installation, start-up and
service instructions
581B
DuraPac Plus Series
Sizes 036-072
3 to 6 Tons
SINGLE PACKAGE ROOFTOP
GAS HEATING/ELECTRIC COOLING UNITS
Cancels: II 581B-36-6
II 581B-36-7
10/1/05
WARNING: Before performing service or mainte-
nance operations on unit, turn off main power switch to
unit. Electrical shock could cause personal injury.
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-33
I. Step 1 — Provide Unit Support. . . . . . . . . . . . . . . . . 1
II. Step 2 — Field Fabricate Ductwork . . . . . . . . . . . . . 2
Unit is shipped in the vertical configuration. To convert to
horizontal application, remove side duct opening covers.
Using the same screws, install covers on vertical duct open-
ings with the insulation-side down. Seals around duct open-
ings must be tight. See Fig. 1.
III. Step 3 — Determine Location of Drain Line
and External Trap. . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
IV. Step 4 — Rig and Place Unit. . . . . . . . . . . . . . . . . . . 4
V. Step 5 — Install Flue Hood . . . . . . . . . . . . . . . . . . . . 4
VI. Step 6 — Install Gas Piping . . . . . . . . . . . . . . . . . . . 4
VII. Step 7 — Make Electrical Connections . . . . . . . . . . 9
VIII. Step 8 — Adjust Factory-Installed Options. . . . . . 13
IX. Step 9 — Adjust Evaporator-Fan Speed . . . . . . . . 22
I. STEP 1 — PROVIDE UNIT SUPPORT
A. Roof Curb
Assemble and install accessory roof curb in accordance with
instructions shipped with curb. See Fig. 2. Install insulation,
cant strips, roofing felt, and counter flashing as shown. Duct-
work must be attached to curb. If gas is to be routed through
the curb, attach the accessory thru-the-curb service connec-
tion plate to the roof curb in accordance with the accessory
installation instructions. Connection plate must be installed
before unit is set in roof curb.
PRE-START-UP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34-37
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38-44
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . .45-49
INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1
IMPORTANT: The gasketing of the unit to the roof curb is crit-
ical for a watertight seal. Install gasket supplied with the roof
curb as shown in Fig. 2. Improperly applied gasket can also
result in air or water leaks and poor unit performance.
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Curb should be level. This is necessary for unit drain to func-
tion properly. Unit leveling tolerances are shown in Fig. 3.
Refer to Accessory Roof Curb Installation Instructions for
additional information as required.
Untrained personnel can perform basic maintenance func-
tions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained service per-
sonnel. When working on air-conditioning equipment,
observe precautions in the literature, tags and labels
attached to the unit, and other safety precautions that may
apply.
B. Slab Mount (Horizontal Units Only)
Provide a level concrete slab that extends a minimum of 6 in.
beyond unit cabinet. Install a gravel apron in front of con-
denser coil air inlet to prevent grass and foliage from
obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if
required.
Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloth for unbrazing operations. Have fire
extinguishers available for all brazing operations.
C. Alternate Unit Support
A non-combustible sleeper rail can be used in the unit curb
support area. If sleeper rails cannot be used, support the long
sides of the unit with a minimum of 3 equally spaced 4-in. x
4-in. pads on each side.
CAUTION: Ensure voltage listed on unit data plate
agrees with electrical supply provided for the unit.
WARNING: Disconnect gas piping from unit when
leak testing at pressure greater than 1/2 psig. Pressures
1
greater than /2 psig will cause gas valve damage result-
ing in hazardous condition. If gas valve is subjected to
1
pressure greater than /2 psig, it must be replaced before
use. When pressure testing field-supplied gas piping at
1
pressures of /2 psig or less, a unit connected to such
piping must be isolated by manually closing the gas
valve(s).
ROOF CURB
ACCESSORY
D ALT
DRAIN
HOLE
A
UNIT SIZE
CONNECTOR
PKG. ACCY.
ACCESSORY
PWR
B
C
GAS
POWER
CONTROL
1′-2″
CRRFCURB001A01
CRRFCURB002A01
CRBTMPWR001A01
CRBTMPWR002A01
3/4″ [19] NPT
11/4″ [31.7]
3/4″ [19] NPT
3/4″
1/2″
[356]
581B036-072
[19] NPT
[12.7]
2′-0″
1′-911
/
″
1′-4″
13/4″
1/2″
[610]
1/2″
[5511]6 [406]
[44.5]
[12.7]
CRBTMPWR003A01
CRBTMPWR004A01
1/2″
[12.7] NPT
3/4″
[12.7]
NOTES:
11/4″ [31.7]
1. Roof curb accessory is shipped disassembled.
2. Insulated panels.
[19] NPT
3. Dimensions in [ ] are in millimeters.
4. Roof curb: galvanized steel.
5. Attach ductwork to curb (flanges of duct rest on
curb).
6. Service clearance: 4 ft on each side.
7.
Direction of airflow.
8. Connector packages CRBTMPWR001A01 and
002A01 are for thru-the-curb type gas. Packages
CRBTMPWR003A01 and 004A01 are for thru-the-
bottom type gas connections.
Fig. 2 — Roof Curb Details
—3—
A. Positioning
Maintain clearance around and above unit to provide mini-
mum distance from combustible materials, proper airflow,
and service access. See Fig. 7.
Do not install unit in an indoor location. Do not locate unit
air inlets near exhaust vents or other sources of contami-
nated air.
Be sure that unit is installed so that snow will not block the
combustion intake or flue outlet.
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
Unit may be installed directly on wood flooring or on Class
A, B, or C roof-covering material when roof curb is used.
A-B
0.5
B-C
1.0
A-C
1.0
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
Fig. 3 — Unit Leveling Tolerances
Position unit on roof curb so that the following clearances are
1
maintained: /4 in. clearance between the roof curb and the
base rail inside the front and rear, 0.0 in. clearance between
the roof curb and the base rail inside on the duct end of the
unit. This will result in the distance between the roof curb
and the base rail inside on the condenser end of the unit
being approximately equal to Fig. 2, section C-C.
Locate mechanical draft system flue assembly at least 48 in.
from an adjacent building or combustible material. Units
having accessory flue discharge deflector require only 18 in.
clearance. When unit is located adjacent to public walkways,
flue assembly must be at least 7 ft above grade.
Flue gas can deteriorate building materials. Orient unit so
that flue gas will not affect building materials.
HORIZONTAL
DRAIN PLUG
DRAIN PLUG
Adequate combustion and ventilation air space must be pro-
vided for proper operation of this equipment. Be sure that
installation complies with all local codes and Section 5.3, Air
for Combustion and Ventilation per NFGC (National Fuel Gas
Code), ANSI (American National Standards Institute) Z223.1-
latest year and addendum Z223.1A-latest year. In Canada,
installation must be in accordance with the CAN1.B149.1 and
CAN1.B149.2 installation codes for gas burning appliances.
NOTE: Drain plug is shown in factory-installed position.
Fig. 4 — Condensate Drain Pan
Flue vent discharge must have a minimum horizontal clear-
ance of 4 ft from electric and gas meters, gas regulators, and
gas relief equipment.
After unit is in position, remove shipping materials and rig-
ging skids.
V. STEP 5 — INSTALL FLUE HOOD
Flue hood is shipped screwed to the burner compartment
access panel. Remove from shipping location and, using
screws provided, install flue hood in location shown in Fig. 7
and 8.
For units being installed in California Air Quality Manage-
ment Districts which require NOx emissions of 40 nanograms/
joule or less, a low NOx unit must be installed.
NOTE: Trap should be deep enough to offset maximum unit static dif-
ference. A 4-in. trap is recommended.
NOTE: Low NOx units are available for 3 to 5 ton units.
Fig. 5 — Condensate Drain Piping Details
VI. STEP 6 — INSTALL GAS PIPING
Unit is equipped for use with type of gas shown on name-
plate. Refer to local building codes, or in the absence of local
codes, to ANSI Z223.1-latest year and addendum Z223.1A-
latest year entitled NFGC. In Canada, installation must be
in accordance with the CAN1.B149.1 and CAN1.B149.2
installation codes for gas burning appliances.
IV. STEP 4 — RIG AND PLACE UNIT
Inspect unit for transportation damage. File any claim with
transportation agency. Keep unit upright and do not drop.
Spreader bars are not required if top crating is left on unit.
Rollers may be used to move unit across a roof. Level by
using unit frame as a reference. See Table 1 and Fig. 6
for additional information. Operating weight is shown in
Table 1 and Fig. 6.
For natural gas applications, gas pressure at unit gas con-
nection must not be less than 4.0 in. wg or greater than
13.0 in. wg while unit is operating. For liquid propane and
high heat applications, the gas pressure must not be less
than 5.0 in. wg or greater than 13.0 in. wg at the unit
connection.
Lifting holes are provided in base rails as shown in Fig. 6
and 7. Refer to rigging instructions on unit.
—4—
NOTES:
OPERATING
WEIGHT
1. Place unit on curb as close as possible to the duct end.
2. Dimension in ( ) is in millimeters.
“A”
“B”
“C”
UNIT
581B
3. Hook rigging shackles through holes in base rail as shown in detail
“A.” Holes in base rails are centered around the unit center of grav-
ity. Use wooden top skid when rigging to prevent rigging straps
from damaging unit.
4. Weights include base unit without economizer. See Table 1 for unit
operating weights and economizer weights.
5. Weights include base unit without the Perfect Humidity™ dehumid-
ification system. See Table 1 for additional unit operating weights
with the Perfect Humidity system.
lb
kg
in.
mm
in.
mm
in.
mm
036
048
060
072
530
540
560
635
240
245
254
288
73.69 1872 35.50 902 33.31 847
73.69 1872 35.50 902 33.31 847
73.69 1872 35.50 902 33.31 847
73.69 1872 35.50 902 33.31 847
CAUTION: All panels must be in place when rigging.
Fig. 6 — Rigging Details
Size gas supply piping for 0.5-in. wg maximum pressure
drop. Do not use supply pipe smaller than unit gas
connection.
Installation Instructions for information on power wiring
and gas connection piping. Power wiring, control wiring and
gas connection piping can be routed through field-drilled
holes in the basepan, which is specifically designed and dim-
pled for drilling the accessory connection holes.
Support gas piping as shown in the table in Fig. 9. For exam-
ple, a 3/4-in. gas pipe must have one field-fabricated support
beam every 8 ft. Therefore, an 18-ft long gas pipe would have
a minimum of 3 support beams. See Fig. 9 for typical pipe
guide and locations of external manual gas shutoff valve.
CAUTION: When connecting the gas line to the
unit gas valve, the installer MUST use a backup
wrench to prevent damage to the valve.
NOTE: If accessory thru-the-bottom connections and roof
curb are used, refer to the Thru-the-Bottom Accessory
—5—
Table 1 — Physical Data — 581B036-072
UNIT SIZE 581B
036
048
060
072
NOMINAL CAPACITY
3
4
5
6
OPERATING WEIGHT (lb)
Unit
EconoMi$er IV
Perfect Humidity™ Dehumidification System
Roof Curb
530
50
540
50
560
50
635
50
15
23
23
29
115
115
115
115
COMPRESSOR
Quantity
Oil (oz)
Scroll
R-22
1
42
1
53
1
50
1
60
REFRIGERANT TYPE
Operating Charge (lb-oz)
Standard Unit
5-8
9-0
10-2
15-8
10-0
17-0
12-8
21-0
Unit With Perfect Humidity Dehumidification System
CONDENSER FAN
Propeller
Quantity...Diameter (in.)
1...22
3500
1...22
3500
1...22
4100
1...22
4100
Nominal Cfm
Motor Hp...Rpm
1/4...825
180
1/4...825
180
1/4...1100
320
1/4...1100
320
Watts Input (Total)
CONDENSER COIL
Rows...Fins/in.
Total Face Area (sq ft)
Enhanced Copper Tubes, Aluminum Lanced Fins
1...17
14.6
2...17
16.5
2...17
16.5
2...17
16.5
EVAPORATOR COIL
Standard Unit
Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Acutrol™ Metering Device
Rows...Fins/in.
Total Face Area (sq ft)
2...15
5.5
2...15
5.5
4...15
5.5
4...15
5.5
Unit with Perfect Humidity Dehumidification System
Rows...Fins/in.
1...17
3.9
2...17
3.9
2...17
3.9
2...17
5.2
Total Face Area (sq ft)
EVAPORATOR FAN
Centrifugal Type, Belt Drive
1...10 x 10
Quantity...Size (in.)
1...10 x 10
1200
1...10 x 10
1...10 x 10
2400
Nominal Cfm
1600
1.20
2000
1.30/2.40*
2.90
48/56*
56
Maximum Continuous Bhp
Std
Hi-Static
Std
1.20
2.40
2.40
2.40
2.90
Motor Frame Size
Fan Rpm Range
48
48
56
Hi-Static
Std
56
56
56
680-1044
1075-1455
Ball
770-1185
1075-1455
Ball
1035-1460
1300-1685
Ball
1119-1585
1300-1685
Ball
Hi-Static
Motor Bearing Type
Maximum Fan Rpm
2100
2100
2100
2100
Motor Pulley Pitch Diameter A/B (in.)
Std
Hi-Static
Std
1.9/2.9
1.9/2.0
2.4/3.4
2.4/3.4
2.8/3.8
2.8/3.8
3.4/4.4
3.4/3.4
1
1
5
5
Nominal Motor Shaft Diameter (in.)
Fan Pulley Pitch Diameter (in.)
Belt — Type...Length (in.)
/
/
/
/
2
2
8
8
5
5
5
7
Hi-Static
Std
/
/
/
/
4.85
4.80
4.0
4.0
4.0
8
8
Hi-Static
Std
4.5
4.5
4.5
1...A...36
1...A...36
1....4...40
1...A...38
Hi-Static
1...A...39
1...A...39
1...A...40
1...A...40
Pulley Center Line Distance (in.)
Speed Change per Full Turn of
Movable Pulley Flange (rpm)
Movable Pulley Maximum Full
Turns from Closed Position
10.0-12.4
10.0-12.4
14.7-15.5
14.7-15.5
Std
Hi-Static
Std
65
65
5
70
65
5
75
60
6
95
60
5
Hi-Static
Std
6
3
6
3
5
5
3
Factory Setting — Full Turns Open
3
Hi-Static
Std
31/2
826
31/2
936
31/2
1248
31/2
1305
Factory Speed Setting (rpm)
Hi-Static
1233
1233
1396
1396
5
5
5
5
Fan Shaft Diameter at Pulley (in.)
/
8
/
/
/
8
8
8
LEGEND
Bhp — Brake Horsepower
††An LP kit is available as an accessory. If an LP kit is used with low NOx units,
one low NOx baffle must be removed and the units will no longer be classified
as low NOx units.
||California compliant three-phase models.
*Single phase/three phase.
†Indicates automatic reset.
**60,000 and 72,000 Btuh heat input units have 2 burners. 90,000 and
120,000 Btuh heat input units have 3 burners. 115,000 Btuh heat input units
and 150,000 Btuh Heat input units have 3 burners.
***California SCAQMD compliant low NOx models have combustion products that
are controlled to 40 nanograms per joule or less.
—6—
Table 1 — Physical Data — 581B036-072 (cont)
UNIT SIZE 581B
036
048
060
072
FURNACE SECTION
Rollout Switch Cutout Temp (F)†
Burner Orifice Diameter (in. ...drill size)**
Natural Gas — Std
195
195
195
195
071/072
114/115
149/150
.113...33
.113...33
—
.113...33
.113...33
.129...30
.113...33
.113...33
.129...30
.113...33
.113...33
.129...30
060N
090N
120N
.102...38
.102...38
—
.102...38
.102...38
.116...32
.102...38
.102...38
.116...32
—
—
—
Liquid Propane — Alt††
071/072
114/115
149/150
.089...43
.089...43
—
.089...43
.089...43
.102...38
.089...43
.089...43
.102...38
.089...43
.089...43
.102...38
060N
090N
120N
.082...45
.082...45
—
.082...45
.082...45
.094...42
.082...45
.082...45
.094...42
—
—
—
Thermostat Heat Anticipator Setting (amps)
208/230/460 v
First Stage
.14
.14
.14
.14
.14
.14
.14
.14
Second Stage
Gas Input (Btuh)
First Stage/Second Stage (3-phase units)
072
115
150
50,000/ 72,000
82,000/115,000
—
50,000/ 72,000
82,000/115,000
120,000/150,000
50,000/ 72,000
82,000/115,000
120,000/150,000
50,000/ 72,000
82,000/115,000
120,000/150,000
071II
114II
149II
—/ 72,000
—/115,000
—
—/ 72,000
—/115,000
—/150,000
—/ 72,000
—/115,000
—/150,000
—
—
—
060N***
090N***
120N***
—/ 60,000
—/ 90,000
—
—/ 60,000
—/ 90,000
—/120,000
—/ 60,000
—/ 90,000
—/120,000
—
—
—
Efficiency (Steady State) (%)
072
115
150
82.8
80
—
82.8
81
80.4
82.8
81
80.4
82
81
80
071
114
149
82
80
—
82
81
80
82
81
80
—
—
—
060N
090N
120N
80.2
81
—
80.2
81
80.7
80.2
81
80.7
—
—
—
Temperature Rise Range
072
115
150
25-55
55-85
—
25-55
35-65
50-80
25-55
35-65
50-80
25-55
35-65
50-80
071
114
149
25-55
55-85
—
25-55
35-65
50-80
25-55
35-65
50-80
—
—
—
060N
090N
120N
20-50
30-60
—
20-50
30-60
40-70
20-50
30-60
40-70
—
—
—
Manifold Pressure (in. wg)
Natural Gas — Std
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
Liquid Propane — Alt††
Maximum Static Pressure (in. wg)
Field Gas Connection Size (in.)
1.0
1.0
1.0
1.0
1
1
1
1
/
2
/
2
/
2
/
2
HIGH-PRESSURE SWITCH (psig)
450 50
428
320
Standard Compressor Internal Relief
Cutout
Reset (Auto.)
LOSS-OF-CHARGE SWITCH/LOW-PRESSURE
SWITCH (Liquid LIne) (psig)
Cutout
7
22
3
5
Reset (Auto.)
FREEZE PROTECTION THERMOSTAT
Opens (F)
Closes (F)
30
45
5
5
OUTDOOR-AIR INLET SCREENS
Quantity...Size (in.)
Cleanable
1...20 x 24 x 1
RETURN-AIR FILTERS
Quantity...Size (in.)
Throwaway
2...16 x 25 x 2
4...16 x 16 x 2
LEGEND
††An LP kit is available as an accessory. If an LP kit is used with low NOx units,
one low NOx baffle must be removed and the units will no longer be classified
as low NOx units.
Bhp— Brake Horsepower
||California compliant three-phase models.
*Single phase/three phase.
†Indicates automatic reset.
**60,000 and 72,000 Btuh heat input units have 2 burners. 90,000 and
120,000 Btuh heat input units have 3 burners. 115,000 Btuh heat input units
and 150,000 Btuh Heat input units have 3 burners.
***California SCAQMD compliant low NOx models have combustion products that
are controlled to 40 nanograms per joule or less.
—7—
—8—
Refer to unit label diagram for additional information. Pig-
tails are provided for field service. Use factory-supplied
splices or UL (Underwriters’ Laboratories) approved copper
connector.
When installing units, provide a disconnect per NEC.
All field wiring must comply with NEC and local require-
ments. In Canada, electrical connections must be in accor-
dance with CSA (Canadian Standards Association) C22.1
Canadian Electrical Code Part One.
Install conduit through side panel openings indicated in
Fig. 7. Route power lines through connector to terminal
connections as shown in Fig. 10.
On 3-phase units, voltages between phases must be balanced
within 2% and the current within 10%. Use the formula
shown in Note 3 under Tables 2A-2D to determine the per-
centage of voltage imbalance. Operation on improper line
voltage or excessive phase imbalance constitutes abuse and
may cause damage to electrical components. Such operation
would invalidate any applicable Bryant warranty.
Fig. 8 — Flue Hood Details
NOTE: If thru-the-bottom accessory connections are used,
refer to the thru-the-bottom accessory installation instruc-
tions for power wiring. Refer to Fig. 7 for location to drill
holes in basepan.
B. Field Control Wiring
Install a Bryant-approved accessory thermostat assembly
according to installation instructions included with the
accessory. Locate thermostat assembly on a solid wall in the
conditioned space to sense average temperature in accor-
dance with thermostat installation instructions.
LEGEND
NFGC — National Fuel Gas Code
*Field supplied.
Route thermostat cable or equivalent single leads of colored
wire from thermostat subbase terminals to low-voltage con-
nections on unit (shown in Fig. 11) as described in Steps 1-4
below.
NOTE: Follow all local codes.
1. If mounted on a roof curb and electrical power is to be
run through the basepan, an accessory thru-the-bot-
tom connection kit is required. This is available
through the local Bryant distributor. This kit is
required to ensure a reliable water-tight connection.
STEEL PIPE
SPACING OF SUPPORTS
NOMINAL DIAMETER
X DIMENSION
(ft)
(in.)
1
/
6
8
10
2
3/4 or 1
11/4 or larger
2. If unit is mounted on roof curb and accessory thru-
the-bottom connections are used, route wire through
connection plate.
Fig. 9 — Gas Piping Guide (With Accessory
Thru-the-Curb Service Connections)
3. Pass control wires through the hole provided on unit
(see connection D, Connection Sizes table, Fig. 7).
VII. STEP 7 — MAKE ELECTRICAL CONNECTIONS
4. Feed wires through the raceway built into the corner
post to the 24-v barrier located on the left side of the
control box. See Fig. 12. The raceway provides the
UL-required clearance between high- and low-voltage
wiring.
WARNING: Unit cabinet must have an uninter-
rupted, unbroken electrical ground to minimize the
possibility of personal injury if an electrical fault
should occur. This ground may consist of electrical wire
connected to unit ground lug in control compartment,
or conduit approved for electrical ground when
installed in accordance with NEC (National Electrical
Code), ANSI/NFPA (National Fire Protection Associa-
tion), latest edition, and local electrical codes. Do not
use gas piping as an electrical ground. Failure to follow
this warning could result in the installer being liable
for personal injury of others.
5. Connect thermostat wires to screw terminals of low-
voltage connection board (see Fig. 11).
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American
Wire Gage) insulated wire (35 C minimum). For 51 to 75 ft,
use no. 16 AWG insulated wire (35 C minimum). For over
75 ft, use no. 14 AWG insulated wire (35 C minimum).
NOTE: All wire larger than no. 18 AWG cannot be directly
connected to the thermostat and will require a junction box
and splice at the thermostat.
A. Field Power Supply
All units except 208/230-v units are factory wired for the
voltage shown on the nameplate. If the 208/230-v unit is to
be connected to a 208-v power supply, the transformer must
be rewired by moving the black wire from the 230-v terminal
on the transformer and connecting it to the 200-v terminal
on the transformer.
C. Heat Anticipator Settings
Set heat anticipator settings at 0.14 amp for first stage and
0.14 amp for second-stage heating, when available.
—9—
LEGEND
C
—
Contactor
COMP
—
Compressors
EQUIP — Equipment
GND
IFC
—
Ground
—
Indoor (Evaporator)
Fan Contactor
NEC
TB
—
National Electrical Code
—
Terminal Block
Fig. 10 — Power Wiring Connections
BRYANT ELECTRONIC THERMOSTAT
R
G
COOL STAGE 1
FAN
Y1/W2
G
RACEWAY
LOW VOLTAGE
CONNECTIONS
INTEGRATED GAS UNIT
CONTROLLER (IGC)
Y1
HEAT STAGE 1
COOL STAGE 2
HEAT STAGE 2
24 VAC HOT
W/W1
Y/Y2
O/W2
R
WIRE
Y2
CONNECTIONS
TO
W1
W2
C
LOW-VOLTAGE
SECTION
24 VAC COM
N/A
C
IPD/X
OUTDOOR AIR
SENSOR
S1
S2
THERMOSTAT DIPSWITCH SETTINGS
ON
OFF
D
A
B
C
LEGEND
Field Wiring
HOLE IN END PANEL (HIDDEN)
NOTE: Underlined letter indicates active thermostat output when con-
figured for A/C operation.
Fig. 12 — Field Control Wiring Raceway
Fig. 11 — Low-Voltage Connections With or
Without Economizer
—10—
Table 2A — Electrical Data — Standard Motor Units Without Electrical Convenience Outlet
VOLTAGE
RANGE
Min Max Qty
COMPRESSOR
(each)
OFM
COMBUSTION
FAN MOTOR
POWER
MINIMUM UNIT
IFM
UNIT
581B
NOMINAL VOLTAGE
(V-Ph-Hz)
(each)
SUPPLY*
DISCONNECT SIZE†
RLA
16.0
10.3
5.1
LRA
FLA
0.7
0.7
0.4
0.4
0.7
0.7
0.4
0.4
1.5
1.5
0.8
0.8
1.4
0.6
0.6
FLA
4.9
4.9
2.2
2.2
4.9
4.9
2.2
2.2
8.8
5.8
2.6
2.6
5.8
2.6
2.6
FLA
.60
.60
.30
.30
.60
.60
.30
.30
.60
.60
.30
.30
.60
.30
.30
MCA
MOCP**
30/30
25/25
20
FLA
25/25
18/18
9
LRA
101/101
90/90
46
208/230-1-60
208/230-3-60
460-3-60
187
187
414
518
187
187
414
518
187
187
414
518
187
414
518
254
254
508
632
254
254
508
632
254
254
508
632
254
508
632
88.0
77.0
39.0
31.0
126.0
93.0
46.5
40.0
169.0
123.0
62.0
50.0
156.0
75.0
56.0
25.6/25.6
18.5/18.5
9.0
036
(3 Tons)
1
1
575-3-60
4.2
7.3
20
7
37
208/230-1-60
208/230-3-60
460-3-60
23.7
13.5
6.4
35.2/35.2
22.5/22.5
10.6
45/45
30/30
20
34/34
22/22
10
139/139
106/106
54
048
(4 Tons)
575-3-60
6.4
10.1
20
10
46
208/230-1-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
28.8
17.3
9.0
46.3/46.3
28.9/28.9
14.7
60/60
35/35
20
45/45
28/28
14
216/216
168/168
84
060
(5 Tons)
1
1
7.1
11.6
20
12
68
20.5
9.6
32.8/32.8
15.2
40/40
20
32/32
15
200/200
97
072
(6 Tons)
575-3-60
7.7
12.2
20
12
74
Table 2B — Electrical Data — Standard Motor Units With Electrical Convenience Outlet
POWER
VOLTAGE
RANGE
COMPRESSOR
(each)
OFM
(each)
COMBUSTION
FAN MOTOR
MINIMUM UNIT
DISCONNECT SIZE†
IFM
SUPPLY
UNIT
581B
NOMINAL VOLTAGE
(V-Ph-Hz)
WITH OUTLET*
Min Max Qty
RLA
16.0
10.3
5.1
LRA
FLA
0.7
0.7
0.4
0.4
0.7
0.7
0.4
0.4
1.5
1.5
0.8
0.8
1.4
0.6
0.6
FLA
4.9
4.9
2.2
2.2
4.9
4.9
2.2
2.2
8.8
5.8
2.6
2.6
5.8
2.6
2.6
FLA
.60
.60
.30
.30
.60
.60
.30
.30
.60
.60
.30
.30
.60
.30
.30
MCA
31.6/31.6
24.5/24.5
11.7
MOCP**
FLA
30/30
24/24
11
LRA
106/106
95/95
48
208/230-1-60
208/230-3-60
460-3-60
187
187
414
518
187
187
414
518
187
187
414
518
187
414
518
254
254
508
632
254
254
508
632
254
254
508
632
254
508
632
88.0
77.0
39.0
31.0
126.0
93.0
46.5
40.0
169.0
123.0
62.0
50.0
156.0
75.0
56.0
35/35
30/30
20
036
(3 Tons)
1
1
575-3-60
4.2
9.5
20
9
38
208/230-1-60
208/230-3-60
460-3-60
23.7
13.5
6.4
41.2/41.2
28.5/28.5
13.3
50/50
35/35
20
39/39
27/27
13
144/144
111/111
56
048
(4 Tons)
575-3-60
6.4
12.2
20
12
47
208/230-1-60
208/230-3-60
460-3-60
28.8
17.3
9.0
7.1
20.5
9.6
52.3/52.3
34.9/34.9
17.4
13.8
38.8/38.8
17.9
60/60
40/40
20
20
45/45
20
50/50
34/34
17
13
37/37
17
221/221
173/173
87
70
205/205
99
060
(5 Tons)
1
1
575-3-60
208/230-3-60
460-3-60
575-3-60
072
(6 Tons)
7.7
14.3
20
14
75
LEGEND
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and
Refrigeration
Maximum deviation is 7 v.
IFM
LRA
— Indoor (Evaporator) Fan Motor
— Locked Rotor Amps
Determine percent of voltage imbalance.
7
% Voltage Imbalance = 100 x
457
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC — National Electrical Code
= 1.53%
OFM — Outdoor (Condenser) Fan Motor
This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.
RLA
UL
— Rated Load Amps
— Underwriters’ Laboratories
*The values listed in this table do not include power exhaust. See table at right for
power exhaust requirements.
†Used to determine minimum disconnect per NEC.
**Fuse or HACR circuit breaker.
POWER EXHAUST ELECTRICAL DATA
MOCP
POWER EXHAUST
PART NO.
MCA
MCA
MCA
NOTES:
(for separate
(230 v)
(460 v)
(575 v)
1. In compliance with NEC requirements for multimotor and combination load
equipment (refer to NEC Articles 430 and 440), the overcurrent protective
device for the unit shall be fuse or HACR breaker. The UL, Canada units
may be fuse or circuit breaker.
power source)
CRPWREXH021A01
CRPWREXH022A01
CRPWREXH023A01
CRPWREXH028A01
CRPWREXH029A01
CRPWREXH030A01
N/A
3.3
N/A
1.7
N/A
1.6
0.9
N/A
1.8
N/A
1.0
N/A
1.32
N/A
0.68
N/A
15
15
15
15
15
15
2. Electrical data based on 95 F ambient outdoor-air temperature 10% voltage.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where phase imbalance in supply voltage is greater
than 2%. Use the following formula to determine the percent voltage
imbalance.
N/A
0.64
% Voltage Imbalance
N/A — Not available
max voltage deviation from average voltage
= 100 x
NOTE: If a single power source is to be used, size wire to include power exhaust
MCA and MOCP.
average voltage
Example: Supply voltage is 460-3-60.
Check MCA and MOCP when power exhaust is powered through the unit. Deter-
mine the new MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using a 581B072 unit with MCA = 32.8 and MOCP = 40, with
CRPWREXH030A01 power exhaust.
MCA New = 32.8 amps + 1.6 amps = 34.4 amps
If the new MCA does not exceed the published MOCP, then MOCP would not
change. The MOCP in this example is 40 amps and the MCA New is below 40;
therefore the MOCP is acceptable. If “MCA New” is larger than the published
MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for
the power exhaust will be 15 amps per NEC.
AB = 452 v
BC = 464 v
AC = 455 v
452 + 464 + 455
Average Voltage =
3
1371
3
=
= 457
Determine maximum deviation from average voltage.
—11—
Table 2C — Electrical Data — High-Static Motor Units Without Electrical Convenience Outlet
MINIMUM UNIT
DISCONNECT
SIZE†
VOLTAGE
RANGE
COMPRESSOR
(each)
OFM
COMBUSTION
FAN MOTOR
POWER
NOMINAL
VOLTAGE
(V-Ph-Hz)
IFM
UNIT
581B
(each)
SUPPLY*
Min
Max
Qty
RLA
10.3
5.1
LRA
FLA
0.7
0.4
0.4
0.7
0.4
0.4
1.5
0.8
0.8
1.4
0.6
0.6
FLA
5.8
RLA
0.6
0.3
0.3
0.6
0.3
0.3
0.6
0.3
0.3
0.6
0.3
0.3
MCA
MOCP**
25
20
20
30
20
20
35
20
20
40
20
20
FLA
19
9
LRA
120
60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
187
414
518
187
414
518
187
414
518
187
414
518
254
508
632
254
508
632
254
508
632
254
508
632
77.0
39.0
31.0
93.0
46.5
40.0
123.0
62.0
50.0
156.0
75.0
56.0
19.4
9.4
7.7
036
048
060
072
1
2.6
2.6
5.8
2.6
2.6
7.5
3.4
3.4
7.5
3.4
3.4
4.2
8
48
13.5
6.4
23.4
11.0
10.4
30.6
15.5
12.2
34.5
16
23
11
10
30
15
12
34
16
13
136
68
57
187
94
76
219
107
81
1
1
1
6.4
17.3
9.0
7.1
20.5
9.6
7.7
12.8
Table 2D — Electrical Data — High-Static Motor Units With Electrical Convenience Outlet
MINIMUM UNIT
DISCONNECT
SIZE†
VOLTAGE
RANGE
COMPRESSOR
(each)
OFM
COMBUSTION
FAN MOTOR
POWER
NOMINAL
VOLTAGE
(V-Ph-Hz)
IFM
UNIT
581B
(each)
SUPPLY*
Min
Max
254
508
632
254
508
632
254
508
632
254
508
632
Qty
RLA
10.3
5.1
LRA
FLA
0.7
0.4
0.4
0.7
0.4
0.4
1.5
0.8
0.8
1.4
0.6
0.6
FLA
5.8
RLA
0.6
0.3
0.3
0.6
0.3
0.3
0.6
0.3
0.3
0.6
0.3
0.3
MCA
MOCP**
FLA
25
12
10
29
13
12
36
18
14
39
18
15
LRA
124
63
50
140
70
59
192
96
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
187
414
518
187
414
518
187
414
518
187
414
518
77.0
39.0
31.0
93.0
46.5
40.0
123.0
62.0
50.0
156.0
75.0
56.0
25.4
12.1
9.8
30
20
20
35
20
20
40
20
20
45
25
20
036
048
060
072
1
2.6
2.6
5.8
2.6
2.6
7.5
3.4
3.4
7.5
3.4
3.4
4.2
13.5
6.4
29.4
13.7
12.6
36.6
18.2
14.4
40.5
18.7
15.0
1
1
1
6.4
17.3
9.0
7.1
77
20.5
9.6
224
109
83
7.7
LEGEND
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and
Refrigeration
Maximum deviation is 7 v.
IFM
LRA
— Indoor (Evaporator) Fan Motor
— Locked Rotor Amps
Determine percent of voltage imbalance.
7
% Voltage Imbalance = 100 x
457
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC
— National Electrical Code
= 1.53%
OFM — Outdoor (Condenser) Fan Motor
This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.
RLA
UL
— Rated Load Amps
— Underwriters’ Laboratories
*The values listed in this table do not include power exhaust. See table at right for
power exhaust requirements.
†Used to determine minimum disconnect per NEC.
**Fuse or HACR circuit breaker.
POWER EXHAUST ELECTRICAL DATA
MOCP
POWER EXHAUST
PART NO.
MCA
MCA
MCA
NOTES:
(for separate
(230 v)
(460 v)
(575 v)
1. In compliance with NEC requirements for multimotor and combination load
equipment (refer to NEC Articles 430 and 440), the overcurrent protective
device for the unit shall be fuse or HACR breaker. The UL, Canada units
may be fuse or circuit breaker.
power source)
CRPWREXH021A01
CRPWREXH022A01
CRPWREXH023A01
CRPWREXH028A01
CRPWREXH029A01
CRPWREXH030A01
N/A
3.3
N/A
1.7
N/A
1.6
0.9
N/A
1.8
N/A
1.0
N/A
1.32
N/A
0.68
N/A
15
15
15
15
15
15
2. Electrical data based on 95 F ambient outdoor-air temperature 10% voltage.
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where phase imbalance in supply voltage is greater
than 2%. Use the following formula to determine the percent voltage
imbalance.
N/A
0.64
% Voltage Imbalance
N/A — Not available
max voltage deviation from average voltage
= 100 x
NOTE: If a single power source is to be used, size wire to include power exhaust
MCA and MOCP.
average voltage
Example: Supply voltage is 460-3-60.
Check MCA and MOCP when power exhaust is powered through the unit. Deter-
mine the new MCA including the power exhaust using the following formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using a 581B072 unit with MCA = 32.8 and MOCP = 40, with
CRPWREXH030A01 power exhaust.
MCA New = 32.8 amps + 1.6 amps = 34.4 amps
If the new MCA does not exceed the published MOCP, then MOCP would not
change. The MOCP in this example is 40 amps and the MCA New is below 40;
therefore the MOCP is acceptable. If “MCA New” is larger than the published
MOCP, raise the MOCP to the next larger size. For separate power, the MOCP for
the power exhaust will be 15 amps per NEC.
AB = 452 v
BC = 464 v
AC = 455 v
452 + 464 + 455
Average Voltage =
3
1371
=
3
= 457
Determine maximum deviation from average voltage.
—12—
VIII. STEP 8 — ADJUST FACTORY-INSTALLED OPTIONS
A. Disconnect Switch
The optional disconnect switch is non-fused. The switch has
the capability of being locked in place for safety purposes.
B. Perfect Humidity™ Dehumidification System
Perfect Humidity system operation can be controlled by field
installation of a Bryant-approved humidistat device (Fig. 13),
or light commercial Thermidistat™ device (Fig. 14). To install
the humidistat device:
% RELATIVE HUMIDITY
1. Route humidistat cable through hole provided in unit
corner post.
2. Feed wires through the raceway built into the corner
post to the 24-v barrier located on the left side of the
control box. See Fig. 12. The raceway provides the
UL-required clearance between high-voltage and low-
voltage wiring.
Fig. 13 — Accessory Field-Installed Humidistat Device
3. Use a wire nut to connect humidistat cable into low-
voltage wiring as shown in Fig. 15.
To install Thermidistat device:
1. Route Thermidistat cable through hole provided in
unit corner post.
2. Feed the wires through the raceway built into the cor-
ner post to the 24-v barrier located on the left side of
the control box. See Fig. 12. The raceway provides the
UL-required clearance between high and low voltage
wiring.
3. A field-supplied relay must be installed between the
Thermidistat device and the Perfect Humidity circuit
(recommended relay: HN612KK324). See Fig. 16. The
relay coil is connected between the DEHUM output
and C (common) of the unit. The relay controls the
Perfect Humidity solenoid valve and must be wired
between the Perfect Humidity fuse and the low-pres-
sure switch. Refer to the installation instructions
included with the Bryant Light Commercial Thermi-
distat device for more information.
Fig. 14 — Light Commercial Thermidistat Device
LEGEND
C
— Contactor (Compressor)
— Circuit Breaker
Low Temperature Lockout
LTLO
—
CB
CR
TRAN — Transformer
— Cooling Relay
Terminal (Unmarked)
DHR — Dehumidify Relay
DSV — Discharge Solenoid Valve
Splice
HU
LPS
— Humidistat
Factory Wiring
Low Pressure Switch
—
LSV — Liquid Line Solenoid Valve
Accessory or Optional Wiring
Fig. 15 — Typical Perfect Humidity Dehumidification System
Humidistat Wiring (208/230-v Unit Shown)
—13—
LCT
ROOF TOP UNIT
R
C
R
C
Y1
Y2
G
Y1
Y2
G
W1
W2
W1
W2
DEHUM
OC
CB
R1
R1
3.2 AMPS
PINK
RED
24V
T STAT WIRES
LTLO
PINK
PINK
FROM
PERFECT HUMIDITY
SYSTEM LLSV
LEGEND
— Circuit Breaker
CB
LCT — Light Commercial Thermidistat™ Device
LLSV — Liquid Line Solenoid Valve
LTLO — Low Temperature Lockout
PERFECT HUMIDITY SYSTEM
Fig. 16 — Typical Rooftop Unit with Perfect Humidity™ Dehumidification System with Thermidistat Device
C. Convenience Outlet
An optional convenience outlet provides power for rooftop
use. For maintenance personnel safety, the convenience out-
let power is off when the unit disconnect is off. Adjacent unit
outlets may be used for service tools. An optional “Hot Out-
let” is available from the factory as a special order item.
OUTDOOR
AIR OPENING
PANEL
3 SCREWS
(SIDE)
D. Manual Outdoor-Air Damper
The outdoor-air hood and screen are attached to the basepan
at the bottom of the unit for shipping.
Assembly:
1. Determine quantity of ventilation required for build-
ing. Record amount for use in Step 8.
2. Remove outdoor-air opening panel. Save panels and
screws. See Fig. 17.
3. Remove evaporator coil access panel. Separate hood
and screen from basepan by removing the 4 screws
securing them. Save all screws.
Fig. 17 — Damper Panel with Manual
Outdoor-Air Damper Installed
4. Replace evaporator coil access panel.
5. Place hood on front of outdoor-air opening panel. See
Fig. 18 for hood details. Secure top of hood with the 4
screws removed in Step 3. See Fig. 19.
6. Remove and save 6 screws (3 on each side) from sides
of the manual outdoor-air damper.
7. Align screw holes on hood with screw holes on side of
manual outdoor-air damper. See Fig. 18 and 19.
Secure hood with 6 screws from Step 6.
8. Adjust minimum position setting of the damper blade
by adjusting the manual outdoor-air adjustment
screws on the front of the damper blade. See Fig. 17.
Slide blade vertically until it is in the appropriate
position determined by Fig. 20. Tighten screws.
9. Remove and save screws currently on sides of hood.
Insert screens. Secure screens to hood using the
screws. See Fig. 19.
Fig. 18 — Outdoor-Air Hood Details
—14—
ECONOMI$ER IV
CONTROLLER
OUTSIDE AIR
TEMPERATURE SENSOR
WIRING
HARNESS
LOW AMBIENT
SENSOR
ACTUATOR
Fig. 19 — Optional Manual Outdoor-Air Damper
with Hood Attached
Fig. 21 — EconoMi$er IV Component Locations
FILTER ACCESS PANEL
COMPRESSOR
ACCESS PANEL
OUTDOOR-AIR OPENING AND
INDOOR COIL ACCESS PANEL
Fig. 22 — Typical Access Panel Locations
Fig. 20 — Outdoor-Air Damper Position Setting
E. Optional EconoMi$er IV
HOOD BOX
BRACKET
See Fig. 21 for EconoMi$er IV component locations.
NOTE: These instructions are for installing the optional
EconoMi$er IV only. Refer to the accessory EconoMi$er IV
installation instructions when field installing an EconoMi$er
IV accessory.
1. To remove the existing unit filter access panel, raise
the panel and swing the bottom outward. The panel is
now disengaged from the track and can be removed.
See Fig. 22.
2. The box with the economizer hood components is
shipped in the compartment behind the economizer.
The EconoMi$er IV controller is mounted on top of
the EconoMi$er IV in the position shown in Fig. 21.
To remove the component box from its shipping posi-
tion, remove the screw holding the hood box bracket
to the top of the economizer. Slide the hood box out of
the unit. See Fig. 23.
Fig. 23 — Hood Box Removal
—15—
IMPORTANT: If the power exhaust accessory is to be
installed on the unit, the hood shipped with the unit will not
be used and must be discarded. Sa ve th e a lu m in u m filter
for u se in th e p ow er exh a u st h ood a ssem b ly.
17 1/4”
3. The indoor coil access panel will be used as the top of
the hood. Remove the screws along the sides and bot-
tom of the indoor coil access panel. See Fig. 24.
4. Swing out indoor coil access panel and insert the
hood sides under the panel (hood top). Use the screws
provided to attach the hood sides to the hood top. Use
screws provided to attach the hood sides to the unit.
See Fig. 25.
DIVIDER
OUTSIDE
AIR
5. Remove the shipping tape holding the economizer
barometric relief damper in place.
HOOD
CLEANABLE
ALUMINUM
FILTER
6. Insert the hood divider between the hood sides. See
Fig. 25 and 26. Secure hood divider with 2 screws on
each hood side. The hood divider is also used as the
bottom filter rack for the aluminum filter.
FILTER
BAROMETRIC
RELIEF
FILTER
CLIP
Fig. 26 — Filter Installation
SIDE
PANEL
7. Open the filter clips which are located underneath
the hood top. Insert the aluminum filter into the bot-
tom filter rack (hood divider). Push the filter into
position past the open filter clips. Close the filter clips
to lock the filter into place. See Fig. 26.
8. Caulk the ends of the joint between the unit top panel
and the hood top. See Fig. 24.
9. Replace the filter access panel.
TOP
10. Install all EconoMi$er IV accessories. EconoMi$er IV
wiring is shown in Fig. 27.
SIDE
PANEL
CAULK
HERE
Barometric flow capacity is shown in Fig. 28. Outdoor air
leakage is shown in Fig. 29. Return air pressure drop is
shown in Fig. 30.
INDOOR
COIL
ACCESS
PANEL
INDOOR
COIL
ACCESS
PANEL
F. EconoMi$er IV Standard Sensors
Outdoor Air Temperature (OAT) Sensor
Fig. 24 — Indoor Coil Access Panel Relocation
The outdoor air temperature sensor (HH57AC074) is a 10 to
20 mA device used to measure the outdoor-air temperature.
The outdoor-air temperature is used to determine when the
EconoMi$er IV can be used for free cooling. The sensor is
factory-installed on the EconoMi$er IV in the outdoor
airstream. See Fig. 21. The operating range of temperature
measurement is 40 to 100 F.
TOP
PANEL
INDOOR COIL
ACCESS PANEL
Supply Air Temperature (SAT) Sensor
The supply air temperature sensor is a 3 K thermistor
located at the inlet of the indoor fan. See Fig. 31. This sensor
is factory installed. The operating range of temperature
measurement is 0° to 158 F. See Table 3 for sensor tempera-
ture/resistance values.
LEFT
HOOD
SIDE
SCREW
B
19 1/16”
The temperature sensor looks like an eyelet terminal with
wires running to it. The sensor is located in the “crimp end”
and is sealed from moisture.
33 3/8”
Outdoor Air Lockout Sensor
The EconoMi$er IV is equipped with an ambient tempera-
ture lockout switch located in the outdoor airstream which is
used to lockout the compressors below a 42 F ambient tem-
perature. See Fig. 21.
HOOD DIVIDER
Fig. 25 — Outdoor-Air Hood Construction
—16—
FOR OCCUPANCY CONTROL
REPLACE JUMPER WITH
FIELD-SUPPLIED TIME CLOCK
Potentiometer Defaults Settings:
Power Exhaust Middle
LEGEND
NOTES:
1. 620 ohm, 1 watt 5% resistor should be removed only when using differential
enthalpy or dry bulb.
DCV— Demand Controlled Ventilation
IAQ — Indoor Air Quality
Minimum Pos.
DCV Max.
DCV Set
Fully Closed
Middle
2. If a separate field-supplied 24 v transformer is used for the IAQ sensor power
supply, it cannot have the secondary of the transformer grounded.
3. For field-installed remote minimum position POT, remove black wire jumper
between P and P1 and set control minimum position POT. to the minimum
position.
LA — Low Ambient Lockout Device
OAT — Outdoor-Air Temperature
POT— Potentiometer
Middle
Enthalpy
C Setting
RAT — Return-Air Temperature
Fig. 27 — EconoMi$er IV Wiring
6000
5000
4000
3000
2000
1000
0
2500
2000
1500
1000
500
0
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.15
STATIC PRESSURE (in. wg)
0.05
0.25
STATIC PRESSURE (in. wg)
Fig. 30 — Return-Air Pressure Drop
Fig. 28 — Barometric Flow Capacity
30
25
20
15
10
5
SUPPLY AIR
TEMPERATURE
SENSOR
MOUNTING
LOCATION
SUPPLY AIR
TEMPERATURE
SENSOR
0
0.13 0.20 0.22 0.25 0.30 0.35 0.40 0.45 0.50
STATIC PRESSURE (in. wg)
Fig. 31 — Supply Air Sensor Location
Fig. 29 — Outdoor-Air Damper Leakage
—17—
Table 3 — Supply Air Sensor
Table 4 — EconoMi$er IV Sensor Usage
Temperature/Resistance Values
ECONOMI$ER IV WITH OUTDOOR AIR
DRY BULB SENSOR
Accessories Required
APPLICATION
TEMPERATURE (F)
RESISTANCE (ohms)
–58
–40
–22
–4
14
32
50
68
77
86
104
122
140
158
176
185
194
212
230
248
257
266
284
302
200,250
100,680
53,010
29,091
16,590
9,795
5,970
3,747
3,000
2,416
1,597
1,080
746
Outdoor Air
Dry Bulb
None. The outdoor air dry bulb sensor
is factory installed.
Differential
Dry Bulb
Single Enthalpy
CRTEMPSN002A00*
HH57AC078
HH57AC078
and
CRENTDIF004A00*
Differential
Enthalpy
CO2 for DCV
Control using a
Wall-Mounted
CO2 Sensor
33ZCSENCO2
CO2 for DCV
Control using a
Duct-Mounted
CO2 Sensor
33ZCSENCO2†
and
CRCBDIOX005A00††
33ZCASPCO2**
525
376
321
274
203
153
116
102
*CRENTDIF004A00 and CRTEMPSN002A00 accessories are used on many
different base units. As such, these kits may contain parts that will not be
needed for installation.
†33ZCSENCO2 is an accessory CO2 sensor.
**33ZCASPCO2 is an accessory aspirator box required for duct-mounted appli-
cations.
††CRCBDIOX005A00 is an accessory that contains both 33ZCSENCO2 and
33ZCASPCO2 accessories.
89
70
55
G. EconoMi$er IV Control Modes
Determine the EconoMi$er IV control mode before set up of the
control. Some modes of operation may require different sensors.
Refer to Table 4. The EconoMi$er IV is supplied from the fac-
tory with a supply air temperature sensor and an outdoor air
temperature sensor. This allows for operation of the
EconoMi$er IV with outdoor air dry bulb changeover control.
Additional accessories can be added to allow for different
types of changeover control and operation of the EconoMi$er
IV and unit.
Outdoor Dry Bulb Changeover
The standard controller is shipped from the factory config-
ured for outdoor dry bulb changeover control. The outdoor
air and supply air temperature sensors are included as stan-
dard. For this control mode, the outdoor temperature is com-
pared to an adjustable set point selected on the control. If the
outdoor-air temperature is above the set point, the
EconoMi$er IV will adjust the outside air dampers to mini-
mum position. If the outdoor-air temperature is below the set
point, the position of the outdoor-air dampers will be con-
trolled to provide free cooling using outdoor air. When in this
mode, the LED next to the free cooling set point potentiome-
ter will be on. The changeover temperature set point is con-
trolled by the free cooling set point potentiometer located on
the control. See Fig. 32. The scale on the potentiometer is A,
B, C, and D. See Fig. 33 for the corresponding temperature
changeover values.
Fig. 32 — EconoMi$er IV Controller Potentiometer
and LED Locations
19
LED ON
18
D
17
LED ON
LED OFF
16
15
14
C
LED ON
LED OFF
B
Differential Dry Bulb Control
13
12
LED ON
For differential dry bulb control the standard outdoor dry
bulb sensor is used in conjunction with an additional acces-
sory dry bulb sensor (part number CRTEMPSN002A00). The
accessory sensor must be mounted in the return airstream.
See Fig. 34. Wiring is provided in the EconoMi$er IV wiring
harness. See Fig. 27.
LED OFF
A
11
10
9
LED OFF
85 90
95
100
50
55 60
40 45
65 70 75 80
DEGREES FAHRENHEIT
Fig. 33 — Outdoor Air Temperature
Changeover Set Points
In this mode of operation, the outdoor-air temperature is
compared to the return-air temperature and the lower tem-
perature airstream is used for cooling. When using this mode
of changeover control, turn the enthalpy set point potentiom-
eter fully clockwise to the D setting. See Fig. 32.
—18—
Exhaust Set Point Adjustment
ECONOMI$ER IV
CONTROLLER
The exhaust set point will determine when the exhaust fan
runs based on damper position (if accessory power exhaust is
installed). The set point is modified with the Exhaust Fan
Set Point (EXH SET) potentiometer. See Fig. 32. The set
point represents the damper position above which the
exhaust fans will be turned on. When there is a call for
exhaust, the EconoMi$er IV controller provides a 45 ± 15
second delay before exhaust fan activation to allow the
dampers to open. This delay allows the damper to reach the
appropriate position to avoid unnecessary fan overload.
ECONOMI$ER IV
GROMMET
Minimum Position Control
There is a minimum damper position potentiometer on the
EconoMi$er IV controller. See Fig. 32. The minimum damper
position maintains the minimum airflow into the building
during the occupied period.
RETURN AIR
SENSOR
RETURN DUCT
(FIELD-PROVIDED)
When using demand ventilation, the minimum damper posi-
tion represents the minimum ventilation position for VOC
(volatile organic compound) ventilation requirements. The
maximum demand ventilation position is used for fully occu-
pied ventilation.
Fig. 34 — Return Air Temperature or Enthalpy
Sensor Mounting Location
Outdoor Enthalpy Changeover
For enthalpy control, accessory enthalpy sensor (part num-
ber HH57AC078) is required. Replace the standard outdoor
dry bulb temperature sensor with the accessory enthalpy
sensor in the same mounting location. See Fig. 21. When the
outdoor air enthalpy rises above the outdoor enthalpy
changeover set point, the outdoor-air damper moves to its
minimum position. The outdoor enthalpy changeover set
point is set with the outdoor enthalpy set point potentiome-
ter on the EconoMi$er IV controller. The set points are A, B,
C, and D. See Fig. 35. The factory-installed 620-ohm jumper
must be in place across terminals SR and SR+ on the
EconoMi$er IV controller. See Fig. 21 and 36.
When demand ventilation control is not being used, the min-
imum position potentiometer should be used to set the occu-
pied ventilation position. The maximum demand ventilation
position should be turned fully clockwise.
Adjust the minimum position potentiometer to allow the
minimum amount of outdoor air, as required by local codes,
to enter the building. Make minimum position adjustments
with at least 10 F temperature difference between the out-
door and return-air temperatures.
To determine the minimum position setting, perform the fol-
lowing procedure:
1. Calculate the appropriate mixed air temperature
using the following formula:
Differential Enthalpy Control
For differential enthalpy control, the EconoMi$er IV control-
ler uses two enthalpy sensors (HH57AC078 and
CRENTDIF004A00), one in the outside air and one in the
return air duct. The EconoMi$er IV controller compares the
outdoor air enthalpy to the return air enthalpy to determine
EconoMi$er IV use. The controller selects the lower enthalpy
air (return or outdoor) for cooling. For example, when the
outdoor air has a lower enthalpy than the return air, the
EconoMi$er IV opens to bring in outdoor air for free cooling.
OA
100
RA
100
(TO
x
) + (TR
x
) = TM
TO = Outdoor-Air Temperature
OA = Percent of Outdoor Air
TR = Return-Air Temperature
RA = Percent of Return Air
TM = Mixed-Air Temperature
Replace the standard outside air dry bulb temperature sen-
sor with the accessory enthalpy sensor in the same mounting
location. See Fig. 21. Mount the return air enthalpy sensor
in the return air duct. See Fig. 34. Wiring is provided in the
EconoMi$er IV wiring harness. See Fig. 27. The outdoor
enthalpy changeover set point is set with the outdoor
enthalpy set point potentiometer on the EconoMi$er IV con-
troller. When using this mode of changeover control, turn the
enthalpy set point potentiometer fully clockwise to the D
setting.
As an example, if local codes require 10% outdoor air dur-
ing occupied conditions, outdoor-air temperature is 60 F,
and return-air temperature is 75 F.
(60 x .10) + (75 x .90) = 73.5 F
2. Disconnect the supply air sensor from terminals T
and T1.
3. Ensure that the factory-installed jumper is in place
across terminals P and P1. If remote damper posi-
tioning is being used, make sure that the terminals
are wired according to Fig. 27 and that the minimum
position potentiometer is turned fully clockwise.
Indoor Air Quality (IAQ) Sensor Input
The IAQ input can be used for demand control ventilation
control based on the level of CO2 measured in the space or
return air duct.
4. Connect 24 vac across terminals TR and TR1.
5. Carefully adjust the minimum position potentiometer
until the measured mixed air temperature matches
the calculated value.
Mount the accessory IAQ sensor according to manufacturer
specifications. The IAQ sensor should be wired to the AQ and
AQ1 terminals of the controller. Adjust the DCV potentiome-
ters to correspond to the DCV voltage output of the indoor air
quality sensor at the user-determined set point. See Fig. 37.
6. Reconnect the supply air sensor to terminals T and T1.
Remote control of the EconoMi$er IV damper is desirable when
requiring additional temporary ventilation. If a field-supplied
remote potentiometer (Honeywell part number S963B1128) is
wired to the EconoMi$er IV controller, the minimum position of
the damper can be controlled from a remote location.
If a separate field-supplied transformer is used to power the
IAQ sensor, the sensor must not be grounded or the
EconoMi$er IV control board will be damaged.
—19—
85
90
95 100 105 110
(29) (32) (35) (38) (41) (43)
CONTROL CONTROL POINT
CURVE
APPROX. °F (°C)
AT 50% RH
80
(27)
A
B
C
D
73 (23)
70 (21)
67 (19)
63 (17)
75
(24)
70
(21)
65
(18)
60
(16)
A
55
(13)
B
50
(10)
C
45
(7)
D
40
(4)
35
(2)
A
B
C
D
HIGH LIMIT
CURVE
35
40
45
50
55
60
65
70
75
80
85
90
95 100 105 110
(2)
(4) (7) (10) (13) (16) (18) (21) (24) (27) (29) (32) (35) (38) (41) (43)
APPROXIMATE DRY BULB TEMPERATURE— °F (°C)
Fig. 35 — Enthalpy Changeover Set Points
CO SENSOR MAX RANGE SETTING
2
TR1
6000
5000
4000
3000
2000
1000
0
EXH
Set
10V
TR
N1
N
2V
EXH
24
Vac
HOT
24 Vac
COM
P1
T1
P
T
Min
Pos
800 ppm
900 ppm
1000 ppm
1100 ppm
_
+
Open
DCV
Max
10V
1
2
5
2V
AQ1
AQ
SO+
SO
SR+
SR
DCV
DCV
Set
4
3
2V
10V
2
3
4
5
6
7
8
Free
Cool
DAMPER VOLTAGE FOR MAX VENTILATION RATE
EF1
EF
C
D
B
Fig. 37 — CO2 Sensor Maximum Range Setting
A
Fig. 36 — EconoMi$er IV Control
—20—
To control the minimum damper position remotely, remove
the factory-installed jumper on the P and P1 terminals on
the EconoMi$er IV controller. Wire the field-supplied poten-
tiometer to the P and P1 terminals on the EconoMi$er IV
controller. See Fig. 36.
Once base ventilation has been determined, set the mini-
mum damper position potentiometer to the correct position.
The same equation can be used to determine the occupied or
maximum ventilation rate to the building. For example, an
output of 3.6 volts to the actuator provides a base ventilation
rate of 5% and an output of 6.7 volts provides the maximum
ventilation rate of 20% (or base plus 15 cfm per person). Use
Fig. 37 to determine the maximum setting of the CO2 sensor.
For example, a 1100 ppm set point relates to a 15 cfm per
person design. Use the 1100 ppm curve on Fig. 37 to find the
point when the CO2 sensor output will be 6.7 volts. Line up
the point on the graph with the left side of the chart to deter-
mine that the range configuration for the CO2 sensor should
be 1800 ppm. The EconoMi$er IV controller will output the
6.7 volts from the CO2 sensor to the actuator when the CO2
concentration in the space is at 1100 ppm. The DCV set point
may be left at 2 volts since the CO2 sensor voltage will be
ignored by the EconoMi$er IV controller until it rises above
the 3.6 volt setting of the minimum position potentiometer.
Damper Movement
Damper movement from full open to full closed (or vice
versa) takes 21/2 minutes.
Thermostats
The EconoMi$er IV control works with conventional thermo-
stats that have a Y1 (cool stage 1), Y2 (cool stage 2), W1
(heat stage 1), W2 (heat stage 2), and
G
(fan). The
EconoMi$er IV control does not support space temperature
sensors. Connections are made at the thermostat terminal
connection board located in the main control box.
Occupancy Control
The factory default configuration for the EconoMi$er IV con-
trol is occupied mode. Occupied status is provided by the
black jumper from terminal TR to terminal N. When unoccu-
pied mode is desired, install a field-supplied timeclock func-
tion in place of the jumper between TR and N. See Fig. 27.
When the timeclock contacts are closed, the EconoMi$er IV
control will be in occupied mode. When the timeclock con-
tacts are open (removing the 24-v signal from terminal N),
the EconoMi$er IV will be in unoccupied mode.
Once the fully occupied damper position has been deter-
mined, set the maximum damper demand control ventilation
potentiometer to this position. Do not set to the maximum
position as this can result in over-ventilation to the space
and potential high-humidity levels.
CO2 Sensor Configuration
The CO2 sensor has preset standard voltage settings that
can be selected anytime after the sensor is powered up. See
Table 5.
Demand Controlled Ventilation (DCV)
When using the EconoMi$er IV for demand controlled venti-
lation, there are some equipment selection criteria which
should be considered. When selecting the heat capacity and
cool capacity of the equipment, the maximum ventilation
rate must be evaluated for design conditions. The maximum
damper position must be calculated to provide the desired
fresh air.
Use setting 1 or 2 for Bryant equipment. See Table 5.
1. Press Clear and Mode buttons. Hold at least 5 sec-
onds until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to select the preset number.
See Table 5.
Typically the maximum ventilation rate will be about 5 to
10% more than the typical cfm required per person, using
normal outside air design criteria.
4. Press Enter to lock in the selection.
5. Press Mode to exit and resume normal operation.
A proportional anticipatory strategy should be taken with
the following conditions: a zone with a large area, varied
occupancy, and equipment that cannot exceed the required
ventilation rate at design conditions. Exceeding the required
ventilation rate means the equipment can condition air at a
maximum ventilation rate that is greater than the required
ventilation rate for maximum occupancy. A proportional-
anticipatory strategy will cause the fresh air supplied to
increase as the room CO2 level increases even though the
CO2 set point has not been reached. By the time the CO2
level reaches the set point, the damper will be at maximum
ventilation and should maintain the set point.
The custom settings of the CO2 sensor can be changed any-
time after the sensor is energized. Follow the steps below to
change the non-standard settings:
1. Press Clear and Mode buttons. Hold at least 5 sec-
onds until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to toggle to the NONSTD
menu and press Enter.
4. Use the Up/Down button to toggle through each of
the nine variables, starting with Altitude, until the
desired setting is reached.
In order to have the CO2 sensor control the economizer
damper in this manner, first determine the damper voltage
output for minimum or base ventilation. Base ventilation is
the ventilation required to remove contaminants during
unoccupied periods. The following equation may be used to
determine the percent of outside-air entering the building for
a given damper position. For best results there should be at
least a 10 degree difference in outside and return-air tem-
peratures.
5. Press Mode to move through the variables.
6. Press Enter to lock in the selection, then press Mode
to continue to the next variable.
Dehumidification of Fresh Air with DCV Control
Information from ASHRAE indicates that the largest humid-
ity load on any zone is the fresh air introduced. For some
applications, a device such as an energy recovery unit is
added to reduce the moisture content of the fresh air being
brought into the building when the enthalpy is high. In most
cases, the normal heating and cooling processes are more
than adequate to remove the humidity loads for most com-
mercial applications.
OA
100
RA
100
(TO
x
) + (TR
x
) = TM
TO = Outdoor-Air Temperature
OA = Percent of Outdoor Air
TR = Return-Air Temperature
RA = Percent of Return Air
TM = Mixed-Air Temperature
If normal rooftop heating and cooling operation is not ade-
quate for the outdoor humidity level, an energy recovery unit
and/or a dehumidification option should be considered.
—21—
Table 5 — CO2 Sensor Standard Settings
VENTILATION
RATE
(cfm/Person)
CO2
CONTROL RANGE
(ppm)
OPTIONAL
RELAY SETPOINT
(ppm)
RELAY
HYSTERESIS
(ppm)
ANALOG
OUTPUT
SETTING
EQUIPMENT
OUTPUT
0-10V
1
2
3
4
5
6
7
8
9
Proportional
Proportional
Exponential
Proportional
Proportional
Exponential
Exponential
Proportional
Proportional
Any
Any
Any
15
0-2000
0-2000
0-2000
0-1100
0- 900
0-1100
0- 900
0-9999
0-2000
1000
1000
1100
1100
900
50
50
4-20 mA
Interface w/Standard
2-10V
7-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
Building Control System
50
50
20
50
Economizer
15
1100
900
50
20
50
Health & Safety
—
5000
700
500
50
Parking/Air Intakes/
Loading Docks
—
LEGEND
ppm — Parts Per Million
IX. STEP 9 — ADJUST EVAPORATOR-FAN SPEED
speed. Increasing fan speed increases load on motor.
Do not exceed maximum speed specified in Table 1.
Adjust evaporator-fan speed to meet jobsite conditions.
Tables 6A and 6B show fan rpm at motor pulley settings for
standard and alternate motors. Tables 7 and 8 show evapora-
tor fan motor data. Table 9 shows EconoMi$er IV pressure
drop. Table 10 shows sound data. Refer to Tables 11-28 for
fan performance data. See Fig. 38 for Perfect Humidity™ sys-
tem static pressure drop.
5. Set movable flange at nearest keyway of pulley hub
and tighten setscrew. (See Table 1 for speed change
for each full turn of pulley flange.)
To align fan and motor pulleys:
1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft.
NOTE: Before adjusting fan speed, make sure the new fan
speed will provide an acceptable air temperature rise range
on heating as shown in Table 1.
3. Make angular alignment by loosening motor from
mounting plate.
To adjust belt tension:
To change fan speed:
1. Loosen fan motor mounting nuts.
1. Shut off unit power supply.
2. Slide motor mounting plate away from fan scroll for
proper belt tension (1/2-in. deflection with 8 to 10 lb of
force) and tighten mounting nuts (see Fig. 39).
2. Loosen belt by loosening fan motor mounting nuts.
See Fig. 39.
3. Loosen movable pulley flange setscrew (see Fig. 40).
3. Adjust bolt and nut on mounting plate to secure
motor in fixed position.
4. Screw movable flange toward fixed flange to increase
fan speed and away from fixed flange to decrease fan
Table 6A — 581B Fan Rpm at Motor Pulley Setting With Standard Motor*
MOTOR PULLEY TURNS OPEN
UNIT
1
581B
0
/
1
971
1102
1389
1492
11/2
935
1061
1354
1445
2
898
1019
1318
1399
21/2
862
3
31/2
789
4
41/2
716
812
1141
1166
5
51/2
—
—
1070
—
6
—
—
1035
—
2
036
1044
1185
1460
1585
1008
1144
1425
1538
826
936
1248
1305
753
853
1177
1212
680
770
1106
1119
048
060 (single and 3-phase)
072
978
895
1283
1352
1212
1259
*Approximate fan rpm shown (standard motor/drive).
Table 6B — 581B Fan Rpm at Motor Pulley Setting With High-Static Motor*
MOTOR PULLEY TURNS OPEN
UNIT
581B
1
0
/
2
1
11/2
2
21/2
3
31/2
4
41/2
5
51/2
6
036
048
060
072
1455
1455
1685
1685
1423
1423
1589
1589
1392
1392
1557
1557
1360
1360
1525
1525
1328
1328
1493
1493
1297
1297
1460
1460
1265
1265
1428
1428
1233
1233
1396
1396
1202
1202
1364
1364
1170
1170
1332
1332
1138
1138
1300
1300
1107
1107
—
1075
1075
—
—
—
*Approximate fan rpm shown (high-static motor/drive).
—22—
0.35
0.3
0.25
0.2
0.15
0.1
4 & 5 ton
6 ton
0.05
0
3 ton
4000
1000
3000
2000
5000
6000
0
Fig. 38 — Humidi-MiZer™ Adaptive Dehumidification System Static Pressure Drop (in. wg)
MOTOR MOUNTING
PLATE NUTS
Fig. 39 — Belt-Drive Motor Mounting
Fig. 40 — Evaporator-Fan Pulley Adjustment
Table 7 — Evaporator-Fan Motor Data — Standard Motor
UNIT
581B
UNIT
PHASE
MAXIMUM
CONTINUOUS BHP*
MAXIMUM
OPERATING WATTS*
MAXIMUM
AMP DRAW
UNIT VOLTAGE
Single
Three
Single
Three
Single
Three
1.20
1.20
1.20
1.20
1.30
2.40
1000
1000
1000
1000
1650
2120
208/230
208/230
460
4.9
4.9
2.2
2.2
4.9
4.9
2.2
2.2
10.1
6.7
3.0
3.0
6.7
3.0
3.0
036
048
575
208/230
208/230
460
575
208/230
208/230
460
575
208/230
460
060
072
Three
2.40
2120
575
LEGEND
Bhp — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the
full horsepower and watts range of the motors can be utilized with con-
fidence. Using the fan motors up to the ratings shown in this table will
not result in nuisance tripping or premature motor failure. Unit warranty
will not be affected.
—23—
Table 8 — Evaporator-Fan Motor Data — High-Static Motors
UNIT
581B
UNIT
PHASE
MAXIMUM
CONTINUOUS BHP*
MAXIMUM
OPERATING WATTS*
MAXIMUM
AMP DRAW
UNIT VOLTAGE
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
6.7
3.0
3.0
6.7
3.0
3.0
8.6
3.9
3.9
8.6
3.9
3.9
036
046
060
072
Three
Three
Three
Three
2.40
2.40
2.90
2.90
2120
2120
2615
2615
LEGEND
Bhp — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the
full horsepower and watts range of the motors can be utilized with con-
fidence. Using the fan motors up to the ratings shown in this table will
not result in nuisance tripping or premature motor failure. Unit warranty
will not be affected.
Table 9 — Accessory/FIOP EconoMi$er IV Static Pressure* (in. wg)
CFM
COMPONENT
1250
0.045
—
1500
0.065
—
1750
0.08
0.1
2000
0.12
0.125
2250
0.145
0.15
2500
0.175
0.18
2750
0.22
0.225
3000
0.255
0.275
Vertical EconoMi$er IV
Horizontal EconoMi$er IV
LEGEND
FIOP — Factory-Installed Option
*The static pressure must be added to external static pressure. The
sum and the evaporator entering-air cfm should be used in conjunction
with the Fan Performance tables to determine indoor blower rpm and
watts.
Table 10 — Outdoor Sound Power (Total Unit)
OCTAVE BANDS
ARI RATING
UNIT
581B
(decibels)
63
55.9
59.1
125
66.0
68.9
250
64.0
68.7
500
66.2
71.9
1000
68.4
74.0
2000
64.5
68.9
4000
61.7
65.7
8000
57.3
59.0
036-048
060-072
76
80
LEGEND
Air Conditioning and Refrigeration Institute
ARI
—
Table 11 — Fan Performance 581B036 — Vertical Discharge Units; Standard Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
CFM
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
900
1000
1100
1200
1300
1400
1500
567
599
632
666
701
737
773
0.15
0.18
0.22
0.26
0.31
0.36
0.42
145
177
215
257
306
361
422
688
717
747
778
810
842
875
0.22
0.27
0.31
0.37
0.43
0.49
0.57
222
265
313
367
426
491
564
786
814
842
871
901
931
963
0.30
0.35
0.41
0.47
0.54
0.62
0.70
296
349
407
471
540
616
699
871
897
0.37
0.43
0.50
0.57
0.65
0.74
0.84
368
430
498
572
651
738
831
947
972
0.44
0.51
0.59
0.67
0.76
0.86
0.96
437
509
587
670
760
856
960
925
999
952
981
1010
1040
1025
1053
1081
1110
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
CFM
1.2
Bhp
1.4
Bhp
1.8
Bhp
2.0
Bhp
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Watts
Rpm
Watts
900
1000
1100
1200
1300
1400
1500
1016
1041
1066
1093
1119
1147
1175
0.51
0.59
0.68
0.77
0.87
0.98
1.09
505
587
674
767
866
972
1086
1080
1104
1129
1155
1181
1208
—
0.57
0.67
0.76
0.87
0.98
1.09
—
572
662
759
861
970
1086
—
1139
1163
1188
1213
1239
—
0.64
0.74
0.85
0.96
1.08
—
637
737
843
955
1073
—
1195
1219
1243
1268
1294
—
0.71
0.81
0.93
1.05
1.18
—
702
811
925
1047
1175
—
1249
1272
1296
1321
—
0.77
0.89
1.01
1.14
—
765
883
1007
1137
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
— Brake Horsepower
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 1.20.
Bhp
3. See page 33 for general fan performance notes.
*Motor drive range: 680 to 1044 rpm. All other rpms require field-
supplied drive.
—24—
Table 12 — Fan Performance 581B036 — Vertical Discharge Units; High-Static Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
CFM
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
900
1000
1100
1200
1300
1400
1500
567
599
632
666
701
737
773
0.15
0.18
0.22
0.26
0.31
0.36
0.42
145
177
215
257
306
361
422
688
717
747
778
810
842
875
0.22
0.27
0.31
0.37
0.43
0.49
0.57
222
265
313
367
426
491
564
786
814
842
871
901
931
963
0.30
0.35
0.41
0.47
0.54
0.62
0.70
296
349
407
471
540
616
699
871
897
0.37
0.43
0.50
0.57
0.65
0.74
0.84
368
430
498
572
651
738
831
947
972
0.44
0.51
0.59
0.67
0.76
0.86
0.96
437
509
587
670
760
856
960
925
999
952
1025
1053
1081
1110
981
1010
1040
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
CFM
1.2
Bhp
1.4
Bhp
1.8
Bhp
2.0
Bhp
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Watts
Rpm
Watts
900
1000
1100
1200
1300
1400
1500
1016
1041
1066
1093
1119
1147
1175
0.51
0.59
0.68
0.77
0.87
0.98
1.09
505
587
674
767
866
972
1086
1080
1104
1129
1155
1181
1208
1235
0.57
0.67
0.76
0.87
0.98
1.09
1.22
572
662
1139
1163
1188
1213
1239
1265
1292
0.64
0.74
0.85
0.96
1.08
1.21
1.34
637
737
1195
1219
1243
1268
1294
1320
1346
0.71
0.81
0.93
1.05
1.18
1.32
1.46
702
811
1249
1272
1296
1321
1346
1371
1397
0.77
0.89
1.01
1.14
1.28
1.43
1.58
765
883
1007
1137
1275
1419
1572
759
843
925
861
970
1086
1209
955
1047
1175
1310
1452
1073
1199
1332
LEGEND
— Brake Horsepower
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
Bhp
3. See page 33 for general fan performance notes.
*Motor drive range: 1075 to 1455 rpm. All other rpms require field-
supplied drive.
Table 13 — Fan Performance 581B048 — Vertical Discharge Units; Standard Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
CFM
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1200
1300
1400
1500
1600
1700
1800
1900
2000
666
701
737
773
810
847
885
923
962
0.26
0.31
0.36
0.42
0.49
0.57
0.66
0.75
0.85
257
306
361
422
491
567
652
745
847
778
810
0.37
0.43
0.49
0.57
0.65
0.73
0.83
0.94
1.05
367
426
491
564
643
730
826
930
1043
871
901
0.47
0.54
0.62
0.70
0.79
0.89
1.00
1.11
—
471
540
616
699
790
888
994
1109
—
952
981
0.57
0.65
0.74
0.84
0.94
1.05
1.16
—
572
651
738
831
932
1040
1157
—
1025
1053
1081
1110
1140
1170
—
0.67
0.76
0.86
0.96
1.08
1.20
—
670
760
856
960
1070
1189
—
842
931
1010
1040
1070
1101
1133
—
875
963
994
1027
1060
1093
—
909
943
978
1014
1049
—
—
—
—
—
—
—
—
—
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
CFM
1.2
Bhp
1.4
Bhp
1.8
Bhp
2.0
Bhp
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Watts
Rpm
Watts
1200
1300
1400
1500
1600
1700
1800
1900
2000
1093
1119
1147
1175
—
0.77
0.87
0.98
1.09
—
767
866
972
1086
—
1155
1181
1208
—
0.87
0.98
1.09
—
861
970
1086
—
1213
1239
—
0.96
1.08
—
955
1073
—
1268
1294
—
1.05
1.18
—
1047
1175
—
1321
—
1.14
—
1137
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
— Brake Horsepower
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 1.20.
Bhp
3. See page 33 for general fan performance notes.
*Motor drive range: 770 to 1185 rpm. All other rpms require field-
supplied drive.
—25—
Table 14 — Fan Performance 581B048 — Vertical Discharge Units; High-Static Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
CFM
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1200
1300
1400
1500
1600
1700
1800
1900
2000
666
701
737
773
810
847
885
923
962
0.26
0.31
0.36
0.42
0.49
0.57
0.66
0.75
0.85
257
306
361
422
491
567
652
745
847
778
810
0.37
0.43
0.49
0.57
0.65
0.73
0.83
0.94
1.05
367
426
491
564
643
730
826
930
1043
871
901
0.47
0.54
0.62
0.70
0.79
0.89
1.00
1.11
1.24
471
540
952
981
0.57
0.65
0.74
0.84
0.94
1.05
1.16
1.29
1.42
572
651
1025
1053
1081
1110
1140
1170
1200
1231
1263
0.67
0.76
0.86
0.96
1.08
1.20
1.32
1.46
1.61
670
760
842
931
616
1010
1040
1070
1101
1133
1165
1198
738
856
875
963
994
1027
1060
1093
1127
699
831
932
1040
1157
1283
1417
960
909
790
1070
1189
1316
1453
1598
943
888
978
994
1014
1049
1109
1233
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
CFM
1.2
Bhp
1.4
Bhp
1.8
Bhp
2.0
Bhp
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Watts
Rpm
Watts
1200
1300
1400
1500
1600
1700
1800
1900
2000
1093
1119
1147
1175
1204
1233
1262
1293
1323
0.77
0.87
0.98
1.09
1.21
1.34
1.48
1.63
1.79
767
866
1155
1181
1208
1235
1263
1292
1321
1350
1380
0.87
0.98
1.09
1.22
1.35
1.49
1.64
1.79
1.96
861
970
1213
1239
1265
1292
1320
1348
1376
1405
1434
0.96
1.08
1.21
1.34
1.48
1.63
1.79
1.96
2.13
955
1073
1199
1332
1472
1622
1779
1946
2123
1268
1294
1320
1346
1373
1401
1428
1457
1486
1.05
1.18
1.32
1.46
1.61
1.77
1.94
2.12
2.31
1047
1175
1310
1452
1603
1762
1930
2106
2293
1321
1346
1371
1397
1424
1451
1479
1506
—
1.14
1.28
1.43
1.58
1.74
1.91
2.09
2.28
—
1137
1275
1419
1572
1732
1901
2078
2265
—
972
1086
1209
1340
1480
1627
1784
1950
1086
1207
1336
1473
1620
1776
LEGEND
— Brake Horsepower
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
Bhp
3. See page 33 for general fan performance notes.
*Motor drive range: 1075 to 1455 rpm. All other rpms require field-
supplied drive.
Table 15 — Fan Performance 581B060, Single-Phase — Vertical Discharge Units;
Standard Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
CFM
0.2
Bhp
0.4
Bhp
0.6
0.8
1.0
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
848
887
0.42
0.49
0.57
0.65
0.75
0.85
0.97
1.09
1.23
—
371
433
502
579
663
757
859
970
1091
—
968
1004
1040
1077
1115
1153
1191
1230
—
0.55
0.63
0.71
0.81
0.91
1.03
1.15
1.29
—
486
556
633
718
811
913
1023
1143
—
1069
1103
1137
1172
1208
1244
—
0.68
0.76
0.86
0.96
1.08
1.20
—
600
678
763
856
957
1066
—
1158
1190
1223
1257
1291
—
0.80
0.90
1.00
1.12
1.24
—
715
800
892
993
1101
—
1238
1269
1302
1334
—
0.94
1.04
1.15
1.27
—
831
922
1022
1130
—
927
967
1007
1048
1090
1131
1173
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
CFM
1.2
Bhp
1.4
Bhp
1.8
Bhp
2.0
Bhp
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Watts
Rpm
Watts
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
1312
1342
1374
—
1.07
1.18
1.30
—
948
1047
1153
—
1380
—
1.20
—
—
—
—
—
—
—
—
—
—
1067
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
— Brake Horsepower
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 1.30.
Bhp
3. See page 33 for general fan performance notes.
*Motor drive range: 1035 to 1460 rpm. All other rpms require field-
supplied drive.
—26—
Table 16 — Fan Performance 581B060, Three-Phase — Vertical Discharge Units;
Standard Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
CFM
0.2
Bhp
0.4
Bhp
0.6
0.8
1.0
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
848
887
0.42
0.49
0.57
0.65
0.75
0.85
0.97
1.09
1.23
1.38
1.54
371
433
968
1004
1040
1077
1115
1153
1191
1230
1269
1309
1349
0.55
0.63
0.71
0.81
0.91
1.03
1.15
1.29
1.43
1.59
1.76
486
556
1069
1103
1137
1172
1208
1244
1281
1318
1355
1393
1431
0.68
0.76
0.86
0.96
1.08
1.20
1.33
1.48
1.63
1.80
1.98
600
678
1158
1190
1223
1257
1291
1326
1361
1397
1433
1470
1506
0.80
0.90
1.00
1.12
1.24
1.37
1.51
1.67
1.83
2.01
2.20
715
800
1238
1269
1302
1334
1368
1401
1435
1470
1505
1540
—
0.94
1.04
1.15
1.27
1.40
1.54
1.69
1.86
2.03
2.21
—
831
922
927
502
633
763
892
1022
1130
1246
1371
1505
1649
1803
1967
—
967
579
718
856
957
993
1007
1048
1090
1131
1173
1215
1258
663
811
1101
1219
1345
1481
1627
1784
1951
757
913
1066
1185
1313
1451
1600
1759
859
1023
1143
1273
1413
1564
970
1091
1223
1365
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
CFM
1.2
Bhp
1.4
Bhp
1.8
Bhp
2.0
Bhp
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Watts
Rpm
Watts
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
1312
1342
1374
1406
1438
1471
1504
1538
1572
—
1.07
1.18
1.30
1.43
1.57
1.72
1.87
2.04
2.23
—
948
1047
1153
1268
1391
1523
1665
1816
1978
—
1380
1411
1441
1473
1504
1536
1569
1602
—
1.20
1.32
1.45
1.58
1.73
1.89
2.06
2.23
—
1067
1173
1286
1407
1537
1677
1825
1984
—
1445
1474
1505
1535
1567
1598
1630
—
1.34
1.46
1.60
1.74
1.90
2.06
2.24
—
1189
1300
1420
1548
1685
1831
1986
—
1506
1535
1565
1595
1626
1657
—
1.48
1.61
1.75
1.90
2.06
2.24
—
1312
1429
1555
1690
1833
1986
—
1564
1593
1622
1652
1682
—
1.62
1.76
1.91
2.06
2.23
—
1437
1560
1692
1833
1983
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
— Brake Horsepower
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
Bhp
3. See page 33 for general fan performance notes.
*Motor drive range: 1035 to 1460 rpm. All other rpms require field-
supplied drive.
Table 17 — Fan Performance 581B060 — Vertical Discharge Units; High-Static Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
CFM
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
848
887
0.42
0.49
0.57
0.65
0.75
0.85
0.97
1.09
1.23
1.38
1.54
371
433
968
1004
1040
1077
1115
1153
1191
1230
1269
1309
1349
0.55
0.63
0.71
0.81
0.91
1.03
1.15
1.29
1.43
1.59
1.76
486
556
1069
1103
1137
1172
1208
1244
1281
1318
1355
1393
1431
0.68
0.76
0.86
0.96
1.08
1.20
1.33
1.48
1.63
1.80
1.98
600
678
1158
1190
1223
1257
1291
1326
1361
1397
1433
1470
1506
0.80
0.90
1.00
1.12
1.24
1.37
1.51
1.67
1.83
2.01
2.20
715
800
1238
1269
1302
1334
1368
1401
1435
1470
1505
1540
1576
0.94
1.04
1.15
1.27
1.40
1.54
1.69
1.86
2.03
2.21
2.41
831
922
927
502
633
763
892
1022
1130
1246
1371
1505
1649
1803
1967
2142
967
579
718
856
957
993
1007
1048
1090
1131
1173
1215
1258
663
811
1101
1219
1345
1481
1627
1784
1951
757
913
1066
1185
1313
1451
1600
1759
859
1023
1143
1273
1413
1564
970
1091
1223
1365
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
CFM
1.2
Bhp
1.4
Bhp
1.8
Bhp
2.0
Bhp
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Watts
Rpm
Watts
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
1312
1342
1374
1406
1438
1471
1504
1538
1572
1607
1642
1.07
1.18
1.30
1.43
1.57
1.72
1.87
2.04
2.23
2.42
2.63
948
1047
1153
1268
1391
1523
1665
1816
1978
2150
2333
1380
1411
1441
1473
1504
1536
1569
1602
1635
1669
1704
1.20
1.32
1.45
1.58
1.73
1.89
2.06
2.23
2.42
2.63
2.84
1067
1173
1286
1407
1537
1677
1825
1984
2153
2332
2523
1445
1474
1505
1535
1567
1598
1630
1663
1695
1729
—
1.34
1.46
1.60
1.74
1.90
2.06
2.24
2.42
2.62
2.83
—
1189
1300
1420
1548
1685
1831
1986
2152
2328
2515
—
1506
1535
1565
1595
1626
1657
1688
1720
1753
—
1.48
1.61
1.75
1.90
2.06
2.24
2.42
2.61
2.82
—
1312
1429
1555
1690
1833
1986
2149
2321
2504
—
1564
1593
1622
1652
1682
1713
1744
1775
—
1.62
1.76
1.91
2.06
2.23
2.41
2.60
2.81
—
1437
1560
1692
1833
1983
2142
2312
2491
—
—
—
—
—
—
—
—
—
—
LEGEND
— Brake Horsepower
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
Bhp
3. See page 33 for general fan performance notes.
*Motor drive range: 1300 to 1685 rpm. All other rpms require field-
supplied drive.
—27—
Table 18 — Fan Performance 581B072 — Vertical Discharge Units; Standard Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
CFM
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
967
1008
1049
1091
1133
1176
1218
1261
1305
1348
1392
1435
1479
0.63
0.72
0.82
0.93
1.05
1.18
1.32
1.47
1.63
1.80
1.99
2.19
2.40
563
643
1075
1112
1151
1189
1229
1268
1308
1349
1390
1431
1472
—
0.80
0.91
1.02
1.14
1.26
1.40
1.55
1.72
1.89
2.07
2.27
—
715
805
1170
1205
1241
1278
1315
1352
1390
1429
1468
1507
—
0.97
1.08
1.20
1.33
1.47
1.62
1.78
1.96
2.14
2.33
—
861
960
1255
1289
1323
1358
1393
1429
1466
1503
1540
—
1.13
1.25
1.38
1.52
1.67
1.84
2.01
2.19
2.38
—
1002
1111
1228
1353
1487
1630
1782
1945
2117
—
1333
1366
1399
1433
1467
1501
1537
—
1.28
1.42
1.56
1.71
1.87
2.04
2.23
—
1139
1258
1384
1519
1662
1815
1977
—
731
903
1068
1183
1308
1441
1584
1736
1900
2073
—
827
933
1008
1123
1247
1380
1523
1677
1841
2016
—
1047
1170
1304
1448
1602
1768
1945
2135
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
CFM
1.2
Bhp
1.4
Bhp
1.8
Bhp
2.0
Bhp
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Watts
Rpm
Watts
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
1406
1438
1470
1502
1535
1569
—
1.43
1.58
1.73
1.89
2.06
2.25
—
1273
1401
1537
1681
1834
1996
—
1475
1505
1537
1568
1600
—
1.58
1.73
1.90
2.07
2.25
—
1403
1541
1686
1840
2002
—
1540
1569
1600
1631
—
1.72
1.89
2.06
2.25
—
1531
1678
1833
1996
—
1601
1630
1660
—
1.87
2.04
2.23
—
1657
1813
1977
—
1660
1689
1718
—
2.00
2.19
2.38
—
1780
1945
2118
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
— Brake Horsepower
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
Bhp
3. See page 33 for general fan performance notes.
*Motor drive range: 1119 to 1585 rpm. All other rpms require field-
supplied drive.
Table 19 — Fan Performance 581B072 — Vertical Discharge Units; High-Static Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
CFM
0.2
Bhp
0.4
Bhp
0.6
0.8
1.0
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
967
1008
1049
1091
1133
1176
1218
1261
1305
1348
1392
1435
1479
0.63
0.72
0.82
0.93
1.05
1.18
1.32
1.47
1.63
1.80
1.99
2.19
2.40
563
643
1075
1112
1151
1189
1229
1268
1308
1349
1390
1431
1472
1514
1556
0.80
0.91
1.02
1.14
1.26
1.40
1.55
1.72
1.89
2.07
2.27
2.48
2.70
715
805
1170
1205
1241
1278
1315
1352
1390
1429
1468
1507
1547
1587
—
0.97
1.08
1.20
1.33
1.47
1.62
1.78
1.96
2.14
2.33
2.54
2.76
—
861
960
1255
1289
1323
1358
1393
1429
1466
1503
1540
1578
1616
—
1.13
1.25
1.38
1.52
1.67
1.84
2.01
2.19
2.38
2.59
2.81
—
1002
1111
1228
1353
1487
1630
1782
1945
2117
2301
2495
—
1333
1366
1399
1433
1467
1501
1537
1572
1608
1645
—
1.28
1.42
1.56
1.71
1.87
2.04
2.23
2.42
2.62
2.84
—
1139
1258
1384
1519
1662
1815
1977
2149
2331
2524
—
731
903
1068
1183
1308
1441
1584
1736
1900
2073
2258
2455
—
827
933
1008
1123
1247
1380
1523
1677
1841
2016
2203
2402
1047
1170
1304
1448
1602
1768
1945
2135
—
—
—
—
—
—
—
—
—
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
CFM
1.2
Bhp
1.4
Bhp
1.8
Bhp
2.0
Bhp
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Watts
Rpm
Watts
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
1406
1438
1470
1502
1535
1569
1603
1638
1673
—
1.43
1.58
1.73
1.89
2.06
2.25
2.44
2.64
2.86
—
1273
1401
1537
1681
1834
1996
2167
2349
2541
—
1475
1505
1537
1568
1600
1633
1666
1700
—
1.58
1.73
1.90
2.07
2.25
2.45
2.65
2.87
—
1403
1541
1686
1840
2002
2174
2355
2546
—
1540
1569
1600
1631
1662
1694
1727
—
1.72
1.89
2.06
2.25
2.44
2.64
2.86
—
1531
1678
1833
1996
2167
2348
2539
—
1601
1630
1660
1690
1721
1752
—
1.87
2.04
2.23
2.42
2.62
2.84
—
1657
1813
1977
2149
2330
2520
—
1660
1689
1718
1747
1778
—
2.00
2.19
2.38
2.59
2.80
—
1780
1945
2118
2300
2490
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
— Brake Horsepower
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
Bhp
3. See page 33 for general fan performance notes.
*Motor drive range: 1300 to 1685 rpm. All other rpms require field-
supplied drive.
—28—
Table 20 — Fan Performance 581B036 — Horizontal Discharge Units; Standard Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
CFM
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
900
1000
1100
1200
1300
1400
1500
553
582
612
643
675
707
740
0.14
0.16
0.20
0.23
0.28
0.33
0.38
134
163
196
234
277
326
382
681
707
734
762
790
819
849
0.22
0.26
0.30
0.34
0.40
0.45
0.52
221
257
297
343
394
452
515
782
807
833
859
886
913
941
0.32
0.36
0.41
0.46
0.52
0.58
0.66
316
358
405
458
517
581
653
870
894
919
944
969
996
1023
0.42
0.47
0.52
0.58
0.65
0.72
0.80
417
466
519
579
644
716
795
948
971
0.53
0.58
0.64
0.71
0.78
0.86
0.95
526
580
639
705
777
855
941
995
1020
1044
1070
1096
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
CFM
1.2
Bhp
1.4
Bhp
1.8
Bhp
2.0
Bhp
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Watts
Rpm
Watts
900
1000
1100
1200
1300
1400
1500
1019
1042
1065
1089
1113
1138
1163
0.64
0.70
0.77
0.84
0.92
1.01
1.10
640
700
1084
1107
1130
1153
1177
1201
—
0.76
0.83
0.90
0.98
1.06
1.15
—
760
825
896
974
1058
1149
—
1146
1168
1190
1213
—
0.89
0.96
1.04
1.12
—
885
956
1032
1115
—
1203
1225
1247
—
1.02
1.10
1.18
—
1016
1091
1173
—
1258
—
1.16
—
1152
—
765
—
—
—
837
—
—
—
915
—
—
—
—
—
—
1000
1092
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
— Brake Horsepower
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 1.20.
Bhp
3. See page 33 for general fan performance notes.
*Motor drive range: 680 to 1044 rpm. All other rpms require field-
supplied drive.
Table 21 — Fan Performance 581B036 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
CFM
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
900
1000
1100
1200
1300
1400
1500
553
582
612
643
675
707
740
0.14
0.16
0.20
0.23
0.28
0.33
0.38
134
163
196
234
277
326
382
681
707
734
762
790
819
849
0.22
0.26
0.30
0.34
0.40
0.45
0.52
221
257
297
343
394
452
515
782
807
833
859
886
913
941
0.32
0.36
0.41
0.46
0.52
0.58
0.66
316
358
405
458
517
581
653
870
894
919
944
969
996
1023
0.42
0.47
0.52
0.58
0.65
0.72
0.80
417
466
519
579
644
716
795
948
971
0.53
0.58
0.64
0.71
0.78
0.86
0.95
526
580
639
705
777
855
941
995
1020
1044
1070
1096
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
CFM
1.2
Bhp
1.4
Bhp
1.8
Bhp
2.0
Bhp
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Watts
Rpm
Watts
900
1000
1100
1200
1300
1400
1500
1019
1042
1065
1089
1113
1138
1163
0.64
0.70
0.77
0.84
0.92
1.01
1.10
640
700
1084
1107
1130
1153
1177
1201
1226
0.76
0.83
0.90
0.98
1.06
1.15
1.25
760
825
1146
1168
1190
1213
1237
1261
1285
0.89
0.96
1.04
1.12
1.21
1.31
1.41
885
956
1032
1115
1205
1303
1407
1203
1225
1247
1270
1293
1317
1341
1.02
1.10
1.18
1.27
1.36
1.47
1.58
1016
1091
1173
1262
1358
1461
1571
1258
1279
1301
1324
1347
1370
1394
1.16
1.24
1.33
1.42
1.52
1.63
1.75
1152
1232
1319
1413
1514
1623
1740
765
896
837
915
1000
1092
974
1058
1149
1247
LEGEND
— Brake Horsepower
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
Bhp
3. See page 33 for general fan performance notes.
*Motor drive range: 1075 to 1455 rpm. All other rpms require field-
supplied drive.
—29—
Table 22 — Fan Performance 581B048 — Horizontal Discharge Units; Standard Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
CFM
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1200
1300
1400
1500
1600
1700
1800
1900
2000
643
675
707
740
773
807
841
875
910
0.23
0.28
0.33
0.38
0.45
0.52
0.59
0.68
0.77
234
277
326
382
444
513
589
674
767
762
790
819
849
879
910
942
974
1006
0.34
0.40
0.45
0.52
0.59
0.67
0.75
0.85
0.95
343
394
452
515
586
663
749
842
944
859
886
0.46
0.52
0.58
0.66
0.73
0.82
0.91
1.02
1.13
458
517
944
969
0.58
0.65
0.72
0.80
0.88
0.98
1.08
1.19
—
579
644
716
795
880
973
1074
1184
—
1020
1044
1070
1096
1123
1150
—
0.71
0.78
0.86
0.95
1.04
1.14
—
705
777
855
941
1034
1134
—
913
581
996
941
653
1023
1050
1078
1106
1135
—
970
731
999
817
1029
1059
1090
910
1012
1122
—
—
—
—
—
—
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
CFM
1.2
Bhp
1.4
Bhp
1.8
Bhp
2.0
Bhp
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Watts
Rpm
Watts
1200
1300
1400
1500
1600
1700
1800
1900
2000
1089
1113
1138
1163
1189
—
0.84
0.92
1.01
1.10
1.20
—
837
915
1000
1092
1191
—
1153
1177
1201
—
0.98
1.06
1.15
—
974
1058
1149
—
1213
—
1.12
—
1115
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
— Brake Horsepower
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 1.20.
Bhp
3. See page 33 for general fan performance notes.
*Motor drive range: 770 to 1185 rpm. All other rpms require field-
supplied drive.
Table 23 — Fan Performance 581B048 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
CFM
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1200
1300
1400
1500
1600
1700
1800
1900
2000
643
675
707
740
773
807
841
875
910
0.23
0.28
0.33
0.38
0.45
0.52
0.59
0.68
0.77
234
277
326
382
444
513
589
674
767
762
790
819
849
879
910
942
974
1006
0.34
0.40
0.45
0.52
0.59
0.67
0.75
0.85
0.95
343
394
452
515
586
663
749
842
944
859
886
0.46
0.52
0.58
0.66
0.73
0.82
0.91
1.02
1.13
458
517
944
969
0.58
0.65
0.72
0.80
0.88
0.98
1.08
1.19
1.31
579
644
1020
1044
1070
1096
1123
1150
1177
1205
1234
0.71
0.78
0.86
0.95
1.04
1.14
1.25
1.37
1.49
705
777
913
581
996
716
855
941
653
1023
1050
1078
1106
1135
1165
795
941
970
731
880
1034
1134
1242
1360
1485
999
817
973
1029
1059
1090
910
1074
1184
1302
1012
1122
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
CFM
1.2
Bhp
1.4
Bhp
1.8
Bhp
2.0
Bhp
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Watts
Rpm
Watts
1200
1300
1400
1500
1600
1700
1800
1900
2000
1089
1113
1138
1163
1189
1216
1242
1270
1297
0.84
0.92
1.01
1.10
1.20
1.31
1.42
1.55
1.68
837
915
1153
1177
1201
1226
1252
1277
1303
1330
1357
0.98
1.06
1.15
1.25
1.36
1.48
1.60
1.73
1.87
974
1058
1149
1247
1353
1468
1590
1721
1862
1213
1237
1261
1285
1310
1335
1361
1387
1414
1.12
1.21
1.31
1.41
1.53
1.65
1.78
1.92
2.07
1115
1205
1303
1407
1520
1640
1770
1908
2055
1270
1293
1317
1341
1365
1390
1415
1441
1467
1.27
1.36
1.47
1.58
1.70
1.83
1.96
2.11
2.26
1262
1358
1461
1571
1690
1817
1953
2098
2252
1324
1347
1370
1394
1418
1442
1467
1493
—
1.42
1.52
1.63
1.75
1.87
2.01
2.15
2.30
—
1413
1514
1623
1740
1865
1998
2140
2292
—
1000
1092
1191
1299
1414
1538
1672
LEGEND
— Brake Horsepower
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
Bhp
3. See page 33 for general fan performance notes.
*Motor drive range: 1075 to 1455 rpm. All other rpms require field-
supplied drive.
—30—
Table 24 — Fan Performance 581B060, Single-Phase — Horizontal Discharge Units;
Standard Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
CFM
0.2
Bhp
0.4
Bhp
0.6
0.8
1.0
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
800
839
879
919
960
1001
1043
1085
1127
—
0.39
0.46
0.54
0.63
0.73
0.84
0.96
1.09
1.23
—
350
412
483
561
648
744
850
966
1092
—
904
938
974
1010
1047
1085
1123
1162
—
0.49
0.57
0.65
0.75
0.85
0.96
1.09
1.22
—
438
505
580
663
754
855
965
1086
—
999
1030
1062
1095
1129
1163
1199
—
0.60
0.68
0.77
0.87
0.98
1.09
1.22
—
535
605
684
771
867
972
1086
—
1087
1115
1144
1174
1206
1238
—
0.72
0.80
0.90
1.00
1.11
1.23
—
640
714
796
886
986
1095
—
1169
1195
1221
1250
1279
—
0.85
0.93
1.03
1.14
1.25
—
753
829
914
1008
1111
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
CFM
1.2
Bhp
1.4
Bhp
1.8
Bhp
2.0
Bhp
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Watts
Rpm
Watts
—
—
—
—
—
—
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
1247
1270
1295
1321
—
0.98
1.07
1.17
1.28
—
873
952
1040
1137
—
1320
1342
—
1.13
1.22
—
1002
1083
—
1390
—
1.28
—
—
—
—
—
—
—
—
—
—
1137
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
— Brake Horsepower
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 1.30.
Bhp
3. See page 33 for general fan performance notes.
*Motor drive range: 1035 to 1460 rpm. All other rpms require field-
supplied drive.
Table 25 — Fan Performance 581B060, Three-Phase — Horizontal Discharge Units;
Standard Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
CFM
0.2
Bhp
0.4
Bhp
0.6
0.8
1.0
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
800
839
0.39
0.46
0.54
0.63
0.73
0.84
0.96
1.09
1.23
1.38
1.55
350
412
904
938
0.49
0.57
0.65
0.75
0.85
0.96
1.09
1.22
1.37
1.53
1.70
438
505
999
1030
1062
1095
1129
1163
1199
1235
1272
1310
1348
0.60
0.68
0.77
0.87
0.98
1.09
1.22
1.36
1.52
1.68
1.86
535
605
1087
1115
1144
1174
1206
1238
1271
1305
1340
1375
1412
0.72
0.80
0.90
1.00
1.11
1.23
1.37
1.51
1.67
1.84
2.02
640
714
1169
1195
1221
1250
1279
1309
1340
1372
1405
1439
1473
0.85
0.93
1.03
1.14
1.25
1.38
1.52
1.67
1.83
2.00
2.19
753
829
879
483
974
580
684
796
914
919
960
561
1010
1047
1085
1123
1162
1201
1241
1281
663
771
886
986
1008
1111
1224
1346
1479
1623
1778
1945
648
754
867
1001
1043
1085
1127
1169
1212
744
855
972
1095
1213
1342
1482
1633
1796
850
965
1086
1211
1347
1493
1652
966
1086
1217
1359
1513
1092
1229
1378
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
CFM
1.2
Bhp
1.4
Bhp
1.8
Bhp
2.0
Bhp
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Watts
Rpm
Watts
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
1247
1270
1295
1321
1348
1377
1406
1437
1468
1500
1533
0.98
1.07
1.17
1.28
1.40
1.53
1.67
1.83
1.99
2.17
2.36
873
952
1320
1342
1365
1390
1415
1442
1470
1499
1529
1559
—
1.13
1.22
1.32
1.43
1.56
1.69
1.83
1.99
2.16
2.35
—
1002
1083
1173
1273
1381
1500
1629
1769
1920
2083
—
1390
1411
1432
1455
1479
1505
1531
1559
1587
—
1.28
1.37
1.48
1.59
1.72
1.86
2.00
2.16
2.34
—
1137
1221
1313
1415
1526
1648
1780
1923
2077
—
1457
1476
1497
1518
1541
1565
1591
1617
—
1.44
1.54
1.64
1.76
1.89
2.03
2.18
2.34
—
1280
1365
1459
1563
1677
1801
1936
2082
—
1522
1540
1559
1579
1601
1624
1648
—
1.61
1.71
1.82
1.93
2.06
2.21
2.36
—
1430
1517
1612
1718
1834
1961
2098
—
1040
1137
1243
1359
1485
1621
1769
1928
2098
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
— Brake Horsepower
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
Bhp
3. See page 33 for general fan performance notes.
*Motor drive range: 1035 to 1460 rpm. All other rpms require field-
supplied drive.
—31—
Table 26 — Fan Performance 581B060 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
CFM
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
800
839
0.39
0.46
0.54
0.63
0.73
0.84
0.96
1.09
1.23
1.38
1.55
350
412
904
938
0.49
0.57
0.65
0.75
0.85
0.96
1.09
1.22
1.37
1.53
1.70
438
505
999
1030
1062
1095
1129
1163
1199
1235
1272
1310
1348
0.60
0.68
0.77
0.87
0.98
1.09
1.22
1.36
1.52
1.68
1.86
535
605
1087
1115
1144
1174
1206
1238
1271
1305
1340
1375
1412
0.72
0.80
0.90
1.00
1.11
1.23
1.37
1.51
1.67
1.84
2.02
640
714
1169
1195
1221
1250
1279
1309
1340
1372
1405
1439
1473
0.85
0.93
1.03
1.14
1.25
1.38
1.52
1.67
1.83
2.00
2.19
753
829
879
483
974
580
684
796
914
919
960
561
1010
1047
1085
1123
1162
1201
1241
1281
663
771
886
986
1008
1111
1224
1346
1479
1623
1778
1945
648
754
867
1001
1043
1085
1127
1169
1212
744
855
972
1095
1213
1342
1482
1633
1796
850
965
1086
1211
1347
1493
1652
966
1086
1217
1359
1513
1092
1229
1378
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
CFM
1.2
Bhp
1.4
Bhp
1.8
Bhp
2.0
Bhp
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Watts
Rpm
Watts
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
1247
1270
1295
1321
1348
1377
1406
1437
1468
1500
1533
0.98
1.07
1.17
1.28
1.40
1.53
1.67
1.83
1.99
2.17
2.36
873
952
1320
1342
1365
1390
1415
1442
1470
1499
1529
1559
1591
1.13
1.22
1.32
1.43
1.56
1.69
1.83
1.99
2.16
2.35
2.54
1002
1083
1173
1273
1381
1500
1629
1769
1920
2083
2257
1390
1411
1432
1455
1479
1505
1531
1559
1587
1616
1647
1.28
1.37
1.48
1.59
1.72
1.86
2.00
2.16
2.34
2.53
2.73
1137
1221
1313
1415
1526
1648
1780
1923
2077
2243
2421
1457
1476
1497
1518
1541
1565
1591
1617
1644
1672
—
1.44
1.54
1.64
1.76
1.89
2.03
2.18
2.34
2.52
2.71
—
1280
1365
1459
1563
1677
1801
1936
2082
2239
2408
—
1522
1540
1559
1579
1601
1624
1648
1673
1699
1726
—
1.61
1.71
1.82
1.93
2.06
2.21
2.36
2.53
2.71
2.90
—
1430
1517
1612
1718
1834
1961
2098
2246
2406
2579
—
1040
1137
1243
1359
1485
1621
1769
1928
2098
LEGEND
— Brake Horsepower
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
Bhp
3. See page 33 for general fan performance notes.
*Motor drive range: 1300 to 1685 rpm. All other rpms require field-
supplied drive.
Table 27 — Fan Performance 581B072 — Horizontal Discharge Units; Standard Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
CFM
0.2
Bhp
0.4
Bhp
0.6
0.8
1.0
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
913
952
0.64
0.73
0.84
0.95
1.07
1.21
1.36
1.51
1.69
1.87
2.07
2.28
—
569
652
1010
1046
1083
1120
1158
1196
1234
1273
1312
1352
1392
—
0.80
0.91
1.02
1.14
1.27
1.41
1.57
1.73
1.91
2.10
2.31
—
715
805
1098
1131
1166
1200
1236
1272
1308
1345
1382
1420
—
0.98
1.09
1.21
1.33
1.47
1.62
1.78
1.96
2.14
2.34
—
869
965
1178
1210
1242
1275
1308
1343
1377
1412
1448
—
1.16
1.28
1.40
1.54
1.68
1.84
2.01
2.19
2.38
—
1032
1134
1245
1365
1495
1634
1784
1945
2117
—
1252
1282
1313
1345
1377
1409
1443
—
1.35
1.48
1.61
1.75
1.90
2.07
2.24
—
1203
1311
1427
1553
1689
1834
1990
—
992
744
903
1070
1184
1307
1440
1584
1738
1904
2081
—
1032
1073
1114
1155
1196
1238
1280
1322
1364
—
844
954
1010
1127
1254
1391
1538
1697
1867
2050
—
1074
1204
1345
1497
1660
1835
2023
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
CFM
1.2
Bhp
1.4
Bhp
1.8
Bhp
2.0
Bhp
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Watts
Rpm
Watts
—
—
—
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
1322
1351
1380
1411
1441
1473
—
1.56
1.68
1.82
1.97
2.13
2.30
—
1382
1495
1617
1748
1890
2041
—
1388
1416
1444
1473
1503
—
1.77
1.90
2.04
2.20
2.36
—
1568
1686
1814
1950
2097
—
1451
1477
1505
—
1.98
2.12
2.27
—
1762
1885
2017
—
1510
1536
—
2.21
2.35
—
1962
2090
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
— Brake Horsepower
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
Bhp
3. See page 33 for general fan performance notes.
*Motor drive range: 1119 to 1585 rpm. All other rpms require field-
supplied drive.
—32—
Table 28 — Fan Performance 581B072 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
CFM
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
913
952
0.64
0.73
0.84
0.95
1.07
1.21
1.36
1.51
1.69
1.87
2.07
2.28
2.50
569
652
1010
1046
1083
1120
1158
1196
1234
1273
1312
1352
1392
1432
1472
0.80
0.91
1.02
1.14
1.27
1.41
1.57
1.73
1.91
2.10
2.31
2.53
2.76
715
805
1098
1131
1166
1200
1236
1272
1308
1345
1382
1420
1458
1496
—
0.98
1.09
1.21
1.33
1.47
1.62
1.78
1.96
2.14
2.34
2.56
2.78
—
869
965
1178
1210
1242
1275
1308
1343
1377
1412
1448
1484
1521
—
1.16
1.28
1.40
1.54
1.68
1.84
2.01
2.19
2.38
2.59
2.81
—
1032
1134
1245
1365
1495
1634
1784
1945
2117
2300
2496
—
1252
1282
1313
1345
1377
1409
1443
1477
1511
1546
—
1.35
1.48
1.61
1.75
1.90
2.07
2.24
2.43
2.63
2.84
—
1203
1311
1427
1553
1689
1834
1990
2157
2335
2526
—
992
744
903
1070
1184
1307
1440
1584
1738
1904
2081
2270
2472
—
1032
1073
1114
1155
1196
1238
1280
1322
1364
1406
844
954
1010
1127
1254
1391
1538
1697
1867
2050
2245
2452
1074
1204
1345
1497
1660
1835
2023
2224
—
—
—
—
—
—
—
—
—
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
CFM
1.2
Bhp
1.4
Bhp
1.8
Bhp
2.0
Bhp
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Watts
Rpm
Watts
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
1322
1351
1380
1411
1441
1473
1505
1537
1571
—
1.56
1.68
1.82
1.97
2.13
2.30
2.48
2.68
2.88
—
1382
1495
1617
1748
1890
2041
2203
2376
2560
—
1388
1416
1444
1473
1503
1533
1564
—
1.77
1.90
2.04
2.20
2.36
2.54
2.73
—
1568
1686
1814
1950
2097
2254
2422
—
1451
1477
1505
1533
1562
1591
—
1.98
2.12
2.27
2.43
2.60
2.79
—
1762
1885
2017
2159
2311
2474
—
1510
1536
1563
1590
1618
—
2.21
2.35
2.51
2.67
2.85
—
1962
2090
2227
2374
2532
—
1568
1593
1619
—
2.44
2.59
2.75
—
2169
2302
2443
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
— Brake Horsepower
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
Bhp
3. See below for general fan performance notes.
*Motor drive range: 1300 to 1686 rpm. All other rpms require field-
supplied drive.
GENERAL FAN PERFORMANCE NOTES
1. Values include losses for filters, unit casing, and wet coils. See Fig. 38 and
Table 9 for accessory/FIOP static pressure information.
2. Extensive motor and electrical testing on these units ensures that the full range
of the motor can be utilized with confidence. Using the fan motors up to
the ratings shown will not result in nuisance tripping or premature motor failure.
Unit warranty will not be affected. See Tables 7 and 8 for additional information.
3. Use of a field-supplied motor may affect wire sizing. Contact your Bryant repre-
sentative to verify.
4. Interpolation is permissible. Do not extrapolate.
—33—
PRE-START-UP
START-UP
I. UNIT PREPARATION
WARNING: Failure to observe the following warn-
ings could result in serious personal injury.
Make sure that unit has been installed in accordance with
installation instructions and applicable codes.
1. Follow recognized safety practices and wear
protective goggles when checking or servicing
refrigerant system.
II. GAS PIPING
Check gas piping for leaks.
2. Do not operate compressor or provide any elec-
tric power to unit unless compressor terminal
cover is in place and secured.
WARNING: Disconnect gas piping from unit when
1
leak testing at pressure greater than
sures greater than /2 psig will cause gas valve damage
/
psig. Pres-
2
1
3. Do not remove compressor terminal cover until
all electrical sources are disconnected.
resulting in hazardous condition. If gas valve is sub-
1
jected to pressure greater than
/
psig, it must be
2
4. Relieve all pressure from system before touch-
ing or disturbing anything inside terminal box
if refrigerant leak is suspected around compres-
sor terminals.
replaced before use. When pressure testing field-
1
supplied gas piping at pressures of
/
2
psig or less, a
unit connected to such piping must be isolated by man-
ually closing the gas valve.
5. Never attempt to repair soldered connection
while refrigerant system is under pressure.
III. RETURN-AIR FILTERS
Make sure correct filters are installed in unit (see Table 1). Do
not operate unit without return-air filters.
6. Do not use torch to remove any component. Sys-
tem contains oil and refrigerant under pres-
sure. To remove a component, wear protective
goggles and proceed as follows:
IV. OUTDOOR-AIR INLET SCREENS
Outdoor-air inlet screen must be in place before operating
unit.
a. Shut off electrical power and then gas to
unit.
b. Recover refrigerant to relieve all pressure
from system using both high-pressure and
low-pressure ports.
c. Cut component connection tubing with tub-
ing cutter and remove component from
unit.
d. Carefully unsweat remaining tubing stubs
when necessary. Oil can ignite when
exposed to torch flame.
V. COMPRESSOR MOUNTING
Compressors are internally spring mounted. Do not loosen or
remove compressor holddown bolts.
VI. INTERNAL WIRING
Check all electrical connections in unit control boxes.
Tighten as required.
VII. REFRIGERANT SERVICE PORTS
Each unit system has 4 Schrader-type service ports: one on
the suction line, one on the liquid line, and 2 on the compres-
sor discharge line. Be sure that caps on the ports are tight.
Two additional Schrader valves are located under the high-
pressure and low-pressure switches, respectively.
Proceed as follows to inspect and prepare the unit for initial
start-up:
1. Remove all access panels.
2. Read and follow instructions on all WARNING, CAU-
TION, and INFORMATION labels attached to, or
shipped with, unit.
VIII. HIGH FLOW REFRIGERANT VALVES
Two high flow valves are located on the hot gas tube coming
out of the compressor and the suction tube going into the
compressor. Large black plastic caps identify these valves.
These valves have O-rings inside which screw the cap onto a
brass body to prevent leaks. No field access to these valves is
available at this time. Ensure the plastic caps remain on the
valves and are tight or the possibility of refrigerant leakage
could occur.
3. Make the following inspections:
a. Inspect for shipping and handling damages such
as broken lines, loose parts, or disconnected
wires, etc.
b. Inspect for oil at all refrigerant tubing connec-
tions and on unit base. Detecting oil generally
indicates a refrigerant leak. Leak-test all refrig-
erant tubing connections using electronic leak
detector, halide torch, or liquid-soap solution.
c. Inspect all field-wiring and factory-wiring con-
nections. Be sure that connections are completed
and tight. Be sure that wires are not in contact
with refrigerant tubing or sharp edges.
IX. COMPRESSOR ROTATION
On 3-phase units with scroll compressors, it is important to
be certain compressor is rotating in the proper direction. To
determine whether or not compressor is rotating in the
proper direction:
d. Inspect coil fins. If damaged during shipping and
handling, carefully straighten fins with a fin
comb.
1. Connect service gages to suction and discharge pres-
sure fittings.
2. Energize the compressor.
4. Verify the following conditions:
3. The suction pressure should drop and the discharge
pressure should rise, as is normal on any start-up.
a. Make sure that condenser-fan blade are correctly
positioned in fan orifice. See Condenser-Fan
Adjustment section on page 38 for more details.
b. Make sure that air filter(s) is in place.
c. Make sure that condensate drain trap is filled
with water to ensure proper drainage.
If the suction pressure does not drop and the discharge pres-
sure does not rise to normal levels:
1. Note that the evaporator fan (size 060 and 072 only)
is probably also rotating in the wrong direction.
d. Make sure that all tools and miscellaneous loose
parts have been removed.
2. Turn off power to the unit and install lockout tag.
—34—
3. Reverse any two of the unit power leads.
Table 29B — Altitude Compensation* —
581B036-072 Low NOx Units
4. Reenergize to the compressor. Check pressures.
60,000 AND 90,000 BTUH
NOMINAL INPUT
120,000 BTUH
NOMINAL INPUT
The suction and discharge pressure levels should now move
to their normal start-up levels.
ELEVATION
(Ft)
Natural
Gas
Orifice
Size†
Liquid
Propane
Orifice
Size†
Natural
Liquid
Propane
Orifice
Size†
Gas
Orifice
Size†
NOTE: When the compressor is rotating in the wrong direc-
tion, the unit will make an elevated level of noise and will
not provide cooling.
0-2,000
2,000
3,000
4,000
5,000
6,000
7,000
8,000
9,000
10,000
11,000
12,000
13,000
14,000
38
40
41
42
43
43
44
45
46
47
48
49
50
51
45
47
48
49
49
50
50
51
52
52
53
53
54
54
32
33
35
36
37
38
39
41
42
43
44
44
46
47
42
43
43
44
45
45
46
47
48
49
50
51
52
52
X. COOLING
Set space thermostat to OFF position. To start unit, turn on
main power supply. Set system selector switch at COOL
position and fan switch at AUTO. position. Adjust thermo-
stat to a setting below room temperature. Compressor starts
on closure of contactor.
Check unit charge. Refer to Refrigerant Charge section on
page 38.
Reset thermostat at a position above room temperature.
Compressor will shut off. Evaporator fan will shut off after a
30-second delay.
*As the height above sea level increases, there is less oxygen per cubic foot of
air. Therefore, heat input rate should be reduced at higher altitudes.
†Orifice available through your local Bryant distributor.
A. To Shut Off Unit
XII. HEATING
Set system selector switch at OFF position. Resetting ther-
mostat at a position above room temperature shuts unit off
temporarily until space temperature exceeds thermostat
setting. Units are equipped with Cycle-LOC™ protection
device. Unit shuts down on any safety trip, and indicator
light on thermostat comes on. Check reason for all safety
trips.
1. Purge gas supply line of air by opening union ahead
of the gas valve. If gas odor is detected, tighten union
and wait 5 minutes before proceeding.
2. Turn on electrical supply and manual gas valve.
3. Set system switch selector at HEAT position and fan
switch at AUTO. or ON position. Set heating temper-
ature lever above room temperature.
Compressor restart is accomplished by manual reset at the
thermostat by turning the selector switch to OFF and then to
ON position.
4. The induced-draft motor will start.
5. After a call for heating, the main burners should light
within 5 seconds. If the burner does not light, then there
is a 22-second delay before another 5-second try. If the
burner still does not light, the time delay is repeated. If
the burner does not light within 15 minutes, there is a
lockout. To reset the control, break the 24-v power to W1.
XI. MAIN BURNERS
Main burners are factory set and should require no
adjustment.
TO CHECK ignition of main burners and heating controls,
move thermostat set point above room temperature and ver-
ify that the burners light and evaporator fan is energized.
Check heating effect, then lower the thermostat setting
below the room temperature and verify that the burners and
evaporator fan turn off.
6. The evaporator-fan motor will turn on 45 seconds
after burner ignition.
7. The evaporator-fan motor will turn off in 45 seconds
after the thermostat temperature is satisfied.
8. Adjust airflow to obtain a temperature rise within
the range specified on the unit nameplate.
Refer to Tables 29A and 29B for the correct orifice to use at
high altitudes.
NOTE: The default value for the evaporator-fan motor on/off
delay is 45 seconds. The Integrated Gas Unit Controller (IGC)
modifies this value when abnormal limit switch cycles occur.
Based upon unit operating conditions, the on delay can be
reduced to 0 seconds and the off delay can be extended to 180
seconds. When one flash of the LED (light-emitting diode) is
observed, the evaporator-fan on/off delay has been modified.
Table 29A — Altitude Compensation* —
581B036-072 Standard Units
72,000 AND 115,000 BTUH
NOMINAL INPUT
150,000 BTUH
NOMINAL INPUT
ELEVATION
(Ft)
Natural
Gas
Liquid
Propane
Orifice
Size†
Natural
Liquid
Propane
Orifice
Size†
Gas
Orifice
Size†
Orifice
Size†
If the limit switch trips at the start of the heating cycle dur-
ing the evaporator on delay, the time period of the on delay
for the next cycle will be 5 seconds less than the time at
which the switch tripped. (Example: If the limit switch trips
at 30 seconds, the evaporator-fan on delay for the next cycle
will occur at 25 seconds.) To prevent short-cycling, a 5-second
reduction will only occur if a minimum of 10 minutes has
elapsed since the last call for heating.
0-2,000
2,000
3,000
4,000
5,000
6,000
7,000
8,000
9,000
10,000
11,000
12,000
13,000
14,000
33
36
36
37
38
40
41
42
43
44
45
46
47
48
43
44
45
45
46
47
48
49
50
50
51
52
52
53
30
31
31
32
32
34
35
36
37
39
41
42
43
44
38
39
40
41
42
43
43
44
45
46
47
48
49
50
The evaporator-fan off delay can also be modified. Once the
call for heating has ended, there is a 10-minute period dur-
ing which the modification can occur. If the limit switch trips
during this period, the evaporator-fan off delay will increase
by 15 seconds. A maximum of 9 trips can occur, extending
the evaporator-fan off delay to 180 seconds.
*As the height above sea level increases, there is less oxygen per cubic foot of
air. Therefore, heat input rate should be reduced at higher altitudes.
†Orifice available through your local Bryant distributor.
To restore the original default value, reset the power to the
unit.
—35—
A. To Shut Off Unit
decreases because of the increase in fresh air, the outdoor-air
damper will be proportionally closed. Damper position will
follow the higher demand condition from DCV mode or free
cooling mode.
Set system selector switch at off position. Resetting heating
selector lever below room temperature will temporarily shut
unit off until space temperature falls below thermostat setting.
Damper movement from full closed to full open (or vice
versa) will take between 11/2 and 21/2 minutes.
XIII. SAFETY RELIEF
A soft-solder joint at the suction service Schrader port
provides pressure relief under abnormal temperature and
pressure conditions.
If free cooling can be used as determined from the appropri-
ate changeover command (switch, dry bulb, enthalpy curve,
differential dry bulb, or differential enthalpy), a call for cool-
ing (Y1 closes at the thermostat) will cause the control to
modulate the dampers open to maintain the supply air tem-
perature set point at 50 to 55 F.
XIV. VENTILATION (Continuous Fan)
Set fan and system selector switches at ON and OFF posi-
tions, respectively. Evaporator fan operates continuously to
provide constant air circulation. When the evaporator-fan
selector switch is turned to the OFF position, there is a
30-second delay before the fan turns off.
As the supply-air temperature drops below the set point range
of 50 to 55 F, the control will modulate the outdoor-air damp-
ers closed to maintain the proper supply-air temperature.
D. Heating, Units With EconoMi$er IV
XV. OPERATING SEQUENCE
When the room temperature calls for heat, the heating con-
trols are energized as described in the Heating, Units With-
out Economizer section. When the thermostat is satisfied,
the economizer damper moves to the minimum position.
A. Cooling, Units Without Economizer
When thermostat calls for cooling, terminals G and Y1 and
the compressor contactor (C) are energized. The indoor
(evaporator) fan motor (IFM), compressor, and outdoor (con-
denser) fan motor (OFM) start. The OFM runs continuously
while the unit is in cooling. When the thermostat is satisfied,
C is deenergized and the compressor and OFM shut off. After
a 30-second delay, the IFM shuts off. If the thermostat fan
selector switch is in the ON position, the evaporator motor
will run continuously.
E. Units With Perfect Humidity™ Dehumidification
System
Normal Design Cooling Operation
When the rooftop operates under the normal sequence of
operation, the compressors will cycle to maintain indoor con-
ditions. See Fig. 41.
B. Heating, Units Without Economizer
The Perfect Humidity adaptive dehumidification system
includes a factory-installed Motormaster® low ambient con-
trol to keep the head and suction pressure high, allowing
normal design cooling mode operation down to 0° F.
When the thermostat calls for heating, terminal W1 is ener-
gized. The induced-draft motor is energized and the burner
ignition sequence begins. The indoor (evaporator) fan motor
(IFM) is energized 45 seconds after a flame is ignited. When
additional heat is needed, W2 is energized and the high-fire
solenoid on the main gas valve (MGV) is energized. When
the thermostat is satisfied and W1 is deenergized, the IFM
stops after a 45-second time-off delay.
Subcooling Mode
When subcooling mode is initiated, this will energize (close)
the liquid line solenoid valve (LLSV) forcing the hot liquid
refrigerant to enter the subcooling coil (see Fig. 42).
As the hot liquid refrigerant passes through the subcooling/
reheat dehumidification coil, it is exposed to the cold supply
airflow coming through the evaporator coil. The liquid is fur-
ther subcooled to a temperature approaching the evaporator
leaving-air temperature. The liquid then enters a thermostatic
expansion valve (TXV) where the liquid drops to a lower pres-
sure. The TXV does not have a pressure drop great enough to
change the liquid to a 2-phase fluid, so the liquid then enters
the Acutrol™ device at the evaporator coil.
C. Cooling, Units With EconoMi$er IV
When free cooling is not available, the compressors will be
controlled by the zone thermostat. When free cooling is avail-
able, the outdoor-air damper is modulated by the
EconoMi$er IV control to provide a 50 to 55 F supply-air
temperature into the zone. As the supply-air temperature
fluctuates above 55 or below 50 F, the dampers will be modu-
lated (open or close) to bring the supply-air temperature
back within the set points.
The liquid enters the evaporator coil at a temperature lower
than in standard cooling operation. This lower temperature
increases the latent capacity of the rooftop unit. The refriger-
ant passes through the evaporator and is turned into a
vapor. The air passing over the evaporator coil will become
colder than during normal operation. However, as this same
air passes over the subcooling coil, it will be slightly warmed,
partially reheating the air.
Integrated EconoMi$er IV operation on single-stage units
requires a 2-stage thermostat (Y1 and Y2).
For EconoMi$er IV operation, there must be a thermostat
call for the fan (G). This will move the damper to its mini-
mum position during the occupied mode.
If the increase in cooling capacity causes the supply-air tem-
perature to drop below 45 F, then the outdoor-air damper
position will be fully closed. If the supply-air temperature
continues to fall, the outdoor-air damper will close. Control
returns to normal once the supply-air temperature rises
above 48 F.
Subcooling mode operates only when the outside-air temper-
ature is warmer than 40 F. A factory-installed temperature
switch located in the condenser section will lock out subcool-
ing mode when the outside temperature is cooler than 40 F.
The scroll compressors are equipped with crankcase heaters
to provide protection for the compressors due to the addi-
tional refrigerant charge required by the subcooling/reheat
coil.
If optional power exhaust is installed, as the outdoor-air
damper opens and closes, the power exhaust fans will be
energized and deenergized.
If field-installed accessory CO2 sensors are connected to the
EconoMi$er IV control, a demand controlled ventilation
strategy will begin to operate. As the CO2 level in the zone
increases above the CO2 set point, the minimum position of
the damper will be increased proportionally. As the CO2 level
When in subcooling mode, there is a slight decrease in sys-
tem total gross capacity (5% less), a lower gross sensible
capacity (20% less), and a greatly increased latent capacity
(up to 40% more).
—36—
Hot Gas Reheat Mode
When the humidity levels in the space require humidity con-
trol, a hot gas solenoid valve (specific to hot gas reheat mode
only) will open to bypass a portion of hot gas refrigerant
around the condenser coil (see Fig. 43).
This hot gas will mix with liquid refrigerant leaving the con-
denser coil and flow to the subcooling/reheat dehumidification
coil. Now the conditioned air coming off the evaporator will be
cooled and dehumidified, but will be warmed to neutral conditions
(72 F to 75 F) by the subcooling/reheat dehumidification coil.
The net effect of the rooftop when in hot gas reheat mode is to
provide nearly all latent capacity removal from the space when
sensible loads diminish (when outdoor temperature conditions are
moderate). When in hot gas reheat mode, the unit will operate to
provide mostly latent capacity and extremely low sensible heat
ratio capability.
Similar to the subcooling mode of operation, hot gas reheat
mode operates only when the outside-air temperature is warmer
than 40 F. Below this temperature, a factory-installed outside air
temperature switch will lock out this mode of operation.
Fig. 42 — Perfect Humidity Subcooling
Mode Operation
See Table 30 for the dehumidification system sequence of
operation.
Fig. 43 — Perfect Humidity Hot Gas
Reheat Mode Operation
Fig. 41 — Perfect Humidity™ Normal
Design Cooling Operation
Table 30 — Perfect Humidity Dehumidification System Sequence of Operation and
System Response — Single Compressor Unit
THERMOSTAT INPUT
ECONOMIZER FUNCTION
581B UNIT OPERATION
Subcooling Mode Hot Gas Reheat Mode
H
Y1
—
Y2
—
OAT. < Economizer Set Point
Economizer
Comp. 1
Normal Operation
Off
On
On
On
On
On
On
On
On
On
Off
On
Off
On
Off
Off
No
No
Yes
Yes
No
Off
Off
On
On
Off
On
On
On
On
On
Yes
Yes
Yes
No
No
No
No
Yes
Yes
No
LEGEND
OAT — Outdoor Air Temperature
NOTE: On a thermostat call for W1, all cooling and dehumidification will
be off.
—37—
SERVICE
D. Filters
Clean or replace at start of each heating and cooling season,
or more often if operating conditions require it. Replacement
filters must be same dimensions as original filters.
CAUTION: When servicing unit, shut off all elec-
trical power to unit and install lockout tag to avoid
shock hazard or injury from rotating parts.
E. Outdoor-Air Inlet Screens
Clean screen with steam or hot water and a mild detergent.
Do not use disposable filters in place of screen.
I. CLEANING
Inspect unit interior at the beginning of heating and cooling
season and as operating conditions require.
II. LUBRICATION
A. Compressors
A. Evaporator Coil
Each compressor is charged with correct amount of oil at the
factory.
1. Turn unit power off, tag disconnect. Remove evapora-
tor coil access panel.
B. Fan Motor Bearings
2. If economizer or two-position damper is installed,
remove economizer by disconnecting Molex plug and
removing mounting screws. Refer to accessory econo-
mizer installation instructions or Optional EconoMi$er
IV section on page 15 for additional information.
Fan motor bearings are of the permanently lubricated type.
No further lubrication is required. No lubrication of con-
denser-fan or evaporator-fan motors is required.
III. CONDENSER-FAN ADJUSTMENT (Fig. 47)
3. Slide filters out of unit.
Shut off unit power supply. Remove condenser-fan assembly
(grille, motor, motor cover, and fan) and loosen fan hub
setscrews. Adjust fan height as shown in Fig. 47. Tighten
setscrews and replace condenser-fan assembly.
4. Clean coil using a commercial coil cleaner or dish-
washer detergent in a pressurized spray canister.
Wash both sides of coil and flush with clean water.
For best results, back-flush toward return-air section
to remove foreign material. Flush condensate pan
after completion.
IV. ECONOMI$ER IV ADJUSTMENT
Refer to Optional EconoMi$er IV section on page 15.
5. Reinstall economizer and filters.
6. Reconnect wiring.
V. EVAPORATOR FAN BELT INSPECTION
Check condition of evaporator belt or tension during heating
and cooling inspections or as conditions require. Replace belt
or adjust as necessary.
7. Replace access panels.
B. Condenser Coil
Inspect coil monthly. Clean condenser coil annually, and as
required by location and outdoor air conditions.
VI. HIGH-PRESSURE SWITCH
The high-pressure switch contains a Schrader core depressor,
and is located on the compressor hot gas line. This switch
opens at 428 psig and closes at 320 psig. No adjustments are
necessary.
One-Row Coil
Wash coil with commercial coil cleaner. It is not necessary to
remove top panel.
2-Row Coils
VII. LOSS-OF-CHARGE SWITCH
Clean coil as follows:
The loss-of-charge switch contains a Schrader core depressor,
and is located on the compressor liquid line. This switch opens
at 7 psig and closes at 22 psig. No adjustments are necessary.
1. Turn off unit power, tag disconnect.
2. Remove top panel screws on condenser end of unit.
VIII. FREEZE-STAT
3. Remove condenser coil corner post. See Fig. 44. To
hold top panel open, place coil corner post between
top panel and center post. See Fig. 45.
The freeze-stat is a bimetal temperature-sensing switch that
is located on the “hair-pin” end of the evaporator coil. The
switch protects the evaporator coil from freeze-up due to lack
of airflow. The switch opens at 30 F and closes at 45 F. No
adjustments are necessary.
4. Remove screws securing coil to compressor plate and
compressor access panel.
5. Remove fastener holding coil sections together at
return end of condenser coil. Carefully separate the
outer coil section 3 to 4 in. from the inner coil section.
See Fig. 46.
IX. REFRIGERANT CHARGE
Amount of refrigerant charge is listed on unit nameplate
(also refer to Table 1). Refer to HVAC Servicing Procedures
literature available at your local distributor and the follow-
ing procedures.
6. Use a water hose or other suitable equipment to flush
down between the 2 coil sections to remove dirt and
debris. Clean the outer surfaces with a stiff brush in
the normal manner.
Unit panels must be in place when unit is operating during
charging procedure. Unit must operate
10 minutes before checking or adjusting refrigerant charge.
a
minimum of
7. Secure inner and outer coil rows together with a field-
supplied fastener.
An accurate superheat, thermocouple-type or thermistor-
type thermometer, and a gage manifold are required when
using the superheat charging method for evaluating the unit
charge. Do not use mercury or small dial-type thermometers
because they are not adequate for this type of measurement.
8. Reposition the outer coil section and remove the coil
corner post from between the top panel and center
post. Reinstall the coil corner post and replace all
screws.
C. Condensate Drain
Check and clean each year at start of cooling season. In win-
ter, keep drain dry or protect against freeze-up.
—38—
A. No Charge
Use standard evacuating techniques. After evacuating sys-
tem to 500 microns, weigh in the specified amount of refrig-
erant. (Refer to Table 1 and unit information plate.)
B. Low Charge Cooling
Using Cooling Charging Charts, Fig. 48-51, vary refrigerant
until the conditions of the charts are met. Note the charging
charts are different from type normally used. Charts are
based on charging the units to the correct superheat for the
various operating conditions. Accurate pressure gage and
temperature sensing device are required. Connect the
pressure gage to the service port on the suction line. Mount
the temperature sensing device on the suction line and
insulate it so that outdoor ambient temperature does not
affect the reading. Indoor-air cfm must be within the normal
operating range of the unit.
Fig. 44 — Cleaning Condenser Coil
C. Perfect Humidity™ System Charging
The system charge for units with the Perfect Humidity system
is greater than that of the standard unit alone. The charge for
units with this option is indicated on the unit nameplate
drawing. Also refer to Fig. 52-55. To charge systems using the
Perfect Humidity Dehumidification system, fully evacuate,
recover, and recharge the system to the unit information plate
specified charge level.
To check or adjust refrigerant charge on systems using the Per-
fect Humidity Dehumidification system, charge per Fig. 52-55.
NOTE: When using the charging charts, it is important that
only the subcooling/reheat dehumidification coil liquid line
solenoid valve be energized. The subcooling/reheat dehumid-
ification coil liquid line solenoid valve MUST be energized to
use the charging charts and the outdoor motor speed control-
ler jumpered to run the fan at full speed.
Fig. 45 — Propping Up Top Panel
The charts reference a liquid pressure (psig) and tempera-
ture at
a
point between the condenser coil and the
subcooling/reheat dehumidification coil. A tap is provided on
the unit to measure liquid pressure entering the subcooling/
reheat dehumidification coil.
IMPORTANT: The subcooling mode charging charts
(Fig. 52-55) are to be used ONLY with units having the
optional Perfect Humidity subcooling option. DO NOT use
standard charge (Fig. 48-51) for units with Perfect Humidity
system, and DO NOT use Fig. 52-55 for standard units.
D. To Use Cooling Charging Chart, Standard Unit
Take the outdoor ambient temperature and read the suction
pressure gage. Refer to charts to determine what suction tem-
perature should be. If suction temperature is high, add refrig-
erant. If suction temperature is low, carefully recover some of
the charge. Recheck the suction pressure as charge is adjusted.
Example (Fig. 50):
Outdoor Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 F
Suction Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70 psig
Suction Temperature should be . . . . . . . . . . . . . . . . . . . . 48 F
(Suction temperature may very ± 5 F.)
Fig. 46 — Separating Coil Sections
If charging device is used, temperature and pressure read-
ings must be accomplished using the charging charts.
UNIT 581B
FAN HEIGHT — “A” (in.)
036-060 and 072 (208/230 V)
072 (460 and 575 V)
2.75
3.50
Fig. 47 — Condenser-Fan Adjustment
—39—
Fig. 50 — Cooling Charging Chart, Standard 581B060
Fig. 48 — Cooling Charging Chart, Standard 581B036
Fig. 49 — Cooling Charging Chart, Standard 581B048
Fig. 51 — Cooling Charging Chart, Standard 581B072
—40—
CONDENSER FAN MUST BE OPERATING
CONDENSER FAN MUST BE OPERATING
NOTE: When using the charging charts, it is important that only the subcooling/reheat dehu-
midification coil liquid line solenoid valve be energized. The subcooling/reheat dehumidifica-
tion coil liquid line solenoid valve MUST be energized to use the charging charts and the
outdoor motor speed controller jumpered to run the fan at full speed.
NOTE: When using the charging charts, it is important that only the subcooling/reheat dehu-
midification coil liquid line solenoid valve be energized. The subcooling/reheat dehumidifica-
tion coil liquid line solenoid valve MUST be energized to use the charging charts and the
outdoor motor speed controller jumpered to run the fan at full speed.
Fig. 52 — Cooling Charging Chart, 581B036 with the
Perfect Humidity Dehumidification System
Fig. 54 — Cooling Charging Chart, 581B060 with the
Perfect Humidity Dehumidification System
CONDENSER FAN MUST BE OPERATING
CONDENSER FAN MUST BE OPERATING
NOTE: When using the charging charts, it is important that only the subcooling/reheat dehu-
midification coil liquid line solenoid valve be energized. The subcooling/reheat dehumidifica-
tion coil liquid line solenoid valve MUST be energized to use the charging charts and the
outdoor motor speed controller jumpered to run the fan at full speed.
NOTE: When using the charging charts, it is important that only the subcooling/reheat
dehumidification coil liquid line solenoid valve be energized. The subcooling/reheat dehu-
midification coil liquid line solenoid valve MUST be energized to use the charging charts
and the outdoor motor speed controller jumpered to run the fan at full speed.
Fig. 53 — Cooling Charging Chart, 581B048 with the
Perfect Humidity Dehumidification System
Fig. 55 — Cooling Charging Chart, 581B072 with the
Perfect Humidity Dehumidification System
—41—
E. To Use Cooling Charging Charts, Units With Perfect
Humidity™ Dehumidification System
Refer to charts (Fig. 52-55) to determine the proper leaving
condenser pressure and temperature.
Example (Fig. 52):
Leaving Condenser Pressure. . . . . . . . . . . . . . . . . . . .250 psig
Leaving Condenser Temperature . . . . . . . . . . . . . . . . . . 105 F
Table 31 — LED Error Code Description*
LED INDICATION
ERROR CODE DESCRIPTION
Normal Operation
ON
OFF
Hardware Failure
1 Flash†
2 Flashes
3 Flashes
4 Flashes
5 Flashes
6 Flashes
7 Flashes
8 Flashes
9 Flashes
Evaporator Fan On/Off Delay Modified
Limit Switch Fault
Flame Sense Fault
4 Consecutive Limit Switch Faults
Ignition Lockout Fault
Induced-Draft Motor Fault
Rollout Switch Fault
Internal Control Fault
Software Lockout
NOTE: When using the charging charts, it is important that
only the subcooling/reheat dehumidification coil liquid line
solenoid valve be energized. The subcooling/reheat dehumid-
ification coil liquid line solenoid valve MUST be energized to
use the charging charts and the outdoor motor speed control-
ler jumpered to run the fan at full speed.
X. FLUE GAS PASSAGEWAYS
To inspect the flue collector box and upper areas of the heat
exchanger:
LEGEND
LED — Light-Emitting Diode
*A 3-second pause exists between LED error code flashes. If more
than one error code exists, all applicable codes will be displayed in
numerical sequence.
†Indicates a code that is not an error. The unit will continue to operate
when this code is displayed.
1. Remove the combustion blower wheel and motor
assembly according to directions in Combustion-Air
Blower section following.
2. Remove the 3 screws holding the blower housing to
the flue cover.
IMPORTANT: Refer to Troubleshooting Tables 32-36 for additional
information.
3. Remove the flue cover to inspect the heat exchanger.
4. Clean all surfaces as required using a wire brush.
XIV. MAIN BURNERS
At the beginning of each heating season, inspect for deteriora-
tion or blockage due to corrosion or other causes. Observe the
main burner flames and adjust, if necessary.
XI. COMBUSTION-AIR BLOWER
Clean periodically to ensure proper airflow and heating effi-
ciency. Inspect blower wheel every fall and periodically during
heating season. For the first heating season, inspect blower
wheel bimonthly to determine proper cleaning frequency.
CAUTION: When working on gas train, do not hit
or plug orifice spuds.
To inspect blower wheel, remove draft hood and screen.
Shine a flashlight into opening to inspect wheel. If cleaning
is required, remove motor and wheel as follows:
A. Removal and Replacement of Gas Train (See Fig. 56
and 57)
1. Slide burner access panel out.
1. Shut off manual gas valve.
2. Remove the 5 screws that attach induced-draft motor
assembly to the vestibule cover.
2. Shut off power to unit tag disconnect.
3. Remove compressor access panel.
4. Slide out burner compartment side panel.
5. Disconnect gas piping at unit gas valve.
3. Slide the motor and blower wheel assembly out of the
blower housing. The blower wheel can be cleaned at
this point. If additional cleaning is required, continue
with Steps 4 and 5.
6. Remove wires connected to gas valve. Mark each
wire.
4. To remove blower from the motor shaft, by remove
2 setscrews.
7. Remove induced-draft motor, ignitor, and sensor
wires at the Integrated Gas Unit Controller (IGC).
5. To remove motor, remove the 4 screws that hold the
motor to mounting plate. Remove the motor cooling
fan by removing one setscrew. Then remove nuts that
hold motor to mounting plate.
8. Remove the 2 screws that attach the burner rack to
the vestibule plate.
9. Remove the gas valve bracket.
10. Slide the burner tray out of the unit (Fig. 57).
11. To reinstall, reverse the procedure outlined above.
6. To reinstall, reverse the procedure outlined above.
XII. LIMIT SWITCH
B. Cleaning and Adjustment
Remove blower access panel (Fig. 7). Limit switch is located
on the fan deck.
1. Remove burner rack from unit as described above.
2. Inspect burners and, if dirty, remove burners from
rack.
XIII. BURNER IGNITION
Unit is equipped with a direct spark ignition 100% lockout
system. Integrated Gas Unit Controller (IGC) is located in
the control box (Fig. 12). A single LED on the IGC provides a
visual display of operational or sequential problems when
the power supply is uninterrupted. The LED can be observed
through the viewport. When a break in power occurs, the
IGC will be reset (resulting in a loss of fault history) and the
evaporator fan on/off times delay will be reset. During servic-
ing, refer to the label on the control box cover or Table 31 for
an explanation of LED error code descriptions.
3. Using a soft brush, clean burners and cross-over port
as required.
4. Adjust spark gap. See Fig. 58.
5. Reinstall burners on rack.
6. Reinstall burner rack as described above.
XV. REPLACEMENT PARTS
A complete list of replacement parts may be obtained from
your Bryant distributor upon request. Refer to Fig. 59 for a
typical unit wiring schematic.
If lockout occurs, unit may be reset by interrupting power
supply to unit for at least 5 seconds.
—42—
INDUCED-
DRAFT
ROLLOUT
SWITCH
MOTOR
MOUNTING
PLATE
BURNER
SECTION
FLUE
EXHAUST
VESTIBULE
PLATE
INDUCED-
DRAFT
MOTOR
Fig. 57 — Burner Tray Details
BLOWER
HOUSING
MANIFOLD
PRESSURE
TAP
GAS
VALVE
Fig. 56 — Burner Section Details
LOW HEAT UNITS
581B036060N
60,000 BTUH
INPUT
581B048060N
581B060060N
581B036071
581B036072
581B048071
581B048072
581B060071
581B060072
581B072072
72,000 BTUH
INPUT
MEDIUM AND
HIGH HEAT UNITS
581B036090N
90,000 BTUH
581B048090N
INPUT
581B060090N
581B036114
581B036115
581B048114
115,000 BTUH
581B048115
INPUT
581B060114
581B060115
581B072115
581B048120N
581B060120N
581B048149
581B048150
581B060149
581B060150
581B072150
120,000 BTUH
INPUT
150,000 BTUH
INPUT
Fig. 58 — Spark Gap Adjustment
—43—
NOTES:
1. If any of the original wire furnished must be replaced, it must
be replaced with type 90 C wire or its equivalent.
2. Three phase motors are protected under primary single
phasing conditions.
3. Use copper conductors only.
4. TRAN is wired for 230 v unit. If unit is to be run with 208 v
power supply, disconnect BLK wire from 230 v tap (ORN)
and connect to 208 v tap (RED). Insulate end of 230 v tap.
LEGEND
OFM
OLR
P
—
—
—
—
—
—
—
—
Outdoor (Condenser) Fan Motor
Overload Relay
C
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Contactor, Compressor
Capacitor
Compressor Lockout
Compressor Motor
Equipment
Freeze Up Protection Thermostat
Fuse
Ground
High-Pressure Switch
Hall-Effect Sensor
Ignitor
CAP
CLO
COMP
EQUIP
FPT
FU
Splice
Plug
PL
Plug Assembly
Quadruple Terminal
Rollout Switch
Supply Air Temperature Sensor
Transformer
Splice (Marked)
Factory Wiring
QT
RS
SAT
TRAN
GND
HPS
HS
Field Control Wiring
Field Splice
Field Power Wiring
I
Accessory or Optional Wiring
To indicate common potential only;
not to represent wiring.
Marked Wire
IDM
IFC
Induced-Draft Motor
Indoor Fan Contactor
Indoor Fan Motor
Integrated Gas Unit Controller
Low-Pressure Switch
Limit Switch
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
IFM
IGC
LPS
LS
MGV
Main Gas Valve
Fig. 59 — Typical Wiring Schematic and Component Arrangement (208/230-3-60 Shown)
—44—
TROUBLESHOOTING
I. UNIT TROUBLESHOOTING
Refer to Tables 32-36.
Table 32 — LED Error Code Service Analysis
CAUSE
SYMPTOM
REMEDY
Hardware Failure
(LED OFF)
Loss of power to control module (IGC).
Check 5 amp fuse on IGC, power to unit, 24-v circuit breaker, and
transformer. Units without a 24-v circuit breaker have an internal
overload in the 24-v transformer. If the overload trips, allow
10 minutes for automatic reset.
Fan ON/OFF Delay Modified High limit switch opens during heat
IGC board has modified either blower on delay time or blower off
delay time.
(LED/FLASH)
exchanger warm-up period before fan-on
delay expires.
Limit switch opens within three minutes
after blower-off delay timing in Heating mode.
Limit Switch Fault
(LED 2 Flashes)
High temperature limit switch is open.
Check the operation of the indoor (evaporator) fan motor.
Ensure that the supply-air temperature rise is in accordance with
the range on the unit nameplate.
Flame Sense Fault
(LED 3 Flashes)
The IGC sensed flame that should not be
present.
Reset unit. If problem persists, replace control board.
4 Consecutive Limit
Switch Faults
(LED 4 Flashes)
Inadequate airflow to unit.
Check operation of indoor (evaporator) fan motor and that supply-air
temperature rise agrees with range on unit nameplate information.
Ignition Lockout
(LED 5 Flashes)
Unit unsuccessfully attempted ignition for
15 minutes.
Check ignitor and flame sensor electrode spacing, gaps, etc.
Ensure that flame sense and ignition wires are properly routed
and terminated. Verify that unit is obtaining proper amount of gas.
Induced-Draft Motor Fault
(LED 6 Flashes)
IGC does not sense that induced-draft
motor is operating.
Check for proper voltage. If motor is operating, check the
speed sensor plug/IGC Terminal J2 connection. Proper
connection: PIN 1— White, PIN 2 — Red, PIN 3 — Black.
Rollout Switch Fault
(LED 7 Flashes)
Rollout switch has opened.
Rollout switch will automatically reset, but IGC will continue to
lock out unit. Check gas valve operation. Ensure that induced-
draft blower wheel is properly secured to motor shaft.
Reset unit at unit disconnect.
Internal Control Fault
(LED 8 Flashes)
Microprocessor has sensed an error in the
software or hardware.
If error code is not cleared by resetting unit power, replace the IGC.
Temporary Software
Lockout
(LED 9 Flashes)
Electrical interference is impeding the IGC
software.
Reset 24-v to control board or turn thermostat off and then on.
Fault will automatically reset itself in one hour.
IMPORTANT: Refer to heating troubleshooting for additional heating
CAUTION: If the IGC must be replaced, be sure to
ground yourself to dissipate any electrical charge that may be
present before handling new control board. The IGC is sensitive
to static electricity and may be damaged if the necessary pre-
cautions are not taken.
section troubleshooting information.
LEGEND
IGC — Integrated Gas Unit Controller
LED — Light-Emitting Diode
—45—
Table 33 — Heating Service Analysis
PROBLEM
CAUSE
REMEDY
Burners Will Not
Ignite
Misaligned spark electrodes.
No gas at main burners.
Check flame ignition and sensor electrode positioning. Adjust as needed.
Check gas line for air purge as necessary. After purging gas line of
air, allow gas to dissipate for at least 5 minutes before attempting
to relight unit.
Check gas valve.
Water in gas line.
No power to unit.
Drain water and install drip leg to trap water.
Check power supply, fuses, wiring, and circuit breaker.
No 24 v power supply to control circuit.
Check transformer. Transformers with internal overcurrent protection
require a cool-down period before resetting. Check 24-v circuit breaker;
reset if necessary.
Miswired or loose connections.
Burned-out heat anticipator in thermostat.
Broken thermostat wires.
Dirty air filter.
Check all wiring and wirenut connections.
Replace thermostat.
Run continuity check. Replace wires, if necessary.
Clean or replace filter as necessary.
Inadequate Heating
Gas input to unit too low.
Check gas pressure at manifold. Clock gas meter for input. If too low,
increase manifold pressure or replace with correct orifices.
Unit undersized for application.
Restricted airflow.
Replace with proper unit or add additional unit.
Clean filter, replace filter, or remove any restrictions.
Blower speed too low.
Use high speed tap, increase fan speed, or install optional blower, as suit-
able for individual units, Adjust pulley.
Limit switch cycles main burners.
Too much outdoor air.
Check rotation of blower, thermostat heat anticipator settings,
and temperature rise of unit. Adjust as needed.
Adjust minimum position.
Check economizer operation.
Poor Flame
Characteristics
Incomplete combustion (lack of
combustion air) results in:
Check all screws around flue outlets and burner compartment.
Tighten as necessary.
Aldehyde odors, CO (carbon monoxide),
sooting flame, or floating flame.
Cracked heat exchanger. Replace heat exchanger.
Overfired unit — reduce input, change orifices, or adjust gas line or mani-
fold pressure.
Check vent for restriction. Clean as necessary.
Check orifice to burner alignment.
Burners Will Not
Turn Off
Unit is locked into Heating mode for a
one minute minimum.
Wait until mandatory one-minute time period has elapsed or reset power to
unit.
Table 34 — Perfect Humidity™ Adaptive Dehumidification System Subcooling Mode Service Analysis
PROBLEM
CAUSE
REMEDY
Subcooling Mode (Liquid Reheat)
Will Not Energize.
No power to control transformer from
evaporator-fan motor.
Check power source and evaporator-fan relay. Ensure all
wire connections are tight.
No power from control transformer to liquid line
solenoid valve.
1. Fuse open; check fuse. Ensure continuity of wiring.
2. Low-pressure switch open. Cycle unit off and allow low-
pressure switch to reset. Replace switch if it will not
close.
3. Transformer bad; check transformer.
Liquid line solenoid valve will not operate.
1. Solenoid coil defective; replace.
2. Solenoid valve stuck open; replace.
Liquid line solenoid valve will not open.
Valve is stuck closed; replace valve.
Low System Capacity.
Low refrigerant charge or frosted evaporator coil.
1. Check charge amount. Charge per Fig. 52-55.
2. Evaporator coil frosted; check and replace low-
pressure switch if necessary.
Loss of Compressor Superheat
Conditions with Subcooling/Reheat
Dehumidification Coil Energized.
Thermostatic expansion valve (TXV).
1. Check TXV bulb mounting, and secure tightly to suction
line.
2. Replace TXV if stuck open or closed.
Table 35 — Perfect Humidity Dehumidification System Hot Gas Reheat Mode Service Analysis
PROBLEM
CAUSE
REMEDY
Reheat Mode Will Not Energize.
No power to control transformer from
evaporator-fan motor.
Check power source and evaporator-fan relay. Ensure all
wire connections are tight.
No power from control transformer to hot gas
line solenoid valve.
1. Fuse open; check fuse. Ensure continuity of wiring.
2. Low-pressure switch open. Cycle unit off and allow low-
pressure switch to reset. Replace switch if it will not
close.
3. Transformer bad; check transformer.
Hot gas line solenoid valve will not operate.
1. Solenoid coil defective; replace.
2. Solenoid valve stuck closed; replace.
Low refrigerant charge or frosted evaporator coil.
1. Check charge amount. Charge per Fig. 52-55.
2. Evaporator coil frosted; check and replace low-
pressure switch if necessary.
Loss of Compressor Superheat
Conditions with Subcooling/Reheat
Dehumidification Coil Energized.
Thermostatic expansion valve (TXV).
1. Check TXV bulb mounting, and secure tightly to suction
line.
2. Replace TXV if stuck open or closed.
Excessive Superheat.
Liquid line solenoid valve will not operate.
Hot gas line solenoid valve will not close.
Valve is stuck; replace valve.
Valve is stuck; replace valve.
—46—
Table 36 — Cooling Service Analysis
CAUSE
PROBLEM
REMEDY
Compressor and Condenser Fan
Will Not Start
Power failure.
Fuse blown or circuit breaker tripped.
Defective thermostat, contactor, transformer,
or control relay.
Call power company.
Replace fuse or reset circuit breaker.
Replace component.
Insufficient line voltage.
Incorrect or faulty wiring.
Thermostat setting too high.
Faulty wiring or loose connections in com-
pressor circuit.
Determine cause and correct.
Check wiring diagram and rewire correctly.
Lower thermostat setting below room temperature.
Check wiring and repair or replace.
Compressor Will Not Start
But Condenser Fan Runs
Compressor motor burned out, seized, or
internal overload open.
Defective run/start capacitor, overload, start
relay.
Determine cause. Replace compressor.
Determine cause and replace.
One leg of 3-phase power dead.
Replace fuse or reset circuit breaker. Determine
cause.
Compressor Cycles (Other Than
Normally Satisfying Thermostat)
Refrigerant overcharge or undercharge.
Recover refrigerant, evacuate system, and recharge
to nameplate.
Defective compressor.
Insufficient line voltage.
Blocked condenser.
Defective run/start capacitor, overload, or
start relay.
Replace and determine cause.
Determine cause and correct.
Determine cause and correct.
Determine cause and replace.
Defective thermostat.
Replace thermostat.
Faulty condenser-fan motor or capacitor.
Restriction in refrigerant system.
Dirty air filter.
Replace.
Locate restriction and remove.
Replace filter.
Compressor Operates Continuously
Unit undersized for load.
Thermostat set too low.
Low refrigerant charge.
Leaking valves in compressor.
Air in system.
Decrease load or increase unit size.
Reset thermostat.
Locate leak, repair, and recharge.
Replace compressor.
Recover refrigerant, evacuate system, and
recharge.
Condenser coil dirty or restricted.
Dirty air filter.
Clean coil or remove restriction.
Replace filter.
Excessive Head Pressure
Dirty condenser coil.
Refrigerant overcharged.
Air in system.
Clean coil.
Recover excess refrigerant.
Recover refrigerant, evacuate system, and
recharge.
Condenser air restricted or air short-cycling.
Low refrigerant charge.
Compressor valves leaking.
Restriction in liquid tube.
High heat load.
Compressor valves leaking.
Refrigerant overcharged.
Dirty air filter.
Determine cause and correct.
Check for leaks, repair, and recharge.
Replace compressor.
Remove restriction.
Check for source and eliminate.
Replace compressor.
Head Pressure Too Low
Excessive Suction Pressure
Suction Pressure Too Low
Recover excess refrigerant.
Replace filter.
Low refrigerant charge.
Metering device or low side restricted.
Insufficient evaporator airflow.
Check for leaks, repair, and recharge.
Remove source of restriction.
Increase air quantity. Check filter and replace if
necessary.
Temperature too low in conditioned area.
Outdoor ambient below 25 F.
Time off delay not finished.
Reset thermostat.
Install low-ambient kit.
Wait for 30-second off delay.
Evaporator Fan Will Not Shut Off
—47—
II. ECONOMI$ER IV TROUBLESHOOTING
D. DCV (Demand Controlled Ventilation) and Power
Exhaust
See Table 37 for EconoMi$er IV logic.
To check DCV and Power Exhaust:
A functional view of the EconoMi$er IV is shown in Fig. 60.
Typical settings, sensor ranges, and jumper positions are
also shown. An EconoMi$er IV simulator program is avail-
able from Bryant to help with EconoMi$er IV training and
troubleshooting.
1. Make sure EconoMi$er IV preparation procedure has
been performed.
2. Ensure terminals AQ and AQ1 are open. The LED for
both DCV and Exhaust should be off. The actuator
should be fully closed.
A. EconoMi$er IV Preparation
3. Connect a 9-v battery to AQ (positive node) and AQ1
(negative node). The LED for both DCV and Exhaust
should turn on. The actuator should drive to between
90 and 95% open.
This procedure is used to prepare the EconoMi$er IV for
troubleshooting. No troubleshooting or testing is done by
performing the following procedure.
NOTE: This procedure requires a 9-v battery, 1.2 kilo-ohm
resistor, and a 5.6 kilo-ohm resistor which are not supplied
with the EconoMi$er IV.
4. Turn the Exhaust potentiometer CW until the
Exhaust LED turns off. The LED should turn off
when the potentiometer is approximately 90%. The
actuator should remain in position.
IMPORTANT: Be sure to record the positions of all potenti-
ometers before starting troubleshooting.
5. Turn the DCV set point potentiometer CW until the
DCV LED turns off. The DCV LED should turn off
when the potentiometer is approximately 9 v. The
actuator should drive fully closed.
1. Disconnect power at TR and TR1. All LEDs should be
off. Exhaust fan contacts should be open.
2. Disconnect device at P and P1.
3. Jumper P to P1.
6. Turn the DCV and Exhaust potentiometers CCW
until the Exhaust LED turns on. The exhaust con-
tacts will close 30 to 120 seconds after the Exhaust
LED turns on.
4. Disconnect wires at T and T1. Place 5.6 kilo-ohm
resistor across T and T1.
5. Jumper TR to 1.
6. Jumper TR to N.
7. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
7. If connected, remove sensor from terminals SO and +.
Connect 1.2 kilo-ohm 4074EJ M checkout resistor
across terminals SO and +.
E. DCV Minimum and Maximum Position
To check the DCV minimum and maximum position:
8. Put 620-ohm resistor across terminals SR and +.
1. Make sure EconoMi$er IV preparation procedure has
been performed.
9. Set minimum position, DCV set point, and exhaust
potentiometers fully CCW (counterclockwise).
2. Connect a 9-v battery to AQ (positive node) and AQ1
(negative node). The DCV LED should turn on. The
actuator should drive to between 90 and 95% open.
10. Set DCV maximum position potentiometer fully CW
(clockwise).
3. Turn the DCV Maximum Position potentiometer to
midpoint. The actuator should drive to between 20
and 80% open.
11. Set enthalpy potentiometer to D.
12. Apply power (24 vac) to terminals TR and TR1.
B. Differential Enthalpy
4. Turn the DCV Maximum Position potentiometer to
fully CCW. The actuator should drive fully closed.
To check differential enthalpy:
1. Make sure EconoMi$er IV preparation procedure has
been performed.
5. Turn the Minimum Position potentiometer to mid-
point. The actuator should drive to between 20 and
80% open.
2. Place 620-ohm resistor across SO and +.
6. Turn the Minimum Position Potentiometer fully CW.
The actuator should drive fully open.
3. Place 1.2 kilo-ohm resistor across SR and +. The Free
Cool LED should be lit.
7. Remove the jumper from TR and N. The actuator
should drive fully closed.
4. Remove 620-ohm resistor across SO and +. The Free
Cool LED should turn off.
8. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
5. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
F. Supply-Air Input
C. Single Enthalpy
To check supply-air input:
To check single enthalpy:
1. Make sure EconoMi$er IV preparation procedure has
been performed.
1. Make sure EconoMi$er IV preparation procedure has
been performed.
2. Set the Enthalpy potentiometer to A. The Free Cool
LED turns on. The actuator should drive to between
20 and 80% open.
2. Set the enthalpy potentiometer to A (fully CCW). The
Free Cool LED should be lit.
3. Set the enthalpy potentiometer to D (fully CW). The
Free Cool LED should turn off.
3. Remove the 5.6 kilo-ohm resistor and jumper T to T1.
The actuator should drive fully open.
4. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
4. Remove the jumper across T and T1. The actuator
should drive fully closed.
5. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
—48—
G. EconoMi$er IV Troubleshooting Completion
6. Remove 1.2 kilo-ohm checkout resistor from termi-
nals SO and +. If used, reconnect sensor from termi-
nals SO and +.
This procedure is used to return the EconoMi$er IV to opera-
tion. No troubleshooting or testing is done by performing the
following procedure.
7. Remove jumper from TR to N.
8. Remove jumper from TR to 1.
1. Disconnect power at TR and TR1.
2. Set enthalpy potentiometer to previous setting.
9. Remove 5.6 kilo-ohm resistor from T and T1. Recon-
nect wires at T and T1.
3. Set DCV maximum position potentiometer to previ-
ous setting.
10. Remove jumper from P to P1. Reconnect device at P
and P1.
4. Set minimum position, DCV set point, and exhaust
potentiometers to previous settings.
11. Apply power (24 vac) to terminals TR and TR1.
5. Remove 620-ohm resistor from terminals SR and +.
Table 37 — EconoMi$er IV Input/Output Logic
INPUTS
Enthalpy*
OUTPUTS
Compressor
N Terminal†
Demand Control
Ventilation (DCV)
Y1 Y2
Occupied
Minimum position
Unoccupied
Stage Stage
Outdoor
Return
1
2
Damper
Below set
(DCV LED Off)
High
Low
On On
On Off
Off Off
On On
On Off
Off Off
On On
On Off
Off Off
On On
On Off
Off Off
On
On
Off
On
Off
Off
On
On
Off
On
Off
Off
On
Off
Off
Off
Off
Off
On
Off
Off
Off
Off
Off
Closed
(Free Cooling LED Off)
Low
High
Low
High
Modulating** (between min.
position and full-open)
Modulating** (between
closed and full-open)
(Free Cooling LED On)
Minimum position
Modulating†† (between min.
position and DCV maximum)
Closed
Above set
(DCV LED On)
High
Modulating†† (between
closed and DCV
maximum)
(Free Cooling LED Off)
Low
Modulating***
Modulating†††
(Free Cooling LED On)
***Modulation is based on the greater of DCV and supply-air sensor
signals, between minimum position and either maximum position
(DCV) or fully open (supply-air signal).
†††Modulation is based on the greater of DCV and supply-air sensor
signals, between closed and either maximum position (DCV) or fully
open (supply-air signal).
*For single enthalpy control, the module compares outdoor enthalpy
to the ABCD set point.
†Power at N terminal determines Occupied/Unoccupied setting:
24 vac (Occupied), no power (Unoccupied).
**Modulation is based on the supply-air sensor signal.
††Modulation is based on the DCV signal.
Fig. 60 — EconoMi$er IV Functional View
—49—
INDEX
Access panels 15
Heat exchanger
7
Weight
Corner
EconoMi$er IV 6, 8
Unit 5, 6, 8
Wiring
Altitude compensation 35
Barometric flow capacity 17
Burner ignition 42
High flow valves 34
High pressure switch
Horizontal units 1, 2
Humidistat 13
8
7
Burner rack 43
Burner section 43
Burner spark gap 43
Charging chart, refrigerant 40, 41
Indoor air quality sensor 19
Integrated gas controller 42
Error codes 42, 45
Leak test 34
Light commercial Thermistat™ device 13
Limit switch 42
Humidistat 13
EconoMi$er IV 17
Perfect Humidity dehumidification 14
Power connections 10
Thermostat 10
Clearance
4
CO2 sensor
Configuration 21
Settings 20, 22
Combustion blower wheel 42
Compressor
Unit 44
Liquid propane
Low pressure switch
7
7
Main burners 35, 42
Lubrication 38
Mounting 34
Manual outdoor air damper 14
Mounting
Rotation 34
Compressor 34
Condensate drain
Cleaning 38
Location 2, 4
Condenser coil
Cleaning 38
Condenser fan
Unit
Natural gas
Non-fused disconnect switch 13
Operating limits
Operating sequence 36
Cooling 36
4
7
6
2
6
Adjustment 38, 39
Control circuit
EconoMi$er IV 36
Heating 36
Wiring
9
Perfect Humidity dehumidification 36, 37
Outdoor air hood 14-16
Outdoor air temperature sensor 16
Outdoor air inlet screens 34
Wiring raceway 10
Convenience outlet 14
Demand control ventilation 21
Dehumidification 21
Dimensions 3, 8
Dimensions
7
Perfect Humidity dehumidification
package 13, 14, 23, 36, 39, 41, 46
Physical data 6, 7
Ductwork
2
EconoMi$er IV 15-21
Adjustment 38
Components 15
Controller 20
Power supply
Wiring 10
9
Pressure, drop
Damper movement 21
Wiring 17
Perfect Humidity dehumidification 23
Pre-Start-Up 34
Electrical connections
Electrical data 11, 12
Enthalpy changeover set points 20
9
Pressure switches
High pressure 7, 38
Low pressure 7, 38
Refrigerant
Evaporator coil
6
Cleaning 38
Evaporator fan motor
Lubrication 38
Motor data 23, 24
Performance 24-33
Pulley adjustment 23
Pulley setting 6, 22
Charge 6, 38-42
Type
6
Refrigerant service ports 34
Replacement parts 42
Return air filter 7, 34
Return air temperature sensor 19
Rigging unit 4, 5
Speed
6
Roof curb
Factory-installed options
Convenience outlet 14
Disconnect switch 13
EconoMi$er IV 15-21
Humidistat 13
Manual outdoor air damper 14
Perfect Humidity™ dehumidification 13
Filter
Assembly
Dimensions
Connector package
Leveling tolerances
Weight
Safety considerations
Safety relief 36
Service 38-44
1
3
3
4
6
1
Cleaning 38
Service ports 34
Installation 16
Slab mount
Start-up 34-37
1
Size
7
Flue gas passageways 42
Flue hood 4, 9
Freeze protection thermostat 7, 38
Start-up checklist CL-1
Thermostat 9, 10
Troubleshooting 45-49
Ventilation 36
Gas connection
Gas input
7
7
Gas piping 4, 9, 34
Gas pressure 1, 7
Heat anticipator settings 7, 9
Copyright 2005 Bryant Heating & Cooling Systems
Printed in U.S.A.
CATALOG NO. 04-53581002-01
START-UP CHECKLIST
(Remove and Store in Job File)
I. PRELIMINARY INFORMATION
MODEL NO.: _________________________________
DATE:________________________________________
SERIAL NO.:________________________________________
TECHNICIAN: ______________________________________
II. PRE-START-UP (insert checkmark in box as each item is completed)
VERIFY THAT JOBSITE VOLTAGE AGREES WITH VOLTAGE LISTED ON RATING PLATE
VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT
REMOVE ALL SHIPPING HOLDDOWN BOLTS AND BRACKETS PER INSTALLATION INSTRUCTIONS
VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS
CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS
CHECK GAS PIPING FOR LEAKS
CHECK THAT RETURN (INDOOR) AIR FILTERS ARE CLEAN AND IN PLACE
VERIFY THAT UNIT INSTALLATION IS LEVEL
CHECK FAN WHEELS AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS
CHECK TO ENSURE THAT ELECTRICAL WIRING IS NOT IN CONTACT WITH REFRIGERANT LINES
OR SHARP METAL EDGES
CHECK PULLEY ALIGNMENT AND BELT TENSION PER INSTALLATION INSTRUCTIONS
III. START-UP
ELECTRICAL
SUPPLY VOLTAGE
COMPRESSOR AMPS
INDOOR-FAN AMPS
L1-L2
L1
L1
L2-L3
L2
L2
L3-L1
L3
L3
TEMPERATURES
OUTDOOR-AIR TEMPERATURE
RETURN-AIR TEMPERATURE
DB
DB
WB
COOLING SUPPLY AIR
GAS HEAT SUPPLY AIR
DB
DB
PRESSURES
GAS INLET PRESSURE
IN. WG
GAS MANIFOLD PRESSURE
REFRIGERANT SUCTION
REFRIGERANT DISCHARGE
IN. WG
PSIG
PSIG
VERIFY REFRIGERANT CHARGE USING CHARGING TABLES
VERIFY THAT 3-PHASE SCROLL COMPRESSOR ROTATING IN CORRECT DIRECTION
Copyright 2005 Bryant Heating & Cooling Systems
Printed in U.S.A.
CL-1
CATALOG NO. 04-53581002-01
|
Brother MFC 925 User Manual
Epson All in One Printer CX7000F User Manual
Fisher Price G2623 User Manual
GE ASP14 User Manual
Haier HWF05XCK E User Manual
Haier HWR05XC5 User Manual
HandHeld Entertainment Barcode Reader 4600G User Manual
Havis Shields Heavy Duty Trak Mount 2003 2006 Ford Expedition C TM EXPD User Manual
Honda Automobiles Ashtray 08U25 SEC 2000 81 User Manual
HP Hewlett Packard CH350 90038 User Manual