Excell Precision Surge Protector SP151 User Manual

Weighing System Surge protector  
User Manual  
SP151  
©ꢀExcellꢀPrecisionꢀLimitedꢀ2012.ꢀ ꢀ AllꢀrightsꢀreservedꢀWorldwide.ꢀ  
TheꢀinformationꢀcontainedꢀhereinꢀisꢀtheꢀpropertyꢀofꢀExcellꢀPrecisionꢀLimitedꢀ  
andissuppliedwithoutliabilityforerrorsoromissions.ꢀ ꢀ Nopartmaybeꢀ  
reproducedꢀ orꢀ usedꢀ exceptꢀ asꢀ authorisedꢀ byꢀ contractꢀ orꢀ otherꢀ writtenꢀ  
permission.ꢀ ꢀ Theꢀ copyrightꢀ andꢀ theꢀ foregoingꢀ restrictionꢀ onꢀ reproductionꢀ  
andꢀuseꢀextendꢀtoꢀallꢀmediaꢀinꢀwhichꢀtheꢀinformationꢀmayꢀbeꢀembodied.ꢀ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCELL PRECISION CO., LTD  
SP151 Weighing System Surge Protector  
Theꢀhighꢀperformanceꢀsurgeꢀprotectorꢀdeviceꢀappliesꢀtoꢀ4ꢁꢀorꢀ6ꢁwireꢀloadꢀcellꢀ  
weighingꢀsystemsꢀorꢀotherꢀrelatedꢀapplications.ꢀ  
1. General  
SP151ꢀSurgeꢀProtectorꢀisꢀdesignedꢀforꢀaccessingꢀdirectꢀintoꢀtheꢀcablingꢀofꢀtheꢀweighingꢀ  
system,ꢀinꢀorderꢀtoꢀpreventꢀtheꢀloadꢀcellsꢀandꢀotherꢀsensitiveꢀelectronicꢀcomponentsꢀfromꢀ  
damageꢀbyꢀaꢀnearꢀsurgeꢀstrikeꢀorꢀpowerꢀfailure.ꢀSurgeꢀprotectorꢀworksꢀatꢀtheꢀlocalꢀonly,ꢀ  
therefore,ꢀSP151ꢀdevicesꢀshouldꢀbeꢀinstalledꢀonꢀbothꢀendsꢀofꢀcircuitryꢀloop.ꢀ  
Aꢀcompleteꢀsystemꢀprotectionꢀrequiresꢀadditionalꢀsurgeꢀprotectionꢀdevice(s)ꢀtoꢀensureꢀ  
thatꢀotherꢀitems,ꢀsuchꢀasꢀACꢀpower,ꢀexternalꢀprinters,ꢀmainframes,ꢀandꢀtelephoneꢀandꢀsoꢀ  
on.ꢀ  
2. Installation  
Theꢀfollowingꢀrecommendationꢀisꢀonlyꢀasꢀaꢀreference.ꢀTakeꢀintoꢀaccountꢀofꢀlocalꢀconditions,ꢀ  
theꢀinstallationꢀshouldꢀalwaysꢀbeꢀcarriedꢀoutꢀbyꢀprofessionals.ꢀ  
2.1 Siting  
SP151ꢀshouldꢀbeꢀsetꢀwithinꢀ3mꢀfromꢀtheꢀloadꢀcellsꢀorꢀsystemsꢀtoꢀbeꢀprotected.ꢀForꢀtheꢀ  
maximumꢀdegreeꢀofꢀprotection,ꢀSP151ꢀshouldꢀbeꢀusedꢀatꢀbothꢀendsꢀconcurrentlyꢀofꢀtheꢀ  
interconnectedꢀcables.ꢀInꢀgeneral,ꢀinstallꢀaꢀprotectiveꢀdeviceꢀbetweenꢀtheꢀjunctionꢀboxꢀandꢀ  
loadꢀcellsꢀsetꢀ(Figureꢀ1).ꢀSomeꢀsystemsꢀspecifyꢀloadꢀcellꢀindividualꢀcable(s),ꢀprotectionsꢀareꢀ  
neededꢀforꢀeveryꢀloadꢀcellꢀ(Figureꢀ2).ꢀWithinꢀtheꢀweighbridge,ꢀtheꢀSP151ꢀshouldꢀbeꢀsetꢀ  
closeꢀtoꢀtheꢀindicationꢀsystems,ꢀtheꢀinterconnectingꢀcablesꢀmustꢀbeꢀseparatedꢀbyꢀatꢀ  
leastꢀ50mmꢀfromꢀotherꢀirrelevantꢀcables.ꢀ  
1ꢀ  
ZSME000000016ꢀ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCELL PRECISION CO., LTD  
Loadꢀ ꢀ  
Cellꢀ  
Loadꢀ ꢀ  
Cellꢀ  
Juctionꢀ  
Boxꢀ  
Loadꢀ ꢀ  
Cellꢀ  
Loadꢀ ꢀ  
Cellꢀ  
SP151ꢀ  
Connectionꢀtoꢀweightꢀcabinꢀ  
LocalꢀStructuralꢀearthꢀbondꢀ  
Figureꢀ1ꢀ  
Loadꢀ ꢀ  
Cellꢀ  
Loadꢀ ꢀ  
SP151ꢀ  
Cellꢀ  
SP151ꢀ  
Loadꢀ ꢀ  
SP151ꢀ  
Cellꢀ  
Loadꢀ ꢀ  
Cellꢀ  
SP151ꢀ  
Figureꢀ2ꢀ  
2ꢀ  
ZSME000000016ꢀ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCELL PRECISION CO., LTD  
2.2 Securing  
◄ꢀ ꢀ SP151ꢀshouldꢀbeꢀmountedꢀvertically,ꢀandꢀ  
theꢀcableꢀshouldꢀbeꢀconnectedꢀupsideꢀ  
downꢀtoꢀavoidꢀwaterꢀfromꢀseepage.ꢀ  
3ꢀ  
ZSME000000016ꢀ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCELL PRECISION CO., LTD  
▼ꢀSP151ꢀsealingꢀringꢀhasꢀ4ꢀmountingꢀholesꢀwithꢀcenterꢀtoꢀcenterꢀspacingꢀofꢀ ꢀ  
113.5ꢀ×ꢀ113.5ꢀmm.ꢀꢀ  
UsingꢀM4x16ꢀorꢀM4x20ꢀroundꢀheadꢀscrewꢀtoꢀsecureꢀtheꢀSurgeꢀProtectorꢀboxꢀontoꢀtheꢀ  
mountingꢀsurface.ꢀ  
UsingꢀM4x16ꢀorꢀM4x20ꢀroundꢀheadꢀ  
screwꢀtoꢀsecureꢀtheꢀSurgeꢀProtectorꢀ  
boxꢀontoꢀtheꢀmountingꢀsurface.ꢀ  
4ꢀ  
ZSME000000016ꢀ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCELL PRECISION CO., LTD  
Lockꢀattachedꢀtoꢀtheꢀscrewꢀsizeꢀ  
Theꢀscrewꢀdiameterꢀisꢀ4mm,ꢀandꢀ7mmꢀforꢀtheꢀheadꢀdiameterꢀ(M4ꢀscrewsꢀminimumꢀlengthꢀ  
isꢀ16mm).ꢀTheꢀstainlessꢀsteelꢀscrewsꢀareꢀrecommendedꢀtoꢀuseꢀforꢀsecuringꢀpurpose.ꢀꢀꢀ  
Cablesꢀwithinꢀ200mmꢀfromꢀSP151ꢀshouldꢀbeꢀsupportedꢀandꢀfixedꢀtoꢀpreventꢀtheꢀcableꢀ  
connectorꢀfromꢀunableꢀtoꢀsupportꢀtheꢀweightꢀofꢀtheꢀcable.ꢀ  
5ꢀ  
ZSME000000016ꢀ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCELL PRECISION CO., LTD  
2.3 Grounding  
Properlyꢀgroundingꢀcanꢀonlyꢀelaborateꢀtheꢀperformanceꢀofꢀaꢀsurgeꢀprotector.ꢀToꢀselectꢀtheꢀ  
weldingꢀpointꢀbyꢀreferringꢀtoꢀtheꢀlocalꢀvoltage,ꢀallꢀtheꢀweldingꢀpointsꢀwillꢀshareꢀtheꢀꢀ  
commonꢁmodeꢀvoltageꢀtoꢀtheꢀground.ꢀTheꢀweldingꢀpointꢀisꢀconnectedꢀtoꢀtheꢀlocalꢀgroundꢀ  
networkꢀorꢀgroundꢀrodꢀsystem;ꢀhence,ꢀnoꢀextraꢀgroundꢀnetworkꢀorꢀgroundꢀrodꢀsystemꢀisꢀ  
neededꢀtoꢀbeꢀinstalled.ꢀ  
Properꢀgroundingꢀisꢀtheꢀlocalꢀstructureꢀofꢀtheꢀdeviceꢀ(Figureꢀ1ꢀandꢀFigureꢀ2),ꢀnoꢀmatterꢀ  
connectedꢀtoꢀtheꢀsteelꢀconnectionꢀofꢀmetalꢀorꢀreinforcedꢀconcreteꢀweighbridge.ꢀFromꢀtheꢀꢀ  
groundingꢀboltꢀM8ꢀexternalꢀconnectꢀtoꢀtheꢀgroundꢀwireꢀofꢀtheꢀgroundingꢀpointꢀ(10mm2mmꢀ  
copperꢀorꢀequivalentꢀmetalꢀwireꢀorꢀribbon).ꢀTheꢀcombinationꢀthatꢀlessꢀthanꢀ3mꢀdevelopsꢀforꢀ  
optimumꢀperformance.ꢀUseꢀproperꢀamountꢀofꢀpreservativesꢀtoꢀprotectꢀtheꢀexposedꢀmetal.ꢀ  
Inꢀloadometerꢀ(weighbridge)ꢀorꢀcontrolꢀroom,ꢀSP151ꢀsurgeꢀprotectorꢀshouldꢀbeꢀlocatedꢀ  
closeꢀtoꢀtheꢀweighingꢀcomputerꢀorꢀdashboardꢀdisplay,ꢀandꢀtheꢀgroundꢀwireꢀshouldꢀbeꢀ  
connectedꢀtoꢀindependentꢀgroundingꢀrodsꢀofꢀtheꢀACꢀpower.ꢀGroundꢀwiresꢀthatꢀmoreꢀthanꢀ  
3mꢀlong,ꢀaꢀgroundꢀbetweenꢀtheꢀSP151ꢀwithꢀtheꢀinstrumentꢀisꢀneededꢀ(SeeꢀFigureꢀ4).ꢀ  
GroundingꢀWireꢀ  
ꢀTightenꢀtheꢀstudꢀM8ꢀupward  
Earthing/groundingꢀ ꢀ  
M8  
studꢀM8ꢀ  
6ꢀ  
ZSME000000016ꢀ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCELL PRECISION CO., LTD  
2.4 Connections  
Twoꢀterminalsꢀareꢀprovided,ꢀlabeledꢀ"Fieldꢀcable”ꢀandꢀ“Instrumentꢀcable”.ꢀFieldꢀcableꢀisꢀtheꢀ  
independent,ꢀexposedꢀcableꢀbetweenꢀtheꢀweighbridgeꢀandꢀweighingꢀcabin.ꢀInstrumentꢀorꢀ  
loadꢀcellꢀcableꢀisꢀaꢀlocallyꢀshortꢀconnection,ꢀsuchꢀasꢀfromꢀSP151ꢀtoꢀtheꢀjunctionꢀbox,ꢀ  
independentꢀloadꢀcellꢀorꢀweighingꢀscale.ꢀEquipmentsꢀconnectedꢀtoꢀtheꢀterminalꢀareꢀsubjectꢀ  
toꢀSP151ꢀprotection.ꢀ  
SP151ꢀallowsꢀtheꢀ4ꢁwireꢀ(SIG1,ꢀSIG2,ꢀEXC1,ꢀEXC2)ꢀorꢀlineꢀ6ꢀ(SIG1,ꢀSIG2,EXC1,ꢀEXC2,ꢀꢀ  
SENSE1,ꢀSENSE2)ꢀasꢀwellꢀasꢀtwoꢀisolatedꢀlines.ꢀTheꢀfunctionꢀofꢀeachꢀterminalꢀisꢀclearlyꢀ  
markedꢀonꢀtheꢀjunctionꢀbox.ꢀ ꢀ  
Theꢀisolatedꢀlinesꢀconnectedꢀtoꢀfieldꢀcablesꢀandꢀinstrumentationꢀcablesꢀareꢀnotꢀconnectedꢀ  
withꢀtheꢀgroundꢀwireꢀofꢀtheꢀSP151ꢀwithoutꢀaffectingꢀtheꢀgroundꢀoperationꢀofꢀtheꢀgeneralꢀ  
weighingꢀsystem.ꢀ  
Ifꢀyourꢀvendorꢀrequiresꢀtheꢀisolatedꢀlinesꢀtoꢀbeꢀgrounded,ꢀitꢀshouldꢀbeꢀconnectedꢀtoꢀ  
theꢀjunctionꢀboxꢀorꢀloadꢀcell.ꢀ ꢀ  
Cableꢀthroughꢀtheꢀcableꢀsealꢀsleeve,ꢀstrippedꢀandꢀattachedꢀtoꢀtheꢀcorrespondingꢀꢀ  
connectionsꢀareꢀclearlyꢀmarkedꢀandꢀtheꢀsubsequentꢀfailureꢀdetectionꢀwouldꢀbeꢀeasier.ꢀ  
Ensureꢀthatꢀtheꢀsealꢀsleeveꢀcasingꢀisꢀtight,ꢀandꢀthenꢀlockꢀtheꢀlid.ꢀ  
FieldꢀCableꢀ  
ACꢀ Powerꢀ feedꢀ  
(Unprotected)ꢀ  
SP151ꢀ  
Earth/Groundꢀ  
Connectionꢀ  
Instrumentationꢀ  
orꢀCellꢀCableꢀ  
*
Subsidiaryꢀearthꢀ  
bondꢀifꢀ ꢀ  
earth/groundꢀlinkꢀ  
>3m/10ft  
ConsumerꢀUnitꢀ  
WeighꢀComputerꢀ  
Figureꢀ4ꢀ  
7ꢀ  
ZSME000000016ꢀ  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXCELL PRECISION CO., LTD  
3. Maintenance  
Note:ꢀForꢀcertifiedꢀsystems,ꢀyouꢀmustꢀconfirmꢀthatꢀtheꢀsystemꢀcanꢀbeꢀ  
reꢁcalibrated.ꢀBeforeꢀtearingꢀoffꢀtheꢀsealꢀforꢀmaintenance,ꢀaꢀnewꢀcalibrationꢀsealꢀisꢀrequiredꢀ  
forꢀreplacingꢀafterꢀtheꢀmaintenance.ꢀ  
Processingꢀtheꢀmaintenanceꢀeveryꢀtheꢀotherꢀyear.ꢀ(higherꢀrepairꢀandꢀmaintenanceꢀꢀ  
frequencyꢀforꢀparticularlyꢀharshꢀenvironments)ꢀ  
3.1ꢀꢀCheckꢀSP151ꢀtoꢀseeꢀifꢀitꢀisꢀsurroundedꢀbyꢀintactꢀandꢀsealedꢀcorrectly.ꢀ  
3.2ꢀꢀRemoveꢀtheꢀchassisꢀcoverꢀandꢀconfirmꢀthatꢀtheꢀsealingꢀeffect,ꢀifꢀnecessary,ꢀtoꢀreplaceꢀ  
theꢀdamagedꢀsealꢀstrip.ꢀ ꢀ  
3.3ꢀꢀCheckꢀallꢀinternalꢀcablesꢀlabeled.ꢀ  
3.4ꢀ Checkꢀtheꢀtightnessꢀofꢀallꢀconnectedꢀcables,ꢀandꢀrepairꢀanyꢀlooseꢀorꢀdamagedꢀ  
connections.ꢀ  
3.5ꢀ Checkꢀtheꢀinternalꢀandꢀexternalꢀgroundingꢀline,ꢀtightenꢀitꢀifꢀloose.ꢀ  
4. Troubleshooting  
Whenꢀtheꢀelectronicꢀcircuitꢀsystemꢀsufferedꢀfromꢀsurgeꢀstruck,ꢀitꢀwillꢀoperateꢀautomaticallyꢀ  
andꢀselfꢁrecovery.ꢀTheꢀSP151ꢀserviceꢀlifespanꢀcouldꢀbeꢀaroundꢀ20ꢀyears,ꢀdependsꢀonꢀtheꢀ  
lifespanꢀofꢀtheꢀprotectionꢀcomponentsꢀofꢀtheꢀprimaryꢀgasꢀdischargeꢀtube.ꢀ  
Attention  
FieldꢀcableꢀthatꢀconnectedꢀtoꢀtwoꢀSP151ꢀofꢀtheꢀinstrumentation,ꢀtheꢀisolatedꢀlinesꢀmustꢀbeꢀ  
connectedꢀandꢀwithꢀaꢀdrainꢀofꢀpipeline.ꢀ  
Whenꢀtheꢀisolatedꢀlinesꢀsufferedꢀfromꢀtheꢀsurge,ꢀtheꢀgasꢀdischargeꢀtubeꢀwillꢀdischargeꢀtoꢀ  
theꢀearthꢀtoꢀimproveꢀtheꢀoverallꢀprotection.ꢀ  
8ꢀ  
ZSME000000016ꢀ  
Download from Www.Somanuals.com. All Manuals Search And Download.  

CompuSTAR Remote Starter CM4200DX User Manual
Continental Platinum Blender CP42149 User Manual
Cuisinart Blender SMO 56C User Manual
Cypress Computer Hardware AN20639 User Manual
Cypress Computer Hardware CY8C24094 User Manual
Desa Tech Gas Heater CBN20 User Manual
Earthquake Sound Speaker SUB100 User Manual
Fellowes Paper Shredder DS 12Cs User Manual
Field Controls Oxygen Equipment FC95HRV User Manual
Fisher Price Automobile Parts T7160 User Manual