Carrier Oxygen Equipment 19XB User Manual

19XB  
Positive Pressure Storage System  
50/60 Hz  
Installation, Operating, and Maintenance  
Instructions  
For Use With Positive Pressure Chillers  
SAFETY CONSIDERATIONS  
Positive pressure storage systems are designed to pro-  
vide safe and reliable service when operated within de-  
sign specifications. When operating this equipment, use  
good judgment and safety precautions to avoid damage  
to equipment and property or injury to personnel.  
Be sure you understand and follow the procedures and  
safety precautions contained in this guide.  
with soap and water. If any enters the eyes, IMMEDIATELY FLUSH  
EYES with water and consult a physician.  
NEVER APPLY an open flame or live steam to a refrigerant cyl-  
inder. Dangerous overpressure can result. When necessary to heat  
refrigerant, use only warm (110 F [43 C]) water.  
DO NOT REUSE disposable (nonreturnable) cylinders or  
attempt to refill them. It is DANGEROUS AND ILLEGAL. When  
cylinder is emptied, evacuate remaining gas pressure, loosen  
the collar and unscrew and discard the valve stem. DO NOT  
INCINERATE.  
CHECK THE REFRIGERANT TYPE before transferring refrig-  
erant to the machine. The introduction of the wrong refrigerant can  
cause damage or malfunction to this machine.  
Operation of this equipment with refrigerants other than those  
cited herein should comply with ASHRAE 15 (latest edition). Con-  
tact Carrier for further information on use of this machine with other  
refrigerants.  
DO NOTATTEMPT TO REMOVE fittings, covers, etc., while ma-  
chine is under pressure or while machine is running. Be sure pres-  
sure is at 0 psig (0 kPa) before breaking any refrigerant  
connection.  
CAREFULLY INSPECT all relief devices, rupture discs, and other  
relief devices AT LEAST ONCE A YEAR. If machine operates in  
a corrosive atmosphere, inspect the devices at more frequent  
intervals.  
DO NOT VENT refrigerant relief valves within a building. Outlet  
from rupture disc or relief valve must be vented outdoors in ac-  
cordance with the latest edition of ASHRAE 15 (American Society  
of Heating, Refrigeration, and Air Conditioning Engineers). The  
accumulation of refrigerant in an enclosed space can displace oxy-  
gen and cause asphyxiation.  
PROVIDE adequate ventilation in accordance with ASHRAE 15,  
especially for enclosed and low overhead spaces. Inhalation of high  
concentrations of vapor is harmful and may cause heart irregulari-  
ties, unconsciousness, or death. Misuse can be fatal. Vapor is heavier  
than air and reduces the amount of oxygen available for breathing.  
Product causes eye and skin irritation. Decomposition products are  
hazardous.  
DO NOT USE OXYGEN to purge lines or to pressurize a machine  
for any purpose. Oxygen gas reacts violently with oil, grease, and  
other common substances.  
NEVER EXCEED specified test pressures, VERIFY the allowable  
test pressure by checking the instruction literature and the design  
pressures on the equipment nameplate.  
DO NOT USE air for leak testing. Use only tracer gases and dry  
nitrogen.  
DO NOT ATTEMPT TO REPAIR OR RECONDITION any relief  
device when corrosion or build-up of foreign material (rust, dirt,  
scale, etc.) is found within the valve body or mechanism. Replace  
the device.  
DO NOT install relief devices in series or backwards.  
DO NOT VALVE OFF any safety device.  
BE SURE that all pressure relief devices are properly installed and  
functioning before operating any machine.  
USE CARE when working near or in line with a compressed spring.  
Sudden release of the spring can cause it and objects in its path to  
act as projectiles.  
DO NOT STEP on refrigerant lines. Broken lines can whip about  
and cause personal injury and damage to the machine.  
DO NOT climb over a machine. Use platform, catwalk, or staging.  
Follow safe practices when using ladders.  
USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or  
move inspection covers or other heavy components. Even if com-  
ponents are light, use such equipment when there is a risk of slip-  
ping or losing your balance.  
BE AWARE that certain automatic start arrangements CAN EN-  
GAGE THE STARTER. Open the disconnect ahead of the starter  
in addition to shutting off the machine or pump.  
USE only repair or replacement parts that meet the code require-  
ments of the original equipment.  
DOUBLE-CHECK that coupling nut wrenches, dial indicators, or  
other items have been removed before rotating any shafts.  
DO NOT LOOSEN a packing gland nut before checking that the  
nut has a positive thread engagement.  
PERIODICALLY INSPECT all valves, fittings, and piping for cor-  
rosion, rust, leaks, or damage.  
DO NOT WELD OR FLAMECUT any refrigerant line or vessel  
until all refrigerant (liquid and vapor) has been removed from chiller.  
Traces of vapor should be displaced with dry air or nitrogen and  
the work area should be well ventilated. Refrigerant in contact with  
an open flame produces toxic gases.  
DO NOT USE eyebolts or eyebolt holes to rig machine sections or  
the entire assembly.  
DO NOT work on high-voltage equipment unless you are a quali-  
fied electrician.  
DO NOT WORK ON electrical components, including control pan-  
els, switches, starters, or oil heater until you are sure ALL POWER  
IS OFF and no residual voltage can leak from capacitors or solid-  
state components.  
LOCK OPENAND TAG electrical circuits during servicing. IF WORK  
IS INTERRUPTED, confirm that all circuits are deenergized be-  
fore resuming work.  
DO NOT syphon refrigerant by mouth.  
AVOID SPILLING liquid refrigerant on skin or getting it into the  
eyes. USE SAFETY GOGGLES. Wash any spills from the skin  
DO NOT MIX REFRIGERANT from chillers that use different com-  
pressor oils. Compressor damage can result.  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book 2  
PC 211  
Catalog No. 531-927  
Printed in U.S.A.  
Form 19XB-1SI  
Pg 1  
6-96  
Replaces: New  
Tab 5a  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 1 — Positive Pressure System Assembly Numbers  
POSITIVE PRESSURE  
SYSTEM ASSEMBLY  
NUMBER  
PUMPOUT UNIT  
ASSEMBLY NO.  
COMPRESSOR MOTOR  
(V-Ph-Hz)  
MAXIMUM  
RLA  
STORAGE  
TANK  
REFRIGERANT  
LRA  
19XB04280205  
19XB04280206  
19XB04280207  
19XB04280208  
19XB04280213  
19XB04280214  
19XB04280215  
19XB04280216  
19XB04280601  
19XB04280602  
19XB04280603  
19XB04280604  
19XB04280605  
19XB04280606  
19XB04280607  
19XB04280608  
19XB04520205  
19XB04520206  
19XB04520207  
19XB04520208  
19XB04520213  
19XB04520214  
19XB04520215  
19XB04520216  
19EA42-748  
19EA44-748  
19EA46-748  
19EA47-748  
19EA48-748  
19EA49-748  
19EA51-748  
19EA52-748  
19EA42-748  
19EA44-748  
19EA46-748  
19EA47-748  
19EA48-658  
19EA49-658  
19EA51-658  
19EA52-658  
19EA42-748  
19EA44-748  
19EA46-748  
19EA47-748  
19EA48-748  
19EA49-748  
19EA51-748  
19EA52-748  
R-22  
R-22  
208-3-60  
230-3-60  
13.2  
11.5  
5.8  
63.5  
57.5  
28.8  
23.0  
63.5  
57.5  
28.8  
23.0  
63.5  
57.5  
28.8  
23.0  
63.5  
57.5  
28.8  
23.0  
63.5  
57.5  
28.8  
23.0  
63.5  
57.5  
28.8  
23.0  
28 cu ft  
28 cu ft  
28 cu ft  
28 cu ft  
28 cu ft  
28 cu ft  
28 cu ft  
28 cu ft  
None  
R-22  
400/460-3-50/60  
575-3-60  
R-22  
4.6  
R-134a  
R-134a  
R-134a  
R-134a  
R-22  
208-3-60  
13.2  
11.5  
5.8  
230-3-60  
400/460-3-50/60  
575-3-60  
4.6  
208-3-60  
13.2  
11.5  
5.8  
R-22  
230-3-60  
None  
R-22  
400/460-3-50/60  
575-3-60  
None  
R-22  
4.6  
None  
R-134a  
R-134a  
R-134a  
R-134a  
R-22  
208-3-60  
13.2  
11.5  
5.8  
None  
230-3-60  
None  
400/460-3-50/60  
575-3-60  
None  
4.6  
None  
208-3-60  
13.2  
11.5  
5.8  
52 cu ft  
52 cu ft  
52 cu ft  
52 cu ft  
52 cu ft  
52 cu ft  
52 cu ft  
52 cu ft  
R-22  
230-3-60  
R-22  
400/460-3-50/60  
575-3-60  
R-22  
4.6  
R-134a  
R-134a  
R-134a  
R-134a  
208-3-60  
13.2  
11.5  
5.8  
230-3-60  
400/460-3-50/60  
575-3-60  
4.6  
LEGEND  
NOTES:  
1. All storage vessels are 300 psig (2068 kPa) designs per the ASME  
(American Society of Mechanical Engineers) Boiler Pressure  
Vessel Code, Section VIII Division 1.  
2. All units above are shipped with a 15 psig (103 kPa) nitrogen charge.  
3. Nominal horsepower for all pumpout units is 3.0.  
LRA  
RLA  
Locked Rotor Amps  
Rated Load Amps  
Mount the Pumpout Unit — The pumpout unit, if pur-  
chased separately, may be mounted directly on the chiller or  
it may be floor mounted.  
Rig the Storage Tank — The complete 19XB system  
can be rigged as a single assembly. See the rigging instruc-  
tions on the label attached to the assembly. Also refer to the  
rigging guide (Fig. 4), physical data in Tables 2 and 3, and  
contact surface and dimensions for the complete system in  
Fig. 5. Lift the assembly only from the 4 points indicated in  
the rigging guide. Each rigging cable must be capable of  
supporting the entire weight of the assembly.  
MOUNTING ON THE CHILLER — See instructions pro-  
vided with the chiller for mounting the pumpout unit. A typi-  
cal chiller mount is shown in Fig. 2.  
FLOOR MOUNTING — Select a ventilated and accessible  
area, free of traffic or other hazards. Remove and discard the  
4 angle supports at the base of the pumpout unit and bolt the  
unit to the floor through the 4716 in. holes at the base of the  
pumpout unit. Special isolation is unnecessary. Contact sur-  
face and dimensions for the pumpout unit are given in  
Fig. 3.  
Lifting the assembly from points other than those speci-  
fied may result in serious damage to the assembly and  
personal injury. Rigging equipment and procedures must  
be adequate for assembly. See Tables 2 and 3 for weights.  
NOTE: These weights are broken down into pumpout  
unit and storage tank weights. For the complete assem-  
bly weight, add all components together.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
VENT VALVE  
VALVES  
CONTROL BOX  
(WIRING BY  
CONTRACTOR)  
VALVES  
COMPRESSOR  
CONDENSER  
WATER  
CONNECTIONS  
(FIELD PIPING)  
REFRIGERANT  
INLET VALVE  
19EA PUMPOUT UNIT  
19EA CONTROL BOX (INTERIOR)  
19EA PUMPOUT UNITS  
Fig. 1 — 19XB Positive Pressure Storage System  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
*38-16 bolts × 1-in. lg; 4 required.  
Fig. 2 — 19EA Pumpout Unit: Typical Chiller Mount  
ELECTRICAL CONNECTION  
OPTION LIST  
TRADE SIZE  
QTY  
LOCATION  
1
2
؆
1
1
1
1
TOP  
3
4؆  
BOTTOM  
MIDDLE  
MIDDLE  
1؆  
114  
؆
Fig. 3 — Pumpout Unit Contact Surfaces and Dimensions  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTES:  
1. Each chain must be capable of supporting the entire weight of the  
machine.  
2. Minimum chain length:  
28 ft3 tank — 10Ј-0Љ  
52 ft3 tank — 15Ј-6Љ  
3. Total weight equals empty weight from chart and charge weight  
given on label.  
CENTER OF GRAVITY  
STORAGE  
TANK SIZE  
EMPTY WEIGHT  
LB (Kg)  
APPROX. DIM. — ft-in. (mm)  
A
B
4- 514  
1-778  
2380  
28 Ft3  
52 Ft3  
(1353)  
(505)  
(1080)  
6-1018  
(2086)  
1-834  
(527)  
3460  
(1569)  
Fig. 4 — Rigging Guide  
Table 2 — Physical Data  
19EA Pumpout Unit  
ENGLISH  
(SI)  
Pumpout Unit Weight*  
Pumpout Condenser Water Flow Rate  
lb (kg)  
gpm (L/s)  
210  
5 to 7  
(95)  
(.32 to .44)  
Pumpout Condenser Water Pressure Drop  
psig (kPa)  
6 to 10.7  
85  
(41.4 to 73.8)  
(29)  
Maximum Entering Condenser Water Temperature  
Maximum Leaving Condenser Water Temperature  
Condenser Relief Valve (Fusible Plug)  
F (C)  
F (C)  
100  
(37)  
psig (kPa)  
385  
(2655)  
Condenser Pressure Rating  
Refrigerant Side  
Waterside  
psig (kPa)  
psig (kPa)  
385  
150  
(2655)  
(1034)  
Compressor Rating 1750 rpm (29 r/s) Reciprocating  
Valves (4-Valve Manifold, Copper with  
Brass Turn Knob Valves)  
cfm (L/s)  
in. OD  
8.7  
(.25)  
1
1
2
2
*The pumpout unit weight includes the compressor/condenser, control box, and the oil separator.  
NOTES:  
1. The motor is hermetic with thermal protection.  
2. The control box is mounted and wired with a fuse on/off switch according to NEMA 1 (National  
Electrical Manufacturing Association).  
3. The starter contactor is located in the control box. The overloads on the motor are wired and the  
disconnect switch is supplied by the customer.  
4. The condenser tube is copper.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 3 — 19XB Storage Tank Rated Dry Weight and Refrigerant Capacity  
English  
MAXIMUM REFRIGERANT CAPACITY (lb)  
TANK OD  
(in.)  
DRY WEIGHT*  
(lb)  
SIZE CODE  
ASHRAE/ANSI 15  
UL 1963  
R-22  
R-134a  
1860  
R-22  
1704  
3264  
R-134a  
1716  
0428  
0452  
24.00  
27.25  
2380  
3460  
1842  
3527  
3563  
3286  
SI  
MAXIMUM REFRIGERANT CAPACITY (kg)  
ASHRAE/ANSI 15 UL 1963  
TANK OD  
(mm)  
DRY WEIGHT*  
(kg)  
SIZE CODE  
R-22  
836  
R-134a  
844  
R-22  
773  
R-134a  
778  
0428  
0452  
610  
592  
1080  
1569  
1600  
1616  
1481  
1491  
LEGEND  
ANSI  
American National Standards Institute  
American Society of Heating, Refrigeration,  
and Air Conditioning Engineers  
ASHRAE  
UL  
Underwriters’ Laboratories  
*The above dry weight includes the pumpout unit weight of 210 lbs (95 kg).  
1. If relief devices are manifolded, the cross-sectional area  
of the relief pipe must at least equal the sum of the areas  
required for individual relief pipes.  
2. Provide a pipe plug near outlet side of each relief device  
for leak testing. Provide pipe fittings that allow vent pip-  
ing to be disconnected periodically for inspection of valve  
mechanism.  
Make Piping Connections — Figure 6 represents typi-  
cal pumpout unit/chiller piping connections. Standard con-  
1
nections for 2-in. OD copper tubing are provided. Install  
the field-supplied FPT tee with pipe plug in the piping as  
shown in Fig. 6. This tee is used for refrigerant charging.  
NOTE: If any field piping runs exceed 50 ft in length, use  
7
8-in. OD copper tubing to minimize pressure drop.  
3. Piping to relief devices must not apply stress to the de-  
vice. Adequately support piping. A length of flexible tub-  
ing or piping near the device is essential on spring-  
isolated machines.  
4. Cover the outdoor vent with a rain cap and place a con-  
densation drain at the low point in the vent piping to pre-  
vent water build-up on the atmospheric side of the relief  
device.  
Pumpout unit water piping connections are shown in  
Fig. 6. Both connections are 12-in. NPT (female). A shutoff  
valve should be installed in the water line. Provide a means  
for blowing water from the condenser coil at winter shut-  
down to prevent freeze-up damage. Refer to the Job Data for  
water piping particulars.  
INSTALL VENT PIPING TO RELIEF DEVICES — The  
pumpout storage tank is factory-equipped with relief de-  
vices. Refer to Fig. 5 and Table 2 for size and location of the  
relief devices. Vent the relief devices to the outdoors in ac-  
cordance with ANSI/ASHRAE 15 Safety Code (latest edi-  
tion) for Mechanical Refrigeration and all other applicable  
codes. Relief devices are set to relieve at 300 psig  
(2068 kPa).  
Make Electrical Connections — See nameplate on  
compressor of pumpout unit and Table 1 for motor electrical  
data. Wire unit according to the diagram inside the control  
box.  
Fig. 7 is the wiring schematic for a complete system that  
includes the 19XB storage tank and the pumpout unit.  
Fig. 8 is the wiring schematic for the pumpout unit. Use this  
schematic for installations that do not include an auxiliary  
pumpout storage tank.  
Refrigerant discharged into confined spaces can dis-  
place oxygen and cause asphyxiation.  
NOTE: Use copper conductors only.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
DIMENSIONS  
ENGLISH (ft-in.)  
TANK  
SIZE  
A
B
C
D
E
F
G
H
J
K
L
M
N
P
R
S
T
0428 10- 5  
9-10  
4-9  
2-434 1-238 3-1316 4-11  
3-818 3- 8  
2-9716 3-2  
0-312 4-834 1-778 1-7516 3-734 5-014  
0452 14-1114 14- 412 5-078 2-812 1-414 3-4716 7- 214 4-0  
3-1178 3-1516 3-578 0-338 7-112 1-834 1-7916 3-8  
5-012  
SI (mm)  
TANK  
SIZE  
A
B
C
D
E
F
G
H
J
K
L
M
N
P
R
S
T
0428  
0452  
3175  
4553  
2997  
4382  
1448  
1546  
730  
826  
365  
413  
945  
1499  
2191  
1121  
1219  
1118  
1216  
849  
948  
965  
89  
86  
1442  
2172  
505  
528  
491  
497  
1111  
1118  
1530  
1537  
1027  
1064  
NOTES:  
1.  
Denotes center of gravity.  
2. Dimensions in ( ) are in millimeters.  
3. The weights and center of gravity values given are for an empty storage  
tank.  
4. For additional information on the pumpout unit, see certified drawings.  
5. The available conduit knockout sizes are:  
TRADE  
SIZE  
QTY  
LOCATION  
1
2
؆
1
1
1
1
top  
3
4؆  
bottom  
middle  
middle  
1؆  
114  
؆
Fig. 5 — PPS Contact Surface and Dimensions  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
CHILLERS WITHOUT ISOLATION VALVES  
CHILLERS WITH ISOLATION VALVES  
(WITH OR WITHOUT PUMPOUT STORAGE TANKS)  
LEGEND  
GENERAL PIPING CONNECTION SIZES  
Factory-Supplied Tubing  
CONNECTION  
SIZE (in.)  
Field-Supplied Tubing  
1
1
3
Refrigerant Transfer Connections  
Condenser Water Cooling Connectors  
Safety Relief Head Pumpdown Condenser  
2
2
8
ODS (female)  
NPT (female)  
Flare (male)  
Field-Supplied Tubing (Multiple Chillers)  
Service Valve (Factory Supplied)  
Service Valve (Field Supplied)  
ODS  
Outside Diameter, Sweat  
NOTES:  
1. The field-supplied tubing is to be 12-in. OD tubing (min.) and must  
be arranged and supported to avoid stresses on the equipment,  
transmission of vibrations, and interference with routine access  
during the reading, adjusting, and servicing of the equipment. If  
the distance from the chiller to the pumpout unit is over 50 ft, then  
7
8-in. OD tubing (min.) must be used. Provisions should be made  
for adjustment in each plane of the tubing and for both periodic  
and major servicing of the equipment. Special care must be taken  
so that the safety head does not experience tubing strain. Vent  
the safety head per ASHRAE 15 (American Society of Heating,  
Refrigeration, and Air Conditioning Engineers), latest revision.  
2. The tubing and valve from the storage tank to the pumpout com-  
pressor is factory supplied when the unit is factory mounted.  
Fig. 6 — Typical Pumpout Unit/Chiller Connection Schematic  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4 — Relief Devices  
REQUIRED FACTOR  
STORAGE  
TANK SIZE  
RELIEF VALVE  
OUTLET SIZE  
QUANTITY  
lb air  
min  
Kg air  
min  
1 in. NPT  
28  
52  
2
2
31.4  
52.3  
14.2  
23.7  
Female Connector  
1 in. NPT  
Female Connector  
LEGEND  
Ground  
Field Wiring  
Factory Wiring  
Contactor Term.  
Overload Term.  
Pumpdown Term.  
Pumpdown Comp’r.  
Term.  
Fig. 7 — 19XB Pumpout System Wiring Schematic  
LEGEND  
C
Contactor  
Fu  
HP  
L
Fuse, 3 Amps  
Compressor Terminal  
High-Pressure Cutout  
Compressor Motor Voltage Line (3-phase)  
Low-Line Control Voltage (single-phase)  
Compressor Overload  
Contactor Terminal  
Overload Terminal  
Pumpout Unit Terminal  
LL  
OL  
T’stat  
Internal Thermostat  
*Bimetal thermal protector imbedded in motor winding.  
Fig. 8 — Pumpout Unit Wiring Schematic  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LEVEL GAGE — Liquid level gage (magnetically coupled  
dial type) with electronic shut-off at 90% liquid capacity.  
CONTROLS AND COMPONENTS  
Figure 1 shows the major components of the PPS system.  
Pumpout Unit — The pumpout unit consists of a spring-  
mounted direct motor-driven reciprocating compressor, a water-  
cooled refrigerant condenser, an oil separator, suction and  
discharge valves to control refrigerant flow, and prewired safety  
and control devices. The pumpout unit comes equipped with  
a 4-way transfer valve manifold to interconnect both liquid  
and vapor transfer and to pressurize the chiller during trans-  
fer of refrigerant from chiller to storage tank.  
During transfer of refrigerant into and out of the pump-  
out storage tank, carefully monitor the storage tank level  
gage. Do not fill the tank more than 90% of capacity to  
allow for refrigerant expansion. Overfilling may result  
in damage to the tank and personal injury. For maxi-  
mum refrigerant capacity, refer to Table 2.  
CONTROLS — The pumpout unit has the following con-  
trols: an on/off switch, a 3-amp fuse, compressor overloads,  
an internal thermostat, a compressor contactor, and a refrig-  
erant high pressure cutout.  
OPERATION  
Overview — Transferring refrigerant from one vessel to  
another is accomplished by using either gravity or pressure  
differential. A difference in elevation between 2 vessels re-  
sults in a gravity flow of liquid; a difference in pressure forces  
the liquid from one vessel to the other. The latter method  
requires lowering the pressure in one vessel. If there is liq-  
uid in that vessel, its temperature must be lowered, and the  
pressure in the other vessel must be simultaneously  
increased.  
Under most circumstances, creating the pressure differ-  
ential is not a difficult process. Some applications, such as  
ice storage, outdoor installations, or installations with high  
temperature differentials between the storage tank and the  
chiller may require additional consideration. In some in-  
stances, it may be necessary to add auxiliary heat to one of  
the vessels or to insulate the storage tank at job sites where  
high ambient temperature or sun load make it difficult to re-  
duce the temperature and pressure in the tank. Outdoor in-  
stallations must have a roof or cover over the storage tank to  
ensure that the pressure in the tank does not exceed the chiller  
relief pressure setting.  
SAFETY CONTROL SETTINGS — The pumpout unit high-  
pressure switch (Fig. 1) is set to open at the settings listed  
in Table 5. The switch setting is checked by operating the  
pumpout condenser and slowly throttling the pumpout con-  
denser water.  
Table 5 — High Condition Pressure Switch Settings  
English  
HIGH-PRESSURE SWITCH  
REFRIGERANT  
Cutout  
CutIn  
+ 0  
R-134a  
R-22  
161 ± 5 psig  
130 − 5 psig  
+ 0  
185 − 5 psig  
220 ± 5 psig  
SI  
HIGH-PRESSURE SWITCH  
REFRIGERANT  
Cutout  
Cut-In  
+ 0  
R-134a  
R-22  
1110 ± 34 kPa  
896 − 34 kPa  
REFRIGERANT TRANSFER — When refrigerant is being  
evacuated from the chiller cooler or condenser vessels, any  
liquid refrigerant left in a vessel will flash off, lowering the  
temperature in that vessel enough to freeze the fluid (usually  
water) flowing through the cooler or condenser tubes. This  
event, called tube freeze-up, can cause extensive damage to  
the chiller; therefore, all liquid refrigerant must be removed  
from a vessel before evacuation of refrigerant vapor is started.  
If all the liquid cannot be removed, then the cooler water  
and condenser water pumps must be operated throughout the  
process of evacuating refrigerant vapor to keep fluid moving  
through the cooler and condenser tubes.  
+ 0  
1517 ± 34 kPa  
1276 − 34 kPa  
NOTES:  
1. R-22 units use high-pressure cutout switch HK01UA181.  
2. R-134a units use high-pressure cutout switch HK01UA187.  
COMPRESSOR — The pumpout compressor assembly has  
a positive displacement of 1750 rpm (29 r/s) and 8.7 cfm  
(0.004 m3/s). It comes equipped with thermal protection on  
the motor and an in-line oil separator.  
CONDENSER — The water-cooled condenser is fully ASME  
constructed. During transfer, it condenses refrigerant vapor  
to liquid. The condenser transfer tank safety relief valves com-  
ply with ASHRAE 15 standards.  
TRANSFERRING LIQUID REFRIGERANT FROM THE  
CHILLER COOLER TO THE CHILLER CONDENSER OR  
PUMPOUT STORAGE TANK — Chiller and pumpout unit  
valves are set to permit the pumpout compressor to dis-  
charge refrigerant vapor into the cooler vessel, lowering pres-  
sure in the condenser vessel/storage tank. The pressure dif-  
ferential forces liquid from the cooler vessel into the condenser  
vessel/storage tank. After all the liquid is transferred, the re-  
frigerant vapor remaining in the cooler vessel can be drawn  
off by reducing pressure in the chiller and discharging the  
vapor through the pumpout unit condenser into the con-  
denser vessel/storage tank.  
OIL SEPARATOR — The pumpout unit includes an in-line  
oil separator to remove oil that becomes mixed with refrig-  
erant and returns the oil to the compressor.  
SUCTION AND DISCHARGE VALVES — The pumpout  
unit comes with a 4-way transfer valve manifold to inter-  
connect both liquid and vapor transfer and to pressurize the  
chiller during transfer of refrigerant from chiller to storage  
tank or from one chiller vessel to another.  
Storage Tank — The storage tank is rated for positive  
pressure refrigerants under ASME Section VIII pressure ves-  
sel codes with a minimum of 300 psig (2068 kPa) rating.  
The tank components include:  
TRANSFERRING LIQUID REFRIGERANT FROM THE  
CHILLER CONDENSER OR PUMPOUT STORAGE TANK  
TO THE CHILLER COOLER — Chiller and pumpout unit  
valves are set to increase pressure in the chiller condenser  
vessel/storage tank and to reduce pressure in the cooler ves-  
sel. Pressure in the cooler vessel is lowered to correspond to  
a saturated refrigerant liquid temperature 2 F (1.1 C) above  
the freezing temperature of the liquid circulating through the  
chiller cooler/condenser tubes (34 F [1.1 C] for water). The  
valves are set so that the pressure in the cooler vessel is lower  
than that of the condenser vessel/storage tank, forcing the  
liquid into the cooler vessel.  
DRAIN VALVE — Located at its lowest point of drain with  
a minimum of 1 in. NPT.  
DUAL RELIEF VALVES — Two relief valves and a 3-way  
shut-off valve.  
PRESSURE GAGE — A 30 in.-0-400 psig (101-0-2760 kPa)  
compound pressure gage.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE: During this operation, maintain water circulation  
through the chiller cooler and condenser vessels to prevent  
tube freeze-up.  
VENT VALVE 8  
OIL RETURN  
LINE  
CONNECTION  
DISTILLING THE REFRIGERANT — Refrigerant vapor  
is transferred from the chiller cooler vessel or pumpout stor-  
age tank through the pumpout condenser, condensed to a liq-  
uid, and pumped to the chiller condenser vessel. During this  
operation, water circulation must be maintained in the pump-  
out condenser. Refrigerant impurities left in the chiller cooler  
vessel or storage tank are then drained off. This operation  
can take from 4 to 14 hours, depending on the type and amount  
of refrigerant being distilled.  
The Pumpout and Refrigerant Transfer Procedures sec-  
tion gives step-by-step instructions on performing these  
operations.  
PUMPOUT  
CONTROL BOX  
(WIRING BY  
CONTRACTOR)  
Pumpout and Refrigerant Transfer Procedures  
Three possibilities are available:  
1. If there are no isolation valves on the chiller, a complete  
pumpout system with a pumpout storage tank and pump-  
out unit is needed.  
CONDENSER  
WATER  
CONNECTIONS  
REFRIGERANT  
INLET VALVE  
Fig. 9 — Pumpout Unit  
2. Whether or not isolation valves are available on the chiller,  
the refrigerant can be pumped to and isolated in a pump-  
out storage tank by using the pumpout unit.  
3. If isolation valves are available on the chiller, the refrig-  
erant can be pumped to either the cooler vessel or the  
condenser vessel using the pumpout unit.  
The following procedures describe how to transfer refrig-  
erant from one vessel to another and how to evacuate the  
chiller.  
2. Attach a 30 in.-0-400 psi (101-0-2760 kPa) gage to the  
storage tank to determine its pressure.  
POSITIVE PRESSURE CHILLERS WITH STORAGE  
TANKS — In the Valve/Condition tables that accompany  
these instructions, the letter ЉCЉ indicates a closed valve.  
Figures 9 and 10 show the locations of the valves.  
Always run chiller cooler and condenser water pumps  
and always charge or transfer refrigerant as a gas when  
chiller vessel pressure is less than 60 psig (414 kPa)  
[30 psig (207 kPa)]. Below these pressures, liquid re-  
frigerant flashes into gas, resulting in extremely low tem-  
peratures in the cooler/condenser tubes and possibly causing  
tube freeze-up.  
Do not mix refrigerants from chillers that use different  
compressor oils. Compressor damage can result. For ex-  
ample, the compressor oil in a 23XL chiller that uses  
HCFC-22 refrigerant can cause severe lubrication prob-  
lems in a 19XL chiller that uses HCFC-22 refrigerant.  
OPERATING THE PUMPOUT UNIT  
Transfer Refrigerant from Pumpout Storage Tank to Chiller:  
1. Be sure that the suction and the discharge service valves  
on the pumpout compressor (Fig. 9) are open (back-  
seated) during operation. Rotate the valve stem fully coun-  
terclockwise to open. Frontseating the valve closes the  
refrigerant line and opens the gage port to compressor  
pressure.  
During transfer of refrigerant into and out of the 19XB  
storage tank, carefully monitor the storage tank level gage.  
Do not fill the tank more than 90% of capacity to allow  
for refrigerant expansion. Overfilling may result in dam-  
age to the tank and personal injury.  
2. Make sure that the pumpout compressor holddown bolts  
(Fig. 2) have been loosened to allow free spring travel.  
1. Equalize refrigerant pressure.  
Transfer, addition, or removal of refrigerant in spring-  
isolated chillers may place severe stress on external pip-  
ing if springs on the chiller have not been blocked in  
both up and down directions.  
a. Turn on chiller water pumps and monitor chiller  
pressures.  
b. Close pumpout and storage tank valves 2, 4, 5, 8, and  
10, and close refrigerant charging valve 7; open chiller  
isolation valve 11 and any other chiller isolation valves,  
if present.  
3. Open the refrigerant inlet valve (Fig. 9) on the pumpout  
compressor.  
c. Open pumpout and storage tank valves 3 and 6; open  
chiller valves 1a and 1b.  
4. Oil should be visible in the pumpout compressor sight  
glass under all operating conditions and during shut-  
down. If oil is low, add oil as described in the Mainte-  
nance section.  
VALVE  
1a 1b  
2
3
4
5
6
7
8
10 11  
C
CONDITION  
C
C
C
C
C
TO READ REFRIGERANT PRESSURES — During pump-  
out or leak testing:  
1. Refer to the display on the chiller control center to de-  
termine refrigerant-side pressures and low (soft) vacuum.  
Use a quality vacuum indicator or manometer to measure  
evacuation and dehydration and to ensure the desired range  
and accuracy.  
d. Gradually crack open valve 5 to increase chiller pres-  
sure to 60 psig (414 kPa), [ 30 psig (207 kPa)]. Slowly  
feed refrigerant to prevent freeze-up.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 10 — Valve Locations for 19XB Pumpout Unit With 19XB Storage Tank  
e. Open valve 5 fully after the chiller pressure rises above k. Close valves 1a, 1b, 2, 5, and 6.  
the freezing point of the refrigerant. Let the storage  
tank and chiller pressure equalize. Open refrigerant charg-  
ing valve 7 and storage tank charging valve 10 to let  
liquid refrigerant drain into the chiller.  
VALVE  
1a 1b  
2
3
4
5
6
7
8
10 11  
C
CONDITION  
C
C
C
C
C
C
C
C
C
l. Turn off pumpout condenser water.  
VALVE  
1a 1b  
2
3
4
5
6
7
8
10 11  
Transfer the Refrigerant from Chiller to Pumpout Storage  
Tank.  
CONDITION  
C
C
C
2. Transfer remaining refrigerant.  
a. Close valve 5 and open valve 4.  
1. Equalize refrigerant pressure.  
a. Valve positions:  
VALVE  
1a 1b  
2
3
4
5
6
7
8
10 11  
CONDITION  
C
C
C
VALVE  
1a 1b  
2
3
4
5
6
7
8
10 11  
C
CONDITION  
C
C
C
C
C
b. Turn off the pumpout condenser water, and turn on the  
pumpout compressor to push liquid refrigerant out of  
the storage tank. Monitor the storage tank level until  
the tank is empty.  
b. Slowly open valve 5 and refrigerant charging valves 7  
and 10 to allow liquid refrigerant to drain by gravity  
into the storage tank.  
c. Close refrigerant charging valves 7 and 10.  
d. Turn off the pumpout compressor.  
e. Turn off the chiller water pumps.  
f. Close valves 3 and 4.  
VALVE  
1a 1b  
2
3
4
5
6
7
8
10 11  
CONDITION  
C
C
C
2. Transfer the remaining liquid.  
a. Turn off pumpout condenser water. Place valves in the  
following positions:  
g. Open valves 2 and 5.  
VALVE  
1a 1b  
2
3
4
5
6
7
8
10 11  
C
VALVE  
1a 1b  
2
3
4
5
6
7
8
10 11  
CONDITION  
C
C
C
C
CONDITION  
C
C
C
h. Turn on pumpout condenser water.  
b. Run the pumpout compressor for approximately 30 min-  
utes, then close valve 7 and 10.  
i. Run the pumpout compressor until the storage tank pres-  
sure reaches 5 psig (34 kPa), 18 in. Hg (41 kPa  
absolute).  
VALVE  
1a 1b  
2
3
4
5
6
7
8
10 11  
C
CONDITION  
C
C
C
C
j. Turn off the pumpout compressor.  
c. Turn off the pumpout compressor.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Remove any remaining refrigerant.  
a. Turn on chiller water pumps.  
Transfer All Refrigerant to Chiller Condenser Vessel:  
1. Push refrigerant into chiller condenser vessel.  
b. Turn on pumpout condenser water.  
c. Place valves in the following positions:  
a. Turn on the chiller water pumps and monitor the chiller  
pressure.  
b. Valve positions:  
VALVE  
1a 1b  
2
3
4
5
6
7
8
10 11  
C
VALVE  
1a  
1b  
2
3
4
5
8
11  
CONDITION  
C
C
C
C
CONDITION  
C
C
C
d. Run the pumpout compressor until the chiller pres-  
sure reaches 60 psig (414 kPa), [30 psig (207 kPa)];  
then, shut off the pumpout compressor. Warm chiller  
condenser water will boil off any entrapped liquid re-  
frigerant and chiller pressure will rise.  
c. Equalize the refrigerant in the chiller cooler and  
condenser.  
d. Turn off chiller water pumps and pumpout condenser  
water supply.  
e. When chiller pressure rises to 70 psig (483 kPa),  
[40 psig (276 kPa)]; turn on the pumpout compressor  
until the pressure again reaches 60 psig (414 kPa)  
[30 psig (207 kPa)]; then, turn off the pumpout com-  
pressor. Repeat this process until the chiller pressure  
no longer rises; then, turn on the pumpout compressor  
and pump out until the chiller pressure reaches  
18 in. Hg (41 kPa absolute).  
e. Turn on pumpout compressor to push liquid out of the  
chiller cooler vessel.  
f. When all liquid has been pushed into the chiller con-  
denser vessel, close the cooler refrigerant isolation valve  
(11).  
g. Turn on the chiller water pumps.  
h. Turn off the pumpout compressor.  
f. Close valves 1a, 1b, 3, 4, and 6.  
2. Evacuate gas from chiller cooler vessel.  
a. Close pumpout valves 2 and 5; open valves 3 and 4.  
VALVE  
1a 1b  
2
3
4
5
6
7
8
10 11  
C
CONDITION  
C
C
C
C
C
C
C
C
C
VALVE  
1a  
1b  
2
3
4
5
8
11  
C
CONDITION  
C
C
C
g. Turn off the pumpout condenser water.  
4. Establish vacuum for service. To conserve refrigerant, op-  
erate the pumpout compressor as described in Step 3e un-  
til the chiller pressure is reduced to 18 in. Hg (41 kPa  
absolute).  
b. Turn on pumpout condenser water.  
c. Run pumpout compressor until the chiller cooler ves-  
sel pressure reaches 18 in. Hg vac (41 kPa absolute).  
Monitor pressures on the chiller control panel and on  
refrigerant gages.  
CHILLERS WITH ISOLATION VALVES — The valves re-  
ferred to in the following instructions are shown in Fig. 9  
and 11. Valve 7 remains closed.  
Fig. 11 — Valve Locations for 19XB Pumpout Unit Without Storage Tank  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
d. Close valve 1a.  
6. Open valve 5 fully.  
e. Turn off pumpout compressor.  
f. Close valves 1b, 3, and 4.  
VALVE  
1a  
1b  
2
3
4
5
8
11  
C
CONDITION  
C
C
C
VALVE  
1a  
C
1b  
C
2
3
4
5
8
11  
C
7. Close valves 1a, 1b, 3, and 5.  
8. Open chiller isolation valve 11 and any other isolation  
valves, if present.  
CONDITION  
C
C
C
C
C
g. Turn off pumpout condenser water.  
h. Turn off chiller water pumps and lock out chiller  
compressor.  
VALVE  
1a  
C
1b  
C
2
3
4
5
8
11  
CONDITION  
C
C
C
C
C
Transfer All Refrigerant to Chiller Cooler Vessel:  
1. Push refrigerant into the chiller cooler vessel.  
9. Turn off chiller water pumps.  
DISTILLING THE REFRIGERANT  
1. Transfer the refrigerant from the chiller to the pumpout  
storage tank as described in the Transfer the Refrigerant  
from Chiller to Pumpout Storage Tank section.  
a. Turn on the chiller water pumps and monitor the chiller  
pressure.  
b. Valve positions:  
VALVE  
1a  
1b  
2
3
4
5
8
11  
2. Equalize the refrigerant pressure.  
CONDITION  
C
C
C
a. Turn on chiller water pumps and monitor chiller  
pressures.  
b. Close pumpout and storage tank valves 2, 4, 5, 8, and  
10, and close chiller charging valve 7; open chiller iso-  
lation valve 11 and any other chiller isolation valves,  
if present.  
c. Equalize the refrigerant in the chiller cooler and  
condenser.  
d. Turn off chiller water pumps and pumpout condenser  
water.  
e. Turn on pumpout compressor to push refrigerant out  
of the chiller condenser.  
f. When all liquid is out of the chiller condenser, close  
valve 11 and any other liquid isolation valves on the  
chiller.  
c. Open pumpout and storage tank valves 3 and 6; open  
chiller valves 1a and 1b.  
VALVE  
1a 1b  
2
3
4
5
6
7
8
10 11  
C
CONDITION  
C
C
C
C
C
g. Turn off the pumpout compressor.  
2. Evacuate gas from chiller condenser vessel.  
a. Turn on chiller water pumps.  
d. Gradually crack open valve 5 to increase chiller pres-  
sure to 60 psig (414 kPa), [30 psig (207 kPa)]. Slowly  
feed refrigerant to prevent freeze-up.  
e. Open valve 5 fully after the chiller pressure rises above  
the freezing point of the refrigerant. Let the storage  
tank and chiller pressure equalize.  
b. Make sure that pumpout valves 3 and 4 are closed and  
valves 2 and 5 are open.  
VALVE  
1a  
1b  
2
3
4
5
8
11  
C
CONDITION  
C
C
C
3. Transfer remaining refrigerant.  
a. Close valve 3.  
c. Turn on pumpout condenser water.  
b. Open valve 2.  
d. Run the pumpout compressor until the chiller con-  
denser reaches 18 in. Hg (41 kPa absolute). Monitor  
pressure at the chiller control panel and refrigerant gages.  
VALVE  
1a 1b  
2
3
4
5
6
7
8
10 11  
C
CONDITION  
C
C
C
C
e. Close valve 1b.  
f. Turn off pumpout compressor.  
g. Close valves 1a, 2, and 5.  
c. Turn on pumpout condenser water.  
d. Run the pumpout compressor until the storage tank  
pressure reaches 5 psig (34 kPa), 18 in. Hg (41 kPa  
absolute).  
e. Turn off the pumpout compressor.  
f. Close valves 1a, 1b, 2, 5, and 6.  
g. Turn off pumpout condenser water.  
VALVE  
1a  
C
1b  
C
2
3
4
5
8
11  
C
CONDITION  
C
C
C
C
C
h. Turn off pumpout condenser water.  
i. Turn off chiller water pumps and lock out chiller com-  
pressor.  
VALVE  
1a 1b  
2
3
4
5
6
7
8
10 11  
C
CONDITION  
C
C
C
C
C
C
C
C
C
Return Refrigerant to Normal Operating Conditions  
1. Be sure that the chiller vessel that was opened has been  
evacuated.  
2. Turn on chiller water pumps.  
3. Open valves 1a, 1b, and 3.  
4. Drain the contaminants from the bottom of the storage  
tank into a container. Dispose of contaminants safely.  
MAINTENANCE  
Periodic maintenance is necessary to keep all components  
functioning as designed. A maintenance log is recom-  
mended to ensure a proper maintenance schedule is  
followed.  
VALVE  
1a  
1b  
2
3
4
5
8
11  
C
CONDITION  
C
C
C
C
4. Crack open valve 5, gradually increasing pressure in the  
evacuated chiller vessel to 60 psig (414 kPa), [30 psig  
(207 kPa)]. Feed refrigerant slowly to prevent tube  
freeze-up.  
Pumpout Unit — For maintenance details, refer to the  
06D, 07D Installation, Start-Up, and Service Instructions.  
5. Leak test to ensure chiller vessel integrity.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PUMPOUT COMPRESSOR OIL CHARGE — Use oil con-  
forming to Carrier specifications for reciprocating compres-  
sor use. Oil requirements are listed in Table 6.  
4. Stop the pumpout compressor and isolate the pumpout  
system by closing the discharge service valve.  
5. Slowly remove the oil return line connection (Fig. 9). Add  
oil as required.  
6. Replace the connections and reopen the pumpout com-  
pressor service valves.  
Table 6 — Pumpout Compressor Oil Requirements  
CARRIER  
SPECIFICATION  
NO.  
ISO  
VISCOSITY  
CARRIER  
PART NO.  
REFRIGERANT  
Storage Tank — To prevent moisture and contami-  
nants from entering the storage tank, maintain positive pres-  
sure in the tank when not transferring refrigerant. Leak test  
the storage tank according to your normal vessel leak test  
procedures and schedule.  
R-22  
86  
68  
PP49-7  
PP23BZ101  
PP23BZ103  
R-134a  
PP47-31  
The total oil charge, 4.5 pints (2.6 L), consists of 3.5 pints  
(2.0 L) for the compressor and one additional pint (0.6 L)  
for the oil separator.  
Oil should be visible in one of the pumpout compressor  
sight glasses both during operation and at shutdown. Always  
check the oil level before operating the pumpout compres-  
sor. Before adding or changing oil, relieve the refrigerant  
pressure as follows:  
Ordering Replacement Parts — The following in-  
formation must accompany an order for Carrier-specified parts:  
• machine model number and serial number  
• name, quantity, and part number of the part required  
• delivery address and method of shipment  
1. Attach a pressure gage to the gage port of either pumpout  
compressor service valve (Fig. 10).  
TROUBLESHOOTING  
2. Close the suction service valve and open the discharge  
line to the pumpout storage tank or the chiller.  
3. Operate the compressor until the crankcase pressure drops  
to 2 psig (13 kPa).  
Information on troubleshooting for the PPS is included in  
Table 7.  
Table 7 — Troubleshooting  
SYMPTOM  
PROBABLE CAUSE  
Main power line open  
REMEDY  
Replace fuse or reset circuit breaker.  
Check connections.  
Compressor does not run  
Loose terminal connection  
Improperly wired controls  
Low line voltage  
Check wiring and rewire.  
Check line voltage; determine location of voltage drop.  
Compressor motor defective  
Check motor winding for open or short. Replace compressor if  
necessary.  
Seized compressor  
Replace compressor.  
High level gage alarm  
High-pressure control erratic in action  
Discharge valve partially closed.  
Air in system  
Check refrigerant level and remove excess.  
Check capillary tube for pinches. Set control as required..  
Open valve.  
Compressor cycles on  
high-pressure control  
Purge system.  
Condenser scaled.  
Clean condenser.  
Condenser water pump or fans not operat- Start pump or fans.  
ing.  
Unit operates too long  
System Noises  
Isolation valves partially open  
Piping vibrations  
Close valves.  
Support piping as required. Check for loose pipe connectors.  
Compressor noisy  
Check valve plates for valve noise. Replace compressor (worn  
bearings). Check for loose compressor holddown bolts.  
Insufficient compressor oil  
Leak in system  
Add oil.  
Compressor Loses Oil  
Locate and repair leak.  
Repair or replace valve.  
Plugged or stuck compressor oil return  
check valve  
Dirty accumulator  
Clean accumulator.  
Copyright 1996 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book 2  
PC 211  
Catalog No. 531-927  
Printed in U.S.A.  
Form 19XB-1SI  
Pg 16  
6-96  
Replaces: New  
Tab 5a  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Black Decker Blower 387739 User Manual
Bolens Lawn Mower 117 074 000 User Manual
Bosch Appliances Smoke Alarm DS9400Ms User Manual
Bosch Power Tools Laser Level GPL3T User Manual
Braun Electric Shaver EP 50 User Manual
Brother Printer PT 1760 User Manual
Campbell Hausfeld Staple Gun CHN10310 User Manual
Canon Camera Lens EF80 User Manual
C Crane Humidifier EE 5201A User Manual
Chauvet Welding System DERBY X User Manual