Instructions/Parts List
CycleFlo II
Pneumatic Pump Controller
309004C
ENG
Controls pump speed for precise batching, metering, and dosing of fluids at high or low
pressures and flow rates.
Not for use in explosive atmospheres.
Important Safety Instructions
Read all warnings and instructions in this manual.
Save these instructions.
Part No. 195265
120 psi (0.8 MPa, 8 bar) Maximum Air Working
Pressure
Integrated Air Valves with Silenced Exhaust
Infinite Cycle Rate Adjustment Between 10 and
200 cpm
Standard 120 VAC Power
Download from Www.Somanuals.com. All Manuals Search And Download.
Warning Symbol
Caution Symbol
This symbol alerts you to the possibility of serious This symbol alerts you to the possibility of damage
injury or death if you do not follow the instructions. to or destruction of equipment if you do not follow
the instructions.
Equipment Misuse Hazard
Equipment misuse can cause the equipment to rupture or malfunction and result in serious
injury.
•
•
•
This equipment is for professional use only.
Read all instruction manuals, tags, and labels before operating the equipment.
Use the equipment only for its intended purpose. If you are uncertain about usage, call
your Graco distributor.
•
Other than for installation purposes do not alter or modify this equipment. Use only
genuine Graco parts and accessories.
•
•
•
Check equipment daily. Repair or replace worn or damaged parts immediately.
Do not exceed the maximum working pressure of the lowest rated system component.
Route hoses away from traffic areas, sharp edges, moving parts, and hot surfaces. Do
not expose Graco hoses to temperatures above 200 F (93 C) or below 0 F (-18 C).
•
•
Do not lift pressurized equipment.
Comply with all applicable local, state, and national fire, electrical and safety
regulations.
3
309004
Download from Www.Somanuals.com. All Manuals Search And Download.
Fire, Explosion, and Electric Shock Hazard
Improper grounding, poor air ventilation, open flames, or sparks can cause a hazardous
condition and resulting fire or explosion and serious injury.
•
•
•
•
•
Ground the equipment.
Proper grounding dissipates static electricity generated in the equipment.
This equipment is not intended for intrinsically safe areas.
Keep the dispense area free of debris, including solvent, rags, and gasoline.
If there is any static sparking or you feel an electric shock while using the equipment,
stop operating immediately. Do not use the equipment until you have identified and
corrected the problem.
•
•
Make sure all electrical work is performed only by a qualified electrician.
Have any checks, installation or service to electrical equipment performed by a
qualified electrician only.
•
Make sure all electrical equipment is installed and operated in compliance with local
and applicable codes.
•
•
•
•
Make sure power is disconnected when servicing and repairing equipment.
Keep liquids away from the electrical components.
Disconnect electrical power at the main switch before servicing the equipment.
Never exceed maximum wattage of the supply unit.
4
309004
Download from Www.Somanuals.com. All Manuals Search And Download.
General Description
The CycleFlo II is a pneumatic pump controller that allows precise control over the cycle rate of the pump and
therefor the flow rate.
The pump cycle is initiated by a 120 volt signal. The pump cycle may be initiated by some other piece of equipment
such as a timer or a pH controller. An isolation relay may be required in some installations. Always follow local and
applicable electrical codes. The CycleFlo II will halt the pump cycle whenever the 120 volt signal is removed.
Installation
Electrical Connections
An access hole with a strain relief installed has been provided for the external power connection. Due to the unique
requirements of each installation, access holes have not been provided for the other optional external wiring
connections such as the external air supply
valve signal. Have a qualified electrician
determine the proper strain relief, wire type, and
wire size for your particular application. When
positioning or adding access holes, be careful
not to damage any internal components. Failure
Fire, Explosion, and Electric Shock
to use the proper strain relief, wire type and wire
size can cause damage to internal components
or personal injury.
Hazard
To reduce the risk of fire, explosion, or electric
shock:
There are three connections on the 120V input
signal terminal block (see Fig. 1). The two right-
hand connections are for line and neutral wires
respectively. The left-hand connection is for a
true earth ground.
•
The power source conduit is not an
adequate grounding for the system. The
unit must be grounded to a true earth
ground.
•
•
A qualified electrician must complete all
grounding and wiring connections and
check the resistance.
Refer to your local code for the
requirements for a “true earth ground” in
your area.
5
309004
Download from Www.Somanuals.com. All Manuals Search And Download.
Fig.1 - Electrical Diagrams
Cycle Rate
Adjustment
Relay
120 Volt
Signal
Solenoid
Valves
Pneumatic Connections
6
309004
Download from Www.Somanuals.com. All Manuals Search And Download.
The integrated air valves, have a common air inlet (1/4" NPT) port and two outlet ports A and B (1/4” Tube) toward
the front of the unit. The exhaust is silenced with a muffler. Do not exceed 120 psi at the air inlet to the unit. Refer to
your pump owner’s manual for the maximum air pressure limit of the pump.
B Outlet
Port
Exhaust
Muffler
Strain Relief
for Power
Supply LIne
Common
Air Inlet
A Outlet
Port
Failure to use the following recommended valve can cause damage to the unit and possible
personal injury. Follow the pressure relief procedure in the pump manual before moving or
servicing the pump.
The A and B outlet ports are to be connected to the A and B ports respectively on the Husky 205, or to the two air
valve control ports located on the air motors of pumps larger than the Husky 205. On pumps larger than the Husky
205, a three way solenoid valve (Graco Part Number 115606 or equivalent) MUST be installed on the main air
supply to the pump. This ensures that pressure is not generated by the pump when the controller is not operating.
The same signal used to start the CycleFlo II controller can also control this valve.
7
309004
Download from Www.Somanuals.com. All Manuals Search And Download.
Setup & Adjustment
Cycles Per Minute (CPM) Rate
The pump cycle rate is adjustable to accommodate different pump sizes, varying product viscosities and product
delivery speed. The pump cycle rate is measured in Cycles Per Minute (CPM), i.e. the number of times the pump
performs a pump cycle in one minute. One pump cycle consists of a momentary pressurization of each one of the
two diaphragms.
Adjustment
The CycleFlo II comes with a cycle rate adjustment relay
that can be adjusted using a screwdriver to control the
energizing and deenergizing rate of the built-in solenoid
Electric Shock Hazard
valves. This timer is adjustable between 10 and 200 cpm.
Turning the screw clockwise will decrease the cycle rate
of the pump. Turning the screw counter-clockwise will
increase the cycle rate of the pump.
To prevent accidental shock or
electrocution disconnect the supply
signal before opening the enclosure
cover.
Cycle rate adjustment
screw
8
309004
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Priming the Pump
Prime the pump by applying a 120 Volt signal to the controller to allow the temporary operation of the pump. This
cycle rate may be increased or decreased to facilitate pump priming. Shut off electrical supply before making
adjustments.
Operation Procedures
The controller and pump are now ready for operation. The pump will cycle at the preset rate any time a 120 Volt
signal is supplied to the controller.
Troubleshooting
The following is a list of possible problems and their causes.
Problem
No operation at all
Possible Cause & Remedy
1. No power to the CycleFlo – check power source to unit.
2. Damaged cycle rate adjustment relay – replace.
3. No or low air supply – check air supply to make sure there is
sufficient pressure and air available.
4. Bad wire connections – turn off power and check wire connections
from time delay relay to make sure they are all connected and
seated properly.
5. Bad solenoid valve(s) – turn off air supply and listen for ‘clicking’ on
solenoid valves; replace valves if no ‘clicking’ is audible.
Pump only operates on one side /
diaphragm.
1. Bad solenoid valve. Turn off and replace.
2. Damaged cycle rate adjustment relay.
9
309004
Download from Www.Somanuals.com. All Manuals Search And Download.
Parts
Cycle rate
adjustment
relay
Enclosure
Air Solenoid
Valves
Part No.
Description
-----
Enclosure
-----
Emblem (not shown – on front of unit)
115414
115418
Cycle rate adjustment relay
Air Solenoid Valves (Note: two valves are required per controller)
Optional Accessories
Part No.
Description
102518
115988
115606
Cord Set, Electrical
Tube, Polyurethane, 50 ft.
Valve, Solenoid, 110 VAC, 8.5W
----- Not sold separately.
10
309004
Download from Www.Somanuals.com. All Manuals Search And Download.
Typical Installation Diagram
CycleFlo II Controller
Chemical
Injector
CycleFlo II
Controller
110V on/off
Isolation Relay
(recommended)
Compressed Air In
On
Off
Control Signal (24VDC)
110 VAC
Solenoid
Valve #2
Solenoid
Valve #1
Air Supply
Solenoid Valve
*Monitor /
Controller
Husky 1040
Metering Pump
Out
Flow Controller
sends an on/off
signal (24VDC) to
the isolation relay to
control power to the
CycleFlo II.
*Flow
Sensors
Inline Mixers*
TI0335
* Provided by others
11
309004
Download from Www.Somanuals.com. All Manuals Search And Download.
Typical Installation Diagram
Control ON/OFF signal
(110VAC)
CycleFlo II
Controller
Compressed Air In
Diaphragm Pump
(Husky 205 shown)
*PH Controller,
Flow Controller
Timer, etc. sends 110
VAC on/off signal to
CycleFlo II
*
Flow Sensor
*
Provided by others
9410A
Technical Data
Power Requirements:
120Vac, 50/60 Hz, .2A, 24W
Air Supply:
120 psi (0.8 MPa, 8 bar) Max
12
309004
Download from Www.Somanuals.com. All Manuals Search And Download.
Mounting Hole Layout
All mounting tabs
may be placed in
either position
7 3/8”
(187 mm)
5”
(127 mm)
7 3/8”
(187 mm)
5”
(127 mm)
13
309004
Download from Www.Somanuals.com. All Manuals Search And Download.
Graco Standard Warranty
Graco warrants all equipment referenced in this document which is manufactured by Graco and bearing its name to be free from
defects in material and workmanship on the date of sale by an authorized Graco distributor to the original purchaser for use. With the
exception of any special, extended, or limited warranty published by Graco, Graco will, for a period of twelve months from the date of
sale, repair or replace any part of the equipment determined by Graco to be defective. This warranty applies only when the
equipment is installed, operated and maintained in accordance with Graco's written recommendations.
This warranty does not cover, and Graco shall not be liable for general wear and tear, or any malfunction, damage or wear caused by
faulty installation, misapplication, abrasion, corrosion, inadequate or improper maintenance, negligence, accident, tampering, or
substitution of non-Graco component parts. Nor shall Graco be liable for malfunction, damage or wear caused by the incompatibility
of Graco equipment with structures, accessories, equipment or materials not supplied by Graco, or the improper design,
manufacture, installation, operation or maintenance of structures, accessories, equipment or materials not supplied by Graco.
This warranty is conditioned upon the prepaid return of the equipment claimed to be defective to an authorized Graco distributor for
verification of the claimed defect. If the claimed defect is verified, Graco will repair or replace free of charge any defective parts. The
equipment will be returned to the original purchaser transportation prepaid. If inspection of the equipment does not disclose any
defect in material or workmanship, repairs will be made at a reasonable charge, which charges may include the costs of parts, labor,
and transportation.
THIS WARRANTY IS EXCLUSIVE, AND IS IN LIEU OF ANY OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT
NOT LIMITED TO WARRANTY OF MERCHANTABILITY OR WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE.
Graco's sole obligation and buyer's sole remedy for any breach of warranty shall be as set forth above. The buyer agrees that no
other remedy (including, but not limited to, incidental or consequential damages for lost profits, lost sales, injury to personal property,
or any other incidental or consequential loss) shall be available. Any action for breach of warranty must be brought within two (2)
years of the date of sale.
GRACO Makes no warranty and disclaims all implied warranties of merchantability and fitness for a particular purpose in connection
with accessories, equipment, materials or components sold but not manufactured by GRACO. These items sold, but not
manufactured by Graco (such as electric motors, switches, hose, etc.), are subject to the warranty, if any, of their manufacturer.
Graco will provide purchaser with reasonable assistance in making any claim for breach of these warranties.
In no event will Graco be liable for indirect, incidental, special or consequential damages resulting from Graco supplying equipment
hereunder, or the furnishing, performance, or use of any products or other goods sold hereto, whether due to a breach of contract,
breach of warranty, the negligence of Graco, or otherwise.
FOR GRACO CANADA CUSTOMERS
The parties acknowledge that they have required that the present document, as well as all documents, notices and legal proceedings
entered into, given or instituted pursuant hereto or relating directly or indirectly hereto, be drawn up in English. Les parties
reconnaissent avoir convenu que la rédaction du présent document ainsi que de tous les documents, avis et procédures judiciaires
exécutés, donnés ou intentés à la suite de ou en rapport, directement ou indirectement, avec les procédures concernées sera en
Anglais.
Graco Phone Number
TO PLACE AN ORDER, contact your Graco distributor, or call this number to identify the distributor closest to you:
Phone: 612-623-6921 or Toll Free: 1-800-328-0211 Fax: 612-378-3505
All written and visual data contained in this document reflects the latest product information available at the time of publication.
Graco reserves the right to make changes at any time without notice.