
1400  
048  
1500  
060  
1800  
6
ECONOMIZER  
COIL  
FILTER ACCESS DOOR  
(HORIZONTAL  
APPLICATION ONLY.)  
DO NOT REMOVE  
FROM DOWNFLOW  
DISCHARGE.  
FILTER  
REPLACEMENT  
PANEL  
ECONOMIZER  
HOLE FOR  
ECONOMIZER  
WIRING HARDNESS  
17 13/32  
11 13/32”  
RAINHOOD  
DOOR  
LATCH ANGLE  
CAULK BOTTOM CORNER  
OF ECONOMIZER  
ON EACH SIDE  
16 1/4”  
SIDE VIEW  
HINGED FILTER  
ACCESS DOOR  
INSTALL  
FILTER ACCESS  
DOOR STICKER  
FI LTER  
ALUMINUM  
FILTER  
COIL  
ECONOMIZER  
BASE  
FLANGE  
ON BASE  
AIL  
DET  
MANUAL OUTSIDE AIR DAMPER  
FILTER RACK  
BEND FLANGE AT 90˚ -SCREW TO  
DIVIDER WITH 1-IN. SCREW  
REPLACEMENT  
PANEL  
MANUAL OUTSIDE  
AIR HOOD  
TOP FILTER RACK  
EV APORATOR  
COIL  
DAMPER  
BLADE  
BOTTOM FILTER  
RACK  
A05239  
7
UNIT DIMENSIONS -- 50XP024--036  
A08452  
8
UNIT DIMENSIONS -- 50XP042--060  
A08453  
9
ACCESSORY ROOF CURB - 50XP024  
                                                                          
-060  
HVACunit  
base  
HVAC unit  
base  
Gask eting  
inner flange*  
Screw  
(NOTE A)  
Screw  
(NOTE A)  
Gasketing  
inner flange*  
*Gasketing  
outer flange  
*Gasketing  
outer flange  
Wood nailer*  
Wood nailer*  
Flashing field  
supplied  
Flashing field  
supplied  
Roofcurb*  
Roofcurb*  
Insulation(field  
supplied)  
Insulation(field  
supplied)  
Roofing material  
field supplied  
Roofing material  
field supplied  
Duct work  
field supplied  
Duct work  
field supplied  
Cant strip  
field supplied  
Cant strip  
field supplied  
Roof  
Roof  
*Provided with roofcurb  
*Provided with roofcurb  
Roof Curb for Small Cabinet  
Roof Curb for  
Large Cabinet  
Note A:When unit mounting screw is use,d  
retainer bracket must also be used.  
Note A:When unit mounting screw is use,d  
retainer bracket must also be used.  
Supply opening  
(B x C)  
BTyp.  
D
CTyp.  
445/16"  
(1126 mm)  
R/A  
S/A  
A
Gasket around  
duct  
Short  
Support  
Insulated  
deck pan  
Gasket around  
outer edge  
Insulated  
deck pan  
Long  
Support  
Return opening  
(B X C)  
C00076  
A
B
C
D
UNIT SIZE  
ORDERING NUMBER  
IN. (MM)  
IN. (MM)  
11 (279)  
IN. (MM)  
IN. (MM)  
CPRFCURB006A00  
CPRFCURB007A00  
CPRFCURB008A00  
CPRFCURB009A00  
8 (203)  
14 (356)  
8 (203)  
16--1/2 (419)  
16--1/2 (419)  
17--3/8 (441)  
17--3/8 (441)  
28--3/4 (730)  
28--3/4 (730)  
40--1/4 (1022)  
40--1/4 (1022)  
50XP024 -036  
50XP042 -060  
11 (279)  
16--3/16 (411)  
16--3/16 (411)  
14 (356)  
NOTES:  
1. Roof curb must be set up for unit being installed.  
2. Seal strip must be applied, as required, to unit being installed.  
3. Roof curb is made of 16--gauge steel.  
4. Attach ductwork to curb (flanges of duct rest on curb).  
5. Insulated panels: 1--in. (25.4 mm) thick fiberglass 1 lb. density.  
6. When unit mounting screw is used (see Note A), a retainer bracket must be used as well. This bracket must also be used when required by code for hurricane or seismic  
conditions. This bracket is available through Micrometl.  
10  
50XP UNIT SUGGESTED RIGGING  
1
2
(914 mm)  
DETAIL A  
3
4
A07216  
A08005  
SMALL CABINET  
LARGE CABINET  
Unit*  
024  
lb  
024  
kg  
030  
lb  
030  
kg  
036  
lb  
036  
kg  
042  
lb  
042  
kg  
048  
lb  
048  
kg  
060  
060  
kg  
Unit*  
lb  
Rigging  
Weight  
Rigging  
Weight  
345  
156  
349  
158  
367  
166  
425  
193  
459  
208  
504  
229  
NOTE: See dimensional drawing for corner weight distribution. Corner weights shown on drawing are based on unit---only weights and do not include pack-  
aging.  
SELECTION PROCEDURE (WITH EXAMPLE)  
1. Determine cooling and heating requirements at  
design conditions:  
4. Determine fan speed and power requirements at  
design conditions.  
Given:  
Before entering the air delivery tables, calculate the total static  
pressure required. From the given example, the Filter Pressure  
Drop Table, and the Accessory Electric Heat Pressure Drop table,  
find:  
Required Cooling Capacity (TC) . . . . . . . . . . 34,500 Btuh  
Sensible Heat Capacity (SHC) . . . . . . . . . . . . 26,000 Btuh  
Required Heating Capacity . . . . . . . . . . . . . . . 15,000 Btuh  
Condenser Entering Air Temperature . . . . . . . . 95°F(35°C)  
Indoor--Air Temperature . . . . . . . . . . . . . 80°F (26°C) edb  
67°F (19°C) ewb  
Evaporator Air Quantity . . . . . . . . . . . . . . . . . . 1200 CFM  
External Static Pressure . . . . . . . . . . . . . . . . . 0.20 IN. W.C.  
Electrical Characteristics . . . . . . . . . . . . . . . . . . . 230--1--60  
External Static Pressure  
Filter  
0.200 IN. W.C.  
0.130 IN. W.C.  
0.032 IN. W.C.  
0.362 IN. W.C.  
Wet Coil Pressure Drop  
Total Static Pressure  
Enter the table for Dry Coil Air Delivery—At 0.362 IN. W.C. ESP  
(external static pressure) and NOM speed pin selection, the motor  
will deliver 1235 cfm.  
2. Select unit based on required cooling capacity.  
5. Select unit that corresponds to power source  
available.  
The Electrical Data Table shows that the unit is designed to operate  
at 208--1--60.  
Enter Net Cooling Capacities table at condenser entering  
temperature of 95°F (35°C). The 036 unit at 1225 CFM and 67°F  
(19°C) ewb (entering wet bulb) will provide a total capacity of  
36,500 Btuh and a SHC of 27,600 Btuh. Calculate SHC correction,  
if required, using Note 4 under Cooling Capacities tables.  
3. Select electric heat.  
The required heating capacity is 15,000 Btuh.  
Determine additional electric heat capacity in kW.  
15,000 Btuh  
= 4.4kW of heat required  
3,414 Btuh/kW  
Enter the Electric Heater Packages table for 208/240, single--phase,  
036 unit. The 5 kW heater at 240v most closely satisfies the  
heating required. To calculate kW at the 208v, multiply the heater  
kW by multiplication factor 0.75 found in the Wattage  
Multiplication Factors table.  
5 kW x 0.75 = 3.75 kW  
3.75 kW x 3414 = 12,802.50 Btuh  
11  
12  
13  
14  
15  
PERFORMANCE DATA (CONT)  
Economizer 1--in. Filter Pressure Drop (IN. W.C.)  
UNIT50XP  
024 -036  
042 -060  
PRESSURE DROP  
0.20  
0.25  
Multiplication Factors  
HEATER kW RATING  
VOLTAGE DISTRIBUTION V/3/60  
MULTIPLICATION FACTOR  
200  
208  
230  
240  
0.69  
0.75  
0.92  
1.00  
240  
Filter Pressure Drop Table (IN. W.C.)  
CFM  
900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300  
FILTER SIZE  
in. (mm)  
500  
600  
700  
800  
20X20X1  
0.05 0.07 0.08 0.10 0.12 0.13 0.14 0.15  
(508X508X25)  
20X24X1  
(508X610x25)  
24X30X1  
(610X762x25)  
0.09 0.10 0.11 0.13 0.14 0.15 0.16  
0.07 0.08 0.09 0.10 0.11 0.12 0.13 0.14 0.15 0.16 0.17 0.18  
Electric Heat Pressure Drop Tables (IN. W.C.)  
Small Cabinet: 024--036  
CFM  
STATIC  
500  
0.00  
0.00  
0.00  
0.00  
600  
0.00  
0.00  
0.00  
0.00  
700  
0.00  
0.00  
0.00  
0.00  
800  
0.00  
0.00  
0.00  
0.02  
900  
0.00  
0.00  
0.00  
0.04  
1000  
0.00  
0.00  
0.02  
0.06  
1100  
0.00  
0.02  
0.04  
0.08  
1200  
0.00  
0.03  
0.06  
0.10  
1300  
0.02  
0.05  
0.07  
0.12  
1400  
0.04  
0.07  
0.09  
0.14  
1500  
0.06  
0.08  
0.10  
0.16  
1600  
0.07  
0.09  
0.11  
0.18  
5 kW  
7.5 kW  
10 kW  
15 kW  
Large Cabinet: 042--060  
CFM  
1800  
0.05  
0.06  
0.06  
0.08  
0.09  
STATIC  
1100  
0.00  
0.00  
0.00  
0.00  
0.02  
1200  
0.00  
0.00  
0.00  
0.02  
0.03  
1300  
0.00  
0.01  
0.01  
0.03  
0.04  
1400  
1500  
0.02  
0.03  
0.03  
0.05  
0.06  
1600  
0.03  
0.04  
0.04  
0.06  
0.07  
1700  
1900  
2000  
2100  
0.08  
0.09  
0.09  
0.11  
0.12  
2200  
2300  
0.10  
0.11  
0.11  
0.13  
0.14  
2400  
2500  
5 kW  
7.5 kW  
10 kW  
15 kW  
20 kW  
0.01  
0.02  
0.02  
0.04  
0.05  
0.04  
0.05  
0.05  
0.07  
0.08  
0.06  
0.07  
0.07  
0.09  
0.10  
0.07  
0.08  
0.08  
0.10  
0.11  
0.09  
0.10  
0.10  
0.12  
0.13  
0.11  
0.12  
0.12  
0.14  
0.15  
0.12  
0.13  
0.13  
0.15  
0.16  
ECM Dry Coil Airflow--Small Cabinet  
CFM ADJUST PIN SELECT  
LO PIN  
NOM PIN  
0.4 -0.69  
HI PIN  
UNIT  
EXTERNAL STATIC  
PRESSURE RANGE  
COOLING  
COOLING DEHUMIDIFY  
COOLING  
COOLING DEHUMIDIFY  
COOLING  
COOLING DEHUMIDIFY  
SIZE  
024  
030  
036  
0.0 -0.39  
0.4 -0.69  
0.7 -1.0  
0.0 -0.39  
0.7 -1.0  
0.0 -0.39  
0.4 -0.69  
0.7 -1.0  
800  
715  
1010  
890  
1110  
990  
725  
670  
920  
845  
1025  
960  
--  
--  
825  
795  
970  
910  
885  
715  
1105  
890  
1235  
990  
805  
695  
1030  
865  
1175  
975  
730  
645  
930  
825  
1115  
940  
990  
795  
1255  
1010  
1400  
1125  
930  
775  
1160  
980  
1355  
1110  
855  
745  
1050  
925  
1280  
1085  
ECM Dry Coil Airflow--Large Cabinet  
CFM ADJUST PIN SELECT  
LO PIN  
NOM PIN  
NOM PIN  
UNIT SIZE  
EXTERNAL STATIC PRESSURE RANGE  
COOLING  
0.1 -1.0  
1100  
980  
1260  
1120  
1575  
1400  
0.1 -1.0  
1225  
980  
1400  
1120  
1750  
1400  
0.1 -1.0  
1410  
1125  
1610  
1290  
2010  
1610  
042  
COOLING DEHUMIDIFY  
COOLING  
COOLING DEHUMIDIFY  
COOLING  
048  
060  
COOLING DEHUMIDIFY  
Wet Coil Pressure Drop (IN. W.C.)  
Standard CFM (S.C.F.M)  
Unit  
Size  
024  
030  
036  
042  
048  
060  
600  
0.005  
700  
0.007  
0.007  
800  
0.010  
0.010  
900  
1000  
0.015  
0.015  
0.023  
0.014  
1100  
1200  
1300  
1400  
1500  
1600  
1700  
1800  
1900  
2000  
2100  
0.012  
0.012  
0.019  
0.018  
0.027  
0.017  
0.021  
0.032  
0.020  
0.027  
0.024  
0.037  
0.024  
0.032  
0.042  
0.027  
0.036  
0.047  
0.031  
0.041  
0.029  
0.035  
0.046  
0.032  
0.039  
0.052  
0.036  
0.043  
0.057  
0.040  
0.063  
0.045  
0.068  
0.049  
0.053  
16  
TYPICAL PIPING AND WIRING  
ROOF-MOUNTING  
CURB  
ROOF  
RETURN-AIR  
FLEXIBLE DUCT  
SUPPLY-AIR  
FLEXIBLE DUCT  
CEILING  
CONCENTRIC DIFFUSER BOX  
(FIELD-SUPPLIED)  
C00023  
INDOOR  
THERMOSTAT  
RETURN  
AIR  
FROM  
POWER  
SOURCE  
TOP COVER  
DISCONNECT  
PER NEC*  
*NEC - NATIONAL ELECTRICAL CODE  
C00063  
17  
APPLICATION DATA  
Maximum cooling airflow — To minimize the possibility of  
condensate blow--off from the evaporator, airflow through the units  
should not exceed 450 cfm per ton.  
Condensate trap — A 2--in. (51 mm) condensate trap must be  
field supplied.  
1” (25 mm) MIN  
.
Minimum cooling airflow — Minimum cooling airflow is 350  
cfm per ton for standard cooling modes. Airflow can be lower in  
certain modes when humidity removal is an issue.  
TRAP  
OUTLET  
2” (51 mm) MIN.  
Minimum cooling operating outdoor air temperature — All  
standard units have a minimum outdoor operating temperature of  
55_F (13_C). With accessory low ambient temperature kit, units  
can operate at temperatures down to 0_F (--17_C).  
A08001  
Ductwork — Secure downflow discharge ductwork to roof curb.  
For horizontal discharge applications, attach ductwork to unit with  
flanges.  
Maximum cooling operating outdoor air temperature —  
Maximum outdoor operating air temperature is 125_F (52_C).  
To convert a unit to downflow discharge — Units are equipped  
with factory--installed inserts in the downflow openings. Removal  
of the inserts is similar to removing an electrical knock--out. Leave  
on duct covers to seal the horizontal discharge openings in the unit.  
Units installed in horizontal discharge orientation do not require  
duct covers.  
18  
ELECTRICAL DATA  
ELECTRIC HEAT  
POWER SUPPLY  
VOLTAGE  
COMPRESSOR  
OFM  
FLA  
IFM  
FLA  
NOMINAL  
V --- P H --- H Z  
RANGE  
MAX  
FUSE or  
CKT BKR  
30/30  
30/35  
40/45  
60/60  
30/30  
30/35  
40/45  
60/60  
-
UNIT  
NOMINAL  
FLA  
MCA  
MOCP  
KW  
MIN  
MAX  
RLA  
LRA  
-/-  
3.8/5  
5.4/7.2  
7.5/10  
-/-  
3.8/5  
5.4/7.2  
7.5/10  
11.3/15  
-/-  
-/-  
22.0/22.0  
27.9/31.4  
37.9/42.9  
50.5/57.5  
23.6/23.6  
27.9/31.4  
37.9/42.9  
50.5/57.5  
73.1/83.5  
26.9/26.9  
31.1/34.5  
41.0/46.0  
53.6/60.6  
76.2/86.6  
23.0/23.0  
23.0/23.5  
34.6/38.6  
47.6/53.6  
30.9/30.9  
31.1/34.5  
41.0/46.0  
53.6/60.6  
76.2/86.6  
---  
18.1/20.8  
26/30  
36.1/41.7  
-/-  
18.1/20.8  
26/30  
36.1/41.7  
54.2/62.5  
-/-  
---  
50XP-024  
50XP-030  
208/230-1-60  
208/230-1-60  
187  
253  
13.5  
61.0  
0.8  
0.8  
4.3  
4.3  
---  
---  
---  
---  
187  
253  
15.9  
73.0  
---  
---  
80/90  
35/35  
35/35  
45/50  
---  
---  
3.8/5  
5.4/7.2  
7.5/10  
11.3/15  
-/-  
5
10  
18.1/20.8  
26/30  
36.1/41.7  
54.2/62.5  
-/-  
10.4/12  
20.8/24.1  
31.3/36.1  
-/-  
---  
208/230-1-60  
208/230-3-60  
187  
187  
253  
253  
16.9  
12.2  
83.0  
77.0  
0.8  
0.8  
6.8  
6.8  
---  
60/70  
50XP-036  
---  
80/90  
30/30  
30/30  
35/35  
50/60  
45/45  
45/45  
45/50  
---  
---  
---  
---  
15  
-/-  
---  
---  
3.8/5  
5.4/7.2  
7.5/10  
11.3/15  
15/20  
-/-  
3.8/5  
7.5/10  
11.3/15  
15/20  
-/-  
18.1/20.8  
26/30  
36.1/41.7  
54.2/62.5  
72.2/83.3  
-/-  
10.4/12  
20.8/24.1  
31.3/36.1  
41.6/48  
-/-  
---  
---  
208/230-1-60  
208/230-3-60  
208/230-1-60  
208/230-3-60  
208/230-1-60  
208/230-3-60  
187  
187  
187  
187  
187  
187  
253  
253  
253  
253  
253  
253  
22.4  
15.4  
21.3  
14.7  
27.0  
19.2  
105.0  
88.0  
0.8  
0.8  
1.6  
1.6  
1.6  
1.6  
6.8  
6.8  
6.8  
6.8  
9.1  
9.1  
60/70  
---  
---  
80/90  
100/125  
50XP-042  
98.8/112.7  
27.0/27.0  
27.0/27.0  
34.6/38.6  
47.6/53.6  
60.5/68.5  
33.9/33.9  
33.9/34.5  
41.0/46.0  
53.6/60.6  
76.2/86.6  
98.8/112.7  
26.7/26.7  
26.7/26.7  
34.6/38.6  
47.6/53.6  
60.5/68.5  
44.3/44.3  
44.3/44.3  
44.3/48.9  
56.5/63.5  
79.1/89.5  
101.6/115.5  
33.0/33.0  
33.0/33.0  
37.4/41.4  
50.5/56.5  
63.3/71.3  
35/35  
35/35  
35/35  
50/60  
---  
45/45  
45/45  
45/50  
---  
---  
---  
35/35  
35/35  
35/35  
50/60  
---  
60/60  
60/60  
60/60  
---  
---  
---  
---  
---  
---  
---  
70/70  
---  
3.8/5  
5.4/7.2  
7.5/10  
11.3/15  
15/20  
-/-  
3.8/5  
7.5/10  
11.3/15  
15/20  
-/-  
18.1/20.8  
26/30  
36.1/41.7  
54.2/62.5  
72.2/83.3  
-/-  
10.4/12  
20.8/24.1  
31.3/36.1  
41.6/48  
-/-  
---  
---  
109.0  
91.0  
60/70  
80/90  
100/125  
50XP-048  
---  
---  
---  
---  
70/70  
---  
---  
---  
3.8/5  
5.4/7.2  
7.5/10  
11.3/15  
15/20  
-/-  
3.8/5  
7.5/10  
11.3/15  
15/20  
18.1/20.8  
26/30  
36.1/41.7  
54.2/62.5  
72.2/83.3  
-/-  
10.4/12  
20.8/24.1  
31.3/36.1  
41.6/48  
145.0  
137.0  
60/70  
80/90  
100/125  
---  
50XP-060  
40/40  
40/40  
40/45  
60/60  
---  
---  
---  
---  
70/80  
460-3-60.  
452 v  
464 v  
455 v  
464 455  
452  
1371  
*Heater capacity (kW) based on heater voltage of 208v, 240v, &  
480v. If power distribution voltage to unit varies from rated  
heater voltage, heater kW will vary accordingly.  
457  
452  
457  
5
7
2
464  
457  
457  
455  
7
7
457  
1.53  
19  
TYPICAL WIRING SCHEMATIC 208/230--1--60  
A08460  
20  
TYPICAL WIRING SCHEMATIC 208/230--3--60  
A08461  
21  
CONTROLS  
Operating sequence  
Cooling — When the system thermostat calls for cooling, 24 V is  
supplied to the “Y” and “G” terminals of the thermostat. This  
completes the circuit to the contactor coil (C) and indoor fan  
board. The normally open contacts of C close and complete the  
circuit to compressor motor (COMP) and to outdoor (condenser)  
fan motor (OFM). Both motors start instantly. The IFM starts  
according to the selection pin set--up on the Easy Select Board.  
On the loss of the thermostat call for cooling, 24 V is removed  
from both the “Y” and “G” terminals (provided the fan switch is in  
the “AUTO” position) de--energizing the compressor contactor and  
opening the contacts supplying power to compressor/OFM. After a  
preselected delay, the IFM shuts off. If the thermostat fan selector  
switch is in the “ON” position, the IFM will run continuously at  
speed selected on Easy Select Board  
Heating — If accessory electric heaters are installed, on a call for  
heat, circuit R--W is made through the thermostat contacts. Circuit  
R--G is made which energizes the IFM. If the heaters are staged,  
then the thermostat closes a second set of contacts (W2) when  
second stage is required. When thermostat is satisfied, contacts  
open, deenergizing the heater relay. After a preselected delay, the  
IFM shuts off. If the thermostat fan selector switch is in the “ON”  
position, the IFM will run continuously at speed selected on Easy  
Select Board.  
NOTE: On units with a Time Guard II device: Once the  
compressor has started and then stopped, it cannot be restarted  
again until 5 minutes have elapsed.  
The indoor blower operation with a call for fan operation (G) in  
cooling mode will perform by the on/off delay profile selected at  
start up on the Easy Select Board.  
®
22  
C. Fans:  
1. The evaporator fan shall be direct--drive variable speed  
GUIDE SPECIFICATIONS  
Packaged Electric Cooling Unit  
Constant Volume Application  
HVAC Guide Specifications  
motor and control, as shown on equipment drawings.  
2. Fan wheel shall be made from steel, be double--inlet type  
with forward curved blades with corrosion resistant finish.  
Fan wheel shall be dynamically balanced.  
Size Range:  
Model Number: 50XP  
Part 1 — General  
2 to 5 Tons, Nominal Cooling  
3. Condenser fan shall be direct drive propeller type with alu-  
minum blades riveted to corrosion resistant steel spiders, be  
dynamically balanced, and discharge air vertically.  
D. Compressor:  
SYSTEM DESCRIPTION  
1. Fully hermetic compressors with factory--installed vibration  
isolation.  
2. Scroll compressors shall be standard on all units.  
Outdoor rooftop mounted or ground mounted, electric cooling  
unit utilizing a hermetic compressor for cooling duty and  
optional electric heating. Unit shall discharge supply air  
vertically or horizontally as shown on contract drawings.  
Condenser fan/coil section shall have a draw--thru design with  
vertical discharge for minimum sound levels.  
E. Coils:  
Evaporator and condenser coils shall have aluminum plate fins  
mechanically bonded to seamless copper tubes with all joints  
brazed. (Copper/copper and vinyl--coated construction  
available as option). Tube sheet openings shall be belled to  
prevent tube wear.  
QUALITY ASSURANCE  
A. Unit shall be rated in accordance with ARI Standards  
210/240 and 270.  
B. Unit shall be designed in accordance with UL Standard  
1995.  
C. Unit shall be manufactured in a facility registered to ISO  
9001 manufacturing quality standard.  
F. Refrigerant Components:  
Refrigerant expansion device shall be of the TXV  
(thermostatic expansion valve) type.  
G. Filters:  
D. Unit shall be UL listed and c--UL certified as a total  
package for safety requirements.  
E. Roof curb shall be designed to conform to NRCA  
Standards.  
Filter section shall consist of field--installed, throwaway, 1--in.  
(25 mm) thick fiberglass filters of commercially available  
sizes.  
H. Controls and Safeties:  
F. Insulation and adhesives shall meet NFPA 90A  
requirements for flame spread and smoke generation.  
1. Unit controls shall be complete with a self--contained low  
voltage control circuit.  
G. Cabinet insulation shall meet ASHRAE Standard 62P.  
DELIVERY, STORAGE AND HANDLING  
2. Units shall incorporate an internal compressor protector that  
provides reset capability.  
Unit shall be stored and handled per manufacturer’s  
recommendations.  
3. Unit shall provide High and Low/Loss--of--Charge Pressure  
Safety Protection.  
Part 2 — Products  
EQUIPMENT  
A. General:  
I. Operating Characteristics:  
1. Unit shall be capable of starting and running at 125_F  
(51_C) ambient outdoor temperature,exceeding maximum  
load criteria of ARI Standard 210.  
Factory--assembled, single--piece, cooling unit. Contained  
within the enclosure shall be all factory wiring, piping,  
controls, refrigerant charge with R--410A refrigerant, and  
special features required prior to field start--up.  
2. Compressor with standard controls shall be capable of op-  
eration down to 55_F (13_C) ambient outdoor temperature.  
3. Indoor Fan on/off delay profile is selected (for cooling) on  
the Easy Select board.  
B. Unit Cabinet:  
J. Electrical Requirements:  
1. Unit cabinet shall be constructed of phosphated,  
zinc--coated, pre--painted steel capable of with--standing 500  
hours in salt spray.  
All unit power wiring shall enter the unit cabinet at a single  
location.  
2. Normal service shall be through a single removable cabinet  
panel.  
K. Motors:  
1. Compressor motors shall be of the refrigerant--cooled type  
with line--break thermal and current overload protection.  
3. The unit shall be constructed on a rust proof unit base that  
has an externally trapped, integrated sloped drain pan.  
2. All fan motors shall have permanently lubricated bearings,  
and inherent, automatic reset, thermal overload protection.  
4. Evaporator fan compartment top surface shall be insulated  
with a minimum 1/2--in. (13 mm) thick, flexible fiberglass  
insulation, coated on the air side and retained by adhesive  
and mechanical means. The evaporator wall sections will be  
insulated with a minimum semi--rigid foil--faced board ca-  
pable of being wiped clean. Aluminum foil--faced fiberglass  
insulation shall be used in the entire indoor air cavity  
section.  
3. Condenser fan motor shall be totally enclosed.  
L. Grille:  
1. Louvered Grille:  
Louvered grille shall be standard on all units.  
5. Unit shall have a field--supplied condensate trap.  
23  
6. Low Ambient Package:  
GUIDE SPECIFICATIONS (CONT)  
Shall consist of a solid--state control and condenser coil  
temperature sensor for controlling condenser--fan motor op-  
eration, which shall allow unit to operate down to 0_F  
(--18_C) outdoor ambient temperature when properly  
installed.  
M. Special Features:  
1. Coil Options:  
Shall include factory--installed optional tin--plated indoor,  
copper/copper and vinyl--coated refrigerant coils.  
2. Economizer:  
7. Filter Rack Kit:  
Shall provide filter mounting for downflow or horizontal  
applications.  
a. Economizer controls capable of providing free cooling  
using outside air.  
8. Square--To--Round Duct Transitions (024--048):  
Shall have the ability to convert the supply and return open-  
ings from rectangular to round. (024--048 only)  
b. Equipped with low leakage dampers not to exceed 3%  
leakage, at 1.0 IN. W.C. pressure differential.  
c. Spring return motor shuts off outdoor damper on power  
failure.  
3. Flat Roof Curb:  
9. Compressor Protection:  
Solid--state control shall protect compressor by preventing  
“short cycling.“  
Curbs shall have seal strip and a wood nailer for flashing  
and shall be installed per manufacturer’s instructions.  
4. Manual Outdoor Air Damper:  
10. Crankcase Heater:  
Shall provide anti--floodback protection for low--load cool-  
ing applications.  
Package shall consist of damper, birdscreen, and rainhood  
which can be preset to admit outdoor air for year--round  
ventilation.  
11. Electric Heaters:  
a. Electric heater shall be availabel as a field--installed  
option.  
5. Thermostat:  
b. Heater elements shall be open wire type, adequately  
supported and insulated with ceramic bushings.  
To provide for one--stage heating and cooling in addition  
manual or automatic changeover and indoor fan control.  
c. Electric heater packages must provide single point  
power connection capability.  
12. Compressor Start Kit (single phase units only):  
Shall provide additional starting torque for single--phase  
compressors.  
Catalog No: 50XP---05PD  
Copyright 2008 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231  
Printed in U.S.A.  
Edition Date: 09/08  
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.  
Replaces: 50XP---4PD  
24  

Carrier 09DK054 094 User Manual
Cornelius Hotel Dispenser CHD30 User Manual
Danby DAC8010E User Manual
Energizer Battery Charger User Manual
Epson Stylus CX9475Fax User Manual
Friedrich Air Conditioner CP24N30 User Manual
GE General Electric Air Conditioner AHM24 User Manual
Goodman Mfg CKLB24 1E User Manual
Graco MetroLite 1761213 User Manual
Haier AU072ACAAA User Manual