FieldServer Computer Drive FS 8700 43 User Manual

A Sierra Monitor Company  
Driver Manual  
(Supplement to the FieldServer Instruction Manual)  
FS-8700-43 VESDA  
APPLICABILITY & EFFECTIVITY  
Effective for all systems manufactured after May 1, 2001  
Driver Version:  
1.01  
Document Revision: 2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-43 VESDA Driver Manual  
Page 3 of 18  
1.  
VESDA Description  
The VESDA driver allows the FieldServer to transfer data to and from devices over RS-232  
using VESDA protocol. The FieldServer can emulate a VESDA Client.  
The information that follows describes how to expand upon the factory defaults provided in the  
configuration files included with the FieldServer.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-43 VESDA Driver Manual  
Page 4 of 18  
2.  
Driver Scope of Supply  
2.1. Supplied by FieldServer Technologies for this Driver  
FieldServer  
Technologies PART #  
DESCRIPTION  
FS-8915-10  
FS-8917-02  
FS-8917-01  
FS-8700-43  
UTP cable (7 foot) for RS-232 use  
RJ45 to DB9F connector adapter  
RJ45 to DB25M connector adapter  
Driver Manual  
2.2.  
Provided by Supplier of 3rd Party Technology  
PART #  
DESCRIPTION  
VESDA PC Link HLI  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-43 VESDA Driver Manual  
Page 5 of 18  
3.  
Hardware Connections  
The FieldServer is connected to the Vesda as shown in connection drawing.  
Configure the Vesda according to manufacturer’s instructions  
LaserPlus  
ETA232  
FieldServer  
X20/X40  
VESDA HLI  
LaserPlus  
LaserPlus  
LaserPlus  
VESDAnet  
(408)-262-2299  
FIELDSERVER  
VESDA  
CONNECTION CONFIGURATIONS  
BASE NAME:  
FILE NAME:  
DATE: 3/17/04  
BY: MC  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-43 VESDA Driver Manual  
Page 6 of 18  
4.  
Configuring the FieldServer as a VESDA Client  
For a detailed discussion on FieldServer configuration, please refer to the FieldServer  
Configuration Manual. The information that follows describes how to expand upon the factory  
defaults provided in the configuration files included with the FieldServer (See “.csv” sample files  
provided with the FieldServer).  
This section documents and describes the parameters necessary for configuring the FieldServer  
to communicate with a Vesda Server.  
4.1.  
Data Arrays  
The configuration file tells the FieldServer about its interfaces, and the routing of data  
required. In order to enable the FieldServer for Vesda communications, the driver  
independent FieldServer buffers need to be declared in the “Data Arrays” section, the  
destination device addresses need to be declared in the “Client Side Nodes” section, and  
the data required from the servers needs to be mapped in the “Client Side Map Descriptors”  
section. Details on how to do this can be found below.  
Note that in the tables, * indicates an optional parameter, with the bold legal value being the  
default.  
Section Title  
Data_Arrays  
Column Title  
Function  
Legal Values  
Up to 15 alphanumeric  
characters  
Data_Array_Name  
Provide name for Data Array  
Data_Format  
Data_Array_Length  
Provides data format  
Number of Data Objects  
BIT,FLOAT,BYTE  
1-10000  
Example:  
// Data Arrays  
Data_Arrays  
Data_Array_Name,  
set_op,  
Data_Format,  
bit,  
float,  
bit,  
float,  
bit,  
float,  
bit,  
Data_Array_Length  
32  
32  
32  
32  
32  
32  
32  
32  
32  
VESDA01_1_f,  
VESDA01_1_b,  
VESDA01_2_f,  
VESDA01_2_b,  
VESDA01_3_f,  
VESDA01_3_b,  
VESDA01_4_f,  
VESDA01_4_b,  
float,  
bit,  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-43 VESDA Driver Manual  
Page 7 of 18  
4.2.  
Client Side Node Descriptors  
Section Title  
Nodes  
Column Title  
Function  
Legal Values  
Up to 32 alphanumeric  
characters  
VESDA  
Node_Name  
Protocol  
Provide name for node  
Specify protocol used  
Example:  
Nodes  
Node_name,  
VESDA_HLI,  
Protocol,  
VESDA,  
Port, Timeout,  
P1, 10.0s,  
Recovery_Interval,  
-,  
Retry_Interval  
-
4.3.  
Client Side Connection Descriptors  
Section Title  
Connections  
Column Title  
Function  
Legal Values  
Specify which port the device  
is connected to the FieldServer  
Specify baud rate  
Specify parity  
Specify data bits  
Port  
P1-P8, R1-R21  
Baud  
Parity  
Data_Bits  
19200  
None  
8
Stop_Bits  
Timeout  
IC_timeout  
Specify stop bits  
Message timeout  
Inter character timeout  
1
10s  
1.0s  
Example:  
// Client Side Connections  
//  
Connections  
Port,  
P1,  
Baud,  
19200,  
Timeout,  
10.0s,  
IC_Timeout, Parity,  
1.0s, none,  
Data_bits, Stop_bits  
8,  
1
1
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction  
manual for details of the ports available on specific hardware.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-43 VESDA Driver Manual  
Page 8 of 18  
4.4.  
4.4.1.  
Client Side Map Descriptors  
FieldServer Related Map Descriptor Parameters  
Column Title  
Function  
Legal Values  
Up to 32 alphanumeric  
characters  
Map_Descriptor_Name Name of this Map Descriptor  
Name of Data Array where  
One of the Data Array  
names from “Data Array”  
section above. Must be of  
type BIT  
data is to be stored in the  
Data_Array_Name  
FieldServer. Only used for  
commands 1,4,6,12.  
0 to maximum specified in  
“Data Array” section above  
Data_Array_Location  
Function  
Starting location in Data Array  
Function of Client Map  
Descriptor. A Command is a  
write, and a response is a read  
RDBC, WRBC, WRBX  
4.4.2.  
Driver Related Map Descriptor Parameters  
Column Title  
Function  
Legal Values  
One of the node names  
Node_Name  
Name of Node to fetch data from specified in “Client Node  
Descriptor” above  
Data_Type  
Length  
Data type  
Dig_input or dig_output  
Length of Map Descriptor  
1 to end of data block or less  
The start bit number of the data  
of interest  
Address  
Starting address of read block  
The command id as given in the  
notes.  
The network number  
Command  
Network  
Zone  
1,4,6,10,12,16  
1-255  
1-255 or 0 if the Zone is not  
configured on the Panel  
1-255 or 0 to read the average  
smoke level and highest alarms.  
One of the Data Array names  
The zone number  
Sector  
The sector number  
Name of Data Array where data  
DA_Bit_Name  
DA_Bit_offset  
is to be stored in the FieldServer. from “Data Array” section above.  
Used for command 10 and 16.  
Starting location in Data Array.  
Used for command 10 and 16  
Name of Data Array where data  
Must be of type BIT  
0 to maximum specified in “Data  
Array” section above  
One of the Data Array names  
DA_Float_Name is to be stored in the FieldServer. from “Data Array” section above.  
Only used for command 10.  
Starting location in Data Array.  
Only used for command 10  
Name of Data Array where data  
Must be of type FLOAT  
0 to maximum specified in “Data  
Array” section above  
DA_Float_offset  
One of the Data Array names  
DA_Byte_Name is to be stored in the FieldServer. from “Data Array” section above.  
Only used for command 16.  
Starting location in Data Array.  
Only used for command 16  
Must be of type BYTE  
0 to maximum specified in “Data  
Array” section above  
DA_Byte_offset  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-43 VESDA Driver Manual  
Page 9 of 18  
4.4.3.  
Map Descriptor Example  
Map_Descriptors  
Map_Descriptor_Name,  
set_op_vesda_hli,  
Data_Array_Name, Data_Array_Offset, Function,  
Data_Type, Node_Name, Address,  
Length,  
8,  
Command,  
1,  
Network,  
0,  
Zone,  
255,  
Sector  
-
set_op,  
0,  
WRBC,  
dig_output,  
VESDA_HLI,  
0,  
Map_Descriptors  
Map_Descriptor_Name,  
rd_vesda_01_1,  
rd_vesda_01_2,  
rd_vesda_01_3,  
rd_vesda_01_4,  
Zone,  
Sector,  
128,  
64,  
32,  
16,  
node_name,  
VESDA_HLI,  
VESDA_HLI,  
VESDA_HLI,  
VESDA_HLI,  
Function,  
DA_Bit_Name  
VESDA01_1_  
VESDA01_2_b  
VESDA01_3_b  
VESDA01_4_b  
DA_Float_Name,  
VESDA01_1_f,  
VESDA01_2_f,  
VESDA01_3_f,  
VESDA01_4_f,  
DA_Bit_offset,  
DA_Float_offset,  
Data_Array_Offset,  
Data_Type,  
Command,  
Network,  
Address,  
Length  
32  
32  
32  
32  
0,  
0,  
0,  
0,  
rdbc,  
rdbc,  
rdbc,  
rdbc,  
0,  
0,  
0,  
0,  
0,  
0,  
0,  
0,  
0
0
0
0
dig_input,  
dig_input,  
dig_input,  
dig_input,  
10,  
10,  
10,  
10,  
0,  
0,  
0,  
0,  
0,  
0,  
0,  
0,  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-43 VESDA Driver Manual  
Page 10 of 18  
4.5.  
Common Applications and Examples  
Each Command on the VESDA has a particular data format.  
4.5.1.  
VESDA data format for command 1 (Set Operation)  
This command is mandatory as it turns the VESDA system into a master slave  
relationship and is of type BIT. The content of the data is irrelevant. The format for the  
data is as follows:  
Data Arrays  
Column Title  
Data_Array_Name Provide name for Data Array  
Data_Format Provides data format  
Function  
Legal Values  
Up to 15 alphanumeric  
characters  
BIT  
8
Data_Array_Length Number of Data Objects  
Client Side Map Descriptors  
Column Title  
Function  
Name of this Map  
Descriptor  
Legal Values  
Up to 32 alphanumeric  
characters  
Map_Descriptor_Name  
Name of Data Array where  
data is to be stored in the  
FieldServer  
Data_Array_Name  
As above.  
Starting location in Data  
Array  
Function of Client Map  
Descriptor.  
Data_Array_Location  
Function  
0
WRBC, WRBX  
One of the node names  
specified in “Client Node  
Descriptor” above  
dig_output  
Name of Node to fetch data  
from  
Node_Name  
Data_Type  
Length  
Data type  
Length of Map Descriptor  
Starting address of read  
block  
8
0
Address  
The command id as given in  
the notes.  
Command  
1
Network  
Zone  
Sector  
The network number  
The zone number  
The sector number  
1-255  
1-255  
1-255  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-43 VESDA Driver Manual  
Page 11 of 18  
4.5.2.  
VESDA data format for command 4 (Zone Update)  
This request returns the Current Zone Status in a BIT data array. The format for the data  
is as follows:  
Data Arrays  
Column Title  
Function  
Legal Values  
Up to 15 alphanumeric  
characters  
BIT  
Data_Array_Name  
Provide name for Data Array  
Data_Format  
Provides data format  
Data_Array_Length Number of Data Objects  
1 - 16  
Client Side Map Descriptors  
Column Title  
Function  
Legal Values  
Name of this Map  
Descriptor  
Up to 32 alphanumeric  
characters  
Map_Descriptor_Name  
Name of Data Array where  
data is to be stored in the  
FieldServer  
Data_Array_Name  
As above.  
Starting location in Data  
Array  
Function of Client Map  
Descriptor.  
Data_Array_Location  
Function  
0 -16  
RDBC  
One of the node names  
specified in “Client Node  
Descriptor” above  
dig_input  
Name of Node to fetch data  
from  
Node_Name  
Data_Type  
Length  
Data type  
1-16 (must not overflow the  
data array)  
Length of Map Descriptor  
Starting address of read  
block  
The command id as given in  
the notes.  
Address  
1-16  
4
Command  
Network  
Zone  
Sector  
The network number  
The zone number  
The sector number  
1-255  
1-255  
1-255  
Data Block Description2  
BIT offset  
Function  
Other Zone Info  
Scanning  
Autolearning  
Normalising  
Isolated  
Fault Filter  
Fault Airflow  
Fault Network  
BIT offset  
8
9
10  
11  
12  
13  
14  
15  
Function  
0
1
2
3
4
5
6
7
Fault Power  
Fault Urgent  
Fault Zone  
Fault System  
Alarm Fire2  
Alarm Fire1  
Alarm Action  
Alarm Alert  
2 1 indicates TRUE; 0 indicates FALSE  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-43 VESDA Driver Manual  
Page 12 of 18  
4.5.3.  
VESDA data format for command 6 (Remote Input)  
This command sends the Remote Input in a BIT data array.  
Data Array  
Column Title  
Function  
Legal Values  
Provide name for Data  
Array  
Up to 32 alphanumeric  
characters  
Data_Array_Name  
Data_Format  
Provides data format  
BIT  
Data_Array_Length Number of Data Objects  
1 - 8  
Client Map Descriptors  
Column Title  
Function  
Name of this Map  
Descriptor  
Legal Values  
Up to 32 alphanumeric  
characters  
Map_Descriptor_Name  
Name of Data Array where  
data is to be stored in the  
FieldServer  
Data_Array_Name  
As above.  
Starting location in Data  
Array  
Function of Client Map  
Descriptor.  
Data_Array_Location  
Function  
0 –8  
WRBX  
One of the node names  
specified in “Client Node  
Descriptor” above  
dig_output  
Name of Node to fetch data  
from  
Node_Name  
Data_Type  
Length  
Data type  
1-8 (must not overflow the  
data array)  
Length of Map Descriptor  
Starting address of read  
block  
The command id as given in  
the notes.  
Address  
1-8  
6
Command  
Network  
Zone  
Sector  
The network number  
The zone number  
The sector number  
1-255  
1-255  
1-255  
Data Block Description34  
BIT offset  
Function  
0
1
2
3
4
5
6
7
Stop Test  
Scan Start  
Start Test  
Silence  
De-Isolate  
Isolate  
Reset  
Reserved  
3 1 indicates TRUE; 0 indicates FALSE  
4 ONLY 1 OF THE 8 BITS MAY BE SET IN ONE COMMAND  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-43 VESDA Driver Manual  
Page 13 of 18  
4.5.4.  
VESDA data format for command 12 (Current Fault Status)  
This request returns the Current Fault Status in a BYTE data array. The format for the  
data is as follows:  
Data Arrays  
Column Title  
Function  
Provide name for Data  
Array  
Legal Values  
Up to 15 alphanumeric  
characters  
Data_Array_Name  
Data_Format  
Provides data format  
BYTE  
Data_Array_Length Number of Data Objects  
1 – 21  
Client Side Map Descriptors  
Column Title  
Function  
Legal Values  
Name of this Map  
Descriptor  
Up to 32 alphanumeric  
characters  
Map_Descriptor_Name  
Name of Data Array where  
data is to be stored in the  
FieldServer  
Data_Array_Name  
As above.  
Starting location in Data  
Array  
Function of Client Map  
Descriptor.  
Data_Array_Location  
Function  
0
RDBC  
One of the node names  
specified in “Client Node  
Descriptor” above  
dig_input  
Name of Node to fetch data  
from  
Node_Name  
Data_Type  
Length  
Data type  
1-21 (must not overflow the  
data array)  
Length of Map Descriptor  
Starting address of read  
block  
Address  
0
The command id as given in  
the notes.  
Command  
12  
Network  
Zone  
Sector  
The network number  
The zone number  
The sector number  
1-255  
1-255  
1-255  
Data Block Description5  
BYTE offset  
Function  
0
Number of faults  
Fault list  
1 - 20  
5 1 indicates TRUE; 0 indicates FALSE  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-43 VESDA Driver Manual  
Page 14 of 18  
4.5.5.  
VESDA data format for command 10 (Update Display Status)  
This request returns the Current Display Status in a split data array (2 data arrays of  
different type in one map descriptor). The format for the data is as follows:  
Data Arrays 1  
Column Title  
Function  
Legal Values  
Provide name for Data  
Array  
Up to 15 alphanumeric  
characters  
Data_Array_Name  
Data_Format  
Provides data format  
BIT  
Data_Array_Length Number of Data Objects  
32  
Data Arrays 2  
Column Title  
Function  
Legal Values  
Provide name for Data  
Array  
Up to 15 alphanumeric  
characters  
Data_Array_Name  
Data_Format  
Provides data format  
FLOAT  
Data_Array_Length Number of Data Objects  
32 (only first position used)  
Client Side Map Descriptors  
Column Title  
Function  
Legal Values  
Up to 32 alphanumeric  
characters  
Map_Descriptor_Name Name of this Map Descriptor  
Starting location in Data  
Data_Array_Location  
Array  
0
Function of Client Map  
Descriptor  
Function  
RDBC  
One of the node names  
specified in “Client Node  
Descriptor” above  
Dig_input  
Name of Node to fetch data  
Node_Name  
from  
Data_Type  
Length  
Data type  
Length of Map Descriptor  
Starting address of read  
block  
32  
0
Address  
Command  
Network  
Zone  
The command id  
10  
The network number  
The zone number  
The sector number  
Name of Data Array where  
data is to be stored in the  
FieldServer.  
1-255  
1-255  
1-255  
Sector  
DA_Bit_Name  
DA_Bit_offset  
Data Array 1 name  
Starting location in Data  
Array.  
0
Name of Data Array where  
data is to be stored in the  
FieldServer.  
Starting location in Data  
Array.  
DA_Float_Name  
DA_Float_offset  
Data Array 2 name  
0
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-43 VESDA Driver Manual  
Page 15 of 18  
Data Block 1 Description6  
BIT offset  
Function  
0
1
2
3
4
5
6
7
Reserved Flash  
Fault Filter Flash  
Fault Airflow Flash  
Fault Network Flash  
Fault Power Flash  
Fault Urgent Flash  
Fault Zone Flash  
Fault System Flash  
OK Flash  
8
9
Isolate Flash  
Fault Minor Flash  
Fault Major Flash  
Alarm Fire2 Flash  
Alarm Fire1 Flash  
Alarm Action Flash  
Alarm Alert Flash  
Reserved  
Fault Filter  
Fault Airflow  
Fault Network  
Fault Power  
Fault Urgent  
Fault Zone  
Fault System  
OK  
Isolate  
Fault Minor  
Fault Major  
Alarm Fire2  
Alarm Fire1  
Alarm Action  
Alarm Alert  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
Data Block 2 Description  
FLOAT offset  
Function  
0
Average Smoke Level (Sector must be set to zero)  
6 1 indicates TRUE; 0 indicates FALSE  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-43 VESDA Driver Manual  
Page 16 of 18  
4.5.6.  
VESDA data format for command 16 (Update Airflow Status)  
This request returns the Current Airflow Status in a split data array (2 data arrays of  
different type in one map descriptor). The format for the data is as follows:  
Data Arrays 1  
Column Title  
Function  
Legal Values  
Provide name for Data  
Array  
Up to 15 alphanumeric  
characters  
Data_Array_Name  
Data_Format  
Data_Array_Length Number of Data Objects  
Provides data format  
BIT  
4
Data Arrays 2  
Column Title  
Function  
Legal Values  
Data_Array_Name Provide name for Data  
Array  
Up to 15 alphanumeric  
characters  
BYTE  
4
Data_Format  
Provides data format  
Data_Array_Length Number of Data Objects  
Client Side Map Descriptors  
Column Title  
Function  
Legal Values  
Up to 32 alphanumeric  
characters  
Map_Descriptor_Name Name of this Map Descriptor  
Starting location in Data  
Data_Array_Location  
Array  
0
Function of Client Map  
Descriptor  
Function  
RDBC  
One of the node names  
specified in “Client Node  
Descriptor” above  
Dig_input  
Name of Node to fetch data  
Node_Name  
from  
Data_Type  
Length  
Data type  
Length of Map Descriptor  
Starting address of read  
block  
4
0
Address  
Command  
Network  
Zone  
The command id  
16  
The network number  
The zone number  
The sector number  
Name of Data Array where  
data is to be stored in the  
FieldServer.  
Starting location in Data  
Array.  
Name of Data Array where  
data is to be stored in the  
FieldServer.  
1-255  
1-255  
1-255  
Sector  
DA_Bit_Name  
DA_Bit_offset  
DA_Byte_Name  
DA_Byte_offset  
Data Array 1 name  
0
Data Array 2 name  
0
Starting location in Data  
Array.  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-43 VESDA Driver Manual  
Page 17 of 18  
Data Block 1 Description7  
BIT offset  
Function  
0
1
2
3
Pipe1 status  
Pipe2 status  
Pipe3 status  
Pipe4 status  
Data Block 2 Description  
BYTE offset  
Function  
0
1
2
3
Airflow in pipe 1 as percentage of normalised pipe airflow.  
Airflow in pipe 2 as percentage of normalised pipe airflow.  
Airflow in pipe 3 as percentage of normalised pipe airflow.  
Airflow in pipe 4 as percentage of normalised pipe airflow.  
4.5.7.  
Reading Smoke Levels on the VESDA Panels  
The Vesda panel only allows the driver to read the average Smoke Level on all the  
ports. Polling for individual sector smoke levels will always return a value of zero.  
Zone setup  
If the zone on the Panel has not been configured the zone must be set to zero in the  
FieldServer configuration file.  
Sector setup  
Setting the sector to zero will allow the driver to poll for the average smoke level.  
4.5.8.  
VESDA Panel start-up delay.  
When the HLI is powered on the FieldServer will not be able to communicate with the  
Panel for 10 to 30 seconds. During this time the HLI starts up its application code and  
initializes various internal parameters.  
7 1 indicates OPEN; 0 indicates CLOSE  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FS-8700-43 VESDA Driver Manual  
Page 18 of 18  
THIS PAGE INTENTIONALLY LEFT BLANK  
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com  
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Craftsman Blower 136748270 User Manual
Craftsman Trimmer 31679249 User Manual
Crate Amplifiers Stereo Amplifier B60 User Manual
Curtis Flat Panel Television LCD1923A User Manual
Dacor Oven EO230 User Manual
Danby Refrigerator DFF1044W BLS User Manual
Electro Voice Microphone PL6 User Manual
Everpure Water System EV9100 66 User Manual
EV Rider Microphone N D767A User Manual
Gateway Computer Monitor FPD2475W User Manual