Installation and Operation Instructions
Document 1244
Installation and Operation
Instructions for
Brute Deluxe
Hydronic Boiler
Model BMT2H
Water Heater
Model BMT2V
Sizes 200, 300, 400
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician,
qualified in hot water boiler installation and maintenance. Improper installation and/or operation could
create carbon monoxide gas in flue gases which could cause serious injury, property damage, or
death. Improper installation and/or operation will void the warranty. For indoor installations, as an
additional measure of safety, Bradford White strongly recommends installation of suitable Carbon
Monoxide detectors in the vicinity of this appliance and in any adjacent occupied spaces.
AVERTISSEMENT
Assurez-vous de bien suivres les instructions
données dans cette notice pour réduire au
minimum le risque d’incendie ou d’explosion ou
pour éviter tout dommage matériel, toute blessure
ou la mort.
WARNING
If the information in this manual is not
followed exactly, a fire or explosion may
result causing property damage, personal
injury or loss of life.
Do not store or use gasoline or other
flammable vapors and liquids in the vicinity of
this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not
use any phone in your building.
• Immediately call your gas supplier from
a nearby phone. Follow the gas supplier's
instructions.
• If you cannot reach your gas supplier, call
the fire department.
Installation and service must be performed
by a qualified installer, service agency, or gas
supplier.
Ne pas entreposer ni utiliser d’essence ni d’autres
vapeurs ou liquides inflammables dans le voisinage
de cet appareil ou de tout autre appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareils.
• Ne touchez à aucun interrupteur. Ne pas vous
servirdestéléphonesdanslebâtimentoùvous
trouvez.
• Appelez immédiatement votre fournisseur de
gaz depuis un voisin. Suivez les instructions
du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de
gaz, appelez le sservice des incendies.
L’installation et l’entretien doivent être assurés par
un installateur ou un service d’entretien qualifié ou
par le fournisseur de gaz.
238-49221-00A REV 4/11
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (200, 300, 400)
Page 3
SECTION 1.
General Information
AVERTISSEMENT
Afin de réduire au minimum les risques de
commotion électrique, de feu ou d’autre nature, qui
pourraient causer des dommages matériels, des
blessures ou des accidents mortels, les chaudières
à eau chaude ou les chauffe-eau Brute Deluxe
doivent être installés conformément aux directives
détaillées contenues dans ce manuel, à défaut de
quoi la garantie fournie par Bradford White serait
annulée. L’installation doit être conforme aux
exigences de la réglementation locale en vigueur
et, aux États-Unis, à l’édition la plus récente
du Natural Fuel Gas Code (Code pour le gaz
combustible naturel) ANSI Z223.1/NFPA54. Au
Canada, l’installation doit respecter les exigences
de la plus récente édition du Code d’installation du
gaz naturel et du propane CSA B149.1, et/ou des
codes locaux de construction en vigueur. Lorsque
la réglementation locale l’exige, l’installation des
appareils électroménagers Brute Deluxe doit
respecter les exigences du Standard for Controls
and Safety Devices for Automatically Fired Boilers
(Code pour les équipements de commande et de
sécurité des chaudières à combustion automatique),
ANSI/ASME CSD-1. Toute modification apportée à
la chaudière, aux régulateurs de gaz ou au câblage,
peut compromettre la garantie. Si certaines
USING THIS MANUAL – Because the Brute
Deluxe Boilers and Brute Deluxe Water Heaters are
identical appliances, with the exception of materials
of manufacture, labels and ultimate use application,
this manual provides information for the proper
installation, operation and maintenance of both
products. Where differences exist between the
application of the appliances and their operation,
the sections pertinent to only one appliance or the
other will be so identified.
In the Commonwealth of Massachusetts, this
appliance must be installed by a licensed plumber or
gas fitter.
WARNING
To minimize the risk of electric shock, fire or other
hazards which could result in property damage,
injury, or death. The Brute Deluxe hydronic, boiler
or water heater must be installed in accordance
with the procedures detailed in this manual, or
the Bradford White warranty may be voided. The
installation must conform to the requirements of
the local jurisdiction having authority, and, in the
United States, to the latest edition of the National
Fuel Gas Code, ANSI Z223.1/NFPA54. In Canada,
the installation must conform to the latest edition
of the Natural Gas and Propane Installation Code,
CSA B149.1 and/or applicable local codes. Where
required by the authority having jurisdiction, the
installation of Brute Deluxe appliances must
conform to the Standard for Controls and Safety
Devices for Automatically Fired Boilers, ANSI/
ASME CSD-1. Any modifications to the boiler, its
gas controls, or wiring may void the warranty. If field
conditions require modifications, consult the factory
representative before initiating such modifications.
conditions particulières rendent des adaptations
nécessaires, consulter un représentant du fabricant
avant d’entreprendre ces modifications.
All application and installation procedures
should be reviewed completely before proceeding
with the installation. Consult the Bradford White
factory, or local factory representative, with any issues
or questions regarding this equipment. Experience
has shown that most operating issues are caused by
improper installation.
The Brute Deluxe appliance is protected against
over pressurization. A pressure relief valve is fitted to
all appliances. It is installed on the outlet header, at the
water outlet of the appliance.
1.1 Introduction
This manual provides information necessary
for the installation, operation, and maintenance
of Bradford White's Brute Deluxe copper tube
appliances, sizes 200-400 MBTU/hr (larger models are
covered in a separate manual). Read it carefully before
installation.
1
2
3
T
4
2
5
6
7
8
9
10
11
12
C
13
14
1
15
16
X
17
N
B
M
SERIES
USAGE
SIZE
FUEL
ALTITUDE LOCATION
FIRING
MODE
REVISION
HEAT
EXCHANGER
OPTIONS
CODE
PUMP
OPTIONS
B
M
T
2
H
V
0
0
0
2
3
4
0
0
0
0
0
0
N
P
A (0-5000')
C
1
(indoor or
outdoor)
C
K
BMT2H: C
X
N
H (over
5000')
N
P
BMT2V: B
P
2
5
Download from Www.Somanuals.com. All Manuals Search And Download.
BraDforD White Corp.
Page 4
IMPORTANT: The inlet gas pressure to the appliance
must not exceed 13 in. w.c. (3.2 kPa).
15 Options Code
X = Standard unit
16 Pump Options
X = No Pump
All installations must be made in accordance with:
1) In the U.S., the " National Fuel Gas Code "ANSI
Z223.1/NFPA54, Latest Edition and all applicable
local codes as required by the Authorities Having
Jurisdiction (AHJ), or
2) In Canada, the "Natural Gas and Propane
Installation Code", CSA B149.1, latest edition and all
applicable local codes as required by the AHJ.
1.3 Warranty
Bradford White's Brute Deluxe appliances are
covered by a limited warranty. The owner should
fill out the warranty registration card and return it to
Bradford White.
All warranty claims must be made to an
All electrical wiring is to be done in accordance with:
1). In the U.S., the "National Electrical Code" (NEC),
ANSI/NFPA 70, latest Edition and all applicable local
codes as required by the AHJ, or
2). In Canada, the “Canadian Electrical Code - Part
1”, CSA STD. C22.1 and all applicable local codes as
required by the AHJ.
authorized Bradford White representative or directly
to the factory. Claims must include the serial number
and model (this information can be found on the rating
plate), installation date, and name of the installer.
Shipping costs are not included in the warranty
coverage.
Some accessory items are shipped in separate
packages. Verify receipt of all packages listed on
the packing slip. Inspect everything for damage
immediately upon delivery, and advise the carrier of
any shortages or damage. Any such claims should be
filed with the carrier. The carrier, not the shipper, is
responsible for shortages and damage to the shipment
whether visible or concealed.
This appliance must be electrically grounded in
accordance with the applicable codes and standards
referenced above.
1.2 Model Identification
Consult the rating plate on the unit. The
following information describes the model number
structure.
1.4 Dimensions
See Figures 1A and 1B.
Model Character Designation
1.5 Locating the Appliance
1-3 Model Series Designation
The appliance should be located to provide
clearances on all sides for maintenance and inspection.
It should not be located in an area where leakage of
any connections will result in damage to the area
adjacent to the appliance or to lower floors of the
structure.
B M T 2 = Brute Deluxe
4
Usage
H = Hydronic
V = Volume Water
5-8 Size
0 2 0 0 = 199,900 BTU/h input
When such a location is not available, it is
recommended that a suitable drain pan, adequately
drained, be installed under the appliance.
0 3 0 0 = 299,000 BTU/h input
0 4 0 0 = 399,900 BTU/h input
Fuel
9
The appliance is design certified by CSA-
N = Natural Gas
International for installation on combustible flooring;
in basements; in closets, utility rooms or alcoves.
Brute Deluxe Boilers or Water Heaters must never
be installed on carpeting. The location for the
appliance should be chosen with regard to the vent
pipe lengths and external plumbing. The unit shall be
installed such that the gas ignition system components
are protected from water (dripping, spraying, rain, etc.)
during operation and service (circulator replacement,
control replacement, etc.). When vented vertically, the
Brute Deluxe must be located as close as practical to
a chimney or outside wall. If the vent terminal and/
or combustion air terminal terminate through a wall,
and there is potential for snow accumulation in the
local area, both terminals should be installed at an
appropriate level above grade such that blockage of
the terminal from accumulated debris or precipitation
is prevented.
P = Propane
10 Altitude
A = 0-5000 feet
H = over 5000 feet
11 Location
C = Indoor and Outdoor
12 Firing Mode
C = On-Off (standard)
K = Two-stage (optional)
13 Revision
1 = Revision Level 1
14 Heat Exchanger
B = Glass-lined CI / copper / brz trim (std. BMT2V)
C = Glass-lined cast iron / copper (std. BMT2H)
N = Glass-lined cast iron / cu-nickel (BMT2H)
P = Glass-lined cast iron / cu-nickel / brz trim (BMT2V)
2 = Glass-lined cast iron / copper, brz trim, HLW
5 = Glass-lined cast iron / cu-nickel / brz, HLW
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (200, 300, 400)
Page 5
Dimensions shown in inches, cm.
Combustion Air
Connection
B*
Horizontal
(Cat III)
Vent Pipe Size
Vent Connection
C*
Size
A
in.
cm
52
67
85
in.
4
cm
10
10
15
in.
5
cm
13
15
18
in.
4
cm
10
13
15
200
300
400
20.5
26.5
33.6
4
6
5
6
7
6
*Air and vent connections may be on top or back of the Brute Deluxe, and are field convertible.
Figure 1A. Dimensional Data - Non Pump Mounted.
Download from Www.Somanuals.com. All Manuals Search And Download.
BraDforD White Corp.
Page 6
Dimensions shown in inches, cm.
Combustion Air
Connection
B*
Horizontal
(Cat III)
Vent Pipe Size
Vent Connection
C*
Size
A
in.
cm
52
67
85
in.
4
cm
10
10
15
in.
5
cm
13
15
18
in.
4
cm
10
13
15
200
300
400
20.5
26.5
33.6
4
6
5
6
7
6
*Air and vent connections may be on top or back of the Brute Deluxe, and are field convertible.
Figure 1b. Dimensional Data - Pump Mounted.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (200, 300, 400)
Page 7
Intake
Air Collar
& Pipe
Side Wall
Combustion
Air Terminal
Size
Vent Collar
Size
Horizontal
Vent Pipe
Diameter
Max. Pipe
Length
Max. No.
of Elbows
Side Vent
Terminal
Diameter
Part Number Part Number
in
5
cm
13
15
18
in
4
cm
10
13
15
in
4
cm
ft
m
200
300
400
10
10
15
50
50
50
15
15
15
3
3
3
CA003101
CA003102
CA003103
CA003201
CA003201
CA003202
6
5
4
7
6
6
Table 1. Horizontal Vent / Combustion Air Parameters.
Appliance
Surface
Required
Clearance From
Combustible Material
Recommended
Service Access
Clearance
1.8 Locating Appliance for Correct
Horizontal Vent/Ducted Air Distance
inches
cm
2.5
2.5
2.5
2.5
2.5
inches
24
cm
61
From Outside Wall
Left Side
Right Side
Top
1
1
1
1
1
The forced draft combustion air blower in the
appliance has sufficient power to pull air and vent
properly when the guidelines for horizontal air and
vent are followed (see Table 1).
24
61
12
30
Back
12**
36
30**
91
NOTE: On some models, the vent collar size is
larger than the size of the vent pipe that can be
used. Vent collar size and horizontal pipe diameters
can be found in Table 1. The larger vent collar
size is to accommodate Category I (vertical) vent
systems.
Front
Vertical
(Category 1)
Vent
6*
15.2*
Horizontal
per UL 1738 venting
NOTE: When located on the same wall, the Brute
Deluxe combustion air intake terminal must be
installed a minimum of 12" (30cm) below the
exhaust vent terminal and separated by a minimum
of 36 inches (91cm) horizontally.
(Category 3) system supplier's
Vent instructions
*1" (2.5 cm) when b-vent is used.
**When vent and/or combustion air connects to the back,
recommended clearance is 36" (91cm).
The air intake terminal must be installed high
enough to avoid blockage from snow, leaves and other
debris.
Table 2. Clearances.
The dimensions and requirements that are shown
in Table 2 should be met when choosing the locations
for the appliance.
1.6 Locating Pump-Mounted Water Heater
with Respect to Storage Tank(s)
For best results, a pump-mounted Brute Deluxe
water heater should be located within 15 feet (4.6m)
of the storage tank(s). The pump is sized for 30 feet
(9.1m) of piping.
If the appliance must be installed with longer
piping runs, then larger diameter pipe or tubing may be
acceptable. Consult the factory for assistance.
1.7 Locating Pump-Mounted Boiler with
Respect to Return/Supply Header
For the best results, a pump-mounted Brute
Deluxe boiler should be located within 15 feet (4.6m)
of the supply and return headers. The pump is sized for
30 feet (9.1m) of piping.
If the appliance must be installed with longer
piping runs, then larger diameter tubing may be
acceptable. Consult the factory for assistance.
Download from Www.Somanuals.com. All Manuals Search And Download.
BraDforD White Corp.
Page 8
Method 2: One permanent opening, commencing
within 12 inches (30 cm) of the top of the enclosure,
shall be permitted. The opening shall directly
communicate with the outdoors or shall communicate
through a vertical or horizontal duct to the outdoors
or spaces that directly communicate with the outdoors
and shall have a minimum free area of 1 square inch
per 3000 Btu/hr (7 square cm/kW) of the total input
rating of all equipment located in the enclosure. This
opening must not be less than the sum of the areas of
all vent connectors in the confined space.
Other methods of introducing combustion and
ventilation air are acceptable, providing they conform
to the requirements in the applicable codes listed
above.
In Canada, consult local building and safety
codes or, in absence of such requirements, follow
CSA B149.1, the Natural Gas and Propane Installation
Code.
SECTION 2.
Venting and Combustion Air
WARNING
For indoor installations, as an additional measure
of safety, Bradford White strongly recommends
installation of suitable Carbon Monoxide detectors
in the vicinity of this appliance and in any adjacent
occupied spaces.
AVERTISSEMENT
Pour des installations intérieures, Bradford White
recommande fortement, comme mesure de sécurité
supplémentaire, l’installation de détecteurs de
monoxyde de carbone adaptés dans le voisinage
de l’appareil et dans chacune des pièces habitées
adjacentes.
2.1 Combustion Air
Brute Deluxe boilers and water heaters must
have provisions for combustion and ventilation air in
accordance with the applicable sections addressing
requirements for air for combustion and ventilation of
the National Fuel Gas Code, ANSI Z223.1. In Canada,
the applicable sections of the Natural Gas and Propane
Installation Code (CSA B149.1) must be followed. In
all cases any and all applicable local installation codes
must also be followed.
Each Opening*
Boiler
Size
200
300
400
Square inches
Square cm
50
75
323
484
100
645
*Net Free Area in Square Inches / Square cm
Area indicated is for one of two openings; one at floor level
and one at the ceiling, so the total net free area could be
double the figures indicated.
A Brute Deluxe appliance may receive
This chart is for use when communicating directly with the
outdoors. For special conditions and alternate methods, refer
to the latest edition of ANSI Z223.1.
combustion air from the space in which it is installed,
or it can be ducted directly to the unit from the outside.
Proper ventilation air must be provided in either case.
Note: Check with louver manufacturers for net free area of
louvers. Correct for screen resistance to the net free area
if a screen is installed. Check all local codes applicable to
combustion air.
2.1.1 Combustion Air From Room
In the United States, the most common
requirements specify that the space shall communicate
with the outdoors in accordance with method 1 or 2,
which follow. Where ducts are used, they shall be of
the same cross-sectional area as the free area of the
openings to which they connect.
Table 3. Combustion Air Openings.
Method 1: Two permanent openings, one
commencing within 12 inches (30 cm) of the top
and one commencing within 12 inches (30 cm) of
the bottom, of the enclosure shall be provided. The
openings shall communicate directly, or by ducts,
with the outdoors or spaces that freely communicate
with the outdoors. When directly communicating
with the outdoors, or when communicating to the
outdoors through vertical ducts, each opening shall
have a minimum free area of 1 square inch per 4000
Btu/hr (5.5 square cm/kW) of total input rating of all
equipment in the enclosure. When communicating to
the outdoors through horizontal ducts, each opening
shall have a minimum free area of not less than
1 square inch per 2000 Btu/hr (11 square cm/kW) of
total input rating of all equipment in the enclosure.
Table 3 shows data for this sizing method.
Figure 2. Combustion Air and Vent Through Roof.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (200, 300, 400)
Page 9
vertical vent system does not satisfy the criteria for
Category I venting, it must be vented as a Category III
system.
All Brute Deluxe vent systems which discharge
horizontally (without the use of a power venter) are
considered Category III vent systems.
2.1.2 Intake Combustion Air
The combustion air can be taken through the
wall, or through the roof. When taken from the wall,
it must be taken from out-of-doors by means of the
Bradford White horizontal wall terminal (see Table 1).
When taken from the roof, a field-supplied rain cap or
an elbow arrangement must be used to prevent entry of
rain water (see Figure 2).
2.2.2 Category I Vent
When vented as a Category I appliance, the
vent system must conform to the National Fuel Gas
Code (ANSI Z223.1-Latest Edition) in the U.S., or in
Canada, to the Natural Gas and Propane Installation
Code (CSA B149.1 latest edition). The vent system
must be sized and installed for a Category I Fan-
Assisted Appliance.
If chimney height is greater than 25 feet, or
if multiple units are vented into the same vertical
vent, a barometric damper must be installed on each
appliance, such that the flue draft does not exceed
(negative) 0.1 in. w.c.
Use single-wall galvanized pipe, per Table
4, for the combustion air intake (see Table 1 for
appropriate size). Route the intake to the heater as
directly as possible. Seal all joints with tape. Provide
adequate hangers. The unit must not support the
weight of the combustion air intake pipe. Maximum
linear pipe length allowed is 50 feet (15.2m). Three
elbows have been calculated into the 50-foot (15.2m)
linear run. Subtract 10 allowable linear feet (3.0m) for
every additional elbow used (see Table 1). When fewer
than 3 elbows are used, the maximum linear pipe
length allowed is still 50 feet (15.2m).
If using a power venter for any type of Category
I venting, the draft should be set between (negative)
0.01 and 0.05 in. w.c.
Term
Pipe
Description
Single-wall galvanized steel pipe, 24 gauge
minimum (either insulated or non-insulated)
2.2.3 Common Venting Systems
Joint Sealing Permanent duct tape or aluminum tape
Brute Deluxe units are Category I fan-assisted
when vented vertically and adhering to all applicable
codes. Brute Deluxe units are not allowed to be
vented into a common horizontal vent system, unless
a properly sized vent fan is used, and the common
vent system is properly designed by the vent fan
manufacturer or a qualified engineer. When common
venting Brute Deluxe fan-assisted unit with other
appliances through one shared vertical duct called a
“common vent”, special care must be taken by the
installer to ensure safe operation. In the event that
the common vent is blocked, it is possible, especially
for fan-assisted devices, to vent backwards through
non-operating appliances sharing the vent, allowing
combustion products to infiltrate occupied spaces.
If the appliances are allowed to operate in this
condition, serious injury or death may occur.
Table 4. Required Combustion Air Piping Material.
The connection for the intake air pipe is on the
filter box. The Brute Deluxe appliances may have
venting and combustion air ducting attached to the top
or the back. They are shipped with the connections
at the top. For attaching either or both pipes to the
back, the mounting flanges are reversible by removing
the mounting screws and orienting the flanges in the
desired position. Replace the screws after positioning
flanges. Run a bead of silicone around the collar and
slide the pipe over the collar. Secure with sheet metal
screws.
In addition to air needed for combustion, air
shall also be supplied for ventilation, including all air
required for comfort and proper working conditions
for personnel. The Brute Deluxe loses less than 1
percent of its input rating to the room, but other heat
sources may be present.
WARNING
Operation of appliances with a blocked common
vent may lead to serious injury or death. Safety
devices must be implemented to prevent blocked
common vent operation. If safe operation of all
appliances connected to a common vent cannot
be assured, including prevention of spillage of flue
gasses into living spaces, common venting should
not be applied, and appliances should each be
vented separately.
2.2 Venting
2.2.1 Vent Categories
Depending upon desired Brute Deluxe venting,
it may be considered a Category I or a Category III
appliance. In general, a vertical vent system will be
a Category I system. However, in rare instances, a
Brute Deluxe’s vertical vent system may be considered
Category III. In the U.S., the National Fuel Gas Code
(ANSI Z223.1), or in Canada the Natural Gas and
Propane Installation Code (CSA B149.1), defines a
Category I vent system, and includes rules and tables
to size these vent systems. If the Brute Deluxe’s
Download from Www.Somanuals.com. All Manuals Search And Download.
BraDforD White Corp.
Page 10
as required in the venting system manufacturer’s
installation instructions. Horizontal portions of the
venting system must be supported to prevent sagging
and may not have any low sections that could trap
condensate.
The unit must not support the weight of the vent
pipe. Horizontal runs must slope downwards not less
than ¼ inch per foot (2 cm/m) from the unit to the vent
terminal.
L’appareil ne doit pas supporter le poids de la
gaine d’évent. Les parties horizontales doivent être
installées avec une pente de 2 cm/m (1/4 inch par pied)
descendant de l’appareil vers la sortie de l’évent.
Reference Table 1 for the size of the Category
III vent system. Up to three elbows can be used with
50 linear feet (15.2m) of pipe. Subtract 10 allowable
linear feet (3.0m) for every additional elbow used.
AVERTISSEMENT
Le fonctionnement d’appareils connectés à un
évent commun bouché peut provoquer de sérieuses
blessures corporelles ou la mort. Des dispositifs de
sécurité doivent être mis en place pour empêcher
que les appareils soient utilisés avec un évent
commun bouché. Si un fonctionnement sécuritaire
de tous les appareils reliés à un évent commun et si
la prévention des dégagements accidentels de gaz
de combustion dans des zones habitées ne peuvent
pas être assurés, un évent commun ne doit pas
être mis en place et les appareils doivent être munis
d’évents individuels séparés.
It is for this reason that, in addition to
following proper vent sizing, construction and safety
requirements from the National Fuel Gas Code,
ANSI Z223.1 or in Canada, from the Natural Gas
and Propane Installation Code (CSA B149.1) as
well as all applicable local codes, it is required that
installers provide some means to prevent operation
with a blocked common vent. It is suggested that a
blocked vent safety system be employed such that if
the switch from one appliance trips due to excessive
stack spill or back pressure indicating a blocked vent
condition, that all appliances attached to the vent be
locked out and prevented from operating. Note that
the Brute Deluxe is equipped with a blocked vent
safety (pressure) switch, as shipped. However, this
safety switch has only been designed and tested to
be effective in installations where the Brute Deluxe
is vented separately and NOT common vented with
other appliances. As an additional precaution, it is
recommended that a Carbon Monoxide (CO) alarm be
installed in all enclosed spaces containing combustion
appliances. If assistance is required in determining
how a blocked vent safety system should be connected
to a Bradford White product, please call Applications
Engineering at the Rochester phone number on the
back cover of this manual.
2.3 Locating Vent & Combustion Air
Terminals
2.3.1 Side Wall Vent Terminal
The appropriate Bradford White side wall vent
terminal must be used, and is listed in the installation
and operation manual. The terminal provides a means
of installing the vent piping through the building wall,
and must be located in accordance with ANSI Z223.1/
NFPA 54 and applicable local codes. In Canada, the
installation must be in accordance with CSA B149.1
and local applicable codes. Consider the following
when installing the terminal:
1. Figure 3 shows the requirements for mechanical
vent terminal clearances for the U.S. and Canada.
2. Locate the vent terminal so that vent gases cannot
be drawn into air conditioning system inlets.
3. Locate the vent terminal so that vent gases cannot
enter the building through doors, windows,
gravity inlets or other openings. Whenever
possible, locations under windows or near doors
should be avoided.
4. Locate the vent terminal so that it cannot be
blocked by snow. The installer may determine
that a vent terminal must be higher than the
minimum shown in codes, depending upon local
conditions.
5. Locate the terminal so the vent exhaust does
not settle on building surfaces or other nearby
objects. Vent products may damage such surfaces
or objects.
Refer to the installation and operating
instructions on all appliances to be common vented
for instructions, warnings, restrictions and safety
requirements. If safe operation of all appliances
connected to a common vent cannot be assured,
including prevention of spillage of flue gases into
living spaces, common venting should not be applied,
and appliances should each be vented separately.
2.2.4 Category III Vent
Term
Pipe
Description
When the Brute Deluxe is vented with horizontal
discharge, it must be installed per this installation
manual and the venting system manufacturer’s
installation instructions. The vent system must be
sealed stainless steel, per Table 5.
Route the vent pipe to the heater as directly as
possible. Seal all joints and provide adequate hangers
Must comply with UL Standard 1738 such
as Type AL29-4C Stainless Steel
(either insulated or non-insulated).
Joint
Sealing
Follow vent manufacturer's instructions.
Table 5. Required Horizontal Venting Material.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (200, 300, 400)
Page 11
U.S. Installations (see note 1)
Canadian Installations (see note 2)
A= Clearance above grade, veranda, porch,
12 inches (30 cm)
12 inches (30 cm)
deck, or balcony
B= Clearance to window or door that may
Direct Vent Only: 12 inches (30 cm)
be opened
Other Than Direct Vent: 4 feet (1.2 m) below or 36 inches (91 cm)
to side of opening; 1 foot (30 cm) above opening
C= Clearance to permanently closed window
See note 4
See note 5
D= Vertical clearance to ventilated soffit located
above the terminal within a horizontal
See note 4
See note 5
distance of 2 feet (61cm) from the center line of the terminal
E= Clearance to unventilated soffit
F= Clearance to outside corner
G= Clearance to inside corner
See note 4
See note 4
See note 4
See note 4
See note 5
See note 5
See note 5
H= Clearance to each side of center line
3 feet (91 cm) within a height 15 feet
above the meter/regulator assembly
extended above meter/regulator assembly
I= Clearance to service regulator vent outlet
See note 4
3 feet (91 cm)
J= Clearance to non mechanical air supply
inlet to building or the combustion air inlet
to any other appliance
Direct Vent Only: 12 inches (30 cm)
Other Than Direct Vent: 4 feet (1.2 m) below or 36 inches (91 cm)
to side of opening; 1 foot (30 cm) above opening
K= Clearance to a mechanical air supply inlet 3 feet (91 cm) above if within 10 feet (3 m)
6 feet (1.83 m)
horizontally
L= Clearance above paved sidewalk or paved Vent termination not allowed in this location
Vent termination not allowed in this
location
driveway located on public property
M= Clearance under veranda, porch, deck,
See note 4
12 inches (30 cm) (see note 3)
or balcony
Notes:
1. In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code.
2. In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.
3. Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
4. For clearances not specified in ANSI Z223.1 / NFPA 54, clearance is in accordance with local installation codes and the requirements of
the gas supplier.
5. For clearances not specified in CSA B149.1, clearance is in accordance with local installation codes and the requirements of the gas
supplier.
Figure 3. Vent Terminal Clearances.
Download from Www.Somanuals.com. All Manuals Search And Download.
BraDforD White Corp.
Page 12
6. If the boiler or water heater uses ducted
combustion air from an intake terminal located
on the same wall, locate the vent terminal at least
3 feet (0.9m) horizontally from the combustion
air terminal, and locate the vent terminal at least
1 foot (0.3m) above the combustion air terminal.
b. In the event that the requirements of this
subdivision cannot be met at the time of
completion of installation, the owner shall
have a period of thirty (30) days to comply
with the above requirements; provided,
however, that during said thirty (30) day
period, a battery operated carbon monoxide
detector with an alarm shall be installed.
WARNING
The outdoor vent terminal gets hot. Unit must be
installed in such a way as to reduce the risk of
burns from contact with the vent terminal.
2. APPROVED CARBON MONOXIDE
DETECTORS.
Each carbon monoxide detector as required
in accordance with the above provisions shall
comply with NFPA 720 and be ANSI/UL 2034
listed and IAS certified.
AVERTISSEMENT
La sortie d’évent à l’extérieur devient très chaude.
Elle doit être installée de façon à réduire le risque
de brûlures au contact de l’extrémité de l’évent.
3. SIGNAGE.
A metal or plastic identification plate shall be
permanently mounted to the exterior of the
building at a minimum height of eight (8) feet
above grade directly in line with the exhaust vent
terminal for the horizontally vented gas fueled
heating appliance or equipment. The sign shall
read, in print size no less than one-half (½) inch
in size, “GAS VENT DIRECTLY BELOW.
KEEP CLEAR OF ALL OBSTRUCTIONS”.
Important Note: Massachusetts Code
Requirement.
From Massachusetts Rules and Regulations 248
CMR 5.08:
(a) For all side wall horizontally vented gas
fueled equipment installed in every dwelling,
building or structure used in whole or in
part for residential purposes, including those
owned or operated by the Commonwealth and
where the side wall exhaust vent termination
is less than seven (7) feet above finished grade
in the area of the venting, including but not
limited to decks and porches, the following
requirements shall be satisfied:
4. INSPECTION.
The state or local gas inspector of the side
wall horizontally vented gas fueled equipment
shall not approve the installation unless, upon
inspection, the inspector observes carbon
monoxide detectors and signage installed in
accordance with the provisions of 248 CMR
5.08(2)(a) 1 through 4.
1. INSTALLATION OF CARBON MONOXIDE
DETECTORS.
(b) EXEMPTIONS: The following equipment is
exempt from 248 CMR 5.08(2)(a) 1 through 4:
At the time of installation of the side wall
horizontal vented gas fueled equipment, the
installing plumber or gasfitter shall observe that
a hard-wired carbon monoxide detector with
an alarm and battery back-up is installed on
the floor level where the gas equipment is to be
installed. In addition, the installing plumber or
gasfitter shall observe that a battery operated or
hard-wired carbon monoxide detector with an
alarm is installed on each additional level of the
dwelling, building or structure served by the side
wall horizontal vented gas fueled equipment.
It shall be the responsibility of the property
owner to secure the services of qualified licensed
professionals for the installation of hard-wired
carbon monoxide detectors.
1. The equipment listed in Chapter 10 entitled
“Equipment Not Required To Be Vented” in the
most current edition of NFPA 54 as adopted by
the Board; and
2. Product Approved side wall horizontal vented gas
fueled equipment installed in a room or structure
separate from the dwelling, building or structure
used in whole or in part for residential purposes.
(c) MANUFACTURER REQUIREMENTS
– GAS EQUIPMENT VENTING SYSTEM
PROVIDED. When the manufacturer of
Product Approved side wall horizontally
vented gas equipment provides a venting
system design or venting system components
with the equipment, the instructions provided
by the manufacturer for installation of the
equipment and the venting system shall
include:
a. In the event that the side wall horizontally
vented gas fueled equipment is installed
in a crawl space or an attic, the hard-wired
carbon monoxide detector with alarm and
battery back-up may be installed on the next
adjacent floor level.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (200, 300, 400)
Page 13
1. Detailed instructions for the installation of the
venting system design or the venting system
components; and
2.3.3 Vertical Vent Terminal
When the unit is vented through the roof, the
vent must extend at least 3 feet (0.9m) above the point
at which it penetrates the roof. It must extend at least
2 feet (0.6m) higher than any portion of a building
within a horizontal distance of 10 feet (3.0m), and high
enough above the roof line to prevent blockage from
snow. When the combustion air is taken from the roof,
the combustion air must terminate at least 12" (30cm)
below the vent terminal (see Figure 2).
2. A complete parts list for the venting system
design or venting system.
(d) MANUFACTURER REQUIREMENTS
– GAS EQUIPMENT VENTING SYSTEM
NOT PROVIDED. When the manufacturer
of a Product Approved side wall horizontally
vented gas fueled equipment does not
provide the parts for venting the fuel gases,
but identifies “special venting systems”, the
following requirements shall be satisfied by
the manufacturer:
2.3.4 Vertical Combustion Air Terminal
When combustion air is taken from the roof, a
field-supplied rain cap or an elbow arrangement must
be used to prevent entry of rain water (see Figure 2).
The opening on the end of the terminal must be at least
12" (30cm) above the point at which it penetrates the
roof, and high enough above the roof line to prevent
blockage from snow. When the vent terminates on the
roof, the combustion air must terminate at least 12"
(30cm) below the vent terminal.
1. The referenced “special venting system”
instructions shall be included with the appliance
or equipment installation instructions; and
2. The “special venting systems” shall be Product
Approved by the Board, and the instructions for
that system shall include a parts list and detailed
installation instructions.
2.4 Common Vent Test — Boilers
When an existing boiler is removed from a
common venting system, the common venting system
is likely to be too large for proper venting of the
appliances remaining connected to it.
At the time of removal of an existing boiler, the
following steps shall be followed with each appliance
remaining connected to the common venting system
placed in operation, while the other appliances
remaining connected to the common venting system
are not in operation.
(e) A copy of all installation instructions for all
Product Approved side wall horizontally
vented gas fueled equipment, all venting
instructions, all parts lists for venting
instructions, and/or all venting design
instructions shall remain with the appliance
or equipment at the completion of the
installation.
1. Seal any unused openings in the common venting
system.
2. Visually inspect the venting system for proper
size and horizontal pitch and determine there is
non blockage or restriction, leakage, corrosion
and other deficiencies which could cause an
unsafe condition.
3. Insofar as it is practical, close all building doors
and windows and all doors between the space in
which the appliances remaining connected to the
common venting system are located and other
spaces of the building. Turn on clothes dryers
and any appliance not connected to the common
venting system. Turn on any exhaust fans, such
as range hoods and bathroom exhausts, so they
will operate at maximum speed. Do not operate a
summer exhaust fan. Close fireplace dampers.
4. Place in operation the appliance being
inspected. Follow the lighting instructions.
Adjust thermostat so appliance will operate
continuously.
2.3.2 Side Wall Combustion Air Terminal
The Bradford White side wall combustion air
terminal (listed in Table 1) must be used when the
unit takes its combustion air through a duct from a
side wall. Consider the following when installing the
terminal:
1. Do not locate the air inlet terminal near a source
of corrosive chemical fumes (e.g., cleaning fluid,
chlorinated compounds, etc.)
2. Locate the terminal so that it will not be subject
to damage by accident or vandalism.
3. Locate the combustion air terminal so that it
cannot be blocked by snow. The National Fuel
Gas Code requires that it be at least 12 inches (30
cm) above grade, but the installer may determine
it should be higher, depending upon local
conditions.
4. If the Brute Deluxe is side-wall vented to the
same wall, locate the vent terminal at least 3
feet (0.9m) horizontally from the combustion air
terminal, and locate the vent terminal at least 1
foot (0.3m) above the combustion air terminal
(see Figure 3).
5. Test for spillage at the draft hood relief opening
after 5 minutes of main burner operation. Use
the flame of a match or candle, or smoke from a
cigarette, cigar or pipe.
6. After it has been determined that each appliance
Download from Www.Somanuals.com. All Manuals Search And Download.
BraDforD White Corp.
Page 14
remaining connected to the common venting
fumée d'une cigarette, d'un cigare ou d'une pipe.
6. Une fois qu'il a été déterminé, selon la méthode
indiquée ci-dessus, que chaque appareil
raccordé au système d'évacuation est mis à l'air
libre de façon adéquate. Remettre les portes
et les fenêtres, les ventilateurs, les registres de
cheminées et les appareils au gaz à leur position
originale.
7. Tout mauvais fonctionnement du système
d'évacuation commun devrait être corrigé
de façon que l'installation soit conforme au
National Fuel Gas Code, ANSI Z223.1/NFPA
54 et (ou) aux codes d'installation CSA-B149.1.
Si la grosseur d'une section du système devrait
être modifié, le système devrait être modifié pour
respecter les valeurs minimales des tableaux
pertinents de l'appendice F du National Fuel Gas
Code, ANSI Z223.1/NFPA 54 et (ou) les codes
d'installation CSA-B149.1
system properly vents when tested as outlined
above, return doors, windows, exhaust fans,
fireplace dampers and any other gas burning
appliance to their previous conditions of use.
7. Any improper operation of the common venting
system should be corrected so that the installation
conforms with the National Fuel Gas Code,
ANSI Z223.1/NFPA 54 and/or CSA B149.1,
Natural Gas and Propane Installation Codes.
When resizing any portion of the common
venting system, the common venting system
should be resized to approach the minimum size
as determined using the appropriate tables in
Appendix F in the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 and/or CSA B149.1, Natural
Gas and Propane Installation Codes.
2.4 Vérification des évents communs
2.5 Vent Terminals for Outdoor Units
For outdoor applications, the vent and
combustion air openings must be covered with proper
terminals to prevent rain, snow and other objects from
falling into the Brute Deluxe.
— Chaudières
Lorsqu’une chaudière existante est déconnectée
du réseau d’évents commun, ce réseau d’évents
commun devient probablement trop grand pour
les appareils qui lui restent connectés. Lorsqu’une
chaudière existante est retirée, les étapes suivantes
doivent être accomplies pour chaque appareil qui
reste connecté au réseau d’évents commun utilisé,
alors que les autres appareils qui sont encore
connectés au réseau commun d’évents ne sont pas en
fonctionnement.:
Outdoor Vent / Air kit part numbers are shown in
Table 6. These kits contain parts for both combustion
air inlet and exhaust vent connections. An angled sheet
metal assembly with louvers replaces the sheet metal
assembly with the air collar. An adapter, a 12" length
of pipe, and a rain cap are included for the exhaust
vent opening.
If local codes allow, Bradford White kits are
not required for outdoor units. The installer may use
12" of appropriately sized galvanized single wall or
b-type vent pipe and a rain cap for the exhaust vent. In
addition, an appropriately sized galvanized 90° elbow,
positioned with the opening facing down, may be used
on the combustion air inlet.
1. Sceller toutes les ouvertures non utilisées du
système d'évacuation.
2. Inspecter de façon visuelle le système
d'évacuation pour déterminer la grosseur et
l'inclinaison horizontale qui conviennent et
s'assurer que le système est exempt d'obstruction,
d'étranglement, de fuite, de corrosion et autres
défaillances qui pourraient présenter des risques.
3. Dans la mesure du possible, fermer toutes les
portes et les fenêtres du bâtiment et toutes les
portes entre l'espace où les appareils toujours
raccordés au système d'évacuation sont installés
et les autres espaces du bâtiment. Mettre en
marche les sécheuses, tous les appareils non
raccordés au système d'évacuation common
et tous les ventilateurs d'extraction comme
les hottes de cuisinière et les ventilateurs des
salles de bain. S'assurer que ces ventilateurs
fonctionnent à la vitesse maximale. Ne pas faire
fonctionner les ventilateurs d'été. Fermer les
registres des cheminées.
Outdoor Vent and
Size
Air Terminal Kit
200
300
400
CA003001
CA003002
CA003003
Table 6. Vent / Air Kits for Outdoor Units.
4. Mettre l'appareil inspecté en marche. Suivre les
instructions d'allumage. Réegler le thermostat de
façon continue.
5. Faire fonctionner le brûleur principal pendant
5 min ensuite, déterminer si le coupe-tirage
déborde à l'ouverture de décharge. Utiliser la
flamme d'une allumette ou d'une chandelle ou la
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (200, 300, 400)
Page 15
8. The appliance and its individual shutoff valve
SECTION 3.
Gas Supply and Piping
must be disconnected from the gas supply piping
during any pressure testing of that system at test
pressures in excess of 0.5 psig (3.45 kpa).
9. The unit must be isolated from the gas supply
system by closing its individual manual shutoff
valve during any pressure testing of the gas
supply piping system at test pressures equal to or
less than 0.5 psig (3.45 kpa).
3.1 Gas Supply and Piping
Gas piping should be supported by suitable
hangers or floor stands, not by the appliance.
The Brute Deluxe’s gas train allows the user to
pipe the gas from either the right side or the left side
of the unit. As shipped, the right side of the gas train is
capped off, and there is a manual valve on the left side.
If desired, the manual valve on the left side of the gas
train may be moved to the right side, and the cap on
the right side may be moved to the left.
10. The appliance and its gas connection must be
leak tested before placing it in operation.
11. Purge all air from gas lines.
WARNING
Do not use open flame to check for leaks. An open
flame could lead to explosion, which could result in
property damage, serious injury or death.
Review the following instructions before
proceeding with the installation.
1. Verify that the appliance is fitted for the proper
type of gas by checking the rating plate. Brute
Deluxe appliances are equipped to operate at
elevations up to 10,000 feet (3050m). Brute
Deluxe appliances may be adjusted to operate
properly at altitudes above 2500 feet (see Section
6.5.2) and the input will be reduced if the heating
value of the gas supply is below sea level values.
2. The maximum inlet gas pressure must not
exceed 13" w.c. (3.2kPa). The minimum inlet gas
pressure is 5 in. w.c. (1.2 kPa).
3. Refer to Table 7, size supply.
4. Run gas supply line in accordance with all
applicable codes.
5. Locate and install manual shutoff valves in
accordance with state and local requirements.
6. A sediment trap must be provided upstream of
the gas controls.
AVERTISSEMENT
Ne recherchez pas les fuites avec une flamme nue.
Une flamme nue peut provoquer une explosion qui
peut causer des dommages matériels, de sérieuses
blessures corporelles ou la mort.
NOTE: The Brute Deluxe appliance and all other
gas appliances sharing the gas supply line must
be firing at maximum capacity to properly measure
the inlet supply pressure. The pressure can be
measured at the supply pressure port on the gas
valve. Low gas pressure could be an indication of
an undersized gas meter, undersized gas supply
lines and/or an obstructed gas supply line.
7. All threaded joints should be coated with
piping compound resistant to action of liquefied
petroleum gas.
Distance from Gas Meter or Last Stage Regulator
Size and
Gas Type
0-31 m
3.2 cm
2.5 cm
3.2 cm
2.5 cm
3.2 cm
3.2 cm
100-200'
1¼"
1"
31-61m
3.2 cm
2.5 cm
4.0 cm
3.2 cm
4.0 cm
3.2 cm
200-300'
1¼"
1¼"
1½"
1¼"
2"
61-91m
3.2 cm
3.2 cm
4.0 cm
3.2 cm
5.0 cm
4.0 cm
0-100'
1¼"
1"
200 natural
200 propane
300 natural
300 propane
400 natural
400 propane
Notes:
1¼"
1
1½"
1¼"
1½"
1¼"
1¼"
1¼"
1½"
1. These figures are based on 1/2" (0.12 kPa) water column pressure drop.
2. Check supply pressure and local code requirements before proceeding with work.
3. Pipe fittings must be considered when determining gas pipe sizing.
Table 7. Gas Piping Size.
Download from Www.Somanuals.com. All Manuals Search And Download.
BraDforD White Corp.
Page 16
4A.3 Water Flow Requirements — Boiler
A hydronic heating (closed loop) application
recirculates the same fluid in the piping system. As a
result, no new minerals or oxygen are introduced into
the system. To ensure a proper operating temperature
leading to long boiler life, a flow rate has been
established based on the fluid temperature rise for this
specific size boiler.
Pump-mounted boilers can be ordered for use in
primary secondary piping systems. The pumps used
are sized for the head loss through the heater, plus 30
feet (9.1 m) of full-sized piping (same size as boiler
outlet) and a normal number of fittings.
Table 8 specifies water flow rates for boilers,
which will enable the user to size a pump. The head
loss shown is for the heater only, and the user will
need to add the head loss of the system piping to
properly size the pump.
The minimum inlet water temperature for the
Brute Deluxe is 120°F (49°C) to avoid condensing on
the copper coils.
SECTION 4A.
Water Connections —
Brute Deluxe Boiler
4A.1 Heating System Piping:
Hot Supply Connections — Boiler
NOTE: This appliance must be installed in a closed
pressure system with a minimum of 12 psig (82.7
kPa) static pressure at the boiler.
Hot water piping should be supported by suitable
hangers or floor stands. Do not support piping with
this appliance. Due to expansion and contraction of
copper pipe, consideration should be given to the type
of hangers used. Rigid hangers may transmit noise
through the system resulting from the piping sliding in
the hangers. It is recommended that padding be used
when rigid hangers are installed. Maintain 1" clearance
to combustibles for hot water pipes.
Pipe the discharge of the relief valve (full size)
to a drain or in a manner to prevent injury in the event
of pressure relief. Install an air purger, an air vent,
a diaphragm-type expansion tank, and a hydronic
flow check in the system supply loop. Minimum fill
pressure must be 12 psig (82.7 kPa). Install shutoff
valves where required by code.
4A.4 Freeze Protection — Boiler
Boiler installations are not recommended in
areas where the danger of freezing exists unless proper
precautions are made for freeze protection. A non
toxic, heating system, anti-freeze may be added to
the hydronic system provided that the concentration
does not exceed 50% and the anti freeze contains an
anti foamant. When a 50/50 mixture is used, increase
the water flow requirements by 15%, and increase the
head loss requirements by 20%.
Suggested piping diagrams are shown in Figures
4, 5, 6, 7 and 8. These diagrams are meant only as a
guide. Components required by local codes must be
properly installed.
4A.2 Cold Water Make-Up — Boiler
1. Connect the cold water supply to the inlet
connection of an automatic fill valve.
Power outage, interruption of gas supply, failure
of system components, activation of safety devices,
etc., may prevent a boiler from firing. Any time a
boiler is subjected to freezing conditions, and the
boiler is not able to fire, and/or the water is not able
to circulate, there is a risk of freezing in the boiler
or in the pipes in the system. When water freezes,
it expands. This can result in bursting of pipes in the
system, or damage to the boiler, which could result in
leaking or flooding conditions.
IMPORTANT NOTES: Different glycol products
may provide varying degrees of protection. Glycol
products must be maintained properly in a heating
system, or they may become ineffective. Consult
the glycol specifications, or the glycol manufacturer,
for information about specific products,
2. Install a suitable back flow preventer between the
automatic fill valve and the cold water supply.
3. Install shut off valves where required.
NOTE: The boiler, when used in connection with a
refrigeration system, must be installed so the chilled
medium is piped in parallel with the boiler with
appropriate valves to prevent the chilled medium
from entering the boiler.
The boiler piping system of a hot water heating
boiler connected to heating coils located in air
handling appliances where they may be exposed to
refrigerated air circulation must be equipped with flow
control valves or other automatic means to prevent
gravity circulation of the boiler water during the
cooling cycle.
A boiler installed above radiation level, or as
required by the authority having jurisdiction, must be
provided with a low water cutoff device either as a part
of the boiler or at the time of boiler installation.
maintenance of solutions, and set up according to
your particular conditions. Never use ethylene glycol
(automotive antifreeze).
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (200, 300, 400)
Page 17
20°F
25°F
30°F
35°F
Size
flow H/L flow H/L flow H/L flow H/L
gpm feet gpm feet gpm feet gpm feet
200
300
400
17
26
34
1.6
3.5
6.3
14
20
27
1.0
2.3
4.0
11
17
23
0.7
1.6
2.8
10
15
19
0.5
1.2
2.1
Metric Equivalent
11°C
Size
14°C
17°C
19°C
flow H/L flow H/L flow H/L flow H/L
lpm
m
lpm
m
lpm
m
lpm
m
200
300
400
64
0.5
1.1
51
0.3
0.7
43
0.2
0.5
0.9
37 0.2
55 0.4
74 0.6
97
77
64
129 1.9 103 1.2
86
Notes: gpm = gallons per minute, lpm = liters per minute,
H/L = head loss, ft = head loss in feet,
m = head loss in meters.
Maximum temperature rise is 35°F (19°C), as shown.
Head loss is for boiler’s heat exchanger only.
N/R = not recommended.
Table 8. Water Flow Requirements - BMT2H.
Figure 4. Hydronic Piping — Multiple Boilers, Primary Secondary System.
Download from Www.Somanuals.com. All Manuals Search And Download.
BraDforD White Corp.
Page 18
Figure 5. Hydronic Piping — Multiple Boilers, Low Temperature System.
Figure 6. Hydronic Piping — One Boiler, Multi-Temperature System.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (200, 300, 400)
Page 19
Figure 7. Hydronic Piping — Primary-Secondary, Reverse-Return.
Figure 8. Hydronic Piping — Primary-Secondary, Reverse-Return, Low Temperature.
Download from Www.Somanuals.com. All Manuals Search And Download.
BraDforD White Corp.
Page 20
must be installed in the separate storage tank
system.
SECTION 4B.
Water Connections —
Brute Deluxe Water Heater
If the Brute Deluxe water heater is installed in
a closed water supply system, such as one having a
backflow preventer in the cold water supply line, the
relief valve may discharge periodically, due to thermal
expansion. Means (such as a properly-sized expansion
tank) shall be provided to control thermal expansion.
Contact the water supplier or local plumbing inspector
on how to control this situation.
4B.1 Water System Piping —
Water Heater
Hot water piping should be supported by suitable
hangers or floor stands. Do not support piping with
this appliance. Due to expansion and contraction of
copper pipe, consideration should be given to the type
of hangers used. Rigid hangers may transmit noise
through the system resulting from the piping sliding in
the hangers. It is recommended that padding be used
when rigid hangers are installed.
4B.3 Water Flow Requirements —
Water Heater
In a water heating application (an open system),
new water is constantly being introduced. With the
new water comes a fresh supply of minerals that can
be deposited on the unit’s heat exchanger. This is
commonly known as scaling. The amount of minerals
will depend upon the hardness of the water. Water can
also be aggressive, and can erode metals, including
copper, if the water is moved too quickly. The water
flow requirements for the Brute Deluxe water heater
are based upon the hardness of the water. The water
flow is kept high enough to prevent scaling, but low
enough to prevent tube erosion. For extremely soft or
hard water, cupro-nickel tubes are available. Contact a
Bradford White representative if you have questions or
concerns about water quality.
The Brute Deluxe can be used with several
different types of readily available storage tanks. A
pump draws water from the storage tank and pumps
the water through the heater and back into the tank.
Pump-mounted units have a circulating pump built
into the water heater. The pumps used are sized for
the head loss through the heater, plus 30 feet (9.1 m)
of full-sized piping (same size as boiler outlet) and
a normal number of fittings. Pumps used on pump-
mounted unit are sized for soft/normal or hard water,
so make sure a pump-mounted unit matches the water
quality of the installation.
Pipe the outlet from the heater’s relief valve
such that any discharge from the relief valve will be
conducted to a suitable place for disposal when relief
occurs. Do not reduce line size or install any valves in
this line. The line must be installed to allow complete
drainage of both the valve and the line.
Pump-mounted water heaters can be ordered
with standard pumps for soft or normal water or with
pumps for hard water. The pumps used are sized for
the head loss through the heater, plus 30 feet (9.1m)
of full-sized piping (same size as heater outlet) and a
normal number of fittings.
Suggested piping diagrams are shown in Figures
9, 10, 11 and 12. These diagrams are meant only as a
guide. Components required by local codes must be
properly installed.
Table 9 specifies water flow rates for water
heaters, which will enable the user to size a pump. The
head loss shown is for the heater only, and the user
will need to add the head loss of the piping system to
properly size the pump.
Note the recommended location of the
temperature sensor on the diagrams. The Brute Deluxe
is shipped with an additional sensor that can be used
for more full-featured domestic water heating control.
To get these features, you must provide a location for
the additional sensor. It can be strapped to a pipe from
1" to 4" diameter, or inserted into a tank immersion
well.
4B.4 Combined Water Heating (potable)
and Space Heating — Water Heater
NOTE: These systems are not allowed in the
Commonwealth of Massachusetts.
The minimum inlet water temperature for the
Brute Deluxe is 120°F (49°C) to avoid condensing on
the copper coils.
Piping and components connected to this water
heater for the space heating application shall be
suitable for use with potable water.
Toxic chemicals, such as used for boiler
treatment, shall not be introduced into the potable
water used for space heating.
This water heater when used to supply potable
water shall not be connected to any heating system
or component(s) previously used with a non-potable
water heating appliance.
When the system requires water for heating at
temperatures higher than required for other uses,
an anti-scald mixing or tempering valve shall be
4B.2 Hot Water Supply Piping —
Water Heater
Follow the tank manufacturer’s guidelines for
completion of the hot water system connections.
NOTE: A listed temperature and pressure relief
valve listed as complying with the Standard
for Relief Valves and Automatic Gas Shutoff
Devices for Hot Water Supply Systems (ANSI
Z21.22/CSA 4.4), of suitable discharge capacity
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (200, 300, 400)
Page 21
installed to temper the water for those uses in order
to reduce scald hazard potential.
heater is subjected to freezing conditions, and the
heater is not able to fire, and/or the water is not
able to circulate, there is a risk of freezing in the
heater or in the pipes in the system. When water
freezes, it expands. This can result in bursting of pipes
in the system, or damage to the heater, which could
result in leaking or flooding conditions.
4B.5 Freeze Protection — Water Heater
Although Brute Deluxe water heaters are design-
certified for outdoor installations, such installations
are not recommended in areas subject to freezing
temperatures, unless proper precautions are taken.
Power outage, interruption of gas supply, failure
of system components, activation of safety devices,
etc., may prevent a heater from firing. Any time a
Contact the local factory representative or
Bradford White for additional information.
gpm
N
ft
Temp Rise °F
lpm
N
m
N
Temp. Rise °C
Size
S
H
S
N
H
S
N
H
S
H
S
H
S
N
6
H
200
300
23
23
23
35
45
45
45
1.9
2.0
2.0
4.4
4.5
4.5
7.3
7.4
7.4
15
22
30
10
15
19
8
87
87
87
132
132
132
170
170
170
0.6
0.6
0.6
1.3
1.4
1.4
2.2
2.3
2.3
8
4
6
8
35
11
15
12
17
8
400
35
11
Notes:
1. S = soft water (1 to 7.5 grains hardness)
2. N = normal water (7.6 to 17 grains hardness)
3. H = hard water (more than 17 grains hardness)
4. gpm = gallons per minute, lpm = liters per minute, ft = head loss in feet, m = head loss in meters
5. Head loss is for heater's heat exchanger only
Table 9. Water Flow Requirements - BMT2V.
Download from Www.Somanuals.com. All Manuals Search And Download.
BraDforD White Corp.
Page 22
Figure 9. Water Heater Piping — One Heater, One Tank.
Figure 10. Water Heater Piping — Multiple Heaters, One Tank.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (200, 300, 400)
Page 23
Figure 11. Water Heater Piping — One Heater, Multiple Tanks.
Figure 12. Water Heater Piping — Multiple Heaters, Multiple Tanks.
Download from Www.Somanuals.com. All Manuals Search And Download.
BraDforD White Corp.
Page 24
SECTION 5.
Electrical Connections
Single pole switches, including those of safety
controls and protective devices must not be wired in a
grounded line.
WARNING
The appliance must be electrically grounded in
accordance with the requirements of the authority
having jurisdiction or, in the absence of such
requirements, with the latest edition of the National
Electrical Code, ANSI/NFPA 70, in the U.S. and
with latest edition of CSA C22.1 Canadian Electrical
Code, Part 1, in Canada. Do not rely on the gas
or water piping to ground the metal parts of the
boiler. Plastic pipe or dielectric unions may isolate
the boiler electrically. Service and maintenance
personnel, who work on or around the boiler, may
be standing on wet floors and could be electrocuted
by an ungrounded boiler.
NOTE: All internal electrical components have been pre-
wired. No attempt should be made to connect electrical
wires to any other location except the wiring box.
5.1 Main Power
Connect a 15 amp. fused, 120-volt supply to
the main power switch. Both hot and neutral wires
are provided for connections inside the boiler jacket.
Ground wire can be connected to the grounding screw
in the box.
Wiring diagrams are shown in Figures 15-18.
AVERTISSEMENT
L’appareil doit être relié à la terre conformément
aux exigences de la réglementation locale ou,
en l’absence d’une telle réglementation, à la plus
récente édition du National Electrical Code (Code
national de l’électricité) ANSI/NFPA 70 aux États-
Unis, et à la plus récente édition du Code Canadien
de l’électricité 1ère partie (Canadian Electrical
Code Part 1) CSA C22.1, au Canada. N’utilisez
pas les tuyauteries d’eau ou de gaz pour mettre
à la terre les pièces métalliques de la chaudière;
des tuyauteries en plastique ou des raccords
union diélectriques peuvent isoler électriquement
la chaudière. Les employés qui sont appelés à
travailler sur la chaudière ou autour peuvent être
électrocutés par une chaudière qui n’est pas mise à
la terre.
Figure 13. Terminal Block.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (200, 300, 400)
Page 25
To connect the pump, crimp the two spade
5.2 Field Wiring
connectors to the black (hot) and white (neutral) pump
wires (as shown in pump diagram, Figure 14). The
other end of the pump wired needs to be connected
to the boiler's 110V legs using the existing wire nuts
(located in the transformer cover box). Also note
the transformer cover box is removed by lifting the
retaining tab (on the left side of the box) up and out of
the retaining slot, and sliding the box to the left until it
stops, before raising it straight up.
Other Field Interlocks: To install other field-
wired switches (proving switches, flow switches, etc.),
remove the jumper between the terminals labeled “3”
and “4” (see Figure 13)
Field Installed Pump: A pump contactor can be
wired to the “2” and “4” terminals on the pump time
delay relay, attached to dry contacts of an adjustable
delay. The contacts may be used to switch a larger
pump contactor or can be used to directly switch the
hot leg of a circulator pump, up to 1 hp at 120 VAC or
3/4 hp at 240 VAC.
Note that in some cases, the pump is run
continuously by switching the pump status switch
position to "constant".
Note terminals “2” and “4” are located on the
time delay relay, which is mounted to the bottom of
the control panel tray and accessed when the tray is
swiveled to the "up" position.
Figure 14. Field Wiring.
Download from Www.Somanuals.com. All Manuals Search And Download.
BraDforD White Corp.
Page 26
Figure 15. Wiring Diagram, ON/OFF Boiler or Water Heater.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (200, 300, 400)
Page 27
Figure 16. Wiring Diagram, 2-STAGE Boiler or Water Heater.
Download from Www.Somanuals.com. All Manuals Search And Download.
BraDforD White Corp.
Page 28
Figure 17. Logic Diagram, ON/OFF Boiler or Water
Heater.
Figure 18. Logic Diagram, 2-STAGE Boiler or Water
Heater.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (200, 300, 400)
Page 29
First, shut off the manual gas valve, and call
the unit for heat. After the pre-purge and ignitor
heat-up time, the main gas terminals will be
energized, attempting to light, for seven (7)
seconds, and then will de-energize. The unit will
attempt to light two more times, and then will go
into lockout mode. Second, turn the power off
and then on again, open the manual gas valve
and allow the unit to light. While the unit is
operating, close the manual gas valve and ensure
that power to the main gas valve has been cut.
16. Within three (3) days of start-up, recheck all air
bleeders and the expansion tank as described in
Steps 4 and 8 above.
SECTION 6.
Operating Instructions
6.1 Filling the Boiler System
1. Ensure the system is fully connected. Close all
bleeding devices and open make-up water valve.
Allow system to fill slowly.
2. If make-up water pump is employed, adjust
pressure switch on pumping system to provide
a minimum of 12 psi (81.8 kPa) at the highest
point in the heating loop.
3. If a water pressure regulator is provided on the
make-up water line, adjust the pressure regulator
to provide at least 12 psi (81.8 kPa) at the highest
point in the heating loop.
Important: The installer is responsible for identifying
to the owner/operator the location of all emergency
shutoff devices.
4. Open bleeding devices on all radiation units
at the high points in the piping throughout
the system, unless automatic air bleeders are
provided at such points.
5. Run system circulating pump for a minimum of
30 minutes with the boiler shut off.
6. Open all strainers in the circulating system,
check flow switch operation, and check for
debris. If debris is present, clean out to ensure
proper circulation.
WARNING
Do not use this appliance if any part has been
under water. Immediately call a qualified service
technician to inspect the appliance and to replace
any part of the control system and any gas control
that may have been under water.
AVERTISSEMENT
N’utilisez pas cet appareil si l’une de ses pièces est
passée sous l’eau. Appelez tout de suite un technicien
en entretien et en réparation pour inspection de
l’appareil et remplacement des pièces du système de
commande, et des pièces de commande du circuit
gaz, qui sont passées sous l’eau.
7. Recheck all air bleeders as described in Step 4.
8. Check liquid level in expansion tank. With the
system full of water and under normal operating
pressure, the level of water in the expansion tank
should not exceed ¼ of the total, with the balance
filled with air.
9. Start up boiler according to the procedure in this
manual. Operate the entire system, including the
pump, boiler, and radiation units for one (1) hour.
10. Recheck the water level in the expansion tank. If
the water level exceeds ¼ of the volume of the
expansion tank, open the tank drain, and drain to
that level.
11. Shut down the entire system and vent all
radiation units and high points in the system
piping, as described in Step 4.
12. Close make-up water valve and check strainer in
pressure reducing valve for sediment or debris
from the make-up water line. Reopen make-up
water valve.
13. Check gauge for correct water pressure and also
check water level in the system. If the height
indicated above the boiler insures that water is at
the highest point in the circulating loop, then the
system is ready for operation.
6.2 Operating Temperature Control
(Note: BMT2 may be ordered with either an on/
off or 2-stage aquastat.)
To utilize the boiler's on-board controller, be sure
to have the “Local/Remote” selector switch to “Local”.
Set the controller to the desired operating set point.
The controller has an interstage differential that can be
adjusted from 3°F to 10°F. This allows the user to have
some control over how stage 2 and stage 1 call for heat
(see Figure 19).
Because the Brute Deluxe controller senses inlet
water and the manual reset high limit senses outlet
water, the high limit should be set 40-50°F higher than
the controller, to avoid nuisance lockout of the manual
reset high limit.
6.3 External Boiler Operations
If controlling the stages of the BMT2 from an
external source (multiple boiler control, BAS, etc) the
“Local/Remote” selector switch above the terminal
strip must be placed in the “Remote” position. In this
mode, the controller that is mounted on the BMT2
will no longer have control of the unit. The 24V from
the unit waits at the input terminal, and the external
14. Refer to local codes and the make-up water
valve manufacturer’s instructions as to whether
the make-up water valve should be left open or
closed.
15. After placing the unit in operation, the ignition
system safety shutoff device must be tested.
Download from Www.Somanuals.com. All Manuals Search And Download.
BraDforD White Corp.
Page 30
If the airflow proving circuit is not proven,
ignition module will lock out. Section 6.5 describes
the result of air flow faults in more detail.
When the ignition control gets the signal at the
PSW terminal, it will energize its MV terminal, which
sends power to the stage one (or on/off) main valve.
After a 7-second trial for ignition, the ignitor
switches to flame sense mode. If a flame is not
detected, the gas valve will close and the ignition
module will attempt ignition again (up to two more
times, for a total of three attempts.) If all three
attempts fail, the ignition control will lock out.
If flame is sensed, the burner will continue to
fire as long as there is a call for heat, and none of the
safety circuit is interrupted.
If there is a call for stage 2 on a 2-stage unit, that
valve will be energized.
If there is a loss of flame signal during a
successful firing sequence, the ignition control will
remove power from the gas valves, and then attempt
to light up to two more times. If successful, the Brute
Deluxe will fire normally. If unsuccessful, the ignition
control will lock out.
*1 Difference between the temperatures at which the two switches
make R-W. Adjustable from 3°F to 10°F (1.7°C to 5.6°C) on standard
models, or from 3.6°F to 12°F (2.0°C to 6.7°C); 55°F to 175°F (13°C
to 79°C) models.
When the call for heat is satisfied, the gas
valve(s) closes, and the blower starts a 45 second post-
purge. Any pump connected to the Brute Deluxe pump
time delay relay will continue to run for the time delay
period (dialed by the user, 0.1 to 10 minutes).
*2 Two DPDT switches operate in sequence. Each switch
differential is fixed at approximately 3°F (1.7°C) on standard models,
or 3.6°F (2.0°C); 55°F to 175°F (13°C to 79°C) models.
Figure 19. Honeywell L8008G.
6.5 Ignition Control Reaction to Air Flow /
control switches this 24V from the input terminal to
the stage terminal. The input for stage 1 is initiated
by closing the circuit between the 2 terminals on the
terminal strip labeled "input stage 1." The input for
stage 2 is initiated by closing the circuit between the 2
terminals on the terminal strip labeled "input stage 2."
Blocked Vent Pressure Switch
Air flow and blocked vent status are continuously
monitored by the Brute Deluxe ignition control, at the
control’s PSW terminal.
At the start of an ignition sequence, if the ignition
control sees power at PSW for 30 seconds, but the
combustion blower has not yet been energized by the
control (F1 and F2). The ignition control will remain
in this fault mode, with the blower off. If the power to
PSW is removed while there is still a call for heat, the
ignition sequence will start again, but the main valves
will not be energized until PSW sees power during the
ignition sequence.
At the start of an ignition sequence, the control
sends the combustion blower output (F1 and F2). If
the control does not see power at PSW for more than
30 seconds, the control will remain in this fault mode,
with the blower on. If proper airflow is later detected
on PSW, the control begins a pre-purge and a normal
trial for ignition.
6.4 Sequence of Operation
The pump time delay relay will receive a signal
to initiate. If the unit is pump-mounted, the pump
will be energized. The pump terminals on the field-
wiring terminals strip will energize a field pump that is
properly interlocked with the Brute Deluxe.
Once the water flow switch makes, if all of the
safety interlocks are closed, the ignition module will
energize the blower(s) for a 15-second pre-purge,
followed by a 40-second period to allow the ignitor to
heat.
The ignition control energizes the blower. The
blower pressurizes the air box (which supplies air to
the burners) and closes the normally-open contact
on the airflow pressure switch. The blocked vent
pressure switch senses the pressure in the exhaust
plenum. This switch opens if the pressure is excessive
(as an indicator of a blocked vent). When these two
pressure switches are closed, voltage is sent to the
PSW terminal on the ignition control, which allows the
ignition module to proceed with the ignition sequence.
If the PSW signal is lost while the Brute Deluxe
is firing, the control will immediately de-energize the
gas valve terminal (MV). The blower will remain on
for the post-purge period (45 seconds), and the control
will continue to monitor the PSW input. If the signal
is detected during the post-purge period, a normal trial
for ignition will begin, starting with the 15-second
pre-purge. If the signal is not detected during the post-
purge, the control will lockout with the blower off.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (200, 300, 400)
Page 31
control will lockout, and will have to be
reset by cycling the power before the unit
will operate.
(c) Open gas shutoff valve. Restart the
appliance. The ignition sequence will
start again and the burner will start. The
appliance will return to its previous mode
of operation.
6.6 Operating the Burner and Set-Up
6.6.1 Set-Up for 0 to 2500 Feet Altitude
The setup must be checked before the unit is put
in operation. Problems such as failure to start, rough
ignition, strong exhaust odors, etc. can be due to
improper setup. Damage to the Brute Deluxe resulting
from improper setup is not covered by the limited
warranty.
6.6.2 High Altitude Adjustment and
Set-Up
1. Using this manual, make sure the installation
is complete and fully in compliance with the
instructions.
2. Determine that the appliance and system are
filled with water and all air has been bled from
both. Open all valves.
3. Observe all warnings on the Operating
Instructions label and turn on gas and electrical
power to appliance.
4. Switch on the appliance power switch located on
the right side of the unit.
5. The Brute Deluxe will enter the start sequence,
as long as the unit is being called for heat. The
blower and pump come on for pre-purge, then
the ignitor warm-up sequence starts and after
the ignitor warm-up is complete and all safety
devices are verified, the gas valves open. If
ignition doesn’t occur, check that there is proper
gas supply. Wait 5 minutes and start the unit
again. During initial start up, air in the gas line
may cause the Brute Deluxe to "lock out" during
the first few trials for ignition. If the ignition
control locks out, reset by cycling the power off
and on using the main power switch on the right
side of the cabinet.
High altitude adjustment must not be made on
appliances operating at elevations below 2500 ft. (762 m).
No orifice changes are required to adjust the
Brute Deluxe appliances for high altitude. High
altitude adjustment is accomplished by adjustment
of the air shutter. A CO2 or O2 analyzer is required to
make these adjustments.
Start the adjustment process by checking the CO2
in the “as installed” condition. Adjust the air shutter(s)
so that the CO2 is about 8% or the O2 is about 6.8%
for appliances operating on natural gas. For appliances
operating on LP Gas adjust the air shutter(s) so that the
CO2 is about 9.2% or the O2 is about 6.8%.
If the appropriate CO2 / O2 levels cannot be
achieved by adjusting the air shutter. Contact the
Technical Services Department at number shown on
back page.
The amount of derate will vary depending on
heating value of the fuel and the elevation at the
installation site.
Caution
Should any odor of gas be detected, or if the gas
burner does not appear to be functioning in a
normal manner, close main shutoff valve, do not
shut off switch, and contact your heating contractor,
gas company, or factory representative.
6. When the unit is running, the supply gas pressure
must be checked. Inlet gas pressure must not
exceed 13 in. w.c. (3.2 kPa). The minimum inlet
gas pressure is 5 in. w.c. (1.2 kPa) and 8 in. w.c.
(2 kPa) for LP.
Attention
7. Once the inlet gas pressure is verified, the
outlet gas pressure from each valve (manifold
gas pressure) must be checked, and adjusted, if
necessary. The manifold gas pressure must be 3.0
in. w.c. (0.62 kPa) for natural gas and 9.0 in. w.c.
(2.2 kPa) for LP.
8. Complete the setup by checking the CO2 at the
outlet of the unit. The CO2 should be 8% for
natural gas, or 9.2% for LP.
Si vous sentez une odeur de gaz ou si le brûleur
à gaz ne parait pas fonctionner de manière
normale, fermez la vanne d’isolement, ne fermez
aucun interrupteur, et appelez votre entreprise de
chauffage, la compagnie de gaz ou un représentant
du fabricant..
6.7 Shutting Down the Brute Deluxe
1. Switch off the main electrical disconnect switch.
2. Close all manual gas valves.
3. If freezing is anticipated, drain the Brute Deluxe
and be sure to also protect building piping from
freezing.
9. After placing the appliance in operation, the
Burner Safety Shutoff Device must be tested.
To test:
(a) Close gas shutoff valve with burner
operating.
(b) The flame will go out and blower will
continue to run for the post purge cycle.
Three attempts to light will follow. Ignition
will not occur as the gas is off. The ignition
This step to be performed by a qualified
service person.
Download from Www.Somanuals.com. All Manuals Search And Download.
BraDforD White Corp.
Page 32
SECTION 7.
Maintenance
6.8 To Restart the Brute Deluxe
If drained, follow Section 6.1 in this manual for
proper filling and purging.
7.1 System Maintenance
1. Lubricate the system water-circulating pump, if
required, per the instructions on the pump.
2. If a strainer is employed in a pressure reducing
valve or the piping, clean it every six months.
3. Inspect the venting system for obstruction or
leakage at least once a year. Periodically clean
the screens in the vent terminal and combustion
air terminal (when used).
4. Keep the appliance area clear and free from
combustible materials, gasoline, and other
flammable vapors and liquids.
5. If the appliance is not going to be used for
extended periods in locations where freezing
normally occurs, it should be isolated from the
system and completely drained of all water. All
systems connected to it should also be drained or
protected from freezing.
1. Switch off the main electrical disconnect switch.
2. Close all manual gas valves.
3. WAIT FIVE (5) MINUTES.
4. Set the aquastat or thermostat to its lowest
setting.
5. Open all manual gas valves.
6. Reset all safety switches (pressure switch,
manual reset high limit, etc.).
7. Set the temperature controller to the desired
temperature setting and switch on electrical
power.
8. Burner will go through a pre-purge period and
ignitor warm-up period, followed by ignition.
6. Low water cutoffs, if installed, should be
checked every 6 months. Float type low water
cutoff should be flushed periodically.
7. Inspect flue passages, and clean with brushes/
vacuums, if necessary. Sooting in flue passages
indicates improper combustion. Determine the
cause and correct.
8. Inspect the vent system and air intake system,
and if the vent system is Category III, ensure
that all joints are sealed properly. If joints need
to be resealed, follow venting manufacturer's
instructions to clean and reseal vent system.
7.2 Appliance Maintenance and
Component Description
Only genuine Bradford White replacement parts should
be used.
Caution
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and
dangerous operation. Verify proper operation after
servicing.
Attention
Lors d’entretien ou de réparation des commandes,
étiquetez tous les câbles avant de les déconnecter.
Des erreurs de câblage peuvent provoquer des
fonctionnements incorrects et dangereux. Après
toute intervention d’entretien ou de réparation,
vérifier que l’appareil fonctionne correctement.
The gas and electric controls on the appliance
are engineered for long life and dependable operation,
but the safety of the equipment depends on their
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (200, 300, 400)
Page 33
proper functioning. It is strongly recommended that
a qualified service technician inspect the basic items
listed below every year.
7.2.4 Manual Reset High Limit Control
The high limit switch is a manual reset, non-
adjustable switch with a remote bulb-type sensor.
Switches for water heaters and low temperature boiler
models are set at 200°F. Switches for standard boilers
are set at 240°F.
The control is located behind the front door, on a
panel in front of the blower. The probe is in the outlet
side of the header.
To reset the switch, unscrew the black cover that
is over the reset button, and push the button. Replace
the cover after the switch is reset.
To replace, shut off power to the appliance.
Remove the cover that is over the button, and remove
the nut that is around the button. Pull the control
through the panel, and remove the spade terminals.
Replace in reverse order.
a. Ignition control
b. Ignitor
c. Water temperature control
d. Automatic gas valve
e. Pressure switches and tubing
f.
Blower
g. High limit
h. Pump (if required)
i.
j.
Relays
Flow switch
k. Gas train
l.
Control components
7.2.1 Burners
Close main manual gas valve before proceeding.
Checking the burners for debris - Remove the ignitor/
burner access panel and ignitor, and inspect the
burners through the ignitor hole using a flashlight to
illuminate. If there is any indication of debris on the
burners that is visible, all the burners will need to be
inspected more thoroughly. Remove the gas manifold
assemblies and the burner assemblies. Inspect the
burners. Clean burners, if necessary, by blowing
compressed air from the outside of the burners into
the center of the burner. A dirty burner may be an
indication of improper combustion or dirty combustion
air. Determine the cause, and correct. Replace the
burners in the reverse order.
7.2.5 Ignition Control
The ignition control controls the hot surface
ignitor and proves that the flame signal is appropriate
for powering the gas valves. It also controls the
blower’s pre-purge and post-purge.
To replace a control, shut off the 120-volt power
to the appliance. Remove the cover from the control
panel. Remove the electrical connectors from the
ignition control. Take out the controller’s mounting
screws, and pull the controller out. Replace in reverse
order.
7.2.6 Ignitor
The ignitor used is a 120v “Hot Surface” type.
It is energized whenever there is a call for heat and
switched off when ignition is established and the flame
has been sensed. To replace the ignitor, shut off the
120-volt power to the appliance, remove the ignitor/
burner access panel, disconnect the Molex connector,
remove the two mounting screws on the ignitor flange,
and pull the ignitor out. Install in reverse order, always
using a new ignitor gasket with the replacement
ignitor.
7.2.2 Filter
The filter used in the Brute Deluxe is washable
and has an 80% arrestance rating. Since the filter is
washable, it will only need replacement occasionally.
If filter replacement is needed, it should only be
replaced with a factory part. Inspect the air filter
monthly, or more often in dirty environments. If there
is debris on the air filter, remove it from the filter
frame, and wash it with mild soap and water. Ensure
that the filter is completely dry before reinstalling.
Caution
Ignitor gets hot. To avoid injury, handle the ignitor
with caution.
7.2.3 Gas Valves
The gas valves are designed to operate with
supply pressures of 4-13 in. w.c. (1.0 to 3.2 kPa).
To remove a valve, shut off 120-volt power
and the manual gas shutoff valve. Remove the front
panels from the unit. Disconnect the wires to the valve.
Disengage the unions before and after the valve, and
remove the valve. Pull the pipe nipples from the inlet
and outlet of the valve, and clean the threads on the
pipe nipples for reuse. Apply new tape or pipe dope
to the pipe nipples (threaded joints should be coated
with piping compound resistant to action of liquefied
petroleum gas), and reinstall in reverse order. Turn
on manual gas shutoff valve and 120 volt power and
check appliance operation and tightness of gas valve
connections.
Attention
Le dispositif d’allumage devient très chaud.
Manipulez le dispositif d’allumage avec précaution.
7.2.7 Transformer
The Brute Deluxe’s transformer is not capable
of supplying control voltage for external devices such
as zone valves, which must have their own separate
power supply. Should a transformer need replacing,
shut off the 120-volt power. Unplug the transformer
Download from Www.Somanuals.com. All Manuals Search And Download.
BraDforD White Corp.
Page 34
wires, remove the mounting screws and remove the
transformer. Replace transformer in the reverse order.
7.2.8 Flow Switch
The Brute Deluxe uses a paddle-type flow switch
to ensure that the unit has water flow before ignition is
allowed. To replace the flow switch, turn off the 120-
volt power to the appliance. Isolate the boiler or water
heater from the system by closing the isolation valves.
valve on the heater.
3. Disconnect and remove the wires, conduit and
sensors from all components that are attached to
the inlet/outlet header.
4. Isolate the heat exchanger from the water supply.
5. Disconnect the header flanges from the inlet and
outlet.
6. Allow the heat exchanger to drain. Remove the
venting and remove the top, by removing the
screws that attach the top to the side panels.
Remove the side panels.
7. Remove the heat exchanger from the unit.
NOTE: Heat exchangers are heavy and may
require two people to remove to avoid personal
injury.
8. Clean the heat exchanger: A light accumulation
of soot or corrosion on the outside of the heat
exchanger can be easily removed. Use a wire
brush to remove loose soot and scale from the
heat exchanger.
9. NOTE: While the heat exchanger is out of the
unit, inspect the firewall refractory insulation.
Replace if necessary.
10. Inspect the inside of the copper tubes for scale
buildup. Scale can build up on the inner surface
of the heat exchanger tubes, which can restrict
water flow. If the tubes show signs of scaling,
clean the internal surface.
11. Reassemble in the reverse order, and check
appliance operation after start-up.
Caution
Water may be hot enough to scald. Allow water to
cool before proceeding.
Attention
L’eau peut être chaude au point de vous brûler.
Laissez refroidir l’eau avant d’intervenir.
Release pressure in the system by actuating
the pressure relief valves or field supplied boiler
drain valve. Remove cover from the flow switch
and disconnect the wires. Unthread the flow switch
from piping. Ensure the new flow switch paddles are
trimmed to the same size as the original paddles, and
reinstall in the reverse order. For boiler and other static
pressure systems, restore the system pressure to the
original setting, (or 10 psi minimum).
7.2.9 Heat Exchanger Coil
WARNING
NOTE: The warranty does not cover damage
caused by lack of required maintenance, lack of
water flow, or improper operating practices.
Black carbon soot buildup on a dirty heat exchanger
can be ignited by a random spark or flame thereby
creating a risk of fire or explosion. To prevent this
from happening, dampen the soot deposits with a
wet brush or fine water spray before servicing the
heat exchanger.
AVERTISSEMENT
L’accumulation de suie sur un échangeur thermique
sale peut s’enflammer au contact d’une étincelle ou
d’une flamme et présenter un risque d’incendie ou
d’explosion. Afin d’empêcher que cela se produise,
humidifier les dépôts de suie à l’aide d’une brosse
mouillée ou par une pulvérisation fine d’eau avant
d’effectuer l’entretien de l’échangeur thermique.
The Brute Deluxe has a premixed burner system.
These systems provide the burners with sufficient air
for complete combustion, and black carbon sooting is
seldom experienced. If sooting is suspected, view ports
for inspection of the heat exchanger are provided on
the side of the boiler. In the unlikely event that there is
a buildup of black carbon soot or other debris on the
heat exchanger, clean per the following:
1. Disconnect the electrical supply to the unit.
2. Turn off the gas supply by closing the manual gas
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (200, 300, 400)
Page 35
a load distribution problem. If the set points are correct
and the system design, controls scheme, etc. are fixed,
the temperature differentials may be increased to
reduce short cycling. If desired temperature response
is not achievable without short cycling it may be
necessary to install a buffer tank in the system. Contact
your Bradford White representative to discuss possible
remedies.
SECTION 8.
Trouble Shooting
8.1 Resolving Lockouts
There are many causes of lockouts. The three
most common causes are: (1) inadequate gas supply,
(2) poor combustion, (3) ignitor failure.
1. Inadequate gas supply: Before proceeding, ensure
that the gas supply has not been shutoff or the LP
tank (LP boilers) is not empty. Then, restart the
boiler and observe the operational cycle. After
a 15-second fan pre-purge, the ignitor will heat
up for 40 seconds, and then the unit will light.
If it does not, check the gas supply pressure to
the appliance, after resetting the appliance and
attempting another start-up. The gas pressure to
the appliance must be above 5 in. w.c. (1.2 kPa)
throughout the entire start-up cycle. If it is not,
correct the supply problem (check gas valves or
supply piping). If the supply pressure is adequate,
consult the factory for assistance.
2. Poor Combustion: Poor combustion should be
suspected if there is a strong flue gas odor. The
odor may result from an improper gas/air ratio
(high or low O2 or CO2). Brute Deluxe appliances
operate best with 45% excess air (8% CO2 on
natural gas, 9.2% CO2 on LP). Check the CO2 of
the appliance and adjust if necessary.
8.4 Short Cycling — Water Heater
Short cycling will generally occur only in
combination space heating and water heating
applications when the water heater is operating in the
space-heating mode. If the heating load drops below
the minimum input of the water heater for an extended
period, the water heater will have a tendency to short
cycle. If short cycling is frequently experienced,
regardless of the control’s attempt to limit it, the
heating load should be redistributed to control it.
If short cycling occurs in a water heater
application, it is probably caused by undersized
piping between the water heater and the storage tank
or by some other factor that restricts proper water
flow through the water heater. The cause should be
determined and corrected.
8.5 High Gas Consumption
Appliances operating with an improper air/
fuel ratio are very inefficient and consequently, have
very high gas consumption. Because efficiency is
high when the CO2 is high (or O2 is low), appliances
operating with low CO2 or high O2 (especially LP
appliances) consume more gas. Adjust the CO2 or O2
for optimum efficiency. If no combustion analyzing
equipment (CO2 or O2) is available then a proper
adjustment of the air/fuel ratio (CO2 or O2) cannot be
accomplished. The CO2 should be 8% at high fire for
natural gas and 9.2% at high fire for LP. To check the
CO2, first verify that the supply gas pressure is within
5 to 13 in. w.c. (1.2 to 3.2 kPa). With the Brute Deluxe
running with all stages firing, set the air box pressure
to 1.8 in. w.c. (0.42 kPa) (as a starting point), by
adjusting the air shutter(s) at the intake of the fan(s).
Check the CO2, and adjust the air shutters if further
adjustment to the CO2 is needed.
3. Ignitor failure: If the boiler goes through a
normal start cycle but combustion does not
occur, ignitor failure should be suspected. Check
the ignitor by unplugging the ignitor plug and
measuring the ignitor resistance. It should be
50-80 ohms. If the resistance is not 50-80 ohms,
replace the ignitor. If the resistance is correct,
reset the boiler and check for 120 VAC at the
ignitor plug during the start cycle. If there is no
voltage, replace the faulty ignitor wire harness or
the ignition control.
8.2 Delayed Ignition — Possible Causes
A defective burner can cause a delayed ignition.
If the gas supply pressure is proper and the gas
valves are functioning properly, then burners should
be inspected. There should be no distortion or
perforations in the burners outside of the active burner
port area. Replace if indicated.
8.3 Short Cycling — Boiler
Boiler short cycling is caused when the load
on the boiler system swings rapidly causing frequent
cycling between call for heat and satisfied conditions.
This condition is greatly reduced on two stage units
or stage controlled multiple boiler systems which can
change heat input to better match the load. If short
cycling is a problem, it may be due to an oversized
boiler, improper control strategy, incorrect set points or
Download from Www.Somanuals.com. All Manuals Search And Download.
BraDforD White Corp.
Page 36
SECTION 9.
Replacement Parts
Only genuine Bradford White replacement parts should be used.
9.1 General Information
To order or purchase parts for the Bradford White Brute Deluxe, contact your nearest Bradford White
dealer or distributor. If they cannot supply you with what you need, contact Customer Service (see back cover for
information).
9.2 Parts List
Item
Description
Size 200
Size 300
Size 400
COMBUSTION CHAMBER COMPONENTS
See Figure 20
1
Base Assembly
2C1000
2C2019
3C1000
3C2019
4C1000
4C2019
2
Support, Tile Notch
3
Chamber, Refractory, Heat Exchanger
Assembly, Front Panel, Combustion Chamber
Panel, Rear, Combustion Chamber
Panel, Top, Combustion Chamber
Chamber, Right Side, Bottom
Chamber, Left Side, Bottom
Chamber, Side, Top
T2108802
2C2023
T2108803
3C2023
T2108804
4C2023
4
5
2C2006
3C2006
4C2006
6
2C2001
3C2001
4C2001
7
2C2201
2C2201
2C2201
8
2C2601
2C2601
2C2601
9
2C2002
2C2002
2C2002
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
Panel, Right Side, Air Box
Panel, Left Side, Air Box
Weldment, Duct, Blower
Panel, Top, Air Box
2C2016
2C2016
2C2016
2C2015
2C2015
2C2015
2C2500
2C2500
2C2500
2C2008
3C2008
4C2008
Plate, Spacer, Burner/Manifold
Panel, Front, Air Box
2C2017
3C2017
4C2017
2C2009
3C2009
4C2009
Assembly, Exhaust Vent, Vertical
Weldment, Flue
2C2100
3C2100
4C2100
2C2300
2C2300
2C2300
Assembly, Air Shutter, Blower
Assembly, Filter Housing
Media, Filter
2C5000
2C5000
2C5000
2C3800
2C3800
2C3800
2C3803
2C3803
2C3803
Clip, Retaining, Filter Media
Hose, Duct, Flexible, 4" Dia.
Blower/Motor
F2022300
P0101402
E0254000
S2104400
10956000
RW2002300
52104300
L0063301
L0063300
S2104500
T2015808
S2104600
F2022300
P0101403
E0254000
S2104400
10956000
RW2002300
52104300
L0063301
L0063300
S2104500
T2015809
S2104600
F2022300
P0101404
E0254000
S2104400
10956000
RW2002300
52104300
L0063301
L0063300
S2104500
T2015810
S2104600
Gasket, Blower
Assembly, Sight Glass
Ignitor, Hot Surface
Gasket, Burner
Burner, Main (Pressure Port)
Burner, Main
Gasket, Blower Duct
Kit, Insulation, Combustion Chamber
Gasket, Flue Housing
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (200, 300, 400)
Page 37
Item
Description
Size 200
Size 300
Size 400
JACKET COMPONENTS
See Figure 21
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
Panel, Front, Jacket
R2C3320
2C3220
2C3021
2F3019
2C3620
2C3621
2C3520
2C3420
2C3622
2C3623
2C3010
2C3700
2C3702
10338600
2C3015
2C3016
R3C3320
3C3220
3C3021
3F3019
2C3620
2C3621
2C3520
2C3420
2C3622
2C3623
2C3010
2C3700
3C3702
10338600
2C3014
2C3016
R4C3320
4C3220
4C3021
4F3019
2C3620
2C3621
2C3520
2C3420
2C3622
2C3623
2C3010
4C3700
4C3702
10338600
2C3014
2C3016
Panel, Rear, Jacket
Panel, Top, Jacket
Panel, Jacket, Control Access
Panel, HX Side Access, Jacket
Panel, Right Side, Upper, Jacket
Panel, Right Side, Jacket
Panel, Left Side, Jacket
Panel, Lower Access, Jacket
Panel, Filter Side, Upper, Jacket
Panel, Filter Access, Jacket
Weldment, Cover, Air Inlet
Panel, Cover, Exhaust
Plate, Cover, Sight Glass
Side Panel, Pump Cover, Jacket
Cover, Pump
HEAT EXCHANGER COMPONENTS
See Figure 22
60
Assembly, Tube, Heat Exchanger, Copper
Assembly, Tube, Heat Exchanger, Copper-Nickel
Header, Inlet/Outlet
R2C4100
R2C4120
2F4122
R3C4100
R3C4120
2F4122
R4C4100
R4C4120
2F4122
61
62
63
64
65
66
67
Header, Return
2C4103
2C4103
2C4103
Chamber, Header, Heat Exchanger
Baffle, End, Heat Exchanger Tube
Flange, Connection, 1-1/2" NPT, Cast Iron
Gasket, Connection Flange, 1-1/2"
Valve, Pressure Relief, 3/4" NPT X 75 PSI
Valve, Pressure Relief, 3/4" NPT X 125 PSI
Gauge, Temperature/Pressure
2C4001
2C4001
2C4001
2C4002
2C4002
2C4002
S0077700
S0076500
A0063300
RA0001200
RA0079000
E0234201
E0253900
RE0013000
A0076700
A0095704
S0070800
S0077700
S0076500
A0063300
RA0001200
RA0079000
E0234201
E0253900
RE0013000
A0076800
A0095704
S0070800
S0077700
S0076500
A0063300
RA0001200
RA0079000
E0234201
E0253900
RE0013000
A0076800
A0095704
S0070800
68
69
70
71
72
Well, Immersion, Hi-Limit Temperature
Probe, Thermistor
Switch, Water Flow
Pump, Circulator, Hydronic
Pump, Circulator, Volume Water
Gasket, 5/8" Tube, 7/32" Thk. Heat Exch. (each)
73
GAS TRAIN COMPONENTS
See Figure 23
80
81
82
83
84
Weldment, Gas Manifold, Main
Manifold, Gas, On/Off
L0063702
L0063414
L0063404
L0063402
L0062900
L0063000
L0063703
L0063416
L0063413
L0063403
L0062900
L0063000
L0063704
L0063418
L0063414
L0063405
L0062900
L0063000
Manifold, Gas, 2 Stage Left Bank
Manifold, Gas, 2 Stage Right Bank
Orifice, Nat. Gas
Orifice, LP Gas
Download from Www.Somanuals.com. All Manuals Search And Download.
BraDforD White Corp.
Page 38
Item
Description
Size 200
Size 300
Size 400
85
86
Spacer, Gas Orifice
F2022400
V0079400
F2022400
V0079400
F2022400
V0079400
Gas Valve, Combination, Nat. (DSI) 3/4" NPT x
3/4" NPT
Gas Valve, Combination, LP (DSI) 3/4" NPT x
3/4" NPT
V0079500
2C2018
V0079500
2C2018
V0079500
2C2018
87
Cover, Gas Inlet, Air Box
CONTROL PANEL COMPONENTS
See Figure 24
92
93
94
95
Bracket, Mounting, Hi-Limt/Pressure Switch
Switch, Pressure, Diaphragm, SPST
Switch, Pressure, Diaphragm, SPDT
Switch, Limit, High Temperature, Hydronic
Switch, Limit, High Temperature, Volume Water
Transformer, 24, 120 V, 50VAC
2C7004
E0255500
RE0240900
E2304800
E2324200
E0180500
E0253400
R2007700
2F7002
2C7004
E0255500
RE0240900
E2304800
E2324200
E0180500
E0253400
R2007700
3F7002
2C7004
E0255500
RE0240900
E2304800
E2324200
E0180500
E0253400
R2007700
4F7002
96
97
Ignition Control, Hot Surface Ignition
Switch, Toggle, SPDT
98
99
Tray, Control Panel
100
Relay, Time Delay, (24VAC) Delay On Break,
Adjustable
RE2077700
RE2077700
RE2077700
101
102
Relay, 24VAC, DPDT
E2327800
E2328900
E2328900
Controller, Temp, 100°F to 240°F, auto reset
Thermostat, 2-Stage, 130°F to 230°F
RE0014400
RE0093200
RE0014400
RE0093200
RE0014400
RE0093200
103
104
Switch, Rocker, 15A, 125 VAC, 1/2 HP
RE2322700
E2103200
RE2322700
n/a
RE2322700
n/a
Switch, Temperature, Manual Reset, SPST,
250° F
105
106
Cover, Transformer
2C7005
E2056300
E2327500
2C7006
2C7005
E2056300
E2327500
2C7006
2C7005
E2056300
E23275800
2C7006
Switch, Toggle, SPST
107
Terminal Block, Double-Row, 16-Position
Stablilzer, Control Panel
Jumper, Terminal Block
Label, Terminal, Control Contacts
Harness, Main
108
109
E0102000
H2339100
E2337800
E2337900
E2337901
E0102000
E2339100
E2337800
E2337900
E2337901
E0102000
E2339100
E2337800
E2337900
E2337901
110
not shown
not shown
not shown
Harness, Switch, On/Off
Harness, Switch, 2-Stage
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (200, 300, 400)
Page 39
21
20
16
17
19
31
22
31
31
19
32
18
24
23
5
31
30
8
6
12
4
13
11
9
26
27
28
14
7
25
15
10
3
29
2
1
31
Figure 20. Combustion Chamber Components.
Download from Www.Somanuals.com. All Manuals Search And Download.
BraDforD White Corp.
Page 40
51
52
50
42
49
48
43
41
45
47
44
46
53
40
55
54
54
Figure 21. Jacket Components.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (200, 300, 400)
Page 41
65
71
66
68
66
65
67
69
61
72
63
73
64
63
64
60
70
62
Figure 22. Heat Exchanger Components.
Download from Www.Somanuals.com. All Manuals Search And Download.
BraDforD White Corp.
Page 42
80
87
86
ON/OFF
81
80
84 85
86
2 STAGE
86
82
85
84
Figure 23. Gas Train Components.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Deluxe (200, 300, 400)
Page 43
Figure 24. Control Panel Components.
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions and specifications subject to change without notice in accordance with our policy of continuous product improvement.
®
Ambler, PA 19002
Tech. Service (800) 334-3393
Service Parts (800) 538-2020
Warranty Service (800) 531-2111
Litho in U.S.A. © Bradford White 1101 Document 1244
Download from Www.Somanuals.com. All Manuals Search And Download.
|