The Remote Control Smart Sweeper is an intelligent
component for simple lighting control. It provides 12
individual switch inputs and one Master input for a group
of 12 relays. Each input will accept any 2- or 3-wire
switch. The RSP12 converts any switch input to a
momentary output to drive the corresponding relay(s).
Each output can drive up to three relays in parallel.
WHITE
RED
REV 0
HORTON CONTROLS COPYRIGHT
BLACK Y
BLACK
WHITE
S
W
T
1
BLACK
437D687
BLUE
RSP12
1 WHITE
RED
R
L
RED
S
BLACK
W
BLACK Y
2
BLUE
T
2 WHITE
RED
S
BLACK
W
T
3 WHITE
The RSP12 also provides several advanced functions for
basic lighting automation. Besides the Master ON/OFF
function, it allows options for Time Delay and Flick
Warning for individual overrides, as well as Automatic
ON for all lights.
RED
S
BLACK
W
E
T
4 WHITE
MASTER SWITCH
Y PWR
ACCESSOR
24V RECT
INPUT
POWER INPUT
AC
RED
S
BLACK
W
24V
T
otal Lighting Control
GE T
RSP12
Catalog Number
Description
Remote Control Smart Sweeper
Converts 2- or 3-wire switch inputs to momentar
Each switch input drives corresponding relay output.
Master Switch controls all 12 outputs.
5 WHITE
The RSP12 should be installed in a lighting automation
panel or an accessory cabinet as detailed on the
following page.
RED
S
BLACK
W
y outputs.
T
1
SWITCHINPUT
6 WHITE
Installation
AC power to Power Input.
•
•
•
Wire 24V
RED
S
Connect up to 3 relays to each Relay Output.
Wire any 2- or 3- wire switch to Switch Inputs, including
Master Switch, if desired.
BLACK
W
T
7 WHITE
FEATURES
Close contact during normal working hours.
Occupied –
Opening contact turns OFF all relays and enables time delays.
ime Delay –
• T
to 8=2 hrs. 9=1 min. test). After "occupied" hours, any
relays manually switched ON will automatically turn OFF
Set dial in 15-minute increments (1=15min.
RED
S
• 12 individual relay outputs, with up to 3 relays wired
in parallel per output.
after the set amount of time.
arn –
• W
BLACK
W
Lights "flick" 5-minutes before turning OFF at
).
NO
or
YES
end of day or time delay (
T
).
NO
8 WHITE
Lights turn ON automatically at start of normal
• Auto On –
working hours (
LISTED 533F
) or require manual switch ON (
YES
• 12 individual switch inputs (one per relay) and one
Master input.
vice: 1-800-884-4852
Ser
RED
S
ENERGY MANAGEMENT
EQUIPMENT SUBASSEMBL
Y
R
Made in U.S.A.
BLACK
W
GE Wiring Devices
wick, RI
T
ar
W
• Inputs accept any 2- or 3-wire switch (dry contact).
• Master ON/OFF control for group of relays while
retaining individual switch override.
• Additional control of subgroups by tying any
combination of inputs together.
9 WHITE
RED
S
WBLACK
T
1
WHITE
0
L
Y
1
1
BLACK
BLUE
RED
S
WBLACK
• “Occupied” contact to indicate normal working hours.
• Option to turn lights on automatically at start of
normal working hours.
• Time delay in 15-minute increments up to 2 hours.
• Option to “flick warn” occupants 5 minutes before
lights go off.
T
1
RED
WHITE
1
R
L
Y
1
2
AUTO ON
YES
BLACK
BLUE
RED
WARN
S
TIME DELAY
2
1
YES
NO
W
O
N
T BLACK
NO
0
OCCUPIED
BLACK
1
2
WHITE
RED
ASM 437D688G
Before starting, read the installation instructions inside.
If you have questions call GE Service at:
1-877-584-2685 (USA) or 1-800-661-6619 (Canada)
Installation Instructions
IMRSP12
Download from Www.Somanuals.com. All Manuals Search And Download.
Catalog Number: RSP12
CAUTION: The power supply must be OFF when
inserting or removing components. These instructions
assume the panel has a standard cover which exposes
both line-voltage and low-voltage sections. The line-
voltage sections must be covered to avoid exposure to
live high-voltage wiring.
INSTALLATION
There are two recommended ways to install the RSP12
Remote Control Smart Sweeper — in a Lighting
Automation Panel (LAP) or in an Accessory Cabinet near
a Lighting Automation Panel
18/2 AWG
2.
WIRE
24 VOLT
RECTIFIED
POWER
24V
24V
PILOT
COMMON
YELLOW
RECT
BLUE
RECT
BLUE
Installation in a Lighting Automation Panel
24VRECT ACC
BLUE WHITE
24VAC COM
A complete LAP assembly includes the following TLC
components:
RSP12
Tub
RTUB12, -24 or -48
Cover
Interior
RCOV12xx, -24xxx or -48xxx
RINTER0012RC, -0024RC or -0048RC*
ON TLC PANEL
MOTHERBOARD
Power Supply RPWRxxx
Relays
RR7P or RR9P
LOAD
* RINTER0012RC and -0024RC accept one RSP12, RINTER0048RC accepts one or two
RED BLACK YELLOW WHITE
1
Details for assembling a complete Lighting Automation
Panel are outlined separately in the RINTER installation
instructions. Once the panel is assembled and relays are
connected to the motherboard, the RSP12 may be
installed.
CIRCUIT
RRxP RELAY
ON TLC PANEL
MOTHERBOARD
20/2 AWG
RED
BLACK
BLUE
3.
WIRE
Basic Installation Steps
RELAYS
RSP12
1. Mount the RSP12(s) on the panel accessory bracket.
2. Wire 24V rectified power from the panel motherboard
to the blue and white power input tabs on the RSP12.
3. Wire red and black connections for each relay from
the panel motherboard to relay outputs on the RSP12.
4. Wire any 2- or 3-wire switch to the individual switch
inputs and/or the Master switch input on the RSP12
(not on the panel motherboard).
4. WIRE ANY 2- OR 3-WIRE SWITCHES
20/2 AWG 1000 FT. MAX.
RED
BLACK
WHITE
RED
5. Select additional control functions.
JUMP RED TO BLACK
MAINTAINED
BLACK
WHITE
ISOLATED
CONTACT
Installation in an Accessory Cabinet near the LAP
RED
BLACK
WHITE
20/2 AWG 1000 FT. MAX.
JUMP BLACK TO WHITE
Accessory cabinets with covers include:
RED
BLACK
WHITE
RBS1
RBS2
Accepts one (1) RSP12
Accepts two (2) RSP12s
RED
BLACK
WHITE
2-WIRE
MOMENTARY
PUSH BUTTON
Mount the RSP12 in the accessory cabinet and wire the
same as above.
RED
BLACK
WHITE
20/3 AWG 1000 FT. MAX.
RSP12
RED
BLACK
WHITE
RED
BLACK
WHITE
STANDARD
3-WIRE
MOMENTARY
RED
BLACK
WHITE
20/3 AWG 1000 FT. MAX.
RED
12-RELAY
LIGHTING
BLACK
WHITE
AUTOMATION
PANEL
24-RELAY LIGHTING
AUTOMATION PANEL
RED
BLACK
WHITE
STANDARD
3-WIRE
MAINTAINED
RED
BLACK
WHITE
48-RELAY LIGHTING
AUTOMATION PANEL
1. MOUNT RSP12 IN PANEL
Download from Www.Somanuals.com. All Manuals Search And Download.
Catalog Number: RSP12
EMERGENCY SERVICE OR SUPPORT:
1-877-584-2685 (USA) or 1-800-661-6619 (Canada)
ADDITIONAL CONTROL FUNCTIONS
Four optional control functions are available at the
bottom of the RSP12 board: Occupied, Time Delay, Warn
and Auto Off. Set these functions for all relays connected
to the RSP12 as a group, based on the needs at the site.
RSP12
WARN
YES
AUTO ON
YES
NO
0
OCCUPIED
RD WHTE
NO
Occupied
20/2 AWG 1000 FT. MAX.
The Occupied contact is available for connection with a
timeclock or building automation system. It indicates
when the building is operating under normal working
hours (CLOSED contact) or after hours (OPEN contact).
Properly connecting and scheduling the Occupied
contact determines when other functions will be enabled.
MAINTAINED ISOLATED CONTACT
IN TIME CLOCK (BY OTHERS)
OCCUPIED CONTACT
Time Delay
RSP12
If the Time Delay function is set, when an occupant turns
on a switch after hours (Occupied contact OPEN), the
RSP12 will turn off the lights again after a predetermined
amount of time. Each occupant override will have its own
time delay.
WARN
YES
NO
AUTO ON
YES
N
0
OCCUPIED
RED WHITE
0
TIME DELAY
0 = NO TIME DELAY
1 = 15-MINUTE DELAY
2 = 30-MINUTE DELAY
3 = 45-MINUTE DELAY
…ETC. TO…
8 = 2-HOUR DELAY
9 = 1-MINUTE TEST
Set the Time Delay dial as follows:
0
No time delay (no automatic off; lights must be
manually turned off)
1-8 15-minute to 2-hour delay, in 15-minute
increments
9
1-minute test
RSP12
WARN
YES
NO
AUTO ON
YES
NO
Warn
0
CCUPIED
WHITE
When the RSP12 turns relays OFF (at the end of normal
working hours, or at the end of a time delay), it will
optionally warn the occupants by blinking the lights five
minutes before they go off.
WARN
YES
NO
1
O
N
WARN SWITCH
Set the WARN switch to YES or NO as follows:
YES Gives a 5-minute warning before lights turn off
NO Turns lights off without giving the warning
Auto On
RSP12
When the Occupied contact closes at the start of normal
working hours, the RSP12 can optionally turn all the
relays ON automatically.
WARN
YES
NO
AUTO ON
YES
NO
0
CCUPIED
WHITE
Set the AUTO ON switch to YES or NO as follows:
AUTO ON
YES
NO
2
YES Automatically turns all relays ON at start of
normal working hours
NO Manual switch required to turn relays ON
AUTO ON SWITCH
GE Lighting Controls, 41 Woodford Ave., Plainville, CT 06062
Made in U.S.A.
Download from Www.Somanuals.com. All Manuals Search And Download.
|