33CS
Commercial
Programmable Thermostat
Owner’s Manual
Part Number 33CS250-01
IMPORTANT: Read entire instructions before pro-
gramming the thermostat.
GENERAL
Carrier’s 7-day, commercial, programmable thermostats
are wall-mounted, low-voltage thermostats which maintain
room temperature by controlling the operation of an HVAC
(heating, cooling and ventilation) system. Separate heating
and cooling set points and auto-changeover capability allow
occupied and unoccupied programming schedules for en-
ergy savings.
All thermostats allow up to 3 occupied and one unoccu-
pied time/temperature setting to be programmed per
24-hour period. Each thermostat stores programs for 7 in-
dependent days. Batteries are not required. During power in-
terruption the internal NEVERLOST™ memory stores pro-
grams for an unlimited time.
Fig. 1 — Thermostat Display
Thermostat Front Panel Buttons — The thermo-
stat has buttons on the front cover which are used to raise or
lower the desired set point and override the current program.
See Fig. 2.
SET POINT BUTTONS — The UP ARROW and DOWN
ARROW buttons will raise or lower the current desired tem-
perature set point. If the thermostat is in AUTO mode, press-
ing the UPARROW or DOWN ARROW buttons will adjust
both the heating heating and cooling set points. Pressing the
UP ARROW or DOWN ARROW buttons in Cooling mode
will adjust only the cooling set points. Pressing the UPAR-
ROW or DOWN ARROW buttons in Heating mode will ad-
just only the heating set points. The UPARROW and DOWN
ARROW buttons are also used in programming mode.
OVERRIDE BUTTON — The Override button is used to
force the thermostat from Unoccupied mode into the Occu-
pied 1 mode comfort settings. The Override period will be
set at 30 minutes. The thermostat will then return to Unoc-
cupied mode. To increase the amount of time in Override
mode, press the Override button again. Thirty minutes of over-
ride time will be added for each time the Override button is
pressed up to a maximum of 4 hours. After the 4-hour limit
has been reached, press the Override button again to cancel
override mode.
IMPORTANT: The thermostat has a configurable se-
curity level. If certain functions are not available (chang-
ing set points, changing programming schedules), the
thermostat security level may be configured to ex-
clude those functions. Call the installer to reconfigure
the security level.
CONFIGURATION
Thermostat Display — The thermostat display is lo-
cated in the center of the thermostat. See Fig. 1. The fol-
lowing information can be displayed on the screen:
• mode (OFF, HEAT, COOL, AUTO, or PROGRAM ON)
• fan setting (FAN ON or blank)
• override indication
• room temperature
• desired temperature
• service filter indicator
• time of day
• day of the week
• schedule period (Occupied 1, 2, or 3; or Unoccupied)
• setup indicator (programming mode)
• lock indicator
While in Override mode, the Override icon and the Oc-
cupied 1 icon will be displayed on the thermostat. The time
of day and the minutes remaining in Override mode will al-
ternate on the thermostat display.
The set points are adjustable with the UP ARROW and
DOWN ARROW keys during Override mode.
• start/stop indicator (schedule period program mode)
Heat or Cool Indicator — A Heat or Cool indicator is
located on the bottom left cover of the thermostat. See
Fig. 2. The light will be red if the thermostat is in Heating
mode. The light will be green if the thermostat is in Cooling
mode.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 PC 111 Catalog No. 533-318 Printed in U.S.A. Form 33CS-4SO Pg 1 12-97 Replaces: New
Tab 11a 13a
4
Download from Www.Somanuals.com. All Manuals Search And Download.
PROGRAMMING MODE — To program the daily sched-
ules, perform the following procedure:
1. Enter programming mode by pressing the Program but-
ton. The Occupied 1 annunciator will appear on the ther-
mostat display. See Fig. 5. Use the UP ARROW and
DOWN ARROW buttons to set the maximum number
of Occupied periods available. The thermostat can be
set to 1, 2, or 3. After the number of Occupied periods
has been selected, press the Mode button.
2. The cooling set point for Occupied 1 will be displayed.
Use the UP ARROW and DOWN ARROW buttons to
raise or lower the cooling set point until the desired tem-
perature is shown. The range of acceptable values is 35
to 99 F (1 to 37 C). Press the Mode button to continue.
See Fig. 5.
3. The heating set point for Occupied 1 will be displayed.
Use the UP ARROW and DOWN ARROW buttons to
raise or lower the heating set point until the desired tem-
perature is shown. The range of acceptable values is 35
to 99 F (1 to 37 C). Press the Mode button to continue.
See Fig. 5.
Fig. 6 — Start Time Display
11. The Copy command can be used to copy the previous
day’s schedule if the schedules are the same. The copy
command becomes available after all the occupied pe-
riods are programmed in a day. Use the UP ARROW to
change the copy command to YES. Use the DOWNAR-
ROW to change the copy command to NO. Press the
Mode button when the choice has been made. See
Fig. 7.
If NO was selected, the schedule will automatically change
to the next day and the user must enter the occupied and
unoccupied schedules for that day.
NOTE: Occupied 1 schedule heating and cooling set points
are the same for each day. Occupied 2 and 3 set points
may be set to different values for each day of the week.
If YES was selected, the schedule will be copied to the
next day. The schedule copy may be repeated until Sun-
day is reached. The Sunday schedule cannot be copied
to Monday.
12. After all the times and set points for each day have been
entered, press the Program button to finish entering the
schedule.
NOTE: The thermostat will continue to follow the schedule
until a new one is entered.
• If only one occupied schedule is selected, the Occupied 2
and 3 schedules are skipped.
• If the start time is set later in the day than the stop time,
the program will run from midnight of that day to the stop
time and then from the start time to midnight.
Fig. 5 — Setting Occupied 1 Set Points
4. The cooling set point for Unoccupied will be displayed.
Use the UP ARROW and DOWN ARROW buttons to
raise or lower the cooling set point until the desired tem-
perature is shown. The range of acceptable values is 35
to 99 F (1 to 37 C) or ‘‘OF’’(no unoccupied cooling).
Press the Mode button to continue.
5. The heating set point for Unoccupied will be displayed.
Use the UP ARROW and DOWN ARROW buttons to
raise or lower the heating set point until the desired tem-
perature is shown. The range of acceptable values is 35
to 99 F (1 to 37 C) or ‘‘OF’’ (no unoccupied heating).
Press the Mode button to continue.
• If the same start and stop times are programmed for an
occupancy schedule, the thermostat will be in Occupied
mode for 24 hours.
• If one occupied period starts or stops within another oc-
cupied period, the lower numbered schedule has priority.
For example, if schedule Occupied 3 is running for 24 hours
and occupied schedule 2 comes on from 1 to 3 PM, the set
points from Occupied 2 are in effect from 1 to 3 PM.
6. The day of the week will be shown. Use the UP AR-
ROW and DOWN ARROW buttons to change the day
of the week until the desired starting day is shown. Pos-
sible choices are M (Monday) through S (Sunday). Press
the Mode button when the desired day is shown.
7. The Start Time for Occupied 1 will be displayed. Use
the UP ARROW and DOWN ARROW buttons to raise
or lower the time until the desired Start Time is shown.
Press the Mode button to continue. See Fig. 6.
8. The Stop Time for Occupied 1 will be displayed. Use
the UP ARROW and DOWN ARROW buttons to raise
or lower the time until the desired Stop Time is shown.
Press the Mode button.
OVERRIDING THE SCHEDULE — The schedule can be
overridden during operation by pressing the UP or DOWN
ARROW buttons to change the desired temperature. The ther-
mostat will use the new set point until the next scheduled
time period starts.
9. The On/Off icon will be displayed. Use the UP AR-
ROW to turn the Occupied 1 period ON for this day.
Use the DOWN ARROW to turn the Occupied 1 period
OFF for this day.
10. Repeat Steps 2 through 9 to program the remaining sched-
ule for occupied periods 2 and 3 (if selected in Step 1).
Fig. 7 — Copy Command Display
3
Download from Www.Somanuals.com. All Manuals Search And Download.
OPERATION
Electric Heat — When the Electric Heat option in the
advanced set up is set to ON (configured by installer), the
thermostat will turn on the fan immediately any time there
is a heat demand. This feature should only be used on elec-
tric heating applications. Do not use with gas heat.
The Mode button selects the operating mode of the ther-
mostat. If OFF is selected, the thermostat will not enter Heat-
ing or Cooling mode. If HEAT is selected, the thermostat
will only enter Heating mode (if the room temperature is
below the heating set point). If COOL is selected, the ther-
mostat will only enter Cooling mode (if the room tempera-
ture is above the cooling set point). If AUTO is selected, the
thermostat will enter Heating or Cooling mode based on the
room temperature and the heating and cooling set points. If
PROGRAM ON is selected, the stored schedule is enabled
and the thermostat will follow the Occupied and Unoccu-
pied schedules stored in its memory.
Holiday Mode — When the thermostat is in Holiday mode,
the thermostat will operate under Unoccupied set points. To
configure and activate the Holiday mode, press the Holiday
button. The ‘‘HOL’’ icon will be displayed along with the
remaining days of Holiday mode operation. Press the UP or
DOWN ARROWS to select the number of days that the holi-
day schedule will be in effect. A value of 0 disables Holiday
mode. The duration can be set from 1 to 99 days. The ther-
mostat will enter Holiday mode on midnight of the next day
after the mode has been activated. Holiday mode will re-
main in effect until midnight of the last configured day.
Auto-Changeover — When the thermostat mode is set
to AUTO, the thermostat will provide automatic changeover
from Heating to Cooling mode and Cooling to Heating mode
when required. The thermostat will automatically switch to
maintain the desired temperature setting. The thermostat does
not need to be manually changed from heating to cooling or
cooling to heating operation.
If the Holiday mode is in effect, the number of days re-
maining will blink on and off and the ‘‘Unoccupied’’ icon
will be displayed. The Override button will be active during
Holiday mode. The Dry Contact Switch is ignored.
To turn off the Holiday mode before the remaining con-
figured days have passed, press the Holiday button to enter
into the configuration mode. Press the DOWN ARROW to
set the number of days to zero. Holiday mode will be
disabled.
Two-Stage Operation — The second stage of heat or
cool is turned on when the first stage has been on for a mini-
mum of 2 minutes and the temperature differential from the
set point is equal to or greater than the set point plus the
deadband plus 2 degrees.
Dry Contact Switch — A dry contact switch is pro-
vided to allow an external device to force the thermostat into
Occupied 1. When the thermostat is forced into Occupied 1
via the dry contact closure, the Occupied 1 icon will blink
each second.
Clock Backup — In the event of a power loss, the ther-
mostat will keep time for a minimum of 48 hours without
external power or batteries.
Fan Operation — If Fan On is selected, the fan will run
continuously during occupied schedule (except when Mode
is switched to OFF). The fan will be off during unoccupied
schedule except during heating or cooling operation.
If Fan On is not selected, the fan will only operate during
heating or cooling operation.
SOFT START — When multiple thermostats are controlled
by the same external device, a Soft Start option can be used
to stagger the turn on times of the HVAC equipment. This
feature may cause a delay in operation after entering
Occupied 1.
Remote Temperature Sensor — A remote tempera-
ture sensor is available to read the temperature from a space.
If a remote temperature sensor is connected, the thermostat
will ignore the reading of its internal sensor. When the ther-
mostat is using a reading from a remote sensor, the degree
symbol above the temperature reading will blink.
Emergency Heat — Emergency heat is available for heat
pump applications. To turn on emergency heat, press and hold
the Fan button. While holding the Fan button, press the UP
button for 2 seconds. An ‘‘EH’’ will be displayed. During
emergency heat, the fan will operate and the second stage of
heat will be energized (locking out the first stage compres-
sor). To exit emergency heat, press and hold the Fan button.
While holding the Fan button, press the UP button for 2 sec-
onds. During emergency heat, only OFF and HEAT modes
are available.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 1 — Daily Schedule Planner
SCHEDULE
Occupied 2
DAY
OF THE
WEEK
Occupied 1
Occupied 3
Unoccupied
Start / Stop / Heat / Cool
Start / Stop / Heat / Cool
Start / Stop / Heat / Cool
Heat / Cool
Monday
Tuesday
Wednesday
Thursday
Friday
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
Saturday
Sunday
NOTE: The cooling temperature set point must be higher than the heating temperature set point.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Copyright 1997 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.