Carrier Gas Heater 48HC User Manual

48HC  
Single Package Rooftop  
Gas Heating/Electric Cooling Unit  
with Puronr (R---410A) Refrigerant  
Sizes: 17, 20, 24, 28  
Installation Instructions  
NOTE: Read the entire instruction manual before starting  
the installation  
TABLE OF CONTENTS  
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . 2  
Units without Thru-Base Connections . . . . . . . . . 22  
Field Control Wiring . . . . . . . . . . . . . . . . . . . . . . . 22  
Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22  
Unit without Thru-Base Conversion Kit . . . . . . . 22  
Heat Anticipator Settings . . . . . . . . . . . . . . . . . . . 23  
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9  
Jobsite Survey . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9  
Step 1 - Plan for Unit Location . . . . . . . . . . . . . . . . . . 9  
Roof Mount . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9  
Step 2 - Plan for Sequence of Unit Installation . . . . . 10  
Curb-Mount Installation . . . . . . . . . . . . . . . . . . . . 10  
Pad-Mount Installation . . . . . . . . . . . . . . . . . . . . . 10  
Frame-Mount Installation . . . . . . . . . . . . . . . . . . . 10  
Step 3 - Inspect Unit . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
Step 4 - Provide Unit Support . . . . . . . . . . . . . . . . . . 10  
Roof Curb Mount . . . . . . . . . . . . . . . . . . . . . . . . . 10  
Slab Mount (Horizontal Units Only) . . . . . . . . . . 10  
Transformer Connection  
for 208-v Power Supply . . . . . . . . . . . . . . . . . . . . . 23  
Humidi-MiZerR Control Connections . . . . . . . . . . 24  
Humidi-MiZer - Space RH Controller . . . . . . . . 24  
PremierLinkt (Factory Option) . . . . . . . . . . . . . . . 26  
Supply Air Temperature (SAT) Sensor . . . . . . . . . 29  
Outdoor Air Temperature (OAT) Sensor . . . . . . . 29  
EconoMi$er2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29  
Field Connections . . . . . . . . . . . . . . . . . . . . . . . . . . 29  
Space Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31  
Connect Thermostat . . . . . . . . . . . . . . . . . . . . . . . 31  
Configure the Unit for Thermostat Mode . . . . . . 31  
Economizer Controls . . . . . . . . . . . . . . . . . . . . . . . . 32  
Indoor Air Quality (CO2) Sensor . . . . . . . . . . . . . 32  
Outdoor Air Quality Sensor . . . . . . . . . . . . . . . . . 32  
Alternate Unit Support  
(In Lieu of Curb or Slab Mount) . . . . . . . . . . . . . 10  
Step 5 - Field Fabricate Ductwork . . . . . . . . . . . . . . . 14  
Step 6 - Rig and Place Unit . . . . . . . . . . . . . . . . . . . . 14  
Positioning on Curb . . . . . . . . . . . . . . . . . . . . . . . 15  
Step 7 - Horizontal Duct Connection . . . . . . . . . . . . 15  
Step 8 - Install Outside Air Hood — Factory Option . . 15  
Step 9 - Install Flue Hood and Combustion Air Hood . . 16  
Step 10 - Install Gas Piping . . . . . . . . . . . . . . . . . . . . 16  
Gas Supply Line . . . . . . . . . . . . . . . . . . . . . . . . . . 16  
Factory-Option Thru-Base Connections . . . . . . . 18  
Step 11 - Install External Condensate Trap and Line . . 19  
Step 12 - Make Electrical Connections . . . . . . . . . . . 19  
Field Power Supply . . . . . . . . . . . . . . . . . . . . . . . . 19  
Units without Factory-Installed Disconnect . . . . 20  
Units with Factory-Installed Disconnect . . . . . . . 20  
All Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20  
Convenience Outlets . . . . . . . . . . . . . . . . . . . . . . . 20  
Factory-Option Thru-Base Connections . . . . . . 22  
Space Relative Humidity Sensor or  
Humidistat Connections . . . . . . . . . . . . . . . . . . . . 33  
Smoke Detector/Fire Shutdown (FSD) . . . . . . . . . 34  
Filter Status Switch . . . . . . . . . . . . . . . . . . . . . . . . 34  
Supply Fan Status Switch . . . . . . . . . . . . . . . . . . . 34  
Remote Occupied Switch . . . . . . . . . . . . . . . . . . . 34  
Power Exhaust (output) . . . . . . . . . . . . . . . . . . . . . 34  
CCN Communication Bus . . . . . . . . . . . . . . . . . . 35  
RTU Open Control System . . . . . . . . . . . . . . . . . . . 36  
Supply Air Temperature (SAT) Sensor . . . . . . . . . 39  
Outdoor Air Temperature (OAT) Sensor . . . . . . . 39  
EconoMi$er2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C10896  
Fig. 1 - Unit Dimensional Drawing – 17 Size Unit  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
C10897  
Fig. 1 - Unit Dimensional Drawing – 17 Size Unit (cont.)  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
C10892  
Fig. 2 - Unit Dimensional Drawing – 20 and 24 Size Units  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
C10893  
Fig. 2 - Unit Dimensional Drawing – 20 and 24 Size Units (cont.)  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
C10900  
Fig. 3 - Unit Dimensional Drawing – 28 Size Unit  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
C10901  
Fig. 3 - Unit Dimensional Drawing – 28 Size Unit (cont.)  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
Jobsite Survey  
Be sure that the unit is installed such that snow will not  
block the combustion air intake or flute outlet.  
Complete the following checks before installation.  
Unit may be installed directly on wood flooring or on Class  
A, B, or C roof-covering material when roof curb is used.  
1. Consult local building codes and the NEC (National  
Electrical Code) ANSI/NFPA 70 for special installa-  
tion requirements.  
2. Determine unit location (from project plans) or select  
unit location.  
Do not install unit in an indoor location. Do not locate air  
inlets near exhaust vents or other sources of contaminated  
air. For proper unit operation, adequate combustion and  
ventilation air must be provided in accordance with  
Section 5.3 (Air for Combustion and Ventilation) of the  
National Fuel Gas Code, ANSI Z223.1 (American  
National Standards Institute) and NFPA (National Fire  
Protection Association) 54 TIA- -54- -84- -1. In Canada,  
installation must be in accordance with the CAN1- -B149  
installation codes for gas burning appliances.  
3. Check for possible overhead obstructions which may  
interfere with unit lifting or rigging.  
Step 1 — Plan for Unit Location  
Select a location for the unit and its support system (curb  
or other) that provides for the minimum clearances  
required for safety. This includes the clearance to  
combustible surfaces, unit performance and service access  
below, around and above unit as specified in unit  
drawings. See Fig. 4.  
Although unit is weatherproof, avoid locations that permit  
water from higher level runoff and overhangs to fall onto  
the unit.  
NOTE: Consider also the effect of adjacent units.  
Locate mechanical draft system flue assembly at least 4 ft  
(1.2 m) from any opening through which combustion  
products could enter the building, and at least 4 ft (1.2 m)  
from any adjacent building (or per local code). Locate the  
flue assembly at least 10 ft (3.05 m) from an adjacent  
unit’s fresh air intake hood if within 3 ft (0.91 m) of same  
elevation (or per local code). When unit is located  
adjacent to public walkways, flue assembly must be at  
least 7 ft (2.1 m) above grade.  
96” (2438)  
36” (914)  
42” (1067)  
Select a unit mounting system that provides adequate  
height to allow installation of condensate trap per  
requirements. Refer to Step 11 — Install External  
Condensate Trap and Line – for required trap dimensions.  
42” (1067)  
36” (914)  
Roof Mount —  
Check building codes for weight distribution  
requirements. Unit operating weight is shown in Table 1.  
C10638  
Fig. 4 - Service Clearance Dimensional Drawing  
Table 1 – Operating Weights  
UNIT LB (KG)  
48HC**  
17  
20  
24  
28  
Base Unit  
1892 (858)  
245 (111)  
32 (15)  
2102 (954)  
245 (111)  
32 (15)  
2247 (1019)  
245 (111)  
32 (15)  
2292 (1040)  
245 (111)  
32 (15)  
Economizer  
Powered Outlet  
R
83 (38)  
83 (38)  
88 (40)  
92 (42)  
H u m i d i --- Mi Z e r System  
Curb  
14---in/356 mm  
24---in/610 mm  
273 (124)  
350 (159)  
273 (124)  
350 (159)  
273 (124)  
350 (159)  
273 (124)  
350 (159)  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE: The gasketing of the unit to the roof curb is critical  
for a watertight seal. Install gasket supplied with the roof  
curb as shown in Figs. 6, 7 and 8. Improperly applied gasket  
can also result in air leaks and poor unit performance.  
Step 2 — Plan for Sequence of Unit Installation  
The support method used for this unit will dictate different  
sequences for the steps of unit installation. For example, on  
curb-mounted units, some accessories must be installed on  
the unit before the unit is placed on the curb. Review the  
following for recommended sequences for installation steps.  
Curb should be level. This is necessary for unit drain to  
function properly. Unit leveling tolerances are show in  
Fig. 9. Refer to Accessory Roof Curb Installation  
Instructions for additional information as required.  
Curb-mounted installation —  
Install curb  
Install insulation, cant strips, roofing felt, and counter  
flashing as shown. Ductwork must be attached to curb and  
not to the unit. Thru-the-base power connection must be  
installed before the unit is set on the roof curb. If  
field-installed thru-the-roof curb gas connections are  
desired remove knockout in basepan located in the gas  
section, see Fig. 5 for location. Gas connections and  
power connections to the unit must be field installed after  
the unit is installed on the roof curb.  
Install field-fabricated ductwork inside curb  
Install thru-base service connection fittings (affects  
curb and unit)  
Rig and place unit  
Remove top skid  
Install outside air hood  
Install smoke detector tube  
Install combustion air hood  
Install flue hood  
If electric and control wiring is to be routed through the  
basepan, remove knockouts in basepan located in control  
box area of access panel; see Fig. 1, 2, or 3 for basepan  
knockout locations for location. Attach the service  
connections to the basepan.  
Install gas piping  
Install condensate line trap and piping  
Make electrical connections  
Install other accessories  
Hood Carton Location  
(rear access panel)  
Pad-mounted installation —  
Prepare pad and unit supports  
Rig and place unit  
Remove duct covers and top skid  
Install smoke detector return air sensor tube  
Install field-fabricated ductwork at unit duct openings  
Install outside air hood  
Install combustion air hood  
Install flue hood  
Install gas piping  
Control Box  
Access Panel  
Filter and  
Indoor Coil  
Access Panel  
Indoor Blower  
Access Panel  
Gas Heat  
Install condensate line trap and piping  
Make electrical connections  
Install other accessories  
Access Panel  
Compressor  
(each side)  
C11154  
Fig. 5 - Typical Access Panel and Compressor Locations  
Frame-mounted installation —  
Slab Mount (Horizontal Units Only) —  
Frame-mounted applications generally follow the  
sequence for a curb installation. Adapt as required to  
suit specific installation plan.  
Provide a level concrete slab that extends a minimum of  
6–in. (150 mm) beyond unit cabinet. Install a gravel apron  
in front of condenser coil air inlet to prevent grass and  
foliage from obstructing airflow.  
Step 3 — Inspect unit  
Inspect unit for transportation damage. File any claim  
with transportation agency.  
NOTE: Horizontal units may be installed on a roof curb  
if required.  
Confirm before installation of unit that voltage, amperage  
and circuit protection requirements listed on unit data  
plate agree with power supply provided.  
Alternate Unit Support (In Lieu of Curb or Slab  
Mount) —  
A non-combustible sleeper rail can be used in the unit  
curb support area. If sleeper rails cannot be used, support  
the long sides of the unit with a minimum of 4 equally  
spaced 4-in. x 4-in. (102 mm x 102 mm) pads on each  
side. Locate pads so that they support the rails. Make sure  
to avoid the fork openings.  
Locate the carton containing the outside air hood parts; see  
Figs. 5 and 12. Do not remove carton until unit has been  
rigged and located in final position.  
Step 4 — Provide Unit Support  
Roof Curb Mount —  
Accessory roof curb details and dimensions are shown in  
Figs. 6, 7 and 8. Assemble and install accessory roof curb  
in accordance with instructions shipped with the curb.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C10954  
Fig. 6 - Roof Curb Details – 17 Size Unit  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C10955  
Fig. 7 - Roof Curb Details – 20 and 24 Size Units  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C10956  
Fig. 8 - Roof Curb Details – 28 Size Unit  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A minimum clearance is not required around ductwork.  
!
CAUTION  
C
PROPERTY DAMAGE HAZARD  
Failure to follow this caution may result in damage  
to roofing materials.  
MAXIMUM ALLOWABLE  
DIFFERENCE IN. (MM)  
A
Membrane roofs can be cut by sharp sheet metal  
edges. Be careful when placing any sheet metal parts  
on such roof.  
B
A-B  
B-C  
A-C  
0.25” (6)  
0.5” (12)  
0.5” (12)  
C10628  
Fig. 9 - Unit Leveling Tolerances  
Step 5 — Field Fabricate Ductwork  
Step 6 — Rig and Place Unit  
Keep unit upright and do not drop. Spreader bars are not  
required if top crating is left on unit. Rollers may be used  
to move unit across a roof. Level by using unit frame as a  
reference. See Table 1 (on page 9) and Fig. 10 for  
additional information.  
Cabinet return-air static pressure (a negative condition)  
shall not exceed 0.5 in. wg (87 Pa) with economizer or  
without economizer.  
For vertical ducted applications, secure all ducts to roof curb  
and building structure. Do not connect ductwork to unit.  
Lifting holes are provided in base rails as shown in  
Fig. 10. Refer to rigging instructions on unit.  
Fabricate supply ductwork so that the cross sectional  
dimensions are equal to or greater than the unit supply  
duct opening dimensions for the first 18 in. (458 mm) of  
duct length from the unit basepan.  
!
CAUTION  
UNIT DAMAGE HAZARD  
Insulate and weatherproof all external ductwork, joints,  
and roof openings with counter flashing and mastic in  
accordance with applicable codes.  
Failure to follow this caution may result in  
equipment damage.  
All panels must be in place when rigging. Unit is not  
designed for handling by fork truck when packaging  
is removed.  
Ducts passing through unconditioned spaces must be  
insulated and covered with a vapor barrier.  
If a plenum return is used on a vertical unit, the return  
should be ducted through the roof deck to comply with  
applicable fire codes.  
Before setting the unit onto the curb, recheck gasketing on  
curb.  
PLACE ALL SEAL STRIP  
IN PLACE BEFORE PLACING  
UNIT ON ROOF CURB.  
DETAIL A  
"914-1371"  
(36"-54")  
"B"  
SEE DETAIL A  
DUCT END  
"C"  
"A"  
C09107  
DIMENSIONS  
MAX WEIGHT  
A
B
C
UNIT  
LB  
KG  
IN  
MM  
3249  
3595  
3595  
4007  
IN  
MM  
1491  
1816  
1816  
2040  
IN  
MM  
1328  
1328  
1532  
1532  
48HC**17  
48HC**20  
48HC**24  
48HC**28  
2339  
2549  
2699  
2748  
1061  
1156  
1224  
1246  
127.8  
141.5  
141.5  
157.8  
58.7  
71.5  
71.5  
80.3  
52.3  
52.3  
60.3  
60.3  
NOTES:  
1. Dimensions in ( ) are inches.  
2. Hook rigging shackles through holes in base rail, as shown in detail A.” Holes in base rails are centered around the unit center of  
gravity. Use wooden top to prevent rigging straps from damaging unit.  
Fig. 10 - Rigging Details  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Positioning on Curb —  
Field  
-supplied (3/4-inch) flanges should be attached to  
                                                                                                                  
horizontal duct openings (see Fig. 11) and all ductwork  
should be secured to the flanges. Insulate and weatherproof  
all external ductwork, joints, and roof or building openings  
with counter flashing and mastic in accordance with  
applicable codes.  
Position unit on roof curb so that the following clearances  
1
are maintained: /4 in. (6 mm) clearance between the roof  
1
curb and the base rail inside the right and left,  
/
in.  
2
(12 mm) clearance between the roof curb and the base rail  
inside the front and back. This will result in the distance  
between the roof curb and the base rail inside on the  
condenser end of the unit being approximately equal to  
Details A and B in Figs. 6, 7 and 8.  
Step 8 — Install Outside Air Hood — Factory  
Option  
The outside air hood for factory-option economizer and  
two-position damper is shipped in knock-down form and  
requires field assembly. The panel for the hood top is  
shipped on the end of the unit (see Fig. 12). The  
remaining parts for the hood assembly (including side  
panels, filters and tracks) are shipped in a carton that is  
secured to the rear of the blower assembly. Access the  
carton location through rear panel (see Fig. 13).  
Do not attempt to slide unit on curb after unit is set. Doing  
so will result in damage to the roof curb seal.  
Although unit is weatherproof, guard against water from  
higher level runoff and overhangs.  
Flue vent discharge must have a minimum horizontal  
clearance of 48 in. (1220 mm) from electric and gas meters,  
gas regulators, and gas relief equipment. Minimum distance  
between unit and other electrically live parts is 48 inches  
(1220 mm).  
Hood Top  
Shipping  
Position  
Flue gas can deteriorate building materials. Orient unit such  
that flue gas will not affect building materials. Locate  
mechanical draft system flue assembly at least 48 in. (1220  
mm) from an adjacent building or combustible material.  
After unit is in position, remove rigging skids and  
shipping materials.  
C09134  
Fig. 12 - Hood Top – Shipping Position  
Step 7 — Horizontal Duct Connection  
Refer to Figs. 1, 2 and 3 for locations and sizes of the  
horizontal duct connections. Note that there are two different  
return air duct connection locations – one for unit without an  
economizer (on back side of unit) and a different one for  
unit equipped with an economizer (on left end, under the  
economizer hood). The supply air duct connection is on the  
back side. See Fig. 11 for top view depicting typical  
horizontal duct arrangements.  
To remove the hood parts package:  
1. Remove the back blower access panel.  
2. Locate and cut the strap, being careful to not damage  
any wiring.  
3. Carefully lift the hood package carton through the  
back blower access opening.  
See Fig. 14 for identification of the various parts of the  
hood assembly.  
Hood  
Package  
Horizontal  
Supply Air  
Return Air Duct  
without  
Economizer  
Return Air Duct  
with Economizer  
C10626  
C09133  
Return without Return with  
Supply  
Fig. 13 - Hood Package – Shipping Location  
Economizer  
Economizer  
Location  
Back  
7
Back  
3
Left end  
3
Height --- In. (mm) 15 / (402)  
8
49 / (1253)  
8
18 / (467)  
8
3
3
5
W id t h --- in . ( m m )  
29 / (756)  
23 / (593)  
61 / (1564)  
4
8
8
Fig. 11 - Horizontal Duct Opening Dimensions  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
To assemble the outside air hood:  
The combustion air hood is attached to the back of the  
burner access panel. Remove the two screws securing the  
hood to the back of the burner access panel. Using the two  
screws, re-attach the hood to the front of the burner  
access panel as shown in Fig. 16.  
1. Remove hood top panel from shipping position on  
unit end.  
2. Install four angles to the upper end panel using the  
screws provided.  
3. Apply seal strip to mating flanges on the side plates  
of the hood (see Fig. 14).  
Apply Seal Strips  
3
to the back of  
Apply Seal Strip  
to the front of  
this flange  
these surfaces  
Apply Seal Strip  
to the front of  
this flange  
7
Apply Seal Strips  
to the back of  
these flanges  
7
2
5
2
4
4
4
4
6
Apply Seal Strip  
to the back of  
this flange  
1
5
6
Seal Strips  
Item #  
Description  
Angles  
Side Plates  
Hood  
Outdoor Air Screens  
Side Filter Supports  
Side Drip Angles  
Top Diverters  
Qty  
4
2
1
4
2
2
2
Combustion  
Flue Hood  
Air Hood  
1
2
3
4
5
6
7
C10744  
Fig. 16 - Flue Hood and Combustion Air Hood Details  
C09079  
Step 10 — Install Gas Piping  
Fig. 14 - Hood Part Identification and Seal Strip  
Application Areas  
Installation of the gas piping must be in accordance with  
local building codes and with applicable national codes.  
In U.S.A., refer to NFPA 54/ANSI Z223.1 National Fuel  
Gas Code (NFGC). In Canada, installation must be  
accordance with the CAN/CSA B149.1 and CAN/CSA  
B149.2 installation codes for gas burning appliances.  
4. Secure side plates to panel using the screws provided.  
5. Apply seal strip to mating flange of the hood (see  
Fig. 14).  
6. Secure top flange using screws provided in kit.  
This unit is factory equipped for use with Natural Gas fuel  
at elevations up to 2000 ft (610 m) above sea level. Unit  
may be field converted for operation at elevations above  
2000 ft (610 m) and/or for use with liquefied petroleum  
fuel. See accessory kit installation instructions regarding  
these accessories.  
7. Install outdoor air screens by sliding them into the  
channel formed by the four angles installed in step 2.  
Make sure that the screens extend across the entire  
length of the hood.  
8. Install side filter supports using the screws provided.  
9. Install side drip angles using the screws provided.  
NOTE: Furnace gas input rate on rating plate is for  
installation up to 2000 ft (610 m) above sea level. In  
U.S.A. the input rating for altitudes above 2000 ft (610 m)  
must be derated by 4% for each 1000 ft (305 m) above sea  
level. In Canada the input rating must be derated by 10%  
for altitudes of 2000 ft (610 m) to 4500 ft (1372 m) above  
sea level.  
10. Run a continuous length of seal strip across the hood  
covering the engagement holes in the lower hood.  
11. Install top diverter using the screws provided.  
12. On units with barometric relief, remove screws at bot-  
tom of relief damper. Do not discard damper door.  
For natural gas applications, gas pressure at unit gas  
connection must not be less than 5 in. wg (1246 Pa) or  
greater than 13 in. wg (3240 Pa) while the unit is  
operating. For liquified petroleum applications, the gas  
pressure must not be less than 11 in. wg (2740 Pa) or  
greater than 13 in. wg (3240 Pa) at the unit connection.  
C09090  
Gas Supply Line —  
Fig. 15 - Hood Assembly – Completed  
The gas supply pipe enters the unit adjacent to the burner  
access panel on the front side of the unit, through the  
grommeted hole. The gas connection to the unit is made  
to the 3/4 in. FPT gas inlet port on the unit gas valve.  
Step 9 — Install Flue Hood and Combustion Air  
Hood  
The flue hood is shipped screwed to the fan deck inside  
the burner compartment. Remove the burner access panel  
and then remove the flue hood from its shipping location.  
Using the screws provided, install flue hood in the  
location shown in Fig. 16.  
3
Table 2 lists typical /4 inch NPT (National Pipe Thread)  
field supplied pipe fittings required for Thru-Base gas  
supply, starting from the unit gas valve (see Fig. 17).  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 2 – Typical 3/4-in NPT Field Supplied Piping Parts  
4
5
3
2
6
1
Item Qty  
CPN  
Description  
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
CA15RA201 90 Deg Street Elbow  
CA01CA226 5 Inch Long Nipple  
CA85RA201 Ground---Joint Union  
CA01CA218 3 Inch Long Nipple  
CA05RA201 90 Deg Elbow  
7
3
15  
4
8
5
9
6
CA01CA250 12 Inch Long Nipple  
CA05RA201 90 Deg Elbow  
7
10  
8
CA01CA218 3 Inch Long Nipple  
CA20RA201 TEE  
11  
9
12  
13  
10  
11  
12  
13  
14  
15  
CA01CN222 4 Inch Long Nipple (Sediment Trap)  
14  
CA38RA201 Cap  
1
CA01CA220  
GB30  
3
/
Inch Long Nipple  
R
2
NIBCO Ball Valve  
CA01CA238 8 Inch Long Nipple  
CA05RA201 90 Deg Elbow  
Fig. 17 - Gas Supply Line Piping with Thru-BaCs1e0999  
Pipe gas supply into 90 degree elbow item 15 (see Table 2)  
through the hole in the unit basepan.  
4
5
3
2
6
1
3
For typical /4 inch NPT field supplied fittings required  
for NON Thru-Base gas supply starting from the unit gas  
valve, omit items 14 and 15 from Table 2 and pipe gas  
supply into TEE. See Fig. 18.  
7
8
9
12  
Table 3 – Natural Gas Supply Line Pressure Ranges  
UNIT MODEL  
UNIT SIZE  
MIN  
MAX  
5.0 in. wg  
(1246 Pa)  
13.0 in. wg  
(3240 Pa)  
10  
13  
48HC**  
17, 20, 24, 28  
11  
!
CAUTION  
EQUIPMENT DAMAGE HAZARD  
Failure to follow this caution may result in damage  
to equipment.  
C101006  
Fig. 18 - Gas Supply Line Piping  
When connecting the gas line to the unit gas valve,  
the installer MUST use a backup wrench to prevent  
damage to the valve.  
X
9” MINIMUM CLEARANCE  
FOR PANEL REMOVAL  
GAS  
FROM  
GAS  
REGULATOR  
*
MANUAL GAS  
METER  
Install a gas supply line that runs to the unit heating  
section. Refer to the NFPA 54/NFGC or equivalent code  
for gas pipe sizing data. Do not use a pipe smaller than the  
size specified. Size the gas supply line to allow for a  
maximum pressure drop of 0.5-in wg (124 Pa) between  
gas regulator source and unit gas valve connection when  
unit is operating at high-fire flow rate.  
SHUTOFF VALVE  
*
BASE UNIT  
48” MINIMUM  
DRIP LEG  
PER NFGC  
*
BASE RAIL  
FIELD-  
ROOF  
CURB  
FABRICATED  
SUPPORT  
*
LEGEND  
The gas supply line can approach the unit in two ways:  
horizontally from outside the unit (across the roof), or  
through unit basepan. Observe clearance to gas line  
components per Fig. 19.  
NFGC – National Fuel Gas Code  
Field supplied.  
*
NOTE: Follow all local codes.  
STEEL PIPE  
NOMINAL DIAMETER  
(in.)  
SPACING OF SUPPORTS  
X DIMENSION  
(ft)  
1
/
6
2
3
/
4 or 1  
8
11  
/
4 or larger  
10  
C11121  
Fig. 19 - Gas Piping Guide  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Factory-Option Thru-Base Connections —  
NOTE: Pressure test the gas supply system after the gas  
supply piping is connected to the gas valve. The supply  
piping must be disconnected from the gas valve during the  
testing of the piping systems when test pressure is in  
excess of 0.5 psig (3450 Pa). Pressure test the gas supply  
piping system at pressures equal to or less than 0.5 psig  
(3450 Pa). The unit heating section must be isolated from  
the gas piping system by closing the external main manual  
shutoff valve and slightly opening the ground-joint union.  
Electrical Connections: Knockouts are located in the  
control box area. Remove the appropriate size knockout  
for high voltage connection. Use the field supplied  
connector depending on wiring or conduit being utilized.  
Remove the 7/8 -in (22mm) knockout and appropriate  
connector for low voltage wiring. If non-unit powered  
convenience outlet is being utilized, remove the 7/8 - i n  
(22mm) knockout and utilize appropriate connector for  
115 volt line. See “Step 12 — Making Electrical  
Connections” for details.  
Check for gas leaks at the field-installed and  
factory-installed gas lines after all piping connections have  
been completed. Use soap-and-water solution (or method  
specified by local codes and/or regulations).  
Gas Connections: Remove the knockout in the base pan  
3
and route /4 -in. gas line up through the opening. Install  
an elbow and route gas line through opening in panel after  
first removing plastic bushing. Install a gas shut off  
followed by a drip leg and ground-joint union. Route gas  
line into gas section through the grommet (Part #:  
KA56SL112) at the gas inlet and into the gas valve. See  
Fig. 17 and Table 2. If a regulator is installed, it must be  
located 4 feet (1.22 meters) from the flue outlet.  
!
WARNING  
FIRE OR EXPLOSION HAZARD  
Failure to follow this warning could result in personal  
injury, death and/or property damage.  
S Connect gas pipe to unit using a backup wrench to  
avoid damaging gas controls.  
S Never purge a gas line into a combustion chamber.  
S Never test for gas leaks with an open flame. Use a  
commercially available soap solution made  
specifically for the detection of leaks to check all  
connections.  
Some municipal codes require that the manual shutoff  
valve be located upstream of the sediment trap. See  
Fig. 18 for typical piping arrangements for gas piping that  
has been routed through the sidewall of the base pan.  
When installing the gas supply line, observe local codes  
pertaining to gas pipe installations. Refer to the NFPA  
54/ANSI Z223.1 NFGC latest edition (in Canada, CAN/CSA  
B149.1). In the absence of local building codes, adhere to  
the following pertinent recommendations:  
S Use proper length of pipe to avoid stress on gas  
control manifold.  
NOTE: If orifice hole appears damaged or it is suspected to  
have been redrilled, check orifice hole with a numbered drill  
bit of correct size. Never redrill an orifice. A burr-free and  
squarely aligned orifice hole is essential for proper flame  
characteristics.  
1. Avoid low spots in long runs of pipe. Grade all pipe  
1/4 -in. in every 15 ft (7 mm in every 5 m) to prevent  
traps. Grade all horizontal runs downward to risers.  
Use risers to connect to heating section and to meter.  
2. Protect all segments of piping system against physical  
and thermal damage. Support all piping with appro-  
priate straps, hangers, etc. Use a minimum of one  
hanger every 6 ft (1.8 m). For pipe sizes larger than  
1/2 -in., follow recommendations of national codes.  
3. Apply joint compound (pipe dope) sparingly and only to  
male threads of joint when making pipe connections.  
Use only pipe dope that is resistant to action of lique-  
fied petroleum gases as specified by local and/or nation-  
al codes. If using PTFE (Teflon) tape, ensure the materi-  
al is Double Density type and is labeled for use on gas  
lines. Apply tape per manufacturer’s instructions.  
BURNER  
ORIFICE  
4. Pressure-test all gas piping in accordance with local  
and national plumbing and gas codes before connect-  
ing piping to unit.  
A93059  
Fig. 20 - Orifice Hole  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 11 — Install External Condensate Trap and  
Line  
Step 12 — Make Electrical Connections  
!
3
WARNING  
The unit has one /4-in. condensate drain connection on  
the end of the condensate pan (see Fig. 21). See Figs. 1, 2  
and 3, item “E”, in the view labeled “BACK  
(HORIZONTAL DISCHARGE)” for the location of the  
condensate drain connection.  
ELECTRICAL SHOCK HAZARD  
Failure to follow this warning could result in personal  
injury or death.  
Do not use gas piping as an electrical ground. Unit  
cabinet must have an uninterrupted, unbroken electrical  
ground to minimize the possibility of personal injury if  
an electrical fault should occur. This ground may consist  
of electrical wire connected to unit ground lug in control  
compartment, or conduit approved for electrical ground  
when installed in accordance with NEC (National  
Electrical Code); ANSI/NFPA 70, latest edition (in  
Canada, Canadian Electrical Code CSA [Canadian  
Standards Association] C22.1), and local electrical  
codes.  
CONDENSATE  
DRAIN  
CONNECTION  
NOTE: Field-supplied wiring shall conform with the  
limitations of minimum 63_F (33_C) rise.  
Field Power Supply —  
C10729  
If equipped with optional Powered Convenience Outlet:  
The power source leads to the convenience outlet’s  
transformer primary are not factory connected. Installer  
must connect these leads according to required operation  
of the convenience outlet. If an always-energized  
convenience outlet operation is desired, connect the  
source leads to the line side of the unit-mounted  
disconnect. (Check with local codes to ensure this method  
is acceptable in your area.) On a unit without a  
unit-mounted disconnect, connect the source leads to the  
line side with unit field power leads. See Fig. 23.  
Fig. 21 - Condensate Drain Pan Connection  
The piping for the condensate drain and external trap can  
be completed after the unit is in place. Hand tighten  
fittings to the drain pan fitting. Provide adequate support  
for the drain line. Failure to do so can result in damage to  
the drain pan. See Fig. 22.  
MINIMUM PITCH  
1” (25mm) PER  
10’ (3m) OF LINE  
BASE RAIL  
BLK  
YEL  
BLU  
2˝ (51) MIN  
OPEN  
VENT  
LOAD  
SIDE  
TO ROOF  
DRAIN  
SEE NOTE  
LINE  
SIDE  
ROOF  
CURB  
DRAIN PLUG  
SEE  
NOTE: Trap should be deep enough to offset maximum unit static  
difference. A 4” (102) trap is recommend. ed  
DETAIL  
A
L1  
C08022  
L2  
Fig. 22 - Condensate Drain Piping Details  
L3  
DETAIL  
A
All units must have an external trap for condensate  
drainage. Install a trap at least 4-in. (102 mm) deep and  
protect against freeze-up. If drain line is installed  
downstream from the external trap, pitch the line away  
from the unit at 1-in. per 10 ft (25 mm in 3 m) of run. Do  
not use a pipe size smaller than the unit connection  
(3/4-in.).  
CONTROL BOX  
C11181  
Fig. 23 - Location of TB1  
Field power wires are connected to the unit at line-side  
pressure lugs on the terminal block (see wiring diagram  
label for control box component arrangement) or at  
factory-installed option non-fused disconnect switch. Use  
copper conductors only.  
NOTE: Make field power connections directly to line  
connection pressure lugs only.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
!
!
CAUTION  
WARNING  
UNIT DAMAGE HAZARD  
FIRE HAZARD  
Failure to follow this caution may result in equipment  
damage.  
Failure to follow this warning could result in  
intermittent operation or unsatisfactory performance.  
Do not connect aluminum wire between disconnect  
switch and air conditioning unit. Use only copper  
wire. (See Fig. 24.)  
Operation on improper line voltage or excessive phase  
imbalance constitutes abuse and may cause damage to  
electrical components. Such operation would invalidate  
any applicable Carrier warranty.  
Units Without Disconnect Option  
ELECTRIC  
DISCONNECT  
SWITCH  
TB1  
12  
11  
13  
COPPER  
WIRE ONLY  
ALUMINUM  
WIRE  
Disconnect  
per  
A93033  
NEC  
Fig. 24 - Disconnect Switch and Unit  
L1  
L2  
L3  
208/230-3-60  
460-3-60  
Units without Factory-Installed Disconnect —  
575-3-60  
When installing units, provide a disconnect switch per  
NEC (National Electrical Code) of adequate size.  
Disconnect sizing data is provided on the unit informative  
plate. Locate on unit cabinet or within sight of the unit per  
national or local codes. Do not cover unit informative  
plate if mounting the disconnect on the unit cabinet.  
Units With Disconnect Option  
Factory  
Wiring  
Units with Factory-Installed Disconnect —  
The factory-installed option disconnect switch is located  
in the main control box. The manual switch handle is  
accessible on the corner post adjacent to the control box  
access panel.  
T1  
T2  
T3  
Optional  
Disconnect  
Switch  
All Units -  
L1  
L2  
L3  
All field wiring must comply with NEC and all local code  
requirements.  
L1  
L2  
L3  
Size wire based on MCA (Minimum Circuit Amps) on the  
unit informative plate. See Fig. 25 for power wiring  
connections to the unit power terminal block and equipment  
ground. Maximum wire size is 2/0 AWG per pole.  
C101000  
Fig. 25 - Power Wiring Connections  
Convenience Outlets —  
Provide a ground-fault and short-circuit over-current  
protection device (fuse or breaker) per NEC Article 440  
(or local codes). Refer to unit informative data plate for  
MOCP (Maximum Over-current Protection) device size.  
!
WARNING  
ELECTRICAL OPERATION HAZARD  
Voltage to compressor terminals during operation must be  
within voltage range indicated on unit nameplate. See  
Table 11. On 3-phase units, voltages between phases must  
be balanced within 2% and the current within 10%. Use  
the formula shown in the legend for Table 11 (see Note 2  
on page 49) to determine the percent of voltage  
imbalance.  
Failure to follow this warning could result in personal  
injury or death.  
Units with convenience outlet circuits may use  
multiple disconnects. Check convenience outlet for  
power status before opening unit for service. Locate  
its disconnect switch, if appropriate, and open it.  
Lock-out and tag-out this switch, if necessary.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Two types of convenience outlets are offered on 48HC  
models: Non-unit powered and unit-powered. Both types  
provide a 125-volt GFCI (ground-fault circuit-interrupter)  
duplex receptacle rated at 15-A behind a hinged access  
cover, located on the corner panel of the unit. See Fig. 26.  
Non-unit powered type: This type requires the field  
                                                                                                                  
installation of a general-purpose 125-volt 15-A circuit  
powered from a source elsewhere in the building. Observe  
national and local codes when selecting wire size, fuse or  
breaker requirements and disconnect switch size and  
location. Route 125-v power supply conductors into the  
bottom of the utility box containing the duplex receptacle.  
Control Box  
Access Panel  
Electric  
Disconnect  
Switch  
Unit-powered type: A unit-mounted transformer is  
factory-installed to stepdown the main power supply  
voltage to the unit to 115-v at the duplex receptacle. This  
option also includes a manual switch with fuse, located in  
a control box and mounted on a bracket behind the  
convenience outlet; access is through the unit’s control  
box access panel. See Fig. 26.  
Convenience  
Outlet  
The primary leads to the convenience outlet transformer  
are not factory-connected. If local codes permit, the  
transformer primary leads can be connected at the  
line-side terminals on the unit-mounted non-fused  
disconnect switch; this will provide service power to the  
unit when the unit disconnect switch is open. See Fig. 28.  
C10641  
Fig. 26 - Convenience Outlet Location  
Installing Weatherproof Cover:  
A
weatherproof  
while-in-use cover for the factory-installed convenience  
outlets is now required by UL standards. This cover cannot  
be factory-mounted due to its depth; it must be installed at  
unit installation. For shipment, the convenience outlet is  
covered with a blank cover plate.  
The weatherproof cover kit is shipped in the unit’s control  
box. The kit includes the hinged cover, a backing plate  
and gasket.  
DISCONNECT ALL POWER TO UNIT AND  
CONVENIENCE OUTLET. LOCK-OUT AND TAG-OUT  
ALL POWER.  
Remove the blank cover plate at the convenience outlet;  
discard the blank cover.  
Loosen the two screws at the GFCI duplex outlet, until  
approximately 1/2-in (13 mm) under screw heads are  
exposed. Press the gasket over the screw heads. Slip the  
backing plate over the screw heads at the keyhole slots  
and align with the gasket; tighten the two screws until  
snug (do not over-tighten).  
Mount the weatherproof cover to the backing plate as  
shown in Fig. 27. Remove two slot fillers in the bottom of  
the cover to permit service tool cords to exit the cover.  
Check for full closing and latching.  
C10730  
UNIT  
CONNECT  
AS  
PRIMARY  
TRANSFORMER  
TERMINALS  
COVER – WHILE-IN-USE  
RECEPTACLE  
VOLTAGE  
CONNECTIONS  
WEATHERPROOF  
NOT SHOWN  
208,  
230  
L1: RED +YEL  
L2: BLU + GRA  
H1 + H3  
H2 + H4  
240  
480  
600  
L1: RED  
Splice BLU + YEL  
L2: GRA  
H1  
H2 + H3  
H4  
460  
575  
L1: RED  
L2: GRA  
H1  
H2  
Fig. 28 - Powered Convenience Outlet Wiring  
BASE PLATE FOR  
GFCI RECEPTACLE  
C09022  
Fig. 27 - Weatherproof Cover Installation  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Field Control Wiring —  
NOTICE/AVIS  
The 48HC unit requires an external temperature control  
device. This device can be a thermostat (field-supplied)  
or a PremierLink controller (available as factory-installed  
option or as field-installed accessory, for use on a Carrier  
Comfort Network or as a stand alone control) or the RTU  
Open for Building Management Systems using non-CCN  
protocols (RTU Open is available as a factory-installed  
option only).  
Convenience Outlet Utilization  
Maximum Intermittent Use 15 - Amps  
Maximum Continuous Use 8 - Amps  
Observe a 50% limit on the circuit  
Loading above 8 - Amps  
Utilisation de la prise utilitaire  
Usage intermittent maximum 15 - Amps  
Usage continu maximum 8 - Amps  
Observez une limite de 50% sur le circuit  
Chargement au-dessus de 8 - Amps  
50HE501288 2.0  
C10077  
Thermostat —  
Fig. 29 - Convenience Outlet Utilization Notice  
Install a Carrier-approved accessory 2-stage thermostat  
according to installation instructions included with the  
accessory. Locate the thermostat accessory on a solid wall  
in the conditioned space to sense average temperature in  
accordance with the thermostat installation instructions.  
Test the GFCI receptacle by pressing the TEST button on  
the face of the receptacle to trip and open the receptacle.  
Check for proper grounding wires and power line phasing  
if the GFCI receptacle does not trip as required. Press the  
RESET button to clear the tripped condition.  
If the thermostat contains a logic circuit requiring 24-v  
power, use a thermostat cable or equivalent single leads of  
different colors with minimum of seven leads. If the  
thermostat does not require a 24-v source (no “C”  
connection required), use a thermostat cable or equivalent  
with minimum of six leads. Check the thermostat  
installation instructions for additional features which  
might require additional conductors in the cable.  
Using unit-mounted convenience outlets: Units with  
unit-mounded convenience outlet circuits will often  
require that two disconnects be opened to de-energize all  
power to the unit. Treat all units as electrically energized  
until the convenience outlet power is also checked and  
de-energization is confirmed. Observe National Electrical  
Code Article 210, Branch Circuits, for use of convenience  
outlets.  
For wire runs up to 50 ft. (15 m), use no. 18 AWG  
(American Wire Gage) insulated wire (35_C minimum).  
For 50 to 75 ft. (15 to 23 m), use no. 16 AWG insulated  
wire (35_C minimum). For over 75 ft. (23 m), use no. 14  
AWG insulated wire (35_C minimum). All wire sizes  
larger than no. 18 AWG cannot be directly connected to  
the thermostat and will require a junction box and splice  
at the thermostat.  
Factory-Option Thru-Base Connections —  
All units are equipped with the ability to bring utilities  
through the base.  
Gas is brought up through an embossed area located in the  
gas section behind the gas entrance post. Access is gained  
through the gas access panel. A knock out must be  
removed to accomplish this.  
Unit without Thru-Base Connection Kit —  
The electrical entrance is located in the control box area  
and can be accessed through the control box access panel.  
An embossed area is provided with three knock outs. High  
voltage is brought through the multi knock out by  
removing the appropriate size for the size of the fitting  
Correctly rated low voltage wire can be routed through the  
rubber grommet located on the corner post adjacent to the  
control box access panel. Route wire through the grommet  
and then route the wire behind the corner post utilizing the  
factory provided wire ties secured to the control box. This  
will insure separation of the field low voltage wire and the  
high voltage circuit. Route the low voltage wire to the  
central terminal board. See Fig. 30.  
7
required. A /8 -in. knock out is provided for low voltage.  
7
An additional /8 -in. knock out is provided for a 115 volt  
line which is used when the unit is equipped with the  
non-unit powered convenience outlet option.  
All required fittings are field supplied. Install fittings  
when access to both top and bottom of the base pan is  
available. See electrical and gas connections for routing  
and connection information.  
Units without Thru-Base Connections —  
1. Install liquid tight conduit between disconnect and  
control box.  
2. Pull correctly rated high voltage wires through the  
conduit.  
3. Install power lines to terminal connections as shown  
in Fig. 25.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Central  
Terminal  
Board  
Rubber  
Grommet  
Typical  
Thermostat  
Corrections  
X
C
X
C
G
C
G
Corner  
Post  
See  
Caution  
G
W2  
W2  
W2  
W1  
Y2  
Y1  
R
W1  
W1  
Wire  
Ties  
O/B/Y2  
(see Note)  
Y2  
Y1  
R
Y1  
R
T–STAT  
Note: Typical multi-function marking. Follow manufacturer’s configuration  
instructions to select Y2.  
Field Wiring  
Thru the Base  
Connection  
!
CAUTION  
C10734  
UNIT DAMAGE HAZARD  
Fig. 31 - Field Control Wiring Raceway  
Failure to follow this caution may cause a short circuit.  
Carefully check the connection of control coductor  
for indoor fan control at terminal G. Connecting the  
indoor fan lead to terminal C will cause a short circuit  
condition which can cause component damage inside  
the unit or at thermostat.  
Heat Anticipator Settings —  
Set heat anticipator settings at 0.14 amp for the first stage  
and 0.14 amp for second-stage heating.  
Transformer Connection for 208-v Power Supply —  
C10731  
Fig. 30 - Typical Low-Voltage Control Connections  
All units except 208/230-v units are factory wired for the  
voltage shown on the nameplate. If the 208/230-v unit is  
to be connected to a 208-v power supply, the control  
transformer must be rewired by moving the black wire  
with the 1/4-in. female spade connector from the 230-v  
connection and moving it to the 208-v 1/4-in. male  
terminal on the primary side of the transformer. Refer to  
unit label diagram for additional information.  
NOTE: If utilizing the through the base connections,  
route the low voltage wire through the wire ties to the  
central terminal board.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Humidi--MiZerR Control Connections  
Humidi-MiZer – Space RH Controller —  
NOTE: The Humidi-MiZer is a factory installed option.  
The Humidi-MiZer dehumidification system requires a  
field-supplied and -installed space relative humidity  
control device. This device may be a separate humidistat  
control (contact closes on rise in space RH above control  
setpoint) or a combination thermostat-humidistat control  
device such as Carrier’s EDGER Pro Thermidistat with  
isolated contact set for dehumidification control. The  
humidistat is normally used in applications where a  
temperature control is already provided (units with  
PremierLinkt control).  
% RELATIVE HUMIDITY  
C09295  
Fig. 32 - Accessory Field-Installed Humidistat  
To connect the Carrier humidistat (HL38MG029):  
1. Route the humidistat 2-conductor cable (field-sup-  
plied) through the hole provided in the unit corner  
post.  
2. Feed wires through the raceway built into the corner  
post (see Fig. 31) to the 24-v barrier located on the  
left side of the control box. The raceway provides the  
UL-required clearance between high-voltage and  
low-voltage wiring.  
3. Use wire nuts to connect humidistat cable to two  
PINK leads in the low–voltage wiring as shown in  
Fig. 34.  
To connect the Thermidistat device (33CS2PPRH-01):  
1. Route the Thermidistat multi-conductor thermostat  
cable (field-supplied) through the hole provided in  
the unit corner post.  
®
2. Feed wires through the raceway built into the corner  
post (see Fig. 31) to the 24-v barrier located on the  
left side of the control box. The raceway provides the  
UL-required clearance between high-voltage and  
low-voltage wiring.  
C09296  
Fig. 33 - EDGE Pro Thermidistat  
3. The Thermidistat has dry contacts at terminals D1  
and D2 for dehumidification operation (see Fig. 35).  
The dry contacts must be wired between CTB  
terminal R and the PINK lead to the LTLO switch  
with field-supplied wire nuts. Refer to the installation  
instructions included with the Carrier Edge  
Thermidistat device (Form 33CS-65SI or latest) for  
more information.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C11139  
Fig. 34 - Typical Humidi-MiZerR Adaptive Dehumidification System Humidistat Wiring  
EDGE Pro THERMIDISTAT  
Unit CTB  
THERMOSTAT  
X*  
Rc  
Rh  
C
W1  
G
G
Y2  
W2  
C
O/W2/B  
Y1  
W1  
Y2  
Y1  
R
OAT  
RRS  
SRTN  
HUM  
D1  
Humidi-MiZer™ FIOP  
D2  
V+  
Vg  
*Connection not required.  
C09298  
Fig. 35 - Typical Rooftop Unit with Humidi-MiZer Adaptive Dehumidification System  
with EDGE Pro Thermidistat Device  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PremierLinkt (Factory--Option)  
C08199  
Fig. 36 - PremierLink Controller  
The PremierLink controller (see Fig. 36) is compatible  
with Carrier Comfort Networkr (CCN) devices. This  
control is designed to allow users the access and ability to  
change factory-defined settings, thus expanding the  
function of the standard unit control board. CCN service  
access tools include System Pilott, Touch Pilott and  
Service Tool. (Standard tier display tools Navigatort and  
Scrolling Marquee are not suitable for use with latest  
PremierLink controller (Version 2.x).)  
The PremierLink control is factory-mounted in the 48HC  
unit’s main control box to the right of the Central Terminal  
Board (CTB) (see Fig. 37). Factory wiring is completed  
through harnesses connected to the CTB thermostat. Field  
connections are made at a 16-pole terminal block (TB3)  
located at the top of the unit control box in front of the  
PremierLink controller. The factory-installed PremierLink  
control includes the supply-air temperature (SAT) sensor.  
The outdoor air temperature (OAT) sensor is included in the  
FIOP/accessory EconoMi$ert2 package. (See page 45 for  
accessory enthalpy controls.)  
The PremierLink controller requires the use of a Carrier  
electronic thermostat or a CCN connection for time  
broadcast to initiate its internal timeclock. This is  
necessary for broadcast of time of day functions  
(occupied/unoccupied).  
C10643  
Fig. 37 - 48HC Control Box Component Locations  
NOTE: PremierLink controller is shipped in Sensor  
mode. To be used with a thermostat, the PremierLink  
controller must be configured to Thermostat mode. Refer  
to PremierLink Configuration instructions for Operating  
Mode.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C11140  
Fig. 38 - PremierLink Wiring Schematic  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C11141  
Fig. 39 - PremierLink Wiring Schematic with Humidi-MiZerR  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Supply Air Temperature (SAT) Sensor —  
NOTE: The sensor must be mounted in the discharge  
airstream downstream of the cooling coil and any heating  
devices. Be sure the probe tip does not come in contact  
with any of the unit’s heater surfaces.  
On FIOP-equipped 48HC unit, the unit is supplied with a  
supply-air temperature (SAT) sensor (33ZCSENSAT).  
This sensor is a tubular probe type, approx 6-inches (12.7  
mm) in length. It is a nominal 10-k ohm thermistor.  
Outdoor Air Temperature (OAT) Sensor —  
The OAT is factory-mounted in the EconoMi$er2 (FIOP  
or accessory). It is a nominal 10k ohm thermistor attached  
to an eyelet mounting ring.  
The SAT is factory-wired. The SAT probe is mounted in  
the fan deck (see Fig. 40). It can be removed or  
remounted per local codes.. Drill or punch a 1/2-in. hole  
in the flange or duct. Use two field-supplied, self-drilling  
screws to secure the sensor probe in a horizontal  
orientation. Insure that the sensor wires do not contact the  
hot surface of the heat exchanger.  
EconoMi$er2 —  
The PremierLink control is used with EconoMi$er2  
(option or accessory) for outdoor air management. The  
damper position is controlled directly by the PremierLink  
control; EconoMi$er2 has no internal logic device.  
Outdoor air management functions can be enhanced with  
field-installation of these accessory control devices:  
Enthalpy control (outdoor air or differential sensors)  
Space CO2 sensor  
Outdoor air CO2 sensor  
Refer to Table 4 for accessory part numbers.  
SUPPLY AIR  
ROOF  
TEMPERATURE  
CURB  
SENSOR  
Field Connections  
SUPPLY AIR  
RETURN AIR  
Field connections for accessory sensor and input devices  
are made at the 16-pole terminal block (TB3, see Fig. 38  
and Fig. 39) located on the control box top shelf in front  
of the PremierLink control. Some input devices also  
require a 24-vac signal source; connect at CTB terminal  
R at “THERMOSTAT” connection strip for this signal  
source. See connections figures on following pages for  
field connection locations (and for continued connections  
at the PremierLink board inputs).  
C10733  
Fig. 40 - Mounting Location for Supply Air  
Temperature (SAT) Sensor on 48HC Units  
NOTE:  
Refer to Form 33CS-67SI for complete  
PremierLink configuration, operating sequences and  
troubleshooting information. Have a copy of this manual  
available at unit start-up.  
Table 5 provides a summary of field connections for units  
equipped with Space Sensor. Table 6 provides a summary of  
field connections for units equipped with Space Thermostat.  
Table 4 – PremierLink Sensor Usage  
OUTDOOR AIR  
TEMPERATURE  
SENSOR  
RETURN AIR  
TEMPERATURE  
SENSOR  
OUTDOOR AIR  
ENTHALPY SENSOR  
RETURN AIR  
ENTHALPY SENSOR  
APPLICATION  
Differential Dry Bulb  
Temperature with  
PremierLink  
(PremierLink requires  
4 --- 20 m A A ctuator)  
R eq uired ---  
33ZCT55SPT  
or equivalent  
I nclud ed ---  
---  
---  
---  
CRTEMPSN001A00  
Single Enthalpy with  
PremierLink  
(PremierLink requires  
4 --- 20m A A ctuator)  
I nclud ed ---  
Not Used  
R eq uires ---  
33CSENTHSW  
---  
---  
Differential Enthalpy  
with PremierLink  
(PremierLink requires  
4 --- 20m A A ctuator)  
R eq uires ---  
33CSENTHSW  
or equivalent  
R eq uires ---  
33CSENTSEN  
or equivalent  
I nclud ed ---  
Not Used  
NOTES:  
CO Sensors (Optional):  
2
33ZCSENCO2 --- Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor.  
33ZCASPCO2 --- Aspirator box used for duct---mounted CO room sensor.  
2
33ZCT55CO2 --- Space temperature and CO room sensor with override.  
2
33ZCT56CO2 --- Space temperature and CO room sensor with override and setpoint.  
2
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 5 – Space Sensor Mode  
TB3 TERMINAL  
FIELD CONNECTION  
T55 --- S E N /T56 --- S E N  
RMTOCC  
INPUT SIGNAL  
Analog (10k thermistor)  
Discrete, 24VAC  
1
2
3
4
T55 --- S E N /T56 --- S E N  
CMPSAFE  
Analog (10k thermistor)  
Discrete, 24VAC  
5
6
T56---SET  
Analog (10k thermistor)  
Discrete, 24VAC  
FSD  
7
LOOP---PWR  
Analog, 24VDC  
8
SPS  
Discrete, 24VAC  
9
IAQ---SEN  
FILTER  
A nalog, 4 --- 20m A  
Discrete, 24VAC  
A nalog, 4 --- 20m A  
Digital, , 5VDC  
A nalog, 4 --- 20m A  
Digital, 5VDC  
10  
11  
12  
13  
14  
15  
16  
I A Q --- CO M /O A Q --- CO M /R H --- CO M  
CCN + (RED)  
OAQ---SEN/RH---SEN  
CCN Gnd (WHT)  
AUX OUT(Power Exhaust)  
CCN --- (BLK)  
(Output)Discrete 24VAC  
Digital, 5VDC  
LEGEND:  
T55  
--- Space Temperature Sensor  
T56  
--- Space Temperature Sensor  
CCN  
--- Carrier Comfort Network (communication bus)  
CMPSAFE  
FILTER  
--- Compressor Safety  
--- Dirty Filter Switch  
F S D  
IAQ  
--- F ir e S h u t d o w n  
--- Indoor Air Quality (CO )  
2
OAQ  
--- Outdoor Air Quality (CO )  
2
RH  
SFS  
--- Relative Humidity  
--- Supply Fan Status  
Table 6 – Thermostat Mode  
TB3 TERMINAL  
FIELD CONNECTION  
INPUT SIGNAL  
Analog (10k thermistor)  
Discrete, 24VAC  
1
2
RAT SEN  
G
3
4
RAT SEN  
Y1  
Analog (10k thermistor)  
Discrete, 24VAC  
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
Y2  
LOOP---PWR  
W1  
I A Q --- S E N  
Discrete, 24VAC  
Analog, 24VDC  
Discrete, 24VAC  
Analog, 4---20mA  
Discrete, 24VAC  
Analog, 4---20mA  
Digital, 5VDC  
W2  
I A Q --- CO M /O A Q --- CO M /R H --- CO M  
CCN + (RED)  
O A Q --- S E N /R H --- S E N  
CCN Gnd (WHT)  
AUX OUT (Power Exhaust)  
CCN --- (BLK)  
Analog, 4---20mA  
Digital, 5VDC  
(Output) Discrete 24VAC  
Digital, 5VDC  
LEGEND:  
CCN  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
Carrier Comfort Network (communication bus)  
T h e r m o st a t Fa n  
G
IAQ  
OAQ  
RAT  
RH  
W1  
W2  
Y1  
Indoor Air Quality (CO )  
2
Outdoor Air Quality (CO )  
2
Return Air Temperature  
Relative Humidity  
Thermostat Heat Stage 1  
Thermostat Heat Stage 2  
Thermostat Cool Stage 1  
Thermostat Cool Stage 2  
Y2  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Space Sensors —  
TB3  
1
PL  
SEN  
SEN  
J6-7  
The PremierLink controller is factory-shipped configured  
for Space Sensor Mode. A Carrier T-55 or T-56 space  
sensor must be used. T-55 space temperature sensor  
provides a signal of space temperature to the PremierLink  
control. T-56 provides same space temperature signal plus  
it allows for adjustment of space temperature setpoints  
from the face of the sensor by the occupants.  
PL  
TB3  
3
J6-6  
Jumper  
SET  
SET  
J6-5  
5
C10022  
Fig. 44 - PremierLink T-56 Sensor  
Connect Thermostat —  
1
2
4
5
6
3
RED(+)  
A 7-wire thermostat connection requires a 24-v power  
source and a common connection. Use the R and C  
terminals on the CTB’s THERMOSTAT connection strip  
for these. Connect the thermostat’s Y1, Y2, W1, W2 and  
G terminals to PremierLink TB3 as shown in Fig. 45.  
WHT(GND)  
CCN COM  
BLK(-)  
SEN  
SW1  
BRN (GND)  
BLU (SPT)  
SENSOR WIRING  
If the 48HC unit is equipped with factory-installed smoke  
detector(s), disconnect the factory BLU lead at TB3-6  
(Y2) before connecting the thermostat. Identify the BLU  
lead originating at CTB-DDC-1; disconnect at TB3-6  
and tape off. Confirm that the second BLU lead at TB3-6  
remains connected to PremierLink J4-8.  
C08201  
Fig. 41 - T-55 Space Temperature Sensor Wiring  
SPACE  
THERMOSTAT  
CTB  
THERMOSTAT  
Connect T-55: See Fig. 41 for typical T-55 internal  
connections. Connect the T-55 SEN terminals to TB3  
terminals 1 and 3 (see Fig. 42).  
R
TB3  
2
R
PL  
J4-12  
G
Y1  
Y2  
W1  
W2  
C
TB3  
1
PL  
4
6
J4-10  
J4-8  
J4-6  
J4-4  
SEN  
SEN  
J6-7  
J6-6  
3
8
C10023  
10  
C
Fig. 42 - PremierLink T-55 Sensor  
CTB  
THERMOSTAT  
Connect T-56: See Fig. 43 for T-56 internal connections.  
Install a jumper between SEN and SET terminals as  
illustrated. Connect T-56 terminals to TB3 terminals 1, 3  
and 5 (see Fig. 44).  
C10283  
Fig. 45 - Space Thermostat Connections  
If the 48HC unit has an economizer system and free-cooling  
operation is required, a sensor representing Return Air  
Temperature must also be connected (field-supplied and  
installed). This sensor may be a T-55 Space Sensor (see Fig.  
41) installed in the space or in the return duct, or it may be  
sensor PNO 33ZCSENSAT, installed in the return duct.  
Connect this sensor to TB3-1 and TB3-3 per Fig. 42.  
1
2
4
5
6
3
RED(+)  
WHT(GND)  
CCN COM  
BLK(-)  
Configure the Unit for Thermostat Mode —  
SET  
SEN  
SW1  
BLK  
(T56)  
Connect to the CCN bus using a CCN service tool and  
navigate to PremierLink Configuration screen for  
Operating Mode. Default setting is Sensor Mode (value  
1). Change the value to 0 to reconfigure the controller for  
Thermostat Mode.  
BRN (GND)  
BLU (SPT)  
SENSOR WIRING  
JUMPER  
TERMINALS  
AS SHOWN  
When the PremierLink is configured for Thermostat  
Mode, these functions are not available: Fire Shutdown  
(FSD), Remote Occupied (RMTOCC), Compressor Safety  
(CMPSAFE), Supply Fan Status (SFS), and Filter Pressure  
Switch (FILTER).  
Cool  
Warm  
C08202  
Fig. 43 - T-56 Internal Connections  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
To connect the sensor to the control, identify the positive  
(4 to 20 mA) and ground (SIG COM) terminals on the  
sensor. See Fig. 46. Connect the 4-20 mA terminal to  
terminal TB3-9 and connect the SIG COM terminal to  
terminal TB3-11. See Fig. 47.  
Economizer Controls  
Indoor Air Quality (CO2) Sensor —  
The indoor air quality sensor accessory monitors space  
carbon dioxide (CO2) levels. This information is used to  
monitor IAQ levels. Several types of sensors are available,  
for wall mounting in the space or in return duct, with and  
without LCD display, and in combination with space  
temperature sensors. Sensors use infrared technology to  
measure the levels of CO2 present in the space air.  
IAQ Sensor  
J4  
4-20mA  
TB3  
9
PL  
J5-5  
TB3  
11  
SIG COM  
J5-3  
24 VAC  
C11156  
The CO2 sensors are all factory set for a range of 0 to  
2000 ppm and a linear mA output of 4 to 20. Refer to the  
instructions supplied with the CO2 sensor for electrical  
requirements and terminal locations. See Fig. 46 for  
typical CO2 sensor wiring schematic.  
Fig. 47 - Indoor CO2 Sensor (33ZCSENCO2)  
Connections  
Refer to Form 33CS-67SI, PremierLink Installation,  
Start-up, and Configuration Instructions, for detailed  
configuration information.  
Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plus  
weatherproof enclosure) —  
The outdoor air CO2 sensor is designed to monitor carbon  
dioxide (CO2) levels in the outside ventilation air and  
interface with the ventilation damper in an HVAC system.  
The OAQ sensor is packaged with an outdoor cover. See  
Fig. 48. The outdoor air CO2 sensor must be located in the  
economizer outside air hood.  
+ 0-10VDC  
-
SIG COM  
4-20mA  
+
ALARM  
NC  
COM RELAY  
}
NO CONTACTS  
24 VAC  
OR  
24 VDC  
H G  
+
-
2 1  
J3  
5 4 3 2 1  
8 7 6  
J4  
C08635  
Fig. 46 - Indoor/Outdoor Air Quality (CO2) Sensor  
(33ZCSENCO2) - Typical Wiring Diagram  
To accurately monitor the quality of the air in the  
conditioned air space, locate the sensor near a return-air  
grille (if present) so it senses the concentration of CO2  
leaving the space. The sensor should be mounted in a  
location to avoid direct breath contact.  
COVER REMOVED  
SIDE VIEW  
C07135  
Fig. 48 - Outdoor Air Quality Sensor Cover  
Do not mount the IAQ sensor in drafty areas such as near  
supply ducts, open windows, fans, or over heat sources.  
Allow at least 3 ft (0.9 m) between the sensor and any  
corner. Avoid mounting the sensor where it is influenced  
by the supply air; the sensor gives inaccurate readings if  
the supply air is blown directly onto the sensor or if the  
supply air does not have a chance to mix with the room air  
before it is drawn into the return airstream.  
Wiring the Outdoor Air CO2 Sensor: A dedicated  
power supply is required for this sensor. A two-wire cable  
is required to wire the dedicated power supply for the  
sensor. The two wires should be connected to the power  
supply and terminals 1 and 2.  
To connect the sensor to the control, identify the positive  
(4 to 20 mA) and ground (SIG COM) terminals on the  
OAQ sensor. See Fig. 46. Connect the 4 to 20 mA  
terminal to the TB3-13 terminal of the 48HC. Connect the  
SIG COM terminal to the TB3-11 terminal of the 48HC.  
See Fig. 49.  
Wiring the Indoor Air Quality Sensor: For each sensor,  
use two 2-conductor 18 AWG (American Wire Gage)  
twisted-pair cables (unshielded) to connect the separate  
isolated 24 vac power source to the sensor and to connect  
the sensor to the control board terminals.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OAQ Sensor  
24 VAC  
The sensor must be mounted vertically on the wall. The  
Carrier logo should be orientated correctly when the  
sensor is properly mounted.  
Avoid corner locations. Allow at least 4 ft between the  
sensor and any corner. Airflow near corners tends to be  
reduced, resulting in erratic sensor readings. The sensor  
should be vertically mounted approximately 5 ft up from  
the floor, beside the space temperature sensor.  
For wiring distances up to 500 feet, use a 3-conductor, 18  
or 20 AWG cable. ACCN communication cable can be  
used, although the shield is not required. The shield must  
be removed from the sensor end of the cable if this cable  
is used. See Fig. 51 for wiring details.  
TB3  
13  
PL  
J5-2  
4-20mA  
TB3  
11  
SIG COM  
J5-3  
C11157  
Fig. 49 - Outdoor CO2 Sensor Connections  
Space Relative Humidity Sensor or Humidistat  
Connections —  
Space Relative Humidity Sensor connections: The  
accessory space relative humidity sensor (33ZCSENSRH-01)  
is installed on an interior wall to measure the relative  
humidity of the air within the occupied space.  
The use of a standard 2 X 4 inch electrical box to  
accommodate the wiring is recommended for installation.  
The sensor can be mounted directly on the wall, if  
acceptable by local codes.  
TB3-7  
TB3-13  
!
CAUTION  
UNIT DAMAGE HAZARD  
Failure to follow this caution may result in  
permanent damage to the sensor.  
Io Vin Gnd Vo  
DO NOT clean or touch the sensing element with  
chemical solvents as they can permanently damage the  
sensor.  
!
CAUTION  
C11085  
Fig. 51 - Space Relative Humidity Sensor Connection  
UNIT PERFORMANCE HAZARD  
Failure to follow this caution will result in inaccurate  
sensor readings.  
The power for the sensor is provided by the PremierLink  
control on terminal J5-4 (+33 to +35vdc).  
To wire the sensor:  
DO NOT mount the sensor in drafty areas such as near  
heating or air-conditioning ducts, open windows, fans,  
or over heat sources such as baseboard heaters,  
radiators, or wall-mounted dimmers. Sensors mounted  
in those areas will produce inaccurate readings.  
1. At the sensor, remove 4 inches of the jacket from the  
1
cable. Strip /4 inch of insulation from each conduct-  
or. Route the cable through the wire clearance open-  
ing in the center of the sensor. See Fig. 50.  
2. Connect a field-supplied BLACK wire to the sensor  
screw terminal marked Vin.  
3. Connect a field-supplied RED wire into the sensor  
screw terminal marked Io.  
If the sensor is installed directly on a wall service, install the  
humidity sensor using 2 screws and 2 hollow wall anchors  
(field supplied). Do not over tighten screws. See Fig. 50.  
4. Connect the field-supplied RED wire from the sensor  
to TB3-13.  
5. Connect the field-supplied BLACK wire from the  
sensor to TB3-7.  
MOUNTING  
HOLES  
WIRING  
OPENING  
Io  
Vin Gnd  
Vo  
Humidistat connections: A humidistat can not be directly  
connected to the PremierLink controller. Follow the  
instructions on pages 24 & 25 to connect a humidistat or a  
thermostat as an electromechanical device.  
3 SW2  
6
5
4
1
2
O N  
Fig. 50 - Space Relative Humidity Sensor InstallaCti1o10n84  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Smoke Detector/Fire Shutdown (FSD) —  
Connect one side of the switch’s NO contact set to CTB’s  
THERMOSTAT-R terminal. Connect the other side of the  
NO contact set to TB3-8. Setpoint for Supply Fan Status  
is set at the switch. See Fig. 53.  
This function is available only when PremierLink is  
configured for (Space) Sensor Mode. The unit is  
factory-wired for PremierLink FSD operation when  
PremierLink is factory-installed.  
Fan (Pressure) Switch (NO, close on rise in pressure)  
CTB  
On 48HC units equipped with factory-installed Smoke  
Detector(s), the smoke detector controller implements the  
unit shutdown through its NC contact set connected to the  
unit’s CTB input. The FSD function is initiated via the  
smoke detector’s Alarm NO contact set. The PremierLink  
communicates the smoke detector’s tripped status to the  
CCN building control. See Figs. 38 and 39, the PremierLink  
wiring schematics.  
Thermostat  
R
TB3  
8
PL  
J4-6  
C10287  
Fig. 53 - PremierLink Wiring Fan Pressure Switch  
Connection  
Filter Status Switch —  
Remote Occupied Switch —  
This function is available only when PremierLink is  
configured for (Space) Sensor Mode.  
The PremierLink control permits a remote timeclock to  
override the control’s on-board occupancy schedule and  
place the unit into Occupied mode. This function may also  
provide a “Door Switch” time delay function that will  
terminate cooling and heating functions after a 2-20  
minute delay.  
PremierLink control can monitor return filter status in two  
ways: By monitoring a field-supplied/installed filter  
pressure switch or via supply fan runtime hours.  
Using switch input: Install the dirty filter pressure switch  
according to switch manufacturer’s instructions, to  
measure pressure drop across the unit’s return filters.  
Connect one side of the switch’s NO contact set to CTB’s  
THERMOSTAT-R terminal. Connect the other side of the  
NO contact set to TB3-10. Setpoint for Dirty Filter is set  
at the switch. See Fig. 52.  
Connect one side of the NO contact set on the timeclock  
to CTB’s THERMOSTAT-R terminal. Connect the other  
side of the timeclock contact to the unit’s TB3-2 terminal.  
LCTB  
Remote Occupied  
Thermostat  
R
Filter Switch (NO, close on rising pressure (high drop))  
Time Clock  
TB3  
2
PL  
J4-12  
CTB  
Thermostat  
C10288  
R
Fig. 54 - PremierLink Wiring Remote Occupied  
TB3  
10  
PL  
J4-4  
Refer to Form 33CS-67SI for additional information on  
configuring the PremierLink control for Door Switch  
timer function.  
C10286  
Fig. 52 - PremierLink Filter Switch Connection  
Power Exhaust (output) —  
When the filter switch’s NO contact set closes as filter  
pressure drop increases (indicating dirt-laden filters), the  
input signal to PremierLink causes the filter status point to  
read “DIRTY”.  
Connect the accessory Power Exhaust contactor coils(s)  
per Fig. 55.  
Power Exhaust  
TB3  
15  
PL  
J8-3  
Using Filter Timer Hours: Refer to Form 33CS-67SI for  
instructions on using the PremierLink Configuration  
screens and on unit alarm sequence.  
PER  
VIO  
CTB  
THERMOSTAT  
Supply Fan Status Switch —  
C
BRN  
C11158  
The PremierLink control can monitor supply fan operation  
through a field-supplied/installed differential pressure  
switch. This sequence will prevent (or interrupt) operation  
of unit cooling, heating and economizer functions until  
the pressure switch contacts are closed indicating proper  
supply fan operation.  
Fig. 55 - PremierLink Power Exhaust Output  
Connection  
NOTE: The Power Exhaust and Humidi-MiZerR options  
can not be used with PremierLink at the same time as both  
options require connection at TB3-15 (AUX OUT).  
Install the differential pressure switch in the supply fan  
section according to switch manufacturer’s instructions.  
Arrange the switch contact to be open on no flow and to  
close as pressure rises indicating fan operation.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CCN Communication Bus —  
The communication bus shields must be tied together at  
each system element. If the communication bus is entirely  
within one building, the resulting continuous shield must  
be connected to ground at only one single point. If the  
communication bus cable exits from one building and  
enters another building, the shields must be connected to  
the grounds at a lightning suppressor in each building (one  
point only).  
The PremierLink controller connects to the bus in a daisy  
chain arrangement. Negative pins on each component  
must be connected to respective negative pins, and  
likewise, positive pins on each component must be  
connected to respective positive pins. The controller  
signal pins must be wired to the signal ground pins.  
Wiring connections for CCN must be made at the 3-pin  
plug.  
Connecting CCN Bus:  
NOTE: When connecting the communication bus cable,  
At any baud (9600, 19200, 38400 baud), the number of  
controllers is limited to 239 devices maximum. Bus length  
may not exceed 4000 ft (1219 m), with no more than 60  
total devices on any 1000-ft section. Optically isolated  
RS-485 repeaters are required every 1000 ft (305 m).  
a
color code system for the entire network is  
recommended to simplify installation and checkout. See  
Table 8 for the recommended color code.  
Table 8 – Color Code Recommendations  
NOTE: Carrier device default is 9600 baud.  
CCN BUS WIRE  
COLOR  
CCN PLUG PIN  
NUMBER  
SIGNAL TYPE  
Communications Bus Wire Specifications: The CCN  
Communication Bus wiring is field-supplied and  
field-installed. It consists of shielded 3-conductor cable  
with drain (ground) wire. The cable selected must be  
identical to the CCN Communication Bus wire used for  
the entire network.  
+
Ground  
---  
Red  
White  
Black  
1
2
3
Connect the CCN (+) lead (typically RED) to the unit’s  
TB3-12 terminal. Connect the CCN (ground) lead  
(typically WHT) to the unit’s TB3-14 terminal. Connect  
the CCN (-) lead (typically BLK) to the unit’s TB3-16  
terminal. See Fig. 56.  
See Table 7 for recommended cable.  
Table 7 – Recommended Cables  
MANUFACTURER  
Alpha  
CABLE PART NO.  
2413 or 5463  
A22503  
CCN Bus  
American  
Belden  
PL  
J2-1  
TB3  
12  
8772  
+ (RED)  
GND (WHT)  
– (BLK)  
Columbia  
02525  
TB3  
14  
J2-2  
J2-3  
NOTE: Conductors and drain wire must be at least 20  
AWG, stranded, and tinned copper. Individual conductors  
must be insulated with PVC, PVC/nylon, vinyl, Teflon, or  
polyethylene. An aluminum/polyester 100% foil shield  
and an outer jacket of PVC, PVC/nylon, chrome vinyl, or  
Teflon with a minimum operating temperature range of  
- 2 0 _C (-4_F) to 60_C (140_F) is required. Do not run  
communication wire in the same conduit as or next to any  
AC voltage wiring.  
TB3  
16  
C10290  
Fig. 56 - PremierLink CCN Bus Connections  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The RTU Open controller is an integrated component of the  
Carrier rooftop unit. Its internal application programming  
provides optimum performance and energy efficiency. RTU  
Open enables the unit to run in 100% stand-alone control  
mode, Carrier’s I-Vu Open network, or a Third Party  
Building Automation System (BAS). On-board DIP  
switches allow you to select your protocol (and baud rate) of  
choice among the four most popular protocols in use today:  
BACnet, Modbus, Johnson N2 and LonWorks. (See Fig. 57.)  
RTU Open Control System  
The RTU Open control is factory-mounted in the 48HC  
unit’s main control box, to the right of the CTB. See  
Fig. 37. Factory wiring is completed through harnesses  
connected to the CTB. Field connections for RTU Open  
sensors will be made at the Phoenix connectors on the  
RTU Open board. The factory-installed RTU Open  
control includes the supply-air temperature (SAT) sensor.  
The outdoor air temperature (OAT) sensor is included in  
the FIOP/accessory EconoMi$er2 package.  
Refer to Table 9, RTU Open Controller Inputs and Outputs  
for locations of all connections to the RTU Open board.  
C10811  
Fig. 57 - RTU Open Multi-Protocol Control Board  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C11142  
Fig. 58 - RTU Open System Control Wiring Diagram  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C11143  
Fig. 59 - RTU Open System Control Wiring Diagram with Humidi-MiZerR  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 9 – RTU Open Controller Inputs and Outputs  
BACnet OBJECT  
TYPE OF I/O  
NAME  
CONNECTION PIN  
NUMBER(S)  
POINT NAME  
DEDICATED INPUTS  
Space Temp / Zone Temp  
Supply Air Temperature  
Outdoor Air Temperature  
Space Temperature Offset Pot  
Safety Chain Feedback  
Compressor Safety Status  
Fire Shutdown Status  
zone_temp  
sa_temp  
oa_temp  
stpt_adj_offset  
safety_status  
comp_status  
firedown_status  
enthalpy_status  
humstat_status  
AI (10K Thermistor)  
AI (10K Thermistor)  
AI (10K Thermistor)  
AI (100K Potentiometer)  
DI (24 VAC)  
J 2 0 --- 1 , 2  
J 2 --- 1 , 2  
J 2 --- 3 , 4  
J 2 0 --- 3  
J 1 --- 9  
J 1 --- 2  
J 1 --- 1 0  
J 2 --- 6  
DI (24 VAC)  
DI (24 VAC)  
DI (24 VAC)  
DI (24 VAC)  
Enthalpy Status  
Humidistat Input Status  
J 5 --- 7  
CONFIGURABLE INPUTS  
Indoor Air CO2  
iaq  
oaq  
space_rh  
A I ( 4 --- 2 0 m a )  
A I ( 4 --- 2 0 m a )  
A I ( 4 --- 2 0 m a )  
DI (24 VAC)  
DI (24 VAC)  
DI (24 VAC)  
DI (24 VAC)  
Outdoor Air CO2  
Space Relative Humidity  
Supply Fan Status*  
Filter Status*  
Door Contact Input*  
Occupancy Contact*  
J 4 --- 2 o r J 4 --- 5  
sfan_status  
filter_status  
door_contact_status  
occ_contact_status  
J 5 --- 1 o r J 5 --- 3 o r  
J5 5 or J5---7  
OUTPUTS  
Economizer Output  
econ_output  
sfan  
A O ( 4 --- 2 0 m a )  
J 2 --- 5  
J 1 --- 4  
J 1 --- 8  
J 1 --- 7  
J 1 --- 6  
J 1 --- 5  
J 1 1 --- 3  
J 1 1 --- 7 , 8  
Supply Fan Relay State  
Compressor 1 Relay State  
Compressor 2 Relay State  
Heat Stage 1 Relay State  
Heat Stage 2 Relay State  
Power Exhaust Relay State  
Dehumidification Relay State  
DO Relay (24VAC , 1A)  
DO Relay (24VAC , 1A)  
DO Relay (24VAC , 1A)  
DO Relay (24VAC , 1A)  
DO Relay (24VAC , 1A)  
DO Relay (24VAC , 1A)  
DO Relay (24VAC, 1A)  
comp_1  
comp_2  
heat_1  
heat_2  
pexh  
dehum  
LEGEND  
AI --- An al og In pu t  
AO --- An al og Ou tpu t  
DI --- D iscr ete In pu t  
DO --- Discrete Output  
*
These inputs (if installed) take the place of the default input on the specific channel according to schematic.  
Par al l el pin s J 5 --- 1 = J 2 --- 6, J 5 --- 3 = J 1 --- 10, J 5 --- 5 = J 1 --- 2 ar e u sed f or f iel d --- in stal l ation .  
The RTU Open controller requires the use of a Carrier  
space sensor. A standard thermostat cannot be used with  
the RTU Open system.  
EconoMi$er2 —  
The RTU Open control is used with EconoMi$er2 (option  
or accessory) for outdoor air management. The damper  
position is controlled directly by the RTU Open control;  
EconoMi$er2 has no internal logic device.  
Supply Air Temperature (SAT) Sensor —  
On FIOP-equipped 48HC unit, the unit is supplied with a  
supply-air temperature (SAT) sensor (33ZCSENSAT). This  
sensor is a tubular probe type, approx 6-inches (12.7 mm) in  
length. It is a nominal 10-k ohm thermistor.  
Outdoor air management functions can be enhanced with  
field-installation of these accessory control devices:  
Enthalpy control (outdoor air or differential sensors)  
Space CO2 sensor  
Outdoor air CO2 sensor  
The SAT is factory-wired. The SAT probe is wire-tied to the  
supply-air opening (on the horizontal opening end) in its  
shipping position. Remove the sensor for installation.  
Re-position the sensor in the flange of the supply-air  
opening or in the supply air duct (as required by local  
Field Connections  
1
codes). Drill or punch a /2-in. hole in the flange or duct.  
Field connections for accessory sensors and input devices  
are made the RTU Open, at plugs J1, J2, J4, J5, J11 and  
J20. All field control wiring that connects to the RTU  
Open must be routed through the raceway built into the  
corner post as shown in Fig. 31. The raceway provides the  
UL required clearance between high- and low-voltage  
wiring. Pass the control wires through the hole provided in  
the corner post, then feed the wires thorough the raceway  
Use two field-supplied, self-drilling screws to secure the  
sensor probe in a horizontal orientation. See Fig. 40.  
Outdoor Air Temperature (OAT) Sensor —  
The OAT is factory-mounted in the EconoMi$er2 (FIOP or  
accessory). It is a nominal 10k ohm thermistor attached to  
an eyelet mounting ring.  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
to the RTU Open. Connect to the wires to the removable  
Phoenix connectors and then reconnect the connectors to  
the board.  
Connect T  
                                                                                                                             
-59: The T-59 space sensor requires a  
                                                                                                                                                
separate, isolated power supply of 24 VAC. See Fig. 62  
for internal connections at the T-59. Connect the SEN  
terminal (BLU) to RTU Open J20-1. Connect the COM  
terminal (BRN) to J20-2. Connect the SET terminal (STO  
or BLK) to J20-3.  
Space Temperature (SPT) Sensors —  
There are two types of SPT sensors available from Carrier,  
resistive input non-communicating (T55, T56, and T59)  
and Rnet communicating (SPS, SPPL, SPP, and SPPF)  
sensors. Each type has a variety of options consisting of:  
timed override button, set point adjustment, a LCD  
screen, and communication tie in. Space temperature can  
be also be written to from a building network or zoning  
system. However, it is still recommended that return air  
duct sensor be installed to allow stand-alone operation for  
back-up. Refer to the configuration section for details on  
controller configurations associated with space sensors.  
BLK (STO)  
J20-3  
BRN (COM)  
SENSOR  
J20-2  
WIRING  
BLU (SPT)  
J20-1  
OR  
SET SEN  
S 33ZCT55SPT, space temperature sensor with override  
button (T-55)  
OPB COM- PWR+  
S 33ZCT56SPT, space temperature sensor with override  
button and setpoint adjustment (T-56)  
S 33ZCT59SPT, space temperature sensor with LCD  
(liquid crystal display) screen, override button, and  
setpoint adjustment (T-59)  
POWER  
WIRING  
24 VAC  
NOTE: Must use a separate isolated transformer.  
C10291  
Use 20 gauge wire to connect the sensor to the controller.  
The wire is suitable for distances of up to 500 ft. (152 m).  
Use a three-conductor shielded cable for the sensor and  
setpoint adjustment connections. If the setpoint  
adjustment (slidebar) is not required, then an unshielded,  
18 or 20 gauge, two-conductor, twisted pair cable may be  
used.  
Fig. 62 - Space Temperature Sensor Typical Wiring  
(33ZCT59SPT)  
Indoor Air Quality (CO2) Sensor —  
The indoor air quality sensor accessory monitors space  
carbon dioxide (CO2) levels. This information is used to  
monitor IAQ levels. Several types of sensors are available,  
for wall mounting in the space or in return duct, with and  
without LCD display, and in combination with space  
temperature sensors. Sensors use infrared technology to  
measure the levels of CO2 present in the space air.  
Connect T-55: See Fig. 41 for typical T-55 internal  
connections. Connect the T-55 SEN terminals to RTU  
Open J20-1 and J20-2. See Fig. 60.  
J20-1  
J20-2  
SEN  
SEN  
The CO2 sensors are all factory set for a range of 0 to  
2000 ppm and a linear mA output of 4 to 20. Refer to the  
instructions supplied with the CO2 sensor for electrical  
requirements and terminal locations. See Fig. 46 for  
typical CO2 sensor wiring schematic.  
C08460  
Fig. 60 - RTU Open T-55 Sensor Connections  
To accurately monitor the quality of the air in the  
conditioned air space, locate the sensor near a return-air  
grille (if present) so it senses the concentration of CO2  
leaving the space. The sensor should be mounted in a  
location to avoid direct breath contact.  
Connect T-56: See Fig. 43 for T-56 internal connections.  
Install a jumper between SEN and SET terminals as  
illustrated. Connect T-56 terminals to RTU Open J20-1,  
J20-2 and J20-3 per Fig. 61.  
Do not mount the IAQ sensor in drafty areas such as near  
supply ducts, open windows, fans, or over heat sources.  
Allow at least 3 ft (0.9 m) between the sensor and any  
corner. Avoid mounting the sensor where it is influenced  
by the supply air; the sensor gives inaccurate readings if  
the supply air is blown directly onto the sensor or if the  
supply air does not have a chance to mix with the room air  
before it is drawn into the return airstream.  
SEN  
SEN  
J20-1  
J20-2  
Jumper  
SET  
SET  
J20-3  
Wiring the Indoor Air Quality Sensor: For each sensor,  
use two 2-conductor 18 AWG (American Wire Gage)  
twisted-pair cables (unshielded) to connect the separate  
C08461  
Fig. 61 - RTU Open T-56 Sensor Connections  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
isolated 24 vac power source to the sensor and to connect  
the sensor to the control board terminals.  
Space Relative Humidity Sensor or Humidistat —  
Humidi-MiZerR Control Wiring: In units equipped  
with the Humidi-MiZer option there are two pink (PNK)  
wires loose in the control box used to control the  
dehumidification function of the unit. These pink wires  
are meant to be tied to a space humidistat or thermidistat  
on an electromechanical unit. On RTU Open equipped  
units these pink wires must be connected to J11-7 & 8 to  
allow the Open board to operate the dehumidification  
function for the unit. Disconnect the J11 Phoenix style  
connector from the board and use the plug screws to  
secure the pink wires in pins 7 and 8, reconnect the plug  
to the board at J11.  
To connect the sensor to the control, identify the positive  
(4 to 20 mA) and ground (SIG COM) terminals on the  
sensor. See Fig. 46. Connect the 4-20 mA terminal to  
RTU Open terminal J4-2 and connect the SIG COM  
terminal to RTU Open terminal J4-3. See Fig. 63.  
IAQ Sensor  
4-20mA  
J4-2  
SIG COM  
J4-3  
Relative Humidity Sensors (Space or Duct Mounted):  
The accessory space humidity sensor (33ZCSENSRH-01)  
or duct humidity sensor (33ZCSENDRH-01) is used to  
measure the relative humidity of air within the space or  
return air duct. The RH reading is used to control the  
Humidi-MiZer option of the rooftop unit. For wiring  
distances up to 500 ft (152 m), use a 3-conductor, 18 or  
20 AWG shielded cable. The shield must be removed  
from the sensor end of the cable and grounded at the unit  
end. The current loop power for sensor is provided by the  
RTU Open controller as 24vdc. Refer to the instructions  
supplied with the RH sensor for the electrical  
requirements and terminal locations. RTU Open  
configurations must be changed after adding an RH  
sensor. See Fig. 65 and 66 for typical RH sensor wiring.  
24 VAC  
C10738  
Fig. 63 - RTU Open / Indoor CO2 Sensor  
(33ZCSENCO2) Connections  
Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plus  
weatherproof enclosure) —  
The outdoor air CO2 sensor is designed to monitor carbon  
dioxide (CO2) levels in the outside ventilation air and  
interface with the ventilation damper in an HVAC system.  
The OAQ sensor is packaged with an outdoor cover. See  
Fig. 48. The outdoor air CO2 sensor must be located in the  
economizer outside air hood.  
S J4-1 or J4-4 = 24vdc loop power  
Wiring the Outdoor Air CO2 Sensor: A dedicated  
power supply is required for this sensor. A two-wire cable  
is required to wire the dedicated power supply for the  
sensor. The two wires should be connected to the power  
supply and terminals 1 and 2.  
S J4-2 or J4-5 = 4-20mA signal input  
NOTE: The factory default for dehumidification control  
is normally open humidistat.  
To connect the sensor to the control, identify the positive  
(4 to 20 mA) and ground (SIG COM) terminals on the  
OAQ sensor. See Fig. 46. Connect the 4 to 20 mA  
terminal to RTU Open terminal J4-5. Connect the SIG  
COM terminal to RTU Open terminal J4-6. See Fig. 64.  
MOUNTING  
HOLES  
WIRING  
Io  
Gnd  
Vin  
Vo  
OPENING  
OAQ Sensor/RH Sensor  
4-20mA  
J4-5  
J4-6  
C10739  
SIG COM  
24 VAC  
3 SW2  
6
5
4
1
2
O N  
Fig. 64 - RTU Open / Outdoor CO2 Sensor  
(33ZCSENCO2) Connections  
Vin - J4-1 or J4-4 24Vdc  
Io - J4-2 or J4-5 -20mA output  
C11087  
Fig. 65 - Space Relative Humidity Sensor Typical Wiring  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
J4-1 or J4-4 + 24 VDC Supply Voltage  
J4-2 or J4-5 (-) 4 to 20 mA Current Loop Output  
to RTU-OPEN  
Relative Humidity Sensor  
(Polarized Male Connector)  
SPAN  
ZERO  
4-20 VAC GND 0-5V  
mA or  
VDC  
or  
0-10V  
C10839  
Fig. 66 - Duct Relative Humidity Sensor Typical Wiring  
Humidistat: The accessory humidistat provides the RTU  
Open insight to the relative humidity in the space. The  
humidistat reads the RH level in the space and compares it  
to its setpoint to operate a dry contact. The humidistat is a  
dedicated input on the configurable input 9 and tells the  
RTU Open when the RH level is HIGH or LOW. The  
normal condition for humidity is LOW. A normally open  
humidistat is the factory default control for the  
Humidi-MiZerR option.  
Fan Status: The fan status accessory is a field-installed  
accessory. This accessory detects when the indoor fan is  
blowing air. When installing this accessory, the unit must  
be  
configured  
for  
fan  
status  
by  
setting  
MENUConfigInputsinput 3, 5, 8, or 9 to Fan  
Status and normally open (N/O) or normally closed (N/C).  
Input 8 or 9 is recommended for easy of installation. Refer  
to Fig. 57 and Fig. 58 or 59 for wire terminations at J5.  
Remote Occupancy: The remote occupancy accessory is  
a field-installed accessory. This accessory overrides the  
unoccupied mode and puts the unit in occupied mode.  
When installing this accessory, the unit must be  
To wire in the field:  
S J5-8 = 24 VAC source for dry contact  
S J5-7 = Signal input  
configured for  
remote occupancy by setting  
Smoke Detector/Fire Shutdown (FSD) —  
MENUConfigInputsinput 3, 5, 8, or 9 to Remote  
Occupancy and normally open (N/O) or normally closed  
(N/C).  
On 48HC units equipped with factory-installed Smoke  
Detector(s), the smoke detector controller implements the  
unit shutdown through its NC contact set connected to the  
unit’s CTB input. The FSD function is initiated via the  
smoke detector’s Alarm NO contact set. The RTU Open  
controller communicates the smoke detector’s tripped status  
to the BAS building control. See Figs. 58 and 59, the RTU  
Open wiring schematics.  
Also set MENUSchedulesoccupancy source to DI  
on/off. Input 8 or 9 is recommended for easy of  
installation. Refer to Fig. 57 and Table 9 for wire  
terminations at J5.  
Power Exhaust (output): The relay used by the RTU  
Open board to control power exhaust is a dry contact  
which means it does not have 24vac. This 24vac must be  
connected to the relay to allow it to operate the power  
exhaust relay in the PE accessory. A 24vac source must be  
provided to J11-2 on the RTU Open control board. This  
can be provided by the unit’s transformer from various  
sources. The “R” terminal on the unit’s low voltage  
terminal board (LVTB) is a logical source. Refer to Fig.  
57 and Fig. 58 or 59 for wire terminations at J11.  
The  
Fire  
Shutdown  
Switch  
configuration,  
identifies the  
MENUConfigInputsinput 5,  
normally open status of this input when there is no fire  
alarm.  
Connecting Discrete Inputs —  
Filter Status: The filter status accessory is  
a
field-installed accessory. This accessory detects plugged  
filters. When installing this accessory, the unit must be  
configured  
for  
filter  
status  
by  
setting  
MENUConfigInputsinput 3, 5, 8, or 9 to Filter  
Status and normally open (N/O) or normally closed (N/C).  
Input 8 or 9 is recommended for easy of installation. Refer  
to Fig. 57 and Fig. 58 or 59 for wire terminations at J5.  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The RTU Open can be set to communicate on four  
different protocols: BACnet, Modbus, N2, and LonWorks.  
Switch 3 (SW3) on the board is used to set protocol and  
baud rate. Switches 1 and 2 (SW1 and SW2) are used to  
set the board’s network address. See Fig. 67 and 68 for  
protocol switch settings and address switches. The 3rd  
party connection to the RTU Open is through plug J19.  
See Fig. 69 for wiring.  
NOTE: Power must be cycled after changing the SW1-3  
switch settings.  
Refer to the RTU Open Controller Integration Guide  
(Catalog No. 11-808-428-01) for more detailed information  
on protocols, 3rd party wiring, and networking.  
Communication Wiring -- Protocols  
General —  
Protocols are the communication languages spoken by  
control devices. The main purpose of a protocol is to  
communicate information in the most efficient method  
possible. Different protocols exist to provide different  
kinds of information for different applications. In the BAS  
application, many different protocols are used, depending  
on manufacturer. Protocols do not change the function of  
a controller; just make the front end user different.  
SW3 Protocol Selection  
DS6 DS5  
PROTOCOL  
DS8  
DS7  
DS4  
DS3  
DS2  
DS1  
BACnet MS/TP  
(Master)  
Unused  
OFF  
OFF  
OFF  
ON  
OFF  
Select Baud Select Baud  
Select Baud Select Baud  
Modbus  
(Slave)  
Unused  
OFF  
OFF  
ON  
ON  
OFF  
N2  
Unused  
Unused  
OFF  
ON  
OFF  
ON  
OFF  
OFF  
ON  
ON  
ON  
OFF  
OFF  
OFF  
OFF  
(Slave)  
LonWorks  
OFF  
NOTE:  
DS = Dip Switch  
BACnet MS/TP SW3 example shown  
Baud Rate Selections  
BAUD RATE  
9600  
DS2  
OFF  
ON  
DS1  
OFF  
OFF  
ON  
19,200  
38,400  
OFF  
ON  
76,800  
ON  
C07166  
Fig. 67 - RTU Open SW3 Dip Switch Settings  
C10815  
Fig. 68 - RTU Open Address Switches  
C10816  
Fig. 69 - Network Wiring  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Local Access —  
Virtual BACview: Virtual BACview is a freeware computer  
program that functions as the BACview6 Handheld. The  
USB Link interface (USB-L) is required to connect a  
computer to the RTU Open board. The link cable connects  
a USB port to the J12 local access port. This program  
functions and operates identical to the handheld.  
BACview6 Handheld: The BACview6 is a keypad/display  
interface used to connect to the RTU Open to access the  
control information, read sensor values, and test the RTU,  
see Fig. 70. This is an accessory interface that does not  
come with the RTU Open controller and can only be used  
at the unit. Connect the BACview6 to the RTU Open J12  
local access port. There are 2 password protected levels in  
the display (User and Admin). The user password is  
defaulted to 0000 but can be changed. The Admin  
password is 1111 and cannot be changed. There is a 10  
minute auto logout if a screen is idle. See Form  
48-50HCTQ-01T, Appendix A for navigation and screen  
content.  
RTU Open Troubleshooting —  
Communication LEDs: The LEDs indicate if the  
controller is speaking to the devices on the network. The  
LEDs should reflect communication traffic based on the  
baud rate set. The higher the baud rate the more solid the  
LEDs will appear. See Table 10.  
Access Port  
P1 P1  
Protocol Selector  
RTU Open  
J12  
P5 P5  
Cable  
BACview6 Local Access Cable  
C10812  
Fig. 70 - BACview6 Handheld Connections  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 10 – LEDs  
The LEDs on the RTU Open Control Board (see Fig. 57) show the status of certain functions:  
If this LED is on...  
Status is...  
Power  
Rx  
Tx  
RTU Open has power  
RTU Open is receiving data from the network segment  
RTU Open is transmitting data over the network segment  
The digital output is active  
DO#  
The Run and Error LEDs indicate control module and network status  
If Run LED shows...  
And Error LED shows...  
Status is...  
2 flashes per second  
Off  
Normal  
2 flashes,  
2 flashes per second  
2 flashes per second  
2 flashes per second  
2 flashes per second  
Five minute auto---restart delay after system error  
Control module has just been formatted  
alternating with Run LED  
3 flashes,  
then off  
4 flashes,  
then pause  
Two or more devices on this network have the  
same ARC156 network address  
Exec halted after frequent system errors or  
control programs halted  
On  
5 flashes per second  
5 flashes per second  
On  
Off  
Exec start---up aborted, Boot is running  
Firmware transfer in progress, Boot is running  
7 flashes per second, alternating with  
7 flashes per second  
14 flashes per second  
Ten second recovery period after brownout  
Run LED  
14 flashes per second,  
alternating with Run LED  
Brownout  
Failure. Try the following solutions:  
S
S
S
S
Turn RTU Open off, then on.  
Format RTU Open.  
Download memory to RTU Open.  
Replace RTU Open.  
On  
On  
NOTE:  
Refer to Catalog No. 48-50HCTQ-01T for  
Enthalpy  
Switch  
complete configuration of RTU Open, operating sequences  
and troubleshooting information. Refer to RTU Open  
Controller Integration Guide (Catalog No. 11-808-428-01)  
for details on configuration and troubleshooting of connected  
networks. Have a copy of these manuals available at unit  
start-up.  
24V  
RED  
BLK  
PL6-1 (24-V)  
PL6-4 (COM)  
GND  
LOW  
GRA  
7
CTB ECON  
(P’LINK: to J4-2) or  
(RTU Open: to J2-6)  
Outdoor Air Enthalpy Control  
(PNO 33CSENTHSW)  
Factory Wiring Harness  
C11160  
Fig. 71 - Enthalpy Switch (33CSENTHSW) Connections  
The enthalpy control (33CSENTHSW) is available as a  
field-installed accessory to be used with the EconoMi$er2  
damper system. The outdoor air enthalpy sensor is part of  
the enthalpy control. (The separate field-installed  
accessory return air enthalpy sensor (33CSENTSEN) is  
required for differential enthalpy control. See Fig. 71.)  
The outdoor enthalpy changeover setpoint is set at the  
enthalpy controller.  
Differential Enthalpy Control —  
Differential enthalpy control is provided by sensing and  
comparing the outside air and return air enthalpy  
conditions. Install the outdoor air enthalpy control as  
described above. Add and install a return air enthalpy  
sensor (see Fig. 72).  
Locate the enthalpy control in the economizer next to the  
Actuator Motor. Locate two GRA leads in the factory  
harness and connect the gray lead labeled “ESL” to the  
terminal labeled “LOW”. See Fig. 71. Connect the  
enthalpy control power input terminals to economizer  
actuator power leads RED (connect to 24V) and BLK  
(connect to GND).  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Return Air Sampling Tube  
(Shipping Location)  
24V  
RED  
PL6-1 (24-V)  
PL6-4 (COM)  
4-20  
Main  
BLK  
GND  
LOW  
+ VDC  
Out  
CTB ECON  
(P’LINK: to J4-2) or  
(RTU Open: to J2-6)  
GRA  
7
Outside Air  
Enthalpy Switch  
+ 24-36  
Return Air  
Enthalpy  
Sensor  
VDC In  
4-20 Main  
Out  
C11161  
C09102  
Fig. 72 - Outside and Return Air Enthalpy Sensor  
Wiring  
Fig. 73 - Typical Supply Air Smoke Detector Sensor  
Location  
To wire the return air enthalpy sensor, perform the  
following:  
1. Use a 2-conductor, 18 or 20 AWG, twisted pair cable  
to connect the return air enthalpy sensor to the enthal-  
py controller.  
2. Connect the field-supplied RED wire to (+) spade  
connector on the return air enthalpy sensor and the  
(+) terminal on the enthalpy controller. Connect the  
BLK wire to (-) spade connector on the return air en-  
thalpy sensor and the (-) terminal on the enthalpy  
controller.  
Smoke Detectors  
Return Air Detector  
Sampling Tube  
Smoke detectors are available as factory-installed options  
on 48HC models. Smoke detectors may be specified for  
Supply Air only or for Return Air without or with  
economizer or in combination of Supply Air and Return  
Air. Return Air smoke detectors are arranged for vertical  
return configurations only. The unit is factory-configured  
for immediate smoke detector shutdown operation;  
additional wiring or modifications to unit terminal board  
may be necessary to complete the unit and smoke detector  
configuration to meet project requirements.  
C09135  
Fig. 74 - Return Air Sampling Tube Location  
in Unit without Economizer  
Return Air Sensor Tube Installation –  
The return air sampling tube is shipped in the unit s  
supply fan section, attached to the blower housing (see  
Fig. 73. Its operating location is in the return air section  
of the unit (see Fig. 74, unit without economizer, or  
Fig. 75, unit with economizer), inserted into the return air  
sensor module housing which protrudes through the back  
of the control box.  
Return Air Detector  
Sampling Tube  
C09136  
Fig. 75 - Return Air Sampling Tube Location  
in Unit with Economizer  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
To install the return air sensor sampling tube:  
Smoke Detector Test Magnet —  
1. Remove the tube from its shipping location.  
2. Open the unit end to access the return air sensor (loc-  
ated on right-hand partition)  
Locate the magnet; it is shipped in the control box area.  
Additional Application Data —  
3. Orient the tube’s sampling holes into the return air  
flow direction. For vertical application, position the  
sampling holes on the bottom of the tube, facing into  
the bottom return duct opening. For horizontal applic-  
ation, position the sampling holes on the side of the  
tube, facing the unit’s end panel.  
Refer to Catalog No. HKRNKA-1XA for discussions on  
additional control features of these smoke detectors  
including multiple unit coordination.  
4. Insert the sampling tube into the return air sensor  
module until the tube snaps into position.  
5. Replace end panel or outside air hood.  
Table 11 – Unit Wire/Fuse or HACR Breaker Sizing Data  
COMBUSTION  
FAN MOTOR  
POWER  
EXHAUST  
NO C.O. or UNPWR C.O.  
NO P.E.  
FUSE or  
w/ P.E. (pwrd fr/ unit)  
NOM.  
V --- P h --- H z  
IFM  
TYPE  
FUSE or  
HACR  
BRKR  
DISC. SIZE  
DISC. SIZE  
FLA  
FLA  
MCA  
MCA  
HACR  
BRKR  
FLA  
LRA  
FLA  
LRA  
STD  
MED  
HIGH  
68.3  
71.0  
75.8  
90.0  
90.0  
71  
74  
80  
393  
410  
419  
80.1  
82.8  
87.6  
100.0  
100.0  
100.0  
85  
88  
93  
413  
430  
439  
208/230---3---60  
460 --- 3 --- 60  
0.52  
0.3  
5.9  
3.1  
2.4  
5.9  
3.1  
2.4  
5.9  
3.1  
2.4  
5.9  
3.1  
2.4  
100.0  
STD  
MED  
HIGH  
34.9  
36.3  
38.9  
45.0  
45.0  
50.0  
36  
38  
41  
234  
243  
247  
41.1  
42.5  
45.1  
50.0  
50.0  
50.0  
44  
45  
48  
246  
255  
259  
STD  
MED  
HIGH  
26.2  
26.2  
29  
30.0  
30.0  
35  
27  
27  
31  
184  
184  
198  
31.0  
31.0  
33.8  
40.0  
40.0  
40  
33  
33  
36  
192  
192  
206  
575 --- 3 --- 60  
0.24  
0.52  
0.3  
STD  
MED  
HIGH  
75.7  
80.5  
85.9  
100  
100  
100  
79  
85  
91  
440  
449  
459  
87.5  
92.3  
97.7  
100  
100  
125  
93  
98  
460  
469  
479  
208/230---3---60  
460 --- 3 --- 60  
104  
STD  
MED  
HIGH  
36.6  
39.2  
42  
45  
50  
50  
38  
41  
45  
245  
249  
254  
42.8  
45.4  
48.2  
50  
50  
60  
46  
49  
52  
257  
261  
266  
STD  
MED  
HIGH  
26.2  
29  
30  
35  
40  
27  
31  
35  
186  
200  
198  
31  
40  
40  
45  
33  
36  
40  
194  
208  
206  
33.8  
37.2  
575 --- 3 --- 60  
0.24  
0.52  
0.3  
32.4  
STD  
MED  
HIGH  
88.7  
94.1  
100.0  
110  
93  
544  
554  
628  
100.5  
105.9  
119.4  
125.0  
125  
107  
113  
128  
564  
574  
648  
100  
114  
208/230---3---60  
460 --- 3 --- 60  
107.6  
125  
150  
STD  
MED  
HIGH  
48.6  
51.4  
57.4  
60.0  
60  
51  
54  
61  
277  
282  
319  
54.8  
57.6  
63.6  
60.0  
70  
58  
61  
68  
289  
294  
331  
70  
80  
STD  
MED  
HIGH  
35.5  
38.9  
39.4  
45.0  
50  
37  
41  
42  
204  
202  
229  
40.3  
43.7  
44.2  
50.0  
50  
43  
47  
47  
212  
210  
237  
575 --- 3 --- 60  
0.24  
0.52  
0.3  
50  
50  
STD  
MED  
HIGH  
117.4  
122.8  
135.5  
150.0  
150  
121  
127  
142  
584  
594  
668  
129.2  
134.6  
147.3  
175.0  
175  
135  
141  
156  
604  
614  
688  
208/230---3---60  
460 --- 3 --- 60  
175  
175  
STD  
MED  
HIGH  
54.0  
56.8  
62.8  
60.0  
70  
57  
60  
67  
303  
308  
345  
60.2  
63  
70.0  
80  
64  
67  
74  
315  
320  
357  
80  
69  
80  
STD  
MED  
HIGH  
40.4  
43.8  
44.3  
50.0  
50  
42  
46  
47  
228  
226  
253  
45.2  
48.6  
49.1  
50.0  
60  
48  
52  
52  
236  
234  
261  
575 --- 3 --- 60  
0.24  
50  
60  
NOTE: See page 49 for table legend and notes.  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 11 - Unit Wire/Fuse or HACR Breaker Sizing Data (cont)  
w/ PWRD C.O.  
COMBUSTION  
FAN MOTOR  
POWER  
EXHAUST  
NO P.E.  
FUSE or  
HACR  
BRKR  
w/ P.E. (pwrd fr/ unit)  
FUSE or  
NOM.  
V --- P h --- H z  
IFM  
TYPE  
DISC. SIZE  
DISC. SIZE  
FLA  
FLA  
MCA  
MCA  
HACR  
BRKR  
FLA  
LRA  
FLA  
LRA  
STD  
MED  
HIGH  
73.1  
75.8  
80.6  
90.0  
100.0  
100.0  
77  
80  
85  
398  
415  
424  
84.9  
87.6  
92.4  
100.0  
100.0  
100.0  
90  
93  
99  
418  
435  
444  
208/230---3---60  
460 --- 3 --- 60  
0.52  
5.9  
STD  
MED  
HIGH  
37.1  
38.5  
41.1  
45.0  
50.0  
50.0  
39  
41  
44  
236  
245  
249  
43.3  
44.7  
47.3  
50.0  
50.0  
60.0  
46  
48  
51  
248  
257  
261  
0.3  
0.24  
0.52  
0.3  
3.1  
2.4  
5.9  
3.1  
2.4  
5.9  
3.1  
2.4  
5.9  
3.1  
2.4  
STD  
MED  
HIGH  
27.9  
27.9  
30.7  
35.0  
35.0  
40.0  
29  
29  
33  
186  
186  
200  
32.7  
32.7  
35.5  
40.0  
40.0  
45.0  
35  
35  
38  
194  
194  
208  
575 --- 3 --- 60  
STD  
MED  
HIGH  
80.5  
85.3  
90.7  
100  
100  
100  
85  
90  
96  
445  
454  
464  
92.3  
97.1  
100  
110  
125  
98  
465  
474  
484  
104  
110  
208/230---3---60  
460 --- 3 --- 60  
102.5  
STD  
MED  
HIGH  
38.8  
41.4  
44.2  
50  
50  
50  
41  
44  
47  
247  
251  
256  
45  
50  
60  
60  
48  
51  
54  
259  
263  
268  
47.6  
50.4  
STD  
MED  
HIGH  
27.9  
30.7  
34.1  
35  
40  
40  
29  
33  
36  
188  
202  
200  
32.7  
35.5  
38.9  
40  
45  
45  
35  
38  
42  
196  
210  
208  
575 --- 3 --- 60  
0.24  
0.52  
0.3  
STD  
MED  
HIGH  
93.5  
98.9  
110.0  
125  
99  
549  
559  
633  
105.3  
110.7  
124.2  
125.0  
125  
112  
119  
133  
569  
579  
653  
105  
120  
208/230---3---60  
460 --- 3 --- 60  
112.4  
125  
150  
STD  
MED  
HIGH  
50.8  
53.6  
59.6  
60.0  
60  
54  
57  
64  
279  
284  
321  
57.0  
59.8  
65.8  
70.0  
70  
61  
64  
71  
291  
296  
333  
70  
80  
STD  
MED  
HIGH  
37.2  
40.6  
41.1  
45.0  
50  
39  
43  
44  
206  
204  
231  
42.0  
45.4  
45.9  
50.0  
50  
45  
49  
49  
214  
212  
239  
575 --- 3 --- 60  
0.24  
0.52  
0.3  
50  
50  
STD  
MED  
HIGH  
122.2  
127.6  
140.3  
150.0  
175  
127  
133  
148  
589  
599  
673  
134.0  
139.4  
152.1  
175.0  
175  
140  
147  
161  
609  
619  
693  
208/230---3---60  
460 --- 3 --- 60  
175  
200  
STD  
MED  
HIGH  
56.2  
59  
70.0  
70  
59  
62  
69  
305  
310  
347  
62.4  
65.2  
71.2  
80.0  
80  
66  
70  
76  
317  
322  
359  
65  
80  
80  
STD  
MED  
HIGH  
42.1  
45.5  
46  
50.0  
60  
44  
48  
49  
230  
228  
255  
46.9  
50.3  
50.8  
60.0  
60  
50  
54  
54  
238  
236  
263  
575 --- 3 --- 60  
0.24  
60  
60  
NOTE: See page 49 for table legend and notes.  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Legend and Notes for Table 11  
LEGEND:  
Example: Supply voltage is 230-3-60  
BRKR  
CO  
--- Circuit breaker  
AB = 224 v  
BC = 231 v  
AC = 226 v  
--- Convenience outlet  
--- Disconnect  
DISC  
FLA  
--- Full load amps  
LRA  
--- Locked rotor amps  
--- Minimum circuit amps  
--- Po w e r e x h a u st  
MCA  
(224 + 231 + 226)  
681  
3
Average Voltage =  
3
=
P E  
PWRD CO  
UNPWR CO  
NOTES:  
--- Powered convenient outlet  
--- Unpowered convenient outlet  
=
227  
Determine maximum deviation from average voltage.  
(AB) 227 – 224 = 3 v  
(BC) 231 – 227 = 4 v  
(AC) 227 – 226 = 1 v  
Maximum deviation is 4 v.  
1. In compliance with NEC requirements for multimotor and  
combination load equipment (refer to NEC Articles 430 and  
440), the overcurrent protective device for the unit shall be  
fuse or HACR breaker. Canadian units may be fuse or circuit  
breaker.  
Determine percent of voltage imbalance.  
2. Unbalanced 3-Phase Supply Voltage  
Never operate a motor where a phase imbalance in supply  
voltage is greater than 2%. Use the following formula to de-  
termine the percentage of voltage imbalance.  
4
% Voltage Imbalance  
= 100 x  
= 1.76%  
227  
max voltage deviation from average voltage  
This amount of phase imbalance is satisfactory as it is below the  
maximum allowable 2%.  
IMPORTANT: If the supply voltage phase imbalance is more than  
2%, contact your local electric utility company immediately.  
% Voltage Imbalance = 100 x  
average voltage  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Unit Without Economizer or  
2 Position Damper  
Economizer  
2 Position Damper  
Fig. 76 - EconoMi$ert IV Wiring  
C10645  
Two-Position motorized outside air damper  
EconoMi$er2 (without control/for external signal and  
integrated barometric relief)  
Step 13 — Adjust Factory--Installed Options  
EconoMi$er IV Occupancy Switch —  
Refer to Fig. 76 for general EconoMi$er IV wiring.  
External occupancy control is managed through a  
connection on the Central Terminal Board.  
EconoMi$er IV (with control and integrated barometric  
relief)  
Power Exhaust  
Differential dry-bulb sensor (EconoMi$er IV)  
Outdoor enthalpy sensor  
Differential enthalpy sensor  
CO2 sensor  
DDC interface (PremierLink)  
Louvered hail guard  
If external occupancy control is desired, connect a time  
clock or remotely controlled switch (closed for Occupied,  
open for Unoccupied sequence) at terminals marked  
OCCUPANCY on CTB. Remove or cut jumper JMP 2 to  
complete the installation.  
Step 14 — Install Accessories  
Available accessories include:  
Roof Curb  
Phase monitor control  
Winter Start kit  
Thru-base connection kit (must be installed before unit  
is set on curb)  
Refer to separate installation instructions for information  
on installing these accessories.  
LP conversion kit  
Pre-Start and Start-Up  
Manual outside air damper  
High Altitude Gas kits  
Low Ambient Controls  
Thermostat / Sensors  
This completes the mechanical installation of the unit.  
Refer to the unit’s Service and Maintenance manual for  
detailed Pre-Start and Start-up instructions.  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Catalog No: 48HC---11SI  
Copyright 2011 Carrier Corp. D 7310 W. Morris St. D Indianapolis, IN 46231  
Printed in U.S.A.  
Edition Date: 04/11  
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.  
Replaces: 48HC---08SI  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Black Box Network Card LBH1500A User Manual
Black Decker Fryer SKG110 User Manual
Black Decker Work Light 90515795 User Manual
Bowflex Home Gym 001 7057 User Manual
Briggs Stratton Computer Monitor 170700 User Manual
Briggs Stratton Pressure Washer 020239 1 User Manual
Canon Digital Camera 1000D User Manual
Capcom Video Games 2 User Manual
Chamberlain Garage Door Opener 1000SDC R, 2000SDC R User Manual
Chicago Electric Automobile Battery Charger 95000 User Manual