50XT
Infinity 15t SEER Single---Packaged Heat Pump System
with Puronr (R---410A) Refrigerant
Single Phase
2---5 Nominal Tons (Sizes 024---060)
Product Data
Comfort Heat Pump System with IdealHumidityt featuring
Infinityt control variable--speed blower motor and two--stage
cooling and heating that provides greater comfort, humidity
control, and energy efficiency.
Variable--speed blower motors provide better comfort and energy
efficiency. You can expect up to 30 times better dehumidification;
economical constant airflow which provides improved indoor air
quality and more even temperatures from room to room; and
reduced indoor noise due to lower air velocity. In addition, you’ll
realize improved installation flexibility with 3 different airflow
choices for best overall comfort.
Easy installation
Factory--assembled package is a compact, fully self--contained heat
pump unit that is pre--wired, pre--piped, and pre--charged for
minimum installation expense. 50XT units are available in a
variety of standard capacity ranges. Units install easily on a rooftop
or at ground level.
Durable, dependable components
Compressors have two stages of cooling and heating and are
designed for high efficiency. Each compressor is hermetically
sealed against contamination to help promote longer life and
dependable operation. Vibration isolation provides quiet operation.
Compressors have internal high--pressure and overcurrent
protection.
A05307
Fig. 1 -- Unit 50XT
Convertible duct configuration
Single--Packaged Products with energy--saving features and
Puron refrigerant.
S Up to 15.5 SEER
Unit is designed for easy use in either downflow or horizontal
applications. Each unit is easily converted from horizontal to
downflow with two duct covers (available as an accessory).
Downflow operation is easily provided in the field to allow vertical
ductwork connections. The basepan utilizes knockout style seals
on the bottom openings to ensure a positive seal in the horizontal
airflow mode.
®
S Up to 8.0 HSPF
S Up to 12 EER at 95°F (35°C) OD
S Low Sound Levels
S Variable--Speed Blower (Standard)
S Factory--Installed TXV
Direct--drive, variable--speed blower motor is standard on all
50XT models.
S Two--stage cooling and heat pump operation
Direct--drive, PSC condenser fan motors are designed to help
reduce energy consumption and provide for cooling operation
down to 55°F (12.7°C) outdoor temperature. Low--ambient
cooling is available below 55°F (12.7°C) when low--ambient
FEATURES/BENEFITS
One--piece Heat Pump unit with optional electric heater, low
installation cost, dependable performance and easy maintenance.
®
cooling is enabled in the User Interace (UI). Motormaster II
low--ambient kit is not required.
Infinityt User Interface is designed to work as a system with
Carrier’s single--packaged product.
Refrigerant system is designed to provide dependability. Liquid
refrigerant filter driers are used to promote clean, unrestricted
operation. Each unit leaves the factory with a full Puron refrigerant
charge. Refrigerant service connections make checking operating
pressures easier.
Efficient operation
High--efficiency design with SEERs (Seasonal Energy Efficiency
Ratio) of up to 15.5.
®
Puron environmentally--sound refrigerant is Carrier’s unique
refrigerant designed to help protect the environment. Puron is an
HFC refrigerant which does not contain chlorine that can harm the
ozone layer. Puron refrigerant is in service in millions of systems
proving highly reliable, environmentally sound performance.
Indoor and outdoor coils are computer designed for optimum
heat transfer and cooling efficiency. The indoor coil is fabricated
from copper tube and aluminum fins and is located inside the unit
1
Download from Www.Somanuals.com. All Manuals Search And Download.
MODEL NUMBER NOMENCLATURE
50XT
024
– – –
3
0
1
– –
Options
BT - AL evap, vinyl condens
CC - AL evap, CU condens
CU - CU evap & condens
TP - Base unit with tin plated
indoor coil hairpins
Type of Unit
50XT - Packaged
Electric Heat Pump
TV - TP with vinyl coating on outdoor coil
TC - TP with AL indoor coil and
CU/CU outdoor coil
Nominal Cooling Capacity
024 - 2 Ton
030 - 2.5 Ton
036 - 3 Ton
042 - 3.5 Ton
048 - 4 Ton
Only used if ordering an option
060 - 5 Ton
Packaging
N/A
Series
LEGEND
Electrical Supply
AL - Aluminum
CU - Copper
3- 208/230-1-60
ARI* CAPACITIES
Cooling Capacities and Efficiencies
UNIT
50XT
NOMINAL
TONS
STANDARD CFM (High/Low Stage)
(Cooling & Heating)
NET COOLING CAPACITIES (Btuh)
(High/Low Stage)
SEER‡
EER @A{
024
030
036
042
048
060
2
2--1/2
3
3--1/2
4
800 / 600
1000 / 700
1200 / 850
1500 / 975
1600 / 1100
1750 / 1200
22,600 / 17,600
28,600 / 21,400
34,600 / 24,400
40,500 / 29,000
46,000 / 33,400
57,000 / 40,500
11.4
11.6
12
11.6
11
15.5
15.0
15.0
15.0
15.0
14.5
5
11
Heating Capacities and Efficiencies
HIGH HEAT CAPACITY
(BTUH) @ 47°F (8.3°C)
(High/Low Stage)
HIGH HEAT COP
LOW HEAT CAPACITY
(BTUH) @ 17°F (-8.3°C)
(High/Low Stage)
LOW HEAT COP
@ 17°F (-8.3°C)
(High/Low Stage)
UNIT
50XT
@ 47°F (8.3°C)
(High/Low Stage)
HSPF‡
024
030
036
042
048
060
20,800 / 16,800
27,600 / 20,400
33,600 / 23,000
39,500 / 27,600
45,500 / 32,200
56,000 / 39,500
3.3 / 3.2
3.5 / 3.5
3.4 / 3.4
3.6 / 3.5
3.3 / 3.5
3.2 / 3.3
11,600 / 8,400
14,000 / 9,600
17,200 / 11,200
20,600 / 14,200
25,000 / 15,200
30,800 / 20,400
2.2 / 1.8
2.1 / 1.9
2.4 / 1.7
2.3 / 2.0
2.4 / 1.9
2.2 / 1.9
8.0
8.0
8.0
8.0
8.0
8.0
{ ”A” conditions---80°F (26.6°C) indoor db/67°F (19.4°C) indoor wb & 95°F (35°C) outdoor db.
}
Rated in accordance with U.S. Government DOE (Department of Energy) test procedures and/or ARI Standards 210/240.
** Tested in accordance with ARI Standard 270---95 (not listed in ARI).
NOTES:
1. Ratings are net values, reflecting the effects of circulating fan heat. Ratings are based on:
Cooling Standard: 80°F (26.6°C) db, 67°F (19.4°C) wb indoor entering ---air temperature and 95°F (35°C) db outdoor entering---air temperature.
2. Before purchasing this appliance, read important energy cost and efficiency information available from your retailer.
LEGEND
dBA—Sound Levels (decibels)
db—Dry Bulb
SEER—Seasonal Energy Efficiency Ratio
wb—Wet Bulb
COP—Coefficient of Performance
HSPF—Heating Season Performance Factor
3
Download from Www.Somanuals.com. All Manuals Search And Download.
PHYSICAL DATA
UNIT SIZE
024
2
405
184
030
2 --- 1/2
435
036
3
464
210
042
3 --- 1/2
476
048
4
492
223
060
5
535
243
NOMINAL CAPACITY (ton)
OPERATING WEIGHT (lb)
(kg)
197
216
COMPRESSOR
Two --- Stage Scr ol l
REFRIGERANT: PURON (R---410A) Quantity (lb)
10.3
4.7
11.5
5.2
9.7
4.4
14.0
6.4
15.5
7.0
16.0
7.3
(kg)
EXPANSION DEVICE---HEATING
ORIFICE OD (in.) --- Left
ORIFICE OD (in.) --- Right
AccuRater
0.038
0.038
0.035
0.035
0.040
0.042
0.038
0.046
0.046
0.046
0.042
EXPANSION DEVICE---COOLING
Size
TXV
2 Ton
3 Ton
3 Ton
4 Ton
4 Ton
5 Ton
Part Number
EA36YD129
EA36YD139
EA36YD139
EA36YD149
EA36YD149
EA36YD159
OUTDOOR COIL
Rows…Fins/in.
Face Area (sq. ft.)
OUTDOOR FAN
Nominal Cfm
2…21
13.6
2…21
15.3
2…21
17.5
2…21
19.4
2…21
19.4
2…21
23.3
2700
22
559
2700
22
559
2800
22
559
2800
22
559
3300
22
559
3300
22
559
Diameter (in.)
(mm)
Motor HP (RPM)
INDOOR COIL
Rows…Fins/in.
Face Area (sq. ft.)
INDOOR FAN
Nominal Airflow (Cfm)
Comfort
1/8 (825)
1/8 (825)
1/8 (825)
1/8 (825)
1/4 (1100)
1/3 (1110)
3…17
3.7
3…17
3.7
3…17
4.7
3…17
4.7
3…17
5.7
4…17
5.7
Variable based on Comfort Settings (see User Interface instructions for more information).
Efficiency
Max
700
800
875
1000
1050
1200
1225
1400
1400
1600
1750
2000
Size (in.)
10x10
254x254
10x10
254x254
11x10
279x254
11x10
279x254
11x10
279x254
11x10
279x254
(mm)
Motor HP (RPM)
1/2
1/2
3/4
3/4
3/4
1
HIGH---PRESSURE SWITCH (psig)
Cutout
670 ± 10
Reset (Auto)
470 ± 25
HIGH---PRESSURE SWITCH 2 (psig)
(Compressor Solenoid)
Cutout
565 ± 15
455 ± 15
Reset (Auto)
LOS S --- OF --- CHARGE /LOW --- PRE S SU RE SWIT C H
(Liquid Line) (psig)
Cutout
Reset (Auto)
23 ± 5
55 ± 5
RETURN---AIR FILTERS Throwaway (in.)*
(mm)
20x24x1
508x610x25
24x30x1
610x762x25
24x36x1
610x914x25
*Recommended filter sizes for field---installed air filter grilles mounted on the wall or ceiling of the conditioned structure. Required filter sizes shown are based
on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 ft/minute for throwaway type or
450 ft/minute for high---capacity type. Air filter pressure drop for non---standard filters must not exceed 0.08 IN. WC.
ISO 9001:2000
REGISTERED
A--WEIGHTED SOUND POWER LEVEL (dBA)
STANDARD
RATING
(dBA)
TYPICAL OCTAVE BAND SPECTRUM (dBA) (without tone adjustment)
MODEL 50XT
125
250
500
1000
2000
4000
8000
024
030
036
042
048
060
75
75
75
75
78
78
58.8
58.8
60.7
56.7
62.4
63.5
63.5
63.5
63.3
62.8
69.9
67.6
67.2
67.2
66.8
67.8
71.3
71.8
66.9
66.9
66.5
67.4
73.4
75.5
63.7
63.7
64.2
63.7
70.0
71.0
58.3
58.3
60.3
57.7
66.3
68.1
50.0
50.0
53.0
50.8
60.1
59.9
NOTE: Tested in accordance with ARI Standard 270---95 (not listed in ARI).
4
Download from Www.Somanuals.com. All Manuals Search And Download.
OPTIONS AND ACCESSORIES
Factory--installed options
compartment. Heater sizes range from 5.0 to 20.0 kW. The electric
heater design allows the use of a single--point power supply for the
entire unit, resulting in lower installed costs.
Coil options include tin--plated* indoor hairpins, copper/copper
and vinyl--coated construction for refrigerant coils. Units are
shipped standard with copper tube/aluminum fin construction. See
model number nomenclature for coil options.
Flat roof curbs in both 8 in. (203 mm) and 14 in. (256 mm) sizes
are available for roof mounted applications.
*Tin--plated indoor coils are built with special hairpins that are
designed to resist both general pitting corrosion and excessive
indoor corrosion (Formicary Corrosion).
Square--to--round duct transition kit enables 024--048 size units
to be fitted to 14 in. round ductwork.
Infinity User Interface coupled with the system’s variable--speed
indoor blower delivers Carrier’s patented IdealHumidity
technology that allows for even greater humidity control. Along
with more precisely controlling temperature and humidity, the
Infinity User Interface offers full seven--day programmability
allowing you to further customize your comfort and energy
savings.
Field--installed accessories
Manual Air Damper (25% open)
Electric Heaters
Filter Rack
Flat Roof Curbs (8--in. and 14--in.) (203 mm and 256 mm)
Square--to--Round Duct Transition Kit
Infinityt User Interface
Crankcase Heater
Lifting Kit
Lifting kit includes 4 metal brackets that are available to assist in
lifting this product onto a roof application.
Crankcase heater
provides anti--floodback protection for
low--load cooling applications.
Compressor Hard Start Kit
Filter rack
features easy installation, serviceability, and
high--filtering performance for vertical or horizontal applications.
Manual outside air damper includes hood and filter rack with
adjustable damper blade for up to 25% outdoor air.
Electric heaters provide additional heat in the unit when required.
Each package has a heater module that slides into the controls
Compressor hard start kit assists compressor start--up by
providing additional starting torque on single phase units and
prolongs compressor motor life.
Electric Heaters
NOMINAL
USED WITH SIZES
CATALOG
ORDERING NO.
CAPACITY
(kW)
FUSED
STAGES
24
30
36
42
48
60
208/240 — SINGLE PHASE (60 Hz)
CPHEATER080A00
CPHEATER081A00
CPHEATER083A00
CPHEATER085A00
CPHEATER087A00
CPHEATER089A00
NOTE
3.8 / 5.0
3.8 / 5.0
NO
YES
YES
YES
YES
YES
1
1
1
1
2
2
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
5.4 / 7.2
X
X
X
X
X
X
X
X
7.5 / 10.0
11.3 / 15.0
15.0 / 20.0
Electric heaters are rated at 240v. Refer to Multiplication Factors table for other voltages.
X=Approved combination
5
Download from Www.Somanuals.com. All Manuals Search And Download.
FILTER RACK
MANUAL OUTSIDE AIR DAMPER
BEND FLANGE AT 90°-SCREW TO
DIVIDER WITH 1-IN. SCREW
REPLACEMENT
PANEL
MANUAL OUTSIDE
AIR HOOD
TOP FILTER RACK
EVAPORATOR
COIL
DAMPER
BLADE
BOTTOM FILTER
RACK
6
Download from Www.Somanuals.com. All Manuals Search And Download.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
ACCESSORY DIMENSIONS
HVACunit
base
HVAC unit
base
Gask eting
inner flange*
Screw
(NOTE A)
Screw
(NOTE A)
Gasketing
inner flange*
*Gasketing
outer flange
*Gasketing
outer flange
Wood nailer*
Wood nailer*
Flashing field
supplied
Flashing field
supplied
Roof curb*
Roof curb*
Insulation(field
supplied)
Insulation(field
supplied)
Roofing material
field supplied
Roofing material
field supplied
Ductwork
field supplied
Ductwork
field supplied
Cant strip
field supplied
Cant strip
field supplied
Roof
Roof
*Provided with roof curb
*Provided with roof curb
Roof Curb for Small Cabinet
Roof Curb for Large Cabinet
Note A: When unit mounting screw is used,
retainer bracket must also be used.
Note A: When unit mounting screw is used,
retainer bracket must also be used.
E
G
F
Supply opening
(B x C)
G
BTyp.
D
CTyp.
F
R/A
S/A
A
Gasket around
duct
D
E
Short
Support
Insulated
deck pan
Gasket around
outer edge
Insulated
deck pan
Long
Support
Return opening
(B X C)
A05308
CATALOG
NUMBER
A
B
C
D
E
F
G
UNIT SIZE
024-030
036-060
IN. (MM)
IN. (MM)
IN. (MM)
IN. (MM)
IN. (MM)
IN. (MM)
IN. (MM)
CPRFCURB006A00
CPRFCURB007A00 14 (356)
CPRFCURB008A00
CPRFCURB009A00 14 (356) 16--3/16 (411) 17--3/8 (441) 40--1/4 (1022) 41--15/16 (1065) 44--7/16 (1129)
8 (203)
11 (279)
11 (279)
16--1/2 (419)
16--1/2 (419)
28--3/4 (730)
28--3/4 (730)
30--3/8 (771)
30--3/8 (771)
44--5/16 (1126) 45--15/16 (1167)
44--5/16 (1126) 45--15/16 (1167)
8 (203) 16--3/16 (411) 17--3/8 (441) 40--1/4 (1022) 41--15/16 (1065) 44--7/16 (1129)
46--1/16 (1169)
46--1/16 (1169)
NOTES:
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied, as required, to unit being installed.
3. Roof curb is made of 16--gauge steel.
4. Attach ductwork to curb (flanges of duct rest on curb).
5. Insulated panels: 1--in. (25 mm) thick fiberglass 1 lb. density.
6. When unit mounting screw is used (see Note A), a retainer bracket must be used as well. This bracket must also be used when required by code for hurricane or seismic
conditions. This bracket is available through Micrometl.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
50XT SUGGESTED RIGGING
-in. (914 mm)
DETAIL
A
A06296
RIGGING WT
lb
CABINET
MODEL
A06298
kg
50XT--024
50XT--030
418
448
190
203
Small
50XT--036
50XT--042
50XT--048
50XT--060
469
491
497
548
213
223
225
249
Large
NOTE: See dimensional drawing for corner weight distribution. Corner
weights shown on drawing are based on unit---only weights and do
not include packaging.
SELECTION PROCEDURE
Enter the Electric Heater table on page
5
for 208/230v,
Determine cooling and heating requirements at design
single--phase, unit. The 7.2--kW heater at 240v most closely
satisfies the heating required. To calculate kW at 230v, multiply the
heater kW by multiplication factor 0.92 found in the Multiplication
Factors table on page 29.
conditions
Given:
REQUIRED COOLING CAPACITY (TC) . . . . . . 34,500 BTUH
SENSIBLE HEAT CAPACITY (SHC) . . . . . . . . . 24,000 BTUH
7.2 kW x 0.92 = 6.6 kW
REQUIRED HEATING CAPACITY (SHC) . . . . . 36,000 BTUH
CONDENSER ENTERING AIR TEMPERATURE 95°F (35°C)
INDOOR--AIR TEMPERATURE . . . 80°F (26.6°C) EDB, 67°F
(19.4°C) EWB
6.6 kW x 3414 Btuh/kW = 22,532 Btuh
Total unit heating capacity is 39,342 Btuh
(16,810 + 22,532).
EVAPORATOR AIR QUANTITY . . . . . . . . . . . . . . . 1200 CFM
ELECTRICAL CHARACTERISTICS . . . . . . . . . . . . . 230--1--60
Select unit that corresponds to power source available
The Electrical Data table shows that the unit is designed to operate
at 208/230--1--60.
Select unit based on required cooling capacity
Enter Net Cooling Capacities table at condenser entering
temperature of 95°F (35°C). The 036 unit at 1200 cfm and 67°F
(19.4°C) ewb (entering wet bulb) will provide a total capacity of
34,600 Btuh and a SHC of 24,220 Btuh. Calculate SHC correction,
if required, using Note 4 under Cooling Capacities tables.
Select electric heat
Enter the 036 unit Heating Extended Performance table at 1200
cfm. At 70°F (21.1°C) return indoor air and 20°F (--6.6°C) air
entering outdoor coil, the integrated heating capacity is 16,810
Btuh. (Select integrated heating capacity value since deductions for
outdoor--coil frost and defrosting have already been made. No
correction is required.)
The required heating capacity is 36,000 Btuh. Therefore, at least
19,190 Btuh additional electric heat is required.
Determine additional electric heat capacity in kW.
19,190 Btuh
3414 Btuh/kW
= 5.6kW of heat required
10
Download from Www.Somanuals.com. All Manuals Search And Download.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
13
Download from Www.Somanuals.com. All Manuals Search And Download.
14
Download from Www.Somanuals.com. All Manuals Search And Download.
15
Download from Www.Somanuals.com. All Manuals Search And Download.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
17
Download from Www.Somanuals.com. All Manuals Search And Download.
18
Download from Www.Somanuals.com. All Manuals Search And Download.
19
Download from Www.Somanuals.com. All Manuals Search And Download.
20
Download from Www.Somanuals.com. All Manuals Search And Download.
21
Download from Www.Somanuals.com. All Manuals Search And Download.
22
Download from Www.Somanuals.com. All Manuals Search And Download.
23
Download from Www.Somanuals.com. All Manuals Search And Download.
24
Download from Www.Somanuals.com. All Manuals Search And Download.
25
Download from Www.Somanuals.com. All Manuals Search And Download.
26
Download from Www.Somanuals.com. All Manuals Search And Download.
27
Download from Www.Somanuals.com. All Manuals Search And Download.
28
Download from Www.Somanuals.com. All Manuals Search And Download.
PERFORMANCE DATA (CONT)
Multiplication Factors
Heater kW
Rating
Voltage Distribution
V/3/60
Example: 15.0 kW (at 240v) heater on 208v
= 15.0 (.75 mult factor)
Multiplication Factor
= 11.25 capacity at 208v
200
208
230
240
.69
.75
.92
240
Sensible capacity (Btuh)
1.10 x cfm
1.00
LEGEND
BF— Bypass Factor
edb— Entering Dry--Bulb
Ewb— Entering Wet--Bulb
kW — Total Unit Power Input
ldb— Leaving Dry--Bulb
t
t
t
--
ldb = edb
Wet---bulb temperature corresponding to enthalpy
lwb =
h
air leaving evaporator coil ( lwb)
total capacity (Btuh)
lwb— Leaving Wet--Bulb
SHC— Sensible Heat Capacity (1000 Btuh)
TC — Total Capacity (1000 Btuh) (net)
h
h
lwb = e w b ---
4.5 x cfm
h
Where: ewb = Enthalpy of air entering evaporator coil
4. The SHC is based on 80_F (26.6_C) edb temperature of air
entering evaporator coil. Below 80_F (26.6_C) edb, subtract (corr
factor x cfm) from SHC.
*At 75°F (23.8°C) entering dry bulb (Tennessee Valley Authority
[TVA] rating conditions); all other at 80°F (26.6°C) entering dry
bulb.
COOLING NOTES:
1. Ratings are net; they account for the effects of the evaporator
fan motor power and heat.
Above 80_F (26.6_C) edb, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 + BF) x (edb + 80).
5. Integrated capacity is maximum (instantaneous) capacity less the
effect of frost on the outdoor coil and the heat required to defrost it.
2. Direct interpolation is permissible. Do not extrapolate.
3. The following formulas may be used:
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Wet coil air delivery -- low stage
208/230 VOLT
EXTERNAL STATIC PRESSURE (in. wc)
0.4 0.5 0.6 0.7
Variable based on Comfort Settings
UNIT
SYSTEM SETTING
SIZE
0.1
0.2
0.3
0.8
0.9
1.0
COMFORT (Default)
EFFICIENCY
MAX
COMFORT (Default)
EFFICIENCY
MAX
COMFORT (Default)
EFFICIENCY
MAX
COMFORT (Default)
EFFICIENCY
MAX
COMFORT (Default)
EFFICIENCY
MAX
COMFORT (Default)
EFFICIENCY
MAX
525
600
525
600
525
600
525
600
525
600
525
600
525
600
525
600
525
600
525
600
024
030
036
042
048
060
Variable based on Comfort Settings
613
700
Variable based on Comfort Settings
743
850
Variable based on Comfort Settings
853
975
Variable based on Comfort Settings
963
613
700
613
700
613
700
613
700
613
700
613
700
613
700
613
700
613
700
743
850
743
850
743
850
743
850
743
850
743
850
743
850
743
850
743
850
853
975
853
975
853
975
853
975
853
975
853
975
853
975
853
975
853
975
963
1100
963
1100
963
1100
963
1100
963
1100
963
1100
963
1100
963
1100
963
1100
1100
Variable based on Comfort Settings
1200
1372
1200
1372
1200
1372
1200
1372
1200
1372
1200
1372
1200
1372
1200
1372
1200
1372
1200
1372
Wet coil air delivery -- high stage
208/230 VOLT
EXTERNAL STATIC PRESSURE (in. wc)
0.4 0.5 0.6 0.7
Variable based on Comfort Settings
UNIT
SYSTEM SETTING
SIZE
0.1
0.2
0.3
0.8
0.9
1.0
COMFORT (Default)
EFFICIENCY
MAX
COMFORT (Default)
EFFICIENCY
MAX
COMFORT (Default)
EFFICIENCY
MAX
COMFORT (Default)
EFFICIENCY
MAX
COMFORT (Default)
EFFICIENCY
MAX
COMFORT (Default)
EFFICIENCY
MAX
700
800
700
800
700
800
700
800
700
800
700
800
700
800
700
800
700
800
700
800
024
030
036
042
048
060
Variable based on Comfort Settings
875
1000
Variable based on Comfort Settings
1050
1200
Variable based on Comfort Settings
1225
1400
Variable based on Comfort Settings
1400
1600
Variable based on Comfort Settings
1750
2000
875
1000
875
1000
875
1000
875
1000
875
1000
875
1000
875
1000
875
1000
875
1000
1050
1200
1050
1200
1050
1200
1050
1200
1050
1200
1050
1200
1050
1200
1050
1200
1050
1200
1225
1400
1225
1400
1225
1400
1225
1400
1225
1400
1225
1400
1225
1400
1225
1400
1225
1400
1400
1600
1400
1600
1400
1600
1400
1600
1400
1600
1400
1600
1400
1600
1400
1600
1400
1600
1750
2000
1750
2000
1750
2000
1750
2000
1750
2000
1750
2000
1750
2000
1750
2000
1750
2000
Air delivery values are based on operating voltage of 230v, and wet coil. Filter and electric heater will not change air delivery values.
NOTES:
1. See User Interface instructions for more information on Max, Efficiency, and Comfort Settings
2. Efficiency Setting operates at 350 cfm/ton (nominal) and Max Setting operates at 400 cfm/ton (nominal)
30
Download from Www.Somanuals.com. All Manuals Search And Download.
TYPICAL PIPING AND WIRING
ROOF-MOUNTING
CURB
ROOF
RETURN-AIR
FLEXIBLE DUCT
SUPPLY-AIR
FLEXIBLE DUCT
CEILING
CONCENTRIC DIFFUSER BOX
(FIELD-SUPPLIED)
C00023
USER
INTERFACE
RETURN
AIR
FROM
POWER
SOURCE
TOP COVER
DISCONNECT
PER NEC*
*NEC - NATIONAL ELECTRICAL CODE
A06279
31
Download from Www.Somanuals.com. All Manuals Search And Download.
To convert a unit to downflow discharge — Units are equipped
with factory--installed inserts in the downflow openings. Remove the
inserts similar to removing an electrical knock--out. Leave on duct
covers to seal the horizontal discharge openings in the unit. Units
installed in horizontal discharge orientation do not require duct cov-
ers.
APPLICATION DATA
Condensate trap — A 2--in. (51 mm) condensate trap must be field
supplied.
1” (25mm) MIN.
TRAP
OUTLET
Minimum cooling ambient operating temperature — All stan-
dard units have a minimum ambient operating temperature of 55°F
(12.7°C). With low--ambient cooling enabled at the UI, units can op-
erate at temperatures down to 0°F (--17.7°C).
2” (50mm) MIN.
Maximum operating outdoor air temperature — Maximum out-
door operating air temperature for cooling is 125°F (51.6°C).
Ductwork — Secure downflow dischargeductwork toroof curb.For
horizontal discharge applications, attach ductwork to unit with
flanges.
Balance Point Worksheet
70
60
50
40
30
20
10
0
Based on Entering Indoor Air of 70 Deg. F and Rated CFM
060
048
042
036
030
024
-20
-10
0
10
20
30
40
50
60
Outdoor Air Temp (Deg F)
C03008
32
Download from Www.Somanuals.com. All Manuals Search And Download.
ELECTRICAL DATA
SINGLE POINT POWER
SUPPLY
ELECTRIC HEAT
VOLTAGE
RANGE
COMPRESSOR
OFM
FLA
IFM
FLA
UNIT SIZE
024
V--PH--HZ
NOMINAL
kW*
-- / --
FLA
MCA
MOCP
MIN
MAX
RLA
LRA
-- / --
24.3/24.3
46.9/50.3
56.8/61.8
69.4/76.4
26.2/26.2
48.7/52.2
58.7/63.7
71.3/78.3
93.9/104.3
28.6/28.6
51.2/54.6
61.1/66.1
73.7/80.7
96.3/106.7
34.9/34.9
57.5/60.9
67.4/72.4
80.0/87.0
102.6/113.0
125.2/139.1
43.1/43.1
65.7/69.1
75.6/80.6
88.2/95.2
110.8/121.2
133.4/147.3
45.2/45.2
67.7/71.2
77.6/82.7
90.3/97.2
112.9/123.3
135.4/149.3
35/35
50/60
60/70
70/80
40/40
50/60
60/70
80/80
100/110
45/45
60/60
70/70
80/90
100/110
50/50
60/70
70/80
90/90
110/125
150/150
60/60
70/70
80/90
90/100
125/125
150/150
60/60
70/80
80/90
3.8/5.0
5.4/7.2
7.5/10.0
-- / --
18.1/20.8
26.0/30.0
36.1/41.7
-- / --
208/230--1--60
187
187
253
253
15.3
52.0
0.9
0.9
4.3
4.3
3.8/5.0
5.4/7.2
7.5/10.0
11.3/15.0
-- / --
18.1/20.8
26.0/30.0
36.1/41.7
54.2/62.5
-- / --
030
036
208/230--1--60
208/230--1--60
16.8
16.7
70.0
82.0
3.8/5.0
5.4/7.2
7.5/10.0
11.3/15.0
-- / --
18.1/20.8
26.0/30.0
36.1/41.7
54.2/62.5
-- / --
187
187
253
253
0.9
0.9
6.8
6.8
3.8/5.0
5.4/7.2
7.5/10.0
11.3/15.0
15.0/20.0
-- / --
18.1/20.8
26.0/30.0
36.1/41.7
54.2/62.5
72.2/83.3
-- / --
042
048
060
208/230--1--60
208/230--1--60
208/230--1--60
21.8
27.8
27.3
96.0
96.0
3.8/5.0
5.4/7.2
7.5/10.0
11.3/15.0
15.0/20.0
-- / --
18.1/20.8
26.0/30.0
36.1/41.7
54.2/62.5
72.2/83.3
-- / --
187
187
253
253
1.5
1.9
6.8
9.1
3.8/5.0
5.4/7.2
7.5/10.0
11.3/15.0
15.0/20.0
18.1/20.8
26.0/30.0
36.1/41.7
54.2/62.5
72.2/83.3
118.0
100/110
125/125
150/150
*Heater capacity (kW) based on heater voltage of 208v & 240v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accord-
ingly.
LEGEND
FLA
—
—
—
—
—
Full Load Amps
LRA
Locked Rotor Amps
®
MCA
MOCP
RLA
Minimum Circuit Amps
Maximum Overcurrent Protection
Rated Load Amps
NOTES:
1. In compliance with NEC (National Electrical Code) requirements
for multimotor and combination load equipment (refer to NEC
Articles 430 and 440), the overcurrent protective device for the
unit shall be Power Supply fuse. The CGA (Canadian Gas
Association) units may be fuse or circuit breaker.
2. Minimum wire size is based on 60 C copper wire. If other than
60 C wire is used, or if length exceeds wire length in table,
determine size from NEC.
33
Download from Www.Somanuals.com. All Manuals Search And Download.
TYPICAL WIRING SCHEMATIC — 230--1--60
A08201
34
Download from Www.Somanuals.com. All Manuals Search And Download.
satisfied, the compressor will shut off. The reversing valve will
remain energized until the control board power is removed or a call
for heating is initiated. With a call for heating, the outdoor fan and
compressor are energized. The compressor will operate in high or
low stage operation, as needed, to meet the heating demand. When
the heating demand is satisfied, the compressor and fan will shut
off. The reversing valve is de--energized in the heating mode.
CONTROLS
Sequence of Operation
The 50XT packaged heat pump is designed for installation with a
communicatingUI. Thisunit willnot respondto commandsprovided
by a common thermostat except under certain emergency situations.
The UI uses temperature, humidity and other data supplied from
indoor and outdoor system components to control heating or cooling
system for optimum comfort. The unit will be commanded by the UI
to supply airflow. The unit will operate the indoor fan at requested
airflow for most modes.
NOTE: When two--stage unit is operating at low--stage, system
vapor (suction) pressure will be higher than a standard single--stage
system or high--stage operation.
NOTE:
Outdoor fan motor will continue to operate for one
The nominal requested airflow in high stage will be 350 cfm per ton
of nominal cooling capacity as defined by unit size. Actual airflow
request will be adjusted from nominal using indoor and outdoor
temperature and indoor humidity data to optimize the system
operation for occupant comfort and system efficiency. Refer to UI
literature for further system control details.
minute after compressor shuts off, when outdoor ambient is greater
than or equal to 100°F (38°C).
UTILITY INTERFACE WITH INFINITY CONTROL
The utility curtailment relay should be connected to factory
supplied pigtails (PINK connected to R, VIOLET connected to Y2
on the control board) located in the low voltage splice box (see
Typical Wiring Schematic ). This input allows a power utility
device to interrupt compressor operation during peak load periods.
When the utility sends a signal to shut the system down, the UI will
display “Curtailment Active”.
Airflow during electric heater operation must be greater than a
minimum level for safe operation. If UI instructs unit to turn on
electric heat and the requested airflow is less than the minimum level
the fan coil control will override requested value.
NOTE: Once the compressor has started and then has stopped, it
should not be started again until 4 minutes have elapsed. The cooling
cycle remains “on” until the room temperature drops to point that is
slightly below the cooling control setting of the UI.
Infinity Controlled Low Ambient Cooling
NOTE: When this unit is operating below 55_F (12.7°C) outdoor
temperature, provisions must be made for low ambient operation.
This unit is capable of low ambient cooling down to 0_F
(--17.7°C)ONLY when using the Infinity control. A low ambient kit
isnotrequired,andtheoutdoorfanmotor doesnot needto bereplaced
for Infinity controlled low ambient operation. Low ambient cooling
must be enabled in the UI set--up. Fan may not begin to cycle until
about 40_F (4.4°C) OAT. Fan will cycle based on coil and outdoor
air temperature.
COOLING AND HEATING OPERATION
With a call for first stage cooling, the outdoor fan, reversing valve,
and low stage compressor are energized. If low--stage cannot
satisfy cooling demand, high--stage cooling is energized by the UI.
After second stage is satisfied, the unit returns to low--stage
operation until first stage is satisfied or until second stage is
required again. When both first stage and second stage cooling are
35
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Fan wheel shall be made from steel, be double--inlet type. It
shall have forward--curved blades with a corrosion--resistant
finish and shall be dynamically balanced.
GUIDE SPECIFICATIONS
SINGLE--PACKAGED HEAT PUMP UNITS
CONSTANT VOLUME APPLICATION
3. Outdoor fan shall be of the direct--driven propeller type with
aluminum blades, riveted to corrosion--resistant steel spiders.
It shall be dynamically balanced, and discharge air vertically.
HVAC GUIDE SPECIFICATIONS
SIZE RANGE: 2 TO 5 TONS, NOMINAL (COOLING)
MODEL NUMBER: 50XT
D. Compressor:
1. Fully hermetic, 2--stage scroll compressors with
factory--installed vibration isolation.
PART I -- GENERAL
SYSTEM DESCRIPTION
2. Scroll compressors shall be standard on all units.
3. Compressor Protection:
Outdoor rooftop or ground mounted heat pump unit utilizing a
hermetic, 2--stage scroll compressor for heating and cooling duty
and optional electric heating. Unit shall discharge supply air ver-
tically or horizontally as shown on contract drawings. Outdoor
fan/coil section shall have a draw--thru design with vertical dis-
charge for minimum sound levels.
Defrost control shall protect compressor by preventing
“short cycling.”
E. Coils:
1. Indoor and outdoor coils shall have aluminum plate fins
mechanically bonded to seamless copper tubes with all joints
brazed.
QUALITY ASSURANCE
A. Unit shall be rated in accordance with ARI Standards
210/240 and 270.
2. Tube sheet openings shall be bellied to prevent tube wear.
B. Unit shall be designed in accordance with UL Standard
1995.
C. Unit shall be manufactured in a facility registered to ISO
9001 manufacturing quality standard
F. Refrigerant Metering Device:
Refrigerant metering device shall be of the single body,
fixed orifice feed type (outdoor) and TXV (indoor).
G. Filters:
Filter section shall consist of field--installed, throw--away,
1--in. thick fiberglass filters of commercially available sizes.
D. Unit shall be UL listed and c--UL certified as a total
package for safety requirements.
H. Controls and Safeties:
E. Roof curb shall be designed to conform to NRCA
Standards.
F. Insulation and adhesives shall meet NFPA 90A
requirements for flame spread and smoke generation.
1. Unit controls shall be complete with self--contained low
voltage control circuit.
2. Units shall incorporate an internal compressor protector that
provides reset capability.
G. Cabinet insulation shall meet ASHRAE Standard 62P.
DELIVERY, STORAGE, AND HANDLING
3. Unit shall provide high-- and low--/loss--of--charge pressure
safety protection.
Unit shall be stored and handled per manufacturer’s recommen-
dations.
I. Operating Characteristics:
1. Unit shall be capable of starting and running at 125°F
(51.6_C) ambient outdoor temperature, exceeding maximum
load criteria of ARI Standard 240.
PART 2-- PRODUCTS
EQUIPMENT
A. General:
2. Compressor shall be capable of operation down to 55°F
(12.7_C) ambient outdoor temperature in cooling and --10°F
in heating.
Factory--assembled, single--piece, heat pump. Contained within
the unit enclosure shall be all factory wiring, piping, controls, re-
frigerant charge (R--410A), and special features required prior to
field start--up.
3. Unit shall be capable of low--ambient cooling (below 55_F
(12.7_C) ambient outdoor temperature) with low--ambient
cooling enabled on the UI.
B. Unit Cabinet:
1. Unit cabinet shall be constructed of phosphated, zinc--coated,
prepainted steel capable of withstanding 500 hrs of salt spray.
J. Electrical Requirements:
All unit power wiring shall enter unit cabinet at a single location.
2. Normal service shall be through a single removable cabinet
panel.
K. Motors:
1. Compressor motors shall be of the refrigerant--cooled type
with line--break thermal and current overload protection.
3. The unit shall be constructed on a rust proof unit base that has
an externally trapped, integrated sloped drain pan.
2. All fan motors shall have permanently lubricated bearingsand
inherent automatic--reset thermal overload protection.
4. Indoor fan compartment top surface shall be insulated with a
minimum 1/2--in. (13 mm) thick, flexible fiberglass
insulation, coated on the air side and retained by adhesive and
mechanical means. The indoor wall sections will be insulated
with a foil--faced insulation capable of being wiped clean.
Aluminum foil--faced fiberglass insulation shall be used in the
entire indoor air cavity section.
3. Outdoor fan motor shall be totally enclosed.
L. Grille
1. Louvered Grille:
Louvered grille shall be standard on all units.
5. Unit shall have a field--supplied condensate trap.
C. Fans:
1. The indoor fan shall be variable--speed motor and control, as
shown on equipment drawings.
36
Download from Www.Somanuals.com. All Manuals Search And Download.
6. Filter Rack Kit:
GUIDE SPECIFICATIONS (CONT)
Shall provide filter mounting for downflow and horizontal
applications.
M. Special Features:
1. Coil Options:
7. Square--To--Round Duct Transitions:
Shall include factory--installed optional tin--plated indoor
copper/copper and vinyl--coated refrigerant coils.
Shall have the ability to convert the supply and return open-
ings from rectangular to round (024--048 sizes only).
2. Flat Roof Curb:
8. Crankcase Heater:
Curbs shall have seal strip and a wood nailer for flashing and
shall be installed per manufacturer’s instructions.
Shall provide anti--floodback protection for low--load cool-
ing applications. (Standard on 042--060 sizes.)
3. Manual Outdoor Air Damper:
9. Electric heaters:
Package shall consist of damper, bird screen, and rain hood
which can be preset to admit outdoor air for year--round ven-
tilation.
a. Electric heater shall be available as a field--installed
option.
b. Heater elements shall be open--wire type, adequately
supported and insulated with ceramic bushings.
c. Electric heater packages must provide single--point
power connection capability.
4. Infinityt User Interface:
Toprovidefortwo--stage heatpump heating, two--stagecool-
ing, and electric (auxiliary) heat, in addition to manual or au-
tomatic changeover and indoor fan control.
10. Compressor Hard Start Kit:
5. Low--Ambient Cooling:
Shall be available to give a boost to the compressor motor at
each start--up.
Low--ambient cooling must be enabled in the UI setup to al-
low unit to operate down to 0°F (--17_C) outdoor ambient
temperature in cooling.
37
Download from Www.Somanuals.com. All Manuals Search And Download.
Catalog No: 50XT---04PD
Copyright 2008 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231
Printed in U.S.A.
Edition Date: 06/08
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Replaces: 50XT---3PD
38