| Generac Power Systems Portable Generator 004917 2 User Manual | 
| Installation and   Owner’s Manual   Liquid-cooled, Prepackaged   Standby Generators   Model Number   004917-2   27 kW NG, 30 kW LP Vapor   This manual should   remain with the unit.   Not intended for use in life-support applications.   ! ! DANGER   DEADLY EXHAUST FUMES. OUTDOOR INSTALLATION ONLY!!   Download from Www.Somanuals.com. All Manuals Search And Download.   Table of Contents   QUIETSOURCE   ™ Liquid-cooled 30 kW Generators   INTRODUCTION................................................IFC   Section 3 — OPERATION ................................12   3.1 Using a Standard “GTS” Transfer Switch............12   3.2 Control Console Components..............................13   3.3 Manual Transfer and Startup..............................14   3.4 Engine Governor Adjustments ............................14   3.5 Retransfer and Shutdown....................................14   3.6 Automatic Operation ..........................................15   3.7 Weekly Exercise Cycle..........................................15   Section 4 — MAINTENANCE ..........................15   SAFETY RULES....................................................2   Section 1 — GENERAL INFORMATION ............4   1.1 Generator..............................................................4   1.2 Transfer Switch ....................................................4   1.3 Automatic System Operation ................................4   1.4 Generator AC Connection Systems........................4   1.5 Main Circuit Breaker ............................................4   1.6 Generator Fuel System..........................................5   1.7 Engine Protective Devices......................................5   1.8 Unpacking ............................................................6   1.9 Lifting the Generator ............................................6   1.10 Specifications ........................................................7   1.11 Fuel Consumption ................................................7   1.12 Reconfiguring the Fuel System ..............................7   1.13 Torque Specifications............................................8   1.14 Engine Oil Recommendations ..............................8   1.15 Coolant Recommendations....................................8   1.16 Before Installation ................................................8   Section 2 — INSTALLATION ............................8   2.1 Standby Generator Installation ............................8   2.2 Generator Location................................................9   2.3 Generator Mounting and Support ........................9   2.4 Basic Standby Electric System..............................9   2.5 Emergency Circuit Isolation Method....................10   2.6 Total Circuit Isolation Method ............................10   2.7 Grounding the Generator ....................................10   2.8 Generator AC Neutral Connections......................10   2.9 Transfer Switch Start Signal Connections ..........10   2.10 Battery Installation..............................................11   2.11 Preparation Before Start-Up................................12   4.1 Maintenance Performed by Authorized   Service Facilities..................................................15   4.2 Cooling System....................................................16   4.3 Overload Protection for Engine DC   Electrical System ................................................16   4.4 Checking Fluid Levels ........................................16   4.5 Maintenance Owner/Operator   Can Perform........................................................16   4.6 Miscellaneous Maintenance ................................18   4.7 Scheduled Maintenance ......................................20   Section 5 — TROUBLESHOOTING ..................23   Section 6 — ELECTRICAL DATA ....................24   Section 7 — EXPLODED VIEWS AND   PARTS LISTS ..............................28   Section 8 — INSTALLATION DIAGRAM ..........44   Section 9 — NOTES ........................................45   Section 10 — WARRANTY .................Back Cover   ® Generac Power Systems, Inc.   1 Download from Www.Somanuals.com. All Manuals Search And Download.   IMPORTANT SAFETY INSTRUCTIONS   QUIETSOURCE   ™ Liquid-cooled 30 kW Generators   SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe   operation be copied and posted in potential hazard areas. Safety should be stressed to all   operators, potential operators, and service and repair technicians for this equipment.   ! ! ! SAVE THESE INSTRUCTIONS – This manual contains important instructions that should be   followed during installation and maintenance of the generator and batteries.   ! ! ! ! ! GENERAL HAZARDS   WARNING:   The engine exhaust from this product   contains chemicals known to the state   of California to cause cancer, birth   defects or other reproductive harm.   • For safety reasons, Generac recommends that this   equipment be installed, serviced and repaired by a   Generac Authorized Service Dealer or other compe-   tent, qualified electrician or installation technician   who is familiar with applicable codes, standards and   regulations. The operator also must comply with all   such codes, standards and regulations.   • Installation, operation, servicing and repair of this   (and related) equipment must always comply with   applicable codes, standards, laws and regulations.   Adhere strictly to local, state and national electrical   and building codes. Comply with regulations the   Occupational Safety and Health Administration   (OSHA) has established. Also, ensure that the gener-   ator is installed, operated and serviced in accordance   with the manufacturer’s instructions and recommen-   dations. Following installation, do nothing that might   render the unit unsafe or in noncompliance with the   aforementioned codes, standards, laws and regula-   tions.   • The engine exhaust fumes contain carbon monoxide   gas, which can be DEADLY. This dangerous gas, if   breathed in sufficient concentrations, can cause   unconsciousness or even death. For that reason, ade-   quate ventilation must be provided. Exhaust gases   must be piped safely away from any building or   enclosure that houses the generator to an area where   people, animals, etc., will not be harmed. This   exhaust system must be installed properly, in strict   compliance with applicable codes and standards.   • Keep hands, feet, clothing, etc., away from drive belts,   fans, and other moving or hot parts. Never remove   any drive belt or fan guard while the unit is operating.   • Adequate, unobstructed flow of cooling and ventilat-   ing air is critical to prevent buildup of explosive gases   and to ensure correct generator operation. Do not   alter the installation or permit even partial blockage   of ventilation provisions, as this can seriously affect   safe operation of the generator.   ! ! WARNING:   This product contains or emits chemicals   known to the state of California to cause   cancer, birth defects or other reproductive harm.   Study these SAFETY RULES carefully before installing,   operating or servicing this equipment. Become familiar   with this Owner’s Manual and with the unit. The gen-   erator can operate safely, efficiently and reliably only if   it is properly installed, operated and maintained. Many   accidents are caused by failing to follow simple and   fundamental rules or precautions.   Generac cannot possibly anticipate every possible cir-   cumstance that might involve a hazard. The warnings in   this manual, and on tags and decals affixed to the unit   are, therefore, not all-inclusive. If using a procedure,   work method or operating technique that Generac does   not specifically recommend, ensure that it is safe for   others. Also make sure the procedure, work method or   operating technique chosen does not render the genera-   tor unsafe.   DANGER   Despite the safe design of this generator,   ! operating this equipment imprudently, neglecting   its maintenance or being careless can cause   possible injury or death. Permit only responsible   and capable persons to install, operate or main-   tain this equipment.   Potentially lethal voltages are generated by these   machines. Ensure all steps are taken to render the   machine safe before attempting to work on the   generator.   • Keep the area around the generator clean and unclut-   tered. Remove any materials that could become haz-   ardous.   • When working on this equipment, remain alert at all   times. Never work on the equipment when physically   or mentally fatigued.   Parts of the generator are rotating and/or hot   during operation. Exercise care near running gen-   ! erators.   ® 2 Generac Power Systems, Inc.   Download from Www.Somanuals.com. All Manuals Search And Download.   IMPORTANT SAFETY INSTRUCTIONS   QUIETSOURCE   ™ Liquid-cooled 30 kW Generators   • Inspect the generator regularly, and promptly repair • Generators installed with an automatic transfer   or replace all worn, damaged or defective parts using   switch will crank and start automatically when NOR-   MAL (UTILITY) source voltage is removed or is below   an acceptable preset level. To prevent such automat-   ic start-up and possible injury to personnel, disable   the generator’s automatic start circuit (battery cables,   etc.) before working on or around the unit. Then,   place a “Do Not Operate” tag on the generator control   panel and on the transfer switch.   only factory-approved parts.   • Before performing any maintenance on the generator,   disconnect its battery cables to prevent accidental   start-up. Disconnect the cable from the battery post   indicated by a NEGATIVE, NEG or (–) first.   Reconnect that cable last.   • Never use the generator or any of its parts as a step.   Stepping on the unit can stress and break parts, and   may result in dangerous operating conditions from   leaking exhaust gases, fuel leakage, oil leakage, etc.   • In case of accident caused by electric shock, immedi-   ately shut down the source of electrical power. If this   is not possible, attempt to free the victim from the   live conductor. AVOID DIRECT CONTACT WITH   THE VICTIM. Use a nonconducting implement, such   as a dry rope or board, to free the victim from the live   conductor. If the victim is unconscious, apply first aid   and get immediate medical help.   • Never wear jewelry when working on this equipment.   Jewelry can conduct electricity resulting in electric   shock, or may get caught in moving components   causing injury.   ELECTRICAL HAZARDS   • All generators covered by this manual produce dan-   gerous electrical voltages and can cause fatal electrical   shock. Utility power delivers extremely high and dan-   gerous voltages to the transfer switch as well as the   standby generator. Avoid contact with bare wires, ter-   minals, connections, etc., on the generator as well as   the transfer switch, if applicable. Ensure all appropri-   ate covers, guards and barriers are in place before   operating the generator. If work must be done around   an operating unit, stand on an insulated, dry surface   to reduce shock hazard.   • Do not handle any kind of electrical device while   standing in water, while barefoot, or while hands or   feet are wet. DANGEROUS ELECTRICAL SHOCK   MAY RESULT.   • If people must stand on metal or concrete while   installing, operating, servicing, adjusting or repairing   this equipment, place insulative mats over a dry   wooden platform. Work on the equipment only while   standing on such insulative mats.   FIRE HAZARDS   • Keep a fire extinguisher near the generator at all   times. Do NOT use any carbon tetra-chloride type   extinguisher. Its fumes are toxic, and the liquid can   deteriorate wiring insulation. Keep the extinguisher   properly charged and be familiar with its use. If there   are any questions pertaining to fire extinguishers,   consult the local fire department.   EXPLOSION HAZARDS   • The National Electrical Code (NEC), Article 250   requires the frame and external electrically conduc-   tive parts of the generator to be connected to an   approved earth ground and/or grounding rods. This   grounding will help prevent dangerous electrical   shock that might be caused by a ground fault condi-   tion in the generator set or by static electricity. Never   disconnect the ground wire.   • Wire gauge sizes of electrical wiring, cables and cord   sets must be adequate to handle the maximum elec-   trical current (ampacity) to which they will be sub-   jected.   • Before installing or servicing this (and related) equip-   ment, make sure that all power voltage supplies are   positively turned off at their source. Failure to do so   will result in hazardous and possibly fatal electrical   shock.   • Connecting this unit to an electrical system normally   supplied by an electric utility shall be by means of a   transfer switch so as to isolate the generator electric   system from the electric utility distribution system   when the generator is operating. Failure to isolate the   two electric system power sources from each other by   such means will result in damage to the generator   and may also result in injury or death to utility power   workers due to backfeed of electrical energy.   • Properly ventilate any room or building housing the   generator to prevent build-up of explosive gas.   • Do not smoke around the generator. Wipe up any fuel   or oil spills immediately. Ensure that no combustible   materials are left in the generator compartment, or   on or near the generator, as FIRE or EXPLOSION   may result. Keep the area surrounding the generator   clean and free from debris.   • Generac generator sets may operate using one of sev-   eral types of fuels. All fuel types are potentially FLAM-   MABLE and/or EXPLOSIVE and should be handled   with care. Comply with all laws regulating the storage   and handling of fuels. Inspect the unit’s fuel system   frequently and correct any leaks immediately. Fuel   supply lines must be properly installed, purged and   leak tested according to applicable fuel-gas codes   before placing this equipment into service.   • Diesel fuels are highly FLAMMABLE. Gaseous fluids   such as natural gas and liquid propane (LP) gas are   extremely EXPLOSIVE. Natural gas is lighter than air,   and LP gas is heavier than air; install leak detectors   accordingly.   ® Generac Power Systems, Inc.   3 Download from Www.Somanuals.com. All Manuals Search And Download.   Section 1 - General Information   QUIETSOURCE   ™ Liquid-cooled 30 kW Generators   1.1 GENERATOR   1.3 AUTOMATIC SYSTEM OPERATION   When this generator, along with a transfer switch, has   been installed and interconnected, a circuit board in   the generator panel constantly monitors UTILITY   power source voltage. Should that voltage drop below   a preset value, and remain at such a low state for a   preset amount of time, the generator cranks and   starts. After the generator starts, the transfer switch   transfers load circuits so the generator can power   them.   This equipment is a liquid-cooled, engine-driven gen-   erator set. The generator is designed to supply elec-   trical power that operates critical electrical loads   during utility power failure. The unit has been facto-   ry-installed in a weather resistant, all aluminum   enclosure and is intended for outdoor installation   only. Use this generator as a source of electrical   power for the operation of 120 and/or 240VAC, sin-   gle-phase loads.   When utility source voltage has been restored, the   switch re-transfers back to the UTILITY source volt-   age and the generator then shuts down.   If this generator is used to power electrical   load circuits normally powered by a UTILITY   power source, it is required by code to install   Please reference the transfer switch manual for spe-   cific information.   ! a transfer switch. The transfer switch must   effectively isolate the electric system from the   utility distribution system when the generator   is operating (NEC 701). Failure to isolate an   electrical system by such means results in   damage to the generator and may also result   in injury or even death to utility power work-   ers due to backfeed of electrical energy.   1.4 GENERATOR AC CONNECTION   SYSTEMS   The generator was shipped from the factory with its   stator AC output leads connected in a single-phase,   three-wire generator AC connection system (Figure   1.1). The stator assembly in this system consists of a   pair of stationary windings, with two leads brought   out of each winding. Each single winding can supply   120VAC, 60 Hertz. When the two windings are con-   nected in series, a 240VAC, 60 Hertz AC output   results. Typically the two HOT leads in the circuit are   wires 11 and 44. The NEUTRAL leads are the junc-   tion of Wires 22 and 33. The NEUTRAL is not   grounded.   1.2 TRANSFER SWITCH   This generator system may include a matched auto-   matic transfer switch which is intended to be used in   conjunction with the Generac generator. It is supplied   in either a NEMA 1 enclosure or a NEMA 3R enclo-   sure. The NEMA 1 enclosure is intended for indoor   use only. The NEMA 3R enclosure is weather proof   and can be used indoors or outdoors. Follow these   rules:   Figure 1.1 - Generator AC Connection System   • Install the transfer switch on a firm, sturdy sup-   porting structure.   • To prevent switch distortion, level the switch if nec-   essary. This can be done by placing washers   between the switch enclosure and the mounting   surface.   • Never install the switch where water or any corro-   sive substance might drip onto the enclosure.   • Protect the switch at all times against excessive   moisture, dust, dirt, lint, construction grit and cor-   rosive vapors.   If a transfer switch is not included, one may be pur-   chased separately from a Generac Authorized Dealer.   1.5 MAIN CIRCUIT BREAKER   The generator’s main circuit breaker is included with   the unit as shipped from the factory. The breaker for   each unit is described in Figure 1.2.   Figure 1.2 - Main Circuit Breaker   Model   004917-0   Rating   27,000 NG   30,000 LP   Phase   Actual Current   112.5   C/B Rating*   Circuit Breaker   150A QN2   1 1 150   150   125.0   150A QN2   * Amp Rating of C/B structured under model.   ® 4 Generac Power Systems, Inc.   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 1 - General Information   QUIETSOURCE   ™ Liquid-cooled 30 kW Generators   NOTE:   1.6 GENERATOR FUEL SYSTEM   The unit has been factory tested and adjusted using a   natural gas fuel system. If propane (LP) gas is neces-   sary. Refer to Section 1.11, Fuel Consumption.   The Low Oil Pressure, High Coolant Temperature   and Low Coolant Level are not monitored for the   first 10 seconds of engine run time.   Fuel pressure for a natural gas set up should be five   inches to 14 inches of water column (0.18 to 0.5   psi) at all load ranges.   Figure 1.4 - Low Oil Pressure Switch   Fuel pressure for an LP vapor set up should be 11   inches to 14 inches of water column (0.4 to 0.5   psi) at all load ranges.   NOTE:   A seperate gas line and regulator may be needed   to assure proper gas pressure to the generator.   Improper gas pressure can cause hard starting and   affect engine durability.   Gaseous fuels such as natural and LP (propane)   gas are highly explosive. Even the slightest   spark can ignite such fuels and cause an explo-   sion. No leakage of fuel is permitted. Natural   gas, which is lighter than air, tends to collect in   high areas. LP gas is heavier than air and tends   to settle in low areas.   1.7.2 HIGH COOLANT TEMPERATURE   SWITCH    This normally open (N.O.) thermostatic switch has   sensing tip which is immersed in captive coolant.   Should coolant temperature exceed about 230°F   (110°C), the switch contacts close. This causes the   engine to shut down automatically and turns on the   high coolant temperature/low coolant level LED   (Figure 1.5).   1.7 ENGINE PROTECTIVE DEVICES   The engine has several safety switches which cause   the engine to automatically shut down under the fol-   lowing conditions: low oil pressure, high coolant tem-   perature, engine overspeed, low coolant level or over-   crank (Figure 1.3).   Figure 1.5- High Coolant Temperature Switch   Figure 1.3 - Engine Protective Devices   LOW COOLANT   LEVEL SWITCH   LOW OIL   PRESURE   SWITCH   HIGH   COOLANT   TEMPERATURE   SWITCH   1.7.3 LOW COOLANT LEVEL SWITCH    Should engine coolant level drop below the level of   the high coolant temperature switch, it is possible for   the engine to overheat without automatic shutdown.   To prevent such overheating without automatic shut   down, the engine has a low coolant level sensor. If the   engine coolant drops too low, the engine automatical-   ly shuts down and turns on the high coolant temper-   ature/low coolant level LED (Figure 1.6 on page 6).   1.7.1 LOW OIL PRESSURE SWITCH    This switch is normally-closed (N.C.), but is held   open by engine oil pressure during engine running.   Should operating oil pressure drop below about 8-10   psi (55-68 kPa), the switch contacts close, the engine   shuts down automatically, and the low oil pressure   LED is turned ON (Figure 1.4).   ® Generac Power Systems, Inc.   5 Download from Www.Somanuals.com. All Manuals Search And Download.   Section 1 — General Information   QUIETSOURCE   ™ Liquid-cooled 30 kW Generators   Figure 1.6 - Low Coolant Level Sensor   1.7.7 LOW BATTERY    The engine control board continually monitors the   battery voltage and turns on the low battery LED if   the battery voltage falls below 11.0 VDC for one   minute. Low battery voltage is a non-latching alarm,   which will automatically clear if the battery voltage   rises above 11.0 VDC.   The control system will not attempt to start the   engine if there is a low battery condition, however, if   the engine is already running when the low battery   condition occurs, the engine will continue to run as   long as possible.   1.7.4 OVERSPEED SHUTDOWN    Battery voltage is NOT monitored during the crank   cycle.   The engine control board receives AC frequency sig-   nals from an engine run winding in the alternator.   Should AC frequency exceed about 72 Hertz for three   seconds or 75 Hertz instantaniously, the engine shuts   down and the overspeed LED turns on. Should AC   frequency exceed about 72 Hertz, circuit board action   will automatically shutdown the engine (Figure 1.7).   1.7.8 ALARM RESET    If the engine control board shuts down the generator   for any of the above reasons, the engine remains   stopped until the alarm is cleared by placing the   AUTO/OFF/MANUAL switch into the OFF position.   Figure 1.7 - Printed Circuit Board Assembly   1.7.9 DC FUSE    These fuses are located on the front panel of the con-   trol system. They protect the panel wiring and com-   ponents from damaging overload. Always remove the   15 amp main fuse before working on the generator.   The unit will not start or crank if this fuse is blown.   Replace the fuse with one of the same size, type, and   rating (main AGC-15, battery charger AG4).   R44   LED1   C27   Q2   C9   J2   C26   U7   C4   D10   C21   C30   C2   1.8 UNPACKING   RL1   RL2   R1   R48   D17   1.8.1 UNPACKING PRECAUTIONS    R49   Handle shipping cartons and crates with care. Use   care to avoid damage from dropping, bumping, colli-   sion, etc. Store and unpack cartons with the proper   side up, as noted on the shipping carton.   U1   J1   L3   D19   . R E V 9 0 6 E 0 4 B #    1.8.2 INSPECTION   1.7.5 RPM SENSOR LOSS    After unpacking, carefully inspect the generator for   any damage that may have occurred during ship-   ment. If loss or damage is noted at the time of deliv-   ery, have the person(s) making delivery note all dam-   age on the freight bill or affix their signature under   the consignor’s memo of loss or damage.   If the engine control board does not receive a proper   rpm signal from the starter during cranking or run-   ning, it shuts down the engine on rpm sensor loss   and flash the overspeed LED.   1.7.6 OVERCRANK SHUTDOWN    The engine control board uses a cyclic cranking   process when attempting to start the engine. The first   crank cycle is a 15-second crank followed by a seven-   second rest. This is followed by five more crank   cycles each with a seven second crank followed by a   seven second rest.   1.9 LIFTING THE GENERATOR   When lifting or hoisting equipment is used,   be careful not to touch overhead power lines.   The generators weight of more than 900   ! If the engine fails to start after all six attempts, the   start attempt is stopped and the overcrank LED   turned on.   pounds requires proper tools, equipment, and   qualified personnel to be used in all phases of   handling and unpacking.   ® 6 Generac Power Systems, Inc.   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 1 — General Information   QUIETSOURCE   ™ Liquid-cooled 30 kW Generators   NOTE:   1.10 SPECIFICATIONS   Fuel consumption is given at rated maximum con-   tinuous power output when using natural gas rated   at 1000 Btu per cubic foot. LP gas is rated at 2520   Btu per cubic foot. Actual fuel consumption   obtained may vary depending on such variables as   applied load, ambient temperature, engine condi-   tions and other environmental factors.   1.10.1 GENERATOR SPECIFICATIONS    Single-phase   4917-0   27 (NG), 30 (LP)   Model   Rated Max. Cont.   AC Power Output (kW)   Rated voltage (volts)   No. of Rotor Poles   Driven Speed of Rotor   Fuel pressure for a natural gas set up should be five   inches to 14 inches of water column (0.18 to 0.5   psi) at all load ranges.   120/240   4 1800   Fuel pressure for an LP vapor set up should be 11   inches to 14 inches of water column (0.4 to 0.5   psi) at all load ranges.   Rotor Excitation System Direct excited brush type   Type of Stator   4 Wire   Class F/H   Rotor/Stator Insulation   1.12 RECONFIGURING THE FUEL   1.10.2 ENGINE SPECIFICATIONS    SYSTEM   Make ......................................................................................Ford   Displacement ..................................................................3.0 liters   Cylinder Arrangement ..............................................................V-6   Valve Arrangement ..............................................Overhead Valve   Firing Order ................................................................1-4-2-5-3-6   Number of Main Bearings............................................................4   Compression Ratio............................................................9.3 to 1   No. of Teeth on Flywheel ........................................................164   Ignition Timing at 1800 rpm..............................30 degrees BTDC   Spark Plug Gap ..................................................0.035-0.045 inch   Recommended Spark Plugs   NOTE:   All models are configured for natural gas from the   factory.   To reconfigure the fuel system from NG to LP vapor,   follow these steps:   1. Turn the main gas supply off.   2. Remove the carburetor fuel hose from the outlet   port (Port 1) of the demand regulator (Figure 1.8).   3. Remove the brass hose fitting from the outlet port   (Port 1) of the demand regulator.   4. Remove pipe plug from Port 2.   Motor Craft..........................................................AG, SF 32PGM   Oil Pressure....................................................................40-50 psi   Crankcase Oil Capacity........................5.0 U.S. quarts (4.7 liters)   Recommended Engine Oil..........................................SAE 5W-20   Type of Cooling System ..................Pressurized, closed recovery   Cooling Fan ..............................................................Pusher Type   Cooling System Capacity..................3.0 U.S. gallons (11.4 liters)   5. Install brass hose fitting into Port 2.   6. Install pipe plug into Port 1.   7. Connect carburetor gas hose to brass fitting.   8. Tighten all clamps and plugs.   9. Make sure fuel supply is of the proper pressure   and type for configuration.   10. Reverse the procedure to convert back to natural   gas.   Recommended Coolant............................Use a 50-50 mixture of   ethylene glycol base   Figure 1.8 — Reconfigure the Fuel System   and de-ionized water.   Port 1   Port 2   FUEL HOSE   FUEL HOSE   1.11 FUEL CONSUMPTION   BRASS HOSE   FITTING   BRASS HOSE   FITTING   Natural Gas:   PLUG   PLUG   OUT   PORT 1   OUT   PORT 2   % of Load   m3/hr   25%   3.1   50%   5.9   75%   8.5   100%   11.0   HOUSING   PORTS   HOUSING   PORTS   ft3/hr   110.3   209.0   299.5   387.0   LP Vapor:   % of Load   m3/hr   25%   1.3   50%   2.4   75%   3.5   100%   4.5   ft3/hr   45.6   86.4   123.8   160.0   NG FUEL SYSTEM   LP FUEL SYSTEM   ® Generac Power Systems, Inc.   7 Download from Www.Somanuals.com. All Manuals Search And Download.   Section 2 — Installation   QUIETSOURCE   ™ Liquid-cooled 30 kW Generators   NOTE:   Port 1 is for NG only and Port 2 is for LP vapor   only. No provision for dual fuel has been made.   Do not use any chromate base rust inhibitor   with ethylene glycol base anti-freeze or   chromiumhydroxide (“green slime”) forms and   will cause overheating. Engines that have   been operated with a chromate base rust   inhibitor must be chemically cleaned before   adding ethylene glycol base anti-freeze. Using   any high silicate anti-freeze boosters or addi-   tives will also cause overheating. It is also rec-   ommend that any soluble oil inhibitor is NOT   USED for this equipment.   ! DANGER   Serious injury or damage may occur if not   configured properly. Please consult an author-   ized Generac Service Dealer with any ques-   ! tions.   1.13 TORQUE SPECIFICATIONS   Cylinder Head ............................................15 (+ 90° + 90°) ft.lb.   Intake Manifold ................................................................13 ft.lb.   Exhaust Manifold..............................................................13 ft.lb.   1.16 BEFORE INSTALLATION   Before installing this equipment, check the ratings of   both the generator and the transfer switch. Read   “Emergency Isolation Method” and “Total Circuit   Isolation Method” in the installation manual (Part No.   079699).   1.14 ENGINE OIL RECOMMENDATIONS   The unit has been filled with 5W-20 engine oil at the   factory. Use a high-quality detergent oil classified “For   Service CC, SD, SE, SF.” Detergent oils keep the   engine cleaner and reduce carbon deposits. Use oil   having the following SAE viscosity rating, based on   the ambient temperature range anticipated before the   next oil change:   The generator’s rated wattage/amperage capacity   must be adequate to handle all electrical loads that   the unit will power. The critical (essential) loads may   need to be grouped together and wired into a sepa-   rate “emergency” distribution panel.   Temperature   Above 80° F (27° C)   32° to 80° F (-1° to 27° C)   Below 32° F (0° C)   Oil Grade (Recommended)   SAE 5W-20   This generator can be installed in conjunction with a   standard Generac “GTS” type transfer switch, if nec-   essary.   SAE 5W-20   SAE 5W-20   The standard transfer switch has no sensing or con-   trolling circuit boards. Instead, the generator control   console houses a “Printed Circuit Board Assembly”,   which controls all phases of operation, including   engine start up and load transfer.   NOTE:   5W-30 full synthetic oil is highly recommended in   any element with temperatures above 90°F or   below 30°F.   2.1 STANDBY GENERATOR   INSTALLATION   Any attempt to crank or start the engine   before it has been properly serviced with the   recommended oil may result in an engine fail-   DANGER   ! Connecting this generator to an electrical sys-   tem normally supplied by an electric utility   shall be by means of a transfer switch, so as to   isolate the electric system from the utility distri-   bution system when the generator is operating.   Failure to isolate the electric system by these   means will result in damage to the generator   and may also result in injury or death to utility   workers due to backfeed of electrical energy.   ure.   1.15 COOLANT RECOMMENDATIONS   Use a mixture of half low silicate ethylene glycol base   anti-freeze and half de-ionized water. Cooling system   capacity is about 12 U.S. quarts (11.4 liters). Use   only de-ionized water and only low silicate anti-   freeze. If desired, add a high quality rust inhibitor to   the recommended coolant mixture. When adding   coolant, always add the recommended 50-50 mix-   ture.   If an open bottom is used, the engine-genera-   tor is to be installed over non-combustible   materials and should be located such that com-   bustible materials are not capable of accumu-   lating under the generator set.   ® 8 Generac Power Systems, Inc.   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 2 — Installation   QUIETSOURCE   ™ Liquid-cooled 30 kW Generators   Only qualified, competent installation contractors or   2.2 GENERATOR LOCATION   electricians thoroughly familiar with applicable   codes, standards and regulations should install this   standby electric power system. The installation must   comply strictly with all codes, standards and regula-   tions pertaining to the installation.   Install the generator set, in its protective enclosure   outdoors, where adequate cooling and ventilating air   always is available. Consider these factors:   • Install the unit where air inlet and outlet openings   will not become obstructed by leaves, grass, snow,   etc. If prevailing winds will cause blowing or drift-   ing, consider using a windbreak to protect the unit.   • Install the generator on high ground where water   levels will not rise and endanger it.   • This genset must be installed on a level surface.   The base frame must be level within 1/2 inch all   around.   • Allow sufficient room on all sides of the generator   for maintenance and servicing. A good rule is to   allow five feet of space on all sides.   • Where strong prevailing winds blow from one   direction, face the generator air inlet openings into   the prevailing winds.   After the system has been installed, do nothing   that might render the installation in noncompli-   ance with such codes, standards and regulations.   ! NOTE:   For more information about the installation of a   standby system, order Engine-Generator Standby   Electric Power Systems Installer’s Guide and   Reference Manual (part #046622) from the   Generac Authorized Service Dealer.   2.1.1 NFPA STANDARDS    The following published standards booklets pertain-   ing to standby electric systems are available form the   National Fire Protection Association (NFPA),   Batterymarch Park, Quincy, MA 02269:   • Install the generator as close as possible to the   transfer switch. This reduces the length of wiring   and conduit.   • Install the generator as close as possible to the fuel   supply, to reduce the length of piping. HOWEVER,   REMEMBER THAT LAWS OR CODES MAY REG-   ULATE THE DISTANCE.   • NFPA No. 37, STATIONARY COMBUSTION   ENGINES AND GAS TURBINES.   • NFPA No. 76A, ESSENTIAL ELECTRICAL SYS-   TEMS FOR HEALTH CARE FACILITIES.   • NFPA No. 220, STANDARD TYPES OF BUILDING   CONSTRUCTION   • NFPA No. 68, GUIDE FOR EXPLOSION VENTING   • NFPA No. 70, NATIONAL ELECTRICAL CODE.   • NFPA No. 30, FLAMMABLE AND COMBUSTIBLE   LIQUIDS CODE.   2.3 GENERATOR MOUNTING AND   SUPPORT   Retain the generator compartment to a concrete slab   with 1/4-inch masonry type anchor bolts. Be sure the   bolts are long enough to retain the compartment. The   slab should be at least six inches thick and should   extend beyond the enclosure to a distance of at least   three inches on all sides. See Section 6 for generator   major dimensions.   • NFPA No. 10, INSTALLATION, MAINTENANCE AND   USE OF PORTABLE FIRE EXTINGUISHERS.   2.1.2 OTHER PUBLISHED STANDARDS   In addition to NFPA standards, the following infor-   mation pertaining to the installation and use of   standby electric systems is available:    2.4 BASIC STANDBY ELECTRIC   SYSTEM   Figure 2.1 shows a schematic diagram of a basic   standby electric system. Both the UTILITY power   supply and the STANDBY (GENERATOR) output are   connected to an approved transfer switch. The trans-   fer switch is required by electrical code and serves   the following functions:   • Article X, NATIONAL BUILDING CODE, available   from the American Insurance Association, 85 John   Street, New York, N.Y. 10038.   • AGRICULTURAL WIRING HANDBOOK, obtainable   from the Food and Energy Council, 909 University   Avenue, Columbia, MO, 65201.   • ASAE EP-364.2, INSTALLATION AND MAINTE-   NANCE OF FARM STANDBY ELECTRIC POWER,   available from the American Society of Agricultural   Engineers, 2950 Niles Road, St. Joseph, MI 49085.   • A52.1, AMERICAN NATIONAL STANDARD FOR   CHIMNEYS, FIREPLACES AND VENTING SYS-   TEMS, available from the American National   Standard Institute, 1430 Broadway, New York, N.Y.   10018.   • Allows the LOAD circuits to be connected to only   one power supply at a time.   • Prevents electrical backfeed between the generator   and the UTILITY power circuits.   Both the STANDBY and the UTILITY power supplies   to the transfer switch are protected against overload   by a main line circuit breaker.   ® Generac Power Systems, Inc.   9 Download from Www.Somanuals.com. All Manuals Search And Download.   Section 2 — Installation   QUIETSOURCE   ™ Liquid-cooled 30 kW Generators   Figure 2.1 – Basic Standby Electric System   2.7 GROUNDING THE GENERATOR   The National Electrical Code requires the frame and   external electrically conductive parts of this equip-   ment to be properly connected to an approved earth   ground and/or grounding rods. For that purpose, a   GROUND LUG (Figure 2.2) is provided on the gener-   ator mounting base. Consult a qualified electrician   for grounding requirements in the area. Grounding   procedures must meet local regulations.   DANGER   Do not connect the ground wire to any pipe   that carries a flammable or explosive substance   – FIRE or an EXPLOSION may result.   Proper grounding helps protect personnel against   electrical shock in the event of a ground fault condi-   tion in the generator or in connected electrical   devices. In addition, grounding helps dissipate static   electricity that often builds up in ungrounded   devices.   2.5 EMERGENCY CIRCUIT ISOLATION   METHOD   This prevents overloading the generator by keeping   electrical loads below the wattage/amperage capacity   of the generator. If the generator is powering only crit-   ical loads, within the wattage/amperage capacity, dur-   ing utility power outages, consider using the emer-   gency circuit isolation method.   Figure 2.2 – Generator Grounding Lug (typical)   Critical electrical loads are grouped together and   wired into a separate “Emergency Distribution   Panel.” Load circuits powered by that panel are with-   in the wattage/amperage capacity of the generator set.   When this method is used, it is difficult to overload   the generator. The transfer switch must meet the fol-   lowing requirements:   GROUNDING   LUG   • It must have an ampere rating equal to the total   amperage rating of the emergency distribution   panel circuit.   • Have it installed between the building’s main dis-   tribution panel and the emergency distribution   panel.   2.8 GENERATOR AC NEUTRAL   CONNECTIONS   Generac uses an UNGROUNDED AC neutral.   Grounding is recommended only at the main service   entrance. If the neutral wire is grounded and one of   the phase loads becomes grounded, the excessive   current opens the load circuit breaker or collapses   the generator field. The actual result depends on the   electrical characteristics of the particular installed   generator.   2.6 TOTAL CIRCUIT ISOLATION   METHOD   When a generator capable of powering all electrical   loads in the circuit is to be installed, use the “Total   Circuit Isolation Method.” It is possible for the gener-   ator to be overloaded when this isolation method is   employed. The following apply to the transfer switch   in this type of system.   2.9 TRANSFER SWITCH SIGNAL   CONNECTIONS   • Ampere rating of the transfer switch must equal   the ampere rating of the normal incoming utility   service.   • The transfer switch is installed between the utility   service entrance and the building distribution   panel.    2.9.1 PRE-PACKAGED ATS   If the generator is to be installed with a pre-packaged   transfer switch, it is necessary to connect the control   wires to the generator and set position two of the   four-position dip switch to OFF.   ® 10 Generac Power Systems, Inc.   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 2 — Installation   QUIETSOURCE   ™ Liquid-cooled 30 kW Generators   Setting switch two to OFF allows the control PCB to   perform the ATS control functions.   Battery electrolyte fluid is an extremely caustic   sulfuric acid solution that can cause severe   ! burns. Do not permit fluid to contact eyes, skin,   clothing, painted surfaces, etc. Wear protective   goggles, protective clothing and gloves when   handling a battery. If fluid is spilled, flush the   affected area immediately with clear water.   Control system interconnections consist of N1 and   N2, and leads 23 and 194. Control system intercon-   nection leads must be run in a conduit that is sepa-   rate from the AC power leads. Recommended wire   gauge sizes for this wiring depends on the length of   the wire, as recommended below:   MAXIMUM WIRE LENGTH   RECOMMENDED WIRE   SIZE   Do not dispose of the battery in a fire. The bat-   tery is capable of exploding.   460 feet (140m)   No. 18 AWG.   No. 16 AWG.   No. 14 AWG.   No. 12 AWG.   461 to 730 feet (223m)   731 to 1,160 feet (354m)   1,161 to 1,850 feet (565m)   Do not open or mutilate the battery. Released   electrolyte can be toxic and harmful to the skin   and eyes.   ! The battery represents a risk of high short circuit   current. When working on the battery, always   remove watches, rings or other metal objects,   and only use tools that have insulated handles.    2.9.2 GTS-TYPE ATS   If the generator is to be installed with an automatic   transfer switch, such as a Generac GTS-type switch,   it is necessary to connect the two-wire start control   system.   2.10.1 VENTED BATTERIES    Connect the two-wire start signal from the automatic   transfer switch to the automatic start connection,   which is located in the middle, on the bottom, inside   the control panel. Match wires 178 and 183 in the   transfer switch to 178 and 183 on the terminal strip   in the control panel. The conductors for the two-wire   start circuit must be in their own conduit. (See   Section 3.1 for further explanation.)   The electrolyte is a dilute sulfuric acid that is   harmful to the skin and eyes. It is electrically   conductive and corrosive. The following proce-   dures are to be observed:   ! • Wear full eye protection and protective clothing,   • Where electrolyte contacts the skin, wash it off   immediately with water,   • Where electrolyte contacts the eyes, flush thor-   oughly and immediately with water and seek med-   ical attention, and   2.10 BATTERY INSTALLATION   DANGER   • Spilled electrolyte is to be washed down with an   acid-neutralizing agent. A common practice is to   use a solution of one pound (500 grams) bicarbon-   ate of soda to one gallon (4 liters) of water. The   bicarbonate of soda solution is to be added until   the evidence of reaction (foaming) has ceased. The   resulting liquid is to be flushed with water and the   area dried.   Standby generators installed with automatic   transfer switches will crank and start automati-   ! cally when NORMAL (UTILITY) source voltage is   removed or is below an acceptable preset level.   To prevent such automatic start-up and possible   injury to personnel, do not connect battery   cables until certain that normal source voltage   at the transfer switch is correct and the system   is ready to be placed into operation.   Lead acid batteries present a risk of fire   because they generate hydrogen gas. The fol-   lowing procedure are to be followed:   Storage batteries give off explosive hydrogen   gas. This gas can form an explosive mixture   around the battery for several hours after   charging. The slightest spark can ignite the gas   and cause an explosion. Such an explosion can   shatter the battery and cause blindness or   other injury. Any area that houses a storage   battery must be properly ventilated. Do not   allow smoking, open flame, sparks or any spark   producing tools or equipment near the battery.   • DO NOT SMOKE when near batteries,   • DO NOT cause flame or spark in battery area, and   • Discharge static electricity from body before touch-   ing batteries by first touching a grounded metal   surface.   Servicing of batteries is to be performed or super-   vised by personnel knowledgeable of batteries and   the required precautions. Keep unauthorized person-   nel away from batteries.   The recommended battery is Group 26, 12VDC, 550   CCA/75 AH minimum. All batteries must be at 100   percent state-of-charge before they are installed on   the generator.   ® Generac Power Systems, Inc. 11   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 3 — Operation   QUIETSOURCE   ™ Liquid-cooled 30 kW Generators   When using maintenance-free batteries, it is not nec-   essary to check the specific gravity or electrolyte level.   Have these procedures performed at the intervals   specified in Section 4, “Maintenance.” A negative   ground system is used. Battery connections are   shown on the wiring diagrams. Make sure all batter-   ies are correctly connected and terminals are tight.   Observe battery polarity when connecting batteries to   the generator set.    2.11.4 GENERATOR SET LUBRICATION   Check the engine crankcase oil level before operating   and add oil to the proper level – the dipstick “FULL”   mark. Never operate the engine with the oil level   below the dipstick “ADD” mark. See “Specifications”   (Section 1.10) and “Engine Oil Recommendations”   (Section 1.14).   NOTE:   NOTE:   This engine is shipped from the manufacturer   with 5W-20 oil. This oil should be changed after   30 hours of operation.   Damage will result if the battery connections are   made in reverse.   2.11 PREPARATION BEFORE START-UP   The instructions in this section assume that the stand-   by generator has been properly installed, serviced,   tested, adjusted and otherwise prepared for use by a   competent, qualified installation contractor. Be sure to   read the “Safety Rules” on Pages 2 and 3, as well as all   other safety information in this manual, before   attempting to operate this (and related) equipment.    2.11.5 ENGINE COOLANT   Have the engine cooling system properly filled with   the recommended coolant mixture. Check the system   for leaks and other problems. See “Specifications”   (Section 1.10) and “Coolant” (Section 1.15).    2.11.6 BELT TENSION   2.11.1 PRIOR TO INITIAL START-UP    Check the engine fan belt tension and condition prior   to placing the unit into service and at recommended   intervals. Belt tension is correct when a force of   approximately 22 pounds (10 kg), applied midway   between pulleys, deflects the belt about 3/8- to 5/8-   inch (10 to 16 mm).   Prior to initially starting the generator, it must   be properly prepared for use. Any attempt to   crank or start the engine before it has been   properly serviced with the recommended types   and quantities of engine fluids (oil, coolant,   fuel, etc.) may result in an engine failure.   !  2.11.7 ELECTRICAL SYSTEM   Make sure the generator is properly connected to an   approved earth ground and/or ground rod.   Before starting the generator for the first time, the   installer must complete the following procedures. For   follow-up maintenance information and/or service   intervals, please refer to Section 4, “Maintenance.”   Make sure the generator battery is fully charged,   properly installed and interconnected, and ready for   use.   Check to ensure that there are no loose electrical con-   nections. Restrain any loose wires to keep them clear   of any moving generator set components.    2.11.2 TRANSFER SWITCH   If this generator is used to supply power to any elec-   trical system normally powered by an electric utility,   the National Electrical Code requires that a transfer   switch be installed. The transfer switch prevents elec-   trical backfeed between two different electrical sys-   tems (for additional information, see the applicable   transfer switch manual for this unit). The transfer   switch, as well as the generator and other standby   components, must be properly located and mounted   in strict compliance with applicable codes, standards   and regulations.   3.1 USING A STANDARD “GTS”   TRANSFER SWITCH   When required, the pre-packaged standby generator   can be installed with an engineered Generac “GTS”   type automatic transfer switch.   In this application, the GTS is responsible for utility   sensing, weekly exercising, and load transferring.   Position two of the four-position dip switch is used to   turn over this control to the GTS.    2.11.3 FUEL SYSTEM   Make sure the fuel supply system to the generator (a)   delivers the correct fuel at the correct pressure and   (b) is properly purged and leak tested according to   code. No fuel leakage is permitted. See   “Specifications” (Section 1.10) for more information.   Pos2 ON — GTS Application   • The control board will NOT monitor utility.   • The control board will NOT perform a weekly exer-   cise. (The five red LEDs will not flash in this   mode.)   ® 12 Generac Power Systems, Inc.   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 3 - Operation   QUIETSOURCE   ™ Liquid-cooled 30 kW Generators   • The control board will NOT activate the transfer   3.2.1 AUTO/OFF/MANUAL SWITCH   Use this three-position switch as follows:    output.   • The control board WILL monitor all engine condi-   tions and shut down on all the faults listed in this   document.   • Set the switch to AUTO for fully automatic opera-   tion. See “Automatic Operation” (Section 3.5).   • Set switch to MANUAL position to crank and start   the generator engine.   • Set switch to OFF position to shut down an oper-   ating engine. With OFF selected, operation will not   be possible.   Pos2 OFF — ATS Application   • The control board will perform all of the automat-   ic features listed in this document.   • The two-wire start connections should NOT be   used.   DANGER   GTS Mode Operation   When in GTS mode, the control board will respond   as follows based on the AUTO/OFF/MANUAL switch   position.   With switch set to AUTO, engine can crank   and start suddenly without warning. Such   automatic start up normally occurs when utili-   ty source voltage drops below a pre-set level.   To prevent possible injury that might be   caused by such sudden starts, set   ! OFF — The generator will not start and run in this   position.   MANUAL — The control board will start and run the   generator whenever the switch is in the manual posi-   tion.   AUTO/OFF/MANUAL switch to OFF before   working on or around the unit. Then, place a   “DO NOT OPERATE” tag on control console.   AUTO — The control board will monitor the two-wire   start circuit. When a two-wire start is issued the con-   trol board will immediately start and run the genera-   tor. Whe the two-wire start is removed the control   board will immediately stop the generator.   3.2.2 FAULT INDICATOR LED   This LED goes ON when one or more of the following   engine faults occurs and when engine shuts down.    • Low Oil Pressure   • Overcrank   NOTE:   • Low Battery   If the generator is installed in conjunction with an   engineered GTS type transfer switch, refer to the   applicable transfer switch manual for exact oper-   ating parameters and timing sequences.   • Overspeed/RPM Sensor Loss   • High Coolant Temperature/Low Coolant Level   See Section 1.7 for further explanation of engine pro-   tection functions.   3.2 CONTROL CONSOLE   3.2.3 15 AMP FUSE    COMPONENTS   This fuse protects the control console’s DC control   circuit against electrical overload. If the fuse has   melted open because of an overload, engine cranking   and startup cannot occur. If the fuse needs to be   replaced, use only an identical 15-amp replacement   fuse. (Type AGC)   The components of a home standby generator control   console (Figure 3.1) are as follows:   Figure 3.1 - Home Standby Generator Panel   LED INDICATORS:   FLASHING GREEN LED   = NO UTILITY SENSE   5 FLASHING RED LED'S   = EXERCISER NOT SET   (IN AUTO MODE ONLY) SOLID GREEN LED   RED LED'S INDIVIDUAL FAULT   = SYSTEM READY, UTILITY POWER ON   = 3.2.4 4 AMP INLINE FUSE   This fuse protects the battery charger against electri-   cal overload. If the fuse needs to be replaced, use only   an identical 4 amp replacement fuse (type AG).    (SEE OWNER'S MANUAL FOR COMPLETE LED DETAILS)   OVER CRANK   RED LED   E E U U AUTO   OFF   OFF   ON   SET   EXECISER   TIME   NOTE:   SET   EXERCISE   TIME   MANUAL   GREEN LED   TO SET EXERCISER TIME   1) PLACE AUTO/OFF/MANUAL SWITCH TO AUTO POSITION.   This fuse will not remove the + battery input   power from the PCB when it opens. This means   the exercise timer will not be reset.   0E7194   SWITCH   AUTO/OFF/MANUAL   SWITCH   3.2.5 SET EXERCISE TIME SWITCH    4A FUSE   This switch allows programming the generator to   start and exercise automatically. “See Weekly   Exercise Cycle.”   BATTERY   CHARGER   15A FUSE   MAIN   POWER   ® Generac Power Systems, Inc. 13   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 3 — Operation   QUIETSOURCE   ™ Liquid-cooled 30 kW Generators   6. Adjust differential pot to make the recovery to   3.2.6 SYSTEM READY LED    load changes even faster and minimize load   change undershoot and overshoot. If it is set too   high it may introduce oscillations at some load. It   can be set to zero (full CCW) if a small amount   causes oscillations at some load.   The System Ready LED (green) has two main pro-   poses. First, the LED will be ON when the   AUTO/OFF/MANUAL switch is in the AUTO position,   utility is present, and there are no system alarms.   This ON state indicates the system is fully ready for   automatic operation.   Figure 3.2 — Engine Governor Adjustment   The system ready LED will be OFF when the switch   is in the manual or OFF positions.   R44   LED1   C27   Q2   C9   J2   The system ready LED is also used to indicate the   presence of utility sensing at the PCB when the switch   is either in the AUTO or MANUAL modes. The LED   will flash at the rate of 1/2 second on, 1/2 second off   if the utility sensing level is below the transfer back   threshold.   C26   U7   C4   D10   C21   C30   This secondary function is only available with dip   switch two in the OFF position (standard ATS appli-   cation).   C2   RL1   RL2   R1   R48   D17   R49   3.3 MANUAL TRANSFER AND   U1   START-UP   J1   L3   To transfer electrical loads to the Standby (EMER-   GENCY) power source side and start the engine man-   ually, refer to the Owner’s Manual of the particular   transfer switch.   D19   0 DIP SWITCH   DIFFERENTIAL   STABILITY   POSITION 1   50/60 HZ   POSITION 2   GTS/ATS Select   ON = GTS   1 3 2 4 UNUSED   ON = 50 HZ   GTS/ATS   OFF = ATS (standard mode)   OFF = 60 HZ   50/60 HZ   3.4 ENGINE GOVERNOR   ADJUSTMENTS   Engine speed governing is also controlled by the   engine control board. Connector J2 on the engine   control board interfaces with a governor driver mod-   ule and the Bosch throttle body. The engine governor   has been set by the factory during final testing of the   generator and, in most cases, should not be adjusted.   3.5 RETRANSFER AND SHUTDOWN   When utility power source voltage has been restored,   electrical loads may be transferred back to that   source and the generator can be shut down as follows:   • Verify that utility power supply voltage to the trans-   fer switch has been positively turned OFF, using   whatever means provided (such as utility main line   circuit breaker).   If, however, adjustments are necessary, or a new   engine control board is installed in the generator, the   following procedure should be followed (Figure 3.2):   • Set the generator’s main circuit breaker to its OFF   1. Set all three potentiometers (pots) fully counter-   clockwise.   2. Under no load condition, increase the GAIN pot   as much as possible without causeing instability.   3. Apply 1/4, 1/2, 3/4 and full load to the unit.   Decrease the GAIN pot if there is instability at any   load point.   4. Under full load condition, increase the stability   pot until the unit returns to 60 Hertz (or 50 Hertz   in 50 Hertz applications).   5. Reduce load to 3/4, 1/2, 1/4 and no load.   Decrease the stability pot if there is instability at   any load point.   or OPEN position.   • Let the generator engine run at no-load for a few   minutes, to stabilize internal unit temperatures.   • On the generator console, set the AUTO/OFF/   MANUAL switch to OFF. Wait for engine to come to   a complete stop.   • For transfer to UTILITY position, refer to the   Owner’s Manual of the particular transfer switch.   • Turn on the utility power supply to the transfer   switch, using whatever means provided (such as a   utility main line circuit breaker). The utility power   source now powers the loads.   ® 14 Generac Power Systems, Inc.   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 4 — Maintenance   QUIETSOURCE   ™ Liquid-cooled 30 kW Generators   Figure 3.2 - “Set Exercise” Switch   3.6 AUTOMATIC OPERATION   To set the system for fully automatic operation, pro-   ceed as follows:   • Check that load circuits are connected to the   utility power supply.   FUSE   FUSE   4A   BAT.   CHARGER   15A   MAIN   • Set the AUTO/OFF/MANUAL switch to its AUTO   position.   • Set the generator main circuit breaker to its ON or   CLOSED position.   AUTO   OFF   OFF   ON   3.7 WEEKLY EXERCISE CYCLE   The engine control board will start and run the gen-   erator once every seven days for approximately 12   minutes. If utility should fail during this exercise   period, the engine control board will transfer the load   to the generator output and continue to run until util-   ity returns.   SET   EXERCISE   TIME   MANUAL   On the day, and at the time of day chosen for the gen-   erator to exercise, set the weekly exercise cycle as fol-   lows:   4.1 MAINTENANCE PERFORMED BY   AUTHORIZED SERVICE FACILITIES   1. Place the AUTO/OFF/MANUAL switch in the   AUTO position.   A. EVERY THREE MONTHS   2. Press and hold the “Set Exercise” switch for three   1. Check battery state of charge and condition.   2. Inspect and test fuel system.   3. Check transfer switch.   4. Inspect exhaust system.   5. Check engine ignition system.   6. Check fan belts.   seconds, then release.   At this time all five red LEDs will flash for approxi-   mately 10 seconds, then the engine will start and run   for it’s 12 minute exercise period, then shut down.   The generator will now start and run each week at the   same time.   If DC power to the control board is lost, the weekly   exercise setting will be lost. This is indicated by all   five red LEDs continually flashing. In this state the   generator will still start and run in manual mode, or   automatically start and run if UTILITY is lost while in   Auto mode, but it will not perform a weekly exercise   cycle.   B. ONCE EVERY SIX MONTHS   1. Test Engine Safety Devices (low oil pressure, low   coolant level, high coolant temperature).   C. ONCE ANNUALLY   1. Test engine governor. Adjust or repair, if needed.   2. Clean, inspect generator.   If a failure occurs while running in this mode, the five   red LEDs will stop flashing, the individual fault LED   will turn on and the engine will shut down. Once the   AUTO/OFF/MANUAL switch has been switch to OFF,   the individual fault LED will turn OFF and the five   red LEDs will begin flashing to show exercise has still   not been set.   3. Flush cooling system.   D. FIRST 100 OPERATING HOURS   1. Change engine oil and oil filter. (After initial   change, service engine oil and filter at 150 oper-   ating hours or 6 months, whichever comes first.)   2. Retorque cylinder head. (See Torque Specs,   Section 1.13.)   3. Retorque intake and exhaust manifold. (See   Torque Specs, Section 1.13.)   E. EVERY 500 OPERATING HOURS   1. Service air cleaner.   2. Check starter.   3. Check engine DC alternator.   ® Generac Power Systems, Inc. 15   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 4 — Maintenance   QUIETSOURCE   ™ Liquid-cooled 30 kW Generators   Figure 4.1 - Oil Dipstick and Oil Fill Cap   4.2 COOLING SYSTEM   Air intake and outlet openings in the generator com-   partment must be open and unobstructed for contin-   ued proper operation. This includes such obstruc-   tions as high grass, weeds, brush, leaves and snow.   OIL   DIPSTICK   Without sufficient cooling and ventilating air flow, the   engine/generator quickly overheats, which causes it   to shut down. (See Section 6 for installation drawings   and vent locations.)   OIL   FILL   The exhaust system parts from this product get   extremely hot and remain hot after shutdown.   High grass, weeds, brush, leaves, etc. must   remain clear of the exhaust. Such materials may   ignite and burn from the heat of the exhaust   system.   4.4.2 BATTERY FLUID    Check battery electrolyte fluid at least once weekly.   Fluid should cover separators in all battery cells. If   fluid level is low, add distilled water to cover tops of   separators. DO NOT USE TAP WATER IN BATTERY.   4.3 OVERLOAD PROTECTION FOR   ENGINE DC ELECTRICAL SYSTEM   Engine cranking, start up and running are controlled   by a solid state Engine Controller circuit board.   Battery voltage is delivered to that circuit board via a   15 amp fuse. These overcurrent protection devices   will open if the circuit is overloaded.   4.4.3 ENGINE COOLANT   Check coolant level in coolant recovery bottle. See   Specifications, Section 1.10.    • Add recommended coolant mixture as necessary.   • Periodically remove radiator pressure cap to make   sure the coolant recovery system is functioning   properly. Coolant should be at bottom of radiator   filler neck. If coolant level is low, inspect gasket in   radiator pressure cap. Replace cap, if necessary.   To have pressure cap tested, contact an authorized   Generac Service Dealer. Inspect cooling system   and coolant recovery system for leaks.   If a circuit breaker opens or a fuse element   melts, find the cause of the overload before   resetting the circuit breaker or replacing the   ! fuse.   4.4 CHECKING FLUID LEVELS   4.4.1 CHECK ENGINE OIL   Check engine crankcase oil level (Figure 4.1) at least   every 20 hours of operation, or prior to use.    4.5 MAINTENANCE OWNER/   OPERATOR CAN PERFORM   • Remove oil dipstick and wipe dry with a clean,   lint-free cloth.   4.5.1 CHECK ENGINE OIL LEVEL   Refer to “Checking Fluid Levels” in Section 4.4.    • Install oil dipstick, then remove again.   • Oil should be between FULL and ADD marks.   • If oil level is below the dipstick ADD mark, remove   oil fill cap. Add the recommended oil to bring oil   level up to the FULL mark. DO NOT FILL ABOVE   THE “FULL” MARK. See Section 1.14 for recom-   mended oils.   4.5.2 CHECK BATTERY   • Check battery fluid level each week as outlined   under “Check Fluid Levels”.   • Check battery cables for condition, tightness, cor-   rosion or damage. Clean, tighten or replace as   necessary.    4.5.3 EXERCISE SYSTEM    Start the generator engine at least once every seven   days and let it run at least 20 minutes. See Section   3.6, “Weekly Exercise Cycle”.   ® 16 Generac Power Systems, Inc.   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 4 — Maintenance   QUIETSOURCE   ™ Liquid-cooled 30 kW Generators   4.5.4 INSPECT COOLING SYSTEM   4.5.10 CHANGING ENGINE OIL     • Inspect engine cooling system at least once each   month.   • Check hoses for damage, deterioration, leaks, etc.   Correct any discrepancies found.   • Check hose clamps for tightness.   Refer to maintenance performed by authorized serv-   ice facilities for engine oil and filter change frequen-   cies.   Drain the oil while the engine is still warm from run-   ning. This means warm up the engine, shut it down   and drain immediately as follows:   4.5.5 CHECK ENGINE COOLANT LEVEL    1. Remove OIL DRAIN HOSE from its retaining clip.   2. Loosen and remove OIL DRAIN HOSE CAP. Drain   oil completely into suitable container.   3. When all oil has drained, install and tighten OIL   DRAIN HOSE CAP, and re-install into its retaining   clip.   See “Checking Fluid Levels” in Section 4.4.   4.5.6 PERFORM VISUAL INSPECTION    Complete a thorough visual inspection of the entire   engine-generator monthly. Look for obvious damage,   loose, missing or corroded nuts, bolts and other fas-   teners. Look for fuel, oil or coolant leaks.   4. Turn OIL FILTER (Figure 4.2) counterclockwise   and remove. Dispose of old filter.   5. Apply light coating of new engine oil to seal of new   oil filter. Install FILTER and tighten by hand only.   DO NOT OVERTIGHTEN.   6. Remove OIL FILL CAP. Add recommended oil (see   SPECIFICATIONS). DO NOT FILL ABOVE THE   DIPSTICK “FULL” MARK. Crankcase oil capacity   is 4.0 U.S. quarts (3.8 liters).   4.5.7 INSPECT EXHAUST SYSTEM    Inspect the exhaust system at least once every three   months. Check all exhaust system pipes, mufflers,   clamps, etc. for condition, tightness, leaks, security,   damage.   4.5.8 CHECK FAN BELT    • Inspect fan belts every three months. Replace any   damaged, deteriorated, worn or otherwise defec-   tive belt.   • Check fan belt tension. Thumb pressure, exerted   midway between pulleys, should deflect about 3/8   to 5/8 inch. Adjust belt tension as required.   After refilling the crankcase with oil, always   check oil level on dipstick. NEVER OPERATE   ENGINE WITH OIL BELOW THE DIPSTICK   ! “ADD” MARK.   7. Start engine and check for oil leaks.   Figure 4.2 - Oil Filter   4.5.9 INSPECT ENGINE GOVERNOR    Visually inspect electronic governor.   DANGER   Do not attempt to adjust the governor. Only   qualified service facilities should adjust the   governor. Excessively high operating speeds   ! are dangerous and increase the risk of person-   al injury. Low speeds impose a heavy load on   the engine when adequate engine power is   not available and may shorten engine life.   Correct rated frequency and voltage are sup-   plied only at the proper governed speed.   Some connected electrical load devices may   be damaged by incorrect frequency and/or   voltage. Only qualified service technicians   should adjust the governed speed.   4.5.11 CHANGING THE ENGINE AIR CLEANER    To replace the engine air cleaner, (part number   059402), remove the air cleaner cover and replace   the air filter making sure it is positioned properly   before reattaching the cover (Figure 4.3).   ® Generac Power Systems, Inc. 17   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 4 — Maintenance   QUIETSOURCE   ™ Liquid-cooled 30 kW Generators   Figure 4.3 – Engine Air Cleaner   4.6 MISCELLANEOUS MAINTENANCE   4.6.1 CLEANING THE GENERATOR    Keep the generator as clean and as dry as possible.   Dirt and moisture that accumulates on internal gen-   erator windings have an adverse effect on insulation   resistance.   Periodically clean generator exterior surfaces. A soft   brush may be used to loosen caked on dirt. Use a   vacuum system or dry, low pressure air to remove   any accumulations of dirt. The generator is housed   inside an all-weather enclosure, clean the enclosure   with a soft, damp cloth or sponge and water.   Once each year, have the generator cleaned and   inspected by an Authorized Service Dealer. That deal-   er will use dry, low pressure air to clean internal   windings. Parts inside the control console should be   cleaned and inspected at this time as well.   See the “Service Schedule,” Section 6, for air cleaner   maintenance.   4.5.12 SPARK PLUGS   Reset the spark plug gap or replace the spark plugs   as necessary. See Section 6.    Finally, have the insulation resistance of stator and   rotor windings checked. If insulation resistances are   excessively low, the generator may require drying.   1. Clean the area around the base of the spark plugs   to keep dirt and debris out of the engine. Clean by   scraping or washing using a wire brush and com-   mercial solvent. Do not blast the spark plugs to   clean.   2. Remove the spark plugs and check the condition.   Replace the spark plugs if worn or if reuse is   questionable. See the “Service Schedule,” Section   6, for recommended inspection.   4.6.2 BATTERY    All lead-acid storage batteries discharge when not in   use. Refer to specific instructions and warnings that   accompany the battery. If such information is not   available, observe the following precautions when   handling a battery:   • DO NOT use jumper cables and a booster battery   to crank or start the generator engine.   3. Check the spark plug gap using a wire feeler   gauge. Adjust the gap to 0.5-0.6 mm (0.020-0.025   inch) by carefully bending the ground electrode   (Figure 4.4).   • DO NOT recharge a weak battery while it is   installed in the generator. Remove battery from   generator and recharge in a well-ventilated area,   away from fuel vapors, sparks, heat or flames.   • Battery electrolyte fluid is an extremely caustic   sulfuric solution that can cause severe burns. DO   NOT permit fluid to contact eyes, skin, clothing,   painted surfaces, wiring insulation, etc. If any bat-   tery fluid is spilled, flush the affected area with   clear water immediately.   Figure 4.4 – Setting the Spark Plug Gap   SET PLUG GAP AT 0.5-0.6 mm   (0.020-0.025 inch)   • Always wear safety glasses, rubber apron and   gloves when handling a battery.   • Batteries give off explosive hydrogen gas while   charging. The gas can form an explosive mixture   around the battery for several hours after charging.   Any spark, heat or flames can ignite the gas and   cause an explosion which can shatter the battery,   causing blindness or other serious injury.   4.5.13 COOLANT CHANGE    Every year, have Authorized Service Facility drain,   flush and refill the cooling system. See SPECIFICA-   TIONS (Section 1.10) for cooling system recommen-   dations.   ® 18 Generac Power Systems, Inc.   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 4 — Maintenance   QUIETSOURCE   ™ Liquid-cooled 30 kW Generators   4.6.3 BATTERY MAINTENANCE    The battery should be inspected per the “Service   Schedule,” Section 6. The following procedure   should be followed for inspection:   Be sure the AUTO/OFF/MANUAL switch is set to   the OFF position before connecting the battery   cables. If the switch is set to AUTO or MANUAL,   the generator can crank and start as soon as   the battery cables are connected.   ! 1. Inspect the battery posts and cables for tightness   and corrosion. Tighten and clean as necessary.   2. Check the battery fluid level of unsealed batteries   and, if necessary, fill with DISTILLED WATER   ONLY. DO NOT USE TAP WATER IN BATTERIES.   3. Have the state of charge and condition checked.   This should be done with an automotive-type bat-   tery hydrometer.   Be sure the UTILITY power supply is turned off,   or sparking may occur at the battery posts as   the cables are attached and cause an explosion.   4.6.4 BATTERY REPLACEMENT   When replacing batteries, use the same number and   the type of battery that follows:    DANGER   BCI Group No.   26/26R   CCA   525 @ 0 deg. F   Storage batteries give off explosive hydrogen   gas. This gas can form an explosive mixture   around the battery for several hours after   charging. The slightest spark can ignite the gas   and cause an explosion. Such an explosion can   shatter the battery and cause blindness or   other injury. Any area that houses a storage   battery must be properly ventilated. Do not   allow smoking, open flame, sparks or any spark   producing tools or equipment near the battery.   27   600 @ 0 deg. F   NOTE:   The BCI number should be located directly   on the battery.   PERIODIC REPLACEMENT PARTS   Part Name   Generac’s Part Number   Oil Filter   # 0E7180   # 046627   # 0C8127   # 0E7079   Radiator Cap   Air Cleaner   Spark Plug   Battery electrolyte fluid is an extremely caustic   sulfuric acid solution that can cause severe   ! burns. Do not permit fluid to contact eyes, skin,   clothing, painted surfaces, etc. Wear protective   goggles, protective clothing and gloves when   handling a battery. If the fluid is spilled, flush   the affected area immediately with clear water.   Do not use any jumper cables or booster bat-   tery to crank and start the generator engine. If   ! the battery has completely discharged, remove   it from the generator for recharging.   ® Generac Power Systems, Inc. 19   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 4 — Maintenance   QUIETSOURCE   ™ Liquid-cooled 30 kW Generators   4.7 SCHEDULED MAINTENANCE   Following is a recommended maintenance schedule for Generac small standby and residential generator sets. The   established intervals in the schedule are the maximum recommended when the unit is used in an average service   application. They will need to be decreased (performed more frequently) if the unit is used in a severe application.   Use the unit hour meter or calendar time, whichever occurs first, from the previous maintenance interval to deter-   mine the next required maintenance interval.   Service Maintenance Interval Information:   The various service maintenance intervals are designated by interval numbers as follows:   1 An early inspection of the generator set to ensure it is ready to operate when required and to identify any poten-   tial problem areas.   Performed monthly or following each 10 hours of operation of the unit and requires approximately .5 man-   hours per unit to complete.   This inspection may be performed by the end user providing the following safety steps are taken to prevent   the engine from starting automatically without warning:   To prevent injury, perform the following steps in the order indicated before starting any maintenance:   • Disable the generator set from starting and/or connecting to the load by setting the control panel   AUTO-OFF-MANUAL switch to the “OFF” position.   Remove the control panel fuse.   Turn off the battery charger.   Remove the negative battery cable.   • • • The battery charger must be turned off BEFORE removing the battery cable to prevent an over current condi-   tion from burning out sensitive control panel components and circuits.   Following all maintenance, reverse these steps to insure the unit is returned to standby setup for normal   operation when required.   2 A break-in service inspection of the generator set to ensure it is ready to operate and carry the load when   required, and to identify any potential problem areas.   Performed ONLY ONCE following the first three months or the first 30 hours of operation after purchase of   the unit and requires approximately 2.5 man-hours per unit to complete.   This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge   to accomplish and should be performed only by an authorized Generac Service Dealer.   3 An operational inspection of the generator set to ensure it is ready to operate and carry the load when required,   and to identify any potential problem areas.   Performed semi-annually or following each 50 hours of operation of the unit and requires approximately 1.5   man-hours per unit to complete.   This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge   to accomplish and should be performed only by an authorized Generac Service Dealer.   4 A mid-level inspection of the generator set to ensure it is ready to operate and carry the load when required,   and to identify any potential problem areas.   Performed annually or following each 100 hours of operation of the unit and requires approximately 4.0   man-hours per unit to complete.   This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge   to accomplish and should be performed only by an authorized Generac Service Dealer.   ® 20 Generac Power Systems, Inc.   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 4 — Maintenance   QUIETSOURCE   ™ Liquid-cooled 30 kW Generators   Maintenance   Tasks   Level 1   Recom-   mended   Level 2   Required   Level 3   Required   Level 4   Task   Task   Task   Task   Comp.   Comp. to be done Comp. to be done Comp.   Required   to be done (Date-   monthly Initials)   3 months/   Break-in   (Date-   Initials)   Semi-   annually   (Date-   Initials)   to be done (Date-   Annually Initials)   1. Disable the unit from   operating per the first page   warning.   2. Check the engine oil level.   Adjust as necessary.   3. Check the engine coolant   level. Adjust as necessary.   4. Check the engine coolant   thermal protection level.   Correct as necessary.   5. Check the natural gas or LP   delivery system on gas   engine driven units.   Tighten connections as   necessary.   6. Check the air inlets and   outlets for debris. Clean as   necessary.   7. Check the battery   electrolyte level if   accessible. Adjust as   necessary.   8. Check the battery posts,   cables, and charger for   loose connections,   corrosion, and proper   operation. Correct as   necessary.   9. Check the unit wiring for   loose connections,   corrosion, and damage.   Correct as necessary.   10. Check the engine   accessory drive belts for   wear, weather cracking,   and damage. Replace as   necessary.   11. Visually inspect the unit   looking for leaks, wear or   damage, loose connections   or components, and   corrosion. Correct as   necessary.   12. Test the engine and   transfer switch safety   devices. Correct and/or   adjust as necessary.   ® Generac Power Systems, Inc. 21   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 4 — Maintenance   QUIETSOURCE   ™ Liquid-cooled 30 kW Generators   Maintenance   Tasks   Level 1   Recom-   mended   Level 2   Required   Level 3   Required   Level 4   Task   Task   Task   Task   Comp.   Comp. to be done Comp. to be done Comp.   Required   to be done (Date-   monthly Initials)   3 months/   Break-in   (Date-   Initials)   Semi-   annually   (Date-   Initials)   to be done (Date-   Annually Initials)   13. Initiate an automatic start   and transfer of the unit to   site load and exercise it for   at least 1 hour looking for   leaks, loose connections   or components, and   abnormal operating   conditions. Correct as   necessary.   14. Start and exercise the unit   at full rated load (use a   load bank if the site load is   not enough) for at least 2   hours looking for leaks,   loose connections or   components, and abnormal   operating conditions.   Correct as necessary.   15. Change the engine oil.   16. Replace the engine oil   filter(s).   17. Replace the engine air   filter(s).   18. Replace the engine fuel   filter(s) on diesel engine   driven units and re-prime   the fuel system.   19. Check the engine spark   plugs on gas engine driven   units. Clean and re-gap or   replace as necessary.   20. Perform a 5 minute no-load   operational run of the unit   looking for any post service   problems.   21. Return the unit to standby   setup for operation when   required.   ® 22 Generac Power Systems, Inc.   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 5 — Troubleshooting   Liquid-cooled 30 kW Generators   QUIETSOURCE   ™ TROUBLESHOOTING POINTS   PROBLEM   CAUSE   CORRECTION   Engine won’t crank.   1. 15 amp fuse blown.   1. Replace fuse.   2. Loose or corroded or defective   battery cables.   3. Defective starter contactor.   4. Defective starter motor.   5. Dead or Defective Battery.   6. 4 amp fuse blown.   2. Tighten, clean or replace   battery cables as necessary.   3. Replace contactor.   4. Replace starter motor.   5. Remove, change or replace battery.   6. Replace fuse.   Engine cranks, but won't start   1. Out of fuel.   2. Fuel solenoid (FS) is defective   3. Open Wire #14 from Engine Control   circuit board.   1. Replenish fuel.   2. Replace solenoid.   3. Reconnect wire.   4. Spark plugs defective.   4. Clean, regap or replace plugs.   1. Clean or replace as needed.   Engine starts hard, runs rough.   Engine starts, then shuts down.   1. Flame arrestor (air cleaner) plugged or   damaged.   2. Plugged fuel line.   3. Defective spark plugs.   2. Unclog fuel line.   3. Clean, regap or replace plugs.   1. Engine oil level is low.   2. Engine is overheated.   3. Defective Low Oil Pressure Switch   4. Defective Coolant Temperature Switch   5. Defective Control Module circuit board.   6. Coolant Level is Low.   1. Check oil and add oil as needed.   2. Check cooling system for leaks.   3. Replace switch.   4. Replace switch.   5. Replace board.   6. Repair leak - Add coolant.   7. Replace Switch.   7. Defective Low Coolant Level Switch   AUTO/OFF/MANUAL Switch at,   OFF engine continues to run   1. Defective AUTO/OFF/MANUAL switch   1. Replace switch.   2. Reconnect/close wire.   2. Open/disconnected wire #15A between   AUTO/OFF/MANUAL switch and Control   Module circuit board.   3. Defective Control Module circuit board   3. Replace board.   No AC output from generator.   1. Check main line circuit breaker.   2. Check circuit breaker & fuses.   3. Transfer switch set to NORMAL position   4. Generator internal failure.   1. Reset to ON or CLOSED.   2. Reset and replace, if necessary.   3. Set to GENERATOR position.   4. Contact an Authorized Generac   facility.   5. Thermal circuit breaker open.   5. Auto-reset - Wait five minutes and   attempt restart.   ® Generac Power Systems, Inc. 23   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 6 - Electrical Data   QUIETSOURCE   ™ Liquid-cooled 30 kW Generators   Wiring Diagram — Engine — Drawing No. 0E6199-E   2 NOTE:   SIZE (AWG)   CB2   162   ALL WIRES ARE 18 AWG 300   VOLT UL LISTED UNLESS   OTHERWISE NOTED AS SHOWN:   1 162   11   4 AVR   0 0 2 4 5 TB1   0 0 0 55   14   44   6 14   14   225   224   D1   4 4 TR2   55   0 OA   225A   224A   0 13A   0 239   15A   15   16   16   TR1   178   178   8 1 2 7 4 5 1b   1 2b   1 1a   2a   85   3 6 BC1   16   0 1 15   RL1   F2   F1   0 0 2 13A   13   13   3 4 14   0A   13   11   44   5 14A   15A   15E   14   6 1 7 4 8 2 5 1 4 5 6 11   9 6 224   225   239   10   11   12   6 IC   CB1   55   66   44   BA   44   11   22   33   6 NB   6 6 23   66   23   66   CUSTOMER CONNECTION   LEGEND {CONT.]:   FUSE, B/C (4A AGC TYPE)   BRUSH ASSEMLY (GENERATOR)   TB1 -   TR1 -   CB1 -   CB2 -   D1 -   BULKHEAD CONNECTOR 1 (ENGINE)   CIRCUIT BREAKER (OUTPUT)   CIRCUIT BREAKER (EXCITATION)   DIODE [FIELD BOOST]   TRANSFORMER 1 (56 VA 240/16 VAC)   TRANSFORMER 2 (6 VA 240/16 VAC)   FUSE, BAT. POWER (15A AGC TYPE)   ® 24 Generac Power Systems, Inc.   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 6 - Electrical Data   QUIETSOURCE   ™ Liquid-cooled 30 kW Generators   Wiring Diagram — Engine — Drawing No. 0E6199-E   NOTE:   SIZE (AWG)   PCB J2   1 DEG   767   ALL WIRES ARE 18 AWG 300   VOLT UL LISTED UNLESS   OTHERWISE NOTED AS SHOWN:   0 765   766   14   1 2 765   769   766   768   0 2 16   3 4 5 6 7 8 3 4 CC   JB   766   765   767   770   771   768   767   769   5 6 14   14   14   N/C   14   7 8 9 10   11   12   PCB J1   10   1 56   86   16   10   4 2 13   13   16   3 4 15A   23   BAT   GOV   5 224   0 771   767   765   770   N/C   766   1 2 3 4 5 6 4 4 6 7 SM   4 8 239   0 9 10   11   12   13   14   15E   85   10   10   13   0 14A   225   66   0 LT   16   16   16   16   14   14   0 IM   16   0 0 C1   449   449   1 2 0 0 5 3 3 0 0A   0 0A   0 GND1   14   0 4 14   16   IC   5 13   16   16   6 14A   15A   15E   14   0 14   3 2 1 7 5 FS   8 9 10   11   12   224   225   239   85   85   BLK   RED   HCT   0 WLS   86   0 LEGEND [CONT.]:   0 23   66   23   66   CONNECTOR 1 (ENGINE)   IGNITION MODULE (ON DISTRIBUTOR)   JUNCTION 1 (ON PCB)   DEG -   JUNCTION 2 (ON PCB)   JUNCTION BLOCK (RUN POWER)   GROUND (SENSING/LOW AMP)   GROUND (POWER/HIGH AMP)   WLS -   ® Generac Power Systems, Inc. 25   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 6 - Electrical Data   QUIETSOURCE   ™ Liquid-cooled 30 kW Generators   Electrical Schematic — Engine — Drawing No. 0E6200-A   LEGEND {CONT.]:   FUSE, BAT. POWER (15A AGC TYPE)   BRUSH ASSEMLY (GENERATOR)   FUSE, B/C (4A AGC TYPE)   TERMINAL BLOCK, INTERCONNECT.   TR1 -   CB1 -   CB2 -   D1 -   CIRCUIT BREAKER (OUTPUT)   CIRCUIT BREAKER (EXCITATION)   DIODE [FIELD BOOST]   SWITCH, AUTO/OFF/MANUAL   TRANSFORMER 1 (56 VA 240/16 VAC)   TRANSFORMER 2 (6 VA 240/16 VAC)   BCW   AR   1 1 BA   2 3   3 4 4 4 4 2 1 6 5 6 5 2 2 162   1 2 CB2   11   44   3 4 5 6 7 8 9 10   11   12   1 2 1a 2a   1 4 5 2 CB1   NB   ® 26 Generac Power Systems, Inc.   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 6 - Electrical Data   QUIETSOURCE   ™ Liquid-cooled 30 kW Generators   Electrical Schematic — Engine — Drawing No. 0E6200-A   WLS   HCT   0 LOS   12V BATTERY   CC   ) +   (-)   RED   SC   PCB   56   86   J1-1   J1-2   J1-3   J1-4   J1-5   J1-6   J1-7   J1-8   J1-9   15A   23   224   0 IC   5 6   4 J2-1   J2-2   J2-3   J2-4   J2-5   J2-6   J2-7   J2-8   767   765   769   766   768   0 239   6 1 5 15E   85   J1-10   J1-11   J1-12   J1-13   J1-14   IM   14A   225   66   N/C   14   DEG   0 765   1 2 766   14   3 4 5 6 7 8 9 GOV   1 771   2 767   765   770   N/C   766   766   765   767   770   771   768   767   769   3 4 5 6 10   11   12   1 2 LEGEND [CONT.]:   3 4 5 6 7 8 9 10   11   12   CONNECTOR 1 (ENGINE)   IGNITION MODULE (ON DISTRIBUTOR)   CONTACTOR, STARTER MOTOR   WLS -   DEG -   SWITCH, HIGH COOLANT TEMP   SENSOR, COOLANT LEVEL   ® Generac Power Systems, Inc. 27   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 7 - Exploded Views and Parts   QUIETSOURCE Liquid-cooled 30 kW Generators   Mounting Base — Drawing No. 0E6266-E   ™ ® 28 Generac Power Systems, Inc.   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 8 - Exploded Views and Parts   QUIETSOURCE Liquid-cooled 30 kW Generators   Mounting Base — Drawing No. 0E6266-E   ™ ITEM   PART NO.   QTY.   DESCRIPTION   1 2 3 4 5 6 7 8 9 10   11   12   13   14   15   16   17   18   20   21   22   23 *   24 *   25 *   26 *   30   0E5822   052860   052251   052257   052252   052259   052891   0536210213   074906   047411   055414   026850   022097   022473   049813   0A1694   052213   025507   027482   022129   045771   051756   046526   022131   055934M   077483   058665   038804D   038805AA   021991   049814   046526   022131   075763   050331   050331A   0A4010   052858   061902   059473   049820   1 4 4 4 4 4 4 1 1 1 1 2 1 2 1 4 1 3 2 1 1 1 1 1 1 REF.   REF.   1 1 1 1 2 1 1 BASEFRAME, WELDMENT 3.0L FORD   NUT FLANGED HEX M12-1.75   DAMPENER VIBRATION 40 BLUE   SPACER .49 X .62 X 1.87 PWDR/ZNC   DAMPENER VIBRATION   WASHER FLAT M12   SCREW HHC M12-1.75 X 80 G8.8   ASSY GRNDWIRE 11"/3/8 & 5/16 LUG   SCREW HHTT M6-1.0 X 20 BP   SCREW HHC M6-1.0 X 16 BP   LUG SLDLSS #2-#8 X 17/64 CU   WASHER SHAKEPROOF EXT 1/4 STL   WASHER LOCK M6-1/4   WASHER FLAT M6-1/4 ZINC   NUT HEX M6 -1.0 G8 YEL CHR   1-1/2" BUTTON PLUG   SCREW HHC M10-1.25 X 20 G8.8   WASHER SHAKEPROOF EXT 7/16 STL   WASHER SHAKEPROOF EXT 5/16 STL   WASHER LOCK M8-5/16   NUT HEX M8-1.25 G8 YEL CHR   SCREW HHC M10-1.5 X 20 G8.8   WASHER LOCK M10   WASHER FLAT 3/8-M10 ZINC   CLAMP VINYL .75 X .343 Z   BATT 12VDC 75-AH 26   BATT 12VDC 90-AH 27F   31   32   33   34   35   36   37   38   39   40   41   42   43   44   CABLE BATT RED #4 X 20.00   CABLE BATT BLK #4 X 30"   EARTH STRAP   SCREW HHC M10-1.5 X 25 G8.8   WASHER LOCK M10   WASHER FLAT 3/8 ZINC   BOOT BATTERY CABLE   1 1 2 2 1 1 2 BATTERY POST COVER BACLK -   BATTERY POST COVER RED +   SCREW HHC M8-1.25 X 60 G8.8 FT   NUT TOP LOCK FL M8-1.25   HOLD DOWN BATTERY   HOLD DOWN BATTERY   NUT HEX LOCK M8-1.25 NY INS   * NOT SHOWN-USED TO HOLD DOWN I/N 32   ® Generac Power Systems, Inc. 29   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 7 - Exploded Views and Parts   QUIETSOURCE Liquid-cooled 30 kW Generators   Compartment — Drawing No. 0E8519-B   ™ ® 30 Generac Power Systems, Inc.   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 7 - Exploded Views and Parts   QUIETSOURCE Liquid-cooled 30 kW Generators   Compartment — Drawing No. 0E8519-B   ™ ITEM   PART NO.   QTY.   DESCRIPTION   1 2 3 4 5 6 7 8 9 0E8418   0E8414   0E8413   0C2454   0E8402   0E5902   0E5903   0E8387   0E5912   0E5911   089961   0A2115   0E8404   0D2538A   0D2538   043116   022097   022473   0E7570   0E7571   070015   0E7662   0D2537A   0D2537   0D2023   0E7869   0E8001   0E5913   0E5915   0D3037A   0C7781   0E5910   0E8052   0D3037   0E5900   0E5901   0E5916   0E8415   026850   0912970063   0912970064   049813   0E8416   0E8417   0E8665   0D2023   0E8441   0E7829A   0E7829B   0E7829P   0E7829R   0E7829S   0E7829T   0E7829N   0E7829U   078115   1 1 1 62   1 1 1 1 2 1 2 4 1 1 1 8 12   12   2 4 4 4 1 1 2 2 1 1 1 1 2 1 1 1 1 1 1 1 4 2 2 2 1 1 1 1 1 1 2 4 2 1 1 2 2 8 DUCT INTAKE MID AL   DUCT DISCHARGE RH AL   DUCT DISCHARGE LH AL   SCREW TH-FRM M6-1 X 16 N WA Z/JS   BAFFLE REAR BOTTOM   POST CORNER LH REAR HSB AL   POST CORNER RH REAR HSB AL   BAFFLE REAR TOP   DOOR SIDE HSB AL   10   11   12   13   14   15   16   17   18   19   20   21   22   23   24   25   26   27   28   29   30   31   32   33   34   35   36   37   38   39   40   41   42   43   44   45   46   50 *   51   52   53   54   55   56   57   58   59   SUPPORT RH SIDE HSB AL   FOAM STRIP 3/4" WIDE X 3/16" THK (40" LG)   WASHER NYLON .257   BRACKET STIFFENER RH FRONT   HINGE LIFT OFF TYPE B KNUCKLE   HINGE LIFT OFF TYPE B PIN   SCREW HHC M6-1.0 X 12 G8.8   WASHER LOCK M6-1/4   WASHER FLAT 1/4-M6 ZINC   GAS SPRING   BALL STUD GAS SPRING MOUNT   NUT HEX 5/16-18 LOCK   SCREW WING M6-1.00 X 25   HINGE LIFT OFF TYPE A KNUCKLE   HINGE LIFT OFF TYPE A PIN   TRIM VINYL SELF GRIPPING (91" LG)   BRACKET STIFFENING BACK   MUFFLER BOX   ROOF HSB AL   BRACE FRONT TOP HSB AL   LATCH 1/4 TURN NONLOCKING   PAWL DOOR HSB   SUPPORT LH SIDE HSB AL   MUFFLER BOX TOP   LATCH QUARTER TURN LOCKING   POST CORNER LH FRONT HSB AL   POST CORNER RH FRONT HSB AL   BRACE FRONT BOTTOM HSB AL   DUCT DISCHARGE MID AL   WASHER SHAKEPROOF EXT 1/4 STL   ASSY GRD WIRE 99HSB   ASSEMBLY,BASE-DOOR GROUND WIRE   NUT HEX M6 X 1.0 G8 YEL CHR   DUCT INTAKE LH AL   DUCT INTAKE RH AL   BRACKET STIFFENER LH FRONT   TRIM VINYL SELF GRIPPING (165.5"LG)   KIT INSULATION 3.0L HSB   AI ROOF PANEL 1   AI DOOR PANEL   AI CORNER POST PANEL 1   AI CORNER POST PANEL 2   AI SUPPORT LH PANEL   AI SUPPORT RH PANEL   AI ROOF PANEL 2   AI BRACE PANEL   WASHER SELF LOCKING DOME   * ALL ITEMS NOTATED WITH "AI" ARE COMPONENTS OF 0E8441   ® Generac Power Systems, Inc. 31   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 7 - Exploded Views and Parts   QUIETSOURCE Liquid-cooled 30 kW Generators   Control Panel — Drawing No. 0E7118-G   ™ ® 32 Generac Power Systems, Inc.   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 7 - Exploded Views and Parts   QUIETSOURCE Liquid-cooled 30 kW Generators   Control Panel — Drawing No. 0E7118-G   ™ ITEM PART NO. QTY.   DESCRIPTION   ITEM PART NO. QTY.   DESCRIPTION   1 2 3 4 5 6 7 8 9 10   11   12   13   14   15   16   0E7195   0E7196   0E7197   0E7193   0E7194   0E4494   082573   032300   022676   067682B   060015   054199   0C2657   099076   040213   0E9668   0E4905   1 1 1 1 1 1 1 2 1 1 1 1 1 1 2 1 1 CONTROL BOX HSB   34   35   36   0D4698 *   0E7252   0C1229   REF.   1 1 BLOCK TERM 20A 6 X 3 X 1100V   BRACKET CB 221.5 X 102   DECAL WARNING ELECTRICAL   SHOCK   DECAL AVR COVER   COVER PLATE, AVR   HARNESS CNTRL PNL 3.0L FORD   (NOT SHOWN)   SCREW PPPH HI-LO #4-24 X 3/8   SCREW HHTT M5-0.8 X 10 BP   CONN DEUTSCH GASKET 8/12 POS   DT   SCREW PHTT #6-32 X 3/8 ZYC   SCREW PHTT #6-32 X 5/8 ZYC   WASHER LOCK #6   SCREW PHTT M4-0.7 X 12 ZYC   WASHER LOCK #8-M4   SCREW PPHM M5-0.8 X 30 ZINC   SCREW HHTT M5-0.8 X 16   WASHER LOCK #10   WASHER FLAT #10 ZINC   NUT HEX M5-0.8 G8 YEL CHR   SCREW HHTT M6-1.0 X 12 ZINC   SCREW HHC M6-1.0 X 20 G8.8   WASHER LOCK M6-1/4   WASHER FLAT 1/4-M6 ZINC   WIRE ASSY 3" X (2) 3/16" TABS   WASHER MICA .203   WASHER SHAKEPROOF EXT #10   STL   COVER FRONT PANEL HSB   COVER TOP PANEL HSB   DECAL WARNINGS HSB   DECAL CONTROLS HSB   SWITCH ROC DPDT ON-OFF-ON   SWITCH ROCKER DPST 125V SPD   HOLDER FUSE   37   38   39   0C1127   0A1441B   0E7128   1 1 1 FUSE 15A X AGC15   40   41   42   0E7358   074908   0C5141   8 6 1 FUSE 4A SLO BLO GLASS   FITTING CONDUIT 90D 3/8"   DECAL DANGER HIGH VOLTAGE   TRANSFRMR 16V 6VA   TRANSFORMER 16V 56VA   PCB SUPPORT SNAP-IN 1/4"   ASSY PCB HSB CONTROLLER 3.9L   ASSY PCB HSB CONTRLR 3.0L   FORD   ASSY VOLTAGE REGULATOR 60HZ   RELAY 12VDC C FORM W/DIODE   SOCKET RELAY   CONN DEUTSCH RECEPT GY/FLN   CONN DEUTSCH RECEPT WDGE   BLKHD   ASSY BOSCH GOV DRIVER   CIRCT BRK 5.5 X 1 ETA 46-500-P   ASSY 2A 12V UL BATTERY   CHARGER   FITTING CONDUIT STR 1-1/2"   DECAL NEUTRAL   DECALCUSTOMER CNNCTN XFER   SW   BLOCK TERM 20A 6 X 6 X 1100V   DECAL CUSTOMER CNNCTN E1 E3   N 43   44   45   46   47   49   50   51   52   53   54   55   56   57   58   59   60   0C2699   0C2323   022155   0C2265   022264   020911   066849   022152   023897   051716   090388   042568   022097   022473   0441140187   070370   023762   11   4 15   4 4 2 2 4 3 2 2 4 8 6 2 2 1 17   18   19   20   21   067680   1 1 REF.   REF.   REF.   0E6875A   0E6881 *   0C5139 *   0E5142 *   22   23   24   0E3161   054450   0D5070A   1 1 1 25   26   27   0E2514   0A9457   0E7539   1 1 1 61   62   63   64   65   66   67   68   055444   030468   049939   022158   022985   038750   0A2115   0C2454   1 1 1 1 1 2 4 4 HEATSINK   WASHER STEP NYLON .20   RECTIFIER MSC 12A 600V 1N1206R   NUT HEX #10-32 STEEL   WASHER FLAT #6 ZINC   SCREW HHC M6-1.0 X 30 G8.8   WASHER NYLON .257   28   29   046357 *   0D3719B   REF.   1 30   31   057073   0E7283   0E3628   0E3664   0E7539A   1 1 1 1 1 JUNCTION BLOCK 3/8-16   CB 0150A2P240V S QN2 LL   CB 0200A2P240V S QN2 LL   BASE QN CIRCUIT BREAKER   DECAL TB1 HSB CONTROL PANEL   SCREW THF M6-1 X 16 N WA Z/JS   32   33   * ITEMS INCLUDED AS PART OF I/N 39   ® Generac Power Systems, Inc. 33   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 7 - Exploded Views and Parts   QUIETSOURCE Liquid-cooled 30 kW Generators   ™ Engine — Drawing No. 0E8170-J   69   27   28   57   58   14   1 15   60   10   8 25   61   36   35   36   3 35   42   34   38   36   42   2 43   55   35   3 40   7 43   36   35   5 42   47   37   51   54   43   6 78   12   BAFFLE   REAR UPPER   21   47   38   26   7 73   29   2 57   58   30   60   48   44   30   31   64   36   35   39   48   32   17   45   25   39   24   35   61   42   65   41   66   GROUND   WIRE   68   18   16   19   ® 34 Generac Power Systems, Inc.   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 7 - Exploded Views and Parts   QUIETSOURCE   ™ Liquid-cooled 30 kW Generators   Engine — Drawing No. 0E8170-J   ITEM PART NO. QTY.   DESCRIPTION   ITEM PART NO. QTY.   DESCRIPTION   1 2 3 0E6202   0E8824   0E8963   1 2 1 ENGINE 3.0L FORD (RD) (MAKE)   STAMPING ENG FOOT 3.0L FORD   PULLEY CRANKSHAFT 3.0L FORD   RD   BRACKET DC ALT 3.0L FORD   D.C. ALTERNATOR ASSY   PULLEY POLY-V 82 OD.   BRACKET ALTERNATOR   PULLEY WATERPUMP 3.0L FORD   (RD)   HARN IGNITION 3.0L FORD (NOT   SHOWN)   FAN BELT 3.0L FORD   CLUTCH COOLING FAN FORD   FAN 18" 7 BLADE STEEL ECS   SENSOR HI COOLANT SHUTDOWN   ASSY WATER LEVEL SENSOR C/E   PL   STARTER 12 VOLT   COVER FLYWHEEL ACCESS   3.0LHSB   ENGINE ADAPTER 3L FORD   FLEXPLATE 3.0L FORD   BUSHING REDUCER 1/4 TO 1/8   SWITCH OIL PRESSURE 10PSI   2POL   WASHER LOCK 1/4-M6 SS   WASHER FLAT 1/4 SS   SCREW HHC M12-1.75 X 85 G8.8   CAP HOSE   CLAMP HOSE #10 .56-1.06   RELAY SOLENOID 12VDC PNL MNT   SCREW HHC M6-1.0 X 16 G8.8   WASHER LOCK M6-1/4   43   44   45   46   47   48   49   50   51   53   54   55   56   022131   059982   098780   051769   049808   051430   045773   0E6203C   0E6679   049226   091526   093278   0E6517   11   4 2 3 2 6 3 1 2 7 3 4 1 WASHER FLAT 3/8-M10 ZINC   SCREW SHC M12-1.75 X 45 G10.9   SCREW HHC M12-1.75 X 65 G8.8   WASHER LOCK M12   4 5 6 7 8 0E9020   0A1232   0A7801B   0A5610   0E6308   1 1 1 1 1 WASHER FLAT M12   WASHER SHAKEPROOF INT 1/2   NUT HEX M12-1.75 G8 YEL CHR   COIL IGNITION 3.0L FORD   BRACKET IGN COIL 3.0L FORD   WASHER LOCK M5   SCREW PPHM M5-0.8 X 12 ZNC   SCREW HHTT M5-0.8 X 25 BP   HARNESS ENGINE 3.0L FORD HSB   (NOT SHOWN)   GASKET EXHAUST 3.0L FORD   MANIFOLD EXHAUST 3.0L FORD   HEAT SHIELD 260 X 80 HOT   SCREW HHC 1/4-20 X 1/2 SS   WIRE SET 3.0L FORD (NOT   SHOWN)   9 **   0E7804   1 10   11   12   14   15   0E6310   0E7996   0E8006   035606   0E0561   1 1 1 1 1 57   58   60   61   62   0E7163   0E5527   0E7202   085296   0E6203D   2 2 2 6 1 16   17   0E9747   0E6703   1 1 63   64   65   66   67   68   69   70 *   71 *   72   057772   057765   061696   069860C   057822   069811   026925   065852   0A2111   057073   066849   022152   0E7880   1 1 1 1 2 1 1 1 1 1 2 2 2 WASHER NYLON .565   18   19   20   21   0E6667   0E5048   035579   0A8584   1 1 1 1 ADAPTER M14-1.50 X 3/8 NPT   BARBED EL 90 3/8 NPT X 1/2   HOSE OIL DRAIN ASSY 21"   CLAMP HOSE #8 .53-1.00   CAP HEX 1/4NPT BRASS   PLUG STD PIPE 3/8 STEEL SQ HD   SPRING CLIP HOLDER .37-.62   SCREW SWAGE 10-32 X 5/16 Z/YC   JUNCTION BLOCK 3/8-16   SCREW HHTT M5-0.8 X 16   WASHER LOCK #10   CLIP SPARK PLUG 3P SCREW-   MOUNT (NOT SHOWN)   CLIP SPARK PLUG 2P SCREW-   MOUNT (NOT SHOWN)   CLIP SPARK PLUG 3P FREEHANG   (NOT SHOWN)   CLAMP VINYL .5 X .406 Z   WASHER SHAKEPROOF EXT 5/16   STL   24   25   26   27   28   29   30   31   32   33   34   35   36   37   38   39   40   41   42   083896   084929   055597   077996   057823   056739   047411   022097   022473   042907   040976   022129   022145   045771   051756   049821   059980   0D5417   046526   6 6 1 1 1 1 6 6 6 4 4 24   22   1 6 16   4 REF.   17   73   74   75   WASHER FLAT 1/4-M6 ZINC   SCREW HHC M8-1.25 X 16 G8.8   SCREW SHC M8-1.25 X 20 G12.9   WASHER LOCK M8-5/16   WASHER FLAT 5/16-M8 ZINC   NUT HEX M8-1.25 G8 YEL CHR   SCREW HHC M10-1.5 X 20 G8.8   SCREW SHC M8-1.25 X 30 G12.9   SCREW HHC M10-1.5 X 25 G10.9   SCREW HHC M10-1.0 X 25 G10.9   WASHER LOCK M10   76   77   0E7880A   0E7880B   4 1 78   79   055934C   027482   1 1 80   0E8940   1 SPACER FLEXPLATE HSB   * NOT SHOWN-USED TO HOLD OIL DRAIN ASSEMBLY.   ** NOT SHOWN   ® Generac Power Systems, Inc. 35   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 7 - Exploded Views and Parts   QUIETSOURCE Liquid-cooled 30 kW Generators   Radiator — Drawing No. 0E8528-B   ™ ® 36 Generac Power Systems, Inc.   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 7 - Exploded Views and Parts   QUIETSOURCE Liquid-cooled 30 kW Generators   Radiator — Drawing No. 0E8528-B   ™ ITEM   PART NO.   QTY.   DESCRIPTION   1 2 3 4 5 6 7 8 9 10   11   12   13   14   15   17   18   20   21   22   23   24   25   26   27   0E9947   0E6340   0E8531   0E6398   0E6397   080713   076749   049814   022131   046526   045772   035685   0E8562   058443   0C2454   048031C   029032   046627   069811   065852   0A2111   052250   035461   0C7649   069860C   1 1 2 1 1 1 1 4 8 4 4 4 1 4 9 1 1 1 1 1 1 2 1 1 1 RADIATOR R-IN,L-OUT 658X489X49   VENTURI 3.0L FORD HSB   SIDE SUPPORT RADIATOR HSB   TUBE LOWER RAD 3.0L FORD HSB   HOSE UPPER RAD 3.0LFORD HSB   BRACKET COOLANT TANK   TANK COOLANT RECOVERY   SCREW HHC M10-1.5 X 25 G8.8   WASHER FLAT 3/8-M10 ZINC   WASHER LOCK M10   NUT HEX M10-1.5 G8 YEL CHR   CLAMP HOSE #28 1.32-2.25   FAN GUARD HSB   SCREW CRIMPTITE 1/4-20 X 5/8   SCREW TH-FRM M6-1 X 16 N WA Z/JS   CLAMP HOSE BAND 1/4   HOSE 9/32 ID (30" LG)   CAP RADIATOR   CAP HEX 1/4 NPT BRASS   SPRING CLIP HOLDER .37-.62   SCREW SWAGE 10-32 X 5/16 Z/YC   TAPE FOAM 1 X 1 (27" LG)   BARBED STR 1/4 NPT X 3/8   CLAMP HOSE .38-.87   HOSE OIL DRAIN ASSY 21"   ® Generac Power Systems, Inc. 37   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 7 - Exploded Views and Parts   QUIETSOURCE Liquid-cooled 30 kW Generators   Fuel System — Drawing No. 0E8190-B   ™ ® 38 Generac Power Systems, Inc.   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 7 - Exploded Views and Parts   QUIETSOURCE Liquid-cooled 30 kW Generators   Fuel System — Drawing No. 0E8190-B   ™ ITEM   PART NO.   QTY.   DESCRIPTION   1 *   2 3 4 5 6 7 8 9 ---------   1 1 1 2 2 4 2 2 2 1 1 1 2 1 1 1 1 1 1 1 1 4 8 4 2 4 1 1 1 1 1 1 1 1 1 1 WELDMENT MOUNTING BASE   FLANGE FUEL INLET   ASSY REGULATOR 3.0L NG OR LPV   SCREW HHC M8-1.25 X 20 G8.8   WASHER FLAT 5/16 ZINC   075580   0E7691   039253   022145   022129   045771   042907   0C2454   026307   0E1056   0E6584   057823   059194   044117   0D1509   050279   0E6123   0E6586   0E4395   057753B   047487   022097   051751   035685   057823   047290   047290   0A4121   0E6609   049099   055934M   047411   022097   O22473   0E9295A   WASHER LOCK M8-5/16   NUT HEX M8-1.25 G8 YEL CHR   SCREW HHC M8-1.25 X 16 G8.8   SCREW TH-FRM M6-1 X 16 N WA Z/JS   ELBOW 90D STREET 3/4   FUEL HOSE ASSY NAT.GAS/L.P.V.   BRACKET REGULATOR 3.0L FORD HSB   CLAMP HOSE #10 .56 - 1.06   HOSE 5/8 ID LPG & NG (20" LG)   BARBED STR 3/8 NPT X 5/8   DECAL INLET PRESSURE   DECAL FUEL INLET NG   INTAKE ADAPTER 3.0L FORD-BOSCH   GASKET BOSCH 32   ACTUATOR BOSCH 32 GOVERNOR   HOSE 1.5 ID X 2 LG 20R4   SCREW SHC M6-1.0 X 18 G12.9   WASHER LOCK M6-1/4   SCREW HHC M6-1.0 X 50 G8.8   CLAMP HOSE #28 1.32-2.25   CLAMP HOSE #10 .56-1.06   HOSE 3/8 ID SINGLE BRAID (305mm [12"] LONG)   HOSE 3/8 ID SINGLE BRAID (432mm [17"] LONG)   VALVE PCV   GROMMET ROCKER COVER 3.0LFORD   BARBED EL 90 3/8 X 3/8 PLST   CLAMP VINYL .75 X .343 Z   SCREW HHC M6-1.0 X 16 G8.8   WASHER LOCK M6-1/4   10   11   12   13   14   15   16   17   18   19   20   21   25   26   27   28   29   30   31   32   33   34   35 **   36 **   37 **   38 **   39   WASHER FLAT 1/4-M6 ZINC   ASSY THROTTLE 27MM   * SHOWN IN OTHER VIEW   ** NOT SHOWN-USED TO HOLD #31 IN PLACE   ® Generac Power Systems, Inc. 39   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 7 - Exploded Views and Parts   QUIETSOURCE Liquid-cooled 30 kW Generators   Alternator — Drawing No. 0E8660-B   ™ ® 40 Generac Power Systems, Inc.   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 7 - Exploded Views and Parts   QUIETSOURCE Liquid-cooled 30 kW Generators   Alternator — Drawing No. 0E8660-B   ™ ITEM   PART NO.   QTY.   DESCRIPTION   1 0F1659A   0F1657A   0F1655A   0E5093A   0E7413A   0F1660A   0F1658A   0F1656A   0E5094A   0E7412A   0E5706   1 1 1 1 1 1 1 1 1 1 1 REF   REF   REF   1 1 8 4 4 ROTOR 390 15KW 1P DIRECT HSB (2.5L FORD)   ROTOR 390 20KW 1P DIRECT HSB (2.5L FORD)   ROTOR 390 25KW 1P DIRECT HSB (2.5L FORD)   ROTOR 390 30KW 1P DIRECT HSB (3.0L FORD & 2.5L FORD)   ROTOR 390 40KW 1P DIRECT HSB (3.9L CHRYSLER)   STR 390 15AD HSB (382MM LONG)(2.5L FORD)   STR 390 20AD HSB (382MM LONG)(2.5L FORD)   STR 390 25AD HSB (382MM LONG)(2.5L FORD)   STR 390 35AD1 HSB (382MM LONG)(3.0L FORD & 2.5L FORD)   STR 390 40AD HSB (433MM LONG)(3.9L CHRYSLER)   REAR BEARING CARRIER 390/DRCT   FLEXPLATE 3.0L FORD   FLEXPLATE 3.9L HSB   FLEXPLATE 2.5L FORD   FLYWHEEL ASSY 3.0L HSB LG GEAR   REVCOR FAN 10.75 X 2 W/PRESS DIS   WASHER LOCK M10   2 3 4 0E5048   0E5048A   0E5048B   0E6668   0E6076   046526   5 6 7 8 9 051755   SCREW HHC M10-1.5 X 16 G8.8   04576100BK   04576100BF   043123   STUD M14-2.0 X 490 G5 ZINC (3.0L FORD & 2.5L FORD)   STUD M14-2.0 X 540 G5 ZINC (3.9L CHRYSLER)   WASHER LOCK M14   4 4 10   11   12   13   14   15   16   17   18   19   20   21   051779   0E7587   023365   092980   057192   0A2602   042558   0A2601   022264   038150   077043F   077043F   4 1 1 4 4 1 1 1 4 4 1 1 NUT HEX M14-2.0 G8 YEL CHR   ASSY BRUSH HOLDER 390/HSB   WASHER SHAKEPROOF INT #8   SCREW PPHM M4-0.7 X 25   SCREW SHC M10-1.5 X 30 G12.9   WASHER FLAT .688 ID X 3.25 OD   KEY SQ 3/8 X 1 STEEL   SCREW HHC M16-2.0 X 45 G8.8   WASHER LOCK #8-M4   WASHER FLAT #8 ZINC   CONDUIT FLEX 1-1/4" (30" LG - 3.0L FORD & 3.9L CHRYSLER)   CONDUIT FLEX 1-1/4" (18" LG - 2.5L FORD)   ROTOR REPLACEMENT PARTS   30   31   047248   070892   1 1 BALL BEARING-45 MM   SLIP RING -MACHINED-   ® Generac Power Systems, Inc. 41   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 7 - Exploded Views and Parts   QUIETSOURCE Liquid-cooled 30 kW Generators   ™ Muffler — Drawing No. 0E8766-B   2 11   18   1 19   7 17   16   8 16   16   17   20   18   19   8 TO   COMPARTMENT   15   TO   MANIFOLD   16   11   22   17   10   4 11   21   6 11   12   TO   MANIFOLD   3 9 4 22   17   14   10   21   12   13   14   9 5 ITEM PART NO. QTY.   DESCRIPTION   ITEM PART NO. QTY.   DESCRIPTION   1 0E8616   1 MUFFLER 7" X 9" X 21" 2.5" IN &   OUT   PIPE MUFFLER OUT   WYE PIPE 2-1/2"   11   12   13   14   15   16   17   18   19   080762   0E8816   085917   0D2611   039253   022145   022129   045771   0C2454   4 2 4 4 2 5 7 3 4 BOLT U 3/8-16 X 2.62   EXHAUST FLANGE 2" PIPE   WASHER LOCK 3/8 SS   2 3 4 5 6 7 0E8727   0E8822   0E8821   0E6465   0E6465A   0E5914   1 1 2 1 1 1 SCREW HHC 3/8-16 X 1-3/4 SS   SCREW HHC M8-1.25 X 20 G8.8   WASHER FLAT 5/16-M8 ZINC   WASHER LOCK M8-5/16   NUT HEX M8-1.25 G8 YEL CHR   SCREW TH-FRM M6-1 X 16 N WA   Z/JS   SCREW HHC M8-1.25 X 55 G8.8   GASKET EXHAUST RING   NUT HEX 5/16-18 STEEL   EXHAUST ELBOW HSB (2"-2-1/2")   EXHAUST PIPE LH 3.0L FORD HSB   EXHAUST PIPE RH 3.0L FORD HSB   BRACKET MUFFLER 3.0L FORD   HSB   STRAP MUFFLER   EXHAUST BLANKET 3.0L FORD   HSB   8 9 0E8726   0E0170A   2 2 20   21   22   039288   044149   022259   1 2 4 10   036797   2 BOLT U 5/16-18 X 2.25   ® 42 Generac Power Systems, Inc.   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 7 - Exploded Views and Parts   QUIETSOURCE Liquid-cooled 30 kW Generators   Air Cleaner — Drawing No. 0E8189   ™ ITEM PART NO. QTY.   DESCRIPTION   ITEM PART NO. QTY.   DESCRIPTION   1 2 3 4 5 0E5193   0E8200   0E8201   036434   0E0519A   1 1 1 1 1 PLATE AIR CLEANER ADAPTER   TUBE AIR INTAKE 3.0L FORD   BRACKET AIR INTAKE 3.0L FORD   BOLT U 5/16-18 X 2.09   ADAPTER, CARBURETOR W/PVC   CONN   ELEMENT, AIR CLEANER   COVER - AIR CLEANER   STUD TH 1/4-20 X 4-1/2 G2 ZNC   NUT HEX 1/4-20 STEEL   11   12   13   14   15   16   17   18   19   20   21   049226   091526   052619   051713   051716   022131   046526   051755   022145   022129   022259   8 4 4 4 4 2 2 2 2 2 2 WASHER LOCK M5   SCREW PPHM M5-0.8 X 12 ZNC   SCREW HHC M5-0.8 X 20 G8.8   WASHER FLAT M5   NUT HEX M5-0.8 G8 YEL CHR   WASHER FLAT 3/8-M10   6 7 8 9 10   0C8127   0A5547   062974   022127   037561   1 1 1 1 1 WASHER FLAT M10   SCREW HHC M10-1.5 X 16 G8.8   WASHER FLAT 5/16-M8 ZINC   WASHER LOCK M8-5/16   NUT HEX 5/16-18 STEEL   NUT WING 1/4-20 NYLK   ® Generac Power Systems, Inc. 43   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 8 — Installation Diagram   QUIETSOURCE   ™ Liquid-cooled 30 kW Generators   Installation Diagram — Drawing No. 0E8696   ® 44 Generac Power Systems, Inc.   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 9 — Notes   QUIETSOURCE   ™ Liquid-cooled 30 kW Generators   ® Generac Power Systems, Inc. 45   Download from Www.Somanuals.com. All Manuals Search And Download.   Section 10 – Warranty   QUIETSOURCE   ™ Liquid-cooled 30 kW Generators   GENERAC POWER SYSTEMS "TWO YEAR" LIMITED WARRANTY FOR QUIETSOURCE™   "PREPACKAGED EMERGENCY AUTOMATIC STANDBY GENERATORS"   For a period of two years from the date of original sale, Generac Power Systems, Inc. (Generac) warrants that its Quietsource gener-   ator will be free from defects in material and workmanship for the items and period set forth below. Generac will, at its option, repair   or replace any part which, upon examination, inspection and testing by Generac or an Authorized Warranty Service Dealer, is found   to be defective. Any equipment that the purchaser/owner claims to be defective must be examined by the nearest Authorized Warranty   Service Dealer. All transportation costs under the warranty, including return to the factory, are to be borne and prepaid by the pur-   chaser/owner. This warranty applies only to Generac Quietsource prepackaged emergency automatic standby generators sold and   rated for use in "Standby" applications.   WARRANTY SCHEDULE   YEARS ONE and TWO - 100% (one hundred percent) transferable coverage on Labor and Part(s) listed (proof of purchase and main-   tenance is required):   Engine - All Components   Alternator - All Components   Transfer System - All Components   All warranty expense allowances are subject to the conditions defined in Generac's Warranty Policies, Procedures and Flat Rate   Manual.   THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING:   • Quietsource generators that utilize non-Generac/Quietsouce replacement parts.   • Quietsource generators utilizing non-Generac/Quietsource automatic transfer switches.   • Repairs performed by individuals other than Guardian/Generac authorized dealers.   • Any Quietsource generators used as rental or trailer mounted applications.   • Air-cooled units used for prime power in place of existing utility power where utility power is present or in place of utility power where   utility power service does not normally exist.   • Costs of normal maintenance, adjustments, installation and start-up.   • Failures caused by any contaminated fuels, oils, coolants or lack of proper fluid amounts.   • Failures due, but not limited, to normal wear and tear, accident, misuse, abuse, negligence or improper installation. As with all   mechanical devices, the Generac engines need periodic part(s) service and replacement to perform well. This warranty will not   cover repair when normal use has exhausted the life of a part(s) or engine.   • Failures caused by any external cause or act of God, such as collision, theft, vandalism, riot or wars, nuclear holocaust, fire,   freezing, lightning, earthquake, windstorm, hail, volcanic eruption, water or flood, tornado or hurricane.   • Damage related to rodent and/or insect infestation.   • Products that are modified or altered in a manner not authorized by Generac in writing.   • Any incidental, consequential or indirect damages caused by defects in materials or workmanship, or any delay in repair or   replacement of the defective part(s).   • Failure due to misapplication.   • Telephone, cellular phone, facsimile, internet access or other communication expenses.   • Living or travel expenses of person(s) performing service, except as specifically included within the terms of a specific unit warranty   period.   • Expenses related to "customer instruction" or troubleshooting where no manufacturing defect is found.   • Rental equipment used while warranty repairs are being performed.   • Costs incurred for equipment used for removal and/or reinstallation of generator, (i.e.; cranes, hoists, lifts, etc.)   • Overnight freight costs for replacement part(s).   • Overtime labor.   • Starting batteries, fuses, light bulbs and engine fluids.   THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED. SPECIFICALLY, GENERAC MAKES   NO OTHER WARRANTIES AS TO THE MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some states do not   allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.   GENERAC'S ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED ABOVE. IN NO EVENT   SHALL GENERAC BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES, EVEN IF SUCH DAMAGES ARE A   DIRECT RESULT OF GENERAC'S NEGLIGENCE. Some states do not allow the exclusion or limitation of incidental or consequential   damages, so the above limitation may not apply to you.   This warranty gives you specific legal rights. You also have other rights from state to state.   ® GENERAC POWER SYSTEMS, INC.   P.O. BOX 297 • WHITEWATER, WI 53190   Revision (10/01/04)   Part No. 0E8565   Revision E (10/06/04)   Printed in U.S.A.   Download from Www.Somanuals.com. All Manuals Search And Download.   |