installation, start-up and
service instructions
551B
DuraPac Plus Series
Sizes 090-150
SINGLE PACKAGE ROOFTOP
ELECTRIC COOLING UNITS
71/2 to 121/2 Tons
Cancels: II 551B-90-6
II 551B-90-7
10/15/05
I. STEP 1 — PROVIDE UNIT SUPPORT
A. Roof Curb
CONTENTS
Assemble and install accessory roof curb in accordance with
instructions shipped with curb. Install insulation, cant
strips, roofing felt, and counter flashing as shown. Ductwork
must be attached to curb. If electric or control power is to be
routed through the basepan, attach the accessory thru-the-
bottom service connections to the basepan in accordance
with the accessory installation instructions. Connections
must be installed before unit is set on roof curb.
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-37
I. Step 1 — Provide Unit Support. . . . . . . . . . . . . . . . . 1
II. Step 2 — Field Fabricate Ductwork . . . . . . . . . . . . . 1
III. Step 3 — Install Condensate Drain Line
and External Trap. . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
IV. Step 4 — Rig and Place Unit. . . . . . . . . . . . . . . . . . . 2
V. Step 5 — Make Electrical Connections . . . . . . . . . . 7
VI. Step 6 — Adjust Factory-Installed Options. . . . . . 11
VII. Step 7 — Adjust Evaporator-Fan Speed . . . . . . . . 21
IMPORTANT: The gasketing of the unit to the roof curb is
critical for a watertight seal. Install gasket supplied with the
roof curb as shown in Fig. 2. Improperly applied gasket can
also result in air leaks and poor unit performance.
PRE-START-UP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38-41
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41-45
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . .46-49
INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1
Curb should be level. This is necessary for unit drain to func-
tion properly. Unit leveling tolerances are shown in Fig. 3.
Refer to Accessory Roof Curb Installation Instructions for
additional information as required.
B. Slab Mount (Horizontal Units Only)
Provide a level concrete slab that extends a minimum of 6 in.
beyond unit cabinet. Install a gravel apron in front of con-
denser coil air inlet to prevent grass and foliage from
obstructing airflow.
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
NOTE: Horizontal units may be installed on a roof curb if
required.
C. Alternate Unit Support (Curb or Slab Mount)
Untrained personnel can perform basic maintenance func-
tions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained service per-
sonnel. When working on air-conditioning equipment,
observe precautions in the literature, tags and labels
attached to the unit, and other safety precautions that may
apply.
A non-combustible sleeper rail can be used in the unit curb
support area. If sleeper rails cannot be used, support the
long sides of the unit with a minimum of 3 equally spaced
4-in. x 4-in. pads on each side.
II. STEP 2 — FIELD FABRICATE DUCTWORK
On vertical discharge units, secure all ducts to roof curb and
building structure. Do not connect ductwork to unit. For hori-
zontal applications, field-supplied flanges should be attached
to horizontal discharge openings and all ductwork attached
to the flanges. Insulate and weatherproof all external duct-
work, joints, and roof openings with counter flashing and
mastic in accordance with applicable codes.
Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloth for unbrazing operations. Have fire
extinguisher available for all brazing operations.
CAUTION: Ensure voltage listed on unit data plate
agrees with electrical supply provided for unit.
Ducts passing through an unconditioned space must be insu-
lated and covered with a vapor barrier.
WARNING: Before performing service or mainte-
nance operations on unit, turn off main power switch
to unit and install lockout tag. Electrical shock could
cause personal injury.
If a plenum return is used on a vertical unit, the return
should be ducted through the roof deck to comply with appli-
cable fire codes.
A minimum clearance to combustibles is not required around
ductwork on vertical discharge units. On horizontal dis-
charge units, a minimum clearance of 1 in. is required for the
first 12 in. of ductwork. Cabinet return-air static pressure (a
negative condition) should not exceed 0.30 in. wg with
EconoMi$er IV, or 0.45 in. wg without economizer.
INSTALLATION
Unit is shipped in the vertical configuration. To convert to
horizontal configuration, remove side duct opening covers.
Using the same screws, install covers on vertical duct open-
ings with the insulation-side down. Seals around duct
openings must be tight. See Fig. 1.
ROOF CURB
ACCESSORY
CRRFCURB003A01 1′-2″ [356]
CRRFCURB004A01 2′-0″ [610]
“A”
UNIT SIZE
CONNECTOR
PKG. ACCY.
CRBTMPWR001A01
CRBTMPWR002A01
D ALT
ACCESSORY
POWER
B
C
GAS
POWER
CONTROL
DRAIN HOLE
551B090-150
3/4″ [19] NPT
11/4″ [31.7]
3/4″
[19] NPT
2′-87/16″ 1′-1015
/
″
13/4″
1/2″
1/2″
1/2″
NOTES:
[827]
[583]16
[44.5]
[12.7] NPT [12.7] NPT
CRBTMPWR003A01
CRBTMPWR004A01
3/4″ [19] NPT
[12.7] NPT
1. Roof curb accessory is shipped disassembled.
2. Insulated panels: 1-in. thick polyurethane foam,
13/4 lb density.
3/4″
11/4″ [31.7]
[19] NPT
3. Dimensions in [ ] are in millimeters.
4. Roof curb: 16-gage steel.
5. Attach ductwork to curb (flanges of duct rest on
curb).
6. Service clearance 4 ft on each side.
7.
Direction of airflow.
8. Connector packages CRBTMPWR001A01 and
2A01 are for thru-the-curb gas type. Packages
CRBTMPWR003A01 and 4A01 are for thru-the-
bottom type gas connections.
Fig. 2 — Roof Curb Details
—3—
MAXIMUM ALLOWABLE DIFFERENCE
(in.)
A-B
B-C
A-C
0.5
1.0
1.0
NOTE: Trap should be deep enough to offset maximum unit static differ-
ence. A 4-in. trap is recommended.
Fig. 3 — Unit Leveling Tolerances
Fig. 5 — Condensate Drain Piping Details
HORIZONTAL
DRAIN OUTLET
DRAIN PLUG
NOTE: Drain plug is shown in factory-installed position.
Fig. 4 — Condensate Drain Location
NOTES:
OPERATING
WEIGHT
1. Place unit on curb as close as possible to the duct end.
2. Dimension in ( ) is in millimeters.
A
B
C
551B
lb
kg
in.
mm
in.
mm
in.
mm
3. Hook rigging shackles through holes in base rail, as shown in
detail “A.” Holes in base rails are centered around the unit center
of gravity. Use wooden top skid when rigging to prevent rigging
straps from damaging unit.
4. Unit weights do not include economizer. See Table 1 for econo-
mizer weights.
5. Weights include base unit without the Perfect Humidity™ dehumid-
ification system. See Table 1 for additional unit operating weights
with the Perfect Humidity dehumidification system.
090
102
120
150
755
895
915
930
343
406
415
422
77.42 1967 41.5 1054 42.12 1070
77.42 1967 41.5 1054 50.12 1273
77.42 1967 41.5 1054 50.12 1273
77.42 1967 41.5 1054 50.12 1273
CAUTION: All panels must be in place when rigging.
Fig. 6 — Rigging Details
—4—
—5—
Table 1 — Physical Data
UNIT 551B
090
102
120
150
NOMINAL CAPACITY (tons)
71/2
81/2
10
121/2
OPERATING WEIGHT (lb)
Unit
755
75
895
75
915
75
930
75
EconoMi$er IV
Perfect Humidity™ Dehumidification Package
Roof Curb
44
51
51
51
143
143
143
143
COMPRESSOR
Scroll
Quantity
2
53
2
53
2
50
2
60
Oil (oz) (each compressor)
REFRIGERANT TYPE
R-22
Metering Device
Expansion Device
Operating Charge (lb-oz)
Standard Unit
Circuit 1
7-10
8- 2
9- 8
8-13
9-6
10-9
9-8
9-5
Circuit 2
Unit With Perfect Humidity Dehumidification Package
Circuit 1
Circuit 2
13-0
13-6
16-0
16-8
16-8
17-8
15-3
16-6
CONDENSER FAN
Quantity...Diameter (in.)
Nominal Cfm
Propeller Type
2...22
6500
2...22
6500
2...22
7000
2...22
7000
Motor Hp...Rpm
1/4...1100
650
1/4...1100
650
1/4...1100
650
1/4...1100
650
Watts Input (Total)
CONDENSER COIL
Rows...Fins/in.
Total Face Area (sq ft)
High-Efficiency Enhanced Copper Tubes, Lanced Aluminum Fins
2...17
20.5
2...17
25.0
2...17
25.0
2...17
25.0
EVAPORATOR COIL
High Efficiency Enhanced Copper Tubes, Aluminum Double-Wavy Fins, Face Split
Standard Unit
Rows...Fins/in.
3...15
8.9
4...15
11.1
4...15
11.1
4...15
11.1
Total Face Area (sq ft)
Unit with Perfect Humidity Dehumidification Package
Rows...Fins/in.
2...17
6.3
2...17
8.4
2...17
8.4
2...17
8.4
Total Face Area (sq ft)
EVAPORATOR FAN
Size (in.)
Centrifugal Type, Belt Drive
15 x 15
3000
15 x 15
3400
15 x 15
4000
15 x 15
5000
Nominal Cfm — Standard
Maximum Continuous Bhp
Standard
2.90
4.20
56
2.90
4.20
56
3.70
5.25
56
5.25
—
56
High Static
Motor Frame
Fan Rpm Range
Standard
840-1085
860-1080
Ball
840-1085
860-1080
Ball
860-1080
830-1130
Ball
830-1130
—
Ball
2100
High Static
Motor Bearing Type
Maximum Fan Rpm
Motor Pulley Pitch Diameter A/B (in.)
Standard
2100
2100
2100
3.4/4.4
4.0/5.0
3.4/4.4
4.0/5.0
4.0/5.0
2.8/3.8
2.8/3.8
—
High Static
7
/
7
/
7
/
7
/
Nominal Motor Shaft Diameter (in.)
Fan Pulley Pitch Diameter (in.)
Standard
8
8
8
8
7.0
8.0
7.0
8.0
8.0
5.8
5.8
—
High Static
Belt — Quantity...Type...Length (in.)
Standard
1...A...48
1...A...55
16.75-19.25
1...A...51
1...A...55
16.75-19.25
1...A...51
1...BX...46
15.85-17.50
1...BX...46
—
15.85-17.50
High Static
Pulley Center Line Distance (in.)
Speed Change per Full Turn of
Movable Pulley Flange (rpm)
Standard
50
60
50
60
45
60
60
—
High Static
Movable Pulley Maximum Full Turns
From Closed Position
Standard
5
5
5
5
5
5
5
6
5
6
—
5
High Static
Factory Setting — Full Turns Open
Factory Speed Setting (rpm)
Standard
840
860
1
840
860
1
862
887
1
887
—
1
High Static
Fan Shaft Diameter at Pulley (in.)
HIGH-PRESSURE SWITCH (psig)
Standard Compressor Internal Relief (Differential)
450 50
428
320
Cutout
Reset (Auto.)
LOSS-OF-CHARGE/LOW-PRESSURE
SWITCH (Liquid Line) (psig)
Cutout
7
22
3
5
Reset (Auto.)
FREEZE-PROTECTION THERMOSTAT
Opens (F)
Closes (F)
30
45
5
5
OUTDOOR-AIR INLET SCREENS
RETURN-AIR FILTERS
Quantity...Size (in.)
Cleanable. Screen size and quantity varies by options selected.
Throwaway
4...16 x 20 x 2
4...16 x 20 x 2
4...20 x 20 x 2
4...20 x 20 x 2
LEGEND
Bhp — Brake Horsepower
—6—
V. STEP 5 — MAKE ELECTRICAL CONNECTIONS
When installing units, provide a disconnect per the NEC.
All field wiring must comply with the NEC and local require-
ments. In Canada, electrical connections must be made in
accordance with CSA (Canadian Standards Association)
C22.1 Canadian Electrical Code Part One.
WARNING: Unit cabinet must have an uninter-
rupted, unbroken electrical ground to minimize the
possibility of personal injury if an electrical fault
should occur. This ground may consist of electrical wire
connected to unit ground lug in control compartment,
or conduit approved for electrical ground when
installed in accordance with NEC (National Electrical
Code) ANSI (American National Standards Institute) /
NFPA (National Fire Protection Association) 70-latest
year and local electrical codes. Failure to follow this
warning could result in the installer being liable for
personal injury of others.
Install field wiring as follows:
1. Install conduit through side panel openings. For units
without electric heat, install conduit between discon-
nect and control box.
2. Install power lines to terminal connections as shown
in Fig. 8.
3. For units with electric heat, refer to Accessory Instal-
lation Instructions.
During operation, voltage to compressor terminals must be
within range indicated on unit nameplate (see Table 2). On
3-phase units, voltages between phases must be balanced
within 2%, and the current within 10%. Use the formula
shown in Table 2, Note 2 on page 10 to determine the per-
centage of voltage imbalance. Operation on improper line
voltage or excessive phase imbalance constitutes abuse and
may cause damage to electrical components. Such operation
would invalidate any applicable Bryant warranty.
A. Field Power Supply
All units except 208/230-v units are factory-wired for the
voltage shown on the unit nameplate. If the 208/230-v unit is
to be connected to a 208-v power supply, the transformer
must be rewired by disconnecting the black wire from the
230-v terminal wire on the transformer and connecting it to
the 200-v red terminal of the transformer. The end of the
orange wire must then be insulated.
See Table 3 for electric heater and single point box usage.
Refer to unit label diagram for additional information.
Pigtails are provided for field wire connections. Use factory-
supplied splices or UL (Underwriters’ Laboratories)
approved copper/aluminum connector.
551B150, 208/230-3-60
551B090-120, 208/230-3-60
551B090-150, 460-3-60
LEGEND
C
—
Contactor
COMP(S) — Compressor
IFC
—
—
—
—
Indoor (Evaporator) Fan Contactor
National Electrical Code
Outdoor (Condenser) Fan Contactor
Terminal Block
NEC
OFC
TB
Terminal Block Connection
Field Wiring
Factory Wiring
Splice Connection
(Factory-Supplied)
551B090-150, 575-3-60
Fig. 8 — Power Wiring Connections
—7—
Table 2 — Electrical Data
VOLTAGE
RANGE
ELECTRIC HEATER
POWER SUPPLY
DISCONNECT
SIZE†
COMP NO. 1 COMP NO. 2
Fuse
or
UNIT
551B
NOMINAL
V-PH-Hz
IFM
TYPE
CONV
OUTLET
OFM OFM IFM
Nominal
QTY
FLA FLA
FLA
MCA
MOCP
Min Max RLA
LRA
RLA
LRA
kW*
HACR
Bkr
FLA
LRA
—
—/—
38.2/ 38.2
38.2/ 40.6
51.1/ 57.5
74.0/ 84.0
92.8/105.6
119.9/136.9
45/45
45/45
60/60
—
—
—
40/ 40
40/ 40
47/ 53
68/ 77
85/ 97
110/126
242/242
242/242
242/242
242/242
242/242
242/242
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
21.7/ 25.0
33.4/ 38.5
51.7/ 59.7
66.7/ 77.0
88.4/102.0
—
STD
STD
NO
YES
NO
187
187
187
187
414
414
414
414
254
254
254
254
508
508
508
508
12.4
12.4
12.4
12.4
6.4
88.0 12.4
88.0 12.4
88.0 12.4
88.0 12.4
88.0
2
1.4
1.4
1.4
1.4
0.7
0.7
0.7
0.7
7.5
7.5
80/ 90
100/110
125/150
—
—
—
—/—
44.2/ 44.2
44.2/ 45.6
56.1/ 62.5
79.0/ 89.0
97.8/110.6
124.9/141.9
50/50
50/50
—
—
46/ 46
46/ 46
53/ 58
74/ 83
91/103
116/131
247/247
247/247
247/247
247/247
247/247
247/247
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
21.7/ 25.0
33.4/ 38.5
51.7/ 59.7
66.7/ 77.0
88.4/102.0
—
60/ 70
80/ 90
100/125
125/150
88.0
88.0
88.0
44.0
44.0
44.0
44.0
2
2
2
2
2
2
2
—
—
—
208/230-3-60
—
—/—
41.3/ 41.3
41.3/ 44.5
54.9/ 61.4
77.9/ 87.8
96.6/109.5
123.7/140.8
45/45
50/50
—
—
—
60/ 70
80/ 90
100/110
125/150
44/ 44
44/ 44
51/ 56
72/ 81
89/101
114/129
267/267
267/267
267/267
267/267
267/267
267/267
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
21.7/ 25.0
33.4/ 38.5
51.7/ 59.7
66.7/ 77.0
88.4/102.0
HIGH
STATIC
10.6
10.6
3.4
—
—
—
—
—/—
47.3/ 47.3
47.3/ 49.5
59.9/ 66.4
82.9/ 92.8
101.6/114.5
128.7/145.8
50/50
60/60
—
—
—
70/ 70
90/100
110/125
150/150
49/ 49
49/ 49
56/ 62
77/ 86
94/106
119/135
271/271
271/271
271/271
271/271
271/271
271/271
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
21.7/ 25.0
33.4/ 38.5
51.7/ 59.7
66.7/ 77.0
88.4/102.0
HIGH
STATIC
YES
NO
—
—
—
—
—
19.2
25.1
29.1
46.0
53.9
66.9
20
20
20
50
60
—
—
—
—
—
—
70
20
23
27
42
50
62
121
121
121
121
121
121
13.9
16.5
27.8
33.0
41.7
16.7
19.8
33.4
39.7
50.2
STD
STD
44.0
44.0
44.0
44.0
6.4
6.4
6.4
6.4
090
—
—
21.9
28.5
31.8
48.7
56.6
69.6
20
20
35
50
60
—
—
—
—
—
—
70
23
26
29
45
52
64
123
123
123
123
123
123
13.9
16.5
27.8
33.0
41.7
16.7
19.8
33.4
39.7
50.2
YES
NO
6.4
3.4
460-3-60
—
—
20.6
26.9
30.8
47.8
55.6
68.7
20
20
35
50
60
—
—
—
—
—
—
70
22
25
28
44
51
63
133
134
134
134
134
134
13.9
16.5
27.8
33.0
41.7
16.7
19.8
33.4
39.7
50.2
HIGH
STATIC
6.4
4.8
—
—
23.3
30.3
33.5
50.5
58.3
71.4
20
35
35
60
60
—
—
—
—
—
—
80
24
27
31
46
54
66
135
136
136
136
136
136
13.9
16.5
27.8
33.0
41.7
16.7
19.8
33.4
39.7
50.2
HIGH
STATIC
YES
6.4
4.8
—
—
14.6
23.8
44.3
20
20
45
—
—
—
15
22
41
94
95
95
STD
STD
NO
YES
NO
518
518
518
518
632
632
632
632
4.8
4.8
4.8
4.8
34.0
34.0
34.0
34.0
4.8
4.8
4.8
4.8
34.0
34.0
34.0
34.0
2
2
2
2
0.7
0.7
0.7
0.7
3.4
3.4
4.8
4.8
17.0
34.0
16.4
32.7
—
17.0
34.0
—
16.4
32.7
16.8
26.5
44.3
20
20
45
—
—
—
17
24
43
96
96
96
575-3-60
—
17.0
34.0
—
16.4
32.7
15.8
25.2
45.7
20
20
50
—
—
—
17
23
42
104
104
104
HIGH
STATIC
—
17.0
34.0
—
16.4
32.7
17.9
27.9
45.7
20
20
50
—
—
—
19
25
44
106
106
106
HIGH
STATIC
YES
—
—/—
40.2/ 40.2
40.2/ 40.6
51.1/ 57.5
74.0/ 84.0
92.8/105.6
119.9/136.9
45/45
45/45
60/60
—
—
—
42/ 42
42/ 42
47/ 53
68/ 77
85/ 97
110/126
276/276
276/276
276/276
276/276
276/276
276/276
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
21.7/ 25.0
33.4/ 38.5
51.7/ 59.7
66.7/ 77.0
88.4/102.0
—
STD
STD
NO
YES
NO
187
187
187
187
414
414
414
414
254
254
254
254
508
508
508
508
13.4 105.0 13.1 105.0
13.4 105.0 13.1 105.0
13.4 105.0 13.1 105.0
13.4 105.0 13.1 105.0
2
2
2
2
2
2
2
2
1.4
1.4
1.4
1.4
0.7
0.7
0.7
0.7
7.5
7.5
80/ 90
100/110
110/150
—
—
—
—/—
46.2/ 46.2
46.2/ 46.2
56.1/ 62.5
79.0/ 89.0
97.8/110.6
124.9/141.9
50/50
50/50
—
—
48/ 48
48/ 48
53/ 58
74/ 83
91/103
116/131
281/281
281/281
281/281
281/281
281/281
281/281
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
21.7/ 25.0
33.4/ 38.5
51.7/ 59.7
66.7/ 77.0
88.4/102.0
—
60/ 70
80/ 90
100/125
125/150
—
—
—
208/230-3-60
—
—/—
43.3/ 43.3
43.3/ 44.5
54.9/ 61.4
77.9/ 87.8
96.6/109.5
123.7/140.8
50/50
50/50
—
—
—
60/ 70
80/ 90
100/110
125/150
46/ 46
46/ 46
51/ 56
72/ 81
89/101
114/129
301/301
301/301
301/301
301/301
301/301
301/301
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
21.7/ 25.0
33.4/ 38.5
51.7/ 59.7
66.7/ 77.0
88.4/102.0
HIGH
STATIC
10.6
10.6
3.4
—
—
—
—
—/—
49.3/ 49.3
49.3/ 49.5
59.9/ 66.4
82.9/ 92.8
101.6/114.5
128.7/145.8
60/60
60/60
—
—
—
70/ 70
90/100
110/125
150/150
51/ 51
51/ 51
56/ 62
77/ 86
94/106
119/135
305/305
305/305
305/305
305/305
305/305
305/305
7.8/10.4
12.0/16.0
18.6/24.8
24.0/32.0
31.8/42.4
21.7/ 25.0
33.4/ 38.5
51.7/ 59.7
66.7/ 77.0
88.4/102.0
HIGH
STATIC
YES
NO
—
—
—
102
—
—
21.5
25.1
29.1
46.0
53.9
66.9
20
20
20
50
60
—
—
—
—
—
—
70
23
23
27
42
50
62
143
143
143
143
143
143
13.9
16.5
27.8
33.0
41.7
16.7
19.8
33.4
39.7
50.2
STD
STD
7.4
7.4
7.4
7.4
55.0
55.0
55.0
55.0
7.4
7.4
7.4
7.4
55.0
55.0
55.0
55.0
—
—
24.2
28.5
31.8
48.7
56.6
69.6
20
20
35
50
60
—
—
—
—
—
—
70
25
26
29
45
52
64
145
145
145
145
145
145
13.9
16.5
27.8
33.0
41.7
16.7
19.8
33.4
39.7
50.2
YES
NO
3.4
460-3-60
—
—
22.9
26.9
30.8
47.8
55.6
68.7
20
20
35
50
60
—
—
—
—
—
—
70
24
25
28
44
51
63
155
156
156
156
156
156
13.9
16.5
27.8
33.0
41.7
16.7
19.8
33.4
39.7
50.2
HIGH
STATIC
4.8
—
—
25.6
30.3
33.5
50.5
58.3
71.4
20
35
35
60
60
—
—
—
—
—
—
80
27
27
31
46
54
66
157
158
158
158
158
158
13.9
16.5
27.8
33.0
41.7
16.7
19.8
33.4
39.7
50.2
HIGH
STATIC
YES
4.8
See page 10 for legend and notes.
—8—
Table 2 — Electrical Data (cont)
VOLTAGE
RANGE
ELECTRIC HEATER
POWER SUPPLY
DISCONNECT
SIZE†
COMP NO. 1 COMP NO. 2
Fuse
or
UNIT
551B
NOMINAL
V-PH-Hz
IFM
TYPE
CONV
OUTLET
OFM OFM IFM
Nominal
kW*
QTY
FLA FLA
FLA
MCA
MOCP
Min
Max RLA
LRA
RLA
LRA
HACR
Bkr
FLA
LRA
—
—
18.2
23.8
44.3
20
20
45
—
—
—
19
22
41
114
115
115
STD
STD
NO
YES
NO
518
632
632
632
632
6.4
6.4
6.4
6.4
44.0
6.4
44.0
2
2
2
2
0.7
0.7
0.7
0.7
3.4
3.4
3.4
4.8
17.0
34.0
16.4
32.7
—
17.0
34.0
—
16.4
32.7
20.4
26.5
46.9
25
25
50
—
—
—
21
24
43
116
116
116
518
518
518
44.0
44.0
44.0
6.4
6.4
6.4
44.0
44.0
44.0
102
(cont)
575-3-60
—
17.0
34.0
—
16.4
32.7
18.2
23.8
44.3
20
20
45
—
—
—
19
22
41
114
115
115
HIGH
STATIC
—
17.0
34.0
—
16.4
32.7
21.5
27.9
48.3
25
25
50
—
—
—
22
25
44
126
126
126
HIGH
STATIC
YES
—
—/—
53.0/ 53.0
53.0/ 53.0
54.9/ 61.4
96.6/109.5
123.7/140.8
143.5/133.5
60/60
60/60
—
—
56/ 56
56/ 56
56/ 56
89/101
114/129
132/151
341/341
341/341
341/341
341/341
341/341
341/341
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.5/50.0
21.7/ 25.0
33.4/ 38.5
66.7/ 77.0
88.4/102.0
104.2/120.3
—
60/ 70
100/110
125/150
150/150
STD
STD
NO
YES
NO
187
187
187
187
414
414
414
414
254
254
254
254
508
508
508
508
17.6 125.0 17.6 125.0
17.6 125.0 17.6 125.0
17.6 125.0 17.6 125.0
17.6 125.0 17.6 125.0
2
2
2
2
2
2
2
2
1.4
1.4
1.4
1.4
0.7
0.7
0.7
0.7
10.6
10.6
15.0
15.0
4.8
—
—
—
—
—/—
59.0/ 59.0
59.0/ 59.0
59.9/ 66.4
101.6/114.5
128.7/145.8
148.5/137.5
70/70
—
—
61/ 61
61/ 61
61/ 62
94/106
119/135
138/156
345/345
345/345
345/345
345/345
345/345
345/345
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.5/50.0
21.7/ 25.0
33.4/ 38.5
66.7/ 77.0
88.4/102.0
104.2/120.3
70/ 70
70/ 70
110/125
150/150
150/150
—
—
—
—
208/230-3-60
—
—/—
57.4/ 57.4
57.4/ 57.4
60.4/ 66.9
102.1/115.0
129.2/146.3
149.0/139.0
70/70
—
—
61/ 61
61/ 61
61/ 62
94/106
119/135
137/156
364/364
364/364
364/364
364/364
364/364
364/364
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.5/50.0
21.7/ 25.0
33.4/ 38.5
66.7/ 77.0
88.4/102.0
104.2/120.3
70/ 70
70/ 80
110/125
150/150
150/175
HIGH
STATIC
—
—
—
—
—
—/—
63.4/ 63.4
63.4/ 63.4
65.4/ 71.9
107.1/120.0
134.2/151.3
154.0/143.0
70/70
—
—
66/ 66
66/ 66
66/ 67
99/111
124/140
143/161
369/369
369/369
369/369
369/369
369/369
369/369
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.5/50.0
21.7/ 25.0
33.4/ 38.5
66.7/ 77.0
88.4/102.0
104.2/120.3
70/ 70
80/ 80
110/125
150/175
175/175
HIGH
STATIC
—
YES
NO
—
—
—
—
—
24.9
26.9
30.8
55.6
68.7
66.1
20
20
35
60
—
—
—
—
—
—
70
80
26
26
28
51
63
75
170
171
171
171
171
171
13.9
16.5
33.0
41.7
50.0
16.7
19.8
39.7
50.2
60.1
STD
STD
8.3
8.3
8.3
8.3
62.5
62.5
62.5
62.5
8.3
8.3
8.3
8.3
62.5
62.5
62.5
62.5
—
—
27.6
30.3
33.5
58.3
71.4
70.1
20
35
35
60
—
—
—
—
—
—
80
80
29
29
31
54
66
77
172
173
173
173
173
173
13.9
16.5
33.0
41.7
50.0
16.7
19.8
39.7
50.2
60.1
120
YES
NO
4.8
460-3-60
—
—
27.5
30.1
34.1
58.9
71.9
69.4
20
35
40
60
—
—
—
—
—
—
80
80
29
29
31
54
66
78
182
182
182
182
182
182
13.9
16.5
33.0
41.7
50.0
16.7
19.8
39.7
50.2
60.1
HIGH
STATIC
7.4
—
—
30.2
33.5
36.8
61.6
74.6
73.4
35
40
40
—
—
—
—
—
—
70
80
80
32
32
34
57
69
80
184
184
184
184
184
184
13.9
16.5
33.0
41.7
50.0
16.7
19.8
39.7
50.2
60.1
HIGH
STATIC
YES
7.4
—
—
19.1
25.2
45.7
53.9
25
25
50
60
—
—
—
—
20
23
42
61
136
136
136
136
17.0
34.0
51.0
16.4
32.7
49.1
STD
STD
NO
YES
NO
518
518
518
518
632
632
632
632
6.3
6.3
6.3
6.3
50.0
50.0
50.0
50.0
6.3
6.3
6.3
6.3
50.0
50.0
50.0
50.0
2
2
2
2
0.7
0.7
0.7
0.7
4.8
4.8
7.4
7.4
—
—
21.3
27.9
48.3
56.5
25
25
50
60
—
—
—
—
22
25
44
63
138
138
138
138
17.0
34.0
51.0
16.4
32.7
49.1
575-3-60
—
—
21.2
27.8
48.3
56.5
25
25
50
—
—
—
—
70
23
26
44
63
145
146
146
146
HIGH
STATIC
17.0
34.0
51.0
16.4
32.7
49.1
—
—
23.4
30.5
50.9
59.1
25
35
60
—
—
—
—
70
25
28
46
65
147
148
148
148
HIGH
STATIC
17.0
34.0
51.0
16.4
32.7
49.1
YES
—
—/—
60.6/ 60.6
60.6/ 60.6
60.4/ 66.9
102.1/115.0
129.2/146.3
149.0/139.0
70/70
—
—
64/ 64
64/ 64
64/ 64
94/106
119/135
137/156
426/426
426/426
426/426
426/426
426/426
426/426
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.5/50.0
21.7/ 25.0
33.4/ 38.5
66.7/ 77.0
88.4/102.0
104.2/120.3
70/ 70
70/ 80
110/125
150/150
150/175
—
STD
STD
STD
STD
NO
YES
NO
187
187
414
414
254
254
508
508
19.0 156.0 19.0 156.0
19.0 156.0 19.0 156.0
2
2
2
2
1.4
1.4
0.7
0.7
15.0
15.0
7.4
—
—
—
208/230-3-60
—
—/—
66.6/ 66.6
66.6/ 66.6
65.4/ 71.9
107.1/120.0
134.2/151.3
154.0/143.0
70/70
—
—
70/ 70
70/ 70
70/ 70
99/111
124/140
143/161
431/431
431/431
431/431
431/431
431/431
431/431
7.8/10.4
12.0/16.0
24.0/32.0
31.8/42.4
37.5/50.0
21.7/ 25.0
33.4/ 38.5
66.7/ 77.0
88.4/102.0
104.2/120.3
70/ 70
80/ 80
110/125
150/175
175/175
—
—
—
—
—
—
29.1
30.1
34.1
58.9
71.9
69.4
35
35
40
60
—
—
—
—
—
—
80
80
31
31
31
54
66
78
197
197
197
197
197
197
13.9
16.5
33.0
41.7
50.0
16.7
19.8
39.7
50.2
60.1
9.0
9.0
70.0
70.0
9.0
9.0
70.0
70.0
150
460-3-60
—
—
31.8
33.5
36.8
61.6
74.6
73.4
35
40
40
—
—
—
—
—
—
70
80
80
33
33
34
57
69
80
199
199
199
199
199
199
13.9
16.5
33.0
41.7
50.0
16.7
19.8
39.7
50.2
60.1
YES
7.4
—
—
23.7
27.8
48.3
56.5
30
30
50
—
—
—
—
70
25
26
44
63
153
154
154
154
17.0
34.0
51.0
16.4
32.7
49.1
STD
STD
NO
518
518
632
632
7.4
7.4
54.0
54.0
7.4
7.4
54.0
54.0
2
2
0.7
0.7
7.4
7.4
575-3-60
—
—
25.9
30.5
50.9
59.1
30
35
60
—
—
—
—
70
27
28
46
65
155
155
155
155
17.0
34.0
51.0
16.4
32.7
49.1
YES
See page 10 for legend and notes.
—9—
LEGEND AND NOTES FOR TABLE 2
LEGEND
Example: Supply voltage is 460-3-60.
FLA — Full Load Amps
AB = 452 v
BC = 464 v
AC = 455 v
HACR — Heating, Air Conditioning and Refrigeration
IFM — Indoor (Evaporator) Fan Motor
LRA — Locked Rotor Amps
MCA — Minimum Circuit Amps
452 + 464 + 455
3
Average Voltage =
MOCP— Maximum Overcurrent Protection
NEC — National Electrical Code
OFM — Outdoor (Condenser) Fan Motor
RLA — Rated Load Amps
1371
3
=
=
*Heater capacity (kW) is based on heater voltage of 208, 240, 480, and 575-V. If power
distribution voltage varies from rated heater voltage, heater kW will vary accordingly.
†Used to determine minimum disconnect per NEC.
457
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
NOTES:
(AC) 457 – 455 = 2 v
1. In compliance with NEC requirements for multimotor and combination load equip-
ment (refer to NEC Articles 430 and 440), the overcurrent protective device for the
unit shall be fuse or HACR breaker.
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
2. Unbalanced 3-Phase Supply Voltage
7
% Voltage Imbalance = 100 x
457
Never operate a motor where a phase imbalance in supply voltage is greater than
2%. Use the following formula to determine the percent of voltage imbalance.
% Voltage Imbalance
= 1.53%
max voltage deviation from average voltage
This amount of phase imbalance is satisfactory as it is below the maximum allow-
able 2%.
= 100 x
average voltage
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your
local electric utility company immediately.
3. Non-fused disconnect switch cannot be used when rooftop unit electrical ratings
exceed 80 amps.
Table 3 — Electric Heater Usage
ACCESSORY HEATER
PART NUMBER
CRHEATER---A00
ACCESSORY SINGLE POINT BOX
PART NUMBER
UNIT
551B
VOLTAGE
(60 Hz)
ACCESORY
kW
CRSINGLE---A00
7.8/ 9.6/10.4
12.0/14.7/16.0
18.6/22.8/24.8
24.0/29.4/32.0
31.8/39.0/42.4
017
010
006
006
007
007
009
208/230/240
(3 phase)
011
012
012+017
12.8/13.9
15.2/16.5
25.6/27.8
30.4/33.0
38.4/41.7
016
013
006
006
006
006
008
090
460/480
(3 phase)
014
015
014+016
575
(3 phase)
17.0
34.0
018
019
006
006
7.8/ 9.6/10.4
12.0/14.7/16.0
18.6/22.8/24.8
24.0/29.4/32.0
31.8/39.0/42.4
017
010
011
011
012
012
015
208/230/240
(3 phase)
011
012
012+017
12.8/13.9
15.2/16.5
25.6/27.8
30.4/33.0
38.4/41.7
016
013
011
011
011
011
014
102
460/480
(3 phase)
014
015
014+016
575
(3 phase)
17.0
34.0
018
019
011
011
7.8/ 9.6/10.4
12.0/14.7/16.0
24.0/29.4/32.0
31.8/38.9/42.4
37.5/46.0/50.0
017
010
011
012
012
015
015
208/230/240
(3 phase)
012
012+017
010+012
12.8/13.9
15.2/16.5
30.4/33.0
38.4/41.7
46.0/50.0
016
013
011
011
011
014
014
120
460/480
(3 phase)
015
014+016
013+015
17.0
34.0
51.0
018
019
018+019
011
011
014
575
(3 phase)
7.8/ 9.6/10.4
12.0/14.7/16.0
24.0/29.4/32.0
31.8/38.9/42.4
37.5/46.0/50.0
017
010
012
012
012
015
015
208/230/240
(3 phase)
012
012+017
010+012
12.8/13.9
15.2/16.5
30.4/33.0
38.4/41.7
46.0/50.0
016
013
011
011
011
014
014
150
460/480
(3 phase)
015
014+016
013+015
17.0
34.0
51.0
018
019
018+019
011
014
014
575
(3 phase)
NOTES:
1. The rated heater voltage is 240, 480, and 575 v. If power distribution voltage varies from rated heater voltage, heater kW vary accordingly.
2. To determine heater kW at voltages other than those shown in table, use the following formula:
Heater kW new = Heater kW rated x (unit power distribution voltage / rated heater voltage) 2
As an example:
For a 16 kW heater rated at 240 v with a power distribution voltage of 215 v
kW new = 16 kW (215/240) 2
kW new = 12.8 kW (rating at 215 v)
—10—
B. Field Control Wiring
UL required clearance between the high-voltage and
low-voltage wiring.
Install a Bryant-approved accessory thermostat assembly
according to installation instructions included with the
accessory. Locate thermostat assembly on a solid wall in the
conditioned space to sense average temperature in accor-
dance with thermostat installation instructions.
5. Connect thermostat wires to screw terminals of low-
voltage connector (see Fig. 9).
NOTE: If thru-the-bottom power connections are used refer
to the accessory installation instructions for information on
power wiring. Refer to Fig. 7 for drilling holes in basepan.
Route thermostat cable or equivalent single leads of colored
wire from subbase terminals to low-voltage connections on
unit (shown in Fig. 9) as described in Steps 1 through 4 below.
C. Heat Anticipator Settings
For units with electric heat, set heat anticipator settings as
shown in Table 4.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American
Wire Gage) insulated wire (35 C minimum). For 51 to 75 ft,
use no. 16 AWG insulated wire (35 C minimum). For over
75 ft, use no. 14 AWG insulated wire (35 C minimum). All
wire larger than no. 18 AWG cannot be directly connected to
the thermostat and will require a junction box and splice at
the thermostat.
VI. STEP 6 — ADJUST FACTORY-INSTALLED OPTIONS
A. Disconnect Switch
The optional disconnect switch is non-fused. The switch has
the capability of being locked in place for safety purposes.
B. Perfect Humidity™ Dehumidification System
1. If mounted on a roof curb and electrical power is to be
run through the basepan, an accessory thru-the-
bottom connection kit is required. This is available
through the local Bryant distributor. This kit is
required to ensure a reliable water-tight connection.
Perfect Humidity system operation can be controlled by field
installation of a Bryant-approved humidistat (Fig. 11), or
light commercial Thermidistat™ device (Fig. 12). To install
the humidistat:
1. Route humidistat cable through hole provided in unit
corner post.
2. If unit is mounted on roof curb and accessory thru-
the-bottom service connections are used, route wire
through connections.
2. Feed wires through the raceway built into the corner
post to the 24-v barrier located on the left side of the
control box. See Fig. 10. The raceway provides the
UL-required clearance between high-voltage and low-
voltage wiring.
3. Pass control wires through the hole provided on unit
(see connection D in Connection Sizes table in Fig. 7).
4. Feed wire through the raceway built into the corner
post to the 24-v barrier located on the left side of the
control box. See Fig. 9. The raceway provides the
CONNECTION
BOARD
R
G
COOL STAGE 1
FAN
Y1/W2
G
FACTORY-
INSTALLED
DISCONNECT
(OPTION)
WIRE
Y1
HEAT STAGE 1
COOL STAGE 2
HEAT STAGE 2
24 VAC HOT
W/W1
Y/Y2
O/W2
R
CONNECTIONS
TO
Y2
LOW-VOLTAGE
SECTION
(CONNECTION
BOARD)
W1
W2
C
RACEWAY
COMPRESSOR
NO. 2
24 VAC COM
N/A
C
COMPRESSOR
NO. 1
IPD/X
OUTDOOR AIR
SENSOR
S1
S2
CONVENIENCE
OUTLET
(OPTION)
THERMOSTAT DIPSWITCH SETTINGS
ON
OFF
HOLE IN
END
PANEL
D
A
B
C
LEGEND
Field Wiring
NOTE: Underlined letter indicates active thermostat output when configured
for A/C operation.
Fig. 9 — Low-Voltage Connections
Fig. 10 — Field Control Wiring Raceway
Table 4 — Heat Anticipator Settings
UNIT VOLTAGE
460
208/230
Configuration
2-Stage
575
Configuration
2-Stage
UNIT
551B
Configuration
2-Stage
Stage 1
Heater
kW*
Heater
kW
Heater
kW
1-Stage
1-Stage
1-Stage
Stage 1
NA
Stage 2
NA
Stage 2
Stage 1
Stage 2
10.4, 16.0
24.8, 32.0
42.4, 50.0
0.3
0.6
0.9
13.9, 16.5
27.8, 33.0
41.7, 50.0
0.3
0.6
NA
NA
17.0, 34.0
51.0
0.3
0.6
NA
NA
0.3
0.3
0.3
0.6
0.3
0.3
0.3
0.3
*Heater capacity (kW) is based on heater voltage of 208 v, 240 v, 480 v or 575 v. If power distribution voltage to unit varies from rated heater voltage,
heater kW will vary accordingly.
—11—
3. Use a wire nut to connect humidistat cable into low-
voltage wiring as shown in Fig. 13.
3. A field-supplied relay must be installed between the
Thermidistat device and the Perfect Humidity™ cir-
cuit (recommended relay: HN612KK324) Fig. 14. The
relay coil is connected between the DEHUM output
and C (common) of the unit. The relay controls the
Perfect Humidity solenoid valve and must be wired
between the Perfect Humidity fuse and the low-
pressure switch. Refer to the installation instructions
included with the Bryant Light Commercial Thermi-
distat device for more information.
To install Thermidistat™ device:
1. Route Thermidistat cable through hole provided in
unit corner post.
2. Feed the wires through the raceway built into the cor-
ner post to the 24-v barrier located on the left side of
the control box. See Fig. 10. The raceway provides the
UL-required clearance between high and low voltage
wiring.
% RELATIVE HUMIDITY
Fig. 12 — Light Commercial Thermidistat Device
Fig. 11 — Accessory Field-Installed Humidistat
LEGEND
CB
—
—
—
—
—
—
—
—
—
—
Circuit Breaker
TRAN — Transformer
CR
Cooling Relay
Field Splice
DHR
DSV
HR
Dehumidify Relay
Discharge Solenoid Valve
Heater Relay
Terminal (Unmarked)
HU
Humidistat
Splice
LPS
LSV
LTLO
TB
Low Pressure Switch
Liquid Solenoid Valve
Low Temperature Lockout
Terminal Block
Factory Wiring
Field Control Wiring
Fig. 13 — Typical Perfect Humidity Dehumidification System Humidistat Wiring (208/230-v Unit Shown)
LCT
ROOF TOP UNIT
R
C
R
C
Y1
Y2
G
Y1
Y2
G
W1
W2
W1
W2
CB
R1
R1
DEHUM
OC
3.2 AMPS
PINK
RED
24V
T STAT WIRES
LEGEND
LTLO
PINK
PINK
FROM
PERFECT HUMIDITY
SYSTEM LLSV
CB
—
—
—
—
Circuit Breaker
LCT
LLSV
LTLO
Light Commercial Thermidistat Device
Liquid Line Solenoid Valve
Low Temperature Lockout
PERFECT HUMIDITY SYSTEM
Fig. 14 — Typical Rooftop Unit with Perfect Humidity Dehumidification System with Thermidistat Device
—12—
C. Convenience Outlet
1. To remove the existing unit filter access panel, raise
the panel and swing the bottom outward. The panel is
now disengaged from the track and can be removed.
See Fig. 20.
An optional convenience outlet provides power for rooftop
use. For maintenance personnel safety, the convenience out-
let power is off when the unit disconnect is off. Adjacent unit
outlets may be used for service tools. An optional “Hot Out-
let” is available from the factory as a special order item.
D. Manual Outdoor-Air Damper
The outdoor-air hood and screen are attached to the basepan
at the bottom of the unit for shipping.
Assembly:
1. Determine quantity of ventilation required for build-
ing. Record amount for use in Step 8.
2. Remove filter access panel by raising panel and
swinging panel outward. Panel is now disengaged
from track and can be removed. No tools are required
to remove the filter access panel. Remove outdoor-air
opening panel. Save panels and screws. See Fig. 15.
3. Separate hood and screen from basepan by removing
the screws and brackets securing them. Save all
screws and discard brackets.
4. Replace outdoor air opening panel.
5. Place hood on front of outdoor air opening panel. See
Fig. 16 for hood details. Secure top of hood with the
6 screws removed in Step 3. See Fig. 17.
6. Remove and save 8 screws (4 on each side) from sides
of the manual outdoor-air damper.
Fig. 16 — Outdoor-Air Hood Details
7. Align screw holes on hood with screw holes on side of
manual outdoor-air damper. See Fig. 16 and 17.
Secure hood with 8 screws from Step 6.
SCREW
HOLES
(TOP)
8. Adjust minimum position setting of the damper blade
by adjusting the manual outdoor-air adjustment
screws on the front of the damper blade. See Fig. 15.
Slide blade vertically until it is in the appropriate
position determined by Fig. 18. Tighten screws.
9. Remove and save screws currently on sides of hood.
Insert screen. Secure screen to hood using the screws.
See Fig. 17.
HOOD
HOOD
SCREEN
LOCATION
(SCREEN
NOT
10. Replace filter access panel. Ensure filter access panel
slides along the tracks and is securely engaged.
SHOWN)
E. Optional EconoMi$er IV
See Fig. 19 for EconoMi$er IV component locations.
NOTE: These instructions are for installing the optional
EconoMi$er IV. Refer to the accessory EconoMi$er IV installa-
tion instructions when field installing an EconoMi$er IV
accessory.
Fig. 17 — Optional Manual Outdoor-Air
Damper with Hood Attached
FILTER
ACCESS
PANEL
OUTDOOR AIR
OPENING
PANEL
SCREWS
(SIDE)
MANUAL
OUTDOOR-AIR
ADJUSTMENT
SCREWS
DAMPER
BLADE
Fig. 15 — Damper Panel with Manual
Outdoor-Air Damper Installed
Fig. 18 — Outdoor Air Damper Position Setting
—13—
2. The box with the economizer hood components is
shipped in the compartment behind the economizer.
The EconoMi$er IV controller is mounted on top of
the EconoMi$er IV in the position shown in Fig. 19.
To remove the component box from its shipping posi-
tion, remove the screw holding the hood box bracket
to the top of the economizer. Slide the hood box out of
the unit. See Fig. 21.
position past the open filter clips. Close the filter clips
to lock the filter into place. See Fig. 24.
8. Caulk the ends of the joint between the unit top panel
and the hood top. See Fig. 22.
9. Replace the filter access panel.
10. Install all EconoMi$er IV accessories. EconoMi$er IV
wiring is shown in Fig. 25.
Barometric flow capacity is shown in Fig. 26. Outdoor air
leakage is shown in Fig. 27. Return air pressure drop is
shown in Fig. 28.
IMPORTANT: If the power exhaust accessory is to be
installed on the unit, the hood shipped with the unit will not
be used and must be discarded. Sa ve th e a lu m in u m filter
for u se in th e p ow er exh a u st h ood a ssem b ly.
F. EconoMi$er IV Standard Sensors
Outdoor Air Temperature (OAT) Sensor
3. The indoor coil access panel will be used as the top of
the hood. Remove the screws along the sides and bot-
tom of the indoor coil access panel. See Fig. 22.
The outdoor air temperature sensor (HH57AC074) is a 10 to
20 mA device used to measure the outdoor-air temperature.
The outdoor-air temperature is used to determine when the
EconoMi$er IV can be used for free cooling. The sensor is
factory-installed on the EconoMi$er IV in the outdoor air-
stream. See Fig. 19. The operating range of temperature
measurement is 40 to 100 F.
4. Swing out indoor coil access panel and insert the
hood sides under the panel (hood top). Use the screws
provided to attach the hood sides to the hood top. Use
screws provided to attach the hood sides to the unit.
See Fig. 23.
Supply Air Temperature (SAT) Sensor
5. Remove the shipping tape holding the economizer
barometric relief damper in place.
The supply air temperature sensor is a 3 K thermistor
located at the inlet of the indoor fan. See Fig. 29. This sensor
is factory installed. The operating range of temperature
measurement is 0° to 158 F. See Table 5 for sensor tempera-
ture/resistance values.
6. Insert the hood divider between the hood sides. See
Fig. 23 and 24. Secure hood divider with 2 screws on
each hood side. The hood divider is also used as the
bottom filter rack for the aluminum filter.
7. Open the filter clips which are located underneath
the hood top. Insert the aluminum filter into the bot-
tom filter rack (hood divider). Push the filter into
ECONOMI$ER IV
CONTROLLER
HOOD BOX
BRACKET
OUTSIDE AIR
WIRING
TEMPERATURE SENSOR
HARNESS
LOW AMBIENT
SENSOR
ACTUATOR
Fig. 21 — Hood Box Removal
Fig. 19 — EconoMi$er IV Component Locations
FILTER ACCESS PANEL
SIDE
PANEL
TOP
SIDE
PANEL
CAULK
HERE
INDOOR
COIL
ACCESS
PANEL
INDOOR
COIL
ACCESS
PANEL
INDOOR COIL ACCESS PANEL
Fig. 20 — Typical Access Panel Locations
Fig. 22 — Indoor Coil Access Panel Relocation
—14—
22 1/4”
TOP
PANEL
INDOOR COIL
ACCESS PANEL
DIVIDER
LEFT
HOOD
SIDE
SCREW
OUTSIDE
AIR
B
24 9/16”
HOOD
CLEANABLE
ALUMINUM
FILTER
40 3/8”
FILTER
HOOD DIVIDER
BAROMETRIC
RELIEF
Fig. 23 — Outdoor-Air Hood Construction
FILTER
CLIP
Fig. 24 — Filter Installation
FOR OCCUPANCY CONTROL
REPLACE JUMPER WITH
FIELD-SUPPLIED TIME CLOCK
LEGEND
Potentiometer Defaults Settings:
Power Exhaust Middle
NOTES:
1. 620 ohm, 1 watt 5% resistor should be removed only when using differential
enthalpy or dry bulb.
DCV— Demand Controlled Ventilation
IAQ — Indoor Air Quality
Minimum Pos.
DCV Max.
DCV Set
Fully Closed
Middle
2. If a separate field-supplied 24 v transformer is used for the IAQ sensor power
supply, it cannot have the secondary of the transformer grounded.
3. For field-installed remote minimum position POT, remove black wire jumper
between P and P1 and set control minimum position POT. to the minimum
position.
LA — Low Ambient Lockout Device
OAT — Outdoor-Air Temperature
POT— Potentiometer
Middle
Enthalpy
C Setting
RAT — Return-Air Temperature
Fig. 25 — EconoMi$er IV Wiring
—15—
Table 5 — Supply Air Sensor Temperature/Resistance
Values
2500
2000
1500
1000
500
TEMPERATURE (F)
RESISTANCE (ohms)
–58
–40
–22
–4
14
32
50
68
77
86
104
122
140
158
176
185
194
212
230
248
257
266
284
302
200,250
100,680
53,010
29,091
16,590
9,795
5,970
3,747
3,000
2,416
1,597
1,080
746
0
0.15
0.05
0.25
STATIC PRESSURE (in. wg)
Fig. 26 — Barometric Relief Flow Capacity
525
376
321
274
203
153
116
102
30
25
20
15
10
5
89
70
55
0
0.13 0.20 0.22 0.25 0.30 0.35 0.40 0.45 0.50
The temperature sensor looks like an eyelet terminal with
wires running to it. The sensor is located in the “crimp end”
and is sealed from moisture.
STATIC PRESSURE (in. wg)
Fig. 27 — Outdoor Air Damper Leakage
Outdoor Air Lockout Sensor
The Economi$er IV is equipped with an ambient tempera-
ture lockout switch located in the outdoor airstream which is
used to lock out the compressors below a 42 F ambient tem-
perature. See Fig. 19.
6000
5000
4000
3000
2000
1000
0
G. EconoMi$er IV Control Modes
Determine the EconoMi$er IV control mode before set up of the
control. Some modes of operation may require different sensors.
Refer to Table 6. The EconoMi$er IV is supplied from the fac-
tory with a supply air temperature sensor and an outdoor air
temperature sensor. This allows for operation of the
EconoMi$er IV with outdoor air dry bulb changeover control.
Additional accessories can be added to allow for different
types of changeover control and operation of the EconoMi$er
IV and unit.
0.05
0.10
0.15
0.20
0.25
0.30
0.35
STATIC PRESSURE (in. wg)
Fig. 28 — Return Air Pressure Drop
Table 6 — EconoMi$er IV Sensor Usage
ECONOMI$ER IV WITH OUTDOOR AIR
DRY BULB SENSOR
Accessories Required
APPLICATION
None. The outdoor air dry bulb sensor
is factory installed.
Outdoor Air Dry Bulb
Differential Dry Bulb
Single Enthalpy
CRTEMPSN002A00*
HH57AC078
HH57AC078
and
CRENTDIF004A00*
Differential Enthalpy
SUPPLY AIR
TEMPERATURE
SENSOR
MOUNTING
LOCATION
CO2 for DCV Control
using a Wall-Mounted
CO2 Sensor
CO2 for DCV Control
using a Duct-Mounted
CO2 Sensor
33ZCSENCO2
33ZCSENCO2†
and
CRCBDIOX005A00††
33ZCASPCO2**
SUPPLY AIR
TEMPERATURE
SENSOR
*CRENTDIF004A00 and CRTEMPSN002A00 accessories are used on
many different base units. As such, these kits may contain parts that will
not be needed for installation.
†33ZCSENCO2 is an accessory CO2 sensor.
**33ZCASPCO2 is an accessory aspirator box required for duct-mounted
applications.
††CRCBDIOX005A00 is an accessory that contains both 33ZCSENCO2
and 33ZCASPCO2 accessories.
Fig. 29 — Supply Air Sensor Location
—16—
Outdoor Dry Bulb Changeover
The standard controller is shipped from the factory configured
for outdoor dry bulb changeover control. The outdoor air and
supply air temperature sensors are included as standard. For
this control mode, the outdoor temperature is compared to an
adjustable set point selected on the control. If the outdoor-air
temperature is above the set point, the EconoMi$er IV will
adjust the outdoor-air dampers to minimum position. If the
outdoor-air temperature is below the set point, the position of
the outdoor-air dampers will be controlled to provide free cool-
ing using outdoor air. When in this mode, the LED next to the
free cooling set point potentiometer will be on. The changeover
temperature set point is controlled by the free cooling set point
potentiometer located on the control. See Fig. 30. The scale on
the potentiometer is A, B, C, and D. See Fig. 31 for the corre-
sponding temperature changeover values.
Differential Dry Bulb Control
For differential dry bulb control the standard outdoor dry
bulb sensor is used in conjunction with an additional acces-
sory dry bulb sensor (part number CRTEMPSN002A00). The
accessory sensor must be mounted in the return airstream.
See Fig. 32. Wiring is provided in the EconoMi$er IV wiring
harness. See Fig. 25.
Fig. 30 — EconoMi$er IV Controller Potentiometer
and LED Locations
19
LED ON
18
D
In this mode of operation, the outdoor-air temperature is
compared to the return-air temperature and the lower tem-
perature airstream is used for cooling. When using this mode
of changeover control, turn the enthalpy set point potentiom-
eter fully clockwise to the D setting. See Fig. 30.
17
LED ON
LED OFF
16
15
14
C
LED ON
LED OFF
B
13
12
Outdoor Enthalpy Changeover
LED ON
For enthalpy control, accessory enthalpy sensor (part num-
ber HH57AC078) is required. Replace the standard outdoor
dry bulb temperature sensor with the accessory enthalpy
sensor in the same mounting location. See Fig. 19. When the
outdoor air enthalpy rises above the outdoor enthalpy
changeover set point, the outdoor-air damper moves to its
minimum position. The outdoor enthalpy changeover set
point is set with the outdoor enthalpy set point potentiome-
ter on the EconoMi$er IV controller. The set points are A, B,
C, and D. See Fig. 33. The factory-installed 620-ohm jumper
must be in place across terminals SR and SR+ on the
EconoMi$er IV controller. See Fig. 19 and 34.
LED OFF
A
11
10
9
LED OFF
85 90
95
100
50
55 60
70 75
40 45
65
80
DEGREES FAHRENHEIT
Fig. 31 — Outdoor Air Temperature Changeover Set Points
ECONOMI$ER IV
CONTROLLER
Differential Enthalpy Control
ECONOMI$ER IV
For differential enthalpy control, the EconoMi$er IV control-
ler uses two enthalpy sensors (HH57AC078 and
CRENTDIF004A00), one in the outside air and one in the
return air duct. The EconoMi$er IV controller compares the
outdoor air enthalpy to the return air enthalpy to determine
EconoMi$er IV use. The controller selects the lower enthalpy
air (return or outdoor) for cooling. For example, when the
outdoor air has a lower enthalpy than the return air, the
EconoMi$er IV opens to bring in outdoor air for free cooling.
GROMMET
Replace the standard outside air dry bulb temperature sensor
with the accessory enthalpy sensor in the same mounting loca-
tion. See Fig. 19. Mount the return air enthalpy sensor in the
return air duct. See Fig. 32. Wiring is provided in the
EconoMi$er IV wiring harness. See Fig. 25. The outdoor
enthalpy changeover set point is set with the outdoor enthalpy
set point potentiometer on the EconoMi$er IV controller. When
using this mode of changeover control, turn the enthalpy set-
point potentiometer fully clockwise to the D setting.
RETURN AIR
SENSOR
RETURN DUCT
(FIELD-PROVIDED)
Fig. 32 — Return Air Temperature or
Enthalpy Sensor Mounting Location
—17—
Indoor Air Quality (IAQ) Sensor Input
AQ1 terminals of the controller. Adjust the DCV potentiome-
ters to correspond to the DCV voltage output of the indoor air
quality sensor at the user-determined set point. See Fig. 35.
The IAQ input can be used for demand control ventilation
control based on the level of CO2 measured in the space or
return air duct.
If a separate field-supplied transformer is used to power the
IAQ sensor, the sensor must not be grounded or the
EconoMi$er IV control board will be damaged.
Mount the accessory IAQ sensor according to manufacturer
specifications. The IAQ sensor should be wired to the AQ and
85
90
95 100 105 110
(29) (32) (35) (38) (41) (43)
CONTROL CONTROL POINT
CURVE
APPROX. °F (°C)
AT 50% RH
80
(27)
A
B
C
D
73 (23)
70 (21)
67 (19)
63 (17)
75
(24)
70
(21)
65
(18)
60
(16)
A
55
(13)
B
50
(10)
C
45
(7)
D
40
(4)
35
(2)
A
B
C
D
HIGH LIMIT
CURVE
35
40
45
50
55
60
65
70
75
80
85
90
95 100 105 110
(2)
(4) (7) (10) (13) (16) (18) (21) (24) (27) (29) (32) (35) (38) (41) (43)
APPROXIMATE DRY BULB TEMPERATURE— °F (°C)
Fig. 33 — Enthalpy Changeover Set Points
CO SENSOR MAX RANGE SETTING
2
TR1
EXH
Set
TR
N1
6000
5000
4000
3000
2000
1000
0
N
2V
10V
EXH
24
Vac
HOT
24 Vac
COM
P1
T1
P
T
Min
Pos
_
800 ppm
900 ppm
1000 ppm
1100 ppm
+
Open
DCV
Max
10V
1
2
5
2V
AQ1
AQ
SO+
SO
SR+
SR
DCV
DCV
Set
4
3
2V
10V
2
3
4
5
6
7
8
Free
Cool
EF1
EF
DAMPER VOLTAGE FOR MAX VENTILATION RATE
C
B
Fig. 35 — CO2 Sensor Maximum Range Setting
D
A
Fig. 34 — EconoMi$er IV Control
—18—
Exhaust Set Point Adjustment
To control the minimum damper position remotely, remove
the factory-installed jumper on the P and P1 terminals on
the EconoMi$er IV controller. Wire the field-supplied poten-
tiometer to the P and P1 terminals on the EconoMi$er IV
controller. See Fig. 34.
The exhaust set point will determine when the exhaust fan
runs based on damper position (if accessory power exhaust is
installed). The set point is modified with the Exhaust Fan
Set Point (EXH SET) potentiometer. See Fig. 30. The set
point represents the damper position above which the
exhaust fans will be turned on. When there is a call for
exhaust, the EconoMi$er IV controller provides a 45 ±
15 second delay before exhaust fan activation to allow the
dampers to open. This delay allows the damper to reach the
appropriate position to avoid unnecessary fan overload.
Damper Movement
Damper movement from full open to full closed (or vice
versa) takes 21/2 minutes.
Thermostats
The EconoMi$er IV control works with conventional thermo-
stats that have a Y1 (cool stage 1), Y2 (cool stage 2), W1
Minimum Position Control
(heat stage 1), W2 (heat stage 2), and
G
(fan). The
There is a minimum damper position potentiometer on the
EconoMi$er IV controller. See Fig. 30. The minimum damper
position maintains the minimum airflow into the building
during the occupied period.
EconoMi$er IV control does not support space temperature
sensors. Connections are made at the thermostat terminal
connection board located in the main control box.
Occupancy Control
When using demand ventilation, the minimum damper posi-
tion represents the minimum ventilation position for VOC
(volatile organic compound) ventilation requirements. The
maximum demand ventilation position is used for fully occu-
pied ventilation.
The factory default configuration for the EconoMi$er IV con-
trol is occupied mode. Occupied status is provided by the
black jumper from terminal TR to terminal N. When unoccu-
pied mode is desired, install a field-supplied timeclock func-
tion in place of the jumper between TR and N. See Fig. 25.
When the timeclock contacts are closed, the EconoMi$er IV
control will be in occupied mode. When the timeclock con-
tacts are open (removing the 24-v signal from terminal N),
the EconoMi$er IV will be in unoccupied mode.
When demand ventilation control is not being used, the min-
imum position potentiometer should be used to set the occu-
pied ventilation position. The maximum demand ventilation
position should be turned fully clockwise.
Adjust the minimum position potentiometer to allow the
minimum amount of outdoor air, as required by local codes,
to enter the building. Make minimum position adjustments
with at least 10 F temperature difference between the out-
door and return-air temperatures.
Demand Controlled Ventilation (DCV)
When using the EconoMi$er IV for demand controlled venti-
lation, there are some equipment selection criteria which
should be considered. When selecting the heat capacity and
cool capacity of the equipment, the maximum ventilation
rate must be evaluated for design conditions. The maximum
damper position must be calculated to provide the desired
fresh air.
To determine the minimum position setting, perform the
following procedure:
1. Calculate the appropriate mixed-air temperature
using the following formula:
Typically the maximum ventilation rate will be about 5 to
10% more than the typical cfm required per person, using
normal outside air design criteria.
OA
100
RA
100
(TO
x
) + (TR
x
) = TM
TO = Outdoor-Air Temperature
OA = Percent of Outdoor Air
TR = Return-Air Temperature
RA = Percent of Return Air
TM = Mixed-Air Temperature
A proportional anticipatory strategy should be taken with
the following conditions: a zone with a large area, varied
occupancy, and equipment that cannot exceed the required
ventilation rate at design conditions. Exceeding the required
ventilation rate means the equipment can condition air at a
maximum ventilation rate that is greater than the required
ventilation rate for maximum occupancy. A proportional-
anticipatory strategy will cause the fresh air supplied to
increase as the room CO2 level increases even though the
CO2 set point has not been reached. By the time the CO2
level reaches the set point, the damper will be at maximum
ventilation and should maintain the set point.
As an example, if local codes require 10% outdoor air
during occupied conditions, outdoor-air temperature
is 60 F, and return-air temperature is 75 F.
(60 x .10) + (75 x .90) = 73.5 F
2. Disconnect the supply air sensor from terminals T
and T1.
3. Ensure that the factory-installed jumper is in place
across terminals P and P1. If remote damper posi-
tioning is being used, make sure that the terminals
are wired according to Fig. 25 and that the minimum
position potentiometer is turned fully clockwise.
In order to have the CO2 sensor control the economizer
damper in this manner, first determine the damper voltage
output for minimum or base ventilation. Base ventilation is
the ventilation required to remove contaminants during
unoccupied periods. The following equation may be used to
determine the percent of outside-air entering the building for
a given damper position. For best results there should be at
4. Connect 24 vac across terminals TR and TR1.
5. Carefully adjust the minimum position potentiometer
until the measured mixed-air temperature matches
the calculated value.
least
a
10 degree difference in outside and return-air
temperatures.
OA
100
RA
100
6. Reconnect the supply-air sensor to terminals T and T1.
Remote control of the EconoMi$er IV damper is desirable
(TO
x
) + (TR
x
) = TM
TO = Outdoor-Air Temperature
OA = Percent of Outdoor Air
TR = Return-Air Temperature
RA = Percent of Return Air
TM = Mixed-Air Temperature
when requiring additional temporary ventilation. If
a
field-supplied remote potentiometer (Honeywell part num-
ber S963B1128) is wired to the EconoMi$er IV controller, the
minimum position of the damper can be controlled from a
remote location.
—19—
Once base ventilation has been determined, set the mini-
mum damper position potentiometer to the correct position.
3. Use the Up/Down button to select the preset number.
See Table 7.
The same equation can be used to determine the occupied or
maximum ventilation rate to the building. For example, an
output of 3.6 volts to the actuator provides a base ventilation
rate of 5% and an output of 6.7 volts provides the maximum
ventilation rate of 20% (or base plus 15 cfm per person). Use
Fig. 35 to determine the maximum setting of the CO2 sensor.
For example, a 1100 ppm set point relates to a 15 cfm per
person design. Use the 1100 ppm curve on Fig. 35 to find the
point when the CO2 sensor output will be 6.7 volts. Line up
the point on the graph with the left side of the chart to deter-
mine that the range configuration for the CO2 sensor should
be 1800 ppm. The EconoMi$er IV controller will output the
6.7 volts from the CO2 sensor to the actuator when the CO2
concentration in the space is at 1100 ppm. The DCV set point
may be left at 2 volts since the CO2 sensor voltage will be
ignored by the EconoMi$er IV controller until it rises above
the 3.6 volt setting of the minimum position potentiometer.
4. Press Enter to lock in the selection.
5. Press Mode to exit and resume normal operation.
The custom settings of the CO2 sensor can be changed any-
time after the sensor is energized. Follow the steps below to
change the non-standard settings:
1. Press Clear and Mode buttons. Hold at least 5 sec-
onds until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to toggle to the NONSTD
menu and press Enter.
4. Use the Up/Down button to toggle through each of
the nine variables, starting with Altitude, until the
desired setting is reached.
5. Press Mode to move through the variables.
6. Press Enter to lock in the selection, then press Mode
to continue to the next variable.
Once the fully occupied damper position has been deter-
mined, set the maximum damper demand control ventilation
potentiometer to this position. Do not set to the maximum
position as this can result in over-ventilation to the space
and potential high-humidity levels.
Dehumidification of Fresh Air with DCV Control
Information from ASHRAE indicates that the largest humid-
ity load on any zone is the fresh air introduced. For some
applications, an energy recovery unit is added to reduce the
moisture content of the fresh air being brought into the
building when the enthalpy is high. In most cases, the nor-
mal heating and cooling processes are more than adequate to
remove the humidity loads for most commercial applications.
CO2 Sensor Configuration
The CO2 sensor has preset standard voltage settings that
can be selected anytime after the sensor is powered up. See
Table 7.
Use setting 1 or 2 for Bryant equipment. See Table 7.
If normal rooftop heating and cooling operation is not ade-
quate for the outdoor humidity level, an energy recovery unit
and/or a dehumidification option should be considered.
1. Press Clear and Mode buttons. Hold at least 5 sec-
onds until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
Table 7 — CO2 Sensor Standard Settings
VENTILATION
RATE
(cfm/Person)
CO2
CONTROL RANGE
(ppm)
OPTIONAL
RELAY SETPOINT
(ppm)
RELAY
HYSTERESIS
(ppm)
ANALOG
OUTPUT
SETTING
EQUIPMENT
OUTPUT
0-10V
1
2
3
4
5
6
7
8
9
Proportional
Proportional
Exponential
Proportional
Proportional
Exponential
Exponential
Proportional
Proportional
Any
Any
Any
15
0-2000
0-2000
0-2000
0-1100
0- 900
0-1100
0- 900
0-9999
0-2000
1000
1000
1100
1100
900
50
50
4-20 mA
Interface w/Standard
2-10V
7-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
Building Control System
50
50
20
50
Economizer
15
1100
900
50
20
50
Health & Safety
—
5000
700
500
50
Parking/Air Intakes/
Loading Docks
—
LEGEND
ppm — Parts Per Million
—20—
VII. STEP 7 — ADJUST EVAPORATOR-FAN SPEED
2. Slide fan pulley along fan shaft.
3. Make angular alignment by loosening motor from
mounting plate.
Adjust evaporator-fan rpm to meet jobsite conditions.
For units with electric heat, required minimum cfm is 2250
for 551B090 and 102 and 3000 for 551B120 and 150. See
Table 8 for exceptions.
To adjust belt tension:
1. Loosen fan motor mounting nuts.
2. Size 090 — Slide motor mounting plate away from fan
scroll for proper belt tension (1/2-in. deflection with
8 to 10 lb of force) and tighten mounting nuts (see
Fig. 37).
Table 8 — Minimum Required Airflow Exceptions
UNIT
REQUIRED
MINIMUM
CFM
UNIT
551B
UNIT
HEATER
kW
CONFIG-
URATION
VOLTAGE
Sizes 102-150 — Slide motor mounting plate down-
ward to tighten belt tension. Secure motor mounting
plate nuts. See Fig. 38. Use 1/2-in. deflection with 10 lb of
force.
208/230
208/230
42.4
50.0
Horizontal
Horizontal
Horizontal
or Vertical
3200
3200
120,150
090-150
460
575
50.0
3200
17.0
34.0
2800
2350
Horizontal
or Vertical
3. Adjust bolt and nut on mounting plate to secure
motor in fixed position.
Tables 9 and 10 show fan rpm at motor pulley settings for
standard and high-static motors. Tables 11 and 12 show
evaporator-fan motor data. See Tables 13 and 14 and Fig. 36
for accessory and option static pressure drops. Refer to
Tables 15-28 to determine fan speed settings.
Fan motor pulleys are factory set for speed shown in Table 1.
To change fan speeds:
1. Shut off unit power supply and install lockout tag.
2. Loosen belt by loosening fan motor mounting nuts.
See Fig. 37 and 38.
MOTOR MOUNTING
PLATE NUTS
3. Loosen movable pulley flange setscrew (see Fig. 39).
4. Screw movable flange toward fixed flange to increase
rpm or away from fixed flange to decrease rpm.
Increasing fan rpm increases load on motor. Do not
exceed maximum speed specified in Table 1.
5. Set movable flange at nearest keyway of pulley hub
and tighten setscrew. (See Table 1 for speed change
for each full turn of pulley flange.)
Fig. 37 — Typical Belt-Drive Motor Mounting for
Size 090
To align fan and motor pulleys:
1. Loosen fan pulley setscrews.
0.35
0.3
0.25
0.2
0.15
0.1
7.5 ton
0.05
0
8.5, 10 & 12.5 ton
4000
1000
2000
3000
5000
6000
0
CFM
Fig. 36 — Perfect Humidity™ Dehumidification System Static Pressure Drop (in. wg)
—21—
Fig. 38 — Typical Belt-Drive Motor Mounting for
Sizes 102-150
Fig. 39 — Indoor-Fan Pulley Adjustment
Table 9 — Fan Rpm at Motor Pulley Setting*; Standard Motor/Drive
MOTOR PULLEY TURNS OPEN
UNIT
551B
1
0
/
1
11/2
2
21/2
3
31/2
910
925
962
4
41/2
865
880
912
5
51/2
—
—
6
—
—
830
2
090,102
120
150
1085
1080
1130
1060
1060
1112
1035
1035
1087
1010
1015
1062
985
990
1037
960
970
1212
935
950
987
890
905
937
840
860
887
862
*Approximate fan rpm shown.
Table 10 — Fan Rpm at Motor Pulley Setting*; High-Static Motor/Drive
MOTOR PULLEY TURNS OPEN
UNIT
11/2
2
21/2
3
31/2
915
915
962
4
41/2
878
878
912
5
51/2
—
—
6
—
—
830
551B
1
0
/
1
2
090
102
120
1080
1080
1130
1025
1025
1112
1007
1007
1087
988
988
1062
970
970
1037
952
952
1212
933
933
987
897
897
937
860
860
887
862
*Approximate fan rpm shown.
Table 11 — Evaporator-Fan Motor Data — Standard Motor
UNIT
551B
UNIT
MAXIMUM
MAXIMUM
MAXIMUM
UNIT VOLTAGE
PHASE
CONTINUOUS BHP*
OPERATING WATTS*
AMP DRAW
8.6
208/230
460
575
208/230
460
575
090,102
120
Three
Three
Three
2.90
3.70
5.25
2615
3775
4400
3.9
3.9
12.2
5.5
5.5
208/230
460
17.3
8.5
150
575
8.5
LEGEND
BHP — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range
of the motors can be utilized with confidence. Using your fan motors up to the ratings shown in this
table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
—22—
Table 12 — Evaporator-Fan Motor Data — High-Static Motors
UNIT
5551B
UNIT
PHASE
MAXIMUM
CONTINUOUS BHP*
MAXIMUM
OPERATING WATTS*
MAXIMUM
AMP DRAW
UNIT VOLTAGE
208/230
460
575
208/230
460
12.2
5.5
5.5
17.3
8.5
090,102
120
Three
Three
4.20
5.25
3775
4400
575
8.5
LEGEND
BHP — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range
of the motors can be utilized with confidence. Using your fan motors up to the ratings shown in this
table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
Table 13 — Accessory/FIOP EconoMi$er IV Static Pressure* (in. wg)
CFM
COMPONENT
2250
0.06
—
2500
0.075
0.1
2750
0.09
0.125
3000
0.115
0.15
3250 3500 3750
4000
0.195
0.275
4250 4500
4750
5000
5250 6250
Vertical EconoMi$er IV
Horizontal EconoMi$er IV
0.13
0.18
0.15
0.21
0.17
0.25
0.22
0.3
0.25
0.34
0.285 0.325
0.36
—
—
—
0.388
—
LEGEND
FIOP — Factory-Installed Option
*The static pressure must be added to external static pressure. The sum and the evaporator entering-
air cfm should be used in conjunction with the Fan Performance tables to determine indoor blower
rpm and watts.
Table 14 — Accessory/FIOP Electric Heaters Static Pressure (in. wg)
CFM
COMPONENT
2200
0.02
0.03
2500
0.03
0.05
3000
0.05
0.07
3500
0.065
0.09
4000
0.08
0.12
4500
0.10
0.14
5000
0.12
0.16
5500
0.14
0.19
6000
0.155
0.21
1 Heater Module
2 Heater Modules
LEGEND
FIOP — Factory-Installed Option
*The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should
be used in conjunction with the Fan Performance tables to determine indoor blower rpm and watts.
GENERAL FAN PERFORMANCE NOTES
1. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using
fan motors up to the ratings shown will not result in nuisance trip-
ping or premature motor failure. Unit warranty will not be affected.
For additional information on motor performance refer to Evapora-
tor-Fan Motor Data, Tables 11 and 12.
2. Values include losses for filters, unit casing, and wet coils. See
Tables 13 and 14 and Fig. 36 for accessory/FIOP static pressure
information.
3. Use of a field-supplied motor may affect wire sizing. Contact
Bryant representative to verify.
4. Interpolation is permissible. Do not extrapolate.
—23—
Table 15 — Fan Performance 551B090 — Vertical Discharge Units; Standard Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
CFM
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
2250
2300
2400
2500
2550
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750
511
519
534
550
558
565
581
597
613
630
646
663
679
696
713
729
746
755
0.53
0.56
0.61
0.67
0.71
0.74
0.81
0.89
0.97
1.06
1.15
1.25
1.35
1.46
1.58
1.70
1.83
1.89
492
518
591
597
611
624
631
638
652
667
681
696
711
726
741
756
772
787
803
811
0.73
0.76
0.82
0.89
0.93
0.97
1.04
1.13
1.22
1.31
1.41
1.51
1.62
1.74
1.86
1.99
2.13
2.20
680
709
660
666
678
690
697
703
716
729
742
756
770
784
798
812
827
841
856
864
0.95
0.98
1.05
1.13
1.17
1.21
1.29
1.38
1.48
1.58
1.68
1.79
1.91
2.03
2.16
2.30
2.44
2.52
885
916
722
727
739
750
756
762
774
786
799
811
824
837
851
864
878
892
906
913
1.19
1.22
1.30
1.38
1.42
1.46
1.55
1.65
1.75
1.86
1.97
2.09
2.21
2.34
2.48
2.62
2.77
2.84
1106
1140
1210
1285
1324
1365
1449
1538
1632
1731
1835
1944
2060
2181
2308
2441
2580
2653
779
784
795
805
811
816
828
839
851
863
875
888
900
913
926
—
1.44
1.48
1.56
1.64
1.69
1.73
1.83
1.93
2.04
2.15
2.27
2.39
2.52
2.66
2.80
—
1342
1378
1453
1533
1574
1617
1707
1801
1900
2004
2114
2229
2351
2478
2610
—
571
768
982
629
832
1051
1088
1125
1204
1287
1376
1469
1568
1672
1781
1896
2017
2144
2277
2346
660
866
691
901
758
974
829
1051
1133
1220
1313
1411
1514
1623
1737
1857
1985
2051
905
985
1071
1162
1259
1361
1469
1583
1703
1766
—
—
—
—
—
—
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
CFM
1.2
Bhp
1.4
Bhp
1.8
Bhp
2.0
Bhp
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Watts
Rpm
Watts
2250
2300
2400
2500
2550
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750
832
837
847
857
862
867
878
889
900
912
923
935
947
—
1.71
1.75
1.83
1.92
1.97
2.02
2.12
2.23
2.34
2.46
2.58
2.71
2.84
—
1592
1630
1710
1794
1838
1884
1978
2077
2181
2290
2406
2526
2652
—
882
886
896
905
910
915
926
936
947
958
969
—
1.99
2.03
2.12
2.22
2.27
2.32
2.42
2.54
2.65
2.78
2.90
—
1855
1896
1980
2069
2114
2162
2261
2365
2474
2588
2708
—
928
933
942
951
956
961
971
981
—
2.29
2.33
2.43
2.52
2.58
2.63
2.74
2.86
—
2131
2174
2262
2355
2403
2453
2556
2664
—
973
977
986
995
999
—
2.59
2.64
2.74
2.84
2.90
—
2420
2463
2556
2653
2704
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
Bhp
— Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 840 to 1085 rpm. All other rpms require field-
supplied drive.
3. See page 23 for general fan performance notes.
—24—
Table 16 — Fan Performance 551B090 — Vertical Discharge Units; High-Static Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
CFM
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
2250
2300
2400
2500
2550
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750
511
519
534
550
558
565
581
597
613
630
646
663
679
696
713
729
746
755
0.53
0.56
0.61
0.67
0.71
0.74
0.81
0.89
0.97
1.06
1.15
1.25
1.35
1.46
1.58
1.70
1.83
1.89
492
518
591
597
611
624
631
638
652
667
681
696
711
726
741
756
772
787
803
811
0.73
0.76
0.82
0.89
0.93
0.97
1.04
1.13
1.22
1.31
1.41
1.51
1.62
1.74
1.86
1.99
2.13
2.20
680
709
660
666
678
690
697
703
716
729
742
756
770
784
798
812
827
841
856
864
0.95
0.98
1.05
1.13
1.17
1.21
1.29
1.38
1.48
1.58
1.68
1.79
1.91
2.03
2.16
2.30
2.44
2.52
885
916
722
727
739
750
756
762
774
786
799
811
824
837
851
864
878
892
906
913
1.19
1.22
1.30
1.38
1.42
1.46
1.55
1.65
1.75
1.86
1.97
2.09
2.21
2.34
2.48
2.62
2.77
2.84
1106
1140
1210
1285
1324
1365
1449
1538
1632
1731
1835
1944
2060
2181
2308
2441
2580
2653
779
784
795
805
811
816
828
839
851
863
875
888
900
913
926
939
953
959
1.44
1.48
1.56
1.64
1.69
1.73
1.83
1.93
2.04
2.15
2.27
2.39
2.52
2.66
2.80
2.95
3.10
3.18
1342
1378
1453
1533
1574
1617
1707
1801
1900
2004
2114
2229
2351
2478
2610
2749
2894
2969
571
768
982
629
832
1051
1088
1125
1204
1287
1376
1469
1568
1672
1781
1896
2017
2144
2277
2346
660
866
691
901
758
974
829
1051
1133
1220
1313
1411
1514
1623
1737
1857
1985
2051
905
985
1071
1162
1259
1361
1469
1583
1703
1766
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
CFM
1.2
Bhp
1.4
Bhp
1.8
Bhp
2.0
Bhp
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Watts
Rpm
Watts
2250
2300
2400
2500
2550
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750
832
837
847
857
862
867
878
889
900
912
923
935
947
959
972
984
997
1004
1.71
1.75
1.83
1.92
1.97
2.02
2.12
2.23
2.34
2.46
2.58
2.71
2.84
2.99
3.13
3.29
3.45
3.54
1592
1630
1710
1794
1838
1884
1978
2077
2181
2290
2406
2526
2652
2785
2923
3068
3218
3296
882
886
1.99
2.03
2.12
2.22
2.27
2.32
2.42
2.54
2.65
2.78
2.90
3.04
3.18
3.33
3.48
3.64
3.81
3.90
1855
1896
1980
2069
2114
2162
2261
2365
2474
2588
2708
2834
2966
3103
3246
3396
3553
3633
928
933
2.29
2.33
2.43
2.52
2.58
2.63
2.74
2.86
2.98
3.11
3.24
3.38
3.53
3.68
3.84
4.01
4.18
—
2131
2174
2262
2355
2403
2453
2556
2664
2778
2897
3022
3152
3289
3432
3581
3736
3897
—
973
977
986
995
999
1004
1013
1023
1033
1043
1053
1064
1075
1086
—
2.59
2.64
2.74
2.84
2.90
2.95
3.07
3.19
3.32
3.45
3.59
3.73
3.89
4.04
—
2420
2463
2556
2653
2704
2755
2862
2975
3094
3217
3347
3482
3623
3771
—
1015
1020
1028
1037
1041
1045
1055
1064
1073
1083
1093
1103
—
2.92
2.97
3.07
3.18
3.23
3.29
3.41
3.54
3.67
3.80
3.95
4.10
—
2720
2766
2861
2962
3014
3068
3180
3297
3419
3547
3682
3821
—
896
942
905
951
910
956
915
961
926
971
936
981
947
991
958
1001
1012
1023
1034
1045
1057
1068
1080
—
969
980
992
1003
1015
1027
1040
1046
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 4.20.
Bhp
— Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field-
supplied drive.
3. See page 23 for general fan performance notes.
—25—
Table 17 — Fan Performance 551B102 — Vertical Discharge Units; Standard Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
CFM
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
489
502
515
529
542
556
569
583
597
611
625
639
654
668
683
697
712
726
741
0.41
0.45
0.50
0.55
0.59
0.65
0.70
0.76
0.83
0.89
0.96
1.04
1.11
1.20
1.28
1.37
1.47
1.57
1.67
386
424
564
576
587
599
611
623
636
648
661
674
687
700
713
726
739
753
766
780
794
0.54
0.59
0.64
0.69
0.74
0.80
0.86
0.93
1.00
1.07
1.14
1.22
1.31
1.39
1.48
1.58
1.68
1.79
1.89
506
548
629
640
650
661
672
684
695
707
718
730
742
754
767
779
792
804
817
830
843
0.67
0.72
0.77
0.83
0.89
0.95
1.02
1.09
1.17
1.24
1.32
1.41
1.50
1.59
1.69
1.79
1.89
2.00
2.12
625
672
688
697
707
718
728
738
749
760
771
782
794
805
817
828
840
852
864
876
889
0.80
0.85
0.91
0.98
1.04
1.11
1.18
1.26
1.33
1.42
1.50
1.59
1.69
1.78
1.88
1.99
2.10
2.22
2.34
745
797
741
750
760
769
779
789
799
809
820
831
841
852
863
874
886
897
909
920
932
0.93
0.99
1.05
1.12
1.19
1.26
1.34
1.42
1.50
1.59
1.68
1.78
1.87
1.98
2.08
2.20
2.31
2.43
2.56
866
923
465
594
723
852
982
508
642
776
910
970
1044
1109
1177
1249
1323
1401
1483
1567
1656
1748
1844
1943
2048
2155
2268
2384
555
693
832
604
748
891
1034
1100
1170
1244
1320
1400
1484
1571
1662
1758
1857
1960
2067
2179
656
805
953
712
865
1018
1086
1158
1233
1312
1395
1481
1572
1666
1764
1866
1973
770
929
832
996
898
1066
1140
1218
1299
1385
1474
1567
1665
1767
967
1040
1116
1197
1281
1370
1462
1559
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
CFM
1.2
Bhp
1.4
Bhp
1.8
Bhp
2.0
Bhp
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Watts
Rpm
Watts
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
791
799
808
817
827
836
846
856
866
876
886
897
907
918
929
940
951
962
973
1.06
1.12
1.19
1.26
1.34
1.42
1.50
1.58
1.67
1.76
1.86
1.96
2.06
2.17
2.28
2.40
2.52
2.65
2.78
988
1049
1113
1179
1249
1322
1398
1477
1559
1645
1734
1827
1924
2025
2130
2238
2351
2468
2589
837
845
854
863
872
881
890
899
909
919
929
939
949
959
970
980
991
1002
—
1.19
1.26
1.34
1.41
1.49
1.57
1.66
1.75
1.84
1.94
2.04
2.14
2.25
2.37
2.48
2.61
2.73
2.86
—
1112
1177
1245
1316
1390
1467
1547
1631
1718
1808
1902
2000
2101
2207
2316
2429
2547
2668
—
881
889
897
905
914
923
932
941
950
960
969
979
989
999
1009
1019
—
1.33
1.40
1.48
1.56
1.64
1.73
1.82
1.92
2.01
2.12
2.22
2.33
2.44
2.56
2.68
2.81
—
1236
1306
1378
1454
1532
1613
1698
1786
1878
1972
2071
2173
2279
2389
2502
2620
—
922
930
938
946
954
963
972
980
989
998
1008
1017
1027
1036
1046
—
1.46
1.54
1.62
1.71
1.80
1.89
1.98
2.08
2.19
2.29
2.40
2.52
2.63
2.76
2.88
—
1362
1436
1513
1592
1675
1761
1849
1942
2038
2137
2240
2347
2457
2571
2690
—
962
969
977
985
993
1001
1010
1018
1027
1036
1045
1054
1063
—
1.60
1.68
1.77
1.86
1.95
2.05
2.15
2.25
2.36
2.47
2.58
2.70
2.83
—
1490
1568
1648
1732
1819
1909
2002
2099
2199
2303
2410
2521
2636
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
Bhp
— Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 840 to 1085 rpm. All other rpms require field-
supplied drive.
3. See page 23 for general fan performance notes.
—26—
Table 18 — Fan Performance 551B102 — Vertical Discharge Units; High-Static Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
CFM
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
489
502
515
529
542
556
569
583
597
611
625
639
654
668
683
697
712
726
741
0.41
0.45
0.50
0.55
0.59
0.65
0.70
0.76
0.83
0.89
0.96
1.04
1.11
1.20
1.28
1.37
1.47
1.57
1.67
386
424
564
576
587
599
611
623
636
648
661
674
687
700
713
726
739
753
766
780
794
0.54
0.59
0.64
0.69
0.74
0.80
0.86
0.93
1.00
1.07
1.14
1.22
1.31
1.39
1.48
1.58
1.68
1.79
1.89
506
548
629
640
650
661
672
684
695
707
718
730
742
754
767
779
792
804
817
830
843
0.67
0.72
0.77
0.83
0.89
0.95
1.02
1.09
1.17
1.24
1.32
1.41
1.50
1.59
1.69
1.79
1.89
2.00
2.12
625
672
688
697
707
718
728
738
749
760
771
782
794
805
817
828
840
852
864
876
889
0.80
0.85
0.91
0.98
1.04
1.11
1.18
1.26
1.33
1.42
1.50
1.59
1.69
1.78
1.88
1.99
2.10
2.22
2.34
745
797
741
750
760
769
779
789
799
809
820
831
841
852
863
874
886
897
909
920
932
0.93
0.99
1.05
1.12
1.19
1.26
1.34
1.42
1.50
1.59
1.68
1.78
1.87
1.98
2.08
2.20
2.31
2.43
2.56
866
923
465
594
723
852
982
508
642
776
910
970
1044
1109
1177
1249
1323
1401
1483
1567
1656
1748
1844
1943
2048
2155
2268
2384
555
693
832
604
748
891
1034
1100
1170
1244
1320
1400
1484
1571
1662
1758
1857
1960
2067
2179
656
805
953
712
865
1018
1086
1158
1233
1312
1395
1481
1572
1666
1764
1866
1973
770
929
832
996
898
1066
1140
1218
1299
1385
1474
1567
1665
1767
967
1040
1116
1197
1281
1370
1462
1559
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
CFM
1.2
Bhp
1.4
Bhp
1.8
Bhp
2.0
Bhp
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Watts
Rpm
Watts
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
791
799
808
817
827
836
846
856
866
876
886
897
907
918
929
940
951
962
973
1.06
1.12
1.19
1.26
1.34
1.42
1.50
1.58
1.67
1.76
1.86
1.96
2.06
2.17
2.28
2.40
2.52
2.65
2.78
988
1049
1113
1179
1249
1322
1398
1477
1559
1645
1734
1827
1924
2025
2130
2238
2351
2468
2589
837
845
854
863
872
881
890
899
909
919
929
939
949
959
970
980
991
1002
1013
1.19
1.26
1.34
1.41
1.49
1.57
1.66
1.75
1.84
1.94
2.04
2.14
2.25
2.37
2.48
2.61
2.73
2.86
3.00
1112
1177
1245
1316
1390
1467
1547
1631
1718
1808
1902
2000
2101
2207
2316
2429
2547
2668
2794
881
889
1.33
1.40
1.48
1.56
1.64
1.73
1.82
1.92
2.01
2.12
2.22
2.33
2.44
2.56
2.68
2.81
2.94
3.08
3.22
1236
1306
1378
1454
1532
1613
1698
1786
1878
1972
2071
2173
2279
2389
2502
2620
2743
2869
2999
922
930
1.46
1.54
1.62
1.71
1.80
1.89
1.98
2.08
2.19
2.29
2.40
2.52
2.63
2.76
2.88
3.02
3.15
3.29
3.44
1362
1436
1513
1592
1675
1761
1849
1942
2038
2137
2240
2347
2457
2571
2690
2812
2939
3070
3205
962
969
1.60
1.68
1.77
1.86
1.95
2.05
2.15
2.25
2.36
2.47
2.58
2.70
2.83
2.95
3.09
3.22
3.36
3.51
3.66
1490
1568
1648
1732
1819
1909
2002
2099
2199
2303
2410
2521
2636
2755
2877
3004
3136
3271
3411
897
938
977
905
946
985
993
914
954
923
963
1001
1010
1018
1027
1036
1045
1054
1063
1073
1082
1092
1102
1112
1122
932
972
941
980
950
989
960
998
969
1008
1017
1027
1036
1046
1056
1066
1076
1087
979
989
999
1009
1019
1029
1040
1050
LEGEND
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 4.20.
Bhp
— Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field-
supplied drive.
3. See page 23 for general fan performance notes.
—27—
Table 19 — Fan Performance 551B120 — Vertical Discharge Units; Standard Motor (Belt Drive*
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
CFM
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
556
569
583
597
611
625
639
654
668
683
697
712
726
741
755
770
785
800
815
829
844
0.65
0.70
0.76
0.83
0.89
0.96
1.04
1.11
1.20
1.28
1.37
1.47
1.57
1.67
1.78
1.89
2.01
2.14
2.26
2.40
2.54
604
656
623
636
648
661
674
687
700
713
726
739
753
766
780
794
807
821
835
849
863
877
891
0.80
0.86
0.93
1.00
1.07
1.14
1.22
1.31
1.39
1.48
1.58
1.68
1.79
1.89
2.01
2.13
2.25
2.38
2.51
2.65
2.80
748
805
684
695
707
718
730
742
754
767
779
792
804
817
830
843
856
869
882
895
909
922
936
0.95
1.02
1.09
1.17
1.24
1.32
1.41
1.50
1.59
1.69
1.79
1.89
2.00
2.12
2.23
2.36
2.49
2.62
2.76
2.91
3.06
891
953
738
749
760
771
782
794
805
817
828
840
852
864
876
889
901
914
926
939
952
965
978
1.11
1.18
1.26
1.33
1.42
1.50
1.59
1.69
1.78
1.88
1.99
2.10
2.22
2.34
2.46
2.59
2.72
2.86
3.01
3.16
3.31
1034
1100
1170
1244
1320
1400
1484
1571
1662
1758
1857
1960
2067
2179
2295
2415
2541
2670
2805
2944
3089
789
799
809
820
831
841
852
863
874
886
897
909
920
932
944
956
968
980
993
1005
1018
1.26
1.34
1.42
1.50
1.59
1.68
1.78
1.87
1.98
2.08
2.20
2.31
2.43
2.56
2.69
2.82
2.96
3.10
3.25
3.41
3.57
1177
1249
1323
1401
1483
1567
1656
1748
1844
1943
2048
2155
2268
2384
2505
2630
2760
2895
3034
3178
3328
712
865
1018
1086
1158
1233
1312
1395
1481
1572
1666
1764
1866
1973
2084
2200
2320
2445
2575
2709
2849
770
929
996
832
898
1066
1140
1218
1299
1385
1474
1567
1665
1767
1873
1984
2099
2219
2344
2473
2608
967
1040
1116
1197
1281
1370
1462
1559
1660
1766
1876
1991
2111
2235
2365
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
CFM
1.2
Bhp
1.4
Bhp
1.8
Bhp
2.0
Bhp
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Watts
Rpm
Watts
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
836
846
856
866
876
886
897
907
918
929
940
951
962
973
985
996
1008
1020
1032
1044
—
1.42
1.50
1.58
1.67
1.76
1.86
1.96
2.06
2.17
2.28
2.40
2.52
2.65
2.78
2.91
3.05
3.20
3.34
3.50
3.66
—
1322
1398
1477
1559
1645
1734
1827
1924
2025
2130
2238
2351
2468
2589
2715
2845
2979
3119
3263
3413
—
881
890
899
909
919
929
939
949
959
970
980
991
1002
1013
1024
1035
1046
1058
—
1.57
1.66
1.75
1.84
1.94
2.04
2.14
2.25
2.37
2.48
2.61
2.73
2.86
3.00
3.14
3.28
3.43
3.58
—
1467
1547
1631
1718
1808
1902
2000
2101
2207
2316
2429
2547
2668
2794
2924
3059
3199
3343
—
923
932
941
950
960
969
979
989
999
1009
1019
1029
1040
1050
1061
1072
1083
—
1.73
1.82
1.92
2.01
2.12
2.22
2.33
2.44
2.56
2.68
2.81
2.94
3.08
3.22
3.36
3.51
3.67
—
1613
1698
1786
1878
1972
2071
2173
2279
2389
2502
2620
2743
2869
2999
3134
3274
3418
—
963
972
980
989
998
1008
1017
1027
1036
1046
1056
1066
1076
1087
1097
—
1.89
1.98
2.08
2.19
2.29
2.40
2.52
2.63
2.76
2.88
3.02
3.15
3.29
3.44
3.59
—
1761
1849
1942
2038
2137
2240
2347
2457
2571
2690
2812
2939
3070
3205
3345
—
1001
1010
1018
1027
1036
1045
1054
1063
1073
1082
1092
1102
1112
1122
—
2.05
2.15
2.25
2.36
2.47
2.58
2.70
2.83
2.95
3.09
3.22
3.36
3.51
3.66
—
1909
2002
2099
2199
2303
2410
2521
2636
2755
2877
3004
3136
3271
3411
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 3.70.
Bhp
— Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field-
supplied drive.
3. See page 23 for general fan performance notes.
—28—
Table 20 — Fan Performance 551B120 — Vertical Discharge Units; High-Static Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
CFM
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
556
569
583
597
611
625
639
654
668
683
697
712
726
741
755
770
785
800
815
829
844
0.65
0.70
0.76
0.83
0.89
0.96
1.04
1.11
1.20
1.28
1.37
1.47
1.57
1.67
1.78
1.89
2.01
2.14
2.26
2.40
2.54
604
656
623
636
648
661
674
687
700
713
726
739
753
766
780
794
807
821
835
849
863
877
891
0.80
0.86
0.93
1.00
1.07
1.14
1.22
1.31
1.39
1.48
1.58
1.68
1.79
1.89
2.01
2.13
2.25
2.38
2.51
2.65
2.80
748
805
684
695
707
718
730
742
754
767
779
792
804
817
830
843
856
869
882
895
909
922
936
0.95
1.02
1.09
1.17
1.24
1.32
1.41
1.50
1.59
1.69
1.79
1.89
2.00
2.12
2.23
2.36
2.49
2.62
2.76
2.91
3.06
891
953
738
749
760
771
782
794
805
817
828
840
852
864
876
889
901
914
926
939
952
965
978
1.11
1.18
1.26
1.33
1.42
1.50
1.59
1.69
1.78
1.88
1.99
2.10
2.22
2.34
2.46
2.59
2.72
2.86
3.01
3.16
3.31
1034
1100
1170
1244
1320
1400
1484
1571
1662
1758
1857
1960
2067
2179
2295
2415
2541
2670
2805
2944
3089
789
799
809
820
831
841
852
863
874
886
897
909
920
932
944
956
968
980
993
1005
1018
1.26
1.34
1.42
1.50
1.59
1.68
1.78
1.87
1.98
2.08
2.20
2.31
2.43
2.56
2.69
2.82
2.96
3.10
3.25
3.41
3.57
1177
1249
1323
1401
1483
1567
1656
1748
1844
1943
2048
2155
2268
2384
2505
2630
2760
2895
3034
3178
3328
712
865
1018
1086
1158
1233
1312
1395
1481
1572
1666
1764
1866
1973
2084
2200
2320
2445
2575
2709
2849
770
929
996
832
898
1066
1140
1218
1299
1385
1474
1567
1665
1767
1873
1984
2099
2219
2344
2473
2608
967
1040
1116
1197
1281
1370
1462
1559
1660
1766
1876
1991
2111
2235
2365
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
CFM
1.2
Bhp
1.4
Bhp
1.8
Bhp
2.0
Bhp
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Watts
Rpm
Watts
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
836
846
856
866
876
886
897
907
918
929
940
951
962
973
985
996
1008
1020
1032
1044
1056
1.42
1.50
1.58
1.67
1.76
1.86
1.96
2.06
2.17
2.28
2.40
2.52
2.65
2.78
2.91
3.05
3.20
3.34
3.50
3.66
3.82
1322
1398
1477
1559
1645
1734
1827
1924
2025
2130
2238
2351
2468
2589
2715
2845
2979
3119
3263
3413
3566
881
890
1.57
1.66
1.75
1.84
1.94
2.04
2.14
2.25
2.37
2.48
2.61
2.73
2.86
3.00
3.14
3.28
3.43
3.58
3.74
3.91
4.08
1467
1547
1631
1718
1808
1902
2000
2101
2207
2316
2429
2547
2668
2794
2924
3059
3199
3343
3492
3646
3805
923
932
1.73
1.82
1.92
2.01
2.12
2.22
2.33
2.44
2.56
2.68
2.81
2.94
3.08
3.22
3.36
3.51
3.67
3.83
3.99
4.16
4.34
1613
1698
1786
1878
1972
2071
2173
2279
2389
2502
2620
2743
2869
2999
3134
3274
3418
3567
3721
3880
4044
963
972
1.89
1.98
2.08
2.19
2.29
2.40
2.52
2.63
2.76
2.88
3.02
3.15
3.29
3.44
3.59
3.74
3.90
4.07
4.24
4.41
4.59
1761
1849
1942
2038
2137
2240
2347
2457
2571
2690
2812
2939
3070
3205
3345
3489
3638
3792
3950
4113
4282
1001
1010
1018
1027
1036
1045
1054
1063
1073
1082
1092
1102
1112
1122
1132
1142
1152
1163
1174
1184
1195
2.05
2.15
2.25
2.36
2.47
2.58
2.70
2.83
2.95
3.09
3.22
3.36
3.51
3.66
3.81
3.97
4.14
4.31
4.48
4.66
4.85
1909
2002
2099
2199
2303
2410
2521
2636
2755
2877
3004
3136
3271
3411
3555
3704
3857
4016
4179
4347
4520
899
941
980
909
950
989
998
919
960
929
969
1008
1017
1027
1036
1046
1056
1066
1076
1087
1097
1108
1118
1129
1140
1151
1162
939
979
949
989
959
999
970
1009
1019
1029
1040
1050
1061
1072
1083
1094
1105
1117
1128
980
991
1002
1013
1024
1035
1046
1058
1069
1081
1093
LEGEND
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 5.25.
Bhp
— Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 830 to 1130 rpm. All other rpms require field-
supplied drive.
3. See page 23 for general fan performance notes.
—29—
Table 21 — Fan Performance 551B150 — Vertical Discharge Units; Standard Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
CFM
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
6300
654
668
683
697
712
726
741
755
770
785
800
815
829
844
859
874
889
904
920
935
950
965
980
995
1011
1026
1041
1.11
1.20
1.28
1.37
1.47
1.57
1.67
1.78
1.89
2.01
2.14
2.26
2.40
2.54
2.68
2.83
2.99
3.15
3.32
3.49
3.67
3.85
4.05
4.24
4.45
4.66
4.88
1040
1116
1197
1281
1370
1462
1559
1660
1766
1876
1991
2111
2235
2365
2499
2640
2784
2936
3092
3253
3421
3594
3773
3958
4149
4347
4550
713
726
739
753
766
780
794
807
821
835
849
863
877
891
906
920
934
949
963
977
992
1006
1021
1036
1050
1065
—
1.31
1.39
1.48
1.58
1.68
1.79
1.89
2.01
2.13
2.25
2.38
2.51
2.65
2.80
2.95
3.10
3.26
3.43
3.60
3.78
3.97
4.16
4.35
4.56
4.77
4.99
—
1218
1299
1385
1474
1567
1665
1767
1873
1984
2099
2219
2344
2473
2608
2747
2892
3042
3198
3359
3525
3698
3876
4060
4250
4446
4649
—
767
779
792
804
817
830
843
856
869
882
895
909
922
936
949
963
977
990
1004
1018
1032
1046
1060
1074
1088
—
1.50
1.59
1.69
1.79
1.89
2.00
2.12
2.23
2.36
2.49
2.62
2.76
2.91
3.06
3.21
3.37
3.54
3.71
3.89
4.07
4.26
4.46
4.66
4.87
5.09
—
1395
1481
1572
1666
1764
1866
1973
2084
2200
2320
2445
2575
2709
2849
2994
3143
3298
3459
3625
3796
3974
4157
4346
4541
4742
—
817
828
840
852
864
876
889
901
914
926
939
952
965
978
991
1004
1017
1030
1044
1057
1070
1084
1098
1111
—
1.69
1.78
1.88
1.99
2.10
2.22
2.34
2.46
2.59
2.72
2.86
3.01
3.16
3.31
3.47
3.64
3.81
3.99
4.17
4.36
4.56
4.76
4.97
5.18
—
1571
1662
1758
1857
1960
2067
2179
2295
2415
2541
2670
2805
2944
3089
3238
3393
3553
3719
3890
4066
4249
4436
4630
4831
—
863
874
886
897
909
920
932
944
956
968
980
993
1005
1018
1030
1043
1056
1068
1081
1094
1107
1120
—
1.87
1.98
2.08
2.20
2.31
2.43
2.56
2.69
2.82
2.96
3.10
3.25
3.41
3.57
3.73
3.91
4.08
4.27
4.45
4.65
4.85
5.06
—
1748
1844
1943
2048
2155
2268
2384
2505
2630
2760
2895
3034
3178
3328
3483
3642
3807
3977
4153
4335
4522
4715
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
CFM
1.2
Bhp
1.4
Bhp
1.8
Bhp
2.0
Bhp
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Watts
Rpm
Watts
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
6300
907
918
929
940
951
962
973
985
996
1008
1020
1032
1044
1056
1068
1080
1093
1105
1118
1130
—
2.06
2.17
2.28
2.40
2.52
2.65
2.78
2.91
3.05
3.20
3.34
3.50
3.66
3.82
4.00
4.17
4.35
4.54
4.74
4.94
—
1924
2025
2130
2238
2351
2468
2589
2715
2845
2979
3119
3263
3413
3566
3726
3891
4060
4236
4417
4603
—
949
959
970
980
991
1002
1013
1024
1035
1046
1058
1069
1081
1093
1104
1116
1128
1140
1152
—
2.25
2.37
2.48
2.61
2.73
2.86
3.00
3.14
3.28
3.43
3.58
3.74
3.91
4.08
4.26
4.44
4.63
4.82
5.02
—
2101
2207
2316
2429
2547
2668
2794
2924
3059
3199
3343
3492
3646
3805
3969
4139
4314
4494
4679
—
989
999
1009
1019
1029
1040
1050
1061
1072
1083
1094
1105
1117
1128
1139
1151
1163
1174
—
2.44
2.56
2.68
2.81
2.94
3.08
3.22
3.36
3.51
3.67
3.83
3.99
4.16
4.34
4.52
4.70
4.90
5.10
—
2279
2389
2502
2620
2743
2869
2999
3134
3274
3418
3567
3721
3880
4044
4212
4386
4566
4751
—
1027
1036
1046
1056
1066
1076
1087
1097
1108
1118
1129
1140
1151
1162
1173
1185
1196
—
2.63
2.76
2.88
3.02
3.15
3.29
3.44
3.59
3.74
3.90
4.07
4.24
4.41
4.59
4.78
4.97
5.17
—
2457
2571
2690
2812
2939
3070
3205
3345
3489
3638
3792
3950
4113
4282
4456
4634
4819
—
1063
1073
1082
1092
1102
1112
1122
1132
1142
1152
1163
1174
1184
1195
1206
—
2.83
2.95
3.09
3.22
3.36
3.51
3.66
3.81
3.97
4.14
4.31
4.48
4.66
4.85
5.04
—
2636
2755
2877
3004
3136
3271
3411
3555
3704
3857
4016
4179
4347
4520
4699
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 5.25.
Bhp
— Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 830 to 1130 rpm. All other rpms require field-
supplied drive.
3. See page 23 for general fan performance notes.
—30—
Table 22 — Fan Performance 551B090 — Horizontal Discharge Units; Standard Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
CFM
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
2250
2300
2400
2500
2550
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750
465
471
483
495
501
507
519
532
544
557
570
583
596
609
622
635
649
655
0.43
0.45
0.49
0.54
0.56
0.59
0.64
0.70
0.75
0.82
0.88
0.95
1.03
1.10
1.19
1.27
1.36
1.41
402
421
555
560
571
581
587
592
603
614
625
637
648
660
672
684
696
708
720
726
0.64
0.66
0.71
0.77
0.79
0.82
0.88
0.95
1.01
1.08
1.16
1.23
1.32
1.40
1.49
1.59
1.69
1.74
596
618
629
634
644
654
659
664
674
684
695
705
716
727
738
749
760
771
783
789
0.86
0.89
0.94
1.01
1.04
1.07
1.14
1.21
1.28
1.36
1.44
1.53
1.61
1.71
1.81
1.91
2.02
2.07
802
828
694
699
708
717
722
727
737
746
756
766
776
787
797
808
818
829
840
845
1.10
1.13
1.19
1.26
1.29
1.33
1.40
1.48
1.56
1.64
1.73
1.82
1.92
2.02
2.13
2.24
2.35
2.41
1021
1050
1109
1171
1204
1237
1306
1378
1453
1533
1615
1702
1792
1887
1985
2088
2195
2250
753
757
766
775
779
784
793
803
812
822
831
841
851
861
872
882
892
897
1.34
1.38
1.45
1.52
1.56
1.60
1.68
1.76
1.85
1.94
2.03
2.13
2.24
2.35
2.46
2.58
2.70
2.76
1252
1283
1348
1416
1452
1488
1563
1641
1723
1808
1897
1991
2088
2188
2294
2403
2517
2575
461
665
881
503
715
937
526
740
967
549
767
996
597
823
1059
1125
1194
1266
1342
1422
1506
1593
1685
1781
1881
1932
649
882
703
944
761
1009
1079
1151
1228
1308
1392
1481
1573
1621
823
888
957
1030
1106
1187
1272
1316
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
CFM
1.2
Bhp
1.4
Bhp
1.8
Bhp
2.0
Bhp
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Watts
Rpm
Watts
2250
2300
2400
2500
2550
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750
806
811
819
828
832
836
845
854
864
873
882
892
901
911
921
—
1.60
1.64
1.71
1.79
1.83
1.88
1.96
2.05
2.15
2.24
2.35
2.45
2.56
2.68
2.80
—
1494
1528
1599
1672
1710
1749
1830
1914
2002
2093
2189
2288
2391
2499
2610
—
856
860
868
877
881
885
894
903
912
921
930
939
948
—
1.87
1.91
1.99
2.08
2.12
2.17
2.26
2.36
2.46
2.56
2.67
2.78
2.90
—
1747
1784
1859
1938
1979
2021
2107
2197
2290
2388
2489
2595
2704
—
903
907
915
923
927
931
940
948
957
966
—
2.15
2.20
2.28
2.37
2.42
2.47
2.57
2.67
2.77
2.89
—
2009
2048
2129
2214
2258
2302
2394
2488
2587
2691
—
947
950
958
966
971
975
983
—
2.45
2.49
2.58
2.68
2.73
2.78
2.88
—
2282
2323
2410
2499
2545
2592
2689
—
988
992
1000
—
2.75
2.80
2.89
—
2564
2607
2698
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
Bhp
— Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 840 to 1085 rpm. All other rpms require field-
supplied drive.
3. See page 23 for general fan performance notes.
—31—
Table 23 — Fan Performance 551B090 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
CFM
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
2250
2300
2400
2500
2550
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750
465
471
483
495
501
507
519
532
544
557
570
583
596
609
622
635
649
655
0.43
0.45
0.49
0.54
0.56
0.59
0.64
0.70
0.75
0.82
0.88
0.95
1.03
1.10
1.19
1.27
1.36
1.41
402
421
555
560
571
581
587
592
603
614
625
637
648
660
672
684
696
708
720
726
0.64
0.66
0.71
0.77
0.79
0.82
0.88
0.95
1.01
1.08
1.16
1.23
1.32
1.40
1.49
1.59
1.69
1.74
596
618
629
634
644
654
659
664
674
684
695
705
716
727
738
749
760
771
783
789
0.86
0.89
0.94
1.01
1.04
1.07
1.14
1.21
1.28
1.36
1.44
1.53
1.61
1.71
1.81
1.91
2.02
2.07
802
828
694
699
708
717
722
727
737
746
756
766
776
787
797
808
818
829
840
845
1.10
1.13
1.19
1.26
1.29
1.33
1.40
1.48
1.56
1.64
1.73
1.82
1.92
2.02
2.13
2.24
2.35
2.41
1021
1050
1109
1171
1204
1237
1306
1378
1453
1533
1615
1702
1792
1887
1985
2088
2195
2250
753
757
766
775
779
784
793
803
812
822
831
841
851
861
872
882
892
897
1.34
1.38
1.45
1.52
1.56
1.60
1.68
1.76
1.85
1.94
2.03
2.13
2.24
2.35
2.46
2.58
2.70
2.76
1252
1283
1348
1416
1452
1488
1563
1641
1723
1808
1897
1991
2088
2188
2294
2403
2517
2575
461
665
881
503
715
937
526
740
967
549
767
996
597
823
1059
1125
1194
1266
1342
1422
1506
1593
1685
1781
1881
1932
649
882
703
944
761
1009
1079
1151
1228
1308
1392
1481
1573
1621
823
888
957
1030
1106
1187
1272
1316
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
CFM
1.2
Bhp
1.4
Bhp
1.8
Bhp
2.0
Bhp
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Watts
Rpm
Watts
2250
2300
2400
2500
2550
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3750
806
811
819
828
832
836
845
854
864
873
882
892
901
911
921
931
941
946
1.60
1.64
1.71
1.79
1.83
1.88
1.96
2.05
2.15
2.24
2.35
2.45
2.56
2.68
2.80
2.92
3.05
3.12
1494
1528
1599
1672
1710
1749
1830
1914
2002
2093
2189
2288
2391
2499
2610
2726
2847
2908
856
860
868
877
881
885
894
903
912
921
930
939
948
958
967
977
987
992
1.87
1.91
1.99
2.08
2.12
2.17
2.26
2.36
2.46
2.56
2.67
2.78
2.90
3.02
3.15
3.28
3.41
3.48
1747
1784
1859
1938
1979
2021
2107
2197
2290
2388
2489
2595
2704
2817
2935
3057
3184
3249
903
907
2.15
2.20
2.28
2.37
2.42
2.47
2.57
2.67
2.77
2.89
3.00
3.12
3.24
3.37
3.50
3.64
3.78
3.86
2009
2048
2129
2214
2258
2302
2394
2488
2587
2691
2798
2909
3024
3144
3268
3396
3529
3597
947
950
2.45
2.49
2.58
2.68
2.73
2.78
2.88
2.99
3.10
3.22
3.34
3.47
3.60
3.73
3.87
4.01
4.16
—
2282
2323
2410
2499
2545
2592
2689
2790
2894
3003
3115
3233
3353
3479
3608
3743
3882
—
988
992
2.75
2.80
2.89
3.00
3.05
3.10
3.21
3.32
3.44
3.56
3.69
3.82
3.96
4.10
—
2564
2607
2698
2793
2842
2891
2993
3099
3209
3323
3441
3564
3690
3821
—
915
958
1000
1008
1012
1016
1024
1032
1041
1049
1057
1066
1075
1084
—
923
966
927
971
931
975
940
983
948
991
957
1000
1008
1017
1026
1035
1044
1053
1062
1071
—
966
975
984
993
1002
1011
1021
1030
1035
—
—
—
—
—
—
—
—
—
LEGEND
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 4.20.
Bhp
— Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field-
supplied drive.
3. See page 23 for general fan performance notes.
—32—
Table 24 — Fan Performance 551B102 — Horizontal Discharge Units; Standard Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
CFM
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
462
474
486
498
510
523
536
549
562
575
588
601
614
628
641
655
668
682
696
0.37
0.41
0.45
0.49
0.53
0.58
0.63
0.68
0.74
0.80
0.86
0.93
1.00
1.07
1.15
1.23
1.31
1.40
1.49
348
381
541
551
561
571
581
592
603
614
626
637
649
661
673
685
697
709
722
734
747
0.50
0.54
0.58
0.63
0.68
0.73
0.78
0.84
0.90
0.96
1.03
1.10
1.17
1.25
1.33
1.42
1.51
1.60
1.70
467
505
614
622
630
639
648
657
666
676
686
696
707
717
728
739
750
761
773
784
796
0.64
0.68
0.73
0.78
0.83
0.88
0.94
1.00
1.07
1.14
1.21
1.28
1.36
1.44
1.53
1.61
1.71
1.80
1.91
594
635
681
688
695
702
710
718
726
735
743
752
762
771
781
791
801
812
822
833
844
0.78
0.83
0.88
0.93
0.99
1.05
1.11
1.17
1.24
1.31
1.39
1.47
1.55
1.64
1.72
1.82
1.92
2.02
2.12
728
773
744
750
756
762
768
775
783
790
798
806
815
823
832
841
850
860
870
880
890
0.93
0.98
1.04
1.09
1.15
1.22
1.28
1.35
1.42
1.50
1.58
1.66
1.75
1.84
1.93
2.03
2.13
2.23
2.34
868
916
417
545
679
820
967
456
587
725
870
1020
1076
1135
1196
1260
1328
1398
1472
1548
1629
1712
1799
1890
1984
2082
2184
497
632
774
922
541
680
825
977
587
730
879
1035
1096
1159
1226
1296
1369
1445
1525
1608
1695
1786
1880
1979
637
783
936
689
839
996
744
898
1059
1125
1194
1267
1343
1423
1506
1593
1683
1777
802
961
864
1026
1095
1167
1243
1322
1405
1492
1582
929
997
1069
1144
1223
1305
1392
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
CFM
1.2
Bhp
1.4
Bhp
1.8
Bhp
2.0
Bhp
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Watts
Rpm
Watts
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
804
809
813
819
824
830
837
843
850
858
865
873
881
889
898
907
916
925
934
1.09
1.14
1.20
1.26
1.32
1.39
1.46
1.53
1.61
1.69
1.77
1.86
1.95
2.04
2.14
2.24
2.35
2.45
2.57
1013
1065
1119
1176
1235
1298
1363
1431
1502
1576
1653
1733
1816
1904
1995
2089
2187
2289
2395
861
864
869
873
878
883
889
894
901
907
914
921
928
936
944
952
960
969
978
1.25
1.31
1.37
1.43
1.50
1.57
1.65
1.72
1.80
1.88
1.97
2.06
2.16
2.25
2.35
2.46
2.57
2.68
2.80
1164
1219
1277
1337
1400
1466
1534
1606
1680
1758
1838
1922
2010
2100
2195
2293
2395
2500
2610
915
918
921
925
929
934
938
944
949
955
961
967
974
981
988
996
1004
—
1.41
1.48
1.54
1.61
1.68
1.76
1.83
1.91
2.00
2.09
2.18
2.27
2.37
2.47
2.57
2.68
2.80
—
1319
1378
1439
1503
1569
1638
1710
1785
1863
1944
2029
2116
2207
2302
2399
2501
2607
—
967
969
972
975
978
982
986
991
996
1001
1007
1012
1019
1025
1032
—
1.59
1.65
1.72
1.79
1.87
1.95
2.03
2.11
2.20
2.29
2.38
2.48
2.58
2.69
2.80
—
1479
1541
1606
1673
1742
1815
1891
1969
2051
2135
2223
2314
2409
2507
2608
—
1017
1018
1021
1023
1026
1029
1033
1037
1041
1046
1051
1056
1062
—
1.76
1.83
1.90
1.98
2.06
2.14
2.23
2.31
2.40
2.50
2.60
2.70
2.80
—
1642
1708
1776
1847
1920
1996
2075
2157
2242
2331
2422
2516
2615
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
Bhp
— Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 840 to 1085 rpm. All other rpms require field-
supplied drive.
3. See page 23 for general fan performance notes.
—33—
Table 25 — Fan Performance 551B102 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
CFM
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
462
474
486
498
510
523
536
549
562
575
588
601
614
628
641
655
668
682
696
0.37
0.41
0.45
0.49
0.53
0.58
0.63
0.68
0.74
0.80
0.86
0.93
1.00
1.07
1.15
1.23
1.31
1.40
1.49
348
381
541
551
561
571
581
592
603
614
626
637
649
661
673
685
697
709
722
734
747
0.50
0.54
0.58
0.63
0.68
0.73
0.78
0.84
0.90
0.96
1.03
1.10
1.17
1.25
1.33
1.42
1.51
1.60
1.70
467
505
614
622
630
639
648
657
666
676
686
696
707
717
728
739
750
761
773
784
796
0.64
0.68
0.73
0.78
0.83
0.88
0.94
1.00
1.07
1.14
1.21
1.28
1.36
1.44
1.53
1.61
1.71
1.80
1.91
594
635
681
688
695
702
710
718
726
735
743
752
762
771
781
791
801
812
822
833
844
0.78
0.83
0.88
0.93
0.99
1.05
1.11
1.17
1.24
1.31
1.39
1.47
1.55
1.64
1.72
1.82
1.92
2.02
2.12
728
773
744
750
756
762
768
775
783
790
798
806
815
823
832
841
850
860
870
880
890
0.93
0.98
1.04
1.09
1.15
1.22
1.28
1.35
1.42
1.50
1.58
1.66
1.75
1.84
1.93
2.03
2.13
2.23
2.34
868
916
417
545
679
820
967
456
587
725
870
1020
1076
1135
1196
1260
1328
1398
1472
1548
1629
1712
1799
1890
1984
2082
2184
497
632
774
922
541
680
825
977
587
730
879
1035
1096
1159
1226
1296
1369
1445
1525
1608
1695
1786
1880
1979
637
783
936
689
839
996
744
898
1059
1125
1194
1267
1343
1423
1506
1593
1683
1777
802
961
864
1026
1095
1167
1243
1322
1405
1492
1582
929
997
1069
1144
1223
1305
1392
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
CFM
1.2
Bhp
1.4
Bhp
1.8
Bhp
2.0
Bhp
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Watts
Rpm
Watts
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
804
809
813
819
824
830
837
843
850
858
865
873
881
889
898
907
916
925
934
1.09
1.14
1.20
1.26
1.32
1.39
1.46
1.53
1.61
1.69
1.77
1.86
1.95
2.04
2.14
2.24
2.35
2.45
2.57
1013
1065
1119
1176
1235
1298
1363
1431
1502
1576
1653
1733
1816
1904
1995
2089
2187
2289
2395
861
864
869
873
878
883
889
894
901
907
914
921
928
936
944
952
960
969
978
1.25
1.31
1.37
1.43
1.50
1.57
1.65
1.72
1.80
1.88
1.97
2.06
2.16
2.25
2.35
2.46
2.57
2.68
2.80
1164
1219
1277
1337
1400
1466
1534
1606
1680
1758
1838
1922
2010
2100
2195
2293
2395
2500
2610
915
918
921
925
929
934
938
944
949
955
961
967
974
981
988
996
1004
1011
1020
1.41
1.48
1.54
1.61
1.68
1.76
1.83
1.91
2.00
2.09
2.18
2.27
2.37
2.47
2.57
2.68
2.80
2.91
3.03
1319
1378
1439
1503
1569
1638
1710
1785
1863
1944
2029
2116
2207
2302
2399
2501
2607
2716
2828
967
969
1.59
1.65
1.72
1.79
1.87
1.95
2.03
2.11
2.20
2.29
2.38
2.48
2.58
2.69
2.80
2.91
3.03
3.15
3.27
1479
1541
1606
1673
1742
1815
1891
1969
2051
2135
2223
2314
2409
2507
2608
2713
2822
2935
3052
1017
1018
1021
1023
1026
1029
1033
1037
1041
1046
1051
1056
1062
1068
1074
1080
1087
1094
1101
1.76
1.83
1.90
1.98
2.06
2.14
2.23
2.31
2.40
2.50
2.60
2.70
2.80
2.91
3.03
3.14
3.26
3.39
3.52
1642
1708
1776
1847
1920
1996
2075
2157
2242
2331
2422
2516
2615
2716
2821
2930
3042
3159
3279
972
975
978
982
986
991
996
1001
1007
1012
1019
1025
1032
1038
1046
1053
1061
LEGEND
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 4.20.
Bhp
— Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field-
supplied drive.
3. See page 23 for general fan performance notes.
—34—
Table 26 — Fan Performance 551B120 — Horizontal Discharge Units; Standard Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
CFM
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
523
536
549
562
575
588
601
614
628
641
655
668
682
696
710
723
737
751
765
779
793
0.58
0.63
0.68
0.74
0.80
0.86
0.93
1.00
1.07
1.15
1.23
1.31
1.40
1.49
1.59
1.69
1.80
1.91
2.02
2.14
2.26
541
587
592
603
614
626
637
649
661
673
685
697
709
722
734
747
760
773
785
798
812
825
838
0.73
0.78
0.84
0.90
0.96
1.03
1.10
1.17
1.25
1.33
1.42
1.51
1.60
1.70
1.80
1.90
2.01
2.13
2.25
2.37
2.50
680
730
657
666
676
686
696
707
717
728
739
750
761
773
784
796
808
820
832
844
856
869
881
0.88
0.94
1.00
1.07
1.14
1.21
1.28
1.36
1.44
1.53
1.61
1.71
1.80
1.91
2.01
2.12
2.24
2.35
2.48
2.61
2.74
825
879
718
726
735
743
752
762
771
781
791
801
812
822
833
844
855
866
877
889
900
912
923
1.05
1.11
1.17
1.24
1.31
1.39
1.47
1.55
1.64
1.72
1.82
1.92
2.02
2.12
2.23
2.35
2.46
2.59
2.71
2.85
2.98
977
1035
1096
1159
1226
1296
1369
1445
1525
1608
1695
1786
1880
1979
2081
2187
2297
2412
2531
2654
2782
775
783
790
798
806
815
823
832
841
850
860
870
880
890
900
910
921
932
942
953
965
1.22
1.28
1.35
1.42
1.50
1.58
1.66
1.75
1.84
1.93
2.03
2.13
2.23
2.34
2.46
2.57
2.70
2.82
2.95
3.09
3.23
1135
1196
1260
1328
1398
1472
1548
1629
1712
1799
1890
1984
2082
2184
2290
2400
2514
2633
2756
2883
3014
637
783
936
689
839
996
744
898
1059
1125
1194
1267
1343
1423
1506
1593
1683
1777
1876
1978
2085
2195
2310
2430
2554
802
961
864
1026
1095
1167
1243
1322
1405
1492
1582
1677
1775
1877
1984
2095
2210
2330
929
997
1069
1144
1223
1305
1392
1482
1577
1675
1778
1885
1996
2112
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
CFM
1.2
Bhp
1.4
Bhp
1.8
Bhp
2.0
Bhp
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Watts
Rpm
Watts
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
830
837
843
850
858
865
873
881
889
898
907
916
925
934
944
954
963
974
984
994
1005
1.39
1.46
1.53
1.61
1.69
1.77
1.86
1.95
2.04
2.14
2.24
2.35
2.45
2.57
2.69
2.81
2.93
3.07
3.20
3.34
3.49
1298
1363
1431
1502
1576
1653
1733
1816
1904
1995
2089
2187
2289
2395
2504
2618
2736
2858
2985
3116
3251
883
889
894
901
907
914
921
928
936
944
952
960
969
978
986
996
1005
1014
1024
1034
—
1.57
1.65
1.72
1.80
1.88
1.97
2.06
2.16
2.25
2.35
2.46
2.57
2.68
2.80
2.92
3.05
3.18
3.31
3.45
3.60
—
1466
1534
1606
1680
1758
1838
1922
2010
2100
2195
2293
2395
2500
2610
2723
2840
2962
3088
3219
3353
—
934
938
944
949
955
961
967
974
981
988
996
1004
1011
1020
1028
1037
1045
1054
—
1.76
1.83
1.91
2.00
2.09
2.18
2.27
2.37
2.47
2.57
2.68
2.80
2.91
3.03
3.16
3.29
3.42
3.56
—
1638
1710
1785
1863
1944
2029
2116
2207
2302
2399
2501
2607
2716
2828
2946
3067
3192
3322
—
982
986
1.95
2.03
2.11
2.20
2.29
2.38
2.48
2.58
2.69
2.80
2.91
3.03
3.15
3.27
3.40
3.54
3.67
—
1815
1891
1969
2051
2135
2223
2314
2409
2507
2608
2713
2822
2935
3052
3173
3297
3426
—
1029
1033
1037
1041
1046
1051
1056
1062
1068
1074
1080
1087
1094
1101
1108
—
2.14
2.23
2.31
2.40
2.50
2.60
2.70
2.80
2.91
3.03
3.14
3.26
3.39
3.52
3.65
—
1996
2075
2157
2242
2331
2422
2516
2615
2716
2821
2930
3042
3159
3279
3403
—
991
996
1001
1007
1012
1019
1025
1032
1038
1046
1053
1061
1068
1076
1085
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 3.70.
Bhp
— Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 860 to 1080 rpm. All other rpms require field-
supplied drive.
3. See page 23 for general fan performance notes.
—35—
Table 27 — Fan Performance 551B120 — Horizontal Discharge Units; High-Static Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
CFM
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
523
536
549
562
575
588
601
614
628
641
655
668
682
696
710
723
737
751
765
779
793
0.58
0.63
0.68
0.74
0.80
0.86
0.93
1.00
1.07
1.15
1.23
1.31
1.40
1.49
1.59
1.69
1.80
1.91
2.02
2.14
2.26
541
587
592
603
614
626
637
649
661
673
685
697
709
722
734
747
760
773
785
798
812
825
838
0.73
0.78
0.84
0.90
0.96
1.03
1.10
1.17
1.25
1.33
1.42
1.51
1.60
1.70
1.80
1.90
2.01
2.13
2.25
2.37
2.50
680
730
657
666
676
686
696
707
717
728
739
750
761
773
784
796
808
820
832
844
856
869
881
0.88
0.94
1.00
1.07
1.14
1.21
1.28
1.36
1.44
1.53
1.61
1.71
1.80
1.91
2.01
2.12
2.24
2.35
2.48
2.61
2.74
825
879
718
726
735
743
752
762
771
781
791
801
812
822
833
844
855
866
877
889
900
912
923
1.05
1.11
1.17
1.24
1.31
1.39
1.47
1.55
1.64
1.72
1.82
1.92
2.02
2.12
2.23
2.35
2.46
2.59
2.71
2.85
2.98
977
1035
1096
1159
1226
1296
1369
1445
1525
1608
1695
1786
1880
1979
2081
2187
2297
2412
2531
2654
2782
775
783
790
798
806
815
823
832
841
850
860
870
880
890
900
910
921
932
942
953
965
1.22
1.28
1.35
1.42
1.50
1.58
1.66
1.75
1.84
1.93
2.03
2.13
2.23
2.34
2.46
2.57
2.70
2.82
2.95
3.09
3.23
1135
1196
1260
1328
1398
1472
1548
1629
1712
1799
1890
1984
2082
2184
2290
2400
2514
2633
2756
2883
3014
637
783
936
689
839
996
744
898
1059
1125
1194
1267
1343
1423
1506
1593
1683
1777
1876
1978
2085
2195
2310
2430
2554
802
961
864
1026
1095
1167
1243
1322
1405
1492
1582
1677
1775
1877
1984
2095
2210
2330
929
997
1069
1144
1223
1305
1392
1482
1577
1675
1778
1885
1996
2112
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
CFM
1.2
Bhp
1.4
Bhp
1.8
Bhp
2.0
Bhp
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Watts
Rpm
Watts
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
830
837
843
850
858
865
873
881
889
898
907
916
925
934
944
954
963
974
984
994
1005
1.39
1.46
1.53
1.61
1.69
1.77
1.86
1.95
2.04
2.14
2.24
2.35
2.45
2.57
2.69
2.81
2.93
3.07
3.20
3.34
3.49
1298
1363
1431
1502
1576
1653
1733
1816
1904
1995
2089
2187
2289
2395
2504
2618
2736
2858
2985
3116
3251
883
889
894
901
907
914
921
928
936
944
952
960
969
978
986
996
1005
1014
1024
1034
1044
1.57
1.65
1.72
1.80
1.88
1.97
2.06
2.16
2.25
2.35
2.46
2.57
2.68
2.80
2.92
3.05
3.18
3.31
3.45
3.60
3.74
1466
1534
1606
1680
1758
1838
1922
2010
2100
2195
2293
2395
2500
2610
2723
2840
2962
3088
3219
3353
3492
934
938
1.76
1.83
1.91
2.00
2.09
2.18
2.27
2.37
2.47
2.57
2.68
2.80
2.91
3.03
3.16
3.29
3.42
3.56
3.71
3.85
4.01
1638
1710
1785
1863
1944
2029
2116
2207
2302
2399
2501
2607
2716
2828
2946
3067
3192
3322
3456
3594
3737
982
986
1.95
2.03
2.11
2.20
2.29
2.38
2.48
2.58
2.69
2.80
2.91
3.03
3.15
3.27
3.40
3.54
3.67
3.82
3.96
4.12
4.27
1815
1891
1969
2051
2135
2223
2314
2409
2507
2608
2713
2822
2935
3052
3173
3297
3426
3560
3697
3839
3986
1029
1033
1037
1041
1046
1051
1056
1062
1068
1074
1080
1087
1094
1101
1108
1115
1123
1131
1139
1148
1156
2.14
2.23
2.31
2.40
2.50
2.60
2.70
2.80
2.91
3.03
3.14
3.26
3.39
3.52
3.65
3.79
3.93
4.08
4.23
4.38
4.55
1996
2075
2157
2242
2331
2422
2516
2615
2716
2821
2930
3042
3159
3279
3403
3531
3664
3801
3943
4088
4238
944
991
949
996
955
1001
1007
1012
1019
1025
1032
1038
1046
1053
1061
1068
1076
1085
1093
1102
1111
1119
961
967
974
981
988
996
1004
1011
1020
1028
1037
1045
1054
1063
1073
1082
LEGEND
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 5.25.
Bhp
— Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 830 to 1130 rpm. All other rpms require field-
supplied drive.
3. See page 23 for general fan performance notes.
—36—
Table 28 — Fan Performance 551B150 — Horizontal Discharge Units; Standard Motor (Belt Drive)*
EXTERNAL STATIC PRESSURE (in. wg)
AIRFLOW
CFM
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
6300
614
628
641
655
668
682
696
710
723
737
751
765
779
793
807
821
835
850
864
878
892
907
921
935
949
964
978
1.00
1.07
1.15
1.23
1.31
1.40
1.49
1.59
1.69
1.80
1.91
2.02
2.14
2.26
2.39
2.53
2.67
2.81
2.96
3.12
3.28
3.44
3.61
3.79
3.98
4.16
4.36
929
997
673
685
697
709
722
734
747
760
773
785
798
812
825
838
851
864
878
891
905
918
932
945
959
973
987
1000
1014
1.17
1.25
1.33
1.42
1.51
1.60
1.70
1.80
1.90
2.01
2.13
2.25
2.37
2.50
2.63
2.77
2.91
3.06
3.22
3.38
3.54
3.71
3.89
4.07
4.26
4.45
4.65
1095
1167
1243
1322
1405
1492
1582
1677
1775
1877
1984
2095
2210
2330
2455
2584
2718
2856
3000
3148
3302
3461
3626
3795
3970
4151
4337
728
739
750
761
773
784
796
808
820
832
844
856
869
881
894
906
919
932
945
958
971
984
997
1010
1023
1036
1050
1.36
1.44
1.53
1.61
1.71
1.80
1.91
2.01
2.12
2.24
2.35
2.48
2.61
2.74
2.88
3.02
3.17
3.32
3.48
3.64
3.81
3.99
4.17
4.35
4.54
4.74
4.95
1267
1343
1423
1506
1593
1683
1777
1876
1978
2085
2195
2310
2430
2554
2682
2815
2953
3096
3242
3396
3554
3716
3885
4059
4238
4422
4613
781
791
801
812
822
833
844
855
866
877
889
900
912
923
935
947
959
971
984
996
1008
1021
1033
1046
1059
1071
1084
1.55
1.64
1.72
1.82
1.92
2.02
2.12
2.23
2.35
2.46
2.59
2.71
2.85
2.98
3.13
3.27
3.42
3.58
3.74
3.91
4.09
4.26
4.45
4.64
4.84
5.04
5.25
1445
1525
1608
1695
1786
1880
1979
2081
2187
2297
2412
2531
2654
2782
2914
3050
3193
3339
3491
3648
3810
3976
4149
4326
4510
4698
4892
832
841
850
860
870
880
890
900
910
921
932
942
953
965
976
987
999
1010
1022
1034
1045
1057
1069
1082
1094
—
1.75
1.84
1.93
2.03
2.13
2.23
2.34
2.46
2.57
2.70
2.82
2.95
3.09
3.23
3.38
3.53
3.69
3.85
4.01
4.19
4.36
4.55
4.74
4.93
5.13
—
1629
1712
1799
1890
1984
2082
2184
2290
2400
2514
2633
2756
2883
3014
3150
3292
3437
3588
3743
3903
4069
4240
4416
4598
4785
—
1069
1144
1223
1305
1392
1482
1577
1675
1778
1885
1996
2112
2232
2357
2487
2622
2762
2906
3055
3211
3370
3536
3707
3883
4066
—
—
—
EXTERNAL STATIC PRESSURE (in. wg)
1.6
AIRFLOW
CFM
1.2
Bhp
1.4
Bhp
1.8
Bhp
2.0
Bhp
Rpm
Watts
Rpm
Watts
Rpm
Bhp
Watts
Rpm
Watts
Rpm
Watts
3700
3800
3900
4000
4100
4200
4300
4400
4500
4600
4700
4800
4900
5000
5100
5200
5300
5400
5500
5600
5700
5800
5900
6000
6100
6200
6300
881
889
1.95
2.04
2.14
2.24
2.35
2.45
2.57
2.69
2.81
2.93
3.07
3.20
3.34
3.49
3.64
3.79
3.95
4.12
4.29
4.46
4.65
4.83
5.03
5.23
—
1816
1904
1995
2089
2187
2289
2395
2504
2618
2736
2858
2985
3116
3251
3391
3536
3685
3840
3999
4163
4333
4508
4688
4873
—
928
936
944
952
960
969
978
986
996
1005
1014
1024
1034
1044
1054
1064
1075
1085
1096
1106
1117
1128
—
2.16
2.25
2.35
2.46
2.57
2.68
2.80
2.92
3.05
3.18
3.31
3.45
3.60
3.74
3.90
4.06
4.22
4.39
4.57
4.75
4.93
5.13
—
2010
2100
2195
2293
2395
2500
2610
2723
2840
2962
3088
3219
3353
3492
3636
3784
3938
4096
4259
4427
4601
4779
—
974
981
2.37
2.47
2.57
2.68
2.80
2.91
3.03
3.16
3.29
3.42
3.56
3.71
3.85
4.01
4.17
4.33
4.50
4.67
4.85
5.03
5.22
—
2207
2302
2399
2501
2607
2716
2828
2946
3067
3192
3322
3456
3594
3737
3885
4037
4194
4356
4523
4695
4872
—
1019
1025
1032
1038
1046
1053
1061
1068
1076
1085
1093
1102
1111
1119
1129
1138
1147
1157
1167
—
2.58
2.69
2.80
2.91
3.03
3.15
3.27
3.40
3.54
3.67
3.82
3.96
4.12
4.27
4.44
4.60
4.78
4.95
5.14
—
2409
2507
2608
2713
2822
2935
3052
3173
3297
3426
3560
3697
3839
3986
4137
4293
4454
4619
4790
—
1062
1068
1074
1080
1087
1094
1101
1108
1115
1123
1131
1139
1148
1156
1165
1174
1183
1192
—
2.80
2.91
3.03
3.14
3.26
3.39
3.52
3.65
3.79
3.93
4.08
4.23
4.38
4.55
4.71
4.88
5.06
5.24
—
2615
2716
2821
2930
3042
3159
3279
3403
3531
3664
3801
3943
4088
4238
4393
4553
4718
4886
—
898
988
907
996
916
1004
1011
1020
1028
1037
1045
1054
1063
1073
1082
1092
1101
1111
1121
1132
1142
1152
—
925
934
944
954
963
974
984
994
1005
1015
1026
1037
1048
1059
1070
1082
1093
1105
1116
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 5.25.
Bhp
— Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 830 to 1130 rpm. All other rpms require field-
supplied drive.
3. See page 23 for general fan performance notes.
—37—
PRE-START-UP
d. Make sure that all tools and miscellaneous loose
parts have been removed.
e. Make sure that the start-up checklist has been
performed and filled out.
WARNING: Failure to observe the following warn-
ings could result in serious personal injury:
1. Follow recognized safety practices and wear
protective goggles when checking or servicing
refrigerant system.
NOTE: Ensure wiring does not contact any refrigerant
tubing.
2. Do not operate compressor or provide any elec-
tric power to unit unless compressor terminal
cover is in place and secured.
START-UP
I. UNIT PREPARATION
Make sure that unit has been installed in accordance with
these installation instructions and applicable codes.
3. Do not remove compressor terminal cover until
all electrical sources are disconnected and prop-
erly tagged.
II. RETURN-AIR FILTERS
4. Relieve all pressure from system before touch-
ing or disturbing anything inside terminal box
if refrigerant leak is suspected around compres-
sor terminals. Use accepted methods to recover
refrigerant.
Make sure correct filters are installed in unit (see Table 1).
Do not operate unit without return-air filters.
III. OUTDOOR-AIR INLET SCREENS
Outdoor-air inlet screens must be in place before operating
unit.
5. Never attempt to repair soldered connection
while refrigerant system is under pressure.
IV. COMPRESSOR MOUNTING
6. Do not use torch to remove any component. Sys-
tem contains oil and refrigerant under pres-
sure. To remove a component, wear protective
goggles and proceed as follows:
Compressors are internally spring mounted. Do not loosen or
remove compressor holddown bolts.
V. INTERNAL WIRING
a. Shut off electrical power to unit and install
lockout tag.
Check all electrical connections in unit control boxes; tighten
as required.
b. Relieve all pressure from system using
both high and low-pressure ports. Use
accepted methods to recover refrigerant.
c. Cut component connection tubing with tub-
ing cutter and remove component from
unit.
VI. REFRIGERANT SERVICE PORTS
Each refrigerant system has 4 Schrader-type service gage
ports: one on the suction line, one on the liquid line, and 2 on
the compressor discharge line. Be sure that caps on the ports
are tight.
d. Carefully unsweat remaining tubing stubs
when necessary. Oil can ignite when
exposed to torch flame.
VII. HIGH FLOW VALVES
Two high flow refrigerant valves are located on the compres-
sor hot gas and suction tubes. Large black plastic caps dis-
tinguish these valves with o-rings located inside the caps.
These valves can not be accessed for service in the field.
Ensure the plastic caps are in place and tight or the possibil-
ity of refrigerant leakage could occur.
Proceed as follows to inspect and prepare the unit for initial
start-up:
1. Remove all access panels.
2. Read and follow instructions on all WARNING, CAU-
TION, and INFORMATION labels attached to or
shipped with unit.
VIII. COMPRESSOR ROTATION
On 3-phase units, it is important to be certain the scroll
compressor is rotating in the proper direction. To determine
whether or not compressor is rotating in the proper direction:
3. Make the following inspections:
a. Inspect for shipping and handling damages such
as broken lines, loose parts, or disconnected
wires.
1. Connect service gages to suction and discharge pres-
sure fittings.
2. Energize the compressor.
b. Inspect for oil at all refrigerant tubing connec-
tions and on unit base. Detecting oil generally
indicates a refrigerant leak. Leak-test all refrig-
erant tubing connections using electronic leak
detector, halide torch, or liquid-soap solution.
c. Inspect all field-wiring and factory-wiring con-
nections. Be sure that connections are completed
and tight.
3. The suction pressure should drop and the discharge
pressure should rise, as is normal on any start-up.
If the suction pressure does not drop and the discharge pres-
sure does not rise to normal levels:
1. Note that the evaporator fan is probably also rotating
in the wrong direction.
d. Inspect coil fins. If damaged during shipping and
handling, carefully straighten fins with a fin
comb.
2. Turn off power to the unit and install lockout tag.
3. Reverse any two of the unit power leads.
4. Turn on power to the unit.
4. Verify the following:
The suction and discharge pressure levels should now move
to their normal start-up levels.
a. Make sure that condenser-fan blades are
correctly positioned in fan orifice. Refer to
Condenser-Fan Adjustment section on page 42
for more details.
b. Make sure that air filters are in place.
c. Make sure that condensate drain trap is filled
with water to ensure proper drainage.
NOTE: When the compressor is rotating in the wrong direc-
tion, the unit makes an elevated level of noise and does not
provide heating or cooling.
CAUTION: Compressor damage will occur if rota-
tion is not immediately corrected.
—38—
IX. COOLING
C. Cooling, Units With EconoMi$er IV
To start unit, turn on main power supply. Set system selector
switch at COOL position and fan switch at AUTO position.
Adjust thermostat to a setting below room temperature.
Compressor starts on closure of contactor.
When free cooling is not available, the compressors will be
controlled by the zone thermostat. When free cooling is avail-
able, the outdoor-air damper is modulated by the
EconoMi$er IV control to provide a 50 to 55 F supply-air
temperature into the zone. As the supply-air temperature
fluctuates above 55 or below 50 F, the dampers will be modu-
lated (open or close) to bring the supply-air temperature
back within the set point limits.
Check unit charge. Refer to Refrigerant Charge section on
page 42.
Reset thermostat at a position above room temperature.
Compressor will shut off.
For EconoMi$er IV operation, there must be a thermostat
call for the fan (G). This will move the damper to its mini-
mum position during the occupied mode.
To Shut Off Unit
Set system selector switch at OFF position. Resetting ther-
mostat at a position above room temperature shuts unit off
temporarily until space temperature exceeds thermostat set-
ting. Units are equipped with Cycle-LOC™ protection
device. Unit shuts down on any safety trip and remains off;
an indicator light on the thermostat comes on. Check reason
for safety trip.
Above 50 F supply-air temperature, the dampers will modu-
late from 100% open to the minimum open position. From
50 F to 45 F supply-air temperature, the dampers will main-
tain at the minimum open position. Below 45 F the dampers
will be completely shut. As the supply-air temperature rises,
the dampers will come back open to the minimum open posi-
tion once the supply air temperature rises to 48 F.
Compressor restart is accomplished by manual reset at the
thermostat by turning the selector switch to OFF position
and then ON position.
If optional power exhaust is installed, as the outdoor-air
damper opens and closes, the power exhaust fans will be
energized and deenergized.
X. HEATING (IF ACCESSORY HEATER IS INSTALLED)
If field-installed accessory CO2 sensors are connected to the
EconoMi$er IV control, a demand controlled ventilation
strategy will begin to operate. As the CO2 level in the zone
increases above the CO2 set point, the minimum position of
the damper will be increased proportionally. As the CO2 level
decreases because of the increase in fresh air, the outdoor-air
damper will be proportionally closed. Damper position will
follow the higher demand condition from DCV mode or free
cooling mode.
To start unit, turn on main power supply.
Set thermostat at HEAT position and a setting above room
temperature, and set fan at AUTO position.
First stage of thermostat energizes the first-stage electric
heater elements; second stage energizes second-stage electric
heater elements. Check heating effects at air supply grille(s).
If accessory electric heaters do not energize, reset limit
switch (located on evaporator-fan scroll) by pressing button
located between terminals on the switch.
Damper movement from full closed to full open (or vice
versa) will take between 11/2 and 21/2 minutes.
To Shut Off Unit
If free cooling can be used as determined from the appropri-
ate changeover command (switch, dry bulb, enthalpy curve,
differential dry bulb, or differential enthalpy), a call for cool-
ing (Y1 closes at the thermostat) will cause the control to
modulate the dampers open to maintain the supply air tem-
perature set point at 50 to 55 F.
Set system selector switch at OFF position. Resetting heating
selector lever below room temperature temporarily shuts unit
off until space temperature falls below thermostat setting.
XI. SAFETY RELIEF
A soft solder joint in the suction line at the loss-of-charge/
low-pressure switch fitting provides pressure relief under
abnormal temperature and pressure conditions.
As the supply-air temperature drops below the set point
range of 50 to 55 F, the control will modulate the outdoor-
air dampers closed to maintain the proper supply-air
temperature.
XII. VENTILATION (CONTINUOUS FAN)
Set fan and system selector switches at ON and OFF posi-
tions, respectively. Evaporator fan operates continuously to
provide constant air circulation.
D. Heating, Units with EconoMi$er IV
Upon a call for heating through terminal W1, IFC and
heater contactor no. 1 (HC1) are energized. On units
equipped for 2 stages of heat, when additional heat is
needed, HC2 is energized through W2. The economizer
damper moves to the minimum position. When the thermo-
stat is satisfied, the damper moves to the fully closed
position.
XIII. OPERATING SEQUENCE
A. Cooling, Units Without EconoMi$er IV
When the thermostat calls for cooling, terminals G and Y1
are energized. The indoor (evaporator) fan contactor (IFC),
outdoor (condenser) fan contactor (OFC), and compressor
contactor no. 1 (C1) are energized and the evaporator-fan
motor, compressor no. 1, and condenser fans start. The
condenser-fan motors run continuously while unit is in cool-
ing. If the thermostat calls for a second stage of cooling by
energizing Y2, compressor contactor no. 2 (C2) is energized
and compressor no. 2 starts.
E. Units With Perfect Humidity™ Dehumidification System
Normal Design Cooling Operation
When the rooftop operates under the normal sequence of
operation, the compressors will cycle to maintain indoor con-
ditions. See Fig. 40.
The Perfect Humidity dehumidification system includes a
factory-installed Motormaster® low ambient control to keep
the head and suction pressure high, allowing normal design
cooling mode operation down to 0° F.
B. Heating, Units Without EconoMi$er IV (If Accessory
Heater is Installed)
Upon a call for heating through terminal W1, IFC and
heater contactor no. 1 (HC1) are energized. On units
equipped for 2 stages of heat, when additional heat is
needed, HC2 is energized through W2.
—39—
Fig. 40 — Perfect Humidity™ System
Normal Design Cooling Operation
Fig. 41 — Perfect Humidity System
Subcooling Mode Operation
Subcooling Mode
will be cooled and dehumidified, but will be warmed to neu-
tral conditions (72 F to 75 F) by the subcooling/reheat dehu-
midification coil.
When subcooling mode is initiated, this will energize (close)
the liquid line solenoid valve (LLSV) forcing the hot liquid
refrigerant to enter into the subcooling coil (see Fig. 41).
NOTE: The 551B090-150 rooftop units can operate one cir-
cuit in subcooling mode and one circuit in hot gas reheat
mode or both circuits in hot gas reheat mode, or both in nor-
mal design cooling mode.
As the hot liquid refrigerant passes through the subcooling/
reheat dehumidification coil, it is exposed to the cold supply
airflow coming through the evaporator coil. The liquid is fur-
ther subcooled to a temperature approaching the evaporator
leaving-air temperature. The liquid then enters a thermo-
static expansion valve (TXV) where the liquid drops to a
lower pressure. The TXV does not have a pressure drop great
enough to change the liquid to a 2-phase fluid, so the liquid
then enters the Acutrol™ device at the evaporator coil.
The net effect of the rooftop when in hot gas reheat mode is
to provide nearly all latent capacity removal from the space
when sensible loads diminish (when outdoor temperature
conditions are moderate). When in hot gas reheat mode, the
unit will operate to provide mostly latent capacity and
extremely low sensible heat ratio capability.
The liquid enters the evaporator coil at a temperature lower
than in standard cooling operation. This lower temperature
increases the latent capacity of the rooftop unit. The refriger-
ant passes through the evaporator and is turned into a
vapor. The air passing over the evaporator coil will become
colder than during normal operation. However, as this same
air passes over the subcooling coil, it will be slightly warmed,
partially reheating the air.
Similar to the subcooling mode of operation, hot gas reheat
mode operates only when the outside air temperature is
warmer than 40 F. Below this temperature, a factory-installed
outside air temperature switch will lock out this mode of
operation.
See Table 29 for the Perfect Humidity dehumidification sys-
tem sequence of operation.
Subcooling mode operates only when the outside-air temper-
ature is warmer than 40 F. A factory-installed temperature
switch located in the condenser section will lock out subcool-
ing mode when the outside temperature is cooler than 40 F.
The scroll compressors are equipped with crankcase heaters
to provide protection for the compressors due to the addi-
tional refrigerant charge required by the subcooling/reheat
coil.
When in subcooling mode, there is a slight decrease in sys-
tem total gross capacity (5% less), a lower gross sensible
capacity (20% less), and a greatly increased latent capacity
(up to 40% more).
Hot Gas Reheat Mode
When the humidity levels in the space require humidity con-
trol, a hot gas solenoid valve (specific to hot gas reheat mode
only) will open to bypass a portion of hot gas refrigerant
around the condenser coil (see Fig. 42).
This hot gas will mix with liquid refrigerant leaving the con-
denser coil and flow to the subcooling/reheat dehumidifica-
tion coil. Now the conditioned air coming off the evaporator
Fig. 42 — Perfect Humidity System
Hot Gas Reheat Mode Operation
—40—
Table 29 — Perfect Humidity™ Dehumidification System Sequence of Operation
and System Response — Dual Compressor Units
551B UNIT OPERATION
ECONOMIZER FUNCTION
THERMOSTAT
INPUT
First Stage
Second Stage
OAT < Economizer
Set Point
Compressor Subcooling
Hot Gas
Reheat Mode
Compressor Subcooling
Hot Gas
Reheat Mode
H
Y1
Y2
Economizer
1
Mode
2
Mode
Off
On
On
On
On
On
—
—
Unit Operates Under Normal Sequence of Operation
On
On
On
On
Off
On
Off
On
Off
Off
No
No
Yes
Yes
No
Off
Off
On
On
Off
On
On
On
On
On
Yes
Yes
Yes
No
No
No
No
Yes
Yes
On
On
On
On
On
Yes
No
No
No
No
No
Yes
Yes
Yes
Yes
No
LEGEND
— Outdoor Air Temperature
OAT
NOTE: On a thermostat call for W1, all cooling and dehumidification will be off.
F. Units With Power Exhaust
3. Remove condenser coil corner post. See Fig. 43. To
hold top panel open, place coil corner post between
top panel and center post. See Fig. 44.
4. Remove device holding coil sections together at
return end of condenser coil. Carefully separate the
outer coil section 3 to 4 in. from the inner coil section.
See Fig. 45.
5. Use a water hose or other suitable equipment to flush
down between the 2 coil sections to remove dirt and
debris. Clean the outer surfaces with a stiff brush in
the normal manner.
6. Secure the sections together. Reposition the coil sec-
tions, and remove the coil corner post from between
the top panel and center post. Install the coil corner
post and coil center post, and replace all screws.
When the outdoor-air damper is modulated open, the two
end switches located in the actuator are tripped. The factory
settings are: switch no. 1 will close at 30% outdoor air;
switch no. 2 will close at 70% outdoor-air. Both switches are
field adjustable. As the outdoor-air damper opens, switch no.
1 closes, energizing a double-pole relay that starts fan no. 1.
As the outdoor-air damper continues to open, switch no. 2
will close, energizing a double-pole relay that starts fan no.
2. When the outdoor-air damper closes to a point below the
fan start points (30% fan no. 1, 70% fan no. 2), the respective
fan will be deenergized.
SERVICE
CAUTION: When servicing unit, shut off all elec-
trical power to unit to avoid shock hazard or injury
from rotating parts.
I. CLEANING
Inspect unit interior at the beginning of each heating and
cooling season or as operating conditions require.
A. Evaporator Coil
1. Turn unit power off and install lockout tag. Remove
evaporator coil access panel.
2. If EconoMi$er IV or accessory two-position damper is
installed, remove economizer or two-position damper
by disconnecting EconoMi$er IV plug and removing
mounting screws.
3. Slide filters out of unit.
4. Clean coil using a commercial coil cleaner or dish-
washer detergent in a pressurized spray canister.
Wash both sides of coil and flush with clean water.
For best results, back-flush toward return-air section
to remove foreign material.
Fig. 43 — Cleaning Condenser Coil
5. Flush condensate pan after completion.
6. Reinstall economizer or two-position damper and filters.
7. Reconnect wiring.
8. Replace access panels.
B. Condenser Coils
Inspect coils monthly. Clean condenser coils annually, and as
required by location and outdoor-air conditions.
Clean 2-row coils as follows:
1. Turn off unit power and install lockout tag.
2. Remove top panel screws on condenser end of unit.
Fig. 44 — Propping Up Top Panel
—41—
V. ECONOMI$ER IV ADJUSTMENT
Refer to Optional EconoMi$er IV section on page 13.
VI. REFRIGERANT CHARGE
Amount of refrigerant charge is listed on unit nameplate
(also refer to Table 1). Refer to Bryant Standard Service
Techniques Manual, Chapter 1, Refrigerants section.
Unit panels must be in place when unit is operating during
charging procedure.
A. No Charge
Locate and repair any refrigerant leak. Use standard evacu-
ating techniques. After evacuating system, weigh in the
specified amount of refrigerant (refer to Table 1).
B. Low Charge Cooling
Use Cooling Charging Charts, Fig. 47-50. Vary refrigerant until
the conditions of the appropriate chart are met. Note that charg-
ing charts are different from the type normally used. Charts are
based on charging the units to the correct superheat for the var-
ious operating conditions. Accurate pressure gage and tempera-
ture sensing device are required. Connect the pressure gage to
the service port on the suction line. Mount the temperature
sensing device on the suction line and insulate it so that outdoor
ambient temperature does not affect the reading. Indoor-air cfm
must be within the normal operating range of the unit.
Fig. 45 — Separating Coil Sections
C. Condensate Drain
Check and clean each year at start of cooling season. In win-
ter, protect against freeze-up.
D. Filters
Clean or replace at start of each heating and cooling season,
or more often if operating conditions require it. Replacement
filters must be same dimensions as original filters.
C. Perfect Humidity™ System Charging
The system charge for units with the Perfect Humidity option is
greater than that of the standard unit alone. The charge for
units with this option is indicated on the unit nameplate draw-
ing. Also refer to Fig. 51-53. To charge systems using the Perfect
Humidity dehumidification system, fully evacuate, recover and
recharge the system to the nameplate specified charge level.
E. Outdoor-Air Inlet Screen
Clean screen with steam or hot water and a mild detergent.
Do not use throwaway filters in place of screens.
II. LUBRICATION
A. Compressors
To check or adjust refrigerant charge on systems using the
Perfect Humidity Dehumidification system, charge per
Fig. 51-53.
Each compressor is charged with correct amount of oil from
the factory.
NOTE: When using the charging charts, it is important that
only the subcooling/reheat dehumidification coil liquid line
solenoid valve be energized. The subcooling/reheat dehumid-
ification coil liquid line solenoid valve MUST be energized to
use the charging charts and the outdoor motor speed control-
ler jumpered to run the fan at full speed.
B. Fan Motor Bearings
Fan motor bearings are permanently lubricated. No further
lubrication of condenser-fan or evaporator-fan motors is
required.
III. CONDENSER-FAN ADJUSTMENT (FIG. 46)
The charts reference a liquid pressure (psig) and tempera-
ture at
a
point between the condenser coil and the
1. Shut off unit power supply and install lockout tag.
2. Remove condenser-fan assembly (grille, motor, motor
cover, and fan) and loosen fan hub setscrews.
subcooling/reheat dehumidification coil. A tap is provided on
the unit to measure liquid pressure entering the subcooling/
reheat dehumidification coil.
3. Adjust fan height as shown in Fig. 46.
IMPORTANT: The subcooling mode charging charts
(Fig. 51-53) are to be used ONLY with units having the
optional Perfect Humidity dehumidification system. DO NOT
use standard charts (Fig. 47-50) for units with Perfect Humid-
ity option, and DO NOT use Fig. 51-53 for standard units.
4. Tighten setscrews and replace condenser-fan assembly.
D. To Use Cooling Charging Charts, Standard Units
Take the outdoor ambient temperature and read the suction
pressure gage. Refer to appropriate chart to determine what
the suction temperature should be. If suction temperature is
high, add refrigerant. If suction temperature is low, carefully
recover some of the charge. Recheck the suction pressure as
charge is adjusted.
UNIT VOLTAGE
208/230 v
460 v and 575 v
FAN HEIGHT “A” (in.)
2.75
3.50
Fig. 46 — Condenser-Fan Adjustment
EXAMPLE (Fig. 47):
Circuit 1
IV. BELT/PULLEY ADJUSTMENT
Outdoor Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . 85 F
Suction Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 psig
Suction Temperature should be . . . . . . . . . . . . . . . . . . 46 F
(Suction Temperature may vary ±5° F.)
Inspect once each season or sooner if conditions warrant,
verifying that belt tension and pulley alignment are correct.
Replace belt if required.
—42—
Fig. 47 — Cooling Charging Charts, Standard 551B090 Unit
Fig. 48 — Cooling Charging Charts, Standard 551B102 Unit
—43—
Fig. 49 — Cooling Charging Charts, Standard 551B120 Unit
Fig. 50 — Cooling Charging Charts, Standard 551B150 Unit
—44—
E. To Use Cooling Charging Charts, Units the Perfect
Humidity™ Dehumidification System
Refer to the charts (Fig. 51-53) to determine the proper leav-
ing condenser pressure and temperature.
EXAMPLE: (Fig. 51)
Circuit 1
Leaving Condenser Pressure . . . . . . . . . . . . . . . . . . . 300 psig
Leaving Condenser Temperature . . . . . . . . . . . . . . . . . .117 F
NOTE: When using the charging charts, it is important that
only the subcooling/reheat dehumidification coil liquid line
solenoid valve be energized. The subcooling/reheat dehumid-
ification coil liquid line solenoid valve MUST be energized to
use the charging charts and the outdoor motor speed control-
ler jumpered to run the fan at full speed.
VII. REPLACEMENT PARTS
A complete list of replacement parts may be obtained from
any Bryant distributor upon request.
NOTE: When using the charging charts, it is important that only the subcooling/
reheat dehumidification coil liquid line solenoid valve be energized. The subcool-
ing/reheat dehumidification coil liquid line solenoid valve MUST be energized to
use the charging charts and the outdoor motor speed controller jumpered to run
the fan at full speed.
Fig. 52 — Cooling Charging Chart, 581B102 and 120
With the Perfect Humidity Dehumidification System
NOTE: When using the charging charts, it is important that only the subcooling/
reheat dehumidification coil liquid line solenoid valve be energized. The subcool-
ing/reheat dehumidification coil liquid line solenoid valve MUST be energized to
use the charging charts and the outdoor motor speed controller jumpered to run
the fan at full speed.
Fig. 51 — Cooling Charging Chart, 581B090
With the Perfect Humidity Dehumidification System
NOTE: When using the charging charts, it is important that only the subcooling/
reheat dehumidification coil liquid line solenoid valve be energized. The subcool-
ing/reheat dehumidification coil liquid line solenoid valve MUST be energized to
use the charging charts and the outdoor motor speed controller jumpered to run
the fan at full speed.
Fig. 53 — Cooling Charging Chart, 581B150
With the Perfect Humidity Dehumidification System
—45—
TROUBLESHOOTING
I. UNIT TROUBLESHOOTING
Refer to Tables 30-32 for additional information.
Table 30 — Cooling Troubleshooting
PROBLEM
CAUSE
REMEDY
Compressor(s) and
Condenser Fan
Will Not Start.
Power failure.
Fuse blown or circuit breaker tripped.
Defective thermostat, contactor, transformer,
control relay.
Call power company.
Replace fuse or reset circuit breaker.
Replace component.
Insufficient line voltage.
Determine cause and correct.
Incorrect or faulty wiring.
Check wiring diagram and rewire correctly.
Lower thermostat setting below room temperature.
See problem “Excessive Head Pressure.”
Check system for leaks, repair, and recharge.
See problem “Suction Pressure Too Low.”
Check wiring and repair or replace.
Thermostat setting too high.
High pressure switch tripped.
Low pressure switch tripped.
Freeze-up protection thermostat tripped.
Faulty wiring or loose connections in compressor
circuit.
Compressor(s) Will Not
Start but Condenser Fan
Runs.
Compressor motor(s) burned out, seized, or internal
overload open.
Determine cause. Replace compressor(s).
Defective overload.
Determine cause and replace.
One leg of 3-phase power dead.
Refrigerant overcharge or undercharge.
Replace fuse or reset circuit breaker. Determine cause.
Recover refrigerant, evacuate system, and recharge
to nameplate.
Replace and determine cause.
Determine cause and correct.
Determine cause and correct.
Determine cause and replace.
Replace thermostat.
Compressor(s) Cycles
(Other Than Normally
Satisfying Thermostat).
Defective compressor.
Insufficient line voltage.
Blocked condenser.
Defective overload.
Defective thermostat.
Faulty condenser-fan motor(s) or capacitor.
Restriction in refrigerant system.
Dirty air filter.
Unit undersized for load.
Thermostat set too low.
Replace.
Locate restriction and remove.
Replace filter.
Decrease load or increase unit size.
Reset thermostat.
Compressor(s) Operates
Continuously.
Low refrigerant charge.
Leaking valves in compressor.
Air in system.
Condenser coil dirty or restricted.
Compressor(s) rotating in the wrong direction.
Locate leak, repair, and recharge.
Replace compressor.
Recover refrigerant, evacuate system, and recharge.
Clean coil or remove restriction.
Reverse the 3-phase power leads as described in
Start-Up section, page 38.
Scroll Compressor(s)
Makes Excessive Noise.
Excessive Head Pressure.
Dirty air filter.
Replace filter.
Dirty condenser coil.
Refrigerant overcharged.
Air in system.
Clean coil.
Remove excess refrigerant.
Recover refrigerant, evacuate system to 500 microns,
and recharge.
Condenser air restricted or air short-cycling.
Low refrigerant charge.
Compressor valves leaking.
Restriction in liquid tube.
High heat load.
Compressor valves leaking.
Refrigerant overcharged.
Dirty air filter.
Determine cause and correct.
Check for leaks, repair, and recharge.
Replace compressor(s).
Remove restriction.
Check for source and eliminate.
Replace compressor(s).
Head Pressure Too Low.
Excessive Suction
Pressure.
Recover excess refrigerant.
Replace filter.
Suction Pressure Too Low.
Low refrigerant charge.
Metering device or low side restricted.
Insufficient evaporator airflow.
Check for leaks, repair, and recharge.
Remove source of restriction.
Increase air quantity. Check filter and replace if
necessary.
Temperature too low in conditioned area.
Field-installed filter drier restricted.
Outdoor ambient temperature below 25 F.
Unit in economizer mode.
Reset thermostat.
Replace.
Install low-ambient kit.
Proper operation; no remedy necessary.
Compressor No. 2
Will Not Run.
—46—
Table 31 — Perfect Humidity™ Dehumidification System Subcooling Mode Service Analysis
PROBLEM
CAUSE
REMEDY
Subcooling Mode (Liquid Reheat)
Will Not Energize.
No power to control transformer from
evaporator-fan motor.
Check power source and evaporator-fan relay. Ensure all wire
connections are tight.
No power from control transformer to liquid 1. Fuse open; check fuse. Ensure continuity of wiring.
line solenoid valve.
2. Low-pressure switch open. Cycle unit off and allow low-
pressure switch to reset. Replace switch if it will not close.
3. Transformer bad; check transformer.
Liquid line solenoid valve will not operate. 1. Solenoid coil defective; replace.
2. Solenoid valve stuck open; replace.
Liquid line solenoid valve will not open.
Valve is stuck closed; replace valve.
Low System Capacity.
Low refrigerant charge or frosted evapora- 1. Check charge amount. Charge per Fig. 51-53.
tor coil.
2. Evaporator coil frosted; check and replace low-pressure
switch if necessary.
Loss of Compressor Superheat
Conditions with Subcooling/Reheat
Dehumidification Coil Energized.
Thermostatic expansion valve (TXV).
1. Check TXV bulb mounting, and secure tightly to suction line.
2. Replace TXV if stuck open or closed.
Table 32 — Perfect Humidity Dehumidification Hot Gas Reheat Mode Service Analysis
PROBLEM
CAUSE
REMEDY
Reheat Mode Will Not Energize.
No power to control transformer from
evaporator-fan motor.
Check power source and evaporator-fan relay. Ensure all wire
connections are tight.
No power from control transformer to hot
gas line solenoid valve.
1. Fuse open; check fuse. Ensure continuity of wiring.
2. Low-pressure switch open. Cycle unit off and allow low-
pressure switch to reset. Replace switch if it will not close.
3. Transformer bad; check transformer.
Hot gas line solenoid valve will not operate. 1. Solenoid coil defective; replace.
2. Solenoid valve stuck closed; replace.
Low refrigerant charge or frosted evapora- 1. Check charge amount. Charge per Fig. 51-53.
tor coil.
2. Evaporator coil frosted; check and replace low-pressure
switch if necessary.
Loss of Compressor Superheat
Conditions with Subcooling/Reheat
Dehumidification Coil Energized.
Thermostatic expansion valve (TXV).
1. Check TXV bulb mounting, and secure tightly to suction line.
2. Replace TXV if stuck open or closed.
Excessive Superheat.
Liquid line solenoid valve will not operate. Valve is stuck; replace valve.
Hot gas line solenoid valve will not close. Valve is stuck; replace valve.
—47—
II. ECONOMI$ER IV TROUBLESHOOTING
D. DCV (Demand Controlled Ventilation) and Power
Exhaust
See Table 33 for EconoMi$er IV logic.
To check DCV and Power Exhaust:
A functional view of the EconoMi$er IV is shown in Fig. 54.
Typical settings, sensor ranges, and jumper positions are
also shown. An EconoMi$er IV simulator program is avail-
able from Bryant to help with EconoMi$er IV training and
troubleshooting.
1. Make sure EconoMi$er IV preparation procedure has
been performed.
2. Ensure terminals AQ and AQ1 are open. The LED for
both DCV and Exhaust should be off. The actuator
should be fully closed.
A. EconoMi$er IV Preparation
3. Connect a 9-v battery to AQ (positive node) and AQ1
(negative node). The LED for both DCV and Exhaust
should turn on. The actuator should drive to between
90 and 95% open.
This procedure is used to prepare the EconoMi$er IV for
troubleshooting. No troubleshooting or testing is done by
performing the following procedure.
NOTE: This procedure requires a 9-v battery, 1.2 kilo-ohm
resistor, and a 5.6 kilo-ohm resistor which are not supplied
with the EconoMi$er IV.
4. Turn the Exhaust potentiometer CW until the
Exhaust LED turns off. The LED should turn off
when the potentiometer is approximately 90%. The
actuator should remain in position.
IMPORTANT: Be sure to record the positions of all potenti-
ometers before starting troubleshooting.
5. Turn the DCV set point potentiometer CW until the
DCV LED turns off. The DCV LED should turn off
when the potentiometer is approximately 9 v. The
actuator should drive fully closed.
1. Disconnect power at TR and TR1. All LEDs should be
off. Exhaust fan contacts should be open.
2. Disconnect device at P and P1.
3. Jumper P to P1.
6. Turn the DCV and Exhaust potentiometers CCW
until the Exhaust LED turns on. The exhaust con-
tacts will close 30 to 120 seconds after the Exhaust
LED turns on.
4. Disconnect wires at T and T1. Place 5.6 kilo-ohm
resistor across T and T1.
5. Jumper TR to 1.
6. Jumper TR to N.
7. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
7. If connected, remove sensor from terminals SO and +.
Connect 1.2 kilo-ohm 4074EJ M checkout resistor
across terminals SO and +.
E. DCV Minimum and Maximum Position
To check the DCV minimum and maximum position:
8. Put 620-ohm resistor across terminals SR and +.
1. Make sure EconoMi$er IV preparation procedure has
been performed.
9. Set minimum position, DCV set point, and exhaust
potentiometers fully CCW (counterclockwise).
2. Connect a 9-v battery to AQ (positive node) and AQ1
(negative node). The DCV LED should turn on. The
actuator should drive to between 90 and 95% open.
10. Set DCV maximum position potentiometer fully CW
(clockwise).
3. Turn the DCV Maximum Position potentiometer to
midpoint. The actuator should drive to between 20
and 80% open.
11. Set enthalpy potentiometer to D.
12. Apply power (24 vac) to terminals TR and TR1.
B. Differential Enthalpy
4. Turn the DCV Maximum Position potentiometer to
fully CCW. The actuator should drive fully closed.
To check differential enthalpy:
1. Make sure EconoMi$er IV preparation procedure has
been performed.
5. Turn the Minimum Position potentiometer to mid-
point. The actuator should drive to between 20 and
80% open.
2. Place 620-ohm resistor across SO and +.
6. Turn the Minimum Position Potentiometer fully CW.
The actuator should drive fully open.
3. Place 1.2 kilo-ohm resistor across SR and +. The Free
Cool LED should be lit.
7. Remove the jumper from TR and N. The actuator
should drive fully closed.
4. Remove 620-ohm resistor across SO and +. The Free
Cool LED should turn off.
8. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
5. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
F. Supply-Air Input
C. Single Enthalpy
To check supply-air input:
To check single enthalpy:
1. Make sure EconoMi$er IV preparation procedure has
been performed.
1. Make sure EconoMi$er IV preparation procedure has
been performed.
2. Set the Enthalpy potentiometer to A. The Free Cool
LED turns on. The actuator should drive to between
20 and 80% open.
2. Set the enthalpy potentiometer to A (fully CCW). The
Free Cool LED should be lit.
3. Set the enthalpy potentiometer to D (fully CW). The
Free Cool LED should turn off.
3. Remove the 5.6 kilo-ohm resistor and jumper T to T1.
The actuator should drive fully open.
4. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
—48—
4. Remove the jumper across T and T1. The actuator
should drive fully closed.
4. Set minimum position, DCV set point, and exhaust
potentiometers to previous settings.
5. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
5. Remove 620-ohm resistor from terminals SR and +.
6. Remove 1.2 kilo-ohm checkout resistor from termi-
nals SO and +. If used, reconnect sensor from termi-
nals SO and +.
G. EconoMi$er IV Troubleshooting Completion
This procedure is used to return the EconoMi$er IV to opera-
tion. No troubleshooting or testing is done by performing the
following procedure.
7. Remove jumper from TR to N.
8. Remove jumper from TR to 1.
1. Disconnect power at TR and TR1.
9. Remove 5.6 kilo-ohm resistor from T and T1. Recon-
nect wires at T and T1.
2. Set enthalpy potentiometer to previous setting.
10. Remove jumper from P to P1. Reconnect device at P
and P1.
3. Set DCV maximum position potentiometer to previ-
ous setting.
11. Apply power (24 vac) to terminals TR and TR1.
Table 33 — EconoMi$er IV Input/Output Logic
INPUTS
Enthalpy*
OUTPUTS
Compressor
N Terminal†
Demand Control
Ventilation (DCV)
Y1 Y2
Occupied
Minimum position
Unoccupied
Stage Stage
Outdoor
Return
1
2
Damper
Below set
(DCV LED Off)
High
Low
On On
On Off
Off Off
On On
On Off
Off Off
On On
On Off
Off Off
On On
On Off
Off Off
On
On
Off
On
Off
Off
On
On
Off
On
Off
Off
On
Off
Off
Off
Off
Off
On
Off
Off
Off
Off
Off
Closed
(Free Cooling LED Off)
Low
High
Low
High
Modulating** (between min.
position and full-open)
Modulating** (between
closed and full-open)
(Free Cooling LED On)
Minimum position
Modulating†† (between min.
position and DCV maximum)
Closed
Above set
(DCV LED On)
High
Modulating†† (between
closed and DCV
maximum)
(Free Cooling LED Off)
Low
Modulating***
Modulating†††
(Free Cooling LED On)
***Modulation is based on the greater of DCV and supply-air sensor
signals, between minimum position and either maximum position
(DCV) or fully open (supply-air signal).
†††Modulation is based on the greater of DCV and supply-air sensor
signals, between closed and either maximum position (DCV) or fully
open (supply-air signal).
*For single enthalpy control, the module compares outdoor enthalpy
to the ABCD set point.
†Power at N terminal determines Occupied/Unoccupied setting:
24 vac (Occupied), no power (Unoccupied).
**Modulation is based on the supply-air sensor signal.
††Modulation is based on the DCV signal.
Fig. 54 — EconoMi$er IV Functional View
—49—
INDEX
Access panels 14
Barometric flow capacity 16
Charging chart, refrigerant 43-45
Clearance 2, 5
Perfect Humidity™ dehumidification
system 11, 12, 21, 39-42, 45, 47
Physical data
Power supply
6
CO2 sensor
Wiring
7
Configuration 20
Settings 18, 20
Compressor
Pressure, drop
EconoMi$er IV 23
Electric heat 23
Perfect Humidity dehumidification 21
Pressure switches
Lubrication 42
Mounting 38
Rotation 38
High pressure
Low pressure
Pre-start-up 38
Refrigerant
6
6
Condensate drain
Cleaning 42
Location 2, 4
Condenser coil
Cleaning 41
Condenser fan
6
Charge 6, 42
Type
6
6
Refrigerant service ports 38
Replacement parts 45
Return air filter 6, 38
Return air temperature sensor 17
Rigging unit 2, 4
Adjustment 42
Control circuit
Wiring 11
Wiring raceway 11
Convenience outlet 13
Demand ventilation control 19
Dehumidification 20
Dimensions 3, 5
Roof curb
Assembly
1
Dimensions
3
Connector package
3
4
Ductwork
1
Leveling tolerances
EconoMi$er IV 13-20, 48, 49
Adjustment 42
Weight
6
Safety considerations
Safety relief 39
Service 41-45
1
Components 14
Damper movement 19
Wiring 15
Service ports 38
Electrical connections
Electrical data 8-10
Electric heaters 10
7
Slab mount
1
Start-up 38-41
Start-up checklist CL-1
Supply air temperature sensor 14
Thermostat 11
Enthalpy changeover set points 18
Evaporator coil
Cleaning 41
6
Troubleshooting 46-49
Ventilation 39
Evaporator fan motor
Lubrication 42
6
Weight
Corner
Motor data 22, 23
Performance 24-37
Pulley adjustment 22
Pulley setting 6, 22
5
EconoMi$er IV 5, 6
Perfect Humidity dehumidification
Unit 4-6
6
Speed
6
Wiring
Factory-installed options
Convenience outlet 13
Disconnect switch 11
EconoMi$er IV 13-20
Manual outdoor air damper 13
Perfect Humidity™ dehumidification
system 11, 12
EconoMi$er IV 15
Humidistat 12
Perfect Humidity system 12
Power connections
7
Filter
Cleaning 42
Installation 15
Size
6
Freeze protection thermostat
Heat anticipator settings 11
High flow valves 38
6
High pressure switch
Horizontal units 1, 2
Humidistat 12
6
Indoor air quality sensor 18
Low pressure switch
6
Manual outdoor air damper 13
Mounting
Unit
2
Non-fused disconnect switch 11
Operating sequence
Cooling 39
EconoMi$er IV 39
Heating 39
Perfect Humidity™ dehumidification
package 39-41
Outdoor air hood 13-15
Outdoor air temperature sensor 14
Outdoor air inlet screens
Cleaning 42
Copyright 2005 Bryant Heating & Cooling Systems
Printed in U.S.A.
CATALOG NO. 04-53551004-01
START-UP CHECKLIST
(Remove and Store in Job File)
I. PRELIMINARY INFORMATION
MODEL NO.: ______________________________________
DATE:_____________________________________________
BUILDING LOCATION: ____________________________
SERIAL NO.: ___________________________________________
TECHNICIAN: _________________________________________
II. PRE-START-UP (insert checkmark in box as each item is completed)
VERIFY J OBSITE VOLTAGE AGREES WITH VOLTAGE LISTED ON RATING PLATE
VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS
CHECK THAT ALL ELECTRICAL CONNECTIONS AND TERMINALS ARE TIGHT
CHECK THAT RETURN (INDOOR SECTION) AIR FILTERS ARE CLEAN AND IN PLACE
VERIFY THAT UNIT INSTALLATION IS LEVEL
CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING AND ORIFICE AND CHECK THAT
SETSCREW IS TIGHT
CHECK PULLEY ALIGNMENT AND BELT TENSION PER INSTALLATION INSTRUCTIONS
CHECK TO ENSURE THAT ELECTRICAL WIRING IS NOT IN CONTACT WITH REFRIGERANT LINES OR
SHARP METAL EDGES
III. START-UP
ELECTRICAL
SUPPLY VOLTAGE
L1-L2
L1
L1
L2-L3
L2
L2
L3-L1
L3
L3
CIRCUIT 1 COMPRESSOR AMPS
CIRCUIT 2 COMPRESSOR AMPS
EVAPORATOR FAN AMPS
L1
L2
L3
TEMPERATURES
OUTDOOR-AIR TEMPERATURE
RETURN-AIR TEMPERATURE
COOLING SUPPLY AIR
DB
WB
WB
WB
DB
DB
PRESSURES
REFRIGERANT SUCTION, CIRCUIT 1
REFRIGERANT SUCTION, CIRCUIT 2
REFRIGERANT DISCHARGE, CIRCUIT 1
REFRIGERANT DISCHARGE, CIRCUIT 2
PSIG AT
PSIG AT
PSIG AT
PSIG AT
F (AT SERVICE PORT)
F (AT SERVICE PORT)
F (CONDENSER LIQUID LINE OUTLET TUBE)
F (CONDENSER LIQUID LINE OUTLET TUBE)
VERIFY THAT 3-PHASE SCROLL COMPRESSOR IS ROTATING IN THE CORRECT DIRECTION
VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS ON PAGES 43-45.
Copyright 2005 Bryant Heating & Cooling Systems
Printed in U.S.A.
CL-1
CATALOG NO. 04-53551004-01
|
Brother UTILISATEUR MFC 9030 User Manual
Bunn JDF 2 User Manual
Chromalox UB 2002E User Manual
Dakota Digital LED Tail Lights for 1973 74 Nova LAT NR380 User Manual
Energizer E95 User Manual
Epson Stylus Printer CX6400 User Manual
Fisher Price B7275 User Manual
Friedrich SL28M30 User Manual
GE AZ58H09DAD User Manual
Haier ESA412K User Manual