Carrier Heating System 48HJ015 025 User Manual

48HJ015-025  
Single Package Rooftop Units  
Electric Cooling/Gas Heating  
Installation Instructions  
CONTENTS  
Page  
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1  
1. Improper installation, adjustment, alteration, serv-  
ice, or maintenance can cause property damage, per-  
sonal injury, or loss of life. Refer to the User’s In-  
formation Manual provided with this unit for more  
details.  
2. Do not store or use gasoline or other flammable va-  
pors and liquids in the vicinity of this or any other  
appliance.  
What to do if you smell gas:  
1. DO NOT try to light any appliance.  
2. DO NOT touch any electrical switch, or use any phone  
in your building.  
3. IMMEDIATELY call your gas supplier from a neigh-  
bor’s phone. Follow the gas supplier’s instructions.  
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-12  
Step 1 — Provide Unit Support . . . . . . . . . . . . . . . 1  
• ROOF CURB  
• ALTERNATE UNIT SUPPORT  
Step 2 — Rig and Place Unit . . . . . . . . . . . . . . . . . . 3  
• POSITIONING  
• ROOF MOUNT  
Step 3 — Field Fabricate Ductwork . . . . . . . . . . . . 7  
Step 4 — Make Unit Duct Connections . . . . . . . . 7  
Step 5 — Install Flue Hood . . . . . . . . . . . . . . . . . . . 7  
Step 6 — Trap Condensate Drain . . . . . . . . . . . . . 8  
Step 7 — Install Gas Piping . . . . . . . . . . . . . . . . . . . 8  
Step 8 — Make Electrical Connections . . . . . . . . 9  
• FIELD POWER SUPPLY  
• FIELD CONTROL WIRING  
Step 9 — Make Outdoor-Air Inlet  
4. If you cannot reach your gas supplier, call the fire  
department.  
Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
• MANUAL OUTDOOR-AIR DAMPER  
• OPTIONAL FACTORY-INSTALLED  
ECONOMIZER  
Disconnect gas piping from unit when pressure testing  
at pressure greater than 0.5 psig. Pressures greater than  
0.5 psig will cause gas valve damage resulting in haz-  
ardous condition. If gas valve is subjected to pressure  
greater than 0.5 psig, it must be replaced before use. When  
pressure testing field-supplied gas piping at pressures of  
0.5 psig or less, a unit connected to such piping must be  
isolated by closing the manual gas valve(s).  
Step 10 — Install Outdoor-Air Hood . . . . . . . . . . 10  
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-17  
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18-27  
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . CL-1  
SAFETY CONSIDERATIONS  
INSTALLATION  
Installation and servicing of air-conditioning equipment  
can be hazardous due to system pressure and electrical com-  
ponents. Only trained and qualified service personnel should  
install, repair, or service air-conditioning equipment.  
Untrained personnel can perform the basic maintenance  
functions of cleaning coils and filters and replacing filters.  
All other operations should be performed by trained service  
personnel. When working on air-conditioning equipment, ob-  
serve precautions in the literature, tags and labels attached  
to the unit, and other safety precautions that may apply.  
Step 1 — Provide Unit Support  
ROOF CURB — Assemble or install accessory roof curb in  
accordance with instructions shipped with this accessory. See  
Fig. 1 and 2. Install insulation, cant strips, roofing, and counter  
flashing as shown. Ductwork can be installed to roof curb  
before unit is set in place. Curb should be level. This is nec-  
essary to permit unit drain to function properly. Unit level-  
ing tolerance is ± 116 in. per linear ft in any direction. Refer  
to Accessory Roof Curb Installation Instructions for addi-  
tional information as required. When accessory roof curb is  
used, unit may be installed on class A, B, or C roof covering  
material.  
Follow all safety codes. Wear safety glasses and work gloves.  
Use quenching cloth for unbrazing operations. Have fire ex-  
tinguishers available for all brazing operations.  
IMPORTANT: The gasketing of the unit to the roof  
curb is critical for a watertight seal. Install gasket with  
the roof curb as shown in Fig. 1. Improperly applied  
gasket can also result in air leaks and poor unit  
performance.  
Before performing service or maintenance operations on  
unit, turn off main power switch to unit. Electrical shock  
could cause personal injury.  
Instructions continued on page 3.  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book 1  
PC 111  
Catalog No. 534-807  
Printed in U.S.A.  
Form 48HJ-9SI  
Pg 1  
2-95  
Replaces: 48HJ-5SI  
Tab 1a  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Do not drop unit; keep upright. Use spreader bars over  
unit to prevent sling or cable damage. Rollers may be used  
to move unit across a roof. Level by using unit frame as a  
1
reference; leveling tolerance is ± 16 in. per linear ft in any  
direction. See Fig. 3 for additional information. Unit oper-  
ating weight is shown in Table 1.  
Four lifting holes are provided in ends of unit base rails  
as shown in Fig. 3. Refer to rigging instructions on unit.  
POSITIONING — Maintain clearance, per Fig. 4 and 5, around  
and above unit to provide minimum distance from combus-  
tible materials, proper airflow, and service access.  
Do not install unit in an indoor location. Do not locate  
unit air inlets near exhaust vents or other sources of con-  
taminated air. For proper unit operation, adequate combus-  
tion and ventilation air must be provided in accordance with  
Section 5.3 (Air for Combustion and Ventilation) of the  
National Fuel Gas Code, ANSI Z223.1 (American National  
Standards Institute).  
Although unit is weatherproof, guard against water from  
higher level runoff and overhangs.  
Locate mechanical draft system flue assembly at least  
4 ft from any opening through which combustion products  
could enter the building, and at least 4 ft from any adjacent  
building. When unit is located adjacent to public walkways,  
flue assembly must be at least 7 ft above grade.  
Fig. 2 — Horizontal Supply/Return Curb  
and Horizontal Adapter Details  
ALTERNATE UNIT SUPPORT — When the curb cannot  
be used, install unit on a noncombustible surface. Support  
unit with sleepers, using unit curb support area. If sleepers  
cannot be used, support long sides of unit with a minimum  
of 3 equally spaced 4-in. x 4-in. pads on each side.  
ROOF MOUNT — Check building codes for weight distri-  
bution requirements. Unit weight is shown in Table 1.  
Instructions continued on page 7.  
Step 2 — Rig and Place Unit — Inspect unit for trans-  
portation damage. File any claim with transportation agency.  
NOTES:  
MAXIMUM SHIPPING  
1. Dimensions in ( ) are in millimeters.  
UNIT  
48HJ  
WEIGHT  
2. Refer to Table 1 for unit operating weights.  
3. Remove boards at ends of unit and runners prior to rigging.  
4. Rig by inserting hooks into unit base rails as shown. Use corner  
post from packaging to protect coil from damage. Use bumper boards  
for spreader bars.  
5. Weights do not include optional economizer. See Table 1 for econo-  
mizer weight.  
6. Weights given are for aluminum evaporator coil plate fins and cop-  
per condenser coil plate fins. Weights of other metal combinations  
are listed in Table 1.  
Lb  
Kg  
871  
D015  
E015  
E017  
D025  
1920  
1940  
2310  
2535  
880  
1048  
1150  
Dimension A  
UNIT  
Ft-in.  
3-138  
3-114  
3-434  
3-434  
mm  
949  
48HJD015  
48HJE015  
48HJE017  
48HJD025  
All panels must be in place when rigging.  
946  
1035  
1010  
Fig. 3 — Rigging Details  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 1 — Physical Data  
HJD015/HJE015  
208/230, 460 V  
UNIT SIZE 48  
HJE017  
HJD025  
575 V  
OPERATING WT (lb)  
Al/Al*  
1640/1660  
1770/1790  
1840/1860  
110  
2010  
2160  
2250  
110  
2235  
2385  
2515  
110  
Unit Al/Cu*  
Cu/Cu*  
Economizer  
Roof Curb†  
200  
200  
200  
COMPRESSOR  
Number  
Cylinders  
06D Semi-Hermetic  
1
6
2
4
2
6
REFRIGERANT TYPE  
Charge (lb)  
R-22  
System 1  
22.50  
14.25  
15.00  
17.50  
17.00  
System 2  
CONDENSER COIL  
Rows  
Copper Tubes, Aluminum or Copper Plate Fins  
3
4
4
Fins/in.  
15  
15  
22.2  
15  
Total Face Area (sq ft)  
22.2  
22.2  
CONDENSER FAN  
Nominal Cfm  
Number...Diameter (in.)  
Motor Hp (1075 Rpm)  
Watts Input (Total)  
Propeller Type, Direct Drive  
10,500  
10,500  
14,200  
2...30  
1...1075  
3400  
3...22  
3...22  
1
1
2
2
1090  
1090  
EVAPORATOR COIL  
Rows  
Copper Tubes, Aluminum or Copper Plate Fins  
2
3
4
Fins/in.  
17  
15  
17.9  
15  
Total Face Area (sq ft)  
17.9  
17.9  
EVAPORATOR FAN  
Centrifugal, Adjustable Pitch Belt Drive  
Quantity...Size (in.)  
2...10 x 10  
5000  
2...10 x 10  
5000  
2...12 x 12  
6000  
2...12 x12  
8000  
Nominal Cfm  
Fan Rpm Range  
1194-1526  
1550  
1201-1462  
1550  
1238-1494  
1550  
1323-1579  
1550  
Maximum Allowable Rpm  
Motor Pulley Pitch Diameter (in.)  
Fan Pulley Pitch Diameter (in.)  
Belt, Quantity...Type...Length (in.)  
Factory Speed Setting (Rpm)  
Motor Hp (Service Factor)  
Motor Frame Size  
3.4/4.4  
5.2  
4.3/5.3  
6.4  
5.4/6.6  
7.9  
5.8/7.0  
7.9  
1...AX...42  
1293  
1...B...45  
1279  
1...BX...50  
1366  
1...BX...51  
1451  
3.7 (1.15)  
56H  
3 (1.15)  
56H  
5 (1.15)  
184T  
10 (1.15)  
215T  
FURNACE SECTION  
Rollout Switch Cutout Temp (F)**  
Burner Orifice Diameter (in. ...drill size)  
Natural Gas  
190  
190  
190  
.113...33  
.113...33  
.113...33  
(1) .055...54/  
(1) .055...54  
(1) .041...59  
Pilot Orifice Diameter (Quantity) in. ...drill size  
Natural Gas  
(1) .055...54  
(1) .041...59  
(1) .055...54  
(1) .041...59  
Thermostat Heat Anticipator Setting  
Stage 1  
Stage 2  
1.2/1.2  
—/0.6  
1/2  
1.2  
0.6  
2
1.2  
0.6  
2
Gas Valve Quantity  
HIGH-PRESSURE SWITCH  
Cutout (psig)  
Reset (psig)  
426  
320  
LOW-PRESSURE SWITCH  
Cutout (psig)  
Reset (psig)  
7
22  
AIR INLET SCREENS  
Cleanable  
2...20 x 25 x 1  
1...20 x 20 x 1  
Economizer, Quantity...Size (in.)  
RETURN-AIR FILTERS (TYPE)  
Quantity... Size (in.)  
10% Efficient — 2-in. Throwaway Fiberglass  
4...20 x 20 x 2  
4...16 x 20 x 2  
LEGEND  
Al  
Cu  
Aluminum  
Copper  
*Evaporator coil fin material/condenser coil fin material.  
†Weight of 14 in. roof curb.  
**Rollout switch is manual reset.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAXIMUM SHIPPING WEIGHT  
UNIT  
48HJ  
Lb  
Kg  
871  
880  
1048  
D015  
E015  
E017  
1920  
1940  
2310  
DIMENSIONS  
UNIT  
48HJ  
X
Y
Ft-in.  
3-2  
mm  
965  
Ft-in.  
mm  
1219  
1219  
1083  
D015  
E015  
E017  
4-0  
4-0  
3-2  
3-738  
965  
1102  
3-658  
WEIGHT OF CORNER*  
UNIT  
48HJ  
A
B
C
D
Lb  
Kg  
Lb  
Kg  
163  
165  
230  
Lb  
Kg  
Lb  
Kg  
245  
248  
235  
D015  
E015  
E017  
365  
372  
509  
166  
169  
231  
360  
363  
506  
373  
377  
475  
169  
171  
216  
540  
547  
519  
*Weights are for unit only and do not include options or crating.  
NOTES:  
1. Dimensions in ( ) are in millimeters.  
2.  
Center of gravity.  
3.  
Direction of airflow.  
4. Ductwork to be attached to accessory roof curb only.  
5. Minimum clearance:  
a. Rear: 7Ј-0Љ (2134) for coil removal. This dimension can be reduced  
to 4Ј-0Љ (1219) if conditions permit coil removal from the top.  
b. Left side: 4Ј-0Љ (1219) for proper condenser coil airflow.  
c. Front: 4Ј-0Љ (1219) for control box access.  
d. Right side: 4Ј-0Љ (1219) for proper operation of damper and power  
exhaust (if so equipped).  
e. Top: 6Ј-0Љ (1829) to assure proper condenser fan operation.  
f. Local codes or jurisdiction may prevail.  
6. With the exception of clearance for the condenser coil and the damper/  
power exhaust as stated in Note No. 5, a removable fence or barri-  
cade requires no clearance.  
7. Dimensions are from outside of corner post. Allow 0Ј-516Љ (8) on each  
side for top cover drip edge.  
Fig. 4 — Base Unit Dimensions, 48HJ015,017  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAXIMUM SHIPPING WEIGHT  
Lb  
Kg  
2535  
1150  
NOTES:  
1. Dimensions in ( ) are in millimeters.  
2.  
Center of gravity.  
3.  
Direction of airflow.  
4. Ductwork to be attached to accessory roof curb only.  
5. Minimum clearance:  
a. Rear: 7Ј0Љ (2134) for coil removal. This dimen-  
sion can be reduced to 4Ј0Љ (1219) if conditions  
permit coil removal from the top.  
b. 4Ј0Љ (1219) to combustible surfaces, all four sides  
(includes between units).  
c. Left side: 4Ј0Љ (1219) for proper condenser coil  
airflow.  
d. Front: 4Ј0Љ (1219) for control box access.  
e. Right side: 4Ј0Љ (1219) for proper operation of  
damper and power exhaust (if so equipped).  
f. Top: 6Ј0Љ (1829) to assure proper condenser fan  
operation.  
g. Bottom: 14Љ (356) to combustible surfaces (when  
not using curb).  
h. Control box side: 3Ј0Љ (914) to ungrounded sur-  
faces (non-combustible).  
i. Control box side: 3Ј6Љ (1067) to block or concrete  
walls, or other grounded surfaces.  
j. Local codes or jurisdiction may prevail.  
6. With the exception of clearance for the condenser  
coil and the damper/power exhaust as stated in Note  
No. 5, a removable fence or barricade requires no  
clearance.  
7. Dimensions are from outside of corner post. Allow  
0Ј-516Љ (8) on each side for top cover drip edge.  
CORNER WEIGHT*  
A
B
C
D
Lb  
Kg  
Lb  
Kg  
Lb  
Kg  
Lb  
Kg  
523  
237  
541  
245  
574  
260  
596  
270  
*Weights are for unit only and do not include options or crating.  
Fig. 5 — Base Unit Dimensions, 48HJ025  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 3 — Field Fabricate Ductwork — Secure all  
ducts to building structure. Use flexible duct connectors be-  
tween unit and ducts as required. Insulate and weatherproof  
all external ductwork, joints, and roof openings with counter  
flashing and mastic in accordance with applicable codes.  
Ducts passing through an unconditioned space must be  
insulated and covered with a vapor barrier.  
Step 5 — Install Flue Hood — Flue hood is shipped  
secured to a baffle under main control box. To install, secure  
flue hood to access panel. See Fig. 9.  
NOTE: When properly installed, flue hood will line up with  
combustion fan housing. See Fig. 10.  
Step 4 — Make Unit Duct Connections — Unit  
is shipped for through-the-bottom duct connections. Duct-  
work openings are shown in Fig. 1, 4, and 5. Duct connec-  
tions are shown in Fig. 6. Field-fabricated concentric duct-  
work may be connected as shown in Fig. 7 and 8. Attach all  
ductwork to roof curb and roof curb basepans.  
NOTE: Dimensions A, AЈ, B, and BЈ are obtained from field-supplied  
ceiling diffuser.  
areas indicate block-off pans.  
Fig. 8 — Concentric Duct Details  
NOTE: Do not drill in this area; damage to basepan may result in  
water leak.  
Fig. 6 — Air Distribution — Through-the-Bottom  
(48HJ017 and 025 Shown)  
NOTE: Do not drill in this area; damage to basepan may result in  
water leak.  
Fig. 7 — Concentric Duct Air Distribution  
(48HJ017 and 025 Shown)  
Fig. 9 — Flue Hood Location  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRESSURE  
SWITCH  
COMBUSTION  
FAN HOUSING  
3/4" FPT DRAIN  
CONNECTION  
1-3/8"  
DRAIN HOLE  
Fig. 11 — Condensate Drain Details  
HEAT  
EXCHANGER  
SECTION  
Fig. 10 — Combustion Fan Housing Location  
Fig. 12 — Condensate Drain Piping Details  
Step 6 — Trap Condensate Drain — See Fig. 11  
3
for drain location. One 4-in. half coupling is provided  
inside unit evaporator section for condensate drain connec-  
tion. An 812 in. x 34-in. diameter and 2-in. x 34-in. diameter  
pipe nipple, coupled to standard 34-in. diameter elbows, pro-  
vides a straight path down through hole in unit base rail (see  
Fig. 12). A trap at least 4-in. deep must be used.  
Step 7 — Install Gas Piping — Unit is equipped for  
use with natural gas. Installation must conform with local  
building codes or, in the absence of local codes, with the  
National Fuel Gas Code, ANSI Z223.1.  
1
Install manual gas shutoff valve with a 8-in. NPT pres-  
sure tap for test gage connection at unit. Field gas piping  
must include sediment trap and union. See Fig. 13.  
Do not pressure test gas supply while connected to unit.  
Always disconnect union before servicing.  
Fig. 13 — Field Gas Piping  
Natural gas pressure at unit gas connection must not be  
less than 5 in. wg or greater than 13.5 in. wg.  
Size gas-supply piping for 0.5-in. wg maximum pressure  
drop. Do not use supply pipe smaller than unit gas connec-  
tion (34-in. NPT).  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 8 — Make Electrical Connections  
FIELD POWER SUPPLY — Unit is factory wired for volt-  
age shown on unit nameplate.  
When installing units, provide a disconnect per NEC  
(National Electrical Code) of adequate size (Table 2).  
All field wiring must comply with NEC and local  
requirements.  
Route power and ground lines through control box end  
panel or unit basepan (see Fig. 4 and 5) to connections as  
shown on unit wiring diagram and Fig. 14.  
LEGEND  
The unit must be electrically grounded in accordance  
with local codes and NEC ANSI/NFPA 70 (National Fire  
Protection Association).  
EQUIP  
GND  
NEC  
TB  
Equipment  
Ground  
National Electrical Code  
Terminal Board  
NOTE: Maximum wire size for TB1 is 2/0.  
Field wiring must conform to temperature limitations for  
type ‘‘T’’ wire. All field wiring must comply with NEC and  
local requirements.  
Fig. 14 — Field Power Wiring Connections  
Transformer no. 1 is wired for 230-v unit. If 208/230-v  
unit is to be run with 208-v power supply, the transformer  
must be rewired as follows:  
1. Remove cap from red (208 v) wire.  
2. Remove cap from orange (230 v) spliced wire.  
3. Replace orange wire with red wire.  
4. Recap both wires.  
IMPORTANT: BE CERTAIN UNUSED WIRES  
ARE CAPPED. Failure to do so may damage the  
transformers.  
Operating voltage to compressor must be within voltage  
range indicated on unit nameplate. On 3-phase units, volt-  
ages between phases must be balanced within 2%.  
Table 2 — Electrical Data  
COMPRESSOR  
No. 1 No. 2  
VOLTAGE  
RANGE  
POWER COMBUSTION  
EXHAUST FAN MOTOR  
DISCONNECT  
SIZE  
NOMINAL  
OFM  
IFM  
FLA  
POWER SUPPLY  
MCA MOCP*  
UNIT VOLTAGE  
48HJ  
(3 Ph,  
60 Hz)  
FLA LRA  
(ea) (ea)  
Min Max RLA LRA RLA LRA Qty  
Hp  
LRA  
FLA LRA  
FLA  
FLA  
LRA  
0.57  
0.57  
0.30  
0.30  
0.57  
0.57  
0.57  
0.57  
0.30  
0.30  
0.57  
0.57  
0.57  
0.57  
0.30  
0.30  
0.57  
0.57  
65/65 100/100 64/64 324/324  
70/70 100/100 70/70 343/343  
208/230 187 254 39.7 228  
3
3
3
3
3
3
2
2
2
1.7 3.8 3.7 10.5/10.5 84.5/84.5  
4.6 18.8  
32  
34  
26  
28  
50  
50  
40  
40  
32  
34  
26  
29  
162  
168  
119  
124  
015  
460  
575  
414 508 19.9 114  
518 632 16.0 91  
0.8 1.9 3.7  
4.8  
3.9  
42.3  
23.4  
2.3 6.0  
0.75 1.5  
1.7 24.8  
0.8 10.8  
0.75 8.4  
3
5
5
5
2.1 4.8  
84/84 110/100 90/90 499/485  
89/89 110/110 95/95 518/504  
208/230 187 254 28.2 160 28.2 160  
15.8/15.8 105/91  
4.6 18.8  
42  
44  
34  
36  
50  
50  
40  
45  
45  
47  
36  
39  
238  
244  
190  
195  
017  
025  
460  
575  
414 508 14.1 80 14.1 80  
518 632 11.3 64 11.3 64  
7.9  
6.0  
46  
37  
2.3 6.0  
2.1 4.8  
119/119 150/150 127/127 639/614  
124/124 150/150 133/133 657/632  
208/230 187 254 35.6 198 35.6 198  
5.5 24.8 10 28.0/28.0 193/168  
4.6 18.8  
60  
63  
52  
54  
70  
80  
60  
60  
65  
67  
56  
59  
304  
310  
241  
246  
460  
575  
414 508 17.8 99 17.8 99  
518 632 14.3 79 14.3 79  
LEGEND  
2.8 10.8 10  
3.4 8.4 10  
14.6  
13.0  
84  
66  
2.3 6.0  
2.1 4.8  
NOTES: In compliance with NEC requirements for multimotor and combina-  
tion load equipment (refer to NEC Articles 430 and 440), the overcurrent pro-  
tective device for the unit shall be fuse or HACR breaker. The Canadian units  
may be fuse or circuit breaker.  
FLA  
HACR  
IFM  
LRA  
MCA  
MOCP  
NEC  
OFM  
RLA  
Full Load Amps  
Heating, Air Conditioning and Refrigeration  
Indoor (Evaporator) Fan Motor  
Locked Rotor Amps  
Minimum Circuit Amps  
Maximum Overcurrent Protection  
National Electrical Code  
Outdoor (Condenser) Fan Motor  
Rated Load Amps  
*This is the maximum size permissible; smaller fuse size may be used where  
conditions permit.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Use the following formula to determine the percent volt-  
age imbalance.  
Damper can be preset to admit up to 25% outdoor air into  
return-air compartment. To adjust, loosen securing screws  
and move damper to desired setting, then retighten screws to  
secure damper (Fig. 16).  
% Voltage Imbalance:  
max voltage deviation from average voltage  
OPTIONAL FACTORY-INSTALLED ECONOMIZER  
= 100 x  
average voltage  
Economizer Motor Control Module (See Fig. 17-19) — Set  
economizer motor to the D setting (Fig. 18).  
Damper Vent Position Setting  
1. Set fan switch at ON position (continuous fan operation)  
and close night switch if used.  
EXAMPLE: Supply voltage is 460-3-60.  
AB =452 v  
BC =464 v  
AC =455 v  
452 +464 +455  
2. Set system selector switch at OFF position.  
Average Voltage =  
3
3. Turn damper adjustment knob located on control module  
clockwise slowly until dampers assume desired vent po-  
sition. Do not manually operate economizer motor. Dam-  
age to motor will result.  
1371  
=
3
= 457  
NOTE: Refer to accessory installation instructions included  
with the field-installed economizer for installation informa-  
tion. Also see Accessory Field-Installed Economizer Adjust-  
ment section on page 12.  
Determine maximum deviation from average voltage:  
(AB) 457 −452 =5 v  
(BC) 464 −457 =7 v  
(AC) 457 −455 =2 v  
Maximum deviation is 7 v.  
Determine percent voltage imbalance:  
Step 10 — Install Outdoor-Air Hood — The outdoor-  
air hood is common to 25% air ventilation and economizer.  
If economizer is used, all electrical connections have been  
made and adjusted at the factory. Assemble and install hood  
in the field.  
NOTE: The hood top cover, upper and lower filter retain-  
ers, hood drain pan, baffle (017 and 025 only), and filter sup-  
port bracket are secured opposite the condenser end of the  
unit. The screens, hood side panels, remaining section of fil-  
ter support bracket, seal strip, and hardware are in a package  
located inside the return-air filter access panel (Fig. 20).  
7
% Voltage Imbalance =100 x  
457  
=1.53%  
This amount of phase imbalance is satisfactory as it is be-  
low the maximum allowable 2%.  
IMPORTANT: If the supply voltage phase imbalance  
is more than 2%, contact your local electric utility com-  
pany immediately.  
1. Attach seal strip to upper filter retainer. See Fig. 21.  
2. Assemble hood top cover, side panels, upper filter re-  
tainer, and drain pan (see Fig. 22).  
3. Secure lower filter retainer and long portion of support  
bracket to unit. See Fig. 22. Leave screws loose on 017  
and 025 units.  
Unit failure as a result of operation on improper line  
voltage or excessive phase imbalance constitutes abuse and  
may cause damage to electrical components.  
FIELD CONTROL WIRING — Install a Carrier-approved  
accessory thermostat assembly according to installation  
instructions included with accessory. Locate thermostat as-  
sembly on a solid interior wall in the conditioned space to  
sense average temperature.  
4. 48HJ017,025 Units Only: Slide baffle behind lower filter  
retainer and tighten screws.  
Route thermostat cable or equivalent single leads of col-  
ored wire from subbase terminals through conduit in unit to  
low-voltage connections as shown on unit label wiring dia-  
gram and in Fig. 15.  
NOTE: For wire runs up to 50 ft, use no. 18 AWG (Ameri-  
can Wire Gage) insulated wire (35 C minimum). For 50 to  
75 ft, use no. 16 AWG insulated wire (35 C minimum). For  
over 75 ft, use no. 14 AWG insulated wire (35 C minimum).  
All wire larger than no. 18 AWG cannot be directly con-  
nected at the thermostat and will require a junction box and  
splice at the thermostat.  
Fig. 15 — Field Control Thermostat Wiring  
Set heat anticipator settings as follows:  
UNIT  
VOLTAGE UNIT  
W1  
W2  
48HJD015  
All  
1.20  
48HJD025, HJE015,  
HJE017  
All  
1.20  
0.60  
Settings may be changed slightly to provide a greater de-  
gree of comfort for a particular installation.  
Refer to Accessory Remote Control Panel instructions if  
required.  
Step 9 — Make Outdoor-Air Inlet Adjustments  
MANUAL OUTDOOR-AIR DAMPER — All units (except  
those equipped with a factory-installed economizer) have a  
manual outdoor-air damper to provide ventilation air.  
Fig. 16 — 25% Outdoor-Air Section Details  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. Loosen sheet metal screws for top cover of base unit  
located above outdoor-air inlet opening.  
6. Match notches in hood top cover with unit top cover screws.  
Insert hood flange between top cover flange and unit. Tighten  
screws.  
7. Insert outdoor-air inlet screens and spacer in channel  
created by lower filter retainer and filter support bracket.  
8. Attach remaining shorter section of filter support bracket.  
Fig. 19 — Economizer Motor Control  
Module Location  
Fig. 17 — Economizer Damper Assembly — End View  
Fig. 20 — Outdoor-Air Hood Component Location  
LED  
Light-Emitting Diode  
Fig. 18 — Economizer Motor Control Module  
Fig. 21 — Seal Strip Location  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Crankcase Heater — Crankcase heater is energized  
as long as there is power to the unit.  
IMPORTANT: Unit power must be on for 24 hours  
prior to start-up. Otherwise, damage to compressor may  
result.  
Evaporator Fan — Fan belt and pulleys are factory in-  
stalled. See Tables 3A, 3B, 4, and 5 for Fan Performance  
Data. Remove tape from fan pulley and adjust pulleys on  
48HJ015 units as required. See Evaporator-Fan Perfor-  
mance Adjustment section on page 19. Be sure that fans ro-  
tate in the proper direction. See Table 6 for air quantity lim-  
its. See Table 7 for static pressure drops for accessories and  
options. See Fig. 23 and 24 for fan performance using hori-  
zontal adapter and power exhaust. To alter fan performance,  
see Performance Adjustment sections on page 19.  
Fig. 22 — Outdoor-Air Hood Details  
START-UP  
Use the following information and Start-Up Checklist  
on page CL-1 to check out unit PRIOR to start-up.  
Condenser-Fans and Motors — Condenser fans and  
motors are factory set. Refer to Condenser-Fan Adjustment  
section on page 20 as required. Be sure that fans rotate in the  
proper direction.  
Unit Preparation — Check that unit has been installed  
in accordance with these installation instructions and appli-  
cable codes.  
Return-Air Filters — Check that correct filters are in-  
stalled in filter tracks (see Table 1). Do not operate unit with-  
out return-air filters.  
Compressor Mounting — Loosen the compressor hold-  
down bolts until sidewise movement of the washer under  
each holddown bolt head can be obtained. Do not loosen  
completely as bolts are self-locking and will maintain  
adjustment.  
Outdoor-Air Inlet Screens — Outdoor-air inlet screens  
must be in place before operating unit.  
Accessory Field-Installed Economizer Adjust-  
ment — Remove filter access panel. Check that outdoor-  
Internal Wiring — Check all electrical connections in  
air damper is closed and return-air damper is open.  
unit control boxes; tighten as required.  
Economizer operation and adjustment are described in  
Base Unit Operation section on page 17; and Economizer  
Adjustment section on page 20.  
Refrigerant Service Ports and Valves — Each 48HJ  
unit has 2 Schrader-type service ports per circuit; one on the  
suction line and one on the liquid line. Be sure that the caps  
on the ports are tight. The units also have 2 service valves  
per circuit; one on the suction line and one on the discharge  
line. Be sure all valves are open.  
NOTE: The 50DP900211 horizontal supply/return adapter accessory  
improves 48HJ fan performance by increasing external static pres-  
sure by amount shown above.  
NOTES:  
1. Dimensions are in millimeters.  
2. The 50DP900211 high static regain adapter accessory may be used  
to provide horizontal supply/return.  
Fig. 23 — Horizontal Supply/Return Fan Performance  
With 50DP900211 High Static Regain Adapter  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 3A — Fan Performance Data, 48HJ015, 208/230, 460-V Units  
EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
(CFM)  
0.2  
0.4  
0.6  
0.8  
1.0  
Rpm  
Watts  
Bhp  
Rpm  
Watts  
Bhp  
Rpm  
Watts  
Bhp  
Rpm  
Watts  
Bhp  
Rpm  
Watts  
Bhp  
3750  
4000  
4250  
4500  
4750  
5000  
5250  
5500  
5750  
6000  
6250  
741  
773  
510  
647  
0.58  
0.74  
0.91  
1.09  
1.29  
1.51  
1.74  
1.99  
2.25  
2.54  
2.84  
854  
882  
715  
859  
0.82  
0.98  
1.16  
1.35  
1.56  
1.78  
2.02  
2.27  
2.54  
2.83  
3.13  
952  
978  
921  
1071  
1233  
1407  
1595  
1796  
2011  
2240  
2484  
2742  
3015  
1.05  
1.22  
1.40  
1.60  
1.82  
2.05  
2.29  
2.55  
2.83  
3.12  
3.44  
1041  
1064  
1089  
1114  
1140  
1167  
1195  
1223  
1252  
1282  
1312  
1130  
1285  
1452  
1632  
1825  
2032  
2252  
2487  
2736  
2999  
3279  
1.29  
1.46  
1.65  
1.86  
2.08  
2.32  
2.57  
2.83  
3.12  
3.42  
3.74  
1124  
1145  
1167  
1191  
1215  
1241  
1267  
1293  
1321  
1349  
1378  
1344  
1502  
1674  
1859  
2056  
2268  
2494  
2733  
2988  
3257  
3541  
1.53  
1.71  
1.91  
2.12  
2.34  
2.58  
2.84  
3.11  
3.40  
3.71  
4.03  
806  
796  
912  
1015  
1183  
1365  
1560  
1769  
1992  
2230  
2483  
2751  
1004  
1032  
1060  
1089  
1118  
1148  
1179  
1210  
1241  
839  
958  
942  
972  
873  
1134  
1323  
1527  
1745  
1978  
2227  
2491  
908  
1003  
1035  
1067  
1099  
1132  
1166  
942  
978  
1013  
1049  
1085  
EXTERNAL STATIC PRESSURE (in. wg)  
1.6  
AIRFLOW  
(CFM)  
1.2  
1.4  
1.8  
2.0  
Rpm  
Watts  
Bhp  
Rpm  
Watts  
Bhp  
Rpm  
Watts  
Bhp  
Rpm  
Watts  
Bhp  
Rpm  
Watts  
Bhp  
3750  
4000  
4250  
4500  
4750  
5000  
5250  
5500  
5750  
6000  
6250  
1203  
1222  
1242  
1264  
1286  
1310  
1335  
1360  
1386  
1413  
1440  
1562  
1724  
1900  
2089  
2290  
2507  
2737  
2981  
3241  
3514  
3803  
1.78  
1.96  
2.16  
2.38  
2.61  
2.86  
3.12  
3.40  
3.69  
4.00  
4.33  
1277  
1294  
1313  
1333  
1354  
1376  
1399  
1423  
1448  
1474  
1500  
1784  
1950  
2129  
2322  
2528  
2748  
2983  
3231  
3495  
3773  
4066  
2.03  
2.22  
2.43  
2.65  
2.88  
3.13  
3.40  
3.68  
3.98  
4.30  
4.63  
1349  
1364  
1381  
1399  
1419  
1440  
1461  
1484  
1508  
1532  
1558  
2010  
2180  
2362  
2558  
2769  
2992  
3230  
3483  
3750  
4032  
4330  
2.29  
2.48  
2.69  
2.91  
3.15  
3.41  
3.68  
3.97  
4.27  
4.59  
4.93  
1417  
1431  
1446  
1463  
1482  
1501  
1522  
1543  
2240  
2413  
2599  
2799  
3012  
3240  
3481  
3737  
2.55  
2.75  
2.96  
3.19  
3.43  
3.69  
3.97  
4.26  
1483  
1495  
1509  
1525  
1542  
1560  
2473  
2650  
2839  
3042  
3259  
3489  
2.82  
3.02  
3.23  
3.47  
3.71  
3.98  
LEGEND  
5. Static pressure losses (i.e., economizer) must be added to exter-  
nal static pressure before entering Fan Performance table. See  
Table 7 for accessory/FIOP static pressure information.  
6. Interpolation is permissible. Do not extrapolate.  
7. Maximum continuous bhp is 4.25 and the maximum continuous  
watts are 3775. Extensive motor and drive testing on these units  
ensures that the full horsepower range of the motor can be uti-  
lized with confidence. Using your fan motors up to the watts rating  
shown will not result in nuisance tripping or premature motor fail-  
ure. Unit warranty will not be affected.  
Bhp  
FIOP  
Watts  
Brake Horsepower Input to Fan  
Factory-Installed Option  
Input Watts to Motor  
NOTES:  
1. Boldface indicates standard operating range.  
2. indicates field-supplied motor and drive required.  
3. All other numbers indicate field-supplied drive required.  
4. Factory shipped motor drive range is 1194 to 1526 rpm. Other rpms  
require a field-supplied drive.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 3B — Fan Performance Data, 48HJ015, 575-V Units  
EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
(CFM)  
0.2  
0.4  
0.6  
0.8  
1.0  
Rpm  
Watts  
Bhp  
Rpm  
Watts  
Bhp  
Rpm  
Watts  
Bhp  
Rpm  
Watts  
Bhp  
Rpm  
Watts  
Bhp  
3750  
4000  
4250  
4500  
4750  
5000  
5250  
5500  
5750  
6000  
6250  
741  
773  
510  
647  
0.58  
0.74  
0.91  
1.09  
1.29  
1.51  
1.74  
1.99  
2.25  
2.54  
2.84  
854  
882  
715  
859  
0.82  
0.98  
1.16  
1.35  
1.56  
1.78  
2.02  
2.27  
2.54  
2.83  
3.13  
952  
978  
921  
1071  
1233  
1407  
1595  
1796  
2011  
2240  
2484  
2742  
3015  
1.05  
1.22  
1.40  
1.60  
1.82  
2.05  
2.29  
2.55  
2.83  
3.12  
3.44  
1041  
1064  
1089  
1114  
1140  
1167  
1195  
1223  
1252  
1282  
1312  
1030  
1285  
1452  
1632  
1825  
2032  
2252  
2487  
2736  
2999  
3279  
1.29  
1.46  
1.65  
1.86  
2.08  
2.32  
2.57  
2.83  
3.12  
3.42  
3.74  
1124  
1145  
1167  
1191  
1215  
1241  
1267  
1293  
1321  
1349  
1378  
1344  
1502  
1674  
1859  
2056  
2268  
2494  
2733  
2988  
3257  
3541  
1.53  
1.71  
1.91  
2.12  
2.34  
2.58  
2.84  
3.11  
3.40  
3.71  
4.03  
806  
796  
912  
1015  
1183  
1365  
1560  
1769  
1992  
2230  
2483  
2751  
1004  
1032  
1060  
1089  
1118  
1148  
1179  
1210  
1241  
839  
958  
942  
972  
873  
1134  
1323  
1527  
1745  
1978  
2227  
2491  
908  
1003  
1035  
1067  
1099  
1132  
1166  
942  
978  
1013  
1049  
1085  
EXTERNAL STATIC PRESSURE (in. wg)  
1.6  
AIRFLOW  
(CFM)  
1.2  
1.4  
1.8  
2.0  
Rpm  
Watts  
Bhp  
Rpm  
Watts  
Bhp  
Rpm  
Watts  
Bhp  
Rpm  
Watts  
Bhp  
Rpm  
Watts  
Bhp  
3750  
4000  
4250  
4500  
4750  
5000  
5250  
5500  
5750  
6000  
6250  
1203  
1222  
1242  
1264  
1286  
1310  
1335  
1360  
1386  
1413  
1440  
1562  
1724  
1900  
2089  
2290  
2507  
2737  
2981  
3241  
3514  
3803  
1.78  
1.96  
2.16  
2.38  
2.61  
2.86  
3.12  
3.40  
3.69  
4.00  
4.33  
1277  
1294  
1313  
1333  
1354  
1376  
1399  
1423  
1448  
1474  
1500  
1784  
1950  
2129  
2322  
2528  
2748  
2983  
3231  
3495  
3773  
4066  
2.03  
2.22  
2.43  
2.65  
2.88  
3.13  
3.40  
3.68  
3.98  
4.30  
4.63  
1349  
1364  
1381  
1399  
1419  
1440  
1461  
1484  
1508  
1532  
1558  
2010  
2180  
2362  
2558  
2769  
2992  
3230  
3483  
3750  
4032  
4330  
2.29  
2.48  
2.69  
2.91  
3.15  
3.41  
3.68  
3.97  
4.27  
4.59  
4.93  
1417  
1431  
1446  
1463  
1482  
1501  
1522  
1543  
2240  
2413  
2599  
2799  
3012  
3240  
3481  
3737  
2.55  
2.75  
2.96  
3.19  
3.43  
3.69  
3.97  
4.26  
1483  
1495  
1509  
1525  
1542  
1560  
2473  
2650  
2839  
3042  
3259  
3489  
2.82  
3.02  
3.23  
3.47  
3.71  
3.98  
LEGEND  
5. Static pressure losses (i.e., economizer) must be added to exter-  
nal static pressure before entering Fan Performance table. See  
Table 7 for accessory/FIOP static pressure information.  
6. Interpolation is permissible. Do not extrapolate.  
7. Maximum continuous bhp is 3.45 and the maximum continuous  
watts are 3065. Extensive motor and drive testing on these units  
ensures that the full horsepower range of the motor can be uti-  
lized with confidence. Using your fan motors up to the watts rating  
shown will not result in nuisance tripping or premature motor fail-  
ure. Unit warranty will not be affected.  
Bhp  
FIOP  
Watts  
Brake Horsepower Input to Fan  
Factory-Installed Option  
Input Watts to Motor  
NOTES:  
1. Boldface indicates standard operating range.  
2. indicates field-supplied motor and drive required.  
3. All other numbers indicate field-supplied drive required.  
4. Factory shipped motor drive range is 1201 to 1462 rpm. Other rpms  
require a field-supplied drive.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4 — Fan Performance Data, 48HJ017 Units  
EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
(CFM)  
0.2  
0.4  
0.6  
0.8  
1.0  
Rpm  
Watts  
Bhp  
Rpm  
Watts  
Bhp  
Rpm  
Watts  
Bhp  
Rpm  
Watts  
Bhp  
Rpm  
Watts  
Bhp  
4500  
4800  
5100  
5400  
5700  
6000  
6300  
6600  
6900  
7200  
7500  
630  
659  
688  
717  
748  
776  
804  
835  
863  
892  
923  
805  
943  
0.9  
1.1  
1.2  
1.4  
1.6  
1.8  
2.1  
2.4  
2.6  
2.9  
3.3  
741  
765  
789  
814  
842  
867  
892  
919  
946  
972  
1001  
1059  
1208  
1371  
1550  
1752  
1963  
2190  
2445  
2712  
2998  
3318  
1.2  
1.4  
1.5  
1.7  
2.0  
2.2  
2.5  
2.7  
3.0  
3.4  
3.7  
846  
865  
1341  
1497  
1668  
1856  
2067  
2289  
2526  
2793  
3072  
3371  
3704  
1.5  
1.7  
1.9  
2.1  
2.3  
2.6  
2.8  
3.1  
3.4  
3.8  
4.1  
945  
961  
1653  
1816  
1993  
2187  
2406  
2635  
2880  
3156  
3445  
3754  
4098  
1.9  
2.0  
2.2  
2.4  
2.7  
2.9  
3.2  
3.5  
3.9  
4.2  
4.6  
1039  
1052  
1064  
1079  
1096  
1112  
1129  
1149  
1169  
1189  
1213  
1993  
2163  
2345  
2546  
2770  
3004  
3256  
3540  
3835  
4152  
4506  
2.2  
2.4  
2.6  
2.8  
3.1  
3.4  
3.6  
4.0  
4.3  
4.6  
5.0  
1094  
1262  
1450  
1648  
1861  
2103  
2356  
2628  
2933  
885  
977  
907  
994  
930  
1015  
1034  
1053  
1076  
1098  
1120  
1146  
952  
975  
1000  
1024  
1049  
1076  
EXTERNAL STATIC PRESSURE (in. wg)  
1.6  
AIRFLOW  
(CFM)  
1.2  
1.4  
1.8  
2.0  
Rpm  
Watts  
Bhp  
Rpm  
Watts  
Bhp  
Rpm  
Watts  
Bhp  
Rpm  
Watts  
Bhp  
Rpm  
Watts  
Bhp  
4500  
4800  
5100  
5400  
5700  
6000  
6300  
6400  
6900  
7200  
7500  
1128  
1138  
1148  
1160  
1175  
1188  
1203  
1221  
1238  
1256  
1278  
2355  
2533  
2722  
2928  
3158  
3398  
3654  
3944  
4245  
4569  
4930  
2.6  
2.8  
3.0  
3.3  
3.5  
3.8  
4.1  
4.4  
4.8  
5.1  
5.5  
1211  
1219  
1228  
1238  
1251  
1262  
1275  
1290  
1305  
1322  
1341  
2734  
2921  
3119  
3332  
3569  
3814  
4075  
4370  
4676  
5006  
5373  
3.1  
3.3  
3.5  
3.7  
4.0  
4.3  
4.6  
4.9  
5.2  
5.6  
6.0  
1289  
1297  
1305  
1313  
1324  
1334  
1344  
1358  
1371  
1386  
1403  
3127  
3325  
3532  
3755  
3999  
4250  
4517  
4817  
5128  
5463  
5835  
3.5  
3.7  
4.0  
4.2  
4.5  
4.8  
5.1  
5.4  
5.7  
6.1  
6.5  
1363  
1370  
1377  
1385  
1395  
1403  
1412  
1424  
1436  
1449  
1465  
3531  
3742  
3961  
4192  
4445  
4704  
4976  
5283  
5598  
5938  
6316  
4.0  
4.2  
4.4  
4.7  
5.0  
5.3  
5.6  
5.6  
6.3  
6.6  
7.1  
1433  
1440  
1447  
1454  
1462  
1470  
1478  
1489  
1499  
1509  
1515  
3944  
4170  
4400  
4643  
4906  
5173  
5453  
5765  
6087  
6420  
6733  
4.4  
4.7  
4.9  
5.2  
5.5  
5.8  
6.1  
6.5  
6.8  
7.2  
7.5  
LEGEND  
5. Static pressure losses (i.e., economizer) must be added to exter-  
nal static pressure before entering Fan Performance table. See  
Table 7 for accessory/FIOP static pressure information.  
6. Interpolation is permissible. Do not extrapolate.  
7. Maximum continuous bhp is 5.9 and the maximum continuous watts  
are 5180. Extensive motor and drive testing on these units en-  
sures that the full horsepower range of the motor can be utilized  
with confidence. Using your fan motors up to the watts rating shown  
will not result in nuisance tripping or premature motor failure. Unit  
warranty will not be affected.  
Bhp  
FIOP  
Watts  
Brake Horsepower Input to Fan  
Factory-Installed Option  
Input Watts to Motor  
NOTES:  
1. Boldface indicates standard operating range.  
2. indicates field-supplied motor and drive required.  
3. All other numbers indicate field-supplied drive required.  
4. Factory shipped motor drive range is 1238 to 1494 rpm. Other rpms  
require a field-supplied drive.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 5 — Fan Performance Data, 48HJ025 Units  
EXTERNAL STATIC PRESSURE (in. wg)  
AIRFLOW  
(CFM)  
0.2  
0.4  
0.6  
0.8  
1.0  
Rpm  
Watts  
Bhp  
Rpm  
Watts  
Bhp  
Rpm  
Watts  
Bhp  
Rpm  
Watts  
Bhp  
Rpm  
Watts  
Bhp  
6000  
6500  
7000  
7500  
8000  
8500  
9000  
9500  
10000  
800  
853  
1732  
2134  
2596  
3123  
3717  
4385  
5129  
5955  
6865  
1.88  
2.32  
2.82  
3.39  
4.04  
4.76  
5.57  
6.47  
7.45  
891  
939  
2047  
2471  
2957  
3507  
4126  
4818  
5587  
6437  
7372  
2.22  
2.68  
3.21  
3.81  
4.48  
5.23  
6.07  
6.99  
8.00  
975  
1018  
1064  
1111  
1160  
1209  
1260  
1311  
1363  
2376  
2819  
3324  
3895  
4536  
5250  
6042  
6915  
7873  
2.58  
3.06  
3.61  
4.23  
4.93  
5.70  
6.56  
7.51  
8.65  
1055  
1094  
1136  
1179  
1225  
1271  
1323  
1369  
1419  
2728  
3185  
3707  
4295  
4954  
5688  
6501  
7395  
8376  
2.96  
3.46  
4.02  
4.66  
5.38  
6.18  
7.06  
8.03  
9.09  
1133  
1167  
1205  
1245  
1287  
1332  
1377  
1424  
1472  
3104  
3573  
4107  
4710  
5386  
6137  
6968  
7881  
8882  
3.37  
3.88  
4.46  
5.11  
5.85  
6.66  
7.57  
8.56  
9.64  
907  
989  
962  
1039  
1091  
1143  
1196  
1250  
1304  
1017  
1072  
1128  
1185  
1241  
EXTERNAL STATIC PRESSURE (in. wg)  
1.6  
AIRFLOW  
(CFM)  
1.2  
1.4  
1.8  
2.0  
Rpm  
Watts  
Bhp  
Rpm  
Watts  
Bhp  
Rpm  
Watts  
Bhp  
Rpm  
Watts  
Bhp  
Rpm  
Watts  
Bhp  
6000  
6500  
7000  
7500  
8000  
8500  
9000  
9500  
10000  
1208  
1239  
1273  
1309  
1349  
1390  
1433  
1478  
1524  
3504  
3983  
4529  
5143  
5833  
6600  
7446  
8378  
9396  
3.80  
4.32  
4.92  
5.58  
6.33  
7.17  
8.08  
9.10  
10.20  
1282  
1308  
1339  
1372  
1409  
1447  
1488  
3926  
4415  
4970  
5597  
6297  
7077  
7938  
4.26  
4.79  
5.40  
6.08  
6.84  
7.68  
8.62  
1353  
1376  
1403  
1434  
1467  
1504  
4368  
4866  
5432  
6067  
6779  
7571  
4.74  
5.28  
5.90  
6.59  
7.36  
8.22  
1421  
1442  
1467  
1494  
1529  
4826  
5337  
5911  
6558  
7313  
5.24  
5.79  
6.42  
7.12  
7.94  
1488  
1507  
1520  
1548  
5299  
5823  
6339  
7014  
5.75  
6.32  
6.88  
7.62  
LEGEND  
5. Interpolation is permissible. Do not extrapolate.  
6. Maximum continuous bhp is 10.2 for 208/230 and 575-v units and  
11.8 for 460-v units. The maximum continuous watts are 9510 for  
the 208/230 and 575-v units and 11,000 for the 460-v units. Ex-  
tensive motor and drive testing on these units ensures that the full  
horsepower range of the motor can be utilized with confidence.  
Using your fan motors up to the watts rating shown will not result  
in nuisance tripping or premature motor failure. Unit warranty will  
not be affected.  
Bhp  
FIOP  
Watts  
Brake Horsepower Input to Fan  
Factory-Installed Option  
Input Watts to Motor  
NOTES:  
1. Boldface indicates standard operating range.  
2. All other numbers indicates field-supplied drive required.  
3. Factory shipped motor drive range is 1323 to 1579 rpm. Other rpms  
require a field-supplied drive.  
4. Static pressure losses (i.e., economizer) must be added to exter-  
nal static pressure before entering Fan Performance table. See  
Table 7 for accessory/FIOP static pressure information.  
Table 6 — Air Quantity Limits  
UNIT 48HJ  
015  
MINIMUM CFM  
3,750  
MAXIMUM CFM  
6,250  
017  
4,500  
7,500  
025  
6,000  
10,000  
Fig. 24 — Fan Performance Using Accessory  
Power Exhaust  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 7 — Accessory/FIOP Economizer Static Pressure (in. wg)  
UNIT  
480HJ  
UNIT  
VOLTAGE  
ECONOMIZER  
PRESSURE DROP  
CFM  
3,750  
4,000  
5,000  
6,000  
7,500  
.03  
.03  
.05  
.07  
.10  
015, 017  
All  
6,000  
7,200  
.07  
.09  
.11  
.12  
025  
All  
9,000  
10,000  
LEGEND  
2. The static pressure must be added to external static pressure. The  
sum and the evaporator entering-air cfm should then be used in  
conjunction with the Fan Performance table to determine blower  
rpm, bhp, and watts.  
BHP  
FIOP  
Brake Horsepower  
Factory-Installed Option  
NOTES:  
1. The factory-assembled horizontal adapter substantially improves  
fan performance. See Fig. 24.  
Pressure switch closes and pilot valve no. 1 opens, allow-  
ing gas to flow to the first-stage pilot. Spark ignitor  
ignites pilot flame. Sensor detects flame and the main gas  
valve no. 1 opens. Gas flows to main burners and first-stage  
burners ignite. Spark igniter turns off.  
When sequence is complete, time-delay relay closes and  
evaporator fans start.  
Gas Heat — Verify gas pressures before turning on heat  
as follows:  
1. Turn off manual gas stop.  
2. Connect pressure gage to supply gas tap (See Fig. 13 on  
page 8).  
3. Connect pressure gage to manifold pressure tap on gas  
valve.  
4. Turn on manual gas stop and set thermostat to HEAT po-  
sition. After the unit has run for several minutes, verify  
that incoming pressure is 5.0 in. wg or greater, and that  
the manifold pressure is 3.5 in. wg. If manifold pressure  
must be adjusted, refer to Gas Valve Adjustment section  
on page 22.  
5. After unit has been in operation for 5 minutes, check tem-  
perature rise across the heat exchangers. See unit infor-  
mative plate for correct rise limits of the heat supplied.  
Air quantities may need to be adjusted to bring the actual  
rise to within the allowable limits.  
Second-Stage — On 2-stage units, with an additional heat-  
ing call, the second-stage thermostat closes. (The control re-  
lay [HR2] closes during the first stage of operation.) Pilot  
valve no. 2 opens, and the spark ignitor ignites pilot. The  
sensor detects a flame and energizes main gas valve coil  
no. 2, opening main gas valve no. 2. Gas flows to the main  
burners, and the second-stage burners ignite. The spark ignitor  
turns off.  
When the second-stage thermostat is satisfied, the second-  
stage gas valve closes.  
When the first-stage thermostat is satisfied, the first-stage  
gas valve closes. The induced-draft motor turns off, the time  
delay relay is deenergized, and the timer sequence begins.  
When the sequence is complete, the evaporator-fan motor  
turns off.  
Base Unit Operation  
COOLING, UNITS WITHOUT ECONOMIZER — When  
thermostat calls for cooling, terminals G and Y1 are ener-  
gized. The indoor (evaporator) fan contactor (IFC) and  
compressor contactor no. 1 (C1) are energized and evaporator-  
fan motor (IFM), compressor no. 1 (017,025) or unloaded  
compressor (015), and condenser fan start. The condenser-  
fan motors run continuously while unit is cooling. If the ther-  
mostat calls for a second stage of cooling by energizing Y2,  
compressor contactor no. 2 (C2) is energized and compres-  
sor no. 2 starts (017,025), or compressor no. 1 runs fully  
loaded (015).  
A freeze protection thermostat (FPT) is located on the  
evaporator coil. It detects frost build-up and locks out the  
compressors, allowing the coil to clear. Once frost has melted,  
the compressors can be reenergized by resetting the  
thermostat.  
COOLING, UNITS WITH ECONOMIZER — Upon a call  
for cooling, when outdoor ambient is above the changeover  
control setting, the economizer damper moves to VENT  
position. The compressors and evaporator and condenser fans  
energize and operate as per Cooling, Units Without Econo-  
mizer section above.  
Upon a first call for cooling, when outdoor ambient is be-  
low the changeover control setting, the evaporator fan starts  
and the economizer is fully open. The compressors remain  
off.  
Upon a second-stage call for cooling, compressor no. 1  
(017,025) or unloaded compressor (015) is energized and me-  
chanical cooling is integrated with economizer cooling. If  
the outdoor-air temperature drops below 50 F, a cooling lock-  
out switch prevents the compressors from running.  
When supply-air temperature drops below a fixed set point,  
the economizer damper modulates to maintain the tempera-  
ture at the fixed set point.  
HEATING, UNITS WITHOUT ECONOMIZER  
NOTE: The 48HJD015 units have 1 stage of heat, and the  
48HJE015, 48HJE017, and HJD025 units have 2 stages of  
heat.  
HEATING, UNITS WITH ECONOMIZER — Outdoor-air  
damper stays at VENT position while evaporator fan is  
operating.  
First Stage — Turn unit power on. Open manual gas line  
valve. Set thermostat system switch at HEAT or AUTO. po-  
sition and set fan switch to AUTO. position for heating.  
First-stage thermostat calls for heat. Time-delay relay for  
evaporator fan begins timer sequence. Induced-draft relay  
closes, and induced-draft motor starts.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICE  
Before performing service or maintenance operations on  
unit, turn off main power switch to unit. Electrical shock  
could cause personal injury.  
Cleaning — Inspect unit interior at beginning of each heat-  
ing and cooling season and as operating conditions require.  
Remove unit top panel and/or side panels for access to unit  
interior.  
MAIN AND PILOT BURNERS — At the beginning of each  
heating season, inspect for deterioration or blockage due to  
corrosion or other causes. Observe the pilot and main burner  
flames through view port (in condenser section), and adjust  
if necessary. Refer to Pilot Adjustment or Main Burners sec-  
tions on pages 22 and 23.  
Fig. 25 — Typical Gas Heating Section  
(48HJE015, 48HJE017, and 48HJD025 Shown)  
FLUE GAS PASSAGEWAYS — The flue collector box and  
heat exchanger cells may be inspected by removing heat ex-  
changer access panel (Fig. 4 and 5), flue box cover, and main  
burner assembly (Fig. 25). Refer to Main Burners section on  
page 23 for burner removal sequence. If cleaning is re-  
quired, remove heat exchanger turbulators (Fig. 26) and clean  
all parts with a wire brush.  
COMBUSTION-AIR BLOWER — Clean periodically to as-  
sure proper airflow and heating efficiency. Inspect blower  
wheel every fall and periodically during heating season. For  
the first heating season, inspect blower wheel bi-monthly to  
determine proper cleaning frequency.  
To inspect blower wheel, remove heat exchanger access  
panel. Shine a flashlight into opening to inspect wheel. If  
cleaning is required, remove motor and wheel assembly by  
removing screws holding motor mounting plate to top of com-  
bustion fan housing (Fig. 25 and 26). The motor and wheel  
assembly will slide up and out of the fan housing. Remove  
the blower wheel from the motor shaft and clean with a de-  
tergent or solvent. Replace motor and wheel assembly.  
EVAPORATOR COIL — Clean as required with commer-  
cial coil cleaner.  
CONDENSER COIL — Clean condenser coil annually and  
as required by location and outdoor-air conditions. Inspect  
coil monthly; clean as required.  
CONDENSATE DRAIN — Check and clean each year at  
start of cooling season. In winter, keep drains and traps dry.  
Fig. 26 — Typical Heating Section With  
Main Burners Removed  
(48HJE015, 48HJE017, and 48HJD025 Shown)  
FILTERS — Clean or replace at start of each heating and  
cooling season, or more often if operating conditions re-  
quire. Refer to Table 1 for type and size.  
OUTDOOR-AIR INLET SCREENS — Clean screens with  
steam or hot water and a mild detergent. Do not use dis-  
posable filters in place of screens.  
Lubrication  
COMPRESSORS — Each compressor is charged with the  
correct amount of oil at the factory. Observe the level in the  
sight glass immediately after shutdown while the oil is still  
warm. If the oil level is observed when the oil is cold, the  
level observed may be a mixture of oil and refrigerant which  
is not a true indication of the oil level. If oil level observed  
is not between the low limit and high limit levels as indi-  
cated in Fig. 27, add oil until it is in the correct range.  
Fig. 27 — Compressor Sight Glass Oil Level  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FAN SHAFT BEARINGS — For 015 units, the bearings are  
permanently lubricated. No field lubrication is required. For  
017 and 025 units, the bearings are of the pillow block type  
and have grease fittings. The bearing opposite the motor end  
has an extended tube line so it can be lubricated from the  
motor side. Lubricate the bearings twice annually.  
2. Loosen nuts on the 2 carriage bolts in the mounting base.  
Install jacking bolt and plate under motor base (bolt and  
plate are shipped in installer’s packet). Using bolt and  
plate, raise motor to top of slide and remove belt. Secure  
motor in this position by tightening the nuts on the car-  
riage bolts.  
Typical lubricants are given below:  
3. Loosen movable-pulley flange setscrew (see Fig. 28).  
MANUFACTURER  
LUBRICANT  
Texaco  
Mobil  
Sunoco  
Texaco  
Regal AFB-2*  
Mobilplex EP No. 1  
Prestige 42  
Multifak 2  
*Preferred lubricant because it contains rust and oxidation inhibitors.  
CONDENSER- AND EVAPORATOR-FAN MOTOR  
BEARINGS — The condenser- and evaporator-fan motors  
have permanently-sealed bearings, so no field lubrication is  
necessary.  
Evaporator Fan, 48HJ015 Units  
PERFORMANCE ADJUSTMENT — The 48HJ015 fan mo-  
tor pulleys are factory set for speed shown in Table 1.  
To change fan speeds:  
1. Shut off unit power supply.  
2. Loosen belt by loosening fan motor mounting plate nuts.  
3. Loosen movable-pulley flange setscrew (see Fig. 28).  
4. Screw movable flange toward fixed flange to increase speed  
and away from fixed flange to decrease speed. Increasing  
fan speed increases load on motor. Do not exceed maxi-  
mum speed specified in Table 1.  
Fig. 28 — Evaporator-Fan Alignment and  
Adjustment  
5. Set movable flange at nearest keyway of pulley hub and  
tighten setscrew.  
To align fan and motor pulleys:  
1. Loosen fan pulley setscrews.  
2. Slide fan pulley along fan shaft.  
3. Make angular alignment by loosening motor from mount-  
ing plate.  
SERVICE AND REPLACEMENT (See Fig. 29)  
NOTE: To remove belts only, follow Steps 1-7.  
1. Remove filter and supply-air section panels.  
2. Remove unit top cover.  
3. Remove coil guard.  
4. Loosen screws A and B on both sides of motor mount  
assembly.  
5. Loosen screw C.  
6. Rotate motor mount assembly (with motor attached) as  
far as possible away from evaporator coil.  
7. Remove belt.  
8. Rotate motor mount assembly back past original posi-  
tion toward evaporator coil.  
9. Remove motor mounting nuts D and E (both sides).  
10. Lift motor up through top of unit.  
11. Reverse above procedure to reinstall motor.  
12. Check and adjust belt tension as necessary.  
Evaporator Fan, 48HJ017,025 Units  
PERFORMANCE ADJUSTMENT — Fan motor pulleys are  
factory set for speed shown in Table 1.  
To change fan speeds:  
1. Shut off unit power supply.  
Fig. 29 — 48HJ015 Evaporator-Fan  
Motor Adjustment  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICE AND REPLACEMENT (See Fig. 30) — The  
48HJ017,025 units use a fan motor mounting system that  
features a slide-out motor mounting plate. To replace or serv-  
ice the motor, slide out the bracket.  
2. Turn the thermostat fan switch to the ON position. The  
damper will go to the vent position.  
3. Adjust the vent position with the minimum position ad-  
justment on the economizer motor control module. See  
Fig. 18.  
1. Remove the evaporator-fan access panel and the heat-  
ing control access panel.  
2. Remove the center post (located between the evaporator  
fan and heating control access panels) and all screws  
securing it.  
4. Set the system selector switch to COOL position and set  
the cooling temperature selector to its lowest setting.  
NOTE: The Cooling mode may also be simulated by  
removing the thermostat wires from terminals Y1 and  
Y2 and installing a jumper between terminals R and Y1.  
Refer to unit label diagram for terminal locations.  
3. Loosen nuts on the two carriage bolts in the motor mount-  
ing base.  
4. Using jacking bolt under motor base, raise motor to top  
of slide and remove belt. Secure motor in this position  
by tightening the nuts on the carriage bolts.  
5. Remove the belt drive.  
6. Remove jacking bolt and tapped jacking bolt plate.  
7. Remove the 2 screws that secure the motor mounting  
plate to the motor support channel.  
8. Remove the 3 screws from the end of the motor support  
channel that interfere with the motor slide path.  
9. Slide out the motor and motor mounting plate.  
10. Disconnect wiring connections and remove the 4 mount-  
ing bolts.  
11. Remove the motor.  
12. To install the new motor, reverse Steps 1-11.  
Belt Tension Adjustment — To adjust belt tension:  
1. Loosen fan motor bolts.  
2. a. 015 Units: Move motor mounting plate up or down  
for proper belt tension (12 in. deflection with one  
finger).  
b. 017,025 Units: Turn motor jacking bolt to move mo-  
tor mounting plate up or down for proper belt tension  
(38 in. deflection at midspan with one finger [9 lb force]).  
3. Tighten nuts.  
4. Adjust bolts and nut on mounting plate to secure motor  
in fixed position.  
NOTE: A 312-in. bolt and threaded plate are included in the installer’s  
packet. They can be added to the motor support channel below the  
motor mounting plate to aid in raising the motor.  
Condenser-Fan Adjustment  
48HJ015,017 UNITS (Fig. 31)  
1. Shut off unit power supply.  
Fig. 30 — 48HJ017,025 Evaporator-Fan  
Motor Section  
2. Remove access panel(s) closest to the fan to be  
adjusted.  
3. Loosen fan hub setscrews.  
4. Adjust the fan height on the shaft using a straightedge  
placed across the fan orifice.  
5. Tighten setscrews and replace panel(s).  
6. Turn on unit power.  
Fig. 31 — Condenser Fan Adjustment,  
48HJ015,017  
48HJ025 UNITS (Fig. 32)  
1. Shut off unit power supply.  
2. Remove fan top-grille assembly and loosen fan hub screws.  
3. Adjust fan height on unit, using a straightedge placed across  
the fan orifice.  
4. Tighten setscrews and replace rubber hubcap to prevent  
hub from rusting to motor shaft.  
5. Fill hub recess with permagum if rubber hubcap is  
missing.  
Economizer Adjustment — Refer to Tables 8 and 9  
for economizer checkout procedures. Make certain the outdoor-  
air damper is fully closed and the return-air damper is fully  
open before completing the following steps:  
Fig. 32 — Condenser-Fan Adjustment,  
48HJ025  
1. Turn on power to the unit.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. Set the outdoor-air thermostat (OAT), located in the econo-  
mizer section of the unit to 75 F.  
Unit panels must be in place when unit is operating dur-  
ing charging procedure.  
6. If the outdoor temperature is below 75 F, the econo-  
mizer will control the mixed air with the mixed-air sen-  
sor. If the outdoor air is above 75 F, place a jumper around  
the contacts of the OAT.  
7. Jumper terminal T to terminal T1 on the module (see  
Fig. 18). The economizer will go to the full open position.  
The outdoor-air damper will go to the full open posi-  
tion, and the return-air damper will go to the full closed  
position.  
8. Adjust mechanical linkage, if necessary, for correct po-  
sitioning. If may be necessary to remove the filters to  
adjust the linkage.  
9. Remove the jumper from around the contacts of the OAT  
if installed in Step 6. Remove the jumper from termi-  
nals T and T1 installed in Step 7.  
NO CHARGE — Use standard evacuating techniques. After  
evacuating system, weigh in the specified amount of  
refrigerant (refer to Table 1).  
LOW CHARGE COOLING — Using appropriate cooling  
charging chart (see Fig. 33-35), add refrigerant until condi-  
tions of the chart are met. Note that charging charts are dif-  
ferent from those normally used. Charts are based on charg-  
ing units to correct superheat for various operating conditions.  
An accurate pressure gage and temperature sensing device  
are required. Connect temperature sensing device to service  
port on suction line and insulate it so that outdoor ambient  
temperature does not affect reading. Indoor-air cfm must be  
within normal operating range of unit.  
TO USE COOLING CHARGING CHART — Take outdoor  
ambient temperature and read the suction pressure gage. Re-  
fer to appropriate chart to determine correct suction tem-  
perature. If suction temperature is high, add refrigerant. If  
suction temperature is low, carefully reclaim some of the charge.  
Recheck suction pressure as charge is adjusted.  
10. If the Cooling mode was simulated to operate the unit  
in Step 4, remove the jumper and reconnect the ther-  
mostat wires to terminals Y1 and Y2.  
Table 8 — Economizer Checkout Procedures  
Pilot Light — If pilots do not light as described in Gas  
Heat section on page 17, be sure that pilot orifice is not ob-  
structed, then check for spark ignitor malfunctions as fol-  
lows:  
TEST PROCEDURE  
RESULTS  
A. Disconnect power at TR and  
TR1. Disconnect jumper be-  
tween P and P1. See Fig. 18.  
B. Jumper TR to 1.  
C. Jumper T1 to T.  
1. Shut off control supply power to ignitor control pack (ICP).  
D. Disconnect outdoor-air ther-  
mostat connections from SO  
and +. Factory-installed  
1
1
2. Check that spark gap is 8 in. Ϯ 32 inch.  
3. Check that ICP is securely grounded.  
4. Check that high-voltage lead is securely connected be-  
tween ICP and electrode body.  
800 ohm resistor should re-  
main connected to SR and +.  
E. Reconnect power to terminals  
TR and TR1.  
1. LED (light-emitting diode)  
should be off.  
2. Motor is in closed position.  
5. Restore power to ICP. Check that 24 v is supplied  
to terminal TH of ICP.  
TEST PROCEDURE  
RESULTS  
6. Check unit label diagram for correct terminal usage if any  
wires are removed.  
Disconnect factory-installed re-  
sistor from terminals SR  
and +.  
1. LED (light-emitting diode)  
should be on.  
2. Motor drives toward open.  
Table 9 — High and Low Outdoor-Air Temperature  
TEST PROCEDURE  
RESULTS  
A. Reconnect factory-installed  
800 ohm resistor between ter-  
minals SR and +.  
B. Connect 1200 ohm checkout  
resistor between terminals SO  
and +.  
C. Turn set point potentiometer  
to position A.  
Low outdoor-air temperature  
test results:  
1. LED (light-emitting diode)  
should be on.  
2. Motor drives toward open.  
D. Turn set point potentiometer  
to position D.  
E. Disconnect 1200 ohm check-  
out resistor.  
High outdoor-air temperature  
test results:  
1. LED should be off.  
2. Motor drives toward closed.  
Power Failure — Dampers have a spring return. In event  
of power failure, dampers will return to fully closed position  
until power is restored. Do not manually operate damper  
motor.  
Refrigerant Charge — Amount of refrigerant charge  
is listed on unit nameplate and in Table 1. Refer to Carrier  
GTAC II; Module 5; Charging, Recovery, Recycling, and Rec-  
lamation section for charging methods and procedures.  
Fig. 33 — Cooling Charging Chart, 48HJ015  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7. Check for proper burner operation by cycling the burn-  
ers. Wait 30 seconds between burner cycles.  
8. Check that all unit panels are in place before leaving unit.  
Gas Valve Adjustment  
NATURAL GAS — The gas valve opens and closes in re-  
sponse to the thermostat or limit control.  
When power is supplied to valve terminals 3 and 4, the  
pilot valve opens to the preset position. When power is sup-  
plied to terminals 1 and 2, the main valve opens to its preset  
position.  
The regular factory setting is stamped on the valve body  
(3.5 in. wg).  
To adjust regulator:  
1. Set thermostat at setting for no call for heat.  
2. Turn main gas valve to OFF position.  
3. Remove 18-in. pipe plug from manifold or gas valve pres-  
sure tap connection. Install a suitable pressure-measuring  
device.  
4. Set main gas valve to ON position.  
5. Set thermostat at setting to call for heat.  
6. Remove screw cap covering regulator adjustment screw  
(See Fig. 36).  
7. Turn adjustment screw clockwise to increase pressure or  
counterclockwise to decrease pressure.  
Fig. 34 — Cooling Charging Chart, 48HJ017  
8. Once desired pressure is established, set thermostat set-  
ting for no call for heat, turn off main gas valve, remove  
1
pressure-measuring device and replace 8-in. pipe plug  
and screw cap.  
Fig. 36 — Gas Valve  
VIEW  
PORT  
PRIMARY AIR  
SHUTTER  
FLUE BOX  
COVER  
Fig. 35 — Cooling Charging Chart, 48HJ025  
Pilot Adjustment  
1. Set system selector switch at OFF position to shut off unit.  
Turn off power to unit.  
2. Remove screw cap cover on pilot gas valve to expose  
adjusting screw (See Fig. 36).  
3. Turn valve knobs to pilot position.  
4. Turn on power to unit. Set system selector switch to HEAT  
position and set thermostat to a setting that will call for  
heat. Pilot ignites.  
5. With a small screwdriver, turn adjustment screw until flame  
fully engulfs sensor. Flame can be observed through view  
port (Fig. 37).  
6. Turn off power to unit. Replace cap on pilot gas valve.  
Return valve knob(s) to original position.  
MAIN BURNER  
SECTION  
Fig. 37 — Typical Heating Section  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
in the crankcase when the compressor is idle. Since power  
for the crankcase heaters is drawn from the unit incoming  
power, main unit power must be on for the heaters to be  
energized.  
Main Burners — For most applications, main burners  
are factory set and should require no adjustment. However,  
if burner adjustment is necessary:  
1. Perform pilot adjustment.  
IMPORTANT: After a prolonged shutdown or serv-  
ice job, energize the crankcase heaters for 24 hours  
before starting the compressors.  
2. Turn gas valve to ON position. Allow unit to operate at  
least 15 minutes with burner access panel in place.  
3. Remove access panel.  
4. Loosen primary air shutter (Fig. 37) and adjust to a mini-  
5
Compressor Lockout — If any of the safeties (high-, low-  
pressure, freeze protection thermostat, compressor internal  
thermostat) trip, or if there is loss of power to the compres-  
sors, the cooling lockout (CLO) will lock the compressors  
off. To reset, manually move the thermostat setting.  
EVAPORATOR-FAN MOTOR PROTECTION — A manual  
reset, calibrated trip, magnetic circuit breaker protects against  
overcurrent. Do not bypass connections or increase the size  
of the breaker to correct trouble. Determine the cause and  
correct it before resetting the breaker.  
mum opening of 8 inch.  
5. Retighten primary air shutter and reinstall access panel.  
To check ignition of main burners and fan switch opera-  
tion, move thermostat dial above and below room tempera-  
ture several times, pausing at least one minute between cycles.  
MAIN BURNER REMOVAL  
1. Shut off (field-supplied) manual main gas valve.  
2. Shut off power to unit.  
3. Remove unit control box/gas valve access panel, burner  
section access panel, and center post (Fig. 4 and 5).  
4. Disconnect pilot ignitor and pilot proving sensor leads at  
ICP, rollout switch leads at switch, and pilot tube gas con-  
nection(s) at the pilot orifice.  
5. Disconnect gas connection(s) from between gas valve(s)  
and main burners.  
6. Remove 2 screws securing burner assembly to base unit.  
7. Slide burner assembly out of unit.  
CONDENSER-FAN MOTOR PROTECTION — Each  
condenser-fan motor is internally protected against  
overtemperature.  
HIGH- AND LOW-PRESSURE SWITCHES — If either  
switch trips, or if the compressor overtemperature switch ac-  
tivates, that refrigerant circuit will be automatically locked  
out by the CLO. To reset, manually move the thermostat  
setting.  
FREEZE PROTECTION THERMOSTAT (FPT) — An  
FPT is located on the evaporator coil. It detects frost  
build-up and turns off the compressor, allowing the coil to  
clear. Once the frost has melted, the compressor can be  
reenergized by resetting the CLO from the thermostat.  
Filter Drier — Replace whenever refrigerant system is  
exposed to atmosphere.  
Protective Devices  
COMPRESSOR PROTECTION  
Relief Devices — All units have relief devices to pro-  
tect against damage from excessive pressures (i.e., fire). These  
devices protect the high and low side.  
Overcurrent — Each compressor has one manual reset, cali-  
brated trip, magnetic circuit breaker. Do not bypass connec-  
tions or increase the size of the circuit breaker to correct trouble.  
Determine the cause and correct it before resetting the breaker.  
Overtemperature — Each compressor has an internal pro-  
tector to protect it against excessively high discharge gas  
temperatures.  
Control Circuit, 24-V — This control circuit is pro-  
tected against overcurrent by a 3.2-amp circuit breaker. Breaker  
can be reset. If it trips, determine cause of trouble before  
resetting.  
Replacement Parts — A complete list of replacement  
parts may be obtained from any Carrier distributor upon  
request.  
Crankcase Heater— Each compressor has a 125-watt crank-  
case heater to prevent absorption of liquid refrigerant by oil  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 38 — Typical Wiring Schematic (48HJ025 Shown)  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 38 — Typical Wiring Schematic (48HJ025 Shown) (cont)  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 39 — Typical Component Arrangement (48HJ025 Shown)  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LEGEND FOR FIG. 38 and 39  
AHA  
BKR W/AT  
C
Adjustable Heat Anticipator  
Breaks with Amp Turns  
Contactor, Compressor  
Circuit Breaker  
IFM  
IFR  
Indoor (Evaporator)  
Fan Motor  
TH  
TRAN  
Thermostat Heating  
Transformer  
Indoor (Evaporator)  
Fan Relay  
Terminal (Marked)  
CB  
CC  
CH  
Cooling Compensator  
Crankcase Heater  
Compressor Lockout  
Compressor Lockout Switch  
Compressor Motor  
Control Relay  
IP  
L
LOR  
LPS  
LS  
MAT  
MGV  
NEC  
OAT  
OFC  
Internal Protector  
Light  
Lockout Relay  
Low-Pressure Switch  
Limit Switch  
Mixed-Air Thermostat  
Main Gas Valve  
National Electrical Code  
Outdoor-Air Thermostat  
Outdoor (Condenser)  
Fan Contactor  
Outdoor (Condenser)  
Fan Motor  
Pilot Gas Valve  
Plug Assembly  
Primary  
Pressure Switch  
Quadruple Terminal  
Relay  
Terminal (Unmarked)  
CLO  
CLS  
COMP  
CR  
Terminal Block  
Splice  
CT  
Current Transformer  
Damper Motor  
DM  
Splice (Marked)  
DU  
Dummy Terminal  
Equipment  
EQUIP  
FPT  
Freeze Protection  
Thermostat  
Splice (Field Supplied)  
OFM  
FU  
Fuse  
Ground  
Factory Wiring  
GND  
HPS  
HR  
HV  
PGV  
PL  
PRI  
PS  
QT  
R
RS  
SN  
SW  
TB  
TC  
TDR  
High-Pressure Switch  
Heat Relay  
Field Control Wiring  
Field Power Wiring  
Accessory or Optional Wiring  
High Voltage  
Ignitor  
I
ICP  
IDM  
IDR  
IFC  
Ignitor Control Pack  
Induced-Draft Motor  
Induced-Draft Relay  
Indoor (Evaporator)  
Fan Contactor  
Rollout Switch  
Sensor  
Switch  
Terminal Block  
Thermostat Cooling  
Time Delay Relay  
To Indicate Common Potential Only,  
Not To Represent Wiring  
IFCB  
Indoor (Evaporator)  
Fan Circuit Breaker  
NOTES:  
5. CB must-trip amps are equal to or less than 140% full load amps.  
6. Number(s) indicates the line location of used contacts. A bracket  
over (2) numbers signifies a single-pole, double-throw contact. An  
underlined number signifies a normally-closed contact. A plain (no  
line) number signifies a normally-open contact.  
7. The CLO locks out the compressor to prevent short cycling on com-  
pressor overload and safety devices. Before replacing CLO, check  
these devices.  
1. Compressor and fan motors thermally protected; 3-phase motors  
protected against primary single-phasing conditions.  
2. If any of the original wire furnished must be replaced, it must be  
replaced with type 90 C wire or its equivalent.  
3. Jumpers are omitted when unit is equipped with economizer.  
4. Set thermostat heat anticipator(s):  
UNIT  
W1  
W2  
VOLTAGE  
48HJD015  
1.20  
All  
48HJD025, HJE015,  
HJE017  
1.20  
0.60  
All  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PACKAGED SERVICE TRAINING  
Our packaged service training programs provide an excellent way to increase your knowledge of the  
equipment discussed in this manual. Product programs cover:  
• Unit Familiarization  
• Installation Overview  
• Maintenance  
• Operating Sequence  
A large selection of product, theory, and skills programs is available. All programs include a video  
cassette and/or slides and a companion booklet. Use these for self teaching or to conduct full training  
sessions.  
For a free Service Training Material Catalog (STM), call 1-800-962-9212. Ordering instructions are  
included.  
Copyright 1995 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book 1  
PC 111  
Catalog No. 534-807  
Printed in U.S.A.  
Form 48HJ-9SI  
Pg 30  
2-95  
Replaces: 48HJ-5SI  
Tab 1a  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
START-UP CHECKLIST  
MODEL NO.:  
DATE:  
SERIAL NO.:  
TECHNICIAN:  
PRE-START-UP:  
VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT  
REMOVE ALL SHIPPING HOLDDOWN BOLTS AND BRACKETS PER INSTRUCTIONS  
VERIFY INSTALLATION OF ECONOMIZER HOOD  
VERIFY INSTALLATION OF EXHAUST HOOD  
VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTRUCTIONS  
VERIFY THAT ALL ELECTRICAL CONNECTIONS AND TERMINALS ARE TIGHT  
CHECK GAS PIPING FOR LEAKS  
CHECK THAT INDOOR-AIR FILTER IS CLEAN AND IN PLACE  
VERIFY THAT UNIT IS LEVEL  
CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE, AND VERIFY SETSCREW  
IS TIGHT  
VERIFY THAT FAN SHEAVES ARE ALIGNED AND BELTS ARE PROPERLY TENSIONED  
START-UP  
ELECTRICAL  
SUPPLY VOLTAGE L1-L2  
L2-L3  
L3-L1  
COMPRESSOR AMPS — COMPRESSOR NO. 1 L1  
— COMPRESSOR NO. 2 L1  
L2  
L2  
L3  
L3  
SUPPLY FAN AMPS  
EXHAUST FAN AMPS  
TEMPERATURES  
OUTDOOR-AIR TEMPERATURE  
F DB (Dry Bulb)  
RETURN-AIR TEMPERATURE  
COOLING SUPPLY AIR  
F DB  
F
WB (Wet Bulb)  
F
F
GAS HEAT SUPPLY AIR  
PRESSURES  
GAS INLET PRESSURE  
GAS MANIFOLD PRESSURE  
REFRIGERANT SUCTION  
REFRIGERANT DISCHARGE  
IN. WG  
IN. WG  
PSIG  
STAGE NO. 1  
CIRCUIT NO. 1  
CIRCUIT NO. 1  
STAGE NO. 2  
IN. WG  
PSIG  
PSIG  
CIRCUIT NO. 2  
CIRCUIT NO. 2  
PSIG  
VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS ON PAGES 21 AND 22  
GENERAL  
ECONOMIZER MINIMUM VENT AND CHANGEOVER SETTINGS TO JOB REQUIREMENTS  
Copyright 1995 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book 1  
PC 111  
Catalog No. 534-807  
Printed in U.S.A.  
Form 48HJ-9SI  
Pg CL-1  
2-95  
Replaces: 48HJ-5SI  
Tab 1a  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Belkin Switch F1DA116T User Manual
Blue Rhino Gas Grill NPG230 User Manual
Blue Rhino Patio Heater EWTS8119L User Manual
Bradford White Corp Water Heater Commercial Electric Energy Saver Medium Duty E32 Series Models User Manual
Bravo View Water Pump B409 User Manual
BRK electronic Network Card ADF Adapter User Manual
BRK electronic Smoke Alarm 4000LB User Manual
Broan Range RM533604 User Manual
Bush Hog Automobile Parts M146 User Manual
Califone Portable Speaker PA916 User Manual