Reclosers
®
Service Information
Kyle Form 5, Form 5 UDP, Form 5 DC NOVA
Microprocessor-Based Recloser Controls
Installation and Operation Instructions
S280-79-10
Applicable to serial numbers above 3000 or beginning with CP57.
99001KM
Figure 1.
®
Kyle Form 5/UDP microprocessor-based recloser control.
Contents
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . 2
Product Information . . . . . . . . . . . . . . . . . . . . . . . . 3
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
ANSI Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Quality Standards . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Acceptance and Initial Inspection . . . . . . . . . . . . . . 3
Handling and Storage . . . . . . . . . . . . . . . . . . . . . . . 3
Battery Replacement . . . . . . . . . . . . . . . . . . . . . . . 3
Control Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Initializing the Control . . . . . . . . . . . . . . . . . . . . . . . 4
Form 5 Control Description . . . . . . . . . . . . . . . . . . 5
Recloser Interface (RIF) Module . . . . . . . . . . . . . . 6
Central Processing Unit (CPU) Module . . . . . . . . . 6
Discrete Interface (DIF) Module . . . . . . . . . . . . . . . 6
Power Supply Module . . . . . . . . . . . . . . . . . . . . . . . 6
Form 5 Control Operator Panel . . . . . . . . . . . . . . . 7
Battery Test Procedure . . . . . . . . . . . . . . . . . . . . . . 14
Control Features . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Auxiliary Power for Accessories . . . . . . . . . . . . . . 20
Recloser Interface (RIF) Module Configuration . . 20
Discrete Interface (DIF) Accessory . . . . . . . . . . . . 23
Customer Connection Information . . . . . . . . . . . . . 23
Standard and UDP DIF Module 1 Inputs . . . . . . . . 26
Standard and UDP DIF Module 1 Outputs . . . . . . . 28
Standard and UDP Module 2 Inputs . . . . . . . . . . . . 29
Standard and UDP Module 2 Outputs . . . . . . . . . . 30
Input Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Installation Procedure . . . . . . . . . . . . . . . . . . . . . . 32
Initial Programming Prior to Installation . . . . . . . . . 32
Control / Recloser Compatibility . . . . . . . . . . . . . . . 32
Control Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Mounting the Control . . . . . . . . . . . . . . . . . . . . . . . 33
Grounding the Control . . . . . . . . . . . . . . . . . . . . . . 34
Customer Connections for AC Power . . . . . . . . . . . 38
Customer Connections for Metering . . . . . . . . . . . . 38
Before Placing Control and Recloser into Service . 42
Testing and Troubleshooting . . . . . . . . . . . . . . . . 43
Testing an Installed Control . . . . . . . . . . . . . . . . . . 43
Testing with Type MET Tester . . . . . . . . . . . . . . . . 43
Closing the Recloser During Testing . . . . . . . . . . . 44
Form 5 Control Default Test Procedure . . . . . . . . 47
Remove the Control from Service . . . . . . . . . . . . . 55
Return the Control to Service . . . . . . . . . . . . . . . . 55
Additional Information . . . . . . . . . . . . . . . . . . . . . . 56
Form 5 Universal Device Protection (UDP)
Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Form 5 DC NOVA Control . . . . . . . . . . . . . . . . . . . 22
November 2001 • Supersedes 1/01
1
Download from Www.Somanuals.com. All Manuals Search And Download.
Printed in USA
!
SAFETY
FOR LIFE
S280-79-10
PRODUCT INFORMATION
Control Battery Storage and Charging
Introduction
Service Information S280-79-10 provides installation and
operation instructions for the Kyle Form 5 and Form 5
UDP microprocessor-based electronic recloser controls.
The 24 Vdc control battery in the Form 5 control is fully
charged prior to shipment and is ready for use. In order to
maintain sufficient charge to operate the control, the
sealed lead acid battery should be charged after no more
than three months of storage.
Read This Manual First
Note: Two 12 Vdc, 13 amp-hour batteries are available for
use with the Form 5 Distribution Automation upgrade
accessory.
Read and understand the contents of this manual and fol-
low all locally approved procedures and safety practices
before installing or operating this equipment.
Temperature has an effect on battery life. Sealed lead
acid batteries should be stored, fully charged, at room
temperature. Never store lead acid batteries at tempera-
ture exceeding 47°C (117°F), as damage can result in
approximately one month.
Additional Information
These instructions cannot cover all details or variations in
the equipment, procedures, or process described, nor
provide directions for meeting every possible contingency
during installation, operation, or maintenance. When
additional information is desired to satisfy a problem not
covered sufficiently for the user's purpose, please contact
your Cooper Power Systems sales representative.
IMPORTANT: To maintain sufficient charge to oper-
ate the control and prevent battery cell damage, the
sealed lead-acid batteries should be charged after no
more than three months of storage.
ANSI Standards
Kyle reclosers are designed and tested in accordance
with the following ANSI standards: C37.60 and C37.85
and ANSI Guide C37.61.
To keep the battery charged, energize the control’s built-
in charger with AC power applied to the user AC supply
input connector block TB1, located left of the RIF module
within the control cabinet.
Note: When shipped from the factory, the battery source is
disconnected and its output plugs are taped to the cab-
inet. Connect the battery plugs into the mating connec-
tors to complete the battery circuit.
Quality Standards
ISO 9001:2000-Certified Quality Management System
Acceptance and
Initial Inspection
Each Form 5 control is completely assembled, tested, and
inspected at the factory. It is carefully calibrated, adjusted
and in good condition when accepted by the carrier for
shipment.
IMPORTANT: Connect the control battery when AC
power is connected to the control’s AC supply Input Ter-
minal Block. The battery must be disconnected prior to
shipping or storing the control.
Upon receipt, inspect the carton for signs of damage.
Unpack the control and inspect it thoroughly for damage
incurred during shipment. If damage is discovered, file a
claim with the carrier immediately.
Battery Replacement
The 24 Vdc control battery has a life expectancy of 4 to 6
years. It is recommended that the battery be replaced
after 4 years.
Handling and Storage
Control Power
Be careful during handling and storage of the control to min-
imize the possibility of damage. If the control is to be stored
for any length of time prior to installation, provide a clean,
dry storage area. If storage is in a humid atmosphere, make
provisions to keep the control circuitry energized.
The primary source of power is factory configured for 120 Vac
or 240 Vac. The 240 Vac version is available as an option
at time of order entry. Primary power is rectified to charge
the power capacitor and to power the dc/dc converter that
provides power to the control. A minimum of 500 mA of ac
current is required for heater operation, battery charging
current, and to keep all modules energized.
Note: To energize the control, apply AC power to the AC sup-
ply input connector block TB1 located left of the
Recloser Interface (RIF) module within the control.
Refer to the Customer Connection for AC power sec-
tion in this manual.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
The AC power LED indicator on the operator panel of the
AC Reclosers
control will turn off after 15 seconds upon loss of AC
power. The indicator will illuminate immediately upon
return of ac power.
Power to operate the tripping and closing solenoids in the
recloser is provided by the power capacitor located
behind the operator panel of the control. A sealed, 24-volt,
lead acid battery is located in the lower portion of the con-
trol cabinet and is utilized to provide operating and trip-
ping energy when AC power is temporarily lost. The
control is equipped with an ac-powered, temperature-
compensated battery charger.
Initializing the Control
Two methods are available to initialize the Form 5 control.
Method 1: Connect AC power to the input connector ter-
minal TB-1. Refer to the Customer Connec-
tions for AC Power section of this manual.
Operation Upon Loss Of AC Power
Method 2: Connect the battery terminal on the control
and press the MANUAL BATTERY RECON-
NECT button located on the Form 5 power
supply. See Figure 4.
If the control is equipped with the standard 24 Vdc lead-
acid battery, the control maintains full operation from the
battery power supply for a minimum of 32 hours at 20°C
(24 hours at -40°C). To prevent battery damage, the con-
trol shuts down automatically upon detection of low bat-
tery voltage below 22.7 Vdc.
Note: Method 2 powers the control off the battery
and is not intended for long term operation.
In both methods, after initialization, set the control clock
via the interface software.
Control programming settings and parameters—including
event recorder, duty monitor, and data profile metering
parameters—are stored in non-volatile memory and
retained upon loss of control power. The time/date clock
resets to 0:00:00, 1970 upon loss of control power.
LCD Display
CONTROL OK
AC POWER
ABOVE MIN TRIP
CHECK BATTERY
RECLOSER MALFUNCTION
REVERSE POWER FLOW
BACK
NEXT
BUSHINGS 1-2 FAULT TARGET
LED Indicators
RESET
TARGETS
BUSHINGS 3-4 FAULT TARGET
CHANGE
RESET
MAX CURRENT
LAMP
TEST
BUSHINGS 5-6 FAULT TARGET
GROUND FAULT TARGET
LCD Display Dedicated
Function Keys
NON
RECLOSING
GND TRIP
BLOCKED
SUPERVISORY
BLOCKED
SENSITIVE-GROUND FAULT TARGET
COLD LOAD
PICK UP
FAST
TRIPS
DISABLED
BUSHINGS 1-2 VOLTAGE
BUSHINGS 3-4 VOLTAGE
BUSHINGS 5-6 VOLTAGE
BATTERY
TEST
BLOCKED
ALTERNATE
PROFILE
ALTERNATE
PROFILE
ALTERNATE
PROFILE
NO.
1
NO.
2
NO.
3
Operation "Hot Keys"
TX 2
TX 3
HOT LINE
TAG
RECLOSER CLOSED
RECLOSER OPEN
ON
OFF RX 3
CLOSE Pushbutton
RS232
RX 2
CONTROL LOCKOUT
RS232 Data Port
Hot Line Tag
TRIP (LOCKOUT)
Pushbutton
TRIP
(LOCKOUT)
®
CLOSE
KYLE
FORM 5
RECLOSER CONTROL
Figure 2.
Form 5 recloser control operator panel.
99005KM
4
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S280-79-10
FORM 5 CONTROL DESCRIPTION
Current sensing is provided by three current transformers
located in the recloser and interfaced to the Form 5 control
via the control cable. This cable also supplies Trip, Close,
and Recloser status, and connects to the Recloser Inter-
face (RIF) module to provide isolation for reliable opera-
tion. Voltages for metering are also connected to the RIF
module via the connector terminal block, TB-1 (Figure 3).
The following chain of events occurs for an operating
sequence of two trips to lockout:
1. The overcurrent signal is integrated with time on the
selected curve for the first trip operation (TCC1) to
produce the signal which energizes the trip circuit.
2. Energizing the trip circuit connects the battery and
capacitor to the trip solenoid to open the recloser.
A functional block diagram of the Form 5 control is shown
in Figure 3. Line current flowing through the recloser is
converted by the CPU module to a digital signal suitable
for metering and fault current calculations. Data sampling
occurs at a rate 32 times per cycle. The CPU contains a
data acquisition section that uses the acquired samples to
compute the fundamental currents and voltage for use in
overcurrent, under/over voltage and under/over frequency
protection, as well as currents and voltages for metering
functions. The current for overcurrent protection is calcu-
lated on a sub-cycle basis; it includes only the fundamen-
tal and DC component. For metering, the fundamental and
harmonic current and voltages are determined.
3. Upon opening, the control starts timing on the first
reclosing interval-delay time.
4. Upon expiration of this reclosing interval-delay, a clos-
ing signal is issued from the control, closing the
recloser and selecting the time-current characteristics
for the second trip operation (TCC2).
5. If current remains above the minimum-trip level, the
tripping and reclosing sequence is repeated.
6. The control begins the reset-delay timer if the over-
current is cleared before the operating sequence
reaches lockout indicated by a closed recloser and
current below minimum trip.
When the phase or ground current exceeds its pro-
grammed minimum-trip value and associated time-cur-
rent curve (TCC) timing, the control initiates the
programmed sequence of recloser tripping and reclosing
operations via the CPU and RIF modules. If the fault is
temporary, the control ceases to command recloser oper-
ations after a successful reclose, and the control resets to
the start of its operating sequence after a preset time
delay. If the fault is permanent, the control performs its
complete programmed sequence of reclose commands
and locks out with the recloser open. Once locked out, the
control must be closed via the operator panel or SCADA
communications. This resets the control to the start of the
operating sequence.
7. When the reset-delay times out, the control is reset to
the home state and is ready for another programmed
operating sequence. If current rises above minimum
trip prior to the reset-delay timing out, the timer is
halted and the control resumes the operating
sequence while the accumulated reset-delay timing is
restarted.
TB1 TERMINAL BLOCK
POWER SUPPLY
BATTERY
CUSTOMER P.T. INPUTS
RECLOSER
RIF
OPTICAL
ISOLATION
OPERATOR'S
PANEL
DIF#2
(OPTIONAL)
TRIP SOLENOID
DIF#1
(OPTIONAL)
CPU
OPTICAL
ISOLATION
CLOSE SOLENOID
KEYBOARD
LED's
OPEN / CLOSE
SWITCHES
OPTICAL
ISOLATION
LCD
RS232 PORT
A Ø CT
B Ø CT
C Ø CT
MATCHING
TRANSFORMERS
AND SIGNAL
CONDITIONING
12
12
RS232
Or
12
12
FIBER-OPTIC
PORT
USER
USER
CT COMMON
CONNECTIONS
6 unlatched outputs
6 latched outputs
12 inputs
CONNECTIONS
6 unlatched outputs
6 latched outputs
12 inputs
OPTIONS
RS232
Or
FIBER-OPTIC
PCB
Figure 3.
Form 5 control operational flow diagram.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
The Form 5 control is constructed in a modular fashion to
Central Processing Unit (CPU)
simplify service and the addition of accessories (Figure
4). The standard configuration incorporates a Central
Processing Unit (CPU) module, power supply module,
Recloser Interface (RIF) module, and an operator panel.
Module
The CPU module is the center of the Form 5 control. The
CPU contains a 32-bit micro-controller, a Digital Signal
Processor, RAM and EEPROM memory, and a 16-bit
analog-to-digital converter. The CPU module accepts 16
analog inputs which it routes through the digital signal
processor, which samples 32 times per cycle, to compute
harmonic analysis to the 15th harmonic.
Discrete Interface (DIF) module(s), the fiber-optic board
and the RS-232 communication interface cards may be
ordered as accessories. Mounting provisions can be
provided to add customer-supplied radio and modem
modules.
Discrete Interface (DIF) Module
Recloser Interface (RIF) Module
The Discrete Interface (DIF) module allows users with
existing RTUs the ability to interface with the Form 5 con-
trol. The DIF module contains 12 inputs and 12 outputs
can be customized for a remote or supervisory function.
One Form 5 control can accommodate two DIF modules.
See DISCRETE INTERFACE (DIF) ACCESSORY sec-
tion of this manual.
The Recloser Interface (RIF) Module provides the inter-
face between the recloser and the CPU module, as well
as the interface between the voltage sensors and the
CPU module. The RIF is designed to interface with the fol-
lowing reclosers: WE/WVE group, NOVA group,
VSA/VSO group, and KFME/KFVME (50Hz) group.
The recloser connector includes three current-trans-
former inputs, Open and Closed status sensing, and Trip
and Close controls. The voltage sensor connector
accepts six voltage inputs; three for source-side, and
three for load-side voltage. Two sets of dip switches,
located on the RIF front panel, utilize different switch posi-
tions to configure the desired voltage. See Figure 17.
Power Supply Module
The Power Supply module is designed to accept 100 to
134 Vac or 200 to 268 Vac user-supplied input power at
either 50 or 60 Hz.
The Power supply module (connection P9) provides aux-
iliary power to radio communications units, RTUs and
other accessories. The auxiliary output provides 24 Vdc
(12 Vdc is available) for user loads. The auxiliary power
supply has the capability to provide a load of up to 40 W
peak (1 second) and 3 W average. The auxiliary power is
fused and current-limited to prevent user loads from dis-
abling the control.
The RIF board accepts either 12, 120, or 240 Vac voltage
inputs for metering. The factory configuration is outlined
on the module label and can be customized to user spec-
ification. See RECLOSER INTERFACE (RIF) MODULE
CONFIGURATION section of this manual.
Recloser Interface
(RIF) Module
Manual Battery
Reconnect Button
Auxiliary Power
Connection (P9)
Grounding Strap
Power Capacitor
Central Processing
Unit (CPU) Module
Power
Supply
Module
(Located behind operator
panel)
TB1 Connector
Block
Control Cable Receptacle
and Control Grounding Lug
(located beneath cabinet)
Control Battery
99001KM
Figure 4.
Form 5 UDP control operating panel with interface modules and radio mounting provisions.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S280-79-10
AC POWER
Form 5 Control Operator Panel
This green LED is illuminated when the presence of ac
input power to the control is sensed. The LED will turn off
if ac power is lost for more than 10 seconds.
The Form 5 control operator panel (Figure 8) allows local
operation and status interrogation through built-in operator
controls and status displays. The operator panel contains
LED indicators, operational pushbuttons, membrane-type
functional/indication switches, backlit LCD display, and
Hot Line Tag switch with indication. An RS-232 port is also
provided to permit the temporary connection of a PC for
programming the parameters in the control.
ABOVE MIN TRIP
This red LED is illuminated when the control detects that
current is above the programmed minimum trip value for
Bushings 1-2, Bushings 3-4, Bushings 5-6, Ground, or
Sensitive Ground.
All indicators with the exception of Hot Line Tag and
recloser status are automatically turned off after 5 minutes
of operator panel inactivity.
CHECK BATTERY
This red indicator illuminates for two conditions:
Reactivating is accomplished by pressing any operation
switch. The LCD messages will remain while in this
power-saving mode, although the illuminating backlight
will shut off.
1. Battery voltage is below 20 Vdc or drops 2Vdc or more
during battery test.
2. The control fails a manual battery test. The LED will
remain on until a successful battery test is completed.
Refer to the Battery Test Procedure in this manual for
more information.
CONTROL OK
AC POWER
ABOVE MIN TRIP
RECLOSER MALFUNCTION
This red indicator is illuminated when the control detects
a failure in a trip or close operation. It turns off automati-
cally if the recloser returns to the proper state.
CHECK BATTERY
RECLOSER MALFUNCTION
REVERSE POWER FLOW
BACK
NEXT
BUSHINGS 1-2 FAULT TARGET
REVERSE POWER FLOW
RESET
TARGETS
BUSHINGS 3-4 FAULT TARGET
BUSHINGS 5-6 FAULT TARGET
GROUND FAULT TARGET
CHANGE
RESET
MAX CURRENT
LAMP
TEST
This red indicator illuminates when the control detects
power flow from the load side to the source side of the
recloser.
NON
GND TRIP
BLOCKED
SENSITIVE-GROUND FAULT TARGET
SUPERVISORY
BLOCKED
RECLOSING
Note: Voltage sensor polarity and phase must be correct for
COLD LOAD
PICK UP
FAST
TRIPS
DISABLED
BUSHINGS 1-2 VOLTAGE
BUSHINGS 3-4 VOLTAGE
BUSHINGS 5-6 VOLTAGE
BATTERY
TEST
BLOCKED
reverse power flow to function properly.
ALTERNATE
PROFILE
ALTERNATE
PROFILE
ALTERNATE
PROFILE
NO.
1
NO.
2
NO.
3
BUSHINGS 1-2 FAULT TARGET
BUSHINGS 3-4 FAULT TARGET
BUSHINGS 5-6 FAULT TARGET
GROUND FAULT TARGET
TX 2
TX 3
HOT LINE
TAG
RECLOSER CLOSED
RECLOSER OPEN
ON
OFF RX 3 RX 2
RS232
CONTROL LOCKOUT
SENSITIVE GROUND FAULT TARGET
These red target LEDs illuminate when the control issues
an overcurrent trip signal while the respective phase cur-
rent or ground current exceeds the minimum pickup
value. Reset is accomplished automatically when Auto
Reset is activated and a successful close operation is per-
formed or manual reset is accomplished by pressing the
RESET TARGETS button on the control operator panel.
TRIP
(LOCKOUT)
®
CLOSE
KYLE
FORM 5
RECLOSER CONTROL
Figure 5.
BUSHINGS 1-2 VOLTAGE
BUSHINGS 3-4 VOLTAGE
BUSHINGS 5-6 VOLTAGE
Form 5 control operator panel.
LED Indicators
These red voltage LEDs illuminate when the control
detects the presence of voltage on the respective bush-
ings as connected to TB1. Refer to the Customer Con-
nections for AC Power section in these instructions to
determine the appropriate power connections.
The operator panel LED indicators (Figure 5) give instant
information on the control and recloser status.
LED indicators include:
CONTROL OK
RECLOSER CLOSED
This green LED is illuminated when the continuous self-
diagnostics of the control have detected no CPU or mem-
ory malfunctions and indicate that the control is capable of
normal operation.
This red indicator is illuminated when the control senses
that the recloser mechanism is in the closed position.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
RECLOSER OPEN
This green indicator is illuminated when the control senses
that the recloser mechanism is in the open position.
CONTROL LOCKOUT
This green indicator is illuminated when the recloser is
open and a reclosing sequence is not in progress or when
the lockout handle on the recloser mechanism is in the
BACK
NEXT
down position; i.e., trip and close circuits are open.
RESET
TARGETS
Note: The RECLOSER MALFUNCTION, RECLOSER OPEN,
RECLOSER CLOSED, and RECLOSER LOCKOUT
LEDs will flash upon detection of a trip failure. See the
Control Features section of this manual.
CHANGE
RESET
MAX CURRENT
LAMP
TEST
Figure 6.
TRIP (Lockout) Pushbutton
LCD display and dedicated function keys.
The TRIP pushbutton (Figure 2) provides front-panel
access to trip (lockout) the recloser. When pressed, the
TRIP push-button opens the recloser and locks out the
control.
BACK Key
Pressing the BACK key causes the LCD display to scroll
to the previous screen of available information. Pressing
and holding the BACK key causes the control to scroll to
previous screen.
CLOSE Pushbutton
When pressed, the CLOSE pushbutton (Figure 2) returns
the control to the initial or home position, closing the
recloser. The control is ready for the start of a new
trip/close sequence.
RESET TARGETS/RESET MAX
CURRENT Key
Pressing the RESET TARGETS/RESET MAX CURRENT
key resets the fault target indicators on the control opera-
tor panel. The fault current values shown on Screen 2 of
the LCD display will reset to values of zero.
Note: Pressing the CLOSE pushbutton from the Lockout posi-
tion, will initiate Cold Load Pickup (CLPU) protection, if
the feature is first enabled from the interface software
Protection Profile screen, and the COLD LOAD PICKUP
BLOCKED LED on the operator panel is not lit.
Pressing and holding the RESET TARGETS/RESET
MAX CURRENT key for three seconds will reset the min-
imum and maximum current and histogram values in LCD
Display screens 34 through 37. This key will also reset the
Trip Failure Detection feature. See the Control Features
section of this manual.
If the recloser is closed, pushing the CLOSE pushbutton
has no effect on the control. Depressing and holding the
CLOSE pushbutton does not activate the Cold Load
Pickup feature. See Cold Load Pickup in the Control
Features section of this manual.
The Form 5 control has a Manual Close Delay feature that
provides an interval of time from when the CLOSE push-
button is depressed to the time when manual close oper-
ation is performed. See Manual Close Delay in the
Control Features section of this manual.
CHANGE/LAMP TEST Key
Pressing this key for less than three seconds places the
control into a CHANGE mode for 10 seconds as indicated
by the LCD display. CHANGE mode permits the user to
change the state of the nine function/indicator switches on
the operator panel. Security is enhanced by permitting a
only one selection for each CHANGE mode period.
LCD Display
The control operator panel has a large, backlit LCD dis-
play (Figure 6) used for viewing control parameters and
monitoring system conditions. Data is organized into
screens of information, with each display containing four
lines of information, with up to 20 characters per line.
Access to the screens is obtained through navigational
keys which permit the user to scroll through the menu in a
timely and efficient manner.
Pressing and holding the CHANGE/LAMP TEST key for
three seconds will cause the control to perform a front-
panel lamp test. In the Lamp Test Mode, the status indi-
cators flash three times (one second on, one second off).
All status indicators then return to their previous state.
While in the Lamp Test Mode, the control response to
operator panel keys is disabled, except for the TRIP
(LOCKOUT), CLOSE, and HOT LINE TAG switches.
When an overcurrent trip occurs, the control automatically
displays the fault current values as shown on the LCD dis-
play as Screen 1. Refer to LCD Display Screens section
of this manual.
NEXT Key
Pressing the NEXT key causes the LCD display to scroll to
the next screen of available information. Pressing and hold-
ing the NEXT key causes the control to scroll to subsequent
screens at the rate of about two screens per second.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S280-79-10
LCD Display Screens
Screen 6 – S1 Phase-to-Neutral, Instant. Voltage
6 Instant S1 Ph-N
Every LCD display screen contains a parameter name,
parameter value, and parameter units. If the control
detects that a parameter value is invalid, the LCD display
shows five dash characters (- - - - -) in the value field of the
screen. Demand metered values are indicated by (D) and
instantaneous values by (I).
Ph1-N
Ph3-N
Ph5-N
____________ V
____________ V
____________ V
Screen 1 – Instantaneous Load Current
Screen 1 displays line current values present for the last
overcurrent trip operation. Values are reset to zero when
the fault targets are reset.
Screen 7 – S1 Phase-to-Phase, Instant. Voltage
7 Instant S1 Ph-Ph
Ph1-3
Ph3-5
Ph5-1
____________ V
____________ V
____________ V
1 Gnd
Ph1-2
Ph3-4
Ph5-6
____________ A
____________ A
____________ A
____________ A
Screen 8 – S2 Phase-to-Neutral, Instant. Voltage
8 Instant S2 Ph-N
Screen 2 – Fault Targets
Ph2-N
Ph4-N
Ph6-N
____________ V
____________ V
____________ V
2 Gnd Fault
Ph1-2 Fault
Ph3-4 Fault
Ph5-6 Fault
____________ A
____________ A
____________ A
____________ A
Screen 9 – S2 Phase-to-Phase, Instant. Voltage
9 Instant S2 Ph-Ph
Ph2-4
Ph4-6
Ph6-2
____________ V
____________ V
____________ V
Screen 3 – Frequency Trip
3 Freq Trip____________ Hz
Screen 10 – Instantaneous Voltage
Time
Date
Present Freq ____________ Hz
10 Instant S1-S2
Ph1-2 Dif ____________ V
Ph3-4 Dif ____________ V
Ph5-6 Dif ____________ V
Screen 4 – Voltage Trip
Screen 11 – Real Power
4 Ph1-N VTrip ____________ V
Ph3-N VTrip
Ph5-N VTrip
Time
____________ V
____________ V
Date
11 Tot
Ph1-2
Ph3-4
Ph5-6
____________ kW
____________ kW
____________ kW
____________ kW
Screen 12 – Instantaneous kVA
Screen 5 – Power kWh
12 Tot
Ph1-2
Ph3-4
Ph5-6
____________ kVA
____________ kVA
____________ kVA
____________ kVA
5 Tot
____________ kWh
Ph1-2
Ph3-4
Ph5-6
____________ kWh
____________ kWh
____________ kWh
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
Screen 19 – Demand Phase-to-Neutral Voltage
19 Demand S2 Ph-N
Screen 13 – Instantaneous kVAR
13 Tot
Ph1-2
Ph3-4
Ph5-6
____________ kVAr
____________ kVAr
____________ kVAr
____________ kVAr
Ph2-N(d)
Ph4-N(d)
Ph6-N(d)
____________ V
____________ V
____________ V
Screen 14 – Instantaneous Power Factor
Screen 20 – Demand Phase-to-Phase Voltage
14 Tot
Ph1-2
Ph3-4
Ph5-6
____________ PF
____________ PF
____________ PF
____________ PF
20 Demand S2 Ph-Ph
Ph2-4(d)
Ph4-6(d)
Ph6-2(d)
____________ V
____________ V
____________ V
Screen 15 –Instantaneous Total Harmonic Distortion
Current
Screen 21 – Demand Voltage
15 Gnd
Ph1-2
Ph3-4
Ph5-6
____________ %THDI
____________ %THDI
____________ %THDI
____________ %THDI
21 Demand S1-S2
Ph1-2(d)
Ph3-4(d)
Ph5-6(d)
____________ V
____________ V
____________ V
Screen 16 –Instantaneous Total Harmonic Distortion
Voltage
Screen 22 – Demand Current
16 Instant S1 Ph-N
22 Gnd
____________ A
____________ A
____________ A
____________ A
Ph1-N
Ph3-N
Ph5-N
____________ %THDV
____________ %THDV
____________ %THDV
Ph1-2 (d)
Ph3-4 (d)
Ph5-6 (d)
Screen 17 – Demand Phase to Neutral Voltage
Screen 23 – Demand kW
17 Demand S1 Ph-N
23 Tot (d)
Ph1-2(d)
Ph3-4 (d)
Ph5-6 (d)
____________ kW
Ph1-N(d) ____________ V
Ph3-N(d) ____________ V
Ph5-N(d) ____________ V
____________ kW
____________ kW
____________ kW
Screen 24 – Demand kVA
Screen 18 – Demand Phase-to-Phase Voltage
24 Tot
____________ kVA
18 Demand S1 Ph-Ph
Ph1-2(d)
Ph3-4(d)
Ph5-6(d)
____________ kVA
____________ kVA
____________ kVA
Ph1-3 (d) ____________ V
Ph3-5(d) ____________ V
Ph5-1(d) ____________ V
10
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S280-79-10
Screen 31 – Battery Monitor
Screen 25 – Total kVAr and kVAr per Phase
The Battery Monitor displays the battery voltage, current,
and voltage during a battery test. The Battery Monitor is
used with the Battery Test pushbutton. Refer to the Bat-
tery Test Procedure section of these instructions for
more information.
25 Tot
____________ kVAr
____________ kVAr
____________ kVAr
____________ kVAr
Ph1-2(d)
Ph3-4(d)
Ph5-6(d)
31 Battery Monitor
Normal
Normal
Test
_______ V
_____ mA
_______ V
Screen 26 – Demand Power Factor
26 Tot ____________ PF
Ph1-2(d) ____________ PF
Ph3-4(d) ____________ PF
Ph5-6(d) ____________ PF
Screen 32 – Phase Minimum Trip Settings
Phase minimum trip settings are listed for the four protec-
tion profiles. Line 1 is the normal setting, ALT1 is profile
No. 1, ALT2 is profile No. 2, and ALT3 is profile No. 3.
Phase Minimum Trip Settings allow verification of trip set-
tings before selection of an alternate profile.
Screen 27 – Demand THD Current
32 – Phase MT
ALT1 MT
______ A
______ A
______ A
______ A
27 Gnd
____________ %THDI
____________ %THDI
____________ %THDI
____________ %THDI
Ph1-2(d)
Ph3-4(d)
Ph5-6(d)
ALT2 MT
ALT3 MT
Screen 33 – Ground Minimum Trip Settings
Ground minimum trip settings are listed for the four pro-
tection profiles. Line 1 is the normal setting, ALT1 is pro-
file No. 1, ALT2 is profile No. 2, and ALT3 is profile No. 3.
Ground Minimum Trip Settings allow verification of trip
settings before selection of an alternate profile.
Screen 28 – Demand THD Voltage
28 Demand S1 Ph-N
Ph1-N(d)
Ph3-N(d)
Ph5-N(d)
____________ %THDV
____________ %THDV
____________ %THDV
33 Gnd MT
Alt1 MT
______ A
_______A
______A
_______A
Alt2 MT
Alt3 MT
Screen 29 – Number of Trips for Ground and Phase
29 Gnd OC Trip
Ph1-2 OC Trip
Ph3-4 OCTrip
Ph5-6 OC Trip
____________
____________
____________
____________
Screen 34 – Ground Max, Phase 1-2 Max Demand
Currents
34 Gnd Max
Time
____________A
Date
Ph1-2 Max
Time
____________A
Date
Screen 30 – Number of SGF Trips and Total Trip
Operations
Screen 35 – Phase 3-4 Max, Phase 5-6 Max Demand
Currents
30 SGF OC Trip ______
35 Ph 3-4 Max
Time
____________A
Date
Operations
______
Ph5-6 Max
Time
____________A
Date
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
Screen 41 – Communication Port 3 Settings
Screen 36 – Ground Min, Phase 1-2 Min Demand
Currents
This message displays the protocol settings (2179 or
DNP3.0), baud rate, and address for Serial Port #3.
Baud rate and address are set using the interface soft-
ware, while protocol is set at the factory based on user’s
specifications.
36 Gnd Min
Time
____________A
Date
Ph1-2 Min
Time
____________A
Date
41 – Comm Port 3
Protocol
______
_______
_______
_______
Note: Demand currents are a time integrated value and do not
reflect minimum or maximum instantaneous currents.
The demand integration time constant is set via the inter-
face software demand metering screen. These are the
same values displayed in the histogram screen.
Speed
Address
Operation/Indication Pushbuttons
Nine frequently used features are provided on the control
operator panel (Figure 7).
Screen 37 – Phase 3-4 Min, Phase 5-6 Min Currents
37 Ph3-4 Min
Time
____________A
Date
Note: These features are activated from the keypad, control
interface software or SCADA signal.
Ph5-6 Min
Time
____________A
Date
To initiate an operation from the operator panel, press the
CHANGE/LAMP TEST key to enter the CHANGE mode.
The operator has 10 seconds to select an operation and
modify settings. If no changes are made, the control will
return to its operational state prior to entering the
CHANGE mode. This prevents accidental changing of
settings.
Note: Pressing and holding the RESET TARGETS/RESET
MAX CURRENT key for three seconds will reset the
minimum and maximum Demand values.
Red LEDs located on each switch indicate the status of
the function, regardless of local or remote activation. For
example, if Cold Load Pickup was activated from a
SCADA signal, the red indicator would illuminate even
though it was not activated from the operator panel.
Screen 38 – Fault Location
38 Fault Location
Distance
____________miles
<Control Identification>
Date
Note: Operation LEDs activated from local or remote sources
do not illuminate when the front panel is in the power-
save mode.
Time
Screen 39 – Control Information
SUPERVISORY
BLOCKED
GND TRIP
BLOCKED
NON
RECLOSING
39 CPU Firmware
X.XX
Firmware FW Database
X
FAST
TRIPS
DISABLED
COLD LOAD
PICKUP
BLOCKED
BATTERY
TEST
<Control Identification>
Date
Time
ALTERNATE
PROFILE
NO. 1
ALTERNATE
PROFILE
NO. 2
ALTERNATE
PROFILE
NO. 3
Screen 40 – Communication Port 2 Settings
Figure 7.
This message displays the protocol settings (2179 or
DNP3.0), baud rate, and address for Serial Port #2.
Baud rate and address are set using the interface soft-
ware, while protocol is set at the factory based on user’s
specifications.
Operation/indication pushbuttons.
GND TRIP BLOCKED
Ground Trip Blocked is activated by pressing the
CHANGE/LAMP TEST key, then pressing the GND TRIP
BLOCKED key. The red indicator illuminates.
40 – Comm Port 2
Protocol
______
_______
_______
_______
Speed
Address
12
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S280-79-10
NON RECLOSING
HOT LINE TAG Switch
Non-reclosing mode disables any automatic reclosing
operations. Non-reclosing does not alter the active TCC.
The feature is activated by pressing the CHANGE/LAMP
TEST key, then pressing the NON RECLOSING key. The
red indicator illuminates.
WARNING: Hazardous voltage. Do not use Hot
!
Line Tag as a substitute for a visible disconnect.
Always establish a visible disconnect prior to perform-
ing any work requiring a de-energized line. Failure to
comply may cause death, severe personal injury, or
SUPERVISORY BLOCKED
equipment damage.
T276.0
Supervisory Blocked disables supervisory SCADA and the
interface software; remote SCADA remains active. Opera-
tional data and metering information are available while
the control is in the SUPERVISORY BLOCKED position.
The TRIP and CLOSE pushbuttons are active indepen-
dently of the SUPERVISORY BLOCKED function.
Hot Line Tag is provided for live-line work applications. All
closing operations are disabled when the Hot Line Tag
feature is activated. While active, the control utilizes an
independent, user-selectable time-current curve for trip
operations.
Activation of the feature is restricted to the operator panel
keypad by pressing the CHANGE/LAMP TEST key, then
pressing the SUPERVISORY BLOCKED key.
IMPORTANT: Hot Line Tag activation does not
cause the recloser to trip open. It only prevents the
recloser from closing.
COLD LOAD PICKUP BLOCKED
The Cold Load Pickup feature is blocked while the COLD
LOAD PICKUP BLOCKED is active. When CLPU is not
blocked, the control utilizes the Cold Load Pickup TCC,
reclose interval, operations to lockout and minimum trip set-
tings in lieu of the normal first operation protection settings.
IMPORTANT: Hot Line Tag is intended solely for
live-line work applications, such as maintenance,
repairs or improvements to the distribution system, that
occur while the line remains energized.
Note: The Cold Load Pickup Blocked key is replaced by the SEN-
SITIVE GROUND FAULT key on international controls.
The Hot Line Tag feature (Figure 8) consists of a toggle
switch and an LED indicator which illuminates when the
function is active. When active, Hot Line Tag prevents all
closing attempts and shifts protection to one trip to lockout
on the programmed time-current curve. The Hot Line Tag
function takes precedence over Cold Load Pickup, Non
Reclosing, and Fast Trips Disabled.
BATTERY TEST
Depressing the BATTERY TEST key performs a control
battery test. The red indicator illuminates and turns off
automatically when the control has finished performing the
test. Refer to the Battery Test Procedure section of these
instructions for further details on testing the control battery.
Activation is accomplished by placing the operator panel
toggle switch to the ON position, or via SCADA command.
Hot Line Tag is activated from the operator panel, com-
munication Port 2, communication Port 3, or a Discrete
Interface Module (DIF). All sources must be off to de-acti-
vate Hot Line Tag.
FAST TRIPS DISABLED
Fast Trips Disabled commands the control to use the pro-
grammed Fast Trips Disabled time-current curve for all
tripping operations.
ALTERNATE PROFILE Indicator/Key
The Hot Line Tag feature may only be reset by the source
which initiates the function. For example, if Hot Line Tag
is activated at the operator panel, resetting the function is
only possible at the operator panel, and not via SCADA
command. For SCADA, Hot Line Tag must be disabled
via the same port number where Hot Line Tag was origi-
nally enabled.
The control has four separate protection profiles; a normal
profile, and Alternate Profiles 1, 2, and 3. Each profile
changes all protection parameters for the control. Except for
the normal profile, each has an indication and selection key.
During control operation, if the three alternate profile indica-
tor lights are not illuminated, the normal profile is active.
To select an alternate profile, press the CHANGE/LAMP
TEST key, then press the desired alternate profile. To
return to the normal profile, simply turn off the active alter-
nate profile. These functions can also be operated
remotely via communications interfaces.
Note: Program all protection profiles. Program unused alter-
nate profiles should be programmed with the same set-
ting as one of the applicable profiles. Default settings on
unused alternate profiles can cause unnecessary out-
ages if they are below normal system requirements.
Note: The minimum trip values for each protection profile are
shown on Screens 32 and 33 of the LCD display. Check
these minimum trip values prior to changing an alternate
profile to avoid misoperation of the control under load
conditions.
HOT LINE
TAG
ON
OFF
Figure 8.
Note: On Form 5 UDP controls, Alternate Profile 3 is replaced
Hot Line Tag Switch.
with SWITCH MODE.
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
RS-232 Communication Port
Control Features
The standard Form 5 control is equipped with a operator
panel RS-232 port for interface with a personal computer
running the Form 5 interface software program. This nine-
pin female data communication equipment (DCE) Port 1
permits the uploading of all programming information
stored in the control, including protection profiles, event
recorder, data profiles, alarms, counters, and metering
information. Port 1 provides a simple means to download
operating parameters from a personal computer to the
control.The protocol, baud rate and address for Port 1 are
identified from the LCD display.
The Form 5 recloser control offers numerous standard
features and accessories that allow the user the utmost
flexibility in designing a control suitable for their applica-
tion requirements.
Under/Over Frequency Loadshedding
The Form 5 control includes provisions for frequency
loadshedding that trips the recloser for conditions of under
or over system frequency. Access to this feature is
through frequency threshold, trip time, and allowable volt-
age threshold.
If a fiber-optic or RS-232 accessory board is connected to
Port 2 (located on the back of the operator panel) any
external electrical connection from the operator panel will
disable the accessory board.
With the auto-restoration feature, the Form 5 can be set to
close the recloser after the system frequency and voltage
have recovered. Parameters available for setting include
frequency and voltage thresholds and time delay.
Note: The operator panel RS-232 port is intended only for
temporary connection of a personal computer. Perma-
nent serial communications must be made via the RS-
232 or fiber-optic accessory board.
A frequency alarm is available and can be configured for
notification.
Voltage Protection (120 Vac-based)
Battery Test Procedure
The condition of the control battery is tested by depress-
ing the BATTERY TEST hot key on the operator panel. No
external current/voltage meter is necessary for testing.
Voltage protection functionality is included as standard on
all Form 5 controls. A recloser trip will be issued for under
and over voltage conditions when the monitored voltage
falls outside user-specified limits for a selectable time.
Response mode includes any single-phase, all three
phases, and single-phase with three-phase inhibit.
Response mode facilitates protecting against a single
phase condition common when a high side fuse operates
on a distribution transformer. Parameters are also avail-
able to provide auto restoration after a trip. A voltage
alarm is available and can be configured for notification.
The control performs a self-test every 12 hours or when
initiated by an external command. When a battery test is
initiated, the spurious charge is first drained to allow the
battery voltage to equalize. A 10-ohm, 55-watt resistor is
then placed across the battery terminals and a voltage
drop is calculated. If the drop from the equalized voltage
to the test voltage exceeds 2 volts, then the CHECK BAT-
TERY LED is illuminated.
Protection Profiles
To perform a battery test:
Four separate protection profiles are included to allow the
user to adapt overcurrent settings for varying system con-
ditions such as load, live line work or weather. The active
profile is selected from the operator panel or with the inter-
face software or SCADA (Figure 9). Each profile has 14
TCC specifications plus reclose intervals, sequence coor-
dination and reset times to maintain independent protec-
tion parameters.
1. Using the Next and BACK keys, scroll through the
LCD display to Screen 31, the Battery Monitor screen.
2. Record the NORMAL VOLTS and NORMAL CUR-
RENT readings from the screen.
Note: Voltage should be between 25 to 31 volts with
higher readings at colder temperatures. Under nor-
mal conditions with ac connected and the battery
trickle charging, the current should read less than
20 mA. With ac connected and in bulk charging
mode, current will range from 12 to 600 mA. With ac
disconnected and the battery supplying the load,
current will read -180 mA to -600mA depending on
accessories connected.
3. Momentarily, press the CHANGE/LAMP TEST key,
then BATTERY TEST key.
Note: AC power can be either connected or disconnected
for Step 3.
4. Record the TEST VOLTS reading from the LCD and
the status of the CHECK BATTERY LED. Service the
battery if the CHECK BATTERY LED is illuminated.
Figure 9.
Interface software sample protection profile.
14
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S280-79-10
Power Metering
Power metering includes single- and three-phase Watts,
VARS, KVARS, KWH measurements, and the per phase
and total system Power Factor (PF).
AC POWER
ABOVE MIN TRIP
CHECK BATTERY
RECLOSER MALFUNCTION
REVERSE POWER FLOW
Power Factor Sign Metering
This feature allows a user to configure the sign that is
applied to the power factor. The user may select between
the standard definition of power factor (cosine of angle
between current and voltage) or the Cooper Power Sys-
tems default of the power factor sign following power flow.
BUSHINGS 1-2 FAULT TARGET
BUSHINGS 3-4 FAULT TARGET
BUSHINGS 5-6 FAULT TARGET
GROUND FAULT TARGET
Voltage Metering
SENSITIVE-GROUND FAULT TARGET
Six voltages (3-source and 3-load) are metered as stan-
dard on the Form 5 control. The user selects either phase-
to-phase or phase-to-ground values from the control
operator panel, interface software, or serial communica-
tions. This reference is changed by selecting the voltage
sensor correction in the “Hardware” setup portion of the
interface software.
BUSHINGS 1-2 VOLTAGE
BUSHINGS 3-4 VOLTAGE
BUSHINGS 5-6 VOLTAGE
Fast Trips Disabled
Fast Trips Disabled provides the user a quick and effi-
cient method for reducing momentary interruptions or
“blinks”. When activated from the front keypad, pro-
grammed trips to lockout will time according to the
selected time-current curve for Fast Trips Disabled. This
curve is programmable for both phase and ground on
each protection profile. A separate trips-to-lockout setting
is also provided. See Figure 9.
RECLOSER CLOSED
RECLOSER OPEN
CONTROL LOCKOUT
Figure 10.
RECLOSER MALFUNCTION, RECLOSER CLOSED,
RECLOSER OPEN and CONTROL LOCKOUT LEDs
will blink for the affected phase as indication of Trip
Failure.
Trip Failure Detection
The Trip Failure Detection feature is an internal diagnos-
tic alarm for verifying the proper operation of circuit trip-
ping and fault clearing of the recloser. Trip Failure
detection indicates the recloser has failed to trip all
phases following a trip signal from the control. Failure to
trip is assumed if a current of at least 10 Amps is detected
approximately 2 seconds after the trip signal is initiated.
IMPORTANT: The recloser must be isolated and de-
energized immediately upon detection of trip failure.
Follow proper procedures and safety practices to iso-
late and de-energize the recloser.
Upon activation of the feature, these four LEDs flash 1
second on, 1 second off (Figure 10):
The Trip Failure Detection alarm may be triggered from
many potential sources including mechanical, electrical,
control, or interrupter failure. Interrupter failure may
include loss of vacuum in a vacuum interrupter.
• RECLOSER MALFUNCTION
• RECLOSER CLOSED
• RECLOSER OPEN
To clear Trip Failure Alarm, depress and hold the RESET
TARGETS/RESET MAX CURRENTS keypad for 3 sec-
onds. This also resets targets and demand currents.
• CONTROL LOCKOUT
Note: There is no remote reset available with the trip failure
detection feature. It cannot be remotely turned off.
DANGER: Explosion. Stay clear of a recloser
!
that is in a trip failure mode. A recloser in trip fail-
When the trip failure alarm is activated, an event is
recorded and a status alarm activated (if enabled) and
preserved during system resets.
ure mode may explode resulting in death or severe per-
sonal injury.
T271.0
To test the Trip Failure Detection feature, see Testing
With Type MET Tester in the TESTING AND TROU-
BLESHOOTING section of this manual.
WARNING: Hazardous voltage. This device is
!
not a substitute for a visible disconnect. Follow all
locally approved safety practices. Failure to follow
proper safety practices can result in contact with high
voltage, which will cause death or severe personal
injury.
G112.1
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
Manual Close Delay
Event Recorder
Manual Close Delay provides a delay from the time that
the manual CLOSE button is pushed to the time the man-
ual close operation is performed.
The Event Recorder maintains a log of operating events
for later readout and analysis by the user. Approximately
500 events can be stored in non-volatile memory. For
each event type, time of occurrence, and other relevant
information is stored. When the event recorder has
reached is capacity, the oldest event is deleted as a new
event is added.
The delay is programmable from 0 to 60 seconds in 1 sec-
ond increments. A programmed delay value can be over-
ridden for immediate closing by pressing the CLOSE
button a second time.
Histograms
An active Manual Close Delay can be canceled by press-
ing the TRIP/LOCKOUT button.
Demand metered voltages and currents can be reported
using the histogram tool. It displays the number of occur-
rences of a variable versus its value in between user-
defined minimum and maximum limits. Date and time are
recorded for the maximum and minimum demand values.
The default setting has the feature disabled (0 seconds).
The RECLOSER CLOSED LED indicates the status of the
feature. See Figure 11.
RECLOSER CLOSED
RECLOSER OPEN
Data Profiler
A fully configurable data profiler is available which allows
the user to collect information by sampling demand data
at selectable intervals. These time-stamped values can
then be plotted to determine weekly load profiles, daily
harmonic disturbances or hourly voltage fluctuations. The
data profiler can provide more than 200 days of informa-
tion, depending upon configuration parameters.
CONTROL LOCKOUT
Figure 11.
The blinking of the RECLOSER CLOSED LED indi-
cates Manual Close Delay is active.
Harmonic Analysis
Cold Load Pickup
Extensive harmonic analysis is performed by the Form 5
control for both currents and voltages. Analysis is per-
formed on-line (updates every 30 seconds) or demand
integrated to user-specified time values. The Total Har-
monic Distortion (THD) for current and voltage is available
from the operator panel display (Figure 12) while com-
plete analysis, including graphing capabilities, is provided
from the Form 5 interface software.
Cold Load Pickup (CLPU) must be enabled through the
interface software (Figure 13) before it can be activated
remotely or from the CLOSE pushbutton on the operator
panel. The CLPU feature provides the user with the abil-
ity to alter protection for abnormal system conditions. It is
active for a programmable time interval which begins with
each manual close. Once this time elapses, protection
reverts back to the programmed sequence. Use the Form
5 control interface software to program the activation time
and time-current characteristics applicable to Cold-Load
Pickup.
Pg14 Gnd
Ph1-2
%THDI
%THDI
%THDI
%THDI
Ph3-4
Ph5-6
Note: When CLPU is active, the control utilizes the Cold Load
Pickup TCC, reclose interval, operations to lockout, and
minimum trip settings in lieu of the normal protection
settings.
BACK
NEXT
RESET
TARGETS
CHANGE
LAMP
TEST
RESET
MAX CURRENT
Figure 12.
Form 5 operator panel harmonic readout.
Reverse Power Flow
Feeder load monitoring is enhanced with the inclusion of
the power flow monitoring feature. When power flow from
the load to the source side of the recloser is detected, the
control illuminates an operator-panel indicator. Response
time to a reverse power condition is one second. An alarm
is also available for remote interrogation.
Note: Voltage sensor polarity must be correct for reverse
Figure 13.
power flow to function properly.
Interface software Cold Load Pickup settings.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S280-79-10
Alarms
Status and data alarms are available for many control
parameters such as voltage, currents, thresholds. Data
alarm function compares metered data to user-pro-
grammed alarm high and low limits and issues an alarm of
user-specified priority if limits are exceeded. The status
alarm function monitors status and issues an alarm of
user-defined priority when the user programmed alarm
conditions are met. The alarms are reported via commu-
nication ports and can be configured to trigger a data pro-
file and event record. Alarms do not affect the protection
functions of the control.
Fault Location
Fault Location provides an approximate distance of a fault
from the the Form 5 Control The distance is based on the
current fault magnitude, the type of fault, and system
parameters entered by the user. The LCD display (Screen
38) identifies the estimated distance in miles or kilometers
(km) from the control.
The fault location algorithm performs an impedance cal-
culation based on:
Figure 14.
Fault Location configuration screen.
• Single-phase to ground fault
• Phase-to-phase fault
The following system parameters must be entered via the
Protection Profile menu for each profile:
• Double-line to ground fault
• Three-phase fault
• Nominal system line-to-line voltage
This information is recorded as an event in the control
Event Recorder for retrieval. The fault location algorithm
does not require voltage sensing. If the location cannot be
determined, no event is recorded and dashes are dis-
played on the LCD screen.
Note: If the Fault Location feature is not desired, the nom-
inal system voltage parameter should be set at 1.
• Source-side zero sequence and positive sequence
impedance. This includes impedance up to the loca-
tion of the Form 5 control.
Setting the parameters for Fault Location is done through
the interface software. The user enters line impedance
parameters and system voltage information into the soft-
ware via the Protection Profile menu. See Figure 14.
• Line-side zero sequence and positive sequence
impedance per mile or km.
• The distance units of the line impedance in miles or
km.
IMPORTANT: Fault Location is not a protection func-
tion. Its purpose is to define a fault and provide its
approximate location relative to the Form 5 control
detecting the fault.
Refer to Service Information S280-79-2 Form 5 Micropro-
cessor-Based Recloser Control Programming Guide for
additional information.
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
Torque Angle Width parameter restricts the tripping to an
Directional Sensitive Ground/Earth
(SGF/SEF) Fault
angle of plus or minus the specified width about the
Torque angle setting. For example, if the Maximum
Torque Angle is 45°, and the Torque Angle Width is set for
10°, then the control will trip at angles between 35° and
55°.
The Directional SGF/SEF Fault feature adds directional
capabilities to the SGF/SEF protection features. It pro-
vides a sensitive ground/earth trip if the fault is downline
of the recloser on a radial distribution system. Directional
SGF/SEF is used on ungrounded Delta systems for sup-
pression of ground trips for faults occurring on other circuit
branches.
The Zero Sequence Voltage Threshold is used to set the
threshold voltage below the disabled directional SGF/SEF
tripping voltage.
Note: In most cases, a default value of 4 is adequate.
The user sets the parameters for Direction SGF/SEF
through the interface software via the Protection Profile
menu. See Figure 15. In addition to the normal (non-direc-
tional) SGF/SEF settings, the user enters the following
directional SGF/SEF parameters:
Directional SGF/SEF Fault is recorded as an event in the
control Event Recorder for retrieval. Refer to Service Infor-
mation S280-79-2 Form 5 Microprocessor-Based Recloser
Control Programming Guide for additional information.
• Direction Enable
Note: If Direction Enable is not selected, SGF/SEF tripping
occurs through normal (non-directional) settings.
• Maximum Torque Angle (-180° to 180°, in 1° increments)
• Torque Angle Width (10° to 90°, in 1° increments)
• Zero Sequence Voltage (V ) Threshold (4 to 130 V)
0
The Maximum Torque Angle parameter determines the
angle of maximum tripping sensitivity between the phase
angle of the zero sequence voltage and current at the time
of fault. The setting of this value depends on knowledge
of the power system. Typically, a resistive fault has a
value of 0°, and a capacitive fault has a value of 90°.
Figure 15.
Directional SGF/SEF configuration screen.
18
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S280-79-10
The RS-232 accessory board and the fiber-optic acces-
sory boards are located behind the operator panel. Each
accessory board can be connected to either Port 2 or Port
3; no two boards can use the same port. The operator
panel LEDs indicate the status of communication on the
accessory boards. Temporary connections to the operator
panel RS-232 port disables fiber-optic or RS-232 commu-
nication at Port 2.
Communications
Communication Ports
The Form 5 control has three communication ports from
the CPU module. Two of the three ports are user-acces-
sible. Communication Port 1 is the operator panel LCD
display where data is exchanged between the CPU and
the operator panel. Though not user-configurable, Port 1
allows for flexible modifications to the front panel for cus-
tom applications.
Port 3 provides uninterrupted communication to a
remote terminal unit (RTU). Refer to S280-79-4 Form 5
Serial communications Accessory Operation Instruc-
tions for additional information.
The operator panel RS-232 communication Port 2 pro-
vides temporary local personal computer (PC) access
when connected with a standard 9-pin cable. Port 2 pro-
vides a dual communication interface for the user. The
port includes a software switch for two external connec-
tions; the operator panel RS-232 DB-9 connector, or the
fiber-optic/RS-232 communication accessories. Local
connection to the operator panel RS-232 connection
takes precedence over the communication accessory.
Disconnecting the operator panel RS-232 communication
automatically reconnects the communication accessory
to Port 2.
TX 3
TX 2
RS232
RX 3
RX 2
Figure 17.
Fiber-Optic/RS-232 receive and transmit LEDs and
data port on the operator panel. The TX2 and RX2
LEDs illuminate during communication with the
operator panel RS-232 port.
Accessory Ports 2 and 3 are resident on the back of the
operator panel and can be configured to either 2179 or
DNP3.0 protocols. Port 3 provides uninterrupted commu-
nication to the RS-232 or Fiber-Optic accessory, and is
not affected by any other port or physical connection.
Figure 16 illustrates the communication configuration for
serial ports1, 2, and 3.
Protocols
Three protocols are available for the Form 5 control and
are factory-configurable to communication Ports 2 and 3.
TEMPORARY
ENGINEERING
ENGINEERING
SCADA SYSYEM
The protocols are:
OPERATIONS
(Local PC)
(Radio, Fiber-Optic, Modem) (Radio, Fiber-Optic, Modem)
• Cooper Power Systems 2179
• DNP3.0, Level 3
OPERATOR PANEL
DISPLAY AND
KEYPAD
OPERATOR
PANEL
RS-232
RS-232 or
FIBER-OPTIC
ACCY
RS-232 or
FIBER-OPTIC
ACCY
• S-Comm Protocol accessory
Protocol DNP3.0 includes “Unsolicited Report by Excep-
tion” functionality and Protocol 2179 includes 2-bit status
functionality.
AUTO TRANSFER
SWITCH
(Operator Panel
Connection Disables
Accessory)
Complete documentation for Cooper Power Systems pro-
tocols are:
COMMUNICATIONS
PORT 2
(Shared)
• Reference Data R280-90-12, Serial Communication
Protocol 2179
COMMUNICATIONS
PORT 1
(Internal Use Only)
COMMUNICATIONS
CPU
PORT 3
(Metering, Histograms
(Dedicated)
Profiles, Alarms, Targets)
• Reference Data R280-90-13, Communication Point
Database for Protocol 2179
Figure 16.
• Reference Date R280-90-14, Communication Point
Database for Protocol DNP3.0
Control communication port configuration.
Control Information
Fiber-Optic/RS-232 Accessory
Control information, including firmware version and
database version, is factory installed and can not be
altered by the user. This information is accessible from
the LCD display, Screen 39.
Two sets of receive and transmit LEDs (Figure 17) are
provided on the operator panel for fiber-optic and RS-232
communications. The TX2 and RX2 LEDs illuminate when
communicating with the operator panel RS-232 port. The
TX3 and RX3 LEDs illuminate when communicating with
either the fiber-optic or RS-232 interface accessory
boards on communication Port 3.
Communication Ports 2 and 3 settings can be referenced
from the LCD display, Screens 40 and 41 respectively.
(Port 1 shares the same settings as Port 2.)
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
To remove the RIF Module for configuration:
AUXILIARY POWER FOR
ACCESSORIES
1. Disconnect the control battery.
2. Remove the four connectors from the front of the RIF
Connection P9 (Figure 18) on the Power Supply module
provides 24Vdc (12Vdc is available) to power radio com-
munication units, RTUs and other accessories. The auxil-
iary power provides 40W peak load capability. Auxiliary
power is fused and current-limited to prevent user loads
from disabling the control.
Module.
3. Remove the nut and disconnect the grounding strap to
the operator panel. See Figure 4.
4. Disconnect the wiring harness connectors from the
bottom of the RIF Module.
Customer 28V connections for auxiliary power are made
to terminals 3 and 1 and are continually energized. Ter-
minal 2 and 4 are not used at this time.
Note: Press the locking tabs to release the harness con-
nectors.
5. Remove the four 11mm (.437 in) screws securing the
board to the mounting bracket.
6. Pull the module out of the cabinet.
P
8
The dip switches are located on the side of the module.
7. Configure the RIF board as shown in Figure 19.
P
C
P
O
U
W
E
R
F1
8. After configuration, place the module back into posi-
tion in the control cabinet and secure to the mounting
bracket with screws previously removed.
GDC-1A
S
9. Replace nut securing the RIF Module grounding strap
U
P
9
SW (-) 4
28V (-) 3
P
P
L
10. Replace all connectors on the front and bottom of the
A
U
X
SW (+) 2
28V (+) 1
RIF Module.
Y
Example shown for 120Vac operation:
Figure 18.
SENSOR
VOLTAGE
Power Supply Module Connection P9 provides
24Vdc power to radio communication units.
POLE1
POLE2
12Vac
120Vac*
240Vac
OFF
OFF
ON
OFF
ON
ON
*120Vac is factory-set configuration
RECLOSER INTERFACE (RIF)
MODULE CONFIGURATION
INPUT VOLTAGE
SELECTION
The Recloser Interface (RIF) Module is factory-configured
at 120Vac. For operating voltages other than 120Vac, the
RIF module must be removed from the control cabinet for
configuration.
OFF
ON
POLE 1
BUSHING 2 (XØ)
POLE 2
POLE 1
POLE 2
BUSHING 4 (YØ)
POLE 1
POLE 2
S
BUSHING 6 (ZØ)
CAUTION: Equipment damage. Always wear a ground-
ing wrist strap to control static electricity before handling
circuit boards. Failure to use this strap may result in cir-
S7
INPUT VOLTAGE
SELECTION
cuit board damage.
T253.1
OFF
ON
POLE 1
BUSHING 1 (AØ)
POLE 2
POLE 1
POLE 2
IMPORTANT: The Form 5 control must be com-
pletely de-energized prior to removing and configuring
the RIF board.
BUSHING 3 (BØ)
BUSHING 5 (CØ)
POLE 1
POLE 2
S8
Figure 19.
Recloser Interface (RIF) Module indicates the fac-
tory-configured metering voltage (120Vac).
20
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S280-79-10
FORM 5 UNIVERSAL DEVICE PROTECTION (UDP) CONTROL
The UDP function allows the Form 5 control to become a
switch control to provide indication of overcurrent trip con-
ditions without issuing an overcurrent trip signal. The con-
trol is in the recloser mode when the feature is in the OFF
position, and in the switch mode when the feature is
ACTIVE.
While in the switch mode, all automatic open and close
operations of the recloser (including overcurrent voltage
and frequency) are blocked. Fault targeting, metering,
alarms, and event recording functions are active.
This non-tripping fault indication state is initiated via a
operator panel pushbutton (labeled SWITCH MODE), dig-
ital SCADA, or discrete SCADA. The UDP feature has
local indication at the operator panel (LED), digital indica-
tion, and remote indication via status contacts on the Dis-
crete Interface (DIF) module 1.
Figure 21.
Interface software Switch Mode settings.
SUPERVISORY
BLOCKED
GND TRIP
BLOCKED
NON
RECLOSING
CONTROL OK
AC POWER
FAST
TRIPS
DISABLED
COLD LOAD
PICKUP
BLOCKED
BATTERY
TEST
ABOVE MIN TRIP
CHECK BATTERY
ALTERNATE
PROFILE
NO. 1
ALTERNATE
PROFILE
NO. 2
RECLOSER MALFUNCTION
REVERSE POWER FLOW
SWITCH
MODE
BACK
NEXT
Figure 20.
BUSHINGS 1-2 FAULT TARGET
BUSHINGS 3-4 FAULT TARGET
BUSHINGS 5-6 FAULT TARGET
GROUND FAULT TARGET
Function/Indication pushbuttons for the Form 5
equipped with the UDP accessory.
RESET
TARGETS
CHANGE
RESET
MAX CURRENT
LAMP
TEST
NON
RECLOSING
GND TRIP
BLOCKED
SENSITIVE-GROUND FAULT TARGET
SUPERVISORY
BLOCKED
COLD LOAD
PICK UP
BLOCKED
FAST
TRIPS
DISABLED
AØ
BATTERY
TEST
SOURCE
VOLTAGE
BØ
CØ
XØ
ALTERNATE
PROFILE
ALTERNATE
PROFILE
SWITCH
MODE
NO.
1
NO.
2
LOAD
VOLTAGE
YØ
ZØ
TX 2
TX 3
HOT LINE
TAG
RECLOSER CLOSED
RECLOSER OPEN
ON
OFF RX 3
RS232
RX 2
CONTROL LOCKOUT
TRIP
(LOCKOUT)
®
CLOSE
KYLE
FORM 5/UDP
RECLOSER CONTROL
Figure 22.
Form 5/UDP Operator Panel.
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
FORM 5 DC NOVA CONTROL
The Kyle Form 5 recloser control can be equipped with a
dc-to-dc converter, interface circuit, and a fully shielded
19-pin cable for use with a Type DC NOVA recloser. See
Figure 23.
The dc-to-dc converter board (Figure 24) converts the con-
trol’s 24 Vdc battery supply voltage to 53 Vdc to drive the
trip/close capacitors in the NOVA mechanism. The output
of the board is separately fused for operator indication.
The dc-to-dc converter houses voltage monitoring and
conditioning circuits which protect the battery from failure
and provides trip/close operations without AC power. The
19-pin control cable interfaces the NOVA dc recloser to
the Form 5 control through the interface circuit. The cable
also provides AC power from the control to the recloser
mechanism heater.
dc NOVA
Potential
Transformer
O
P
E
N
(120/240Vac)
Figure 24.
99007KM
Form 5
Control
Dc-to-dc converter located behind Form 5 operator
panel (removed).
19 Pin
Control Cable
120Vac/240Vac
Power Cable
Figure 23.
Connections of a Form 5 control with dc NOVA
accessory to a dc NOVA recloser.
22
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S280-79-10
DISCRETE INTERFACE (DIF)
ACCESSORY
CAUTION: Equipment damage; misoperation.
!
External leads must be shielded and the shield
must be grounded at both ends. Terminate each lead
with a 320 Vac, 160 Joules metal oxide varistor (MOV),
or equivalent, at the remote end. Attach MOVs between
the leads and ground. Failure to properly shield and
protect leads can result in equipment damage and/or
The Discrete Interface (DIF) module accessory (Figure
25) permits connection of contact-type input devices
(switches, relays) and discrete indicating devices (relays,
LEDs, lamps) to the Form 5 control to effect local discrete
input/output (I/O). The DIF module accessory is used for
supplementing normal local controls and status indicators
for discrete SCADA functions. All DIF inputs and outputs
have been factory-set and are shown in Figure 27.
unintentional operation.
G117.3
INPUT COMMON
28V (–)
4
3
2
1
IMPORTANT: Do not use DIF module for overcurrent
protection. Digital SCADA can be used for this applica-
tion. The control gives priority to TCC timing and issu-
ing a trip signal rather than changing the status of a DIF
output or responding to a DIF input.
P5
28V (+)
WHETTING
VOLTAGE
OUTPUT COMMON
12
11
10
9
8
7
6
5
4
3
6
5
4
3
2
1
P3
UNLATCHED
OUTPUTS
The DIF module contains 12 factory-set inputs and out-
puts for discrete SCADA functions. Each Form 5 control
can accommodate two DIF modules.
DISCRETE
INTERFACE
MODULE
2
1
Whetting voltage for the DIF inputs can be supplied by the
DIF module or by the customer as shown in Figure 26.
ACCESSORY
12
11
10
9
8
7
6
5
4
3
12
11
10
9
Note: 28 Vdc (nominal) is provided from the DIF module via
connector P5 for use as whetting voltage for inputs to
P4. As an alternative, the user can supply whetting volt-
age from an auxiliary source, such as a RTU.
P2
LATCHED
OUTPUTS
The input voltage range is 12 to 120 Vac or Vdc. The 12
outputs are Form C relay contacts. Six of the module out-
puts are latching and the other six are non-latching.
8
2
1
7
Note: Latching is defined as an output that retains its status
12
11
10
9
8
7
6
5
4
when control power is removed.
12
11
10
9
Non-latching is defined as an output that changes its
status when control power is removed.
8
7
6
5
4
3
2
1
Note: A remote function is not controlled by the SUPERVI-
P4
INPUTS
(12 TO 120
VAC OR VDC)
WHETTING
VOLTAGE
SORY BLOCKED switch.
3
2
1
Customer Connection
Information
Figure 25.
Discrete Interface (DIF) Module.
CAUTION: Equipment damage. Do not drill con-
nection holes into the top of the cabinet. Connec-
!
tion holes in the top of the cabinet will allow moisture to
seep into the control and damage the components or
cause control misoperation. Failure to comply will void
P5
INPUT COMMON
4
28V (-)
3
the control’s factory warranty.
T249.0
28V (+)
2
Customer-Supplied
Wiring for Whetting Voltage
OUTPUT COMMON
1
Figure 25 shows the customer-supplied wiring of whetting
voltage for DIF module inputs. Connection is made from
terminal P5 on the DIF module to the respective connec-
tions on P4 inputs 1 through 12.
REMOTE
CONTACTS
Note: Wiring to P5-2 and P5-3 can be
reversed if necessary.
To P4
Inputs 1 thru 12
Figure 27 shows customer connections to the DIF outputs
at P2 and P3.
Figure 26.
Customer connections for supplying whetting volt-
age to DIF inputs.
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
FORM 5 CONTROL
*28 Vdc (nominal)
P5
Remote Terminal Unit (RTU)
supplied by
DIF module for
whetting voltage.
INPUT COMMON
*28V (–)
*28V (+)
OUTPUT COMMON
COMMON
P3
CONTROL OK
AC POWER
R
SUPERVISORY BLOCKED
COLD LOAD PICKUP BLOCKED
INPUT
VOLTAGE
NON-RECLOSING
NORMAL PROFILE
G
R
P2
ALTERNATE PROFILE 3
ALTERNATE PROFILE 2
Discrete Interface
Module (DIF)
ALTERNATE PROFILE 1
GROUND TRIP BLOCKED
HOT LINE TAG
RECLOSER OPEN
P4
REMOTE TRIP AND LOCKOUT
Not All Remote
Connections
Shown
REMOTE TRIP AND RECLOSE
SUPERVISORY COLD LOAD PICKUP BLOCKED
SUPERVISORY NON-RECLOSING
SUPERVISORY NORMAL PROFILE
SUPERVISORY ALTERNATE PROFILE 3*
(*SWITCH MODE ON FORM 5 UDP)
SUPERVISORY ALTERNATE PROFILE 2
SUPERVISORY ALTERNATE PROFILE 1
SUPERVISORY GROUND TRIP BLOCKED
REMOTE HOT LINE TAG
SUPV. CLOSE
SUPV. TRIP & L.O.
Figure 27.
Customer connections to DIF module outputs with shielding and surge protection.
24
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S280-79-10
TABLE 1
DIF Input Ratings
Minimum Detection Level: . . . . . . . . . . . . . . . . . . . . . . . . 8 Vac
Maximum Operating Voltage: . . . . . . . . . . . . . . . . . . . . . 135 Vac
(50 or 60Hz)
(50 or 60Hz)
10 Vdc
175 Vdc
Input Impedance: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 k minimum (inputs are current limited)
Maximum Input Loading: . . . . . . . . . . . . . . . . . . . . . . . . . 2 mA per input
Maximum Leakage Rejection: . . . . . . . . . . . . . . . . . . . . . 1 mA
Maximum Pickup Time: . . . . . . . . . . . . . . . . . . . . . . . . . . 10 msec (does not count control response time)
Minimum Input Pulse Time: . . . . . . . . . . . . . . . . . . . . . . . 100 msec
Minimum Transition Time between Pulse Inputs: . . . . . . 200 msec
Input Protection: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Shunting type using MOVs and capacitors.
Opto Isolation from input to system.
IMPORTANT: Each DIF contains a small, isolated
current source for use with external dry contacts. This
supply is intended for use with the DIF inputs only and
must not be used for powering external circuits. This is
considered a dry contact input for customer connection.
TABLE 2
Whetting Voltage Source
(Supplied by Internal Voltage Source of DIF Module)
Voltage Level: . . . . . 28 Vdc (nominal)
Output Current: . . . . 30 mA maximum
TABLE 3
DIF Output Ratings
Maximum Switching Voltage: . . . . . 135 Vac 110 Vdc
Maximum Switching Loading: . . . . . 600 mA
Maximum Pickup-Release Time: . . 3 msec (does not count control response time)
Input Protection: . . . . . . . . . . . . . . . Shunting type using MOVs and capacitors
Standard and UDP Controls
Standard and UDP Form 5 control DIF inputs and outputs
are described in the following pages.
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
Standard and UDP Control DIF Module 1
Inputs
The DIF inputs are factory-configured as momentary (0.25 sec. duration) or maintained functions. Supervisory signals
do not have any effect when supervisory blocked is active. Remote inputs function when supervisory is blocked.
Input
Connector
Function
Description
1
P4-1
Supervisory Trip and Lockout
Supervisory Trip and Lockout trips the recloser open and locks out
the control. The control remains locked out until closed manually or
by the supervisory close feature. A momentary signal is required.
2
3
P4-2
P4-3
Supervisory Close
Supervisory Close initiates a closing signal to the recloser. A
momentary signal is required for proper operation.
Remote Hot Line Tag
Remote Hot Line Tag performs the same functions as the HOT
LINE TAG switch on the operator panel. Remote Hot line Tag is
activated by a maintained SCADA command, a serial command,
or locally via a operator panel switch. This input is active regardless
of the state of the supervisory function.
4
P4-4
Supervisory Ground Trip Block
Supervisory Ground Trip Block provides supervisory operation of
ground trip block by a remote momentary signal.
This input performs the same function as the GND TRIP BLOCKED
key on the operator panel. This input is inactive if the Supervisory
function is disabled.
5
6
7
P4-5
P4-6
P4-7
Supervisory Alternate Profile 1
Supervisory Alternate Profile 2
Supervisory Alternate Profile 3*
Supervisory Alternate Profiles provides selection of alternate pro-
grammed values for phase and ground. This feature is activated by
a remote momentary signal.
These inputs are active with a momentary whetting voltage and
cause the control to select the respective Supervisory Alternate Pro-
file. The inputs are inactive if the Supervisory function is disabled.
8
P4-8
Supervisory Normal Profile
Supervisory Normal Profile requires a momentary signal for proper
operation.
This input is active with a whetting voltage and causes the control
to select Normal Protection Profile. This input is inactive if the
Supervisory function is disabled.
Note: Supervisory Alternate Profile 3 replaced by Switch
Mode on UDP controls.
26
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S280-79-10
Standard and UDP Control DIF Module 1
Inputs (cont’d)
Input
Connector
Function
Description
9
P4-9
Supervisory Non-Reclosing
Supervisory Non-Reclosing provides supervisory non-reclosing
input by a remote momentary signal.
This input performs the same function as the NON-RECLOSING
key on the operator panel. This input is inactive if the Supervisory
function is disabled.
10
11
P4-10
P4-11
Suprv Cold-Load Pickup Blocked
Remote Trip and Reclose
This input performs the same function as the COLD LOAD
PICKUP BLOCKED key on the operator panel. This input is inac-
tive if the Supervisory function is disabled. A momentary signal is
required for proper operation.
Remote Trip and Reclose initiates a trip operation followed by a
reclose operation. A momentary signal is required for proper
operation.
This input is active with a whetting voltage and causes the control
to perform a trip operation followed by a reclose operation. This
input is active regardless of the state of the Supervisory function.
12
P4-12
Remote Trip and Lockout
Remote Trip and Lockout trips the recloser open and locks out the
control. It can be used for tripping from external relays and alarms.
A momentary signal is required for proper operation.
This input performs the same function as the TRIP (LOCKOUT)
switch on the operator panel and is active regardless of the state
of the Supervisory function.
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
Standard and UDP Control DIF Module 1
Outputs
The 12 outputs of the DIF Module are Form C relay contacts. Six of the outputs are latching and six are non-latching.
Note: Contacts shown in inactive mode.
Output Connector
Function
Type
Description
1
2
3
P3-1 NC
P3-2 NO
Normal Profile
Non-Latched
Normal Profile is active only when Alternate Profiles are
inactive. Normal reclosing operations will follow.
P3-3 NC
P3-4 NO
Non-Reclosing
Non-Latched
This output is active when the NON-RECLOSING indicator
in the operator panel is illuminated.
P3-5 NC
P3-6 NO
Cold-Load Pickup Blocked Non-Latched
This output is active when the COLD LOAD PICKUP
BLOCKED indicator on the operator panel is illuminated.
4
P3-7 NC
P3-8 NO
Supervisory Blocked
Non-Latched
Supervisory Blocked prevents operation from supervisory
control. Programming is accessible from the operator panel.
This output is active when the SUPERVISORY BLOCKED
indicator on the operator panel is illuminated.
AC power indicator is active when the control detects the
presence of AC power. This output is active when the AC
power indicator on the operator panel is illuminated.
5
6
7
8
P3-9 NC
P3-10 NO
AC power
Non-Latched
Non-Latched
Latched
P3-11 NC
P3-12 NO
Control OK
Recloser Open
Hot Line Tag
Control OK indicator is active when the control is able to per-
form protection operations. This output is active when the
CONTROL OK indicator on the operator panel is illuminated.
P2-1 NO
P2-2 NC
Recloser Open indicator is active when the recloser signals
the control that the recloser contacts are open. This output is
active when the RECLOSER OPEN indicator is illuminated.
P2-3 NO
P2-4 NC
Latched
With Hot Line Tag active, close circuit is disabled and the
HOT LINE TAG indicator is illuminated. With Hot Line Tag
inactive, the control switched back to the previous time cur-
rent curve for the active profile, close circuit is enabled and
the HOT LINE TAG indicator is off. This output is active
when the operator panel indicator is illuminated.
Ground Trip Blocked causes the control to block ground trip-
ping operations. This output is active when the GND TRIP
BLOCKED INDICATOR on the operator panel is illuminated.
9
P2-5 NO
P2-6 NC
Ground Trip Blocked
Latched
10
11
12
P2-7 NO
P2-8 NC
Alternate Profile 1
Alternate Profile 2
Alternate Profile 3*
Latched
Latched
Latched
These outputs are active when the respective ALTERNATE
PROFILE indicators on the operator panel is illuminated.
P2-9 NO
P2-10 NC
P2-11 NO
P2-12 NC
*Note: Supervisory Alternate Profile 3 replaced by Switch
Mode on UDP controls.
28
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S280-79-10
Standard and UDP Control DIF Module 2
Inputs
The DIF inputs are factory-configured as momentary or maintained functions. Whetting voltage for the DIF inputs is
supplied by the DIF module or by the user. The input voltage range is 12 to 120 VAC or VDC.
Input
Connector
Function
Description
1
P4-1
Supervisory Fast Trips Disabled
This input performs the same function as the FAST TRIPS DIS-
ABLED key on the operator panel and is inactive if the Supervisory
function is disabled. This is a momentary function.
2
P4-2
Supervisory Reset Targets
This input performs the same function as the RESET
TARGETS/RESET MAX CURRENT key on the operator panel.
This input is inactive if the Supervisory function is disabled. This is
a momentary function.
3
4
5
P4-3
P4-4
P4-5
Supervisory Operation Counter OFF The operation counter is disabled when this input is active with a
maintained whetting voltage. This input is inactive if the Supervi-
sory function is disabled.
Supervisory Battery Test
This input performs the same function as the BATTERY TEST key
on the operator panel. This input is inactive if the Supervisory func-
tion is disabled. This is a momentary function.
Supervisory SGF Blocked
This input is active with a momentary whetting voltage and causes
the control to block, or unblock sensitive ground fault operations.
The input is inactive if the Supervisory function is disabled.
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
Standard and UDP Control DIF Module 2
Outputs
The 12 outputs of the DIF Module are Form C relay contacts. Six of the outputs are latching and six are non-latching.
Note: Contacts shown in inactive mode.
Output Connector
Function
Type
Description
1
2
3
4
5
P3-1 (NC)
P3-2 (NO)
Control Lockout
Non-Latched
This output is active when the CONTROL LOCKOUT
indicator is illuminated.
P3-3 (NC)
P3-4 (NO)
Check Battery
Non-Latched
Non-Latched
Non-Latched
Non-Latched
This output is active when the CHECK BATTERY indi-
cator is illuminated.
P3-5 (NC)
P3-6 (NO)
Reverse Power Flow
Fast Trips Disabled
Operation Counter
This output is active when the REVERSE POWER
FLOW indicator is illuminated.
P3-7 (NC)
P3-8 (NO)
This output is active when the FAST TRIPS DIS-
ABLED indicator is illuminated.
P3-9 (NC)
If the Supervisory function is enabled, this output is
active when the OPERATION COUNTER OFF inputs
from Comm Port 1-DIF2, Comm Port 2 and Comm Port
3 are not active.
P3-10 (NO)
6
P3-11 (NC) Recloser Malfunction
P3-12 (NO)
Non-Latched
This output is active when the RECLOSER MAL-
FUNCTION indicator is illuminated.
This output is active when the BUSHINGS 1-2 FAULT
TARGET indicator is illuminated.
7
8
9
P2-1 (NO)
P2-2 (NC)
Bushings 1-2 Fault Target
Bushings 3-4 Fault Target
Bushings 5-6 Fault Target
Latched
Latched
Latched
P2-3 (NO)
P2-4 (NC)
This output is active when the BUSHINGS 3-4 FAULT
TARGET indicator is illuminated.
P2-5 (NO)
P2-6 (NC)
This output is active when the BUSHINGS 5-6 FAULT
TARGET indicator is illuminated.
10
11
12
P2-7 (NO)
P2-8 (NC)
Ground Fault Target
Latched
Latched
Latched
Output is active when the GROUND FAULT TARGET
indicator is illuminated.
P2-9 (NO)
Sensitive Ground Fault Target
Output is active when the SENSITIVE GROUND
FAULT TARGET indicator is illuminated.
P2-10 (NC)
Output is active when Sensitive Ground Fault is
blocked.
P2-11 (NO) Sensitive Ground Fault Blocked
P2-12 (NC)
30
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S280-79-10
INPUT ACCURACY
Sensed Currents
Sensed Source Voltages
Three-phase voltages used in voltage, power and power-
factor related calculations:
Note: Control only, does not include sensor tolerance, but
does include the phase current summing process.
Phase Current—Individual Phase Currents:
Range: 1 A to 10,000 A for 500:1 CTs
2 A to 20,000 A for 1000:1 CTs
Voltage measurement accuracy:
0.4V from 5V to 80V
0.5% from 80V to 135V
4 A to 40,000 A for 2000:1 CTs
Accuracy: 1 mA from 10 mA to 125 mA
0.8% from 125 mA to 1600 mA
(Control only, does not include sensor
tolerance.)
Ground Current—Vector Sum of Three-Phase Currents:
Range: 1 A to 5,000 A for 500:1 CTs
2 A to 10,000 A for 1000:1 CTs
4 A to 20,000 A for 2000:1 CTs
Accuracy: 3 mA from 10 mA to 125 mA
2.4% from 125 mA to 1600 mA
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
INSTALLATION PROCEDURE
The Form 5 control can be used with the old-style Type A
Initial Programming
Prior to Installation
CTs; however, the event recorder, data profiler and duty
cycle monitor will have limited accuracy for currents
above 5000 Amps.
CAUTION: Equipment Misoperation. Do not
Retrofit kits with the new Type B sensing CTs are avail-
able to upgrade existing families of reclosers for operation
with Form 5 controls. For additional information, contact
your Cooper Power Systems representative.
!
connect this control to an energized recloser until
all control settings have been properly programmed
and verified. Refer to the programming information for
this control. Failure to comply can result in control and
recloser misoperation, equipment damage, and per-
For identification, Table 4 lists the serial number breaks
between old-style Type A and the new-style Type B sens-
ing CTs. Below this serial number, the recloser is
equipped with the Type A CTs.
sonal injury.
G110.3
The control must be programmed with all necessary oper-
ating settings, all alternate profiles, and parameters prior
to operation with an energized recloser.
Note: For reclosers shipped prior to June 1989 and not listed
below, please contact your Cooper Power Systems rep-
resentative with the recloser type and serial number for
verification of Type A or B bushing current transformers.
Note: Program all protection profiles. Unused alternate pro-
files should be programmed with the same settings as
one of the applicable profiles. Default settings on
unused alternate profiles can cause unnecessary out-
ages if they are below normal system requirements.
TABLE 4
Serial Number Break for Reclosers with Type A
Sensing CTs
Initial programming of the control is the responsibility of a
qualified technician or engineer familiar with control func-
tions and programming parameters required for the spe-
cific recloser installation.
Recloser
Below Serial Number
RXE
5831
5894
11199
3695
7199
7208
1204
RVE
The control must be programmed with the Form 5 inter-
face software.
WE
WVE
Control / Recloser Compatibility
VWE
Reclosers manufactured prior to June 1989 are equipped
with Type A bushing current transformers. These
reclosers were designed for use with Form 2, Form 3, and
Form 3A controls. Because the Form 5 control is designed
for use with reclosers equipped with Type B current-sens-
ing Transformers, reclosers retrofitted with Form 5 con-
trols should be retrofitted with Type B current
transformers. All reclosers manufactured since 1989 are
equipped with Type B (1000:1, 1000/500:1, or 2000:1)
sensing CTs.
VWVE27
VWVE38
Control Cable
WARNING: Hazardous voltage. Recloser and
!
control must be solidly grounded. Follow all locally
approved procedures and safety practices when
grounding this equipment. Improper grounding can
result in contact with high voltage, which will cause
Reclosers equipped with Type B sensing CTs are com-
patible with all Kyle recloser controls (Form 2, Form 3,
Form 3A, Form 4A, Form 4C, FXA, FXB and Form 5, Form
5 LS/UDP controls), and are identified with the following
label prominently displayed on the recloser sleet hood or
the front of the operator cabinet:
death or severe personal injury.
G115.1
The control cable is fabricated with connectors which
mate with the female receptacle of the recloser on one
end and the male receptacle of the control on the other
end.
Note: The control cable must be supported along its length to
prevent repeated movement due to wind or other out-
side forces which can damage the cable.
NOTICE
RECLOSER IS EQUIPPED WITH
TYPE B SENSING CTs.
RECLOSER DOES NOT HAVE A
BATTERY CHARGER.
IMPORTANT: All external inputs to the Form 5 con-
trol must be routed within 8 inches of their correspond-
ing ground. During a surge, a potential of
approximately 1.5 kV per foot can develop in the con-
ductors. Differences between conductor and ground
path lengths can add additional stress to the control
components in the event of a power surge.
32
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S280-79-10
Limits on control cable length are determined by the max-
imum distance between the control and recloser:
Mounting the Control
Mount the Form 5 recloser control in a convenient, acces-
sible location. Mounting dimensions are provided in Fig-
ure 28.
• Up to 410 m (125* ft) for solenoid-operated reclosers
(VWE, VWVE27, VWVE38X, WE, WVE27, WVE38X,
and NOVA).
• For pole-mounted installation, a hole and keyway in
the control mounting bracket accommodates a 5/8”
bolt.
• Up to 10,7 m (35* ft) for motor-operated reclosers
(VSA12, VSA12B, VSA16, VSA20, VSA20A, VSO12,
VSO16).
• For substation installation, brackets are available as
an accessory for mounting the control to a substation
frame.
Up to 41 m (135* ft) for NOVA DC.
* These lengths are based on standard control cables.
Consult your Cooper Power Systems representative if
longer cable lengths are required.
Female Receptacle
C
L
For Control
Cable
Vent
35mm (1-7/16") Dia. Hole
For User 120Vac
Input Connection
(Cap-Plug Installed)
110mm
(4-1/4")
120mm (4-3/4")
40mm
(1-1/2")
45mm (1-3/4") Dia. Hole
For Automation Accessory
(Cap-Plug Installed)
130mm
(5-1/8")
190mm
(7-3/8")
C
L
200mm
(7-7/8")
Mtg Hole For
15mm (5/8") Max
Bolt Dia.*
480mm
380mm
(15")
30mm (1-1/8") Hole
In Lifting Lug
(19")
240mm
(9-1/2")
* USER-PROVIDED HARDWARE
40mm (1-1/2")
160mm
(6-3/8")
76mm
(3")
685mm
Die-cast-zinc latchable
(27")
Handle For User-
Provided Utility-Grade
Padlock
Male Receptacle
For Control Cable
110mm
(4-3/8")
350mm
Grounding Terminal
30mm
(13-13/16")
One Internal and
One External
(1-1/8")
165mm
(6-1/2")
Use No. 14 To No. 4
Stranded Wire
52 kg (115 LBS)
CONTROL WEIGHT
Figure 28.
Control cabinet mounting dimensions.
33
Download from Www.Somanuals.com. All Manuals Search And Download.
Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
Figure 29 illustrates grounding methods for 3-wire
ungrounded and 4-wire multi-grounded systems with local
supply voltage transformer.
Grounding the Control
WARNING: Hazardous Voltage. The recloser
Figure 30 illustrates grounding methods for 3-wire
ungrounded and 4-wire multi-grounded systems with
remote supply voltage transformer.
!
and control must be solidly grounded. Follow all
locally approved procedures and safety practices when
grounding this equipment. Improper grounding can
result in contact with high voltage, which will cause
Figure 31 illustrates grounding on a 3-wire uni-grounded
system.
death, severe personal injury.
G115.1
For effective surge protection all control and power con-
ductors for the Form 5 must be routed parallel to a corre-
sponding ground path. For example, the AC power supply
for the control should be parallel to and equal in length to
the transformer ground path. The control cable should be
parallel to and routed close to the recloser ground path.
The control cabinet must be grounded. A grounding con-
nector on the underside of the cabinet will accommodate
No. 14 solid through No. 4 stranded conductors.
Suggested methods for grounding the control and
recloser are shown in Figures 29, 30, and 31.
34
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S280-79-10
Grounding with a Local Supply Voltage Transformer; 4-Wire Multi-Grounded,
3-Wire Ungrounded, or Impedance-Grounded
Installation of a Form 5 control with a local supply voltage
transformer must include the following:
4-Wire Multi-Grounded Systems
IMPORTANT: In pole-mounted applications, a
ground connection must be made between the
recloser, transformer, recloser control, and SCADA
equipment for proper protection of the equipment. The
pole ground must be sized per local utility practices to
minimize the impedance between the recloser and the
control.
• Protection of the recloser bushings and the supplying
transformer with lightning arresters.
• Grounding of the recloser head and tank.
• Grounding of the transformer tank.
• Grounding of the control cabinet.
• Grounding of the SCADA equipment.
3-Wire Ungrounded and Impedance Grounded Systems
The use of a grounding mat may be required depending
upon the local safety regulations defining the permissible
step and touch potential levels. Consult local regulations
for proper grounding procedures.
IMPORTANT: All external inputs to the Form 5 con-
trol must be routed within 8 inches of their correspond-
ing ground. During a surge, a potential of approximately
1.5 kV per foot can develop in the conductors. Differ-
ences between conductor and ground path lengths can
add additional stress to the control components in the
event of a power surge.
Surge
Transformer
Arrester
Surge
Supply Voltage
Arrester
Surge
Arrester
Form 5 LS Control
Input Terminal
Block
Transformer
AC
Recloser
NEUTRAL
Head Ground
AC
NEU
GND
External
Ground Lug
Arrester Ground
ELECTRICAL CONNECTIONS
Line to Neutral connected transformer
Supply
Voltage
Recloser
Supply Voltage
Transformer
Form 5 LS Control
Line
to
Line
Voltage
Control
Cable
AC
Pole
NEUTRAL
Pole
Ground
Form 5 LS
Control
Input Terminal
Block
External
Ground Lug
Input
Terminal
Block
ELECTRICAL CONNECTIONS
Line to Line connected transformer
Customer Ground Connection
At External Lug
Figure 29.
Recommended grounding method for the Form 5 Control installed on 4-wire multi-grounded, 3-wire
ungrounded, or impedance-grounded systems with local supply voltage transformer.
35
Download from Www.Somanuals.com. All Manuals Search And Download.
Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
Grounding with a Remote Supply Voltage Transformer; 4-Wire Multi-Grounded,
3-Wire Ungrounded, or Impedance-Grounded
Installation of a Form 5 control with a remote supply volt-
age transformer must include the following:
IMPORTANT: In pole-mounted applications, a
ground connection must be made between the
recloser, transformer, recloser control, and SCADA
equipment for proper protection of the equipment. The
pole ground must be sized per local utility practices to
minimize the impedance between the recloser and the
control.
• Protection of the recloser bushings and the supplying
transformer with lightning arresters.
• Grounding of the recloser head and tank.
• Grounding of the transformer tank.
• Grounding of the control cabinet.
IMPORTANT: All external inputs to the Form 5 con-
trol must be routed within 8 inches of their correspond-
ing ground. During a surge, a potential of
approximately 1.5kV per foot can develop in the con-
ductors. Differences between conductor and ground
path lengths can add additional stress to the control
components in the event of a power surge.
• Grounding of the SCADA equipment
Low Voltage Distribution Network
Supply Voltage
Input
115 Vac
Input
Form 5 LS Control
Supply Voltage
Terminal
Block
Terminal
Block
Form 5 LS Control
Transformer
Local Isolation
Transformer
AC
AC
NEUTRAL
Customer
Supplied
NEUTRAL
Low Voltage
Low Voltage
Arrester
External
Ground Lug
External
Ground Lug
ELECTRICAL CONNECTIONS - Remote dedicated
supply transformer
ELECTRICAL CONNECTIONS - using isolation transformer
Surge
Arrester
Transformer
Surge
Arrester
Surge
Arrester
Recloser
Head
Ground
HOT
NEU
GND
Arrester
Ground
Arrester
Ground
System
Neutral
Note: Distance between
transformer and
recloser should be
one pole span or
less
Recloser
Control Cable
Pole
Supply
Voltage
Form 5 LS Control
Pole
Ground
Input Terminal Block
Pole
Customer Ground Connection
at External Lug
Figure 30.
Recommended grounding method for the Form 5 Control installed on 4-wire multi-grounded, 3-wire
ungrounded, or impedance-grounded systems with remote supply voltage transformer.
36
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S280-79-10
Grounding on a 3-Wire Uni-Grounded System
Supply Voltage
Transformer
Installation of a Form 5 control on a 3-wire uni-ground sys-
tem must include the following:
Input Terminal Block
Form 5 LS Control
Line
to
Line
Voltage
AC
• Protection of the recloser bushings and the supplying
transformer with lightning arresters.
Neutral
• Grounding of the recloser head and tank.
• Grounding of the transformer tank.
• Grounding of the control cabinet.
External Ground Lug
ELECTRICAL CONNECTIONS - Dedicated Supply
Transformer
• Grounding of the SCADA equipment.
Surge
Arrester
Surge
Arrester
Surge
WARNING: Hazardous Voltage. Use locally
approved operator safety procedures for proper
Arrester
!
insulation when maintaining this equipment. High Volt-
age step and touch potential is characteristic in uni-
ground systems. Failure to comply can cause death or
Recloser
Head Ground
HOT
NEU
GND
severe personal injury.
T262.0
Arrester Ground
Recloser
Supply
Voltage
CAUTION: Exported Potential. Do not make
!
direct electrical connections to remote devices. All
SCADA equipment must be mounted locally or con-
nected using the fiber-optic or radio communication
accessory. Direct connections to remote devices can
produce exported potential causing equipment damage
Control
Cable
Form 5 LS
Control
or personal injury.
T263.0
Input Terminal Block
CAUTION: Hazardous Voltage. Do not use a
Customer Ground
Connection
at External Lug
!
shared low voltage network to power the recloser
control unless the network is specifically designed to
withstand maximum ground potential rise. Ground
faults on a high voltage network can create a rise in
Pole
Ground
Control Height must be
3 Meters (10 feet)
minimum above earth
ground potential.
T264.0
IMPORTANT: In pole-mounted applications, a
ground connection must be made between the
recloser, transformer, recloser control, and SCADA
equipment for proper protection of the equipment. The
pole ground must be sized per local utility practices to
minimize the impedance between the recloser and the
control.
Figure 31.
Recommended grounding method for the Form 5
Control installed on a 3-wire uni-grounded system.
IMPORTANT: All external inputs to the Form 5 con-
trol must be routed within 8 inches of their correspond-
ing ground. During a surge, a potential of
approximately 1.5kV per foot can develop in the con-
ductors. Differences between conductor and ground
path lengths can add additional stress to the control
components in the event of a power surge.
37
Download from Www.Somanuals.com. All Manuals Search And Download.
Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
Customer Connections for AC
Power
CAUTION: Equipment damage. Do not drill con-
!
nection holes into the top of the cabinet. Connec-
tion holes in the top of the cabinet will allow moisture to
seep into the control and damage the components or
cause control misoperation. Failure to comply will void
the control’s factory warranty.
T249.0
Input power to the Form 5 control is connected to terminal
block TB1 (located behind the operator panel, on the left
side of the control). See Figure 33.
Input power is required:
• To power the control
• To provide voltage and power metering
• For voltage detection for loop scheme accessory
• For the low voltage closing accessory
• For the convenience outlet accessory
Figure 33.
Terminal Connector Block TB1.
99003KM
Power Connections
Power Supply Verification
Customer connections to TB1 vary upon application. TB1
connections provide power and metering inputs to the
control. Figures 34 through 39 show the customer con-
nections for 120 Vac and 240 Vac low voltage closing.
Incoming power is routed to the Power Supply module
which is factory configured for either 120 or 240 volt oper-
ation. The power supply module is factory wired to TB-1
and protected by the 3.15 Amp fuse labeled F2 on the
power supply operator panel. A label on the Power Sup-
ply module indicates the proper voltage rating. See Figure
32.
Figures 34 through 37 illustrate customer connections for
single-phase transformers. Figure 34 shows standard
wiring with BØ transformer connected to TB1-2 location.
Other phases should be connected from the single-phase
transformer by wiring the BLACK wire from the Power
Supply module to the terminal of the respective phase as
shown in Figure 38 and 39. For example, Figure 39 shows
connection from the Power Supply module to an AØ
transformer.
M
F2
O
GDC-3.15A
D
CONFIGURED
U
FOR
L
120
VAC
E
The transformer required for power should be a minimum
of 5kVA for low-voltage ac closing reclosers and 1kVA for
dc closing reclosers.
240
VAC
Note: An out-of-service Form 5 or Form 5 UDP control (for
either Wye or Delta) can be powered by connecting to
TB1-2 (hot) and TB1-4 (neutral) to an appropriate power
source.
Figure 32.
Label on Power Supply module indicates factory-
configured voltage rating (120Vac).
IMPORTANT: Delta connections are not used on any
Form 5 control accessory that utilizes the low voltage
transfer relay.
Inserting and Releasing Wire
Connections
In Terminal Block TB1, each terminal has a wire locking
clamp that has to be opened to accept and secure the
wire. A 3/32 inch flat-blade screwdriver is inserted into
each terminal hole to open the locking clamp. Figure 34
provides the procedure for opening and securing the wire
connections.
Customer Connections for
Metering
Customer voltage inputs for metering are field config-
urable on the RIF module to accept 12, 120, or 240 Vac.
The incoming power supply must match the indication for
incoming power on the RIF module. The factory-config-
ured settings for the RIF are displayed on the module
panel. See Figure 19.
The wire is inserted into the terminal connection hole
while the screwdriver is placed into the wire release and
locking hole.
Follow the same procedure to release wire connections.
See RIF Module Configuration section of this manual.
38
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S280-79-10
TB1
(Top View)
To insert wire:
1. Insert 3/32 inch flat-
blade screwdriver into
Wire Release and
Locking hole.
TB1
16
AØ
240Vac CLOSING
OPTION
2. Carefully insert the
screwdriver along side
the locking clamp.
15
14
Y' VOLTAGE
120Vac
B' VOLTAGE
120Vac
CLOSING
VOLTAGE
3. Pull toward the center
of terminal block TB1
until the locking clamp
opens.
13
12
NEUTRAL
SOURCE 2
BØ
NEUTRAL
SOURCE 1
11
10
9
4. Insert wire into Terminal
Connection hole.
NEUTRAL
5. Release screwdriver.
6. Carefully pull wire to be
sure it is secure.
Note: Only slight pressure is
required to open the
AC
ZØ
CUSTOMER
CONNECTIONS
locking clamp. Excessive
pressure can damage
the terminal block.
CØ
SOURCE 2
POWER
YØ
XØ
8
Wire Release
and Locking Hole
7
6
HOT (LV Closing Output)
NEU (LV Closing Output)
OUTPUT
VOLTAGE
POWER
SOURCE
OUTPUT
Terminal
TB1
NEUTRAL
5
Connection Hole
16
NEU
*NEUTRAL
4
3
15
14
13
AC
CØ
BØ
AØ
CØ
CUSTOMER
CONNECTIONS
SOURCE 1
POWER
*BØ
AØ
2
1
12
11
10
9
3/32 inch
Flat-Blade
Screwdriver
Connection
Wire
*REQUIRED FOR
CONTROL OPERATION
8
Figure 34.
Form 5 and Form 5 UDP Power and Low Voltage Closing customer connections to terminal block TB1
(120Vac or 240Vac Wye Connection).
TB1
AØ
16
240V CLOSING
OPTION
15
14
13
12
BØ
11
10
9
ZØ
YØ
XØ
CØ
AC
CUSTOMER
SOURCE 2
POWER
8
CONNECTIONS
7
6
HOT (LV Closing Output)
HOT (LV Closing Output)
OUTPUT
VOLTAGE
POWER
SOURCE
OUTPUT
OUTPUT
VOLTAGE
5
CØ
BØ
AØ
4
3
*CØ
BØ
AC
CUSTOMER
CONNECTIONS
SOURCE 1
POWER
*AØ
2
1
*REQUIRED FOR
CONTROL OPERATION
SEE POWER SUPPLY
MODULE FOR
CORRECT VOLTAGE
Figure 35.
Form 5 and Form 5 UDP Power and Low Voltage Closing customer connections to terminal block TB1
(120Vac or 240Vac Delta Connection).
39
Download from Www.Somanuals.com. All Manuals Search And Download.
Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
TB1
AØ
16
240V CLOSING
OPTION
15
14
13
12
BØ
CØ
11
10
9
ZØ
YØ
XØ
AC
CUSTOMER
SOURCE 2
POWER
8
CONNECTIONS
7
6
OUTPUT
VOLTAGE
HOT (LV Closing Output)
HOT (LV Closing Output)
POWER
SOURCE
OUTPUT
OUTPUT
VOLTAGE
5
CØ
BØ
AØ
4
3
*CØ
BØ
AC
CUSTOMER
CONNECTIONS
SOURCE 1
POWER
*AØ
2
1
*REQUIRED FOR
CONTROL OPERATION
SEE POWER SUPPLY
MODULE FOR
CORRECT VOLTAGE
Figure 36.
Form 5 and Form 5 UDP Power and Low Voltage Closing customer connections to terminal block TB1
(120Vac or 240Vac Open-Delta Connection).
TB1
120Vac
HOT (240Vac LV Closing Output)†
16
240V CLOSING
OPTION
HOT (240Vac LV Closing Output)†
Neutral
120Vac
15
Y' VOLTAGE
14
13
12
CLOSING
VOLTAGE
120Vac
B' VOLTAGE
120Vac
NEUTRAL
SOURCE 2
NEUTRAL
SOURCE 1
11
10
9
NEUTRAL
AC
ZØ
YØ
CUSTOMER
CONNECTIONS
8
SOURCE 2
POWER
XØ
7
6
OUTPUT
VOLTAGE
HOT (120Vac LV Closing Output)
NEU (120Vac LV Closing Output)
POWER
SOURCE
OUTPUT
OUTPUT
VOLTAGE
5
4
3
*NEUTRAL
AC
CØ
CUSTOMER
CONNECTIONS
SOURCE 1
POWER
2
1
*BØ
AØ
† For use with accessories:
3-Wire Low-Voltage Closing with receptacle
or
3-Wire Low-Voltage Closing with inlet hole for hardwiring
*REQUIRED FOR
CONTROL OPERATION
Figure 37.
Form 5 and Form 5 UDP Power and Low Voltage Closing customer connections to terminal block TB1
(3-wire, 240Vac Connection).
40
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S280-79-10
P
O
W
E
TB1
16
240Vac CLOSING
OPTION
R
15
14
S
U
P
P
L
YØ VOLTAGE
P
9
120Vac
BØ VOLTAGE
120Vac
CLOSING
VOLTAGE
13
12
A
U
X
Y
NEUTRAL
SOURCE 2
BØ
M
O
D
U
L
F2
NEUTRAL
SOURCE 1
GDC-3.15A
11
10
9
CONFIGURED
FOR
NEUTRAL
120
VAC
E
AC
240
ZØ
VAC
CUSTOMER
CONNECTIONS
SOURCE 2
YØ
8
POWER
BLK
WHT
XØ
7
6
HOT (LV Closing Output)
NEU (LV Closing Output)
OUTPUT
VOLTAGE
POWER
SOURCE
OUTPUT
NEUTRAL
5
NEU
*NEUTRAL
4
3
AC
CØ
Jumper**
CUSTOMER
CONNECTIONS
SOURCE 1
*BØ
BØ
2
1
POWER
AØ
*REQUIRED FOR
CONTROL OPERATION
**Jumper necessary for use with Low-Voltage Closing Accessory
Figure 38.
Form 5 and Form 5 UDP Power and Low Voltage Closing customer connections to terminal block TB1 (Single-
Phase Connection, Standard BØ Input).
P
O
TB1
16
W
E
R
240Vac CLOSING
OPTION
15
14
S
U
P
P
L
Y' VOLTAGE
P
9
120Vac
B' VOLTAGE
120Vac
CLOSING
VOLTAGE
13
12
A
U
X
Y
NEUTRAL
SOURCE 2
AØ
M
O
D
U
L
F2
NEUTRAL
SOURCE 1
GDC-3.15A
11
10
9
CONFIGURED
FOR
NEUTRAL
120
VAC
E
AC
240
ZØ
VAC
CUSTOMER
CONNECTIONS
SOURCE 2
POWER
YØ
XØ
8
BLK
WHT
7
6
HOT (LV Closing Output)
NEU (LV Closing Output)
OUTPUT
VOLTAGE
POWER
SOURCE
OUTPUT
NEUTRAL
5
NEU
*NEUTRAL
4
3
AC
CØ
Jumper**
CUSTOMER
CONNECTIONS
SOURCE 1
POWER
*BØ
AØ
2
1
AØ
*REQUIRED FOR
CONTROL OPERATION
**Jumper necessary for use with Low-Voltage Closing Accessory
Figure 39.
Form 5 and Form 5 UDP Power and Low Voltage Closing customer connections to terminal block TB1 (Single-
Phase Connection, AØ Input).
41
Download from Www.Somanuals.com. All Manuals Search And Download.
Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
Before Placing the Control and
WARNING: Hazardous voltage. Recloser and
the Recloser into Service
!
control must be solidly grounded. Follow all
locally approved procedures and safety practices when
grounding this equipment. Improper grounding can
result in contact with high voltage, which will cause
CAUTION: Equipment misoperation. Do not
!
connect this control to an energized recloser
death or severe personal injury.
G115.1
until all control settings have been properly pro-
grammed and verified. Refer to the programming
information for this control. Failure to comply can
result in control and recloser misoperation, equip-
3. Control and recloser properly grounded in accordance
with guidelines in this manual.
ment damage and personal injury.
G110.3
4. AC power connected to the control. (AC power LED
indicator is illuminated.)
5. Control battery connected and tested for proper
Prior to placing the control and recloser into service, the
following installation procedures must be properly com-
pleted and verified:
operation.
6. All control programming entered and verified by
appropriate personnel.
1. Control properly mounted for the installation.
7. Control clock set to the correct time.
2. Recloser installed according to all locally approved
standards and practices.
8. Customer connections for remote and supervisory
operation checked and completed in accordance with
proper shielding and surge protection.
9. Control cable properly connected and supported.
42
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S280-79-10
TESTING AND TROUBLESHOOTING
CAUTION: Equipment misoperation. Do not
!
connect this control to an energized recloser
until all control settings have been properly pro-
grammed and verified. Refer to the programming
information for this control. Failure to comply can
result in control and recloser misoperation, equip-
CPU Module LED Indicator
ment damage and personal injury.
G110.3
IMPORTANT: The Form 5 recloser control can be
taken out of service for testing and placed back into
service without de-energizing its recloser and interrupt-
ing the system. However, during the time the control is
out of service, the recloser is inoperative.
CPU Module
(Central Processing Unit)
Testing an Installed Control
The following tests to determine initial operation of the
Form 5 control can be performed while connected to an
operating recloser. These are the only tests performed on
an installed, operating control. All other tests described in
this Testing and Troubleshooting section require the
Form 5 control to be removed from service, connected to
a bypassed recloser, or tested at a location where the
proper testing equipment is available.
99002KM
Figure 40.
Form 5 control CPU module.
of all operating parameters. Refer to Service Information
S280-76-1 Type MET Electronic Recloser Control Tester
Operator Instructions for proper setup and use of the MET
tester. Refer to Form 5 Control Default Test Procedure
section of this manual for specific tests requiring the
KMET Tester.
1. Wake-up the operator panel display by pressing the
CHANGE/LAMP TEST button on the control operator
panel.
2. Scroll through the LCD display messages as
described in the LCD Display Messages section of
these instructions. Refer to Form 5 Control operator
panel section of this manual.
IMPORTANT: The Form 5 DC NOVA control cannot
be tested with the standard Kyle MET Tester. A junc-
tion box accessory for the MET tester is available for
testing the Form 5 DC NOVA control.
Check the operational values for currents, voltages,
and other metering information.
3. Check that the LED for AC power is illuminated on the
control operator panel. This indicates the presence of
AC power.
IMPORTANT: When the control is open and current
is present, the Trip Fail detection circuit in the Form 5
control will activate when the Kyle Type MET tester
CALIBRATE switch is ON. Depress and hold the
RESET TARGET keypad on the control for 3 seconds
to reset the condition.
4. Test battery operation, using the procedures
described in the Battery Test Procedure section of
these instructions.
Check CPU Status
Check the operating status of the CPU module. Open the
cabinet door and locate the LED indicator (Figure 40).
The LED indicator on the CPU module should flash at a
rate of one flash per second for normal 60 Hz operation
(slightly faster for 50Hz).
Testing With Type MET Tester
The Kyle Type MET Electronic Recloser Control Tester
(Figure 41) is used for testing the Form 5 control.
The MET Tester is completely self-contained, includes all
necessary metering and interconnecting cables, and is
capable of performing all required checks and tests from
a simple verification of operation to a complete verification
010028KM
Figure 41.
Kyle Type MET electronic recloser control tester.
43
Download from Www.Somanuals.com. All Manuals Search And Download.
Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
Electrical Closing—Motor-Operated
Reclosers
Closing the Recloser During
Testing
WARNING: Hazardous voltage. Solidly ground
WARNING: Hazardous voltage. The switchgear
!
!
all equipment. Failure to comply can result in
and high voltage transformer must be in a test
death, severe personal injury, and equipment damage.
cage or similar protective device to prevent accidental
contact with the high voltage parts. Solidly ground all
equipment. Failure to comply can result in death,
T223.2
severe personal injury, and equipment damage.
T221.3
High-voltage is not required for reclosers utilizing a motor-
operated closing mechanism energized from a 230VAC
power source. For information on energizing the recloser,
refer to the appropriate motor-operated recloser installa-
tion manual.
Electrical Closing—Solenoid-Operated
Reclosers
Line voltage is required for automatic recloser operation
during testing of reclosers equipped with a closing
solenoid (except for reclosers equipped with the low volt-
age closing accessory).
Figure 43 shows a test circuit for motor-operated and
solenoid-closing reclosers with low-voltage closing. Since
these reclosers require only a 240 Vac source for closing,
high-voltage transformer T3 and its protective cage is
eliminated. All other equipment is the same as the test
equipment shown in Figure 42.
For on-line testing, bypass the recloser, open the load-
side disconnects and keep the source-side disconnects
closed. This will remove the recloser from service, but will
keep line voltage supplied to the closing solenoid (Figure
44).
Sensing CTs (3)
For shop testing, the closing solenoid voltage is supplied
by back-feeding a transformer with a low-side rating equal
to the voltage rating of an available power source, and a
high-side rating equal to the voltage rating of the recloser
(Figure 45). A 75kVA transformer of the proper voltage
rating with an impedance drop of approximately 3% is sat-
isfactory. The ac source must have a comparable
impedance drop.
5
6
J
3
1
4
2
H
G
The closing coil requirement is approximately 200kVA
during the two-to-three cycle closing operation. The
solenoid coil operating voltage must be maintained at the
recloser bushings during the cycle interval the closing coil
is energized. This procedure is not used on reclosers
equipped with the low-voltage closing accessory.
X
W
K
Closing
Motor
240 Vac
Power
Supply
WARNING: Hazardous voltage. Interconnect
source leads X and Y and ground solidly to the
!
recloser tank (Figure 45). Do not connect lead Z to any
other phase or mechanical ground. Dangerous voltages
to ground exist on the phase connected to lead Z. Solidly
ground all equipment. Failure to comply can result in
240 Vac
To Ammeter
and Relay
to operate
cycle counter or
other timing
device
T1
Variable
Autotransformer
240 Vac-20 A
T2
Electronic
Control
severe personal injury and/or equipment damage.
T224.1
120 Vac
Variable
115Vac
Autotransformer
(10 Amp)
600:5
Recloser
Figure 43.
BCT ON 600:5 Tap
Suggested test circuit for motor-operated, solenoid-
closing reclosers with low-voltage closing.
2
Clamp-On
Ammeter
1
Note: This test circuit
can apply over
800 Amps to the
recloser.
Electrical Closing—NOVA Reclosers
Note: Use at least 2/0
cable between
bushings.
Type NOVA 3-phase reclosers utilize an interface circuit
located in the mechanism housing. The electronic inter-
face circuit controls the opening and closing signals to the
magnetic actuator.
Figure 42.
Alternate method of producing variable line current
(substitute for T2 and W-X circuit in Figures 43 and
45).
The Dc NOVA Recloser is tested with the dc-to-dc con-
verter and 19-pin cable connected to the dc power supply.
44
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S280-79-10
BYPASS SWITCHES
(CLOSED)
C
B
A
5
3
1
6
4
2
LOAD SIDE
SOURCE SIDE
DISCONNECT SWITCHES
(OPEN)
DISCONNECT SWITCHES
(CLOSED)
Figure 44.
Closing source-side switches of a bypassed “on-line” recloser provides closing solenoid power for automatic
operation during testing.
CLOSING
VOLTAGE RATING OF
RECLOSER CLOSING
SOLENOID COIL
SENSING CTs (3)
SOLENOID
CONTACTOR
Z
5
6
J
TO
MAIN
CONTACTS (S)
240 OR
480 VAC
SOURCE
ROTARY
SOLENOID
T3
Y
3
4
TRIP
SOLENOID
E F
H
CLOSING
SOLENOID
COIL
A
B
X
W
2
1
CONTROL
CABLE RECEPTACLE
G
K
TO
240 VAC
SOURCE
TO
AMMETER AND RELAY TO
OPERATE CYCLE COUNTER
OR OTHER TIMING DEVICE
ELECTRONIC
CONTROL
T2
VARIABLE
120 VAC
AUTOTRANSFORMER
240 VAC
20 AMPS
Figure 45.
Suggested test circuit for “shop-testing” solenoid-closing reclosers.
45
Download from Www.Somanuals.com. All Manuals Search And Download.
Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
4. After each trip operation, about 1/2 second elapses
Manual Closing—Solenoid-Operated
Reclosers
while the closing solenoid plunger is moving upward to
reset the main toggle latch.
5. After the main toggle latch resets, the recloser can be
WARNING: Explosion Hazard. Excessive Con-
!
closed again by operating the manual closing tool.
tact Arcing. Do not use the manual closing tool to
close an oil-insulated, energized recloser. Closing an
energized oil-insulated recloser with a manual closing
tool can cause excessive contact arcing, rapid build-up
of gas within the equipment, and possible explosion
that can cause death, severe personal injury, and
6. Replace the gasket and port cover on the recloser
head after testing has been completed.
equipment damage.
T203.2
If high-voltage for operating the closing solenoid is not
available, manual closing can be substituted for electrical
closing. However, not all control settings can be checked
since manual closing is not synchronized with the closing
coil control circuit in the control.
To manually close the recloser:
1. Remove the closing tool port cover and gasket from
the side of the recloser head casting.
2. Insert the tee-handled tool (available as an accessory)
into the port, engaging the pin on the closing shaft
(Figure 46).
CAUTION: Equipment damage. Do not turn the man-
ual closing tool more than one-quarter turn clockwise.
Forcing the tool beyond the mechanism stop may shear
82284KMA-F
Figure 46.
the pin on the closing shaft of the recloser.
T222.0
Using a manual closing tool to operate the recloser.
3. Close the recloser by placing the yellow operating
handle (located under the sleethood) into the up or
CLOSED position and turning the closing tool one-
quarter turn clockwise.
46
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S280-79-10
FORM 5 CONTROL DEFAULT TEST PROCEDURE
Test Battery Circuitry
CAUTION: Equipment misoperation. Do not con-
!
nect this control to an energized recloser until all
IMPORTANT: The Battery Test procedure requires
large current drain. Overuse of this procedure will drain
the battery.
control settings have been properly programmed and
verified. Refer to the programming information for this
control. Failure to comply can result in control and
recloser misoperation, equipment damage, and per-
sonal injury.
G110.3
1. Press BACK button on display panel until Battery Test
Screen 31 appears.
2. Record values for all settings.
IMPORTANT: The Form 5 recloser control can be
taken out of service for testing and placed back into
service without de-energizing its recloser and interrupt-
ing the system. However, during the time the control is
out of service, the recloser is inoperative.
3. Press CHANGE button on the display panel.
4. Press BATTERY TEST button on display panel.
5. Record values for all readings.
Test Phase Minimum Trip Values
1. Verify Ground Trip Block LED is on.
IMPORTANT: The Form 5 DC NOVA control can not
be tested with the standard Kyle MET Tester. A junction
box accessory for the MET tester is availble for testing
the Form 5 DC NOVA control.
2. Set KMET Phase Selector S5 to A.
3. Set KMET switch S4 to 300 milliampere range.
4. Set KMET Variac TR1 to zero.
Use this procedure to test the Form 5 control with factory
default control settings. Follow all cautions and warnings
in these service instructions.
5. Set KMET switch S2 to test fault current position.
6. Press the TRIP button on the display panel.
7. Press the CLOSE button on the display panel.
Before installation on an active feeder, the Form 5 con-
trol’s final control settings must be fully tested using an
appropriate test procedure. The Form 5 Control Default
Test Sheet follows these instructions. The Form 5 Control
Default Test Sheet Optimal Values gives the optimal val-
ues for the test results.
8. Slowly raise TR1 until Above Minimum Trip LED is on,
on display panel. Control should trip out quickly for
load currents above 105 milliamperes. Record value.
9. Repeat steps 4 – 8 for phases B and C (move KMET
When performing these tests, change the Form 5 panel
settings by first pressing the CHANGE button and then
pressing the button of the function to be changed.
S5 to B, then C).
10. Change Form 5 control from Normal Profile to Alter-
nate Profile 1.
Initial Settings
11. Verify Cold Load Pickup Blocked (LED is on) on the
1. Apply 120 (240) Vac to the control phase B and neu-
display panel.
tral for standard controls.
12. Repeat steps 2 – 9 for Form 5 Alternate Profiles 1, 2,
and 3. The control is programmed to trip out at 200
milliamperes on the Alternate 1, 2, and 3 Profiles.
2. Plug in battery.
3. Verify control is programmed for all default settings.
• Phase Minimum Trip is set to 100 amps.
• Ground Minimum Trip is set to 50 amps.
Note: If Cold Load Pickup LED is off, the control will trip on a
time delayed Time Current Curve with two trips to lock-
out for 30 seconds after closing in the control, per the
default Cold Load Pickup control settings.
4. Disable Sequence Coordination in normal profile
Note: If Alternate Profiles 1, 2, and 3 have the sequence coor-
dination function enabled while testing the Form 5 con-
trol minimum trip values, it may result in the control
skipping past the fast TCC curves during the test for
minimum trip. The control will then lock out on the
delayed TCC curves.
using personal computer (PC).
5. Activate COLD LOAD PICKUP BLOCKED (LED is on)
on Form 5 display panel.
6. Activate GROUND TRIP BLOCK (LED is on) on Form
5 display panel.
Note: If the Form 5 control has Switch Mode rather than Pro-
file 3, the control will indicate current Above Minimum
Trip, but will not trip out.
47
Download from Www.Somanuals.com. All Manuals Search And Download.
Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
16. Set KMET test set Fault Current Switch S2 to test fault
Test Ground Minimum Trip Values
1. Change the Form 5 control from an Alternate Profile to
the Normal Profile (all three Profile LEDs are off). Dis-
able Ground Trip Block (LED off).
current position. Record timings from the KMET test
set for all trips on the B 5X ___ locations on the test
sheet.
17. Set KMET Phase Selector S5 to phase C.
2. Set KMET switch S4 to 100 milliampere range.
3. Set KMET Variac TR1 to zero.
18. Calibrate KMET Phase Selector S5 to 1000% of fault
(1000 milliamperes).
4. Set KMET switch S2 to test fault position.
19. Press the TRIP button on the display panel.
20. Press the CLOSE button on the display panel.
5. Verify the Form 5 phase minimum trip values are
higher than the ground trip values.
21. Set KMET test set Fault Current Switch S2 to test fault
current position. Record timings from the KMET test
set for all trips on the C 10X ___ locations on the test
sheet.
6. Set KMET Phase Selector S5 to A.
7. Press the TRIP button on the display panel.
8. Press the CLOSE button on the display panel.
22. Repeat steps 2 – 21 for Alternate Profiles 1, 2, and 3.
Note that the Phase minimum trip for the Alternate
Profiles is 200 amps. The 200% fault will then be 400
milliamperes or .4 amp, the 500% fault will then be
1000 milliamperes or 1 amp, and the 1000% fault will
then be 2000 milliamperes or 2 amps.
9. Slowly raise TR1 until Above Minimum Trip shows on
Form 5 control. Control should trip out for load cur-
rents above 50 milliamperes. Record values.
10. Repeat steps 4 – 9 for the Form 5 Alternate Profiles 1,
2, and 3. The control is programmed to trip out at 100
milliamperes on the Alternate 1, 2, and 3 Profiles.
Test Ground Timing
1. Verify control is programmed for all default settings.
Note: If Cold Load Pickup is activated (LED off), the control will
trip on a time delayed TCC with two trips to lockout for
30 seconds after closing in the control, per the default
Cold Load Pickup control settings.
2. Disable GROUND TRIP BLOCK (LED off). Ground
Trip is active.
Test Phase Timing
3. Activate the Normal Profile (Alternate Profile LEDs
off).
1. Set the Form 5 control to Normal profile (all Alternate
Profile LEDs off).
Note: When testing the ground trip timing circuit, the KMET
test set applies a phase to ground fault to the Form 5
control. If the applied fault current exceeds the phase
minimum trip value, the control may time out on the
phase time current curve, which may be shorter than the
proper ground time current curve. For this reason, the
Form 5 phase minimum trip value should be increased
to a higher value while testing Form 5 ground trip time
current curves.
2. Activate GROUND TRIP BLOCK (LED on). Ground
Trip is blocked.
3. Set KMET Phase Selector S5 to phase A.
4. Set KMET switch S4 to 300 milliampere range.
5. Press the Form 5 trip switch once to lock out the Form
5 control.
4. Increase the Form 5 phase minimum trip value to
6. Set KMET phase selector S3 to Control Response.
1600 amperes.
7. While holding the KMET Test Fault Current Switch S2
in the Calibrate position, adjust the fault current to 200
percent fault (100 X 2 or 200 milliamperes).
5. Set KMET Test Set switch S4 to the 300 milliampere
position.
6. While holding the Fault Current Switch S2 in the Cali-
brate position, adjust the fault current to 200 percent
fault (50 X 2 or 60 milliamperes).
Note: On newer controls, applying fault current while the
control is locked out will set the Recloser Malfunction
LED. This will not affect testing. To clear, press the
Reset Targets button after all tests are complete.
7. Press the TRIP button on the display panel.
8. Press the CLOSE button on the display panel.
8. Press the TRIP button on the display panel.
9. Press the CLOSE button on the display panel.
9. Set KMET test set Fault Current switch S2 in the test
fault current position. Record timings from the KMET
test set for all trips on the G 2X ___ locations on the
test sheet.
10. Set KMET Fault Switch S2 to test fault current posi-
tion. Record timing readings from the KMET time
clock for all trips on the A 2X___ test sheet location.
11. Set KMET Test Set switch S4 to the 1A position.
12. Set KMET Phase Selector S5 to phase B.
10. Calibrate KMET fault current to 500 percent, (50 X 5
or 250 milliamperes).
11. Press the TRIP button on the display panel.
12. Press the CLOSE button on the display panel.
13. Calibrate KMET fault current to 500 percent (100 X 5
or 500 milliamperes) using the KMET 1A range.
14. Press the TRIP button on the display panel.
15. Press the CLOSE button on the display panel.
48
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S280-79-10
13. Set KMET test set Fault Current switch S2 in the test
fault current position. Record timings from the KMET
test set for all trips on the G 5X ___ locations on the
test sheet.
5. Control should trip twice on slow TCC curve, then indi-
cate open and lockout. Record timing value.
6. Activate COLD LOAD PICKUP BLOCKED (LED on).
7. Repeat steps 2 – 4. Record value.
14. Set KMET Test Set switch S4 to the 1A position.
Test Fast Trips Disabled
1. Activate FAST TRIPS DISABLED (LED on).
2. CLOSE the Form 5 control.
15. Calibrate KMET fault current to 1000 percent, (50 X 10
or 500 milliamperes).
16. Press the TRIP button on the display panel.
17. Press the CLOSE button on the display panel.
3. Adjust fault current to 200 percent or 200 mil-
liamperes.
18. Set KMET test set Fault Current switch S2 in the test
fault current position. Record timings from the KMET
test set for all trips on the G 10X ___ locations on the
test sheet.
4. Set KMET test set Fault Current Switch S2 to fault
position.
5. Control should trip two times to lockout, on all slow
19. Repeat steps 4 – 18 for Alternate Profiles 1, 2, and 3.
Note that the ground minimum trip for the Alternate
Profiles is 100 amps. The 200% fault will then be 200
milliamperes, the 500% fault will then be 500 mil-
liamperes, and the 1000% fault will then be 1000 mil-
liamperes or 1 amps.
TCCs, then indicate OPEN and lockout. Record value.
6. Deactivate Fast Trips Disabled (LED off).
7. Repeat steps 2 -4. Control should trip on two fast, two
slow TCCs. Record values.
Test Hot Line Tag
1. CLOSE the Form 5 control.
20. Return the Normal Profile Phase Minimum Trip Value
to the pretest value, 100 amps.
2. Activate HOT LINE TAG (LED on).
Test Non-Reclose
3. Adjust fault current to 200 percent or 200 mil-
1. Activate NON-RECLOSING (LED on).
2. Activate GROUND TRIP BLOCK (LED on).
3. Set KMET Phase Selector switch S5 to phase A.
liamperes.
4. Set KMET test set Fault Current Switch S2 to fault
position.
4. Set Form 5 control to Normal Profile (all Alternate Pro-
5. Control should trip out once on the 101 TCC curve,
file LEDs off).
then indicate open and lockout. Record value.
5. Adjust fault current to 200 percent or 200 mil-
6. Verify that it is not possible to close the Form 5 control.
7. Deactivate HOT LINE TAG (LED off).
liamperes.
6. Press the TRIP button on the display panel.
7. Press the CLOSE button on the display panel.
8. Verify that you can CLOSE the Form 5 control.
Test Reclose
8. Set KMET test set Fault Current Switch S2 to fault
position.
1. Set KMET selector switch S3 to Control Reclose
Reset.
9. Control should trip once, then indicate open and lock-
out. Record time value.
2. Reset the KMET Time Clock if required.
10. Disable NON-RECLOSE (LED off).
3. Adjust fault current to 200 percent or 200 mil-
liamperes.
11. Repeat steps 5 – 8, to lockout. Record time value.
4. Set KMET test set Fault Current Switch S2 to fault
Test Cold Load Pickup Blocked
1. Disable COLD LOAD PICKUP BLOCKED (LED off).
2. CLOSE the Form 5 control.
position.
5. After trip, turn fault switch S2 off.
6. Record reclose time.
3. Adjust fault current to 200 percent or 200 mil-
7. Repeat steps 2 – 6 until control locks out.
liamperes.
4. Within 30 seconds of Step 3, set KMET test set Fault
Current Switch S2 to fault position.
49
Download from Www.Somanuals.com. All Manuals Search And Download.
Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
Test Close Circuit Disable Fuse
This test is only applicable to Form 5 LS controls and stan-
dard Form 5 controls below Serial Number 3000.
Verify Instantaneous Demand
Metering
1. Enable GROUND TRIP BLOCK (LED on).
1. Set KMET Fault Switch S2 to OFF.
2. CLOSE the Form 5 control.
2. Set KMET switch S2 to OFF.
3. Set KMET Phase Selector S5 to A.
4. Set KMET Variac to zero.
3. Remove Close Circuit Disable fuse.
4. Adjust fault current to 200 percent or 200 mil-
5. Set KMET switch S4 to the 100 milliampere range.
6. CLOSE Form 5 control.
liamperes.
5. Set KMET test set Fault Current Switch S2 to fault
7. Set KMET switch S2 to ON.
position. The control will trip once.
8. Set KMET Variac to read 80 milliamperes.
9. Scroll the Form 5 LCD screen to screen 1.
6. Verify that it is not possible to close the Form 5 control.
7. Replace Close Circuit Disable fuse.
10. Verify Instantaneous metering on Phase A and
8. Verify it is now possible to CLOSE the Form 5 control.
Ground reads 80 milliamperes.
11. Set KMET Phase Selector S5 to B.
12. Verify Instantaneous metering on Phase B and
Ground reads 80 milliamperes.
13. Set KMET Phase Selector S5 to C.
14. Verify Instantaneous metering on Phase C and
Ground reads 80 milliamperes.
50
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S280-79-10
Form 5 Control Default Test Optimal Values
2.
Volts
MA
28.0
35
2.6 Volts
2.6 MA
28.0
550
Battery Circuitry
Volts
27.0
2.6 volts
24.2
3.
Normal Profile
Phase A Amps Phase B Amps
100.5 100.3
Phase A Amps Phase B Amps
200.9 200.2
Phase A Amps Phase B Amps
200.9 200.2
Phase A Amps Phase B Amps
Phase C Amps
100.7
Phase
Profile #1
Profile #2
Profile #3
Phase C Amps
200.5
Minimum Trip
Phase C Amps
200.5
Phase C Amps
200.5
200.9
200.2
50.1
4.
Normal
Ground Amps
Ground Amps
Ground Amps
Ground Amps
Ground
Minimum Trip
Profile #1
Profile #2
Profile #3
100.3
100.3
100.3
5.
Trip to Lockout Sequence
1st
2nd
3rd
1.416
0.278
0.088
1.443
0.273
4th
Phase Timing
Normal
Phase A 2X
0.161 0.164
0.018 0.017
0.016 0.014
0.153 0.154
0.015 0.014
1.421
0.280
0.086
1.441
0.275
0.087
1.441
0.275
0.087
1.441
0.275
0.087
Phase B 5X
Phase C 10X
Phase A 2X
Phase B 5X
Phase C 10X
Phase A 2X
Phase B 5X
Phase C 10X
Phase A 2X
Phase B 5X
Phase C 10X
Profile #1
Profile #2
Profile #3
0.011
0.009 0.087
0.153 0.154
0.015 0.014
1.443
0.273
0.011
0.009 0.087
0.153 0.154
0.015 0.014
1.443
0.273
0.011
0.009 0.087
51
Download from Www.Somanuals.com. All Manuals Search And Download.
Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
Form 5 Control Default Test Optimal Values
6.
Trip Sequence
Normal
1st
2nd
3rd
4th
Ground Timing
Ground 2X
Ground 5X
Ground 10X
Ground 2X
Ground 5X
Ground 10X
Ground 2X
Ground 5X
Ground 10X
Ground 2X
Ground 5X
Ground 10X
Phase 2X
0.214
0.212 3.894
3.896
1.099
0.012 0.016 1.097
0.008 0.014
0.652 0.653
0.212 3.894 3.896
Profile #1
Profile #2
Profile #3
0.214
0.012 0.016 0.952* 0.954*
0.008 0.014 0.280* 0.276*
0.214
0.212 3.984
3.896
0.012 0.016 0.952* 0.954*
0.008 0.014 0.280* 0.276*
0.214
0.212 3.894
3.896
0.012 0.016 0.952* 0.954*
0.008 0.014 0.280* 0.276*
0.153 lockout lockout lockout
7.
Enabled
Disabled
Block Off
Block On
Enabled
Non-Reclose
8. Cold Load
PickUp Blocked
9. Fast Trips
Phase 2X
0.152 0.153
1.420 1.433 lockout lockout
0.158 0.154 1.420 1.433
1.419 1.422 lockout lockout
0.155 0.156 1.418 1.424
0.014 lockout lockout lockout
1.420 1.433
Phase 2X
Phase 2X
Phase 2X
Phase 2X
Phase 2X
Disabled
No Reclose
Enabled
10.
Hot Line Tag
11.
0.155
0.156 1.148 1.424
2nd 3rd 4th
1.975 1.974 4.968 lockout
Reclose Sequence
Reclose Times
1st
Test Reclose
12.
Fuse Out
Can’t Close?
Yes
No
XXX
No
Close Circuit
Disable Fuse
Fuse In
Can Close?
Yes
XXX
13. Instantaneous
Demand Metering
Phase A
Phase B
Phase C
Amps 80
Amps 80
Amps 81
*Refer to the Test Ground Timing section of this manual.
52
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S280-79-10
Form 5 Control Default Test Sheet
Date:
Serial No:
2.
Volts
MA
2.6 Volts
2.6 MA
Battery Circuitry
Volts
2.6 volts
3.
Normal Profile
Phase A Amps Phase B Amps
Phase A Amps Phase B Amps
Phase A Amps Phase B Amps
Phase A Amps Phase B Amps
Phase C Amps
Phase C Amps
Phase C Amps
Phase C Amps
Phase
Profile #1
Profile #2
Profile #3
Minimum Trip
4.
Normal
Ground Amps
Ground Amps
Ground Amps
Ground Amps
Ground
Minimum Trip
Profile #1
Profile #2
Profile #3
5.
Trip to Lockout Sequence
1st
2nd
3rd
4th
Phase Timing
Normal
Phase A 2X
Phase B 5X
Phase C 10X
Profile #1
Phase A 2X
Phase B 5X
Phase C 10X
Phase A 2X
Phase B 5X
Phase C 10X
Phase A 2X
Phase B 5X
Phase C 10X
Profile #2
Profile #3
53
Download from Www.Somanuals.com. All Manuals Search And Download.
Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
Form 5 Control Default Test Sheet
6.
Trip Sequence
Normal
1st
2nd
3rd
4th
Ground Timing
Ground 2X
Ground 5X
Ground 10X
Profile #1
Ground 2X
Ground 5X
Ground 10X
Ground 2X
Ground 5X
Ground 10X
Ground 2X
Ground 5X
Ground 10X
Phase 2X
Profile #2
Profile #3
7.
Enabled
Disabled
Block Off
Block On
Enabled
lockout lockout lockout
lockout lockout
Non-Reclose
8. Cold Load
PickUp Blocked
9. Fast Trips
Phase 2X
Phase 2X
Phase 2X
Phase 2X
Phase 2X
Phase 2X
lockout lockout
Disabled
No Reclose
Enabled
10.
Hot Line Tag
11.
Reclose Sequence
Reclose Times
1st
Yes
Yes
2nd
No
3rd
4th
Test Reclose
12.
Fuse Out
Can’t Close?
Close Circuit
Disable Fuse
Fuse In
Can Close?
No
13.Instantaneous
Demand Metering
Phase A
Amps
Phase B
Amps
Phase C
Amps
54
Download from Www.Somanuals.com. All Manuals Search And Download.
!
SAFETY
FOR LIFE
S280-79-10
REMOVE THE CONTROL
FROM SERVICE
RETURN THE CONTROL TO
SERVICE
IMPORTANT: Disconnect switches for ac sensing
and power connections are necessary to isolate the
Form 5 Recloser Control for testing and servicing.
CAUTION: Equipment misoperation. Do not
!
connect this control to an energized recloser
until all control settings have been properly pro-
grammed and verified. Refer to the programming
information for this control. Failure to comply can
result in control and recloser misoperation, equip-
1. Enable GND TRIP BLOCKED to allow for ground trip
to be disabled when re-energized.
ment damage, and personal injury.
G110.3
A. Press the CHANGE/LAMP TEST key on the Oper-
ator Panel to enter the CHANGE mode.
Note: The LCD Display Screen will indicate the amount
of time available in CHANGE mode to make a
change.
After the required work is completed, disconnect the con-
trol from the test set and follow this procedure to return the
control to service:
B. Depress the GND TRIP BLOCKED key.
1. Plug in the control battery.
Note: After the GND TRIP BLOCKED key is
depressed, the red LED indicator will illuminate
to indicate GROUND TRIP BLOCKED is active.
2. Apply ac power to the control.
3. Verify that all control settings are correct.
4. Reconnect the control cable to the control.
5. Disable GND TRIP BLOCKED.
WARNING: Hazardous voltage. If the recloser
is energized while the control cable is discon-
nected, the CT secondaries can generate high volt-
ages. Contact with high voltage can cause severe
!
A. Press the CHANGE/LAMP TEST key on the Oper-
ator Panel to enter the CHANGE mode.
personal injury or death.
T204.2
Note: The LCD Display Screen will indicate the amount
of time available in CHANGE mode to make a
change.
2. Disconnect control cable from the control.
3. De-energize ac power from the control.
4. Unplug the control battery.
B. Depress the GND TRIP BLOCKED key.
Note: After the GND TRIP BLOCKED key is
depressed, the red LED indicator will not be illu-
minated indicating GROUND TRIP BLOCKED is
not active.
6. Reset the control clock after AC power has been re-
applied. Refer to Setting the Control Clock in Service
Information S280-79-2 Form 5 Microprocessor-Based
Recloser Control Programming Guide.
55
Download from Www.Somanuals.com. All Manuals Search And Download.
Kyle Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Control Installation and Operation Instructions
ADDITIONAL INFORMATION
Factory Maintenance Classes
CAUTION: This equipment requires routine
!
inspection and maintenance to ensure proper
The factory service department offers a basic testing and
troubleshooting course for the Form 5 Microprocessor-
Based Electronic Recloser Control and Reclosers. This
course, taught by experienced service technicians, is
held at the factory‘s in-house training facility. For addi-
tional information, contact your Cooper Power Systems
representative.
operation. If it is not maintained, it can fail to operate
properly. Improper operation can cause equipment
damage and possible personal injury.
G105.1
Replacement Kits
Replacement kits for the Kyle Form 5 Control are avail-
able through the factory Service Department. To order
these kits, refer to the Replacement Parts price list for cat-
alog numbers and pricing. Contact your Cooper Power
Systems representative for additional information and
ordering procedures.
Type MET Recloser Control Tester
A 30-minute video cassette program, KSPV7 Kyle Type
MET Electronic Recloser Control Tester Operation and
Testing Procedures is available as a supplemental train-
ing aid for service personnel.
®
Factory-Authorized Service
Centers
Factory-authorized service centers are located through-
out the continental United States to provide maintenance,
repair and testing services for Kyle controls and reclosers.
For further information, contact your Cooper Power Sys-
tems representative.
!
SAFETY
FOR LIFE
KA2048-476 Rev: 02
1045 Hickory Street
Pewaukee, WI 53072
©2005 Cooper Power Systems or its affiliates.
Kyle® is a registered trademark of Cooper Power Systems or its affiliates.
KDL
5/05
56
Download from Www.Somanuals.com. All Manuals Search And Download.
|