NetworX™ Series
NX-8V2 Control Panel
Installation and Startup
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
I.
GENERAL DESCRIPTION.................................................................................................................................................................4
II.
III.
IV.
V.
ORDERING INFORMATION ............................................................................................................................................................4
BOARD INSTALLATION...................................................................................................................................................................4
NX-8V2 WIRING DIAGRAM .............................................................................................................................................................5
TERMINAL DESCRIPTIONS ............................................................................................................................................................6
NETWORX KEYPAD MAXIMUM WIRE RUN..................................................................................................................................6
PROGRAMMING THE LED KEYPADS ..........................................................................................................................................7
VI.
KEYPAD ADDRESS AND PARTITION ..............................................................................................................................................7
CHANGING USER CODES: .................................................................................................................................................................7
ASSIGNING AUTHORITY LEVEL:.....................................................................................................................................................8
VII.
PROGRAMMING THE CONTROL ..................................................................................................................................................8
ENTERING THE PROGRAM MODE...................................................................................................................................................8
SELECTING THE MODULE TO PROGRAM......................................................................................................................................8
PROGRAMMING A LOCATION .........................................................................................................................................................8
EXITING A LOCATION .......................................................................................................................................................................9
EXITING THE PROGRAM MODE.......................................................................................................................................................9
VIII.
PROGRAMMING DATA TYPES.......................................................................................................................................................9
NUMERICAL DATA.............................................................................................................................................................................9
FEATURE SELECTION DATA ............................................................................................................................................................9
PROGRAMMING EXAMPLE.............................................................................................................................................................10
IX.
X.
LOADING FACTORY DEFAULTS.................................................................................................................................................11
ENROLLING MODULES AND KEYPADS....................................................................................................................................11
XI.
L
QUICK START INSTALLATION ...........................................................................................................................................11
XII.
PROGRAMMING LOCATIONS......................................................................................................................................................11
REPORTING EVENTS TO PHONE NUMBER 1...............................................................................................................................12
REPORTING EVENTS TO PHONE NUMBER 2...............................................................................................................................13
REPORTING EVENTS TO PHONE NUMBER 3...............................................................................................................................14
XIII.
XIV.
XV.
DEFAULT ZONE TYPES (CONFIGURATIONS) .........................................................................................................................16
PROGRAMMING WORKSHEETS .................................................................................................................................................32
GLOSSARY.........................................................................................................................................................................................46
APPENDIX 1.......................................................................................................................................................................................50
APPENDIX 2.......................................................................................................................................................................................51
XVI.
XVII.
XVIII. APPENDIX 3.......................................................................................................................................................................................52
XIX.
XX.
APPENDIX 4.......................................................................................................................................................................................53
LOCAL TELEPHONE COMPANY INTERFACE INFORMATION...........................................................................................54
NOTICES.............................................................................................................................................................................................55
UNDERWRITERS LABORATORIES INFORMATION...............................................................................................................56
XXI.
XXII.
XXIII. ANSI / SIA CP-01 REQUIREMENTS ..............................................................................................................................................58
XXIV. SPECIFICATIONS.............................................................................................................................................................................60
NX-8V2 Control
3
Download from Www.Somanuals.com. All Manuals Search And Download.
I.
GENERAL DESCRIPTION
The NetworX NX-8V2 represents a new approach to security systems design. Drawing on our experience in the world market as the
largest exporter of USA manufactured controls, we have developed the most flexible, durable, and user-friendly control ever seen in
our industry. Featuring sophisticated software, which allows up to 99 users to interface with 48 zones, 8 partitions, and a host of
integrated fire, access, verification, and input/output modules, all reported with the most comprehensive and fast SIA and Contact ID
formats. The NetworX design allows a fully loaded system to be housed in one single metal enclosure, establishing for the first time, a
logical solution and design response to modular systems. Up to 32 modules can be added to expand the capabilities of the NX-8V2.
For product warranty information, please refer to the GE Security Product Catalog.
II.
ORDERING INFORMATION
PART #
NX-8
NX-8-KIT
DESCRIPTION
NX-8V2 Control Only
NX-8V2 Control, NX-108E LED Keypad, 16.5V
40VA Transformer
PART #
NX-507E
NX-508E
DESCRIPTION
Seven Relay Module
Eight Output Module
NX-848-KIT
NX-8V2 Control, NX-148E LCD Keypad, 16.5V
40VA Transformer
NX-534E **
Two-Way Listen-In Module
NX-108E
NX-116E
NX-124E
NX-148E
NX-200 **
8 Zone LED Keypad
16 Zone LED Keypad
24 Zone LED Keypad
Alphanumeric LCD Keypad
Zone Doubling Kit (Includes 100 3.74k and 100
6.98k resistors)
NX-540E **
NX-591E **
NX-1192E
NX-1208E
NX-1248E
"Operator" Telephone Interface Module
Cellemetry Interface
192 Zone LCD Keypad
8 Zone LED Keypad
48 Zone LCD Keypad
NX-216E
NX-320E
NX-408E #
16 Zone Expander Module
NX-1308E
NX-1316E
NX-1324E
8 Zone LED Door Design Keypad
16 Zone LED Door Design Keypad
24 Zone LED Door Design Keypad
Smart Power Supply and Buss Extender
8 Zone Wireless Expansion Module
(UL listed part #60-904)
NX-416E #
NX-448E #
16 Zone Wireless Expansion Module
(UL listed part #60-904)
48 Zone Wireless Expansion Module
(UL listed part #60-904)
NX-1448E
48 Zone Fixed Language Icon Keypad
** These products have not been tested and approved by Underwriters Laboratories, Inc.
# These wireless devices are only UL listed for residential applications.
III.
BOARD INSTALLATION
Inside the can, several 2-holed insertion points have been constructed. This allows for either
vertical or horizontal placement of the modules. Notice that each insertion point has two sizes of
holes -a larger hole and a smaller hole.
Diagram 1: The black plastic PCB guides are grooved on one edge where the PC board will be
seated. The end with the half-moon protrusion fits into the larger hole. The smaller hole is for the
screw.
Diagram 2: Place the first black plastic PCB guide in the top insertion point, grooved edge
downward. The half-moon protrusion will be in the large hole. It does not require force. Insert one
of the provided screw into the smaller hole (from inside the can) to secure it in place.
A
screwdriver should reach through the notch that runs the length of the guide to tighten the screw.
The second PBC guide should be positioned opposite the first (grooved edge up) and placed in the
lower insertion point, using the same procedures described above. Once mounted, screw it in
securely.
Diagram 3: The PC Board should slide freely in the grooves of both guides.
4
NX-8V2 Control
Download from Www.Somanuals.com. All Manuals Search And Download.
IV.
NX-8V2 WIRING DIAGRAM
NX-8V2 Control
5
Download from Www.Somanuals.com. All Manuals Search And Download.
V.
TERMINAL DESCRIPTIONS
TERMINAL
DESCRIPTION
House Telephone Ring (Grey).
Telephone Ring (Red).
R1
R
T
Telephone Tip (Green).
T1
House Telephone Tip (Brown).
EARTH
AC
Earth Ground. Connect to a cold water pipe or a 6 to 10 foot driven rod.
AC input. Connect to a 16.5V 40 or 50 VA Class ll U.L. approved transformer.
If used as a siren output (default), the speaker rating should be 15 watt at 8 or 16 ohm, or 30/40 watt at 4, 8,
or 16 ohms. If voltage output is selected in location 37, this output becomes voltage output, 12VDC, 1 Amp
maximum load. NOTE: A 3.3K Ω resistor may be required across the bell terminals when a 12 VDC
siren is used. If no resistor is used, you may experience voltage leakage into the siren, which will
cause these devices to output a small signal.
BELL + & BELL
-
Connect to the data terminal on the keypads and the expanders. Maximum number of devices (keypads +
expanders) is 32. See AMaximum Wire Run@ chart below.
Connect to the Common terminal on the keypads and the expanders.
DATA
COM
POS
Connect to the POS terminal on the keypads and the expanders. Individually, this terminal is limited to 1
Amp. Combined, this terminal and AUX PWR + are limited to 2 amps total current.
Smoke detector power 12VDC, 1.5 amps maximum (For those jurisdictions which allow the Priority zone to
be used with smoke detectors.)
Connect negative wire of powered devices such as motion detectors and smoke detectors.
Connect positive wire of all powered devices except smoke detectors and keypads. Individually, this terminal
is limited to 1 Amp. Combined, this terminal and KP POS are limited to 2 amps total current.
Connect to one side of zone 8 loop. Connect the other side to com terminal. Open or short causes alarm.
Zone 8 may be used for a two-wire smoke detector using a 680 Ω E.O.L. resistor. Refer to wiring diagram.
Program location 37, segment 6, option 1.
SMOKE+
COM
AUX +
ZONE 8
COM
ZONE 7
ZONE 6 - ZONE
1
Common (-) terminal for zones 7 & 8. (See the wiring diagram for examples.)
Connect to one side of zone 7 loop. Connect the other side to COM terminal. Open or short causes alarm.
Connect as described for zones 7 & 8. Only zone 8 can be a two-wire zone. (See the wiring diagram for
examples.)
Connect negative lead of low current device [relay, LED (install 1KΩ resistor in series with LED), etc.].
Connect positive lead of device to COM. Current is limited to 50mA when output is negative, and 250FA
when output is positive.
AUX 1-AUX 4
NETWORX KEYPAD MAXIMUM WIRE RUN
(Note: These numbers are for one keypad at the end of the wire. When connecting more than one keypad to the end of the wire, a
higher gauge wire will be required.)
WHEN CONNECTED TO NX-8V2
WHEN CONNECTED TO NX320-E
Length in feet
250
Wire Gauge
Wire Gauge
24
20
18
16
14
22
18
16
14
12
500
1000
1500
2500
6
NX-8V2 Control
Download from Www.Somanuals.com. All Manuals Search And Download.
VI.
PROGRAMMING THE LED KEYPADS
KEYPAD ADDRESS AND PARTITION
This section describes how to program the address and partition of each keypad as well as the options that are available. The address
of the keypad is important because this is how the panel supervises the keypads.
The factory default for the Master code is [1]-[2]-[3]-[4] when using a 4-digit code or [1]-[2]-[3]-[4]-[5]-[6] for a 6-digit code. The factory
default for the "Go To Program" code is [9]-[7]-[1]-[3] for a 4-digit code or [9]-[7]-[1]-[3]-[0]-[0] for a 6-digit code.
[r] [9] [2] (Applies to LED keypad ONLY)
•
•
•
Enter [r] [9] [2] [program code].
Enter the zone number (1 - 48) you want the keypad to start at.
Enter [r] to save and exit.
[r]-[9]-[3] Set keypad options
•
•
•
Enter [r]-[9]-[3] [program code]. The "Service" LED will flash.
LEDs 1-8 can now be toggled on/off to enable/disable the following functions:
After enabling/disabling the desired functions press [r]
LED
KEYPAD FEATURE ENABLED
1
RESERVED...DO NOT PROGRAM THIS AT ALL!
2
3
4
5
6
7
ENABLE SILENT KEYPAD OPTION
Silences the entry/exit sounder & chime only.
ENABLE DING-DONG SOUND FOR CHIME
If off, chime will be a single tone. (See location 40, page 20)
ENABLE KEYPRESS SILENCE OPTION
Silences the pulsing keypad sounder for 5 seconds when a key is pressed)
ENABLE ARMED STATUS SUPPRESSION
Will not allow the keypad to display faulted or bypassed zones when the system is armed)
ENABLE PANIC, FIRE, MEDICAL BEEPTONE
Will sound a short beep to verify that the keypress was accepted)
SUPPRESSES THE "SERVICE" LED (NOTE: For UL installations, the Service LED shall not be suppressed.)
Will not allow the "Service" LED to illuminate for any reason. If there is a system trouble, pressing [r]-[2] will
still show the service menu.)
8
ENABLE MULTI-PARTITION VIEWING
Enables temporary viewing of all partitions by pressing [r]-[1]-[partition number])
[r]-[9]-[4] Set Keypad Number and Partition
•
•
•
•
Enter [r]-[9]-[4]-[program code]. The "Service" LED and the "Instant" LED will flash.
Enter the keypad number (1-8)
Press [r]. The "Instant" LED will illuminate steady and the "Service" LED will remain flashing.
Enter the partition number for the keypad. The keypad will automatically exit this mode at this time.
[r]-[9]-[5] Set elapsed increments since last autotest
•
•
Enter [r]-[9]-[5]-[program code]. The "Service" LED will flash.
Enter [100's digit] -[10's digit]-[1's digit]-[#]
[r]-[9]-[6] Set system date
•
•
Enter [r]-[9]-[6]-[master code]. The "Service" LED will flash.
Enter [day of week (1=Sun)]-[month 10's digit]-[month 1's digit]-[day 10's digit] [day 1's digit] -[year 10's digit]-[year 1's digit]
[r]-[9]-[7] Set system clock
•
•
Enter [r]-[9]-[7]-[master code]. The "Service" LED will flash.
Enter [hour 10's digit]-[hour 1's digit]-[minutes 10's digit]-[minutes 1's digit]
CHANGING USER CODES:
•
•
•
Enter [r]-[5]-[master code]. The "Ready" LED will flash.
Enter the 2 digit user number (i.e. “03” for user 3). Maximum number of users is 99.
Enter the new user code designated for that individual. The "Ready" LED will flash indicating that the code was accepted. If
it rejects the code, the sounder will beep 3 times.
•
•
If another user code needs to be programmed, return to step 2.
Press [#] while the "Ready" LED is flashing to exit the User Code Programming Mode.
NX-8V2 Control
7
Download from Www.Somanuals.com. All Manuals Search And Download.
ASSIGNING AUTHORITY LEVEL:
•
•
•
Enter [r]-[6]-[master code]. The "Ready" LED will flash.
Enter the 2 digit user number. The "Ready" LED will illuminate steady and the "Instant" LED will flash.
Refer to the chart below for the description of each LED. Turn the LED on for the features that you desire.
LED
1
2
ATTRIBUTES IF LED 8 IS OFF
LED
1
2
ATTRIBUTES IF LED 8 IS ON
Activate output #1
Activate output # 2
Reserved
Arm Only
3
Arm Only After Close Window
3
Activate output # 3
4
5
Master arm/disarm (can program other codes)
Arm/disarm code
4
5
Activate output # 4
Arm/disarm
6
7
8
Allowed to bypass zones (see location 23)
Code will send open / close reports
If this LED is on, LEDs 1-7 will use the chart to the right
6
7
8
Bypass Zones
Open / Close Reporting
If this LED is off, LEDs 1-7 use the chart to the left
•
•
Enter [r]. The "Instant" LED will illuminate steady.
Now you are in the partition enable mode. This tells the system what partition this user can arm/disarm. LEDs 1-8 illuminate for
each partition that the user has authorization for. To change any of these numbers, press 1-8 to permit or deny access to the
user. (Example: If LED 2 is lit, then user has assigned access to that partition. By pressing the [2] key, the LED will go off
indicating the user has been denied access to that partition.)
•
•
Enter [r]
This returns you back to step 2 above, where you may enter another user number to assign attributes for. You may continue this
procedure until you have assigned authority levels to all user numbers - or - you may press [#] key to exit the Assigning Authority
Level Program.
IMPORTANT NOTE
Any master arm/disarm code can add or change a user code if the master code has access to the same partitions as the code
being added/changed. Consequently, when programming the user codes for a partitioned system, leave at least one code (can
be "go to program code" if enabled in location 43) access to all partitions or you will not be able to add new users. If you desire
the end user to be able to add new codes, you must remove the partition authority from all blank codes.
[r]-[9]-[8]
•
•
Pressing [r]-[9]-[8] while the system is disarmed will cause the control to do a callback for a download.
NOTE: A valid user code may be required after [r]-[9]-[8] if enabled in location 41, page 20.
[r]-[9]-[9]
•
•
Pressing [r]-[9]-[9] while the system is disarmed will cause the control panel to seize the phone line for a download.
NOTE: A valid user code may be required after [r]-[9]-[9] if enabled in location 41, page 20.
VII.
PROGRAMMING THE CONTROL
ENTERING THE PROGRAM MODE
To enter the Program Mode, press [r]-[8]. At this time, the five function LEDs (Stay, Chime, Exit, Bypass, & Cancel) will begin to flash.
Next, enter the "Go To Program Code" (FACTORY DEFAULT IS [9]-[7]-[1]-[3]). If the "Go To Program Code" is valid, the "Service" LED
will flash and the five function LEDs will illuminate steady. You are now in the Program Mode and ready to select the module to program.
SELECTING THE MODULE TO PROGRAM
Since all modules connected to the NX-8V2 are programmed through the keypad, the module you are programming should be the first
entry. To program the NX-8V2 Control Panel, enter [0]-[#]. The [0] is the module number of the control and [#] is the entry key. Other
module entry numbers can be found in their corresponding manuals.
PROGRAMMING A LOCATION
Once the number of the module to be programmed has been entered, the "Armed" LED will illuminate, indicating it is waiting for a
programming location to be entered. Any location can be accessed by directly entering the desired programming location followed by [#]. If
the location entered is a valid location, the "Armed" LED will extinguish, the "Ready" LED will illuminate and the binary data for the first
segment of this location will be shown by the zone LED's. While entering new data, the "Ready" LED will begin flashing to indicate a data
change in process. The flashing will continue until the new data is stored by pressing [r]. Upon pressing [r], the keypad will advance to
the next segment and display its data. This procedure is repeated until the last segment is reached. Pressing the [#] key will exit from this
location, and the "Armed" LED will illuminate again waiting for a new programming location to be entered. If the desired location is the next
sequential location, press the [POLICE] key. If the previous location is desired press the [FIRE] key. If the same location is desired press
8
NX-8V2 Control
Download from Www.Somanuals.com. All Manuals Search And Download.
the [MEDICAL] key. To review the data in a location, repeat the above procedure, pressing [r] without any numeric data entry. Each time
[r] is pressed, the programming data of the next segment will be displayed for review.
EXITING A LOCATION
After the last segment of a location is programmed, pressing [r] will exit that location, turn the "Ready" LED off and the "Armed" LED on.
The [r] must be pressed or the data will not be saved. To exit before the last segment, press [#]. As before, you are now ready to enter
another programming location. If an attempt is made to program an invalid entry for a particular segment, the keypad sounder will emit a
triple error beep (beep, beep, beep), and remain in that segment awaiting a valid entry.
EXITING THE PROGRAM MODE
When all the desired changes in programming have been made, it is time to exit the program mode. Pressing [Exit] will exit this
programming level, and go to the "Select a Module To Program" level. If no additional modules are to be programmed, pressing [Exit]
again will exit the program mode. If there is a module to be programmed, it may be selected by entering its address followed by [#] (see
"Selecting the Module To Program" above). The procedure for programming these devices is the same as for the control panel, except the
locations will be for the module selected.
VIII.
PROGRAMMING DATA TYPES
Programming data is always one of two types. One type of data is numerical and can take on values from 0 to 15 or 0 to 255 depending on
the location's segment. The other type of data is a feature selection type. Feature selection data is used to turn features on or off.
Examples are shown on page 10. Use the following procedures when working with these two data types.
NUMERICAL DATA
Numerical data is programmed by entering a number from 0-255 on the numeric keys of the system keypad. To view the data in a
location, a binary process is used. With this process, the LEDs for zones 1 through 8 are utilized, and the numeric equivalents of their
illuminated LEDs are added together to determine the data in a programming location. The numeric equivalents of these LEDs are as
follows:
Zone 1 LED = 1
Zone 5 LED = 16
Zone 2 LED = 2
Zone 6 LED = 32
Zone 3 LED = 4
Zone 7 LED = 64
Zone 4 LED = 8
Zone 8 LED = 128
Example: If the numerical data to be programmed in a location is "66", press [6]-[6] on the keypad. The LEDs for Zone 2 and Zone 7 will
become illuminated indicating 66 is in that location (2 + 64 = 66). See this example on page 10. Once the data is programmed, press [r] to
enter the data and advance to the next segment of that location. After the last segment of a location is programmed, press [r] to exit that
location, turn the "Ready" LED off and the "Armed" LED on. As before, you are now ready to enter another programming location. If an
attempt is made to program a number too large for a particular segment, the keypad sounder will emit a triple beep, indicating an error, and
remain in that segment awaiting a valid entry. On the LCD keypad, the number in the location will be displayed. For locations with a
maximum of 15, the hexadecimal equivalent will be displayed in parenthesis. Example: 11 (B) or 14 (E).
FEATURE SELECTION DATA
Feature selection data will display the current condition (on or off) of eight features associated with the programming location and segment
selected. Pressing a button on the touchpad (1 thru 8) that corresponds to the "feature number" within a segment will toggle (on/off) that
feature. Pressing any numeric key between [1] and [8] for selection of a feature, will make the corresponding LED illuminate (feature ON).
Press the number again, and the LED will extinguish (feature OFF). You will see that numerous features can be selected from within one
segment. For instance, if all eight features of a segment are desired, pressing [1]-[2]-[3]-[4]-[5]-[6]-[7]-[8] will turn on LED's 1 thru 8 as you
press the keys, indicating that those features are enabled. LCD Keypad Note: The numbers of the enabled features will be displayed.
However, the features not enabled will display a hyphen (-). After the desired setting of features is selected for this segment, press [r].
This will enter the data and automatically advance to the next segment of the location. When you are in the last segment of a location and
press [r] to enter the data, you will exit that location. This will now turn the "Ready" LED off and the "Armed" LED on. As before, you are
now ready to enter another programming location.
NX-8V2 Control
9
Download from Www.Somanuals.com. All Manuals Search And Download.
PROGRAMMING EXAMPLE
FIGURE1 (Numerical Data)
Zone 1 LED = 1
Zone 4 LED = 8
Zone 2 LED = 2
Zone 7 LED = 64
Data = 9
Data = 66
}
}
To change data in a
segment, enter the
data followed by [ꢀ]
Pressing [#] will exit a
location without
changing the data in
the current segment.
Enters the previous
programming “location”.
Returns to the “location”
just programmed.
Advances to the next
programming “location”.
FIGURE 2 (Feature Selection Data)
Location 23 ꢂSegment 1
1 = Quick Arm
2 = Re-Exit
3 = Auto Bypass
4 = Silent Keypad Panic
5 = Audible Keypad Panic
6 = Keypad Auxiliary 1
7 = Keypad Auxiliary 2
8 = Multi-Keypad Tamper
Press the key on the numeric keypad that corresponds to the feature you wish to enable/disable. When an LED is “on”, a feature is
enabled; when “off” the feature is disabled. For example: With the 1, 5, & 7 LEDs “on”, Quick Arm, Audible Keypad Panic and
Keypad Auxiliary 2 are enabled.
10
NX-8V2 Control
Download from Www.Somanuals.com. All Manuals Search And Download.
IX.
LOADING FACTORY DEFAULTS
To load the factory defaults, enter the program mode using the procedure on page 8, then type [9]-[1]-[0]-[#]. The keypad will beep 3
times indicating that the loading is in progress. The loading takes about 6 seconds.
X.
ENROLLING MODULES AND KEYPADS
For supervision purposes, the NX-8V2 has the ability to automatically find and store in its memory, the presence of all keypads, zone
expanders, wireless receivers, and any other module connected to the data terminal. This allows these modules to be supervised by
the control panel. To enroll the modules, enter the Program Mode of the NX-8V2 control panel as described on page 8. When the
Program Mode is exited, the NX-8V2 control will automatically enroll the devices. The enrolling process takes about 12 seconds, during
which time the "Service" LED will illuminate. User codes will not be accepted during the enrolling process. If a speaker is attached to
the NX-8V2, it will click at this time. If a siren or bell is attached to the NX-8V2, it will sound for about 1 second. Once a module is
enrolled, if it is not detected by the control, the "Service" LED will illuminate.
XI. L QUICK START INSTALLATION
For most routine installations, the "Quick Start" option will allow for enabling a majority of the options available with the NX-8V2, when
communicating in Contact ID or SIA formats and without partitioning. The "Quick Start" locations can be identified by the Lsymbol.
XII.
PROGRAMMING LOCATIONS
LOCATION
DESCRIPTION
SEGMENTS....DATA TYPE
20...........numerical
L
0
PHONE NUMBER 1
The first telephone number is programmed in location 0. A "14" indicates the end of the phone number. Delays of four seconds can be
programmed at any point in the phone number by programming a "13" in the appropriate segment. If tone dialing is desired, program a
"15" in the segment where tone dialing should begin. If the entire number should be tone dialing, program a "15" in the first segment.
Program an A11" for a Ar@, and a A12" for a A#@. Caution: A call-waiting cancel on a non- call waiting line will prevent successful
connection to the central station.
L
1
ACCOUNT CODE FOR PHONE 1
6.............numerical
The account code sent when Phone 1 is dialed is programmed in location 1. Program a A10" in the segment immediately after the last
digit of the account code. If the account code is 6 digits long, program all 6 segments.
L
2
COMMUNICATOR FORMAT FOR PHONE 1
1.............numerical
Location 2 contains the communicator format used to transmit to the receiver connected to Phone 1. Consult the instructions for your
central station receiver to determine which format is compatible. Select a format from Table XII-1 COMMUNICATOR FORMAT
SELECTIONS. If you require a format other than those listed, review the override options described in location 18, to build the
appropriate format. A "15" must be programmed in location 2 in addition to the entries in location 18 in order to create a special format.
If this location contains a "0", the built-in communicator will be disabled, and the NX-8V2 will function as a local only control.
Table XII-1 COMMUNICATOR FORMAT SELECTIONS
DATA
0
FORMAT
DESCRIPTION
Local
Communicator is disabled
1
2
3
Universal 4+2
3+1 fast (or 4+1)
Reserved
Two digit event code 1800hz transmit 2300hz handshake double round parity 40pps
One digit event code 1900Hz transmit 1400Hz handshake double round parity 20pps
Reserved
4
Pager
2 digit event code DTMF transmission
5
6
7
8
3/1 or 4/1 slow
3/1 or 4/1 slow
3/1 or 4/1 fast
3/1 or 4/1 fast
3/1 or 4/1 fast with parity
3/1 or 4/1 fast with parity
4+2 express
4+2 fast
Ademco Contact ID
SIA
1800hz transmit 2300hz handshake double round parity 20 p.p.s. hex capability
1800hz transmit 1400hz handshake double round parity 20 p.p.s. hex capability
1800hz transmit 2300hz handshake double round parity 40 p.p.s. hex capability
1800hz transmit 1400hz handshake double round parity 40 p.p.s. hex capability
1800hz transmit 2300hz handshake single round w/parity 40 p.p.s. hex capability
1800hz transmit 1400hz handshake single round w/parity 40 p.p.s. hex capability
2 digit event code DTMF transmission
Two-digit event code 1900hz transmit 1400hz handshake double round parity 20 p.p.s.
DTMF (see pages 50 & 51)
FSK (see pages 50 & 51 )
9
10
11
12
13
14
15
Custom format
(See location 18, page 15)
NX-8V2 Control
11
Download from Www.Somanuals.com. All Manuals Search And Download.
L
3
DIAL ATTEMPTS/BACKUP CONTROL FOR PHONE 1
2 ........... numerical
Segment 1- Dial attempts: Location 3, Segment 1 is used to enter the number of dial attempts (1 to 15 Attempts) the communicator
will make to Phone 1 before ending the notification process. Factory default is "8" and the communicator will make eight (8) attempts
to the first number.
Segment 2- Phone 1 Backup Control: Programming a "0" in Segment 2 of this location will cause the NX-8V2 to make the designated
number of attempts to Phone 2 before setting the "Fail To Communicate" condition and stop reporting. Programming a "1" in this
segment will cause the NX-8V2 to stop trying to communicate after the designated number of attempts have been made to Phone 1. If
a "2" is programmed in this segment, it will cause the NX-8V2 to make the dial attempts in increments of two. The first two attempts will
be made to Phone 1, the next two attempts to Phone 2, then repeating until the total number of attempts designated in Segment 1 is
completed.
REPORTING EVENTS TO PHONE NUMBER 1
Phone 1 has two programming locations that are used to select which events are reported to this phone number. Location 4 is used to
select which events are reported to Phone 1. Location 5 is used to select which partitions are reported to Phone 1. If dual or split
reporting is not desired, location 4 should be used to select all events to Phone 1 and location 5 should be left at the factory default of
"0". If dual or split reporting is desired, and the split is based on the event type (such as alarm, open/close, etc.), location 4 should be
used to select only those events that should be reported to Phone 1 and location 5 should be left at the factory default of "0". If dual or
split reporting is desired, and the split is based on partition, location 4 should be programmed as a "0" and location 5 should be used to
select those partitions that should be reported to Phone 1. If no events should be reported to Phone 1, both locations should be
programmed as "0" (disabling all options).
4
EVENTS REPORTED TO PHONE 1
2 ............ feature select
Segment 1:
1 = Alarms and Alarm Restores.
2 = Opening and Closings.
3 = Zone Bypass and Bypass Restores.
4 = Zone Trouble and Trouble Restores.
5 = Power Fail, Low Battery, Power Restore, and Low Battery Restore.
6 = Bell Cut, Telephone Line Cut, Bell Cut Restore, Telephone Line Restore.
7 = Test Reports.
8 = Start and End programming, Download complete.
Segment 2:
1 = Zone and Box Tamper and Tamper Restore.
2 = Auxiliary Power Overcurrent, Ground Fault, and Restore for both.
3 = Wireless Sensor Missing and Restore.
4 = Wireless Sensor Low Battery and Restore.
5 = Expander Trouble and Restore.
6 = Fail To Communicate.
7 = Zone Activity Monitor.
8 = Reserved.
5
PARTITIONS REPORTED TO PHONE 1
1 ............ feature select
Location 5 is used when events to be reported to a phone number are based upon the partition regardless of the event. If this location
is used, location 4 should be programmed as "0".
Segment 1:
1 = Partition 1
2 = Partition 2
3 = Partition 3
4 = Partition 4
5 = Partition 5
6 = Partition 6
7 = Partition 7
8 = Partition 8
L
6
PROGRAMMING PHONE 2
20 .......... numerical
Phone 2 is programmed in location 6. A "14" indicates the end of the phone number. Delays of four seconds can be programmed at
any point in the phone number by programming a "13" in the appropriate segment. If tone dialing is desired, program a "15" in the
segment where tone dialing should begin. If the entire number should be tone dialing, program a "15" in the first segment. Program an
A11" for a Ar@, and a A12" for a A#@. Caution: A call-waiting cancel on a non- call waiting line will prevent successful connection to the
central station.
L
7
ACCOUNT CODE FOR PHONE 2
6 ............ numerical
The account code sent when Phone 2 is dialed is programmed in location 7. Program a A10" in the segment immediately after the last
digit of the account code. If the account code is 6 digits long, program all 6 segments. If this location is left unprogrammed, account
code 1 will be used when the second phone number is dialed.
12
NX-8V2 Control
Download from Www.Somanuals.com. All Manuals Search And Download.
L
8
COMMUNICATOR FORMAT FOR PHONE 2
1.............numerical
Location 8 contains the communicator format used to transmit to the receiver connected to Phone 2. Consult the instruction manual for
your central station receiver to determine which format is compatible, and select from Table XII-1 COMMUNICATOR FORMAT
SELECTIONS on page 11. If you require a format other than those listed, review the override options described in Location 18 to build
the appropriate format. A "15" must be programmed in location 8 in addition to the entries in location 18 in order to create a special
format. If this location contains a "0", format 1 will be used when Phone 2 is dialed.
9
DIAL ATTEMPTS/BACKUP CONTROL FOR PHONE 2
2.............numerical
Segment 1, Dial attempts: Segment 1 of Location 9 is used to enter the number of dial attempts (1 to 15 attempts) the communicator
will make to Phone 2 before ending the notification process. Factory default is "8" and the communicator will make the same number
of attempts as those programmed in location 3.
Segment 2, Phone 2 Backup Control: Programming a "0" in Segment 2 of this location will cause the NX-8V2 to make the designated
number of attempts to Phone 1 before setting the "Fail To Communicate" condition and stop reporting. Programming a "1" in this
segment will cause the NX-8V2 to stop trying to communicate after the designated number of attempts have been made to Phone 2. If
a "2" is programmed in this segment, it will cause the NX-8V2 to make the dial attempts in increments of two. The first two attempts will
be made to Phone 2, the next two attempts to Phone 1, then repeating until the total number of attempts designated in Segment 1 is
completed.
REPORTING EVENTS TO PHONE NUMBER 2
Phone 2 can be used to back up Phone 1 or for a second receiver to multi-report or split report events. Phone 2 has two programming
locations that are used to select which events are reported to this phone number. Location 10 is used to select which events are
reported to Phone 2, and location 11 is used to select which partitions are reported to Phone 2. If dual or split reporting is not desired,
location 10 and location 11 should be left at the factory default of "0". If multi-reporting or split reporting is desired, and the split is
based on the event type (such as alarm, open close etc.), location 10 should be used to select only those events that should be
reported to Phone 2, and location 11 should be left at the factory default of "0". If dual or split reporting is desired, and the split is
based on partition, then location 10 should be programmed as "0", and location 11 should be used to select those partitions that should
be reported to the Phone 2. If no events should be reported to Phone 2, both locations should be "0".
10
Segment 1:
EVENTS REPORTED TO PHONE 2
2.............feature select
1 = Alarms and Alarm Restores.
2 = Opening and Closings.
3 = Zone Bypass and Bypass Restores.
4 = Zone Trouble and Trouble Restores.
5 = Power Fail, Low Battery, Power Restore, and Low Battery Restore.
6 = Bell Cut, Telephone Line Cut, Bell Cut Restore, Telephone Line Restore.
7 = Test Reports.
8 = Start and End programming, Download complete.
Segment 2:
1 = Zone and Box Tamper and Tamper Restore.
2 = Auxiliary Power Overcurrent and Ground Fault and Restore for both.
3 = Sensor Missing and Restore.
4 = Sensor Low Battery and Restore.
5 = Expander Trouble and Restore.
6 = Fail To Communicate.
7 = Zone Activity Monitor.
8 = Reserved.
11
PARTITIONS REPORTED TO PHONE 2
1.............feature select
Location 11 is used when events to be reported to a phone number are based upon the partition regardless of the event. If this location
is used, location 10 should be "0".
Segment 1:
1 = Partition 1
2 = Partition 2
3 = Partition 3
4 = Partition 4
5 = Partition 5
6 = Partition 6
7 = Partition 7
8 = Partition 8
12
PROGRAMMING PHONE 3
20...........numerical
Phone 3 is programmed in location 12. A "14" indicates the end of the phone number. Delays of four seconds can be programmed at
any point in the phone number by programming a "13" in the appropriate segment. If tone dialing is desired, program a "15" in the
segment where tone dialing should begin. If the entire number should be tone dialing, program a "15" in the first segment. Program an
A11" for a Ar@, and a A12" for a A#@. Caution: A call-waiting cancel on a non- call waiting line will prevent successful connection to the
central station.
NX-8V2 Control
13
Download from Www.Somanuals.com. All Manuals Search And Download.
13
ACCOUNT CODE FOR PHONE 3
6 ............ numerical
The account code sent when Phone 3 is dialed is programmed in location 13. Program a A10" in the segment immediately after the last
digit of the account code. If the account code is 6 digits long, program all 6 segments. If location 6 is left unprogrammed, account
code 1 will be used when the Phone 3 is dialed.
14
COMMUNICATOR FORMAT FOR PHONE 3
1 ............ numerical
Location 14 contains the communicator format used to transmit to the receiver connected to phone 3. Consult the instruction manual
for your central station receiver to determine which format is compatible, and select from Table XII-1 COMMUNICATOR FORMAT
SELECTIONS on page 11. If you require a format other than those listed, review the override options described in Location 18 to build
the appropriate format. A "15" must be programmed in location 14 in addition to the entries in location 18 in order to create a special
format. If this location contains a "0", format 1 will be used when Phone 3 is dialed.
15
DIAL ATTEMPTS/BACKUP CONTROL FOR PHONE 3
2 ............ numerical
Segment 1, Dial Attempts: Segment 1 of Location 15 is used to enter the number of dial attempts (1 to 15 attempts) the
communicator will try to Phone 3 before ending the notification process. Factory default is "8" and the communicator will make the
same number of attempts as those programmed in location 3.
Segment 2, Phone 3 Backup Control: Programming a "0" in Segment 2 of this location will cause the NX-8V2 to make the designated
number of attempts to Phone 2 before setting the "Fail To Communicate" condition and stop reporting. Programming a "1" in this
segment will cause the NX-8V2 to stop trying to communicate after the designated number of attempts have been made to Phone 3. If
a "2" is programmed in this segment, it will cause the NX-8V2 to make the dial attempts in increments of two. The first two attempts will
be made to Phone 3, the next two attempts to Phone 2, then repeating until the total number of attempts designated in Segment 1 is
completed.
REPORTING EVENTS TO PHONE NUMBER 3
Phone 3 can be used for a third receiver to multi-report or split report events. Phone 3 has two programming locations that are used to
select which events are reported to this phone number. Location 16 is used to select which events are reported to Phone 3, and
Location 17 is used to select which partitions are reported to Phone 3. If dual or split reporting is not desired, location 16 and location
17 should be left at the factory default of "0". If multi-reporting or split reporting is desired and the split is based on the event type
(such as alarm, open/close, etc.), then location 16 should be used to select only those events that should be reported to Phone 3 and
location 17 should be left at the factory default of "0". If dual or split reporting is desired, and the split is based on partition, then
location 16 should be programmed to "0" and location 17 should be used to select those partitions that should be reported to Phone 3.
If no events should be reported to Phone 3, both locations should be "0".
16
Segment 1:
EVENTS REPORTED TO PHONE 3
2 ............ feature select
1 = Alarms and Alarm Restores.
2 = Opening and Closings.
3 = Zone Bypass and Bypass Restores.
4 = Zone Trouble and Trouble Restores.
5 = Power Fail, Low Battery, Power Restore, and Low Battery Restore.
6 = Bell Cut, Telephone Line Cut, Bell Cut Restore, Telephone Line Restore.
7 = Test Reports.
8 = Start and End programming, Download complete.
Segment 2:
1 = Zone and Box Tamper and Tamper Restore.
2 = Auxiliary Power Overcurrent and Ground Fault and Restore for both.
3 = Sensor Missing and Restore.
4 = Sensor Low Battery and Restore.
5 = Expander Trouble and Restore.
6 = Fail To Communicate.
7 = Zone Activity Monitor.
8 = Reserved.
17
PARTITIONS REPORTED TO PHONE 3
1 ............ feature select
Location 17 is used when events to be reported to a phone number are based upon the partition regardless of the event. If this location
is used, location 16 should be "0".
Segment 1:
1 = Partition 1
2 = Partition 2
3 = Partition 3
4 = Partition 4
5 = Partition 5
6 = Partition 6
7 = Partition 7
8 = Partition 8
14
NX-8V2 Control
Download from Www.Somanuals.com. All Manuals Search And Download.
18
Segment 1:
CUSTOM COMMUNICATOR FORMAT
Segment 2:
(See loc 2, 8, &14)
1 = On for 1800hz transmit; Off for 1900hz.
2 = On for 2300hz handshake; Off for 1400hz.
3 = On for cksum parity; Off for double round parity.
4 = On for 2 digit event code; Off for 1 digit event code.
5 = Reserved.
1 = On for pager format (no handshake required).
2 = On for 1400/2300 handshake.
3 = Reserved
4 = Reserved.
5 = On for Contact ID.
6 = On for SIA.
6 = Reserved.
7 = On for 20 p.p.s.; Off for 10 or 40 p.p.s.
8 = On for 10 p.p.s.; Off for 20 or 40 p.p.s.
Segment 3 & 4: Reserved
7 = On for Contact ID or 4+3.
8 = On for DTMF.
L
19
DOWNLOAD ACCESS CODE
8.............numerical
Location 19 contains the eight-digit access code the NX-8V2 must receive from the downloading software before the panel will permit
downloading to occur. The factory default code is 84800000.
L
20
NUMBER OF RINGS TO ANSWER
1.............numerical
Location 20 contains the number of rings to answer for a download. Enter a number from A0" (disabled) to "15". Factory default is "8"
and the NX-8V2 will answer on 8 rings.
L
21
DOWNLOAD CONTROL
1.............feature select
Location 21 contains the feature selections for the controlling of download sessions. The following features can be enabled or disabled
using this location. (Refer to Glossary beginning on page 46)
ꢀ
Options 4, 5, 6,
and 7 can only be
viewed from the
Segment 1:
1 = On enables two call answering machine defeat.
2 = On enables tone sniff answering machine defeat.
3 = On requires call back before download session.
4 = Shutdown
keypad. These options
must be changed
through downloading.
5 = On locks all local programming
6 = On locks programming of all locations associated with the communicator
7 = On locks out download section. (If "On", locations 19 - 22 cannot be viewed from the keypad; can only be viewed from the
keypad when "Off".)
8 = On enables call back at auto test interval.
L
22
DOWNLOAD CALL BACK NUMBER
20...........numerical
If a telephone number is programmed into this location, and "Require Callback" is enabled in location 21, the control panel will hang up
for approximately 36 seconds (ensuring that the calling party has disconnected), and then call back. If tone dialing is desired, program
an "15" in the segment where tone dialing should begin. If the entire number should be tone dialing, program an A15" in the first
segment. Four-second delays can be obtained anywhere in the sequence by programming a "13" in the appropriate delay location.
THE CALLBACK PHONE NUMBER SHOULD ALWAYS BE REVIEWED FOR ACCURACY BEFORE
DISCONNECTING.
L
23
PARTITION 1, FEATURE & REPORT SELECTIONS
5.............feature select
Location 23 is used to enable certain features that can be accessed or are visible to the user from the keypad of the system. In
addition, certain communicator reports are enabled in location 23. Each of these features can be enabled by partition. For additional
partition information see locations 88-109 on pages 25- 27. If the feature selection location for any partition is left blank, that
partition will use this location for the feature selection. (For specific definitions, refer to the Glossary beginning on page 46)
Segment 1:
1 = On enables the Quick Arm feature.
2 = On enables the Re-exit feature.
3 = On enables the Automatic Bypass feature.
4 = On enables the Silent Keypad Panic feature (overrides the audible panic selection).
5 = On enables the Audible Keypad Panic feature.
6 = On enables the Keypad Aux 1 feature (FIRE).
7 = On enables the Keypad Aux 2 feature (MEDICAL).
8 = On enables the Keypad Multiple Code Attempt Tamper feature.
NX-8V2 Control
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Segment 2:
1 = On enables the LED Extinguish feature.
2 = On enables the Require Code for Bypassing feature.
3 = On enables the Zone Bypassed Sounder Alert feature.
4 = On enables the AC Power/Low Battery Sounder Alert feature.
5 = On enables Bypass toggle.
6 = On enables Silent Auto Arm.
7 = On enables the Automatic Instant feature.
8 = On enables Instant mode toggle. (Applies to NX-1208E / NX-1248E keypads)
Segment 3:
1 = On enables Opening and Closing reports.
2 = On enables Zone Bypass reporting.
3 = On enables Zone Restore reporting.
4 = On enables Zone Trouble reporting.
5 = On enables Zone Tamper reporting.
6 = On enables the Cancel reporting.
7 = On enables the Recent Closing report.
8 = On enables the Exit Error report.
Segment 4:
1 = On enables Late to Close / Early to Open.
2 = On enables Auto Arm in Stay Mode.
3 = On disables the door delays in Night mode. (Applies to NX-1208E / NX-1248E keypads)
4 = On disables the bypass for Force Arm zones.
Segment 5:
Reserved
L
24
ENTRY / EXIT TIMERS
6 ............ numerical
Location 24 is used to program the Entry/Exit times. There are 2 separate Entry/Exit times.
Segment 1,
Segment 2,
Segment 3,
Segment 4,
Entry time 1:
Exit time 1:
Entry time 2:
Exit time 2:
This is the entry time that will be used when a delay 1 zone type initiates an entry delay. Valid
entries are 30-255 seconds.
This is the exit time that will be used for all zones designated as delay 1. Valid entries are 45-255
seconds.
This is the entry time that will be used when a delay 2 zone type initiates an entry delay. Valid
entries are 30-255 seconds.
This is the exit time that will be used for all zones designated as delay 2. Valid entries are 45-255
seconds.
Segments 5 & 6
Reserved.
XIII.
DEFAULT ZONE TYPES (Configurations)
Zones can be programmed to be one of thirty different zone types (configurations). Zone types 17 - 20 can be used for wireless or
hardwired zones using European double EOL configuration. The default zone types are listed below. These zone types can be
customized by programming locations 110-169.
DATA
1
2
DESCRIPTION OF DEFAULT ZONE TYPES
DAY ZONE - Instant when system is armed trouble zone when system is disarmed.
24-HOUR AUDIBLE - Creates an instant yelping siren alarm regardless of the armed state of the control panel.
ENTRY/EXIT DELAY 1- A trip will start entry delay 1. The lack of a trip during exit delay will enable the Automatic
Bypass or Instant mode if so programmed.
3
FOLLOWER WITH AUTO- BYPASS DISABLED - This zone will be instant when the system is armed and no entry or
exit delays are being timed. It is delayed during entry and exit delay 1 times. This zone will not automatically bypass even
if enabled in Segment 1 of Location 23.
4
INTERIOR FOLLOWER WITH AUTO- BYPASS ENABLED - This zone will be instant when the system is armed and no
entry or exit delay is being timed. It is delayed during entry and exit delay 1 times. This zone will automatically bypass if
enabled in Segment 1 of Location 23.
5
6
7
INSTANT - This zone creates an instant alarm whenever it is tripped and the Armed LED is on.
24-HOUR SILENT - Creates an instant silent alarm regardless of the armed state of the control panel. It will not display
on the keypad.
FIRE - This zone will light the Fire LED and sound the temporal siren each time the zone is shorted. It will also rapidly
flash the Fire LED indicating a trouble if the zone is open.
ENTRY/EXIT DELAY 2- A trip will start entry delay 2. The lack of a trip during exit delay will enable the Automatic
Bypass or Instant mode if so programmed.
8
9
24-HOUR SILENT SUPERVISED- Creates an instant silent alarm regardless of the armed state of the control panel. It
will display on the keypad.
10
16
NX-8V2 Control
Download from Www.Somanuals.com. All Manuals Search And Download.
DATA
11
DESCRIPTION OF DEFAULT ZONE TYPES
KEYSWITCH ZONE - This zone type will arm and disarm the partition or partitions of the control panel that it resides in
each time the zone is shorted. Keyswitch arming will report as user #99.
INTERIOR FOLLOWER WITH "CROSS ZONE" ENABLED - This zone will be instant when the system is armed and no
entry or exit delay is being timed. It is delayed during entry and exit delay times. If a "Cross Zone" is not being timed it will
start a "Cross Zone" timer. If a "Cross Zone" is being timed it will create an instant alarm. This zone will automatically
bypass when enabled in Segment 1 of Location 23.
12
INSTANT ENTRY GUARD - This zone creates an instant alarm whenever it is tripped and the Stay LED is off. It will start
an entry delay time 2 if it is tripped and the system is armed and the Stay LED is on.
ENTRY/EXIT DELAY 1 WITH GROUP BYPASS ENABLED - A trip will start entry delay 1. This zone will bypass when
the "Group Bypass" command is entered at the keypad. The lack of a trip during exit delay will enable the Automatic
Bypass or Instant mode if so programmed.
13
14
INTERIOR FOLLOWER WITH GROUP BYPASS ENABLED - This zone will be instant when the system is armed and no
entry or exit delays are being timed. It is delayed during entry/exit delay times. This zone will bypass when the "Group
Bypass" command is entered at the keypad. This zone will automatically bypass if enabled in Segment 1 of Location 23.
INSTANT WITH GROUP BYPASS ENABLED - This zone creates an instant alarm whenever it is tripped and the Armed
LED is on. This zone will bypass when the "Group Bypass" command is entered at the keypad.
ENTRY/EXIT DELAY 1 WITH TAMPER ENABLED- A trip will start entry delay 1. The lack of a trip during exit delay will
enable the Automatic Bypass or Instant mode if so programmed. This zone type can be used to enable tamper on a
wireless transmitter.
15
16
17
INTERIOR FOLLOWER WITH TAMPER AND AUTO-BYPASS ENABLED - This zone will be instant when the system is
armed and no entry or exit delay is being timed. It is delayed during entry and exit delay times. This zone will
automatically bypass if enabled in Segment 1 of Location 23. This zone type can be used to enable tamper on a
wireless transmitter.
18
INSTANT WITH TAMPER ENABLED - This zone creates an instant alarm whenever it is tripped and the Armed LED is
on. This zone type can be used to enable tamper on a wireless transmitter.
ENTRY/EXIT DELAY 2 WITH TAMPER ENABLED-A trip will start entry delay 2. The lack of a trip during exit delay will
enable the Automatic Bypass or Instant mode if so programmed. This zone type can be used to enable tamper on a
wireless transmitter.
19
20
GAS DETECTION- Creates an instant alarm regardless of the armed state of the control panel. It will display on the
keypad and activate the keypad sounder.
LOW TEMP DETECTION- Creates an instant silent alarm regardless of the armed state of the control panel. It will display
on the keypad and activate the keypad sounder.
HIGH TEMP DETECTION- Creates an instant silent alarm regardless of the armed state of the control panel. It will
display on the keypad and activate the keypad sounder.
MANUAL FIRE - This zone will illuminate the Fire LED and sound the temporal siren each time the zone is shorted. It will
also rapidly flash the Fire LED indicating a trouble if the zone is open.
21
22
23
24
25
CHIME ONLY - Creates no alarm regardless of the armed state of the control panel. It will chime anytime it is faulted and
will display on the keypad. Local only.
INTERIOR FOLLOWER DELAY 2 - This zone will be instant when the system is armed and no entry or exit delay is
being timed. It is delayed during entry and exit delay 2 times. This zone will automatically bypass if enabled in Segment 1
of Location 23.
26
INTERIOR FOLLOWER FORCE ARMABLE - This zone will be instant when the system is armed and no entry or exit
delay is being timed. It is delayed during entry and exit delay 1 times. This zone will automatically bypass if enabled in
Segment 1 of Location 23.
ENTRY/EXIT FORCE ARMABLE DELAY 2 - A trip will start entry delay 2. The lack of a trip during exit delay will enable
the Automatic Bypass or Instant mode if so programmed.
27
28
INTERIOR FOLLOWER WITH ACTIVITY SUPERVISION ENABLED - This zone will be instant when the system is
armed and no entry or exit delay is being timed. It is delayed during entry and exit delay times. It will send a report if the
zone activity time is reached without a change of state. Refer to Location 40 / Segment 11. This zone will automatically
bypass if enabled in Segment 1 of Location 23.
ENTRY/EXIT WITH ACTIVITY SUPERVISION ENABLED- A trip will start entry delay 1. It will send a report if the zone
activity time is reached without a change of state. Refer to Location 40 / Segment 11. The lack of a trip during exit delay
will enable the Automatic Bypass or Instant mode if so programmed.
29
30
L
25
ZONES 1-8 ZONE TYPE
8.............numerical
Location 25 contains the Zone Type for zones 1-8. Segment 1 is for zone 1, and Segment 8 is for zone 8. Default Zone Types are
found in the table on page 16. To customize a Zone Type, see page 28.
26
PARTITION SELECT, ZONES 1-8
8............. feature select
Location 26 is used to select the partition(s) that zones 1 - 8 reside in. A zone may reside in any combination of the 8 partitions. If a
burglary zone resides in more than 1 partition, it will only be active when all partitions it resides in are armed. A zone that
resides in more than 1 partition will be reported to its lowest partition number. Location 26 has 8 segments. Segment 1
corresponds to zone 1, and Segment 8 corresponds to zone 8.
NX-8V2 Control
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Segments 1 - 8:
1 = Partition 1
2 = Partition 2
3 = Partition 3
4 = Partition 4
5 = Partition 5
6 = Partition 6
7 = Partition 7
8 = Partition 8
L
27
ZONES 9-16 ZONE TYPE
8 ............ numerical
Location 27 contains the Zone Type for zones 9 -16. Segment 1 is for zone 9; Segment 8 is for zone 16. Default Zone Types are
found in the table on page 16. To customize a Zone Type, see page 28.
28
PARTITION SELECT, ZONES 9-16
8 ............ feature select
Location 28 is used to select the partition(s) that zones 9-16 reside in. A zone may reside in any combination of the 8 partitions. If a
burglary zone resides in more than 1 partition, it will only be active when all partitions are armed. A zone that resides in more
than 1 partition will be reported to its lowest partition. Location 28 has 8 segments. Segment 1 corresponds to zone 9 and
Segment 8 corresponds to zone 16.
Segments 1 - 8:
1 = Partition 1
2 = Partition 2
3 = Partition 3
4 = Partition 4
5 = Partition 5
6 = Partition 6
7 = Partition 7
8 = Partition 8
L
29
ZONES 17-24 ZONE TYPE
8 ............ numerical
Location 29 contains the Zone Type for zones 17-24. Segment 1 is for zone 17; Segment 8 is for zone 24. Default Zone Types are
found in the table on page 16. To customize a Zone Type, see page 28.
30
PARTITION SELECT, ZONES 17-24
8 ............ feature select
Location 30 is used to select the partition(s) that zones 17-24 reside in. A zone may reside in any combination of the 8 partitions. If a
burglary zone resides in more than 1 partition, it will only be active when all partitions are armed. A zone that resides in
more than 1 partition will be reported to its lowest partition. Location 30 has 8 segments. Segment 1 corresponds to zone 17 and
Segment 8 corresponds to zone 24.
Segments 1 - 8:
1 = Partition 1
2 = Partition 2
3 = Partition 3
4 = Partition 4
5 = Partition 5
6 = Partition 6
7 = Partition 7
8 = Partition 8
L
31
ZONES 25-32 ZONE TYPE
8 ............ numerical
Location 31 contains the Zone Type for zones 25-32. Segment 1 is for zone 25; Segment 8 is for zone 32. Default Zone Types are
found in the table on page 16. To customize a Zone Type, see page 28.
32
PARTITION SELECT, ZONES 25-32
8 ............ feature select
Location 32 is used to select the partition(s) that zones 25-32 reside in. A zone may reside in any combination of the 8 partitions. If a
burglary zone resides in more than 1 partition it will only be active when all partitions are armed. A zone that resides in more
than 1 partition will be reported to its lowest partition. Segment 1 corresponds to zone 25 and Segment 8 corresponds to zone
32.
Segments 1 - 8:
1 = Partition 1
2 = Partition 2
3 = Partition 3
4 = Partition 4
5 = Partition 5
6 = Partition 6
7 = Partition 7
8 = Partition 8
L
33
ZONES 33-40 ZONE TYPE
8 ............ numerical
Location 33 contains the Zone Type for zones 33-40. Segment 1 is for zone 33 Segment 8 is for zone 40. Default Zone Types are
found in the table on page 16. To customize a Zone Type, see page 28.
34
PARTITION SELECT, ZONES 33-40
8 ............ feature select
Location 34 is used to select the partition(s) that zones 33-40 reside in. A zone may reside in any combination of the 8 partitions. If a
burglary zone resides in more than 1 partition, it will only be active when all partitions are armed. A zone that resides in more
than 1 partition will be reported to its lowest partition. Segment 1 corresponds to zone 33 and Segment 8 corresponds to zone 40.
Segments 1 - 8:
1 = Partition 1
2 = Partition 2
3 = Partition 3
4 = Partition 4
5 = Partition 5
6 = Partition 6
7 = Partition 7
8 = Partition 8
L
35
ZONES 41-48 ZONE TYPE
8 ............ numerical
Location 35 contains the Zone type for zones 41-48. Segment 1 is for zone 41 Segment 8 is for zone 48. Default Zone Types are
found in the table on page 16. To customize a Zone Type, see page 28.
18
NX-8V2 Control
Download from Www.Somanuals.com. All Manuals Search And Download.
36
PARTITION SELECT, ZONES 41-48
8.............feature select
Location 36 is used to select the partition or partitions that zones 41-48 reside in. A zone may reside in any combination of the 8
partitions. If a burglary zone resides in more than 1 partition it will only be active when all partitions are armed. A zone that
resides in more than 1 partition will be reported to its lowest partition. Location 36 has 8 segments. Segment 1 corresponds to
zone 41 and Segment 8 corresponds to zone 48.
Segments 1 - 8:
1 = Partition 1
2 = Partition 2
3 = Partition 3
4 = Partition 4
5 = Partition 5
6 = Partition 6
7 = Partition 7
8 = Partition 8
L
37
SIREN AND SYSTEM SUPERVISION
7.............feature select
Location 37 is used to enable various system feature and reporting options. (For specific definitions, refer to the Glossary beginning on
page 46)
Segment 1:
1 = On if siren sounds for "Telephone Line Cut" when armed.
2 = On if siren sounds for "Telephone Line Cut" when disarmed.
3 = On if siren blast at arming.
4 = On if siren blast at exit expiration.
5 = On if siren blast at closing kissoff.
6 = On if siren sounds during a "Cross Zone" verification time.
7 = On if siren sounds for a Zone or Box Tamper.
8 = On if siren blasts 1 time for keyswitch or wireless arming; 2 times for disarming. (Note: Must be disabled for SIA CP-01 installations.)
Segment 2:
1 = On if siren driver should be a voltage output. Off if on board siren driver enabled.
2 = On if siren sounds for expander trouble (required for UL installations).
3 = On for Immediate Restore by zone. Off for zones to restore only when siren is off.
4 = On if Dynamic Battery Test performed at arming. Off if performed at disarming. (See location 40)
5 = On if Battery Missing Test is performed every 12 seconds.
6 = On if Manual Bell Test performed during [r]-[4]-[4] test function.
7 = On if Manual Communicator Test performed during [r]-[4]-[4] test function.
8 = On if Box Tamper terminals on the control panel are enabled.
Segment 3:
1 = On if Box Tamper report enabled.
2 = On if AC Fail reporting enabled.
3 = On if Low Battery reporting enabled.
4 = On if Aux. Power Overcurrent report enabled.
5 = On if Siren Supervision report enabled.
6 = On if Telephone Line Cut report enabled.
7 = On if Ground Fault Detection report enabled.
8 = On if Expander Trouble reporting enabled.
Segment 4:
1 = On if Fail To Communicate report enabled.
2 = On if Log Full report enabled.
3 = On if Autotest report enabled.
4 = On if Start/End programming report enabled.
5 = On if End Download report enabled.
6 = On if Sensor Low Battery report enabled.
7 = On if Sensor Missing report enabled.
8 = On if First to Open / Last to Close.
Segment 5:
1 = On enable Lost Clock service light.
2 = On enables Zone Doubling (requires NX-200 Zone Doubling Kit).
3 = On disables On-Board 8 zones.
4 = On will allow two trips on same cross-zone to activate an alarm.
5 = On will not allow zones that are force armed to report bypass.
6 = Reserved.
7 = Use internal crystal for clock.
8 = Disable Temporal Siren on Fire. NOTE: Do NOT disable for UL listed systems.
NX-8V2 Control
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Segment 6:
1 = Enable 2 wire smoke.
2 = Reserved.
3 = Enable for Zone Activity in Hours (not Days)
4 = Enable Daylight Savings Time (DST)
5 = Reserved
6 = On to disable Clean Me report (Default is OFF)
7 = On to disable Start/End Test report (Default is OFF)
8 = On enables Auto LED Extinguish (Default is OFF)
Segment 7:
Reserved
L
38
SWINGER SHUTDOWN COUNT
1 ............ numerical
Location 38 contains the number of trips during an arming cycle that the NX-8V2 will allow before bypassing a zone. The count
determination is described in the Glossary. Factory default is 1.
L
39
KEYPAD SOUNDER CONTROL
1 ............ feature select
Segment 1:
1 = On if keypad sounds for ATelephone Line Cut@ when the system is armed.
2 = On if keypad sounds for ATelephone Line Cut@ when disarmed.
3 = On if keypad sounds upon AC Power Failure.
4 = On if keypad sounds when a Low Battery is detected.
5 = On if keypad sounds during Cross Zone trip time.
6 = On if keypad sounds for zone and box tampers.
7 = Reserved.
8 = On if keypad sounds for expander trouble (required for UL installations).
L
40
SYSTEM TIMERS
14 .......... numerical
Location 40 contains the duration of various system timing functions. Example: If you desire the duration of the Dynamic Battery Test
to be 30 minutes, you should program [3]-[0]-[r] in segment 1 of this location. The [3]-[0] is the number of minutes, and the [r] stores
the data and moves to the next segment of this location.
Segment 1 -
Segment 2 -
Segment 3 -
Segment 4 -
Segment 5 -
Segment 6 -
Segment 7 -
Segment 8 -
Segment 9 -
Dynamic Battery Test duration in minutes, 0-255 minutes
AC Fail report delay in minutes, 0-255 minutes.
Power Up Delay in seconds, 0-60 seconds
Siren Time in minutes, 1-254 minutes.
Telephone Line Cut delay in seconds, 0-255 seconds
Cross Zone time in minutes, 0-255 minutes
Chime time in 50 mS (1/20th second) increments from 0-12 seconds
Dial delay in seconds, 15-255 seconds
Fire Alarm Verification time in seconds, 120-255 seconds
(0 = no test)
(0 = no delay)
(0 = no power up delay)
(0 = no TLM)
(0 = no cross zoning)
(0 = follows zone 255 latched)
(0 = no fire alarm verification)
NOTE: The fire alarm verification feature is not approved for residential use in California
Segment 10 - Listen-In time in seconds, 0-255 seconds
Segment 11 - Zone Activity Monitor feature timed in days, 0 – 255 days
Segments 12-14 Reserved.
(0 = no Listen-In time)
(0 = disabled)
NOTES FOR UL INSTALLATIONS
The "Listen-In" feature cannot be enabled for UL Listed systems.
The "Dynamic Battery Test" feature cannot exceed four (4) hours.
The dial delay shall be set to -0-. (Must be disabled by zone type in Loc 110-169.)
The combined Dial Delay and Entry Delay (loc 24) must not exceed 1 minute for SIA CP-01 requirements.
41
Segment 1:
SPECIAL FEATURES
1 ............ feature select
1 = On enables the 6-digit code option. If 6-digit option is enabled, all arm/disarm codes and the "Go To Program Code" are 6
digits. If this option is enabled, the default user 1 code is [1]-[2]-[3]-[4]-[5]-[6].
NOTE: IF YOU ENABLE THIS OPTION, VERIFY THAT THE "GO TO PROGRAM CODE" IS A SIX-DIGIT CODE
BEFORE EXITING PROGRAMMING.
2 = On requires code entry for [r]-[9]-[8] (perform call back download) and [r]-[9]-[9] (answer incoming call for download)
functions.
3 = Enable Auto Cancel / Abort (Refer to Glossary beginning on page 46)
4 = Enable Walk-Test Mode (Refer to Glossary beginning on page 46)
5 = On enables Auto Force-Arming with keyfob or keyswitch
6 = Reserved.
7 = Reserved.
8 = Reserved. (Do not program!)
20
NX-8V2 Control
Download from Www.Somanuals.com. All Manuals Search And Download.
L
42
GO TO PROGRAM CODE
6.............numerical
Location 42 contains the "Go To Program Code". This location contains either a 4 or 6-digit code. If the 6-digit code option is enabled
in Location 41, THIS CODE MUST CONTAIN SIX (6) DIGITS. If this option is not enabled in location 41, the last 2 segments (digits)
will be ignored. With the NX-8V2 disarmed, the "Go To Program Code" can be used to enter the Program Mode.
43
GO TO PROGRAM CODE PARTITION & AUTHORIZATION
2.............feature select
The "Go To Program Code" can be used as a standard arm/disarm code. When using the code to arm or disarm, the user ID is 255.
(This code may not be changed in the Run Mode.)
Segment 1:
1 = Reserved.
2 = On enables "Go To Program Code" as an arm only code.
3 = On enables "Go To Program Code" as an arm only after closing.
4 = On enables "Go To Program Code" as a master arm/disarm code (can change user codes)
5 = On enables "Go To Program Code" as an arm/disarm code.
6 = On enables "Go To Program Code" to bypass zones.
7 = On enables "Go To Program Code" opening and closing reports.
8 = Reserved.
Segment 2:
1 = On enables the "Go To Program Code" for Partition #1.
2 = On enables the "Go To Program Code" for Partition #2.
3 = On enables the "Go To Program Code" for Partition #3.
4 = On enables the "Go To Program Code" for Partition #4.
5 = On enables the "Go To Program Code" for Partition #5.
6 = On enables the "Go To Program Code" for Partition #6.
7 = On enables the "Go To Program Code" for Partition #7.
8 = On enables the "Go To Program Code" for Partition #8.
L
44
DURESS CODE
6.............numerical
Location 44 contains the "Duress" code. This Location contains either 4 or 6 digits. If the 6-digit code option is enabled in Location 41,
THIS CODE MUST CONTAIN SIX (6) DIGITS. If the 6-digit option is not enabled in location 41, the last 2 digits will be ignored. If the
duress code is programmed, it will work for all partitions.
45
AUXILIARY OUTPUT 1-4 PARTITION SELECTION
4.............feature select
Location 45 is used to select which partition(s) the events must occur in before the output will activate. Location 45 has 4 segments.
Segment 1 corresponds to output 1, and Segment 4 corresponds to output 4.
Segment 1 (Aux 1)
1= Partition 1
2= Partition 2
3= Partition 3
4= Partition 4
5= Partition 5
6= Partition 6
7= Partition 7
8= Partition 8
Segment 2 (Aux 2)
1= Partition 1
2= Partition 2
3= Partition 3
4= Partition 4
5= Partition 5
6= Partition 6
7= Partition 7
8= Partition 8
Segment 3 (Aux 3)
1= Partition 1
2= Partition 2
3= Partition 3
4= Partition 4
5= Partition 5
6= Partition 6
7= Partition 7
8= Partition 8
Segment 4 (Aux 4)
1= Partition 1
2= Partition 2
3= Partition 3
4= Partition 4
5= Partition 5
6= Partition 6
7= Partition 7
8= Partition 8
46
AUXILIARY OUTPUT 1 - 4 SPECIAL TIMING
4.............feature select
Location 46 contains special timing feature activation for the four auxiliary outputs. Segment 1 corresponds to output 1; Segment 4
corresponds to output 4.
Segments 1 - 4:
1 = On if output should be timed in minutes; Off if timed in seconds.
2 = On if output should latch; Off if output should be timed.
3 = On if output should stop timing upon code entry; Off if the output should continue to time upon code entry.
4 = On if output should only activate between the closing and opening time in loc. 52 and 53.
5 = On if output should only activate between the opening and closing time in loc. 52 and 53.
6 = On if output should be inverted (0 volts going to 12 volts when activated).
7 = Reserved.
8 = Reserved.
47
Segment 1:
AUXILIARY OUTPUT 1, EVENT & TIME
Use Table XIII-1 to select the event that will activate Auxiliary Output 1.
2.............numerical
Segment 2:
Program the timing from 0-255 (minutes or seconds, depending on data programmed in Segment 1, Location 46).
Programming a "0" makes the output follow the event.
NX-8V2 Control
21
Download from Www.Somanuals.com. All Manuals Search And Download.
48
Segment 1:
Segment 2:
AUXILIARY OUTPUT 2, EVENT & TIME
Use Table XIII-1 to select the event that will activate Auxiliary Output 2.
Program the timing from 0-255 (minutes or seconds, depending on data programmed in Segment 2, Location 46).
Programming a "0" makes the output follow the event.
2 ............ numerical
49
AUXILIARY OUTPUT 3, EVENT & TIME
2 ............ numerical
Segment 1:
Segment 2:
Use Table XIII-1 to select the event that will activate Auxiliary Output 3.
Program the timing from 0-255 (minutes or seconds, depending on data programmed in Segment 3, Location 46).
Programming a "0" makes the output follow the event.
50
AUXILIARY OUTPUT 4, EVENT & TIME
2 ............ numerical
Segment 1:
Segment 2:
Use Table XIII-1 to select the event that will activate Auxiliary Output 4. .
Program the timing from 0-255 (minutes or seconds, depending on data programmed in Segment 4, Location 46).
Programming a "0" makes the output follow the event.
Table XIII-1 AUXILIARY OUTPUT EVENT SELECTION
DATA
EVENT
Burglary Alarm
DATA
EVENT
DATA
38
39
40
41
42
43
44
45
EVENT
Download In Process
Smoke Power
Short Circuit (Over-current)
Box Tamper
Siren Tamper
/
0
19
20
21
22
23
24
25
26
27
Exit
1 / Fire Alarm
Entry or Exit
Armed State
Disarmed State
Ready
2 / 24 Hour Alarm
3 / Trouble Alarm
4 / Tamper Alarm
5
6
7
8
9
10
Yelping Siren (Burglary)
Temporal Siren (Fire)
Any Siren
Any Bypass
AC Fail
Low Battery
Not Ready
Fire
Any Open
Any Short
Fire Trouble
Chime
Any Fault (Open/ Short on Non-Fire Zone)
Any Alarm
46 /
47
48 /
28 / Expander Trouble
Beeping Keypad
Code Entry (See note below)
Key FOB Function 1
Key FOB Function 2
Always ON
Alarm Flash
Armed Away
Armed Stay
Aux Comm Fail
29
30
31
32
33
34
35
36
37
Dynamic Battery Test Time
Open Period
Closed Period
Listen-In
Line Seizure
˜ /
˜ /
11 / Duress
49
50
51
52
53
54
55
56
12 / Aux 1 Keypad Zone
13 / Aux 2 Keypad Zone
14 / Panic Keypad Zone
15
Keypad Tamper
Ground Start
16 / Autotest
17
18
Fail To Communicate
Telephone Line Fault
Program Mode
Alarm Memory
Entry
(CP-01) Progress Annunciation
˜
/
Events 49 & 50 require one or more of the following to operate: NX-408E, NX-416E, NX-448E wireless receivers, or NX-
1700E card reader
If set to follow condition, these events will be 1 second.
Note: When Event 48 is programmed, it is possible to program a user code's authorization to select which output(s) a particular code
will activate. When LED 8 is on for an authorization, then LEDs 1- 4 correspond to that code activating outputs 1 - 4
respectively. (See programming the LED keypads on page 7.)
L
51
AUTOTEST CONTROL
4 ............ numerical
Segment 1:
Program a "1" if the interval is to be in hours; Program a "0" if in days. Add a A2" to suppress the daily test or a A3" to
suppress the hourly test if any report has been sent.
Segment 2:
Segment 3:
Segment 4:
Program the Autotest interval from 1-255 hours/days.
Program the Autotest report hour in 24-hour format (if the interval is in hours, this segment is ignored).
Program the Autotest report time, number of minutes after the hour.
52
OPENING TIME
2 ............ numerical
Location 52 contains the time in 24 hour format the NX-8V2 enables codes designated as arm only after closing. This time is only valid
on those days programmed in location 54. Note: Opening time must be earlier than closing time for Auto Arm, Aux. Outputs, or Code
Authorization to function properly.
Segment 1:
Segment 2:
Program the hour of the opening time.
Program the minutes after the hour of the opening time.
53
CLOSING TIME/AUTOMATIC ARMING TIME
2 ............ numerical
Location 53 contains the time in 24 hour format the NX-8V2 disables the disarm capability for codes designated as arm only after
closing. This is also the time the Automatic Arming sequence will begin (if enabled in location 55)..
Segment 1:
Segment 2:
Program the hour of the closing / auto arm time.
Program the minutes after the hour of the closing / auto arm time.
22
NX-8V2 Control
Download from Www.Somanuals.com. All Manuals Search And Download.
54
DAYS OF WEEK EACH PARTITION IS OPEN
8.............feature select
Location 54 selects which days of the week each partition is open. On these days, Aarm only after close window@ codes will be able to
arm and disarm during open window. NOTE: If any partition is not programmed to be opened and is programmed to Auto-Arm
(Location 55), the NX-8V2 will try to arm every 45 minutes for the duration of the closed period unless Auto Retry is disabled
in location 55. On days not selected here, Aarm only after close window@ codes will not disarm. Segment 1 is for partition 1, and
segment 8 is for partition 8. (See locations 52 and 53 for the opening and closing times for the open days.)
Segment 1-8:
1 = Open on Sunday.
2 = Open on Monday.
3 = Open on Tuesday.
4 = Open on Wednesday.
5 = Open on Thursday.
6 = Open on Friday.
7 = Open on Saturday.
8 = Reserved.
55
DAYS OF WEEK EACH PARTITION WILL AUTO ARM
8.............feature select
Location 55 selects which days each partition will auto arm. Segment 1 is for partition 1, and segment 8 is for partition 8. If a zone is
faulted when the panel tries to auto arm, the zone will be bypassed.
Segments 1-8:
1 = Auto Arming on Sunday.
2 = Auto Arming on Monday.
3 = Auto Arming on Tuesday.
4 = Auto Arming on Wednesday.
5 = Auto Arming on Thursday.
6 = Auto Arming on Friday.
7 = Auto Arming on Saturday.
8 = Disable 45 minute retry timer.
LOCATIONS 56- 83 ARE ONLY USED WHEN REPORTING EVENTS TO A PAGER OR USING A SLOW FORMAT SUCH AS
4+2. When using Contact ID or SIA, there is no need to program these locations.
The digit programmed in each of the following locations will be sent as the upper HEX digit in place of the alarm event code. The zone
ID or user ID will always be reported as the lower HEX digit (1-F). For example, if the zone ID or user ID is 15, the 4+2 lower digit will
be “F” and if the zone ID or user ID is 16, the 4+2 digit will be “1”. See Appendix 4 on page 53. NOTE: If Segments 2-8 are left as “0”
(unprogrammed), they will follow the Segment 1 selection. If Segment 1 is left as “0” and the feature is enabled in Location 23, the NX-
8V2 will report “A”.
56
RESTORE COMMUNICATOR CODE
8.............numerical
Location 56 contains the event code for any zone "Restore" for a 4+2 format. Refer to the box on page 23.
Segment 1 = Partition 1
Segment 2 = Partition 2
Segment 3 = Partition 3
Segment 4 = Partition 4
Segment 5 = Partition 5
Segment 6 = Partition 6
Segment 7 = Partition 7
Segment 8 = Partition 8
57
BYPASS COMMUNICATOR CODE
8.............numerical
Location 57 contains the event code for a zone "Bypass" for a 4+2 format. Refer to the box on page 23.
Segment 1 = Partition 1
Segment 2 = Partition 2
Segment 3 = Partition 3
Segment 4 = Partition 4
Segment 5 = Partition 5
Segment 6 = Partition 6
Segment 7 = Partition 7
Segment 8 = Partition 8
58
TAMPER COMMUNICATOR CODE
8.............numerical
Location 58 contains the event code for a zone "Tamper" for a 4+2 format. Refer to the box on page 23.
Segment 1 = Partition 1
Segment 2 = Partition 2
Segment 3 = Partition 3
Segment 4 = Partition 4
Segment 5 = Partition 5
Segment 6 = Partition 6
Segment 7 = Partition 7
Segment 8 = Partition 8
59
TROUBLE COMMUNICATOR CODE
8.............numerical
Location 59 contains the event code for a zone "Trouble" for a 4+2 format. Refer to the box on page 23.
Segment 1 = Partition 1
Segment 2 = Partition 2
Segment 3 = Partition 3
Segment 4 = Partition 4
Segment 5 = Partition 5
Segment 6 = Partition 6
Segment 7 = Partition 7
Segment 8 = Partition 8
60
SENSOR LOW BATTERY COMMUNICATOR CODE
8.............numerical
Location 60 contains the event code for a zone "Sensor Low Battery" for a 4+2 format. Refer to the box on page 23.
Segment 1 = Partition 1
Segment 2 = Partition 2
Segment 3 = Partition 3
Segment 4 = Partition 4
Segment 5 = Partition 5
Segment 6 = Partition 6
Segment 7 = Partition 7
Segment 8 = Partition 8
NX-8V2 Control
23
Download from Www.Somanuals.com. All Manuals Search And Download.
SLOW COMMUNICATOR FORMAT CODES
61
SENSOR MISSING COMMUNICATOR CODE
8 ............ numerical
Location 61 contains the event code for a zone "Sensor Missing" for a 4+2 format. Refer to the box on page 23.
Segment 1 = Partition 1
Segment 2 = Partition 2
Segment 3 = Partition 3
Segment 4 = Partition 4
Segment 5 = Partition 5
Segment 6 = Partition 6
Segment 7 = Partition 7
Segment 8 = Partition 8
62
DURESS COMMUNICATOR CODE
2 ............ numerical
Location 62 contains the digits that will be sent for a 4+2 format if the “Duress” code is enabled in location 44. Refer to the box on
page 23.
63
KEYPAD AUXILIARY 1 COMMUNICATOR CODE
2 ............ numerical
Location 63 contains the digits that will be sent for a 4+2 format if the keypad "Auxiliary 1" (Fire) is enabled in the partition feature
selection. Refer to the box on page 23.
64
KEYPAD AUXILIARY 2 COMMUNICATOR CODE
2 ............ numerical
Location 64 contains the digits that will be sent for a 4+2 format if the keypad "Auxiliary 2" (Medical) is enabled in the partition feature
selection. Refer to the box on page 23.
65
KEYPAD PANIC COMMUNICATOR CODE
2 ............ numerical
Location 65 contains the digits that will be sent for a 4+2 format if the keypad "Panic" is enabled in the partition feature selection. Refer
to the box on page 23.
66
KEYPAD MULTIPLE CODE ENTRY TAMPER COMM CODE
2 ............ numerical
Location 66 contains the digits that will be sent for a 4+2 format if the keypad "Multiple Code Entry" (Tamper) is enabled in the partition
feature selection. Refer to the box on page 23.
67
BOX TAMPER / RESTORE COMMUNICATOR CODE
4 ............ numerical
Location 67 contains the digits that will be sent for a 4+2 format if the "Box Tamper" feature is enabled in location 37. Segments 1 & 2
contain the digits of the "Box Tamper". Segments 3 & 4 contain the digits of the "Box Tamper Restore". Refer to the box on page 23.
68
AC FAIL / RESTORE COMMUNICATOR CODE
4 ............ numerical
Location 68 contains the digits for a 4+2 format that will be sent if "AC Fail Reporting" is enabled. Segments 1 & 2 contain the digits of
the "AC Fail". Segments 3 & 4 contain the digits of the "AC Fail Restore". Refer to the box on page 23.
69
LOW BATTERY / RESTORE COMMUNICATOR CODE
4 ............ numerical
Location 69 contains the digits for a 4+2 format that will be sent if "Low Battery Reporting" is enabled. Segments 1 & 2 contain the
digits of the "Low Battery Reporting". Segments 3 & 4 contain the digits of the "Low Battery Restore". Refer to the box on page 23.
70
AUX POWER OVERCURRENT / RESTORE COMM CODE
4 ............ numerical
Location 70 contains the digits for a 4+2 format that will be sent if "Aux Power Overcurrent Reporting" is enabled. Segments 1 & 2
contain the digits of the "Aux Power Overcurrent Reporting". Segments 3 & 4 contain the digits of the "Aux Power Overcurrent
Restore". Refer to the box on page 23.
71
BELL TAMPER / RESTORE COMMUNICATOR CODE
4 ............ numerical
Location 71 contains the digits for a 4+2 format that will be sent if siren supervision reporting is enabled. Segments 1 & 2 contain the
digits of the "Bell Tamper Reporting". Segments 3 & 4 contain the digits of the "Bell Tamper Restore". Refer to the box on page 23.
72
TELEPHONE LINE CUT / RESTORE COMM CODE
4 ............ numerical
Location 72 contains the digits for a 4+2 format that will be sent if "Telephone Line Cut Reporting" is enabled. Segments 1 & 2 contain
the digits of the "Telephone Line Cut Reporting". Segments 3 & 4 contain the digits of the "Telephone Line Cut Restore". Refer to the
box on page 23.
73
GROUND FAULT / RESTORE COMMUNICATOR CODE
4 ............ numerical
Location 73 contains the digits for a 4+2 format that will be sent if "Ground Fault Reporting" is enabled. Segments 1 & 2 contain the
digits of the "Ground Fault Reporting". Segments 3 & 4 contain the digits of the "Ground Fault Restore". Refer to the box on page 23.
74
EXPANDER TROUBLE / RESTORE COMM CODE
4 ............ numerical
Location 74 contains the digits for a 4+2 format that will be sent if "Expander Trouble Reporting" is enabled. Segments 1 & 2 contain
the digits of the "Expander Trouble Reporting". Segments 3 & 4 contain the digits of the "Expander Trouble Restore". Refer to the box
on page 23.
75
FAIL TO COMMUNICATE COMMUNICATOR CODE
2 ............ numerical
Location 75 contains the digits for a 4+2 format that will be sent if the "Fail To Communicate Reporting" is enabled. Refer to the box on
page 23.
76
LOG FULL COMMUNICATOR CODE
2 ............ numerical
Location 76 contains the digits for a 4+2 format if the "Log Full Reporting" is enabled. Refer to the box on page 23.
24
NX-8V2 Control
Download from Www.Somanuals.com. All Manuals Search And Download.
SLOW COMMUNICATOR FORMAT CODES
77
OPENING COMMUNICATOR CODE
8.............numerical
Location 77 contains the digit of a 4+2 format if the "Opening Reporting" is enabled. Refer to the box on page 23.
Segment 1 = Partition 1
Segment 2 = Partition 2
Segment 3 = Partition 3
Segment 4 = Partition 4
Segment 5 = Partition 5
Segment 6 = Partition 6
Segment 7 = Partition 7
Segment 8 = Partition 8
78
CLOSING COMMUNICATOR CODE
8.............numerical
Location 78 contains the digit of a 4+2 format if the "Closing Reporting" is enabled. Refer to the box on page 23.
Segment 1 = Partition 1
Segment 2 = Partition 2
Segment 3 = Partition 3
Segment 4 = Partition 4
Segment 5 = Partition 5
Segment 6 = Partition 6
Segment 7 = Partition 7
Segment 8 = Partition 8
79
AUTOTEST COMMUNICATOR CODE
2.............numerical
Location 79 contains the digits for a 4+2 format that will be sent if the "Autotest" or "Manual Test" is enabled. Refer to the box on page
23.
80
RECENT CLOSING & EXIT ERROR COMM CODE
2.............numerical
Location 80 contains the digits for a 4+2 format that will be sent if "Recent Closing" and/or "Exit Error Reporting" is enabled. Segment
1 contains the digit for the "Recent Closing Reporting". Segment 2 contains the digit for the "Exit Error Reporting". Refer to the box on
page 23.
81
START PROGRAM & END PROGRAM COMM CODES
4.............numerical
Location 81 contains the digits for a 4+2 format that will be sent if "Start / End Programming Reporting" is enabled. Segment 1
contains the digit for the "Start Program Reporting". Segment 2 contains the digit for the "Start Program Reporting". Segment 3
contains the digit for the "End Program Reporting". Segment 4 contains the digit for the "End Program Reporting". Refer to the box on
page 23.
82
END DOWNLOAD COMMUNICATOR CODE
4.............numerical
Location 82 contains the digits for a 4+2 format that will be sent if "End Downloading Reporting" is enabled. Segments 1 and 2 are
Reserved. Segment 3 contains the digit of the "End Download Reporting". Segment 4 contains the digit of the "End Download
Reporting". Refer to the box on page 23. Note: A start download report will be sent to the internal event log.
83
CANCEL COMMUNICATOR CODE
1.............numerical
Location 83 contains the digit for a 4+2 format that will be sent if "Cancel Reporting" is enabled. Segment 1 contains the digit for the
"Cancel Communicator Reporting". Refer to the box on page 23.
84-87
RESERVED
LOCATIONS 88-109 ARE FOR PROGRAMMING DIFFERENT ACCOUNT CODES AND / OR FEATURES FOR EACH
PARTITION. IF A LOCATION IS LEFT UN-PROGRAMMED,
THE FEATURE FOR PARTITION 1 AND ACCOUNT CODE FOR THE PHONE NUMBER WILL BE USED.
88
ACCOUNT CODE FOR PARTITION 1
6.............numerical
Location 88 contains the account code sent when partition 1 is reported. If location 88 is left unprogrammed (all A10"s), then the
account code corresponding to the Phone number dialed will be used. If the account code is less than six digits, program a A10" in
the segment immediately after the last digit of the account code. If the account code is 6 digits long, program all 6 segments.
89
ACCOUNT CODE FOR PARTITION 2
6.............numerical
Location 89 contains the account code sent when partition 2 is reported. If location 89 is left unprogrammed (all A10"s), then the
account code corresponding to the Phone number dialed will be used. If the account code is less than six digits, program a A10"
in the segment immediately after the last digit of the account code. If the account code is 6 digits long program all 6 segments.
90
PARTITION 2 FEATURE AND REPORTING SELECTIONS
5.............feature select
Location 90 is used to enable certain features that can be accessed or are visible to the user from the keypad of the system. In
addition, certain communicator reports are enabled in this location. Each of these features can be enabled by partition. This location
contains 5 segments, with eight possible features per segment. Refer to Location 23 (page 15) for the feature selections. If all
segments are blank (nothing enabled), the features for partition 1 will be used.
91
PARTITION 2 ENTRY EXIT TIMERS
6.............numerical
Location 91 is used to enter in seconds the Entry and Exit times. There are 2 separate entry and exit times. Valid entries are 10-255
seconds. If all segments are A0", the entry and exit times for partition 1 will be used.
Segment 1, Entry time 1: Entry time that will be used when a Delay 1 zone type initiates an entry delay.
Segment 2, Exit time 1: Exit time that will be used for all zones designated as Delay 1.
Segment 3, Entry time 2: Entry time that will be used when a Delay 2 zone type initiates an entry delay.
Segment 4, Exit time 2: Exit time that will be used for all zones designated as Delay 2.
Segments 5 & 6:
Reserved
NX-8V2 Control
25
Download from Www.Somanuals.com. All Manuals Search And Download.
92
ACCOUNT CODE FOR PARTITION 3
6 ............ numerical
The account code sent when partition 3 is reported is programmed in location 92. If location 92 is left unprogrammed (all A10") then
the account code corresponding to the Phone number dialed will be used. If the account code is less than six digits, program a
A10" in the segment immediately after the last digit of the account code. If the account code is 6 digits long program all 6 segments.
93
PARTITION 3 FEATURE & REPORTING SELECTIONS
5 ............ feature select
Location 93 is used to enable certain features that can be accessed or are visible to the user from the keypad of the system. In
addition, certain communicator reports are enabled in this location. Each of these features can be enabled by partition. This location
contains 5 segments, with eight possible features per segment. Refer to Location 23 (page 15) for the feature selections. If all
segments are blank (nothing enabled), the features for partition 1 will be used.
94
PARTITION 3 ENTRY EXIT TIMERS
6 ............ numerical
Location 94 is used to enter in seconds the Entry and Exit times. There are 2 separate entry and exit times. Valid entries are 10-255
seconds. If all segments are A0", the entry and exit times for partition 1 will be used.
Segment 1, Entry time 1: Entry time that will be used when a Delay 1 zone type initiates an entry delay.
Segment 2, Exit time 1: Exit time that will be used for all zones designated as Delay 1.
Segment 3, Entry time 2: Entry time that will be used when a Delay 2 zone type initiates an entry delay.
Segment 4, Exit time 2: Exit time that will be used for all zones designated as Delay 2.
Segments 5 & 6:
Reserved
95
ACCOUNT CODE FOR PARTITION 4
6 ............ numerical
The account code sent when partition 4 is reported is programmed in location 95. If location 95 is left unprogrammed (all A10") then
the account code corresponding to the Phone number dialed will be used. If the account code is less than six digits, program a
A10" in the segment immediately after the last digit of the account code. If the account code is 6 digits long, program all 6 segments.
96
PARTITION 4 FEATURE & REPORTING SELECTIONS
5 ............ feature select
Location 96 is used to enable certain features that can be accessed or are visible to the user from the keypad of the system. In
addition, certain communicator reports are enabled in this location. Each of these features can be enabled by partition. This location
contains 5 segments, with eight possible features per segment. Refer to Location 23 (page 15) for the feature selections. If all
segments are blank (nothing enabled), the features for partition 1 will be used.
97
PARTITION 4 ENTRY EXIT TIMERS
6 ............ numerical
Location 97 is used to enter in seconds the Entry and exit times. There are 2 separate entry and exit times. Valid entries are 10-255
seconds. If all segments are A0", the entry and exit times for partition 1 will be used.
Segment 1, Entry time 1: Entry time that will be used when a Delay 1 zone type initiates an entry delay.
Segment 2, Exit time 1: Exit time that will be used for all zones designated as Delay 1.
Segment 3, Entry time 2: Entry time that will be used when a Delay 2 zone type initiates an entry delay.
Segment 4, Exit time 2: Exit time that will be used for all zones designated as Delay 2.
Segments 5 & 6:
Reserved
98
ACCOUNT CODE FOR PARTITION 5
6 ............ numerical
The account code sent when partition 5 is reported is programmed in location 98. If location 98 is left unprogrammed (all A10") then
the account code corresponding to the Phone number dialed will be used. If the account code is less than six digits, program a
A10" in the segment immediately after the last digit of the account code. If the account code is 6 digits long, program all 6 segments.
99
PARTITION 5 FEATURE & REPORTING SELECTIONS
5 ............ numerical
Location 99 is used to enable certain features that can be accessed or are visible to the user from the keypad of the system. In
addition, certain communicator reports are enabled in this location. Each of these features can be enabled by partition. This location
contains 5 segments, with eight possible features per segment. Refer to Location 23 (page 15) for the feature selections. If all
segments are blank (nothing enabled), the features for partition 1 will be used.
100
PARTITION 5 ENTRY EXIT TIMERS
6 ............ numerical
Location 100 is used to enter in seconds the Entry and exit times. There are 2 separate entry and exit times. Valid entries are 10-255
seconds. If all segments are A0", the entry and exit times for partition 1 will be used.
Segment 1, Entry Time 1:Entry time that will be used when a delay 1 zone type initiates an entry delay.
Segment 2, Exit Time 1: Exit time that will be used for all zones designated as delay 1.
Segment 3, Entry Time 2:Entry time that will be used when a delay 2zone type initiates an entry delay.
Segment 4, Exit Time 2: Exit time that will be used for all zones designated as delay 2.
Segments 5 & 6:
Reserved
101
ACCOUNT CODE FOR PARTITION 6
6 ............ numerical
The account code sent when partition 6 is reported is programmed in location 101. If location 101 is left unprogrammed (all A10")
then the account code corresponding to the Phone number dialed will be used. Program the account code is less than six digits,
program a A10" in the segment immediately after the last digit of the account code. If the account code is 6 digits long, program all 6
segments.
26
NX-8V2 Control
Download from Www.Somanuals.com. All Manuals Search And Download.
102
PARTITION 6 FEATURE & REPORTING SELECTIONS
5.............feature select
Location 102 is used to enable certain features that can be accessed or are visible to the user from the keypad of the system. In
addition, certain communicator reports are enabled in this location. Each of these features can be enabled by partition. This location
contains 5 segments, with eight possible features per segment. Refer to Location 23 (page 15) for the feature selections. If all
segments are blank (nothing enabled), the features for partition 1 will be used.
103
PARTITION 6 ENTRY EXIT TIMERS
6.............numerical
Location 103 is used to enter in seconds the Entry and Exit times. There are 2 separate entry and exit times. Valid entries are 10-255
seconds. If all segments are A0", the entry and exit times for partition 1 will be used.
Segment 1, Entry Time 1:Entry time that will be used when a Delay 1 zone type initiates an entry delay.
Segment 2, Exit Time 1: Exit time that will be used for all zones designated as Delay 1.
Segment 3, Entry Time 2:Entry time that will be used when a Delay 2 zone type initiates an entry delay.
Segment 4, Exit Time 2: Exit time that will be used for all zones designated as Delay 2.
Segments 5 & 6:
Reserved
104
ACCOUNT CODE FOR PARTITION 7
6.............numerical
The account code sent when partition 7 is reported is programmed in location 104. If location 104 is left unprogrammed (all A10")
then the account code corresponding to the Phone number dialed will be used. If the account code is less than six digits,
program a A10" in the segment immediately after the last digit of the account code. If the account code is 6 digits long, program all 6
segments.
105
PARTITION 7 FEATURE & REPORTING SELECTIONS
5.............feature select
Location 105 is used to enable certain features that can be accessed or are visible to the user from the keypad of the system. In
addition, certain communicator reports are enabled in this location. Each of these features can be enabled by partition. This location
contains 5 segments, with eight possible features per segment. Refer to Location 23 (page 15) for the feature selections. If all
segments are blank (nothing enabled), the features for partition 1 will be used.
106
PARTITION 7 ENTRY EXIT TIMERS
6.............numerical
Location 106 is used to enter in seconds the Entry and Exit times. There are 2 separate entry and exit times. Valid entries are 10-255
seconds. If all segments are A0", the entry and exit times for partition 1 will be used.
Segment 1, Entry Time 1:Entry time that will be used when a Delay 1 zone type initiates an entry delay.
Segment 2, Exit Time 1: Exit time that will be used for all zones designated as Delay 1.
Segment 3, Entry Time 2:Entry time that will be used when a Delay 2 zone type initiates an entry delay.
Segment 4, Exit Time 2: Exit time that will be used for all zones designated as Delay 2.
Segments 5 & 6:
Reserved
107
ACCOUNT CODE FOR PARTITION 8
6.............numerical
The account code sent when partition 8 is reported is programmed in location 107. If location 107 is left unprogrammed (all A10")
then the account code corresponding to the Phone number dialed will be used. If the account code is less than six digits,
program a A10" in the segment immediately after the last digit of the account code. If the account code is 6 digits long, program all 6
segments.
108
PARTITION 8 FEATURE & REPORTING SELECTIONS
5.............feature selecti
Location 108 is used to enable certain features that can be accessed or are visible to the user from the keypad of the system. In
addition, certain communicator reports are enabled in this location. Each of these features can be enabled by partition. This location
contains 5 segments, with eight possible features per segment. Refer to Location 23 (pg 15) for the feature selections. If all segments
are blank (nothing enabled), the features for partition 1 will be used.
109
PARTITION 8 ENTRY EXIT TIMERS
6.............numerical
Location 109 is used to enter in seconds the Entry and Exit times. There are 2 separate entry and exit times. Valid entries are 10-255
seconds. If all segments are A0", the entry and exit times for partition 1 will be used.
Segment 1, Entry Time 1:Entry time that will be used when a Delay 1 zone type initiates an entry delay.
Segment 2, Exit Time 1: Exit time that will be used for all zones designated as Delay 1.
Segment 3, Entry Time 2:Entry time that will be used when a Delay 2 zone type initiates an entry Delay.
Segment 4, Exit Time 2: Exit time that will be used for all zones designated as Delay 2.
Segments 5 & 6:
Reserved
NX-8V2 Control
27
Download from Www.Somanuals.com. All Manuals Search And Download.
LOCATIONS 110-169 ARE USED TO CHANGE THE ZONE TYPES (Configurations) AS LISTED IN THE TABLE ON PAGE 16.
THESE LOCATIONS ARE CONSIDERED ADVANCED PROGRAMMING AND SHOULD ONLY BE CHANGED WITH ATHOROUGH
UNDERSTANDING OF THE OPERATION OF EACH BIT.
110
ZONE TYPE 1 ALARM EVENT CODE
1 ............ numerical
Location 110 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen from the list on
page 16. The zone ID will be that zone that is in alarm.
4+2 Format Note: If 4+2 format is being used, the number programmed in this location will be sent as the upper hex digit. The digit in
location 110 should be from 1 to 15 when using 4+2 formats. The zone ID or user ID will be the lower hex digit of the zone that is in
alarm.
111
Segment 1:
ZONE TYPE 1 CHARACTERISTIC SELECT
5 ............ feature select
1 = Fire (turn on if this is a fire zone).
2 = 24 hour (turn on for non-fire 24 hour zones).
3 = Keyswitch zone. (normally open switch)
4 = Follower (turn on for burglary zones that are Instant during non-entry times).
5 = Delay 1 zone (follows timer 1 entry and exit times).
6 = Delay 2 zone (follows timer 2 entry and exit times).
7 = Interior (turn on if this zone should Automatically Bypass or Bypass for Stay Arming).
8 = Local only (turn on if this zone should not be reported).
Segment 2:
1 = On if Zone Type will beep the keypad for alarm.
2 = On if Zone Type will sound the yelping siren for alarm.
3 = On if Zone Type will sound the temporal siren for alarm.
4 = On if Zone Type will chime.
5 = On if Zone Type can be bypassed.
6 = On if Zone Type is included in the group shunt.
7 = On if Zone Type is force armable.
8 = On if Zone Type is entry guard.
Segment 3:
On enables Fast Loop Response. (50mS)- Off= 500mS
1-
2-
3-
4-
5-
6-
7-
8-
On enables Double End Of Line Tamper zone. (Mainly used for tamper on wireless zones)
On enables Trouble Reporting zone. (Day zone and Fire zones)
On if Zone Type is a Cross Zone.
On enables Dialer Delay zone. (See location 40, page 20)
On if Zone Type will swinger shutdown. (See location 38, page 20)
On enables Restore reporting.
On enables Listen-In. (See location 40, page 20)
Segment 4:
1 = On enables Zone Activity Monitor. (See location 40, page 20)
2 = On enables End of Line Resistor Defeat on Non-Fire/Non-Keyswitch zones.
3 = On enables zone to act as request to exit input / disables for alarm activation.
4 = On enables zone to act as access entry point (Refer to NX-1700E card reader instruction manual. Do not enable this segment
unless configured with Access Control.)
5-8 = Reserved.
Segment 5:
Reserved.
112
ZONE TYPE 2 ALARM EVENT CODE
1 ............ numerical
Location 112 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen from the list on
page 50. The zone ID will be that zone that is in alarm. If 4+2 format is being used, refer to Location 110 on page 28 for details.
113
ZONE TYPE 2 CHARACTERISTIC SELECT
5 ............ feature select
Use "Zone Type Characteristic Selections" described in Location 111, page 28
114
ZONE TYPE 3 ALARM EVENT CODE
1 ............ numerical
Location 114 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen from the list on
page 50. The zone ID will be that zone that is in alarm. If 4+2 format is being used, refer to Location 110 on page 28 for details.
115
ZONE TYPE 3 CHARACTERISTIC SELECT
5 ............ feature select
Use "Zone Type Characteristic Selections" described in Location 111, page 28
28
NX-8V2 Control
Download from Www.Somanuals.com. All Manuals Search And Download.
116
ZONE TYPE 4 ALARM EVENT CODE
1.............numerical
Location 116 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen from the list on
page 50. The zone ID will be that zone that is in alarm. If 4+2 format is being used, refer to Location 110 on page 28 for details.
117
ZONE TYPE 4 CHARACTERISTIC SELECT
5.............feature select
Use "Zone Type Characteristic Selections" described in Location 111, page 28
118
ZONE TYPE 5 ALARM EVENT CODE
1.............numerical
Location 118 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen from the list on
page 50. The zone ID will be that zone that is in alarm. If 4+2 format is being used, refer to Location 110 on page 28 for details.
119
ZONE TYPE 5 CHARACTERISTIC SELECT
5.............feature select
Use "Zone Type Characteristic Selections" described in Location 111, page 28
120
ZONE TYPE 6 ALARM EVENT CODE
1.............numerical
Location 120 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen from the list on
page 50. The zone ID will be that zone that is in alarm. If 4+2 format is being used, refer to Location 110 on page 28 for details.
121
ZONE TYPE 6 CHARACTERISTIC SELECT
5.............feature select
Use "Zone Type Characteristic Selections" described in Location 111, page 28
122
ZONE TYPE 7 ALARM EVENT CODE
1.............numerical
Location 122 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen from the list on
page 50. The zone ID will be that zone that is in alarm. If 4+2 format is being used, refer to Location 110 on page 28 for details.
123
ZONE TYPE 7 CHARACTERISTIC SELECT
5.............feature select
Use "Zone Type Characteristic Selections" described in Location 111, page 28
124
ZONE TYPE 8 ALARM EVENT CODE
1.............numerical
Location 124 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen from the list on
page 50. The zone ID will be that zone that is in alarm. If 4+2 format is being used, refer to Location 110 on page 28 for details.
125
ZONE TYPE 8 CHARACTERISTIC SELECT
5.............feature select
Use "Zone Type Characteristic Selections" described in Location 111, page 28
126
ZONE TYPE 9 ALARM EVENT CODE
1.............numerical
Location 126 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen from the list on
page 50. The zone ID will be that zone that is in alarm. If 4+2 format is being used, refer to Location 110 on page 28 for details.
127
ZONE TYPE 9 CHARACTERISTIC SELECT
5.............feature select
Use "Zone Type Characteristic Selections" described in Location 111, page 28.
128
ZONE TYPE 10 ALARM EVENT CODE
1.............numerical
Location 128 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen from the list on
page 50. The zone ID will be that zone that is in alarm. If 4+2 format is being used, refer to Location 110 on page 28 for details.
129
ZONE TYPE 10 CHARACTERISTIC SELECT
5.............feature select
Use "Zone Type Characteristic Selections" described in Location 111, page 28
130
ZONE TYPE 11 ALARM EVENT CODE
1.............numerical
Location 130 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen from the list on
page 50. The zone ID will be that zone that is in alarm. If 4+2 format is being used, refer to Location 110 on page 28 for details.
131
ZONE TYPE 11 CHARACTERISTIC SELECT
5.............feature select
Use "Zone Type Characteristic Selections" described in Location 111, page 28
132
ZONE TYPE 12 ALARM EVENT CODE
1.............numerical
Location 132 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen from the list on
page 50. The zone ID will be that zone that is in alarm. If 4+2 format is being used, refer to Location 110 on page 28 for details.
133
ZONE TYPE 12 CHARACTERISTIC SELECT
5.............feature select
Use "Zone Type Characteristic Selections" described in Location 111, page 28
134
ZONE TYPE 13 ALARM EVENT CODE
1.............numerical
Location 134 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen from the list on
page 50. The zone ID will be that zone that is in alarm. If 4+2 format is being used, refer to Location 110 on page 28 for details.
135
ZONE TYPE 13 CHARACTERISTIC SELECT
5.............feature select
29
Use "Zone Type Characteristic Selections" described in Location 111, page 28
NX-8V2 Control
Download from Www.Somanuals.com. All Manuals Search And Download.
136
ZONE TYPE 14 ALARM EVENT CODE
1 ............ numerical
Location 136 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen from the list on
page 50. The zone ID will be that zone that is in alarm. If 4+2 format is being used, refer to Location 110 on page 28 for details.
137
ZONE TYPE 14 CHARACTERISTIC SELECT
5 ............ feature select
Use "Zone Type Characteristic Selections" described in Location 111, page 28
138
ZONE TYPE 15 ALARM EVENT CODE
1 ............ numerical
Location 138 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen from the list on
page 50. The zone ID will be that zone that is in alarm. If 4+2 format is being used, refer to Location 110 on page 28 for details.
139
ZONE TYPE 15 CHARACTERISTIC SELECT
5 ............ feature select
Use "Zone Type Characteristic Selections" described in Location 111, page 28
140
ZONE TYPE 16 ALARM EVENT CODE
1 ............ numerical
Location 140 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen from the list on
page 50. The zone ID will be that zone that is in alarm. If 4+2 format is being used, refer to Location 110 on page 28 for details.
141
ZONE TYPE 16 CHARACTERISTIC SELECT
5 ............ feature select
Use "Zone Type Characteristic Selections" described in Location 111, page 28
142
ZONE TYPE 17 ALARM EVENT CODE
1 ............ numerical
Location 142 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen from the list on
page 50. The zone ID will be that zone that is in alarm. If 4+2 format is being used, refer to Location 110 on page 28 for details.
143
ZONE TYPE 17 CHARACTERISTIC SELECT
5 ............ feature select
Use "Zone Type Characteristic Selections" described in Location 111, page 28
144
ZONE TYPE 18 ALARM EVENT CODE
1 ............ numerical
Location 144 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen from the list on
page 50. The zone ID will be that zone that is in alarm. If 4+2 format is being used, refer to Location 110 on page 28 for details.
145
ZONE TYPE 18 CHARACTERISTIC SELECT
5 ............ feature select
Use "Zone Type Characteristic Selections" described in Location 111, page 28
146
ZONE TYPE 19 ALARM EVENT CODE
1 ............ numerical
Location 146 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen from the list on
page 50. The zone ID will be that zone that is in alarm. If 4+2 format is being used, refer to Location 110 on page 28 for details.
147
ZONE TYPE 19 CHARACTERISTIC SELECT
5 ............ feature select
Use "Zone Type Characteristic Selections" described in Location 111, page 28
148
ZONE TYPE 20 ALARM EVENT CODE
1 ............ numerical
Location 148 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen from the list on
page 50. The zone ID will be that zone that is in alarm. If 4+2 format is being used, refer to Location 110 on page 28 for details.
149
ZONE TYPE 20 CHARACTERISTIC SELECT
5 ............ feature select
Use "Zone Type Characteristic Selections" described in Location 111, page 28
150
ZONE TYPE 21 ALARM EVENT CODE
1 ............ numerical
Location 150 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen from the list on
page 50. The zone ID will be that zone that is in alarm. If 4+2 format is being used, refer to Location 110 on page 28 for details.
151
ZONE TYPE 21 CHARACTERISTIC SELECT
5 ............ feature select
Use "Zone Type Characteristic Selections" described in Location 111, page 28
152
ZONE TYPE 22 ALARM EVENT CODE
1 ............ numerical
Location 152 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen from the list on
page 50. The zone ID will be that zone that is in alarm. If 4+2 format is being used, refer to Location 110 on page 28 for details.
153
ZONE TYPE 22 CHARACTERISTIC SELECT
5 ............ feature select
Use "Zone Type Characteristic Selections" described in Location 111, page 28
154
ZONE TYPE 23 ALARM EVENT CODE
1 ............ numerical
Location 154 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen from the list on
page 50. The zone ID will be that zone that is in alarm. If 4+2 format is being used, refer to Location 110 on page 28 for details.
155
ZONE TYPE 23 CHARACTERISTIC SELECT
5 ............ feature select
NX-8V2 Control
Use "Zone Type Characteristic Selections" described in Location 111, page 28
30
Download from Www.Somanuals.com. All Manuals Search And Download.
156
ZONE TYPE 24 ALARM EVENT CODE
1.............numerical
Location 156 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen from the list on
page 50. The zone ID will be that zone that is in alarm. If 4+2 format is being used, refer to Location 110 on page 28 for details.
157
ZONE TYPE 24 CHARACTERISTIC SELECT
5.............feature select
Use "Zone Type Characteristic Selections" described in Location 111, page 28
158
ZONE TYPE 25 ALARM EVENT CODE
1.............numerical
Location 158 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen from the list on
page 50. The zone ID will be that zone that is in alarm. If 4+2 format is being used, refer to Location 110 on page 28 for details.
159
ZONE TYPE 25 CHARACTERISTIC SELECT
5.............feature select
Use "Zone Type Characteristic Selections" described in Location 111, page 28
160
ZONE TYPE 26 ALARM EVENT CODE
1.............numerical
Location 160 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen from the list on
page 50. The zone ID will be that zone that is in alarm. If 4+2 format is being used, refer to Location 110 on page 28 for details.
161
ZONE TYPE 26 CHARACTERISTIC SELECT
5.............feature select
Use "Zone Type Characteristic Selections" described in Location 111, page 28
162
ZONE TYPE 27 ALARM EVENT CODE
1.............numerical
Location 162 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen from the list on
page 50. The zone ID will be that zone that is in alarm. If 4+2 format is being used, refer to Location 110 on page 28 for details.
163
ZONE TYPE 27 CHARACTERISTIC SELECT
5.............feature select
Use "Zone Type Characteristic Selections" described in Location 111, page 28
164
ZONE TYPE 28 ALARM EVENT CODE
1.............numerical
Location 164 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen from the list on
page 50. The zone ID will be that zone that is in alarm. If 4+2 format is being used, refer to Location 110 on page 28 for details.
165
ZONE TYPE 28 CHARACTERISTIC SELECT
5.............feature select
Use "Zone Type Characteristic Selections" described in Location 111, page 28
166
ZONE TYPE 29 ALARM EVENT CODE
1.............numerical
Location 166 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen from the list on
page 50. The zone ID will be that zone that is in alarm. If 4+2 format is being used, refer to Location 110 on page 28 for details.
167
ZONE TYPE 29 CHARACTERISTIC SELECT
5.............feature select
Use "Zone Type Characteristic Selections" described in Location 111, page 28
168
ZONE TYPE 30 ALARM EVENT CODE
1.............numerical
Location 168 contains the event code sent for a Contact ID or SIA report. The desired event code should be chosen from the list on
page 50. The zone ID will be that zone that is in alarm. If 4+2 format is being used, refer to Location 110 on page 28 for details.
169
ZONE TYPE 30 CHARACTERISTIC SELECT
5.............feature select
Use "Zone Type Characteristic Selections" described in Location 111, page 28
170-205
206
RESERVED
AUTO DISARM DAY SELECTION
8.............feature select
Location 206 selects which days each partition will auto disarm. Segment 1 is for partition 1, and segment 8 is for partition 8. If a zone
is faulted when the panel tries to auto disarm, the zone will be bypassed.
Segments 1-8:
1 = Auto Disarming on Sunday.
2 = Auto Disarming on Monday.
3 = Auto Disarming on Tuesday.
4 = Auto Disarming on Wednesday.
5 = Auto Disarming on Thursday.
6 = Auto Disarming on Friday.
7 = Auto Disarming on Saturday.
8 = Reserved.
NX-8V2 Control
31
Download from Www.Somanuals.com. All Manuals Search And Download.
XIV.
PROGRAMMING WORKSHEETS
(Factory defaults for segments are in bold italics text and "Quick Start" locations are identified with the Lsymbol.)
LOC
PG
DESCRIPTION
DEFAULT
PROGRAM DATA
L
0
11 PHONE 1
14-14-14-14-14-14-14-14-14-14- __ __ __ __ __ __ __ __ __ __
14-14-14-14-14-14-14-14-14-14 __ __ __ __ __ __ __ __ __ __
L
L
L
1
2
3
11 PHONE 1, ACCOUNT CODE
11 PHONE 1, REPORTING FORMAT
12 PHONE 1, DIAL ATTEMPTS
BACKUP CONTROL
10 - 10 - 10 - 10 - 10 - 10
_ _ _ _ _ _
0
8
0
_
_
_
4
12 PHONE 1, SELECTING EVENTS TO REPORT TO PHONE 1
Segment 1 (Circle Numbers To Program)
1 = Alarms and Restores
2 = Open/Close
Segment 2 (Circle Numbers To Program)
1 = Tampers
2 = Short Circuit & Ground Fault
3 = Sensor Lost
3 = Bypass
4 = Zone Trouble
4 = Sensor Low Battery
5 = Expander Trouble
6 = Failure To Communicate
7 = Zone Activity Monitor
8 = Reserved
5 = Power Trouble (AC Failure or Low Battery)
6 = Siren & Telephone Fault
7 = Test Reports
8 = Program, Download, & Log Full
5
6
12 PHONE 1, SELECTING WHICH PARTITIONS REPORT TO PHONE 1
Segment 1 (Circle Numbers To Program)
1 = Partition 1
2 = Partition 2
3 = Partition 3
4 = Partition 4
5 = Partition 5
6 = Partition 6
7 = Partition 7
8 = Partition 8
L
12 PHONE 2
14-14-14-14-14-14-14-14-14-14- __ __ __ __ __ __ __ __ __ __
14-14-14-14-14-14-14-14-14-14 __ __ __ __ __ __ __ __ __ __
L
L
7
8
9
12 PHONE 2, ACCOUNT CODE
13 PHONE 2, REPORTING FORMAT
13 PHONE 2, DIAL ATTEMPTS
BACKUP CONTROL
10 - 10 - 10 - 10 - 10 - 10
_ _ _ _ _ _
0
8
0
_
_
_
10
13 PHONE 2, SELECTING EVENTS TO REPORT TO PHONE 2
Segment 1 (Circle Numbers To Program)
1 = Alarms and Restores
2 = Open/Close
Segment 2 (Circle Numbers To Program)
1 = Tampers
2 = Short Circuit & Ground Fault
3 = Sensor Lost
3 = Bypass
4 = Zone Trouble
4 = Sensor Low Battery
5 = Expander Trouble
6 = Failure To Communicate
7 = Zone Activity Monitor
8 = Reserved
5 = Power Trouble (AC Failure or Low Battery)
6 = Siren & Telephone Fault
7 = Test Reports
8 = Program, Download, & Log Full
11
12
13 PHONE 2, SELECTING WHICH PARTITIONS REPORT TO PHONE 2
Segment 1 (Circle Numbers To Program)
1 = Partition 1
2 = Partition 2
3 = Partition 3
4 = Partition 4
5 = Partition 5
6 = Partition 6
7 = Partition 7
8 = Partition 8
13 PHONE 3
14-14-14-14-14-14-14-14-14-14- __ __ __ __ __ __ __ __ __ __
14-14-14-14-14-14-14-14-14-14 __ __ __ __ __ __ __ __ __ __
13
14
15
14 PHONE 3, ACCOUNT CODE
10 - 10 - 10 - 10 - 10 - 10
_ _ _ _ _ _
14 PHONE 3, REPORTING FORMAT
14 PHONE 3, DIAL ATTEMPTS
BACKUP CONTROL
0
8
0
_
_
_
16
14 PHONE 3, SELECTING EVENTS TO REPORT TO PHONE 3
Segment 1 (Circle Numbers To Program)
1 = Alarms and Restores
2 = Open/Close
Segment 2 (Circle Numbers To Program)
1 = Tampers
2 = Short Circuit & Ground Fault
3 = Sensor Lost
3 = Bypass
4 = Zone Trouble
4 = Sensor Low Battery
5 = Expander Trouble
6 = Failure To Communicate
7 = Zone Activity Monitor
8 = Reserved
5 = Power Trouble (AC Failure or Low Battery)
6 = Siren & Telephone Fault
7 = Test Reports
8 = Program, Download, & Log Full
32
NX-8V2 Control
Download from Www.Somanuals.com. All Manuals Search And Download.
LOC
PG
DESCRIPTION
DEFAULT
PROGRAM DATA
17
14 PHONE 3, SELECTING WHICH PARTITIONS REPORT TO PHONE 3
Segment 1 (Circle Numbers To Program)
1 = Partition 1
2 = Partition 2
3 = Partition 3
4 = Partition 4
5 = Partition 5
6 = Partition 6
7 = Partition 7
8 = Partition 8
18
15 FORMAT OVERRIDE
Segment 1 (Circle Numbers To Program)
1 = ON - 1800hz transmit; OFF - 1900hz
2 = ON - 2300hz handshake; OFF - 1400hz.
3 = ON - cksum parity; OFF - double round parity
4 = ON - 2 digit event code; OFF - 1 digit code
5 = Reserved.
Segment 2 (Circle Numbers To Program)
1 = ON - pager format (no handshake required)
2 = ON - 1400/2300 handshake
3 = Reserved
4 = Reserved
5 = ON - Contact ID
6 = Reserved.
6 = ON - SIA
7 = ON - 20 p.p.s.; OFF - 10 or 40 p.p.s.
8 = ON - 10 p.p.s.; OFF - 20 or 40 p.p.s.
Segments 3 & 4 RESERVED
7 = ON - Contact ID or 4+3
8 = ON - DTMF
L
L
L
19
20
21
15 DOWNLOAD ACCESS CODE
15 RINGS TO ANSWER DOWNLOAD
15 DOWNLOAD CONTROL
8-4-8-0-0-0-0-0
8
_ _ _ _ _ _ _ _
_
Segment 1 (Circle Numbers To Program)
1 = Enables two call answering machine defeat
2 = Enables tone sniff answering machine defeat
3 = Requires callback before downloading
4 = Shutdown control panel
5 = Lock out local programming
6 = Lock out communicator programming
7 = Lock out download section
8 = Enables callback at autotest interval
15 CALLBACK PHONE NUMBER
L
L
22
23
14-14-14-14-14-14-14-14-14-14- __ __ __ __ __ __ __ __ __ __
14-14-14-14-14-14-14-14-14-14 __ __ __ __ __ __ __ __ __ __
15 PARTITION 1, FEATURE SELECTION
Segment 1 (Circle Numbers To Program)
1 = Quick Arm
5 = Audible Panic
6 = Auxiliary 1
2 = Re-Exit
3 = Auto Bypass
7 = Auxiliary 2
4 = Silent Panic
8 = Multi Keypress Tamper
Segment 2 (Circle Numbers To Program)
1 = LED extinguish enable
2 = Require user code for bypassing zones
3 = Bypass sounder alert
4 = AC power/low battery sounder alert
Segment 3 (Circle Numbers To Program)
1 = Open/Close
5 = Enables bypass toggle
6 = Enables silent auto arm
7 = Enables automatic instant
8 = Enables Instant mode toggle
5 = Tamper
2 = Bypass
6 = Cancel
3 = Restore
4 = Trouble
7 = Recent Closing
8 = Exit Error
Segment 4 (Circle Numbers To Program)
1 = Late to Close / Early to Open
2 = Auto Arm in Stay Mode
3 = Disables door delays in Night mode
4 = Bypass Disabled for Force Arm zones
Segment 5 RESERVED
L
24
25
16 ENTRY / EXIT TIMERS
Segment 1 (Entry Time 1)
Segment 2 (Exit Time 1)
30
60
30
Segment 3 (Entry Time 2)
Segment 4 (Exit Time 2)
Segments 5 & 6
60
Reserved
3-5-6-6-6-6-6-6
L
17 ZONES 1-8, ZONE TYPES
_ _ _ _ _ _ _ _
NX-8V2 Control
33
Download from Www.Somanuals.com. All Manuals Search And Download.
LOC
26
PG
DESCRIPTION
DEFAULT
PROGRAM DATA
17 ZONES 1-8, PARTITION SELECTION (Segment 1=Zone 1 thru Segment 8=Zone 8)
Segments
Partition 1
Partition 2
Partition 3
Partition 4
Partition 5
Partition 6
Partition 7
Partition 8
1
1
2
3
4
5
6
7
8
2
1
2
3
4
5
6
7
8
3
1
2
3
4
5
6
7
8
4
1
2
3
4
5
6
7
8
5
1
2
3
4
5
6
7
8
6
1
2
3
4
5
6
7
8
7
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
8
L
27
28
18 ZONES 9-16, ZONE TYPES
18 ZONES 9-16, PARTITION SELECTION (Segment 1=Zone 9 thru Segment 8=Zone 16)
6-6-6-6-6-6-6-6
_ _ _ _ _ _ _ _
Segments
Partition 1
Partition 2
Partition 3
Partition 4
Partition 5
Partition 6
Partition 7
Partition 8
1
1
2
3
4
5
6
7
8
2
1
2
3
4
5
6
7
8
3
1
2
3
4
5
6
7
8
4
1
2
3
4
5
6
7
8
5
1
2
3
4
5
6
7
8
6
1
2
3
4
5
6
7
8
7
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
8
L
29
30
18 ZONES 17-24, ZONE TYPES
18 ZONES 17-24, PARTITION SELECTION (Segment 1=Zone 17 thru Segment 8=Zone 24)
6-6-6-6-6-6-6-6
_ _ _ _ _ _ _ _
Segments
Partition 1
Partition 2
Partition 3
Partition 4
Partition 5
Partition 6
Partition 7
Partition 8
1
1
2
3
4
5
6
7
8
2
1
2
3
4
5
6
7
8
3
1
2
3
4
5
6
7
8
4
1
2
3
4
5
6
7
5
1
2
3
4
5
6
7
8
6
1
2
3
4
5
6
7
8
7
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
8
8
31
32
18 ZONES 25-32, ZONE TYPES
18 ZONES 25-32, PARTITION SELECTION (Segment 1=Zone 25 thru Segment 8=Zone 32)
6-6-6-6-6-6-6-6
_ _ _ _ _ _ _ _
L
L
L
Segments
Partition 1
Partition 2
Partition 3
Partition 4
Partition 5
Partition 6
Partition 7
Partition 8
1
1
2
3
4
5
6
7
8
2
1
2
3
4
5
6
7
8
3
1
2
3
4
5
6
7
8
4
1
2
3
4
5
6
7
5
1
2
3
4
5
6
7
8
6
1
2
3
4
5
6
7
8
7
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
8
8
33
34
18 ZONES 33-40, ZONE TYPES
18 ZONES 33-40, PARTITION SELECTION (Segment 1=Zone 33 thru Segment 8=Zone 40)
6-6-6-6-6-6-6-6
_ _ _ _ _ _ _ _
Segments
Partition 1
Partition 2
Partition 3
Partition 4
Partition 5
Partition 6
Partition 7
Partition 8
1
1
2
3
4
5
6
7
8
2
1
2
3
4
5
6
7
8
3
1
2
3
4
5
6
7
8
4
1
2
3
4
5
6
7
8
5
1
2
3
4
5
6
7
8
6
1
2
3
4
5
6
7
8
7
1
2
3
4
5
6
7
8
8
1
2
3
4
5
6
7
8
35
36
18 ZONES 41-48, ZONE TYPES
19 ZONES 41-48, PARTITION SELECTION (Segment 1=Zone 41 thru Segment 8=Zone 48)
6-6-6-6-6-6-6-6
_ _ _ _ _ _ _ _
Segments
Partition 1
Partition 2
Partition 3
Partition 4
Partition 5
Partition 6
Partition 7
Partition 8
1
1
2
3
4
5
6
7
8
2
1
2
3
4
5
6
7
8
3
1
2
3
4
5
6
7
8
4
1
2
3
4
5
6
7
8
5
1
2
3
4
5
6
7
8
6
1
2
3
4
5
6
7
8
7
1
2
3
4
5
6
7
8
8
1
2
3
4
5
6
7
8
34
NX-8V2 Control
Download from Www.Somanuals.com. All Manuals Search And Download.
LOC
37
PG
19
DESCRIPTION
SIREN AND SYSTEM SUPERVISION
Segment 1 (Circle Numbers To Program)
DEFAULT
PROGRAM DATA
L
1 = Siren sounds for telephone line cut while armed.
2 = Siren sounds for telephone line cut while disarmed.
3 = Siren blast at arming.
4 = Siren blast at exit delay expiration.
5 = Siren blast at closing kissoff.
6 = Siren sounds during a cross-zone verification time.
7 = Siren sounds for a tamper.
8 = Siren blast one time for keyswitch arming, two times for disarming. (Note: Must be disabled for SIA CP-01 installations.)
Segment 2 (Circle Numbers To Program)
1 = Convert siren driver to voltage out.
2 = Siren sounds for expander trouble (required for U.L.).
3 = Immediate Restore by zone.
4 = Dynamic battery test performed upon arming.
5 = Battery missing test performed every 12 seconds.
6 = Manual bell test performed during [r]-[4]-[4] test function.
7 = Manual communicator test performed during [r]-[4]-[4] test function.
8 = Box tamper enabled.
Segment 3 (Circle numbers to program)
1 = Box Tamper report enabled.
2 = AC Fail report enabled.
3 = Low Battery report enabled.
4 = Auxiliary power over current report enabled.
5 = Siren supervision report enabled.
6 = Telephone Line Cut report enabled.
7 = Ground Fault Detection report enabled.
8 = Expander trouble report enabled.
Segment 4 (Circle Numbers To Program)
1 = Failure To Communicate report enabled.
2 = Log Full report enabled.
3 = Autotest report enabled.
4 = Start and End Programming report enabled.
5 = End Download report enabled.
6 = Sensor Low Battery report enabled.
7 = Sensor Missing report enabled.
8 = First to Open / Last to Close enabled.
Segment 5 (Circle numbers to program)
1 = Lost Clock service LED enable.
2 = Zone Doubling enable.
3 = Disable on-board eight zones.
4 = Enables two trips on the same cross-zone to activate the alarm.
5 = Disables bypass reports for force armed zones
6 = Reserved.
7 = Clock uses internal crystal.
8 = Disable Temporal Siren on Fire (Do not disable on UL listed systems)
Segment 6 (Circle numbers to program)
1 = Enable 2-wire Smoke Detector.
2 = Reserved.
3 = Enable Zone Activity in Hours (not Days)
4 = Enable Daylight Savings Time (DST)
5 = Reserved
6 = Disable Clean Me report
7 = Disable Start/End Test report
8 = Enables Auto LED Extinguish
Segment 7 - RESERVED
38
20
SWINGER SHUTDOWN COUNT
1
_
L
NX-8V2 Control
35
Download from Www.Somanuals.com. All Manuals Search And Download.
LOC
39
PG
20
DESCRIPTION
KEYPAD SOUNDER
Segment 1 (Circle numbers to program)
DEFAULT
PROGRAM DATA
L
1 = Keypad sounds for Telephone Line Cut when in the Armed state.
2 = Keypad sounds for Telephone Line Cut when in the Disarmed state.
3 = Keypad sounds upon AC Power Failure.
4 = Keypad sounds upon Low Battery Detection.
5 = Keypad sounds during Cross Zone Trip Time.
6 = Keypad sounds for Tamper Alarm.
7 = Reserved.
8 = Keypad sounds for expander trouble (required for UL).
40
20
SYSTEM TIMERS
L
Segment 1 Dynamic Battery Test duration (0-255 minutes)
Segment 2 AC Failure report delay (0-255 minutes)
Segment 3 Power Up Delay (0-60 seconds)
Segment 4 Siren Time (1-254 minutes)
Segment 5 Telephone Line Cut delay (0-255 seconds)
Segment 6 Cross Zone Time (0-255 minutes)
Segment 7 Chime Time in 50 mS increments (0-255)
Segment 8 Dialer delay (15-255 seconds)
Segment 9 Fire Alarm Verification Time (120-255 sec.)
Segment 10 Listen-In Time (0-255 seconds)
Segment 11 Zone Monitor Timer (0-255 Days)
Segments 12 – 14 Reserved
0
_
_
_
_
_
_
_
_
_
_
_
5
60
8
0
5
3
30
0
0
0
41
20
SPECIAL FEATURES
Segment 1 (Circle numbers to program)
1 = Enables 6-digit code option. All arm/disarm/Go To Program codes require six digits
2 = Requires valid user code entry for [r]-[9]-[8] and [r]-[9]-[9] functions to work.
3 = Enable Auto Cancel / Abort.
4 = Enable Walk-Test Mode.
5 = Enable Auto Force-Arming with keyfob or keyswitch
6-8 = Reserved.
42
43
21 GO TO PROGRAM CODE
21 GO TO PROGRAM CODE PARTITION AND AUTHORIZATION
Segment 1 (Circle numbers to program)
9-7-1-3-0-0
_ _ _ _ _ _
L
1 = Reserved.
2 = Enables "Go To Program Code" as an arm only code.
3 = Enables "Go To Program Code" as an arm only after closing.
4 = Enables "Go To Program Code" as a master arm/disarm code (can change user codes)
5 = Enables "Go To Program Code" as an arm/disarm code.
6 = Enables "Go To Program Code" to bypass zones.
7 = Enables "Go To Program Code" opening and closing reports.
8 = Reserved.
Segment 2 (Circle numbers to program)
1 = Enables "Go To Program Code" for partition 1
2 = Enables "Go To Program Code" for partition 2
3 = Enables "Go To Program Code" for partition 3
4 = Enables "Go To Program Code" for partition 4
5 = Enables "Go To Program Code" for partition 5
6 = Enables "Go To Program Code" for partition 6
7 = Enables "Go To Program Code" for partition 7
8 = Enables "Go To Program Code" for partition 8
44
45
21 DURESS CODE
21 AUXILIARY OUTPUTS 1-4 PARTITION SELECTION
15-15-15-15-15-15
_ _ _ _ _ _
L
Segments
1
1
2
3
4
5
6
7
8
2
1
2
3
4
5
6
7
8
3
1
2
3
4
5
6
7
8
4
1
2
3
4
5
6
7
8
1 = Partition 1
2 = Partition 2
3 = Partition 3
4 = Partition 4
5 = Partition 5
6 = Partition 6
7 = Partition 7
8 = Partition 8
36
NX-8V2 Control
Download from Www.Somanuals.com. All Manuals Search And Download.
LOC
PG
21
DESCRIPTION
AUXILIARY OUTPUTS 1-4 SPECIAL TIMING
Segments
1 = Aux output timed in minutes.
2 = Aux output to latch.
3 = Aux output to stop timing upon user code entry.
4 = Aux output to activate only between closing & opening time.
5 = Aux output to activate only between opening & closing time.
6 = Invert auxiliary output (0 Volts going to 12V when activated).
7 = Reserved
DEFAULT
PROGRAM DATA
46
1
1
2
3
4
5
6
7
8
2
3
1
2
3
4
5
6
7
8
4
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
8 = Reserved
47
48
49
50
21 AUXILIARY OUTPUT #1, EVENT & TIME
Segment #1: Event number for output #1
Segment #2: Timing for output #1
22 AUXILIARY OUTPUT #2, EVENT & TIME
Segment # 1: Event number for output #2
Segment# 2: Timing for output #2
22 AUXILIARY OUTPUT #3, EVENT & TIME
Segment #1: Event number for output #3
Segment #2: Timing for output #3
22 AUXILIARY OUTPUT #4, EVENT & TIME
Segment #1: Event number for output #4
Segment #2: Timing for output #4
0=Burglary alarm
10 seconds
1=Fire alarm
10 seconds
2= 24 Hour Alarm
10 seconds
21-Armed State
0=Follow condition
L
51
22 AUTOTEST CONTROL
Segment 1: Program a "1" if the interval is hours, a "0" if in
days. Add a A2" to suppress the daily test or a A3" to suppress
the hourly test.
1
Segment 2: Program the autotest interval from 1-255 days or
hours.
24
Segment 3: Program the autotest report in 24-hour time format.
Segment 4: Program the autotest report time, minutes after the
hour.
2
0
52
53
22 OPENING TIME
Segment 1: Program the hour of the opening time.
Segment 2: Program the minutes after the hour of opening time.
22 CLOSING TIME / AUTO ARMING TIME
Segment 1: Program the hour of closing time / auto arming time.
Segment 2: Program the minutes after hour of closing / auto
arming time.
8
0
20
0
54
23 DAYS OF THE WEEK EACH PARTITION IS OPEN
Segments
Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Reserved
1
1
2
3
4
5
6
7
8
2
1
2
3
4
5
6
7
8
3
1
2
3
4
5
6
7
8
4
1
2
3
4
5
6
7
8
5
1
2
3
4
5
6
7
8
6
1
2
3
4
5
6
7
8
7
1
2
3
4
5
6
7
8
8
1
2
3
4
5
6
7
8
55
23 DAYS OF THE WEEK "AUTO ARMING" WILL OCCUR IN PARTITIONS 1-8
Segments
Sunday
Monday
1
1
2
3
4
5
6
7
8
2
1
2
3
4
5
6
7
8
3
1
2
3
4
5
6
7
8
4
1
2
3
4
5
6
7
8
5
1
2
3
4
5
6
7
8
6
1
2
3
4
5
6
7
8
7
1
2
3
4
5
6
7
8
8
1
2
3
4
5
6
7
8
Tuesday
Wednesday
Thursday
Friday
Saturday
Disable retry timer
NX-8V2 Control
37
Download from Www.Somanuals.com. All Manuals Search And Download.
COMMUNICATOR CODES FOR SLOW SPEED FORMATS ONLY
The digit programmed in each of the following locations will be sent as the upper HEX digit in place of the alarm event code.
The zone ID or user ID will always be reported as the lower HEX digit (1-F). For example, if the zone ID or user ID is 15, the 4+2
lower digit will be “F”. (Refer to Appendix 4 on page 53.)
ꢀ If Segments 2-8 are left as “0” (unprogrammed), they will follow the Segment 1 selection.
If Segment 1 is left as “0” and the feature is enabled, the NX-8V2 will report “”A”.
LOC
PG
DESCRIPTION
DEFAULT
PROGRAMMING DATA
56
23 RESTORE COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY
Segment 1: Partition 1 Restore code
Segment 2: Partition 2 Restore code
Segment 3: Partition 3 Restore code
Segment 4: Partition 4 Restore code
Segment 5: Partition 5 Restore code
Segment 6: Partition 6 Restore code
Segment 7: Partition 7 Restore code
Segment 8: Partition 8 Restore code
0
0
0
0
0
0
0
0
_
_
_
_
_
_
_
_
57
58
59
60
61
23 BYPASS COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY
Segment 1: Partition 1 Bypass code
Segment 2: Partition 2 Bypass code
Segment 3: Partition 3 Bypass code
Segment 4: Partition 4 Bypass code
Segment 5: Partition 5 Bypass code
Segment 6: Partition 6 Bypass code
Segment 7: Partition 7 Bypass code
Segment 8: Partition 8 Bypass code
0
0
0
0
0
0
0
0
_
_
_
_
_
_
_
_
23 TAMPER COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY
Segment 1: Partition 1 Tamper Code
Segment 2: Partition 2 Tamper Code
Segment 3: Partition 3 Tamper Code
Segment 4: Partition 4 Tamper Code
Segment 5: Partition 5 Tamper Code
Segment 6: Partition 6 Tamper Code
Segment 7: Partition 7 Tamper Code
Segment 8: Partition 8 Tamper Code
0
0
0
0
0
0
0
0
_
_
_
_
_
_
_
_
23 TROUBLE COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY
Segment 1: Partition 1 Trouble Code
Segment 2: Partition 2 Trouble Code
Segment 3: Partition 3 Trouble Code
Segment 4: Partition 4 Trouble Code
Segment 5: Partition 5 Trouble Code
Segment 6: Partition 6 Trouble Code
Segment 7: Partition 7 Trouble Code
Segment 8: Partition 8 Trouble Code
0
0
0
0
0
0
0
0
_
_
_
_
_
_
_
_
23 SENSOR LOW BATTERY COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY
Seg 1: Partition 1 Sensor Low Battery Code
Seg 2: Partition 2 Sensor Low Battery Code
Seg 3: Partition 3 Sensor Low Battery Code
Seg 4: Partition 4 Sensor Low Battery Code
Seg 5: Partition 5 Sensor Low Battery Code
Seg 6: Partition 6 Sensor Low Battery Code
Seg 7: Partition 7 Sensor Low Battery Code
Seg 8: Partition 8 Sensor Low Battery Code
0
0
0
0
0
0
0
0
_
_
_
_
_
_
_
_
24 SENSOR MISSING COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY
Seg 1: Partition 1 Sensor Missing Code
Seg 2: Partition 2 Sensor Missing Code
Seg 3: Partition 3 Sensor Missing Code
Seg 4: Partition 4 Sensor Missing Code
Seg 5: Partition 5 Sensor Missing Code
Seg 6: Partition 6 Sensor Missing Code
Seg 7: Partition 7 Sensor Missing Code
Seg 8: Partition 8 Sensor Missing Code
0
0
0
0
0
0
0
0
_
_
_
_
_
_
_
_
62
63
24 DURESS
24 AUXILIARY 1
0-0
0-0
_ _
_ _
38
NX-8V2 Control
Download from Www.Somanuals.com. All Manuals Search And Download.
LOC
64
65
66
67
68
69
70
71
72
73
74
75
76
77
PG
DESCRIPTION
DEFAULT
0-0
PROGRAMMING DATA
24 AUXILIARY 2
24 KEYPAD PANIC
_ _
_ _
_ _
0-0
0-0
24 KEYPAD MULTIPLE CODE ENTRY TAMPER
24 BOX TAMPER / BOX TAMPER RESTORE
24 AC FAIL / AC RESTORE
24 LOW BATTERY / LOW BATTERY RESTORE
24 POWER SHORT / POWER SHORT RESTORE
24 BELL TAMPER / BELL TAMPER RESTORE
24
24
24
24 FAILURE TO COMMUNICATE
24 LOG FULL COMMUNICATOR CODE
25 OPENING CODE COMMUNICATOR CODE
Segment 1: Partition 1 Opening Code
Segment 2: Partition 2 Opening Code
Segment 3: Partition 3 Opening Code
Segment 4: Partition 4 Opening Code
Segment 5: Partition 5 Opening Code
Segment 6: Partition 6 Opening Code
Segment 7: Partition 7 Opening Code
Segment 8: Partition 8 Opening Code
25 CLOSING COMMUNICATOR CODE
Segment 1: Partition 1 Closing Code
Segment 2: Partition 2 Closing Code
Segment 3: Partition 3 Closing Code
Segment 4: Partition 4 Closing Code
Segment 5: Partition 5 Closing Code
Segment 6: Partition 6 Closing Code
Segment 7: Partition 7 Closing Code
Segment 8: Partition 8 Closing Code
25 AUTOTEST COMMUNICATOR CODE
25 RECENT CLOSING AND EXIT ERROR
0-0-0-0
0-0-0-0
0-0-0-0
0-0-0-0
0-0-0-0
0-0-0-0
0-0-0-0
0-0-0-0
0-0
_ _ _ _
_ _ _ _
_ _ _ _
_ _ _ _
_ _ _ _
_ _ _ _
_ _ _ _
_ _ _ _
_ _
TELEPHONE LINE CUT / LINE CUT RESTORE
GROUND FAULT / GROUND FAULT RESTORE
EXPANDER TROUBLE / EXP TROUBLE RESTORE
0-0
_ _
0
0
0
0
0
0
0
0
_
_
_
_
_
_
_
_
78
0
0
0
0
0
0
0
0
_
_
_
_
_
_
_
_
_ _
79
80
81
82
83
0-0
0-0
0-0-0-0
_ _
START PROGRAMMING / END PROGRAMMING
25
_ _ _ _
X X _ _
_
Reserved
_ _ _ _ _
_ _ __ _ _
25 END DOWNLOAD
25 CANCEL COMMUNICATOR CODE
25 RESERVED
25 PARTITION 1, ACCOUNT CODE
25 PARTITION 2, ACCOUNT CODE
0-0-0-0
0
84-87
88
0-0-0-0
10-10-10-10-10-10
10-10-10-10-10-10
89
90
25 PARTITION 2, FEATURE AND REPORTING SELECTION
Segment 1
1 = Quick Arm
2 = Re-Exit
5 = Audible Panic
6 = Auxiliary 1
3 = Auto Bypass
4 = Silent Panic
Segment 2
7 = Auxiliary 2
8 = Multi Keypress Tamper
1 = LED extinguish enable
2 = Require user code for bypassing zones
3 = Bypass sounder alert
4 = AC power/low battery sounder alert
Segment 3
5 = Enables bypass toggle
6 = Enables silent auto arm
7 = Enables auto instant
8 = Reserved
1 = Open/Close
2 = Bypass
5 = Tamper
6 = Cancel
3 = Restore
4 = Trouble
7 = Recent Closing
8 = Exit Error
Segment 4
1 =Late to Close / Early to Open
2-8 =Reserved
Segment 5 RESERVED
NX-8V2 Control
39
Download from Www.Somanuals.com. All Manuals Search And Download.
LOC
91
PG
DESCRIPTION
DEFAULT
PROGRAMMING DATA
25 PARTITION 2 ENTRY/EXIT TIMERS
Segment 1: Entry Time 1
0
0
0
0
_
_
_
_
Segment 2: Exit Time 1
Segment 3: Entry Time 2
Segment 4: Exit Time 2
Segment 5 & 6 RESERVED
26 PARTITION 3, ACCOUNT CODE
26 PARTITION 3, FEATURE AND REPORTING SELECTION
92
93
10-10-10-10-10-10
_ _ _ _ _ _
Segment 1
1 = Quick Arm
5 = Audible Panic
2 = Re-Exit
6 = Auxiliary 1
3 = Auto Bypass
7 = Auxiliary 2
4 = Silent Panic
8 = Multi Keypress Tamper
Segment 2
1 = LED extinguish enable
2 = Require user code for bypassing zones
3 = Bypass sounder alert
4 = AC power/low battery sounder alert
Segment 3
5 = Enables bypass toggle
6 = Enables silent auto arm
7 = Enables auto instant
8 = Reserved
1 = Open/Close
2 = Bypass
5 = Tamper
6 = Cancel
3 = Restore
4 = Trouble
7 = Recent Closing
8 = Exit Error
Segment 4
1 =Late to Close / Early to Open
2-8 =Reserved
Segment 5 RESERVED
26 PARTITION 3 ENTRY/EXIT TIMERS
Segment 1: Entry Time 1
Segment 2: Exit Time 1
Segment 3: Entry Time 2
Segment 4: Exit Time 2
Segment 5 & 6 RESERVED
94
0
0
0
0
_
_
_
_
95
96
26
PARTITION 4, ACCOUNT CODE
10-10-10-10-10-10
_ _ _ _ _ _
26 PARTITION 4, FEATURE AND REPORTING SELECTION
Segment 1
1 = Quick Arm
5 = Audible Panic
2 = Re-Exit
6 = Auxiliary 1
3 = Auto Bypass
7 = Auxiliary 2
4 = Silent Panic
8 = Multi Keypress Tamper
Segment 2
1 = LED extinguish enable
2 = Require user code for bypassing zones
3 = Bypass sounder alert
4 = AC power/low battery sounder alert
Segment 3
5 = Enables bypass toggle
6 = Enables silent auto arm
7 = Enables auto instant
8 = Reserved
1 = Open/Close
2 = Bypass
5 = Tamper
6 = Cancel
3 = Restore
4 = Trouble
7 = Recent Closing
8 = Exit Error
Segment 4
1 =Late to Close / Early to Open
2-8 =Reserved
Segment 5 RESERVED
26 PARTITION 4 ENTRY/EXIT TIMERS
Segment 1: Entry Time 1
Segment 2: Exit Time 1
Segment 3: Entry Time 2
Segment 4: Exit Time 2
Segment 5 & 6 RESERVED
26 PARTITION 5, ACCOUNT CODE
97
98
0
0
0
0
_
_
_
_
10-10-10-10-10-10
_ _ _ _ _ _
40
NX-8V2 Control
Download from Www.Somanuals.com. All Manuals Search And Download.
LOC
99
PG
DESCRIPTION
DEFAULT
PROGRAMMING DATA
26 PARTITION 5, FEATURE AND REPORTING SELECTION
Segment 1
1 = Quick Arm
2 = Re-Exit
5 = Audible Panic
6 = Auxiliary 1
3 = Auto Bypass
7 = Auxiliary 2
4 = Silent Panic
8 = Multi Keypress Tamper
Segment 2
1 = LED extinguish enable
2 = Require user code for bypassing zones
3 = Bypass sounder alert
4 = AC power/low battery sounder alert
Segment 3
5 = Enables bypass toggle
6 = Enables silent auto arm
7 = Enables auto instant
8 = Reserved
1 = Open/Close
2 = Bypass
5 = Tamper
6 = Cancel
3 = Restore
4 = Trouble
7 = Recent Closing
8 = Exit Error
Segment 4
1 =Late to Close / Early to Open
2-8 =Reserved
Segment 5 RESERVED
100 26 PARTITION 5 ENTRY/EXIT TIMERS
Segment 1: Entry Time 1
0
0
0
0
_
_
_
_
Segment 2: Exit Time 1
Segment 3: Entry Time 2
Segment 4: Exit Time 2
Segment 5 & 6 RESERVED
101 26 PARTITION 6, ACCOUNT CODE
10-10-10-10-10-10
_ _ _ _ _ _
102 27 PARTITION 6, FEATURE AND REPORTING SELECTION
Segment 1
1 = Quick Arm
5 = Audible Panic
2 = Re-Exit
6 = Auxiliary 1
3 = Auto Bypass
7 = Auxiliary 2
4 = Silent Panic
8 = Multi Keypress Tamper
Segment 2
1 = LED extinguish enable
2 = Require user code for bypassing zones
3 = Bypass sounder alert
4 = AC power/low battery sounder alert
Segment 3
5 = Enables bypass toggle
6 = Enables silent auto arm
7 = Enables auto instant
8 = Reserved
1 = Open/Close
2 = Bypass
5 = Tamper
6 = Cancel
3 = Restore
4 = Trouble
7 = Recent Closing
8 = Exit Error
Segment 4
1 =Late to Close / Early to Open
2-8 =Reserved
Segment 5 RESERVED
103 27 PARTITION 6 ENTRY/EXIT TIMERS
Segment 1: Entry Time 1
0
0
0
0
_
_
_
_
Segment 2: Exit Time 1
Segment 3: Entry Time 2
Segment 4: Exit Time 2
Segment 5 & 6 RESERVED
104 27 PARTITION 7 ACCOUNT CODE
10-10-10-10-10-10
_ _ _ _ _ _
105 27 PARTITION 7 FEATURE AND REPORTING SELECTION
Segment 1
1 = Quick Arm
2 = Re-Exit
5 = Audible Panic
6 = Auxiliary 1
3 = Auto Bypass
4 = Silent Panic
7 = Auxiliary 2
8 = Multi Keypress Tamper
NX-8V2 Control
41
Download from Www.Somanuals.com. All Manuals Search And Download.
LOC
PG
DESCRIPTION
DEFAULT
PROGRAMMING DATA
105 27
Segment 2
1 = LED extinguish enable
2 = Require user code for bypassing zones
3 = Bypass sounder alert
5 = Enables bypass toggle
6 = Enables silent auto arm
7 = Enables auto instant
8 = Reserved
4 = AC power/low battery sounder alert
Segment 3
1 = Open/Close
2 = Bypass
5 = Tamper
6 = Cancel
3 = Restore
4 = Trouble
7 = Recent Closing
8 = Exit Error
Segment 4
1 =Late to Close / Early to Open
2-8 = Reserved
Segment 5 RESERVED
106 27 PARTITION 7 ENTRY/EXIT TIMERS
Segment 1: Entry Time 1
0
0
0
0
_
_
_
_
Segment 2: Exit Time 1
Segment 3: Entry Time 2
Segment 4: Exit Time 2
Segment 5 & 6 RESERVED
107 27 PARTITION 8 ACCOUNT CODE
10-10-10-10-10-10
_ _ _ _ _ _
108 27 PARTITION 8 FEATURE AND REPORTING SELECTION
Segment 1
1 = Quick Arm
5 = Audible Panic
2 = Re-Exit
6 = Auxiliary 1
3 = Auto Bypass
7 = Auxiliary 2
4 = Silent Panic
8 = Multi Keypress Tamper
Segment 2
1 = LED extinguish enable
2 = Require user code for bypassing zones
3 = Bypass sounder alert
4 = AC power/low battery sounder alert
Segment 3
5 = Enables bypass toggle
6 = Enables silent auto arm
7 = Enables auto instant
8 = Reserved
1 = Open/Close
2 = Bypass
5 = Tamper
6 = Cancel
3 = Restore
4 = Trouble
7 = Recent Closing
8 = Exit Error
Segment 4
1 =Late to Close / Early to Open
2-8 =Reserved
Segment 5 RESERVED
109 27 PARTITION 8 ENTRY/EXIT TIMERS
Segment 1: Entry Time 1
0
0
0
0
_
_
_
_
Segment 2: Exit Time 1
Segment 3: Entry Time 2
Segment 4: Exit Time 2
Segment 5 & 6 RESERVED
110 28 ZONE TYPE 1 ALARM EVENT CODE
111 28 ZONE TYPE 1 CHARACTERISTIC SELECT
Segment 1
8
_
1 = Fire (enable for fire zone)
2 = 24-Hour (enable for non-fire 24 hour)
3 = Keyswitch zone
5 = Delay 1 zone (enable to follow Timer 1 Entry/Exit times)
6 = Delay 2 zone (enable to follow Timer 2 Entry / Exit times)
7 = Interior (Enable for auto bypass or stay arming)
4 = Follower (enable for burg zones that are 8 = Local Only (enable if zone is not to be reported)
instant during non-entry times)
Segment 2
1 = Keypad audible on alarm.
2 = Yelping siren on alarm.
3 = Temporal siren on alarm.
4 = Chime.
5 = Bypassable.
6 = Group Shunt.
7 = Force armable.
8 = Entry Guard.
42
NX-8V2 Control
Download from Www.Somanuals.com. All Manuals Search And Download.
LOC
111 28 Segment 3
1 = Fast Loop Response.
PG
DESCRIPTION
DEFAULT
PROGRAMMING DATA
5 = Dialer Delay zone.
6 = Swinger zone.
7 = Restore reporting.
8 = Listen-In.
2 = Double End of Line Tamper zone.
3 = Trouble zone (Day zone).
4 = Cross Zone.
Segment 4
1 = Zone Activity Monitor.
2 = End of Line Resistor Defeat.
3 = Zone acts as Request to Exit input.
Segment 5 RESERVED
4 = Zone acts as access entry point (Do not enable this segment unless
configured with Access Control module)
5 -8 = Reserved.
LOCATIONS 112 – 169
EVEN NUMBERED Contains the event code sent for Contact ID or SIA and chosen from the list on pg 16. 4+2 Format Note: If 4+2
format is being used, the number programmed in this location will be sent as the upper hex digit. The digit should be
from 1 to 15 when using 4+2 formats. The zone ID or user ID will be the lower hex digit of the zone that is in alarm.
ODD NUMBERED
The defaults listed below represent the five segments of each of those locations. Use the data from location 111 (table
above and pg 28)
LOC
DESCRIPTION
DEFAULT
PROGRAMMING DATA
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
ZONE TYPE 2 ALARM EVENT CODE
ZONE TYPE 2 CHARACTERISTIC SELECT
ZONE TYPE 3 ALARM EVENT CODE
ZONE TYPE 3 CHARACTERISTIC SELECT
ZONE TYPE 4 ALARM EVENT CODE
ZONE TYPE 4 CHARACTERISTIC SELECT
ZONE TYPE 5 ALARM EVENT CODE
ZONE TYPE 5 CHARACTERISTIC SELECT
ZONE TYPE 6 ALARM EVENT CODE
ZONE TYPE 6 CHARACTERISTIC SELECT
ZONE TYPE 7 ALARM EVENT CODE
ZONE TYPE 7 CHARACTERISTIC SELECT
ZONE TYPE 8 ALARM EVENT CODE
ZONE TYPE 8 CHARACTERISTIC SELECT
ZONE TYPE 9 ALARM EVENT CODE
ZONE TYPE 9 CHARACTERISTIC SELECT
ZONE TYPE 10 ALARM EVENT CODE
ZONE TYPE 10 CHARACTERISTIC SELECT
ZONE TYPE 11 ALARM EVENT CODE
ZONE TYPE 11 CHARACTERISTIC SELECT
ZONE TYPE 12 ALARM EVENT CODE
ZONE TYPE 12 CHARACTERISTIC SELECT
ZONE TYPE 13 ALARM EVENT CODE
ZONE TYPE 13 CHARACTERISTIC SELECT
ZONE TYPE 14 ALARM EVENT CODE
ZONE TYPE 14 CHARACTERISTIC SELECT
ZONE TYPE 15 ALARM EVENT CODE
ZONE TYPE 15 CHARACTERISTIC SELECT
ZONE TYPE 16 ALARM EVENT CODE
ZONE TYPE 16 CHARACTERISTIC SELECT
ZONE TYPE 17 ALARM EVENT CODE
ZONE TYPE 17 CHARACTERISTIC SELECT
ZONE TYPE 18 ALARM EVENT CODE
ZONE TYPE 18 CHARACTERISTIC SELECT
ZONE TYPE 19 ALARM EVENT CODE
ZONE TYPE 19 CHARACTERISTIC SELECT
ZONE TYPE 20 ALARM EVENT CODE
ZONE TYPE 20 CHARACTERISTIC SELECT
ZONE TYPE 21 ALARM EVENT CODE
ZONE TYPE 21 CHARACTERISTIC SELECT
ZONE TYPE 22 ALARM EVENT CODE
ZONE TYPE 22 CHARACTERISTIC SELECT
ZONE TYPE 23 ALARM EVENT CODE
ZONE TYPE 23 CHARACTERISTIC SELECT
2
__
2-125-78-0-0
__ __ __ __ __
7
__
5-1245-5678-0-0
__ __ __ __ __
5
__
45-125-5678-0-0
__ __ __ __ __
5
__
457-125-5678-0-0
__ __ __ __ __
4
__
0-1245-5678-0-0
__ __ __ __ __
0
__
2-0-78-0-0
__ __ __ __ __
1
__
1-13-378-0-0
__ __ __ __ __
7
__
6-1245-5678-0-0
__ __ __ __ __
2
__
24-5-78-0-0
__ __ __ __ __
3
__
3-0-0-0-0
__ __ __ __ __
5
__
457-125-45678-0-0
__ __ __ __ __
4
__
0-12458-5678-0-0
__ __ __ __ __
7
__
5-12456-5678-0-0
__ __ __ __ __
5
__
457-1256-5678-0-0
__ __ __ __ __
4
__
0-12456-5678-0-0
__ __ __ __ __
7
__
5-1245-25678-0-0
__ __ __ __ __
5
__
__ __ __ __ __
__
__ __ __ __ __
__
__ __ __ __ __
__
__ __ __ __ __
__
457-125-25678-0-0
4
0-1245-25678-0-0
7
6-1245-25678-0-0
15
24-15-78
20
24-15-78
21
__ __ __ __ __
__
__ __ __ __ __
24-15-78
NX-8V2 Control
43
Download from Www.Somanuals.com. All Manuals Search And Download.
LOC
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170-205
206
DESCRIPTION
DEFAULT
22
1-13-378
PROGRAMMING DATA
ZONE TYPE 24 ALARM EVENT CODE
ZONE TYPE 24 CHARACTERISTIC SELECT
ZONE TYPE 25 ALARM EVENT CODE
ZONE TYPE 25 CHARACTERISTIC SELECT
ZONE TYPE 26 ALARM EVENT CODE
ZONE TYPE 26 CHARACTERISTIC SELECT
ZONE TYPE 27 ALARM EVENT CODE
ZONE TYPE 27 CHARACTERISTIC SELECT
ZONE TYPE 28 ALARM EVENT CODE
ZONE TYPE 28 CHARACTERISTIC SELECT
ZONE TYPE 29 ALARM EVENT CODE
ZONE TYPE 29 CHARACTERISTIC SELECT
ZONE TYPE 30 ALARM EVENT CODE
ZONE TYPE 30 CHARACTERISTIC SELECT
RESERVED
__
__ __ __ __ __
14
__
__ __ __ __ __
__
__ __ __ __ __
__
__ __ __ __ __
__
__ __ __ __ __
__
248-45-0-0-0
5
467-125-5678-0-0
5
457-1257-5678-0-0
7
6-12457-5678-0-0
5
457-125-5678-1-0
7
5-1245-5678-1-0
__ __ __ __ __
__
__ __ __ __ __
DAYS OF THE WEEK "AUTO DISARMING" WILL OCCUR IN PARTITIONS 1-8
Segments
Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Reserved
1
1
2
3
4
5
6
7
8
2
1
2
3
4
5
6
7
8
3
1
2
3
4
5
6
7
8
4
1
2
3
4
5
6
7
8
5
1
2
3
4
5
6
7
8
6
1
2
3
4
5
6
7
8
7
1
2
3
4
5
6
7
8
8
1
2
3
4
5
6
7
8
44
NX-8V2 Control
Download from Www.Somanuals.com. All Manuals Search And Download.
ZONE WORKSHEET
1
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
NX-8V2 Control
45
Download from Www.Somanuals.com. All Manuals Search And Download.
XV.
GLOSSARY
Abort
If enabled, the NX-8V2 will wait the programmed number of seconds in location 40 prior to sending an alarm. During this delay time, the
“Cancel” LED will flash. To abort the report, type in a code and press the Cancel key. The LED will extinguish. If the report is not
aborted within the allotted time, the LED will extinguish when the report is sent. ADialer Delay@ must be enabled in the ACharacteristic
Select@ of locations 110-169. (Loc 40 & 110-169, pg 20 & 28-31)
AC Fail / Low Battery Report / Warning
The NX-8V2 can be programmed to report AC failure and/or Low Battery conditions to the central station. It can also be programmed to
sound the keypad immediately upon detection of the condition. The AC failure report/warning can be delayed. (Loc 37 & 39, pg 19)
AC Power / Low Battery Sounder Alert
If enabled, the NX-8V2 will beep the keypad sounder upon arming or disarming if the AC power is missing or a low battery has been
detected. (Loc 23, pg 15)
Arm / Disarm Codes
The NX-8V2 can have 99 four-digit codes or 66 six-digit codes to arm/disarm the control. All codes must have the same number of
digits. The factory default for User #1 is ÎÏÐÑwhen using a 4-digit code, or ÎÏÐÑÒÓfor a 6-digit code. This code can then be
used to enter the new arm/disarm codes. (Loc 41, pg 20)
Automatic Arming
NOTE: This feature must be disabled for UL installations
If programmed, the NX-8V2 will Auto Arm at a specified time. At this time, the keypad will beep for 50 seconds before the panel arms.
The arming process will be stopped if a code is entered on the keypad. The NX-8V2 will attempt to arm after every 45 minutes of
inactivity until the next “opening” time (loc. 52), or until the system is armed. The 45-minute timer will be extended when there is activity
in the building causing the "Ready" LED to turn off and on. If closing reports are sent, the user code will be 97. (Loc 23 & 52-55, pg 15
& 22)
Automatic Bypass / Instant Arming
When enabled, the control panel can automatically bypass interior follower zones if an exit is not detected during the exit delay time.
Entry delay zones can also be made instant. (Loc 23, segments 1 & 3, pg 15)
Auto Cancel / Abort
If enabled, the Cancel and/or Abort features will be automatic (pressing the [Cancel] button is not required). The Cancel and Abort
features, in locations 23 & 40 respectively, must be enabled to permit this Auto feature to work. For proper operation of these features,
ADialer Delay@ must be enabled in the ACharacteristic Select@ of locations 110-169 Zone Types. (Loc 41, pg 20)
Auto Test
This feature will cause the panel to call the central station to report a communicator test at a specified interval. (Loc 51, pg 22)
Auxiliary Outputs
The NX-8V2 has 4 programmable outputs that can be used to activate relays, LED=s, etc. (See the terminal description on pg 6 and Loc
45-50, pg 21)
Auxiliary Power Over-current
The NX-8V2 will illuminate the "Service" LED on the keypad whenever too much current is drawn from any device powered by the
system. This condition can be reported to the central station. (Loc 37, pg 19)
Box Tamper
The NX-8V2 has an input for a normally closed tamper switch (see terminal drawing). The Box Tamper can be programmed to report
and/or sound the siren and/or the keypad. These terminals can be enabled or disabled in programming. (Loc 37 & 39, pg 19)
Built In Siren Driver
The NX-8V2 has a built-in 112db-siren driver. When desired, this built-in driver can be easily converted to a 1-amp voltage output
through programming. (Loc 37, pg 19)
Bypass Toggle
This feature will enable the end user to toggle (turn on or off) the bypass of an interior zone with the system armed by pressing the
[Bypass] key. (Loc 23, pg 15)
Call Back
When enabled, the control will use the call back phone number to call the download computer before beginning a download. (Loc 21,
pg 15)
Cancel
If enabled, the NX-8V2 will send a "Cancel" report if when the system is disarmed and the [Cancel] button is pressed within 5 minutes of
an alarm. Once the [Cancel] key is pressed, the "Cancel" LED will illuminate until the central station acknowledges the "Cancel" report.
ADialer Delay@ must be enabled in the ACharacteristic Select@ of locations 110-149. (Loc 23, pg 15)
Code Required Options
The NX-8V2 can be programmed to require a code for bypassing zones and/or initiating a download using the r98 or r99
function. (Loc 23 & 41, pg 15 & 20)
Communication Formats
The NX-8V2 can report in multiple formats. It is recommended that you use Contact ID or SIA formats if possible. If you wish to report to
a pager or in a 4+2 format to a central station, you must program each code to be reported. (Loc 56-83 & 111-169, pg 23-25 & 28-31)
Cross Zoning
This feature requires two or more trips on a zone or zones programmed as "cross zones" within a specified time before reporting an
alarm. During the time between trips, the NX-8V2 can be programmed to sound the keypad and/or the siren. The NX-8V2 can also be
programmed to report an alarm after two or more trips on the same zone. (Loc 37, 39, 40 & 110-149, pg 19, 20, 28-31)
46
NX-8V2 Control
Download from Www.Somanuals.com. All Manuals Search And Download.
Dual / Split / Multiple Reports
The NX-8V2 can send communication reports to three different phone numbers for dual, split or multiple reports selectable by event or
partition. (Loc 4, 10, & 16, pg 12, 13, 14)
Duress Code
If a duress code is programmed the NX-8V2 will send a duress signal whenever the panel is armed or disarmed with this code. If
open/close reports are sent, the user code will be 254. (Loc 44, pg 21)
Dynamic Battery Test
The NX-8V2 can be programmed to perform a Dynamic Battery Test for a selected duration the first time the panel is armed or
disarmed every day, as well as by using r4 (Test function). If the panel is not armed or disarmed during the day, it will perform the
test at midnight. The NX-8V2 can also be programmed to perform a missing battery test every 12 seconds. (Loc 37 & 40, pg 19 & 20)
Early to Open / Late to Close
If an opening occurs before the opening and closing times, the NX-8V2 will send an “Early Open” report. If it fails to close on or before
the designated closing time, the NX-8V2 will send a “Late to Close” report.
NOTE: For UL installations, all zones must be programmed as supervised.
End of Line Resistor Defeat
The NX-8V2 can be programmed to make zones 1-8 for normally closed operation only, eliminating the need for the end of line resistors
on these zones. When a zone is programmed for normally closed operation, a short on that zone will not change the loop condition, and
an open on that zone will produce a faulted condition. This feature will be ignored by any Priority zone. (Loc 111-169, pg 28-31)
NOTE: For UL installations, this feature shall be disabled.
Entry-Guard
This unique low level arming mode has been developed to reduce the most common source of false alarms. When armed with the
AInstant@ LED on, the opening of any zones designated as "Entry Guard zone" will initiate the keypad sounder and start the entry delay
before creating an alarm. All other zones will function as normal. This arming mode will encourage system owners to use their system
more frequently when the premises are occupied. (Loc 111-169, pg 28-31)
Exit Error
If enabled, the NX-8V2 will send an "Exit Error Report" if an entry/exit zone is faulted at the instant the exit delay expires. This report
will be sent along with the user number that armed the system, if the panel is not disarmed before the entry delay expires. The alarm
report will also be sent. Even if this feature is not enabled, the siren will sound if any entry/exit zone is faulted at the instant the exit
delay expires. (Loc 23, pg 15)
Expander Trouble
The NX-8V2 will report expander trouble to the central station if enabled. This condition will illuminate the "Service" LED on the keypad
even if not reported. NOTE: The keypads are considered expanders. The expansion device number that will report can be found on
page 52. (Loc 37, pg 19)
Fail to Communicate
The NX-8V2 will illuminate the "Service" LED if a report fails to reach the central station. If enabled, when the next report is successfully
communicated, a Fail to Communicate code will be reported. (Loc 37, pg 19)
Fire Alarm Verification
When enabled, the NX-8V2 will verify a Fire alarm by requiring more than one trip on a smoke detector within a specified time before
creating an alarm. (Loc 40, pg 20) This feature is not approved for residential use in California.
First to Open / Last to Close
The first partition that opens from a completely armed system (all valid partitions armed) will send an “Open” report. All other partitions
opened will be log only. The last partition to close from a completely armed system (all valid partitions armed) will report to the central
station. Any prior closing(s) will be log only. (Loc 37, pg 19)
NOTE: For UL installations, this feature shall be disabled.
Force Arming
When enabled, the NX-8V2 can be Force Armed with zones violated. Under this condition, if a force armable zone is not secure, the
"Ready" LED will flash. At the end of the exit delay, these zones will become bypassed. If these zones become secured any time during
the arming cycle, they will be unbypassed and active in the system. If "Bypass Report" is enabled, the force arming zones can be
programmed to report bypass when they are Force Armed (default), or to not report bypass even if "Bypass Report" is enabled. (Loc
37 & 111-169, pg 19 & 28-31)
Ground Fault
A fault of the earth ground can be reported to the central station. Even if it is not reported, this condition will illuminate the "Service" LED
on the keypad. (Loc 37, pg 19)
NOTE: For UL installations, this feature shall be disabled.
Group Bypass
A designated group of zones can be programmed to bypass by pressing [Bypass]- [0]-[Bypass]- [Bypass] prior to arming. (Loc 111-
169, pg 28-31)
Immediate Restore By Zone
The NX-8V2 can be programmed to send alarm and restore reports as soon as they occur, or wait until the siren time has expired. (Loc
37, pg 19)
Internal Event Log
Up to 512 events can be stored in memory along with the date and time of the event. These events can later be viewed through
downloading. All reportable events report to the log.
Keypad Activated Panics
The NX-8V2 has three keypad activated panics that will send reports to the central station: Auxiliary 1 (Fire), Auxiliary 2 (Medical), and
Keypad Panic. Auxiliary 1 will activate the steady (Fire) siren, Auxiliary 2 will sound the keypad, and the Keypad Panic can be
programmed to be silent or audible (sound siren). (Loc 23, pg 15)
Keypad Sounder Control
The NX-8V2 can be programmed to sound the keypad sounder for certain events. (Loc 39, pg 20)
Keypad Tamper
If enabled, the NX-8V2 will disable the keypad for 60 seconds and communicate a tamper signal to the central station if 30 keypresses
are entered without producing a valid code. (Loc 23, pg 15)
NX-8V2 Control
47
Download from Www.Somanuals.com. All Manuals Search And Download.
Keyswitch Arm/Disarm
Any zone on the NX-8V2 can be programmed as a keyswitch zone. If this is done, a momentary short on this zone will arm/disarm the
control. If opening/closing reports are sent, the user code will be 99. (See "Default Zone Types", pg 16)
LED Extinguish
This feature will extinguish all LEDs on the keypad, except the "Power" LED, after 60 seconds without a keypress. Pressing any
numeric key will illuminate all LED=s. (Loc 23, pg 15)
Local Programming Lockout
This feature will disable programming of all locations or specified locations from the keypad. (Loc 21, pg 15)
Log Full Report
A report can be sent to the central station when the event log is full. (Loc 37, pg 19)
Lost Clock Service Light
The NX-8V2 can be programmed to illuminate the "Service" LED when the internal clock has an invalid time due to power loss. (Loc
37, pg 19)
Manual Test
The NX-8V2 can be programmed to perform a bell and/or communicator test when r44 is entered while the system is in the
disarmed state. (Loc 37, pg 19)
Night Mode
NOTE: This mode applies to NX1208E / NX1248E keypads.
In this mode, the control panel will bypass all zones that have the Entry Guard feature enabled. (Loc 23, pg 15)
On Board Zone Disable
The 8 zones on the NX-8V2 panel can be disabled in order to have a completely wireless alarm system. (Loc 37, pg 19)
Partitions
The NX-8V2 can be partitioned into a maximum of eight separate systems with distinct reporting codes, user codes, and operating
features for each system. (Loc 26 - 36, pg 17-19)
Program Code
The factory default for the "Go To Program" code is 9713 when using a 4-digit code or, if the 6-digit option is used, the default is
971300. The program code can also be used as an Arm/Disarm code. If used as an Arm/Disarm code, and open/close reports
are sent, the user code will be 255. (Loc 43, pg 21)
Quick Arm Feature
The NX-8V2 has a one-button "Quick Arm" feature which can be used to arm the system by pressing the [Exit] key or the [Stay] key on
the keypad. If closing reports are sent, the user code will be 98. (Loc 23, pg 15)
Recent Closing
If enabled, the NX-8V2 will send a "Recent Closing Report" to the central station if an alarm occurs within 2 minutes after the panel is
armed. The user number that armed the system will also be sent. (Loc 23, pg 15)
Re-exit
The NX-8V2 has the ability to restart the exit delay for a quick exit without disarming the system by pressing the [Exit] key while the
system is armed. (Loc 23, pg 15)
Shutdown
When enabled, the keypads will turn off all LED=s, except the "Power" LED, and not accept keypresses. (Loc 21, pg 15)
Siren Blast For Arming
The NX-8V2 can be programmed to give a one-second siren blast when the panel is armed, at the end of the exit delay, or when the
central station receiver acknowledges the closing report. It can also give one blast for remote (keyswitch) arming and two blasts for
remote disarming. (Loc 37, pg 19)
Siren Supervision
The NX-8V2 has a ASiren Supervision@ circuit that will constantly monitor the siren on the NX-8V2 and can be programmed to report if
the wires are cut. (Loc 37, pg 19)
Silent Exit Option
The exit delay can be silenced by pressing [r]-[Exit] before arming the control panel or when using the re-exit feature.
Start / End Programming and End Downloading
A report can be sent when local programming is started and ended. A report can also be sent when a download session ends. (Loc
37, pg 19)
Swinger Shutdown
This feature allows a zone or zones to be automatically bypassed after a specified number of alarms. When a zone is tripped, the alarm
‘counter’ reflects “1” in memory. If a new (first) alarm is detected in a different zone, the counter remains at “1”. If an alarm is detected
on a previously tripped zone, the count increments to “2”. The ‘counter’ will increment each time an alarm is detected on a zone with
multiple trips. Bypassing will occur on the zone that causes the count to equal the number programmed in location 38; the ‘counter’ will
reset to zero (0); and begin a new trip count where the next alarm will set the ‘counter’ to 1. If immediate restore is enabled in location
37, the alarms (and restores, if enabled) will be sent as they occur. If immediate restore is not enabled, a second or subsequent alarm
will not be sent until the siren times out. Factory default is 1. (Loc 37 & 38, pg 19)
Telephone Line Monitor
The NX-8V2 has a Telephone Line Monitor that monitors the voltage and current of the telephone line for a detection of a faulted phone
line. This condition can also be reported to the central station. If the report is enabled, only the Telephone Line Restore will be reported .
(Loc 37, 39, & 40, pg 19-20)
NOTE: For UL installations, do NOT disable.
Temporal Siren Disable
If disabled, the Fire Siren will be steady and Fire Voltage Out will be the same as Burglary (continuous). Otherwise, the Fire Siren will
be temporal. (Loc 37, pg 19)
48
NX-8V2 Control
Download from Www.Somanuals.com. All Manuals Search And Download.
Tone Sniff Answering Machine Defeat
If enabled, only one call is required to defeat the answering machine. To use this feature you must have a Hayes 1200 Smart Modem.
From the computer, call the panel as normal. When the answering machine answers, the panel will hear the tones from the modem and
seize the phone line for a download. (Loc 21, pg 15)
This is not recommended for commercial applications.
Two Call Answering Machine Defeat
If enabled, to defeat an answering machine, two telephone calls must be made to the premises. On the first call, let the phone ring one
or two times. The control panel will detect these rings and start a 45-second timer, during which, the control panel will answer the next
call on the first ring. (Loc 21, pg 15)
Walk-Test Mode
If enabled, entering [r] [Chime] followed by a user code will allow a walk-through zone test where all zones become silent and local
(non-reporting). During this test the chime light will flash on the LED keypad. Each time a zone is faulted, the zone light on the LED
keypad will illuminate and the chime will sound. The number of the faulted zone(s) will be displayed on the LCD keypad. It will also be
entered into alarm memory and the internal log. To exit at any time during this mode, enter a user code. Otherwise the AWalk-Test
Mode@ will automatically exit after 15 minutes. (Loc 41, pg 20)
Wireless Sensor Missing/Low Battery
The NX-8V2 will send a report to the central station when a wireless sensor has detected a low battery or has not reported to the
receiver. The "Service" LED will illuminate when either condition exists. (Loc 37, pg 19)
Zone Activity Monitor
This feature will send a report to the central station when a particular zone does not change conditions within the specified number of
days programmed. (Loc 40 & 110-169 pg 20 & 28-31).
Zone Bypassed Sounder Alert
If this feature is enabled, the NX-8V2 will beep the keypad sounder upon arming if a zone is bypassed. (Loc 23, pg 15)
Zone Doubling
This feature allows you to use the eight zones on the panel as sixteen normally closed zones. When this feature is used, European
double E.O.L. configuration cannot be used on the first sixteen zones. THIS FEATURE DOES NOT INCREASE THE TOTAL
NUMBER OF AVAILABLE ZONES BEYOND 48. If one of the sixteen zones must be a fire zone, it must be one of Zones 1 to 8. The
corresponding upper zone will become unavailable. For example: if Zone 6 is a fire zone, then Zone 14 will not be available. (Loc 37,
pg 19)
Zone Types (Configurations)
The NX-8V2 has 30 programmable Zone Types that determine how each zone will function and report. The default Zone Types are
listed on page 16. (Loc 111-169, pg 28-31)
NX-8V2 Control
49
Download from Www.Somanuals.com. All Manuals Search And Download.
XVI.
APPENDIX 1
REPORTING FIXED CODES IN CONTACT ID AND SIA
The table below lists the event codes sent for the following reports (if enabled) when using CONTACT ID or SIA formats.
REPORT
CONTACT ID
SIA
AC FAIL (device number)...........................................................301 ..................................................AT
AC RESTORE (device number) .................................................301 ..................................................AR
AUTOTEST ................................................................................602 ..................................................RP
AUX POWER OVER CURRENT (device number).....................312 ..................................................YP
AUX POWER RESTORE (device number) ................................312 ..................................................YQ
BOX TAMPER (device number).................................................137 ..................................................TA
BOX TAMPER RESTORE (device number)...............................137 ..................................................TR
BYPASS RESTORE (zone number) ..........................................570 ..................................................*U
CANCEL (user number) .............................................................406 ..................................................OC
CLEANME RESTORE................................................................393 ..................................................YZ
CLEANME..................................................................................393 ..................................................YX
CLOSE (user number)................................................................401 ..................................................CL
DOWNLOAD COMPLETE..........................................................412 ..................................................RS
DURESS ....................................................................................121 ..................................................HA
EARLY OPEN/LATE CLOSE .....................................................451 ..................................................OK
END PROGRAM ........................................................................628 ..................................................LX
EVENT LOG FULL.....................................................................605 ..................................................JL
EXIT ERROR (user number)......................................................457 ..................................................EE
EXPANDER RESTORE (device number)...................................333 ..................................................ER
EXPANDER TROUBLE (device number)...................................333 ..................................................ET
FAIL TO CLOSE.........................................................................454 ..................................................CI
FAIL TO COMMUNICATE..........................................................354 ..................................................RT
FORCED DOOR ........................................................................423 ..................................................DF
FORCED DOOR RESTORE ......................................................423 ..................................................DR
GROUND FAULT RESTORE.....................................................310 ..................................................GK
GROUND FAULT.......................................................................310 ..................................................GF
KEYPAD AUXILIARY 1 ..............................................................110 ..................................................FA
KEYPAD AUXILIARY 2 ..............................................................100 ..................................................MA
KEYPAD PANIC (audible)..........................................................120 ..................................................PA
KEYPAD PANIC (silent) .............................................................121 ..................................................HA
KEYPAD TAMPER.....................................................................137 ..................................................TA
LOW BATTERY (device number)...............................................309 ..................................................YT
LOW BATTERY RESTORE (device number).............................309 ..................................................YR
MANUAL TEST ..........................................................................601 ..................................................RX
OPEN (user number)..................................................................401 ..................................................OP
RECENT CLOSE (user number)................................................401 ..................................................CR
RF SENSOR LOST (zone number)............................................381 ..................................................*T
RF SENSOR RESTORE (zone number)....................................381 ..................................................*R
SENSOR BATTERY RESTORE (zone number) ........................384 ..................................................XR
SENSOR LOW BATTERY (zone number) .................................384 ..................................................XT
SIREN RESTORE (device number) ...........................................321 ..................................................YH
SIREN TAMPER (device number)..............................................321 ..................................................YA
START PROGRAM....................................................................627 ..................................................LB
TELEPHONE FAULT .................................................................351 ..................................................LT
TELEPHONE RESTORE ...........................................................351 ..................................................LR
ZONE ACTIVITY FAULT............................................................391 ..................................................NA
ZONE ACTIVITY RESTORE......................................................391 ..................................................NS
ZONE BYPASS (zone number)..................................................570 ..................................................*B
ZONE TAMPER (zone number) .................................................137 ..................................................TA
ZONE TAMPER RESTORE (zone number)...............................137 ..................................................TR
ZONE TROUBLE (zone number) ...............................................380 ..................................................*T
ZONE TROUBLE RESTORE (zone number).............................380 ..................................................*R
THE NUMBER IN PARENTHESES FOLLOWING THE EVENT IS THE NUMBER THAT WILL BE REPORTED AS THE ZONE
NUMBER. IF THERE ARE NO PARENTHESES, THE ZONE WILL BE A0". SEE PAGE 52 FOR THE DEVICE NUMBERS.
* The character transmitted in this slot will be the first character from the event code of the zone that is bypassed or in trouble. (See
locations 110 - 141)
50
NX-8V2 Control
Download from Www.Somanuals.com. All Manuals Search And Download.
XVII.
APPENDIX 2
REPORTING ZONE CODES IN SIA OR CONTACT ID
The NX-8V2 has the ability to report SIA level 1 transmissions to either or both phone numbers. Each report in SIA consists of an Event
Code and a Zone or User ID. The Zone ID will be the zone number that is in alarm. The event code will come from the chart below and
be programmed in the zone type event code.
Programmed Event Code
SIA Code
Description
0....................................................... HA.............................................................. Holdup Alarm
1....................................................... FA.............................................................. Fire Alarm
2....................................................... PA.............................................................. Panic alarm
3....................................................... BA.............................................................. Burglary Alarm
4....................................................... BA.............................................................. Burglary Alarm
5....................................................... BA.............................................................. Burglary Alarm
6....................................................... UA.............................................................. Untyped Alarm
7....................................................... BA.............................................................. Burglary Alarm
8....................................................... BA.............................................................. Burglary Alarm
9....................................................... UA.............................................................. Untyped Alarm
10...................................................... HA.............................................................. Holdup Alarm
11...................................................... MA ............................................................. Medical Alarm
12...................................................... PA.............................................................. Panic alarm
13...................................................... TA.............................................................. Tamper Alarm
14...................................................... RP.............................................................. Periodic Test
15...................................................... GA ............................................................. Gas Alarm
16...................................................... KA.............................................................. Heat Alarm
17...................................................... WA............................................................. Water Alarm
18...................................................... QA ............................................................. Emergency Alarm
19...................................................... SA.............................................................. Sprinkler Alarm
20...................................................... ZA.............................................................. Freeze Alarm
21...................................................... KH.............................................................. High Temp Alarm
22...................................................... FA.............................................................. Manual Fire Alarm
The NX-8V2 has the ability to report Ademco Contact ID transmissions. Each report in Contact ID consists of an Event Code and a
Zone ID. The zone ID is the zone that created the alarm. The event code will come from the chart below and be programmed in the
zone type event code.
Programmed Event Code
Contact ID Code
Description
0....................................................... 122............................................................. Silent Panic
1....................................................... 110............................................................. Fire Alarm
2....................................................... 120............................................................. Panic alarm
3....................................................... 130............................................................. Burglary Alarm
4....................................................... 131............................................................. Perimeter Alarm
5....................................................... 132............................................................. Interior Alarm
6....................................................... 133............................................................. 24 Hour Burglary
7....................................................... 134............................................................. Entry Alarm
8....................................................... 135............................................................. Day/Night Alarm
9....................................................... 150............................................................. Non Burglary 24 Hour
10...................................................... 121............................................................. Duress Alarm
11...................................................... 100............................................................. Medical Alarm
12...................................................... 123............................................................. Audible Panic Alarm
13...................................................... 137............................................................. Tamper Alarm
14...................................................... 602............................................................. Periodic Test
15...................................................... 151............................................................. Gas Detected
16...................................................... 158............................................................. High Temp
17...................................................... 154............................................................. Water Leakage
18...................................................... 140............................................................. General Alarm
19...................................................... 140............................................................. General Alarm
20...................................................... 159............................................................. Low Temp
21...................................................... 158............................................................. High Temp Alarm
22...................................................... 115............................................................. Manual Fire Alarm
NX-8V2 Control
51
Download from Www.Somanuals.com. All Manuals Search And Download.
XVIII. APPENDIX 3
EXPANDER NUMBERS FOR REPORTING EXPANDER TROUBLE
The tables below list the device numbers that will be reported for trouble conditions.
Device
NX-8V2 Control Panel
Device # reported
0
See page 50 for possible report codes.
NX-534E Two Way Listen-In
NX-540E “Operator”
NX-591E Cellemetry Interface
64
40
76
KEYPADS
KEYPAD
PART 1
192
PART 2
193
PART 3
PART 4
195
PART 5
196
PART 6
197
PART 7
198
PART 8
199
1
2
3
4
5
6
7
8
194
202
210
218
226
234
242
250
200
208
216
224
232
240
248
201
209
217
225
233
241
249
203
211
219
227
235
243
251
204
212
220
228
236
244
252
205
213
221
229
237
245
253
206
214
222
230
238
246
254
207
215
223
231
239
247
255
HARDWIRE EXPANDER (NX-216E)
Starting zone number
Expander # reported
Zone 09 (All switches off)
Zone 09 (Switch 1 on)
Zone 17 (Switch 2 on)
Zone 25 (Switches 1 & 2 on)
Zone 33 (Switch 3 on)
Zone 41 (Switches 1 & 3 on)
22
23
16
17
18
19
REMOTE POWER SUPPLY (NX-320E)
Switch Setting
All switches off
Switch 1 on
Switch 2 on
Switch 1 & 2 on
Switch 3 on
Switch 1 & 3 on
Switch 2 & 3 on
WIRELESS RECEIVER (NX-448E)
Switch Setting
All switches off
Switch 1 on
Switch 2 on
Switches 1 & 2 on
Switch 3 on
Switches 1 & 3 on
Switches 2 & 3 on
Switch 1, 2 & 3 on
Address
84
Expander # reported
35
36
37
38
39
32
33
34
85
86
87
88
89
90
91
Switches 1, 2, & 3 on
OUTPUT MODULE (NX-508E)
Switch Setting
Switch 1 & 2 on
Switch 3 on
Address
Switch Setting
Switch 2 & 3 on
Switch 1,2,&3 on
All switches off
Address
Switch Setting
Switch 1 on
Switch 2 on
Address
24
25
26
27
28
29
30
31
Switch 1 & 3 on
52
NX-8V2 Control
Download from Www.Somanuals.com. All Manuals Search And Download.
XIX.
APPENDIX 4
USER ID OR ZONE ID HEX DIGIT FOR 4+2 FORMATS
The following appendix applies only to slow formats (locations 56- 83 lower digit). The digit programmed in the locations will be
sent as the upper HEX digit in place of the alarm event code. The zone ID or user ID will always be reported as the lower HEX digit (1-
F) as shown in the chart below. For example, if the zone ID or user ID is 15, the 4+2 lower digit will be “F”. Use the chart shown below
for convenience.
ꢀ
If Segments 2-8 are left as “0” (unprogrammed), they will follow the Segment 1 selection. If Segment 1 is left as “0” and the
feature is enabled in Location 23, the NX-8V2 will report “A”.
ZONE
ZONE
ZONE
HEX
1
HEX
4
HEX
7
USER
USER
USER
1
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
2
2
5
8
3
3
6
9
4
4
7
A
B
C
D
E
F
1
5
5
8
6
6
9
7
7
A
B
C
D
E
F
1
8
8
9
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
A
B
C
D
E
F
1
2
3
4
2
5
3
7
4
8
2
5
9
3
6
A
B
C
D
E
F
1
4
7
5
8
6
9
7
A
B
C
D
E
F
1
8
9
A
B
C
D
E
F
1
2
3
4
5
2
6
3
7
4
8
2
5
9
3
6
NX-8V2 Control
53
Download from Www.Somanuals.com. All Manuals Search And Download.
XX.
LOCAL TELEPHONE COMPANY INTERFACE INFORMATION
TELEPHONE CONNECTION REQUIREMENTS
Except for telephone company provided ringers, all connections to the telephone network shall be made through standard plugs and
standard telephone company provided jacks or equivalent in such a manner as to allow for immediate disconnection of the terminal
equipment. Standard jacks shall be so arranged that if the plug connected thereto is withdrawn, no interference to the operation of the
equipment at the customer’s premises, which remains connected to the telephone network, shall occur by reason of such withdrawal.
INCIDENCE OF HARM
Should terminal equipment or protective circuitry cause harm to the telephone network, the telephone company shall, where practical,
notify the customer that temporary discontinuance of service may be required. However, where prior notice is not practical, the
telephone company may temporarily discontinue service if such action is deemed reasonable in the circumstances. In the case of such
temporary discontinuance, the telephone company shall promptly notify the customer who will be given the opportunity to correct the
situation. The customer also has the right to bring a complaint to the FCC if he feels the disconnection is not warranted.
CHANGES IN TELEPHONE COMPANY EQUIPMENT OR FACILITIES
The telephone company may make changes in its communications facilities, equipment, operations, or procedures where such action
is reasonably required and proper in its business. Should any such change render the customers terminal equipment incompatible with
the telephone company facilities, the customer shall be given adequate notice to make modifications to maintain uninterrupted service.
GENERAL
The FCC prohibits customer-provided terminal equipment to be connected to party lines.
IMPORTANCE OF THE RINGER EQUIVALENCE NUMBER
The Ringer Equivalence Number (REN) of this device is 0.1B. This number is a representation of the electrical load that it applies to
your telephone line.
MALFUNCTION OF THE EQUIPMENT
In the event that the device should fail to operate properly, the customer shall disconnect the equipment from the telephone line to
determine if it is the customers’ equipment that is not functioning properly. If the problem is with the device, the customer shall
discontinue use until it is repaired.
EQUIPMENT INFORMATION
Manufacturer Of Connecting Equipment: GE SECURITY, INC.
FCC Registration Number: US:GCQAL01BNX-V2, RINGER EQUIVALENCE: 0.1 B
XXI.
INDUSTRY CANADA INFORMATION
NOTICE: The Industry Canada label identifies certified equipment. This certification means that the equipment meets
telecommunications network protective, operational and safety requirements as prescribed in the appropriate Terminal Equipment
Technical Requirements document(s). The Department does not guarantee the equipment will operate to the user’s satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local
telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer should
be aware that compliance with the above conditions might not prevent degradation of service in some situations.
Repairs to certified equipment should be coordinated by a representative designated by the supplier. Any repairs or alternations made
by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request the user to
disconnect the equipment.
Users should ensure for their protection that the electrical ground connections of the power utility, telephone lines and internal metallic
water pipe system, if present, are connected together. This precaution may be particularly important in rural areas.
Caution: Users should not attempt to make such connections themselves, but should contact the appropriate electrical inspection
authority, or electrician, as appropriate.
The Ringer Equivalence Number (REN) of this device is 0.1B. This number is a representation of the electrical load that it applies to
your telephone line. NOTICE: The Ringer Equivalence Number (REN) assigned to each terminal device provides an indication of the
maximum number of terminals allowed to be connected to a telephone interface. The termination on an interface may consist of any
combination of devices subject only to the requirement that the sum of the Ringer Equivalence Numbers of all the devices does not
exceed 5.
54
NX-8V2 Control
Download from Www.Somanuals.com. All Manuals Search And Download.
XXII.
NOTICES
Network Compatibility Declaration
(Applies to products which have the CE mark attached)
We declare under our sole responsibility that this product is
designed to work with the networks in the countries marked
with a check (ꢁ) and may have interworking problems with the
countries that are not checked. Due to the inherent differences
in the individual PSTNs, certain software settings may need to
be adjusted on a country-to-country basis. If it is desired to use
this equipment on a network other than the one on which it
was originally installed, you should contact your equipment
supplier.
Declaration Of Conformity
Manufacturer’s Name:
Caddx Controls
Manufacturer’s Address: 1420 North Main Street
Gladewater Texas 75647
EU Representative:
Interlogix Europe
(ꢁ) Austria
(ꢁ) Belgium
(ꢁ) Denmark
(ꢁ) Finland
(ꢁ) France
(ꢁ) Germany
(ꢁ) Greece
(ꢁ) Iceland
(ꢁ) Ireland
(ꢁ) Italy
(_) Liechtenstein
(ꢁ) Luxembourg
(ꢁ) Netherlands
(ꢁ) Norway
(ꢁ) Poland
(ꢁ) Portugal
(ꢁ) Spain
(ꢁ) Sweden
(ꢁ) Switzerland
(ꢁ) United Kingdom
Product Identification
Product:
Model Numbers: NX-8V2
Brand:
NetworX
CADDX
R&TTE Directive
See EMC and LVD tests below
EMC Directive
EN50081-1
EN50130-4
EN55022
EN60950
EN61000-3-2
EN61000-3-3
Telecom Approval Notice
This equipment has been approved in accordance with the
Council Decision 98/482/EC for pan-European, single terminal
connection to the public switched telephone network (PSTN).
However, due to the differences between the individual PSTNs
provided in different countries, the approval does not, of itself,
give an unconditional assurance of successful operation on
every PSTN network termination point. In the event of
problems, you should contact your equipment supplier in the
first instance.
LVD Directive
EN 60950: 1999-4 3rd edition
Means of Conformity
Electrical Requirements
This device automatically adjusts to voltages within the range
of 230 V 50/60 Hz.
We declare under our sole responsibility that this product is in
conformity with Directive 1999/5/EC (R&TTE); Directive
73/23/EEC (LVD); and Directive 89/336/EEC (EMC) and
based on test results using (non)-harmonized standards in
accordance with the Directives mentioned.
Fuse: Type T 200mA 250 VAC
Additional Tests
This equipment has been tested and found to comply with the
following standards (which are no longer required for
compliance).
NX-8V2 Control
55
Download from Www.Somanuals.com. All Manuals Search And Download.
XXIII. UNDERWRITERS LABORATORIES INFORMATION
The NetworX NX-8V2 holds the following listings from Underwriters Laboratories (US and Canadian):
UL294
Access Control System Units
UL365
UL609
CAN/ULC-S303-M91
Police Station Connected Burglar Alarms
Local Grade A Mercantile, Police Station Connect with Basic Line Security
* requires #NX-003-C enclosure
UL985
CAN/ULC-S545-M89
UL1023
Household Fire
Household Burglary
ORD-C1023-1974
UL1610
CAN/ULC-S304-M88
UL1635
Grade B & C Central Station Burglar Alarm Unit
Digital Alarm Communicator System Units
Home Health Care Signaling
UL1637
WHEN INSTALLING AN NX-8V2 IN COMPLIANCE WITHUNDERWRITERS LABORATORIES, THE FOLLOWING INSTRUCTIONS
MUST BE OBSERVED:
•
•
•
•
•
•
Initiating and indicating devices must be rated at 11.5 to 12.4 V DC residential, 12.0 V DC commercial.
When using partitioning in Commercial Burglary applications, the main control must be protected by a 24-hour alarm circuit.
Force Arming and Auto Arming shall not be enabled.
For residential fire applications, the indicating devices shall be a Wheelock 34T-12 or equivalent.
The "Listen-In" feature shall not be enabled.
The Siren/Bell Test shall be enabled. The auxiliary outputs controlling the audible device require a minimum cutoff time of 15
minutes for commercial burglary, 4 minutes for residential applications, or 30 minutes for Commercial Burglary for Canada.
•
•
•
•
•
•
•
For residential fire installations, the Dynamic Battery Test time cannot exceed four (4) hours.
Ringback shall be enabled on UL commercial burglary installations.
On commercial burglary installations, the fire initiating circuits shall not be connected.
The Entry-Guard feature shall be disabled.
Group Bypassing shall be disabled.
Delay before dial seizure shall be set to "0".
Total current draw from aux power connections at terminal positions POS, AUX PWR, and SMOKE PWR must not exceed
400 mA.
•
•
Remote Downloading shall not be used on UL listed systems.
For residential burglary applications, the maximum entry and exit delay times shall be 45 and 60 seconds respectively. The
exit delay time shall not exceed 60 seconds for commercial burglar alarm applications.
•
•
•
•
•
•
•
•
The keyswitch options shall not be used.
The Telephone Line Monitor shall be enabled.
The Telephone Line Cut delay shall not exceed 90 seconds.
24-hour communicator test transmission is required.
For 24 hours of standby power using a 7.0 AH battery, limit auxiliary power load to 140 mA.
For 24 hours of standby power using a 17.2 AH battery, limit auxiliary power load to 400 mA.
The silent keypad option shall not be enabled.
UL has only verified compatibility with the following listed DACRs and formats: Sure-Gard SG-MLR2-DG: 2,9,10,12,13,14;
Silent Knight 9000 - 2,12; FBI - CP220FBI, 13; and Ademco 685: 2,11,12, and 13.
•
For burglary installations, cross-zoned detectors shall overlap 100 percent in the area of coverage and similar coverage areas
must be used. For example, interior protection is cross-zoned with interior protection, and so on.
•
•
•
Expander trouble must activate the siren (Loc. 37, Segment 2, LED 2)
For UL 1637, expander trouble must activate keypad sounder (Loc. 39, Segment 1, LED 8)
If the Late to Close/Early to Open feature is enabled, the Opening and Closing reports shall be enabled (Loc. 23, Seg. 4,
Option 1 and Loc. 23, Seg. 3, Option 1).
•
ꢃ
ꢃ
For Canadian installations, the class II transformer secure tab shall not be employed.
The 4-wire smoke detector employed shall be rated to operate over the voltage range of 11.5 to 12.4V.
Compatible listed devices: (Special Applications)
o Bell Output (Sirens): Wheelock models: NS-1215W, NS-121575W, NS4-1215W, NS4-121575W, AS-1215W, AS-121575W
o Horn / Strobe: System Sensor: S1224MC Strobe series; 1224MC Horn/Strobe series; H12/24 Horn series
o Smoke Output (4 wire detectors):
ꢄESL: 500N series; 449CTE series; 521 series; 541 series
ꢄSystem Sensor models: 2112/24R; 2112/24TR; 2112/24AT; 2112/ATR; 2112/24AITR; 4WTA-B; 4WTR-B; 4WTAR-B; 4WITAR-B.
ꢄDetection Systems: F220-B6C; D273 series
ꢄHochiki: SBC-4/12, 4/12W
56
NX-8V2 Control
Download from Www.Somanuals.com. All Manuals Search And Download.
MINIMUM SYSTEM CONFIGURATIONS FOR UL INSTALLATIONS
(Residential Fire, Residential Burglary, Commercial Burglary)
•
•
•
The NetworX NX-8V2 panel is necessary to initiate Residential and Commercial installations.
At least one compatible keypad is needed for all applications.
At least one bell fixture is required for all applications, except Grade C Central Station. For Grade A Local, the AD10-12 bell
and Grade A bell housing shall be used.
•
•
•
•
Commercial UL applications require #NX-003-C metal enclosure. Supplied screws to be used.
A minimum of two (2) keypads is required for Home Health applications and each keypad must be set to a unique address.
The wireless devices are only UL listed for residential applications.
The DACT shall be enabled for all commercial burglary applications.
STANDBY TIME
TOTAL AUXILIARY
CURRENT
1.9 Amps
1.25 Amps
600 mA
STANDBY BATTERY
CAPACITY
51 AH
ALARM CURRENT
24 hours
600 mA
1 Amp
1 Amp
1 Amp
1 Amp
1 Amp
1 Amp
1 Amp
1 Amp
34 AH
17 AH
51 AH
34 AH
17 AH
51 AH
34 AH
17 AH
48 hours
72 hours
900 mA
600 mA
300 mA
600 mA
400 mA
200 mA
Calculations based on three 17-Amp batteries.
IMPORTANT!
K
If separate power supplies are necessary to accommodate additional devices, safety standards require that each power
supply be prominently marked with adequate instructions for removing all power from the unit.
Dispose of used batteries according to the manufacturer’s instructions and/or local government authorities.
Installation personnel should thoroughly read and understand the installation instructions and the users manuals for the panel
and all the accessories to be included with the system before attempting to install a security system.
WARNING!
ꢅ
Replace only with Panasonic #LC12V4BP or Yuasa #NP4-12 battery. Observe polarity when installing a new battery.
Installing the battery backwards may cause damage to the panel. There is a risk of explosion if the battery is replaced with an
incorrect type.
NOTE
Electrical codes will vary depending upon the country and city where the system is installed. It is the installer’s responsibility
to ensure that the electrical installation is safe and conforms to all applicable codes, laws, or regulations. Only qualified
persons should connect this device to the mains supply.
NX-8V2 Control
57
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
SYSTEM NOTES
Download from Www.Somanuals.com. All Manuals Search And Download.
XXV.
SPECIFICATIONS
OPERATING POWER
16.5 VAC 40, or 50 VA Transformer
AUXILIARY POWER
w/25 VA Transformer
w/40 or 50 VA Transformer
w/NX-320E Power Supply
12 VDC Regulated 500 mA
12 VDC Regulated 1 AMP
12 VDC Regulated 2 AMPS + Control
Panel Power
LOOP RESISTANCE
Standard Loop
2-Wire Smokes
300 Ohms Maximum
30 Ohms Maximum
BUILT-IN SIREN DRIVER
LOOP RESPONSE
2-tone (Temporal and Yelp)
Selectable 50mS or 500mS
32 to 120 degrees F
OPERATING TEMPERATURE
LED KEYPAD
Current Draw
Zones Normal w/o Sounder
Dimensions
130 mA max.
55 mA
6.4" Wide
4.0" High
1.1" Deep
NX148E LCD KEYPAD
Current Draw
w/o Sounder
110 mA max.
75 mA
Dimensions
6.4" Wide
5.3" High
1.0" Deep
METAL ENCLOSURE DIMENSION
SHIPPING WEIGHT
11.25" Wide
11.25" High
3.50" Deep
9 lbs.
Main
Outside the US
Main Fax
800-727-2339
903-845-6941
903-845-6811
Technical Support
Sales & Literature
888-437-3287
800-547-2556
Web: www.gesecurity.com
UL approved
for ANSI/SIA
CP-01-2000
NX-8V2 INSTALLATION MANUAL
NX8V2ID05 REV. D (APR 2005)
Download from Www.Somanuals.com. All Manuals Search And Download.
|