Goodman Mfg Air Conditioner SS CPG36 72 User Manual

CPG CommerCial  
3- to 6-ton  
PaCkaGed Gas/eleCtriC Units  
CoolinG CaPaCity:  
35,000 — 71,000 BtU/h  
13 seer / 11.3 eer & 80%  
aFUe  
heatinG CaPaCity:  
56,000 — 112,000 BtU/h  
Standard Features  
• R-410A chlorine-free refrigerant  
• TuffTube™ tubular heat exchanger  
• High-efficiency scroll compressor  
• HIgh- and low-pressure switches  
• Copper tube / aluminum fin coils  
• Contactor with lugs  
• High-capacity, steel-cased filter dryer  
• 24-volt terminal strip  
• Convertible  
• Easy to service  
• Built-in filter rack with standard 2” filters  
• Bottom utility entry  
• Complies with California NOx emissions standards  
• AHRI Certified; ETL Listed  
Cabinet Features  
• Heavy-gauge, galvanized-steel cabinet with  
UV-resistant powder-paint finish  
• Full Perimeter Rail  
Contents  
Nomenclature....................................................................2  
Product Specifications .......................................................3  
Airflow Data .....................................................................10  
Expanded Cooling Data ...................................................17  
Dimensions ......................................................................25  
Wiring Diagrams .............................................................29  
Accessories .......................................................................39  
SS-CPG36-72  
6/11  
Supersedes 4/11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ProdUCt sPeCiFiCations  
ProdUCt sPeCiFiCations — CPG036 B models  
CPG036  
0451DXXX  
CPG036  
0453DXXX  
CPG036  
0453BXXX  
CPG036  
0454BXXX  
Cooling Capacity  
Total BTU/h  
Sensible BTU/h  
SEER / EER  
Decibels  
34,600  
25,600  
13 / 11.3  
78  
34,600  
25,600  
13 / 11.3  
78  
34,600  
25,600  
13 / 11.3  
78  
34,600  
25,600  
13 / 11.3  
78  
AHRI Reference #s  
4385059  
4385060  
4385060  
4385061  
Heating Capacity  
Max. Input / Output kBTU/h  
Steady State Efficiency (AFUE)  
Temperature Rise Range (°F)  
No. of Burners  
46 / 36.8  
80  
25-55  
2
46 / 36.8  
80  
25-55  
2
46 / 36.8  
80  
25-55  
2
46 / 36.8  
80  
25-55  
2
Evaporator Motor / Coil  
Motor Type  
Direct Drive  
1 (10” x 9”)  
1,200  
Low Speed  
2.50  
⅓ - 890  
0.072  
(1) 24 x 24 x 2  
¾”  
Direct Drive  
1 (10” x 9”)  
1,200  
Low Speed  
2.50  
⅓ - 890  
0.072  
(1) 24 x 24 x 2  
¾”  
Belt Drive  
1 (11” x 10”)  
1,200  
Belt Drive  
1 (11” x 10”)  
1,200  
# of Wheels (D x W)  
Indoor Nominal CFM  
Motor Speed Tap (Cooling)  
Indoor Motor FLA (Cooling)  
Horsepower - RPM  
Piston Size (Cooling)  
Filter Size (“)  
Drain Size (NPT)  
---  
3.8  
---  
1.9  
1.0 - 1725  
0.072  
(1) 24 x 24 x 2  
¾”  
1.0 - 1725  
0.072  
(1) 24 x 24 x 2  
¾”  
R-410A Refrigerant Charge Cir #1(oz.)  
Evaporator Coil Face Area (ſt²)  
Rows Deep/ Fins per Inch  
Belt Drive Evap Fan Data  
# of Wheels (D x W)  
Motor Sheave / Blower Sheave  
Belt  
83  
5.4  
3/16  
83  
5.4  
3/16  
83  
5.4  
3/16  
83  
5.4  
3/16  
---  
---  
---  
---  
---  
---  
1 (11” x 10”)  
1 (11” x 10”)  
1VL40 X ⅝ / AK69 X 1  
AX55  
AX55  
Condenser Fan / Coil  
Quanꢀty of Condenser Fan Motors  
Horsepower - RPM  
Fan Diameter/ # Fan Blades  
Outdoor Nominal CFM  
Face Area (ſt²)  
1
1
1
1
¼ / 1,090  
22/4  
3,800  
17.0  
¼ / 1,090  
22/4  
3,800  
17.0  
¼ / 1,090  
22/4  
3,800  
17.0  
¼ - 890  
22/4  
3,800  
17.0  
Rows Deep/ Fins per Inch  
Compressor  
1 / 24  
1 / 24  
1 / 24  
1 / 24  
Quanꢀty / Stage  
Type  
1 / Single  
Scroll  
1 / Single  
Scroll  
1 / Single  
Scroll  
1 / Single  
Scroll  
Compressor RLA / LRA  
Electrical Data  
16.7 / 79.0  
10.4 / 73.0  
10.4 / 73.0  
5.8 / 38.0  
Voltage-Phase-Frequency  
Indoor Blower HP / FLA  
Outdoor Fan HP / FLA  
Total Unit Amps  
Min. Circuit Ampacity¹  
Max. Overcurrent Protecꢀon (amps)²  
Power Supply Conduit Hole / Knockout  
Low-Voltage Conduit Hole  
Operating Weight (lbs)  
Ship Weight (lbs)  
208/230-1-60  
⅓ / 2.5  
¼ / 1.4  
20.57  
25  
208/230-3-60  
⅓ / 2.5  
¼ / 1.4  
14.35  
17  
208/230-3-60  
1 / 3.8  
¼ / 1.4  
15.65  
18  
460-3-60  
1 / 1.9  
¼ / 0.8  
8.47  
10  
15  
1.125  
½”  
40  
1.125  
½”  
525  
550  
25  
1.125  
½”  
525  
550  
25  
1.125  
½”  
525  
550  
525  
550  
¹ Wire size should be determined in accordance with Naꢀonal Electrical Codes. Extensive wire runs will require larger wire sizes.  
May use fuses or HACR-type circuit breakers of the same size as noted.  
Note: Always check the S&R plate for electrical data on the unit being installed.  
²
SS-CPG36-72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3
ProdUCt sPeCiFiCations  
ProdUCt sPeCiFiCations — CPG036 B models (Cont.)  
CPG036  
0901DXXX  
CPG036  
0903DXXX  
CPG036  
0903BXXX  
CPG036  
0904BXXX  
CPG036  
0907BXXX  
Cooling Capacity  
Total BTU/h  
Sensible BTU/h  
SEER / EER  
Decibels  
34,600  
25,600  
13 / 11.3  
78  
34,600  
25,600  
13 / 11.3  
78  
34,600  
25,600  
13 / 11.3  
78  
34,600  
25,600  
13 / 11.3  
78  
35,000  
25,900  
13 / 11.3  
78  
AHRI #s  
4385059  
4385060  
4385060  
4385061  
4397607  
Heating Capacity  
Hi. Input / Output BTU/h  
Low. Input / Output kBTU/h  
Steady State Efficiency (AFUE)  
Temperature Rise Range (°F) Hi / Low  
No. of Burners  
92 / 74  
69 / 55  
80  
92 / 74  
69 / 55  
80  
92 / 74  
69 / 55  
80  
92 / 74  
69 / 55  
80  
92 / 74  
69 / 55  
80  
40-70 / 30-60  
4
40-70 / 30-60  
4
40-70 / 30-60  
4
40-70 / 30-60  
4
40-70 / 30-60  
3
Evaporator Motor / Coil  
Motor Type  
Direct Drive  
1 (10” x 9”)  
1,200  
Low Speed  
2.50  
⅓ - 890  
0.068  
(1) 24 x 24 x 2  
¾”  
Direct Drive  
1 (10” x 9”)  
1,200  
Low Speed  
2.50  
⅓ - 890  
0.068  
(1) 24 x 24 x 2  
¾”  
Belt Drive  
1 (11” x 10”)  
1,200  
Belt Drive  
1 (11” x 10”)  
1,200  
Belt Drive  
1 (11” x 10”)  
1,200  
# of Wheels (D x W)  
Indoor Nominal CFM  
Motor Speed Tap (Cooling)  
Indoor Motor FLA (Cooling)  
Horsepower - RPM  
Piston Size (Cooling)  
Filter Size (“)  
Drain Size (NPT)  
---  
3.8  
---  
1.9  
---  
1.9  
1.0 - 1,725  
0.068  
(1) 24 x 24 x 2  
¾”  
1.0 - 1,725  
0.068  
(1) 24 x 24 x 2  
¾”  
1.0 - 1,725  
0.068  
(1) 24 x 24 x 2  
¾”  
R-410A Refrigerant Charge Cir #1(oz.)  
Evaporator Coil Face Area (ſt²)  
Rows Deep / Fins per Inch  
Belt Drive Evap Fan Data  
# of Wheels (D x W)  
Motor Sheave / Blower Sheave  
Belt  
90  
5.4  
3 / 16  
83  
5.4  
3 / 16  
83  
5.4  
3 / 16  
90  
5.4  
3 / 16  
90  
5.4  
3 / 16  
---  
---  
---  
---  
---  
---  
1 (11” x 10”)  
1 (11” x 10”)  
1VL40 X ⅝ / AK69 X 1  
AX55  
1 (11” x 10”)  
AX55  
AX55  
Condenser Fan / Coil  
Quanꢀty of Condenser Fan Motors  
Horsepower - RPM  
Fan Diameter/ # Fan Blades  
Outdoor Nominal CFM  
Face Area (ſt²)  
1
1
1
¼ / 1,090  
22 / 4  
3,800  
18  
1
1
¼ - 1,075  
22 / 4  
3,800  
13  
¼ / 1,090  
22 / 4  
3,800  
18.0  
¼ / 1,090  
22 / 4  
3,800  
18.0  
¼ - 890  
22 / 4  
3,800  
18  
Rows Deep/ Fins per Inch  
Compressor  
1 / 22  
1 / 22  
1 / 22  
1 / 22  
2 / 16  
Quanꢀty / Stage  
Type  
1 / Single  
Scroll  
1 / Single  
Scroll  
1 / Single  
Scroll  
1 / Single  
Scroll  
1 / Single  
Scroll  
Compressor RLA / LRA  
Electrical Data  
16.7 / 79.0  
10.4 / 73.0  
10.4 / 73.0  
5.8 / 38.0  
3.8 / 36.5  
Voltage-Phase-Frequency  
Indoor Blower HP / FLA  
Outdoor Fan HP / FLA  
Total Unit Amps  
Min. Circuit Ampacity¹  
Max. Overcurrent Protecꢀon (amps)²  
Power Supply Conduit Hole  
Low-Voltage Conduit Hole  
Operating Weight (lbs)  
Ship Weight (lbs)  
208/230-1-60  
⅓ / 2.5  
¼ / 1.4  
20.57  
25  
208/230-3-60  
⅓ / 2.5  
¼ / 1.4  
14.35  
17  
208/230-3-60  
1 / 3.8  
¼ / 1.4  
15.65  
18  
460-3-60  
1 / 1.9  
¼ / 0.8  
8.47  
10  
15  
1.125  
½”  
575-3-60  
1 / 1.9  
¼ / 0.8  
6.68  
8
15  
1.125  
½”  
40  
1.125  
½”  
535  
560  
25  
1.125  
½”  
535  
560  
25  
1.125  
½”  
535  
560  
535  
560  
535  
560  
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.  
May use fuses or HACR-type circuit breakers of the same size as noted.  
Note: Always check the S&R plate for electrical data on the unit being installed.  
²
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPG36-72  
ProdUCt sPeCiFiCations  
ProdUCt sPeCiFiCations — CPG048 B models  
CPG048  
0901DXXX  
CPG048  
0903DXXX  
CPG048  
0903BXXX  
CPG048  
0904BXXX  
Cooling Capacity  
Total BTU/h  
Sensible BTU/h  
SEER / EER  
Decibels  
45,500  
35,000  
13.0 / 11.3  
78  
45,500  
35,000  
13.0 / 11.3  
78  
45,500  
35,000  
13.0 / 11.3  
78  
45,500  
35,000  
13.0 / 11.3  
78  
AHRI Reference #s  
4385062  
4385063  
4385063  
4385064  
Heaꢀng Capacity  
Max. Input /Output kBTU/h  
Low Input /Output kBTU/h  
Steady State Efficiency (AFUE)  
Temperature Rise Range (°F) Hi / Low  
No. of Burners  
92 / 74  
69 / 55  
80  
92 / 74  
69 / 55  
80  
92 / 74  
69 / 55  
80  
92 / 74  
69 / 55  
80  
30-60 / 15-45  
4
30-60 / 15-45  
4
30-60 / 15-45  
4
30-60 / 15-45  
4
Evaporator Motor / Coil  
Motor Type  
Indoor Nominal CFM  
Motor Speed Tap (Cooling)  
Indoor Motor FLA (Cooling)  
Horsepower - RPM  
Piston Size (Cooling)  
Filter Size (#)  
Drain Size (NPT)  
Direct Drive  
1,600  
Medium  
2.87  
½ - 1,000  
0.076  
14 x 20 x 2 (4)  
¾”  
Direct Drive  
1,600  
Medium  
2.87  
½ - 1,000  
0.076  
14 x 20 x 2 (4)  
¾”  
Belt Drive  
1,600  
Belt Drive  
1,600  
---  
3.8  
---  
1.9  
1.0 / 1,725  
0.076  
14 x 20 x 2 (4)  
¾”  
1.0 / 1,725  
0.076  
14 x 20 x 2 (4)  
¾”  
R-410A Refrigerant Charge (oz.)  
Evaporator Coil Face Area (ſt²)  
Rows Deep / Fins per Inch  
Belt Drive Evap Fan Data  
# of Wheels (D” x W”)  
Motor Sheave / Blower Sheave  
Belt  
103  
7.0  
4 / 16  
103  
7.0  
4 / 16  
105  
7.0  
4 / 16  
103  
7.0  
4 / 16  
---  
---  
---  
---  
---  
---  
(1) 11 x 10  
(1) 11 x 10  
VL44 X ⅝ / AK66 X 1  
AX55  
AX55  
Condenser Fan / Coil  
Quanꢀty of Condenser Fan Motors  
Horsepower - RPM  
Fan Diameter / # Fan Blades  
Outdoor Nominal CFM  
Face Area (ſt²)  
1
1
1
1
¼ - 1,090  
22 / 4  
3,800  
17.0  
¼ - 1,090  
22 / 4  
3,800  
17.0  
¼ - 1,090  
22 / 4  
3,800  
17.0  
¼ - 890  
22 / 4  
3,800  
17.0  
Rows Deep / Fins per Inch  
Compressor  
1 / 24  
1 / 24  
1 / 24  
1 / 24  
Quanꢀty / Stage  
Type  
1 / Single  
Scroll  
1 / Single  
Scroll  
1 / Single  
Scroll  
1 / Single  
Scroll  
Compressor RLA / LRA  
Electrical Data  
19.9 / 109  
13.1 / 83.1  
13.1 / 83.1  
6.1 / 41  
Voltage-Phase-Frequency  
Outdoor Fan FLA  
Total Unit Amps  
Min. Circuit Ampacity¹  
Max. Overcurrent Protecꢀon (amps)²  
Power Supply Conduit Hole  
Low-Voltage Conduit Hole  
Operating Weight (lbs)  
Ship Weight (lbs)  
208/230-1-60  
208/230-3-60  
208/230-3-60  
460-3-60  
0.80  
8.8  
10  
15  
1.125  
½”  
575  
1.40  
24.1  
29  
45  
1.125  
½”  
1.40  
17.4  
21  
30  
1.125  
½”  
1.40  
18.3  
22  
30  
1.125  
½”  
575  
600  
575  
600  
575  
600  
600  
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.  
May use fuses or HACR-type circuit breakers of the same size as noted.  
Note: Always check the S&R plate for electrical data on the unit being installed.  
²
SS-CPG36-72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5
ProdUCt sPeCiFiCations  
ProdUCt sPeCiFiCations — CPG048 B models (Cont.)  
CPG048  
1151DXXX  
CPG048  
1153DXXX  
CPG048  
1153BXXX  
CPG048  
1154BXXX  
CPG048  
1157BXXX  
Cooling Capacity  
Total BTU/h  
45,500  
35,000  
13.0 / 11.3  
78  
45,500  
35,000  
13.0 / 11.3  
78  
45,500  
35,000  
13.0 / 11.3  
78  
45,500  
35,000  
13.0 / 11.3  
78  
45,500  
35,000  
13.0 / 11.3  
78  
Sensible BTU/h  
SEER / EER  
Decibels  
AHRI Reference #s  
4385062  
4385063  
4385063  
4385064  
4397608  
Heating Capacity  
Max. Input /Output kBTU/h  
Low Input /Output kBTU/h  
Steady State Efficiency (AFUE)  
Temperature Rise Range (°F) Hi / Low  
No. of Burners  
115 / 92  
86.25 / 69  
80  
115 / 92  
86.25 / 69  
80  
115 / 92  
86.25 / 69  
80  
115 / 92  
86.25 / 69  
80  
115 / 92  
86.25 / 69  
80  
40-70 / 25-55  
5
40-70 / 25-55  
5
40-70 / 25-55  
5
40-70 / 25-55  
5
40-70 / 25-55  
5
Evaporator Motor / Coil  
Motor Type  
Direct Drive  
1,600  
Direct Drive  
1,600  
Belt Drive  
1,600  
--  
Belt Drive  
1,600  
--  
Belt Drive  
1,600  
--  
Indoor Nominal CFM  
Motor Speed Tap (Cooling)  
Indoor Motor FLA (Cooling)  
Horsepower - RPM  
Medium  
2.87  
Medium  
2.87  
3.8  
1.9  
2.3  
½ - 1,000  
0.076  
½ - 1,000  
0.076  
1.0 / 1,725  
0.076  
14 x 20 x 2 (4)  
¾”  
1.0 / 1,725  
0.076  
14 x 20 x 2 (4)  
¾”  
1½ / 1,725  
0.076  
14 x 20 x 2 (4)  
¾”  
Piston Size (Cooling)  
Filter Size (#)  
14 x 20 x 2 (4)  
¾”  
14 x 20 x 2 (4)  
¾”  
Drain Size (NPT)  
R-410A Refrigerant Charge Cir #1(oz.)  
Evaporator Coil Face Area (ſt²)  
Rows Deep / Fins per Inch  
Belt Drive Evap Fan Data  
# of Wheels (D” x W”)  
Motor Sheave / Blower Sheave  
Belt  
103  
103  
103  
103  
105  
7.0  
7.0  
7.0  
7.0  
7.0  
4 / 16  
4 / 16  
4 / 16  
4 / 16  
4 / 16  
---  
---  
---  
---  
---  
---  
(1) 11 x 10  
(1) 11 x 10  
VL44 X ⅝ / AK66 X 1  
AX55  
(1) 11 x 10  
AX55  
AX55  
Condenser Fan / Coil  
Quanꢀty of Condenser Fan Motors  
Horsepower - RPM  
1
1
1
1
1
¼ - 1,090  
22 / 4  
3,800  
17.0  
¼ - 1,090  
22 / 4  
3,800  
17.0  
¼ - 1,090  
22 / 4  
3,800  
17.0  
¼ - 890  
22 / 4  
3,800  
17.0  
¼ - 1,075  
22 / 4  
3,800  
17.0  
Fan Diameter / # Fan Blades  
Outdoor Nominal CFM  
Face Area (ſt²)  
Rows Deep/ Fins per Inch  
Compressor  
1 / 24  
1 / 24  
1 / 24  
1 / 24  
1 / 24  
Quanꢀty / Stage  
1 / Single  
Scroll  
1 / Single  
Scroll  
1 / Single  
Scroll  
1 / Single  
Scroll  
1 / Single  
Scroll  
Type  
Compressor RLA / LRA  
Electrical Data  
19.9 / 109  
13.1 / 83.1  
13.1 / 83.1  
6.1 / 41  
4.4 / 33  
Voltage-Phase-Frequency  
Outdoor Fan FLA  
208/230-1-60  
208/230-3-60  
208/230-3-60  
460-3-60  
0.80  
8.8  
575-3-60  
0.60  
7.3  
1.40  
24.1  
29  
1.40  
17.4  
21  
1.40  
18.3  
22  
Total Unit Amps  
Min. Circuit Ampacity¹  
Max. Overcurrent Protecꢀon (amps)²  
Power Supply Conduit Hole  
Low-Voltage Conduit Hole  
Operating Weight (lbs)  
Ship Weight (lbs)  
10  
8
45  
30  
30  
15  
15  
1.125  
½”  
1.125  
½”  
1.125  
½”  
1.125  
½”  
1.125  
½”  
580  
605  
580  
605  
580  
605  
580  
580  
605  
605  
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.  
May use fuses or HACR-type circuit breakers of the same size as noted.  
Note: Always check the S&R plate for electrical data on the unit being installed.  
²
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPG36-72  
ProdUCt sPeCiFiCations  
ProdUCt sPeCiFiCations — CPG060 B models  
CPG060  
0901DXXX  
CPG060  
0903DXXX  
CPG060  
0903BXXX  
CPG060  
0904BXXX  
Cooling Capacity  
Total BTU/h  
59,500  
43,200  
13 / 11.3  
78  
59,500  
43,200  
13 / 11.3  
78  
59,500  
43,200  
13 / 11.3  
78  
59,500  
43,200  
13 / 11.3  
78  
Sensible BTU/h  
SEER / EER  
Decibels  
ARI Reference Nos.  
Gas Heating Capacity  
Max. Input /Output kBTU/h  
Low Input /Output kBTU/h  
Steady State Efficiency (AFUE)  
Temperature Rise Range (°F)  
No. of Burners  
4385065  
4385066  
4385066  
4385067  
92 / 74  
92 / 74  
92 / 74  
92 / 74  
69 / 55  
69 / 55  
69 / 55  
69 / 55  
80  
80  
80  
80  
20-50 / 15-45  
4
20-50 / 15-45  
4
20-50 / 15-45  
4
20-50 / 15-45  
4
Evaporator Motor / Coil  
Motor Type  
Direct  
2,000  
Direct  
2,000  
Belt  
2,000  
Belt  
2,000  
Indoor Nominal CFM  
Piston Size (Cooling)  
Filter Size (#)  
0.086  
0.086  
0.086  
0.086  
14 x 20 x 2 (4)  
¾”  
14 x 20 x 2 (4)  
¾”  
14 x 20 x 2 (4)  
¾”  
14 x 20 x 2 (4)  
¾”  
Drain Size (NPT)  
R-410A Refrigerant Charge (oz.)  
Face Area (ſt²)  
162  
162  
162  
165  
7.8  
7.8  
7.8  
7.8  
Rows Deep/ Fins per Inch  
Tube Diameter - Material  
Belt Drive Evap Fan Data  
# of Wheels (D x W)  
Motor Sheave / Blower Sheave  
Belt  
4 / 16  
4 / 16  
4 / 16  
4 / 16  
5/16 - Copper  
5/16 - Copper  
5/16 - Copper  
5/16 - Copper  
---  
---  
---  
---  
---  
---  
1 (11” x 10”)  
1 (11” x 10”)  
VL44 X ⅝ / AK61 X 1  
AX53  
AX53  
Condenser Fan / Coil  
Horsepower / RPM  
Fan Diameter/ # Fan Blades  
Outdoor Nominal CFM  
Face Area (ſt²)  
¼ / 1,090  
22 / 4  
¼ / 1,090  
22 / 4  
¼ / 1,090  
22 / 4  
¼ / 1,090  
22 / 4  
3,800  
3,800  
3,800  
3,800  
17.0  
17.0  
17.0  
17.0  
Rows Deep/ Fins per Inch  
Tube Diameter - Material  
Compressor  
2 / 18  
2 / 18  
2 / 18  
2 / 18  
5/16 - Copper  
5/16 - Copper  
5/16 - Copper  
5/16 - Copper  
Quanꢀty / Stage  
1 / Single  
Scroll  
1 / Single  
Scroll  
1 / Single  
Scroll  
1 / Single  
Scroll  
Type  
Compressor RLA / LRA  
Electrical Data  
26.4 / 134  
16 / 110  
16 / 110  
7.8 / 52  
Voltage-Phase-Frequency  
Indoor Blower HP / FLA )STD Staꢀc)  
Indoor Blower LRA  
Outdoor Fan HP / FLA  
Min. Circuit Ampacity¹  
Max. Overcurrent Protecꢀon (amps)²  
Power Supply Conduit Hole  
Low-Voltage Conduit Hole  
Operating Weight (lbs)  
Ship Weight (lbs)  
208/230-1-60  
1.0 / 7.6  
----  
208/230-3-60  
1.0 / 7.6  
----  
208/230-3-60  
460-3-60  
1.0 / 1.9  
13  
1.0 / 3.8  
24  
¼ / 1.40  
42  
¼ / 1.40  
29  
¼ / 1.40  
25  
¼ / 0.8  
13  
60  
45  
40  
20  
1.125  
½”  
1.125  
½”  
1.125  
½”  
1.125  
½”  
620  
620  
620  
620  
645  
645  
645  
645  
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.  
May use fuses or HACR-type circuit breakers of the same size as noted.  
Note: Always check the S&R plate for electrical data on the unit being installed.  
²
SS-CPG36-72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7
ProdUCt sPeCiFiCations  
ProdUCt sPeCiFiCations — CPG060 B models (Cont.)  
CPG060  
1401DXXX  
CPG060  
1403DXXX  
CPG060  
1403BXXX  
CPG060  
1404BXXX  
CPG060  
1407BXXX  
Cooling Capacity  
Total BTU/h  
59,500  
43,200  
13 / 11.3  
78  
59,500  
43,200  
13 / 11.3  
78  
59,500  
43,200  
13 / 11.3  
78  
59,500  
43,200  
13 / 11.3  
78  
59,500  
43,200  
13 / 11.3  
78  
Sensible BTU/h  
SEER / EER  
Decibels  
AHRI Nos.  
4385065  
4385066  
4385066  
4385067  
4397609  
Gas Heating Capacity  
Max. Input / Output kBTU/h  
Low. Input / Output kBTU/h  
Steady State Efficiency (AFUE)  
Temperature Rise Range (°F) Hi / Low  
No. of Burners  
138 / 110.4  
138 / 110.4  
138 / 110.4  
138 / 110.4  
138 / 110.4  
103 / 83  
103 / 83  
103 / 83  
103 / 83  
103 / 83  
80  
80  
80  
80  
80  
35-65 / 25-55  
6
35-65 / 25-55  
6
35-65 / 25-55  
6
35-65 / 25-55  
6
35-65 / 25-55  
6
Evaporator Motor / Coil  
Motor Type  
Direct  
2,000  
Direct  
2,000  
Belt  
2,000  
Belt  
2,000  
Belt  
2,000  
Indoor Nominal CFM  
Piston Size (Cooling)  
Filter Size (#)  
0.086  
0.086  
0.086  
0.086  
0.086  
14 x 20 x 2 (4)  
¾”  
14 x 20 x 2 (4)  
¾”  
14 x 20 x 2 (4)  
¾”  
14 x 20 x 2 (4)  
¾”  
14 x 20 x 2 (4)  
¾"  
Drain Size (NPT)  
R-410A Refrigerant Charge (oz.)  
Face Area (ſt²)  
162  
162  
162  
162  
162  
7.8  
7.8  
7.8  
7.8  
7.8  
Rows Deep/ Fins per Inch  
Tube Diameter - Material  
Belt Drive Evap Fan Data  
# of Wheels (D x W)  
Motor Sheave / Blower Sheave  
Belt  
4 / 16  
4 / 16  
4 / 16  
4 / 16  
4 / 16  
5/16 - Copper  
5/16 - Copper  
5/16 - Copper  
5/16 - Copper  
5/16 - Copper  
---  
---  
---  
---  
---  
---  
1 (11” x 10”)  
1 (11” x 10”)  
VL44 X ⅝ / AK61 X 1  
AX53  
1 (11" x 10")  
AX53  
AX53  
Condenser Fan / Coil  
Horsepower / RPM  
¼ / 1,090  
22 / 4  
¼ / 1,090  
22 / 4  
¼ / 1,090  
22 / 4  
¼ / 1,090  
22 / 4  
¼ / 1,075  
22 / 1  
Fan Diameter/ # Fan Blades  
Outdoor Nominal CFM  
Face Area (ſt²)  
3,800  
3,800  
3,800  
3,800  
3,800  
17.0  
17.0  
17.0  
17.0  
17½  
Rows Deep/ Fins per Inch  
Tube Diameter - Material  
Compressor  
2 / 18  
2 / 18  
2 / 18  
2 / 18  
2 / 18  
5/16 - Copper  
5/16 - Copper  
5/16 - Copper  
5/16 - Copper  
5/16 - Copper  
Quanꢀty / Stage  
1 / Single  
Scroll  
1 / Single  
Scroll  
1 / Single  
Scroll  
1 / Single  
Scroll  
1 / Single  
Scroll  
Type  
Compressor RLA / LRA  
Electrical Data  
26.4 / 134  
16 / 110  
16 / 110  
7.8 / 52  
5.7 / 38.9  
Voltage-Phase-Frequency  
Indoor Blower HP / FLA (STD Staꢀc)  
Indoor Blower LRA  
Outdoor Fan HP / FLA  
Min. Circuit Ampacity¹  
Max. Overcurrent Protecꢀon (amps)²  
Power Supply Conduit Hole  
Low-Voltage Conduit Hole  
Operating Weight (lbs)  
Ship Weight (lbs)  
208/230-1-60  
1.0 / 7.6  
----  
208/230-3-60  
1.0 / 7.6  
----  
208/230-3-60  
460-3-60  
1.0 / 1.9  
13  
575-3-60  
1.5 / 2.3  
12  
1.0 / 3.8  
24  
¼ / 1.40  
42  
¼ / 1.40  
29  
¼ / 1.40  
25  
¼ / 0.8  
12  
¼ / 0.6  
10  
60  
40  
40  
20  
15  
1.125  
½”  
1.125  
½”  
1.125  
½”  
1.125  
½”  
1.125  
½"  
630  
630  
630  
630  
630  
655  
655  
655  
655  
655  
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.  
May use fuses or HACR-type circuit breakers of the same size as noted.  
Note: Always check the S&R plate for electrical data on the unit being installed.  
²
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPG36-72  
ProdUCt sPeCiFiCations  
ProdUCt sPeCiFiCations — CPG072 B models  
CPG072  
1403BXXX  
CPG072  
1404BXXX  
CPG072  
1407BXXX  
Cooling Capacity  
Total BTU/h  
71,000  
48,280  
11.1  
71,000  
48,280  
11.1  
71,000  
48,280  
11.1  
Sensible BTU/h  
EER  
Decibels  
78.0  
78.0  
78.0  
AHRI Number  
3397632  
3397632  
3397632  
Heating Capacity  
Max. Input / Output KBTU/h  
Low Input/ Output KBTU/h  
Steady State Efficiency  
Temperature Rise Range (°F)  
No. of Burners  
138 / 110.4  
138 / 110.4  
138 / 110.4  
103 / 83  
103 / 83  
103 / 83  
80  
80  
80  
30-60 / 15-45  
6
30-60 / 15-45  
6
30-60 / 15-45  
6
Evaporator Motor / Coil  
Motor Type  
Belt Drive  
1 (11" x 10")  
2,400  
Belt Drive  
1 (11" x 10")  
2,400  
Belt Drive  
1 (11" x 10")  
2,400  
# of Wheels (D x W)  
Indoor Nominal CFM  
Indoor Motor FLA (Cooling)  
Horsepower - RPM  
Piston Size (Cooling)  
Filter Size (Qty)  
5.0  
2.5  
2.3  
1.5-1,725  
0.094  
1.5-1,725  
0.094  
1.5-1,725  
t
(4) 16" x 20" x 2"  
¾"  
(4) 16" x 20" x 2"  
¾"  
(4) 16" x 20" x 2"  
¾"  
Drain Size (NPT)  
R-410A Refrigerant Charge (oz.)  
Evaporator Coil Face Area (ſt²)  
Rows Deep/ Fins per Inch  
Motor Sheave  
213.0  
213.0  
213.0  
8.9  
8.9  
8.9  
4/ 16  
4/ 16  
4/ 16  
VL44 x 7/8  
AK59x1 / AX53  
VL44 x 7/8  
AK59x1 / AX53  
VL44 x 7/8  
AK59x1 / AX53  
Blower Sheave / Belt  
Condenser Fan / Coil  
Quanꢀty of Condenser Fan Motors  
Horsepower - RPM  
Fan Diameter/ # Fan Blades  
Outdoor Nominal CFM  
Face Area (ſt²)  
1
⅓ - 1,075  
22/ 4  
1
⅓ - 1,075  
22/ 4  
1
⅓ - 1,075  
22/ 4  
4,300  
18.7  
4,300  
18.7  
4,300  
18.7  
Rows Deep/ Fins per Inch  
Compressor  
2/ 20  
2/ 20  
2/ 20  
Quanꢀty / Stage  
1 / Single  
Scroll  
1 / Single  
Scroll  
1 / Single  
Scroll  
Type  
Compressor RLA / LRA  
Electrical Data  
19/ 123  
9.7/ 62  
7.4/ 50  
Voltage/ Phase/ Frequency  
Belt-Driven Standard Max Staꢀc  
Outdoor Fan FLA  
208-230/ 3/ 60  
460/ 3/ 60  
1.0  
575/ 3/ 60  
1.0  
1.0  
1.90  
25.9  
31  
1.20  
13.4  
16  
0.90  
10.6  
12  
Total Unit Amps  
Min. Circuit Ampacity¹  
Max. Overcurrent Protecꢀon (amps)²  
Entrance Power Supply  
Entrance Control Voltage  
Operating Weight (lbs)  
Ship Weight (lbs)  
45  
25  
15  
1.125"  
½"  
1.125”  
½"  
1.125”  
½"  
690  
715  
690  
690  
715  
715  
¹ Wire size should be determined in accordance with Naꢀonal Electrical Codes. Extensive wire runs will require larger wire sizes.  
May use fuses or HACR-type circuit breakers of the same size as noted.  
Note: Always check the S&R plate for electrical data on the unit being installed.  
²
SS-CPG36-72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9
ProdUCt sPeCiFiCations  
airFlow data — CPG036B  
standard direCt drive — horizontal  
standard direCt drive — down shot  
Speed  
Tap  
Speed  
Tap  
CFM  
Static  
Amps  
Watts  
RPM  
Static  
Amps  
Watts  
RPM  
CFM  
1293  
1235  
1173  
1124  
1056  
978  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
0.4  
0.5  
0.6  
0.7  
0.8  
0.9  
1.72  
1.67  
1.62  
1.58  
1.54  
1.47  
2.13  
2.10  
2.04  
2.00  
1.94  
1.88  
1.80  
1.72  
2.35  
2.28  
2.21  
2.13  
2.03  
1.90  
364  
354  
342  
330  
316  
298  
462  
448  
436  
424  
406  
392  
370  
350  
504  
484  
468  
446  
418  
388  
715  
759  
803  
841  
880  
913  
808  
838  
869  
902  
929  
951  
990  
1017  
940  
962  
989  
1012  
1034  
1067  
1313  
1247  
1178  
1094  
1002  
919  
0.10  
0.20  
0.30  
0.40  
0.50  
0.60  
0.10  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
0.30  
0.40  
0.50  
0.60  
0.70  
0.80  
1.68  
1.63  
1.59  
1.55  
1.50  
1.45  
2.11  
2.06  
2.02  
1.95  
1.90  
1.82  
1.74  
2.37  
2.31  
2.25  
2.17  
2.09  
1.99  
356  
344  
334  
324  
312  
296  
454  
440  
432  
416  
398  
378  
356  
510  
492  
476  
454  
436  
412  
748  
786  
832  
869  
913  
940  
830  
863  
896  
929  
957  
984  
1012  
935  
957  
978  
1000  
1023  
1045  
Low  
Med  
High  
Low  
Med  
High  
1500  
1434  
1381  
1318  
1238  
1163  
1055  
936  
1471  
1400  
1354  
1271  
1188  
1083  
955  
1470  
1390  
1310  
1206  
1098  
966  
1441  
1355  
1264  
1157  
1027  
840  
Note: Assumes dry coil with filter in place; SCFM correcꢀon for wet coil = 4%  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPG36-72  
ProdUCt sPeCiFiCations  
airFlow data — CPG036B (Cont.)  
standard Belt drive — horizontal  
Turns Open  
ESP  
(“ H2O)  
0
1
2
3
4
5
CFM  
BHP  
CFM  
BHP  
CFM  
BHP  
CFM  
BHP  
CFM  
1524  
1171  
714  
BHP  
0.32  
0.24  
0.14  
CFM  
1340  
900  
BHP  
0.25  
0.16  
0.2  
0.4  
0.6  
0.8  
1.0  
1.2  
1628  
1284  
936  
0.41  
0.32  
0.24  
1396  
1024  
0.32  
0.23  
1541  
1193  
806  
0.43  
0.33  
0.23  
1444  
1111  
744  
0.45  
0.34  
0.22  
hiGh-statiC Belt drive — horizontal  
Turns Open  
ESP  
(“ H2O)  
0
1
2
3
4
5
CFM  
BHP  
CFM  
BHP  
CFM  
BHP  
CFM  
BHP  
CFM  
1568  
1194  
856  
BHP  
0.45  
0.34  
0.24  
CFM  
1266  
922  
BHP  
0.32  
0.23  
0.6  
0.8  
1.0  
1.2  
1.4  
1.6  
1.8  
1492  
1163  
802  
0.47  
0.37  
0.25  
1476  
1146  
782  
0.52  
0.41  
0.30  
1458  
1139  
844  
0.57  
0.46  
0.36  
1458  
1139  
844  
0.63  
0.52  
0.42  
standard Belt drive — down shot  
Turns Open  
ESP  
(“ H2O)  
0
1
2
3
4
5
CFM  
BHP  
CFM  
BHP  
CFM  
BHP  
CFM  
1596  
1224  
856  
BHP  
0.36  
0.28  
0.19  
CFM  
1368  
981  
BHP  
0.28  
0.20  
CFM  
BHP  
0.2  
0.4  
0.6  
0.8  
1.0  
1162  
0.21  
1468  
1124  
776  
0.37  
0.28  
0.20  
1610  
1293  
948  
0.51  
0.40  
0.29  
1383  
1021  
614  
0.39  
0.29  
0.17  
hiGh-statiC Belt drive — down shot  
Turns Open  
ESP  
(“ H2O)  
0
1
2
3
4
5
CFM  
BHP  
CFM  
BHP  
CFM  
BHP  
CFM  
1655  
1342  
1002  
BHP  
0.53  
0.43  
0.32  
CFM  
1389  
1035  
713  
BHP  
0.39  
0.29  
0.19  
CFM  
1103  
775  
BHP  
0.28  
0.19  
0.6  
0.8  
1.0  
1.2  
1.4  
1.6  
1.8  
1640  
1326  
984  
0.57  
0.47  
0.36  
1638  
1307  
1002  
717  
0.63  
0.52  
0.42  
0.32  
1638  
1307  
1002  
717  
0.69  
0.58  
0.48  
0.38  
Note: Tables represent dry coil without filter; to compensate for filter, add 0.08” to measured E.S.P. SCFM correcꢀon for wet coil = 4%.  
SS-CPG36-72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11  
ProdUCt sPeCiFiCations  
airFlow data — CPG048B  
standard direCt drive — horizontal  
standard direCt drive — down shot  
Speed  
Tap  
Speed  
Tap  
CFM  
Static  
Amps  
Watts  
RPM  
CFM  
Static  
Amps  
Watts  
RPM  
1592  
1528  
1464  
1380  
1296  
1828  
1700  
1606  
1531  
1401  
1287  
1123  
1926  
1825  
1712  
1598  
1482  
1357  
0.1  
0.2  
0.3  
0.4  
0.5  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
2.54  
2.43  
2.32  
2.21  
2.10  
3.08  
2.75  
2.61  
2.48  
2.32  
2.22  
2.05  
3.34  
3.18  
3.03  
2.87  
2.76  
2.62  
543  
521  
499  
475  
451  
665  
601  
563  
537  
503  
477  
441  
740  
700  
660  
626  
596  
564  
815  
858  
1612  
1548  
1484  
1400  
1316  
1846  
1718  
1624  
1549  
1419  
1305  
1141  
1954  
1853  
1740  
1626  
1510  
1385  
0.1  
0.2  
0.3  
0.4  
0.5  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
2.60  
2.49  
2.38  
2.27  
2.16  
3.14  
2.81  
2.67  
2.54  
2.38  
2.28  
2.11  
3.43  
3.27  
3.12  
2.96  
2.85  
2.71  
554  
532  
510  
486  
462  
676  
612  
574  
548  
514  
488  
452  
758  
718  
678  
644  
614  
582  
789  
832  
901  
Low  
875  
Low  
930  
904  
959  
933  
892  
866  
924  
898  
966  
940  
990  
Med  
964  
Med  
1023  
1045  
1073  
937  
997  
1019  
1047  
924  
965  
952  
989  
976  
High  
High  
1015  
1032  
1049  
1002  
1019  
1036  
Note: Assumes dry coil with filter in place; SCFM correcꢀon for wet coil = 4%  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPG36-72  
ProdUCt sPeCiFiCations  
airFlow data — CPG048B (Cont.)  
standard Belt drive — horizontal  
Turns Open  
ESP  
(“ H2O)  
0
1
2
3
4
5
CFM  
BHP  
CFM  
BHP  
CFM  
BHP  
CFM  
BHP  
CFM  
1800  
1438  
1030  
BHP  
0.47  
0.36  
0.23  
CFM  
1556  
1167  
BHP  
0.35  
0.22  
0.2  
0.4  
0.6  
0.8  
1.0  
1.2  
2002  
1612  
1222  
0.65  
0.50  
0.36  
1708  
1330  
989  
0.49  
0.37  
0.25  
1910  
1571  
1142  
0.67  
0.54  
0.32  
1813  
1478  
1107  
0.69  
0.56  
0.41  
hiGh-statiC Belt drive — horizontal  
Turns Open  
ESP  
(“ H2O)  
0
1
2
3
4
5
CFM  
BHP  
CFM  
BHP  
CFM  
BHP  
CFM  
BHP  
CFM  
1894  
1532  
1170  
BHP  
0.66  
0.53  
0.39  
CFM  
1585  
1223  
BHP  
0.49  
0.37  
0.6  
0.8  
1.0  
1.2  
1.4  
1.6  
1.8  
1839  
1477  
1115  
0.71  
0.55  
0.40  
1782  
1445  
1107  
0.73  
0.59  
0.46  
1786  
1426  
1098  
0.80  
0.64  
0.50  
1764  
1446  
1099  
0.86  
0.72  
0.56  
standard Belt drive — down shot  
Turns Open  
ESP  
(“ H2O)  
0
1
2
3
4
5
CFM  
BHP  
CFM  
BHP  
CFM  
BHP  
CFM  
1891  
1533  
1206  
BHP  
0.56  
0.43  
0.32  
CFM  
1632  
1290  
910  
BHP  
0.42  
0.31  
0.19  
CFM  
1391  
1055  
BHP  
0.30  
0.19  
0.2  
0.4  
0.6  
0.8  
1.0  
1796  
1446  
1096  
0.57  
0.44  
0.31  
1948  
1654  
1337  
0.74  
0.63  
0.50  
1744  
1409  
987  
0.61  
0.48  
0.28  
hiGh-statiC Belt drive — down shot  
Turns Open  
ESP  
(“ H2O)  
0
1
2
3
4
5
CFM  
BHP  
CFM  
BHP  
CFM  
BHP  
CFM  
1989  
1662  
1335  
1008  
BHP  
0.77  
0.63  
0.49  
0.36  
CFM  
1712  
1384  
1056  
BHP  
0.59  
0.47  
0.34  
CFM  
1433  
1106  
BHP  
0.44  
0.33  
0.6  
0.8  
1.0  
1.2  
1.4  
1.6  
1.8  
1929  
1622  
1315  
1007  
0.79  
0.67  
0.54  
0.42  
1952  
1611  
1298  
1007  
0.88  
0.73  
0.59  
0.46  
1897  
1616  
1316  
0.93  
0.80  
0.66  
Note: Tables represent dry coil without filter; to compensate for filter, add 0.08” to measured E.S.P. SCFM correcꢀon for wet coil = 4%.  
SS-CPG36-72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
13  
ProdUCt sPeCiFiCations  
airFlow data — CPG060B  
standard direCt-drive — horizontal  
standard direCt-drive — down shot  
Speed  
Tap  
Speed  
Tap  
RPM  
CFM  
Static  
Amps  
Watts  
RPM  
CFM  
Static Amps  
Watts  
1416  
1295  
1200  
1133  
1045  
1543  
1485  
1425  
1352  
1304  
2107  
2031  
1980  
1954  
1887  
1839  
1782  
2224  
2165  
2123  
2079  
2029  
1978  
1926  
1872  
1817  
2318  
2296  
2228  
2193  
2145  
2097  
2054  
1991  
1952  
0.1  
0.2  
0.3  
0.4  
0.5  
0.1  
0.2  
0.3  
0.4  
0.5  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
0.9  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
0.9  
1.63  
1.61  
1.68  
1.79  
1.90  
2.00  
2.12  
2.20  
2.26  
2.39  
4.02  
4.13  
4.27  
4.37  
4.48  
4.58  
4.72  
4.73  
4.79  
4.91  
5.01  
5.14  
5.26  
5.38  
5.48  
5.58  
5.42  
5.55  
5.66  
5.76  
5.90  
5.99  
6.10  
6.15  
6.26  
176  
174  
186  
196  
208  
220  
236  
250  
258  
274  
502  
518  
536  
554  
572  
582  
602  
592  
612  
630  
642  
666  
676  
698  
712  
722  
700  
720  
734  
748  
766  
784  
798  
810  
826  
588  
621  
660  
704  
753  
627  
671  
698  
748  
786  
797  
819  
858  
880  
913  
940  
968  
832  
860  
891  
913  
946  
969  
1001  
1028  
1056  
874  
903  
929  
950  
979  
1012  
1034  
1050  
1079  
1237  
1191  
1127  
1065  
994  
0.1  
0.2  
0.3  
0.4  
0.5  
0.1  
0.2  
0.3  
0.4  
0.5  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
0.9  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
0.9  
1.64  
1.75  
1.80  
1.89  
1.97  
2.13  
2.24  
2.29  
2.42  
2.54  
4.49  
4.58  
4.69  
4.80  
4.87  
4.97  
5.05  
5.14  
5.26  
5.32  
5.47  
5.54  
5.61  
5.73  
5.81  
5.84  
5.87  
5.96  
6.06  
6.15  
6.21  
6.32  
6.28  
6.22  
6.04  
180  
194  
200  
214  
220  
248  
254  
262  
280  
294  
558  
574  
582  
600  
612  
626  
642  
650  
670  
678  
696  
706  
726  
736  
750  
752  
762  
772  
788  
804  
814  
834  
830  
814  
786  
638  
682  
T1  
T2  
T1  
T2  
715  
753  
797  
1437  
1384  
1312  
1245  
1185  
1988  
1942  
1882  
1847  
1784  
1762  
1688  
2106  
2050  
1993  
1960  
1920  
1880  
1810  
1760  
1694  
2199  
2146  
2121  
2066  
2010  
1978  
1919  
1837  
1738  
687  
726  
759  
803  
847  
885  
907  
935  
T3  
962  
T3  
990  
1008  
1039  
924  
951  
969  
1001  
1021  
1041  
1072  
1093  
1122  
968  
T4  
T4  
989  
1012  
1039  
1056  
1084  
1102  
1122  
1127  
T5  
T5  
Notes  
Assumes dry coil with filter in place; SCFM correcꢀon for wet coil = 4%  
Five-ton models are shipped from the factory with speed tap set on T4.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPG36-72  
ProdUCt sPeCiFiCations  
airFlow data — CPG060B (Cont.)  
standard Belt drive — horizontal  
Turns Open  
ESP  
(“ H2O)  
0
1
2
3
4
5
CFM  
BHP  
CFM  
BHP  
CFM  
2460  
2206  
1943  
1667  
BHP  
0.96  
0.84  
0.72  
0.59  
CFM  
2251  
1982  
1701  
BHP  
0.80  
0.68  
0.55  
CFM  
2073  
1808  
1511  
BHP  
0.65  
0.55  
0.43  
CFM  
1862  
1572  
BHP  
0.51  
0.41  
0.2  
0.4  
0.6  
0.8  
1.0  
1.2  
2408  
2173  
1917  
1634  
1.00  
0.89  
0.77  
0.63  
2402  
2153  
1888  
1601  
1.08  
0.95  
0.82  
0.67  
hiGh-statiC Belt drive — horizontal  
Turns Open  
ESP  
(“ H2O)  
0
1
2
3
4
5
CFM  
BHP  
CFM  
BHP  
CFM  
BHP  
CFM  
BHP  
CFM  
2219  
1956  
1681  
BHP  
0.95  
0.82  
0.67  
CFM  
1970  
1697  
BHP  
0.75  
0.62  
0.6  
0.8  
1.0  
1.2  
1.4  
1.6  
1.8  
2215  
1957  
1683  
1.04  
0.90  
0.74  
2240  
1983  
1711  
1.15  
1.00  
0.84  
2260  
2009  
1741  
1.26  
1.10  
0.93  
2288  
2032  
1776  
1.38  
1.21  
1.04  
standard Belt drive — down shot  
Turns Open  
ESP  
(“ H2O)  
0
1
2
3
4
5
CFM  
BHP  
CFM  
2210  
2021  
1822  
1610  
1384  
BHP  
0.91  
0.82  
0.72  
0.62  
0.51  
CFM  
2041  
1841  
1635  
1425  
BHP  
0.76  
0.67  
0.58  
0.48  
CFM  
1869  
1660  
1445  
BHP  
0.63  
0.54  
0.44  
CFM  
1739  
1521  
1288  
BHP  
0.52  
0.44  
0.35  
CFM  
1565  
1339  
BHP  
0.40  
0.32  
0.2  
0.4  
0.6  
0.8  
1.0  
2197  
2002  
1799  
1587  
0.98  
0.88  
0.77  
0.67  
hiGh-statiC Belt drive — down shot  
Turns Open  
ESP  
(“ H2O)  
0
1
2
3
4
5
CFM  
BHP  
CFM  
BHP  
CFM  
2262  
2070  
1872  
1668  
BHP  
1.16  
1.05  
0.93  
0.81  
CFM  
2051  
1852  
1647  
BHP  
0.95  
0.84  
0.72  
CFM  
1851  
1646  
BHP  
0.76  
0.66  
CFM  
BHP  
0.6  
0.8  
1.0  
1.2  
1.4  
1.6  
1657  
0.60  
2277  
2089  
1893  
1690  
1.27  
1.15  
1.03  
0.90  
2304  
2104  
1912  
1720  
1.39  
1.26  
1.13  
1.00  
Note: Tables represent dry coil without filter; to compensate for filter, add 0.08” to measured E.S.P. SCFM correction for wet coil = 4%.  
SS-CPG36-72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
15  
ProdUCt sPeCiFiCations  
airFlow data — CPG072B  
standard Belt drive — horizontal  
0 Turns  
1 Turn  
2 Turns  
3 Turns  
4 Turns  
BHP  
5 Turns  
BHP  
ESP (In W.C.)  
CFM  
BHP  
CFM  
BHP  
CFM  
BHP  
CFM  
2749  
2544  
2306  
2076  
BHP  
1.18  
1.06  
0.92  
0.81  
CFM  
2573  
2346  
2094  
CFM  
2402  
2164  
1890  
0.2  
0.4  
0.6  
0.8  
1
0.96  
0.84  
0.72  
0.79  
0.68  
0.57  
2680  
2498  
2263  
2002  
1.22  
1.10  
0.97  
0.83  
2655  
2486  
2272  
2028  
1.31  
1.20  
1.07  
0.93  
2703  
2515  
2253  
1.47  
1.34  
1.16  
1.2  
standard Belt drive — down shot  
0 Turns  
1 Turn  
2 Turns  
3 Turns  
4 Turns  
5 Turns  
ESP (In W.C.)  
CFM  
BHP  
CFM  
BHP  
CFM  
2625  
2476  
2325  
2068  
1806  
BHP  
CFM  
2486  
2327  
2070  
1868  
BHP  
1.02  
0.94  
0.80  
0.71  
CFM  
2322  
2159  
1898  
BHP  
0.83  
0.75  
0.64  
CFM  
2152  
1938  
BHP  
0.68  
0.59  
0.2  
0.4  
0.6  
0.8  
1
1.18  
1.09  
1.00  
0.86  
0.73  
2765  
2650  
2443  
2258  
2021  
1.52  
1.43  
1.29  
1.17  
1.02  
2596  
2452  
2251  
2040  
1.28  
1.18  
1.06  
0.94  
1.2  
hiGh statiC Belt drive — horizontal  
0 Turns  
1 Turn  
2 Turns  
3 Turns  
4 Turns  
5 Turns  
ESP (In W.C.)  
CFM  
BHP  
CFM  
BHP  
CFM  
BHP  
CFM  
BHP  
CFM  
2677  
2529  
2246  
1970  
BHP  
1.29  
1.20  
1.02  
0.87  
CFM  
2486  
2263  
1972  
BHP  
1.07  
0.94  
0.79  
0.6  
0.8  
1
2690  
2471  
2255  
2025  
1.42  
1.27  
1.13  
0.99  
2740  
2518  
2273  
2035  
1.60  
1.44  
1.27  
1.11  
1.2  
1.4  
1.6  
1.8  
2
2748  
2562  
2314  
2037  
1.74  
1.59  
1.40  
1.21  
2797  
2556  
2342  
2137  
1.87  
1.67  
1.50  
1.35  
hiGh statiC Belt drive — down shot  
0 Turns  
1 Turn  
2 Turns  
3 Turns  
4 Turns  
5 Turns  
ESP (In W.C.)  
CFM  
BHP  
CFM  
BHP  
CFM  
2793  
2638  
2407  
2228  
2013  
BHP  
CFM  
2575  
2407  
2194  
1977  
BHP  
1.37  
1.25  
1.12  
0.98  
CFM  
2407  
2226  
2012  
BHP  
1.15  
1.04  
0.92  
CFM  
2250  
2011  
BHP  
0.96  
0.84  
0.6  
0.8  
1
1.64  
1.53  
1.36  
1.23  
1.10  
2775  
2660  
2497  
2236  
2032  
1.76  
1.67  
1.54  
1.35  
1.20  
2821  
2696  
2455  
2262  
2069  
1.89  
1.79  
1.59  
1.44  
1.30  
1.2  
1.4  
1.6  
1.8  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPG36-72  
ProdUCt sPeCiFiCations  
exPanded CoolinG data — CPG036B  
SS-CPG36-72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
17  
ProdUCt sPeCiFiCations  
exPanded CoolinG data — CPG036B (Cont.)  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPG36-72  
ProdUCt sPeCiFiCations  
exPanded CoolinG data — CPG048B  
SS-CPG36-72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
19  
ProdUCt sPeCiFiCations  
exPanded CoolinG data — CPG048B (Cont.)  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPG36-72  
ProdUCt sPeCiFiCations  
exPanded CoolinG data — CPG060B  
SS-CPG36-72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
21  
ProdUCt sPeCiFiCations  
exPanded CoolinG data — CPG060B (Cont.)  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPG36-72  
ProdUCt sPeCiFiCations  
exPanded CoolinG data — CPG072B  
SS-CPG36-72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
23  
ProdUCt sPeCiFiCations  
exPanded CoolinG data — CPG072B (Cont.)  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPG36-72  
ProdUCt sPeCiFiCations  
dimensions  
47¹/”  
73¹/”  
3 to 5 Tons: 38¹³/₆”  
”  
6 Tons: 42¹³/₆”  
74¹/₆”  
48³/₆”  
11”  
4/”  
7³/”  
17”  
19/₆”  
RETURN  
25”  
SUPPLY  
12”  
RETURN  
DRAIN  
THRU CURB  
LOCATION  
EMBOSS  
FOR  
THRU THE  
BASE  
”  
5/”  
UTILITIES  
6 1/4”  
SUPPLY  
27³/
Horizontal Discharge  
4 1/2”  
4¹/”  
8³/₆”  
7
7¹/”  
47¹/”  
BOTTOM VIEW OF UNIT  
Verꢀcal Discharge  
SS-CPG36-72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
25  
ProdUCt sPeCiFiCations  
Unit ClearanCes  
Maintain an adequate clearance around the unit for safety, service,  
maintenance, and proper unit operation. Leave a total clearance of 75”  
on the main control panel side of the unit for possible removal of  
fan shaft, coil, electric heat, and gas furnace. Leave a clearance  
of 48” on all other sides of the unit for possible compressor  
removal or service access, and to ensure proper  
ventilation and condenser airflow. Do not install  
the unit beneath any obstruction. Install the  
unit away from all building exhausts  
to inhibit ingestion of exhaust air  
into the unit’s fresh-air intake.  
eleCtriCal entranCe loCations  
High-Voltage Entrance  
(Remove Plug)  
12⅜”  
30¼”  
Low-Voltage Entrance  
3½” Dia.  
Power Thru  
the Curb  
4½”  
47½”  
7½”  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPG36-72  
ProdUCt sPeCiFiCations  
rooF CUrB installation — riGGinG  
Provisions for forks have been included in the unit base frame. No other fork  
locations are approved.  
• Unit must be lifted by the four lifting holes located at the base frame  
corners.  
• Lifting cables should be attached to the unit with shackles.  
• The distance between the crane hook and the top of the unit must not be  
less than 60”.  
• Two spreader bars must span over the unit to prevent damage to the cabi-  
net by the lift cables. Spreader bars must be of sufficient length so that ca-  
bles do not come in contact with the unit during transport. Remove wood  
struts mounted beneath unit base frame before setting unit on roof curb.  
These struts are intended to protect unit base frame from fork lift damage.  
To remove the struts, extract the sheet metal retainers and pull the struts  
through the base of the unit. Refer to rigging label on the unit.  
Important: If using bottom discharge with roof curb, duct-work should be  
attached to the curb prior to installing the unit. Duct-work dimensions are  
shown in Roof Curb Installation Instructions Manual.  
Refer to the Roof Curb Installation Instructions for proper curb installation.  
Curbing must be installed in compliance with the National Roofing Contractors Association Manual.  
Lower unit carefully onto roof mounting curb. While rigging the unit, the center of gravity will cause the condenser end to be lower  
than the supply air end.  
Bring condenser end of unit into alignment with the curb. With condenser end of the unit resting on curb member and using curb as  
a fulcrum, lower opposite end of the unit until entire unit is seated on the curb. When a rectangular cantilever curb is used, take care  
to center the unit. Check for proper alignment and orientation of supply and return openings with duct.  
Corner & Center-oF-Gravity loCations  
3-Ton  
4-Ton  
5-Ton  
6-Ton  
Unit Weights  
Weights Weights Weights Weights  
Corner Weight (A)  
Corner Weight (B)  
Corner Weight (C)  
Corner Weight (D)  
Unit Shipping Weight  
Unit Operaꢀng Weight  
100  
170  
105  
170  
550  
525  
110  
180  
110  
180  
595  
570  
115  
195  
120  
195  
625  
600  
130  
215  
130  
215  
715  
690  
Return  
Evaporator Coil  
30”  
Condenser  
Coil  
Supply  
Note: Weights are calculated without accessories installed.  
Compressor  
37”  
SS-CPG36-72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
27  
ProdUCt sPeCiFiCations  
rooF CUrB installation (Cont.)  
Curb installations must comply with local codes and should follow the established guidelines of the National Roofing Contractors  
Association.  
Proper unit installation requires that the roof curb be firmly and permanently attached to the roof structure. Check for adequate  
fastening method prior to setting the unit on the curb.  
Full perimeter roof curbs are available from the factory and are shipped unassembled. The installing contractor is responsible for  
field assembly, squaring, leveling, and mounting on the roof structure. All required hardware necessary for the assembly of the sheet  
metal curb is included in the curb accessory package.  
• Determine sufficient structural support before locating and mounting the curb and package unit.  
• Duct-work must be constructed using industry guidelines. The duct-work must be placed into the roof curb before mounting the  
package unit. Our full perimeter curbs include duct connection frames to be assembled with the curb. Cantilevered-type curbs  
are not available from the factory.  
• Contractor furnishes curb insulation, cant strips, flashing, and general roofing material.  
• Support curbs on parallel sides with roof members. To prevent damage to the unit, the roof members cannot penetrate supply  
and return duct openings.  
Note: The unit and curb accessories are designed to allow vertical duct installation before unit placement. Duct installation after unit  
placement is not recommended.  
See the manual shipped with the roof curb for assembly and installation instructions.  
3-d view  
Insulated  
Panels  
70¾  
40¼  
14 x 20  
Supply Opening  
14  
31⅝ x 14  
Return Opening  
15/6  
¾
14  
1⅜  
toP view  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPG36-72  
Product SPecificationS  
Wiring diagram cPg0360451d (Single-PhaSe, direct drive)  
YL  
RD  
BK  
PU  
RD  
BK  
T3 T2 T1  
COMP  
BR  
T1  
L1  
T2  
L2  
GND  
BK  
PU  
BL  
YL  
C
BL  
BK  
RD  
BK  
208-240/1/60  
SEE NOTE 5  
CM  
PU  
RD  
BR  
RD  
NOTE 2  
EM  
3 SPEED  
BC  
1
C
2
208  
3
240  
FOR  
TR  
24V  
ALTERNATE  
MOTOR  
6-WIRES  
BL  
SMOKE/FIRE  
DETECTOR  
REPLACE  
JUMPER  
LS  
RD  
RD  
PU  
RD  
PU  
YL RD  
YL  
BK  
PK  
BL  
BL  
GR  
SEE NOTE 6 & 7  
S1  
PK  
BR  
EM  
3 SPEED  
BC  
BR  
PU  
TB1  
S2  
SEE NOTE 7  
BL  
2
C 2  
T 2  
T 1  
BK  
P 2  
RD  
OR  
YL  
1 5 0  
1 3 5  
1 2 0  
ALS  
P 3  
X A P M M  
A
S U E F  
3
1 F  
IIC  
PU  
RD  
GR  
RD  
BR  
BL  
PS  
RS  
YL  
YL  
PU  
YL  
PU  
YL  
YL  
WH  
RD  
NOTE 4  
PLF  
BR  
GR  
RD  
BK  
BK  
3
2
1
6
RD  
BK  
5
4
YL  
BL  
PU  
YL  
PU  
BL  
BL  
RD WH  
W. R.  
GAS VALVE  
(ALT.) HONEYWELL  
GAS VALVE  
BL  
BL  
BK  
MV  
PU  
YL  
BL  
RD  
PU  
GR  
GV  
LPS  
GV  
RD  
MV  
BL  
YL/PK  
BL/PK  
Y2  
TB1  
C
RY1W1G  
RD  
SEE NOTE 8  
GREEN JUMPER  
BL  
TO THERMOSTAT  
RD  
FS  
VM  
IGN  
OR  
RD  
BK  
RCCF  
H
HPS  
RD  
F
C
BR  
YL  
L1  
L2  
FACTORY WIRING  
SUPPLY VOLTAGE  
208-240/1/60  
COMPONENT LEGEND  
ALS  
COMP  
CM  
C
AUXILLARY LIMIT SWITCH  
COMPRESSOR  
CONDENSER MOTOR  
CONTACTOR  
LINE VOLTAGE  
LOW VOLTAGE  
OPTIONAL  
HIGH VOLTAGE  
T2  
C
C
C
T1  
R
S
L2  
EM  
F
FS  
EVAPORATOR MOTOR  
FUSE  
FLAME SENSOR  
L1  
C
COMP  
H
RCCF  
FIELD WIRING  
HIGH VOLTAGE  
LOW VOLTAGE  
F
GND  
GV  
HPS  
EQUIPMENT GROUND  
GAS VALVE  
HIGH PRESSURE SWITCH  
CM  
HEAT  
PCB  
WIRE CODE  
IIC  
IGN  
LS  
LPS  
INTEGRATED IGNITION CONTROL  
IGNITOR  
LIMIT SWITCH  
BK BLACK  
BL BLUE  
BR BROWN  
GR GREEN  
OR ORANGE  
PK PINK  
PU PURPLE  
RD RED  
WH WHITE  
YL YELLOW  
BL/PK BLUE WITH PINK STRIP  
FC  
EM  
LOW PRESSURE SWITCH  
PCB  
LI  
PLF  
PS  
FEMALE PLUG/CONNECTOR  
PRESSURE SWITCH  
RCCF RUN CAPACITOR FOR CONDENSER FAN  
COOL  
DI  
VM  
SEE NOTE 2  
2
RS  
TB1  
TR  
VM  
VMR  
BC  
ROLLOUT SWITCH  
3
1
TERMINAL BLOCK (24V SIGNAL)  
TRANSFORMER  
VENT MOTOR  
VENT MOTOR RELAY  
BLOWER CAPACITOR  
TR  
TB1  
FS  
IIC  
IGN  
FS  
F
YL/PK YELLOW WITH PINK STRIP  
NOTES  
1. REPLACEMENT WIRE MUST BE THE SAME  
SIZE AND TYPE OF INSULATION AS ORIGINAL.  
(USE COPPER CONDUCTOR ONLY).  
4
5
LS  
2. FOR 208 VOLT TRANSFORMER OPERATION  
TO  
ALS  
RS  
THERMOSTAT  
FIELD WIRING  
IIC  
3
6
GV  
MOVE BLACK WIRE FROM TERMINAL  
TERMINAL ON TRANSFORMER.  
3
2
3. FOR DIFFERENT THAN FACTORY SPEED TAP.  
CHANGE COOLING SPEED AT COOL  
TERMINAL. CHANGE HEATING SPEED AT  
HEAT TERMINAL ON CONTROL BOARD  
3 SPEED MOTOR  
RD - LOW SPEED  
BL - MED. SPEED  
BK - HIGH SPEED  
PS  
NO ECONOMIZER  
8
ECON  
W
G
WH  
GR  
RD  
W
G
R
9
7
10  
12  
11  
LPS  
HPS  
C
NOTE  
R
Y1  
Y/Y2  
C
YL  
BL  
6
5
2
4
Y
C
4. ACCESSORY ECONOMIZER PLUG ADJACENT  
TO BLOWER HOUSING IN RETURN AIR  
COMPARTMENT. REMOVE MALE PLUG AND  
ATTACH FEMALE PLUG TO ECONOMIZER  
ACCESSORY.  
4
3
1
R
G
W
Y1  
Y2  
C
PLF  
TB1  
TO THERMOSTAT  
TERMINAL BLOCK  
STAT  
TB1  
5. USE COPPER CONDUCTORS ONLY.  
USE NEC CLASS 2 WIRE.  
WITH ECONOMIZER OPTION  
INSTALLER/SERVICEMAN  
THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO  
TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS:  
W
G
WH  
GR  
RD  
W
G
R
Y
6. PURPLE WIRE CONNECTS TO TRANSFORMER  
(PIN 1).  
R
7. SPEED TAP TERMINATIONS SHOWN ON  
DIAGRAM ARE REPRESENTATIVE, BUT ACTUAL  
FACTORY SETTING MAY BE DIFFERENT BASED  
ON HEATING VALUE AND CAPACITY OF UNIT.  
EQUIP. STATUS  
NORMAL OPERATION  
CHECK  
-
STATUS LIGHT  
ON  
YL  
Y1  
Y/Y2  
C
NO POWER OR  
INTERNAL CONTROL  
FAULT  
CHECK INPUT POWER  
CHECK FUSE ON CONTROL  
REPLACE CONTROL  
OFF  
BL  
8. TO RUN DIFFERENT SPEED FOR HEATING AND  
COOLING, DISCONNECT GEEEN JUMPER FROM  
"COOL" TERMINAL AND REPLACE WITH  
APPROPRIATE SPEED TAP. THEN PLACE  
DISCONNECTED END OF JUMPER ON  
"UNUSED" TERMINAL LEFT OPEN BY MOVING  
THE SPEED TAP.  
C
IGNITION FAILURE  
OR  
GAS FLOW  
GAS PRESSURE  
GAS VALVE  
FLAME SENSOR  
FLAME ROLLOUT  
BAD SWITCH  
1 BLINK  
STAT  
TB1  
OPEN ROLLOUT  
SWITCH  
OR  
2 STAGE COOLING  
W
WH  
GR  
RD  
YL  
W
G
OPEN AUX. LIMIT  
SWITCH  
PRESSURE SWITCH  
OPEN  
PRESSURE SWITCH CLOSED  
WITHOUT INDUCER ON  
OPEN LIMIT SWITCH  
AUX. LIMIT OPEN  
CHECK  
PRESSURE SWITCH  
CHECK  
PRESSURE SWITCH  
MAIN LIMIT OPEN  
BAD SWITCH  
G
R
2 BLINKS  
3 BLINKS  
4 BLINKS  
SEE UNIT RATING PLATE FOR TYPE AND SIZE OF  
OVERCURRENT PROTECTION.  
R
Y1  
Y1  
Y2  
C
PK  
BL  
Y/Y2  
C
5 BLINKS  
6 BLINKS  
FALSE FLAME SENSED  
COMPRESSOR  
OUTPUT DELAY  
STICKING GAS VALVE  
3 MIN. COMP.  
ANTI-CYCLE TIMER  
STAT  
TB1  
208-240/1/60 0140L00510 REV A  
SS-CPG36-72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
29  
Product SPecificationS  
Wiring diagram cPg036/480901d (Single-PhaSe direct drive)  
YL  
RD  
BK  
PU  
RD  
BK  
T3 T2 T1  
COMP  
BR  
T1  
L1  
T2  
L2  
GND  
BK  
PU  
BL  
YL  
C
BL  
BK  
RD  
BK  
208-240/1/60  
SEE NOTE 5  
CM  
PU  
RD  
BR  
RD  
NOTE 2  
EM  
3 SPEED  
BC  
1
C
2
208  
3
240  
FOR  
TR  
24V  
ALTERNATE  
MOTOR  
6-WIRES  
BL  
SMOKE/FIRE  
DETECTOR  
REPLACE  
JUMPER  
LS  
RD  
RD  
PU  
RD  
PU  
YL RD  
YL  
BK  
PK  
BL  
BL  
GR  
SEE NOTE 6 & 7  
S1  
PK  
BR  
EM  
3 SPEED  
BC  
BR  
PU  
TB1  
S2  
SEE NOTE 7  
BL  
2
C 2  
T 2  
T 1  
BK  
P 2  
RD  
OR  
YL  
1 5 0  
1 3 5  
1 2 0  
ALS  
P 3  
X A P M M  
A
S U E F  
3
1 F  
IIC  
PU  
RD  
GR  
RD  
BR  
BL  
PS  
RS  
YL  
YL  
PU  
YL  
PU  
YL  
YL  
WH  
RD  
NOTE 4  
PLF  
BR  
GR  
RD  
BK  
BK  
3
2
1
6
RD  
BK  
5
4
YL  
BL  
PU  
YL  
PU  
BL  
BL  
RD WH  
W. R.  
GAS VALVE  
(ALT.) HONEYWELL  
GAS VALVE  
BL  
BL  
BK  
MV  
PU  
YL  
BL  
RD  
PU  
GR  
GV  
MV  
BR  
LPS  
GV  
RD  
BL  
BL  
YL/PK  
BL/PK  
Y2 W2 C RY1W1G  
RD  
SEE NOTE 8  
GREEN JUMPER  
WH  
TO THERMOSTAT  
RD  
TB1  
SEE  
NOTE 9  
FS  
IGN  
VM  
OR  
RD  
BK  
RCCF  
H
HPS  
RD  
YL  
F
C
BR  
L1  
L2  
COMPONENT LEGEND  
ALS  
AUXILLARY LIMIT SWITCH  
COMP COMPRESSOR  
FACTORY WIRING  
SUPPLY VOLTAGE  
208-240/1/60  
LINE VOLTAGE  
LOW VOLTAGE  
CM  
C
CONDENSER MOTOR  
CONTACTOR  
OPTIONAL  
HIGH VOLTAGE  
T2  
C
C
T1  
R
S
L2  
EM  
F
EVAPORATOR MOTOR  
FUSE  
L1  
C
COMP  
H
RCCF  
F
C
FIELD WIRING  
FS  
FLAME SENSOR  
EQUIPMENT GROUND  
GAS VALVE  
HIGH VOLTAGE  
LOW VOLTAGE  
GND  
GV  
HPS  
CM  
HIGH PRESSURE SWITCH  
IIC  
IGN  
LS  
LPS  
INTEGRATED IGNITION CONTROL  
IGNITOR  
LIMIT SWITCH  
LOW PRESSURE SWITCH  
FEMALE PLUG/CONNECTOR  
HEAT  
PCB  
WIRE CODE  
BK BLACK  
BL BLUE  
BR BROWN  
GR GREEN  
OR ORANGE  
PK PINK  
PU PURPLE  
RD RED  
WH WHITE  
YL YELLOW  
BL/PK BLUE WITH PINK STRIP  
FC  
EM  
PCB  
LI  
PLF  
RCCF RUN CAPACITOR FOR CONDENSER FAN  
PS  
RS  
TB1  
TR  
VM  
VMR  
BC  
COOL  
DI  
VM  
SEE NOTE 2  
2
PRESSURE SWITCH  
ROLLOUT SWITCH  
TERMINAL BLOCK (24V SIGNAL)  
TRANSFORMER  
VENT MOTOR  
VENT MOTOR RELAY  
BLOWER CAPACITOR  
3
1
TR  
TB1  
FS  
IIC  
IGN  
FS  
F
YL/PK YELLOW WITH PINK STRIP  
NOTES  
1. REPLACEMENT WIRE MUST BE THE SAME  
SIZE AND TYPE OF INSULATION AS ORIGINAL.  
(USE COPPER CONDUCTOR ONLY).  
4
5
LS  
2. FOR 208 VOLT TRANSFORMER OPERATION  
TO  
ALS  
RS  
THERMOSTAT  
FIELD WIRING  
IIC  
3
6
GV  
MOVE BLACK WIRE FROM TERMINAL  
TERMINAL ON TRANSFORMER.  
3
2
3. FOR DIFFERENT THAN FACTORY SPEED TAP.  
CHANGE COOLING SPEED AT COOL  
TERMINAL. CHANGE HEATING SPEED AT  
HEAT TERMINAL ON CONTROL BOARD  
3 SPEED MOTOR  
RD - LOW SPEED  
BL - MED. SPEED  
BK - HIGH SPEED  
PS  
NO ECONOMIZER  
8
ECON  
W
G
WH  
GR  
RD  
W
G
R
9
7
10  
12  
11  
LPS  
HPS  
C
NOTE  
R
Y1  
Y/Y2  
C
YL  
BL  
6
5
2
4
Y
C
4. ACCESSORY ECONOMIZER PLUG ADJACENT  
TO BLOWER HOUSING IN RETURN AIR  
COMPARTMENT. REMOVE MALE PLUG AND  
ATTACH FEMALE PLUG TO ECONOMIZER  
ACCESSORY.  
4
3
1
R
G
W
Y1  
Y2  
C
PLF  
TB1  
TO THERMOSTAT  
TERMINAL BLOCK  
STAT  
TB1  
5. USE COPPER CONDUCTORS ONLY.  
USE NEC CLASS 2 WIRE.  
WITH ECONOMIZER OPTION  
INSTALLER/SERVICEMAN  
THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO  
TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS:  
W
G
WH  
GR  
RD  
W
G
R
Y
6. PURPLE WIRE CONNECTS TO TRANSFORMER  
(PIN 1).  
R
7. SPEED TAP TERMINATIONS SHOWN ON  
DIAGRAM ARE REPRESENTATIVE, BUT ACTUAL  
FACTORY SETTING MAY BE DIFFERENT BASED  
ON HEATING VALUE AND CAPACITY OF UNIT.  
EQUIP. STATUS  
NORMAL OPERATION  
CHECK  
-
STATUS LIGHT  
ON  
YL  
Y1  
Y/Y2  
C
NO POWER OR  
INTERNAL CONTROL  
FAULT  
CHECK INPUT POWER  
CHECK FUSE ON CONTROL  
REPLACE CONTROL  
OFF  
BL  
8. TO RUN DIFFERENT SPEED FOR HEATING AND  
COOLING, DISCONNECT GEEEN JUMPER FROM  
"COOL" TERMINAL AND REPLACE WITH  
APPROPRIATE SPEED TAP. THEN PLACE  
DISCONNECTED END OF JUMPER ON  
"UNUSED" TERMINAL LEFT OPEN BY MOVING  
THE SPEED TAP.  
C
IGNITION FAILURE  
OR  
GAS FLOW  
GAS PRESSURE  
GAS VALVE  
FLAME SENSOR  
FLAME ROLLOUT  
BAD SWITCH  
1 BLINK  
STAT  
TB1  
OPEN ROLLOUT  
SWITCH  
OR  
2 STAGE COOLING  
W
WH  
GR  
RD  
YL  
W
G
OPEN AUX. LIMIT  
SWITCH  
PRESSURE SWITCH  
OPEN  
PRESSURE SWITCH CLOSED  
WITHOUT INDUCER ON  
OPEN LIMIT SWITCH  
AUX. LIMIT OPEN  
CHECK  
PRESSURE SWITCH  
CHECK  
PRESSURE SWITCH  
MAIN LIMIT OPEN  
BAD SWITCH  
9. FOR LOW STAGE OPERATION ONLY, REMOVE  
WHITE JUMPER. FOR 2 STAGE OPERATION,  
REMOVE JUMPER AND CONNECT W2 TO W1  
ON THERMOSTAT.  
G
R
2 BLINKS  
3 BLINKS  
4 BLINKS  
R
Y1  
Y1  
Y2  
C
PK  
BL  
Y/Y2  
C
SEE UNIT RATING PLATE FOR TYPE AND SIZE OF  
OVERCURRENT PROTECTION.  
5 BLINKS  
6 BLINKS  
FALSE FLAME SENSED  
COMPRESSOR  
OUTPUT DELAY  
STICKING GAS VALVE  
3 MIN. COMP.  
ANTI-CYCLE TIMER  
STAT  
TB1  
208-240/1/60 0140L00506 REV A  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPG36-72  
Product SPecificationS  
Wiring diagram cPg060*1d (Single-PhaSe direct drive)  
YL  
RD  
BK  
PU  
RD  
BK  
S
R
C
T1  
L1  
T2  
L2  
GND  
BL  
YL  
COMP  
C
POWER SUPPLY  
240/1/60  
SEE NOTE 6  
RD  
PU  
BK  
BK  
BK  
BR  
RD  
RD  
CM  
BK  
BK  
NOTE 2  
RD  
BK  
1
2
3
BL  
GR  
C
208  
240  
3
TR  
24V  
2
LS  
C
L
G
N
RD  
1
BL  
EM  
VMR  
T1 T2 T3 T4 T5  
OR YL  
RD  
PK  
BL  
GR  
BK  
WH  
NOTE 3 & 7  
WH PU  
BR  
YL/PK  
LPS  
BL  
OR  
YL  
WH PU  
BR  
TB1  
1
2
C 2  
5
T 2  
T 1  
WH  
YL  
P 2  
HPS  
OR  
1 5 0  
ALS  
P 3  
1 3 5  
1 2 0  
X A M P A M 3 E S U F  
1 F  
PU  
YL  
RD  
GR  
RD  
YL/PK  
RD  
BL  
PU  
YL  
YL  
PK  
PS  
RS  
YL  
PU  
S1  
YL  
YL WH  
RD  
GR  
PLF  
NOTE 4  
BR WH  
BL YL  
S2  
TB1  
SMOKE/FIRE  
RD  
WH  
BR  
YL  
DETECTOR  
REPLACES  
JUMPER  
WIRE  
3
2
1
6
5
4
BL  
SEE  
NOTE 6  
RD  
BL  
BL  
PU  
YL  
PU  
RD WH  
W. R.  
GAS VALVE  
(ALT.) HONEYWELL  
GAS VALVE  
PU  
YL  
BL  
GR  
BR  
MV  
PU  
BL  
BL  
BL BL  
GV  
MV  
GV  
G
Y Y1 C R W W2  
BL  
BR  
TB1  
YL WH  
WH  
SEE  
NOTE 8  
TO THERMOSTAT  
RD  
FS  
VM  
IGN  
OR  
BK  
RD  
BL  
BR  
YL  
RCCF  
YL  
WH  
BR  
F
H
C
RD  
L1  
L1  
L2  
L2  
SUPPLY VOLTAGE  
240/1/60  
FACTORY WIRING  
COMPONENT LEGEND  
LINE VOLTAGE  
LOW VOLTAGE  
ALS  
COMP  
CM  
C
AUXILLARY LIMIT SWITCH  
COMPRESSOR  
CONDENSER MOTOR  
CONTACTOR  
OPTIONAL  
HIGH VOLTAGE  
T2  
C
C
T1  
R
S
EM  
F
EVAPORATOR MOTOR  
FUSE  
C
COMP  
H
RCCF  
C
FIELD WIRING  
FS  
FLAME SENSOR  
HIGH VOLTAGE  
LOW VOLTAGE  
C
CM  
GND  
GV  
EQUIPMENT GROUND  
GAS VALVE  
HPS  
IIC  
IGN  
LPS  
LS  
HIGH PRESSURE SWITCH  
INTEGRATED IGNITION CONTROL  
IGNITOR  
LOW PRESSURE SWITCH  
LIMIT SWITCH  
L
N
WIRE CODE  
VMR  
EM  
BK BLACK  
BL BLUE  
4
2
VM  
SEE NOTE 2  
2
BR BROWN  
GR GREEN  
PLF  
PS  
FEMALE PLUG/CONNECTOR  
PRESSURE SWITCH  
3
1
RCCF RUN CAPACITOR FOR COMPRESSOR/FAN  
OR ORANGE  
PK PINK  
PU PURPLE  
RD RED  
WH WHITE  
TR  
TB1  
NOTE 6  
T5  
RS  
TB1  
TR  
ROLLOUT SWITCH  
TERMINAL BLOCK (24V SIGNAL)  
TRANSFORMER  
NOTE 6  
L1  
L2  
TB1  
IGN  
IIC  
FS  
D1  
FS  
VM  
VENT MOTOR  
F
C
H
T4  
T3  
VMR  
VENT MOTOR RELAY  
EM  
C
YL YELLOW  
BL/PK BLUE WITH PINK STRIP  
YL/PK YELLOW WITH PINK STRIP  
T2 T1  
NOTES  
1
3
1. REPLACEMENT WIRE MUST BE THE SAME  
SIZE AND TYPE OF INSULATION AS ORIGINAL.  
(USE COPPER CONDUCTOR ONLY).  
4
5
VMR  
TB1  
LS  
2. FOR 208 VOLT TRANSFORMER OPERATION  
ALS  
RS  
THERMOSTAT  
FIELD WIRING  
IIC  
3
6
GV  
MOVE BLACK WIRE FROM TERMINAL  
TERMINAL ON TRANSFORMER.  
3
TO  
2
3. FOR DIFFERENT THAN FACTORY SPEED TAP.  
CHANGE COOLING SPEED AT MOTOR T4 AND  
T5 TERMINALS. CHANGE HEATING SPEED AT  
MOTOR T1. T2, AND T3 TERMINALS  
PS  
NO ECONOMIZER  
8
ECON  
W
G
WH  
GR  
RD  
W
G
R
9
7
C
10  
12  
11  
COOLING SPEED (YELLOW WIRE)  
T3 - LOW SPEED  
T4 - HIGH SPEED  
R
LPS  
HPS  
Y1  
Y/Y2  
C
NOTE  
4
HEATING SPEED (WHITE WIRE)  
T1 - LOW SPEED (070)  
T2 - MED. SPEED  
YL  
BL  
6
3
5
2
4
1
Y
PLF  
C
Y
Y2  
R
G
W1  
Y1  
C
TB1  
T5 - HIGH SPEED (140)  
TO THERMOSTAT  
TERMINAL BLOCK  
STAT  
4. ACCESSORY ECONOMIZER PLUG ADJACENT  
TO BLOWER HOUSING IN RETURN AIR  
COMPARTMENT. REMOVE MALE PLUG AND  
ATTACH FEMALE PLUG TO ECONOMIZER  
ACCESSORY.  
TB1  
WITH ECONOMIZER OPTION  
W
G
WH  
GR  
RD  
W
G
R
Y
INSTALLER/SERVICEMAN  
THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO  
TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS:  
5. USE COPPER CONDUCTORS ONLY.  
USE NEC CLASS 2 WIRE.  
R
EQUIP. STATUS  
CHECK  
-
STATUS LIGHT  
ON  
6. L1 AND L2 ON ICC CONTROL IS 24V INPUT.  
7. SPEED TAP TERMINATIONS SHOWN ON  
DIAGRAM ARE REPRESENTATIVE, BUT  
ACTUAL FACTORY SETTINGS MAY BE  
DIFFERENT BASED ON THE HEATING VALUE  
OF THE UNIT.  
8. FOR LOW STAGE OPERATION ONLY, REMOVE  
WHITE JUMPER. FOR 2 STAGE OPERATION,  
REMOVE JUMPER AND CONNECT W2 TO W2  
ON THERMOSTAT.  
YL  
Y1  
Y/Y2  
C
NORMAL OPERATION  
NO POWER OR  
INTERNAL CONTROL  
FAULT  
IGNITION FAILURE  
OR  
OPEN ROLLOUT  
SWITCH  
CHECK INPUT POWER  
CHECK FUSE ON CONTROL  
REPLACE CONTROL  
GAS FLOW  
GAS PRESSURE  
GAS VALVE  
FLAME SENSOR  
FLAME ROLLOUT  
BAD SWITCH  
OFF  
BL  
C
1 BLINK  
STAT  
TB1  
2 STAGE COOLING  
OR  
W
G
WH  
GR  
RD  
YL  
W
G
OPEN AUX. LIMIT  
SWITCH  
PRESSURE SWITCH  
OPEN  
PRESSURE SWITCH CLOSED  
WITHOUT INDUCER ON  
OPEN LIMIT SWITCH  
AUX. LIMIT OPEN  
CHECK  
PRESSURE SWITCH  
2 BLINKS  
3 BLINKS  
4 BLINKS  
R
R
CHECK  
PRESSURE SWITCH  
MAIN LIMIT OPEN  
BAD SWITCH  
Y1  
Y/Y2  
C
Y1  
Y2  
C
PK  
BL  
SEE UNIT RATING PLATE FOR TYPE AND SIZE  
OF OVER CURRENT PROTECTION .  
5 BLINKS  
6 BLINKS  
FALSE FLAME SENSED  
STICKING GAS VALVE  
3 MIN. COMP.  
ANTI-CYCLE TIMER  
COMPRESSOR  
OUTPUT DELAY  
STAT  
TB1  
240/1/60 0140L00429 REV A  
SS-CPG36-72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
31  
Product SPecificationS  
Wiring diagram cPg060*3d (three-PhaSe, direct drive)  
RD  
YL  
BK  
PU  
RD  
BK  
T3 T2 T1  
T1  
L1  
T2  
L2  
T3  
L3  
GND  
YL  
OR  
BK  
POWER SUPPLY  
COMP  
C
BL  
PU  
BK  
RD  
240/3/60  
SEE NOTE 5  
BR  
BK  
RD  
NOTE 2  
CM  
BK  
BK  
BK  
1
C
2
3
240  
3
1
208  
TR  
24V  
RD  
2
BL  
GR  
LS  
RD  
RD  
OR  
YL RD  
BL  
VMR  
WH  
C
L G N  
EM  
BL  
GR PK  
BK  
T1 T2 T3 T4 T5  
BL  
WH PU  
OR BR YL  
WH PU  
OR BR YL  
TB1  
RE  
S
M
2 2  
C
CR  
O
T 2  
Q
U
T 1  
U
E
W
1
5
B
S
RE  
P 2  
P
E
A
C
K
ED  
O
F
WH  
YL  
NOTE 3 & 7  
O
-
U
R
R
P
ES  
TW  
OR  
S
O
OR  
ST  
0 5 1  
5 3 1  
0 2 1  
A
GE  
P 3  
X
M A P A M 3 S E U F  
F 1  
ALS  
PS  
P
1
RD  
RD  
GR  
PU  
10  
RD  
1
1
PK  
YL  
BL  
12  
YL  
YL  
PU  
YL  
PU  
S1  
TB1  
YL  
YL  
WH  
RD  
NOTE 4  
PLF  
BR WH  
BL YL  
GR  
S2  
FOR  
RS  
RD  
WH  
BR  
SMOKE/FIRE  
DETECTOR  
REPLACE  
JUMPER  
3
2
1
6
5
4
YL  
BL  
SEE  
RD  
BL  
BL  
NOTE 6  
PU  
YL  
PU  
LPS  
IIC  
YL/PK  
W. R.  
GAS VALVE  
(ALT.) HONEYWELL  
GAS VALVE  
RD  
WH BR  
BL  
MV  
PU  
YL  
BL  
GR BL  
BL  
PU  
GV  
GV  
MV  
BL  
Y2 C R Y1 W W2 G  
TO THERMOSTAT  
BR  
TB1  
BL  
YL WH  
SEE  
NOTE 8  
BL/PK  
VM  
FS  
IGN  
RD  
OR  
HPS  
BK  
WH  
BL  
FC  
YL  
WH  
RD  
BR  
BR  
L1  
SUPPLY VOLTAGE  
240/3/60  
L2  
L2  
L3  
FACTORY WIRING  
COMPONENT LEGEND  
LINE VOLTAGE  
LOW VOLTAGE  
OPTIONAL  
ALS  
COMP  
CM  
C
AUXILIARY LIMIT SWITCH  
COMPRESSOR  
CONDENSER MOTOR  
CONTACTOR  
C
T2  
HIGH VOLTAGE  
C
T1  
T2  
EM  
F
FC  
EVAPORATOR MOTOR  
FUSE  
FAN CAPACITOR  
FLAME SENSOR  
EQUIPMENT GROUND  
GAS VALVE  
COMP  
L1  
T1  
L3  
FIELD WIRING  
T3  
T3  
C
HIGH VOLTAGE  
LOW VOLTAGE  
FS  
GND  
GV  
FC  
CM  
WIRE CODE  
HPS  
IIC  
HIGH PRESSURE SWITCH  
L
N
VMR  
BK BLACK  
INTEGRATED IGNITION CONTROL  
IGNITOR  
LIMIT SWITCH  
LOW PRESSURE SWITCH  
FEMALE PLUG/CONNECTOR  
PRESSURE SWITCH  
ROLLOUT SWITCH  
TERMINAL BLOCK (24V SIGNAL)  
TRANSFORMER  
VENT MOTOR  
EM  
BL BLUE  
BR BROWN  
GR GREEN  
IGN  
LS  
LPS  
PLF  
PS  
3
1
VM  
SEE NOTE 2  
2
3
1
OR ORANGE  
PK PINK  
TR  
TB1  
NOTE 6  
NOTE 6  
RS  
TB1  
TR  
PU PURPLE  
RD RED  
L1  
L2  
IIC  
IGN  
1
WH WHITE  
FS  
D1  
FS  
2
3
4
5
VM  
VMR  
F
EM  
C
YL YELLOW  
BL/PK BLUE WITH PINK STRIP  
YL/PK YELLOW WITH PINK STRIP  
H
VENT MOTOR RELAY  
C
NOTE 3  
TB1  
NOTES  
1. REPLACEMENT WIRE MUST BE THE SAME  
4
5
SIZE AND TYPE OF INSULATION AS ORIGINAL.  
(USE COPPER CONDUCTOR ONLY).  
VMR  
RS  
LS  
2. FOR 208 VOLT TRANSFORMER OPERATION  
MOVE BLACK WIRES FROM TERMINAL  
TERMINAL ON TRANSFORMER.  
ALS  
THERMOSTAT  
FIELD WIRING  
3
TO  
IIC  
3
GV  
2
6
8
3. FOR DIFFERENT THAN FACTORY SPEED TAP.  
CHANGE COOLING SPEED AT MOTOR T3 AND  
T4 TERMINALS. CHANGE HEATING SPEED AT  
MOTOR T1. T2, AND T5 TERMINALS  
PS  
NO ECONOMIZER  
ECON  
W
G
WH  
GR  
RD  
W
G
R
9
7
10  
12  
11  
COOLING SPEED (YELLOW WIRE)  
T3 - LOW SPEED  
T4 - HIGH SPEED  
LPS  
HPS  
C
NOTE 4  
PLF  
R
Y1  
Y/Y2  
C
HEATING SPEED (WHITE WIRE)  
T1 - LOW SPEED (070)  
T2 - MED. SPEED  
YL  
BL  
Y
6
3
5
4
1
C
2
R
G
W
W2  
Y1  
Y2  
C
T5 - HIGH SPEED (140)  
TB1  
4. ACCESSORY ECONOMIZER PLUG ADJACENT  
TO BLOWER HOUSING IN RETURN AIR  
COMPARTMENT. REMOVE MALE PLUG AND  
ATTACH FEMALE PLUG TO ECONOMIZER  
ACCESSORY.  
TO THERMOSTAT  
TERMINAL BLOCK  
STAT  
TB1  
WITH ECONOMIZER OPTION  
W
G
WH  
GR  
RD  
W
G
R
Y
INSTALLER/SERVICEMAN  
THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO  
TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS:  
5. USE COPPER CONDUCTORS ONLY.  
USE NEC CLASS 2 WIRE.  
R
6. L1 AND L2 ON ICC CONTROL IS 24V INPUT.  
7. SPEED TAP TERMINATIONS SHOWN ON  
DIAGRAM ARE REPRESENTATIVE, BUT  
EQUIP. STATUS  
CHECK  
STATUS LIGHT  
ON  
YL  
Y1  
Y/Y2  
C
NORMAL OPERATION  
-
NO POWER OR  
INTERNAL CONTROL  
FAULT  
CHECK INPUT POWER  
CHECK FUSE ON CONTROL  
REPLACE CONTROL  
OFF  
ACTUAL FACTORY SETTINGS MAY BE  
DIFFERENT BASED ON THE HEATING VALUE  
OF THE UNIT.  
BL  
C
IGNITION FAILURE  
OR  
OPEN ROLLOUT  
SWITCH  
OR  
OPEN AUX. LIMIT  
SWITCH  
GAS FLOW  
GAS PRESSURE  
GAS VALVE  
FLAME SENSOR  
FLAME ROLLOUT  
BAD SWITCH  
AUX. LIMIT OPEN  
CHECK  
PRESSURE SWITCH  
1 BLINK  
STAT  
8. FOR LOW STAGE OPERATION ONLY, REMOVE  
TB1  
WHITE JUMPER. FOR 2 STAGE OPERATION,  
REMOVE JUMPER AND CONNECT W2 TO W2  
ON THERMOSTAT.  
2 STAGE COOLING  
W
G
WH  
GR  
RD  
YL  
W
G
2 BLINKS  
3 BLINKS  
4 BLINKS  
PRESSURE SWITCH  
OPEN  
R
R
PRESSURE SWITCH CLOSED  
WITHOUT INDUCER ON  
CHECK  
PRESSURE SWITCH  
Y1  
Y/Y2  
C
Y1  
Y2  
C
SEE UNIT RATING PLATE FOR TYPE AND SIZE OF OVER  
CURRENT PROTECTION  
PK  
BL  
OPEN LIMIT SWITCH  
MAIN LIMIT OPEN  
BAD SWITCH  
5 BLINKS  
6 BLINKS  
FALSE FLAME SENSED  
COMPRESSOR  
OUTPUT DELAY  
STICKING GAS VALVE  
3 MIN. COMP.  
ANTI-CYCLE TIMER  
STAT  
TB1  
230/3/60 0140L00980 REV B  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPG36-72  
Product SPecificationS  
Wiring diagram cPg036.48*3d (three-PhaSe direct drive)  
RD  
YL  
RD  
BK  
PU  
BK  
T3 T2 T1  
COMP  
BR  
T1  
L1  
T2  
L2  
T3  
L3  
GND  
BK  
PU  
BL  
YL  
C
BL  
BK  
RD  
POWERSUPPLY  
208-240/3/60  
SEE NOTE 5  
BK  
CM  
PU  
RD  
BR  
RD  
NOTE 2  
EM  
3 SPEED  
BC  
1
C
2
208  
3
240  
FOR  
TR  
24V  
ALTERNATE  
MOTOR  
6-WIRES  
BL  
SMOKE/FIRE  
DETECTOR  
REPLACE  
JUMPER  
LS  
RD  
RD  
PU  
RD  
YL RD  
BK  
PK  
BL  
BL  
GR  
SEE NOTE 6 & 7  
PU  
S1  
PK  
BR  
EM  
3 SPEED  
BC  
BR  
PU  
TB1  
S2  
SEE NOTE 7  
BL  
R
S
M
2 2  
C
O
T 2  
U
T 1  
U
EW  
NT  
BK  
B
S
RE  
P 2  
D
P
E
A
C
K
O
RD  
D-  
F
O
U
R
RE  
P
TW  
OR  
S
SO  
O
ST  
R
0 5 1  
5 3 1  
0 2 1  
A
ALS  
GE  
P 3  
X
M A P A M 3 S E U F  
F 1  
IIC  
P
1
PU  
RD  
GR  
RD  
10  
BR  
BL  
1
1
YL  
YL  
PS  
RS  
12  
YL  
YL  
PU  
PU  
YL  
YL  
WH  
RD  
NOTE 4  
PLF  
BR  
GR  
RD  
BK  
BK  
3
2
1
6
RD  
BK  
5
4
YL  
BL  
PU  
YL  
PU  
BL  
RD WH  
W. R.  
GAS VALVE  
(ALT.) HONEYWELL  
GAS VALVE  
BL  
BL  
BK  
MV  
PU  
YL  
Y2  
BL  
RD  
GR  
PU  
GV  
LPS  
GV  
RD  
MV  
BL  
YL/PK  
C
RY1W1G  
RD  
SEE NOTE 8  
GREEN JUMPER  
BL  
TB1  
TO THERMOSTAT  
VM  
FS  
IGN  
RD  
OR  
RD  
BK  
BL/PK  
FC  
HPS  
RD  
F
C
BR  
COMPONENT LEGEND  
L1  
SUPPLY VOLTAGE  
208-240/3/60  
L2  
L3  
L3  
FACTORY WIRING  
ALS  
COMP  
CM  
C
AUXILLARY LIMIT SWITCH  
COMPRESSOR  
CONDENSER MOTOR  
CONTACTOR  
LINE VOLTAGE  
LOW VOLTAGE  
OPTIONAL  
HIGH VOLTAGE  
C
T2  
C
T1  
L2  
T2  
EM  
F
FC  
EVAPORATOR MOTOR  
FUSE  
FAN CAPACITOR  
FLAME SENSOR  
EQUIPMENT GROUND  
GAS VALVE  
L1  
T1 COMP  
T3  
FIELD WIRING  
T3  
C
FS  
HIGH VOLTAGE  
LOW VOLTAGE  
FC  
FC  
GND  
GV  
HPS  
CM  
HIGH PRESSURE SWITCH  
WIRE CODE  
IIC  
IGN  
LS  
LPS  
INTEGRATED IGNITION CONTROL  
IGNITOR  
LIMIT SWITCH  
HEAT  
PCB  
BK BLACK  
BL BLUE  
EM  
BR BROWN  
GR GREEN  
LOW PRESSURE SWITCH  
PCB  
PLF  
PS  
RS  
FEMALE PLUG/CONNECTOR  
PRESSURE SWITCH  
ROLLOUT SWITCH  
VM  
DI  
LI  
COOL  
OR ORANGE  
PK PINK  
PU PURPLE  
SEE NOTE 2  
2
3
1
TB1  
TR  
VM  
VMR  
BC  
TERMINAL BLOCK (24V SIGNAL)  
TRANSFORMER  
VENT MOTOR  
VENT MOTOR RELAY  
BLOWER CAPACITOR  
RD RED  
WH WHITE  
YL YELLOW  
TR  
TB1  
FS  
IIC  
IGN  
BL/PK BLUE WITH PINK STRIP  
YL/PK YELLOW WITH PINK STRIP  
FS  
F
NOTES  
1. REPLACEMENT WIRE MUST BE THE SAME  
SIZE AND TYPE OF INSULATION AS ORIGINAL.  
(USE COPPER CONDUCTOR ONLY).  
4
5
LS  
2. FOR 208 VOLT TRANSFORMER OPERATION  
TO  
ALS  
RS  
THERMOSTAT  
FIELD WIRING  
MOVE BLACK WIRE FROM TERMINAL  
TERMINAL ON TRANSFORMER.  
3
IIC  
3
6
GV  
2
3. FOR DIFFERENT THAN FACTORY SPEED TAP.  
CHANGE COOLING SPEED AT COOL  
TERMINAL. CHANGE HEATING SPEED AT  
HEAT TERMINAL ON CONTROL BOARD  
3 SPEED MOTOR  
PS  
NO ECONOMIZER  
8
ECON  
W
G
WH  
GR  
RD  
W
G
R
9
7
10  
12  
11  
LPS  
HPS  
C
NOTE  
RD - LOW SPEED  
BL - MED. SPEED  
BK - HIGH SPEED  
R
Y1  
Y/Y2  
C
YL  
BL  
6
5
2
4
Y
C
4. ACCESSORY ECONOMIZER PLUG ADJACENT  
TO BLOWER HOUSING IN RETURN AIR  
COMPARTMENT. REMOVE MALE PLUG AND  
ATTACH FEMALE PLUG TO ECONOMIZER  
ACCESSORY.  
4
3
1
R
G
W
Y1  
Y2  
C
PLF  
TB1  
TO THERMOSTAT  
TERMINAL BLOCK  
STAT  
TB1  
5. USE COPPER CONDUCTORS ONLY.  
USE NEC CLASS 2 WIRE.  
WITH ECONOMIZER OPTION  
W
G
WH  
GR  
RD  
W
G
R
Y
INSTALLER/SERVICEMAN  
THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO  
TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS:  
6. PURPLE WIRE CONNECTS TO TRANSFORMER  
(PIN 1).  
R
7. SPEED TAP TERMINATIONS SHOWN ON  
DIAGRAM ARE REPRESENTATIVE, BUT ACTUAL  
FACTORY SETTING MAY BE DIFFERENT BASED  
ON HEATING VALUE AND CAPACITY OF UNIT.  
EQUIP. STATUS  
CHECK  
STATUS LIGHT  
ON  
YL  
Y1  
Y/Y2  
C
NORMAL OPERATION  
-
NO POWER OR  
INTERNAL CONTROL  
FAULT  
CHECK INPUT POWER  
CHECK FUSE ON CONTROL  
REPLACE CONTROL  
OFF  
BL  
8. TO RUN DIFFERENT SPEED FOR HEATING AND  
COOLING, DISCONNECT GEEEN JUMPER FROM  
"COOL" TERMINAL AND REPLACE WITH  
APPROPRIATE SPEED TAP. THEN PLACE  
DISCONNECTED END OF JUMPER ON  
"UNUSED" TERMINAL LEFT OPEN BY MOVING  
THE SPEED TAP.  
C
IGNITION FAILURE  
OR  
OPEN ROLLOUT  
SWITCH  
OR  
OPEN AUX. LIMIT  
SWITCH  
GAS FLOW  
GAS PRESSURE  
GAS VALVE  
FLAME SENSOR  
FLAME ROLLOUT  
BAD SWITCH  
AUX. LIMIT OPEN  
CHECK  
PRESSURE SWITCH  
1 BLINK  
STAT  
TB1  
2 STAGE COOLING  
W
WH  
GR  
RD  
YL  
W
G
G
R
2 BLINKS  
3 BLINKS  
4 BLINKS  
PRESSURE SWITCH  
OPEN  
R
SEE UNIT RATING PLATE FOR TYPE AND SIZE OF  
OVERCURRENT PROTECTION.  
PRESSURE SWITCH CLOSED  
WITHOUT INDUCER ON  
CHECK  
PRESSURE SWITCH  
Y1  
Y/Y2  
C
Y1  
Y2  
C
PK  
BL  
OPEN LIMIT SWITCH  
MAIN LIMIT OPEN  
BAD SWITCH  
5 BLINKS  
6 BLINKS  
FALSE FLAME SENSED  
COMPRESSOR  
OUTPUT DELAY  
STICKING GAS VALVE  
3 MIN. COMP.  
ANTI-CYCLE TIMER  
STAT  
TB1  
208-240/3/60 0140L00512 REV B  
SS-CPG36-72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
33  
Product SPecificationS  
Wiring diagram cPg036/48*3d (three-PhaSe, direct drive)  
RD  
YL  
RD  
BK  
PU  
BK  
T3 T2 T1  
COMP  
BR  
T1  
L1  
T2  
L2  
T3  
L3  
GND  
BK  
PU  
BL  
YL  
C
BL  
BK  
RD  
POWERSUPPLY  
208-240/3/60  
SEE NOTE 5  
BK  
CM  
PU  
RD  
BR  
RD  
NOTE 2  
EM  
3 SPEED  
BC  
1
C
2
208  
3
240  
FOR  
TR  
24V  
ALTERNATE  
MOTOR  
6-WIRES  
BL  
SMOKE/FIRE  
DETECTOR  
REPLACE  
JUMPER  
LS  
RD  
RD  
PU  
RD  
YL RD  
BK  
PK  
BL  
BL  
GR  
SEE NOTE 6 & 7  
PU  
S1  
PK  
BR  
EM  
3 SPEED  
BC  
BR  
PU  
TB1  
S2  
SEE NOTE 7  
BL  
R
S
M
2 2  
C
C
O
T 2  
RE  
U
T 1  
W
BK  
ED  
B
S
R
P 2  
P
EA  
E
CO  
K
E
RD  
D
F
M
O
-
U
P
R
RE  
P
T
OR  
S
S
OR  
S
0 5 1  
5 3 1  
0 2 1  
T
A
ALS  
GE  
P 3  
A X M P A M 3 E S U F  
F 1  
IIC  
P
1
PU  
RD  
GR  
RD  
10  
BR  
BL  
1
1
YL  
YL  
PS  
RS  
12  
YL  
YL  
PU  
PU  
YL  
YL  
WH  
RD  
NOTE 4  
PLF  
BR  
GR  
RD  
BK  
BK  
3
2
1
6
RD  
BK  
5
4
YL  
BL  
PU  
YL  
PU  
BL  
RD WH  
W. R.  
GAS VALVE  
(ALT.) HONEYWELL  
GAS VALVE  
BL  
BL  
BK  
MV  
PU  
YL  
BL  
RD  
GR  
PU  
GV  
BR  
LPS  
GV  
RD  
MV  
BL  
BL  
YL/PK  
Y2 W2 C RY1W1G  
RD  
SEE NOTE 8  
GREEN JUMPER  
WH  
TO THERMOSTAT  
RD  
TB1  
SEE  
NOTE 9  
VM  
FS  
IGN  
OR  
RD  
BK  
BL/PK  
FC  
HPS  
RD  
F
C
BR  
COMPONENT LEGEND  
L1  
L1  
SUPPLY VOLTAGE  
208-240/3/60  
L2  
L3  
L3  
FACTORY WIRING  
ALS  
COMP  
CM  
C
AUXILIARY LIMIT SWITCH  
COMPRESSOR  
CONDENSER MOTOR  
CONTACTOR  
LINE VOLTAGE  
LOW VOLTAGE  
OPTIONAL  
HIGH VOLTAGE  
C
T2  
C
T1  
L2  
T2  
EM  
F
FC  
EVAPORATOR MOTOR  
FUSE  
FAN CAPACITOR  
FLAME SENSOR  
EQUIPMENT GROUND  
GAS VALVE  
T1 COMP  
T3  
FIELD WIRING  
T3  
C
FS  
HIGH VOLTAGE  
LOW VOLTAGE  
FC  
GND  
GV  
HPS  
CM  
HIGH PRESSURE SWITCH  
WIRE CODE  
IIC  
INTEGRATED IGNITION CONTROL  
IGNITOR  
LIMIT SWITCH  
HEAT  
PCB  
BK BLACK  
BL BLUE  
IGN  
LS  
LPS  
FC  
EM  
BR BROWN  
GR GREEN  
LOW PRESSURE SWITCH  
PCB  
PLF  
PS  
RS  
FEMALE PLUG/CONNECTOR  
PRESSURE SWITCH  
ROLLOUT SWITCH  
VM  
DI  
LI  
COOL  
OR ORANGE  
PK PINK  
PU PURPLE  
SEE NOTE 2  
2
3
1
TB1  
TR  
VM  
VMR  
BC  
TERMINAL BLOCK (24V SIGNAL)  
TRANSFORMER  
VENT MOTOR  
VENT MOTOR RELAY  
BLOWER CAPACITOR  
RD RED  
WH WHITE  
YL YELLOW  
TR  
TB1  
FS  
IIC  
IGN  
BL/PK BLUE WITH PINK STRIP  
YL/PK YELLOW WITH PINK STRIP  
FS  
F
NOTES  
1. REPLACEMENT WIRE MUST BE THE SAME  
SIZE AND TYPE OF INSULATION AS ORIGINAL.  
(USE COPPER CONDUCTOR ONLY).  
4
5
LS  
2. FOR 208 VOLT TRANSFORMER OPERATION  
MOVE BLACK WIRE FROM TERMINAL  
TERMINAL ON TRANSFORMER.  
ALS  
RS  
THERMOSTAT  
FIELD WIRING  
3
TO  
IIC  
3
6
GV  
2
3. FOR DIFFERENT THAN FACTORY SPEED TAP.  
CHANGE COOLING SPEED AT COOL  
TERMINAL. CHANGE HEATING SPEED AT  
HEAT TERMINAL ON CONTROL BOARD  
3 SPEED MOTOR  
PS  
NO ECONOMIZER  
8
ECON  
W
G
WH  
GR  
RD  
W
G
R
9
7
10  
12  
11  
LPS  
HPS  
C
NOTE  
RD - LOW SPEED  
BL - MED. SPEED  
BK - HIGH SPEED  
R
Y1  
Y/Y2  
C
YL  
BL  
6
5
2
4
1
Y
C
4. ACCESSORY ECONOMIZER PLUG ADJACENT  
TO BLOWER HOUSING IN RETURN AIR  
COMPARTMENT. REMOVE MALE PLUG AND  
ATTACH FEMALE PLUG TO ECONOMIZER  
ACCESSORY.  
4
3
R
G
W
Y1  
Y2  
C
PLF  
TB1  
TO THERMOSTAT  
TERMINAL BLOCK  
STAT  
TB1  
5. USE COPPER CONDUCTORS ONLY.  
USE NEC CLASS 2 WIRE.  
WITH ECONOMIZER OPTION  
W
G
WH  
GR  
RD  
W
G
R
Y
INSTALLER/SERVICEMAN  
THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO  
TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS:  
6. PURPLE WIRE CONNECTS TO TRANSFORMER  
(PIN 1).  
R
7. SPEED TAP TERMINATIONS SHOWN ON  
DIAGRAM ARE REPRESENTATIVE, BUT ACTUAL  
FACTORY SETTING MAY BE DIFFERENT BASED  
ON HEATING VALUE AND CAPACITY OF UNIT.  
EQUIP. STATUS  
CHECK  
STATUS LIGHT  
ON  
YL  
Y1  
Y/Y2  
C
NORMAL OPERATION  
-
NO POWER OR  
INTERNAL CONTROL  
FAULT  
CHECK INPUT POWER  
CHECK FUSE ON CONTROL  
REPLACE CONTROL  
OFF  
BL  
8. TO RUN DIFFERENT SPEED FOR HEATING AND  
C
COOLING, DISCONNECT GEEEN JUMPER FROM  
"COOL" TERMINAL AND REPLACE WITH  
APPROPRIATE SPEED TAP. THEN PLACE  
DISCONNECTED END OF JUMPER ON  
"UNUSED" TERMINAL LEFT OPEN BY MOVING  
THE SPEED TAP.  
9. FOR LOW STAGE OPERATION ONLY, REMOVE  
WHITE JUMPER. FOR 2 STAGE OPERATION,  
REMOVE JUMPER AND CONNECT W2 TO W1  
ON THERMOSTAT.  
IGNITION FAILURE  
OR  
OPEN ROLLOUT  
GAS FLOW  
GAS PRESSURE  
GAS VALVE  
1 BLINK  
STAT  
TB1  
SWITCH  
OR  
OPEN AUX. LIMIT  
SWITCH  
FLAME SENSOR  
FLAME ROLLOUT  
BAD SWITCH  
AUX. LIMIT OPEN  
CHECK  
PRESSURE SWITCH  
2 STAGE COOLING  
W
WH  
GR  
RD  
YL  
W
G
G
R
2 BLINKS  
3 BLINKS  
4 BLINKS  
PRESSURE SWITCH  
OPEN  
R
PRESSURE SWITCH CLOSED  
WITHOUT INDUCER ON  
CHECK  
PRESSURE SWITCH  
Y1  
Y/Y2  
C
Y1  
Y2  
C
PK  
BL  
SEE UNIT RATING PLATE FOR TYPE AND SIZE OF  
OVERCURRENT PROTECTION.  
OPEN LIMIT SWITCH  
MAIN LIMIT OPEN  
BAD SWITCH  
5 BLINKS  
6 BLINKS  
FALSE FLAME SENSED  
COMPRESSOR  
OUTPUT DELAY  
STICKING GAS VALVE  
3 MIN. COMP.  
ANTI-CYCLE TIMER  
STAT  
TB1  
208-240/3/60 0140L00507 REV B  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPG36-72  
Product SPecificationS  
Wiring diagram — cPg036-600904B/7B — cPg036*4B/7B — cPg072*4B/7B (460v/575v, Belt drive)  
RD  
YL  
RD  
BK  
PU  
BK  
GND  
T3 T2 T1  
T1  
L1  
T2  
L2  
T3  
L3  
BL  
BL  
YL  
COMP  
C
POWER SUPPLY  
BK  
BK  
BK  
OR  
PU  
BK  
460/3/60  
575/3/60  
SEE NOTE 4  
BR  
RD  
BK  
OR  
BK  
OR  
OR  
CM  
3
1
2
1
460  
575  
2
3
C
460/575  
TR  
240  
BL  
TR  
24V  
VMR  
RD WH  
LS  
RD  
RD  
BL  
GR  
EM  
BL  
BC GR  
PK  
S1  
S2  
BK  
RD  
BK  
RD  
SMOKE/FIRE  
DETECTOR  
REPLACES JUMPER  
WIRE  
TB1  
BR  
OR  
OR  
OR  
OR  
ALS  
PS  
BL  
ECON  
RD  
PU  
GR  
RD  
RD  
BL  
PU  
YL  
YL  
YL  
PU  
WH  
YL  
YL  
YL  
GR  
RD  
NOTE 2  
PLF  
RS  
RD  
YL  
3
2
1
6
5
4
OR  
WH  
BR  
IIC  
BL  
PU  
RD  
BL  
BL  
YL/PK  
SEE  
NOTE 3  
YL  
PU  
W. R.  
GAS VALVE  
(ALT.) HONEYWELL  
GAS VALVE  
GR  
WH  
BL  
GR  
MV  
PU  
RD  
BL  
GR  
YL  
Y
BL  
C
BR  
GV  
BK  
GV  
MV  
BL  
Y1  
W
W2 G  
R
LPS  
WH  
BL  
WH  
BR  
SEE  
NOTE 5  
TO THERMOSTAT  
RD  
VM  
FS  
HPS  
BL/PK  
IGN  
OR  
BK  
RD  
BR  
FC  
COMPONENT LEGEND  
L1  
L1  
SUPPLY VOLTAGE  
208-240/3/60  
L2  
L2  
L3  
L3  
FACTORY WIRING  
ALS  
COMP  
CM  
C
AUXILIARY LIMIT SWITCH  
COMPRESSOR  
CONDENSER MOTOR  
CONTACTOR  
LINE VOLTAGE  
LOW VOLTAGE  
OPTIONAL  
HIGH VOLTAGE  
C
T2  
C
T1  
T2  
EM  
F
FC  
EVAPORATOR MOTOR  
FUSE  
FAN CAPACITOR  
FLAME SENSOR  
EQUIPMENT GROUND  
GAS VALVE  
T1 COMP  
T3  
FIELD WIRING  
T3  
C
FS  
HIGH VOLTAGE  
LOW VOLTAGE  
FC  
GND  
GV  
HPS  
CM  
HIGH PRESSURE SWITCH  
WIRE CODE  
IIC  
INTEGRATED IGNITION CONTROL  
IGNITOR  
LIMIT SWITCH  
HEAT  
PCB  
BK BLACK  
BL BLUE  
IGN  
LS  
LPS  
FC  
EM  
BR BROWN  
GR GREEN  
LOW PRESSURE SWITCH  
PCB  
PLF  
PS  
RS  
FEMALE PLUG/CONNECTOR  
PRESSURE SWITCH  
ROLLOUT SWITCH  
VM  
DI  
LI  
COOL  
OR ORANGE  
PK PINK  
PU PURPLE  
SEE NOTE 2  
2
3
1
TB1  
TR  
VM  
VMR  
BC  
TERMINAL BLOCK (24V SIGNAL)  
TRANSFORMER  
VENT MOTOR  
VENT MOTOR RELAY  
BLOWER CAPACITOR  
RD RED  
WH WHITE  
YL YELLOW  
TR  
TB1  
FS  
IIC  
IGN  
BL/PK BLUE WITH PINK STRIP  
YL/PK YELLOW WITH PINK STRIP  
FS  
F
NOTES  
1. REPLACEMENT WIRE MUST BE THE SAME  
SIZE AND TYPE OF INSULATION AS ORIGINAL.  
(USE COPPER CONDUCTOR ONLY).  
4
5
LS  
2. FOR 208 VOLT TRANSFORMER OPERATION  
MOVE BLACK WIRE FROM TERMINAL  
TERMINAL ON TRANSFORMER.  
ALS  
RS  
THERMOSTAT  
FIELD WIRING  
3
TO  
IIC  
3
6
GV  
2
3. FOR DIFFERENT THAN FACTORY SPEED TAP.  
CHANGE COOLING SPEED AT COOL  
TERMINAL. CHANGE HEATING SPEED AT  
HEAT TERMINAL ON CONTROL BOARD  
3 SPEED MOTOR  
PS  
NO ECONOMIZER  
8
ECON  
W
G
WH  
GR  
RD  
W
G
R
9
7
10  
12  
11  
LPS  
HPS  
C
NOTE  
RD - LOW SPEED  
BL - MED. SPEED  
BK - HIGH SPEED  
R
Y1  
Y/Y2  
C
YL  
BL  
6
5
2
4
Y
C
4. ACCESSORY ECONOMIZER PLUG ADJACENT  
TO BLOWER HOUSING IN RETURN AIR  
COMPARTMENT. REMOVE MALE PLUG AND  
ATTACH FEMALE PLUG TO ECONOMIZER  
ACCESSORY.  
4
3
1
R
G
W
Y1  
Y2  
C
PLF  
TB1  
TO THERMOSTAT  
TERMINAL BLOCK  
STAT  
TB1  
5. USE COPPER CONDUCTORS ONLY.  
USE NEC CLASS 2 WIRE.  
WITH ECONOMIZER OPTION  
W
G
WH  
GR  
RD  
W
G
R
Y
INSTALLER/SERVICEMAN  
THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO  
TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS:  
6. PURPLE WIRE CONNECTS TO TRANSFORMER  
(PIN 1).  
R
7. SPEED TAP TERMINATIONS SHOWN ON  
DIAGRAM ARE REPRESENTATIVE, BUT ACTUAL  
FACTORY SETTING MAY BE DIFFERENT BASED  
ON HEATING VALUE AND CAPACITY OF UNIT.  
EQUIP. STATUS  
CHECK  
STATUS LIGHT  
ON  
YL  
Y1  
Y/Y2  
C
NORMAL OPERATION  
-
NO POWER OR  
INTERNAL CONTROL  
FAULT  
CHECK INPUT POWER  
CHECK FUSE ON CONTROL  
REPLACE CONTROL  
OFF  
BL  
8. TO RUN DIFFERENT SPEED FOR HEATING AND  
COOLING, DISCONNECT GEEEN JUMPER FROM  
"COOL" TERMINAL AND REPLACE WITH  
APPROPRIATE SPEED TAP. THEN PLACE  
DISCONNECTED END OF JUMPER ON  
"UNUSED" TERMINAL LEFT OPEN BY MOVING  
THE SPEED TAP.  
9. FOR LOW STAGE OPERATION ONLY, REMOVE  
WHITE JUMPER. FOR 2 STAGE OPERATION,  
REMOVE JUMPER AND CONNECT W2 TO W1  
ON THERMOSTAT.  
C
IGNITION FAILURE  
OR  
OPEN ROLLOUT  
GAS FLOW  
GAS PRESSURE  
GAS VALVE  
1 BLINK  
STAT  
TB1  
SWITCH  
OR  
OPEN AUX. LIMIT  
SWITCH  
FLAME SENSOR  
FLAME ROLLOUT  
BAD SWITCH  
AUX. LIMIT OPEN  
CHECK  
PRESSURE SWITCH  
2 STAGE COOLING  
W
WH  
GR  
RD  
YL  
W
G
G
R
2 BLINKS  
3 BLINKS  
4 BLINKS  
PRESSURE SWITCH  
OPEN  
R
PRESSURE SWITCH CLOSED  
WITHOUT INDUCER ON  
CHECK  
PRESSURE SWITCH  
Y1  
Y/Y2  
C
Y1  
Y2  
C
PK  
BL  
SEE UNIT RATING PLATE FOR TYPE AND SIZE OF  
OVERCURRENT PROTECTION.  
OPEN LIMIT SWITCH  
MAIN LIMIT OPEN  
BAD SWITCH  
5 BLINKS  
6 BLINKS  
FALSE FLAME SENSED  
COMPRESSOR  
OUTPUT DELAY  
STICKING GAS VALVE  
3 MIN. COMP.  
ANTI-CYCLE TIMER  
STAT  
TB1  
208-240/3/60 0140L00507 REV B  
SS-CPG36-72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
35  
Product SPecificationS  
Wiring diagram cPg036/48/600903B cPg072*3B (three-PhaSe, Belt drive)  
RD  
YL  
RD  
BK  
PU  
BK  
GND  
T3 T2 T1  
T1  
L1  
T2  
L2  
T3  
L3  
BL  
YL  
COMP  
C
BL  
BK  
OR  
POWER SUPPLY  
208-240/3/60  
SEE NOTE 4  
PU  
BK  
BR  
BK  
BK  
BK  
RD  
RD  
CM  
BK  
3
2
1
C
2
208  
TR  
24V  
3
BL  
1
240  
BK  
VMR  
LS  
WH  
RD  
BL  
GR  
EM  
RD  
BL  
PK  
GR  
BC  
BK  
RD  
OR  
BK  
RD  
OR  
S1  
SMOKE/FIRE DETECTOR  
REPLACES JUMPER  
WIRE  
S2  
TB1  
BR  
OR  
BL  
OR  
ALS  
PS  
IIC  
ECON  
RD  
PU  
OR  
GR  
RD  
RD  
BL  
PU  
YL  
YL  
YL  
PU  
WH  
YL  
YL  
YL  
YL  
GR  
RD  
NOTE 2  
PLF  
RS  
RD  
YL  
3
2
1
6
5
4
WH  
BR  
BL  
PU  
RD  
BL  
BL  
RD  
WH  
YL/PK  
SEE  
NOTE 3  
YL  
PU  
W. R.  
GAS VALVE  
(ALT.) HONEYWELL  
GAS VALVE  
GR  
BL  
GR  
MV  
GV  
MV  
PU  
BL  
YL  
BL  
GR  
BR  
GV  
BL  
BR  
Y
Y1 C R W W2 G  
LPS  
HPS  
WH  
BL  
WH  
TO THERMOSTAT  
SEE NOTE 6  
VM  
RD  
OR  
FS  
BL/PK  
IGN  
BK  
RD  
BR  
FC  
COMPONENT LEGEND  
ALS  
AUXILIARY LIMIT SWITCH  
BC  
BLOWER CONTACTOR  
COMP COMPRESSOR  
L1  
L2  
L3  
SUPPLY VOLTAGE  
208-240/3/60  
FACTORY WIRING  
LINE VOLTAGE  
LOW VOLTAGE  
OPTIONAL  
HIGH VOLTAGE  
C
CM  
C
CONDENSER MOTOR  
CONTACTOR  
T2  
C
L2  
T2  
T1  
L1  
T1  
COMP  
EM  
F
EVAPORATOR MOTOR  
FUSE  
FAN CAPACITOR  
FLAME SENSOR  
EQUIPMENT GROUND  
GAS VALVE  
T3  
L3  
FIELD WIRING  
T3  
C
FC  
FS  
HIGH VOLTAGE  
LOW VOLTAGE  
FC  
CM  
GND  
GV  
BC  
WIRE CODE  
BC  
BC  
HPS  
IBR  
IIC  
IGN  
LPS  
LS  
HIGH PRESSURE SWITCH  
INDOOR BLOWER RELAY  
INTEGRATED IGNITION CONTROL  
IGNITOR  
LOW PRESSURE SWITCH  
LIMIT SWITCH  
FEMALE PLUG/CONNECTOR  
PRESSURE SWITCH  
ROLLOUT SWITCH  
TERMINAL BLOCK (24V SIGNAL)  
TRANSFORMER  
BK BLACK  
BL BLUE  
EM  
BR BROWN  
GR GREEN  
OR ORANGE  
3
1
VM  
VMR  
1
3
PK PINK  
PU PURPLE  
PLF  
PS  
TR  
NOTE 3  
F
NOTE 3  
L1  
L2  
RD RED  
RS  
TB1  
TR  
IGN  
IIC  
WH WHITE  
YL YELLOW  
BC  
FS  
D1  
FS  
H
C
BL/PK BLUE WITH PINK STRIP  
YL/PK YELLOW WITH PINK STRIP  
VM  
VMR  
VENT MOTOR  
VENT MOTOR RELAY  
4
5
VMR  
THERMOSTAT  
FIELD WIRING  
LS  
ALS  
NOTES  
RS  
NO ECONOMIZER  
3
6
GV  
1. REPLACEMENT WIRE MUST BE THE SAME  
SIZE AND TYPE OF INSULATION AS ORIGINAL.  
(USE COPPER CONDUCTOR ONLY).  
2. ACCESSORY ECONOMIZER PLUG ADJACENT  
TO BLOWER HOUSING IN RETURN AIR  
COMPARTMENT. REMOVE MALE PLUG AND  
ATTACH FEMALE PLUG TO THE ECONOMIZER  
ACCESSORY.  
IIC  
W
G
W
G
R
WH  
GR  
RD  
PS  
R
8
ECON  
Y1  
Y/Y2  
C
9
7
10  
12  
11  
YL  
BL  
Y
C
C
3. L1 AND L2 ON IIC CONTROL IS 24V INPUT.  
LPS  
HPS  
4. USE COPPER CONDUCTORS ONLY.  
USE NEC CLASS 2 WIRE.  
NOTE 2  
PLF  
STAT  
TB1  
6
5
4
WITH ECONOMIZER OPTION  
5. FOR 208 VOLT TRANSFORMER OPERATION,  
MOVE BLACK WIRE FROM TERMINAL 3 TO  
TERMINAL 2 ON TRANSFORMER.  
Y
Y2  
3
2
1
R
G
W
W2 Y1  
C
W
G
WH  
GR  
RD  
W
G
R
Y
TO THERMOSTAT  
6. FOR LOW STAGE OPERATION ONLY, REMOVE  
WHITE JUMPER. FOR 2 STAGE OPERATION,  
REMOVE JUMPER AND CONNECT W2 TO W2  
ON THERMOSTAT.  
R
YL  
Y1  
Y/Y2  
C
INSTALLER/SERVICEMAN  
THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO  
TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS:  
BL  
C
EQUIP. STATUS  
CHECK  
-
STATUS LIGHT  
STAT  
ON  
NORMAL OPERATION  
TB1  
NO POWER OR  
INTERNAL CONTROL  
CHECK INPUT POWER  
CHECK FUSE ON CONTROL  
REPLACE CONTROL  
OFF  
2 STAGE COOLING  
W
G
WH  
GR  
RD  
YL  
W
G
IGNITION FAILURE  
GAS FLOW  
GAS PRESSURE  
GAS VALVE  
1 BLINK  
OPEN ROLLOUT  
SWITCH  
R
R
FLAME SENSOR  
FLAME ROLLOUT  
BAD SWITCH  
AUX. LIMIT OPEN  
Y1  
Y/Y2  
C
Y1  
Y2  
C
OPEN AUX. LIMIT  
SWITCH  
PK  
BL  
PRESSURE SWITCH  
OPEN  
CHECK  
PRESSURE SWITCH  
2 BLINKS  
3 BLINKS  
4 BLINKS  
PRESSURE SWITCH CLOSED  
WITHOUT INDUCER ON  
CHECK  
PRESSURE SWITCH  
SEE UNIT RATING PLATE FOR TYPE AND SIZE OF OVER  
CURRENT PROTECTION  
STAT  
TB1  
OPEN LIMIT SWITCH  
MAIN LIMIT OPEN  
BAD SWITCH  
5 BLINKS  
6 BLINKS  
FALSE FLAME SENSED  
COMPRESSOR  
OUTPUT DELAY  
STICKING GAS VALVE  
3 MIN. COMP.  
ANTI-CYCLE TIMER  
208-240/3/60 0140L00981 REV B  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPG36-72  
Product SPecificationS  
Wiring diagram cPg036/480454B cPg072*4B/7B (460v/ 575v Belt drive)  
RD  
YL  
RD  
BK  
PU  
BK  
GND  
T3 T2 T1  
T1  
L1  
T2  
L2  
T3  
L3  
BL  
BL  
YL  
COMP  
C
POWER SUPPLY  
BK  
BK  
BK  
OR  
PU  
BK  
460/3/60  
575/3/60  
SEE NOTE 4  
BR  
RD  
BK  
OR  
BK  
OR  
C
OR  
CM  
3
1
2
460/575  
TR  
240  
BL  
460  
575  
TR  
24V  
VMR  
RD WH  
LS  
RD  
RD  
BL  
GR  
EM  
BL  
BC GR  
PK  
S1  
S2  
BK  
RD  
BK  
RD  
SMOKE/FIRE  
DETECTOR  
REPLACES JUMPER  
WIRE  
TB1  
BR  
OR  
OR  
OR  
OR  
ALS  
PS  
BL  
ECON  
RD  
PU  
GR  
RD  
RD  
BL  
PU  
YL  
YL  
YL  
PU  
WH  
YL  
YL  
YL  
GR  
RD  
NOTE 2  
PLF  
RS  
RD  
YL  
3
2
1
6
5
4
WH  
BR  
IIC  
BL  
PU  
RD  
BL  
BL  
OR  
YL/PK  
SEE  
NOTE 3  
YL  
PU  
W. R.  
GAS VALVE  
(ALT.) HONEYWELL  
GAS VALVE  
GR  
WH  
BL  
BL  
GR  
MV  
PU  
YL  
Y2  
BL RD  
GR  
GV  
GV  
MV  
BL  
C
R W1  
Y1  
G
LPS  
WH  
BL  
BK  
TO THERMOSTAT  
RD  
VM  
FS  
IGN  
HPS  
BL/PK  
OR  
BK  
BR  
F
C
RD  
FC  
SUPPLY VOLTAGE  
460-575/3/60  
T2  
COMPONENT LEGEND  
ALS  
AUXILLARY LIMIT SWITCH  
BC  
BLOWER CONTACTOR  
COMP COMPRESSOR  
L1  
L1  
L2  
L3  
C
FACTORY WIRING  
C
L2  
T2  
T1  
LINE VOLTAGE  
LOW VOLTAGE  
OPTIONAL HIGH  
VOLTAGE  
T1  
COMP  
T3  
L3  
CM  
C
CONDENSER MOTOR  
CONTACTOR  
T3  
C
FC  
CM  
BC  
BC  
EM  
F
FC  
EVAPORATOR MOTOR  
FUSE  
FAN CAPACITOR  
FIELD WIRING  
BC  
HIGH VOLTAGE  
LOW VOLTAGE  
FS  
FLAME SENSOR  
EQUIPMENT GROUND  
GAS VALVE  
HIGH PRESSURE SWITCH  
INDOOR BLOWER RELAY  
INTEGRATED IGNITION CONTROL  
IGNITOR  
EM  
GND  
GV  
HPS  
IBR  
IIC  
IGN  
LPS  
LS  
VMR  
WIRE CODE  
BK BLACK  
BL BLUE  
BR BROWN  
GR GREEN  
1
3
VM  
RD  
BK  
OR  
LOW PRESSURE SWITCH  
LIMIT SWITCH  
1
3
OR ORANGE  
PK PINK  
PLF  
PS  
RS  
TB1  
TR  
FEMALE PLUG/CONNECTOR  
PRESSURE SWITCH  
ROLLOUT SWITCH  
TERMINAL BLOCK (24V SIGNAL)  
TRANSFORMER  
TR  
NOTE 3  
F
NOTE 3  
PU PURPLE  
RD RED  
WH WHITE  
YL YELLOW  
BL/PK BLUE WITH PINK STRIP  
YL/PK YELLOW WITH PINK STRIP  
L1  
L2  
IGN  
FS  
IIC  
BC  
FS  
D1  
H
C
VM  
VMR  
VENT MOTOR  
VENT MOTOR RELAY  
4
5
VMR  
LS  
THERMOSTAT  
FIELD WIRING  
ALS  
PS  
NOTES  
RS  
NO ECONOMIZER  
3
6
8
GV  
1. REPLACEMENT WIRE MUST BE THE SAME  
SIZE AND TYPE OF INSULATION AS ORIGINAL.  
(USE COPPER CONDUCTOR ONLY).  
IIC  
W
G
W
G
R
WH  
GR  
RD  
2. ACCESSORY ECONOMIZER PLUG ADJACENT  
TO BLOWER HOUSING IN RETURN AIR  
COMPARTMENT. REMOVE MALE PLUG AND  
ATTACH FEMALE PLUG TO THE ECONOMIZER  
ACCESSORY.  
R
ECON  
Y1  
Y/Y2  
C
9
7
10  
12  
11  
YL  
BL  
Y
C
C
3. L1 AND L2 ON IIC CONTROL IS 24V INPUT.  
LPS  
HPS  
4. USE COPPER CONDUCTORS ONLY.  
USE NEC CLASS 2 WIRE.  
NOTE 2  
PLF  
STAT  
TB1  
6
3
5
2
4
WITH ECONOMIZER OPTION  
Y
Y2  
1
R
G
W
Y1  
C
W
G
WH  
GR  
RD  
W
G
R
Y
TO THERMOSTAT  
R
Y1  
Y/Y2  
C
YL  
INSTALLER/SERVICEMAN  
THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO  
TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS:  
BL  
C
EQUIP. STATUS  
CHECK  
STATUS LIGHT  
STAT  
ON  
NORMAL OPERATION  
-
TB1  
NO POWER OR  
INTERNAL CONTROL  
CHECK INPUT POWER  
CHECK FUSE ON CONTROL  
REPLACE CONTROL  
OFF  
2 STAGE COOLING  
W
G
WH  
GR  
RD  
YL  
W
G
IGNITION FAILURE  
GAS FLOW  
GAS PRESSURE  
GAS VALVE  
FLAME SENSOR  
FLAME ROLLOUT  
BAD SWITCH  
AUX. LIMIT OPEN  
CHECK  
PRESSURE SWITCH  
1 BLINK  
OPEN ROLLOUT  
SWITCH  
R
R
Y1  
Y/Y2  
C
Y1  
Y2  
C
OPEN AUX. LIMIT  
SWITCH  
PK  
BL  
SEE UNIT RATING PLATE FOR TYPE AND  
SIZE OF OVER CURRENT PROTECTION.  
PRESSURE SWITCH  
OPEN  
2 BLINKS  
3 BLINKS  
4 BLINKS  
PRESSURE SWITCH CLOSED  
WITHOUT INDUCER ON  
CHECK  
PRESSURE SWITCH  
STAT  
TB1  
OPEN LIMIT SWITCH  
MAIN LIMIT OPEN  
BAD SWITCH  
5 BLINKS  
6 BLINKS  
FALSE FLAME SENSED  
COMPRESSOR  
OUTPUT DELAY  
STICKING GAS VALVE  
3 MIN. COMP.  
ANTI-CYCLE TIMER  
460-575/3/60 0140L00871 REV B  
SS-CPG36-72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
37  
Product SPecificationS  
Wiring diagram cPg036/480453B (three-PhaSe, Belt drive)  
RD  
YL  
RD  
BK  
PU  
BK  
GND  
T3 T2 T1  
T1  
L1  
T2  
L2  
T3  
L3  
BL  
YL  
COMP  
C
BL  
BK  
OR  
POWER SUPPLY  
208-240/3/60  
SEE NOTE 4  
PU  
BK  
BR  
BK  
BK  
BK  
RD  
RD  
CM  
BK  
3
2
1
C
2
208  
TR  
24V  
3
BK  
BL  
1
240  
VMR  
LS  
WH  
RD  
BL  
GR  
EM  
RD  
BL  
PK  
S1  
S2  
GR  
BC  
BK  
RD  
OR  
BK  
RD  
OR  
SMOKE/FIRE DETECTOR  
REPLACES JUMPER  
WIRE  
TB1  
BR  
OR  
BL  
OR  
ALS  
PS  
IIC  
ECON  
RD  
PU  
OR  
GR  
RD  
RD  
BL  
PU  
YL  
YL  
YL  
PU  
WH  
YL  
YL  
YL  
YL  
GR  
RD  
NOTE 2  
PLF  
RS  
RD  
YL  
3
2
1
6
5
4
WH  
BR  
BL  
RD  
BL  
BL  
RD  
WH  
YL/PK  
PU  
SEE  
NOTE 3  
YL  
PU  
W. R.  
GAS VALVE  
(ALT.) HONEYWELL  
GAS VALVE  
GR  
BL  
GR  
MV  
GV  
MV  
PU  
BL  
BL  
YL  
BL  
GR  
GV  
Y2 Y1 C R W1  
TO THERMOSTAT  
G
LPS  
HPS  
WH  
BL  
VM  
RD  
OR  
FS  
BL/PK  
IGN  
BK  
F
C
RD  
BR  
FC  
COMPONENT LEGEND  
AUXILIARY LIMIT SWITCH  
BLOWER CONTACTOR  
COMP COMPRESSOR  
L1  
L2  
L3  
SUPPLY VOLTAGE  
208-240/3/60  
FACTORY WIRING  
ALS  
BC  
LINE VOLTAGE  
LOW VOLTAGE  
OPTIONAL  
C
CM  
C
CONDENSER MOTOR  
CONTACTOR  
T2  
HIGH VOLTAGE  
C
L2  
T2  
T1  
L1  
T1  
COMP  
EM  
F
EVAPORATOR MOTOR  
FUSE  
FAN CAPACITOR  
FLAME SENSOR  
EQUIPMENT GROUND  
GAS VALVE  
T3  
L3  
FIELD WIRING  
T3  
C
FC  
FS  
HIGH VOLTAGE  
LOW VOLTAGE  
FC  
CM  
GND  
GV  
BC  
WIRE CODE  
BC  
BC  
HPS  
IBR  
IIC  
HIGH PRESSURE SWITCH  
INDOOR BLOWER RELAY  
INTEGRATED IGNITION CONTROL  
IGNITOR  
LOW PRESSURE SWITCH  
LIMIT SWITCH  
FEMALE PLUG/CONNECTOR  
PRESSURE SWITCH  
ROLLOUT SWITCH  
TERMINAL BLOCK (24V SIGNAL)  
TRANSFORMER  
BK BLACK  
BL BLUE  
EM  
BR BROWN  
GR GREEN  
3
VM  
1
IGN  
LPS  
LS  
PLF  
PS  
VMR  
OR ORANGE  
1
3
PK PINK  
PU PURPLE  
TR  
NOTE 3  
F
NOTE 3  
L1  
L2  
RD RED  
RS  
TB1  
TR  
VM  
VMR  
IGN  
IIC  
WH WHITE  
YL YELLOW  
BC  
FS  
D1  
FS  
H
C
BL/PK BLUE WITH PINK STRIP  
YL/PK YELLOW WITH PINK STRIP  
VENT MOTOR  
VENT MOTOR RELAY  
4
5
VMR  
THERMOSTAT  
FIELD WIRING  
LS  
ALS  
RS  
NOTES  
NO ECONOMIZER  
3
6
8
GV  
1. REPLACEMENT WIRE MUST BE THE SAME  
SIZE AND TYPE OF INSULATION AS ORIGINAL.  
(USE COPPER CONDUCTOR ONLY).  
2. ACCESSORY ECONOMIZER PLUG ADJACENT  
TO BLOWER HOUSING IN RETURN AIR  
COMPARTMENT. REMOVE MALE PLUG AND  
ATTACH FEMALE PLUG TO THE ECONOMIZER  
ACCESSORY.  
IIC  
W
G
W
G
R
WH  
GR  
RD  
PS  
R
ECON  
Y1  
Y/Y2  
C
9
7
10  
12  
YL  
BL  
Y
C
11  
C
3. L1 AND L2 ON IIC CONTROL IS 24V INPUT.  
LPS  
HPS  
4. USE CCOPPER COONDUCTOORRS ONLY.  
USE NEC CLASS 2 WIRE.  
NOTE 2  
PLF  
STAT  
TB1  
6
5
4
1
WITH ECONOMIZER OPTION  
5. FOR 208 VOLT TRANSFORMER OPERATION,  
MOVE BLACK WIRE FROM TERMINAL  
TERMINAL ON TRANSFORMER.  
Y
Y2  
3
2
R
G
W
Y1  
C
3
TO  
W
G
WH  
GR  
RD  
W
G
R
Y
2
TO THERMOSTAT  
R
YL  
Y1  
Y/Y2  
C
INSTALLER/SERVICEMAN  
THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO  
TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS:  
BL  
C
EQUIP. STATUS  
CHECK  
-
STATUS LIGHT  
STAT  
ON  
NORMAL OPERATION  
TB1  
NO POWER OR  
INTERNAL CONTROL  
CHECK INPUT POWER  
CHECK FUSE ON CONTROL  
REPLACE CONTROL  
OFF  
2 STAGE COOLING  
W
G
WH  
GR  
RD  
YL  
W
G
IGNITION FAILURE  
GAS FLOW  
GAS PRESSURE  
GAS VALVE  
1 BLINK  
OPEN ROLLOUT  
SWITCH  
R
R
FLAME SENSOR  
FLAME ROLLOUT  
BAD SWITCH  
AUX. LIMIT OPEN  
Y1  
Y/Y2  
C
Y1  
Y2  
C
OPEN AUX. LIMIT  
SWITCH  
PK  
BL  
PRESSURE SWITCH  
OPEN  
CHECK  
PRESSURE SWITCH  
2 BLINKS  
3 BLINKS  
4 BLINKS  
PRESSURE SWITCH CLOSED  
WITHOUT INDUCER ON  
CHECK  
PRESSURE SWITCH  
SEE UNIT RATING PLATE FOR TYPE AND SIZE OF OVER  
CURRENT PROTECTION  
STAT  
TB1  
OPEN LIMIT SWITCH  
MAIN LIMIT OPEN  
BAD SWITCH  
5 BLINKS  
6 BLINKS  
FALSE FLAME SENSED  
COMPRESSOR  
OUTPUT DELAY  
STICKING GAS VALVE  
3 MIN. COMP.  
ANTI-CYCLE TIMER  
208-240/3/60 0140L00979 REV B  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPG36-72  
ProdUCt sPeCiFiCations  
aCCessories  
Fits  
Model Sizes  
Item #  
Description  
14CURB3672B  
25FD3672  
Roof Curb – 14" Tall  
3-6 tons  
3-6 tons  
3-6 tons  
3-6 tons  
3 tons  
25% Manual Fresh Air Damper  
25% Motorized Fresh Air Damper  
Horizontal Barometric Relief Damper  
Concentric Duct Kit  
25MFD3672  
BRD3672  
CDK36  
CDK4872  
Concentric Duct Kit  
4-6 tons  
3-6 tons  
3-6 tons  
3 tons  
DNECONGS3672B  
DNECONGS3672B-NR  
DNSQRRND36B  
DNSQRRND4872B  
DNBBS3672B  
GHRC-1  
Downflow Economizer  
Downflow Economizer w/o Barometric Relief  
Downflow Square-to-Round Adapter 16" Round  
Downflow Square-to-Round Adapter 18" Round  
Burglar Bar Sleeves Includes Supply & Return  
Hurricane Restraint Clip  
4-6 tons  
3-6 tons  
All Models  
3-5 tons  
6 tons  
HAILGD03  
Condenser Coil Hail Guard  
HAILGD04  
Condenser Coil Hail Guard  
HA-02  
High-Alꢀtude Kit  
All Models  
3-5 tons  
6 tons  
HSKT036B / 048B /0 60B  
HSKT072B  
High-Staꢀc Kits (230/460v)  
High-Staꢀc Kit (230/460v)  
HZECONGS3672B  
LAKT01  
Horizontal Economizer  
3-6 tons  
3-6 tons  
3-6 tons  
3 tons  
Low-Ambient Kit  
LPM-05  
LP Conversion Kit  
LPT-00A  
LP Conversion Kit for CPG036045 only  
Power Exhaust 208/230v CPX Unit  
Power Exhaust 460v CPX Unit  
PE36722B  
3-6 tons  
3-6 tons  
PE36724B  
SS-CPG36-72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
39  
ProdUCt sPeCiFiCations  
notes  
Goodman Manufacturing Company, L.P., reserves the right to discontinue, or change at any time, specifications or designs without  
notice or without incurring obligations. © 2011 • Goodman Manufacturing Company, L.P. Houston, Texas • Printed in the USA.  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SS-CPG36-72  

Edimax Technology Switch ES 5224RM+ User Manual
Everpure Water System MR 225 User Manual
Extron electronic Network Card CIA114F5 User Manual
FEIN Power Tools Trimmer BLs 35 User Manual
Fellowes Laminator L80 95 User Manual
Fluke Universal Remote Fluke 16 User Manual
Fostex Computer Drive EX12 User Manual
Fujitsu TV Cables FCN 086 User Manual
Garmin Cell Phone Cell Phone User Manual
Gateway Speaker System kas103 User Manual