Goodman Mfg Heat Pump GSZ VSZ 13 SEER User Manual

®
TECHNICAL MANUAL  
GSZ/VSZ 13 SEER  
Split System Heat Pumps  
Refer to Service Manual RS6200006 for installation, operation, and troubleshooting information.  
All safety information must be followed as provided in the Service Manual.  
Refer to the appropriate Parts Catalog for part number information.  
Models listed on page 3.  
This manual is to be used by qualified, professionally trained HVAC technicians only. Goodman does  
not assume any responsibility for property damage or personal injury due to improper service  
procedures or services performed by an unqualified person.  
RT6212006Rev.5  
August 2010  
Copyright © 2007-2010 Goodman Manufacturing Company, L.P.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRODUCT IDENTIFICATION  
The model number is used for positive identification of component parts used in manufacturing. Please use this number  
when requesting service or parts information.  
GSZ130181A*  
GSZ130241A*  
GSZ130301A*  
GSZ130361A*  
GSZ130421A*  
GSZ130481A*  
GSZ130601A*  
VSZ130181A*  
VSZ130241A*  
VSZ130301A*  
VSZ130361A*  
VSZ130421A*  
VSZ130481A*  
VSZ130601A*  
GSZ130241B*  
GSZ130361B*  
VSZ130241B*  
VSZ130361B*  
GSZ130363A*  
GSZ130483A*  
GSZ130484A*  
GSZ130603A*  
GSZ130604A*  
* Indicates minor revision & is not used for order entry or inventory management  
The United States Environmental Protection Agency (“EPA”) has issued various regulations re-  
WARNING  
garding the introduction and disposal of refrigerants introduced into this unit. Failure to follow  
these regulations may harm the environment and can lead to the imposition of substantial fines.  
These regulations may vary by jurisdiction. Should questions arise, contact your local EPA office.  
Do not connect or use any device  
To prevent the risk of property  
WARNING  
WARNING  
thatisnotdesigncertifiedbyGood-  
damage, personal injury, or death,  
man for use with this unit. Serious  
do not store combustible materi-  
property damage, personal injury, reduced unit perfor-  
mance and/or hazardous conditions may result from the  
use of such non-approved devices.  
als or use gasoline or other flammable liquids or vapors  
in the vicinity of this appliance.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRODUCT DESIGN  
GSZ/VSZ13 models are available in 1 1/2 through 5 ton sizes  
and use R-410A refrigerant. They are designed for 208/230  
volt single phase applications.  
NOTE: This unit cannot be completely enclosed. At least  
one side must be unrestricted.  
These clearances will help avoid air recirculation. If installing  
two or more units at the same location, allow at least 24  
inches between units. If only one side is restricted (for ex-  
ample, against the outside wall of a house), the unit may be  
placed as close as 8" to that one wall.  
Select GSZ13 models are available in 208/230 and 460 volt  
3-phase applications. These models use R-410A refrigerant.  
The condenser air is pulled through the condenser coil by a  
direct drive propeller fan. This condenser air is then dis-  
charged out of the top of the cabinet.  
DO NOT locate the unit:  
* Directly under a vent termination for a gas appliance.  
* Within 3 feet of a clothes drier vent  
* Where the refreezing of defrost water would create  
a hazard  
These units are designed for free air discharge, so no addi-  
tional resistance like duct work shall be attached.  
The suction and liquid line connections on present models  
are of the sweat type for field piping with refrigerant type cop-  
per. Front seating valves are factory installed to accept the  
field run copper. The total refrigerant charge for a normal in-  
stallation is factory installed in the condensing unit. GSZ units  
are charged for the matching evaporator coil and a 15 foot  
refrigerant line set.  
* Where water may rise into the unit.  
Systems should be properly sized by heat gain and loss  
calculations made according to methods of the Air Condi-  
tioning Contractors Association (ACCA) or equivalent. It is  
the contractors responsibility to ensure the system has ad-  
equate capacity to heat or cool the conditioned space.  
NOT  
RECOMMENDED  
OK!  
B
OK!  
B
B
B
GSZ/VSZ models use high-efficiency Copeland® scroll  
"Ultratech" compressors which are specifically desgined for  
R-410A refrigerant. There are a number of design character-  
istics which are different from the scroll compared to the tra-  
ditional reciprocating compressor.  
"Ultratech" Series scroll compressors with Copeland®  
ComfortAlert diagnositics will not have a discharge thermo-  
stat. Some of the early model scroll compressors required  
discharge thermostats.  
A
AA  
AA  
AA  
OK!  
C
C
OK!  
AA  
AA  
AA  
OK!  
OK!  
AA  
A
Due to their design Scroll compressors are inherently more  
tolerant of small quantities of liquid refrigerant.  
C
C
NOTE: Even though the compressor section of a Scroll com-  
pressor is more tolerant of liquid refrigerant, continued  
floodback or flooded start conditions may wash oil from the  
bearing surfaces causing premature bearing failure.  
Minimum Airflow Clearance  
Model Type  
Residential  
A
B
C
AA  
20"  
24"  
"Ultratech" Series scroll compressors use "POE" or  
polyolester oil which is NOT compatible with mineral oil based  
lubricants like 3GS. "POE" oil must be used if additional oil  
is required.  
10"  
12"  
10"  
12"  
18"  
18"  
Light Commercial  
WARNING  
To avoid possible injury, explosion or death, practice  
safe handling of refrigerants.  
Operating pressures and amp draws may differ from stan-  
dard reciprocating and/or scroll compressors. This informa-  
tion may be found in the "Cooling Performance Data" sec-  
tion.  
This unit is for outdoor installation only. Refer to minimum  
figure for clearances from the sides of the unit to full walls  
and other objects.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRODUCT DESIGN  
Product Dimensions  
Model  
Dimensions - W x D x H  
G/VSZ130181A*  
G/VSZ130241A*  
G/VSZ130241B*  
G/VSZ130301A*  
26 x 26 x 32¼  
26 x 26 x 32¼  
26 x 26 x 32½  
26 x 26 x 32¼  
G/VSZ130361A*  
GSZ130363A*  
29 x 29 x 38¼  
G/VSZ130361B*  
G/VSZ130421A*  
29 x 29 x 32½  
29 x 29 x 38¼  
G/VSZ130481A*  
GSZ130483A*  
GSZ130484A*  
G/VSZ130601A*  
GZX130603A*  
GSZ130604A*  
29 x 29 x 34¼  
35½ x 35½ x 34¼  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
HEAT PUMP SPECIFICATIONS  
G/VSZ130[18-60]1A*  
Nominal Capacities  
Cooling Capacity, BTUH  
18,000  
17,000  
24,000  
23,000  
30,000  
26,400  
36,000  
34,000  
42,000  
40,500  
48,000  
44,000  
60,000  
58,000  
Heating Capacity, BTUH  
Compressor  
R.L. Amps  
9.0  
12.8  
58.3  
14.1  
73.0  
16.6  
79.0  
17.9  
19.8  
26.4  
L.R. Amps  
48.0  
112.0  
109.0  
134.0  
Low Pressure Switch  
Open  
22 PSIG  
50 PSIG  
22 PSIG  
50 PSIG  
22 PSIG  
50 PSIG  
22 PSIG  
50 PSIG  
22 PSIG  
50 PSIG  
22 PSIG  
50 PSIG  
22 PSIG  
50 PSIG  
Close  
High Pressure Switch  
Open  
610 PSIG  
420 PSIG  
610 PSIG  
420 PSIG  
610 PSIG  
420 PSIG  
610 PSIG  
420 PSIG  
610 PSIG  
420 PSIG  
610 PSIG  
420 PSIG  
610 PSIG  
420 PSIG  
Close  
Condenser Fan Motor  
Horsepower  
1/6  
1.10  
1/6  
1.10  
1/6  
1.10  
1/4  
1.50  
1/4  
1.50  
1/4  
1.50  
1/4  
1.50  
F.L. Amps  
Liquid Line, Inches O.D.*  
Suction Line, Inches O.D.*  
Refrigerant Charge  
Power Supply  
3/8"  
3/8"  
3/8"  
3/8"  
3/8"  
3/8"  
3/8"  
3/4"  
3/4"  
3/4"  
3/4"  
7/8"  
7/8"  
7/8"  
122.0  
208/230-60-1  
12.3  
122.0  
208/230-60-1  
17.1  
127.0  
208/230-60-1  
18.7  
171.0  
208/230-60-1  
22.3  
174.0  
208/230-60-1  
23.9  
222.0  
208/230-60-1  
26.3  
245.0  
208/230-60-1  
34.5  
Minimum Circuit Ampacity(1)  
Maximum Overcurrent Device(2)  
Electrical Conduit Size  
Power Supply (Inches)  
20  
25  
30  
35  
40  
45  
60  
1/2 or 3/4  
198  
1/2 or 3/4  
198  
1/2 or 3/4  
202  
1/2 or 3/4  
232  
1/2 or 3/4  
235  
1/2 or 3/4  
240  
1/2 or 3/4  
266  
Approximate Shipping Weight  
*
Up to 24' in equivalent line length  
(1) Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes.  
(2)  
Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.  
NOTES:  
Always check the S & R plate for electrical data on the unit being installed.  
Installer will need to supply 7/8" to 1-1/8" adapters for suction line connections (4 & 5 ton units).  
Installer will need to supply 3/4" to 7/8" adapters for suction line connections (3 ton unit).  
Unit is charged with refrigerant for 15' of 3/8" liquid line. System charge must be adjusted per Installation Instructions Final Charge  
Procedure.  
Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED BY THE  
OUTDOORUNIT,NOTTHEINDOORCOIL.  
NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and  
wires in accordance with all national and/or local electrical codes. Use copper wire only.  
Unit specifications are subject to change without notice. ALWAYS refer to the unit's serial plate for the most up-to-date general  
and electrical information.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
HEAT PUMP SPECIFICATIONS  
G/VSZ130[24,36]B*  
Nom inal Capac ities  
Cooling Capacity, B TUH  
24,000  
23,000  
36,000  
34,000  
Heating Capac ity , B TUH  
Com pres sor  
R.L. A m ps  
12.8  
58.3  
16.7  
79.0  
L.R. A m ps  
Low P ress ure S witch  
O pen  
22 P S IG  
50 P S IG  
22 P S IG  
50 P S IG  
Clos e  
High P ress ure S witch  
O pen  
610 P S IG  
420 P S IG  
610 P S IG  
420 P S IG  
Clos e  
Condenser Fan M otor  
Horsepower  
1/6  
1.10  
1/4  
1.50  
F.L. A m ps  
Liquid Line, Inches O .D.*  
S uction Line, Inc hes O .D.*  
Refrigerant Charge  
P ower S upply  
3/8"  
3/8"  
3/4"  
3/4"  
113.0  
208/230-60-1  
17.1  
131.0  
208/230-60-1  
22.3  
M inim um Circ uit A m pacity(1)  
M axim um O verc urrent Device(2)  
E lectric al Conduit S iz e  
25  
35  
P ower S upply (Inc hes)  
1/2 or 3/4  
162  
1/2 or 3/4  
182  
A pprox im ate S hipping W eight  
(1) Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes.  
(2) Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.  
(3)  
Tested and rated in accordance with AHRI Standard 210/240  
NOTES:  
Always check the S & R plate for electrical data on the unit being installed.  
Installer will need to supply 7/8" to 1-1/8" adapters for suction line connections (4 & 5 ton units).  
Installer will need to supply 3/4" to 7/8" adapters for suction line connections (3 ton unit).  
Unit is charged with refrigerant for 15' of 3/8" liquid line. System charge must be adjusted per Installation Instructions Final Charge  
Procedure.  
Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED BY THE  
OUTDOORUNIT,NOTTHEINDOORCOIL.  
NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and  
wires in accordance with all national and/or local electrical codes. Use copper wire only.  
Unit specifications are subject to change without notice. ALWAYS refer to the unit's serial plate for the most up-to-date general  
and electrical information.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
HEAT PUMP SPECIFICATIONS  
GSZ130[36-60][3,4]A*  
Nominal Capacities  
Cooling Capacity, BTUH  
36,000  
48,000  
48,000  
60,000  
60,000  
Heating Capacity, BTUH  
Decibels  
34,000  
74  
44,000  
76  
44,000  
76  
58,000  
75  
58,000  
75  
Compressor  
R.L. Amps  
10.4  
73.0  
13.1  
83.1  
6.1  
16.0  
110.0  
Scroll  
7.8  
L.R. Amps  
41.0  
52.0  
Type  
Scroll  
Scroll  
Scroll  
Scroll  
Condenser Fan Motor  
Horsepower  
1/4  
1/4  
1/4  
1/4  
1/4  
F.L. Amps  
1.50  
1.50  
0.80  
1.50  
0.80  
Refrigerant System  
Liquid Line, Inches O.D.*  
3
3/8"  
7/8"  
3/8"  
1 1/8"  
3/8"  
3/8"  
1 1/8"  
3/8"  
3/8"  
1 1/8"  
3/8"  
3/8"  
1 1/8"  
3/8"  
3
Suction Line, Inches O.D.*  
Liquid Valve Connection, Inches O.D.*  
Suction Valve Connection, Inches O.D.*  
Refrigerant Charge  
3/8"  
3/4"  
7/8"  
7/8"  
7/8"  
7/8"  
171.0  
0.068  
208/230-60-3  
14.5  
222.0  
222.0  
0.078  
460-60-3  
8.4  
245.0  
245.0  
0.088  
460-60-3  
10.6  
Piston Size  
0.078  
0.088  
Power Supply  
208/230-60-3  
17.9  
208/230-60-3  
21.5  
Minimum Circuit Ampacity(1)  
Maximum Overcurrent Device(2)  
Min / Max Volts  
20  
30  
15  
35  
15  
197 / 253  
197 / 253  
414 / 506  
197 / 253  
414 / 506  
Electrical Conduit Size  
Power Supply (Inches)  
1/2 or 3/4  
232  
1/2 or 3/4  
235  
1/2 or 3/4  
234  
1/2 or 3/4  
262  
1/2 or 3/4  
261  
Approximate Shipping Weight  
(1) Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes.  
(2)  
Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.  
Tested and rated in accordance with AHRI Standard 210/240  
(3)  
NOTES:  
Always check the S & R plate for electrical data on the unit being installed.  
Installer will need to supply 7/8" to 1-1/8" adapters for suction line connections (4 & 5 ton units).  
Installer will need to supply 3/4" to 7/8" adapters for suction line connections (3 ton unit).  
Unit is charged with refrigerant for 15' of 3/8" liquid line. System charge must be adjusted per Installation Instructions Final Charge  
Procedure.  
Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED BY THE  
OUTDOORUNIT,NOTTHEINDOORCOIL.  
NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and  
wires in accordance with all national and/or local electrical codes. Use copper wire only.  
Unit specifications are subject to change without notice. ALWAYS refer to the unit's serial plate for the most up-to-date general  
and electrical information.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
G/VSZ130181A*  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
G/VSZ130181A*  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
G/VSZ130241A*  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
G/VSZ130241A*  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
G/VSZ130241B*  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
G/VSZ130241B*  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
G/VSZ130301A*  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
G/VSZ130301A*  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
G/VSZ130361A*  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
G/VSZ130361A*  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
G/VSZ130361B*  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
G/VSZ130361B*  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
GZ130363A*  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
GZ130363A*  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
G/VSZ130421A*  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
G/VSZ130421A*  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
G/VSZ130481A*  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
G/VSZ130481A*  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
GSZ130483A*  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
GSZ130483A*  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
GSZ130484A*  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
GSZ130484A*  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
G/VSZ130601A*  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
G/VSZ130601A*  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
GSZ130603A*  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
GSZ130603A*  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
GSZ130604A*  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING PERFORMANCE DATA  
GSZ130604A*  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPLIT SYSTEM HEATING PERFORMANCE  
EXPANDED PERFORMANCE DATA  
MODEL: G/VSZ130181A* / AR*F182416**  
HEATING OPERATION  
Outdoor Am bient Tem perature  
65  
60  
55  
50  
47  
45  
40  
35  
30  
25  
20  
17  
15  
10  
5
0
-5  
-10  
MBh  
21.4  
20.2  
31.2  
1.64  
6.7  
19.0  
29.4  
1.61  
6.3  
17.8  
27.5  
1.58  
5.9  
17.0  
26.2  
1.56  
5.7  
16.5  
25.4  
1.54  
5.6  
15.3  
23.6  
1.51  
5.3  
14.1  
21.8  
1.48  
5.0  
13.3  
20.6  
1.46  
4.8  
12.3  
19.0  
1.42  
4.6  
11.3  
17.5  
1.39  
4.3  
10.7  
16.5  
1.37  
4.2  
10.3  
15.9  
1.36  
4.2  
9.2  
14.3  
1.32  
4.0  
8.2  
12.7  
1.29  
3.7  
7.2  
11.0  
1.26  
3.5  
6.1  
9.4  
5.0  
7.7  
DELTA T 33.0  
KW  
AMPS  
COP  
1.68  
7.3  
1.23  
3.2  
1.19  
2.9  
3.73  
12.8  
392  
145  
3.60  
12.3  
375  
134  
3.46  
11.8  
361  
126  
3.30  
11.3  
345  
115  
3.19  
10.9  
337  
109  
3.12  
10.7  
331  
105  
2.96  
10.1  
318  
96  
2.79  
9.5  
2.68  
9.2  
2.53  
8.7  
2.39  
8.2  
2.29  
7.8  
2.22  
7.6  
2.04  
7.0  
1.86  
6.3  
1.66  
5.7  
1.46  
5.0  
1.22  
4.2  
EER  
HI PR  
LO PR  
305  
86  
292  
77  
279  
69  
268  
61  
262  
57  
257  
55  
247  
46  
238  
40  
228  
34  
220  
29  
212  
23  
MODEL: G/VSZ130241A* / AR*F182416**  
HEATING OPERATION  
Outdoor Am bient Tem perature  
65  
60  
55  
50  
47  
45  
40  
35  
30  
25  
20  
17  
15  
10  
5
0
-5  
-10  
MBh  
DT  
28.9  
32.6  
2.20  
9.7  
27.4  
30.9  
2.15  
9.0  
25.8  
29.1  
2.11  
8.4  
24.1  
27.2  
2.07  
7.9  
23.0  
26.0  
2.04  
7.6  
22.3  
25.2  
2.02  
7.5  
20.7  
23.4  
1.98  
7.0  
19.1  
21.6  
1.94  
6.7  
16.7  
18.9  
1.75  
6.4  
15.4  
17.4  
1.71  
6.1  
14.2  
16.0  
1.67  
5.8  
13.4  
15.1  
1.65  
5.6  
12.9  
14.6  
1.63  
5.6  
11.6  
13.1  
1.59  
5.3  
10.3  
11.6  
1.56  
4.9  
9.0  
10.1  
1.52  
4.6  
7.6  
8.6  
6.3  
7.1  
KW  
1.48  
4.3  
1.44  
3.8  
AMPS  
COP  
EER  
3.85  
13.2  
407  
135  
3.72  
12.7  
390  
126  
3.57  
12.2  
375  
118  
3.41  
11.7  
358  
108  
3.30  
11.3  
350  
102  
3.23  
11.0  
343  
98  
3.06  
10.5  
330  
90  
2.89  
9.9  
2.79  
9.5  
2.63  
9.0  
2.48  
8.5  
2.38  
8.1  
2.31  
7.9  
2.13  
7.3  
1.93  
6.6  
1.73  
5.9  
1.51  
5.2  
1.27  
4.4  
HI PR  
LO PR  
317  
80  
303  
73  
290  
65  
278  
57  
272  
53  
267  
51  
257  
43  
247  
37  
237  
31  
228  
27  
220  
22  
MODEL: G/VSZ130241B*/ AR*F182416**  
HEATING OPERATION  
Outdoor Ambient Temperature  
65  
60  
55  
50  
47  
45  
40  
35  
30  
25  
20  
17  
15  
10  
5
0
-5  
-10  
MBh  
Delta T  
KW  
28.9  
33.5  
2.17  
10.1  
3.91  
13.3  
413  
27.4  
31.7  
2.12  
9.3  
25.8  
29.8  
2.08  
8.7  
24.1  
27.9  
2.04  
8.2  
22.3  
25.8  
2.00  
7.7  
20.7  
24.0  
1.96  
7.3  
19.1  
22.1  
1.91  
6.9  
16.9  
19.5  
1.80  
6.6  
15.6  
18.0  
1.76  
6.3  
14.3  
16.6  
1.72  
6.0  
13.6  
15.7  
1.70  
5.9  
13.0  
15.1  
1.68  
5.8  
11.7  
13.6  
1.64  
5.5  
10.4  
12.0  
1.60  
5.2  
9.1  
10.5  
1.57  
4.9  
7.7  
8.9  
6.3  
7.3  
23.0  
26.6  
2.02  
7.9  
1.52  
4.5  
1.49  
4.0  
AMPS  
COP  
3.77  
12.9  
395  
122  
3.62  
12.4  
380  
114  
3.46  
11.8  
364  
105  
3.34  
11.4  
355  
99  
3.27  
11.2  
348  
95  
3.10  
10.6  
335  
88  
2.92  
10.0  
321  
78  
2.74  
9.4  
2.59  
8.8  
2.44  
8.3  
2.33  
8.0  
2.27  
7.7  
2.08  
7.1  
1.89  
6.5  
1.69  
5.8  
1.48  
5.1  
1.25  
4.3  
EER  
HI PR  
LO PR  
308  
70  
294  
63  
282  
55  
275  
51  
271  
50  
260  
42  
250  
36  
240  
30  
231  
27  
223  
21  
131  
MODEL: G/VSZ130301A* / AR*F30301**  
HEATING OPERATION  
Outdoor Am bie nt Te m pe rature  
65  
60  
55  
50  
47  
45  
40  
35  
30  
25  
20  
17  
15  
10  
5
0
-5  
-10  
MBh  
DELTA T  
KW  
33.2  
29.3  
2.52  
9.7  
31.4  
27.7  
2.47  
9.0  
29.6  
26.1  
2.42  
8.5  
27.6  
24.4  
2.37  
8.0  
26.4  
23.3  
2.35  
7.7  
25.6  
22.6  
2.32  
7.6  
23.8  
21.0  
2.28  
7.2  
21.9  
19.3  
2.23  
6.9  
19.9  
17.6  
2.37  
6.6  
18.4  
16.2  
2.32  
6.3  
16.9  
14.9  
2.26  
6.0  
16.0  
14.1  
2.23  
5.9  
15.4  
13.6  
2.21  
5.8  
13.8  
12.2  
2.16  
5.6  
12.3  
10.8  
2.11  
5.2  
10.7  
9.4  
9.1  
8.0  
7.5  
6.6  
2.05  
5.0  
2.00  
4.6  
1.95  
4.2  
A MPS  
COP  
3.86  
13.2  
366  
129  
3.72  
12.7  
351  
119  
3.57  
12.2  
337  
112  
3.41  
11.6  
323  
103  
3.29  
11.3  
315  
97  
3.22  
11.0  
309  
93  
3.05  
10.4  
297  
86  
2.88  
9.8  
2.46  
8.4  
2.32  
7.9  
2.19  
7.5  
2.10  
7.2  
2.04  
7.0  
1.88  
6.4  
1.70  
5.8  
1.52  
5.2  
1.34  
4.6  
1.12  
3.8  
EER  
HI PR  
LO PR  
285  
76  
273  
69  
261  
62  
250  
54  
244  
50  
240  
49  
231  
41  
222  
35  
213  
30  
205  
26  
198  
20  
High pressure is measured at the liquid service valve (the smaller valve).  
Low pressure is measured at the gauge port connection.  
AMPS = Outdoor unit amps (comp.+fan)  
KW = Total system power  
Calculations are based on nominal CFM and 70 °F indoor dry bulb.  
*Note:ShadedareaisAHRIRatingConditionsat 47°outdoorambienttemberature  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPLIT SYSTEM HEATING PERFORMANCE  
EXPANDED PERFORMANCE DATA  
MODEL: G/VSZ130361A* / AR*F364216**  
HEATING OPERATION  
Outdoor Ambient Temperature  
65  
60  
55  
50  
47  
45  
40  
35  
30  
25  
20  
17  
15  
10  
5
0
-5  
-10  
MBh  
42.7  
40.5  
29.4  
3.01  
13.2  
3.93  
13.4  
356  
123  
38.1  
27.7  
2.96  
12.3  
3.77  
12.9  
343  
115  
35.6  
25.9  
2.90  
11.6  
3.59  
12.3  
328  
106  
32.9  
23.9  
2.85  
11.0  
3.39  
11.6  
314  
30.6  
22.2  
2.79  
10.4  
3.21  
11.0  
302  
28.2  
20.5  
2.74  
9.9  
19.9  
14.5  
2.82  
9.4  
18.4  
13.4  
2.76  
9.0  
16.9  
12.3  
2.70  
8.6  
16.0  
11.6  
2.67  
8.4  
15.4  
11.2  
2.64  
8.3  
13.8  
10.0  
2.58  
7.9  
12.3  
8.9  
10.7  
7.8  
9.1  
6.6  
7.5  
5.4  
34.0  
24.7  
2.87  
11.2  
3.47  
11.8  
320  
100  
DELTA T 31.0  
KW  
AMPS  
COP  
3.07  
14.2  
4.07  
13.9  
372  
133  
2.52  
7.4  
2.46  
7.0  
2.40  
6.5  
2.35  
5.8  
3.02  
10.3  
290  
2.07  
7.1  
1.95  
6.7  
1.84  
6.3  
1.76  
6.0  
1.71  
5.8  
1.57  
5.4  
1.42  
4.9  
1.27  
4.3  
1.11  
3.8  
0.93  
3.2  
EER  
HI PR  
LO PR  
277  
71  
265  
64  
254  
56  
248  
52  
244  
50  
235  
42  
226  
37  
216  
31  
209  
27  
201  
21  
96  
89  
79  
MODEL: G/VSZ130361B* / AR*F364216**  
HEATINGOPERATION  
Outdoor Ambient Temperature  
65  
60  
55  
50  
47  
45  
40  
35  
30  
25  
20  
17  
15  
10  
5
0
-5  
-10  
MBh  
Delta T  
KW  
42.7  
33.0  
3.09  
14.0  
4.05  
13.8  
383  
40.5  
31.2  
3.03  
13.0  
3.91  
13.4  
368  
38.1  
29.4  
2.97  
12.1  
3.76  
12.8  
353  
35.6  
27.5  
2.90  
11.4  
3.59  
12.3  
338  
32.9  
25.4  
2.84  
10.8  
3.39  
11.6  
324  
96  
30.6  
23.6  
2.79  
10.2  
3.21  
11.0  
311  
89  
28.2  
21.8  
2.73  
9.7  
2.6  
2.0  
2.4  
1.9  
2.2  
1.7  
2.1  
1.6  
2.0  
1.6  
1.8  
1.4  
1.6  
1.2  
1.4  
1.1  
1.2  
0.9  
1.0  
0.8  
34.0  
26.2  
2.87  
11.0  
3.47  
11.8  
330  
2.70  
9.3  
2.64  
8.8  
2.58  
8.4  
2.54  
8.2  
2.52  
8.1  
2.45  
7.7  
2.39  
7.2  
2.33  
6.8  
2.27  
6.3  
2.21  
5.6  
AMPS  
COP  
3.03  
10.4  
299  
79  
0.28  
1.0  
0.27  
0.9  
0.25  
0.9  
0.24  
0.8  
0.23  
0.8  
0.22  
0.7  
0.20  
0.7  
0.18  
0.6  
0.15  
0.5  
0.13  
0.4  
EER  
HI PR  
LO PR  
286  
71  
273  
64  
262  
56  
256  
52  
251  
50  
242  
42  
233  
37  
223  
31  
215  
27  
208  
21  
133  
123  
115  
106  
100  
MODEL: GSZ130363A* / AR*F364216**  
HEATING OPERATION  
Outdoor Ambient Temperature  
65  
60  
55  
50  
47  
45  
40  
30.6  
22.2  
2.63  
7.4  
35  
28.2  
20.5  
2.58  
7.0  
30  
19.9  
14.5  
2.42  
6.7  
25  
18.4  
13.4  
2.37  
6.5  
20  
16.9  
12.3  
2.32  
6.2  
17  
16.0  
11.6  
2.29  
6.0  
15  
15.4  
11.2  
2.27  
6.0  
10  
13.8  
10.0  
2.22  
5.7  
5
0
-5  
9.1  
6.6  
2.07  
4.7  
1.29  
4.4  
215  
28  
-10  
7.5  
MBh  
DT  
42.7  
31.0  
2.90  
9.9  
40.5  
29.4  
2.84  
9.2  
38.1  
27.7  
2.79  
8.7  
35.6  
25.9  
2.73  
8.2  
34.0  
24.7  
2.70  
7.9  
32.9  
23.9  
2.68  
7.8  
12.3  
8.9  
10.7  
7.8  
5.4  
KW  
2.17  
5.3  
2.12  
5.1  
2.02  
4.3  
AMPS  
COP  
EER  
4.32  
14.8  
383  
138  
4.17  
14.2  
368  
128  
4.00  
13.7  
353  
120  
3.81  
13.0  
338  
110  
3.68  
12.6  
330  
104  
3.60  
12.3  
324  
100  
3.41  
11.6  
311  
92  
3.21  
11.0  
299  
82  
2.41  
8.2  
2.27  
7.8  
2.14  
7.3  
2.05  
7.0  
1.99  
6.8  
1.82  
6.2  
1.65  
5.7  
1.48  
5.0  
1.08  
3.7  
HI PR  
LO PR  
286  
74  
273  
66  
262  
58  
256  
54  
251  
52  
242  
44  
233  
38  
223  
32  
208  
22  
High pressure is measured at the liquid service valve (the smaller valve).  
Low pressure is measured at the gauge port connection.  
AMPS = Outdoor unit amps (comp.+fan)  
KW = Total system power  
Calculations are based on nominal CFM and 70 °F indoor dry bulb.  
*Note:ShadedareaisAHRIRatingConditionsat 47°outdoorambienttemberature  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPLIT SYSTEM HEATING PERFORMANCE  
EXPANDED PERFORMANCE DATA  
MODEL: G/VSZ130421A* / AR*F36421**  
Outdoor Am bient Tem perature  
HEATING OPERATION  
65  
60  
55  
50  
47  
45  
40  
35  
30  
25  
20  
17  
15  
10  
5
0
-5  
-10  
MBh  
DT  
50.3  
34.5  
3.60  
16.9  
4.09  
14.0  
368  
47.6  
32.6  
3.53  
15.6  
3.95  
13.5  
353  
44.8  
30.7  
3.46  
14.5  
3.79  
12.9  
340  
41.9  
28.7  
3.39  
13.6  
3.62  
12.4  
325  
40.0  
27.4  
3.35  
13.1  
3.49  
11.9  
317  
97  
38.8  
26.6  
3.32  
12.9  
3.42  
11.7  
311  
93  
36.0  
24.7  
3.25  
12.1  
3.24  
11.1  
299  
86  
33.2  
22.8  
3.18  
11.5  
3.05  
10.4  
287  
76  
29.9  
20.5  
3.24  
10.9  
2.70  
9.2  
27.6  
18.9  
3.16  
10.4  
2.55  
8.7  
25.4  
17.4  
3.09  
9.9  
24.0  
16.5  
3.05  
9.7  
23.1  
15.9  
3.02  
9.5  
20.7  
14.2  
2.95  
9.0  
18.4  
12.6  
2.88  
8.4  
16.0  
11.0  
2.80  
7.9  
13.7  
9.4  
11.2  
7.7  
KW  
2.73  
7.2  
2.66  
6.4  
AMPS  
COP  
EER  
2.40  
8.2  
2.30  
7.9  
2.24  
7.6  
2.06  
7.0  
1.87  
6.4  
1.67  
5.7  
1.47  
5.0  
1.23  
4.2  
HI PR  
LO PR  
275  
69  
262  
62  
252  
54  
246  
50  
242  
49  
232  
41  
223  
35  
214  
30  
207  
26  
199  
20  
129  
119  
112  
103  
MODEL: G/VSZ130481A* /AR*F48601**  
HEATING OPERATION  
Outdoor Ambient Temperature  
65  
60  
55  
50  
47  
45  
40  
35  
30  
25  
20  
17  
15  
10  
5
0
-5  
-10  
MBh  
DELTA T  
KW  
55.3  
32.0  
3.93  
18.2  
4.11  
14.1  
380  
129  
52.4  
30.3  
3.87  
16.8  
3.96  
13.5  
364  
119  
49.3  
28.5  
3.80  
15.7  
3.80  
13.0  
350  
112  
46.1  
26.7  
3.73  
14.8  
3.62  
12.4  
335  
103  
44.0  
25.5  
3.69  
14.3  
3.49  
11.9  
327  
97  
42.6  
24.7  
3.66  
14.0  
3.41  
11.7  
321  
39.6  
22.9  
3.59  
13.2  
3.23  
11.0  
308  
36.5  
21.1  
3.52  
12.5  
3.03  
10.4  
296  
33.6  
19.5  
3.37  
12.0  
2.93  
10.0  
284  
31.1  
18.0  
3.30  
11.4  
2.76  
9.4  
28.6  
27.0  
15.6  
3.19  
10.6  
2.47  
8.5  
26.0  
15.0  
3.17  
10.5  
2.40  
8.2  
23.3  
13.5  
3.10  
9.9  
20.7  
12.0  
3.04  
9.3  
18.0  
10.4  
2.97  
8.7  
15.4  
8.9  
12.6  
7.3  
16.5  
3.23  
10.9  
2.59  
8.8  
2.90  
8.1  
2.84  
7.3  
AMPS  
COP  
2.20  
7.5  
1.99  
6.8  
1.78  
6.1  
1.55  
5.3  
1.30  
4.4  
EER  
HI PR  
LO PR  
271  
260  
54  
254  
50  
249  
49  
240  
41  
231  
35  
221  
30  
213  
26  
206  
20  
93  
86  
76  
69  
62  
MODEL: G/VSZ130601A* / AR*F48601**  
HEATING OPERATION  
Outdoor Ambient Temperature  
65  
60  
55  
50  
47  
45  
40  
35  
30  
25  
20  
17  
15  
10  
5
0
-5  
-10  
MBh  
72.9  
69.0  
35.5  
5.11  
22.2  
3.95  
13.5  
399  
123  
65.0  
33.4  
5.01  
20.7  
3.79  
13.0  
383  
115  
60.7  
31.2  
4.92  
19.5  
3.62  
12.4  
367  
106  
56.2  
28.9  
4.82  
18.4  
3.41  
11.7  
351  
52.2  
26.9  
4.72  
17.3  
3.23  
11.1  
338  
48.1  
24.8  
4.63  
16.4  
3.05  
10.4  
324  
44.9  
23.1  
4.66  
15.7  
2.82  
9.6  
41.4  
21.3  
4.56  
15.0  
2.66  
9.1  
38.1  
19.6  
4.46  
14.2  
2.50  
8.6  
36.0  
18.5  
4.40  
13.9  
2.40  
8.2  
34.7  
17.8  
4.36  
13.7  
2.33  
8.0  
31.1  
16.0  
4.26  
13.0  
2.14  
7.3  
27.6  
14.2  
4.16  
12.1  
1.94  
6.6  
24.0  
12.4  
4.06  
11.3  
1.73  
5.9  
20.5  
10.6  
3.96  
10.5  
1.52  
5.2  
16.8  
8.6  
58.0  
29.8  
4.86  
18.8  
3.49  
11.9  
358  
100  
DELTA T 37.5  
KW  
AMPS  
COP  
5.21  
24.0  
4.10  
14.0  
416  
133  
3.86  
9.4  
1.28  
4.4  
EER  
HI PR  
LO PR  
310  
296  
285  
278  
52  
273  
50  
262  
42  
252  
37  
242  
31  
233  
27  
225  
21  
96  
89  
79  
71  
64  
56  
High pressure is measured at the liquid service valve (the smaller valve).  
Low pressure is measured at the gauge port connection.  
AMPS = Outdoor unit amps (comp.+fan)  
KW = Total system power  
Calculations are based on nominal CFM and 70 °F indoor dry bulb.  
*Note:ShadedareaisAHRIRatingConditionsat 47°outdoorambienttemberature  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPLIT SYSTEM HEATING PERFORMANCE  
EXPANDED PERFORMANCE DATA  
MODEL: GSZ130483A* / AR*F486016**  
HEATING OPERATION  
Outdoor Ambient Temperature  
65  
60  
55  
50  
47  
44.0  
25.5  
3.68  
8.8  
45  
42.6  
24.7  
3.65  
8.6  
40  
39.6  
22.9  
3.58  
8.2  
35  
36.5  
21.1  
3.51  
7.8  
30  
33.6  
19.5  
3.49  
7.5  
25  
31.1  
18.0  
3.42  
7.2  
20  
28.6  
16.5  
3.34  
6.8  
17  
27.0  
15.6  
3.30  
6.7  
15  
26.0  
15.0  
3.27  
6.6  
10  
23.3  
13.5  
3.20  
6.3  
5
0
-5  
15.4  
8.9  
-10  
12.6  
7.3  
MBh  
DT  
55.3  
32.0  
3.94  
11.1  
4.10  
14.0  
386  
52.4  
30.3  
3.87  
10.3  
3.96  
13.5  
370  
49.3  
28.5  
3.80  
9.7  
46.1  
26.7  
3.72  
9.1  
20.7  
12.0  
3.12  
5.9  
18.0  
10.4  
3.05  
5.6  
KW  
2.98  
5.2  
2.90  
4.7  
AMPS  
COP  
EER  
3.80  
13.0  
356  
110  
3.62  
12.4  
340  
101  
3.50  
11.9  
332  
95  
3.42  
11.7  
326  
91  
3.24  
11.1  
313  
84  
3.05  
10.4  
300  
75  
2.82  
9.6  
2.66  
9.1  
2.50  
8.6  
2.39  
8.2  
2.33  
7.9  
2.14  
7.3  
1.94  
6.6  
1.73  
5.9  
1.51  
5.2  
1.27  
4.3  
HI PR  
LO PR  
288  
68  
275  
60  
264  
53  
258  
49  
253  
48  
243  
40  
234  
35  
224  
29  
216  
26  
209  
20  
126  
117  
MODEL: GSZ130484A* / AR*F486016**  
HEATING OPERATION  
Outdoor Ambient Temperature  
65  
60  
55  
50  
47  
44.0  
25.5  
3.68  
4.9  
45  
42.6  
24.7  
3.65  
4.8  
40  
39.6  
22.9  
3.58  
4.6  
35  
36.5  
21.1  
3.51  
4.4  
30  
33.6  
19.5  
3.49  
4.2  
25  
31.1  
18.0  
3.42  
4.0  
20  
28.6  
16.5  
3.34  
3.8  
17  
27.0  
15.6  
3.30  
3.8  
15  
26.0  
15.0  
3.27  
3.7  
10  
23.3  
13.5  
3.20  
3.5  
5
0
-5  
15.4  
8.9  
-10  
12.6  
7.3  
MBh  
DT  
55.3  
32.0  
3.94  
6.1  
52.4  
30.3  
3.87  
5.7  
49.3  
28.5  
3.80  
5.4  
46.1  
26.7  
3.73  
5.1  
20.7  
12.0  
3.12  
3.3  
18.0  
10.4  
3.05  
3.2  
KW  
2.98  
3.0  
2.90  
2.7  
AMPS  
COP  
EER  
4.10  
14.0  
386  
126  
3.96  
13.5  
370  
117  
3.80  
13.0  
356  
110  
3.62  
12.4  
340  
101  
3.50  
11.9  
332  
95  
3.42  
11.7  
326  
91  
3.24  
11.1  
313  
84  
3.05  
10.4  
300  
75  
2.82  
9.6  
2.66  
9.1  
2.50  
8.6  
2.39  
8.2  
2.33  
7.9  
2.14  
7.3  
1.94  
6.6  
1.73  
5.9  
1.51  
5.2  
1.27  
4.3  
HI PR  
LO PR  
288  
68  
275  
60  
264  
53  
258  
49  
253  
48  
243  
40  
234  
35  
224  
29  
216  
26  
209  
20  
MODEL: GSZ130603A* /AR*F486016**  
HEATING OPERATION  
Outdoor Ambient Temperature  
65  
60  
55  
50  
47  
45  
40  
52.2  
26.9  
4.72  
9.5  
35  
48.1  
24.8  
4.62  
9.0  
30  
44.9  
23.1  
4.65  
8.6  
25  
41.4  
21.3  
4.55  
8.2  
20  
38.1  
19.6  
4.45  
7.8  
17  
36.0  
18.5  
4.39  
7.7  
15  
34.7  
17.8  
4.34  
7.6  
10  
31.1  
16.0  
4.24  
7.2  
5
0
-5  
-10  
16.8  
8.6  
MBh  
DT  
72.9  
37.5  
5.21  
13.1  
4.10  
14.0  
416  
69.0  
35.5  
5.11  
12.2  
3.95  
13.5  
399  
65.0  
33.4  
5.01  
11.4  
3.79  
13.0  
383  
115  
60.7  
31.2  
4.91  
10.7  
3.62  
12.4  
367  
58.0  
29.8  
4.86  
10.3  
3.50  
11.9  
358  
56.2  
28.9  
4.81  
10.1  
3.42  
11.7  
351  
96  
27.6  
14.2  
4.14  
6.7  
24.0  
12.4  
4.04  
6.3  
20.5  
10.6  
3.94  
5.8  
KW  
3.84  
5.2  
AMPS  
COP  
EER  
3.24  
11.1  
338  
89  
3.05  
10.4  
324  
79  
2.82  
9.6  
2.67  
9.1  
2.51  
8.6  
2.40  
8.2  
2.34  
8.0  
2.15  
7.3  
1.95  
6.7  
1.74  
6.0  
1.53  
5.2  
1.28  
4.4  
HI PR  
LO PR  
310  
71  
296  
64  
285  
56  
278  
52  
273  
50  
262  
42  
252  
37  
242  
31  
233  
27  
225  
21  
133  
123  
106  
100  
MODEL: GSZ130604A* /AR*F486016**  
HEATING OPERATION  
Outdoor Ambient Temperature  
65  
60  
55  
50  
47  
45  
56.2  
28.9  
4.81  
5.1  
40  
52.2  
26.9  
4.72  
4.8  
35  
48.1  
24.8  
4.62  
4.6  
30  
44.9  
23.1  
4.65  
4.4  
25  
41.4  
21.3  
4.55  
4.2  
20  
38.1  
19.6  
4.45  
4.1  
17  
36.0  
18.5  
4.39  
4.0  
15  
34.7  
17.8  
4.34  
3.9  
10  
31.1  
16.0  
4.24  
3.7  
5
0
-5  
-10  
16.8  
8.6  
MBh  
DT  
72.9  
37.5  
5.21  
6.5  
69.0  
35.5  
5.11  
6.1  
65.0  
33.4  
5.01  
5.7  
60.7  
31.2  
4.91  
5.4  
58.0  
29.8  
4.86  
5.2  
27.6  
14.2  
4.14  
3.5  
24.0  
12.4  
4.04  
3.3  
20.5  
10.6  
3.94  
3.1  
KW  
3.84  
2.8  
AMPS  
COP  
EER  
4.10  
14.0  
416  
133  
3.95  
13.5  
399  
123  
3.79  
13.0  
383  
115  
3.62  
12.4  
367  
106  
3.50  
11.9  
358  
100  
3.42  
11.7  
351  
96  
3.24  
11.1  
338  
89  
3.05  
10.4  
324  
79  
2.82  
9.6  
2.67  
9.1  
2.51  
8.6  
2.40  
8.2  
2.34  
8.0  
2.15  
7.3  
1.95  
6.7  
1.74  
6.0  
1.53  
5.2  
1.28  
4.4  
HI PR  
LO PR  
310  
71  
296  
64  
285  
56  
278  
52  
273  
50  
262  
42  
252  
37  
242  
31  
233  
27  
225  
21  
High pressure is measured at the liquid service valve (the smaller valve).  
Low pressure is measured at the gauge port connection.  
AMPS = Outdoor unit amps (comp.+fan)  
KW = Total system power  
Calculations are based on nominal CFM and 70 °F indoor dry bulb.  
*Note:ShadedareaisAHRIRatingConditionsat 47°outdoorambienttemberature  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PERFORMANCE DATA  
PERFORMANCE TEST  
All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor  
air cubic feet per minute (CFM) as listed in the Performance Data Sheets:  
If conditions vary from this, results will change as follows:  
1. As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (Delta T). Low  
and high side pressures and power will not change.  
2. As indoor CFM decreases, a slight increase will occur in indoor temperature drop (Delta T). A slight decrease will  
occur in low and high side pressures and power.  
A properly operating unit should be within plus or minus 2 degrees of the subcooling value shown in the Heat Pump  
Specifications.  
A properly operating unit should be within plus or minus 3 degrees of the typical (Delta T) value shown.  
A properly operating unit should be within plus or minus 7 PSIG of the HI PR shown.  
A properly operating unit should be within plus or minus 3 PSIG of the LO PR shown.  
A properly operating unit should be within plus or minus 3 Amps of the typical value shown.  
NOTE: Pressures are measured at the liquid and suction service valve ports.  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WIRING DIAGRAMS  
G/VSZ130[18-60]1[A/B]*  
HIGH VOLTAGE!  
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS  
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO  
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.  
Y L N R O O T C A N T C O L E O P  
E L B U O D E T A N R E L T  
Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WIRING DIAGRAMS  
GSZ130[36-60][3,4]A*  
HIGH VOLTAGE!  
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS  
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO  
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.  
Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Dyson Vacuum Cleaner DC02 User Manual
Esoteric DVD Player D 03 User Manual
Extron electronic Network Card DVI 201 A D User Manual
FoodSaver Food Saver V2240 CN User Manual
Fostex Recording Equipment X 30 User Manual
GE Fax Machine D780 User Manual
GE Label Maker RPN1605 User Manual
Gemini Musical Instrument PS 650I User Manual
Generac Portable Generator 005982 0 User Manual
Global Machinery Company Brush Cutter 25CC User Manual