Bradford White Corp Water Heater BWCH User Manual

Installation and Operation Instructions  
Document 1270  
Installation and Operation  
Instructions for  
Copper Brute II  
Hydronic Boiler  
Model BWCH  
Water Heater  
Model BWCV  
Sizes 500-2000  
U.S. Reg. 2,765,423  
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician,  
qualified in hot water boiler installation and maintenance. Improper installation and/or operation could  
create carbon monoxide gas in flue gases which could cause serious injury, property damage, or  
death. Improper installation and/or operation will void the warranty. For indoor installations, as an  
additional measure of safety, Bradford White strongly recommends installation of suitable Carbon  
Monoxide detectors in the vicinity of this appliance and in any adjacent occupied spaces.  
AVERTISSEMENT  
Assurez-vous de bien suivres les instructions  
données dans cette notice pour réduire au  
minimum le risque d’incendie ou d’explosion ou  
pour éviter tout dommage matériel, toute blessure  
ou la mort.  
WARNING  
If the information in this manual is not  
followed exactly, a fire or explosion may  
result causing property damage, personal  
injury or loss of life.  
Do not store or use gasoline or other  
flammable vapors and liquids in the vicinity of  
this or any other appliance.  
WHAT TO DO IF YOU SMELL GAS  
• Do not try to light any appliance.  
• Do not touch any electrical switch; do not  
use any phone in your building.  
• Immediately call your gas supplier from  
a nearby phone. Follow the gas supplier's  
instructions.  
• If you cannot reach your gas supplier, call  
the fire department.  
Installation and service must be performed  
by a qualified installer, service agency, or gas  
supplier.  
Ne pas entreposer ni utiliser d’essence ni d’autres  
vapeurs ou liquides inflammables dans le voisinage  
de cet appareil ou de tout autre appareil.  
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:  
• Ne pas tenter d’allumer d’appareils.  
• Ne touchez à aucun interrupteur. Ne pas vous  
servir des téléphones dansle bâtiment où vous  
trouvez.  
• Appelez immédiatement votre fournisseur de  
gaz depuis un voisin. Suivez les instructions  
du fournisseur.  
• Si vous ne pouvez rejoindre le fournisseur de  
gaz, appelez le sservice des incendies.  
L’installation et l’entretien doivent être assurés par  
un installateur ou un service d’entretien qualifié ou  
par le fournisseur de gaz.  
238-50605-00A REV 12/13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COPPER BRUTE II (500 - 2000)  
Page 3  
SECTION 6.  
Operating Instructions  
SECTION 7.  
Maintenance  
6.1  
6.2  
6.3  
Sequence of Operation.................................. 36  
Filling the Boiler System ................................ 36  
Programming the Temperature Control ......... 37  
7.1  
System Maintenance..................................... 48  
7.2  
Appliance Maintenance and  
Component Description................................. 48  
7.2.1 Burners .......................................................... 48  
7.2.2 Filter............................................................... 48  
7.2.3 Gas Valves..................................................... 48  
7.2.4 Manual Reset High Limit Control................... 48  
7.2.5 Automatic Reset High Limit Control............... 48  
7.2.6 Temperature Control...................................... 49  
7.2.7 Ignition Controls............................................. 49  
7.2.8 Ignitors........................................................... 49  
7.2.9 Ignition Sensors............................................. 49  
7.2.10 Transformer ................................................... 49  
7.2.11 Blowers.......................................................... 49  
7.2.12 Flow Switch ................................................... 49  
7.2.13 Heat Exchanger Coil...................................... 49  
6.3.1 System Piping................................................ 37  
6.3.2 Choosing the Mode........................................ 37  
6.3.3 Programming ................................................. 38  
6.3.4 Choosing the Mode for your Application........ 40  
6.4  
Advanced Topics............................................ 42  
6.4.1 Differential...................................................... 42  
6.4.2 Staging Mode................................................. 42  
6.4.3 Boiler Minimum (BOIL MIN)........................... 43  
6.4.4 Boiler Maximum (BOIL MAX)......................... 43  
6.4.5 Boiler Target Temperature ............................. 43  
6.4.6 Pump Operation............................................. 43  
6.4.7 Setpoint Operation ........................................ 44  
6.4.8 Dedicated Domestic Hot Water ..................... 44  
6.4.9 Outdoor Reset Operation............................... 44  
6.4.10 External Boiler Operation .............................. 46  
6.4.11 Limit Controls................................................. 46  
6.4.12 Advanced Programming Mode...................... 46  
SECTION 8.  
Trouble Shooting  
8.1  
8.2  
8.3  
8.4  
8.5  
8.6  
8.7  
Resolving Lockouts........................................ 51  
Delayed Ignition – Possible Causes.............. 51  
Short Cycling – Boiler.................................... 51  
Short Cycling – Water Heater........................ 51  
High Gas Consumption.................................. 51  
Troubleshooting the Temperature Control ..... 51  
Troubleshooting Copper Brute II Controls ..... 51  
6.5  
Operating the Burner and Set Up.................. 46  
6.5.1 Set Up for 0 to 2500 Feet Altitude.................. 46  
6.5.2 High Altitude Adjustment and Set Up............. 47  
6.6  
6.5  
Shutting Down the Copper Brute II................ 47  
To Restart the Copper Brute II....................... 47  
SECTION 9.  
Replacement Parts  
9.1  
General Information....................................... 54  
9.2  
Parts List........................................................ 54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 4  
1.1 Introduction  
SECTION 1.  
This manual provides information necessary  
for the installation, operation, and maintenance of  
Bradford White Corp, Copper Brute II copper tube  
appliances. Read it carefully before installation.  
All application and installation procedures  
should be reviewed completely before proceeding  
with the installation. Consult the Bradford White  
factory, or local factory representative, with any issues  
or questions regarding this equipment. Experience  
has shown that most operating issues are caused by  
improper installation.  
General Information  
USING THIS MANUAL – Because the  
Copper Brute II Boilers and Copper Brute II Water  
Heaters are identical appliances, with the exception  
of materials of manufacture, labels and ultimate  
use application, this manual provides information  
for the proper installation, operation and  
maintenance of both products. Where differences  
exist between the application of the appliances and  
their operation, the sections pertinent to only one  
appliance or the other will be so identified.  
In the Commonwealth of Massachusetts, this  
appliance must be installed by a licensed plumber or  
gas fitter.  
The Copper Brute II appliance is protected  
against over pressurization. A pressure relief valve  
is fitted to all appliances. It is installed on the outlet  
header, at the water outlet of the appliance.  
IMPORTANT: The inlet gas pressure to the appliance  
must not exceed 13" w.c. (3.2kPa).  
WARNING  
The Copper Brute II hydronic, boiler or water  
heater must be installed in accordance with the  
procedures detailed in this manual, or the Bradford  
White warranty may be voided. The installation must  
conform to the requirements of the local jurisdiction  
having authority, and, in the United States, to the  
latest edition of the National Fuel Gas Code, ANSI  
Z223.1/NFPA54. In Canada, the installation must  
conform to the latest edition of the Natural Gas  
and Propane Installation Code, CSA B149.1 and/  
or local codes. Where required by the authority  
having jurisdiction, the installation of Copper Brute  
II appliances must conform to the Standard for  
Controls and Safety Devices for Automatically Fired  
Boilers, ANSI/ASME CSD-1. Any modifications to  
the boiler, its gas controls, or wiring may void the  
warranty. If field conditions require modifications,  
consult the factory representative before initiating  
such modifications.  
All installations must be made in accordance with:  
1) In the U.S., the " National Fuel Gas  
Code"ANSI Z223.1/NFPA54, Latest Edition and all  
applicable local codes as required by the Authorities  
Having Jurisdiction (AHJ), or  
2) In Canada, the "Natural Gas and Propane  
Installation Code", CSA B149.1, latest edition and all  
applicable local codes as required by the AHJ.  
All electrical wiring is to be done in accordance with:  
1). In the U.S., the "National Electrical Code"  
(NEC), ANSI/NFPA 70, latest Edition and all  
applicable local codes as required by the AHJ, or  
2). In Canada, the “Canadian Electrical Code  
- Part 1”, CSA STD. C22.1 and all applicable local  
codes as required by the AHJ.  
This appliance must be electrically grounded in  
accordance with the applicable codes and standards  
referenced above.  
1.2 Model Identification  
Consult the rating plate on the unit. The  
following information describes the model number  
structure.  
1
2
3
4
5
6
7
8
9
10  
A
11  
C
12  
13  
2
14  
15  
16  
B
W
C
SERIES  
SIZE  
LOCATION  
REVISION  
USAGE  
FUEL  
ALTITUDE  
FIRING  
MODE  
HEAT  
EXCHANGER  
OPTIONS  
CODE  
PUMP  
OPTIONS  
B
W
C
H
V
0
5
0
0
0
0
0
0
0
0
N
A
C
2
K (500/750)  
N (1000)  
B
C
K
N
P
S
X
J
L
X
H
N
S
0
1
1
1
1
2
7
0
2
5
7
0
5
0
5
0
5
0
P
L (1250-2000)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COPPER BRUTE II (500 - 2000)  
Page 5  
Model Character Designation  
Some accessory items are shipped in separate  
packages. Verify receipt of all packages listed on  
the packing slip. Inspect everything for damage  
immediately upon delivery, and advise the carrier of  
any shortages or damage. Any such claims should be  
filed with the carrier. The carrier, not the shipper, is  
responsible for shortages and damage to the shipment  
whether visible or concealed.  
1-3 Model Series Designation  
B W C = Bradfrod White, Copper Brute II  
4
Usage  
H = Hydronic  
V = Volume Water  
5-8 Size  
0 5 0 0 = 500,000 BTU/h input  
0 7 5 0 = 750,000 BTU/h input  
1 0 0 0 = 999,000 BTU/h input  
1 2 5 0 = 1,250,000 BTU/h input  
1 5 0 0 = 1,500,000 BTU/h input  
1 7 5 0 = 1,750,000 BTU/h input  
2 0 0 0 = 1,999,000 BTU/h input  
Fuel  
1.4 Dimensions  
See Figure 1.  
1.5 Locating the Appliance  
The appliance should be located to provide  
clearances on all sides for maintenance and inspection.  
It should not be located in an area where leakage of  
any connections will result in damage to the area  
adjacent to the appliance or to lower floors of the  
structure.  
9
N = Natural Gas  
P = Propane  
10 Altitude  
A = 0-10,000 feet  
11 Location  
C = Indoor and Outdoor  
12 Firing Mode  
K = Two-stage (models 500 & 750)  
When such a location is not available, it is  
recommended that a suitable drain pan, adequately  
drained, be installed under the appliance.  
The appliance is design certified by CSA-  
N = Three-stage (model 1000)  
International for installation on combustible flooring;  
in basements; in closets, utility rooms or alcoves.  
Copper Brute II Boilers or Water Heaters must  
never be installed on carpeting. The location for the  
appliance should be chosen with regard to the vent  
pipe lengths and external plumbing. The unit shall be  
installed such that the gas ignition system components  
are protected from water (dripping, spraying, rain, etc.)  
during operation and service (circulator replacement,  
control replacement, etc.). When vented vertically, the  
Copper Brute II must be located as close as practical  
to a chimney or outside wall. If the vent terminal and/  
or combustion air terminal terminate through a wall,  
and there is potential for snow accumulation in the  
local area, both terminals should be installed at an  
appropriate level above grade.  
L = Four-stage (models 1250 - 2000)  
13 Revision  
2 = Second version  
14 Heat Exchanger  
B = Glass-lined CI / copper / brz trim (std. BWCV)  
C = Glass-lined cast iron / copper (standard BWCH)  
K = Bronze / copper  
N = Glass-lined cast iron / cu-nickel  
P = Glass-lined cast iron / cu-nickel / brz trim  
S = Bronze / cu-nickel  
15 Option Code  
X = Standard unit  
J = CSD-1, FM, IRI, IL  
L = MN and LDS (Indoor units only)  
16 Pump Options  
X = No Pump  
The dimensions and requirements that are shown  
in Table 1 should be met when choosing the locations  
for the appliance.  
H = Pump mounted, hard water pump  
N = Pump mounted, normal pump  
S = Pump mounted, soft water pump  
REQUIRED  
RECOMMENDED  
1.3 Warranty  
Bradford White, Copper Brute II appliances  
are covered by a limited warranty. The owner should  
fill out the warranty registration card and return it to  
Bradford White.  
All warranty claims must be made to an  
authorized Bradford White representative or directly  
to the factory. Claims must include the serial number  
and model (this information can be found on the rating  
plate), installation date, and name of the installer.  
Shipping costs are not included in the warranty  
coverage.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 6  
pump-mounted units.  
AIR  
CONN.  
W
VENT  
CONN.  
V
HORIZ.  
VENT  
PIPE  
A
B
C
D
E
F
G
H
SIZE  
500  
750  
in  
cm  
in  
cm  
in cm  
in cm  
in cm  
in cm  
in cm  
in cm  
33½ 85  
45½ 116  
15¾ 40  
21¾ 55  
15  
15  
15  
101/8 26  
101/8 26  
101/8 26  
101/8 26  
29¾ 76  
29¾ 76  
29¾ 76  
30¾ 78  
30¾ 78  
30¾ 78  
30¾ 78  
32¾ 83  
32¾ 83  
32¾ 83  
29½ 75  
29½ 75  
29½ 75  
29½ 75  
20  
20  
20  
22  
22  
22  
22  
22  
22  
46 117  
58 147  
70 178  
80 203  
91 231  
6
6
8
8
8
8
15  
8
20  
8
8
8
8
8
8
20  
15 10 25  
20 10 25  
20 12 30  
20 12 30  
20 14 36  
20  
20  
20  
20  
20  
1000 57½ 146 28¾ 73  
1250 68 172 34 86  
1500 78½ 199 39¾ 101  
1750 89 226 44½ 113  
2000 99½ 253 49¾ 126  
7
18  
22  
22  
22 101 256  
22  
0
B
284 12 30 14 36 12 3  
*Air and vent connections may be on top or back of the Copper Brute II, and are field convertible.  
Dimensions in inches cm.  
Figure 1. Dimensional Data.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COPPER BRUTE II (500 - 2000)  
Page 7  
1.6 Locating Pump-Mounted Water Heater  
1.8 Locating Appliance for Correct  
with Respect to Storage Tank(s)  
For best results, a pump-mounted Copper Brute  
II water heater should be located within 15 feet (4.6m)  
of the storage tank(s). The pump is sized for 30 feet  
(9.1m) of piping.  
If the appliance must be installed with longer  
piping runs, then larger diameter pipe or tubing shall  
be used. Consult the factory for assistance.  
Horizontal Vent/Ducted Air Distance  
From Outside Wall  
The forced draft combustion air blower/blowers  
in the appliance has/have sufficient power to pull air  
and vent properly when the following guidelines for  
horizontal air and vent are followed (see Table 2).  
NOTE: On all model sizes, the vent collar size is  
larger than the size of the vent pipe that can be used.  
Vent collar size and horizontal pipe diameters can  
be found in Table 2. The larger vent collar size is to  
accommodate Category I (vertical) vent systems.  
1.7 Locating Pump-Mounted Boiler with  
Respect to Return/Supply Header  
For the best results, a pump-mounted Copper  
Brute II Boiler should be located within 15 feet (4.6m)  
of the supply and return headers. The pump is sized for  
30 feet (9.1m) of piping.  
If the appliance must be installed with longer  
piping runs, then larger diameter tubing shall be used.  
Consult the factory for assistance.  
NOTE: When located on the same wall, the Copper  
Brute II combustion air intake terminal must be  
installed a minimum of 12" (30cm) below the exhaust  
vent terminal and separated by a minimum of  
36 inches (91cm) horizontally.  
The air intake terminal must be installed high  
enough to avoid blockage from snow, leaves and other  
debris.  
APPLIANCE  
SURFACE  
CLEARANCE FROM  
SERVICE ACCESS  
CLEARANCE  
COMBUSTIBLE MATERIAL  
inches  
cm  
inches  
24  
24  
12  
**12**  
36  
cm  
61  
61  
30  
30**  
91  
Left Side  
Right Side  
Top  
1
1
1
1
1
2.5  
2.5  
2.5  
2.5  
2.5  
Back  
Front  
Vertical  
(Category 1)  
Vent  
Horizontal  
(Category 3)  
Vent  
6*  
15.2*  
per UL1738 venting  
system supplier’s  
instructions  
*1" (2.5cm) when b-vent is used.  
**When vent and/or combustion air connects to the back,  
recommended clearance is 36" (91cm).  
Table 1. Clearances.  
HORIZONTAL  
VENT PIPE  
DIAMETER  
AIR COLLAR  
& PIPE  
DIAMETER  
VENT COLLAR  
SIZE  
MAX. PIPE  
LENGTH  
MAX. NO.  
OF ELBOWS  
SIDE WALL  
VENT  
TERMINAL  
SIDE WALL  
COMBUSTION  
AIR TERMINAL  
PART NUMBER  
20260701  
20260701  
20260703  
20260703  
20260703  
20260703  
SIZE  
in.  
8
cm  
20  
25  
25  
30  
30  
36  
36  
in.  
6
cm  
15  
20  
20  
20  
20  
20  
30  
in. cm  
ft.  
m
PART NUMBER  
CA001401  
CA001402  
CA001402  
CA001403  
CA001403  
CA001403  
500  
750  
1000  
1250  
1500  
1750  
2000  
6
6
15  
15  
20  
20  
20  
20  
30  
50 15  
50 15  
50 15  
50 15  
50 15  
50 15  
50 15  
3
3
3
3
3
3
3
10  
10  
12  
12  
14  
14  
8
8
8
8
8
8
8
8
8
12  
12  
CA001404  
20260706  
Table 2. Horizontal Vent / Combustion Air Parameters.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 8  
total input rating of all equipment in the enclosure.  
Table 3 shows data for this sizing method, for each  
Copper Brute II model.  
SECTION 2.  
Venting and Combustion Air  
2.1 Combustion Air  
Copper Brute II boilers and water heaters must  
have provisions for combustion and ventilation air  
in accordance with Section 5.3, Air for Combustion  
and Ventilation, of the National Fuel Gas Code, ANSI  
Z223.1, or Sections 7.2, 7.3 or 7.4 of CSA B149.1,  
Installation Codes, or applicable provisions of the local  
building codes.  
Method 2: One permanent opening, commencing  
within 12 inches (30 cm) of the top of the enclosure,  
shall be permitted. The opening shall directly  
communicate with the outdoors or shall communicate  
through a vertical or horizontal duct to the outdoors  
or spaces that directly communicate with the outdoors  
and shall have a minimum free area of 1 square inch  
per 3000 Btu/hr (7 square cm/kW) of the total input  
rating of all equipment located in the enclosure. This  
opening must not be less than the sum of the areas of  
all vent connectors in the confined space.  
Other methods of introducing combustion and  
ventilation air are acceptable, providing they conform  
to the requirements in the applicable codes listed  
above.  
A Copper Brute II appliance may receive  
combustion air from the space in which it is installed,  
or it can be ducted directly to the unit from the outside.  
Ventilation air must be provided in either case.  
2.1.1 Combustion Air From Room  
In the United States, the most common  
requirements specify that the space shall communicate  
with the outdoors in accordance with method 1 or 2,  
which follow. Where ducts are used, they shall be of  
the same cross-sectional area as the free area of the  
openings to which they connect.  
In Canada, consult local building and safety  
codes or, in absence of such requirements, follow CSA  
B149.1.  
Method 1: Two permanent openings, one  
2.1.2 Intake Combustion Air  
commencing within 12 inches (30 cm) of the top  
and one commencing within 12 inches (30 cm) of  
the bottom, of the enclosure shall be provided. The  
openings shall communicate directly, or by ducts,  
with the outdoors or spaces that freely communicate  
with the outdoors. When directly communicating  
with the outdoors, or when communicating to the  
outdoors through vertical ducts, each opening shall  
have a minimum free area of 1 square inch per 4000  
Btu/hr (5.5 square cm/kW) of total input rating of all  
equipment in the enclosure. When communicating to  
the outdoors through horizontal ducts, each opening  
shall have a minimum free area of not less than  
1 square inch per 2000 Btu/hr (11 square cm/kW) of  
The combustion air can be taken through the  
wall, or through the roof. When taken from the wall,  
it must be taken from out-of-doors by means of the  
Bradford White horizontal wall terminal (see Table 2).  
When taken from the roof, a field-supplied rain cap or  
an elbow arrangement must be used to prevent entry of  
rain water (see Figure 2).  
Use single-wall galvanized pipe, per Table 4, for  
the combustion air intake (see Table 2 for appropriate  
size). Route the intake to the heater as directly as  
possible. Seal all joints with tape. Provide adequate  
hangers. The unit must not support the weight of the  
combustion air intake pipe. Maximum linear pipe  
EACH OPENING*  
SIZE  
500  
SQUARE INCHES  
SQUARE CM  
807  
125  
188  
250  
313  
375  
438  
500  
750  
1213  
1000  
1250  
1500  
1750  
2000  
1613  
2020  
2420  
2826  
3226  
*Net Free Area in Square Inches / Square cm  
Area indicated is for one of two openings; one at floor level and  
one at the ceiling, so the total net free area could be double the  
figures indicated.  
This chart is for use when communicating directly with the  
outdoors. For special conditions and alternate methods, refer to  
the latest edition of ANSI Z223.1.  
Note: Check with louver manufacturers for net free area of  
louvers. Correct for screen resistance to the net free area  
if a screen is installed. Check all local codes applicable to  
combustion air.  
Table 3. Combustion Air Openings.  
Figure 2. Combustion Air and Vent Through Roof.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COPPER BRUTE II (500 - 2000)  
Page 9  
length allowed is 50 feet (15.2m). Three elbows have  
been calculated into the 50-foot (15.2m) linear run.  
Subtract 10 allowable linear feet (3.0m) for every  
additional elbow used (see Table 2). When fewer than  
3 elbows are used, the maximum linear pipe length  
allowed is still 50 feet (15.2m).  
The connection for the intake air pipe is on the  
filter box. The Copper Brute II appliances may have  
venting and combustion air ducting attached to the top  
or the back. They are shipped with the connections  
at the top. For attaching either or both pipes to the  
back, the mounting flanges are reversible by removing  
the mounting screws and orienting the flanges in the  
desired position. Replace the screws after positioning  
flanges. Run a bead of silicone around the collar and  
slide the pipe over the collar. Secure with sheet metal  
screws.  
if multiple units are vented into the same vertical  
vent, a barometric damper must be installed on each  
appliance, such that the flue draft does not exceed  
(negative) 0.1" w.c.  
If using a power venter for any type of Category  
I venting, the draft should be set between (negative)  
0.01 and 0.10" w.c.  
2.2.3 Common Venting Systems  
Copper Brute II units are Category I fan-assisted  
when vented vertically and adhering to all applicable  
codes. Copper Brute II units are not allowed to be  
vented into a common horizontal vent system, unless  
a properly sized vent fan is used, and the common  
vent system is properly designed by the vent fan  
manufacturer or a qualified engineer. When common  
venting Copper Brute II fan-assisted unit with other  
appliances through one shared vertical duct called a  
“common vent”, special care must be taken by the  
installer to ensure safe operation. In the event that  
the common vent is blocked, it is possible, especially  
for fan-assisted devices, to vent backwards through  
non-operating appliances sharing the vent, allowing  
combustion products to infiltrate occupied spaces.  
If the appliances are allowed to operate in this  
condition, serious injury or death may occur.  
In addition to air needed for combustion, air  
shall also be supplied for ventilation, including all air  
required for comfort and proper working conditions  
for personnel. The Copper Brute II loses less than 1  
percent of its input rating to the room, but other heat  
sources may be present.  
2.2 Venting  
2.2.1 Vent Categories  
Depending upon desired Copper Brute II venting,  
it may be considered a Category I or a Category III  
appliance. In general, a vertical vent system will  
be a Category I system. However, in rare instances,  
a Copper Brute II’s vertical vent system may be  
considered Category III. In the U.S., the National Fuel  
Gas Code (ANSI Z223.1-Latest Edition), or in Canada  
the CSA B149.1 (latest edition), defines a Category  
I vent system, and includes rules and tables to size  
these vent systems. If the Copper Brute II’s vertical  
vent system does not satisfy the criteria for Category I  
venting, it must be vented as a Category III system.  
All Copper Brute II vent systems which  
WARNING  
Operation of appliances with a blocked common  
vent may lead to serious injury or death. Safety  
devices must be implemented to prevent blocked  
common vent operation. If safe operation of all  
appliances connected to a common vent cannot  
be assured, including prevention of spillage of flue  
gasses into living spaces, common venting should  
not be applied, and appliances should each be  
vented separately.  
It is for this reason that, in addition to  
following proper vent sizing, construction and safety  
requirements from the National Fuel Gas Code,  
ANSI Z223.1 or in Canada, from CSA B149.1 as  
well as all applicable local codes, it is required that  
installers provide some means to prevent operation  
with a blocked common vent. It is suggested that a  
blocked vent safety system be employed such that if  
the switch from one appliance trips due to excessive  
stack spill or backpressure indicating a blocked vent  
condition, that all appliances attached to the vent be  
locked out and prevented from operating. Note that  
the Copper Brute II is equipped with a blocked vent  
safety (pressure) switch, as shipped. However, this  
safety switch has only been designed and tested to be  
effective in installations where the Copper Brute II  
is vented separately and NOT common vented with  
other appliances. As an additional precaution, it is  
recommended that a Carbon Monoxide (CO) alarm be  
installed in all enclosed spaces containing combustion  
discharge horizontally (without the use of a power  
venter) are considered Category III vent systems.  
2.2.2 Category I Vent  
When vented as a category I appliance, the  
vent system must conform to the National Fuel Gas  
Code (ANSI Z223.1-Latest Edition) in the U.S., or  
in Canada, to CSA B149.1 (latest edition). The vent  
system must be sized and installed for a Category I  
Fan-Assisted Appliance.  
If chimney height is greater than 25 feet, or  
TERM  
DESCRIPTION  
Pipe  
Single-wall galvanized steel pipe, 24 gauge  
minimum (either insulated or non-insulated)  
Joint  
Permanent duct tape or aluminum tape  
Sealing  
Table 4. Required Combustion Air Piping Material.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 10  
U.S. Installations (see note 1)  
Canadian Installations (see note 2)  
A = Clearance above grade, veranda, porch,  
12 inches (30 cm)  
12 inches (30 cm)  
36 inches (91 cm)  
See note 5  
deck, or balcony  
B = Clearance to window or door that may be  
4 feet (1.2 m) below or to side of opening;  
1 foot (30 cm) above opening  
opened  
C = Clearance to permanently closed window  
See note 4  
D = Vertical clearance to ventilated soffit located  
above the terminal within a horizontal  
distance of 2 feet (61cm) from the center  
line of the terminal  
See note 4  
See note 5  
E = Clearance to unventilated soffit  
F = Clearance to outside corner  
G = Clearance to inside corner  
See note 4  
See note 4  
See note 4  
See note 5  
See note 5  
See note 5  
H = Clearance to each side of center line  
3 feet (91 cm) within a height 15 feet above  
the meter/regulator assembly  
extended above meter/regulator assembly See note 4  
I = Clearance to service regulator vent outlet  
See note 4  
3 feet (91 cm)  
J = Clearance to nonmechanical air supply inlet  
to building or the combustion air inlet to  
any other appliance  
4 feet (1.2 m) below or to side of opening;  
1 foot (30 cm) above opening  
36 inches (91 cm)  
K = Clearance to a mechanical air supply inlet 3 feet (91 cm) above if within 10 feet (3 m)  
6 feet (1.83 m)  
horizontally  
Vent termination not allowed in this location  
Vent termination not allowed in this location for category IV appliances. A vent shall not  
L = Clearance above paved sidewalk or paved for category IV appliances. For Category III terminate directly above a sidewalk or paved  
driveway located on public property  
appliances, vent must terminate at least 7  
driveway that is located between two single  
feet (2.13m) above the sidewalk or driveway. family dwellings and serves both dwellings.  
For Category III appliances that do not violate  
the previous condition, vent must terminate  
at least 7 feet (2.13m) above the sidewalk or  
driveway.  
M = Clearance under veranda, porch, deck,  
See note 4  
12 inches (30 cm) (see note 3)  
or balcony  
Notes:  
1. In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code.  
2. In accordance with the current CSA-B149.1 Installation Codes.  
3. Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.  
4. For clearances not specified in ANSI Z223.1 / NFPA 54, clearance is in accordance with local installation codes and the requirements of  
the gas supplier.  
5. For clearances not specified in CSA-B149.1, clearance is in accordance with local installation codes and the requirements of the gas supplier.  
Figure 3. Combustion Air and Vent Through Side Wall.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COPPER BRUTE II (500 - 2000)  
Page 11  
appliances. If assistance is required in determining  
how a blocked vent safety system should be connected  
to a Bradford White product, please call Applications  
Engineering at the Rochester phone number listed on  
back cover of this manual.  
and must be located in accordance with ANSI Z223.1/  
NFPA 54 and applicable local codes. In Canada, the  
installation must be in accordance with CSA B149.1 or  
.2 and local applicable codes. Consider the following  
when installing the terminal:  
1. Figure 3 shows the requirements for mechanical  
vent terminal clearances for the U.S. and Canada.  
2. Vent terminals for condensing appliances or  
appliances with condensing vents are not  
permitted to terminate above a public walkway,  
or over an area where condensate or vapor could  
create a nuisance or hazard.  
3. Locate the vent terminal so that vent gases cannot  
be drawn into air conditioning system inlets.  
4. Locate the vent terminal so that vent gases cannot  
enter the building through doors, windows,  
gravity inlets or other openings. Whenever  
possible, locations under windows or near doors  
should be avoided.  
5. Locate the vent terminal so that it cannot be  
blocked by snow. The installer may determine  
that a vent terminal must be higher than the  
minimum shown in codes, depending upon local  
conditions.  
6. Locate the terminal so the vent exhaust does  
not settle on building surfaces or other nearby  
objects. Vent products may damage such  
surfaces or objects.  
7. If the boiler or water heater uses ducted  
combustion air from an intake terminal located  
on the same wall, locate the vent terminal at least  
3 feet (0.9m) horizontally from the combustion  
air terminal, and locate the vent terminal at least  
1 foot (0.3m) above the combustion air terminal.  
Refer to the installation and operating  
instructions on all appliances to be common vented  
for instructions, warnings, restrictions and safety  
requirements. If safe operation of all appliances  
connected to a common vent cannot be assured,  
including prevention of spillage of flue gasses into  
living spaces, common venting should not be applied,  
and appliances should each be vented separately.  
2.2.4 Category III Vent  
When the Copper Brute II is vented with  
horizontal discharge, it must be installed per  
this installation manual and the venting system  
manufacturer’s installation instructions. The vent  
system must be sealed stainless steel, per Table 5.  
Route the vent pipe to the heater as directly as  
possible. Seal all joints and provide adequate hangers  
as required in the venting system manufacturer’s  
Installation Instructions. Horizontal portions of the  
venting system must be supported to prevent sagging  
and may not have any low sections that could trap  
condensate. The unit must not support the weight of  
the vent pipe. Horizontal runs must slope downwards  
not less than ¼ inch per foot (2 cm/m) from the unit to  
the vent terminal. Reference Table 2 for the size of the  
Category III vent system. Up to three elbows can be  
used with 50 linear feet (15.2m) of pipe. Subtract 10  
allowable linear feet (3.0m) for every additional elbow  
used.  
WARNING  
2.3.2 Side Wall Combustion Air Terminal  
The Bradford White side wall combustion air  
terminal (listed in Table 2) must be used when the  
unit takes its combustion air through a duct from a  
side wall. Consider the following when installing the  
terminal:  
1. Do not locate the air inlet terminal near a source  
of corrosive chemical fumes (e.g., cleaning fluid,  
chlorinated compounds, etc.)  
The outdoor vent terminal gets hot. Unit must be  
installed in such a way as to reduce the risk of  
burns from contact with the vent terminal.  
2.3 Locating Vent & Combustion Air  
Terminals  
2.3.1 Side Wall Vent Terminal  
The appropriate Bradford White side wall vent  
hood must be used, and is listed in the installation and  
operation manual. The terminal provides a means of  
installing the vent piping through the building wall,  
2. Locate the terminal so that it will not be subject  
to damage by accident or vandalism.  
3. Locate the combustion air terminal so that it  
cannot be blocked by snow. The National Fuel  
Gas Code requires that it be at least 12 inches (30  
cm) above grade, but the installer may determine  
it should be higher, depending upon local  
conditions.  
4. If the Copper Brute II is side-wall vented to the  
same wall, locate the vent terminal at least 3  
feet (0.9m) horizontally from the combustion air  
terminal, and locate the vent terminal at least 1  
foot (0.3m) above the combustion air terminal  
(see Figure 3).  
TERM  
DESCRIPTION  
Pipe  
Must comply with UL Standard 1738  
such as Type 29-4C Stainless Steel  
(either insulated or non-insulated).  
Follow vent manufacturer’s instructions  
Joint  
Sealing  
Table 5. Required Horizontal Venting Material.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 12  
cigarette, cigar or pipe.  
6. After it has been determined that each appliance  
remaining connected to the common venting  
system properly vents when tested as outlined  
above, return doors, windows, exhaust fans,  
fireplace dampers and any other gas burning  
appliance to their previous conditions of use.  
7. Any improper operation of the common venting  
system should be corrected so that the installation  
conforms to the National Fuel Gas Code, ANSI  
Z223.1/NFPA 54 and/or CSA B149.1, Installation  
Codes. When resizing any portion of the common  
venting system, the common venting system  
should be resized to approach the minimum size  
as determined using the appropriate tables in Part  
II of the National Fuel Gas Code, ANSI Z223.1/  
NFPA 54 and/or CSA B149.1, Installation Codes.  
2.3.3 Vertical Vent Terminal  
When the unit is vented through the roof, the  
vent must extend at least 3 feet (0.9m) above the point  
at which it penetrates the roof. It must extend at least  
2 feet (0.6m) higher than any portion of a building  
within a horizontal distance of 10 feet (3.0m), and high  
enough above the roof line to prevent blockage from  
snow. When the combustion air is taken from the roof,  
the combustion air must terminate at least 12" (30cm)  
below the vent terminal (see Figure 2).  
2.3.4 Vertical Combustion Air Terminal  
When combustion air is taken from the roof, a  
field-supplied rain cap or an elbow arrangement must  
be used to prevent entry of rain water (see Figure 2).  
The opening on the end of the terminal must be at least  
12" (30cm) above the point at which it penetrates the  
roof, and high enough above the roof line to prevent  
blockage from snow. When the vent terminates on the  
roof, the combustion air must terminate at least 12"  
(30cm) below the vent terminal.  
2.5 Vent Terminals for Outdoor Units  
For outdoor applications, the vent and  
combustion air openings must be covered with proper  
terminals to prevent rain, snow and other objects from  
falling into the Copper Brute II.  
If local codes allow, outdoor installations may  
use 1' of appropriately sized galvanized single wall  
or B-Vent and a rain cap for exhaust vent termination  
in the default configuration (venting out of the top).  
An appropriately sized galvanized 90° ell, positioned  
with the opening facing down, may be used on the  
combustion air inlet in the default configuration on  
the back of the unit. Note that some local codes may  
require a higher vertical vent height, extending above  
any perimeter fencing, etc. In installations where the  
appearance of the vent is objectionable, the low profile  
vent terminals in Table 6 may be used.  
2.4 Common Vent Test — Boilers  
When an existing boiler is removed from a  
common venting system, the common venting system  
is likely to be too large for proper venting of the  
appliances remaining connected to it.  
At the time of removal of an existing boiler, the  
following steps shall be followed with each appliance  
remaining connected to the common venting system  
placed in operation, while the other appliances  
remaining connected to the common venting system  
are not in operation.  
1. Seal any unused openings in the common venting  
system.  
2. Visually inspect the venting system for proper  
size and horizontal pitch and determine there is  
no blockage or restriction, leakage, corrosion and  
other deficiencies which could cause an unsafe  
condition.  
Part numbers for the low profile terminals to  
cover the vent and combustion air openings are shown  
in Table 6.  
3. Insofar as it is practical, close all building doors  
and windows and all doors between the space in  
which the appliances remaining connected to the  
common venting system are located and other  
spaces of the building. Turn on clothes dryers  
and any appliance not connected to the common  
venting system. Turn on any exhaust fans, such  
as range hoods and bathroom exhausts, so they  
will operate at maximum speed. Do not operate a  
summer exhaust fan. Close fireplace dampers.  
4. Place in operation the appliance being  
inspected. Follow the lighting instructions.  
Adjust thermostat so appliance will operate  
continuously.  
OUTDOOR  
VENT  
OUTDOOR  
COMBUSTION  
SIZE  
TERMINAL  
20254703  
20254705  
20254705  
D2007700  
D2007700  
D2007800  
D2007800  
AIR TERMINAL  
D2007900  
D2007900  
D2008000  
D2008000  
D2008000  
D2008000  
D2008200  
500  
750  
1000  
1250  
1500  
1750  
2000  
5. Test for spillage at the draft hood relief opening  
after 5 minutes of main burner operation. Use  
the flame of a match or candle, or smoke from a  
Table 6. Vent Terminals for Outdoor Units.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COPPER BRUTE II (500 - 2000)  
Page 13  
6. A sediment trap must be provided upstream of  
SECTION 3.  
Gas Supply and Piping  
the gas controls.  
7. All threaded joints should be coated with  
piping compound resistant to action of liquefied  
petroleum gas.  
3.1 Gas Supply and Piping  
Gas piping should be supported by suitable  
hangers or floor stands, not by the appliance.  
The Copper Brute II’s gas train allows the user to  
pipe the gas from either the right side or the left side  
of the unit. As shipped, the right side of the gas train is  
capped off, and there is a manual valve on the left side.  
If desired, the manual valve on the left side of the gas  
train may be moved to the right side, and the cap on  
the right side may be moved to the left.  
8. The appliance and its individual shutoff valve  
must be disconnected from the gas supply piping  
during any pressure testing of that system at test  
pressures in excess of 1/2 PSIG (3.45kpa).  
9. The unit must be isolated from the gas supply  
system by closing its individual manual shutoff  
valve during any pressure testing of the gas  
supply piping system at test pressures equal to or  
less than 1/2 PSIG (3.45kpa).  
Review the following instructions before  
proceeding with the installation.  
10. The appliance and its gas connection must be  
leak tested before placing it in operation.  
11. Purge all air from gas lines.  
1. Verify that the appliance is fitted for the proper  
type of gas by checking the rating plate. Copper  
Brute II appliances are equipped to operate at  
elevations up to 10,000 feet (3050m). Copper  
Brute II appliances may be adjusted to operate  
properly at altitudes above 2500 feet (see Section  
6.5.2) and the input will be reduced if the heating  
value of the gas supply is below sea level values.  
2. The maximum inlet gas pressure must not  
exceed 13" w.c. (3.2kPa). The minimum inlet gas  
pressure is 5" w.c. (1.2kPa).  
3. Refer to Table 7, size supply.  
4. Run gas supply line in accordance with all  
applicable codes.  
5. Locate and install manual shutoff valves in  
accordance with state and local requirements.  
WARNING  
Do not use open flame to check for leaks. An open  
flame could lead to explosion, which could result in  
property damage, serious injury or death.  
NOTE: The Copper Brute II appliance and all other  
gas appliances sharing the gas supply line must be  
firing at maximum capacity to properly measure the  
inlet supply pressure. The pressure can be measured  
at the supply pressure port on the gas valve. Low  
gas pressure could be an indication of an undersized  
gas meter, undersized gas supply lines and/or an  
obstructed gas supply line.  
DISTANCE FROM GAS METER  
OR LAST STAGE REGULATOR  
SIZE AND  
GAS TYPE  
0-100'  
0-31m  
100-200' 31-61m  
200-300' 61-91m  
500 natural  
500 propane  
1-1/2"  
1"  
3.8cm  
2.5cm  
2"  
1-1/2"  
5.1cm  
3.8cm  
2"  
1-1/2"  
5.1cm  
3.8cm  
750 natural  
750 propane  
2"  
1-1/2"  
5.1cm  
3.8cm  
2"  
1-1/2"  
5.1cm  
3.8cm  
2-1/2"  
2"  
6.4cm  
5.1cm  
1000 natural  
1000 propane  
2"  
1-1/2"  
5.1cm  
3.8cm  
2-1/2"  
2"  
6.4cm  
5.1cm  
3"  
2-1/2"  
7.6cm  
6.4cm  
1250 natural  
1250 propane  
2-1/2"  
2"  
6.4cm  
5.1cm  
2-1/2"  
2"  
6.4cm  
5.1cm  
3"  
2-1/2"  
7.6cm  
6.4cm  
1500 natural  
1500 propane  
2-1/2"  
2"  
6.4cm  
5.1cm  
3"  
2-1/2"  
7.6cm  
6.4cm  
3"  
2-1/2"  
7.6cm  
6.4cm  
1750 natural  
1750 propane  
2-1/2"  
2"  
6.4cm  
5.1cm  
3"  
2-1/2"  
7.6cm  
6.4cm  
3"  
2-1/2"  
7.6cm  
6.4cm  
2000 natural  
2000 propane  
3"  
2-1/2"  
7.6cm  
6.4cm  
3"  
2-1/2"  
7.6cm  
6.4cm  
3-1/2"  
3"  
8.9cm  
7.6cm  
Notes:  
1.These figures are based on 1/2" (0.12kPa) water column pressure drop.  
2.Check supply pressure and local code requirements before proceeding with work.  
3.Pipe fittings must be considered when determining gas pipe sizing.  
Table 7. Gas Piping Size.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 14  
Components required by local codes must be properly  
installed.  
SECTION 4A.  
Water Connections —  
Copper Brute II Boiler  
Note the recommended location of the  
temperature sensor on the diagrams; you must provide  
a location for the additional sensor shipped with  
the Copper Brute II. This sensor may be strapped  
onto pipe from 1" to 4" diameter, or inserted into an  
immersion well.  
4A.1 Heating System Piping:  
Hot Supply Connections — Boiler  
NOTE: This appliance must be installed in a closed  
pressure system with a minimum of 12 psi (82.7kPa)  
static pressure at the boiler.  
4A.2 Cold Water Make-Up — Boiler  
1. Connect the cold water supply to the inlet  
connection of an automatic fill valve.  
2. Install a suitable back flow preventer between the  
automatic fill valve and the cold water supply.  
3. Install shut off valves where required.  
Hot water piping should be supported by suitable  
hangers or floor stands. Do not support piping with  
this appliance. Due to expansion and contraction of  
copper pipe, consideration should be given to the type  
of hangers used. Rigid hangers may transmit noise  
through the system resulting from the piping sliding in  
the hangers. It is recommended that padding be used  
when rigid hangers are installed. Maintain 1" clearance  
to combustibles for hot water pipes.  
NOTE: The boiler, when used in connection with a  
refrigeration system, must be installed so the chilled  
medium is piped in parallel with the boiler with  
appropriate valves to prevent the chilled medium from  
entering the boiler.  
Pipe the discharge of the relief valve (full size)  
to a drain or in a manner to prevent injury in the event  
of pressure relief. Install an air purger, an air vent,  
a diaphragm-type expansion tank, and a hydronic  
flow check in the system supply loop. Minimum fill  
pressure must be 12psig (82.7kPa). Install shutoff  
valves where required by code.  
The boiler piping system of a hot water heating  
boiler connected to heating coils located in air  
handling appliances where they may be exposed to  
refrigerated air circulation must be equipped with flow  
control valves or other automatic means to prevent  
gravity circulation of the boiler water during the  
cooling cycle.  
A boiler installed above radiation level, or as  
required by the authority having jurisdiction, must be  
provided with a low water cutoff device either as a part  
of the boiler or at the time of boiler installation.  
Suggested piping diagrams are shown in Figures  
4 through 8. These diagrams are meant only as a guide.  
20°F  
25°F  
30°F  
35°F  
SIZE  
flow  
H/L  
flow  
H/L  
flow  
H/L  
flow  
H/L  
gpm  
feet  
gpm  
34  
51  
68  
85  
feet  
gpm  
28  
43  
57  
71  
85  
feet  
gpm  
24  
36  
49  
61  
73  
85  
feet  
500  
750  
1000  
1250  
1500  
1750  
2000  
43  
64  
85  
106 8.1  
1.7  
3.3  
5.0  
1.1  
2.3  
3.6  
6.1  
0.9  
1.7  
3.1  
4.7  
5.5  
8.4  
0.7  
1.2  
2.2  
3.4  
4.2  
5.8  
8.3  
4A.3 Water Flow Requirements — Boiler  
A hydronic heating (closed loop) application  
re-circulates the same fluid in the piping system. As a  
result, no new minerals or oxygen is introduced into  
the system. To ensure a proper operating temperature  
leading to long boiler life, a flow rate has been  
established based on the fluid temperature rise for this  
specific size boiler.  
Pump-mounted boilers can be ordered for use in  
primary secondary piping systems. The pumps used  
are sized for the headloss through the heater, plus 30  
feet (9.1m) of full-sized piping (same size as boiler  
outlet) and a normal number of fittings.  
Table 8 specifies water flow rates for boilers,  
which will enable the user to size a pump. The  
headloss shown is for the heater only, and the user  
will need to add the headloss of the system piping to  
properly size the pump.  
The minimum inlet water temperature for the  
Copper Brute II is 120°F (49°C) to avoid condensing  
on the copper coils.  
128 10.0 102 7.2  
N/R N/R 119 10.5 99  
N/R N/R 136 12.5 113 10.4 97  
Metric Equivalent  
11°C  
14°C  
17°C  
19°C  
SIZE  
flow  
H/L  
flow  
H/L  
flow  
H/L  
flow  
H/L  
lpm  
m
lpm  
m
lpm  
m
lpm  
m
500  
750  
1000  
1250  
1500  
1750  
2000  
161 0.5 129 0.3 107 0.3  
92  
0.2  
241 1.0 193 0.7 161 0.5 138 0.4  
321 1.5 257 1.1 214 0.9 184 0.7  
401 2.5 322 1.9 269 1.4 231 1.0  
483 3.0 386 2.2 322 1.7 276 1.3  
N/R N/R 451 3.2 375 2.6 322 1.8  
N/R N/R 515 3.8 429 3.2 368 2.5  
Notes: gpm = gallons per minute, lpm = liters per minute,  
H/L = headloss, ft = headloss in feet, m = headloss in meters.  
Maximum temperature rise is 35°F (19°C), as shown.  
Headloss is for boiler’s heat exchanger only.  
N/R = not recommended.  
Table 8. Water Flow Requirements - BWCH.  
4A.4 Freeze Protection — Boiler  
Boiler installations are not recommended in  
areas where the danger of freezing exists unless proper  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COPPER BRUTE II (500 - 2000)  
Page 15  
COLD WATER  
MAKE-UP  
SYSTEM  
RETURN  
C
C
SYSTEM  
SUPPLY  
SYSTEM PUMP  
PUMP LOCATION FOR  
NON-PUMP-MOUNTED UNITS  
CAUTION: THIS DRAWING SHOWS SUGGESTED  
PIPING CONFIGURATION AND VALVING, CHECK  
WITH LOCAL CODES AND ORDINANCES FOR  
ADDITIONAL REQUIREMENTS.  
PUMP LOCATION FOR PUMP-MOUNTED UNITS  
PRIMARY/SECONDARY MANDITORY FOR ALL  
VARIABLE FLOW SYSTEMS  
INSTALL AIR VENTS AT HIGH POINTS IN SYSTEM  
LEGEND  
PIPING & SIZING OF EXPANSION TANK  
PER TANK MANUFACTURER'S INSTRUCTIONS  
DIMENSION "C" (COMMON PIPING) TO BE FOUR  
PIPE DIAMETERS, MAX. (NO ELBOWS OR VALVES)  
BOILER CIRCUIT PIPING MUST BE EQUAL  
TO BOILER WATER CONNECTION SIZE  
EXPANSION TANK  
THERMOMETER  
WITH AIR SCOOP AND  
AUTO AIR VENT  
PURGE  
VALVE  
TEMPERATURE  
SENSOR  
BOILER CIRC. PUMP SIZED FOR FLOW THROUGH BOILER  
DOTTED DEVICES INDICATE ALTERNATE LOCATIONS  
3-WAY VALVE  
VALVE  
GLOBE VALVE  
CHECK VALVE  
PUT BOILER CONTROL SENSOR IN THE SYSTEM  
SUPPLY WHEN USING THIS PIPING STYLE.  
MINIMUM BOILER INLET WATER TEMPERATURE  
MUST BE AT LEAST 120°F.  
PRESSURE REDUCING VALVE  
W/ FAST FILL BYPASS  
PUMP  
Figure 4. Hydronic Piping — Multiple Boilers, Primary Secondary System.  
precautions are made for freeze protection. A non  
toxic, heating system, anti-freeze may be added to  
the hydronic system provided that the concentration  
does not exceed 50% and the anti freeze contains an  
anti foamant. When a 50/50 mixture is used, increase  
the water flow requirements by 15%, and increase the  
headloss requirements by 20%.  
Power outage, interruption of gas supply, failure  
of system components, activation of safety devices,  
etc., may prevent a boiler from firing. Any time a  
boiler is subjected to freezing conditions, and the  
boiler is not able to fire, and/or the water is not able  
to circulate, there is a risk of freezing in the boiler  
or in the pipes in the system. When water freezes,  
it expands. This can result in bursting of pipes in the  
system, or damage to the boiler, which could result in  
leaking or flooding conditions.  
IMPORTANT NOTES: Different glycol products  
may provide varying degrees of protection. Glycol  
products must be maintained properly in a heating  
system, or they may become ineffective. Consult the  
glycol specifications, or the glycol manufacturer, for  
information about specific products, maintenance  
of solutions, and set up according to your particular  
conditions.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 16  
COLD WATER  
MAKE-UP  
C
A
C
A
SYSTEM  
SUPPLY  
SYSTEM  
RETURN  
SYSTEM PUMP  
B
B
ADJUSTMENT PROCEDURE TO MAINTAIN  
120°F INLET TEMP:  
1. Turn on boiler and open valves A & B.  
2. After steady-state operation, if T1 is less than  
120°F, slowly close valve B until T1 climbs to  
120°F.  
3. If T1 is greater than 120°F, slowly close  
valve A until T1 drops to 120°F.  
4. Check after system operating temperature  
has stabilized. Make final adjustments.  
PUMP LOCATION FOR  
NON-PUMP-MOUNTED UNITS  
T1  
T1  
CAUTION: THIS DRAWING SHOWS SUGGESTED  
PIPING CONFIGURATION AND VALVING, CHECK  
WITH LOCAL CODES AND ORDINANCES FOR  
ADDITIONAL REQUIREMENTS.  
PUMP LOCATION FOR PUMP-MOUNTED UNITS  
PRIMARY/SECONDARY MANDITORY FOR ALL  
VARIABLE FLOW SYSTEMS  
INSTALL AIR VENTS AT HIGH POINTS IN SYSTEM  
PIPING & SIZING OF EXPANSION TANK  
PER TANK MANUFACTURER'S INSTRUCTIONS  
LEGEND  
EXPANSION TANK  
THERMOMETER  
DIMENSION "C" (COMMON PIPING) TO BE FOUR  
PIPE DIAMETERS, MAX. (NO ELBOWS OR VALVES)  
WITH AIR SCOOP AND  
AUTO AIR VENT  
PURGE  
VALVE  
TEMPERATURE  
SENSOR  
BOILER CIRCUIT PIPING MUST BE EQUAL  
TO BOILER WATER CONNECTION SIZE  
3-WAY VALVE  
VALVE  
GLOBE VALVE  
CHECK VALVE  
BOILER CIRC. PUMP SIZED FOR FLOW THROUGH BOILER  
DOTTED DEVICES INDICATE ALTERNATE LOCATIONS  
PUT BOILER CONTROL SENSOR IN THE SYSTEM  
SUPPLY WHEN USING THIS PIPING STYLE.  
PRESSURE REDUCING VALVE  
W/ FAST FILL BYPASS  
PUMP  
MINIMUM BOILER INLET WATER TEMPERATURE  
MUST BE AT LEAST 120°F.  
Figure 5. Hydronic Piping — Multiple Boilers, Low Temperature System.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COPPER BRUTE II (500 - 2000)  
Page 17  
150°F  
C
COLD WATER  
MAKE-UP  
C
180°F  
C
130°F  
180°F  
C
SYSTEM PUMP  
NOTES:  
1. BOILER LOOP IN EXAMPLE IS MAINTAINED AT 180°F.  
2. ZONE THERMOSTATS CAN BE INTERLOCKED WITH BOILER,  
SO THAT BOILER FIRES UPON CALL FOR HEAT FROM ANY  
ZONE.  
PUMP LOCATION FOR  
NON-PUMP-MOUNTED UNITS  
3. ZONE PIPING AND INTERLOCK WIRING TO BE DESIGNED  
BY SYSTEM ENGINEER.  
CAUTION: THIS DRAWING SHOWS SUGGESTED  
PIPING CONFIGURATION AND VALVING, CHECK  
WITH LOCAL CODES AND ORDINANCES FOR  
ADDITIONAL REQUIREMENTS.  
PUMP LOCATION FOR PUMP-MOUNTED UNITS  
PRIMARY/SECONDARY MANDITORY FOR ALL  
VARIABLE FLOW SYSTEMS  
INSTALL AIR VENTS AT HIGH POINTS IN SYSTEM  
LEGEND  
PIPING & SIZING OF EXPANSION TANK  
PER TANK MANUFACTURER'S INSTRUCTIONS  
EXPANSION TANK  
THERMOMETER  
WITH AIR SCOOP AND  
DIMENSION "C" (COMMON PIPING) TO BE FOUR  
PIPE DIAMETERS, MAX. (NO ELBOWS OR VALVES)  
AUTO AIR VENT  
PURGE  
VALVE  
TEMPERATURE  
SENSOR  
BOILER CIRCUIT PIPING MUST BE EQUAL  
TO BOILER WATER CONNECTION SIZE  
3-WAY VALVE  
VALVE  
GLOBE VALVE  
CHECK VALVE  
BOILER CIRC. PUMP SIZED FOR FLOW THROUGH BOILER  
DOTTED DEVICES INDICATE ALTERNATE LOCATIONS  
PUT BOILER CONTROL SENSOR IN THE SYSTEM  
SUPPLY WHEN USING THIS PIPING STYLE.  
PRESSURE REDUCING VALVE  
W/ FAST FILL BYPASS  
MINIMUM BOILER INLET WATER TEMPERATURE  
MUST BE AT LEAST 120°F.  
PUMP  
Figure 6. Hydronic Piping — One Boiler, Multi-Temperature System.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 18  
COLD WATER  
MAKE-UP  
SYSTEM  
RETURN  
C
SYSTEM  
SUPPLY  
SYSTEM PUMP  
PUMP LOCATION FOR  
NON-PUMP-MOUNTED UNITS  
PUMP LOCATION FOR PUMP-MOUNTED UNITS  
PRIMARY/SECONDARY MANDITORY FOR ALL  
VARIABLE FLOW SYSTEMS  
CAUTION: THIS DRAWING SHOWS SUGGESTED  
PIPING CONFIGURATION AND VALVING, CHECK  
WITH LOCAL CODES AND ORDINANCES FOR  
ADDITIONAL REQUIREMENTS.  
INSTALL AIR VENTS AT HIGH POINTS IN SYSTEM  
PIPING & SIZING OF EXPANSION TANK  
PER TANK MANUFACTURER'S INSTRUCTIONS  
LEGEND  
DIMENSION "C" (COMMON PIPING) TO BE FOUR  
PIPE DIAMETERS, MAX. (NO ELBOWS OR VALVES)  
EXPANSION TANK  
THERMOMETER  
BOILER CIRCUIT PIPING MUST BE EQUAL  
TO BOILER WATER CONNECTION SIZE  
WITH AIR SCOOP AND  
AUTO AIR VENT  
PURGE  
VALVE  
TEMPERATURE  
SENSOR  
BOILER CIRC. PUMP SIZED FOR FLOW THROUGH BOILER  
DOTTED DEVICES INDICATE ALTERNATE LOCATIONS  
3-WAY VALVE  
VALVE  
GLOBE VALVE  
CHECK VALVE  
PUT BOILER CONTROL SENSOR IN THE SYSTEM  
SUPPLY WHEN USING THIS PIPING STYLE.  
MINIMUM BOILER INLET WATER TEMPERATURE  
MUST BE AT LEAST 120°F.  
PRESSURE REDUCING VALVE  
W/ FAST FILL BYPASS  
PUMP  
Figure 7. Hydronic Piping - Primary-Secondary, Reverse-Return.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COPPER BRUTE II (500 - 2000)  
Page 19  
COLD WATER  
MAKE-UP  
SYSTEM  
RETURN  
C
SYSTEM  
SUPPLY  
SYSTEM PUMP  
ADJUSTMENT PROCEDURE TO MAINTAIN  
120°F INLET TEMP:  
1. Turn on boiler and open valves A & B.  
2. After steady-state operation, if T1 is less than  
120°F, slowly close valve B until T1 climbs to  
120°F.  
B
B
A
A
3. If T1 is greater than 120°F, slowly close valve  
A until T1 drops to 120°F.  
4. Check after system operating temperature has  
stabilized. Make final adjustments.  
PUMP LOCATION FOR  
NON-PUMP-MOUNTED UNITS  
T1  
T1  
CAUTION: THIS DRAWING SHOWS SUGGESTED  
PIPING CONFIGURATION AND VALVING, CHECK  
WITH LOCAL CODES AND ORDINANCES FOR  
ADDITIONAL REQUIREMENTS.  
PUMP LOCATION FOR PUMP-MOUNTED UNITS  
PRIMARY/SECONDARY MANDITORY FOR ALL  
VARIABLE FLOW SYSTEMS  
INSTALL AIR VENTS AT HIGH POINTS IN SYSTEM  
LEGEND  
PIPING & SIZING OF EXPANSION TANK  
PER TANK MANUFACTURER'S INSTRUCTIONS  
EXPANSION TANK  
THERMOMETER  
WITH AIR SCOOP AND  
DIMENSION "C" (COMMON PIPING) TO BE FOUR  
PIPE DIAMETERS, MAX. (NO ELBOWS OR VALVES)  
AUTO AIR VENT  
PURGE  
VALVE  
TEMPERATURE  
SENSOR  
BOILER CIRCUIT PIPING MUST BE EQUAL  
TO BOILER WATER CONNECTION SIZE  
3-WAY VALVE  
VALVE  
GLOBE VALVE  
CHECK VALVE  
BOILER CIRC. PUMP SIZED FOR FLOW THROUGH BOILER  
DOTTED DEVICES INDICATE ALTERNATE LOCATIONS  
PUT BOILER CONTROL SENSOR IN THE SYSTEM  
SUPPLY WHEN USING THIS PIPING STYLE.  
PRESSURE REDUCING VALVE  
W/ FAST FILL BYPASS  
PUMP  
MINIMUM BOILER INLET WATER TEMPERATURE  
MUST BE AT LEAST 120°F.  
Figure 8. Hydronic Piping - Primary-Secondary, Reverse-Return, Low Temperature.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 20  
for Hot Water Supply Systems (ANSI Z21.22 /  
CSA 4.4) of suitable discharge capacity must be  
installed in the separate storage tank system.  
SECTION 4B.  
Water Connections —  
Copper Brute II Water Heater  
If the Copper Brute II water heater is installed  
in a closed water supply system, such as one having a  
backflow preventer in the cold water supply line, the  
relief valve may discharge periodically, due to thermal  
expansion. Means (such as a properly-sized expansion  
tank) shall be provided to control thermal expansion.  
Contact the water supplier or local plumbing inspector  
on how to control this situation.  
4B.1 Water System Piping —  
Water Heater  
Hot water piping should be supported by suitable  
hangers or floor stands. Do not support piping with  
this appliance. Due to expansion and contraction of  
copper pipe, consideration should be given to the type  
of hangers used. Rigid hangers may transmit noise  
through the system resulting from the piping sliding in  
the hangers. It is recommended that padding be used  
when rigid hangers are installed.  
4B.3 Water Flow Requirements —  
Water Heater  
In a water heating application (an open system),  
new water is constantly being introduced. With the  
new water comes a fresh supply of minerals that can  
be deposited on the unit’s heat exchanger. This is  
commonly known as scaling. The amount of minerals  
will depend upon the hardness of the water. Water can  
also be aggressive, and can erode metals, including  
copper, if the water is moved too quickly. The water  
flow requirements for the Copper Brute II water heater  
are based upon the hardness of the water. The water  
flow is kept high enough to prevent scaling, but low  
enough to prevent tube erosion. For extremely soft or  
hard water, cupro-nickel tubes are available. Contact a  
Bradford White Representative if you have questions  
or concerns about water quality.  
Pump-mounted water heaters can be ordered  
with standard pumps for soft or normal water or with  
pumps for hard water. The pumps used are sized for  
the headloss through the heater, plus 30 feet (9.1m)  
of full-sized piping (same size as heater outlet) and a  
normal number of fittings.  
The Copper Brute II can be used with several  
different types of readily available storage tanks. A  
pump draws water from the storage tank and pumps  
the water through the heater and back into the tank.  
Pump-mounted units have a circulating pump built  
into the water heater. The pumps used are sized for the  
headloss through the heater, plus 30 feet (9.1m) of full-  
sized piping (same size as boiler outlet) and a normal  
number of fittings. Pumps used on pump-mounted unit  
are sized for soft/normal or hard water, so make sure  
a pump-mounted unit matches the water quality of the  
installation.  
Pipe the outlet from the heater’s relief valve  
such that any discharge from the relief valve will be  
conducted to a suitable place for disposal when relief  
occurs. Do not reduce line size or install any valves in  
this line. The line must be installed to allow complete  
drainage of both the valve and the line.  
Suggested piping diagrams are shown in Figures  
9 through 12. These diagrams are meant only as a  
guide. Components required by local codes must be  
properly installed.  
Table 9 specifies water flow rates for water  
heaters, which will enable the user to size a pump.  
The headloss shown is for the heater only, and the user  
will need to add the headloss of the piping system to  
properly size the pump.  
Note the recommended location of the  
temperature sensor on the diagrams. The Copper Brute  
II is shipped with an additional sensor that can be used  
for more full-featured domestic water heating control.  
To get these features, you must provide a location for  
the additional sensor. It can be strapped to a pipe from  
1" to 4" diameter, or inserted into a tank immersion  
well.  
The minimum inlet water temperature for the  
Copper Brute II is 120°F (49°C) to avoid condensing  
on the copper coils.  
4B.4 Combined Water Heating (potable)  
and Space Heating — Water Heater  
NOTE: These systems are not allowed in the  
Commonwealth of Massachusetts.  
Piping and components connected to this water  
heater for the space heating application shall be  
suitable for use with potable water.  
Toxic chemicals, such as used for boiler  
treatment, shall not be introduced into the potable  
water used for space heating.  
This water heater when used to supply potable  
water shall not be connected to any heating system  
or component(s) previously used with a non-potable  
water heating appliance.  
4B.2 Hot Water Supply Piping —  
Water Heater  
Follow the tank manufacturer’s guidelines for  
completion of the hot water system connections.  
NOTE: A listed temperature and pressure relief  
valve listed as complying with the Standard for  
Relief Valves and Automatic Gas Shutoff Devices  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COPPER BRUTE II (500 - 2000)  
Page 21  
LOCATION OF  
FACTORY-MOUNTED  
PUMP  
KEY:  
WATER CATEGORY  
GRAIN HARDNESS PER GALLON  
S = SOFT  
N = NORMAL 7.6 THROUGH 17  
H = HARD  
OVER 17  
1 THROUGH 7.5  
5
PPM / 17.1 = Grains Per Gallon  
1
2
3
4
CAUTION: THIS DRAWING SHOWS SUGGESTED  
PIPING CONFIGURATION AND VALVING, CHECK  
WITH LOCAL CODES AND ORDINANCES FOR  
ADDITIONAL REQUIREMENTS.  
NOTES:  
LEGEND  
1. OPTIONAL CWMU & RECIRC. LINE LOCATION.  
THERMOMETER  
EXPANSION TANK  
2. LOCATE PENNANT DHW SENSOR OR REMOTE AQUASTAT  
WELL IN LOWER 1/3 OF TANK.  
TEMPERATURE  
SENSOR  
TPRV  
PRV  
3. BACK FLOW PREVENTER MAY BE REQUIRED. CHECK LOCAL CODES.  
4. THERMAL EXPANSION TANK MAY BE REQUIRED. CHECK LOCAL CODES.  
3-WAY VALVE  
VALVE  
GLOBE VALVE  
CHECK VALVE  
5. WHEN USING FACTORY MOUNTED PUMP, MAX PIPE LENGTH IS  
30 FEET TOTAL, SIX 90° ELBOWS , FULL PIPE SIZE.  
PRESSURE REDUCING  
VALVE  
6. CAUTION: PUMP SIZING MUST BE BASED UPON WATER HARDNESS AT  
JOB SITE  
PUMP  
Figure 9. Water Heater Piping — One Heater, One Tank.  
When the system requires water for heating at  
temperatures higher than required for other uses,  
an anti-scald mixing or tempering valve shall be  
installed to temper the water for those uses in order  
to reduce scald hazard potential.  
of system components, activation of safety devices,  
etc., may prevent a heater from firing. Any time a  
heater is subjected to freezing conditions, and the  
heater is not able to fire, and/or the water is not  
able to circulate, there is a risk of freezing in the  
heater or in the pipes in the system. When water  
freezes, it expands. This can result in bursting of pipes  
in the system, or damage to the heater, which could  
result in leaking or flooding conditions.  
4B.5 Freeze Protection – Water Heater  
Although Copper Brute II water heaters are  
design-certified for outdoor installations, such  
installations are not recommended in areas subject to  
freezing temperatures, unless proper precautions are  
taken.  
Contact the local factory representative or  
Bradford White for additional information.  
Power outage, interruption of gas supply, failure  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 22  
Figure 10. Water Heater Piping — Multiple Heaters, One Tank.  
Figure 11. Water Heater Piping — One Heater, Multiple Tanks.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COPPER BRUTE II (500 - 2000)  
Page 23  
Figure 12. Water Heater Piping — Multiple Heaters, Multiple Tanks.  
GPM  
N
FT  
TEMP RISE °F  
LPM  
M
TEMP RISE °C  
SIZE  
500  
S
H
S
N
H
S
N
H
S
N
H
S
N
H
S
N
H
5
45  
45  
45  
68  
68  
68  
68  
68  
68  
68  
68  
68  
90  
90  
90  
90  
90  
90  
1.8 2.3 3.5  
2.1 3.0 6.0  
2.3 3.6 6.1  
3.8 3.8 6.3  
3.9 3.9 6.5  
4.0 4.0 6.7  
10.0 10.0 10.0  
19  
28  
38  
31  
38  
44  
30  
13  
19  
25  
31  
38  
44  
30  
9
170 257 341  
170 257 341  
170 257 341  
257 257 341  
257 257 341  
257 257 341  
424 424 424  
0.5 0.7 1.1  
0.6 0.9 1.8  
0.6 1.1 1.9  
1.2 1.2 1.9  
1.2 1.2 2.0  
1.2 1.2 2.0  
3.0 3.0 3.0  
10  
16  
21  
17  
21  
24  
17  
7
750  
14  
19  
24  
28  
33  
30  
10  
14  
17  
21  
24  
17  
8
1000  
1250  
1500  
1750  
2000  
10  
13  
16  
18  
17  
112 112 112  
NOTES: 1. S = soft water (1 to 7.5 grains hardness)  
2. N = normal water (7.6 to 17 grains hardness)  
3. H = hard water (more than 17 grains hardness)  
4. gpm = gallons per minutes, lpm = liters per minute, ft = headless in feet, m = headloss in meters  
5. Headloss is for heater’s heat exchanger only  
Table 9. Water Flow Requirements – BWCV.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 24  
Copper Brute II 1750-2000 will require two 120-  
volt fused supplies. Heater circuit can be identified  
with 10AWG wires to include black, white and green  
(all solid colors). Pump circuit can be identified with  
three 12AWG wires to include a black wire with a  
white tracer (stripe), a white and green wire.  
SECTION 5.  
Electrical Connections  
WARNING  
The appliance must be electrically grounded in  
accordance with the requirements of the authority  
having jurisdiction or, in the absence of such  
requirements, with the latest edition of the National  
Electrical Code, ANSI/NFPA 70, in the U.S. and  
with latest edition of CSA C22.1 Canadian Electrical  
Code, Part 1, in Canada. Do not rely on the gas  
or water piping to ground the metal parts of the  
boiler. Plastic pipe or dielectric unions may isolate  
the boiler electrically. Service and maintenance  
personnel, who work on or around the boiler, may  
be standing on wet floors and could be electrocuted  
by an ungrounded boiler.  
5.1.2 Pump Circuit  
Conversion to separate pump circuit will  
necessitate removing the three jumpers within  
the internal wiring of the 120-volt portion of the  
heater (see Figure 13). Only do this with the power  
disconnected to the unit.  
To rewire the pump circuit, bring in another  
120-volt fused supply (L2, N2 & Ground). Connect  
incoming power (L2) to the main power switch using  
spade (fork) terminal. From the other side of the main  
power switch connect to the main terminal block using  
a ¼" female insulated quick connect. This will be  
the same position where the jumper had terminated.  
Connect N2 and Ground to the main terminal block  
using ¼" female insulated quick connect (refer to  
Figure 13).  
5.1 Main Power  
Single pole switches, including those of safety  
controls and protective devices must not be wired in a  
grounded line.  
All electrical connections are made in the field  
wiring terminal strip, which is located at the right side  
of the appliance.  
Ladder diagrams are shown in Figures 16  
through 18, while wire diagrams are shown in Figures  
19 through 21.  
NOTE: All internal electrical components have been  
prewired. No attempt should be made to connect  
elec-trical wires to any other location except the wiring  
box.  
5.2 Temperature Control  
5.2.1 Temperature Control Description  
The field wiring panel is located on the right  
side of the Copper Brute II (shown in Figure 14).  
The following components are connected to the field  
wiring panel:  
5.1.1 Power Circuits  
All Copper Brute II non-pump-mounted heaters  
require a single 120-volt fused supply.  
Temperature sensor: The sensor supplied loose  
Pump-mounted Copper Brute IIs models 500-  
1500 also uses a single 120-volt fused supply and  
models 1750-2000 use two 120-volt fused supplies.  
The installer can change the pump mounted  
single service heaters to use a separate circuit for the  
pump, if desired. Instructions to make this change are  
found in Section 5.1.2.  
Copper Brute II 500-1500 main power (L1, N1  
& Ground) shall be connected to the three wires (10  
AWG) supplied. Over current protection ratings can be  
found in Table 10.  
SINGLE CIRCUIT CONNECTIONS  
HEATER  
PUMP  
ONLY  
W/O PUMP  
WITH PUMP  
500  
750  
15  
15  
20  
25  
25  
25  
25  
20  
20  
25  
30  
30  
15  
15  
15  
15  
15  
15  
20  
1000  
1250  
1500  
1750  
2000  
Table 10. Electrical Data.  
Figure 13. Removing Jumpers.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COPPER BRUTE II (500 - 2000)  
Page 25  
wired devices to interlock with the boiler (louver  
with the Copper Brute II is installed in the piping  
or tank, per the suggested piping diagrams, and  
connected to the “S C2” and “SUP S” terminals. See  
Section 6.3 for “Mode” definitions and Figures 22 to  
24 for field wiring schematics.  
Outdoor Reset Sensor: The outdoor reset  
sensor, if used, is connected to the “OD S” and “S C2”  
terminals.  
Field Installed Pump: A pump contactor can  
be wired to the “PMP” and “PMP” terminals (these  
terminals supply 24VAC to close the contactor  
whenever the boiler pump would be operated).  
NOTE: In some cases, the boiler pump is operated  
continuously.  
External Alarm: An external power supply and  
alarm can be connected to the “ALRM” and “ALRM”  
terminals. In the event of an ignition system lockout, a  
contact closure occurs across these terminals.  
External Heat Demand Indication: 24VAC  
is present across the “HT OUT” and “LWCO GND”  
terminals whenever the temperature control sees a  
system heat demand. This can be used to power a  
contactor (0.5 Amp, maximum) for devices operated  
whenever the boiler could fire (combustion air fans,  
motorized louvers, etc.) NOTE: In some cases, the  
temperature control will always see a heat demand  
in the system, such as when the “Ht D” and Com D”  
terminals are jumpered.  
switches, flow switches, etc.), remove the jumper  
between the “COM” and “NO” terminals and wire the  
device in series across these terminals. (See Section  
5.3 for important information about external staging  
controls and building automation systems.)  
System Heat Demand: Remove the jumper  
across the “COM D” and “Ht D” terminals, and con-  
nect the zone pump or valve end switch, thermostat,  
aquastat, or other indication of system heat demand  
to these terminals. If no indication of a system heat  
demand will be provided, the jumper must remain in  
place. When jumpered, the temperature control will  
always see a heat demand, and the Copper Brute II  
pump (if equipped) or any pump with its contactor  
connected to the “PMP” and “PMP” terminals will  
run continuously. In addition, any device connected  
through the “HT OUT” and “LWCO GND” terminals  
for an external indication of the heat demand will  
run continuously. See Section 6 for more information  
on the system heat demand for various modes of  
operation.  
Refer to Figures 22 through 24 for field wiring of  
Other Field Interlocks: To install other field-  
Figure 14. Field Wiring Panel  
Figure 15. External Control Connection Wiring.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 26  
additional components.  
5.3 External Staging Control Wiring  
WARNING  
Improper field wiring may result in fire or explosion  
which can cause property damage, severe injury,  
or death. Make only wiring connections which are  
in accordance with the Installation and Operation  
manual.  
AVERTISSEMENT  
Un câblage incorrect lors de l’installation peut  
causer un incendie ou une explosion pouvant  
entraîner des dommages matériels, de graves  
blessures ou la mort. Ne faire seulement que les  
connexions conformes au Manuel d’installation et  
d’exploitation.  
The wiring methods in this section must be  
used to connect an external staging control, such as a  
multiple boiler control, building automation system,  
energy management system, etc.) Other wiring  
methods may be unsafe.  
Figure 15 shows how to wire the external  
controller to the Copper Brute II’s field wiring panel,  
which is located on the right side of the Copper Brute  
II.  
Most of the time, the number of stages from the  
external control will match the number of stages on  
the Copper Brute II. However, in some instances, the  
controller will not have enough staging capability to  
work with all of the stages on a Copper Brute II unit  
(for instance, using an 8-stage external control with  
four 4-stage Copper Brute II units.) In these instances,  
it is very important to follow the instructions in this  
section Figure 15 shows how to combine stages on the  
Copper Brute II for those instances when the external  
controller cannot control all the stages available.  
NOTE: The only time Copper Brute II stages should  
be jumpered is when the Copper Brute II has an  
external control, and the Copper Brute II is used in  
Mode 6. In all other modes, when the Copper Brute II  
controls its stages, the terminals shown in Figure 15  
must NOT be jumpered.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COPPER BRUTE II (500 - 2000)  
Page 27  
Figure 16. Copper Brute II 500 - 750 Ladder Diagram.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 28  
Figure 17. Copper Brute II 1000 Ladder Diagram.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COPPER BRUTE II (500 - 2000)  
Page 29  
Figure 18. Copper Brute II 1250 - 2000 Ladder Diagram.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 30  
Figure 19. Copper Brute II 500 - 1000 Wiring Schematic.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COPPER BRUTE II (500 - 2000)  
Page 31  
Figure 20. Copper Brute II 1250 - 1500 Wiring Schematic.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 32  
Figure 21. Copper Brute II 1750 - 2000 Wiring Schematic.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COPPER BRUTE II (500 - 2000)  
Page 33  
Figure 22. Field Wiring.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 34  
Figure 23. Field Wiring for Modes 1 - 5.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COPPER BRUTE II (500 - 2000)  
Page 35  
Figure 24. Field Wiring for Mode 6.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 36  
display, and the energizing of additional burner stages  
is indicated by front panel lights.  
SECTION 6.  
Operating Instructions  
If there is a subsequent loss of flame signal, the  
burner will attempt re-ignition up to three times (only  
once if optional lockout ignition module is used.)  
When the call for heat is satisfied, the gas  
valve(s) closes and the blower(s) continues to run  
for 30 seconds. The pump will continue to run for a  
minimum of 20 seconds and up to a programmable  
maximum of 10 minutes.  
If a call for heat is prevented from being satisfied  
either by a safety interlock or due to an ignition  
lockout, the red SERVICE indicator on the front panel  
will light. To reset the standard ignition module,  
the reset button on the module must be pressed.  
Interrupting power to this module will not reset the  
lockout.  
6.1 Sequence of Operation  
A call for heat can be initiated either  
automatically (auto mode) under thermostatic control  
by the Copper Brute II temperature control, or by an  
external contact closure (manual mode).  
In auto mode, the Copper Brute II burner will  
fire its stages of input to maintain a target temperature  
programmed into the temperature control. The  
controller can be programmed per Section 6.3.  
In manual mode, an external control will control  
the Copper Brute II stages, as long as the Copper  
Brute II control is set to mode 6, and the auto/manual  
switch (located inside the control compartment) is set  
to manual.  
The amber READY light on the front panel  
indicates that the control system is energized. Upon  
a call for heat, the green HEAT indicator on the front  
panel will light.  
The Copper Brute II 1000–2000 models have  
two ignition modules that control different burners. If  
one module should fail for any reason, the remaining  
module can operate its burner(s) independently.  
If the unit is pump-mounted, the pump will be  
energized. The pump terminals on the field-wiring  
terminals strip will energize a field pump that is  
properly interlocked with the Copper Brute II. The  
green PUMP indicator on the front panel will light.  
Once the water flow switch makes, and if all of  
the safety interlocks are closed, the ignition module  
will energize the blower(s) for a 15-second pre-purge,  
followed by a 20-second period to allow the ignitor to  
heat.  
Energizing the blower pressurizes the air box  
(which supplies air to the burners) and closes the  
normally-open contact(s) of the airflow pressure  
switch(es). This allows the ignition module to proceed  
with the ignition sequence.  
The blocked flue pressure switch senses the  
pressure in the plenum. It will interrupt the airflow  
sensing circuit if this pressure exceeds a maximum  
value. If airflow is not proven, the ignition module  
will lockout.  
The ignition module checks that the ignitor  
current has reached a minimum value and energizes  
the gas valve at the end of the ignitor heating period.  
The green STAGE 1 indicator on the front panel will  
light, indicating that the stage 1 gas valve is open.  
After a 4-second trial for ignition, the ignitor  
switches off, and unless a flame is detected by the  
flame sensor, the gas valve will close and the ignition  
module will either attempt ignition again (up to three  
times) or will lockout (if the optional lockout ignition  
module is used).  
6.2 Filling the Boiler System  
1. Ensure the system is fully connected. Close all  
bleeding devices and open make-up water valve.  
Allow system to fill slowly.  
2. If make-up water pump is employed, adjust  
pressure switch on pumping system to provide  
a minimum of 12 psi (81.8 kPa) at the highest  
point in the heating loop.  
3. If a water pressure regulator is provided on the  
make-up water line, adjust the pressure regulator  
to provide at least 12 psi (81.8 kPa) at the highest  
point in the heating loop.  
4. Open bleeding devices on all radiation units  
at the high points in the piping throughout  
the system, unless automatic air bleeders are  
provided at such points.  
5. Run system circulating pump for a minimum of  
30 minutes with the boiler shut off.  
6. Open all strainers in the circulating system,  
check flow switch operation, and check for  
debris. If debris is present, clean out to ensure  
proper circulation.  
7. Recheck all air bleeders as described in Step 4.  
8. Check liquid level in expansion tank. With the  
system full of water and under normal operating  
pressure, the level of water in the expansion tank  
should not exceed ¼ of the total, with the balance  
filled with air.  
9. Start up boiler according to the procedure in this  
manual. Operate the entire system, including the  
pump, boiler, and radiation units for one (1) hour.  
10. Recheck the water level in the expansion tank. If  
the water level exceeds ¼ of the volume of the  
expansion tank, open the tank drain, and drain to  
that level.  
If flame is sensed, the burner will continue to  
fire as long as there is a call for heat. In Auto mode,  
additional stages are delayed by a minimum of 60  
seconds (less prepurge and ignitor warm-up time) and  
once energized, must fire for at least 30 seconds. The  
request for additional stages is indicated on the control  
11. Shut down the entire system and vent all  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COPPER BRUTE II (500 - 2000)  
Page 37  
plumbing loop that has, in turn, one or more plumbing  
loops connected to it, which provide heat to radiant  
tubing, radiators, DHW heat exchangers, etc. This  
plumbing loop is the “primary loop.”  
radiation units and high points in the system  
piping, as described in Step 4.  
12. Close make-up water valve and check strainer in  
pressure reducing valve for sediment or debris  
from the make-up water line. Reopen make-up  
water valve.  
13. Check gauge for correct water pressure and also  
check water level in the system. If the height  
indicated above the boiler insures that water is at  
the highest point in the circulating loop, then the  
system is ready for operation.  
14. Refer to local codes and the make-up water  
valve manufacturer’s instructions as to whether  
the make-up water valve should be left open or  
closed.  
15. After placing the unit in operation, the ignition  
system safety shutoff device must be tested. First,  
shut off the manual gas valve, and call the unit  
for heat. After the pre-purge and ignitor heat-up  
time, the main gas terminals will be energized,  
attempting to light, for four (4) seconds, and then  
will de-energize. The unit will go into lockout  
mode. Second, turn the power off and then on  
again, open the manual gas valve and allow the  
unit to light. While the unit is operating, close the  
manual gas valve and ensure that power to the  
main gas valve has been cut.  
In primary secondary piping modes, the  
temperature control monitors the primary loop  
temperature. The extra sensor that is shipped loose  
with Copper Brute II is installed in the primary loop.  
The temperature control fires the boiler stages to  
provide the “target temperature” at that sensor. Over  
time, the temperature control will learn the system  
curve and adjust the firing of the stages to meet the  
demand in the most efficient way.  
For complex systems, with variable speed  
injection circulators, multiple temperature zones, etc.,  
you may need to consult with a qualified engineer or  
Bradford White Applications Engineering.  
“Parallel Piping”  
The term “parallel piping” means the Copper  
Brute II is supplying heat directly to one or more  
storage tanks, radiators, radiant zones, etc., plumbed  
in series. In these systems, the target temperature is  
the boiler’s outlet temperature. An exception is for  
domestic hot water systems using mode 3, where the  
extra sensor is placed in the tank.  
6.3.2 Choosing the Mode  
There are six modes of operation for the Copper  
Brute II temperature control. The loose sensor must  
be installed and connected prior to programming the  
temperature control, as it provides sensing the “target”  
temperature. The location of the sensor is dependent  
on the type of piping used. Figures 4 through 8 show  
suggested locations for the temperature sensor in  
various hydronic piping configurations.  
16. Within three (3) days of start-up, recheck all air  
bleeders and the expansion tank as described in  
Steps 4 and 8 above.  
Important: The installer is responsible for identifying  
to the owner/operator the location of all emergency  
shutoff devices.  
Modes 1 through 5 are the automatic modes,  
requiring the diagnostic panel’s AUTO/MAN switch  
(located on the slide-out control drawer) to remain in  
the default AUTO position. These modes enable the  
temperature control to fire the Copper Brute II’s stages  
to meet the demand of the system. In these modes,  
the Copper Brute II temperature control continuously  
samples the inlet, outlet and target temperatures.  
Mode 6 is the manual mode, and the AUTO/  
MAN switch must be moved to the MAN position. An  
external control, such as a building automation system  
or multiple boiler control, just be wired to the field  
wiring panel in order to fire the boiler, bypassing the  
temperature control (see Section 5.3 for important  
information about external staging controls and  
building automation systems).  
WARNING  
Do not use this appliance if any part has been  
under water. Immediately call a qualified service  
technician to inspect the appliance  
and to replace any part of the control system and  
any gas control that may have been  
under water.  
6.3 Programming the Temperature  
Control  
The same temperature control is used on all  
versions of the Copper Brute II (in two-and four-stage  
configurations), providing maximum flexibility to meet  
the needs of any system. Before start-up, you must  
program the temperature control for the type of system  
you have. You must determine the type of piping the  
system has, the mode the temperature control will  
operate in, and the various settings for that mode.  
Table 11 contains information to identify the  
mode you should use for your system.  
6.3.3 Programming  
6.3.1 System Piping  
“Primary Secondary Piping”  
In the context of these instructions, “primary  
secondary piping” means the boiler provides heat to a  
Before programming, you must determine the  
type of piping you have, the mode you will use, and  
install the extra sensor if required for that mode. See  
Sections 6.3.1 and 6.3.2 for more information, or  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 38  
contact the factory.  
BOIL MASS (Boiler Mass): Always choose “1”.  
BOIL TARGET (Boiler Target Temperature):  
Your desired set-point temperature. See Section 6.4.5  
and Figure 26 for more information.  
BOIL MIN (Boiler Minimum Temperature): This  
setting tells the Temperature Control to maintain at  
least this temperature, even if the PID logic determines  
a lower setting would save energy. The BOIL MIN  
should always be 120°F (49°C) or higher to prevent  
condensation, and can be set up to 10°F below your  
BOIL TARGET temperature. See Section 6.4.3 for  
more information.  
There are three black programming buttons on  
the Temperature Control (see Figure 25). Press and  
hold all three programming buttons until the word  
ADJUST appears in the upper right corner of the LCD  
display (it replaces the word VIEW).  
Pressing ITEM cycles you through the items you  
need to program. UP ARROW increases the value of  
that item, while DOWN ARROW decreases it. ADJUST  
mode exits if you don’t press a button for 20 seconds.  
To return to ADJUST mode, simply press and hold the  
three buttons again.  
The first item is MODE; enter the mode number  
as determined above. The Temperature Control will  
then present you with some or all of the following  
options, depending on the mode you have chosen:  
In mode 6 (external boiler control), you will not  
see the following options. Refer to Section 6.4.10 for  
setup information for mode 6.  
BOIL MAX (Boiler Maximum Temperature):  
This setting tells the Temperature Control to limit the  
maximum outlet temperature to this setting or below,  
and determines how quickly the temperature control  
“stages down” or off. If the BOIL MAX setting is  
much higher than the BOIL TARGET temperature, the  
temperature control will fire all stages until the target  
temperature is reached, and then shut down all stages  
at once. To enable gradual staging down of the boiler  
as you approach your target temperature, set the BOIL  
MAX to the same setting as the target temperature. See  
Section 6.4.4 for more information.  
DIFF (Boiler Differential): This setting is divided  
above and below the target temperature. The water  
will be allowed to cool ½ this setting below the target  
temperature before first stage fires, and will heat to ½  
this setting above the target temperature before staging  
the boiler down. See Section 6.4.1 and Figure 28 for  
more information.  
FOR ALL OTHER MODES:  
APPLICATION  
MODE  
SYSTEM  
SETTING  
SENSORS USED  
• Parallel piping (non-  
primary/secondary)  
hydronic system  
• DHW with or without  
a tank aquastat  
1
2
• None  
• Primary/secondary  
hydronic system  
(pref'd by Bradford White)  
• No outdoor reset  
• Bradford White System  
Sensor (shipped  
with each Copper Brute II)  
PUMP DLY (Pump Delay): On pump mounted  
units, the boiler mounted pump continues to run for  
the time selected after the heat demand in the system is  
satisfied. This setting also affects the 24VAC output on  
the “PMP” “PMP” terminals (see Section 5.2). These  
terminals can power a contactor for a larger system  
pump. Bradford White recommends a minimum pump  
• Parallel piping (non-  
primary/secondary)  
hydronic system  
• DHW  
• Advanced control  
capability  
3
• Bradford White System  
Sensor (shipped (with  
each Copper Brute II)  
• No outdoor reset  
• Parallel piping (non-reset  
primary/secondary)  
hydronic system  
• Advanced control  
capability  
• Bradford White outdoor  
sensor (optional  
part #R2014000)  
4
5
• Outdoor reset  
• Primary/secondary  
hydronic system  
(preferred by  
• Bradford White System  
Sensor (shipped  
with each  
Bradford White)  
• Outdoor reset  
Copper Brute II)  
• Bradford White outdoor  
reset sensor (optional part  
# R2014000)  
• Building automation  
control  
• Multiple boiler system  
control  
6
• None  
• Energy management  
system  
• Other external control  
Table 11. Modes and Sensors for Applications.  
Figure 25. Temperature Control.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COPPER BRUTE II (500 - 2000)  
Page 39  
EXAMPLE 1  
delay setting of 5 minutes. See Section 6.4.6 for more  
DHW (Mode 3) Programming. For domestic  
hot water systems up to 175°F / 79°C, use mode 3 as  
described below.  
information.  
NOTE: In modes other than mode 6, the pump will  
run continuously if the “HtD” and “ComD” terminals  
are jumpered and not connected to a zone valve or  
pump end switch, or other “contact closure” device  
to indicate when the heat demand in the system is  
satisfied. The pump will never run, and the boiler will  
never fire, if the jumper is removed and the terminals  
left empty.  
Step 1: Install the additional sensor into the  
storage tank, wiring it to “SC2” and “SUPS” terminals  
on the field wiring panel (Figure 23).  
Step 2: Press the three programming buttons  
to enter ADJUST mode (Figure 25). Press ITEM to  
select the programming item, and the arrow keys to  
adjust the setting. TARGET TANK is desired tank  
temperature. Recommended settings with a desired  
tank temperature of 125°F:  
OUTDOOR RESET (modes 4 and 5): Outdoor  
reset adjusts the target temperature based on the  
outdoor air temperature and reset ratio. The reset ratio  
is determined from the Boiler Start, Boiler Design,  
Outdoor Start and Outdoor Design settings.  
HEAT DEMAND For heat demand to exist,  
there must be continuity between the Com D (common  
demand) and Ht D (heat demand) terminals. The  
Copper Brute II ships with a jumper between these  
terminals.  
The control also evaluates the sensor(s) installed  
in the system. If the control is not in warm weather  
shutdown (WWSD), and the sensor(s) are below the  
target temperature, the “Dem” segment is turned on in  
the display. The control energizes the pump (on pump  
mounted boilers) and energizes both “PMP” terminals.  
The pump symbol appears in the display (see Figures  
25 and 26). The control then operates the stages to  
maintain the setpoint temperature.  
Example DHW Programming  
Item  
MODE  
F°  
3
C°  
3
BOIL TARGET  
TARGET TANK  
DIFF TANK  
BOIL MASS  
DIFF  
140°F  
125°F  
2°F  
1
2°F  
5:00  
F°  
60°C  
52°C  
1°C  
1
1°C  
5:00  
°C  
DLY  
F°  
Step 4: See Section 6.4.11 Limit Controls.  
Set both high limits 25°F / 14°C higher than BOIL  
TARGET to allow for temperature rise across heat  
exchanger. Manual high limits on water heaters have  
a maximum 200°F / 93°C setting. (If water must be  
at 175°F / 79°C or higher with a volume water heater  
model, use mode 1. For volume water applications  
exceeding 200°F / 93°C, contact the factory.)  
Fine tuning: For faster staging, increase BOIL  
TARGET setting. Larger DIFF TANK and DIFF  
settings will slow response to demand, but may save  
energy.  
Boil Start (Boiler Start): The BOIL START  
temperature is the theoretical boiler supply  
temperature that the heating system requires when the  
outdoor air temperature equals the OUTDR START  
temperature setting.  
If unit short cycles, enter Advanced  
Programming mode (Section 6.4) and increase  
BOILER MAX setting to the BOIL TARGET setting  
or higher. Set BOILER MIN to 120°F / 49°C, and  
STGMODE to PID. See Section 6.4.12 Advanced  
Programming Mode to enter Advanced Programming  
mode, or contact the factory for assistance.  
EXAMPLE 2  
Hydronic Primary/Secondary (Mode 2)  
Figure 27. Temperature Control Target Temperature  
Graph.  
Figure 26. Temperature Control Symbol Description.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 40  
Programming. Mode 2 is used in primary-secondary  
piping hydronic systems without outdoor reset. Mode  
5 adds outdoor reset.  
Step 1: Install the additional sensor in the  
primary loop (see Figure 4), and wired to the “SC2”  
and “SUPS” terminals on the field wiring panel  
(Figure 23).  
Step 2: Remove the factory-installed jumper  
between the “HtD” and “ComD” terminals on the  
field wiring panel (Figure 14), and connect a zone  
valve or pump end switch or other contact closure  
device (aquastat, etc.) to these terminals to provide an  
indication of heat demand in the system.  
This is not recommended for other applications.  
The Copper Brute II is shipped with a jumper  
between the “Com D” and “Ht D” terminals, which  
must remain in place to allow the unit to fire. The unit  
will fire whenever the outlet temperature cools below  
the target temperature.  
Important Note: If the Copper Brute II is pump-  
mounted at the factory, or if a field-supplied pump  
contractor is connected to the Copper Brute II’s pump  
contactors  
(Pmp Pmp), the user must program the controller’s  
pump delay (DLY) setting to ON. When ON is selected,  
pump operation is continuous. The unit’s inlet and  
outlet sensors must be able to detect the temperature  
in the storage tank in order to control it. Without the  
tank water continuously running through the heater,  
the heater will have no way of knowing what the  
temperature in the tank is, and will not be able to  
respond to a change in tank temperature. Short cycling  
or lack of hot water may result if the pump does not  
run continuously.  
Note: The boiler must have an indication of heat  
demand to fire. If a zone valve or pump end switch is  
not connected to the “HtD” and “ComD” terminals, the  
jumper must be left in place. However, the boiler pump  
(if equipped) and any pump connected to a contactor  
wired to the PMP-PMP terminals on the field wiring  
panel will run continuously and not cycle off according  
to the setting for the Pump Delay. In addition, the LCD  
screen will always show “dem” (demand) and will not  
allow cycling of the display to verify all the sensor  
settings.  
Mechanical aquastat in a domestic hot  
water storage tank.  
Remove the jumper from the “Com D” and  
“HtD” terminals and connect the aquastat’s leads to  
these terminals. This connection uses a standard, non-  
powered mechanical aquastat. When the aquastat calls  
for heat, the Copper Brute II’s temperature control will  
respond and start the boiler pump (if equipped) and  
fire the boiler.  
If the Copper Brute II is not a pump mounted  
model, a 24VAC pump contactor may be connected to  
the “PMP” terminals to control a field installed pump.  
(If desired, the pump can run continuously, with the  
aquastat telling the heater when to fire.)  
Step 3: Press the three programming buttons  
to enter ADJUST mode (Figure 25). Press Item to  
select the programming item, and the ARROW keys  
to adjust the setting. See Section 6.3 Programming  
the Temperature Control if more programming  
instructions are needed.  
Recommended settings for hydronic system with  
180°F / 83°C primary loop temperature:  
Item  
F°  
2
180  
1
20  
5:00  
F°  
C°  
2
83  
1
10  
5:00  
°C  
MODE  
BOIL TARGET  
BOIL MASS  
DIFF  
DLY  
F°  
Program the temperature control to use Mode 1.  
The AUTO/MAN switch must be in the AUTO position in  
this mode.  
Mode 3: Bradford White R2014800 sensor  
installed in the domestic hot water  
storage tank.  
The Copper Brute II ships with a jumper between  
the “Com D” and “Ht D” terminals. Verify this jumper  
is in place, and connect the sensor leads to the “S C2”  
and “SUP S” terminals. When the sensor detects a  
temperature below the target temperature, the control  
will respond and start the heater pump (if equipped)  
and fire the heater.  
Step 4: See Section 6.4.11 Limit Controls. Set  
both high limit controls at least 25°F / 14°C higher  
than the BOIL TARGET to allow for temperature rise  
across the heat exchanger.  
6.3.4 Choosing the Mode for your  
Application  
This section describes various applications and  
the recommended field wiring and Mode selections.  
If the heater is not a pump mounted model, a  
24VAC pump contactor may be connected to the  
“PMP” terminals to control a field installed pump. (If  
desired, the pump can run continuously).  
Program the temperature control to use Mode 3.  
The AUTO/MAN switch must be in the AUTO position in  
this mode.  
Mode 1: Boiler operates using its own inlet  
and outlet sensors only, not relying  
on a remote thermostat, aquastat,  
or external sensor.  
This setup is most commonly found in domestic  
hot water applications with a continuous run pump.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COPPER BRUTE II (500 - 2000)  
Page 41  
If the boiler is not a pump mounted model, a  
Caution  
24VAC pump contactor may be connected to the  
“PMP” terminals to control a field installed pump.  
Program the temperature control to use Mode 4.  
The AUTO/MAN switch must be in the AUTO position in  
this mode.  
If the tank temperature control is set too high, a  
potential for hot water scalding may exist.  
Mode 2: Primary secondary piping.  
Install a “supply sensor” in the primary loop  
using the Bradford White part number R2014800  
sensor (included with every Copper Brute II unit).  
Connect the sensor to the “S C2” and “SUP S”  
terminals.  
You must provide an indication of the system’s  
heat demand by removing the jumper across the  
“ComD” and “HtD” terminals on the field wiring  
panel and connecting a zone valve or zone pump end  
switch, thermostat, aquastat or other contact closure to  
these terminals. If the “ComD” and “HtD” terminals  
are left jumpered, the control will always see a heat  
demand and remain in “Dem” mode, with the boiler  
pump running continuously. See Section 5.2 for more  
information.  
Mode 5: Primary secondary piping with  
outdoor reset.  
Install the outdoor reset sensor, Bradford White  
part number R2014000, and connect the leads to  
the “OD S” and “S C2” terminals. Install a “supply  
sensor” in the primary loop using the Bradford White  
part number R2014800 sensor (included with every  
Copper Brute II unit). Connect the sensor to the “S  
C2” and “SUP S” terminals.  
You must provide an indication of the system’s  
heat demand by removing the jumper across the  
“ComD” and “HtD” terminals on the field wiring  
panel and connecting a zone valve or zone pump end  
switch, thermostat, aquastat or other contact closure to  
these terminals. If the “ComD” and “HtD” terminals  
are left jumpered, the control will always see a heat  
demand and remain in “Dem” mode, with the boiler  
pump running continuously. See Section 5.2 for more  
information.  
A secondary aquastat, such as for a separate heat  
exchanger for DHW, can be connected to the “Set D”  
and “Com D” terminals. A call for heat from these  
controls will start the boiler pump and cause the boiler  
to fire.  
If the boiler is not a pump mounted model, a  
24VAC pump contactor may be connected to the  
“PMP” terminals to control a field installed pump.  
Program the temperature control to use Mode 2.  
The AUTO/MAN switch must be in the AUTO position in  
this mode.  
A secondary aquastat, such as for a separate heat  
exchanger for DHW, can be connected to the “Set D”  
and “Com D” terminals. A call for heat from these  
controls will start the boiler pump and cause the boiler  
to fire.  
If the boiler is not a pump mounted model, a  
24VAC pump contactor may be connected to the  
“PMP” terminals to control a field installed pump.  
Program the temperature control to use Mode 5.  
The AUTO/MAN switch must be in the AUTO position in  
this mode.  
Mode 4: Hydronic outdoor reset system  
without primary / secondary piping.  
Bradford White strongly suggests the use of  
primary secondary piping with the Copper Brute II  
boiler. This piping style best ensures that the Copper  
Brute II will have proper water flow. However, non-  
primary secondary methods can be used successfully,  
so this section has been included.  
Install the outdoor reset sensor, Bradford White  
part number R2014000, and connect the leads to the  
“OD S” and “S C2” terminals.  
You must provide an indication of the system’s  
heat demand by removing the jumper across the  
“ComD” and “HtD” terminals on the field wiring  
panel and connecting a zone valve or zone pump end  
switch, thermostat, aquastat or other contact closure to  
these terminals. If the “ComD” and “HtD” terminals  
are left jumpered, the control will always see a heat  
demand and remain in “Dem” mode, with the boiler  
pump running continuously. See Section 5.2 for more  
information.  
Reset Override: An additional thermostat or aquastat  
may be connected to the “Set D” and “Com D”  
terminals. A call for heat from either of these controls  
will start the boiler’s pump and cause the boiler to fire.  
Mode 6: Boiler with external staging control  
(multiple boiler control, building  
automation system, energy  
management system, etc.)  
Leave the jumper installed between “Ht D” and  
“Com D” terminals. There are terminals on the field  
wiring panel that must be wired per the instructions in  
Section 5.3 of this manual. Other wiring methods  
may be unsafe. The wiring in Section 5.3 of this  
manual must be used.  
The AUTO/MAN switch is located on the circuit  
board in the slide-out control panel on the front of the  
Copper Brute II. This switch is placed in the manual  
position (MAN) when an external control is controlling  
the Copper Brute II stages.  
Program the temperature control to use Mode  
6. Mode 6 tells the Copper Brute II control that an  
external staging control is being used.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 42  
Interstage Differential (STG DIFF) – The  
interstage differential is the temperature drop at which  
the next stage will turn on. Once a stage turns on, the  
next stage cannot turn on until the temperature drops  
the interstage differential below the temperature at  
which the previous stage turned on. The interstage  
differential is adjustable through the STG DIFF  
setting in the Adjust menu (see Figure 28).  
Interstage Delay On (ON DLY) – The interstage  
delay on is the amount of time that must elapse before  
turning on the next stage. Once a stage turns on, the  
next stage cannot turn on until the interstage delay  
on time elapses. The interstage delay on is adjustable  
through the ON DLY setting in the Adjust menu.  
Interstage Delay Off (OFF DLY) – The  
interstage delay off is the amount of time that must  
elapse before turning off the next stage. Once a stage  
turns off, the next stage cannot turn off until the  
interstage delay off time elapses. The interstage delay  
off is adjustable through the OFF DLY setting in the  
Adjust menu.  
Minimum On Time (MIN ON) – The minimum  
on time is the minimum amount time that a stage must  
be on before it is allowed to turn off. Once a stage  
turns on, it cannot turn off until a minimum on time  
elapses. The minimum on time is adjustable through  
the MIN ON setting in the Adjust menu.  
6.4 Advanced Topics  
For most installations, Section 6.3 provides  
all the information required to set up the Copper Brute  
II boiler, and this section should be skipped. Continue  
setup in Section 6.5.  
This section provides definitions of the pro-  
gramming parameters, advanced programming topics,  
and other information that may be of interest.  
Advanced programming mode allows the  
installer to set the temperature control for proportional  
staging. In advanced programming mode, the  
interstage differential, interstage delay, interstage on  
and off delay, and minimum time on and off are all set  
manually.  
NOTE: Advanced programming mode is not required  
in most applications, and is intended for advanced  
installers only.  
To enter advanced programming mode, remove  
the bezel on the temperature control by pulling out at  
the bottom. Remove the small phillips head screw to  
access the dip switch. The dip switch is mounted on  
a circuit board. Locate the letter “A” on the circuit  
board and slide the corresponding dip switch toward  
the letter “A”. The default setting of this dip switch is  
toward the OFF lettering on the circuit board.  
6.4.1 Differential  
Minimum Off Time (MIN OFF) – The  
Differential has an abbreviated name of DIFF. An  
on/off heat source must be operated with a differential  
in order to prevent short cycling. The differential  
is divided around the boiler target temperature (see  
Figure 28). The first stage contact will close when the  
water temperature at the operating sensor is one-half of  
the differential setting below the target temperature. It  
will open when the water temperature at the operating  
sensor is one-half of the differential setting above the  
target temperature. The remaining stages will operate  
sequentially, based on the staging mode selected.  
minimum off time is the minimum amount time that a  
stage must be off before it is allowed to turn on. Once  
a stage turns off, it cannot turn on until a minimum  
off time elapses. The minimum off time is adjustable  
through the MIN OFF setting in the Adjust menu.  
Proportional & Integral & Derivative (PID)  
– PID staging allows the control to determine when  
the next stage is required to turn on. The control  
automatically determines the settings that are manually  
selected in proportional staging mode. After each stage  
is turned on in the firing sequence, the control waits a  
6.4.2 Staging Mode  
The Copper Brute II 500 and 750 control  
operates two stages. The Copper Brute II 1000 control  
operates three stages. The Copper Brute II control for  
models 1250–2000 operates four stages. The method  
of staging used by the control is either P (proportional)  
or PID (proportional & integral & derivative), and is  
selected using the STGMODE item in the ADJUST  
menu.  
Proportional (P) – Proportional staging, also  
known as step staging, is based on manually adjusted  
settings which determine when the next stage is  
required to turn on. These manual settings are based  
on temperature and time. The interstage differential  
sets the temperature drop at which the next stage turns  
on. However, in order for a stage to fire, the interstage  
delay on and minimum off times must first elapse.  
Figure 28. Temperature Control Interstage Differential.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COPPER BRUTE II (500 - 2000)  
Page 43  
minimum amount of time before turning on the next  
stage. After the minimum time delay between stages  
has expired, the control examines the control error to  
determine when the next stage is to fire. The control  
error is determined using PID logic.  
Proportional compares the actual operating  
sensor temperature to the boiler target temperature.  
The colder the temperature, the sooner the next stage  
is turned on.  
lowest water temperature that the control is allowed  
to use as a target temperature. During mild conditions,  
if the control calculates a target temperature that is  
below this setting, the target temperature is adjusted to  
at least the minimum setting. During this condition, if  
the unit is operating, the MIN segment turns on in the  
LCD while the target temperature or operating sensor  
temperature is viewed. For Copper Brute II units, this  
must be set no lower than 120°F (49°C) to protect the  
unit  
Integral compares the actual operating sensor  
temperature to the boiler target temperature over a  
period of time.  
from condensing on the heat exchanger (see Figure 29).  
Derivative determines how fast or slow the  
operating sensor temperature is changing. If the  
temperature is increasing slowly, the next stage is  
turned on sooner. If the temperature is increasing  
quickly, the next stage is turned on later, if at all.  
Boiler Mass (BOIL MASS) – The boiler mass  
setting allows the installer to adjust the control to the  
thermal mass of different types of heat sources used.  
The boiler mass setting automatically determines the  
interstage differential, interstage delay on, interstage  
delay off, minimum on time and minimum off time of  
the stages when PID staging is used. A higher thermal  
mass setting provides slower staging, while a lower  
thermal mass setting provides faster staging. Copper  
Brute II boilers and water heaters are low-mass  
appliances, and therefore, should be used with the  
lower thermal mass setting. Set BOIL MASS to “1”.  
6.4.4 Boiler Maximum (BOIL MAX)  
The boiler maximum (BOIL MAX) is the highest  
water temperature that the control is allowed to use  
as a target temperature. If the control does target  
BOIL MAX, and the boiler outlet sensor is near the  
BOIL MAX temperature, the MAX segment turns on  
in the LCD while the target, inlet, outlet or supply  
temperature is viewed (see Figure 29).  
6.4.5 Boiler Target Temperature  
The target temperature is determined from  
the mode of operation. The control displays the  
temperature that is currently trying to maintain at the  
operating sensor as BOIL TARGET in the View menu.  
The operating sensor for modes 1, 3 and 4 is the outlet  
sensor (on the Copper Brute II). The operating sensor  
for modes 2 and 5 is the supply sensor (in the system  
or primary loop). If the control does not presently have  
a requirement for heat, it displays “- - -” in the LCD.  
There is no target temperature generated in mode 6  
(external controller mode).  
6.4.3 Boiler Minimum (BOIL MIN)  
The minimum boiler setting (BOIL MIN) is the  
6.4.6 Pump Operation  
The pump terminals (Pmp Pmp) are energized  
with 24 VAC to control a field supplied pump  
contactor. During setpoint operation (modes 1 and 2),  
the terminals are energized whenever there is a heat  
demand. During dedicated DHW operation (mode  
3), the terminals are energized whenever there is an  
internal heat demand. During outdoor reset (modes 4  
and 5), the terminals are energized whenever there is  
either a heat demand and the control is not in Warm  
Weather Shut Down (WWSD), or whenever there is  
a setpoint demand. During WWSD, if the pump has  
not operated at least once every 70 hours, the control  
energizes the terminals for 10 seconds. This minimizes  
the possibility of the pump seizing during a long  
period of inactivity. During External Boiler Operation  
(mode 6), the pump contact closes whenever there is a  
heat demand.  
Boiler Purge (PUMP DLY) – After a demand  
is satisfied, the control continues to operate the pump  
for a period of time. The length of time that the  
pump continues to run is based on the pump delay  
setting. Once the last stage of the control turns off,  
the control keeps the pump contacts energized for  
Figure 29. Temperature Control Min & Max.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 44  
the time selected (between 0 and 10 minutes). When  
OFF is selected, there is no purging. When ON is  
selected, pump operation is continuous. Also, during  
outdoor reset, with the pump delay set to ON, the pump  
continues to run even during Warm Weather Shut  
Down.  
uses outdoor reset to control the water temperature.  
Outdoor reset adjusts the target temperature based  
on the outdoor air temperature and reset ratio. The  
reset ratio is determined from the Boiler Start, Boiler  
Design, Outdoor Start and Outdoor Design settings.  
Heat Demand – For “heat demand” to exist,  
there must be continuity between the Com D (common  
demand) and the Ht D (heat demand) terminals. The  
Copper Brute II ships with a jumper between these  
terminals.  
The control also evaluates the sensor(s) installed  
in the system. If the control is not in warm weather  
shutdown (WWSD), and the sensor(s) are below the  
target temperature, the Dem segment is turned on  
in the display. The control energizes the pump (on  
pump mounted boilers) and energizes the Pmp-Pmp  
terminals, and the boiler pump segment is turned on  
in the display. The control then operates the stages to  
maintain the setpoint temperature.  
6.4.7 Setpoint Operation  
When either mode 1 or 2 is selected, the control  
controls the water temperature based on a fixed  
setpoint. The setpoint temperature is set using the  
BOIL TARGET item in the ADJUST menu.  
Heat Demand – For “heat demand” to exist,  
there must be continuity between the Com D (common  
demand) and the Ht D (heat demand) terminals. The  
Copper Brute II ships with a jumper between these  
terminals.  
The control also evaluates the sensor(s) installed  
in the system, including the outlet sensor provided on  
the boiler when using mode 1. When the control senses  
continuity between Com D and Ht D terminals, and  
that the sensor reading is below the target temperature,  
the control will activate the Dem segment in the  
display.  
Boiler Start (BOIL START) – The BOIL  
START temperature is the theoretical boiler supply  
water temperature that the heating system requires  
when the outdoor air temperature equals the OUTDR  
START temperature setting. The BOIL START is  
typically set to the desired building temperature (see  
Figure 30).  
The control energizes the pump (on pump  
mounted boilers) and energizes the Pmp Pmp  
terminals. The boiler pump segment is turned on in  
the display. The control then operates the stages to  
maintain the setpoint temperature.  
Outdoor Start (OUTDR START) – The  
OUTDR START temperature is the outdoor air  
temperature at which the control provides the BOIL  
START water temperature to the system. The OUTDR  
START is typically set to the desired building  
temperature.  
Outdoor Design (OUTDR DSGN) – The  
OUTDR DSGN is the outdoor air temperature that is  
6.4.8 Dedicated Domestic Hot Water  
When mode 3 is selected, the control provides  
dedicated domestic hot water operation.  
Internal DHW Demand – A sensor is required  
to be connected on the SC2 and Sup/S terminals.  
An internal demand for DHW is generated when the  
temperature demand for DHW sensor drops ½ of the  
tank differential setting below the desired DHW tank  
temperature. The TANK TARGET setting is used to  
set the desired DHW tank temperature.  
Once an internal demand is generated, the  
Dem segment turns on in the LCD. The control then  
closes the Pmp Pmp contact, which starts the pump  
and the control turns on the boiler pump segment in  
the display. The control then operates the stages to  
maintain the programmed boiler target temperature at  
the boiler outlet sensor.  
The boiler target temperature is set using the  
BOIL TARGET item in the Adjust menu. NOTE:  
External demand is not required in this mode of  
operation.  
Tank Differential – A differential setting that  
operates ½ above and below the TANK TARGET is  
selectable using the TANK DIFF item in the Adjust  
menu.  
6.4.9 Outdoor Reset Operation  
When either mode 4 or 5 is selected, the control  
Figure 30. Temperature Control Outdoor Start Graph.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COPPER BRUTE II (500 - 2000)  
Page 45  
the typical coldest temperature of the year where the  
building is located. This temperature is used when  
doing heat loss calculations for the building.  
Boiler Design (BOIL DSGN) – The BOIL  
DSGN temperature is the water temperature required  
to heat the boiler zones when the outdoor air is as cold  
as the OUTDR DSGN temperature.  
Warm Weather Shut Down (WWSD) – When  
the outdoor air temperature rises above the WWSD  
setting, the control turns on the WWSD segment  
in the display. When the control is in WWSD,  
the Dem segment is displayed if there is a heat  
demand. However, the control does not operate the  
heating system to satisfy this demand. The control  
does respond to a setpoint demand and operates as  
described in the Reset Override section (next).  
Reset Override (SETPOINT DEMAND) – This  
is used when override of the outdoor reset curve is  
needed, such as when an indirect water heater is served  
by the heating system. A setpoint demand is required  
whenever heat is required for the setpoint load. The  
setpoint demand overrides the reset water temperature.  
The control turns on the Setp Dem pointer in the  
display. The control energizes the pump (on pump-  
mounted boilers), energizes the Pmp-Pmp terminals,  
and turns on the boiler pump segment in the display.  
Figure 31. Typical Gas Train Configuration.  
Figure 32. Typical Control Panel.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 46  
The control then operates the boiler stages to maintain  
the programmed boiler target temperature. The reset  
override operation is not affected by WWSD.  
access the dip switch. The dip switch is mounted on a  
circuit board.  
Locate the letter “A” on the circuit board and  
slide the corresponding dip switch toward the letter  
“A”. The default setting of this dip switch is toward  
the OFF lettering on the circuit board.  
6.4.10 External Boiler Operation  
When mode 6 is selected, the control allows for  
an external control to operate the Copper Brute II’s  
stages. In this mode, the control operates the pump in  
order to provide purging and exercising. The staging  
operation is provided by an external device such as  
an Energy Management System (EMS) or External  
Staging Control.  
Heat Demand – A heat demand is generated  
when stage one is wired properly, and the external  
control closes the contacts on the stage one terminals  
(1C-1NO), calling the Copper Brute II for heat. The  
Copper Brute II is shipped with a jumper between  
the Com D and Ht D terminals, and this jumper must  
remain in place when and external control is providing  
the heat demand signal to these terminals. The control  
energizes the boiler pump (if equipped), energizes  
the Pmp-Pmp terminals, and turns on the boiler pump  
segment in the display. The control also turns on  
stage 1 of the boiler. Section 5.3 contains important  
information about external staging controls and  
building automation systems. Other wiring methods  
may be unsafe. The wiring in Section 5.3 of this  
manual must be used.  
6.5 Operating the Burner and Set Up  
6.5.1 Set Up for 0 to 2500 Feet Altitude  
The Copper Brute II appliance utilizes a modular  
design to achieve its stage-firing. The setup must be  
checked before the unit is put in operation. Problems  
such as failure to start, rough ignition, strong exhaust  
odors, etc. can be due to improper setup. Damage to  
the Copper Brute II resulting from improper setup is  
not covered by the limited warranty.  
1. Using this manual, make sure the installation  
is complete and fully in compliance with the  
instructions.  
2. Determine that the appliance and system are  
filled with water and all air has been bled from  
both. Open all valves.  
3. Observe all warnings on the Operating  
Instructions label and turn on gas and electrical  
power to appliance.  
4. Switch on the appliance power switch located on  
the right side of the unit.  
5. The Copper Brute II will enter the start sequence,  
as long as the unit is being called for heat. The  
blower and pump come on for pre-purge, then  
the ignitor warm-up sequence starts and after  
the ignitor warm-up is complete and all safety  
devices are verified, the gas valves open. If  
ignition doesn’t occur, check that there is proper  
gas supply. Wait 5 minutes and start the unit  
again. During initial start up, air in the gas line  
may cause the Copper Brute II to "lock out"  
during the first few trials for ignition. Depending  
on the ignition modules installed, the manual  
reset button on the ignition modules may need to  
be depressed to restart the Copper Brute II.  
6. When the unit is running, the supply gas pressure  
must be checked. Inlet gas pressure must not  
exceed 13" w.c. (3.2kPa). The minimum inlet gas  
pressure is 5" w.c. (1.2kPa).  
7. Once the inlet gas pressure is verified, the  
outlet gas pressure from each valve (manifold  
gas pressure) must be checked, and adjusted, if  
necessary. The manifold gas pressure must be  
2.5" w.c. (0.62kPa).  
8. Complete the setup by checking the CO2 at the  
outlet of the unit. The CO2 should be 8% for  
natural gas, or 9.2% for propane.  
6.4.11 Limit Controls  
In addition to the temperature control, Copper  
Brute II appliances are fitted with a manual reset  
high limit and an automatic reset high limit. These  
are located near the rear of the cabinet on the right  
side, behind the slide out drawer (see Figure 32).  
Both controls should be set at least 25°F higher than  
the target temperature to avoid short cycling. To set  
these controls, remove the control panel cover and  
pull the control panel out to gain access. Appliances  
with reversed heat exchangers have the limit controls  
relocated to the left side of the appliance. The left  
access door must be removed to gain access to the  
limit controls on these appliances.  
6.4.12 Advanced Programming Mode  
Advanced programming mode allows the  
installer to set the temperature control for proportional  
staging. In advanced programming mode, the  
interstage differential, interstage delay, interstage on  
and off delay, and minimum time on and off are all set  
manually.  
NOTE: Advanced programming mode is rarely  
required. It is intended for advanced installers,  
and only when the application demands such  
programming.  
9. After placing the appliance in operation, the  
Burner Safety Shutoff Device must be tested.  
To test:  
To enter advanced programming mode, remove  
the bezel on the temperature control by pulling out at  
the bottom. Remove the small phillips head screw to  
(a) Close gas shutoff valve with burner  
operating.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COPPER BRUTE II (500 - 2000)  
Page 47  
(b) The flame will go out and blower will  
continue to run for the post purge cycle.  
One additional attempt to light will follow.  
Ignition will not occur as the gas is off. The  
ignition control will lockout, and will have  
to be reset before the unit will operate.  
(c) Open gas shutoff valve. Restart the  
appliance. The ignition sequence will  
start again and the burner will start. The  
appliance will return to its previous mode  
of operation.  
pressure and replaced after the adjustments have been  
completed and the fitting, hose and manometer have  
been removed and the 1/8" plug has been replaced.  
Repeat this process until all gas valves have been set.  
Note: The pressure can be set only when the appliance  
is operating and only when the particular gas valve  
being adjusted is energized by a call for heat from the  
staging control.  
After all of the gas valve manifold pressures  
have been set, the CO2 or O2 must be reset. CO2 or O2  
will have changed when the manifold pressure was  
adjusted. Open the air shutter(s) to reduce the CO2 or  
O2 to the values achieved previously.  
The procedure is complete when all gas valves  
are adjusted to a manifold pressure of 3.0 in. w.c. (0.75  
kPa) and the CO2 is adjusted to 8.0% for Natural Gas  
appliances or 9.2% for LP appliances. When using an  
O2 analyzer, the correct O2 is 6.8% for both Natural  
Gas and LP appliances.  
NOTE: Sizes 1000–2000 have two ignition controls  
and two ignitors, which work independently of one  
another. If the ignition control for stages 1 and 2 fails  
to properly light the main burners for those stages, the  
second ignition control will still be active, and will be  
able to energize stages 3 and 4. This, of course, will  
only occur if all other safety devices confirm that the  
unit will run in a safe condition.  
Caution  
6.5.2 High Altitude Adjustment and Set Up  
Copper Brute II appliances may be operated at  
high altitude (7700 ft., 2347 m) with a reduction in  
output of approx-imately 10%. At altitudes of less  
than or more than 7700 ft. (2347 m) the appliance will  
perform equally as well, but with differing reductions  
in output. At elevations higher than 7700 ft. (2347  
m) the reduction in output will exceed 10% and at  
elevations below 7700 ft. (2347 m) it will be less than  
10%. High altitude adjustment must not be made on  
appliances operating at elevations below 2500 ft. (762  
m).  
Should any odor of gas be detected, or if the gas  
burner does not appear to be functioning in a  
normal manner, close main shutoff valve, do not  
shut off switch, and contact your heating contractor,  
gas company, or factory representative.  
6.6 Shutting Down the Copper Brute II  
1. Switch off the main electrical disconnect switch.  
2. Close all manual gas valves.  
3. If freezing is anticipated, drain the Copper Brute  
II and be sure to also protect building piping  
from freezing.  
No orifice changes are required to adjust the  
Copper Brute II appliances for high altitude. High  
altitude adjustment is accomplished by adjustment of  
the gas valve manifold pressure and the air shutter(s).  
The required instruments used to assist in these  
adjust-ments are a CO2 or O2 Analyzer and a U-Tube  
Manometer or other device capable of reading a  
pressure of 2.5-3.0 inches w.c. (0.62-0.75 kPa).  
Start the adjustment process by checking the CO2  
in the “as installed” condition. Adjust the air shutter(s)  
so that the CO2 is about 8% or the O2 is about 6.8% for  
appliances operating on Natural Gas. For appliances  
operating on LP Gas adjust the air shutter(s) so that the  
CO2 is about 9.2% or the O2 is about 6.8%. Appliances  
with two blowers should be adjusted so that the air  
shutters below each blower are open the same amount.  
Once the CO2 or O2 has been set, the manifold  
pressure may be adjusted. Remove the 1/8 NPT plug  
from the lower side of the gas valve that is to be set  
and install a fitting, hose and manometer. Start the  
appliance and observe the manifold pressure. Manifold  
pressure must be adjusted to 3.0 in. w.c. (0.75 kPa)  
(for high altitude only, standard operating pressure is  
2.5 in. w.c. (0.62 kPa)). It is adjusted by removing the  
slotted cap on the gas valve and turning the adjustment  
screw (beneath the cap) clockwise to increase  
This step to be performed by a qualified  
service person.  
6.7 To Restart the Copper Brute II  
If drained, follow Section 6.1 in this manual for  
proper filling and purging.  
1. Switch off the main electrical disconnect switch.  
2. Close all manual gas valves.  
3. WAIT FIVE (5) MINUTES.  
4. Set the aquastat or thermostat to its lowest  
setting.  
5. Open all manual gas valves.  
6. Reset all safety switches (pressure switch,  
manual reset high limit, etc.).  
7. Set the temperature controller to the desired  
temperature setting and switch on electrical  
power.  
8. Burner will go through a prepurge period and  
ignitor warm-up period, followed by ignition.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 48  
7.2.1 Burners  
SECTION 7.  
Maintenance  
Close main manual gas valve before proceeding.  
Checking the burners for debris - Remove the ignitor  
inspection panels(s) and ignitor(s) and inspect the  
burners through the ignitor hole(s) using a flashlight  
to illuminate. If there is any indication of debris on  
the burners that are visible, all the burners will need  
to be inspected more thoroughly. Remove the screws  
from around the front of the air box (large panel from  
which the ignitor inspection panel(s) were removed),  
and remove the large panel. Remove the gas manifold  
assemblies and the burner panels. Inspect the burners.  
Clean burners, if necessary, by blowing compressed  
air from the outside of the burners into the center  
of the burner. A dirty burner may be an indication  
of improper combustion or dirty combustion air.  
Determine the cause, and correct. Replace the burners  
in the reverse order  
7.1 System Maintenance  
1. Lubricate the system water-circulating pump, if  
required, per the instructions on the pump.  
2. If a strainer is employed in a pressure reducing  
valve or the piping, clean it every six months.  
3. Inspect the venting system for obstruction or  
leakage at least once a year. Periodically clean  
the screens in the vent terminal and combustion  
air terminal (when used).  
4. Keep the appliance area clear and free from  
combustible materials, gasoline, and other  
flammable vapors and liquids.  
5. If the appliance is not going to be used for  
extended periods in locations where freezing  
normally occurs, it should be isolated from the  
system and completely drained of all water. All  
systems connected to it should also be drained or  
protected from freezing.  
6. Low water cutoffs, if installed, should be  
checked every 6 months. Float type low water  
cutoff should be flushed periodically.  
7. Inspect flue passages, and clean with brushes/  
vacuums, if necessary. Sooting in flue passages  
indicates improper combustion. Determine the  
cause and correct.  
7.2.2 Filter  
The filter used in the Copper Brute II is washable  
with an 83% arrestance. Since the filter is washable,  
it will only need replacement when unwashable,  
deteriorated or damaged. If filter replacement is  
needed, it should only be replaced with a factory part.  
Inspect the air filter. If there is debris on the air filter,  
remove it from the filter box, and wash it with mild  
soap and water. Ensure that the filter is completely dry  
before re-installing, in reverse order.  
8. Inspect the vent system and air intake system,  
and if the vent system is Category III, ensure that  
all joints are sealed properly. If joints need to  
be resealed, completely remove existing sealing  
material, and clean with alcohol. Apply new  
sealing material, and re-assemble.  
7.2.3 Gas Valves  
The gas valves are designed to operate with  
supply pressures of 4-13 inches w.c. (1.0 to 3.2 kPa).  
To remove a valve, shut off 120-volt power  
and the manual gas shutoff valve. Remove the top  
front panel from the unit. Disconnect the wires to the  
valve. Disengage the flanged fitting before and after  
the valve, and remove the valve. Re-install in reverse  
order. Ensure o-rings are properly installed for both  
inlet and outlet. Turn on manual gas shutoff valve and  
120 volt power and check appliance operation and  
tightness of gas valve connections.  
7.2 Appliance Maintenance and  
Component Description  
Only genuine Bradford White replacement parts should  
be used.  
Caution  
7.2.4 Manual Reset High Limit Control  
The high limit switch is manual reset switch with  
an adjustable set point, up to 240°F (116°C) on boiler  
models and 200°F (93°C) on water heater models  
and boilers ordered with low temperature controls. To  
replace the switch, shut off the 120-volt power to the  
appliance. Remove the cover from the switch to access  
the mounting screws. Remove the screws, and pull the  
switch off the control panel. Remove the capilliary  
and bulb from the thermal well located in the header.  
Replace in reverse order.  
Label all wires prior to disconnection when servicing  
controls. Wiring errors can cause improper and  
dangerous operation. Verify proper operation after  
servicing.  
See Figures 31 and 32 for location of gas train  
and control components.  
The gas and electric controls on the appliance  
are engineered for long life and dependable operation,  
but the safety of the equipment depends on their  
proper functioning. It is strongly recommended that  
a qualified service technician inspect the basic items  
listed below every year:  
7.2.5 Automatic Reset High Limit Control  
An automatic reset high limit is used in addition  
to the manual reset high limit. The high limit switch  
has an adjustable set point, up to 240°F (116°C) on  
boiler models and 200°F (93°C) water heater models  
a. Ignition controls  
b. Ignitors  
c. Water temperature  
control  
d. Automatic gas valve  
e. Pressure switches  
f. Blowers  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COPPER BRUTE II (500 - 2000)  
Page 49  
and boilers ordered with low temperature controls. To  
replace the switch, shut off the 120-volt power to the  
appliance. Remove the cover from the switch to access  
the mounting screws. Remove the screws, and pull the  
switch off the control panel. Remove the capilliary  
and bulb from the thermal well located in the header.  
Replace in reverse order.  
7.2.10 Transformer  
The Copper Brute II’s transformer is not capable  
of supplying control voltage for external devices such  
as zone valves, which must have their own separate  
power supply. Should a transformer need replacing,  
shut off the 120-volt power. Unplug the transformer  
wires, remove the mounting screws and remove the  
transformer. Replace transformer in the reverse order.  
7.2.6 Temperature Control  
The temperature control is a Bradford White  
LHSC. To replace the control, shut off the 120-volt  
power to the appliance. Remove the cover from the  
control panel, and remove the mounting screws to  
remove the controller. Replace in reverse order.  
7.2.11 Blowers  
The combustion air blowers bring the combustion  
air for the Copper Brute II from the upper chamber to  
the lower chamber. Mixing of the gas and air occurs  
in the burners. Sizes 500, 750 and 1000 each have one  
blower, and sizes 1250 to 2000 each have two blowers  
(one blower for stages 1 and 2, and one for stages 3  
and 4). If a blower change is required, turn off the  
120-volt power and gas supply to the unit. Remove  
the front panel. Disconnect the blower's wire harness.  
Remove the screws at the blower flange, and pull the  
blower out. Replace blower in reverse order, ensuring  
that all joints are made correctly. After replacement,  
ensure that the unit operates properly, by following the  
set-up procedure in this manual.  
7.2.7 Ignition Controls  
The ignition controls ensure the proved  
interrupted-type ignition system. They control the  
hot surface ignitors and prove that the flame signal  
is appropriate for powering the gas valves. It also  
controls the blower’s pre-purge and post-purge.  
Copper Brute II sizes 500 and 750 have one ignition  
control. Sizes 1000 to 2000 have two ignition controls.  
On sizes 1000, one ignition control controls stages 1  
and 2, and the second ignition control controls stage 3.  
On sizes 1250–2000, one ignition control is for stages  
1 and 2, and the other is for stages 3 and 4.  
To replace a control, shut off the 120-volt power  
to the appliance. Remove the cover from the control  
panel. Remove the electrical connectors from the  
ignition control. Take out the controller’s mounting  
screws, and pull the controller out. Replace in reverse  
order.  
7.2.12 Flow Switch  
The Copper Brute II uses a paddle-type flow  
switch to ensure that the unit has water flow before  
ignition is allowed.  
7.2.13 Heat Exchanger Coil  
WARNING  
Black carbon soot buildup on a dirty heat exchanger  
can be ignited by a random spark or flame, thereby  
creating a risk of fire or explosion.. To prevent this  
from happening, dampen the soot deposits with a  
wet brush or fine water spray before servicing the  
heat exchanger.  
7.2.8 Ignitors  
The ignitors used are 120v “Hot Surface” type.  
They are energized whenever there is a call for heat  
and switched off when ignition is established and the  
flame has been sensed. Copper Brute II sizes 500 and  
750 have one ignitor. Sizes 1000 to 2000 have two  
ignitors. To replace the ignitor, shut off the 120-volt  
power to the appliance, remove the ignitor access  
panel, disconnect the Molex connector, remove the  
two mounting screws on the ignitor flange, and pull the  
ignitor out. Install in reverse order, always using a new  
ignitor gasket with the replacement ignitor.  
The Copper Brute II has a pre-mixed burner  
system. These systems provide the burners with  
sufficient air for complete combustion, and black  
carbon sooting is seldom experienced. If sooting  
is suspected, view ports for inspection of the heat  
exchanger are provided on both sides of the boiler.  
They are located below the headers, and are accessed  
by opening the small round cover that is attached by  
one screw. In the unlikely event that there is a buildup  
of black carbon soot or other debris on the heat  
exchanger, clean per the following:  
1. Disconnect the electrical supply to the unit.  
2. Turn off the gas supply by closing the manual gas  
valve on the heater.  
3. Disconnect and remove the wires, conduit and  
sensors from all components that are attached to  
the inlet/outlet header.  
Caution  
Ignitor gets hot.  
7.2.9 Ignition Sensors  
The ignition sensors ensure that the main flame  
is ignited, so that raw gas is not allowed to fill the  
combustion chamber. Copper Brute II sizes 500 and  
750 have one sensor. Sizes 1000 to 2000 have two  
sensors (one for each ignition control). The ignitors  
are the ignition sensors on Copper Brute II appliances.  
There are no separate ignition sensors.  
4. Isolate the heat exchanger from the water supply.  
5. Disconnect header flanges from inlet and outlet.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 50  
6. Allow the heat exchanger to drain. Remove the  
front cover(s) by removing the rubber access  
strip(s) and the retaining screws. Remove the  
venting and remove the top, by removing the  
screws that attach the top to the side panels.  
Remove the side panels. Remove the front lower  
panels sealing the combustion area. To remove  
the gas train, disconnect the unions located  
below the intermediate pan and the field installed  
union located outside the cabinet, and pull up,  
bringing the union end connectors through the  
grommets in the intermediate pan. To remove the  
intermediate pan, remove the slide out control  
assembly and blower(s) to reveal the screws.  
Remove the screws holding the intermediate pan,  
and lift up to remove it. The heat exchanger has  
integral metal sections attached, which connect  
to the frame of the boiler. Locate and remove  
the screws along the front, rear and bottom of  
the integral metal sections, and remove the heat  
exchanger and metal sections by lifting up.On the  
larger appliances, a center heat exchanger support  
must be unbolted before it can be removed.  
7. Remove the heat exchanger from the unit.  
NOTE: The heat exchangers are heavy and may  
require two people to remove to avoid personal injury.  
8. Clean the heat exchanger: A light accumulation  
of soot or corrosion on the outside of the heat  
exchanger can be easily removed. Use a wire  
brush to remove loose soot and scale from the  
heat exchanger. Do not use water or compressed  
air for cleaning.  
9. While the heat exchanger is out of the unit,  
inspect the firewall refractory insulation. Replace  
if necessary.  
10. Inspect the inside of the copper tubes for scale  
buildup. Scale can build up on the inner surface  
of the heat exchanger tubes, which can restrict  
water flow. If the tubes show signs of scaling,  
clean the internal surface. Bradford White offers  
a tube cleaning kit part number R0010000.  
11. Reassemble in the reverse order, and check  
appliance operation after start-up.  
NOTE: The Warranty does not cover damage  
caused by lack of required maintenance, lack of  
water flow, or improper operating practices.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COPPER BRUTE II (500 - 2000)  
Page 51  
SECTION 8.  
Trouble Shooting  
8.1 Resolving Lockouts  
a load distribution problem. See Section 6.3 regarding  
controller setup. Contact your Bradford White  
representative to discuss possible remedies.  
There are many causes of lockouts. The three  
most common causes are: (1) inadequate gas supply,  
(2) poor combustion, (3) ignitor failure.  
1. Inadequate gas supply: Before proceeding, ensure  
that the gas supply has not been shutoff or the LP  
tank (LP boilers) is not empty. Then, restart the  
boiler and observe the operational cycle. After  
a 15-second fan pre-purge, the ignitor will heat  
up for 20 seconds, and then the unit will light.  
If it does not, check the gas supply pressure to  
the appliance, after resetting the appliance and  
attempting another start-up. The gas pressure  
to the appliance must be above 5" w.c. (1.2kPa)  
throughout the entire start-up cycle. If it is not,  
correct the supply problem (check gas valves or  
supply piping). If the supply pressure is adequate,  
consult the factory for assistance.  
2. Poor Combustion: Poor combustion should  
be suspected if there is a strong flue gas odor.  
The odor may result from an improper gas/air  
ratio (high or low O2 or CO2). Copper Brute II  
appliances operate best with 45% excess air (8%  
CO2 on natural gas, 9.2% CO2 on LP). Check the  
CO2 of the appliance and adjust if necessary.  
3. Ignitor failure: If the boiler goes through a  
normal start cycle but combustion does not  
occur, ignitor failure should be suspected. Check  
the ignitor by unplugging the ignitor plug and  
measuring the ignitor resistance. It should be  
50-80 ohms. If the resistance is not 50-80 ohms,  
replace the ignitor. If the resistance is correct,  
reset the boiler and check for 120 VAC at the  
ignitor plug during the start cycle. If there is no  
voltage, replace the faulty ignitor wire harness or  
the ignition control.  
8.4 Short Cycling — Water Heater  
Short cycling will generally occur only in  
combination space heating and water heating  
applications when the water heater is operating in the  
space-heating mode. Because the Copper Brute II is a  
stage-fired water heater and its input will reduce when  
there is a reduction in heating load, short cycling is  
greatly reduced. If the heating load drops below the  
minimum input of the water heater for an extended  
period, the water heater will have a tendency to short  
cycle. If short cycling is frequently experienced,  
regardless of the control’s attempt to limit it, the  
heating load should be redistributed to control it. See  
Section 6.3 regarding controller setup.  
If short cycling occurs in a water heater  
application, it is probably caused by undersized  
piping between the water heater and the storage tank  
or by some other factor that restricts proper water  
flow through the water heater. The cause should be  
determined and corrected.  
8.5 High Gas Consumption  
Appliances operating with an improper air/  
fuel ratio are very inefficient and consequently, have  
very high gas consumption. Because efficiency is  
high when the CO2 is high (or O2 is low), appliances  
operating with low CO2or high O2 (especially LP  
appliances) consume more gas. Adjust the CO2 or O2  
for optimum efficiency. If no combustion analyzing  
equipment (CO2 or O2) is available then a proper  
adjustment of the air/fuel ratio (CO2 or O2) cannot be  
accomplished. However, by briefly sniffing the flue  
gases it is possible to determine if the CO2 or O2 is  
within the proper range. No significant flue gas odor  
should be detected when combustion is proper. A  
strong piercing smell indicates poor combustion and  
generally a lean mixture - low CO2 or high O2 . The  
CO2 should be 8% at high fire. To check the CO2, first  
verify that the supply gas pressure is within 5" to 13"  
w.c. (1.2 to 3.2 kPa) With the Copper Brute II running  
with all stages firing, set the air box pressure to 1.5"  
w.c. (0.37 kPa) (as a starting point), by adjusting the  
air shutter(s) at the bottom of the fan(s). Check the  
CO2, and adjust the air shutters if further adjustment  
to the CO2 is needed. Sizes 1250 to 2000 have two  
blowers and two air chambers (boxes). The pressure of  
each air box must be equal when the final adjustment  
is made.  
8.2 Delayed Ignition — Possible Causes  
A defective burner can cause a delayed ignition.  
If the gas supply pressure is proper and the gas  
valves are functioning properly, then burners should  
be inspected. There should be no distortion or  
perforations in the burners outside of the active burner  
port area. Replace if indicated.  
8.3 Short Cycling — Boiler  
Because the Copper Brute II is a stage-fired  
boiler, and its input will decrease when there is a  
reduction in heating load, short cycling is greatly  
reduced. If the heating load drops below the minimum  
input of the boiler for an extended period, the boiler  
will have a tendency to short cycle. This can be a  
symptom of improper control strategy or setpoints, or  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 52  
2, and ignition module #2 handles stage 3. The single  
blower is energized directly through the “inducer”  
terminals of either ignition module. The 24V power to  
the T’STAT terminal of both ignition modules is routed  
through the safety interlocks.  
8.6 Troubleshooting the Temperature  
Control  
See Table 12.  
8.7 Troubleshooting Copper Brute II  
The ladder diagram for sizes 1250 to 2000 is  
Controls  
The Copper Brute II series consists of two  
2-stage models (500 and 750), one 3-stage model  
(1000), and four 4-stage models (1250 to 2000). The  
2-stage models have one ignition module, and the 3-  
and 4-stage models have two ignition modules capable  
of independent operation.  
shown in Figure 18. These 4-stage models have two  
ignition modules, each with its own blower, and each  
controlling 2 stages. The blowers are energized by  
the ignition modules indirectly via switching relays.  
When either ignition module receives a call for heat, it  
switches its blower to high speed and the blower of the  
idle ignition module to low speed.  
A diagnostic panel, that includes test points, as  
well as diagnostic lights, is provided in the control  
module. It is located on the right side of the module,  
behind the display. To access, remove the retaining  
screws from the display cover panel and remove  
it. Grasp the control module at its base and pull it  
outward. Ladder diagrams are shown in Figures 16  
through 18. Voltage test points on the diagnostic  
panel are indicated by solid circles connected by short  
diagonal lines.  
Figure 16 shows the diagram for the 2-stage sizes  
500 and 750. These have one blower and one ignition  
module. The blower is energized directly through the  
“inducer” terminals F1 and F2 of the (Fenwal) ignition  
module. The 24V power to the 2nd stage gas valve is  
routed through the 1st stage VALVE terminal, so that  
stage 2 cannot fire unless the stage 1 gas valve is open.  
The 750 differs from the 500 only in that the 750 has  
two gas trains in stage 1, while the 500 has only one.  
The ladder diagram for the size 1000 is shown  
in Figure 17. Ignition module #1 handles stages 1 and  
The wiring schematics for the Copper Brute II  
500 – 1000 are shown in Figure 19, the schematics for  
the 1250–1500 are shown in Figure 20, and Figure 21  
shows the schematic for 1750–2000. All 24V wiring  
is routed through the diagnostic PC board. Wiring  
harnesses connect between the diagnostic PC board  
and the control components, indicator board, or field  
wiring terminal strip. The diagnostic board contains  
LEDs that indicate open status of the safety interlocks,  
and quick-connect terminals that provide tests points  
for checking voltage/continuity at various points in the  
control circuit. Line-voltage connections are routed via  
the line-voltage terminal buss.  
Certain control elements that may need to be  
re-wired in the field are connected via the field wiring  
terminal strip rather than to the diagnostic PC board.  
These include the low-water cutoff (LWCO), water  
flow switch, and inlet/outlet water temperature sensors.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COPPER BRUTE II (500 - 2000)  
Page 53  
Table 12. Troubleshooting Error Codes.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COPPER BRUTE II (500 - 2000)  
Page 55  
1
(
(
(
(
(1)  
C
   6
5
 2
5
C205  
C021  
C
C
C
C
C
C
C
C
C208  
4-0286  
T
T
T
T21690  
1
(
(
(
(
(1)  
C
   6
5
 2
 0
C205  
72C01  
7
   3
  0
7
C
1
5
7
17C208  
4-0286  
T
T
T
T21690  
1
(
(
(
(
(1)  
C
   6
5
 2
  2
C205  
52C01  
5
   3
  0
5
C
1
1
1
1
15C204  
4-0286  
T
T
T
T21690  
1
(
(
(
(
(1)  
C
   6
5
 2
5
C205  
C021  
C
1
1
C
C
1
1
1
C
1C208  
4-0286  
T
T
T
T21690  
(
(
(
(
(1)  
C
   6
5
 2
  2
C205  
C
1
1
C
1
1
1
C210  
4-0286  
T
T
T2710  
(
(
(
(
(1)  
7
  3
C
  1
7
  0
5
  0
5
  0
7
C205  
12C07  
4-0286  
T
T
T21630  
(
(
(
(1)  
5
  3
C
  1
5
  0
5
5
  2
5
  0
5
C205  
4-0286  
T
T21730  
,
,Front  
L
Righ,Btom  
Fornt  
,
,
,FronRight  
,
op  
,
,FronRight  
T
Aecs  
,
,Chamber  
op  
T
A
Asembly  
,
      n
       t
  a
,
Side,  
Cahmber  
,
,
,Lower  
HouSrfc,whikGaste  
,
    e
,Chamber  
Aesmbly  
,Chamber  
l
    o
       i
l
ilFo,Cnter  
S
B
   e
   r
   r
  b
C
   r
C
   e
      u
    h
B
    a
D
   r
D
  e
C
D
  r
   o
T
T
T
T
T
1
1
1
1
1
2
2
2
2
2
2
2
2
2
2
2
2
3
3
3
3
3
3
35B  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COPPER BRUTE II (500 - 2000)  
Page 57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COPPER BRUTE II (500 - 2000)  
Page 59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 60  
NOTE: Model 2000 shown  
for reference.  
13  
14  
16A  
6
7
16C  
BASE SHOWN  
FOR REFERENCE  
16  
9
5A  
12  
1
11  
5
16B  
16D  
2
3
8
4
10  
Figure 33. Sheet Metal Components.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COPPER BRUTE II (500 - 2000)  
Page 61  
See  
Electrical Components  
for detail.  
Figure 34. Internal Components.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP.  
Page 62  
See pump chart below  
for pump numbers.  
Copper Brute II Water Heater  
Copper Brute II Hydronic  
PUMP P/N  
SIZE  
500  
750  
1000  
1250  
1500  
1750  
2000  
Soft Water  
A2001700  
A2001700  
A2001700  
A2001700  
A2001700  
A2001900  
A2109700  
Normal Water  
Hard Water  
A2001900  
A2001900  
A2001900  
A2001900  
A2001900  
A2001900  
A2109700  
SIZE  
500  
750  
1000  
1250  
1500  
1750  
2000  
PUMP P/N  
A2001700  
A2001700  
A2001800  
A2001800  
A2001900  
A2001900  
A2109700  
A2001700  
A2001700  
A2001800  
A2001800  
A2001900  
A2001900  
A2109700  
Figure 35. Heat Exchanger Components.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COPPER BRUTE II (500 - 2000)  
Page 63  
Figure 36. Electrical Components.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Bradford White Corp. reserves the right to change specifications, components, features, or to discontinue products without notice.  
Ambler, PA 19002  
Tech. Service (800) 334-3393  
Service Parts (800) 538-2020  
Warranty Service (800) 531-2111  
Litho in U.S.A. © Bradford White 1211 Document 1270  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Belkin Switch 1394 User Manual
Belkin Switch F5U403 User Manual
Blue Rhino Outdoor Fireplace WAD8160L User Manual
BodyCraft Home Gym F413 User Manual
Bosch Appliances Car Amplifier PLE 2MA120 US User Manual
Broan Ventilation Hood 613004 User Manual
Califone Headphones 1218AV 03 User Manual
Carson Car Amplifier SA 500 11 14V User Manual
Chamberlain Garage Door Opener PD758S 3 4 HP User Manual
Chief Manufacturing TV Mount LVS1U LVSXU User Manual