Carrier Air Conditioner 30RA RH User Manual

30RA/RH “B”  
30RY/RYH “B”  
PRO-DIALOG Control  
AQUASNAP  
Operation and maintenance instructions  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5 - PRO-DIALOG CONTROL OPERATION ............................................................................................................................29  
5.1 - Start/stop control ................................................................................................................................................................29  
5.2 - Heating/cooling operation ..................................................................................................................................................30  
5.2.1 - General .......................................................................................................................................................................30  
5.2.2 - Heating/cooling selection .......................................................................................................................................... 30  
5.3 - Evaporator water pump control .......................................................................................................................................... 31  
5.4 - Control interlock contact ....................................................................................................................................................31  
5.5 - Evaporator heater control ................................................................................................................................................... 31  
5.6 - Control point.......................................................................................................................................................................31  
5.6.1 - Active setpoint ...........................................................................................................................................................31  
5.6.2 - Reset........................................................................................................................................................................... 33  
5.7 - Demand limit ...................................................................................................................................................................... 33  
5.8 - Night mode ......................................................................................................................................................................... 33  
5.9 - Capacity control.................................................................................................................................................................. 33  
5.10 - Head pressure control .......................................................................................................................................................33  
5.11 - Defrost function ................................................................................................................................................................34  
5.12 - Additional electric heater stage control ............................................................................................................................34  
5.13 - Control of a boiler ............................................................................................................................................................34  
5.14 - Master/slave assembly ...................................................................................................................................................... 34  
5.15 - Controlling Pro-Dialog units with a System Manager .....................................................................................................34  
6 - DIAGNOSTICS - TROUBLESHOOTING ............................................................................................................................35  
6.1 - General ...............................................................................................................................................................................35  
6.2 - Displaying alarms ...............................................................................................................................................................35  
6.3 - Resetting alarms .................................................................................................................................................................35  
6.4 - Alarm codes ........................................................................................................................................................................35  
GENERAL LEGEND  
Each of the following drawings is replaced in the whole document by the corresponding explanation:  
Start/stop button  
Return key  
Down arrow  
Up arrow  
DELTA T. Example: temperature difference between entering and leaving heat exchanger temperatures  
means character is flashing  
The cover graphics are solely for illustration and forms no part of any offer for sale or any sale contract. The manufacturer  
reserves the right to change the design at any time without notice.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
1 - SAFETY CONSIDERATIONS  
1.1 - General  
2 - GENERAL DESCRIPTION  
2.1 - General  
Installation, start-up and servicing of equipment can be  
hazardous if certain factors particular to the installation are not  
considered: operating pressures, presence of electrical  
components and voltages and the installation site (elevated  
plinths and built-up up structures). Only properly qualified  
installation engineers and highly qualified installers and  
technicians, fully trained for the product, are authorised to  
install and start-up the equipment safely. During all servicing  
operations all instructions and recommendations which appear  
in the installation and service instructions for the product, as  
well as on tags and labels fixed to the equipment and  
Pro-Dialog is a system for controlling single or dual-circuit  
30RA/RY air-cooled liquid chillers or air-to-water 30RH/RYH  
heat pumps. Pro-Dialog controls compressor start-up needed to  
maintain the desired heat exchanger entering or leaving water  
temperature. In cooling mode it controls the operation of the fans  
to maintain the correct condensing pressure in each circuit. For  
heat pump units it controls and optimises the defrost cycles of  
each circuit in order to minimize the heating capacity  
reduction. Safety devices are constantly monitored by Pro-  
Dialog to ensure their safe operation. Pro-Dialog also gives  
access to a Quick Test program covering all inputs and outputs.  
components and accompanying parts supplied separately, must  
be read, understood and followed.  
All PRO-DIALOG controls can work in accordance with three  
independent modes:  
Apply all standard safety codes and practices.  
Wear safety glasses and gloves.  
Use the proper tools to move heavy objects. Move units  
carefully and set them down gently.  
Local mode: the machine is controlled by commands from  
the user interface.  
Remote mode: the machine is controlled by remote  
contacts (volt-free contacts).  
CCN mode: the machine is controlled by commands from  
the Carrier Comfort Network (CCN). In this case, a data  
communication cable is used to connect the unit to the  
CCN communication bus.  
1.2 - Avoid electrocution  
Only personnel qualified in accordance with IEC (International  
Electrotechnical Commission) recommendations may be  
permitted access to electrical components. It is particularly  
recommended that all sources of electricity to the unit be shut  
off before any work is begun. Shut off the main power supply  
at the main circuit breaker or isolator.  
The operating mode must be chosen with the Start/Stop button  
described in section 4.2.1. When the PRO-DIALOG system  
operates autonomously (Local or Remote mode) it retains all of  
its own control capabilities but does not offer any of the  
features of the CCN network.  
IMPORTANT: This equipment uses and emits  
electromagnetic signals. Tests have shown that the equipment  
conforms to all applicable codes with respect to  
electromagnetic compatibility.  
2.2 - Abbreviations used  
In this manual, the refrigeration circuits are called circuit A and  
circuit B. The compressors in circuit A are labelled A1, A2 and  
A3. Those in circuit B are B1, B2 and B3.  
RISK OF ELECTROCUTION: Even when the main circuit  
breaker or isolator is switched off, certain circuits may still  
be energised, since they may be connected to a separate power  
source.  
The following abbreviations are used frequently:  
CCN : Carrier Comfort Network  
RISK OF BURNS: Electrical currents cause components to  
get hot either temporarily or permanently. Handle power  
cable, electrical cables and conduits, terminal box covers and  
motor frames with great care.  
CCn : Operating type: CCN  
LED : Light Emitting Diode  
LOFF : Operating type: Local Off  
L-On : Operating type: Local On mode  
L-Sc : Operating type: Local On following a time schedule  
MASt : Operating type: master unit (master/slave assembly)  
rEM : Operating type: by remote contacts  
SCT : Saturated Condensing Temperature  
SIO : Sensor Bus (internal communication bus linking the  
basic board to the slave boards)  
Fanstart-up:  
ATTENTION: In accordance with the operating conditions  
the fans can be cleaned periodically. A fan can start at any  
time, even if the unit has been shut down.  
SST : Saturated Suction Temperature  
TXV : Thermal Expansion Valve  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
3 - HARDWARE DESCRIPTION  
3.1 - General  
3.2 - Electrical supply to boards  
All boards, except the PD-RCPM board, are supplied from a  
common 24 V a.c. supply referred to earth.  
Figure 1  
CAUTION: Maintain the correct polarity when connecting  
the power supply to the boards, otherwise the boards may be  
damaged.  
4
1
3
2
In the event of a power supply interrupt, the unit restarts  
automatically without the need for an external command.  
However, any faults active when the supply is interrupted are  
saved and may in certain cases prevent a circuit or unit from  
restarting.  
9
3
3.3 - Light emitting diodes on boards  
All boards continuously check and indicate the proper  
operation of their electronic circuits. A light emitting diode  
(LED) lights on each board when it is operating properly.  
The red LED flashing for a 2 second period on the NRCP-  
BASE board indicates correct operation. A different rate  
indicates a board or a software failure.  
On dual-circuit units or units equipped with optional  
board, the green LED flashes continuously on all boards  
to show that the board is communicating correctly over its  
internal bus. If the LED is not flashing, this indicates a  
SIO bus wiring problem.  
10  
7
5
8
6
Legend  
1
2
3
4
5
6
7
8
9
CCN connector  
Red LED, status of the board  
Green LED, communication bus SIO  
Orange LED, communication bus CCN  
Remote master board customer control connection contacts  
Remote slave board customer control connection contacts  
Master board customer connection relay outputs  
Slave board customer connection relay outputs  
Master NRCP basic board  
The orange LED of the master board flashes during any  
communication via the CCN bus.  
3.4 - The sensors  
Pressure sensors  
10 Slave NRCP basic board  
Two types of electronic sensors are used to measure the suction  
and discharge pressure in each circuit.  
The control system consists of an NRCP-BASE board for  
single-circuit units and two NRCP-BASE boards (a master and  
a slave board) for dual-circuit units. Heat pump units equipped  
with optional additional heater stages use an additional board,  
type PD-AUX. All boards communicate via an internal SIO bus.  
The NRCP-BASE boards continuously manage the information  
received from the various pressure and temperature probes. The  
NRCP-BASE master board incorporates the program that  
controls the unit.  
Thermistors  
The evaporator water sensors are installed in the entering and  
leaving side. The outdoor temperature sensor is mounted below  
the control box. An optional water system temperature sensor  
can be used for master/slave assembly control (in the case of  
leaving water control).  
In heat pump units a sensor placed on an air heat exchanger  
pipe ensures defrost operation.  
The user interface consists of two display blocks with up to 26  
LEDs and 16 buttons (according to unit type). It is connected  
to the main basic board and gives access to a full array of  
control parameters.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.5 - The controls  
3.6 - Connections at the user's terminal block  
Evaporator pumps  
3.6.1 - General description  
The controller can regulate one or two evaporator pumps and  
takes care of automatic change-over between pumps.  
The contacts below are available at the user's terminal block on  
the NRCP-BASE board (see figure 1). Some of them can only  
be used if the unit operates in remote operating type (rEM).  
The following table summarises the connections at the user’s  
terminal block.  
Evaporator heater  
It protects the evaporator (and the pipe heater for units without  
pump) against freezing if the unit is off.  
Boiler  
This relay output authorises start/stop of a boiler.  
Condensate defrost heater  
This heater is used for heat pump units and is located at the  
bottom of the air heat exchanger of each circuit. It prevents ice  
build-up, if defrost cycles are initiated at low outdoor  
temperatures.  
SINGLE-CIRCUIT UNITS  
Description  
Connector/channel  
J3 / CH24  
Terminal  
30 - 31  
Board  
Remarks  
Remarks  
Alarm relay output  
Boiler relay output  
NRCP-BASE  
NRCP-BASE  
Indicates alarms  
Volt-free contact 24 V a.c.  
48 V d.c. max, 20 V a.c. or  
V d.c., 3 A max, 80 mA min,  
external power supply.  
J3 / CH25  
37 - 38  
Boiler start/stop control output.  
See section 5.13.  
Connector: 4 pin  
WAGO 734-104 pitch 3.5.  
One per board needed.  
Contact 1:  
start/stop/heat/cool  
J4 / CH8  
J4 / CH9  
32 - 33  
63 - 64  
NRCP-BASE  
NRCP-BASE  
The contacts are used for unit start/stop and  
heat/cool control. They are only taken into  
account if the unit is under remote operation  
control (rEM).  
24 V a.c., 20 mA  
Connector: 8 pin WAGO  
734-168, pitch 3.5  
Contact 2:  
start/stop/heat/cool  
See the description of these contacts in  
sections 3.6.2 and 3.6.3.  
Contact 3:  
demand limit selection or  
setpoint selection  
J4 / CH10  
73 - 74  
NRCP-BASE  
Depending on the configuration, this dry  
contact can be used for remote setpoint  
selection or demand limit selection (see  
sections 4.3.11.3 and 3.6.4).  
- The remote setpoint selection contact is  
only taken into account if the unit is in  
remote control operating type.  
- The remote demand limit selection contact  
is active whatever the operating type of the  
unit.  
User safety loop input  
Connection to CCN  
J4 / CH11a  
34 - 35  
NRCP-BASE  
NRCP-BASE  
This contact is mounted in series with the  
water flow control contact. It can be used for  
any customer safety loop that requires that  
the unit is stopped, if it is open.  
If it is unused this contact must be bridged.  
J12  
1 - 2 - 3  
An RS-485 bus is used for connection to the  
CCN.  
Connector: 3 pin WAGO  
231-303, pitch 5.08  
- Pin 1: signal +  
- Pin 2: ground  
- Pin 3: signal -  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
DUAL-CIRCUIT UNITS  
Description  
Connector/channel  
Terminal  
Board  
Remarks  
Remarks  
Alarm relay output  
circuit A  
J3 / CH24  
30A - 31A  
Master NRCP- Indicates alarms/alerts for circuit A*  
BASE  
Volt-free contact 24 V a.c.  
48 V d.c. max, 20 V a.c. or  
V d.c., 3 A max, 80 mA min,  
external power supply.  
Alarm relay output  
circuit B  
J3 / CH24  
J3 / CH25  
30B - 31B  
37 - 38  
Slave NRCP-  
BASE  
Indicates alarms/alerts for circuit B*  
Boiler relay output  
Master NRCP- Boiler start/stop control output.  
BASE See section 5.13.  
Connector: 4 pin  
WAGO 734-104 pitch 3.5.  
One per board needed.  
Contact 1:  
start/stop/heat/cool  
J4 / CH8  
J4 / CH9  
32 - 33  
63 - 64  
Master NRCP- The contacts are used for unit start/stop and  
24 V a.c., 20 mA  
BASE  
heat/cool control. They are only taken into  
account if the unit is under remote operation  
Connector: 8 pin WAGO  
734-168, pitch 3.5  
Contact 2:  
start/stop/heat/cool  
Master NRCP- control (rEM).  
BASE  
See the description of these contacts in  
sections 3.6.2 and 3.6.3.  
Contact 3:  
demand limit selection  
J4 / CH10  
J4 / CH10  
J4 / CH8  
73 - 74  
75 - 76  
65 - 66  
Master NRCP- These dry contacts are used for demand  
BASE  
limit selection. See description of these  
contacts in section 3.6.5.  
Contact 4:  
demand limit selection  
Slave  
NRCP-BASE  
The remote demand limit selection contact is  
active whatever the operating type of the  
unit.  
Contact 5:  
setpoint selection  
Slave  
NRCP-BASE  
These dry contacts are used for setpoint  
selection.  
They are only taken into account if the unit is  
in remote control operating type (rEM).  
Control contact 6:  
setpoint selection  
J4 / CH9  
67 - 68  
34 - 35  
Slave  
NRCP-BASE  
See the description of these contacts in  
sections 3.6.6.  
User safety loop input  
J4 / CH11a  
Master  
NRCP-BASE  
This contact is mounted in series with the  
water flow control contact. It can be used for  
any customer safety loop that requires that  
the unit is stopped, if it is open.  
If it is unused this contact must be bridged.  
Connection to CCN  
J12  
1 - 2 - 3  
Master  
NRCP-BASE  
An RS-485 bus is used for connection to the  
CCN.  
- Pin 1: signal +  
- Pin 2: ground  
- Pin 3: signal -  
Connector: 3 pin WAGO  
231-303, pitch 5.08  
*
The operation of these relays can vary depending on the user configuration. See section ‘Description of the User 2 configuration sub-menu’.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.6.2 - Volt-free contact on/off/cooling/heating without  
multiplexing  
If the automatic heating/cooling changeover function is not  
selected (see sections 4.3.11.3, 5.1 and 5.2) the operation of  
contacts 1 and 2 is as follows:  
3.6.5 - Demand limit volt-free contact for dual-circuit units  
On dual-circuit units the operation of the demand limit  
selection contacts is multiplexed. The demand limit setpoints are  
adjustable in the setpoint menu (see section 4.3.8).  
100%  
Limit 1  
Limit 2  
Limit 3  
(no limit)  
OFF  
Open  
-
ON cooling  
Closed  
ON heating  
Closed  
Contact 3 Open  
Contact 4 Open  
Closed  
Open  
Open  
Closed  
Closed  
Contact 1  
Contact 2  
Closed  
Open  
Closed  
Contact status not significant  
3.6.6 - Water setpoint selection volt-free contact with  
multiplexing for dual-circuit units  
3.6.3 - Volt-free contact on/off/cooling/heating with  
multiplexing  
If the automatic heating/cooling changeover function is  
selected (see sections 4.3.11.3, 5.1 and 5.2) the operation of  
contacts 1 and 2 is multiplexed:  
On dual-circuit units the operation of the cold water or hot  
water setpoint selection contacts is multiplexed. The set-points  
are adjustable in the setpoint menu (see section 4.3.8). Auto  
means that the active setpoint is determined by the setpoint  
schedule (see section 5.6.1).  
OFF  
Contact 1 Open  
Contact 2 Open  
ON cooling  
Closed  
ON heating  
Closed  
ON auto  
Open  
Cooling mode  
Open  
Closed  
Closed  
Setpoint 1  
Setpoint 2  
Setpoint 3  
Auto  
Contact 5  
Contact 6  
Open  
Open  
Open  
Closed  
Closed  
Open  
Closed  
Closed  
NOTE: The automatic changeover function (ON auto) selects  
the cooling or heating mode based on the outdoor  
temperature (see section 5.2).  
Heating mode  
Setpoint 1  
Setpoint 2  
Setpoint 3  
Auto  
Contact 5  
Contact 6  
Open  
Open  
Open  
Closed  
Closed  
Open  
Closed  
Closed  
3.6.4 - Demand limit or setpoint volt-free contact for single-  
circuit units  
On single-circuit units contact 3 determines the selection of  
demand limit or setpoint, based on the configuration (see User  
Configuration 1 menu).  
Demand limit selection  
Setpoint selection  
100%  
Limit 1  
Setpoint 1  
Setpoint 2  
(no limit)  
Contact 3 Open  
Closed  
Open  
Closed  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
4 - SETTING UP PRO-DIALOG CONTROL  
4.1 - Local interface general features  
MAIN INTERFACE  
SUMMARY INTERFACE  
PRO-DIALOG JUNIOR INTERFACE  
PRO-DIALOG PLUS INTERFACE  
MENU BLOCK  
The local interface enables a number of operating parameters to  
be displayed and modified.  
A two-digit display showing the number of the item  
selected.  
A four-digit display showing the contents of the item  
selected.  
LEDs and buttons for unit start/stop, menu selection,  
menu item selection and value adjustment.  
The interface consists of two distinct parts: the main interface  
(left-hand section) and the summary interface (right-hand section).  
Main interface  
It gives access to all PRO-DIALOG data and operating functions. PRO-DIALOG Junior interface: On some units the local user  
It consists of:  
interface consists only of a simplified main interface (left-hand  
section) that is identical to the main interface described below,  
but does not include the menu block diodes.  
MAIN INTERFACE  
BUTTON  
NAME  
DESCRIPTION  
Menu  
Permits the selection of a main menu. Each main menu is represented by an icon. The icon is lit if active.  
Up arrow  
Down arrow  
Enter  
Permits scrolling through the menu items (in the two-digit display). If the modification mode is active this button authorises  
increase of the value of any parameter.  
Permits scrolling through the menu items (in the two-digit display). If the modification mode is active this button authorises  
decrease of the value of any parameter.  
Gives access to the modification mode, validates a modification or displays expanded item description.  
Start/stop  
Authorises start or stop of the chiller in local mode or modification of its operating type.  
MAIN INTERFACE MENU LED'S  
LED*  
NAME  
DESCRIPTION  
INTERFACE DISLAY  
INFORMATION menu  
Displays the general operating parameters for the unit.  
Information  
TEMPERATURES menu  
PRESSURES menu  
Displays the unit operating temperatures.  
Displays the unit operating pressures.  
Temperatures  
Pressures  
kPa  
SETPOINTS menu  
INPUTS menu  
Displays the unit setpoints and enables them to be modified.  
Displays the status of the unit digital and analogue inputs.  
Setpoints  
Inputs  
OUTPUTS/TESTS menu  
Displays the status of the unit outputs and enables them to be tested.  
Outputs  
CONFIGURATIONS menu  
ALARMS menu  
Displays the unit configuration and enables it to be modified.  
Displays active alarms.  
Confguration  
Alarms  
ALARMS HISTORY menu  
Displays the history of the alarms.  
History  
RUNTIMES menu  
Displays the operating times and number of starts for the unit and the  
compressors.  
Runtimes  
* Not available on the PRO-DIALOG Junior interface.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
The summary interface (right hand section) includes a mimic  
diagram of the unit, together with push-buttons and LEDs. It  
gives quick access to the main operating parameters of the unit.  
The following operating types can be selected using the  
Start/Stop button:  
OPERATING TYPES  
4 DIGIT DISPLAY  
LOFF  
DESCRIPTION  
SUMMARY INTERFACE LEDs*  
Local Off. The unit is halted in local mode.  
LED  
INDICATION WHEN LIT  
L-On  
Local On. The unit is in local control mode and is  
authorised to start.  
Green LED:  
The unit is authorised to start or is already running  
L-Sc*  
Local On - timer control. The unit is in local control  
mode. It is authorised to start if the period is occupied.  
If the timer program for unit operation is unoccupied,  
the unit remains shut down until the period becomes  
occupied.  
Red LED:  
- Lit: circuit A or unit shut down by alarm  
- Flashing: circuit A or unit running with alarm present  
Red LED:  
CCN*  
rEM*  
CCN. The unit is controlled by CCN commands.  
- Lit: circuit B or unit shut down by alarm  
- Flashing: circuit B or unit running with alarm present  
Remote. The unit is controlled by remote control  
contacts.  
Red LED:  
Water flow switch default or user safety lock open.  
MAST*  
Master Unit. The unit runs as a master in a two unit  
lead/lag arrangement.This is displayed if the unit is  
configured for master/slave control.  
Green LED:  
The evaporator pump is running.  
Legend  
Yellow LEDs:  
*
Displayed if the configuration requires it.  
From top to bottom - start/stop status of compressor A1, A2 and A3  
or B1, B2 and B3. Flashing LED indicates that the circuit is in the  
protection or defrost mode (A or B).  
Section 5.1 gives a more detailed description of the commands to start/stop  
the unit, analysed by operating type.  
Green LED:  
The unit operates in heating mode.  
4.2.2 - Stopping the unit in local mode  
The unit can be stopped in local mode at any time by pressing  
the Start/Stop button.  
Green LED:  
The unit operates in cooling mode.  
* Not available on the PRO-DIALOG Junior interface.  
TO STOP THE UNIT  
SUMMARY INTERFACE PUSH BUTTONS*  
BUTTON DISPLAY  
BUTTON  
ACTION  
2-DIGIT DISPLAY 4-DIGIT DISPLAY  
Press the Start/Stop  
button for less than  
4 seconds (one short  
press is enough).  
C
t
LOFF  
LOFF  
Blue button: evaporator leaving or entering water temperature in °C  
Gray button: outdoor air temperature in °C  
Control point (setpoint + reset) in °C  
If the button is  
released, the unit stops  
without the need for  
further action.  
Press 1: circuit A/B discharge pressure in kPa  
Press 2: circuit A/B saturated condensing temperature in °C  
4.2.3 - Starting unit and selecting an operating type  
The unit can be started in local mode, or unit operating type  
can be changed at any time using the Start/Stop button. In the  
example that follows, the unit is stopped (LOFF) and the user  
wants to start the unit in local mode.  
Press 1: circuit A/B suction pressure in kPa  
Press 2: circuit A/B saturated suction temperature in °C  
Press 1: compressor A1/B1 operating hours in h/10 or h/100  
Press 2: compressor A2/B2 operating hours in h/10 or h/100  
Press 3: compressor A3/B3 operating hours in h/10 or h/100  
* Not available on the PRO-DIALOG Junior interface.  
START UP WITH THE PREVIOUSLY USED OPERATING TYPE WHEN THE UNIT  
IS STOPPED IN LOCAL MODE (LOFF)  
4.2 - Unit start/stop control  
BUTTON ACTION  
2-DIGIT  
4-DIGIT  
DISPLAY  
LOFF  
DISPLAY  
4.2.1 - Description  
The unit start/stop can be controlled by one of the following  
methods:  
The unit is in local stop mode. The  
previously used operating type is local on  
(L-ON)  
Press the Start/Stop button for 4 seconds  
(one short press-down is sufficient). L-ON  
illuminates immediately. "C" flashes in the  
2-digit display to show that the controller is  
awaiting confirmation.  
L-On  
L-On  
Locally on the actual unit (Local control type)  
By remote control with the aid of user contacts (remote  
control type)  
By CCN control with the aid of the CCN (CCN control  
type)  
Press the Enter button to confirm the  
operating type. "t" is displayed in the 2-digit  
display to indicate the operating type  
selected. If the Enter button is not pressed  
soon enough, the controller will cancel the  
change and remain in the stop mode.  
t
The main interface includes a Start/Stop button which can be  
used to stop or start the unit in the local operating type or to  
select the remote or CCN operating type.  
The available operating types are described in the following  
table.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CHANGING THE OPERATING TYPE  
BUTTON ACTION  
4.3.3 - Modifying the value of a parameter/access to a sub-  
menu  
2-DIGIT  
DISPLAY  
C
4-DIGIT  
DISPLAY  
LOFF  
Press the Enter button for more than 2 seconds to enter the  
modification mode or to select a sub-menu. This lets you correct  
the value of an item or select a sub-menu with the aid of the up  
and down Arrow buttons (if you are authorised to overwrite the  
item concerned). When modification mode is activated, the LED  
for the main menu to which the item belongs as well as the 2-  
digit display flash in the menu block. Once the required value is  
obtained, press the Enter button again to validate the change or  
to access the sub-menu. The LED for the menu to which the  
item and the 2-digit display belong then stops flashing,  
indicating that modification mode no longer applies.  
Continually press the operating type  
selection button for more than 4 seconds.  
Hold down the Start/Stop button.  
The available operating types are displayed  
one by one until the button is released.  
L-On  
L-Sc  
rEM  
Release the Start/Stop button if the  
operating type you want is displayed (in this  
example L-On). "C" flashes in the 2-digit  
display to show that the controller is  
awaiting confirmation.  
L-On  
Press the Enter button to confirm the  
t
L-On  
In modification mode, the value to be modified increases or  
decreases in steps of 0.1 every time you press the Arrow  
buttons. Holding one of these buttons down increases the rate  
of increase or decrease.  
operating type selected (in this example:  
L-On). "t" is displayed in the 2-digit display  
to indicate the operating type selected. If the  
Enter button is not pressed soon enough,  
the controller will cancel the change and  
continue to use the previous operating type.  
NOTE: The access to a sub-menu may require entering a  
password. This is automatically requested. See section  
4.3.11.2.  
4.3 - Menus  
4.3.1 - Selecting a menu  
The following example shows how to modify the value of item  
1 in the Setpoint menu.  
The MENU button authorises you to select a menu from the 10  
main menus that are available. Each time you press this button  
one of the 10 LEDs lights up in turn alongside each of the  
icons representing a main menu. The active menu is the one  
against which the LED is lit. If a menu is empty then its LED is  
not lit. To scroll quickly through the menus, hold the MENU  
button down.  
4.3.2 - Selecting a menu item  
The up and down Arrow buttons let you scroll through the  
menu items. Menu item numbers are displayed in the two-digit  
display. The item number increases or decreases every time you  
press the up or down Arrow button. The menu items that are not  
in use or incompatible with the configuration are not displayed.  
The value or status associated with the active item is displayed  
in the four-digit display. To scroll quickly through the items,  
hold the up or down Arrow button down.  
The following example shows how to access item 3 in the  
Pressures menu.  
SELECTING A MENU ITEM  
OPERATION  
PRESS  
BUTTON  
MENU LED  
ITEM NUMBER  
2-DIGIT  
DISPLAY  
Press the MENU button until the  
LED marked PRESSURE lights.  
0
Note: On the PRO-DIALOG Junior  
interface the menu LEDs are not  
available. Instead, each time the  
menu button is pressed, the name  
of the active menu is dsplayed in  
the 4-digit display. In this example,  
press the MENU button until  
PRESSURE is displayed in the  
4-digit display.  
kPa  
Press one of the Arrow buttons  
until the two-digit display shows 3  
(item number 3).  
1
2
3
kPa  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.3.4 - Expand display  
Pressing the Enter button causes a 23 character text expansion to  
be scrolled across the four-digit display. All user menus  
provide an expansion of the current displayed parameters. If  
the expansion is complete the four-digit display reverts to item  
value. This function can be inhibited through the User  
Configuration menu.  
MODIFYING THE VALUE OF A PARAMETER  
OPERATION  
PRESS BUTTON  
MENU LED  
ITEM NUMBER  
ITEM VALUE  
2-DIGIT DISPLAY  
4-DIGIT DISPLAY  
0
Hold on the MENU button until the LED for SETPOINT lights.  
PRO-DIALOG Junior interface: Press the menu button, until SETPOINTS is  
displayed in the 4-digit display  
0
1
SEtPoint  
Press one of the Arrow buttons until the two-digit display shows 1  
(item number 1- cooling setpoint 2).  
The value for setpoint 2 is displayed in the four-digit display (6.0°C in this  
example).  
1
6.0  
6.0  
Press the Enter button for more than 2 seconds to enable the value associated  
with item 1 to be modified.  
The Setpoint menu LED and the two-digit display flash indicating that modification  
mode is active.  
1
5.9  
5.8  
Keep pressing the Down Arrow button until the value 5.7 is displayed in the four-  
digit display. The Setpoint menu LED and the two-digit display keep flashing.  
1
1
1
5.7  
5.7  
1
Press the Enter button again to validate the change.The new setpoint is 5.7°C.  
The Setpoint menu LED and the two-digit display stop flashing, indicating that  
modification mode no longer applies.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MENU STRUCTURE  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Menu tree structure  
MENU  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.3.5 - Description of the Information menu  
INFORMATION MENU (3)  
ITEM FORMAT  
UNITS DESCRIPTION  
Automatic display mode. It cycles through the following displays:  
0
±nn.n  
°C  
1:  
2:  
Controlled water temperature: temperature of the water that the unit tries to maintain at the control point.  
Unit operating type  
LOFF  
L-On  
L-Sc  
CCn  
rEM  
-
-
-
-
-
-
Local Off  
Local On  
Local On - based on unit clock. Displayed if the CCN/clock board is installed.  
CCN Control. Displayed if the CCN/clock board is installed.  
Remote Control  
Master unit  
MASt  
3:  
Unit status  
OFF  
rEADY  
dELAY  
-
-
-
Off: Unit is stopped and not authorised to start.  
Ready: Unit is authorised to start  
Delay: Unit is in delay at start-up.This delay is active after the unit has been switched on. The delay can be  
configured in the User Configuration menu.  
Stopping: Unit is currently stopping.  
On: Unit is running or authorised to start.  
Fault shutdown.  
Limit: The operating conditions do not allow total unit operation.  
Defrost: One circuit is in defrost mode.  
StOPPing  
running  
triPout  
OvErridE  
dEFrOSt  
-
-
-
-
-
4.  
5.  
Unit occupied/unoccupied status  
Occupied: Unit in occupied mode  
Unoccupied: Unit in unoccupied mode  
OCCUPIEd  
UNOCCUPIEd -  
-
Heating/cooling operating mode  
COOL  
HEAT  
StAndbY  
BotH  
-
-
-
-
Cooling: Unit operates in cooling mode  
Heating: Unit operates in heating mode  
Standby: Unit is in auto cooling/heating changeover mode, and is in standby  
Both: The unit operates in cooling (compressors) and heating (boiler). Only with HSM operation.  
ALArM  
ALErt  
-
-
6:  
7:  
Alarm mode  
Alarm: Unit is totally stopped because of failure.  
Alert: Unit is in failure but not completely stopped.  
Master/Slave status  
MAStEr  
SLAvE  
-
-
Master:The master/slave control is active and the unit is the master  
Slave: The master/slave control is active and the unit is the slave  
1 [1]  
2 [2]  
nn  
Active mode codes. Each active mode is displayed in turn. This Item is masked when nil. Pressing the enter button when a mode  
code is displayed causes a character text expansion to be scrolled accross the four-digit display. See the description in the following  
table  
-
-
This item indicates the current unit occupied/unoccupied mode. Displayed if the CCN/clock board is installed.  
occu  
unoc  
Forc  
Occupied  
Unoccupied  
The value is displayed in turn with 'Forc' when the unit is in CCN control and if this variable if forced through CCN.  
3
nn.n  
minutes Start-up delay. This item indicates the minutes left before the unit can be started. This delay at start-up is always active after the unit  
has been switched on.The delay can be configured in the User Configuration 1 menu.  
4 [2]  
-
Heating/cooling on selection: This item is accessible in read/write, if the unit is in local control mode. It is only displayed, if the unit is  
in LOFF, L-On or L-Sc operating type. Displayed for heat pumps or if the unit controls a boiler.  
HEAt  
COOL  
Auto  
-
-
-
Heating mode selection  
Cooling mode selection  
Automatic heating/cooling mode changeover selection. Only displayed if the auto changeover function is selected (User Configuration  
1 menu).  
5 [2]  
Heating/cooling mode. This item indicates whether the unit is in cooling or heating. Displayed if the unit controls a boiler.  
HEAt  
COOL  
StbY  
both  
-
-
-
-
-
Heating  
Cooling  
Standby: Unit is in auto cooling/heating changeover mode, and is in standby.  
Both:The unit operates in cooling (compressors) and heating (boiler). Only with HSM operation.  
The value is displayed in turn with 'Forc' when the unit is in CCN control and if this variable if forced through CCN.  
Forc  
6
nnn  
nnn  
nnn  
nnn  
%
%
%
%
Total active capacity of unit. It is the percentage of compressor capacity used by the unit.  
7
Total active capacity of circuit A. It is the percentage of compressor capacity used by on circuit A..  
Total active capacity of circuit B. It is the percentage of compressor capacity used by on circuit B. Dual-circuit units only.  
Active electric heating stages. Only displayed for heat pumps and if the unit controls additional electric heating stages.  
8 [2]  
9 [2]  
10  
nnn  
Present demand limit. This is the authorised operating capacity of the unit. See section 5.7.  
Forc  
%
%
-
The value is displayed in turn with 'Forc' when the unit is in CCN control and if this variable if forced through CCN.  
11 [2] nnn  
Present lag chiller demand limit. Displayed when the master/slave control is selected.  
12 [2]  
Setpoint select in local mode. This point is read/write accessible. Displayed only when the unit is LOFF, L-On or L-Sc operating type.  
SP-1  
SP-1 = cooling/heating setpoint 1  
SP-2  
SP-3  
AUtO  
SP-2 = cooling/heating setpoint 2  
SP-3 = heating setpoint 3  
AUtO = active setpoint depends on schedule 2 (setpoint selection schedule). See section 5.6.1 & 4.3.11.6.  
13 [2]  
-
Setpoint occupied mode. Displayed if the CCN/clock board is installed.  
Occupied: cooling setpoint 1 is active  
Unoccupied: cooling setpoint 2 is active  
occu  
unoc  
Forc  
The value shall be displayed in turn with 'Forc' when the unit is in CCN control and if this variable if forced through CCN.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INFORMATION MENU (3) continued  
ITEM  
FORMAT UNITS  
DESCRIPTION  
14  
±nn.n  
°C  
°C  
°C  
Active setpoint. This is the current cooling/heating setpoint: it refers to cooling setpoint 1 or cooling/heating setpoint 2. See section  
5.6.1.  
15  
±nn.n  
Forc  
Control point. This is the setpoint used by the controller to adjust the temperature of the leaving or entering water (according to  
configuration).  
Control point = active setpoint + reset. See section 5.6  
The value is displayed in turn with 'Forc' when the unit is in CCN control and if this variable if forced through CCN.  
16  
±nn.n  
Controlled water temperature. Water temperature that the unit tries to maintain at the control point.  
1
2
3
This item is masked when nil.  
This item is displayed in certain unit configurations only.  
Access to this menu is read-only except for item 10 that can be forced when the unit is in Local operating type.  
DESCRIPTION OF OPERATING MODES (ITEM 1 OF THE INFORMATION MENU)  
MODE # MODE NAME  
DESCRIPTION  
1
Delay at start-up active  
The delay at start-up operates after the unit has been switched on. If the delay has not expired, the mode is  
active. The delay is configured in the User Configuration 1 menu.  
2
3
4
5
2nd cooling/heating setpoint active  
3rd heating setpoint active  
Setpoint reset active  
The second cooling/heating setpoint is active. See section 5.6.1  
The third heating setpoint is active. See section 5.6.1  
In this mode, the unit uses the reset function to adjust the leaving water temperature setpoint. See section 5.6.  
Auto heating/cooling changeover  
active  
If the unit is in auto mode, the heating/cooling changeover is automatic, based on the outdoor temperature. See  
section 5.2.  
6
7
Demand limit active  
Ramp loading active  
In this mode, the demand at which the unit is authorised to operate is limited. See section 5.7.  
Ramp loading is active. In this mode, the rate of water temperature drop or rise (heating mode) in °C/min is limited  
to a preset value in order to prevent compressor overloading. Ramp function must be configured (see User  
Configuration 1 menu). Ramp values can be modified (see Setpoint menu).  
8
Water or air heat exchanger  
heater active  
The water or air heat exchanger heater is active. See section 5.5.  
9
Evaporator pump reversal in effect  
Evaporator pump periodic start  
The unit is fitted with two evaporator water pumps and reversal between pumps is in effect. See section 5.3.  
10  
The unit is stopped and the pump is started each day at 14.00 p.m. for two seconds. This function needs to be  
configured in the User Configuration 1 menu. See section 5.3 & 4.3.11.3.  
11  
Night condensing mode  
The night mode is active. Fan runs at low speed (if permitted by operating conditions) and unit capacity can be  
limited. See section 5.8 & 4.3.11.3.  
12, 13  
14, 15  
Low suction temperature protection  
High pressure protection  
12 = circuit A & 13 = circuit B. Protection for evaporator low suction temperature circuit is active. In this mode,  
circuit capacity is not authorised to rise and the circuit can be unloaded.  
14 = circuit A & 15 = circuit B.The unit is in cooling or heating mode.The circuit is in high pressure protection  
mode because the HP protection threshold has been exceeded. Circuit has been unloaded and the circuit  
capacity is not authorised to rise.  
16, 17  
18  
Defrost  
16 = circuit A & 17 = circuit B. The unit is in heating mode, and the defrost sequence is active on the relevant  
circuit.  
Low water entering temperature  
protection in heating mode  
The unit is in heating mode and compressor start is not authorised, as the entering water temperature is below  
10°C.  
19, 20  
21, 22  
Hot gas protection in heating mode  
19 = circuit A & 20 = circuit B.The unit is in heating protection mode and hot gas discharge protection is active. In  
this mode, the circuit capacity cannot increase, and the circuit may be unloaded or go into defrost mode.  
Low suction temperature protection  
in heating mode  
21 = circuit A & 22 = circuit B. The unit is in heating mode and low suction temperature protection is active. In this  
mode, circuit capacity is not authorised to rise and the circuit can be unloaded or go into defrost mode.  
23  
24  
25  
26  
27  
Boiler active  
The unit controls a boiler and this is operating. See section 5.13.  
Electric heating stages active  
Unit in SM control  
The unit controls additional electric heating stages, and these are operating. See section 5.12.  
Unit is in control of a System Manager (FSM, CSM III or HSM).  
Master/slave link active  
Low outside temperature protection  
Unit is connected to a secondary unit by a master slave link and the master/slave modes are active.  
The unit is in heating mode, and compressor start-up is not permitted, when the outside air temperature is lower  
than the value configured in item 12 of the User 1 configuration menu. See the relevant section.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.3.6 - Description of the Temperatures menu  
4.3.7 - Description of the Pressures menu  
TEMPERATURES MENU [2]  
PRESSURES MENU [2]  
ITEM FORMAT UNITS COMMENTS  
ITEM  
FORMAT UNITS  
COMMENTS  
0
±nn.n  
°C  
Water heat exchanger entering water tempera-  
ture  
0
nnnn  
kPa  
kPa  
kPa  
kPa  
Discharge pressure, circuit A.  
Relative pressure.  
1
±nn.n  
°C  
Water heat exchanger leaving water tempera-  
ture  
1
nnn  
Suction pressure, circuit A.  
Relative pressure.  
2
±nn.n  
±nn.n  
±nn.n  
±nn.n  
±nn.n  
±nn.n  
±nn.n  
±nn.n  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
°C  
Outdoor temperature  
2 [1]  
3 [1]  
nnnn  
nnn  
Discharge pressure, circuit B.  
Relative pressure.  
3
Saturated discharge temperature, circuit A  
Saturated suction temperature, circuit A  
Saturated discharge temperature, circuit B  
Saturated suction temperature, circuit B  
Defrost temperature, circuit A  
Suction pressure, circuit B.  
Relative pressure.  
4
5 [1]  
6 [1]  
7 [1]  
8 [1]  
9 [1]  
1
2
This item is displayed in certain unit configurations only.  
Access to this menu is read-only  
Defrost temperature, circuit B  
Chilled water system temperature. Used for  
master/slave control.  
1
2
This item is displayed in certain unit configurations only  
Access to this menu is read-only.  
4.3.8 - Description of the Setpoints menu  
SETPOINTS MENU [2]  
ITEM  
0
FORMAT UNITS  
RANGE  
COMMENTS  
±nn.n  
±nn.n  
nnn  
°C  
°C  
°C  
°C  
°C  
°C  
See table below  
See table below  
See table below  
See table below  
See table below  
3.8 to 50  
This item lets you display and modify Cooling setpoint 1*  
1
This item lets you display and modify Cooling setpoint 2*  
2
This item lets you display and modify Heating setpoint 1*, only displayed for heat pumps.  
This item lets you display and modify Heating setpoint 2*, only displayed for heat pumps.  
This item lets you display and modify Heating setpoint 3*, only displayed for heat pumps.  
3 [1]  
4 [1]  
5 [1]  
nnn  
nn.n  
±nn.n  
Automatic changeover threshold, cooling mode. This item lets you display and modify the outdoor  
temperature threshold at which the unit changes over in cooling mode. See section 5.2. Displayed only if  
the auto cooling/heating changeover function is selected.  
6 [1]  
±nn.n  
°C  
0 to 46  
Automatic changeover threshold, heating mode. This item lets you display and modify the outdoor  
temperature threshold at which the unit changes over in heating mode. Displayed only if the auto cooling/  
heating changeover function is selected and if the unit is a heat pump.The heating threshold must be  
3.8°C below the cooling threshold, otherwise the new setpoint will be rejected.  
7
nnn  
nnn  
%
%
0 to 100  
0 to 100  
Demand limit 1 setpoint. Limitation by volt-free contact.This item is used to define the maximum  
capacity that the unit is authorised to use, if the demand limit contact(s) activate limit 1. Contact control  
depends on the unit type and configuration. See sections 3.6.4 and 3.6.5.  
8 [1]  
Demand limit 2 setpoint. Limitation by volt-free contact.This item is used to define the maximum  
capacity that the unit is authorised to use, if the demand limit contact(s) activate limit 2. Contact control  
depends on the unit type and configuration. Displayed and used only for dual-circuit units. See section  
3.6.5 for the contact control description.  
9 [1]  
10  
nnn  
%
0 to 100  
Demand limit 3 setpoint. Limitation by volt-free contact.This item is used to define the maximum  
capacity that the unit is authorised to use, if the demand limit contact(s) activate limit 3. Displayed and  
used only for dual-circuit units. See section 3.6.5 for the contact control description.  
±nn.n  
°C/min  
0.1 to 1.1  
Cooling or heating ramp loading rate. This parameter is only accessible if the ramp function is  
validated in the User Configuration 1 menu. This item refers to the rates of temperature drop in °C in the  
evaporator. When capacity loading is effectively limited by the ramp, mode 7 is active.  
11 [1]  
12 [1]  
13 [1]  
14 [1]  
15 [1]  
16 [1]  
±nn.n  
±nn.n  
±nn.n  
±nn.n  
±nn.n  
±nn.n  
°C  
°C  
°C  
°C  
°C  
°C  
See table below  
See table below  
See table below  
See table below  
See table below  
-16 to 16  
Zero reset threshold, cooling mode**  
Full reset threshold, cooling mode**  
Full reset value, cooling mode**  
Zero reset threshold, heating mode**  
Full reset threshold, heating mode**  
Full reset value, heating mode**  
1
2
*
This item is displayed in certain unit configurations only.  
All points contained in this table can be modified.  
Those setpoints can be used for entering or leaving water temperature control. By default the unit controls the evaporator entering fluid temperature.  
Leaving fluid temperature control requires a parameter modification in the Service Configuration menu.  
** These parameters are only accessible when reset based on OAT or delta T has been selected in the User Configuration 1 menu. See section 4.3.11.3 & 5.6.2.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LEAVING WATER TEMPERATURE CONTROL  
SETPOINT - °C  
RESET THRESHOLDS IN COOLING OR HEATING MODE  
R-22/R-407C  
Reset threshold  
Zero  
Full  
Minimum cooling value  
Water  
Reset based on outdoor  
air temperature  
-10 to 51 °C  
-10 to 51 °C  
5.0  
Medium brine  
Brine  
0.0  
Reset based on  
Delta T  
0 to 11.1 °C  
0 to 11.1 °C  
-10.0  
20.0  
6.0  
20.6  
56.1  
48.0  
Maximum cooling value  
Feedback setpoint, cooling  
Minimum heating value  
Maximum heating value  
Feedback setpoint heating  
ENTERING WATER TEMPERATURE CONTROL  
SETPOINT - °C  
R-22/R-407C  
Minimum cooling value  
Water  
10.0  
6.1  
Medium brine  
Brine  
-3.9  
26.1  
12.0  
14.4  
50.0  
42.0  
Maximum cooling value  
Feedback setpoint, cooling  
Minimum heating value  
Maximum heating value  
Feedback setpoint heating  
4.3.9 - Description of the Inputs menu  
INPUTS MENU [2]  
ITEM  
FORMAT  
UNITS  
COMMENTS  
0
oPEn/CLoS  
-
Remote contact 1 status.  
If the auto cooling/heating changeover function is not selected (User Configuration 1), this contact is used to start and  
stop the unit. If the auto cooling/heating changeover function is selected, this contact is multiplexed with contact 2 to  
permit starting and stopping the unit and the selection of heating/cooling/auto.This contact is only valid, if the unit is in  
the remote operating control (rEM) mode. See section 3.6 for the description of the connections of this contact.  
1 [1]  
oPEn/CLoS  
oPEn/CLoS  
-
-
Remote contact 2 status.  
If the auto cooling/heating changeover function is not selected (User Configuration 1), this contact is used to select the  
heating or cooling mode. If the auto cooling/heating changeover function is selected, this contact is multiplexed with  
contact 1 to permit starting and stopping the unit and the selection of heating/cooling/auto.This contact is only valid, if  
the unit is in the remote operating control (rEM) mode. See section 3.6 for the description of the connections of this  
contact.  
2
Remote contact 3 status.  
The operation of this contact depends on the unit type.  
Single-circuit unit: this contact can be used either to limit unit demand or to select a setpoint, as described in User  
Configuration. If this contact is used for selecting a setpoint it is only active if the unit is in the remote operating control  
mode. If the contact is used to limit the demand of the unit, it is active in all operating types.  
Open contact: unit capacity is not limited or unit control is based on setpoint 1.  
Closed contact: unit capacity is limited at limit setpoint 1 or unit control is based on setpoint 2.  
See section 4.3.11.3 for the configuration of contact 3 - section 5.6.1 for the description of the setpoint selection -  
section 5.7 for the description of the demand limit function and 3.6 for the description of the connection of contact 3 for  
single-circuit units.  
Dual-circuit units: this contact is multiplexed with contact 4 to permit the selection of a demand limit point.This  
contact is active in all operating types. See section 3.6.5 for the description of this contact and section 5.7 for the  
description of the demand limit function.  
3
oPEn/CLoS  
oPEn/CLoS  
oPEn/CLoS  
-
-
-
Remote contact 4 status.  
This contact is only used for dual-circuit units: this contact is multiplexed with contact 3 to permit selection of a  
demand limit value. This contact is active in all operating types. See section 3.6.5 for the description of this contact  
and section 5.7 for the description of the demand limit function.  
4 [1]  
5 [1]  
Remote contact 5 status.  
This contact is only used for dual-circuit units: this contact is multiplexed with contact 6 to permit selection of a  
setpoint. This contact is only active in the remote operating control mode. See section 3.6.6 for the description of this  
contact and section 5.6.1 for the description of the setpoint selection function.  
Remote contact 6 status.  
This contact is only used for dual-circuit units: this contact is multiplexed with contact 5 to permit selection of a  
setpoint. This contact is only active in the remote operating control mode. See section 3.6.6 for the description of this  
contact and section 5.6.1 for the description of the setpoint selection function.  
6 [1]  
7
oPEn/CLoS  
oPEn/CLoS  
-
-
Interlock status. When this contact opens the unit stops or is prevented from starting and an alarm is created. This  
contact is used to control the water flow. In addition, a customer safety device can be connected in series with this  
contact (see section 3.6).  
Water pump run contact status. When this contact opens while an evaporator pump has received a command to be  
on then a pump failure alarm is tripped.  
8 [1]  
9 [1]  
b1b2b3  
b1b2b3  
-
-
Compressor feedback contacts, circuit A  
Compressor feedback contacts, circuit B  
b1 = feedback A1  
b1 = feedback B1  
b2 = feedback A2  
b2 = feedback B2  
b3 = feedback A3  
b3 = feedback B3  
1
2
This item is displayed in certain unit configurations only  
Access to this menu is read-only.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.3.10 - Description of the Outputs/Tests menu  
4.3.10.1 - General  
This menu displays the status of the controller outputs. More-  
over, when the machine is fully stopped (LOFF) the outputs  
can be activated for manual or automatic tests (the access to the  
tests is password controlled).  
4.3.10.2 - Menu description  
OUTPUTS STATUS & TESTS MENU [2] [3]  
ITEM  
FORMAT  
UNITS  
DESCRIPTION  
0
b1b2b3  
Circuit A compressors, command status  
b1 = compressor A1  
tESt  
b2 = compressor A2  
FAIL  
Good  
b3 = compressor A3  
-
In test mode, the Arrow buttons display 001, 010 and 100 in succession, so as to force the status of the compressor outputs  
in turn. During the test phase, power to the compressor is switched on for 10 seconds only. It is then not possible to restart the  
compressor for a further 30 seconds. When the test is completed the following is displayed:  
- Fail: displayed if the test has failed because the compressor was not started or run in reverse rotation.  
- Good: displayed if test was successful  
1 [1]  
b1b2b3  
Circuit B compressor, dual-circuit units only  
b1 = compressor B1  
tESt  
b2 = compressor B2  
FAIL  
Good  
b3 = compressor B3  
In test mode... as above  
-
-
2
StoP  
LOW  
HIGH  
tESt  
Two-speed fan status, circuit A  
Stop = fan is stopped  
Low = fan is in low speed  
High = fan is in high speed  
3 [1]  
4 [1]  
5 [1]  
StoP  
LOW  
HIGH  
tESt  
Two-speed fan status, circuit B  
Stop = fan is stopped  
Low = fan is in low speed  
High = fan is in high speed  
-
-
b1b2  
Single-speed fan status  
b1 = fan A2  
b2 = fan B2  
Only for dual-circuit units  
On  
Evaporator water pump #1 command status. Not displayed if the unit does not control a pump.  
On: pump is running  
OFF  
tESt  
FAIL  
Good  
Forc  
Stop: pump is stopped  
Forc: this item is displayed only when the unit is stopped locally (LOFF). selecting this item authorises turning on the  
pump with no delay and for an unlimited length of time.The pump will remain on until any button of the user interface is  
pressed: it is then immediately stopped. If the unit is in CCN control, then the pump status is displayed in turn with "Forc"  
if the pump status if forced through CCN.  
-
During the test phase, power to the pump is switched on for 10 seconds only. When the test is completed the following is  
displayed:  
- Fail: displayed if the test has failed because the pump was not started  
- Good: displayed if the test was successful  
6 [1]  
On  
Evaporator water pump #2 command status. Not displayed if the unit does not control a secondary pump.  
On: pump is running  
OFF  
tESt  
FAIL  
Good  
Forc  
Stop: pump is stopped  
Forc: this item is displayed only when the unit is stopped locally (LOFF). selecting this item authorises turning on the  
pump with no delay and for an unlimited length of time.The pump will remain on until any button of the user interface is  
pressed: it is then immediately stopped. If the unit is in CCN control, then the pump status is displayed in turn with "Forc"  
if the pump status if forced through CCN.  
-
During the test phase, ...as above  
7
8
On  
OFF  
tESt  
Water or air heat exchanger heater command status  
See sections 5.5 and 5.11  
-
-
b1b2  
tESt  
Alarm output command status  
b1 = alarm circuit A  
b2 = alarm circuit B  
In test mode, the Arrow buttons display 01 and 10 in succession, so as to force each alarm output status in turn.  
9 [1]  
On  
Boiler command status. Displayed if the unit controls a boiler. See section 5.13.  
OFF  
tESt  
-
10 [1]  
11 [1]  
12 [1]  
nnn  
tESt  
Variable fan speed, circuit A. Displayed if the unit controls a variable-speed fan.  
%
%
nnn  
tESt  
Variable fan speed, circuit B. Dual-circuits only and if the unit controls a variable-speed fan.  
b1b2  
tESt  
4-way reversing cycle valve status. In test mode, the arrow keys successively display 01 and 10, in order to authorise the  
test for each valve in turn.  
b1 = valve circuit A  
b2 = valve circuit B  
This item is only displayed for heat pump units.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OUTPUTS STATUS & TESTS MENU [2] [3] continued  
ITEM  
FORMAT  
UNITS  
DESCRIPTION  
13 [1]  
b1b2b3b4  
tESt  
Additional heating stage status.  
b1 = stage 1  
b2 = stage 2  
b3 = stage 3  
b4 = stage 4  
In test mode the arrow keys successively display 0001, 0010, 0100 and 1000 to force the status of each electric heating stage  
in turn.  
This item is only displayed for heat pump units controlling additional electric heater stages. See section 5.12.  
14 [1]  
15  
YES  
no  
tESt  
-
-
%
Used for local interface test only. Lights or flashes all LEDs and blocks, so as to check that they are working properly.  
Automatic test. Selecting this item activates the automatic test function.  
Auto tESt  
-
1
2
3
This item is displayed in certain unit configurations only.  
Testing authorised only if the unit is in Local Off and all compressors are off.  
Password needed only for testing.  
“Test” Displayed in turn with the item value during tests.  
4.3.10.3 - Manual tests  
If a test fails, an error message and an error code are dis-  
played. The automatic test procedure is interrupted.  
This function allows the user to test the outputs individually, if  
the machine is completely shut down (LOFF). To carry out a  
manual test use the arrow keys to access the output to be tested  
and press the Enter key (longer than 2 seconds) to activate the  
modification mode. The password is automatically requested, if it  
has not previously been verified. The Outputs/Test LED on the  
user interface begins to flash. Enter the desired test value and  
again press Enter to start the test. 'TESt' is displayed on the 4-  
digit display alternately with the value tested. The Outputs/Test  
LED stops flashing. Press the Enter key or an arrow key to stop  
the test.  
When all tests have been completed, an end-of-test message  
appears.  
The table below describes the messages shown on the user  
interface during the automatic test sequence.  
TEXT  
DESCRIPTION  
Thermistor test failed [XX]  
Pressure test failed [XX]  
Test number XX of the thermistor has failed  
Test number XX of the pressure sensor has  
failed  
Output test failed [XX]  
Input test failed [XX]  
Output test number XX has failed  
Input test number XX has failed  
4.3.10.4 - Automatic tests  
The automatic test function verifies the integrity of the analo-  
gue entries and activates the outputs in sequence. For each test  
't XX' is displayed on the user interface. 'xx' indicates the  
number of the test in progress. When a test has been completed,  
the following test is automatically activated.  
Press enter if test [XX] correct  
Request for the operator to validate test XX  
OAT [value] press enter if  
test [XX] correct  
Request for the operator to validate the  
outdoor air temperature value displayed.  
Test number XX  
Auto test completed  
Automatic test completed  
A message may appear, asking the operator for a validation  
with the Enter key, if the control cannot automatically verify a  
sensor value or an output status. If the value read or the output  
status is incorrect, the operator must press a different key (not  
the Enter key) to cancel the automatic test procedure.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The table below describes the different sequences of the  
automatic test.  
TEST NUMBER  
DESCRIPTION  
CONFIRMATION  
0
Outdoor temperature sensor test  
yes  
no  
1
Pressure sensor test - circuit A  
2
Pressure sensor test - circuit B (dual-circuit units only)  
Defrost sensor test - circuit A (heat pumps only)  
no  
3
no  
4
Defrost sensor test - circuit B (dual-circuit heat pumps only)  
Water flow switch test and primary pump test  
no  
5, 6  
no  
7, 8, 9  
Entering and leaving water temperature sensor test  
Water system temperature sensor test (for master/slave units equipped with this sensor only)  
Water flow switch test and secondary pump test (for units equipped with a secondary pump only)  
Test compressor A1, A2 (if applicable), A3 (if applicable)  
4-way reversing valve test, circuitA (heat pumps only)  
Test compressor B1 (if applicable), B2 (if applicable), B3 (if applicable)  
4-way reversing valve test, circuit B (dual-circuit heat pumps only)  
Low-speed test, fan A1 (units not equipped withVarifan)  
High-speed test, fan A1 (units not equipped with Varifan)  
Low-speed test, fanA2 (dual-circuit units not equipped withVarifan)  
High-speed test, fan A2 (dual-circuit units not equipped with Varifan)  
Fixed-speed test, fan A2 (for circuits equipped with a second fan)  
Fixed-speed test, fan B2 (for circuits equipped with a second fan)  
Water and air heat exchanger heater test  
no  
10, 11  
no  
12, 13, 14  
no  
15, 16, 17  
no  
18  
no  
19, 20, 21  
22  
no  
no  
23  
yes  
yes  
yes  
yes  
yes  
yes  
yes  
24  
25  
26  
27  
28  
29  
30  
Not used  
31  
Boiler output activation (if unit controls a boiler)  
yes  
yes  
yes  
yes  
yes  
yes  
yes  
-
32  
Additional electric heating stage 1 activation (if unit controls electric heating stages)  
Additional electric heating stage 2 activation (if unit controls electric heating stages)  
Additional electric heating stage 3 activation (if unit controls electric heating stages)  
Additional electric heating stage 4 activation (if unit controls electric heating stages)  
Alarm output A activation  
33  
34  
35  
36  
37  
Alarm output B activation  
38  
Automatic test completed  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The table below describes the faults that can be displayed  
during the automatic test.  
4.3.11- Description of the configuration menu  
4.3.11.1- General  
TEST FAULT  
DESCRIPTION  
This menu can be used to display and modify all configura-  
tions: Factory, Service and User. Only the User Configuration can  
be modified by the end-user. The Factory, Service and master/  
slave configurations are not described in this document. A  
configuration can only be modified if the unit is fully stopped  
(LOFF).  
1
2
Outdoor air thermistor outside range  
Outdoor air value read not validated by operator  
3
4
5
6
Low pressure transducer, circuit A, outside range  
High pressure transducer, circuit A, outside range  
Low pressure transducer, circuit B, outside range  
High pressure transducer, circuit B, outside range  
7
8
Defrost thermistor, circuit A, outside range  
Defrost thermistor, circuit B, outside range  
The menus User 1 [USEr 1] and User 2 [USEr 2] are pass-  
word-protected. The other menus are directly accessible,  
except if item 11 of the User 2 menu (password for all con-  
figurations) has been validated.  
9
Water flow switch not open  
10  
Primary pump not started or water flow switch not  
closed  
11, 12, 13; 14, 15  
16, 17, 18, 19, 20  
Water entering temperature sensor outside range  
Water leaving temperature sensor outside range  
21  
Temperature difference between entering and leaving  
water sensors too high  
4.3.11.2 - Password  
22, 23; 24, 25, 26  
Water system leaving temperature sensor outside  
range  
A password must be entered in order to access the test function  
or to modify a configuration. It is automatically requested, if  
necessary: 'EntEr PASS' is displayed on the 4-digit display and  
the configuration menu LED flashes, indicating that the  
modification mode is active. Press the arrow keys until the  
value '11' is displayed on the 4-digit display. Press Enter to  
validate this. The configuration menu LED stops flashing. If the  
password is correct, 'Good' is displayed. If the password is  
incorrect, 'PASS incorrEct' is displayed. The User password has  
a default value of 11.  
27  
28  
29  
30  
Temperature difference between the system entering  
and leaving water sensors too high  
Water flow switch not closed or primary pump not  
stopped  
Secondary pump not started or water flow switch not  
closed  
Water flow switch not closed or secondary pump not  
stopped  
31  
32  
33  
Command fault; compressor A1  
Command fault; compressor A2  
Command fault; compressor A3  
34  
Command fault, 4-way reversing valve, circuit A  
This value can be modified through the Service configuration.  
The password can be entered if the unit is fully stopped,  
otherwise 'ACCES dEniEd' (access denied) will be displayed on  
the 4-digit display. The controller automatically deactivates the  
password after 5 minutes without activity (i.e. no buttons  
pressed) or after powering up.  
35  
36  
37  
Command fault; compressor B1  
Command fault; compressor B2  
Command fault; compressor B3  
38  
Command fault, 4-way reversing valve, circuit B  
39  
40  
41  
42  
43  
44  
Low-speed test, fan A1 not validated by the operator  
High-speed test, fan A1 not validated by the operator  
Low-speed test, fan B1 not validated by the operator  
High-speed test, fan B1 not validated by the operator  
Test fan A2 not validated by the operator  
Test fan B2 not validated by the operator  
45  
Water heat exchanger heater and air heat exchanger  
condensate heater test, circuit A not validated by the  
operator  
46  
Air heat exchanger condensate heater, circuit B, not  
validated by the operator  
47  
48  
Boiler activation test not validated by the operator  
Electric heating stage 1 activation test not validated  
by the operator  
49  
50  
51  
Electric heating stage 2 activation test not validated  
by the operator  
Electric heating stage 3 activation test not validated  
by the operator  
Electric heating stage 4 activation test not validated  
by the operator  
52  
53  
Alarm relay output activation test, circuit A not  
validated by the operator  
Alarm relay output activation test, circuit B not  
validated by the operator  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SUB-MENU USER CONFIGURATION  
ITEM USER 1  
USER 2  
[USER2]  
DATE  
[dAtE]*  
SCHEDULE 1  
[ScHEduLE 1MEnu]*  
SCHEDULE 2  
[ScHEduLE 2 MEnu]* [HOLidAy MEnu]*  
HOLIDAYS  
BROADCAST  
[BrodCASt]*  
[USER1]  
0
Return to previous menu  
Return to previous  
menu  
Return to previous Return to previous menu Return to previous  
Return to previous menu  
Return to previous menu  
menu  
menu  
1
-
Periodic pump start-  
up  
Hour*  
SUB-MENU:  
Period 1 [PErIod 1]  
SUB-MENU:  
Period 1 [PErIod 1]  
SUB-MENU:  
Holidays 1 [HOLidAy 1]  
Broadcast acknowledger  
selection  
2
Ramp selection*  
Start-up delay*  
Water pump selection  
Night mode - start  
hour  
Night mode - end  
hour  
Night mode demand  
limit  
Day of the week* SUB-MENU:  
Period 2 [PErIod 2]  
SUB-MENU:  
SUB-MENU:  
Period 2 [PErIod 2]  
SUB-MENU:  
Period 3 [PErIod 3]  
SUB-MENU:  
Period 4 [PErIod 4]  
SUB-MENU:  
Holidays 2 [HOLidAy 2]  
SUB-MENU:  
Holidays 3 [HOLidAy 3]  
SUB-MENU:  
Holidays 4 [HOLidAy 4]  
Broadcast activation  
3
Day and month*  
Outdoor temperature  
broadcast bus  
Outdoor temperature  
broadcast element  
Period 3 [PErIod 3]  
4
Year*  
SUB-MENU:  
Period 4 [PErIod 4]  
5
Water pump changover  
delay*  
Pump shutdown in  
standby mode  
Control contact 3  
selection*  
Setpoint reset selection,  
cooling mode  
Night mode min.  
demand  
Alarm relay selection  
-
-
-
-
-
-
-
-
-
-
-
-
SUB-MENU:  
Period 5 [PErIod 5]  
SUB-MENU:  
Period 6 [PErIod 6]  
SUB-MENU:  
Period 7 [PErIod 7]  
SUB-MENU:  
Period 8 [PErIod 8]  
-
-
-
-
-
-
-
-
SUB-MENU:  
Period 5 [PErIod 5]  
SUB-MENU:  
Period 6 [PErIod 6]  
SUB-MENU:  
Period 7 [PErIod 7]  
SUB-MENU:  
Period 8 [PErIod 8]  
-
-
-
-
-
-
-
-
SUB-MENU:  
Holidays 5 [HOLidAy 5]  
SUB-MENU:  
Holidays 6 [HOLidAy 6]  
SUB-MENU:  
Holidays 7 [HOLidAy 7]  
SUB-MENU:  
Holidays 8 [HOLidAy 8]  
SUB-MENU:  
Holidays 9 [HOLidAy 9]  
SUB-MENU:  
Holidays 10 [HOLidAy 10]  
SUB-MENU:  
Holidays 11 [HOLidAy 11]  
SUB-MENU:  
Holidays 12 [HOLidAy 12]  
SUB-MENU:  
Holidays 13 [HOLidAy 13]  
SUB-MENU:  
Holidays 14 [HOLidAy 14]  
SUB-MENU:  
Holidays 14 [HOLidAy 14]  
SUB-MENU:  
Holidays 16 [HOLidAy 16]  
Start month daylight  
saving time  
Start day daylight saving  
time  
Start hour daylight saving  
time  
Minutes to add  
6
7
Number clock 1  
Number clock 2  
8
8
Setpoint reset selection,  
heating mode*  
Boiler selection  
CCN element  
number  
CCN bus number  
End month daylight saving  
time  
End day daylight saving  
10  
11  
12  
13  
14  
15  
16  
time  
Boiler operation  
threshold*  
Operating threshold,  
heating mode*  
Electric heating stage  
operation threshold*  
Electric heating safety  
stage threshold*  
Electric heating stage  
operation schedule*  
Quick start-up, electric  
heater stages in defrost  
mode*  
Password for all user  
configurations  
-
End hour daylight saving  
time  
Minutes to subtract  
Software version  
number  
-
-
-
-
-
-
-
17  
18  
Automatic heating/cooling  
changeover selection  
Extended display  
selection  
-
-
-
-
-
-
-
-
-
-
-
-
*
only displayed if configuration requires.  
NOTE: The items in brackets show what is displayed on the  
user interface.  
SUB-MENU PERIOD CONFIGURATION*  
CONFIGURATION  
Item  
PERIOD 1 to 8  
[PEriod X MEnu]*  
USER  
[USEr]  
0
1
2
3
4
5
6
7
8
9
10  
Return to previous menu  
Start of occupied period  
End of occupied period  
Selection Monday  
USER1  
[USEr 1]  
USER2  
[USEr 2]  
SCHEDULE 1  
[SCHEduLE 1]*  
SCHEDULE 2  
[SCHEduLE 2]*  
HOLIDAYS  
[HOLIDAYS]*  
HOUR + DATE  
[dAtE]*  
BROADCAST  
[broAdCASE]*  
Selection Tuesday  
Selection Wednesday  
Selection Thursday  
Selection Friday  
PERIOD 1  
PERIOD 2  
PERIOD 3  
PERIOD 4  
PERIOD 5  
PERIOD 6  
PERIOD 7  
PERIOD 8  
HOLIDAY 1  
HOLIDAY 2  
HOLIDAY 3  
HOLIDAY 4  
HOLIDAY 5  
HOLIDAY 6  
HOLIDAY 7  
HOLIDAY 8  
PERIOD 1  
PERIOD 2  
PERIOD 3  
PERIOD 4  
PERIOD 5  
PERIOD 6  
PERIOD 7  
PERIOD 8  
Selection Saturday  
Selection Sunday  
Selection holidays  
SUB-MENU HOLIDAY CONFIGURATION*  
Item  
HOLIDAYS 1 to 16  
[HoLidAy X MEnu]*  
0
1
3
4
Return to previous menu  
Start month holidays  
Start day holidays  
Number of days, holidays  
*
only displayed if configuration requires.  
...  
...  
NOTE: The items in brackets show what is displayed on the  
user interface.  
...  
HOLIDAY 15  
HOLIDAY 16  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.3.11.3 - Description of the User 1 Configuration sub-menu  
USER 1 CONFIGURATION SUB-MENU [2]  
ITEM  
0
FORMAT  
USEr MEnu  
YES/no  
UNITS  
DEFAULT  
COMMENTS  
-
-
-
When selected this item authorises return to the previous menu.  
2 [1]  
no  
Ramp loading select. For units with more than one compressor only.  
Yes = ramp enabled  
No = ramp disabled  
This configuration enables the ramp to be activated for heating or cooling (depending on configuration): the  
maximum rate (in °C/min) of temperature drop or rise for the heat exchanger water (leaving or entering, upon  
configuration). Ramp setting value can be configured in the Setpoint menu.  
3
4
1 to 15  
min  
-
1
0
Delay at start-up. This value is reinitialised after power-up or when both circuits are halted by local, remote or  
CCN command. No compressor will be started up until this pause has expired. However, the evaporator pump  
command will be activated immediately.The safety lockout loop will not be checked until the pause has  
expired.  
0/1/2/3/4  
Pump sequence select  
0 = no pump  
1 = one pump only  
2 = two pumps with auto rotation  
3 = pump #1 manual select  
4 = pump #2 manual select  
If the auto sequence is selected, the pump change-over occurs when the rotation delay is elapsed. If the  
manual sequence is selected then, the selected pump is used in priority. Change-over occurs if one pump fails.  
5 [1]  
6 [1]  
7 [1]  
24 to 3000  
«YES/no»  
0/1  
hours  
48  
noi  
0
Pump changeover delay. Displayed if auto pump sequence is selected. This parameter is used for pump  
auto-rotation: the control tries to limit the pump run time difference to the pump changeover delay value.  
Change-over between pumps occurs when this difference becomes greater than the configured pump  
changeover delay.  
-
-
Pump shutdown in standby mode  
Displayed if the unit controls a water pump. If this parameter is validated, the pump will be shut down when  
the standby mode is active (in automatic heating/cooling changeover). It automatically restarts in heating or  
cooling mode.  
Contact 3 select (for single-circuit units)  
0 = input is used for demand limit command control  
1 = input is used for dual setpoint command control  
Determines whether contact 3 is used for remote demand limit or dual setpoint control. For single-circuit units  
only.  
8
0/1/2  
-
-
-
0
Cooling setpoint reset select. See section 5.6.2.  
0 = reset not selected  
1 = reset based on outdoor temperature  
2 = reset based on return water temperature  
9 [1]  
10  
0/1/2  
0
Heating setpoint reset select. See section 5.6.2  
0 = reset not selected  
1 = reset based on outdoor temperature  
2 = reset based on return water temperature  
«YES/no»  
no  
Boiler control select  
Yes = boiler controlled by the unit  
No = boiler not controlled  
11 [1]  
12 [1]  
13 [1]  
14 [1]  
-15 to 0  
-20 to 0  
-5 to 21  
«YES/no»  
°C  
°C  
°C  
-
-10  
-15  
5
Boiler threshold. Outdoor air temperature limit; if the temperature is lower, the heat pump is stopped or only  
the boiler is used for hot water production. Only for heat pumps controlling an additional boiler.  
Operating threshold, heating mode. Outside air temperature threshold below which the heat pump shuts  
down.The unit switches the electric heaters on and off (if these exist). For heat pumps only.  
Electric heating stage threshold. Maximum outdoor air temperature threshold for the use of electric heating  
stages. Only for heat pumps, equipped with optional additional electric heating stages.  
no  
Electric heating safety stage. In this configuration the last electric heating stage is only activated in the safety  
mode (in case of a unit fault that prevents unit operation in heat pump mode).The other electric heating stages  
operate normally. See section 5.12.  
15 [1]  
16 [1]  
17 [1]  
0 to 60  
minutes  
Electric heating stage operation schedule. Permits configuration of a start-up delay after unit start-up during  
which the electric heater stages are not allowed to start.  
«YES/no»  
«YES/no»  
-
-
no  
no  
Quick start-up, electric heater stages in defrost mode. If a circuit switches to defrost mode, the electric  
heater stages are allowed to start up immediately. For heat pumps only.  
Automatic cooling/heating changeover select. Permits activation of the automatic changeover function.  
Caution:This function requires a special operation for control contacts 1 and 2, if the machine is under remote  
control (see section 3.6.3).  
18  
«YES/no»  
-
yes  
Extended menu select  
Yes = menu description available  
No = menu description not available  
This item authorises activating or inhibiting the menu item expanded display.  
1
2
This item shall be masked when not used.  
Access to menu is read/write.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.3.11.4 - Description of the User 2 Configuration sub-menu  
USER 1 CONFIGURATION SUB-MENU  
ITEM  
FORMAT  
UNITS  
DEFAULT  
COMMENTS  
0
1
USEr 2 Menu  
«YES/no»  
When selected this item authorises return to the previous menu.  
-
no  
Periodic pump quick-start of the water pump(s)  
Yes = the pump is started periodically when the unit is manually stopped.  
No = periodic pump start is disabled  
When the unit is manually stopped (e.g. during the winter season) the pump is started each day at 14.00 hours  
for 2 seconds. If two pumps are available, pump #1 is started on odd days and pump #2 on even days.  
2
n1n2n3 n4  
Night control mode - start time*  
00:00 to 23:59  
-
00:00  
Authorises entering the time of day at which the night control mode starts. During this period the fan runs at  
low speed (to reduce fan noise) if permitted by operating conditions, and unit capacity is limited to the  
maximum night values.  
3 [1]  
4
n1n2n3 n4  
00:00 to 23:59  
Night control mode - end time*  
Authorises entering the time of day at which the night control mode ends.  
-
-
00:00  
no  
«YES/no»  
Night mode demand limit value. This item permits demand limitation in the night control mode. In this case, if  
the unit fans cannot be kept at low speed due to the operating conditions, the unit capacity is reduced to  
prevent fan operation at high speed.  
5
6
0 to 100  
0/1/2  
%
-
0
0
Night mode demand limit.The unit capacity is never reduced below this capacity in night control mode.  
Alarm relay selection  
0 = alarms/alerts, one alarm/alert output per circuit.  
1 = alarms only, one alarm output per circuit.  
2 = mixed mode, one alarm relay and one alert relay, dual-circuit units only.  
7
8
0 or 65 to 99  
0 or 65 to 99  
-
-
0
0
Schedule 1 clock number (for unit on/off schedule, see section 4.3.11.6).  
0 = schedule in local operating mode  
65 to 99 = schedule in CCN operating mode  
Schedule 2 clock number (schedule for setpoint selection, see section 4.3.11.6).  
0 = schedule in local operating mode  
65 to 99 = schedule in CCN operating mode  
9
1 to 239  
0 to 239  
«YES/no»  
-
-
-
1
CCN element address.  
No two network elements can have the same element number and bus number at the same time.  
10  
11  
0
CCN bus number.  
No two network elements can have the same element number and bus number at the same time.  
no  
Password for all User Configurations  
Yes = password required for all User Configurations (Date, Time Schedule, Broadcast)  
No = password require for User menu only  
When this item is validated, the User Password will be required for all configurations accessible by the User.  
12  
nn.n  
-
-
Software version number  
This item shows the number of the software version used by this controller. Access is read only.  
*
n1n2: hours (00 to 23). The first time the Enter button is continuously pressed, the first two characters in the 4-digit display flash so that hours can be adjusted.  
n3n4: minutes (00 to 59). Continuous pressing of the Enter key again causes the last two characters to flash so that minutes can be adjusted.  
4.3.11.5 - Description of Date and Time configuration sub-  
menu  
4.3.11.6 - Description of the Time Schedules sub-menus  
The control provides two timer programs: schedule 1 and  
schedule 2 that can be activated if the unit is equipped with an  
optional CCN/clock board (if the CCN/clock board is not  
installed, the two schedules are permanently in occupied  
mode).  
DATE & TIME CONFIGURATION SUB-MENU  
ITEM  
FORMAT  
COMMENTS  
0
dAtE MEnu  
When selected this item authorises return to the  
previous menu.  
1
2
n1n2n3n4  
Current time setting.  
The first timer program (schedule #1) provides a means to  
automatically switch the unit from an occupied mode to an  
unoccupied mode: the unit is started during occupied periods.  
00:00 to 23:59 n1n2: hours (00 to 23).The first time the Enter button is  
continuously pressed, the first two characters in the 4-  
digit display flash so that hours can be adjusted.  
n3n4: minutes (00 to 59). Continuous pressing of the  
Enter key again causes the last two characters to flash  
and minutes can be adjusted.  
The second timer program (schedule #2) provides a means to  
automatically switch the active setpoint from an occupied  
setpoint to an unoccupied setpoint: cooling setpoint 1 is used  
during occupied periods, cooling or heating setpoint 2 during  
unoccupied periods. Heating setpoint 3 is activated during  
holiday periods. For additional information on set-point  
activation see section 5.6.1.  
Current day of week setting.  
«Mon»  
«tUe»  
«uEd»  
«tHu»  
«FrI»  
Monday  
Tuesday  
Wednesday  
Thursday  
Friday  
«SAt»  
«Sun»  
Saturday  
Sunday  
3
4
n1n2n3n4  
Current day and month setting.  
01:01 to 31:12 n1n2:day (01 to 31).The first time the Enter button is  
continuously pressed, the first two characters in the 4-  
digit display flash so that day can be adjusted.  
Each schedule consists of eight time periods set by the operator.  
These time periods can be flagged to be in effect or not in effect  
on each day of the week plus a holiday period (see section  
4.3.11.7 on public holidays). The day begins at 00.00 hours  
and ends at 24.00 hours.  
n3n4:month (01 to 12). Continuous pressing of the Enter  
key again causes the last two characters to flash so  
that month can be adjusted.  
nnnn  
Current year setting.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Program is in unoccupied mode unless a schedule time period  
is in effect. If two periods overlap and are both active on the  
same day, the occupied mode takes priority over the  
unoccupied period.  
4.3.11.7 - Description of the Holidays sub-menus  
This function is used to define 16 public holiday periods. Each  
period is defined with the aid of three parameters: the month,  
starting day and duration of the public holiday period. During  
these public holidays the controller will be in occupied or  
unoccupied mode, depending on the programmed periods  
validated for public holidays (see section 4.3.11.6).  
Each of the eight periods can be displayed and changed with  
the aid of a sub-sub-menu. The table below shows how to  
access the period configuration. Method is the same for the  
time schedule #1 or the time schedule #2.  
Each of these public holiday periods can be displayed and  
changed with the aid of a sub-menu.  
PERIOD X CONFIGURATION SUB-MENUS (X = 1 TO 8)  
ITEM # FORMAT  
COMMENTS  
ATTENTION: The broadcast function must be activated to  
utilise the holiday schedule, even if the unit is running in  
stand-alone mode (not connected to CCN). See section  
4.3.11.8.  
0
1
2
Period X Menu  
Indicates the period (X) you are going to configure.  
When selected this item authorises a return to the  
main menu.  
n1n2n3n4  
00:00 to 24:00  
Occupied period - Start time*.  
Authorises entering the time of day at which the  
occupied period starts.  
n1n2n3n4  
Occupied period - End time*.  
Authorises entering the time of day at which the  
occupied period ends.  
00:00 to 24:00  
3
Mo- 0 or Mo- 1  
tu- 0 or tu- 1  
1 = the period is in effect on Monday.  
0 = period not in effect on Monday  
4
1 = the period is in effect on Tuesday.  
0 = period not in effect on Tuesday.  
5
UE-0 or UE- 1  
tH- 0 or tH- 1  
Fr-0 or Fr- 1  
1 = the period is in effect on Wednesday.0 =  
period not in effect on Wednesday.  
6
1 = the period is in effect on Thursday.  
0 = period not in effect on Thursday.  
7
1 = the period is in effect on Friday.  
0 = period not in effect on Friday.  
8
SA- 0 or SA- 1  
Su- 0 or Su- 1  
Ho- 0 or Ho- 1  
1 = the period is in effect on Saturday.  
0 = period not in effect on Saturday.  
9
1 = the period is in effect on Sunday.  
0 = period not in effect on Sunday.  
10  
1 = the period is in effect on public holidays.  
0 = period not in effect on public holidays.  
*
n1n2: hours (00 to 24). The first time the Enter button is continuously pressed,  
the first two characters in the 4-digit display flash so that hours can be  
adjusted.  
n3n4: minutes (00 to 59). Continuous pressing of the Enter key again causes  
the last two characters to flash so that minutes can be adjusted.  
Typical timer program:  
Time MON TUE WES THU FRI SAT SUN HOL  
P1  
P1  
P1  
0
1
2
3
4
5
6
P2 P2 P3  
P2 P2 P3  
P2 P2 P3  
P2 P2 P3  
P2 P2 P3  
P2 P2 P3  
P2 P2 P3  
P2 P2 P3  
P2 P2 P3  
P2 P2 P3  
P2 P2 P3  
P3  
P4  
P4  
P4  
P4  
P4  
P4  
P4  
P4  
P4  
P4  
P4  
P4  
P4  
P4  
P4  
P4  
P4  
P4  
P4  
P4  
P5  
P5  
P5  
P5  
P5  
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
MON :  
TUE :  
WED :  
THU :  
FRI :  
SAT :  
SUN :  
HOL :  
Monday  
Tuesday  
Wednesday  
Thursday  
Friday  
Saturday  
Sunday  
Starts at  
Ends at  
Active on  
P1: period 1,  
P2: period 2,  
P3: period 3,  
P4: period 4,  
P5: period 5,  
P6: period 6,  
P7: period 7,  
P8: period 8,  
0h00,  
7h00,  
7h00,  
7h00,  
7h00,  
20h00,  
3h00,  
Monday  
Monday and Tuesday  
Wednesday  
Thursday and Friday  
Saturday  
Public holidays  
18h00,  
21h00,  
17h00,  
12h00,  
21h00,  
P3  
Public holidays  
P3  
P6  
Not used in this example  
Not used in this example  
Occupied  
Unoccupied  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HOLIDAY PERIOD X CONFIGURATION SUB-MENUS (X = 1 TO 16)  
4.3.11.8 - Description of the Broadcast sub-menu  
The controller provides a broadcast configuration menu which  
you can use to configure the unit to be the CCN’s broadcaster,  
responsible for transmitting the time, outdoor temperature, and  
holiday flags to all system elements.  
ITEM # FORMAT  
COMMENTS  
0
HoLidAy X Sub-menu  
When selected this item authorises a return to  
the configuration menu.  
1
0 to 12  
Start month of public holiday period  
0 = period not in use  
1 = January, 2 = February, etc.  
2
3
0 to 31  
Start day of public holiday period. 0 period  
not in use.  
This menu also authorises setting the date of the daylight  
saving time. There should be only one broadcaster in a CCN, so  
this table should not be configured if any other system element  
is acting as broadcaster.  
0 to 99 days  
Duration of the public holiday period in  
days.  
Typical programming for public holidays:  
A public holiday period lasting 1 day on 20th May, for instance, is configured as  
follows: start month = 5, start day = 20, duration = 1  
A public holiday period lasting 2 day on 25th May, for instance, is configured as  
follows: start month = 5, start day = 25, duration = 2  
ATTENTION: If the unit operates in standalone mode (not  
CCN connected) this menu can also must be used if the holi-day  
function is used or to correct for daylight saving time.  
BROADCAST CONFIGURATION SUB-MENU  
ITEM #  
FORMAT  
COMMENTS  
0
1
broAdCASt MEnu  
YES/no  
When selected this item authorises a return to the main menu.  
Determines whether or not the unit is a broadcast acknowledger when the unit is connected on a CCN network.There must be only  
one broadcast acknowledger in a CCN.  
Warning: if the unit operates in standalone mode (not CCN connected) this choice must be set to Yes if the holiday function is used  
(see section 4.3.11.6) or if you want to configure the daylight saving time function.  
2
YES/no  
This item authorises enabling or disabling the Broadcast function. When it is set to Yes, the control will make a periodic broadcast  
on the CCN. When it is set to No, the control is not the broadcaster and there is no need to configure the other choice in this table.  
There must be only one broadcaster in a CCN and this item should not be configured if any other system element is acting as  
broadcaster.  
Warning: if the unit operates in standalone (not CCN connected) this choice must be set to Yes if the holiday function is used (see  
section 4.3.11.6) or if you want to configure the daylight saving time function.  
3
nnn  
OAT Broadcaster bus number: it is the bus number of the system that has the outside air temperature sensor connected to it.  
0 to 239  
Used for CCN network function only.  
4
5
6
7
nnn  
0 to 239  
OAT Broadcaster element number: it is the element number of the system element that has the outside air temperature sensor  
connected to it. Used for CCN network function only.  
nn  
1 to 12  
Daylight saving start month. In this mode you enter the month in which the broadcaster will adjust its time for the start of  
daylight saving time.  
nn  
1 to 31  
Daylight saving start day. In this mode you enter the day on which the broadcaster will adjust its time for the start of daylight  
saving time.  
n1n2n3n4  
Authorises entering the hours and minutes for saving start. In this mode you enter the time of day when the broadcaster will  
00:00 to 24:00  
adjust its time for the start of daylight saving time.  
n1n2: hours (00 to 24).The first time the Enter button is continuously pressed, the first two characters in the 4-digit display flash so that  
hours can be adjusted.  
n3n4: minutes (00 to 59). Continuous pressing of the Enter key again causes the last two characters to flash so that minutes can be  
adjusted.  
8
nnnn  
Daylight saving start minutes to add: number of minutes by which the broadcaster will adjust its time for the start of daylight  
1 to 1440 minutes  
saving time.  
9
nn  
Daylight saving stop month. In this mode you enter the month in which the broadcaster will adjust its time for the end of  
1 to 12  
daylight saving time.  
10  
11  
nn  
1 to 31  
Daylight saving stop day. In this mode you enter the day on which the broadcaster will adjust its time for the end of daylight  
saving time.  
n1n2n3n4  
Authorises entering the hours and minutes for saving stop. In this mode you enter the time of day when the broadcaster  
00:00 to 24:00  
will adjust its time for the end of daylight saving time.  
n1n2: hours (00 to 24).The first time the Enter button is continuously pressed, the first two characters in the 4-digit display flash so that  
hours can be adjusted.  
n3n4: minutes (00 to 59). Continuous pressing of the Enter key again causes the last two characters to flash so that minutes can be  
adjusted.  
12  
nnnn  
Daylight saving start minutes to subtract: number of minutes by which the broadcaster will adjust its time for the end of  
1 to 1440 minutes  
daylight saving time.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.3.12 - Description of the Alarms menu  
4.3.14 - Runtime menu description  
This menu is used to display and reset up to 5 active alarms. It  
also permits alarm reset. If no alarm is active this menu is not  
accessible. See section 6 for a complete description of the  
alarm codes and alarm reset.  
RUNTIMES  
RUNTIMES 1  
[runtiMES 1]  
RUNTIMES 2  
[runtiMES 2]  
MAINTENANCE  
[MAintEnAnCE]  
ALARMS MENU  
ITEM #  
0 [1]  
FORMAT  
COMMENTS  
NOTE: The items in brackets show what is displayed on the  
user interface.  
X ALArM  
rESEt ALArM  
X alarms are active  
Reset of alarms is requested  
To reset all active alarms, continuously press  
the Enter key. ‘rESET ALArM’ is then displayed.  
Press the select key again: all alarms are reset.  
4.3.14.1 - Description of the Runtimes 1 menu  
RUNTIMES MENU [2]  
1 [1]  
2 [1]  
3 [1]  
4 [1]  
5 [1]  
1 to 55  
1 to 55  
1 to 55  
1 to 55  
1 to 55  
Current alarm code 1*  
Current alarm code 2*  
Current alarm code 3*  
Current alarm code 4*  
Current alarm code 5*  
ITEM # FORMAT  
UNITS  
COMMENTS  
0
-
-
When selected this item  
authorises return to the  
previous menu  
1
nnnn | M 10 | M100  
hrs/10 or 100  
hrs/10 or 100  
Unit operating hours*  
2 [1] nnnn | M 10 | M100  
Unit operating hour in cooling  
mode  
1
This item is masked when nil  
3 [1] nnnn | M 10 | M100  
hrs/10 or 100  
hrs/10 or 100  
hrs/10 or 100  
hrs/10 or 100  
hrs/10 or 100  
hrs/10 or 100  
hrs/10 or 100  
Unit operating hours in heating  
mode  
*
Pressing the Enter key when alarm code is displayed causes the following  
message to be scrolled:  
“time of alarm” “date of alarm” “full CCN alarm message”  
- “time of alarm”: xxhmm  
- “date”: dd-mm  
- “full CCN alarm message”: up to 64 characters  
4
nnnn | M 10 | M100  
Compressor A1 operating  
hours*  
5 [1] nnnn | M 10 | M100  
6 [1] nnnn | M 10 | M100  
7 [1] nnnn | M 10 | M100  
8 [1] nnnn | M 10 | M100  
9 [1] nnnn | M 10 | M100  
Compressor A2 operating  
hours*  
Compressor A3 operating  
hours*  
Compressor B1 operating  
hours*  
4.3.13 - Description of the Alarms History menu  
Compressor B2 operating  
hours*  
ALARMS HISTORY MENU  
Compressor B3 operating  
hours*  
ITEM #  
1 [1]  
2 [1]  
3 [1]  
4 [1]  
5 [1]  
6 [1]  
7 [1]  
8 [1]  
9 [1]  
10 [1]  
FORMAT  
1 to 55  
1 to 55  
1 to55  
COMMENTS  
10 nnnn | M 10 | M100  
11 nnnn | M 10 | M100  
12 [1] nnnn | M 10 | M100  
13 [1] nnnn | M 10 | M100  
14 [1] nnnn | M 10 | M100  
15 [1] nnnn | M 10 | M100  
16 [1] nnnn | M 10 | M100  
17 [1] nn  
-/10 or 100  
-/10 or 100  
-/10 or 100  
-/10 or 100  
-/10 or 100  
-/10 or 100  
-/10 or 100  
hrs/10 or 100  
hrs/10 or 100  
Machine starts*  
Alarm history code 1*  
Alarm history code 2*  
Alarm history code 3*  
Alarm history code 4*  
Alarm history code 5*  
Alarm history code 6*  
Alarm history code 7*  
Alarm history code 8*  
Alarm history code 9*  
Alarm history code 10*  
Compressor A1 starts*  
Compressor A2 starts*  
Compressor A3 starts*  
Compressor B1 starts*  
Compressor B2 starts*  
Compressor B3 starts*  
Pump #1 operating hours*  
Pump #2 operating hours*  
1 to 55  
1 to 55  
1 to 55  
1 to 55  
1 to 55  
1 to 55  
1 to 55  
18 [1] nn  
1
This item is masked when not used  
1
*
This item is masked when nil  
NOTES  
*
Certain values are divided by 10 or by 100, so that number of hours or start-  
ups of less then 10 are displayed as 0.  
Pressing the Enter key when alarm code is displayed causes the following  
message to be scrolled:  
“time of alarm” “date of alarm” “full CCN alarm message”  
- “time of alarm”: xxhmm  
- “date”: dd-mm  
When the value is divided by 10 or by 100 it is displayed in turn with “M 10” or  
“M100”.  
- “full CCN alarm message”: up to 64 characters  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.3.14.2 - Description of Runtimes 2 menu  
5 - PRO-DIALOG CONTROL OPERATION  
5.1 - Start/stop control  
ITEM #  
FORMAT  
UNITS  
DESCRIPTION  
0
-
-
When selected this item  
authorises return to the  
previous menu  
The table below summarises the unit control type and stop or  
go status with regard to the following parameters.  
1
nn  
-
Compressor starts for  
compressor with most starts  
during the last hour  
-
Operating type: this is selected using the start/stop button  
on the front of the user interface.  
-
Remote start/stop contacts: these contacts are used when  
the unit is in remote operating type (rEM). See sections  
3.6.2 and 3.6.3.  
2
3
nn  
nn  
-
24 hours average number of  
starts/hour, compressor  
minutes  
Minimum compressor  
operating time during last  
hour  
-
-
CHIL_S_S: this network command relates to the chiller  
start/stop when the unit is in CCN control (CCn). Vari-  
able forced to disable: the unit is halted. Variable forced to  
Enable: the unit runs in accordance with schedule 1.  
Start/Stop schedule: occupied or unoccupied status of the  
unit as determined by the chiller start/stop program  
(Schedule #1). Used when the unit is equipped with an  
optional CCN/clock board, otherwise the chiller occupied  
mode is forced to occupied all the time.  
4
nn  
minutes  
24 hours average minimum  
operating time above  
5 [1]  
6 [1]  
7 [1]  
8 [1]  
nnnn | M 10 | M100 hrs/10 or 100  
nnnn | M 10 hrs/10 or 100  
Boiler operating hours  
Electric heating stage  
operating hours  
nnnn | M 10 | M100 -/10 or 100  
nnnn | M 10 | M100 -/10 or 100  
No. of defrost cycles, circuit  
A
No. of defrost cycles, circuit  
B
-
Master control type. This parameter is used when the  
unit is the master unit in a two chiller lead/lag arrange-  
ment. The master control type determines whether the unit  
is to be controlled locally, remotely or through CCN (this  
parameter is a Service configuration).  
4.3.14.3 - Maintenance menu description  
To be active, the maintenance function must be preset in the  
Service configuration  
-
-
CCN emergency shutdown: if this CCN command is  
activated, it shuts the unit down whatever the active  
operating type.  
ITEM #  
FORMAT  
DESCRIPTION  
0
MAintEnAnCE MEnu  
When selected this item authorises return to  
the previous menu.  
1 [1]  
2 [1]  
3 [1]  
4 [1]  
5 [1]  
Accessible with the Service password.  
For future use  
General alarm: the unit is totally stopped due to failure.  
For future use  
ALErt  
Water loop rate to low  
nnn/ALErt  
Next primary pump maintenance operation in  
nnn days. 'ALErt' is displayed, when the delay  
before maintenance has elapsed.  
6 [1]  
7 [1]  
nnn/ALErt  
nnn/ALErt  
Next secondary pump maintenance operation  
in nnn days. 'ALErt' is displayed, when the  
delay before maintenance has elapsed.  
Next water filter maintenance operation in nnn  
days. 'ALErt' is displayed, when the delay  
before maintenance has elapsed.  
1
This item is masked when not used.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACTIVE OPERATING TYPE  
LOFF L-C L-SC rEM  
STATUS OF PARAMETERS  
CONTROL UNIT  
TYPE  
MODE  
CCN MASt CHIL_S_S REMOTE  
MASTER  
START/STOP CCN  
GENERAL  
START/STOP CONTROL  
SCHEDULE  
MODE  
EMERGENCY ALARM  
SHUTDOWN  
CONTACT  
TYPE  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Enable  
-
-
-
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
On  
On  
On  
On  
On  
On  
On  
On  
On  
On  
On  
-
-
-
-
-
Yes  
-
-
Active  
-
-
-
-
Local  
Local  
Remote  
Remote  
CCN  
Active  
-
-
-
Unoccupied  
-
-
Active  
Active  
-
Off  
-
-
-
-
-
Unoccupied  
-
-
Active  
Active  
Disable  
-
-
-
-
-
-
-
-
-
Unoccupied  
Unoccupied  
-
-
CCN  
Active  
Active  
Active  
-
Local  
-
Local  
Remote  
Remote  
CCN  
Off  
Remote  
-
-
Remote  
Unoccupied  
-
-
Active Disable  
-
CCN  
-
Active  
-
-
CCN  
Unoccupied  
-
-
CCN  
Active  
-
-
-
Disable  
Disable  
Disable  
Disable  
Disable  
Disable  
Disable  
Disable  
Disable  
Disable  
Disable  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
No  
Local  
Local  
Remote  
Remote  
Remote  
CCN  
Active  
-
-
-
Occupied  
Occupied  
Occupied  
Occupied  
Occupied  
Occupied  
Occupied  
Occupied  
Occupied  
Occupied  
Active  
Active  
Active  
-
On cooling  
-
-
On heating  
-
-
On auto  
-
Active  
Enable  
-
-
Active  
Active  
Active  
Active  
-
-
-
-
-
Local  
Remote  
Remote  
Remote  
CCN  
Local  
Remote  
Remote  
Remote  
CCN  
On cooling  
On heating  
On auto  
-
Active Enable  
5.2 - Heating/cooling/standby operation  
5.2.2 - Heating/cooling/auto selection  
The table below summarises the unit heating/cooling opera-  
tion, based on the following parameters:  
5.2.1 - General  
The heating/cooling/standby selection applies to all units. But  
only 30RA/RY (liquid chillers) units, controlling a boiler and  
30RH/RYH (heat pumps) units can change over to heating  
mode. Heating/cooling control can be automatic or manual.  
-
Control type: indicates whether the unit operates in local,  
remote or CCN mode. See section 5.1.  
Unit on/off status: indicates whether the unit is shut  
down (not authorised to start) or in operation (or  
authorised to start).  
-
In automatic mode the outdoor temperature determines the  
heating/cooling/standby changeover based on the two  
threshold values configured by the user (see Setpoint menu for  
cooling and heating mode changeover thresholds). If the unit is in  
standby it does not cool or heat, and no compressor can be  
activated. The diagram below summarises the operating  
principle in automatic mode.  
-
-
-
-
Heating/cooling/auto selection in local mode: operating  
mode selected via the user interface. See Information  
menu.  
Remote heating/cooling contacts: these contacts are only  
active if the unit is under remote control. See sections  
3.6.2 and 3.6.3.  
HC_SEL: this network command permits heating/  
cooling/auto control, if the unit is in CCN operating  
mode.  
Outdoor temperature: determines the operation, if the  
unit is in automatic heating/cooling/standby changeover  
mode.  
HEATING  
STANDBY  
COOLING  
Outdoor  
temperature  
Heating  
Cooling  
threshold*  
threshold  
*
This threshold does not apply to cooling only units that do not control a boiler.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PARAMETER STATUS  
HEATING/COOLING REMOTE HEATING/ HC_SEL  
ON/OFF  
STATUS  
CONTROL  
TYPE  
OUTDOOR TEMPERATURE  
OPERATING  
MODE  
SELECTION IN  
LOCAL MODE  
COOLING CONTACTS  
Off  
On  
On  
On  
On  
On  
On  
On  
On  
On  
On  
On  
On  
On  
On  
On  
-
-
-
-
-
Cooling  
Cooling  
Heating  
Cooling  
Heating*  
Standby  
Cooling  
Heating  
Cooling  
Heating*  
Standby  
Cooling  
Heating  
Cooling  
Heating*  
Standby  
Local  
Local  
Local  
Local  
Local  
Remote  
Remote  
Remote  
Remote  
Remote  
CCN  
Cooling  
-
-
-
Heating  
-
-
-
Auto  
-
-
> Cooling threshold  
Auto  
-
-
< Heating threshold  
Auto  
-
-
Between cooling and heating thresholds  
-
-
-
-
-
-
-
-
-
-
Cooling mode  
-
-
Heating mode  
-
-
Auto mode  
-
> Cooling threshold  
Auto mode  
-
< Heating threshold  
Auto mode  
-
Between cooling and heating thresholds  
-
-
-
-
-
Cooling  
Heating  
Auto  
Auto  
Auto  
-
CCN  
-
CCN  
> Cooling threshold  
CCN  
< Heating threshold  
CCN  
Between cooling and heating thresholds  
*
Does not apply to cooling only units that do not control a boiler.  
5.3 - Evaporator water pump control  
5.4 - Control interlock contact  
The unit can control one or two evaporator water pumps. The  
evaporator water pump is turned on when this option is  
configured (see User configuration) and when the unit is in one  
of the on modes described above or in delay mode. Since the  
minimum value for the delay at start-up is 1 minute  
(configurable between 1 and 15 minutes), the pump will run  
for at least one minute before the first compressor starts. The  
pump is kept running for 20 seconds after the unit goes to stop  
mode. The pump keeps working when the unit switches from  
heating to cooling mode or vice-versa. It is turned off if the  
unit is shut down due to an alarm unless the fault is a frost  
protection error. The pump can be started in particular  
operating conditions when the evaporator heater is active (see  
section 5.5). See section 5.14 for the particular evaporator  
pump control for the follower unit (master/slave assembly).  
This contact checks the status of a loop (water flow switch and  
customer safety loop, see section 3.6). It prevents the unit from  
starting if it is open when the delay at start-up has expired. This  
open contact leads to an alarm shut-down, if the unit is  
running.  
5.5 - Evaporator antifreeze protection  
The heater for the evaporator and water pump cycling (for units  
with a pump) can be energised to protect the evaporator, if it  
can be damaged by freezing, when the unit is shut down for a  
long time at low outdoor temperature.  
NOTE: Evaporator heater control parameters can be  
modified, using the Service configuration.  
If two pumps are controlled and the reversing function has  
been selected (see User 1 configuration), the control tries to  
limit the pump run time delta to the configured pump change-  
over delay. If this delay has elapsed, the pump reversing  
function is activated, when the unit is running. During the  
reversing function both pumps run together for two seconds.  
5.6 - Control point  
The control point represents the water temperature that the unit  
must produce. The inlet water is controlled by default, but the  
outlet water can also be controlled (requires a Service  
configuration modification).  
If a pump has failed and a secondary pump is available, the  
unit is stopped and started again with this pump.  
Control point = active setpoint + reset  
The control provides a means to automatically start the pump  
each day at 14.00 hours for 2 seconds when the unit is off. If  
the unit is fitted with two pumps, the first pump is started on  
odd days and the second pump is started on even days. Starting  
the pump periodically for few seconds increases the life-time  
of the pump bearings and the tightness of the pump seal.  
5.6.1 - Active setpoint  
Two setpoints can be selected as active in cooling mode and  
three in heating mode. Usually, the second cooling setpoint is  
used for unoccupied periods or for ice storage (brine unit). The  
second setpoint in heating mode is used for unoccupied  
periods, and the third heating setpoint is used for holiday  
periods or public holidays. Depending on the current opera-  
tions, the active setpoint can be selected by choosing the item  
in the Information menu, with the user’s volt-free contacts,  
with network commands or with the setpoint timer program  
(schedule 2).  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The following table summarises the possible selections  
depending on the control types (local, remote or CCN) and the  
following parameters:  
REMOTE OPERATING MODE - DUAL-CIRCUIT UNITS  
PARAMETER STATUS  
HEATING/COOLING CONTROL SCHEDULE 2  
ACTIVE SETPOINT  
OPERATING MODE  
CONTACTS STATUS  
-
Setpoint select in local control: item #12 of the Infor-  
mation menu permits selection of the active setpoint, if  
the unit is in local operating type.  
Cooling  
sp 1  
sp 2  
sp 3  
Auto  
Auto  
sp 1  
sp 2  
sp 3  
Auto  
Auto  
Auto  
-
Cooling setpoint 1  
Cooling setpoint 2  
Cooling setpoint 2  
Cooling setpoint 1  
Cooling setpoint 2  
Heating setpoint 1  
Heating setpoint 2  
Heating setpoint 3  
Heating setpoint 1  
Heating setpoint 2  
Heating setpoint 3  
Cooling  
-
Cooling  
-
-
-
Heating/cooling operating mode  
Cooling  
Occupied  
Control contacts: status of control contacts 5 and 6 (dual-  
circuit units only). These contacts are only active if the  
unit is in remote control operating type. See section 3.6.6.  
Control contact 3: status of control contact 3 (single-  
circuit units only). See section 3.6.4.  
Contol contact 3 selection: this selection, only used for  
single-circuit units, indicates if contact 3 is used for dual  
setpoint control or for demand limit control (see User  
Configuration menu).  
Cooling  
Unoccupied  
Heating  
-
Heating  
-
-
-
Heating  
-
Heating  
Occupied  
Unoccupied  
Holiday  
Heating  
Heating  
CCN OPERATING MODE  
PARAMETER STATUS  
-
Schedule 2 status: schedule for setpoint selection. See  
section 4.3.11.6.  
HEATING/COOLING SCHEDULE 2  
OPERATING MODE STATUS  
ACTIVE SETPOINT  
Cooling  
Cooling  
Heating  
Heating  
Heating  
Occupied  
Unoccupied  
Occupied  
Unoccupied  
Holiday  
Cooling setpoint 1  
Cooling setpoint 2  
Heating setpoint 1  
Heating setpoint 2  
Heating setpoint 3  
LOCAL OPERATING MODE  
PARAMETER STATUS  
HEATING/COOLING LOCAL  
OPERATING MODE SETPOINT STATUS  
SELECTION  
SCHEDULE 2 ACTIVE SETPOINT  
Cooling  
Cooling  
Cooling  
Cooling  
Heating  
Heating  
Heating  
Heating  
Heating  
Heating  
sp 1  
sp 2  
Auto  
Auto  
sp 1  
sp 2  
sp 3  
Auto  
Auto  
Auto  
-
Cooling setpoint 1  
Cooling setpoint 2  
Cooling setpoint 1  
Cooling setpoint 2  
Heating setpoint 1  
Heating setpoint 2  
Heating setpoint 3  
Heating setpoint 1  
Heating setpoint 2  
Heating setpoint 3  
-
Occupied  
Unoccupied  
-
-
-
Occupied  
Unoccupied  
Holiday  
REMOTE OPERATING MODE - SINGLE-CIRCUIT UNITS  
PARAMETER STATUS  
ACTIVE SETPOINT  
HEATING/COOLING  
OPERATING MODE  
CONTROL CONTACT 3  
SELECTION  
CONTROL CONTACT 3  
SCHEDULE 2 STATUS  
Cooling  
Cooling  
Cooling  
Cooling  
Heating  
Heating  
Heating  
Heating  
Heating  
Setpoint  
Setpoint 1  
-
Cooling setpoint 1  
Cooling setpoint 2  
Cooling setpoint 1  
Cooling setpoint 2  
Heating setpoint 1  
Heating setpoint 2  
Heating setpoint 1  
Heating setpoint 2  
Heating setpoint 3  
Setpoint  
Setpoint 2  
-
Demand limit  
Demand limit  
Setpoint  
-
Occupied  
Unoccupied  
-
-
Setpoint 1  
Setpoint  
Setpoint 2  
-
Demand limit  
Demand limit  
Demand limit  
-
-
-
Occupied  
Unoccupied  
Holiday  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.6.2 - Reset  
5.7 - Demand limit  
Reset means that the active setpoint is modified so that less  
machine capacity is required (in cooling mode, the setpoint is  
increased, in heating mode it is decreased). This modification is  
in general a reaction to a drop in the load. For the Pro-Dialog  
control system, the source of the reset can be configured in the  
User 1 configuration: it can be provided either by the outdoor  
temperature (that gives a measure of the load trends for the  
building) or by the return water temperature (delta T that gives  
an average building load). In response to a drop in the outdoor  
temperature or to a drop in delta T, the cooling setpoint is  
normally reset upwards in order to optimise unit performance:  
Generally, demand limit is used by an energy management  
system to restrict the unit electricity consumption. The PRO-  
DIALOG control system enables the capacity of the unit to be  
limited by means of user-controlled volt-free contacts. Single-  
circuit units only have one contact (control contact 3), available in  
the User Configuration function for demand limiting or setpoint  
selection. Dual-circuit units have two volt-free contacts that  
permit several limit levels. The capacity of the unit cannot exceed  
the demand limit setpoint activated by the position of the  
contacts (see section 3.6.4 and 3.6.5 for the contact description).  
The demand limit setpoints are adjustable via the setpoint menu.  
In both cases the reset parameters, i.e. slope, source and  
maximum value, are configurable in the Setpoints menu (see  
section 4.3.8). Reset is a linear function based on three  
parameters.  
The demand limit is active in all operating types: Local,  
Remote or CCN. However in CCN operating type, demand  
limit can be controlled directly with the aid of CCN commands.  
A reference at which reset is zero (outdoor temperature or  
delta T - no reset value).  
A reference at which reset is maximum (outdoor  
temperature or delta T - full reset value).  
The maximum reset value.  
A limitation value of 100% means that the unit may call upon  
the full array of its capacity stages.  
5.8 - Night mode  
Reset example in cooling mode  
The night period is defined (see User configuration) by a start  
time and an end time that are the same for each day of the  
week. During the night period, the fan runs at low speed, if  
permitted by the current operating conditions. In addition, the  
user can reduce the unit capacity (but a minimum capacity  
value can be configured).  
5.9 - Capacity control  
This function adjusts the number of active compressors to keep  
the heat exchanger water temperature at its setpoint. The  
precision with which this is achieved depends on the capacity  
of the water loop, the flow rate, the load, and the number of  
stages available on the unit. The control system continuously  
takes account of the temperature error with respect to the  
setpoint, as well as the rate of change in this error and the  
difference between entering and leaving water temperatures, in  
order to determine the optimum moment at which to add or  
withdraw a capacity stage. If the same compressor undergoes  
too many starts (per hour) or runs below one minute each time  
it is started this automatically brings about reduction of  
compressor starts, which makes leaving water temperature  
control less precise. In addition, the high pressure, low pressure  
or defrost unloading functions can also affect the temperature  
control accuracy. Compressors are started and stopped in a  
sequence designed to equalise the number of start-ups (value  
weighted by their operating time).  
Outdoor temperature (OAT)  
Evaporator Delta T  
Legend  
A
B
C
D
Maximum reset value  
OAT or delta T for no reset  
OAT or delta T for full reset  
Building Load  
NOTE: Circuits with 3 compressors (reversible heat pump  
units) only provide 2 capacity stages (2 compressors are  
started/stopped together).  
5.10 - Head pressure control  
Condensing pressure control is automatically ensured by a two-  
speed fan and can also be ensured by an additional fan on each  
circuit (no adjustment).  
Fanstart-up:  
ATTENTION: In accordance with the operating conditions  
the fans can be cleaned periodically. A fan can start at any  
time, even if the unit has been shut down.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The master/slave assembly can operate with constant or  
variable flow. In the case of variable flow each machine must  
control its own water pump and automatically shut down the  
pump, if the cooling capacity is zero. For constant flow  
operation the pumps for each unit are continuously operating, if  
the system is operating. The master unit can control a common  
pump that will be activated, when the system is started. In this  
case the slave unit pump is not used.  
5.11 - Defrost function  
Defrost is activated, when the unit is in heating mode, in order  
to reduce frost build-up on the air heat exchanger. The defrost  
cycle can only be applied to one circuit at a time. During the  
defrost cycle the fans of that circuit are stopped, and the four-  
way refrigerant valve is reversed, forcing the circuit to cooling  
mode. The fan can temporarily be restarted during the defrost  
cycle. The defrost cycle is fully automatic and does not require  
any setting. A condensate heater prevents ice formation at the  
bottom of the heat exchangers, if the defrost cycles are taking  
place at low outdoor temperature.  
All control commands to the master/slave assembly (start/stop,  
setpoint, heating/cooling operation, load shedding, etc.) are  
handled by the unit which is configured as the master, and  
must therefore only be applied to the master unit. They will be  
transmitted automatically to the slave unit. The master unit can  
be controlled locally, remotely or by CCN com-mands.  
Therefore to start up the assembly, simply validate the Master  
operating type (MASt) on the master unit. If the Master has  
been configured for remote control then use the remote volt-  
free contacts for unit start/stop. The slave unit must stay in  
CCN operating type continuously. To stop the master/slave  
assembly, select Local Off (LOFF) on the master unit or use  
the remote volt-free contacts if the unit has been configured for  
remote control.  
5.12 - Additional electric heater stage control  
The heat pump units can control up to four additional electric  
heating stages.  
The electric heating stages are activated to complement the  
heating capacity when the following conditions are satisfied:  
-
The unit uses 100% of the available heating capacity, or the  
unit is limited in its operation by a protection mode (low  
suction temperature, hot gas or defrost sequence in  
progress protection), and in all cases cannot satisfy the  
heating load.  
One of the functions of the master unit (depending on its  
configuration) may be the designation, whether the master or  
slave is to be the lead machine or the follower. The roles of  
lead machine and follower will be reversed when the differ-  
ence in running hours between the two units exceeds a con-  
figurable value, ensuring that the running times of the two  
units are automatically equalised. The changeover between lead  
machine and follower may take place when the assembly is  
started up, or even whilst running. The running time balancing  
function is not active if it has not been configured: in this case  
the lead machine is always the master unit.  
-
-
The outdoor temperature is below a configured threshold  
(see User 1 configuration).  
The unit demand limit is not active.  
The user may configure the last available electric heating stages  
as a safety stage. In this case, the safety stage is only activated in  
addition to the other stages if there is a machine fault, preventing  
the use of the heating capacity. The other electric heating stages  
will continue to operate as described above.  
5.13 - Control of a boiler  
The lead machine will always be started first. When the lead  
machine is at its full available capacity, start-up delay (con-  
figurable) is initialised on the follower. When this delay has  
expired, and if the error on the control point is greater than  
1.7°C, the follower unit is authorised to start and the pump is  
activated. The follower will automatically use the master unit  
active setpoint. The lead machine will be held at its full  
available capacity for as long as the active capacity on the  
follower is not zero. When the follower unit receives a com-  
mand to stop, its evaporator water pump is turned off with 20  
seconds delay.  
NOTE: The control of the electric heating stages or of a  
boiler is not authorised for slave units.  
The unit can control the start-up of a boiler, if it is in heating  
mode. When the boiler is operating, the unit water pump is  
stopped.  
A heat pump unit and a boiler cannot operate together. In this  
case the boiler output is activated in the following conditions:  
-
The unit is in heating mode, but a fault prevents the use of  
the heat pump capacity.  
In the event of a communication fault between the two units, each  
shall return to an autonomous operating mode until the fault is  
cleared. If the master unit is halted due to an alarm, the slave  
unit is authorised to start without prior conditions.  
-
The unit is in heating mode, but works at a very low  
outdoor temperature, making the heat pump capacity  
insufficient. The outdoor air temperature threshold for use  
of the boiler is fixed at -10°C, but this value can be  
adjusted in the User 1 menu.  
5.15 - Controlling Pro-Dialog units with a System  
Manager  
5.14 - Master/slave assembly  
Up to eight PRO-DIALOG units (or System Manager  
compatible units) can be controlled by one control module of  
the FSM, CSM III or HSM type which can handle multitasking  
of control functions such as starting units in sequence.  
Two PRO-DIALOG units can be linked to produce a master/  
slave assembly. The two machines are interconnected over the  
CCN bus. All parameters required for the master/slave function  
must be configured through the Service configuration menu.  
Master/slave operation requires the connection of a temperature  
probe at the common manifold on each machine, if the heat  
exchanger leaving water temperature is controlled.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 - DIAGNOSTICS - TROUBLESHOOTING  
6.1 - General  
This means that an alarm can be reset without stopping the  
machine. In the event of a power supply interrupt, the unit  
restarts automatically without the need for an external com-  
mand. However, any faults active when the supply is inter-  
rupted are saved and may in certain cases prevent a circuit or a  
The PRO-DIALOG control system has many fault tracing aid  
functions. The local interface and its various menus give access unit from restarting.  
to all unit operating conditions. The test function makes it  
possible to run a quick test of all devices on the unit. If an  
operating fault is detected, an alarm is activated and an alarm  
code is stored in the Alarm menu.  
A manual reset must be run from the main interface using the  
following procedure:  
RESET OF ACTIVE ALARMS  
OPERATION  
ITEM NUMBER  
2-DIGIT DISPLAY 4-DIGIT DISPLAY BUTTON LED  
ITEM VALUE  
PRESS MENU  
6.2 - Displaying alarms  
Hold down the MENU  
button until the LED for  
alarms lights. The 4-  
digit display shows the  
number of active  
The alarm LEDs on the summary interface (see section 4.1)  
give a quick display of the status of each circuit and the unit as  
a whole.  
0
alarms (2 in this  
example).  
0
0
2 ALArM  
-
A flashing LED shows that the circuit is operating but  
there is an alarm.  
Press the Enter button  
until "rESEt ALARrM" is  
shown in the 4-digit  
display.  
rESEt ALArM  
-
A steady LED shows that the circuit has been shut down  
due to a fault.  
The Alarm menu on the main interface displays up to 5 fault  
codes that are active on the unit.  
Press the Enter button  
again to validate the  
reset. "Good" is  
0
Good  
then, 2 AL  
then, no ALArM  
displayed for 2 seconds  
then, "2 ALArM" and  
then, "no ALArM".  
6.3 - Resetting alarms  
When the cause of the alarm has been corrected the alarm can  
be reset, depending on the type, either automatically on return  
to normal, or manually when action has been taken on the unit.  
Alarms can be reset even if the unit is running.  
6.4 - Alarm codes  
The following list gives a complete description of each alarm code and its possible cause.  
ALARM CODE DESCRIPTIONS  
ALARM ALARM NAME  
CODE  
ALARM DESCRIPTION  
ACTION TAKEN BY  
THE CONTROL  
RESET TYPE  
PROBABLE CAUSE  
1
Compressor A1 failure  
Motor safety input has opened due to  
compressor overtemperature protection.  
Compressor is shut  
down  
Manual  
Compressor overheat  
2
3
5
6
7
9
Compressor A2 failure  
Compressor A3 failure  
Compressor B1 failure  
Compressor B2 failure  
Compressor B3 failure  
As above  
As above  
As above  
As above  
As above  
As above  
Unit shut down  
As above  
As above  
As above  
As above  
As above  
As above  
As above  
As above  
As above  
As above  
As above  
As above  
As above  
As above  
Heat exchanger leaving fluid  
thermistor failure  
Thermistor outside range  
Automatic, if temp. measured by sensor Faulty thermistor, wiring error or  
returns to permitted range of values  
disconnection  
10 Heat exchanger entering fluid  
As above  
As above  
As above  
As above  
As above  
As above  
As above  
thermistor failure  
11  
CHWS fluid thermistor failure  
(master/slave)  
As above  
As above  
As above  
12 Defrost sensor fault, circuit A  
Circuit shut down, if unit As above  
is in heating mode  
13 Defrost sensor fault, circuit B  
14 OAT sensor failure  
As above  
As above  
As above  
As above  
As above  
As above  
As above  
As above  
15 Discharge pressure transducer Voltage delivered by the sensor is incorrect Circuit A shut down  
Automatic if the voltage delivered by the Defective transducer, wiring fault  
sensor returns to normal  
failure, Circuit A  
16 Discharge pressure transducer Value read by the sensor is outside range  
Circuit B shut down  
As above  
As above  
failure, Circuit B  
17 Suction pressure transducer  
Voltage delivered by the sensor is incorrect Circuit A shut down  
As above  
As above  
failure, Circuit A  
18 Suction pressure transducer  
Value read by the sensor is outside range  
Circuit B shut down  
As above  
As above  
failure, Circuit B  
21 CCN/clock board failure  
The clock board is no longer detected  
Unit shut down  
Automatic if board is detected again  
Defective CCN/clock board  
22 Loss of communication with  
Communication has been lost with the slave Circuit B shut down  
board (circuit B control)  
Automatic if communication is re-  
established  
Bus wiring fault, wrong software in slave  
board or defective slave board  
slave board  
23 Loss of communication with  
Communication has been lost with the  
compressor A3 + B3 control board  
Compressors A3 + B3  
shut down  
As above  
As above  
compressor slave board  
24 Loss of communication with PD- Communication has been lost with the  
4 x DO slave board electric heating stage control board  
Electric heating stages As above  
shut down  
As above  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ALARM CODE DESCRIPTIONS (continued)  
ALARM ALARM NAME  
CODE  
ALARM DESCRIPTION  
ACTION TAKEN BY  
THE CONTROL  
RESET TYPE  
PROBABLE CAUSE  
30 Low refrigerant pressure failure, Circuit running and the suction pressure  
circuit A below threshold  
Circuit shut down  
Automatic when pressure returns to  
normal and if the same fault has not  
occurred the same day (machine  
equipped with CCN/clock board, If not,  
manual)  
Shortage of refrigerant, filter blocked or  
faulty pressure sensor  
31 Low refrigerant pressure failure, As above  
As above  
As above  
As above  
circuit B  
32 High pressure failure, circuit A  
Circuit running and the discharge pressure Circuit shut down  
exceeds the high pressure trip point  
Manual, the high pressure switch must  
be reset manually with the push-button  
located on or in the pressure switch  
Fan circuit fault, high condenser  
entering air temperature  
33 High pressure failure, circuit B  
As above  
As above  
As above  
As above  
As above  
As above  
34 Reverse compressor rotation,  
One circuit compressor runs in reverse  
rotation  
Incorrect compressor wiring  
circuit A  
35 Reverse compressor rotation,  
As above  
As above  
As above  
As above  
circuit B  
36 Water heat exchanger frost  
The heat exchanger entering or leaving  
water sensor is below the frost trip point  
Unit shut down  
Automatic if the same alarm has not  
tripped the same day (machine equipped  
with CCN/clock board, If not, manual)  
Low water flow or defective thermistor  
protection  
37 Repeated low evaporator  
More than 6 successive circuit capacity  
Circuit shut down  
Manual  
Faulty pressure sensor, clogged filter or  
low refrigerant charge  
suction temperature unloading, unloads because of low suction temperature  
circuit A override.  
38 Repeated low evaporator suction As above  
As above  
None  
As above  
Automatic  
As above  
temperature unloading, circuit B  
39 Repeated high pressure  
More than 6 successive circuit capacity  
Faulty transducer, high condenser  
entering air temperature, high entering  
water temperature, condenser fouled  
fan flow rate too low.  
unloading, circuit A  
unloads because of high pressure override.  
As above  
40 Repeated high pressure  
As above  
As above  
As above  
As above  
As above  
unloading, circuit B  
41 Repeated high discharge  
temperature unloading in  
heating mode, circuit A  
More than 8 successive circuit capacity  
unloads because of high discharge  
temperature  
Pressure sensor faulty or heat  
exchanger fouled  
42 Repeated high discharge  
temperature unloading in  
heating mode, circuit B  
As above  
As above  
As above  
As above  
As above  
As above  
As above  
As above  
As above  
43 Repeated low suction  
temperature unloading in  
heating mode, circuit A  
More than 8 successive circuit capacity  
unloads because of low suction temperature  
Pressure sensor faulty, filter obstructed,  
shortage of refrigerant, heat exchanger  
fouled or fan faulty.  
44 Repeated low suction  
temperature unloading in  
heating mode, circuit B  
As above  
As above  
45 Low heat exchanger entering  
water temperature in heating  
mode  
Heat exchanger temperature is too low (less Unit shut down  
than 10°C), preventing unit start-up  
As above  
46 Safety interlock open  
Safety interlock not closed before end of the Unit prevented to start  
Manual  
Manual  
Evaporator pump control or water flow  
switch failure  
start-up delay or opens during operation  
or shut down  
47 Pump #1 fault  
Evap. water pump run contact opens while Unit shut down  
the pump has received a command to be on  
Pump overheat, incorrect pump  
connection  
48 Pump #2 fault  
As above  
Unit shut down  
Unit shut down  
Manual  
Manual  
As above  
49 CCN emergency stop  
CCN command received to shutdown the  
unit  
Network command  
50 Loss of communication with  
The unit is controlled by a System Manager Unit returns to  
and communication with this module is lost autonomous operating  
Automatic when communication is re-  
established  
Defective CCN bus wiring or system  
module failure  
System Manager  
for more than 2 minutes  
mode  
51 Communication failure with the The master/slave link is broken due to a  
As above  
As above  
Automatic  
As above  
master or the slave unit  
loss of communication between the two  
units for more than 2 minutes  
52 Initial factory configuration  
All factory parameters are zero  
Unit prevented to start  
As above  
No factory configuration  
required  
53 Illegal factory configuration  
Wrong factory configuration  
Automatic  
Automatic  
Factory configuration error  
54 Master/slave configuration error Wrong master/slave configuration  
Master/slave control  
disabled  
Master or slave configuration error  
Maintenance alerts  
A maintenance alert is active  
None  
Manual  
55-2 Water loop flow rate too low  
55-4 Maintenance delay, pump 1,  
elapsed  
55-5 Maintenance delay, pump 2,  
elapsed  
55-6 Maintenance delay, water filter,  
elapsed  
Order No. 13444-76, 06.2005. Supersedes order No.: 13429-76, 06.2004.  
Manufacturer reserves the right to change any product specification without notice.  
Manufactured by: Carrier s.a., Montluel, France.  
Printed in the Netherlands on chlorine-free paper.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

BenQ Laptop 2000 Series User Manual
Black Decker Carpet Cleaner 90503695 User Manual
Bosch Appliances Laptop D5500CU User Manual
Bosch Appliances Washer WFMC6401UC User Manual
Brother Answering Machine PT 9400 User Manual
Canon Digital Camera 0206B001 User Manual
Canon Switch M15 155 User Manual
Carrier Furnace 58UVB User Manual
Celestron Telescope NexStar GT User Manual
Chauvet Home Safety Product DMX 750 User Manual