Bosch Appliances Smoke Alarm DS9400Ms User Manual

Fire Alarm Systems | DS9400M AddressiFire Fire Alarm Control Panel  
DS9400M AddressiFire Fire Alarm Control  
Panel  
Digital Fire Alarm Control Panel  
Provided with four conventional on-board inputs,  
expandable to eight  
Up to 247 Addressable Multiplex Points  
Supports two-wire and four-wire conventional type  
detectors  
Two NACs  
Two On-Board Auxiliary Relays  
Internal 24 V, 4 A power supply  
Supports four remote LCD Keypads  
On-board programming via front panel  
Expandable to 255 points  
Initiating circuits  
The DS9400M AddressiFire 255 is a microprocessor-based  
Fire Alarm Control Panel. This four conventional point panel  
can expand to 255 input points. It supports up to twenty  
two-wire detectors per on-board conventional point, or any  
number of four-wire detectors (depending on available  
power). Two Notification Appliance Circuits (NACs) provide  
up to 4 A of 24 V power to operate horns, strobes, bells and  
other notification appliances. The DS9431 Multiplex  
Expansion Module (pre-installed) enhances the DS9400M’s  
conventional system features by adding addressable point  
capability, increasing the number of relay outputs and  
allowing for more system users.  
All on-board conventional input points will work with two-  
wire or four-wire smoke detectors. Twenty detectors (two-  
wire) maximum per zone.  
Multiplex expansion technology  
The DS9431 Multiplex Expansion Module (pre-installed)  
enhances the DS9400M conventional system features by  
expanding the base system to 255 total points, increasing  
the number of relay outputs to 58 and adding an additional  
400 events to the history buffer for a total of 500 non-  
volatile events. The DS9431 also allows for up to 100  
system users on the DS9400M.  
Built-In and remote alpha keypad support  
The keypad built in to the control panel and the DS9447  
remote LCD keypad are alphanumeric keypads that provide  
a two-line, 16‑character (per line) LCD display. Text is freely  
programmable for zone descriptions. Up to four DS9447  
remote LCD keypads are allowed per system.  
Functions  
Easy user interface  
Nine labeled function keys allow the user to easily silence  
bells, sirens, reset smoke detectors, or view history events.  
Menu driven keypad programming allows for customizing of  
the control panel.  
Personal ID Numbers (PINs)  
The system supports up to 100 Personal ID Numbers (PINs),  
which are four digits in length. The PINs may contain any  
combination of digits. PINs may be programmed with four  
different levels of authority. These PINs may be restricted  
to silencing, resetting, disabling, and/or programming the  
system.  
Keypad programmable  
The system is completely keypad programmable, thus  
eliminating the need for an expensive hand-held  
programmer.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Belkin Switch F1D201 User Manual
Belson Hair Dryer PR1045 User Manual
Billy Goat Blower F601HS User Manual
Blodgett Range B36 XX User Manual
Bushnell Hunting Equipment 20 1925 User Manual
Campbell Hausfeld Staple Gun CHN10600 User Manual
Canon Printer BJC 50 User Manual
Carrier Air Conditioner 38AE012 User Manual
Century Car Seat ISPB009BA User Manual
Chicago Electric Welder 98759 User Manual