Installation & Operating Manual
P61 Pellet Stove Owners Manual
“Ce manuel est disponible en Français sur demande”
SAFETY NOTICE
PlEASE rEAd ThIS ENTIrE MANuAl bEFOrE YOu INSTAll ANd uSE YOur NEw rOOM hEATEr. FAIlurE
TO FOllOw INSTruCTIONS MAY rESulT IN PrOPErTY dAMAgE, bOdIlY INjurY, Or EvEN dEATh.
FOr uSE IN ThE u.S. ANd CANAdA. SuITAblE FOr INSTAllATION IN MObIlE hOMES
IF ThIS hArMAN STOvE IS NOT PrOPErlY INSTAllEd, AhOuSE FIrE MAY rESulT. FOr YOur SAFETY, FOllOw
INSTAllATION dIrECTIONS.
CONTACT lOCAl buIldINg Or FIrE OFFICIAlS AbOuT rESTrICTIONS ANd INSTAllATION INSPECTION
rEQuIrEMENTS IN YOur ArEA.
CONTACT YOur lOCAl AuThOrITY (SuCh AS MuNICIPAl buIldINg dEPArTMENT, FIrE dEPArTMENT, FIrE
PrEvENTION burEAu, ETC.) TO dETErMINE ThE NEEd FOr A PErMIT.
CETTE guIdE d'uTIlISATION EST dISPONIblE EN FrANCAIS. ChEz vOTrE CONCESSIONNAIrE dE hArMAN
hOME hEATINg.
SAvE ThESE INSTruCTIONS.
Item# 3-90-05810
r10
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
Testing label
2
Assembly & Installation
venting
4
7
Operation
12
14
15
18
19
20
21
22
24
25
ESP Control
Maintenance
Trouble Shooting
Feeder Parts
Specifications
wiring diagram
Options
Parts list
warranty
Please read this entire manual before you install and use your new
room heater. Failure to follow instructions may result in
property damage, bodily injury, or even death.
SuITAblE FOr MObIlE hOME INSTAllATIONS.
SAVE THESE INSTRUCTIONS
harman home heating
352 Mountain House Road
Halifax, PA 17032
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Assembly and Installation
unpacking
The P61 is bolted to the skid to prevent movement
during shipping.
To free the stove from the skid you must remove the
hold-down bolts in the rear of the pedestal base.
removing or Installing rear cover panels
To remove the rear cover panels, loosen the screws
slightly and slide the covers outward as shown in the
illustration. To reinstall, simply slide back into place and
retighten the screws.
Firebrick
Install the firebrick vertically on the angle above the
burnpot.
Flame guide
Install the cast iron flame guide on top of the burnpot
and make sure it is fully seated against the auger
opening. The bottom of the flame guide is marked 38+.
Fig. 2
Shipping Bolts: These
holes are also used for
Mobile Home Installation
Rear Cover
Panels
draft Test Procedure
Before attaching any vent pipe to the stove, perform
a draft test, for later comparison.
Remove the plug bolt on the underside of the firebox
as shown. Using the hole from the bolt, attach a draft
meter that is capable of reading at least .5 inches of
water column (W.C.). You are going to want the meter
reading negative pressure.
Turn the feed adjuster to "Test". For the first minute,
everything will run. Record the high draft reading
_______ . After the first minute, the distribution blower
will go to a low speed. Then, after the second minute,
two minutes after turning to test, the distribution
blower will come back up to high, and the combustion
blower will drop to low. During this time, record the low
draft________. Perform the test again after the venting
is complete. Compare your readings. If there is more
than a .05 difference, you have too much restriction in
the venting. There is no adjustment for the draft other
than improving the venting configuration. Leaving the
stove in "test" will continue to cycle the blowers each
minute. Record your final draft redings here. _________
High, and ________ Low.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Installing
Place the stove on a non-combustible floor or a floor
protector providing a minimum .84k value. Floor protection
must extend 6 inches to the front, 6 inches to the sides
and 1 inch to the rear of the stove.
9"-13"
Place the stove away from combustible walls at least
as far as shown in figures 3,4 and 5. Please note the
difference in side wall clearance with and without side
shields.
Note that the clearances shown are minimum for safety
but do not leave much room for access when cleaning
or servicing. Please take this into account when placing
the stove.
9"-13"
Connect the power cord to a 120 V.A.C. 60Hz grounded
receptacle.
After connecting the flue system, perform the second draft
test. However, prior to taking the draft reading be sure all
doors and windows in the home are closed. Record the
draft reading_______. If this reading is more than .05"
lower than the unconnected reading, check for possible
restrictions or the need for outside air (see page 7).
9" With Side Shields
13" Without Side Shields
Fig. 3
Mobile home Installation
When installing this unit in a mobile home, several
requirements must be followed:
1. The unit must be bolted to the floor. This can be done with
1/4" lag screws through the 2 holes in the base plate.
2. The unit must also be connected for the outside air.
See page 7.
3. Floor protection and clearances must be followed as
shown.
4. Unit must be grounded to the metal frame of the mobile
home.
5. The stove may not be installed in a room designated
for sleeping.
CAuTION: This appliance must be vented to the
outside.
Fig. 4
Due to high temperatures, the stove should be placed out
of traffic and away from furniture and draperies.
Children and adults should be alerted to the hazards of
high surface temperatures and should stay away to avoid
burn to skin and/or clothing.
Young children should be carefully supervised when they
are in the same room as the stove.
Clothing and other flammable materials should not be
placed on or near this unit.
18"
Installation and repair of this Harman Stove should be
done by a qualified service person. The appliance should
be inspected before use and at least annually by a qualified
service person. More frequent cleaning will be required.
It is imperative that control compartments, burners, and
circulating air passageways of the stove be kept clean.
Mobile home installation should be done in
accordance with the Manufactured home and Safety
Standard (hud), CFr 3280, Part 24.
Fig. 5
5
Download from Www.Somanuals.com. All Manuals Search And Download.
venting
J. The clearance to a non-mechanical air supply inlet to
requirements for Terminating the venting
wArNINg: Venting terminals must not be recessed
into a wall or siding.
the building or the combustion air inlet to any other
appliance must be a minimum of 48”.1
K. The clearance to a mechanical air supply inlet must
be a minimum of 10 feet.1
NOTE: Only pellet vent pipe wall pass-throughs
and fire stops should be used when venting through
combustible materials.
(with outside air installed, 6 feet )
L. The clearance above a paved sidewalk or a paved
driveway located on public property must be a
minimum of 7 feet.1,2
NOTE: Always take into consideration the effect the
prevailing wind direction or other wind currents will
cause with flyash and /or smoke when placing the
termination.
In addition, the following must be observed:
A. The clearance above grade must be a minimum
of 18".1
M. The clearance under a veranda, porch, deck or
balcony must be a minimum of 12 inches.1,3 (see b.)
NOTE: The clearance to vegetation and other exterior
combustibles such as mulch is 36” as measured from
the center of the outlet or cap. This 36” radius continues
to grade or a minimum of 7 feet below the outlet.
1Certain Canadian and or Local codes or regulations
may require different clearances.
B. The clearance to a window or door that may be
opened must be a minimum of 48".1
(with outside air installed, 18”)
C. A 12" clearance to a permanently closed window
is recommended to prevent condensation on the
window.
D. The vertical clearance to a ventilated soffit located
above the terminal within a horizontal distance of
2 feet (60 cm) from the center-line of the terminal
must be a minimum of 18".
2A vent shall not terminate directly above a side-walk
or paved driveway which is located between two
single family dwellings and serves both dwellings.
3Only permitted if veranda, porch, deck, or balcony is
fully open on a minimum of 2 sides beneath the floor.
E. The clearance to an unventilated soffit must be a
minimum of 12".
F. The clearance to an outside corner is 11" from center
of pipe.
NOTE: where passage through a wall, or partition of
combustible construction is desired, the installation
shall conform to CAN/CSA-b365. (if in Canada)
G. The clearance to an inside corner is 12".
H. A vent must not be installed within 3 feet (90 cm)
above a meter/regulator assembly when measured
from the horizontal center-line of the regulator.1
I. The clearance to service regulator vent outlet must
be a minimum of 6 feet.1
= Vent terminal
v
Download from Www.Somanuals.com. All Manuals Search And Download.
venting
Acombustion blower is used to extract the combustion
IMPOrTANT NOTICE
gases from the firebox. This causes a negative pressure
in the firebox and a positive pressure in the venting
system as shown in fig. 6. The longer the vent pipe
and more elbows used in the system, the greater the
flow resistance. Because of these facts we recommend
using as few elbows as possible and 15 feet or less
of vent pipe. The maximum horizontal run should not
exceed 48". If more than 15 feet of pipe is needed, the
diameter should be increased from 3" to 4" because
a larger pipe causes less flow resistance. be sure
to use approved pellet vent pipe wall and ceiling
pass through fittings to go through combustible
walls and ceilings. Be sure to use a starting collar to
attach the venting system to the stove. The starting
collar must be sealed to the stove with high temp
silicone caulking.
Pellet Vent "L" or "PL" Vent Pipe Must be used.
+
vent Pipe
Pellet vent pipe (known as type "L" or "PL" vent) is
constructed of two layers with air space between the
layers. This air space acts as an insulator and reduces
the outside surface temperature to allow a clearance
to combustibles of only 3 inches. The sections of pipe
lock together to form an air tight seal in most cases;
however, in some cases a perfect seal is not achieved.
For this reason and the fact that the P61 operates with
a positive vent pressure we specify that the joints
also be sealed with high temp silicone.
Fig. 6
+
+
= Positive static pressure
- = Negative static pressure
Outside Air
Outside air flex
pipe goes here
Outside air is optional except in mobile homes and
where building codes require. The benefit of outside air
is mainly noticed in small very tight houses.
To install outside air use 2 3/8" I.D. flex pipe part
number 1-00-08543 (25 ft.). There is a break-away
hole on the rear panel which must be removed before
connecting the flex pipe. The pipe should be run outside
and terminate to the side or below the vent pipe outlet
so the flue outlet is more than 12" from the inlet cover.
The maximum length run of this pipe is 15 feet. If a
longer run is needed the size must be increased to 3".
Inlet cover part number 1-10-08542 should be used to
keep birds, rodents etc. out of the pipe.
Flex pipe part #
1-00-08543 (25 ft.)
Fig. 7
Inlet Cover part#
1-10-08542
The Harman Direct Vent Wall
Passthrough allows the proper
protection of the wall and
brings outside air to the stove
with one component. Part #
1-00-677077 is all you need.
(fits only 3" pellet pipe)
hrv
When installing in a house with a Heat Reclaiming
Ventilation System (HRV) be sure the system is
balanced and is not creating a negative pressure in
the house.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
venting
#1 Preferred method
This method provides excellent venting for normal
operation and allows the stove to be installed
closest to the wall. Two inches from the wall is
safe; however, four inches allows better access to
remove the rear panel. The vertical portion of the
vent should be three to five feet high. This vertical
section will provide natural draft in the event of a
power failure.
3 ft.
to combustibles
Fig. 8
#2 Preferred method
This method also provides excellent venting for
normal operation but requires the stove to be
installed farther from the wall. The vertical portion
of the vent should be three to five feet high and at
least three inches from a combustible wall. This
vertical section will provide natural draft in the event
of a power failure.
3 ft.
to combustibles
Fig. 9
8
Download from Www.Somanuals.com. All Manuals Search And Download.
venting
#4 Installing into an existing chimney
This method provides excellent venting for normal
operation. This method also provides natural draft
in the event of a power failure. If the chimney
condition is questionable you may want to install a
liner as in method #7. Check with your local codes
to be sure a liner is not mandatory.
Fig. 10
#5 Installing into an existing fireplace
chimney
This method provides excellent venting for normal
operation. This method also provides natural draft
in the event of a power failure.
The damper area must be sealed with a steel
plate or fiberglass.Acap should be installed on the
chimney to keep out rain. If the chimney condition
is questionable you may want to install a liner all
the way to the top as in method #6. Check with
your local codes to be sure a liner is not mandatory.
Fig. 11
9
Download from Www.Somanuals.com. All Manuals Search And Download.
venting
#6 Installing into an existing fireplace
chimney
This method provides excellent venting for normal
operation. This method also provides natural draft
in the event of a power failure.
Some places in the US and Canada it is required
that the vent pipe extend all the way to the top of
the chimney.
In this method a cap should also be installed
on the chimney to keep out rain. Be sure to use
approved pellet vent pipe fittings. Seal pipe joints
with silicone in addition to the sealing system used
by the manufacturer. Pipe size should be increased
to 4" using this method.
Fig. 12
#7 Installing into an existing chimney
This method provides excellent venting for normal
operation. This method also provides natural draft
in the event of a power failure.
Some places in the US and Canada it is required
that the vent pipe extend all the way to the top of
the chimney. The pipe or liner inside the chimney
should be 4"diameter.
In this method a cap should also be installed on
the chimney to keep out rain.
Fig. 13
10
Download from Www.Somanuals.com. All Manuals Search And Download.
venting
#8 Installing through the ceiling vent
Through the ceiling vent, follow the vent manufacturers
recommendations when using wall and ceiling pass
throughs.
Minimum flue vent
configuration
It is recommended that outside
air be installed with this venting
configuration.
(See Page 9 for
corner installation
clearances)
Fig. 15
Fig. 14
dO NOT INSTAll A FluE dAMPEr IN ThE
EXhAuST vENTINg SYSTEM OF ThIS uNIT.
dO NOT CONNECT ThIS uNIT TOAChIMNEY FluE
SErvINg ANOThEr APPlIANCE.
INSTAll vENT AT ClEArANCES SPECIFIEd bY
ThE MANuFACTurEr
CAuTION
ThE STruCTurAl INTEgrITY OF ThE MObIlE
hOME FlOOr, wAll, ANd CEIlINg/rOOF
MuST bE MAINTAINEd.
CAuTION
ThE STOvE IS hOT whIlE IN OPErATION.
KEEP ChIldrEN, ClOThINgANd FurNITurE
AwAY. CONTACT MAY CAuSE SKIN burNS.
Fig. 16
11
Download from Www.Somanuals.com. All Manuals Search And Download.
MANuAl STArT uP
Operation
Starting First Fire
Be sure the power cord is plugged into a 120 volt
receptacle. This can be verified by the red power light
on the control panel.
be sure there is no fuel or other combustibles in
the ash pan prior to lighting.
Fill the hopper with pellets.
Fill the burn pot with pellets to a level just short of
overflowing, fig. 17.
Fig. 17
Adjust feed rate. If this is your first fire or you are trying
different pellets, set the feed adjuster to "4", fig. 18.
This is a conservative number and will probably need
to be increased. After you know a feed rate setting that
works well, use that setting. Remember, too high of a
feed rate will waste fuel.
Turn Mode selector to "OFF" and then to "Stove
Temp". This will turn the combustion blower to high.
When starting a fire always turn the mode selector to
"OFF" before selecting the desired mode. This resets
the control for start-up.
Fig. 18
Turn Temp dial to 7. This will allow the stove to burn
at maximum for feed rate adjusting purposes.
Apply starting gel to pellets in burn pot and light
the gel. Close the door after lighting. At this point the
distribution and combustion lights will be on and the
feed motor light will be off.As the temperature of the fire
increases, the feed motor light will come on and pellets
will feed into the burn pot. As the stove temperature
increases the distribution blower speed will increase.
Fig. 19
1"
After 30 to 45 minutes it may be necessary to readjust
the feed rate. The feed rate should be adjusted so
there is about one inch of ash in front of the fire, fig. 20.
This is a maximum burn position and the stove may not
achieve this position under normal burn rates.
"NEVER USE GASOLINE, GASOLINE-TYPE LANTERN
FUEL, KEROSENE, CHARCOAL LIGHTER FLUID, OR
SIMILAR LIQUIDS TO START OR "FRESHEN UP " A FIRE
IN THIS HEATER. KEEPALL SUCH LIQUIDS WELLAWAY
FROM THE HEATER WHILE IN USE".
Fig. 20
12
Download from Www.Somanuals.com. All Manuals Search And Download.
MANuAl IgNITION/OPErATION
when to use "Stove Temp Mode"
In "Stove Temp Mode" the Stove Temp Dial determines
the temperature of the stove. Heat output and fuel
consumption will remain constant. This makes it
possible to tell how long a hopper full of pellets will last.
The distribution blower speed will vary according to the
position of the mode selector, fig. 21.
Fig. 21
when to use "room Temp Mode"
In "Room Temp Mode" heat output is controlled
automatically by the Room Sensing Probe. When
the Room Sensing Probe calls for heat, the stove will
increase output. When the Room Sensing Probe is
getting close to the set temperature, the stove will begin
to level off output and keep the fire burning at just the
right temperature to maintain that setting.
High output is determined by the feed rate. The
maximum feed rate should be set for 1" of ash in front
of fire.
In "Room Temp Mode" fuel consumption is sacrificed
for exact room temperature. Therefore, as it gets colder,
more pellets will be burned automatically.
This setting will produce medium heat with the distribution
blower on "low".
The distribution blower speed will vary according to
the position of the mode selector, fig. 21.
Shut-down Procedure
To kill the fire or stop burning the stove, turn the Mode
Selector to "OFF". This will cause the fire to diminish
and burn out. When the fire burns out and the stove
cools down everything will stop.
Never pull the plug to shut down the stove, all motors
will stop. This will cause incomplete combustion and
smoke in the firebox. If the load door is opened the
smoke will escape.
This setting will produce a room temperature of 70
degrees with the distribution blower at medium speed.
The best way to shut down the stove is to simply
let it run out of pellets, then the stove will shut down
automatically.
This setting will produce continuous maximum heat output
with the distribution blower at full speed.
13
Download from Www.Somanuals.com. All Manuals Search And Download.
ESP CONTrOl
Feed adjuster
Sets the maximum feed
rate
Power Light
Indicates power to the
control.
Test
Status Light
Runs all motors at full
speed for two minutes
to check operation. After
two minutes the stove
will go to minimum burn
and the blowers will
alternate from high to
low every two minutes
to remind you that you
are still in "Test Mode".
Will be lit in either stove
or room temp mode when
pointer is not within off
position band except after
normal shut down. Blinks
to indicate errors listed
below.
Indicates power to
distribution blower.
Distribution Blower
speed adjustment range.
Indicates Power to
combustion blower
Indicates Power to the
feed motor.
Temp dial
Mode Selector
Allows you to adjust the Room temperature in Room Temp Mode
using the outer scale marked in degrees Fahrenheit. It also allows
you to adjust the stove temperature while in Stove Temp Mode
using the inner scale marked from 1 to 7.
Allows you to choose between Room Temp Mode,
Stove Temp Mode, or OFF. Also allows you to vary
the distribution blower speed by turning the knob to
the high or low side of each mode.
STATuS lIghT ErrOr MESSAgES:
6 blinks : Indicates that the control has calculated poor
or incomplete combustion occurring for more than 50
minutes. See Troubleshooting section for more details.
1 blink: Indicates control board self diagnostic failure.
This requires a manual reset*.
* Manual reset, disconnect power cord for a few
seconds and reconnect. If error still occurs call your
Dealer.
3 blinks: Indicates ESP (Exhaust Sensing Probe)
failure. This requires a manual reset*.
4 blinks: Can occur only in Room Temp Mode and
indicates Room Sensing Probe failed or not installed.
If a Room Sensing Probe is then installed the status
light will automatically reset.
14
Download from Www.Somanuals.com. All Manuals Search And Download.
room Sensor and rear Shield Installation
room Sensor Installation
rear Shields
5/16" Hex Head
Screws (2 on
each side)
5/16" Hex
Head Screws
(2 on each
side)
Fig. 22
Fig. 23
The room sensor is a small temperature sensor
The rear insulated shields are split in the middle
on the end of a 60" wire. This sensor is installed for easy removal. Each shield has two 5/16" hex
much like a standard wall thermostat. Because head screws that only need to be loosened (NOT
it is so small, it can be hidden along the trim of a REMOVED) to allow the shield to slide away from
doorway or even up the leg of a coffee table. There the unit.
is a remote room sensor port on the rear of the
unit for easy external connection. Use standard
18-2 thermostat wire to extend the distance to the
desired location (100' maximum). The room sensor
should be installed in the location where you want
to control the temperature.
NOTE: It is not recommended that the unit be
operated with the shields removed, due to the
hot and moving parts which they protect.
NOTE: Distances of more than 25 feet from the
unit or in another room are not recommended. The
room sensor is essential for the P61's excellent
efficiency.
NOTE: It is recommended that the room sensor
be installed, even if only installed on the rear of
the unit as a return air sensor.
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
removing Ashes:
When approximately 1 ton of pellets has been burned,
it will be necessary to empty the ash pan.
Ashes should be placed in a metal container with
a tight fitting lid. The closed container of ashes
should be placed on a noncombustible floor or
on the ground, well away from all combustible
materials, pending final disposal. If ashes are
disposed of by burial in soil or otherwise locally
dispersed, they should be retained in the closed
container until all cinders have thoroughly cooled.
It is recommended that the stove is cold and shut down
when removing the ash pan.
Fig. 24
Combustion
Blower Cover
Blower Cover
Latch
1. Pull on latch handle to open the ash door, and remove
ash pan.
Heat Exchanger Fins
2. Close the ash door while dumping ashes. Use ash
pan handle to carry and dispose of ashes.
3. Return the ash pan into the stove and latch the ash
door securely.
Cleaning:
Scrape the burn pot surface regularly. Whenever
adding fuel, it is a good time to scrape the burn pot.
Using the flat end of the scraper tool, scrape under
the fire to remove any carbon deposits which may be
forming. The more frequent the scraping, the better
performanc you'll have.
Scraper
The stove will need to be cleaned for approximately
every 2 to 5 tons of pellets burned. The amount of
pellets burned before cleaning will vary depending on
the brand of pellets.
Flue Outlet
Blower Cover
Latch
1. Shut down the stove and disconnect the power
cord to insure that all motors are stopped.
Blower Wheel
Fig. 25
2. Remove ash pan as described earlier.
3. Remove combustion blower cover by turning the latch
vertical as shown in Fig.26 and sliding the cover out
of the slot on the left (Fig.27.) This will expose the
combustion blower wheel and flue outlet, (Fig.24.)
The draft pressure switch senses the pressure in
the hopper. Note the location of this fitting, known
as the muffler. Depending on the amount of fines
in the fuel, this muffler may need to be cleaned
periodically.Usecautionwhencleaningoremptying
the hopper.
4. Clean the blower wheel with a brush and a vacuum
cleaner.
5. Use a brush (Fig.30) to clean the flue, being careful
not to damage the ESP probe. The flue goes straight
through into the vent pipe (Fig.29) therefore, the vent
pipe can also be cleaned, to some extent, through
the flue outlet.
6. Reinstall the blower cover and relatch.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
7. Open the burn pot slide as shown, clean with vacuum
and close.
8. Clean the heat exchanger with the scraper as shown
in Fig. 25.
9. Brush or scrape the inside of the stove to remove
fly ash.
10. Scrape the burnpot with the flat end of the provided
scraper. Fig.31.
Fig. 27
Latch "open "with blower
cover partly removed. Burn
pot clean-out is open.
Fig. 26
11.Slide the ash pan into stove and re-latch the ash
pan door.
Latch "closed "with blower
cover in place. Burn pot
clean-out is closed.
Brush not supplied. Can be found in
hardware stores.
ESP probe
Fig. 30
Soot and Fly Ash
The products of combustion will contain small particles
of fly ash. The fly ash will collect in the exhaust venting
system and restrict the flow of the flue gases. Incomplete
combustion, such as occurs during startup, shutdown,
or incorrect operation of the room heater, will lead to
some soot formation which will collect in the exhaust
venting system. The exhaust venting system should
be inspected at least once every year to determine if
cleaning is necessary.
Fig. 28
Exposed blower wheel
and flue opening, NOTE:
ESP probe is visible.
Blower cover
removed.
ESP Probe
Be careful not
to damage ESP
probe when
cleaning with
brush.
Fig. 29
Fig. 31
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Trouble-Shooting
FEEdEr dOES NOT FEEd
SMOKE SMEll
1. No pellets in hopper.
Seal the vent pipe joints and connection to stove with
2. Feed motor will not run until ESP senses 165 deg.
F. Maybe you did not put enough pellets in the burn
pot before lighting the fire.
3. Feed motor has failed.
4. Something is restricting flow in the hopper or causing
the slide plate to stick.
5. Firebox draft may be too low for low draft pressure
switch in feeder circuit to operate. Check for closed
doors, loose or missing gasket on doors or hopper
lid, faulty pressure switch.
high temp silicone.
FIrE hAS gONE OuT
1. No pellets in hopper.
2. Feed rate too low.
3. Something is restricting fuel flow.
4. Feed motor or draft motor has failed.
5. Power failure or blown fuse.
SMOKE IS vISIblE COMINg OuT OF vENT
1. Air-fuel ratio is too rich.
A. Feed rate too high.
B. Draft too low caused by a gasket leak.
lOw hEAT OuTPuT
PArTIAllY burNEd PEllETS
1. Feed rate too high.
2. Draft too low. (Check burn pot clean-out slide and
door gasket).
3. Burn pot or heat exchanger fins may need to be
cleaned.
4. Combination of all of the above.
1. Feed rate too low
2. Draft too low because of gasket leak.
3. Poor quality or damp pellets
4. Combination of 1. and 2.
helpful hints
removing Ashes
Cleaning burn Pot
Turn the Temperature Dial to minimum approximately
30 minutes before removing ashes. This will result in a
cooler stove and ash pan.
Whenever your stove is not burning, take the
opportunity to scrape the burn pot to remove carbon
buildup. A vacuum cleaner is handy to remove the
residue. Be sure the stove is cold if you use a vacuum.
Maximum feed settings are not needed in most cases.
Operating in the normal range is recommended when
maximum heat output is not required. The ESP probe
prevents the stove from being over-fired.
Carbon buildup can be scraped loose with the fire
burning using the special tool provided with your stove.
Scrape the floor and sides of the burn pot. The carbon
will be pushed out by the incoming fuel. Always wear
gloves to do this.
Keep the stove free of dust and dirt.
Fuel
Pellet fuels are put into 3 categories in terms of ash content. Premium at 1% or less, Standard at 3% or less
and all others at 3% or more.
The P61 is capable of burning all 3 categories of pellets due to a patented feeder and burn pot system.
It should be noted, however, that higher ash content will require more frequent ash removal and may provide
less BTU's per lb. Normally, standard and high ash pellets cost less than premium pellets and can be cost effec-
tive when burned in the P61.
The moisture content must not exceed 8%. Higher moisture will rob BTU's and may not burn properly.
18
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications
23.5"
9"
5.250"
weight
249 lbs.
blower
135 cfm
Feed rate
hopper Capacity
Fuel
.75 to 7.5 lbs. per hr.
72 lbs.
wood Pellets
3 inch
Flue Size
Outside Air Size
On-board Fuse
2 3/8 in. Inside diameter
6 amp
19
Download from Www.Somanuals.com. All Manuals Search And Download.
wiring diagram
20
Download from Www.Somanuals.com. All Manuals Search And Download.
door Options
Door Frame
Ash Lip Trim
Ash Door Tile Frame
Brushed Stainless
Cutout Tile Plate
Optional Trim
decorative Tile
The door trim kit includes the door frame, the ash lip
trim, and the ash door tile frame. Available in brushed
stainless, gold or bright nickel, they add a beautiful
accent to your stove. To install, lay the frame face down
on a soft surface. Drill the four holes in the door using
the bit provided. You'll see there are dimples in the cast
iron showing where to drill. Fasten the door frame by
inserting the 4 threaded posts on the frame through the
door. The posts should line up with the 4 holes located
at the corners of the door. Once the posts are through
the door, fasten frame with 4 nuts and tighten until the
frame is snug.
Decorative tile is available in several designs. The tile
installs behind the trim on the ash door. Along with the
above pictured cut-out tile plate, there are ten different
picture tiles and four slate tiles available. See your
dealer for choices.
Cleaning Plated Trim
Gold or nickel plated hardware should never be buffed
or polished. Abrasive cleansers and metal polishes will
remove the plating and therefore should never be used.
If the plating needs to be cleaned, wait until the stove
is completely cool, then use a sponge, soap and water
to gently remove dirt and stains. Before relighting the
stove, remove all soap residue and wipe dry.
To install ash lip trim, simply slide the trim over the ash
lip and into the groove on the trim.
The ash door tile frame can be used with or without
the optional decorative tile. Slide the spring clip into the
channel on one end of the frame. Place the frame into
the recessed area on the door inserting the clip end
first. The tension of the spring holds the frame in place.
21
Download from Www.Somanuals.com. All Manuals Search And Download.
OPTIONS
Side heat Shields
hopper Extension
Side heat shields are available to reduce the clearance
to combustible materials.
The hopper extension allows you to put more pellet
fuel in the hopper and extends the burn time on one
load of pellets. The hopper extension adds 60 pounds
to the existing 72 pound hopper capacity, allowing you
to load 132 pounds of pellets at one time.
22
Download from Www.Somanuals.com. All Manuals Search And Download.
harman gold warranty
hArMAN gOld wArrANTY
6 YEAr TrANSFErAblE lIMITEd
wArrANTY (residential)
1 YEAr lIMITEd wArrANTY (Commercial)
Harman Home Heating warrants its products to be free from defects in material or workmanship, in normal use and service,
for a period of 6 years from the date of sales invoice and for mechanical and electrical failures, in normal use and service,
for a period of 3 years from the date of sales invoice.
If defective in material or workmanship, during the warranty period, Harman Home Heating will, at its option, repair or replace
the product as described below.
The warranty above constitutes the entire warranty with respect to Harman Home Heating products. HARMAN HOME
HEATING MAKES NO OTHER WARRANTY, EXPRESSED OR IMPLIED, INCLUDING “ANY” WARRANTY OF
MERCHANTABILITY, OR WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. No employee, agent, dealer, or
other person is authorized to give any warranty on behalf of Harman Home Heating. This warranty does not apply if the product
has been altered in any way after leaving the factory. Harman Home Heating and its agents assume no liability for “resultant
damages of any kind” arising from the use of its products. In addition, the manufacturer and its warranty administrator shall be
held free and harmless from liability from damage to property related to the operation, proper or improper, of the equipment.
THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF.
THESE WARRANTIES APPLY only if the device is installed and operated as recommended in the user’s manual.
THESE WARRANTIES WILL NOT APPLY if abuse, accident, improper installation, negligence, or use beyond rated
capacity causes damage.
HOW TO MAKE A CLAIM - Any claim under this warranty should be made to the dealer from whom this appliance was
purchased. Then contact is made with manufacturer, giving the model and serial numbers, the date of purchase, your dealer’s
name and address, plus a simple explanation of the nature of the defect. Extra costs such as mileage and overtime are not
covered. Nuisance calls are not covered by these warranties.
THIS WARRANTY IS LIMITED TO DEFECTIVE PARTS - REPAIR AND/OR REPLACEMENT AT HARMAN HOME
HEATING’S OPTION AND EXCLUDES ANY INCIDENTAL AND CONSEQUENTIAL DAMAGES CONNECTED
THEREWITH.
WARRANTY EXCLUSIONS: Failure due, but not limited to, fire, lightning, acts of God, power failures and/or surges, rust,
corrosion and venting problems are not covered. Damage and/or repairs including but not limited to; remote controls, filters,
fuses, knobs, glass, ceramic brick panels, ceramic fiber afterburners, door packing, tile, ceramic log sets, paint, batteries or
battery back-up and related duct work are not covered. Also excluded from this warranty are consumable or normal wear
items including but not limited to; flame guides, grates, coal bars, afterburner hoods, fire brick, gaskets. Additional exclusions
for corn stoves are burnpot housing weldment, burnpot grate weldment (pellet or corn), burnpot front plate (pellet or corn),
burnpot front plate lock, corn auger extension, ceramic insert, and ceramic insert plate. Additional or unusual utility bills
incurred due to any malfunction or defect in equipment and the labor cost of gaining access to or removal of a unit that
requires special tools or equipment are not covered. Maintenance needed to keep the stove in “good operating condition” is
not covered. This includes, but is not limited to, cleaning, adjustment of customer controls and customer education. Labor,
materials, expenses and/or equipment needed to comply with law and/or regulations set forth by any governmental agencies
are not covered.
This Warranty provides specific legal rights and the consumer may have other rights that vary from state to state.
In the event of change in ownership, the remaining portion of this warranty may be transferred to the new owner by sending
the new owner information to Harman Home Heating.
PLEASE READ THE LITERATURE BY THE MANUFACTURER FOR THE VARIOUS ACCESSORY DEVICES.
THE MANUFACTURER WARRANTS THESE ACCESSORY DEVICES, NOT HARMAN HOME HEATING OR THEIR
WARRANTY ADMINISTRATOR. FURTHERMORE, THESE ACCESSORY DEVICES MUST BE INSTALLED AND
USED ACCORDING TO THE RECOMMENDATIONS OF THE MANUFACTURER.
REMEDIES - The remedies set forth herein are exclusive and the liability of seller with respect to any contract or sale or
anything done in connection therewith, whether in Contract, in tort, under any warranty, or otherwise, shall not, except as
herein expressly provided, exceed the price of the equipment or part of which such liability is based.
CLARIFY - The above represents the complete warranty, which is given in connection with stoves, manufactured by Harman
Home Heating. No other commitments, verbal or otherwise, shall apply except by a written addendum to this warranty.
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
|