Delta Electronics Network Card VFDB 4132 Series User Manual

3.2 Brake unit  
2008-09-10  
] Wiring Warnings  
-(N)  
DC -  
DC -  
DC -  
DC+  
+(P)  
DC+  
DC+  
Do not proceed with wiring while power is applied to the circuit.  
The wiring gauge and distance must comply with the local regulations.  
The +(P), -(N) terminals of the AC motor drive (VFD Series), connected to the  
brake unit (VFDB), must be confirmed for correct polarity lest the drive and the  
brake unit be damaged when power on.  
M1  
M2  
S1  
S2  
M1  
M2  
S1  
S2  
VFD  
Series  
M
5011669601-1CBU  
S
S
CHARGE ACT  
OC  
OH  
When the brake unit performs braking, the wires connected to DC+, DC-, B1 and  
B2 would generate a powerful electromagnetic field for a moment due to high  
current passing through. These wires should be wired separately from other low  
voltage control circuits lest they make interference or mis-operation.  
Inflammable solids, gases or liquids must be avoided at the location where the  
brake resistor is installed. The brake resistor had better be installed in individual  
metallic box with forced air-cooling.  
B1 B2  
BR  
B1 B2  
BR  
B1 B2  
BR  
VFDB 4132 Series Brake Modules  
VFDB4132  
O.L.  
O.L.  
O.L.  
The Position of the Jumper  
Instruction Sheet  
M
MASTER/SLAVE  
Setting Jumper  
S
Connect the ground terminal to the Earth Ground. The ground lead must be at  
least the same gauge wire as leads DC+, DC-.  
Please install the brake resistor with forced air-cooling or the equivalent when  
frequent deceleration braking is performed (over 10%ED).  
Do NOT change any wirings and settings and touch any terminals and  
components while power is applied to avoid electric shock.  
It is recommended to use the ring terminals for main circuit wiring. Make sure the  
terminals are fastened before power on.  
Input Voltage Setting  
X Preface  
480V  
460V  
440V  
415V  
400V  
380V  
M1: SLAVE output signal +  
M2: SLAVE output signal -  
S1: SLAVE input signal +  
S2: SLAVE input signal -  
Thank you for choosing DELTA’s brake module. VFDB brake units are applied to  
absorb the motor regeneration energy when the three-phase induction motor stops by  
deceleration. With VFDB brake unit, the regeneration energy will be dissipated in  
dedicated brake resistors. To prevent mechanical or human injury, please refer to this  
instruction sheet before wiring. VFDB brake units are suitable for DELTA AC Motor  
Drives VFD Series 230V/460V/575V. VFDB brake units need to be used in conjunction  
with BR series brake resistors to provide the optimum brake characteristics. VFDB  
brake units (4132) are approved by Underwriters Laboratories, Inc. (UL) and Canadian  
Underwriters Laboratories (cUL). The content of this instruction sheet may be revised  
without prior notice. Please consult our distributors or download the most updated  
NOTE: Please use shielded  
wires while wiring.  
[ Internal Components and Terminals  
4.1 Internal Components  
M1  
S1  
M2  
RA RC  
S2  
SLAVE output/input terminal  
Alarm output terminals  
Wiring distance  
NOTE  
Please make sure that power is OFF before setting the jumper.  
The steps for jumper setting:  
Step 1. Remove the top cover.  
Step 2. Remove the screws on the side case (3 screws for each side).  
Step 3. Remove the screws that connected bottom case to the side case (2  
screws for each side).  
Step 4. After removing the power line of the fan, pull out the heat sink slowly until  
the jumper can be seen. Then the jumper can be set.  
VFDB  
series  
VFD series  
BR  
Max 5M  
Brake Resistor  
Max 8M  
AC Motor Drive  
Brake Unit  
^ Definition for the Brake Usage ED%  
100%  
Y Specifications  
` Brake Resistors/Units for Delta VFD  
VFDB 4132 Brake Units  
Specification  
Max. Motor Capacity (kW)  
460V Series  
132  
AC Motor Drives Series  
T1  
ED% = T1/T0x100(%)  
Brake Time  
4.2 Wire Gauge for Terminals  
Min.  
Typical  
Thermal  
Overload  
Relay  
T0  
Applicable  
Motor  
Resistor Value Brake Unit  
Spec. for Each Part No.  
AC Motor  
Drive  
Max. Discharge Current (A) 10%ED  
240  
Cycle Time  
Wire Gauge AWG  
Full-load  
Torque  
kg-M  
Brake Resistors Brake  
Equivalent  
Resistor Value  
for Each AC  
Motor Drive  
Circuit  
Terminals  
DC+, DC-  
Screw  
M8  
Torque  
(mm2)  
4~6AWG  
Torque  
Part No. and  
Continuous Discharge Current (A)  
Braking Start-up Voltage (DC)  
75  
and  
Quantity  
The definition of the brake usage ED(%) is to assure having enough time for the brake  
unit and brake resistor to dissipate the heat generated by brake. When the brake  
resistor heats up, the resistance would increase with temperature, and brake torque  
would decrease accordingly.  
Quantity  
10%ED  
Power Input  
Circuit  
Brake  
30 kgf-cm  
(26 in-lbf)  
30 kgf-cm  
(26 in-lbf)  
HP kW  
Value  
(13.3~21.2mm2)  
4~6AWG  
618/642/667/690/725/750±6V  
120 90  
150 110  
175 132  
215 160  
250 185  
52.5  
61  
13500W 54132  
21600W 44132  
21600W 44132  
21600W 3.44132  
27000W 2.54132  
1
1
1
1
2
2
BR1K5W005  
9
120  
5Ω  
4Ω  
110A  
135A  
135A  
160A  
220A  
220A  
Input  
Rating  
B1, B2  
M8  
Resistor  
(13.3~21.2mm2)  
18~20AWG  
DC Voltage  
480-750VDC  
BR1K2W008 18 120  
BR1K2W008 18 100  
73.5  
89  
4Ω  
Output M1, M2  
Input S1, S2  
3.4Ω  
Min. Equivalent Resistor for Each Brake Unit  
Heat Sink Overheat Temperature  
SLAVE  
Circuit  
4 kgf-cm  
(3 in-lbf)  
(0.8~0.5mm2)  
(With shielded wires)  
18~20AWG  
BR1K2W6P8 18  
BR1K5W005 18 115  
BR1K5W005 18 96  
97  
3.4Ω  
2.5Ω  
2.5Ω  
M2  
M2  
Temperature exceeds +95 oC (203oF)  
Relay contact 3A250VAC/30VDC  
(RA, RC)  
ON until the bus (P-N) voltage is  
below 50VDC  
_ The Voltage Settings  
1. Voltage setting: the power source of the brake unit is DC voltage from +(P), -(N)  
terminals of the AC motor drive. It is very important to set the voltage of the brake  
unit based on the actual input power of the AC motor drive before operation. The  
setting has a great influence on the potential of the operation voltage for the brake  
unit. Please refer to the table below.  
103  
Fault  
Circuit  
4 kgf-cm  
(3 in-lbf)  
300 220 122.5 27000W 2.54132  
Alarm Output for Overheat  
RA, RC  
(0.8~0.5mm2)  
Power Charge Display  
Over-current Protection Level  
Installation Location  
a Examples  
\ Basic Wiring Diagram  
320A  
Indoor (no corrosive gases, metallic  
dust)  
NOTE  
NFB  
MC  
Motor  
IM  
NOTE  
Before wiring, please notice equivalent resistors value shown in the column  
“Equivalent resistors specification for each brake unit” in the above table to  
prevent damage.  
Operating Temperature  
Storage Temperature  
Humidity  
-10oC~+50oC (14oF to 122oF)  
-20oC ~+60oC (-4oF to 140oF)  
Less than 90% Non-condensing  
9.8m/s2 (1G) under 20Hz / 2m/s2  
(0.2G) at 20~50Hz  
R/L1  
S/L2  
T/L3  
R/L1  
S/L2  
T/L3  
R/L1  
S/L2  
T/L3  
Before changing the setting of the power voltage, make sure the power has been  
turned off. Please set power voltage as the possible highest voltage for unstable  
power system. Take 380VAC power system for example. If the voltage may be up  
to 410VAC, 415VAC should be set.  
For DELTA’s AC motor drive (VFD Series), please set parameter (Over Voltage  
Stall Prevention) as “close” to disable over-voltage stall prevention, to ensure  
stable deceleration characteristic.  
Thermal  
Overload  
Relay  
460V 120HP  
O.L.  
VFD Series  
Thermal Overload Relay  
B1  
Vibration  
MC  
+(P)  
DC+  
B1  
O.L.  
BR  
+(P)  
-(N)  
DC+  
DC-  
DC- VFDB  
-(N)  
E.F  
Mechanical Configuration  
Wall-mounted enclosed type IP10  
O.L.  
SA  
BR  
BR  
BR  
BR  
BR  
BR  
BR  
BR  
BR  
VFD  
Series  
VFDB  
4132  
Brake Unit  
Brake  
Unit  
RA  
RC  
Surge Absorber  
Brake  
Resistor  
DCM  
B2  
Brake  
Resistor  
Thermal Overload  
Relay or Temperature switch  
Brake Resistors  
Table 1: The Selection of AC Power Voltage and Voltage Setting  
M
VFD900_43_  
Model no.  
Specification  
1500W 5.0Ω  
1200W 6.8Ω  
1200W 8.0Ω  
1500W 40Ω  
1000W 50Ω  
1000W 75Ω  
Temperature Switch  
Brake Start-up voltage  
AC Power Voltage  
B2  
BR1K5W005  
BR1K2W6P8  
BR1K2W008  
BR1K5W040  
BR1K0W050  
BR1K0W075  
Note 1: When the AC motor drive is used with DC reactor, please refer to the wiring  
diagram in the AC drive user manual for wiring terminal DC+ of brake unit.  
Note 2: DO NOT wire terminal DC- to the neutral point of power system.  
DC Bus (DC+, DC-) Voltage  
VFD900_43_ uses with 3 BR sets in parallel, which 3PCS 1K5W005 brake resistors  
are connected in series.  
380VAC (460V Mode)  
400VAC (460V Mode)  
415VAC (460V Mode)  
440VAC (460V Mode)  
460VAC (460V Mode)  
480VAC (460V Mode)  
618VDC  
642VDC  
667VDC  
690VDC  
725VDC  
750VDC  
460V 150HP, 175HP, 215HP  
NOTE  
Therm al Over load Relay  
B1  
For safety consideration, install an overload relay between the brake unit and the  
brake resistor. In conjunction with the magnetic contactor (MC) prior to the drive,  
it can perform complete protection against abnormality.  
The purpose of installing the thermal overload relay is to protect the brake resistor  
from damage due to frequent brake, or due to brake unit keeping operating  
resulted from unusual high input voltage. Under such circumstance, just turn off  
the power to prevent damaging the brake resistor.  
+(P)  
-( N)  
DC+  
DC-  
BR  
BR  
BR  
BR  
BR BR BR  
O.L.  
VFD  
Ser ies  
VFDB  
4132  
Bra ke Unit  
BR  
BR  
BR BR BR  
Bra ke  
Resistor  
NOTE: Input Power With Tolerance ±10%  
VFD1100_ 43_  
VFD13 20_43_  
VFD16 00_43_  
Z Dimensions  
3.1 Brake resistor  
M
BR  
BR  
BR  
BR BR BR  
Input voltage setting for VFDB 4132  
B2  
CHARGE  
Power lamp  
OC  
OH  
ACT  
VFD1100_ 43_ uses with 6 BR sets in p arallel, which 3PCS 1K2W 008 bra ke r esisto rs  
are con necte d in serie s.  
Please refer to the specification of the thermal overload relay.  
Brake lamp  
Over-current Overheat  
lamp lamp  
The alarm output terminals (RA, RC) of the brake unit will be activated when the  
temperature of the heat sink exceeds 95°C. It means that the temperature of the  
installation environment may exceed 50°C, or the brake %ED may exceed  
10%ED. With this kind of alarm, please install a fan to force air-cooling or reduce  
the environment temperature. If the condition not due to the temperature, the  
control circuit or the temperature sensor may have been damaged. At this time,  
please send the brake unit back to the manufacturer or agency for repair.  
The AC Motor Drive and brake unit will be electrified at the same time while  
turning on the NFB (No-fuse breaker). For the operation/stop method of the motor,  
please refer to the user manual of the AC Motor Drives VFD Series. The brake  
unit will detect the inner DC voltage of the AC motor drive when it stops the motor  
by deceleration. The extra regeneration will be dissipated away rapidly by the  
brake resistor in the form of heat. It can ensure the stable deceleration  
characteristic.  
VFD13 20_43_ use s with 6 BR sets in par allel, wh ich 3PCS 1 K2W00 8 brake resistors  
are con necte d in serie s.  
Input Voltage Setting  
480V  
VFD16 00_43_ use s with 6 BR sets in pa rallel, wh ich 3PCS 1K2W6 P8 brake re sistors  
are con necte d in serie s.  
460V  
For VFDB4132  
Factory setting: 440V 440V  
460V 250HP, 300HP  
415V  
400V  
380V  
Thermal Overload Relay  
Thermal Overload Relay  
DC+ DC-  
DC+ DC-  
+ (P) -(N)  
B1  
B1  
2. MASTER (M) /SLAVE (S) setting: the factory setting is “M”. The “S” setting is  
applied to two or more brake units in parallel, making these brake units be  
enabled/disabled synchronously. Then the power dissipation of each unit will be  
equivalent so that they can perform the brake function completely.  
BR BR BR  
BR BR BR  
BR BR BR  
BR BR BR  
BR BR BR  
BR BR BR  
VFDB  
4132  
VFDB  
4132  
O.L.  
O.L.  
Brake  
Resistor  
VFD  
Series  
Brak e Unit  
Brake Unit  
M
VFD1850_43_  
VFD2200_43_  
B2  
S1 S2  
B2  
M1 M2  
S
Brak e  
Resistor  
In the following diagram, it shows jumper setting for the application of three brake  
units. After wiring, the jumper in the first brake unit should be set to “M” and others  
must be set to “S” to complete the system setting.  
Besides, using thermal overload relay to be the protection system and brake  
resistor, temperature switch can be installed on brake resistor side as the  
protection. The temperature switch must comply with the brake resistor  
specification or contact your dealer.  
VFD1850_43_ uses with 2 VFDB4132 brake units and each brake unit uses with  
3 BR sets in parallel, which 3PCS 1K5W005 brake resistors are connected in series.  
VFD2200_43_ uses with 2 VFDB4132 brake units and each brake unit uses with  
3 BR sets in parallel, which 3PCS1K5W005 brake resistors are connected in series.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Conair Styling Iron Curling Iro User Manual
Cuisinart Cooktop MSC 600 User Manual
Danby Freezer DCFM102WSB User Manual
Digicom Network Router V92S User Manual
Dynacord Stereo Receiver DDL 204 User Manual
Dynex Handheld TV DX 7HTV 09 User Manual
Edelbrock Automobile Accessories 15013 User Manual
Electro Voice Speaker System FRX+660 User Manual
Geemarc Hearing Aid LH100 User Manual
Global Machinery Company Drill 444B User Manual