Bosch Appliances Smoke Alarm LBB 1990 0 User Manual

Communication Systems | LBB 1990/00 Plena Voice Alarm Controller  
LBB 1990/00 Plena Voice Alarm Controller  
Heart of the Plena Voice Alarm System  
Compliant with standards for emergency sound  
systems (IEC60849)  
6-zone system controller  
Built-in 240 W booster amplifier  
12 Business and emergency control inputs and  
outputs  
The Plena Voice Alarm Controller is the heart of the voice  
alarm system. It is the basis of the Plena Voice Alarm  
System, and has all the essential functionality for  
compliance with the IEC 60849 standard, including full  
system supervision, loudspeaker line impedance  
supervision, a supervised emergency microphone on the  
front panel and a supervised message manager.  
The messages can be merged to allow even more flexible  
use of pre-recorded announcements and evacuation  
messages. The controller can be used as a stand-alone  
system with up to 6 zones, or expanded to up to  
60 zones using additional 6-zone routers. Up to 8 call  
stations can be connected. Interconnections are made  
using standard RJ45 connectors and shielded CAT-5  
cable.  
A built-in 240 W amplifier provides the power for the  
emergency call channel and BGM. Additional Plena  
Amplifiers can be added to provide two-channel  
operation, or for additional power if the total power  
requirement exceeds 240 W (maximum 480 W per 6  
zones). All amplifiers are supervised. The audio output  
uses standard analog audio 100 V line switching for full  
compatibility with the Plena family of public address  
equipment and Bosch EVAC-compliant loudspeakers.  
The system is configured using DIP switches for basic  
functionality and a PC for more advanced functions.  
Functions  
The controller has two BGM source inputs and a mic/line  
input with configurable priority, speech filter, phantom  
power and selectable VOX activation. A total of 16  
priority levels can be specified for microphone, call  
stations and trigger inputs for optimum system  
flexibility.  
The powerful 240 W output section has six transformer-  
isolated 100 V constant voltage outputs for driving 100 V  
loudspeakers in six separate zones. The 100 V-technique  
reduces line losses on longer distances and allows for  
easy parallel connection of multiple loudspeakers. All  
zones may be individually selected from the front panel,  
and the BGM output level in each zone can be  
individually set in 6 steps. The BGM output is connected  
to the 70 V line, so it is possible to connect a total load  
of 480 Watts in a two-channel system combined with a  
480 Watt booster.  
The output of the booster is also available as a separate  
output on 100 V and 70 V. A separate 100 V Call Only  
output is provided for addressing an area where BGM is  
not required but where priority announcements are. Six  
configurable Volume Override output contacts are  
available for overriding local volume controls during  
priority calls. A LED VU-meter monitors the output.  
Up to 255 messages can be stored in the internal  
16 MB flash ROM, without a need for battery backup.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LBB 1990/00 Plena Voice Alarm Controller | 3  
Outputs  
Supervision Flash ROM  
Supervision DAC  
Continuous checksum control  
1 Hz pilot tone  
Tape Output  
Cinch, 2x mono  
Nominal Level  
Impedance  
350 mV  
Data Retention Time  
>10 years  
<1 kOhm  
Loudspeaker Outputs  
100 V Outputs  
Volume Override Type  
MSTB 2,5 /16-ST floating  
480 W rated per zone  
3 wire, 4 wire (24V), 4 wire failsafe  
Ordering Information  
Model | Description  
LBB 1990/00 Plena Voice Alarm Controller  
BGM Zone Output  
Attenuation  
70/50/35/25/18/13 V for  
0/-3/-6/-9/-12/-15 dB (120/60/30/15/8/4  
W)  
Output Contacts  
All Contacts  
Connector Type  
Rating  
MC 1,5/14-ST-3,5  
250 V 7A voltage free  
NO / COM / NC  
Emergency Active Relay  
Call Active Relay  
Fault Relay  
NO / COM / NC  
NO / COM / NC normally energized (failsafe)  
NO / COM  
General Purpose Relays (2x)  
Environmental  
Operating Temperature  
Storage Temperature  
Relative Humidity  
+5°C to +55°C  
-25°C to +55°C  
<95%  
Acoustic Noise Level of Fan  
<48 dB SPL @ 1m, at max speed  
temperature controlled 0 to max speed  
Dimensions  
144 x 430 x 360 mm  
(19" wide, 3U high)  
Weight  
approx. 15 kg  
Rack Building  
Rack mounting kit included  
Messages  
Data Format  
WAV-file, 16-bit PCM, mono  
Supported Sample Rates (fs)  
24 kHz, 22.05 kHz, 16 kHz, 12 kHz,  
11.025 kHz, 8 kHz  
Frequency Response  
@ fs = 24kHz  
100 Hz – 11 kHz (+1/-3 dB)  
100 Hz – 10 kHz (+1/-3 dB )  
100 Hz – 7.3 kHz (+1/-3 dB )  
100 Hz – 5.5 kHz (+1/-3 dB)  
100 Hz – 5 kHz (+1/-3 dB)  
100 Hz – 3.6 kHz (+1/-3 dB)  
<0.1% @ 1 kHz  
@ fs = 22.05kHz  
@ fs = 16kHz  
@ fs = 12kHz  
@ fs = 11.025kHz  
@ fs = 8kHz  
Distortion  
S/N (flat at max volume)  
Memory Capacity  
Recording / Playback Time  
>80 dB  
16 MB Flash ROM  
1000 seconds @ fs = 8 kHz  
333 seconds @ fs = 24 kHz  
Number of Messages  
Max. 255  
Americas:  
Europe, Middle East, Africa:  
Bosch Security Systems B.V.  
P.O. Box 80002  
5600 JB Eindhoven, The Netherlands  
Phone: +31 (0) 40 27 83955  
Fax: +31 (0) 40 27 86668  
Asia-Pacific:  
Represented by  
Bosch Security Systems  
130 Perinton Parkway  
Fairport, New York, 14450, USA  
Phone: +1 585 223 4060  
Fax: +1 800 289 0096  
Bosch Security Systems Pte Ltd  
38C Jalan Pemimpin  
Singapore 577180  
Phone: +65 6319 3450  
Fax: +65 6319 3499  
© Bosch Security Systems, 2005 | Data subject to change without notice | 12. Dec. 2005  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Belkin Network Router PM01218ea F5D7634 4 User Manual
Blaupunkt Car Stereo System Seattle MP74 US User Manual
Bolens Blower TB720r User Manual
Bosch Appliances Cooktop NET 74 User Manual
Bradford White Corp Water Heater TGHE 160E NX User Manual
Bush Hog Lawn Mower HS1736 User Manual
Canon Copier IR2200i User Manual
Casio Projector XJ 460 User Manual
CFM Ventilation Hood HRV 0904 User Manual
Channel Plus Home Theater Server 5314 User Manual