50CR
Infinityt Single--Packaged Heat Pump Units
With Puron® (R--410A) Refrigerant
Sizes 024--060
Installation Instructions
NOTE: Read the entire instruction manual before starting the
installation.
NOTE: Installer: Make sure the Owner’s Manual and Service
Instructions are left with the unit after installation.
TABLE OF CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . 2
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
RECEIVING AND INSTALLATION . . . . . . . . . . . . . . . . 2--16
Check Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Identify Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Inspect Shipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Provide Unit Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Roof Curb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Slab Mount . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Ground Mount . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Provide Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Use of Rigging Bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Select and Install Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Converting Horizontal Discharge Units to Downflow
A05307
Fig. 1 -- Unit 50CR
(Vertical) Discharge Units . . . . . . . . . . . . . . . . . . . . . . . . . 9
Provide for Condensate Disposal . . . . . . . . . . . . . . . . . . . . . 9
Install Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . 11
High--Voltage Connections . . . . . . . . . . . . . . . . . . . . . . . 11
Routing Power Leads Into Unit . . . . . . . . . . . . . . . . . . . . 11
Connecting Ground Lead to Ground Screw . . . . . . . . . . 11
Routing Control Wires . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Accessory Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Special Procedures for 208--v Operation . . . . . . . . . . . . . 16
PRE--START--UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
START--UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Unit Start--Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17--23
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Check for Refrigerant Leaks . . . . . . . . . . . . . . . . . . . . . . . . 20
Start--Up Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Checking Cooling and Heating Control Operation . . . . . 20
Checking and Adjusting Refrigerant Charge . . . . . . . . . . 22
Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
No Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Low Charge Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
To Use Cooling Charging Charts . . . . . . . . . . . . . . . . . . . 22
Indoor Airflow and Airflow Adjustments . . . . . . . . . . . . 22
Defrost Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Quiet Shift . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Defrost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Emergency Heat/Cool Mode . . . . . . . . . . . . . . . . . . . . . . . . 22
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24--28
Air Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Indoor Blower and Motor . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Outdoor Coil, Indoor Coil, and Condensate Drain Pan . . . . 25
Outdoor Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Electrical Controls and Wiring . . . . . . . . . . . . . . . . . . . . . . 26
Refrigerant Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Indoor Airflow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
®
Metering Devices–TXV & AccuRater Piston . . . . . . . . . . 26
Pressure Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
L o s s -- o f -- C h a r g e S w i t c h . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 7
High--Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
®
Copeland Scroll Compressor (Puron Refrigerant) . . . . . . . 27
Refrigerant System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Compressor Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Servicing Systems on Roofs with Synthetic Materials . . . 27
Liquid--Line Filter Drier . . . . . . . . . . . . . . . . . . . . . . . . . 28
Puron (R--410A) Refrigerant Charging . . . . . . . . . . . . . . 28
System Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
L o s s -- o f -- C h a r g e S w i t c h . . . . . . . . . . . . . . . . . . . . . . . . . 2 8
Check Defrost Thermostat . . . . . . . . . . . . . . . . . . . . . . . . 28
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
START--UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
1
Download from Www.Somanuals.com. All Manuals Search And Download.
HVACunit
base
HVAC unit
base
Gask eting
inner flange*
Screw
(NOTE A)
Screw
(NOTE A)
Gasketing
inner flange*
*Gasketing
outer flange
*Gasketing
outer flange
Wood nailer*
Wood nailer*
Flashing field
supplied
Flashing field
supplied
Roof curb*
Roof curb*
Insulation(field
supplied)
Insulation(field
supplied)
Roofing material
field supplied
Roofing material
field supplied
Ductwork
field supplied
Ductwork
field supplied
Cant strip
field supplied
Cant strip
field supplied
Roof
Roof
*Provided with roof curb
*Provided with roof curb
Roof Curb for Small Cabinet
Roof Curb for Large Cabinet
Note A: When unit mounting screw is used,
retainer bracket must also be used.
Note A: When unit mounting screw is used,
retainer bracket must also be used.
E
G
F
Supply opening
(B x C)
G
BTyp.
D
CTyp.
F
R/A
S/A
A
Gasket around
duct
D
E
Short
Support
Insulated
deck pan
Gasket around
outer edge
Insulated
deck pan
Long
Support
Return opening
(B X C)
A05308
ODS CATALOG
NUMBER
A
B
C
D
E
F
G
UNIT SIZE
IN. (MM)
IN. (MM)
IN. (MM)
IN. (MM)
IN. (MM)
IN. (MM)
IN. (MM)
CPRFCURB006A00
8 (203)
11 (279)
11 (279)
16--1/2 (419)
16--1/2 (419)
28--3/4 (730)
28--3/4 (730)
30--3/8 (771)
30--3/8 (771)
44--5/16 (1126) 45--15/16 (1167)
44--5/16 (1126) 45--15/16 (1167)
50CR024 -036
CPRFCURB007A00 14 (356)
CPRFCURB008A00
CPRFCURB009A00 14 (356) 16--3/16 (411) 17--3/8 (441) 40--1/4 (1022) 41--15/16 (1065) 44--7/16 (1129)
8 (203) 16--3/16 (411) 17--3/8 (441) 40--1/4 (1022) 41--15/16 (1065) 44--7/16 (1129)
46--1/16 (1169)
46--1/16 (1169)
50CR042 -060
NOTES:
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied, as required, to unit being installed.
3. Dimension in ( ) are in millimeters.
4. Roof curb is made of 16--gauge steel.
5. Table lists only the dimensions, per part number, that have changed.
6. Attach ductwork to curb (flanges of duct rest on curb).
7. Insulated panels: 1--in. thick fiberglass 1 lb. density.
8. Dimensions are in inches.
9. When unit mounting screw is used (see Note A), a retainer bracket must be used as well. This bracket must also be used when required by code for hurricane or seismic
conditions. This bracket is available through Micrometl.
Fig. 2 -- Roof Curb Dimensions
3
Download from Www.Somanuals.com. All Manuals Search And Download.
A
C
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
B
A-B
1/4
B-C
1/4
A-C
1/4
C99065
Fig. 3 -- Unit Leveling Tolerances
OPTIONAL
RETURN
AIR
OPTIONAL
SUPPLY
AIR
OPENING
OPENING
2"
EVAP. COIL
COND. COIL
C99096
Fig. 4 -- Slab Mounting Detail
A06114
Fig. 5 -- Corner Weights (Lbs.)
CORNER WEIGHTS (SMALL CABINET)
CORNER WEIGHTS (LARGE CABINET)
Unit
Total Weight
Corner Weight 1
Corner Weight 2
Corner Weight 3
Corner Weight 4
024
349
70
54
84
030
349
70
54
84
036
373
75
58
90
Unit
Total Weight
Corner Weight 1
Corner Weight 2
Corner Weight 3
Corner Weight 4
042
438
88
68
106
177
048
463
98
61
127
177
060
499
107
70
136
186
141
141
150
4
Download from Www.Somanuals.com. All Manuals Search And Download.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Step 4—Rig and Place Unit
USE OF RIGGING BRACKET
Rigging and handling of this equipment can be hazardous for many
reasons due to the installation location (roofs, elevated structures,
etc.).
Field Installation of Rigging Bracket
1. If applicable, remove unit from shipping carton. Leave top
shipping skid on the unit for use as a spreader bar to prevent
the rigging straps from damaging the unit. If the skid is not
available, use a spreaderbar ofsufficient length to protectthe
unit from damage.
Only trained, qualified crane operators and ground support staff
should handle and install this equipment.
When working with this equipment, observe precautions in the
literature,on tags, stickers,and labelsattached to the equipment,and
any other safety precautions that might apply.
2. Remove 4 screws in unit corner posts.
3. Attach each of the 4 metal rigging brackets under the panel
rain lip (See Fig. 8). Use the screws removed in step 2 above
to secure the brackets to the unit.
Training for operators of the lifting equipment should include, but
not be limited to, the following:
1. Application of the lifter to the load, and adjustment of the
lifts to adapt to various sizes or kinds of loads.
!
WARNING
2. Instruction in any special operation or precaution.
PROPERTY DAMAGE HAZARD
3. Condition of the load as it relates to operation of the lifting
kit, such as balance, temperature, etc.
Failure to follow this warning could result in personal
injury/death or property damage.
Follow all applicable safety codes. Wear safety shoes and work
gloves.
Rigging bracket MUST be under the rain lip to provide
adequate lifting.
INSPECTION
Prior to initial use, and at monthly intervals, all rigging brackets and
straps should be visually inspected for any damage, evidence of
wear, structural deformation, or cracks. Particular attention should
be paid to excessive wear at hoist hooking points and load support
areas. Brackets or straps showing any kind of wear in these areas
must not be used and should be discarded.
!
WARNING
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal
injury/death or property damage.
Do not strip screws when re--securing the unit. If a screw is
stripped, replace the stripped one with a larger diameter screw
(included).
!
WARNING
ELECTRICAL SHOCK HAZARD
Rigging/Lifting of Unit
Failure to follow this warning could result in personal injury
or death.
1. Bend top of brackets down approximately 30 degrees from
the corner posts.
Before installing or servicing system, always turn off main
power to system. There may be more than one disconnect
switch. Turn off accessory heater power switch if applicable.
Tag disconnect switch with a suitable warning label.
2. Attach straps of equal length to the rigging brackets at
opposite ends of the unit. Be sure straps are rated to hold the
weight of the unit (See Fig. 9).
3. Attach a clevis of sufficient strength in the middle of the
straps. Adjust the clevis location to ensure unit is lifted level
with the ground.
!
WARNING
UNIT FALLING HAZARD
4. After unit is securely in place detach rigging straps. Remove
corner posts, screws, and rigging brackets then reinstall
screws.
Failure to follow this warning could result in personal injury
or death.
Never stand beneath rigged units or lift over people.
!
WARNING
INTRODUCTION
UNIT FALLING HAZARD
The lifting/rigging bracket is engineered and designed to be
installed only on Small Packaged Products. This bracket is to be
used to rig/lift a Small Packaged Product onto roofs or other
elevated structures.
Failure to follow this warning could result in personal
injury/death or property damage.
When straps are taut, the clevis should be a minimum of 36
inches above the unit top cover.
!
WARNING
After the unit is placed on the roof curb or mounting pad, remove
the top crating. On 50CR060 units only, 2 wire ties fastened to the
outdoor coils and reversing valve/accumulator assembly must be
cut. Remove the left and front louvered panels and corner post to
access wire ties. The wire tie to be cut on the left is located
approximately 4 in. down the tube sheet. The wire tie to be cut on
the right is located approximately 6 in. down the tube sheet.
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal
injury/death or property damage.
Rigging brackets for one unit use only. When removing a
unit at the end of its useful life, use a new set of brackets.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
DETAIL
A
C03017
Fig. 8 -- Rigging Bracket Under Unit Rain Lip
A06113
MAXIMUM SHIPPING WEIGHT
UNIT SIZE
Lb
Kg
50CR024
50CR030
50CR036
50CR042
50CR048
50CR060
372
372
395
462
485
521
169
169
179
210
220
236
Fig. 9 -- Suggested Rigging
8
Download from Www.Somanuals.com. All Manuals Search And Download.
Step 5—Select and Install Ductwork
CONVERTING HORIZONTAL DISCHARGE UNITS TO
DOWNFLOW (VERTICAL) DISCHARGE UNITS
Thedesign and installation ofthe ductsystem mustbe in accordance
with the standards of the NFPA for installation of non--residence
type air conditioning and ventilating systems, NFPA 90A or
residence type, NFPA 90B and/or local codes and ordinances.
!
WARNING
ELECTRICAL SHOCK HAZARD
Select and size ductwork, supply--air registers, and return air grilles
according to ASHRAE (American Society of Heating,
Refrigeration, and Air Conditioning Engineers) recommendations.
Failure to follow this warning could result in personal injury
or death.
Before installing or servicing system, always turn off main
power to system. There may be more than one disconnect
switch.Turn off accessory heater power switch if applicable.
The unit has duct flanges on the supply-- and return--air openings on
the side of the unit.
!
WARNING
1. Open all electrical disconnects and install lockout tag before
starting any service work.
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury
or death.
2. Remove side duct covers to access bottom return and supply
knockouts.
For vertical supply and return units, tools or parts could drop
into ductwork, therefore, install a 90 degree turn in the return
ductwork between the unit and the conditioned space. If a 90
degree elbow cannot be installed, then a grille of sufficient
strength and density should be installed to prevent objects
from falling into the conditioned space. Units with electric
heaters require 90 degree elbow in supply duct.
NOTE: These panels are held in place with tabs similar to an
electrical knockout.
3. Use a screwdriver and hammer to remove the panels in the
bottom of the composite unit base.
4. Ensure the side duct covers are in place to block off the
horizontal air openings (See Fig. 11).
Step 6—Provide for Condensate Disposal
NOTE: Ensure that condensate--water disposal methods comply
When designing and installing ductwork, consider the following:
with local codes, restrictions, and practices.
1. Allunitsshouldhavefield--supplied filtersor accessory filter
rack installed in the return--air side of the unit.
Recommended sizes for filters are shown in Table 1.
Theunits disposeof condensatethrough a3/4 in.NPT femalefitting
that exits on the compressor end of the unit. Condensate water can
be drained directly onto the roof in rooftop installations (where
permitted) or onto a gravel apron in ground level installations.
Install a field--supplied condensate trap at end of condensate
connection to ensure proper drainage. Make sure that the outlet of
the trap is at least 1 in. lower than the drain--pan condensate
connectiontoprevent thepan fromoverflowing. Primethe trapwith
water. When using agravel apron,make sureit slopesaway fromthe
unit.
2. Avoid abrupt duct size increases and reductions. Abrupt
change in duct size adversely affects air performance.
IMPORTANT: Use flexible connectors between ductwork and
unit to prevent transmission of vibration. Use suitable gaskets to
ensure weather tight and airtight seal.When electricheat isinstalled,
use fireproof canvas (or similar heat resistant material) connector
between ductwork and unit discharge connection. If flexible duct is
used, insert a sheet metal sleeve inside duct. Heat resistant duct
connector (or sheet metal sleeve) must extend 24--in. from electric
heater element.
If the installation requires draining the condensate water away from
the unit, install a field--supplied 2--in. trap at the condensate
connection to ensure proper drainage. Condensate trap is available
as an accessory or is field--supplied. Make sure that the outlet of the
trap is at least 1 in. lower than the unit drain--pan condensate
connection to prevent the pan from overflowing. Connect a drain
trough using a minimum of field--supplied 3/4 --in. PVC or
field--supplied 3/4 --in. copper pipe at outlet end of the 2 --in. trap
(See Fig. 12). Do not undersize the tube. Pitch the drain trough
downward at aslope ofat least1 in.for every10 ft.of horizontalrun.
Be sure to check the drain trough for leaks. Prime the trap at the
beginning of the cooling season start--up.
3. Size ductwork for max cooling air quantity (400 cfm/ton).
4. Seal, insulate, and weatherproof all external ductwork. Seal,
insulate and cover with a vapor barrier all ductwork passing
through conditioned spaces. Follow latest Sheet Metal and
Air Conditioning Contractors National Association
(SMACNA) and Air Conditioning Contractors Association
(ACCA) minimum installation standards for residential
heating and air conditioning systems.
5. Secure all ducts to building structure. Flash, weatherproof,
and vibration--isolate duct openings in wall or roof
according to good construction practices.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 1—Physical Data -- Unit 50CR
UNIT SIZE
024
2
350
030
2--1/2
350
036
3
373
042
3--1/2
440
048
4
463
060
5
499
NOMINAL CAPACITY (ton)
OPERATING WEIGHT (lb.)
Compressor
Scroll
TXV
Refrigerant (R--410A) Quantity (lb.)
REFRIGERANT METERING DEVICE
7.5
8
9.5
10.8
11.5
14.0
0.038 (Left OD Coil)
0.046 (Right OD Coil)
0.042 (Left OD Coil)
0.052 (Right OD Coil)
ORIFICE OD (in.)
0.035 (2)
0.035 (2)
0.038 (2)
0.038 (2)
OUTDOOR COIL
Rows…Fins/in.
Face Area (sq. ft.)
OUTDOOR FAN
Nominal Cfm
2…21
12.3
2…21
12.3
2…21
13.6
2…21
15.4
2…21
17.2
2…21
19.4
2700
22
2700
22
2800
22
2800
22
3300
22
3300
22
Diameter
Motor HP (RPM)
INDOOR COIL
1/8 (825)
1/8 (825)
1/8 (825)
1/8 (825)
1/4 (1100)
1/4 (1100)
Rows…Fins/in.
Face Area (sq. ft.)
INDOOR BLOWER
Nominal Airflow (Cfm)
3…15
3.7
3…15
3.7
4…15
3.7
3…15
4.7
4…15
4.7
4…17
5.7
Comfort
Variable based on Comfort Roll back (see User Interface instructions for more information).
Efficiency
Max
700
800
10x10
1/2
875
1000
10x10
1/2
1050
1200
11x10
3/4
1225
1400
11x10
3/4
1400
1600
11x10
3/4
1750
2000
11x10
1
Size (in.)
Motor HP (RPM)
HIGH--PRESSURE SWITCH (psig)
650 ± 15
420 ± 25
Cutout
Reset (Auto)
LOSS--OF--CHARGE/LOW--PRESSURE SWITCH
(Liquid Line) (psig)
Cutout
20 ± 5
45 ± 10
Reset (Auto)
Return--Air Filters (in.)*
Throwaway
20x24x1
20x24x1
24x30x1
24x36x1
24x36x1
24x36x1
*Required filter sizes shown are based on the larger of the ARI (Air Conditioning and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 ft/minute
for throwaway type or 450 ft/minute for high--capacity type. Air filter pressure drop for non--standard filters must not exceed 0.08 in. wg.
USER
INTERFACE
RETURN
AIR
FROM
POWER
TOP COVER
SOURCE
DISCONNECT
PER NEC*
FROM
GAS LINE
*NEC - NATIONAL ELECTRICAL CODE
A06091
Fig. 10 -- Typical Installation
10
Download from Www.Somanuals.com. All Manuals Search And Download.
!
CAUTION
UNIT COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in damage to the unit
being installed.
1. Make all electrical connections in accordance with NEC
ANSI/NFPA (latest edition) and local electrical codes
governing such wiring. In Canada, all electrical
connections must be in accordance with CSA standard
C22.1 Canadian Electrical CodePart 1 and applicablelocal
codes. Refer to unit wiring diagram.
2. Use only copper conductor for connections between
field--supplied electrical disconnect switch and unit. DO
NOT USE ALUMINUM WIRE.
3. Be sure that high--voltage power to unit is within operating
voltage range indicated on unit rating plate. On 3--phase
units, ensure phases are balanced within 2 percent. Consult
local power company for correction of improper voltage
and/or phase imbalance.
Duct Covers
A05301
Fig. 11 -- 50CR with Duct Covers On
4. Insulate low--voltage wires for highest voltage contained
withinconduitwhen low--voltagecontrol wiresare insame
conduit as high--voltage wires.
5. Do not damageinternal componentswhen drilling through
any panel to mount electrical hardware, conduit, etc.
1” (25mm) MIN.
TRAP
OUTLET
2” (50mm) MIN.
ROUTING POWER LEADS INTO UNIT
Use only copper wire between disconnect and unit. The high
voltage leads should be in a conduit until they enter the duct panel;
conduit termination at the duct panel must be watertight. Run the
high--voltage leads through the power entry knockout on the power
entry side panel. See Fig. 6 and 7 for location and size. For
single--phase units, connect leads to the black and yellow wires ; for
3--phaseunits, connectthe leadsto theblack, yellow, and bluewires.
C99013
Fig. 12 -- Condensate Trap
Step 7—Install Electrical Connections
!
WARNING
CONNECTING GROUND LEAD TO GROUND SCREW
ELECTRICAL SHOCK HAZARD
Connect the ground lead to the chassis usingthe groundscrew inthe
wiring splice box (See Fig. 14 and 17).
Failure to follow this warning could result in personal injury
or death.
ROUTING CONTROL POWER WIRES
The unit cabinet must have an uninterrupted, unbroken
electricalgroundtominimizethepossibility of personalinjury
if an electrical fault should occur. This ground may consist of
an electrical wire connected to the unit ground screw in the
control compartment, or conduit approved for electrical
ground when installed in accordance with NEC, ANSI/NFPA
American National Standards Institute/National Fire
Protection Association (latest edition) (in Canada, Canadian
Electrical Code CSA C22.1) and local electrical codes.
For detailed instruction on the low voltage connections to the User
Interface (UI), refer to the UI installation guide.
Form a drip--loop with thecontrol leadsbefore routingthem intothe
unit. Route the low voltage control leads through grommeted,
low--voltageholeprovidedintounit(SeeFig.6and7). Connectuser
interface leads to unit control power leads as shown in Fig. 14.
The unit transformer supplies 24--v power for complete system
including accessory electrical heater. A fuse is provided in the 24--v
circuit on the control board (See Fig. 19); see the caution label on
the transformer. Transformer is factory wired for 230--v operation.
If supply voltage is 208--v, rewire transformer primary as described
in Special Procedures for 208--v Operation section.
HIGH--VOLTAGE CONNECTIONS
The unit must have a separate electrical service with
a
field--supplied, waterproof disconnect switch mounted at, or within
sight from the unit. Refer to the unit rating plate, NEC and local
codes for maximum fuse/circuit breaker size and minimum circuit
amps (ampacity) for wire sizing (See Table 2 for electrical data).
The field--supplied disconnect may be mounted on the unit over the
high--voltage inlet hole (See Fig. 6 and 7).
If the unit has an electric heater, a second disconnect may be
required. Consult the Installation, Start--Up, and Service
Instructions provided with the accessory for electrical service
connections.
Operation of unit on improper line voltage constitutes abuse and
may cause unit damage that could affect warranty.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 2—Electrical Data—50CR
SINGLE POINT POWER
SUPPLY
ELECTRIC HEAT
VOLTAGE
RANGE
V--PH--HZ
COMPRESSOR
OFM
FLA
IFM
FLA
UNIT SIZE
024
NOMINAL
kW*
-- / --
FLA
MCA
MOCP
MIN
MAX
RLA
LRA
-- / --
22.1/22.1
44.6/48.1
54.6/59.6
67.2/74.2
25.1/25.1
47.6/51.1
57.6/62.6
70.2/77.2
29.5/29.5
52.1/55.6
62.0/67.0
74.7/81.6
97.2/107.7
23.7/23.7
36.7/38.7
49.7/53.7
62.7/68.8
35.7/35.7
58.3/61.7
68.2/73.2
80.8/87.8
103.4/113.8
126.0/139.9
27.0/27.0
40.0/42.0
53.0/57.0
66.0/72.1
78.9/86.9
35.0/35.0
57.6/61.1
67.5/72.5
80.2/87.1
102.7/113.2
125.3/139.2
26.8/26.8
39.8/41.8
52.8/56.8
65.9/71.9
78.7/86.7
44.2/44.2
66.8/70.3
76.7/81.7
89.4/96.3
111.9/122.4
134.5/148.4
34.6/34.6
47.6/49.6
60.7/64.7
73.7/79.7
86.6/94.6
30/30
50/50
60/60
70/80
30/30
50/60
60/70
80/80
35/35
60/60
70/70
80/90
100/110
30/30
45/45
50/60
70/70
45/45
70/70
80/80
90/90
110/125
150/150
35/35
50/50
60/60
70/80
80/90
45/45
70/70
80/80
90/90
110/125
150/150
35/35
50/50
60/60
70/80
80/90
60/60
80/90
90/100
100/110
125/125
150/150
40/40
60/60
70/70
80/80
90/100
3.8/5
18.1/20.8
26.0/30.0
36.1/41.7
-- / --
208/230--1--60
208/230--1--60
187
187
253
253
13.5
61.0
0.9
0.9
4.3
4.3
5.4/7.2
7.5/10.0
-- / --
3.8/5
18.1/20.8
26.0/30.0
36.1/41.7
-- / --
030
15.9
16.9
12.2
73.0
83.0
77.0
5.4/7.2
7.5/10.0
-- / --
3.8/5
18.1/20.8
26.0/30.0
36.1/41.7
54.2/62.5
-- / --
208/230--1--60
208/230--3--60
187
187
253
253
0.9
1.6
6.8
6.8
5.4/7.2
7.5/10.0
11.3/15.0
-- / --
036
3.8/5.0
7.5/10.0
11.3/15.0
-- / --
10.4/12.0
20.8/24.1
31.3/36.1
-- / --
3.8/5.0
5.4/7.2
7.5/10.0
11.3/15.0
15.0/20.0
-- / --
18.1/20.8
26.0/30.0
36.1/41.7
54.2/62.5
72.2/83.3
-- / --
208/230--1--60
208/230--3--60
208/230--1--60
208/230--3--60
208/230--1--60
208/230--3--60
187
187
187
187
187
187
253
253
253
253
253
253
22.4
15.4
21.3
14.7
26.9
17.6
105.0
88.0
0.9
0.9
1.6
1.6
1.5
1.5
6.8
6.8
6.8
6.8
9.1
9.1
042
3.8/5.0
7.2/10.0
11.3/15.0
15.0/20.0
-- / --
10.4/12.0
20.8/24.1
31.3/36.1
41.6/48.0
-- / --
3.8/5.0
5.4/7.2
7.5/10.0
11.3/15.0
15.0/20.0
-- / --
18.1/20.8
26.0/30.0
36.1/41.7
54.2/62.5
72.2/83.3
-- / --
109.0
91.0
048
3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
-- / --
10.4/12.0
20.8/24.1
31.3/36.1
41.6/48.0
-- / --
3.8/5.0
5.4/7.2
7.5/10.0
11.3/15.0
15.0/20.0
-- / --
18.1/20.8
26.0/30.0
36.1/41.7
54.2/62.5
72.2/83.3
-- / --
145.0
123.0
060
3.8/5.0
7.5/10.0
11.3/15.0
15.0/20.0
10.4/12.0
20.8/24.1
31.3/36.1
41.6/48.0
12
Download from Www.Somanuals.com. All Manuals Search And Download.
EXAMPLE: Supply voltage is 230-3-60.
AB = 228 v
BC = 231 v
AC = 227 v
LEGEND
FLA
LRA
MCA
— Full Load Amps
— Locked Rotor Amps
-- Minimum Circuit Amps
228 + 231 + 227
®
Average Voltage =
3
MOCP — Maximum Overcurrent Protection
686
3
RLA
— Rated Load Amps
=
= 229
NOTES:
Determine maximum deviation from average voltage.
(AB) 229 - 228 = 1 v
1. In compliance with NEC (National Electrical Code) requirements
for multimotor and combination load equipment (refer to NEC
Articles 430 and 440), the overcurrent protective device for the
unit shall be Power Supply fuse. The CGA (Canadian Gas
Association) units may be fuse or circuit breaker.
(BC) 231 - 229 = 2 v
(AC) 229 - 227 = 2 v
Maximum deviation is 2 v.
2. Minimum wire size is based on 60 C copper wire. I fother than
60 C wire is used, or if length exceeds wire length in table,
determine size from NE.C.
Determine percent of voltage imbalance.
2
229
% Voltage Imbalance = 100 x
3. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%. Use the following formula to determine
the percentage of voltage imbalance.
= 0.8%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
% Voltage imbalance
max voltage deviation from average voltage
= 100 x
IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.
average voltage
Heater capacity (kW) based on heater voltage of 208v & 240v.
If power distibution voltage to unit varies from rated heater
*
voltage, heater kW will vary accordingly.
C03014
Fig. 13 -- Electrical Data Legend
User Interface
Infinity Control Board
D
D
C
B
A
C
B
A
Outdoor Air Thermistor
(if used)
Humidifier
(Optional)
LEGEND
Field Control-Voltage Wiring
A05302
Fig. 14 -- Control Voltage Wiring Connections
13
Download from Www.Somanuals.com. All Manuals Search And Download.
7.0
A05304
Fig. 15 -- Wiring Schematics--50CR Single Phase
14
Download from Www.Somanuals.com. All Manuals Search And Download.
5.0
A05259
Fig. 16 -- Wiring Schematics--50CR Three Phase
15
Download from Www.Somanuals.com. All Manuals Search And Download.
ACCESSORY INSTALLATION
A. Accessory Electric Heaters
GROUND SCREW
(IN SPLICE BOX)
GROUND
LEAD
Electric heaters may be installed in 50CR per instructions supplied
with electric heater package. See unit rating plate for
factory--approved electric heater kits.
BLK
SINGLE-PHASE
CONNECTIONS
TO DISCONNECT
PER NEC
L1
NOTE: Units installed without electric heat should have a
factory--supplied sheet metal block--off plate installed over heater
opening. This reduces air leakage and formation of exterior
condensation.
YEL
BLU
L2
L3
3-PHASE
CONNECTIONS
B. Outdoor Air Thermistor (OAT)
NOTE: Use copper wire only.
A 2--screw terminal strip is provided for connection of an outdoor
temperature thermistor. This strip is marked OAT.
LEGEND
NEC – National Electrical Code
Field Wiring
NOTE: While the installation of an outdoor temperature sensor
using the Infinity control board OAT terminals is optional, certain
Infinity features (ComfortHeat, electric heat lockout, auto humidity
control) will be lost.
Splice Connections
C99057
Fig. 17 -- Line Power Connections
OAT input is used to supply outdoor temperature data for system
level functions and for temperature display on User Interface.
Using two wires of field--supplied thermostat wire cable, wire one
lead of thermistor to one screw terminal and the other lead to
remaining screw terminal; there is no polarity to be observed. It is
strongly recommended that two wires be used to connect the
thermistor to eliminate noise interference in temperature reading. If
there are not two spare wires available in cable, one wire may be
used to connect thermistor to OAT screw terminal 1 and the other
lead of the thermistor can be wired to 24--vac COM (C) wire. OAT
screw terminal 1 is terminal located closest to the ABCD system
communications and is marked with a small number 1 next to the
terminal strip.
NOTE: Mis--wiring OAT inputs will not cause damage to either
Infinity control or thermistor. If the thermistor is wired incorrectly,
no reading will appear at User Interface. Re--wire thermistor
correctly for normal operation.
C. Humidifier Connections
The Infinity control board terminal marked HUM is provided for
low voltage (24--vac) control of a humidifier. No humidistat is
required as User Interface monitors indoor humidity. When
commanded to operate humidifier, the unit control will energize the
HUM output to turn humidifier on and de--energize HUM output to
turn humidifier off. Wire HUM and C terminals directly to
humidifier as shown in Fig. 14.
SPECIAL PROCEDURES FOR 208--V OPERATION
Be sure unit disconnect switch is open.
A05303
Fig. 18 -- Control Plate
Disconnect the yellow primary lead from the transformer. See unit
wiring label. (See Fig. 15, 16 and 18)
The low--voltage circuit is fused by a board--mounted automotive
fuse placed in series with transformer SEC1 and R circuit. The C
circuit of transformer circuit is referenced to chassis groundthrough
a printed circuit run at SEC2 and metal control board mounting
eyelets. Check to be sure control board is mounted securely using
both factory--installed screws.
Connecttheyellow primary lead to thetransformer terminallabeled
200--v.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
3. Make the following inspections:
a. Inspect for shipping and handling damages, such as
broken lines, loose parts, disconnected wires, etc.
SEC-2
SEC-1
b. Inspect for oil at all refrigerant tubing connections and on
unit base. Detecting oil generally indicates a refrigerant
leak. Leak test all refrigerant tubing connections using
electronic leak detector, or liquid--soap solution. If a
refrigerant leak is detected, see following Check for
Refrigerant Leaks section.
c. Inspect all field-- and factory--wiring connections. Be
sure that connections are completed and tight.
d. Ensure wires do not touch refrigerant tubing or sharp
sheet metal edges.
e. Inspect coil fins. If damaged during shipping and
handling, carefully straighten fins with a fin comb.
4. Verify the following conditions:
a. Make sure that outdoor fan blade is correctly positioned
in fan orifice (See Fig. 24).
b. Make sure that condensate drain pan and trap are filled
with water to ensure proper drainage.
c. Make sure that all tools and miscellaneous loose parts
have been removed.
MOTOR
5. Compressors are internally spring mounted. Do not loosen
or remove compressor holddown bolts.
A03169
Fig. 19 -- Detail of Printed Circuit Board
PRE--START--UP
6. Each unit system has two Schrader--typeports, onelow--side
Schrader fitting located on the suction line, and one
high--side Schrader fitting located on the compressor
discharge line. Be sure that caps on the ports are tight.
!
START--UP
WARNING
Step 1—Unit Start--Up
FIRE,EXPLOSION,ELECTRICAL SHOCKHAZARD
NOTE: Always check high-- and low--voltage supply to the unit
components. Check the integrity of the plug receptacle connections
and unit wiring harness prior to assuming a component failure.
Failure to follow this warning could result in personal injury
or death and/or property damage.
1. Follow recognized safety practices and wear protective
goggles when checking or servicing refrigerant system.
2. Do not operate compressor or provide any electric power
to unit unless compressor terminal cover is in place and
secured.
3. Do not remove compressor terminal cover until all
electrical sources are disconnected and tagged.
4. Relieve and recover all refrigerant from system before
touching or disturbing anything inside terminal box if
refrigerant leak is suspected around compressor terminals.
5. Never attempt to repair soldered connection while
refrigerant system is under pressure.
A. LED Description:
LEDs built into Infinityt control board provide installer or service
person information concerning operation and/or fault condition of
the unit control and ECM motor. This information is also available
at the system user interface in text with basic troubleshooting
instructions. Careful use of information displayed will reduce the
need for extensive manual troubleshooting.
The amber LED located at bottom center of control adjacent to
motor harness plug is Motor Status LED and it is labeled MOTOR.
A second amber LED located in upper right center of control
adjacent to System Communications connector (A,B,C,D) is the
System Status LED and it is labeled STATUS. The green LED
labeled COMM is also located adjacent to System Communications
connector, below STATUS LED, and is used as an indicator of
system communications status. Status Codes will be displayed on
the STATUS LED using the following protocol:
6. Do not use torch to remove any component. System
contains oil and refrigerant under pressure.
7. To remove a component, wear protective goggles and
proceed as follows:
a. Shut off electrical power to unit and install lockout
tag.
b. Relieve and reclaim all refrigerant from system
using both high-- and low--pressure ports.
c. Cut component connecting tubing with tubing
cutter and remove component from unit.
d. Carefully unsweat remaining tubing stubs when
necessary. Oil can ignite when exposed to torch
flame.
1. The number of short flashes indicates first digit of code.
2. The number of long flashes indicates second digit of code.
3. A short flash is 0.25 seconds on. A long flash is 1 second on.
4. The time between flashes is 0.25 seconds.
5. The time between last short flash and first long flash is 1
second.
Use the Start--Up Checklist supplied at the end of this book and
proceed as followsto inspectand preparethe unitfor initialstart--up:
6. The LED will be off for 2.5 seconds before repeating code.
B. Control
Start--Up
and
System
Communications
1. Remove all access panels.
Troubleshooting:
2. Read and follow instructions on all DANGER, WARNING,
CAUTION, and INFORMATION labels attached to, or
shipped with unit.
On power up, green COMM LED will be turned off until successful
system communications are established (this should happen within
17
Download from Www.Somanuals.com. All Manuals Search And Download.
10 seconds). Once communications with User Interface are
successful, COMM LED will be lit and held on. At the same time,
amber STATUS LED will be lit and held continuously on until a
request for operating mode is received. The STATUS LED will be
on any time unit is in idle mode.
2. Recheck airflow and system static pressure using User
Interface service screens with access panel in place.
NOTE: Blower motor faults will not cause a lockout of blower
operation. The unit control will attempt to run the blower motor as
long as User Interface maintains a demand for airflow. The unit
control will not operate electric heaters while a fault condition
exists. The unit control communicates with the motor at least once
everyfiveseconds,evenwhenthemotoris idle.If, duringoperation,
the unit control does not communicate with the motor for more than
25 seconds, the motor will shut itself down and wait for
communications to be reestablished.
If, at any time, communications are not successful for a period
exceeding 2 minutes, the Infinity control willonly allow emergency
heating or cooling operation using a common thermostat and the R,
C, Y, O, W terminal strip connections and will display Status Code
16, System Communication Fault, on amber STATUS LED. No
further troubleshooting information will be available at User
Interface until communications are re--established.
D. Using Motor LED in Troubleshooting
If COMM LED does not light within proper time period and status
code is not displayed;
The MOTOR LED is connected to the blower motor
communicationlineand workswith theunit controlmicroprocessor
and the STATUS LED to provide unit operation and
troubleshooting information. When the motor is commanded to
operate, the MOTOR LED will beturned on and willflash each time
instructions are sent to the motor. When the motor is commanded to
stop, the MOTOR LED will be turned off.
1. Check system transformer high-- and low--voltage to be sure
the system is powered.
2. Check fuse on control board to be sure it is not blown. If fuse
is open, check system wiring before replacing it to be sure a
short does not cause a failure of replacement fuse.
If COMM LED does not light within proper time period and status
code is displayed,
If the MOTOR LED is lit, flashing, and the motor is running, or if
the MOTOR LED is off and the motor is stopped, operation is
normal and no motor fault exists.
1. Check system wiring to be sure User Interface is powered
and connections are made A to A, B to B, etc. and wiring is
not shorted. Mis--wiring or shorting of the ABCD
communications wiring will not allow successful
communications.
If the MOTOR LED is lit, flashing, and the motor does not run, or
if the MOTOR LED is off and the motor is running, check the
STATUS LED for the Status Code. Refer to the troubleshooting
instructions for the indicated Status Code in Section E, Unit
Troubleshooting.
NOTE:Shortingormis--wiringlow--voltage systemwiring willnot
cause damage to unit control or user interface but may cause low
voltage fuse to open.
E. Unit Troubleshooting
Unit faults indicated by flashing codes on the amber system
STATUS LED can be resolved using troubleshooting information
provided below. Codes are listed in order of their priority, highest
to lowest. Though multiple faults can exist at any time, only the
highest priority code will be displayed on STATUS LED. Clearing
the indicated fault when multiple faults exist will cause the next
highest priority Status Code tobe flashed.All existingfaults, aswell
as a fault history, can be viewed at User Interface.
C. ECM Motor Troubleshooting
The ECM motor used in this product consists of two parts: the
control module and the motor winding section. Do not assume
motor or module is defective if it will not start. Use the designed--in
LED information aids and follow troubleshooting steps described
below before replacing motor control module or entire motor.
Motor control module is available as a replacement part.
STATUS CODE 45, CONTROL BOARD TEST FAULT
VERIFY MOTOR WINDING SECTION
Unit control has failed internal start--up tests and must be replaced.
No other service procedure will correct.
!
WARNING
STATUS CODE 37, HEATER OUTPUT SENSED “ON” WHEN
NOT ENERGIZED:
ELECTRICAL SHOCK HAZARD
Unitcontrolisprovided with circuitry to detect presenceof a24--vac
signal on electric heater stage 1 and stage 2 outputs.
Failure to follow this warning could result in personal injury
or death.
After disconnecting power from the ECM motor, wait at least
5 minutes before removing the control section. Internal
capacitors require time to discharge.
If unit control detects a 24--vac signal on either heater stage output
and it is not supplying signal, Status Code 37 will be displayed on
STATUS LED. Unit control will turn off output and command
blower motor to supply an airflow determined to be safe for current
operation mode with electric heaters energized.
Before proceeding to replace a motor control module:
1. Check motor winding section to be sure it is functional.
To find the fault:
1. Stop all system operations at User Interface and check heater
stage 24--vac outputs.
2. Remove motor control module section and unplug winding
plug. Motor shaft should turn freely, resistance between any
two motor leads should be similar and resistance between
any motor lead and unpainted motor end should exceed
100,000 ohms.
2. Disconnect electric heater at power and check heater wiring
for faults. See Status Code 36 for more information.
STATUS CODE 44, MOTOR COMMUNICATION FAULT
3. Failing any of these tests, entire ECM motor must be
replaced.
The MOTOR LED is connected to the blower motor
communicationlineand workswith theunit controlmicroprocessor
and STATUS LED to provide unit operation and troubleshooting
information.
4. Passing all of the tests, motor control module alone can be
replaced.
MOTOR TURNS SLOWLY
When motor is commanded to operate, the MOTOR LED will be
turned on and will flash each time instructions are sent to the motor.
1. Low static pressure loading of blower while access panel is
removed will cause blower to run slowly. Particularly at low
airflow requests. This is normal, do not assume a fault exists.
18
Download from Www.Somanuals.com. All Manuals Search And Download.
When the motor is commanded to stop, the MOTOR LED will be
turned off. The MOTOR LED will not flash to indicate
communications when it is turned off.
2. If symptoms persist, disconnect wiring harness at unit
control board and check for a resistance value greater than
5000 ohms.
3. Check for proper wiring of resistor assembly.
Unit control is constantly communicating with the motor, even
when the motor and MOTOR LED are off. If motor does not
acknowledge receipt of communications, the control will display
Status Code 44 on STATUS LED and continue to try to
communicate with the motor. If motor acknowledges
communication, status code will be cleared.
4. Make sure heater size installed is an approved size for unit
and size installed.
NOTE: Unit control will not operate electric heater until this Status
Code is resolved. If the heater size is set through the User Interface,
the heater will be operated as a single stage heater. If staging is
desired, the IDR value must be read in by the unit control.
If MOTOR LED is lit and flashing and motor does not run:
1. Check the STATUS LED. If STATUS LED is indicating a
Status 44 code, check the motor wiring harness for proper
connection to control and motor receptacles.
STATUS CODE 36, HEATER OUTPUT NOT SENSED WHEN
ENERGIZED
Unitcontrolisprovided with circuitry to detect presenceof a24--vac
signal on electric heater stage 1 and stage 2 outputs.
2. Check motor wiring harness to be sure all wiring complies
with wiring diagram description, makes a complete circuit
from connector to connector, and is not shorted.
If unit control energizes either heater stage and does not detect the
24--vac signal on output, Status Code 36 will be displayed on the
STATUS LED, unit control will continue to energize heater
output(s) and adjust blower operation to a safe airflow level for
energized electric heat stage(s).
3. Check 12--vdc low voltage supply to motor at pins 1 (+) and
2 (--) of motor header connection to unit control.
If all checks are normal, unit control is good and control module on
motor may need replacement. Check motor and Motor Control
Module following the instructions in Section C, ECM Motor
Troubleshooting.
To find the fault:
1. Check for 24--vac on heater stage outputs. Unit control or
sensing circuit may be bad.
Shorted or mis--wiring of the low voltage motor harness wiring will
not cause damage to unit control or to motor control module.
NOTE: It may be useful as an electric heater troubleshooting
procedure to disconnect the system communications to force Status
Code 16 enabling of emergency heat mode. It is difficult to know
which heater output is energized or not energized in normal
operation. When unit is operated in emergency heat mode using
electric heaters, both outputs are energized and de--engergized
together. Terminal strip inputs to control can then be connected R to
W to turn on both electric heat outputs. Heater output sensing
circuits can then be checked to resolve Status Code 36 or 37
problems.
If the MOTOR LED is off, STATUS LED is indicating a Status
Code 44 and motor is running:
1. Disconnect the motor harness at the unit control. If motor
continues to run, unit control is good and control module on
motor may need replacement.
STATUS CODE 25, INVALID MOTOR / MODEL SELECTION
On initial start--up, unit control shall poll motor for its size data and
check unit size data stored in unit control memory.
1. If motor size is incorrect for unit size or size data is invalid,
Status Code 25 will be displayed on STATUS LED.
STATUS CODE 41, BLOWER MOTOR FAULT
If MOTOR LED is lit and flashing and motor does not run:
2. If model size data is missing (as is the case when a
replacement control board is installed), system User
Interface will prompt installer to enter correct model size
from a list of valid sizes.
1. Check STATUS LED. If STATUS LED is indicating Status
Code 41, motor control has detected that the motor will not
come up to speed within 30 seconds of being commanded to
run or that the motor has been slowed to below 250 rpm for
more than 10 seconds after coming up to speed. Motor
wiring harness and unit control are operating properly, do
not replace.
3. If motor size is incorrect for model size, motor must be
replaced with proper size motor. Unit control will not
respond to operation requests until this fault condition is
resolved.
2. Check to be sure that the blower wheel is not rubbing the
housing.
STATUS CODE 26, INVALID HEATER SIZE
On initial power--up, unit control will write into memory electric
heater size as read from heater if heater is provided with Identifier
Resistor (IDR). Heater size must be valid for combination of indoor
and outdoor components installed. Unit control will read IDR value
connected to pins 1 and 2 of heater harness connector. If no resistor
is found, system User Interfacewill promptinstaller toverify thatno
heater is installed. Verifying that this is correct will establish that the
unit is operating without an electric heater accessory. Upon
choosing negative option, installer will be prompted to select heater
size installed from a list of valid heater sizes for unit size installed.
3. Check motor to be sure that the motor shaft is not seized
(motor control module must be removed and electronics
disconnected from windings to perform this check
properly).
4. Check motor windings section following instructions in
Section C, ECM Motor Troubleshooting.
If all these checks are normal, the motor control module may need
replacement.
STATUS CODE 16, SYSTEM COMMUNICATION FAULT
If heater ID resistor value read is invalid, Status Code 26 will be
displayed on STATUS LED.
If, at any time, system communications are not successful for a
period exceeding 2 minutes, the unit control will only allow
emergency heating or cooling operation using a common
thermostat,and theR,C,Y,O,W terminal strip connections and will
display Status code 16 on the amber STATUS LED (see section E,
Emergency Heating and Cooling Modes). No further unit
troubleshooting information will be available at the User Interface
until communications are re--established.
If heater installed is equipped with a resistor connected to pins 1 and
2 of heater harness connector and status code 26 is displayed on
STATUS LED:
1. Check wiring harness connectionsto besure connectionsare
secure.
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Check system wiring to be sure the User Interface is powered and
connections are made A to A, B to B, etc., and wiring is not shorted.
Mis--wiring or shorting of the ABCD communications wiring will
not allow successful communications. Correcting wiring faults will
clear the code and re--establish communications.
NOTE: Once the compressor has started and then has stopped, it
should not be started again until 4 minutes have elapsed. The
cooling cycle remains “on” until the room temperature drops to
point that is slightly below the cooling control setting of the user
interface. Additionally, there is a 5--minute compressor delay built
into the control for heat pump heating mode.
Shortingormis--wiringthelowvoltagesystemwiringwill notcause
damage to unit control or to User Interface but may cause the low
voltage fuse to open.
Step 3—Check for Refrigerant Leaks
Locate and repair refrigerant leaks and charge the unit as follows:
STATUS CODE 46, BROWNOUT CONDITION
1. Use both high-- and low--pressure ports to relieve system
pressure and reclaim remaining refrigerant.
If the secondary voltage of the transformer falls below 15--vac for
a period exceeding 4 seconds, Status Code 46 will be displayed on
STATUS LED and the User Interface will command the control
board to turn off Y output controlling compressor.
2. Repair leak following accepted practices.
NOTE: Install a bi--flow filter drier whenever the system has been
When secondary voltage rises above 17--vac for more than 4
seconds, the brownout condition is cleared and normal system
operation will resume subject to any minimum compressor
off--delayfunctionwhich maybe ineffect. Brownoutdoes notaffect
blower or electric heater operation.
opened for repair.
3. Check system for leaks using an approved method.
4. Evacuate refrigerant system and reclaim refrigerant if no
additional leaks are found.
5. Charge unit with Puron (R--410A) refrigerant, using a
volumetric--charging cylinder or accurate scale. Refer to unit
rating plate for required charge.
STATUSCODE53,OUTDOORAIR TEMPERATURESENSOR
FAULT
If an OAT sensor is found at power--up, input is constantly checked
to be within a valid temperature range. If sensor is found to be open
or shorted at any time after initial validation, Status Code 53 will be
displayed at amber STATUS LED.
Step 4—Start--Up Adjustments
Complete the required procedures given in the Pre--Start--Up
section before starting the unit. Do not jumper any safety devices
when operating the unit. Do not operate the unit in cooling mode
when the outdoor temperature is below 40°F (unless accessory
low--ambient kit is installed). Do not rapid cycle the compressor.
Allow 5 min. between “on” cycles to prevent compressor damage.
Check for faults in wiring connecting sensor to OAT terminals.
Using an Ohm meter, check resistance of thermistor for a short or
open condition.
If thermistor is shorted or open, replace it to return the system to
normal operation.If faultis inthe wiringconnections, correctingthe
fault will clear the code and return the system to normal operation.
CHECKING COOLING AND HEATING CONTROL
OPERATION
Start and check the unit for proper control operation as follows:
NOTE: If fault condition is an open thermistor or a wiring problem
that appears to be an open thermistor and the power to the unit is
cycled off, the fault code will be cleared on the next power--up but
the fault will remain and system operation will not be as expected.
Thisisbecauseon power--up, theunit controlcannot discern the
difference between an open sensor or if a sensor is not installed.
1. Place room UI SYSTEM switch or MODE control in OFF
position. Observe that blower motor starts when FAN mode
is placed in FAN ON position and shuts down within 60 sec
(030--060 size) or 30 sec (024 size) when FAN MODE
switch is placed in AUTO position.
Step 2—Sequence of Operation
2. PlacesystemswitchorMODEcontrolinHEAT position.Set
control above room temperature. Observe that compressor,
outdoor fan, and indoor blower motors start. Observe that
heating cycle shuts down when control setting is satisfied.
The packaged heat pump is designed for installation with a
communicating User Interface. This unit will not respond to
commands provided by a common thermostat except under certain
emergency situations described in Step 1—Start--Up.
3. When using an automatic changeover room thermostat,
place both SYSTEM or MODE control and FAN mode
switches in AUTO positions. Observe that unit operates in
cooling mode when temperature control is set to “call for
cooling” (below room temperature), and unit operates in
heating mode when temperature control is set to “call for
heating” (above room temperature).
The User Interface uses temperature, humidity and other data
supplied from indoor and outdoor system components to control
heating or cooling system for optimum comfort. The unit will be
commanded by User Interface to supply airflow. The unit will
operate the indoor blower at requested airflow for most modes.
The nominal requested airflow will be 350 cfm per ton of nominal
cooling capacity as defined by unit size. Actual airflow request will
be adjusted from nominal using indoor and outdoor temperature
and indoor humidity data to optimize the system operation for
occupant comfort and system efficiency. Refer to User Interface
literature for further system control details.
IMPORTANT: Three--phase, scroll compressors are direction
oriented. Unit must be checked to ensure proper compressor
3--phase power lead orientation. If not corrected within 5 minutes,
the internal protector will shut off the compressor. The 3--phase
power leads to the unit must be reversed to correct rotation. When
turning backwards, the difference between compressor suction and
discharge pressures may be dramatically lower than normal.
Airflow during electric heater operation must be greater than a
minimum level for safe operation. If User Interface instructs unit to
turn on electric heat and the requested airflow is less than the
minimum level the unit control will override requested value.
20
Download from Www.Somanuals.com. All Manuals Search And Download.
INDOOR COIL
OUTDOOR COIL
TXV in Metering
Position
LCS
HPS
Bypass
Position
LEGEND
HPS – High Pressure Switch
LCS – Loss of Charge Switch
®
Accurater Metering Device
Arrow indicates direction of flow
C03011
Fig. 20 -- Typical Heat Pump Operation, Cooling Mode
INDOOR COIL
OUTDOOR COIL
TXV in Bypass
Position
LCS
HPS
Metering
Position
LEGEND
HPS – High Pressure Switch
LCS – Loss of Charge Switch
®
Accurater Metering Device
Arrow indicates direction of flow
C03012
Fig. 21 -- Typical Heat Pump Operation, Heating Mode
21
Download from Www.Somanuals.com. All Manuals Search And Download.
CHECKING AND ADJUSTING REFRIGERANT CHARGE
When Quiet Shift switch is placed in ON position, and a defrost is
initiated, the following sequence of operation will occur. Reversing
valve will energize, outdoor fan will turn off, compressor will turn
off for 30 sec and then turn back on to complete defrost. At the start
of heating after conclusion of defrost reversing valve will
de--energize, compressor will turn off for another 30 sec, and the
outdoor fan will stay off for 40 sec, before starting in the heating
mode.
The refrigerant system is fully charged with Puron (R--410A)
refrigerant and is tested and factory sealed.
NOTE: Adjustment of the refrigerant charge is not required unless
the unit is suspected of not having the proper R--410A charge. The
charging labeland thetablesshown referto system temperaturesand
pressures in cooling mode only. A refrigerant charging label is
attached to the outside of the service access door. If charge level is
suspect in heating mode, reclaim all refrigerant and charge to
informative plate amount. (This information may be obtained from
the physical data table also.) The charging label and the tables
shown refer to system temperatures and pressures in cooling mode
only. A refrigerant charging label is attached to the outside of the
service access door.
DEFROST
The defrost control is a time/temperature control which includes a
field--selectable time period (DIP switch 1 and 2 on the board)
between defrost cycles of 30, 60, 90, or 120 minutes (factory set at
30 minutes).
To initiate a forced defrost, two options are available depending on
the status of the defrost thermostat.
IMPORTANT: When evaluating the refrigerant charge, an
indicated adjustment to the specified factory charge must always be
very minimal. If a substantial adjustment is indicated, an abnormal
condition exists somewhere in the cooling system, such as
insufficient airflow across either coil or both coils.
If defrost thermostat is closed, speedup pins (J1) must be shorted by
placing a flat head screw driver in between for 5 sec and releasing,
to observe a complete defrost cycle. When the Quiet Shift switch is
selected, compressor will be turned off for two 30 sec intervals
during this complete defrost cycle, as explained previously. When
Quiet Shift switch is in factory default OFF position, a normal and
complete defrost cycle will be observed.
REFRIGERANT CHARGE
The amount of refrigerant charge is listed on the unit rating plate
and/or the physical data table. Refer to the Refrigeration Service
Techniques Manual, Refrigerants Section.
If defrost thermostat is in open position, and speedup pins are
shorted (with a flat head screw driver) for 5 sec and released, a short
defrost cycle will be observed (actual length is dependent upon the
selected Quiet Shift position). When Quiet Shift switch is in ON
position, the length of defrost is 1 minute (30 sec compressor off
period followed by 30 sec of defrost with compressor operation).
On return to heating operation, compressor will again turn off for an
additional 30 sec and the outdoor fan for 40 sec. When the Quiet
Shift is in OFF position, only a brief 30 sec cycle will be observed.
NO CHARGE
Check for leak. Use standard evacuating techniques. After
evacuating system, weigh in the specified amount of refrigerant
(refer to system rating plate).
LOW CHARGE COOLING
Use Cooling Charging Chart (Fig. 22). Vary refrigerant until the
conditions of the chart are met. Note that charging charts are
different from type normally used. Charts are based on charging the
units to correct subcooling for the various operating conditions.
Accurate pressure gauge and temperature sensing devices are
required. Connect the pressure gauge to the service port on the
suction line. Mount the temperature sensing device on the suction
line and insulate it so that the outdoor ambient does not affect the
reading. Indoor air CFM must be within the normal operating range
of the unit.
If it is desirable to observea completedefrost inwarmer weather,the
defrost thermostat must be closed as follows:
1. Turn off power to outdoor unit.
2. Disconnect outdoor fan motor lead from OF2 on control
board (See Fig. 23). Tape to prevent grounding.
3. Restartunitin heating mode,allowing frostto accumulateon
outdoor coil.
4. After
a
few minutes in heating mode, liquid--line
temperature should drop below closing point of defrost
thermostat (approximately 30°F).
TO USE COOLING CHARGING CHARTS
Take the liquid line temperature and read the manifold pressure
gauges. Refer to the chart to determine what the liquid line
temperature should be.
NOTE: Unit will remain in defrost until defrost thermostat reopens
at approximately 80°F coil temperature at liquid line or remainder
of defrost cycle time.
NOTE: If the problem causing the inaccurate readings is a
refrigerant leak, refer to Check for Refrigerant Leaks section.
5. Turn off power to outdoor and reconnect fan motor lead to
OF2 on control board after above forced defrost cycle.
INDOOR AIRFLOW AND AIRFLOW ADJUSTMENTS
NON--COMMUNICATING EMERGENCY COOLING
HEATING MODE
/
NOTE: Be sure that all supply-- and return--air grilles are open, free
from obstructions, and adjusted properly.
This mode ofoperation isprovided onlyin thecase wherethe UIhas
failed or is otherwise unavailable. If communications cannot be
established with the UI, the Infinity control board will enable the
following thermostat input terminals to allow simple thermostatic
control of the 50CR unit:
Unit 50CR utilizes state of the art ECM (Electronic Computated
Motor) ID Blower Motors. See user interface instructions for
detailed information on adjusting airflow.
Step 5—Defrost Control
a. Y & O for cooling
QUIET SHIFT
b. W for electric heat (if applicable)
c. Y for heat pump heat
Quiet Shift is a field--selectable defrost mode, which will eliminate
occasional noise that could be heard at the start of defrost cycle and
restarting of heating cycle. It is selected by placing DIP switch 3 (on
defrost board) in ON position.
The Infinity control will respond to cooling and heating demands
with the maximum safe airflow based on electric heat size (if
applicable) and unit capacity.
22
Download from Www.Somanuals.com. All Manuals Search And Download.
Required Subcooling oF (oC)
Outdoor Ambient Temperature
Required Liquid Line Temperature for a Specific Subcooling (R-410A)
Required Subcooling (oF) Required Subcooling (oC)
Model Size
Pressure
(psig)
Pressure
(kPa)
75 (24)
82 (28)
85 (29)
95 (35)
105 (41)
5
10
56
58
61
63
15
51
53
56
58
20
46
48
51
53
25
41
43
46
48
3
6
8
11
8
14
5
024
030
036
042
048
060
10.3 ( 5.7 )
9.3 ( 5.2 )
17.6 ( 9.8 )
12.8 ( 7.1 )
17.5 ( 9.7 )
13.7 ( 7.6 )
9.8 ( 5.4 )
8.8 ( 4.9 )
16.8 ( 9.3 )
12.7 ( 7.1 )
16.9 ( 9.4 )
13 ( 7.2 )
9.4 ( 5.2 )
8.6 ( 4.8 )
16.5 ( 9.2 )
12.7 ( 7.1 )
16.6 ( 9.2 )
13 ( 7.2 )
9 ( 5 )
8.6 ( 4.7 )
7 ( 3.9 )
14.3 ( 7.9 )
12.6 ( 7 )
14.8 ( 8.2 )
11.5 ( 6.4 )
189
196
203
210
217
224
231
238
245
252
260
268
276
284
292
300
309
318
327
336
345
354
364
374
384
394
404
414
424
434
444
454
464
474
484
494
504
514
524
534
61
63
66
68
70
72
1303
1351
1399
1448
1496
1544
1593
1641
1689
1737
1792
1848
1903
1958
2013
2068
2130
2192
2254
2316
2378
2440
2509
2578
2647
2716
2785
2854
2923
2992
3061
3130
3199
3268
3337
3406
3475
3544
3612
3681
16
17
19
20
21
22
23
24
25
26
27
29
30
31
32
33
34
35
36
37
38
39
40
41
42
44
45
46
47
48
48
49
50
51
52
53
54
55
56
56
13
15
16
17
18
19
20
21
22
23
25
26
27
28
29
30
31
32
33
34
35
36
38
39
40
41
42
43
44
45
46
47
48
48
49
50
51
52
53
54
11
12
13
14
15
16
18
19
20
21
22
23
24
25
26
27
28
29
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
47
48
49
50
51
7.8 ( 4.3 )
15.4 ( 8.6 )
12.6 ( 7 )
15.7 ( 8.7 )
14.5 ( 8.1 )
9
6
8
9
10
11
13
14
15
16
17
18
19
20
21
22
23
24
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
46
47
48
65
67
60
62
55
57
50
52
10
11
12
13
14
15
16
17
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
45
Charging Procedure
74
76
69
71
64
66
59
61
54
56
77
79
81
83
72
74
76
78
67
69
71
73
62
64
66
68
57
59
61
63
1- Measure Discharge line pressure by attaching a gauge to the service port.
2- Measure the Liquid line temperature by attaching a temperature sensing
device to it.
3- Insulate the temperature sensing device so that the Outdoor Ambient
doesn’t affect the reading.
85
87
89
91
80
82
84
86
75
77
79
81
70
72
74
76
65
67
69
71
4- Refer to the required Subcooling in the table based on the model size and
the Outdoor Ambient temperature.
5- Interpolate if the Outdoor ambient temperature lies in between the table
values. Extrapolate if the temperature lies beyond the table range.
93
95
97
99
88
90
92
94
83
85
87
89
78
80
82
84
73
75
77
79
6- Find the Pressure Value in the table corresponding to the the measured
Pressure of the Compressor Discharge line.
7- Read across from the Pressure reading to obtain the Liquid line
temperature for a required Subcooling
101
103
105
107
108
110
112
114
116
118
119
121
123
124
126
127
129
131
132
134
96
98
91
93
95
97
86
88
90
92
81
83
85
87
8- Add Charge if the measured temperature is higher than the table value.
100
102
103
105
107
109
111
113
114
116
118
119
121
122
124
126
127
129
98
93
95
97
99
88
90
92
94
100
102
104
106
108
109
111
113
114
116
117
119
121
122
124
101
103
104
106
108
109
111
112
114
116
117
119
96
98
99
101
103
104
106
107
109
111
112
114
C03027
Fig. 22 -- Cooling Charging Table--Subcooling
Table 3—ECM Wet Coil Pressure Drop (in. wg)
STANDARD CFM (SCFM)
UNIT
SIZE
600
700
800
900
0.012
0.012
0.019
–
1000
0.015
0.015
0.023
0.014
–
1100
–
1200
–
1300
–
1400
–
1500
–
1600
–
1700
–
1800
1900
2000
2100
024
030
036
042
048
060
0.005
0.007
0.010
–
–
–
–
–
–
–
–
–
–
–
–
–
0.007
0.010
0.018
0.027
0.017
–
0.021
0.032
0.020
0.027
–
0.024
0.037
0.024
0.032
–
–
–
–
–
–
–
–
–
–
–
–
–
–
0.042
0.027
0.036
–
0.047
0.031
0.041
0.029
–
–
–
–
–
–
0.035
0.046
0.032
0.039
0.052
0.036
0.043
0.057
0.040
–
–
–
0.063
0.045
0.068
0.049
–
–
–
–
0.053
Table 4—Filter Pressure Drop Table (in. wg)
CFM
FILTER SIZE
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300
20X20X1
24X30X1
24X36X1
0.05 0.07 0.08 0.1 0.12 0.13 0.14 0.15
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
0.05 0.6 0.07 0.07 0.08 0.09 0.1
—
—
—
0.06 0.07 0.07 0.08 0.09 0.09 0.10 0.11 0.12 0.13 0.14 0.14
Table 5—Electric Heat Pressure Drop Table
Small Cabinet: 024--036
CFM
500
0.00
0.00
0.00
0.00
0.00
600
700
0.00
0.00
0.00
0.00
0.02
800
0.00
0.00
0.00
0.02
0.04
900
0.00
0.00
0.00
0.04
0.06
1000
0.00
0.00
0.02
0.06
0.08
1100
0.00
0.02
0.04
0.08
0.09
1200
0.00
0.03
0.06
0.10
0.11
1300
0.02
0.05
0.07
0.12
0.13
1400
0.04
0.07
0.09
0.14
0.15
1500
0.06
0.08
0.10
0.16
0.17
1600
0.07
0.09
0.11
0.18
0.19
5 kw
7.2 kw
10 kw
15 kw
20 kw
0.00
0.00
0.00
0.00
0.00
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 6—Electric Heat Pressure Drop Table
Large Cabinet: 042--060
CFM
1100
0.00
0.00
0.00
0.00
0.02
1200
0.00
0.00
0.00
0.02
0.03
1300
0.00
0.01
0.01
0.03
0.04
1400
0.01
0.02
0.02
0.04
0.05
1500
0.02
0.03
0.03
0.05
0.06
1600
0.03
0.04
0.04
0.06
0.07
1700
0.04
0.05
0.05
0.07
0.08
1800
0.05
0.06
0.06
0.08
0.09
1900
0.06
0.07
0.07
0.09
0.10
2000
0.07
0.08
0.08
0.10
0.11
2100
0.08
0.09
0.09
0.11
0.12
2200
0.09
0.10
0.10
0.12
0.13
2300
0.10
0.11
0.11
0.13
0.14
2400
0.11
0.12
0.12
0.14
0.15
2500
0.12
0.13
0.13
0.15
0.16
5kw
7.2 kw
10 kw
15 kw
20 kw
CESO130076–00
Speedup
Pins
Quiet
Shift
Defrost interval
DIP switches
Fig. 23 -- Defrost Control
MAINTENANCE
!
WARNING
To ensure continuing high performance, and to minimize the
possibility of premature equipment failure, periodic maintenance
must be performed on this equipment. This heat pump unit should
be inspected at least once each year by a qualified service person. To
troubleshoot unit, refer to Table 8, Troubleshooting Chart.
ELECTRICAL SHOCK HAZARD
Failure to follow these warnings could result in serious injury
or death:
1. Turn off electrical power to the unit before performing any
maintenance or service on this unit.
NOTE TO EQUIPMENT OWNER: Consult your local dealer
about the availability of a maintenance contract.
2. Use extreme caution when removing panels and parts.
!
3. Never place anything combustible either on or in contact
with the unit.
WARNING
PERSONAL INJURY AND UNIT DAMAGE HAZARD
Failure to follow this warning could result in personal injury
or death and possible unit component damage.
!
CAUTION
The ability to properly perform maintenance on this
equipment requires certain expertise, mechanical skills, tools
and equipment. If you do not possess these, do not attempt to
perform any maintenance on this equipment, other than those
procedures recommended in the Owner’s Manual.
UNIT OPERATION HAZARD
Failure to follow this caution may resultin equipmentdamage
or improper operation.
Errors made when reconnecting wires may cause improper
and dangerous operation. Label all wires prior to
disconnecting when servicing.
24
Download from Www.Somanuals.com. All Manuals Search And Download.
The minimum maintenance requirements for this equipment are as
follows:
Step 4—Outdoor Fan
1. Inspect air filter(s) each month. Clean or replace when
necessary.
!
CAUTION
2. Inspect indoor coil, drain pan, and condensate drain each
cooling season for cleanliness. Clean when necessary.
UNIT OPERATION HAZARD
Failure to follow this caution may result in damage to unit
components.
3. Inspect blower motor and wheel for cleanliness each cooling
season. Clean when necessary.
Keep the condenser fan free from all obstructions to ensure
proper cooling operation. Never place articles on top of the
unit.
4. Check electrical connections for tightness and controls for
proper operation each cooling season. Service when
necessary.
1. Remove 6 screws holding outdoor grille and motor to top
cover.
Step 1—Air Filter
IMPORTANT: Never operate the unit without a suitable air filter
in the return--air duct system.Always replacethe filterwith thesame
dimensional size and type as originally installed. See Table 1 for
recommended filter sizes.
2. Turn motor/grille assembly upside down on top cover to
expose fan blade.
3. Inspect the fan blades for cracks or bends.
4. If fan needs to be removed, loosen setscrew and slide fan off
motor shaft.
Inspect air filter(s) at least once each month and replace
(throwaway--type) or clean (cleanable--type) at least twice during
each cooling season and twice during the heating season, or
whenever the filter becomes clogged with dust and lint.
5. When replacing fan blade, position blade so that the hub is
1/8 in. away from the motor end (1/8 in. of motor shaft will
be visible) (See Fig. 24).
Step 2—Indoor Blower and Motor
6. Ensure that set screw engages the flat area on the motor shaft
when tightening.
NOTE: All motors are pre--lubricated. Do not attempt to lubricate
these motors.
7. Replace grille.
For longerlife, operatingeconomy, andcontinuing efficiency,clean
accumulated dirt and grease from the blower wheel and motor
annually.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Infinity Top
A06035
Disconnect and tag electrical powerto theunit beforecleaning
and lubricating the blower motor and wheel.
“A” DIMENSION
UNIT SIZE
Infinity
024
030
036
042
048
060
25
25
24
24
24
19
Step 3—Outdoor Coil, Indoor Coil, and Condensate
Drain Pan
Inspect the condenser coil, evaporator coil, and condensate drain
pan at least once each year.
The coils are easily cleaned when dry; therefore, inspect and clean
the coils either before or after each cooling season. Remove all
obstructions, including weeds and shrubs, that interfere with the
airflow through the condenser coil. Straighten bent fins with a fin
comb. If coated with dirt or lint, clean the coils with a vacuum
cleaner, using the soft brush attachment. Be careful not to bend the
fins. If coated with oil or grease, clean the coils with a mild detergent
and watersolution.Rinsecoilswith clearwater, using a garden hose.
Be careful not to splash water on motors, insulation, wiring, or air
filter(s). For best results, spray condenser coil fins from inside to
outside the unit. On units with an outer and inner condenser coil, be
sure to clean between the coils. Be sure to flush all dirt and debris
from the unit base.
Fig. 24 -- Fan Blade Clearance
Step 5—Electrical Controls and Wiring
Inspect and check the electrical controls and wiring annually. Be
sure to turn off the electrical power to the unit.
Remove access panel to locate all the electrical controls and wiring.
Check all electrical connections for tightness. Tighten all screw
connections. If any smoky or burned connections are noticed,
disassemble the connection, clean all the parts, re--strip the wire end
and reassemble the connection properly and securely.
After inspecting the electrical controls and wiring, replace all the
panels. Start the unit, and observe at least one complete cooling
cycle to ensure proper operation. If discrepancies are observed in
operating cycle, or if a suspected malfunction has occurred, check
each electrical component with the proper electrical
instrumentation. Refer to the unit wiring label when making these
checks.
Inspect the drain pan and condensate drain line when inspecting the
coils. Clean the drain pan and condensate drain by removing all
foreign matter from the pan. Flush the pan and drain trough with
clear water. Do not splash water on the insulation, motor, wiring, or
air filter(s). If the drain trough is restricted, clear it with a “plumbers
snake” or similar probe device.
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Balance Point Worksheet
70
60
50
40
30
20
10
0
Based on Entering Indoor Air of 70 Deg. F and Rated CFM
060
048
042
036
030
024
-20
-10
0
10
20
30
40
50
60
Outdoor Air Temp (Deg F)
C03008
Fig. 25 -- 50CR Balance Point Worksheet
Step 6—Refrigerant Circuit
Inspect all refrigerant tubing connections and the unit base for oil
accumulation annually. Detecting oil generally indicates a
refrigerant leak.
If oil is detected or if low performance is suspected, leak test all
refrigerant tubing using an electronic leak detector, or liquid--soap
solution. If a refrigerant leak is detected, refer to Check for
Refrigerant Leaks section.
If no refrigerant leaks are found and low performance is suspected,
refer to Checking and Adjusting Refrigerant Charge section.
Step 7—Indoor Airflow
Theheating and/orcooling airflowdoes notrequire checkingunless
improper performance is suspected. If a problem exists, be sure that
all supply-- and return--air grilles are open and free from
obstructions, and that the air filter is clean.
Step 8—Metering Devices--TXV & Accurater Piston
This unit uses 2 types of metering devices. The outdoor metering
device is a fixed orifice and iscontained inthe brass--hexbody inthe
liquid line feeding the outdoor coils. The indoor metering device is
a TXV--type device.
Step 9—Pressure Switches
C99097
Pressure switches are protective devices wired into control circuit
(low voltage). They shut off compressor if abnormally high or low
pressures are present in the refrigeration circuit. These pressure
switches are specifically designed to operate with Puron (R--410A)
systems. R--22 pressure switches must not be used as replacements
for the Puron (R--410A) system.
Fig. 26 -- Refrigerant Circuit
Step 10—Loss--of--Charge Switch
This switch is located on the liquid line and protects against low
suction pressures caused by such events as loss of charge, low
26
Download from Www.Somanuals.com. All Manuals Search And Download.
airflow across indoor coil, dirty filters, etc. It opens on a pressure
drop at about 20 psig. If system pressureis abovethis, switchshould
be closed. To check switch:
REFRIGERANT
!
CAUTION
1. Turn off all power to unit.
2. Disconnect leads on switch.
PERSONAL INJURY, UNIT OPERATION HAZARD
3. Apply ohm meter leads across switch. You should have
continuity on a good switch.
Failure to follow this caution may result in personal injury,
equipment damage or improper operation.
This system uses Puron (R--410A) refrigerant which has
higher operating pressures than R--22 and other refrigerants.
No other refrigerant may be used in this system. Gauge set,
hoses,andrecoverysystemmustbe designedto handlePuron.
If you are unsure, consult the equipment manufacturer.
NOTE: Because these switches are attached to refrigeration system
under pressure, it is not advisable to remove this device for
troubleshooting unless you are reasonably certain that a problem
exists. If switch must be removed, remove and recover all system
charge so that pressure gauges read 0 psi. Never open system
without breaking vacuum with dry nitrogen.
COMPRESSOR OIL
Step 11—High--Pressure Switch
The compressor in this system uses a polyolester (POE) oil, Mobil
3MA POE. This oil is extremely hygroscopic, meaning it absorbs
water readily. POE oils can absorb 15 times as much water as other
oils designed for HCFC and CFC refrigerants. Take all necessary
precautions to avoid exposure of the oil to the atmosphere.
The high--pressure switch is located in the discharge line and
protects against excessive condenser coil pressure. It opens at 650
psig.
High pressure may be caused by a dirty outdoor coil, failed fan
motor, or outdoor air recirculation.
SERVICING SYSTEMS ON ROOFS WITH SYNTHETIC
MATERIALS
To check switch:
POE (polyolester) compressor lubricants are known to cause long
term damage to some synthetic roofing materials.
1. Turn off all power to unit.
2. Disconnect leads on switch.
Exposure, even if immediately cleaned up, may cause
embrittlement (leading to cracking) to occur in one year or more.
When performing any service that may risk exposure ofcompressor
oil to the roof, take appropriate precautions to protect roofing.
Procedures which risk oil leakage include, but are not limited to,
compressor replacement, repairing refrigerant leaks, and replacing
refrigerant components such as filter drier, pressure switch,
metering device, coil, accumulator, or reversing valve.
3. Apply ohm meter leads across switch. You should have
continuity on a good switch.
Step 12—Copeland Scroll Compressor (Puron Refrigerant)
The compressor used in this product is specifically designed to
operate with Puron (R--410A) refrigerant and cannot be
interchanged.
The compressor is an electrical (as well as mechanical) device.
Exercise extreme caution when working near compressors. Power
should be shut off, if possible, for most troubleshooting techniques.
Refrigerants present additional safety hazards.
Synthetic Roof Precautionary Procedure
1. Cover extended roof working area with an impermeable
polyethylene (plastic) drip cloth or tarp. Cover an
approximate 10 X 10 ft area.
2. Cover area in front of the unit service panel with a terry cloth
shop towel to absorb lubricant spills and prevent run--offs,
and protect drop cloth from tears caused by tools or
components.
!
WARNING
EXPLOSION,FIRE,ELECTRICAL SHOCKHAZARD
Failure to follow this warning could result in personal injury
or death and/or property damage.
3. Place terry cloth shop towel inside unit immediately under
component(s) to be serviced and prevent lubricant run--offs
through the louvered openings in the unit base.
Wear safety glasses and gloves when handling refrigerants.
Keep torches and other ignition sources away from
refrigerants and oils.
4. Perform required service.
5. Remove and dispose of any oil--contaminated material per
local codes.
The scroll compressor pumps refrigerant throughout the system by
the interaction of a stationary and an orbiting scroll. The scroll
compressor has no dynamic suction or discharge valves, and it is
more tolerant of stresses caused by debris, liquid slugging, and
flooded starts. The compressor is equipped with an anti--rotational
device and an internal pressure--relief port. The anti--rotational
device prevents the scroll from turning backwards and replaces the
need for a cycle protector.The pressure--reliefport isa safetydevice,
designed to protect against extreme high pressure. The relief port
has an operating range between 550 and 625 psi differential
pressure.
LIQUID--LINE FILTER DRIER
The biflow filter drieris specifically designed to operate with Puron.
Use only factory--authorized components. Filter drier must be
replaced whenever the refrigerant system is opened. When
removing a filter drier, use a tubing cutter to cut the drier from the
system. Do not unsweat a filter drier from the system. Heat from
unsweating will release moisture and contaminants from drier into
system.
PURON (R--410A) REFRIGERANT CHARGING
The Copeland scroll compressor uses Mobil 3MA POE oil. This
is the only oil allowed for oil recharge.
Refer to unit information plate and charging chart. Some R--410A
refrigerant cylinders contain a dip tube to allow liquid
refrigerant to flow from cylinder in upright position. For
cylinders equipped with a dip tube, charge Puron units with
cylinder in upright position and a commercial metering device in
manifold hose. Charge refrigerant into suction line.
Step 13—Refrigerant System
®
This step covers the refrigerant system of the 50CR, including the
compressor oil needed, servicing systems on roofs containing
synthetic materials, the filter drier, and refrigerant charging.
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Step 14—System Information
Unit Top
LOSS--OF--CHARGE SWITCH
The loss of charge switch is a protective device wired into control
circuit (low voltage). It shuts off the compressor if abnormally low
pressures are present in the refrigeration circuit.
Defrost
Sensor
NOTE: Because these switches are attached to refrigeration system
under pressure, it is not advisable to remove this device for
troubleshooting unless you are reasonably certain that a problem
exists. If switch must be removed, remove and recover all system
charge so that pressure gauges read 0 psi. Never open system
without breaking vacuum with dry nitrogen.
CHECK DEFROST THERMOSTAT
There is a liquid header with a brass distributor and feeder tube
going into outdoor coil. At the end of one of the feeder tubes, there
isa 3/8--in.OD stubtube approximately3 in.long (SeeFig. 27).The
defrost thermostat should be located on stub tube.
NOTE: There is only one stub tube used with liquid header, and on
most units it is the bottom circuit.
Detail A
The defrost thermostat signals heat pump that conditions are right
for defrost or that conditions have changed to terminate defrost. It
is a thermally--actuated switch clamped to outdoor coil to sense its
temperature. Normal temperature range is closed at 30° ± 3°F and
open at 80° ± 5°F.
TROUBLESHOOTING
See
Detail A
Refer to the Cooling and Heating Troubleshooting Chart (Table 7)
for troubleshooting information.
START--UP CHECKLIST
Use the Start--Up Checklist at the back of this manual.
A06068
Fig. 27 -- Defrost Sensor Location
28
Download from Www.Somanuals.com. All Manuals Search And Download.
HEAT PUMP WITH PURON
REFRIGERATION SECTION QUICK--REFERENCE GUIDE
Puron refrigerant operates at 50--70 percent higher pressures than R--22. Be sure that servicing equipment and replacement components are
designed to operate with Puron. Puron refrigerant cylinders are rose colored.
S
Puron refrigerant cylinders manufactured prior to March 1, 1999, have a dip tube that allows liquid to flow out of cylinder in
upright position. Cylinders manufactured March 1, 1999 and later DO NOT have a dip tube and MUST be positioned upside down
to allow liquid to flow.
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
Recovery cylinder service pressure rating must be 400 psig. DOT 4BA400 or DOT BW400.
Puron systems should be charged with liquid refrigerant. Use a commercial--type metering device in the manifold hose.
Manifold sets should be 750 psig high side and 200 psig low side with 520 psig low side retard.
Use hoses with 750 psig service pressure rating.
Leak detectors should be designed to detect HFC refrigerant.
Puron, as with other HFCs, is only compatible with POE oils.
Vacuum pumps will not remove moisture from oil.
Only use factory--specified liquid--line filter driers with rated working pressures no less than 600 psig.
Do not install a suction--line filter drier in liquid line.
POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
POE oils may cause damage to certain plastics and roofing materials.
Wrap all filter driers and service valves with wet cloth when brazing.
A Puron liquid--line filter drier is required on every unit.
Do not use an R--22 TXV.
Never open system to atmosphere while it is under a vacuum.
When system must be opened for service, break vacuum with dry nitrogen and replace filter driers.
Do not vent Puron into the atmosphere.
Observe all warnings, cautions, and bold text.
Do not leave Puron suction line driers in place for more than 72 hrs.
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 7—Troubleshooting Chart
SYMPTOM
CAUSE
REMEDY
Call power company
Power failure
Fuse blown or circuit breaker tripped
Replace fuse or reset circuit breaker
Defective contactor, transformer, control relay, defrost
board, or high--pressure, loss--
of--charge or low--pressure switch
Replace component
Insufficient line voltage
Determine cause and correct
Check wiring diagram and rewire correctly
Reset UI setting
Compressor and outdoor fan
will not start
Incorrect or faulty wiring
User Interface setting too low/too high
DO NOT bypass this compressor time
delay–wait for 5 minutes until time--delay
relay is de--energized
Units have a 5--minute time delay
Faulty wiring or circuit
Loose connections in compressor
Check wiring and repair or replace
Compressor motor burned out, seized, or
internal overload open
Defective run capacitor, overload, or PTC (positive
temperature coefficient) thermistor
Determine cause
Replace compressor
Compressor will not start but condenser fan
runs
Determine cause and replace
Replace fuse or reset circuit breaker
Determine cause
One leg of 3--phase power dead
Low input voltage (20 percent low)
Determine cause and correct
Three--phase scroll compressor (size 030--
060 unit) has a low pressure differential
Correct the direction of rotation by reversing the
3--phase power leads to the unit
Scroll compressor is rotating in the wrong direction
Recover refrigerant, evacuate system, and re-
charge to capacities shown on rating plate
Refrigerant overcharge or undercharge
Defective compressor
Insufficient line voltage
Blocked outdoor coil
Defective run/start capacitor, overload or start relay
Faulty outdoor fan motor or capacitor
Damaged reversing valve
Restriction in refrigerant system
Dirty air filter
Replace and determine cause
Determine cause and correct
Determine cause and correct
Determine cause and replace
Replace
Determine cause and correct
Locate restriction and remove
Replace filter
Compressor cycles (other than normally satis-
fying) cooling/heating calls
Unit undersized for load
UI temperature set too low/too high
Low refrigerant charge
Decrease load or increase unit size
Reset UI setting
Locate leak, repair, and recharge
Check defrost time settings
Reset as necessary
Check defrost temperature switch
Replace as necessary
Compressor operates continuously
Frosted coil with incorrect defrost operation
Recover refrigerant, evacuate system, and re-
charge
Air in system
Outdoor coil dirty or restricted
Dirty air filter
Clean coil or remove restriction
Replace filter
Dirty indoor or outdoor coil
Refrigerant overcharged
Clean coil
Recover excess refrigerant
Excessive head pressure
Recover refrigerant, evacuate system, and re-
charge
Air in system
(Heat) Indoor air restricted or recirculating
Indoor or outdoor air restricted or air short--cycling
Determine cause and correct
Determine cause and correct
(Continued next page)
30
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 7—Troubleshooting Chart (Cont’d)
SYMPTOM
CAUSE
REMEDY
Low refrigerant charge
Restriction in liquid tube
(Cool) High Heat load
Reversing valve hung up or leaking internally
Refrigerant overcharged
(Cool) Dirty air filter
Check for leaks, repair and recharge
Remove restriction
Check for source and eliminate
Replace valve
Recover excess refrigerant
Replace filter
Head pressure too low
Excessive suction pressure
Move timer on control board to 30 minutes between
defrost cycles
(Heat) Outdoor coil frosted
Low refrigerant charge
Metering device or low side restricted
Check for leaks, repair and recharge
Remove source of restriction
Suction pressure too low
Increase air quantity
Check filter–replace if necessary
(Cool) Insufficient coil airflow
(Cool) Temperature too low in conditioned area
(Cool) Outdoor ambient below 55°F
Filter drier restricted
Reset UI setting
Install low--ambient kit
Replace
NC (normally closed) contacts on defrost board
open
Check condition of relay on board
Replace if necessary
Compressor runs but outdoor fan does not
IFM does not run
Blower wheel not secured to shaft
Insufficient voltage at motor
Properly tighten blower wheel to shaft
Determine cause and correct
Power connectors not properly sealed
Water dripping into motor
Connectors should snap easily; do not force
Verify proper drip loops in connector wires
IFM operation is intermittent
Gently pull wires individually to be sure they are
crimped into the housing
Connectors not firmly sealed
IFM-Indoor Fan Motor
31
Download from Www.Somanuals.com. All Manuals Search And Download.
START-UP CHECKLIST
(Remove and Store in Job File)
I. Preliminary Information
MODEL NO.:_________________________________
SERIAL NO.:__________________________________
DATE:_______________________________________
TECHNICIAN:_________________________________
II. PRE-START-UP (Insert checkmark in box as each item is completed)
( ) VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT
( ) REMOVE ALL SHIPPING HOLD DOWN BOLTS AND BRACKETS PER INSTALLATION INSTRUCTIONS
( ) CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS
( ) CHECK GAS PIPING FOR LEAKS (WHERE APPLICABLE)
( ) CHECK THAT INDOOR (EVAPORATOR) AIR FILTER IS CLEAN AND IN PLACE
( ) VERIFY THAT UNIT INSTALLATION IS LEVEL
( ) CHECK FAN WHEEL, AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS
( ) MAKE SURE THAT - (If Applicable) ON 060 SIZE PURON HEATPUMP ONLY, THE TWO WIRE TIES FASTEN
TO THE OUTDOOR COILS AND REVERSING VALVE/ACCUMULATOR HAVE BEEN REMOVED
III. START-UP
ELECTRICAL
SUPPLY VOLTAGE __________________________________
COMPRESSOR AMPS_________________________________
INDOOR (EVAPORATOR) FAN AMPS___________
TEMPERATURES
OUTDOOR (CONDENSER) AIR TEMPERATURE ___________DB
RETURN-AIR TEMPERATURE ___________DB ___________WB
COOLING SUPPLY AIR ___________DB ___________WB
HEAT PUMP SUPPLY AIR ___________
ELECTRIC HEAT SUPPLY AIR ___________
PRESSURES
REFRIGERANT SUCTION ___________PSIG SUCTION LINE TEMP*___________
REFRIGERANT DISCHARGE ___________PSIG DISCHARGE TEMP†___________
( ) VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS
*Measured at suction inlet to compressor
†Measured at liquid line leaving condenser.
A05306
Catalog No: 50CR---1SI
Printed in U.S.A.
Edition Date: 03/06
Copyright 2006 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231
Replaces: New
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
32
Download from Www.Somanuals.com. All Manuals Search And Download.
|