Chromalox
SERVICE REFERENCE
Installation
DIVISION
SALES
4
SECTION NWHO
(Supersedes PE437)
and
REFERENCE
PE437-1
RENEWAL PARTS IDENTIFICATION
161-303184-001
DATE
APRIL, 1999
Type NWHO(F)-27 Series Circulation Heater
(for Regular and Fuel Oil Heating)
Thermostat
(When Specified)
Specifications — Table A
Regular Oil Heaters
3 - 1-3/8" K.O.
Dimensions (In.)
B
for 1" Conduit
15-15/16"
Model
Volts
Phase
kW
W/In2
A
C
3" Pipe
Outlet (Std.)
NWHO-2780R15
NWHO-2790R15
NWHO-27100R15
NWHO-27120R15
240 or 480
240 or 480
240 or 480
240 or 480
3
3
3
3
80
90
100
120
20
20
20
20
77-9/16
81-9/16
87-9/16
97-9/16
52
56
62
72
48-1/2
52-1/2
58-1/2
68-1/2
2 Mtg. Lugs Ea
with Three 3/4" - 10
x1-1/8" Deep
Holes on 1-3/4"
Centers
A
C
B
Fuel Oil Heaters
A
NWHO-2750R15
NWHO-2760R15
NWHO-2770R15
240 or 480
240 or 480
240 or 480
3
3
3
50
60
70
12
12
12
77-9/16
87-9/16
97-9/16
52
62
72
48-1/2
58-1/2
68-1/2
A
3" Pipe
Inlet (Std.)
11"
3/4" NPT
Pipe Plug
Dimensions and ratings vary according to customer requirements.
Check engineering drawing for specifications.
F-Denotes heater is baffled, i.e., NWH0F
17-1/8"
GENERAL
Depending upon the specifications, the NWHO-27 may or may not be
factory equipped with AR or other Chromalox thermostats. Such ther-
mostats function to control outlet temperatures and limits internal tem-
perature under abnormal flow conditions. These controls do not fail-safe.
Thermocouples are also available as an option.
WARNING: This heater is not intended for use in haz-
ardous atmospheres where flammable vapors, gases,
liquids or other combustible atmospheres are present
as defined in the National Electrical Code. Failure to
comply can result in explosion or fire.
CAUTION: Users should install adequate back-up con-
trols and safety devices with their electric heating
equipment. Where the consequences of failure may be
severe, back-up controls are essential. Although the
safety of installation is the responsibility of the user,
Chromalox will be glad to make equipment recom-
mendations.
Hazardous area terminal enclosures are available, consult your
local Chromalox representative for details.
The NWHO-27 series is a general-purpose oil circulation heater
intended for use indoors.
The 27 or 36 steel sheathed tubular elements are welded to a remov-
able steel flange and centered in a 10 inch diameter steel heating chamber.
INSTALLATION
ing assembly on either of the lugs.
WARNING: Hazard of Shock. Disconnect all power
before installing heater.
5. DANGER: Hazard of Fire. Provide minimum of 6” spacing
from a chamber and related piping to nearest combustible materi-
al. Avoid operation of heater near combustible fluids or in com-
bustible vapor or gas laden atmosphere.
1. Vertical mounting (axis of chamber vertical as in sketch above) is
preferred. (Terminal housing at top of heater) (Figure A)
2. When mounting heater horizontally, inlet and outlet MUST be up.
In any other position, heater cannot be purged of air and elements
may be seriously damaged. (Figure B)
3. This series of circulation heaters are provided with mounting lugs
to support the heater chamber. Refer to sketch above for location
of these mounting lugs.
6. Provide adequate space at terminal end to permit withdrawal of the
heater from chamber should servicing be required.
7. If two or more heaters are needed to provide the needed heating
capacity, arrange them for series oil flow.
8. DANGER: Possible Explosion. A pressure relief valve
should be provided by customer at outlet of vessel. There should
be no other valving between vessel and valve.
4. Mount heaters to permit unrestrained expansion of chamber due to
temperature. This can be accomplished by using a slotted mount-
Correct
Incorrect
Correct
Incorrect
Figure A — Vertical Mounting
Figure B — Horizontal Mounting
© 2010 Chromalox, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
|