Goodman Mfg Furnace GCH9 User Manual

TECHNICAL MANUAL  
GCH9  
40" 95% Gas Furnace  
Refer to Service Manual RS6610004 for installation, operation, and troubleshooting information.  
All safety information must be followed as provided in the Service Manual.  
Refer to the appropriate Parts Catalog for part number information.  
Model numbers listed on page 3.  
®
US  
C
This manual is to be used by qualified, professionally trained HVAC technicians only.  
Goodman does not assume any responsibility for property damage or personal  
injury due to improper service procedures or services performed by an unqualified  
person.  
RT6612019Rev.2  
April 2010  
Copyright © 2007, 2009-2010 Goodman Manufacturing Company, L.P.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRODUCT IDENTIFICATION  
The model and manufacturing number are used for positive identification of component parts used in manufacturing.  
Please use these numbers when requesting service or parts information.  
GCH90453BXA*  
GCH90703BXA*  
GCH90704CXA*  
GCH90904CXA*  
GCH90905DXA*  
GCH91155DXA*  
These models are Low NOx.  
The United States Environmental Protection Agency (“EPA”) has issued various regulations re-  
garding the introduction and disposal of refrigerants introduced into this unit. Failure to follow  
WARNING  
these regulations may harm the environment and can lead to the imposition of substantial fines.  
These regulations may vary by jurisdiction. Should questions arise, contact your local EPA office.  
Do not connect or use any device  
To prevent the risk of property  
WARNING  
WARNING  
that is not design certified by  
Goodman for use with this unit.  
damage, personal injury, or death,  
do not store combustible materials or use gasoline or  
other flammable liquids or vapors in the vicinity of this  
appliance.  
Serious property damage, personal injury, reduced unit  
performance and/or hazardous conditions may result  
from the use of such non-approved devices.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRODUCT DESIGN  
3. Conversion kits for high altitude natural or propane gas  
operation are available. See High Altitude Derate chart  
for details.  
General Operation  
The GCH9 furnaces are equipped with an electronic ignition  
device used to light the burners and an induced draft blower  
to exhaust combustion products.  
4. Installer must supply the following gas line fittings, de-  
pending on which entrance is used:  
An interlock switch prevents furnace operation if the blower  
door is not in place. Keep the blower access door in place  
except for inspection and maintenance.  
Left -- Two 90º Elbows, one close nipple, straight pipe.  
Right -- Straight pipe to reach gas valve.  
This furnace is also equipped with a self-diagnosing elec-  
tronic control module. In the event a furnace component is  
not operating properly, the control module LED will flash on  
and off in a factory-programmed sequence, depending on  
the problem encountered. This light can be viewed through  
the observation window in the blower access door. Refer to  
the Troubleshooting Chart for further explanation of the LED  
codes and Abnormal Operation - Integrated Ignition Control  
section in the Service Instructions for an explanation of the  
possible problem.  
Accessibility Clearances (Minimum)  
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS  
(INCHES)  
POSITION* FRONT SIDES REAR  
TOP  
FLUE FLOOR  
Upflow  
3
3
0
6
0
0
1
6
0
0
C
C
Horizontal  
*= All positioning is determined as installed unit is viewed from the front.  
C= If placed on combustible floor, floor MUST be wood only.  
NC= For instalaltion on non-combustible floors only. A non-combustible  
subbase must be used for installations on combustible flooring.  
The rated heating capacity of the furnace should be greater  
than or equal to the total heat loss of the area to be heated.  
The total heat loss should be calculated by an approved  
method or in accordance with “ASHRAE Guide” or “Manual  
J-Load Calculations” published by the Air Conditioning Con-  
tractors of America.  
24" at front is required for servicing or cleaning.  
Note: In all cases accessibility clearance shall take prece-  
dence over clearances from the enclosure where accessibil-  
ity clearances are greater. All dimensions are given in inches.  
*Obtain from: American National Standards Institute 1430  
Broadway New York, NY 10018  
High Altitude Derate  
When this furnace is installed at high altitude, the appropri-  
ate High Altitude orifice kit must be installed. This is re-  
quired due to the natural reduction in the density of both the  
gas fuel and combustion air as altitude increases. The kit  
will provide the proper design certified input rate within the  
specified altitude range.  
Location Considerations  
The furnace should be as centralized as is practical  
with respect to the air distribution system.  
Do not install the furnace directly on carpeting, tile, or  
combustible material other than wood flooring.  
When suspending the furnace from rafters or joists,  
use 3/8" threaded rod and 2” x 2” x 3/8” angle as  
shown in the Installation and Service Instructions. The  
length of the rod will depend on the application and  
clearance necessary.  
P ROP ANE AND HIG H ALTITUDE KITS  
M ODEL  
NUM BER  
0
to  
7 ,001 to  
9,000 ft.  
9 ,001 to  
11,000 ft.  
7 ,001 to  
11,000 ft.  
7,001 to  
1 1,00 0 ft.  
7,00 0 ft.  
LPM -031  
LPM -051  
LPM -062  
Prop ane  
C onve rs ion Kit  
(#55 Orifices )  
HANG1 1  
H ig h Altitude  
N atu ral Ga s Kit N atu ral Gas Kit  
(#44 Orifices ) (#45 Orifices )  
HANG1 2  
H ig h Altitude  
HALP 10  
H igh Altitude  
LP Gas Kit  
GCH9*****XA*  
TBD  
(#56 Orifices )  
When installed in a residential garage, the furnace  
must be positioned so the burners and ignition source  
are located not less than 18 inches (457 mm) above  
the floor and protected from physical damage by ve-  
hicles.  
1
2
LPM -03 / LPM -05 supports W hite-Rodgers 2 -stage valves only  
LPM -06 s upports Honeyw ell and W hite-Rodgers stage valves  
2
High altitude kits are purchased according to the installa-  
tion altitude and usage of either natural or propane gas. Refer  
to the chart above for a tabular listing of appropriate altitude  
ranges and corresponding manufacturer’s high altitude Natu-  
ral Gas and Propane Gas kits. For a tabular listing of appro-  
priate altitude ranges and corresponding manufacturer's High  
Altitude Pressure Switch kits, refer to either the Pressure  
Switch Trip Points & Usage Chart in this manual or the Ac-  
cessory Charts in Service Instructions.  
Notes:  
1. Installer must supply one or two PVC pipes: one for com-  
bustion air (optional) and one for the flue outlet (required).  
Vent pipe must be either 2” or 3” in diameter, depending  
upon furnace input, number of elbows, length of run and  
installation (1 or 2 pipes). The optional Combustion Air  
Pipe is dependent on installation/code requirements and  
must be 2” or 3” diameter PVC.  
2. Line voltage wiring can enter through the right or left side  
of the furnace. Low voltage wiring can enter through the  
right or left side of furnace.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMPONENT IDENTIFICATION  
10  
5
26  
27  
31  
24  
11  
28  
25  
3
15  
23  
14  
3
29  
30  
31  
18  
16  
17  
18  
19  
19  
20  
20  
13  
12  
2
21  
1
9
6
4
8
7
7
Downflow /Horizontal  
1
2
3
4
5
6
7
8
9
Two-Stage Gas Valve  
19 Coil Front Cover Drain Port  
20 Drain Line Penetrations  
21 Drain Trap  
Gas Line Entrance (Alternate)  
Pressure Switch(es)  
Gas Manifold  
22 Blower Door Interlock Switch  
23 Capicitor  
Combustion Air Intake Connection  
Hot Surface Igniter  
Rollout Limit  
24 Integrated Control Module  
(with fuse and diagnostic LED)  
25 24 Volt Thermostat Connections  
26 Transformer (40 VA)  
27 Circulator Blower  
Burners  
Flame Sensor  
10 Flue Pipe Connection  
11 Flue Pipe  
28 Auxiliary Limits  
12 Primary Limit  
29 Junction Box  
13 Gas Line Entrance  
30 Electrical Connection Inlet  
31 Coil Front Cover  
14 Flue Pipe Connection (Alternate)  
15 Rubber Elbow  
16 Induced Draft Blower  
17 Electrical Connection Inlets (Alternate)  
18 Coil Front Cover Pressure Tap  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMPONENT IDENTIFICATION  
GCH9*****XA*  
LEFT SIDE  
VIEW  
FRONTVIEW  
RIGHT SIDE  
VIEW  
28 3/4  
A
3/4  
3/4  
2 1/2  
AIR INTAKE PIPE  
2" PVC  
3/4  
VENT/FLUE PIPE  
2" PVC  
B
20 1/4  
(RETURN)  
2 1/16  
CONDENSATE  
DRAIN TRAP  
w/ 3/4" PVC  
DISCHARGE  
(RIGHT OR  
LOW VOLTAGE  
ELECTRICAL HOLE  
1 3/4  
1 3/4  
LOW VOLTAGE  
ELECTRICAL HOLE  
HIGH VOLTAGE  
ELECTRICAL HOLE  
40  
LEFT SIDE)  
ALTERNATE  
VENT/FLUE  
LOCATION  
6 1/8  
2 11/16  
28 5/16  
28 5/16  
HIGH VOLTAGE  
ELECTRICAL HOLE  
ALTERNATE  
AIR INTAKE LOCATION  
19 7/8  
18 13/16  
DRAIN  
TRAP  
DRAIN  
TRAP 2 5/8  
2 5/8  
C
L
C
L
RIGHT SIDE  
DRAIN LINE  
HOLES  
LEFT SIDE  
DRAIN LINE  
HOLES  
15 1/2  
14  
11 5/8  
9 3/4  
2
11 1/2  
9 13/16  
8 1/4  
7 3/8  
ALTERNATE GAS  
SUPPLY HOLE  
STANDARD GAS  
SUPPLY HOLE  
4 1/8  
18 5/8  
UNFOLDED FLANGES  
D
UNFOLDED FLANGES  
20 5/32  
FOLDED FLANGES  
E
FOLDED FLANGES  
AIR  
DISCHARGE  
AIR  
DISCHARGE  
DISCHARGE  
Cabinet Size  
A
B
C
D
E
GCH90453BX**  
GCH90703BX**  
17-1/2  
21  
16  
19-1/2  
23  
12-15/16  
15-15/16  
20-7/16  
12-1/8  
16  
13-5/8  
GCH90704CXA*  
GCH90904CXA*  
17-1/2  
20-7/8  
GCH90905DXA*  
GCH91155DXA*  
24-1/2  
19-3/8  
All dimensions are in inches.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRODUCT DESIGN  
PRESSURE SWITCH TRIP POINTS AND USAGE CHART  
0 to 7,000 ft.  
ID BLOWER  
PRESSURE  
SWITCH  
TRIP POINT  
COIL COVER  
PRESSURE SWITCH  
TRIP POINT  
ID BLOWER  
PRESSURE SWITCH  
MODEL  
PRESSURE  
SWITCH  
PART #  
PART #  
GCH90453BX  
GCH90703BX  
GCH90704CX  
GCH90904CX  
GCH90905CX  
GCH91155DX  
-.60  
-.60  
-.37  
-.60  
-.37  
-.60  
20197311  
20197311  
20197313  
20197311  
20197313  
20197311  
-.60  
-.60  
-.37  
-.60  
-.37  
-.60  
20197311  
20197311  
20197313  
20197311  
20197313  
20197311  
Note: Replacement pressure switch number is listed below high altitude kit number.  
Note: All negative pressure readings are in inches of water column (" w.c.).  
T.O.D. PRIMARY LIMIT  
Part Number  
20162906 20162904 20162907  
Open Setting (°F)  
GCH90453BX  
GCH90703BX  
GCH90704CX  
GCH90904CX  
GCH90905DX  
GCH91155DX  
170  
1
150  
155  
1
1
1
1
1
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRODUCT DESIGN  
ROLLOUT LIMIT SWITCHES  
Part Number  
10123517  
10123534  
Open Setting (°F)  
GCH90453BX  
GCH90703BX  
GCH90704CX  
GCH90904CX  
GCH90905DX  
GCH91155DX  
210  
1
220  
2
2
2
2
2
AUXILIARY LIMIT SWITCHES  
Part Number  
Open Setting (°F)  
GCH90453BX  
GCH90703BX  
GCH90704CX  
GCH90904CX  
GCH90905DX  
GCH91155DX  
10123518  
10123519  
170  
160  
2
2
2
2
2
2
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRODUCT DESIGN  
Coil Matches:  
A large array of Amana® brand coils are available for use with the GCH9 furnaces, in either counterflow or horizontal  
applications. These coils are available in both cased and uncased models (with the option of a field installed TXV expansion  
device). These 90%+ furnaces match up with the existing Amana® brand coils as shown in the chart below.  
Coil Matches (Goodman® units using R22 and R-410A):  
C
A
P
F 1824 A  
6
A
EXPANSION  
DEVICE:  
F: Flowrater  
REVISION  
A: Revision  
PRODUCT  
TYPE:  
C: Indoor Coil  
REFRIGERANT  
CHARGE:  
6: R-410A or R-22  
2: R-22  
4: R-410a  
CABINET FINISH:  
U: Unpainted  
P: Painted  
N: Unpainted Case  
NOMINAL WIDTH FOR GAS FURNACE  
A: Fits 14" Furnace Cabinet  
B: Fits 17 1/2" Furnace Cabinet  
C: Fits 21" Furnace Cabinet  
D: Fits 24 1/2" Furnace Cabinet  
N: Does Not Apply (Horizontal Slab Coils)  
APPLICATION  
A: Upflow/Downflow Coil  
H: Horizontal A Coil  
S: Horizontal Slab Coil  
NOMINAL CAPACITY RANGE  
@ 13 SEER  
1824: 1 1/2 to 2 Tons  
3030: 2 1/2 Tons  
3636: 3 Tons  
3642: 3 to 3 1/2 Tons  
3743: 3 to 3 1/2 Tons  
4860: 4 & 5 Tons  
4961: 4 & 5 Tons  
• All CAPF coils in B, C, & D widths have insulated blank off plates for use with one size smaller furnaces.  
• All CAPF coils have a CAUF equivalent.  
• All CHPF coils in B, C & D heights have an insulated Z bracket for use with one size smaller furnace.  
• All proper coil combinations are subject to being ARI rated with a matched outdoor unit.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRODUCT DESIGN  
Thermostats:  
NOTE: Complete lineup of thermostats can be found in the Thermostat Specification Sheets.  
Filters:  
Filters are required with this furnace and must be provided by the installer. The filters used must comply with UL900 or  
CAN/ULCS111 standards. Installing this furnace without filters will void the unit warranty.  
Upflow Filters  
This furnace has provisions for the installation of return air filters at the side and/or bottom return. The furnace will  
accommodate the following filter sizes depending on cabinet size:  
Side Return(s)  
Nominal  
Bottom Return  
Nominal  
Approx.  
Approx.  
Flow Area  
Cabinet  
Width  
(in.)  
Cabinet  
Width  
(in.)  
Flow Area  
Filter Size  
(in.)  
Filter Size  
(in.)  
(in2)  
400  
(in2)  
350  
400  
500  
All  
16 x 25 x 1  
17-1/2  
21  
14 x 25 x 1  
16 x 25 x 1  
20 x 25 x 1  
24-1/2  
RefertoMinimumFilterAreatablestodeterminefilterarearequirement. NOTE:Filterscanalsobeinstalledelsewherein  
the duct system such as a central return.  
COOLING AIRFLOW REQUIREMENT (CFM)  
COOLING AIRFLOW REQUIREMENT (CFM)  
600  
194*  
---  
800  
194*  
324*  
---  
1000  
240  
324*  
291*  
432*  
---  
1200  
288  
1400 1600  
2000  
---  
600  
388*  
---  
800  
388*  
647*  
---  
1000  
480  
647*  
583*  
863*  
---  
1200  
576  
1400  
---  
1600  
---  
2000  
---  
0453BXA*  
0703BXA*  
0704CXA*  
0904CXA*  
0905DXA*  
1155DXA*  
---  
---  
0453BXA*  
0703BXA*  
0704CXA*  
0904CXA*  
0905DXA*  
1155DXA*  
324*  
291*  
432*  
388*  
486*  
336  
336  
432*  
388*  
486*  
---  
---  
647*  
583*  
863*  
777*  
971*  
672  
672  
863*  
777*  
971*  
---  
---  
---  
384  
432*  
388*  
486*  
---  
---  
768  
863*  
777*  
971*  
---  
---  
---  
---  
---  
---  
---  
---  
---  
480  
486*  
---  
---  
960  
971*  
---  
---  
---  
---  
---  
---  
*Minimum filter area dictated by heating airflow requirement.  
*Minimum filter area dictated by heating airflow requirement.  
Disposable Minimum Filter Area (in2)  
Permanent Minimum Filter Area (in2)  
[Based on a 300 ft/min filter face velocity]  
[Based on 600 ft/min filter face velocity]  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRODUCT DESIGN  
Dual $aver Configuration & Operation  
Dual $aver  
This furnace is capable fo the following heating modes:  
• Single Stage (Factory Setting)  
• Modified Two-Stage  
> Fixed 5-Min. Low Stage  
> Auto Time (1-12 Min.) Low Stage  
To change from the factory single-stage operation,  
adjust the dipswitches on the ignition control as follows:  
OFF  
ON  
Mode  
Mode Dipswitch  
5 Min. Fixed  
Auto  
2nd Stage Delay  
Dipswitch  
Note: This furnace is designed to be used  
with a single-stage room thermosat.  
Start  
Start  
Call for Heat  
Call for Heat  
Safety Circuit Check  
Safety Circuit Check  
Start Furnace  
in Low Stage  
Start Furnace  
in Low Stage  
Low-Heat Blower  
Low-Heat Blower  
Delay Time (5 Min)  
Delay Time (1-12 Min)  
Gas Valve Switch  
to 2nd Stage  
Gas Valve Switch  
to 2nd Stage  
Blower Switch to  
Hi Heat Operation  
Blower Switch to  
Hi Heat Operation  
T-Stat Satisfied  
T-Stat Satisfied  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FURNACE SPECIFICATIONS  
GCH9  
MODEL  
GCH90453BX  
GCH90703BX GCH90704BX GCH90904CX GCH90905CX GCH91155DX  
Btuh Input (US)  
Output (US)  
46,000  
42,800  
38,502  
93  
69,000  
64,400  
57,753  
93  
69,000  
64,400  
57,753  
93  
92,000  
86,000  
77,004  
93  
92,000  
86,000  
77,004  
93  
115,000  
106,500  
96,255  
93  
BTUH Output (US) LP  
A.F.U.E.  
Rated External Static (" w.c.)  
Temperature Rise (°F)  
Pressure Switch Trip Point (" w.c.)  
Front Cover Pressure Switch Trip Point (" w.c)  
Blower Wheel (D" x W")  
Blower Horsepower  
.20" - .50"  
35-65  
-0.60  
-0.60  
10 X 8  
1/3  
.20" - .50"  
35-65  
-0.60  
-0.60  
10 X 8  
1/3  
.20" - .50"  
35-65  
-0.37  
-0.37  
10 X 10  
1/2  
.20" - .50"  
35-65  
-0.60  
-0.60  
10 X 10  
1/2  
.20" - .50"  
35-65  
-0.37  
-0.37  
11 X 10  
3/4  
.20" - .50"  
35-65  
-0.60  
-0.60  
11 x 10  
3/4  
Blower Speeds  
4
4
4
4
4
4
Max CFM @ 0.5 E.S.P.  
Power Supply  
1,200  
115-60-1  
9.40  
15  
1,200  
115-60-1  
9.40  
15  
1,600  
115-60-1  
13.80  
15  
1600  
115-60-1  
13.80  
15  
2000  
115-60-1  
13.20  
15  
2000  
115-60-1  
13.20  
15  
Minimum Circuit Ampacity (MCA)(1)  
Maximum Overcurrent Device(2)  
Transformer (VA)  
40  
40  
40  
40  
40  
40  
Primary Limit Setting (°F)  
Auxiliary Limit Setting (°F)  
Rollout Limit Setting (°F)  
Fan Delay On Heating  
170  
170  
170  
150  
170  
155  
160  
160  
170  
160  
170  
160  
210  
210  
210  
220  
220  
210  
30  
30  
30  
30  
30  
30  
Off Heating(3)  
150  
150  
150  
150  
150  
150  
Fan Delay On Cooling  
5
5
5
5
5
5
Off Cooling  
45  
45  
45  
45  
45  
45  
Fan Delay On - Fan Only  
Gas Supply Pressure (Natural/Propane) (" w.c.)  
Manifold Pressure (Natural/Propane)  
Orifice Size (Natural/Propane)  
Number of Burners  
0
0
0
0
0
0
7/11  
3.5/10  
43/55  
2
7/11  
3.5/10  
43/55  
3
7/11  
3.5/10  
43/55  
3
7/11  
3.5/10  
43/55  
4
7/11  
3.5/10  
43/55  
4
7/11  
3.5/10  
43/55  
5
Vent Connector Diameter (inches) (4)  
Shipping Weight (lbs.)  
2
2
2
2
2
2
132  
135  
136  
158  
172  
178  
(1) Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.  
(2) Maximum Overcurrent Protection Device: May use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.  
(3) Off Heating - this fan delay timing is adjustable (100 or 150 seconds), 150 seconds as shipped.  
(4) See Installation Instructions for appropriate vent diameter, length and number of elbows.  
NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in  
accordance with all national and/or local electrical codes. Use copper wire only.  
1. These furnaces are manufactured for natural gas operation. Optional kits are available for conversion to propane operation.  
2. For elevations above 2000 feet the rating should be reduced by 4% for each 1000 feet above sea level. The furnace must not be derated, orifice changes should only  
be made if necessary for altitude.  
3. The total heat loss from the structure as expressed in TOTAL BTU/HR must be calculated by the manufacturers method or in accordance with the "A.S.H.R.A.E.  
GUIDE" or "MANUAL J-LOAD CALCULATIONS" published by the AIR CONDITIONING CONTRACTORS OF AMERICA. The total heat loss calculated should be equal  
to or less than the heating capacity. Output based on D.O.E. test procedures.  
4. Minimum Circuit Ampacity calculated as: (1.25 x Circulator Blower Amps) + I.D. Blower Amps.  
Unit specifications are subject to change without notice. ALWAYS refer to the units serial plate for the most up-to-date general and electrical information.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BLOWER PERFORMANCE SPECIFICATIONS  
BLOWER PERFORMANCE  
(CFM & Temperature Rise vs. External Static Pressure)  
EXTERNAL STATIC PRESSURE (Inches Water Column)  
0.2 0.3 0.4 0.5  
Tons AC  
at 0.5"  
Model  
Motor  
Speed  
0.1  
0.6 0.7 0.8  
Heating Speed  
( As Shipped )  
ESP CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM CFM CFM  
HIGH  
MED  
3.0  
2.5  
2.0  
1.5  
3.0  
2.5  
2.0  
1.5  
4.0  
3.5  
3.0  
2.5  
4.0  
3.5  
3.0  
2.5  
5.0  
4.0  
3.5  
3.0  
5.0  
4.0  
3.5  
3.0  
1352 29 1318 30 1260 31 1202 33 1128 35 1044 955 853  
1214 32 1172 34 1123 35 1064 37 1012 39 938 859 741  
997 40 994 40 960 41 923 43 884 45 817 741 611  
757 52 753 52 734 54 704 56 674 59 620 524 438  
1449 41 1409 42 1326 45 1273 47 1201 49 1194 1136 1018  
1192 50 1172 51 1141 52 1094 54 1046 57 973 904 793  
981 61 962 62 943 63 917 65 888 67 830 764 665  
750 79 730 81 714 83 692 86 657 90 620 570 502  
2069 29 1965 30 1871 32 1756 34 1661 36 1549 1415 1275  
1752 34 1724 34 1667 36 1603 37 1488 40 1402 1290 1082  
1437 41 1437 41 1417 42 1369 43 1320 45 1256 1140 984  
1184 50 1177 50 1161 51 1132 52 1095 54 1047 928 837  
1970 40 1874 42 1757 45 1667 48 1566 51 1431 1334 1182  
1713 46 1650 48 1572 50 1510 52 1418 56 1313 1211 1079  
1439 55 1412 56 1370 58 1327 60 1260 63 1166 1078 956  
1183 67 1155 69 1122 71 1108 72 1062 75 1011 931 816  
2147 37 2114 37 2057 39 2030 39 1978 40 1889 1784 1713  
1675 47 1686 47 1640 48 1623 49 1557 51 1501 1455 1360  
1489 53 1470 54 1436 55 1409 56 1361 58 1318 1243 1130  
1307 61 1265 63 1234 64 1203 66 1168 68 1096 1053 991  
2134 46 2103 47 2029 48 1941 51 1906 51 1818 1733 1625  
1678 58 1643 60 1643 60 1577 62 1527 64 1489 1423 1339  
1453 68 1440 68 1426 69 1363 72 1349 73 1314 1253 1205  
1259 78 1239 79 1220 80 1181 83 1159 85 1118 1082 1015  
GCH90453BXA*  
(MED-HI)  
MED-LO  
LOW  
HIGH  
MED  
GCH90703BXA*  
(MED-HI)  
MED-LO  
LOW  
HIGH  
MED  
GCH90704CXA*  
(MED-HI)  
MED-LO  
LOW  
HIGH  
MED  
GCH90904CXA*  
(MED-HI)  
MED-LO  
LOW  
HIGH  
MED  
GCH90905DXA*  
(MED-HI)  
MED-LO  
LOW  
HIGH  
MED  
GCH91155DXA*  
(MED-HI)  
MED-LO  
LOW  
1. CFM in chart is without filters(s). Filters do not ship with this furnace, but must be provided by the installer.  
2. All furnaces ship as high speed cooling. Installer must adjust blower cooling speed as needed.  
3. For most jobs, about 400 CFM per ton when cooling is desirable.  
4. INSTALLATION IS TO BE ADJUSTED TO OBTAIN TEMPERATURE RISE WITHIN THE RANGE SPECIFIED ON THE RATING PLATE.  
5. The chart is for information only. For satisfactory operation, external static pressure must not exceed value shown on rating plate. The shaded  
area indicates ranges in excess of maximum external static pressure allowed when heating. The data for 0.6" w.c. to 0.8" w.c. is shown for  
air conditioning purposes only.  
6
The dashed (---) areas indicate a temperature rise not recommended for this model.  
7. The above chart is for U.S. furnaces installed at 0-4000 feet. At higher altitudes, a properly derated unit will have approximately the same  
temperature rise at a particular CFM, while the ESP at that CFM will be lower.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BLOWER PERFORMANCE SPECIFICATIONS  
E S I R E R U A T E R P M E T  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WIRING DIAGRAMS  
GCH9*****X[AA,AB]  
BLOWER  
INTEGRATED  
HUMIDIFIER  
24 VAC  
HUMIDIFIER  
OR  
COMPARTMENT  
DOOR SWITCH  
(OPEN WHEN  
DOOR OPEN)  
CONTROL MODULE  
GY  
TR (6)  
GND  
24 VAC  
GND (8)  
MVC (9)  
C
GAS  
VALVE  
HI  
115 VAC  
MVH (12)  
MVL(2)  
24V THERMO T  
STA  
PM  
CONNECTIONS  
C
C
NO  
C
G
R
W
Y
ID BLOWER  
PRESSURE  
SWITCH  
FRONT COVER  
PRESSURE SWITCH  
WH  
BK  
G
Y
NO  
PS (10)  
C
PSO(4)  
HLI (7)  
TO  
MICRO  
OR  
FUSE  
GY  
3
6
1
4
2
5
PK  
OR  
W
HLO (1)  
INTEGRATED  
CONTROL  
MODULE  
9
8
7
BL  
YL  
R
RO2 (11)  
RO1 (5)  
GR  
ON  
OFF  
11  
12  
10  
2ND  
STAGE  
DELAY  
OR  
BR  
OR  
*
GY  
OR  
MODE  
RD  
GY  
*
TH (3)  
24 VAC  
HEAT  
OFF  
DELAY  
40 VA  
TRANSFORMER  
*
FACTORYSETTINGS  
SHOWN  
WH  
FS  
XFMR-H  
115 VAC  
FLAME SENSOR  
SEE  
NOTE 6  
DIAGNOSTIC  
LED  
*
2
1
FS  
WH  
HOT SURFACE  
IGNITER  
115 VAC HOT AND PARK TERMINALS  
COOL-H  
HEAT-H  
IGN  
BK  
LINE-H  
SEE  
NOTE 4  
GND  
WH  
ID  
BLWR  
BK (HI)  
BL (MED)  
OR (MED LOW)  
RD (LOW)  
IND  
PK  
YL  
RD  
BK  
COOL-H  
CIRCULATOR  
BLWR  
BR  
BR  
CAPACITOR  
PU  
ELECTRONIC  
AIR CLEANER  
BLOWER COMPARTMENT  
BURNER COMPARTMENT  
GND  
EAC-H  
LINE-H  
MANUAL RESET  
AUXILIARY LIMITS  
(1) IN UPFLOW  
BLOWER DECK  
(2) IN C'FLOW  
JUNCTION BOX  
DOOR  
SWITCH  
BK  
BLOWER HOUSING  
WH  
WH  
INDUCED DRAFT  
BLOWER  
DISCONNECT  
WH  
PU  
BL  
GND  
Ø /60 HZ POWER SUPPLY WITH  
L
N
YL  
TO 115VAC/ 1  
OR  
PK  
RD  
OR  
OVERCURRENT PROTECTION DEVICE  
N
O
C
RD  
WH  
ID BLOWER  
PRESSURE  
SWITCH  
JUNCTION  
BOX  
BL  
24 VAC  
HUMIDIFIER  
FRONT COVER  
PRESSURE SWIT  
CH  
GY  
N
O
C
1
2 CIRCUIT  
CONNECTOR  
PM  
GY  
BR  
N
WH  
BK  
GND  
GR  
GND  
HOT  
SURFACE  
IGNITER  
2
C
L
FLAME  
3
OR  
HI  
SENSOR  
GAS VALVE  
0
STEADY ON = NORMAL OPERATION  
LOW VOLTAGE (24V)  
LOW VOLTAGE FIELD  
HI VOLTAGE (115V)  
HI VOLTAGE FIELD  
JUNCTION  
EQUIPMENT GND  
FIELD GND  
OFF  
= CONTROL FAILURE  
1
2
3
4
5
6
1 FLASH  
=
2 FLASHES = PRESSURE SWITCH STUCK CLOSED  
3 FLASHES = PRESSURE SWITCH STUCK OPEN  
FIELD SPLICE  
SWITCH (TEMP.)  
4 FLASHES = OPEN HIGH LIMIT  
5 FLASHES = FLAME SENSE WITHOUT GAS VALVE  
6 FLASHES =  
IGNITER  
TERMINAL  
SWITCH (PRESS.)  
INTERNAL TO  
INTEGRATED CONTROL  
7 FLASHES = LOW FLAME SIGNAL  
7
8
C
OVERCURRENT  
PROT. DEVICE  
8 FLASHES = CHECK IGNITER OR IMPROPER GROUNDING  
CONTINUOUS/RAPID FLASHES = REVERSED 115 VAC POLARITY  
PLUG CONNECTION  
NOTES:  
PK PINK  
COLOR CODES:  
YL YELLOW  
1. SET HEAT ANTICIPATOR ON ROOMTHERMOSTAT AT 0.7 AMPS.  
2. MANU 'S SPEC PARTS MUST BE USED WHEN SE  
BR BROWN  
WH WHITE  
BL BLUE  
GY GRAY  
RD RED  
FACTURER IFIEDREPLACEMENT RVICING.  
3. IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE FURNACE MUST BEREPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL  
°C. USE COPPERCONDUCTORS ONLY.  
OR ORANGE  
HAVING A TEMPERATURERATING OF AT LEAST 105  
4. IF HEATING AND COOLINGBLOWER SPEEDS ARE NOT THE SAME, DISCARD JUMPERBEFORECONNECTING BLOWER LEADS. UNUSED  
BLOWER LEAD T BE PLA ON "PAR TERMIN OF INTEGRATED CO TROL OR TAPED.  
PU PURPLE  
GN GREEN  
S MUS CED K" ALS  
N
BK BLACK  
5. UNIT MUST BE PERMANENTLY GROUNDED AND CONFORMTO N.E.C. ANDLOCAL CODES.  
6. TO RECALL THE LAST 5 FAULTS, MOST RECEN T TO LEAST RECENT, DEPRESS SWITCH FOR MORE THAN 2 SECONDS WHILE IN  
STANDBY (NO THERMOSTAT INPUTS)  
0140F00592 REV. A  
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WIRING DIAGRAMS  
GCH9*****XAC  
BLOWER  
INTEGRATED  
CONTROLMODULE  
HUMIDIFIER  
24VAC  
HUMIDIFIER  
OR  
COMPARTMENT  
DOORSWITCH  
(OPENWHEN  
DOOROPEN)  
GY  
TR(6)  
C
GND  
24VAC  
GAS  
VALVE  
GND(8)  
MVC(9)  
40VA  
TRANSFORMER  
HI  
PM  
115VAC  
MVH(12)  
24VTHERMOSTAT  
CONNECTIONS  
AUXILIARYLIMITCONTROLS  
C
C
G
R
W
Y
C
MVL(2)  
WH  
NO  
FRONTCOVER  
PRESSURESWITCH  
BK  
G
Y
PS(10)  
PSO(4)  
HLI(7)  
TO  
MICRO  
OR  
FUSE  
GY  
3
6
1
4
2
5
PU  
OR  
W
HLO(1)  
INTEGRATED  
CONTROL  
MODULE  
NO  
C
AUTORESETPRIMARY  
LIMITCONTROL  
9
8
7
BL  
YL  
R
IDBLOWER  
PRESSURE  
SWITCH  
GR  
RO2(11)  
ON  
OFF  
11  
12  
10  
2ND  
STAGE  
DELAY  
RO1(5)  
OR  
BR  
OR  
MANUALRESETROLLOUT  
LIMITCONTROL(S)  
(SINGLECONTROLON45KBTU)  
*
*
GY  
OR  
MODE  
RD  
GY  
TH(3)  
24VAC  
HEAT  
OFF  
DELAY  
40VA  
*
TRANSFORMER  
FACTORYSETTINGS  
SHOWN  
*
WH  
FS  
XFMR-H  
115VAC  
FLAMESENSOR  
SEE  
DIAGNOSTIC  
LED  
NOTE6  
2
1
FS  
WH  
HOTSURFACE  
IGNITER  
115VACHOTANDPARKTERMINALS  
COOL-H  
HEAT-H  
IGN  
BK  
LINE-H  
SEE  
GND  
NOTE4  
WH  
ID  
GY  
BLWR  
BK(HI)  
BL(MED)  
OR(MEDLOW)  
RD(LOW)  
IND  
PK  
RD  
L
O
H
E
A
T
-
H
BK  
CIRCULATOR  
BLOWER  
COOL-H  
CIRCULATOR  
BLWR  
BR  
BR  
YL  
I
H
H
-
T
A
E
H
CAPACITOR  
GY  
PU  
ELECTRONIC  
AIRCLEANER  
BLOWERCOMPARTMENT  
BURNERCOMPARTMENT  
GND  
EAC-H  
LINE-H  
JUNCTIONBOX  
DOOR  
SWITCH  
BK  
WH  
WH  
WARNING:  
INDUCEDDRAFT  
BLOWER  
DISCONNECTPOWER  
BEFORESERVICING.  
WIRINGTOUNIT  
MUSTBE  
PROPERLY  
POLARIZED  
DISCONNECT  
WH  
BL  
AUTORESET  
PRIMARYLIMIT  
CONTROL  
PU  
ANDGROUNDED.  
GND  
Ø/60HZPOWERSUPPLYWITH  
L
N
YL  
TO115VAC/1  
OR  
PK  
RD  
OR  
OVERCURRENTPROTECTIONDEVICE  
N
O
C
RD  
WH  
WARNING:DISCONNECTPOWERBEFORE  
SERVICING.WIRINGTOUNITMUSTBE  
PROPERLYPOLARIZEDANDGROUNDED.  
MANUALRESETROLLOUTLIMITCONTROL(S)  
(SINGLECONTROLON45KBTU)  
IDBLOWER  
PRESSURE  
SWITCH  
JUNCTION  
BOX  
BL  
24VAC  
HUMIDIFIER  
FRONTCOVER  
PRESSURESWITCH  
N
O
C
1
2CIRCUIT  
CONNECTOR  
PM  
GY  
GY  
N
WH  
BK  
GR  
GND  
GND  
HOT  
SURFACE  
IGNITER  
2
C
OR  
L
FLAME  
SENSOR  
3
BR  
DISCONNECT  
HI  
GASVALVE  
(HONEYWELL)  
0
1
STEADYON=NORMALOPERATION  
LOWVOLTAGE(24V)  
LOWVOLTAGEFIELD  
HIVOLTAGE(115V)  
HIVOLTAGEFIELD  
JUNCTION  
EQUIPMENTGND  
FIELDGND  
OFF  
=CONTROLFAILURE  
1FLASH  
=
SYSTEMLOCKOUT(RETRIESEXCEEDED)  
2FLASHES =PRESSURESWITCHSTUCKCLOSED  
3FLASHES =PRESSURESWITCHSTUCKOPEN  
2
3
4
5
6
FIELDSPLICE  
SWITCH(TEMP.)  
4FLASHES =OPENHIGHLIMIT  
5FLASHES =FLAMESENSEWITHOUTGASVALVE  
IGNITER  
TERMINAL  
6FLASHES =  
OPENROLLOUTOROPENFUSE  
SWITCH(PRESS.)  
INTERNALTO  
INTEGRATEDCONTROL  
7FLASHES =LOWFLAMESIGNAL  
7
8
C
OVERCURRENT  
PROT.DEVICE  
8FLASHES =CHECKIGNITERORIMPROPERGROUNDING  
CONTINUOUS/RAPIDFLASHES=REVERSED115VACPOLARITY  
PLUGCONNECTION  
NOTES:  
PKPINK  
COLORCODES:  
YLYELLOW  
ORORANGE  
1.SETHEATANTICIPATORONROOMTHERMOSTATAT0.7AMPS.  
BRBROWN  
WHWHITE  
BLBLUE  
2.MANUFACTURER'SSPECIFIEDREPLACEMENTPARTSMUSTBEUSEDWHENSERVICING.  
3.IFANYOFTHEORIGINALWIREASSUPPLIEDWITHTHEFURNACEMUSTBEREPLACED,ITMUSTBEREPLACEDWITHWIRINGMATERIAL  
°C.USECOPPERCONDUCTORSONLY.  
HAVINGATEMPERATURERATINGOFATLEAST105  
PUPURPLE  
GNGREEN  
BKBLACK  
4.IFHEATINGANDCOOLINGBLOWERSPEEDSARENOTTHESAME,DISCARDJUMPERBEFORECONNECTINGBLOWERLEADS.UNUSED  
BLOWERLEADSMUSTBEPLACEDON"PARK"TERMINALSOFINTEGRATEDCONTROLORTAPED.  
GYGRAY  
RDRED  
5.UNITMUSTBEPERMANENTLYGROUNDEDANDCONFORMTON.E.C.ANDLOCALCODES.  
6.TORECALLTHELAST5FAULTS,MOSTRECENTTOLEASTRECENT,DEPRESSSWITCHFORMORETHAN2SECONDSWHILEIN  
STANDBY(NOTHERMOSTATINPUTS)  
0140F00647REV.B  
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Ericsson Network Card W2x Series User Manual
Extron electronic Network Card GMK 1 User Manual
FieldServer Computer Drive FS 8700 39 User Manual
Fisher Price Baby Toy T7164 User Manual
Fitness Quest Home Gym Brutus 655 User Manual
Frigidaire Refrigerator FFSC2323L User Manual
Fujitsu Scanner P3PC 1492 04ENC2 User Manual
Gefen Network Card EXT USB20 LR User Manual
GE Thermostat CC SCSTAT User Manual
Globalsat Technology GPS Receiver BT 338 User Manual