INSTALLATION INSTRUCTIONS
AND USER MANUAL
M O D E L S
HEPA 2000*
HF 2.0*
HEPA 1000*
HF 1.0*
HEPA 3000*
HF 3.0*
VB0061
*Patents pending
HEPA 4000*
NOTE: HEPA 4000 model available in United States only.
RESIDENTIAL USE ONLY
READ AND SAVE THESE INSTRUCTIONS
INSTALLER: LEAVE THIS MANUAL WITH THE HOMEOWNER.
HOMEOWNER: USE AND CARE INFORMATION
ON PAGES 28 and 32 to 36.
04313 rev C
Download from Www.Somanuals.com. All Manuals Search And Download.
ABOUT THESE UNITS
!
WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO
PERSON(S) OBSERVE THE FOLLOWING:
1. This unit is intented for residential installation only.
2. Use this unit only in the manner intended by the manufacturer. If you have
questions, contact the manufacturer at the address or telephone number listed
in the warranty.
3. Before replacing filters, servicing or cleaning unit, disconnect power cord from
electrical outlet.
4. Installation must be done in accordance with all applicable codes and standards,
including fire-rated construction codes and standards.
5. This unit is not designed to provide combustion and/or dilution air for fuel-burning
appliances.
6. When cutting or drilling into wall or ceiling, do not damage electrical wiring and
other hidden utilities.
7. Do not use this unit with any solid-state speed control device other than
optional wall controls C12, CM, C34 and CMR (sold separately).
8. This unit must be grounded. The power supply cord has a 3-prong grounding
plug for your personal safety. It must be plugged into a mating 3-prong grounding
receptacle, grounded in accordance with the national electrical code and local
codes and ordinances. Do not remove the ground prong. Do not use an
extension cord.
9. Do not install in a cooking area or connect directly to any appliances.
10. Do not use to exhaust hazardous or explosive materials and vapors.
CAUTION
1. To avoid prematurate clogged filters, turn OFF the unit during construction or
renovation.
2. Please read specification label on product for further information and requirements.
3. For HEPA 2000, HF 2.0, HEPA 3000, HF 3.0 and HEPA 4000 units only: Be
sure to duct air outside – Do not intake / exhaust air into spaces within walls
or ceiling or into attics, crawl spaces, or garage.
4. Itended for residential installation only in accordance with the requirements of
NFPA 90B.
5. Do not run any air ducts directly above or closer than 2 ft (0.61 m) to any furnace
or its supply plenum, boiler, or other heat producing appliance. For HEPA 2000,
HF 2.0, HEPA 3000, HF 3.0 and HEPA 4000 units only, if a duct has to be
connected to the furnace return plenum, it must be connected not closer than
9’10” (3 m) from this plenum connection to the furnace. For HEPA 1000 and
HF 1.0 units only, the distance must be not closer than 2’ (0.61 m).
6. The ductwork is intended to be installed in compliance with all local and
national codes that are applicable.
- 3 -
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE OF CONTENTS
1.0
BEFORE STARTING . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
1.1 Inspect the Content of the Boxes . . . . . . . . . . .. . 6
2.0
TYPICAL INSTALLATIONS . . . . . . . . . . . . . . . . . . . . . . . .6
2.1 HEPA 1000 and HF 1.0 Unit Installations . . . . . . 7
2.1.1 Stand Alone . . . . . . . . . . . . . . . . . . . . . . . . . .7
2.1.2 Central Draw Point . . . . . . . . . . . . . . . . . . . . .8
2.1.3 Return-to-Return Installation . . . . . . . . . . . . . . . .9
2.2 Installations for HEPA 4000 Only . . . . . . . . . . . .10
2.2.1 Geographical Location . . . . . . . . . . . . . . . . .10
2.2.2 HEPA 4000 Attic Installation . . . . . . . . . . . . . .11
2.3 HEPA 2000, HF 2.0, HEPA 3000, HF 3.0
and HEPA 4000 Unit Installations . . . . . . . . . . . .12
2.3.1 Stand Alone . . . . . . . . . . . . . . . . . . . . . . . . .12
2.3.2 Central Draw Point . . . . . . . . . . . . . . . . . . . .13
2.3.3 Return-to-Return Installation . . . . . . . . . . . . . . .14
3.0
DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
3.1 HEPA 1000 and HF 1.0 Units . . . . . . . . . . . . . .15
3.2 HEPA 2000, HF 2.0, HEPA 3000, HF 3.0
and HEPA 4000 units . . . . . . . . . . . . . . . . . . . .15
3.3 Mounting and Servicing Considerations . . . . . . . .16
4.0
INSTALL THE UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . .17
4.1 Locating and Mounting the Unit . . . . . . . . . . . . .17
4.2 Mount the Ports on the Unit . . . . . . . . . . . . . . . .17
4.3 How to Hang the Unit . . . . . . . . . . . . . . . . . . .18
4.4 Planning of the Ductwork . . . . . . . . . . . . . . . . .19
4.5 Installing Ductwork and Registers . . . . . . . . . . . .20
4.5.1 Stand Alone System . . . . . . . . . . . . . . . . . . .20
4.5.2 Central Draw Point . . . . . . . . . . . . . . . . . . . .21
4.5.3 Return-to-Return . . . . . . . . . . . . . . . . . . . . . .22
- 4 -
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE DES MATIÈRES
4.6 Installation des conduit flexibles isolés . . . . . . . . .23
4.6.1 Raccordement à la transition Tandem® . . . . . .23
4.6.2 Raccordement aux bouches ovales de 5”à 6” . .24
4.7 Installation de la bouche extérieure double . . . . . .25
4.7.1 Assemblage de la bouche extérieure double . . .25
4.7.2 Localisation de la bouche extérieure double . . .25
4.7.3 Raccordement de la transition Tandem®
à la bouche extérieure double . . . . . . . . . . . . .25
4.8 Raccordement du boyau de drainage . . . . . . . . .27
5.0
CONTRÔLES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
5.1 Interrupteur principal . . . . . . . . . . . . . . . . . . . .28
5.2 Contrôle muraux optionnels . . . . . . . . . . . . . . . .28
5.3 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . .28
5.4 Installation des contrôles muraux optionnels . . . . .29
5.5 Fonctionnement du contrôle C12 / CM . . . . . . . .32
5.5.1 Description du contrôle C12 / CM . . . . . . . . .32
5.5.2 Utilisation du contrôle C12 / CM . . . . . . . . . .32
5.6 Fonctionnement du contrôle C34 / CMR . . . . . . .33
5.6.1 Description du contrôle C34/ CMR . . . . . . . .33
5.6.2 Utilisation du contrôle C34 / CMR . . . . . . . . .33
6.0
ENTRETIEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
6.1 Entretien semestriel . . . . . . . . . . . . . . . . . . . . . .34
6.2 Entretien annuel . . . . . . . . . . . . . . . . . . . . . . .36
6.3 Réinitialisation générale . . . . . . . . . . . . . . . . . . .36
7.0
8.0
PIÈCES DE SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . .37
DÉPANNAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
- 5 -
Download from Www.Somanuals.com. All Manuals Search And Download.
1. BEFORE STARTING
1.1 INSPECT THE CONTENTS OF THE BOXES
!
WARNING
0
To avoid risk of suffocation, discard the plastic bag wrapping the unit.
• Inspect the exterior of the unit for shipping damage. Ensure that there is
no damage to the door, door latches, main switch, etc.
CAUTION
Remove the cardboard strip inside the unit (if applicable).
• Inspect the interior of the unit for damage. Ensure that blower assembly, heat
recovery core (HEPA 3000 et HF 3.0), energy recovery core (HEPA 4000),
insulation, dampers (HEPA 2000, HF 2.0, HEPA 3000, HF 3.0 and HEPA 4000),
prefilter, HEPA filter, etc. are all intact.
2. TYPICAL INSTALLATIONS
Installations may vary according to the model number and the position in which
the unit is installed. Use the following illustrations as guidelines to help you decide
on how your unit will be installed.
All the units should be hung to the joist, and installed either vertically or
horizontally. NOTE: For more details, see Point 5.3 in Section 5 INSTALL THE
UNIT.
In every case, bathroom fans and a range hood should be used to exhaust stale
air. Also, for homes with more than one level, we recommend one exhaust
register at the highest level.
There are 3 installation methods: Stand Alone, Central Draw Point and Return-to-
Return Installation.
NOTE: An electrical outlet has to be available within 3 feet from the unit.
- 6 -
Download from Www.Somanuals.com. All Manuals Search And Download.
2. TYPICAL INSTALLATIONS (CONT’D)
2.1 HEPA 1000 AND HF 1.0 UNIT INSTALLATIONS
2.1.1 STAND ALONE (Primarily for homes with radiant hot water or electric
baseboard heating.)
Stale air is drawn to the unit by the register located at the highest level of the
house. Filtered air is supplied by the register located at the lowest level.
See figure below.
- 7 -
Download from Www.Somanuals.com. All Manuals Search And Download.
2. TYPICAL INSTALLATIONS (CONT’D)
2.1 HEPA 1000 AND HF 1.0 UNIT INSTALLATIONS (CONT’D)
2.1.2 CENTRAL DRAW POINT (CONNECTION TO FORCED AIR SYSTEM)
Stale air is drawn to the unit by the register located at the highest level of the
house. Filtered air is supplied to the return (plenum) of the forced air unit.
For this type of installation, it is not essential that the forced air system blower
runs when the unit is in operation, but we recommend it.
See figure below.
NOTE: Home with multiple forced air systems should have 1 unit on each system.
VH0038
CAUTION
Do not connect the unit (HEPA 1000 or HF 1.0) on any forced air system supply
duct. Connect it only to the air return duct. Do not install duct or duct
connector directly above the forced air unit or not less than 2’ (0.61 m) of the
plenum connection to the forced air unit, as measured along the length of
the duct.
- 8 -
Download from Www.Somanuals.com. All Manuals Search And Download.
2. TYPICAL INSTALLATIONS (CONT’D)
2.1 HEPA 1000 AND HF 1.0 UNIT INSTALLATIONS (CONT’D)
2.1.3 RETURN-RETURN INSTALLATION (CONNECTION TO A FORCED AIR SYSTEM)
Filtered air and stale air flow through the forced air system ducts which simplifies
the installation. Filtered air is supplied to the return (plenum) of the forced air unit.
To avoid cross-contamination and achieve highest efficiencies, the forced air system
blower must always be ON (or the unit efficiency will be affected).
See figure below.
NOTE: Home with multiple forced air systems should have 1 unit on each system.
CAUTION
Do not connect the unit (HEPA 1000 or HF 1.0) on any forced air system supply
duct. Connect it only to the air return duct. Do not install duct or duct
connector directly above the forced air unit or not less than 2’ (0.61 m) of the
plenum connection to the forced air unit, as measured along the length of
the duct.
- 9 -
Download from Www.Somanuals.com. All Manuals Search And Download.
2. TYPICAL INSTALLATIONS (CONT’D)
2.2 INSTALLATION FOR HEPA 4000 ONLY
2.2.1 GEOGRAPHICAL LOCATION
The HEPA 4000 unit was created to meet specific requirements related to
geographic locations. Take a look on the map below. The shaded area shows
where the HEPA 4000 can be installed.
HELENA
OLYMPIA
BISMARCK
ST. PAUL
SALEM
MADISON
BOISE
DETROIT
BOS
DES MOINES
SALT LAKE CITY
HARTFORD
HARRISBURG
COLUMBUS
INDIANAPOLIS
DENVER
RENO
SPRINGFIELD
TOPEKA
WASHINGTON
SACRAMENTO
NASHVILLE
RALEIGH
SANTA FE
OKLAHOMA CITY
COLUMBIA
ATLANTA
PHOENIX
HEPA 4000 RESTRICTED AREA
BATON ROUGE
AUSTIN
VN0005A
CAUTION
Never install an HEPA 4000 unit out of the HEPA 4000 restricted area.
NOTE:The HEPA 4000 unit is designed to assist in the management of humidity
introduced into the home. In extreme humidity conditions, the use of additional
dehumidification may be desirable. Quickly remove all excess moisture and
keep areas clean.
- 10 -
Download from Www.Somanuals.com. All Manuals Search And Download.
2. TYPICAL INSTALLATIONS (CONT’D)
2.2 INSTALLATION FOR HEPA 4000 ONLY (CONT’D)
2.2.2 HEPA 4000 ATTIC INSTALLATION
All 3 types of installation can be used in the attic (Stand Alone, Central Draw Point
or Return-Return). The example shown below is a Return-Return installation
(connection to a forced air system).
CAUTION
Due to the potential temperature difference between the attic and the rest of
the house, all unit ducts must be insulated.
CAUTION
The attic temperature must always be above 0°C (32°F).
A portion of stale air is exhausted to the outside and the rest is drawn to the unit.
Outside fresh air is blended with interior air and then filtered. This filtered air is
supplied to the return (plenum) of the forced air unit.
To avoid the cross-contamination and achieve highest efficiencies, the forced air
system blower must always be ON (or the unit efficiency will be affected).
See figure below.
NOTE: Home with multiple forced air systems should have 1 unit on each system.
VH0051
CAUTION
Do not connect the HEPA 4000 on any forced air system supply duct.
Connect it only to the air return duct. Do not install duct or duct connector
directly above the forced air unit or not less than 9’10’’ (3 m) of the plenum
connection to the forced air unit, as measured along the length of the duct.
- 11 -
Download from Www.Somanuals.com. All Manuals Search And Download.
2. TYPICAL INSTALLATIONS (CONT’D)
2.3 HEPA 2000, HF 2.0, HEPA 3000, HF 3.0 AND HEPA 4000
UNIT INSTALLATIONS
2.3.1 STAND ALONE (Primarily for homes with radiant hot water or electric
baseboard heating.)
A portion of stale air (coming from the register located at the highest level of the
house) is exhausted to the outside and the rest is drawn to the unit. Outside fresh
air is blended with interior air and then filtered. Fresh filtered air is supplied by the
register located in the lowest livable level. See figure below.
VH0039
- 12 -
Download from Www.Somanuals.com. All Manuals Search And Download.
2. TYPICAL INSTALLATIONS (CONT’D)
2.3 HEPA 2000, HF 2.0, HEPA 3000, HF 3.0 AND HEPA 4000 UNIT
INSTALLATIONS (CONT’D)
2.3.2 CENTRAL DRAW POINT (CONNECTION TO A FORCED AIR SYSTEM)
A portion of stale air (coming from the register located in the highest level of the
house) is exhausted to the outside and the rest is drawn to the unit. Outside fresh
air is blended with interior air and then filtered. This filtered air is supplied to the
return (plenum) of the forced air unit.
For this type of installation, it is not essential that the forced air system blower
runs when the unit is in operation, but we recommend it.
See figure below.
NOTE: Home with multiple forced air systems should have 1 unit on each system.
CAUTION
Do not connect the unit (HEPA 2000, HF2.0, HEPA 3000, HF 3.0 or HEPA 4000)
on any forced air system supply duct. Connect it only to the air return duct.
Do not install duct or duct connector directly above the forced air unit or
not less than 9’10’’ (3 m) of the plenum connection to the forced air unit, as
measured along the length of the duct.
- 13 -
Download from Www.Somanuals.com. All Manuals Search And Download.
2. TYPICAL INSTALLATIONS (CONT’D)
2.3 HEPA 2000, HF 2.0, HEPA 3000, HF 3.0 AND HEPA 4000 UNIT
INSTALLATIONS (CONT’D)
2.3.3 RETURN-TO-RETURN INSTALLATION (CONNECTION TO A FORCED AIR SYSTEM)
A portion of stale air is exhausted to the outside and the rest is drawn to the unit.
Outside fresh air is blended with interior air and then filtered. This filtered air is
supplied to the return (plenum) of the forced air unit.
To avoid the cross-contamination and achieve highest efficiencies, the forced air
system blower must always be ON (or the unit efficiency will be affected).
The HEPA 2000 and HF 2.0 units need to be ON all the time, since they don’t
have motorized dampers. If these units are OFF, then the forced air unit will draw
outdoor air inside.
NOTE: Home with multiple forced air systems should have 1 unit on each system.
VH0043
CAUTION
Do not connect the unit (HEPA 2000, HF2.0, HEPA 3000, HF 3.0 or HEPA 4000)
on any forced air system supply duct. Connect it only to the air return duct.
Do not install duct or duct connector directly above the forced air unit or
not less than 9’10’’ (3 m) of the plenum connection to the forced air unit, as
measured along the length of the duct.
- 14 -
Download from Www.Somanuals.com. All Manuals Search And Download.
3. DIMENSIONS
3.1 HEPA 1000 AND HF 1.0 UNITS
29''
(737 mm)
17.8''
(452 mm)
22.9'' (581 mm)
VK0047
FRONT VIEW
TOP VIEW
3.2 HEPA 2000, HF 2.0, HEPA 3000, HF 3.0 AND HEPA 4000 UNITS
29.4''
(748 mm)
17.8''
(452 mm)
22.9'' (581 mm)
VK0048
FRONT VIEW
TOP VIEW
- 15 -
Download from Www.Somanuals.com. All Manuals Search And Download.
3. DIMENSIONS (CONT’D)
3.3 MOUNTING AND SERVICING CONSIDERATIONS
•
The two following pictures are showing the minimum clearance needed
to open the door completely.
8”
(203 mm)
22”
(559 mm)
22.5”
15.75”
(572 mm)
(400 mm)
VD0117
VD0116
NOTE: A minimum of 8” (203 mm) clearance from any obstruction on top of the
unit is required for the ductwork radius turn.
®
•
The joist opening needed to install the Tandem tansition must be 9 3/4”
®
(248 mm) minimum. Also, the maximum height of the Tandem transition
®
is 8 3/4” (222 mm). See Tandem transition end view below.
9 3/4"
248 mm
8 3/4"
222 mm
VD0118
- 16 -
Download from Www.Somanuals.com. All Manuals Search And Download.
4. INSTALL THE UNIT
4.1 LOCATING AND MOUNTING THE UNIT
Choose an appropriate location for the unit.
• Within an area of the house where the ambiant temperature is between 10°C
(50°F) and 65°C (149°F) (basement, furnace room, closet, etc.).
• So as to provide easy access to the interior of the unit, for filter maintenance.
• Close to an exterior wall, so as to limit the length of the insulated flexible
duct to and from the unit (not necessary for HEPA 1000 and HF 1.0 units).
• Away from hot chimneys and other fire hazards.
• Allow for a power source (standard 3-prong grounding outlet).
• Close to a drain. If no drain is close by, use a pail to collect run-off.
(for HEPA 3000 and HF 3.0 units only).
Here are the tools and materials needed to perform the installation:
- Phillips screwdriver #2 or Robertson #1
- Hammer and flat blade screwdriver (for plenum connection installation only, to
make holes in existing metal duct)
- Scissors or utility knife (to cut duct tape)
- Duct tape
- Tin snips or metal shear (for plenum connection installation only, to cut ductwork)
- Aluminum duct tape (for plenum connection installation only)
- Jig saw (except for the HEPA 1000 unit)
- Caulking gun and caulking (except for HEPA 1000 and HF 1.0 units)
4.2 MOUNT THE PORTS ON THE UNIT
Mount the 8” oval ports and the 5” to 6” oval
ports on the top of the unit using the screws
provided in the hardware box (4 screws
#8 x 3/4” long per port).
NOTES: 1. The HEPA 1000 and the HF 1.0
units don’t have the 5” to 6” oval
ports.
2. If an optional wall control has to be
installed, do not install the front
8’’ oval port at this time.
VO0018
- 17 -
Download from Www.Somanuals.com. All Manuals Search And Download.
4. INSTALL THE UNIT (CONT’D)
4.3 HOW TO HANG THE UNIT
Use the 4 chains and springs in the hardware pack provided with the unit.
According to your needs, you can install the unit either in vertical or horizontal
position.
VERTICAL POSITION - ALL MODELS
VD0074
HORIZONTAL POSITION (RIGHT SIDE)
MODELS HEPA 1000, HF 1.0
HEPA 2000, HF 2.0 AND
HEPA 4000 ONLY
HORIZONTAL POSITION (LEFT SIDE)
ALL MODELS
VD0075
VD0076
- 18 -
Download from Www.Somanuals.com. All Manuals Search And Download.
4. INSTALL THE UNIT (CONT’D)
4.3 HOW TO HANG THE UNIT (CONT’D)
• Turn the switch knob to OFF position in
order to unlock the door. Unlatch the door
and open it. Using a screwdriver, remove
the 2 retaining screws of the front plate and
carefully remove the front plate from the unit.
VO0019
• Insert the 4 hooks in the square holes and fix them to the
unit using 4 screws #8 - 32 x 3/4”.
NOTE: If an optional wall controll has to be installed, go to
Section 5.0 on pages 29 to 31. If not, continue the installation.
• Reinstall the front plate and close the door.
VO0020
• Hang the unit to the floor joist, using 4 #8 x 1 1/2” screws, 4 chains and
4 spings. See following illustration.
VD0077
4.4 PLANNING OF THE DUCTWORK
• Keep it simple. Plan for a minimum of bends and joints.
• Keep the length of outside insulated duct to a minimum (not for HEPA 1000).
• Do not ventilate crawl spaces or cold rooms. Do not attempt to recover the
exhaust air from a dryer or a range hood. This would cause clogging of the
filters and recovery module (if applicable).
• If the house has two floors or more, be sure to plan for at least one exhaust
register on the highest lived-in level.
- 19 -
Download from Www.Somanuals.com. All Manuals Search And Download.
4. INSTALL THE UNIT (CONT’D)
4.5 INSTALLING 8’’ DUCTS AND REGISTERS
4.5.1 STAND ALONE SYSTEM (AS ILLUSTRATED IN SECTIONS 2.1.1 AND 2.3.1)
Stale air exhaust ductwork
!
WARNING
0
Never install a stale air exhaust register in a closed room where a combustion
device operates, such as a gas furnace, a gas water heater or a fireplace.
• Install the stale air exhaust register in the main area where the contaminants
are produced: kitchen, living room, etc. Position the register as far from the
stairway as possible and in such a way that the air circulates in all the lived-in
spaces in the house. If desired, you can install another register (sold separately).
NOTE: If an additional register is installed, connect it to a 8” flexible duct.
• If the register is installed in the kitchen, it must be located at least 4 feet
(1.2 m) from the range.
• Install the register 6 to 12 inches (152 to 305 mm) from the ceiling on an
interior wall OR install it in the ceiling.
Fresh / Filtered air distribution ductwork
• Install the fresh / filtered air distribution register in a large, open area in the
lowest level to ensure the greatest possible air circulation. Keep in mind that
the filtered air register must be located as far as possible from the stale air
register. If desired, you can install another register (sold separately).
NOTE: If an additional register is installed, connect it to a 8” flexible duct.
• Install the register in the ceiling OR 6 to 12 inches (152 to 305 mm) from the
ceiling on an interior wall. The duct lenght should be at least 15’ (4.6 m).
(The filtered air will then flow through the room and mix with room air, ensuring
a continuous recirculating airflow.)
How to connect the 8’’ flexible duct to the registers and unit ports.
• Once the register location
is determined, cut out a
10-1/4’’ x 6 7/8’’ (260 mm x
175 mm) hole. Run one end
of the 8’’ flexible duct
through the hole and fix it to
the duct connector (1),
using a 30’’ tie wrap and
duct tape. Fix the duct
connector to the wall (or
ceiling) using its 4 plastic
1
anchors and 4 #8 x 3/4”
screws. Then, snap on the
register (2).
2
VD0078
- 20 -
Download from Www.Somanuals.com. All Manuals Search And Download.
4. INSTALL THE UNIT (CONT’D)
4.5 INSTALLING 8’’ DUCTS AND REGISTERS (CONT’D)
How to connect the 8’’ flexible duct to the registers and unit ports (cont’d)
• Using the colored sticker dot included, identify which duct it is (red dot for
stale airflow and blue dot for filtered airflow). Repeat the procedure for the
other register.
• Each port is identified on top of the unit (see illustrations below). Attach the
fresh air to building duct (the one with the blue dot) to its corresponding port,
using tie wrap (1). Then, attach the exhaust air from building duct (the one
with the red dot) to the other 8’’ port (2).
1
2
NOTE: Use a 8’’ insulated duct (not included) if the duct will have to go through a
non-tempered room (eg: in northern area, not heated attic in winter or attic
not cooled in southern area). Also, if you plan to stop the unit for more than
12 hours, we recommend to cover the duct with R12 insulation.
4.5.2 CENTRAL DRAW POINT (AS ILLUSTRATED IN SECTIONS 2.1.2 AND 2.3.2)
Stale air ductwork
Same as for Stand Alone System, described in point 4.5.1.
Fresh/Filtered air ductwork (Return side connection)
!
WARNING
0
When performing duct connections, always use approved tools and
materials. Respect all corresponding laws and/or safety regulations. Please
refer to your local building code.
• Trace a 10 1/4’’x 6 7/8’’(260 mm x175mm)
minimum
9’10” (3 m)
opening on the forced air unit return duct
at a minimum linear distance of 9’10” (3 m)
upstream (from forced air unit drop:
A+B+C).
A
upstream
B
C
NOTE: For Hepa 1000 and HF 1.0 units
only, the minimum linear
distance is 2’ (0.61 m) upstream
(A+B+C).
VD0114
• Using a metal shear or a hammer and a flat
blade screwdriver, punch a hole into the
furnace/air handler return duct. Then, using
metal shear, cut out the rectangular hole.
- 21 -
Download from Www.Somanuals.com. All Manuals Search And Download.
4. INSTALL THE UNIT (CONT’D)
4.5 INSTALLING 8’’ DUCTS AND REGISTERS (CONT’D)
4.5.2 CENTRAL DRAW POINT (AS ILLUSTRATED IN SECTIONS 2.1.2 AND 2.3.2) (CONT’D)
Filtered air ductwork (Return side connection) (cont’d)
• Fix the duct connector to the forced air unit
duct using its 4 retaining screws (#8 x 3/4” long).
Seal with duct tape.
• Take one end of the 8’’ flexible duct and slide
it over the duct connector. Secure with a tie
wrap. Carefully seal the connection with duct
tape. Identifiy the duct using the blue sticker
dot included.
• Attach this duct to the FRESH AIR TO BUILDING
port (see icon on the top of the unit), using tie
wrap and duct tape.
4.5.3 RETURN-TO-RETURN (AS ILLUSTRATED IN SECTIONS 2.1.3 AND 2.3.3)
!
WARNING
0
When performing duct connections, always use approved tools and
materials. Respect all corresponding laws and/or safety regulations. Please
refer to your local building code.
Fresh/Filtered air ductwork (Return side connection)
Same as for Central Draw Point, described in point 4.5.2.
Stale air ductwork (Return side connection)
• Locate the stale air ductwork opening at
least 3’ (0.9 m) from the fresh/filtered air
ductwork connection. Proceed as for the
fresh/filtered air ductwork, but instead of
using the blue dot sticker to identify the
duct, use the red dot.
3’ (0.9 m)
minimum
• Attach this duct to the EXHAUST AIR FROM
BUILDING port (see icon on the top of the
unit), using tie wrap and duct tape.
- 22 -
Download from Www.Somanuals.com. All Manuals Search And Download.
4. INSTALL THE UNIT (CONT’D)
4.6 INSTALLING INSULATED FLEXIBLE DUCTS
(HEPA 2000, HF2.0, HEPA 3000, HF 3.0 AND HEPA 4000 UNITS ONLY)
CAUTION
Make sure the vapor barrier on the insulated ducts does not tear during
installation.
Use the following procedure for connecting the insulated flexible ducts to the Tandem®
transition* (EXHAUST AIR TO OUTSIDE and FRESH AIR FROM OUTSIDE).
NOTE: If the joist are perpendicular to the ducts, or if the connection to the exterior
hood is in a limited area, your installation will need two exterior hoods
instead of one. In this case, do not use the Tandem® transition. Identify
each insulated duct. For fresh air from outside duct, use the blue sticker
dots (one dot at each end). For exhaust air to outside duct, use the red
sticker dots (one dot at each end). Then, go to point 4.6.2 and refer to
the optional single hood enclosed instructions.
*Patent pending.
4.6.1 CONNECTION TO TANDEM® TRANSITION
1. For each duct, pull back the insulation to expose the interior flexible duct.
2. Connect the interior flexible duct to the smaller part of the Tandem® transition
(5’’ oval) using a 24’’ tie wrap.
NOTE: If you are using a 6’’ diameter insulated duct, use the bigger part of the
Tandem® transition (6’’ oval).
3. Pull the insulation over the joint. Pull the vapor barrier over the insulation.
4. Apply duct tape gently to the joint in order to make an airtight seal. See figures
below.
EXHAUST AIR TO OUTSIDE
DUCT ON TOP
1
2
VJ0022
VJ0025
3
4
VJ0023
VJ0024
Identify each insulated duct. For fresh air from outside duct, use the blue sticker
dots (one dot at each end). For exhaust air to outside duct, use the red sticker dots
(one dot at each end). Be careful to identify the exhaust air to outside duct
(red dot) at the upper section of the transition.
- 23 -
Download from Www.Somanuals.com. All Manuals Search And Download.
4. INSTALL THE UNIT (CONT’D)
4.6 INSTALLING INSULATED FLEXIBLE DUCTS
(HEPA 2000, HF 2.0, HEPA 3000, HF 3.0 AND HEPA 4000 UNITS ONLY) (CONT’D)
4.6.2 CONNECTION TO THE 5’’ TO 6’’ OVAL PORTS OF THE UNIT
Use the following procedure for connecting the insulated flexible ducts to the 5’’ to 6’’
oval ports of the unit (EXHAUST AIRTO OUTSIDE and FRESH AIR FROM OUTSIDE).
1. Pull back the insulation to expose the flexible
duct.
VJ0016
2. Connect the interior flexible duct to the smaller
part of the port (5’’ oval) using a 24’’ tie wrap.
NOTE: If you are using a 6’’ diameter insulated duct,
use the bigger part of the port (6’’ oval).
VJ0017
3. Pull the insulation over the joint and tuck it
between the inner and outer rings of the port.
Pull the vapor barrier over the insulation and
over the outer ring of the port.
VJ0018
4. Apply duct tape gently to the joint in order to
make an airtight seal.
VJ0019
CAUTION
Avoid compressing the insulation when you pull the tape tightly around the
joint. Compressed insulation loses its insulation properties and causes
water dripping due to condensation on the exterior surface of the duct.
5. Repeat steps 1 to 4 for the other 5’’ to 6’’ port.
1
2
See figure beside to find the EXHAUST AIR
TO OUTSIDE (1) and FRESH AIR FROM
OUTSIDE (2) oval ports on the top of the unit.
Be careful to connect the right insulated
duct to its corresponding port.
- 24 -
Download from Www.Somanuals.com. All Manuals Search And Download.
4. INSTALL THE UNIT (CONT’D)
4.7 INSTALLING DUAL EXTERIOR HOOD*
(HEPA 2000, HF 2.0, HEPA 3000, HF 3.0 AND HEPA 4000 UNITS ONLY)
4.7.1 ASSEMBLING DUAL EXTERIOR HOOD
Exterior dual hood is coming in separate
parts. Using 2 #8 x 3/4” screws, assemble the
top metal screen and the plastic grille to the
dual exterior hood. Then, slide the bottom
metal screen to the dual exterior hood. See
illustration beside.
VO0024
*Patent pending
4.7.2 LOCATING THE DUAL EXTERIOR HOOD
The dual exterior hood must be installed at a minimum
distance of 18 inches (457 mm) from the ground.
See illustration beside.
18''
(457 mm)
VD0083
!
WARNING
0
Make sure this hood is at least 3 feet (0.9 m) away from any of the following:
• High efficiency furnace vent.
• Gas meter exhaust, gas barbecue-grill.
• Any exhaust from a combustion source.
• Garbage bin and any other source of contamination.
4.7.3 CONNECTING TANDEM® TRANSITION TO THE DUAL EXTERIOR HOOD
1
1. Using a jig saw, cut a 6’’ diameter
hole in the exterior wall and
insert the Tandem® transition
through this hole.
VD0084
1) EXHAUST AIR TO OUTSIDE duct
CAUTION
The Tandem® transition must be inserted in such a way that the EXHAUST
AIR TO OUTSIDE duct will be located on the top.
- 25 -
Download from Www.Somanuals.com. All Manuals Search And Download.
4. INSTALL THE UNIT (CONT’D)
4.7 INSTALLING DUAL EXTERIOR HOOD
(HEPA 2000, HF 2.0, HEPA 3000, HF 3.0 AND HEPA 4000 UNITS ONLY) (CONT’D)
4.7.3 CONNECTING TANDEM® TRANSITION TO EXTERIOR DUAL HOOD (CONT’D)
2. Joint the end of the Tandem®
transition to the rear of the
exterior backplate. Secure
with 2 Xmas tree pins and seal
properly with duct tape.
Xmas tree pin
VD0085
CAUTION
The exterior backplate must be installed with the word ‘’TOP’’ pointing
upward.
3. Lean the exterior backplate to the
exterior wall.Using 4 #8 x 1 1/2”screws,
fix it to the wall. Seal the outline
with caulking.
VD0086
4. Snap the assembled exterior hood
on its backplate and secure with
2 provided screws (#8 x 3/4” long).
VD0087
screw
- 26 -
Download from Www.Somanuals.com. All Manuals Search And Download.
4. INSTALL THE UNIT (CONT’D)
4.8 CONNECTING THE DRAIN (HEPA 3000 AND HF 3.0 UNITS ONLY)
1
2
3
1
1
2
VO0046
VO0025
1.Remove the door by turning the
switch knob to the OFF position (to
unlock the door).Then, unlatch the
door and open it. Slide out the core
assembly to access the 2 drain
fitting hole locations (1). Punch out
the holes.
2.Hand tighten the 2 plastic drain
fittings (1) using the gaskets (2)
and nuts (3) as shown. Close the
door.
27''
686 mm
7''
(178 mm)
VO0027
4
3
VO0028
3.Cut 2 sections of plastic tubing; one
7’’ (178 mm) long and one 27’’ (686 mm)
long, and attach them to each drain
fitting as shown.
4.Join these 2 sections to the ‘’T’’
junction and main tube as shown.
5.Make a water trap loop in the tube to
prevent the unit from drawing
unpleaseant odors from the drain
source. Make sure this loop is situated
BELOW the ‘’T’’ as shown. This will
prevent water from being drawn back
up into the unit in case of negative
pressure. Run the tube to the floor
drain or an alternative drain pipe or
pail. Be sure there is a slight slope
for the run-off.
Tie-wrap
To drain
5
VO0029
- 27 -
Download from Www.Somanuals.com. All Manuals Search And Download.
5. CONTROLS
5.1 MAIN SWITCH
All units are equipped with a 3-position main switch, located on the front panel.
NORMAL/REMOTE:
UNIT IS OPERATING ON
NORMAL SPEED. THIS IS
THE RIGHT POSITION
WHEN AN OPTIONAL
OFF:
UNIT IS OFF AND
DOOR IS
WALL CONTROL IS USED.
UNLOCKED.
BOOST:
UNIT IS OPERATING
ON HIGH SPEED.
VC0053
5.2 OPTIONAL WALL CONTROLS
There are 2 optional wall controls available: C12 / CM control (intented for
HEPA 1000 / HF 1.0 and HEPA 2000 / HF 2.0 units only) and C34 / CMR control
(intented HEPA 3000 / HF 3.0 and HEPA 4000 units only).
VC0054
VC0055
C12 CONTROL
CM CONTROL
C34 CONTROL
CMR CONTROL
5.3 DIMENSIONS
Dimensions are the same for both C12 / CM
and C34 / CMR models.
VC0049
- 28 -
Download from Www.Somanuals.com. All Manuals Search And Download.
5. CONTROLS (CONT’D)
5.4 INSTALLATION OF THE OPTIONAL WALL CONTROLS
(CONTROLS C12 / CM AND C34 / CMR)
!
WARNING
0
Always disconnect the unit before making any connections. Failure in
disconnecting power could result in electrical shock or damage of the wall
control or electronic module inside the unit.
CAUTION
Never install more than one optional wall control per unit.
1.Determine the more convenient location for the control.
2
2.Remove the cover plate control (1). If you prefer to
have your optional main control mounted on an
approved outlet box or an approved mounting bracket
(not included), discard the backplate (2).
1
!
WARNING
0
To avoid risk of electrical shocks, never install another wire in the same
electrical box than the one for the optional wall control.
3. Take one end of the cable and pass it through the wall control backplate (or outlet
box or mounting bracket).
4. Splice back this end of the cable to access to the 4 wires. Remove the insulated
sleeve of each wire ends. Make a loop with each bare end wire to hook them
to their corresponding screw. Connect YELLOW wire to ‘’Y’’screw, RED wire to
‘’R’’screw, GREEN to ‘’G’’screw and BLACK to ‘’B’’screw. See illustration below.
BLACK
wire
YELLOW
wire
RED
GREEN
wire
wire
!
WARNING
Make sure that the wires don’t short circuit between themselves or by
touching any other components on the wall control.
- 29 -
Download from Www.Somanuals.com. All Manuals Search And Download.
5. CONTROLS (CONT’D)
5.4 INSTALLATION OF THE OPTIONAL WALL CONTROLS
(CONTROLS C12 / CM AND C34 / CMR) (CONT’D)
5. Pass the other end of the cable through the wall. Reinstall the cover plate.Using
wall anchors (not included) and provided screws, mount the wall control on the
wall. See illustrations below.
2
3
2
3
1
4
1
5
4
VC0051
VC0052
1) Wall anchors
2) Control cable
3) Control backplate
4) Control
5) Screws
1) Outlet box
2) Control cable
3) Control
4) Screws
6. Route the cable to the unit.
CAUTION
Keep control low voltage wiring at least 1 foot (305 mm) away from motors,
lightning ballast, light dimming circuit and power distribution panel. Do not
route control wiring along with house power wiring. Avoid poor wiring
connections. Failure to follow these practices can introduce electrical
interference, which can cause erratic control operations.
7. Remove the front 8’’ oval port (A) and the front panel (B) of the unit by unscrewing
their retaining screws.
A
B
VO0019
VO0018
- 30 -
Download from Www.Somanuals.com. All Manuals Search And Download.
5. CONTROLS (CONT’D)
5.4 INSTALLATION OF THE OPTIONAL WALL CONTROLS
(CONTROLS C12 / CM AND C34 / CMR) (CONT’D)
8. Using a small rod, pierce a hole through
the unit at the end of the wire channel.
(See picture beside.) Splice back the
end of the cable to access the 4 wires.
Remove the insulated sleeve of each
wire ends. Insert the end of the cable
through the unit, using the small hole
previously done.
VD0088
9. In order to access the unit PCB terminals,
remove the side door located on the
electrical box and punch out its knock
out. Run the cable through the knock-out
hole and connect each wire in their
corresponding terminal (YELLOW in
‘’Y’’, RED in ‘’R’’, GREEN in ‘’G’’and
BLACK in ‘’B’’).
1
NOTE: Push forward slightly on the
little tabs (1) to ease insertion
of each wires.
See picture beside.
VE0049
10. Reinstall the side door on the electrical box and the 8’’ oval port on the unit.
11. Route the wire through its
channel and reinstall the
front panel on the unit. See
picture beside.
VD0089
12. If the installation is not completed, return to Section 4 on page 19. If the
installation is completed, plug the unit.
NOTE: When using an optional wall control, the main switch on the unit must
always be positioned to NORMAL/REMOTE.
- 31 -
Download from Www.Somanuals.com. All Manuals Search And Download.
5. CONTROLS (CONT’D)
5.5 OPERATING C12 / CM CONTROL
5.5.1 C12 / CM CONTROL DESCRIPTION
POWER INDICATOR:
LIGHTS UP WHEN SLIDE SWITCH
IS ON NORMAL OR BOOST
POSITION.
BOOST:
UNIT IS OPERATING ON
HIGH SPEED.
NORMAL:
UNIT IS OPERATING ON
NORMAL SPEED.
FILTER MAINTENANCE
INDICATOR:
FLASHES EVERY MINUTE TO
INDICATE IT IS ON DUTY.
FLASHES EVERY SECOND WHEN
ITS TIME TO REPLACE
OFF:
UNIT IS OFF.
PREFILTER. SEE BIANNUAL
MAINTENANCE IN SECTION 6.
LIGHTS UP WHEN ITS TIME TO
REPLACE FILTER AND
VC0054
RESET FILTER HOLE:
ONCE THE MAINTENANCE DONE, RESET THE FILTER
MAINTENANCE INDICATOR BY CAREFULLY INSERTING
A SMALL ROD (EG: PAPER CLIP) IN THE RESET FILTER
HOLE, DURING 1 SECOND. THE FILTER MAINTENANCE
INDICATOR WILL TURN OFF.
PREFILTER. SEE ANNUAL
MAINTENANCE IN SECTION 6.
5.5.2 USING C12 / CM CONTROL
• OFF: To stop the unit, slide the button on this position.
• NORMAL: For a day-to-day usage, slide the button on this position. The
unit then will operate on normal speed.
• BOOST: For a high speed operation, slide the button on this position.
Generally used when extreme conditions occur, eg.: parties,
smokers, etc.
- 32 -
Download from Www.Somanuals.com. All Manuals Search And Download.
5. CONTROLS (CONT’D)
5.6 OPERATING C34 / CMR CONTROL
5.6.1 C34 / CMR CONTROL DESCRIPTION
RECIRCULATION INDICATOR:
LIGHTS UP WHEN SLIDE
SWITCH IS ON
FRESH AIR INDICATOR:
LIGHTS UP WHEN SLIDE
SWITCH IS ON NORMAL
OR BOOST POSITION.
RECIRCULATION. UNIT IS
OPERATING ON NORMAL
SPEED.
FILTER MAINTENANCE
INDICATOR:
FLASHES WHEN IT IS TIME
TO REPLACE PREFILTER
AND WASH CORE FILTERS.
SEE BIANNUAL
BOOST INDICATOR:
LIGHTS UP WHEN SLIDE
SWITCH IS ON BOOST
POSITION. UNIT IS OPERATING
ON HIGH SPEED.
MAINTENANCE IN
SECTION 6.
NORMAL INDICATOR:
LIGHTS UP WHEN SLIDE
SWITCH IS ON NORMAL
POSITION. UNIT IS OPERATING
ON NORMAL SPEED.
VC0048
LIGHTS UP WHEN IT IS
TIME TO REPLACE FILTER
AND PREFILTER AND
CLEAN CORE AND CORE
FILTERS. SEE ANNUAL
RESET FILTER HOLE:
MAINTENANCE IN
SECTION 6.
ONCE THE MAINTENANCE DONE, RESET THE FILTER
MAINTENANCE INDICATOR BY CAREFULLY INSERTING
A SMALL ROD (EG: PAPER CLIP) IN THE RESET FILTER
HOLE, DURING 1 SECOND. THE FILTER MAINTENANCE
INDICATOR WILL TURN OFF.
5.6.2 USING C34 / CMR CONTROL
• OFF: To stop the unit, slide the button on this position.
• NORMAL: For a day-to-day usage, slide the button on this position. The
unit then will operate on normal speed.
• BOOST: For a high speed operation, slide the button on this position.
Generally used when extreme conditions occur, eg.: parties,
smokers, etc.
• RECIRCULATION: For a normal speed operation, without exchanging air with
the outside, slide the button on this position. This mode is
recommended in high humidity days (rain, heat wave).
Also, use it when the outside temperature is extremely cold
and/or the inside air is too dry. It can be used also to recirculate
the heat coming from a wood stove throughout the house,
or the fresh air from a cooling system.
- 33 -
Download from Www.Somanuals.com. All Manuals Search And Download.
6. MAINTENANCE
!
WARNING
Risk of electrical shocks. B0efore performing any maintenance or servicing,
always disconnect the unit from its power source.
6.1 BIANNUAL MAINTENANCE (ESSENTIAL)
If your unit is equipped with an optionnal wall control (C12 / CM or C34 / CMR)
you should perform this maintenance when the Filter Maintenance light is flashing.
Otherwise, this maintenance must be performed every 6 months to ensure your
unit proper operation for years to come. Follow these steps:
1.
2.
Turn switch knob to OFF to unlock the door.
Unlatch the door and open it. Clean the inner side of the door with a clean
damp cloth, them wipe with a dry one.
3.
Slide out the air diffuser (HEPA 2000 and HF 2.0 units only), the recovery
core (HEPA 3000 and HF 3.0 units only), the energy recovery core (HEPA 4000
units only) and the filter cartridge from the unit.
NOTES: 1. On HEPA 2000 and HF 2.0 only, never grab the white shaft (item 2)
to pull out the air diffuser.
2. To remove the filter cartridge, pull on its tabs (item 5).
2
3
1
VD0091
VD0107
1) Air diffuser
2) White Shaft
3) Heat Recovery Core
4
5
VD0112
VD0155
4) Energy recovery Core
5) Filter Cartridge Tabs
- 34 -
Download from Www.Somanuals.com. All Manuals Search And Download.
6. MAINTENANCE (CONT’D)
6.1 BIANNUAL MAINTENANCE (ESSENTIAL) (CONT’D)
4.
Using your thumbs, push on the prefilter* side to disengage it from the filter
cartridge. Then, slide it out of the filter cartridge and discard it. Install the
new prefilter* by reversing this operation.
1
2
VD0092
VD0093
1) Filter cartridge
2) Prefilter
NOTE: If you are using a washable foam filter (MERV 8), vacuum to remove most
of the dust. Let it soak in a solution of warm water and mild soap. Rinse
thoroughly and let dry before reinstalling it.
* When using a washable foam filter (MERV 8), there is no prefilter.
5.
Clean the inside walls of the unit with a clean damp cloth, them wipe with a
dry one.
For HEPA 2000 and HF 2.0 only
Clean the air diffuser with a clean damp cloth, them wipe with a dry one. Once the
air diffuser completely dry, slide it back into the unit.
For HEPA 3000, HF 3.0 and HEPA 4000 only
1
2
1
Wash the 2 core filters under hot water with mild
soap. Rinse thoroughly and let dry completely
before reinstalling on the core. Remove the dust
on the core using a vacuum cleaner with a soft
brush attachment.
VD0091
1) Core filters
2) Core
NOTE: Make sure the damper spring (1) is still
inside the left front port opening before
reinstalling the recovery module.
1
VD0120
1) Damper spring
- 35 -
Download from Www.Somanuals.com. All Manuals Search And Download.
6. MAINTENANCE (CONT’D)
6.1 BIANNUAL MAINTENANCE (ESSENTIAL) (CONT’D)
6.
Close the door, close the latches and turn ON the switch knob to its
previous position.
7.
If your unit is equipped with an optionnal wall control (C12 / CM) or C34 / CMR),
reset the filter maintenance indicator by inserting a small rod (eg: paper clip
end) into the reset filter hole of the optional wall control. Press lightly until
the Filter Maintenance indicator light turns off.
6.2 ANNUAL MAINTENANCE (ESSENTIAL)
If your unit is equipped with an optionnal wall control (C12 / CM or C34 / CMR)
you should perform this maintenance when the Filter Maintenance light stays
ON. Otherwise, this maintenance must be performed once a year to ensure your
unit proper operation for years to come. Proceed as the Biannual Maintenance
(Section 6.1), but instead of replacing the prefilter (point 4), discard the complete
HEPA Filter cartridge (including prefilter). Install a new HEPA filter cartridge (or a
new pleated filter cartridge) with a new prefilter on it.
NOTE: If you are using a washable foam filter, just do the same operations as the
Biannual Maintenance (Section 6.1).
6.3 MASTER RESET (C12 / CM AND C34 / CMR CONTROLS)
Use the master reset only if you replace the filters before the annual maintenance
indicator is on. By inserting a small rod (eg: paper clip end) during 5 seconds and
more into the reset filter hole of the optional wall control, a master reset will be
done and both biannual and annual maintenance filter are reset.
C12 / CM Control: The filter maintenance indicator will flash 1/4 second.
C34 / CMR Control: If the wall control is in ”Off” position, “Fresh air” light indicator
will flash for 1 second.
If the wall control is in ”Normal” or “Boost” position, the unit
motor, the “Fresh air” light indicator and speed light indicator
(“Normal” or “Boost”) will turn off for 3 seconds.
If the wall control is in ”Recirculation” position, the “Recirculation”
light indicator and the unit motor will turn off during 3 seconds.
- 36 -
Download from Www.Somanuals.com. All Manuals Search And Download.
7. PARTS ORDERING CHART
Part
Number
05123
04803
04804
04852
05120
13940
04862
HEPA 1000 HEPA 2000
No. Description
HF 1.0
HF 2.0
1
2
3
4
5
6
7
Prefilter Kit (2)
1
1
1
1
-
1
1
1
1
-
HEPA Pleated Filter Kit
MERV 12 Filter Kit*
Foam Filter MERV 8 Kit*
Core Filter Kit (2)
Single Exterior Hood Kit**
Wall Control C12**
-
1
1
1
Part
Number
05123
04803
04804
04852
05120
05689
13940
04391
HEPA 3000
HF 3.0
No. Description
HEPA 4000
1
2
3
4
Prefilter Kit (2)
1
1
1
1
1
-
1
1
1
1
-
1
1
1
HEPA Pleated Filter Kit
MERV 12 Filter Kit*
Foam Filter MERV 8 Kit*
5A Core Filter Kit (2)
5B Core Filter Kit (2)
6
7
Single Exterior Hood Kit**
Wall Control C34**
1
1
*The HEPA filter is factory installed in all our units. However, when it will be time to be
replaced, a pleated filter or a foam filter can be purchased, but the filtration
efficiency will not be the same as a HEPA filter.
**Items 6 and 7 are optionals.
All listed parts are available where you have bought your unit.
NOTE: Please note that parts not listed are not available; those parts require
assembly knowledge that only manufacturer can garantee.
- 37 -
Download from Www.Somanuals.com. All Manuals Search And Download.
8. TROUBLESHOOTING
PROBLEMS
SOLUTIONS
• Check breaker or fuse in main
distribution panel.
• Check there is 120V at the
electrical outlet.
• Make sure the unit main switch is
properly set in Normal or Boost
position.
1.Unit does not start at Normal
or Boost position.
• If a wall control (C12 / CM or
C34 / CMR) is connected,
disconnect control wire from the
unit, then make sure the unit
main switch is properly set in
Normal or Boost position.
• If a wall control (C12 / CM or
C34 / CMR) is used, disconnect
control wire from the unit. Then, if
the unit runs at Normal speed,
chech control wiring and wall
control connections.
2. Unit does not run at Normal
speed, but runs at Boost.
• Check if the unit main switch is in
“Normal/Remote” position.
• Check wall control wiring.
• Check wall control wiring.
3. Unit is not operating as per
the selected mode.
4. Wall control indicators do not work
properly or not at all.
5. On C34 / CMR wall control only, 1 or
2 light indicators are flashing
every second.
• Check if the unit main switch is in
“Normal/Remote” position.
• Check wall control wiring.
If the problem is still not solved, call your installer or the nearest approved Service
Center.
Also, you can reach the Customer Service Department at the following telephone
numbers:
Exclusively for models HEPA 1000, HEPA 2000, HEPA 3000 and HEPA 4000:
1 800 567-3855.
Exclusively for models HF 1.0, HF 2.0 and HF 3.0:
1 866 737-7770.
- 38 -
Download from Www.Somanuals.com. All Manuals Search And Download.
|