Carrier Humidifier HUMCCLFP1025 A User Manual

Humidifiers and  
Humidistat  
Installation, Start-Up, and Operating Instructions  
MODEL HUMCCLFP1025-A--  
FAN-POWERED  
HUMIDIFIER  
MODEL HUMCCSFP1016-A--  
FAN-POWERED  
MODEL HUMCCLBP2018-A--  
BYPASS HUMIDIFIER  
HUMIDIFIER  
MODEL HUMCCWTR2019-A--  
WATER-SAVER  
MODEL HUMCCSBP2017-A--  
BYPASS HUMIDIFIER  
A98362  
Humidifiers  
NOTE: Read the entire instruction in manual applicable to  
specific unit before starting the installation.  
Before installing or servicing system, always turn off main  
power to system. There may be more than 1 disconnect  
switch. Turn off accessory heater power if applicable. Elec-  
trical shock can cause personal injury or death.  
This symbol indicates a change since the last issue.  
SAFETY CONSIDERATIONS  
Improper installation, adjustment, alteration, service, maintenance,  
or use can cause explosion, fire, electrical shock, or other  
conditions which may cause personal injury or property damage.  
Consult a qualified installer, service agency, distributor, or branch  
for information or assistance. The qualified installer or agency  
must use factory-authorized kits or accessories when modifying  
this product. Refer to the individual instructions packaged with the  
kits or accessories when installing.  
Unit must not be installed where freezing temperatures could  
occur. Do not install unit on the furnace or fan coil jacket. Do  
not install unit where ends of cooling coil could restrict  
airflow to the humidifier. Condensation damage could occur  
if home has closed-off, unheated rooms.  
Follow all safety codes. Wear safety glasses and work gloves. Use  
quenching cloth for brazing operations. Have fire extinguisher  
available. Read these instructions thoroughly and follow all  
warnings or cautions attached to the unit. Consult local building  
codes and National Electrical Code (NEC) for special require-  
ments.  
INSTALLATION OF HUMCCLBP2018-A--  
BYPASS HUMIDIFIER  
Carrier’s HUMCCLBP2018-A-- bypass humidifier can be in-  
stalled on either the supply or return plenum of a forced-air system.  
This unit requires an external bypass duct between the supply- and  
return-air ductwork.  
Recognize safety information. This is the safety-alert symbol  
When you see this symbol on the unit and in instructions or  
manuals, be alert to the potential for personal injury.  
.
It is recommended to install the humidifier where it can be easily  
serviced. If this humidifier is installed with a central cooling  
system the bypass duct must have a shutoff damper to close during  
the cooling season. Always install humidifier downstream of an  
electronic air cleaner.  
Understand the signal words DANGER, WARNING, and CAU-  
TION. These words are used with the safety-alert symbol. DAN-  
GER identifies the most serious hazards which will result in severe  
personal injury or death. WARNING signifies hazards which  
could result in personal injury or death. CAUTION is used to  
identify unsafe practices which would result in minor personal  
injury or product and property damage.  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book  
Tab 7a 9a  
1
4
PC 101  
Catalog No. 03HU-MC1  
Printed in U.S.A.  
Form HUM-1SI  
Pg 1  
7-98  
Replaces: 49-4SI  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Inform homeowner of proper operation, maintenance, and  
humidistat setting.  
HUMIDIFIER  
HUMIDISTAT  
BROWN  
24VAC  
FURNACE  
BROWN  
a. If unit is installed during cooling season, close bypass  
damper, set humidistat for summer setting (OFF or lowest  
setting).  
b. If installed during heating season, set unit for normal  
operation.  
TRANSFORMER  
INSTALLATION OF HUMCCLFP1025-A--  
FAN POWERED HUMIDIFIER  
(FIELD SUPPLIED)  
HUMIDISTAT  
HUMIDIFIER  
RED  
BLU  
115V  
FIELD  
WIRING  
24V  
Carrier’s HUMCCLFP1025-A-- fan powered humidifier can only  
be installed on the supply plenum of a forced-air system. This unit  
requires an external 115-vac (fused) plug-in receptacle near the  
equipment for proper operation.  
It is recommended to install the humidifier where it can be easily  
serviced. Pad access can be easily obtained from either the top or  
bottom of unit. Always install humidifier downstream of an  
electronic air cleaner.  
A98365  
Fig. 4—Installation of Humidistat  
on Bypass-Type Humidifier  
Step 1—Inspect Package and Check Equipment  
Step 7—Make Water Connection  
Inspect the contents of packaged humidifier. File claim with  
shipping company prior to installation if shipment is damaged or  
incomplete.  
If garden hose is not used for water supply:  
1. Mount saddle valve on water line according to instructions  
supplied with valve.  
The package should contain:  
2. Run 1/4-in. diameter (water line grade) tubing from saddle  
valve to adapter on solenoid valve and tighten compression  
fittings.  
1. Humidifier and media assembly  
2. Humidistat  
3. Template  
IMPORTANT: If water pressure is higher than normal (60 psi),  
use noise suppression disk included in parts bag. (Read water noise  
reducer note located inside package for instructions.) For normal  
operation, saddle valve need only be opened 1 full turn to meet  
performance requirements.  
4. Owner’s Manual  
5. Warranty Certificate  
6. Solenoid valve  
7. Saddle valve assembly with adapter  
8. Four sheet metal screws  
9. Foam tape  
3. Open valve and check installation for leaks.  
NOTE: Saddle valve is self piercing on copper lines; 1/4-in. hole  
must be drilled in steel or iron pipes. Use only a grounded drill or  
a hand drill to avoid shock hazard. Turn off water and drain the  
pipe prior to drilling 1/4-in. hole.  
10. Water noise reducer (use for water pressure over 60 psi)  
11. Worm clamp for field-supplied drain tube  
12. Humidifier maintenance instruction sticker  
13. Carrier logo label  
Step 8—Install Humidistat and Complete Wiring  
1. Mount humidistat on inside wall, or return-air duct in accor-  
dance with section INSTALLATION OF HUMIDISTAT on  
page 10.  
RED  
2. Wire brown low voltage leads to furnace control board, or  
install a field-supplied step-down transformer 115vac/24vac  
60Hz to power solenoid valve. (See Fig. 4.) Make sure bridge  
rectifier is attached to coil of solenoid valve.  
"N" COIL  
BLUE  
NOTE: Wiring must comply with National Electrical Code and  
any local codes or ordinances that may apply.  
Step 9—Start-Up  
1. Open saddle valve to permit water flow to the solenoid.  
2. Check all connections for water leaks.  
3. Set thermostat to call for heat. Set humidistat for highest  
humidity setting making sure contacts are closed. After a few  
minutes of operation, check the drain connection for leaks and  
to see if water is flowing through humidifier.  
VERTICAL  
HORIZONTAL  
A98366  
4. Reverse thermostat and humidistat settings to insure proper  
shutdown.  
Fig. 5—Installation of HUMCCLFP1025-A--  
Fan-Type Humidifier  
5. Reset thermostat to normal setting. Reset humidistat to rec-  
ommended setting.  
Step 2—Select Location (See Fig. 5.)  
Step 10—Final Steps  
Humidifier must be installed on supply plenum only. If furnace has  
air conditioning coil, be sure humidifier does not interfere with coil  
ends.  
Attach humidifier maintenance instruction sticker to a visible  
location.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Remember to provide clearance for maintenance and evaporator  
pad removal. To access pad remove top or bottom cover to expose  
assembly (turn knob counter-clockwise).  
HUMIDIFIER  
HUMIDISTAT  
RED  
BLU  
24VAC  
FURNACE  
Step 3—Prepare Plenum Opening (See Fig. 2.)  
1. Use template for marking humidifier opening.  
115V FIELD WIRING  
FAN TYPE UNITS ONLY  
2. Tape in place on plenum making sure template is level.  
IMPORTANT: For humidifier to operate properly it must be level  
and mounted on a vertical surface.  
TRANSFORMER  
(FIELD SUPPLIED)  
HUMIDISTAT  
HUMIDIFIER  
3. Drill four 1/8-in. holes in plenum.  
RED  
BLU  
115V  
FIELD  
WIRING  
24V  
4. Cut opening in plenum using heavy solid lines on template as  
a guide.  
Step 4—Mount the Humidifier (See Fig. 3.)  
115V FIELD WIRING  
FAN TYPE UNITS ONLY  
1. Attach foam tape on inside of mounting flange.  
2. Hook bottom notch of humidifier on opening cut in plenum.  
A96010  
3. Push top of humidifier to plenum aligning screw holes with  
flange.  
Fig. 6—Installation of Humidistat  
on Fan-Type Humidifier  
4. Align, level, and secure using top screws first.  
5. Insert bottom screws and tighten all screws for air tight seal.  
Step 5—Install Drain Line  
3. Set thermostat to call for heat. Set humidistat for highest  
humidity setting making sure contacts are closed. After a few  
minutes of operation, check the drain connection for leaks and  
to see if water is flowing through humidifier.  
1. Use 1/2- or 5/8-in. vinyl tubing (field supplied) to connect  
drain on bottom of humidifier housing to an open drain.  
4. Reverse thermostat and humidistat settings to insure proper  
shutdown.  
2. Use supplied worm drain clamp to hold drain tubing in  
position over drain fitting outlet.  
5. Reset thermostat to normal setting. Reset humidistat to rec-  
ommended setting.  
Step 9—Final Steps  
Unit may leak if drain tubing is misapplied. Do not insert  
tubing inside of drain fitting outlet.  
Attach humidifier maintenance instruction sticker to a visible  
location.  
3. Make sure line is free of traps due to sagging and has  
sufficient pitch to drain.  
1. Inform homeowner of proper operation, maintenance, and  
humidistat setting.  
Step 6—Make Water Connection  
a. If unit is installed during cooling season set humidistat for  
summer setting (OFF or lowest setting).  
If garden hose is not used for water supply:  
b. If installed during heating season, set unit for normal  
operation.  
1. Mount saddle valve on water line according to instructions  
supplied with saddle valve.  
2. Run 1/4-in. diameter (water line grade) tubing from saddle  
valve to adapter on solenoid valve and tighten compression  
fittings.  
INSTALLATION OF HUMCCSFP1016-A--  
FAN POWERED HUMIDIFIER  
Carrier’s HUMCCSFP1016-A-- fan powered humidifier can only  
be installed on the supply plenum of a forced-air system. This unit  
requires an external 115-vac (fused) plug-in receptacle near the  
equipment for proper operation.  
IMPORTANT: If water pressure is higher than normal (60 psi),  
use noise suppression disk included in parts bag. (Read water noise  
reducer note located inside package for instructions). For normal  
operation, saddle valve need only be opened 1 full turn to meet  
performance requirements.  
It is recommended to install the humidifier where it can be easily  
serviced. Pad access door can be easily converted from right to the  
left hand side. Always install humidifier downstream of an  
electronic air cleaner.  
3. Open valve and check installation for leaks.  
NOTE: Saddle valve is self piercing on copper lines; 1/4-in. hole  
must be drilled in steel or iron pipes. Use only a grounded drill or  
a hand drill to avoid shock hazard. Turn off water and drain the  
pipe prior to drilling 1/4-in. hole.  
Step 1—Inspect Package and Check Equipment  
Inspect contents of packaged humidifier. File claim with shipping  
company prior to installation, if shipment is damaged or incom-  
plete.  
Step 7—Install Humidistat and Complete Wiring  
The package should contain:  
1. Humidifier and media assembly  
2. Humidistat  
1. Mount humidistat on inside wall, or return-air duct in accor-  
dance with section INSTALLATION OF HUMIDISTAT on  
page 10.  
2. Wire red and blue low voltage. (See Fig. 6.)  
3. Template  
3. Plug power cord in to 115-vac 60Hz source.  
NOTE: Wiring must comply with National Electrical Code and  
any local codes or ordinances that may apply.  
4. Owner’s Manual  
5. Warranty Certificate  
6. Solenoid valve  
Step 8—Start-Up  
1. Open saddle valve to permit water flow to the solenoid.  
2. Check all connections for water leaks.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
7. Saddle valve assembly with adapter  
8. Four sheet metal screws  
9. Foam tape  
10. Noise suppressor (use for water pressure over 60 psi)  
11. Worm clamp for field-supplied drain tube  
12. Humidifier maintenance instruction sticker  
13. Carrier logo label  
"N" COIL  
HORIZONTAL  
A96049  
Fig. 8—Reversing Door Access  
on HUMCCSFP1016-A--  
VERTICAL  
HORIZONTAL  
MEDIA PAD  
ASSEMBLY  
A97098  
Fig. 7—Installation of HUMCCSFP1016-A--  
Fan-Type Humidifier  
DRAIN  
OUTLET  
HOUSING  
ENCLOSURE  
VINYL DRAIN  
TUBING  
Step 2— Select Location (See Fig. 7.)  
Humidifier must be installed on supply plenum only. If furnace has  
air conditioning coil, be sure humidifier does not interfere with coil  
ends. Remember to provide clearance for maintenance and evapo-  
rator pad removal.  
DRAIN OUTLET  
A97108  
Fig. 9—Media Pad Assembly Installation  
To reverse pad access from right to the left side:  
IMPORTANT: For humidifier to operate properly it must be level  
and mounted on a vertical surface.  
1. Remove side door and media pad assembly.  
2. Remove 4 screws and separate top assembly from lower  
mounting base. (See Fig. 8.)  
3. Drill four 1/8-in. holes in plenum.  
4. Cut opening in plenum using heavy solid lines on template as  
a guide.  
3. Rotate lower mounting base 180 degrees, so side access door  
is now on left.  
Step 4—Mount the Humidifier  
4. Snap together top assembly to mounting base and reinstall  
screws.  
1. Attach foam tape to back of mounting flange (exclude the  
off-set edge).  
5. Replace media pad assembly (with distributor reservoir up)  
and side access door.  
2. Hook off-set edge over opening cut in plenum.  
3. Place humidifier in plenum aligning screw holes with flange.  
4. Align, level, and tighten all screws for air tight seal.  
Step 5—Install Drain Line  
When re-installing media pad assembly into plastic housing,  
insure the assembly drain stub aligns into the drain outlet  
located in bottom of humidifier. Unit can leak if drain stub  
does not align with drain outlet. (See Fig. 9.)  
1. Use 5/8-in. vinyl tubing (field supplied) to connect drain on  
bottom of humidifier housing to an open drain.  
2. Use clamp to hold drain tubing in position over drain fitting  
outlet.  
IMPORTANT: Make sure front housing assembly with electrical  
cord is facing down.  
Unit may leak if drain tubing is misapplied. Do not insert  
tubing inside of drain fitting outlet.  
Step 3—Prepare Plenum Opening (See Fig. 2.)  
1. Use template for marking humidifier opening.  
3. Make sure line is free of traps due to sagging and has  
sufficient pitch to drain.  
2. Tape in place on plenum making sure template is level.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOLENOID  
VALVE  
TUBING  
ENCLOSURE  
INLET HOLE  
INLET HOLE  
SEAT  
SOLENOID  
VALVE  
HOUSING  
ENCLOSURE  
FLUSH  
AGAINST  
INLET  
POSITION TUBING  
INSIDE INLET HOLE  
(CUT LENGTH  
IF REQUIRED)  
A97107  
Fig. 10—Top Mounting of Water Solenoid Valve  
Step 6—Mount Solenoid Valve  
The water solenoid valve should be mounted on top of humidifier  
enclosure.  
1. To mount solenoid on top, see Fig. 10.  
a. Firmly press valve into the top inlet hole on enclosure. Seat  
valve flush against inlet hole.  
A97099  
Fig. 11—Alternate Mounting of Solenoid Valve  
on HUMCCSFP1016-A-- Humidifier  
2. If alternate mounting of solenoid is required, see Fig. 11.  
a. To mount solenoid on side, use 3/8-in. ID, 1/2-in. OD vinyl  
tubing (field supplied). Place tubing onto valve stem and  
secure with clamp.  
Step 9—Start-Up  
1. Open saddle valve to permit water flow to the solenoid.  
2. Check all connections for water leaks.  
b. Mount valve upside down securing to side of housing.  
c. Place open end of tubing into the top inlet hole.  
IMPORTANT: Be careful not to kink tubing.  
Step 7—Make Water Connection  
3. Set thermostat to call for heat. Set humidistat for highest  
humidity setting making sure contacts are closed. After a few  
minutes of operation, check the drain connection for leaks and  
to see if water is flowing through humidifier.  
If garden hose is not used for water supply:  
4. Reverse thermostat and humidistat settings to insure proper  
shutdown.  
1. Mount saddle valve on water line according to instructions  
supplied with valve.  
5. Reset thermostat to normal setting. Reset humidistat to rec-  
ommended setting.  
2. Run 1/4-in. diameter (water line grade) tubing from saddle  
valve to adapter on solenoid valve and tighten compression  
fittings.  
Step 10—Final Steps  
Attach humidifier maintenance instruction sticker to a visible  
location.  
IMPORTANT: If water pressure is higher than normal (60 psi),  
use noise suppression disk included in parts bag. (Read water noise  
reducer note located inside package for instructions). For normal  
operation, saddle valve need only be opened 1 full turn to meet  
performance requirements.  
1. Inform homeowner of proper operation, maintenance, and  
humidistat setting.  
a. If unit is installed during cooling season set humidistat for  
summer setting (OFF or lowest setting).  
3. Open valve and check installation for leaks.  
NOTE: Saddle valve is self piercing on copper lines; 1/4-in. hole  
must be drilled in steel or iron pipes. Use only a grounded drill or  
a hand drill to avoid shock hazard. Turn off water and drain the  
pipe prior to drilling 1/4-in. hole.  
b. If installed during heating season, set unit for normal  
operation.  
INSTALLATION OF HUMCCSBP2017-A--  
BYPASS HUMIDIFIER  
Carrier’s HUMCCSBP2017-A-- bypass humidifier can be in-  
stalled on either the supply or return plenum of a forced air system.  
This unit requires an external bypass duct between the supply- and  
return-air ductwork.  
Step 8—Install Humidistat and Complete Wiring  
1. Mount humidistat on inside wall, or return-air duct in accor-  
dance with section INSTALLATION OF HUMIDISTAT on  
page 10.  
It is recommended to install the humidifier where it can be easily  
serviced. If this humidifier is installed with a central cooling  
system the bypass duct must have a shutoff damper to close during  
the cooling season. Always install humidifier downstream of an  
electronic air cleaner.  
2. Wire red and blue low-voltage leads. (See Fig. 6.)  
3. Plug power cord in to 115-vac 60Hz source.  
NOTE: Wiring must comply with National Electrical Code and  
any local codes or ordinances that may apply.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 1—Inspect Package and Check Equipment  
Step 3—Prepare Plenum Opening (See Fig. 2.)  
1. Use template for marking humidifier opening.  
Inspect the contents of packaged humidifier. File claim with  
shipping company prior to installation if shipment is damaged or  
incomplete.  
2. Tape in place on plenum making sure template is level.  
IMPORTANT: For humidifier to operate properly it must be level  
and mounted on a vertical surface.  
The package should contain:  
1. Humidifier and media assembly  
2. Humidistat  
3. Drill four 1/8-in. holes in plenum.  
SOLENOID  
VALVE  
ASSEMBLY  
BROWN  
3. Template  
4. 6-in. damper  
5. Owner’s Manual  
6. Warranty Certificate  
7. Solenoid valve with bridge rectifier  
8. Transfer tube  
9. Saddle valve assembly with adapter  
10. Three pair of miscellaneous screws  
11. Six sheet metal screws  
12. Foam tape  
13. Water noise reducer (use for water pressure over 60 psi)  
14. Worm clamp for field-supplied drain tube  
15. Humidifier maintenance instruction sticker  
16. Carrier logo label  
PAD  
ACCESS  
DOOR  
BYPASS UNITS  
A98368  
Fig. 13—Mounting Solenoid Valve  
on HUMCCSBP2017-A-- Humidifier  
"N" COIL  
4. Cut opening in plenum using heavy solid lines on template as  
a guide.  
ACCESS  
DOOR  
Step 4—Mount Humidifier  
1. Attach foam tape on inside of mounting flange.  
2. Determine discharge direction.  
DRILL (2) HOLES  
IN DUCT  
FOR #8 SHEETMETAL  
SCREWS  
3. If right-hand discharge is required:  
a. Remove side door and media pad assembly.  
b. Invert unit 180 degrees.  
c. Re-install media pad and door.  
IMPORTANT: Always ensure pad assembly is in the upright  
position.  
4. Attach solenoid valve to unit housing using two screws in  
upper mounting holes. (See Fig. 13.) Do not over tighten  
screws.  
HORIZONTAL  
VERTICAL  
5. Attach transfer tube to solenoid valve and insert free end into  
inlet fitting on top of unit housing.  
A98367  
Fig. 12—Installation of  
HUMCCSBP2017-A--  
Bypass-Type Humidifier  
6. Attach bridge rectifier to solenoid valve.  
7. Insert sheet metal screws into lower holes in plenum, pre-  
drilled using template.  
8. Tighten screws until heads protrude approximately 3/16-in.  
Step 2—Select Location (See Fig. 12.)  
9. Hang humidifier on bottom screws and push top of humidifier  
to plenum, aligning top screw holes with flange, and insert  
screws.  
Humidifier may be installed on either supply or return plenum. If  
furnace has air conditioning coil, be sure unit does not interfere  
with coil ends. Remember to provide clearance for maintenance  
and evaporator pad removal.  
10. Align and level unit.  
11. Tighten all screws for air tight seal.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 5—Install Bypass Duct  
to see if water is flowing through humidifier.  
Attach field-supplied 6-in. diameter duct, elbow, or starting collar  
with field-supplied 1/4-in. zip screws. Install supplied 6-in. damper  
in 6-in. duct connector.  
4. Reverse thermostat and humidistat settings to insure proper  
shutdown.  
5. Reset thermostat to normal setting. Reset humidistat to rec-  
ommended setting.  
IMPORTANT: On systems with central cooling, the damper  
should be closed during cooling season to prevent bypass air.  
Step 10—Final Steps  
Attach humidifier maintenance instruction sticker to a visible  
location.  
Do not support weight of bypass duct from humidifier —  
damage could result.  
1. Inform homeowner of proper operation, maintenance, and  
humidistat setting.  
Step 6—Install Drain Line  
a. If unit is installed during cooling season, close bypass  
damper, set humidistat for summer setting (OFF or lowest  
setting).  
1. Use 5/8-in. ID vinyl tubing (field supplied) to connect drain on  
bottom of humidifier housing to an open drain.  
2. Use worm clamp to hold drain tubing in position over drain  
b. If installed during heating season, set unit for normal  
operation.  
fitting outlet.  
3. Make sure line is free of traps due to sagging and has  
sufficient pitch to drain.  
INSTALLATION OF HUMCCWTR2019-A--  
BYPASS WATER SAVER HUMIDIFIER  
Carrier’s HUMCCWTR2019-A-- bypass water saver humidifier  
can be installed on either the supply or return plenum of a  
forced-air system. This unit requires an external bypass duct  
between the supply- and return-air ductwork.  
Unit may leak if drain tubing is misapplied. Do not insert  
tubing inside of drain fitting outlet.  
Step 7—Make Water Connection  
It is recommended to install the humidifier where it can be easily  
serviced. If this humidifier is installed with a central cooling  
system the factory-supplied 6-in. shutoff damper must be installed  
to close during the cooling season to prevent bypass air. Always  
install humidifier downstream of an electronic air cleaner.  
If garden hose is not used for water supply:  
1. Mount saddle valve on water line according to instructions  
supplied with valve.  
2. Run 1/4-in. diameter (water line grade) tubing from saddle  
valve to adapter on solenoid valve and tighten compression  
fittings.  
Step 1—Inspect Package and Check Equipment  
Inspect contents of packaged humidifier. File claim with shipping  
company prior to installation if shipment is damaged or incom-  
plete.  
IMPORTANT: If water pressure is higher than normal (60 psi),  
use noise suppression disk included in parts bag. (Read water noise  
reducer note located inside package for instructions). For normal  
operation, saddle valve need only be opened 1 full turn to meet  
performance requirements.  
The package should contain:  
1. Humidifier and media assembly  
2. Humidistat  
3. Open valve and check installation for leaks.  
NOTE: Saddle valve is self piercing on copper lines; 1/4-in. hole  
must be drilled in steel or iron pipes. Use only a grounded drill or  
a hand drill to avoid shock hazard. Turn off water and drain the  
pipe prior to drilling 1/4-in. hole.  
3. Template  
4. Ten ft 1/4-in. water supply tubing  
5. Owner’s Manual  
Step 8—Install Humidistat and Complete Wiring  
6. Warranty Certificate  
1. Mount humidistat on inside wall, or return-air duct in accor-  
dance with section INSTALLATION OF HUMIDISTAT on  
page 10.  
7. Support Bracket  
8. One 1/4-in. blunt point screw  
9. Saddle valve assembly  
10. Four sheet metal screws  
11. 6-in. damper  
2. Wire brown low-voltage leads to furnace control board, or  
install a field-supplied step-down transformer 115vac/24vac  
60Hz to power solenoid valve. (See Fig. 4.) Make sure bridge  
rectifier is attached to coil of solenoid valve.  
12. Worm clamp for field-supplied drain tube  
13. Humidifier maintenance instruction sticker  
14. Carrier logo label  
NOTE: Wiring must comply with National Electrical Code and  
any local codes or ordinances that may apply.  
Step 9—Start-Up  
1. Open saddle valve to permit water flow to the solenoid.  
2. Check all connections for water leaks.  
Step 2—Select Location (See Fig. 14.)  
Humidifier may be installed on either supply or return plenum. If  
furnace has air conditioning coil, be sure humidifier does not  
interfere with coil ends. Remember to provide clearance for  
maintenance and evaporator pad removal.  
3. Set thermostat to call for heat. Set humidistat for highest  
humidity setting making sure contacts are closed. After a few  
minutes of operation, check the drain connection for leaks and  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
GASKET  
FLOAT  
ARM  
PIN  
RETAINER  
BEARING  
WASHER  
12 IN. LONG  
VALVE BODY  
SCREW  
VALVE SEAT  
14 IN. BLUNT  
POINT SCREW  
SUPPORT  
BRACKET  
(LEFT HAND INSTALLATION SHOWN)  
FLOAT VALVE ASSEMBLY  
REINSTALLING MEDIA ASSEMBLY  
A98370  
Fig. 15—Valve and Media Assembly for HUMCCWTR2019-A--  
Step 3—Prepare Plenum Opening (See Fig. 2.)  
6. Level unit and attach support bracket to unit using 1/4-in.  
blunt point screw. Attach other end of support bracket to duct  
by drilling a hole and using remaining 1/4-in. long screw.  
1. Use template for marking humidifier opening.  
BYPASS UNITS  
7. Re-install water pan and drain plug. Re-attach float arm to  
valve body by aligning holes in both parts and re-inserting pin.  
NOTE: Pin may be re-inserted from either direction.  
8. Re-install media assembly. Ensure that square shaft of media  
assembly is located inside mating opening of motor coupling.  
Ensure that bearing washer is located on interior side of  
bearing retainer. (See Fig. 15.)  
"N" COIL  
DRILL (2) HOLES  
Step 5—Install Bypass Duct  
IN DUCT  
FOR #8 SHEETMETAL  
SCREWS  
Attach field-supplied 6-in. diameter duct, elbow, or starting collar  
with field-supplied 1/4-in. zip screws. Install supplied 6-in. damper  
in 6-in. duct connector.  
IMPORTANT: On systems with central cooling, the damper  
should be closed during cooling season to prevent bypass air.  
VERTICAL  
HORIZONTAL  
Do not support weight of duct from humidifier — damage  
could result.  
A98369  
Fig. 14—Installation of HUMCCWTR2019-A--  
Step 6—Install Drain Line  
Water Saver Humidifier  
1. Use 1/2-in. ID field-supplied vinyl tubing or equivalent tubing  
to connect overflow drain connection on unit water pan to  
drain. (See Fig. 16.)  
2. Tape in place on plenum making sure template is level.  
IMPORTANT: For humidifier to operate properly it must be level  
and mounted on a vertical surface.  
2. Use worm drain clamp to hold tubing in position over  
overflow drain connection.  
3. Drill four 1/8-in. holes in plenum.  
4. Cut opening in plenum using heavy solid lines on template as  
a guide.  
IMPORTANT: Make sure that line is free of traps due to sagging  
and has sufficient pitch to drain.  
Step 4—Mount the Humidifier  
3. Unit must be level to provide proper drainage.  
Supply or return plenum mounting:  
14″  
1. Remove unit access door by turning 2 pawl latches 1/2 turn  
and pulling door forward.  
2. Determine whether unit is to be used for right- or left-hand  
installation and apply gasket tape (supplied) to unit flange  
intended to seat against duct.  
OVERFLOW TUBE  
DRAIN PLUG  
3. Remove media assembly from cabinet by lifting bearing end  
of assembly out of bearing retainer and pulling assembly  
toward outlet duct, thus disengaging media from motor.  
Remove media through unit access opening.  
A96013  
Fig. 16—Water Level in HUMCCWTR2019-A--  
Step 7—Make Water Connection  
4. Remove pin from float assembly and remove float and arm.  
Remove drain plug and water pan.  
1. Mount saddle valve on cold water line according to local  
codes.  
NOTE: Water pan must be tilted for removal.  
2. For plastic tube installations: run 1/4-in. OD tubing (supplied)  
from saddle valve to float valve. Prepare tubing ends with  
plastic compression sleeves and brass inserts, and tighten  
5. Mount unit to duct using pre-drilled holes and four 1/2-in.  
long screws found in parts bag.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
compression fittings. Plastic compression nut supplied with  
float valve should not be torqued greater than 25 in.-lb. For  
copper tubing installations: copper tubing may be connected to  
float valve by using a field-supplied 1/4 to 1/4 in. straight-  
through compression union. Run copper tubing to 1 side of  
compression union and use a standard compression sleeve.  
Tighten compression nut to torque recommended by manu-  
facturer. Attach approximately 6 in. of polyethylene supply  
tubing (supplied) between compression union and float valve.  
Prepare polyethylene tubing on both ends with brass inserts to  
prevent tubing collapse. Use compression nut at union to  
manufacturer’s recommended torque, tighten plastic nut on  
float valve to maximum of 25 in.-lb.  
b. If installed during heating season, set unit for normal  
operation.  
INSTALLATION OF HUMIDISTAT  
The humidistat provides automatic control of humidifiers in  
central heating systems. It is designed for low voltage, wall, or  
surface duct mounting and contains a SPST snap-acting dustproof  
switch.  
Disconnect power supply before making wiring connections  
to prevent possible electrical shock and equipment damage.  
Make wiring connections in accordance with Installation  
Instruction supplied with the humidifier.  
3. Open valve and check installation for leaks.  
NOTE: Valve is self piercing on copper lines; 1/4-in. hole must  
be drilled in steel or iron pipes. Use only a grounded drill or a hand  
drill to avoid shock hazard. Turn off water and drain the pipe prior  
to drilling 1/4-in. hole.  
1. Installer must be a trained, experienced service person.  
2. Disconnect power supply before beginning installation.  
3. Conduct a thorough checkout before leaving installation.  
Step 1—Wall Mounting (Low Voltage)  
Step 8—Install Humidistat and Complete Wiring  
1. Mount humidistat on inside wall or return-air duct in accor-  
dance with section INSTALLATION OF HUMIDISTAT on  
page 10.  
1. Choose a location for humidistat about 5 ft above floor on  
inside wall with average room temperature and relative  
humidity conditions. Maximum ambient temperature of se-  
lected location must not exceed 125°F. Humidistat may be  
mounted directly on wall.  
NOTE: Wiring must comply with national electrical code and any  
local codes or ordinances that may apply. (See Fig. 17.)  
2. Drill a small hole in wall and run low-voltage wiring to  
location chosen. Pull about 6 in. of wire through hole. Plug  
opening to prevent drafts from affecting humidistat operation.  
HUMIDISTAT  
24VAC  
FURNACE  
MOTOR  
3. Remove knob, faceplate, and switch assembly from case by  
following steps listed below.  
a. Remove knob by pulling away from casing. (See Fig. 18.)  
TRANSFORMER  
(10-VA)  
b. Lift off faceplate, starting at right side. Left end of  
faceplate protrudes under lip of casing. (See Fig. 18.)  
HUMIDISTAT  
115V  
24V  
MOTOR  
FIELD  
c. Remove switch by removing 2 screws in back of casing.  
Pressing tab on case. Lift out control. (See Fig. 19.)  
WIRING  
MOUNTING HOLES  
A96014  
Fig.17—Humidistat Installation for  
HUMCCWTR2019-A--  
Step 9—Start-Up  
1. Open saddle valve to permit water to flow to the solenoid  
valve.  
2. Check all connections for water leaks.  
3. Set thermostat to call for heat. Set humidistat at highest  
humidity setting to be sure the contacts are closed. After a few  
minutes of operation, check the drain connection for leaks and  
to see if water is flowing through humidifier.  
4. Reverse thermostat and humidistat settings to insure proper  
shutdown.  
5. Reset thermostat to normal setting. Reset humidistat to rec-  
ommended setting.  
KNOB  
Step 10—Final Steps  
CASE  
Attach humidifier maintenance instruction sticker to a visible  
location.  
FACEPLATE  
A97102  
1. Inform homeowner of proper operation, maintenance, and  
humidistat setting.  
Fig. 18—Knob and Faceplate Removal  
a. If unit is installed during cooling season, close bypass  
damper, set humidistat for summer setting (OFF or lowest  
setting).  
4. Make connections to screw terminals on switch assembly.  
Re-install switch into casing — secure with 2 short screws.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Remove protective backing from foam gasket provided with  
control and apply to template.  
CASING  
4. Run low-voltage wire from humidifier to template. Lay wire  
over 1 side of foam gasket. Wire can enter humidistat case  
from any direction.  
CONTROL  
IMPORTANT: Do not position wire directly under standoff pro-  
jections at back of case. If wire is under these projections, case will  
not seat tightly against gasket causing air leakage and possible  
improper operation.  
5. Remove knob, faceplate, and switch assembly from case by  
following steps listed below.  
a. Remove knob by pulling away from casing. (See Fig. 18.)  
TAB  
b. Lift off faceplate, starting at right side. Left end of  
faceplate protrudes under lip on casing. (See Fig. 18.)  
c. Remove switch by removing 2 screws in back of casing.  
Pressing tab on case. Lift out control. (See Fig. 19.)  
A97103  
Fig. 19—Switch Assembly Removal  
6. Make connections to screw terminals on switch assembly.  
Re-install switch into casing — secure with 2 short screws.  
5. Mount case horizontally over wires directly to wall using 2  
long screws provided.  
7. While holding wire in place. Mount humidistat case horizon-  
tally on duct using 2 mounting screws provided. Tighten  
firmly so that gasket seals space around wires and between  
case and duct. (See Fig. 21.)  
6. Replace faceplate and knob.  
Step 2—Duct Mounting (Low Voltage)  
1. Locate humidistat at least 8 in. upstream of humidifier in  
return-air duct. If mounting near elbow area, keep device 6 in.  
upstream of elbow so element will be affected by normal  
airflow. (See Fig. 20.)  
8. Replace faceplate and knob.  
Step 3—Wiring  
All wiring must comply with local codes and ordinances.  
Step 4—Adjustment  
2. Remove protective backing from template furnished with each  
control and apply self-adhesive side on return air duct at  
selected location. Following instructions on template and in  
Fig. 21, drill 2 mounting holes and six 1/4-in. diameter sensing  
holes in duct. Sensing holes allow return air to reach nylon  
sensing element and operate humidistat.  
Recommended humidistat setting should only be used as a guide.  
After adjustment of setting, allow at least 5 hr for equilibrium to be  
reached. Condensation on single pane windows or woodwork  
indicates excessive moisture. Condensation must not be allowed to  
continue for extended periods of time, or moisture damage can  
result. Lower humidistat setting in small steps until condensation  
disappears. However, if air is too dry, raise the setting.  
NOTE: If desired, cut square hole in duct as indicated on template  
as an alternative to holes.  
ALTERNATE LOCATIONS  
RETURN AIR  
RETURN AIR  
5 IN. MIN.  
15 IN. MIN.  
RETURN AIR DUCT  
BEST LOCATION  
A97104  
Fig. 20—Alternate Location Duct Mount Installation  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 5—Operation  
Recommended Humidistat Setting  
When relative humidity falls to humidistat set point, the humidistat  
switch makes contact and starts humidifier. In some central unit  
humidifier systems, furnace fan must be operating before humidi-  
fier will start. An increase in relative humidity above set point will  
stop humidifier.  
OUTSIDE  
TEMPERATURES  
RECOMMENDED  
HUMIDISTAT SETTING  
-20°F  
-10°F  
0°F  
15%  
20% (LO)  
25%  
+10°F  
+20°F  
+30°F  
30%  
Step 6—Checkout  
35%  
40% (MED)  
Place system in operation and observe at least 1 complete cycle to  
make certain that all components are functioning properly.  
MAKE OPENING IN DUCT  
MOUNT HUMIDISTAT CASE  
MOUNTING TEMPLATE  
FOAM GASKET  
CASE  
DRILL SIX 1/4 IN.  
DIAMETER HOLES  
ALTERNATE PROCEDURE:  
MOUNTING SCREWS (2)  
A97105  
Fig. 21—Humidistat Installation Schematic  
Copyright 1998 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231  
hum1si  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book  
Tab 7a 9a  
1
4
PC 101  
Catalog No. 03HU-MC1  
Printed in U.S.A.  
Form HUM-1SI  
Pg 12  
7-98  
Replaces: 49-4SI  
Download from Www.Somanuals.com. All Manuals Search And Download.  

BenQ Network Card AWL400 User Manual
Bionaire Humidifier BCM4655 CN User Manual
Black Decker Paint Remover 9756 User Manual
Boston Acoustics Speaker DSi465T2 User Manual
Briggs Stratton Portable Generator 01648 1 User Manual
Bryant Patio Heater 379A User Manual
Bushnell Hunting Equipment 730132A User Manual
Canon Calculator MP18DII User Manual
Canon Webcam D20 User Manual
Cisco Systems Network Card HWIC 1FE User Manual