Bosch Appliances Washer Dryer FPE 1000 CITY User Manual

City Tie Plug-in Module  
FPE-1000-CITY  
en Installation Guide  
es Guía de instalación  
pt  
th  
Manual de Instalação  
คมอการตดตง  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FPE-1000-CITY  
3
en  
es  
pt  
Installation Guide  
Guía de instalación  
Manual de Instalação  
th  
คมอการตดตง  
Bosch Security Systems, Inc.  
F.01U.078.100 | 04 | 2011.11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4
en  
FPE-1000-CITY  
Notices  
Use these instructions to install the FPE-1000-CITY City Tie Plug-in Module in FPA-1000 Analog Addressable Fire  
Panels.  
1. Install, test, and maintain the FPE-1000-CITY according to these instructions, NFPA 72, local codes, and the  
Authority Having Jurisdiction (AHJ).  
2. Follow the procedures in this document to avoid personal injury and damage to the equipment. Failure to follow  
these procedures can cause the FPE-1000-CITY to operate improperly. Bosch is not responsible for improperly  
installed, tested, or maintained devices.  
3. Failure to follow the mounting instructions in this document can damage the fire panel.  
4. Refer to the FPA-1000 Installation and Operation Guide for detailed wiring style requirements and complete  
programming instructions.  
Short Information  
The FPE-1000-CITY provides the system with two supervised City Tie Local Energy circuits or Reverse Polarity  
circuits. It connects to a Master Box (Local Energy Mode) or Central Station (Reverse Polarity Mode).  
Installation  
CAUTION!  
Electrostatic discharge!  
Ground yourself using a wrist strap or take other suitable actions.  
The FPA-1000 mainboard and FPE-1000-CITY plug-in module have static-sensitive components  
that could become damaged. Run the ground wire to the enclosure before handling the  
mainboard or plug-in modules. Touch ground before unpacking and handling the mainboard or  
plug-in modules. This discharges any static electricity in your body. Continue touching the  
enclosure while installing the mainboard or plug-in modules.  
DANGER!  
Before installing the FPE-1000-CITY plug-in module, remove all AC and battery power from the  
fire panel.  
The main board allows for the installation of one FPE-1000-CITY plug-in module. Refer to Figure 2 on Page 5 for the  
position of the FPE-1000-CITY City Tie Plug-in Module.The upper two plug-in slots can be used solely for the first and  
second FPE-1000-SLC Signaling Line Circuit board.  
The plug-in modules connect directly to the main board, and are detected and supervised automatically when power  
is applied to the control panel.  
FPE-1000-CITY DIP Switch Settings  
Note: Before installing the FPE-1000-CITY, set the DIP switches on the module to obtain the desired operation mode  
(Local Energy or Reverse Polarity Mode).  
Refer to Figure 1 for the location and setting of DIP switches.  
1
2
Reverse  
ON  
Reverse  
Reverse  
ON  
Reverse  
Reverse Reverse  
ON ON  
ON  
ON  
1
2
3
1
2
3
Local  
Local  
S1  
S2  
S1  
S2  
3
3
3
3
1 2  
1 2  
1 2  
1 2  
BOSCH  
Local  
Local  
Local  
Local  
S1  
S2  
S1  
S2  
Figure 1 DIP Switch Settings on the City Tie Plug-in Module  
Legend  
S1  
S2  
1
Switch 1 Supervisory (SUP)  
Switch 2 Fire Alarm (ALM)  
DIP switch setting for Reverse Polarity Mode  
DIP switch setting for Local Energy Mode  
2
F.01U.078.100 | 04 | 2011.11  
Bosch Security Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
FPE-1000-CITY  
en  
5
FPE-1000-CITY  
DIP Switches  
S1 = SUP  
2
S2 = ALM  
2
1
3
1
3
Reverse Polarity Mode  
Local Energy  
ON  
OFF  
ON  
OFF  
ON  
OFF  
ON  
OFF  
ON  
OFF  
ON  
OFF  
Note: You may use different operation modes for the circuits. The DIP switch settings 1 to 3 for each switch (S1  
and S2) must be set to the same position.  
Mounting  
1. Bring the plug-in module into position with the horizontal terminal lettering facing the front side of the control  
panel. Slide the plug-in module carefully into position along the guide rails (refer to Figure 2, Page 5, Item 1)  
2. Ensure that the connections seat into the slot properly (refer to Figure 2, Page 5, Item 2).  
3. Press down softly until the snap-fit hook locks into place (refer to Figure 2, Page 5, Item 3).  
Fire  
Gas Alarm  
Silenced  
Power  
1
Supervisory  
Trouble  
DRILL  
RESET  
SILENCE  
ACK  
2
?
@
_
3
.
:
,
A
a
1
Figure 2 Installing the FPE-1000-CITY City Tie Plug-in Module  
To remove a plug-in module, press the snap-fit hook carefully from left to right and pull the board toward the panel  
front.  
Wiring  
No special wire is required for addressable loops. The wire can be untwisted, unshielded, solid or stranded as long  
as it meets the National Electric Code 760-51 requirements for power-limited fire protective signaling cables.  
Observe a maximum circuit resistance of 65 Ω.  
Note: Use the appropiate DIP switch setting at the module to obtain the desired operation mode (refer to Figure 1,  
Page 4).  
Reverse Polarity Mode  
The FPE-1000-CITY connects the FPA-1000 Analog Addressable Fire Panel to either a single set or a pair of dual  
leased telephone company (telco) lines in NFPA 72 Remote Station applications. The FPE-1000-CITY relays system  
alarm status information from the control panel to a monitoring station.  
In normal conditions, the FPE-1000-CITY sends a steady current to a monitoring station. In an alarm condition, it  
reverses the polarity of the output current. The FPE-1000-CITY signals a trouble condition by interrupting the output  
voltage and current.  
The default setting is fire alarm for circuit 1 and supervisory for circuit 2.  
NOTICE!  
Intended for connection to a polarity reversal circuit of a remote station receiving unit having  
compatible ratings.  
Terminal  
ALM - | +  
SUP - | +  
Legend  
Default setting  
Fire Alarm  
Supervisory  
-
M
ALM  
SUP  
+
-
+
M
Monitoring Station  
Figure 3 Reverse Polarity Mode  
Bosch Security Systems, Inc.  
F.01U.078.100 | 04 | 2011.11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
6
en  
FPE-1000-CITY  
Local Energy Mode  
The FPE-1000-CITY connects Local Energy signaling devices to the FPA-1000 fire panel for auxiliary service  
operation.  
Refer to the FPA-1000 Installation and Operation Guide for a listing of compatible Gamewell devices.  
Terminal  
ALM - | +  
SUP - | +  
Connects to Municipal Master Box  
Not used  
ALM-  
ALM+  
SUP-  
SUP+  
Figure 4 Local Energy Mode  
Specifications  
Circuit resistance  
Wire gauge  
65 Ω  
12 to 18 AWG (3.3 mm2 to 0.8 mm2)  
32 °F to 120 °F (0 °C to 49 °C)  
-4 °F to 140 °F (-20 °C to 60 °C)  
Up to 93%, non-condensing  
Operating temperature  
Storage temperature  
Relative humidity  
Reverse Polarity Mode  
Nominal Voltage  
24 V DC nominal (26.4 V DC maximum), power-limited, supervised  
Output current  
33 mA maximum  
5 mA  
Supervisory/standby current  
Local Energy Mode  
Type of connection  
Alarm, trip coil  
In series  
24 V DC  
Alarm current  
250 mA (momentary, <1 ms)  
<50 mA DC  
14.5 Ω  
Supervisory/standby current  
Trip coil resistance  
Nominal coil voltage  
3.65 V DC, power-limited, supervised  
F.01U.078.100 | 04 | 2011.11  
Bosch Security Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FPE-1000-CITY  
es  
7
Avisos  
Utilice estas instrucciones para instalar el Módulo Enchufable City Tie FPE-1000-CITY en Centrales de Incendios  
Analógicas Direccionables FPA-1000.  
1. Instale, pruebe y mantenga el dispositivo FPE-1000-CITY según estas instrucciones, la norma NFPA 72, los  
códigos locales y la autoridad con jurisdicción (AHJ).  
2. Siga los procedimientos de este documento para evitar daños personales y daños al equipo. Si no sigue estos  
procedimientos, es posible que la unidad FPE-1000-CITY no funcione correctamente. Bosch no se hace  
responsable de la instalación, prueba o mantenimiento incorrecto de los dispositivos.  
3. Si no sigue las instrucciones de montaje de este documento podría producir daños en la central de incendios.  
4. Consulte la Guía de Instalación y Operación FPA-1000 para obtener información sobre los requisitos de estilo de  
cableado e instrucciones de programación completas.  
Información breve  
El dispositivo FPE-1000-CITY dota al sistema de dos circuitos supervisados de energía local City Tie o de polaridad  
inversa. Se conecta a la caja master (modo de energía local) o estación central (modo de polaridad inversa).  
Instalación  
¡PRECAUCIÓN!  
Descarga electrostática  
Protéjase con un brazalete antiestático o mediante otros procedimientos apropiados.  
La placa principal de la central FPA-1000 y el módulo enchufable FPE-1000-CITY tienen  
componentes sensibles a las cargas electrostáticas que pueden quedar dañados. Conecte el  
cable de tierra al gabinete antes de manipular la placa principal o los módulos enchufables.  
Toque tierra antes de desembalar y manipular la placa principal o los módulos enchufables.  
Esto descargará cualquier electricidad electrostática de su cuerpo. Siga tocando el gabinete  
mientras instala la placa principal o los módulos enchufables.  
¡PELIGRO!  
Antes de instalar el módulo enchufable FPE-1000-CITY, retire la alimentación de CA y baterías  
de la central de incendios.  
La placa principal permite la instalación de un módulo enchufable FPE-1000-CITY. Consulte Figura 6 en Página 8 para  
conocer la posición del módulo enchufable City Tie FPE-1000-CITY. Las dos ranuras enchufables superiores sólo se  
pueden utilizar para la primera y segunda placa del circuito de línea de señalización FPE-1000-SLC.  
Los módulos enchufables se conectan directamente a la placa principal y se detectan y supervisan de forma  
automática cuando el panel de control recibe alimentación.  
Ajustes del conmutador DIP FPE-1000-CITY  
Nota: antes de instalar el dispositivo FPE-1000-CITY, configure los conmutadores DIP en el módulo para obtener el  
modo de funcionamiento deseado (energía local o modo de polaridad inversa).  
Consulte la Figura 5 para conocer la ubicación y la configuración de los conmutadores DIP.  
1
2
Reverse  
ON  
Reverse  
ON  
Reverse  
ON  
Reverse  
ON  
Reverse Reverse  
ON ON  
1
2
3
1
2
3
Local  
Local  
S1  
S2  
S1  
S2  
3
3
3
3
1
2
1
2
1
2
1
2
BOSCH  
Local  
Local  
Local  
Local  
S1  
S2  
S1  
S2  
Figura 5 Configuración del Conmutador DIP del Módulo Enchufable City Tie  
Leyenda  
S1  
S2  
1
Conmutador 1, Supervisión (SUP)  
Conmutador 2, Alarma de Incendio (ALM)  
Configuración del conmutador DIP para el modo de polaridad inversa  
Configuración del conmutador DIP para el modo de energía local  
2
Bosch Security Systems, Inc.  
F.01U.078.100 | 04 | 2011.11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
8
es  
FPE-1000-CITY  
FPE-1000-CITY  
S1 = SUP  
S2 = ALM  
Conmutadores DIP  
1
2
3
1
2
3
Modo de polaridad inversa  
Energía local  
ON  
OFF  
ON  
OFF  
ON  
OFF  
ON  
OFF  
ON  
OFF  
ON  
OFF  
Nota: puede utilizar varios modos de funcionamiento para los circuitos. Los ajustes de los conmutador DIP (1 a  
3) deben quedar en la misma posición en ambos conjuntos (S1 y S2).  
Montaje  
1. Coloque el módulo enchufable en posición con la rotulación del terminal horizontal orientada hacia la parte  
frontal del panel de control. Deslice el módulo enchufable con cuidado por las guías hasta su posición (consulte  
la Figura 6, Página 8,elemento 1).  
2. Compruebe que las conexiones encajan correctamente en la ranura (consulte la Figura 6, Página 8, elemento 2).  
3. Presione suavemente hasta que el gancho de ajuste entre en su lugar (consulte la Figura 6, Página 8,  
elemento 3).  
Fire  
Gas Alarm  
Silenced  
Power  
1
Supervisory  
Trouble  
DRILL  
RESET  
SILENCE  
ACK  
2
?
@
_
3
.
:
,
A
a
1
Figura 6 Instalación del módulo enchufable City Tie FPE-1000-CITY  
Para retirar un módulo enchufable, presione el gancho de ajuste de izquierda a derecha con cuidado y tire de la  
placa hacia la parte frontal del panel.  
Cableado  
Para los lazos direccionables no se necesitan cables especiales. El cable puede ser no trenzado, no apantallado,  
sólido o multifilar, siempre que cumpla los requisitos del código NEC (Código Eléctrico Nacional) 760-51 para cables  
de señalización de protección contra incendios de potencia limitada.  
Respete una resistencia de circuito máxima de 65 Ω.  
Nota: utilice la configuración del conmutador DIP correcta en el módulo para obtener el modo de funcionamiento  
deseado (consulte Figura 5, Página 7).  
Modo de polaridad inversa  
El módulo FPE-1000-CITY conecta la Central de Incendios Analógica Direccionable FPA-1000 a una o dos líneas  
telefónicas, arrendadas a la compañía telefónica para aplicaciones de Estación Remota NFPA 72. El dispositivo FPE-  
1000-CITY suministra información del estado de alarma del panel de control a la estación de monitoreo.  
En condiciones normales, el dispositivo FPE-1000-CITY envía una corriente constante a la estación de monitoreo. Si  
se produce una condición de alarma, invierte la polaridad de corriente de salida. El dispositivo FPE-1000-CITY indica  
un problema mediante la interrupción de la tensión y la corriente de salida.  
El ajuste por defecto es alarma de incendio para el circuito 1 y supervisado para el circuito 2.  
¡NOTA!  
Diseñado para conexión a un circuito de polaridad inversa de una unidad de recepción de  
estación remota compatible.  
Terminal  
ALM - | +  
SUP - | +  
Leyenda  
Ajuste por defecto  
Alarma de Incendio  
Supervisado  
-
M
ALM  
SUP  
+
-
+
M
Estación de monitoreo  
Figura 7 Modo de polaridad inversa  
F.01U.078.100 | 04 | 2011.11  
Bosch Security Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
FPE-1000-CITY  
es  
9
Modo de energía local  
El dispositivo FPE-1000-CITY conecta los dispositivos de señalización de energía local a la Central de Incendio FPA-  
1000 para la operación de servicio auxiliar.  
Consulte la Guía de Instalación y Operación FPA-1000 para ver una lista de dispositivos Gamewell compatibles.  
Terminal  
ALM - | +  
SUP - | +  
Conecta a la caja maestra municipal  
Sin utilizar  
ALM-  
ALM+  
SUP-  
SUP+  
Figura 8 Modo de energía local  
Especificaciones  
Resistencia del circuito  
Sección del cable  
65 Ω  
De 3,3 mm2 a 0,8 mm2 (de 12 a 18 AWG)  
De 0 °C a 49 °C (de 32 °F a 120 °F)  
De -20 °C a 60 °C (de -4 °F a 140 °F)  
Hasta 93%, sin condensación  
Temperatura de operación  
Temperatura de almacenamiento  
Humedad relativa  
Modo de polaridad inversa  
Tensión nominal  
Nominal de 24 VCC (máxima de 26,4 VCC), potencia limitada, supervisada  
Corriente de salida  
Corriente de supervisión/espera  
Modo de energía local  
33 mA máximo  
5 mA  
Tipo de conexión  
En serie  
Alarma, bobina de conexión  
Corriente de alarma  
Corriente de supervisión/espera  
Resistencia de bobina de conexión  
Tensión nominal de bobina  
24 VCC  
250 mA (momentánea, <1 ms)  
<50 mA CC  
14,5 Ω  
3,65 VCC, potencia limitada, supervisada  
Bosch Security Systems, Inc.  
F.01U.078.100 | 04 | 2011.11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10 pt  
FPE-1000-CITY  
Avisos  
Utilize estas instruções para instalar o Módulo City Tie tipo Plug-in FPE-1000-CITY nos Painéis de Incêndio  
Endereçáveis Analógicos FPA-1000.  
1. Instale, teste e mantenha o FPE-1000-CITY de acordo com estas instruções, a norma NFPA 72, os códigos locais  
e a autoridade com jurisdição.  
2. Siga os procedimentos descritos neste documento para evitar danos pessoais e danos no equipamento. O não  
cumprimento destes procedimentos pode fazer com que o FPE-1000-CITY funcione incorretamente. A Bosch  
não se responsabiliza por dispositivos instalados, testados ou mantidos incorretamente.  
3. O não cumprimento das instruções de instalação contidas neste documento pode danificar o painel de  
incêndio.  
4. Consulte o Manual de Instalação e Operação do FPA-1000 para obter informações detalhadas dos requisitos do  
estilo de cabeamento e de todas as instruções de programação.  
Informações resumidas  
O FPE-1000-CITY equipa o sistema com dois circuitos de Energia Local supervisionados ou dois circuitos de  
Polaridade Invertida. Ele conecta a uma Master Box (caixa principal) (Modo de Energia Local) ou a uma Central de  
Monitoramento (Modo de Polaridade Invertida).  
Instalação  
CUIDADO!  
Descarga eletrostática!  
Coloque uma pulseira antiestática ou tome outras medidas adequadas.  
A placa principal FPA-1000 e o módulo tipo plug-in FPE-1000-CITY possuem componentes  
sensíveis à estática que podem ser danificados. Toque ou conecte o fio de ligação à terra no  
gabinete antes de manusear a placa principal ou os módulos tipo plug-in. Toque na ligação à  
terra antes de desembalar e manusear a placa principal ou os módulos tipo plug-in. Isso  
descarrega qualquer eletricidade estática presente no corpo. Continue tocando o gabinete  
enquanto instala a placa principal ou os módulos tipo plug-in.  
PERIGO!  
Antes de instalar o Módulo Plug-in FPE-1000-CITY, desligue a alimentação CA ou a alimentação  
por bateria do painel de incêndio.  
A placa principal permite instalar um módulo tipo plug-in FPE-1000-CITY. Consulte Figura 10 na Página 11 para obter  
informações sobre a posição do Módulo City Tie tipo Plug-in FPE-1000-CITY. Os dois slots superiores para placas  
tipo plug-in só podem ser utilizados para a primeira e a segunda placa de Circuito de Linha de Sinalização  
FPE-1000-SLC.  
Os módulos plug-in são conectados diretamente à placa principal, e são detectados e supervisionados  
automaticamente quando o painel de incêndio é alimentado com corrente elétrica.  
Configurações do interruptor DIP do FPE-1000-CITY  
Nota: Antes de instalar o FPE-1000-CITY, configure os interruptores DIP no módulo para selecionar o modo de  
funcionamento desejado (Energia Local ou Modo de Polaridade Invertida).  
Consulte Figura 9 para se informar sobre a localização e a configuração dos interruptores DIP.  
1
2
Reverse  
ON  
Reverse  
ON  
Reverse  
ON  
Reverse  
ON  
Reverse Reverse  
ON ON  
1
2
3
1
2
3
S1  
Local  
Local S2  
S1  
S2  
3
3
3
3
1
2
1
2
1
2
1
2
BOSCH  
Local  
Local  
Local  
Local  
S1  
S2  
S1  
S2  
Figura 9 Configurações dos Interruptores DIP no Módulo City Tie tipo Plug-in  
Legenda  
S1  
S2  
1
Interruptor 1 Supervisão (SUP)  
Interruptor 2 Alarme de Incêndio (ALAR)  
Configuração dos interruptores DIP para o Modo de Polaridade Invertida  
Configuração dos interruptores DIP para o Modo de Energia Local  
2
F.01U.078.100 | 04 | 2011.11  
Bosch Security Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
FPE-1000-CITY  
pt 11  
FPE-1000-CITY  
S1 = SUP  
S2 = ALM  
Interruptores DIP  
1
2
3
1
2
3
Modo de Polaridade Invertida  
Energia Local  
ON  
OFF  
ON  
OFF  
ON  
OFF  
ON  
OFF  
ON  
OFF  
ON  
OFF  
Nota: Pode-se utilizar diferentes modos de operação para os circuitos. As configurações dos interruptores DIP  
1 a 3 para cada um dos interruptores (S1 e S2) devem ser para a mesma posição.  
Instalação  
1. Coloque o módulo plug-in na posição correta, com o texto horizontal inscrito no terminal virado para o lado  
frontal do painel de controle. Faça deslizar o módulo plug-in cuidadosamente ao longo dos trilhos de guia até à  
posição correta (consulte Figura 10, Página 11, Item 1)  
2. Certifique-se de que as conexões encaixem adequadamente no slot (consulte Figura 10, Página 11, Item 2).  
3. Pressione ligeiramente para baixo, até o gancho de encaixe rápido travar corretamente (consulte Figura 10,  
Página 11, Item 3).  
Fire  
Gas Alarm  
Silenced  
Power  
1
Supervisory  
Trouble  
DRILL  
RESET  
SILENCE  
ACK  
2
?
@
_
3
.
:
,
A
a
1
Figura 10 Instalação do Módulo de Comunicação, tipo Plug-in, FPE-1000-CITY  
Para remover um módulo plug-in, empurre o gancho de encaixe rápido cuidadosamente da esquerda para a direita e  
puxe a placa para a parte frontal do painel.  
Cabeamento  
Não é necessário um cabo especial para loops endereçáveis. O cabo pode ser não trançado, sem blindagem, sólido  
ou em filamentos, desde que esteja em conformidade com os requisitos do National Electric Code 760-51 para  
cabos com sinalização de proteção contra incêndio com limitação de corrente.  
Respeite a resistência máxima do circuito de 65 Ω.  
Nota: no módulo, utilize as configurações apropriadas nos interruptores DIP para selecionar o modo de  
funcionamento desejado (consulte a Figura 9 na Página 10).  
Modo de Polaridade Invertida  
O FPE-1000-CITY conecta o Painel de Incêndio Endereçável Analógico FPA-1000 a um conjunto de uma ou duas  
linhas duplas privativas da companhia telefônica (companhia telefônica) em aplicações de Estações Remotas NFPA  
72. O FPE-1000-CITY retransmite as informações do estado do alarme do sistema do painel de incêndio para uma  
central de monitoramento de alarmes.  
Sob condições normais, o FPE-1000-CITY envia uma corrente regular para uma central de monitoramento de  
alarmes. Numa situação de alarme, ele inverte a polaridade da corrente de saída. O FPE-1000-CITY sinaliza uma  
situação de falha, interrompendo a tensão e a corrente de saída.  
A configuração predefinida para o circuito 1 é alarme de incêndio e para o circuito 2 é supervisão.  
NOTA!  
Destinado para ligação a um circuito de inversão de polaridade de uma unidade de recepção  
de uma estação remota com níveis compatíveis.  
Terminal  
ALM - | +  
SUP - | +  
Legenda  
Configuração Predefinida  
Alarme de Incêndio  
Supervisório  
-
M
ALM  
SUP  
+
-
+
M
Central de Monitoramento de Alarmes  
Figura 11 Modo de Polaridade Invertida  
Bosch Security Systems, Inc.  
F.01U.078.100 | 04 | 2011.11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
12 pt  
FPE-1000-CITY  
Modo de Energia Local  
O FPE-1000-CITY conecta os dispositivos sinalizadores de Energia Local ao painel de incêndio FPA-1000 para  
operação de serviço auxiliar.  
Consulte o Manual de Instalação e Operação para obter uma lista dos dispositivos Gamewell compatíveis.  
Terminal  
ALM - | +  
SUP - | +  
Conecta a Master Box (Caixa Principal) Municipal  
Não utilizado  
ALM-  
ALM+  
SUP-  
SUP+  
Figura 12 Modo de Energia Local  
Especificações  
Resistência do circuito  
Bitola do cabo  
65 Ω  
12 a 18 AWG (3,3 mm2 a 0,8 mm2)  
0 °C a 49 °C (32 °F a 120 °F)  
-20 °C a 60 °C (-4 °F a 140 °F)  
Até 93 %, sem condensação  
Temperatura de operação  
Temperatura de armazenamento  
Umidade relativa  
Modo de Polaridade Invertida  
Tensão Nominal  
24 Vcc nominal (máximo de 26,4 Vcc), com limitação de corrente,  
supervisionada  
33 mA no máximo  
5 mA  
Corrente de saída  
Corrente em supervisão/em  
repouso  
Modo de Energia Local  
Tipo de conexão  
Em série  
Alarme, bobina de disparo  
Corrente em alarme  
Corrente em supervisão/em  
repouso  
24 Vcc  
250 mA (momentânea, <1 ms)  
<50 mA DC  
Resistência da bobina de disparo 14,5 Ω  
Tensão nominal da bobina  
3,65 Vcc, com potência limitada, supervisionado  
F.01U.078.100 | 04 | 2011.11  
Bosch Security Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FPE-1000-CITY  
th 13  
หมายเหต  
ใชคาแนะนาเหลานเพอตดตงโมดลปลกอน City Tie FPE-1000-CITY ในแผงควบคมอคคภยทสามารถระบตาแหนงไดแบบอะนาลอก FPA-1000  
1. ตดตง ทดสอบ และบารงรกษา FPE-1000-CITY ตามคาแนะนาตอไปน คอ NFPA 72, กฎหมายในพนท  
และหนวยงานทมอานาจทางกฎหมาย (AHJ)  
2. ปฏบตตามขนตอนในเอกสารนเพอปองกนอนตรายกบตวบคคลและปองกนไมใหอปกรณเสยหาย  
การไมปฏบตตามขนตอนเหลานอาจทาให FPE-1000-CITY ทางานไมถกตอง Bosch ไมรบผดชอบตอความเสยหายทเกดจากการตดตง  
ทดสอบ หรอบารงรกษาอปกรณอยางไมเหมาะสม  
3. การไมปฏบตตามขนตอนการตดตงในเอกสารฉบบนอาจทาใหแผงสญญาณเตอนอคคภยเสยหาย  
4. สาหรบรปแบบการเดนสายไฟและคาแนะนาในการตงคาโปรแกรมโดยละเอยด โปรดดทคมอการตดตงและใชงาน FPA-1000  
ขอมลโดยยอ  
FPE-1000-CITY เปนระบบทมวงจร City Tie ผานการควบคมสองโหมดแบบใชพลงงานในพนทหรอแบบวงจรสลบขว  
ซงจะเชอมตอกบมาสเตอรบอกซ (โหมดใชพลงงานในพนท) หรอศนยรกษาความปลอดภย (โหมดสลบขว)  
การตดตง  
ขอควรระวง  
ระวงประจไฟฟาสถต!  
ใหตอสายดนกบตวคณเอง โดยใชสายรดขอมอหรอวธอนทเหมาะสม  
เมนบอรด FPA-1000 และโมดลปลกอน FPE-1000-CITY มชนสวนทไวตอไฟฟาสถตซงอาจเสยหายได  
เดนสายดนเขากบตอปกรณกอนทางานกบเมนบอรดหรอโมดลปลกอน  
ใหตอสายดนกอนการนาออกจากกลองและทางานกบเมนบอรดหรอโมดลปลกอน  
ซงจะเปนการปลดปลอยไฟฟาสถตใดๆ ทอยบนรางกายของคณ รกษาการสมผสกบตอปกรณตอไป  
ขณะตดตงเมนบอรดหรอโมดลปลกอน  
อนตราย  
กอนตดตงโมดลปลกอน FPE-1000-CITY ใหถอดแหลงจายไฟ AC  
และแบตเตอรทงหมดออกจากแผงสญญาณเตอนอคคภย  
สามารถตดตงโมดลปลกอน FPE-1000-CITY ตวหนงบนเมนบอรดได สาหรบตาแหนงของโมดลปลกอน City Tie FPE-1000-CITY โปรดดท รป  
14 หนา 14 ชองปลกอนสองชองดานบนสามารถใชสาหรบบอรดวงจรสายสงสญญาณ FPE-1000-SLC ตวทหนงและตวทสองเทานน  
โมดลปลกอนเหลานตดตงกบเมนบอรดไดโดยตรงและจะไดรบการตรวจจบและควบคมโดยอตโนมตเมอจายไฟฟาใหกบแผงควบคม  
การตงคาสวตช DIP สาหรบ FPE-1000-CITY  
หมายเหต: กอนตดตง FPE-1000-CITY ใหตงคาสวตช DIP บนโมดลตามโหมดการทางานทตองการ (โหมดพลงงานในเครองหรอโหมดสลบขว)  
โปรดดท รป 13 สาหรบตาแหนงและการตงคา DIP สวตช  
1
2
Reverse  
ON  
Reverse  
Reverse  
ON  
Reverse  
Reverse Reverse  
ON ON  
ON  
ON  
1
2
3
1
2
3
Local  
Local  
S1  
S2  
S1  
S2  
3
3
3
3
1 2  
1 2  
1 2  
1 2  
BOSCH  
Local  
Local  
Local  
Local  
S1  
S2  
S1  
S2  
รป 13 การตงคา DIP สวตชบนโมดลปลกอน City Tie  
Bosch Security Systems, Inc.  
F.01U.078.100 | 04 | 2011.11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
14 th  
FPE-1000-CITY  
คาอธบายสญลกษณ  
S1  
S2  
1
สวตช 1 การตรวจสอบ (SUP)  
สวตช 2 สญญาณเตอนอคคภย (ALM)  
การตงคาสวตช DIP สาหรบโหมดสลบขว  
การตงคาสวตช DIP สาหรบโหมดใชพลงงานในเครอง  
2
FPE-1000-CITY  
สวตช DIP  
S1 = SUP  
S2 = ALM  
1
ON  
OFF  
2
3
ON  
OFF  
1
ON  
OFF  
2
3
ON  
OFF  
โหมดสลบขว  
พลงงานในเครอง  
ON  
OFF  
ON  
OFF  
หมายเหต: คณสามารถใชงานวงจรในโหมดการทางานอนได การตงคาสวตช DIP แบบท 1 ถง 3 สาหรบสวตชแตละตว (S1 และ S2)  
จะตองอยในตาแหนงเดยวกน  
การตดตง  
1. วางโมดลปลกอนใหเขาทโดยใหตวอกษรของขวในแนวนอนหนเขาหาดานหนาของแผงควบคม  
เลอนโมดลปลกอนใหเขาทอยางระมดระวงตามราง (โปรดดท รป 14, หนา 14, ขอ 1)  
2. ตรวจสอบใหแนใจวาการเชอมตอวางอยในชองเสยบอยางถกตอง (โปรดดท รป 14, หนา 14, ขอ 2)  
3. กดเบาๆ จนกวาตะขอเกยวจะลอกเขาท (โปรดดท รป 14, หนา 14, ขอ 3)  
Fire  
Gas Alarm  
Silenced  
Power  
1
Supervisory  
Trouble  
DRILL  
RESET  
SILENCE  
ACK  
2
?
@
_
3
.
:
,
A
a
1
รป 14 การตดตงโมดลปลกอน City Tie FPE-1000-CITY  
หากตองการถอดโมดลปลกอน ใหกดขอเกยวอยางระมดระวงจากซายไปขวาและดงบอรดออกมาทางแผงดานหนา  
การเดนสาย  
ไมจาเปนตองใชสายไฟเพมสาหรบลปทสามารถระบตาแหนงได สายไฟอาจเปนแบบไมมการปองกนการแพรกระจายคลน  
เปนสายแขงหรอสายตเกลยวตามขอกาหนด National Electric Code 760-51 สาหรบสายสญญาณปองกนอคคภยแบบจากดกาลงไฟ  
ตรวจสอบความตานทานวงจรสงสดท 65 Ω  
หมายเหต: ใชการตงคาสวตช DIP ทเหมาะสมทโมดลเพอรบโหมดการทางานทตองการ (โปรดดท รป 13 หนา 13)  
โหมดสลบขว  
FPE-1000-CITY เชอมตอกบแผงควบคมอคคภยทสามารถระบตาแหนงไดแบบอะนาลอก FPA-1000 เขากบคสายโทรศพทเชาของบรษท (telco)  
ชดเดยวหรอสายคในแอพพลเคชนสาหรบสถานทางไกล NFPA 72 ขอมลสถานะสญญาณเตอนของระบบรเลย FPE-1000-CITY  
จากแผงควบคมเขากบสถานตรวจสอบ  
ในสถานการณปกต FPE-1000-CITY จะสงกระแสไฟคงทไปยงสถานตรวจสอบ ในสถานการณทมสญญาณเตอน  
โมดลจะกลบขวของกระแสเอาตพต FPE-1000-CITY จะสงสญญาณแจงเหตขดของโดยหยดกระแสไฟฟาและแรงดนไฟฟาเอาตพต  
การตงคาเบองตนคอวงจรสญญาณเตอนอคคภยสาหรบวงจร 1 และวงจรควบคมสาหรบวงจร 2  
F.01U.078.100 | 04 | 2011.11  
Bosch Security Systems, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
FPE-1000-CITY  
th 15  
หมายเหต  
ออกแบบขนเพอการเชอมตอเขากบวงจรสลบขวของหนวยรบสญญาณของสถานทางไกลทมอตราการทางานทเขากน  
ได  
แผงขวตอ  
ALM - | +  
SUP - | +  
การตงคาเบองตน  
สญญาเตอนอคคภย  
การตรวจสอบ  
-
M
ALM  
SUP  
+
-
+
คาอธบายสญลกษณ  
สถานตรวจสอบ  
โหมดใชพลงงานภายในระบบ  
รป 15 โหมดสลบขว  
M
FPE-1000-CITY เชอมตออปกรณสงสญญาณทใชพลงงานในพนทเขากบแผงควบคมอคคภย FPA-1000 เพอการใหบรการเสรม  
สาหรบรายการของอปกรณ Gamewell ททางานรวมกนได โปรดดทคมอการตดตงและการใชงาน FPA-1000  
แผงขวตอ  
ALM - | +  
SUP - | +  
เชอมตอกบมาสเตอรบอกซของเขตชมชน  
ไมใชงาน  
ALM-  
ALM+  
SUP-  
SUP+  
รป 16 โหมดใชพลงงานภายในระบบ  
ขอมลจาเพาะ  
ความตานทานของวงจร  
65 Ω  
12 ถง 18 AWG (3.3 มม.2 ถง 0.8 มม.2)  
32 °F ถง 120 °F (0 °C ถง 49 °C)  
-4 °F ถง 140 °F (-20 °C ถง 60 °C)  
ไมเกน 93%, ไมมการควบแนน  
ขนาดสายไฟ  
อณหภมในการทางาน  
อณหภมในการเกบรกษา  
ความชนสมพทธ  
โหมดสลบขว  
แรงดนไฟฟาปกต  
ปกต 24 V DC (สงสด 26.4 V DC ), จากดกาลงไฟฟา, มการตรวจสอบ  
กระแสไฟเอาตพต  
สงสด 33 mA  
กระแสไฟฟาควบคม/ขณะรอใชงาน  
โหมดใชพลงงานภายในระบบ  
ประเภทของการเชอมตอ  
สญญาณเตอน, ทรปคอยล  
กระแสไฟฟาสญญาณเตอน  
กระแสไฟฟาควบคม/ขณะรอใชงาน  
ความตานทานของทรปคอยล  
แรงดนไฟฟาปกตทคอยล  
5 mA  
ตออนกรม  
24 V DC  
250 mA (ชวขณะ, <1 ms)  
<50 mA DC  
14.5 Ω  
3.65 V DC จากดกาลงไฟ มการตรวจสอบ  
Bosch Security Systems, Inc.  
F.01U.078.100 | 04 | 2011.11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Bosch Security Systems, Inc.  
130 Perinton Parkway  
Fairport, NY 14450  
USA  
© Bosch Security Systems, Inc., 2011  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Black Decker Drill 611196 00 User Manual
Braun Electric Shaver P40 User Manual
Breville Blender BBL800 User Manual
Breville Slow Cooker BRC600 User Manual
Briggs Stratton Lawn Mower S50X User Manual
Brother Typewriter em 550 User Manual
Bush Hog Brush Cutter 320 Series User Manual
Canon Digital Camera SUPER135 User Manual
CFM Ventilation Hood GEF10 User Manual
Cisco Systems IP Phone OL 5378 01 User Manual