FieldServer Computer Drive FS 8700 88 User Manual

A Sierra Monitor Company  
Driver Manual  
(Supplement to the FieldServer Instruction Manual)  
FS-8700-88 Envirotronics SystemsPlus  
APPLICABILITY & EFFECTIVITY  
Effective for all systems manufactured after May 1, 2001  
Driver Version:  
1.02  
Document Revision: 6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Table of Contents  
4.4.39. Map Descriptor Example 36 - stop program .......................................................21  
4.4.40. Map Descriptor Example 37 - stop system .........................................................21  
4.4.41. Map Descriptor Example 38 - alarm reset...........................................................21  
4.4.42. Map Descriptor Example 39 - alarm acknowledge..............................................21  
4.4.43. Map Descriptor Example 40 - edit alarms...........................................................22  
4.4.44. Map Descriptor Example 41 - set circulators = Boolean .....................................22  
4.4.45. Map Descriptor Example 42 - set lights = Boolean .............................................22  
4.4.46. Map Descriptor Example 43 - select program program_num..............................22  
4.4.47. Map Descriptor Example 44 - use keypad = Boolean.........................................23  
4.4.48. Map Descriptor Example 45 - edit program program_num .................................23  
4.4.49. Map Descriptor Example 46 - edit step step_num ..............................................23  
4.4.50. Map Descriptor Example 47 - edit analog channel..............................................23  
4.4.51. Map Descriptor Example 48 - edit fuzzy channel................................................24  
4.4.52. Map Descriptor Example 49 - edit remove step..................................................24  
4.4.53. Map Descriptor Example 50 - edit insert step .....................................................24  
4.4.54. Map Descriptor Example 51 - edit add step........................................................24  
4.4.55. Map Descriptor Example 52 - edit clear program................................................25  
4.4.56. Map Descriptor Example 53 - use emulator mode..............................................25  
4.4.57. Map Descriptor Example 54 - end edit mode......................................................25  
4.4.58. Map Descriptor Example 55 - edit set cycles = num_cycles ...............................25  
4.4.59. Map Descriptor Example 56 - edit set next = next_step_num.............................26  
4.4.60. Map Descriptor Example 57 - edit set analog min. = value.................................26  
4.4.61. Map Descriptor Example 58 - edit set analog max. = value................................26  
4.4.62. Map Descriptor Example 59 - edit set analog type = number..............................26  
4.4.63. Map Descriptor Example 60 - edit set engineering min. = value .........................27  
4.4.64. Map Descriptor Example 61 - edit set engineering max. = value ........................27  
4.4.65. Map Descriptor Example 62 - edit set analog address = number........................27  
4.4.66. Map Descriptor Example 63 - edit set units = number ........................................27  
4.4.67. Map Descriptor Example 64 - edit set fuzzy heat cycles time = value.................28  
4.4.68. Map Descriptor Example 65 - edit set fuzzy cool cycles time = value .................28  
4.4.69. Map Descriptor Example 66 - edit set fuzzy heat sensitivity = value...................28  
4.4.70. Map Descriptor Example 67- edit set fuzzy cool sensitivity = value ....................28  
4.4.71. Map Descriptor Example 68 - edit set fuzzy heat max. power = value................29  
4.4.72. Map Descriptor Example 69 - edit set fuzzy cool max. power = value.................29  
4.4.73. Map Descriptor Example 70 - edit set fuzzy heat min. time = value....................29  
4.4.74. Map Descriptor Example 71 - edit set fuzzy cool min. time = value ....................29  
4.4.75. Map Descriptor Example 72 - edit set fuzzy heat stage delay = value ................30  
4.4.76. Map Descriptor Example 73 - edit set fuzzy cool stage delay = value.................30  
4.4.77. Map Descriptor Example 74 - edit set fuzzy dead band = value .........................30  
4.4.78. Map Descriptor Example 75 - edit set duration = hour:minute:second................31  
4.4.79. Map Descriptor Example 76 - set start time = month/day hour:minute................31  
4.4.80. Map Descriptor Example 77 - set stop time = month/day hour:minute................32  
4.4.81. Map Descriptor Example 78 - set date = month / day / year ...............................32  
4.4.82. Map Descriptor Example 79 - set time = hour:minute:second.............................33  
4.4.83. Map Descriptor Example 80 - edit set setpoint channel = value..........................33  
4.4.84. Map Descriptor Example 80 - edit set gsoak channel = value.............................34  
4.4.85. Map Descriptor Example 81 - edit set gsoak enabled channel = Boolean...........34  
4.4.86. Map Descriptor Example 82 - edit set events = event_list...................................35  
4.4.87. Map Descriptor Example 83 - edit set auxs = aux_list ........................................35  
4.4.88. Map Descriptor Example 84 - edit read program ................................................36  
4.4.89. Map Descriptor Example 85 - edit read step.......................................................36  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Table of Contents  
4.4.90. Map Descriptor Example 86 - edit read number steps........................................36  
4.4.91. Map Descriptor Example 87 - edit read duration.................................................37  
4.4.92. Map Descriptor Example 88 - edit read events...................................................37  
4.4.93. Map Descriptor Example 89 - edit read aux........................................................38  
4.4.94. Map Descriptor Example 90 - edit read cycles....................................................38  
4.4.95. Map Descriptor Example 91 - edit read next.......................................................39  
4.4.96. Map Descriptor Example 92 - edit read analog min. ...........................................39  
4.4.97. Map Descriptor Example 93 - edit read analog max. ..........................................39  
4.4.98. Map Descriptor Example 94 - edit read analog type ...........................................40  
4.4.99. Map Descriptor Example 95 - edit read engineering min. ...................................40  
4.4.100.  
4.4.101.  
4.4.102.  
4.4.103.  
4.4.104.  
4.4.105.  
4.4.106.  
4.4.107.  
4.4.108.  
4.4.109.  
4.4.110.  
4.4.111.  
4.4.112.  
4.4.113.  
4.4.114.  
4.4.115.  
4.4.116.  
4.4.117.  
4.4.118.  
4.4.119.  
Map Descriptor Example 96 - edit read engineering max. ...............................40  
Map Descriptor Example 97 - edit read analog address..................................41  
Map Descriptor Example 98 - edit read units...................................................41  
Map Descriptor Example 99 - edit read fuzzy heat cycle time..........................41  
Map Descriptor Example 100 - edit read fuzzy cool cycle time........................42  
Map Descriptor Example 101 - edit read fuzzy heat sensitivity........................42  
Map Descriptor Example 102 - edit read fuzzy cool sensitivity ........................42  
Map Descriptor Example 103 - edit read fuzzy heat max. power.....................43  
Map Descriptor Example 104 - edit read fuzzy cool max. power .....................43  
Map Descriptor Example 105 - edit read fuzzy heat min. time.........................43  
Map Descriptor Example 106 - edit read fuzzy cool min. time .........................44  
Map Descriptor Example 107 - edit read fuzzy heat stage delay .....................44  
Map Descriptor Example 108 - edit read fuzzy cool stage delay......................44  
Map Descriptor Example 109 - edit read fuzzy dead band ..............................45  
Map Descriptor Example 110 - read alarm log ................................................45  
Map Descriptor Example 111 - edit read setpoint channel...............................45  
Map Descriptor Example 112 - edit read gsoak enabled channel....................46  
Map Descriptor Example 113 - edit read gsoak channel..................................46  
Map Descriptor Example 114 - edit read scan alarm.......................................46  
Map Descriptor Example 115 - edit set scan alarm = Boolean.........................47  
APPENDIX A. PARAMETER TABLES .................................................................................48  
Appendix A.1. System plus data types................................................................................48  
Appendix A.2. Legal System PlusCommands.....................................................................48  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 5 of 49  
1.  
Envirotronics SystemsPlus Description  
The Envirotronics SystemsPlus driver allows the FieldServer to transfer data to and from  
devices over RS-232 using Envirotronics SystemsPlus protocol. The FieldServer can only  
emulate a Client.  
Max Nodes Supported  
FieldServer Mode  
Nodes  
Comments  
Client  
1
Only 1 Client node per port allowed  
The Envirotronics SystemsPlus driver allows for direct interfacing to a SystemsPlus  
Programmer/Controller device. The driver acts as a Client to the device and can be used to  
read and set system parameters for status monitoring and control purposes. Combined with  
other protocol drivers on a FieldServer such as BACNet, complete SystemsPlus monitoring and  
control is made possible via control systems such as Scada.  
The driver is not available as a Server since a FieldServer cannot fully emulate a SystemsPlus  
device’s interfaces. Any existing Server drivers are for FieldServer testing purposes only.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 6 of 49  
2.  
Driver Scope of Supply  
2.1. Supplied by FieldServer Technologies for this driver  
FieldServer Technologies  
PART #  
Description  
FS-8915-10  
FS-8917-02  
FS-8917-01  
FS-8700-88  
UTP cable (7 foot) for RS-232 use  
RJ45 to DB9F connector adapter  
RJ45 to DB25M connection adapter  
Driver Manual.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 7 of 49  
3.  
Hardware Connections  
The FieldServer is connected to the SystemsPlus Controller as shown below.  
Configure the SystemsPlus Controller according to manufacturer’s instructions.  
8917-01 W IRE LIST  
DB25M  
FUNCTION FROM  
TO  
COLOUR  
RX  
CTS  
DSR  
GND  
GND  
DTR  
RTS  
TX  
RJ45-01 DB25M-03 W HITE  
RJ45-02 DB25M-05 BROW N  
RJ45-03  
YELLOW  
RJ45-04 DB25M-07 GREEN  
RJ45-05  
RJ45-06  
RED  
BLACK  
RJ45-07 DB25M-04 ORANGE  
RJ45-08 DB25M-02  
BLUE  
8917-02 W IRE LIST  
DB9F  
FUNCTION FROM  
TO  
COLOUR  
W HITE  
Rx  
GND  
Tx  
RJ45-01 DB9F-03  
RJ45-04 DB9F-05 GREEN  
RJ45-08 DB9F-02  
BLUE  
Envirotronics SystemsPlus  
Controller  
RJ45 Connector  
OR  
(408)-262-2299  
FIELDSERVER  
ENVIROTRONICS  
CONNECTION DIAGRAM  
BASE NAME:  
FILE NAME:  
DATE: 8/30/05  
BY: MC  
Note:  
The SystemsPlus Controller MUST be set to COMMAND MODE using the manufacturer’s  
software before connecting the FieldServer.  
The SystemsPlus Controller’s “Command End of Line” setting MUST be set to “CR”. Using  
the manufacturer’s software to do this setting before connecting the FieldServer  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 8 of 49  
4.  
Configuring the FieldServer as a Envirotronics SystemsPlus Client  
For a detailed discussion on FieldServer configuration, please refer to the FieldServer  
instruction manual. The information that follows describes how to expand upon the factory  
defaults provided in the configuration files included with the FieldServer (See “.csv” sample files  
provided with the FieldServer).  
This section documents and describes the parameters necessary for configuring the FieldServer  
to communicate with an Envirotronics SystemsPlus Server.  
4.1.  
Data Arrays/Descriptors  
The configuration file tells the FieldServer about its interfaces, and the routing of data  
required. In order to enable the FieldServer for Envirotronics SystemsPlus communications,  
the driver independent FieldServer buffers need to be declared in the “Data Arrays” section,  
the destination device addresses need to be declared in the “Client Side Nodes” section,  
and the data required from the Servers needs to be mapped in the “Client Side Map  
Descriptors” section. Details on how to do this can be found below.  
Note that in the tables, * indicates an optional parameter, with the bold legal value being the  
default.  
Section Title  
Data_Arrays  
Column Title  
Function  
Legal Values  
Up to 15 alphanumeric  
characters  
Data_Array_Name Provide name for Data Array  
Float, Bit, UInt16, SInt16,  
Packed_Bit, Byte,  
Packed_Byte,  
Provide data format. Each Data Array  
Data_Array_Format  
can only take on one format.  
Swapped_Byte  
Number of Data Objects. Must be  
larger than the data storage area  
required by the Map Descriptors for the  
Data_Array_Length  
1-10,000  
data being placed in this array.  
Example  
// Data Arrays  
Data_Arrays  
Data_Array_Name,  
Event_States,  
Data_Format,  
bit,  
Data_Array_Length  
10  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 9 of 49  
4.2.  
Client Side Connection Descriptions  
Section Title  
Connections  
Column Title  
Function  
Specify which port the device is connected  
to the FieldServer  
Legal Values  
Port  
P1-P81  
Protocol  
Baud*  
Specify protocol used  
SystemsPlus  
300 – 19200, standard baud  
rates only  
Specify baud rate  
Even, Odd, None  
7, 8  
1, 2  
Parity*  
Data_Bits*  
Stop_Bits*  
Specify parity  
Specify data bits  
Specify stop bits  
RTS, RTS/CTS, None  
0-32000 seconds, 1 second  
Handshaking* Specify hardware handshaking  
Poll _Delay*  
Time between internal polls  
Example  
// Client Side Connections  
Connections  
Port,  
P1,  
Protocol,  
SystemsPlus,  
Baud,  
19200,  
Parity,  
None,  
Handshaking,  
None,  
Poll_Delay  
0.100s  
4.3.  
Client Side Node Descriptors  
Section Title  
Nodes  
Column Title  
Node_Name  
Protocol  
Function  
Provide name for node  
Legal Values  
Up to 32 alphanumeric  
characters  
Specify protocol used  
SystemsPlus  
Specify which port the device is  
connected to the FieldServer  
Port  
P1-P81  
Example  
// Client Side Nodes  
Nodes  
Node_Name,  
SYSPLUS_01,  
Protocol,  
SystemsPlus,  
Port  
P1  
1 Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction  
manual for details of the ports available on specific hardware.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 10 of 49  
4.4.  
4.4.1.  
Client Side Map Descriptors  
FieldServer Related Map Descriptor Parameters  
Column Title  
Function  
Name of this Map  
Descriptor  
Legal Values  
Up to 32 alphanumeric  
characters  
Map_Descriptor_Name  
Name of Data Array where  
data is to be stored in the  
FieldServer  
One of the Data Array names  
from “Data Array” section  
above  
Data_Array_Name  
Starting location in Data  
Array  
Function of Client Map  
Descriptor  
0 to maximum specified in  
“Data Array” section above  
RDBC, WRBC, WRBX, AWT,  
ART2  
Data_Array_Offset  
Function  
4.4.2.  
Driver Related Map Descriptor Parameters  
Column Title  
Function  
Legal Values  
One of the node names  
specified in “Client Node  
Descriptor” above  
Name of Node to fetch data  
from  
Node_Name  
Specifies a SystemsPlus data  
type this mapdesc will use  
SysPlus_Data_Type  
Refer to Appendix A.1  
Any four character alarm  
name  
SysPlus_Alarm_Name  
A SystemsPlus alarm name  
Specifies a SystemsPlus  
command this mapdesc will  
use  
SysPlus_Cmd  
Refer to Appendix A.2  
Name of the data array where  
data must be stored  
Store_Data_Array_Name  
Store_Data_Array_Offset  
Any data array name  
Offset where data must be  
stored  
0 to maximum offset into  
store data array  
Name of the data array that  
will contain parameters  
needed by this mapdesc  
Par_Data_Array_Name  
Par_Data_Array_Offset  
Any data array name  
Offset where parameters will  
be located  
0 to maximum offset into  
parameter data array  
0 to value allowed for the  
specific mapdesc  
1 to value allowed for the  
specific mapdesc  
Address  
Length  
Starting address  
Length of Map Descriptor  
4.4.3.  
Timing Parameters  
Column Title  
Scan_Interval  
Function  
Legal Values  
Rate at which data is polled 0.001s  
2 The new ART function stands for “Active Read on Trigger” and is used to effect a single data  
read per trigger. Please refer to the Map Descriptor examples for using this function.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 11 of 49  
4.4.4.  
Map Descriptor Example 1 - read event event_num  
// Client Side Map Descriptors  
Map Descriptors  
Map_Descriptor_Name, Scan_Interval, Data_Array_Name, Data_Array_Offset, Function, Node_Name,  
SysPlus_Data_Type, Address, Length  
Event_States_00, 0s, Event_States, 0, rdbc, SYSPLUS_01, Event,  
0,  
1
The event_num is specified by the “Address” field. The state of the event will be stored as 1 for “ON” or 0 for “OFF”.  
4.4.5. Map Descriptor Example 2 - set event event_num = Boolean  
// Client Side Map Descriptors  
Map Descriptors  
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name,  
SysPlus_Data_Type, Address, Length  
Event_States_00,  
Event_States_0,  
0,  
awt,  
SYSPLUS_01, Event,  
0,  
1
The event_num is specified by the “Address” field. The Boolean state of the event is retrieved from the value written into  
Data_Array_Name at Data_Array_Offset. Use a value of 1 for “ON” and a value of 0 for “OFF”.  
4.4.6.  
Map Descriptor Example 3 - read aux. aux_num  
// Client Side Map Descriptors  
Map Descriptor  
Map_Descriptor_Name, Scan_Interval, Data_Array_Name, Data_Array_Offset, Function, Node_Name,  
SysPlus_Data_Type, Address, Length  
0,  
Aux_States_00,  
0s,  
Aux_States,  
0,  
rdbc,  
SYSPLUS_01, Aux,  
1
The aux_num is specified by the “Address” field. The state of the aux will be stored as 1 for “ON” or 0 for “OFF”.  
4.4.7. Map Descriptor Example 4 - set aux. aux_num = Boolean  
// Client Side Map Descriptors  
Map Descriptors  
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name,  
SysPlus_Data_Type, Address, Length  
0,  
Aux_States_00,  
Aux_States_0,  
0,  
awt,  
SYSPLUS_01, Aux,  
1
The aux_num is specified by the “Address” field. The Boolean state of the aux is retrieved from the value written into  
Data_Array_Name at Data_Array_Offset. Use a value of 1 for “ON” and a value of 0 for “OFF”.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 12 of 49  
4.4.8.  
Map Descriptor Example 5 - read setpoint channel  
// Client Side Map Descriptors  
Map Descriptors  
Map_Descriptor_Name, Scan_Interval, Data_Array_Name, Data_Array_Offset, Function, Node_Name,  
Setpoints_00, 0s, Setpoints, 0, rdbc, SYSPLUS_01, Setpoint,  
SysPlus_Data_Type, Address, Length  
0,  
1
The channel is specified by the “Address” field.  
4.4.9. Map Descriptor Example 6 - set setpoint channel = value  
// Client Side Map Descriptors  
Map Descriptors  
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name,  
SysPlus_Data_Type, Address, Length  
0,  
Setpoints_00,  
Setpoints_0,  
0,  
awt,  
SYSPLUS_01, Setpoint,  
1
The channel is specified by the “Address” field.  
value is retrieved from the value written into Data_Array_Name at  
Data_Array_Offset.  
4.4.10.  
Map Descriptor Example 7 - read pv channel  
// Client Side Map Descriptors  
Map Descriptors  
Map_Descriptor_Name, Scan_Interval, Data_Array_Name, Data_Array_Offset, Function, Node_Name,  
Pvs_00, 0s, Pvs, 0, rdbc, SYSPLUS_01, Pv,  
SysPlus_Data_Type, Address, Length  
0,  
1
The channel is specified by the “Address” field.  
4.4.11. Map Descriptor Example 8 - read deviation channel  
// Client Side Map Descriptors  
Map Descriptors  
Map_Descriptor_Name, Scan_Interval, Data_Array_Name, Data_Array_Offset, Function, Node_Name,  
SysPlus_Data_Type, Address, Length  
0,  
Deviation_00,  
0s,  
Deviations,  
0,  
rdbc,  
SYSPLUS_01, Deviation,  
1
The channel is specified by the “Address” field.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 13 of 49  
4.4.12.  
Map Descriptor Example 9 - read initial setpoint channel  
// Client Side Map Descriptors  
Map Descriptors  
Map_Descriptor_Name, Scan_Interval, Data_Array_Name, Data_Array_Offset, Function, Node_Name,  
Init_Setpoint_00, 0s, Init_Setpoint, 0, rdbc, SYSPLUS_01, Init_Setpoint,  
SysPlus_Data_Type, Address, Length  
0,  
1
The channel is specified by the “Address” field.  
4.4.13. Map Descriptor Example 10 - set initial setpoint channel = value  
// Client Side Map Descriptors  
Map Descriptors  
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name,  
SysPlus_Data_Type, Address, Length  
0,  
Init_Setpoint_00,  
Init_Setpoint_0,  
0,  
awt,  
SYSPLUS_01, Init_Setpoint,  
1
The channel is specified by the “Address” field; value is retrieved from the value written into Data_Array_Name at Data_Array_Offset.  
4.4.14. Map Descriptor Example 11 - read program status  
// Client Side Map Descriptors  
Map Descriptor  
Map_Descriptor_Name, Scan_Interval, Data_Array_Name, Data_Array_Offset, Function, Node_Name,  
SysPlus_Data_Type, Length  
Prg_Sts,  
0s,  
Prog_Status,  
0,  
rdbc,  
SYSPLUS_01, Prog_Status,  
1
The program status will be stored to Data_Array_Name at Data_Array_Offset with one of the following possible values:  
Program Status VALUE  
0
1
2
3
4
5
6
Undefined  
Timed Start  
Alarm Hold  
Hold  
Run  
Timed Stop  
Stop  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 14 of 49  
4.4.15.  
Map Descriptor Example 12 - read remaining step cycles  
// Client Side Map Descriptors  
// Map Descriptors  
Map_Descriptor_Name, Scan_Interval, Data_Array_Name, Data_Array_Offset, Function, Node_Name,  
SysPlus_Data_Type, Length  
Rm_Stp_Cy, 0s, Rem_Stepcycles, 0, rdbc, SYSPLUS_01, Rem_Step_Cyc,  
1
4.4.16.  
Map Descriptor Example 13 - read selected program  
// Client Side Map Descriptors  
Map Descriptors  
Map_Descriptor_Name,  
Sel_Prog,  
Scan_Interval,  
0s,  
Data_Array_Name,  
Selected_Prog,  
Data_Array_Offset,  
0,  
Function,  
rdbc,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Data_Type,  
Selected_Prog,  
Length  
1
4.4.17.  
Map Descriptor Example 14 - read step number  
// Client Side Map Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Step_Number,  
Scan_Interval,  
0s,  
Data_Array_Name,  
Step_Number,  
Data_Array_Offset,  
0,  
Function,  
rdbc,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Data_Type,  
Step_Number,  
Length  
1
4.4.18.  
Map Descriptor Example 15 - read step time  
// Client Side Map Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Step_Time,  
Scan_Interval,  
0s,  
Data_Array_Name,  
Step_Time,  
Data_Array_Offset,  
0,  
Function,  
rdbc,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Data_Type,  
Step_Time,  
Length  
3
The retrieved step time will be stored as follows in Data_Array_Name:  
Offset from Data_Array_Offset Description  
0
1
2
Hour  
Minute  
Second  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 15 of 49  
4.4.19.  
Map Descriptor Example 16 - read remaining step time  
// Client Side Map Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Rm_Stp_Tm,  
Scan_Interval,  
0s,  
Data_Array_Name,  
Rem_Steptime,  
Data_Array_Offset,  
0,  
Function,  
rdbc,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Data_Type,  
Rem_Step_Tim,  
Length  
3
The retrieved remaining step time will be stored as follows in Data_Array_Name:  
Offset from Data_Array_Offset Description  
0
1
2
Hour  
Minute  
Second  
4.4.20.  
Map Descriptor Example 17 -read start step  
// Client Side Map Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Start_Step,  
Scan_Interval,  
0s,  
Data_Array_Name,  
Start_Step,  
Data_Array_Offset,  
0,  
Function,  
rdbc,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Data_Type,  
Start_Step,  
Length  
1
4.4.21.  
Map Descriptor Example 18 - set start step = step_num  
// Client Side Map Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Start_Step,  
Data_Array_Name,  
Start_Step_0,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Data_Type,  
Start_Step,  
Length  
1
The step_num must be written into Data_Array_Name at Data_Array_Offset to trigger this command.  
4.4.22. Map Descriptor Example 19 - read start time enabled  
// Client Side Map Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Start_Time_Ena,  
Scan_Interval,  
0s,  
Data_Array_Name,  
Start_Time_Ena,  
Data_Array_Offset,  
0,  
Function,  
rdbc,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Data_Type,  
Start_Time_Ena,  
Length  
1
The start time enabled status will be stored as 1 for “Enabled” or 0 for “Disabled” in Data_Array_Name at Data_Array_Offset.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 16 of 49  
4.4.23.  
Map Descriptor Example 20 - set start time enabled = Boolean  
// Client Side Map Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Start_Time_Ena,  
Data_Array_Name,  
Start_Time_Ena_0,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Data_Type,  
Start_Time_Ena,  
Length  
1
A Boolean value of 1 for “Enabled” or 0 for “Disabled” must be written to Data_Array_Name at Data_Array_Offset to trigger this  
command.  
4.4.24.  
Map Descriptor Example 21 - read stop time enabled  
// Client Side Map Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Stop_Time_Ena,  
Scan_Interval,  
0s,  
Data_Array_Name,  
Stop_Time_Ena,  
Data_Array_Offset,  
0,  
Function,  
rdbc,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Data_Type,  
Stop_Time_Ena,  
Length  
1
The stop time enabled status will be stored as 1 for “Enabled” or 0 for “Disabled” in Data_Array_Name at Data_Array_Offset.  
4.4.25. Map Descriptor Example 22 - set stop time enabled = Boolean  
// Client Side Map Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Stop_Time_Ena,  
Data_Array_Name,  
Stop_Time_Ena_0,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Data_Type,  
Stop_Time_Ena,  
Length  
1
A Boolean value of 1 for “Enabled” or 0 for “Disabled” must be written to Data_Array_Name at Data_Array_Offset to trigger this  
command.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 17 of 49  
4.4.26.  
Map Descriptor Example 23 - read start time  
// Client Side Map Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Start_Time,  
Scan_Interval,  
0s,  
Data_Array_Name,  
Start_Time,  
Data_Array_Offset,  
0,  
Function,  
rdbc,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Data_Type,  
Start_Time,  
Length  
4
The retrieved start time will be stored as follows in Data_Array_Name:  
Offset from Data_Array_Offset Description  
0
1
2
3
Month  
Day  
Hour  
Minute  
4.4.27.  
Map Descriptor Example 24 - read stop time  
// Client Side Map Descriptor  
Map Descriptor  
Map_Descriptor_Name,  
Stop_Time,  
Scan_Interval,  
0s,  
Data_Array_Name,  
Stop_Time,  
Data_Array_Offset,  
0,  
Function,  
rdbc,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Data_Type,  
Stop_Time,  
Length  
4
The retrieved stop time will be stored as follows in Data_Array_Name:  
Offset from Data_Array_Offset Description  
Month  
Day  
Hour  
0
1
2
3
Minute  
4.4.28.  
Map Descriptor Example 25 - read audible alarm  
// Client Side Map Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Audible_Alarm,  
Scan_Interval,  
0s,  
Data_Array_Name,  
Audible_Alarm,  
Data_Array_Offset,  
0,  
Function,  
rdbc,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Data_Type,  
Audible_Alarm,  
Length  
1
The status of the audible alarm will be stored as 1 for “on” or 0 for “off” in Data_Array_Name at Data_Array_Offset.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 18 of 49  
4.4.29.  
Map Descriptor Example 26 - set audible alarm = Boolean  
// Client Side Map Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Audible_Alarm,  
Data_Array_Name,  
Audible_Alarm_0,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Data_Type,  
Audible_Alarm,  
Length  
1
A Boolean value of 1 for “on” or 0 for “off” must be written to Data_Array_Name at Data_Array_Offset to trigger this command.  
4.4.30. Map descriptor Example 27 - read software version  
// Cleint Side Map Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Sw_Version,  
Scan_Interval,  
0s,  
Data_Array_Name,  
Sw_Version,  
Data_Array_Offset,  
0,  
Function,  
rdbc,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Data_Type,  
Sw_Version,  
Length  
1
4.4.31.  
Map Descriptor Example 28 - read events  
// Client Side Map Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
All_Event_States,  
Scan_Interval,  
0s,  
Data_Array_Name,  
All_Event_States,  
Data_Array_Offset,  
0,  
Function,  
rdbc,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Data_Type,  
All_Events,  
Length  
10  
The retrieved event states will be stored as follows in Data_Array_Name:  
( A value of 1 will be stored for “on” or 0 for “off” )  
Offset from Data_Array_Offset Description  
0
1
2
..  
9
Event_0 state  
Event_1 state  
Event_2 state  
..  
Event_9 state  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 19 of 49  
4.4.32.  
Map Descriptor Example 29 - read auxs  
// Client Side Map Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
All_Aux_States,  
Scan_Interval,  
0s,  
Data_Array_Name,  
All_Aux_States,  
Data_Array_Offset,  
0,  
Function,  
rdbc,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Data_Type,  
All_Auxs,  
Length  
10  
The retrieved aux states will be stored as follows in Data_Array_Name: (A value of 1 will be stored for “on” or 0 for “off”)  
Offset from Data_Array_Offset Description  
0
1
2
..  
9
Aux_0 state  
Aux_1 state  
Aux_2 state  
..  
Aux_9 state  
4.4.33.  
Map Descriptor Example 30 - read alarm status alarm  
// Client Side Map Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Alarm_Sts_00,  
Scan_Interval,  
0s,  
Data_Array_Name,  
Alarm_Statuses,  
Data_Array_Offset,  
0,  
Function,  
rdbc,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Data_Type,  
Alarm,  
SysPlus_Alarm_Name,  
volt,  
Length  
1
alarm is specified by the name under SysPlus_Alarm_Name. The status of the alarm will be stored as 1 for “OK” or 0 for “FAIL” in  
Data_Array_Name at Data_Array_Offset.  
4.4.34.  
Map Descriptor Example 31 - emergency stop  
// Client Side Map Descriptors  
Map Descriptors  
Map_Descriptor_Name,  
Emergency_Stop,  
Data_Array_Name,  
ProgSysControl,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Emergency_Stop,  
Length  
1
Triggger this command by writing any value to Data_Array_Name at Data_Array_Offset.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 20 of 49  
4.4.35.  
Map Descriptor Example 32 - hold program  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Hold_Program,  
Data_Array_Name,  
ProgSysControl,  
Data_Array_Offset,  
1,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Hold_Program,  
Length  
1
Triggger this command by writing any value to Data_Array_Name at Data_Array_Offset.  
4.4.36. Map Descriptor Example 33 - resume program  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Resume_Program,  
Data_Array_Name,  
ProgSysControl,  
Data_Array_Offset,  
2,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Resume_Program,  
Length  
1
Triggger this command by writing any value to Data_Array_Name at Data_Array_Offset.  
4.4.37. Map Descriptor Example 34 - start program  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Start_Program,  
Data_Array_Name,  
ProgSysControl,  
Data_Array_Offset,  
3,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Start_Program,  
Length  
1
Triggger this command by writing any value to Data_Array_Name at Data_Array_Offset.  
4.4.38. Map Descriptor Example 35 - start system  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Start_System,  
Data_Array_Name,  
ProgSysControl,  
Data_Array_Offset,  
4,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Start_System,  
Length  
1
Triggger this command by writing any value to Data_Array_Name at Data_Array_Offset.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 21 of 49  
4.4.39.  
Map Descriptor Example 36 - stop program  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Stop_Program,  
Data_Array_Name,  
ProgSysControl,  
Data_Array_Offset,  
5,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Stop_Program,  
Length  
1
Triggger this command by writing any value to Data_Array_Name at Data_Array_Offset.  
4.4.40. Map Descriptor Example 37 - stop system  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Stop_System,  
Data_Array_Name,  
ProgSysControl,  
Data_Array_Offset,  
6,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Stop_System,  
Length  
1
Triggger this command by writing any value to Data_Array_Name at Data_Array_Offset.  
4.4.41. Map Descriptor Example 38 - alarm reset  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Alarm_Reset,  
Data_Array_Name,  
AlarmControl,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Alarm_Reset,  
Length  
1
Triggger this command by writing any value to Data_Array_Name at Data_Array_Offset.  
4.4.42. Map Descriptor Example 39 - alarm acknowledge  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Alarm_Ack,  
Data_Array_Name,  
AlarmControl,  
Data_Array_Offset,  
1,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Alarm_Ack,  
Length  
1
Triggger this command by writing any value to Data_Array_Name at Data_Array_Offset.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 22 of 49  
4.4.43.  
Map Descriptor Example 40 - edit alarms  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Edit_Alarms,  
Data_Array_Name,  
Edit_Alarms,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Alarms,  
Length  
1
Triggger this command by writing any value to Data_Array_Name at Data_Array_Offset.  
4.4.44. Map Descriptor Example 41 - set circulators = Boolean  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Set_Circs,  
Data_Array_Name,  
ManualControl,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Set_Circs,  
Length  
1
Write a value of 1 for “on” or 0 for “off” to Data_Array_Name at Data_Array_Offset to trigger this command.  
4.4.45. Map Descriptor Example 42 - set lights = Boolean  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Set_Lights,  
Data_Array_Name,  
ManualControl,  
Data_Array_Offset,  
1,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Set_Lights,  
Length  
1
Write a value of 1 for “on” or 0 for “off” to Data_Array_Name at Data_Array_Offset to trigger this command.  
4.4.46. Map Descriptor Example 43 - select program program_num  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Select_Program,  
Data_Array_Name,  
Program_Num,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Select_Prog,  
Length  
1
A program_num value must be written to Data_Array_Name at Data_Array_Offset to trigger this command.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 23 of 49  
4.4.47.  
Map Descriptor Example 44 - use keypad = Boolean  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Use_Keypad,  
Data_Array_Name,  
Use_Keypad,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Use_Keypad,  
Length  
1
A Boolean value of 1 for “true” or 0 for “false” must be written to Data_Array_Name at Data_Array_Offset to trigger this command.  
4.4.48. Map Descriptor Example 45 - edit program program_num  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Program,  
Data_Array_Name,  
Ed_Program,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Program,  
Length  
1
A program_num value must be written to Data_Array_Name at Data_Array_Offset to trigger this command.  
4.4.49. Map Descriptor Example 46 - edit step step_num  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Step,  
Data_Array_Name,  
Ed_Step,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Step,  
Length  
1
A step_num value must be written to Data_Array_Name at Data_Array_Offset to trigger this command.  
4.4.50. Map Descriptor Example 47 - edit analog channel  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Analog,  
Data_Array_Name,  
Ed_Analog,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Analog,  
Length  
1
A channel value must be written to Data_Array_Name at Data_Array_Offset to trigger this command.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 24 of 49  
4.4.51.  
Map Descriptor Example 48 - edit fuzzy channel  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Fuzzy,  
Data_Array_Name,  
Ed_Fuzzy,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Fuzzy,  
Length  
1
A channel value must be written to Data_Array_Name at Data_Array_Offset to trigger this command.  
4.4.52. Map Descriptor Example 49 - edit remove step  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Remove_Step,  
Data_Array_Name,  
Ed_Remove_Step,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Remove_Step,  
Length  
1
Any value must be written to Data_Array_Name at Data_Array_Offset to trigger this command.  
4.4.53.  
Map Descriptor Example 50 - edit insert step  
Map_Descriptor_Name,  
Ed_Insert_Step,  
Data_Array_Name,  
Ed_Insert_Step,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Insert_Step,  
Length  
1
Any value must be written to Data_Array_Name at Data_Array_Offset to trigger this command.  
4.4.54. Map Descriptor Example 51 - edit add step  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Add_Step,  
Data_Array_Name,  
Ed_Add_Step,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Add_Step,  
Length  
1
Any value must be written to Data_Array_Name at Data_Array_Offset to trigger this command.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 25 of 49  
4.4.55.  
Map Descriptor Example 52 - edit clear program  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Clr_Program,  
Data_Array_Name,  
Ed_Clr_Program,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Clr_Program,  
Length  
1
Any value must be written to Data_Array_Name at Data_Array_Offset to trigger this command.  
4.4.56. Map Descriptor Example 53 - use emulator mode  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Use_Emu_Mode,  
Data_Array_Name,  
Misc_Cmds,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Use_Emu_Mode,  
Length  
1
A value of 1 to use emulator mode or a value of 0 to return to command mode must be written to Data_Array_Name at  
Data_Array_Offset to trigger this command. Note that all driver RDBC function Map Descriptors are stopped when entering emulator  
mode. Map Descriptors will resume polling when returning to command mode.  
4.4.57.  
Map Descriptor Example 54 - end edit mode  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
End_Edit_Mode,  
Data_Array_Name,  
Misc_Cmds,  
Data_Array_Offset,  
1,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
End_Edit_Mode,  
Length  
1
Any value must be written to Data_Array_Name at Data_Array_Offset to trigger this command.  
4.4.58. Map Descriptor Example 55 - edit set cycles = num_cycles  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Set_Cycles,  
Data_Array_Name,  
Ed_Cycles,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Set_Cycles,  
Length  
1
A value of num_cycles must be written to Data_Array_Name at Data_Array_Offset to trigger this command.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 26 of 49  
4.4.59.  
Map Descriptor Example 56 - edit set next = next_step_num  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Set_Next,  
Data_Array_Name,  
Ed_Next,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Set_Next,  
Length  
1
A value of next_step_num must be written to Data_Array_Name at Data_Array_Offset to trigger this command.  
4.4.60. Map Descriptor Example 57 - edit set analog min. = value  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Set_Ana_Min,  
Data_Array_Name,  
Ed_Set_Ana_Min,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Set_Ana_Min,  
Length  
1
A value of value must be written to Data_Array_Name at Data_Array_Offset to trigger this command.  
4.4.61. Map Descriptor Example 58 - edit set analog max. = value  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Set_Ana_Max,  
Data_Array_Name,  
Ed_Set_Ana_Max,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Set_Ana_Max,  
Length  
1
A value of value must be written to Data_Array_Name at Data_Array_Offset to trigger this command.  
4.4.62. Map Descriptor Example 59 - edit set analog type = number  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Set_Ana_Type,  
Data_Array_Name,  
Ed_Set_Ana_Type,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Set_Ana_Type,  
Length  
1
A value of number must be written to Data_Array_Name at Data_Array_Offset to trigger this command.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 27 of 49  
4.4.63.  
Map Descriptor Example 60 - edit set engineering min. = value  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Set_Eng_Min,  
Data_Array_Name,  
Ed_Set_Eng_Min,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Set_Eng_Min,  
Length  
1
A value of value must be written to Data_Array_Name at Data_Array_Offset to trigger this command.  
4.4.64. Map Descriptor Example 61 - edit set engineering max. = value  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Set_Eng_Max,  
Data_Array_Name,  
Ed_Set_Eng_Max,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Set_Eng_Max,  
Length  
1
A value of value must be written to Data_Array_Name at Data_Array_Offset to trigger this command.  
4.4.65. Map Descriptor Example 62 - edit set analog address = number  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Set_Ana_Addr,  
Data_Array_Name,  
Ed_Set_Ana_Addr,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Set_Ana_Addr,  
Length  
1
A value of number must be written to Data_Array_Name at Data_Array_Offset to trigger this command.  
4.4.66. Map Descriptor Example 63 - edit set units = number  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Set_Units,  
Data_Array_Name,  
Ed_Set_Units,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Set_Units,  
Length  
1
A value of number must be written to Data_Array_Name at Data_Array_Offset to trigger this command.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 28 of 49  
4.4.67.  
Map Descriptor Example 64 - edit set fuzzy heat cycles time = value  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Set_Fuz_Hct,  
Data_Array_Name,  
Ed_Set_Fuz_Hct,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Set_Fuz_Hct,  
Length  
1
A value of value must be written to Data_Array_Name at Data_Array_Offset to trigger this command.  
4.4.68. Map Descriptor Example 65 - edit set fuzzy cool cycles time = value  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Set_Fuz_Cct,  
Data_Array_Name,  
Ed_Set_Fuz_Cct,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Set_Fuz_Cct,  
Length  
1
A value of value must be written to Data_Array_Name at Data_Array_Offset to trigger this command.  
4.4.69. Map Descriptor Example 66 - edit set fuzzy heat sensitivity = value  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Set_Fuz_HSens,  
Data_Array_Name,  
Ed_Set_Fuz_HSens,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Set_Fuz_HSens,  
Length  
1
A value of value must be written to Data_Array_Name at Data_Array_Offset to trigger this command.  
4.4.70. Map Descriptor Example 67- edit set fuzzy cool sensitivity = value  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Set_Fuz_CSens,  
Data_Array_Name,  
Ed_Set_Fuz_CSens,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Set_Fuz_CSens,  
Length  
1
A value of value must be written to Data_Array_Name at Data_Array_Offset to trigger this command.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 29 of 49  
4.4.71.  
Map Descriptor Example 68 - edit set fuzzy heat max. power = value  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Set_Fuz_HMPwr,  
Data_Array_Name,  
Ed_Set_Fuz_HMPwr,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Set_Fuz_HMPwr,  
Length  
1
A value of value must be written to Data_Array_Name at Data_Array_Offset to trigger this command.  
4.4.72. Map Descriptor Example 69 - edit set fuzzy cool max. power = value  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Set_Fuz_CMPwr,  
Data_Array_Name,  
Ed_Set_Fuz_CMPwr,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Set_Fuz_CMPwr,  
Length  
1
A value of value must be written to Data_Array_Name at Data_Array_Offset to trigger this command.  
4.4.73. Map Descriptor Example 70 - edit set fuzzy heat min. time = value  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Set_Fuz_HMTim,  
Data_Array_Name,  
Ed_Set_Fuz_HMTim,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Set_Fuz_HMTim,  
Length  
1
A value of value must be written to Data_Array_Name at Data_Array_Offset to trigger this command.  
4.4.74. Map Descriptor Example 71 - edit set fuzzy cool min. time = value  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Set_Fuz_CMTim,  
Data_Array_Name,  
Ed_Set_Fuz_CMTim,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Set_Fuz_CMTim,  
Length  
1
A value of value must be written to Data_Array_Name at Data_Array_Offset to trigger this command.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 30 of 49  
4.4.75.  
Map Descriptor Example 72 - edit set fuzzy heat stage delay = value  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Set_Fuz_HSDly,  
Data_Array_Name,  
Ed_Set_Fuz_HSDly,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Set_Fuz_HSDly,  
Length  
1
A value of value must be written to Data_Array_Name at Data_Array_Offset to trigger this command.  
4.4.76. Map Descriptor Example 73 - edit set fuzzy cool stage delay = value  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Set_Fuz_CSDly,  
Data_Array_Name,  
Ed_Set_Fuz_CSDly,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Set_Fuz_CSDly,  
Length  
1
A value of value must be written to Data_Array_Name at Data_Array_Offset to trigger this command.  
4.4.77. Map Descriptor Example 74 - edit set fuzzy dead band = value  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Set_Fuz_Deadb,  
Data_Array_Name,  
Ed_Set_Fuz_Deadb,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Set_Fuz_Deadb,  
Length  
1
A value of value must be written to Data_Array_Name at Data_Array_Offset to trigger this command.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 31 of 49  
4.4.78.  
// Client Side Mao Descriptors  
Map Descriptor  
Map Descriptor Example 75 - edit set duration = hour:minute:second  
Map_Descriptor_Name,  
Ed_Set_Duration,  
Data_Array_Name,  
Par_Bit_Triggers,  
Data_Array_Offset,  
0,  
Function,  
awt,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Set_Duration,  
Par_Data_Array_Name,  
Ed_Set_Duration,  
Par_Data_Array_Offset,  
0,  
Length  
1
This command is used by first writing the parameter data (hour:minute:second) and then triggering the command by writing any value  
to Data_Array_Name at Data_Array_Offset.  
Parameter data setup:  
Offset from par_data_array_offset Description  
Hour  
Minute  
Second  
0
1
2
4.4.79.  
Map Descriptor Example 76 - set start time = month/day hour:minute  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name,  
Set_Start_Time, Par_Bit_Triggers, 1, awt, SYSPLUS_01, Set_Start_Time, Set_Start_Time,  
SysPlus_Cmd,  
Par_Data_Array_Name, Par_Data_Array_Offset, Length  
0,  
1
This command is used by first writing the parameter data and then triggering the command by writing any value to Data_Array_Name  
at Data_Array_Offset.  
Parameter data setup:  
Offset from par_data_array_offset Description  
Month  
Day  
Hour  
0
1
2
3
Minute  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 32 of 49  
4.4.80.  
Map Descriptor Example 77 - set stop time = month/day hour:minute  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name,  
SysPlus_Cmd,  
Par_Data_Array_Name, Par_Data_Array_Offset, Length  
0,  
Set_Stop_Time,  
Par_Bit_Triggers,  
2,  
awt,  
SYSPLUS_01, Set_Stop_Time, Set_Stop_Time,  
1
This command is used by first writing the parameter data and then triggering the command by writing any value to Data_Array_Name  
at Data_Array_Offset.  
Parameter data setup:  
Offset from par_data_array_offset Description  
Month  
Day  
Hour  
0
1
2
3
Minute  
4.4.81.  
Map Descriptor Example 78 - set date = month / day / year  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name,  
SysPlus_Cmd, Par_Data_Array_Name, Par_Data_Array_Offset, Length  
Set_Date, 0,  
Set_Date,  
Par_Bit_Triggers,  
3,  
awt,  
SYSPLUS_01, Set_Date,  
1
This command is used by first writing the parameter data and then triggering the command by writing any value to Data_Array_Name  
at Data_Array_Offset.  
Parameter data setup:  
Offset from par_data_array_offset Description  
Month  
Day  
Year  
0
1
2
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 33 of 49  
4.4.82.  
Map Descriptor Example 79 - set time = hour:minute:second  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name,  
Set_Time, Par_Bit_Triggers, 4, awt, SYSPLUS_01, Set_Time,  
SysPlus_Cmd, Par_Data_Array_Name, Par_Data_Array_Offset, Length  
Set_Time, 0,  
1
This command is used by first writing the parameter data and then triggering the command by writing any value to Data_Array_Name  
at Data_Array_Offset.  
Parameter data setup:  
Offset from par_data_array_offset Description  
Hour  
Minute  
Second  
0
1
2
4.4.83.  
Map Descriptor Example 80 - edit set setpoint channel = value  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name,  
Ed_Set_Setpoint, Par_Val_Trigger, 0, awt, SYSPLUS_01, Ed_Set_Setpoint, Ed_Set_Setpoint,  
SysPlus_Cmd,  
Par_Data_Array_Name, Par_Data_Array_Offset, Length  
0,  
1
This command is used by first writing the parameter data value and then triggering the command by writing channel to  
Data_Array_Name at Data_Array_Offset.  
Parameter data setup:  
Offset from par_data_array_offset Description  
Value  
0
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 34 of 49  
4.4.84.  
Map Descriptor Example 80 - edit set gsoak channel = value  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name,  
SysPlus_Cmd,  
Par_Data_Array_Name, Par_Data_Array_Offset, Length  
Ed_Set_Gsoak,  
Par_Val_Trigger,  
1,  
awt,  
SYSPLUS_01, Ed_Set_Gsoak, Ed_Set_Gsoak,  
0,  
1
This command is used by first writing the parameter data value and then triggering the command by writing channel to  
Data_Array_Name at Data_Array_Offset.  
Parameter data setup:  
Offset from par_data_array_offset Description  
Value  
0
4.4.85.  
Map Descriptor Example 81 - edit set gsoak enabled channel = Boolean  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name,  
SysPlus_Cmd,  
Par_Data_Array_Name, Par_Data_Array_Offset, Length  
Ed_Set_Gs_Ena,  
Par_Val_Trigger,  
2,  
awt,  
SYSPLUS_01, Ed_Set_Gsoak_Ena, Ed_Set_Gs_Ena,  
0,  
1
This command is used by first writing the parameter data Boolean and then triggering the command by writing channel to  
Data_Array_Name at Data_Array_Offset.  
Parameter data setup:  
Offset from par_data_array_offset Description  
0
Boolean  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 35 of 49  
4.4.86.  
Map Descriptor Example 82 - edit set events = event_list  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name,  
SysPlus_Cmd,  
Par_Data_Array_Name, Par_Data_Array_Offset, Length  
Ed_Set_Events,  
Par_Val_Trigger,  
3,  
awt,  
SYSPLUS_01, Ed_Set_Events, Ed_Set_Events, 0, 10  
This command is used by first writing the parameter data event_list and then triggering the command by writing the number of events  
to Data_Array_Name at Data_Array_Offset.  
Note: Only consecutive events can be set ( eg. to set event9, all 10 events must be set and 10 written to Data_Array_Name ).  
Parameter data setup: (Use a value of 1 for “on” or a value of 0 for “off” per event)  
Offset from par_data_array_offset Description  
Event0  
..  
Event9  
0
..  
9
4.4.87.  
Map Descriptor Example 83 - edit set auxs = aux_list  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name,  
SysPlus_Cmd, Par_Data_Array_Name, Par_Data_Array_Offset, Length  
Ed_Set_Auxs,  
Par_Val_Trigger,  
4,  
awt,  
SYSPLUS_01, Ed_Set_Auxs, Ed_Set_Auxs, 0, 10  
This command is used by first writing the parameter data aux_list and then triggering the command by writing the number of auxs to  
Data_Array_Name at Data_Array_Offset. Note: Only consecutive auxs can be set ( eg. to set aux1, all auxs from 0 to 1 must be set  
and 2 written to Data_Array_Name ).  
Parameter data setup: (Use a value of 1 for “on” or a value of 0 for “off” per aux)  
Offset from par_data_array_offset Description  
Aux0  
..  
Aux9  
0
..  
9
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 36 of 49  
4.4.88.  
Map Descriptor Example 84 - edit read program  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Rd_Program,  
Data_Array_Name,  
Rd_Triggers,  
Data_Array_Offset,  
0,  
Function,  
art,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Rd_Program,  
Store_Data_Array_Name,  
Ed_Rd_Program,  
Store_Data_Array_Offset,  
0,  
Length  
1
This command is triggered by writing any value to Data_Array_Name at Data_Array_Offset.  
The retrieved data is stored as follows:  
Offset from Store_Data_Array_Offset Description  
Program number  
0
4.4.89.  
Map Descriptor Example 85 - edit read step  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Rd_Step,  
Data_Array_Name,  
Rd_Triggers,  
Data_Array_Offset,  
1,  
Function,  
art,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Rd_Step,  
Store_Data_Array_Name,  
Ed_Rd_Step,  
Store_Data_Array_Offset,  
0,  
Length  
1
This command is triggered by writing any value to Data_Array_Name at Data_Array_Offset.  
The retrieved data is stored as follows:  
Offset from Store_Data_Array_Offset Description  
Step number  
0
4.4.90.  
Map Descriptor Example 86 - edit read number steps  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name,  
SysPlus_Cmd,  
Store_Data_Array_Name, Store_Data_Array_Offset, Length  
0,  
Ed_Rd_Num_Steps,  
Rd_Triggers,  
2,  
art,  
SYSPLUS_01, Ed_Rd_Num_Steps, Ed_Rd_Num_Steps,  
1
This command is triggered by writing any value to Data_Array_Name at Data_Array_Offset.  
The retrieved data is stored as follows:  
Offset from Store_Data_Array_Offset Description  
Number of steps  
0
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 37 of 49  
4.4.91.  
Map Descriptor Example 87 - edit read duration  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Rd_Duration,  
Data_Array_Name,  
Rd_Triggers,  
Data_Array_Offset,  
3,  
Function,  
art,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Rd_Duration,  
Store_Data_Array_Name,  
Ed_Rd_Duration,  
Store_Data_Array_Offset,  
0,  
Length  
1
This command is triggered by writing any value to Data_Array_Name at Data_Array_Offset.  
The retrieved data is stored as follows:  
Offset from Store_Data_Array_Offset Description  
Duration  
0
4.4.92.  
Map Descriptor Example 88 - edit read events  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Rd_Events,  
Data_Array_Name,  
Rd_Triggers,  
Data_Array_Offset,  
4,  
Function,  
art,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Rd_Events,  
Store_Data_Array_Name,  
Ed_Rd_Events,  
Store_Data_Array_Offset,  
0,  
Length  
1
This command is triggered by writing any value to Data_Array_Name at Data_Array_Offset.  
The retrieved data is stored as follows:  
Offset from Store_Data_Array_Offset Description  
Event0 status  
..  
Event9 status  
0
..  
9
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 38 of 49  
4.4.93.  
Map Descriptor Example 89 - edit read aux.  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name,  
SysPlus_Cmd, Store_Data_Array_Name, Store_Data_Array_Offset, Length  
Ed_Rd_Aux,  
Rd_Triggers,  
5,  
art,  
SYSPLUS_01, Ed_Rd_Aux,  
Ed_Rd_Aux,  
0,  
1
This command is triggered by writing any value to Data_Array_Name at Data_Array_Offset.  
The retrieved data is stored as follows:  
Offset from Store_Data_Array_Offset Description  
Aux0 status  
..  
Aux9 status  
0
..  
9
4.4.94.  
Map Descriptor Example 90 - edit read cycles  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Rd_Cycles,  
Data_Array_Name,  
Rd_Triggers,  
Data_Array_Offset,  
6,  
Function,  
art,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Rd_Cycles,  
Store_Data_Array_Name,  
Ed_Rd_Cycles,  
Store_Data_Array_Offset,  
0,  
Length  
1
This command is triggered by writing any value to Data_Array_Name at Data_Array_Offset.  
The retrieved data is stored as follows:  
Offset from Store_Data_Array_Offset Description  
Number of cycles  
0
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 39 of 49  
4.4.95.  
Map Descriptor Example 91 - edit read next  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Rd_Next,  
Data_Array_Name,  
Rd_Triggers,  
Data_Array_Offset,  
7,  
Function,  
art,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Rd_Next,  
Store_Data_Array_Name,  
Ed_Rd_Next,  
Store_Data_Array_Offset,  
0,  
Length  
1
This command is triggered by writing any value to Data_Array_Name at Data_Array_Offset.  
The retrieved data is stored as follows:  
Offset from Store_Data_Array_Offset Description  
Next  
0
4.4.96.  
Map Descriptor Example 92 - edit read analog min.  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Rd_Ana_Min,  
Data_Array_Name,  
Rd_Triggers,  
Data_Array_Offset,  
8,  
Function,  
art,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Rd_Ana_Min,  
Store_Data_Array_Name,  
Ed_Rd_Ana_Min,  
Store_Data_Array_Offset,  
0,  
Length  
1
This command is triggered by writing any value to Data_Array_Name at Data_Array_Offset.  
The retrieved data is stored as follows:  
Offset from Store_Data_Array_Offset Description  
Min analog value  
0
4.4.97.  
Map Descriptor Example 93 - edit read analog max.  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Rd_Ana_Max,  
Data_Array_Name,  
Rd_Triggers,  
Data_Array_Offset,  
9,  
Function,  
art,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Rd_Ana_Max,  
Store_Data_Array_Name,  
Ed_Rd_Ana_Max,  
Store_Data_Array_Offset,  
0,  
Length  
1
This command is triggered by writing any value to Data_Array_Name at Data_Array_Offset.  
The retrieved data is stored as follows:  
Offset from Store_Data_Array_Offset Description  
Max analog value  
0
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 40 of 49  
4.4.98.  
Map Descriptor Example 94 - edit read analog type  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Rd_Ana_Type,  
Data_Array_Name,  
Rd_Triggers,  
Data_Array_Offset,  
10,  
Function,  
art,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Rd_Ana_Type,  
Store_Data_Array_Name,  
Ed_Rd_Ana_Type,  
Store_Data_Array_Offset,  
0,  
Length  
1
This command is triggered by writing any value to Data_Array_Name at Data_Array_Offset.  
The retrieved data is stored as follows:  
Offset from Store_Data_Array_Offset Description  
0
Analog type  
4.4.99.  
Map Descriptor Example 95 - edit read engineering min.  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Rd_Eng_Min,  
Data_Array_Name,  
Rd_Triggers,  
Data_Array_Offset,  
11,  
Function,  
art,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Rd_Eng_Min,  
Store_Data_Array_Name,  
Ed_Rd_Eng_Min,  
Store_Data_Array_Offset,  
0,  
Length  
1
This command is triggered by writing any value to Data_Array_Name at Data_Array_Offset.  
The retrieved data is stored as follows:  
Offset from Store_Data_Array_Offset Description  
0
Min engineering value  
4.4.100.  
Map Descriptor Example 96 - edit read engineering max.  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Rd_Eng_Max,  
Data_Array_Name,  
Rd_Triggers,  
Data_Array_Offset,  
12,  
Function,  
art,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Rd_Eng_Max,  
Store_Data_Array_Name,  
Ed_Rd_Eng_Max,  
Store_Data_Array_Offset,  
0,  
Length  
1
This command is triggered by writing any value to Data_Array_Name at Data_Array_Offset.  
The retrieved data is stored as follows:  
Offset from Store_Data_Array_Offset Description  
0
Max engineering value  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 41 of 49  
4.4.101.  
// Client Side Mao Descriptors  
Map Descriptor  
Map Descriptor Example 97 - edit read analog address  
Map_Descriptor_Name,  
Ed_Rd_Ana_Addr,  
Data_Array_Name,  
Rd_Triggers,  
Data_Array_Offset,  
13,  
Function,  
art,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Rd_Ana_Addr,  
Store_Data_Array_Name,  
Ed_Rd_Ana_Addr,  
Store_Data_Array_Offset,  
0,  
Length  
1
This command is triggered by writing any value to Data_Array_Name at Data_Array_Offset.  
The retrieved data is stored as follows:  
Offset from Store_Data_Array_Offset Description  
0
Analog address  
4.4.102.  
Map Descriptor Example 98 - edit read units  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Rd_Units,  
Data_Array_Name,  
Rd_Triggers,  
Data_Array_Offset,  
14,  
Function,  
art,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Rd_Units,  
Store_Data_Array_Name,  
Ed_Rd_Units,  
Store_Data_Array_Offset,  
0,  
Length  
1
This command is triggered by writing any value to Data_Array_Name at Data_Array_Offset.  
The retrieved data is stored as follows:  
Offset from Store_Data_Array_Offset Description  
0
Units value  
4.4.103.  
Map Descriptor Example 99 - edit read fuzzy heat cycle time  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Rd_Fuz_Hct,  
Data_Array_Name,  
Rd_Triggers,  
Data_Array_Offset,  
15,  
Function,  
art,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Rd_Fuz_Hct,  
Store_Data_Array_Name,  
Ed_Rd_Fuz_Hct,  
Store_Data_Array_Offset,  
0,  
Length  
1
This command is triggered by writing any value to Data_Array_Name at Data_Array_Offset.  
The retrieved data is stored as follows:  
Offset from Store_Data_Array_Offset Description  
0
Heat cycle time  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 42 of 49  
4.4.104.  
Map Descriptor Example 100 - edit read fuzzy cool cycle time  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Rd_Fuz_Cct,  
Data_Array_Name,  
Rd_Triggers,  
Data_Array_Offset,  
16,  
Function,  
art,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Rd_Fuz_Cct,  
Store_Data_Array_Name,  
Ed_Rd_Fuz_Cct,  
Store_Data_Array_Offset,  
0,  
Length  
1
This command is triggered by writing any value to Data_Array_Name at Data_Array_Offset.  
The retrieved data is stored as follows:  
Offset from Store_Data_Array_Offset Description  
0
Cool cycle time  
4.4.105.  
Map Descriptor Example 101 - edit read fuzzy heat sensitivity  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name,  
SysPlus_Cmd,  
Store_Data_Array_Name, Store_Data_Array_Offset, Length  
0,  
Ed_Rd_Fuz_HSens,  
Rd_Triggers,  
17,  
art,  
SYSPLUS_01, Ed_Rd_Fuz_HSens, Ed_Rd_Fuz_HSens,  
1
This command is triggered by writing any value to Data_Array_Name at Data_Array_Offset.  
The retrieved data is stored as follows:  
Offset from Store_Data_Array_Offset Description  
0
Heat sensitivity  
4.4.106.  
Map Descriptor Example 102 - edit read fuzzy cool sensitivity  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name,  
SysPlus_Cmd,  
Store_Data_Array_Name, Store_Data_Array_Offset, Length  
0,  
Ed_Rd_Fuz_CSens,  
Rd_Triggers,  
18,  
art,  
SYSPLUS_01, Ed_Rd_Fuz_CSens, Ed_Rd_Fuz_CSens,  
1
This command is triggered by writing any value to Data_Array_Name at Data_Array_Offset.  
The retrieved data is stored as follows:  
Offset from Store_Data_Array_Offset Description  
0
Cool sensitivity  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 43 of 49  
4.4.107.  
Map Descriptor Example 103 - edit read fuzzy heat max. power  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name,  
SysPlus_Cmd,  
Store_Data_Array_Name, Store_Data_Array_Offset, Length  
0,  
Ed_Rd_Fuz_HMPwr,  
Rd_Triggers,  
19,  
art,  
SYSPLUS_01, Ed_Rd_Fuz_HMPwr, Ed_Rd_Fuz_HMPwr,  
1
This command is triggered by writing any value to Data_Array_Name at Data_Array_Offset.  
The retrieved data is stored as follows:  
Offset from Store_Data_Array_Offset Description  
0
Max heat power  
4.4.108.  
Map Descriptor Example 104 - edit read fuzzy cool max. power  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name,  
SysPlus_Cmd,  
Store_Data_Array_Name, Store_Data_Array_Offset, Length  
0,  
Ed_Rd_Fuz_CMPwr,  
Rd_Triggers,  
20,  
art,  
SYSPLUS_01, Ed_Rd_Fuz_CMPwr, Ed_Rd_Fuz_CMPwr,  
1
This command is triggered by writing any value to Data_Array_Name at Data_Array_Offset.  
The retrieved data is stored as follows:  
Offset from Store_Data_Array_Offset Description  
0
Max cool power  
4.4.109.  
Map Descriptor Example 105 - edit read fuzzy heat min. time  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name,  
SysPlus_Cmd,  
Store_Data_Array_Name, Store_Data_Array_Offset, Length  
0,  
Ed_Rd_Fuz_HMTim,  
Rd_Triggers,  
21,  
art,  
SYSPLUS_01, Ed_Rd_Fuz_HMTim, Ed_Rd_Fuz_HMTim,  
1
This command is triggered by writing any value to Data_Array_Name at Data_Array_Offset.  
The retrieved data is stored as follows:  
Offset from Store_Data_Array_Offset Description  
0
Min heat time  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 44 of 49  
4.4.110.  
Map Descriptor Example 106 - edit read fuzzy cool min. time  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name,  
SysPlus_Cmd,  
Store_Data_Array_Name, Store_Data_Array_Offset, Length  
0,  
Ed_Rd_Fuz_CMTim,  
Rd_Triggers,  
22,  
art,  
SYSPLUS_01, Ed_Rd_Fuz_CMTim, Ed_Rd_Fuz_CMTim,  
1
This command is triggered by writing any value to Data_Array_Name at Data_Array_Offset.  
The retrieved data is stored as follows:  
Offset from Store_Data_Array_Offset Description  
0
Min cool time  
4.4.111.  
Map Descriptor Example 107 - edit read fuzzy heat stage delay  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name,  
SysPlus_Cmd,  
Store_Data_Array_Name, Store_Data_Array_Offset, Length  
0,  
Ed_Rd_Fuz_HSDly,  
Rd_Triggers,  
23,  
art,  
SYSPLUS_01, Ed_Rd_Fuz_HSDly, Ed_Rd_Fuz_HSDly,  
1
This command is triggered by writing any value to Data_Array_Name at Data_Array_Offset.  
The retrieved data is stored as follows:  
Offset from Store_Data_Array_Offset Description  
0
Heat stage delay  
4.4.112.  
Map Descriptor Example 108 - edit read fuzzy cool stage delay  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name,  
SysPlus_Cmd,  
Store_Data_Array_Name, Store_Data_Array_Offset, Length  
0,  
Ed_Rd_Fuz_CSDly,  
Rd_Triggers,  
24,  
art,  
SYSPLUS_01, Ed_Rd_Fuz_CSDly, Ed_Rd_Fuz_CSDly,  
1
This command is triggered by writing any value to Data_Array_Name at Data_Array_Offset.  
The retrieved data is stored as follows:  
Offset from Store_Data_Array_Offset Description  
0
Cool stage delay  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 45 of 49  
4.4.113.  
Map Descriptor Example 109 - edit read fuzzy dead band  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name,  
SysPlus_Cmd,  
Store_Data_Array_Name, Store_Data_Array_Offset, Length  
Ed_Rd_Fuz_Deadb,  
Rd_Triggers,  
25,  
art,  
SYSPLUS_01, Ed_Rd_Fuz_Deadb, Ed_Rd_Fuz_Deadb,  
0,  
1
This command is triggered by writing any value to Data_Array_Name at Data_Array_Offset.  
The retrieved data is stored as follows:  
Offset from Store_Data_Array_Offset Description  
0
Dead band  
4.4.114.  
Map Descriptor Example 110 - read alarm log  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Rd_Alarm_Log,  
Data_Array_Name,  
Rd_Triggers,  
Data_Array_Offset,  
26,  
Function,  
art,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Rd_Alarm_Log,  
Store_Data_Array_Name,  
Rd_Alarm_Log,  
Store_Data_Array_Offset,  
0,  
Length  
1
This command is triggered by writing any value to Data_Array_Name at Data_Array_Offset.  
The retrieved data is stored as follows:  
Offset from Store_Data_Array_Offset Description  
0
To be determined !  
4.4.115.  
Map Descriptor Example 111 - edit read setpoint channel  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Rd_Setpoint,  
Data_Array_Name,  
Rd_Par_Triggers,  
Data_Array_Offset,  
0,  
Function,  
art,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Rd_Setpoint,  
Store_Data_Array_Name,  
Ed_Rd_Setpoint,  
Store_Data_Array_Offset,  
0,  
Length  
1
This command is triggered by writing channel to Data_Array_Name at Data_Array_Offset.  
The retrieved data is stored as follows:  
Offset from Store_Data_Array_Offset Description  
0
Setpoint  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 46 of 49  
4.4.116.  
Map Descriptor Example 112 - edit read gsoak enabled channel  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_Name,  
SysPlus_Cmd,  
Store_Data_Array_Name, Store_Data_Array_Offset, Length  
Ed_Rd_Gsoak_Ena,  
Rd_Par_Triggers,  
1,  
art,  
SYSPLUS_01, Ed_Rd_Gsoak_Ena, Ed_Rd_Gsoak_Ena,  
0,  
1
This command is triggered by writing channel to Data_Array_Name at Data_Array_Offset.  
The retrieved data is stored as follows: ( A value of 1 is used for “true” or 0 for “false” )  
Offset from Store_Data_Array_Offset Description  
0
Gsoak enabled  
4.4.117.  
Map Descriptor Example 113 - edit read gsoak channel  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Rd_Gsoak,  
Data_Array_Name,  
Rd_Par_Triggers,  
Data_Array_Offset,  
2,  
Function,  
art,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Rd_Gsoak,  
Store_Data_Array_Name,  
Ed_Rd_Gsoak,  
Store_Data_Array_Offset,  
0,  
Length  
1
This command is triggered by writing channel to Data_Array_Name at Data_Array_Offset.  
The retrieved data is stored as follows:  
Offset from Store_Data_Array_Offset Description  
0
Gsoak value  
4.4.118.  
Map Descriptor Example 114 - edit read scan alarm  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Rd_Scan_00,  
Data_Array_Name,  
Scan_Alm_Trigs,  
Data_Array_Offset,  
0,  
Function,  
art,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Rd_Scan,  
SysPlus_Alarm_Name,  
fire,  
Store_Data_Array_Name,  
Ed_Rd_Scan,  
Store_Data_Array_Offset,  
0,  
Length  
1
This command is triggered by writing any value to Data_Array_Name at Data_Array_Offset.  
The retrieved data is stored as follows: ( A value of 1 is stored for “Fail” or 0 for “Normal” )  
Offset from Store_Data_Array_Offset Description  
0
Alarm status  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 47 of 49  
4.4.119.  
Map Descriptor Example 115 - edit set scan alarm = Boolean  
// Client Side Mao Descriptors  
Map Descriptor  
Map_Descriptor_Name,  
Ed_Set_Scan_00,  
Data_Array_Name,  
Set_Scan_Trig,  
Data_Array_Offset,  
0,  
Function,  
wrbx,  
Node_Name,  
SYSPLUS_01,  
SysPlus_Cmd,  
Ed_Set_Scan,  
SysPlus_Alarm_Name,  
fire,  
Length  
1
This command is triggered by writing a Boolean value to Data_Array_Name at Data_Array_Offset.  
A value of 1 is used for “true” or 0 for “false”.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 48 of 49  
Appendix A. Parameter Tables  
Appendix A.1. System plus data types  
Event  
Aux  
Setpoint  
Pv  
Deviation  
Init_Setpoint  
Selected_Prog  
Rem_Step_Tim  
Stop_Time_Ena  
Audible_Alarm  
All_Auxs  
Prog_Status  
Step_Number  
Start_Step  
Start_Time  
Sw_Version  
Alarm  
Rem_Step_Cyc  
Step_Time  
Start_Time_Ena  
Stop_Time  
All_Events  
Appendix A.2. Legal System PlusCommands  
Ed_Rd_Program  
Ed_Rd_Duration  
Ed_Rd_Cycles  
Ed_Rd_Ana_Max  
Ed_Rd_Eng_Max  
Ed_Rd_Fuz_Hct  
Ed_Rd_Fuz_CSens  
Ed_Rd_Fuz_HMTim  
Ed_Rd_Fuz_CSDly  
Ed_Rd_Setpoint  
Ed_Rd_Scan  
Ed_Rd_Step  
Ed_Rd_Num_Steps  
Ed_Rd_Aux  
Ed_Rd_Events  
Ed_Rd_Next  
Ed_Rd_Ana_Min  
Ed_Rd_Eng_Min  
Ed_Rd_Units  
Ed_Rd_Ana_Type  
Ed_Rd_Ana_Addr  
Ed_Rd_Fuz_Cct  
Ed_Rd_Fuz_HMPwr  
Ed_Rd_Fuz_CMTim  
Ed_Rd_Fuz_Deadb  
Ed_Rd_Gsoak_Ena  
Emergency_Stop  
Start_Program  
Ed_Rd_Fuz_HSens  
Ed_Rd_Fuz_CMPwr  
Ed_Rd_Fuz_HSDly  
Rd_Alarm_Log  
Ed_Rd_Gsoak  
Hold_Program  
Resume_Program  
Stop_Program  
Start_System  
Stop_System  
Alarm_Reset  
Alarm_Ack  
Ed_Alarms  
Set_Circs  
Set_Lights  
Select_Prog  
Use_Keypad  
Ed_Program  
Ed_Step  
Ed_Analog  
Ed_Fuzzy  
Ed_Remove_Step  
Ed_Clr_Program  
Ed_Set_Next  
Ed_Insert_Step  
Use_Emu_Mode  
Ed_Set_Ana_Min  
Ed_Set_Eng_Min  
Ed_Set_Units  
Ed_Add_Step  
Ed_Set_Cycles  
Ed_Set_Ana_Max  
Ed_Set_Eng_Max  
Ed_Set_Fuz_Hct  
Ed_Set_Fuz_CSens  
Ed_Set_Fuz_HMTim  
Ed_Set_Fuz_CSDly  
Ed_Set_Duration  
Set_Date  
Ed_Set_Ana_Type  
Ed_Set_Ana_Addr  
Ed_Set_Fuz_Cct  
Ed_Set_Fuz_HMPwr  
Ed_Set_Fuz_CMTim  
Ed_Set_Fuz_Deadb  
Set_Start_Time  
Set_Time  
Ed_Set_Fuz_HSens  
Ed_Set_Fuz_CMPwr  
Ed_Set_Fuz_HSDly  
Ed_Set_Scan  
Set_Stop_Time  
Ed_Set_Setpoint  
Ed_Set_Events  
Ed_Set_Gsoak  
Ed_Set_Auxs  
Ed_Set_Gsoak_Ena  
End_Edit_Mode  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-88 Envirotronics SystemsPlus  
Page 49 of 49  
THIS PAGE INTENTIONALLY LEFT BLANK  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Echo Trimmer GT 225 User Manual
Edelbrock Automobile Parts 1727 User Manual
Edelbrock Automobile Parts Blazer User Manual
Electro Voice Portable Speaker EVM 12L User Manual
Extron electronic Stereo Amplifier 246 03 User Manual
FireplaceXtrordinair Indoor Fireplace 36A BI User Manual
Frigidaire Food Warmer 318201822 User Manual
Gateway Personal Computer E 6100 User Manual
GE Convection Oven PT7050 User Manual
Goodman Mfg Heat Pump SSZ 14 SEER User Manual