T7047C,G,H REMOTE SPACE SENSORS
INSTALLATION
When Installing this Product...
2000
1800
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a
hazardous condition.
1695 OHMS AT
75°F (24°C)
1600
1400
1200
1000
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
°F
10
-10
20
30
40
50
10
60
70
20
80
90
100
°C
0
30
40
CAUTION
TEMPERATURE (DEGREES)
M3399
Electrical Shock or Equipment Damage
Hazard.
Fig. 3. T7047C1009 Remote Sensor resistance
change with change in temperature.
Can shock individuals or short equipment
circuitry.
Disconnect power supply before installation.
RESISTANCE
(OHMS)
2000
Location
Locate the remote sensor about 5 ft (1.5m) above the
floor on an inside wall where it will be affected by freely
circulating air at average room temperatures.
1800
1600
1420 OHMS AT
75 F (24 C)
1400
Mounting
1200
1000
1. Loosen the cover locking screw with the Allen
wrench provided and remove the device cover.
2. Run wire to the selected location.
3. Thread wire through the semicircular hole in the
device.
F
10
-10
20
30
40
50
10
60
70
20
80
90
100
C
0
30
40
4. Make connections to the T7047 (see the Wiring
section).
TEMPERATURE (DEGREES)
M4034
5. Select the proper screws for the application. Four
mounting screws are provided:
Fig. 4. T7047C1025 Remote Sensor resistance
change with change in temperature.
a. Two self-tapping type for wall mounting.
b. Two for outlet box mounting.
6. If air drafts occur through the wall opening,
eliminate with suitable material.
7. Fasten the T7047 on the wall or outlet box with
screws through the mounting holes in the device.
120K
100K
80K
60K
8. Replace the cover and tighten the cover locking
screw.
22,800 OHMS AT
40K
77 F (25 C)
THERMOSTAT
20K
MOUNTING
TAB SLOT (2)
F
220
20
-7
40
60
80
100 120 140 160 180 200
C
MOUNTING
SCREW (2)
0
10
20 30
40
50
60
70
80
90 100
M3398
TEMPERATURE (DEGREES)
MOUNTING
TAB (2 INSIDE
COVER)
Fig. 5. T7047C1082 Remote Sensor resistance
change with change in temperature.
WIRING
TERMINALS
OUTLET
BOX
COVER
COVER LOCKING SCREW
M20072
Fig. 2. Mounting the T7047.
3
62-0179