Bryant Furnace 350MAV User Manual

service and  
350MAV  
Series G  
maintenance procedures  
4-WAY MULTIPOISE  
FIXED-CAPACITY DIRECT-VENT  
CONDENSING GAS FURNACE  
Cancels: SP05-47  
SP05-52  
8-02  
WARNING: ELECTRICAL SHOCK, FIRE,  
OR EXPLOSION HAZARD  
Failure to follow safety warnings exactly could result in  
dangerous operation, serious injury, death, or property  
damage.  
Improper servicing could result in dangerous operation,  
serious indury, death, or property damage.  
Before servicing, disconnect all electrical power to fur-  
nace.  
When servicing controls, label all wires prior to discon-  
necting. Reconnect wires correctly.  
Verify proper operation after servicing.  
A93040  
WARNING: The ability to properly perform mainte-  
nance on this equipment requires certain expertise, me-  
chanical skills, tools, and equipment. If you do not  
possess these, do not attempt to perform any maintenance  
on this equipment other than those procedures recom-  
mended in the User’s Manual. FAILURE TO FOLLOW  
THIS WARNING COULD RESULT IN POSSIBLE  
DAMAGE TO THIS EQUIPMENT, SERIOUS PER-  
SONAL INJURY, OR DEATH.  
Flushing Collector Box and Drainage  
System.......................................................................................6  
Servicing Hot Surface Ignitor ..................................................7  
Electrical Controls and Wiring.................................................8  
Checking Heat Tape Operation  
(If Applicable)...........................................................................8  
Winterizing................................................................................8  
WIRING DIAGRAM.....................................................................9  
TROUBLESHOOTING .................................................................9  
Status Codes..............................................................................9  
Component Test........................................................................9  
WARNING: Never store anything on, near, or in contact  
with the furnace, such as:  
1. Spray or aerosol cans, rags, brooms, dust mops,  
vacuum cleaners, or other cleaning tools.  
SAFETY CONSIDERATIONS  
2. Soap powders, bleaches, waxes or other cleaning  
compounds, plastic or plastic containers, gasoline,  
kerosene, cigarette lighter fluid, dry cleaning fluids, or  
other volatile fluids.  
3. Paint thinners and other painting compounds, paper  
bags, or other paper products.  
Recognize safety information. This is the safety-alert symbol  
When you see this symbol on the furnace and in instructions or  
manuals, be alert to the potential for personal injury.  
.
Understand the signal words DANGER, WARNING, and CAU-  
TION. These words are used with the safety-alert symbol. DAN-  
GER identifies the most serious hazards which will result in severe  
personal injury or death. WARNING signifies hazards which  
could result in personal injury or death. CAUTION is used to  
identify unsafe practices which would result in minor personal  
injury or product and property damage. NOTE is used to highlight  
suggestions which will result in enhanced installation, reliability,  
or operation.  
Failure to follow this warning can cause corrosion of  
the heat exchanger, fire, personal injury, or death.  
NOTE: Read the entire instruction manual before starting the  
installation.  
This symbol indicates a change since the last issue.  
Installing and servicing heating equipment can be hazardous due to  
gas and electrical components. Only trained and qualified service  
agency personnel should install, repair, or service heating equip-  
ment.  
TABLE OF CONTENTS  
SAFETY CONSIDERATIONS.....................................................1  
GENERAL......................................................................................2  
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS........2  
Untrained personnel can perform basic maintenance functions  
such as cleaning and replacing air filters. All other operations must  
be performed by trained and qualified service agency personnel.  
When working on heating equipment, observe precautions in the  
literature, on tags, and on labels attached to or shipped with the  
unit and other safety precautions that may apply.  
Follow all safety codes including the National Fuel Gas Code  
(NFGC) NFPA 54-1999/ANSI Z223.1-1999 in the USA; National  
Standard of Canada, Natural Gas and Propane Installation Code  
CARE AND MAINTENANCE.....................................................2  
Cleaning and/or Replacing Air Filter.......................................3  
Blower Motor and Wheel Maintenance...................................3  
Cleaning Burners ......................................................................4  
Cleaning Heat Exchangers........................................................5  
Primary Heat Exchangers....................................................5  
Secondary Heat Exchangers................................................6  
—1—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WASHABLE  
FILTER  
IN FURNACE  
FILTER  
RETAINER  
WASHABLE  
FILTER  
FILTER  
SUPPORT  
FILTER  
RETAINER  
WASHABLE FILTER OR  
DISPOSABLE MEDIA  
FILTER IN FILTER CABINET  
WASHABLE FILTER OR  
DISPOSABLE MEDIA FILTER  
IN FILTER CABINET  
A00233  
Fig. 4Filter Installed for Side Inlet  
A00232  
Fig. 3Bottom Filter Arrangement  
If filter is installed in filter cabinet adjacent to furnace:  
1. Turn off electrical supply to furnace.  
2. Remove filter cabinet door.  
WARNING: Turn off the gas and electrical supplies to  
the unit before performing any maintenance or service.  
Follow the operating instructions on the label attached to  
the furnace. Failure to follow this warning could result in  
personal injury or death.  
3. Slide filter out of cabinet.  
4. If equipped with permanent, washable filter, clean filter by  
spraying cold tap water through filter in opposite direction  
of airflow. Rinse filter and let dry. Oiling or coating of the  
filter is not recommended.  
The minimum maintenance that should be performed on this  
equipment is as follows:  
1. Check and clean or replace air filter each month as needed.  
2. Check blower motor and wheel for cleanliness annually.  
5. If equipped with factory specified disposable media filter,  
replace only with a factory-authorized media filter of the  
same size.  
3. Check electrical connections for tightness and controls for  
proper operation each heating season. Service as necessary.  
6. Slide filter into cabinet.  
7. Replace filter cabinet door.  
4. Check for proper condensate drainage. Clean as necessary.  
8. Turn on electrical supply to furnace.  
5. Check for blockages in combustion-air and vent pipes  
annually.  
If filter is installed in furnace blower compartment:  
1. Turn off electrical supply to furnace.  
2. Remove main furnace door and blower access panel.  
3. Release filter retainer wire. (See Figs. 3 or 4.)  
4. Slide filter out of furnace.  
6. Check burners for cleanliness annually.  
CAUTION: Personal injury could result from sharp  
metal edges, etc. Use care and wear protective clothing  
safety glasses, and gloves when removing parts.  
5. Furnaces are equipped with permanent, washable filter(s).  
Clean filter by spraying cold tap water through filter in  
opposite direction of airflow.  
I. CLEANING AND/OR REPLACING AIR FILTER  
The air filter arrangement may vary depending on the application  
or orientation. Filter could be located in furnace blower compart-  
ment or in filter cabinet.  
6. Rinse filter and let dry. Oiling or coating filter is not  
recommended.  
7. Slide filter into furnace.  
WARNING: Never operate unit without a filter or with  
the blower access panel removed. Failure to follow this  
warning could result in a fire or personal injury.  
8. Recapture filter retainer wire.  
9. Replace blower access panel and main furnace door.  
10. Turn on electrical supply to furnace.  
II. BLOWER MOTOR AND WHEEL MAINTENANCE  
CAUTION: Operating a unit without a filter or with the  
blower access door removed could cause damage to the  
furnace blower motor. Dust and lint on internal parts of  
furnace can cause a loss of efficiency.  
To ensure long life, economy, and high efficiency, clean accumu-  
lated dirt and grease from blower wheel and motor annually.  
The inducer and blower motors are pre-lubricated and require no  
additional lubrication. These motors can be identified by the  
absence of oil ports on each end of the motor.  
NOTE: If the filter has an airflow direction arrow, the arrow must  
point toward the blower.  
The following items should be performed by a qualified service  
technician.  
Clean blower motor and wheel as follows:  
To clean or replace filters, proceed as follows:  
3—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Turn off electrical supply to furnace.  
(2.) Connect 1 tube (violet or unmarked) from inducer  
housing.  
2. Remove main furnace door and blower access panel.  
(3.) Connect 1 tube (relief port, green or pink) from  
collector box.  
3. Disconnect blower motor wires from furnace control.  
Field thermostat connections may need to be disconnected  
depending on their length and routing.  
c. Connect field drain to condensate trap.  
4. Remove control box mounting screws, and position control  
box, transformer, and door switch assembly to right side of  
furnace casing.  
13. Reconnect wires.  
Refer to furnace wiring diagram and connect thermostat  
leads if previously disconnected. (See Fig. 15.)  
5. If condensate trap is located in left- or right-hand side of  
furnace casing, proceed to item 6, otherwise remove trap  
and tubing as described below (see Fig. 8, top left):  
NOTE: Refer to Table 1 for motor speed lead reconnection if  
leads were not identified before disconnection.  
a. Disconnect field drain connection from condensate trap.  
CAUTION: Heating speed selection MUST be adjusted  
to provide proper temperature rise as specified on the  
rating table. Failure to adjust the heating speed may  
shorten heat exchanger life.  
b. Disconnect drain and relief port tubes from condensate  
trap.  
c. Remove condensate trap from blower shelf.  
6. Remove screws securing blower assembly to blower shelf  
and slide blower assembly out of furnace.  
7. Clean blower wheel and motor by using a vacuum with soft  
brush attachment. Be careful not to disturb balance weights  
(clips) on blower wheel vanes. Do not bend wheel or blades  
as balance will be affected.  
TABLE 1SPEED SELECTION  
FACTORY  
COLOR  
SPEED  
ATTACHED TO  
Black  
High  
Medium High  
Medium Low  
Low  
Cool  
8. If greasy residue is present on blower wheel, remove wheel  
from the blower housing and wash it with an appropriate  
degreaser. To remove wheel:  
Yellow (When Present)  
Spare  
Blue  
Red  
Heat  
Spare  
a. Mark blower wheel location on shaft before disassembly  
to ensure proper reassembly.  
White  
Common  
Com  
b. Loosen setscrew holding blower wheel on motor shaft.  
14. Turn on electrical supply. Manually close blower access  
door switch. Use a piece of tape to hold switch closed.  
Check for proper rotation and speed changes by perroming  
a componenet self-test as shown at the bottom of Service  
Label. (See Fig. 17.)  
NOTE: Mark blower mounting arms and blower housing so each  
arm is positioned at the same hole location during reassembly.  
c. Mark blower wheel orientation and cutoff plate location  
to ensure proper reassembly.  
d. Remove screws securing cutoff plate and remove cutoff  
plate from housing.  
WARNING: Blower access door switch opens 115-v  
power to furnace control. No component operation can  
occur. Caution must be taken when manually closing this  
switch for service purposes. Failure to follow this warn-  
ing could result in personal injury or death.  
e. Remove bolts holding motor mounts to blower housing  
and slide motor and mounts out of housing. Disconnect  
capacitor and ground wire attached to blower housing  
before removing motor. Motor mounts need not be  
removed from motor.  
f. Remove blower wheel from housing.  
15. If furnace is operating properly, release blower access door  
switch, replace blower access door, and replace main  
furnace door.  
CAUTION: The blower wheel should not be dropped or  
betn as balance will be affected.  
III. CLEANING BURNERS  
The following items should be performed by a qualified service  
technician. If the burners develop an accumulation of light dirt or  
dust, they may be cleaned by using the following procedure:  
g. Clean wheel per instructions on degreaser cleaner. Do  
not get degreaser in motor.  
9. Reassemble motor and blower wheel by reversing items 8b  
through 8f. Ensure wheel is positioned for proper rotation.  
Be sure to attach ground wire. Tighten set-screw to 140 to  
160 in.-lb torque.  
1. Turn off gas and electrical supplies to furnace.  
2. Remove main furnace door.  
3. Remove burner box cover.  
10. Reinstall blower assembly in furnace.  
4. Using backup wrench, disconnect gas supply pipe from  
furnace gas control valve.  
11. Reinstall control box, transformer, and door switch assem-  
bly on blower shelf.  
CAUTION: Label all wires prior to disconnection when  
servicing controls. Wiring errors can cause improper and  
dangerous operation.  
12. Reinstall condensate trap and tubing if previously removed.  
a. Reinstall condensate trap in hole in blower shelf.  
b. Connect condensate trap drain tubes. See Fig. 8 or tubing  
diagram on main furnace door for proper tube location.  
5. Remove wires from gas valve. Note location for reassem-  
bly.  
NOTE: Ensure tubes are not kinked or pinched, as this will affect  
operation.  
6. Remove burner box pressure tube from gas valve regulator  
fitting.  
(1.) Connect 1 tube (blue or blue and white striped)  
from collector box.  
4—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7. Remove screws that secure manifold to burner box. (See  
Fig. 5.)  
WARNING: FIRE OR EXPLOSION HAZARD  
Failure to follow the safety warnings exactly could result  
in serious injury, death, or property damage.  
Never test for gas leaks with an open flame. Use a  
commercially available soap solution made specifically  
for the detection of leaks to check all connections. A fire  
or explosion may result causing property damage, per-  
sonal injury, or loss of life.  
NOTE: Do not remove burner box from cell panel.  
8. Remove manifold, orifices, and gas valve as 1 assembly.  
9. Remove screws attaching burner assembly in burner box.  
10. Remove burner assembly from burner box.  
NOTE: All burners are attached to burner bracket and can be  
removed as 1 assembly.  
18. Check for gas leaks.  
11. Clean burners with soft brush and vacuum.  
19. Replace main furnace door.  
IV. CLEANING HEAT EXCHANGERS  
12. Reinstall manifold, orifice, and gas valve assembly in  
burner box. Ensure manifold seal grommet is installed  
properly and burners fit over orifices.  
The following items should be performed by a qualified service  
technician.  
13. Reconnect wires to gas valve. Refer to furnace wiring  
diagram for proper wire location.  
A. Primary Heat Exchangers  
If the heat exchangers get an accumulation of light dirt or dust on  
the inside, they may be cleaned by the following procedure:  
14. Reinstall burner box pressure tube to gas valve regulator  
fitting.  
NOTE: If the heat exchangers get a heavy accumulation of soot  
and carbon, both the primary and secondary heat exchangers  
should be replaced rather than trying to clean them thoroughly due  
to their intricate design. A build-up of soot and carbon indicates  
that a problem exists which needs to be corrected, such as  
improper adjustment of manifold pressure, insufficient or poor  
quality combustion air, improper vent termination, incorrect size  
or damaged manifold orifice(s), improper gas, or a restricted heat  
exchanger (primary or secondary). Action must be taken to correct  
the problem.  
15. Reinstall gas supply pipe to furnace gas control valve using  
backup wrench on gas valve to prevent rotation and  
improper orientation.  
NOTE: Use propane gas resistant pipe dope to prevent gas leaks.  
DO NOT use Teflon tape.  
WARNING: Gas valve switch MUST be facing forward  
or tilted upward. Failure to follow this warning could  
result in property damage, personal injury, or death.  
1. Turn off gas and electrical supplies to furnace.  
2. Remove main furnace door.  
16. Replace burner box cover.  
CAUTION: Label all wires prior to disconnection when  
servicing controls. Wiring errors can cause improper and  
hazardous operation. .  
17. Turn on gas and electrical supplies to furnace.  
3. Disconnect wires or connectors to flame rollout switch, gas  
valve, igniter, and flame sensor.  
4. Disconnect combustion-air intake pipe from intake housing.  
5. Remove the pressure switch tube from intake housing.  
CELL  
PANEL  
6. Remove screws attaching intake housing to burner box, and  
rotate intake housing away from burner box for removal.  
MANIFOLD  
MOUNTING  
SCREW  
7. Using backup wrench, disconnect gas supply pipe from gas  
valve.  
8. Disconnect pressure tubing from gas valve.  
9. Remove 2 screws attaching top filler panel and rotate  
upwards to gain access to screws attaching burner box to  
cell panel.  
10. Remove screws attaching burner box to cell panel. (See Fig.  
5.)  
NOTE: Burner box cover, manifold, gas valve, and burner  
assembly should be removed as 1 assembly.  
MANIFOLD  
11. Clean heat exchanger openings with a vacuum and a soft  
brush. (See Fig. 6.)  
GAS VALVE  
REGULATOR  
FITTING  
NOTE: After cleaning, inspect the heat exchangers to ensure they  
are free of all foreign objects that may restrict flow of combustion  
products.  
GAS VALVE  
A96304  
12. Reverse items 4 through 10 for reassembly.  
Fig. 5Burner Box Assembly  
5—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRIMARY HX  
INLET OPENINGS  
WARNING: FIRE OR EXPLOSION HAZARD  
Failure to follow the safety warnings exactly could result  
in serious injury, death, or property damage.  
Never test for gas leaks with an open flame. Use a  
commercially available soap solution made specifically  
for the detection of leaks to check all connections. A fire  
or explosion may result causing property damage, per-  
sonal injury, or loss of life.  
17. Check for gas leaks.  
18. Replace main furnace door.  
B. Secondary Heat Exchangers  
NOTE: The condensing side (inside) of the secondary heat  
exchangers CANNOT be serviced or inspected. A small number of  
bottom outlet openings can be inspected by removing the inducer  
assembly. See Flushing Collector Box and Drainage System  
section for details on removing inducer assembly.  
A96305  
V. FLUSHING COLLECTOR BOX AND DRAINAGE  
SYSTEM  
Fig. 6Cleaning Inlet Openings of Primary Heat  
Exchangers  
1. Turn off gas and electrical supplies to furnace.  
2. Remove main furnace door.  
CAUTION: The ground wire from the gas valve MUST  
be attached to the burner box attachment screw. Failure to  
attach this ground wire to an adequate casing ground will  
cause the furnace control to lock out.  
3. Disconnect inducer motor and pressure switch wires or  
connectors.  
4. Disconnect pressure switch tubes.  
5. Disconnect vent pipe from inducer housing outlet by  
loosening coupling clamp on inducer outlet.  
NOTE: Be sure burner box gasket is installed between burner box  
and cell panel. If gasket is damaged, replace it.  
6. Disconnect drain tube from inducer housing. (See Fig. 8.)  
NOTE: Inspect combustion-air intake housing. If foamed gasket  
was removed, check for any damage. If gasket is damaged in any  
way, it must be repaired. To repair, remove damaged gasket  
section, apply sealant releasing agent such as PAM cooking spray  
or equivalent (must not contain corn or canola oil, aromatic or  
halogenated hydrocarbons or inadequate seal may occur) to burner  
box and apply a small bead of G.E. RTV 162, G.E. RTV 6702, or  
Dow-Corning RTV 738 sealant to edge of combustion-air intake  
housing. (See Fig. 7.)  
7. Remove inducer housing assembly by removing 4 bolts  
attaching assembly to cell panel.  
8. Flush inside of collector box with water until discharge  
from condensate trap is clean and runs freely.  
NOTE: Ensure the drain tube disconnected from the inducer  
housing is higher than the collector box opening or water will flow  
out tube.  
9. Inspect inside area of collector box for any pieces of foreign  
materials and remove if present.  
CAUTION: DO NOT use wire brush or other sharp  
object to inspect or dislodge materials in secondary heat  
exchangers as failure of the secondary heat exchanger  
will occur. Flush with water only.  
RTV  
PAM  
10. Reassemble inducer assembly by reversing items 5-7.  
Tighten the vent coupling clamp screw(s) to 15 in.-lb of  
torque.  
A93087  
NOTE: If seal between the inducer housing and the collector box  
is damaged in any way, it must be repaired. To repair, apply  
sealant releasing agent such as PAM cooking spray or equivalent  
(must not contain corn or canola oil, aromatic or halogenated  
hydrocarbons which can cause an inadequate seal to occur) to  
inducer housing. (See Fig. 10.) Apply a small bead of G.E. RTV  
162, G.E. RTV 6702, or Dow-Corning RTV 738 sealant to groove  
in collector box.  
Fig. 7Combustion-Air Intake Housing Gasket Repair  
13. Refer to furnace wiring diagram and reconnect wires to  
rollout switch, gas valve, igniter, and flame sensor.  
14. Reconnect pressure switch tubes to gas valve and intake  
housing. Refer to tube routing label on main furnace door  
for proper tube location. Be sure tubes are not kinked. (See  
Fig. 8.)  
11. Refer to furnace wiring diagram and reconnect wires to  
inducer motor and pressure switches or connectors.  
15. Turn on gas and electrical supplies to furnace.  
12. Reconnect pressure tubes to pressure switches. See diagram  
on main furnace door for proper location of tubes. Be sure  
tubes are not kinked. (See Fig. 8.)  
16. Check furnace operation through 2 complete heat operating  
cycles. Look through sight glass in burner enclosure to  
check burners. Burner flames should be clear blue, almost  
transparent. (See Fig. 9.)  
13. Turn on gas and electrical supplies to furnace.  
6—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
14. Check furnace operation through 2 complete heat operating  
cycles. Check area below inducer housing, vent pipe, and  
condensate trap to ensure no condensate leaks occur. If  
leaks are found, correct the problem.  
2. Remove main furnace door.  
3. Disconnect igniter wire connection.  
4. Check igniter resistance.  
a. Using an ohm meter, check resistance across both igniter  
leads in connector.  
WARNING: FIRE OR EXPLOSION HAZARD  
Failure to follow the safety warnings exactly could result  
in serious injury, death, or property damage.  
b. Cold reading should be between 45 ohms and 90 ohms.  
Never test for gas leaks with an open flame. Use a  
commercially available soap solution made specifically  
for the detection of leaks to check all connections. A fire  
or explosion may result causing property damage, per-  
sonal injury, or loss of life.  
c. If ohm reading is higher than 110 ohms, igniter is  
cracked and must be replaced.  
5. Remove igniter assembly.  
CAUTION: Allow igniter to cool before removal. Nor-  
mal operating temperatures exceed 2000°F.  
15. Check for gas leaks.  
16. Replace main furnace door.  
a. Do not remove igniter from bracket while assembly is in  
furnace. Using a 1/4 in. nutdriver, remove screw secur-  
ing bracket and igniter assembly to bottom of burner  
box. The screw in the bracket is always located toward  
outside of burner box. The screw may be hidden by inlet  
VI. SERVICING HOT SURFACE IGNITER  
The igniter does NOT require annual inspection. Check igniter  
resistance before removal.  
1. Turn off gas and electrical supplies to furnace.  
TUBE ROUTING  
Furnace is shipped from factory in upflow configuration. Pressure tube and drain tube routing MUST match the diagrams below.  
Condensate Trap on LEFT  
Condensate Trap; Factory Installed  
Tube location when used in UPFLOW application  
Side Optional  
in Blower Shelf  
BURNER ENCLOSURE  
PRESSURE REFERENCE  
TUBE ASSEMBLY  
BURNER ENCLOSURE  
PRESSURE REFERENCE  
TUBE ASSEMBLY  
(Blower access panel removed)  
CAP  
CAP  
COLLECTOR BOX TUBE  
(PINK)  
PLUG  
PLUG  
COLLECTOR BOX TUBE  
COLLECTOR BOX TUBE  
(GREEN)  
(PINK)  
COLLECTOR BOX DRAIN  
TUBE  
COLLECTOR BOX TUBE (GREEN)  
(BLUE & WHITE STRIPED)  
COLLECTOR BOX DRAIN TUBE  
(BLUE & WHITE STRIPED)  
INDUCER HOUSING (MOLDED) DRAIN TUBE  
(BEHIND COLLECTOR BOX DRAIN TUBE)  
CONDENSATE TRAP  
COLLECTOR BOX DRAIN TUBE  
(BLUE)  
COLLECTOR BOX DRAIN TUBE  
(BLUE)  
FIELD-INSTALLED  
FACTORY-SUPPLIED  
DRAIN TUBE COUPLING  
(RIGHT DRAIN OPTION)  
CONDENSATE TRAP  
FIELD-INSTALLED  
FACTORY-SUPPLIED DRAIN TUBE  
COUPLING (LEFT DRAIN OPTION)  
INDUCER HOUSING DRAIN TUBE  
(VIOLET)  
FIELD-INSTALLED  
FACTORY-SUPPLIED 1/2-IN.  
CPVC STREET ELBOWS (2)  
FOR LEFT DRAIN OPTION  
FIELD-INSTALLED FACTORY-SUPPLIED  
DRAIN TUBE  
Condensate Trap on  
LEFT Side  
Condensate Trap on  
RIGHT Side  
Tube location when used in DOWNFLOW application  
PLUG  
COLLECTOR BOX  
DRAIN TUBE (BLUE)  
PLUGGED END  
CAP  
CAP  
COLLECTOR BOX DRAIN TUBE  
(BLUE)  
COLLECTOR BOX DRAIN  
TUBE  
(BLUE & WHITE STRIPED)  
COLLECTOR BOX  
TUBE (GREEN)  
COLLECTOR BOX TUBE  
(PINK)  
PLUG  
COLLECTOR BOX DRAIN TUBE  
(BLUE & WHITE STRIPED)  
COLLECTOR BOX TUBE  
(GREEN)  
INDUCER HOUSING DRAIN  
TUBE (VIOLET)  
COLLECTOR BOX  
EXTENSION TUBE  
COLLECTOR BOX EXTENSION TUBE  
BURNER ENCLOSURE PRESSURE  
REFERENCE TUBE ASSEMBLY  
COLLECTOR BOX  
EXTENSION TUBE  
CONDENSATE TRAP  
DRAIN TUBE COUPLING  
CONDENSATE TRAP  
COLLECTOR BOX  
TUBE (PINK)  
BURNER ENCLOSURE PRESSURE  
REFERENCE TUBE ASSEMBLY  
DRAIN TUBES ROUTED IN  
FRONT OF GAS VALVE  
COLLECTOR BOX  
EXTENSION DRAIN TUBE  
GAS VALVE  
INDUCER HOUSING DRAIN TUBE (VIOLET)  
Tube location when used on  
HORIZONTAL - LEFT application  
Tube location when used on  
HORIZONTAL - RIGHT application  
COLLECTOR BOX DRAIN TUBE  
(BLUE)  
COLLECTOR BOX DRAIN TUBE  
(BLUE & WHITE STRIPED)  
COLLECTOR BOX EXTENSION TUBE  
COLLECTOR BOX TUBE (PINK)  
PLUG  
CAP  
AUXILIARY "J" BOX RELOCATED HERE  
PLUG  
COLLECTOR BOX  
TUBE (GREEN)  
BURNER ENCLOSURE  
PRESSURE REFERENCE  
TUBE ASSEMBLY  
INDUCER HOUSING  
DRAIN TUBE  
(VIOLET)  
CAP  
COLLECTOR BOX  
BURNER ENCLOSURE  
PRESSURE REFERENCE  
TUBE ASSEMBLY  
EXTENSION TUBE  
COLLECTOR BOX  
DRAIN TUBE (BLUE)  
CONDENSATE TRAP  
COLLECTOR BOX  
EXTENSION TUBE  
COLLECTOR BOX  
TUBE (GREEN)  
DRAIN TUBE  
COUPLING  
COLLECTOR BOX TUBE (PINK)  
RELOCATE TUBE BETWEEN BLOWER  
SHELF AND INDUCER HOUSING FOR  
040,060, AND 080 HEATING INPUT  
FURNACES  
COLLECTOR BOX EXTENSION DRAIN TUBE  
COLLECTOR BOX DRAIN TUBE  
(BLUE AND WHITE STRIPED)  
CONDENSATE TRAP  
INDUCER HOUSING DRAIN TUBE (VIOLET)  
NOTE:  
1. All tubing must be connected securely and routed to avoid kinks and traps.  
2. Pressure tubing must always slope away from pressure switch to collector box connection as shown.  
3. HORIZONTAL-LEFT installations require the collector box pressure tube to be relocated between the inducer housing and the blower shelf to  
prevent a trap.Refer to the Installation Instructions for further details.  
324999-201 REV. C  
A00308  
Fig. 8Furnace Pressure and Drain Tubing Diagram  
7—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
box or inlet pipe, but can be removed without removing  
either. After removing screw, slide igniter and bracket  
toward outside of burner box and pull straight out.  
8. Turn on gas and electrical supplies to furnace.  
9. Verify igniter operation by initiating furnace control self-  
test feature or by cycling thermostat.  
10. Replace main furnace door.  
CAUTION: The igniter is fragile. DO NOT allow it to  
hit the side of the burner box opening while removing or  
replacing it.  
VII. ELECTRICAL CONTROLS AND WIRING  
CAUTION: There may be more than 1 electrical supply  
to the unit. Check accessories and cooling unit for  
additional electrical supplies.  
b. Inspect igniter for a white area indicating a crack may be  
present. If found, replace igniter.  
NOTE: A small crack cannot be seen on a new igniter. After a  
period of operation, a white area will be visible around the crack.  
The electrical ground and polarity for 115-v wiring must be  
maintained properly. Refer to Fig. 11 for field wiring information  
and to Fig. 15 for unit wiring information.  
c. If replacement is required, replace igniter on igniter  
bracket external to furnace to avoid damage as the  
silicon portion is very brittle and will easily crack or  
shatter.  
NOTE: If the polarity is not correct, the STATUS LED on the  
furnace control will flash rapidly and prevent the furnace from  
operating. The control system also requires an earth ground for  
proper operation of the furnace control and flame sensor.  
d. To remove igniter from igniter bracket, remove screw  
holding igniter ceramic block to bracket and pull ce-  
ramic block out of bracket.  
The 24-v circuit contains an automotive-type, 3-amp fuse located  
on the control center. (See Fig. 11.) Any direct shorts of the 24-v  
wiring during installation, service, or maintenance will cause this  
fuse to blow. If fuse replacement is required, use ONLY a fuse of  
identical size (3 amp). The control LED will flash status code 24  
when fuse needs to be replaced.  
6. To replace igniter/igniter assembly, reverse items 5a  
through 5d.  
7. Reconnect igniter wire connection.  
With power to the unit disconnected, check all electrical connec-  
tions for tightness. Tighten all screws on electrical connections. If  
any smoky or burned connections are found, disassemble the  
connection, clean all parts, strip wire, and reassemble properly and  
securely.  
BURNER FLAME  
BURNER  
Reconnect electrical supply to unit and observe unit through 1  
complete operating cycle for proper operation.  
VIII. CHECKING HEAT TAPE OPERATION  
(IF APPLICABLE)  
In applications where the ambient temperature around the furnace  
is 32°F or lower, freeze protection measures are required. If heat  
tape has been applied, check to ensure it will operate when low  
temperatures are present.  
CAUTION: If this furnace is to be operated in an  
unconditioned space where the ambient temperatures may  
be 32°F or lower, freeze protection measures must be  
taken. (See Fig. 13.)  
MANIFOLD  
A89020  
Fig. 9Burner Flame  
NOTE: See CONDENSATE DRAIN PROTECTION section of  
Installation, Start-Up, and Operating Instructions.  
NOTE: Heat tape, when used, should be wrapped around the  
condensate drain trap and drain line. There is no need to use heat  
tape within the furnace casing. Most heat tapes are temperature  
activated, and it is not practical to verify the actual heating of the  
tape. Check the following:  
PAM  
RTV  
1. Check for signs of physical damage to heat tape such as  
nicks, cuts, abrasions, gnawing by animals, etc.  
2. Check for discolored heat tape insulation. If any damage or  
discolored insulation is evident, replace heat tape.  
3. Check that heat tape power supply circuit is on.  
IX. WINTERIZING  
CAUTION: Freezing condensate left in the furnace will  
damage the equipment.  
If the furnace will be off for an extended period of time in a  
structure where the temperature will drop to 32° or below,  
winterize as follows:  
A93081  
Fig. 10Gasket on Collector Box  
8—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIELD 24-V WIRING  
FIELD 115-, 208/230-, 460-V WIRING  
FACTORY 24-V WIRING  
FACTORY 115-V WIRING  
NOTE 2  
THERMOSTAT  
TERMINALS  
W
C
R
G
Y
FIVE WIRE  
FIELD-SUPPLIED  
DISCONNECT  
THREE-WIRE  
HEATING-ONLY  
208/230- OR  
460-V  
BLOWER DOOR SWITCH  
THREE  
PHASE  
W
BLK  
BLK  
WHT  
C
R
WHT  
O
N
T
208/230-V  
SINGLE  
PHASE  
GND  
GND  
G
R
AUXILIARY  
J-BOX  
115-V FIELD-  
SUPPLIED  
DISCONNECT  
O
COM  
GND  
L
NOTE 1  
CONDENSING  
UNIT  
Y/Y2  
TWO  
WIRE  
24-V  
TERMINAL  
BLOCK  
NOTES: 1. Connect Y-terminal in furnace as shown for proper blower operation.  
2. Some thermostats require a "C" terminal connection as shown.  
3. If any of the original wire, as supplied, must be replaced, use  
same type or equivalent wire.  
FURNACE  
A99440  
Fig. 11Field Wiring  
1. Turn off electrical supply to furnace.  
2. Remove main furnace door.  
NOTE: Removing the blower access door will open the blower  
access door switch and terminate 115-v power to the control.  
To read current status code, remove main furnace door. The status  
code LED can be viewed through the sight glass on the blower  
access door.  
3. Disconnect cap from unused drain tap on inducer housing.  
(See Fig. 14.)  
4. Connect field-supplied 1/2-in. I.D. tube to upper inducer  
housing drain connection.  
NOTE: NO thermostat signals may be present at control and all  
blower off delays must be completed to view previous codes.  
5. Insert funnel in drain tube and pour up to 1 quart antifreeze,  
propylene glycol (RV, swimming pool antifreeze, or  
equivalent) into funnel until it is visible at point where  
condensate enters open drain. (See Fig. 15.)  
To retrieve previous codes, remove 1 of the red main limit or flame  
rollout switch wires for 1 to 4 sec until the LED light goes out, then  
reconnect it. (Do not leave red wire disconnected for longer  
periods of time as the control will assume an overtemperature  
condition exists and will respond with blower operation.) This  
places the control in the status recall mode and displays the first  
code stored in memory.  
6. Reconnect drain cap to inducer housing.  
7. Replace main furnace door.  
Record the code and repeat the disconnect and reconnect of the red  
wire, recording each code until code 11 is displayed indicating no  
addition codes. After the last code is displayed or after 2 minutes  
in the code recall mode the control will return to normal standby  
mode.  
CAUTION: Do not use ethylene glycol (Prestone II  
antifreeze/coolant or equivalent automotive type). Failure  
of plastic components will occur.  
8. Propylene glycol need not be removed before restarting  
furnace.  
B. Component Test  
WARNING: Blower access panel door switch opens  
115-v power to control center. No component operation  
can occur. Caution must be taken when manually closing  
this switch for service purposes. Failure to follow this  
warning could result in electrical shock, personal injury,  
or death.  
WIRING DIAGRAM  
See Fig. 16 for Wiring Diagram.  
TROUBLESHOOTING  
Use the Troubleshooting Guide, the status code LED on the  
cotntrol and the Component Test to isolate furnace operation  
problems.  
A. Status Codes  
Use the Component Test to check furnace components for proper  
operation. To initiate the component self-test sequence, shut off  
the room thermostat or disconnect the Rthermostat lead. Briefly  
(approximately 2 sec) short the TWIN/TEST terminal to the COM  
24V terminal. The status LED will turn off. The test sequence will  
be as follows:  
For an explanation of status codes, refer to service label located on  
back of main furnace door or Fig. 17 and the Troubleshooting  
Guide. The stored status codes will NOT be erased from the  
control memory if 115- or 24-v power in interrupted. The control  
will store up to 7 Status Codes.  
9—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TWINNING AND/OR  
COMPONENT TEST  
TERMINAL  
BLOWER OFF-DELAY  
BLOWER OFF-DELAY  
HUMIDIFIER TERMINAL  
(24-VAC 0.5 AMP MAX.)  
24-V THERMOSTAT  
TERMINALS  
TRANSFORMER 24-VAC  
CONNECTIONS  
TEST/TWIN  
HUM  
0.5 AMP@24VAC  
3-AMP FUSE  
FUSE 3-AMP  
SEC-2 SEC-1  
LED OPERATION &  
DIAGNOSTIC LIGHT  
EAC-2  
L2  
PL1-LOW VOLTAGE MAIN  
HARNESS CONNECTOR  
115-VAC(L2)NEUTRAL  
CONNECTIONS  
COOL  
HEAT  
1-AMP@  
115VAC  
FAN  
EAC-1  
SPARE-1 SPARE-2  
PR-1  
PL2  
1
SPARE-1  
SPARE-2  
PL2-HOT SURFACE  
IGNITER & INDUCER  
MOTOR CONNECTOR  
115 VAC (L1) LINE  
VOLTAGE CONNECTION  
FAN  
BLOWER SPEED  
SELECTION TERMINALS  
EAC-1 TERMINAL  
(115-VAC 1.0 AMP MAX.)  
A02142  
Fig. 12Control Center  
1. LED flashes a current status code, or code 11, 4 times.  
Record this status code for further troubleshooting.  
2. The inducer will start and continue to run until test is over.  
3. Hot surface igniter (HSI) is energized for 15 sec, then  
de-energized.  
4. The blower motor operates on HEATING speed for 10 sec,  
then turns off.  
5. The blower motor operates on COOLING speed for 10 sec,  
then turns off.  
32°F MINIMUM INSTALLED  
AMBIENT OR FREEZE  
PROTECTION REQUIRED  
6. Blower operates on continuous fan speed, then turns off.  
7. Inducer turns off.  
8. The gas valve and humidifier terminal HUM are not  
energized for safety reasons.  
A93058  
Fig. 13Winterizing the Furnace  
10—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A99118  
Fig. 14Inducer Housing Drain Tube  
A99119  
Fig. 15Funnel in Drain and Antifreeze Running  
Through Trap  
11—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TO 115VAC FIELD DISCONNECT  
(WHEN USED)  
LGPS  
SCHEMATIC DIAGRAM  
BLOWER OFF DELAY  
JUMPER SELECT  
PRS  
NOTE #2  
L1  
(NATURAL GAS & PROPANE)  
L2  
PCB  
GND  
EQUIPMENT GROUND  
FAN  
Y1  
ORN  
RED  
90  
120  
150  
180  
J1  
DHUM  
G
Com  
24V  
LO  
CAP-1  
ILK  
MED LO  
MED HI  
HI  
NOTE #11  
BLU  
HEAT  
YEL  
L1  
FAN  
BLU  
START  
SPARE-1  
COOL  
NOTE #10  
L2  
OL  
HI/LO  
W
BLWR  
GV  
M
EAC-2  
RED  
Y/Y2  
R
TEST/TWIN  
HUM  
BLWM  
ORN  
LS  
FRS  
COM  
HSI  
C
EAC-1  
HSIR  
GRN/YEL  
NOTE #3  
FU1  
NOTE #6  
RED  
GRN/YEL  
WHT  
1
2
1
2
IDR  
IDM  
WHT  
SEC-1  
SEC-2  
PL2  
PL3  
OL  
BLU  
BLK  
WHT  
PR1  
115VAC  
M
AUX  
LED 1  
EAC-2  
RED  
RED  
RED  
WHT  
L2  
TRAN  
1
CAP -2  
24VAC  
GRN/YEL  
3
2
GRN/YEL  
PL4  
TEST/TWIN  
BRN  
BRN  
PL4  
3
CAP - 2  
FRS  
YEL  
WHT  
WHT  
M
PL1  
FSE  
BLK  
NOTE #6  
F U 1  
AUX  
GRN/YEL  
BLK  
2
1
IDM  
PL2  
OL  
SEC-1  
GVR-2  
SEC-2  
LS  
6
BHT/CLR BFANR  
COOL  
BLWR  
L1  
2
1
WHT  
PL3  
WHT  
BLK  
2
1
HUM  
FAN  
HEAT  
8
2
BLK  
R
LGPS  
(WHEN USED)  
SPARE 1  
EAC-1  
SPARE 2  
PR1  
W
WHT (COM)  
PL1  
BLK (HI)  
WHT  
(COM)  
NOTE #11  
PRS  
WHT  
BLK  
JB  
BLWM  
FUSED OR CIRCUIT BREAKER  
GRN/YEL  
CAP -1  
DISCONNECT SWITCH (WHEN REQD)  
YEL  
NOTE #2  
(MED HI)  
BRN  
OL  
4
WHT  
BLK  
NEUTRAL  
L1  
WHT  
BLK  
FU2  
GV  
START  
GVR-1  
NOTE #10  
RED (LO)  
Y/Y2  
10  
M
CPU  
BLU  
(MED LO)  
ILK  
BRN  
GND  
DHUM  
Y1  
C
5
NOTE #3  
OL  
AUTO-RESET INTERNAL MOTOR OVERLOAD  
TEMPERATURE SWITCH (N.C.)  
PRINTED CIRCUIT BOARD CONTROL  
11-CIRCUIT PCB CONNECTOR  
2-CIRCUIT CONNECTOR  
2-CIRCUIT HSI, CONNECTOR  
3-CIRCUIT IDM EXTENSION CONNECTOR  
PRESSURE SWITCH, SPST-(N.O.)  
BFANR  
BHT/CLR  
BLWR  
BLWM  
CAP 1, 2  
CPU  
EAC-1  
EAC-2  
FRS  
CONTINUOUS-FAN SELECT RELAY, SPDT  
L
1
9
BLOWER MOTOR SPEED CHANGE RELAY, SPDT  
BLOWER MOTOR RELAY, SPST-(N.O.)  
BLOWER MOTOR, PERMANENT-SPLIT-CAPACITOR  
CAPACITOR  
G
E
G
E
N
D
PCB  
PL1  
PL2  
PL3  
PL4  
PRS  
FSE  
7
3
MICROPROC ESSOR AND C IRCUITRY  
COM  
PCB  
NOTE #5  
ELECTRONIC AIR CLEANER CONNECTION (115 VAC 1.0 AMP MAX.)  
ELECTRONIC AIR CLEANER CONNECTION (COMMON)  
FLAME ROLLOUT SW. -MANUAL RESET, SPST-(N.C.)  
FLAME-PROVING ELECTRODE  
11  
NOTES:  
TEST/ TWIN  
TRAN  
COMPONENT TEST & TWIN TERMINAL  
TRANSFORMER-115VAC/24VAC  
FSE  
FU 1  
FU 2  
FUSE, 3 AMP, AUTOMOTIVE BLADE TYPE, FACTORY INSTALLED  
FUSE OR CIRCUIT BREAKER CURRENT INTERRUPT DEVICE  
(FIELD INSTALLED & SUPPLIED)  
EQUIPMENT GROUND  
GAS VALVE-REDUNDANT  
1. If any of the original equipment wire is replaced use wire rated for 105°C.  
JUNCTION  
2. Use only copper wire between the disconnect switch and the furnace junction box (JB).  
3. This wire must be connected to furnace sheet metal for control to prove flame.  
4. Symbols are electrical representation only.  
UNMARKED TERMINAL  
PCB CONTROL TERMINAL  
FACTORY WIRING (115VAC)  
FACTORY WIRING (24VAC)  
FIELD WIRING (115VAC)  
FIELD WIRING (24VAC )  
CONDUCTOR ON CONTROL PCB  
FIELD WIRING SCREW TERMINAL  
FIELD EARTH GROUND  
EQUIPMENT GROUND  
FIELD SPLICE  
GND  
GV  
GVR 1, 2  
HSI  
HSIR  
HUM  
IDM  
IDR  
ILK  
J1  
JB  
LED  
LGPS  
LS  
5. Solid lines inside PCB are printed circuit board conductors and are not included in legend.  
6. Replace only with a 3 amp fuse.  
7. Inducer (IDM) and blower (BLWM) motors contain internal auto-reset thermal overload switches (OL).  
8. Neutral connections are interchangeable within the NEUTRAL connector block.  
9. Blower motor speed selections are for average conditions, see installation instructions for details on  
optimum speed selection.  
GAS VALVE RELAY, DPST-(N.O.)  
HOT SURFACE IGNITER (115 VAC)  
HOT SURFACE IGNITER RELAY, SPST-(N.O.)  
24VAC HUMIDIFIER CONNECTION (0.5 AMP. MAX.)  
INDUCED DRAFT MOTOR, PSC  
INDUCED DRAFT MOTOR RELAY, SPST-(N.O.)  
BLOWER ACCESS PANEL INTERLOCK SWITCH, SPST-(N.O.)  
BLOWER - OFF DELAY JUMPER SELECTOR  
JUNCTION BOX  
LIG HT-EMITTING DIODE FOR STATUS CODES - AMBER  
LOW GAS PRESSURE SWITCH, SPST-(N.O.)  
LIMIT SWITCH, AUTO-RESET, SPST (N.C.)  
10. YELLOW lead not on all motors.  
11. Factory connected when LGPS is not used.  
12. Ignition-lockout will occur after four consecutive unsuccessful trials-for-ignition. Control will  
auto-reset after three hours.  
13. Blower-on delay: gas heating 60 seconds, cooling or heat pump 2 seconds.  
14. Blower-off delay: gas heating selections are 90, 120, 150 or 180 seconds, cooling or heat pump  
90 seconds or 5 seconds when dehumidify call is active.  
PLUG RECEPTACLE  
326796-101 REV. A  
Fig. 16Wiring Diagram  
A02157  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICE  
If status code recall is needed, briefly remove then reconnect one main limit wire to display  
stored status code. On RED LED boards do not remove power or blower door before initiat-  
ing status code recall. After status code recall is completed component test will occur.  
LED CODE  
STATUS  
CONTINUOUS OFF - Check for 115VAC at L1 & L2, & 24VAC at SEC-1 & SEC-2.  
CONTINUOUS ON - Control has 24VAC power.  
RAPID FLASHING - Line voltage (115VAC) polarity reversed. If twinned,  
refer to twinning kit instructions.  
EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WITH THE FIRST  
DIGIT DETERMINED BY THE NUMBER OF SHORT FLASHES AND THE SECOND DIGIT BY  
THE NUMBER OF LONG FLASHES.  
11 NO PREVIOUS CODE - Stored status code is erased automatically after 72  
hours. On RED LED boards stored status codes can also be erased when power  
(115 VAC or 24 VAC) to control is interrupted.  
12 BLOWER ON AFTER POWER UP (115 VAC or 24 VAC) -Blower runs for 90  
seconds, if unit is powered up during a call for heat (R-W closed) or R-W opens  
during blower on-delay.  
13 LIMIT CIRCUIT LOCKOUT - Lockout occurs if the limit or flame rollout switch is  
open longer than 3 minutes.  
- Control will auto reset after three hours.  
- Refer to #33.  
14 IGNITION LOCKOUT - Control will auto-reset after three hours. Refer to #34.  
21 GAS HEATING LOCKOUT - Control will NOT auto reset.  
Check for: - Mis-wired gas valve  
-Defective control (valve relay)  
22 ABNORMAL FLAME-PROVING SIGNAL - Flame is proved while gas valve is  
de-energized. Inducer will run until fault is cleared. Check for:  
- Leaky gas valve  
- Stuck-open gas valve  
23 PRESSURE SWITCH DID NOT OPEN Check for:  
- Obstructed pressure tubing.  
- Pressure switch stuck closed.  
24 SECONDARY VOLTAGE FUSE IS OPEN Check for:  
- Short circuit in secondary voltage (24VAC) wiring.  
31 PRESSURE SWITCH DID NOT CLOSE OR REOPENED - If open longer than  
five minutes, inducer shuts off for 15 minutes before retry. Check for:  
- Excessive wind - Proper vent sizing  
- Low inducer voltage (115VAC)  
- Inadequate combustion air supply  
- Disconnected or obstructed pressure tubing  
- Low inlet gas pressure (if LGPS used)  
- Defective inducer motor  
- Defective pressure switch  
- Restricted vent  
If it opens during blower on-delay period, blower will come on for the selected  
blower off-delay.  
33 LIMIT CIRCUIT FAULT - Indicates a limit, or flame rollout is open. Blower will  
run for 4 minutes or until open switch remakes whichever is longer. If open  
longer than 3 minutes, code changes to lockout #13. If open less than 3 minutes  
status code #33 continues to flash until blower shuts off. Flame rollout switch  
requires manual reset. Check for: - Restricted vent  
- Proper vent sizing  
- Loose blower wheel  
- Excessive wind  
- Dirty filter or restricted duct system.  
- Defective blower motor or capacitor. - Defective switch or connections.  
- Inadequate combustion air supply (Flame Roll-out Switch open).  
34 IGNITION PROVING FAILURE - Control will try three more times before lockout  
#14 occurs. If flame signal lost during blower on-delay period, blower will come  
on for the selected blower off-delay. Check for: - Control ground continuity  
- Flame sensor must not be grounded  
- Oxide buildup on flame sensor (clean with fine steel wool).  
- Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal).  
- Gas valve defective or gas valve turned off  
- Defective Hot Surface Ignitor  
- Manual valve shut-off  
- Low inlet gas pressure  
- Inadequate flame carryover or rough ignition  
- Green/Yellow wire MUST be connected to furnace sheet metal  
45 CONTROL CIRCUITRY LOCKOUT Auto-reset after one hour lockout due to;  
- Gas valve relay stuck open  
- Software check error  
- Flame sense circuit failure  
Reset power to clear lockout. Replace control if status code repeats.  
COMPONENT TEST  
To initiate the component test sequence, shut OFF the room thermostat or disconnect  
the "R" thermostat lead. Briefly short the TEST/TWIN terminal to the "Com 24V" ter-  
minal. Status LED will flash code and then turn ON the inducer motor. The inducer  
motor will run for the entire component test. The hot surface ignitor, blower motor  
FAN speed (AMBER LED boards only) blower motor HEAT speed, and blower motor  
COOL speed will be turned ON for 10-15 seconds each. Gas Valve and Humidifier  
will not be turned on.  
327884-101 REV. A  
A02154  
Fig. 17Service Label  
13—  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLESHOOTING GUIDE  
START  
Is LED status light on?  
NO  
NO  
NO  
NO  
Is there 115V at L1 and L2?  
Is door switch closed?  
Close door switch and go back to START.  
YES  
YES  
YES  
Is there 115V going to switch?  
YES  
NO  
Is there 24V at SEC-1 and SEC-2?  
YES  
Is circuit breaker closed?  
YES  
NO  
Replace furnace control.  
Replace door switch.  
Check for continuity in wire from circuit breaker  
to furnace.  
Check for correct line voltage polarity. If units  
are twinned, check for proper low-voltage  
(24V) transformer phasing.  
YES  
NO  
Replace transformer.  
Close circuit breaker and go back to START.  
Is LED status light blinking rapidly without a  
pause?  
NO  
To recall status code briefly remove and reconnect one RED wire from the Limit  
Switch or Flame Rollout switch to display stored status code. On RED LED  
control do not remove power or blower access panel before initiating status  
code recall. You can also recall the previous status code by momentarily shorting  
the TEST/TWIN terminal to Com24V terminal until the LED goes out. LED will  
flash the previous status code or status code #11 (1 short and 1 long flash) if  
there was no previous code. After the control repeats the code 4 times, the  
control will go through a brief component test sequence. The inducer will start  
and run for the entire component test. The HSI, blower motor FAN speed  
(AMBER LED boards only) HEAT speed, and COOL speed will run for 10 15  
seconds each. Gas valve and humidifier will not be turned on.  
Is LED status light blinking ON/OFF slowly  
with a combination of short and long flashes?  
YES  
Determine status code. The status code is a  
2 digit number with the first digit determined  
by the number of short flashes and the second  
digit by the number of long flashes?  
Check room thermostat or  
interconnecting cable.  
NO  
YES  
NO  
Does the control respond to W,Y1 (if present),  
Y/Y2, and G (24V) thermostat signals?  
Is 24V present at W, Y1 (if present), Y/Y2 or  
G thermostat terminals on the furnace control?  
Was there a previous status code  
other than #11?  
NO  
Go to section below for the status code that  
was flashed.  
YES  
YES  
Run system through a heating or cooling cycle  
to check operation. Status codes are erased  
after 72 hours. On RED LED boards stored  
status codes can also be erased whenever  
(115V or 24V) is interrupted.  
Disconnect all the thermostat wires from the  
furnace control.  
YES  
Does the problem repeat when using  
a jumper wire?  
Replace furnace control.  
NO  
The thermostat is not compatible with the  
furnace control. Either install a ballast resistor,  
connect the Com24V thermostat terminal to  
the thermostat, or replace the thermostat.  
A02204a  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11 NO PREVIOUS CODE Stored codes  
are erased after 72 hours. On RED LED  
boards stored status codes can also be  
erased whenever power (115V or 24V)  
is interrupted. Run system through a  
heating or cooling cycle to check system.  
31 PRESSURE SWITCH DID NOT CLOSE  
OR REOPENED If open longer than 5  
minutes, inducer shuts off for 15 minutes  
before retry. If opens during blower on-  
delay period, blower will come on for the  
selected blower off-delay. Check for:  
45 CONTROL CIRCUITRY LOCKOUT  
Auto-reset after 1 hour lockout due to:  
-
Flame circuit failure.  
Gas valve relay stuck open.  
-
-
Software check error.  
Reset power to clear lockout. Replace  
control if code repeats.  
-
-
-
-
-
Proper vent sizing.  
Low inducer voltage (115V).  
Low inlet gas pressure (if LGPS used).  
Inadequate combustion air supply.  
Disconnected or obstructed pressure  
tubing.  
12 BLOWER ON AFTER POWER UP –  
(115V OR 24V) Normal operation.  
Blower runs for 90 seconds, if unit is  
powered up during a call for heat (R-W  
closed) or when (R-W opens) during the  
blower on-delay period.  
NO  
Unplug igniter harness from control and initiate  
another component test sequence. Check  
for 115V between pin 1 and NEUTRAL-L2 on  
the control. Was 115V present for the 15  
second period?  
Replace furnace control.  
-
-
-
-
Defective inducer motor.  
Defective pressure switch.  
Excessive wind.  
YES  
NO  
Check for continuity in the harness and igniter.  
Replace defective component.  
Restricted vent.  
13 LIMIT CIRCUIT LOCKOUT Lockout  
occurs if the limit or flame rollout switch is  
open longer than 3 minutes. Control will  
auto-reset after 3 hours. See code 33.  
33 LIMIT CIRCUIT FAULT Indicates the  
limit or flame rollout switch is open. Blower  
will run for 4 minutes or until open switch  
remakes whichever is longer. If open  
longer than 3 minutes, code changes to  
lockout #13. If open less than 3 min.  
status code #33 continues to flash until  
blower shuts off. Flame rollout switch  
requires manual reset. Check for:  
Reconnect the R thermostat lead and set  
thermostat to call for heat. Connect voltmeter  
across gas valve connections. Does gas valve  
receive 24V?  
Check connections. If OK, replace control.  
Check that all gas valves are turned on.  
Replace valve.  
YES  
14 IGNITION LOCKOUT System failed to  
ignite gas and prove flame in 4 attempts.  
Control will auto-reset after 3 hours.  
See status code 34.  
Does gas valve open and allow gas to flow?  
Check for:  
NO  
NO  
-
Inadequate flame carryover or rough  
ignition.  
-
-
-
-
-
Dirty filter or restricted duct system.  
Loose blower wheel.  
YES  
-
-
-
Low inlet gas pressure.  
Proper firing rate.  
Check for air leakage around igniter bracket.  
Defective switch or connections.  
Defective blower motor or capacitor.  
Inadequate combustion air supply  
(flame rollout switch open).  
Restricted vent.  
Do the main burners ignite?  
21 GAS HEATING LOCKOUT Turn off  
power and wait 5 minutes to retry.  
Check for:  
YES  
Do the main burners stay on?  
NO  
-
-
-
YES  
NO  
Proper vent sizing.  
Excessive wind.  
-
-
Stuck closed gas valve relay on control.  
Miswire or short to gas valve wire.  
Allow blower to come on and repeat test to  
check for intermittent operation.  
- Blower motor on incorrect speed tap.  
- Input rate to furnace set too high.  
22 ABNORMAL FLAME-PROVING SIGNAL  
Flame is proved while gas valve is de-  
energized. Inducer will run until fault is  
cleared. Check for:  
Check connections and retry. If current is  
near typical value (4.0-6.0 nominal) and  
burners will not stay on, replace control.  
Repeat call for heat and check flame sensor  
current during trial for ignition period. Is the  
DC microamps below 0.5?  
34 IGNITION PROVING FAILURE If flame  
is not sensed during the trial for ignition  
period, the control will repeat the ignition  
sequence 3 more times before lockout  
#14 occurs. If flame signal is lost during  
the blower on-delay period, blower will  
come on for the selected blower off-delay.  
Check the following items first before  
proceeding to the next step.  
-
Stuck open or leaky gas valve.  
NO  
YES  
YES  
23 PRESSURE SWITCH DID NOT OPEN  
Check for:  
Clean flame sensor with fine steel wool and  
recheck current. Nominal current is 4.0 to 6.0  
microamps.  
-
-
Obstructed pressure tube.  
Pressure switch stuck closed.  
-
-
-
Gas valve turned off.  
Manual shut-off valve.  
Green/Yellow wire MUST be connected  
to furnace sheet metal.  
24 SECONDARY VOLTAGE FUSE IS OPEN  
Check for:  
-
Short circuit in secondary voltage (24V)  
wiring including thermostat leads.  
Disconnect thermostat leads to isolate  
short circuit.  
-
Flame sensor must not be grounded.  
NO  
NO  
Is current near typical value?  
Replace electrode.  
To determine whether the problem is in  
the gas valve, igniter, or flame sensor the  
system can be operated in the component  
test mode to check the igniter. First  
remove the R thermostat connection from  
the control and initiate the component  
test sequence. Does the igniter glow  
orange/white by the end of the 15 second  
warm-up period?  
YES  
Will main burners ignite and stay on?  
Replace furnace control.  
YES  
Fixed.  
A02204b  
Download from Www.Somanuals.com. All Manuals Search And Download.  
© 2002 Bryant Heating & Cooling Systems 7310 W. Morris St. Indianapolis, IN 46231  
Printed in U.S.A.  
sp0558  
Catalog No. 5335-207  
16—  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Black Decker Blender IB10 User Manual
Boston Acoustics Speaker Voyager 7 User Manual
Braun Trimmer 5377 User Manual
Brother Landscape Lighting DCP 9045CDN User Manual
Canon All in One Printer 4502B017 User Manual
Canon Camcorder AF310XL User Manual
Canon Camcorder DC 10 User Manual
Celestron Telescope 52291 User Manual
Char Broil Gas Grill 415161209 User Manual
Chief Manufacturing Indoor Furnishings KCG220 User Manual