Bryant COMMERCIAL AIR COOLED CONDENSING UNITS 576b User Manual

installation, start-up and  
service instructions  
COMMERCIAL AIR-COOLED  
CONDENSING UNITS  
569C  
576B  
Cancels: II 569C-72-4  
II 569C-72-5  
8/15/00  
IMPORTANT — READ BEFORE INSTALLING  
1. Read and become familiar with these installation  
instructions before installing this unit (Fig. 1).  
2. Be sure the installation conforms to all applicable  
local and national codes.  
3. These instructions contain important information for  
the proper maintenance and repair of this equipment.  
Retain these instructions for future use.  
CONTENTS  
Page  
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1  
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-8  
I. Locate the Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
II. Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
III. Compressor Mounting. . . . . . . . . . . . . . . . . . . . . . . . 2  
IV. Unit Refrigerant Piping Connections. . . . . . . . . . . . 2  
V. Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . 5  
VI. Accessory Installation. . . . . . . . . . . . . . . . . . . . . . . . 8  
Fig. 1 — Typical Unit (569C072 Shown)  
Recognize safety information. This is the safety-alert sym-  
bol. ( ) When you see this symbol on the unit and in  
instructions or manuals, be alert to the potential for per-  
sonal injury.  
PRE-START-UP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8  
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9  
I. Start-Up and Adjustments . . . . . . . . . . . . . . . . . . . . 9  
CARE AND MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . 9  
Understand the signal words — DANGER, WARNING, and  
CAUTION. These words are used with the safety-alert sym-  
bol. Danger identifies the most serious hazards which will  
result in severe personal injury or death. Warning indicates  
a condition that could result in personal injury. Caution is  
used to identify unsafe practices which would result in minor  
personal injury or product and property damage.  
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-12  
I. Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
II. Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
III. Condenser-Fan Adjustment . . . . . . . . . . . . . . . . . . 10  
IV. Capacity Control . . . . . . . . . . . . . . . . . . . . . . . . . . . 11  
V. Compressor Removal . . . . . . . . . . . . . . . . . . . . . . . 11  
VI. Crankcase Heater . . . . . . . . . . . . . . . . . . . . . . . . . . 11  
VII. Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . 11  
VIII. Refrigerant Service Ports . . . . . . . . . . . . . . . . . . . . 12  
IX. High Flow Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . 12  
WARNING: Before performing service or mainte-  
nance operations on unit, turn off main power switch  
to unit. Electrical shock could cause personal injury.  
TROUBLESHOOTING GUIDE . . . . . . . . . . . . . . . . . . . . . 13,14  
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . CL-1, CL-2  
1. The power supply (volts, hertz, and phase) must cor-  
respond to that specified on unit rating plate.  
SAFETY CONSIDERATIONS  
2. The electrical supply provided by the utility must be  
sufficient to handle load imposed by this unit.  
WARNING: Improper installation, adjustment,  
alteration, service, maintenance, or use can cause  
explosion, fire, electric shock, or other occurrences  
which may injure you or damage your property. Con-  
sult a qualified installer or service agency for informa-  
tion or assistance. The qualified installer or agency  
must use only factory-authorized kits or accessories  
when repairing this product.  
3. Refer to the Locate the Unit section on page 2 and  
Fig. 2 and 3 for locations of electrical inlets, required  
clearances, and weight distribution based on recom-  
mended support points before setting unit in place.  
4. This installation must conform with local building  
codes. Refer to local plumbing or wastewater codes  
and other applicable local codes.  
Table 1 — Physical Data  
UNIT  
569C072  
569C090  
569C120  
576B090  
576B102  
576B120  
1
1
1
NOMINAL CAPACITY (tons)  
6
7 /  
10  
7 /  
8 /  
10  
2
2
2
OPERATING WEIGHT (lb)  
Aluminum Coils (Std)  
Copper Coils (Optional)  
340  
386  
392  
460  
426  
503  
510  
578  
564  
632  
564  
632  
RIGGING WEIGHT (lb)  
Aluminum Coils (Std)  
Copper Coils (Optional)  
390  
436  
420  
488  
445  
522  
560  
628  
614  
682  
614  
682  
REFRIGERANT*  
Operating Charge†  
Typical (lb)  
R-22  
11.4  
2.0  
13.6  
2.0  
16.5  
2.0  
14.3  
2.0  
16.4  
2.0  
16.4  
2.0  
Shipping Charge (lb)  
Reciprocating,  
Hermetic  
COMPRESSOR  
Scroll, Hermetic  
Reciprocating, Semi-Hermetic  
1...06DH824  
(See Note)  
6
Qty...Type  
1...H26A72Q  
1...ZR94KC  
1...ZR125KC  
1...06DA818  
1...06DA824  
Qty Cylinders (ea)  
Speed (rpm)  
Oil Charge (oz) (ea)  
2
NA  
3500  
85  
NA  
3500  
110  
4
6
3500  
65  
1750  
88  
1750  
128  
1750  
128  
CONDENSER AIR FAN  
Qty...Rpm  
Propeller; Direct Drive  
1...850  
1...1100  
1...1100  
1...1100  
26  
1...1100  
1...1100  
Diameter (in.)  
26  
26  
26  
26  
26  
1
3
3
3
3
3
Motor Hp (NEMA)  
/
/
/
/
/
/
3
4
4
4
4
4
Watts  
Nominal Cfm Total  
444  
3800  
976  
6500  
960  
7000  
930  
6500  
930  
6500  
930  
6500  
CONDENSER COIL  
Rows...Fins/in.  
Enhanced Copper Tubes, Aluminum Lanced Fins  
2...17  
Face Area (sq ft)  
12.24  
11.26  
18.0  
20.50  
18.87  
18.0  
18.0  
16.56  
18.0  
16.56  
Storage Capacity (lb)**  
16.56  
16.56  
CONNECTIONS (sweat)  
Suction (in.)  
Liquid (in.)  
1
1
1
1
1
1
1 /  
1 /  
1 /  
1 /  
1 /  
1 /  
8
8
8
8
8
8
1
1
5
1
5
5
/
/
/
/
/
/
2
2
8
2
8
8
CONTROLS  
Pressurestat Settings (psig)  
High Cutout  
Cut-in  
Low Cutout  
Cut-in  
426  
7
320 20  
7
22  
3
5
LEGEND  
**Storage capacity of condenser coil with coil 80% full of liquid R-22 at  
124 F.  
NOTE: Unit 576B120 has one step of unloading. Full load is 100% of  
capacity, and one step of unloading is 67% capacity. Unit 576B120 has  
the following unloader settings: load is 70 1 psig and unload is 60  
2 psig.  
NEMA — National Electrical Manufacturers Association  
*Unit is factory supplied with holding charge only.  
Typical operating charge with 25 ft of interconnecting piping.  
3—  
DIMENSIONS (ft-in.)  
ELECTRICAL CONNECTIONS  
CONNECTION SIZES  
UNIT  
A
B
C
D
E
F
3
AA  
BB  
CC  
DD  
1 / Dia Field Power Supply Hole  
8
With Aluminum Coils (Standard)  
2Dia Power Supply Knockout  
1
3
1
5
5
569C072  
569C090  
569C120  
576B090  
576B102  
576B120  
1-6 /  
1-8  
1-9  
1-6  
1-7  
1-7  
1-2 /  
1-2 /  
1-4 /  
2-9 /  
2
4
2
4
16  
16  
16  
16  
16  
16  
16  
1
2 / Dia Power Supply Knockout  
2
1
13  
5
7
1-6 /  
2-9  
/
1-3  
1-3  
1-3  
1-3  
1-3  
2- /  
3-5 /  
16  
16  
7
/ Dia Field Control Wiring Hole  
8
5
7
1-8  
2-0  
2- /  
3-5 /  
16  
16  
16  
16  
SERVICE VALVE CONNECTIONS  
3
13  
5
7
1-4 /  
2-9  
/
2- /  
3-5 /  
4
16  
16  
16  
13  
13  
5
7
UNIT  
SUCTION  
LIQUID  
1-5  
1-5  
2-9  
2-9  
/
/
2- /  
3-5 /  
1
1
1
5
1
5
5
569C072  
569C090  
569C120  
576B090  
576B102  
576B120  
1 / ″  
/ ″  
5
7
8
2
2- /  
3-5 /  
1
1 / ″  
/ ″  
8
2
With Copper Coils (Optional)  
1
1 / ″  
/ ″  
8
8
1
5
5
569C072  
569C090  
569C120  
576B090  
576B102  
576B120  
1-8  
1-3  
1-6  
1-7  
1-2 /  
1-3  
1-3  
1-3  
1-3  
1-3  
1-4 /  
2-9 /  
4
16  
16  
16  
16  
16  
16  
16  
1
1 / ″  
/ ″  
8
2
1
13  
5
7
1-9 /  
2-9  
/
2- /  
3-5 /  
2
16  
16  
1
1 / ″  
/ ″  
8
8
5
7
1-10  
2-0  
2- /  
3-5 /  
1
16  
16  
16  
16  
1 / ″  
/ ″  
8
8
1
1
13  
5
7
1-7 /  
1-4 /  
2-9  
/
2- /  
3-5 /  
2
2
2
2
16  
16  
16  
WEIGHT CHART (lb)  
1
13  
13  
5
7
1-7 /  
1-4  
1-4  
2-9  
2-9  
/
/
2- /  
3-5 /  
STD UNIT  
CORNER W  
CORNER X  
Al  
1
5
7
UNIT  
1-7 /  
2- /  
3-5 /  
Al  
Cu  
Al  
Cu  
Cu  
569C072  
569C090  
569C120  
576B090  
576B102  
576B120  
340  
392  
426  
510  
564  
564  
386  
460  
503  
578  
632  
632  
86  
91  
106  
120  
126  
143  
161  
161  
53  
84  
99  
89  
97  
97  
65  
100  
126  
106  
114  
114  
96  
114  
133  
133  
CORNER Y  
CORNER Z  
UNIT  
Al  
Cu  
Al  
Cu  
569C072  
569C090  
569C120  
576B090  
576B102  
576B120  
77  
105  
117  
133  
141  
141  
82  
113  
127  
142  
150  
150  
124  
113  
113  
173  
193  
193  
133  
127  
127  
187  
207  
207  
NOTE: Al indicates weight with aluminum-fin coil (standard);  
Cu indicates weight with copper-fin coil (optional).  
NOTES:  
1. Dimensions in [ ] are in millimeters.  
2.  
3.  
Center of Gravity. See chart for dimensions.  
Direction of airflow.  
4. Minimum clearance (local codes or jurisdiction may prevail):  
a. Bottom to combustible surfaces, 0 inches.  
b. Either left or rear side of condensing unit must have 36-in. clearance for proper airflow;  
the remaining side(s) must have 12-in. clearance each.  
c. Overhead, 60 in., to assure proper condenser fan operation.  
d. Between units, control box side, 42 in. per NEC (National Electrical Code).  
e. Between unit and ungrounded surfaces, control box side, 36 in. per NEC.  
f. Between unit and block or concrete walls and other grounded surfaces, control box side,  
42 in. per NEC.  
5. With the exception of the clearance for the condenser coil as stated in Note 4b, a removable  
fence or barricade requires no clearance.  
6. Units may be installed on combustible floors made from wood or Class A, B, or C roof cover-  
ing material.  
7. Certified dimension drawings available on request.  
Fig. 2 — Base Unit Dimensions  
4—  
Table 2 — Refrigerant Piping Sizes  
LINEAR LENGTH OF PIPING — FT (M)  
NOTICE TO RIGGERS  
HOOK RIGGING SHACKLES THROUGH HOLES IN BASE RAIL, ON ALL FOUR SIDES.  
HOLES IN BASE RAILS ARE CENTERED AROUND THE UNIT CENTER OF GRAVITY. USE  
WOODEN TOP SKID, WHEN RIGGING, TO PREVENT RIGGING STRAPS FROM DAMAGING  
UNIT.  
CAUTION: ALL PANELS MUST BE IN PLACE WHEN RIGGING.  
0-25  
25-50  
(7.6-15.2)  
50-75  
(15.2-22.9)  
75-100  
(0-7.6)  
(22.9-30.5)  
UNIT  
Line Size (in. OD)  
L
S
L
S
L
S
L
S
1
1
5
1
5
5
1
1
1
1
1
1
1
569C072  
569C090  
569C120  
576B090  
576B102  
576B120  
/
/
/
/
/
/
1 /  
/
/
/
/
/
/
1 /  
/
/
/
/
/
/
1 /  
/
/
/
/
/
/
1 /  
2
2
8
2
8
8
8
8
8
8
8
8
2
2
8
2
8
8
8
8
8
8
8
8
2
8
8
8
8
8
8
8
8
8
8
8
2
8
8
8
8
8
8
8
8
8
8
8
1
1
5
1
5
5
1
5
5
5
5
5
1
5
5
5
5
5
3
1 /  
1 /  
1 /  
1 /  
1
3
3
3
1 /  
1 /  
1 /  
1 /  
1
1
1
3
1 /  
1 /  
1 /  
1 /  
1
1
3
3
1 /  
1 /  
1 /  
1 /  
1
1
3
3
1 /  
1 /  
1 /  
1 /  
LEGEND  
L — Liquid Line  
S — Suction Line  
NOTES:  
1. Pipe sizes are based on a 2° F (1° C) loss for liquid and suction  
lines.  
2. Pipe sizes are based on the maximum linear length shown for  
each column, plus a 50% allowance for fittings.  
3. Charge units with R-22 in accordance with unit installation  
instructions.  
RIGGING WEIGHT*  
A
B
C
UNIT  
lb  
kg  
in. mm in. mm in. mm  
45.0 1143 38.5 978 35.5 904  
45.0 1143 38.5 978 43.5 1105  
45.0 1143 38.5 978 43.5 1105  
45.0 1143 38.5 978 43.5 1105  
45.0 1143 38.5 978 43.5 1105  
45.0 1143 38.5 978 43.5 1105  
569C072  
569C090  
569C120  
576B090  
576B102  
576B120  
390  
420  
445  
560  
614  
614  
177  
192  
203  
255  
280  
280  
Table 3 — Liquid Line Data  
LIQUID LINE  
MAX  
ALLOWABLE  
LIQUID LIFT  
Max Allowable  
Pressure Drop  
Max Allowable  
Temp Loss  
UNIT  
Ft  
86  
60  
70  
60  
65  
65  
M
psi  
7
7
7
7
kPa  
48.3  
48.3  
48.3  
48.3  
48.3  
48.3  
F
2
2
2
2
2
2
C
1
1
1
1
1
1
*Weights are for aluminum coils.  
569C072  
569C090  
569C120  
576B090  
576B102  
576B120  
26.2  
18.3  
21.3  
18.3  
19.8  
19.8  
Fig. 3 — Rigging Label  
7
7
NOTE: Values shown are for units operating at 45 F (7.2 C) saturated  
suction and 95 F (35 C) entering air.  
V. ELECTRICAL CONNECTIONS  
WARNING: The unit cabinet must have an  
uninterrupted, unbroken electrical ground to minimize  
the possibility of personal injury if an electrical fault  
should occur. This ground may consist of electrical wire  
connected to the unit ground lug in the control  
compartment or conduit approved for electrical ground  
when installed in accordance with the NEC and local  
electrical codes. Failure to adhere to this warning could  
result in personal injury.  
Fig. 4 — Typical Compressor Mounting (576B Units)  
B. Filter Drier and Moisture Indicator  
CAUTION: Failure to follow these precautions  
could result in damage to the unit being installed:  
The filter drier is factory installed. Moisture indicator is a  
field-installed accessory and should be installed just after  
liquid line shutoff valve at the evaporator coil. Do not use a  
receiver. A receiver is not supplied with the unit and should  
not be used.  
A. Field Power Supply (Fig. 5-7)  
1. Make all electrical connections in accordance with  
NEC ANSI/NFPA (American National Standards  
Institute/ National Fire Protection Association) 70,  
latest edition, and local electrical codes governing  
such wiring. Refer to unit wiring diagram.  
NOTE: Unit is shipped with R-22 holding charge. System  
pressure must be relieved before removing caps. Recover  
refrigerant prior to brazing.  
Pass nitrogen or other inert gas through piping while braz-  
ing to prevent formation of copper oxide.  
2. Use only copper or copper-clad conductor fan connec-  
tions between field-supplied electrical disconnect  
switch and unit. DO NOT USE ALUMINUM WIRE.  
Maximum wire size is no. 2 AWG (American Wire  
Gage).  
Install field-supplied thermostatic expansion valve(s) in  
evaporator section. It is r ecom m en d ed that a field supplied  
liquid line solenoid be positioned in the main liquid line  
(near the evaporator coil). It should be wired to close when  
compressor stops to minimize refrigerant migration during  
the OFF cycle.  
3. Voltage to compressor terminals during operation  
must be within voltage range indicated on unit name-  
plate (also see Table 4). On 3-phase units, voltages  
between phases must be balanced within 2% and  
5—  
the current within 10%. Use the formula shown in  
Table 4, Note 2, to determine the percent voltage  
imbalance. Operation on improper line voltage or  
excessive phase imbalance constitutes abuse and may  
cause damage to electrical components. Such opera-  
tion would invalidate any applicable warranty.  
4. Insulate low-voltage wires for highest voltage con-  
tained within conduit when low-voltage control wires  
are run in same conduit as high-voltage wires.  
5. Do not damage internal components when drilling  
through any panel to mount electrical hardware, con-  
duit, etc.  
All units except 208/230-v units are factory wired for the  
voltage shown on the nameplate. If the 208/230-v unit is to  
be connected to a 208-v power supply, the transformer must  
be rewired by moving the black wire from the 230-v terminal  
on the transformer and connecting it to the 200-v terminal  
on the transformer.  
LEGEND  
Contactor  
C
NEC  
National Electrical Code  
Field Wiring  
Factory Wiring  
Refer to unit label diagram for additional information.  
Pigtails are provided for field wire connections. Use factory-  
supplied splices or UL (Underwriters’ Laboratories)  
approved copper/aluminum connector.  
Splice Connection (Factory Supplied)  
Fig. 5 — Power Wiring Connections  
insulated wire (35 C minimum). For over 75 ft, use no. 14  
AWG insulated wire (35 C minimum). All wire larger than  
no. 18 AWG cannot be directly connected to the thermostat  
and will require a junction box and splice at the thermostat.  
When installing units, provide a disconnect per NEC. All  
field wiring must comply with NEC and local requirements.  
Install field wiring as follows:  
1. Install conduit through side panel openings.  
1. Connect thermostat wires to screw terminals of low  
voltage connection board.  
2. Install power lines to terminal connections as shown  
in Fig. 5.  
2. Pass the control wires through the hole provided in  
the corner post. See Fig. 7.  
B. Control Voltage Connections  
3. Feed wire through raceway built into the corner post  
and into the 24-v thermostat connection board. The  
24-v thermostat connection is located on the left side  
of the low voltage connection compartment. The race-  
way provides the UL required clearance between the  
high- and low-voltage wiring.  
Install an accessory thermostat assembly according to instal-  
lation instructions included with the accessory. Locate ther-  
mostat assembly on a solid wall in the conditioned space to  
sense average temperature in accordance with thermostat  
installation instructions.  
Route thermostat cable or equivalent single leads of colored  
wire from subbase terminals to low-voltage connections on  
unit (shown in Fig. 6) as described in Steps 1 through 4 below.  
4. Total combined amperage draw of the field-installed  
liquid line solenoid valve and indoor fan contactor  
must not exceed 22 va. If the specified va must be  
exceeded, use a remote relay to switch the load.  
NOTE: For wire runs up to 50 ft, use no. 18 AWG insulated  
wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG  
LEGEND  
AHA — Adjustable Heat Anticipator  
LLSV  
LPS  
TB  
Liquid Line Solenoid Valve  
Low-Pressure Switch  
Ter minal Block  
Terminal (Marked)  
Spice  
Factory Wiring  
Field Control Wiring  
To Indicate Common Potential Only,  
Not To Represent Wiring  
C
Contactor, Compressor  
Circuit Breaker  
CB  
CC  
Cooling Compensator  
TC  
Thermostat-Cooling  
Time-Delay Relay  
CLO — Compressor Lockout  
HPS — High-Pressure Switch  
TDR  
TH  
Thermostat-Heating  
IFC  
Indoor (Evaporator) Fan Contactor  
TRAN — Transformer  
Fig. 6 — Typical Control Wiring Connections (569C Shown)  
801  
6—  
Table 4 — Electrical Data  
VOLTAGE RANGE  
COMPRESSOR  
OFM  
FLA  
POWER SUPPLY  
NOMINAL VOLTAGE  
(V-Ph-Hz)  
UNIT  
Min  
Max  
RLA  
LRA  
MCA  
MOCP  
208/230-3-60  
460-3-60  
575-3-60  
187  
414  
518  
254  
508  
632  
21.8  
10.0  
9.0  
158  
79  
65  
1.9  
1.0  
1.9  
30.1  
13.5  
14.1  
40  
20  
20  
569C072  
208/230-3-60  
460-3-60  
187  
414  
518  
187  
414  
518  
254  
508  
632  
254  
508  
632  
28.8  
14.7  
10.8  
37.8  
17.2  
14.3  
195  
95  
3.8  
1.9  
1.9  
3.1  
1.4  
1.4  
39.8  
20.3  
15.4  
51.1  
23.4  
19.8  
50  
25  
20  
70  
30  
25  
569C090  
569C120  
575-3-60  
80  
208/230-3-60  
460-3-60  
575-3-60  
239  
125  
90  
208/230-3-60  
380-3-60  
187  
342  
414  
518  
187  
342  
414  
518  
187  
342  
414  
518  
254  
418  
508  
632  
254  
418  
508  
632  
254  
418  
508  
632  
31.5  
19.0  
15.7  
12.6  
39.7  
24.0  
19.9  
15.9  
39.7  
24.0  
19.9  
15.9  
160  
75  
3.1  
2.2  
1.4  
1.4  
3.1  
2.2  
1.4  
1.4  
3.1  
2.2  
1.4  
1.4  
42.5  
26.0  
21.0  
17.2  
52.7  
32.2  
26.3  
21.3  
52.7  
32.2  
26.3  
21.3  
50  
35  
25  
20  
70  
40  
35  
25  
70  
40  
35  
25  
576B090  
576B102  
576B120  
460-3-60  
80  
575-3-60  
64  
208/230-3-60  
380-3-60  
460-3-60  
575-3-60  
208/230-3-60  
380-3-60  
460-3-60  
575-3-60  
198  
93  
99  
79  
198  
93  
99  
79  
LEGEND  
EXAMPLE: Supply voltage is 460-3-60.  
AB = 452 v  
CSA  
FLA  
Canadian Standards Association  
Full Load Amps  
BC = 464 v  
AC = 455 v  
HACR  
LRA  
MCA  
Heating, Air Conditioning and Refrigeration  
Locked Rotor Amps  
452 + 464 + 455  
3
Average Voltage  
=
Minimum Circuit Amps  
MOCP — Maximum Overcurrent Protection  
NEC  
OFM  
RLA  
UL  
National Electrical Code  
Outdoor (Condenser) Fan Motor  
Rated Load Amps  
1371  
3
=
=
Underwriters’ Laboratories  
457  
(AB) 457 – 452 = 5 v  
(BC) 464 – 457 = 7 v  
(AC) 457 – 455 = 2 v  
Maximum deviation is 7 v.  
Determine percent of voltage imbalance:  
7
457  
NOTES:  
% Voltage Imbalance  
=
=
100 x  
1. In compliance with NEC requirements for multimotor and combina-  
tion load equipment (refer to NEC Articles 430 and 440), the over-  
current protective device for the unit shall be fuse or HACR breaker.  
The Canadian units may be fuse or circuit breaker.  
1.53%  
This amount of phase imbalance is satisfactory as it is below the maxi-  
mum allowable 2%.  
2. Unbalanced 3-Phase Supply Voltage  
Never operate a motor where a phase imbalance in supply voltage is  
greater than 2%. Use the following formula to determine the percent  
of voltage imbalance.  
IMPORTANT: If the supply voltage phase imbalance is more than 2%,  
contact your local electric utility company immediately.  
3. The 575-v units are CSA only.  
% of Voltage Imbalance =  
4. The 380-v units are not UL or CSA listed.  
max voltage deviation from average voltage  
100 x  
average voltage  
7—  
PRE-START-UP  
WARNING: Failure to observe the following warn-  
ings could result in serious personal injury:  
1. Follow recognized safety practices and wear  
protective goggles when checking or servicing  
refrigerant system.  
2. Do not operate compressor or provide any elec-  
tric power to unit unless compressor terminal  
cover is in place and secured.  
3. Do not remove compressor terminal cover until  
all electrical sources have been disconnected.  
4. If refrigerant leak is suspected around compres-  
sor terminals, recover refrigerant whenever  
possible and relieve all pressure from system  
before touching or disturbing anything inside  
terminal box.  
5. Never attempt to repair soldered connection  
while refrigerant system is under pressure.  
6. Do not use torch to remove any component.  
System contains oil and refrigerant under  
pressure. To remove a component, wear protec-  
tive goggles and proceed as follows:  
Fig. 7 — Field Control Wiring Raceway  
(576B Unit Shown)  
a. Shut off electrical power to unit.  
b. Recover refrigerant. Relieve all pressure  
from system.  
VI. ACCESSORY INSTALLATION  
c. Cut component-connecting tubing with tub-  
ing cutter and remove component from unit.  
At this time any required accessories should be installed on  
the unit. Refer to Table 5 for available accessories. Control  
wiring information is provided in the unit wiring book.  
d. Carefully unsweat remaining tubing stubs  
when necessary. Oil can ignite when exposed  
to torch flame.  
Table 5 — Accessory List  
ACCESSORY  
Proceed as follows to inspect and prepare the unit for initial  
start-up:  
Gage Panel  
Winter-Start Relay Package  
Weatherprobe™ II Low Ambient Kit  
Hail Guard Package (072)  
Hail Guard Package (090,102,120)  
Thermostats  
1. Field electrical power source must agree with unit  
nameplate rating.  
2. Check voltage imbalance as shown in Table 4, Note 2.  
Subbase  
3. Check that all internal wiring connections are tight  
and that all barriers, covers, and panels are in place.  
4. Ensure all service valves are open. On 576B units, be  
sure all compressor service valves are backseated.  
5. Verify that compressor holddown bolts have been  
loosened and that flat/snubber washers can be  
rotated by applying finger pressure (snug, but not  
tight).  
6. On 569C and 576B units, verify compressor crank-  
case heater is securely in place. Crankcase heater  
must operate for a least 24 hours before start-up.  
7. Note that compressor oil level is visible in the sight  
glass (576B units only).  
8. Check for leaks in refrigerant system by using soap  
bubbles and/or electronic leak detector.  
9. Check that liquid line solenoid valve is located at  
evaporator coil as shown in Filter Drier and Moisture  
Indicator section, page 5.  
10. Check that both outdoor and indoor units are prop-  
erly mounted in accordance with installation instruc-  
tions and applicable codes.  
8—  
START-UP  
thermostat is also energized, allowing the field-supplied  
and -installed (24v) indoor (evaporator) fan contactor to func-  
tion. A field-supplied and -installed liquid line valve (con-  
nected between Terminals G and C at the outdoor unit), will  
also open. This allows the system to function in cooling; the  
LPS will not open if compressor is not running. As cooling  
demand is satisfied, the thermostat contacts break, deener-  
gizing the contactor causing the system to shut off. The liq-  
uid line solenoid (LLS) valve closes, minimizing the potential  
for refrigerant migration at this time. The compressor does  
not restart until the thermostat again calls for cooling. If a  
demand for cooling occurs within 5 minutes after the ther-  
mostat is satisfied, the system will not restart due to the fea-  
ture of Time Guard II device. After the 5-minute time period,  
the system will restart as normal upon thermostat demand.  
I. START-UP AND ADJUSTMENTS  
CAUTION: Complete the required procedures  
given in the Pre-Start-Up section and unit start-up  
checklist at the end of this publication before starting  
the unit. Do not jumper any safety devices when oper-  
ating the unit.  
Do not operate the compressor when the outdoor tem-  
perature is below 25 F (24 C) (unless accessory low  
ambient kit is installed).  
A. Checking Cooling Control Operation  
Start and check the unit for proper cooling control operation  
as follows:  
The system is protected with a Cycle-LOC device so that the  
compressor will not start if a high-pressure or low-pressure  
fault occurs. To reset the Cycle-LOC device, set the thermo-  
stat to eliminate the cooling demand then return to the orig-  
inal set point. This should be done only once, and if system  
shuts down due to the same fault, determine the problem  
before attempting to reset the Cycle-LOC device.  
1. Place room thermostat SYSTEM switch in OFF posi-  
tion. Observe that blower motor starts when FAN  
switch is placed in ON position and shuts down when  
FAN switch is placed in AUTO. position.  
2. Place SYSTEM switch in COOL position and FAN  
switch in AUTO. position. Set cooling control below  
room temperature. Observe that compressor and con-  
denser- and evaporator-fan motors start. Observe  
that cooling cycle shuts down when control setting is  
satisfied.  
The crankcase heaters must be energized for a minimum of  
24 hours before starting a 569C and 576B unit.  
D. Oil Charge  
576B Units  
Allow unit to run for about 20 minutes. Stop unit and check  
compressor oil level. Add oil only if necessary to bring oil into  
view in sight glass. Use only approved compressor oil.  
B. Unit Controls  
All units have the following internal-protection controls:  
Compressor Overload  
Approved oils are:  
This overload interrupts power to the compressor when  
either the current or internal motor winding temperature  
become excessive, and automatically resets when the inter-  
nal temperature drops to a safe level. This overload may  
require up to 60 minutes (or longer) to reset. If the internal  
overload is suspected of being open, disconnect the electrical  
power to the unit and check the circuit through the overload  
with an ohmmeter or continuity tester.  
Suniso 3GS  
WF32-150  
If oil is added, run unit for an additional 10 minutes. Stop  
unit and check oil level. If level is still low, add oil only after  
determining that piping system is designed for proper oil  
return and that system is not leaking oil.  
569C Units  
Time Guard® II Device  
The 569C units do not have a sight glass and are factory  
charged with the correct amount of oil.  
The unit is equipped with accessory Time Guard II recycle  
timer. The device will cause a 5-minute delay between com-  
pressor starts.  
All Units  
Do not reuse drained oil or use any oil that has been exposed  
to the atmosphere. Procedures for adding or removing oil are  
given in the Standard Service Techniques Manual, Chapter  
1, Refrigerants.  
Cycle-LOC™ Device  
When high-pressure or low-pressure fault occurs, the Cycle-  
LOC device will protect the system by not allowing the com-  
pressor to start.  
CARE AND MAINTENANCE  
Low-Pressure Switch/ (LPS)  
To ensure continuing high performance and to minimize the  
possibility of premature equipment failure, periodic mainte-  
nance must be performed on this equipment. This cooling  
unit should be inspected at least once each year by a quali-  
fied service person.  
When the suction line pressure drops below 7 psig (48 kPa),  
the LPS opens 24-v power to the compressor contactor and  
stops the compressor. When the pressure reaches 22 psig  
(152 kPa), the switch resets and the compressor is allowed to  
restart.  
NOTE TO EQUIPMENT OWNER: Consult your local dealer  
about the availability of a maintenance contract.  
High-Pressure Switch (HPS)  
When the refrigerant high-side pressure reaches 426 psig  
(2937 kPa), the HPS opens 24-v power to the compressor con-  
tactor and stops the compressor. When the pressure drops to  
320 psig (2206 kPa), the switch resets and the compressor is  
allowed to restart.  
WARNING: The ability to properly perform main-  
tenance on this equipment requires certain expertise,  
mechanical skills, tools, and equipment. If you do not  
possess these, do not attempt to perform any mainte-  
nance on this equipment other than those procedures  
recommended in the Users Manual. FAILURE TO  
HEED THIS WARNING COULD RESULT IN SERI-  
OUS PERSONAL INJ URY AND POSSIBLE DAM-  
AGE TO THIS EQUIPMENT.  
C. Sequence of Operation  
At start-up, the thermostat calls for cooling. When all  
safety devices are satisfied, the compressor contactor (fan  
contactor) will energize causing the compressor and outdoor  
(condenser) fan motor to operate. Terminal Gat the  
9—  
SERVICE  
WARNING: When servicing unit, shut off all elec-  
trical power to unit to avoid shock hazard or injury  
from rotating parts.  
I. CLEANING  
Inspect unit interior at the beginning of each cooling season  
and as operating conditions require.  
A. Condenser Coil  
Inspect coil monthly. Clean condenser coil annually, or as  
required by location and outdoor-air conditions.  
Clean coil as follows:  
Fig. 9 — Propping Up Top Panel  
1. Turn off unit power and tag disconnect.  
2. Remove and save top panel screws on condensing  
unit.  
3. Remove condenser coil corner post. See Fig. 8. To hold  
top panel open, place coil corner post between top  
panel and side panel. See Fig. 9.  
4. Remove bracket holding coil sections together at  
return end of condenser coil. Carefully separate the  
outer coil section 3 to 4 in. from the inner coil section.  
See Fig. 10.  
5. Use a water hose or other suitable equipment to flush  
down between the 2 coil sections to remove dirt and  
debris. Clean the outer surfaces with a stiff brush in  
the normal manner.  
6. Reposition the outer coil section, attach the bracket  
removed in Step 4, and remove the coil corner post  
from between the top panel and side panel. Secure  
the sections together. Install the coil corner post and  
replace all screws (removed in Step 2).  
Fig. 10 — Separating Coil Sections  
II. LUBRICATION  
A. Compressors  
III. CONDENSER-FAN ADJUSTMENT (Fig. 11)  
1. Shut off unit power supply, and tag disconnect.  
Each compressor is charged with the correct amount of oil at  
the factory. Refer to the Oil Charge section on page 9 for  
additional information.  
2. Remove condenser-fan assembly (grille, motor, motor  
cover, and fan).  
3. Loosen fan hub setscrews.  
4. Adjust fan height as shown in Fig. 11.  
5. Tighten set screws.  
B. Fan Motor Bearings  
Fan motor bearings are of the permanently lubricated type.  
No further lubrication is required.  
6. Replace condenser-fan assembly.  
NOTE: Fan height adjustments are as follows:  
UNIT  
in.  
mm  
569C072  
4.50  
114  
All Units  
(except 569C072)  
6.42  
163  
Fig. 8 — Cleaning Condenser Coil  
Fig. 11 — Outdoor (Condenser) Fan Adjustment  
10—  
IV. CAPACITY CONTROL (576B120 Only)  
7. Remove compressor from unit.  
A suction pressure-actuated unloader controls 2 cylinders  
and provides capacity control. Unloaders are factory set (see  
Table 1), but may be field adjusted:  
8. Clean system. Add new liquid line filter drier.  
9. Install new compressor in unit.  
10. Connect suction and discharge lines to compressor.  
Ensure that compressor holddown bolts are in place.  
A. Control Set Point  
The control set point (cylinder load point) is adjustable from  
0 to 85 psig. To adjust, turn control set point adjustment nut  
(Fig. 12) clockwise to its bottom stop. In this position, set  
point is 85 psig. Then, turn adjustment counterclockwise to  
desired control set point. Every full turn counterclockwise  
decreases set point by 7.5 psig.  
11. Install crankcase heater.  
12. Connect wiring.  
13. Evacuate and recharge unit, per Step VII.  
14. Restore unit power.  
VI. CRANKCASE HEATER  
B. Pressure Differential  
The crankcase heater prevents refrigerant migration and  
compressor oil dilution during shutdown when compressor is  
not operating.  
The pressure differential (difference between cylinder load  
and unload points) is adjustable from 6 to 22 psig. To adjust,  
turn pressure differential adjustment screw (Fig. 12) coun-  
terclockwise to its back stop position. In this position, differ-  
ential is 6 psig. Then, turn adjustment screw clockwise to  
desired pressure differential. Every full turn clockwise  
increases differential by 1.5 psig.  
Close both compressor service valves if applicable when  
crankcase heater is deenergized for more than 6 hours.  
VII. REFRIGERANT CHARGE  
Unit panels must be in place when unit is operating during  
charging procedure. Unit is shipped with a holding charge  
only. Weigh in 7 lbs of R-22 to start unit. Refer to GTAC II,  
Module 5, Charging, Recovery, Recycling, and Reclamation  
for additional information.  
See Troubleshooting Guide on page 13 for additional  
information.  
A. Low Charge Cooling  
Using Cooling Charging Charts, Fig. 13 and 14, vary refrig-  
erant until the conditions of the appropriate chart are met.  
Note the charging charts are different from type normally  
used. The charts are based on charging the units to the cor-  
rect sub-cooling for the various operating conditions. Accu-  
rate pressure gage and temperature sensing device are  
required.  
Connect the pressure gage to the service port on the liquid  
line service valve. Mount the temperature sensing device on  
the liquid line, close the liquid line service valve, and insu-  
late it so that outdoor ambient temperature does not affect  
the reading. Indoor-air cfm must be within the normal oper-  
ating range of the unit.  
Operate unit a minimum of 15 minutes. Ensure that temper-  
ature and pressure have stabilized. Plot liquid pressure and  
temperature on chart and add or reduce charge as required.  
Do not vent refrigerant to the atmosphere. Recover any  
excess charge. Operate the unit until the system stabilizes.  
Adjust charge to conform with charging chart, using liquid  
pressure and temperature to read chart.  
Fig. 12 — Compressor Capacity Control Unloader  
V. COMPRESSOR REMOVAL  
See Table 1 for compressor information.  
Follow safety codes and wear safety glasses and work gloves.  
B. Refrigerant Leaks  
1. Shut off power to unit and install lockout. Remove  
unit access panel (front of unit).  
Proceed as follows to repair a refrigerant leak and to charge  
the unit:  
2. Remove refrigerant from system using refrigerant  
removal methods described in GTAC II, Module 5,  
Charging, Recovery, Recycling, and Reclamation.  
1. Locate the leak and ensure that refrigerant system  
pressure has been relieved.  
3. Disconnect compressor wiring at compressor termi-  
nal box.  
2. Repair leak following accepted practices.  
NOTE: Install a new filter drier in the liquid line whenever  
the system has been opened for repair.  
4. Remove bolts from suction flange and discharge ser-  
vice valve (576B units).  
3. Add a small charge of R-22 refrigerant vapor to sys-  
tem and leak-test unit.  
CAUTION: Excessive movement of copper lines at  
compressor may cause higher levels of vibration when  
unit is restored to service.  
4. Evacuate refrigerant system up to 500 micons. If  
additional leaks are not found.  
5. Charge unit with R-22 refrigerant.  
5. Remove crankcase heater from compressor base  
(576B units only).  
NOTE: Do not vent refrigerant to the atmosphere. Recover  
any excess charge.  
6. Remove compressor holddown bolts.  
11—  
VIII. REFRIGERANT SERVICE PORTS  
IX. HIGH FLOW VALVES  
Each unit has 3 service ports: one on the suction line, one on  
the liquid line, and one on the compressor discharge line. Be  
sure caps on the ports are tight.  
Located on the compressor hot gas and suction tubes are  
High Flow Valves. Large black plastic caps distinguish these  
valves with O-rings located inside the caps. These valves can  
not be accessed for service in the field. Ensure the plastic  
caps are in place and tight or the possibility of refrigerant  
leakage could occur.  
Fig. 14 — Cooling Charging Chart — 569C090, 120  
and 576B090,102,120  
Fig. 13 — Cooling Charging Chart — 569C072  
12—  
TROUBLESHOOTING GUIDE  
CAUSE  
SYMPTOM  
REMEDY  
Compressor does not run —  
Contactor open  
Power off.  
Restore power.  
Replace with correct fuses after finding cause  
and correcting.  
Fuses blown.  
Replace transformer if primary windings are  
receiving power and no output.  
Check thermostat setting.  
Check for refrigerant undercharge or system  
leak.  
Transformer open/shorted.  
Thermostat circuit open.  
Low-pressure switch open.  
Check for refrigerant over charge or  
obstruction of outdoor airflow.  
High-pressure switch open.  
Connections loose.  
Tighten all connections.  
Compressor motor thermostat open.  
Compressor leads loose, broken.  
Single phasing.  
Check for excessive motor temperature.  
Check connections with power off.  
Replace blown fuse.  
Compressor does not run —  
Contactor closed  
Allow compressor motor windings to cool down to reset  
overload. Determine cause for overload opening.  
Compressor internal overload open.  
Compressor cycles on high-  
pressure switch —  
Condenser fan on  
High-pressure switch faulty.  
Airflow restricted. Dirty coil.  
Air recirculating.  
Replace switch.  
Remove obstruction, clean condenser coil.  
Clear airflow area.  
Recover, evacuate and recharge as required. Refer to  
Carrier GTAC-II, Module 5, Charging, Recovery,  
Recycling, and Reclamation.  
Noncondensables in system.  
Refrigerant overcharge.  
Recover as required.  
Check or replace filter drier, expansion  
valve, etc.  
Refrigerant system restrictions.  
Compressor cycles on high-  
pressure switch —  
Fan slips on shaft.  
Motor not running.  
Tighten fan hub screws.  
Check power and capacitor / and / hp motor.  
1
3
3
4
Condenser fan off  
Motor bearings seized.  
Motor overload open.  
Motor burned out, windings open.  
Filter drier plugged.  
Expansion valve power head  
defective.  
Replace motor.  
Check overload rating. Check for fan blade obstruction.  
Replace motor.  
Compressor cycles on low-  
pressure switch —  
Evaporator fan running  
Replace filter drier.  
Replace power head.  
Low refrigerant charge.  
Expansion valve restricted/plugged.  
Evaporator coil iced up.  
Evaporator coil dirty.  
Find leak, repair, evacuate system, and recharge.  
Remove and replace expansion valve.  
Check refrigerant charge.  
Clean coil fins.  
Airflow restricted —  
Low suction pressure  
Indoor-air filter dirty.  
Clean or replace filters.  
Check damper operation and position.  
Tighten all connections.  
Replace relay.  
Indoor-air dampers closed.  
Electrical connections loose.  
Fan relay defective.  
Indoor (evaporator) fan stopped —  
Low suction pressure  
Motor overload open.  
Motor defective.  
Check power supply.  
Replace motor.  
Fan belt broken or slipping.  
Refrigerant charge low.  
Head pressure low.  
Replace or tighten belt.  
Add charge.  
Check refrigerant charge.  
Clean or replace filters.  
Compressor runs but  
cooling insufficient —  
Suction pressure low  
Indoor-air filters dirty.  
Expansion valve power head  
defective.  
Replace power head.  
Expansion valve restricted/plugged.  
Evaporator coil partially iced.  
Evaporator airflow restricted.  
Remove and replace expansion valve.  
Check low-pressure setting.  
Remove obstruction.  
Compressor runs but  
cooling insufficient —  
Suction pressure high  
Heat load excessive.  
Check for open doors or windows.  
NOTE: See Fig. 15 and 16 for component arrangements.  
13—  
LEGEND FOR FIG. 15 AND 16  
LPS — Low-Pressure Switch  
C
Contactor, Compressor  
Terminal (Marked)  
NEC — National Electrical Code  
CAP — Capacitor  
OFC — Outdoor (Condenser) Fan Contactor  
OFM — Outdoor (Condenser) Fan Motor  
CB  
CH  
Circuit Breaker  
Crankcase Heater  
Terminal (Unmarked)  
Terminal Block  
OL  
QT  
TB  
Overload Relay  
Quadruple Terminal  
Terminal Block  
CLO — Compressor Lockout  
COMP — Compressor Motor  
COTP — Compressor Temperature Protection  
EQUIP — Equipment  
Factory Wiring  
TDR — Time-Delay Relay  
TRANTransformer  
Field Power Wiring  
GND — Ground  
HPS — High-Pressure Switch  
Fig. 15 — Typical 569C Component Arrangement  
Fig. 16 — Typical 576B Component Arrangement  
Copyright 2000 Bryant Heating & Cooling Systems  
801  
CATALOG NO. 5356-903  
START-UP CHECKLIST  
I. PRELIMINARY INFORMATION  
OUTDOOR: MODEL NO. __________________________________ SERIAL NO.____________________________________  
INDOOR: AIR HANDLER MANUFACTURER _____________________________________________________________  
MODEL NO. ___________________________________ SERIAL NO.____________________________________  
ADDITIONAL ACCESSORIES ______________________________________________________________________________  
II. PRE-START-UP  
OUTDOOR UNIT  
IS THERE ANY SHIPPING DAMAGE? _______  
(Y/N) _______  
IF SO, WHERE: _________________________________________________________________________________________  
______________________________________________________________________________________________________  
WILL THIS DAMAGE PREVENT UNIT START-UP? (Y/N) _______  
CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT? (Y/N) _______  
HAS THE GROUND WIRE BEEN CONNECTED? (Y/N) _______  
HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY? (Y/N) _______  
ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY? (Y/N) _______  
HAVE COMPRESSOR HOLDDOWN BOLTS BEEN LOOSENED, WHERE APPLICABLE (Snubber washers are snug, but not tight)?  
(Y/N) _______  
CONTROLS  
ARE THERMOSTAT AND INDOOR-FAN CONTROL WIRING  
CONNECTIONS MADE AND CHECKED?  
(Y/N) _______  
ARE ALL WIRING TERMINALS (including main power supply) TIGHT?  
HAS CRANKCASE HEATER BEEN ENERGIZED FOR 24 HOURS?  
(Y/N) _______  
(Y/N) _______  
INDOOR UNIT  
HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE?  
ARE PROPER AIR FILTERS IN PLACE? (Y/N) _______  
HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT?  
DO THE FAN BELTS HAVE PROPER TENSION? (Y/N) _______  
(Y/N) _______  
(Y/N) _______  
(Y/N) _______  
HAS CORRECT FAN ROTATION BEEN CONFIRMED?  
PIPING  
IS LIQUID LINE SOLENOID VALVE LOCATED AT THE EVAPORATOR COIL AS REQUIRED?  
(Y/N) _______  
HAVE LEAK CHECKS BEEN MADE AT COMPRESSOR, CONDENSER, EVAPORATOR,  
TXVs (Thermostatic Expansion Valves), SOLENOID VALVES, FILTER DRIERS, AND FUSIBLE PLUGS  
WITH A LEAK DETECTOR?  
(Y/N) _______  
LOCATE, REPAIR, AND REPORT ANY LEAKS. ________________________________________________________________  
ARE ALL 576B COMPRESSOR SERVICE VALVES FULLY OPENED (BACKSEATED)?  
(Y/N) _______  
HAVE LIQUID LINE SERVICE VALVE AND SUCTION LINE SERVICE VALVE BEEN OPENED?  
(Y/N) _______  
IS THE OIL LEVEL IN COMPRESSOR CRANKCASE ON 576B UNIT IN VIEW IN THE COMPRESSOR SIGHT GLASS?  
(Y/N) _______  
CHECK VOLTAGE IMBALANCE  
LINE-TO-LINE VOLTS:  
AB _______ V  
AC _______ V  
BC _______ V  
(AB + AC + BC)/3 = AVERAGE VOLTAGE =V  
MAXIMUM DEVIATION FROM AVERAGE VOLTAGE = __________ V  
VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) = __________ %  
IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!  
CALL LOCAL POWER COMPANY FOR ASSISTANCE.  
CL-1  
III. START-UP  
CHECK EVAPORATOR-FAN SPEED AND RECORD. _______  
CHECK CONDENSER-FAN SPEED AND RECORD. _______  
AFTER AT LEAST 15 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:  
OIL PRESSURE (576B only)  
SUCTION PRESSURE  
SUCTION LINE TEMP  
DISCHARGE PRESSURE  
DISCHARGE LINE TEMP  
ENTERING CONDENSER-AIR TEMP  
LEAVING CONDENSER-AIR TEMP  
EVAP ENTERING-AIR DB (dry bulb) TEMP  
EVAP ENTERING-AIR WB (wet bulb) TEMP  
EVAP LEAVING-AIR DB TEMP  
EVAP LEAVING-AIR WB TEMP  
COMPRESSOR AMPS (L1/L2/L3)  
_____ / _____ / _____  
HAS REFRIGERANT CHARGE BEEN ADJUSTED PER UNIT CHARGING CHART? _______________  
NOTES:  
______________________________________________________________________________________________________  
______________________________________________________________________________________________________  
______________________________________________________________________________________________________  
______________________________________________________________________________________________________  
______________________________________________________________________________________________________  
______________________________________________________________________________________________________  
______________________________________________________________________________________________________  
______________________________________________________________________________________________________  
______________________________________________________________________________________________________  
______________________________________________________________________________________________________  
______________________________________________________________________________________________________  
______________________________________________________________________________________________________  
Copyright 2000 Bryant Heating & Cooling Systems  
801  
CL-2  
CATALOG NO. 5356-903  

Aastra Telecom Answering Machine 350 User Manual
Admiral AAWV 12CR1FAU User Manual
Briggs Stratton Automobile Parts 124435 8105 01 User Manual
Cannon All in One Printer PIXMA User Manual
Carrier 38CKG User Manual
Chauvet Baby Accessories 3P User Manual
Datalogic Scanning QUICKSCAN QD 2300 User Manual
Epson Stylus Deluxe Photo Printer PICTUREMATED User Manual
HP Hewlett Packard HP 7110 Officejet Wide Format Eprinter CR768AB1H User Manual
HP Hewlett Packard Officejet J5780 User Manual