Campbell Hausfeld Network Card SDM CVO4 User Manual

SDM-CVO4  
4-Channel Current/Voltage  
Output Module  
User Guide  
Issued: 13.3.08  
Copyright 2001-2007 Campbell Scientific Inc.  
©
Printed under Licence by Campbell Scientific Ltd.  
CSL 436  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Guarantee  
This equipment is guaranteed against defects in materials and  
workmanship. This guarantee applies for twelve months from date of  
delivery. We will repair or replace products which prove to be defective  
during the guarantee period provided they are returned to us prepaid. The  
guarantee will not apply to:  
Equipment which has been modified or altered in any way without the  
written permission of Campbell Scientific  
Batteries  
Any product which has been subjected to misuse, neglect, acts of God  
or damage in transit.  
Campbell Scientific will return guaranteed equipment by surface carrier  
prepaid. Campbell Scientific will not reimburse the claimant for costs  
incurred in removing and/or reinstalling equipment. This guarantee and  
the Company’s obligation thereunder is in lieu of all other guarantees,  
expressed or implied, including those of suitability and fitness for a  
particular purpose. Campbell Scientific is not liable for consequential  
damage.  
Please inform us before returning equipment and obtain a Repair Refer-  
ence Number whether the repair is under guarantee or not. Please state the  
faults as clearly as possible, and if the product is out of the guarantee  
period it should be accompanied by a purchase order. Quotations for re-  
pairs can be given on request.  
When returning equipment, the Repair Reference Number must be clearly  
marked on the outside of the package.  
Note that goods sent air freight are subject to Customs clearance fees  
which Campbell Scientific will charge to customers. In many cases, these  
charges are greater than the cost of the repair.  
Campbell Scientific Ltd,  
Campbell Park, 80 Hathern Road,  
Shepshed, Loughborough, LE12 9GX, UK  
Tel: +44 (0) 1509 601141  
Fax: +44 (0) 1509 601091  
Email: support@campbellsci.co.uk  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
1. Introduction..................................................................1  
2. Specifications ..............................................................2  
2.1 General Specifications..............................................................................2  
2.2 Output Specifications................................................................................3  
2.3 Isolation Specifications.............................................................................3  
3. Power Considerations.................................................4  
4. Installation....................................................................4  
4.1 Connection to a Datalogger ......................................................................4  
4.2 Output Device Connections......................................................................6  
4.2.1 Voltage Output Mode .....................................................................6  
4.2.2 Current Output Mode......................................................................6  
4.2.3 Shield and Ground Connections .....................................................8  
4.2.4 Output Terminal Connectors...........................................................8  
4.3 Output Mode Setting ................................................................................8  
4.4 SDM Address Setting ...............................................................................9  
4.5 Safety Considerations.............................................................................10  
5. General Principles of Use.........................................12  
5.1 Voltage or Current Signalling.................................................................12  
5.2 Providing Excitation Supplies to Sensors...............................................12  
6. Datalogger Instruction (103).....................................13  
6.1 Edlog Instruction 103 .............................................................................13  
6.2 Edlog Program Examples .......................................................................15  
6.2.1 Voltage and 0-20 mA Current Output Modes...............................15  
6.2.2 Restricted Range Current Output Modes (4-20 mA) ....................17  
6.2.3 Providing Isolated Power Supplies to Sensor ...............................18  
6.3 CRBasic SDM-CVO4 Instruction ..........................................................20  
6.4 SDM-CVO4 Instruction Example...........................................................21  
Figures  
1. SDM-CVO4................................................................................................1  
4-1. Use of the Spring-Loaded Terminal Blocks (Top Position)....................5  
4-2. Use of the Spring-Loaded Terminal Blocks (Front Position)..................5  
4-3. Location of Jumpers on Circuit Board ....................................................9  
4-4. Address Selection Switch......................................................................10  
i
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Tables  
4-1. Datalogger to SDM-CVO4 Connections.................................................4  
4-2. Switch Position and Addresses .............................................................10  
6-1. Description of Instruction 103 ..............................................................14  
ii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SDM-CVO4 4-Channel Current/Voltage  
Output Module  
The SDM-CVO4 is a synchronously addressed datalogger peripheral designed to allow the  
datalogger to output variable voltage or current signals under program control.  
Figure 1. SDM-CVO4 (shown without mounting brackets)  
1. Introduction  
The SDM-CVO4 expands the analogue output capability of Campbell Scientific  
dataloggers. Each output can be set to 0-10V or 0-20mA by the datalogger. The  
output can be scaled and limited to 4-20mA by the datalogger program if required  
by the application.  
Typical applications will include driving remote ‘current-loop’ display units, re-  
transmitting measured values to industrial control systems which have current or  
high voltage inputs, sending control signals to valve controllers and providing  
excitation voltages or currents to external sensors.  
Each output is isolated both from the datalogger and the other channels on the  
CVO4, thereby avoiding ground loop problems that might otherwise occur.  
In the current mode the output can either act as a 2-wire current controller, where  
the loop is powered from a remote voltage source, or it can be used to generate a  
0-20 mA current source using a voltage output derived from its own power  
supply.  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
SDM-CVO4 4-Channel Current/Voltage Output Module  
The SDM-CVO4 is a synchronously addressed datalogger peripheral. Datalogger  
control ports 1, 2 and 3 are used to address the SDM-CVO4 and send out data that  
defines the desired voltage/current output of each of the four channels. The output  
levels are set by four values in successive input locations in the datalogger. A total  
of up to sixteen SDM-CVO4s or other SDM peripherals may be connected and  
addressed from the same three ‘SDM’ ports.  
For the CR10/10X, CR23X, CR7 and 21X dataloggers Instruction  
103 is used to control the SDM-CVO4. This was introduced in  
August 1988 for controlling SDM-AO4 functions. (The SDM-AO4  
is an older voltage-output-only peripheral.) Dataloggers purchased  
before this date may use a different instruction.  
NOTE  
The SDM-CVO4 instruction is used with the CR800, CR1000,  
CR3000, and CR5000.  
2. Specifications  
2.1 General Specifications  
Compatible dataloggers: CR10X, CR800, CR1000, CR3000, CR5000, and  
CR7. Also compatible with many retired  
dataloggers such as the CR10, 21X, and CR23X.  
Operating voltage:  
12 VDC nominal (8 V to 16 V)  
Current drain at 12V DC: Typical active quiescent current 27 or 54 mA,  
depending on operating mode (no load on output  
ports). To estimate the total current, add the  
quiescent current to the sum of all output currents  
multiplied by 1.5.  
E.g. if each port is at 10 mA output, the total = 54 +  
(1.5*4*10) = 114 mA. The device can be shut down  
to <0.5 mA with all outputs off.  
Maximum Total SDM cable length: 6 m.  
Operating temperature:  
Size:  
-25°C to +50°C standard (-40 to 80°C optional)  
176 mm wide x 111 mm high x 24 mm deep.  
234 mm wide x 111 mm high x 24 mm deep when  
fitted with brackets for mounting in enclosure, etc.  
Mounting brackets have two holes at 203.2 mm (8")  
spacing for screw fixings.  
Weight:  
370 g  
EMC Status:  
Complies with EN55022-1:1998 and EN50082-  
1:1998  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
Instruction Manual  
2.2 Output Specifications  
Voltage Mode:  
Range: 0 – 10,000 mV  
Resolution: 2.5 mV  
Maximum Output Current: 30 mA per channel.  
Minimum load current: 5 μA if output < 200 mV.  
Accuracy (+23°C) ±0.02% of set voltage,  
+ (± 2.5 mV).  
Accuracy (-25 to +50°C) ±0.13% of set voltage,  
+ (± 2.5 mV).  
Current Mode:  
Range: 0 – 20 mA  
Resolution: 5 μA  
Minimum output current (leakage): 5 μA at +50°C.  
Accuracy (+23°C) ±0.02% of full scale range,  
+ (± 5 μA).  
Accuracy (-25 to +50°C) ±0.1% of full scale range,  
+ (± 5 μA).  
Minimum voltage drop across the internal current  
regulating circuit: 2.5 V at 20 mA current flow.  
Maximum voltage into Id relative to channel ground:  
20 VDC.  
When in current mode, the Vo terminal outputs an  
unregulated voltage source at 15 V nominal (±10%),  
30 mA maximum load.  
Please contact Campbell Scientific for the accuracy  
specification on extended temperature tested units.  
2.3 Isolation Specifications  
Design criteria:  
The unit has an internal isolation barrier and  
components rated to provide signal isolation for  
transients up to 1500 VAC (RMS), 2500 VDC  
nominal. The isolation is between any output and  
the SDM-CVO4 ground connection and between  
individual output channels.  
Protection components are built-in, which will break  
down in a controlled fashion at voltages close to this  
limit (see section 4.5, Safety Issues).  
Tested isolation:  
Each channel of each unit is tested for isolation  
resistance at 500 VDC. Pass level > 10 MΩ.  
Maximum recommended continuous operating voltage:  
240 VAC RMS differential between an output and  
datalogger ground - providing all issues relating to  
local regulations for safe installation and operation  
are followed (see section 4.5, safety issues).  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
SDM-CVO4 4-Channel Current/Voltage Output Module  
3. Power Considerations  
The SDM-CVO4 power requirements are large compared to most Campbell  
Scientific products, especially when driving significant loads. Care must be taken  
to ensure that the power supply can cope with this higher demand.  
Alkaline batteries are not recommended for long term applications.  
The SDM-CVO4 has two internal power supplies, one for channels 1 and 2 and  
one for channels 3 and 4. It will only turn on the power supply for channels 3 and  
4 if sent an instruction that sets the output of those channels. If channels 3 and 4  
are not used the power consumption is approximately 20 mA lower than when all  
outputs are used.  
Where supported by the datalogger, and when the application allows it, the SDM-  
CVO4 can be shut down to reduce its consumption to less than 0.5 mA. In this  
state all outputs are switched off.  
4. Installation  
Prior to installing the device you need to set the output mode (current or voltage)  
of each channel by positioning internal jumpers (see section 4.3). You also need  
to set the SDM address of the module (see section 4.4) and additionally consider  
any safety issues specific to the installation (see section 4.5).  
4.1 Connection to a Datalogger  
For datalogger connections, see Table 4-1, below.  
Table 4-1. Datalogger to SDM-CVO4 Connections  
Connection Order SDM-CVO4  
Datalogger  
Function  
First  
12 V  
or G  
12 V on datalogger or external supply  
or G  
Power  
Second  
Common Ground  
C1  
C2  
C3  
SDM-C1 (CR3000, CR5000) or C1 (other dataloggers) Data  
SDM-C2 (CR3000, CR5000) or C2 (other dataloggers) Clock  
SDM-C3 (CR3000, CR5000) or C3 (other dataloggers) Enable  
Multiple SDM-CVO4s may be wired in parallel by connecting the SDM and  
power connections from one SDM-CVO4 to the next.  
If the total cable length connecting SDM-CVO4s to  
SDM-CVO4s, other SDMS and the datalogger exceeds 6 m, the  
SDM baud rate may need to be reduced to ensure reliable operation.  
Please contact Campbell Scientific for more information.  
NOTE  
The transient protection of the SDM-CVO4 relies on a low resistance path to  
earth. Ensure that the ground return wire has as low a resistance as possible. An  
additional G terminal is provided which can be connected directly to the enclosure  
earth ground terminal to ensure this. Make sure the ground wire from the SDM-  
CVO4 to the datalogger goes to its G terminal and not the AG terminal.  
The SDM-CVO4 uses spring-loaded terminal blocks for the connections to the  
datalogger which provide quick, vibration resistant, connections. To attach wires,  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Instruction Manual  
insert a small screwdriver into either the top or front slot, as appropriate, and push  
to open the terminal spring. Strip any insulation from the wire to give 7 to 9 mm  
bare wire. Push the wire into the opening, and, while holding it in position,  
withdraw the screwdriver to release the spring. The wire will now be firmly held  
in place. See Figures 4-1 and 4-2, below.  
Figure 4-1. Use of the Spring-Loaded Terminal Blocks (Top Position)  
Figure 4-2. Use of the Spring-Loaded Terminal Blocks (Front Position)  
You cannot reliably insert more than one solid-core wire into one terminal  
connector unless the wires are soldered or clamped together. When inserting more  
than one stranded wire, twist the bare ends together before insertion.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
SDM-CVO4 4-Channel Current/Voltage Output Module  
4.2 Output Device Connections  
For each output channel there are four terminals which are labelled Vo, Id plus  
there are two ground ( ) connections per channel. The two ground terminals  
are internally connected; two are provided for convenience.  
4.2.1 Voltage Output Mode  
The Vo terminal is the output for either the preset voltage signal, when the channel  
is set to operate in voltage mode or an unregulated 15 VDC power source in  
current mode.  
In voltage mode the connection to a remote device is a simple two wire  
connection:  
+
V
o
Inputs  
CVO4  
Remote Voltage Input  
4.2.2 Current Output Mode  
The Id terminal acts as the input for the current that is to be controlled. In current  
output mode you arrange to sink current into the terminal with a positive current  
flowing relative to the ground terminals. (In voltage output mode this terminal has  
no function.)  
There are several different possible connections in current mode. As each channel  
is isolated and floating, the method of connection to a remote device is flexible.  
There are two different ways of powering the loop current.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Instruction Manual  
a) The remote device powers the loop, where, depending on the ground  
referencing requirements of that device, the connection can be as shown in  
the diagrams below:  
Remote Voltage  
Source +ve  
V+  
+
Remote Current  
Input  
I
d
CVO4  
V-  
or  
I
V+  
d
CVO4  
+
Remote Current  
Input  
V-  
b) The SDM-CVO4 provides the voltage source to drive the loop. In this case  
the only real option is:  
+
V
I
o
Remote Current  
Input  
CVO4  
d
In both cases you need to consider whether the voltage supply is high enough to  
allow the maximum current to flow (20 mA) through all of the series resistances  
in the current loop. When considering this factor you need to allow for a  
minimum 2.5 V drop between the Id and  
terminal of the  
SDM-CVO4. You need to add this value to the estimated drop of 20 mA flowing  
through the total resistance of the cable in the ‘loop’ plus any voltage drop in the  
remote device (normally the voltage drop across a fixed sense resistor).  
As a simple example, consider the situation where the SDM-CVO4 is powering  
the loop (as in (b) above), then the supply voltage output from Vo is 13.5 (absolute  
minimum). If the remote device has a 250 ohms sense resistor this will drop 5V at  
20mA (using Ohm’s law), which in addition to the  
SDM-CVO4's 2.5 V drop in the loop means the maximum allowable voltage drop  
in the cable of the loop should be 13.5 - 5.0 - 2.5 = 6.0 V. At 20 mA current flow,  
the loop could therefore have a maximum resistance of 300 ohms. Standard 24  
AWG (7/0.2 mm) cable has a typical resistance of 85 ohms per 1000 m. Allowing  
double this resistance to form a loop (there and back), will mean the total cable  
length could be as long as 1700 m before the supply voltage started to limit the  
current flowing.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
SDM-CVO4 4-Channel Current/Voltage Output Module  
4.2.3 Shield and Ground Connections  
It is generally advisable to used shielded (screened) cable when connecting the  
output to any remote system to reduce the chances of noise pickup. The shield  
will only be effective if it is connected to a good ground reference point.  
As a result of the isolation barrier in the SDM-CVO4, the ground terminals  
associated with the output connector of each channel cannot be considered as good  
ground reference points. Therefore it is advisable to make the connection of the  
screen to a good ground point at the remote system rather than the  
SDM-CVO4. Do not connect the screen at both ends of the cable as this may  
result in a ground loop being formed.  
The output circuitry of the SDM-CVO4 includes protective components to  
minimize the chances of damage that can be caused by transients which can be  
induced in the signal cable. The protection clamps the transient voltages to non-  
damaging levels relative to the ground terminals on each output channel.  
If the voltage of that ground point exceeds the datalogger ground potential by  
more than approximately 2500 VDC, a secondary level protector will break down  
to provide a path for energy to discharge to the datalogger ground. The likelihood  
of secondary breakdown can be avoided, if required (perhaps for safety reasons),  
by connecting a wire to the output ground terminals of the SDM-CVO4 to provide  
a low impedance path to ground. In doing this, though, there is a risk that you will  
nullify the effects of the isolation barrier, e.g. if the ground you connect to is the  
same ground to which the datalogger is connected.  
You need to carefully study the ground connections of the entire system when  
connecting a grounding wire to the output ground terminal, both to avoid creating  
a ground loop/referencing problem and also possibly causing a safety issue.  
4.2.4 Output Terminal Connectors  
The output connections use normal, 4-way, screw terminal fixings. These can be  
unplugged for ease of wiring, if required.  
4.3 Output Mode Setting  
An internal jumper sets the output mode for each channel of the SDM-CVO4. The  
output mode can either be voltage or current mode, as described above. To change  
the mode setting, the case must be opened. To do this first disconnect the device  
from any source or power, disconnect the output connections (you can unplug the  
connectors) and then remove the four larger screws from the face of the case  
which has the product name written. Lay the unit on a flat surface and then, after  
taking anti-static precautions, lift off the top half of the case to expose the circuit  
board.  
Then refer to Figure 4-3 below to identify the block of jumpers that control the  
output mode. To operate in current mode, the jumper relevant to the channel  
concerned must be installed between the two jumper pins, as shown. If operating  
in voltage mode, the jumper should not bridge any two pins, but may be stored, if  
required, by fitting it to just one of the pins, leaving the other half unconnected.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Instruction Manual  
Select channel(s) by  
fitting jumper (s)  
between appropriate  
terminals. (Current  
mode only.) Jumper  
shown fitted to  
‘enable’ Channel 4.  
Jumper shown fitted  
in the unconnected  
‘stored’ position.  
Figure 4-3. Location of Jumpers on Circuit Board  
CAUTION  
Do not store the jumpers between any other pins in the block  
as this may switch the module into a factory calibration mode,  
which may result in abnormal operation and change of output  
accuracy.  
The jumper settings can be overridden by the datalogger program, if required,  
using special commands. Please contact Campbell Scientific for details.  
4.4 SDM Address Setting  
Each SDM-CVO4 can have 1 of 16 addresses. The factory-set address is 00.  
Table 4-2 shows switch position and the corresponding address. Figure 4-4 shows  
the position of the switch on the right-hand end of the casing. Note that you will  
have to remove the right-hand mounting bracket to gain access to this switch.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
SDM-CVO4 4-Channel Current/Voltage Output Module  
Table 4-2. Switch Position and Addresses  
Switch Setting  
Base 4 Address  
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
00  
01  
02  
03  
10  
11  
12  
13  
20  
21  
22  
23  
30  
31  
32  
33  
Use a screwdriver to select address  
Figure 4-4. Address Selection Switch  
The address switch has a hexadecimal setting position (0..F). Most datalogger  
instructions require you to enter the address as a base 4 number. Please see your  
datalogger manual for more details of the convention required.  
4.5 Safety Considerations  
Where the potential voltage difference between the datalogger and the  
SDM-CVO4 outputs is considered to be non-hazardous (less than 50 V) then the  
unit can be used as any other peripheral without undue concerns as to the risks to  
safety of the user.  
As with the datalogger, it is essential to ensure that the device has a good  
connection to an earth grounding point to allow the safe discharge of any transient  
voltages and also ensure proper screening of the device. The  
SDM-CVO4 has two G terminals on the black connector which are used for  
connections to the datalogger. One of these can be used to connect the device  
directly to the earth ground point of the enclosure to ensure the lowest resistance  
path to ground.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Instruction Manual  
Where the SDM-CVO4 is going to be used in applications where the potential  
difference between the datalogger and the output terminals exceeds 50 V RMS  
AC, 74 VDC then careful consideration has to be taken to ensure safe operation  
and compliance with local safety regulations. For such applications Campbell  
Scientific does not supply the device as a stand-alone device which will meet all  
safety requirements. The SDM-CVO4 is supplied as a component for the user to  
install in a system that is, itself, designed to comply with such regulations. The  
following guidance is given to help users meet the requirements of such  
regulations.  
The SDM-CVO4 is designed such that the internal safety barrier meets the  
requirements of BS EN 61010-1 (similar to IEC 950). However, the method of  
wire connection and earthing facilities prevents the unit being claimed as  
compliant with such standards, when supplied as a stand-alone unit.  
To meet the safety requirements of most countries, wires carrying hazardous  
voltages, terminated in screw terminals must be housed in an enclosure requiring a  
tool to open it, and the enclosure must have international symbols on the outside  
warning of high voltages. An additional warning label, in the local language, may  
be required stating that the source of hazardous voltage must be turned off before  
the enclosure is opened.  
The exact nature of the enclosure is covered by the standards, but an enclosure  
designed to house electrical equipment will usually meet the requirements.  
Campbell Scientific's ENC 12/14 or 16/18 enclosures meet these requirements if  
fitted with a padlock and with the correct labels on the door.  
It is also necessary to ensure that metal parts on the outside of the enclosure that  
might come in contact with active high voltage circuits are connected to a safety  
ground. The ground lug of Campbell Scientific enclosures is the main issue for the  
above enclosures, but this would, in any case, normally be the point of contact to a  
good ground point.  
Cables that connect to the output of the SDM-CVO4 should have adequate strain  
relief at the point of exit from the enclosure, and the cable and any connectors  
used should be rated to a high enough voltage and assembled in a safe fashion.  
If possible, the external device which is operating at a high voltage relative to  
ground should be configured with an earth leakage breaker system to disconnect it  
from the voltage source in the event of a breakdown of the insulation in the  
system causing a leak to ground.  
With a system made to the above requirements the maximum recommended  
continuous operating voltage between the datalogger and input is 240 VAC. This  
value is derived from the voltage rating of the terminal blocks used and an internal  
suppression capacitor (see below).  
The unit is designed to withstand a transient flash test of 1500 V RMS AC, for  
two seconds. However, you need to be aware of some aspects of the design which  
can influence the results of such a test if made.  
a) To help suppress emissions of electromagnetic interference the isolation  
barrier is bridged by a 1nF, class ‘Y’ safety capacitor. This is rated to  
withstand a 2700V, 2 second flash test, but will fail if exposed to  
voltages in excess of 240 V RMS for long periods.  
b) To provide protection from transients and static for this capacitor and the  
opto-isolation component that bridges the barrier, there is a spark gap  
across the barrier that has a 2500 VDC nominal breakdown voltage. If  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SDM-CVO4 4-Channel Current/Voltage Output Module  
this device is at the low end of its tolerance band (±10%), combined  
with the normal tolerance of flash test devices, then the spark gap could  
fire during a 1500 VAC flash test, which may cause an indication of  
failure. Testing at a slightly lower voltage will confirm whether there is  
a true fault or not.  
If you have any doubts about the safety of your installation please first seek  
advice from your local safety advisor and then Campbell Scientific if you require  
further technical details.  
To ensure safe and correct operation, the SDM-CVO4 must  
be installed where there is no risk of water ingress or  
condensation.  
CAUTION  
5. General Principles of Use  
5.1 Voltage or Current Signalling  
Where the SDM-CVO4 is being used to retransmit measured values from sensors  
to remote displays or measurement systems, the datalogger program would  
normally follow the process of taking measurements and writing the measured  
values into input locations using the same principles as given in the manuals for  
those sensors.  
The measured values would then be scaled using the processing instructions of the  
datalogger, using either Instructions 37 and 34 or Instruction 53 (if available in  
your datalogger). Prior to scaling, or during the scaling calculations, the values  
relating to the four channels of the SDM-CVO4 will normally be written into four  
new sequential input locations, both to match the required inputs for Instruction  
103 and also to preserve the original measurement values for other purposes.  
Instruction 103 would then be executed at the same rate as the measurements have  
been made, to transmit the settings to the SDM-CVO4 and cause the outputs to be  
updated at the same rate. As the required output levels are held in a digital form in  
the SDM-CVO4, there is little advantage in sending data more frequently – the  
only benefit being that it would recover more quickly in the event of a loss of  
power.  
5.2 Providing Excitation Supplies to Sensors  
As mentioned in the introduction to this manual, one application for this device is  
to provide an excitation to a sensor or sensors that are to be measured by the  
datalogger. This may be considered where a sensor requires a precise voltage or  
current excitation which cannot be provided by the datalogger itself, or perhaps  
where exciting the sensor from the datalogger or its power supply would cause a  
common-mode measurement problem. An example of the latter problem is where  
the sensor outputs are not within the common-mode voltage that the datalogger  
will accept (±2.5 V for the CR10X).  
Careful consideration should be made before using an SDM-CVO4 for such a  
function. Not only is it a relatively expensive method, but it can also result in a  
less accurate method of sensor measurement (compared to when the datalogger  
excites the sensors directly) if the precision of the output is critical to the sensor  
accuracy.  
The reason for this is that direct datalogger excitation is a ratiometric  
measurement whereby any drift in the excitation output of the datalogger is  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Instruction Manual  
compensated for. With the SDM-CVO4 as an excitation source, any drift in its  
output accuracy, or of the logger measurement accuracy, can result in a  
combination of those errors. It is worth investigating, therefore, the exact  
requirements of the sensors you wish to use. For instance, on closer inspection of  
the specification of many pressure sensors you will often find the recommendation  
of 10V excitation, but in reality many will accept a lower voltage. If new sensors  
are to be bought for a specific project, it can be worth checking if versions of  
sensors are available that will accept a low voltage excitation.  
There are, however, some sensors that have active components or that have large  
common mode output voltages that require an isolated and/or precise high voltage  
supply within the current output capability of the SDM-CVO4. In this context the  
SDM-CVO4 can be used to provide an isolated supply which can be regulated in  
the range of 0-10,000 mV, a regulated current (0-20 mA) or an unregulated 15 V  
(nominal) supply (by setting current output mode and using the Vo terminal).  
In these applications, if all channels of the SDM-CVO4 are being used for  
exciting sensors, you can use the standby mode between measurements to save  
power. To do this you would send a command (instruction 103 with zero reps -  
see below) to the SDM-CVO4 to shut it down after making the measurements.  
When using this mode you need to allow at least 100ms after turning the  
SDM-CVO4 on again (by using instruction 103 with a non-zero number of reps)  
for the outputs to stabilize, before starting your measurement sequence.  
It is possible that you can power more than one sensor from each output of the  
SDM-CVO4, either by parallel connection in voltage output mode or serial  
connection in current output mode. Make sure, however, that you do not try to  
take more current than available in voltage mode. Additionally you also need to  
check that all outputs from the sensors powered by one channel do not have a  
spread which exceeds the common mode range of the datalogger inputs.  
6. Datalogger Programming  
Our CR10(X), 21X, and CR23X dataloggers use Edlog Instruction 103. Our  
CR800, CR1000, CR3000, and CR5000 use the SDM-CVO4 instruction in  
CRBasic. Both Edlog and CRBasic are provided in PC400 or LoggerNet  
software.  
6.1 Edlog Instruction 103  
To allow full backwards compatibility with older dataloggers and operating  
systems, the SDM-CVO4 is designed to work with the instruction supplied to  
control the SDM-AO4 – Instruction 103. However, most datalogger manuals and  
program editor help systems do not refer to the SDM-CVO4 in the description of  
Instruction 103. Please see the details of use below to understand the differences.  
Instruction 103 is described in Table 6-1 and allows you to set four separate  
output levels for one SDM-CVO4, or several output levels with multiple  
SDM-CVO4s. Output levels are reset each time Instruction 103 is executed.  
Instruction 103 was originally designed to take an input location range of  
-5000 to +5000 and output this directly in mV when using the SDM-A04. When  
used with the SDM-CVO4, the same range of values (±5000) in an input location  
is used to scale the output to 0-10000mV for voltage mode, or  
0-20 mA for current output mode.  
In most applications a specific range of a measured value is scaled to utilize the  
full scale output of SDM-CVO4. For instance, a temperature sensor reading in the  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SDM-CVO4 4-Channel Current/Voltage Output Module  
range of -20°C to +50°C would be scaled so at -20C the output is 0 mV and at  
+50°C the output is 10000 mV. To do this with the SDM-CVO4 you would use  
the mathematical functions of the datalogger to calculate a scaled value in a new  
input location, so that the value is -5000 when the temperature is -20°C and  
+5000 at +50°C.  
The datalogger limits the output of the SDM-CVO4 so that even if the measured  
value exceeds the intended range (i.e. the scaling value exceeds  
±5000) the signal output is limited to the equivalent output at -5000 or +5000.  
Therefore the datalogger instruction does not normally need to have extra  
instructions to limit the scaling value range. However for displays or input devices  
which require a current signal of 4-20 mA, the datalogger program needs to  
include extra instructions to prevent the scaling value going below  
- 3000 (see the examples below) and thereby setting the lowest possible output to  
4 mA.  
When checking the output of the SDM-CVO4 against the scaling value you  
should be aware that the output changes in discrete steps, e.g. 2.5 mV in voltage  
mode. When the datalogger works out which of these discrete steps to set for a  
given scaling value, a combination of floating point mathematics followed by  
truncation to an integer value is made. This will sometimes result in the transition  
from one output step to the next not happening at the exact midpoint value of each  
2.5 mV step, although it should happen within a limit of ±0.5 in terms of the  
scaling value stored in the input location.  
The number of repetitions, parameter 1, specifies the total number of  
SDM-CVO4 output channels to be set. The address of the first SDM-CVO4 is  
specified with parameter 2; multiple SDM-CVO4s must have consecutive  
addresses. Parameter 3 is the starting input location containing the scaling value  
for the first output channel of the first SDM-CVO4. Subsequent scaling values  
must be contained in consecutive input locations immediately after the first input  
location specified in parameter 3.  
For example, two SDM-CVO4s can be used to output eight signals, which are  
contained in input locations 15 to 22. There are eight repetitions, and so eight (8)  
is entered for parameter 1. The SDM-CVO4s must have consecutive addresses  
(e.g. 31 and 32), and so parameter 2 would contain 31 in this case. Fifteen (15)  
would be entered for parameter 3.  
Table 6-1. Description of Instruction 103  
Par.  
Number  
Data  
Type  
Description  
01:  
02:  
03:  
2
2
4
Reps — Number of analogue outputs  
Address of SDM-CVO4 in base 4 (00 to 33)  
Input loc. holds scaling value for the output level  
Setting the Reps parameter to 0 (Zero) will cause the addressed SDM-CVO4 to  
shut down, turning off all its outputs. It will turn on channels 1 and 2 at the next  
execution of Instruction P103 where the reps parameter is 1 or 2. If the reps  
parameter is greater than 2, then all the channels will be turned on.  
Refer to the manual for the datalogger being used for full details of the execution  
time of Instruction 103. All of the outputs of the SDM-CVO4 will change  
simultaneously approximately 10ms after the instruction is completed by the  
datalogger, or 100ms after power-up.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Instruction Manual  
If the SDM-CVO4 loses power for any reason, when power is restored the outputs  
will return to the default ‘off’ state. This will be held until the datalogger runs  
Instruction 103 again to update the output levels required.  
6.2 Edlog Program Examples  
The following program examples are given to help you understand the general  
principles involved in the use of the SDM-CVO4.  
6.2.1 Voltage and 0-20 mA Current Output Modes  
This program example is for a simple weather station with a CR23X Micrologger  
measuring wind speed, wind direction, temperature and solar radiation. Each  
parameter is scaled to the full-scale output range of the  
SDM-CVO4 which would be 0-10,000 mV DC or 0-20 mA, depending on the  
output jumper settings. Programming for the CR10X is very similar.  
; {CR23X}  
; Example weather station program to show scaling values  
; for the SDM-CVO4  
*Table 1 Program  
01: 1  
Execution Interval (seconds)  
; Measure the output from a switch closure anemometer (A100R)  
1: Pulse (P3)  
1:  
2:  
3: 22  
4:  
5: 1.25  
6: 0.0  
1
1
Reps  
Pulse Channel 1  
Switch Closure, Output Hz  
Loc [ WindSpeed ]  
Mult ; Scale to m/s  
Offset  
1
; Measure the wind direction from a potentiometer windvane  
2: Excite-Delay (SE) (P4)  
1:  
1
Reps  
2: 14  
1000 mV, Fast Range  
SE Channel  
Excite all reps w/Exchan 1  
Delay (units 0.01 sec)  
mV Excitation  
Loc [ WindDir ]  
Mult ; Scale to angle in degrees  
Offset  
3:  
4:  
5:  
1
1
1
6: 1000  
7:  
2
8: 0.357  
9: 0.0  
; Measure air temperature from a 107 probe  
3: Temp (107) (P11)  
1:  
2:  
1
2
Reps  
SE Channel  
3: 31  
4:  
Excite all reps w/E1, 50Hz, 10ms delay  
3
Loc [ AirT  
]
5: 1.0  
6: 0.0  
Mult ; Scale to degrees C  
Offset  
; Measure solar radiation from an SP-Lite  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SDM-CVO4 4-Channel Current/Voltage Output Module  
4: Volt (SE) (P1)  
1:  
1
Reps  
2: 32  
50 mV, 50 Hz Reject, Slow Range  
3:  
4:  
3
4
SE Channel  
Loc [ Radiation ]  
Mult  
5: 100  
6: 0.0  
Offset  
; Now output data in the normal way to final storage  
5: If time is (P92)  
1:  
2:  
3: 10  
0
1
Minutes (Seconds --) into a  
Interval (same units as above)  
Set Output Flag High (Flag 0)  
6: Real Time (P77)  
1: 110  
Day,Hour/Minute (midnight = 0000)  
7: Wind Vector (P69)  
1:  
2:  
3:  
4:  
5:  
1
0
0
1
2
Reps  
Samples per Sub-Interval  
S, é1, & å(é1) Polar  
Wind Speed/East Loc [ WindSpeed ]  
Wind Direction/North Loc [ WindDir ]  
8: Average (P71)  
1:  
2:  
2
3
Reps  
Loc [ AirT  
]
; Now the code to scale the values and update the SDM-CVO4  
; As we have four channels to output, we will first copy the  
; current readings with P54, block move, in a block of four  
; input locations to hold the scaled outputs  
9: Block Move (P54)  
1:  
2:  
3:  
4:  
5:  
4
1
1
5
1
No. of Values  
First Source Loc [ WindSpeed ]  
Source Step  
First Destination Loc [ ScldOut_1 ]  
Destination Step  
; Then apply the scaling with one Instruction P53  
; The readings are scaled -5000 to +5000, i.e. to  
; cover the full scale range which would equate to  
; 0 - 10,000 mV in voltage mode or 0-20 mA in  
; current mode.  
; Windspeed to cover the range 0-100 m/s  
; Wind direction to cover 0-360 degrees  
; Temperature -25 to +50 degrees C  
; Radiation 0 - 1000 m^2/s  
10: Scaling Array (A*Loc+B) (P53)  
1:  
5
Start Loc [ ScldOut_1 ]  
A1 ; WS multiplier  
B1 ; WS Offset  
2: 100  
3: -5000  
4: 27.7778 A2  
5: -5000 B2  
6: 133.333 A3  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Instruction Manual  
7: -1666.67 B3  
8: 10  
9: -5000  
A4  
B4  
; Now update the SDM-CVO4 with the information  
; for the four channels  
11: SDM-AO4 (P103)  
1:  
2: 30  
3:  
4
Reps  
SDM Address  
Loc [ ScldOut_1 ]  
5
6.2.2 Restricted Range Current Output Modes (4-20 mA)  
When driving a system that requires a restricted current range then the full-scale  
range is reduced accordingly. In the case of 4-20 mA devices the maximum range  
is 8000 units and the minimum value should be scaled to  
-3000 and prevented from going below this level.  
The following partial program could be used in place of the last two instructions  
in the example above.  
; Then apply the scaling with one instruction P53  
; The readings are scaled -3000 to +5000, i.e. to  
; cover the range which would equate to  
; 4-20 mA in current mode.  
; Windspeed to cover the range 0-100 m/s  
; Wind direction to cover 0-360 degrees  
; Temperature -25 to +50 degrees C  
; Radiation 0 - 1000 m^2/s  
10: Scaling Array (A*Loc+B) (P53)  
1:  
2: 80  
3: -3000  
5
Start Loc [ ScldOut_1 ]  
A1 ; WS multiplier  
B1 ; WS Offset  
4: 22.2222 A2  
5: -3000 B2  
6: 106.667 A3  
7: -333.32 B3  
8:  
8
A4  
B4  
9: -3000  
; Now limit the lowest scaled value to -3000 (4 mA)  
; As we have four 4-20 mA current outputs, a loop  
; construct is the easiest way to do this.  
11: Beginning of Loop (P87)  
1: 0000  
2:  
Delay  
Loop Count  
4
; If the scaled value is less the –3000  
12: If (X<=>F) (P89)  
1:  
2:  
5
4
-- X Loc [ ScldOut_1 ]  
<
3: -3000  
4: 30  
F
Then Do  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SDM-CVO4 4-Channel Current/Voltage Output Module  
; then set the value to –3000  
13: Z=F (P30)  
1: -3000  
2: 00  
F
Exponent of 10  
3:  
14: End (P95)  
15: End (P95)  
5
-- Z Loc [ ScldOut_1 ]  
; Now update the SDM-CVO4 with the information  
; for the four channels  
16: SDM-AO4 (P103)  
1:  
2: 30  
3:  
4
Reps  
SDM Address  
Loc [ ScldOut_1 ]  
5
6.2.3 Providing Isolated Power Supplies to Sensors  
This program example sets all the outputs of the SDM-CVO4 to 10 V to provide  
isolated power supplies to four separate sensors. The program includes code to put  
the SDM-CVO4 into standby mode after the measurements are made.  
; {CR10X}  
; An example program which show use of the SDM-CVO4  
; as an isolated power supply for 4 sensors requiring  
; 10 V drive and producing 0-100 mV signals.  
; This shows how to set the SDM-CVO4 into standby mode.  
*Table 1 Program  
01:  
60  
Execution Interval (seconds)  
; Store a fixed value of 5000 = 10 V output  
; in the four scaling locations  
1: Bulk Load (P65)  
1: 5000  
2: 5000  
3: 5000  
4: 5000  
5: 0.0  
F
F
F
F
F
6: 0.0  
F
7: 0.0  
F
8: 0.0  
F
9:  
1
Loc [ Scale_1 ]  
; Tell the SDM-CVO4 to set all four outputs to 10,000 mV  
; The SDM-CVO4 address is zero in this example.  
; This will cause the SDM-CVO4 to come out of standby  
; mode.  
2: SDM-AO4 (P103)  
1:  
2: 00  
3:  
4
Reps  
SDM Address  
Loc [ Scale_1 ]  
1
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Instruction Manual  
; Wait 100 ms for it to power-on and the outputs to stabilize  
; You may need to increase this delay if the sensors ; themselves  
; have a power-on delay  
3: Excitation with Delay (P22)  
1:  
1
Ex Channel  
2: 0000  
3: 10  
4: 0000  
Delay W/Ex (units = 0.01 sec)  
Delay After Ex (units = 0.01 sec)  
mV Excitation  
; Take the four measurements from the Pressure sensors.  
4: Volt (Diff) (P2)  
1:  
4
Reps  
2: 04  
250 mV Slow Range  
DIFF Channel  
Loc [ Press_1 ]  
Mult  
3:  
4:  
1
5
5: 1.0  
6: 0.0  
Offset  
; Now turn off the SDM-CVO4 by using the command with 0 reps.  
5: SDM-AO4 (P103)  
1:  
2: 00  
3:  
0
Reps  
SDM Address  
Loc [ Scale_1 ]  
1
; Now the normal output processing and final storage  
; instructions would follow, for example:  
; Every hour set the output flag  
6: If time is (P92)  
1:  
2: 60  
3: 10  
0
Minutes (Seconds --) into a  
Interval (same units as above)  
Set Output Flag High (Flag 0)  
; Store time  
7: Real Time (P77)  
1: 1110  
Year,Day,Hour/Minute (midnight = 0000)  
; Store the average readings  
8: Average (P71)  
1:  
2:  
4
5
Reps  
Loc [ Press_1 ]  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SDM-CVO4 4-Channel Current/Voltage Output Module  
6.3 CRBasic SDMCVO4 Instruction  
This instruction is used to control the SDM-CVO4 four channel current/voltage  
output device.  
Syntax  
SDMCVO4 ( CVO4Source, CVO4Reps, SDMAddress, CVO4Mode )  
Remarks  
This instruction controls the SDM-CVO4, which outputs a voltage or a current.  
Internal jumpers are used to set the mode for the device, but the jumpers can be  
overridden with the Mode parameter in this instruction.  
CVO4Source The CVO4Source parameter is a variable array that holds the  
values for the voltages (millivolts) or currents (microamps) that  
will be output by each channel of the device (Source(1) sets  
channel1, Source(2) sets channel2, etc.). When outputting a  
voltage, the variable must be within the range of 0 to 10,000.  
When outputting a current, the variable must be within the range  
of 0 to 20,000.  
CVO4Reps  
The CVO4Reps parameter indicates the number of channels to set  
to the defined voltage or current. Additional SDM-CVO4 devices  
can be controlled by one SDMCVO4 instruction by assigning  
them consecutive addresses and setting the CVO4Reps parameter  
to a value equal to the total number of channels of all devices  
(e.g., to set all four channels on two devices, set the CVO4Reps  
parameter to 8).  
If the CVO4Reps parameter is set to 0, power to the device will  
be turned off.  
SDMAddress The SDMAddress parameter defines the address of the SDM-  
CVO4 which will be affected by this instruction. Valid SDM  
addresses are 0 through 14. Address 15 is reserved for the  
SDMTrigger instruction.  
CRBasic dataloggers use base 10 when addressing SDM devices.  
Edlog programmed dataloggers (e.g., CR10X, CR23X) used base 4  
for addressing.  
NOTE  
CVO4Mode  
The CVO4Mode determines what type of signal will be output by  
the device. The options are:  
Option Description  
0
1
10  
11  
Voltage output, use jumper settings (scale only)  
Current output; use jumper settings (scale only)  
Voltage output; override jumper setting  
Current output; override jumper setting  
The two override options (10 and 11) affect all of the channels of  
all of the SDM-CVO4 devices being controlled by this  
instruction. These two options override the hardware settings in  
the device. Use of this mode takes approximately 2 milliseconds  
additional time per device. When either of these options is used  
you lose the flexibility of setting the output mode for each  
channel individually. Additionally, subsequent programs sent to  
the datalogger must also use an override mode or the power must  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Instruction Manual  
be cycled on the device to return it to its default state. Otherwise,  
if 0 or 1 is entered it will be ignored and the device will remain in  
its last override state. Refer to Section 4.2.2 for connection  
details.  
6.4 SDM-CVO4 Instruction Example  
This program example is for a weather station measuring wind speed, wind  
direction, temperature, and relative humidity. Each parameter is scaled to 0 to  
10000 mVDC, and output to a SCADA system through the SDM-CVO4.  
Public WS_ms  
Public WD_0_360  
Public Temp_C  
Public RH  
Public WD_0_540  
Public Flag  
Public CVO4Output(4)  
Alias CVO4Output(1) = WSOut  
Alias CVO4Output(2) = WDOut  
Alias CVO4Output(3) = TempOut  
Alias CVO4Output(4) = RHOut  
'Code for DataTable OneMin  
DataTable(OneMin,1,-1)  
DataInterval(0,1,Min,0)  
WindVector (1, WS_ms,WD_0_360, IEEE4, 0, 0, 0, 0)  
Average(1,Temp_C,IEEE4,0)  
Sample(1,RH, IEEE4)  
EndTable  
BeginProg  
Scan(1,Sec,1,0)  
' Code for 03001 wind measurements, WS_ms & WD_0_360:  
PulseCount(WS_ms, 1, 1, 1, 1, 0.75, 0.2)  
BrHalf(WD_0_360, 1,mV1000, 1, 1, 1, 1000, True, 1000, 250, 355, 0)  
' Code for CS500 measurement, AirTC and RH:  
VoltSE(Temp_C,1,mV1000,3,0, 0, _60Hz,0.1,-40.0)  
VoltSE(RH,1,mV1000,2,0, 0, _60Hz,0.1, 0)  
' Call Data Table  
CallTable(OneMin)  
' Convert 0-360 WD to 0-540:  
If WD_0_540 >= 270 and WD_0_360 <180 Then  
WD_0_540 = WD_0_360 + 360  
Else  
WD_0_540 = WD_0_360  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SDM-CVO4 4-Channel Current/Voltage Output Module  
EndIf  
' Scale the measurements for the SDM-CVO4 to output 0-10000 mV  
WSOut = WS_ms*200 'WS: 0-50 m/s = 0-10000 mV  
WDOut = WD_0_540 *18.59 'WD: 0-540 deg = 0-10000mV  
TempOut= 100*(Temp_C+40) 'Temp: -40-60 deg C = 0-10000 mV  
RHOut = RH *100 'RH: 0-100 % RH = 0-10000 mV  
' Send mV outputs to SDM-CVO4 using the option to override the switch settings  
SDMCVO4 (CVO4Output(),4,0,10)  
NextScan  
EndProg  
This is a blank page.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Campbell Scientific Companies  
Campbell Scientific, Inc. (CSI)  
815 West 1800 North  
Logan, Utah 84321  
UNITED STATES  
Campbell Scientific Africa Pty. Ltd. (CSAf)  
PO Box 2450  
Somerset West 7129  
SOUTH AFRICA  
Campbell Scientific Australia Pty. Ltd. (CSA)  
PO Box 444  
Thuringowa Central  
QLD 4812 AUSTRALIA  
Campbell Scientific do Brazil Ltda. (CSB)  
Rua Luisa Crapsi Orsi, 15 Butantã  
CEP: 005543-000 São Paulo SP BRAZIL  
Campbell Scientific Canada Corp. (CSC)  
11564 - 149th Street NW  
Edmonton, Alberta T5M 1W7  
CANADA  
Campbell Scientific Ltd. (CSL)  
Campbell Park  
80 Hathern Road  
Shepshed, Loughborough LE12 9GX  
UNITED KINGDOM  
Campbell Scientific Ltd. (France)  
Miniparc du Verger - Bat. H  
1, rue de Terre Neuve - Les Ulis  
91967 COURTABOEUF CEDEX  
FRANCE  
Campbell Scientific Spain, S. L.  
Psg. Font 14, local 8  
08013 Barcelona  
SPAIN  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Bionaire Dehumidifier BFH3405 User Manual
Blackberry Cell Phone PGP User Manual
Blackberry Printer 9500 User Manual
Bodum Coffee Grinder 10462 User Manual
Bosch Appliances Clothes Dryer WTC82100US User Manual
Bosch Appliances Water Heater GWH 635 ES User Manual
Califone Headphones NC500TFC User Manual
Canon Camcorder 1014XL S User Manual
Chauvet Outdoor Timer SF 4005 User Manual
Cisco Systems Network Card PA T3 User Manual