®
POWER SYSTEMS, INC.
Owner’s Manual
GTS “HS”Type
Automatic
Transfer Switch
Models: 004635-3
(200 Amp, 250 Volts)
and 004678-2
(100 Amp, 250Volts)
This manual should remain with the unit.
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
• Remove all jewelry (such as rings, watches,
bracelets, etc.) before working on this equipment.
• If work must be done on this equipment while
standing on metal or concrete, place insulative
mats over a dry wood platform. Work on this
equipment only while standing on such insulative
mats.
Safety Rules..........................................Inside Front Cover
Section 1 — General Information ..................................2
1.1 Introduction ............................................................2
1.2 Equipment Description ............................................2
1.3 Transfer Switch Data Decal......................................2
1.4 Transfer Switch Enclosure ......................................2
1.5 Safe Use Of Transfer Switch ....................................2
Section 2 — Installation ....................................................3
2.1 Introduction to Installation ......................................3
2.2 Unpacking ................................................................3
2.3 Mounting ..................................................................3
2.4 Connecting Power Source and Load Lines................3
2.4.1 2-Pole Mechanism ..........................................3
2.5 Connecting Start Circuit Wires ................................4
Section 3 — Operation ......................................................4
3.1 Functional Tests & Adjustments ..............................4
3.2 Manual Operation ....................................................4
3.2.1 Close to Normal Source Side ........................4
3.2.2 Close to Emergency Source Side....................5
3.2.3 Return to Normal Source Side ......................5
3.3 Voltage Checks..........................................................5
3.4 Generator Tests Under Load ....................................6
Section 4 – Notes................................................................7
Section 5 – Installation Diagram....................................8
Section 6 – Electrical Data ..............................................9
Section 7 – Exploded Views & Parts Lists..................12
Section 8 – Warranty ......................................Back Cover
• Never work on this equipment while physically or
mentally fatigued.
• Keep the transfer switch enclosure door closed and
bolted at all times. Only qualified personnel
should be permitted access to the switch interior.
• In case of an accident caused by electric shock,
immediately shut down the source of electrical
power. If this is not possible, attempt to free the
victim from the live conductor but AVOID DIRECT
CONTACT WITH THE VICTIM. Use a nonconduct-
ing implement, such as a dry rope or board, to free
the victim from the live conductor. If the victim is
unconscious, apply first aid and get immediate
medical help.
• When an automatic transfer switch is installed for
a standby generator set, the generator engine may
crank and start at any time without warning. To
avoid possible injury that might be caused by such
sudden start-ups, the system’s automatic start cir-
cuit must be disabled before working on or around
the generator or transfer switch. Then place a “DO
NOT OPERATE” tag on the transfer switch and on
the generator. Remove the Negative (Neg) or (–) bat-
tery cable.
®
Generac Power Systems, Inc.
1
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 1 — General Information
Generac GTS “HS” Type Transfer Switch
1.1 INTRODUCTION
1.3 TRANSFER SWITCH DATA DECAL
A DATA DECAL is permanently affixed to the transfer
switch enclosure. Use this transfer switch only with
the specific limits shown on the DATA DECAL and on
other decals and labels that may be affixed to the
switch. This will prevent damage to equipment and
property.
This manual has been prepared especially for the
purpose of familiarizing personnel with the design,
application, installation, operation and servicing of
the applicable equipment. Read the manual carefully
and comply with all instructions. This will help to
prevent accidents or damage to equipment that might
otherwise be caused by carelessness, incorrect appli-
cation, or improper procedures.
When requesting information or ordering parts for this
equipment, make sure to include all information from
the DATA DECAL.
Every effort has been expended to make sure that the
contents of this manual are both accurate and cur-
rent. Generac, however, reserves the right to change,
alter or otherwise improve the product at any time
without prior notice.
Record the Model and Serial numbers in the space pro-
vided below for future reference.
ASSEMBLY #
SERIAL #
1.2 EQUIPMENT DESCRIPTION
The automatic transfer switch is used for transfer-
ring electrical load from a UTILITY (NORMAL) power
source to a EMERGENCY ( STANDBY) power source.
Such a transfer of electrical loads occurs automati-
cally when the UTILITY power source has failed or is
substantially reduced and the EMERGENCY source
voltage and frequency have reached an acceptable
level. The transfer switch prevents electrical feedback
between two different power sources (such as the
UTILITY and EMERGENCY sources) and, for that
reason, codes require it in all standby electric system
installations.
1.4 TRANSFER SWITCH ENCLOSURE
The standard switch enclosure is a National
Electrical Manufacturer’s Association (NEMA) 3R
type. NEMA 3R type enclosures primarily provide a
degree of protection against falling rain and sleet and
is not damaged by the formation of ice on the
enclosure.
The transfer switch consists of a transfer mecha-
nism, a relay control, and a terminal strip for con-
nection of sensing wires.
1.5 SAFE USE OF TRANSFER SWITCH
Before installing, operating or servicing this equip-
ment, read the SAFETY RULES (inside front cover)
carefully. Comply strictly with all SAFETY RULES to
prevent accidents and/or damage to the equipment.
Generac recommends that a copy of the SAFETY
RULES are posted near the transfer switch. Also, be
sure to read all instructions and information found
on tags, labels and decals affixed to the equipment.
This switch is suitable for control of motors, electric
discharge lamps, tungsten filament and electric heat-
ing equipment where the sum of motor full load
ampere ratings and the ampere ratings of other loads
do not exceed the ampere rating of the switch and the
tungsten load does not exceed 30 percent of the
switch rating.
Two publications that outline the safe use of transfer
switches are the following:
The transfer switch is for use in optional standby sys-
tems only.
• NFPA 70; National Electrical Code
• UL 1008, STANDARD FOR SAFETY-AUTOMATIC
TRANSFER SWITCHES
The transfer switch is suitable for use on a circuit
capable of 10,000 rms symmetrical amperes, 240
VAC when protected by a circuit breaker without an
adjustable short time response or by fuses.
®
2
Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 2 — Installation
Generac GTS “HS” Type Transfer Switch
2.4.1 2-POLE MECHANISM
2.1 INTRODUCTION TO INSTALLATION
This equipment has been wired and tested at the fac-
tory. Installing the switch includes the following pro-
cedures:
These switches (Figure 2.1) are used with a single-
phase system, when the single-phase NEUTRAL line
is to be connected to a Neutral Lug and is not to be
switched.
• Mounting the enclosure.
• Connecting power source and load leads.
• Connecting the generator start circuit.
• Connecting any auxiliary contact (if needed)
• Testing functions.
Figure 2.1 — Typical 2-Pole Transfer Mechanism
(200 Amp Shown)
2.2 UNPACKING
Carefully unpack the transfer switch. Inspect closely
for any damage that might have occurred during ship-
ment. The purchaser must file with the carrier any
claims for loss or damage incurred while in transit.
Check that all packing material is completely
removed from the switch prior to installation.
2.3 MOUNTING
Mounting dimensions for the transfer switch enclo-
sure are in this manual. Enclosures are typically
wall-mounted. See “Installation Diagram”, Section 5.
Solderless, screw-type terminal lugs are standard.
Handle transfer switches carefully when
installing. Do not drop the switch. Protect the
switch against impact at all times, and against
construction grit and metal chips. Never
install a transfer switch that has been dam-
aged.
Switch
Rating
100A
Wire
Range
#14-1/0 AWG
#6-250 MCM
Conductor Tightening
Torque
!
50 in-lbs.
275 in-lbs.
200A
Conductor sizes must be adequate to handle the max-
imum current to which they will be subjected to,
based on the 75°C column of tables, charts, etc. used
to size conductors. The installation must comply fully
with all applicable codes, standards and regulations.
Install the transfer switch as close as possible to the
electrical loads that are to be connected to it. Mount
the switch vertically to a rigid supporting structure.
To prevent switch distortion, level all mounting
points. If necessary, use washers behind mounting
holes to level the unit.
Before connecting wiring cables to terminals, remove
any surface oxides from the cable ends with a wire
brush. All power cables should enter the switch next
to transfer mechanism terminals. If ALUMINUM con-
ductors are used, apply corrosion inhibitor to con-
ductors. Tighten terminal lugs to the torque values as
noted on the decal located on the inside of the door.
After tightening terminal lugs, carefully wipe away
any excess corrosion inhibitor.
2.4 CONNECTING POWER SOURCE
AND LOAD LINES
DANGER
Make sure to turn OFF both the UTILITY
(NORMAL) and EMERGENCY ( STANDBY)
power supplies before trying to connect
power source and load lines to the transfer
switch. Supply voltages are extremely high
and dangerous. Contact with such high volt-
age power supply lines causes extremely haz-
ardous, possibly lethal, electrical shock.
All power cables should enter the switch next to the
transfer mechanism terminals.
Use a torque wrench to tighten the conduc-
tors, being sure not to over tighten, or dam-
age to the switch base could occur. If not
Wiring diagrams and electrical schematics are pro-
vided in this manual. Power source and load connec-
tions are made at a transfer mechanism, inside the
switch enclosure.
!
tightened enough, a loose connection would
result, causing excess heat which could dam-
age the switch base.
®
Generac Power Systems, Inc.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 3 — Operation
Generac GTS “HS” Type Transfer Switch
Connect power source load conductors to clearly
marked transfer mechanism terminal lugs as follows
IMPORTANT: Before proceeding with functional
tests, read and make sure all instructions and infor-
mation in this section are understood. Also read the
information and instructions of labels and decals
affixed to the switch. Note any options or accessories
that might be installed and review their operation.
1. Connect UTILITY (NORMAL) power source cables
to switch terminals N1, N2.
2. Connect EMERGENCY (STANDBY) source power
cables to transfer switch terminals E1, E2.
3. Connect customer LOAD leads to switch termi-
nals T1, T2.
Conductors must be properly supported, of approved
insulative qualities, protected by approved conduit,
and of the correct wire gauge size in accordance with
applicable codes.
3.2 MANUAL OPERATION
DANGER
Do NOT manually transfer under load.
Disconnect transfer switch from all power
sources by approved means, such as a main
!
Be sure to maintain proper electrical clearance
between live metal parts and grounded metal. Allow
at least 1/2 inch for 100-400 amp circuits.
circuit breaker(s).
A manual HANDLE is shipped with the transfer
switch. Manual operation must be checked BEFORE
the transfer switch is operated electrically. To check
manual operation, proceed as follows:
2.5 CONNECTING START CIRCUIT
WIRES
1. Turn the generator’s AUTO-OFF-MANUAL switch
to OFF.
2. Turn OFF both UTILITY and EMERGENCY
power supplies to the transfer switch, with what-
ever means provided (such as the main line cir-
cuit breakers).
3. Note position of transfer mechanism main con-
tacts by observing the moveable contact carrier
arm.
Control system interconnections (Section 6) consist
of UTILITY 1 and 2, LOAD 1 and 2, and leads 23 and
194. Control system interconnection leads must be
run in a conduit that is separate from the AC power
lead. Recommended wire gauge sizes for this wiring
depends on the length of the wire, as recommended
below:
MAXIMUM WIRE LENGTH
RECOMMENDED WIRE
SIZE
• Manual operation handle towards the top of
switch mechanism - LOAD terminals (T1, T2) are
connected to UTILITY terminals (N1, N2).
• Manual operation handle towards the bottom of
switch mechanism - LOAD terminals (T1, T2) are
connected to EMERGENCY terminals (E1, E2).
460 feet (140m)
No. 18 AWG.
No. 16 AWG.
No. 14 AWG.
No. 12 AWG.
461 to 730 feet (223m)
731 to 1,160 feet (354m)
1,161 to 1,850 feet (565m)
NOTE:
When this ATS is used with an air-cooled genera-
tor, the LOAD 1 and LOAD 2 wires are not used.
Do not use excessive force when operating
the transfer switch manually or damage could
be done to the manual handle.
3.1 FUNCTIONAL TESTS AND
!
ADJUSTMENTS
Following transfer switch installation and inter-
connection, inspect the entire installation careful-
ly. A competent, qualified electrician should
inspect it. The installation should comply strictly
with all applicable codes, standards, and regula-
tions. When absolutely certain the installation is
proper and correct, complete a functional test of
the system.
3.2.1 CLOSE TO NORMAL SOURCE SIDE
◆
Before proceeding, verify the position of the switch by
observing the position of manual operation handle in
Figure 3.1. If the handle is UP, the contacts are closed
in the NORMAL position, no further action is
required. If the handle is DOWN, proceed with Step
1.
Step 1: With the handle inserted into the actuating
shaft, move handle UP. Be sure to hold on to
the handle as it will move quickly after the
center of travel.
Perform functional tests in the exact order
presented in this manual, or damage could be
!
done to the switch.
®
4
Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 3 — Operation
Generac GTS “HS” Type Transfer Switch
Figure 3.1 — Actuating Transfer Switch
Attach handle to actuating shaft.
NOTE: Return handle to
storage position in enclosure
when finished with manual transfer.
Move handle
Move handle
DOWN for the
EMERGENCY
(standby)
UP for the
NORMAL
position.
position.
3.2.2 CLOSE TO EMERGENCY SOURCE SIDE
◆
DANGER
Before proceeding, verify the position of the switch by
observing the position of the manual operation han-
dle in Figure 3.1. If the handle is DOWN, the contacts
are closed in the EMERGENCY (STANDBY) position.
No further action is required. If the handle is UP, pro-
ceed with Step 1.
PROCEED WITH CAUTION. THE TRANSFER
SWITCH IS NOW ELECTRICALLY HOT. CONTACT
WITH LIVE TERMINALS RESULTS IN EXTREMELY
HAZARDOUS AND POSSIBLY FATAL ELECTRI-
CAL SHOCK.
2. With an accurate AC voltmeter, check for correct
voltage.
Step 1: With the handle inserted into the actuating
shaft, move the handle DOWN. Be sure to
hold on to the handle as it will move quickly
after the center of travel.
Single-phase utility supply:
Measure across ATS terminal lugs N1 and N2.
Also check N1 to NEUTRAL and N2 to NEUTRAL.
3. When certain that UTILITY supply voltage is cor-
rect and compatible with transfer switch ratings,
turn OFF the UTILITY supply to the transfer
switch.
3.2.3 RETURN TO NORMAL SOURCE SIDE
◆
Manually actuate switch to return manual operating
handle to the UP position.
4. On the generator panel, set the AUTO-OFF-
MANUAL switch to MANUAL position. The gener-
ator should crank and start.
3.3 VOLTAGE CHECKS
1. Turn ON the UTILITY power supply to the trans-
fer switch with whatever means provided (such as
the UTILITY main line circuit breaker).
5. Let the generator stabilize and warm up at no-
load for at least five minutes.
6. Set the generator's main circuit breaker (CB1) to
its ON or CLOSED position.
®
Generac Power Systems, Inc.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 3 — Operation
Generac GTS “HS” Type Transfer Switch
3.4 GENERATOR TESTS UNDER LOAD
1. Set the generator's main circuit breaker to its
OFF or OPEN position.
2. Manually actuate the transfer switch main con-
tacts to their EMERGENCY (STANDBY) position.
Refer to Manual Operation (Section 3.2).
3. To start the generator, set the AUTO-OFF-
MANUAL switch to MANUAL. When engine starts,
let it stabilize for a few minutes.
4. Turn the generator's main circuit breaker to its
ON or CLOSED position. The generator now pow-
ers all LOAD circuits. Check generator operation
under load as follows:
DANGER
PROCEED WITH CAUTION. GENERATOR OUT-
PUT VOLTAGE IS NOW BEING DELIVERED TO
TRANSFER SWITCH TERMINALS. CONTACT
WITH LIVE TERMINALS RESULTS IN EXTREMELY
DANGEROUS AND POSSIBLY FATAL ELECTRI-
CAL SHOCK.
7. With an accurate AC voltmeter and frequency
meter, check the no-load, voltage and frequency.
Single-phase generator supply:
Measure across ATS terminal lugs E1 to E2. Also
check E1 to NEUTRAL and E2 to NEUTRAL.
a. Frequency ......................................60-62 Hertz
b. Terminals E1 to E2 ........................240-246 VAC
c. Terminals E1 to NEUTRAL ............120-123 VAC
d. Terminals E2 to NEUTRAL ............120-123 VAC
8. Set the generator’s main circuit breaker (CB1) to
its OFF or OPEN position.
•
Turn ON electrical loads to the full rated
wattage/amperage capacity of the generator.
DO NOT OVERLOAD.
•
With maximum rated load applied, check
voltage and frequency across transfer switch
terminals E1 and E2. Voltage should be
greater than 230 volts and frequency should
be greater than 59 Hertz.
9. Set the AUTO/OFF/MANUAL switch to the OFF
position to shut down the generator.
•
Let the generator run under rated load for at
least 30 minutes. With unit running, listen for
unusual noises, vibration, overheating, etc.,
that might indicate a problem.
NOTE:
Do NOT proceed until generator AC output voltage
and frequency are correct and within stated limits.
If the no-load voltage is correct but no-load fre-
quency is incorrect, the engine governed speed
probably requires adjustment. If no-load frequen-
cy is correct but voltage is not, the voltage regula-
tor may require adjustment.
5. When checkout under load is complete, set main
circuit breaker of the generator to its OFF or
OPEN position.
6. Let the generator run at no-load for several
minutes. Then, shut down by setting the AUTO-
OFF-MANUAL switch to its OFF position.
7. Move the switch's main contacts back to their
UTILITY position. For example, load connected to
UTILITY power supply. Refer to Manual
Operation (Section 3.2). Handle and operating
lever of transfer switch should be in UP position.
8. Turn on the utility power supply to transfer
switch, using whatever means provided (such as
a utility main line circuit breaker). The utility
power source now powers the loads.
9. Set the generator's AUTO-OFF-MANUAL switch to
its AUTO position. The system is now set for fully
automatic operation.
®
6
Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 4 — Notes
Generac GTS “HS” Type Transfer Switch
®
Generac Power Systems, Inc.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 4 — Notes
Generac GTS “HS” Type Transfer Switch
®
8
Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 4 — Notes
Generac GTS “HS” Type Transfer Switch
®
Generac Power Systems, Inc.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 5 — Installation Diagram
Generac GTS “HS” Type Transfer Switch
Drawing No. 0E7081
®
10 Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 6 — Electrical Data
Generac GTS “HS” Type Transfer Switch
Transfer Switch Interconnections
4
A D 1
T I L I T Y 2
T I L I T Y 1
®
Generac Power Systems, Inc. 11
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 6 — Electrical Data
Generac GTS “HS” Type Transfer Switch
Electrical Schematic - Drawing No. 0E6093-A
TR
F1
1
UTILITY 1
126
E1
N1A
N1
7
TB1
E1
B
A
N1A
N2A
NO
NC
NC
NO
XB1
COM
XA1
COM
E2
VR1
VR2
N2A
C1
C2
F3
F4
LOAD 1
LOAD 2
A
T1A
T1
T2
TB3
TB4
B
TR
T2A
6
9
205
E2
UTILITY 2
N2A
N2
TB2
TB5
NEUTRAL *
(OPTIONAL)
NB
00
23
23
B
A
TB6
* - NOT USED WITH PREPACKAGED STANDBY GENERATORS
194
194
TB7
ATS
TRANSFER SWITCH CONTACTOR
SOLENOID COIL (UTILITY CLOSING)
SOLENOID COIL (STANDBY CLOSING)
RELAY, TRANSFER
C1
C2
NOTE:
TR
ALL CONTACTS SHOWN WITH
TRANSFER SWITCH IN UTILITY
POSITION.
TB
TERMINAL STRIP (CUSTOMER CONNECTION)
LIMIT SWITCHES, ACTUATOR
FUSE, 5A
XA1,XB1
F1,2,3 & 4
VR1,VR2
NB
VARISTOR
NB - NEUTRAL BLOCK
®
12 Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 6 — Electrical Data
Generac GTS “HS” Type Transfer Switch
Electrical Schematic - Drawing No. 0E6093-A
N2A
N1A
N2A
126
N1A
N2A
(C1)
N2A
A
XA1
ATS
XB1
E1
B
(C2)
E2
205
N1A
T1A
126
T2A
TR
E2
1
3
B
9
6
N1A
194
E2
23
205
N2A
N1A
E2
23
N2A
N2A
194
N2A
N1A
T2A
F4
N1A
T1A
23
F2
F3
00
194
* - NOT USED WITH PREPACKAGED
STANDBY GENERATORS
N1
T1
N2
T2
00
Y
Z
47822-T
3
4
5
6
7
CUSTOMER CONTROL
CONNECTIONS
®
Generac Power Systems, Inc. 13
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 7 — Exploded Views and Parts List
Generac GTS “HS” Type Transfer Switch
100A Transfer Switch Assembly – Drawing No. 0E8403$-B
-
®
14 Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 7 — Exploded Views and Parts List
Generac GTS “HS” Type Transfer Switch
100A Transfer Switch Assembly – Drawing No. 0E8403$-B
ITEM
PART NO.
QTY.
DESCRIPTION
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20****
21
22
23***
24
25
26
27*
28
0C2237
077033
036932
022152
066849
045771
062684
0C3168
022129
073590A
073591
090388
0A1495
063617
0C2454
0A1661
0C4449
0E6057
0E6056
0E5567
0A2595
0E8443
095282
067210A
0A9457
0A9517
077036D
081221
064101
0E6055
063378
028739
064113
077441
0E6303
0E6303A
0E6303C
0E6094
1
6
6
6
4
1
1
1
1
4
4
2
6
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
4
1
4
4
1
0
1
1
1
1
TR SW-HSB 100A 2P 250V
LUG SLDLSS 1/0-#14X9/16 AL/CU
SCREW PPHM #10-32 X 1/4
WASHER LOCK #10
SCREW HHTT M5-0.8 X 16 BP
NUT HEX M8-1.25 G8 YEL CHR
LUG SLDLSS 2/0-#12 X 11/32 CU
WASHER LOCK SPECIAL 5/16
WASHER LOCK M8-5/16
FUSE 5A X BUSS
FUSE HOLDER
SCREW HHTT M6-1.0 X 12 ZINC
SCREW HHTT M4-0.7 X 10 BP
RELAY PNL 12VDC DPDT 10A@240VA
SCREW TH-FRM M6-1 X 16 N WA Z/JS
RIVET POP .156 X .675 AL
ASSY NEUTRAL BLOCK 100A
WELDMENT XFER SW BOX HSB
COVER TRANSFER SWITCH BOX HSB
DECAL TRANSFER SWITCH
DECAL TERMINAL STRIP
DECAL SWITCH RATING
DECAL-LIVE CIRCUIT
DECAL GROUND LUG
DECAL NEUTRAL
DECAL MANUAL 5A FUSE
DECAL TEST SEQUENCE 3R
DECAL-UL LIST HSB
NUT HEX FL WHIZ 3/8-16
SUBPLT TRANSFER SWITCH HSB
HOLDER CABLE TIE
TIE WRAP UL 3.9" X .10" NATL
STUD WINGNUT M6-1.0 X 20MM NY
HANDLE TRANSFER SW H.S.
WIRE A
29
30
31*****
32*****
33
34**
35
36
37
38
WIRE B
WIRE E1
WIRE HARNESS 100/200A 2P HS (NOT SHOWN)
*
CENTER DECAL ON INSIDE OF THE COVER (ITEM #19)
** SUPPLIED WITH TRANSFER SWITCH ITEM #1.
*** PLACE DECAL ON OUTSIDE OF COVER, LOWER RIGHT CORNER.
**** NOT SHOWN ON THIS ASSEMBLY, CENTER DECAL ON FRONT OF COVER, 7" FROM TOP OF ENCLOSURE.
***** SUPPLIED WITH HARNESS (P/N 0E6094).
®
Generac Power Systems, Inc. 15
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 7 — Exploded Views and Parts List
Generac GTS “HS” Type Transfer Switch
200A Transfer Switch Assembly – Drawing No. 0E5782$-E
A D
A D
2
1
2
1
®
16 Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 7 — Exploded Views and Parts List
Generac GTS “HS” Type Transfer Switch
200A Transfer Switch Assembly – Drawing No. 0E5782$-E
ITEM
PART NO.
QTY.
DESCRIPTION
1
2
3
4
5
6
7
8
9
0D9618
0E3375
0E6058
022097
066849
045771
057329
027482
022129
073590A
073591
090388
0A1495
063617
0C2454
0A1661
0C4449A
0E6057
0E6056
0E5567
0A2595
095282
0E8443
064101
0E6055
063378
028739
067210A
0A9457
0A9517
0E6190
081221
0E6193
0C4739
0E6155
0E6094
0E6033
0E6303
0E6303A
0E6303B
1
6
6
6
5
1
1
1
1
4
4
2
6
1
2
2
1
1
1
1
1
1
1
4
1
5
5
1
1
1
1
1
1
2
1
1
2
1
1
1
TR SW-HSB 200A 2P 250V
LUG SLDLSS 250-#6 AL/CU
SCREW SHC 1/4-20X3/8
WASHER LOCK M6-1/4
SCREW HHTT M5-0.8 X 16 BP
NUT HEX M8-1.25 G8 YEL CHR
LUG SLDLSS 350-#6 X 13/32 AL/CU
WASHER SHAKEPROOF EXT 5/16 STL
WASHER LOCK M8-5/16
FUSE 5A X BUSS
10
11*****
12
13
14*****
15
16
17
18
19
20****
21
22***
23
24
25
26*****
27*****
29
30
31
32 *
33
34
35
36 **
37
38 **
40
41
FUSE HOLDER
SCREW HHTT M6-1.0 X 12 ZINC
SCREW HHTT M4-0.7 X 10 BP
RELAY PNL 12VDC DPDT 10A@240VA
SCREW TH-FRM M6-1 X 16 N WA Z/JS
RIVET POP .156 X .675 AL
ASS'Y-NTRL BL150-200A
WELDMENT XFER SW BOX HSB
COVER TRANSFER SWITCH BOX HSB
DECAL TRANSFER SWITCH
DECAL TERMINAL STRIP
DECAL-LIVE CIRCUIT
DECAL SWITCH RATING
NUT LOCK FL 3/8-16
SUBPLT TRANSFER SWITCH HSB
HOLDER CABLE TIE
TIE WRAP UL 3.9" X .10" NATL
DECAl GROUND LUG
DECAL NEUTRAL
DECAL MANUAL 5A FUSE
DECAL TEST SEQUENCE 2P TS 3R
DECAL-UL LIST HSB
BRACKET ARM EXTENDER
SCREW PPHM M3-0.5 X 6
ARM EXTENDER PIN
HARN 100/200A 2P HS
90 DEGREE DN SPADE CONNECTOR
WIRE A
WIRE B
WIRE-E1
42
* CENTER DECAL ON INSIDE OF THE COVER (ITEM #19)
** SUPPLIED WITH TRANSFER SWITCH ITEM #1.
*** PLACE DECAL ON OUTSIDE OF COVER, LOWER RIGHT CORNER.
**** NOT SHOWN ON THIS ASSEMBLY, CENTER DECAL ON FRONT OF COVER, 7" FROM TOP OF ENCLOSURE.
***** SUPPLIED WITH HARNESS (P/N 0E6094)
®
Generac Power Systems, Inc. 17
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 8 — Warranty
Generac GTS “HS” Type Transfer Switch
GENERAC POWER SYSTEMS STANDARD TWO-YEAR LIMITED WARRANTY
FOR GENERAC TRANSFER SWITCH SYSTEMS
NOTE: ALL UNITS MUST HAVE A START-UP INSPECTION PERFORMED BY AN AUTHORIZED GENERAC DEALER.
For a period of 2 (two) years from the date of sale/start date, Generac Power Systems, Inc. will, at its option, repair or
replace any part(s) which, upon examination, inspection, and testing by Generac Power Systems or a Generac Power
Systems Authorized Warranty Service Facility, is found to be defective under normal use and service, in accordance with
the warranty schedule set forth below. Any equipment that the purchaser/owner claims to be defective must be returned
to, and examined by the nearest Generac Power Systems Authorized Warranty Service Facility. All transportation costs
under the warranty, including return to the factory, are to be borne and prepaid by the purchaser/owner. This warranty
applies only to Generac Power Systems Transfer Switch applications, as Generac Power Systems, Inc. have defined
Transfer Switch application, provided said Transfer Switch has been initially installed and inspected on-site by a Generac
Power Systems Authorized Service Dealer or branch thereof. A scheduled maintenance agreement with a local Authorized
Generac Power Systems Dealer is highly recommended to verify adequate service has been performed on the unit
throughout the warranty period.
WARRANTY SCHEDULE
• YEAR ONE — 100% (one hundred percent) coverage on mileage*, labor, and parts listed.
• ALL COMPONENTS
• YEAR TWO — 100% (one hundred percent) coverage on parts listed.
• ALL COMPONENTS — *PARTS ONLY
• *Travel allowance is limited to 300 miles maximum, or 7.5 hours maximum (per occurrence), round trip, to the nearest
authorized Generac Service Facility.
• A Generac Power Systems, Inc. Transfer Switch is highly recommended to be used in conjunction with the genset. If a
non Generac genset is substituted for use and directly causes damage to the Generac Transfer Switch, no warranty
coverage shall apply.
• All warranty expense allowances are subject to the conditions defined in Generac Power Systems Warranty, Policies, and
Procedures Flat Rate Manual.
• Units that have been resold are not covered under the Generac Power Systems Warranty, as this Warranty is not transferable.
THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING:
1. Any unit built/manufactured prior to January 1, 2002.
2. Unit enclosure is only covered against rust or corrosion the first year of the warranty provision.
3. Costs of normal maintenance i.e. tune-ups, associated part(s), adjustments, loose/leaking clamps, installation and start-up.
4. Use of Non-Generac replacement part(s) will void the warranty in its entirety.
5. Any failure caused by contaminated fuels, oils, coolants/antifreeze or lack of proper fuels, oils or coolants/antifreeze.
6. Failures due, but not limited to, normal wear and tear, accident, misuse, abuse, negligence, or improper installation or
sizing.
7. Failures caused by any external cause or act of God such as collision, fire, theft, freezing, vandalism, riot or wars, lightning,
earthquake, windstorm, hail, volcanic eruption, water or flood, tornado, hurricane, terrorist acts or nuclear holocaust.
8. Products that are modified or altered in a manner not authorized by Generac Power Systems in writing.
9. Any incidental, consequential or indirect damages caused by defects in materials or workmanship, or any delay in
repair or replacement of the defective part(s).
10. Failure due to misapplication, misrepresentation, or bi-fuel conversion.
11. Telephone, telegraph, teletype or other communication expenses.
12. Living or travel expenses of person(s) performing service, except as specifically included within the terms of a specific
unit warranty period.
13. Rental equipment used while warranty repairs are being performed i.e. rental generators, cranes, etc..
14. Overtime labor or more than one person performing repairs.
15. Any and all expenses incurred investigating performance complaints unless defective Generac materials and or work-
manship were the direct cause of the problem.
16. *Engine coolant heaters (block-heaters), heater controls and circulating pumps after the first year.
17. *Starting batteries, fuses, light bulbs, engine fluids, tires, brakes, and overnight freight cost for replacement part(s).
THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, SPECIFICALLY, GENERAC
POWER SYSTEMS MAKES NO OTHER WARRANTIES AS TO THE MERCHANTABILITY OR FITNESS FOR A PARTICU-
LAR PURPOSE. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may
not apply to you.
GENERAC POWER SYSTEMS ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED
ABOVE. IN NO EVENT SHALL GENERAC POWER SYSTEMS BE LIABLE FOR ANY INCIDENTAL, OR CONSEQUENTIAL
DAMAGES, EVEN IF SUCH DAMAGES ARE A DIRECT RESULT OF GENERAC POWER SYSTEMS, INC. NEGLIGENCE.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations may
not apply to you. Purchaser/owner agrees to make no claims against Generac Power Systems, Inc. based on negligence.
This warranty gives you specific legal rights. You also may have other rights that vary from state to state.
GENERAC® POWER SYSTEMS, INC. • P.O. BOX 8 • WAUKESHA, WI 53187
PH: (262) 544-4811 • FAX: (262) 544-4851
Bulletin 0166260SBY / Printed in USA 5.02
Part No. 0E6347
Revision D (02/05/04)
Printed in U.S.A.
Download from Www.Somanuals.com. All Manuals Search And Download.
|