Honeywell Smoke Alarm C7015A User Manual

Honeywell  
Infrared  
Flame Detector  
The  
Flame Detector includes a lead  
sulfide photocell that is sensitive to the infrared  
radiation emitted by the combustion  
as natural gas, oil, and coal.  
such  
n
suitable for combination or dual-fuel  
radiation is compatible with a wide range of flame  
supervisory applications.  
applications.  
q
When installed properly, can supervise the pilot  
flame and/or the main burner flame.  
Models are available with  
48 and 96 inches  
lengths of 30,  
m].  
Mounts easily on a standard  
inch sight pipe.  
Flexible metal cable protects and electrically  
shields the detector leadwires.  
n
n
The lead sulfide photocell plugs into an electrical  
socket in the  
placeable.  
assembly and is field re-  
q
Accessories available include a heat block, seal-off  
adapter, reducer bushing, swivel mount and orifice  
plate.  
The lead sulfide photocell’s sensitivity to infrared  
CONTENTS  
F.P. Rev.  
l
Inc. 1991 Printed in U.S.A. Form Number  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPECIFICATIONS  
l
ORDERING INFORMATION  
Specifications  
Reducer bushing for mounting the detector on a in.  
l
SUPER  
MODELS  
sight pipe; specifically, for replacing  
flame detectors.  
lead  
SUPER TRADELINE models offer features not  
TRADELINE or standard models, and are designed to  
replace a wide range of Honeywell and competitive  
controls. SUPER TRADELINE models are selected and  
packaged to provide ease of stocking, ease of handling,  
and maximum replacement value. Specifications of  
PER TRADELINE models are the same as those of  
standard models except as noted below.  
SUPER TRADELINE pack with cross reference label  
and special Instruction sheet.  
l
STANDARD MODELS  
MODELS: See Table 6 for flame safeguard controls and  
associated amplifiers.  
RESPONSE: Responds to infrared radiation  
with wavelengths between 0.75 and 1 .O micron.  
LEAD SULFIDE PHOTOCELL: Photoconductor  
decreases as incident radiant energy increases.  
SUPER TRADELINE MODEL AVAILABLE:  
48 in.  
leadwires; includes  
Bushing with  
105061  
and  
Reducer Bushing.  
AMBIENT TEMPERATURE RATING:  
maximum at the lead sulfide photocell.  
MOUNTING:  
F
C]  
SUPER TRADELINE FEATURES:  
l
plate (with  
in.  
mm] diameter  
agonal orifice) for reducing the detector field-of-view.  
Heat block for insulating the detector  
Mount-knurled collar with  
threads for mounting on a standard  
(see fig. 1).  
NPSM in-  
in. pipe  
=
sight pipe  
and up to  
temperatures higher than  
F 121” C].  
F
into socket in  
TABLE l-MODELS AVAILABLE.  
(see Fig. 8).  
0.125 in.  
insulate the detector from sight  
mount the detector on a in. sight pipe, specifically to replace  
mm] diameter hexagonal orifice to  
the detector field of view.  
temperatures higher than  
F
and up to  
F
lead sulfide infrared flame detectors.  
Order Information  
products from your Authorized Flame Safeguard Distributor or Wholesaler, refer to the  
When purchasing replacement and  
Catalog or price sheets for complete ordering number, or  
SUPER TRADELINE. if desired.  
2. Length of leadwires or 96 in.  
3. Lead sulfide cell order  
4. Replacement parts, if desired.  
5. Accessories, if desired.  
or 2.44 m].  
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:  
1. Your local Honeywell Residential and Building Controls Division Sales Office (check white pages of phone directory).  
2. Residential and Building Controls Division Customer Satisfaction  
Honeywell Inc., 1885 Douglas Drive North  
Minneapolis. Minnesota 554224386 (612) 542-7500  
(In Canada-Honeywell  
740 Ellesmere Road, Scarborough, Ontario  
International sales and  
service offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan Mexico,  
Netherlands, Spain Taiwan, United Kingdom, U.S.A.  
Download from Www.Somanuals.com.2All Manuals Search And Download.  
SPECIFICATIONS  
ACCESSORIES:  
WIRING CONNECTIONS:  
Nominal 30, 48, or 96 in.  
18  
Bushing with Focusing Lens  
1.22, or 2.44 ml  
105134  
Plate, to reduce the detector  
of view.  
for 194°F  
and one white.  
C];  
Diameter of  
Hexagonal Orifice  
(in.)  
0.125  
Leadwires enclosed in flexible metal  
mm] maximum outer diameter.  
DIMENSIONS: See Fig. 1.  
in.  
Part No.  
105134  
3.175  
APPROVALS:  
Underwriters Laboratories Inc. listed: File No.  
Canadian Standards Association certified: Master file  
LR-95329-1.  
temperatures higher than 125” F  
250” F  
and up to  
Factory Mutual approved.  
Industrial Risk Insurers acceptable.  
hot gases  
reaching the lead sulfide photocell.  
Reducer Bushing, to mount the detector on a  
IMPORTANT: Caution, stickers, form 96-610, are in-  
in. sight pipe;  
to  
lead  
cluded with  
Underwriters Laboratories  
detectors.  
Inc. requires that this sticker  
on any junction  
Hookup  
box in which  
leadwires are connected. The  
heat and moisture-resistant, No. 20  
stickerprohibits routing any other wiring through the  
junction box.  
C] for continuous duty; tested for operation up to 600  
volts and breakdown up to 7500 volts.  
Swivel Mount; provides adjustable positioning  
of the  
PARTS:  
Lead Sulfide Photocells  
Fig. l-Mounting dimensions of  
infrared Flame Detector and accessories, in in. [mm].  
106061  
HEAT BLOCK  
SEAL-OFF ADAPTER  
105134  
PLATE IN  
INCH  
INCH  
COUPLING  
SIGHTING  
INCH PIPE NIPPLE  
PIPE  
14 NPSM  
INTERNAL THREAD  
THREADS  
‘COLLAR.  
14 NPSM  
INTERNAL THREADS  
EXTERNAL THREADS  
EXTERNAL THREADS  
INSTALLING OR REPLACING A  
AND ACCESSORIES  
105061  
HEAT BLOCK  
396427  
REDUCER  
BUSHING  
SIGHTING PIPE  
14 NPSM  
INTERNAL THREADS  
B U S H I N G ’  
THREADS  
NPSM  
I
COLLAR,  
14  
EXTERNAL THREADS  
14 NPSM  
INTERNAL THREADS  
EXTERNAL THREADS  
REPLACING A  
LEAD  
DETECTOR  
3
60-2306-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION  
l
INSTALLATION  
Operation  
refractory radiation, thus making it fluctuate. This fluctuating  
action can simulate the flickering radiation from a flame,  
and infrared radiation may be present even after the  
refractory has visibly stopped glowing. Therefore, be very  
careful when applying an  
it responds only to flame.  
OPERATION OF INFRARED DETECTORS  
Infrared detectors can be used with gas, oil, coal, or  
fuel flames. Since more than 90% of the total flame radiation  
is infrared, these detectors receive ample radiation and can  
detection system to be sure  
detect weak  
as well as flames of higher intensity.  
The lead sulfide cell used in the detector cannot  
guish between the infrared radiation emitted by hot refrac-  
tory and the infrared radiation from a flame. Therefore, the  
infrared detection system includes an amplifier that re-  
sponds only to the flickering characteristic of flame radiation  
and rejects the steady radiation characteristic of hot refrac-  
CELL CONSTRUCTION  
photosensitive material used in the infrared detector  
is lead sulfide. The electrical resistance of lead sulfide de-  
creases when exposed to infrared radiation. If a voltage is  
applied across the lead sulfide photocell, current flows when  
cell is exposed to infrared radiation.  
tory.  
Unfortunately, smoke or fuel mist within the combustion  
chamber can intermittently reflect, bend, or block the hot  
Installation  
When a flame is present, the lead sulfide photocell  
WHEN INSTALLING THIS PRODUCT.. .  
1. Read these instructions carefully. Failure to follow  
them could damage the product or cause a hazardous condi-  
tion.  
detects the infrared radiation generated. The  
pro-  
duces electric signal that is sent to the amplifier in the flame  
safeguard control. The amplified signal pulls in the flame  
relay in the flame safeguard control to allow proper operation.  
Because it is necessary for the detector to actually see the  
flame, it is best to locate the detector as close to the flame as  
physical arrangement, temperature, and other restrictions  
permit. These restrictions are described in detail below.  
2. Check  
ratings given in  
instructions and on the  
product to make sure the product is suitable for your applica-  
tion.  
3. Installer must be a trained, experienced flame safe-  
guard control service technician.  
4. Afterinstallationiscomplete,checkoutproductopera-  
tion as provided in these instructions.  
DETERMINE THE LOCATION  
Before beginning the actual installation, determine the  
best location for mounting the flame detector. Carefully  
consider the factors discussed in this section before establish-  
ing the location.  
CAUTION  
1. Disconnect power supply before beginning in-  
stallation to prevent electrical shock and equip-  
ment damage, there may be more than one  
disconnect.  
TEMPERATURE  
The sensitivity of the lead sulfide cell decreases as its  
temperature increases. Up to  
F
the loss in  
2. All wiring must be NBC Class 1 (line voltage).  
sensitivity is negligible, but temperatures above this point  
3. Use the  
only with Honeywell lead  
must be avoided. Under normal temperature conditions (be-  
sulfide photocells (part no.  
and flame  
low 125” F  
the life of the lead sulfide cell should be  
signal amplifiers specified, (see Table 6).  
unlimited. The quickest check for excessive temperature is  
simply to grasp the detector-it should not be too hot to hold  
comfortably in your bare hand.  
Proper flame detector installation is the basis of a reliable  
flame safeguard installation. Refer to the burner manufac-  
turer instructions and instructions below. Carefully follow  
instructions for the best possible flame detector application.  
Several methods are available for cooling the lead sulfide  
photocell including ventilating the sight pipe and installing a  
pipe nipple, seal-off adapter, and/or heat block between the  
sight  
and the detector. Refer to Installing Accessories,  
page 8.  
BASIC REQUIREMENTS  
Because all flames produce infrared radiation, a  
SIGHTING  
Infrared (lead sulfide) Flame Detector can be used to prove  
the presence of a flame in a combustion chamber. The  
detector is mounted outside the combustion chamber. Screw  
themountingcollartooneendofasightpipeinsertedthrough  
the wall of the combustion chamber. The lead sulfide photo-  
cell in the detector sights the flame through the sight pipe.  
The infrared detector must continually sight a stable  
portion of the flame being detected. The detector is com-  
monly applied to detect both the gas pilot and main gas flame,  
or thegaspilot and main oil  
either case, the detector  
must be carefully aimed at the intersection of the pilot and  
A Swivel Mount (Honeywell part no.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
is available to facilitate flame sighting after the  
mounted.  
is  
pipe diameter is reduced, the effect is the same as adding an  
orifice plate to the pipe as discussed below.  
FIELD OF VIEW  
A lead sulfide photocell, like other photocells, views an  
area rather than a point. It is unable to pinpoint pilot flame  
Fig. P-Methods of reducing  
field-of-view.  
Detector  
it must view only a part of  
detect the pilot only when it is large enough to successfully  
light the main burner. viewing area must not be so large  
so it can  
AREA  
that a weak and wavering pilot flame could energize the  
photocell and cause the flame relay to pull in.  
0
The area viewed by the photocell depends on:  
UNRESTRICTED VIEW  
1. Diameter of  
opening in front of the cell.  
2. Distance from the cell to the opening.  
3. Distance from the opening to the area to be viewed.  
Fig. 2 shows three ways of reducing the field of view,  
assuming that the distance from the viewing opening to the  
flame or refractory cannot be changed. These are (1) length-  
ening the sight pipe, (2) reducing the diameter of the sight  
pipe, and (3) installing an orifice plate in front of the photo-  
3
BY LENGTHENING  
THE SIGHT PIPE  
cell. Combinations of these methods can  
used.  
CHANGING PIPE LENGTH OR SIZE (DIAMETER)  
Theeffectorchangingthelengthofthesightpipeisshown  
in Tables 2 and 3.  
Changing the diameter of the sight pipe is not as simple as  
changing the  
the  
mount and mount-  
in. pipe. When the sight  
ing accessories are all sized for  
TABLE 2-DIAMETER OF AREA SIGHTED THROUGH VARIOUS LENGTHS OF  
WITHOUT ORIFICE, IN IN.  
-IN. PIPE  
Distance From End of Pipe To Sighted Area-in.  
Length of  
6
12  
18  
30  
36  
42  
54  
66  
72  
7
8
1.5  
1.4  
2.3  
2.1  
3.1  
2.8  
3.9  
3.5  
4.7  
4.2  
5.5  
4.9  
6.3  
5.6  
7.1  
6.3  
8.0  
8.7  
7.7  
9.6  
8.5  
10.4  
7.1  
TABLE 3-DIAMETER OF AREA SIGHTED THROUGH VARIOUS LENGTHS OF  
WITHOUT ORIFICE. IN MM  
IN. PIPE  
Length of  
Pipe-mm 152.4 304.8  
25.4 160.0 302.3  
Distance From End of Pipe To Sighted Area-mm  
457.2  
447.0  
609.6  
589.3  
762.0  
721.4  
914.4 1066.8 11219.2 1371.6 1524.0 11676.4 11828.8  
876.3 Over 1016.0  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
INSTALLING AN  
AnorificeplatewithahexagonalorificediameterofO.125  
mm] is available for the Infrared Flame  
PLATE  
in.  
mm] diameterorifice  
in.  
Detector.  
(or refractory) is 36 in.  
mm], the dieter of the  
orifice can be mounted in front of the cell in the  
sighted area is 2.4 in.  
mm].  
seal-off adapter or in a standard  
in. coupling. (Refer to Fig.  
Fig. 3 shows how a typical orifice plate restricts the view  
of a small area around the flame junction.  
1.)  
The size of the sighted area at various distances can be  
determined  
Table 4 or 5. For example, if the distance  
OF AREA SIGHTED THROUGH ORIFICE, IN IN.  
3.2  
2.1  
2.6  
1.1  
1.6  
6
5-DIAMETER OF AREA SIGHTED THROUGH ORIFICE, IN MM  
Fig.  
orifice plate to restrict detector field of view to intersection of pilot and main flame, or to  
hot  
area  
ORIFICE PLATE  
PLATE  
PILOT  
HOT REFRACTORY  
MAIN FLAME  
PILOT,  
HOT REFRACTORY\  
MAIN  
\
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
RESPONSE TO HOT REFRACTORY  
Fig.  
infrared Flame Detector aimed  
Although the infrared amplifier will not respond to steady  
radiation, as produced by hot refractory, be careful to protect  
the infrared detector from hot refractory radiation because of  
two possible conditions, shimmer and raaiation saturation.  
a. Shimmer-Turbulent hot air, steam, smoke, or fuel  
spray in the combustion chamber can reflect, bend, or  
at side wall of combustion chamber.  
block  
steady infrared radiation emitted by a hot  
refractory. These conditions can change the steady  
radiation from a hot refractory into a fluctuating radia-  
tion. If these fluctuations occur at the same frequency  
as that of a flickering flame, they will simulate flame  
and will hold in the flame relay after the actual burner  
flame has been extinguished.  
MAIN BURNER FLAME  
-
-
-
-
b. Radiation saturation--Steady hot refractory radiation  
can become strong enough to mask the fluctuating  
_-  
--  
AREA VIEWED BY  
I
,
radiation of the  
This is similar to the effect of  
,
holdingupacandleinfrontofthesun-thelightofthe  
sun is so strong that the candle light cannot be seen. If  
radiation saturation is extreme, the flame relay will  
drop out, and the system will shut down as  
flame failure has occurred.  
I
I
.
.
I
a
Fig.  
Infrared Flame Detector aimed  
at a point above refractory.  
Both of these problems will be minimized by aiming the  
detector at a portion of the refractory that is:  
VIEWS AREA  
REFRACTORY  
l
l
l
as cool as possible.  
as far from the cell as possible.  
as small as possible reduce the field of view, see Figs.  
ABOVE TH  
BURNER  
FACEPLATE  
-
-
Refractory temperatures in the combustion chamber will  
vary with combustion chamber design but generally, the end  
wall of the chamber will be the hottest point. It will normally  
be best to aim the detector at the side wall of the refractory  
I
(Fig.  
at a point above the refractory (Fig.  
or at the floor  
AND  
of the combustion chamber (Fig. 6).  
.
.
SIGHTING SUMMARY  
.
.
When sighting  
detector, two important factors to  
junction), and (2) avoiding  
I
I
consider are: (1) proper sighting of the flame being detected  
.
(normally the pilot/main  
hot refractory sighting.  
A typical sighting arrangement is shown in Fig. 4. The  
detector is aimed at the intersection of the pilot and main  
flames, and at a relatively cool side of the combustion  
chamber. The detector, in this case, would be located as close  
as possible to the burner to sight the maximum depth of the  
and reduce the effect of variations in the main flame  
pattern.  
Fig.  
Infrared Flame Detector aimed  
at floor of combustion chamber.  
I
I
,
The detector can also be sighted from a point below and  
close to the burner with the line-of-sight above the refractory  
(Fig. 5).  
The third method is to aim the detector from above the  
burner, sighting a portion of the refractory floor (Fig. 6). This  
type of application requires that the pilot flame be carefully  
sighted from the side. The detector should not be sighted over  
CENTER LINE  
the shoulder of the pilot because  
chances increase of  
sighting pilot too small to satisfactorily light the main flame,  
a
REFRACTORY FLOOR  
AREA VIEWED BY  
as possible and consistent with proper sighting of the flame.  
Refer to Figs. 2 and 3 for methods of reducing the  
refractory sighted.  
of hot  
I
7
60-2306-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
mounting details, refer to form 60-0361 for the 118367A  
Swivel Mount)  
CLEARANCE  
Make sure there will be enough mom to easily mount the  
sight pipe, flame detector, and all required accessories, and to  
REDUCER BUSHING  
remove th  
felame detecto fror troubleshooting and servicing.  
To mount the detector on a  
in. sight pipe,  
detector, install a  
if replacing a  
lead  
INSTALLING THE SIGHT PIPE  
Reducer Bushing (Fig. 1).  
Thelocationofthesightpipeisthemostcriticalpartofthe  
installation. A  
Do  
in. black iron sight pipe is recommended.  
PLATE  
a stainless steel or galvanized pipe because its  
To reduce the detector field-of-view, and restrict it to the  
intersection of the pilot and main flame, or to a small area of  
internal surface blackens with use as deposits from the  
combustion chamber accumulate on it. Initially, its shiny  
intemalsurfacereflectsinharedradiation, whichcouldresult  
in a satisfactory flame signal even though the pipe may be  
hotrefractory (see Fig.  
install a 105 134 Orifice Plate. The  
plate can be inserted into a standard  
in. pipe  
improperly located. As it blackens, less  
radiation is  
signal becomes marginal.  
coupling (Fig. 1) or into the seal-off adapter, if used.  
reflected and the  
MOUNTING SIGHT PIPE  
Because no two situations  
the same, the length and  
sighting angle of the pipe must be determined at the time and  
placeofinstallation.Generally,itisdesirabletohavethesight  
pipe tilting downward to prevent soot or dirt buildup.  
Thmadoneendofthepipetofitthemountingcollaronthe  
detector (or an accessory, if used, see Fig. 1). Cut the pipe to  
the desired length (as  
excessive heat back to the lead  
pipeshould not extendmore than halfway into the refractory.  
practical). T oavoid conducting  
photocell, the sight  
PREPARE HOLE IN WALL OF COMBUSTION  
CHAMBER  
Tack weld  
pipe to the wall in a trial position (Fig. 9) Do  
.
Form a hole of the proper diameter for the sight pipe in the  
permanently weld the sight pipe in place until ajter  
completing the Adjustments and Checkout, page 10.  
the hole (Fig. 9) to leave room for small adjustments of the  
sighting angle. The taper of the hole should be about 1 in. for  
NOTE: If you use a Swivel Mount (part no.  
and  
every 3 in.  
mm for every 76.2 mm] of wall thickness.  
yo uarepositive about the location and sighting angle, you  
can permanently weld the pipe.  
INSTALLING ACCESSORIES  
PIPE NIPPLE  
It may be necessary or desirable to install accessories  
between the sight pipe and the detector. This section  
scribes the installation of these accessories.  
A
in. pipe nipple, 6 to 8 in. 152 to 203 mm] long, can  
Mount  
cell. Usin gthe pip enipple  
be inserted between the sight pipe and the  
(Fig. to help cool the lead  
SIGHT PIPE VENTILATION  
will also reduce the viewing area of the detector, see Table 2  
or 3).  
may be necessary to ventilate the sight pipe to cool the  
detector.  
SEAL-OFF ADAPTER  
For a negative pressure combustion chamber, drilling a  
few holes in  
section of the sight pipe outside of the  
To protect  
detector from hot gases, install a 105 172A  
combustion chamber allows air at atmospheric pressure to  
flow through the sight pipe into the chamber. A perforated  
pipe nipple between the sight pipe and the flame detector can  
also be used. See Fig. 7.  
For a positive pressure combustion chamber, connect a  
supply of pressurized air from the burner blower to flow  
throughthesightpipeintothechamber.Theairpressuremust  
be greater than the chamber pressure.  
Seal-Off Adapter (Fig. 1). The adapter has a glass window  
that prevents hot gases from reaching the lead sulfide  
cell.  
HEAT BLOCK  
To insulate the detector from sight pipe temperatures  
above 125” F  
install a 105061 Heat Block (Fig. 1).  
The device is made of nonheat-conductive, laminated plastic  
that prevents heat being conducted from the sight pipe  
to the detector. It can withstand temperatures up to 250” F  
Fig.  
air cooling.  
SIGHT  
PIPE  
PIPE TEE  
DETECTOR  
PIPE NIPPLE  
MOUNTING THE DETECTOR  
Before mounting the  
install the lead sulfide  
photocell (if not installed already).  
Unscrew the bushing from the cap, plu the phgotocel ilnto  
the cell mount, and screw the bushing back into the cap (Fig.  
COOLING AIR  
APPLIED UNDER  
8). The bushing also includes a  
lens to  
available radiation on the photocell face.  
SWIVEL MOUNT  
Mount the  
Detector onto the sight pipe, heat  
To facilitate flame sighting, a Swivel Mount (part no.  
is available. The Swivel Mount requires a reducer  
block, orotheraccessory (Figs. 1 and 9). Screw the mounting  
collar onto the sight pipe or accessory.  
of the proper size to mount it onto the sight pipe. (For  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
3. The detector comes with  
or in.  
Fig.  
lead sulfide photocell.  
or 2.44 leadwires inside a flexible metal cable. The  
leadwires consist of a twisted pair-one brown and one  
white. The two no. 18 AWG flexible-tinned leadwires are  
CAP  
rated for  
F
C]. The cable protects and electrically  
, MOUNTING  
\
shields the leadwires.  
PLUG-IN LEAD SULFIDE CELL  
(PART NO.  
4. If the leadwires are not long enough to reach the  
terminal strip or wiring subbase, make the required splices in  
a junction box (see IMPORTANT below).  
5. If splicing is necessary, use moisture-resistant no. 14  
wire suitable for at least 167” F  
if the detector is used  
PHOTOCELL  
SOCKET  
METAL CABLE  
SHIELDS LEADWIRES  
194°F  
C] if used with a flame safeguard programming control.  
6. For splicing in high temperature installations, use  
I
FOCUSING LENS  
Honeywell specification no.  
or equivalent for the  
for  
F leadwire. (This wire is rated up to 400” F  
continuous duty. It is tested for operation up to 600 volts and  
breakdown up to  
volts.) For the other leadwire, use  
moisture-resistant no. 14 wire selected for a temperature  
rating above the maximum operating temperature.  
Fig. O-Mounting  
Detector (and accessories).  
Infrared Flame  
IMPORTANT:  
REFRACTORY  
MAIN  
FLAME  
a . Flame detector leadwires must be as short  
sible. The maximum  
CHAMBER WALL  
detector to the  
m].  
safeguard control is 50  
TEMPORARY  
TACK  
Extensions to  
detector leadwires must be  
run alone in either rigid orflexible metal  
When detector leadwires exit a conduit, they  
must be as short as possible, twisted, and not be  
included in bundles or channels that contain other  
wires. Rigid metal conduit  
FLARED HOLE  
INCH BLACK  
IRON SIGHTING PIPE  
detector leadwires are extended  
metal  
conduit may be used  
movement.  
is supported to minimize  
The  
cable shield must be  
C.  
grounded to  
safeguard control subbase  
TO JUNCTION  
OR SUBBASE  
either directly or through the metal cabinetlconduit  
system that contains  
flame safeguard control  
subbase  
detector leadwires.  
10 and 11)  
When  
detector leadwires are routed through  
d.  
junction boxes,  
the junction boxes with the  
pressure-sensitive labels provided wiih the flame  
detector  
I CAUTION  
.
Disconnect power supply before beginning instal-  
lation to prevent electrical shock and equipment  
damage; there may be more than one disconnect  
involved.  
UNDERWRITERS LABORATORIES INC. RE-  
QUIRES THAT THE JUNCTION BOX BE  
MARKED TO INDICATE  
OTHER WIR-  
ING CONNECTIONS CAN BE ROUTED  
THROUGH IT. APPLY CAUTION STICKER  
1. All wiring must comply with applicable electrical  
codes, ordinances, and regulations. Use  
Class 1 wiring.  
(FORM  
FURNISHED) TO THE JUNC-  
Keeptheleadwiresfromtheflamedetectortotheflame  
safeguard control subbase as short as possible. Capacitance  
TION BOX.  
increases with  
length, reducing the signal strength.  
Maximize the separation between ignition trans-  
The maximum permissible  
ultimate in  
Iength is fifty feet.  
length is signal  
former high voltage wires and the  
sensor  
wires to avoid ignition interference.  
current/voltage. Refer to Table 6, Adjustments and Check-  
out, page  
60-2306-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
l
ADUSTMENTS AND CHECKOUT  
Fig. 1 l-Typical wiring of  
Flame Detector to distant wiring subbase or  
terminal strip.  
Infrared  
Fig. 1 O-Typical wiring of  
Infrared  
Flame Detector to nearby wiring subbase or  
terminal  
FLEXIBLE CABLE  
(MECHANICALLY  
SUPPORT TO  
MINIMIZE  
FLEXIBLE CABLE (MECHANICALLY  
SUPPORT TO MINIMIZE MOVEMENT)  
BX CABLE, SHIELDED  
CABLE, OR TWISTED  
PAIR; MUST BE ALONE  
IN CONDUIT.  
SUBBASE  
FLAME SAFEGUARD  
CONTROLS SUBBASE  
OR  
STRAP,  
JUNCTION BOX  
1 BROWN WIRE AND 1 WHITE WIRE FROM THE  
COLOR NOT IMPORTANT; LEADWIRES  
FROM JUNCTION BOX NEED NOT BE PHASED OR POLARIZED.  
CONNECT  
1
1 BROWN WIRE AND 1 WHITE WIRE FROM THE  
CONNECT TO  
APPLY CAUTION STICKER, FORM NO.  
SUPPLIED WITH  
FLAME SAFEGUARD CONTROL’S SUBBASE, COLOR NOT IMPORTANT,  
KEEP WIRES AS SHORT AS POSSIBLE. AND TWIST THEM.  
TO THIS JUNCTION BOX. BOX MUST BE GROUNDED.  
USE RIGID CONDUIT. OR SUPPORT FLEXIBLE CONDUIT TO  
MOVEMENT.  
CABLE MUST BE RUN To  
SAFEGUARD CONTROL ’S  
SUBBASE AND GROUNDED WHERE THE EXPOSED WIRES BEGIN.  
CONDUIT MUST BE RUN TO FLAME SAFEGUARD CONTROL’S  
SUBBASE AND GROUNDED THERE. KEEP EXPOSED WIRES AS  
SHORT AS POSSIBLE AND TWIST THEM.  
Adjustments and Checkout  
should blink at  
same rate that the flame is  
welding the sight pipe in  
location, complete  
below and any tests required by the burner  
flickering (may be as high as 20 times a second). If the lamp  
is ON (bright) continuously or not blinking while measuring  
the flame current, replace the amplifier.  
Tests  
Refer to Table 6 for the minimum acceptable flame  
currents for the amplifiers and associated flame safeguard  
controls.  
ADJ UST DETECTOR SIGHTING P OSITION  
initial burner lightoff, consult the burner manufacturer  
The  
and  
instructions or flame  
control instructions.  
With the flame detector installed and the burner running,  
adjust the sighting position of the detector for optimum flame  
signal.  
7800 SERIES flame safeguard controls respectively, have a  
dc voltage flame signal output.  
To measure flame signal voltages when using a  
amplifier, a 20,000 ohm/voltmeter with a zero to 5 or 10 Vdc  
scale is suggested To measure the flame signal voltage when  
Most existing Honeywell flame safeguard controls have a  
flame signal (current) can be measured  
a volt-ohmmeter  
using  
amplifiers, a volt-ohm meter with a mini-  
is recommended. The  
such as the Honeywell W 136A with a zero to 25 microampdc  
scale. To measure the flame current (signal), a Cable Connec-  
mum sensitivity of one  
flame signal (voltage) measurements are made as shown in  
Figs. 13 and 14. The positive (red) meter lead is connected to  
the positive (+) control jack and the negative (black) meter  
lead to the negative control jack (Corn jack with 7800  
SERIES controls). If the BCS 7700 and  
controls have the Keyboard Display Module, a zero to five  
Vdc voltage is displayed on the module. Refer to Table 6 for  
minimum and maximum flame voltages for the amplifiers  
tor (part number  
used with the meter. With the  
tioned to zero to 25  
included with  
must be  
(or equivalent) posi-  
scale, make connections  
from the meter probes to the two ends of the cable connector  
plug, red to  
black to black The plug end of the connector  
12).  
the flame safeguard control is using a  
amplifier, the red flame-indicating lamp on the  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ADJUSTMENTS AND CHECKOUT  
and associated flame safeguard controls.  
Fig.  
BCS 7700 Flame Safeguard  
Move the detector and sight pipe around to sight the flame  
at various positions and angles. Try to get a maximum steady  
meter reading. The signal must be above the minimum  
acceptable current/voltage listed in Table 6.  
Control flame signal voltage.  
Measure the  
burner flame alone, and both together (unless monitoring  
only the pilot when using an intermittent pilot, or only  
signal for the pilot alone, the main  
burner flame when using direct spark ignition). Also  
measure the flame signal at high and low firing rates and  
while modulating in between (as applicable). With the detec-  
tor in its final position, all required  
signals must be  
steady and as specified in Table 6. If you cannot obtain the  
proper signals, refer to the Troubleshooting section.  
Fig.  
flame Signal.  
PLUG-IN FLAME  
PROBES  
SIGNAL AMPLIFIER  
7700 CHASSIS MODULE  
I
SELECTOR  
SWITCH,  
196146 METER  
CONNECTOR  
TEST  
Fig.  
7800 SERIES Flame  
Safeguard Control flame signal voltage.  
RED CONNECTOR  
CK CONNECTOR  
M E T E R ‘  
LEAD  
El 208  
TABLE 6-FLAME SIGNAL  
Minimum  
Maximum  
Minimum  
Acceptable  
Steady Voltage  
Maximum  
Expected  
Voltage  
Acceptable  
Steady Current  
(microamp)  
Expected  
Current  
(microamp)  
Flame  
Signal  
Amplifier  
Flame Safeguard Control  
2.25  
5.0  
5.0  
5.5  
3.5  
4.0  
4.98  
5.0  
2.2  
BCS 7700  
1.25  
5.0  
1.25  
60-2306-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ADJUSTMENTS AND CHECKOUT  
PILOT TURNDOWN TEST  
solids instead of liquids, or liquids instead of gases.) When  
maximum refractory temperature is reached, close all  
manual fuel shutoff valves or open theelectricalcircuit of all  
automatic fuel valves. Visually observe when the burner  
flame goes out. After the flame goes out, measure the time it  
takes for the flamerelay 2K to drop out. Watch or listen to the  
flame relay to determine when it drops out. If the flame relay  
fails to drop out within four seconds, the infrared detector is  
sensing theradiation from hot refractory. Immediately termi-  
nate the firing cycle, (lower the set point of the burner  
controller, or set the fuel selector switch to OFF). Do not open  
the master switch.  
Ifthedetectorisusedtoproveapilotflamebeforethemain  
fuel  
can be opened, perform a Pilot Turndown Test  
before welding the sight pipe into position. Follow the  
procedures in the instructions for the appropriate flame  
safeguard control, and  
burner manufacturer instructions.  
HOT REFRACTORY SATURATION TEST  
Testtobesureradiationfromhotrefractorydoesnotmask  
the flickering radiation of the  
itself.  
Start the burner and monitor the flame signal during the  
heats up indicates hot refractory saturation. If saturation is  
extreme, the flame relay 2K (in the flame safeguard control)  
will drop out and the system will shut down as though a flame  
failure has occurred.  
If hot refractory saturation occurs, the condition must be  
corrected. Add an orifice plate in front of photocell to  
restrict the viewing area. If this does not work, resight the  
detector at a cooler, more distant background. Lengthening  
the sight pipe or decreasing the pipe size (diameter) may also  
be helpful. Continue adjustments until hot refractory satura-  
tion is eliminated.  
Some burners continue to purge their oil lines be-  
tween  
valves and nozzles even though the fuel valve(s)  
is closed. Terminating the firing cycle (instead of opening  
the master switch) will allow purging of the combustion  
chamber. This will reduce a buildup of fuel vapors in the  
combustion chamber caused by oil line purging.  
If the detector is sensing hot refractory radiation, the  
condition must corrected. Add an orifice plate in front of  
the photocell to restrict the detector viewing area. If this does  
not work, resight the detector at a cooler, more distant part of  
the combustion chamber. While resighting the detector,  
remember that it must also properly sight the flame. Length-  
ening the sight pipe or decreasing the pipe size (diameter)  
may also be helpful. For details, refer to Installation. Con-  
tinue adjustments until hot refractory hold-in is eliminated.  
HOT REFRACTORY HOLD-IN TEST  
Test to make certain that hot refractory will not cause the  
flame relay 2K (in the flame safeguard control) to stay  
in after  
burner flame is extinguished. This condition  
would delay response to flame failure and also would prevent  
a system  
hot refractory is detected.  
long as the infrared radiation emitted by the  
IGNITION INTERFERENCE TEST  
It is possible for infrared amplifiers to respond to ignition  
spark electrical noise (interference) under certain conditions.  
Avoid ignition interference by locating the transformer as  
close as possible to the burner ignition electrode (preferably  
not on the control cabinet). You can also use an ignition cable  
that suppresses electrical noise (such as the type of cable  
in automobiles). Maintain maximum separation of flame  
sensor and ignition wiring.  
First check the plug-in flame signal amplifier by initiating  
a burner cycle. When the programmer stops in the run  
position, terminate the firing cycle while the refractory is at  
a low temperature. Measure  
relay 2K to drop out after  
time it takes for the flame  
flame goes out. Watch or listen  
to the flame relay to determine when it drops out. If the flame  
relay fails to drop out within four seconds, open the master  
switch and replace the amplifier.  
Infrared detectors can respond to infrared radiation emit-  
ted by a hot refractory, even when the refractory has visibly  
ceased to glow. Infrared radiation from a hot refractory is  
steady, whereas radiation from a flame has a flickering  
To determine if an infrared flame amplifier responds to  
ignition interference, complete the following test sequence:  
1. CLOSE MANUAL  
AND MAIN  
VALVES TO THE PILOT  
2. Connect a flame signal meter to the amplifier and start  
the burner.  
a flickering infrared radiation; it can reject a steady signal  
from hot refractory. However, the refractory’s steady signal  
can be made to fluctuate if it is reflected, bent, or blocked by  
smoke or fuel mist within the combustion chamber. Be  
careful when applying an infrared system to ensure its  
response to flame only.  
3. There should be no flame signal when the ignitor is  
energized (momentary meter movement may observed  
when the flame safeguard control switches a load on or off).  
WELD THE SIGHT PIPE  
To check a  
Flame Detector for hot  
After adjustments have been made and an acceptable  
flame signal obtained, remove the detector and weld the sight  
refractory hold-in, operate the burner until the refractory  
reaches its maximum temperature. If the installation has a  
multifuel burner, burn the fuel most likely to reflect, bend, or  
obscure the hot refractory’s steady infrared radiation, (burn  
pipe in  
final position, (if you are using a swivel mount, the  
pipe may already be welded). Then reinstall the detector.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ADJUSTMENTS AND CHECKOUT  
l
TROUBLESHOOTING  
FINAL CHECKOUT  
CAUTION  
Before putting the burner into service, check out the  
installation by using  
Checkout procedures in the instruc-  
Do not put the system into operation until all  
Checkout tests in the instructions for the appropri-  
ate flame safeguard control and any specified in the  
burner installation instructions are satisfactorily  
completed.  
tions for the appropriate flame safeguard control. After  
completing the checkout, run the burner through at least one  
complete cycle to verify proper operation.  
Troubleshooting  
PRELIMINARY INSPECTION  
1.  
the flame is properly adjusted and is not  
CAUTION  
too lean.  
1. Be extremely careful while troubleshooting the  
detector; line voltage is present on some of the  
2. Checkfortheproperlinevoltage. Makesurethemaster  
switch is closed, connections are correct, and power supply  
is of the correct voltage and frequency.  
terminals on the wiring  
when power is on.  
or terminal strip  
3. Check the detector wiring for defects including:  
. incorrect connections.  
2. Open the master switch to disconnect power  
before removing or installing the detector, there  
may be more than one disconnect involved.  
wrong type or size of wire.  
l
l
l
l
l
deteriorated wire.  
open circuits.  
short circuits.  
leakage paths caused by moisture, soot, or dirt.  
If you cannot obtain a satisfactory flame signal while  
adjusting the sighting position of the detector, follow these  
procedures. If you encounter other problems in the system,  
refer to Troubleshooting in the instructions for the appropri-  
ate flame safeguard control.  
4. With the burner running, check the temperature at the  
detector. If it exceeds 125” F  
add additional insulation between the wall of the  
combustion chamber and the detector.  
add a shield or screen to reflect radiated heat away  
from the detector.  
add cooling (refer to Sight Pipe Ventilation, see  
Installation).  
EQUIPMENT REQUIRED  
1.  
300  
scale.  
PROCEDURE FOR A LOW METER READING  
1. Remove the detector and clean the focusing lens  
a soft, clean cloth.  
2. Microammeter (Honeywell  
with 0 to 25 microampdc range.  
3.  
Meter Connector Plug or equivalent (required for some  
meters).  
or equivalent)  
196146, or 117053  
2. If the focusing lens is broken or damaged, or if it is  
coated with a substance that cannot be cleaned off, replace the  
Bushing (which includes the focusing lens).  
3. Clean the inside of the sight pipe before reinstalling the  
detector.  
4. A volt-ohm meter with a zero to 5 or 10 Vdc scale and  
a sensitivity of 20,000 ohm/volt is suggested for  
control flame signal measurements. If the control has the  
Keyboard Display Module option, flame voltage is displayed  
on the module.  
4. If the meter reading is still too low, replace the lead  
sulfide cell (Fig. 8).  
5. If the meter reading is still too low, replace the plug-in  
amplifier.  
5. A one  
meter with a zero to 5 or 10 Vdc  
scale is recommended for 7800 SERIES control flame volt-  
age measurements. If the control has the Keyboard Display  
Module option, flame voltage is displayed on the module.  
6. Replacement parts-see Specifications.  
6. If you still cannot obtain a proper flame signal, replace  
the  
Infrared Flame Detector.  
PROCEDURE FOR A ZERO METER READING  
1. Replace the lead sulfide cell (Fig. 8). Then recheck the  
flame signal.  
TROUBLESHOOTING PROCEDURES  
2. If there is still no flame signal, replace the plug-in  
amplifier.  
Firstperfonn  
Inspection. Then follow the  
applicable procedures for either a low reading or a zero  
reading on the flame signal meter. After reinstalling the  
detector, recheck the meter reading. Adjust the position of the  
3. If you still cannot obtain a meter reading, replace the  
entire  
Infrared Flame Detector.  
detector to try to obtain the proper  
procedures are completed and a satisfactory flame signal  
cannot be obtained, replace the detector.  
signal. If the  
IMPORTANT: At the completion of troubleshooting, be  
sure to perform the Adjustments and Checkout, page  
10.  
60-2306-5  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICE  
PERIODIC MAINTENANCE  
1. Clean the focusing lens andsightpipe when necessary.  
CAUTION  
Remove the detector and use a soft, clean cloth.  
lens does  
1.  
not require removal to clean it. If it is broken or damaged, or  
to service or repair flame safeguard controls and  
burner systems.  
the  
Bushing, which includes the focusing lens.  
2. Keep the flame detection system adjusted for the  
smoothest, most reliable operation as recommended by the  
burner manufacturer.  
3. Replace the bushing with focusing lens or the lead  
sulfide photocell (Fig. 8) only when necessary to obtain  
proper operation.  
2. Open the master switch to disconnect power  
before removing or installing the detector.  
3. If the  
is disassembled for any reason  
lead sulfide cell or bushing  
(e.g., to replace  
with focusing lens), you must perform the Ad-  
justments and Checkout, page 11.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
Table of Contents  
Page  
1
..................................................................................................................................................  
Application and Features  
2
2
3
......................................................................................................................................................................  
Specifications  
Ordering Information  
Dimension Drawings  
..............................................................................................................................................  
................................................................................................................................................  
4
............................................................................................................................................................................  
..........................................................................................................................................................................  
Operation  
4
4
8
8
8
9
Installation  
..................................................................................................................................................  
Basic Requirements  
...........................................................................................................................................  
the Sight Pipe  
Installing Accessories  
Mounting the Detector  
................................................................................................................................................  
.............................................................................................................................................  
.......................................................................................................................................................................  
Wiring  
10  
.............................................................................................................................................  
Adjustments and Checkout  
13  
...............................................................................................................................................................  
.........................  
Troubleshooting  
Service  
..............  
Periodic Maintenance  
.............................................................................................................................................  
Tables  
Table I -Models available  
2
.......................................................................................................................................  
Table 2 -Diameter of area sighted through various lengths of  
Table 3 -Diameter of area sighted through various lengths of  
Table 4 -Diameter of area sighted through orifice, in in  
inch pipe without orifice, in in..  
...................  
.
6
6
inch pipe without orifice, in mm  
..................  
....................................................................................  
Table 5 -Diameter of area sighted through orifice, in mm  
............................................................................................................................................  
11  
Table 6 -Flame Signal  
Figures  
Fig.  
Fig. 2 -Methods of reducing  
.3  
in in. [mm].  
accessories,  
Infrared Flame Detector field-of-view  
Fig. 3 -Using orifice plate to restrict detector field-of-view to intersection of pilot  
1
-Mounting dimensions of  
Infrared Flame Detector and  
...................  
5
...................................................  
6
7
7
7
8
9
.................................................................................  
or to small area of hot refractory  
and main  
Infrared Flame Detector aimed at side wall of combustion chamber  
......................................  
....................................................  
Fig. 4  
Fig. 5  
Infrared Flame Detector aimed at a point above refractory  
Infrared Flame Detector aimed at floor of combustion chamber  
............................................  
Fig. 6  
.....................................................................................................................................  
Fig. 7 -Forced air cooling  
Fig. 8 -Installing lead sulfide photocell  
................................................................................................................  
................................................................  
Infrared Flame Detector and accessories  
Fig. 9 -Mounting  
13  
10  
11  
11  
11  
...............................................  
................................................  
Fig. 10 -Typical wiring of  
Fig. 11 -Typical wiring of  
Fig. 12 -Measuring  
Fig. 13 -Measuring BCS 7700 Flame Safeguard Control flame signal voltage  
Fig. 14 -Measuring 7800 SERIES Flame Safeguard Control  
to nearby wiring subbase or terminal strip  
to distant wiring subbase or terminal strip  
........................................................................................................  
signal  
.................................................  
...........................................  
signal voltage  
60-2306-5  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Marine Sanitation System 237526 User Manual
Haier Washer XPB10 LAP User Manual
Hamilton Beach Can Opener Opening Station User Manual
Hans Grohe Plumbing Product 04169XX0 User Manual
Hasbro Games 06706 User Manual
Heatcraft Refrigeration Products Refrigerator H HTSSB 1208 User Manual
Honeywell Thermostat CMR707A1049 User Manual
Hotpoint Dishwasher HDA3520 User Manual
HP Hewlett Packard Network Card D7522A User Manual
iHome Satellite Radio ZN14 User Manual