| L8124A,C,E,L and M   Aquastat® Relays   INSTALLATION INSTRUCTIONS   APPLICATION   SPECIFICATIONS   These immersion type controllers are used with forced   hydronic heating systems that include domestic hot water   service. All models provide high limit, low limit and   circulator control. Table 1 lists the various models and   their applications.   Low Limit:   Setting: 110°F to 220°F (43°C to 104°C), adjustable.   Differential: 10°F to 25°F (6°C to 14°C), adjustable.   High Limit:   Setting: 130°F to 240°F (54°C to 116°C), adjustable.   Differential: 10°F (6°C), fixed.   These Aquastat® relays have a diaphragm powerhead   and MicroSwitch™ assembly that respond to   temperature changes in the boiler water. L8124 can   provide multizone control by using a separate circulator   and R845 Relay for each zone. L8124E and L have large   transformers and extra terminals for supplying power to   low voltage valves. L8124L includes a large transformer   and extra terminals for low voltage zone valves. L8124M   is for use in a wood-coal/gas-oil multifuel heating system.   Circulator is independently controlled by the thermostat.   WARNING   Can cause serious injury, death or property   damage.   Use this product only in systems with a pressure   relief valve.   Explosion Hazard.   Do not use these Aquastat® Relays where the pressure   can exceed 100 psi (690 kPa) on the bulb if inserted   directly or 200 psi (1380 kPa) when using an immersion   well, or where the ambient temperature can exceed   150°F (66°C) at the case or 265°F (129°C) at the sensing   element.   Table 1. Model Descriptions.   No. of V8043 Zone   Electrical Ratings   Can Be Used For   Multizone With   Burner   Control   Number Circuit   L8124A 120V   L8124C   Valves Powered   Without Additional   Transformer   Model   a Circulators   Burner Circuit   Circulator Circuit   Yes   — Same as L8124A,C,L   circulator rating.   120 Vac: 7.4A (full load),   44.4A (locked rotor).   240 Vac: 3.7A (full load),   22.2A (locked rotor).   L8124L   3 2 L8124E 24V   1.25A at 24 Vac; 30 VA   (total load) B -B , T -Z.   1 2 v L8124M 120V   — Same as L8124A.   None.   a Multizone control can be provided by using a separate circulator and R845 Relay for each zone.   ® U.S. Registered Trademark   Copyright © 2001 Honeywell • All Rights Reserved   95- 6571- 11   Download from Www.Somanuals.com. All Manuals Search And Download.   L8124A,C,E,L AND M AQUASTAT® RELAYS   BACK OF   CONTROLLER   CASE   IMMERSION   WELL CLAMP   CONTROLLER   CASE   BOILER   IMMERSION   WELL CLAMP   1 IMMERSION   WELL SPUD   ADAPTER   IMMERSION   WELL CLAMP   SCREW   ADAPTER   OLD IMMERSION   WELL ASSEMBLY   SENSING   BULB   (A)   (D)   ) (B)   2 HEAT-CONDUCTIVE COMPOUND   1 2 BEND THE CAPILLARY TUBE TO HOLD THE SENSING BULB IN GOOD   THERMAL CONTACT WITH THE IMMERSION WELL AT POINTS (A) AND (B).   CAPILLARY   TUBE   ASSURE THAT CAPILLARY TUBE FITS FREELY IN THE ADAPTER SO THE   TENSION OF THE CAPILLARY TUBE AT POINT (C) HOLDS THE SENSING   BULB IN GOOD THERMAL CONTACT WITH THE IMMERSION WELL AT POINT (D   SETSCREW   SHORT TUBE   FITS IN CENTRAL   RECESS OF ADAPTER   IMMERSION   WELL CLAMP SCREW   Fig. 2. Position of bulb in immersion well and use of well adapter when required.   LOW VOLTAGE   THERMOSTAT   LOW VOLTAGE   THERMOSTAT   L8124A,C   G L8124E   2 2 G T Z TV   L1   (HOT)   L1   (HOT)   T T 1 2 1 2 1K   L2   1 L2   1 1K   1K2   W R W R B B 1K1   1K1   LOW LIMIT/   CIRCULATOR   LOW LIMIT/   CIRCULATOR   ZR   ZC   LINE VOLTAGE   CIRCULATOR   R B HIGH   LIMIT   C1   C2   LINE VOLTAGE   OIL BURNER   RELAY OR   B HIGH   LIMIT   1K2   GAS VALVE   3 3 R B1   TR   TH   B1   B2   B2   C1   LOW VOLTAGE   GAS VALVE   (eg, VR8300)   C2   POWER SUPPLY. PROVIDE DISCONNECT MEANS AND   OVERLOAD PROTECTION AS REQUIRED.   1 2 3 LINE VOLTAGE   CIRCULATOR   CONTROL CASE MUST BE CONNECTED TO EARTH GROUND.   USE GROUNDING SCREW PROVIDED.   POWER SUPPLY. PROVIDE DISCONNECT MEANS AND   OVERLOAD PROTECTION AS REQUIRED.   1 M8803   B1 IS 1/4 IN. TAB TERMINAL.   2 3 CONTROL CASE MUST BE CONNECTED TO EARTH GROUND.   USE GROUNDING SCREW PROVIDED.   Fig. 4. L8124E single zone connections   and internal schematic.   M8802   B1 IS 1/4 IN. TAB TERMINAL.   Fig. 3. L8124A,C single zone connections   and internal schematic.   3 95-6571—11   Download from Www.Somanuals.com. All Manuals Search And Download.   L8124A,C,E,L AND M AQUASTAT® RELAYS   T87F   T87F   T87F   L8124A   R845 RELAY   R845 RELAY   ZC   ZR   B1   T T T 1 T 2 T 1 T 2 3 2 G C1   3 6 3 6 C2 B2   4 5 4 5 L1   L2   L2   L1   (HOT)   1 PUMP   PUMP   PUMP   R8184   T F C554   T F ORANGE   BURNER   AND   IGNITION   BLACK   1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.   CONTROL CASE MUST BE CONNECTED TO EARTH GROUND. USE GROUNDING SCREW PROVIDED.   B1 IS 1/4 IN. TAB TERMINAL.   2 M8822   3 Fig. 5. L8124A in an oil-fired, forced hot water, tankless, zoned, pump system.   TO ADDITIONAL   R845A RELAYS   FOR OTHER ZONES   L2   L1   (HOT)   LOW VOLTAGE   THERMOSTAT   1 2 L8124A,C   G R845A RELAY ZONE 2   ZONE 2   CIRCULATOR   T T 1 2 6 5 3 1K   W R B 1K1   LOW LIMIT/   CIRCULATOR   4 1 ZR   ZC   LINE VOLTAGE   OIL BURNER   RELAY OR   B 2 HIGH   LIMIT   1K2   GAS VALVE   3 ZONE 2   LOW VOLTAGE   THERMOSTAT   R B1   B2   C1   POWER SUPPLY. PROVIDE DISCONNECT MEANS AND   OVERLOAD PROTECTION AS REQUIRED.   1 2 3 CONTROL CASE MUST BE CONNECTED TO EARTH   GROUND. USE GROUNDING SCREW PROVIDED.   C2   LINE VOLTAGE   CIRCULATOR   B1 IS 1/4 IN. TAB TERMINAL.   M8827   Fig. 6. L8124A,C multizone system with circulator connections and internal schematic.   95-6571—11   4 Download from Www.Somanuals.com. All Manuals Search And Download.   L8124A,C,E,L AND M AQUASTAT® RELAYS   1 ZONE 1   THERMOSTAT   ZONE 2   THERMOSTAT   L1   (HOT)   T87F   V8043F   V8043F   L2   2 TH   TR   TH   TR   G L8124E   L2 L1   C1 C2   T T 3 TH   TR   TH   TR   2 B2 B1   L8124G,L   3 G 1 T Z TV   TH   TR   L1   (HOT)   1K   CIRCULATOR   LOW VOLTAGE   GAS VALVE   (eg, VR8300)   2 1 L2   1K1   1 2 3 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND   OVERLOAD PROTECTION AS REQUIRED.   W R B ZR   CONTROL CASE MUST BE CONNECTED TO EARTH GROUND.   USE GROUNDING SCREW PROVIDED.   LOW LIMIT/   CIRCULATOR   ZC   B1 IS 1/4 IN. TAB TERMINAL.   M1796A   LINE VOLTAGE   OIL BURNER   RELAY OR   B R 1K2   HIGH   LIMIT   Fig. 8. L8124E in a 24Vac, gas-fired,   forced hot water, tankless system.   GAS VALVE   4 B1   B2   C2   C1   LINE VOLTAGE   CIRCULATOR   POWER SUPPLY. PROVIDE DISCONNECT MEANS AND   OVERLOAD PROTECTION AS REQUIRED.   1 2 UP TO TWO V8043F ZONE VALVES CAN BE POWERED WITH   L8124G,L. ADD ADDITIONAL TRANSFORMER FOR EVERY   TWO OR LESS VALVES.   CONTROL CASE MUST BE CONNECTED TO EARTH GROUND.   USE GROUNDING SCREW PROVIDED.   3 4 M1795B   B1 IS 1/4 IN. TAB TERMINAL.   Fig. 7. L8124 multizone system with zone valve   connections and internal schematic.   5 95-6571—11   Download from Www.Somanuals.com. All Manuals Search And Download.   L8124A,C,E,L AND M AQUASTAT® RELAYS   T87F   T87F   T87F   R845 RELAY   R845 RELAY   R845 RELAY   T 1 T 2 T 1 T 2 T 1 T 2 3 6 3 6 3 6 4 5 4 5 4 5 1 L1   (HOT)   PUMP   PUMP   PUMP   L2   2 G L2 L1   C1 C2   T T LOW VOLTAGE   GAS VALVE   (eg, VR8300)   TH   TR   B2 B1   3 L8124E   AQUASTAT RELAY   ® 1 2 3 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.   CONTROL CASE MUST BE CONNECTED TO EARTH GROUND. USE GROUNDING SCREW PROVIDED.   B1 IS 1/4 IN. TAB TERMINAL.   M1794A   Fig. 9. L8124E in a 24 Vac, gas-fired, forced hot water, tankless, zoned pump system.   1 TO ADDITIONAL   R845A RELAYS   FOR OTHER ZONES   L1   (HOT)   L2   R845A RELAY ZONE 1   6 5 3 L8124E   2 G T Z TV   4 1 1 2 1K   2 1K2   ZONE 1   LOW VOLTAGE   THERMOSTAT   W R B 1K1   LOW LIMIT/   CIRCULATOR   R B ZONE 1   CIRCULATOR   HIGH   LIMIT   C1   C2   3 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND   OVERLOAD PROTECTION AS REQUIRED.   1 2 3 TR   B1   B2   THTR   TH   CONTROL CASE MUST BE CONNECTED TO EARTH   GROUND. USE GROUNDING SCREW PROVIDED.   LOW VOLTAGE   GAS VALVE (eg, VR8300)   B1 IS 1/4 IN. TAB TERMINAL.   M8828   Fig. 10. L8124E multizone system with circulator connections and internal schematic.   95-6571—11   6 Download from Www.Somanuals.com. All Manuals Search And Download.   L8124A,C,E,L AND M AQUASTAT® RELAYS   LOW VOLTAGE   THERMOSTAT   ZONE 1   1 TO ADDITIONAL   R845A RELAYS   FOR OTHER ZONES   L2   L1   (HOT)   L8124L   2 G T Z TV   R845A RELAY ZONE 2   ZONE 2   CIRCULATOR   1 2 1K   6 5 3 1K1   W R B ZR   ZC   LOW LIMIT/   CIRCULATOR   4 1 B R 1K2   HIGH   LIMIT   3 2 B1   LINE VOLTAGE   OIL BURNER   RELAY OR   ZONE 2   LOW VOLTAGE   THERMOSTAT   B2   C2   GAS VALVE   POWER SUPPLY. PROVIDE DISCONNECT MEANS AND   OVERLOAD PROTECTION AS REQUIRED.   1 2 3 C1   LINE VOLTAGE   CIRCULATOR   ZONE 1   CONTROL CASE MUST BE CONNECTED TO EARTH   GROUND. USE GROUNDING SCREW PROVIDED.   B1 IS 1/4 IN. TAB TERMINAL.   M8829   Fig. 11. L8124L multizone system with circulator connections and internal schematic.   EXAMPLE: Setpoint of 140°F (60°C), differential set   at 25°F (14°C). On a temperature rise, R-B breaks   and R-W makes at 155°F (68°C). On a temperature   fall, R-B makes and R-W breaks at 130°F (54°C).   OPERATION   High Limit Controller   The high limit opens and turns off the burner when the   water temperature reaches the setpoint. The high limit   automatically resets after the water temperature drops   past the setpoint and through the 10°F (6°C) differential.   SWITCH BREAKS ON   TEMPERATURE RISE.   BURNER TURNS OFF.   CIRCULATOR OPERATES   ON A CALL FOR HEAT.   HIGH LIMIT   SETTING   WARNING   Can cause serious injury, death or equipment   damage.   SWITCH MAKES ON   TEMPERATURE FALL.   BURNER OPERATES ON A   CALL FOR HEAT.   Explosion Hazard.   Use this product only in systems with a pressure   relief valve.   SWITCH MAKES R-W   AND BREAKS R-B ON   TEMPERATURE RISE.   1 LOW LIMIT   AND   CIRCULATOR   SETTING   Low Limit and Circulator Controllers   SWITCH MAKES R-W   AND BREAKS R-B ON   TEMPERATURE RISE.   On a temperature rise, with the adjustable differential at   the minimum setting of 10°F (6°C), the burner circuit   (R-B) breaks and the circulator circuit (R-W) makes at   the control setpoint. On a temperature drop of 10°F (6°C)   below the setpoint, the R-B circuit makes and the R-W   circuit breaks. See Fig. 12.   SWITCH MAKES R-B AND   BREAKS R-W ON   TEMPERATURE FALL.   BURNER IS ON TO   MAINTAIN MINIMUM   WATER TEMPERATURE.   CIRCULATOR IS OFF.   At any differential setting greater than 10°F (6°C), the   R-B make temperature and the R-W break temperature   remain the same (control setting minus 10°F [6°C]). The   R-B break and R-W make temperature are the setpoint   temperature plus the difference between the differential   setting and 10°F (6°C).   1 WHEN WATER REACHES PROPER TEMPERATURE, THE BURNER   SHUTS OFF OR THE CIRCULATOR PUMP STARTS (WHEN CALLING   FOR HEAT).   M1523   Fig. 12. Relationship of setpoints and differential.   7 95-6571—11   Download from Www.Somanuals.com. All Manuals Search And Download.   L8124A,C,E,L AND M AQUASTAT® RELAYS   On the L8124M, the burner and circulator circuits are   separately controlled; the low limit controls the burner   circuit (R-B) as described above, while the low voltage   thermostat directly controls the circulator circuit.   See Fig. 13.   SETTING   Follow the boiler manufacturer recommendations when   making the L8124 settings. The high limit setting must be   at least 20°F (11°C) higher than the low limit setting. Set   the indicators over the selected temperature marks. The   low limit differential is set by turning the differential   adjustment knob to the desired amount of differential.   The thermostat heat anticipator should be set at 2.0A.   LOW VOLTAGE   THERMOSTAT   2 L8124M   G CHECKOUT   L1   (HOT)   T T L1   L2   Put the system into operation and observe each function   through at least one complete cycle. Be sure the control   operates as intended.   L2   1 1K   ZC   1K1   LINE VOLTAGE   CIRCULATOR   W R B C1   C2   LOW LIMIT   LINE VOLTAGE   OIL BURNER   RELAY OR   B R HIGH   LIMIT   3 GAS VALVE   B1   B2   POWER SUPPLY. PROVIDE DISCONNECT MEANS   AND OVERLOAD PROTECTION AS REQUIRED.   1 2 CONTROL CASE MUST BE CONNECTED TO EARTH   GROUND. USE GROUNDING SCREW PROVIDED.   M8804   3 B1 IS 1/4 IN. TAB TERMINAL.   Fig. 13. L8124M single zone connections   and internal schematic.   Automation and Control SolutionsAutomation and Control Solutions   Honeywell   Honeywell Limited-Honeywell Limitée   1985 Douglas Drive North   Golden Valley, MN 55422   35 Dynamic Drive   Scarborough, Ontario   M1V 4Z9   95-6571—11 G.R. Rev. 12-01   Download from Www.Somanuals.com. All Manuals Search And Download.   |