Generac Power Systems Portable Generator 05176 0 User Manual

®
POWER SYSTEMS, INC.  
Installation and  
Owner’s Manual  
Air-cooled Automatic  
Standby Generators  
Model:  
05176-0 (13 kW NG, 15 kW LP)  
*This manual should remain with the unit.*  
Not intended for use as Primary Power in place of utility   
or in life-support applications.  
DANGER  
DEADLY EXHAUST FUMES. OUTDOOR INSTALLATION ONLY!!  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
Air-cooled 15 kW Generators  
4.2 Automatic Transfer Operation.....................14  
4.3 Sequence of Automatic Operation ...............14  
4.4 Manual Operation .......................................15  
4.4.1 Close to Normal Source Side.............15  
4.4.2 Close to Emergency Source Side .......16  
4.4.3 Return to Normal Source Side...........16  
4.5 Voltage Checks ............................................16  
4.6 Generator Tests Under Load.......................16  
4.7 Setting the Exercise Timer ..........................17  
4.8 Protection Systems......................................17  
4.8.1 Low Oil Pressure Switch ..................17  
4.8.2 High Temperature Switch.................17  
4.8.3 Overcrank ........................................17  
4.8.4 Overspeed ........................................18  
Introduction ........................Inside Front Cover  
Read This Manual Thoroughly........................ IFC  
Contents.......................................................... IFC  
Operation and Maintenance ............................ IFC  
How to Obtain Service..................................... IFC  
Authorized Dealer Locator Number................... IFC  
Safety Rules ........................................................2  
Standards Index..................................................3  
Section 1 – General Information...................4  
1.1 Unpacking/Inspection....................................4  
1.2 Protection Systems........................................4  
1.3 System Set LED ............................................4  
1.4 The Generator...............................................5  
1.5 Specifications................................................6  
1.5.1 Generator...........................................6  
1.5.2 Engine................................................6  
1.6 Fuel Requirements and Recommendations ...6  
1.7 Fuel Consumption.........................................6  
1.8 Reconfiguring the Fuel System ......................6  
Section 2 – Installation....................................7  
2.1 Installation....................................................7  
2.1.1 Remote Monitoring Connections ........7  
2.1.2 Roof Open Alarm ...............................8  
2.1.3 Transfer Switch Connection...............8  
2.2 Battery Installation........................................9  
2.3 The Battery .................................................10  
Section 5 – Maintenance...............................18  
5.1 Fuse.............................................................18  
5.2 Checking the Engine Oil Level.....................18  
5.3 Changing the Engine Oil..............................18  
5.3.1 Engine Oil Recommendations ..........18  
5.3.2 Oil Change Procedure.......................18  
5.4 Changing the Oil Filter ................................19  
5.5 Changing the Engine Air Cleaner.................19  
5.6 Spark Plug(s) ..............................................19  
5.7 Battery Maintenance....................................20  
5.8 Adjusting Valve Clearance ...........................20  
5.9 Cooling System ...........................................21  
5.10 Attention After Submersion.........................21  
5.11 Corrosion Protection...................................21  
5.12 Out of Service Procedure.............................21  
5.12.1 Removal From Service......................21  
5.12.2 Return to Service .............................22  
Section 3 – Post Installation Start-up  
and Adjustments .......................10  
3.1 Before Initial Start-up..................................10  
3.2 Check Transfer Switch Operation ...............10  
3.3 Electrical Checks ........................................10  
3.4 Generator Tests Under Load.......................11  
3.5 Checking Automatic Operation....................12  
3.6 Adjusting the Regulator (Natural Gas Only)..12  
3.7 Engine Governor Adjustment......................13  
3.7.1 Additional Corrosion Protection.......13  
3.8 Voltage Regulator Adjustment......................13  
Section 4 – Operation ....................................14  
4.1 Using the Auto/Off/Manual Switch...............14  
4.1.1 Auto” Position..................................14  
4.1.2 “Off Position....................................14  
4.1.3 “Manual” Position.............................14  
Section 6 – Troubleshooting.........................27  
6.1 Troubleshooting Guide................................27  
Section 7 – Mounting Dimensions............. 28  
Section 8 – Electrical Data........................... 29  
Section 9 – Exploded Views and  
Parts Lists................................... 34  
Section 10 – Warranty................................... 48  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
IMPORTANT SAFETY INSTRUCTIONS  
Air-cooled 15 kW Generators  
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe  
operation be copied and posted near the unit’s installation site. Safety should be stressed to  
all operators and potential operators of this equipment.  
WARNING:  
contains chemicals known to the state  
of California to cause cancer, birth  
defects or other reproductive harm.  
The engine exhaust from this product  
Please read all hazards carefully!  
GENERAL HAZARDS  
WARNING:  
For safety reasons, the manufacturer recommends  
that the installation, initial start-up and main-  
tenance of this equipment is carried out by an  
Authorized Dealer.  
This product contains or emits chemicals  
known to the state of California to cause  
cancer, birth defects or other reproductive harm.  
• The engine exhaust fumes contain carbon monox-  
ide, which can be DEADLY. This dangerous gas, if  
breathed in sufficient concentrations, can cause  
unconsciousness or even death. This exhaust  
system must be installed properly, in strict com-  
pliance with applicable codes and standards.  
Following installation, do nothing that might ren-  
der the system unsafe or in noncompliance with  
such codes and standards.  
• Keep hands, feet, clothing, etc., away from drive  
belts, fans, and other moving or hot parts. Never  
remove any drive belt or fan guard while the unit  
is operating.  
• Adequate, unobstructed flow of cooling and venti-  
lating air is critical to correct generator operation.  
Do not alter the installation or permit even partial  
blockage of ventilation provisions, as this can seri-  
ously affect safe operation of the generator. The  
generator MUST be installed outdoors.  
• When working on this equipment, remain alert  
at all times. Never work on the equipment when  
physically or mentally fatigued.  
Study these SAFETY RULES carefully before install-  
ing, operating or servicing this equipment. Become  
familiar with this Owner’s Manual and with the  
unit. The generator can operate safely, efficiently and  
reliably only if it is properly installed, operated and  
maintained. Many accidents are caused by failing to  
follow simple and fundamental rules or precautions.  
The manufacturer cannot anticipate every possible  
circumstance that might involve a hazard. The warn-  
ings in this manual, and on tags and decals affixed  
to the unit are, therefore, not all-inclusive. If using  
a procedure, work method or operating technique  
the manufacturer does not specifically recommend,  
ensure that it is safe for others. Also make sure the  
procedure, work method or operating technique uti-  
lized does not render the generator unsafe.  
DANGER  
Despite the safe design of this generator, operat-  
ing this equipment imprudently, neglecting its  
maintenance or being careless can cause possible  
injury or death. Permit only responsible and capa-  
ble persons to operate or maintain this equip-  
ment.  
• Inspect the generator regularly, and contact the  
nearest Authorized Dealer for parts needing repair  
or replacement.  
• Before performing any maintenance on the gen-  
erator, disconnect its battery cables to prevent  
accidental start up. Disconnect the cable from the  
battery post indicated by a NEGATIVE, NEG or (–)  
first. Reconnect that cable last.  
Potentially lethal voltages are generated by  
these machines. Ensure all steps are taken to  
render the machine safe before attempting to  
work on the generator.  
• Never use the generator or any of its parts as a  
step. Stepping on the unit can stress and break  
parts, and may result in dangerous operating con-  
ditions from leaking exhaust gases, fuel leakage,  
oil leakage, etc.  
Parts of the generator are rotating and/or hot  
during operation. Exercise care near running  
generators.  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
IMPORTANT SAFETY INSTRUCTIONS  
Air-cooled 15 kW Generators  
• Keep a fire extinguisher near the generator at all  
times. Extinguishers rated ABC” by the National  
Fire Protection Association are appropriate for  
use on the standby electric system. Keep the extin-  
guisher properly charged and be familiar with its  
use. If there are any questions pertaining to fire  
extinguishers, consult the local fire department.  
ELECTRICAL HAZARDS  
• All generators covered by this manual produce  
dangerous electrical voltages and can cause fatal  
electrical shock. Utility power delivers extremely  
high and dangerous voltages to the transfer switch  
as does the standby generator when it is in opera-  
tion. Avoid contact with bare wires, terminals,  
connections, etc., while the unit is running. Ensure  
all appropriate covers, guards and barriers are in  
place before operating the generator. If work must  
be done around an operating unit, stand on an  
insulated, dry surface to reduce shock hazard.  
• Do not handle any kind of electrical device while  
standing in water, while barefoot, or while hands or  
feet are wet. DANGEROUS ELECTRICAL SHOCK  
MAY RESULT.  
EXPLOSION HAZARDS  
• Do not smoke around the generator. Wipe up any  
fuel or oil spills immediately. Ensure that no com-  
bustible materials are left in the generator com-  
partment, or on or near the generator, as FIRE or  
EXPLOSION may result. Keep the area surround-  
ing the generator clean and free from debris.  
• Gaseous fluids such as natural gas and liquid pro-  
pane (LP) gas are extremely EXPLOSIVE. Install  
the fuel supply system according to applicable  
fuel-gas codes. Before placing the home standby  
electric system into service, fuel system lines must  
be properly purged and leak tested according to  
applicable code. After installation, inspect the fuel  
system periodically for leaks. No leakage is permit-  
ted.  
• The National Electrical Code (NEC) requires the  
frame and external electrically conductive parts of  
the generator to be connected to an approved earth  
ground. Local electrical codes also may require  
proper grounding of the generator electrical sys-  
tem.  
• After installing this home standby electrical sys-  
tem, the generator may crank and start at any  
time without warning. When this occurs, load cir-  
cuits are transferred to the STANDBY (generator)  
power source. To prevent possible injury if such a  
start and transfer occur, always set the generator’s  
AUTO/OFF/MANUAL switch to its OFF position  
before working on equipment and remove the 5A  
and 15A fuses from the generator control panel.  
• In case of accident caused by electric shock, imme-  
diately shut down the source of electrical power. If  
this is not possible, attempt to free the victim from  
the live conductor. AVOID DIRECT CONTACT WITH  
THE VICTIM. Use a nonconducting implement,  
such as a rope or board, to free the victim from the  
live conductor. If the victim is unconscious, apply  
first aid and get immediate medical help.  
STANDARDS INDEX  
In the absence of pertinent standards, codes, regu-  
lations and laws, the published information listed  
below may be used as installation guide for this  
equipment.  
1. NFPA No. 37, STATIONARY COMBUSTION  
ENGINES AND GAS TURBINES, available from  
the National Fire Protection Association, 470  
Atlantic Avenue, Boston, MA 02210.  
2. NFPA No. 76A, ESSENTIAL ELECTRICAL  
SYSTEMS FOR HEALTH CARE FACILITIES,  
available same as Item 1.  
3. NFPA No. 54, NATIONAL FUEL GAS CODE,  
• Never wear jewelry when working on this equip-  
ment. Jewelry can conduct electricity resulting in  
electric shock, or may get caught in moving com-  
ponents causing injury.  
available same as Item 1.  
4. NFPA No. 58, AMERICAN NATIONAL STANDARD  
FOR STORAGE AND HANDLING OF LIQUEFIED  
PETROLEUM GAS, available same as Item 1.  
5. NFPA No. 70, NFPA HANDBOOK OF NATIONAL  
ELECTRIC CODE, available same as Item 1.  
6. Article X, NATIONAL BUILDING CODE, available  
from the American Insurance Association, 85  
John Street, New York, N.Y. 10038.  
FIRE HAZARDS  
For fire safety, the generator must be installed  
and maintained properly. Installation always must  
comply with applicable codes, standards, laws  
and regulations. Adhere strictly to local, state and  
national electrical and building codes. Comply  
with regulations the Occupational Safety and  
Health Administration (OSHA) has established.  
Also, ensure that the generator is installed in  
accordance with the manufacturer’s instructions  
and recommendations. Following proper installa-  
tion, do nothing that might alter a safe installation  
and render the unit in noncompliance with the  
aforementioned codes, standards, laws and regula-  
tions.  
7. AGRICULTURAL WIRING HANDBOOK, avail-  
able from the Food and Energy Council, 909  
University Avenue, Columbia, MO 65201.  
8. ASAE  
EP-3634,  
INSTALLATION  
AND  
MAINTENANCEOFFARMSTANDBYELECTRICAL  
SYSTEMS, available from the American Society  
of Agricultural Engineers, 2950 Niles Road, St.  
Joseph, MI 49085.  
9. NFPA No. 30, FLAMMABLE AND COMBUSTIBLE  
LIQUIDS CODE, available same as Item 1.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1 — General Information  
Air-cooled 15 kW Generators  
1.2 PROTECTION SYSTEMS  
DANGER  
Unlike an automobile engine, the generator may have  
to run for long periods of time with no operator pres-  
ent to monitor engine conditions. For that reason, the  
engine is equipped with the following systems that  
protect it against potentially damaging conditions:  
Only qualified electricians or contractors should  
attempt such installations, which must comply  
strictly with applicable codes, standards and  
regulations.  
1. Low Oil Pressure Sensor  
2. High Temperature Sensor  
There are LED readouts on the control panel to notify  
personnel that one of these faults has occurred. There  
is also a “System Set” LED that is described below.  
3. Overcrank  
4. Overspeed  
1.1 UNPACKING/INSPECTION  
After unpacking, carefully inspect the contents for  
damage.  
• This standby generator set has been factory sup-  
plied with a weather protective enclosure that is  
intended for outdoor installation only.  
1.3 SYSTEM SET LED  
The “System Set” LED is lit when all of the following  
conditions are true:  
If this generator is used to power electrical load  
1. The AUTO/OFF/MANUAL switch is set to the  
AUTO position.  
circuits normally powered by a utility power  
source, it is required by code to install a trans-  
fer switch. The transfer switch must effectively  
isolate the electrical system from the utility  
distribution system when the generator is oper-  
ating (NEC 700, 701 and 702). Failure to isolate  
an electrical system by such means will result in  
damage to the generator and also may result in  
injury or death to utility power workers due to  
backfeed of electrical energy.  
2. The utility voltage being supplied to the unit is  
being sensed by the Control PCB. If the utility  
sense voltage is not connected to the unit or if it  
is below 168 volts AC, then the system set light  
will flash rapidly. This indicates that if the AUTO/  
OFF/MANUAL switch is placed in the Auto posi-  
tion , the generator will start.  
3. The “Not In Auto” dip switch is set to the OFF  
position on the control board.  
If any loss or damage is noted at time of delivery, have  
the person(s) making the delivery note all damage on  
the freight bill or affix his or her signature under the  
consignor's memo of loss or damage.  
4. No alarms are present, for example, low oil pres-  
sure, high temperature, etc.  
If there is loss or damage after delivery, separate the  
damaged materials and contact the carrier for claim  
procedures.  
“Concealed damage” is understood to mean damage  
to the contents of a package that is not in evidence at  
the time of delivery, but is discovered later.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1 — General Information  
Air-cooled 15 kW Generators  
1.4 THE GENERATOR  
Figure 1.1 – 15 kW, V-twin GT-990 Engine  
Control  
Panel  
Oil  
Dipstick  
Data  
Decal  
Exhaust  
Enclosure  
Fuel  
Regulator  
Fuel  
Inlet  
Composite Base  
Battery  
Compartment  
Oil Filter  
Figure 1.2 – 15 kW, V-twin GT-990 Engine Rear View  
AUTOMATIC TRANSFER  
SWITCH  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1 — General Information  
Air-cooled 15 kW Generators  
1.5 SPECIFICATIONS  
1.6 FUEL REQUIREMENTS  
AND RECOMMENDATIONS  
1.5.1 GENERATOR  
With LP gas, use only the vapor withdrawal sys-  
tem. This type of system uses the vapors formed  
above the liquid fuel in the storage tank.  
Rated Max. Continuous Power  
Capacity (Watts*).......................... 13,000 NG/15,000 LP  
Rated Voltage........................................................120/240  
Rated Max. Continuous Load Current (Amps)  
The engine has been fitted with a fuel carburetion  
system that meets the specifications of the 1997  
California Air Resources Board for tamper-proof  
dual fuel systems. The unit will run on natural gas or  
LP gas, but it has been factory set to run on natural  
gas. Should the primary fuel need to be changed to  
LP gas, the fuel system needs to be reconfigured. See  
"Reconfiguring the Fuel System" for instructions on  
reconfiguration of the fuel system.  
120 Volts +...................................... 108.3 NG/125.0 LP  
240 Volts.............................................. 54.2 NG/62.5 LP  
Main Line Circuit Breaker.................................... 70 Amp  
Phase ..............................................................................1  
Number of Rotor Poles....................................................2  
Rated AC Frequency................................................ 60 Hz  
Power Factor ...................................................................1  
Recommended Air Filter ........................... Part # 0C8127  
Battery Requirement......Group 26/26R at -17.8° C ( 0° F)  
12 Volts and 525 Cold-cranking Amperes Minimum  
Weight ............................................................640 Pounds  
Recommended fuels should have a Btu content of at  
least 1,000 Btus per cubic foot for natural gas; or at  
least 2,520 Btus per cubic foot for LP gas. Ask the  
fuel supplier for the Btu content of the fuel.  
Output Sound Level  
@ 23 ft (7m) at full load ...............................71.5 db (A)  
Required fuel pressure for natural gas is five inches  
to seven inches water column (0.18 to 0.25 psi);  
and for liquid propane, 11 inches to 14 inches of  
water column (0.4 to 0.5 psi).  
Normal Operating Range............................-20°F (-28.8°C)  
to 104°F (40°C)  
* Maximum wattage and current are subject to and limited by such  
factors as fuel Btu content, ambient temperature, altitude, engine  
power and condition, etc. Maximum power decreases about 3.5 per-  
cent for each 1,000 feet above sea level; and also will decrease about  
1 percent for each 6° C (42° F) above 16° C (60° F).  
NOTE:  
Any piping used to connect the generator to the  
fuel supply should be of adequate size to ensure  
the fuel pressure NEVER drops below 4 inches  
water colum for natural gas or 10 inches water  
column for liquid propane for all load ranges.  
+ Total current in two separate curcuits. Current in each curcuit must  
not exceed the value stated for 240V.  
1.5.2 ENGINE  
Type of Engine ...................................................... GT-990  
Number of Cylinders.......................................................2  
Rated Horsepower...................................30 @ 3,600 rpm  
Displacement .......................................................... 992cc  
Cylinder Block ......................................Aluminum w/Cast  
Iron Sleeve  
1.7 FUEL CONSUMPTION  
Model #  
Nat. Gas (*)  
LP Vapor (**)  
1/2 Load Full Load 1/2 Load  
Full Load  
2.40/88  
05176  
156  
220  
1.58/58  
Valve Arrangement .................................. Overhead Valves  
Ignition System ...............................Solid-state w/Magneto  
Recommended Spark Plug...................................RC12YC  
Spark Plug Gap............................ 0.508 mm (0.020 inch)  
Compression Ratio....................................................9.5:1  
Starter.....................................................................12Vdc  
Oil Capacity Including Filter.....................Approx. 1.7 Qts  
Recommended Oil Filter ......................... Part # 070185B  
Recommended Air Filter ........................... Part # 0C8127  
Operating RPM.........................................................3,600  
*Natural gas is in cubic feet per hour.  
**LP is in gallons per hour/cubic feet per hour.  
1.8 RECONFIGURING THE  
FUEL SYSTEM  
To reconfigure the fuel system from NG to LP, follow  
these steps:  
NOTE:  
The primary regulator for the propane supply is  
NOT INCLUDED with the generator. A fuel pres-  
sure of 11 to 14 inches of water column (0.4 to  
0.5 psi) to the fuel inlet of the generator MUST  
BE SUPPLIED.  
1. Turn off the gas supply. (if connected)  
2. Open the roof and remove the door.  
3. Remove the battery. (if installed)  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2 — Installation  
Air-cooled 15 kW Generators  
4. Remove the engine air in baffle located on the left-  
hand side of the battery compartment. Two M6  
screws are located on top of the baffle and two  
M6 screws are located on the inside of the baffle  
towards the back.  
5. Remove the small hose clamp and hose from the  
fuel regulator. It may be necessary to pry the hose  
off of the brass fitting using a screwdriver to gen-  
tly lift up the hose edge.  
14. It may be necessary to make minor adjustments  
to the preset adjustment screw settings to achieve  
maximum power, particularly at higher altitudes.  
If experiencing problems with the unit produc-  
ing maximum power, follow the procedure in  
"Adjusting the Fuel Regulator".  
2.1 INSTALLATION  
Install the generator set, in its protective enclosure,  
outdoors, where adequate cooling and ventilating air  
is always available. Consider these factors:  
6. Remove the small brass hose fitting from the  
regulator casting.  
• Install the unit where air inlet and outlet openings  
will not become obstructed by leaves, grass, snow,  
etc. If prevailing winds will cause blowing or drift-  
ing snow, consider using a windbreak to protect  
the unit.  
7. Place the small fuel jet, thread side first, into the  
threaded hole originally occupied by the brass  
hose fitting (Figure 1.3).  
Figure 1.3 - Demand Regulator  
• Install the generator on high ground where water  
OUTLET PORTS  
FUEL HOSE  
levels will not rise and endanger it.  
• Allow sufficient room on all sides of the generator  
for maintenance and servicing. A good rule is to  
allow three feet of space on all sides.  
BRASS HOSE  
FITTING  
IDLE CIRCUIT  
PORT  
BRASS HOSE  
FITTING  
SMALL  
FUEL JET  
1
NP  
• Where strong prevailing winds blow from one  
direction, face the generator air inlet openings to  
the prevailing winds.  
REGULATOR  
HOUSING PORT  
ADJUSTER  
SCREWS  
• Install the generator as close as possible to the fuel  
supply, to reduce the length of piping.  
2.1.1 REMOTE MONITORING CONNECTIONS  
Mounted in the transfer switch is relay contact board  
(Figure 2.1) that can be used to remotely monitor  
various functions of the generator system.  
8. Using a short No. 2 Phillips screw driver, thread  
the small fuel jet into the regulator casting. Do  
not over tighten.  
9. Apply thread sealant to the threads of the hose  
fitting and replace it into the regulator body.  
10. Re-attach the small hose and hose clamp and  
tighten as necessary.  
The contacts are rated as shown below. Failure to fol-  
low these ratings will cause unit failure.  
• Arrangement: SPCT (Form C)  
• Ratings: Resistive Load, 4Amp max switching  
current at 30VDC; 2Amp max switching  
current at 125VAC  
11. Replace the engine air in baffle using the four M6  
screws.  
12. Identify both brass adjustment screws on the  
regulator.  
• Wire Range: 26-14Awg  
Terminal tightening torque: 5 in/lb.  
NOTE:  
Figure 2.1 — Remote Monitoring Connections  
One adjustment screw can be accessed from the  
front of the unit and the second can be accessed  
from the back of the unit enclosure by removing  
the plastic hole plug. The screw can be turned  
with a long flat blade screwdriver.  
RELAY KEY  
RELAY 1  
C
NC  
NO  
C
ENGINE  
RUN  
RELAY 2  
NC  
NO  
C
SWITCH IN  
EMERGENCY  
13. To adjust the system to run on LP fuel, turn  
BOTH adjuster screws 1/2 TURN CLOCKWISE.  
The system should now be set for maximum  
power and best perfomance. DO NOT, UNDER  
ANY CIRCUMSTANCES, REMOVE THE SET  
PINS FROM THE REGULATOR HOUSING.  
THIS WILL VOID THE WARRANTY.  
RELAY 3  
NC  
NO  
C
SWITCH IN  
AUTO  
RELAY 4  
NC  
NO  
C
COMMON  
ALARM  
RELAY 5  
NC  
NO  
C
LOW  
FUEL  
RELAY 6  
NC  
NO  
DOOR  
OPEN  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2 — Installation  
Air-cooled 15 kW Generators  
Remote monitoring functions are only available with  
the AUTO/OFF/MANUAL switch in the Auto or Manual  
position. Since the contacts are SPDT, it is possible  
to monitor either state of each alarm function.  
2.1.3 TRANSFER SWITCH CONNECTION  
These switches (Figure 2.3) are used with a single-  
phase system, when the single-phase NEUTRAL line  
is to be connected to a Neutral Lug and is not to be  
switched.  
Relay 1: Engine running, normally closed.  
Engine not running, normally open  
Figure 2.3 — Typical 2-Pole Transfer Mechanism  
(200 Amp Shown)  
Relay 2: Transfer Switch in Emergency, normally  
closed  
Transfer Switch in Utility, normally open  
UTILITY LUGS  
Relay 3: Control panel switch in Auto, normally  
open  
UTILITY  
CLOSING  
COIL  
Control panel switch in Manual or Off, nor-  
mally closed  
Relay 4: The common alarm is activated by any of  
the following shutdown faults  
Low Oil Pressure  
High Engine Temperature  
GENERATOR  
LUGS (E1 & E2)  
GENERATOR  
CLOSING  
COIL  
Overspeed  
Overcrank  
Common alarm active, normally open  
No Common alarm, normally closed  
Relay 5: Spare, not used on this model  
Relay 6: Enclosure door open, normally closed  
Enclosure door closed, normally open  
LOAD LUGS (T1 & T2)  
Solderless, screw-type terminal lugs are standard.  
Switch  
Rating  
200A  
Wire  
Range  
#6-250 MCM  
Conductor Tightening  
Torque  
275 in-lbs.  
2.1.2 ROOF OPEN ALARM  
This generator is equipped with an alarm to detect  
when the roof of the enclosure is open. A limit switch  
that is installed in the generator enclosure controls  
this alarm. During shipping, the generator's enclosure  
panels may have shifted and this limit switch may  
require adjustment. Simply loosen the two screws  
and adjust the placement of the limit switch. The arm  
of the limit switch should be in the depressed posi-  
tion when the enclosure roof is closed and the door  
latch is secure (see Figure 2.2).  
Conductor sizes must be adequate to handle the  
maximum current to which they will be subjected to,  
based on the 75°C column of tables, charts, etc. used  
to size conductors. The installation must comply fully  
with all applicable codes, standards and regulations.  
Before connecting wiring cables to terminals, remove  
any surface oxides from the cable ends with a wire  
brush. All power cables should enter the switch next  
to transfer mechanism terminals. If ALUMINUM con-  
ductors are used, apply corrosion inhibitor to con-  
ductors. Tighten terminal lugs to the torque values as  
noted on the decal located on the inside of the door.  
After tightening terminal lugs, carefully wipe away  
any excess corrosion inhibitor.  
Figure 2.2 — Limit Switch  
All power cables should enter the switch next to the  
transfer mechanism terminals.  
Up  
Use a torque wrench to tighten the conductors,  
Down  
being sure not to over tighten, or damage to  
the switch base could occur. If not tightened  
enough, a loose connection would result, caus-  
ing excess heat which could damage the switch  
base.  
Slots  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2 — Installation  
Air-cooled 15 kW Generators  
Connect power source load conductors to clearly  
marked transfer mechanism terminal lugs as fol-  
lows  
Lead-acid batteries present a risk of fire because  
they generate hydrogen gas. The  
following procedures are to be followed:  
1. Connect UTILITY (NORMAL) power source cables  
to switch terminals N1, N2.  
• DO NOT SMOKE when near the battery;  
• DO NOT cause flame or spark in battery area; and  
• Discharge static electricity from body before touch-  
ing the battery by first touching a grounded metal  
surface.  
2. Connect customer LOAD leads to switch termi-  
nals T1, T2.  
Conductors must be properly supported, of approved  
insulative qualities, protected by approved conduit,  
and of the correct wire gauge size in accordance with  
applicable codes.  
Be sure the AUTO/OFF/MANUAL switch is set to  
the OFF position before connecting the battery  
cables. If the switch is set to AUTO or MANUAL,  
the generator can crank and start as soon as the  
battery cables are connected.  
Be sure to maintain proper electrical clearance  
between live metal parts and grounded metal. Allow  
at least 1/2 inch for 100-400 amp circuits.  
Be sure the utility power supply is turned off, or  
sparking may occur at the battery posts as the  
2.2 BATTERY INSTALLATION  
DANGER  
cables are attached and cause an explosion.  
Fill the battery with the proper electrolyte fluid if  
necessary and have the battery fully charged before  
installing it.  
Do not dispose of the battery in a fire. The  
battery is capable of exploding.  
Before installing and connecting the battery, complete  
the following steps:  
A battery presents a risk of electrical shock  
and high short circuit current. The following pre-  
1. Set the generator's AUTO/OFF/MANUAL switch to  
cautions are to be observed when working on  
batteries:  
OFF.  
2. Turn off utility power supply to the transfer  
• Remove watches, rings or other metal objects;  
• Use tools with insulated handles;  
• Wear rubber gloves and boots;  
• Do not lay tools or metal parts on top of the  
battery; and  
switch.  
3. Remove the 5 amp fuse from the generator con-  
trol panel.  
• Disconnect charging source prior to connecting or  
disconnecting battery terminals.  
If the AUTO/OFF/MANUAL switch is not set to its  
OFF position, the generator can crank and start  
as soon as the battery cables are connected. If  
the utility power supply is not turned off, spark-  
ing can occur at the battery posts and cause an  
explosion.  
Do not open or mutilate the battery. Released  
electrolyte has been known to be harmful to the  
skin and eyes, and to be toxic.  
Battery cables were factory connected at the genera-  
tor (Figure 2.4). Connect cables to battery posts as  
follows:  
The electrolyte is a dilute sulfuric acid that is  
harmful to the skin and eyes. It is electrically  
conductive and corrosive.  
4. Connect the red battery cable (from starter con-  
tactor) to the battery post indicated by a positive,  
POS or (+).  
5. Connect the black battery cable (from frame  
ground) to the battery post indicated by a nega-  
tive, NEG or (—).  
The following procedures are to be observed:  
• Wear full eye protection and protective clothing;  
• Where electrolyte contacts the skin, wash it off  
immediately with water;  
• Where electrolyte contacts the eyes, immediately  
flush thoroughly with water and seek medical  
attention; and  
6. Replace the 5 amp fuse in the generator control  
panel.  
• Spilled electrolyte is to be washed down with an  
acid neutralizing agent. A common practice is to  
use a solution of 1 pound (500 grams) bicarbonate  
of soda to 1 gallon (4 liters) or water. The bicar-  
bonate of soda solution is to be added until the  
evidence of reaction (foaming) has ceased. The  
resulting liquid is to be flushed with water and the  
area dried.  
NOTE:  
Damage will result if battery connections are made  
in reverse.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3 — Post Installation Start-up and Adjustments  
Air-cooled 15 kW Generators  
Figure 2.4 – Battery Cable Connections  
3.1 BEFORE INITIAL START-UP  
Before starting, complete the following:  
1. Set the generator’s main circuit breaker to its  
OFF (or open) position.  
2. Set the generator's AUTO/OFF/MANUAL switch to  
the OFF position.  
3. Turn OFF the utility power supply to the transfer  
switch using the means provided (such as the  
utility main line circuit breaker).  
4. Check the engine crankcase oil level and, if neces-  
sary, fill to the dipstick FULL mark with the rec-  
ommended oil. Do not fill above the FULL mark.  
5. Check the fuel supply. Gaseous fuel lines must  
have been properly purged and leak tested in  
accordance with applicable fuel-gas codes. All  
fuel shutoff valves in the fuel supply lines must  
be open.  
NOTE:  
The generator is equipped with a battery trickle  
charger that is active when the unit is set up for  
automatic operation. With the battery installed  
and utility power source voltage available to the  
transfer switch, the battery receives a trickle  
charge while the engine is not running, to prevent  
self-discharge. The trickle charger is designed to  
help extend the life of the battery by maintain-  
ing the battery when the unit is not running. The  
trickle charge feature cannot be used to recharge  
a discharged battery.  
Never operate the engine with the oil level  
below the “Add” mark on the dipstick. Doing  
this could damage the engine.  
3.2 CHECK TRANSFER SWITCH  
OPERATION  
Refer to the "Manual Operation" section of the owner’s  
manual for manual operation procedures.  
2.3 THE BATTERY  
DANGER  
Servicing of the battery is to be performed or super-  
vised by personnel knowledgeable of batteries and  
the required precautions. Keep unauthorized person-  
nel away from batteries.  
Do not attempt manual transfer switch opera-  
tion until all power voltage supplies to the  
transfer switch have been positively turned off.  
Failure to turn off all power voltage supplies  
will result in extremely hazardous and possibly  
fatal electrical shock.  
When replacing the battery, use the following type of  
battery: Group 26/26R 12-volt battery with a rating  
of 525 cold-cranking amps minimum at -17.8º C (0º  
F) minimum. When using a maintenance-free battery,  
it is not necessary to check the specific gravity or  
electrolyte level. Have these procedures performed  
at the intervals specified in the “Service Schedule.” A  
negative ground system is used. Battery connections  
are shown on the wiring diagrams. Make sure the  
battery is correctly connected and terminals are tight.  
Observe battery polarity when connecting the battery  
to the generator set.  
3.3 ELECTRICAL CHECKS  
Complete electrical checks as follows:  
1. Turn on the utility power supply to the transfer  
switch using the means provided (such as a utility  
main line circuit breaker).  
DANGER  
The transfer switch is now electrically “hot.”  
Contact with “hot” parts will result in extremely  
hazardous and possibly fatal electrical shock.  
Proceed with caution.  
2. Use an accurate AC voltmeter to check utility  
power source voltage across terminals N1 and  
N2. Nominal line-to-line voltage should be 240  
volts AC.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3 — Post Installation Start-up and Adjustments  
Air-cooled 15 kW Generators  
3. Check utility power source voltage across termi-  
3.4 GENERATOR TESTS UNDER LOAD  
nals N1 and the transfer switch neutral lug; then  
across terminal N2 and neutral. Nominal line-to-  
neutral voltage should be 120 volts AC.  
4. When certain that utility supply voltage is compat-  
ible with transfer switch and load circuit ratings,  
turn OFF the utility power supply to the transfer  
switch.  
Do not attempt manual transfer switch opera-  
tion until all power voltage supplies to the  
transfer switch have been positively turned off.  
Failure to turn off all power voltage supplies  
will result in extremely hazardous and possibly  
fatal electrical shock.  
5. Set the generator's main circuit breaker to its  
OFF (or OPEN) position. Initial tests will be con-  
ducted at no-load condition.  
6. On the generator panel, set the AUTO/OFF/  
MANUAL switch to MANUAL. The engine should  
crank and start.  
7. Let the engine warm up for about five minutes to  
allow internal temperatures to stabilize. Then, set  
the generator’s main circuit breaker to its ON (or  
closed) position.  
To test the generator set with electrical loads applied,  
proceed as follows:  
1. Set generator’s main circuit breaker to its OFF  
(or OPEN) position.  
2. Set the generator's AUTO/OFF/MANUAL  
switch to OFF.  
3. Turn OFF the utility power supply to the transfer  
switch, using the means provided (such as a util-  
ity main line circuit breaker).  
4. Manually set the transfer switch to the STANDBY  
position, i.e., load terminals connected to the  
generator's E1/E2 terminals. The transfer switch  
operating lever should be down.  
5. Set the generator's AUTO/OFF/MANUAL switch  
to MANUAL. The engine should crank and start  
immediately.  
DANGER  
Proceed with caution! Generator power voltage  
is now supplied to the transfer switch. Contact  
with live transfer switch parts will result in dan-  
gerous and possibly fatal electrical shock.  
8. Connect an accurate AC voltmeter and a fre-  
quency meter across transfer switch terminal  
lugs E1 and E2. Voltage should be 242-252 volts;  
frequency should read about 61-63 Hertz.  
9. Connect the AC voltmeter test leads across ter-  
minal lug E1 and neutral; then across E2 and  
neutral. In both cases, voltage reading should be  
121-126 volts AC.  
10. Set the generator’s main circuit breaker to its  
OFF (or open) position. Let the engine run at no-  
load for a few minutes to stabilize internal engine  
generator temperatures.  
6. Let the engine stabilize and warm up for a few  
minutes.  
7. Set the generator’s main circuit breaker to its ON  
(or closed) position. Loads are now powered by  
the standby generator.  
8. Turn ON electrical loads. Apply an electrical load  
equal to the full rated wattage/amperage capacity  
of the installed generator.  
9. Connect an accurate AC voltmeter and a frequen-  
cy meter across terminal lugs E1 and E2. Voltage  
should be greater than 230 volts; frequency  
should be greater than 58 Hertz.  
10. Let the generator run at full rated load for 20-30  
minutes. Listen for unusual noises, vibration or  
other indications of abnormal operation. Check  
for oil leaks, evidence of overheating, etc.  
11. When testing under load is complete, turn OFF  
electrical loads.  
11. Set the generator's AUTO/OFF/MANUAL switch to  
OFF. The engine should shut down.  
NOTE:  
It is important not to proceed until certain that  
generator AC voltage and frequency are correct  
and within the stated limits. Generally, if both AC  
frequency and voltage are high or low, the engine  
governor requires adjustment. If frequency is cor-  
rect, but voltage is high or low, the generator’s  
voltage regulator requires adjustment.  
12. Set the generator's main circuit breakers to their  
OFF (or open) positions.  
13. Let the engine run at no-load for a few minutes.  
14. Set the AUTO/OFF/MANUAL switch to OFF. The  
engine should shut down.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3 — Post Installation Start-up and Adjustments  
Air-cooled 15 kW Generators  
3. Turn on electrical loads. Be cautious not to over-  
3.5 CHECKING AUTOMATIC  
load the generator. Use the following chart as a  
guide:  
OPERATION  
To check the system for proper automatic operation,  
proceed as follows:  
Model  
005176  
120 Volts  
108.3 amps  
240 Volts  
54.1 amps  
1. Set the generator’s main circuit breaker to it’s  
OFF (or open) position.  
4. When full load has been achieved. Connect a fre-  
quency meter to the output lugs of the generator’s  
main line circuit breaker.  
2. Check that the AUTO/OFF/MANUAL switch is set  
to OFF.  
3. Manually set the transfer switch to the UTILITY  
position, i.e., load terminals connected to the util-  
ity power source side.  
4. Turn ON the utility power supply to the transfer  
switch, using the means provided (such as a util-  
ity main line circuit breaker).  
5. Set the AUTO/OFF/MANUAL switch to AUTO.  
Then set the generator’s main circuit breaker to  
its ON (or closed) position. The system is now  
ready for automatic operation.  
5. The fuel regulator is fitted with two adjustment  
screws. While watching the frequency meter,  
slowly turn the adjustment screw clockwise or  
counterclockwise one at a time until highest fre-  
quency is read on the meter. Only limited adjust-  
ment is available between the set pins. Under no  
circumstances should any of the pins be removed  
(Figures 3.1 and 3.2).  
Figure 3.1 — Dual Fuel Regulators  
6. Turn OFF the utility power supply to the transfer  
switch.  
V-twin Engine  
With the AUTO/OFF/MANUAL switch at AUTO, the  
engine should crank and start when the utility source  
power is turned OFF. After starting, the transfer  
switch should connect load circuits to the standby  
side. Let the system go through its entire automatic  
sequence of operation.  
Adjustment  
Screw  
(Both Sides)  
With the generator running and loads powered by  
generator AC output, turn ON the utility power supply  
to the transfer switch. The following should occur:  
Set Pin  
(Both Sides)  
• After about 15 seconds, the switch should transfer  
loads back to the utility power source.  
• About one minute after retransfer, the engine  
should shut down.  
6. When the highest frequency is reached maximum  
power has been set. Then turn both adjustment  
screws 1/4 turn counterclockwise. Regulator is  
now set.  
3.6 ADJUSTING THE REGULATOR  
(NATURAL GAS ONLY)  
Although the generator has been factory set to pro-  
vide maximum power, it may be necessary in some  
areas to adjust this setting. Because natural gas has  
different BTU or power content across the country  
the engine may not perform as designed.  
Figure 3.2 — Placement of Regulator  
If experiencing engine problems at high or full load  
conditions follow these steps. It will require a fre-  
quency meter to perform this procedure.  
1. Turn off utility power to the main distribution  
panel in the house. This can be done by switching  
the service main breaker to the off or open posi-  
tion.  
2. Allow the generator to start before loading the  
generator. Confirm the no-load frequency with  
the roof open and door off is set at 63-63.5 Hz.  
Transfer load to emergency circuits.  
Adjustment Screw  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3 — Post Installation Start-up and Adjustments  
Air-cooled 15 kW Generators  
7. Turn utility power to the main distribution panel  
Figure 3.4 — V-twin Full Load Speed Adjust  
Screw  
back on. This can be done by switching the ser-  
vice main breaker to the on or closed position.  
Allow the generator to shut down.  
Full Load Speed Adjust Screw  
Do not make any unnecessary adjustments.  
Factory settings are correct for most applica-  
tions. However, when making adjustments, be  
careful to avoid overspeeding the engine.  
If this procedure or equipment are not available,  
locate the nearest Service Dealer and they can per-  
form the adjustments.  
NOTE:  
A service fee may be charged for this adjustment.  
3.7 ENGINE GOVERNOR ADJUSTMENT  
If both AC frequency and voltage are correspondingly  
high or low, adjust the engine governor as follows:  
3.7.1 ADDITIONAL CORROSION  
PROTECTION  
Periodically spray all engine linkage parts and brack-  
ets with corrosion inhibiting spray such as WD-40®  
or a comparable product.  
1. Loosen governor clamp bolt (See Figure 3.3).  
Figure 3.3 — V-twin Engine Governor  
Adjustment  
3.8 VOLTAGE REGULATOR  
ADJUSTMENT  
Idle Spring  
With the frequency between 62-63.5 Hertz, slowly  
turn the slotted potentiometer (Figure 3.5) until line  
voltage reads 244-252 volts.  
Governor  
Shaft  
(Rotate  
Clockwise)  
NOTE:  
Remove the access panel on top of the control  
panel to adjust the voltage regulator.  
Figure 3.5 – Voltage Adjustment Potentiometer  
No Load Idle  
Adjustment Screw  
Governor Clamp Bolt  
2. Completely remove the idle spring.  
3. With governor arm at wide open throttle position,  
rotate governor shaft fully clockwise. Tighten  
clamp bolt to 84 inch-pounds.  
4. Start unit and apply full load. Use full load speed  
adjust screw (Figure 3.4) to adjust frequency to  
58 Hz.  
Turn to  
adjust voltage.  
5. Remove load, stop engine, loosen the idle adjust  
screw and reconnect the idle spring.  
6. Using a hand, push the governor arm to the  
closed throttle position. Make sure the idle spring  
does not stretch at all.  
NOTE:  
7. Restart the unit.  
The voltage regulator is housed above the generator's  
control panel. The regulator maintains a voltage in  
direct proportion to frequency. For example, at 62  
Hertz, line-to-neutral voltage will be 124 volts.  
8. Slowly turn the idle adjust screw to adjust the no-  
load idle frequency to 63-63.5 Hz.  
9. The governor is now set.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4 — Operation  
Air-cooled 15 kW Generators  
and N2.  
4.1 USING THE AUTO/OFF/MANUAL  
SWITCH (FIGURE 4.1)  
3. Set the generator’s AUTO/OFF/MANUAL switch to  
AUTO.  
4. Set the generator’s main circuit breaker to its ON  
(or closed) position.  
4.1.1 “AUTO” POSITION  
With the preceding steps complete, the generator will  
start automatically when utility source voltage drops  
below a preset level. After the unit starts, loads are  
transferred to the standby power source. Refer to  
“Sequence of Automatic Operation.”  
Selecting this switch position activates fully automatic  
system operation. It also permits starting and exercising  
of the engine every seven days with the exercise timer  
(see "Generator Test Under Load"). This position also is  
used for remote starting, when it is set up.  
4.3 SEQUENCE OF AUTOMATIC  
4.1.2 “OFF” POSITION  
This switch position shuts down the engine. This  
position also prevents automatic operation.  
OPERATION  
The generator’s control panel houses a control logic  
circuit board. This board constantly monitors util-  
ity power source voltage. Should that voltage drop  
below a preset level, circuit board action will signal  
the engine to crank and start. After the engine starts,  
the circuit board signals the transfer switch to acti-  
vate and connect load circuits to the standby power  
supply (load terminal lugs T1/T2 connect to terminal  
lugs E1/E2).  
4.1.3 “MANUAL POSITION  
Set the switch to MANUAL to crank and start the  
engine. Transfer to standby power will not occur  
unless there is a utility failure.  
Figure 4.1 – Generator Control Panel  
Upon restoration of utility source voltage above a  
preset level, generator circuit board action signals the  
transfer switch to transfer loads back to that power  
supply. After retransfer, the engine is signalled to shut  
down.  
The actual sequence of operation is controlled by  
sensors and timers on a control logic circuit board,  
as follows:  
FUSE  
R
L o c a t  
e
y o u r n e a r e s t  
d e a le r a t  
:
R
POWER SYSTEMS, INC.  
5A  
AUTO OFF MAN.  
SYSTEM SET  
LOW OIL  
HIGH TEMP.  
OVER SPEED  
OVER CRANK  
FUSE  
F L A  
S
H
IN  
N
H
G
O
IN  
G R E E N L E D  
=
SET  
EXERCISE  
TIME  
15A  
U
G
T
IL IT  
E D L E D  
IS E R  
Y
S
E N  
S
S
=
E
A.Utility Voltage Dropout Sensor  
4
F L A  
S
R
E X E R  
C
N
O
T
S
E T  
• This sensor monitors utility source voltage.  
• If utility source voltage drops below about 70  
percent of the nominal supply voltage, the sensor  
energizes a 15-second timer.  
• Once the timer has expired, the engine will crank  
With the switch set to AUTO, the engine may  
crank and start at any time without warning.  
and start.  
B.Engine Warm-up Time Delay  
Such automatic starting normally occurs when  
• This mechanism lets the engine warm up for  
about 10 seconds before the load is transferred  
to a standby source.  
utility power source voltage drops below a pre-  
set level or during the normal exercise cycle. To  
prevent possible injury that might be caused by  
such sudden starts, always set the switch to OFF  
and remove both fuses before working on or  
around the generator or transfer switch. Then,  
place a “Do Not Operate” tag on the generator  
panel and on the transfer switch.  
C.Standby Voltage Sensor  
• This sensor monitors generator AC output volt-  
age. When the voltage has reached 50 percent of  
the nominal rated voltage, transfer to standby  
can occur.  
D.Utility Voltage Pickup Sensor  
4.2 AUTOMATIC TRANSFER  
• This sensor monitors utility power supply volt-  
age. When that voltage is restored to above 70  
percent of the nominal source voltage, a retrans-  
fer time delay starts timing.  
OPERATION  
To select automatic operation, do the following:  
1. Make sure the transfer switch main contacts are  
set to their “Utility” position, i.e., loads connected  
to the utility power source (Figure 4.2).  
E.Retransfer Time Delay  
• This timer runs for about 15 seconds.  
• At end of a 15-second delay, circuit board action  
de-energizes the transfer relay in the transfer  
switch.  
2. Be sure that normal utility power source voltage  
is available to transfer switch terminal lugs N1  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4 — Operation  
Air-cooled 15 kW Generators  
• Retransfer to utility power source then occurs.  
F. Engine Cool-down Timer  
• When the load is transferred back to utility power  
source, the engine cool-down timer starts tim-  
ing.  
3. Note position of transfer mechanism main con-  
tacts by observing the moveable contact carrier  
arm.  
• Manual operation handle towards the top of  
switch mechanism - LOAD terminals (T1, T2) are  
connected to UTILITY terminals (N1, N2).  
• Manual operation handle towards the bottom of  
switch mechanism - LOAD terminals (T1, T2) are  
connected to EMERGENCY terminals (E1, E2).  
• The timer will run for about one minute, and the  
generator will then shut down.  
4.4 MANUAL OPERATION  
DANGER  
Do not use excessive force when operating the  
Do NOT manually transfer under load.  
Disconnect transfer switch from all power sourc-  
es by approved means, such as a main circuit  
breaker(s).  
transfer switch manually or damage could be  
done to the manual handle.  
4.4.1 CLOSE TO NORMAL SOURCE SIDE  
A manual HANDLE is shipped with the transfer  
switch. Manual operation must be checked BEFORE  
the transfer switch is operated electrically. To check  
manual operation, proceed as follows:  
Before proceeding, verify the position of the switch  
by observing the position of manual operation handle  
in Figure 4.2. If the handle is UP, the contacts are  
closed in the NORMAL position, no further action is  
required. If the handle is DOWN, proceed with Step  
1.  
1. Turn the generator’s AUTO/OFF/MANUAL switch  
to OFF.  
2. Turn OFF both UTILITY and EMERGENCY power  
supplies to the transfer switch, with whatever  
means provided (such as the main line circuit  
breakers).  
Step 1: With the handle inserted into the actuating  
shaft, move handle UP. Be sure to hold on to  
the handle as it will move quickly after the  
center of travel.  
Figure 4.2 — Actuating Transfer Switch  
Attach handle to actuating shaft.  
NOTE: Return handle to  
storage position in enclosure  
when finished with manual transfer.  
Move handle  
Move handle  
DOWN for the  
EMERGENCY  
(STANDBY)  
position.  
UP for the  
NORMAL  
(UTILITY)  
position.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4 — Operation  
Air-cooled 15 kW Generators  
7. With an accurate AC voltmeter and frequency  
meter, check the no-load, voltage and frequency.  
Single-phase generator supply:  
4.4.2 CLOSE TO EMERGENCY SOURCE SIDE  
Before proceeding, verify the position of the switch  
by observing the position of the manual operation  
handle in Figure 4.2. If the handle is DOWN, the  
contacts are closed in the EMERGENCY (STANDBY)  
position. No further action is required. If the handle  
is UP, proceed with Step 1.  
Measure across ATS terminal lugs E1 to E2. Also  
check E1 to NEUTRAL and E2 to NEUTRAL.  
a. Frequency.......................................60-62 Hertz  
b. Terminals E1 to E2 ........................240-246 VAC  
c. Terminals E1 to NEUTRAL.............120-123 VAC  
d. Terminals E2 to NEUTRAL.............120-123 VAC  
8. Set the generator’s main circuit breaker (CB1) to  
its OFF or OPEN position.  
Step 1: With the handle inserted into the actuating  
shaft, move the handle DOWN. Be sure to  
hold on to the handle as it will move quickly  
after the center of travel.  
9. Set the AUTO/OFF/MANUAL switch to the OFF  
position to shut down the generator.  
4.4.3 RETURN TO NORMAL SOURCE SIDE  
NOTE:  
Manually actuate switch to return manual operating  
handle to the UP position.  
Do NOT proceed until generator AC output volt-  
age and frequency are correct and within stated  
limits. If the no-load voltage is correct but no-  
load frequency is incorrect, the engine governed  
speed probably requires adjustment. If no-load  
frequency is correct but voltage is not, the voltage  
regulator may require adjustment.  
4.5 VOLTAGE CHECKS  
1. Turn ON the UTILITY power supply to the trans-  
fer switch with whatever means provided (such as  
the UTILITY main line circuit breaker).  
DANGER  
4.6 GENERATOR TESTS UNDER LOAD  
1. Set the generator's main circuit breaker to its  
OFF or OPEN position.  
PROCEED WITH CAUTION. THE TRANSFER  
SWITCH IS NOW ELECTRICALLY HOT. CONTACT  
WITH LIVE TERMINALS RESULTS IN EXTREMELY  
HAZARDOUS AND POSSIBLY FATAL ELECTRICAL  
SHOCK.  
2. Manually actuate the transfer switch main con-  
tacts to their EMERGENCY (STANDBY) position.  
Refer to "Manual Operation".  
2. With an accurate AC voltmeter, check for correct  
voltage.  
3. To start the generator, set the AUTO/OFF/MANUAL  
switch to MANUAL. When engine starts, let it sta-  
bilize for a few minutes.  
Single-phase utility supply:  
4. Turn the generator's main circuit breaker to its  
ON or CLOSED position. The generator now pow-  
ers all LOAD circuits. Check generator operation  
under load as follows:  
Measure across ATS terminal lugs N1 and N2. Also  
check N1 to NEUTRAL and N2 to NEUTRAL.  
3. When certain that UTILITY supply voltage is cor-  
rect and compatible with transfer switch ratings,  
turn OFF the UTILITY supply to the transfer  
switch.  
4. On the generator panel, set the AUTO/OFF/  
MANUAL switch to MANUAL position. The gen-  
erator should crank and start.  
Turn ON electrical loads to the full rated watt-  
age/amperage capacity of the generator. DO  
NOT OVERLOAD.  
With maximum rated load applied, check  
voltage and frequency across transfer switch  
terminals E1 and E2. Voltage should be  
greater than 230 volts and frequency should  
be greater than 59 Hertz.  
5. Let the generator stabilize and warm up at no-  
load for at least five minutes.  
6. Set the generator's main circuit breaker (CB1) to  
its ON or CLOSED position.  
Let the generator run under rated load for at  
least 30 minutes. With unit running, listen for  
unusual noises, vibration, overheating, etc.,  
that might indicate a problem.  
DANGER  
5. When checkout under load is complete, set main  
circuit breaker of the generator to its OFF or  
OPEN position.  
6. Let the generator run at no-load for several min-  
utes. Then, shut down by setting the AUTO/OFF/  
MANUAL switch to its OFF position.  
PROCEED WITH CAUTION. GENERATOR  
OUTPUT VOLTAGE IS NOW BEING DELIVERED  
TO TRANSFER SWITCH TERMINALS. CONTACT  
WITH LIVE TERMINALS RESULTS IN EXTREMELY  
DANGEROUS AND POSSIBLY FATAL ELECTRICAL  
SHOCK.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4 — Operation  
Air-cooled 15 kW Generators  
7. Move the switch's main contacts back to their  
UTILITY position. For example, load connected  
to UTILITY power supply. Refer to "Manual  
Operation". Handle and operating lever of trans-  
fer switch should be in UP position.  
8. Turn on the UTILITY power supply to transfer  
switch, using whatever means provided (such as  
a UTILITY main line circuit breaker). The UTIL-  
ITY power source now powers the loads.  
4.8 PROTECTION SYSTEMS  
4.8.1 LOW OIL PRESSURE SWITCH  
This switch (Figure 4.3) has normally closed con-  
tacts that are held open by engine oil pressure during  
cranking and operating. Should oil pressure drop  
below the 8 psi range, switch contacts close, and the  
engine shuts down. The unit should not be restarted  
until oil is added, and the AUTO/OFF/MANUAL switch  
must be turned to OFF and then back to AUTO.  
9. Set the generator's AUTO/OFF/MANUAL switch to  
its AUTO position. The system is now set for fully  
automatic operation.  
4.8.2 HIGH TEMPERATURE SWITCH  
This switch’s contacts (Figure 4.3) close if the tem-  
perature should exceed approximately 140º C (284º  
F), initiating an engine shutdown. The generator will  
automatically restart and the LED will reset once the  
temperature has returned to a safe operating level.  
4.7 SETTING THE EXERCISE TIMER  
The generator is equipped with an exercise timer.  
Once it is set, the generator will start and exercise  
once every seven days, on the day of the week and at  
the time of day the following sequence is completed.  
During this exercise period, the unit runs for approx-  
imately 12 minutes and then shuts down. Transfer of  
loads to the generator output does not occur during  
the exercise cycle.  
Figure 4.3 – Low Oil Pressure and  
High Temperature Switches  
A switch on the control panel (see Figure 4.1) allows  
for selection of the day and time for system exercise.  
To select the desired day and time of day, the follow-  
ing sequence must be done at that time.  
Low Oil Switch  
High Temp Switch  
1. Verify that the AUTO/OFF/MANUAL switch is set  
to AUTO.  
2. Hold down the set timer switch until the genera-  
tor starts (approximately 10 seconds) and then  
release.  
3. The generator will start and run for approximately  
12 minutes and then shut down on its own. The  
exerciser will then be set to run at that time of day  
every week.  
Oil  
Drain  
Hose  
NOTE:  
Oil Filter  
The exerciser will only work in the AUTO mode  
and will not work unless this procedure is per-  
formed. The exerciser will need to be reset every  
time the 12-volt battery is disconnected and then  
reconnected. The exerciser WILL NOT work if  
dip switch 2 (Remote Not Auto) on the controller  
printed circuit board is ON.  
4.8.3 OVERCRANK  
This feature prevents the generator from damaging  
itself when it continually attempts to start and anoth-  
er problem, such as no fuel supply, prevents it from  
starting. The unit will crank and rest for a preset time  
limit. Then, it will stop cranking, and the LED will  
light indicating an overcrank failure. The AUTO/OFF/  
MANUAL switch will need to be set to OFF and then  
back to AUTO to reset the generator control board.  
NOTE:  
If the fault is not repaired, the overcrank feature  
will continue to activate.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 5 — Maintenance  
Air-cooled 15 kW Generators  
2. Remove the dipstick and wipe it dry with a clean  
cloth.  
4.8.3.1 Approximate Crank Cycle Times  
• 15 seconds ON  
• 7 seconds OFF  
• 7 seconds ON  
• 7 seconds OFF  
Figure 5.2 — Oil Dipstick and Fill  
Oil Dipstick  
• Repeat for 45 seconds  
Approximately 90 seconds total  
4.8.4 OVERSPEED  
Oil Fill  
This feature protects the generator from damage by  
shutting it down if it happens to run faster than the  
preset limit. This protection also prevents the gen-  
erator from supplying an output that could poten-  
tially damage appliances connected to the generator  
circuit. Contact the nearest Authorized Dealer if this  
failure occurs.  
5.1 FUSE  
3. Install the dipstick; then, remove it again. The oil  
level should be at the dipstick “Full” mark. If nec-  
essary, add oil to the “Full” mark only. DO NOT  
FILL ABOVE THE “FULLMARK.  
The generator panel’s 15 amp fuse (Figure 5.1) pro-  
tects the DC control circuit against overload. The fuse  
is wired in series with the battery output lead to the  
panel. If the fuse element has melted open, the engine  
cannot crank or start. Replace the fuse using only an  
identical 15-amp replacement.  
Never operate the engine with the oil level  
The generator panel’s 5 amp fuse protects the battery  
charge circuit against overload. If the fuse element  
has melted open, battery charging will not be pos-  
sible. Replace the fuse using only an identical 5 amp  
replacement. To remove fuse, push cap down and  
rotate counterclockwise.  
below the “Add” mark on the dipstick. Doing  
this could damage the engine.  
4. Install the dipstick.  
5. Reset the AUTO/OFF/MANUAL switch to its origi-  
nal position.  
Figure 5.1 – Generator Control Panel  
5.3 CHANGING THE ENGINE OIL  
5.3.1 ENGINE OIL RECOMMENDATIONS  
FUSE  
R
L o c a t  
e
y o u r n e a r e s t  
d e a le r a t  
:
Use all season SAE 5W-30 synthetic oil or use SAE  
30 oil of American Petroleum Institute (API) Service  
Class SG, SH, SJ or SL.  
R
POWER SYSTEMS, INC.  
5A  
AUTO OFF MAN.  
SYSTEM SET  
LOW OIL  
HIGH TEMP.  
OVER SPEED  
OVER CRANK  
FUSE  
F L  
4
A
S
H
IN  
N
H
G
O
IN  
G R E E N  
L
S
L
E D  
E N  
E D  
=
SET  
EXERCISE  
TIME  
15A  
U
G
T
IL IT  
E D  
IS E R  
Y
S
=
E
F L  
A
S
R
S
Any attempt to crank or start the engine before  
E X E R  
C
N
O
T
S
E T  
it has been properly serviced with the recom-  
mended oil may result in an engine failure.  
5.2 CHECKING THE ENGINE  
OIL LEVEL  
5.3.2 OIL CHANGE PROCEDURE  
To change the oil, proceed as follows:  
For oil capacities, see “Specifications”. For engine oil  
recommendations, see "Changing the Engine Oil". To  
check the engine oil level, proceed as follows (Figure  
5.2):  
1. Run the engine until it is thoroughly warmed up  
then shut OFF the engine.  
2. Immediately after the engine shuts OFF, pull the  
oil drain hose (Figure 5.3) free of its retaining  
clip. Remove the cap from the hose and drain the  
oil into a suitable container.  
1. Start the generator by moving the ATUO/OFF/  
MANUAL switch to the MANUAL position. Allow  
it to run for a short while and then shut it down  
by moving the switch to the OFF position.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 5 — Maintenance  
Air-cooled 15 kW Generators  
Figure 5.3 – Oil Drain Hose and Filter  
Figure 5.4 — Engine Air Cleaner  
Screw  
Oil  
Drain  
Hose  
Cover  
Filter  
Oil Filter  
3. After the oil has drained, replace the cap onto the  
end of the oil drain hose. Retain the hose in the  
clip.  
4. Refill with the proper recommended oil (see  
"Changing the Engine Oil"). See the "Specifications"  
section for oil capacities.  
5.4 CHANGING THE OIL FILTER  
Change the engine oil filter as follows:  
5.6 SPARK PLUG(S)  
1. With the oil drained, remove the old oil filter by  
turning it counterclockwise.  
2. Apply a light coating of clean engine oil to the  
gasket of the new filter. See the "Specifications"  
section for recommended filter.  
3. Screw the new filter on by hand until its gasket  
lightly contacts the oil filter adapter. Then, tighten  
the filter an additional 3/4 to one turn (Figure  
5.3).  
4. Refill with the proper recommended oil (see  
"Changing the Engine Oil"). See the "Specifications"  
section for oil capacities.  
Reset the spark plugs gap or replace the spark plugs  
as necessary. See the “Service Schedule” section for  
maintenance requirements.  
1. Clean the area around the base of the spark plugs  
to keep dirt and debris out of the engine. Clean  
by scraping or washing using a wire brush and  
commercial solvent. Do not blast the spark plugs  
to clean.  
2. Remove the spark plugs and check the condition.  
Replace the spark plugs if worn or if reuse is  
questionable. See the “Service Schedule” section  
for recommended inspection.  
3. Check the spark plug gap using a wire feeler  
gauge. Adjust the gap to 0.50 mm (0.020 inch) for  
by carefully bending the ground electrode (Figure  
5.5).  
5. Start the engine and check for leaks.  
5.5 CHANGING THE ENGINE  
AIR CLEANER  
See Figures 1.1 and 1.2, for the location of the air  
cleaner. Use the following procedure (Figure 5.4):  
Figure 5.5 – Setting the Spark Plug Gap  
1. Turn the two screws counterclockwise to loosen.  
2. Remove the cover and air filter.  
SET PLUG GAP AT 0.50 mm (0.020 inch)  
3. Wipe away dust or debris from inside of the air  
box and around edges.  
4. Install the new air cleaner into the air box.  
5. Install the cover. Turn the two cover screws clock-  
wise to tighten.  
See the “Service Schedule” section for air cleaner  
maintenance. See the "Specifications" section for air  
filter replacement part number.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 5 — Maintenance  
Air-cooled 15 kW Generators  
5.7 BATTERY MAINTENANCE  
Lead-acid batteries present a risk of fire because  
they generate hydrogen gas. The following pro-  
cedures are to be followed:  
The battery should be inspected per the “Service  
Schedule”. The following procedure should be fol-  
lowed for inspection:  
• DO NOT SMOKE when near the battery;  
• DO NOT cause flame or spark in battery area; and  
• Discharge static electricity from body before touch-  
ing the battery by first touching a grounded metal  
surface.  
1. Inspect the battery posts and cables for tightness  
and corrosion. Tighten and clean as necessary.  
2. Check the battery fluid level of unsealed batteries  
and, if necessary, fill with DISTILLED WATER  
ONLY. DO NOT USE TAP WATER IN BATTER-  
IES.  
3. Have the state of charge and condition checked.  
This should be done with an automotive-type bat-  
tery hydrometer.  
Be sure the AUTO/OFF/MANUAL switch is set to  
the OFF position before connecting the battery  
cables. If the switch is set to AUTO or MANUAL,  
the generator can crank and start as soon as the  
battery cables are connected.  
Be sure the utility power supply is turned off,  
DANGER  
Do not dispose of the battery in a fire. The  
and the 5A fuse is removed from the generator  
control panel, or sparking may occur at the bat-  
tery posts as the cables are attached, causing an  
explosion.  
battery is capable of exploding.  
A battery presents a risk of electrical shock  
and high short circuit current. The following pre-  
cautions are to be observed when working on  
batteries:  
5.8 ADJUSTING VALVE CLEARANCE  
After the first 50 hours of operation, adjust the  
valve clearance in the engine.  
• Remove watches, rings or other metal objects;  
• Use tools with insulated handles;  
• Wear rubber gloves and boots;  
• Do not lay tools or metal parts on top of the  
battery; and  
• Disconnect charging source prior to connecting or  
disconnecting battery terminals.  
Important: If feeling uncomfortable about doing this  
procedure or the proper tools are not available, con-  
tact the nearest Authorized Dealer for service assis-  
tance. This is a very important step to insure longest  
life for the engine.  
To adjust valve clearance:  
• Make sure the engine is at room temperature.  
• Make sure that the spark plug wire is removed  
from the spark plug and out of the way.  
Do not open or mutilate the battery. Released  
• Remove the four screws attaching the valve cover  
electrolyte has been known to be harmful to the  
with a #2 or #3 phillips screwdriver.  
skin and eyes, and to be toxic.  
• Make sure the piston is at Top Dead Center (TDC)  
of its compression stroke (both valves closed). To  
get the piston at TDC, remove the intake screen  
at the front of the engine to gain access to the fly-  
wheel nut. Use a large socket and socket wrench  
to rotate the nut and hence the engine. While  
watching the piston through the spark plug hole.  
The piston should move up and down. The piston  
is at TDC when it is up as high as it can go.  
• Loosen the rocker jam nut. Use an 10mm allen  
wrench to turn the pivot ball stud while checking  
clearance between the rocker arm and the valve  
stem with a feeler gauge. Correct clearance is  
0.002-0.004 inch (0.05-0.1 mm). See Figure 5.6.  
The electrolyte is a dilute sulfuric acid that is  
harmful to the skin and eyes. It is electrically  
conductive and corrosive. The following  
procedures are to be observed:  
• Wear full eye protection and protective clothing;  
• Where electrolyte contacts the skin, wash it off  
immediately with water;  
• Where electrolyte contacts the eyes, immediately  
flush thoroughly with water and seek medical  
attention; and  
• Spilled electrolyte is to be washed down with an  
acid neutralizing agent. A common practice is to  
use a solution of 1 pound (500 grams) bicarbonate  
of soda to 1 gallon (4 liters) or water. The bicar-  
bonate of soda solution is to be added until the  
evidence of reaction (foaming) has ceased. The  
resulting liquid is to be flushed with water and the  
area dried.  
NOTE:  
Hold the rocker arm jam nut in place as the pivot  
ball stud is turned.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 5 — Maintenance  
Air-cooled 15 kW Generators  
When valve clearance is correct, hold the pivot ball  
stud in place with the allen wrench and tighten the  
rocker arm jam nut. Tighten the jam nut to 174  
in/lbs. torque. After tightening the jam nut, recheck  
valve clearance to make sure it did not change.  
Figure 5.7 – Cooling Vent Locations  
Figure 5.6 - Valve Clearance Adjustment  
Rocker  
Arm  
Pivot Ball  
Stud  
Jam Nut  
Valve  
Stem  
5.10 ATTENTION AFTER SUBMERSION  
If the generator has been submerged in water,  
it MUST NOT be started and operated. Following  
any submersion in water, have an Authorized Dealer  
thoroughly clean and dry the generator.  
5.11 CORROSION PROTECTION  
• Install new valve cover gasket.  
• Re-attach the valve cover.  
Periodically wash and wax the enclosure using auto-  
motive type products. Frequent washing is recom-  
mended in salt water/coastal areas. Spray engine  
linkages with a light oil such as WD-40®.  
NOTE:  
Start all four screws before tightening or it will not  
be possible to get all the screws in place. Make  
sure the valve cover gasket is in place.  
5.12 OUT OF SERVICE PROCEDURE  
• Re-attach the spark plug wire to the spark plug.  
• Repeat the process for the other cylinder.  
5.12.1 REMOVAL FROM SERVICE  
If the generator cannot be exercised every seven days,  
and it is to be out of service longer than 90 days, pre-  
pare the generator for storage as follows:  
5.9 COOLING SYSTEM  
Air inlet and outlet openings in the generator com-  
partment must be open and unobstructed for con-  
tinued proper operation. This includes such obstruc-  
tions as high grass, weeds, brush, leaves and snow.  
1. Start the engine and let it warm up.  
2. Close the fuel shutoff valve in the fuel supply line  
and allow the unit to shut down.  
3. Once the unit has shut down, it will signal a low  
oil fault.  
Without sufficient cooling and ventilating air flow, the  
engine/generator quickly overheats, which causes it  
to quickly shut down. (See Figure 5.7 for vent loca-  
tions.)  
4. Set the AUTO/OFF/MANUAL switch to OFF and  
turn off the utility power to the transfer switch.  
5. While the engine is still warm from running,  
drain the oil completely. Refill the crankcase with  
oil. See ”Engine Oil Recommendations”.  
6. Attach a tag to the engine indicating the viscosity  
and classification of the oil in the crankcase.  
7. Remove the spark plugs and spray fogging agent  
into the spark plugs threaded openings. Reinstall  
and tighten the spark plugs.  
The exhaust from this product gets extremely  
hot and remains hot after shutdown. High grass,  
weeds, brush, leaves, etc. must remain clear of  
the exhaust. Such materials may ignite and burn  
from the heat of the exhaust system.  
8. Remove the battery and store it in a cool, dry  
room on a wooden board. Never store the battery  
on any concrete or earthen floor.  
The maximum ambient temperature for the  
generator is 48.9° C (104° F).  
9. Clean and wipe the entire generator.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 5 — Maintenance  
Air-cooled 15 kW Generators  
5.12.2 RETURN TO SERVICE  
To return the unit to service after storage, proceed  
as follows:  
1. Set the generator’s main circuit breaker to its  
OFF (or OPEN) position.  
2. Verify that utility power is turned off and that the  
AUTO/OFF/MANUAL switch is set to OFF.  
3. Check the tag on the engine for oil viscosity and  
classification. Verify that the correct recom-  
mended oil is used in the engine (see "Enging Oil  
Requirements"). If necessary, drain and refill with  
the proper oil.  
4. Check the state of the battery. Fill all cells of  
unsealed batteries to the proper level with dis-  
tilled water. DO NOT USE TAP WATER IN THE  
BATTERY. Recharge the battery to 100 percent  
state of charge, or, if defective, replace the bat-  
tery. See the “Specifications” section for type and  
size.  
5. Clean and wipe the entire generator.  
6. Remove the 5A fuse from the generator control  
panel.  
7. Reconnect the battery. Observe battery polarity.  
Damage may occur if the battery is connected  
incorrectly. Replace the 5A fuse in the generator  
control panel.  
8. Open the fuel shutoff valve.  
9. Start the unit by moving the AUTO/OFF/MANUAL  
switch to MANUAL. Allow the unit to warm up  
thoroughly.  
10. Stop the unit and set the AUTO/OFF/MANUAL  
switch to AUTO. Set the generator’s main circuit  
breaker to its ON (or CLOSED) position.  
11. Turn on the utility power to the transfer switch.  
12. The generator is now ready for service.  
NOTE:  
If the battery was dead or disconnected, the exer-  
cise timer must be reset.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 5 — Maintenance  
Air-cooled 15 kW Generators  
7 KW - 40 KW SMALL STANDBY GENERATOR SETS  
Following is a recommended maintenance schedule for small standby and residential generator sets from 7 kW to  
40 kW in size, and applies to gas engine driven units. The established intervals in the schedule are the maximum  
recommended when the unit is used in an average service application. They will need to be decreased (performed  
more frequently) if the unit is used in a severe application. Use calendar time from the previous maintenance  
interval to determine the next required maintenance interval.  
Service Maintenance Interval Information:  
The various service maintenance intervals are designated by interval numbers as follows:  
1 An early inspection of the generator set to insure it is ready to operate when required and to identify any poten-  
tial problem areas.  
Performed monthly or following each 10 hours of operation of the unit and requires approximately .5 man-  
hours per unit to complete.  
This inspection may be performed by the end user providing the following safety steps are taken to prevent  
the engine from starting automatically without warning:  
To prevent injury, perform the following steps in the order indicated before starting any maintenance:  
• Disable the generator set from starting and/or connecting to the load by setting the control panel Auto/Off/  
Manual switch to the “OFF” position.  
• Remove the control panel fuse.  
• Turn off the battery charger.  
• Remove the negative battery cable.  
The battery charger must be turned off BEFORE removing the battery cable to prevent an over current condition  
from burning out sensitive control panel components and circuits.  
Following all maintenance, reverse these steps to insure the unit is returned to standby setup for normal  
operation when required.  
2 A wear-in service inspection of the generator set to insure it is ready to operate and carry the load when  
required, and to identify any potential problem areas.  
Performed ONLY ONCE following the first three months or the first 30 hours of operation after purchase of  
the unit and requires approximately 2.5 man-hours per unit to complete.  
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge  
to accomplish and should be performed only by an Authorized Service Dealer.  
3 An operational inspection of the generator set to insure it is ready to operate and carry the load when required,  
and to identify any potential problem areas.  
Performed semi-annually or following each 50 hours of operation of the unit and requires approximately 1.5  
man-hours per unit to complete.  
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge  
to accomplish and should be performed only by an Authorized Service Dealer.  
4 A mid-level inspection of the generator set to insure it is ready to operate and carry the load when required,  
and to identify any potential problem areas.  
Performed annually or following each 100 hours of operation of the unit and requires approximately 4.0  
man-hours per unit to complete.  
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge  
to accomplish and should be performed only by an Authorized Service Dealer.  
5 A comprehensive inspection of the generator set to insure it is properly serviced and ready to operate and carry  
the load when required, and to identify any potential problem areas.  
Performed annually or following each 250 hours of operation of the unit and requires approximately 6.0  
man-hours per unit to complete.  
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge  
to accomplish and should be performed only by an Authorized Service Dealer.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 5 — Maintenance  
Air-cooled 15 kW Generators  
Maintenance Level 1  
Level 2  
Level 3  
Level 4  
Level5  
Tasks  
Recom-  
mended  
Task  
Task  
Required  
Task  
Task  
Required  
Task  
Comp.  
Comp. to be done Comp.  
Semi-  
Initials) to be done Initials) annually/  
6 months 50 hrs.  
Required  
Comp. to be done Comp.  
Bi- (Date-  
Annually/ Initials) annually/ Initials)  
100 hrs. 250 hrs.  
to be done (Date- Required (Date-  
monthly/  
10 hrs.  
(Date- to be done (Date-  
Initials)  
1. Disable the unit  
from operating  
per the first page  
warning.  
2. Check the engine  
oil level. Adjust  
as necessary.  
3. Check the natural  
gas delivery  
system for leaks  
and correct  
pressure on gas  
engine driven  
units. Tighten  
connections as  
necessary.  
4. Check the air  
inlets and outlets  
for debris. Clean  
as necessary.  
5. Check the battery  
electrolyte level  
and specific  
gravity if  
accessible. Adjust  
as necessary.  
6. Check the battery  
posts, cables,  
and charger for  
loose  
connections,  
corrosion, and  
proper operation.  
Correct as  
necessary.  
7. Check the unit  
wiring for loose  
connections,  
corrosion, and  
damage. Correct  
as necessary.  
8. Check the engine  
valve clearance.  
Adjust as  
necessary.  
9. Visually inspect  
the unit looking  
for leaks, wear or  
damage, loose  
connections or  
components, and  
corrosion. Correct  
as necessary.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 5 — Maintenance  
Air-cooled 15 kW Generators  
Maintenance Level 1  
Level 2  
Level 3  
Level 4  
Level5  
Tasks  
Recom-  
mended  
Task  
Comp.  
Task  
Comp. to be done Comp.  
Semi-  
Initials) to be done Initials) annually/  
6 months 50 hrs.  
Required  
Task  
Task  
Required  
Task  
Required  
Comp. to be done Comp.  
Bi- (Date-  
Annually/ Initials) annually/ Initials)  
to be done (Date- Required (Date-  
monthly/  
10 hrs.  
(Date- to be done (Date-  
Initials)  
100 hrs.  
250 hrs.  
10. Test the engine  
and transfer  
switch safety  
devices. Correct  
and/or adjust as  
necessary.  
11. Initiate an  
automatic start  
and transfer of  
the unit to site  
load and exercise  
it for at least 1  
hour looking for  
leaks, loose  
connections or  
components, and  
abnormal  
operating  
conditions.  
Correct as  
necessary.  
12. Start and  
exercise the unit  
at full rated load  
(use a load bank  
if the site load is  
not enough) for  
at least 2 hours  
looking for leaks,  
loose  
connections or  
components, and  
abnormal  
operating  
conditions.  
Correct as  
necessary.  
13. Perform an  
engine oil  
analysis (send a  
sample to a lab  
for results).  
Change the  
engine oil and  
filters if the  
analysis results  
indicate this is  
required.  
14. Change the  
engine oil.  
15. Replace the  
engine oil filter(s).  
*
*
* Change oil and filter after first eight (8) hours of operation and then every 100 hours thereafter. Change sooner when operating under a heavy load or in  
a dusty or dirty environment or in high ambient temperatures.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 5 — Maintenance  
Air-cooled 15 kW Generators  
Maintenance Level 1  
Level 2  
Level 3  
Level 4  
Level5  
Tasks  
Recom-  
mended  
Task  
Task  
Required  
Task  
Task  
Required  
Task  
Comp.  
Comp. to be done Comp.  
Semi-  
Initials) to be done Initials) annually/  
6 months 50 hrs.  
Required  
Comp. to be done Comp.  
Bi- (Date-  
Annually/ Initials) annually/ Initials)  
100 hrs. 250 hrs.  
to be done (Date- Required (Date-  
monthly/  
10 hrs.  
(Date- to be done (Date-  
Initials)  
16. Replace the  
engine air  
filter(s).  
17. Perform a 5  
minute no-load  
operational run  
of the unit  
looking for any  
post service  
problems.  
18. Return the unit  
to standby setup  
for operation  
when required.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 6 — Troubleshooting  
Air-cooled 15 kW Generators  
6.1 TROUBLESHOOTING GUIDE  
Problem  
Cause  
Correction  
The engine will not crank.  
1. Fuse blown  
1. Replace 15A fuse on generator  
control panel.  
2. Tighten, clean or replace  
as necessary.  
2. Loose, corroded or defective  
battery cables  
3. Defective starter motor  
4. Dead Battery  
3. *  
4. Charge or replace battery.  
The engine cranks but  
will not start.  
1. Out of fuel  
1. Replenish fuel.  
2. *  
3. *  
2. Defective fuel solenoid (FS)  
3. Open #14 wire from  
engine control board  
4. Defective spark plug(s)  
5. Valve lash out of adjustment.  
4. Clean, re-gap or replace plug(s).  
5. Reset valve lash.  
The engine starts hard  
and runs rough.  
1. Air cleaner  
1. Check, replace air cleaner.  
plugged or damaged  
2. Defective spark plug(s)  
3. Fuel regulator not set.  
4. Fuel pressure incorrect.  
2. Clean, re-gap or replace plug(s).  
3. Set fuel regulator.  
4. Confirm fuel pressure is at 11-14”  
water column (0.4-0.5 psi) for LP,  
and 5-7” water column (0.18-0.25  
psi) for natural gas.  
The AUTO/OFF/MANUAL switch 1. Defective switch  
1. *  
2. *  
is set to OFF, but the engine  
2. AUTO/OFF/MANUAL switch  
continues to run.  
wired incorrectly  
3. Defective control board  
3. *  
There is no AC output from  
the generator.  
1. Main line circuit breaker open  
2. Generator internal failure  
1. Reset circuit breaker  
to ON (or closed).  
2. *  
There is no transfer to  
standby after utility  
source failure.  
1. Defective transfer switch coil  
2. Defective transfer relay  
3. Transfer relay circuit open  
4. Defective control logic board  
1. *  
2. *  
3. *  
4. *  
*Contact the nearest Authorized Dealer for assistance.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 7 — Mounting Dimensions  
Air-cooled 15 kW Generators  
Drawing No. 0F5927  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 — Electrical Data  
Air-cooled 15 kW Generators  
Wiring Diagram – Drawing No. 0F5643-B Part 1  
DIAGRAM KEY  
BA - BRUSH ASSEMBLY  
ENGINE WIRING  
BCR - BATTERY CHARGE RELAY  
C1 - 8 POSITION CONNECTOR  
C2 - 12 POSITION CONNECTOR  
C3 - 4 POSITION CONNECTOR  
C4 - 6 POSITION CONNECTIR  
CB1 - MAIN OUTPUT BREAKER  
CB2 - CIRCUIT BREAKER, ALTERNATOR EXCITATION  
D - DIODE  
3
1
BATTERY  
CHARGER  
2
1
DSW - PCB MOUNTED DIP SWITCH  
FS - FUEL SOLENOID  
0
14  
13A  
F1 - FUSE 5A BATTERY CHARGER  
F2 - FUSE 15 AMP SYSTEM  
F3, F4 - FUSE 5A SENSING  
225B  
224B  
GRD - CONTROL PANEL GROUND  
GTS - TRANSFER SWITCH CONTACTOR  
FS  
13A  
0
13A  
0
HTO - HIGH OIL TEMPERATURE SWITCH  
IC - INLINE CONNECTOR  
IM1 - IGNITION MODULE, CYLINDER #1  
14  
224B  
225B  
IM2 - IGNITION MODULE, CYLINDER #2  
LOP - LOW OIL PRESSURE SWITCH  
SC - STARTER CONTACTOR  
0
SCR - STARTER CONTACTOR RELAY  
SP1, SP2 - SPARK PLUGS  
14  
0
0
SW1 - AUTO / OFF / MANUAL SWITCH  
SW2 - SET EXERCISE SWITCH  
SW3 - DOOR ALARM SWITCH  
SM - STARTER MOTOR  
14  
A2  
0
TB - INSULATED TERMINAL BLOCK  
TR - RELAY, TRANSFER  
TS - TERMINAL STRIP  
TX - TRANSFORMER, 16 Vac 56 VA & 16 Vac 1 VA (DUAL SEC.)  
VR1, VR2 - VARISTORS  
XA1, XB1, XC1 - LIMIT SWITCHES  
14  
14  
IC  
SW3  
SP1  
D
6
0
0
IM1  
18  
18  
85  
86  
4
3
14  
14  
A2  
0
SP2  
D
2
1
13  
13  
0
16  
0
0
14  
13  
IC  
IC  
13  
85  
C1  
IM2  
86  
85  
SCR  
15  
15  
16  
A
B
0
0
85  
56  
0
A2  
86  
HTO  
0
14  
56  
85  
86  
351  
351  
86  
229  
86  
1
2
3
4
5
56  
14  
4
86  
23  
4
LOP  
0
J1  
23  
194  
56  
CONTROL  
PRINTED CIRCUIT BOARD  
14  
66A  
239  
15A  
229  
66A  
239  
15A  
RED  
BLACK  
DSW  
ON  
15  
0
15  
0
13  
225  
224  
225  
224  
1 - 20 Vac Sense Transformer  
2 - Remote Not Auto  
3 - 50 Hz Operation  
4 - SPARE  
SM  
16  
-
+
12V  
BATTERY  
SC  
CUSTOMER SUPPLIED  
L.E.D - ALARM INDICATORS  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 — Electrical Data  
Air-cooled 15 kW Generators  
Wiring Diagram – Drawing No. 0F5643-B Part 2  
CONTROL PANEL BOX  
225  
224A  
224  
225A  
224A  
225A  
10  
1
9
7
6
5
CLOSEST TO BEARING  
TX  
BCR  
BA  
CB2  
162  
1
3
4
0
4
N1  
N2  
7
13A  
0
STATOR  
66  
A
77  
2
224B  
225B  
224B  
225B  
2
14  
0
4
10  
9
11  
66  
11  
6
14  
0
55  
2
6
8
22  
4
66  
66A  
11  
6
5
11  
22  
11  
22  
4
22  
4
77  
77 66  
0
22  
44  
0
6
0
6
3
2
33  
225  
0
0
13A  
162  
162  
0
1
224  
N1  
N2  
VOLTAGE  
REGULATOR  
0
66A  
55  
C2  
0
66A  
0
0
66A  
4
N2  
N1  
55  
0
0
0
0
0
0
14  
0
GRD  
13  
0
15  
15  
15  
15  
0
0
0
0
0
0
0
0
0
A2  
22  
33  
11  
44  
225  
CB1  
224  
N2  
N1  
351  
4
AUTO  
351  
0
0
0
N2  
239  
0
N1  
15  
13A  
13  
14  
15  
15  
15  
A2  
SW1  
MANUAL  
15A  
23  
13  
1a  
66A  
194  
1
239  
F1  
F2  
1b  
SW2  
15  
229  
66A  
239  
15A  
15  
15A  
15  
15B  
NEU  
E1  
15  
0
GRD  
0
E2  
225  
224  
23  
0
GRD  
194  
4
3
2
1
N2  
N1  
N2  
N1  
194  
23  
194  
23  
194  
23  
C4  
6
15A  
0
15A  
0
5
4
3
15B  
A2  
15B  
A2  
2
1
14  
14  
229  
229  
C3  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 — Electrical Data  
Air-cooled 15 kW Generators  
Wiring Diagram – Drawing No. 0F5643-B Part 3  
TRANSFER SWITCH  
N2A  
N1A  
126  
15A  
15A  
15A  
147  
COIL  
1
A
XA1  
GTS  
N1A  
N2A  
126  
N2A  
B
COIL  
2
E1 E2  
E2  
205  
126  
15A  
15A  
147  
N1A  
N1A  
126 205  
TR  
1
194  
23  
N1A  
N2A  
N1A  
N2A  
205  
E2  
23  
194  
N2A  
N2A  
N1A  
N1A  
15A  
15A  
147  
E1 E2  
RELAY  
BOARD  
F3 F4  
14  
147  
15B  
0
RY1+  
RY3+  
COM-  
RY4-  
RY5-  
NEUTRAL  
N1  
N2  
229  
194  
TS  
A2  
15A  
COM+  
GRD  
REMOTE  
SIGNALS  
N1  
N2  
194  
RELAY KEY  
NEU  
E1  
RY1 - ENGINE RUN  
RY2 - SWITCH IN EMERGENCY  
RY3 - SWITCH IN AUTO  
RY4 - COMMON ALARM  
RY6 - DOOR OPEN  
0
E2  
GRD  
15B  
GRD  
A2  
N2  
N1  
14  
229  
194  
23  
15A  
0
15B  
A2  
14  
229  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 — Electrical Data  
Air-cooled 15 kW Generators  
Electrical Schematic – Drawing No. 0F5844-B  
11  
22  
11  
22  
TX  
225A  
56VA  
N2  
3
225A  
224A  
2
1
224A  
225  
BATTERY  
CHARGER  
225B  
F1  
13A  
13  
224B  
1VA  
224  
13A  
2
F2  
N1  
1
7
7
9
9
BCR  
1
3
4
11 22  
0
13A  
13 15  
77  
C2-1  
0
77  
14  
BATTERY CHARGE  
WINDING  
66  
66  
15  
0
C2-2  
0
HTO  
13  
55  
LOP  
11  
22  
ENGINE RUN  
WINDING  
(STATOR)  
BA  
FIELD  
SW2  
C1-4  
0
14  
85  
C1-3  
0
351  
C2-3  
4
0
ELECTRONIC  
VOLTAGE  
REGULATOR  
C2-9  
4
4
66A  
0
23  
6
86  
194  
162  
C1-6  
4
6
CB2  
0
225  
14  
224  
C2-7  
C2-8  
66A  
2
DPE WINDING  
(STATOR)  
229  
DIAGRAM KEY  
85  
229  
BA - BRUSH ASSEMBLY  
351  
BCR - BATTERY CHARGE RELAY  
1
3
4
5
C1 - 8 POSITION CONNECTOR  
C2 - 12 POSITION CONNECTOR  
J2  
23  
C3 - 4 POSITION CONNECTOR  
C4 - 6 POSITION CONNECTIR  
CB1 - MAIN OUTPUT BREAKER  
1
2
4
66A  
J1  
194  
86  
3
5
7
23  
194  
CB2 - CIRCUIT BREAKER, ALTERNATOR EXCITATION  
D - DIODE  
FS - FUEL SOLENOID  
F1 - FUSE 5A BATTERY CHARGER  
F2 - FUSE 15 AMP SYSTEM  
56  
18  
14  
66A  
239  
15A  
F3, F4 - FUSE 5A SENSING  
GTS - TRANSFER SWITCH CONTACTOR  
HTO - HIGH OIL TEMPERATURE SWITCH  
IM1 - IGNITION MODULE, CYLINDER #1  
CONTROL  
PRINTED CIRCUIT  
BOARD  
9
10  
IM2 - IGNITION MODULE, CYLINDER #2  
LOP - LOW OIL PRESSURE SWITCH  
11  
12  
13  
14  
15  
16  
17  
15  
NB - NEUTRAL BLOCK  
SC - STARTER CONTACTOR  
0
SCR - STARTER CONTACTOR RELAY  
SP1, SP2 - SPARK PLUGS  
225  
224  
SW1 - AUTO / OFF / MANUAL SWITCH  
SW2 - SET EXERCISE SWITCH  
SW3 - DOOR ALARM SWITCH  
SM - STARTER MOTOR  
TR - RELAY, TRANSFER  
TS - TERMINAL STRIP  
TX - TRANSFORMER, 16 Vac 56 VA & 16 Vac 1 VA (DUAL SEC.)  
VR1, VR2 - VARISTORS  
XA1, XB1, XC1 - LIMIT SWITCHES  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 8 — Electrical Data  
Air-cooled 15 kW Generators  
Electrical Schematic – Drawing No. 0F5844-B  
11  
22  
C2-6  
TR  
TS  
C2-5  
C4-3  
F3  
1
N1  
N1A  
126  
E1  
7
126  
147  
15  
N2  
N2A  
B
A
N1A  
F4  
B
AUTO  
MAN  
E1  
15B  
C4-2  
A
NO  
NC  
NC  
NO  
NC  
NO  
N1  
15  
NB  
XB1  
XA1  
XC1  
SW1  
E2  
194  
COM  
COM  
COM  
23 11 22  
15A  
15  
239 15B  
33  
GTS  
E1  
A
15  
VR2  
B
147  
N2A  
POWER  
WINDING  
(STATOR)  
COIL  
2
COIL  
1
15  
0
44  
13  
CB1  
11  
A
B
9
6
11  
E2  
E2  
205  
15  
TR  
N2A  
194  
0
23  
15  
15  
23  
147  
147  
194  
RELAY  
BOARD  
13 15A  
239  
15B  
C3-2  
C3-5  
14  
RY1+  
RY2+  
RY3+  
COM-  
RY4-  
RY5-  
RY6-  
COM+  
147  
15B  
0
0
0
RELAY KEY  
RY1 - ENGINE RUN  
C3-4  
0
RY2 - SWITCH IN EMERGENCY  
RY3 - SWITCH IN AUTO  
RY4 - COMMON ALARM  
RY6 - DOOR OPEN  
229  
229  
C3-1  
A2  
C3-6  
15A  
15A  
0
14  
REMOTE  
SIGNALS  
C3-3  
A2  
0
NO  
COM  
SW3  
239  
15A  
56  
NC  
C1-5  
13  
18  
18  
14  
IM1  
D
D
14  
SP1  
C1-2  
56  
15  
0
13  
RED  
IM2  
SP2  
SC  
15  
0
15  
SCR  
14  
16  
16  
C1-1  
BATTERY  
12V  
0
SC  
0
FS  
0
SM  
0
0
BLACK  
CUSTOMER  
SUPPLIED  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 — Exploded Views and Parts Lists  
Air-cooled 15 kW Generators  
Enclosure – Drawing No. 0F5845  
71  
40  
68  
69  
41  
30  
17  
78  
72  
1
79  
72  
5
73  
52  
80  
29  
12  
49  
53  
19  
28  
55  
75  
65  
47  
54  
0
35  
46  
11  
49  
51  
25  
14  
8
74  
57  
9
35  
27  
56  
50  
22  
49  
49  
5
1
67  
44  
35  
26  
3
51  
39  
37  
42  
43  
36  
51  
21  
49  
43  
34  
2
32  
10  
18  
52  
20  
4
15  
44  
71  
69  
35  
63  
81  
25  
68  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 — Exploded Views and Parts Lists  
Air-cooled 15 kW Generators  
Enclosure – Drawing No. 0F5845  
ITEM PART NO. QTY. DESCRIPTION  
ITEM PART NO. QTY. DESCRIPTION  
1
2
0C6140  
0C6735  
0F0063  
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
2
1
1
1
1
1
1
1
1
ASSEMBLY, ENCLOSURE BASE  
SUPPORT, ROOF FOLDING  
ENCLOSURE, FRONT  
41  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
62  
63  
64  
65  
66  
67  
68  
69  
70  
71  
72  
73  
74  
75  
76  
77  
78  
79  
80  
81  
82  
0F0165  
0D3037A  
0A2115  
022145  
042907  
0F0710  
047411  
043116  
0D3700  
0D4662  
090388  
092120  
0F5633  
0D3167  
0A3328  
055414  
092079  
0A1658  
042907  
0E9692  
0E1330A  
0E4321  
022129  
074908  
0D2346  
023484F  
0C3906  
0A7836  
0A8475  
0912970069  
0912970070  
055450  
0E5968  
0D3701  
0D3472  
0E2874  
043107  
0F5681  
0F0164A  
0F0165A  
045771  
0D3031  
1
1
4
8
4
HINGE TYPE B WITH STUDS, PIN  
LATCH, QUARTER TURN NON-LOCKING  
WASHER NYLON .250"  
3
4
0C7062  
0F5629  
ENCLOSURE, EXHAUST SIDE  
ENCLOSURE, SIDE & BACK  
ENCLOSURE, ROOF  
WASHER FLAT 5/16  
SCREW HHC M8-1.25 X 16 G8.8  
5
6
0E9873  
0C7065  
0C8101A  
0C8101B  
0C8283  
0C8284A  
0C8284B  
0C8284C  
0C8285  
0C8899A  
0F5630  
14 RIVET POP 0.125 X 0.337  
7
PANEL, ALTERNATOR DIVIDER  
PANEL, MUFFLER BOX SIDE  
COVER, MUFFLER BOX  
6
4
SCREW HHC M6-1.0 X 16 G8.8  
SCREW HHC M6-1.0 X 12 G8.8  
8
9
26 NUT, LOCKING FLANGE M6-1.0  
11 SCREW HHTT M8-1.2 X 20 BP  
36 SCREW TAPTITE M6-1.0 X 12 BP  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
GASKET, DOOR SEAL  
FOAM, BACK ENCLOSURE  
FOAM, ROOF ENCLOSURE  
FOAM, FRONT ENCLOSURE  
BRACKET, BATTERY SUPPORT  
PAD, 24"X48" WITH MOUNTING HOLES  
PANEL, ENGINE DIVIDER  
2
1
1
1
1
1
2
2
1
1
1
NUT LOCK TRIC M6 X 1.0 Y/ZNC  
ASSEMBLY, TRANSFER SWITCH  
GASKET, BATTERY SUPPORT BRACKET  
PLUG, PLASTIC 0.593  
LUG SLDLSS #2-#8X17/64 CU  
SCREW TAPTITE M6-1.0X25 BP  
L/WASH SPECIAL ¼  
0E4244  
0D1606  
0D1839  
0D1840  
0D2425  
0D2588  
0D2676  
0D2677  
0D2979B  
0D2979C  
0D2979D  
0E4245  
0E4245A  
0E4245B  
0D3057D  
0D3059A  
0D3059B  
BAFFLE, INTAKE  
HOUSING, FAN  
BRACKET, TOP SUPPORT  
SCREW HHC M8-1.25 X 16mm  
BRACKET, REGULATOR MOUNTING  
GROMMET, 38.1 CROSS SLIT WITH HOLE  
PANEL, EXHAUST ALIGNMENT  
BRACKET, BOTTOM SUPPORT  
DUCT, BASE AIR  
GASKET, FRONT DIVIDER  
COVER, FRONT EXHAUST ENCLOSURE  
COVER, BACK EXHAUST ENCLOSURE  
CLOTH, HARDWARE 266.7mm x 146mm  
CLOTH, HARDWARE 543mm x 146mm  
CLOTH, HARDWARE 266.7mm x 387.4mm  
FOAM, FRONT INTAKE BAFFLE  
FOAM, TOP INTAKE BAFFLE  
FOAM, BACK INTAKE BAFFLE  
FOAM, BACK ENCL. STRIP  
FOAM, EXHAUST SIDE ENCLOSURE END  
FOAM, EXHAUST SIDE ENCLOSURE  
FRONT  
10 WASHER LOCK 5/16  
8
1
1
2
2
2
1
2
1
SCREW TAPTITE M5-0.8 X 10 BP  
HARNESS, ENGINE  
BUSHING, SNAP SB-1000-12  
SELF-ALIGN SCREW M6 HH  
RIVET,1/8" X 0.126" - 0.375" LSH POP  
L/WASH SPECIAL #10  
ASSEMBLY, ROOF / DOOR GROUND WIRE  
ASSEMBLY, ROOF / DOOR GROUND WIRE  
PLUG PLASTIC 1.375  
11 GASKET, EXTRUDED TRIM  
1
1
1
4
1
1
1
4
1
PLATE, "HOT"  
GROMMET 2.75 X 1/16  
34  
35  
36  
0D3059C  
0D7176  
0D3059D  
1
24 WASHER, SELF LOCKING  
FOAM, EXHAUST FAN HOUSING  
SCREW HHTR 1/4-20 X 3/4  
SCREW HHC M8-1.25 X 25  
HARNESS  
1
1
FOAM, FRONT EXHAUST ENCLOSURE  
COVER  
37  
0D3059E  
FOAM, BACK EXHAUST ENCLOSURE  
COVER  
DOOR, PAWL  
HINGE TYPE A WITH STUDS, SOCKET  
HINGE TYPE B WITH STUDS, SOCKET  
NUT HEX M8-1.25  
38  
39  
40  
0C7781A  
0D3037  
0F0164  
2
1
1
LATCH, QUARTER TURN LOCKING  
HINGE TYPE A WITH STUDS, PIN  
FUEL LINE, 3/4"OUTDOOR (NOT SHOWN)  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 — Exploded Views and Parts Lists  
Air-cooled 15 kW Generators  
Control Panel – Drawing No. 0F5846  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 — Exploded Views and Parts Lists  
Air-cooled 15 kW Generators  
Control Panel – Drawing No. 0F5846  
ITEM  
PART NO.  
QTY.  
DESCRIPTION  
1
2
0E7886G  
0A1801  
083049  
0C2174  
075210A  
0D3062  
0D8615  
032300  
022676  
0E4494  
0E7890  
023484E  
075476  
0F4793  
0E6480  
023897  
0C1085  
0D8443  
054502  
0F5747  
075235  
0D5240  
0D9784  
0D8502  
031879  
0F5679  
074908  
049813  
082025  
0C3910  
022507  
099727  
046689  
063617  
075475  
043180  
0D8439  
092036  
045770  
0E7866  
0D3700  
0912970069  
0E2874  
0A1658  
022473  
038750  
022097  
027770  
027771  
043182  
084464  
042632  
1
1
1
1
2
4
1
2
1
1
1
1
4
2
6
2
4
1
1
1
4
1
6
1
6
1
4
1
6
1
2
1
1
1
2
2
1
8
2
1
8
1
1
2
3
1
3
2
2
2
1
1
CIRCUIT BREAKER 70A X 2P 240V (15KW)  
ASSEMBLY, BATTERY CHARGER ENGINE  
ASSEMBLY, POTTED REGULATOR  
RELAY, 12V 25A SPST  
3
4
5
BLOCK 1 POSITION  
6
HEX STAND-OFF #6-32 x 3/8"  
ASSEMBLY, HOME STANDBY CONTROLLER  
HOLDER, FUSE  
7
8
9
FUSE, 15AMP X AGC15  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
SWITCH, ROCKER DPDT ON-OFF-ON  
CIRCUIT BREAKER MOUNTING BRACKET  
SNAP BUSHING  
SCREW PPHM M4-0.7 x 16mm  
SCREW PPHM M3-0.5 x 10mm  
NUT HEX LOCK M4-0.7 NYLON INSERT  
WASHER FLAT #10  
SCREW PPHM M3-0.5 X 8mm  
DECAL, CONTROL PANEL (NOT SHOWN)  
CIRCUIT BREAKER 3 X 1 ETA 46-500-P  
CONTROL, PANEL BOTTOM  
SCREW HHC M5-0.8 x 30mm  
SWITCH, SPST (ON)-ON N/O  
NUT HEX LOCK M3-0.5 NYLON INSERT  
NEUTRAL CONNECTOR  
WASHER FLAT #4  
HARNESS, CONTROL PANEL (NOT SHOWN)  
SCREW TAPTITE, M5-0.8 x 10 BP  
NUT HEX M6-1.0  
NUT HEX LOCK M5-0.8 NYLON INSERT  
TRANSFORMER  
SCREW HHC 1/4"-20 x 1/2"  
FUSE 5A X AGC5  
BLOCK TERMINAL STRIP 20A 4 X 6 X 1100V  
RELAY PANEL 12VDC DPDT 10A 240VAC  
SCREW PPHM M4-0.7 x 10mm  
WASHER FLAT M4  
COVER, CONTROL PANEL COMPONENT  
SCREW PPHMS/LW #6-32 x 1/4"  
SCREW HHC M5-0.8 x10mm  
COVER, CONTROL PANEL  
NUT FLANGE M6-1.0 NYLOK  
ASSEMBLY, ROOF/DOOR GROUND WIRE  
SCREW HHTR 1/4"-20 X 3/4"  
WASHER LOCK SPECIAL 1/4"  
WASHER FLAT 1/4"-M6  
SCREW HHC M6-1.0 x 30mm  
WASHER LOCK M6-1/4"  
SCREW RHM #4-40 X 5/8"  
NUT HEX #4-40  
WASHER LOCK M3  
LIMIT SWITCH OPERATION  
GROMMET 1/2 X 1/16 X 3/8  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 — Exploded Views and Parts Lists  
Air-cooled 15 kW Generators  
GT-990 Engine – Drawing No. 0E8774-Q Part 1  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 — Exploded Views and Parts Lists  
Air-cooled 15 kW Generators  
GT-990 Engine – Drawing No. 0E8774-Q Part 1  
ITEM PART NO. QTY. DESCRIPTION  
ITEM PART NO. QTY. DESCRIPTION  
1
0C5729  
1
ASSEMBLY, CRANKCASE HOUSING WITH  
SLEEVE  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
62  
63  
64  
65  
66  
67  
68  
69  
70  
71  
72  
73  
0C2992  
0C3971C  
0C5305  
0C3027  
0E9842  
0C5731  
0C3006  
080318  
093064  
0G1839  
0D2723B  
0C2979  
086515  
0D2274  
0D3867  
078672  
0C5371  
072694  
0D3998  
0C3027  
0D5313  
0D6024  
0C2976  
086516  
0C2229  
083897  
0D8067B  
0D9853D  
0C2978  
043790  
0D4010  
0D4011  
0D4012  
0D4013  
0D8675A  
0D8675B  
0D4015  
0D4016  
1
1
1
1
1
1
9
8
1
2
1
2
8
4
4
2
4
4
4
2
4
2
12  
2
2
4
1
4
2
1
1
1
1
1
1
1
1
1
BUSHING, GOVERNOR LOWER  
ASSEMBLY, DIPSTICK WITH HANDLE  
TUBE, DIPSTICK  
2
3
0E9843  
090388  
1
3
1
1
1
1
4
1
4
2
2
2
1
1
2
1
1
1
1
1
1
SEAL, 38 I.D. CRANKSHAFT  
SCREW, TAPTITE M6-1.0 X 12 YC  
ASSEMBLY, BREATHER  
O-RING, OIL CLR 3/8 X 1/2  
SEAL, 42 I.D. CRANKSHAFT  
ASSY, HS COVER W/SLV  
SCREW, HHFC M10-1.5 X 55  
SCREW HHFC M6-1.0 X 25  
ASSEMBLY, OIL FILL CAP  
LIFT HOOK, GT990/760  
ROCKER, COVER WITH OIL FILL  
GASKET, VALVE COVER  
KEEPER, VALVE SPRING  
RETAINER, VALVE SPRING  
SPRING, VALVE  
4
0C5372  
0C3005  
0E3372B  
0D8067A  
071983  
5
GASKET, BREATHER COVER  
SEPARATOR, OIL BREATHER  
ASSEMBLY, HEAD #1 G&S  
RETAINER, PISTON PIN 20  
ROCKER, COVER NO OIL FILL  
STUD M8-1.25/10MM X 30 G5 ZINC  
PISTON, HC  
6
7
8
9
0C2981C  
045761A  
0E2985  
021533  
10  
11  
12  
13  
14  
15  
16A  
16B  
17  
18  
19  
20  
21  
SET, PISTON RING 90MM  
PIN PISTON  
0E1466  
0D4041  
0C2983  
0C2985A  
0C2985B  
0D4042  
0A7811  
0C2977  
0C5943  
0G0140E  
ASSEMBLY, CAMSHAFT & GEAR  
SHAFT, GOVERNOR  
SEAL, VALVE STEM D7  
WASHER, VALVE SPRING  
STUD, ROCKER ARM PIVOT  
NUT HEX M8-1.0 G8 YEL CHR  
O-RING, 3/8” X 1/2”  
ROLLER BEARING, GOVERNOR PLATE  
ROLLER BEARING, GOVERNOR  
ASSEMBLY,GOVERNOR GEAR  
SPOOL, GOVERNOR MACHINED  
GASKET, CRANK CASE  
ROCKER ARM  
SEAL, OIL PASSAGE  
ASSEMBLY, CRANKSHAFT HORIZONTAL  
DIRECT DRIVE  
PLATE, PUSH ROD GUIDE  
SCREW HHFC M8-1.25 X 65  
VALVE, EXHAUST  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
0E3223  
0D2157  
0E6098  
0G1536  
0E8152  
0C3011  
0C3009  
0C3010  
093873  
0F5458  
0C5998  
0D1667  
0C2991  
0C2988  
2
2
1
1
1
2
2
2
2
1
1
1
2
1
ASSEMBLY, CONNECTING ROD  
SCREW SHC M6-1.0 X 50 G8.8  
SCREEN, OIL PICKUP  
VALVE, INTAKE  
TAPPET, SOLID  
ASSEMBLY, HEAD #2 G&S  
PUSHROD, 147  
GASKET, HEAD  
ASSEMBLY, OIL PUMP  
O-RING .49 ID X .07 THICK  
COVER, OIL RELIEF  
SPRING, OIL RELIEF  
BARBED ELBOW 90 3/8NPT X 3/8  
KIT GASKET  
KIT PISTON & RINGS  
BALL, 1/2D OIL RELIEF  
WASHER, LOCK RIB M6  
SCREW, PLASTITE HI-LOW #10  
CLAMP, OIL TUBE  
KIT BREATHER ASSEMBLY  
KIT GOVERNOR ASSEMBLY  
KIT HEAD ASSEMBLY CYLINDER 1  
KIT HEAD ASSEMBLY CYLINDER 2  
KIT OIL RELIEF  
ARM, GOVERNOR  
E-RING, GOVERNOR ARM  
THRUST WASHER, GOVERNOR  
KIT GEAR COVER  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 — Exploded Views and Parts Lists  
Air-cooled 15 kW Generators  
GT-990 Engine – Drawing No. 0E8774-Q Part 2  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 — Exploded Views and Parts Lists  
Air-cooled 15 kW Generators  
GT-990 Engine – Drawing No. 0E8774-Q Part 2  
ITEM PART NO. QTY. DESCRIPTION  
ITEM PART NO. QTY. DESCRIPTION  
74  
75  
76  
77  
78  
0C5136A  
0C3024  
0C3040  
0C8127  
0D8564A  
0D8564B  
0D2595  
0D4417  
0C3025  
0D3083  
0C7292  
070185B  
075281  
0F2094  
2
1
1
1
1
1
4
4
1
1
1
1
1
2
KNOB, AIR CLEANER  
COVER, AIRBOX NG/LP  
PRE-CLEANER,  
110  
111  
112  
0C3022A  
0D1131  
045756  
1
1
HOUSING, BLOWER NG COOLER  
GUARD, FAN  
25  
SCREW TAPTITE M6-1X10 YELLOW  
CHROME  
ELEMENT, AIR CLEANER  
ASSEMBLY, MIXER/AIRBOX 990  
ASSEMBLY, MIXER/AIRBOX 760  
SCREW SHOULDER (8MM) M6-1.0 X 18  
WASHER,RUBBER 1/4" X 1/8" THICK  
SWITCH, OIL PRESS  
113  
114  
115  
116  
117  
118  
119  
120  
121  
122  
123  
124  
125  
126  
127  
128  
129  
1 30  
1 31  
1 32  
1 33  
1 34  
1 35  
1 36  
1 37  
1 38  
1 39  
0C9763  
0C3036A  
022145  
022129  
0C3018  
0C3019  
0D1142A  
0D1143  
0E6043  
0F1177  
0C3052  
022097  
092079  
0E4271  
0D4529  
022129  
061906  
082774  
0E5343  
0C8468  
0C3048  
0D3754  
0D3742  
0C8482  
0E0486  
0D3743  
0D3705  
4
1
1
1
1
1
1
1
2
1
1
4
4
1
2
2
2
1
1
1
1
1
1
1
1
1
1
NUT, GROMMET 1/4 PLUG  
HOSE, BREATHER  
79  
80  
WASHER FLAT 5/16-M8 ZINC  
WASHER LOCK M8-5/16  
81  
82  
WRAPPER, UPPER CYLINDER 1  
WRAPPER, LOWER CYLINDER 1  
WRAPPER, LOWER CYLINDER 2  
WRAPPER, UPPER CYLINDER 2  
SCREW TAPTITE M5-0.8 X 8 ZP  
ASSEMBLY, GROUND WIRE  
ASSY, IGNITION COIL GV-990 CYLINDER 2  
WASHER LOCK M6-1/4  
ASSEMBLY, OIL DRAIN HOSE  
NIPPLE, 3/4"-16 UNF  
OIL FILTER  
83  
84  
85  
86  
SWITCH, THERMAL 284F  
SCREW, M3-0.5 X 6 SEMS  
87  
88  
035461  
0F6301  
0G0286  
0C3026  
0C9764  
0C3043  
0C7694  
0C7693  
0C3041A  
070008  
070006  
040976  
0C3016A  
0E4997  
0C3725B  
0C3031  
0C3032  
0A5992  
051754  
0C3033  
0C3034  
0C8549A  
2
4
2
1
4
2
1
1
2
4
4
4
1
1
1
1
1
2
2
1
1
1
BARBED STR 1/4NPT X 3/8  
CLAMP, HOSE OETIKER 16.5mm  
HOSE, 3/8" I.D. X 6" LG SAE J30R9  
COOLER, OIL  
89  
90  
SCREW TAPTITE M6-1.0 X 25 BP  
STARTER  
SPARKPLUG  
91  
92  
PLASTITE,1/4-15 X 3/4  
WASHER LOCK M8-5/16  
SCREW HHC M8-1.25 X 85 G8.8  
KEY, WOODRFF 4 X 19D  
93  
94  
GASKET, MANIFOLD / PORT  
MANIFOLD CYLINDER 2  
MANIFOLD CYLINDER 1  
SLEEVE, RUBBER  
95  
96  
NUT HEX LOCK M10-1.50  
SPRING, ANTI-LASH  
97  
98  
WASHER FLAT M8 SS  
ROD, GOVERNOR CONTROL  
ASSEMBLY, GOVERNOR LEVER  
SPRING, GOVERNOR  
WASHER LOCK M8 SSTL  
SCREW SHC M8-1.25 X 20 G12.9  
PLATE, BACKING WITH OIL COOLER  
GROUND WIRE CONNECTOR  
FLYWHEEL ASSEMBLY  
FAN, NYLON  
99  
100  
101  
102  
103  
104  
105  
106  
107  
108  
109  
ASSEMBLY, GOVERNOR ADJUSTER  
SCREW SHC M10-1.5 X 75 G10.9  
SPRING, GOVERNOR IDLE  
ASSEMBLY, GOVERNOR ADJUSTER  
BRACKET  
PLATE, FAN  
WASHER SHAKEPROOF INT M8 SS  
SCREW HHC M8-1.25 X 12 G8.8  
WASHER, 25mm I.D.  
140  
142  
143  
144  
145  
0C2993  
045771  
0D6147  
0E8152  
0E7743  
1
1
7
1
1
SEAL, GOVERNOR SHAFT  
NUT HEX M8-1.25 G8  
SCREW HHFC M6-1.0 X 10mm  
O-RING 0.49” I.D. X 0.07” THICK  
ASSY, IGNITION COIL 270mm CYLINDER 1  
NUT,HEX M24  
SNORKEL, AIR INTAKE  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 — Exploded Views and Parts Lists  
Air-cooled 15 kW Generators  
15 kW Generator – Drawing No. 0D3417-L  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 — Exploded Views and Parts Lists  
Air-cooled 15 kW Generators  
15 kW Generator – Drawing No. 0D3417-L  
ITEM  
PART NO.  
QTY.  
DESCRIPTION  
1
2
0C6934  
0C7930  
0D2359  
0C7944  
0D2356  
0C6043  
0D2336  
0D6634  
0D3220  
0C8101  
056482  
0C3168  
0D1838  
0D1846  
0C7038  
0D1609  
0D2559  
0C7038A  
0C7758  
0388050AD0  
0C2417A  
082121C  
066386  
029451  
049451  
022237  
022511  
022131  
051731  
022145  
049820  
045756  
022129  
022259  
059637  
0D4662  
0F7065  
048031M  
0F0462  
0C2824  
025145  
0C4138  
040173  
074995  
066849  
1
1
ADAPTOR, ENGINE  
STATOR 12KW  
STATOR 13KW / 15KW  
ROTOR 12KW  
ROTOR 13KW / 15KW  
3
1
4
5
1
CARRIER, REAR BEARING  
FAN, 12” CURVED BLADE  
MUFFLER  
1
6
1
7
1
TAIL PIPE, MUFFLER  
PANEL, MUFFLER BASE  
BEARING 1.1811-2.8346  
8
1
9
1
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
3
5/16 SPECIAL LOCK WASHER  
BOLT, HHCS 3/8”-24 x 15.50”  
BOLT, HHCS M8-1.25 x 345mm  
BRACKET, ALTERNATOR MOUNTING  
DUCT, ALTERNATOR AIR  
GASKET, ALTERNATOR AIR DUCT  
BRACKET, ENGINE MOUNTING  
RUBBER MOUNT  
1
4
1
1
1
1
4
1
CABLE, #6 48” BLACK BATTERY  
EARTH STRAP 3/8X 3/8  
1
1
CLIP-J, VYNL COAT 0.625” ID  
ASSEMBLY BRUSH HOLDER  
TAPE ELEC UL FOAM 1/8 X 1/2  
WASHER FLAT .406ID X 1.62OD  
WASHER LOCK 3/8  
1
2.6 FT  
1
5
4
SCREW HHC 3/8-16 X 1-1/4 G5  
WASHER FLAT 3/8 ZINC  
4
4
12  
SCREW HHC M8-1.25 X 50 G8.8  
WASHER FLAT 5/16 ZINC  
NUT LOCK HEX M8-1.25 NYL INSERT  
SCREW TAPTITE M6-1.0X10 BP  
WASHER LOCK M8-5/16  
4
2
10  
8
NUT HEX 5/16-18 STEEL  
SCREW TAPTITE 3/8-16 X 3/4 BP  
SCREW 5/16-18X3/4” HH THD ROLL  
HOSE RES 1/2 LP GAS  
2
4
3 FT  
4
HOSE CLAMP 3/4” I.D.  
4
NUT HEX W/TOOTH WSHR M8-1.25  
SCREW TAP-R #10-32 x 9/16  
U-BOLT 5/16”-18 X 1.25” WITH SADDLE  
GASKET, EXHAUST PORT  
CLAMP HOSE #5.5 0.62”-0.62”  
HOSE 1\4 ID LPG 350PSI UL21  
SCREW HHTT M5-0.8 X 16  
1
1
2
2
1.44 FT  
2
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 — Exploded Views and Parts Lists  
Air-cooled 15 kW Generators  
Gas Regulator – Drawing No. 0D8720-H  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 — Exploded Views and Parts Lists  
Air-cooled 15 kW Generators  
Gas Regulator – Drawing No. 0D8720-H  
ITEM  
PART NO.  
QTY.  
DESCRIPTION  
1
2
0D5694  
0F5022  
0C4647  
0D4166  
0C6070  
0F4795  
0C5760J  
0C6606  
097934  
0C4645  
0C5761  
0C5968  
0C6066  
0C5759  
0C5764  
0C5764A  
070728  
0C6069  
0C5762  
045764  
0C6731  
0C6067  
0C4706  
0C6068  
0C4643A  
026073  
026073  
0A4032  
0D3308  
024310  
028414A  
0D5698A  
0D3973  
1
1
CASTING, TWIN REGULATOR HOUSING  
SOLENOID COIL, 12VDC  
GASKET , SOLENOID  
3
1
4
1
PLUNGER, LP REGULATOR ASSEMBLY  
SPRING-SOLENOID, PLUNGER  
SCREW PPHM SEMS M4-0.7 X 10  
JET, GN 410 ENGINE LP (7KW)  
BARBED STRAIGHT 1/2NPT x 1/2  
O-RING, CHECK VALVE  
5
1
8
4
9
1
10  
11  
12  
13  
14  
15  
16  
17  
2*  
2*  
2*  
2
ADJUSTER SCREW, TWIN REGULATOR  
LEVER, REGULATOR  
SUPPORT, INLET SEAL  
2
2
SEAL, INLET  
PIN, PIVOT ARM  
SPRING, REGULATOR  
2
2
2
SPRING, REGULATOR (7KW)  
SCREW, PFHMS M3-0.5 x 5  
GASKET, DIAPHRAGM  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
4
2
2
COVER, TWIN REGULATOR  
SCREW, TAPTITE M4X8 BP  
16  
2
RIVET, POP .118 X .125  
SUPPORT, DIAPHRAGM  
2
2
DIAPHRAGM, TWIN REGULATOR  
CAP, DIAPHRAGM SUPPORT  
INLET, TWIN REGULATOR 11.11 DIA.  
PLUG, STANDARD PIPE 1/8STEEL SQUARE HEAD  
PLUG, STANDARD PIPE 1/8STEEL SQUARE HEAD (7KW)  
PIN, LIMITED ADJUSTMENT  
2
2
1
2
28  
29  
30  
31  
32  
37  
2*  
4
WASHER, FLAT M3 X 10mm O.D.  
PLUG, STANDARD PIPE 1/2” STEEL SQUARE HEAD (7KW)  
BARBED STRAIGHT 1/8”NPT X 1/4”  
JET IDLE PRIMER PHILLIPS HD (V-TWIN ONLY)  
PLUG, EXPANSION 16mm  
1
1
1
1
* A QUANTITY OF 1 IS TO BE USED ON 7KW HOME STANDBY  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 — Exploded Views and Parts Lists  
Air-cooled 15 kW Generators  
Transfer Switch – Drawing No. 0F5633$-A  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 9 — Exploded Views and Parts Lists  
Air-cooled 15 kW Generators  
Transfer Switch – Drawing No. 0F5633$-A  
ITEM  
PART NO.  
QTY.  
DESCRIPTION  
1
2
0D9618  
0E3375  
0F1252  
022097  
074908  
045771  
057329  
027482  
022129  
073590A  
073591  
090388  
0A1495  
063617  
0C2454  
0A1661  
0C4449A  
0F5634  
0E6056  
0F0668  
0C2262  
095282  
027770  
064101  
0F5694  
063378  
028739  
0F5893  
067210A  
0A9457  
0A9517  
0E6190  
081221  
0E6193  
064526  
0E6155  
0F5748  
0E6033  
0E6303B  
0E6303  
0E6303A  
0F5770  
020757  
0D3062  
092036  
048850  
084464  
043182  
1
6
6
6
5
1
1
1
1
2
2
2
4
1
2
2
1
1
1
1
1
1
2
4
1
3
5
1
1
1
1
1
1
1
2
1
1
2
1
1
1
1
1
4
8
1
1
2
TR SW-HSB 200A 2P 250V  
LUG SLDLSS 250-#6 AL/CU  
SCREW BHSC 1/4-20 X 3/8  
WASHER LOCK M6-1/4  
3
4
5
SCREW HHTT M5-0.8 X 16 BP  
NUT HEX M8-1.25 G8 YEL CHR  
LUG SLDLSS 350-#6 X 13/32 AL/CU  
WASHER SHAKEPROOF EXT 5/16 STL  
WASHER LOCK M8-5/16  
FUSE 5A X BUSS  
6
7
8
9
10  
11*****  
12  
13  
FUSE HOLDER  
SCREW HHTT M6-1.0 X 12 ZINC  
SCREW HHTT M4-0.7 X 10 BP  
RELAY PNL 12VDC DPDT 10A@240VA  
SCREW TH-FRM M6-1 X 16 N WA Z/JS  
RIVET POP .156 X .675 AL  
ASSY-NTRL BL150-200A  
WELDMENT XFER SW BOX HSB  
COVER TRANSFER SWITCH BOX HSB  
DECAL TRANSFER SWITCH  
DECAL TERMINAL STRIP  
DECAL-LIVE CIRCUIT  
14*****  
15  
16  
17  
18  
19  
20****  
21  
22***  
23  
SCREW RHM #4-40 x 5/8  
NUT LOCK FL 3/8-16  
24  
25  
SUBPLT TRANSFER SWITCH HSB  
HOLDER CABLE TIE  
26*****  
27*****  
28  
TIE WRAP UL 3.9” X .10” NATL  
DECAL TRANSFER SWITCH DATA 200  
DECAL GROUND LUG  
29  
30  
DECAL NEUTRAL  
31  
DECAL MANUAL 5A FUSE  
DECAL TEST SEQUENCE 2P TS 3R  
DECAL-UL LIST HSB  
32 *  
33  
34  
35  
BRACKET ARM EXTENDER  
SCREW HWHS #6-25 X 3/8 ZNC  
ARM EXTENDER PIN  
36 **  
37  
HARN 100/200A 2P HS  
38 **  
39  
90 DEGREE DN SPADE CONNECTOR  
WIRE E1  
WIRE A  
40  
41  
WIRE B  
DECAL TERMINAL STRIP  
ALARM PCB  
42  
43  
44  
45  
HEX PCB SUPPORT, SCREW-IN  
#6-32 x 0.25” PPH W/ LOCK  
ASSY. TERM. BLOCK 20A 5 x 1100VAC  
LIMIT SW-SW OPERATION  
WASHER LOCK M3  
46  
47  
48  
* CENTER DECAL ON INSIDE OF THE COVER (ITEM #19)  
** SUPPLIED WITH TRANSFER SWITCH (ITEM #1).  
*** PLACE DECAL ON OUTSIDE OF COVER, LOWER RIGHT CORNER.  
**** NOT SHOWN ON THIS ASSEMBLY, CENTER DECAL ON FRONT OF COVER, 7” FROM TOP OF ENCLOSURE.  
***** SUPPLIED WITH HARNESS (P/N 0F5748)  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 10 – Warranty  
Air-cooled 15 kW Generators  
NOTE: This Emission Control Warranty Statement pertains to this product only IF the generator size is 15 kW or below.  
CALIFORNIA EMISSION CONTROL WARRANTY STATEMENT  
YOUR WARRANTY RIGHTS AND OBLIGATIONS  
The California Air Resources Board (CARB) and Generac Power Systems, Inc. (Generac) are pleased to explain the Emission  
Control System Warranty on your new engine.* In California, new utility, and lawn and garden equipment engines must be  
designed, built and equipped to meet the state’s stringent anti-smog standards. Generac will warrant the emission control  
system on your engine for the periods of time listed below provided there has been no abuse, neglect, unapproved modifica-  
tion or improper maintenance of your engine.  
Your emission control system may include parts such as the carburetor, ignition system and exhaust system. Generac will  
repair your engine at no cost to you for diagnosis, replacement parts and labor, should a warrantable condition occur.  
MANUFACTURER’S EMISSION CONTROL SYSTEM WARRANTY COVERAGE:  
Emissions control systems on 1995 and later model year engines are warranted for two years as hereinafter noted. If, dur-  
ing such warranty period, any emission-related component or system on your engine is found to be defective in materials or  
workmanship, repairs or replacement will be performed by a Generac Authorized Warranty Service Facility.  
PURCHASER’S/OWNER’S WARRANTY RESPONSIBILITIES:  
As the engine purchaser/owner, you are responsible for the completion of all required maintenance as listed in your factory  
supplied Owner’s Manual. For warranty purposes, Generac recommends that you retain all receipts covering maintenance  
on your engine. However, Generac cannot deny warranty solely due to the lack of receipts or for your failure to ensure the  
completion of all scheduled maintenance.  
As the engine purchaser/owner, you should, however, be aware that Generac may deny any and/or all warranty coverage or  
responsibility if your engine, or a part/component thereof, has failed due to abuse, neglect , improper maintenance or unap-  
proved modifications, or the use of counterfeit and/or “grey market” parts not made, supplied or approved by Generac.  
You are responsible for contacting a Generac Authorized Warranty Service Facility as soon as a problem occurs. The  
warranty repairs should be completed in a reasonable amount of time, not to exceed 30 days.  
Warranty service can be arranged by contacting either your selling dealer or a Generac Authorized Warranty Service Facility.  
To locate the Generac Authorized Warranty Service Facility nearest you, call our toll-free number:  
1-800-333-1322  
IMPORTANT NOTE: This warranty statement explains your rights and obligations under the Emission Control System  
Warranty (ECS Warranty), which is provided to you by Generac pursuant to California law. See also the “Generac Limited  
Warranties for Generac Power Systems, Inc.,” which is enclosed herewith on a separate sheet, also provided to you by  
Generac. The ECS Warranty applies only to the emission control system of your new engine. If there is any conflict in  
terms between the ECS Warranty and the Generac Warranty, the ECS Warranty shall apply except in circumstances where  
the Generac Warranty may provide a longer warranty period. Both the ECS Warranty and the Generac Warranty describe  
important rights and obligations with respect to your new engine.  
Warranty service can be performed only by a Generac Authorized Warranty Service Facility. When requesting warranty ser-  
vice, evidence must be presented showing the date of the sale to the original purchaser/owner.  
If there are any questions regarding the warranty rights and responsibilities, contact Generac at the following  
address:  
ATTENTION WARRANTY DEPARTMENT  
GENERAC POWER SYSTEMS, INC.  
P.O. BOX 340  
EAGLE, WI 53119  
Part 1  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 10 – Warranty  
Air-cooled 15 kW Generators  
EMISSION CONTROL SYSTEM WARRANTY  
Emission Control System Warranty (ECS Warranty) for 1995 and later model year engines:  
(a) Applicability: This warranty shall apply to 1995 and later model year engines. The ECS Warranty Period shall begin on the  
date the new engine or equipment is purchased by/delivered to its original, end-use purchaser/owner and shall continue  
for 24 consecutive months thereafter.  
(b) General Emissions Warranty Coverage: Generac warrants to the original, end-use purchaser/owner of the new engine or  
equipment and to each subsequent purchaser/owner that each of its engines is ...  
(1) Designed, built and equipped so as to conform with all applicable regulations adopted by the CARB pursuant to its  
authority, and  
(2) Free from defects in materials and workmanship which, at any time during the ECS Warranty Period, may cause a  
warranted emissions-related part to fail to be identical in all material respects to the part as described in the engine  
manufacturer’s application for certification.  
(c) The ECS Warranty only pertains to emissions-related parts on your engine, as follows:  
(1) Any warranted, emissions-related parts that are not scheduled for replacement as required maintenance in the Owner’s  
Manual shall be warranted for the ECS Warranty Period. If any such part fails during the ECS Warranty Period, it shall  
be repaired or replaced by Generac according to Subsection (4) below. Any such part repaired or replaced under the  
ECS Warranty shall be warranted for the remainder of the ECS Warranty Period.  
(2) Any warranted, emissions-related part that is scheduled only for regular inspection as specified in the Owner’s Manual  
shall be warranted for the ECS Warranty Period. A statement in such written instructions to the effect of “repair or  
replace as necessary” shall not reduce the ECS Warranty Period. Any such part repaired or replaced under the ECS  
Warranty shall be warranted for the remainder of the ECS Warranty Period.  
(3) Any warranted, emissions-related part that is scheduled for replacement as required maintenance in the Owner’s  
Manual shall be warranted for the period of time prior to the first scheduled replacement point for that part. If the part  
fails prior to the first scheduled replacement, the part shall be repaired or replaced by Generac according to Subsection  
(4) below. Any such emissions-related part repaired or replaced under the ECS Warranty shall be warranted for the  
remainder of the ECS Warranty Period prior to the first scheduled replacement point for such emissions-related part.  
(4) Repair or replacement of any warranted, emissions-related part under this ECS Warranty shall be performed at no  
charge to the owner at a Generac Authorized Warranty Service Facility.  
(5) When the engine is inspected by a Generac Authorized Warranty Service Facility, the owner shall not be held responsible  
for diagnostic costs if the repair is deemed warrantable.  
(6) Generac shall be liable for damages to other original engine components or approved modifications proximately caused  
by a failure under warranty of any emission-related part covered by the ECS Warranty.  
(7) Throughout the ECS Warranty Period, Generac shall maintain a supply of warranted emission-related parts sufficient  
to meet the expected demand for such emission-related parts.  
(8) Any Generac authorized and approved emission-related replacement part may be used in the performance of any ECS  
Warranty maintenance or repairs and will be provided without charge to the owner. Such use shall not reduce Generac  
ECS Warranty obligations.  
(9) Unapproved, add-on, modified, counterfeit and/or “grey market” parts may not be used to modify or repair a Generac  
engine. Such use voids this ECS Warranty and shall be sufficient grounds for disallowing an ECS Warranty claim.  
Generac shall not be held liable hereunder for failures of any warranted parts of a Generac engine caused by the use of  
such an unapproved, add-on, modified, counterfeit and/or “grey market” part.  
EMISSION RELATED PARTS INCLUDE THE FOLLOWING:  
1) Fuel Metering System:  
3) Ignition System including:  
a) Spark plug  
1.2) LPG/Natural Gas carburetion assembly and its internal  
components.  
b) Ignition module  
a) Fuel controller (if so equipped)  
4) Catalytic Muffler Assembly (if so equipped) including:  
a) Muffler gasket  
b) Exhaust manifold  
b) Mixer and its gaskets (if so equipped)  
c) Carburetor and its gaskets (if so equipped)  
d) Primary gas regulator (if so equipped)  
e) LP liquid vaporizer (if so equipped)  
5) Crankcase Breather Assembly including:  
a) Breather connection tube  
2) Air Induction System including:  
a) Intake pipe/manifold  
b) Air cleaner  
*Generac engine types covered by this warranty statement include the following:  
1) Prepackaged Standby Generator  
2) Auxiliary Power Unit (APU) Generator  
3) Standby Generator  
Part 2  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 10 – Warranty  
Air-cooled 15 kW Generators  
GENERAC POWER SYSTEMS STANDARD LIMITED WARRANTY FOR  
HOME STANDBY/LIGHT COMMERCIAL PRODUCT 45kW AND BELOW  
For a period of two (2) years from the date of sale, or start-up by Authorized/Certified Generac Power Systems Dealer, or branch thereof, Generac  
Power Systems, Inc. will, at its option, repair or replace any part(s) which, upon examination, inspection, and testing by Generac Power Systems or  
an Authorized/Certified Generac Power Systems Dealer, or branch thereof, is found to be defective under normal use and service, in accordance with  
the warranty schedule set forth below. Any equipment that the purchaser/owner claims to be defective must be examined by the nearest Authorized/  
Certified Generac Power Systems Dealer, or branch thereof. This warranty applies only to Generac Power Systems Generators used in "Standby"  
applications, as Generac Power Systems, Inc. has defined Standby, provided said generator has been properly installed and inspected on-site by  
appropriate personnel. Scheduled maintenance, as outlined by the generator owner's manual, is highly recommended. This should be performed by  
an Authorized/Certified Generac Power Systems Dealer, or branch thereof. This will verify service has been performed on the unit throughout the  
warranty period.  
WARRANTY SCHEDULE  
YEARS ONE and TWO — Limited comprehensive coverage on mileage, labor, and parts listed.  
• - ALL COMPONENTS  
*Start-up and/or On-line Registration, or Registration Card, along with Proof of Purchase, must be performed and/or sent in.  
Guidelines:  
• Any and all warranty repairs and/or concerns, must be performed and/or addressed by an Authorized/Certified Generac Power Systems Dealer, or  
branch thereof.  
• A Generac Power Systems, Inc. Transfer Switch is highly recommended to be used in conjunction with the genset. If a Non - Generac Power  
Systems, Inc. Transfer Switch is substituted for use and directly causes damage to the genset, no warranty coverage shall apply.  
• All warranty expense allowances are subject to the conditions defined in Generac Power Systems Warranty, Policies, and Procedures Flat Rate Manual.  
• Units that have been resold are not covered under the Generac Power Systems Warranty, as this Warranty is not transferable.  
• Unit enclosure is only covered against rust or corrosion the first year of the warranty provision.  
• Use of Non-Generac replacement part(s) will void the warranty in its entirety.  
• Engine coolant heaters (block-heaters), heater controls and circulating pumps are only covered during the first year of the warranty provision (If  
applicable).  
THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING:  
1. Any unit built/manufactured prior to January 1, 2005.  
2. Costs of normal maintenance (i.e. tune-ups, associated part(s), adjustments, loose/leaking clamps, installation and start-up).  
3. Any failure caused by contaminated fuels, oils, coolants/antifreeze or lack of proper fuels, oils or coolants/antifreeze.  
4. Units sold, rated or used for "Prime Power", "Trailer Mounted" or "Rental Unit" applications as Generac Power Systems have defined Prime Power,  
Trailer Mounted or Rental Unit. Contact a Generac Power Systems Distributor for Prime Power, Trailer Mounted or Rental Unit definition and warranty.  
5. Units used for prime power in place of existing utility power where utility is present or in place of utility power where utility power service does not  
normally exist.  
6. Failures caused by any external cause or act of God such as, but not limited to, collision, fire, theft, freezing, vandalism, riot or wars, lightning,  
earthquake, windstorm, hail, volcanic eruption, water or flood, tornado, hurricane, terrorist acts or nuclear holocaust.  
7. Products that are modified or altered in a manner not authorized by Generac Power Systems in writing.  
8. Failures due, but not limited to, normal wear and tear, accident, misuse, abuse, negligence, or improper installation or sizing.  
9. Any incidental, consequential or indirect damages caused by defects in materials or workmanship, or any delay in repair or replacement of the  
defective part(s).  
10. Failure due to misapplication, misrepresentation, or bi-fuel conversion.  
11. Telephone, facsimile, cell phone, satellite, internet, or any other communication expenses.  
12. Rental equipment used while warranty repairs are being performed (i.e. rental generators, cranes, etc.).  
13. Overtime, holiday, or emergency labor.  
14. Planes, ferries, railroad, busses, helicopters, snowmobiles, snow-cats, off-road vehicle or any other mode of transportation deemed abnormal.  
15. Any and all expenses incurred investigating performance complaints unless defective Generac materials and/or workmanship were the direct  
cause of the problem.  
16. Starting batteries, fuses, light bulbs, engine fluids, and overnight freight cost for replacement part(s).  
THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, SPECIFICALLY, GENERAC POWER SYSTEMS  
MAKES NO OTHER WARRANTIES AS TO THE MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some states do not allow  
limitations on how long an implied warranty lasts, so the above limitation may not apply to purchaser/owner.  
GENERAC POWER SYSTEMS ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED ABOVE. IN NO EVENT  
SHALL GENERAC POWER SYSTEMS BE LIABLE FOR ANY INCIDENTAL, OR CONSEQUENTIAL DAMAGES, EVEN IF SUCH DAMAGES ARE A  
DIRECT RESULT OF GENERAC POWER SYSTEMS, INC. NEGLIGENCE.  
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations may not apply to purchaser/  
owner. Purchaser/owner agrees to make no claims against Generac Power Systems, Inc. based on negligence. This warranty gives purchaser/owner  
specific legal rights. Purchaser/owner also may have other rights that vary from state to state.  
Generac Power Systems, Inc. • P.O. Box 8 • Waukesha, WI 53187  
Ph: (262) 544-4811 • Fax: (262) 544-4851  
Bulletin 0171360SVE / Printed in U.S.A. 7.05  
Part No. 0F5631  
Revision C (12/07/06)  
Printed in U.S.A.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Conair Scale TH328 User Manual
Continental Toaster CP43469 User Manual
Curtis DVD Player DVD6048 User Manual
Cyclades Server AlterPath BladeManager User Manual
Danby Microwave Oven DMW749SS User Manual
Dixon Lawn Mower Zero Turn Riding Mower User Manual
Dynex Paper Shredder DX PS06CC User Manual
Faber Ventilation Hood INCA User Manual
Fundex Games Board Games Loteria User Manual
GE Dishwasher GFWH2400 User Manual