Carrier Air Conditioner 38AE012 User Manual

38AE012,014,016  
38AKS024  
Air-Cooled Condensing Units  
50/60 Hz  
Installation, Start-Up and  
Service Instructions  
Only trained, qualified installers and service mechanics  
CONTENTS  
should install, start-up, and service this equipment (Fig. 1).  
Page  
Untrained personnel can perform basic maintenance func-  
tions such as cleaning coils. All other operations should be  
performed by trained service personnel.  
When working on the equipment, observe precautions in  
the literature and on tags, stickers, and labels attached to the  
equipment.  
Follow all safety codes. Wear safety glasses and work gloves.  
Keep quenching cloth and fire extinguisher nearby when  
brazing. Use care in handling, rigging and setting bulky  
equipment.  
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1  
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8  
Step 1 — Complete Pre-Installation Checks . . . . 1  
Step 2 — Rig and Mount the Unit . . . . . . . . . . . . . 6  
Step 3 — Complete Refrigerant Piping  
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6  
Step 4 — Install Accessories . . . . . . . . . . . . . . . . . 7  
Step 5 — Complete Electrical Connections . . . . 7  
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9  
Evacuate and Dehydrate . . . . . . . . . . . . . . . . . . . . . . 9  
Leak Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9  
Turn On Crankcase Heaters . . . . . . . . . . . . . . . . . . 9  
Add Preliminary Charge . . . . . . . . . . . . . . . . . . . . . . 9  
Before Starting Unit . . . . . . . . . . . . . . . . . . . . . . . . . . 9  
ELECTRIC SHOCK HAZARD  
Separate power sources (main and control  
power circuits) are used for these units. Be  
sure both main and control power circuits are  
disconnected before servicing.  
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-13  
To Start Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9  
Oil Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9  
Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . 9  
Check Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13  
INSTALLATION  
Step 1 — Complete Pre-Installation Checks  
OPERATING SEQUENCE . . . . . . . . . . . . . . . . . . . . 13  
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13  
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13  
Fan Cycling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13  
Winter Start Control . . . . . . . . . . . . . . . . . . . . . . . . . 13  
UNCRATE UNIT — Remove unit packaging except for the  
top skid assembly, which should be left in place until after  
the unit is rigged into its final location.  
INSPECT SHIPMENT — File claim with shipping com-  
pany if shipment is damaged or incomplete.  
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13,14  
Capacity Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13  
Head Pressure Control . . . . . . . . . . . . . . . . . . . . . . 13  
Time GuardII Circuit . . . . . . . . . . . . . . . . . . . . . . . 13  
Winter Start Control . . . . . . . . . . . . . . . . . . . . . . . . . 13  
Crankcase Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . 13  
Outdoor Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14  
Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14  
Cleaning Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14  
CONSIDER SYSTEM REQUIREMENTS  
• Consult local building codes and National Electrical Code  
(NEC, U.S.A.) for special installation requirements.  
• Allow sufficient space for airflow clearance, wiring, re-  
frigerant piping, and servicing unit. See Fig. 1. See  
Fig. 2 for unit component locations.  
• Locate unit so that outdoor coil (condenser) airflow is un-  
restricted on all sides and above.  
• Unit may be mounted on a level pad directly on the base  
channels or mounted on raised pads at support points. See  
Table 1A-1D for unit operating weights. See Table 2 for  
weight distribution based on recommended support points.  
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . 15,16  
START-UP CHECKLIST . . . . . . . . . . . . . . . . CL-1,CL-2  
SAFETY CONSIDERATIONS  
NOTE: If vibration isolators are required for a particular  
installation, use the data in Table 2 to make the proper  
selection.  
Installing, starting up, and servicing air-conditioning equip-  
ment can be hazardous due to system pressures, electrical  
components, and equipment location (roofs, elevated struc-  
tures, etc.).  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book 1 PC 111 Catalog No. 563-746 Printed in U.S.A. Form 38A-4SI Pg 1 4-94 Replaces: 38AE-17SI  
Tab 3a 2a  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
3
1
2
4
5
6
7
12  
11  
10  
9
8
LEGEND  
1
2
3
4
Low-Voltage Fuse  
No. 1 Fan  
High-Pressure Switch  
Circuit Breakers  
5
6
7
8
No. 2 Fan  
9
Compressor  
Terminal Block 1 (Unit Power)  
10  
Low-Pressure Switch  
Terminal Block 2 (Control Power) 11  
Wraparound Coil 12  
Hot Gas Bypass Piping Stub (38-in. ODM)  
Muffler  
Fig. 2 — Component Locations (Typical — 38AE Shown)  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 1A — Physical Data (English, 60 Hz)  
UNIT  
38AE012  
38AE014  
38AE016  
38AKS024  
OPERATING WEIGHT (lb)  
REFRIGERANT*  
732  
779  
789  
900  
R-22  
COMPRESSOR  
Speed (Rpm)  
No. Cylinders  
Model No.  
Reciprocating, Semi-Hermetic  
1750  
6
06DD824  
10  
6
06DD328  
10  
6
06DD537  
10  
4
06E4250  
15.5  
Oil (pt)  
Crankcase Heater Watts  
Unloader Setting (psig)  
Load  
125  
125  
125  
180  
70 ± 1  
60 ± 2  
Unload  
OUTDOOR-AIR FANS  
No. ...Rpm  
Axial Flow, Direct Drive  
2...1075  
Diameter (in.)  
24  
24  
24  
26  
1
Motor Hp  
Nominal Total Airflow (Cfm)  
2
8800  
8800  
40.3  
8800  
11,000  
OUTDOOR COIL  
Face Area (sq ft)  
29.2  
Storage Capacity (lb)†  
27.2  
39.8  
39.8  
CONTROLS  
Pressurestat Settings (psig)  
High Cutout  
Cut-in  
395 ± 10  
295 ± 10  
29 ± 4  
Low Cutout  
Cut-in.  
60 +15, –0  
FUSIBLE PLUG (F)  
200  
PIPING CONNECTIONS (in. ODM)  
Suction  
Liquid  
118  
138  
138  
158  
5
8
Unit is factory supplied with holding charge only.  
†Storage capacity is measured at liquid saturated temperatures of 125 F for 38AE012,  
123 F for 38AE014, and 130 F for 38AE016 and 38AKS024.  
Table 1B — Physical Data (SI, 60 Hz)  
UNIT  
38AE012  
38AE014  
38AE016  
38AKS024  
OPERATING WEIGHT (kg)  
REFRIGERANT*  
333  
354  
359  
408  
R-22  
COMPRESSOR  
Speed (r/s)  
Reciprocating, Semi-Hermetic  
29.2  
No. Cylinders  
Model No.  
6
06DD824  
4.73  
6
06DD328  
4.73  
6
06DD537  
4.73  
4
06E4250  
7.33  
Oil (L)  
Crankcase Heater Watts  
Unloader Setting (kPa)  
Load  
125  
125  
125  
180  
483 ± 6.9  
414 + 103, –0  
Unload  
OUTDOOR-AIR FANS  
No. ...r/s  
Axial Flow, Direct Drive  
2...17.9  
Diameter (mm)  
Motor Hp  
610  
610  
610  
661  
1
2
Nominal Total Airflow (L/s)  
4153  
4153  
18.3  
4153  
18.1  
5566  
OUTDOOR COIL  
Face Area (sq m)  
Storage Capacity (kg)†  
2.71  
12.4  
18.1  
CONTROLS  
Pressurestat Settings (kPa)  
High Cutout  
Cut-in  
2724 ± 68.9  
2034 ± 68.9  
200 ± 27.6  
Low Cutout  
Cut-in  
414 + 103, –0  
FUSIBLE PLUG (C)  
93.3  
PIPING CONNECTIONS (in. ODM)  
Suction  
Liquid  
118  
138  
138  
158  
5
8
*Unit is factory supplied with holding charge only.  
†Storage capacity is measured at liquid saturated temperatures of 51.7 C for 38AE012,  
50.6 C for 38AE014, and 54.4 C for 38AE016 and 38AKS024.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 1C — Physical Data (English, 50 Hz)  
UNIT  
38AE012  
38AE014  
38AE016  
38AKS024  
OPERATING WEIGHT (lb)  
REFRIGERANT*  
732  
779  
789  
900  
R-22  
COMPRESSOR  
Speed (Rpm)  
No. Cylinders  
Model No.  
Reciprocating, Semi-Hermetic  
1460  
6
06DD824  
10  
6
06DD328  
10  
6
06DD537  
10  
4
06E4250  
15.5  
Oil (pt)  
Crankcase Heater Watts  
Unloader Setting (psig)  
Load  
125  
125  
125  
180  
70 ± 1  
60 ± 2  
Unload  
OUTDOOR-AIR FANS  
No. ...Rpm  
Axial Flow, Direct Drive  
2...900  
Diameter (in.)  
24  
24  
24  
26  
1
Motor Hp  
Nominal Total Airflow (Cfm)  
2
7368  
7368  
40.3  
7368  
9210  
OUTDOOR COIL  
Face Area (sq ft)  
29.2  
Storage Capacity (lb)†  
27.2  
39.8  
39.8  
CONTROLS  
Pressurestat Settings (psig)  
High Cutout  
Cut-in  
Low Cutout  
Cut-in  
395 ± 10  
295 ± 10  
29 ± 4  
60 + 15, –0  
FUSIBLE PLUG (F)  
200  
PIPING CONNECTIONS (in. ODM)  
Suction  
Liquid  
118  
138  
138  
158  
5
8
*Unit is factory supplied with holding charge only.  
†Storage capacity is measured at liquid saturated temperatures of 125 F for 38AE012,  
123 F for 38AE014, and 130 F for 38AE016 and 38AKS024.  
Table 1D — Physical Data (SI, 50 Hz)  
UNIT  
38AE012  
38AE014  
38AE016  
38AKS024  
OPERATING WEIGHT (kg)  
REFRIGERANT*  
333  
354  
359  
408  
R-22  
COMPRESSOR  
Speed (r/s)  
Reciprocating, Semi-Hermetic  
24.3  
No. Cylinders  
Model No.  
6
06DD824  
4.73  
6
06DD328  
4.73  
6
06DD537  
4.73  
4
06E4250  
7.33  
Oil (L)  
Crankcase Heater Watts  
Unloader Setting (kPa)  
Load  
125  
125  
125  
180  
483 ± 6.9  
414 + 103, –0  
Unload  
OUTDOOR-AIR FANS  
No. ...r/s  
Axial Flow, Direct Drive  
2...15.0  
Diameter (mm)  
Motor Hp  
610  
610  
610  
661  
1
2
Nominal Total Airflow (L/s)  
3728  
3728  
18.3  
3728  
18.1  
4660  
OUTDOOR COIL  
Face Area (sq m)  
Storage Capacity (kg)†  
2.71  
12.4  
18.1  
CONTROLS  
Pressurestat Settings (kPa)  
High Cutout  
Cut-in  
2724 ± 68.9  
2034 ± 68.9  
200 ± 27.6  
Low Cutout  
Cut-in  
414 + 103, –0  
FUSIBLE PLUG (C)  
93.3  
PIPING CONNECTIONS (in. ODM)  
Suction  
Liquid  
118  
138  
138  
158  
5
8
*Unit is factory supplied with holding charge only.  
†Storage capacity is measured at liquid saturated temperatures of 51.7 C for 38AE012,  
50.6 C for 38AE014, and 54.4 C for 38AE016 and 38AKS024.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 2 — Weight Distribution  
Step  
3
Complete Refrigerant Piping  
Connections  
WEIGHT — lb (kg)  
UNIT  
Support Point  
Total  
IMPORTANT: A refrigerant receiver is not provided  
with the unit. Do not install a receiver.  
Operating  
A
B
C
D
38AE012  
38AE014  
38AE016  
38AKS024  
732 (333)  
779 (354)  
789 (359)  
900 (408)  
142 (65) 138 (63) 225 (102)  
227(103)  
143 (65) 140 (64) 247 (112) 249 (113)  
143 (65) 143 (65) 250 (114) 253 (115)  
178 (81) 168 (76) 269 (122) 285 (129)  
SIZE REFRIGERANT LINES — Consider the length of  
piping required between outdoor unit and indoor unit  
(evaporator), the amount of liquid lift, and compressor oil  
return. See Tables 3, 4A, and 4B and also refer to Part 3 of  
Carrier System Design Manual for design details and line  
sizing. Refer to indoor installation instructions for addi-  
tional information.  
Table 3 — Liquid Line Data  
MAXIMUM  
ALLOWABLE  
LIQUID LINE  
LIQUID LIFT  
ft (m)  
UNIT  
Maximum Filter Drier  
Maximum  
Allowable  
Pressure Drop  
psig (kPa)  
Allowable  
Temp.  
Loss  
and  
60 Hz  
50 Hz  
Sight Glass  
Flare Conn.*  
in. (mm)  
Step 2 — Rig and Mount the Unit  
F (C)  
38AE012  
38AE014  
38AE016  
52 (15.8)  
67 (20.4)  
82 (25)  
5
7 (48.3)  
2 (1.1)  
8  
Be sure unit panels are securely in place prior to  
rigging.  
38AKS024 87 (26.5) 86 (26)  
*Inlet and outlet.  
RIGGING — These units are designed for overhead rigging  
only. For this purpose, the transverse base channels extend  
beyond the sides of the unit, with holes provided in the end  
plates to attach cables or hooks. Rig with top skid packaging  
assembly in place to prevent unit damage by the rigging cable.  
As further protection for the coil faces, plywood sheets can  
be placed against the sides of the unit, behind the cables.  
Run the cables to a central suspension point so that the angle  
from the horizontal is not less than 45 degrees. Raise and set  
the unit down carefully.  
NOTE: Data shown is for units operating at 45 F (7.2 C) saturated suction and  
95 F (35 C) entering air.  
Table 4A — Refrigerant Piping Sizes — 60 Hz  
LENGTH OF INTERCONNECTING PIPING — FT (M)  
0-15  
15-25  
25-50  
50-75  
75-100  
(0-4.6)  
(4.6-7.6) (7.6-15.2) (15.2-22.9) (22.9-30.5)  
UNIT  
Line Size — in. OD  
L
S
L
S
L
S
L
S
L
S
If it is necessary to roll the unit into position, mount the  
unit on longitudinal rails, using a minimum of 3 rollers. Ap-  
ply force to the rails, not the unit. If the unit is to be skidded  
into position, place it on a large pad and drag it by the pad.  
Do not apply any force to the unit.  
Raise from above to lift unit from the rails or pad when  
unit is in final position.  
1
1
5
5
5
38AE012  
38AE014  
38AE016  
38AKS024  
2  
2  
2  
8  
118  
118  
138  
158  
2
2
8
8
118  
138  
138  
158  
8
8
8
8
138  
138  
158  
158  
8
8
8
8
138  
158  
158  
218  
8  
8  
8  
8  
158  
158  
218  
218  
1
1
5
1
5
5
5
5
7
5
7
7
7
7
7
LEGEND  
L
S
Liquid  
Suction  
Close coupled.  
COMPRESSOR MOUNTING — As shipped, the compres-  
sor is held tightly in place by self-locking bolts. Before start-  
ing unit, loosen self-locking bolts until the snubber  
washer can be moved sideways with finger pres-  
sure. Do not remove shipping bolts. See Fig. 3.  
NOTES:  
1. Pipe sizes are based on a 2 F (1.1 C) loss for liquid lines and a 1.5 F  
(0.8 C) loss for suction lines.  
2. Pipe sizes are based on an equivalent length equal to the maximum length  
of interconnecting piping plus 50% for fittings. A more accurate estimate may  
result in smaller sizes.  
Table 4B — Refrigerant Piping Sizes — 50 Hz  
LENGTH OF INTERCONNECTING PIPING — FT (M)  
0-15  
(0-4.6)  
15-25  
25-50  
50-75  
75-100  
(4.6-7.6) (7.6-15.2) (15.2-22.9) (22.9-30.5)  
UNIT  
Line Size — in. OD  
L
S
L
S
L
S
L
S
L
S
1
1
5
5
5
38AE012  
38AE014  
38AE016  
38AKS024  
2  
2  
2  
8  
118  
118  
138  
158  
2
2
8
8
118  
118  
138  
158  
8
8
8
8
118  
138  
138  
158  
8
8
8
8
138  
138  
138  
158  
8  
8  
8  
8  
138  
138  
158  
158  
1
1
5
1
5
5
5
5
5
5
5
7
5
5
7
LEGEND  
L
S
Liquid  
Suction  
Close coupled.  
NOTES:  
1. Pipe sizes are based on a 2 F (1.1 C) loss for liquid lines and a 1.5 F  
(0.8 C) loss for suction lines.  
2. Pipe sizes are based on an equivalent length equal to the maximum length  
of interconnecting piping plus 50% for fittings. A more accurate estimate may  
result in smaller sizes.  
Fig. 3 — Compressor Mounting  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALL FILTER DRIER(S) AND MOISTURE INDICA-  
TOR(S) — Every unit should have a filter drier and liquid-  
moisture indicator (sight glass). In some applications, depending  
on space and convenience requirements, it may be desirable  
to install 2 filter driers and sight glasses. One filter drier and  
sight glass may be installed at A locations in Fig. 4. Or, 2  
filter driers and sight glasses may be installed at B locations.  
Select the filter drier for maximum unit capacity and mini-  
mum pressure drop. Complete the refrigerant piping from  
indoor unit to outdoor unit before opening the liquid and suc-  
tion lines at the outdoor unit.  
NOTE: 38AKS024 has a fusible plug in the liquid line.  
Fig. 5 — Location of Fusible Plug (38AE)  
Step 4 — Install Accessories — Field install ac-  
cessories such as winter start control or low-ambient control  
before proceeding with wiring. Refer to the instructions shipped  
with the accessory.  
Step 5 — Complete Electrical Connections  
POWER WIRING — Unit is factory wired for voltage shown  
on nameplate. Provide adequate fused disconnect switch within  
sight from unit and readily accessible from unit, but out of  
the reach of children. Lock switch open (off) to prevent power  
from being turned on while unit is being serviced. Discon-  
nect switch, fuses, and field wiring must comply with na-  
tional and local code requirements. See Tables 5A and 5B.  
Route power wires through opening in unit end panel to  
connection in unit control box as shown on unit label dia-  
gram and in Fig. 6. Unit must be grounded.  
TXV — Thermal Expansion Valve  
Fig. 4 — Location of Sight Glass(es)  
and Filter Drier(s)  
Affix crankcase heater warning sticker to unit disconnect  
switch.  
CONTROL CIRCUIT WIRING — Control voltage is 24 v.  
See Fig. 7 and unit label diagram for field-supplied wiring  
details. Route control wires through opening in unit end panel  
to connection in unit control box.  
INSTALL LIQUID LINE SOLENOID VALVE — SOLE-  
NOID DROP — It is recommended that a solenoid valve be  
placed in the main liquid line (see Fig. 4) between condens-  
ing unit (38AE/AKS) and fan coil (40RR, 40RE). (A liquid  
line solenoid valve is required when the liquid line length  
exceeds 100 ft [30.5 m] or when the condensing unit is con-  
nected to the chiller barrel in a built-up chiller system.) This  
valve prevents refrigerant migration (which causes oil dilu-  
tion) to the compressor during the off cycle at low outdoor  
ambient temperatures. The solenoid should be wired in par-  
allel with the compressor contactor coil. This means of elec-  
trical control is referred to as solenoid drop control.  
INSTALL LIQUID LINE SOLENOID VALVE (OPTIONAL)  
— CAPACITY CONTROL — If 2-step cooling is desired,  
place a solenoid valve in the location shown in Fig. 4.  
MAKE PIPING CONNECTIONS — Do not remove run-  
around loop from suction and liquid line stubs in the com-  
pressor compartment until piping connections are ready to  
be made. Pass nitrogen or other inert gas through piping while  
brazing to prevent formation of copper oxide.  
Install field-supplied thermostatic expansion valve(s) in in-  
door section. If 2 thermostatic expansion valves are installed  
for 2-step cooling, install field-supplied liquid line solenoid  
valve ahead of the second expansion valve.  
PROVIDE SAFETY RELIEF — A fusible plug is located  
on the compressor crankcase or in the liquid line (Fig. 5).  
Do not cap this plug. If local code requires additional safety  
devices, install them as directed.  
LEGEND  
EQUIP GND — Equipment Ground  
NEC  
National Electrical Code  
Factory Wiring  
Field Wiring  
Fig. 6 — Main Power Supply Wiring  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
LEGEND  
C
Compressor Contactor  
Heating Device  
Indoor-Fan Contactor  
Liquid Line Solenoid Valve  
R
Relay  
Factory Wiring  
Field Wiring  
HD  
IFC  
LLSV  
NOTES:  
1. Combination LLSV plus IFC va should not exceed 30 va.  
2. Do not exceed 5 va (24 vac) per coil.  
3. If va values shown in Notes 1 and 2 must be exceeded, use  
accessory relay transformer package 38AE900001.  
Fig. 7 — Remote Thermostat Wiring  
Table 5A — Electrical Data (3 Ph/60 Hz)  
UNIT  
COMPR  
FAN MOTORS (Single Phase)  
FLA (ea)  
Volts  
UNIT  
MOCP  
(Fuse)  
Total  
Fan No.  
Model  
Supplied*  
MCA  
ICF  
RLA  
LRA  
kW  
Fans  
Nameplate  
Min  
Max  
1
2
501  
201  
601  
101  
208-230  
380  
187  
342  
414  
518  
253  
418  
528  
660  
62.5  
35.0  
29.1  
22.8  
178  
101  
81  
100  
50  
43.6  
24.0  
20.0  
15.7  
170  
93  
4.3  
4.3  
2.3  
1.8  
3.7  
3.7  
1.9  
1.8  
38AE012  
38AE014  
38AE016  
38AKS024  
2
1.41  
1.41  
1.41  
1.41  
460  
40  
77  
575  
67  
35  
62  
501  
201  
601  
101  
208-230  
380  
460  
575  
187  
342  
414  
518  
253  
418  
528  
660  
69.3  
38.0  
31.7  
25.6  
199  
112  
84  
100  
60  
50  
40  
49.3  
26.5  
22.1  
17.9  
191  
104  
80  
4.3  
4.3  
2.3  
1.8  
3.7  
3.7  
1.9  
1.8  
2
2
2
73  
69  
501  
201  
601  
101  
208-230  
380  
460  
575  
187  
342  
414  
518  
253  
418  
528  
660  
87.5  
49.3  
40.7  
33.0  
274  
153  
124  
100  
125  
80  
60  
50  
63.6  
36.0  
29.3  
23.8  
266  
145  
120  
96  
4.3  
4.3  
2.3  
1.8  
3.7  
3.7  
1.9  
1.8  
501  
201  
601  
101  
208-230  
380  
460  
575  
187  
342  
414  
518  
254  
418  
508  
632  
93.4  
49.7  
48.1  
40.1  
353  
199  
177  
124  
150  
80  
80  
60  
67.9  
34.6  
34.7  
28.8  
345  
191  
173  
120  
4.3  
4.3  
2.3  
1.8  
3.7  
3.7  
1.9  
1.8  
Table 5B — Electrical Data (3 Ph/50 Hz)  
UNIT  
COMPR  
FAN MOTORS 230 v (Single Phase)  
FLA (ea)  
Volts  
UNIT  
MOCP  
(Fuse)  
Total  
Fan No.  
Model  
Supplied*  
MCA  
ICF  
RLA  
LRA  
kW  
Fans  
Nameplate  
Min  
Max  
1
2
803  
903  
230  
400  
198  
342  
264  
457  
47.5  
31.4  
134  
80  
75  
50  
32.9  
20.0  
128  
74  
38AE012  
38AE014  
38AE016  
2
2
2
2.9  
3.5  
1.20  
1.20  
1.20  
803  
903  
230  
400  
198  
342  
264  
457  
51.0  
34.0  
149  
89  
75  
50  
35.7  
22.1  
143  
83  
2.9  
2.9  
3.5  
3.5  
803  
903  
230  
400  
198  
342  
264  
457  
66.9  
43.0  
206  
121  
100  
60  
47.9  
29.3  
200  
115  
803  
303  
903  
230  
346  
400  
198  
311  
342  
254  
380  
440  
91.8  
51.5  
50.2  
213  
121  
179  
150  
80  
80  
67.9  
33.3  
34.6  
207  
115  
173  
38AKS024  
2
2.9  
3.5  
1.20  
LEGEND  
FLA  
ICF  
Full Load Amps (Fan Motors)  
Maximum Instantaneous Current Flow during start-up (LRA of compressor plus total FLA of fan motors)  
Total Fan Motor Input (kilowatts)  
kW  
LRA  
MCA  
Locked Rotor Amps  
Minimum Circuit Amps per NEC (U.S.A.), Section 430-24  
MOCP — Maximum Overcurrent Protection (amps)  
RLA  
Rated Load Amps (Compressor)  
*Units are suitable for use on electrical systems where voltage supplied to the unit terminals is not below or above  
the listed limits.  
NOTES:  
1. The MCA and MOCP values are calculated in accordance with the National Electrical Code (NEC) article 440  
(U.S.A. standard).  
2. Motor RLA and LRA values are established in accordance with Underwriters’ Laboratories (UL) Standard 1995  
(U.S.A. standard).  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
PRE-START-UP  
START-UP  
Evacuate and Dehydrate the entire refrigerant sys-  
tem by either of the methods described in Carrier Standard  
Service Techniques Manual, Chapter 1.  
To Start Unit — Set thermostat set point below the space  
temperature. After starting unit, there is a delay of at least 3  
seconds before compressor starts.  
Leak Test the entire refrigerant system by the pres-  
sure method described in Carrier Standard Service Tech-  
niques Manual, Chapter 1. Use R-22 at approximately  
25 psig (172.4 kPa) backed up with an inert gas to a total  
pressure not to exceed 245 psig (1689 kPa).  
Oil Charge (see Tables 1A-1D) —Allow unit to run for  
about 20 minutes. Stop unit and check compressor oil level  
at sight glass. Add oil if necessary to bring oil to the correct  
level shown in Fig. 8. Use only Carrier-approved compres-  
sor oil. Approved oils are:  
Witco Chemical Corp. . . . . . . . . . . . . . . . . Suniso 3GS  
Texaco, Inc. . . . . . . . . . . . . . . . . . . . . . . . . . . . WF32  
Petroleum Specialties Co. . . . . . . . . . . . . . . . Cryol 150  
Do not reuse drained oil or use any oil that has been ex-  
posed to atmosphere. Procedures for adding or removing oil  
are given in Carrier Standard Service Techniques Manual,  
Chapter 1, Refrigerants.  
Turn on Crankcase Heaters for 24 hours before start-  
ing the unit to be sure all the refrigerant is out of the oil. To  
energize the crankcase heaters, proceed as follows.  
1. Set the space thermostat set point above the space tem-  
perature so there is no demand for cooling.  
2. Close the field disconnect.  
3. Turn the fan circuit breaker on. Leave the compressor cir-  
cuit breakers off. The crankcase heaters are now  
energized.  
If oil is added, run unit for additional 10 minutes. Stop  
unit and check oil level. If level is still low, add oil only after  
determining that piping system is designed for proper oil re-  
turn and that the system is not leaking oil.  
Add Preliminary Charge to the refrigerant system ac-  
cordingly to Carrier Standard Service Techniques Manual,  
Chapter 1. By the liquid charging method and charging by  
weight procedure, charge the units with approximately the  
amounts of R-22 refrigerant shown in Table 6.  
Table 6 — Charging Data (R-22)  
REFRIGERANT CHARGE - lb (kg)  
CONDENSING  
TEMP  
Required Charge  
Above Clear  
Outdoor Unit  
Total Charge  
(Approx)  
UNIT  
38AKS024  
(06E COMPRESSOR)  
38AE012,014,016  
(06D COMPRESSOR)  
DURING  
CHARGING - F (C)  
Sight Glass  
38AE012  
38AE014  
38AE016  
38AKS024  
3.0 (1.4)  
4.8 (2.2)  
3.4 (1.5)  
3.4 (1.5)  
22 (10)  
23 (10.5)  
23 (10.5)  
28 (12.7)  
125 (51.7)  
123 (50.6)  
130 (54.4)  
131 (54.8)  
Fig. 8 — Operating Oil Levels  
Refrigerant Charge — Actual start-up should be done  
only under supervision of a qualified refrigeration me-  
chanic. Refer to charging charts.  
Before Starting Unit ensure the following:  
See Fig. 9-11 for the particular unit being charged. Mea-  
sure pressure at the liquid line service valve, being sure a  
Schrader depressor is used if required. Also, measure liquid  
line temperature as close to the liquid service valve as pos-  
sible. Add or reduce charge until the pressure and tempera-  
ture conditions of the charging charge curve are met. If liq-  
uid pressure and temperature point falls above curve, add  
charge. If liquid pressure and temperature point falls below  
curve, reduce the charge until the conditions match the curve.  
1. Compressor oil level must be at least within sight in  
the compressor sight glass. Add oil if necessary (see  
Tables 1A-1D and Oil Charge section).  
2. Compressor holddown bolts must be snug, but not tight.  
Refer to Compressor Mounting section and tag on com-  
pressor foot.  
3. All internal wiring connections must be tight; all barriers  
and covers must be in place.  
4. Electrical power source must agree with unit nameplate  
rating.  
5. All service valves must be open.  
6. Crankcase heater must be firmly locked into the com-  
pressor crankcase.  
Never charge liquid into the low-pressure side of sys-  
tem. Do not overcharge. During charging or removal of  
refrigerant, be sure indoor fan system is operating.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Check Operation — Verify operation of all safety con-  
trols. Replace all service panels. Be sure that control panel  
cover is closed tightly.  
Head Pressure Control — Fan cycling is a standard  
feature. The no. 2 fan cycles in response to changes in liquid  
pressure. The switch cycles the fan off at 126 ± 4 psig (869  
± 28 kPa) as pressure decreases, and cycles it back on at 257  
(+5, −0) psig (1772 [+103, −0] kPa).  
OPERATING SEQUENCE  
Cooling — When the first stage (TC1) of the cooling ther-  
mostat closes, the timer starts. After approximately 3 sec-  
onds, the timer activates the compressor and fan motor no.  
1 contactor. When the liquid pressure builds to approxi-  
mately 257 psig (1772 kPa), fan motor no. 2 is energized.  
On demand for additional cooling capacity, the second stage  
(TC2) of the cooling thermostat closes, energizing a field-  
supplied liquid line solenoid (LLS) valve, which opens. This  
increases the suction pressure, causing the compressor to op-  
erate at higher capacity.  
When fan switch is set at AUTO, the indoor-air fan cycles  
with the compressor. When the switch is set at CONT, the  
indoor-air fan runs continuously.  
At shutdown, the Time GuardII timer prevents the com-  
pressor from restarting for approximately 5 minutes.  
When installed, a field-supplied solenoid valve (wired in  
parallel with the compressor contactor coil), shuts off the liq-  
uid line to prevent refrigerant migration back to the com-  
pressor during the off cycle.  
Heating — The heating thermostat (TH) energizes a field-  
supplied relay which operates heating controls and ener-  
gizes the indoor-fan relay. When the fan switch is set at AUTO,  
the indoor-air fan cycles with the heating control. The indoor-  
air fan runs continuously when the fan switch is set at CONT.  
Fig. 12 — Compressor Capacity Control Unloader  
Fan Cycling — Head pressure control is accomplished  
by cycling the fans. The no. 2 fan responds to liquid line  
pressure, cycling on at approximately 257 psig (1772 kPa)  
and off at approximately 126 psig (869 kPa).  
Time Guard II Circuit — Prevents short-cycling by pro-  
viding a delay of approximately 5 minutes before restarting  
compressor after shutdown from safety device action.  
On start-up, the Time Guard II timer causes a delay of  
approximately 3 seconds after thermostat closes.  
On compressor shutdown, the timer recycles for approxi-  
mately 5 minutes. During this time, the compressor cannot  
restart.  
Winter Start Control (If Installed) — When the com-  
pressor starts, the control’s bypass timer contacts close for  
150 seconds, thereby bypassing the low-pressure switch dur-  
ing start-up. After 150 seconds, the bypass timer contacts  
open and the low-pressure switch is restored to the safety  
circuit.  
Refer to Fig. 13 and to label diagram on unit.  
SERVICE  
Capacity Control — A suction pressure-actuated un-  
loader controls 2 cylinders and provides capacity control. Un-  
loaders are factory set (see Tables 1A-1D), but can be field  
adjusted as described in the 2 following sections.  
Fig. 13 — Timer Sequence Chart  
CONTROL SET POINT (cylinder load point) is adjustable  
from 0 to 85 psig (586 kPa). To adjust, turn control set point  
adjustment nut (Fig. 12) clockwise to its bottom stop. In this  
position, set point is 85 psig (586 kPa). Next, turn adjust-  
ment counterclockwise to desired control set point. Every  
full turn counterclockwise decreases set point by  
7.5 psig (51.7 kPa).  
Winter-Start Control (If Required) — Install Ac-  
cessory Package 38AE900021.  
Crankcase Heater — The heater prevents refrigerant  
migration and compressor oil dilution during shutdown when-  
ever compressor is not operating. It is wired into the control  
circuit, and cycles with the compressor; the heater is off when  
compressor is running, and on when compressor is off.  
Both compressor service valves must be closed whenever  
the crankcase heater is deenergized for more than 6 hours.  
The crankcase heater is operable as long as the control cir-  
cuit is energized.  
PRESSURE DIFFERENTIAL (difference between cylinder  
load and unload points) is adjustable from 6 to 22 psig (41.4  
to 152 kPa). To adjust, turn pressure differential adjustment  
screw (Fig. 12) counterclockwise to its back stop position.  
In this position, differential is 6 psig (41.4 kPa). Next, turn  
adjustment clockwise to desired pressure differential setting.  
Every full turn clockwise increases differential by 1.5 psig  
(10.3 kPa).  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(38AE014,016, 38AKS024) and restrict outdoor airflow. Use  
a flashlight to determine if dirt or debris has collected be-  
tween coil sections. Clean coil as follows:  
Outdoor Fans — Each fan is supported by a formed-  
wire mount bolted to the fan deck and covered with a wire  
guard. The exposed end of the motor shaft is covered with  
a rubber boot. In case a fan motor must be repaired or re-  
placed, be sure the rubber boot is put back on when the fan  
is reinstalled and be sure the fan guard is in place before  
starting the unit. Figure 14 shows the proper position of the  
mounted fan. Fan motors have permanently lubricated  
bearings.  
1. Turn off unit power.  
2. Remove screws holding rear corner posts and top  
cover in place. Pivot top cover up 12 to 18 in. (305 to  
457 mm) and support with a rigid support. See Fig. 15.  
3. Remove clips securing tube sheets together at the return  
bend end of the coil. Carefully spread the ends of the coil  
rows apart by moving the outer sections. See Fig. 16.  
4. Using a water hose, or other suitable equipment, flush down  
between the sections of coil to remove dirt and debris.  
5. Clean the remaining surfaces in the normal manner.  
6. Reposition outer coil sections.  
7. Reinstall clips which secure tube sheets.  
8. Replace top cover and rear corner posts.  
38AE012,014,016  
38AKS024  
Fig. 14 — Outdoor Fan  
Lubrication  
Fig. 15 — Pivot and Support Top Cover  
FAN MOTORS have sealed bearings. No provisions are made  
for lubrication.  
COMPRESSOR has its own oil supply. Loss of oil due to a  
leak in the system should be the only reason for adding oil  
after the system has been in operation. See Oil Charge  
section.  
Cleaning Coils — The coils can be cleaned with a vacuum  
cleaner, washed out with water, blown out with low-pressure  
compressed air, or brushed (do not use wire brush). Fan mo-  
tors are drip-proof but not waterproof.  
Clean outdoor coil annually or as required by location or  
outdoor air conditions. Inspect coil monthly, and clean as  
required. Fins are not continuous through coil sections; dirt  
and debris may pass through first section, become trapped  
between the 2 rows of fins (38AE012) or 3 rows of fins  
Fig. 16 — Coil Cleaning (Typical)  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLESHOOTING  
PROBLEM  
COMPRESSOR DOES NOT RUN  
Contactor Open  
SOLUTION  
1. Power off.  
1. Restore power.  
2. Fuses blown in field power circuit.  
3. No control power.  
2. After finding cause and correcting, replace with correct size fuse.  
3. Check secondary fuse(s); replace with correct type and size.  
Replace transformer if primary windings receiving power.  
4. Thermostat circuit open.  
4. Check thermostat setting.  
5. Time GuardII device not operating.  
6. Compressor circuit breaker tripped.  
5. Check Time Guard II devices.  
6. Check for excessive compressor current draw. Reset breaker;  
replace if defective.  
7. Safety device lock-out circuit active.  
8. Low-pressure switch open.  
7. Reset lock-out circuit at thermostat or circuit breaker.  
8. Check for refrigerant undercharge, obstruction of indoor airflow, or  
whether compressor suction shutoff valve is fully open. Make sure liquid  
line solenoid valve(s) is open.  
9. High-pressure switch open.  
9. Check for refrigerant overcharge, obstruction of outdoor airflow, air in  
system, or whether compressor discharge valve is fully open. Be sure  
outdoor fans are operating correctly.  
10. Compressor overtemperature switch open.  
11. Loose electrical connections.  
12. Compressor stuck.  
10. Check for open condition. Allow for reset. Replace if defective.  
11. Tighten all connections.  
12. See compressor service literature.  
Contactor Closed  
1. Compressor leads loose.  
1. Check connections.  
2. Motor windings open.  
2. See compressor service literature.  
3. Single phasing.  
3. Check for blown fuse. Check for loose connection at compressor terminal.  
COMPRESSOR STOPS ON HIGH-PRESSURE SWITCH  
Outdoor Fan On  
1. High-pressure switch faulty.  
2. Reversed fan rotation.  
3. Airflow restricted.  
1. Replace switch.  
2. Confirm rotation, correct if necessary.  
3. Remove obstruction.  
4. Air recirculating.  
4. Clear airflow area.  
5. Noncondensables in system.  
6. Refrigerant overcharge.  
7. Line voltage incorrect.  
8. Refrigerant system restrictions.  
5. Purge and recharge as required.  
6. Purge as required.  
7. Consult power company.  
8. Check or replace filter drier, expansion valve, etc. Check that compressor  
discharge service valve is fully open.  
Outdoor Fan Off  
1. Fan slips on shaft.  
1. Tighten fan hub setscrews.  
2. Check power and capacitor.  
3. Replace bearings.  
2. Motor not running.  
3. Motor bearings stuck.  
4. Motor overload open.  
4. Check overload rating. Check for fan blade obstruction.  
5. Replace motor.  
5. Motor burned out.  
COMPRESSOR CYCLES ON LOW-PRESSURE SWITCH  
Indoor-Air Fan Running  
1. Compressor suction service valve partially  
closed.  
1. Open valve fully.  
2. Liquid line solenoid valve(s) fails to open.  
2. Check liquid line solenoid valve(s) for proper operation. Replace if  
necessary.  
3. Filter drier plugged.  
3. Replace filter drier.  
4. Expansion valve power head defective.  
5. Low refrigerant charge.  
4. Replace power head.  
5. Add charge. Check low-pressure switch setting.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLESHOOTING (cont)  
PROBLEM  
SOLUTION  
COMPRESSOR CYCLES ON LOW-PRESSURE SWITCH (cont)  
Airflow Restricted  
1. Coil iced up.  
2. Coil dirty.  
1. Check refrigerant charge.  
2. Clean coil fins.  
3. Air filters dirty.  
4. Dampers closed.  
3. Clean or replace filters.  
4. Check damper operation and position.  
Indoor-Air Fan Stopped  
1. Electrical connections loose.  
2. Fan relay defective.  
1. Tighten all connections.  
2. Replace relay.  
3. Motor overload open.  
3. Power supply.  
4. Motor defective.  
4. Replace motor.  
5. Fan belt broken or slipping.  
COMPRESSOR RUNNING BUT COOLING INSUFFICIENT  
5. Replace or tighten belt.  
Suction Pressure Low  
1. Refrigerant charge low.  
2. Head pressure low.  
1. Add refrigerant.  
2. Check refrigerant charge.  
Check outdoor-air fan thermostat settings.  
3. Air filters dirty.  
3. Clean or replace filters.  
4. Replace power head.  
5. Check low-pressure setting.  
6. Remove obstruction.  
4. Expansion valve power head defective.  
5. Indoor coil partially iced.  
6. Indoor airflow restricted.  
Suction Pressure High  
1. Unloaders not functioning.  
1. Check unloader adjustments.  
Check unloader setting.  
2. Compressor valve defective.  
3. Heat load excessive.  
2. See compressor service literature.  
3. Check for open doors or windows in vicinity of fan coil.  
UNIT OPERATES TOO LONG OR CONTINUOUSLY  
1. Low refrigerant charge.  
2. Control contacts fused.  
1. Add refrigerant.  
2. Replace control.  
3. Air in system.  
3. Purge and evacuate system.  
4. Clean or replace.  
4. Partially plugged expansion valve or filter drier.  
SYSTEM IS NOISY  
1. Piping vibration.  
1. Support piping as required.  
2. Compressor noisy.  
2. Check valve plates for valve noise. Replace compressor if  
bearings are worn.  
COMPRESSOR LOSES OIL  
1. Leak in system.  
1. Repair leak.  
2. Crankcase heaters not energized during shutdown.  
2. Check wiring and relays. Check heater and replace if  
defective.  
3. Improper interconnecting piping design.  
FROSTED SUCTION LINE  
3. Check piping for oil return. Replace if necessary.  
Expansion valve admitting excess refrigerant.  
HOT LIQUID LINE  
Adjust expansion valve.  
1. Shortage of refrigerant due to leak.  
2. Expansion valve opens too wide.  
FROSTED LIQUID LINE  
1. Repair leak and recharge.  
2. Adjust expansion valve.  
1. Restricted filter drier.  
1. Remove restriction or replace.  
2. Replace valve.  
2. Liquid line solenoid valve partially closed.  
COMPRESSOR WILL NOT UNLOAD  
1. Defective unloader.  
1. Replace unloader.  
2. Replace valve.  
3. Rewire correctly.  
4. Replace spring.  
2. Defective capacity control solenoid valve (if used).  
3. Miswired capacity control liquid line solenoid (if used).  
4. Weak, broken, or wrong valve body spring.  
COMPRESSOR WILL NOT LOAD  
1. Miswired capacity control liquid line solenoid (if used).  
2. Defective capacity control solenoid valve (if used).  
3. Plugged strainer (high side).  
1. Rewire correctly.  
2. Replace valve.  
3. Clean or replace strainer.  
4. Clean or replace the necessary parts.  
4. Stuck or damaged unloader piston or piston ring(s).  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PACKAGED SERVICE TRAINING  
Our packaged service training programs provide an excellent way to increase your knowledge of the  
equipment discussed in this manual. Product programs cover:  
• Unit Familiarization  
• Installation Overview  
• Maintenance  
• Operating Sequence  
A large selection of product, theory, and skills programs is available. All programs include a video  
cassette and/or slides and a companion booklet. Use these for self teaching or to conduct full training  
sessions.  
For a free Service Training Material Catalog (STM), call 1-800-962-9212. Ordering instructions are  
included.  
Copyright 1994 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book 1 PC 111 Catalog No. 563-746 Printed in U.S.A. Form 38A-4SI Pg 18 4-94 Replaces: 38AE-17SI  
Tab 3a 2a  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
START-UP CHECKLIST  
A. Preliminary Information  
OUTDOOR: MODEL NO.  
INDOOR: AIR HANDLER MANUFACTURER  
MODEL NO.  
SERIAL NO.  
SERIAL NO.  
ADDITIONAL ACCESSORIES  
B. Pre-Start-Up  
OUTDOOR UNIT  
IS THERE ANY SHIPPING DAMAGE?  
IF SO, WHERE:  
(Y/N)  
(Y/N)  
WILL THIS DAMAGE PREVENT UNIT START-UP?  
(Y/N)  
CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT?  
HAS THE GROUND WIRE BEEN CONNECTED? (Y/N)  
HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY?  
ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY?  
(Y/N)  
(Y/N)  
HAVE COMPRESSOR HOLDDOWN BOLTS BEEN LOOSENED (Snubber washers are snug, but not tight)?  
(Y/N)  
CONTROLS  
ARE THERMOSTAT AND INDOOR FAN CONTROL WIRING  
CONNECTIONS MADE AND CHECKED?  
(Y/N)  
ARE ALL WIRING TERMINALS (including main power supply) TIGHT?  
HAS CRANKCASE HEATER BEEN ENERGIZED FOR 24 HOURS?  
(Y/N)  
(Y/N)  
INDOOR UNIT  
HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE?  
ARE PROPER AIR FILTERS IN PLACE? (Y/N)  
HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT?  
(Y/N)  
(Y/N)  
DO THE FAN BELTS HAVE PROPER TENSION?  
(Y/N)  
HAS CORRECT FAN ROTATION BEEN CONFIRMED?  
(Y/N)  
PIPING  
ARE LIQUID LINE SOLENOID VALVES LOCATED AT THE EVAPORATOR COILS AS REQUIRED?  
(Y/N)  
HAVE LEAK CHECKS BEEN MADE AT COMPRESSOR, CONDENSER, EVAPORATOR(S),  
TXVs (Thermostatic Expansion Valves), SOLENOID VALVES, FILTER DRIERS, AND FUSIBLE PLUGS  
WITH A LEAK DETECTOR?  
(Y/N)  
LOCATE, REPAIR, AND REPORT ANY LEAKS.  
HAVE ALL COMPRESSOR SERVICE VALVES BEEN FULLY OPENED (BACKSEATED)?  
(Y/N)  
HAVE LIQUID LINE SERVICE VALVES BEEN OPENED?  
(Y/N)  
IS THE OIL LEVEL IN EACH COMPRESSOR CRANKCASE VISIBLE IN THE COMPRESSOR SIGHT GLASSES?  
(Y/N)  
CHECK VOLTAGE IMBALANCE  
LINE-TO-LINE VOLTS:  
(AB + AC + BC)/3 = AVERAGE VOLTAGE =  
MAXIMUM DEVIATION FROM AVERAGE VOLTAGE =  
AB  
V
AC  
V
BC  
V
V
V
VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) =  
%
IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!  
CALL LOCAL POWER COMPANY FOR ASSISTANCE.  
CL-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C. Start-Up  
CHECK EVAPORATOR FAN SPEED AND RECORD.  
CHECK CONDENSER FAN SPEED AND RECORD.  
AFTER AT LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:  
OIL PRESSURE  
SUCTION PRESSURE  
SUCTION LINE TEMP  
DISCHARGE PRESSURE  
DISCHARGE LINE TEMP  
ENTERING CONDENSER AIR TEMP  
LEAVING CONDENSER AIR TEMP  
EVAP ENTERING-AIR DB (dry bulb) TEMP  
EVAP ENTERING AIR WB (wet bulb) TEMP  
EVAP LEAVING AIR DB TEMP  
EVAP LEAVING AIR WB TEMP  
COMPRESSOR AMPS (L1/L2/L3)  
/
/
CHECK THE COMPRESSOR OIL LEVEL SIGHT GLASSES; ARE THE SIGHT GLASSES SHOWING  
OIL LEVEL IN VIEW? (Y/N)  
NOTES:  
Copyright 1994 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book 1 PC 111 Catalog No. 563-746 Printed in U.S.A. Form 38A-4SI Pg CL-2 4-94 Replaces: 38AE-17SI  
Tab 3a 2a  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  

Black Box Switch KV0416A R2 User Manual
Black Decker Drill 90504614 User Manual
Black Decker Home Safety Product BDCF12 User Manual
Black Decker Power Screwdriver LI3100 User Manual
Blanco Indoor Furnishings 515 546 User Manual
Brother Sewing Machine BM 3500 User Manual
Brunton Coffeemaker 81 100730 User Manual
Canon Digital Camera 30D1785 User Manual
Casablanca Fan Company Fan RAS 4 13 04 User Manual
Ceiva Digital Photo Frame LF 2003 User Manual