Bryant DURAPAC PLUS 581B User Manual

installation, start-up and  
service instructions  
581B  
DuraPac Plus Series  
Sizes 036-072  
3 to 6 Tons  
SINGLE PACKAGE ROOFTOP  
GAS HEATING/ELECTRIC COOLING UNITS  
Cancels: II 581B-36-6  
II 581B-36-7  
10/1/05  
WARNING: Before performing service or mainte-  
nance operations on unit, turn off main power switch to  
unit. Electrical shock could cause personal injury.  
CONTENTS  
Page  
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1  
INSTALLATION  
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-33  
I. Step 1 — Provide Unit Support. . . . . . . . . . . . . . . . . 1  
II. Step 2 — Field Fabricate Ductwork . . . . . . . . . . . . . 2  
Unit is shipped in the vertical configuration. To convert to  
horizontal application, remove side duct opening covers.  
Using the same screws, install covers on vertical duct open-  
ings with the insulation-side down. Seals around duct open-  
ings must be tight. See Fig. 1.  
III. Step 3 — Determine Location of Drain Line  
and External Trap. . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
IV. Step 4 — Rig and Place Unit. . . . . . . . . . . . . . . . . . . 4  
V. Step 5 — Install Flue Hood . . . . . . . . . . . . . . . . . . . . 4  
VI. Step 6 — Install Gas Piping . . . . . . . . . . . . . . . . . . . 4  
VII. Step 7 — Make Electrical Connections . . . . . . . . . . 9  
VIII. Step 8 — Adjust Factory-Installed Options. . . . . . 13  
IX. Step 9 — Adjust Evaporator-Fan Speed . . . . . . . . 22  
I. STEP 1 — PROVIDE UNIT SUPPORT  
A. Roof Curb  
Assemble and install accessory roof curb in accordance with  
instructions shipped with curb. See Fig. 2. Install insulation,  
cant strips, roofing felt, and counter flashing as shown. Duct-  
work must be attached to curb. If gas is to be routed through  
the curb, attach the accessory thru-the-curb service connec-  
tion plate to the roof curb in accordance with the accessory  
installation instructions. Connection plate must be installed  
before unit is set in roof curb.  
PRE-START-UP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34  
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34-37  
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38-44  
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . .45-49  
INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50  
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1  
IMPORTANT: The gasketing of the unit to the roof curb is crit-  
ical for a watertight seal. Install gasket supplied with the roof  
curb as shown in Fig. 2. Improperly applied gasket can also  
result in air or water leaks and poor unit performance.  
SAFETY CONSIDERATIONS  
Installation and servicing of air-conditioning equipment can  
be hazardous due to system pressure and electrical compo-  
nents. Only trained and qualified service personnel should  
install, repair, or service air-conditioning equipment.  
Curb should be level. This is necessary for unit drain to func-  
tion properly. Unit leveling tolerances are shown in Fig. 3.  
Refer to Accessory Roof Curb Installation Instructions for  
additional information as required.  
Untrained personnel can perform basic maintenance func-  
tions of cleaning coils and filters and replacing filters. All  
other operations should be performed by trained service per-  
sonnel. When working on air-conditioning equipment,  
observe precautions in the literature, tags and labels  
attached to the unit, and other safety precautions that may  
apply.  
B. Slab Mount (Horizontal Units Only)  
Provide a level concrete slab that extends a minimum of 6 in.  
beyond unit cabinet. Install a gravel apron in front of con-  
denser coil air inlet to prevent grass and foliage from  
obstructing airflow.  
NOTE: Horizontal units may be installed on a roof curb if  
required.  
Follow all safety codes. Wear safety glasses and work gloves.  
Use quenching cloth for unbrazing operations. Have fire  
extinguishers available for all brazing operations.  
C. Alternate Unit Support  
A non-combustible sleeper rail can be used in the unit curb  
support area. If sleeper rails cannot be used, support the long  
sides of the unit with a minimum of 3 equally spaced 4-in. x  
4-in. pads on each side.  
CAUTION: Ensure voltage listed on unit data plate  
agrees with electrical supply provided for the unit.  
WARNING: Disconnect gas piping from unit when  
leak testing at pressure greater than 1/2 psig. Pressures  
1
greater than /2 psig will cause gas valve damage result-  
ing in hazardous condition. If gas valve is subjected to  
1
pressure greater than /2 psig, it must be replaced before  
use. When pressure testing field-supplied gas piping at  
1
pressures of /2 psig or less, a unit connected to such  
piping must be isolated by manually closing the gas  
valve(s).  
ROOF CURB  
ACCESSORY  
D ALT  
DRAIN  
HOLE  
A
UNIT SIZE  
CONNECTOR  
PKG. ACCY.  
ACCESSORY  
PWR  
B
C
GAS  
POWER  
CONTROL  
1-2″  
CRRFCURB001A01  
CRRFCURB002A01  
CRBTMPWR001A01  
CRBTMPWR002A01  
3/4[19] NPT  
11/4[31.7]  
3/4[19] NPT  
3/4″  
1/2″  
[356]  
581B036-072  
[19] NPT  
[12.7]  
2-0″  
1-911  
/
1-4″  
13/4″  
1/2″  
[610]  
1/2″  
[5511]6 [406]  
[44.5]  
[12.7]  
CRBTMPWR003A01  
CRBTMPWR004A01  
1/2″  
[12.7] NPT  
3/4″  
[12.7]  
NOTES:  
11/4[31.7]  
1. Roof curb accessory is shipped disassembled.  
2. Insulated panels.  
[19] NPT  
3. Dimensions in [ ] are in millimeters.  
4. Roof curb: galvanized steel.  
5. Attach ductwork to curb (flanges of duct rest on  
curb).  
6. Service clearance: 4 ft on each side.  
7.  
Direction of airflow.  
8. Connector packages CRBTMPWR001A01 and  
002A01 are for thru-the-curb type gas. Packages  
CRBTMPWR003A01 and 004A01 are for thru-the-  
bottom type gas connections.  
Fig. 2 — Roof Curb Details  
3—  
A. Positioning  
Maintain clearance around and above unit to provide mini-  
mum distance from combustible materials, proper airflow,  
and service access. See Fig. 7.  
Do not install unit in an indoor location. Do not locate unit  
air inlets near exhaust vents or other sources of contami-  
nated air.  
Be sure that unit is installed so that snow will not block the  
combustion intake or flue outlet.  
MAXIMUM ALLOWABLE  
DIFFERENCE (in.)  
Unit may be installed directly on wood flooring or on Class  
A, B, or C roof-covering material when roof curb is used.  
A-B  
0.5  
B-C  
1.0  
A-C  
1.0  
Although unit is weatherproof, guard against water from  
higher level runoff and overhangs.  
Fig. 3 — Unit Leveling Tolerances  
Position unit on roof curb so that the following clearances are  
1
maintained: /4 in. clearance between the roof curb and the  
base rail inside the front and rear, 0.0 in. clearance between  
the roof curb and the base rail inside on the duct end of the  
unit. This will result in the distance between the roof curb  
and the base rail inside on the condenser end of the unit  
being approximately equal to Fig. 2, section C-C.  
Locate mechanical draft system flue assembly at least 48 in.  
from an adjacent building or combustible material. Units  
having accessory flue discharge deflector require only 18 in.  
clearance. When unit is located adjacent to public walkways,  
flue assembly must be at least 7 ft above grade.  
Flue gas can deteriorate building materials. Orient unit so  
that flue gas will not affect building materials.  
HORIZONTAL  
DRAIN PLUG  
DRAIN PLUG  
Adequate combustion and ventilation air space must be pro-  
vided for proper operation of this equipment. Be sure that  
installation complies with all local codes and Section 5.3, Air  
for Combustion and Ventilation per NFGC (National Fuel Gas  
Code), ANSI (American National Standards Institute) Z223.1-  
latest year and addendum Z223.1A-latest year. In Canada,  
installation must be in accordance with the CAN1.B149.1 and  
CAN1.B149.2 installation codes for gas burning appliances.  
NOTE: Drain plug is shown in factory-installed position.  
Fig. 4 — Condensate Drain Pan  
Flue vent discharge must have a minimum horizontal clear-  
ance of 4 ft from electric and gas meters, gas regulators, and  
gas relief equipment.  
After unit is in position, remove shipping materials and rig-  
ging skids.  
V. STEP 5 — INSTALL FLUE HOOD  
Flue hood is shipped screwed to the burner compartment  
access panel. Remove from shipping location and, using  
screws provided, install flue hood in location shown in Fig. 7  
and 8.  
For units being installed in California Air Quality Manage-  
ment Districts which require NOx emissions of 40 nanograms/  
joule or less, a low NOx unit must be installed.  
NOTE: Trap should be deep enough to offset maximum unit static dif-  
ference. A 4-in. trap is recommended.  
NOTE: Low NOx units are available for 3 to 5 ton units.  
Fig. 5 — Condensate Drain Piping Details  
VI. STEP 6 — INSTALL GAS PIPING  
Unit is equipped for use with type of gas shown on name-  
plate. Refer to local building codes, or in the absence of local  
codes, to ANSI Z223.1-latest year and addendum Z223.1A-  
latest year entitled NFGC. In Canada, installation must be  
in accordance with the CAN1.B149.1 and CAN1.B149.2  
installation codes for gas burning appliances.  
IV. STEP 4 — RIG AND PLACE UNIT  
Inspect unit for transportation damage. File any claim with  
transportation agency. Keep unit upright and do not drop.  
Spreader bars are not required if top crating is left on unit.  
Rollers may be used to move unit across a roof. Level by  
using unit frame as a reference. See Table 1 and Fig. 6  
for additional information. Operating weight is shown in  
Table 1 and Fig. 6.  
For natural gas applications, gas pressure at unit gas con-  
nection must not be less than 4.0 in. wg or greater than  
13.0 in. wg while unit is operating. For liquid propane and  
high heat applications, the gas pressure must not be less  
than 5.0 in. wg or greater than 13.0 in. wg at the unit  
connection.  
Lifting holes are provided in base rails as shown in Fig. 6  
and 7. Refer to rigging instructions on unit.  
4—  
NOTES:  
OPERATING  
WEIGHT  
1. Place unit on curb as close as possible to the duct end.  
2. Dimension in ( ) is in millimeters.  
“A”  
“B”  
“C”  
UNIT  
581B  
3. Hook rigging shackles through holes in base rail as shown in detail  
“A.Holes in base rails are centered around the unit center of grav-  
ity. Use wooden top skid when rigging to prevent rigging straps  
from damaging unit.  
4. Weights include base unit without economizer. See Table 1 for unit  
operating weights and economizer weights.  
5. Weights include base unit without the Perfect Humidity™ dehumid-  
ification system. See Table 1 for additional unit operating weights  
with the Perfect Humidity system.  
lb  
kg  
in.  
mm  
in.  
mm  
in.  
mm  
036  
048  
060  
072  
530  
540  
560  
635  
240  
245  
254  
288  
73.69 1872 35.50 902 33.31 847  
73.69 1872 35.50 902 33.31 847  
73.69 1872 35.50 902 33.31 847  
73.69 1872 35.50 902 33.31 847  
CAUTION: All panels must be in place when rigging.  
Fig. 6 — Rigging Details  
Size gas supply piping for 0.5-in. wg maximum pressure  
drop. Do not use supply pipe smaller than unit gas  
connection.  
Installation Instructions for information on power wiring  
and gas connection piping. Power wiring, control wiring and  
gas connection piping can be routed through field-drilled  
holes in the basepan, which is specifically designed and dim-  
pled for drilling the accessory connection holes.  
Support gas piping as shown in the table in Fig. 9. For exam-  
ple, a 3/4-in. gas pipe must have one field-fabricated support  
beam every 8 ft. Therefore, an 18-ft long gas pipe would have  
a minimum of 3 support beams. See Fig. 9 for typical pipe  
guide and locations of external manual gas shutoff valve.  
CAUTION: When connecting the gas line to the  
unit gas valve, the installer MUST use a backup  
wrench to prevent damage to the valve.  
NOTE: If accessory thru-the-bottom connections and roof  
curb are used, refer to the Thru-the-Bottom Accessory  
5—  
Table 1 — Physical Data — 581B036-072  
UNIT SIZE 581B  
036  
048  
060  
072  
NOMINAL CAPACITY  
3
4
5
6
OPERATING WEIGHT (lb)  
Unit  
EconoMi$er IV  
Perfect Humidity™ Dehumidification System  
Roof Curb  
530  
50  
540  
50  
560  
50  
635  
50  
15  
23  
23  
29  
115  
115  
115  
115  
COMPRESSOR  
Quantity  
Oil (oz)  
Scroll  
R-22  
1
42  
1
53  
1
50  
1
60  
REFRIGERANT TYPE  
Operating Charge (lb-oz)  
Standard Unit  
5-8  
9-0  
10-2  
15-8  
10-0  
17-0  
12-8  
21-0  
Unit With Perfect Humidity Dehumidification System  
CONDENSER FAN  
Propeller  
Quantity...Diameter (in.)  
1...22  
3500  
1...22  
3500  
1...22  
4100  
1...22  
4100  
Nominal Cfm  
Motor Hp...Rpm  
1/4...825  
180  
1/4...825  
180  
1/4...1100  
320  
1/4...1100  
320  
Watts Input (Total)  
CONDENSER COIL  
Rows...Fins/in.  
Total Face Area (sq ft)  
Enhanced Copper Tubes, Aluminum Lanced Fins  
1...17  
14.6  
2...17  
16.5  
2...17  
16.5  
2...17  
16.5  
EVAPORATOR COIL  
Standard Unit  
Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Acutrol™ Metering Device  
Rows...Fins/in.  
Total Face Area (sq ft)  
2...15  
5.5  
2...15  
5.5  
4...15  
5.5  
4...15  
5.5  
Unit with Perfect Humidity Dehumidification System  
Rows...Fins/in.  
1...17  
3.9  
2...17  
3.9  
2...17  
3.9  
2...17  
5.2  
Total Face Area (sq ft)  
EVAPORATOR FAN  
Centrifugal Type, Belt Drive  
1...10 x 10  
Quantity...Size (in.)  
1...10 x 10  
1200  
1...10 x 10  
1...10 x 10  
2400  
Nominal Cfm  
1600  
1.20  
2000  
1.30/2.40*  
2.90  
48/56*  
56  
Maximum Continuous Bhp  
Std  
Hi-Static  
Std  
1.20  
2.40  
2.40  
2.40  
2.90  
Motor Frame Size  
Fan Rpm Range  
48  
48  
56  
Hi-Static  
Std  
56  
56  
56  
680-1044  
1075-1455  
Ball  
770-1185  
1075-1455  
Ball  
1035-1460  
1300-1685  
Ball  
1119-1585  
1300-1685  
Ball  
Hi-Static  
Motor Bearing Type  
Maximum Fan Rpm  
2100  
2100  
2100  
2100  
Motor Pulley Pitch Diameter A/B (in.)  
Std  
Hi-Static  
Std  
1.9/2.9  
1.9/2.0  
2.4/3.4  
2.4/3.4  
2.8/3.8  
2.8/3.8  
3.4/4.4  
3.4/3.4  
1
1
5
5
Nominal Motor Shaft Diameter (in.)  
Fan Pulley Pitch Diameter (in.)  
Belt — Type...Length (in.)  
/
/
/
/
2
2
8
8
5
5
5
7
Hi-Static  
Std  
/
/
/
/
4.85  
4.80  
4.0  
4.0  
4.0  
8
8
Hi-Static  
Std  
4.5  
4.5  
4.5  
1...A...36  
1...A...36  
1....4...40  
1...A...38  
Hi-Static  
1...A...39  
1...A...39  
1...A...40  
1...A...40  
Pulley Center Line Distance (in.)  
Speed Change per Full Turn of  
Movable Pulley Flange (rpm)  
Movable Pulley Maximum Full  
Turns from Closed Position  
10.0-12.4  
10.0-12.4  
14.7-15.5  
14.7-15.5  
Std  
Hi-Static  
Std  
65  
65  
5
70  
65  
5
75  
60  
6
95  
60  
5
Hi-Static  
Std  
6
3
6
3
5
5
3
Factory Setting — Full Turns Open  
3
Hi-Static  
Std  
31/2  
826  
31/2  
936  
31/2  
1248  
31/2  
1305  
Factory Speed Setting (rpm)  
Hi-Static  
1233  
1233  
1396  
1396  
5
5
5
5
Fan Shaft Diameter at Pulley (in.)  
/
8
/
/
/
8
8
8
LEGEND  
Bhp — Brake Horsepower  
††An LP kit is available as an accessory. If an LP kit is used with low NOx units,  
one low NOx baffle must be removed and the units will no longer be classified  
as low NOx units.  
||California compliant three-phase models.  
*Single phase/three phase.  
†Indicates automatic reset.  
**60,000 and 72,000 Btuh heat input units have 2 burners. 90,000 and  
120,000 Btuh heat input units have 3 burners. 115,000 Btuh heat input units  
and 150,000 Btuh Heat input units have 3 burners.  
***California SCAQMD compliant low NOx models have combustion products that  
are controlled to 40 nanograms per joule or less.  
6—  
Table 1 — Physical Data — 581B036-072 (cont)  
UNIT SIZE 581B  
036  
048  
060  
072  
FURNACE SECTION  
Rollout Switch Cutout Temp (F)†  
Burner Orifice Diameter (in. ...drill size)**  
Natural Gas — Std  
195  
195  
195  
195  
071/072  
114/115  
149/150  
.113...33  
.113...33  
.113...33  
.113...33  
.129...30  
.113...33  
.113...33  
.129...30  
.113...33  
.113...33  
.129...30  
060N  
090N  
120N  
.102...38  
.102...38  
.102...38  
.102...38  
.116...32  
.102...38  
.102...38  
.116...32  
Liquid Propane — Alt††  
071/072  
114/115  
149/150  
.089...43  
.089...43  
.089...43  
.089...43  
.102...38  
.089...43  
.089...43  
.102...38  
.089...43  
.089...43  
.102...38  
060N  
090N  
120N  
.082...45  
.082...45  
.082...45  
.082...45  
.094...42  
.082...45  
.082...45  
.094...42  
Thermostat Heat Anticipator Setting (amps)  
208/230/460 v  
First Stage  
.14  
.14  
.14  
.14  
.14  
.14  
.14  
.14  
Second Stage  
Gas Input (Btuh)  
First Stage/Second Stage (3-phase units)  
072  
115  
150  
50,000/ 72,000  
82,000/115,000  
50,000/ 72,000  
82,000/115,000  
120,000/150,000  
50,000/ 72,000  
82,000/115,000  
120,000/150,000  
50,000/ 72,000  
82,000/115,000  
120,000/150,000  
071II  
114II  
149II  
—/ 72,000  
—/115,000  
—/ 72,000  
—/115,000  
—/150,000  
—/ 72,000  
—/115,000  
—/150,000  
060N***  
090N***  
120N***  
—/ 60,000  
—/ 90,000  
—/ 60,000  
—/ 90,000  
—/120,000  
—/ 60,000  
—/ 90,000  
—/120,000  
Efficiency (Steady State) (%)  
072  
115  
150  
82.8  
80  
82.8  
81  
80.4  
82.8  
81  
80.4  
82  
81  
80  
071  
114  
149  
82  
80  
82  
81  
80  
82  
81  
80  
060N  
090N  
120N  
80.2  
81  
80.2  
81  
80.7  
80.2  
81  
80.7  
Temperature Rise Range  
072  
115  
150  
25-55  
55-85  
25-55  
35-65  
50-80  
25-55  
35-65  
50-80  
25-55  
35-65  
50-80  
071  
114  
149  
25-55  
55-85  
25-55  
35-65  
50-80  
25-55  
35-65  
50-80  
060N  
090N  
120N  
20-50  
30-60  
20-50  
30-60  
40-70  
20-50  
30-60  
40-70  
Manifold Pressure (in. wg)  
Natural Gas — Std  
3.5  
3.5  
3.5  
3.5  
3.5  
3.5  
3.5  
3.5  
Liquid Propane — Alt††  
Maximum Static Pressure (in. wg)  
Field Gas Connection Size (in.)  
1.0  
1.0  
1.0  
1.0  
1
1
1
1
/
2
/
2
/
2
/
2
HIGH-PRESSURE SWITCH (psig)  
450 50  
428  
320  
Standard Compressor Internal Relief  
Cutout  
Reset (Auto.)  
LOSS-OF-CHARGE SWITCH/LOW-PRESSURE  
SWITCH (Liquid LIne) (psig)  
Cutout  
7
22  
3
5
Reset (Auto.)  
FREEZE PROTECTION THERMOSTAT  
Opens (F)  
Closes (F)  
30  
45  
5
5
OUTDOOR-AIR INLET SCREENS  
Quantity...Size (in.)  
Cleanable  
1...20 x 24 x 1  
RETURN-AIR FILTERS  
Quantity...Size (in.)  
Throwaway  
2...16 x 25 x 2  
4...16 x 16 x 2  
LEGEND  
††An LP kit is available as an accessory. If an LP kit is used with low NOx units,  
one low NOx baffle must be removed and the units will no longer be classified  
as low NOx units.  
BhpBrake Horsepower  
||California compliant three-phase models.  
*Single phase/three phase.  
†Indicates automatic reset.  
**60,000 and 72,000 Btuh heat input units have 2 burners. 90,000 and  
120,000 Btuh heat input units have 3 burners. 115,000 Btuh heat input units  
and 150,000 Btuh Heat input units have 3 burners.  
***California SCAQMD compliant low NOx models have combustion products that  
are controlled to 40 nanograms per joule or less.  
7—  
8—  
Refer to unit label diagram for additional information. Pig-  
tails are provided for field service. Use factory-supplied  
splices or UL (Underwriters’ Laboratories) approved copper  
connector.  
When installing units, provide a disconnect per NEC.  
All field wiring must comply with NEC and local require-  
ments. In Canada, electrical connections must be in accor-  
dance with CSA (Canadian Standards Association) C22.1  
Canadian Electrical Code Part One.  
Install conduit through side panel openings indicated in  
Fig. 7. Route power lines through connector to terminal  
connections as shown in Fig. 10.  
On 3-phase units, voltages between phases must be balanced  
within 2% and the current within 10%. Use the formula  
shown in Note 3 under Tables 2A-2D to determine the per-  
centage of voltage imbalance. Operation on improper line  
voltage or excessive phase imbalance constitutes abuse and  
may cause damage to electrical components. Such operation  
would invalidate any applicable Bryant warranty.  
Fig. 8 — Flue Hood Details  
NOTE: If thru-the-bottom accessory connections are used,  
refer to the thru-the-bottom accessory installation instruc-  
tions for power wiring. Refer to Fig. 7 for location to drill  
holes in basepan.  
B. Field Control Wiring  
Install a Bryant-approved accessory thermostat assembly  
according to installation instructions included with the  
accessory. Locate thermostat assembly on a solid wall in the  
conditioned space to sense average temperature in accor-  
dance with thermostat installation instructions.  
LEGEND  
NFGC — National Fuel Gas Code  
*Field supplied.  
Route thermostat cable or equivalent single leads of colored  
wire from thermostat subbase terminals to low-voltage con-  
nections on unit (shown in Fig. 11) as described in Steps 1-4  
below.  
NOTE: Follow all local codes.  
1. If mounted on a roof curb and electrical power is to be  
run through the basepan, an accessory thru-the-bot-  
tom connection kit is required. This is available  
through the local Bryant distributor. This kit is  
required to ensure a reliable water-tight connection.  
STEEL PIPE  
SPACING OF SUPPORTS  
NOMINAL DIAMETER  
X DIMENSION  
(ft)  
(in.)  
1
/
6
8
10  
2
3/4 or 1  
11/4 or larger  
2. If unit is mounted on roof curb and accessory thru-  
the-bottom connections are used, route wire through  
connection plate.  
Fig. 9 — Gas Piping Guide (With Accessory  
Thru-the-Curb Service Connections)  
3. Pass control wires through the hole provided on unit  
(see connection D, Connection Sizes table, Fig. 7).  
VII. STEP 7 — MAKE ELECTRICAL CONNECTIONS  
4. Feed wires through the raceway built into the corner  
post to the 24-v barrier located on the left side of the  
control box. See Fig. 12. The raceway provides the  
UL-required clearance between high- and low-voltage  
wiring.  
WARNING: Unit cabinet must have an uninter-  
rupted, unbroken electrical ground to minimize the  
possibility of personal injury if an electrical fault  
should occur. This ground may consist of electrical wire  
connected to unit ground lug in control compartment,  
or conduit approved for electrical ground when  
installed in accordance with NEC (National Electrical  
Code), ANSI/NFPA (National Fire Protection Associa-  
tion), latest edition, and local electrical codes. Do not  
use gas piping as an electrical ground. Failure to follow  
this warning could result in the installer being liable  
for personal injury of others.  
5. Connect thermostat wires to screw terminals of low-  
voltage connection board (see Fig. 11).  
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American  
Wire Gage) insulated wire (35 C minimum). For 51 to 75 ft,  
use no. 16 AWG insulated wire (35 C minimum). For over  
75 ft, use no. 14 AWG insulated wire (35 C minimum).  
NOTE: All wire larger than no. 18 AWG cannot be directly  
connected to the thermostat and will require a junction box  
and splice at the thermostat.  
A. Field Power Supply  
All units except 208/230-v units are factory wired for the  
voltage shown on the nameplate. If the 208/230-v unit is to  
be connected to a 208-v power supply, the transformer must  
be rewired by moving the black wire from the 230-v terminal  
on the transformer and connecting it to the 200-v terminal  
on the transformer.  
C. Heat Anticipator Settings  
Set heat anticipator settings at 0.14 amp for first stage and  
0.14 amp for second-stage heating, when available.  
9—  
LEGEND  
C
Contactor  
COMP  
Compressors  
EQUIP — Equipment  
GND  
IFC  
Ground  
Indoor (Evaporator)  
Fan Contactor  
NEC  
TB  
National Electrical Code  
Terminal Block  
Fig. 10 — Power Wiring Connections  
BRYANT ELECTRONIC THERMOSTAT  
R
G
COOL STAGE 1  
FAN  
Y1/W2  
G
RACEWAY  
LOW VOLTAGE  
CONNECTIONS  
INTEGRATED GAS UNIT  
CONTROLLER (IGC)  
Y1  
HEAT STAGE 1  
COOL STAGE 2  
HEAT STAGE 2  
24 VAC HOT  
W/W1  
Y/Y2  
O/W2  
R
WIRE  
Y2  
CONNECTIONS  
TO  
W1  
W2  
C
LOW-VOLTAGE  
SECTION  
24 VAC COM  
N/A  
C
IPD/X  
OUTDOOR AIR  
SENSOR  
S1  
S2  
THERMOSTAT DIPSWITCH SETTINGS  
ON  
OFF  
D
A
B
C
LEGEND  
Field Wiring  
HOLE IN END PANEL (HIDDEN)  
NOTE: Underlined letter indicates active thermostat output when con-  
figured for A/C operation.  
Fig. 12 — Field Control Wiring Raceway  
Fig. 11 — Low-Voltage Connections With or  
Without Economizer  
10—  
Table 2A — Electrical Data — Standard Motor Units Without Electrical Convenience Outlet  
VOLTAGE  
RANGE  
Min Max Qty  
COMPRESSOR  
(each)  
OFM  
COMBUSTION  
FAN MOTOR  
POWER  
MINIMUM UNIT  
IFM  
UNIT  
581B  
NOMINAL VOLTAGE  
(V-Ph-Hz)  
(each)  
SUPPLY*  
DISCONNECT SIZE†  
RLA  
16.0  
10.3  
5.1  
LRA  
FLA  
0.7  
0.7  
0.4  
0.4  
0.7  
0.7  
0.4  
0.4  
1.5  
1.5  
0.8  
0.8  
1.4  
0.6  
0.6  
FLA  
4.9  
4.9  
2.2  
2.2  
4.9  
4.9  
2.2  
2.2  
8.8  
5.8  
2.6  
2.6  
5.8  
2.6  
2.6  
FLA  
.60  
.60  
.30  
.30  
.60  
.60  
.30  
.30  
.60  
.60  
.30  
.30  
.60  
.30  
.30  
MCA  
MOCP**  
30/30  
25/25  
20  
FLA  
25/25  
18/18  
9
LRA  
101/101  
90/90  
46  
208/230-1-60  
208/230-3-60  
460-3-60  
187  
187  
414  
518  
187  
187  
414  
518  
187  
187  
414  
518  
187  
414  
518  
254  
254  
508  
632  
254  
254  
508  
632  
254  
254  
508  
632  
254  
508  
632  
88.0  
77.0  
39.0  
31.0  
126.0  
93.0  
46.5  
40.0  
169.0  
123.0  
62.0  
50.0  
156.0  
75.0  
56.0  
25.6/25.6  
18.5/18.5  
9.0  
036  
(3 Tons)  
1
1
575-3-60  
4.2  
7.3  
20  
7
37  
208/230-1-60  
208/230-3-60  
460-3-60  
23.7  
13.5  
6.4  
35.2/35.2  
22.5/22.5  
10.6  
45/45  
30/30  
20  
34/34  
22/22  
10  
139/139  
106/106  
54  
048  
(4 Tons)  
575-3-60  
6.4  
10.1  
20  
10  
46  
208/230-1-60  
208/230-3-60  
460-3-60  
575-3-60  
208/230-3-60  
460-3-60  
28.8  
17.3  
9.0  
46.3/46.3  
28.9/28.9  
14.7  
60/60  
35/35  
20  
45/45  
28/28  
14  
216/216  
168/168  
84  
060  
(5 Tons)  
1
1
7.1  
11.6  
20  
12  
68  
20.5  
9.6  
32.8/32.8  
15.2  
40/40  
20  
32/32  
15  
200/200  
97  
072  
(6 Tons)  
575-3-60  
7.7  
12.2  
20  
12  
74  
Table 2B — Electrical Data — Standard Motor Units With Electrical Convenience Outlet  
POWER  
VOLTAGE  
RANGE  
COMPRESSOR  
(each)  
OFM  
(each)  
COMBUSTION  
FAN MOTOR  
MINIMUM UNIT  
DISCONNECT SIZE†  
IFM  
SUPPLY  
UNIT  
581B  
NOMINAL VOLTAGE  
(V-Ph-Hz)  
WITH OUTLET*  
Min Max Qty  
RLA  
16.0  
10.3  
5.1  
LRA  
FLA  
0.7  
0.7  
0.4  
0.4  
0.7  
0.7  
0.4  
0.4  
1.5  
1.5  
0.8  
0.8  
1.4  
0.6  
0.6  
FLA  
4.9  
4.9  
2.2  
2.2  
4.9  
4.9  
2.2  
2.2  
8.8  
5.8  
2.6  
2.6  
5.8  
2.6  
2.6  
FLA  
.60  
.60  
.30  
.30  
.60  
.60  
.30  
.30  
.60  
.60  
.30  
.30  
.60  
.30  
.30  
MCA  
31.6/31.6  
24.5/24.5  
11.7  
MOCP**  
FLA  
30/30  
24/24  
11  
LRA  
106/106  
95/95  
48  
208/230-1-60  
208/230-3-60  
460-3-60  
187  
187  
414  
518  
187  
187  
414  
518  
187  
187  
414  
518  
187  
414  
518  
254  
254  
508  
632  
254  
254  
508  
632  
254  
254  
508  
632  
254  
508  
632  
88.0  
77.0  
39.0  
31.0  
126.0  
93.0  
46.5  
40.0  
169.0  
123.0  
62.0  
50.0  
156.0  
75.0  
56.0  
35/35  
30/30  
20  
036  
(3 Tons)  
1
1
575-3-60  
4.2  
9.5  
20  
9
38  
208/230-1-60  
208/230-3-60  
460-3-60  
23.7  
13.5  
6.4  
41.2/41.2  
28.5/28.5  
13.3  
50/50  
35/35  
20  
39/39  
27/27  
13  
144/144  
111/111  
56  
048  
(4 Tons)  
575-3-60  
6.4  
12.2  
20  
12  
47  
208/230-1-60  
208/230-3-60  
460-3-60  
28.8  
17.3  
9.0  
7.1  
20.5  
9.6  
52.3/52.3  
34.9/34.9  
17.4  
13.8  
38.8/38.8  
17.9  
60/60  
40/40  
20  
20  
45/45  
20  
50/50  
34/34  
17  
13  
37/37  
17  
221/221  
173/173  
87  
70  
205/205  
99  
060  
(5 Tons)  
1
1
575-3-60  
208/230-3-60  
460-3-60  
575-3-60  
072  
(6 Tons)  
7.7  
14.3  
20  
14  
75  
LEGEND  
(AB) 457 – 452 = 5 v  
(BC) 464 – 457 = 7 v  
(AC) 457 – 455 = 2 v  
FLA  
Full Load Amps  
HACR — Heating, Air Conditioning and  
Refrigeration  
Maximum deviation is 7 v.  
IFM  
LRA  
Indoor (Evaporator) Fan Motor  
Locked Rotor Amps  
Determine percent of voltage imbalance.  
7
% Voltage Imbalance = 100 x  
457  
MCA — Minimum Circuit Amps  
MOCP — Maximum Overcurrent Protection  
NEC — National Electrical Code  
= 1.53%  
OFM — Outdoor (Condenser) Fan Motor  
This amount of phase imbalance is satisfactory as it is below the maximum  
allowable 2%.  
IMPORTANT: If the supply voltage phase imbalance is more than 2%,  
contact your local electric utility company immediately.  
RLA  
UL  
Rated Load Amps  
Underwriters’ Laboratories  
*The values listed in this table do not include power exhaust. See table at right for  
power exhaust requirements.  
†Used to determine minimum disconnect per NEC.  
**Fuse or HACR circuit breaker.  
POWER EXHAUST ELECTRICAL DATA  
MOCP  
POWER EXHAUST  
PART NO.  
MCA  
MCA  
MCA  
NOTES:  
(for separate  
(230 v)  
(460 v)  
(575 v)  
1. In compliance with NEC requirements for multimotor and combination load  
equipment (refer to NEC Articles 430 and 440), the overcurrent protective  
device for the unit shall be fuse or HACR breaker. The UL, Canada units  
may be fuse or circuit breaker.  
power source)  
CRPWREXH021A01  
CRPWREXH022A01  
CRPWREXH023A01  
CRPWREXH028A01  
CRPWREXH029A01  
CRPWREXH030A01  
N/A  
3.3  
N/A  
1.7  
N/A  
1.6  
0.9  
N/A  
1.8  
N/A  
1.0  
N/A  
1.32  
N/A  
0.68  
N/A  
15  
15  
15  
15  
15  
15  
2. Electrical data based on 95 F ambient outdoor-air temperature 10% voltage.  
3. Unbalanced 3-Phase Supply Voltage  
Never operate a motor where phase imbalance in supply voltage is greater  
than 2%. Use the following formula to determine the percent voltage  
imbalance.  
N/A  
0.64  
% Voltage Imbalance  
N/A — Not available  
max voltage deviation from average voltage  
= 100 x  
NOTE: If a single power source is to be used, size wire to include power exhaust  
MCA and MOCP.  
average voltage  
Example: Supply voltage is 460-3-60.  
Check MCA and MOCP when power exhaust is powered through the unit. Deter-  
mine the new MCA including the power exhaust using the following formula:  
MCA New = MCA unit only + MCA of Power Exhaust  
For example, using a 581B072 unit with MCA = 32.8 and MOCP = 40, with  
CRPWREXH030A01 power exhaust.  
MCA New = 32.8 amps + 1.6 amps = 34.4 amps  
If the new MCA does not exceed the published MOCP, then MOCP would not  
change. The MOCP in this example is 40 amps and the MCA New is below 40;  
therefore the MOCP is acceptable. If “MCA New” is larger than the published  
MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for  
the power exhaust will be 15 amps per NEC.  
AB = 452 v  
BC = 464 v  
AC = 455 v  
452 + 464 + 455  
Average Voltage =  
3
1371  
3
=
= 457  
Determine maximum deviation from average voltage.  
11—  
Table 2C — Electrical Data — High-Static Motor Units Without Electrical Convenience Outlet  
MINIMUM UNIT  
DISCONNECT  
SIZE†  
VOLTAGE  
RANGE  
COMPRESSOR  
(each)  
OFM  
COMBUSTION  
FAN MOTOR  
POWER  
NOMINAL  
VOLTAGE  
(V-Ph-Hz)  
IFM  
UNIT  
581B  
(each)  
SUPPLY*  
Min  
Max  
Qty  
RLA  
10.3  
5.1  
LRA  
FLA  
0.7  
0.4  
0.4  
0.7  
0.4  
0.4  
1.5  
0.8  
0.8  
1.4  
0.6  
0.6  
FLA  
5.8  
RLA  
0.6  
0.3  
0.3  
0.6  
0.3  
0.3  
0.6  
0.3  
0.3  
0.6  
0.3  
0.3  
MCA  
MOCP**  
25  
20  
20  
30  
20  
20  
35  
20  
20  
40  
20  
20  
FLA  
19  
9
LRA  
120  
60  
208/230-3-60  
460-3-60  
575-3-60  
208/230-3-60  
460-3-60  
575-3-60  
208/230-3-60  
460-3-60  
575-3-60  
208/230-3-60  
460-3-60  
575-3-60  
187  
414  
518  
187  
414  
518  
187  
414  
518  
187  
414  
518  
254  
508  
632  
254  
508  
632  
254  
508  
632  
254  
508  
632  
77.0  
39.0  
31.0  
93.0  
46.5  
40.0  
123.0  
62.0  
50.0  
156.0  
75.0  
56.0  
19.4  
9.4  
7.7  
036  
048  
060  
072  
1
2.6  
2.6  
5.8  
2.6  
2.6  
7.5  
3.4  
3.4  
7.5  
3.4  
3.4  
4.2  
8
48  
13.5  
6.4  
23.4  
11.0  
10.4  
30.6  
15.5  
12.2  
34.5  
16  
23  
11  
10  
30  
15  
12  
34  
16  
13  
136  
68  
57  
187  
94  
76  
219  
107  
81  
1
1
1
6.4  
17.3  
9.0  
7.1  
20.5  
9.6  
7.7  
12.8  
Table 2D — Electrical Data — High-Static Motor Units With Electrical Convenience Outlet  
MINIMUM UNIT  
DISCONNECT  
SIZE†  
VOLTAGE  
RANGE  
COMPRESSOR  
(each)  
OFM  
COMBUSTION  
FAN MOTOR  
POWER  
NOMINAL  
VOLTAGE  
(V-Ph-Hz)  
IFM  
UNIT  
581B  
(each)  
SUPPLY*  
Min  
Max  
254  
508  
632  
254  
508  
632  
254  
508  
632  
254  
508  
632  
Qty  
RLA  
10.3  
5.1  
LRA  
FLA  
0.7  
0.4  
0.4  
0.7  
0.4  
0.4  
1.5  
0.8  
0.8  
1.4  
0.6  
0.6  
FLA  
5.8  
RLA  
0.6  
0.3  
0.3  
0.6  
0.3  
0.3  
0.6  
0.3  
0.3  
0.6  
0.3  
0.3  
MCA  
MOCP**  
FLA  
25  
12  
10  
29  
13  
12  
36  
18  
14  
39  
18  
15  
LRA  
124  
63  
50  
140  
70  
59  
192  
96  
208/230-3-60  
460-3-60  
575-3-60  
208/230-3-60  
460-3-60  
575-3-60  
208/230-3-60  
460-3-60  
575-3-60  
208/230-3-60  
460-3-60  
575-3-60  
187  
414  
518  
187  
414  
518  
187  
414  
518  
187  
414  
518  
77.0  
39.0  
31.0  
93.0  
46.5  
40.0  
123.0  
62.0  
50.0  
156.0  
75.0  
56.0  
25.4  
12.1  
9.8  
30  
20  
20  
35  
20  
20  
40  
20  
20  
45  
25  
20  
036  
048  
060  
072  
1
2.6  
2.6  
5.8  
2.6  
2.6  
7.5  
3.4  
3.4  
7.5  
3.4  
3.4  
4.2  
13.5  
6.4  
29.4  
13.7  
12.6  
36.6  
18.2  
14.4  
40.5  
18.7  
15.0  
1
1
1
6.4  
17.3  
9.0  
7.1  
77  
20.5  
9.6  
224  
109  
83  
7.7  
LEGEND  
(AB) 457 – 452 = 5 v  
(BC) 464 – 457 = 7 v  
(AC) 457 – 455 = 2 v  
FLA  
Full Load Amps  
HACR — Heating, Air Conditioning and  
Refrigeration  
Maximum deviation is 7 v.  
IFM  
LRA  
Indoor (Evaporator) Fan Motor  
Locked Rotor Amps  
Determine percent of voltage imbalance.  
7
% Voltage Imbalance = 100 x  
457  
MCA — Minimum Circuit Amps  
MOCP — Maximum Overcurrent Protection  
NEC  
National Electrical Code  
= 1.53%  
OFM — Outdoor (Condenser) Fan Motor  
This amount of phase imbalance is satisfactory as it is below the maximum  
allowable 2%.  
IMPORTANT: If the supply voltage phase imbalance is more than 2%,  
contact your local electric utility company immediately.  
RLA  
UL  
Rated Load Amps  
Underwriters’ Laboratories  
*The values listed in this table do not include power exhaust. See table at right for  
power exhaust requirements.  
†Used to determine minimum disconnect per NEC.  
**Fuse or HACR circuit breaker.  
POWER EXHAUST ELECTRICAL DATA  
MOCP  
POWER EXHAUST  
PART NO.  
MCA  
MCA  
MCA  
NOTES:  
(for separate  
(230 v)  
(460 v)  
(575 v)  
1. In compliance with NEC requirements for multimotor and combination load  
equipment (refer to NEC Articles 430 and 440), the overcurrent protective  
device for the unit shall be fuse or HACR breaker. The UL, Canada units  
may be fuse or circuit breaker.  
power source)  
CRPWREXH021A01  
CRPWREXH022A01  
CRPWREXH023A01  
CRPWREXH028A01  
CRPWREXH029A01  
CRPWREXH030A01  
N/A  
3.3  
N/A  
1.7  
N/A  
1.6  
0.9  
N/A  
1.8  
N/A  
1.0  
N/A  
1.32  
N/A  
0.68  
N/A  
15  
15  
15  
15  
15  
15  
2. Electrical data based on 95 F ambient outdoor-air temperature 10% voltage.  
3. Unbalanced 3-Phase Supply Voltage  
Never operate a motor where phase imbalance in supply voltage is greater  
than 2%. Use the following formula to determine the percent voltage  
imbalance.  
N/A  
0.64  
% Voltage Imbalance  
N/A — Not available  
max voltage deviation from average voltage  
= 100 x  
NOTE: If a single power source is to be used, size wire to include power exhaust  
MCA and MOCP.  
average voltage  
Example: Supply voltage is 460-3-60.  
Check MCA and MOCP when power exhaust is powered through the unit. Deter-  
mine the new MCA including the power exhaust using the following formula:  
MCA New = MCA unit only + MCA of Power Exhaust  
For example, using a 581B072 unit with MCA = 32.8 and MOCP = 40, with  
CRPWREXH030A01 power exhaust.  
MCA New = 32.8 amps + 1.6 amps = 34.4 amps  
If the new MCA does not exceed the published MOCP, then MOCP would not  
change. The MOCP in this example is 40 amps and the MCA New is below 40;  
therefore the MOCP is acceptable. If “MCA New” is larger than the published  
MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for  
the power exhaust will be 15 amps per NEC.  
AB = 452 v  
BC = 464 v  
AC = 455 v  
452 + 464 + 455  
Average Voltage =  
3
1371  
=
3
= 457  
Determine maximum deviation from average voltage.  
12—  
VIII. STEP 8 — ADJUST FACTORY-INSTALLED OPTIONS  
A. Disconnect Switch  
The optional disconnect switch is non-fused. The switch has  
the capability of being locked in place for safety purposes.  
B. Perfect Humidity™ Dehumidification System  
Perfect Humidity system operation can be controlled by field  
installation of a Bryant-approved humidistat device (Fig. 13),  
or light commercial Thermidistat™ device (Fig. 14). To install  
the humidistat device:  
% RELATIVE HUMIDITY  
1. Route humidistat cable through hole provided in unit  
corner post.  
2. Feed wires through the raceway built into the corner  
post to the 24-v barrier located on the left side of the  
control box. See Fig. 12. The raceway provides the  
UL-required clearance between high-voltage and low-  
voltage wiring.  
Fig. 13 — Accessory Field-Installed Humidistat Device  
3. Use a wire nut to connect humidistat cable into low-  
voltage wiring as shown in Fig. 15.  
To install Thermidistat device:  
1. Route Thermidistat cable through hole provided in  
unit corner post.  
2. Feed the wires through the raceway built into the cor-  
ner post to the 24-v barrier located on the left side of  
the control box. See Fig. 12. The raceway provides the  
UL-required clearance between high and low voltage  
wiring.  
3. A field-supplied relay must be installed between the  
Thermidistat device and the Perfect Humidity circuit  
(recommended relay: HN612KK324). See Fig. 16. The  
relay coil is connected between the DEHUM output  
and C (common) of the unit. The relay controls the  
Perfect Humidity solenoid valve and must be wired  
between the Perfect Humidity fuse and the low-pres-  
sure switch. Refer to the installation instructions  
included with the Bryant Light Commercial Thermi-  
distat device for more information.  
Fig. 14 — Light Commercial Thermidistat Device  
LEGEND  
C
Contactor (Compressor)  
Circuit Breaker  
Low Temperature Lockout  
LTLO  
CB  
CR  
TRAN — Transformer  
Cooling Relay  
Terminal (Unmarked)  
DHR — Dehumidify Relay  
DSV — Discharge Solenoid Valve  
Splice  
HU  
LPS  
Humidistat  
Factory Wiring  
Low Pressure Switch  
LSV — Liquid Line Solenoid Valve  
Accessory or Optional Wiring  
Fig. 15 — Typical Perfect Humidity Dehumidification System  
Humidistat Wiring (208/230-v Unit Shown)  
13—  
LCT  
ROOF TOP UNIT  
R
C
R
C
Y1  
Y2  
G
Y1  
Y2  
G
W1  
W2  
W1  
W2  
DEHUM  
OC  
CB  
R1  
R1  
3.2 AMPS  
PINK  
RED  
24V  
T STAT WIRES  
LTLO  
PINK  
PINK  
FROM  
PERFECT HUMIDITY  
SYSTEM LLSV  
LEGEND  
Circuit Breaker  
CB  
LCT — Light Commercial Thermidistat™ Device  
LLSV — Liquid Line Solenoid Valve  
LTLO — Low Temperature Lockout  
PERFECT HUMIDITY SYSTEM  
Fig. 16 — Typical Rooftop Unit with Perfect Humidity™ Dehumidification System with Thermidistat Device  
C. Convenience Outlet  
An optional convenience outlet provides power for rooftop  
use. For maintenance personnel safety, the convenience out-  
let power is off when the unit disconnect is off. Adjacent unit  
outlets may be used for service tools. An optional Hot Out-  
let” is available from the factory as a special order item.  
OUTDOOR  
AIR OPENING  
PANEL  
3 SCREWS  
(SIDE)  
D. Manual Outdoor-Air Damper  
The outdoor-air hood and screen are attached to the basepan  
at the bottom of the unit for shipping.  
Assembly:  
1. Determine quantity of ventilation required for build-  
ing. Record amount for use in Step 8.  
2. Remove outdoor-air opening panel. Save panels and  
screws. See Fig. 17.  
3. Remove evaporator coil access panel. Separate hood  
and screen from basepan by removing the 4 screws  
securing them. Save all screws.  
Fig. 17 — Damper Panel with Manual  
Outdoor-Air Damper Installed  
4. Replace evaporator coil access panel.  
5. Place hood on front of outdoor-air opening panel. See  
Fig. 18 for hood details. Secure top of hood with the 4  
screws removed in Step 3. See Fig. 19.  
6. Remove and save 6 screws (3 on each side) from sides  
of the manual outdoor-air damper.  
7. Align screw holes on hood with screw holes on side of  
manual outdoor-air damper. See Fig. 18 and 19.  
Secure hood with 6 screws from Step 6.  
8. Adjust minimum position setting of the damper blade  
by adjusting the manual outdoor-air adjustment  
screws on the front of the damper blade. See Fig. 17.  
Slide blade vertically until it is in the appropriate  
position determined by Fig. 20. Tighten screws.  
9. Remove and save screws currently on sides of hood.  
Insert screens. Secure screens to hood using the  
screws. See Fig. 19.  
Fig. 18 — Outdoor-Air Hood Details  
14—  
ECONOMI$ER IV  
CONTROLLER  
OUTSIDE AIR  
TEMPERATURE SENSOR  
WIRING  
HARNESS  
LOW AMBIENT  
SENSOR  
ACTUATOR  
Fig. 19 — Optional Manual Outdoor-Air Damper  
with Hood Attached  
Fig. 21 — EconoMi$er IV Component Locations  
FILTER ACCESS PANEL  
COMPRESSOR  
ACCESS PANEL  
OUTDOOR-AIR OPENING AND  
INDOOR COIL ACCESS PANEL  
Fig. 22 — Typical Access Panel Locations  
Fig. 20 — Outdoor-Air Damper Position Setting  
E. Optional EconoMi$er IV  
HOOD BOX  
BRACKET  
See Fig. 21 for EconoMi$er IV component locations.  
NOTE: These instructions are for installing the optional  
EconoMi$er IV only. Refer to the accessory EconoMi$er IV  
installation instructions when field installing an EconoMi$er  
IV accessory.  
1. To remove the existing unit filter access panel, raise  
the panel and swing the bottom outward. The panel is  
now disengaged from the track and can be removed.  
See Fig. 22.  
2. The box with the economizer hood components is  
shipped in the compartment behind the economizer.  
The EconoMi$er IV controller is mounted on top of  
the EconoMi$er IV in the position shown in Fig. 21.  
To remove the component box from its shipping posi-  
tion, remove the screw holding the hood box bracket  
to the top of the economizer. Slide the hood box out of  
the unit. See Fig. 23.  
Fig. 23 — Hood Box Removal  
15—  
IMPORTANT: If the power exhaust accessory is to be  
installed on the unit, the hood shipped with the unit will not  
be used and must be discarded. Sa ve th e a lu m in u m filter  
for u se in th e p ow er exh a u st h ood a ssem b ly.  
17 1/4”  
3. The indoor coil access panel will be used as the top of  
the hood. Remove the screws along the sides and bot-  
tom of the indoor coil access panel. See Fig. 24.  
4. Swing out indoor coil access panel and insert the  
hood sides under the panel (hood top). Use the screws  
provided to attach the hood sides to the hood top. Use  
screws provided to attach the hood sides to the unit.  
See Fig. 25.  
DIVIDER  
OUTSIDE  
AIR  
5. Remove the shipping tape holding the economizer  
barometric relief damper in place.  
HOOD  
CLEANABLE  
ALUMINUM  
FILTER  
6. Insert the hood divider between the hood sides. See  
Fig. 25 and 26. Secure hood divider with 2 screws on  
each hood side. The hood divider is also used as the  
bottom filter rack for the aluminum filter.  
FILTER  
BAROMETRIC  
RELIEF  
FILTER  
CLIP  
Fig. 26 — Filter Installation  
SIDE  
PANEL  
7. Open the filter clips which are located underneath  
the hood top. Insert the aluminum filter into the bot-  
tom filter rack (hood divider). Push the filter into  
position past the open filter clips. Close the filter clips  
to lock the filter into place. See Fig. 26.  
8. Caulk the ends of the joint between the unit top panel  
and the hood top. See Fig. 24.  
9. Replace the filter access panel.  
TOP  
10. Install all EconoMi$er IV accessories. EconoMi$er IV  
wiring is shown in Fig. 27.  
SIDE  
PANEL  
CAULK  
HERE  
Barometric flow capacity is shown in Fig. 28. Outdoor air  
leakage is shown in Fig. 29. Return air pressure drop is  
shown in Fig. 30.  
INDOOR  
COIL  
ACCESS  
PANEL  
INDOOR  
COIL  
ACCESS  
PANEL  
F. EconoMi$er IV Standard Sensors  
Outdoor Air Temperature (OAT) Sensor  
Fig. 24 — Indoor Coil Access Panel Relocation  
The outdoor air temperature sensor (HH57AC074) is a 10 to  
20 mA device used to measure the outdoor-air temperature.  
The outdoor-air temperature is used to determine when the  
EconoMi$er IV can be used for free cooling. The sensor is  
factory-installed on the EconoMi$er IV in the outdoor  
airstream. See Fig. 21. The operating range of temperature  
measurement is 40 to 100 F.  
TOP  
PANEL  
INDOOR COIL  
ACCESS PANEL  
Supply Air Temperature (SAT) Sensor  
The supply air temperature sensor is a 3 K thermistor  
located at the inlet of the indoor fan. See Fig. 31. This sensor  
is factory installed. The operating range of temperature  
measurement is 0° to 158 F. See Table 3 for sensor tempera-  
ture/resistance values.  
LEFT  
HOOD  
SIDE  
SCREW  
B
19 1/16”  
The temperature sensor looks like an eyelet terminal with  
wires running to it. The sensor is located in the crimp end”  
and is sealed from moisture.  
33 3/8”  
Outdoor Air Lockout Sensor  
The EconoMi$er IV is equipped with an ambient tempera-  
ture lockout switch located in the outdoor airstream which is  
used to lockout the compressors below a 42 F ambient tem-  
perature. See Fig. 21.  
HOOD DIVIDER  
Fig. 25 — Outdoor-Air Hood Construction  
16—  
FOR OCCUPANCY CONTROL  
REPLACE JUMPER WITH  
FIELD-SUPPLIED TIME CLOCK  
Potentiometer Defaults Settings:  
Power Exhaust Middle  
LEGEND  
NOTES:  
1. 620 ohm, 1 watt 5% resistor should be removed only when using differential  
enthalpy or dry bulb.  
DCV— Demand Controlled Ventilation  
IAQ — Indoor Air Quality  
Minimum Pos.  
DCV Max.  
DCV Set  
Fully Closed  
Middle  
2. If a separate field-supplied 24 v transformer is used for the IAQ sensor power  
supply, it cannot have the secondary of the transformer grounded.  
3. For field-installed remote minimum position POT, remove black wire jumper  
between P and P1 and set control minimum position POT. to the minimum  
position.  
LA — Low Ambient Lockout Device  
OAT — Outdoor-Air Temperature  
POTPotentiometer  
Middle  
Enthalpy  
C Setting  
RAT — Return-Air Temperature  
Fig. 27 — EconoMi$er IV Wiring  
6000  
5000  
4000  
3000  
2000  
1000  
0
2500  
2000  
1500  
1000  
500  
0
0.05  
0.10  
0.15  
0.20  
0.25  
0.30  
0.35  
0.15  
STATIC PRESSURE (in. wg)  
0.05  
0.25  
STATIC PRESSURE (in. wg)  
Fig. 30 — Return-Air Pressure Drop  
Fig. 28 — Barometric Flow Capacity  
30  
25  
20  
15  
10  
5
SUPPLY AIR  
TEMPERATURE  
SENSOR  
MOUNTING  
LOCATION  
SUPPLY AIR  
TEMPERATURE  
SENSOR  
0
0.13 0.20 0.22 0.25 0.30 0.35 0.40 0.45 0.50  
STATIC PRESSURE (in. wg)  
Fig. 31 — Supply Air Sensor Location  
Fig. 29 — Outdoor-Air Damper Leakage  
17—  
Table 3 — Supply Air Sensor  
Table 4 — EconoMi$er IV Sensor Usage  
Temperature/Resistance Values  
ECONOMI$ER IV WITH OUTDOOR AIR  
DRY BULB SENSOR  
Accessories Required  
APPLICATION  
TEMPERATURE (F)  
RESISTANCE (ohms)  
–58  
–40  
–22  
–4  
14  
32  
50  
68  
77  
86  
104  
122  
140  
158  
176  
185  
194  
212  
230  
248  
257  
266  
284  
302  
200,250  
100,680  
53,010  
29,091  
16,590  
9,795  
5,970  
3,747  
3,000  
2,416  
1,597  
1,080  
746  
Outdoor Air  
Dry Bulb  
None. The outdoor air dry bulb sensor  
is factory installed.  
Differential  
Dry Bulb  
Single Enthalpy  
CRTEMPSN002A00*  
HH57AC078  
HH57AC078  
and  
CRENTDIF004A00*  
Differential  
Enthalpy  
CO2 for DCV  
Control using a  
Wall-Mounted  
CO2 Sensor  
33ZCSENCO2  
CO2 for DCV  
Control using a  
Duct-Mounted  
CO2 Sensor  
33ZCSENCO2†  
and  
CRCBDIOX005A00††  
33ZCASPCO2**  
525  
376  
321  
274  
203  
153  
116  
102  
*CRENTDIF004A00 and CRTEMPSN002A00 accessories are used on many  
different base units. As such, these kits may contain parts that will not be  
needed for installation.  
†33ZCSENCO2 is an accessory CO2 sensor.  
**33ZCASPCO2 is an accessory aspirator box required for duct-mounted appli-  
cations.  
††CRCBDIOX005A00 is an accessory that contains both 33ZCSENCO2 and  
33ZCASPCO2 accessories.  
89  
70  
55  
G. EconoMi$er IV Control Modes  
Determine the EconoMi$er IV control mode before set up of the  
control. Some modes of operation may require different sensors.  
Refer to Table 4. The EconoMi$er IV is supplied from the fac-  
tory with a supply air temperature sensor and an outdoor air  
temperature sensor. This allows for operation of the  
EconoMi$er IV with outdoor air dry bulb changeover control.  
Additional accessories can be added to allow for different  
types of changeover control and operation of the EconoMi$er  
IV and unit.  
Outdoor Dry Bulb Changeover  
The standard controller is shipped from the factory config-  
ured for outdoor dry bulb changeover control. The outdoor  
air and supply air temperature sensors are included as stan-  
dard. For this control mode, the outdoor temperature is com-  
pared to an adjustable set point selected on the control. If the  
outdoor-air temperature is above the set point, the  
EconoMi$er IV will adjust the outside air dampers to mini-  
mum position. If the outdoor-air temperature is below the set  
point, the position of the outdoor-air dampers will be con-  
trolled to provide free cooling using outdoor air. When in this  
mode, the LED next to the free cooling set point potentiome-  
ter will be on. The changeover temperature set point is con-  
trolled by the free cooling set point potentiometer located on  
the control. See Fig. 32. The scale on the potentiometer is A,  
B, C, and D. See Fig. 33 for the corresponding temperature  
changeover values.  
Fig. 32 — EconoMi$er IV Controller Potentiometer  
and LED Locations  
19  
LED ON  
18  
D
17  
LED ON  
LED OFF  
16  
15  
14  
C
LED ON  
LED OFF  
B
Differential Dry Bulb Control  
13  
12  
LED ON  
For differential dry bulb control the standard outdoor dry  
bulb sensor is used in conjunction with an additional acces-  
sory dry bulb sensor (part number CRTEMPSN002A00). The  
accessory sensor must be mounted in the return airstream.  
See Fig. 34. Wiring is provided in the EconoMi$er IV wiring  
harness. See Fig. 27.  
LED OFF  
A
11  
10  
9
LED OFF  
85 90  
95  
100  
50  
55 60  
40 45  
65 70 75 80  
DEGREES FAHRENHEIT  
Fig. 33 — Outdoor Air Temperature  
Changeover Set Points  
In this mode of operation, the outdoor-air temperature is  
compared to the return-air temperature and the lower tem-  
perature airstream is used for cooling. When using this mode  
of changeover control, turn the enthalpy set point potentiom-  
eter fully clockwise to the D setting. See Fig. 32.  
18—  
Exhaust Set Point Adjustment  
ECONOMI$ER IV  
CONTROLLER  
The exhaust set point will determine when the exhaust fan  
runs based on damper position (if accessory power exhaust is  
installed). The set point is modified with the Exhaust Fan  
Set Point (EXH SET) potentiometer. See Fig. 32. The set  
point represents the damper position above which the  
exhaust fans will be turned on. When there is a call for  
exhaust, the EconoMi$er IV controller provides a 45 ± 15  
second delay before exhaust fan activation to allow the  
dampers to open. This delay allows the damper to reach the  
appropriate position to avoid unnecessary fan overload.  
ECONOMI$ER IV  
GROMMET  
Minimum Position Control  
There is a minimum damper position potentiometer on the  
EconoMi$er IV controller. See Fig. 32. The minimum damper  
position maintains the minimum airflow into the building  
during the occupied period.  
RETURN AIR  
SENSOR  
RETURN DUCT  
(FIELD-PROVIDED)  
When using demand ventilation, the minimum damper posi-  
tion represents the minimum ventilation position for VOC  
(volatile organic compound) ventilation requirements. The  
maximum demand ventilation position is used for fully occu-  
pied ventilation.  
Fig. 34 — Return Air Temperature or Enthalpy  
Sensor Mounting Location  
Outdoor Enthalpy Changeover  
For enthalpy control, accessory enthalpy sensor (part num-  
ber HH57AC078) is required. Replace the standard outdoor  
dry bulb temperature sensor with the accessory enthalpy  
sensor in the same mounting location. See Fig. 21. When the  
outdoor air enthalpy rises above the outdoor enthalpy  
changeover set point, the outdoor-air damper moves to its  
minimum position. The outdoor enthalpy changeover set  
point is set with the outdoor enthalpy set point potentiome-  
ter on the EconoMi$er IV controller. The set points are A, B,  
C, and D. See Fig. 35. The factory-installed 620-ohm jumper  
must be in place across terminals SR and SR+ on the  
EconoMi$er IV controller. See Fig. 21 and 36.  
When demand ventilation control is not being used, the min-  
imum position potentiometer should be used to set the occu-  
pied ventilation position. The maximum demand ventilation  
position should be turned fully clockwise.  
Adjust the minimum position potentiometer to allow the  
minimum amount of outdoor air, as required by local codes,  
to enter the building. Make minimum position adjustments  
with at least 10 F temperature difference between the out-  
door and return-air temperatures.  
To determine the minimum position setting, perform the fol-  
lowing procedure:  
1. Calculate the appropriate mixed air temperature  
using the following formula:  
Differential Enthalpy Control  
For differential enthalpy control, the EconoMi$er IV control-  
ler uses two enthalpy sensors (HH57AC078 and  
CRENTDIF004A00), one in the outside air and one in the  
return air duct. The EconoMi$er IV controller compares the  
outdoor air enthalpy to the return air enthalpy to determine  
EconoMi$er IV use. The controller selects the lower enthalpy  
air (return or outdoor) for cooling. For example, when the  
outdoor air has a lower enthalpy than the return air, the  
EconoMi$er IV opens to bring in outdoor air for free cooling.  
OA  
100  
RA  
100  
(TO  
x
) + (TR  
x
) = TM  
TO = Outdoor-Air Temperature  
OA = Percent of Outdoor Air  
TR = Return-Air Temperature  
RA = Percent of Return Air  
TM = Mixed-Air Temperature  
Replace the standard outside air dry bulb temperature sen-  
sor with the accessory enthalpy sensor in the same mounting  
location. See Fig. 21. Mount the return air enthalpy sensor  
in the return air duct. See Fig. 34. Wiring is provided in the  
EconoMi$er IV wiring harness. See Fig. 27. The outdoor  
enthalpy changeover set point is set with the outdoor  
enthalpy set point potentiometer on the EconoMi$er IV con-  
troller. When using this mode of changeover control, turn the  
enthalpy set point potentiometer fully clockwise to the D  
setting.  
As an example, if local codes require 10% outdoor air dur-  
ing occupied conditions, outdoor-air temperature is 60 F,  
and return-air temperature is 75 F.  
(60 x .10) + (75 x .90) = 73.5 F  
2. Disconnect the supply air sensor from terminals T  
and T1.  
3. Ensure that the factory-installed jumper is in place  
across terminals P and P1. If remote damper posi-  
tioning is being used, make sure that the terminals  
are wired according to Fig. 27 and that the minimum  
position potentiometer is turned fully clockwise.  
Indoor Air Quality (IAQ) Sensor Input  
The IAQ input can be used for demand control ventilation  
control based on the level of CO2 measured in the space or  
return air duct.  
4. Connect 24 vac across terminals TR and TR1.  
5. Carefully adjust the minimum position potentiometer  
until the measured mixed air temperature matches  
the calculated value.  
Mount the accessory IAQ sensor according to manufacturer  
specifications. The IAQ sensor should be wired to the AQ and  
AQ1 terminals of the controller. Adjust the DCV potentiome-  
ters to correspond to the DCV voltage output of the indoor air  
quality sensor at the user-determined set point. See Fig. 37.  
6. Reconnect the supply air sensor to terminals T and T1.  
Remote control of the EconoMi$er IV damper is desirable when  
requiring additional temporary ventilation. If a field-supplied  
remote potentiometer (Honeywell part number S963B1128) is  
wired to the EconoMi$er IV controller, the minimum position of  
the damper can be controlled from a remote location.  
If a separate field-supplied transformer is used to power the  
IAQ sensor, the sensor must not be grounded or the  
EconoMi$er IV control board will be damaged.  
19—  
85  
90  
95 100 105 110  
(29) (32) (35) (38) (41) (43)  
CONTROL CONTROL POINT  
CURVE  
APPROX. °F (°C)  
AT 50% RH  
80  
(27)  
A
B
C
D
73 (23)  
70 (21)  
67 (19)  
63 (17)  
75  
(24)  
70  
(21)  
65  
(18)  
60  
(16)  
A
55  
(13)  
B
50  
(10)  
C
45  
(7)  
D
40  
(4)  
35  
(2)  
A
B
C
D
HIGH LIMIT  
CURVE  
35  
40  
45  
50  
55  
60  
65  
70  
75  
80  
85  
90  
95 100 105 110  
(2)  
(4) (7) (10) (13) (16) (18) (21) (24) (27) (29) (32) (35) (38) (41) (43)  
APPROXIMATE DRY BULB TEMPERATURE— °F (°C)  
Fig. 35 — Enthalpy Changeover Set Points  
CO SENSOR MAX RANGE SETTING  
2
TR1  
6000  
5000  
4000  
3000  
2000  
1000  
0
EXH  
Set  
10V  
TR  
N1  
N
2V  
EXH  
24  
Vac  
HOT  
24 Vac  
COM  
P1  
T1  
P
T
Min  
Pos  
800 ppm  
900 ppm  
1000 ppm  
1100 ppm  
_
+
Open  
DCV  
Max  
10V  
1
2
5
2V  
AQ1  
AQ  
SO+  
SO  
SR+  
SR  
DCV  
DCV  
Set  
4
3
2V  
10V  
2
3
4
5
6
7
8
Free  
Cool  
DAMPER VOLTAGE FOR MAX VENTILATION RATE  
EF1  
EF  
C
D
B
Fig. 37 — CO2 Sensor Maximum Range Setting  
A
Fig. 36 — EconoMi$er IV Control  
20—  
To control the minimum damper position remotely, remove  
the factory-installed jumper on the P and P1 terminals on  
the EconoMi$er IV controller. Wire the field-supplied poten-  
tiometer to the P and P1 terminals on the EconoMi$er IV  
controller. See Fig. 36.  
Once base ventilation has been determined, set the mini-  
mum damper position potentiometer to the correct position.  
The same equation can be used to determine the occupied or  
maximum ventilation rate to the building. For example, an  
output of 3.6 volts to the actuator provides a base ventilation  
rate of 5% and an output of 6.7 volts provides the maximum  
ventilation rate of 20% (or base plus 15 cfm per person). Use  
Fig. 37 to determine the maximum setting of the CO2 sensor.  
For example, a 1100 ppm set point relates to a 15 cfm per  
person design. Use the 1100 ppm curve on Fig. 37 to find the  
point when the CO2 sensor output will be 6.7 volts. Line up  
the point on the graph with the left side of the chart to deter-  
mine that the range configuration for the CO2 sensor should  
be 1800 ppm. The EconoMi$er IV controller will output the  
6.7 volts from the CO2 sensor to the actuator when the CO2  
concentration in the space is at 1100 ppm. The DCV set point  
may be left at 2 volts since the CO2 sensor voltage will be  
ignored by the EconoMi$er IV controller until it rises above  
the 3.6 volt setting of the minimum position potentiometer.  
Damper Movement  
Damper movement from full open to full closed (or vice  
versa) takes 21/2 minutes.  
Thermostats  
The EconoMi$er IV control works with conventional thermo-  
stats that have a Y1 (cool stage 1), Y2 (cool stage 2), W1  
(heat stage 1), W2 (heat stage 2), and  
G
(fan). The  
EconoMi$er IV control does not support space temperature  
sensors. Connections are made at the thermostat terminal  
connection board located in the main control box.  
Occupancy Control  
The factory default configuration for the EconoMi$er IV con-  
trol is occupied mode. Occupied status is provided by the  
black jumper from terminal TR to terminal N. When unoccu-  
pied mode is desired, install a field-supplied timeclock func-  
tion in place of the jumper between TR and N. See Fig. 27.  
When the timeclock contacts are closed, the EconoMi$er IV  
control will be in occupied mode. When the timeclock con-  
tacts are open (removing the 24-v signal from terminal N),  
the EconoMi$er IV will be in unoccupied mode.  
Once the fully occupied damper position has been deter-  
mined, set the maximum damper demand control ventilation  
potentiometer to this position. Do not set to the maximum  
position as this can result in over-ventilation to the space  
and potential high-humidity levels.  
CO2 Sensor Configuration  
The CO2 sensor has preset standard voltage settings that  
can be selected anytime after the sensor is powered up. See  
Table 5.  
Demand Controlled Ventilation (DCV)  
When using the EconoMi$er IV for demand controlled venti-  
lation, there are some equipment selection criteria which  
should be considered. When selecting the heat capacity and  
cool capacity of the equipment, the maximum ventilation  
rate must be evaluated for design conditions. The maximum  
damper position must be calculated to provide the desired  
fresh air.  
Use setting 1 or 2 for Bryant equipment. See Table 5.  
1. Press Clear and Mode buttons. Hold at least 5 sec-  
onds until the sensor enters the Edit mode.  
2. Press Mode twice. The STDSET Menu will appear.  
3. Use the Up/Down button to select the preset number.  
See Table 5.  
Typically the maximum ventilation rate will be about 5 to  
10% more than the typical cfm required per person, using  
normal outside air design criteria.  
4. Press Enter to lock in the selection.  
5. Press Mode to exit and resume normal operation.  
A proportional anticipatory strategy should be taken with  
the following conditions: a zone with a large area, varied  
occupancy, and equipment that cannot exceed the required  
ventilation rate at design conditions. Exceeding the required  
ventilation rate means the equipment can condition air at a  
maximum ventilation rate that is greater than the required  
ventilation rate for maximum occupancy. A proportional-  
anticipatory strategy will cause the fresh air supplied to  
increase as the room CO2 level increases even though the  
CO2 set point has not been reached. By the time the CO2  
level reaches the set point, the damper will be at maximum  
ventilation and should maintain the set point.  
The custom settings of the CO2 sensor can be changed any-  
time after the sensor is energized. Follow the steps below to  
change the non-standard settings:  
1. Press Clear and Mode buttons. Hold at least 5 sec-  
onds until the sensor enters the Edit mode.  
2. Press Mode twice. The STDSET Menu will appear.  
3. Use the Up/Down button to toggle to the NONSTD  
menu and press Enter.  
4. Use the Up/Down button to toggle through each of  
the nine variables, starting with Altitude, until the  
desired setting is reached.  
In order to have the CO2 sensor control the economizer  
damper in this manner, first determine the damper voltage  
output for minimum or base ventilation. Base ventilation is  
the ventilation required to remove contaminants during  
unoccupied periods. The following equation may be used to  
determine the percent of outside-air entering the building for  
a given damper position. For best results there should be at  
least a 10 degree difference in outside and return-air tem-  
peratures.  
5. Press Mode to move through the variables.  
6. Press Enter to lock in the selection, then press Mode  
to continue to the next variable.  
Dehumidification of Fresh Air with DCV Control  
Information from ASHRAE indicates that the largest humid-  
ity load on any zone is the fresh air introduced. For some  
applications, a device such as an energy recovery unit is  
added to reduce the moisture content of the fresh air being  
brought into the building when the enthalpy is high. In most  
cases, the normal heating and cooling processes are more  
than adequate to remove the humidity loads for most com-  
mercial applications.  
OA  
100  
RA  
100  
(TO  
x
) + (TR  
x
) = TM  
TO = Outdoor-Air Temperature  
OA = Percent of Outdoor Air  
TR = Return-Air Temperature  
RA = Percent of Return Air  
TM = Mixed-Air Temperature  
If normal rooftop heating and cooling operation is not ade-  
quate for the outdoor humidity level, an energy recovery unit  
and/or a dehumidification option should be considered.  
21—  
Table 5 — CO2 Sensor Standard Settings  
VENTILATION  
RATE  
(cfm/Person)  
CO2  
CONTROL RANGE  
(ppm)  
OPTIONAL  
RELAY SETPOINT  
(ppm)  
RELAY  
HYSTERESIS  
(ppm)  
ANALOG  
OUTPUT  
SETTING  
EQUIPMENT  
OUTPUT  
0-10V  
1
2
3
4
5
6
7
8
9
Proportional  
Proportional  
Exponential  
Proportional  
Proportional  
Exponential  
Exponential  
Proportional  
Proportional  
Any  
Any  
Any  
15  
0-2000  
0-2000  
0-2000  
0-1100  
0- 900  
0-1100  
0- 900  
0-9999  
0-2000  
1000  
1000  
1100  
1100  
900  
50  
50  
4-20 mA  
Interface w/Standard  
2-10V  
7-20 mA  
0-10V  
4-20 mA  
0-10V  
4-20 mA  
0-10V  
4-20 mA  
0-10V  
4-20 mA  
0-10V  
4-20 mA  
0-10V  
4-20 mA  
0-10V  
4-20 mA  
Building Control System  
50  
50  
20  
50  
Economizer  
15  
1100  
900  
50  
20  
50  
Health & Safety  
5000  
700  
500  
50  
Parking/Air Intakes/  
Loading Docks  
LEGEND  
ppm — Parts Per Million  
IX. STEP 9 — ADJUST EVAPORATOR-FAN SPEED  
speed. Increasing fan speed increases load on motor.  
Do not exceed maximum speed specified in Table 1.  
Adjust evaporator-fan speed to meet jobsite conditions.  
Tables 6A and 6B show fan rpm at motor pulley settings for  
standard and alternate motors. Tables 7 and 8 show evapora-  
tor fan motor data. Table 9 shows EconoMi$er IV pressure  
drop. Table 10 shows sound data. Refer to Tables 11-28 for  
fan performance data. See Fig. 38 for Perfect Humidity™ sys-  
tem static pressure drop.  
5. Set movable flange at nearest keyway of pulley hub  
and tighten setscrew. (See Table 1 for speed change  
for each full turn of pulley flange.)  
To align fan and motor pulleys:  
1. Loosen fan pulley setscrews.  
2. Slide fan pulley along fan shaft.  
NOTE: Before adjusting fan speed, make sure the new fan  
speed will provide an acceptable air temperature rise range  
on heating as shown in Table 1.  
3. Make angular alignment by loosening motor from  
mounting plate.  
To adjust belt tension:  
To change fan speed:  
1. Loosen fan motor mounting nuts.  
1. Shut off unit power supply.  
2. Slide motor mounting plate away from fan scroll for  
proper belt tension (1/2-in. deflection with 8 to 10 lb of  
force) and tighten mounting nuts (see Fig. 39).  
2. Loosen belt by loosening fan motor mounting nuts.  
See Fig. 39.  
3. Loosen movable pulley flange setscrew (see Fig. 40).  
3. Adjust bolt and nut on mounting plate to secure  
motor in fixed position.  
4. Screw movable flange toward fixed flange to increase  
fan speed and away from fixed flange to decrease fan  
Table 6A — 581B Fan Rpm at Motor Pulley Setting With Standard Motor*  
MOTOR PULLEY TURNS OPEN  
UNIT  
1
581B  
0
/
1
971  
1102  
1389  
1492  
11/2  
935  
1061  
1354  
1445  
2
898  
1019  
1318  
1399  
21/2  
862  
3
31/2  
789  
4
41/2  
716  
812  
1141  
1166  
5
51/2  
1070  
6
1035  
2
036  
1044  
1185  
1460  
1585  
1008  
1144  
1425  
1538  
826  
936  
1248  
1305  
753  
853  
1177  
1212  
680  
770  
1106  
1119  
048  
060 (single and 3-phase)  
072  
978  
895  
1283  
1352  
1212  
1259  
*Approximate fan rpm shown (standard motor/drive).  
Table 6B — 581B Fan Rpm at Motor Pulley Setting With High-Static Motor*  
MOTOR PULLEY TURNS OPEN  
UNIT  
581B  
1
0
/
2
1
11/2  
2
21/2  
3
31/2  
4
41/2  
5
51/2  
6
036  
048  
060  
072  
1455  
1455  
1685  
1685  
1423  
1423  
1589  
1589  
1392  
1392  
1557  
1557  
1360  
1360  
1525  
1525  
1328  
1328  
1493  
1493  
1297  
1297  
1460  
1460  
1265  
1265  
1428  
1428  
1233  
1233  
1396  
1396  
1202  
1202  
1364  
1364  
1170  
1170  
1332  
1332  
1138  
1138  
1300  
1300  
1107  
1107  
1075  
1075  
*Approximate fan rpm shown (high-static motor/drive).  
22—  
0.35  
0.3  
0.25  
0.2  
0.15  
0.1  
4 & 5 ton  
6 ton  
0.05  
0
3 ton  
4000  
1000  
3000  
2000  
5000  
6000  
0
Fig. 38 — Humidi-MiZer™ Adaptive Dehumidification System Static Pressure Drop (in. wg)  
MOTOR MOUNTING  
PLATE NUTS  
Fig. 39 — Belt-Drive Motor Mounting  
Fig. 40 — Evaporator-Fan Pulley Adjustment  
Table 7 — Evaporator-Fan Motor Data — Standard Motor  
UNIT  
581B  
UNIT  
PHASE  
MAXIMUM  
CONTINUOUS BHP*  
MAXIMUM  
OPERATING WATTS*  
MAXIMUM  
AMP DRAW  
UNIT VOLTAGE  
Single  
Three  
Single  
Three  
Single  
Three  
1.20  
1.20  
1.20  
1.20  
1.30  
2.40  
1000  
1000  
1000  
1000  
1650  
2120  
208/230  
208/230  
460  
4.9  
4.9  
2.2  
2.2  
4.9  
4.9  
2.2  
2.2  
10.1  
6.7  
3.0  
3.0  
6.7  
3.0  
3.0  
036  
048  
575  
208/230  
208/230  
460  
575  
208/230  
208/230  
460  
575  
208/230  
460  
060  
072  
Three  
2.40  
2120  
575  
LEGEND  
Bhp — Brake Horsepower  
*Extensive motor and electrical testing on these units ensures that the  
full horsepower and watts range of the motors can be utilized with con-  
fidence. Using the fan motors up to the ratings shown in this table will  
not result in nuisance tripping or premature motor failure. Unit warranty  
will not be affected.  
23—  
Table 8 — Evaporator-Fan Motor Data — High-Static Motors  
UNIT  
581B  
UNIT  
PHASE  
MAXIMUM  
CONTINUOUS BHP*  
MAXIMUM  
OPERATING WATTS*  
MAXIMUM  
AMP DRAW  
UNIT VOLTAGE  
208/230  
460  
575  
208/230  
460  
575  
208/230  
460  
575  
208/230  
460  
575  
6.7  
3.0  
3.0  
6.7  
3.0  
3.0  
8.6  
3.9  
3.9  
8.6  
3.9  
3.9  
036  
046  
060  
072  
Three  
Three  
Three  
Three  
2.40  
2.40  
2.90  
2.90  
2120  
2120  
2615  
2615  
LEGEND  
Bhp — Brake Horsepower  
*Extensive motor and electrical testing on these units ensures that the  
full horsepower and watts range of the motors can be utilized with con-  
fidence. Using the fan motors up to the ratings shown in this table will  
not result in nuisance tripping or premature motor failure. Unit warranty  
will not be affected.  
Table 9 — Accessory/FIOP EconoMi$er IV Static Pressure* (in. wg)  
CFM  
COMPONENT  
1250  
0.045  
1500  
0.065  
1750  
0.08  
0.1  
2000  
0.12  
0.125  
2250  
0.145  
0.15  
2500  
0.175  
0.18  
2750  
0.22  
0.225  
3000  
0.255  
0.275  
Vertical EconoMi$er IV  
Horizontal EconoMi$er IV  
LEGEND  
FIOP — Factory-Installed Option  
*The static pressure must be added to external static pressure. The  
sum and the evaporator entering-air cfm should be used in conjunction  
with the Fan Performance tables to determine indoor blower rpm and  
watts.  
Table 10 — Outdoor Sound Power (Total Unit)  
OCTAVE BANDS  
ARI RATING  
UNIT  
581B  
(decibels)  
63  
55.9  
59.1  
125  
66.0  
68.9  
250  
64.0  
68.7  
500  
66.2  
71.9  
1000  
68.4  
74.0  
2000  
64.5  
68.9  
4000  
61.7  
65.7  
8000  
57.3  
59.0  
036-048  
060-072  
76  
80  
LEGEND  
Air Conditioning and Refrigeration Institute  
ARI  
Table 11 — Fan Performance 581B036 — Vertical Discharge Units; Standard Motor (Belt Drive)*  
EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
CFM  
0.2  
0.4  
0.6  
0.8  
1.0  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
900  
1000  
1100  
1200  
1300  
1400  
1500  
567  
599  
632  
666  
701  
737  
773  
0.15  
0.18  
0.22  
0.26  
0.31  
0.36  
0.42  
145  
177  
215  
257  
306  
361  
422  
688  
717  
747  
778  
810  
842  
875  
0.22  
0.27  
0.31  
0.37  
0.43  
0.49  
0.57  
222  
265  
313  
367  
426  
491  
564  
786  
814  
842  
871  
901  
931  
963  
0.30  
0.35  
0.41  
0.47  
0.54  
0.62  
0.70  
296  
349  
407  
471  
540  
616  
699  
871  
897  
0.37  
0.43  
0.50  
0.57  
0.65  
0.74  
0.84  
368  
430  
498  
572  
651  
738  
831  
947  
972  
0.44  
0.51  
0.59  
0.67  
0.76  
0.86  
0.96  
437  
509  
587  
670  
760  
856  
960  
925  
999  
952  
981  
1010  
1040  
1025  
1053  
1081  
1110  
EXTERNAL STATIC PRESSURE (in. wg)  
1.6  
AIRFLOW  
CFM  
1.2  
Bhp  
1.4  
Bhp  
1.8  
Bhp  
2.0  
Bhp  
Rpm  
Watts  
Rpm  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Watts  
Rpm  
Watts  
900  
1000  
1100  
1200  
1300  
1400  
1500  
1016  
1041  
1066  
1093  
1119  
1147  
1175  
0.51  
0.59  
0.68  
0.77  
0.87  
0.98  
1.09  
505  
587  
674  
767  
866  
972  
1086  
1080  
1104  
1129  
1155  
1181  
1208  
0.57  
0.67  
0.76  
0.87  
0.98  
1.09  
572  
662  
759  
861  
970  
1086  
1139  
1163  
1188  
1213  
1239  
0.64  
0.74  
0.85  
0.96  
1.08  
637  
737  
843  
955  
1073  
1195  
1219  
1243  
1268  
1294  
0.71  
0.81  
0.93  
1.05  
1.18  
702  
811  
925  
1047  
1175  
1249  
1272  
1296  
1321  
0.77  
0.89  
1.01  
1.14  
765  
883  
1007  
1137  
LEGEND  
Brake Horsepower  
Watts — Input Watts to Motor  
NOTES:  
1. Boldface indicates field-supplied drive is required.  
2. Maximum continuous bhp is 1.20.  
Bhp  
3. See page 33 for general fan performance notes.  
*Motor drive range: 680 to 1044 rpm. All other rpms require field-  
supplied drive.  
24—  
Table 12 — Fan Performance 581B036 — Vertical Discharge Units; High-Static Motor (Belt Drive)*  
EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
CFM  
0.2  
0.4  
0.6  
0.8  
1.0  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
900  
1000  
1100  
1200  
1300  
1400  
1500  
567  
599  
632  
666  
701  
737  
773  
0.15  
0.18  
0.22  
0.26  
0.31  
0.36  
0.42  
145  
177  
215  
257  
306  
361  
422  
688  
717  
747  
778  
810  
842  
875  
0.22  
0.27  
0.31  
0.37  
0.43  
0.49  
0.57  
222  
265  
313  
367  
426  
491  
564  
786  
814  
842  
871  
901  
931  
963  
0.30  
0.35  
0.41  
0.47  
0.54  
0.62  
0.70  
296  
349  
407  
471  
540  
616  
699  
871  
897  
0.37  
0.43  
0.50  
0.57  
0.65  
0.74  
0.84  
368  
430  
498  
572  
651  
738  
831  
947  
972  
0.44  
0.51  
0.59  
0.67  
0.76  
0.86  
0.96  
437  
509  
587  
670  
760  
856  
960  
925  
999  
952  
1025  
1053  
1081  
1110  
981  
1010  
1040  
EXTERNAL STATIC PRESSURE (in. wg)  
1.6  
AIRFLOW  
CFM  
1.2  
Bhp  
1.4  
Bhp  
1.8  
Bhp  
2.0  
Bhp  
Rpm  
Watts  
Rpm  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Watts  
Rpm  
Watts  
900  
1000  
1100  
1200  
1300  
1400  
1500  
1016  
1041  
1066  
1093  
1119  
1147  
1175  
0.51  
0.59  
0.68  
0.77  
0.87  
0.98  
1.09  
505  
587  
674  
767  
866  
972  
1086  
1080  
1104  
1129  
1155  
1181  
1208  
1235  
0.57  
0.67  
0.76  
0.87  
0.98  
1.09  
1.22  
572  
662  
1139  
1163  
1188  
1213  
1239  
1265  
1292  
0.64  
0.74  
0.85  
0.96  
1.08  
1.21  
1.34  
637  
737  
1195  
1219  
1243  
1268  
1294  
1320  
1346  
0.71  
0.81  
0.93  
1.05  
1.18  
1.32  
1.46  
702  
811  
1249  
1272  
1296  
1321  
1346  
1371  
1397  
0.77  
0.89  
1.01  
1.14  
1.28  
1.43  
1.58  
765  
883  
1007  
1137  
1275  
1419  
1572  
759  
843  
925  
861  
970  
1086  
1209  
955  
1047  
1175  
1310  
1452  
1073  
1199  
1332  
LEGEND  
Brake Horsepower  
Watts — Input Watts to Motor  
NOTES:  
1. Boldface indicates field-supplied drive is required.  
2. Maximum continuous bhp is 2.40.  
Bhp  
3. See page 33 for general fan performance notes.  
*Motor drive range: 1075 to 1455 rpm. All other rpms require field-  
supplied drive.  
Table 13 — Fan Performance 581B048 — Vertical Discharge Units; Standard Motor (Belt Drive)*  
EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
CFM  
0.2  
0.4  
0.6  
0.8  
1.0  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
1200  
1300  
1400  
1500  
1600  
1700  
1800  
1900  
2000  
666  
701  
737  
773  
810  
847  
885  
923  
962  
0.26  
0.31  
0.36  
0.42  
0.49  
0.57  
0.66  
0.75  
0.85  
257  
306  
361  
422  
491  
567  
652  
745  
847  
778  
810  
0.37  
0.43  
0.49  
0.57  
0.65  
0.73  
0.83  
0.94  
1.05  
367  
426  
491  
564  
643  
730  
826  
930  
1043  
871  
901  
0.47  
0.54  
0.62  
0.70  
0.79  
0.89  
1.00  
1.11  
471  
540  
616  
699  
790  
888  
994  
1109  
952  
981  
0.57  
0.65  
0.74  
0.84  
0.94  
1.05  
1.16  
572  
651  
738  
831  
932  
1040  
1157  
1025  
1053  
1081  
1110  
1140  
1170  
0.67  
0.76  
0.86  
0.96  
1.08  
1.20  
670  
760  
856  
960  
1070  
1189  
842  
931  
1010  
1040  
1070  
1101  
1133  
875  
963  
994  
1027  
1060  
1093  
909  
943  
978  
1014  
1049  
EXTERNAL STATIC PRESSURE (in. wg)  
1.6  
AIRFLOW  
CFM  
1.2  
Bhp  
1.4  
Bhp  
1.8  
Bhp  
2.0  
Bhp  
Rpm  
Watts  
Rpm  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Watts  
Rpm  
Watts  
1200  
1300  
1400  
1500  
1600  
1700  
1800  
1900  
2000  
1093  
1119  
1147  
1175  
0.77  
0.87  
0.98  
1.09  
767  
866  
972  
1086  
1155  
1181  
1208  
0.87  
0.98  
1.09  
861  
970  
1086  
1213  
1239  
0.96  
1.08  
955  
1073  
1268  
1294  
1.05  
1.18  
1047  
1175  
1321  
1.14  
1137  
LEGEND  
Brake Horsepower  
Watts — Input Watts to Motor  
NOTES:  
1. Boldface indicates field-supplied drive is required.  
2. Maximum continuous bhp is 1.20.  
Bhp  
3. See page 33 for general fan performance notes.  
*Motor drive range: 770 to 1185 rpm. All other rpms require field-  
supplied drive.  
25—  
Table 14 — Fan Performance 581B048 — Vertical Discharge Units; High-Static Motor (Belt Drive)*  
EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
CFM  
0.2  
0.4  
0.6  
0.8  
1.0  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
1200  
1300  
1400  
1500  
1600  
1700  
1800  
1900  
2000  
666  
701  
737  
773  
810  
847  
885  
923  
962  
0.26  
0.31  
0.36  
0.42  
0.49  
0.57  
0.66  
0.75  
0.85  
257  
306  
361  
422  
491  
567  
652  
745  
847  
778  
810  
0.37  
0.43  
0.49  
0.57  
0.65  
0.73  
0.83  
0.94  
1.05  
367  
426  
491  
564  
643  
730  
826  
930  
1043  
871  
901  
0.47  
0.54  
0.62  
0.70  
0.79  
0.89  
1.00  
1.11  
1.24  
471  
540  
952  
981  
0.57  
0.65  
0.74  
0.84  
0.94  
1.05  
1.16  
1.29  
1.42  
572  
651  
1025  
1053  
1081  
1110  
1140  
1170  
1200  
1231  
1263  
0.67  
0.76  
0.86  
0.96  
1.08  
1.20  
1.32  
1.46  
1.61  
670  
760  
842  
931  
616  
1010  
1040  
1070  
1101  
1133  
1165  
1198  
738  
856  
875  
963  
994  
1027  
1060  
1093  
1127  
699  
831  
932  
1040  
1157  
1283  
1417  
960  
909  
790  
1070  
1189  
1316  
1453  
1598  
943  
888  
978  
994  
1014  
1049  
1109  
1233  
EXTERNAL STATIC PRESSURE (in. wg)  
1.6  
AIRFLOW  
CFM  
1.2  
Bhp  
1.4  
Bhp  
1.8  
Bhp  
2.0  
Bhp  
Rpm  
Watts  
Rpm  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Watts  
Rpm  
Watts  
1200  
1300  
1400  
1500  
1600  
1700  
1800  
1900  
2000  
1093  
1119  
1147  
1175  
1204  
1233  
1262  
1293  
1323  
0.77  
0.87  
0.98  
1.09  
1.21  
1.34  
1.48  
1.63  
1.79  
767  
866  
1155  
1181  
1208  
1235  
1263  
1292  
1321  
1350  
1380  
0.87  
0.98  
1.09  
1.22  
1.35  
1.49  
1.64  
1.79  
1.96  
861  
970  
1213  
1239  
1265  
1292  
1320  
1348  
1376  
1405  
1434  
0.96  
1.08  
1.21  
1.34  
1.48  
1.63  
1.79  
1.96  
2.13  
955  
1073  
1199  
1332  
1472  
1622  
1779  
1946  
2123  
1268  
1294  
1320  
1346  
1373  
1401  
1428  
1457  
1486  
1.05  
1.18  
1.32  
1.46  
1.61  
1.77  
1.94  
2.12  
2.31  
1047  
1175  
1310  
1452  
1603  
1762  
1930  
2106  
2293  
1321  
1346  
1371  
1397  
1424  
1451  
1479  
1506  
1.14  
1.28  
1.43  
1.58  
1.74  
1.91  
2.09  
2.28  
1137  
1275  
1419  
1572  
1732  
1901  
2078  
2265  
972  
1086  
1209  
1340  
1480  
1627  
1784  
1950  
1086  
1207  
1336  
1473  
1620  
1776  
LEGEND  
Brake Horsepower  
Watts — Input Watts to Motor  
NOTES:  
1. Boldface indicates field-supplied drive is required.  
2. Maximum continuous bhp is 2.40.  
Bhp  
3. See page 33 for general fan performance notes.  
*Motor drive range: 1075 to 1455 rpm. All other rpms require field-  
supplied drive.  
Table 15 — Fan Performance 581B060, Single-Phase — Vertical Discharge Units;  
Standard Motor (Belt Drive)*  
EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
CFM  
0.2  
Bhp  
0.4  
Bhp  
0.6  
0.8  
1.0  
Rpm  
Watts  
Rpm  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
1500  
1600  
1700  
1800  
1900  
2000  
2100  
2200  
2300  
2400  
2500  
848  
887  
0.42  
0.49  
0.57  
0.65  
0.75  
0.85  
0.97  
1.09  
1.23  
371  
433  
502  
579  
663  
757  
859  
970  
1091  
968  
1004  
1040  
1077  
1115  
1153  
1191  
1230  
0.55  
0.63  
0.71  
0.81  
0.91  
1.03  
1.15  
1.29  
486  
556  
633  
718  
811  
913  
1023  
1143  
1069  
1103  
1137  
1172  
1208  
1244  
0.68  
0.76  
0.86  
0.96  
1.08  
1.20  
600  
678  
763  
856  
957  
1066  
1158  
1190  
1223  
1257  
1291  
0.80  
0.90  
1.00  
1.12  
1.24  
715  
800  
892  
993  
1101  
1238  
1269  
1302  
1334  
0.94  
1.04  
1.15  
1.27  
831  
922  
1022  
1130  
927  
967  
1007  
1048  
1090  
1131  
1173  
EXTERNAL STATIC PRESSURE (in. wg)  
1.6  
AIRFLOW  
CFM  
1.2  
Bhp  
1.4  
Bhp  
1.8  
Bhp  
2.0  
Bhp  
Rpm  
Watts  
Rpm  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Watts  
Rpm  
Watts  
1500  
1600  
1700  
1800  
1900  
2000  
2100  
2200  
2300  
2400  
2500  
1312  
1342  
1374  
1.07  
1.18  
1.30  
948  
1047  
1153  
1380  
1.20  
1067  
LEGEND  
Brake Horsepower  
Watts — Input Watts to Motor  
NOTES:  
1. Boldface indicates field-supplied drive is required.  
2. Maximum continuous bhp is 1.30.  
Bhp  
3. See page 33 for general fan performance notes.  
*Motor drive range: 1035 to 1460 rpm. All other rpms require field-  
supplied drive.  
26—  
Table 16 — Fan Performance 581B060, Three-Phase — Vertical Discharge Units;  
Standard Motor (Belt Drive)*  
EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
CFM  
0.2  
Bhp  
0.4  
Bhp  
0.6  
0.8  
1.0  
Rpm  
Watts  
Rpm  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
1500  
1600  
1700  
1800  
1900  
2000  
2100  
2200  
2300  
2400  
2500  
848  
887  
0.42  
0.49  
0.57  
0.65  
0.75  
0.85  
0.97  
1.09  
1.23  
1.38  
1.54  
371  
433  
968  
1004  
1040  
1077  
1115  
1153  
1191  
1230  
1269  
1309  
1349  
0.55  
0.63  
0.71  
0.81  
0.91  
1.03  
1.15  
1.29  
1.43  
1.59  
1.76  
486  
556  
1069  
1103  
1137  
1172  
1208  
1244  
1281  
1318  
1355  
1393  
1431  
0.68  
0.76  
0.86  
0.96  
1.08  
1.20  
1.33  
1.48  
1.63  
1.80  
1.98  
600  
678  
1158  
1190  
1223  
1257  
1291  
1326  
1361  
1397  
1433  
1470  
1506  
0.80  
0.90  
1.00  
1.12  
1.24  
1.37  
1.51  
1.67  
1.83  
2.01  
2.20  
715  
800  
1238  
1269  
1302  
1334  
1368  
1401  
1435  
1470  
1505  
1540  
0.94  
1.04  
1.15  
1.27  
1.40  
1.54  
1.69  
1.86  
2.03  
2.21  
831  
922  
927  
502  
633  
763  
892  
1022  
1130  
1246  
1371  
1505  
1649  
1803  
1967  
967  
579  
718  
856  
957  
993  
1007  
1048  
1090  
1131  
1173  
1215  
1258  
663  
811  
1101  
1219  
1345  
1481  
1627  
1784  
1951  
757  
913  
1066  
1185  
1313  
1451  
1600  
1759  
859  
1023  
1143  
1273  
1413  
1564  
970  
1091  
1223  
1365  
EXTERNAL STATIC PRESSURE (in. wg)  
1.6  
AIRFLOW  
CFM  
1.2  
Bhp  
1.4  
Bhp  
1.8  
Bhp  
2.0  
Bhp  
Rpm  
Watts  
Rpm  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Watts  
Rpm  
Watts  
1500  
1600  
1700  
1800  
1900  
2000  
2100  
2200  
2300  
2400  
2500  
1312  
1342  
1374  
1406  
1438  
1471  
1504  
1538  
1572  
1.07  
1.18  
1.30  
1.43  
1.57  
1.72  
1.87  
2.04  
2.23  
948  
1047  
1153  
1268  
1391  
1523  
1665  
1816  
1978  
1380  
1411  
1441  
1473  
1504  
1536  
1569  
1602  
1.20  
1.32  
1.45  
1.58  
1.73  
1.89  
2.06  
2.23  
1067  
1173  
1286  
1407  
1537  
1677  
1825  
1984  
1445  
1474  
1505  
1535  
1567  
1598  
1630  
1.34  
1.46  
1.60  
1.74  
1.90  
2.06  
2.24  
1189  
1300  
1420  
1548  
1685  
1831  
1986  
1506  
1535  
1565  
1595  
1626  
1657  
1.48  
1.61  
1.75  
1.90  
2.06  
2.24  
1312  
1429  
1555  
1690  
1833  
1986  
1564  
1593  
1622  
1652  
1682  
1.62  
1.76  
1.91  
2.06  
2.23  
1437  
1560  
1692  
1833  
1983  
LEGEND  
Brake Horsepower  
Watts — Input Watts to Motor  
NOTES:  
1. Boldface indicates field-supplied drive is required.  
2. Maximum continuous bhp is 2.40.  
Bhp  
3. See page 33 for general fan performance notes.  
*Motor drive range: 1035 to 1460 rpm. All other rpms require field-  
supplied drive.  
Table 17 — Fan Performance 581B060 — Vertical Discharge Units; High-Static Motor (Belt Drive)*  
EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
CFM  
0.2  
0.4  
0.6  
0.8  
1.0  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
1500  
1600  
1700  
1800  
1900  
2000  
2100  
2200  
2300  
2400  
2500  
848  
887  
0.42  
0.49  
0.57  
0.65  
0.75  
0.85  
0.97  
1.09  
1.23  
1.38  
1.54  
371  
433  
968  
1004  
1040  
1077  
1115  
1153  
1191  
1230  
1269  
1309  
1349  
0.55  
0.63  
0.71  
0.81  
0.91  
1.03  
1.15  
1.29  
1.43  
1.59  
1.76  
486  
556  
1069  
1103  
1137  
1172  
1208  
1244  
1281  
1318  
1355  
1393  
1431  
0.68  
0.76  
0.86  
0.96  
1.08  
1.20  
1.33  
1.48  
1.63  
1.80  
1.98  
600  
678  
1158  
1190  
1223  
1257  
1291  
1326  
1361  
1397  
1433  
1470  
1506  
0.80  
0.90  
1.00  
1.12  
1.24  
1.37  
1.51  
1.67  
1.83  
2.01  
2.20  
715  
800  
1238  
1269  
1302  
1334  
1368  
1401  
1435  
1470  
1505  
1540  
1576  
0.94  
1.04  
1.15  
1.27  
1.40  
1.54  
1.69  
1.86  
2.03  
2.21  
2.41  
831  
922  
927  
502  
633  
763  
892  
1022  
1130  
1246  
1371  
1505  
1649  
1803  
1967  
2142  
967  
579  
718  
856  
957  
993  
1007  
1048  
1090  
1131  
1173  
1215  
1258  
663  
811  
1101  
1219  
1345  
1481  
1627  
1784  
1951  
757  
913  
1066  
1185  
1313  
1451  
1600  
1759  
859  
1023  
1143  
1273  
1413  
1564  
970  
1091  
1223  
1365  
EXTERNAL STATIC PRESSURE (in. wg)  
1.6  
AIRFLOW  
CFM  
1.2  
Bhp  
1.4  
Bhp  
1.8  
Bhp  
2.0  
Bhp  
Rpm  
Watts  
Rpm  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Watts  
Rpm  
Watts  
1500  
1600  
1700  
1800  
1900  
2000  
2100  
2200  
2300  
2400  
2500  
1312  
1342  
1374  
1406  
1438  
1471  
1504  
1538  
1572  
1607  
1642  
1.07  
1.18  
1.30  
1.43  
1.57  
1.72  
1.87  
2.04  
2.23  
2.42  
2.63  
948  
1047  
1153  
1268  
1391  
1523  
1665  
1816  
1978  
2150  
2333  
1380  
1411  
1441  
1473  
1504  
1536  
1569  
1602  
1635  
1669  
1704  
1.20  
1.32  
1.45  
1.58  
1.73  
1.89  
2.06  
2.23  
2.42  
2.63  
2.84  
1067  
1173  
1286  
1407  
1537  
1677  
1825  
1984  
2153  
2332  
2523  
1445  
1474  
1505  
1535  
1567  
1598  
1630  
1663  
1695  
1729  
1.34  
1.46  
1.60  
1.74  
1.90  
2.06  
2.24  
2.42  
2.62  
2.83  
1189  
1300  
1420  
1548  
1685  
1831  
1986  
2152  
2328  
2515  
1506  
1535  
1565  
1595  
1626  
1657  
1688  
1720  
1753  
1.48  
1.61  
1.75  
1.90  
2.06  
2.24  
2.42  
2.61  
2.82  
1312  
1429  
1555  
1690  
1833  
1986  
2149  
2321  
2504  
1564  
1593  
1622  
1652  
1682  
1713  
1744  
1775  
1.62  
1.76  
1.91  
2.06  
2.23  
2.41  
2.60  
2.81  
1437  
1560  
1692  
1833  
1983  
2142  
2312  
2491  
LEGEND  
Brake Horsepower  
Watts — Input Watts to Motor  
NOTES:  
1. Boldface indicates field-supplied drive is required.  
2. Maximum continuous bhp is 2.90.  
Bhp  
3. See page 33 for general fan performance notes.  
*Motor drive range: 1300 to 1685 rpm. All other rpms require field-  
supplied drive.  
27—  
Table 18 — Fan Performance 581B072 — Vertical Discharge Units; Standard Motor (Belt Drive)*  
EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
CFM  
0.2  
0.4  
0.6  
0.8  
1.0  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
1800  
1900  
2000  
2100  
2200  
2300  
2400  
2500  
2600  
2700  
2800  
2900  
3000  
967  
1008  
1049  
1091  
1133  
1176  
1218  
1261  
1305  
1348  
1392  
1435  
1479  
0.63  
0.72  
0.82  
0.93  
1.05  
1.18  
1.32  
1.47  
1.63  
1.80  
1.99  
2.19  
2.40  
563  
643  
1075  
1112  
1151  
1189  
1229  
1268  
1308  
1349  
1390  
1431  
1472  
0.80  
0.91  
1.02  
1.14  
1.26  
1.40  
1.55  
1.72  
1.89  
2.07  
2.27  
715  
805  
1170  
1205  
1241  
1278  
1315  
1352  
1390  
1429  
1468  
1507  
0.97  
1.08  
1.20  
1.33  
1.47  
1.62  
1.78  
1.96  
2.14  
2.33  
861  
960  
1255  
1289  
1323  
1358  
1393  
1429  
1466  
1503  
1540  
1.13  
1.25  
1.38  
1.52  
1.67  
1.84  
2.01  
2.19  
2.38  
1002  
1111  
1228  
1353  
1487  
1630  
1782  
1945  
2117  
1333  
1366  
1399  
1433  
1467  
1501  
1537  
1.28  
1.42  
1.56  
1.71  
1.87  
2.04  
2.23  
1139  
1258  
1384  
1519  
1662  
1815  
1977  
731  
903  
1068  
1183  
1308  
1441  
1584  
1736  
1900  
2073  
827  
933  
1008  
1123  
1247  
1380  
1523  
1677  
1841  
2016  
1047  
1170  
1304  
1448  
1602  
1768  
1945  
2135  
EXTERNAL STATIC PRESSURE (in. wg)  
1.6  
AIRFLOW  
CFM  
1.2  
Bhp  
1.4  
Bhp  
1.8  
Bhp  
2.0  
Bhp  
Rpm  
Watts  
Rpm  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Watts  
Rpm  
Watts  
1800  
1900  
2000  
2100  
2200  
2300  
2400  
2500  
2600  
2700  
2800  
2900  
3000  
1406  
1438  
1470  
1502  
1535  
1569  
1.43  
1.58  
1.73  
1.89  
2.06  
2.25  
1273  
1401  
1537  
1681  
1834  
1996  
1475  
1505  
1537  
1568  
1600  
1.58  
1.73  
1.90  
2.07  
2.25  
1403  
1541  
1686  
1840  
2002  
1540  
1569  
1600  
1631  
1.72  
1.89  
2.06  
2.25  
1531  
1678  
1833  
1996  
1601  
1630  
1660  
1.87  
2.04  
2.23  
1657  
1813  
1977  
1660  
1689  
1718  
2.00  
2.19  
2.38  
1780  
1945  
2118  
LEGEND  
Brake Horsepower  
Watts — Input Watts to Motor  
NOTES:  
1. Boldface indicates field-supplied drive is required.  
2. Maximum continuous bhp is 2.40.  
Bhp  
3. See page 33 for general fan performance notes.  
*Motor drive range: 1119 to 1585 rpm. All other rpms require field-  
supplied drive.  
Table 19 — Fan Performance 581B072 — Vertical Discharge Units; High-Static Motor (Belt Drive)*  
EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
CFM  
0.2  
Bhp  
0.4  
Bhp  
0.6  
0.8  
1.0  
Rpm  
Watts  
Rpm  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
1800  
1900  
2000  
2100  
2200  
2300  
2400  
2500  
2600  
2700  
2800  
2900  
3000  
967  
1008  
1049  
1091  
1133  
1176  
1218  
1261  
1305  
1348  
1392  
1435  
1479  
0.63  
0.72  
0.82  
0.93  
1.05  
1.18  
1.32  
1.47  
1.63  
1.80  
1.99  
2.19  
2.40  
563  
643  
1075  
1112  
1151  
1189  
1229  
1268  
1308  
1349  
1390  
1431  
1472  
1514  
1556  
0.80  
0.91  
1.02  
1.14  
1.26  
1.40  
1.55  
1.72  
1.89  
2.07  
2.27  
2.48  
2.70  
715  
805  
1170  
1205  
1241  
1278  
1315  
1352  
1390  
1429  
1468  
1507  
1547  
1587  
0.97  
1.08  
1.20  
1.33  
1.47  
1.62  
1.78  
1.96  
2.14  
2.33  
2.54  
2.76  
861  
960  
1255  
1289  
1323  
1358  
1393  
1429  
1466  
1503  
1540  
1578  
1616  
1.13  
1.25  
1.38  
1.52  
1.67  
1.84  
2.01  
2.19  
2.38  
2.59  
2.81  
1002  
1111  
1228  
1353  
1487  
1630  
1782  
1945  
2117  
2301  
2495  
1333  
1366  
1399  
1433  
1467  
1501  
1537  
1572  
1608  
1645  
1.28  
1.42  
1.56  
1.71  
1.87  
2.04  
2.23  
2.42  
2.62  
2.84  
1139  
1258  
1384  
1519  
1662  
1815  
1977  
2149  
2331  
2524  
731  
903  
1068  
1183  
1308  
1441  
1584  
1736  
1900  
2073  
2258  
2455  
827  
933  
1008  
1123  
1247  
1380  
1523  
1677  
1841  
2016  
2203  
2402  
1047  
1170  
1304  
1448  
1602  
1768  
1945  
2135  
EXTERNAL STATIC PRESSURE (in. wg)  
1.6  
AIRFLOW  
CFM  
1.2  
Bhp  
1.4  
Bhp  
1.8  
Bhp  
2.0  
Bhp  
Rpm  
Watts  
Rpm  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Watts  
Rpm  
Watts  
1800  
1900  
2000  
2100  
2200  
2300  
2400  
2500  
2600  
2700  
2800  
2900  
3000  
1406  
1438  
1470  
1502  
1535  
1569  
1603  
1638  
1673  
1.43  
1.58  
1.73  
1.89  
2.06  
2.25  
2.44  
2.64  
2.86  
1273  
1401  
1537  
1681  
1834  
1996  
2167  
2349  
2541  
1475  
1505  
1537  
1568  
1600  
1633  
1666  
1700  
1.58  
1.73  
1.90  
2.07  
2.25  
2.45  
2.65  
2.87  
1403  
1541  
1686  
1840  
2002  
2174  
2355  
2546  
1540  
1569  
1600  
1631  
1662  
1694  
1727  
1.72  
1.89  
2.06  
2.25  
2.44  
2.64  
2.86  
1531  
1678  
1833  
1996  
2167  
2348  
2539  
1601  
1630  
1660  
1690  
1721  
1752  
1.87  
2.04  
2.23  
2.42  
2.62  
2.84  
1657  
1813  
1977  
2149  
2330  
2520  
1660  
1689  
1718  
1747  
1778  
2.00  
2.19  
2.38  
2.59  
2.80  
1780  
1945  
2118  
2300  
2490  
LEGEND  
Brake Horsepower  
Watts — Input Watts to Motor  
NOTES:  
1. Boldface indicates field-supplied drive is required.  
2. Maximum continuous bhp is 2.90.  
Bhp  
3. See page 33 for general fan performance notes.  
*Motor drive range: 1300 to 1685 rpm. All other rpms require field-  
supplied drive.  
28—  
Table 20 — Fan Performance 581B036 — Horizontal Discharge Units; Standard Motor (Belt Drive)*  
EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
CFM  
0.2  
0.4  
0.6  
0.8  
1.0  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
900  
1000  
1100  
1200  
1300  
1400  
1500  
553  
582  
612  
643  
675  
707  
740  
0.14  
0.16  
0.20  
0.23  
0.28  
0.33  
0.38  
134  
163  
196  
234  
277  
326  
382  
681  
707  
734  
762  
790  
819  
849  
0.22  
0.26  
0.30  
0.34  
0.40  
0.45  
0.52  
221  
257  
297  
343  
394  
452  
515  
782  
807  
833  
859  
886  
913  
941  
0.32  
0.36  
0.41  
0.46  
0.52  
0.58  
0.66  
316  
358  
405  
458  
517  
581  
653  
870  
894  
919  
944  
969  
996  
1023  
0.42  
0.47  
0.52  
0.58  
0.65  
0.72  
0.80  
417  
466  
519  
579  
644  
716  
795  
948  
971  
0.53  
0.58  
0.64  
0.71  
0.78  
0.86  
0.95  
526  
580  
639  
705  
777  
855  
941  
995  
1020  
1044  
1070  
1096  
EXTERNAL STATIC PRESSURE (in. wg)  
1.6  
AIRFLOW  
CFM  
1.2  
Bhp  
1.4  
Bhp  
1.8  
Bhp  
2.0  
Bhp  
Rpm  
Watts  
Rpm  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Watts  
Rpm  
Watts  
900  
1000  
1100  
1200  
1300  
1400  
1500  
1019  
1042  
1065  
1089  
1113  
1138  
1163  
0.64  
0.70  
0.77  
0.84  
0.92  
1.01  
1.10  
640  
700  
1084  
1107  
1130  
1153  
1177  
1201  
0.76  
0.83  
0.90  
0.98  
1.06  
1.15  
760  
825  
896  
974  
1058  
1149  
1146  
1168  
1190  
1213  
0.89  
0.96  
1.04  
1.12  
885  
956  
1032  
1115  
1203  
1225  
1247  
1.02  
1.10  
1.18  
1016  
1091  
1173  
1258  
1.16  
1152  
765  
837  
915  
1000  
1092  
LEGEND  
Brake Horsepower  
Watts — Input Watts to Motor  
NOTES:  
1. Boldface indicates field-supplied drive is required.  
2. Maximum continuous bhp is 1.20.  
Bhp  
3. See page 33 for general fan performance notes.  
*Motor drive range: 680 to 1044 rpm. All other rpms require field-  
supplied drive.  
Table 21 — Fan Performance 581B036 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*  
EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
CFM  
0.2  
0.4  
0.6  
0.8  
1.0  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
900  
1000  
1100  
1200  
1300  
1400  
1500  
553  
582  
612  
643  
675  
707  
740  
0.14  
0.16  
0.20  
0.23  
0.28  
0.33  
0.38  
134  
163  
196  
234  
277  
326  
382  
681  
707  
734  
762  
790  
819  
849  
0.22  
0.26  
0.30  
0.34  
0.40  
0.45  
0.52  
221  
257  
297  
343  
394  
452  
515  
782  
807  
833  
859  
886  
913  
941  
0.32  
0.36  
0.41  
0.46  
0.52  
0.58  
0.66  
316  
358  
405  
458  
517  
581  
653  
870  
894  
919  
944  
969  
996  
1023  
0.42  
0.47  
0.52  
0.58  
0.65  
0.72  
0.80  
417  
466  
519  
579  
644  
716  
795  
948  
971  
0.53  
0.58  
0.64  
0.71  
0.78  
0.86  
0.95  
526  
580  
639  
705  
777  
855  
941  
995  
1020  
1044  
1070  
1096  
EXTERNAL STATIC PRESSURE (in. wg)  
1.6  
AIRFLOW  
CFM  
1.2  
Bhp  
1.4  
Bhp  
1.8  
Bhp  
2.0  
Bhp  
Rpm  
Watts  
Rpm  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Watts  
Rpm  
Watts  
900  
1000  
1100  
1200  
1300  
1400  
1500  
1019  
1042  
1065  
1089  
1113  
1138  
1163  
0.64  
0.70  
0.77  
0.84  
0.92  
1.01  
1.10  
640  
700  
1084  
1107  
1130  
1153  
1177  
1201  
1226  
0.76  
0.83  
0.90  
0.98  
1.06  
1.15  
1.25  
760  
825  
1146  
1168  
1190  
1213  
1237  
1261  
1285  
0.89  
0.96  
1.04  
1.12  
1.21  
1.31  
1.41  
885  
956  
1032  
1115  
1205  
1303  
1407  
1203  
1225  
1247  
1270  
1293  
1317  
1341  
1.02  
1.10  
1.18  
1.27  
1.36  
1.47  
1.58  
1016  
1091  
1173  
1262  
1358  
1461  
1571  
1258  
1279  
1301  
1324  
1347  
1370  
1394  
1.16  
1.24  
1.33  
1.42  
1.52  
1.63  
1.75  
1152  
1232  
1319  
1413  
1514  
1623  
1740  
765  
896  
837  
915  
1000  
1092  
974  
1058  
1149  
1247  
LEGEND  
Brake Horsepower  
Watts — Input Watts to Motor  
NOTES:  
1. Boldface indicates field-supplied drive is required.  
2. Maximum continuous bhp is 2.40.  
Bhp  
3. See page 33 for general fan performance notes.  
*Motor drive range: 1075 to 1455 rpm. All other rpms require field-  
supplied drive.  
29—  
Table 22 — Fan Performance 581B048 — Horizontal Discharge Units; Standard Motor (Belt Drive)*  
EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
CFM  
0.2  
0.4  
0.6  
0.8  
1.0  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
1200  
1300  
1400  
1500  
1600  
1700  
1800  
1900  
2000  
643  
675  
707  
740  
773  
807  
841  
875  
910  
0.23  
0.28  
0.33  
0.38  
0.45  
0.52  
0.59  
0.68  
0.77  
234  
277  
326  
382  
444  
513  
589  
674  
767  
762  
790  
819  
849  
879  
910  
942  
974  
1006  
0.34  
0.40  
0.45  
0.52  
0.59  
0.67  
0.75  
0.85  
0.95  
343  
394  
452  
515  
586  
663  
749  
842  
944  
859  
886  
0.46  
0.52  
0.58  
0.66  
0.73  
0.82  
0.91  
1.02  
1.13  
458  
517  
944  
969  
0.58  
0.65  
0.72  
0.80  
0.88  
0.98  
1.08  
1.19  
579  
644  
716  
795  
880  
973  
1074  
1184  
1020  
1044  
1070  
1096  
1123  
1150  
0.71  
0.78  
0.86  
0.95  
1.04  
1.14  
705  
777  
855  
941  
1034  
1134  
913  
581  
996  
941  
653  
1023  
1050  
1078  
1106  
1135  
970  
731  
999  
817  
1029  
1059  
1090  
910  
1012  
1122  
EXTERNAL STATIC PRESSURE (in. wg)  
1.6  
AIRFLOW  
CFM  
1.2  
Bhp  
1.4  
Bhp  
1.8  
Bhp  
2.0  
Bhp  
Rpm  
Watts  
Rpm  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Watts  
Rpm  
Watts  
1200  
1300  
1400  
1500  
1600  
1700  
1800  
1900  
2000  
1089  
1113  
1138  
1163  
1189  
0.84  
0.92  
1.01  
1.10  
1.20  
837  
915  
1000  
1092  
1191  
1153  
1177  
1201  
0.98  
1.06  
1.15  
974  
1058  
1149  
1213  
1.12  
1115  
LEGEND  
Brake Horsepower  
Watts — Input Watts to Motor  
NOTES:  
1. Boldface indicates field-supplied drive is required.  
2. Maximum continuous bhp is 1.20.  
Bhp  
3. See page 33 for general fan performance notes.  
*Motor drive range: 770 to 1185 rpm. All other rpms require field-  
supplied drive.  
Table 23 — Fan Performance 581B048 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*  
EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
CFM  
0.2  
0.4  
0.6  
0.8  
1.0  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
1200  
1300  
1400  
1500  
1600  
1700  
1800  
1900  
2000  
643  
675  
707  
740  
773  
807  
841  
875  
910  
0.23  
0.28  
0.33  
0.38  
0.45  
0.52  
0.59  
0.68  
0.77  
234  
277  
326  
382  
444  
513  
589  
674  
767  
762  
790  
819  
849  
879  
910  
942  
974  
1006  
0.34  
0.40  
0.45  
0.52  
0.59  
0.67  
0.75  
0.85  
0.95  
343  
394  
452  
515  
586  
663  
749  
842  
944  
859  
886  
0.46  
0.52  
0.58  
0.66  
0.73  
0.82  
0.91  
1.02  
1.13  
458  
517  
944  
969  
0.58  
0.65  
0.72  
0.80  
0.88  
0.98  
1.08  
1.19  
1.31  
579  
644  
1020  
1044  
1070  
1096  
1123  
1150  
1177  
1205  
1234  
0.71  
0.78  
0.86  
0.95  
1.04  
1.14  
1.25  
1.37  
1.49  
705  
777  
913  
581  
996  
716  
855  
941  
653  
1023  
1050  
1078  
1106  
1135  
1165  
795  
941  
970  
731  
880  
1034  
1134  
1242  
1360  
1485  
999  
817  
973  
1029  
1059  
1090  
910  
1074  
1184  
1302  
1012  
1122  
EXTERNAL STATIC PRESSURE (in. wg)  
1.6  
AIRFLOW  
CFM  
1.2  
Bhp  
1.4  
Bhp  
1.8  
Bhp  
2.0  
Bhp  
Rpm  
Watts  
Rpm  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Watts  
Rpm  
Watts  
1200  
1300  
1400  
1500  
1600  
1700  
1800  
1900  
2000  
1089  
1113  
1138  
1163  
1189  
1216  
1242  
1270  
1297  
0.84  
0.92  
1.01  
1.10  
1.20  
1.31  
1.42  
1.55  
1.68  
837  
915  
1153  
1177  
1201  
1226  
1252  
1277  
1303  
1330  
1357  
0.98  
1.06  
1.15  
1.25  
1.36  
1.48  
1.60  
1.73  
1.87  
974  
1058  
1149  
1247  
1353  
1468  
1590  
1721  
1862  
1213  
1237  
1261  
1285  
1310  
1335  
1361  
1387  
1414  
1.12  
1.21  
1.31  
1.41  
1.53  
1.65  
1.78  
1.92  
2.07  
1115  
1205  
1303  
1407  
1520  
1640  
1770  
1908  
2055  
1270  
1293  
1317  
1341  
1365  
1390  
1415  
1441  
1467  
1.27  
1.36  
1.47  
1.58  
1.70  
1.83  
1.96  
2.11  
2.26  
1262  
1358  
1461  
1571  
1690  
1817  
1953  
2098  
2252  
1324  
1347  
1370  
1394  
1418  
1442  
1467  
1493  
1.42  
1.52  
1.63  
1.75  
1.87  
2.01  
2.15  
2.30  
1413  
1514  
1623  
1740  
1865  
1998  
2140  
2292  
1000  
1092  
1191  
1299  
1414  
1538  
1672  
LEGEND  
Brake Horsepower  
Watts — Input Watts to Motor  
NOTES:  
1. Boldface indicates field-supplied drive is required.  
2. Maximum continuous bhp is 2.40.  
Bhp  
3. See page 33 for general fan performance notes.  
*Motor drive range: 1075 to 1455 rpm. All other rpms require field-  
supplied drive.  
30—  
Table 24 — Fan Performance 581B060, Single-Phase — Horizontal Discharge Units;  
Standard Motor (Belt Drive)*  
EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
CFM  
0.2  
Bhp  
0.4  
Bhp  
0.6  
0.8  
1.0  
Rpm  
Watts  
Rpm  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
1500  
1600  
1700  
1800  
1900  
2000  
2100  
2200  
2300  
2400  
2500  
800  
839  
879  
919  
960  
1001  
1043  
1085  
1127  
0.39  
0.46  
0.54  
0.63  
0.73  
0.84  
0.96  
1.09  
1.23  
350  
412  
483  
561  
648  
744  
850  
966  
1092  
904  
938  
974  
1010  
1047  
1085  
1123  
1162  
0.49  
0.57  
0.65  
0.75  
0.85  
0.96  
1.09  
1.22  
438  
505  
580  
663  
754  
855  
965  
1086  
999  
1030  
1062  
1095  
1129  
1163  
1199  
0.60  
0.68  
0.77  
0.87  
0.98  
1.09  
1.22  
535  
605  
684  
771  
867  
972  
1086  
1087  
1115  
1144  
1174  
1206  
1238  
0.72  
0.80  
0.90  
1.00  
1.11  
1.23  
640  
714  
796  
886  
986  
1095  
1169  
1195  
1221  
1250  
1279  
0.85  
0.93  
1.03  
1.14  
1.25  
753  
829  
914  
1008  
1111  
EXTERNAL STATIC PRESSURE (in. wg)  
1.6  
AIRFLOW  
CFM  
1.2  
Bhp  
1.4  
Bhp  
1.8  
Bhp  
2.0  
Bhp  
Rpm  
Watts  
Rpm  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Watts  
Rpm  
Watts  
1500  
1600  
1700  
1800  
1900  
2000  
2100  
2200  
2300  
2400  
2500  
1247  
1270  
1295  
1321  
0.98  
1.07  
1.17  
1.28  
873  
952  
1040  
1137  
1320  
1342  
1.13  
1.22  
1002  
1083  
1390  
1.28  
1137  
LEGEND  
Brake Horsepower  
Watts — Input Watts to Motor  
NOTES:  
1. Boldface indicates field-supplied drive is required.  
2. Maximum continuous bhp is 1.30.  
Bhp  
3. See page 33 for general fan performance notes.  
*Motor drive range: 1035 to 1460 rpm. All other rpms require field-  
supplied drive.  
Table 25 — Fan Performance 581B060, Three-Phase — Horizontal Discharge Units;  
Standard Motor (Belt Drive)*  
EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
CFM  
0.2  
Bhp  
0.4  
Bhp  
0.6  
0.8  
1.0  
Rpm  
Watts  
Rpm  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
1500  
1600  
1700  
1800  
1900  
2000  
2100  
2200  
2300  
2400  
2500  
800  
839  
0.39  
0.46  
0.54  
0.63  
0.73  
0.84  
0.96  
1.09  
1.23  
1.38  
1.55  
350  
412  
904  
938  
0.49  
0.57  
0.65  
0.75  
0.85  
0.96  
1.09  
1.22  
1.37  
1.53  
1.70  
438  
505  
999  
1030  
1062  
1095  
1129  
1163  
1199  
1235  
1272  
1310  
1348  
0.60  
0.68  
0.77  
0.87  
0.98  
1.09  
1.22  
1.36  
1.52  
1.68  
1.86  
535  
605  
1087  
1115  
1144  
1174  
1206  
1238  
1271  
1305  
1340  
1375  
1412  
0.72  
0.80  
0.90  
1.00  
1.11  
1.23  
1.37  
1.51  
1.67  
1.84  
2.02  
640  
714  
1169  
1195  
1221  
1250  
1279  
1309  
1340  
1372  
1405  
1439  
1473  
0.85  
0.93  
1.03  
1.14  
1.25  
1.38  
1.52  
1.67  
1.83  
2.00  
2.19  
753  
829  
879  
483  
974  
580  
684  
796  
914  
919  
960  
561  
1010  
1047  
1085  
1123  
1162  
1201  
1241  
1281  
663  
771  
886  
986  
1008  
1111  
1224  
1346  
1479  
1623  
1778  
1945  
648  
754  
867  
1001  
1043  
1085  
1127  
1169  
1212  
744  
855  
972  
1095  
1213  
1342  
1482  
1633  
1796  
850  
965  
1086  
1211  
1347  
1493  
1652  
966  
1086  
1217  
1359  
1513  
1092  
1229  
1378  
EXTERNAL STATIC PRESSURE (in. wg)  
1.6  
AIRFLOW  
CFM  
1.2  
Bhp  
1.4  
Bhp  
1.8  
Bhp  
2.0  
Bhp  
Rpm  
Watts  
Rpm  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Watts  
Rpm  
Watts  
1500  
1600  
1700  
1800  
1900  
2000  
2100  
2200  
2300  
2400  
2500  
1247  
1270  
1295  
1321  
1348  
1377  
1406  
1437  
1468  
1500  
1533  
0.98  
1.07  
1.17  
1.28  
1.40  
1.53  
1.67  
1.83  
1.99  
2.17  
2.36  
873  
952  
1320  
1342  
1365  
1390  
1415  
1442  
1470  
1499  
1529  
1559  
1.13  
1.22  
1.32  
1.43  
1.56  
1.69  
1.83  
1.99  
2.16  
2.35  
1002  
1083  
1173  
1273  
1381  
1500  
1629  
1769  
1920  
2083  
1390  
1411  
1432  
1455  
1479  
1505  
1531  
1559  
1587  
1.28  
1.37  
1.48  
1.59  
1.72  
1.86  
2.00  
2.16  
2.34  
1137  
1221  
1313  
1415  
1526  
1648  
1780  
1923  
2077  
1457  
1476  
1497  
1518  
1541  
1565  
1591  
1617  
1.44  
1.54  
1.64  
1.76  
1.89  
2.03  
2.18  
2.34  
1280  
1365  
1459  
1563  
1677  
1801  
1936  
2082  
1522  
1540  
1559  
1579  
1601  
1624  
1648  
1.61  
1.71  
1.82  
1.93  
2.06  
2.21  
2.36  
1430  
1517  
1612  
1718  
1834  
1961  
2098  
1040  
1137  
1243  
1359  
1485  
1621  
1769  
1928  
2098  
LEGEND  
Brake Horsepower  
Watts — Input Watts to Motor  
NOTES:  
1. Boldface indicates field-supplied drive is required.  
2. Maximum continuous bhp is 2.40.  
Bhp  
3. See page 33 for general fan performance notes.  
*Motor drive range: 1035 to 1460 rpm. All other rpms require field-  
supplied drive.  
31—  
Table 26 — Fan Performance 581B060 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*  
EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
CFM  
0.2  
0.4  
0.6  
0.8  
1.0  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
1500  
1600  
1700  
1800  
1900  
2000  
2100  
2200  
2300  
2400  
2500  
800  
839  
0.39  
0.46  
0.54  
0.63  
0.73  
0.84  
0.96  
1.09  
1.23  
1.38  
1.55  
350  
412  
904  
938  
0.49  
0.57  
0.65  
0.75  
0.85  
0.96  
1.09  
1.22  
1.37  
1.53  
1.70  
438  
505  
999  
1030  
1062  
1095  
1129  
1163  
1199  
1235  
1272  
1310  
1348  
0.60  
0.68  
0.77  
0.87  
0.98  
1.09  
1.22  
1.36  
1.52  
1.68  
1.86  
535  
605  
1087  
1115  
1144  
1174  
1206  
1238  
1271  
1305  
1340  
1375  
1412  
0.72  
0.80  
0.90  
1.00  
1.11  
1.23  
1.37  
1.51  
1.67  
1.84  
2.02  
640  
714  
1169  
1195  
1221  
1250  
1279  
1309  
1340  
1372  
1405  
1439  
1473  
0.85  
0.93  
1.03  
1.14  
1.25  
1.38  
1.52  
1.67  
1.83  
2.00  
2.19  
753  
829  
879  
483  
974  
580  
684  
796  
914  
919  
960  
561  
1010  
1047  
1085  
1123  
1162  
1201  
1241  
1281  
663  
771  
886  
986  
1008  
1111  
1224  
1346  
1479  
1623  
1778  
1945  
648  
754  
867  
1001  
1043  
1085  
1127  
1169  
1212  
744  
855  
972  
1095  
1213  
1342  
1482  
1633  
1796  
850  
965  
1086  
1211  
1347  
1493  
1652  
966  
1086  
1217  
1359  
1513  
1092  
1229  
1378  
EXTERNAL STATIC PRESSURE (in. wg)  
1.6  
AIRFLOW  
CFM  
1.2  
Bhp  
1.4  
Bhp  
1.8  
Bhp  
2.0  
Bhp  
Rpm  
Watts  
Rpm  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Watts  
Rpm  
Watts  
1500  
1600  
1700  
1800  
1900  
2000  
2100  
2200  
2300  
2400  
2500  
1247  
1270  
1295  
1321  
1348  
1377  
1406  
1437  
1468  
1500  
1533  
0.98  
1.07  
1.17  
1.28  
1.40  
1.53  
1.67  
1.83  
1.99  
2.17  
2.36  
873  
952  
1320  
1342  
1365  
1390  
1415  
1442  
1470  
1499  
1529  
1559  
1591  
1.13  
1.22  
1.32  
1.43  
1.56  
1.69  
1.83  
1.99  
2.16  
2.35  
2.54  
1002  
1083  
1173  
1273  
1381  
1500  
1629  
1769  
1920  
2083  
2257  
1390  
1411  
1432  
1455  
1479  
1505  
1531  
1559  
1587  
1616  
1647  
1.28  
1.37  
1.48  
1.59  
1.72  
1.86  
2.00  
2.16  
2.34  
2.53  
2.73  
1137  
1221  
1313  
1415  
1526  
1648  
1780  
1923  
2077  
2243  
2421  
1457  
1476  
1497  
1518  
1541  
1565  
1591  
1617  
1644  
1672  
1.44  
1.54  
1.64  
1.76  
1.89  
2.03  
2.18  
2.34  
2.52  
2.71  
1280  
1365  
1459  
1563  
1677  
1801  
1936  
2082  
2239  
2408  
1522  
1540  
1559  
1579  
1601  
1624  
1648  
1673  
1699  
1726  
1.61  
1.71  
1.82  
1.93  
2.06  
2.21  
2.36  
2.53  
2.71  
2.90  
1430  
1517  
1612  
1718  
1834  
1961  
2098  
2246  
2406  
2579  
1040  
1137  
1243  
1359  
1485  
1621  
1769  
1928  
2098  
LEGEND  
Brake Horsepower  
Watts — Input Watts to Motor  
NOTES:  
1. Boldface indicates field-supplied drive is required.  
2. Maximum continuous bhp is 2.90.  
Bhp  
3. See page 33 for general fan performance notes.  
*Motor drive range: 1300 to 1685 rpm. All other rpms require field-  
supplied drive.  
Table 27 — Fan Performance 581B072 — Horizontal Discharge Units; Standard Motor (Belt Drive)*  
EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
CFM  
0.2  
Bhp  
0.4  
Bhp  
0.6  
0.8  
1.0  
Rpm  
Watts  
Rpm  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
1800  
1900  
2000  
2100  
2200  
2300  
2400  
2500  
2600  
2700  
2800  
2900  
3000  
913  
952  
0.64  
0.73  
0.84  
0.95  
1.07  
1.21  
1.36  
1.51  
1.69  
1.87  
2.07  
2.28  
569  
652  
1010  
1046  
1083  
1120  
1158  
1196  
1234  
1273  
1312  
1352  
1392  
0.80  
0.91  
1.02  
1.14  
1.27  
1.41  
1.57  
1.73  
1.91  
2.10  
2.31  
715  
805  
1098  
1131  
1166  
1200  
1236  
1272  
1308  
1345  
1382  
1420  
0.98  
1.09  
1.21  
1.33  
1.47  
1.62  
1.78  
1.96  
2.14  
2.34  
869  
965  
1178  
1210  
1242  
1275  
1308  
1343  
1377  
1412  
1448  
1.16  
1.28  
1.40  
1.54  
1.68  
1.84  
2.01  
2.19  
2.38  
1032  
1134  
1245  
1365  
1495  
1634  
1784  
1945  
2117  
1252  
1282  
1313  
1345  
1377  
1409  
1443  
1.35  
1.48  
1.61  
1.75  
1.90  
2.07  
2.24  
1203  
1311  
1427  
1553  
1689  
1834  
1990  
992  
744  
903  
1070  
1184  
1307  
1440  
1584  
1738  
1904  
2081  
1032  
1073  
1114  
1155  
1196  
1238  
1280  
1322  
1364  
844  
954  
1010  
1127  
1254  
1391  
1538  
1697  
1867  
2050  
1074  
1204  
1345  
1497  
1660  
1835  
2023  
EXTERNAL STATIC PRESSURE (in. wg)  
1.6  
AIRFLOW  
CFM  
1.2  
Bhp  
1.4  
Bhp  
1.8  
Bhp  
2.0  
Bhp  
Rpm  
Watts  
Rpm  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Watts  
Rpm  
Watts  
1800  
1900  
2000  
2100  
2200  
2300  
2400  
2500  
2600  
2700  
2800  
2900  
3000  
1322  
1351  
1380  
1411  
1441  
1473  
1.56  
1.68  
1.82  
1.97  
2.13  
2.30  
1382  
1495  
1617  
1748  
1890  
2041  
1388  
1416  
1444  
1473  
1503  
1.77  
1.90  
2.04  
2.20  
2.36  
1568  
1686  
1814  
1950  
2097  
1451  
1477  
1505  
1.98  
2.12  
2.27  
1762  
1885  
2017  
1510  
1536  
2.21  
2.35  
1962  
2090  
LEGEND  
Brake Horsepower  
Watts — Input Watts to Motor  
NOTES:  
1. Boldface indicates field-supplied drive is required.  
2. Maximum continuous bhp is 2.40.  
Bhp  
3. See page 33 for general fan performance notes.  
*Motor drive range: 1119 to 1585 rpm. All other rpms require field-  
supplied drive.  
32—  
Table 28 — Fan Performance 581B072 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*  
EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
CFM  
0.2  
0.4  
0.6  
0.8  
1.0  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Bhp  
Watts  
1800  
1900  
2000  
2100  
2200  
2300  
2400  
2500  
2600  
2700  
2800  
2900  
3000  
913  
952  
0.64  
0.73  
0.84  
0.95  
1.07  
1.21  
1.36  
1.51  
1.69  
1.87  
2.07  
2.28  
2.50  
569  
652  
1010  
1046  
1083  
1120  
1158  
1196  
1234  
1273  
1312  
1352  
1392  
1432  
1472  
0.80  
0.91  
1.02  
1.14  
1.27  
1.41  
1.57  
1.73  
1.91  
2.10  
2.31  
2.53  
2.76  
715  
805  
1098  
1131  
1166  
1200  
1236  
1272  
1308  
1345  
1382  
1420  
1458  
1496  
0.98  
1.09  
1.21  
1.33  
1.47  
1.62  
1.78  
1.96  
2.14  
2.34  
2.56  
2.78  
869  
965  
1178  
1210  
1242  
1275  
1308  
1343  
1377  
1412  
1448  
1484  
1521  
1.16  
1.28  
1.40  
1.54  
1.68  
1.84  
2.01  
2.19  
2.38  
2.59  
2.81  
1032  
1134  
1245  
1365  
1495  
1634  
1784  
1945  
2117  
2300  
2496  
1252  
1282  
1313  
1345  
1377  
1409  
1443  
1477  
1511  
1546  
1.35  
1.48  
1.61  
1.75  
1.90  
2.07  
2.24  
2.43  
2.63  
2.84  
1203  
1311  
1427  
1553  
1689  
1834  
1990  
2157  
2335  
2526  
992  
744  
903  
1070  
1184  
1307  
1440  
1584  
1738  
1904  
2081  
2270  
2472  
1032  
1073  
1114  
1155  
1196  
1238  
1280  
1322  
1364  
1406  
844  
954  
1010  
1127  
1254  
1391  
1538  
1697  
1867  
2050  
2245  
2452  
1074  
1204  
1345  
1497  
1660  
1835  
2023  
2224  
EXTERNAL STATIC PRESSURE (in. wg)  
1.6  
AIRFLOW  
CFM  
1.2  
Bhp  
1.4  
Bhp  
1.8  
Bhp  
2.0  
Bhp  
Rpm  
Watts  
Rpm  
Watts  
Rpm  
Bhp  
Watts  
Rpm  
Watts  
Rpm  
Watts  
1800  
1900  
2000  
2100  
2200  
2300  
2400  
2500  
2600  
2700  
2800  
2900  
3000  
1322  
1351  
1380  
1411  
1441  
1473  
1505  
1537  
1571  
1.56  
1.68  
1.82  
1.97  
2.13  
2.30  
2.48  
2.68  
2.88  
1382  
1495  
1617  
1748  
1890  
2041  
2203  
2376  
2560  
1388  
1416  
1444  
1473  
1503  
1533  
1564  
1.77  
1.90  
2.04  
2.20  
2.36  
2.54  
2.73  
1568  
1686  
1814  
1950  
2097  
2254  
2422  
1451  
1477  
1505  
1533  
1562  
1591  
1.98  
2.12  
2.27  
2.43  
2.60  
2.79  
1762  
1885  
2017  
2159  
2311  
2474  
1510  
1536  
1563  
1590  
1618  
2.21  
2.35  
2.51  
2.67  
2.85  
1962  
2090  
2227  
2374  
2532  
1568  
1593  
1619  
2.44  
2.59  
2.75  
2169  
2302  
2443  
LEGEND  
Brake Horsepower  
Watts — Input Watts to Motor  
NOTES:  
1. Boldface indicates field-supplied drive is required.  
2. Maximum continuous bhp is 2.90.  
Bhp  
3. See below for general fan performance notes.  
*Motor drive range: 1300 to 1686 rpm. All other rpms require field-  
supplied drive.  
GENERAL FAN PERFORMANCE NOTES  
1. Values include losses for filters, unit casing, and wet coils. See Fig. 38 and  
Table 9 for accessory/FIOP static pressure information.  
2. Extensive motor and electrical testing on these units ensures that the full range  
of the motor can be utilized with confidence. Using the fan motors up to  
the ratings shown will not result in nuisance tripping or premature motor failure.  
Unit warranty will not be affected. See Tables 7 and 8 for additional information.  
3. Use of a field-supplied motor may affect wire sizing. Contact your Bryant repre-  
sentative to verify.  
4. Interpolation is permissible. Do not extrapolate.  
33—  
PRE-START-UP  
START-UP  
I. UNIT PREPARATION  
WARNING: Failure to observe the following warn-  
ings could result in serious personal injury.  
Make sure that unit has been installed in accordance with  
installation instructions and applicable codes.  
1. Follow recognized safety practices and wear  
protective goggles when checking or servicing  
refrigerant system.  
II. GAS PIPING  
Check gas piping for leaks.  
2. Do not operate compressor or provide any elec-  
tric power to unit unless compressor terminal  
cover is in place and secured.  
WARNING: Disconnect gas piping from unit when  
1
leak testing at pressure greater than  
sures greater than /2 psig will cause gas valve damage  
/
psig. Pres-  
2
1
3. Do not remove compressor terminal cover until  
all electrical sources are disconnected.  
resulting in hazardous condition. If gas valve is sub-  
1
jected to pressure greater than  
/
psig, it must be  
2
4. Relieve all pressure from system before touch-  
ing or disturbing anything inside terminal box  
if refrigerant leak is suspected around compres-  
sor terminals.  
replaced before use. When pressure testing field-  
1
supplied gas piping at pressures of  
/
2
psig or less, a  
unit connected to such piping must be isolated by man-  
ually closing the gas valve.  
5. Never attempt to repair soldered connection  
while refrigerant system is under pressure.  
III. RETURN-AIR FILTERS  
Make sure correct filters are installed in unit (see Table 1). Do  
not operate unit without return-air filters.  
6. Do not use torch to remove any component. Sys-  
tem contains oil and refrigerant under pres-  
sure. To remove a component, wear protective  
goggles and proceed as follows:  
IV. OUTDOOR-AIR INLET SCREENS  
Outdoor-air inlet screen must be in place before operating  
unit.  
a. Shut off electrical power and then gas to  
unit.  
b. Recover refrigerant to relieve all pressure  
from system using both high-pressure and  
low-pressure ports.  
c. Cut component connection tubing with tub-  
ing cutter and remove component from  
unit.  
d. Carefully unsweat remaining tubing stubs  
when necessary. Oil can ignite when  
exposed to torch flame.  
V. COMPRESSOR MOUNTING  
Compressors are internally spring mounted. Do not loosen or  
remove compressor holddown bolts.  
VI. INTERNAL WIRING  
Check all electrical connections in unit control boxes.  
Tighten as required.  
VII. REFRIGERANT SERVICE PORTS  
Each unit system has 4 Schrader-type service ports: one on  
the suction line, one on the liquid line, and 2 on the compres-  
sor discharge line. Be sure that caps on the ports are tight.  
Two additional Schrader valves are located under the high-  
pressure and low-pressure switches, respectively.  
Proceed as follows to inspect and prepare the unit for initial  
start-up:  
1. Remove all access panels.  
2. Read and follow instructions on all WARNING, CAU-  
TION, and INFORMATION labels attached to, or  
shipped with, unit.  
VIII. HIGH FLOW REFRIGERANT VALVES  
Two high flow valves are located on the hot gas tube coming  
out of the compressor and the suction tube going into the  
compressor. Large black plastic caps identify these valves.  
These valves have O-rings inside which screw the cap onto a  
brass body to prevent leaks. No field access to these valves is  
available at this time. Ensure the plastic caps remain on the  
valves and are tight or the possibility of refrigerant leakage  
could occur.  
3. Make the following inspections:  
a. Inspect for shipping and handling damages such  
as broken lines, loose parts, or disconnected  
wires, etc.  
b. Inspect for oil at all refrigerant tubing connec-  
tions and on unit base. Detecting oil generally  
indicates a refrigerant leak. Leak-test all refrig-  
erant tubing connections using electronic leak  
detector, halide torch, or liquid-soap solution.  
c. Inspect all field-wiring and factory-wiring con-  
nections. Be sure that connections are completed  
and tight. Be sure that wires are not in contact  
with refrigerant tubing or sharp edges.  
IX. COMPRESSOR ROTATION  
On 3-phase units with scroll compressors, it is important to  
be certain compressor is rotating in the proper direction. To  
determine whether or not compressor is rotating in the  
proper direction:  
d. Inspect coil fins. If damaged during shipping and  
handling, carefully straighten fins with a fin  
comb.  
1. Connect service gages to suction and discharge pres-  
sure fittings.  
2. Energize the compressor.  
4. Verify the following conditions:  
3. The suction pressure should drop and the discharge  
pressure should rise, as is normal on any start-up.  
a. Make sure that condenser-fan blade are correctly  
positioned in fan orifice. See Condenser-Fan  
Adjustment section on page 38 for more details.  
b. Make sure that air filter(s) is in place.  
c. Make sure that condensate drain trap is filled  
with water to ensure proper drainage.  
If the suction pressure does not drop and the discharge pres-  
sure does not rise to normal levels:  
1. Note that the evaporator fan (size 060 and 072 only)  
is probably also rotating in the wrong direction.  
d. Make sure that all tools and miscellaneous loose  
parts have been removed.  
2. Turn off power to the unit and install lockout tag.  
34—  
3. Reverse any two of the unit power leads.  
Table 29B — Altitude Compensation* —  
581B036-072 Low NOx Units  
4. Reenergize to the compressor. Check pressures.  
60,000 AND 90,000 BTUH  
NOMINAL INPUT  
120,000 BTUH  
NOMINAL INPUT  
The suction and discharge pressure levels should now move  
to their normal start-up levels.  
ELEVATION  
(Ft)  
Natural  
Gas  
Orifice  
Size†  
Liquid  
Propane  
Orifice  
Size†  
Natural  
Liquid  
Propane  
Orifice  
Size†  
Gas  
Orifice  
Size†  
NOTE: When the compressor is rotating in the wrong direc-  
tion, the unit will make an elevated level of noise and will  
not provide cooling.  
0-2,000  
2,000  
3,000  
4,000  
5,000  
6,000  
7,000  
8,000  
9,000  
10,000  
11,000  
12,000  
13,000  
14,000  
38  
40  
41  
42  
43  
43  
44  
45  
46  
47  
48  
49  
50  
51  
45  
47  
48  
49  
49  
50  
50  
51  
52  
52  
53  
53  
54  
54  
32  
33  
35  
36  
37  
38  
39  
41  
42  
43  
44  
44  
46  
47  
42  
43  
43  
44  
45  
45  
46  
47  
48  
49  
50  
51  
52  
52  
X. COOLING  
Set space thermostat to OFF position. To start unit, turn on  
main power supply. Set system selector switch at COOL  
position and fan switch at AUTO. position. Adjust thermo-  
stat to a setting below room temperature. Compressor starts  
on closure of contactor.  
Check unit charge. Refer to Refrigerant Charge section on  
page 38.  
Reset thermostat at a position above room temperature.  
Compressor will shut off. Evaporator fan will shut off after a  
30-second delay.  
*As the height above sea level increases, there is less oxygen per cubic foot of  
air. Therefore, heat input rate should be reduced at higher altitudes.  
†Orifice available through your local Bryant distributor.  
A. To Shut Off Unit  
XII. HEATING  
Set system selector switch at OFF position. Resetting ther-  
mostat at a position above room temperature shuts unit off  
temporarily until space temperature exceeds thermostat  
setting. Units are equipped with Cycle-LOC™ protection  
device. Unit shuts down on any safety trip, and indicator  
light on thermostat comes on. Check reason for all safety  
trips.  
1. Purge gas supply line of air by opening union ahead  
of the gas valve. If gas odor is detected, tighten union  
and wait 5 minutes before proceeding.  
2. Turn on electrical supply and manual gas valve.  
3. Set system switch selector at HEAT position and fan  
switch at AUTO. or ON position. Set heating temper-  
ature lever above room temperature.  
Compressor restart is accomplished by manual reset at the  
thermostat by turning the selector switch to OFF and then to  
ON position.  
4. The induced-draft motor will start.  
5. After a call for heating, the main burners should light  
within 5 seconds. If the burner does not light, then there  
is a 22-second delay before another 5-second try. If the  
burner still does not light, the time delay is repeated. If  
the burner does not light within 15 minutes, there is a  
lockout. To reset the control, break the 24-v power to W1.  
XI. MAIN BURNERS  
Main burners are factory set and should require no  
adjustment.  
TO CHECK ignition of main burners and heating controls,  
move thermostat set point above room temperature and ver-  
ify that the burners light and evaporator fan is energized.  
Check heating effect, then lower the thermostat setting  
below the room temperature and verify that the burners and  
evaporator fan turn off.  
6. The evaporator-fan motor will turn on 45 seconds  
after burner ignition.  
7. The evaporator-fan motor will turn off in 45 seconds  
after the thermostat temperature is satisfied.  
8. Adjust airflow to obtain a temperature rise within  
the range specified on the unit nameplate.  
Refer to Tables 29A and 29B for the correct orifice to use at  
high altitudes.  
NOTE: The default value for the evaporator-fan motor on/off  
delay is 45 seconds. The Integrated Gas Unit Controller (IGC)  
modifies this value when abnormal limit switch cycles occur.  
Based upon unit operating conditions, the on delay can be  
reduced to 0 seconds and the off delay can be extended to 180  
seconds. When one flash of the LED (light-emitting diode) is  
observed, the evaporator-fan on/off delay has been modified.  
Table 29A — Altitude Compensation* —  
581B036-072 Standard Units  
72,000 AND 115,000 BTUH  
NOMINAL INPUT  
150,000 BTUH  
NOMINAL INPUT  
ELEVATION  
(Ft)  
Natural  
Gas  
Liquid  
Propane  
Orifice  
Size†  
Natural  
Liquid  
Propane  
Orifice  
Size†  
Gas  
Orifice  
Size†  
Orifice  
Size†  
If the limit switch trips at the start of the heating cycle dur-  
ing the evaporator on delay, the time period of the on delay  
for the next cycle will be 5 seconds less than the time at  
which the switch tripped. (Example: If the limit switch trips  
at 30 seconds, the evaporator-fan on delay for the next cycle  
will occur at 25 seconds.) To prevent short-cycling, a 5-second  
reduction will only occur if a minimum of 10 minutes has  
elapsed since the last call for heating.  
0-2,000  
2,000  
3,000  
4,000  
5,000  
6,000  
7,000  
8,000  
9,000  
10,000  
11,000  
12,000  
13,000  
14,000  
33  
36  
36  
37  
38  
40  
41  
42  
43  
44  
45  
46  
47  
48  
43  
44  
45  
45  
46  
47  
48  
49  
50  
50  
51  
52  
52  
53  
30  
31  
31  
32  
32  
34  
35  
36  
37  
39  
41  
42  
43  
44  
38  
39  
40  
41  
42  
43  
43  
44  
45  
46  
47  
48  
49  
50  
The evaporator-fan off delay can also be modified. Once the  
call for heating has ended, there is a 10-minute period dur-  
ing which the modification can occur. If the limit switch trips  
during this period, the evaporator-fan off delay will increase  
by 15 seconds. A maximum of 9 trips can occur, extending  
the evaporator-fan off delay to 180 seconds.  
*As the height above sea level increases, there is less oxygen per cubic foot of  
air. Therefore, heat input rate should be reduced at higher altitudes.  
†Orifice available through your local Bryant distributor.  
To restore the original default value, reset the power to the  
unit.  
35—  
A. To Shut Off Unit  
decreases because of the increase in fresh air, the outdoor-air  
damper will be proportionally closed. Damper position will  
follow the higher demand condition from DCV mode or free  
cooling mode.  
Set system selector switch at off position. Resetting heating  
selector lever below room temperature will temporarily shut  
unit off until space temperature falls below thermostat setting.  
Damper movement from full closed to full open (or vice  
versa) will take between 11/2 and 21/2 minutes.  
XIII. SAFETY RELIEF  
A soft-solder joint at the suction service Schrader port  
provides pressure relief under abnormal temperature and  
pressure conditions.  
If free cooling can be used as determined from the appropri-  
ate changeover command (switch, dry bulb, enthalpy curve,  
differential dry bulb, or differential enthalpy), a call for cool-  
ing (Y1 closes at the thermostat) will cause the control to  
modulate the dampers open to maintain the supply air tem-  
perature set point at 50 to 55 F.  
XIV. VENTILATION (Continuous Fan)  
Set fan and system selector switches at ON and OFF posi-  
tions, respectively. Evaporator fan operates continuously to  
provide constant air circulation. When the evaporator-fan  
selector switch is turned to the OFF position, there is a  
30-second delay before the fan turns off.  
As the supply-air temperature drops below the set point range  
of 50 to 55 F, the control will modulate the outdoor-air damp-  
ers closed to maintain the proper supply-air temperature.  
D. Heating, Units With EconoMi$er IV  
XV. OPERATING SEQUENCE  
When the room temperature calls for heat, the heating con-  
trols are energized as described in the Heating, Units With-  
out Economizer section. When the thermostat is satisfied,  
the economizer damper moves to the minimum position.  
A. Cooling, Units Without Economizer  
When thermostat calls for cooling, terminals G and Y1 and  
the compressor contactor (C) are energized. The indoor  
(evaporator) fan motor (IFM), compressor, and outdoor (con-  
denser) fan motor (OFM) start. The OFM runs continuously  
while the unit is in cooling. When the thermostat is satisfied,  
C is deenergized and the compressor and OFM shut off. After  
a 30-second delay, the IFM shuts off. If the thermostat fan  
selector switch is in the ON position, the evaporator motor  
will run continuously.  
E. Units With Perfect Humidity™ Dehumidification  
System  
Normal Design Cooling Operation  
When the rooftop operates under the normal sequence of  
operation, the compressors will cycle to maintain indoor con-  
ditions. See Fig. 41.  
B. Heating, Units Without Economizer  
The Perfect Humidity adaptive dehumidification system  
includes a factory-installed Motormaster® low ambient con-  
trol to keep the head and suction pressure high, allowing  
normal design cooling mode operation down to 0° F.  
When the thermostat calls for heating, terminal W1 is ener-  
gized. The induced-draft motor is energized and the burner  
ignition sequence begins. The indoor (evaporator) fan motor  
(IFM) is energized 45 seconds after a flame is ignited. When  
additional heat is needed, W2 is energized and the high-fire  
solenoid on the main gas valve (MGV) is energized. When  
the thermostat is satisfied and W1 is deenergized, the IFM  
stops after a 45-second time-off delay.  
Subcooling Mode  
When subcooling mode is initiated, this will energize (close)  
the liquid line solenoid valve (LLSV) forcing the hot liquid  
refrigerant to enter the subcooling coil (see Fig. 42).  
As the hot liquid refrigerant passes through the subcooling/  
reheat dehumidification coil, it is exposed to the cold supply  
airflow coming through the evaporator coil. The liquid is fur-  
ther subcooled to a temperature approaching the evaporator  
leaving-air temperature. The liquid then enters a thermostatic  
expansion valve (TXV) where the liquid drops to a lower pres-  
sure. The TXV does not have a pressure drop great enough to  
change the liquid to a 2-phase fluid, so the liquid then enters  
the Acutrol™ device at the evaporator coil.  
C. Cooling, Units With EconoMi$er IV  
When free cooling is not available, the compressors will be  
controlled by the zone thermostat. When free cooling is avail-  
able, the outdoor-air damper is modulated by the  
EconoMi$er IV control to provide a 50 to 55 F supply-air  
temperature into the zone. As the supply-air temperature  
fluctuates above 55 or below 50 F, the dampers will be modu-  
lated (open or close) to bring the supply-air temperature  
back within the set points.  
The liquid enters the evaporator coil at a temperature lower  
than in standard cooling operation. This lower temperature  
increases the latent capacity of the rooftop unit. The refriger-  
ant passes through the evaporator and is turned into a  
vapor. The air passing over the evaporator coil will become  
colder than during normal operation. However, as this same  
air passes over the subcooling coil, it will be slightly warmed,  
partially reheating the air.  
Integrated EconoMi$er IV operation on single-stage units  
requires a 2-stage thermostat (Y1 and Y2).  
For EconoMi$er IV operation, there must be a thermostat  
call for the fan (G). This will move the damper to its mini-  
mum position during the occupied mode.  
If the increase in cooling capacity causes the supply-air tem-  
perature to drop below 45 F, then the outdoor-air damper  
position will be fully closed. If the supply-air temperature  
continues to fall, the outdoor-air damper will close. Control  
returns to normal once the supply-air temperature rises  
above 48 F.  
Subcooling mode operates only when the outside-air temper-  
ature is warmer than 40 F. A factory-installed temperature  
switch located in the condenser section will lock out subcool-  
ing mode when the outside temperature is cooler than 40 F.  
The scroll compressors are equipped with crankcase heaters  
to provide protection for the compressors due to the addi-  
tional refrigerant charge required by the subcooling/reheat  
coil.  
If optional power exhaust is installed, as the outdoor-air  
damper opens and closes, the power exhaust fans will be  
energized and deenergized.  
If field-installed accessory CO2 sensors are connected to the  
EconoMi$er IV control, a demand controlled ventilation  
strategy will begin to operate. As the CO2 level in the zone  
increases above the CO2 set point, the minimum position of  
the damper will be increased proportionally. As the CO2 level  
When in subcooling mode, there is a slight decrease in sys-  
tem total gross capacity (5% less), a lower gross sensible  
capacity (20% less), and a greatly increased latent capacity  
(up to 40% more).  
36—  
Hot Gas Reheat Mode  
When the humidity levels in the space require humidity con-  
trol, a hot gas solenoid valve (specific to hot gas reheat mode  
only) will open to bypass a portion of hot gas refrigerant  
around the condenser coil (see Fig. 43).  
This hot gas will mix with liquid refrigerant leaving the con-  
denser coil and flow to the subcooling/reheat dehumidification  
coil. Now the conditioned air coming off the evaporator will be  
cooled and dehumidified, but will be warmed to neutral conditions  
(72 F to 75 F) by the subcooling/reheat dehumidification coil.  
The net effect of the rooftop when in hot gas reheat mode is to  
provide nearly all latent capacity removal from the space when  
sensible loads diminish (when outdoor temperature conditions are  
moderate). When in hot gas reheat mode, the unit will operate to  
provide mostly latent capacity and extremely low sensible heat  
ratio capability.  
Similar to the subcooling mode of operation, hot gas reheat  
mode operates only when the outside-air temperature is warmer  
than 40 F. Below this temperature, a factory-installed outside air  
temperature switch will lock out this mode of operation.  
Fig. 42 — Perfect Humidity Subcooling  
Mode Operation  
See Table 30 for the dehumidification system sequence of  
operation.  
Fig. 43 — Perfect Humidity Hot Gas  
Reheat Mode Operation  
Fig. 41 — Perfect Humidity™ Normal  
Design Cooling Operation  
Table 30 — Perfect Humidity Dehumidification System Sequence of Operation and  
System Response — Single Compressor Unit  
THERMOSTAT INPUT  
ECONOMIZER FUNCTION  
581B UNIT OPERATION  
Subcooling Mode Hot Gas Reheat Mode  
H
Y1  
Y2  
OAT. < Economizer Set Point  
Economizer  
Comp. 1  
Normal Operation  
Off  
On  
On  
On  
On  
On  
On  
On  
On  
On  
Off  
On  
Off  
On  
Off  
Off  
No  
No  
Yes  
Yes  
No  
Off  
Off  
On  
On  
Off  
On  
On  
On  
On  
On  
Yes  
Yes  
Yes  
No  
No  
No  
No  
Yes  
Yes  
No  
LEGEND  
OAT — Outdoor Air Temperature  
NOTE: On a thermostat call for W1, all cooling and dehumidification will  
be off.  
37—  
SERVICE  
D. Filters  
Clean or replace at start of each heating and cooling season,  
or more often if operating conditions require it. Replacement  
filters must be same dimensions as original filters.  
CAUTION: When servicing unit, shut off all elec-  
trical power to unit and install lockout tag to avoid  
shock hazard or injury from rotating parts.  
E. Outdoor-Air Inlet Screens  
Clean screen with steam or hot water and a mild detergent.  
Do not use disposable filters in place of screen.  
I. CLEANING  
Inspect unit interior at the beginning of heating and cooling  
season and as operating conditions require.  
II. LUBRICATION  
A. Compressors  
A. Evaporator Coil  
Each compressor is charged with correct amount of oil at the  
factory.  
1. Turn unit power off, tag disconnect. Remove evapora-  
tor coil access panel.  
B. Fan Motor Bearings  
2. If economizer or two-position damper is installed,  
remove economizer by disconnecting Molex plug and  
removing mounting screws. Refer to accessory econo-  
mizer installation instructions or Optional EconoMi$er  
IV section on page 15 for additional information.  
Fan motor bearings are of the permanently lubricated type.  
No further lubrication is required. No lubrication of con-  
denser-fan or evaporator-fan motors is required.  
III. CONDENSER-FAN ADJUSTMENT (Fig. 47)  
3. Slide filters out of unit.  
Shut off unit power supply. Remove condenser-fan assembly  
(grille, motor, motor cover, and fan) and loosen fan hub  
setscrews. Adjust fan height as shown in Fig. 47. Tighten  
setscrews and replace condenser-fan assembly.  
4. Clean coil using a commercial coil cleaner or dish-  
washer detergent in a pressurized spray canister.  
Wash both sides of coil and flush with clean water.  
For best results, back-flush toward return-air section  
to remove foreign material. Flush condensate pan  
after completion.  
IV. ECONOMI$ER IV ADJUSTMENT  
Refer to Optional EconoMi$er IV section on page 15.  
5. Reinstall economizer and filters.  
6. Reconnect wiring.  
V. EVAPORATOR FAN BELT INSPECTION  
Check condition of evaporator belt or tension during heating  
and cooling inspections or as conditions require. Replace belt  
or adjust as necessary.  
7. Replace access panels.  
B. Condenser Coil  
Inspect coil monthly. Clean condenser coil annually, and as  
required by location and outdoor air conditions.  
VI. HIGH-PRESSURE SWITCH  
The high-pressure switch contains a Schrader core depressor,  
and is located on the compressor hot gas line. This switch  
opens at 428 psig and closes at 320 psig. No adjustments are  
necessary.  
One-Row Coil  
Wash coil with commercial coil cleaner. It is not necessary to  
remove top panel.  
2-Row Coils  
VII. LOSS-OF-CHARGE SWITCH  
Clean coil as follows:  
The loss-of-charge switch contains a Schrader core depressor,  
and is located on the compressor liquid line. This switch opens  
at 7 psig and closes at 22 psig. No adjustments are necessary.  
1. Turn off unit power, tag disconnect.  
2. Remove top panel screws on condenser end of unit.  
VIII. FREEZE-STAT  
3. Remove condenser coil corner post. See Fig. 44. To  
hold top panel open, place coil corner post between  
top panel and center post. See Fig. 45.  
The freeze-stat is a bimetal temperature-sensing switch that  
is located on the hair-pin” end of the evaporator coil. The  
switch protects the evaporator coil from freeze-up due to lack  
of airflow. The switch opens at 30 F and closes at 45 F. No  
adjustments are necessary.  
4. Remove screws securing coil to compressor plate and  
compressor access panel.  
5. Remove fastener holding coil sections together at  
return end of condenser coil. Carefully separate the  
outer coil section 3 to 4 in. from the inner coil section.  
See Fig. 46.  
IX. REFRIGERANT CHARGE  
Amount of refrigerant charge is listed on unit nameplate  
(also refer to Table 1). Refer to HVAC Servicing Procedures  
literature available at your local distributor and the follow-  
ing procedures.  
6. Use a water hose or other suitable equipment to flush  
down between the 2 coil sections to remove dirt and  
debris. Clean the outer surfaces with a stiff brush in  
the normal manner.  
Unit panels must be in place when unit is operating during  
charging procedure. Unit must operate  
10 minutes before checking or adjusting refrigerant charge.  
a
minimum of  
7. Secure inner and outer coil rows together with a field-  
supplied fastener.  
An accurate superheat, thermocouple-type or thermistor-  
type thermometer, and a gage manifold are required when  
using the superheat charging method for evaluating the unit  
charge. Do not use mercury or small dial-type thermometers  
because they are not adequate for this type of measurement.  
8. Reposition the outer coil section and remove the coil  
corner post from between the top panel and center  
post. Reinstall the coil corner post and replace all  
screws.  
C. Condensate Drain  
Check and clean each year at start of cooling season. In win-  
ter, keep drain dry or protect against freeze-up.  
38—  
A. No Charge  
Use standard evacuating techniques. After evacuating sys-  
tem to 500 microns, weigh in the specified amount of refrig-  
erant. (Refer to Table 1 and unit information plate.)  
B. Low Charge Cooling  
Using Cooling Charging Charts, Fig. 48-51, vary refrigerant  
until the conditions of the charts are met. Note the charging  
charts are different from type normally used. Charts are  
based on charging the units to the correct superheat for the  
various operating conditions. Accurate pressure gage and  
temperature sensing device are required. Connect the  
pressure gage to the service port on the suction line. Mount  
the temperature sensing device on the suction line and  
insulate it so that outdoor ambient temperature does not  
affect the reading. Indoor-air cfm must be within the normal  
operating range of the unit.  
Fig. 44 — Cleaning Condenser Coil  
C. Perfect Humidity™ System Charging  
The system charge for units with the Perfect Humidity system  
is greater than that of the standard unit alone. The charge for  
units with this option is indicated on the unit nameplate  
drawing. Also refer to Fig. 52-55. To charge systems using the  
Perfect Humidity Dehumidification system, fully evacuate,  
recover, and recharge the system to the unit information plate  
specified charge level.  
To check or adjust refrigerant charge on systems using the Per-  
fect Humidity Dehumidification system, charge per Fig. 52-55.  
NOTE: When using the charging charts, it is important that  
only the subcooling/reheat dehumidification coil liquid line  
solenoid valve be energized. The subcooling/reheat dehumid-  
ification coil liquid line solenoid valve MUST be energized to  
use the charging charts and the outdoor motor speed control-  
ler jumpered to run the fan at full speed.  
Fig. 45 — Propping Up Top Panel  
The charts reference a liquid pressure (psig) and tempera-  
ture at  
a
point between the condenser coil and the  
subcooling/reheat dehumidification coil. A tap is provided on  
the unit to measure liquid pressure entering the subcooling/  
reheat dehumidification coil.  
IMPORTANT: The subcooling mode charging charts  
(Fig. 52-55) are to be used ONLY with units having the  
optional Perfect Humidity subcooling option. DO NOT use  
standard charge (Fig. 48-51) for units with Perfect Humidity  
system, and DO NOT use Fig. 52-55 for standard units.  
D. To Use Cooling Charging Chart, Standard Unit  
Take the outdoor ambient temperature and read the suction  
pressure gage. Refer to charts to determine what suction tem-  
perature should be. If suction temperature is high, add refrig-  
erant. If suction temperature is low, carefully recover some of  
the charge. Recheck the suction pressure as charge is adjusted.  
Example (Fig. 50):  
Outdoor Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 F  
Suction Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70 psig  
Suction Temperature should be . . . . . . . . . . . . . . . . . . . . 48 F  
(Suction temperature may very ± 5 F.)  
Fig. 46 — Separating Coil Sections  
If charging device is used, temperature and pressure read-  
ings must be accomplished using the charging charts.  
UNIT 581B  
FAN HEIGHT — “A” (in.)  
036-060 and 072 (208/230 V)  
072 (460 and 575 V)  
2.75  
3.50  
Fig. 47 — Condenser-Fan Adjustment  
39—  
Fig. 50 — Cooling Charging Chart, Standard 581B060  
Fig. 48 — Cooling Charging Chart, Standard 581B036  
Fig. 49 — Cooling Charging Chart, Standard 581B048  
Fig. 51 — Cooling Charging Chart, Standard 581B072  
40—  
CONDENSER FAN MUST BE OPERATING  
CONDENSER FAN MUST BE OPERATING  
NOTE: When using the charging charts, it is important that only the subcooling/reheat dehu-  
midification coil liquid line solenoid valve be energized. The subcooling/reheat dehumidifica-  
tion coil liquid line solenoid valve MUST be energized to use the charging charts and the  
outdoor motor speed controller jumpered to run the fan at full speed.  
NOTE: When using the charging charts, it is important that only the subcooling/reheat dehu-  
midification coil liquid line solenoid valve be energized. The subcooling/reheat dehumidifica-  
tion coil liquid line solenoid valve MUST be energized to use the charging charts and the  
outdoor motor speed controller jumpered to run the fan at full speed.  
Fig. 52 — Cooling Charging Chart, 581B036 with the  
Perfect Humidity Dehumidification System  
Fig. 54 — Cooling Charging Chart, 581B060 with the  
Perfect Humidity Dehumidification System  
CONDENSER FAN MUST BE OPERATING  
CONDENSER FAN MUST BE OPERATING  
NOTE: When using the charging charts, it is important that only the subcooling/reheat dehu-  
midification coil liquid line solenoid valve be energized. The subcooling/reheat dehumidifica-  
tion coil liquid line solenoid valve MUST be energized to use the charging charts and the  
outdoor motor speed controller jumpered to run the fan at full speed.  
NOTE: When using the charging charts, it is important that only the subcooling/reheat  
dehumidification coil liquid line solenoid valve be energized. The subcooling/reheat dehu-  
midification coil liquid line solenoid valve MUST be energized to use the charging charts  
and the outdoor motor speed controller jumpered to run the fan at full speed.  
Fig. 53 — Cooling Charging Chart, 581B048 with the  
Perfect Humidity Dehumidification System  
Fig. 55 — Cooling Charging Chart, 581B072 with the  
Perfect Humidity Dehumidification System  
41—  
E. To Use Cooling Charging Charts, Units With Perfect  
Humidity™ Dehumidification System  
Refer to charts (Fig. 52-55) to determine the proper leaving  
condenser pressure and temperature.  
Example (Fig. 52):  
Leaving Condenser Pressure. . . . . . . . . . . . . . . . . . . .250 psig  
Leaving Condenser Temperature . . . . . . . . . . . . . . . . . . 105 F  
Table 31 — LED Error Code Description*  
LED INDICATION  
ERROR CODE DESCRIPTION  
Normal Operation  
ON  
OFF  
Hardware Failure  
1 Flash†  
2 Flashes  
3 Flashes  
4 Flashes  
5 Flashes  
6 Flashes  
7 Flashes  
8 Flashes  
9 Flashes  
Evaporator Fan On/Off Delay Modified  
Limit Switch Fault  
Flame Sense Fault  
4 Consecutive Limit Switch Faults  
Ignition Lockout Fault  
Induced-Draft Motor Fault  
Rollout Switch Fault  
Internal Control Fault  
Software Lockout  
NOTE: When using the charging charts, it is important that  
only the subcooling/reheat dehumidification coil liquid line  
solenoid valve be energized. The subcooling/reheat dehumid-  
ification coil liquid line solenoid valve MUST be energized to  
use the charging charts and the outdoor motor speed control-  
ler jumpered to run the fan at full speed.  
X. FLUE GAS PASSAGEWAYS  
To inspect the flue collector box and upper areas of the heat  
exchanger:  
LEGEND  
LED — Light-Emitting Diode  
*A 3-second pause exists between LED error code flashes. If more  
than one error code exists, all applicable codes will be displayed in  
numerical sequence.  
†Indicates a code that is not an error. The unit will continue to operate  
when this code is displayed.  
1. Remove the combustion blower wheel and motor  
assembly according to directions in Combustion-Air  
Blower section following.  
2. Remove the 3 screws holding the blower housing to  
the flue cover.  
IMPORTANT: Refer to Troubleshooting Tables 32-36 for additional  
information.  
3. Remove the flue cover to inspect the heat exchanger.  
4. Clean all surfaces as required using a wire brush.  
XIV. MAIN BURNERS  
At the beginning of each heating season, inspect for deteriora-  
tion or blockage due to corrosion or other causes. Observe the  
main burner flames and adjust, if necessary.  
XI. COMBUSTION-AIR BLOWER  
Clean periodically to ensure proper airflow and heating effi-  
ciency. Inspect blower wheel every fall and periodically during  
heating season. For the first heating season, inspect blower  
wheel bimonthly to determine proper cleaning frequency.  
CAUTION: When working on gas train, do not hit  
or plug orifice spuds.  
To inspect blower wheel, remove draft hood and screen.  
Shine a flashlight into opening to inspect wheel. If cleaning  
is required, remove motor and wheel as follows:  
A. Removal and Replacement of Gas Train (See Fig. 56  
and 57)  
1. Slide burner access panel out.  
1. Shut off manual gas valve.  
2. Remove the 5 screws that attach induced-draft motor  
assembly to the vestibule cover.  
2. Shut off power to unit tag disconnect.  
3. Remove compressor access panel.  
4. Slide out burner compartment side panel.  
5. Disconnect gas piping at unit gas valve.  
3. Slide the motor and blower wheel assembly out of the  
blower housing. The blower wheel can be cleaned at  
this point. If additional cleaning is required, continue  
with Steps 4 and 5.  
6. Remove wires connected to gas valve. Mark each  
wire.  
4. To remove blower from the motor shaft, by remove  
2 setscrews.  
7. Remove induced-draft motor, ignitor, and sensor  
wires at the Integrated Gas Unit Controller (IGC).  
5. To remove motor, remove the 4 screws that hold the  
motor to mounting plate. Remove the motor cooling  
fan by removing one setscrew. Then remove nuts that  
hold motor to mounting plate.  
8. Remove the 2 screws that attach the burner rack to  
the vestibule plate.  
9. Remove the gas valve bracket.  
10. Slide the burner tray out of the unit (Fig. 57).  
11. To reinstall, reverse the procedure outlined above.  
6. To reinstall, reverse the procedure outlined above.  
XII. LIMIT SWITCH  
B. Cleaning and Adjustment  
Remove blower access panel (Fig. 7). Limit switch is located  
on the fan deck.  
1. Remove burner rack from unit as described above.  
2. Inspect burners and, if dirty, remove burners from  
rack.  
XIII. BURNER IGNITION  
Unit is equipped with a direct spark ignition 100% lockout  
system. Integrated Gas Unit Controller (IGC) is located in  
the control box (Fig. 12). A single LED on the IGC provides a  
visual display of operational or sequential problems when  
the power supply is uninterrupted. The LED can be observed  
through the viewport. When a break in power occurs, the  
IGC will be reset (resulting in a loss of fault history) and the  
evaporator fan on/off times delay will be reset. During servic-  
ing, refer to the label on the control box cover or Table 31 for  
an explanation of LED error code descriptions.  
3. Using a soft brush, clean burners and cross-over port  
as required.  
4. Adjust spark gap. See Fig. 58.  
5. Reinstall burners on rack.  
6. Reinstall burner rack as described above.  
XV. REPLACEMENT PARTS  
A complete list of replacement parts may be obtained from  
your Bryant distributor upon request. Refer to Fig. 59 for a  
typical unit wiring schematic.  
If lockout occurs, unit may be reset by interrupting power  
supply to unit for at least 5 seconds.  
42—  
INDUCED-  
DRAFT  
ROLLOUT  
SWITCH  
MOTOR  
MOUNTING  
PLATE  
BURNER  
SECTION  
FLUE  
EXHAUST  
VESTIBULE  
PLATE  
INDUCED-  
DRAFT  
MOTOR  
Fig. 57 — Burner Tray Details  
BLOWER  
HOUSING  
MANIFOLD  
PRESSURE  
TAP  
GAS  
VALVE  
Fig. 56 — Burner Section Details  
LOW HEAT UNITS  
581B036060N  
60,000 BTUH  
INPUT  
581B048060N  
581B060060N  
581B036071  
581B036072  
581B048071  
581B048072  
581B060071  
581B060072  
581B072072  
72,000 BTUH  
INPUT  
MEDIUM AND  
HIGH HEAT UNITS  
581B036090N  
90,000 BTUH  
581B048090N  
INPUT  
581B060090N  
581B036114  
581B036115  
581B048114  
115,000 BTUH  
581B048115  
INPUT  
581B060114  
581B060115  
581B072115  
581B048120N  
581B060120N  
581B048149  
581B048150  
581B060149  
581B060150  
581B072150  
120,000 BTUH  
INPUT  
150,000 BTUH  
INPUT  
Fig. 58 — Spark Gap Adjustment  
43—  
NOTES:  
1. If any of the original wire furnished must be replaced, it must  
be replaced with type 90 C wire or its equivalent.  
2. Three phase motors are protected under primary single  
phasing conditions.  
3. Use copper conductors only.  
4. TRAN is wired for 230 v unit. If unit is to be run with 208 v  
power supply, disconnect BLK wire from 230 v tap (ORN)  
and connect to 208 v tap (RED). Insulate end of 230 v tap.  
LEGEND  
OFM  
OLR  
P
Outdoor (Condenser) Fan Motor  
Overload Relay  
C
Contactor, Compressor  
Capacitor  
Compressor Lockout  
Compressor Motor  
Equipment  
Freeze Up Protection Thermostat  
Fuse  
Ground  
High-Pressure Switch  
Hall-Effect Sensor  
Ignitor  
CAP  
CLO  
COMP  
EQUIP  
FPT  
FU  
Splice  
Plug  
PL  
Plug Assembly  
Quadruple Terminal  
Rollout Switch  
Supply Air Temperature Sensor  
Transformer  
Splice (Marked)  
Factory Wiring  
QT  
RS  
SAT  
TRAN  
GND  
HPS  
HS  
Field Control Wiring  
Field Splice  
Field Power Wiring  
I
Accessory or Optional Wiring  
To indicate common potential only;  
not to represent wiring.  
Marked Wire  
IDM  
IFC  
Induced-Draft Motor  
Indoor Fan Contactor  
Indoor Fan Motor  
Integrated Gas Unit Controller  
Low-Pressure Switch  
Limit Switch  
Terminal (Marked)  
Terminal (Unmarked)  
Terminal Block  
IFM  
IGC  
LPS  
LS  
MGV  
Main Gas Valve  
Fig. 59 — Typical Wiring Schematic and Component Arrangement (208/230-3-60 Shown)  
44—  
TROUBLESHOOTING  
I. UNIT TROUBLESHOOTING  
Refer to Tables 32-36.  
Table 32 — LED Error Code Service Analysis  
CAUSE  
SYMPTOM  
REMEDY  
Hardware Failure  
(LED OFF)  
Loss of power to control module (IGC).  
Check 5 amp fuse on IGC, power to unit, 24-v circuit breaker, and  
transformer. Units without a 24-v circuit breaker have an internal  
overload in the 24-v transformer. If the overload trips, allow  
10 minutes for automatic reset.  
Fan ON/OFF Delay Modified High limit switch opens during heat  
IGC board has modified either blower on delay time or blower off  
delay time.  
(LED/FLASH)  
exchanger warm-up period before fan-on  
delay expires.  
Limit switch opens within three minutes  
after blower-off delay timing in Heating mode.  
Limit Switch Fault  
(LED 2 Flashes)  
High temperature limit switch is open.  
Check the operation of the indoor (evaporator) fan motor.  
Ensure that the supply-air temperature rise is in accordance with  
the range on the unit nameplate.  
Flame Sense Fault  
(LED 3 Flashes)  
The IGC sensed flame that should not be  
present.  
Reset unit. If problem persists, replace control board.  
4 Consecutive Limit  
Switch Faults  
(LED 4 Flashes)  
Inadequate airflow to unit.  
Check operation of indoor (evaporator) fan motor and that supply-air  
temperature rise agrees with range on unit nameplate information.  
Ignition Lockout  
(LED 5 Flashes)  
Unit unsuccessfully attempted ignition for  
15 minutes.  
Check ignitor and flame sensor electrode spacing, gaps, etc.  
Ensure that flame sense and ignition wires are properly routed  
and terminated. Verify that unit is obtaining proper amount of gas.  
Induced-Draft Motor Fault  
(LED 6 Flashes)  
IGC does not sense that induced-draft  
motor is operating.  
Check for proper voltage. If motor is operating, check the  
speed sensor plug/IGC Terminal J2 connection. Proper  
connection: PIN 1— White, PIN 2 — Red, PIN 3 — Black.  
Rollout Switch Fault  
(LED 7 Flashes)  
Rollout switch has opened.  
Rollout switch will automatically reset, but IGC will continue to  
lock out unit. Check gas valve operation. Ensure that induced-  
draft blower wheel is properly secured to motor shaft.  
Reset unit at unit disconnect.  
Internal Control Fault  
(LED 8 Flashes)  
Microprocessor has sensed an error in the  
software or hardware.  
If error code is not cleared by resetting unit power, replace the IGC.  
Temporary Software  
Lockout  
(LED 9 Flashes)  
Electrical interference is impeding the IGC  
software.  
Reset 24-v to control board or turn thermostat off and then on.  
Fault will automatically reset itself in one hour.  
IMPORTANT: Refer to heating troubleshooting for additional heating  
CAUTION: If the IGC must be replaced, be sure to  
ground yourself to dissipate any electrical charge that may be  
present before handling new control board. The IGC is sensitive  
to static electricity and may be damaged if the necessary pre-  
cautions are not taken.  
section troubleshooting information.  
LEGEND  
IGC — Integrated Gas Unit Controller  
LED — Light-Emitting Diode  
45—  
Table 33 — Heating Service Analysis  
PROBLEM  
CAUSE  
REMEDY  
Burners Will Not  
Ignite  
Misaligned spark electrodes.  
No gas at main burners.  
Check flame ignition and sensor electrode positioning. Adjust as needed.  
Check gas line for air purge as necessary. After purging gas line of  
air, allow gas to dissipate for at least 5 minutes before attempting  
to relight unit.  
Check gas valve.  
Water in gas line.  
No power to unit.  
Drain water and install drip leg to trap water.  
Check power supply, fuses, wiring, and circuit breaker.  
No 24 v power supply to control circuit.  
Check transformer. Transformers with internal overcurrent protection  
require a cool-down period before resetting. Check 24-v circuit breaker;  
reset if necessary.  
Miswired or loose connections.  
Burned-out heat anticipator in thermostat.  
Broken thermostat wires.  
Dirty air filter.  
Check all wiring and wirenut connections.  
Replace thermostat.  
Run continuity check. Replace wires, if necessary.  
Clean or replace filter as necessary.  
Inadequate Heating  
Gas input to unit too low.  
Check gas pressure at manifold. Clock gas meter for input. If too low,  
increase manifold pressure or replace with correct orifices.  
Unit undersized for application.  
Restricted airflow.  
Replace with proper unit or add additional unit.  
Clean filter, replace filter, or remove any restrictions.  
Blower speed too low.  
Use high speed tap, increase fan speed, or install optional blower, as suit-  
able for individual units, Adjust pulley.  
Limit switch cycles main burners.  
Too much outdoor air.  
Check rotation of blower, thermostat heat anticipator settings,  
and temperature rise of unit. Adjust as needed.  
Adjust minimum position.  
Check economizer operation.  
Poor Flame  
Characteristics  
Incomplete combustion (lack of  
combustion air) results in:  
Check all screws around flue outlets and burner compartment.  
Tighten as necessary.  
Aldehyde odors, CO (carbon monoxide),  
sooting flame, or floating flame.  
Cracked heat exchanger. Replace heat exchanger.  
Overfired unit — reduce input, change orifices, or adjust gas line or mani-  
fold pressure.  
Check vent for restriction. Clean as necessary.  
Check orifice to burner alignment.  
Burners Will Not  
Turn Off  
Unit is locked into Heating mode for a  
one minute minimum.  
Wait until mandatory one-minute time period has elapsed or reset power to  
unit.  
Table 34 — Perfect Humidity™ Adaptive Dehumidification System Subcooling Mode Service Analysis  
PROBLEM  
CAUSE  
REMEDY  
Subcooling Mode (Liquid Reheat)  
Will Not Energize.  
No power to control transformer from  
evaporator-fan motor.  
Check power source and evaporator-fan relay. Ensure all  
wire connections are tight.  
No power from control transformer to liquid line  
solenoid valve.  
1. Fuse open; check fuse. Ensure continuity of wiring.  
2. Low-pressure switch open. Cycle unit off and allow low-  
pressure switch to reset. Replace switch if it will not  
close.  
3. Transformer bad; check transformer.  
Liquid line solenoid valve will not operate.  
1. Solenoid coil defective; replace.  
2. Solenoid valve stuck open; replace.  
Liquid line solenoid valve will not open.  
Valve is stuck closed; replace valve.  
Low System Capacity.  
Low refrigerant charge or frosted evaporator coil.  
1. Check charge amount. Charge per Fig. 52-55.  
2. Evaporator coil frosted; check and replace low-  
pressure switch if necessary.  
Loss of Compressor Superheat  
Conditions with Subcooling/Reheat  
Dehumidification Coil Energized.  
Thermostatic expansion valve (TXV).  
1. Check TXV bulb mounting, and secure tightly to suction  
line.  
2. Replace TXV if stuck open or closed.  
Table 35 — Perfect Humidity Dehumidification System Hot Gas Reheat Mode Service Analysis  
PROBLEM  
CAUSE  
REMEDY  
Reheat Mode Will Not Energize.  
No power to control transformer from  
evaporator-fan motor.  
Check power source and evaporator-fan relay. Ensure all  
wire connections are tight.  
No power from control transformer to hot gas  
line solenoid valve.  
1. Fuse open; check fuse. Ensure continuity of wiring.  
2. Low-pressure switch open. Cycle unit off and allow low-  
pressure switch to reset. Replace switch if it will not  
close.  
3. Transformer bad; check transformer.  
Hot gas line solenoid valve will not operate.  
1. Solenoid coil defective; replace.  
2. Solenoid valve stuck closed; replace.  
Low refrigerant charge or frosted evaporator coil.  
1. Check charge amount. Charge per Fig. 52-55.  
2. Evaporator coil frosted; check and replace low-  
pressure switch if necessary.  
Loss of Compressor Superheat  
Conditions with Subcooling/Reheat  
Dehumidification Coil Energized.  
Thermostatic expansion valve (TXV).  
1. Check TXV bulb mounting, and secure tightly to suction  
line.  
2. Replace TXV if stuck open or closed.  
Excessive Superheat.  
Liquid line solenoid valve will not operate.  
Hot gas line solenoid valve will not close.  
Valve is stuck; replace valve.  
Valve is stuck; replace valve.  
46—  
Table 36 — Cooling Service Analysis  
CAUSE  
PROBLEM  
REMEDY  
Compressor and Condenser Fan  
Will Not Start  
Power failure.  
Fuse blown or circuit breaker tripped.  
Defective thermostat, contactor, transformer,  
or control relay.  
Call power company.  
Replace fuse or reset circuit breaker.  
Replace component.  
Insufficient line voltage.  
Incorrect or faulty wiring.  
Thermostat setting too high.  
Faulty wiring or loose connections in com-  
pressor circuit.  
Determine cause and correct.  
Check wiring diagram and rewire correctly.  
Lower thermostat setting below room temperature.  
Check wiring and repair or replace.  
Compressor Will Not Start  
But Condenser Fan Runs  
Compressor motor burned out, seized, or  
internal overload open.  
Defective run/start capacitor, overload, start  
relay.  
Determine cause. Replace compressor.  
Determine cause and replace.  
One leg of 3-phase power dead.  
Replace fuse or reset circuit breaker. Determine  
cause.  
Compressor Cycles (Other Than  
Normally Satisfying Thermostat)  
Refrigerant overcharge or undercharge.  
Recover refrigerant, evacuate system, and recharge  
to nameplate.  
Defective compressor.  
Insufficient line voltage.  
Blocked condenser.  
Defective run/start capacitor, overload, or  
start relay.  
Replace and determine cause.  
Determine cause and correct.  
Determine cause and correct.  
Determine cause and replace.  
Defective thermostat.  
Replace thermostat.  
Faulty condenser-fan motor or capacitor.  
Restriction in refrigerant system.  
Dirty air filter.  
Replace.  
Locate restriction and remove.  
Replace filter.  
Compressor Operates Continuously  
Unit undersized for load.  
Thermostat set too low.  
Low refrigerant charge.  
Leaking valves in compressor.  
Air in system.  
Decrease load or increase unit size.  
Reset thermostat.  
Locate leak, repair, and recharge.  
Replace compressor.  
Recover refrigerant, evacuate system, and  
recharge.  
Condenser coil dirty or restricted.  
Dirty air filter.  
Clean coil or remove restriction.  
Replace filter.  
Excessive Head Pressure  
Dirty condenser coil.  
Refrigerant overcharged.  
Air in system.  
Clean coil.  
Recover excess refrigerant.  
Recover refrigerant, evacuate system, and  
recharge.  
Condenser air restricted or air short-cycling.  
Low refrigerant charge.  
Compressor valves leaking.  
Restriction in liquid tube.  
High heat load.  
Compressor valves leaking.  
Refrigerant overcharged.  
Dirty air filter.  
Determine cause and correct.  
Check for leaks, repair, and recharge.  
Replace compressor.  
Remove restriction.  
Check for source and eliminate.  
Replace compressor.  
Head Pressure Too Low  
Excessive Suction Pressure  
Suction Pressure Too Low  
Recover excess refrigerant.  
Replace filter.  
Low refrigerant charge.  
Metering device or low side restricted.  
Insufficient evaporator airflow.  
Check for leaks, repair, and recharge.  
Remove source of restriction.  
Increase air quantity. Check filter and replace if  
necessary.  
Temperature too low in conditioned area.  
Outdoor ambient below 25 F.  
Time off delay not finished.  
Reset thermostat.  
Install low-ambient kit.  
Wait for 30-second off delay.  
Evaporator Fan Will Not Shut Off  
47—  
II. ECONOMI$ER IV TROUBLESHOOTING  
D. DCV (Demand Controlled Ventilation) and Power  
Exhaust  
See Table 37 for EconoMi$er IV logic.  
To check DCV and Power Exhaust:  
A functional view of the EconoMi$er IV is shown in Fig. 60.  
Typical settings, sensor ranges, and jumper positions are  
also shown. An EconoMi$er IV simulator program is avail-  
able from Bryant to help with EconoMi$er IV training and  
troubleshooting.  
1. Make sure EconoMi$er IV preparation procedure has  
been performed.  
2. Ensure terminals AQ and AQ1 are open. The LED for  
both DCV and Exhaust should be off. The actuator  
should be fully closed.  
A. EconoMi$er IV Preparation  
3. Connect a 9-v battery to AQ (positive node) and AQ1  
(negative node). The LED for both DCV and Exhaust  
should turn on. The actuator should drive to between  
90 and 95% open.  
This procedure is used to prepare the EconoMi$er IV for  
troubleshooting. No troubleshooting or testing is done by  
performing the following procedure.  
NOTE: This procedure requires a 9-v battery, 1.2 kilo-ohm  
resistor, and a 5.6 kilo-ohm resistor which are not supplied  
with the EconoMi$er IV.  
4. Turn the Exhaust potentiometer CW until the  
Exhaust LED turns off. The LED should turn off  
when the potentiometer is approximately 90%. The  
actuator should remain in position.  
IMPORTANT: Be sure to record the positions of all potenti-  
ometers before starting troubleshooting.  
5. Turn the DCV set point potentiometer CW until the  
DCV LED turns off. The DCV LED should turn off  
when the potentiometer is approximately 9 v. The  
actuator should drive fully closed.  
1. Disconnect power at TR and TR1. All LEDs should be  
off. Exhaust fan contacts should be open.  
2. Disconnect device at P and P1.  
3. Jumper P to P1.  
6. Turn the DCV and Exhaust potentiometers CCW  
until the Exhaust LED turns on. The exhaust con-  
tacts will close 30 to 120 seconds after the Exhaust  
LED turns on.  
4. Disconnect wires at T and T1. Place 5.6 kilo-ohm  
resistor across T and T1.  
5. Jumper TR to 1.  
6. Jumper TR to N.  
7. Return EconoMi$er IV settings and wiring to normal  
after completing troubleshooting.  
7. If connected, remove sensor from terminals SO and +.  
Connect 1.2 kilo-ohm 4074EJ M checkout resistor  
across terminals SO and +.  
E. DCV Minimum and Maximum Position  
To check the DCV minimum and maximum position:  
8. Put 620-ohm resistor across terminals SR and +.  
1. Make sure EconoMi$er IV preparation procedure has  
been performed.  
9. Set minimum position, DCV set point, and exhaust  
potentiometers fully CCW (counterclockwise).  
2. Connect a 9-v battery to AQ (positive node) and AQ1  
(negative node). The DCV LED should turn on. The  
actuator should drive to between 90 and 95% open.  
10. Set DCV maximum position potentiometer fully CW  
(clockwise).  
3. Turn the DCV Maximum Position potentiometer to  
midpoint. The actuator should drive to between 20  
and 80% open.  
11. Set enthalpy potentiometer to D.  
12. Apply power (24 vac) to terminals TR and TR1.  
B. Differential Enthalpy  
4. Turn the DCV Maximum Position potentiometer to  
fully CCW. The actuator should drive fully closed.  
To check differential enthalpy:  
1. Make sure EconoMi$er IV preparation procedure has  
been performed.  
5. Turn the Minimum Position potentiometer to mid-  
point. The actuator should drive to between 20 and  
80% open.  
2. Place 620-ohm resistor across SO and +.  
6. Turn the Minimum Position Potentiometer fully CW.  
The actuator should drive fully open.  
3. Place 1.2 kilo-ohm resistor across SR and +. The Free  
Cool LED should be lit.  
7. Remove the jumper from TR and N. The actuator  
should drive fully closed.  
4. Remove 620-ohm resistor across SO and +. The Free  
Cool LED should turn off.  
8. Return EconoMi$er IV settings and wiring to normal  
after completing troubleshooting.  
5. Return EconoMi$er IV settings and wiring to normal  
after completing troubleshooting.  
F. Supply-Air Input  
C. Single Enthalpy  
To check supply-air input:  
To check single enthalpy:  
1. Make sure EconoMi$er IV preparation procedure has  
been performed.  
1. Make sure EconoMi$er IV preparation procedure has  
been performed.  
2. Set the Enthalpy potentiometer to A. The Free Cool  
LED turns on. The actuator should drive to between  
20 and 80% open.  
2. Set the enthalpy potentiometer to A (fully CCW). The  
Free Cool LED should be lit.  
3. Set the enthalpy potentiometer to D (fully CW). The  
Free Cool LED should turn off.  
3. Remove the 5.6 kilo-ohm resistor and jumper T to T1.  
The actuator should drive fully open.  
4. Return EconoMi$er IV settings and wiring to normal  
after completing troubleshooting.  
4. Remove the jumper across T and T1. The actuator  
should drive fully closed.  
5. Return EconoMi$er IV settings and wiring to normal  
after completing troubleshooting.  
48—  
G. EconoMi$er IV Troubleshooting Completion  
6. Remove 1.2 kilo-ohm checkout resistor from termi-  
nals SO and +. If used, reconnect sensor from termi-  
nals SO and +.  
This procedure is used to return the EconoMi$er IV to opera-  
tion. No troubleshooting or testing is done by performing the  
following procedure.  
7. Remove jumper from TR to N.  
8. Remove jumper from TR to 1.  
1. Disconnect power at TR and TR1.  
2. Set enthalpy potentiometer to previous setting.  
9. Remove 5.6 kilo-ohm resistor from T and T1. Recon-  
nect wires at T and T1.  
3. Set DCV maximum position potentiometer to previ-  
ous setting.  
10. Remove jumper from P to P1. Reconnect device at P  
and P1.  
4. Set minimum position, DCV set point, and exhaust  
potentiometers to previous settings.  
11. Apply power (24 vac) to terminals TR and TR1.  
5. Remove 620-ohm resistor from terminals SR and +.  
Table 37 — EconoMi$er IV Input/Output Logic  
INPUTS  
Enthalpy*  
OUTPUTS  
Compressor  
N Terminal†  
Demand Control  
Ventilation (DCV)  
Y1 Y2  
Occupied  
Minimum position  
Unoccupied  
Stage Stage  
Outdoor  
Return  
1
2
Damper  
Below set  
(DCV LED Off)  
High  
Low  
On On  
On Off  
Off Off  
On On  
On Off  
Off Off  
On On  
On Off  
Off Off  
On On  
On Off  
Off Off  
On  
On  
Off  
On  
Off  
Off  
On  
On  
Off  
On  
Off  
Off  
On  
Off  
Off  
Off  
Off  
Off  
On  
Off  
Off  
Off  
Off  
Off  
Closed  
(Free Cooling LED Off)  
Low  
High  
Low  
High  
Modulating** (between min.  
position and full-open)  
Modulating** (between  
closed and full-open)  
(Free Cooling LED On)  
Minimum position  
Modulating†† (between min.  
position and DCV maximum)  
Closed  
Above set  
(DCV LED On)  
High  
Modulating†† (between  
closed and DCV  
maximum)  
(Free Cooling LED Off)  
Low  
Modulating***  
Modulating†††  
(Free Cooling LED On)  
***Modulation is based on the greater of DCV and supply-air sensor  
signals, between minimum position and either maximum position  
(DCV) or fully open (supply-air signal).  
†††Modulation is based on the greater of DCV and supply-air sensor  
signals, between closed and either maximum position (DCV) or fully  
open (supply-air signal).  
*For single enthalpy control, the module compares outdoor enthalpy  
to the ABCD set point.  
†Power at N terminal determines Occupied/Unoccupied setting:  
24 vac (Occupied), no power (Unoccupied).  
**Modulation is based on the supply-air sensor signal.  
††Modulation is based on the DCV signal.  
Fig. 60 — EconoMi$er IV Functional View  
49—  
INDEX  
Access panels 15  
Heat exchanger  
7
Weight  
Corner  
EconoMi$er IV 6, 8  
Unit 5, 6, 8  
Wiring  
Altitude compensation 35  
Barometric flow capacity 17  
Burner ignition 42  
High flow valves 34  
High pressure switch  
Horizontal units 1, 2  
Humidistat 13  
8
7
Burner rack 43  
Burner section 43  
Burner spark gap 43  
Charging chart, refrigerant 40, 41  
Indoor air quality sensor 19  
Integrated gas controller 42  
Error codes 42, 45  
Leak test 34  
Light commercial Thermistat™ device 13  
Limit switch 42  
Humidistat 13  
EconoMi$er IV 17  
Perfect Humidity dehumidification 14  
Power connections 10  
Thermostat 10  
Clearance  
4
CO2 sensor  
Configuration 21  
Settings 20, 22  
Combustion blower wheel 42  
Compressor  
Unit 44  
Liquid propane  
Low pressure switch  
7
7
Main burners 35, 42  
Lubrication 38  
Mounting 34  
Manual outdoor air damper 14  
Mounting  
Rotation 34  
Compressor 34  
Condensate drain  
Cleaning 38  
Location 2, 4  
Condenser coil  
Cleaning 38  
Condenser fan  
Unit  
Natural gas  
Non-fused disconnect switch 13  
Operating limits  
Operating sequence 36  
Cooling 36  
4
7
6
2
6
Adjustment 38, 39  
Control circuit  
EconoMi$er IV 36  
Heating 36  
Wiring  
9
Perfect Humidity dehumidification 36, 37  
Outdoor air hood 14-16  
Outdoor air temperature sensor 16  
Outdoor air inlet screens 34  
Wiring raceway 10  
Convenience outlet 14  
Demand control ventilation 21  
Dehumidification 21  
Dimensions 3, 8  
Dimensions  
7
Perfect Humidity dehumidification  
package 13, 14, 23, 36, 39, 41, 46  
Physical data 6, 7  
Ductwork  
2
EconoMi$er IV 15-21  
Adjustment 38  
Components 15  
Controller 20  
Power supply  
Wiring 10  
9
Pressure, drop  
Damper movement 21  
Wiring 17  
Perfect Humidity dehumidification 23  
Pre-Start-Up 34  
Electrical connections  
Electrical data 11, 12  
Enthalpy changeover set points 20  
9
Pressure switches  
High pressure 7, 38  
Low pressure 7, 38  
Refrigerant  
Evaporator coil  
6
Cleaning 38  
Evaporator fan motor  
Lubrication 38  
Motor data 23, 24  
Performance 24-33  
Pulley adjustment 23  
Pulley setting 6, 22  
Charge 6, 38-42  
Type  
6
Refrigerant service ports 34  
Replacement parts 42  
Return air filter 7, 34  
Return air temperature sensor 19  
Rigging unit 4, 5  
Speed  
6
Roof curb  
Factory-installed options  
Convenience outlet 14  
Disconnect switch 13  
EconoMi$er IV 15-21  
Humidistat 13  
Manual outdoor air damper 14  
Perfect Humidity™ dehumidification 13  
Filter  
Assembly  
Dimensions  
Connector package  
Leveling tolerances  
Weight  
Safety considerations  
Safety relief 36  
Service 38-44  
1
3
3
4
6
1
Cleaning 38  
Service ports 34  
Installation 16  
Slab mount  
Start-up 34-37  
1
Size  
7
Flue gas passageways 42  
Flue hood 4, 9  
Freeze protection thermostat 7, 38  
Start-up checklist CL-1  
Thermostat 9, 10  
Troubleshooting 45-49  
Ventilation 36  
Gas connection  
Gas input  
7
7
Gas piping 4, 9, 34  
Gas pressure 1, 7  
Heat anticipator settings 7, 9  
Copyright 2005 Bryant Heating & Cooling Systems  
Printed in U.S.A.  
CATALOG NO. 04-53581002-01  
START-UP CHECKLIST  
(Remove and Store in Job File)  
I. PRELIMINARY INFORMATION  
MODEL NO.: _________________________________  
DATE:________________________________________  
SERIAL NO.:________________________________________  
TECHNICIAN: ______________________________________  
II. PRE-START-UP (insert checkmark in box as each item is completed)  
VERIFY THAT JOBSITE VOLTAGE AGREES WITH VOLTAGE LISTED ON RATING PLATE  
VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT  
REMOVE ALL SHIPPING HOLDDOWN BOLTS AND BRACKETS PER INSTALLATION INSTRUCTIONS  
VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS  
CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS  
CHECK GAS PIPING FOR LEAKS  
CHECK THAT RETURN (INDOOR) AIR FILTERS ARE CLEAN AND IN PLACE  
VERIFY THAT UNIT INSTALLATION IS LEVEL  
CHECK FAN WHEELS AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS  
CHECK TO ENSURE THAT ELECTRICAL WIRING IS NOT IN CONTACT WITH REFRIGERANT LINES  
OR SHARP METAL EDGES  
CHECK PULLEY ALIGNMENT AND BELT TENSION PER INSTALLATION INSTRUCTIONS  
III. START-UP  
ELECTRICAL  
SUPPLY VOLTAGE  
COMPRESSOR AMPS  
INDOOR-FAN AMPS  
L1-L2  
L1  
L1  
L2-L3  
L2  
L2  
L3-L1  
L3  
L3  
TEMPERATURES  
OUTDOOR-AIR TEMPERATURE  
RETURN-AIR TEMPERATURE  
DB  
DB  
WB  
COOLING SUPPLY AIR  
GAS HEAT SUPPLY AIR  
DB  
DB  
PRESSURES  
GAS INLET PRESSURE  
IN. WG  
GAS MANIFOLD PRESSURE  
REFRIGERANT SUCTION  
REFRIGERANT DISCHARGE  
IN. WG  
PSIG  
PSIG  
VERIFY REFRIGERANT CHARGE USING CHARGING TABLES  
VERIFY THAT 3-PHASE SCROLL COMPRESSOR ROTATING IN CORRECT DIRECTION  
Copyright 2005 Bryant Heating & Cooling Systems  
Printed in U.S.A.  
CL-1  
CATALOG NO. 04-53581002-01  

Brother MFC 925 User Manual
Epson All in One Printer CX7000F User Manual
Fisher Price G2623 User Manual
GE ASP14 User Manual
Haier HWF05XCK E User Manual
Haier HWR05XC5 User Manual
HandHeld Entertainment Barcode Reader 4600G User Manual
Havis Shields Heavy Duty Trak Mount 2003 2006 Ford Expedition C TM EXPD User Manual
Honda Automobiles Ashtray 08U25 SEC 2000 81 User Manual
HP Hewlett Packard CH350 90038 User Manual