FieldServer Server FS B OPC 01 User Manual

A Sierra Monitor Company  
FS-B-OPC-01 Start-up Guide  
APPLICABILITY & EFFECTIVITY  
Description  
FS-B-OPC Series  
FieldServer  
The instructions are effective for the above as of February 2009  
Kernel Version:  
Document Revision:  
5.12  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-B-OPC-01 Series FieldServer Start-up Guide  
Page 3 of 10  
1
PRE-INSTALLATION CHECK LIST  
1.1 Supplied equipment  
FS-B-OPC-01 Series FieldServer  
loaded with Modbus RTU driver, SMT Ethernet driver, FST OPC Server Configurator and any other drivers  
ordered.1  
USB Flash Drive loaded with:  
FS-B-OPC-01 Series Start-up Guide  
FieldServer Configuration Manual  
FieldServer Utilities Manual  
Driver Manual(s) specific to all Drivers ordered with the FieldServer.  
Support Utilities (for the following platforms only:  
Windows XP  
Windows 2000  
Windows NT  
Windows 98  
Any additional folders related to special files configured for a specific FieldServer.  
Additional components as required -. See Driver Manual Supplement for details  
Accessories:  
6 ft Serial RS-232 connection pigtail (Part Number FS-8917-10)  
7-ft Cat5 cable with RJ45 connectors at both ends (Part Number FS-8915-10)  
Power Supply  
1.2 Mounting  
The FS-B-OPC-01 Series FieldServer is supplied with an accessory bag which allows selection of adhesive feet (for  
standing on a shelf).  
1.3 Wiring  
Select an external power supply certified for safety, for the correct destination country and an output rating,  
which is considered a NEC Class 2 circuit or is a SELV Limited power source with the following ratings:  
12-14 VDC, 5.0-4.28A;  
The operating environment for the product is 0 to 60°C (32 to 140°F).  
1 Note that a default configuration file has already been loaded onto the FieldServer. Check the Driver Manual and the FieldServer  
Configuration Manual for further information on this file.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
FS-B-OPC-01 Series FieldServer Start-up Guide  
Page 4 of 10  
2
PRODUCT DESCRIPTION  
2.1 Dimensions  
Figure 2-1: Diagram of FS-B-OPC-01 Showing External Dimensions  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
FS-B-OPC-01 Series FieldServer Start-up Guide  
Page 5 of 10  
2.2 Specifications  
Power requirements (power supply is external)  
FS-B-OPC-01 power supply P/N PWR-ACDC-12v-5A-60W  
Input voltage: 100-240Vac, 60W (max);  
Output voltage / current: 12Vdc @ 5.0A  
Physical Dimensions(excluding the external power supply)  
(WxDxH):  
Weight:  
7.70 x 9.50 x 2.10 inches (19.56 x 24.13 x 5.33 cm)  
2.4 lbs. (1.09 Kg)  
Available Ports  
1 x DB9 RS-232 serial port  
1 x RJ45 10-BaseT Ethernet connector  
Environment:  
Operating Temperature: 0 60°C (32 140°F)  
Humidity:  
10 - 90% RH (non-condensing)  
(Specifications subject to change without notice)  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
FS-B-OPC-01 Series FieldServer Start-up Guide  
Page 6 of 10  
3
CONNECTION TO THE DEVICE  
The 12VDC power supply received with the unit needs to be plugged into a power source and then connected to  
the back of the FieldServer. Ensure that the power supply used complies with the specifications provided in  
Section 2.2.  
Power  
Serial  
Ethernet  
Figure 3-1: View of back of FS-B-OPC-01 showing Connection Ports  
3.1 RS-232 connection  
The FS-B-OPC-01 Series FieldServer is shipped with the RS-232 port activated.  
Connect the FS-8917-10 cable (supplied) between the RS-232 port on the OPC FieldServer and the device as shown  
in the connection diagram. Note that the cable labels refer to the Tx and Rx signals on the FS-B-OPC and must be  
connected to the opposite signal on the remote device.  
Remote RS-232 Device  
3.1.1 Connector Pinouts  
Tx Rx GND  
FS-OPC  
Remote Device  
Wire Color  
Signal Pin # Signal Pin #  
Tx  
Green  
Red  
Black  
Tx  
Rx  
GND  
3
2
5
Rx  
Tx  
GND  
8
1
4
Labels refer to  
signal reference  
on FS-B-OPC  
G
x
N
R
D
FS-8917-10  
FS-8917-10  
DB9M on FS-B-OPC  
Figure 3-2: FS-B-OPC Serial RS-232 Connection  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
FS-B-OPC-01 Series FieldServer Start-up Guide  
Page 7 of 10  
3.2 Ethernet Connection  
If connecting to a hub/switch use the provided Cat5 UTP Ethernet cable to connect the FieldServer to the hub. If  
connecting directly to the device, an Ethernet Crossover cable is required (not provided).  
Note that the front USB ports and Compact Flash port are not activated.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
FS-B-OPC-01 Series FieldServer Start-up Guide  
Page 8 of 10  
4
OPERATION  
Read this Start-up Guide in conjunction with the Configuration Manual, the Driver Manual(s) and the Utilities  
manual.  
4.1 Connect and Power the FieldServer.  
Connect the power adapter to a 100 to 240vAC power supply. Ensure that the power supply used complies  
with the specifications provided in Section 2.2  
Power button  
Figure 4-1: View of front of FS-B-OPC-01 Showing Power LED and power button  
Press the Power Button on the front of the FS-B-OPC-01.  
Wait approximately 3-5 minutes for unit to operate.  
4.2 Connect all wiring to unit  
Connect a standard CAT-5 Ethernet cable to the Ethernet port of the FS-B-OPC-01.  
Make appropriate RS232 wiring connections to the RS-232 port of the FS-B-OPC-01. Refer to Section 3 for  
more information.  
4.3 Set the IP Address  
If the FieldServer was not ordered with a Custom Configuration, the IP address is set to automatically update  
from any local DHCP server.  
If no IP address was ordered, then a standard PC monitor, Keyboard, and Mouse must be connected to the  
FS-B-OPC-01 and the IP address set for a normal PC.  
Once the IP address is found or assigned, the configuration of the FST OPC Server Configuration Utility must  
be changed to match that IP address. Please reference the FS-8707-06 manual for more instruction.  
4.4 Change the Configuration File to Meet the Application  
The configuration of the FieldServer is provided to the FieldServer’s operating system via a comma-delimited  
file  
called  
“CONFIG.CSV”  
which  
can  
be  
accessed  
from  
the  
Start|Programs|FieldServerTechnologies|Configuration File folder.  
If ordered with the FieldServer, the custom configuration is installed; (Reference documentation FS-8790-  
XX).  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
FS-B-OPC-01 Series FieldServer Start-up Guide  
Page 9 of 10  
If a custom configuration is not purchased, a template config.csv is loaded on the FieldServer to facilitate  
user configuration of the FieldServer.  
Refer to the Configuration Manual in conjunction with the Driver supplements for information on  
configuring the FieldServer. Note: FieldServer Technologies offers training on this topic as well as a  
configuration service to complete this portion of the work. See www.fieldserver.com for specific details.  
4.5 Run the FieldServer PC Bridge Utility  
If a Custom Configuration was ordered, this software will run automatically and this step can be skipped  
Once the config.csv file is set-up, double click on the FieldServer PC Bridge icon on the desktop to run the  
FieldServer software.  
4.6 Configure the FST OPC Server Configurator to meet the Application  
If a Custom Configuration was ordered this step can be skipped  
If a Custom Configuration was not ordered, please follow the instructions supplied in the FS-8707-06 driver  
manual to configure the OPC Server to connect to the correct Data Arrays.  
The OPC Configurator is installed in c:\program files\FieldServer\FST., there is a shortcut on the desktop and  
it can be found in the start menu under Start|Programs|FST OPC Server for FieldServers.  
4.7 Test and commission the FieldServer  
Connect the FieldServer to the third party device(s), and test the application.  
It may be necessary to connect a standard PC monitor, PC Keyboard and PC Mouse to perform any  
diagnostics or configuration  
If necessary, refer to the Troubleshooting manual which can be found in the FieldServer utilities directory  
under Documentation.  
Before contacting FieldServer technical support, send your config.csv file, and the *.fst file from your FST  
OPC Configurator to [email protected]. In the email, also provide a detailed description of the  
problem(s) occurring on the system.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
FS-B-OPC-01 Series FieldServer Start-up Guide  
Page 10 of 10  
Appendix A. Limited Warranty  
FieldServer Technologies warrants its products to be free from defects in workmanship or material under normal  
use and service for two years after date of shipment. FieldServer Technologies will repair or replace without  
charge any equipment found to be defective during the warranty period. Final determination of the nature and  
responsibility for defective or damaged equipment will be made by FieldServer Technologies personnel.  
All warranties hereunder are contingent upon proper use in the application for which the product was intended  
and do not cover products which have been modified or repaired without FieldServer Technologies approval or  
which have been subjected to accident, improper maintenance, installation or application, or on which original  
identification marks have been removed or altered. This Limited Warranty also will not apply to interconnecting  
cables or wires, consumables or to any damage resulting from battery leakage.  
In all cases FieldServer Technology’s responsibility and liability under this warranty shall be limited to the cost of  
the equipment. The purchaser must obtain shipping instructions for the prepaid return of any item under this  
warranty provision and compliance with such instruction shall be a condition of this warranty.  
Except for the express warranty stated above, FieldServer Technologies disclaims all warranties with regard to the  
products sold hereunder including all implied warranties of merchantability and fitness and the express warranties  
stated herein are in lieu of all obligations or liabilities on the part of FieldServer Technologies for damages  
including, but not limited to, consequential damages arising out of/or in connection with the use or performance  
of the product.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 

EverFocus DVR EMV200 User Manual
Excalibur electronic Board Games NY06 User Manual
FujiFilm Digital Camera 16162434 User Manual
FujiFilm Digital Camera 16309056 User Manual
FujiFilm Photo Printer FL01712 100 User Manual
Fujioh Ventilation Hood BUF 06P User Manual
GE DVR DVR A05 User Manual
Gemini CD Player CDJ 30 User Manual
GE Monogram Beverage Dispenser ZDOD240PSS User Manual
GE Universal Remote GFK 0804B User Manual