Field Controls Furnace MPL B User Manual

Installation, Operation and  
Maintenance Manual  
Oil Fired Warm Air Furnaces  
WML-C AND MPL-B  
(Down-Flow or Horizontal Model)  
ALL INSTALLATIONS MUST MEET ALL  
LOCAL, PROVINCIAL/STATE, AND  
FEDERAL CODES WHICH MAY  
DIFFER FROM THIS MANUAL  
ECR International Limited  
OLSEN Division  
Read this complete manual before  
beginning installation. These  
instructions must be kept with the  
furnace for future reference.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
enable proper sizing of the trunk and  
branch ductwork. In retrofit applications,  
a
building shell (overall) heat loss  
IMPROPER  
INSTALLATION  
MAY  
DO  
NOT  
USE  
GASOLINE,  
calculation may be used.  
CREATE A CONDITION WHERE THE  
OPERATION OF THE PRODUCT  
COULD CAUSE PERSONAL INJURY  
OR PROPERTY DAMAGE.  
CRANKCASE OIL, OR ANY OTHER  
OIL CONTAINING GASOLINE AS A  
FUEL FOR THIS FURNACE.  
In the United States, Manual J. titled,  
"Load Calculation" published by the Air  
Conditioning Contractors of America,  
(ACCA), describes a suitable procedure  
for calculating the maximum hourly heat  
loss.  
INTRODUCTION  
IMPROPER  
ADJUSTMENT,  
INSTALLATION,  
ALTERATION,  
Please  
read  
these  
instructions  
completely and carefully before installing  
and operating the furnace.  
SERVICE OR MAINTENANCE CAN  
CAUSE INJURY OR PROPERTY  
DAMAGE. REFER TO THIS MANUAL  
FOR ASSISTANCE OR ADDITIONAL  
In Canada, the maximum hourly heat  
loss may be calculated in accordance  
with the procedures described in the  
manuals of the Heating, Refrigeration  
and Air Conditioning Institute (HRAI), or  
by other method prescribed by  
authorities having jurisdiction that are  
suitable for local conditions.  
The furnace must be installed and set up  
by a qualified contractor.  
INFORMATION,  
CONSULT  
A
QUALIFIED INSTALLER, SERVICE  
AGENCY OR THE FUEL SUPPLIER.  
Model WML-C is an oil fired forced air  
multi-positional furnace, with an output  
capacity range of 58,000 BTU/Hr. to  
85,600 BTU/Hr. The MPL-B is also an oil  
fired forced air multi-positional furnace  
with an output capacity range of 85,500  
BTU/Hr. to 123,000 BTU/Hr. The WML-  
C AND MPL-B furnace may be installed  
in the down-flow position, as well as both  
left and right horizontal positions.  
LOCATION OF UNIT  
The furnace should be located such that  
the flue connection to the chimney is  
short, direct and consists of as few  
elbows as possible. When possible, the  
unit should be centralized with respect to  
the supply and return air ductwork. A  
central location minimizes the trunk duct  
sizing. All models may be installed on  
combustible floors. Do not install the  
furnace on carpet or tiled floors.  
THIS PRODUCT MUST BE INSTALLED  
IN STRICT COMPLIANCE WITH THESE  
INSTALLATION INSTRUCTIONS AND  
ANY APPLICABLE LOCAL, STATE,  
AND NATIONAL CODES INCLUDING  
BUT NOT LIMITED TO: BUILDING,  
All models are listed with the Canadian  
Standards Association, (CSA), and  
comply with the standards of both the  
United States and Canada for use with  
No. 1 (Stove) and No. 2 (Furnace) Oil.  
ELECTRICAL  
CODES.  
AND  
MECHANICAL  
In the United States, the installation of  
the furnace and related equipment shall  
be installed in accordance with the  
regulations of NFPA No. 31, Installation  
of Oil Burning Equipment, as well as in  
accordance with local codes.  
Minimum installation clearances are  
listed in Table 1.  
NOTE: The recommended installation  
clearances do not necessarily take into  
consideration the clearances necessary  
to replace the air filter or perform other  
routine maintenance.  
The furnace area must not be used as a  
broom closet or for any other storage  
purposes, as a fire hazard may be  
created. Never store items such as the  
following on, near or in contact with the  
furnace:  
In Canada, the installation of the furnace  
and related equipment shall be installed  
in accordance with the regulations of  
CAN/CSA - B139, Installation Code For  
Oil Burning Equipment, as well as in  
accordance with local codes.  
DOWN-FLOW INSTALLATION  
All WML-C AND MPL-B furnace models  
have been assembled for installation in  
the down-flow position. Maintain all  
clearances to combustibles as outlined in  
Table 1. Suggestion; as a measure to  
prevent fuel oil from accumulating in  
locations other than the fire pot, as could  
be the case in the event of nozzle drip,  
install the furnace with an approximate 2  
degree slope from the oil burner casing  
towards the fire pot. Use shims made of  
noncombustible material.  
1. Spray or aerosol cans, rags,  
brooms,  
dust  
mops,  
vacuum  
cleaners or other cleaning tools.  
When  
questions arise, regulations prescribed in  
the National Codes and Local  
installation  
or  
application  
2. Soap powders, bleaches, waxes or  
other cleaning compounds; plastic  
items or containers, gasoline,  
kerosene, cigarette lighter fluid, dry  
cleaning fluids, or other volatile  
fluids.  
Regulations take precedence over the  
general instructions provided with this  
installation manual. When in doubt,  
please consult your local authorities.  
All models are shipped assembled and  
pre-wired. The furnace should be  
carefully inspected for damage when  
being unpacked.  
3. Paint thinners or other painting  
materials and compounds.  
4. Paper bags, boxes, or other paper  
or cardboard products.  
HEAT LOSS  
Never operate the furnace with the  
blower door removed. To do so could  
result in serious personal injury and/or  
equipment damage.  
To determine the correct furnace and  
firing rate for an application, it is  
necessary to calculate the maximum  
hourly heat loss of the building based on  
local design conditions. In new  
construction, the heat loss should be  
calculated on a room-by-room basis to  
30318 R4 9/9/2005  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
HORIZONTAL INSTALLATION  
Table 1: Clearance to Combustibles  
WML-C AND MPL-B furnaces models  
are assembled and shipped ready for  
installation in the down-flow position. The  
furnace may be installed in either of the  
WML-C  
MPL-B  
Furnace  
Location  
Top  
Down flow Horizontal Down flow Horizontal  
0 in.  
1 in.  
3 in.  
1 in.  
0 in.  
1 in.  
3 in.  
1 in.  
horizontal  
positions;  
warm  
air  
discharging left or warm air-discharging  
right by following these steps:  
Bottom  
S/A Plenum  
Rear  
1 in.  
1 in.  
1 in.  
1 in.  
1. Rotate the furnace 90° to the  
desired position.  
1 in.  
1 in.  
1 in.  
1 in.  
Sides  
1 in.  
1 in.  
1 in.  
1 in.  
2. Remove the three nut and washer  
sets fastening the oil burner  
assembly to the furnace. Rotate the  
oil burner assembly to be in the  
normal upright position.  
Front  
10 in.1  
9 in. 2  
Closet  
10 in.1  
9 in. 2  
Closet  
10 in.1  
9 in. 2  
Closet  
10 in.1  
9 in. 2  
Closet  
Flue Pipe  
Enclosure  
3. Re-align the oil burner assembly to  
the combustion chamber (fire-pot),  
and then secure into place with the  
three nut and washer sets.  
1 24 inches is required for servicing.  
2 18 inches required in the United States.  
shims made of noncombustible material.  
of nozzle drip, install the furnace with an  
approximate 2 degree slope from the oil  
burner casing towards the fire pot.  
NON-SUSPENDED INSTALLATION  
SUSPENDED INSTALLATION  
Maintain clearances to combustibles as  
outlined in Table 1. Installation on a  
combustible floor requires a clearance of  
1 inch. This can be done by using a  
noncombustible material such as one-  
inch thick channel iron or similar  
material. The furnace must be supported  
in such a way as to not allow twisting or  
sagging of the cabinet. Suggestion; as a  
measure to prevent fuel oil from  
accumulating in locations other than the  
fire pot, as could be the case in the event  
of nozzle drip, install the furnace with an  
approximate 2-degree slope from the oil  
burner casing towards the fire pot. Use  
Refer to Figure 1. Maintain clearances to  
combustibles as outlined in Table 1. The  
furnace may be suspended by field  
fabricating a cradle of angle iron and  
threaded rod. Secure the furnace with 2  
AIR CONDITIONING  
If the furnace is used in conjunction with  
air conditioning, the furnace shall be  
installed in parallel with or upstream from  
the evaporator coil to avoid condensation  
in the heat exchanger. In a parallel  
installation, the dampers or air controlling  
means must prevent chilled air from  
entering the furnace. If the dampers are  
manually operated, there must be a  
means of control to prevent the operation  
of either system unless the dampers are  
in the full heat or full cool position. The  
air heated by the furnace shall not pass  
inch  
minimum  
slotted  
angle  
or  
equivalent, as shown in Figure 1. The  
furnace must be supported in such a way  
as to not allow twisting or sagging of the  
cabinet. Position the supports so as to  
not interfere with accessing the burner  
and blower compartments. Suggestion;  
as a measure to prevent fuel oil from  
accumulating in locations other than the  
fire pot, as could be the case in the event  
Fig 1 Suspended Installation  
30318 R4 9/9/2005  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
through a refrigeration unit unless the  
unit is specifically approved for such  
service.  
If the chimney serves the WML-C  
furnace only, the vent should be sized at  
5-inch minimum. The MPL-B should be  
6-inch minimum. The data provided in  
Table 3 is based on dedicated venting. If  
the furnace is to be co-vented with other  
appliances, refer to NFPA 211, Standard  
for Chimneys, Fireplaces, Vents, and  
Solid Fuel-Burning Appliances, NFPA  
31, Standard for the Installation of Oil  
Burning Equipment or CAN/CSA B139,  
Installation Code For Oil Burning  
Equipment for correct sizing information.  
THE  
FURNACE  
MUST  
BE  
Generally, a six-inch clearance between  
the air conditioning evaporator coil and  
the heat exchanger will provide adequate  
airflow through the evaporator coil.  
CONNECTED TO A FLUE HAVING  
SUFFICIENT DRAFT AT ALL TIMES TO  
ENSURE  
SAFE  
AND  
PROPER  
OPERATION OF THE APPLIANCE.  
The blower speed must be checked and  
adjusted to compensate for the pressure  
drop caused by the evaporator coil.  
Refer to Appendix B for recommended  
wiring and electrical connections of the  
air conditioning controls.  
The flue pipe must not be routed through  
concealed space, because it must be  
visually  
checked  
during  
for  
signs  
the annual  
of  
deterioration  
inspection and servicing. The flue pipe  
must not pass through any floor or  
ceiling, but may pass through a wall  
where suitable fire protection provisions  
have been installed. In the United States,  
refer to the latest edition of NFPA 31 for  
regulations governing the installation of  
oil burning equipment. In Canada, refer  
to the latest edition of CAN/CSA B139  
for rules governing the installation of oil  
burning equipment.  
NOTE: This furnace is approved for  
use with L-Vent.  
COMBUSTION AIR  
NOTE: Maximum temperature for L-  
Vent is 575°F (300°C).  
When a furnace is installed in the full  
basement of a typical frame or brick  
house, infiltration is normally adequate to  
provide air for combustion and draft  
operation. If the furnace is installed in a  
closet or utility room, two (2) ventilation  
openings must be provided connecting to  
a well ventilated space (full basement,  
living room or other room opening  
thereto, but not a bedroom or bathroom).  
One opening shall be located 6" from the  
top and bottom of the enclosure at the  
front of the furnace. For furnaces located  
IMPORTANT: The chimney must be  
capable of providing sufficient draft at all  
times for the safe removal of the  
products of combustion.  
The chimney should be tested under  
“winter” conditions; doors and windows  
closed, all other fossil fuel burning  
appliances on, clothes dryer on,  
bathroom fans on, etc. If the chimney  
cannot overcome the competition for air,  
it will be necessary to access the reason  
for it, and take corrective action. If the  
chimney is found to be sized correctly  
and in good repair, it will probably be  
necessary to re-evaluate the availability  
of combustion and ventilation air, and  
take corrective action.  
NOTE: THE RECOMMENDED FLUE  
DRAFT PRESSURE IS -0.02 IN. W.C.  
(AS MEASURED UPSTREAM OF THE  
BAROMETRIC DRAFT REGULATOR).  
SHOWN IN FIGURE 1.  
in  
buildings  
of  
unusually  
tight  
DRAFT REGULATOR CONTROL  
construction, such as those with high  
quality weather stripping, caulking,  
windows and doors, or storm sashed  
windows, or where basement windows  
are well sealed, a permanent opening  
communicating with a well ventilated  
attic or with the outdoors shall be  
provided, using a duct if necessary. Size  
all of the openings and associated  
ductwork by the standards provided in  
the latest Oil Installation Code editions;  
NFPA 31 in the United States, CAN/CSA  
B139 in Canada. Take all fuel burning  
appliances in the area into consideration  
when calculating combustion and  
ventilation air requirements.  
This device is used in conjunction with  
conventional chimney venting. This  
control (or draft regulator) automatically  
maintains a constant negative pressure  
in the furnace to obtain maximum  
efficiency. It ensures that proper  
pressures are not exceeded. If the  
chimney does not develop sufficient  
draft, the draft control cannot function  
properly. The draft regulator, must be  
installed within the same room or  
enclosure as the furnace, and should not  
interfere with the combustion air supplied  
to the burner. The control should be  
The flue pipe should be as short as  
possible with horizontal pipes sloping  
upward toward the chimney at a rate of  
one-quarter inch to the foot. The flue  
pipe should not be smaller in cross  
sectional area than the flue collar on the  
furnace. The flue pipe should connect to  
the chimney such that the flue pipe  
extends into, and terminates flush with  
the inside surface of the chimney liner.  
Seal the joint between the pipe and the  
lining. The chimney outlet should be at  
least two feet above the highest point of  
located  
a
minimum of  
3
flue pipe  
diameters from the furnace breeching  
and installed in accordance to the  
instructions supplied with the regulator.  
The Model CAS-2B-90E Furnace Boot  
manufactured by Field Controls, Inc. may  
be used with the furnace to obtain  
combustion air from outdoors. Use of this  
device does not alter the need for  
ventilation air; however, it does provide a  
good source of combustion air and is  
connected to the oil burner.  
a
peaked roof. All unused chimney  
openings should be closed. Chimneys  
must conform to local, provincial or state  
codes, or in the absence of local  
regulations, to the requirements of the  
National Building Code.  
CHIMNEY VENTING  
See Figure 2 and Table 2 for common  
chimney problems and their remedies.  
The chimney must be sized correctly and  
be in good repair. If the chimney is  
oversized, there is a high risk of the flue  
gases condensing resulting in damage to  
the chimney and other venting parts.  
This problem may be corrected by the  
use of an appropriately sized chimney  
liner.  
30318 R4 9/9/2005  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 2: Common Chimney Problems  
Can be found  
by light and  
mirror reflecting break and  
conditions in  
chimney.  
Obstruction in  
chimney  
Use weight to  
D
E
dislodge.  
Must be  
Lowering a light handled by  
on an extension competent  
cord.  
Joist protruding  
into chimney.  
masonry  
contractor.  
Smoke test -  
build smudge  
fire blocking off  
other opening,  
watching for  
smoke to  
Must be  
handled by  
competent  
masonry  
Break in  
chimney lining.  
F
contractor.  
escape.  
Clean out with  
weighted brush  
or bag of loose  
gravel on end  
of line.  
Collection of  
soot at narrow  
space in flue  
opening.  
Lower light on  
extension cord.  
G
H
Change to  
straight or to  
long offset.  
Lower light on  
extension cord.  
Offset  
The least  
important  
Two or more  
openings to the inspection from  
same chimney.  
Found by  
opening must  
be closed,  
using some  
other chimney  
flue.  
I
basement.  
Leaks should  
be eliminated  
by cementing  
all pipe  
Loose-seated  
pipe in flue  
opening.  
J
K
Smoke test.  
openings.  
Measurement  
of pipe from  
within or  
observation of  
pipe by means  
of a lowered  
light.  
Length of pipe  
must be  
Smoke pipe  
extends into  
chimney.  
reduced to  
allow end of  
pipe to be flush  
with inside of  
tile.  
Table 2: Common Chimney Problems  
Failure to  
Refer to Figure 2  
extend the  
length of flue  
partition to the  
floor.  
By inspection or Extend partition  
Key  
Trouble  
Diagnostic  
Remedy  
L
smoke test.  
to floor level.  
Extend chimney  
above all  
surrounding  
objects within  
30 feet.  
Top of chimney  
lower than  
surrounding  
objects  
A
Observation  
Loose-fitted  
clean-out door.  
Close all leaks  
with cement.  
M
Smoke test.  
Chimney Cap  
or ventilator.  
B
C
Observation  
Observation  
Remove  
Make opening  
as large as  
inside of  
Coping restricts  
opening.  
chimney.  
30318 R4 9/9/2005  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
In general, the oil tank must be properly  
supported and remain stable in both  
empty and full condition. The oil tank  
must be fitted with vent and supply pipes  
to the outdoors. Refer to the above-  
mentioned codes for sizing. The vent  
pipe must be no less than 1¼ inches  
I.P.S., and terminate with an appropriate  
vent cap in a location where it will not be  
blocked. The fill pipe must be no less  
than 2 inches I.P.S., and terminate with  
an appropriate cap in a location where  
debris will not enter the fill pipe during oil  
delivery.  
Table 4: Oil Lines  
OPTIONAL SIDE WALL VENTING  
Certain WML-C AND MPL-B furnace  
models are manufactured to be installed  
as sidewall vented units. Please refer to  
Direct Venting Instructions, P/N 28888  
included with the Vent Kit for details.  
Copper Tubing Oil Line Length (Feet)  
Single-Pipe OD  
Two-Pipe OD  
Lift  
(Feet)  
3/8”  
53  
1/2”  
100  
100  
100  
100  
100  
100  
100  
99  
3/8”  
68  
65  
63  
60  
58  
55  
53  
50  
48  
45  
42  
37  
32  
27  
22  
1/2”  
100  
100  
100  
100  
100  
100  
100  
100  
100  
100  
100  
100  
100  
100  
88  
0
1
Sidewall  
Venting  
(Direct  
Venting)  
49  
requires the use of specific oil burners;  
the Beckett AFII, or the Riello 40BF.  
Please refer to Appendix A, Tables A2,  
and A4.  
2
45  
3
41  
4
37  
Note: Sidewall venting requires special  
attention to combustion air supply. There  
is no natural draft in the venting system  
between furnace cycles; therefore, if the  
indoor pressure is negative relative to  
the outdoors, the vent terminal becomes  
a point of infiltration. This could lead to  
oil odour control problems. This problem  
is rectified by the use of ducted outdoor  
5
33  
6
29  
If located indoors, the tank should  
normally be in the lowest level, (cellar,  
basement, etc.). It must be equipped  
with a shut-off valve at the tank outlet  
used for the oil supply. The oil tank must  
be located as to not block the furnace /  
room exit pathway. Observe all  
clearances specified in the above-  
mentioned codes.  
7
25  
8
21  
83  
9
17  
68  
10  
12  
14  
16  
18  
13  
52  
- - -  
- - -  
- - -  
- - -  
- - -  
- - -  
- - -  
- - -  
air  
for  
combustion  
(semi-sealed  
combustion), using the Beckett AFII or  
Riello 40BF oil burner. See Direct Vent  
Instructions supplied with the Vent Kits.  
PIPING INSTALLATION  
Table 3: Minimum Chimney Base  
Temperatures (°F)  
In the United States, NFPA 31, Standard  
for the Installation of Oil Burning  
Equipment, Chapter 2.  
In retrofit applications, where an existing  
oil line system is in place, a vacuum  
check will help determine the efficacy of  
the existing oil line system The vacuum  
in a system should not exceed 6” Hg. for  
a single pipe system, nor 12” Hg. for a  
two-pipe system.  
Chimney Height (ft.)  
Nozzle  
In Canada, the entire fuel system should  
be installed in accordance with the  
requirements of CAN/CSA B139, and  
local regulations. Use only approved fuel  
oil tanks piping, fittings and oil filters.  
11  
20  
28  
36  
Chimney Thermal Resistance < R6  
0.50  
0.65  
0.70  
0.75  
0.85  
1.00  
300  
275  
270  
260  
250  
225  
400  
340  
330  
320  
300  
300  
535  
430  
405  
380  
355  
365  
725  
535  
505  
475  
430  
430  
NOTE: The oil burner requires the use of  
a bypass plug when converting from  
single-pipe to two-pipe oil piping  
systems. See burner manufacturer’s  
instructions.  
Ensure that all fittings used in a copper  
oil line system are high quality flare  
fittings. Do not use compression fittings.  
Do not use Teflon tape on any fittings.  
All fuel systems should include an oil  
filter between the fuel oil storage tank  
and the oil burner. For best results,  
install the oil filter as close to the burner  
as possible. When using an indoor oil  
tank, the oil filter may be installed at the  
tank downstream from the shut-off valve.  
If firing the furnace under the 0.65 gph  
rate, a 7 to 10 micron line filter should be  
installed as close to the oil burner as  
possible.  
Pressurized or gravity feed installations  
must not exceed 3 PSIG. Pressures  
greater than 10 PSIG may cause  
damage to the shaft seal. If the height of  
the oil stored in a tank above the oil  
burner exceeds 11½ feet, it may be  
necessary to use a pressure-regulating  
device approved for this purpose.  
Chimney Height (ft.)  
20 28  
Nozzle  
11  
36  
Chimney Thermal Resistance > R6  
0.50  
0.65  
0.70  
0.75  
0.85  
1.00  
185  
175  
175  
175  
165  
165  
200  
185  
185  
185  
185  
185  
220  
205  
195  
195  
195  
195  
250  
220  
215  
210  
205  
205  
The furnace may be installed with a one-  
pipe system with gravity feed or lift. The  
maximum allowable lift on a single line  
system is 8 feet. Lift should be measured  
from the bottom (outlet) of the tank, to  
the inlet of the burner. Sizing a single  
line system is complex because of the  
difficulty estimating the pressure drop  
ELECTRICAL CONNECTIONS  
The furnace is listed by the Canadian  
Standards Association (CSA). It is  
factory wired and requires minimal field  
wiring. In the United States, the wiring  
must be in accordance with the National  
Fire Protection Association NFPA-70,  
National Electrical Code, and with local  
codes and regulations. In Canada, all  
field wiring should conform to CAN/CSA  
C22.1 Canadian Electrical Code, Part 1,  
and by local codes, where they prevail.  
< - less than, > - greater than  
OIL TANK  
through  
each  
fitting,  
bend  
and  
component in the line. In general, keep  
single line systems short as possible.  
The following chart shows the allowable  
line lengths (horizontal + vertical) for  
single and two-line oil piping systems. All  
distances are in feet.  
Oil storage tanks must be selected and  
installed in compliance with applicable  
codes; in the United States, NFPA 31,  
Standard for the Installation of Oil  
Burning Equipment, Chapter 2. and in  
Canada, CAN/CSA-B139, Installation  
Code for Oil Burning Equipment, Section  
6. Observe all local codes and by-laws.  
The furnace should be wired to  
a
separate and dedicated circuit in the  
30318 R4 9/9/2005  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
main  
electrical  
panel;  
however,  
2. Connect an ammeter between the  
wire and the thermostat terminal to  
which it was attached.  
If the limit control opens with the United  
Technologies 1158-120 electronic fan  
control, the circulating fan will be  
energized as well. When the limit closes,  
the control initiates a two minute delay.  
When this delay is finished, the fan off  
timer will begin. At the end of the fan off  
time cycle the burner will be energized,  
initiating a normal burner cycle.  
accessory equipment such as electronic  
air cleaners and humidifiers may be  
included on the furnace circuit. Although  
a suitably located circuit breaker can be  
used as a service switch, a separate  
service switch is advisable. The service  
switch is necessary if reaching the circuit  
breaker involves becoming close to the  
furnace, or if the furnace is located  
between the circuit breaker and the  
means of entry to the furnace room. The  
furnace switch (service switch) should be  
clearly marked, installed in an easily  
accessible area between the furnace and  
furnace room entry, and be located in  
such a manner to reduce the likelihood  
that it would be mistaken as a light  
switch or similar device.  
3. Note the amperage reading when  
the heating contacts are closed.  
(System switch must be on “HEAT” if  
so equipped.  
4. Re-connect the thermostat wire. If  
the thermostat is serving  
combination heating and  
a
air  
TABLE 5  
Honeywell ST9103  
conditioning system, pay particular  
attention to polarity.  
Dip Switch  
Position  
Blower Off Delay  
Time  
5. When the thermostat is reconnected  
and re-plumbed, adjust the heat  
anticipator setting to match the  
observed amperage reading.  
1
2
On  
On  
Off  
Off  
On  
Off  
On  
Off  
60 seconds  
90 seconds  
120 seconds  
150 seconds  
FAN TIMER BOARD AND LIMIT  
CONTROL  
The power requirements for all models:  
120 VAC, 1 , 60 Hz., 12A.  
The Electronic Fan Timer integrates  
control of all burner and circulator fan  
operations. This control is the central  
wiring point for most of the electrical  
components in the furnace. The  
Honeywell ST9103 has a fixed fan delay  
on time of 30 seconds after the burner  
ignites. The United Technologies 1158-  
120 has an adjustable fan on time that is  
Accessories requiring 120 VAC power  
sources such as electronic air cleaners  
and humidifier transformers may be  
powered from the ST9103 EFT. Do not  
use the direct drive motor connections as  
a power source, since there is a high risk  
of damaging the accessories by  
exposure to high voltage from the auto-  
generating windings of the direct drive  
motor.  
TABLE 6  
United Technologies 1158-120  
Dip Switch  
Position  
Blower Delay  
Times  
1
2
3
4
On  
Off  
Seconds Minutes  
Off Off  
On Off  
Off On  
On On  
30  
60  
90  
120  
2
set  
by  
selecting  
the  
dipswitch  
combination displayed in Table 6. This  
fan on delay can be set at 30, 60, 90 or  
120 seconds. This provides a delay  
between the burner ignition and blower  
start-up to eliminate excessive flow of  
cold air when the blower comes on. The  
Honeywell ST9103 has an adjustable  
fan off time of 60, 90, 120 and 150  
Thermostat wiring connections and air  
conditioning contactor low voltage  
connections are shown in the wiring  
Off Off  
On Off  
Off On  
On On  
diagrams.  
Some  
micro-electronic  
3
thermostats require additional controls  
and wiring. Refer to the thermostat  
manufacturer's instructions.  
4
seconds that is set by selecting  
a
6
dipswitch combination on the control  
board displayed in Table 5. Similarly the  
United Technologies 1158-120 have an  
adjustable fan off time of 2, 3, 4 or 6  
minutes displayed in Table 6. The fan off  
delay time starts when the burner motor  
is de-energized at the end of a call for  
heat. Blower shutdown is delayed to  
remove any residual heat from the heat  
exchanger and improve the annual  
efficiency of the furnace.  
The thermostat should be located  
approximately 5 feet above the floor, on  
an inside wall where there is good  
natural air circulation, and where the  
thermostat will be exposed to average  
room temperatures. Avoid locations  
where the thermostat will be exposed to  
cold drafts, heat from nearby lamps and  
appliances, exposure to sunlight, heat  
from inside wall stacks, etc.  
Note: It is advisable not to set the  
fan on delay time for a time period  
longer than 90 seconds at highest  
input. Longer fan on delay times  
may result in nuisance limit trips.  
CIRCULATING AIR BLOWER  
All WML-C AND MPL-B furnace models  
are equipped with a direct drive blower  
system. Direct drive blower speed  
adjustments are not normally required in  
properly sized extended plenum duct  
systems. The motor RPM and air CFM  
delivery will vary automatically to  
accommodate conditions within the usual  
range of external static pressures typical  
of residential duct systems. Under-sized  
Normal heat anticipator setting: 0.1 A.  
For more precise adjustment, the heat  
anticipator may be adjusted to the  
amperage draw of the heating control  
circuit as measured between the "R" and  
"W" terminals of the thermostat. To  
reduce the risk of damaging the heat  
anticipator, do not measure circuit  
without first removing one of the two  
wires first. To determine the heating  
circuit amperage draw:  
The electronic fan timer board works in  
conjunction with snap disc limit controls,  
which perform a safety function, and  
breaks power to the oil burner primary  
control, which shuts off the burner if the  
furnace over-heats. The limit control is  
thermally operated and automatically  
resets. The limit control is factory  
installed, pre-set and is not adjustable.  
duct systems may require  
a
higher  
blower speed to obtain a reasonable  
system temperature rise. Some older  
duct systems were not designed to  
provide static pressure. They typically  
feature special reducing fittings at each  
branch run and lack block ends on the  
If a limit control opens, the Honeywell  
ST9103 will energize the circulating fan.  
When the limit control closes the burner  
is re-energized and the heating cycle  
begins again.  
1. Disconnect one of the “R” or “W”  
wires from the thermostat terminal.  
30318 R4 9/9/2005  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
trunk ducts. These systems may require  
modification to provide some resistance  
to the airflow to prevent over-amping of  
the direct drive blower motor. Selecting a  
lower blower speed may correct this  
problem.  
into contact with the furnace heat  
exchanger. Do not use direct drive motor  
connections as a source of power for  
120 VAC humidifiers and humidifier  
transformers.  
box, tape off both ends of the unused  
wire.  
DISCONNECT THE POWER SUPPLY  
OIL BURNER  
Direct drive blower speeds are adjusted  
by changing the "hot" wires to the motor  
winding connections. Please refer to  
wiring diagram in Appendix B or the  
wiring diagram label affixed to the  
TO  
THE  
FURNACE  
BEFORE  
The oil burner must align properly with  
the cerafelt fiber chamber (firepot). The  
cerafelt fiber chamber is initially quite  
soft, but hardens and becomes quite  
brittle after the first firing. The firepot is  
held in place by a retaining bracket;  
however, it is possible for the firepot to  
shift if subjected to rough handling during  
transit.  
OPENING THE BLOWER ACCESS  
DOOR TO SERVICE THE AIR FILTER,  
FAN AND MOTOR. FAILURE TO  
SHUT OFF POWER COULD ALLOW  
furnace.  
THE  
NEUTRAL  
WIRE  
THE  
BLOWER  
TO  
START  
(normally the white wire) IS NEVER  
MOVED TO ADJUST THE BLOWER  
SPEED.  
UNEXPECTEDLY, CREATING A RISK  
OF DEATH OR PERSONAL INJURY.  
Do not use the blower speed wires as  
a source of power to accessories as  
electronic air cleaners and humidifier  
transformers. The unused motor taps  
DO NOT CONNECT POWER LEADS  
BETWEEN MOTOR SPEEDS. THE  
NEUTRAL WIRE MUST ALWAYS BE  
CONNECTED TO THE MOTOR'S  
DESIGNATED NEUTRAL TERMINAL.  
auto-generate  
sufficiently  
high  
BEFORE  
FURNACE  
OPERATING  
CHECK  
THE  
BURNER  
voltages  
equipment.  
to  
damage  
Use the  
accessory  
terminals  
ALIGNMENT WITH COMBUSTION  
CHAMBER. THE END CONE OF THE  
AIR TUBE MUST BE CENTRED TO  
provided on the electronic fan timer.  
THE  
ACCOMODATING  
RING  
It is possible and acceptable to use a  
single blower speed for both heating and  
cooling modes. The simplest method to  
connect the wiring from both modes is to  
PROVIDED IN THE DESIGN OF THE  
COMBUSTION CHAMBER. ADJUST  
ALIGNMENT  
Do not start the burner or blower fan  
unless the blower access door is  
securely in place.  
AS  
NECESSARY  
BEFORE THE FIRST FIRING.  
use  
a
"piggy-back  
connector"  
accommodating both wires on a single  
motor tap. It is also acceptable to  
connect the selected motor speed with a  
pigtail joined to both heating and cooling  
speed wires with a wire nut. As a safety  
OIL BURNER NOZZLES  
Additional ST9103 Fan Timer Control  
information is in Appendix A, Tables, and  
in Appendix B, Wiring Diagrams.  
WML-C AND MPL-B furnaces are  
certified for multiple firing rates, ranging  
from approximately 58,000 to 85,600  
BTU/hr. on the WML-C and 85,500 to  
123,000 BTU/Hr. on the MPL-B By  
changing the oil burner nozzle within the  
specific model range, and temperature  
rise, the furnace may be fired at an ideal  
rate for a wide range of structures.  
HUMIDIFIER  
precaution  
against  
accidental  
disconnection of the wires by vibration, it  
is advisable to secure the wire nut and  
wires with a few wraps of electricians  
tape.  
A humidifier is an optional accessory  
available through most heating supplies  
outlets. Installation should be carried out  
in accordance with the humidifier  
manufacturer's installation instructions.  
Water or water droplets from the  
humidifier should not be allowed to come  
If the joining of the blower speed  
wiring is done in the furnace junction  
Figure 4: Horizontal Smoke Test Port Location  
Figure 5: Vertical Smoke Test Port Location  
30318 R4 9/9/2005  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
BURNER ELECTRODES  
PROCEDURE:  
excess air, or contaminated fuel. Do not  
ignore this indicator.  
Correct positioning of the electrode tips  
with respect to each other, to the fuel oil  
nozzle, and to the rest of the burners is  
essential for smooth light ups and proper  
operation. The electrode tips should be  
adjusted to a gap of 5/32”, 1/16” ahead  
of the nozzle, 5/16” above the centerline  
of the nozzle. The “Z” dimension (front  
edge of the burner head to the front face  
of the nozzle is 1-1/8 inches.  
Start the burner and allow it to run at  
least ten minutes. Set the air shutter to  
STACK TEMPERATURE:  
give  
a
good flame visually. The  
Stack temperature will vary depending  
on fuel input, circulating air blower  
speed, and burner set up, etc. In  
general, stack temperature should  
typically range between 380°F to 550°F,  
assuming that the combustion air is  
approximately room temperature (65°F -  
combustion air supply to the burner is  
controlled by manipulating the air shutter  
on the left side of the burner, and, if  
necessary, the bulk air band. To adjust,  
loosen the bolt on the movable shutter.  
Move the shutter gradually until a good  
flame (visually) has been achieved. Re-  
snug the bolt.  
70°F).  
temperature indicates greater efficiency;  
however, excessively low stack  
In  
general,  
lower  
stack  
Electrode positioning should be checked  
before the first firing of the furnace.  
Check the initial draft setting as the  
furnace warms up. The draft may be  
measured at the test port. The breech  
draft should be approximately - 0.05”  
w.c. to obtain an over fire draft reading of  
- 0.02 inches w.c.  
temperature can lead to condensation  
forming in the chimney and / or venting.  
Sulphur and similar contaminants in the  
fuel oil will mix with condensation to form  
acids. Acids and resultant chemical salts  
will cause rapid deterioration of the  
chimney and venting components, and  
may attack the furnace.  
The electrode porcelains should be free  
of cracks, the electrode tips should be  
tapered and free of burrs, and the  
contact rods must be clean and be in  
firm contact with the ignition transformer  
contact springs. The electrodes must not  
come into contact with the burner head.  
Check the oil pump pressure. Standard  
operating pressure is 100 PSIG.  
OIL BURNER SET-UP  
After reaching steady state, take  
a
If the flue gases are below the range, it  
may be necessary to slow down the  
blower fan. If the flue gases are above  
the range, the blower fan may require  
speeding up. Stack temperature varies  
directly with the system temperature rise.  
System temperature rise is the difference  
between the furnace outlet temperature  
and furnace inlet temperature as  
measured in the vicinity of the  
connection between the plenum take-offs  
and the trunk ducts.  
smoke test. If not indicating a trace, set  
the combustion air controls to provide a  
trace.  
The burner air supply is adjusted to  
maintain the fuel to air ratio to obtain  
ideal combustion conditions. A lack of air  
causes "soft" and "sooty" flames,  
resulting in soot build-up throughout the  
heat exchanger passages. Excess  
combustion air causes a bright roaring  
fire and high stack temperatures  
resulting in poor fuel efficiency.  
Typically, the CO2 reading will range  
from 11.5% to 13.5%.  
After the air adjustments have been  
completed, and the air shutter or air  
adjustment plate has been secured, re-  
check the over fire draft and take another  
smoke test to ensure that the values  
have not changed.  
PREPARATIONS:  
Drill a ¼” test port in the venting, ideally  
at least 2 flue pipe diameters away from  
the furnace breeching, if venting  
horizontally from the furnace, or from the  
flue pipe elbow if venting vertically before  
reaching the furnace. (See Figures 4 and  
5).  
If the venting from the furnace to the  
chimney is long, or exposed to cold  
ambient temperatures, it may be  
necessary to use L-Vent as the vent  
connector to reduce stack temperature  
loss to prevent condensation. The  
venting should be inspected annually to  
ensure that it is intact.  
The test port will allow flue gas samples  
to be taken and stack temperatures to be  
measured.  
FURNACE INSTALLATION SET-  
UP  
Before starting the burner, check the  
burner alignment with the combustion  
chamber (fire pot), check that the correct  
nozzle is tightened into place, and that  
the burner electrodes are properly  
positioned.  
The furnace must be set up as the final  
step in the installation.  
A) The oil burner must be set up  
following the procedures outlined above.  
B) The WML-C models should operate  
within a temperature rise of 45°F to 75°F.  
The MPL-B temperature rise range  
should be 50°F to 80°F. To determine  
the temperature rise, measure the supply  
air and return air temperatures when the  
furnace has reached steady state  
conditions. This is the point at which the  
supply air temperature stops increasing  
relative to the return air temperature. The  
furnace may have to run 10 to 15  
minutes to reach steady state conditions.  
The measurements may be made with  
duct thermometers or thermocouples  
The Beckett burner bulk air band is  
should be closed, and the air shutter  
initial setting should be approximately  
7.00.  
Figure 6: Checking Over-Fire Draft.  
Note A: Locate hole at least 6 inches on  
the furnace side of the draft control.  
SMOKE TEST NOTE:  
Note B: Ideally, hole should be at least  
12 inches from breeching or elbow.  
If oily or yellow smoke spots are found  
on the smoke test filter paper, it is  
usually a sign of unburned fuel. This  
indicates poor combustion. This type of  
problem may be caused by excess draft,  
30318 R4 9/9/2005  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
used in conjunction with multi-meters  
with temperature measurement  
capabilities.  
anywhere within the heating system  
which may cause some concern or  
annoyance to the home owner, etc.  
B: Annual Service By Contractor  
The return air should be measured at a  
point where the thermometer will be well  
within the air stream near the furnace  
return air inlet. Actual location is not  
particularly critical; however, avoid  
F) Be sure that the homeowner is  
THE  
COMBUSTION  
CHAMBER  
familiar  
with  
the  
furnace.  
The  
(FIREPOT) IS FRAGILE. USE CARE  
WHEN INSPECTING AND CLEANING  
THIS AREA.  
homeowner should be aware of the  
location of electrical circuit breaker or  
fuse, the location of any electrical  
switches controlling the furnace, the  
location of the oil tank shut-off valve and  
how to operate the valve. The  
homeowner should be informed where  
the oil tank gauge is located and how to  
read it.  
locations  
where  
the  
temperature  
The heat exchanger should be inspected  
periodically and cleaned if necessary. If  
cleaning is necessary, SHUT OFF  
POWER TO THE FURNACE and  
remove the burner. Using a stiff brush  
with a wire handle, brush off scale and  
soot from inside the drum and flue pipe.  
To clean the radiator, remove the round  
cover or covers on the inner radiator  
access pipes located on the front panel  
between the oil burner and the flue pipe.  
Rear breech models have a single front  
cleanout and front breech models have  
two front cleanouts.  
readings could be affected by humidifier  
bypass ducts, the inside radius of  
elbows, etc.  
The supply air temperature should be  
measured at  
a
point where the  
thermometer will be well within the air  
stream near the furnace supply air outlet.  
Usually, the side mid-point of the supply  
air plenum take-off is ideal, providing it is  
out of the line of sight to the heat  
exchanger. If the thermometer is within  
the line of sight of the heat exchanger,  
the supply air readings may be skewed  
by radiant heat from the heat exchanger.  
If the plenum take-off is unsuitable, the  
supply air temperature may be measured  
within the first 18 inches of the first  
segment of supply air trunk duct.  
It would be beneficial to review safety  
issues with the home owner, such as the  
danger of storing combustibles too close  
to the furnace, hanging anything on the  
furnace vent pipe, and especially the  
dangers of indiscriminately pressing the  
burner reset button.  
IMPORTANT: Be sure that the home  
owner knows where the burner reset  
switch is located, and is aware that the  
reset switch is not to be activated more  
than once without a thorough look for the  
cause of the problem, (lack of fuel, etc.).  
Be sure that the homeowner knows  
when to quit trying to start the furnace  
during these conditions and who to call  
for emergency service.  
A wire brush can be used to loosen dirt  
and debris on the inside surfaces of the  
radiator. Clean out all accumulated dirt,  
soot and debris with a wire handled  
brush and an industrial vacuum cleaner.  
Replace the clean-out covers.  
If the temperature rise is outside the  
recommended range, it may be adjusted  
on direct drive equipped units by  
selecting alternate circulation fan motor  
speeds. If the temperature rise is too  
high, speed the fan up. If the  
temperature rise is too low, slow the fan  
down.  
Most circulating fan motors are  
permanently lubricated by the motor  
manufacturer. These motors will have no  
oil ports. If the blower motor does  
contain oil ports, under normal operating  
conditions it will not require oiling for the  
first two years. Oil sparingly; a few drops  
in each oil port with SAE 20 non-  
detergent oil. Oiling is most easily done  
with a "tele-spout" oiler. This oiler has a  
long flexible plastic spout. DO NOT  
OVER-LUBRICATE. Excess oil may  
result in premature electric motor failure.  
MAINTENANCE AND SERVICE  
A: Routine Maintenance By Home  
Owner  
C) Keep in mind that the stack  
temperature varies directly with the  
temperature rise. The higher the  
temperature rise, the higher the stack  
temperature will be, resulting in lower  
efficiency. The lower the temperature  
rise, the lower the stack temperature will  
be, which, in some cases, may allow  
condensation to form in the chimney and  
other vent parts.  
Other than remembering to arrange for  
the annual professional servicing of the  
furnace by the service or installation  
contractor, the most important routine  
service performed by the homeowner is  
to maintain the air filter or filters. A dirty  
filter can cause the furnace to over-heat,  
fail to maintain indoor temperature during  
cold weather, increase fuel consumption  
and cause component failure.  
Inspect the blower fan. Clean it if  
necessary.  
Oil Burner Maintenance: Follow the  
instructions  
manufacturer.  
of  
the  
(See  
oil  
oil  
burner  
burner  
D) Test the high limit control to ensure  
that it is operating correctly. This may be  
done by temporarily removing the  
circulator fan heating wire or neutral  
wire. Turn of electrical power to the  
furnace before working with the motor  
wires. Be sure to protect any removed  
wires from shorting out on metal furnace  
parts. If the high limit test is successful,  
shut off the electrical power to the  
furnace, restore the proper motor wiring.  
Finally, restore power to the furnace.  
The furnace filter(s) should be inspected,  
cleaned or replaced monthly. The  
furnace is factory equipped with a semi-  
permanent type filter. If the filter is  
damaged, replace with filters of the same  
size and type.  
manufacturer's instructions supplied with  
furnace). The oil burner nozzle should be  
replaced annually. We recommend that  
the oil filter be changed on an annual  
basis.  
During the routine service, inspect the  
general condition of the furnace watching  
for signs of oil leaks in the vicinity of the  
oil burner, soot forming on any external  
part of the furnace, soot forming around  
the joints in the vent pipe, etc. If any of  
these conditions are present, please  
advice your service or installation  
contractor.  
The venting system should be cleaned  
and inspected for signs of deterioration.  
Replace pitted or perforated vent pipe  
and fittings. The barometric draft  
regulator should open and close freely.  
E) Operate the furnace through  
a
All electrical connections should be  
checked to ensure tight connections.  
Safety controls such as the high limit  
minimum of three full heating cycles.  
During this time, check for fuel oil leaks,  
gross air leakage from the supply air  
ductwork, unusual noises originating  
controls  
should  
be  
tested  
for  
functionality. The fan control functions  
30318 R4 9/9/2005  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
should be checked to ensure that all fan  
speeds are operating properly.  
furnace and set the thermostat above  
room temperature. After three or four  
minutes of burner operation, the limit  
control should turn the burner off. When  
the limit function test is complete, shut  
off electrical power to the furnace,  
replace the neutral wire to the blower fan  
motor, and then restore power. The  
blower fan will start up immediately.  
Once the temperature has dropped and  
the limit control has reset, the fan will  
operate until the fan off time is achieved.  
The oil burner will then resume operation  
and continue until the thermostat is  
satisfied. Restore the thermostat setting  
to a comfortable temperature.  
OPERATING INSTRUCTIONS  
Before Lighting  
Open all supply and return air registers  
and grilles.  
Open all valves in oil pipes.  
Turn on electric power supply  
To Light Unit  
Set the thermostat above room  
temperature to call for heat. The burner  
should start. NOTE: It may be necessary  
to press the RESET button on the  
primary combustion control relay.  
To Shut Down Unit  
Set the thermostat to the lowest possible  
setting.  
There will be a fan on time delay before  
the circulating fan is energized. The  
Honeywell ST9103 has a fixed fan delay  
on time of 30 seconds after the burner  
ignites. The United Technologies 1158-  
120 has an adjustable fan on time that is  
Set the manual switch (if installed) in the  
Electrical Power Supply Line to "OFF".  
NOTE: If the furnace is to be shut down  
for an extended period of time, close the  
oil supply valve to the oil burner.  
set  
by  
selecting  
the  
dipswitch  
combination displayed in Chart 1. This  
fan on delay can be set at 30, 60, 90 or  
120 seconds.  
Set the thermostat below room  
temperature. The oil burner should stop.  
DO NOT ATTEMPT TO START THE  
BURNER WHEN EXCESS OIL HAS  
ACCUMULATED,  
WHEN  
THE  
The air circulation blower will continue to  
run until the time off setting selected on  
the electronic fan timer control times out.  
The Honeywell ST9103 has an  
adjustable fan off time of 60, 90, 120 and  
150 seconds that is set by selecting a  
dipswitch combination on the control  
FURNACE IS FULL OF VAPOUR, OR  
WHEN THE COMBUSTION CHAMBER  
IS VERY HOT. NEVER BURN  
GARBAGE OR PAPER IN THE  
FURNACE, AND NEVER LEAVE  
PAPER OR RAGS AROUND THE UNIT.  
board.  
Technologies  
adjustable fan off time of 2, 3, 4 or 6  
minutes The fan timer control  
Similarly  
the  
United  
1158-120  
has an  
adjustments may be altered if the air at  
the room registers is uncomfortably high  
upon blower start up or shutdown.  
The necessary adjustments to the fan  
control settings should be determined by  
measuring the temperature of the air in  
the supply air take-off, or within the first  
few inches of the supply air trunk. The  
side mid point of the transition is usually  
ideal, providing that the thermometer  
probe is beyond the "line of sight"  
wherein false readings from radiant heat  
could be observed. The system  
temperature rise, the difference in  
temperature between the supply air and  
return air, should be within the indicated  
range on the appliance rating plate.  
To check the operation of the limit  
switch, shut off power to the furnace.  
Temporarily remove the neutral wire  
from the direct drive blower motor.  
Restore the electrical power to the  
30318 R4 9/9/2005  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A- WML-C AND MPL-B BURNER SET UP  
WML-C AND MPL-B furnaces may be used with the following oil burners.  
Please note: The Beckett AF, and Riello 40F oil burners are for applications using indoor air for combustion only. For sidewall  
venting applications utilizing outdoor air for combustion, use the Beckett AFII or the Riello 40BF (Balanced Flue) oil burners  
only.  
Table A-1 Beckett AF Oil Burner Set-Up  
Beckett AF Series Oil Burners  
(For use with chimney vented units only)  
Furnace  
Model  
Output  
BTU/Hr  
Burner  
Model  
Pump  
Pressure  
Static  
Plate  
Nozzle  
Flow Rate  
Head 1  
WML-60C 2  
WML-80C  
WML-90C  
58,000  
75,000  
85,600  
AF76BNHS  
AF76BNHS  
AF76BNHS  
0.50 / 80°A  
0.65 / 80°A  
0.75 / 80°A  
100 PSIG  
100 PSIG  
100 PSIG  
0.50 USGPH  
0.65 USGPH  
0.75 USGPH  
F3  
F3  
F3  
3- in.  
3- in.  
3- in.  
MPL-90B  
MPL-100B  
MPL-120B  
MPL-130B  
85,500  
96,000  
AF76XN  
AF76XN  
AF76XN  
AF76YB  
0.75 / 80°A  
0.85 / 80°A  
1.00 / 60°A  
1.10 / 70°A  
100 PSIG  
100 PSIG  
100 PSIG  
100 PSIG  
0.75 USGPH  
0.85 USGPH  
1.00 USGPH  
1.10 USGPH  
F3  
F3  
F3  
F6  
2- ¾ in.  
2- ¾ in.  
2- ¾ in.  
2- ¾ in.  
112,000  
123,000  
1 Head is shielded by ceramic insulator. 2 Low Firing Rate Baffle required when using a 0.50-gallon nozzle.  
Table A-2 Beckett AFII Oil Burner Set-Up  
Beckett AFII Series Oil Burners  
(For use with sidewall vented units using outdoor combustion air)  
Furnace  
Model  
Output  
BTU/Hr  
Burner  
Model  
Pump  
Pressure  
Nozzle  
Flow Rate  
Head  
WML-60CB2  
WML-80CB2  
WML-90CB2  
63,500  
75,000  
85,600  
AFII-85  
AFII-85  
AFII-85  
0.50 / 60°A  
0.60 / 60°A  
0.70 / 60°A  
145 PSIG  
145 PSIG  
145 PSIG  
0.55 USGPH  
0.65 USGPH  
0.75 USGPH  
FB0  
FB3  
FB3  
MPL-90BB2  
MPL-100BB2  
MPL-120BB2  
85,500  
96,000  
112,000  
AFII-150  
AFII-150  
AFII-150  
0.70 / 60°A  
0.80 / 60°A  
0.85 / 70°A  
145 PSIG  
145 PSIG  
145 PSIG  
0.75 USGPH  
0.85 USGPH  
1.00 USGPH  
FB0  
FB3  
FB3  
Table A-3 Riello 40F Series Oil Burner Set-Up  
Riello 40F Series Oil Burners  
(For use with chimney vented units)  
Furnace  
Model  
Output  
BTU/Hr  
Burner  
Model  
Pump  
Pressure  
Turbulator  
Setting  
Nozzle  
Flow Rate  
Air Gate  
WML-60CRF  
WML-80CRF  
WML-90CRF  
59,500  
75,000  
85,600  
40F3  
40F3  
40F3  
0.50 / 60°W  
0.60 / 60°W  
0.65 / 60°W  
105 PSIG  
115 PSIG  
135 PSIG  
0.51 USGPH  
0.65 USGPH  
0.75 USGPH  
2.6  
2.6  
3.6  
1.0  
1.5  
2.0  
MPL-90BRF  
MPL-100BRF  
MPL-120BRF  
85,500  
96,000  
112,000  
40F5  
40F5  
40F5  
0.60 / 60°W  
0.65 / 60°W  
0.85 / 60°W  
145 PSIG  
145 PSIG  
145 PSIG  
0.75 USGPH  
0.85 USGPH  
1.00 USGPH  
2.25  
2.5  
0.0  
0.5  
1.0  
2.75  
30318 R4 9/9/2005  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table A-4 Riello Balanced Flue (BF) Burner Set-Up  
Riello Balanced Flue Series Oil Burners  
(For use with sidewall vented units using outdoor combustion air)  
Furnace  
Model  
Output  
BTU/Hr  
Burner  
Model  
Pump  
Pressure  
Turbulator  
Setting  
Nozzle  
Flow Rate  
WML-60CRB  
WML-80CRB  
WML-90CRB  
59,500  
75,000  
85,600  
40BF3  
40BF3  
40BF3  
0.50 / 60°W  
0.60 / 60°W  
0.65 / 60°W  
105 PSIG  
115 PSIG  
135 PSIG  
0.51 USGPH  
0.65 USGPH  
0.75 USGPH  
1.0  
1.5  
2.0  
NOTE: Air gate setting may vary for sidewall vented units where air gate must be adjusted to achieve zero smoke.  
system temperature rise. System  
temperature rise is the difference  
between the furnace outlet temperature  
and furnace inlet temperature as  
measured in the vicinity of the  
connection between the plenum take-  
offs and the trunk ducts  
A.1 OIL BURNER AIR  
ADJUSTMENT  
A.2 BURNER ELECTRODES  
Adjustment of the electrode tips with  
respect to each other, the nozzle, and  
to the rest of the burner is very  
important to ensure smooth start-ups  
and to permit efficient combustion.  
For complete details, consult the oil  
burner instruction manual provided in  
the furnace documents envelope.  
Beckett AF Burner  
Beckett AF Burner  
Perform a smoke spot test. The smoke  
spot should not exceed No. 1 on the  
Bacharach Scale.  
Adjust the air shutter by loosening the  
locking screws and moving the air  
shutter, and if necessary, the bulk air  
band.  
Electrode gap: 5/32 inch.  
Distance above horizontal centerline:  
5/16 inch. Older instruction sheets  
specify 7/16 inch. The current  
specification is 5/16 inch.  
After the air adjustments have been  
completed, re-check the draft pressure  
at the test port on the burner mounting  
plate as shown in Figure #6. The draft  
should be adjusted to 0.02 inches w.c.  
Beckett AFII Burner  
Adjust the burner air supply by first  
loosening the locking screw located on  
the black dial to the right of the burner.  
Turn the black dial clockwise to  
increase the combustion air and  
counter-clockwise to decrease the  
combustion air. Re-tighten the locking  
screw after obtaining the proper setting.  
Distance ahead of nozzle: 1/16 inch.  
“Z” dimension, the distance from the  
front of the end cone (head) to the face  
of the nozzle should be 1-1/8 inches. If  
a ceramic head is used, the distance  
from the end cone to the nozzle face is  
increased to 1-3/8 inches.  
In the United States, the Beckett AF  
Burner may be equipped with Beckett's  
"Inlet Air Shut-Off" to increase  
efficiency. (Beckett Part No. AF/A  
5861).  
NOTE: USE OF THE INLET AIR  
SHUT-OFF COULD CAUSE POST  
COMBUSTION NOZZLE DRIP.  
Riello 40 Series (Chimney Vented)  
Riello 40F, & BF Burners  
Riello burners are factory set with  
respect to nozzle size; pump pressure,  
air gate and turbulator adjustments for  
each model and firing rate. By  
removing the burner cover and  
loosening the screws that secure the  
air adjustment plate, the combustion air  
can be adjusted. Move the adjusting  
plate to either increase or decrease  
combustion air. When the proper air  
setting is achieved, retighten the fixing  
screws.  
Electrode gap: 5/32 inch.  
A.4 SPECIAL INSTRUCTIONS  
FOR UNITS EQUIPPED WITH  
RIELLO BURNERS  
Distance above horizontal centerline:  
13/64 inch.  
Distance ahead of nozzle: 5/64 to 7/64  
inch.  
Riello burners are factory set with  
respect to nozzle size, pump pressure,  
air gate and turbulator adjustments for  
each model and firing rate; therefore,  
do not use the above listed set up  
procedures.  
A.3 START UP  
The furnace should be operated for a  
minimum of 15 minutes to reach steady  
state conditions before fine tuning  
combustion. The warm up time is ideal  
for testing the oil pump pressure.  
Riello specifications are listed in Tables  
A-3 and A-4. Consult the Riello  
Installation Instructions supplied with  
the Burner for specific information  
Riello Balanced Flue (BF) Series  
Riello burners are factory set with  
respect to nozzle size; pump pressure,  
and turbulator adjustments for each  
model and firing rate. The combustion  
air can be adjusted with the burner  
cover on by first removing the plastic  
cover on the top right hand side of the  
burner cover. With a Philips head  
screw driver, turn the adjustment screw  
clockwise to increase combustion air or  
Drill a 1/4-inch test port in the venting  
between the furnace flue outlet and  
draft regulator (barometric damper).  
Insert a stack thermometer and note  
the flue gas temperature. The flue  
gases should be within a range of  
350°F to 450°F. If the flue gases are  
below the range, it may be necessary  
to slow down the blower fan. If the flue  
gases are above the range, the blower  
fan may require speeding up. Stack  
temperature varies directly with the  
concerning  
operation,  
burner  
and  
adjustments,  
trouble-shooting.  
counter-clockwise  
to  
decrease  
combustion air. When the combustion  
air is set, re-insert the plastic cover.  
30318 R4 9/9/2005  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table A-6 Direct Drive Blower Set-Up  
Blower Set-Up  
Cooling Capacity  
Power  
Furnace  
Model  
Blower  
0.20 in. w.c.  
0.50 in. w.c.  
Tons  
CFM Range  
Speed  
Motor  
Speed  
Motor  
WML-60C  
WML-80C  
WML-90C  
GT10 DD  
GT10 DD  
GT10 DD  
Low  
½ HP  
½ HP  
½ HP  
Med-Low  
Med-High  
High  
½ HP  
½ HP  
½ HP  
3
3
3
3
3
3
3
½ HP  
½ HP  
½ HP  
763 – 1505  
763 – 1505  
763 – 1505  
Med-Low  
Med-High  
MPL-90B  
MPL-100B  
MPL-120B  
MPL-130B  
GT12-10DD  
GT12-10DD  
GT12-10DD  
GT12-10DD  
Low  
Med-High  
High  
¾ HP  
¾ HP  
¾ HP  
¾ HP  
Med-High  
High  
¾ HP  
¾ HP  
¾ HP  
¾ HP  
¾ HP  
¾ HP  
¾ HP  
¾ HP  
1185 – 1553  
1185 – 1553  
1185 – 1553  
1185 – 1553  
High  
High  
High  
Table A-8 Direct Drive Blower Characteristics  
CFM  
External Static Pressure – Inches w.c.  
Furnace  
Model  
Blower  
Motor HP  
Motor FLA  
T  
Speed  
0.20  
0.30  
0.40  
0.50  
LOW  
MED-LOW  
MED-HIGH  
HIGH  
813  
813  
797  
763  
1170  
1423  
1505  
1144  
1381  
1444  
1118  
1291  
1359  
1063  
1220  
1291  
WML-C  
60 - 90  
GT10  
½ HP  
¾ HP  
7.0  
45-75°F  
LOW  
MED-LOW  
MED-HIGH  
HIGH  
1334  
1389  
1423  
1553  
1286  
1332  
1373  
1491  
1239  
1287  
1326  
1449  
1185  
1236  
1289  
1331  
MPL-B  
90-130  
GT12-10DD  
12.5  
50-80°F  
TIP:  
These Formulae will assist with the design of the ductwork and the determination of airflow delivery:  
Bonnet Output  
Bonnet Output  
CFM =  
SystemTemperatureRise=  
1.085x SystemTemperatureRise  
1.085x CFM  
(
)
(
)
30318 R4 9/9/2005  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table A-9 General Dimensions (Inches)  
Plenum Openings  
Cabinet  
Filter  
Flue  
Diameter  
Furnace  
Model  
Shipping  
Weight  
Return  
Width  
A
Depth  
B
Height  
C
Supply  
D x E  
Type  
Size  
H
Side  
Bottom  
WML-C  
MPL-B  
22  
22-1/8  
22-1/4  
55-1/4  
62  
19 x 19  
18 x 18  
18 x 18  
5
Permanent  
Permanent  
20 x 20 x 1  
20 x 20 x 1  
265  
292  
20-1/2 x 20-  
1/2  
22-1/4  
18 x 18  
18 x 18  
6
WML-C &  
MPL-B  
Down flow  
WML-C & MPL-B  
Horizontal  
30318 R4 9/9/2005  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX B: WIRING DIAGRAMS  
Beckett AF Burner Wiring Diagram  
30318 R4 9/9/2005  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Beckett AFII Burner Wiring Diagram  
30318 R4 9/9/2005  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Riello 40F3 and F5 Burner Wiring Diagram  
30318 R4 9/9/2005  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Riello 40BF3 Burner Wiring Diagram  
30318 R4 9/9/2005  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
resume operation and continue until the  
thermostat is satisfied. Restore the  
thermostat setting to a comfortable  
temperature.  
OPERATION OF OIL BURNER  
Once the furnace flue pipe, electrical  
and oil line connections have been  
made, use the following instructions to  
set the burner:  
Set the heat anticipator adjustment in  
the thermostat (if so equipped), by  
removing the "R" or "W" wire to the  
thermostat, then reading the amperage  
draw between the two wires. Failure to  
remove one of the wires from the  
thermostat while performing this test  
Shut off the electrical power to the  
furnace.  
Install an oil pressure gauge to the  
pressure port on the oil pump. (Refer to  
the oil pump specification sheet  
included with the burner instructions).  
could burn out  
the heat anticipator.  
Set the heat anticipator to the  
amperage measured.  
Restore electrical power to the furnace.  
Start the furnace and bleed all air from  
the fuel oil lines.  
NOTE: THE FURNACE SHOULD BE  
RUN THROUGH AT LEAST THREE  
FULL CYCLES BEFORE LEAVING  
THE INSTALLATION, TO ENSURE  
Close the purge valve and fire the unit.  
Allow the furnace to warm up to normal  
operating temperatures. During this  
time, set the pump pressure in  
accordance with the data provided in  
Appendix A, Table A-2, and A-5.  
THAT  
ALL  
CONTROLS  
ARE  
OPERATING PROPERLY AND AS  
EXPECTED.  
NOTE:  
POSITIVE  
ALL JOINTS IN ANY  
PRESSURE VENTING  
SYSTEM MUST BE CHECKED FOR  
LEAKS BEFORE LEAVING THE  
INSTALLATION SITE.  
When the furnace has reached "steady  
state" (after approximately 15 minutes).  
Set combustion air damper to get a  
TRACE of smoke.  
Check the system temperature rise.  
The temperature rise is the difference  
between the return air temperature  
measured at a point near the return air  
inlet, and the supply air temperature  
measured near the furnace outlet. If the  
temperature rise is too high, the airflow  
must be increased. If the temperature  
rise is too low, the fan should be  
slowed down.  
Turn off the burner. Observing the duct  
thermometer in the supply air stream,  
note the temperature at which the  
blower fan stops. The fan adjustments  
can be made by moving the dipswitch  
settings on the timer control board for  
fan off delay.  
To check the operation of the limit  
switch, shut off power to the furnace.  
Temporarily remove the neutral wire  
from the direct drive blower motor.  
Restore the electrical power to the  
furnace and set the thermostat above  
room temperature. After three or four  
minutes of burner operation, the limit  
control should turn the burner off.  
When the limit function test is  
complete, shut off electrical power to  
the furnace, replace the neutral wire to  
the blower fan motor, and then restore  
power. The blower fan will start up  
immediately. Once the temperature has  
dropped and the limit control has reset,  
the fan will operate until the fan off time  
is achieved. The oil burner will then  
30318 R4 9/9/2005  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX C-R7184 TROUBLESHOOTING  
R7184 DETAILED SEQUENCE OF OPERATION (FIGURE 7)  
Power is applied to unit. The R7184 completes a self-diagnostic procedure. If no light or flame is present, and unit  
passes its self-diagnostic procedure, the control enters into the idle mode.  
Thermostat calls for heat:  
A) Safety check is made for flame (4 second delay).  
1) If flame is not present, the R7184 will apply power to the burner motor and igniter.  
2) If flame is present, the control remains in the idle state.  
B) Unit enters a pre-purge period of 15 seconds.  
C) After 10 seconds, control checks for flame presence.  
1) If flame is not present, the R7184 enters the trial for ignition state.  
2) When flame is present, the control enters lock out mode.  
D) Control monitors the burner flame.  
1) When flame is present, the control enters ignition carryover state. (Continues to spark for 10 sec.).  
a) Provides continuous spark after flame is sensed to assure that burner remains lit.  
b) Turns on LED diagnostic light.  
c) Starts carryover timer.  
(i)  
Flame and call for heat are monitored.  
If flame is lost and lockout timer has not expired, R7184 will return to trial for ignition state.  
If flame is lost and lockout timer has expired, R7184 will enter the recycle state.  
Recycle timer starts.  
Burner motor and igniter and solenoid valve are turned off.  
LED diagnostic light flashes slowly.  
E) Carryover timer expires.  
1) Enters run state.  
a) Igniter turns off.  
Combustion continues until thermostat is satisfied, or R7184 detects a loss of flame and enters into Recycle Mode.  
F) Thermostat is satisfied - call for heat is terminated:  
a) R7184 shuts off burner motor and solenoid valve.  
(i)  
If control utilizes a blower motor off delay, after 30 seconds, flame presence is checked.  
If flame is not present, the R7184 LED diagnostic light is off and returns to idle state.  
If flame is presence is detected, the control enters lock out mode.  
30318 R4 9/9/2005  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R7184 INTERRUPTED ELECTRONIC OIL PRIMARY CONTROL  
FIGURE 7  
ELECTRONIC FAN TIMER BOARD ON CONTROL PANEL  
FIGURE 8  
30318 R4 9/9/2005  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IDLE STATE  
THERMOSTAT CALLS FOR HEAT  
R7184  
SEQUENCE of  
OPERATION  
SAFETY CHECK FOR FLAME (5 SEC.)  
REMAINS IN IDLE STATE  
FLAME  
NO FLAME  
BURNER MOTOR & IGNITOR START  
10 SEC.  
SAFETY CHECK FOR FLAME (5 SEC.)  
NO FLAME  
FLAME  
SOLENOID VALVE OPENS  
LOCKOUT STATE  
TRIAL FOR IGNITION  
R7184:  
Shuts off burner motor  
Shuts off igniter  
Shuts off Solenoid Valve  
Fast Flashes LED Diagnostic  
Light  
BURNER FLAME MONITORED  
NO FLAME  
FLAME  
CARRYOVER STATE  
Provides continuous spark  
LED diagnostic light ON  
Start Carryover Timer  
FLAME LOST  
TO EXIT LOCKOUT  
PRESS RESET  
FLAME  
CARRYOVER TIMER EXPIRES  
FLAME LOST  
FLAME LOST  
FLAME  
RUN STATE  
Igniter turns off.  
RECYCLE TIMER STARTS  
R7184:  
THERMOSTAT SATISFIED  
R7184 SHUTS OFF:  
Burner Motor  
Solenoid Valve  
Shuts off Solenoid Valve  
Shuts off Igniter  
Shuts off Burner Motor  
Slow Flashes LED  
diagnostic light  
LED Diagnostic Light  
30 SEC.  
SAFETY CHECK FOR FLAME (5 SEC.)  
RECYCLE TIMER EXPIRES  
(60 SECONDS  
NO FLAME  
FLAME  
RETURNS TO IDLE STATE  
30318 R4 9/9/2005  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table C-1: ELECTRONIC FAN TIMER BOARD (EFT) DETAILED SEQUENCE OF OPERATION  
Mode  
Action  
System Response  
a. EFT closes oil primary control T - T connections).  
b. Ignition system and R7184 oil primary control start the furnace. Oil flows as long as  
the oil primary control senses flame.  
Thermostat calls for heat. ("W"  
terminal is energized).  
c. Burner motor is energized and heat "fan on" delay timing begins. When timing is  
complete, the circulator fan is energized at heat speed.  
a. R7184 oil primary control is de-energized, terminating the burner cycle.  
b. Heat "fan off" delay timing begins. Length of delay depends on EFT dipswitch  
settings. When timing is complete, the circulator fan is de-energized.  
c. EFT returns to standby mode, (Oil primary control and circulator fan are off, unless  
continuous fan operation is selected at the thermostat).  
Thermostat ends call for heat.  
("W" terminal is de-energized).  
HEAT  
a. Oil primary control locks out within lockout timing, (30 seconds).  
b. Burner motor is de-energized. (Even though thermostat is still calling for heat).  
Burner fails to light.  
c. If circulator fan has started, it continues through the selected heat “fan off” delay  
period.  
a.  
b.  
Burner motor is de-energized and oil primary control goes into recycle mode.  
If the selected heat “fan off” delay timing is longer than the recycle delay  
timing, the circulator fan continues to run through the next trial for ignition.  
Established flame fails.  
Thermostat begins call for  
cool. (G and Y terminals are  
energized).  
a. Cooling contactor is energized immediately.  
b. Circulator fan is energized at cool speed.  
COOL  
FAN  
Thermostat ends call for cool.  
(G and Y terminals are de-  
energized).  
a. Cooling contactor is de-energized immediately.  
b. Circulator fan turns off immediately.  
Thermostat begins call for fan.  
(G terminal is energized).  
a. Circulator fan is energized immediately at cooling speed.  
a. Circulator fan is de-energized immediately.  
Thermostat ends call for fan.  
(G terminal is de-energized).  
a. Oil primary control shuts off burner.  
b. Circulator fan is energized immediately at heat speed.  
c. EFT opens oil primary control T - T connections. Circulating fan runs as long as  
limit string stays open.  
Limit switch string opens.  
d. If there is a call for cooling or fan, the circulating fan switches from heating to  
cooling speed.  
a. EFT begins heat “fan off” delay sequence.  
LIMIT  
b. Circulating fan turns off after the selected heat “fan off” timing.  
c. EFT re-closes oil primary control T - T connections.  
d. Oil primary control is energized, initiating burner light off.  
Limit switch string closes  
(with existing call for heat).  
a.  
b.  
Circulator fan turns off when heat “fan off” delay time is complete.  
Normal operation resumes; EFT control is in standby mode awaiting next  
thermostat command.  
Limit switch string closes  
(without existing call for heat).  
a. Circulating fan is energized when there is no call for heat, cool, or fan.  
Continuous circulating fan is  
connected.  
FAN  
EAC  
b. If fan operation is required by a call for heat, cool, or fan, the EFT switches off the  
continuous fan speed tap before energizing the other fan speed.  
Electronic air cleaner (EAC) connections are energized when the heat or cool  
speed of the circulator fan is energized. EAC connections are not energized when  
the optional continuous fan terminal is energized.  
Electronic Air Cleaner is  
connected.  
HUM Humidity control is connected.  
Humidifier connections are energized when the oil burner motor is energized.  
30318 R4 9/9/2005  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R7184 LED DIAGNOSTIC LIGHT  
TROUBLESHOOTING  
The LED diagnostic light has several  
functions. It indicates the state or mode  
in which the oil burner is operating. It will  
also indicate fault conditions, and help  
determine cad cell resistance while the  
burner is operating.  
IMPORTANT: Due to the potential  
hazard of line voltage, only a trained,  
experienced service technician should  
perform the troubleshooting procedure.  
Electrical Shock Hazard.  
Troubleshooting is done with the system  
powered. Be careful to observe all  
necessary precautions to prevent  
electrical shock or equipment damage.  
PRELIMINARY STEPS:  
Check the diagnostic light for indications  
of burner condition. Refer to R7184 LED  
DIAGNOSTIC LIGHT section for details.  
NORMAL CONDITIONS:  
PRELIMINARY CHECKS:  
The LED diagnostic light will turn on  
when the burner enters the carryover  
state; the point at which ignition spark is  
on, and will remain on through the run  
state, where the ignition spark is  
terminated but the burner continues to  
fire.  
Make sure that limit switches are closed  
and those contacts are clean.  
Check for line voltage power on the oil  
primary control black and white lead  
wires.  
WHEN SIMULATING A CALL FOR  
HEAT AT THE R7184, DISCONNECT  
AT LEAST ONE THERMOSTAT LEAD  
WIRE FROM THE T1 - T2 TERMINALS  
TO PREVENT DAMAGE TO THE  
THERMOSTAT. NEGLECTING THIS  
PROCEDURE MAY BURN OUT THE  
Refer to Table C-4 or C-5 for further  
troubleshooting information.  
The LED diagnostic light will turn off at  
the end of the burner cycle as the R7184  
enters the idle state, and will remain off  
until the next heating cycle.  
HEAT  
ANTICIPATOR  
OF  
A
FAULT CONDITIONS:  
STANDARD 24 VAC THERMOSTAT,  
OR CAUSE HARM TO COMPONENTS  
If the LED diagnostic light is flashing  
quickly; 1 Hz (½ second on / ½ second  
off), the R7184 is in the lockout state or  
in restricted mode. To exit the lockout  
state, press the reset button.  
WITHIN  
A
MICRO-ELECTRONIC  
THERMOSTAT.  
Before checking the oil primary control,  
perform these preliminary checks, (repair  
or replace controls as necessary):  
If the LED diagnostic light is flashing  
slowly; ¼ Hz (2 seconds on / 2 seconds  
off), the R7184 is in the recycle state.  
This indicates that flame sensing was  
lost after the lockout timer expired during  
the ignition carryover state. The R7184  
will return to the idle state within 60  
seconds.  
Check the power supply; fuse  
box or breaker, any service switches, all  
wiring connections, and burner motor  
reset button (if equipped).  
Check the limit switches to  
ensure that the switch contacts are  
closed.  
CAD CELL CONDITION:  
Check the electrode gap and  
If the LED diagnostic light is off, the cad  
cell is not sensing flame.  
position.  
Check the contacts between the  
oil primary control and the electrodes.  
If the LED diagnostic light is on, the cad  
cell is sensing flame, or viewing ambient  
light.  
Check oil supply (tank gauge).  
Check the oil nozzle, oil filter,  
The resistance of the cad cell may be  
checked while the R7184 is in the run  
state by pressing the reset button. The  
LED diagnostic light will flash the  
following code:  
and oil valves.  
Check the piping or tubing to  
the oil tank.  
TABLE C-2: CAD CELL RESISTANCE  
Check the oil pump pressure.  
CHECK OIL PRIMARY CONTROL AND  
IGNITER  
Flashes  
Resistance in Ohms  
Less than 400  
If the trouble does not appear to be in  
the burner or ignition hardware, check  
the oil primary control and the igniter by  
using the following equipment:  
1
2
3
4
Between 400 - 800  
Between 800 – 1600  
Between 1600- 5000  
Screwdriver.  
Voltmeter (0 - 150 VAC)  
Insulated jumper wires with both ends  
stripped.  
30318 R4 9/9/2005  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table C-3: R7184 TROUBLESHOOTING  
Condition: Burner motor does not start when there is a call for heat.  
Procedure  
Status  
Corrective Action  
1. Check that limit switches are  
closed and contacts are clean.  
N/A  
N/A  
2. Check for line voltage power at  
the oil primary control. Voltage  
should be 120 Vac between the  
black and white lead wires on  
the oil primary control.  
N/A  
N/A  
3. Check indicator light with burner  
off, no call for heat (no flame).  
Cad cell is defective, sees external light, or connections have  
shorted. Go to step 4.  
Indicator light is on.  
Indicator light turns off.  
Eliminate external light source or permanently shield cad cell.  
Replace cad cell with new cad cell and recheck.  
If indicator light does not turn off, remove yellow lead wires  
from R7184 and recheck.  
4. Shield cad cell from external  
light.  
Indicator light stays on.  
If indicator light is still on, replace the R7184 control.  
If the indicator light turns off, replace cad cell bracket  
assembly.  
5. Verify that the oil valve is closed  
during the “valve on delay”  
period by opening view port and  
verifying that no flame is present  
during the 15-second “valve on  
delay”.  
Indicator light is on.  
Burner starts.  
If flame is present, replace the oil valve.  
Trouble is in thermostat circuit. Check thermostat-wiring  
connections.  
6. Jumper thermostat (T -T)  
terminals on R7184  
If connections are clean and tight, check thermostat wires for  
continuity.  
Disconnect line voltage power and open line switch.  
Check all wiring connections.  
IMPORTANT  
First remove one thermostat lead  
wire.  
Tighten any loose connections and recheck.  
Burner does not start.  
If burner still doesn't start, replace R7184.  
If burner still doesn't start, check the oil burner motor. It may be  
seized or burned out.  
Condition: Burner starts then locks out on safety with indicator light flashing at 1/2 second on, 1/2 second off.  
Procedure  
Status  
Corrective Action  
Indicator light stops flashing.  
Go to Step 8.  
7. Reset oil primary control by  
pushing in and releasing red  
reset button.  
Indicator light continues to flash  
at 1/2 second on, 1/2 second off  
rate.  
Verify that the control is not in restricted mode. (See notes at end of  
this table.). If not in restricted mode, replace R7184  
30318 R4 9/9/2005  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Condition: Burner starts then locks out on safety with indicator light flashing at 1/2 second on, 1/2 second off. (Cont.)  
Procedure  
Status  
Corrective Action  
Spark igniter could be defective. Check for line voltage at igniter  
terminals. If line voltage is present, replace R7484.  
Ignition is off  
8. Listen for spark after burner  
turns on (after 2 second delay).  
Ignition is on.  
Go to Step 9.  
Ignition is on but no oil is being  
sprayed into the combustion  
chamber.  
Wait for “Valve ON” delay to complete. Check oil supply, and oil line  
valve. Check for filter blockage or seized oil pump.  
Indicator light is on until the  
control locks out and starts Replace R7184  
flashing during lockout.  
9. Check indicator light after flame  
is established, but before oil  
primary control locks out.  
Indicator light stays off.  
Burner locks out.  
Go to step 10.  
10. Check cad cell sighting for view  
of flame.  
a. Disconnect line voltage power  
and open line switch.  
Go to step 11.  
b. Unplug cad cell and clean cad  
cell face with soft clothe.  
Check sighting for clear view  
of flame. Replace cad cell in  
socket.  
Burner keeps running.  
Indicator light is on.  
System is OK.  
c. Reconnect line voltage power  
and close line switch.  
d. Start burner.  
11. Check cad cell.  
a. Disconnect line voltage power  
and open line switch.  
Remount control onto burner housing. Go to step 6.  
b. Remove existing cad cell and  
replace with new cad cell.  
c. Disconnect all wires from  
thermostat  
terminals  
to  
ensure that there is no call for  
heat.  
Indicator light is off.  
Go to step 12.  
d. Reconnect line voltage power  
and close line switch.  
e. Expose new cad cell to bright  
light such as a flashlight.  
12. Check cad cell bracket  
assembly.  
a. Disconnect line voltage power  
and open line switch.  
Indicator light is on.  
Indicator light is off.  
Replace cad cell bracket assembly.  
b. Remove cad cell wires from  
quick connect connectors on  
the R7184 and leave control  
lead wires open.  
c. Apply power to device.  
Replace R7184.  
d. Place jumper across cad cell  
terminals after burner motor  
turns on.  
NOTE: Restricted Mode - (Limited Reset): In order to limit the accumulation of unburned oil in the combustion chamber, the control can be reset  
only 3 times, after which, the control locks out. The reset count returns to zero each time a call for heat is successfully completed.  
To reset from RESTRICTED MODE: press and hold the reset button for 30 seconds. When the LED flashes twice, the device has reset.  
NOTE: Disable function: Pressing and holding the reset button will disable all functions until the button is released. The burner will restart at the  
beginning of the normal heat cycle on SAFETY CHECK.  
30318 R4 9/9/2005  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE C4: SYSTEM AND GENERAL TROUBLESHOOTING  
Problem  
Possible Cause  
Remedy  
Check thermostat and adjust. Also, check thermostat for accuracy; if it is  
a mercury switch type, it might be off level.  
Thermostat not calling for heat.  
Check furnace switch, main electrical panel furnace fuse or circuit  
breaker. Also look for any other hand operated switch, such as an old  
poorly located furnace switch, which was not removed during furnace  
replacement.  
No power to furnace.  
Thermostat faulty.  
Furnace will not start.  
Remove thermostat wires from oil primary control terminals T-T. Place a  
jumper across T-T. If furnace starts, replace thermostat, thermostat sub-  
base (if equipped), or both.  
Check reset button on oil primary control. Remove thermostat wires  
from oil primary control terminals T1 - T2. Check for 24v across T -T. If  
no voltage is present, check for 115v to oil primary control. If 115v is  
present, go to Table C-3.  
Oil primary control faulty.  
Photo Cell wiring shorted or room  
light leaking into photo cell  
compartment  
Check photo cell (cad cell) wiring for short circuits. Also, check for room  
light leaking into cad cell compartment. Repair light leak if necessary.  
See Table C-3.  
Furnace will not start.  
Check for open limit or auxiliary limit. Also, check internal wiring  
connections; loose connectors, etc.  
Open safety switch.  
No fuel oil.  
Check fuel oil supply. Check that all hand operated fuel oil valves are in  
the open position. Fill oil storage tank if necessary.  
Replace nozzle with high quality replacement. Use rating plate or Tables  
in Appendix A as a guide.  
Clogged nozzle.  
Clogged oil filter.  
Replace oil tank filter or in-line filter if used.  
Furnace will not start without  
first pushing oil primary  
control reset button.  
Connect pressure gauge to oil pump. Adjust pump pressure, or replace  
oil pump if necessary. Ensure that erratic pressure readings are not  
caused by defective fuel oil line.  
Low oil pump pressure.  
(Happens on frequent basis)  
Air getting into fuel oil lines, or fuel  
oil line dirty, clogged, or in some  
manner defective.  
Check fuel oil lines. Replace any compression fittings found with high  
quality flared fittings. Check for any signs of oil leaks. Any oil leak is a  
potential source of air or contaminants.  
Check burner motor. If burner motor is cutting out on over-load,  
determine why. Replace if necessary.  
Defective burner motor.  
Photo Cell (Cad Cell) defective.  
No fuel oil.  
If cad cell is dirty, clean it. (Determine why cad cell is getting dirty). If  
cad cell is poorly aimed, realign it. NOTE: The photocell should have a  
resistance of 100K in absence of light; a maximum of 1500 in the  
presence of light. Ensure that room light is not leaking into the cad cell  
compartment. (See diagnostic light section).  
Furnace starts, but cuts out  
requiring manually resetting  
the oil protector reset button.  
Check fuel oil supply. Check that all hand operated fuel oil valves are in  
the open position. Fill oil storage tank if necessary.  
Replace nozzle with high quality replacement. Use rating plate or Tables  
in Appendix A as a guide.  
Clogged nozzle.  
Clogged oil filter.  
Replace oil tank filter or in-line filter if used.  
Connect pressure gauge to oil pump. Adjust pump pressure, or replace  
oil pump if necessary. Ensure that erratic pressure readings are not  
caused by defective fuel oil line.  
Low oil pump pressure.  
Furnace starts, but cuts out  
requiring manually resetting  
the oil protector reset button.  
Air getting into fuel oil lines, or fuel  
oil line dirty, clogged, or in some  
manner defective.  
Check fuel oil lines. Replace any compression fittings found with high  
quality flared fittings. Check for any signs of oil leaks. Any oil leak is a  
potential source of air or contaminants.  
Check burner motor. If burner motor is cutting out on over-load,  
determine why. Replace if necessary.  
Defective burner motor.  
Water or contaminants in oil.  
Frozen oil line.  
Drain fuel oil storage tank, replace fuel oil. (Consult with fuel oil  
supplier).  
Gently warm oil line. Insulate oil line. (Outdoor piping size may require  
increased diameter).  
30318 R4 9/9/2005  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE C-4: SYSTEM AND GENERAL TROUBLESHOOTING continued  
Problem  
Possible Cause  
Remedy  
Electrodes out of adjustment or  
defective.  
Check electrode settings. Check electrodes for dirt build-up or cracks in  
porcelain.  
Poor transformer high voltage  
Check contacts between the igniter and electrodes. If OK, replace the  
igniter  
connections  
transformer.  
or  
defective  
Oil burner sputtering at  
nozzle  
Fuel oil filter clogged.  
Defective oil pump.  
Replace fuel oil storage tank filter and / or fuel oil in-line filter.  
Check burner motor / fuel oil pump coupling. Check oil pump pressure.  
Replace fuel oil pump if necessary.  
Fuel oil line partially clogged or  
contains air.  
Bleed air from oil line. If problem persists, replace oil line.  
System temperature rise ideally should not exceed 85°F. Check for  
clogged air filters. Check blower fan for excess dirt build-up or debris.  
Speed up blower fan if necessary.  
System temperature rise too high.  
Check “fan off” delay timing setting. Use a duct thermometer in the  
supply air plenum take-off or first few inches of the supply air trunk duct.  
Ideally, the fan will shut off at a temperature of 90° - 100°F. Manipulate  
the dip switch settings to come as close as possible to this “fan off”  
temperature.  
Poor “fan off” delay timing  
selection, (fan stops too soon).  
Excessive  
fuel  
oil  
consumption.  
Fuel oil leak.  
Check fuel oil line for leaks. Repair or replace if necessary.  
Check stack temperature. Stack temperatures will normally range from  
350° to 450°F. Check draft regulator. Draft should be set to 0.02 in. w.c.  
Stack temperature too high.  
Check thermostat heat anticipator setting against measured amperage  
draw. Increase heat anticipator setting if necessary. If the thermostat is  
being influenced by drafts, sunlight, duct work, etc., relocate to more  
suitable location.  
Thermostat improperly adjusted or  
in poor location.  
Insufficient  
adjustment at oil burner, or  
improper draft pressure.  
combustion  
air  
Adjust the oil burner combustion air band and draft regulator to gain the  
highest practical CO2 or lowest practical O2 content in the flue gases.  
See Burner Set Up.  
Too much smoke.  
Check for soot build-up in heat exchanger flue passages, especially in  
the outer radiator.  
Heat exchanger partially clogged.  
Check alignment. Blast tube should be centered with fire pot burner  
opening. Oil burner head should be ¼ inch back from the inside surface  
of the fire pot.  
Poor alignment between oil burner  
blast tube and fire pot.  
Soot building up on blast  
tube (end coning).  
Flame impingement caused by  
Incorrect nozzle angle.  
Check nozzle size and angle. (See Appendix A). Check distance from  
head to inside surface of the fire pot.  
Defective fire-pot  
Check fire-pot. Repair or replace.  
Clean or replace air filter.  
Airflow blocked or dirty air filter.  
Check thermostat heat anticipator setting against measured amperage  
draw. Increase heat anticipator setting if necessary. If the thermostat is  
being influenced by drafts, sunlight, duct work, etc., relocate to more  
suitable location.  
Thermostat  
location.  
adjustments  
or  
Check all dampers. Open closed dampers including registers in unused  
rooms. Check system temperature rise. If temperature rise is too high,  
speed up blower fan.  
Insufficient airflow.  
Furnace will not warm home  
to desired temperature.  
Test high limit function of all limit switches. Use a duct thermometer to  
assess accuracy of limit control. Check for obstructions to airflow around  
limit switch bi-metal elements. Replace control if necessary.  
Defective high limit control.  
Under-sized nozzle.  
Check nozzle. If problem is not caused by air flow problems, use larger  
nozzle, if permitted by rating plate.  
Blower  
intermittently on overload.  
fan  
motor  
stopping  
stopping  
Check blower fan motor amperage draw. Check motor ventilation ports,  
clean if necessary. Replace motor if necessary.  
Burner motor  
intermittently on overload.  
Improper distribution of heat.  
Check burner motor. Replace if necessary.  
Home does not heat evenly  
This is not likely to be a furnace problem. Balance duct system.  
30318 R4 9/9/2005  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE C-4: SYSTEM AND GENERAL TROUBLESHOOTING continued  
Problem  
Possible Cause  
Remedy  
Airflow blocked or dirty air filter.  
Clean or replace air filter.  
Supply air temperature too  
hot.  
Check all dampers. Open closed dampers including registers in unused  
rooms. Check system temperature rise. If temperature rise is too high,  
speed up blower fan.  
Insufficient airflow.  
Excess airflow.  
Check system temperature rise. Slow down blower fan if necessary.  
Supply air temperature too  
cool.  
Check supply air ductwork. Seal leaky joints and seams. Insulate  
ductwork if necessary.  
Excessive duct losses.  
Fan control "fan on" setting too  
low.  
Increase "fan on” dipswitch settings on EFT if control has this option.).  
Register air deflectors may help.  
Supply air temperature too  
cool during first moments of  
furnace cycle.  
Check supply air ductwork. Seal leaky joints and seams. Insulate  
ductwork if necessary.  
Excessive duct losses.  
Where the circuit breaker or fuse is  
located in the main electrical panel.  
How and where to visually inspect the  
venting system for leaks or other  
problems.  
FINAL CHECK OUT  
ENSURE  
DEVICES  
THAT  
AND  
ALL  
SAFETY  
ELECTRICAL  
Where the furnace switch is located,  
and the switch "on" and "off" positions if  
not obvious.  
How to inspect, clean and replace the  
air filter, and other homeowner  
maintenance procedures.  
COMPONENTS HAVE BEEN SET  
FOR NORMAL OPERATION.  
ENSURE THAT ALL ELECTRICAL  
CONNECTIONS ARE TIGHT AND  
THAT THE WIRING IS SECURE.  
Where the oil shut-off valve from the oil  
storage tank is located.  
Who to call for emergency service and  
routine annual service.  
How to operate the thermostat, and  
other related accessories.  
The terms and conditions of the  
manufacturer's warranty and the  
IMPORTANT:  
How to operate the manual reset button  
on the primary control, and especially  
when not to push the reset button.  
contractor's  
warranty.  
Please ensure that the homeowner is  
informed and understands:  
30318 R4 9/9/2005  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PARTS LISTING: COUNTERFLOW HORIZONTAL MODEL: WML C  
Description  
Ref. No.  
PART NO.  
1
2
3
4
5
6
7
Right and Left Side Panel  
Rear Panel Baffle  
Rear Panel  
Blower Division Panel Assembly  
Base Panel Assembly  
Front Panel  
30072L  
27918  
30272L  
30311  
29007  
30073L  
30074L  
28673  
Blower Access Door  
Door Handle – P2-41  
Logo Bezel  
28479  
Logo Label  
28563  
8
9
End Panel  
29013L  
27876  
27068  
2700WP  
29873  
29005  
28722  
2080175  
21994  
1061A  
2080176  
3011325A  
21260  
21306  
2180032  
28723  
30239  
28654  
30268  
30265  
29388  
Heat Exchanger Assembly  
Firepot Retainer Bracket  
Replacement Combustion Chamber  
Oil Burner Mounting Plate Assembly  
Flue Pipe Connecting Flange  
Junction Box Cover  
10  
11  
12  
13  
14  
15  
16  
17  
Pouch Gasket  
Flue Pipe Gasket (2 per Unit)  
Radiator Cleanout Cover Assembly  
Cleanout Cover Gasket  
Casing Clean-out Cover  
Filter Frame  
Filter Frame End Support  
Air Filter – 20 x 20 x 1 (Permanent)  
Junction Box  
Channel Wire Retainer  
Limit Control 60T11BOF L180º F  
Wire Harness Control  
Wire Harness Blower Direct drive  
Fan Timer Control: Honeywell ST9103A or UTC 1158-150  
Draft Regulator 5”  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
27494  
29  
Beckett oil Burner AF76BNHS  
Burner Motor 1/7 HP 3450 RPM PSC  
Beckett Clean-cut Oil Pump  
Solid State Igniter  
30288  
29689  
29688  
29522  
Primary Combustion Control R7184A  
Flame Retention Head  
Nozzle 0.65 / 80º A  
29664  
11961 (F3)  
210086  
30313  
28142  
26430  
30  
Blower Assembly, Complete, Direct Drive, ½ hp, 4-Speed  
Blower Housing and Wheel, GT10 DD  
Blower Wheel, GT10 DD  
Blower Motor, ½ hp, 4-Speed  
Motor Mounting Band – TR6884B  
Motor Mount Arms – 10-10 DD Blower (3 per unit)  
Motor Run Capacitor, 10 mfd @ 370 vac  
Capacitor Strap  
26088  
17811  
26251  
27743  
27760  
Low Fire Kit  
29880  
Low Firing Rate Baffle  
Nozzle, .50/80° A  
25521101  
29389  
30318 R4 9/9/2005  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PARTS LISTING: COUNTERFLOW HORIZONTAL MODEL: WML C  
Ref. No.  
Description  
Auxiliary Limit 60T11BOF L140º F  
Transformer  
Control Panel  
Wire Harness, Junction Box to Control  
Wire Harness, Supply  
PART NO.  
29198  
31  
32  
33  
34  
35  
36  
37  
27738  
30190  
30264  
29366  
30240  
30195  
Limit Cover, Left  
Limit Cover, Right  
PARTS LISTING: COUNTERFLOW HORIZONTAL DIRECT VENT MODEL: WML CB2U  
Description PART NO.  
Ref. No.  
All parts are the same as listed on the previous pages for Model WML-C except where noted below.  
12  
Oil Burner Mounting Plate Assembly  
Oil Burner Mounting Plate  
Sight Glass Cover Plate  
Sight Glass Gasket (2 per unit)  
Sight Glass  
Flue Connector Assembly 6” to 4” 90º Elbow  
Pouch Gasket (Second gasket required for Direct Vent)  
Flue Collar Gasket (Second gasket required for Direct Vent)  
Beckett Oil Burner AFII 85  
Burner Motor 1/7 HP 3450 RPM PSC  
Beckett Clean-cut Oil Pump A2EA6520  
Solid State Ignitor 10SAY-01  
Primary Combustion Control R7184P  
Air Tube Combination FBX80HGXS  
Flame Retention Head (FB3)  
29872  
29867  
29850  
29870  
29876  
28952  
2080175  
21994  
30069  
28907  
29688  
28558  
29649  
28561  
28533  
28017  
13  
14  
15  
34  
Nozzle, .60/60ºA (WML-80CB2U only)  
PARTS LISTING: VESTIBULE KIT: WML C  
Ref. No.  
Description  
PART NO.  
30554  
Vestibule Kit  
Door Handle  
Base Panel  
28673  
29019  
Top Panel  
Door Panel  
Left Side Panel  
Right Side Panel  
21437L  
29022L  
30527L  
30528L  
PARTS LISTING: SUB BASE FOR COMBUSTIBLE FLOOR INSTALLATION: WML C  
Ref. No.  
Description  
PART NO.  
06000075  
Sub Base  
30318 R4 9/9/2005  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
30318 R4 9/9/2005  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PARTS LISTING: COUNTERFLOW HORIZONTAL MODEL: MPL  
Ref. No.  
Description  
PART NO.  
1a  
1b  
2
3
4
5
6
7
Right Side Panel  
Left Side Panel  
Side Panel Heat Exchanger Support (2 per unit)  
Rear Panel  
Blower Division Panel Assembly  
Base Heat Exchanger Support  
Front Panel  
30360L  
30351L  
27038  
30353L  
30397  
26975  
30350L  
30363L  
28673  
28479  
28563  
30352  
30380  
27068  
27000WP  
29873  
29871  
28306  
2080175  
21994  
1061A  
2080176  
3011325A  
21260  
21306  
2180032  
28723  
30239  
29197  
29662  
30392  
30391  
29388  
30364  
29366  
30240  
30195  
12240  
27738  
30355  
30390  
30393  
Blower Access Door  
Door Handle – P2-41  
Logo Bezel  
Logo Label  
8
9
10  
11  
12  
End Panel  
Heat Exchanger Assembly  
Firepot Retainer Bracket  
Replacement Combustion Chamber  
Oil Burner Mounting Plate Assembly  
Inspection Door Gasket  
Flue Connector  
13  
14  
15  
16  
Pouch Gasket  
Flue Pipe Gasket  
Radiator Cleanout Cover Assembly  
Cleanout Cover Gasket  
Casing Clean-out Cover  
Filter Frame  
Filter Frame End Support  
Air Filter – 20 x 20 x 1 (Permanent)  
Junction Box  
Channel Wire Retainer  
Limit Control 60T11BOF L150º F  
Limit Control 60T11BOF L160º F  
Wire Harness Junction Box to Control  
Wire Harness Blower Direct drive  
Fan Timer Control: Honeywell ST9103A or UTC 1158-150  
Air Baffle  
Wire Harness, Supply  
Limit Cover, Left  
Limit Cover, Right  
Draft Regulator 6”  
Transformer  
Control Panel  
Wire Harness Burner to Timer Board  
Wire Harness Transformer to Timer Board  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
30318 R4 9/9/2005  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PARTS LISTING: COUNTERFLOW HORIZONTAL MODEL: MPL  
Description  
PART NO.  
Ref. No.  
37  
Beckett oil Burner AF76XN  
30389  
29689  
29688  
29522  
29664  
Burner Motor 1/7 HP 3450 RPM PSC  
Beckett Clean-cut Oil Pump A2EA6520  
Solid State Ignitor FRANCE 10SAY-04  
Primary Combustion Control R7184A  
Air Tube Combination AF76XN  
27610  
Flame Retention Head (MPL 80, to 120)  
Flame Retention Head (MPL 130)  
Nozzle 1.00 / 60º A (MPL 120)  
11961 (F3)  
12646 (F6)  
27104  
Nozzle 1.10 / 70º A (MPL 130)  
2100101  
38  
Blower Assembly, Complete, Direct Drive, ½ hp, 4-Speed  
Blower Housing and Wheel, GT12-10 DD  
Blower Wheel, GT12-10 DD  
30387  
17559  
29692  
27161  
17811  
17812  
27745  
29026  
Blower Motor, 3/4 hp, 4-Speed  
Motor Mounting Band – TR6884B  
Motor Mount Arms – 12-12 DD Blower (3 per unit)  
Motor Run Capacitor, 20 mfd @ 370 vac  
Blower Slide Rail  
39  
40  
Auxillary Limit L130°F 60T11 BOF  
Junction Box Cover  
30388  
28722  
PARTS LISTING: COUNTERFLOW HORIZONTAL DIRECT VENT MODEL: MPL BB2U  
Description  
PART NO.  
Ref. No.  
All parts are the same as listed on the previous pages for Model MPL-B except where noted below.  
Oil Burner Mounting Plate Assembly  
Oil Burner Mounting Plate  
12  
29872  
29867  
29850  
29870  
29876  
28952  
2080175  
21994  
30430  
28907  
29688  
28558  
29649  
28561  
28533  
Sight Glass Cover Plate  
Sight Glass Gasket (2 per unit)  
Sight Glass  
13  
14  
15  
37  
Flue Connector Assembly 6” to 4” 90º Elbow  
Pouch Gasket (Second gasket required for Direct Vent)  
Flue Collar Gasket (Second gasket required for Direct Vent)  
Beckett Oil Burner AFII 150  
Burner Motor 1/7 HP 3450 RPM PSC  
Beckett Clean-cut Oil Pump A2EA6520  
Solid State Ignitor 10SAY-01  
Primary Combustion Control R7184P  
Air Tube Combination FBX80HGXS  
Flame Retention Head (FB3)  
Nozzle, 0.85/70ºA (MPL-120BB2U only)  
PARTS LISTING: SUB BASE FOR COMBUSTIBLE FLOOR INSTALLATION: MPL B  
Ref. No.  
Description  
PART NO.  
006000073  
Sub Base  
30318 R4 9/9/2005  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
30318 R4 9/9/2005  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HOMEOWNER’S REFERENCE TABLE  
Model No.  
Serial No.  
Date Installed  
Contractor  
Contact  
Address  
Postal Code  
Telephone No.  
After Hours No.  
FUEL SUPPLIER  
Fuel Oil Supplier  
Contact  
Telephone No.  
After Hours No.  
IF DIFFERENT FROM INSTALLATION CONTRACTOR:  
Service Tech.  
Telephone No.  
After Hours No.  
30318 R4 9/9/2005  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTES:  
30318 R4 9/9/2005  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6800 Base Line, Wallaceburg, Ontario, N8A 5E5, Can. Tel: (519) 627-0791 Fax: (519) 627-4719  
2201 Dwyer Avenue, Utica, New York, 13504, USA. Tel: (315) 797-1310 Fax: (315) 724-9319  
85 Middle Road, Dunkirk, New York, 14048, USA Tel: (716) 366-5500 Fax: (716) 366-1209  
30318 R4 9/9/2005  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Echo Blower 99944200300 User Manual
Echo Trimmer 670 200 User Manual
FEIN Power Tools Trimmer BLs 25 User Manual
Fender Guitar Artist Series User Manual
Fisher Price Motorized Toy Car P8812 User Manual
Freecom Technologies Computer Drive FHD xx User Manual
Garland Range C0836 1 User Manual
GCC Printers Printer Elite 12ppm User Manual
GE Fryer 168998 User Manual
GE Ventilation Hood ZVB36BN User Manual